Hot Attachment of Power Supplies:
1. Unpack the power supply carefully. Inspect for any damages. If any damage is
observed, do not use the power supply and call (949) 250-6510 to report the
damage immediately and request a replacement unit.
2. Attach the power supply to the chassis and reconnect the 48VDC power source
to the FlexPoint power supply.
JULY 2001
LMC200A-2PS-DC
LMC200A-DC
PSFP20-DC
3. Locate the 48VDC circuit breaker and switch the circuit breaker to the ON
position.
4. Turn the FlexPoint Chassis power supply ON.
5. Observe the LED in the front of the chassis indicating that the power has been
restored.
SPECIFICATION
Indicators:
Power ON:
LED (2), Yellow, power applied
FlexPointTM Powered Chassis
Dimensions / Weight: W:19.0"xD:7.0"xH:3.5" / 9 lb.
Power:
48VDC / 3.0 Amps (for model 4386)
2ea. 48VDC / 3.0 Amps (for model 4385)
Environmental:
Temperature:
Humidity:
48V Power Redundant
14 Module Chassis
0 to 40 degrees C
0-90% (non-condensing)
User’s Manual
Order toll-free in the U.S.: Call 877-877-BBOX (outside U.S. call 724-746-5500)
CUSTOMER
SUPPORT
INFORMATION
FREE technical support 24 hours a day, 7 days a week; Call 724-746-5500 or fax 724-746-0746
Mailing address: Black Box Corporation, 1000 Park Drive, Lawrence, PA 15055-1018
©Copyright 1999-2001.Black Box Corporation. All rights reserved.
1000 Park Drive
z
Lawrence, PA 15055-1018
z
724-746-5500
z
Fax 724-746-0746
Download from Www.Somanuals.com. All Manuals Search And Download.
6
Cabling and Power-Up:
FlexPointTM Powered Chassis
User’s Manual
1. Insure that both FlexPoint Chassis power supply switches are in the OFF position.
2. Assure that the 48VDC circuit breaker can supply 3Aof current per power supply.
3. Locate the 48VDC circuit breaker, and switch the 48VDC circuit breaker to the
OFF position.
4. Cut the power cable to the length required.
GENERAL DESCRIPTION
5. Strip approximately 3/8 of an inch of insulation from the power cable wires.
6. Connect the power cables to the FlexPoint Chassis by fastening the stripped
ends to the 48VDC connector.
The FlexPointTM Powered Chassis is a chassis capable of holding up to 14
FlexPointTM media converter modules. It is equipped with two power supplies in a
power-redundant configuration.
WARNING: Note the wire colors used for making the positive, negative and
ground connections. Use the same color assignment for the connection at the
circuit breaker.
7. Connect the power cable to the circuit breaker and switch the circuit breaker
ON.
8. Turn both FlexPoint Chassis power supply switches on and check the power
LED’s on the front panel of the powered chassis. The two LED’s should be ON.
9. Attach the L shaped tabs to the FlexPoint media converter units to be inserted
into the chassis, Secure the FlexPoint module using the enclosed screws.
10. Save the unused tabs in a safe place or secure them to the chassis’ unused
Slots.
POWER SUPPLY REPLACEMENT
WARNING!
This User’s Manual describes the following models:
NEVER ATTEMPT TO OPEN OR SERVICE THE POWER
SUPPLY UNIT. OPENING THE POWER SUPPLY UNIT
MAY CAUSE SERIOUS INJURY OR DEATH.
Model
Description
LMC200A-2PS-DC
Powered Chassis, rack-mountable chassis, 2 power
supplies
LMC200A-DC
PSFP20-DC
Powered Chassis, rack-mountable chassis, 1 power
supply
Power supply unit for models LMC200A-2PS-DC and
LMC200A-DC
The Powered Chassis is intended to be used with two power supplies in a power-
redundant operation. A failure of a single supply should not disturb the operation
of the chassis unit. However, certain power supply failures may cause a
secondary failure to the associated fan and cause undesired overheating of
the chassis unit.
Download from Www.Somanuals.com. All Manuals Search And Download.
4
5
8. Wiring methods used for the connection of the equipment to the primary
power supply shall be in accordance with the National Electrical Code, ANSI/
NFPA 70, and the Canadian Electrical Code, Part I, C22.1.
CONTROLS AND INDICATORS
LEDs Display:
The Powered Chassis features two LEDs on the left front of the chassis, these
LEDs display the status of the two power supplies.
UNPACKING
a. Visual Inspection: Inspect equipment in order to detect any physical damage.
Any evidence of damage should be noted and reported immediately.
Function
Top LED
Bottom LED Yellow / ON
Color/State
Yellow / ON
Description
Power OK in right power supply
Power OK in left power supply
INVENTORY
Review contents, the following items should be included:
Note: Left/right direction as viewed from the front of the chassis.
(1) FlexPoint Powered Chassis unit.
(2) Power supplies (2 for model LMC200A-2PS-DC, 1 for model LMC200A-DC).
(14) L shape tabs.
(14) Screws
(1) User’s manual (this document).
Please note any missing items or discrepancies and report them immediately.
INSTALLATION
WARNING: Only a DC power source that complies with safety extra low
voltage (SLEV) requirements can be connected to the DC-input power supply.
Tools and Equipment Required:
Flat-head screwdriver (not supplied)
Wire cutter/stripper (not supplied)
Three-conductor 14 AWG copper power cable (recommended; not supplied)
SITE PREPARATION REQUIREMENTS
Preparation:
1. Power: Assure the 48VDC power can supply 3A of current.
Assure that the FlexPoint Chassis is physically installed in accordance with
the Site Preparation Requirements outlined earlier in this document.
2. The operating temperature of this equipment is 0-40 degrees C. If installed
in a closed or multiunit rack assembly, the operating ambient temperature
of the rack must not exceed the maximum rated 40 degrees C temperature.
3. Installation of the equipment should be such that the air flow in the front and
back of the unit is not compromised or restricted.
4. Never use this equipment to carry any weight except its own, never use it as
a shelf to support weight of other equipment.
5. Installing this equipment into a rack in such a way as to make it unstable
may cause injury or death. Always make sure that the rack you are installing
this equipment into is properly secure, stable, balanced and designed to
carry the weight and weight distribution of this equipment.
WARNING REGARDING EARTHING GROUND:
a) This equipment shall be connected to the DC supply system earthing
electrode conductor or to a bonding jumper from an earthing terminal bar
or bus to which the DC supply system earthing electrode is connected.
b) This equipment shall be located in the same immediate area (such as,
adjacent cabinets) as any other equipment that has a connection
between the earthed conductor of the same DC supply circuit and the
earthing conductor, and also the point of earthing of the DC system. The
DC system shall not be earthed elswere.
6. When rack-mounting this equipment, the rack should be appropriately
earth-grounded.
c) The DC supply source is to be located within the same premises as this
equipment.
7. This equipment requires 48 VDC / 3.0 Amps per power supply. Appropriate
overloading protection should be provided on all DC power source outlets
utilized.
d) There shall be no switching or disconnecting devices in the earthed circuit
conductor between the DC source and the earthing electrode conductor.
Download from Www.Somanuals.com. All Manuals Search And Download.
|