Black Box Server EME144A R2 User Manual

EME144A-R2  
ServSensor V4E Lite  
Use this intelligent environmental monitoring  
device to identify problems before they disrupt  
your equipment.  
Features an embedded Web server and Linux operating system.  
Order toll-free in the U.S.: Call 877-877-BBOX (outside U.S. call 724-746-5500) •  
Customer  
Support  
Information  
FREE technical support 24 hours a day, 7 days a week: Call 724-746-5500 or fax 724-746-0746 •  
Mailing address: Black Box Corporation, 1000 Park Drive, Lawrence, PA 15055-1018 •  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FCC and IC RFI Statements  
Federal Communications Commission and Industry Canada Radio Frequency Interference  
Statements  
This equipment generates, uses, and can radiate radio-frequency energy, and if not installed and used properly, that is, in strict  
accordance with the manufacturer’s instructions, may cause interference to radio communication. It has been tested and found to  
comply with the limits for a Class A computing device in accordance with the specifications in Subpart B of Part 15 of FCC rules,  
which are designed to provide reasonable protection against such interference when the equipment is operated in a commercial  
environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user at his own  
expense will be required to take whatever measures may be necessary to correct the interference.  
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to  
operate the equipment.  
This digital apparatus does not exceed the Class A limits for radio noise emission from digital apparatus set out in the Radio  
Interference Regulation of Industry Canada.  
Le présent appareil numérique n’émet pas de bruits radioélectriques dépassant les limites applicables aux appareils numériques de  
la classe A prescrites dans le Règlement sur le brouillage radioélectrique publié par Industrie Canada.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOM Statement  
Instrucciones de Seguridad  
(Normas Oficiales Mexicanas Electrical Safety Statement)  
1. Todas las instrucciones de seguridad y operación deberán ser leídas antes de que el aparato eléctrico sea operado.  
2. Las instrucciones de seguridad y operación deberán ser guardadas para referencia futura.  
3. Todas las advertencias en el aparato eléctrico y en sus instrucciones de operación deben ser respetadas.  
4. Todas las instrucciones de operación y uso deben ser seguidas.  
5. El aparato eléctrico no deberá ser usado cerca del agua—por ejemplo, cerca de la tina de baño, lavabo, sótano mojado o cerca  
de una alberca, etc.  
6. El aparato eléctrico debe ser usado únicamente con carritos o pedestales que sean recomendados por el fabricante.  
7. El aparato eléctrico debe ser montado a la pared o al techo sólo como sea recomendado por el fabricante.  
8. Servicio—El usuario no debe intentar dar servicio al equipo eléctrico más allá a lo descrito en las instrucciones de operación.  
Todo otro servicio deberá ser referido a personal de servicio calificado.  
9. El aparato eléctrico debe ser situado de tal manera que su posición no interfiera su uso. La colocación del aparato eléctrico  
sobre una cama, sofá, alfombra o superficie similar puede bloquea la ventilación, no se debe colocar en libreros o gabinetes  
que impidan el flujo de aire por los orificios de ventilación.  
10. El equipo eléctrico deber ser situado fuera del alcance de fuentes de calor como radiadores, registros de calor, estufas u otros  
aparatos (incluyendo amplificadores) que producen calor.  
11. El aparato eléctrico deberá ser connectado a una fuente de poder sólo del tipo descrito en el instructivo de operación, o como  
se indique en el aparato.  
12. Precaución debe ser tomada de tal manera que la tierra fisica y la polarización del equipo no sea eliminada.  
13. Los cables de la fuente de poder deben ser guiados de tal manera que no sean pisados ni pellizcados por objetos colocados  
sobre o contra ellos, poniendo particular atención a los contactos y receptáculos donde salen del aparato.  
14. El equipo eléctrico debe ser limpiado únicamente de acuerdo a las recomendaciones del fabricante.  
15. En caso de existir, una antena externa deberá ser localizada lejos de las lineas de energia.  
16. El cable de corriente deberá ser desconectado del cuando el equipo no sea usado por un largo periodo de tiempo.  
17. Cuidado debe ser tomado de tal manera que objectos liquidos no sean derramados sobre la cubierta u orificios de ventilación.  
18. Servicio por personal calificado deberá ser provisto cuando:  
A: El cable de poder o el contacto ha sido dañado; u  
B: Objectos han caído o líquido ha sido derramado dentro del aparato; o  
C: El aparato ha sido expuesto a la lluvia; o  
D: El aparato parece no operar normalmente o muestra un cambio en su desempeño; o  
E: El aparato ha sido tirado o su cubierta ha sido dañada.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Table of Contents  
1. Specifications.......................................................................................................................................................................................... 6  
2. Overview ............................................................................................................................................................................................ 7  
2.1 Introduction.................................................................................................................................................................................... 7  
2.2 What‘s Included.............................................................................................................................................................................. 7  
2.3 Hardware Description ..................................................................................................................................................................... 8  
2.3.1 Front Panel........................................................................................................................................................................... 8  
2.3.2 Back Panel............................................................................................................................................................................ 9  
3. Installation ...........................................................................................................................................................................................10  
3.1 Setting the IP Address....................................................................................................................................................................10  
3.2 Testing the New IP Address with the “Ping” Command .................................................................................................................12  
3.3 Firmware Upgrade.........................................................................................................................................................................14  
3.4 Multiusers and Groups Setup.........................................................................................................................................................17  
3.4.1 Group Setup........................................................................................................................................................................17  
3.4.2 User Setup ..........................................................................................................................................................................19  
3.5 Services and Security .....................................................................................................................................................................21  
3.5.1 Active Services Application (Disabling).................................................................................................................................21  
3.5.2 Closing or Changing Ports Disabling HTTP and Enabling HTTPS.......................................................................................... 22  
3.5.3 The SNMPv3 SSL Security Feature....................................................................................................................................... 23  
3.5.4 Active Security ................................................................................................................................................................... 24  
3.5.5 The NAC or Network Access Control Security Feature ........................................................................................................ 25  
3.6 Setting Up a Sensor...................................................................................................................................................................... 25  
3.6.1 Notification Thresholds....................................................................................................................................................... 27  
3.6.2 Advanced Sensor Settings .................................................................................................................................................. 29  
3.7 Using an Internal Mic as a Sound Detection Sensor....................................................................................................................... 37  
3.8 Expansion Ports ............................................................................................................................................................................ 40  
4. Notifications.......................................................................................................................................................................................... 43  
4.1 Adding a Notification.................................................................................................................................................................... 43  
4.2 SNMP Trap.................................................................................................................................................................................... 44  
4.3 E-mail .......................................................................................................................................................................................... 48  
4.4 SMS Notification........................................................................................................................................................................... 53  
5. Mapping  
.......................................................................................................................................................................................... 59  
5.1 Adding a Map .............................................................................................................................................................................. 59  
5.2 Monitoring via the Map Interface.................................................................................................................................................. 63  
6. Filters  
.......................................................................................................................................................................................... 64  
6.1 Sensor Filters ................................................................................................................................................................................ 64  
6.2 Syslog Filters................................................................................................................................................................................. 66  
7. Making the ServSensor Visible to the Internet ....................................................................................................................................... 69  
8. Frequently Asked Questions (FAQs)....................................................................................................................................................... 70  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 1: Specifications  
1. Specifications  
Audio — Sampling rate: 8 kHz  
Certifications — AdRem NetCrunch, Quest Software–Big Brother®, Castle Rock, HP® OpenView®, IBM® Tivoli®, LoriotPro,  
Logalot, MRTG®, SiteScope®, Somix®—WebNM® and Denika®, WhatsUp® Gold, Computer Associates Unicenter® TNG  
Components — Manufactured using highly integrated, low-power surface-mount technology to ensure long-term reliability  
Configuration — Via Web browser (HTTP/HTTPS)  
Expandable Modules — EME1X8: 8-port intelligent sensors module;  
EME1DC16: 16-port dry-contacts modules  
Mean Time Between Failures (MTBF) — 400,000 hours  
Memory — 128 MB SDRAM, 128 MB NVRAM  
Network Interface — (1) 10/100BASE-T Ethernet RJ-45  
Operating System — Embedded Linux  
Processor — iMX25 CPU  
Protocols Supported (Client) — DHCP, DNS, SMTP, (5) NTP, SNMP  
Connectors — Inputs: (8) RJ-45 for connecting sensors; (2) RJ-45 expansion ports; (1) USB Version 1.1 Type A; (1) 2.5" jack  
for analog audio; (1) RS-485 2-pin terminal box (used for Modbus®);  
Output: (1) 2.5" jack for analog audio; (1) 2.5" jack for microphone  
Temperature Tolerance — Operating: 32 to 131° F (0 to +55° C)  
Humidity — 20 to 80%, noncondensing  
Altitude — 0 to 9842 ft. (0 to 300 m)  
Indicators — (19) LEDs: (1) Power, (1) Link, (1) Activity, (8) Status, (8) On-line  
Power — Input: 100–240 VAC, 47-63 Hz external power supply;  
Output: 7.0–9 VDC, 3 amps;  
Consumption: 5.025 watts, 0.670 amps  
Size — 1.8"H x 8.5"W x 5.4"D (4.6 x 21.6 x 13.7 cm)  
Weight — 1.7 lb. (0.8 kg)  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 2: Overview  
2. Overview  
2.1 Introduction  
Used for environmental monitoring, the ServSensor V4E Lite identifies problems before they lead to business disruptions. This  
high-speed, accurate, intelligent monitoring device features a completely embedded host and Linux® operating system.  
2.2 What’s Included  
Your package should contain the following items. If anything is missing or damaged, contact Black Box Technical Support at  
724-746-5500.  
• (1) ServSensor V4E Lite unit  
• (1) 5-ft. crossover cable  
• (1) 5-ft. straight-pinned cable  
• (2) rackmounting brackets  
• (1) power adapter  
• (1) power cord  
• (1) temperature/humidity sensor (EME1TH2-005) with RJ-45 to RJ-45 cable  
• (4) terminal blocks (installed)  
• (1) CD-ROM containing this user’s manual and Help files  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 2: Overview  
2.3 Hardware Description  
Figure 2-1 illustrates the ServSensor’s front panel. Table 2-1 describes its components.  
2.3.1 Front Panel  
4
3
6
7
1
2
5
Figure 2-1. Front panel.  
Table 2-1. Front-panel components.  
Description  
Number  
Component  
1
Power LED  
When the unit is powered on, the power LED will be lit continuously. If the  
power LED is flashing, there is a problem with the CPU. Contact Technical  
Support at 724-746-5500 or [email protected].  
2
3
Link LED  
Mic  
The Link LED indicates network connectivity. It lights when a network is  
connected to the ServSensor V4E Lite.  
The mic is a small hole for access to the internal microphone. Use it as a  
sound sensor (or use an external mic).  
4
5
SD card slot  
Activity LED  
SD card (not included) installs here.  
The Activity LED flashes when network traffic is sent to or received by the  
ServSensor V4E Lite.  
6
Status/Online LEDs 1–8  
The Status/Online LEDs are numbered 1–8. They indicate the connectivity  
status of the sensors connected to each port. You can also use these LEDs to  
indicate system status during various operations.  
Additionally, the LEDs can indicate the progress of an upgrade. The red LEDs  
move from left to right to indicate activity, and all the green LEDs indicate  
overall progress of the upgrade. When all the red lights are off and the green  
are on, the upgrade/recovery process is complete.  
These lights also indicate if the unit is operating in safe mode. This is when  
the unit loads the operating system (OS) with a minimal set of drivers. If your  
device enters safe mode after rebooting, contact Black Box Technical Support  
at 724-746-5500 or [email protected].  
The unit may enter recovery mode if a firmware upgrade is incomplete. In this  
case, the unit displays a continuously lit row of red LEDs. If this happens,  
contact Black Box Technical Support at 724-746-5500 or [email protected].  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 2: Overview  
Table 2-1 (Continued) . Front panel components.  
Number  
Component  
Description  
7
Expansion ports E1–E2  
Use the two expansion ports numbered E1–E2 to connect the 8-port  
expansion module (EME1X8) and/or the 16 dry-contact expansion module  
(EME1DC16).  
2.3.2 Back Panel  
Figure 2-2 shows the ServSensor’s back panel. Table 2-2 describes its components.  
10 11 12 13  
14  
15  
16  
17  
8
9
Figure 2-2. Back panel.  
Table 2-2. Back panel components.  
Number  
Component  
Description  
8
(8) RJ-45 connectors  
Barrel connector  
Mic out connector  
Audio in  
Use these ports to connect Intelligent Sensors to the ServSensor V4E Lite.  
This is a 7.5V DC plug. Connect a 7.0–9.0-V, 2.5-A power supply (included).  
Connect an external microphone for voice modem applications.  
Connect an external microphone.  
9
10  
11  
12  
13  
Audio out  
Connect the output for external speakers.  
USB Type A port  
Use the USB 1.1 port to connect a USB GBarPRS/GSM compatible modem,  
a USB Wi-Fi dongle, or a USB Bluetooth® dongle.  
14  
15  
16  
17  
2-pin terminal block (RS-485 port) The ServSensor V4E Lite supports Modbus master or slave.  
RJ-45 10/100 network port  
Use this RJ-45 port to connect your ServSensor V4E Lite to the network.  
Press this button to reset the ServSensor V4E Lite.  
Reset  
EXT GND  
Use the EXT. GND connector to externally ground the unit.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
3. Installation  
3.1 Setting Up the IP Address  
The ServSensor V4E Lite is shipped with the default IP address of 192.168.0.100. Follow the steps listed below to change this IP  
address to fit your own network configuration.  
Before starting, make sure you have these items:  
• (1) RJ-45 male CAT5 crossover cable  
• (1) PC with Ethernet card or LAN socket  
• (1) Power socket for the unit to connect to  
To set up the IP address:  
1. Connect the ServSensor V4E Lite via its Ethernet port to your computer’s Ethernet port with a CAT5 crossover cable.  
2. Open a Web browser and type the default IP address (as in Figure 3-1), then press the Enter key.  
Figure 3-1. Google Web Browser screen.  
NOTE: In some cases, your computer might not be able to connect to this default IP address. In this situation, you will need to  
change the IP address of your PC. See the instructions above.  
3. After you press the Enter key in Step 2, Figure 3-2 appears. The default password for Admin is “public.” Change the password  
to make your unit secure.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
Figure 3-2. User Type/Password screen.  
4. Next, the home page will be displayed. It looks similar to the screen shown in Figure 3-3.  
Figure 3-3. Settings tab.  
5. Click on the “Settings” tab, then click on “Ethernet network” from the list on the left frame of the page. See Figure 3-4.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
Figure 3-4. Ethernet Network screen.  
To change the IP address of the ServSensor V4E Lite:  
1. Select Ethernet network.  
2. Input the new IP address.  
3. Click the “Save” button.  
3.2 Testing the New IP Address with the “Ping” Command  
Once you assign the new IP address, use the “ping” command to test the ServSensor V4E Lite. You can also use this command as  
a diagnostic tool to check whether your unit is connected to the network. See Figure 3-5.  
1. Click “Start.”  
2. Click “Run.”  
3. Type “ping (IP address that the user entered),” and press Enter. An example IP address (10.1.5.206) is shown in Figure 3-5.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
Figure 3-5. Ping Command screen.  
4. After you press the “Enter” key, an MS-DOS® prompt window showing the test results appears (see Figure 3-6). If you get a  
message saying “request timed out,” either the IP address is incorrect or a ServSensor V4E Lite is not connected to the  
network.  
Figure 3-6. MS-DOS window.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
3.3 Firmware Upgrade  
Make sure you are running the latest firmware. Please contact Black Box Technical Support at 724-746-5500 or  
[email protected] for the latest firmware.  
NOTE: This manual refers to the Default IP address, 192.168.0.100. Substitute this for your own IP address if you have changed  
the default IP address.  
This tutorial gives you the information you need to upgrade the firmware.  
To get to the tutorial’s starting point:  
• Log in as administrator.  
• Click the “Settings” tab.  
Figure 3-7. Settings tab.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
Figure 3-8. System Administrator, System Maintenance screen.  
1. Click “System Administrator” and then “System Maintenance.”  
2. Click “Upgrade.”  
3. The popup screen shown in Figure 3-9 appears.  
Figure 3-9. Reboot prompt.  
4. Click “OK.” The unit will reboot in Safe Mode. Then you will be redirected to the Safe Mode Web-based interface. This can  
take some time, so please be patient. The page will display the message shown in Figure 3-10 when rebooting.  
Figure 3-10. Firmware Upgrade Rebooting screen.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
5. After the ServSensor reboots, the page shown in Figure 3-11 appears. Click “Browse” and navigate to the firmware file  
you downloaded, then click “Upgrade.”  
Figure 3-11. Upgrade button.  
6. During the process, you will see the messages shown in Figure 3-12.  
Figure 3-12. Upgrade Status screen.  
7. The unit will then reboot. The process is complete when the LEDs are back to their “normal” status.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
3.4 Multi-users and Groups Setup  
3.4.1 Group Setup  
1. Log in to the ServSensor V4E Lite with the Administrator password. The default will be “public” if you have not changed this  
yet.  
2. Click on the Settings page, then System Adminstrator, then User & Group Management as shown in Figure 3-13.  
NOTE: The following screen diagrams may appear small and hard to read. Please use the zoom feature in your PDF reader  
program to increase the size of the page to better view these screen diagrams.  
Figure 3-13. Group Setup screen.  
3. Click on the “Go to Group Setup” link that will take you to the Groups page shown in Figure 3-14.  
Figure 3-14. Groups page.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
4. Click on the Add” button to add your groups as shown in Figure 3-14.  
Figure 3-15. User & Group Management screen.  
5. Enter your group name. For example, we have added a group called “System Guest” and entered our description.  
6. Check the objects with the Web interface that this group will be able to Modify and View. Then, click the “Finish” button to  
save your group. (See Figure 3-15.)  
Figure 3-16. System Guest group added.  
7. The new group “System Guest” has been added to our group list as shown in Figure 3-16.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
Figure 3-17. User & Group Management screen.  
8. If you want to modify your group settings, click on the group you want to modify. Then click on the “Properties” button as  
shown in Figure 3-17.  
3.4.2 User Setup  
1. Click on the “Users” tab and then click the “Add” button to add the new users to your groups as shown in Figure 3-18.  
Figure 3-18. User Setup screen.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
2. Enter your user details as shown in Figure 3-19. In our example, we have entered Bob Smith as your Guest into our “System  
Guest” group. We have also added the option so that this user cannot change his login password. After adding your users for  
each group, click the “Finish” button to save each user.  
Figure 3-19. Enter user details.  
3. The new user has been entered into our list of users.  
Figure 3-20. User list.  
4. To modify a user’s setting, click on the user to select it, then click the “Properities” button as shown in Figure 3-21.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
FIgure 3-21. Properties button.  
3.5 Services and Security  
3.5.1 Active Services Application (Disabling)  
Figure 3-22. Services and Security screen.  
You can enable or disable the Nagios, Secure Shell, and Telnet applications running on the unit to make it more secure.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
3.5.2 Closing or Changing Ports Disabling HTTP and Enabling HTTPS  
Figure 3-23. Active services.  
You can also close or change the ports used to access the unit’s Web interface, disable HTTP, and enable HTTPS only.  
The “s” at the conclusion of HTTPS stands for secure. The SSL/TLS connection type is used primarily for high-value sites or  
“pages,” to make it more likely to be unreadable to someone at the end points.  
The traffic between client and the ServSensor V4E Lite is not cached along the various units as it moves across the Internet, so it  
can’t be accessed by someone after the connection is terminated.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
3.5.3 The SNMPv3 SSL Security Feature  
Figure 3-24. Add Key screen.  
Use the SNMPv3 SSL (Secure Sockets Layer), which is the standard security technology for establishing the encrypted link betwen  
the ServSensor and the Web browser. The link ensures that all data passed between the ServSensor and the browser remains  
private and integral.  
SNMPv3 provides important security features:  
• Confidentiality—Encrypts packets to prevent snooping by an unauthorized source.  
• Integrity—Message integrity to ensure that a packet has not been tampered with in transmit.  
• Authentication—To verify that the message is from a valid source.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
Figure 3-25. Select SSL Key screen.  
3.5.4 Active Security  
In the active security section, you can enable users who are logged into the unit’s Web interface to Acknowledge” alarms, which  
is normally reserved only for the Administrator.  
When the unit boots up, it will announce the IP address that it has been configured with. As an added security feature, this  
announcement can be disabled so that the IP address remains unknown.  
Figure 3-26. Active Security screen.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
3.5.5 The NAC or Network Access Control Security Feature  
Figure 3-27. Network Access Control screen.  
The NAC or Network Access Control feature enables you to restrict access to the Web interface for only certain IP addresses, or  
deny access to the Web interface for only certain IP addresses.  
3.6 Setting Up a Sensor  
This section describes the basic setup of a sensor, using a Black Box temperature sensor as an example. If you require information  
1. Plug the sensor into one of the RJ-45 “intelligent sensor ports” on the ServSensor’s rear panel. In this example, we will use  
Port 1. See Figure 3-28.  
Figure 3-28. Intelligent sensor Port 1.  
2. Point your browser to the ServSensor’s IP address (the default is 192.168.0.100). Log in as the administrator using your  
administrator password (the default is “public”). You will then be taken to the summary page shown in Figure 3-29.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
Figure 3-29. Summary page.  
The temperature sensor should be listed, along with its current reading and status.  
This summary page enables you to quickly see which sensors are connected and their status, view the system log, and also view  
footage from any connected cameras. Next are some of the tools the Web-based interface provides for getting feedback from  
the sensors.  
3. Click on the temperature sensor’s name (indicated in Figure 3-29). This will bring you to Figure 3-30, the Sensors page.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
Figure 3-30. Sensors page.  
NOTE: Another way to access this page is to click on the “Sensors” tab at the top of the page.  
3.6.1 Notification Thresholds  
From this page, you can carry out various operations as indicated above. You can also view the current status (normal, low critical,  
high critical, etc). In Figure 3-30, the sensor indicates a temperature of 27° C and a status of Normal. If you click on the blue  
marker arrow next to the “Threshold adjustment” label (shown in Figure 3-30), you can drag this marker to re-configure the  
thresholds. After dragging the marker, click “Save.” In Figure 3-31, you can see that this marker has been moved to make a new  
threshold, and the sensor status has changed along with it.  
Figure 3-31. High critical status shown.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
If the marker is then dragged back above the current temperature reading, the status should return to a normal condition again.  
(See Figure 3-32.)  
NOTE: If this does not happen right away, press the browser’s refresh button.  
Figure 3-32. Normal status indicated.  
If you want to take a sensor offline, then click on the “Sensor Currently” button. This will place the sensor offline and you won’t  
have to physically unplug it. See Figure 3-33.  
Figure 3-33. Sensor Online/Offline screen.  
Your page will look similar to Figure 3-34 after you take the sensor offline.  
Figure 3-34. Sensor Offline screen.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
To bring a sensor back online, select the type from the drop-down menu and click “Save.” See Figure 3-35.  
Figure 3-35. Select Sensor Type screen.  
3.6.2 Advanced Sensor Settings  
Click on the Advanced Settings tab to get the options shown in Figure 3-36.  
Figure 3-36. Advanced Sensor Settings screen.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
Advanced Mode Functions:  
FIgure 3-37. Advanced mode functions, units.  
Units: Changes units from C to F or vice versa.  
Figure 3-38. Advanced mode functions, rearm.  
Rearm: The Rearm parameter is useful for sensors, such as the temperature and humidity sensors, whose values can vary.  
This prevents the sensor from flickering between two states. For example, if the Warning High threshold for the temperature  
sensor is set to 80 degrees, and the sensor temperature varies between 79 and 80, you could be faced with a very large number  
of e-mails, traps, and events logged. The Rearm parameter prevents this by forcing the temperature to drop by the Rearm value  
before changing the state back to normal. In this example, if Rearm is set to 2, then the sensor would have to drop from 80  
down to 77 before the status would change from Warning High back to normal.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
Figure 3-39. Advanced setings, reading offset.  
Reading offset: A calibration tool. If you want to calibrate the temperature sensor, for example, you could enter an offset value  
of 5. This means that if the sensor reads 20 degrees then it would record as 25 degrees. This figure can also be a minus figure  
(for example, -5 would show 15 degrees instead of 20).  
Figure 3-40. Advanced settings, data collection type.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
Data Collection Type  
This refers to the data collection from the sensor and how the data is then displayed on the graphs.  
There are three options for collection of data: Average, Highest, and Lowest. The default setting is Average.”  
When the data collection type is set to Average,” the output graphs for the daily, monthy, and yearly all have the same size on  
the screen. For the daily graph, each data point on the graph is one data point collected from the sensor. But for the monthly and  
yearly graph, to display more data into the same size as for the daily graph, some consolidation on the data is needed. One data  
point on the monthly and yearly graph is the average of the sensor data in a range.  
The maximum and minimum values showing on the monthly and yearly graphs are the value of this consolidated data and not  
the raw data over that period of time.  
When the Data Collection Type is set to the highest setting,then you will get the graphing output dsiplaying the sensor‘s highest  
reading. This is the same for the lowest setting.  
Figure 3-41. Advanced settings, display style.  
Display Style  
You can keep the sensors “Dislplay Style” in the Web interface as the Basic Style (slide bar) or you can change it to “Gauge Style.”  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
Figure 3-42. Gauge Style screen.  
When switching to the Gauge Style type, you will first be prompted with the popup dialog box shown above.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
Figure 3-43. Sensor threshold levels.  
You will now see the new display where you can set the sensor’s threshold levels as shown above.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
Figure 3-44. Advanced Settings Text and Colors screen.  
After clicking on the Advanced Settings” tab, you can change the text and colors for each sensor threshold as shown in the  
screen above.  
Figure 3-45. Advanced Settings, Check Rate of Change screen.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
Check rate of change  
When enabling the “check rate of change” feature for the sensor, you can set the rate in a percentage ranging from 1% to 80%  
over a period of time ranging from 1 to 20 minutes. You can set the direction to Up, Down, or Both, and you can set the Status  
when the limit is exceeded to show either High Critical or Low Critical.  
You can tie this sensor alert to any notification. Use it with a fuel level sensor to alert you to theft of fuel or leaks in storage tanks.  
Continuous Time Settings and Minimum Time Settings Tabs  
The following advanced functions set the time frame in which the system should delay a notification being triggered when a  
sensor gives a reading that exceeds the thresholds (high warning, normal, etc).  
Continuous Time to Report High Critical: This helps to eliminate unnecessary messages during minor fluctuations. You can set  
the amount of time to delay a notification of a status change from high warning to high critical. Enter the time in seconds and  
press the “Save” button. The amount of time that you can enter is between 0 and 65535 seconds, which equals approximately  
18 hours.  
Continuous Time to Report High Warning: As above, but delays notification for “High Warning.”  
Continuous Time to Report for Normal: As above, but delays notification for return to “Normal” state.  
Continuous Time to Report for Low Warning: As above, but delays notification for “Low Warning” state.  
Continuous Time to Report for Low Critical: As above, but delays notification for “Low Critical” state.  
Continuous Time to Report for Sensor Error: As above, but delays notification being sent for sensor going into an error state.  
Example: An airflow sensor or humidty sensor may have temporary drops in readings that are normal operating characteristics; a  
logical time limit is set to show abnormal conditions.  
Enable Calendar: If you select this option, the screen shown in Figure 3-46 will be displayed.  
Figure 3-46. Enable Calendar Status screen.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
In this example, we want to monitor an office building between the hours of 7 PM–9 AM Monday–Friday only. You can see in  
this picture we have selected the “Do Not Report” option for the hours in which we do not want to receive any notifications or  
have any events logged. You change the status of that time frame (Report/Do Not Report) simply by clicking on the square. This  
will change it from blue to gray; a second click will return it to blue.  
Figure 3-47. Enable Calendar screen.  
3.7 Using an Internal Mic as a Sound Detection Sensor  
You can use the internal microphone (or an external plugged into the line in jack) as a sound detector.  
This tutorial provides you with the information you need to set up the internal mic as a sound detection sensor.  
To get to the starting point of this tutorial:  
• Log into the Web based interface.  
• Click on the Sensors tab.  
1. Click “Sound Detector” under the Sensors menu. See Figure 3-48.  
2. Click “Advanced Mode.”  
3. After you click on the Advanced Mode button, you’ll see the advanced options available. (See Figure 3-49.)  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
Figure 3-48. Sound Detector tab.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
Figure 3-49. Advanced options.  
Recording Source: Here you can choose either internal or external microphone.  
Microphone Boost (+20 dB): Boosts the microphone by 20 dB.  
Microphone Sensitivity: The level of sensitivity that can be set.  
For example, if you set the level to 80, the microphone will detect more sound than if the level were set at 20.  
Pulse Length: This defines the minimum duration of a sound to trigger an alert notification.  
Rearm: The Rearm parameter prevents the sensor from flickering between two states. For example, if the Warning High thresh-  
old for the sound sensor is set to 80 and the sensor temperature varies between 79 and 80, a very large number of e-mails, traps,  
and events would be logged. The Rearm parameter prevents this by forcing the signal level to drop by the Rearm value before  
changing the state back to normal. In this example, if Rearm is set to 2. then the sensor would have to drop from 80 down to 77  
before the status would change from Warning High back to normal.  
Data Collection Type: There are three settings for this parameter: lowest, highest, and average. Data will be collected for the  
lowest, highest, or average sound reading accordingly.  
Advanced Status Text and Color: Here you can select to change your display text and warning colors.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
NOTE: As with all the other sensors, you can now set up the sound detector to be attached to a notification. Then, when your  
thresholds are broken, it will trigger a specified type of notification.  
3.8 Expansion Ports  
The ServSensor has two expansion ports that enable you to connect up to two daisychainable expansion modules. The available  
expansion modules are an 8-port intelligent sensor board (EME1X8) and an opto-isolated (16) dry-contact expansion module  
(EME1DC16). In this section, we will go through the basic setup of the 8-port intelligent sensor board. If you need information on  
specific functions of a particular sensor or expansion board, then please refer to the relevant manual for that product.  
1. Plug the expansion board into one of the two ports located on the front panel of the unit. These are numbered E1 and E2. See  
Figure 3-50.  
Figure 3-50. Plug expansion boards into these ports.  
2. From the summary page, navigate to the “Sensors” tab. Then click “Extended port” as outlined in Figure 3-51.  
Figure 3-51. Sensors tab, extended port option.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
3. A list of all extended ports will be shown. Each port will display any available extension modules, which will be highlighted in  
green. Click on the module to go to the sensor settings page.  
Figure 3-52. Extended Port1 selection.  
4. This will bring you to the Extended Port Sensors page (see Figure 3-53).  
Figure 3-53. Extended Port Sensors page.  
5. Once you have clicked on the “Dual sensors” tab, you will be directed to the familiar-looking Notification Thresholds page (see  
Figure 3-54). From this page, you can carry out various operations as indicated in the sensor settings tutorials.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3: Installation  
Figure 3-54. Notification Thresholds page.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4: Notifications  
4. Notifications  
If you set up a notification, you can define the action to take when the sensor gives a reading beyond your set thresholds. This  
enables you to determine how you will be notified that a sensor’s reading has reached the specified parameters (high warning,  
critical, etc.) described in Chapter 3.  
This tutorial provides you with the information you need to set up a notification.  
To get to the starting point of this tutorial:  
• Login as administrator.  
• Click the “Notifications” tab.  
4.1 Adding a Notification  
1. Click on the “Begin Notification Wizard” tab as shown in Figure 4-1.  
Figure 4-1. Notification Wizard tab.  
2. The Notification Wizard page will be displayed as shown in Figure 4-2.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4: Notifications  
Figure 4-2. Notification Wizard page.  
Next, you’ll see how to set up a few different ways of notification step by step.  
4.2 SNMP Trap  
If you set up a notification via an SNMP trap, when your sensor reaches a certain threshold, it will send a notification to your  
SNMP server.  
This tutorial provides you with the information you need to set up an SNMP trap.  
To get to the tutorial’s starting point:  
• Log in as administrator.  
• Click the “Notifications” tab.  
• Choose “Notifications Wizard.”  
• Choose “SNMP Trap.”  
1. After selecting to add an SNMP trap, you will need to fill in the following information shown in Figure 4-3.  
Figure 4-3. Add an SNMP trap.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4: Notifications  
2. Once this information is correct, click the Add Trap Destination” button. Input another trap or click on “Next.” Enter the  
parameters shown in Figure 4-4.  
Figure 4-4. Notification parameters.  
These parameters set the maximum number of times to send the trap notification and the time interval between each  
notification.  
3. After clicking “Next,” you’ll see the screens shown in Figures 4-5 and 4-6.  
Figure 4-5. Parameter Selection, screen #1.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4: Notifications  
Figure 4-6. Parameter Selection, screen #2.  
On these screens, you can select the parameters for when to send the SNMP trap notification. In this example, we selected to  
bind the SNMP trap to the temperature sensor connected on Port 1. The trap will be sent when the sensor reads a “High Critical”  
and we bind this to the SNMP trap we just created and named “SNMP Trap 1.”  
4. Once we have created the parameters for the SNMP trap, we need to make it active. To do this, go back to the “Notifications”  
tab. (It should look like the screen shown in Figure 4-7.) Click “Create.”  
Figure 4-7. Notifications tab.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4: Notifications  
5. Select the sensor and SNMP trap parameters (see Figures 4-8 and 4-9). First, click on the board that the sensor is attached to  
and then select the sensor and click “Next.”  
Figure 4-8. Select the sensor.  
6. Select the status that you want to issue the notification for, select the action type, then click “Finish.”  
Figure 4-9. Select the SNMP parameters.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4: Notifications  
7. The SNMP trap has been added to the Notifications page.  
Figure 4-10. SNMP trap added.  
NOTE: To remove this trap and make it inactive, highlight the notification and click “Remove.”  
You can repeat this process to set up multiple SNMP traps for different sensors or for multiple SNMP servers, etc.  
4.3 E-mail  
This tutorial provides you with the information needed to set up an e-mail notification.  
To get to the starting point of this tutorial:  
• Log in as administrator.  
• Select the “Notifications” tab.  
• Click “Notification Wizard.”  
1. If you set up an e-mail notification, Figure 4-11 will appear. Click the “Action Name” field and choose a name for your e-mail.  
Click the “Mail From” and “Mail To” fields and enter the appropriate information, then click “Next.”  
Figure 4-11. E-mail Action Wizard screen.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4: Notifications  
2. After clicking “Next,” you will get a page where you can input the e-mail name and message. Click the “Customize” button,  
and the fields will re-write in a format that will allow for an automated e-mail that will display the sensor information. (See  
Figure 4-12.)  
Figure 4-12. Input e-mail name and message.  
Figure 4-13. Attach graph.  
3. Click “Next.”  
4. Now you need to input your SMTP server address for your e-mail account. (See FIgure 4-14.)  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4: Notifications  
Figure 4-14. Input SMTP server address.  
5. Once this is entered, click “Next.”  
6. Now, as with the SNMP trap, you can select how many times to attempt to resend the e-mail, and the time elapsed between  
each attempt.  
7. Click “Next” after you fill in your parameters. (See Figure 4-15.)  
Figure 4-15. Select frequency to resend e-mail attempts.  
8. Now link the e-mail you just created to the temperature sensor on Port 1. Select the board the sensor is attached to, then  
select the sensor and click “Next.” (See Figure 4-16.)  
Figure 4-16. Select sensor.  
9. Select the status you want to issue the alert for and then select the action type. (See Figure 4-17.)  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4: Notifications  
Figure 4-17. Select status and action type.  
10. Click “Finish.” You will now be taken back to screen shown in Figure 4-18.  
11. Click on “Create.”  
Figure 4-18. Create notification link  
12. Create the notification link as before. Then click “Next.”  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4: Notifications  
Figure 4-19. Create notification tab: select board, select termperature.  
Figure 4-20. Create notification tab: select status, select e-mail.  
14. You will now be back at the main notification page. You should now see listed our two notifications, the SNMP trap and the  
e-mail. (See Figure 4-20.)  
As you can see from this page, an SNMP trap is set up to give us notification of a “High Critical,” and an e-mail notification that  
will activate on a “High Warning.”  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4: Notifications  
Figure 4-21. SNMP Trap and E-mail Notificiations screen.  
4.4 SMS Notification  
Set up a notification so that you will be sent an SMS message. This message can be sent via a GSM/GPRS mobile phone  
connected via a Bluetooth connection or the USB port.  
This tutorial provides you with the information you need to set up a SMS notification.  
To get to the starting point of this tutorial:  
• Log in as administrator.  
• Select the “Notifications” tab.  
• Click “Notification Wizard.”  
1. From the list of notification types, select SMS and click “Next.” You will then be presented with the screen shown in Figure  
4-22. Select the Action Name” field and enter a notification name. Then select the “Phone Number” field and enter the  
phone number you want to send the notification to. Click “Next.”  
2. You can now either add multiple numbers, delete phone numbers, “Cancel” this action, or click “Next.” In this case, we will  
click “Next.” (See Figure 4-23.)  
Figure 4-22. SMS Action Wizard, screen #1.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4: Notifications  
Figure 4-23. SMTP Action Wizard, screen #2.  
3. Now we will set up the message that will be sent to the phone. You will see the screen shown in Figure 4-24.  
Click the “Customized” button to add a macro to your notification.  
Figure 4-24. Customize Macro screen.  
NOTE: A macro is a script that returns specific data collected by the unit. In our example, the macro will tell the notification to  
contain the “description” (sensor name), the value (current sensor reading), and the status (high/low warning, etc.). These  
macros are common to all sensor notifications.  
4. You will now see that the SMS message has changed its format to include the Macro script. (See Figure 4-25.) Click “Next.”  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4: Notifications  
Figure 4-25. Macro script message.  
5. Next, we will set up the type of connection. This will depend on the type of modem you are connecting. For the purpose of  
this tutorial, we will assume you are connecting a GSM/GPRS enabled modem to the serial port. Select COM1 from the list.  
(See Figure 4-26.)  
6. Choose the port that the modem is connected to.  
Figure 4-26. Choose the Connection Type You Wish to Use screen.  
7. You will now be able to select the number of times you want the SMS to be resent and the interval between sending them.  
(See Figure 4-27.)  
8. Select the number of times you want to resend this notification and the interval (in seconds). Click “Next.”  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4: Notifications  
Figure 4-27. Select number of times to resend and intervals.  
9. Select the sensor that you want to bind this notification to.  
10. Choose the board and sensor, then click “Next.”  
Figure 4-28. Choose board and sensor.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4: Notifications  
Figure 4-29. Link sensor to action tab.  
11. This time we will use this notification for a low warning. Then select the notification name we assigned, in this case we chose  
“SMS 1.” Click “Finish” to finalize this. (See Figure 4-29.)  
12. Now we will add the SMS notification to our active list. This is the same process as for the others—simply click on “Create”  
and then select the appropriate parameters. Follow Steps A–F below and on the next page.  
A. Select the board the sensor is connected to.  
B. Select the sensor.  
C. Click “Next.”  
Figure 4-30. Steps A–C.  
D. Select the status you want to issue the alert for.  
E. Select the action type.  
F. Click “Finish.”  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4: Notifications  
Figure 4-31. Steps D–F.  
13. You will now be back at the main notification page (Figure 4-32). The page should display three types of notifications: the  
SNMP trap, e-mail, and SMS.  
Figure 4-32. Main notification page.  
For the purposes of this tutorial, we will not cover the setup of every type of notification. However, with this information you  
should be able to follow the procedure for the other types of notifications easily, as they all follow a similar format. If you have  
questions, contact Black Box Technical Support at 724-746-5500 or [email protected].  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 5: Mapping  
5. Mapping  
The mapping feature allows instant visual feedback about a sensor’s position and status. It is a useful monitoring tool for a setup  
with several sensors in different positions.  
This tutorial provides you with the information needed to set up the mapping feature.  
To get to the starting point of this tutorial:  
• Log in as administrator.  
• Click the “Map” tab.  
5.1 Adding a Map  
1. First, we need to add a picture file to be used as the map. This can be a blueprint of your office, a 3D picture of your office/site  
being monitored, or a photo of the wiring closet you are monitoring.  
NOTE: The maximum map file size is 512 KB.  
Figure 5-1. Click on the “Map” tab.  
2. Browse to the file on your hard drive that you want to use.  
Figure 5-2. Browse to selected file.  
3. In this tutorial, we are going to use a 3D map of a town center we are monitoring.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 5: Mapping  
Figure 5-3. Enter map name.  
4. Choose to have the map as a top-level map.  
Figure 5-4. Enter map level.  
5. You will now have the option to finish or to add sensors to your map. For this tutorial, click “Next.”  
Figure 5-5. “Finish” or “Next.”  
6. You will now be taken to the map page where it will display your map. To add sensors, click “Next.”  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 5: Mapping  
Figure 5-6. Sensor map.  
7. After clicking “Next,” click the “Unlock” button. This enables you to add sensors to the map.  
Figure 5-7. Add sensors to map.  
8. You can now drag sensor icons and position them on the map.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 5: Mapping  
Figure 5-8. Position sensor icons on map.  
9. After you have positioned the sensors in the correct location of your map, click “Lock.”  
Figure 5-9. Click “Lock.”  
10. Finally you click on the “Finish” button to save your changes.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 5: Mapping  
Figure 5-10. Save changes.  
5.2 Monitoring via the Map Interface  
Now we are going to look at how to monitor the sensor status and use the map interface.  
1. To see further information about a sensor, you can click on its icon. First, you must click on the “Unlock Icons” button.  
Figure 5-11. Using the map interface.  
If you connect other sensors, these too can be dragged and positioned on the map.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 6: Filters  
6. Filters  
6.1 Sensor Filters  
1. The ServSensor comes equipped with the option to filter your sensor information that is displayed within the summary page. To  
enter the filter menu, select “Sensor Filters” from the drop-down tab on the left side of the page.  
Figure 6-1. Select sensor filters.  
2. Once you click the tab, you will be able to select your filter results by altering various fields of information contained within the  
sensor filter window.  
Figure 6-2. Add information fields.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 6: Filters  
3. You can alter the page reload interval by using these options.  
Figure 6-3. Alter the page reload interval.  
4. Once you have selected your preferred filter options, your new settings will be displayed in the “Sensor Information” window  
found on the Summary page.  
Figure 6-4. Summary page.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 6: Filters  
6.2 Syslog Filters  
Syslog filters enable you to customize your syslog window. To begin. select the “Syslog Filters” tab found on the summary page.  
Figure 6-5. Syslog Filters tab.  
Once you click the tab, you will be able to select your filter results by altering various fields of information contained within the  
syslog filter window.  
Figure 6-6. Drop-down menu.  
By checking and unchecking various boxes within the Syslog filter window, you can customize your displayed results contained  
within the syslog filter.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 6: Filters  
Figure 6-7. Customize syslog filter results display.  
You can alter your reload interval by using the options shown below.  
Figure 6-8. Change reload interval.  
Once you have selected your preferred filter options, your new settings will be displayed in the “System log Information” window  
found on the Summary page.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 6: Filters  
Figure 6-9. Saved syslog filters display.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 7: Making the ServSensor Visible on the Internet  
7. Making the ServSensor Visible on the Internet  
The setup we have just created will enable you to access your ServSensor V4E Lite on a local area network (LAN), monitor via the  
Web based interface, or with SNMP traps.  
But, what if you want to be able to remotely access your unit from anywhere in the world? This is possible; however, the follow-  
ing steps are only a guide. Your exact setup and configuration will often depend on your network equipment. You are going to  
need access to your router, if you are using one, and know whether your IP address is static or dynamic.  
1. Suppose your ServSensor is connected to a router on your network, and the following IP addresses are assigned:  
Your unit’s IP address is the default 192.168.0.100.  
Your computer’s IP address is 192.168.0.200  
Your router’s IP address is 192.168.0.300  
Suppose your router’s external IP address is 278.67.04.09  
3. You now need to set up port forwarding on your router. This varies depending on your router’s model. Generally, you need to  
point your browser to your router”s IP address (in this case 192.168.0.300). This will then enable you to log into your router’s  
port_forwarding/Linksys/WRT54G/HTTP.htm  
You need to set up your router’s HTTP forwarding to Port 80. This will then mean when you access your router using the external  
IP address, you will be forwarded to your unit’s internal IP address.  
4. To test this, open your Web browser, and go to your external IP address (in our example 278.67.04.09). If you’re using a  
dynamic IP address, check it again before doing this because it may have changed since the start of this tutorial.  
5. To make this easier, you could use a Dynamic Name Server (DNS). This means that you no longer need to remember IP  
mysensorProbe2.homeip.com). This will then automatically point to your router’s external IP address (e.g. 278.67.04.09).  
This will require you to register the domain name and open an account with a DNS service provider. We recommend  
6. If you have set up everything correctly, you will now be able to access your unit from anywhere in the world simply by pointing  
your Web browser to your DNS address.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 8: Frequently Asked Questions (FAQs)  
8. Frequently Asked Questions (FAQs)  
Question: I cannot see the temperature sensor displayed on summary page.  
Answer: After logging in for the first time with the temperature sensor connected, you may need to do the following.  
Figure 8-1. Select sensor to display.  
Next, click on Apply Filter.” The temperature sensor should then be displayed in the list of connected sensors.  
Question: I cannot access my unit’s Web interface.  
If you’re having issues with network connectivity, first make sure that the link100 LED is lit on the front display of the unit. If this is  
not lit, then no network connection is present.  
Answer:  
1. If connected directly to a PC, make sure you’re using a good quality crossover cable.  
2. Make sure you’re using a standard CAT5 Ethernet cable to connect to your network.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 70  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 8: Frequently Asked Questions (FAQs)  
Question: What do my LED lights mean?  
Answer: The following diagrams show what the various LED displays mean.  
Figure 8-2. LED patterns in Normal mode.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 8: Frequently Asked Questions (FAQs)  
Figure 8-3. LED patterns in Safe mode.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 8: Frequently Asked Questions (FAQs)  
Figure 8-4. LED patterns in Recovery mode.  
LEDs run clockwise after the power is connected.  
From left to right, each LED indicates:  
1st LED: U-Boot init  
2nd LED: Kernel loaded with good CRC  
3rd LED: Board init  
4th LED: Serial port  
5th LED: Ethernet  
6th LED: NOR Flash  
7th LED: NAND Flash  
8th LED: Root file-system mounted. Starting initialization process  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 8: Frequently Asked Questions (FAQs)  
After the root file-system is mounted, all green LEDs will be flashing, and red LEDs light increasingly from left to right. The  
onboard Web server can be accessed during this time and shows a splash screen with boot details. After the boot process is  
finished, the LEDs show the status of the online sensors.  
Question: I forgot my unit’s IP address.  
Answer: If you forget the IP address of your unit, you can simply press the reset button on the back of the unit. This will then  
announce the IP address through the unit’s internal speaker.  
Question: I forgot the password for my unit.  
Answer: Hold down the reset button for seven seconds. This will turn off the use password feature for the Web-based interface.  
This will remain turned off until you hold the button down for a further seven seconds, or the unit announces “Now turning off  
password checking.”  
NOTE: This will turn off the password checking for accessing the Web interface only; you still have to enter the password when  
you access the system via Telnet.  
Question: Can I use DHCP to assign my unit’s IP address?  
Answer: Yes, you can use DHCP to assign the IP address. The unit ships with this disabled. To turn it on, you need to log  
into the Web interface and navigate to the Ethernet settings via the “Security” tab, “Ethernet Network,” and then click  
on the “Yes” button for “Use DHCP.”  
Figure 8-5. Activate DHCP.  
NOTE: If the unit has a static IP address assigned, it will no longer send out DHCP requests. If you later want to turn DHCP back  
on, you can do that using the Web-based interface.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 74  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 8: Frequently Asked Questions (FAQs)  
Question: How do I set up my routing table?  
Answer: To set up the routing table, open a DOS window (start, run type command press enter) and at the command prompt,  
then enter: >route add 192.168.0.100.10.1.1.20  
Where 10.1.1.20 is the IP address of the Ethernet interface on the PC that the unit is plugged into with the crossover cable.  
Now ping* 192.168.0.100 to see if the connection was successful.  
Question: How can I change my administrator password?  
Answer: If you want to make your unit more secure and change the administrator password from the default (public) to your  
own choice, follow these steps:  
1. Log into your unit using the default password.  
2. Click the “Settings” tab.  
Figure 8-6. Select change password option.  
3. Change the password.  
Figure 8-7. Change user and/or admin passwords.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 8: Frequently Asked Questions (FAQs)  
Question: What function do the different types of notifications provide?  
Answer: The notifications are used to notify you when a sensor reading has hit a certain preset “critical” threshold. There are  
many ways you can be notified. They are as follows:  
SNMP Trap: This form of notification sends out a signal to your SNMP server.  
E-Mail: This sends a notification via e-mail.  
SMS: This sends an SMS message to your mobile phone.  
MMS: This will send you a multimedia message to your mobile phone. This can include an image captured from one of the  
sensor probe’s cameras.  
Relay: The relay is used as a switch, for example, it could switch on an air-conditioning unit if the temperature reading  
of a temperature sensor reaches a certain threshold.  
Alarm sound: This notification will sound an alarm.  
Speech: Creates a text-to-speech notification.  
Telephone call: Will call you and play a prerecorded message or a text-to-speech message.  
Custom script: Allows you to load a custom script that runs on a sensor reading a preset parameter.  
Fax: Will send a fax to you with a notification message.  
Sound log: Creates a log of sound captured with the internal/external microphone.  
Siren and strobe: Will activate a siren and strobe light.  
Wake up/shut down: This will send a signal to wake up or shut down a server.  
If you require any assistance in setting these up, contact Black Box Technical Support at [email protected].  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 76  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 8: Frequently Asked Questions (FAQs)  
Question: Can I connect my unit via Wi-Fi?  
Answer: Yes, you can connect the unit via Wi-Fi. Simply plug a USB dongle into the USB port on the rear of the unit.  
You then need to configure your connection type and encryption key, etc. Do this from the Web-based interface in the “Settings”  
tab and the connectivity option.  
Figure 8-8. Win Network screen.  
Question: What is the Heartbeat message?  
Answer: This setting is to have the ServSensor notify you that it is still running. You can be notified by either traps or by e-mail:  
Alive Trap settings: Send Keep Alive Traps (Default Off): Select on if you want the system to send Alive Traps.  
Destination: Enter the IP address of the server to send traps to.  
Community: SNMP community string.  
Resend Interval (mins): The period of time between each keep-alive trap. Values range from 1 to 65535 minutes.  
Question: What is the network sniffer?  
Answer: The network sniffer application can be used to capture network packets running to and from the securityProbe, and all  
the network traffic. You can then import the captured file into TCP dump for details of these network packets. The network trace  
will help in debugging any network problems; for example, if e-mail cannot be sent.  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 8: Frequently Asked Questions (FAQs)  
Question: Can I use the camera for a videoconferencing call?  
Answer: Yes, it is possible to use the camera and the integrated microphone to make a videoconferencing call. You need the  
software called “OpenPhone” running on your computer. This is included on the CD-ROM that came with your unit. (Look for  
OpenPhone.exe). Next follow these steps:  
1. Initiate connection from OpenPhone (PC) to ServSensor.  
a. Open the program by double clicking "openphone.exe"  
b. Click the "Make Call" button, enter the IP address of the sensorProbe8Linux/cameraProbe8 to initiate a call in the "Address"  
field. Then, click "OK."  
c. The unit will automatically respond to a call and establish the connection. You will then see the video and hear sound from  
the unit.  
2. Initiate connection from a ServSensor to OpenPhone (PC).  
a. Open the program by double clicking "openphone.exe"  
b. On the Web interface, click on the Applications” tab, and click on “Video Conferencing.”  
c. Select the "Call to" option and enter the IP address of the PC running OpenPhone. Click “Save” to discover your computers  
IP address in the command prompt, type “ipconfig.”  
d. On the OpenPhone application, click Answer” to accept the call.  
3. Connection between two sensorProbe8Linux/cameraProbe8 (only voice conference).  
a. On the Web interface of the calling sensorProbe8Linux/cameraProbe8, click on the Applications” tab, and click “Video  
Conferencing.”  
b. On the right pane, select the “Call to” field and enter the IP address of the receiving sensorProbe8Linux/cameraProbe8 into  
this field. Click “Save.”  
c. The connection should automatically establish.  
You can end the videoconference call by doing the following:  
1. End the call on OpenPhone (PC): To end call, click the "Hang Up" button on the OpenPhone. This method can be used to  
end the call between the system and OpenPhone.  
2. End the call on the unit: From the Web interface, click on the Applications” tab and click on “Video Conferencing.” On the  
right pane, select “End call and wait for a new incoming call” option. Then, click “Save.”  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 78  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
EME144A-R2  
724-746-5500 | blackbox.com  
Page 79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Black Box Tech Support: FREE! Live. 24/7.  
Tech support the  
way it should be.  
Great tech support is just 30 seconds away at 724-746-5500 or blackbox.com.  
About Black Box  
Black Box Network Services is your source for an extensive range of networking and infrastructure products. You’ll find everything  
from cabinets and racks and power and surge protection products to media converters and Ethernet switches all supported by  
free, live 24/7 Tech support available in 30 seconds or less.  
© Copyright 2013. All rights reserved.  
EME144A-R2, version 1  
724-746-5500 | blackbox.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Black Decker Can Opener EM150C User Manual
Black Decker Cordless Sander BDERO100 User Manual
Blanco Indoor Furnishings 157 060 User Manual
Bosch Power Tools Saw 4410L User Manual
Brother Label Maker QL 570 User Manual
Cabletron Systems Switch TRFMIM 28 User Manual
Carrier Air Conditioner 16JB User Manual
CDA Ventilation Hood EVPK9 User Manual
Chicago Electric Welder MIG 170 User Manual
Cisco Systems IP Phone 3010 User Manual