Allied Air Enterprises Heat Pump 4HP16LT User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS  
4HP16LT Series  
Split System Heat Pump  
Save these instructions for future reference  
WARNING  
The equipment covered in this manual is to be installed by trained and experienced service  
and installation technicians. Improper installation, modification, service, or use can cause  
electrical shock, fire, explosion, or other conditions which may cause personal injury, death,  
or property damage. Use appropriate safety gear including safety glasses and gloves when  
installing this equipment.  
WARNING  
TABLE OF CONTENTS  
Risk of electrical shock. Disconnect all remote  
INSTALLATION ...................................... 2  
CONNECTION DIAGRAM ..................... 4  
START-UP............................................ 13  
OPERATION ........................................ 18  
MAINTENANCE ................................... 23  
power supplies before installing or servicing  
any portion of the system. Failure to  
disconnect power supplies can result in  
property damage, personal injury, or death.  
WARNING  
Installation and servicing of air conditioning  
equipment can be hazardous due to internal  
refrigerant pressure and live electrical  
components. Only trained and qualified service  
personnel should install or service this  
equipment. Installation and service performed  
by unqualified persons can result in property  
damage, personal injury, or death.  
Manufactured By  
Allied Air Enterprises, Inc.  
A Lennox International Inc. Company  
215 Metropolitan Drive  
West Columbia, SC 29170  
WARNING  
*506468-01*  
Sharp metal edges can cause injury. When  
installing the unit, use care to avoid sharp  
edges.  
506468-01  
Issue 1004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 1  
NOTE: Elevation of the unit may be accomplished by  
constructing a frame using suitable materials. If a  
support frame is constructed, it must not block drain  
holes in unit base.  
Refer to the furnace or blower coil Installation Instructions  
for additional wiring application diagrams and refer to unit  
rating plate for minimum circuit ampacity and maximum  
overcurrent protection size.  
When installed in areas where low ambient tempera-  
tures exist, locate unit so winter prevailing winds do  
not blow directly into outdoor coil.  
1. Install line voltage power supply to unit from a properly  
sized disconnect switch. Any excess high voltage field  
wiring should be trimmed or secured away from the  
low voltage field wiring.  
Locate unit away from overhanging roof lines which would  
allow water or ice to drop on, or in front of, coil or into unit.  
2. Ground unit at unit disconnect switch or to an earth  
ground. To facilitate conduit, a hole is in the bottom of the  
control box. Connect conduit to the control box using a  
proper conduit fitting. Units are approved for use only with  
copper conductors. 24V Class II circuit connections are  
made in the low voltage junction box. Acomplete unit  
wiring diagram is located inside the unit control box cover  
(see also page 26 of this instruction).  
Slab Mounting  
When installing a unit at grade level, install on level slab  
high enough above grade so that water from higher ground  
will not collect around the unit (see Figure 2).  
3. Install room thermostat on an inside wall that is not  
subject to drafts, direct sunshine, or other heat sources.  
Slab Mounting  
Discharge Air  
4. Install low voltage wiring from outdoor to indoor unit  
and from thermostat to indoor unit (see Figure 3 on  
page 4).  
Building  
Structure  
5. Do not bundle any excess 24V control wire inside control  
box. Run control wire through installed wire tie and tighten  
wire tie to provide low voltage strain relief and to maintain  
separation of field-installed low and high voltage circuits.  
Mounting Slab  
Ground Level  
WARNING  
Line voltage is present at all components  
when unit is not in operation on units with  
single pole contactors. Disconnect all remote  
electric power supplies before opening access  
panel. Unit may have multiple power supplies.  
Failure to disconnect all power supplies could  
result in personal injury or death.  
Figure 2  
Roof Mounting  
Install unit at a minimum of 6" above surface of the roof to  
avoid ice buildup around the unit. Locate the unit above a  
load bearing wall or area of the roof that can adequately  
support the unit. Consult local codes for rooftop applications.  
Refrigerant Piping  
Electrical Wiring  
WARNING  
All field wiring must be done in accordance with the  
National Electrical Code (NEC) recommendations,  
Canadian Electrical Code (CEC) and CSA Standards, or  
local codes, where applicable.  
Refrigerant can be harmful if inhaled. Refrigerant  
must always be used and recovered responsibly.  
Incorrect or irresponsible use of refrigerant can  
result in personal injury or death.  
WARNING  
If the 4HP16LT unit is being installed with a new indoor  
coil and line set, the refrigerant connections should be  
made as outlined in this section. If an existing line set and/  
or indoor coil will be used to complete the system, refer to  
Unit must be grounded in accordance with  
national and local codes. Failure to ground unit  
properly can result in personal injury or death.  
506468-01  
Issue 1004  
Page 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Field refrigerant piping consists of liquid and suction lines  
from the outdoor unit (sweat connections) to the indoor coil  
(flare or sweat connections).  
Thermostat Designations  
(Some connections may not apply. Refer to  
specific thermostat and indoor unit.)  
Without Auxiliary Heat  
Select line set diameters from Table 2 to ensure that oil  
returns to the compressor. Size vertical suction riser to  
maintain minimum velocity at minimum capacity.  
Recommended line length is 50’ or less. If more than 50’  
line set is required, contact Technical Services.  
Table 2 shows the diameters for line sets up to 100’ although  
vertical lift applications and trapping requirements need to  
be reviewed with Technical Services for line sets over 50’.  
Refrigerant Line Set Diameters (in.)  
Liquid Line  
Line S et Length and S ize  
B T UH  
12 f t. 25 ft. 50 ft. 75 ft. 10 0 f t.  
3/8  
3/8  
3/8  
3/8  
3/8  
3/8  
3/8  
3/8  
3/8  
3/8  
3/8  
3/8  
3/8  
3/8  
1/2  
1/2  
3/8  
1/2  
1/2  
1/2  
24,000  
36,000  
48,000  
60,000  
S uction Line  
Line S et Length and S ize  
B T UH  
12 f t. 25 ft. 50 ft. 75 ft. 10 0 f t.  
7/8  
7/8  
3/4  
7/8  
7/8  
3/4  
7/8  
24,000  
36,000  
48,000  
7/8  
7/8  
7/8  
Do not connect C (common) connection between indoor unit and  
thermostat except when required by the indoor thermostat. Refer to  
thermostat installation instructions. C (common) connection between  
indoor unit and outdoor unit required for proper operation.  
1-1/8  
1-1/8  
7/8  
1-1/8  
7/8  
1-1/8 1-1/8  
60,000 1-1/8  
1-1/8  
1-1/8  
Figure 3  
For installations exceeding 50’, contact  
Technical Services.  
this sesction as well as the section that follows entitled  
Flushing Existing Line Set and Indoor Coil.  
Table 2  
If this unit is being matched with an approved line set or  
indoor coil which was previously charged with R-22  
refrigerand, the line set and coil must be flushed prior to  
installation. If the unit is being used with an exisitng indoor  
coil which was equipped with a liquid line which served as a  
metering device (RFCI), the liquid line must be replaced prior  
to the installation of the 4HP16LT unit.  
Page 4  
Issue 1004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506468-01  
Line Set Isolation  
WARNING  
Illustrations on pages 6 and 7 demonstrate procedures  
which ensure proper refrigerant line set isolation. Figure 5  
shows how to install line sets on horizontal runs. Figure 6  
shows how to make a transition from horizontal to vertical.  
Figure 7 shows how to install line sets on vertical runs.  
Polyol ester (POE) oils used with R410A  
refrigerant absorb moisture very quickly. It is  
very important that the refrigerant system be  
kept closed as much as possible. DO NOT  
remove line set caps or service valve stub  
caps until ready to make connections.  
Brazing Connection Procedure  
1. Cut ends of refrigerant lines square (free from nicks  
or dents). Debur the ends. The pipe must remain  
round; do not pinch end of line.  
Installing Refrigerant Line  
During the installation of an air conditioning system, it is  
important to properly isolate the refrigerant line to prevent  
unnecessary vibration. Line set contact with the structure  
(wall, ceiling, or floor) may cause objectionable noise  
when vibration is translated into sound. As a result, more  
energy or vibration can be expected. Close attention to  
line set isolation must be observed.  
2. Before making line set connections, use dry nitrogen to  
purge the refrigerant piping. This will help to prevent  
oxidation and the introduction of moisture into the system.  
3. Use silver alloy brazing rods (5% or 6% silver alloy for  
copper-to-copper brazing or 45% silver alloy for  
copper-to-brass or copper-to-steel brazing) which are  
rated for use with R410A refrigerant.  
Following are some points to consider when placing and  
installing a high-efficiency outdoor unit:  
4. Remove the Schrader core assemblies before brazing  
to protect them from damage due to extreme heat.  
Replace the cores when brazing is complete.  
Placement  
Be aware that some localities are adopting sound ordinances  
based on how noisy the unit is at the neighbor’s home, not at  
the original installation. Install the unit as far as possible from  
the property line. When possible, do not install the unit  
directly outside a bedroom window. Glass has a very high  
level of sound transmission. Figure 4 shows how to place the  
outdoor unit and line set to reduce line set vibration.  
5. Remove light maroon washers from service valves and  
shield light maroon stickers to protect them during  
brazing. Wrap a wet cloth around the valve body and  
copper tube stub to protect it from heat damage.  
6. Braze the line set to the service valve. Quench the joints  
with water or a wet cloth to prevent heat damage to the  
valve core and opening port. The tube end must stay  
bottomed in the fitting during final assembly to  
ensure proper seating, sealing, and rigidity.  
Outside Unit Placement  
and Installation  
7. Install a thermal expansion valve (which is sold  
separately and which is approved for use with R410A  
refrigerant) in the liquid line at the indoor coil (see  
Refrigerant Metering Device on page 9).  
Install unit away  
from windows  
Two 90° elbows installed in lineset  
will reduce lineset vibration  
Figure 4  
506468-01  
Issue 1004  
Page 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Refrigerant Line Sets: Installing Horizontal Runs  
To hang line set from joist or rafter,  
use either metal strapping material  
or anchored heavy nylon wire ties.  
Wire Tie  
(around vapor line only)  
8  
Strapping Material  
(around vapor line only)  
Floor Joist or  
Roof Rafter  
Tape or Wire Tie  
8’  
Strap the vapor line to the joist or rafter  
at 8intervals then strap the liquid line  
to the vapor line.  
Metal Sleeve  
Floor Joist or Roof Rafter  
Tape or Wire Tie  
Figure 5  
Refrigerant Line Sets: Transition from Vertical to Horizontal  
Automotive  
Muffler-Type  
Hanger  
Anchored  
Heavy Nylon  
Wire Tie  
Strap Liquid  
Line to Vapor  
Line  
Strap Liquid  
Line to Vapor  
Line  
Wall  
Stud  
Wall  
Stud  
Liquid Line  
Liquid Line  
Vapor Line Wrapped  
Vapor Line Wrapped  
Metal Sleeve  
in Armaflex  
Metal Sleeve  
in Armaflex  
Figure 6  
Page 6  
Issue 1004  
506468-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Refrigerant Line Sets: Installing Vertical Runs (new construction shown)  
IMPORTANT: Refrigerant  
lines must not contact wall.  
Outside Wall  
Vapor Line  
Liquid Line  
NOTE: Similar installation practices  
should be used if line set is to be  
installed on exterior of outside wall.  
Wood Block  
Between Studs  
Wire Tie  
Inside Wall  
Strap  
Sleeve  
Vapor Line Wrapped  
with Armaflex  
Wire Tie  
Liquid Line  
Outside Wall  
Wood Block  
IMPORTANT:  
Refrigerant  
lines must not  
contact structure.  
Wire Tie  
Strap  
Caulk  
Fiberglass  
PVC Pipe  
Insulation  
Sleeve  
Figure 7  
Flushing Existing Line Set and Indoor Coil  
with a “pump down” feature, and two sets of gauges (one  
for use with R22 and one for use with R410A).  
This procedure should not be performed on systems  
which contain contaminants, such as compressor  
burn out.  
Flushing Procedure  
IMPORTANT: The line set and/or indoor coil must be  
flushed with at least the same amount of refrigerant that  
previously charged the system. Check the charge in the  
flushing cylinder before flushing the unit.  
CAUTION  
When flushing existing line set and/or indoor  
coil, be sure to empty all existing traps. Residual  
mineral oil can act as an insulator, preventing  
proper heat transfer. It can also clog the thermal  
expansion valve, reducing system performance  
and capacity. Failure to properly flush system as  
explained in these instructions will void warranty.  
1. Remove existing R22 refrigerant using the appropriate  
procedure.  
If the existing outdoor unit is not equipped with shutoff  
valves, or if the unit is not operational AND the existing  
R22 refrigerant will be used to flush the system:  
Disconnect all power to the existing outdoor unit.  
Connect the existing unit, a clean recovery cylinder, and  
the recovery machine according to the instructions  
provided with the recovery machine. Remove all R22  
refrigerant from the existing system. Refer to the  
gauges after shutdown to confirm that the entire system  
is completely void of refrigerant. Disconnect the liquid  
and suction lines from the existing outdoor unit.  
Required Equipment  
The following equipment is needed to flush the existing  
line set and indoor coil (see Figure 8 on page 8): Two  
clean R22 recovery bottles, an oil-less recovery machine  
506468-01  
Issue 1004  
Page 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Flushing Connections  
Note: The inverted R22 cylinder must contain  
at least the same amount of refrigerant  
as was recovered from the existing  
system.  
Figure 8  
If the existing outdoor unit is equipped with manual  
shutoff valves AND new R22 refrigerant will be used  
to flush the system:  
are not approved for use with R410A refrigerant and  
may prevent proper flushing. Use a field-provided  
fitting to reconnect the lines.  
Start the existing R22 refrigerant system in cooling mode  
and close the liquid line valve. Pump all the existing R22  
refrigerant back into the outdoor unit.  
5. Remove the pressure tap valve cores from the  
4HP16LT unit’s service valves. Connect an R-22  
cylinder with clean refrigerant to the suction service  
valve. Connect the R-22 gauge set to the liquid line  
valve and connect a recovery machine with an empty  
recovery tank to the gauge set.  
(It may be necessary to bypass the low pressure  
switches to ensure complete refrigerant evacuation.)  
When the low side system pressures reach 0 psig, close  
the suction line valve. Disconnect all power to the  
existing outdoor unit. Refer to the gauges after shutdown  
to confirm that the valves are not allowing refrigerant to  
flow back into the low side of the system. Disconnect the  
liquid and suction lines from the existing outdoor unit.  
6. Set the recovery machine for liquid recovery and start  
the recovery machine. Open the gauge set valves to  
allow the recovery machine to pull a vacuum on the  
existing system line set and indoor coil.  
7. Invert the cylinder of clean R-22 and open its valve to  
allow liquid refrigerant to flow into the system through  
the suction line valve. Allow the refrigerant to pass  
from the cylinder and through the line set and the  
indoor coil before it enters the recovery machine.  
2. Remove the existing outdoor unit. Set the new R410A  
unit and follow the brazing connection procedure  
outlined previously on this page to make line set  
connections. Do not install the R410A thermal  
expansion valve at this time.  
8. After all of the liquid refrigerant has been recovered,  
switch the recovery machine to vapor recovery so that  
all of the R-22 vapor is recovered. Allow the recovery  
machine to pull a vacuum on the system.  
3. Make low voltage and line voltage connections to the  
new outdoor unit. Do not turn on power to the unit or  
open the outdoor unit service valves at this time.  
NOTE: A single system flush should remove all of the  
mineral oil from the existing refrigerant lines and indoor  
coil. A second flushing may be done (using clean  
refrigerant) if insufficient amounts of mineral oil were  
4. Remove the existing R-22 refrigerant flow control  
orifice or thermal expansion valve before continuing  
with flushing procedures. R-22 flow control devices  
Page 8  
Issue 1004  
506468-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
removed during the first flush. After each system flush,  
allow the recovery machine to pull a vacuum on the  
system at the end of the procedure.  
9. Close the valve on the inverted R22 cylinder and the  
gauge set valves. Pump the remaining refrigeraant out of  
the recovery machine and turn the machine off.  
10. Use nitrogen to break the vacuum on the refrigerant  
lines and indoor coil before removing the recovery machine,  
gauges, and R22 refrigerant drum. Re-install pressure tap  
valve cores into the 4HP16LT unit’s service valves.  
11. Install a thermal expansion valve approved for use with  
R410a refrigerant in the liquid line at the indoor coil.  
Refrigerant Metering Device  
Figure 9  
4HP16LT units are designed for use with TXV systems only.  
An R410a system will not operate properly with an R22  
metering device.  
4. Strap the superheat sensing bulb to the suction header.  
Expansion valves equipped with Chatleff-type fittings are  
available from the manufacturer. See Table 3 for proper  
TXV for each unit.  
If installing an expansion valve on an indoor coil that  
previously used a fixed orifice, be sure to remove the existing  
fixed orifice. Failure to remove a fixed orifice when installing  
an expansion valve to the indoor coil will result in improper  
operation and damage to the system.  
TXV Data  
Manifold Gauge Set  
MODEL  
PART NUMBER  
Manifold guage sets used with systems charged with R410A  
refrigerant must be capable of handling the higher system  
operating pressures. The gauges should be rated for use  
with pressures 1 - 800 on the high side and a low side of 30”  
vacuum to 250 psi with dampened speed to 500 psi. Gauge  
hoses must be rated for use at up to 800 psi of pressure  
with a 4000 psi burst rating.  
H4TXV01  
H4TXV02  
H4TXV03  
4HP16LT- 24  
4HP16LT - 36  
4HP16LT - 48, -60  
Table 3  
Liquid and Suction Line Service Valves  
To install an expansion valve (See Figure 9):  
The liquid line and suction line service valves (See Figure  
11) and service ports are used for leak teating, evacuation,  
charging, and checking charge.  
1. Separate the distributor assembly and remove the piston  
orifice and used teflon seal. Insert nozzle end of the  
expansion valve along with a new teflon seal into the  
distributor and tighten to 20 - 30 ft. lbs. Use backup wrench  
on all wrench flats. Overtightening will crush the teflon  
seal and may cause a leak.  
Each valve is equipped with a service port which has a  
factory-installed Schrader valve. Aservice port cap protects  
the Schrader valve from contamination and serves as the  
primary leak seal.  
2. Attach liquid line portion of distributor assembly along  
with new teflon seal to the inlet of the expansion valve.  
Tighten to 20 - 30 ft. lbs. Use backup wrench on all wrench  
flats. Overtightening will crush the teflon seal and may  
cause a leak.  
To Access the Schrader Port:  
1. Remove the service port cap with an adjustable wrench.  
2. Connect gauge to the service port.  
3. Connect the external equalizer line to the equalizer port  
on the suction line and tighten to 8 ft.lbs.  
3. When testing is completed, replace service port cap.  
Tighten finger tight, then an additional 1/6 turn.  
506468-01  
Issue 1004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 9  
Service Valve  
Ball Type Service Valve  
(Valve Open)  
Valve Closed  
Stem Cap  
Service Port  
Insert hex  
wrench here  
To outdoor coil  
Service  
Port Cap  
To indoor coil  
(valve front seated)  
Schrader valve open  
to line set when valve is  
closed (front seated)  
Stem Cap  
Insert hex  
wrench here  
Service Port  
Use adjustable wrench. To open, rotate stem  
counterclockwise 1/4 turn (90°). To close, rotate  
stem clockwise 1/4 turn (90°).  
To outdoor coil  
Figure 11  
To indoor coil  
Service Port Cap  
The ball valve is equipped with a service port with a  
factory-installed Schrader valve. A service port cap  
protects the Schrader valve from contamination and  
serves as the primary seal.  
Schrader  
Valve  
Valve Open  
Figure 10  
Leak Testing  
To Open Liquid or Suction Line Service Valve:  
After the line set has been connected to the indoor and  
outdoor units, the line set connections and indoor unit  
must be checked for leaks.  
1. Remove stem cap with an adjustable wrench.  
2. Use a service wrench with a hex-head extension to back  
the stem out counterclockwise as far as it will go. Use a  
3/16" hex head extension for liquid line service valves  
and a 5/16" extension for suction line service valves.  
WARNING  
Fire, Explosion, and Personal Safety Hazard.  
3. Replace the stem cap. Tighten finger tight, then  
tighten an additional 1/6 turn.  
Failure to follow this warning could result in  
damage, personal injury, or death.  
To Close Liquid or Suction Line Service Valve:  
Never use oxygen to pressurize or purge  
refrigeration lines. Oxygen, when exposed to  
a spark or open flame, can cause damage by  
fire and/or an explosion, that could result in  
personal injury or death.  
1. Remove the stem cap with an adjustable wrench.  
2. Use a service wrench with a hex-head extension to turn  
the stem clockwise to seat the valve. Tighten firmly.  
3. Replace the stem cap. Tighten finger tight, then  
tighten an additional 1/6 turn.  
Using an Electronic Leak Detector  
Suction Line (Ball Type) Service Valve  
1. Connect the high pressure hose of the manifold  
gauge set to the suction valve service port. (Normally  
the high pressure hose is connected to the liquid line  
port; however, connecting it to the suction ports helps  
Suction line (ball type) service valves function the same  
way as the other valves; the difference is in the construc-  
tion (see Figure 11).  
Page 10  
Issue 1004  
506468-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
to protect the manifold gauge set from damage  
caused by high pressure.)  
Low pressure gauge to suction line service valve  
High pressure gauge to liquid line service valve  
2. With both manifold valves closed, connect the cylin-  
der of R410A refrigerant. Open the valve on the  
R410A cylinder (vapor only).  
2. Connect micron gauge.  
3. Connect the vacuum pump (with vacuum gauge) to  
the center port of the manifold gauge set.  
3. Open the high pressure side of the manifold to allow  
R410A into the line set and indoor unit. Weigh in a  
trace amount of R410A. (A trace amount is a maxi-  
mum of 2 oz. of refrigerant or 3 lbs. pressure.) Close  
the valve on the R410A cylinder and the valve on the  
high pressure side of the manifold gauge set. Discon-  
nect the R410A cylinder.  
4. Open both manifold valves and start vacuum pump.  
5. Evacuate the line set and indoor unit to a minimum of  
500 microns or lower. During the early stages of  
evacuation, it is desirable to close the manifold gauge  
valve at least once to determine if there is a rapid rise  
in pressure. A rapid rise in pressure indicates a  
relatively large leak. If this occurs, the leak testing  
procedure must be repeated.  
4. Connect a cylinder of nitrogen with a pressure regulat-  
ing valve to the center port of the manifold gauge set.  
When using high pressure gas such as nitrogen  
for this purpose, be sure to use a regulator that  
can control the pressure down to 1 or 2 psig.  
6. When 500 microns or lower is maintained, close the  
manifold gauge valves, turn off the vacuum pump, and  
disconnect the manifold gauge center port hose from  
the vacuum pump. Attach the manifold gauge center  
port hose to a nitrogen cylinder with pressure regulator  
set to 150 psig and purge the hose. Open the manifold  
gauge valves to break the vacuum in the line set and  
indoor unit. Close the manifold gauge valves.  
5. Adjust nitrogen pressure to 150 psig. Open the valve  
on the high side of the manifold gauge set to pressur-  
ize the line set and the indoor coil.  
6. After a short period of time, open a refrigerant port to  
make sure that an adequate amount of refrigerant has  
been added for detection (refrigerant requirements will  
vary with lengths). Check all joints for leaks. Purge  
nitrogen and R410A mixture. Correct any leaks and  
recheck.  
7. Shut off the nitrogen cylinder and remove the manifold  
gauge hose from the cylinder. Open the manifold  
gauge valves to release the nitrogen from the line set  
and indoor unit.  
Evacuation  
8. Reconnect the manifold gauge to the vacuum pump,  
turn the pump on, and continue to evacuate the line  
set and indoor unit until 500 microns is maintained  
within a 20-minute period after shutting off the  
Evacuating the system of noncondensables is critical for  
proper operation of the unit. Noncondensables are defined  
as any gas that will not condense under temperatures and  
pressures present during operation of an air conditioning  
system. Noncondensables and water vapor combine with  
refrigerant to produce substances that corrode copper  
piping and compressor parts.  
vacuum pump and closing the manifold gauge valves.  
9. When the requirements above have been met,  
disconnect the manifold hose from the vacuum pump.  
Open the service valves to break the vacuum in the  
line set and indoor unit.  
WARNING  
Do not use a compressor to evacuate a sys-  
tem. Avoid deep vacuum operation. Extremely  
low vacuums can cause internal arcing and  
compressor failure. Danger of equipment  
damage. Damage caused by deep vacuum  
operation will void warranty.  
Use a thermocouple or thermistor electronic vacuum  
gauge that is calibrated in microns. Use an instrument that  
reads down to 50 microns.  
1. Connect the manifold gauge set to the service valve  
ports as follows:  
506468-01  
Issue 1004  
Page 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Units are factory charged with the amount of R410A  
refrigerant indicated on the unit rating plate. This charge is  
based on a matching indoor coil and outdoor coil with 15’  
line set. For varying lengths of line set, refer to Table 4 for  
refrigerant charge adjustment. A blank space is provided  
on the unit rating plate to list the actual field charge.  
START-UP  
CAUTION  
If unit is equipped with a crankcase heater, it should be  
energized 24 hours before unit start-up to prevent  
compressor damage as a result of slugging.  
Refrigerant Charge Adjustment  
Liquid Line Set Diameter  
Oz. Per 5 ft. adjust from 15  
ft. line set*  
1. Rotate fan to check for frozen bearings or binding.  
2. Inspect all factory and field-installed wiring for loose  
connections.  
3/8 in.  
3 oz. Per 5 ft.  
* If line length is greater than 15 ft., add this amount.  
If line length is less than 15 ft., remove this amount.  
3. After evacuation is complete, open liquid line and suction  
line service valves to release refrigerant charge (contained  
in outdoor unit) into system.  
Table 4  
IMPORTANT  
4. Replace the stem caps and secure finger tight, then  
tighten an additional 1/6 of a turn.  
Mineral oils are not compatible with R410A. If oil must  
be added, it must be a polyolester oil.  
5. Check voltage supply at the disconnect switch. The  
voltage must be within the range listed on the unit nameplate.  
If not, do not start equipment until the power company has  
been consulted and the voltage condition corrected.  
If the system is void of refrigerant, clean the system using  
the procedure described below.  
1. Use dry nitrogen to pressurized the system and check  
for leaks. Repair leaks, if possible.  
6. Set thermostat for cooling demand, turn on power to  
indoor blower, and close the outdoor unit disconnect switch  
to start the unit.  
2. Evacuate the system to remove as much of the moisture  
as possible.  
7. Recheck unit voltage with unit running. Power must be  
within range shown on unit nameplate.  
3. Use dry nitrogen to break the vacuum.  
4. Evacuate the system again.  
Refrigerant Charging  
This system is charged with R410A refrigerant which  
operates at much higher pressures than R-22. The liquid  
line drier provided with the unit is approved for use with  
R410A. Do not replace it with one designed for use with R-  
22. This unit is NOT approved for use with coils which  
use capillary tubes as a refrigerant metering device.  
5. Weigh the appropriate amount of R410Arefrigerant (listed  
on unit nameplate) into the system.  
6. Monitor the system to determine the amount of moisture  
remaining in the oil. Use a test kit to verify that the moisture  
content is withing the kit’s dry color range. It may be  
necessary to replace the filter drier several times to achieve  
the required dryness level. If system dryness is not  
verified, the compressor will fail in the future.  
R410A refrigerant cylinders are rose colored.  
Refrigerant should be added through the suction valve  
in the liquid state.  
The outdoor unit should be charged during warm weather.  
However, applications arise in which charging must occur in  
the colder months. The method of charging is determined  
by the unit’s refrigerant metering device and the outdoor  
ambient temperature.  
Certain R410Acylinders are identified as being equipped  
with a dip tube. These allow liquid refrigerant to be  
drawn from the bottom of the cylinder without inverting  
the cylinder. Do not turn this type of cylinder upside  
down to draw refrigerant.  
Measure the liquid line temperature and the outdoor ambient  
temperature as outlined below:  
1. Connect the manifold gauge set to the service valve ports  
as follows (See Figure 13 above):  
506468-01  
Issue 1004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 12  
Cooling Cycle  
OUTDOOR UNIT  
DEFROST THERMOSTAT  
EXPANSION/CHECK VALVE  
DISTRIBUTOR  
NOTE - ARROWS INDICATE  
DIRECTION OF  
REFRIGERANT FLOW  
REVERSING VALVE  
OUTDOOR COIL  
BIFLOW  
FILTER / DRIER  
LOW  
PRESSURE  
HIGH  
PRESSURE  
INDOOR UNIT  
MUFFLER  
GAUGE MANIFOLD  
SUCTION  
SERVICE  
PORT  
SUCTION  
LINE  
VALVE  
TO  
R410A  
DRUM  
LIQUID  
LINE  
SERVICE  
PORT  
COMPRESSOR  
INDOOR  
COIL  
EXPANSION/CHECK VALVE  
Use gauge ports on suction line valve and liquid line valve for evacuating refrigerant lines and indoor coil. Use  
suction gauge port to measure suction pressure during charging.  
Figure 12  
Low pressure gauge to suction line service valve  
High pressure gauge to liquid line service valve  
3. Weigh in the charge according to the total amount  
shown on the unit nameplate.  
2. Close manifold gauge set valves. Connect the center  
manifold hose to an upright cylinder of R410A.  
If weighing facilities are not available, use one of the  
following procedures to charge the unit.  
3. If room temperature is below 70°F, set the room thermo-  
stat to call for heat. This will create the necessary load  
for properly charging the system in the cooling cycle.  
Charge Using Subcooling Method –  
Outdoor Temperatures Below 65°F  
When the outdoor ambient temperature is below 65°F, the  
subcooling method can be used to charge the unit. It may  
be necessary to restrict the air flow through the outdoor  
coil to achieve pressures in the 200-250 psig range.  
These higher pressures are necessary for checking the  
charge. Block equal sections of air intake panels and  
move obstructions sideways until the liquid pressure is in  
the 200-250 psig range (see Figure 13 on page 14).  
4. Use a digital thermometer to record the outdoor  
ambient temperature.  
5. When the heating demand has been satisfied, switch  
the thermostat to cooling mode with a set point of 68°F.  
When pressures have stabilized, use a digital thermom-  
eter to record the liquid and suction line temperatures.  
6. The outdoor temperature will determine which charg-  
ing method to use. Proceed with the appropriate  
charging method.  
1. With the manifold gauge hose still on the liquid  
service port and the unit operating stably, use a digital  
thermometer to check the liquid line temperature. For  
best results, use the same digital thermometer to  
check both the outdoor ambient and the liquid line  
temperatures.  
Charge Using Weigh-In Method  
If the system is void of refrigerant, or if the outdoor ambient  
temperature is cool, first locate and repair any leaks then  
use the weigh-in method to charge the unit.  
2. At the same time, record the liquid line pressure reading.  
3. Use the temperature/pressure chart (Table 5 on page 14)  
to determine the saturation temperature for the liquid line  
pressure reading.  
1. Recover the refrigerant from the unit.  
2. Conduct a leak check, then evacuate as previously  
outlined.  
506468-01  
Issue 1004  
Page 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Blocking Outdoor Coil  
Outdoor coil should be  
R410A Temperature/Pressure Chart  
Temp.  
EF  
Pressure  
Psig  
Temp.  
EF  
Pressure  
Psig  
Temp.  
EF  
Pressure  
Psig  
blocked one side at a time  
with cardboard or plastic  
sheet until proper testing  
pressures are reached.  
32  
33  
100.8  
102.9  
74  
75  
214.0  
217.4  
116  
117  
396.0  
401.3  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
64  
65  
66  
67  
68  
69  
70  
71  
72  
73  
105.0  
107.1  
109.2  
111.4  
113.6  
115.8  
118.0  
120.3  
122.6  
125.0  
127.3  
129.7  
132.2  
134.6  
137.1  
139.6  
142.2  
144.8  
147.4  
150.1  
152.8  
155.5  
158.2  
161.0  
163.9  
166.7  
169.6  
172.6  
175.5  
178.5  
181.6  
184.3  
187.7  
190.9  
194.1  
197.3  
200.6  
203.9  
207.2  
210.6  
76  
77  
220.9  
224.4  
228.0  
231.6  
235.3  
239.0  
242.7  
246.5  
250.3  
254.1  
258.0  
262.0  
266.0  
270.0  
274.1  
278.2  
282.3  
286.5  
290.3  
295.1  
299.4  
303.8  
308.2  
312.7  
317.2  
321.8  
326.4  
331.0  
335.7  
340.5  
345.3  
350.1  
355.0  
360.0  
365.0  
370.0  
375.1  
380.2  
385.4  
390.7  
118  
119  
120  
121  
122  
123  
124  
125  
126  
127  
128  
129  
130  
131  
132  
133  
134  
135  
136  
137  
138  
139  
140  
141  
142  
143  
144  
145  
146  
147  
148  
149  
150  
151  
152  
153  
154  
155  
406.7  
412.2  
417.7  
423.2  
428.8  
434.5  
440.2  
445.9  
451.8  
457.6  
463.5  
469.5  
475.6  
481.6  
487.8  
494.0  
500.2  
506.5  
512.9  
519.3  
525.8  
532.4  
539.0  
545.6  
552.3  
559.1  
565.9  
572.8  
579.8  
586.8  
593.8  
601.0  
608.1  
615.4  
622.7  
630.1  
637.5  
645.0  
78  
CARDBOARD OR  
PLASTIC SHEET  
79  
80  
81  
82  
83  
Figure 13  
84  
85  
4. Subtract the liquid line temperature from the saturation  
temperature (according to the chart) to determine  
Subcooling.  
86  
87  
88  
°
°
°
Saturation Temperature °F  
Liquid Line Temperature °F  
Subcooling Value °F  
89  
_
90  
=
91  
92  
5. Compare the subcooling value with those shown in Table  
6. If subcooling is greater than shown, recover some  
refrigerant. If subcooling is less than shown, add some  
refrigerant.  
93  
94  
95  
96  
97  
98  
Subcooling Values  
99  
100  
101  
102  
103  
104  
105  
106  
107  
108  
109  
110  
111  
112  
113  
114  
115  
Table 6  
Charge UsingApproach Method (TXV System) - Outdoor  
Temperatures 65°F or Above  
The following procedure is intended as a general guide and  
is for use on expansion valve systems only. For best results,  
indoor temperature should be 70°F to 80°F. Monitor system  
pressures while charging.  
1. Record outdoor ambient temperature usig a digital  
thermometer.  
72  
73  
207.2  
210.6  
114  
115  
385.4  
390.7  
2. Attach high pressure gauge set and operate unit for  
several minutes to allow system pressures to stabilize.  
Table 5  
3. Compare stabilized pressures with those provided in Table  
7. Minor variations in these pressures may be expected  
506468-01  
Issue 1004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 14  
Normal Operating Pressures  
Heating & Cooling  
Cooling Indoor: 80 db; 67 wb  
Heating (indoor): 70°F  
± 2 psi  
L - Liquid  
S- Suction  
Values provided above are for HSV match pressures; different indoor unit match, and indoor load will cause  
pressures to vary.  
Table 7  
system is undercharged. Verify adjusted charge using the  
approach method.  
due to differences in installations. Significant  
differences could mean that the system is not  
properly charged or that a problem exists with some  
component in the system. Pressures higher than those  
listed indicate that the system is overcharged. Pressures  
4. Use the same digital thermometer to check liquid line  
temperature.  
lower than those listed indicate that the  
506468-01  
Issue 1004  
Page 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Subtract the outdoor ambient temperature from the liquid  
line temperture to determine the approach temperature.  
Check Charge Using Normal Operating Pressures  
Use Table 7 to perform maintenance checks. Table 7 is not  
a procedure for charging the system. Minor variations in  
these pressures may be due to differences in installations.  
Significant deviations could mean that the system is not  
properly charged or that a problem exists with some  
component in the system.  
°
°
°
Liquid Line Temperature °F  
Outdoor Ambient Temperature °F  
Approach Temperature °F  
_
=
6. Compare the approach value with those shown in Table  
8. If the values do not agree with those provided in Table 8,  
add refrigerant to lower the approach temperature or recover  
refrigerant from the system to increase the approach  
temperature.  
Approach Values for TXV Systems  
Approach value is the liquid line temperature minus the outdoor  
ambient temperature (±1°F).  
Note: For best results, use the same digital thermometer to check  
both outdoor ambient and liquid temperatures.  
Table 8  
506468-01  
Issue 1004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 16  
NOTE - The demand defrost board accurately  
measures the performance of the system as frost  
accumulates on the outdoor coil. This typically will  
translate into longer running time between defrost  
cycles as more frost accumulates on the outdoor coil  
before the board initiates defrost cycles.  
OPERATION  
Outdoor unit and indoor blower cycle on demand from the  
room thermostat. When the thermostat blower switch is  
moved to the ON position, the indoor blower operates  
continuously.  
Filter Drier  
DIAGNOSTIC LEDS  
The unit is equipped with a large capacity bi-flow filter  
which keeps the system clean and dry. If replacement is  
necessary, replace with one of similar design and  
capacity. The replacement filter drier must be suitable for  
use with R410A refrigerant.  
The state (Off, On, Flashing) of two LEDs on the defrost  
board (DS1 [Red] and DS2 [Green]) indicate diagnostics  
conditions that are described in table.  
Crankcase Heater  
If unit is equipped with a crankcase heater, it should  
be energized 24 hours before unit start-up to prevent  
compressor damage as a result of slugging.  
Emergency Heat Function (Room Thermostat)  
An emergency heat function is designed into some room  
thermostats. This feature is applicable when isolation of  
outdoor unit is required or when auxiliary electric heat is  
stage by outdoor thermostats. When the room thermostat  
is placed in the emergency heat position, the outdoor unit  
control circuit is isolated from power and the field-supplied  
relays bypass the outdoor thermostats. An amber  
indicating light simultaneously comes on to remind the  
homeowner that the unit is operating in the emergency  
heat mode.  
Emergency heat is usually used during an outdoor  
shutdown, but it should also be used following a power  
outage if power has been off for over an hour and the  
outdoor temperature is below 50°F. System should be left  
in the emergency heat mode at least 6 hours to allow the  
crankcase heater sufficient time to prevent compressor  
slugging.  
Mode  
Green Led (DS2)  
Red Led (DS1)  
OFF  
No power to control  
OFF  
Normal operation/  
power to control  
Anti-short cycle  
lockout  
Simultaneous Slow Flash  
Alternating Slow Flash  
DEMAND DEFROST SYSTEM DESCRIPTION  
The demand defrost controller measures differential  
temperatures to detect when the system is performing  
poorly because of ice build-up on the outdoor coil. The  
controller “self-calibrates” when the defrost system starts  
and after each system defrost cycle. The defrost control  
board components are shown below.  
Low pressure switch  
fault (Optional)  
Slow FLASH  
OFF  
Low pressure switch  
lockout (Optional)  
ON  
OFF  
High presssure switch  
fault (Optional)  
Slow FLASH  
OFF  
OFF  
High pressure switch  
lockout (Optional)  
OFF  
The control monitors ambient temperature, outdoor  
coil temperature, and total run time to determine when a  
defrost cycle is required. The coil temperature probe is  
designed with a spring clip to allow mounting to the  
outside coil tubing. The location of the coil sensor is  
important for proper defrost operation.  
506468-01  
Issue 1004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 17  
DEFROST BOARD PRESSURE SWITCH  
CONNECTIONS  
The unit’s automatic reset pressure switches (LO PS -  
S87 and HI PS - S4) are factory-wired into the defrost  
board on the LO-PS and HI-PS terminals, respectively.  
Sensor Temp. / Resistance Range  
Temperature  
Range °F (°C)  
Pins/Wire  
Color  
Red Led (DS1)  
Sensor  
Outdoor  
-35 (-37 to 120  
(48)  
3 & 4  
280,000 to 3750  
280,000 to 3750  
(Ambient)  
(Black)  
5 & 6  
-35 (-37) to 120  
(48)  
Coil  
(Brown)  
(OPTIONAL) Low Pressure Switch (LO-PS) — When  
the low pressure switch trips, the defrost board will cycle  
off the compressor, and the strike counter in the board  
will count one strike. The low pressure switch is ignored  
under the following conditions:  
Discharge (If  
applicable)  
24 (-4) to 350  
(176)  
1 & 2  
41,000 to 103  
(Yellow)  
Note: Sensor resistance decreases as sensed temperature increases.  
! during the defrost cycle and 90 seconds after the  
termination of defrost  
! when the average ambient sensor temperature is below  
15° F (-9°C)  
! for 90 seconds following the start up of the compressor  
! during “test” mode  
NOTE - When checking the ohms across a sensor, be  
aware that a sensor showing a resistance value that  
is not within the range shown, may be performing as  
designed. However, if a shorted or open circuit is  
detected, then the sensor may be faulty and the  
sensor harness will needs to be replaced.  
High Pressure Switch (HI-PS) — When the high  
pressure switch trips, the defrost board will cycle off the  
compressor, and the strike counter in the board will count  
one strike.  
Coil Sensor—The coil temperature sensor considers  
outdoor temperatures below -35°F (-37°C) or above  
120°F (48°C) as a fault. If the coil temperature sensor is  
detected as being open, shorted or out of the temperature  
range of the sensor, the board will not perform demand or  
time/temperature defrost operation and will display the  
appropriate fault code. Heating and cooling operation will  
be allowed in this fault condition.  
DEFROST BOARD PRESSURE SWITCH SETTINGS  
High Pressure (auto reset) - trip at 590 psig; reset at  
418.  
Low Pressure (auto reset) - trip at 25 psig; reset at 40.  
5-STRIKE LOCKOUT FEATURE  
The internal control logic of the board counts the pressure  
switch trips only while the Y1 (Input) line is active. If a  
pressure switch opens and closes four times during a Y1  
(Input), the control logic will reset the pressure switch trip  
counter to zero at the end of the Y1 (Input). If the  
pressure switch opens for a fifth time during the current  
Y1 (Input), the control will enter a lockout condition.  
Ambient Sensor—The ambient sensor considers  
outdoor temperatures below -35°F (-37°C) or above  
120°F (48°C) as a fault. If the ambient sensor is detected  
as being open, shorted or out of the temperature range of  
the sensor, the board will not perform demand defrost  
operation. The board will revert to time/temperature  
defrost operation and will display the appropriate fault  
code. Heating and cooling operation will be allowed in this  
fault condition.  
The 5-strike pressure switch lockout condition can be  
reset by cycling OFF the 24-volt power to the control  
board or by shorting the TEST pins between 1 and 2  
seconds. All timer functions (run times) will also be reset.  
NOTE - Within a single room thermostat  
demand, if 5-strikes occur, the board will lockout  
the unit. Defrost board 24 volt power “R” must  
be cycled “OFF” or the “TEST” pins on board  
must be shorted between 1 to 2 seconds to reset  
the board.  
If a pressure switch opens while the Y1 Out line is  
engaged, a 5-minute short cycle will occur after the switch  
closes.  
DEFROST SYSTEM SENSORS  
Sensors connect to the defrost board through a field–  
replaceable harness assembly that plugs into the board.  
Through the sensors, the board detects outdoor ambient,  
coil, and discharge temperature fault conditions. As the  
detected temperature changes, the resistance across the  
sensor changes. Sensor resistance values can be  
checked by ohming across pins .  
506468-01  
Issue 1004  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 18  
Defrost Temperature Termination Shunt (Jumper)  
Pins—The defrost board selections are: 50, 70, 90, and  
100°F (10, 21, 32 and 38°C). The shunt termination pin is  
factory set at 50°F (10°C). If the temperature shunt is not  
installed, the default termination temperature is 90°F  
(32°C).  
Actuation—When the reversing valve is de-energized,  
the Y1 circuit is energized, and the coil temperature is  
below 35°F (2°C), the board logs the compressor run  
time. If the board is not calibrated, a defrost cycle will be  
initiated after 30 minutes of heating mode compressor run  
time. The control will attempt to self-calibrate after this  
(and all other) defrost cycle(s).  
DELAY MODE  
The defrost board has a field-selectable function to  
reduce occasional sounds that may occur while the unit is  
cycling in and out of the defrost mode. When a jumper is  
installed on the DELAY pins, the compressor will be  
cycled off for 30 seconds going in and out of the defrost  
mode. Units are shipped with jumper installed on DELAY  
pins.  
Calibration success depends on stable system  
temperatures during the 20-minute calibration period. If  
the board fails to calibrate, another defrost cycle will be  
initiated after 45 minutes of heating mode compressor run  
time. Once the defrost board is calibrated, it initiates a  
demand def rost cycle when the difference between the  
clear coil and frosted coil temperatures exceeds the  
maximum difference allowed by the control OR after 6  
hours of heating mode compressor run time has been  
logged since the last defrost cycle.  
NOTE - The 30 second off cycle is NOT functional  
when jumpering the TEST pins.  
NOTE - If ambient or coil fault is detected, the board  
will not execute the “TEST” mode.  
OPERATIONAL DESCRIPTION  
The defrost control board has three basic operational  
modes: normal, calibration, and defrost.  
Termination—The defrost cycle ends when the coil  
temperature exceeds the termination temperature or after  
14 minutes of defrost operation. If the defrost is  
terminated by the 14-minute timer, another defrost cycle  
will be initiated after 30 minutes of run time.  
Normal Mode—The demand defrost board monitors the  
O line, to determine the system operating mode (heat/  
cool), outdoor ambient temperature, coil temperature  
(outdoor coil) and compressor run time to determine  
when a defrost cycle is required.  
Test Mode—When Y1 is energized and 24V power is  
being applied to the board, a test cycle can be initiated by  
placing the termination temperature jumper across the  
Test” pins for 2 to 5 seconds. If the jumper remains  
across the “Test” pins longer than 5 seconds, the control  
will ignore the test pins and revert to normal operation.  
The jumper will initiate one cycle per test.  
Calibration Mode—The board is considered uncalibrated  
when power is applied to the board, after cool mode  
operation, or if the coil temperature exceeds the  
termination temperature when it is in heat mode.  
Calibration of the board occurs after a defrost cycle to  
ensure that there is no ice on the coil. During calibration,  
the temperature of both the coil and the ambient sensor  
are measured to establish the temperature differential  
which is required to allow a defrost cycle.  
Enter the “TEST” mode by placing a shunt (jumper)  
across the “TEST” pins on the board after power-up.  
(The “TEST” pins are ignored and the test function is  
locked out if the shunt is applied on the “TEST” pins  
before power-up). Board timings are reduced, the low-  
pressure switch is ignored and the board will clear any  
active lockout condition.  
Defrost Mode—The following paragraphs provide a  
detailed description of the defrost system operation.  
DETAILED DEFROST SYSTEM OPERATION  
Defrost Cycles—The demand defrost control board  
initiates a defrost cycle based on either frost detection or  
time.  
Each test pin shorting will result in one test event.  
For each “TEST” the shunt (jumper) must be removed for  
at least 1 second and reapplied. Refer to flow chart for  
“TEST” operation.  
!
Frost Detection—If the compressor runs longer than  
30 minutes and the actual difference between the  
clear coil and frosted coil temperatures exceeds the  
maximum difference allowed by the control, a defrost  
cycle will be initiated.  
Note: The Y1 input must be active (ON) and the “O”  
room thermostat terminal into board must be  
inactive.  
IMPORTANT - The demand defrost control board  
will allow a greater accumulation of frost and will  
initiate fewer defrost cycles than a time/  
DEFROST BOARD DIAGNOSTICS  
See defrost control board diagnostic LED table on next  
page to determine defrost board operational conditions  
and to diagnose cause and solution to problems.  
temperature defrost system.  
!
Time—If 6 hours of heating mode compressor run  
time has elapsed since the last defrost cycle while the  
coil temperature remains below 35°F (2°C), the  
demand defrost control will initiate a defrost cycle.  
506468-01  
Issue 1004  
Page 19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506468-01  
Issue 1004  
Page 20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Defrost Control Board Diagnostic LEDs  
506468-01  
Issue 1004  
Page 21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Diagnostic Module  
flashes correlates to a particular abnormal condition.  
TRIP LED (Red) indicates there is a demand signal from  
the thermostat but no current to the compressor is de-  
tected by the module. The TRIP LED typically indicates  
the compressor protector is open or may indicate missing  
supply power to the compressor.  
4HP16LT units contain a diagnostic module for trouble-  
shooting heat pump system failures. By monitoring and  
analyzing data from the compressor and thermostat  
demand, the module can accurately detect the cause of  
electrical and system related failure without any sensors.  
If a system problem occurs, a flashing LED indicator  
communicates the failure code.  
Interpreting the Diagnostic LEDs  
When an abnormal system condition occurs, the diagnos-  
tic module displays the appropriate ALERT and/or TRIP  
LED. The yellow ALERT LED will flash a number of times  
consecutively, pause, and then repeat the process. To  
identify a flash code number, count the number of con-  
secutive flashes. Refer to Table 10 below and Table 11 on  
page 20 for information on the flash codes.  
LED Description  
POWER LED (Green) indicates voltage is present at the  
power connection of the module.  
ALERT LED (Yellow) communicates an abnormal system  
condition through a unique flash code. The ALERT LED  
will flash a number of times consecutively, pause, and  
then repeat the process. The number of consecutive  
Every time the module powers up, the last ALERT LED  
flash code that occurred prior to shutdown is displayed for  
Flash Codes  
LED  
Status  
Fault Description  
Troubleshooting Information  
POWER  
(Green)  
Module has power  
Supply voltage is present at module terminals  
1. Compressor protector is open  
* Check for high head pressure  
Thermostat demand  
signal Y1 is present,  
but the compressor  
is not running  
* Check compressor supply voltage  
TRIP  
(Red)  
2. Outdoor unit power disconnect is open  
3. Compressor circuit breaker or fuse(s) is open  
4. Broken wire or connector is not making contact  
5. Low pressure switch open if present in system  
6. Compressor contactor has failed open  
Long Run Time  
Compressor is  
running  
extremely long run  
cycles  
ALERT  
(Yellow)  
Flash  
--  
Code 1  
(Not applicable on  
heat pump models)  
1. High head pressure  
* Check high pressure switch if present in system  
* Check if system is overcharged with refrigerant  
* Check for non-condensable in system  
2. Condenser coil poor air circulation (dirty, blocked, damaged)  
3. Condenser fan is not running  
System  
Pressure Trip  
Discharge or suction  
pressure  
ALERT  
(Yellow)  
Flash  
out of limits or  
compressor  
* Check fan capacitor  
* Check fan wiring and connectors  
Code 2  
overloaded  
* Check fan motor for failure or blockage  
4. Return air duct has substantial leakage  
5. If low pressure switch present in system, check Flash Code 1 info  
Table 10  
506468-01  
Issue 1004  
Page 22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
60 seconds. The module will continue to display the  
previous flash code until the condition returns to normal or  
24VAC is removed from the module. TRIP and ALERT  
LEDs flashing at the same time means control circuit  
voltage is too low for operation.  
24VAC Power Wiring  
The diagnostic module requires a constant nominal  
24VAC power supply. The wiring to the module’s R and C  
terminals must be directly from the indoor unit or thermo-  
stat. The module cannot be powered by R and C terminals  
on the defrost board without experiencing nuisance alerts.  
Flash Codes (cont.)  
LED  
Status  
Fault Description  
Troubleshooting Information  
1. Thermostat demand signal is in  
2. Time delay relay or control board defective  
3. If high pressure switch present, go to Flash Code 2 info  
4. If low pressure switch present, go to Flash Code 1 info  
termittent  
ALERT  
(Yellow)  
Flash  
Short Cycling  
Compressor is  
running  
Code 3  
only briefly  
1. Run capacitor has failed  
ALERT  
(Yellow)  
Flash  
2. Low line voltage (contact utility if voltage at disconnect is low)  
* Check wiring connections  
3. Excessive liquid refrigerant in compressor  
4. Compressor bearings are seized  
*Measure compressor oil level  
Locked Rotor  
Code 4  
1. Outdoor unit power disconnect is open  
2. Compressor circuit breaker or fuse(s) is open  
3. Compressor contactor has failed open  
* Check compressor contactor wiring and connectors  
* Check for compressor contactor failure (burned, pitted, or open)  
* Check wiring and connectors between supply and compressor  
* Check for low pilot voltage at compressor contactor coil  
4. High pressure switch is open and requires manual reset  
5. Open circuit in compressor supply wiring or connections  
6. Unusually long compressor protector reset time due to extreme ambient temperature  
7. Compressor windings are damaged  
ALERT  
(Yellow)  
Flash  
Open Circuit  
Code 5  
* Check compressor motor winding resistance  
1. Run capacitor has failed  
ALERT  
(Yellow)  
Flash  
Open Start Circuit  
Current only in run  
circuit  
2. Open circuit in compressor start wiring or connections  
* Check wiring and connectors between supply and the compressor S terminal  
3. Compressor start winding is damaged  
Code 6  
* Check compressor motor winding resistance  
ALERT  
(Yellow)  
Flash  
1. Open circuit in compressor run wiring or connections  
* Check wiring and connectors between supply and the compressor R terminal  
2. Compressor run winding is damaged  
Open Run Circuit  
Current only in start  
circuit  
Code 7  
* Check compressor motor winding resistance  
ALERT  
(Yellow)  
Flash  
Welded Contactor  
Compressor always  
runs  
1. Compressor contactor has failed closed  
2. Thermostat demand signal not connected to module  
Code 8  
ALERT  
(Yellow)  
Flash  
Low Voltage  
Control circuit less  
than 17VAC  
1. Control circuit transformer is overloaded  
2. Low line voltage (contact utility if voltage at disconnect is low)  
* Check wiring conditions  
Code 9  
Table 11  
Page 23  
Issue 1004  
506468-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Thermostat Demand Wiring  
Miswired Module Codes  
The diagnostic module requires a thermostat demand  
signal to operate properly. The thermostat demand signal  
input, labeled Y on the module, should always be con-  
nected to the compressor contactor coil so that when the  
coil is energized, the demand signal input is 24VAC.  
When the coil is not energized, the demand signal input  
should be less than 0.5VAC.  
Depending on the system configuration, some ALERT  
flash codes may not be active. The presence of safety  
switches affects how the system alerts are displayed by  
the module.  
Miswiring the diagnostic module will cause false LED  
codes. Table 12 describes LED operation when the  
module is miswired and what troubleshooting action is  
required to correct the problem.  
Miswired Module Troubleshooting  
Miswired Module Indication  
Recommended Troubleshooting Action  
Determine if both R and C module terminals are connected. Verify voltage is present  
at module's R and C terminals. Review 24VAC Power Wiring section on page 20 for  
R and C wiring.  
Green LED is not on,  
module does not power up.  
Green LED intermittent,  
module powers up only  
when compressor runs.  
Determine if R and Y terminals are wired in reverse. Verify module's R and C  
terminals have a constant source. Review 24VAC Power Wiring section on page 20  
for R and C wiring.  
TRIP LED is on but system  
and compressor check OK.  
Verify Y terminal is connected to 24VAC at contactor coil. Verify voltage at contactor  
coils falls below 0.5VAC when off.  
TRIP LED and ALERT LED  
flashing together.  
Verify R and C terminals are supplied with 19-28VAC.  
ALERT Flash Code 3  
(Compressor Short Cycling)  
displayed incorrectly.  
Verify Y terminal is connected to 24VAC at contactor coil. Verify voltage at contactor  
coil falls below 0.5VAC when off.  
ALERT Flash Code 5, 6, or 7  
(Open Circuit, Open Start  
Circuit, or Open Run Circuit)  
displayed incorrectly.  
Check that compressor run and start wires are through module's current sensing  
holes. Verify Y terminal is connected to 24VAC at contactor coil. Verify voltage at  
contactor coil falls below 0.5VAC when off.  
ALERT Flash Code 6  
(Open Start Circuit)  
displayed for Code 7  
(Open Run Circuit)  
or vice versa.  
Check that compressor run and start wires are routed through the correct module  
sensing holes.  
Determine if module's Y terminal is connected. Verify Y terminal is connected to 24VAC at  
contactor coil. Verify 24VAC is present across Y and C when thermostat demand signal is  
present. If not, R and C are reverse wired. Verify voltage at contactor coil falls below  
0.5VAC when off. Review Thermostat Demand Wiring on this page for Y and C wiring.  
ALERT Flash Code 8  
(Welded Contactor)  
displayed incorrectly.  
Table 12  
506468-01  
Issue 1004  
Page 24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTENANCE  
WARNING  
Before performing maintenance operations on  
system, turn the electric power to unit OFF at  
disconnect switch(es). Unit may have multiple  
power supplies. Electrical shock could cause  
personal injury or death.  
Before the start of each heating and cooling season, the  
following service checks should be performed by a  
qualified service technician.  
Inspect and clean outdoor and indoor coils. The  
outdoor coil may be flushed with a water hose.  
NOTE: It may be necessary to flush the outdoor coil  
more frequently if it is exposed to substances which  
are corrosive or which block airflow across the coil  
(such as pet urine, cottonwood seeds, etc...).  
Visually inspect the refrigerant lines and coils for leaks.  
Check wiring for loose connections.  
Check voltage at the indoor and outdoor units (with  
units operating).  
Check amperage draw at the outdoor fan motor,  
compressor, and indoor blower motor. Values should  
be compared with those given on unit nameplate.  
Check, clean (or replace) indoor unit filters.  
Check the refrigerant charge and gauge the system  
pressures.  
Check the condensate drain line for free and unob-  
structed flow. Clean drain line, if necessary.  
Adjust blower speed for cooling. Measure the pressure  
drop over the coil to determine the correct blower CFM.  
Belt drive blowers: Check drive belt for wear and  
proper tensions.  
If insufficient cooling is reported, the unit should be  
gaugedand refrigerant charge checked (see Refrigerant  
Charging on page 12).  
Page 25  
Issue 1004  
506468-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
is exposed to substances which are corrosive or  
which block airflow across the coil (such as pet urine,  
cottonwood seeds, etc...).  
HOMEOWNER INFORMATION  
In order to ensure peak performance, your system must be  
properly maintained. Clogged filters and blocked airflow  
prevent your unit from operating at its most efficient level.  
Heat Pump Operation  
Heat pump units have several characteristics you should  
be aware of:  
WARNING  
Turn all electric power to unit OFF at discon-  
nect switch(es) before performing any mainte-  
nance operations on system. Unit may have  
multiple power supplies. Electrical shock could  
cause personal injury or death.  
Heat pumps satisfy heating demand by delivering  
large amounts of warm air into the living space. This  
is quite different from gas-fired, oil-fired, or electric  
furnaces which deliver lower volumes of considerably  
hotter air to heat the space.  
Do not be alarmed if you notice frost on the outdoor  
coil in the winter months. Frost develops on the  
outdoor coil during the heating cycle when tempera-  
tures are below 45°F. An electronic control activates a  
defrost cycle lasting 5 to 15 minutes at preset inter-  
vals to clear the outdoor coil of the frost. A shift in  
sound type does occur during the defrost mode.  
Ask your dealer to show you where the indoor unit’s  
filter is located. It will be either at the indoor unit  
(installed internal or external to the cabinet) or behind  
a return air grille in the wall or ceiling. Check the filter  
monthly and clean or replace it as needed.  
Disposable filters should be replaced with a filter of  
the same type and size. If you unsure of the filter you  
need for your system, contact your dealer.  
During the defrost cycle, you may notice steam rising  
from the unit. This is a normal occurrence. The  
thermostat may engage auxiliary heat during the  
defrost cycle to satisfy a heating demand. The unit will  
return to normal operation at the conclusion of the  
defrost cycle.  
Many indoor units are equipped with reusable foam  
filters. These filters can be cleaned with a mild soap  
and water solution. Rinse the filter thoroughly and let  
dry completely before returning to unit or grille.  
In case of extended power outage...  
The filter and all access panels must be in place  
any time the unit is in operation.  
If the outdoor temperature is below 50°F and power to the  
outdoor unit has been interrupted for 6 hours or longer,  
observe the following when restoring power to the heat  
pump system.  
Some systems are equipped with an electronic air  
cleaner, designed to remove the majority of airborne  
particles from the air passing through the cleaner. If  
your system includes an electronic air cleaner, ask  
your dealer for maintenance instructions.  
Set the room thermostat selector to the “Emergency  
Heat” setting to obtain temporary heat for a minimum  
of 6 hours. This will allow system refrigerant pres-  
sures and temperatures enough time to return to a  
stabilized condition.  
Inspect and clean indoor coil. The indoor evaporator  
coil is equipped with a drain pan to collect condensate  
formed as the system removes humidity from the  
inside air. Have your dealer show you the location of  
the drain line and how to check for obstructions. This  
also applies to an auxiliary drain, if one is installed.  
In the Emergency Heat mode, all heating demand is  
satisfied by auxiliary heat; heat pump operation is  
locked out. After a 6-hour “warmup” period, the  
thermostat can then be switched to the “Heat” setting  
and normal heat operation may resume.  
Inspect and clean outdoor coil:  
Make sure no obstructions restrict airflow to the  
outdoor unit. Leaves, trash, or shrubs crowding the unit  
can cause it to work harder and use more energy. Keep  
shrubbery trimmed away from the unit and periodically  
check for debris which collects around the unit.  
Thermostat Operation  
Though your thermostat may vary somewhat from the  
description below, its operation will be similar.  
Temperature Setting Levers  
The outdoor coil may require frequent cleaning,  
depending on environmental conditions. Clean the  
outdoor coil with an unpressurized water hose to  
remove surface contaminants and debris. It may be  
necessary to flush the outdoor coil more frequently if it  
Most heat pump thermostats have two temperature  
selector levers: one for heating and one for cooling. Set  
the levers or dials to the desired temperature setpoints for  
both heating and cooling. Avoid frequent temperature  
506468-01  
Issue 1004  
Page 26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
adjustment; turning the unit off and back on before  
pressures equalize puts stress on unit compressor.  
Preservice Check  
If your system fails to operate, check the following before  
calling for service:  
Fan Switch  
In AUTO or INT (intermittent) mode, the blower operates  
only when the thermostat calls for heating or cooling. This  
mode is generally preferred when humidity control is a  
priority. The ON or CONT mode provides continuous indoor  
blower operation, regardless of whether the compressor or  
auxiliary heat are operating. This mode is required when  
constant air circulation or filtering is desired.  
Check to see that all electrical disconnect switches  
are ON.  
Make sure the thermostat temperature selector is  
properly set.  
Make sure the thermostat system switch is properly set.  
Replace any blown fuses, or reset circuit breakers.  
Make sure unit access panels are in place.  
Make sure air filter is clean.  
System Switch  
Set the system switch for heating, cooling, or auto opera-  
tion. The auto mode allows the heat pump to automatically  
switch from heating mode to cooling mode to maintain  
predetermined comfort settings. Many heat pump thermo-  
stats are also equipped with an emergency heat mode  
which locks out heat pump operation and provides  
temporary heat supplied by the auxiliary heat.  
Locate unit model number and have it handy before  
calling.  
Indicating Light  
Most heat pump thermostats have an amber light which  
indicates when the heat pump is operating in the emer-  
gency heat mode.  
Temperature Indicator  
The temperature indicator displays the actual room  
temperature.  
Programmable Thermostats  
Your system may be controlled by a programmable thermo-  
stat. These thermostats provide the added feature of  
programmable time-of-day setpoints for both heating and  
cooling. Refer to the user’s information manual provided  
with your particular thermostat for operation details.  
Page 27  
Issue 1004  
506468-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start-Up and Performance Checklist  
Job Name _______________________________  
Job No. ________________  
City ___________________  
City ___________________  
Date ______________  
State ______________  
State ______________  
Job Location _____________________________  
Installer _________________________________  
Unit Model No.______________  
Serial No. ___________________  
Service Technician ________________________________________  
Nameplate Voltage ______________  
Rated Load Ampacity ________  
Maximum Fuse or Circuit Breaker________________________  
Compressor Amperage ____________ Outdoor Fan ______________  
Electrical Connections Tight?  
Indoor Filter Clean?  
Supply Voltage (Unit Off) ________________  
Indoor Blower RPM _____________  
S.P. Drop Over Indoor (Dry) ____________  
Outdoor Coil Entering Air Temperature _____________  
Voltage with Compressor Operating _____________  
Outdoor Fan Checked?  
Cooling  
Liquid Line Pressure __________  
Suction Line Pressure ___________ Refrigerant Charge Checked?  
Heating  
Liquid Line Pressure __________  
Suction Line Pressure ___________  
Refrigerant Charge Checked?  
Refrigerant Lines: Leak Checked?  
Service Valves: Fully Opened?  
Properly Insulated?  
Caps Tight?  
Thermostat: Calibrated?  
Properly Set?  
Level?  
Sequence of Operation  
Heating Correct?  
Cooling Correct?  
506468-01  
Issue 1004  
Page 28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Single Stage Wire Diagram  
506468-01  
Issue 1004  
Page 29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Two Stage Wire Diagram  
506468-01  
Issue 1004  
Page 30  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Access Personal Computer AIM 16 User Manual
Adesso Mouse AKB 805MAC User Manual
Aga Ranges Range U104613 03 User Manual
Aiwa Stereo System NSX DS8 User Manual
Alpine CD Player CDA W560EG User Manual
Amana Dishwasher ADB1000AW User Manual
Ask Proxima Projector C2 COMPACT User Manual
Atlona Home Theater System 64 M User Manual
Audiovox Automobile Alarm PRO 9842 User Manual
Beckett Water Gardening Plumbing Product G90AG User Manual