Baldor Remote Starter MN894 User Manual

Multipurpose  
Soft Starter  
Sizes 8 to 840 AMP  
Installation & Operating Manual  
9/06  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Section 1  
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
1-1  
1-1  
1-4  
1-4  
1-6  
1-7  
1-8  
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Major Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Protection Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Safety Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Section 2  
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
2-1  
2-1  
2-1  
2-1  
2-1  
2-1  
2-3  
2-4  
Receiving, Inspection and Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Physical Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
AC Main Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Protection Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Power Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Non-Motor and Special Motor Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Section 3  
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3-1  
3-1  
3-2  
3-2  
3-2  
3-2  
3-2  
3-2  
3-2  
3-2  
3-3  
3-3  
3-3  
3-3  
3-3  
3-5  
3-5  
3-5  
3-5  
3-5  
3-5  
3-5  
3-5  
Types of Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Start Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Ramp Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Torque Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Pulse Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Current Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Stop Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Ramp Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Torque Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Run Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Current Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Power Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Current Calibration Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Operating Parameters Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Control Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
CLOSE TO RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
START/RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
SHUNT TRIP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
RAMP END . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
TACH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
MTR PWR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
CUR MON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
MN894  
Table of Contents i  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Power On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Over Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Motor Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Summary of Start and Stop Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3-6  
3-6  
3-6  
3-6  
3-6  
Section 4  
Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Safety Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Start-up Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Recommended Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Quick Set-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Starting Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Variable Load with Voltage Ramp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
High Friction Load with Voltage Ramp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Inertial Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Tachometer Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Start-up Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
4-1  
4-1  
4-1  
4-1  
4-1  
4-2  
4-4  
4-4  
4-5  
4-6  
4-7  
4-8  
Section 5  
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
5-1  
5-1  
5-1  
5-1  
5-1  
5-2  
5-2  
5-2  
5-3  
5-4  
5-5  
5-6  
5-8  
5-9  
5-9  
Safety Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Power Off Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Blocking Voltage Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
SCR Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Full Voltage Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Resistance Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
SCR Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Logic Control Module Resistance Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Troubleshooting Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Reset the Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Reset an Overload Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Fuse Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
ii Table of Contents  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 6  
Specifications and Product Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
6-1  
6-1  
Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Three Phase Starters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Three Phase Starters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Wire Size & Tightening Torque Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Mounting Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Open Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
NEMA 1, 3R and 12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Connection Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
MA Style 8, 16 and 30 AMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
MB Style 8, 16 and 30 AMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
MA Style 55 and 80 AMP NEMA 1 and Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
MB Style 55 and 80 AMP NEMA 1 and Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
NEMA 1 & Panel Mounted Size 160840 AMP Control Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
NEMA 1 & Panel Mounted Size 160840 AMP Combination & Noncombination . . . . . . . . . . . . . . . . . . . .  
NEMA 12 Size 160840 AMP Combination & Noncombination Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . .  
6-1  
6-2  
6-2  
6-4  
6-5  
6-5  
6-6  
6-7  
6-7  
6-8  
6-9  
6-10  
6-11  
6-12  
6-13  
Appendix A  
Reference Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
A-1  
A-1  
A-1  
A-3  
A-4  
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Current Calibration Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Quick Reference Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Overload Relay Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Appendix B  
Circuit Breaker Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
B-1  
MN894  
Table of Contents iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
iv Table of Contents  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1  
General Information  
Introduction  
Three phase multipurpose soft starter control provides reduced voltage, three phase  
motor starting. Ramp up and extended ramp down features provide an effective means  
to start and stop material handling equipment and pumping equipment to minimize  
spillage and water hammer problems. Adjustable current limit allows constant current  
starting of high inertia loads such as chippers, centrifuges and compressors. It also  
reduces the peak demand of power required from utility companies or generating  
equipment.  
Tachometer feedback may be used to provide consistent starting and stopping times with  
linear acceleration and deceleration. This is especially important under varying load  
conditions like: textile, material handling and pumping equipment.  
Six SCR (silicon controlled rectifier) devices are connected in three sets of inverse  
parallel configuration to provide full wave voltage and current control of the three phase  
AC motor. MOV (metal oxide varistors) provide surge voltage protection at the AC input  
to the starter.  
Several product features make this soft start control easy to use:  
S
S
S
S
S
Two selectable starting methods.  
Individual ramp up and ramp down adjustments.  
Flexible yet simple setup with switch selections and potentiometer adjustments.  
Simple onboard current calibration.  
Indicator lights and status contacts providing information about the starting,  
running and stopping conditions.  
S
Bar graph display provides a visual representation of motor current to assist in  
set-up and troubleshooting. (0 to 400% FLA).  
S
S
S
Tachometer input.  
Five output relay contacts.  
Built-in protection features to reduce down time.  
MN894  
General Information 1-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 1-1 Layout and Identification  
T1 T2 T3  
GND  
CPT  
L1 L2 L3  
CB  
F1  
F2  
F3  
Shunt  
Trip  
CT3  
CT4  
CT2  
OL  
CT1  
MOV  
R1  
R2  
TB1  
LCM  
Overtemperature  
Switch  
PC1  
Fan  
PC2  
PC3  
Snubber  
Capacitor  
Snubber  
Resistor  
Fan  
Fan  
Legend:  
CB -  
CPT -  
Motor Circuit Protector or fusible disconnect  
Control transformer (control voltage)  
CT1, 2, 3, 4 - Current Transformer  
F1, F2, F3 - Control transformer fuses  
GND -  
LCM -  
MOV -  
OL -  
Ground connection  
Logic control module  
Metal oxide varistors  
Overload relay (electronic)  
PC1, 2, 3 - Power Cell  
R1, R2  
TB1, 2 -  
Control Relays  
Terminal block  
1-2 General Information  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Figure 1-2 Logic Control Module Block Diagram  
Ramp  
Mode  
Select  
115 /230 VAC  
Power Input  
Reset  
Logic  
Power  
Supply  
RDD  
CM  
1
2
3
4
5
6
OC  
TACH  
CL  
BP  
Gates & Sync.  
S2 OFF ON  
Power Cell  
Gates and  
Cathodes  
RU  
S
TU  
CL  
T
A
R
T
+
-
PT  
User  
Adjustment  
S
T
Logic &  
PWR  
RD  
TD  
Control Power  
Firing  
O
P
Overcurrent Trip  
OC  
400  
Control  
M
O
T
O
R
R
U
N
CM  
PF  
300  
Status  
MIN MAX  
200  
C
U
R
R
E
N
T
Lights  
Current  
Transformer  
100  
0
S1 OFF ON  
C
x
x
A
1
2
3
4
5
6
7
8
%FLA  
C L  
U
I
R B  
R R  
E A  
N T  
1
2
Current Monitor  
Motor Power  
T
I
O
N
3
6
7
8
9
Relay  
Outputs &  
Status  
Tachometer  
Input  
Ramp End  
Shunt Trip  
Start/Run  
+
-
4
5
10  
11  
Close To  
Run  
12  
13  
Close To Run  
Legend:  
BP -  
CL -  
Bypass  
Current Limit  
CM -  
OC -  
PF -  
Current Monitor  
Overcurrent  
Power Factor  
Pulse Time  
PT -  
RD -  
RDD -  
RU -  
S1  
TACH -  
TD -  
Ramp Down  
Ramp Down Disable  
Ramp Up  
Calibration Switch  
Tachometer  
Torque Down  
Torque Up  
TU -  
MN894  
General Information 1-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Major Components  
Logic Control Module (LCM)  
The LCM (Logic Control Module) operates in the voltage ramp mode or current limit  
mode during ramp up and ramp down (if ramp down is selected). The LCM controls the  
amount of current that the power cells deliver to the motor during ramp up and ramp  
down. It uses gates and synchronous timing circuits to control the firing times of the  
SCR’s in the power cells. The current transformer provides the LCM with motor current  
information. The on board current calibration switches (S1-1 thru S1-8), place burden  
resistors in parallel with the current transformer to calibrate the LCM to the correct FLA  
(full load amperes) of the motor being used.  
Current Transformer  
(CT1) provides starting, stopping and running current information to the LCM. This  
information is used to control starting and stopping current, current limit, current monitor  
and over current shutdown, power factor effect and motor current bar graph indicator.  
(CT2) is required only for sizes 160 through 840 amps. It steps down current to match  
primary rating of CT1 transformer.  
8, 16 and 30 amp models - CT1 is mounted inside the LCM housing.  
55 and 80 amp models - CT1 is mounted externally on the panel.  
160 to 840 amp models - CT1 and CT2 are mounted externally on the panel.  
CT1 ratio is 6000:1  
CT2 ratio is 500:5 for 160, 250 and 420 Amp models.  
CT2 ratio is 1000:5 for 600 and 840 Amp models.  
Power Cells (PC)  
Power cells control the voltage delivered to the motor during ramp up and ramp down (if  
ramp down is enabled). The LCM controls the duty cycle of the SCR’s in the power cells  
(“on” time versus “off” time of each SCR). A power cell contains two silicon controlled  
rectifiers (SCR’s). The SCR’s are solid state switches that are able to control large  
amounts of current with a small amount of gate current supplied by the LCM.  
8, 16 and 30 amp models - six SCR’s are mounted inside the LCM housing.  
55 and 80 amp models - SCR’s are mounted in an isolated package containing two  
SCR’s for each power cell. With this type of package, three power cells are mounted to a  
single heat sink at ground potential. A temperature switch is provided in each cell to  
protect the power cell from overheating.  
160 to 840 amp models - Each SCR is a disk type package containing one SCR. Two  
SCR’s are clamped between two heat sinks. A temperature switch is provided to protect  
the SCR assembly from overheating. Heat sinks are mounted on an insulated base with  
a terminal block and snubber network. The snubber network is a capacitor resistor series  
circuit wired in parallel with the disk type SCR’s. The snubber network enhances the  
electrical characteristics of the SCR’s and provides transient voltage protection. This  
arrangement makes up one power cell. The power cell is at line potential for both line  
and load terminals when line voltage is applied.  
Protection Devices  
Metal Oxide Varistors (MOV)  
An MOV provides voltage surge protection. Voltage surges also called high voltage  
spikes are caused by a number of sources. Short duration high voltage spikes caused by  
starting and stopping other motor loads or switching On and Off capacitor banks may  
appear on the incoming lines. Transients can occur from lightning storms or from other  
lightly loaded devices on the same line, such as motors, transformers, or solenoids.  
Electrical noise can be caused by lightning, arc welders and heat exchange equipment on  
the same transformer bus line.  
An MOVs provide protection by absorbing or clamping these transient energy levels.  
High energy transients that exceed the MOV rating may damage the MOV and the  
multipurpose starter.  
1-4 General Information  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Snubber Network  
160 through 840 amp models only. A resistor and capacitor series circuit (snubber) is  
wired in parallel with each disk type SCR. The RC network enhances the electrical  
characteristics of the SCR and provides high voltage transient protection.  
Shorted SCR Detection: If a shorted SCR condition is detected while starting, running or stopping, the SHUNT  
TRIP contact will close and the SHUNT TRIP light will indicate the condition.  
The SHUNT TRIP contact is used to open the circuit breaker via a shunt trip device.  
Also, the shunt trip contact from the LCM module can be used to activate other circuit  
interrupting device to remove the motor and control from the AC power line.  
When a bypass contactor is used, the shunt trip circuit is disabled when the bypass  
contactor is closed. This is accomplished by switching switch BP S2-6 On.  
Over Current Shut Down: The control module has an over current detection circuit to trip and shut down the control  
if motor current exceeds 450% FLA. To restart, open the Close To Run circuit, then close  
it.  
Current Monitor:  
When the motor is at speed (End of Ramp light is “ON”), the current monitor can detect  
over current or overload motor conditions. This warning can alert an operator or be used  
to stop a motor. It can also be used for indications of jams or blockages.  
Motor Overload Protection: Class 30 motor overload protection is required to protect the control and the motor from  
repetitive or extended starting conditions, as well as running during an overload condition.  
Class 10 or 20 overloads may trip when starting high inertia loads or when operating in  
current limit starting mode.  
Over Temperature Switch: Power cells have over temperature switches to detect an overheating condition. The  
switch is an isolated bimetallic, normally closed contact. If loss of cooling causes a power  
cell to overheat, the temperature switch contact will open and shut down the control  
circuit.  
Note: When a temperature switch opens, the control shuts down. It must be reset  
manually to restart the control.  
Figure 1-3 Starter Diagram  
L1  
L2  
Combination Starter  
L3  
Non-Combination Starter  
Circuit  
Breaker or  
Fusible  
Soft  
Start  
Overload  
Relay  
Control  
Disconnect  
(Control only)  
MN894  
General Information 1-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configurations  
Control Only: Soft start control, without motor overload protection or branch circuit  
protection circuit breaker or fusible disconnect switch. Suitable for installation with a  
series contactor or as a retrofit for an existing motor starter.  
Non-combination Starter: Soft start control with motor overload protection, less branch  
circuit protection circuit breaker or fusible disconnect switch. Installation with existing  
branch circuit protection would use this configuration.  
Combination Starter: Soft start control with motor overload protection and branch circuit  
protection and branch circuit protection circuit breaker or fusible disconnect switch. Only  
push buttons are required to complete the system. New installations with no existing  
control equipment would use this configuration.  
Bypass System, Control Only: Soft start control without overload protection and branch  
protection. Includes a bypass contactor to shunt the power cells after the control is in the  
full run mode to eliminate heat generation across the power cells. Allows installation in a  
NEMA 4 or NEMA 12 enclosure.  
Bypass System, Non-combination: Soft start control noncombination system with  
motor overload protection, less branch circuit protection. Includes a bypass contactor to  
shunt the power cells after the starter is in the full run mode to eliminate heat generation  
across the power cells. Allows installation in a NEMA 4 or NEMA 12 enclosure.  
Bypass System, Combination: Soft start control combination system with motor  
overload protection and branch circuit protection circuit breaker or fusible disconnect  
switch. Includes a bypass contactor to shunt the power cells after the starter is in the full  
run mode to eliminate heat generation across the power cells. Allows installation in a  
NEMA 4 or NEMA 12 enclosure.  
Enclosures and Ventilation: Soft start controls are available in panel mount or in NEMA  
type 1, 12, 3R enclosures. The control will generate approximately 3.3 watts of heat per  
running ampere during operation. All factory supplied enclosures are designed to  
dissipate this heat under maximum specified operating conditions. If the multipurpose  
control is mounted in an enclosure not supplied by the factory, this heat dissipation must  
be considered. Adequate ventilation or convection cooling should be provided unless a  
bypass contactor is used.  
Panel Mount: Soft start control mounted on a panel with provisions for wall or enclosure  
installation.  
NEMA Type 1 (IP23): Soft start control mounted in a ventilated NEMA type 1 panel  
enclosure. Intended for indoor use primarily to provide a degree of protection against  
contact with enclosed electrical components. Available for all sizes and configurations.  
NEMA 12/3R (IP65/IP32): NEMA 12 enclosure provides protection from dust, dirt, oil  
and water. NEMA 3R outdoor installation protects from rain, sleet and snow. A NEMA  
12/3R is shipped as a NEMA 12 and to convert to NEMA 3R, remove the drain screw at  
the bottom of the enclosure.  
1-6 General Information  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Limited Warranty  
For a period of two (2) years from the date of original purchase, BALDOR will  
repair or replace without charge controls and accessories which our  
examination proves to be defective in material or workmanship. This  
warranty is valid if the unit has not been tampered with by unauthorized  
persons, misused, abused, or improperly installed and has been used in  
accordance with the instructions and/or ratings supplied. This warranty is in  
lieu of any other warranty or guarantee expressed or implied. BALDOR  
shall not be held responsible for any expense (including installation and  
removal), inconvenience, or consequential damage, including injury to any  
person or property caused by items of our manufacture or sale. (Some  
states do not allow exclusion or limitation of incidental or consequential  
damages, so the above exclusion may not apply.) In any event, BALDOR’s  
total liability, under all circumstances, shall not exceed the full purchase  
price of the control. Claims for purchase price refunds, repairs, or  
replacements must be referred to BALDOR with all pertinent data as to the  
defect, the date purchased, the task performed by the control, and the  
problem encountered. No liability is assumed for expendable items such as  
fuses.  
Goods may be returned only with written notification including a BALDOR  
Return Authorization Number and any return shipments must be prepaid.  
MN894  
General Information 1-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Safety Notice  
This equipment contains voltages that may be as high as 600 volts! Electrical shock can  
cause serious or fatal injury. Only qualified personnel should attempt the start-up  
procedure or troubleshoot this equipment.  
This equipment may be connected to other machines that have rotating parts or parts  
that are driven by this equipment. Improper use can cause serious or fatal injury. Only  
qualified personnel should attempt the start-up procedure or troubleshoot this equipment.  
PRECAUTIONS  
WARNING: Do not touch any circuit board, power device or electrical connection before you  
first ensure that power has been disconnected and there is no high voltage present  
from this equipment or other equipment to which it is connected.  
Electrical shock can cause serious or fatal injury.  
WARNING: Be sure that you are completely familiar with the safe operation of this equipment.  
This equipment may be connected to other machines that have rotating parts or  
parts that are controlled by this equipment. Improper use can cause serious or  
fatal injury. Only qualified personnel should attempt the start-up procedure or  
troubleshoot this equipment.  
WARNING: Be sure the system is properly grounded before applying power. Do not apply AC  
power before you ensure that all grounding instructions have been followed.  
Electrical shock can cause serious or fatal injury.  
Caution:  
To prevent equipment damage, be certain that the electrical service is not capable  
of delivering more than the maximum line short circuit current amperes listed for  
the control rating.  
Caution:  
Do not “Megger” test the motor while it is connected to the control. Failure to  
disconnect motor will result in extensive damage to the control. The control is  
tested at the factory for high voltage / leakage resistance as part of Underwriter  
Laboratory requirements. Do not megger any part of the control.  
Caution:  
Caution:  
Do not connect power factor correction capacitors to motor terminals. If power  
factor correction capacitors are necessary, contact Baldor.  
If a brake motor is used, the initial starting voltage may not be sufficient to release  
the brake. It may be necessary to provide separate power for the brake and soft  
start control.  
Caution:  
Caution:  
Do not connect AC incoming line power to the Motor terminals T1, T2 and T3.  
Connecting AC power to these terminals may result in damage to the control.  
Do not supply any power to the “Close To Run” terminals. Power on these leads  
can damage the control. Use a dry contact type that requires no external power to  
operate.  
Caution:  
Do not change the position of any switch while power is applied. Changing the  
position of a switch during operation can damage the control and cause erratic  
behavior of the load.  
Caution:  
Caution:  
To prevent equipment damage, be certain that the electrical service is not capable  
of delivering more than the maximum line short circuit current amperes rating.  
This equipment is shipped as a multipurpose apparatus. Before power is applied,  
the line voltage selection and the full load current calibration must be correctly set.  
Failure to select the proper line voltage or to calibrate the full load current may  
cause damage.  
1-8 General Information  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2  
Installation  
Receiving, Inspection and Storage  
When you receive your control, there are several things you should do immediately.  
1. Observe the condition of the shipping container and report any damage  
immediately to the commercial carrier that delivered your control.  
2. Remove the control from the carton. Inspect for shipping damage and report  
any damage immediately to your commercial carrier.  
3. Verify that the part number of the control you received is the same as the part  
number listed on your purchase order.  
4. If the control is to be stored for several weeks before use, be sure that it is  
stored in a location that is clean, dry and free from corrosives and  
contaminants. Storage temperatures must not exceed 140°F (60°C).  
Be sure to read an become familiar with the safety notices in Section 1 of this manual.  
Failure to observe the product safety notices can result in injury or equipment damage.  
If you have questions, please contact your Baldor distributor. Do not proceed unless you  
understand the installation and operation requirements and safety notices.  
Physical Location  
The location of the soft start control is important. It should be installed in an area that is  
protected from direct sunlight, corrosives, harmful gases or liquids, dust, metallic  
particles, and vibration. Exposure to these elements can reduce the operating life and  
degrade performance of the control.  
Several other factors should be carefully evaluated when selecting a location for  
installation:  
1. For effective cooling and maintenance, the control should be mounted vertically  
on a flat, smooth, non-flammable vertical surface. Heat dissipation of 3.3 watts  
per running FLA of the motor must be provided. All factory supplied enclosures  
provided adequate heat dissipation.  
2. If the control is mounted in an enclosure, sufficient air flow must be provided.  
The fan or blower must be rated for at least 0.8 cubic feet per minute for each  
ampere of motor FLA rating.  
3. Keep high voltage and low voltage wiring separated. If the conduits must  
cross, be sure that they cross at 90° angles only.  
1. Motor overload protection is required for starters that do not have an overload  
protection device.  
2. The multipurpose soft starter is suitable for use on a circuit capable of  
delivering no more than the short circuit ARMS listed in Table 2-1.  
3. A short circuit current and overcurrent devices are required for soft start  
controls that do not have a circuit breaker or fusible disconnect switch.  
AC Main Circuit  
Protection Devices  
Be sure a suitable input power protection device is installed. Use the recommended circuit  
breaker or fuses listed in Table2-1. Wire sizes and protective device specifications are based  
on the maximum output power rating of the control.  
Power Disconnect  
A power disconnect should be installed between the input power service and the control for  
a fail safe method to disconnect power. The control will remain in a powered-up condition until  
all input power is removed from the control and internal voltages are depleted.  
MN894  
Installation 2-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 2-1 Three Phase  
Fuse  
MCP (GE)  
Type  
Rating  
(AMPS)  
Short Circuit  
ARMS  
Short Circuit  
ARMS  
Amps  
Class  
Amps  
8
16  
30  
100  
100  
200  
100  
175  
175  
400  
400  
800  
800  
1200  
J
J
J
RK1  
J
J
RK5  
RK5  
L
L
L
5,000  
5,000  
5,000  
20  
20  
50  
5,000  
5,000  
5,000  
5,000  
50  
SELA  
SFLA  
SGLA  
SKLA  
55  
80  
42,000  
42,000  
100,000  
100,000  
100,000  
100,000  
100,000  
100  
100  
300  
300  
600  
600  
600  
10,000  
10,000  
42,000  
42,000  
42,000  
42,000  
42,000  
160  
250  
420  
600  
840  
Note: Maximum recommended fuses/breakers are based on 25°C ambient, maximum continuous current.  
Figure 2-4 Multipurpose Control Terminal Locations  
(A) Line Input  
(C) Control Connections  
(D) GND  
L1 L2 L3  
(D) GND  
T1 T2 T3  
(A) Motor Output Load  
2-2 Installation  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation  
1. Mount the panel or enclosure to the mounting surface. The panel or enclosure must be  
securely fastened to the mounting surface. Refer to the mounting dimensions in Section 6 of  
this manual.  
2. Ground the panel and control per NEC article 250 as well as state and local codes.  
3. Use copper wire rated for at least 75°C. Refer to Figure 2-4 and Table 2-2 for wire size  
recommendations.  
4. Connect the incoming AC power wires from the power disconnect and/or protection devices to  
5. * Connect earth ground to the “GND” of the control. Be sure to comply with local codes.  
6. Verify the input line voltage is correct.  
7. For MA#XX models, verify the line voltage selection jumpers on the LCM module are properly  
set. For MB#XX models, verify the control transformer primary taps are connected for the line  
voltage applied.  
8. Connect the three phase power leads of the AC motor to terminals T1, T2, and T3 of the Main  
Circuit Terminals.  
9. * Connect motor ground wire to the “GND” of the control. Be sure to comply with all applicable  
codes.  
Caution:  
Do not supply any power to the “Close To Run” terminals. Power  
on these leads can damage the control. Use a dry contact type that  
requires no external power to operate.  
*
Grounding by using conduit or panel connection is not adequate. A separate conductor of the  
proper size must be used as a ground conductor.  
Table 2-2 Recommended Wire Size and Tightening Torque  
Torque  
Wire Size  
Terminal  
Starter Rating  
2
lb-in  
Nm  
AWG  
10-16  
8
mm  
6-1.5  
10  
A
B
C
D
A
B
C
D
20  
35  
12  
2.5  
4
1.4  
5.1  
8, 16 and 30 AMPS  
12-22  
6-14  
Note 2  
Note 2  
12-22  
6-14  
4-0.34  
16-2.5  
Note 2  
Note 2  
4-0.34  
16-2.5  
45  
Note 1  
Note 1  
12  
Note 1  
Note 1  
1.4  
55 through 840 AMPS  
45  
5.1  
All wire sizes based on 75°C copper wire, 3% line impedance.  
Higher temperature smaller gauge wire may be used per NEC and local codes.  
Note1: Refer to the label on the equipment panel for line and load tightening torque values.  
Note2: Line and Load wires sizes for 55 through 840 AMP models are as follows:  
Wire Size  
AWG  
AMPS  
2
mm  
25  
55  
4
80  
3
30  
160  
250  
420  
600  
840  
3/0  
95  
185  
2x 150  
2x 240  
2x 240  
350 mcm  
2x 300 mcm  
2x 500 mcm  
3x 500 mcm  
MN894  
Installation 2-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Non-Motor and Special Motor Applications  
Non-motor load:  
The multipurpose control is designed to provide reduced starting voltage for standard  
three phase induction motors. The control may also start non-motor loads for controlled  
inrush current applications with resistive or inductive loads. Consult Baldor if the control  
is to be used with a non-motor load.  
Wye-Delta or  
Part Winding Starter:  
The multipurpose control can replace an existing wye-delta or part winding starter.  
Begin by removing the existing contactors. Wire the motor in its “RUN” delta  
configuration and connect the motor to the control. The control can be used as if it were  
controlling a standard design B motor.  
Wound Rotor Motors:  
High Slip Motors:  
Consult Baldor if the control is to be used with a wound rotor or slip ring type motor. This  
type of load produces high starting torque with reduced starting current and speed. The  
multipurpose control provides low starting current and low starting torque. The  
multipurpose control can be used for applications that do not require high starting torque  
and a continuous speed reduction.  
The multipurpose control can be used with high slip motors, such as design D. These  
motors are used with large inertial loads that require extended starting times. Reduced  
starting voltage will reduce the starting current and extend the starting time. Long starting  
times may require using slow trip overloads. However, the thermal capabilities of the  
motor and control must be evaluated before extending the overload trip times.  
Reversing Applications: For reversing applications, two multipurpose controls can be used or a reversing  
contactor can be used. Consult Baldor for more information.  
Multispeed Motors:  
Consult Baldor if the control is to be used with a multispeed motor. The control can  
be used with a multispeed motor if a multispeed starter is connected between the control  
and the motor. In this case, an additional MOV must be connected to the terminal side of  
the control. Switching is normally done be auxiliary contacts from the multispeed starter  
that are connected to the control circuit of the multipurpose control.  
Motors on Grounded and A multipurpose starter should not be used with “Delta” or “Open” ground systems.  
open delta systems:  
Without a proper ground, the circuit to detect a shorted SCR condition may malfunction or  
may not be able to detect a shorted SCR condition.  
2-4 Installation  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3  
Operation  
Types of Starting  
Voltage Starting (S2-4 = OFF)  
Voltage  
Ramp  
RU  
During start the initial voltage (TU) is set to a level where the  
motor will begin to turn when power is applied. The ramp time  
(RU) is adjustable to provide a smooth start. The pulse time  
(PT) is used for high friction loads to break loose “frozen” loads  
with up to 400% FLA.  
If a ramp down function is needed, the initial voltage TD setting  
is used to lower voltage to a level where the motor will begin to  
slow down when the stop button is pushed. Ramp down (RD)  
can only extend motor stopping time preventing sudden stopping  
problems such as water hammer.  
100  
PT  
TD  
75  
50  
CL  
% Line  
Voltage  
TU  
RD  
25  
0
Time  
Current Limit Starting (S2-5 = ON)  
Current  
Limit  
400  
PT  
If current limit starting is selected the starter will operate similar  
to voltage starting. On high inertia loads such as chippers and  
grinders the Current Limit (CL) setting is what determines the  
starting time. The starter will provide that current regardless of  
the ramp time setting. The CL setting must be high enough to  
provide enough starting current in all starting conditions. Ramp  
down (RD) can only extend motor stopping time preventing  
sudden stopping problems such as water hammer.  
300  
200  
% FLA  
CL  
RD  
100  
0
Time  
RUN  
Tach Feedback Starting (S2-4 = ON)  
Tach feedback starting/stopping uses a 0-10 VDC Tach signal.  
The control will provide voltage to the motor to generate a  
smooth linear starting even under cycling load conditions. Ramp  
down (RD) can only extend motor stopping time preventing  
sudden stopping problems such as water hammer.  
100  
Tach  
RD  
RU  
75  
50  
% Full  
Speed  
25  
0
Time  
MN894  
Operation 3-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start Adjustments (Refer to Figure 3-1).  
Ramp Up  
Ramp up time (RU) is adjustable from 3 to 50 seconds. RU adjusts the voltage ramp or  
the tachometer starting ramp time. For voltage starting, RU adjusts the time it takes the  
motor to reach full voltage. Actual acceleration time to full speed depends upon the  
motor load and the setting of the additional start adjustments.  
For Tach feedback starting, RU adjusts the motor starting time independent of the load  
when used with a 0 to 10 VDC tachometer feedback signal. Smooth linear speed ramp  
up with constant acceleration is achieved.  
Torque Up  
Pulse Time  
The initial starting torque (TU) for ramp up is enabled only in the voltage ramp mode.  
Usually set high enough to start the motor slowly turning the instant the start button is  
pressed.  
Starting pulse time (PT) is adjustable from 0 to 1.5 seconds in the voltage ramp mode.  
When the start button is pressed, the initial motor voltage depends on the setting of TU.  
One second after the start button is pressed, a pulse of approximately 400% FLA will  
occur; the duration will depend upon the setting of PT.  
Current Limit  
Current limit (CL) is adjustable from 75 to 400% of FLA. It can be used in both the  
voltage and tachometer ramp modes of operation. When CL is enabled (S2-5=ON),  
motor starting and stopping current will not exceed the set point of CL, except during PT.  
Note: CL must be set high enough to allow the motor to start under maximum load  
conditions. In the Tach feedback mode, CL will affect linearity and start and  
stop times. The current is held at the CL limit until the motor current  
decreases to less than the CL setting, regardless of the RU setting.  
Figure 3-1  
RU  
S
T
TU  
A
CL  
PT  
R
T
Stop Adjustments (Refer to Figure 3-2).  
Ramp Down  
Ramp downtime (RD) extends the stopping time from 5 to 50 seconds. RD can be used  
in both the voltage and tachometer modes.  
In the tachometer mode, when used with a 0 to 10 VDC tachometer feedback signal, RD  
will adjust the actual stopping time independent of motor load condition. Smooth linear  
speed ramp down with constant deceleration is achieved.  
In the voltage mode, RD adjusts the time it takes to reach minimum motor voltage and  
turn off. The actual stopping time will depend on the motor load condition.  
Note: Ramp down mode is not suitable for coasting or inertial loads that require  
braking. Ramp down will only extend the stopping time.  
Torque Down  
Torque down advance (TD) is adjustable from 0 to 100% advance. TD sets the initial  
torque or voltage which ramp down starts and can be used in both voltage and  
tachometer modes.  
In ramp down mode, when the stop button is pressed, voltage will immediately decrease  
to the set point of TD. Control will continue to ramp down to zero speed or voltage,  
depending upon RD setting, then the control will turn off.  
Figure 3-2  
S
RD  
T
O
P
TD  
3-2 Operation  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Run Adjustments (Refer to Figure 3-3).  
Current Monitor  
Current monitor set point (CM) is adjustable from 50 to 400% FLA to monitor the running  
current after the motor reaches the full run condition.  
With CM enabled (S2-2=ON), if the running current exceeds the CM set point, the control  
will shut down, the CUR MON contact will close, and the light will illuminate.  
With CM disabled (S2-2=OFF), if motor current exceeds CM set point, the control will not  
shut down, the CUR MON contact will close and the light will illuminate.  
Power Factor  
Power factor effect (PF) is adjustable from 0 to 100%. PF is used to adjust the maximum  
voltage applied to the motor under lightly loaded conditions to minimize motor current  
with minimum motor load.  
PF is enabled after the motor reaches full on condition.  
PF should be turned off (CCW) if more than one motor is used with one control or if a  
by-pass contactor is used.  
Note: PF adjustment has no effect in bypass mode.  
Figure 3-3  
R
U
N
CM  
PF  
MIN MAX  
Current Calibration Switch Refer to the multipurpose control Current Calibration Chart in Appendix A. Set switches  
S1 to the motor FLA rating. Calibration is based on the motor nameplate full load  
amperes (FLA), not necessarily actual running current. Motors with more than 6 times  
locked rotor current may require a higher setting to start properly.  
Operating Parameters Switch (Refer to Figure 3-4).  
Switches S2-1 thru S2-6 select the operating modes that best fit the application.  
S2-1 Ramp Down Disable (RDD).  
In the “On” position: When the stop button is pressed, the control will immediately turn off.  
User stop adjustments RD (ramp down time) and TD (ramp down initial starting torque)  
are disabled.  
In the “Off” position: When the stop button is pressed, the control will ramp down. In the  
voltage mode of operation, ramp down time depends on RD and TD settings and the load  
condition.  
S2-2 Current Monitor (CM) “On” position: If the motor running current exceeds the Current Monitor (CM) setting, the  
control will shut down. The shut down condition is indicated by the current monitor light  
and the closure of the current monitor contact. The current monitor is typically used to  
shut the control down when a jam occurs. To restart the control, press stop, then start; or  
open the close to run circuit, then close it.  
“Off” position: If motor running current exceeds the current monitor setting, the current  
monitor light and contact will indicate this condition but the control will not shut down.  
The current monitor can be used as an over and under current monitor.  
S2-3 Over Current Indicator (OC).  
“On” position: If an over current trip occurs (current exceeds 450% FLA), the control will  
shut down and the condition will be indicated by the OC light and CM light and the  
closure of the current monitor contact. To restart the control, press stop then start; or  
open the close to run circuit, then close it.  
“Off” position: An over current trip is indicated by the over current light and will not affect  
the current monitor. The control will shut down.  
MN894  
Operation 3-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
S2-4 Tachometer and Voltage Ramp Select (TACH)  
“On” position: The control is in the tachometer ramp mode during start and stop. Starting  
and stopping times are independent of the load conditions. Ramp up (RU) is dependent  
on the ramp up and current limit (CL) settings. RD is dependent on the RD and CL  
settings.  
Note: Current limit is disabled if S2-5 is “Off”. Operation in the tachometer mode  
requires an isolated input tach signal of 0 to 10 volts DC with a 10 msec  
response time or better. Tachometers with other voltage ranges may be used  
with this control. Consult the factory for instructions.  
If the tachometer full speed voltage is less than 10 volts DC, the starting and stopping  
times will be proportionally shorter. For example, if the starting and stopping times are  
adjusted to 20 seconds with a 0 to 10 volt DC tachometer signal; for a 0 to 5 Volt DC  
tachometer signal with the same setting, the time will be 10 seconds.  
“Off” position: The control is operating in the voltage ramp mode during start and stop (if  
ramp down is selected using S2-1). All user settings for start, stop and run can be used  
to set up the control to meet the application requirements. Starting and stopping times  
are dependent on the actual load condition and control settings.  
S2-5 Current Limit Enable (CL)  
“On” position: Starting and stopping current will not exceed the setting of the current limit  
setting, except during PT, if pulse start is being used. Current limit must be set high  
enough to allow the motor to start under maximum load conditions.  
“Off” position: Current limit is disabled. Maximum motor current is then limited by the  
over current shutdown circuit to 450% FLA, preset at the factory.  
S2-6 By-Pass Select (BP) “On” position: When the end of ramp contact closes, the circuit breaker shunt trip circuit  
(the Shunt Trip contact on the Multipurpose control module) is disabled after the starter is  
in the full run condition. This allows the use of a by-pass contactor without tripping the  
circuit breaker when the power cells are bypassed.  
“Off” position: the Shunt Trip circuit is enabled at all times.  
Figure 3-4  
RDD  
CM  
1
2
3
4
5
6
OC  
TACH  
CL  
BP  
S2 OFF ON  
3-4 Operation  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Control Connections (Refer to Figure 3-5).  
CLOSE TO RUN  
Close to Run terminals 12 and 13. Close to run contact must be closed to initiate ramp  
up and run. Close to Run contact must be opened to initiate ramp down to stop. Close to  
run contact must be dry and electrically isolated contact. If a voltage is applied to these  
terminals, the control may be damaged.  
When the Close to Run circuit is closed, the Start/Run light will be on and the contact will  
close. This normally open contact is typically used to seal in the start button circuit.  
START/RUN  
SHUNT TRIP  
Start/Run light and contact terminals 10 and 11. As long as the Closed to Run circuit  
remains closed, the Start/Run light and contact will remain activated. This condition also  
applies to an over current or a current monitor shutdown.  
Shunt Trip light and contact terminals 8 and 9. If the control detects a shorted SCR condition,  
the shunt trip light will be on and the contact will close. The shunt trip contact is used to  
operate a Shunt Trip device in the circuit breaker or similar disconnection means to remove  
the motor and controller from the line should a shorted SCR condition occur.  
The shunt trip circuit may also detect loss of phase or low voltage on a phase. The circuit  
may not work properly on grounded delta systems or open delta systems. The Shunt Trip  
circuit will trip when energized on single phase or an unbalanced line voltage.  
RAMP END  
Ramp End light and contact terminals 6 and 7. In the voltage or the tachometer modes,  
when the starting ramp is completed and the control is in the full run mode, the ramp end  
light will be on and the contact will close. The starting current limit is then disabled and  
CUR MON (running current monitor) is enabled.  
Note: Since most loads do not require full voltage and torque to reach full speed,  
when control is in the voltage ramp mode, the motor will reach full speed  
before the ramp end contact and light are activated. Ramp end will only be  
activated after the motor and control reach full voltage.  
The ramp end contact can be used to turn on other equipment. The ramp end contact  
can be used to close the bypass contactor to reduce heat dissipation of the SCRs.  
TACH  
Tachometer input terminals 4 and 5. The TACH input is used in the tachometer mode  
(S2-4=ON). The input required for TACH feedback is a 0 to 10 volt DC signal with a  
maximum 10 ms response time.  
MTR PWR  
CUR MON  
Motor Power light and contact at terminals 2 and 3. Indicates that voltage and current are  
supplied to the motor. If a current monitor or an over current shut down condition occurs,  
the contact is deactivated and the light is turned off.  
Current Monitor light and contact terminals 1 and 2. A user adjusted monitor. Maximum  
running current is adjustable from 50% to 400% FLA. Switch S2-2 controls the CM  
monitor.  
S2-2 “On” position: If motor current exceeds the CUR MON setting, the light will be on  
and the contact will close. In addition, the motor power and ramp end LEDs will be off  
and their contacts will open. The control will shut down. The Start/Run light will stay on  
and the contact will remain closed. Typically used to shut down the control in case of a  
mechanical jam. To restart a CUR MON shutdown, press stop then start; or open the  
close to run circuit, then close it.  
S2-2 “Off” position: If current exceeds the CUR MON setting, the light will be on and the  
contact will close for the duration of the over current. The control will not shut down. In  
this mode, the CUR MON monitor can be used as an over and under current monitor.  
Figure 3-5  
+
CUR  
MON  
MTR  
PWR  
Tach  
Ramp  
End  
SHUNT  
TRIP  
START  
/ RUN  
CLOSE  
TO RUN  
MN894  
Operation 3-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Indicators  
Power On  
The PWR light indicates that power is supplied to the internal power supply of the control.  
WARNING: If the power light is not illuminated, it does not necessarily mean  
that the line voltage is off. Electrical shock hazard may exist.  
Measure the voltage at the line terminals before service.  
Over Current  
Motor Current  
OC over current shutdown LED. If the control shuts down due to an over current  
condition (motor current is greater than 450% FLA), the OC light will be on. To restart the  
control, press stop, then start; or open the close to run circuit, then close it.  
The Motor Current display is a 10 segment bar graph representation of motor current  
from 0 to 400% FLA. Used to check ramp up, run and ramp down current conditions  
while the control is in operation.  
Summary of Start and Stop Sequences  
To Start the Motor: Close 12 - 13 (Close to Run) and the following occurs:  
1. 10 - 11 close to confirm start command.  
2. 2 - 3 close when power is applied to motor. Ramp up cycle begins.  
3. 6-7 close at the end of ramp up cycle.  
To Stop the Motor: Open 12 - 13 (Close to Run) and the following occurs:  
1. 10 - 11 open to confirm stop command.  
2. 6-7 opens immediately.  
3. 2 - 3 operation depend on ramp down mode selection:  
With Ramp Down: 2 - 3 opens when ramp down is complete.  
Without Ramp Down: 2 - 3 opens immediately.  
Shunt Trip: During normal operation, detection of a shorted SCR, misfiring SCR will  
cause the following:  
1. 8 - 9 close immediately.  
2. Shunt Trip light turns ON.  
3. The shunt trip breaker is immediately tripped and all power is removed from the  
control and motor.  
Note: The shunt trip breaker will only trip if it is connected to the shunt trip contact at  
terminals 8 & 9.  
3-6 Operation  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4  
Start-up  
Safety Notice  
Be sure to read and understand all notices, warning and caution statements in Section 1  
of this manual. If you have any questions about the safe operation of this equipment,  
please contact your Baldor representative before you proceed.  
Start-up Checklist  
Recommended Equipment  
Volt meter (20kW per volt or better, true RMS meter).  
Clamp on ammeter (5 times FLA full scale).  
Adjustment wand (provided with multipurpose soft start control).  
Overview  
The following adjustment procedures are examples and are intended to be used as a  
guideline to match motor starting characteristics to the load. Actual loads may be  
characterized by one or more of the examples. These procedures are intended to help  
you design your own procedure for your specific application.  
Keep in mind that reducing the starting current by one half will reduce the starting torque  
by one fourth. This will cause the motor to take four times longer to reach full speed. In  
situations where overloads tend to trip because of long starting times, increase the  
starting current and decrease the ramp up time (RU) to help eliminate nuisance trips.  
The potentiometer adjustments have a maximum span of 270°. Use the adjustment  
wand (provided) to adjust these devices and do not force the adjustments beyond their  
mechanical stops.  
Caution:  
This equipment is shipped as a multipurpose apparatus. Before power is applied,  
the line voltage selection and the full load current calibration must be correctly set.  
Failure to select the proper line voltage or to calibrate the full load current may  
cause damage.  
Switches S1 and S2 as well as all potentiometer adjustments are not factory preset.  
These will be set during the example procedures given in this section.  
Before you apply Power  
-
-
Verify the installation procedure has been performed correctly.  
Know if your application is one of the “Non-motor and Special Motor  
Applications” described in Section 2.  
-
-
Verify the wiring to the motor does not have any short circuits.  
Verify the motor is properly connected. Verify the voltage and full load amp  
rating on the motor nameplate.  
Note: A load must be connected to the control for testing. If the actual load cannot  
be connected, connect any small motor temporarily for testing.  
-
Verify that the control transformer is properly jumpered for the line voltage at  
your location. (MB#XXX models).  
-
Verify that the control module jumper is correctly set for the line voltage.  
(MA#XXX models).  
-
-
-
-
Set S1 to the motor nameplate FLA value.  
Set S2 for the type of application.  
Set potentiometers as suggested.  
Verify the overload setting corresponds to the full load current range on the  
calibration label.  
After you apply Power  
-
Verify the input voltage to the starter and the 115VAC from the control  
transformer (if a control transformer is installed).  
-
-
Verify the PWR light is on. (If not, refer to troubleshooting).  
Verify the shunt trip light is OFF. If it is ON, verify the motor is connected and  
all three motor phases are present. If the motor is connected and the shunt trip  
light is on, do not attempt to start the control. A short in the motor or wiring may  
exist.  
-
Perform the starting procedure for your application.  
MN894  
Start-up 4-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Set-Up  
1. Check continuity of the motor wiring and check for phase to phase and  
phase to ground short circuits.  
2. Connect the control wiring for your application.  
(Refer to section 2 for wire size and torque specifications).  
3. For MB#XXX models, verify the control transformer is set for the line voltage.  
For MA#XXX models, verify proper voltage jumper selection on LCM models.  
4. Calibrate S1. Refer to Appendix A for switch settings.  
Voltage Ramp Starting - (Fans or lightly loaded motors)  
5. Set for ramp up with ramp down as follows:  
S2-1 = OFF Ramp down disable  
S2-2 = OFF Current monitor  
S2-3 = OFF Over current shut down  
S2-4 = OFF Tachometer enable  
S2-5 = OFF Current limit enable  
S2-6 = OFF Bypass contactor  
Set RU, TU, PT and PF fully CCW.  
Set RD and RT at mid point.  
6. Set for ramp up with no ramp down as follows:  
S2-1 = ON  
Ramp down disable  
S2-2 = OFF Current monitor  
S2-3 = OFF Over current shut down  
S2-4 = OFF Tachometer enable  
S2-5 = OFF Current limit enable  
S2-6 = OFF Bypass contactor  
Set RU, TU, PT and PF fully CCW.  
Note: If the control OC trips, use Current Ramp Starting.  
Current Ramp Starting - (High inertial loads)  
8. Set for ramp up with ramp down as follows:  
S2-1 = OFF Ramp down disable  
S2-2 = OFF Current monitor  
S2-3 = OFF Over current shut down  
S2-4 = OFF Tachometer enable  
S2-5 = ON  
Current limit enable  
S2-6 = OFF Bypass contactor  
Set RU, TU, PT and PF fully CCW.  
Set RD and RT at mid point.  
9. Set for ramp up with no ramp down as follows:  
S2-1 = ON  
Ramp down disable  
S2-2 = OFF Current monitor  
S2-3 = OFF Over current shut down  
S2-4 = OFF Tachometer enable  
S2-5 = ON  
Current limit enable  
S2-6 = OFF Bypass contactor  
Set TU, PT, RD, TD and PF fully CCW.  
Set RU fully CW.  
Set CL to midpoint.  
4-2 Start-up  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Tach Feedback Starting  
11. Set for ramp up with ramp down as follows:  
S2-1 = OFF Ramp down disable  
S2-2 = OFF Current monitor  
S2-3 = OFF Over current shut down  
S2-4 = ON  
Tachometer enable  
S2-5 = OFF Current limit enable  
S2-6 = OFF Bypass contactor  
Set RU, TU, PT and PF fully CCW.  
Set RD and RT at mid point.  
12. Set for ramp up with no ramp down as follows:  
S2-1 = ON  
Ramp down disable  
S2-2 = OFF Current monitor  
S2-3 = OFF Over current shut down  
S2-4 = ON  
Tachometer enable  
S2-5 = OFF Current limit enable  
S2-6 = OFF Bypass contactor  
Set RU, TU, PT and PF fully CCW.  
WARNING: Be sure the system is properly grounded before applying power.  
Do not apply AC power before you ensure that all grounding  
instructions have been followed. Electrical shock can cause  
serious or fatal injury.  
WARNING: Improper operation of control may cause violent motion of the  
motor shaft and driven equipment. Be certain that unexpected  
motor shaft movement will not cause injury to personnel or damage  
to equipment. Certain failure modes of the control can produce  
peak torque of several times the rated motor torque.  
14. Confirm the Close to Run contact is open.  
15. Turn Power ON.  
16. Close the Run contact.  
17. The motor should just begin to rotate when power is applied and reach Ramp  
End in a minimum starting time. The control is properly set if the motor starts  
smoothly when power is applied and comes to speed as quickly as possible.  
Be sure CL is set high enough so the motor can start with a full load. The  
control is finished starting when the Ramp End light is ON.  
18. If motor operation is not correct, perform one or more of the following  
adjustments:  
If the motor  
Starts abruptly (jerks)  
Starts too slowly  
Starts too quickly  
Is connected to a high inertial  
load or a high slip motor is used  
Remedy  
Decrease TU by turning it CCW.  
Increase CL by turning it CW. Then decrease ramp time RU by turning it CW.  
Decrease CL by turning it CCW. Then increase ramp time RU by turning it CCW.  
It may be necessary to increase S1 setting to allow more motor current for faster  
starting.  
Is not starting properly  
Refer to detailed starting instructions for your application for more information on  
starting adjustments. Also, refer to start-up troubleshooting.  
MN894  
Start-up 4-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Starting Instructions  
Choose one of the following examples that best matches your application. Read the  
procedure and set the control according to the procedure or use the steps to develop  
your own procedure.  
Variable Load with Voltage Ramp (S2-2=OFF, S24=OFF)  
Typically used for non-inertial loads, loads that increase with speed and changing loads,  
such as axial fans and pumps.  
1. Set RU, TU, PT, RD, TD and PF fully counterclockwise CCW).  
2. Set CL and CM fully clockwise (CW).  
3. Adjust TU clockwise sufficiently to start load slowly moving at moment of  
switching.  
4. Adjust RU clockwise to achieve desired starting time with normal load  
conditions.  
Note: Proceed to “Running Adjustment Procedure” if ramp down is not used.  
5. Adjust TD clockwise sufficiently to cause the load to slow down soon after the  
stop button is pressed, with normal load conditions.  
6. Adjust RD clockwise to achieve desired stopping time with normal load  
conditions.  
Running Adjustment Procedure:  
After adjusting the starting and stopping characteristics, current monitor/trip (CM)  
and power factor adjustments can be made. If the power factor circuit is not used,  
turn the PF adjustment fully counterclockwise.  
Power Factor Correction Adjustment (PF):  
1. Use an ammeter to measure motor running current.  
2. With the motor at full speed, minimum load and the “Ramp End” light ON,  
adjust PF clockwise to minimize running current without oscillation. If there is  
no noticeable drop in current, repeat this step while measuring motor voltage.  
Current Monitor/Trip (CM):  
1. Set S2-2=OFF.  
2. Press start and allow the motor to reach full speed and the “Ramp End” light to  
turn ON.  
3. Adjust CM to desired threshold by observing the “CUR MON” light.  
4. The “CUR MON” contact can be used to indicates this threshold, or by setting  
the S2-2=ON, the starter will shut down. Press stop to reset the shutdown and  
trip condition.  
Post Adjustment Check List:  
1. Check fans for proper operation.  
2. If bypass contactor is used, check that the contactor is closing at Ramp End.  
3. Using a current probe, measure current on all three motor phases. Be sure the  
current is balanced during ramp on, run and ramp down.  
4. With the motor in run mode (Ramp End light “ON”), check phase current of all  
three phases. Currents should be balanced and within nameplate FLA.  
5. Measure the line voltage at the control during ramp up to ensure voltage does  
not drop below minimum operating voltage.  
4-4 Start-up  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
High Friction Load with Voltage Ramp (S2-2=OFF, S2-4=OFF)  
Typically used for loads that require high breakaway torque and low acceleration torque;  
i.e., conveyors in icy environment, equipment that resists starting due to lack of use,  
traction loads, etc.  
1. Set RU, TU, PT, RD, TD and PF fully counterclockwise (CCW).  
2. Adjust PT clockwise sufficiently to start load slowly moving at moment of  
switching.  
3. Adjust TU clockwise sufficiently to keep load moving after starting pulse.  
4. Adjust RU clockwise to achieve desired starting time with normal load  
conditions.  
Note: Proceed to “Running Adjustment Procedure” if ramp down is not used.  
5. Adjust TD clockwise sufficiently to cause the load to slow down soon after stop  
button is pressed, with normal load conditions.  
6. Adjust RD clockwise to achieve desired stopping time with normal load  
conditions.  
Running Adjustment Procedure:  
After adjusting the starting and stopping characteristics, current monitor/trip (CM)  
and power factor adjustment can be made. If the power factor circuit is not used,  
turn the PF adjustment fully counterclockwise.  
1. Use an ammeter to measure motor running current.  
2. With the motor at full speed, minimum load and “Ramp End” light on, adjust PF  
clockwise to minimize running current without oscillation. If there is no  
noticeable drop in current, repeat this step while measuring motor voltage.  
Current Monitor/Trip (CM):  
1. Press start and allow the motor to reach full speed and the “Ramp End” light to  
turn on.  
2. Adjust CM to desired threshold by observing the “CUR MON” light.  
3. The “CUR MON” contact can be used to signal this threshold, or by setting the  
S2-2=ON, the starter will shut down. Press stop to reset the shutdown and trip  
condition.  
Post Adjustment Check List  
1. Check fans for proper operation.  
2. If bypass contactor is used, check to ensure that the contactor is closing at  
Ramp End.  
3. Using a current probe, measure current on all three motor phases. Be sure the  
current is balanced during ramp up, run and ramp down.  
4. With the motor in run mode (Ramp End light “ON”), check phase current of all  
three phases. Currents should be balanced and within nameplate FLA.  
5. Measure the line voltage at the control during ramp up to ensure voltage does  
not drop below minimum operating voltage.  
MN894  
Start-up 4-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inertial Load (S2-1=ON, S2-4=OFF, S2-5=ON)  
Typically used on coasting and/or flywheel loads; i.e., chippers, centrifuges, compressors,  
crushers, chillers, band saws, centrifugal fans and blowers.  
Note: Ramp down and pulse start are not normally used with inertial loads.  
1. Set TU, PT, RD, TD and PF fully counterclockwise (CCW).  
2. Set RU approximately 90% clockwise.  
3. Set CL to midpoint.  
4. Set CM fully clockwise (CW).  
5. Adjust CL sufficiently to allow motor to reach full speed in desired time with  
maximum normal load.  
Running Adjustment Procedure:  
After adjusting the starting and stopping characteristics, current monitor/trip (CM)  
and power factor adjustment can be made. If the power factor circuit is not used,  
turn the PF adjustment fully counterclockwise.  
Power Factor Correction Adjustment (PF):  
1. Use an ammeter to measure motor running current.  
2. With the motor at full speed, minimum load and the “Ramp End” light ON,  
adjust PF clockwise to minimize running current without oscillation. If there is  
no noticeable drop in current, repeat this step while measuring motor voltage.  
Current Monitor/Trip (CM):  
1. Set S2-2=OFF.  
2. Press start and allow the motor to reach full speed and the “Ramp End” light to  
turn ON.  
3. Adjust CM to the desired threshold by observing the “CUR MON” light.  
4. The “CUR MON” contact can be used to signal this threshold, or by setting  
S2-2=ON, the starter will shut down. Press stop to reset the shutdown and trip  
condition.  
Post Adjustment Check List:  
1. Check fans for proper operation.  
2. If a bypass contactor is used, check that the contactor closes at ramp end.  
3. Using a current probe, measure current on all three motor phases. Be sure the  
current is balanced during ramp up, run and ramp down.  
4. With the motor in run mode (ramp end light “ON”), check phase current of all  
three phases. Currents should be balanced and within nameplate FLA.  
5. Measure the line voltage at the control during ramp up to ensure voltage does  
not drop below minimum operating voltage.  
4-6 Start-up  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Tachometer Mode (S2-4=ON, S2-5=OFF)  
Typically used for changing loads that require consistent starting and stopping times,  
independent of load condition, and pumping applications with severe head pressure to  
reduce water hammer; i.e., pumps, conveyors, stackers and other material handling  
equipment.  
1. Set RU, TU, PT, RD, TD and PF fully counterclockwise (CCW).  
2. Set CL and CM fully clockwise (CW).  
3. Adjust RU and RD for desired ramp up and ramp down time. RD is only  
effective with S2-1=OFF.  
Running Adjustment Procedure:  
After adjusting the starting and stopping characteristics, the current monitor/trip (CM)  
and power factor correction circuit (PF) can be adjusted. If the power factor circuit is  
not used, turn the PF adjustment fully counterclockwise.  
Power Factor Correction Adjustment (PF):  
1. Use an ammeter to measure motor running current.  
2. With the motor at full speed, minimum load and SSC “Ramp End” light ON,  
adjust PF clockwise to minimize running current without oscillation. If there is  
no noticeable drop in current, repeat this step while measuring motor voltage.  
Current Monitor/Trip (CM):  
1. Set S2-2=OFF.  
2. Press start and allow motor to reach full speed and the “Ramp End” light to turn  
ON.  
3. Adjust CM to the desired threshold by observing the “CUR MON” light.  
4. The “CUR MON” contact can be used to signal this threshold, or by setting the  
S2-2=ON, the starter will shut down. Press stop to reset the shutdown and trip  
condition.  
Post Adjustment Check List:  
1. Check fans for proper operation  
2. If a bypass contactor is used, check to ensure that the contactor closes at ramp  
end.  
3. Using a current probe, measure current on all three motor phases. Be sure the  
current is balanced during ramp up, run and ramp down.  
4. With the motor in run mode (ramp end light “ON”), check phase current of all  
three phases. Currents should be balanced and within nameplate FLA.  
5. Measure the line voltage at the control during ramp up to ensure voltage does  
not drop below minimum operating voltage.  
MN894  
Start-up 4-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start-up Troubleshooting The Multipurpose Control module has 7 LEDs to help diagnose problems. There is a  
summary of the functions and indications on pages 2-8 and 2-9. The Multipurpose starter  
was tested under load with all SCR and electronic functions checked before shipping.  
Note: To test the output of a soft starter a motor must be connected, even if it is a  
1/2 HP motor on a 700 HP starter. Be careful not to start large motors  
repeatedly without a cooling-down period.  
No Power To The Motor  
1. Verify the PWR light is “ON”.  
2. Verify the Start/Run light is “OFF” and confirm terminals 12-13 on the control  
module are open.  
3. Give the starter a start command by closing the start contact connected to  
terminals 12 and 13 (verify the Start/Run light is “ON”).  
If the Start/Run light is not ON, turn off power and connect terminals 12 and 13  
together with a small piece of wire as the jumper. Turn power ON. The  
Start/Run light should come “ON” then the MTR PWR light should come “ON”  
with power going to the motor.  
If this sequence occurs using the jumper, check the start circuit as to why it did  
not close the terminals 12-13. If this sequence did not occur, check the voltage  
going to the logic control module.  
Motor Does Not Start or Motor Does Not Come Up To Speed or  
The Motor Overload Overload Trips  
Adjust the “CL” to the max. If the motor is still not starting, set the S1 switch for  
current calibration to the max. for that control size. Setting the S1 switch to a higher  
setting only effects the calibration of light bar current indicator.  
Test:  
Try restarting the motor while adjusting the “CL” pot during starting. During starting,  
check that the incoming voltage is not dropping. If it fails to start at the max. S1  
setting, record the line voltage during starting, the motor data including the lock rotor  
amps and contact your local Baldor office.  
Circuit Breaker is Tripping On Power Up  
The circuit breaker supplied by Baldor is a motor circuit protector (MCP). It is also  
called an adjustable magnetic only breaker. This means it will only trip during a  
short circuit or instantaneous overcurrent condition. Baldor also adds a shunt trip  
module to the breaker. Isolate the problem by disconnecting the shunt trip circuit.  
Test for short circuit before re-energizing.  
Test:  
After the shunt trip circuit has been disabled, apply power. Check the shunt trip light,  
if it is “ON” it is detecting a shorted SCR, a loss of phase, a lack of a load or a  
grounded delta system. If the SCR’s have been replaced, they may be miswired.  
Do not attempt to start until the problem is found.  
4-8 Start-up  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Circuit Breaker is Tripping During Starting  
If the shunt trip light comes “ON” during starting it may detect a weak input phase.  
This is typical of grounded delta and open delta power systems. For proper  
operation, a four wire WYE system is recommended.  
If the shunt trip light is ON and it is determined that input power is correct and there  
is a motor load; Then, disable the shunt trip circuit and do an SCR resistance test.  
1. If the result of the SCR test shows the SCRE’s are in good condition, try  
restarting. If the shunt trip light comes ON again, check the line voltage for a  
weak phase.  
2. If the SCR’s test bad, find out why they failed.  
SCR’s fail due to high voltage. Is there a capacitor bank or a contactor in the  
circuit? Check MOV’s and line voltage. MOV’s may be shorted or open due to  
clearing of previous voltage spike.  
SCR’s fail due to high current or high temperature.  
a. Check the “T” leads for a phase to phase and phase to ground short  
circuit.  
b. Check the motor winding.  
c. Check the voltage balance of power supply. If one leg is going to 25 - 30%  
of nominal voltage or less during starting this will create high current on the  
other phases.  
d. Make sure the cooling fans are working and the ambient temperature is  
within specification.  
All Baldor starters are tested under load before shipping for proper SCR  
performance.  
OC light Comes ON Shutting “OFF” The Starter  
1. If it trips during starting it may mean that S2-5 (CL) needs to be set to “ON”. If it  
is already ON, be sure there are no capacitors or shorts in the motor leads.  
2. If it trips when the Ramp End light comes ON, make sure that S2-2 (CM) is  
“OFF” or current monitor level is set properly for a given load.  
3. The control will turn OFF any time motor current exceeds 450% of the S1  
current calibration setting.  
MN894  
Start-up 4-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4-10 Start-up  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5  
Troubleshooting  
Safety Notice  
Be sure to read and understand all notices, warning and caution statements in Section 1  
of this manual. If you have any questions about the safe operation of this equipment,  
please contact your Baldor representative before you proceed.  
Preliminary Checks  
Power Off Checks  
In the event of trouble, disconnect all input power to the control and perform these  
preliminary checks.  
1. Check all connections for tightness and signs of overheating.  
2. Check for cracked or damaged insulators and terminal blocks.  
3. Ensure the correct setting of the overload relay.  
4. Check the fuse in the control transformer.  
5. Perform the SCR resistance test for all SCR’s.  
6. If a shorted SCR is suspected, check for possible shorted connections, system  
grounds or any other condition which may cause the short circuit condition.  
7. Replace the SCR pack or power cell if no other causes were found. However,  
installing a new SCR pack or power cell without determining the cause of failure  
can result in repeated failure of the SCR’s. Refer to SCR replacement  
procedure in this manual.  
Blocking Voltage Check This check need only be performed if the resistance checks of the power cells or SCR  
packs (55 and 80 amps) are inconclusive.  
WARNING: Before power is applied to the control, be sure there is no danger to  
personnel or equipment if the motor shaft rotates when power is  
applied. A shorted SCR or damaged control can cause abnormal  
operation of the motor.  
1. Be sure power is off. Disconnect the load from the motor shaft if possible.  
2. The T1, T2 and T3 motor leads should be connected to the control for this test.  
3. Disconnect one of the wires at the shunt trip contact on the control to prevent  
operation of the disconnect circuit during this test.  
4. Apply power to the control.  
5. Measure the voltage from the line terminal to the load terminal on each of the  
power phases. The voltage should be about 0.58 times the input line to line  
voltage. If the voltage on any power cell or SCR pack is significantly less than  
this value, one or both SCR’s in the power cell or SCR pack may be shorted.  
6. Remove all power to the control.  
7. If a shorted SCR is suspected, check for possible shorted connections, system  
grounds or any other condition which may cause the short circuit condition.  
8. Replace the SCR pack or power cell if no other causes were found. However,  
installing a new SCR pack or power cell without determining the cause of failure  
can result in repeated failure of the SCR’s. Refer to SCR replacement  
procedure in this manual.  
MN894  
Troubleshooting 5-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SCR Tests  
If the SCR devices are suspected of failure, these tests can be used to test the SCR’s.  
1. Be sure power is off.  
Inspection  
2. Inspect power cell connections for tightness and signs of overheating.  
3. Replace snubber capacitors if there is any sign of oil or fluid leaking.  
Snubbers are not used on size 55 and 80 amp power cells.  
4. Inspect SCR clamp insulator for cracks.  
5. SCR clamps should be tightened evenly.  
(Use clamp gauge available from Baldor).  
6. Inspection and resistance test should be performed when system has  
experienced:  
Logic Control Module failure  
MOV failure  
Starting or running current imbalance  
SCR replacement  
Phase loss or single phasing  
7. Heat sinks and insulating surfaces must be clean and unobstructed.  
8. Size 55 and 80 amp power cells do not have snubber networks, SCR clamps or  
insulating base.  
Full Voltage Test  
After the motor reaches rated speed and the control is no longer in current limit, the  
SCR’s turn full on and deliver full voltage to the motor. When power factor correction  
(PF) is used, the control will reduce the voltage to the motor. For this reason, the PF  
1. Set the PF adjustment should be set fully CW (OFF) during this test.  
2. Turn power on. Wait for the motor to reach full speed.  
3. With the control in the run mode, measure the voltage across the line side to  
the load side on each control power cell or SCR pack. The voltage should be  
about 2 to 20 VAC. The voltage reading will vary depending upon the motor  
and the type of meter used. Voltage readings must be balanced on all three  
phases.  
4. If the voltage is higher across one or two power cells or SCR packs, not all  
SCR’s are firing properly.  
5. If all three cells or SCR packs have approximately the same voltage drop  
across line to load when the motor is up to speed and motor current is  
unbalanced, the cause is the motor or unbalanced line voltage.  
5-2 Troubleshooting  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Resistance Test  
Disconnect the power cell or SCR pack from all external wiring before you perform a  
resistance check. Use an ohmmeter with 20,000 ohms per volt or greater impedance for  
the resistance measurements. Refer to Table 5-1 and Figure 5-1.  
1. Be sure power is OFF.  
2. Remove all wiring from the power cell or SCR pack.  
3. Sizes 55 and 80 amps have three SCR packs, one for each phase mounted on  
a single ground potential heatsink. Check all three SCR packs. For example  
L-GL must be measured from L1-GL1, L2-GL2 and L3-GL3. Circuit SA-SB  
requires only one measurement.  
4. Sizes 160 through 840 amps have a separate power cell for each phase.  
Check all three power cells.  
5. If any of the resistance measurements are incorrect, the power cell or SCR  
pack should be repaired or replaced before operating the starter.  
Table 5-1  
Circuit  
L-A  
T-B  
Resistance  
Less than 5 Ohms  
SA-SB  
A-B  
L-GL  
T-GT  
Greater than 10k Ohms  
5 to 100 Ohms  
Note: Results from the resistance measurements can be satisfactory and the power  
cells may still be bad if the power cell is breaking down under voltage.  
If resistance checks are not conclusive, perform Blocking Voltage Check and SCR Full  
Voltage Test.  
Figure 5-1 Power Cell Configurations  
MN894  
Troubleshooting 5-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SCR Replacement  
SCR Polarity  
the locations of the tightening bars.  
Figure 5-2 SCR Polarity  
M420 / M600 / M840  
Cathode  
Terminals GT, T, GL and L.  
Tightening Bar  
Gate (White wire)  
Cathode (Red wire)  
White wire to GL terminal,  
Red wire to L terminal  
Anode  
Cathode  
White wire to GT terminal,  
Red wire to T terminal  
Tightening Bar  
Tightening Bar  
Anode  
Cathode  
White wire to GL terminal,  
Red wire to L terminal  
Tightening Bar  
White wire to GT terminal,  
Red wire to T terminal  
Cathode  
Anode  
Cathode  
Anode  
Terminals GT, T, GL and L.  
SCR Pressure Gauge  
Figure 5-3 SCR Tightening Pressure Gauge  
4°  
3°  
3°  
VE3000  
VE3000  
VE2500  
VE1000  
VE2000  
VE3500  
VE5500  
VE2500  
VE1000  
VE2000  
VE3500  
VE5500  
SCR Mounting Kit Number  
Calibration  
Calibration  
Tightening Bar  
Tightening Bar  
True Flat Surface  
Continued on next page.  
Surface Deflection Measurement  
5-4 Troubleshooting  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
1. Tighten the nuts evenly until finger tight.  
2. Tighten bolts in 1/4 turn increments.  
3. Use the SCR tightening pressure gauge and measure the deflection of the  
Tightening bar. The middle and both ends of the gauge must be in solid contact  
with the bar for an accurate reading. Correct pressure is indicated when the  
gauge notch for the tightening kit number align.  
Note: An anti-seize compound may be used on the bolt heads and threads to  
reduce the torque required to obtain the correct mounting pressure.  
Logic Control Module Resistance Test Refer to Figures 5-1 and 5-4.  
This test will verify resistance measurements within the control.  
1. Be sure power is OFF.  
2. Disconnect the logic module from all external wiring before conducting  
resistance checks.  
3. Use an ohmmeter with 20,000 ohms per volt greater.  
4. Compare the measured values with the values shown in Table 5-2.  
Table 5-2  
MB  
MB  
Line/Load  
Gates  
Control Power Input  
Circuit  
Resistance  
Circuit  
L1-GL1  
L2-GL2  
L3-GL3  
T1-GT1  
T2-GT2  
T3-GT3  
Resistance  
Circuit  
14-15  
16-17  
Resistance  
130 to  
180 Ohms  
L1-L2  
L1-L3  
L2-L3  
T1-T2  
T1-T3  
T2-T3  
L1-T1  
L2-T2  
L3-T3  
6.5 Ohms to  
8.5 Ohms  
MA  
Control Power Input  
Greater than  
500k Ohms  
Circuit  
14-15  
14-16  
14-17  
14-18  
Resistance  
220 - 240  
260 - 560  
615 - 910  
1150 - 1180  
Figure 5-4  
Logic Control Module  
L1 L2 L3  
T1 T2 T3  
MN894  
Troubleshooting 5-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Table 5-3 Troubleshooting Chart  
Cause  
Symptom  
Corrective Action  
Motor is not connected.  
ST contact on control is always closed.  
Improper input voltage.  
Shorted SCR.  
Control transformer (if equipped) set for wrong Change tap connections for correct voltage.  
voltage.  
Connect motor to T1, T2 and T3 of control.  
Repair or replace logic control module.  
Obtain the correct source voltage at L1, L2 and L3.  
Replace SCR or power cell.  
MCP trips as it is  
closed (also see  
Shunt Trip light  
comes ON)  
MCP trip setting is too low.  
Increase MCP Trip setting.  
Fix incoming power problem.  
Check terminal and motor wiring.  
Remove capacitors or move to line side of control.  
Replace logic control module.  
Verify S1 settings for motor nameplate FLA rating.  
Reduce PF adjustment (rotate CCW).  
Set S2-6 =ON to disable shunt trip while running.  
Check motor wiring.  
MCP trips as the  
motor is started  
(also see Shunt  
Trip light comes  
ON)  
Line voltage decreases during motor starting.  
Motor or wiring is defective.  
Capacitors on output of control.  
Logic control module is defective.  
Improper current calibration.  
PF set too high.  
Occasional line imbalance.  
Ground or motor fault.  
S2-6=ON but no bypass contactor is installed. Check setting of S2-6. Should be Off.  
MCP trips after  
the motor is  
running (also see  
Shunt Trip light  
comes ON)  
No line voltage.  
Overload is open.  
No contact closure across terminals 12 and 13. Check start circuit.  
Current trip occurs.  
Control module has no power.  
CL set too low.  
Restore line voltage.  
Reset overload.  
Starter does  
nothing when  
start button is  
pressed.  
Check S1 settings for correct current calibration.  
Check control transformer jumper.  
Increase CL adjustment (rotate CW).  
Control does not  
accelerate motor  
to full speed  
(Stalls)  
Line voltage decreases to less than minimum  
operating voltage during motor starting.  
Fix incoming power regulation problem.  
Improper current feedback.  
CL set too low.  
Verify S1 settings for motor nameplate FLA rating.  
Increase CL adjustment (rotate CW).  
Insufficient torque  
available from  
current limit CL.  
Motor  
accelerates too  
slowly.  
Ramp up (RU) time set too long.  
Improper current feedback.  
Decrease RU (rotate CCW).  
Verify S1 settings for motor nameplate FLA rating.  
Current limit (CL) set too high.  
Ramp up time (RU) set too short.  
Initial pulse time (PT) set too long.  
Improper current feedback.  
Reduce CL (rotate CCW).  
Increase RU (rotate CW).  
Reduce PT (rotate CCW).  
Verify S1 settings for motor nameplate FLA rating.  
Motor  
accelerates too  
quickly.  
Light or no load (is dependent on motor load). Decrease TU, increase RU or install tachometer.  
A lightly loaded motor will reach full speed with  
low starting current or voltage. Motor may  
require the use of a tachometer.  
Motor current  
and voltage  
oscillates after  
start  
Power factor correction set too high.  
Reduce PF setting (rotate CCW) until oscillation  
stops.  
Line voltage decreases to less than minimum  
operating voltage during motor starting.  
Single phasing due to an open phase.  
Fix incoming power regulation problem.  
Check wiring and overload heaters.  
Motor is noisy or  
vibrates when  
starting  
Single phasing or unbalanced current due to a Check for shorted SCR and replace.  
non-firing SCR.  
Single phasing or unbalanced current due to a Repair or replace the logic control module.  
defective logic control module.  
Defective motor.  
Check motor for shorts, opens or grounds.  
5-6 Troubleshooting  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Table 5-3 Troubleshooting Chart Continued  
Symptom  
Cause  
Corrective Action  
Incorrect heater size or setting.  
Loose or burned heater.  
Check overload relay heater table in Appendix A.  
Tighten or replace heater.  
Long starting time. (high inertia loads may  
Evaluate the thermal capabilities of the motor  
Overload relay  
require slow trip overloads.  
before extending the overload trip time.  
trips when starting  
Mechanical failure within the load.  
Single phasing or unbalanced start circuit.  
Excessive starting time (CL too low).  
Incorrect heater size or setting.  
Check machinery for binding or excessive loading.  
Refer to “Motor is noisy or vibrates when starting”.  
Increase CL (rotate CW).  
Check overload relay heater table in Appendix A.  
Tighten or replace heater.  
Check machinery for binding or excessive loading.  
Refer to “Motor is noisy or vibrates when starting”.  
Use ambient compensated overload relay.  
Decrease RD (rotate CW).  
Loose or burned heater.  
Overload relay  
trips when running  
Mechanical failure within the load.  
Single phasing or unbalanced start circuit.  
Ambient temperature too high.  
Motor decelerates Ramp down time (RD) set too short.  
too quickly  
(RDD=OFF)  
Motor decelerates Ramp down time (RD) set too long.  
Decrease RD (rotate CCW).  
too slowly  
(RDD=OFF)  
Erratic operation  
Loose connections.  
Check all connections.  
No load attached.  
Loss of phase or low input voltage to starter.  
Bad or misfiring SCR.  
Connect a motor to T1, T2 and T3 terminals.  
Repair the input voltage problem.  
Check resistance and replace SCR if defective.  
Shunt trip is not effective.  
Grounded delta power source.  
Shunt trip light  
comes ON  
Note: If the MCP is tripping, remove the relay or disconnect the wires from terminals 8 and 9.  
You can then determine if the MCP is tripping or if the module is opening the MCP.  
MN894  
Troubleshooting 5-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The control panel is intended to provide years of trouble free service with appropriate  
cooling and protection from the elements. Should trouble occur, refer to the appropriate  
control manual for control and motor troubleshooting information.  
Reset the Circuit Breaker If the circuit breaker is tripped, it must be reset to restore power. The breaker is tripped if  
Before the breaker is reset, locate the source of electrical trouble.  
1. Check for phase-to-phase and phase-to-ground shorts.  
2. Check for loose connections at power connectors (L1, L2, L3 and Earth as well  
as T1, T2, T3 and Motor Ground).  
to the “Reset” position then move the handle to the “ON” position to restore  
power. (In the “Reset” position, a click sound will be heard.)  
4. Verify that an overcurrent condition is tripping the circuit breaker (not a shunt  
trip). If the circuit breaker shunt trip was energized, the trip was caused by the  
LCM soft start module shunt trip feature. Eliminate the cause of the shunt trip.  
Figure 5-5 Magnetic Circuit Breaker  
ON  
Tripped  
OFF  
Reset  
Handle  
Shunt Trip Device  
Manual Trip  
Rating Plug  
Trip Level  
Shunt Trip Wires to  
LCM soft start module  
5-8 Troubleshooting  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
the “Tripped” position.  
1. Verify that the overload condition has been cleared to allow restart.  
2. Verify motor lead connections are tight.  
3. Allow time for the overload to cool.  
Figure 5-6 Overload Relay  
Reset  
Reset  
Button  
Button  
Fuse Replacement  
If the control circuit voltage drops to zero volts, the control power transformer fuses  
1. Check for line-to-ground short circuit condition and repair if necessary.  
2. Check control wiring and control devices (timers, relays, terminal blocks, wire  
terminations, etc.) for signs of damage, overheating, or loose connections and  
repair if necessary.  
3. Replace the fuse with the same fuse class, type, rating and interrupting  
capacity.  
Figure 5-7 Control Transformer with Fuses  
MN894  
Troubleshooting 5-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
5-10 Troubleshooting  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 6  
Specifications and Product Data  
Identification  
Three Phase Starters  
*  
*
M B 7 030 C B  
Control Type  
Bypass Contactor  
M- Multipurpose  
0 Normally not shown unless a  
reduced size bypass is used.  
A First size smaller bypass.  
B Second size smaller bypass.  
C Third size smaller bypass.  
Control Group  
A - Self powered logic control module  
B - Logic control modules that require  
115 or 230VAC.  
Input Voltage Code  
Disconnect Size  
7-  
8-  
MA9-  
MB9-  
208/230/460VAC (60Hz)  
230/460/575VAC (60Hz)  
220/380/415 (50Hz)  
0 Normally not shown unless a  
reduced size disconnect is used.  
1 Reduced size disconnect used:  
i.e. 800 amp breaker on a 840amp  
control instead of a 1000 amp  
breaker.  
380/400/415VAC (50Hz)  
Ampere Rating  
008- 8 Amp  
016- 16 Amp  
030- 30 Amp  
055- 55 Amp  
080- 80 Amp  
160- 160 Amp  
250- 250 Amp  
420- 420 Amp  
600- 600 Amp  
840- 840 Amp  
Enclosure  
A- Open  
B- NEMA1 (IP32)  
C- NEMA12 (IP65)  
P- Panel Mount  
Configuration  
A - Combination with overload & circuit  
breaker).  
B - Non-combination (with overload).  
C - Starter only.  
D - Combination with fuse disconnect.  
G - Bypass, combination starter.  
H - Bypass, non-combination starter.  
J - Bypass, starter only.  
K - Bypass combination starter with  
fuse disconnect.  
MN894  
Specifications and Product Data 6-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Multipurpose Control Specifications  
Three Phase Starters  
Input  
Voltage  
VAC  
MA7-008  
MA8-008  
MA7-016  
MA8-016  
MA7-030  
MA8-030  
HP  
I
C
HP  
I
C
HP  
I
C
3PH 60Hz  
230  
460  
575  
2
8
5
5
10  
20  
25  
10  
10  
8
16  
30  
Input  
Voltage  
VAC  
MB7-055  
MB8-055  
HP  
MB7-080  
MB8-080  
HP  
MB7-160  
MB8-160  
HP  
MB7-250  
MB8-250  
MB7-420  
MB8-420  
MB7-600  
MB8-600  
MB7-840  
MB8-840  
I
C
I
C
I
C
HP  
I
C
HP  
I
C
HP  
I
C
HP  
I
C
3PH 60Hz  
208  
230  
460  
575  
15  
20  
40  
50  
25  
30  
60  
75  
50  
60  
75  
150  
150  
350  
400  
200  
250  
500  
600  
100  
200  
250  
300  
700  
800  
55  
80  
160  
250  
420  
600  
840  
125  
150  
I = Continuous Current Rating  
C
Input Ratings  
Input Frequency  
Input Voltage  
Overload Rating  
Phase  
60/50 HZ ± 5%  
+10% to 15% of Voltage Rating (except 575 VAC, max= 620VAC)  
Continuous 115% of FLA; 400% for 30 seconds.  
Three Phase  
Continuous  
Duty  
Storage Conditions  
Ambient Temperature:  
Humidity:  
-4 to 140°F (-20 to 60 °C)  
0 - 95% RH Non-Condensing  
Operating Conditions  
Enclosure:  
Open Panel  
NEMA 1  
NEMA 12  
NEMA 4  
(Indoor)  
(Industrial indoor, general purpose)  
(Industrial indoor, dust proof)  
(Outdoor)  
The SCR’s generate about 3.3 watts of heat per running amp (motor FLA). If the control  
is mounted in an enclosure, the installer must provide fans or blower with sufficient ventila-  
tion. Fan or blower should be rated for at least 0.8 CFM per ampere of motor FLA rating.  
Baldor provided enclosures are designed to dissipate the heat from the SCR’s.  
Humidity:  
0 - 95% RH Non-Condensing  
Control Heat Loss  
3.3 Watt per running ampere of input current  
Ambient Operating Temperature:  
32-113°F (0 to +45 °C) enclosed  
32-122°F (0 to +50 °C) open panel  
Altitude:  
Derating  
Sea level to 3300 Feet (1000 Meters)  
Derate 1% per 330 Feet (100 Meters) above 3300 Feet  
Derate Amp rating 1% per 330 Feet (100 Meters) above 3300 Feet  
Derate Amp rating 1.5% per °C over 45 °C to 55 °C Max  
6-2 Specifications and Product Data  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Specifications  
Control Method  
6 SCR’s connected in inverse parallel for full-wave 3 phase control  
Peak Inverse Voltage  
208/230  
460  
575  
1200VAC minimum  
1200VAC minimum  
1600VAC  
Start Time  
Adjustable range 3-50 seconds (current limit starting is not timed).  
Adjustable range 5-50 seconds (can only extend stop time).  
Adjustable range: Starting 40-75%, Stopping 0-100%.  
Adjustable range 75-400% of FLA (full load amperes).  
Adjustable range 0.1-1.5 seconds.  
Stop Time  
Initial Torque  
Current Limit (Selectable)  
Pulse Time (Selectable)  
Current Monitor (Selectable)  
Adjustable range 50-400% of FLA. Causes contact closure or control shut  
down when current level is reached (after starting).  
Power Factor  
Adjustable for maximum reduced motor voltage, dependent on load.  
0-10VDC (maximum 10msec response time from tach).  
12VA at 115/230VAC ±5%  
Tach input (Selectable)  
Control module power  
Status Contacts  
125VAC at 0.5A, normally open. 60VA maximum rating.  
UL (Underwriters Laboratory) and cUL (Canada)  
40 °F to +140 °F (40 °C to +60 °C)  
Agency Listings  
Rated Storage Temperature:  
Note: A minimum inductance of 0.01 Henry is require for the SCR’s to commutate. Some large horsepower motors may  
not have enough inductance and require adding inductors between the motor and control.  
SCR Specifications  
Overcurrent  
Over current shut down at 450% of motor FLA nameplate rating.  
Shunt Trip contract.  
Shorted SCR detection  
Protective Features  
Overload  
Electronic overload class 30.  
SCR Thermostat  
Phase Loss  
Trips on overtemperature of heatsink (sizes 55 amps and larger only).  
Shunt Trip contact (sizes 55 amps and larger only) active only at power-up.  
MOV (metal oxide varistor).  
Voltage Transient  
Indicator LEDs  
Power ON  
Ramp End  
Shunt Trip  
Start/Run  
Over Current  
Current Monitor  
Motor Power  
Motor Current  
MOV Devices Four varistors connected in wye configuration with one to ground.  
MOV505EL  
Max line volts=510VAC  
Watts = 1.0  
MOV620E  
Max line volts=625VAC  
Watts = 1.0  
Max one time surge of 6500A @ 8V/20ms  
Max one time surge of 6500A @ 8V/20ms  
MN894  
Specifications and Product Data 6-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wire Size & Tightening Torque Specifications  
8, 16 Amp Control Only  
Combination Starter and Non-Combination Starter  
and Control Only  
TB1  
Line Input  
Line Input  
(A)  
(C)  
Control Connections  
(B)  
(D)  
GND  
(C)  
(D)  
GND  
GND  
OR  
GND  
Control  
(D)  
Motor Output Load  
(A)  
(D)  
(B)  
Motor Output Load  
Wire Size Torque Specifications Size 8,16  
Terminal  
Amps  
Wire Size  
Torque  
(Identifier)  
AWG  
10 - 16  
8 - 18  
lb-in  
Note1: Refer to the label on the  
equipment panel for line and  
load tightening torque values.  
A
B
8, 16  
30  
20  
35  
55  
80  
4
3
3/0  
Note 1  
Note 1  
Note 1  
Note 1  
Note 1  
Note 1  
Note 1  
12  
Note2: Refer to the label on the  
equipment panel for ground  
wire sizes.  
160  
250  
420  
600  
840  
All  
350 KCMIL  
(2) 300 KCMIL  
(2) 500 KCMIL  
(3) 500 KCMIL  
12 - 22  
6-14  
C
D
8, 16, 30  
55  
45  
Note 2  
Note 2  
Note 2  
Note 2  
Note 2  
Note 2  
Note 2  
Note 1  
Note 1  
Note 1  
Note 1  
Note 1  
Note 1  
Note 1  
80  
160  
250  
420  
600  
840  
6-4 Specifications and Product Data  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mounting Dimensions  
Open Panel  
B
d
Dia  
h
A
w
Open/Panel Dimensions  
Amp  
Rating  
Control Only  
Non-Combination Starter  
Combination Starter  
A
B
h
w
d
Dia  
A
B
h
w
d
Dia  
A
B
h
w
d
Dia  
8
16  
30  
55  
12.25 10.25 11.63 9.63 10.16 0.25 21.00 14.50 19.50 13.00 10.16 0.50 21.00 14.50 19.50 13.00 10.16 0.50  
12.25 10.25 11.63 9.63 10.16 0.25 21.00 14.50 19.50 13.00 10.16 0.50 21.00 14.50 19.50 13.00 10.16 0.50  
12.25 10.25 11.63 9.63 10.16 0.25 21.00 14.50 19.50 13.00 10.16 0.50 21.00 14.50 19.50 13.00 10.16 0.50  
21.00 21.00 19.24 19.24 12.62 0.50 21.00 21.00 19.24 19.24 12.62 0.50 21.00 21.00 19.24 19.24 12.62 0.50  
21.00 21.00 19.24 19.24 12.62 0.50 21.00 21.00 19.24 19.24 12.62 0.50 21.00 21.00 19.24 19.24 12.62 0.50  
80  
160  
250  
420  
600  
840  
39.00 27.00 31.24 25.24 9.35  
0.50 39.00 27.00 31.24 25.24 9.35  
0.50 39.00 27.00 31.24 25.24 9.35  
0.50  
39.00 27.00 31.24 25.24 11.35 0.50 39.00 27.00 31.24 25.24 11.35 0.50 39.00 27.00 31.24 25.24 11.35 0.50  
45.00 33.00 43.24 31.24 13.35 0.50 45.00 33.00 43.24 31.24 13.35 0.50 45.00 33.00 43.24 31.24 13.35 0.50  
57.00 33.00 55.24 31.24 13.35 0.50 57.00 33.00 55.24 31.24 13.35 0.50 57.00 33.00 55.24 31.24 13.35 0.50  
57.00 33.00 55.24 31.24 13.35 0.50 57.00 33.00 55.24 31.24 13.35 0.50 57.00 33.00 55.24 31.24 13.35 0.50  
MN894  
Specifications and Product Data 6-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mounting Dimensions Continued  
NEMA 1, 3R and 12  
B
d
Dia  
h
A
w
NEMA 1 Dimensions  
Amp  
Rating  
Control Only  
Non-Combination Starter  
Combination Starter  
A
B
h
w
d
Dia  
A
B
h
w
d
Dia  
A
B
h
w
d
Dia  
8
16  
30  
55  
14.00 12.00 11.00 11.00 11.35 0.28 24.00 16.00 21.88 11.00 11.35 0.31 24.00 16.00 21.88 11.00 11.35 0.31  
14.00 12.00 11.00 11.00 11.35 0.28 24.00 16.00 21.88 11.00 11.35 0.31 24.00 16.00 21.88 11.00 11.35 0.31  
14.00 12.00 11.00 11.00 11.35 0.28 24.00 16.00 21.88 11.00 11.35 0.44 24.00 16.00 21.88 11.00 11.35 0.31  
24.00 24.00 25.24 18.00 12.62 0.44 24.00 24.00 25.24 18.00 12.62 0.44 24.00 24.00 25.24 18.00 12.62 0.44  
24.00 24.00 25.24 18.00 12.62 0.44 24.00 24.00 25.24 18.00 12.62 0.44 24.00 24.00 25.24 18.00 12.62 0.44  
80  
160  
250  
420  
600  
840  
42.00 30.00 37.24 24.00 9.35  
0.44 42.00 30.00 37.24 24.00 9.35  
0.44 42.00 30.00 37.24 24.00 9.35  
0.44  
42.00 30.00 37.24 24.00 11.35 0.44 42.00 30.00 37.24 24.00 11.35 0.44 42.00 30.00 37.24 24.00 11.35 0.44  
48.00 36.00 49.24 30.00 13.35 0.44 48.00 36.00 49.24 30.00 13.35 0.44 48.00 36.00 49.24 30.00 13.35 0.44  
60.00 36.00 61.24 30.00 13.35 0.44 60.00 36.00 61.24 30.00 13.35 0.44 60.00 36.00 61.24 30.00 13.35 0.44  
60.00 36.00 61.24 30.00 13.35 0.44 60.00 36.00 61.24 30.00 13.35 0.44 60.00 36.00 61.24 30.00 13.35 0.44  
NEMA 12/3R Dimensions  
Amp  
Rating  
Control Only  
Non-Combination Starter  
Combination Starter  
A
B
h
w
d
Dia  
A
B
h
w
d
Dia  
A
B
h
w
d
Dia  
8
16  
30  
55  
20.00 16.00 21.24 10.00 11.35 0.44 20.00 16.00 21.24 10.00 11.35 0.44 24.00 20.00 25.24 14.00 11.35 0.44  
20.00 16.00 21.24 10.00 11.35 0.44 20.00 16.00 21.24 10.00 11.35 0.44 24.00 20.00 25.24 14.00 11.35 0.44  
20.00 16.00 21.24 10.00 11.35 0.44 20.00 16.00 21.24 10.00 11.35 0.44 24.00 20.00 25.24 14.00 11.35 0.44  
30.00 24.00 31.24 18.00 11.35 0.44 30.00 24.00 31.24 18.00 11.35 0.44 30.00 24.00 31.24 18.00 11.35 0.44  
30.00 24.00 43.24 18.00 11.35 0.44 30.00 24.00 31.24 18.00 11.35 0.44 30.00 24.00 31.24 18.00 11.35 0.44  
80  
160  
250  
420  
600  
840  
42.00 36.00 43.24 30.00 9.35  
0.44 42.00 36.00 43.24 30.00 9.35  
0.44 42.00 36.00 43.24 30.00 9.35  
0.44  
42.00 36.00 43.24 30.00 11.35 0.44 42.00 36.00 43.24 30.00 11.35 0.44 42.00 36.00 43.24 30.00 11.35 0.44  
60.00 36.00 61.24 30.00 13.35 0.44 60.00 36.00 61.24 30.00 13.35 0.44 60.00 36.00 61.24 30.00 13.35 0.44  
60.00 48.00 61.24 42.00 13.35 0.44 60.00 48.00 61.24 42.00 13.35 0.44 60.00 48.00 61.24 42.00 13.35 0.44  
60.00 48.00 61.24 42.00 13.35 0.44 60.00 48.00 61.24 42.00 13.35 0.44 60.00 48.00 61.24 42.00 13.35 0.44  
6-6 Specifications and Product Data  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connection Diagrams  
MA Style 8, 16 and 30 AMP Combination and Non-Combination Starter and Control only  
(Three Wire)  
(Hand - Off - Auto)  
Two Wire  
Start  
Caution: Read Note  
Control Device  
H
Stop  
O
(Two Wire)  
Line Input  
A
R
L1  
L2  
L3  
TB1 11  
12 13  
14  
TB1 11 12 13 14  
TB1 11 12 13 14  
CB  
MOV  
X
F1  
F2  
A
A
B
B
F3  
A
B
115VAC  
OL  
15  
17 18  
14  
16  
95  
96  
13  
12  
11  
10  
9
8
7
6
5
4
3
2
1
Close  
To Run  
Start /  
Run  
60Hz  
50Hz  
Shunt  
Trip  
CB  
Shunt  
Trip  
97  
L1  
L2  
L3  
OL  
98  
Ramp  
End  
Tach  
Input  
T1  
T2  
T3  
MTR  
PWR  
CUR  
MON  
LCM  
CT Input  
20  
19  
Legend:  
CB -  
Shunt trip motor circuit protector or fuse disconnect.  
Caution:  
F1, F2 - Control transformer fuses.  
F3 - Control branch circuit fuse.  
LCM - Logic control module - type M.  
MOV - Metal oxide varistors.  
To avoid equipment damage, jumper  
terminal 14 to the appropriate terminal  
that matches the line voltage.  
OL  
OL -  
R -  
TB1 -  
X -  
Overload relay (electronic).  
Run relay (customer provided).  
Terminal block.  
LCM  
Terminals 60Hz  
Voltage  
50Hz  
14-15 208VAC 220VAC  
14-16 230VAC 380VAC  
14-17 460VAC 415VAC  
T1  
T2  
To Motor  
T3  
Control transformer (control voltage).  
14-18 575VAC  
−−  
Notes:  
Control transformer must be properly connected for line voltage (see transformer nameplate).  
Do not apply voltage to LCM terminals 12 and 13. Dry contact type only.  
Motor must be connected before power is applied. Otherwise, the shunt trip will will trip the motor circuit  
protector.  
Tachometer is only required when LCM is used in Tach Feedback mode.  
Motor circuit protector and this circuit are not provided with the noncombination starters, control only and fuse  
disconnect versions.  
MN894  
Specifications and Product Data 6-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connection Diagrams Continued  
MB Style 8, 16 and 30 AMP Combination and Non-Combination Starter and Control only  
(Three Wire)  
(Hand - Off - Auto)  
Two Wire  
Start  
Caution: Read Note ꢀ  
Control Device  
H
Stop  
O
(Two Wire)  
Line Input  
A
R
L1  
L2  
L3  
TB1 11  
12 13  
14  
TB1 11 12 13 14  
TB1 11 12 13 14  
CB  
MOV  
X
F1  
F2  
A
A
B
B
F3  
A
B
115VAC  
OL  
15  
17  
14  
14  
16  
95  
96  
13  
12  
11  
10  
9
8
7
6
Close  
To Run  
Start /  
Run  
230VAC  
15  
Shunt  
Trip  
CB  
Shunt  
Trip  
97  
L1  
L2  
L3  
OL  
17  
16  
98  
Ramp  
End  
5
4
3
2
Tach  
Input  
T1  
T2  
T3  
MTR  
PWR  
CUR  
MON  
LCM  
CT Input  
1
20  
19  
Legend:  
CB -  
Shunt trip motor circuit protector or fuse disconnect.  
F1, F2 - Control transformer fuses.  
F3 - Control branch circuit fuse.  
LCM - Logic control module - type M.  
MOV - Metal oxide varistors.  
OL  
OL -  
R -  
TB1 -  
X -  
Overload relay (electronic).  
Run relay (customer provided).  
Terminal block.  
T1  
T2  
To Motor  
T3  
Control transformer (control voltage).  
Notes:  
Control transformer must be properly connected for line voltage (see transformer nameplate).  
Do not apply voltage to LCM terminals 12 and 13. Dry contact type only.  
Motor must be connected before power is applied. Otherwise, the shunt trip will will trip the motor circuit  
protector.  
Tachometer is only required when LCM is used in Tach Feedback mode.  
Motor circuit protector and this circuit are not provided with the noncombination starters, control only and fuse  
disconnect versions.  
6-8 Specifications and Product Data  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connection Diagrams Continued  
MA Style 55 and 80 AMP NEMA 1 and Panels Combination and Non-Combination Starter and Control only  
(Three Wire)  
(Hand - Off - Auto)  
Two Wire  
Start  
Control Device  
H
Caution: Read Note ꢀ  
Line Input  
O
Stop  
A
L1  
L2  
L3  
2
5
8
10  
R1  
2
5
8
1
3
4
6
7
9
1
3
4
6
7
9
10  
TB1  
95  
96  
TB1  
CB  
OL  
13  
14  
MOV  
F3  
X
F1  
A
B
A
A
B
B
115VAC  
F2  
CF  
14 15 16 17 18  
9
5
R1  
R1  
13  
12  
11  
10  
9
Close  
To Run  
12  
8
L1  
L2  
L3  
GL1  
GL2  
GL3  
GT1  
GT2  
GT3  
T1  
PC1  
60Hz  
50Hz  
GL3  
GL2  
GL1  
GT3  
GT2  
GT1  
SB  
L3  
Start /  
Run  
L2  
L1  
T1  
T2  
T3  
SA  
SCR  
SCR  
SCR  
Shunt  
Trip  
8
7
6
5
13 14  
R2  
9
CB  
Shunt Trip  
Ramp  
End  
5
R2  
S
97 98  
Tach  
Input  
OL  
4
LCM  
MTR  
3
2
1
PWR  
CUR  
MON  
T2  
T3  
CT Input  
20  
19  
CT1  
OL  
Legend:  
CB -  
CF -  
Shunt trip motor circuit protector or fuse disconnect.  
Power cell cooling fan.  
Caution:  
T1  
T2  
To Motor  
T3  
To avoid equipment damage, jumper  
terminal 14 to the appropriate terminal  
that matches the line voltage.  
CT1 -  
LCM current transformer.  
F1, F2 - Control transformer fuses.  
F3 - Control branch circuit fuse.  
LCM - Logic control module - type M.  
MOV - Metal oxide varistors.  
LCM Voltage  
Terminals 60Hz 50Hz  
OL -  
Overload relay (electronic).  
14-15 208VAC 220VAC  
14-16 230VAC 380VAC  
14-17 460VAC 415VAC  
PC1 - SCR power cell.  
R1 -  
R2 -  
S -  
Run relay, DPDT.  
Shunt trip relay, DPDT.  
SCR overtemperature switch.  
14-18 575VAC  
−−  
SCR - Silicon controlled rectifier.  
TB1 -  
X -  
Terminal block.  
Control transformer (control voltage).  
Notes:  
Control transformer must be properly connected for line voltage (see transformer nameplate).  
Do not apply voltage to LCM terminals 12 and 13. Dry contact type only.  
Motor must be connected before power is applied. Otherwise, the shunt trip will will trip the motor circuit  
protector.  
Tachometer is only required when LCM is used in Tach Feedback mode.  
Motor circuit protector and this circuit are not provided with the noncombination starters and fuse disconnect  
versions.  
MN894  
Specifications and Product Data 6-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connection Diagrams Continued  
MB Style 55 and 80 AMP NEMA 1 and Panels Combination and Non-Combination Starter and Control only  
(Three Wire)  
(Hand - Off - Auto)  
Two Wire  
Start  
Control Device  
H
Caution: Read Note ꢀ  
Line Input  
O
Stop  
A
L1  
L2  
L3  
2
5
8
10  
R1  
2
5
8
1
3
4
6
7
9
1
3
4
6
7
9
10  
TB1  
95  
96  
TB1  
CB  
OL  
13  
14  
MOV  
F3  
X
F1  
A
B
A
A
B
B
115VAC  
F2  
CF  
14 15 16 17  
9
5
R1  
R1  
13  
12  
11  
10  
9
Close  
To Run  
12  
8
L1  
L2  
L3  
GL1  
GL2  
GL3  
GT1  
GT2  
GT3  
T1  
PC1  
GL3  
GL2  
GL1  
GT3  
GT2  
GT1  
SB  
230VAC  
L3  
Start /  
Run  
L2  
L1  
T1  
T2  
T3  
SA  
SCR  
SCR  
SCR  
14 15 16 17  
S
Shunt  
Trip  
8
7
6
5
13 14  
R2  
9
CB  
Shunt Trip  
Ramp  
End  
5
R2  
97 98  
Tach  
Input  
OL  
4
LCM  
MTR  
3
2
1
PWR  
CUR  
MON  
T2  
T3  
CT Input  
20  
19  
CT1  
OL  
Legend:  
CB -  
CF -  
Shunt trip motor circuit protector or fuse disconnect.  
Power cell cooling fan.  
T1  
T2  
To Motor  
T3  
CT1 -  
LCM current transformer.  
F1, F2 - Control transformer fuses.  
F3 - Control branch circuit fuse.  
LCM - Logic control module - type M.  
MOV - Metal oxide varistors.  
OL -  
Overload relay (electronic).  
PC1 - SCR power cell.  
R1 -  
R2 -  
S -  
Run relay, DPDT.  
Shunt trip relay, DPDT.  
SCR overtemperature switch.  
SCR - Silicon controlled rectifier.  
TB1 -  
X -  
Terminal block.  
Control transformer (control voltage).  
Notes:  
Control transformer must be properly connected for line voltage (see transformer nameplate).  
Do not apply voltage to LCM terminals 12 and 13. Dry contact type only.  
Motor must be connected before power is applied. Otherwise, the shunt trip will will trip the motor circuit  
protector.  
Tachometer is only required when LCM is used in Tach Feedback mode.  
Motor circuit protector and this circuit are not provided with the noncombination starters and fuse disconnect  
versions.  
6-10 Specifications and Product Data  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connection Diagrams Continued  
NEMA 1 & Panel Mounted Size 160840 AMP Control Only  
(Hand - Off - Auto)  
Two Wire  
Control Device  
Enclosure  
Fan  
(Three Wire)  
H
O
A
115VAC  
Line Starter  
Control Circuit  
(Line Switched)  
OL  
Start  
Enclosure  
Fan  
M
Stop  
OL  
Enclosure  
Fan  
1
2
3
4
5
6
7
8
9
10  
1
2
3
4
5
6
7
8
9
10  
OL  
TB1  
TB1  
Line Input  
TB1  
1
2
3
4
5
6
7
8
9
10  
R1  
Caution: Read Note ꢀ  
L1  
L2  
L3  
13  
14  
MOV  
F3  
X
F1  
A
B
A
A
B
B
115VAC  
F2  
R1  
9
5
CF  
15  
17  
14  
16  
CF  
CF  
R1  
13  
12  
11  
10  
9
8
7
6
5
4
3
2
1
Close  
To Run  
12  
8
PC1/L  
L1  
L2  
L3  
GL1  
GL2  
GL3  
GT1  
GT2  
GT3  
T1  
PC2/L  
PC3/L  
PC1  
Line  
PC2  
Line  
PC3  
Line  
Start /  
Run  
L1  
L2  
L3  
SC  
RS  
SC  
RS  
SC  
PC1/GL  
PC2/GL  
PC3/GL  
PC1/GT  
PC2/GT  
PC3/GT  
PC1/T  
L
L
L
GL  
GT  
T
SA  
SB  
Shunt  
Trip  
GL1  
GT1  
T1  
GL2  
GT2  
T2  
GL3  
GL  
GT  
T
SA  
SB  
GL  
GT  
T
SA  
SB  
GT3  
LCM  
RS  
Ramp  
End  
T3  
S
S
S
S1A  
S1B  
S2A  
S2B  
S3A  
Tach  
Input  
S3B  
MTR  
Load  
Load  
Load  
PC2/T  
PWR  
CUR  
MON  
T2  
T3  
PC3/T  
CT Input  
20  
19  
CT1  
CT2  
Legend:  
CF -  
CS -  
CT1 -  
CT2 -  
Power cell cooling fan.  
Snubber capacitor.  
LCM current transformer.  
OL -  
Overload relay (electronic).  
T1  
T2  
To Motor  
T3  
PC1,2,3 - SCR power cells.  
R1 -  
RS -  
S -  
Run relay, DPDT.  
Snubber resistor.  
SCR overtemperature switch.  
CT1  
Primary current transformer.  
MBX140 = 8 Turns  
MBX160 = 8 Turns  
MBX250 = 4 Turns  
MBX420 = 4 Turns  
MBX600 = 4 Turns  
MBX840 = 4 Turns  
F1, F2 - Control transformer fuses.  
F3 - Control branch circuit fuse.  
LCM - Logic control module - type M.  
M -  
SCR - Silicon controlled rectifier.  
TB1 -  
X -  
Terminal block.  
Control transformer (control voltage).  
MOV - Metal oxide varistors.  
4 Turns (3 Loops)  
Notes:  
Control transformer must be properly connected for line voltage (see transformer nameplate).  
Do not apply voltage to LCM terminals 12 and 13. Dry contact type only.  
Number of cooling fans depends on the FLA rating.  
Tachometer is only required when LCM is used in Tach Feedback mode.  
MOVs are connected in parallel for greater energy absorption for control sizes above 420Amp FLA.  
For factory supplied enclosure fans only.  
MN894  
Specifications and Product Data 6-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connection Diagrams Continued  
NEMA 1 & Panel Mounted Size 160840 AMP Combination & Noncombination  
(Hand - Off - Auto)  
Two Wire  
Control Device  
H
O
Enclosure  
Fan  
(Three Wire)  
Start  
A
Caution: Read Note ꢀ  
1
2
3
4
5
6
7
8
9
10  
Enclosure  
Fan  
TB1  
Stop  
Line Input  
L1  
L2  
L3  
TB1  
2
5
8
10  
R1  
1
3
4
6
7
9
95  
96  
CB  
OL  
13  
14  
MOV  
F3  
X
F1  
A
B
A
A
B
B
115VAC  
F2  
R1  
9
5
CF  
14 15 16 17  
CF  
CF  
R1  
13  
12  
11  
10  
9
8
7
6
5
4
3
2
1
Close  
To Run  
12  
8
PC1/L  
L1  
L2  
L3  
GL1  
GL2  
GL3  
GT1  
GT2  
GT3  
T1  
PC2/L  
PC3/L  
PC1  
Line  
PC2  
Line  
PC3  
Line  
Start /  
Run  
L2  
L3  
L1  
L
SC  
RS  
L
SC  
RS  
L
SC  
RS  
PC1/GL  
PC2/GL  
PC3/GL  
PC1/GT  
PC2/GT  
PC3/GT  
PC1/T  
Shunt  
Trip  
GL2  
GT2  
T2  
GL3  
GT3  
T3  
GL1  
GT1  
GL  
GT  
T
SA  
SB  
GL  
GT  
T
SA  
SB  
GL  
GT  
T
SA  
SB  
13 14  
R2  
CB  
Ramp  
End  
9
5
T1  
R2  
S1A  
S2A  
S2B  
S3A  
S3B  
LCM  
Shunt Trip  
S
S
S
97 98  
Tach  
Input  
S1B  
OL  
MTR  
Load  
Load  
Load  
PC2/T  
PWR  
CUR  
MON  
T2  
T3  
PC3/T  
CT Input  
CT2  
CT3  
CT4  
19 20  
OL  
OL  
CT1  
OL  
Legend:  
CB -  
CF -  
Shunt trip motor circuit protector or fuse disconnect..  
OL -  
Overload relay (electronic).  
Power cell cooling fan.  
Snubber capacitor.  
PC1,2,3 - SCR power cells.  
CS -  
T1  
T2  
To Motor  
T3  
R1 -  
R2 -  
RS -  
S -  
Run relay, DPDT.  
Shunt trip relay, DPDT.  
Snubber resistor.  
CT1 -  
LCM current transformer.  
CT2,3,4 - Overload current transformer.  
F1, F2 - Control transformer fuses.  
F3 -  
LCM - Logic control module - type M.  
MOV - Metal oxide varistors.  
CT1  
MBX140 = 8 Turns  
MBX160 = 8 Turns  
MBX250 = 4 Turns  
MBX420 = 4 Turns  
MBX600 = 4 Turns  
MBX840 = 4 Turns  
SCR overtemperature switch.  
Control branch circuit fuse.  
SCR - Silicon controlled rectifier.  
TB1 -  
X -  
Terminal block.  
Control transformer (control voltage).  
4 Turns (3 Loops)  
Notes:  
Control transformer must be properly connected for line voltage (see transformer nameplate).  
Do not apply voltage to LCM terminals 12 and 13. Dry contact type only.  
Number of cooling fans depends on the FLA rating.  
Tachometer is only required when LCM is used in Tach Feedback mode.  
MOVs are connected in parallel for greater energy absorption for control sizes above 420Amp FLA.  
Motor circuit protector and this circuit are not provided with the noncombination starters and fuse disconnect  
versions.  
For factory supplied enclosure fans only.  
6-12 Specifications and Product Data  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connection Diagrams Continued  
NEMA 12 Size 160840 AMP Combination & Noncombination Bypass  
H
O
A
Two Wire Control Device  
(Hand - Off - Auto)  
(Three Wire)  
Enclosure  
Fan  
Start  
Caution: Read Note ꢀ  
Enclosure  
Fan  
Stop  
2
5
8
10  
1
3
4
6
7
9
Line Input  
L2  
TB1  
L1  
L3  
TB1  
2
5
8
10  
1
3
4
6
7
9
95  
96  
CB  
R1  
OL  
MOV  
13  
14  
F3  
X
F1  
A
B
A
B
B
115VAC  
F2  
A
R1  
9
5
CF  
14 15 16 17  
BP  
CF  
CF  
R1  
13  
12  
11  
10  
9
8
7
6
5
4
3
2
1
Close  
To Run  
12  
8
PC1/L  
PC2/L  
PC3/L  
L1  
L2  
L3  
GL1  
GL2  
GL3  
GT1  
GT2  
GT3  
T1  
PC1  
Line  
PC2  
Line  
PC3  
Line  
Start /  
Run  
L2  
L3  
L1  
PC1/GL  
PC2/GL  
PC3/GL  
PC1/GT  
PC2/GT  
PC3/GT  
PC1/T  
L
SC  
RS  
L
SC  
RS  
L
SC  
RS  
Shunt  
Trip  
GL2  
GT2  
T2  
GL3  
GT3  
T3  
GL1  
GT1  
GL  
GT  
T
SA  
SB  
GL  
GT  
T
SA  
SB  
GL  
GT  
T
SA  
SB  
13 14  
R2  
CB  
LCM  
Ramp  
End  
9
5
T1  
R2  
S1A  
S2A  
S2B  
S3A  
S3B  
Shunt  
Trip  
S
S
S
97 98  
OL  
Tach  
Input  
S1B  
MTR  
Load  
Load  
Load  
CT4  
13 14  
R3  
9
BP  
PC2/T  
PWR  
CUR  
MON  
T2  
T3  
5
PC3/T  
CT Input  
A1  
A2  
R3  
19 20  
OL  
CT2  
OL  
OL  
CT1  
CT3  
Legend:  
BP -  
BYPASS Contactor.  
Shunt trip motor circuit protector or fuse disconnect..  
CB -  
CF -  
CS -  
CT1 -  
Power cell cooling fan.  
Snubber capacitor.  
LCM current transformer.  
OL -  
Overload relay (electronic).  
PC1,2,3 - SCR power cells.  
T1  
T2  
To Motor  
T3  
R1 -  
R2 -  
RS -  
S -  
Run relay, DPDT.  
Shunt trip relay, DPDT.  
Snubber resistor.  
CT2,3,4 - Overload current transformer.  
F1, F2 - Control transformer fuses.  
F3 -  
LCM - Logic control module - type M.  
MOV - Metal oxide varistors.  
CT1  
MBX140 = 8 Turns  
MBX160 = 8 Turns  
MBX250 = 4 Turns  
MBX420 = 4 Turns  
MBX600 = 4 Turns  
MBX840 = 4 Turns  
Control branch circuit fuse.  
SCR overtemperature switch.  
SCR - Silicon controlled rectifier.  
TB1 -  
X -  
Terminal block.  
Control transformer (control voltage).  
4 Turns (3 Loops)  
Notes:  
Control transformer must be properly connected for line voltage (see transformer nameplate).  
Do not apply voltage to LCM terminals 12 and 13. Dry contact type only.  
Number of cooling fans depends on the FLA rating.  
Tachometer is only required when LCM is used in Tach Feedback mode.  
MOVs are connected in parallel for greater energy absorption for control sizes above 420Amp FLA.  
Motor circuit protector and this circuit are not provided with the noncombination starters and fuse disconnect  
versions.  
For factory supplied enclosure fans only.  
MN894  
Specifications and Product Data 6-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6-14 Specifications and Product Data  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix A  
Reference Information  
Glossary  
BP  
CC  
CCW  
CL  
CM  
CS & RS  
Bypass Contactor  
PF  
PIV  
PT  
Power Factor Correction  
Peak Inverse Voltage  
Starting Pulse Time  
Power  
End of Voltage Ramp  
Ramp Down Time  
Ramp Down Disable  
Root Means Squared  
Ramp Up Time  
Silicon Controlled Rectifier  
Shorted SCR Detection  
Soft Start Control  
Tachometer  
Current Calibrator  
Counterclockwise  
Current Limit  
Current Monitor  
Resistor & Capacitor series  
circuit  
Current Monitor  
Current Transformer  
Clockwise  
Full Load Amperes (Motor)  
Logic Control Module  
Light Emitting Diode  
Motor Circuit Protector  
Metal Oxide Varistor  
Motor Power  
PWR  
Ramp End  
RD  
RDD  
RMS  
RU  
CUR MON  
CT  
CW  
FLA  
SCR  
Shunt Trip  
SSC  
TACH  
TD  
LCM  
LED  
MCP  
MOV  
MTR PWR  
OC  
Reduced torque value at start  
of Ramp Down Time  
Initial starting torque at Ramp  
Up Time  
Control Transformer  
TU  
X
Over Current Shutdown  
Overload Relay  
OL  
PC  
Power Cells  
Current Calibration Chart Settings for S1 are based on motors with 600% locked rotor amps. Motors with locked  
rotor amps greater than 600% should use a higher setting. Baldor Super-ER motors on  
high inertia loads should be set 1 or 2 settings higher than the suggested S1 setting. If a  
load takes too long to start, use the next higher setting.  
Caution:  
Select the table that matches you starter size only. Do not use the switch settings for a starter  
size that is different than the one you are setting up. Using the wrong switch setting can damage  
the Multipurpose Soft Starter control.  
S1 Switch Position and Setting  
S1 Switch Position and Setting  
Size 008  
Motor FLA  
Size 016  
Motor FLA  
1
1
0
0
0
0
0
1
0
0
0
1
0
0
0
0
1
0
0
1
1
1
1
0
0
0
1
2
1
0
0
0
1
0
0
1
0
0
0
1
1
1
1
0
0
0
1
0
1
0
1
0
1
1
3
1
0
0
0
1
1
0
1
1
0
1
0
1
0
1
0
1
0
0
1
1
0
0
1
1
1
4
0
0
1
0
0
1
0
0
1
0
0
1
1
0
0
1
1
0
0
0
0
1
1
1
1
1
5
0
1
1
0
0
0
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
0
0
0
0
0
6
0
0
0
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
7
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
8
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
1
1
1
1
1
0
0
1
2
0
0
1
0
1
0
1
0
1
1
3
0
1
1
0
0
1
1
0
0
0
4
0
0
0
1
1
1
1
0
0
0
5
0
0
0
0
0
0
0
1
1
1
6
1
1
1
1
1
1
1
1
1
1
7
1
1
1
1
1
1
1
1
1
1
8
1
1
1
1
1
1
1
1
1
1
1.01.1  
1.11.2  
1.21.3  
1.31.4  
1.41.5  
1.51.6  
1.61.7  
1.71.8  
1.81.9  
1.92.1  
2.12.3  
2.32.5  
2.52.7  
2.73.0  
3.03.3  
3.33.6  
3.63.9  
3.94.4  
4.44.8  
4.85.2  
5.25.6  
5.66.0  
6.06.4  
6.46.8  
6.87.4  
7.48.0  
6.06.5  
6.57.0  
78  
89  
910  
1011  
1112  
1213  
1314  
1416  
S1 Switch Position and Setting  
Size 030  
Motor FLA  
1
1
1
1
1
1
1
1
0
0
0
2
0
1
0
1
0
1
0
1
0
1
3
0
0
1
1
0
0
1
1
0
0
4
0
0
0
0
1
1
1
1
0
0
5
0
0
0
0
0
0
0
0
1
1
6
1
1
1
1
1
1
1
1
1
1
7
1
1
1
1
1
1
1
1
1
1
8
1
1
1
1
1
1
1
1
1
1
1213  
1314  
1415  
1516  
1618  
1820  
2022  
2224  
2427  
2730  
Note: 0=Off, 1=On  
MN894  
Appendix A-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S1 Switch Position and Setting  
S1 Switch Position and Setting  
Size 055  
Size 250  
Motor FLA  
Motor FLA  
1
0
1
0
0
0
0
1
0
1
2
1
0
0
1
0
1
1
0
0
3
0
1
0
0
1
1
1
0
0
4
0
0
1
1
1
1
1
0
0
5
0
0
0
0
0
0
0
1
1
6
1
1
1
1
1
1
1
1
1
7
1
1
1
1
1
1
1
1
1
8
1
1
1
1
1
1
1
1
1
1
1
0
0
1
0
1
0
0
2
1
1
0
1
0
1
1
0
3
0
0
1
0
0
0
1
0
4
0
0
0
0
0
1
0
0
5
1
0
1
0
1
1
0
1
6
0
1
1
0
0
0
1
1
7
1
1
1
0
0
0
0
0
8
0
0
0
1
1
1
1
1
2426  
2730  
3134  
3538  
3942  
4345  
4648  
4951  
5255  
108113  
114127  
128144  
145161  
162180  
181201  
202224  
225250  
S1 Switch Position and Setting  
Size 420  
Motor FLA  
S1 Switch Position and Setting  
Size 080  
1
1
0
1
1
0
1
0
0
0
2
1
1
0
1
0
1
0
0
0
3
0
0
0
1
1
0
0
1
0
4
0
1
0
0
1
0
1
1
0
5
0
0
1
1
1
0
0
0
1
6
1
1
1
1
1
0
0
0
0
7
0
0
0
0
0
1
1
1
1
8
1
1
1
1
1
1
1
1
1
Motor FLA  
1
0
0
1
1
0
1
0
2
1
0
0
1
0
0
1
3
1
0
0
0
1
1
1
4
1
0
0
0
0
0
0
5
0
1
1
1
1
1
1
6
1
1
1
1
1
1
1
7
1
1
1
1
1
1
1
8
1
1
1
1
1
1
1
200214  
215234  
235249  
250274  
275299  
300329  
330361  
362390  
391420  
4446  
4752  
5358  
5964  
6569  
7075  
7680  
S1 Switch Position and Setting  
Size 140  
Motor FLA  
S1 Switch Position and Setting  
1
0
1
1
0
0
0
1
1
0
2
1
0
1
0
1
0
1
0
0
3
0
0
1
1
1
0
0
0
0
4
0
0
1
1
0
0
1
0
1
5
0
1
1
0
1
0
0
1
1
6
1
1
1
0
0
1
1
1
1
7
1
1
1
0
0
0
0
0
0
8
0
0
0
1
1
1
1
1
1
Size 600  
Motor FLA  
5863  
6470  
7178  
7986  
8795  
96105  
106120  
121128  
129140  
1
1
0
0
1
1
0
1
1
2
1
1
1
1
1
1
0
1
3
0
0
0
0
0
0
0
1
4
1
0
1
0
1
0
1
1
5
0
1
1
0
0
1
1
1
6
0
0
0
1
1
1
1
1
7
0
0
0
0
0
0
0
0
8
1
1
1
1
1
1
1
1
320340  
341360  
361390  
391430  
431470  
471520  
521570  
571600  
S1 Switch Position and Setting  
S1 Switch Position and Setting  
Size 160  
Size 840  
Motor FLA  
Motor FLA  
1
1
1
0
1
0
1
0
1
1
2
0
1
0
1
1
1
0
1
0
3
0
1
1
1
0
0
1
0
0
4
0
1
1
0
0
1
0
1
0
5
1
1
0
1
0
0
1
1
0
6
1
1
0
0
1
1
1
1
0
7
1
1
0
0
0
0
0
0
1
8
0
0
1
1
1
1
1
1
1
1
0
1
1
0
1
1
0
2
1
0
1
1
0
0
0
3
0
0
1
1
0
1
0
4
0
1
1
0
1
1
0
5
1
1
1
0
0
0
1
6
1
1
1
0
0
0
0
7
0
0
0
1
1
1
1
8
1
1
1
1
1
1
1
6570  
7178  
7987  
471520  
521570  
571630  
631690  
691740  
741800  
801840  
8897  
98108  
109120  
121135  
136148  
149160  
Note: 0=Off, 1=On  
A-2 Appendix  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference Chart  
Ramp Up Time (3-50 sec.)  
RU  
Tachometer:  
Voltage:  
Time to reach full speed.  
Time to reach full speed.  
+ −  
50  
40  
3
S
T
A
R
T
Torque Up (40-75% voltage)  
TU  
Tachometer:  
Voltage:  
Disabled.  
Initial starting voltage for ramp.  
75  
− +  
Current Limit (75-400% FLA)  
Tachometer or voltage: Enabled by S2-5=ON. Maximum current during ramp up and ramp down.  
CL  
− +  
75  
400  
1.5  
Pulse Time (0-1.5 sec.)  
Tachometer:  
Voltage:  
Disabled.  
Duration of 400% FLA starting pulse.  
PT  
0
− +  
Ramp Down Time (5-50 sec.) (Disabled with S2-1=ON)  
Tachometer:  
Voltage:  
Time to reach zero speed.  
Time to reach zero speed.  
S
T
RD  
+ −  
Torque Down Advance (0-100%) (Disabled with S2-1=ON)  
Tachometer or voltage: Percentage reduction from full motor voltage for starting ramp down to zero volts.  
50  
0
5
O
P
TD  
− +  
100  
Current Monitor (50-400% FLA) Enabled at end of start cycle.  
S2-2=ON:  
If motor current exceeds CM value, control will shutdown, CUR MON contact will close and  
CUR MON light is ON.  
R
U
N
CM  
− +  
CUR MON:  
MTR PWR:  
Indicates CM or CL have been exceeded.  
S2-2=OFF:  
Control will not shutdown, contact  
will close, LED is ON.  
50  
0
400  
100  
Indicates voltage is applied to motor  
during start, run & ramp down.  
Tachometer input (0-10VDC).  
End of start ramp (full run condition).  
Shunt trip due to shorted SCR.  
Confirm Close to Run contact is closed.  
PF  
− +  
Power Factor  
(0-100%)  
TACH:  
0 to maximum allowable motor voltage  
reduction to improve power factor.  
RAMP END:  
SHUNT TRIP:  
START/RUN:  
CLOSE TO RUN: Start contact is closed.  
Power applied to control.  
Overcurrent shut down  
(450% FLA)  
CUR MTR  
MON PWR  
RAMP  
END  
SHUNT  
TRIP  
START/ CLOSE  
RUN TO RUN  
TACH  
S1 Current Calibration and “Motor Current” bar graph. S1 selects 255 calibration points for motor FLA.  
See “Current Calibration Chart” in this section for the proper setting.  
Bar Graph, displays the value of motor current during operation.  
RDD: S2-1, Ramp Down Disable.  
ON  
OFF  
Control is immediately disabled when the “Close to Run” input is opened.  
Control will ramp down when the “Close to Run” input is opened.  
CM:  
S2-2, Current Monitor Trip.  
ON  
Control will disable and CUR MON light and contact will indicate an overcurrent condition.  
CUR MON light and contact will indicate an overcurrent condition.  
S2-3, Over current shut down.  
OFF  
OC:  
ON  
OFF  
Overcurrent shutdown will turn on CUR MON light and close the CUR MON contact.  
Overcurrent shutdown will disable control with no affect to CUR MON light and contact.  
TACH: S2-4, Tachometer input enable.  
ON  
OFF  
Control is in tachometer feedback ramp mode.  
Control is in voltage ramp mode.  
CL:  
S2-5, Current Limit enable.  
ON  
Current will not exceed Current Limit adjustment during ramp up and down except during pulse start.  
Current Limit adjustment has no effect.  
OFF  
BP:  
S2-6, Bypass contactor enable.  
ON  
Shunt trip circuit is disabled during full on condition for bypass contactor to be used.  
Shunt trip circuit is enabled in all conditions.  
OFF  
MN894  
Appendix A-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Overload Relay Adjustment  
A class 30 electonic relay is provided with combination and non-combination starters.  
Read the FLA from the motor nameplate and set the overload dial to the correct ampere  
setting. Refer to the table that represents the starter size.  
Caution:  
Select the table that matches you starter size only. Do not use the  
switch settings for a starter size that is different than the one you  
are setting up. Using the wrong switch setting can damage the  
Multipurpose Soft Starter control.  
Caution:  
For starters size 8, 16 and 30A is direct reading. Using the wrong  
setting may damage the multiputpose soft start control.  
Overload Relay - Electronic Class 30  
Size 055# Passes  
through the window  
Dial Setting / Amps  
Dial Setting / Amps  
Size 250  
# Passes through the window  
3
4
5
6
200  
150  
120  
1 (Straight through)  
2 (1 loop)  
45  
22.5  
11  
50  
25  
12.5  
60  
30  
15  
70  
35  
17.5  
80  
40  
20  
90  
45  
22.5  
2 (1 loop)  
3 (2 loop)  
4 (3 loop)  
5 (4 loop)  
150  
100  
75  
200  
133  
100  
80  
250  
167  
125  
100  
3 (2 loop)  
60  
# Passes  
5 (4 loops)  
6 (5 loops)  
7 (6 loops)  
9
10  
11  
12  
14  
16  
18  
Size 080# Passes  
through the window  
1 (Straight Through)  
2 (1 loop)  
Dial Setting / Amps  
180 200 220 240  
166 185 203 216  
126 140 154 168 196 224 254  
45  
22.5  
50  
25  
60  
30  
70  
35  
80  
40  
90  
45  
Dial Setting / Amps  
Size 840  
Dial Setting / Amps  
Size 160  
# Passes through the window  
3
4
5
6
600  
300  
# Passes through the window  
3
4
5
6
150  
120  
100  
1 (Straight Through)  
2 (1 loop)  
600  
300  
150  
800  
400  
200  
1000  
500  
250  
3 (2 loops)  
4 (3 loops)  
5 (4 loops)  
6 (5 loops)  
100  
75  
60  
50  
133  
100  
80  
167  
125  
100  
83  
3 (2 loop)  
# Passes  
3 (2 loops)  
4 (3 loops)  
5 (4 loops)  
9
10  
11  
12  
14  
16  
18  
67  
600 667 734 800  
# Passes  
6 (5 loops)  
7 (6 loops)  
8 (7 loops)  
9
160  
10  
11  
12  
14  
16  
18  
450 500 550 600 700 800  
360 400 440 480 560 640 720  
128 143 157  
112 125 137 150  
Dial Setting / Amps  
Size 420  
# Passes through the window  
3
4
5
6
1 (Straight Through)  
2 (1 loop)  
300  
150  
100  
75  
400  
200  
133  
100  
500  
250  
167  
125  
300  
200  
150  
3 (2 loop)  
4 (3 loop)  
# Passes  
3 (2 loops)  
4 (3 loops)  
5 (4 loops)  
9
10  
11  
12  
14  
16  
18  
300 333 366 400  
225 250 275 300 350 400  
180 200 220 240 280 320 360  
1 Pass (Straight Through)  
2 Pass (1 Loop)  
A-4 Appendix  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix B  
Circuit Breaker Adjustments  
Circuit Breaker Adjustment (Inrush current estimation)  
Mechanical adjustment of the trip setting may be necessary if the circuit breaker is  
replaced. The first step of this adjustment procedure is to determine the motor inrush  
current (in amperes). Inrush current is also called “Locked Rotor AMPS” or “LRA”.  
In soft start applications, the initial voltage applied to the motor is reduced to  
approximately 40% to 70% of nominal line voltage. It is necessary to set set the trip  
current for the circuit breaker to the proper inrush current value. This inrush current is  
determined by motor horsepower and motor design characteristics. To define inrush  
characteristics, code letters are used. This code letter defines both the low voltage and  
high voltage inrush values for dual voltage motors. Table B-1 shows these code letters.  
(KVA = Kilovolt-Amperes; HP = Horsepower).  
KVA/HP Calculation of motor  
Table B-1 Code Letter Definition  
Code Letter  
KVA/HP  
Range  
KVA/HP  
Mid-Range Value  
A
B
C
D
E
F
G
H
J
K
L
M
N
P
R
0.00 - 3.14  
1.6  
3.3  
3.8  
4.3  
4.7  
5.3  
5.9  
6.7  
7.5  
8.5  
9.5  
10.6  
11.8  
13.2  
15.0  
3.15 - 3.54  
3.55 - 3.99  
4.00 - 4.49  
4.50 - 4.99  
5.00 - 5.59  
5.60 - 6.29  
6.30 - 7.09  
7.10 - 7.99  
8.00 - 8.99  
9.00 - 9.99  
10.00 - 11.19  
11.20 - 12.49  
12.50 - 13.99  
14.00 - 15.99  
3 Phase Inrush Current Calculation (Use mid range value for KVA/HP)  
KVA  
ǒ
Ǔ
x HP x 577  
HP mid range value  
Inrush AMPS +  
Rated Volts  
MN894  
Adjustments B-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Example: 3 phase Motor rated at 50 HP at 460VAC, 65 amps (continuous), code letter J.  
7.5 x 50 x 577  
+ ǒ  
Ǔ
IInrush  
+ 470Amperes  
460  
Circuit Breaker AdjustmentThe calculated Inrush Amps value is used to initially set the breaker. If the circuit breaker  
Caution:  
The trip level of the circuit breaker must remain as low as possible  
to avoid damage to equipment. If set too high, the circuit breaker  
may not trip during a high overcurrent condition.  
1. Refer to the manufacturers literature or the rating label on the circuit breaker.  
Determine the correct setting of the Trip Level adjustment based on the  
calculated Inrush Amps. Set the Trip Level adjustment to this initial level.  
2. Turn on power and start the motor.  
3. If the breaker trips and the shunt trip indicator on the LCM soft start control  
module is OFF, the circuit breaker tripped for an overcurrent condition. Turn  
power off and set the Trip Level to the next greater setting.  
4. Turn on power and start the motor.  
5. If the breaker trips, repeat steps 3 and 4. If the Trip Level adjustment is at the  
maximum setting and you have verified there is no phase to phase or phase to  
to Troubleshooting Section 5 of this manual.  
6. If the breaker continues to trip due to inrush current (and not a short circuit) the  
Rating Plug may be replaced with one that has a greater current rating. Refer  
to the circuit breaker manufacturers information and ratings.  
Figure B-1 Magnetic Circuit Breaker  
ON  
Tripped  
OFF  
Reset  
Handle  
Shunt Trip Device  
Manual Trip  
Rating Plug  
Trip Level  
Shunt Trip Wires to  
LCM soft start module  
B-2 Adjustments  
MN894  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Baldor District Offices  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BALDOR ELECTRIC COMPANY  
P.O. Box 2400  
Ft. Smith, AR 729012400  
(479) 6464711  
Fax (479) 6485792  
© Baldor Electric Company  
MN894  
Printed in USA  
9/06  
Download from Www.Somanuals.com. All Manuals Search And Download.  

3Com Switch 2226 PLUS User Manual
3M Laminator TL1306 TL1307 User Manual
Abit Computer Hardware SG 80DC User Manual
Acer Computer Monitor UMHG6AAD02 User Manual
Addonics Technologies Blu ray Player DDU7SAS User Manual
Addonics Technologies Network Card RCMR256I User Manual
Alamo Lawn Mower DSEB D16 User Manual
Allied Telesis Switch AR700 Series User Manual
Alpine CD Player CDE 9843 User Manual
American Innovative Clock Teach Me Time Talking Alarm Clock Nightlight User Manual