Installation
User and
Service Manual
XTRA HIGH EEFFICCIIENCY
WATER PRODUCTS
COMPANY
A DIVISION OF A. O. SMITH CORPORATION
Download from Www.Somanuals.com. All Manuals Search And Download.
gis
Read this manual carefully
Warning
Read this manual carefully before starting up the water heater. Failure to
read this manual and to follow the instructions in this manual may lead to
accidents, personal injury, and damage to the appliance.
Copyright © 2008 A.O. Smith water Products Company
All rights reserved.
Nothing from this publication may be copied, reproduced and/or published by
means of printing, photocopying or by whatsoever means, without the prior
written approval of A.O. Smith water Products Company.
A.O. Smith water Products Company reserves the right to modify specifications
stated in this manual.
Any brand names mentioned in this manual are registered trademarks of their
respective owners.
Trademarks
Liability
A.O. Smith water Products Company accepts no liability for claims from third
parties arising from improper use other than that stated in this manual and in
accordance with the General Conditions registered at the Eindhoven Chamber
of Commerce.
Refer further to the General Conditions. These are available on request, free of
charge.
Although considerable care has been taken to ensure a correct and suitably
comprehensive description of all relevant components, the manual may
nonetheless contain errors and inaccuracies.
Should you detect any errors or inaccuracies in the manual, we would be
grateful if you would inform us. This helps us to further improve our
documentation.
If you have any comments or queries concerning any aspect related to the
appliance, then please do not hesitate to contact:
More information
A.O. Smith water Products Company
PO Box 70
5500 AB Veldhoven
Netherlands
Telephone:
(free) 0870 - AOSMITH
0870 - 267 64 84
General:
Fax:
+31 40 294 25 00
+31 40 294 25 39
E-mail :
Website:
In the event of problems with connecting to the gas, electricity or water supply,
please contact your installation's supplier/installation engineer .
Instruction manual BFC
3
Download from Www.Somanuals.com. All Manuals Search And Download.
gis
4
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
gis
Table of contents
Instruction manual BFC
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of contents
6
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
Instruction manual BFC
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of contents
8
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
gis
1 Introduction
This manual describes how to install, service and use the BFC appliance. The
BFC appliance is a condensing water heater with a fan in the air intake. The
BFC can be installed as either an open or room-sealed appliance. A concentric
chimney connector is fitted standard to the appliance. Alternatively, the
appliance can be connected using a parallel system.
1.1 About the appliance
The alternative installation types are B23, C13, C33, C43, C53 and C63.
The information in this manual applies to the: BFC 28, BFC 30, BFC 50 and BFC
60.
The appliance has been manufactured and equipped in accordance with the
European standard for gas-fired storage water heaters for the production of
domestic hot water (EN 89). The appliances are therefore compliant with the
European Directive for Gas Appliances, and and are entitled to bear the CE
mark.
Warning
Read this manual carefully before starting up the water heater. Failure to
read the manual and to follow the printed instructions may lead to personal
injury and damage to the appliance.
Warning
If there is a gas smell:
1.2 What to do if you
smell gas
No naked flames! No smoking!
Avoid causing sparks! Do not use any electrical equipment or switch, i.e. no
telephones, plugs or bells!
Open windows and doors!
Shut off the mains gas supply valve!
Warn occupants and leave the building!
After leaving the building, alert the gas distribution company or your installation
engineer.
As the (end) user, installation engineer or service and maintenance engineer,
you must ensure that the entire installation complies, as a minimum, with the
official local:
1.3 Regulations
•
•
•
•
•
•
•
•
•
•
building regulations;
energy supplier's directives for existing gas installations;
directives and technical guidelines for natural gas installations;
safety requirements for low-voltage installations;
regulations governing the supply of drinking water;
regulations governing ventilation in buildings;
regulations governing the supply of air for combustion;
regulations governing the discharge of products of combustion;
requirements for installations that consume gas;
regulations governing indoor waste water disposal;
Instruction manual BFC
9
Download from Www.Somanuals.com. All Manuals Search And Download.
1
Introduction
gis
regulations imposed by fire brigade, power companies and municipality.
•
Furthermore, the installation must comply with the manufacturer's instructions.
Note
Later amendments and/or additions to all regulations, requirements and
guidelines published on or prior to the moment of installing, will apply to the
installation.
The three target groups for this manual are:
1.4 Target groups
•
•
•
(end) users;
installation engineers;
service and maintenance engineers.
Symbols on each page indicate the target groups for whom the information is
intended. See the table.
Target group symbols
Symbol
Target group
(End) user
Installation engineer
Service and maintenance engineer
A service should be carried out at least once a year, both on the water side and
on the gas side. Maintenance frequency depends, among other things, on the
water quality, the average burning time per day and the set water temperature.
1.5 Maintenance
Note
To determine the correct maintenance frequency, it is recommended to
arrange for the service and maintenance engineer to check the appliance on
both the water and gas side within three months following installation. Based on
this check, the best maintenance frequency can be determined.
Note
Regular maintenance extends the service life of the appliance.
Note
Both the end user and the service and maintenance engineer are
responsible for regular maintenance. They will need to establish clear
agreements on this.
Note
If the appliance is not regularly maintained, the warranty will become void.
10
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
gis
1.6 Forms of notation
The following notation is used in this manual:
Note
Important information.
Attention
Ignoring this information can lead to the appliance being damaged.
Warning
Failure to carefully read this information may lead to personal injury and
serious damage to the appliance.
Instruction manual BFC
11
Download from Www.Somanuals.com. All Manuals Search And Download.
1
Introduction
gis
The table provides an overview of the contents of this document.
1.7 Overview of this
document
Contents of this document
Chapter
Target groups
Description
This chapter describes how the appliance functions.
This chapter describes the installation activity to be
completed before you actually start up the appliance.
This chapter describes how to fill the appliance.
This chapter describes how to drain the appliance.
This chapter describes the general control of the
appliance using the display.
This chapter describes the status (mode or condition) that
the appliance may have, and possible actions to take.
This chapter describes how to start the appliance running.
The general heating cycle of the appliance is also
described.
This chapter describes how to shut the appliance down for
a brief or long period of time.
This chapter describes the main menu of the display. This
is the actual menu for the user, however the installation
engineer and service and maintenance engineers will also
need to use this menu.
This chapter describes the service menu. It is mainly
intended for the installation engineer and service and
maintenance engineers. End users may also refer to this
chapter for additional information about the appliance.
This chapter is mainly intended for the installation
engineer and the service and maintenance engineer. It
describes appliance errors. These errors are indicated on
the display. A troubleshooting table of possible causes
and solutions is provided. End users may also refer to this
chapter for additional information about the appliance.
This chapter describes how to determine the optimum
frequency at which to carry out maintenance. Both the
end user and the service and maintenance engineer are
responsible for regular maintenance. They need to reach
clear agreement on this.
Note
If the appliance is not regularly maintained, the
warranty will become void.
This chapter sets out the maintenance tasks to be carried
out during a service.
This chapter states the warranty terms and conditions.
12
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
gis
2 Working principle of
the appliance
Topics covered in this chapter:
2.1 Introduction
•
•
•
•
The figure shows a cut-away view of the appliance.
2.2 General working
principle of the
appliance
Cut-away view of the appliance
1
2
3
4
Legend
16
17
18
Only applicable numbers are
mentioned.
1. cover
2. hot water outlet
3. electrical connector block
4. electronic controller
5. pressure switch
6. control panel
19
5
6
7. temperature sensor T
8. combustion chamber
9. anode
1
20
21
7
8
10. tank
11. heat exchanger
12. inspection and cleaning opening 9
13. temperature sensor T
14. cold water inlet
15. drain valve
16. gas control
17. burner
2
10
22
11
18. fan
19. air supply hose
20. hot surface igniter
21. flame probe
22. chimney pipe
23. siphon
12
24. insulation layer
13
14
15
23
24
IMD-0070 R1
Instruction manual BFC
13
Download from Www.Somanuals.com. All Manuals Search And Download.
2
Working principle of the appliance
gis
In this appliance the cold water enters the bottom of the tank via the cold water
inlet (14). Once heated by the combustion chamber (8) and heat exchanger
(11), the hot tapwater leaves the tank through the hot water outlet (2). Once the
appliance is completely filled with water, it remains constantly under water
supply pressure. As hot water is drawn from the appliance, it is immediately
replenished with cold water.
The air required for combustion is forced into the burner (17) by the fan (18).
The gas is fed to the burner via the gas valve (16). Thanks to the modulated
supply of gas and air, the optimum gas/air mixture is always achieved. The
special construction of the burner causes the mixture to form a vortex (the
cyclone effect), before it becomes ignited. This vorticity improves the ignition on
the hot surface igniter (20), as well as ensuring optimum combustion efficiency.
Through the special design of the heat exchanger (11), the flue gases are first
led downwards via the combustion chamber, then upwards again via the heat
exchanger, then once more downwards beside the water in the tank. In this
process, the flue gases gradually become cooler. Because the cooled flue
gases flow alongside the cold water lower down in the tank, they start to
condense. This condensation causes latent heat energy to be released, which
is transferred to the cooler water, thereby increasing the energy performance of
the unit. The condensate yielded by this process is discharged via the siphon
(23).
The insulation layer (24) prevents heat from escaping. The inside of the tank is
enamelled to protect against corrosion. The anodes (9) provide extra protection
against corrosion.
For use during maintenance, the appliance has an inspection and cleaning
opening (12).
2.3 The appliance's
heating cycle
The water temperature is measured by temperature sensors T1 (7) in the top of
the tank (10) and T2 (13) at the bottom of the tank. These temperatures are sent
to the electronic controller. Based on these two observations, the electronic
controller calculates a net water temperature: T . The value of T lies
net
net
between the temperatures at the top and bottom of the tank. As soon as
Tnet
falls below the set water temperature (T ), the electronic controller registers a
set
"heat demand". The gas control (16) is opened, and the gas is mixed with air.
This mixture is ignited by the hot surface igniter (20) and the water becomes
heated. As soon as
rises above T the heat demand ends, and the
Tnet
set
electronic controller stops the heating cycle.
The electronic controller assumes a certain margin both when registering and
ending heat demand. We refer to this margin as the hysteresis (12.2 "Setting
2.4 Protection for the
appliance
2.4.1 Introduction
The electronic controller monitors the water temperature and ensures safe
combustion. This is achieved by:
•
•
•
•
•
14
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
gis
2.4.2 Water temperature protection
The electronic controller uses temperatures sensors T1 (7) and T2 (13) to
monitor three temperatures that are important for safety. The table explains the
functioning of the temperature sensors.
Temperature protection
Protection
Description
Against frost
The frost protection cuts in. The water is heated to 20°C.
(T1 < 5°C or T2 < 5°C)
For maximum water temperature The high-limit safeguard serves to prevent overheating and/or excessive
(T1 > 85°C or T2 > 85°C)
formation of scale in the appliance. If the high-limit safeguard is activated, the
heating is stopped. This causes the water in the tank to cool down. Once the
water has cooled sufficiently (T1 < 78°C), the electronic controller resets the
appliance.
For extra safety
(T1 > 93°C or T2 > 93°C)
A lockout error of the water heater controller takes place. The controller must
be manually reset before the appliance can resume operation (8.3 "Error
1
2.4.3 Gas valve
The electronic controller opens the gas valve so that gas can be supplied to the
burner. As a safety measure, the gas valve has a double shut-off. The double
shut-off guarantees complete isolation of the appliance from the gas supply.
To help ensure smooth ignition, the gas valve opens gradually ('softlite").
2.4.4 Fan
The fan (18) provides an optimum air supply when there is a heat demand. As
a safety feature, the fan ensures that any gases present in the combustion
chamber are removed, both before and after combustion. We refer to this as
pre- and post-purge.
The fan speed is continuously monitored by the electronic controller (4). The
electronic controller takes control if the speed of rotation varies too much from
the set value.
2.4.5 Pressure switch
The pressure switch ensures the discharge of flue gases and the supply of
incoming air during the pre-purge and normal running of the appliance. The
default state of the pressure switch is open. When sufficient pressure difference
is reached, the pressure switch closes. However, in the event of a fault, the
pressure switch is tripped open, and the heating cycle is interrupted. The table
shows the trip point per appliance.
Note
The trip point of the pressure switch is not adjustable.
Pressure switch trip points
Appliance Closing pressure
differential
Opening pressure differential
< 605 Pa
BFC
28
> 635 Pa
> 855 Pa
> 885 Pa
> 1085 Pa
BFC
30
< 825 Pa
BFC
50
< 855 Pa
BFC
60
< 1055 Pa
Instruction manual BFC
15
Download from Www.Somanuals.com. All Manuals Search And Download.
2
Working principle of the appliance
gis
2.4.6 Flame probe
To ensure that no gas can flow when there is no combustion, the water heater
is fitted with a flame probe (21). The electronic controller uses this probe to
detect the presence of a flame, by means of ionisation detection. The electronic
controller closes the gas control the instant it detects that there is a gas flow but
no flame.
2.5 Safety of the instal-
lation
In addition to the appliance's standard built-in safety monitoring, the appliance
must also be protected by an expansion vessel, expansion valve, pressure
reducing valve, non-return valve and a T&P valve.
The use of an expansion vessel, expansion valve and/or pressure reducing
valve depends on the type of installation: unvented or vented.
2.5.1 Unvented installation
With an unvented installation, an expansion valve valve and expansion vessel
prevent the buildup of excessive pressure in the tank. This prevents damage
being caused to the enamelled coating (in the appliance) or to the tank. A non-
return valve prevents excessive pressure buildup in the water supply system.
This valve also prevents water from flowing backwards from the tank into the
cold water supply system. The pressure reducing valve protects the installation
against an excessively high water supply pressure (> 8 bar). These components
2.5.2 Vented installation
With a vented installation, excess pressure is taken up by the open cold water
head tank. The height of the head tank determines the working pressure in the
water heater, which may not exceed 8 bar. The installation must also be fitted
with a vent pipe from the hot water pipe, that opens into the cold water tank.
Ideally, the vent pipe should discharge into a separate tundish/drain or
otherwise to the open cold water head tank. The water heater should also be
2.5.3 T&P valve
A T&P valve is only mandatory in an unvented installation. However, A.O. Smith
also recommends the use of a T&P valve in vented installations.
A T&P (Temperature and Pressure Relief) valve monitors the pressure in the
tank and the water temperature at the top of the tank. If the pressure in the tank
becomes excessive (> 10 bar) or the water temperature is too high (> 97°C), the
valve will open. The hot water can now flow out of the tank. Because the
appliance is under water supply pressure, cold water will automatically flow into
the tank. The valve remains open until the unsafe situation has been rectified.
The appliance is fitted standard with a connecting point for a T&P
16
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
is
3 Installation
Warning
Installation work should be carried out by an approved installation engineer
in compliance with the general and local regulations imposed by the gas, water
and power supply companies and the fire service.
The appliance may only be installed in a room that complies with the
requirements stated in national and local ventilation
This chapter describes the installation activities to be carried out before you
3.1 Introduction
•
•
•
•
•
•
•
•
•
In the event of conversion to a different gas category, see
To avoid damaging the appliance, remove the packaging carefully.
We recommend unpacking the appliance at or near its intended location.
3.2 Packaging
Attention
The appliance may only be manoeuvred in an upright position. Take care
that the appliance is not damaged after unpacking.
The appliance is suitable for either open or room-sealed combustion. If
installed as a room-sealed appliance, then the availability of the necessary
external air supply will depend on the place of installation. In this event, there
are no additional ventilation requirements.
3.3 Environmental
conditions
If the appliance is to be installed as an open system, then it will be subject to
the guidelines and ventilation regulations that are in force locally.
The alternative installation types are B23, C13, C33, C43, C53 and C63.
Attention
The appliance may not be used in rooms where chemical substances are
stored or used, due to the risk of explosion and/or corrosion of the appliance.
Some propellants, bleaching agents, degreasing agents etc. disperse vapours
which are explosive and/or which cause accelerated corrosion. If the appliance
is used in a room in which such substances are present, the warranty will be
void.
Instruction manual BFC
17
Download from Www.Somanuals.com. All Manuals Search And Download.
3
Installation
is
3.3.1 Air humidity and ambient temperature
The boiler room must be frost-free, or be protected against frost. The table
shows the environmental conditions that must be adhered to for correct
functioning of the electronics present in the appliance to be guaranteed.
Air humidity and ambient temperature specifications
Air humidity and ambient temperature
Air humidity
max. 93% RV at +25°C
Functional: 0 < T < 60°C
Ambient temperature
3.3.2 Appliance maximum floor load
In connection with the appliance's weight, take account of the maximum floor
loading, refer to the table.
Weight specifications related to maximum floor load
Weight of the appliance filled with water
BFC 28
394 kg
582 kg
BFC 30, BFC 50, BFC 60
3.3.3 Water composition
The appliance is intended for heating drinking water. The drinking water must
comply with the regulations governing drinking water for human consumption.
The table gives an overview of the specifications.
Water specifications
Water composition
Hardness
> 1.00 mmol/l:
(alkaline earth ions)
•
•
•
German hardness> 5.6° dH
French hardness > 10.0° fH
English hardness > 7.0° eH
Conductivity
> 125 µS/cm
Acidity (pH value)
7.0 < pH value < 9.5
Note
If the water specifications deviate from those stated in the table, then the
3.3.4 Working clearances
For access to the appliance, it is recommended that the following clearances
are observed (see figure):
•
•
•
AA: around the appliance's control column and cleaning openings: 100 cm.
BB: all sides of the appliance: 50 cm.
Above the appliance (room to replace the anodes):
-
-
100 cm if using fixed anodes, or
50 cm if using flexible anodes.
18
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
is
If the available clearance is less than 100 cm, flexible magnesium anodes
may be ordered.
Note
When installing the appliance, be aware that any leakage from the tank
and/or connections can cause damage to the immediate environment or floors
below the level of the boiler room. If this is the case, the appliance should be
installed above a wastewater drain or in a suitable metal leak tray.
The leak tray must have an appropriate wastewater drain and must be at least
5cm deep with a length and width at least 5cm greater than the diameter of the
appliance.
Working clearances
IMD-0228 R1
Instruction manual BFC
19
Download from Www.Somanuals.com. All Manuals Search And Download.
3
Installation
is
The appliance is supplied without accessories. Check the
3.4 Technical specifica-
tions
accessories you plan to use.
3.4.1 Dimensions of the appliance
Plan and elevation of the appliance
Hx
Legend
See the table.
3
Hy
30º
Ny
2
5
6
4
45º
18º
45º
D
G
2
3
5
A
N
H
K
S
6
1
7
4
P
W
M
R
IMD-0073 R5
20
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
is
Dimensions (all sizes in mm, unless otherwise stated)
Dimen Description
sion
BFC
28
BFC
30
BFC
50
BFC
60
A
Total height
1390
705
1910
705
1910
705
1910
705
D
G
H
Hx
Hy
K
Diameter of the appliance
Flue gas outlet diameter
Height of flue/air supply
80/125
1365
265
100/150
1905
265
100/150
1905
265
100/150
1905
265
x position of flue
y-position of flue
375
375
375
375
Height of gas connection
Height of cold water supply
Height of hot water outlet
y-position of hot water outlet
Height of cleaning opening
Height of drain valve connection
Height of T&P valve connection
Height of condensation drain
Cold water supply connection (ext.)
Hot water outlet (ext.)
1270
170
1800
160
1800
160
1800
160
M
N
Ny
P
1405
205
1940
205
1940
205
1940
205
170
175
175
175
R
S
85
75
75
75
900
1410
1410
1410
W
1
125
145
145
145
1
1
1
1
R1 /
R1 /
R1 /
R1 /
2
2
4
2
2
4
2
2
4
2
2
4
1
1
1
1
2
R1 /
R1 /
R1 /
R1 /
3
3
3
3
3
Gas valve connection (int.)
Drain valve connection (int.)
T&P valve connection (int.)
Inspection/cleaning opening
Condensation drainage connection (int.)
Rp /
Rp /
Rp /
Rp /
3
3
3
3
4
/ "
/ "
/ "
/ "
4
4
4
4
5
1-11.5 NPT
95x70
1-11.5 NPT
95x70
1-11.5 NPT
95x70
1-11.5 NPT
95x70
6
7
Ø40
Rp1
Rp1
Rp1
3.4.2 General and electrical specifications
General and electrical specifications
DESCRIPTION
Unit
litres
kg
BFC 28
217
177
8
BFC 30
368
214
8
BFC 50
368
214
8
BFC 60
368
214
8
Volume
Empty weight
Maximum operating pressure
Number of anodes
bar
-
4
4
4
4
Fan rotation speed at ignition
Operational speed of fan
Diameter of air restrictor
Heating time ∆T = 45°C
Electrical power consumption
rpm
rpm
mm
minutes
W
4500
5000
23.0
22
4500
5400
23.0
35
4500
6000
28.0
24
4500
6660
29.0
19
275
230
275
230
275
230
275
230
Supply voltage
volts
(-15% +10% VAC)
Mains frequency
IP class
Hz (± 1Hz)
-
50
30
50
30
50
30
50
30
Instruction manual BFC
21
Download from Www.Somanuals.com. All Manuals Search And Download.
3
Installation
is
3.4.3 Gas data
Gas data
Description II
Unit
BFC
28
BFC
30
BFC
50
BFC
60
2H3+
Gas category 2H: G20 - 20 mbar
Injector orifice diameter
mm
4.90
2
5.10
2
7.00
2
7.10
2
(1) = Blank plate
1 or 2
(2) = Burner pressure regulator
Nominal load (gross calorific value)
Nominal output
kW
32.1
30.5
20
34.5
32.7
20
52.6
48.8
20
63.2
59.6
20
kW
Supply pressure
mbar
mbar
Burner pressure
8.5
8.5
8.5
11.5
6.0
(*)
3
Gas consumption
m /h
3.1
3.3
5.0
General 3+
Injector orifice diameter
mm
2.50
1
2.60
1
3.40
1
3.80
1
(1) = Blank plate
1 or 2
(2) = Burner pressure regulator
Gas category: G30-30 mbar (butane)
Nominal load (gross calorific value)
Nominal output
kW
30.7
29.8
30
32.8
31.8
30
50.6
48.1
30
59.4
57.4
30
kW
Supply pressure
mbar
mbar
kg/h
(†)
Burner pressure
-
-
-
-
(*)
Gas consumption
2.2
2.4
3.7
4.3
Gas category: G31-37 mbar (propane)
Nominal load (gross calorific value)
Nominal output
kW
29.0
28.1
37
30.9
29.8
37
50.3
47.7
37
59.1
56.9
37
kW
Supply pressure
mbar
mbar
kg/h
(†)
Burner pressure
-
-
-
-
(*)
Gas consumption
2.1
2.2
3.6
4.2
(*) Based on 1013.25 mbar and 15 °C.
(†) If using a blank plate instead of a burner pressure regulator, it is assumed that the burner pressure is equal to
the supply pressure. In practice, however, the burner pressure will be lower.
22
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
is
3.5 Installation diagram
Installation diagram
Legend
UNVENTED
14
14
14
Only applicable numbers are
mentioned.
B
11
1. pressure reducing valve
(mandatory)
T
12
10
D
3. T&P valve (mandatory)
4. stop valve (recommended in
pipe C and mandatory in pipe A)
5. non-return valve (mandatory)
6. circulation pump (optional)
9. drain valve
3
4
6
5
4
10. manual gas valve (mandatory)
11. service stop valve
12. temperature gauge (optional)
13. condensation drainage
14. hot water draw-off points
15. expansion valve (mandatory)
16. expansion vessel (mandatory)
C
16
5
1
4
A
15
17. 3-way aeration valve
(recommended)
9
13
18. water tank
19. float valve
VENTED
A. cold water supply
B. hot water supply
C. circulation pipe
D. gas supply
H
19
A
E
17
4
14
18
11
B
E. overflow pipe
H. overflow pipe
C
12
T
D
10
4
3
4
5
6
4
C
9
13
IMD-0464 R0
Instruction manual BFC
23
Download from Www.Somanuals.com. All Manuals Search And Download.
3
Installation
Warning
is
3.6 Water connections,
Unvented
The installation should be carried out by an authorised installation engineer,
3.6.1 Cold water side
1. Fit an approved stop valve (4) on the cold water side as required by
2. The maximum working pressure of the appliance is 8 bar. Because the
pressure in the water pipe at times can exceed 8 bar, you must fit an
approved pressure-reducing valve (1).
3. Fit a non-return valve (5) and an expansion vessel (16).
4. Fit an expansion valve (15) and connect the overflow side to an open
wastewater pipe.
3.6.2 Hot water side
Note
Insulating long hot water pipes will prevent unnecessary energy loss.
1. Optional: fit a temperature gauge (12) so you can check the temperature of
the tap water.
2. Fit the T&P valve (3).
3. Fit a stop valve (11) in the hot water outlet pipe for servicing.
3.6.3 Circulation pipe
If an immediate flow of hot water is required at draw-off points, a circulation
pump can be installed. This improves comfort and reduces water wastage.
1. Fit a circulation pump (6) of the correct capacity for the length and resistance
of the circulation system.
2. Fit a non-return valve (5) behind the circulation pump to guarantee the
direction of circulation.
3. Fit two stop valves for service purposes (4).
4. Connect the circulation pipe to the cold water supply pipe.
3.6.4 Condensation drainage
1. Fit a sloping wastewater pipe to the siphon (13) for condensation drainage
and connect this to the wastewater discharge in the boiler room.
Attention
All fittings behind the siphon must be condensation-resistant.
24
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
is
3.7 Water connections,
Vented
Warning
The installation should be carried out by an authorised installation engineer,
3.7.1 Cold water side
1. Fit an approved stop valve (4) on the cold water side between the cold water
head tank (18) and the appliance, as required by
3.7.2 Hot water side
Note
Insulating long hot water pipes prevents unnecessary energy loss.
1. Fit the T&P valve (3).
2. Optional: fit a temperature gauge (12) so you can check the temperature of
the tap water.
3. Fit a stop valve (4) in the hot water outlet pipe, for use when servicing.
4. If a circulation pipe is required, continue further by installing the circulation
3.7.3 Circulation pipe
If an immediate flow of hot water is required at draw-off points, a circulation
pump can be installed. This improves comfort and reduces water wastage.
1. Fit a circulation pump (6) of the correct capacity for the length and resistance
of the circulation system.
2. Fit a non-return valve (5) behind the circulation pump to guarantee the
direction of circulation.
3. Fit two stop valves for service purposes (4).
4. Connect the circulation pipe to the cold water supply pipe.
3.7.4 Condensation drainage
1. Fit a sloping wastewater pipe to the siphon (13) for condensation drainage
and connect this to the wastewater discharge in the boiler room.
Attention
All fittings behind the siphon must be condensation-resistant.
Instruction manual BFC
25
Download from Www.Somanuals.com. All Manuals Search And Download.
3
Installation
Warning
is
3.8 Gas connection
The installation should be carried out by an authorised installation engineer,
Attention
Make sure that the diameter and length of the gas supply pipe are large
enough to supply sufficient capacity to the appliance.
1. Fit a manual gas valve (10) in the gas supply pipe.
2. Blow the gas pipe clean before use.
3. Close the manual gas valve.
4. Fit the gas supply pipe to the gas control.
Warning
After fitting, check for leaks.
3.9 Air supply and flue
3.9.1 Introduction
This section covers the following subjects:
•
•
•
3.9.2 Requirements for flue gas discharge materials
Warning
The installation should be carried out by an authorised installation engineer,
Depending on the approved installation types, there are several alternatives for
connecting the air supply and flue gas discharge.
The appliances are approved for installation types B23, C13, C33, C43, C53
and C63.
The figure and table give information about these appliance types. For an
explanation of the possibilities, please contact the manufacturer.
26
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
is
Types of appliances
C43
B23
C33
C13
C53
IMD-0468 R0
Instruction manual BFC
27
Download from Www.Somanuals.com. All Manuals Search And Download.
3
Installation
is
Explanation of type of appliance
Type of appliance
Description
B23
C13
C33
C43
Air for combustion is drawn from the boiler room.
Concentric and / or parallel wall flue terminal
Concentric and / or parallel roof flue terminal
Appliances on common air supply and flue gas discharge (concentric and / or
parallel) in multi-storey building.
C53
C63
Air supply and flue terminal types mixed.
Appliances supplied without flue components and / or terminal. These
appliances must be installed in compliance with local regulations.
Note
Make sure that the chimney discharges into an area where this is permitted
for this category of appliance.
3.9.3 Concentric connections
The table shows the requirements for concentric systems.
Warning
Install flue gas discharge pipe runs with a run-off of 5 mm per metre.
Flue gas discharge requirements for concentric systems (C13, C33)
Appliance
Diameter
Maximum length Maximum
number of 90º
bends
BFC 28
BFC 30
BFC 50
BFC 60
80/125 mm
100/150 mm
100/150 mm
100/150 mm
40 m
40 m
40 m
15 m
7
7
7
4
Attention
Both conditions stated in the table must be fulfilled.
Even if there are less bends than the stated maximum, the maximum pipe
length may not be exceeded.
Even if the total pipe length is less than the stated maximum, the maximum
number of bends may not be exceeded.
The following example illustrates how to use the table.
Practical example of concentric flue gas discharge
Example
The figure shows a BFC 30 installation. The appliance must be fitted with 25 m
of concentric pipe (C13/C33) and four 90 degree bends. We need to check
whether this configuration complies with the requirements stated in the table.
28
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
is
Appliance with concentric flue gas discharge material
IMD-0284 R1
According to the table, the maximum length allowed is 40 metres, and there may
be up to seven 90 degree bends. Both requirements are fulfilled.
Specifications
Attention
For type C13 and C33 installations,A.O. Smith prescribes the use of a roof
or wall-mounted terminal, exclusively of a type approved for the appliance. Use
of an incorrect roof or wall-mounted flue terminal can cause the installation to
malfunction.
Instruction manual BFC
29
Download from Www.Somanuals.com. All Manuals Search And Download.
3
Installation
is
Concentric wall flue terminal specifications C13
Specification
Wall flue terminal set:
Description
1
Art. No.
BFC 28
BFC 30-50-60
0302 515
0302 504
1
•
1X Wall flue terminal (incl. wall flange
& clamping ring)
Construction
Manufacturer
Model
Concentric
•
•
1X Pipe 500mm
1X Bend 90°
Muelink & Grol
M2000 MDV SEC
Concentric
Pipe material
Construction
Flue
Thick-walled aluminium with lip ring seal
Thin-walled galvanised sheet steel
Air supply
Flue
Pipe diameters
BFC 28
Ø 80 mm
BFC 30-50-60
Ø 100 mm
Air supply
BFC 28
BFC 30-50-60
Ø 125 mm
Ø 150 mm
(1) No other wall flue terminal is permitted. Use this item number to order the wall conduit set from supplier,
manufacturer or wholesaler.
Concentric roof flue terminal specifications C33
Specification
Description
1
1
Roof flue terminal set:
Art. No.
BFC 28
BFC 30-50-60
0305 042
0304 423
•
1X Wall flue terminal (incl. clamping
ring)
Construction
Manufacturer
Model
Concentric
•
•
1X Pipe 1000mm
Muelink & Grol
M2000 DDV HR-C
Concentric
1 X Mounting flange
Pipe material
Construction
Flue
Thick-walled aluminium with lip ring seal
Thin-walled galvanised sheet steel
Air supply
Flue
Pipe diameters
BFC 28
Ø 80 mm
BFC 30-50-60
Ø 100 mm
Air supply
BFC 28
BFC 30-50-60
Ø 125mm
Ø 150 mm
(1) No other wall flue terminal is permitted. Use this item number to order the wall conduit set from supplier,
manufacturer or wholesaler.
30
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
is
3.9.4 Parallel connections
The table states the maximum pipe lengths for parallel systems. The maximum
pipe length depends on the chosen diameter.
Warning
Install flue component pipe runs with a run-off of 5 mm per metre.
Flue gas outlet requirements for parallel systems
1
Appliance
Diameter
Maximum
L
L
equivalent
equivalent
total length
90º bend
3.9m
4.6m
4.6m
4.6m
4.6m
2.4m
2.4m
2.4m
45º bend
1.1m
1.2m
1.2m
1.2m
1.2m
1.4m
1.4m
1.4m
BFC 28
BFC 30
BFC 50
BFC 60
BFC 28
BFC 30
BFC 50
BFC 60
80mm
25m
100mm
100mm
100mm
100mm
130mm
130mm
130mm
80m
45m
25m
100m
100m
100m
100m
1) Parallel systems with diameter of 130mm or 150mm. If the maximum total
length for a diameter of 130mm is insufficient, 150mm diameter must be used.
Any diameter enlargement must be carried out on both air supply and flue gas
outlet.
You must use the longest pipe when calculating the pipe length. For example, if
the chimney pipe is 35 metres and the air supply pipe is 32 metres, use 35
metres as the length for the calculation. Next, add the L
for every 90°
equivalent
and 45° bend to this 35 metres, in both the air supply and flue gas outlet. The
following practical example illustrates how to use the table.
Practical example of parallel flue gas outlet
Example
The diagram shows a BFC 30. This has to be fitted with a 25m parallel pipe
100mm in diameter, plus eight 90-degree bends. The configuration must be
checked for compliance with the requirements stated in the table.
Instruction manual BFC
31
Download from Www.Somanuals.com. All Manuals Search And Download.
3
Installation
is
Appliance with parallel flue gas discharge material
3
2
4
5
1
IMD-0283 R1
The longest pipe must be used to check the maximum length. In this case, the
chimney pipe is the longest. This is 25 metres. This 25 metres is the sum of pipe
sections 1, 2, 3, 4 and 5. The length of the transition piece can be ignored. The
total number of bends used in the flue gas outlet and air supply is 8. The bend
in the transition piece can be ignored. According to the table, 4.6 metres must
be added for each bend. This brings the total pipe length to:
(4.6 x 8) + 25 = 36.8 + 25 = 61.8m.
This is less than the maximum length of 80 metres stated in the table. The
installation therefore fulfils the requirements.
Warning
3.10 Electrical
connection
The installation should be carried out by an authorised installation engineer,
3.10.1 Introduction
Topics covered in this paragraph, in sequence:
•
•
32
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
is
Optionally, it is possible to connect an isolating transformer, a continuous pump,
a program-controlled pump, an extra ON mode switch and an extra alarm signal
to the appliance. For these options, see:
•
•
•
•
Note
The optional components are not included in the rating for electrical power
3.10.2 Preparation
Attention
The appliance is phase-sensitive. It is absolutely essential to connect the
mains phase (L) to the phase of the appliance, and the mains neutral (N) to the
neutral of the appliance.
Attention
There may be no potential difference between neutral (N) and earth ( ).
If this is the case, then an isolating transformer must be applied in the supply
For more information or to order this isolating transformer, please contact A.O.
Smith water Products Company.
The figure shows a view of the electrical connector block, and the table shows
the appropriate connections.
Connector block
Legend
A
A. screws
B. protective cap
C. connector block
B
A
1
C
24
IMD-0077 R2
Instruction manual BFC
33
Download from Www.Somanuals.com. All Manuals Search And Download.
3
Installation
is
In preparation, you must first remove the two plastic covers and the protective
cap of the electrical section.
1. Undo the screws of the plastic covers.
2. Carefully remove the covers from the appliance.
The electrical section is now visible.
3. Loosen the 2 screws (A) of the electrical section, and remove the protective
cap (B) from the electrical section.
The connector block (C) is now visible.
Note
Consult the table for the connections and consult the electrical diagram for
the electrical component connections.
Electrical connector block
Program-
controlled
pump
Tank
ON
Continuous
pump
Mains
voltage
Unus
ed
Alarm Off
Isolating transformer
primary
secondary
X1 X2
L
8
N
9
N
L
X1 X2
N
L
N
L
N
L
1-4
5
6
7
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
3.10.3 Connecting the mains voltage
The appliance is supplied without a power cable and isolator.
Note
In order to receive electrical power, the appliance has to be connected to the
mains power by means of a permanent electrical connection. A double-pole
isolator with a contact gap of at least 3 mm must be fitted between this
permanent connection and the appliance. The power cable must have cores of
2
at least 3 x 1.0 mm .
Warning
Leave the appliance isolated until you are ready to start it up.
1. Connect phase (L), neutral (N) and earth ( ) of the power cable to terminals
22 through 24 of the connection block as indicated in the
2. Fit the power cable in the strain relief.
3. Connect the power cable to the isolator.
4. If you have no more connections to make:
-
-
Fit the cap on the electrical terminal block.
Fit the plastic covers onto the appliance.
3.10.4 Isolating transformer
An isolating transformer should be used if there is a case of 'floating neutral'.
1. Refer to fitting instructions provided with the isolating transformer. (Contact
the supplier for details of the correct isolating transformer.)
2. Connect phase (L), neutral (N) and earth ( ) to terminals 16 through 21 of
3. Fit the cables in the strain relief.
34
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
is
4. If you have no more connections to make:
-
-
Fit the cap on the electrical terminal block.
Fit the plastic covers onto the appliance.
5. Connect the power cable to the isolator.
3.10.5 Connecting continuous pump
1. Connect phase (L), neutral (N) and earth ( ) to terminals 7, 8 and 9 as
2. Fit the cable in the strain relief.
3. If you have no more connections to make:
-
-
Fit the cap on the electrical terminal block.
Fit the plastic covers onto the appliance.
3.10.6 Connecting a program-controlled pump
1. Connect phase (L), neutral (N) and earth ( ) to terminals 10, 11 and 12 as
2. Fit the cable in the strain relief.
3. If you have no more connections to make:
-
-
Fit the cap on the electrical terminal block.
Fit the plastic covers onto the appliance.
3.10.7 Connecting an extra ON mode switch ("Tank ON")
Tank ON is a facility for connecting an external ON/OFF switch. In the OFF
position, the programmed operating state is active. In the ON position, the
programmed operating mode is overruled, and the "ON mode" is active.
1. Connect cables (X and X ) to terminals 5 and 6 as indicated in the
1
2
2. Fit the cable in the strain relief.
3. If you have no more connections to make:
-
-
Fit the cap on the electrical terminal block.
Fit the plastic covers onto the appliance.
3.10.8 Connecting an extra error signal ('Alarm OUT' )
Alarm OUT is a potential free terminal that is switched when an error is
detected. This can be used to signal errors, for example with a lamp. A 230 V
circuit can be directly powered. Other voltages require a relay prescribed by
the manufacturer.
1. Connect the phase cables (X and X ) to terminals 13 and 14 according to
1
2
2. Fit the cable in the strain relief.
3. If you have no more connections to make:
-
-
Fit the cap on the electrical terminal block.
Fit the plastic covers onto the appliance.
Instruction manual BFC
35
Download from Www.Somanuals.com. All Manuals Search And Download.
3
Installation
Note
is
3.11 Checking the supply
pressure and burner
pressure
Before starting the appliance and/or checking the supply pressure and
Attention
Before starting up for the first time or after conversion, you must always
check the supply pressure and burner pressure.
Note
The easiest way to check the gas pressures is by using two pressure
gauges. This procedure assumes that these two gauges are available.
Gas control
Legend
Only applicable numbers are
mentioned.
1. supply pressure test nipple
2. burner pressure test nipple
3. burner pressure regulator
4. burner pressure control cap
1
5. burner pressure control
adjusting screw
2
4
3
IMD-0079a R2
5
3.11.1 Preparation
To check the supply pressure and burner pressure, proceed as follows:
power supply.
2. Undo the screws of the plastic covers.
3. Carefully remove the covers from the top of the appliance. The electrical
section is now visible.
36
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
is
3.11.2 Procedure to check pressures
1. There are two test nipples on the gas control:
-
-
a supply pressure nipple (1)
a burner pressure nipple (2)
Sealing screws are located inside the test nipples. Loosen both sealing
screws by a few turns. Do not completely loosen them; they can be difficult
to re-tighten.
2. Connect a pressure gauge to the burner pressure nipple (2).
3. Open the gas supply and vent the gas supply line with the supply pressure
nipple (1).
4. Connect a pressure gauge to the supply pressure nipple (1) when gas starts
to flow from this nipple.
5. Switch on the power to the appliance using the isolator on the appliance.
6. Switch the electronic controller ON by setting the 0/I switch to position I.
n
min
0063
IMD-0423 R0
The display will now show INTERNAL CHECKfor about 10 seconds and
go to the main menu.
INTERNAL CHECK
MENU
»OFF
^ ON
È WEEK PROGRAM
7. Activate the "ON mode" by going through the following steps:
-
Press the blue arrow once ( ) to position the cursor in front of ONand
press . The display shown here will appear.
»START OPERATION
^ CHANGE SETPOINT
È
Tset=65ÉC
-
Confirm the
by pressing START OPERATION.
The appliance is now in the "ON mode" and will ignite.
8. Once the display shows the text RUNNINGyou must wait about 1 minute
before reading the dynamic pressures (the fan needs this time to run up to
full rotational speed).
Instruction manual BFC
37
Download from Www.Somanuals.com. All Manuals Search And Download.
3
Installation
is
9. Use the pressure gauge to read the supply pressure at 1nipple
Note
Consult the mains gas supply company if the supply pressure is not correct.
10. Use the pressure gauge to read the burner pressure at nipple
If the burner pressure is not correct and the appliance is fitted with a blank plate,
this case, consult your installation engineer or supplier.
If the appliance is indeed fitted with a burner pressure regulator, the pressure can
3.11.3 Adjusting the pressure
1. Remove the cap (4) from the burner pressure regulator (3).
2. Correct the burner pressure by turning the adjusting screw (5), depending
on the correction required:
-
-
Adjustment screw anticlockwise: burner pressure decreases.
Adjustment screw clockwise: burner pressure increases.
3. Cover the opening of the adjusting screw and check the burner pressure
4. If the pressure is not set correctly, repeat the preceding steps until the
correct pressure is attained.
5. Fit the cap (4) back on the burner pressure regulator.
6. Activate the "OFF mode" of the electronic controller:
MENU
»OFF
^ ON
È WEEK PROGRAM
7. If the MENUis not displayed:
press
.
-
-
Use and to place the cursor beside OFF
.
Confirm with
.
8. Wait until the fan has stopped, and switch the electronic controller off.
Attention
Failure to wait until the fan stops can cause damage to the appliance.
3.11.4 Finalising
1. Shut off the gas supply.
2. Disconnect the two pressure gauges and retighten the sealing screws in the
test nipples.
3. Replace the cover.
Note
Before starting-up the appliance, take time to fill in the warranty card
supplied with the appliance. This enables us to guarantee the quality of our
systems, and to further enhance our warranty procedure.
Please return this card as soon as possible. Your customer will then receive a
warranty certificate with our warranty conditions.
38
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
is
4 Conversion to a
different gas category
Attention
The conversion may only by carried out by an authorised installation
engineer.
If the appliance must operate on a family of gases (LP gas or natural gas) or
other gas category than that for which the appliance has been set at the
factory, the appliance will have be adapted using a special conversion kit.
Attention
You must check the supply pressure and burner pressure once the
conversion is complete.
Orifice assembly
Legend
1. connector
2. gas coupling
3. air supply hose
4. pressure switch hose
5. gas/air distribution plate
6. stamped figures
Instruction manual BFC
39
Download from Www.Somanuals.com. All Manuals Search And Download.
4
Conversion to a different gas category
is
2. Shut off the gas supply.
3. Undo the screws of the plastic covers.
4. Carefully remove the covers from the top of the appliance.
5. Detach the connector (1) that connects the leads of the hot surface igniter
and the flame probe to the controller.
6. Detach the three-part gas coupling (2) adjacent to the burner.
-
-
Detach the air supply hose (3).
Detach the pressure switch hose (4).
7. Remove the burner as complete assembly.
8. Place and fit the burner with parts from the conversion kit.
Note
The burner for LP gases can be recognised by the letter 'P' which is stamped
into the metal of the gas/air distribution plate (5).
9. Select and fit the correct orifice from the conversion kit, based on the gas
(6).
Conversion of gas control
Legend
7. burner pressure regulator
8. blank plate
9. gas control connector
8
9
7
IMD-0079b R2
40
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
is
10. Check whether there is a burner pressure regulator (7) attached to the top
of the gas control, or simply a blank plate (8).
Note
In the event of the supply pressure for a gas category being the same as the
blanking plate with a cork gasket. A burner pressure that deviates with respect
to the supply pressure requires a burner pressure regulator with rubber gasket
to be used. Each conversion kit contains all the necessary components.
11. If the blank plate or burner pressure regulator need to be replaced:
-
-
-
Unscrew the connector (9) from the gas control.
If necessary, remove the blank plate or burner pressure regulator (7).
If necessary, fit the blank plate or burner pressure regulator supplied
with the conversion kit.
-
Fit the gas control's connector (9).
12. Fit the connector (1) of the hot surface igniter and flame probe to the
controller.
13. Fit the 3-part gas coupling (2).
14. Check the burner pressure and supply pressure (3.11 "Checking the supply
15. Replace the cover.
16. Remove the sticker showing the new gas category from the conversion kit,
and attach it below the appliance's rating plate. This clearly indicates that the
appliance may no longer be run on the gas for which it was originally
supplied.
Instruction manual BFC
41
Download from Www.Somanuals.com. All Manuals Search And Download.
4
Conversion to a different gas category
is
42
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
gis
5 Filling
Installation diagram
Legend
UNVENTED
14
14
14
Only applicable numbers are
mentioned.
B
11
1. pressure reducing valve
(mandatory)
T
12
10
D
3. T&P valve (mandatory)
4. stop valve (recommended in
pipe C and mandatory in pipe A)
5. non-return valve (mandatory)
6. circulation pump (optional)
9. drain valve
3
4
6
5
4
10. manual gas valve (mandatory)
11. service stop valve
12. temperature gauge (optional)
13. condensation drainage
14. hot water draw-off points
15. expansion valve (mandatory)
16. expansion vessel (mandatory)
C
16
5
1
4
A
15
17. 3-way aeration valve
(recommended)
9
13
18. water tank
19. float valve
VENTED
A. cold water supply
B. hot water supply
C. circulation pipe
D. gas supply
H
19
A
E
17
4
14
18
11
B
E. overflow pipe
H. overflow pipe
C
12
T
D
10
4
3
4
5
6
4
C
9
13
IMD-0464 R0
Instruction manual BFC
43
Download from Www.Somanuals.com. All Manuals Search And Download.
5
Filling
gis
5.1 Filling the appliance
5.1.1 Filling unvented installations
To fill the appliance, proceed as follows:
1. Open the stop valve (11) in the hot water pipe and, if present, the stop valves
(4) for the circulation pump (6).
2. Close the drain valve (9).
3. Open the nearest hot water draw-off point (14).
4. Open the stop valve (4) on the cold water side (A) so that cold water flows
into the appliance.
5. Completely fill the appliance. When a full water jet flows from the nearest
draw-off point, the appliance is full.
6. Bleed the entire installation of air, for example by opening all draw-off points.
7. The appliance is now under water supply pressure. There should be no
water coming out of the expansion valve (15), nor the T&P valve (3). If this
does happen, the cause might be:
-
The water supply pressure is greater than the specified 8 bar.
Rectify this by fitting a pressure reducing valve (1).
-
The expansion valve in the protected cold supply setup is defective or
incorrectly fitted.
5.1.2 Filling vented installations
To fill the appliance, proceed as follows:
1. Open the stop valve (11) in the hot water pipe and, if present, the stop valves
(4) for the circulation pump (6).
2. Close the drain valve (9).
3. Open the nearest hot water draw-off point (14).
4. Open the stop valve (4) on the cold water side (A) so that cold water flows
into the appliance.
5. Completely fill the appliance. When a full water jet flows from the nearest
draw-off point, the appliance is full.
6. Bleed the entire installation of air, for example by opening all draw-off points.
7. The appliance is now under water supply pressure. There should be no
water coming out of the T&P valve (3). If this does happen, the T&P valve
might be defective or incorrectly fitted.
44
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
gis
6 Draining
Installation diagram
Legend
UNVENTED
14
14
14
Only applicable numbers are
mentioned.
B
11
1. pressure reducing valve
(mandatory)
T
12
10
D
3. T&P valve (mandatory)
4. stop valve (recommended in
pipe C and mandatory in pipe A)
5. non-return valve (mandatory)
6. circulation pump (optional)
9. drain valve
3
4
6
5
4
10. manual gas valve (mandatory)
11. service stop valve
12. temperature gauge (optional)
13. condensation drainage
14. hot water draw-off points
15. expansion valve (mandatory)
16. expansion vessel (mandatory)
C
16
5
1
4
A
15
17. 3-way aeration valve
(recommended)
9
13
18. water tank
19. float valve
VENTED
A. cold water supply
B. hot water supply
C. circulation pipe
D. gas supply
H
19
A
E
17
4
14
18
11
B
E. overflow pipe
H. overflow pipe
C
12
T
D
10
4
3
4
5
6
4
C
9
13
IMD-0464 R0
Instruction manual BFC
45
Download from Www.Somanuals.com. All Manuals Search And Download.
6
Draining
gis
6.1 Draining unvented
installations
1. Activate the MENUwith
.
MENU
»OFF
^ ON
È WEEK PROGRAM
2. Position the cursor in front of OFF
3. Confirm OFFwith
.
.
4. Wait until the fan has stopped. The symbol is then dimmed.
Attention
Failure to wait until the fan stops purging can cause damage to the
appliance.
5. Switch the appliance OFF (position 0) using the ON/OFF switch on the
control panel.
n
min
0063
IMD-0423 R0
6. Isolate the water heater from the power supply by putting the isolator
between the appliance and the mains power supply to position 0.
7. Shut off the gas supply (10).
8. Close the stop valve (11) in the hot water pipe.
9. Close the supply valve (4) in the cold water supply (A).
10. Open the drain valve (9).
11. Bleed the appliance (or installation) so that it drains completely.
6.2 Draining vented
installations
1. Activate the MENUwith
2. Position the cursor in front of OFF
3. Confirm OFFwith
.
.
.
4. Wait until the fan has stopped. The symbol is then dimmed.
Attention
Failure to wait until the fan stops purging can cause damage to the
appliance.
5. Switch the appliance OFF (position 0) using the ON/OFF switch on the
control panel.
46
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
gis
n
min
0063
IMD-0423 R0
6. Isolate the water heater from the power supply by putting the isolator
between the appliance and the mains power supply to position 0.
7. Shut off the gas supply (10).
8. Close the stop valve (11) in the hot water pipe.
9. Close the stop valve (4) between the water tank and the cold water inlet (A).
10. Open the drain valve (9).
11. Bleed the appliance (or installation) so that it drains completely.
Instruction manual BFC
47
Download from Www.Somanuals.com. All Manuals Search And Download.
6
Draining
gis
48
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
gis
7 The control panel
7.1 Introduction
Topics covered in this chapter:
a
•
•
•
•
•
»START OPERATION
^ CHANGE SETPOINT
È
Tset=70ÉC
7.3 Meaning of icons
The table explains the meanings of the icons.
7.2 Controls
The figure shows the electronic controller.
Icons and their meaning
Name
Meaning
n
min
Heat demand
Purge
Heat demand detected
Pre- and post-purge using
fan
0063
Pressure switch Pressure switch is closed
Glowing
(Pre)glow
Gas control
Gas control open/ignition
Flame detection Appliance operational
IMD-0423 R0
The control panel is completely menu-driven, and
comprises:
7.4 Electronic controller ON/OFF switch
The ON/OFF switch of the electronic controller is used
to switch the appliance ON and OFF. Note that in the
OFF position the appliance remains electrically live, in
order for the continuous pump to stay running.
•
•
a 4-line display with 20 characters per line;
6 pushbuttons for operating the appliance (below
the display);
•
•
•
6 graphical symbols (above the display);
a connector for a service PC;
an ON/OFF switch.
INTERNAL CHECK
The pushbuttons are divided into three groups:
•
Navigation buttons:
After switching on, the text INTERNAL CHECK
appears on the display for about 10 seconds. Themain
is made in the main menu, the appliance automatically
-
-
-
Buttons for UP , and DOWN
;
Enter:
;
Reset button:
•
•
;
.
Note
This chapter is specifically intended for the service
and maintenance engineer and installation
engineer.
To electrically isolate the appliance, you must use
the isolator between the appliance and the mains
power supply.
In this manual, the display of the electronic controller
is shown as in the figure, both with and without icons.
7.5 Navigation buttons
The use of these buttons is explained with the help of
the figure that shows the main menu (11 "Main
The navigation buttons are:
Instruction manual BFC
49
Download from Www.Somanuals.com. All Manuals Search And Download.
7
The control panel
gis
•
•
•
Buttons for UP , and DOWN
;
Enter:
;
Reset button:
.
The
^
arrows and
È
indicate that you can scroll up
and/or down. Use the buttons and to scroll.
MENU
OFF
^»ON
È WEEK PROGRAM
EXTRA PERIOD
SETTINGS
The cursor
»points to the option to be activated. In the
display as shown in the figure, you can scroll through
the main menu.
The main menu comprises: OFF
WEEK PROGRAM EXTRA PERIODand
SETTINGS. You have to scroll down further to see the
,
ON,
,
options EXTRA PERIODand SETTINGS
.
The selected option is confirmed using
.
Pressing the
button takes you back one page
in a menu and discards all options selected in the
current menu.
Note
The
button is also used to reset the
appliance following an error.
7.6 PC connection
The PC connection is solely intended to enable
technicians from A.O. Smith to display the status and
history of the appliance. These details can be
important for troubleshooting and/or responding to
complaints.
50
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
gis
8 Status of the
appliance
•
line four: blank when the appliance is idle, or
depending on the heating cycle (9.3 "The
appliance's heating cycle"), displays a text such as
8.1 Introduction
Topics covered in this chapter:
•
•
•
HEAT DEMAND
.
ON
13:45 Thursday 67ÉC
Tset 75ÉC
8.2 Operating modes
When running, the appliance has four basic operating
modes, namely:
8.2.3
EXTRA
•
•
•
•
OFF
In this mode, one extra period is programmed and
activated. In this mode, the OFForPROGmode is
temporarily overruled to fulfil a single period of
demand. Once the period has passed, the appliance
automatically returns to the previous operating mode.
The figure shows the display with the following
information:
ON
EXTRA
PROG
8.2.1
OFF
In this mode, the frost protection is activated. The
figure shows the display with the following information:
•
•
line one: the text EXTRA
line two: the time, the day and alternately (9.3 "The
;
•
•
line one: the text OFF
;
;
net
1
line two: the time, the day and alternately (9.3 "The
•
•
line three: the switch-on time, and the related
water temperature setting;
.
net
1
•
lines three and four: the text
FROST PROTECTION ACTIVATED
line four: the text PERIOD ACTIVATED
.
.
EXTRA
OFF
12:30 Thursday 76ÉC
TH 12:45 Tset 75ÉC
PERIOD ACTIVATED
13:45 Thursday 6ÉC
FROST PROTECTION
ACTIVATED
8.2.2
ON
In this mode, the appliance continually responds to the
hot water demand. The figure shows the display with
the following information:
•
•
line one: the text ON
line two: the time, the day and alternately (9.3 "The
;
.
net
1
•
line three: the programmed water temperature
T
;
set
Instruction manual BFC
51
Download from Www.Somanuals.com. All Manuals Search And Download.
8
Status of the appliance
gis
8.2.4
PROG
8.3 Error conditions
In this mode a preset week program is active, and the
appliance responds continually to demand within the
time periods set in the week program. There are two
distinct situations possible in this mode:
The figure shows an example of an error condition. If
the appliance enters this condition, the display will
show the following information:
•
line one: error code comprising a letter and two
digits, followed by the error description;
PROG
•
lines two to four: alternately, a brief explanation of
the error, and a brief action to resolve the error.
10:00 Monday
76ÉC
MO 11:15 Tset 75ÉC
S04: SENSOR ERROR
1. The current time falls within a set time period
CHECK
SENSOR OR DUMMY
of the week program.
The figure shows the display with the following
information:
-
-
line one: the text PROG
;
Attention
line two: the time, the day and T and T
alternately (9.3 "The appliance's heating
1
net
The displayed action to resolve the error may only
be performed by a service and maintenance engineer.
-
-
line three: the next scheduled switch-off time
There are various types of errors:
and the water temperature T of the active
set
•
•
LOCK OUT ERRORS
period;
When the cause has been removed, these errors
require a reset with the button
appliance can resume operation.
line four: is empty, or depending on the
heating cycle (9.3 "The appliance's heating
before the
.
BLOCKING ERRORS
PROG
12:00 Monday
MO 11:15
These errors disappear automatically once the
cause of the error has been removed, after which
the appliance resumes operation by itself.
76ÉC
PERIOD ACTIVATED
The display does not show what type of error has been
detected. A comprehensive overview of the errors is
provided elsewhere in the
2. The current time falls outside a set time period
of the week program.
The figure shows the display with the following
information:
If, as end-user, you find the appliance in an error
condition, you may attempt to restart the appliance by
-
-
line one: the text PROG
;
pressing the
button
line two: the time, the day and T and T
alternately (9.3 "The appliance's heating
1
net
However, if the error returns or occurs several times in
a short time you must contact your service and
maintenance engineer.
-
-
line three: the next scheduled switch-on
time;
line four: displays the text
PERIOD ACTIVATED
.
In all modes, the temperature may at any moment
drop below the desired temperature. The appliance
then enters a heating cycle. This heating cycle is
basic operating modes.
Note
Setting and if necessary programming of the basic
operating modes are described in the main
52
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
gis
8.4 Service condition
The figure shows the message
!!! WARNING !!!
MAX. BURNING HOURS:
SERVICE REQUIRED
SERVICE REQUIRED.Should this message appear,
then the appliance is in need of a service and
maintenance inspection. In that case, contact your
service and maintenance engineer.
Note
The message SERVICE REQUIREDis based on
the number of expired burning hours and the preset
service interval. Should the service interval have been
incorrectly selected, contact the service and
maintenance engineer for instructions on how to
adjust this. Information on the maintenance frequency
is provided elsewhere in the
Instruction manual BFC
53
Download from Www.Somanuals.com. All Manuals Search And Download.
8
Status of the appliance
gis
54
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
gis
9 Starting and running
9.1 Introduction
Topics covered in this chapter, in sequence:
a
•
•
»START OPERATION
^ CHANGE SETPOINT
9.2 Starting and running
Start the appliance as follows:
È
Tset=65ÉC
6. Confirm the START OPERATIONby pressing
.
valve.
The appliance is now in "ON mode". If there is a
heat demand, the appliance will run through the
heating cycle (9.3 "The appliance's heating
3. Switch on the power to the appliance using the
isolator between the appliance and the power
supply.
If the heating cycle is not run, there is no heat
demand; if this is the case, Tset will probably need
4. Switch the electronic controller ON by setting the
ON/OFF switch to position I.
9.3 The appliance's heating cycle
The appliance's heating cycle is activated as soon as
n
min
the measured water temperature (T ) falls below the
net
threshold value (T ). This threshold value depends
set
on the currently selected appliance operating mode.
For example, if the appliance is in "OFF mode" (frost
protection), then this value is 5°C. If the appliance is in
"ON mode", then this threshold value is selectable, for
example, 65°C.
0063
The heating cycle runs in turn through the following
states:
IMD-0423 R0
The display will now show INTERNAL CHECKfor
about 10 seconds and go to the main menu.
1. HEAT DEMAND;
2. PRE-PURGE;
3. PRESSURE SWITCH;
4. PRE-GLOW;
a
5. IGNITION;
INTERNAL CHECK
6. RUNNING;
7. POST-PURGE.
The complete cycle is explained in the following
example, which assumes the appliance is in the basic
mode ON
.
a
MENU
»OFF
^ ON
È WEEK PROGRAM
Note
The same heating cycle applies to the other
operating modes.
5. Press the blue arrow once ( ) to position the
cursor in front of ONand press
. The
display shown in the figure will appear.
Instruction manual BFC
55
Download from Www.Somanuals.com. All Manuals Search And Download.
9
Starting and running
gis
Once the appliance starts, it will run through the
following steps:
5. After a number of seconds pre-glow, the gas
control is opened and ignition takes place.
1. The water temperature drops below the set
temperature of (for example) 65°C. The electronic
controller detects a demand and starts the heating
cycle.
-
-
The icon is activated.
The message IGNITIONappears.
a
-
-
The icon is activated.
ON
Ê
Ê Ê
13:45 Thursday 63ÉC
Tset 65ÉC
The message HEAT DEMANDappears.
a
IGNITION
ON
Ê
6. After ignition, the flame is detected and the
appliance will be running. This means that actual
heating has started. The fan speed then increases
to the normal working speed, and the pressure
switch closes:
13:45 Thursday 63ÉC
Tset 65ÉC
HEAT DEMAND
2. Once demand is registered, the fan is started to
exhaust any gases that may be present. This
phase is called pre-purge and lasts about 15
seconds.
-
-
-
The icon is dimmed.
The icons and are activated.
The message RUNNINGappears.
-
-
The icon is activated.
a
The message PRE PURGEappears.
ON
Ê Ê Ê Ê
a
13:45 Thursday 63ÉC
Tset 65ÉC
ON
Ê Ê
RUNNING
13:45 Thursday 63ÉC
Tset 65ÉC
7. When the water is up to temperature, the heat
demand drops off and the post-purge starts. This
lasts about 25 seconds.
PRE PURGE
3. During the pre-purge, the pressure switch closes.
-
-
-
The icons
,
and are dimmed.
-
-
The icon is activated.
The icon is activated.
The message PRESSURE SWITCH
appears.
The message POST PURGEappears.
a
a
ON
Ê Ê Ê
ON
Ê Ê
13:45 Thursday 63ÉC
Tset 65ÉC
PRESSURE SWITCH
13:45 Thursday 65ÉC
Tset 65ÉC
POST PURGE
4. After some time, the pre-purge ceases and the
electronic controller reduces the fan speed to the
ignition speed. This is followed by the (pre-)glow of
the hot surface igniter.
8. Following the post-purge, the fan stops and the
pressure switch opens:
-
-
The icons and are dimmed.
The message POST PURGEvanishes.
-
-
The icons and are dimmed
The icon is activated.
a
ON
a
14:05 Thursday 65ÉC
ON
Ê
Ê
13:45 Thursday 63ÉC
Tset 65ÉC
With any subsequent heat demand, the heating cycle
will resume from step 1.
GLOW PLUG
56
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
gis
10 Shutting down
4. Wait until the fan has stopped. The symbol is
then dimmed.
10.1 Introduction
This chapter describes:
5. Switch the appliance OFF (position 0) using the
•
ON/OFF switch on the control panel.
•
•
n
min
10.2 Shut the appliance down for a brief
period ("OFF mode")
0063
To shut the appliance down for a brief period, you must
activate the frost protection.
You can use the frost protection to prevent water
freezing in the appliance.
Activate the frost protection as follows:
IMD-0423 R0
6. Isolate the appliance from the power supply by
setting the isolator between the appliance and the
mains power supply to position 0.
1. Press the
2. Use and to position the cursor in front of OFF
Confirm with
button to select the main menu.
.
.
10.4 Shutting the appliance down for a long
period
OFF
Drain the appliance if you are shutting it down for a
long period. Proceed as follows:
13:45 Thursday 6ÉC
FROST PROTECTION
ACTIVATED
1. Isolate the appliance from the power
The frost protection cuts in if the water temperature
drops below 5°C. The text FROSTwill then appear on
2. Shut off the gas supply.
line one of the display. The appliance heats the water
3. Close the stop valve in the hot water pipe.
to 20°C (T ) and drops back to the OFFmode.
set
4. Close the supply valve of the protected cold supply
set-up.
Note
5. Open the drain valve
These values of 5°C and 20°C cannot be adjusted.
6. Bleed the appliance (or installation) so that it
drains completely.
10.3 Electrically isolating the appliance
The appliance should only be isolated from mains
power in the correct way. The correct procedure is as
follows:
1. Activate the MENUwith
.
2. Position the cursor in front of OFF
.
3. Confirm OFFwith
.
MENU
»OFF
^ ON
È WEEK PROGRAM
Attention
Failure to wait until the fan stops purging can
cause damage to the appliance.
Instruction manual BFC
57
Download from Www.Somanuals.com. All Manuals Search And Download.
10
Shutting down
gis
58
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
gis
11 Main menu
For example, LANGUAGEis a submenu of
SETTINGS. So, for example, to select the
LANGUAGEmenu, this manual uses the following
notational convention:
11.1 Introduction
The MENUis reached by pressing the
electronic controller.
button on the
MENU
»OFF
^ ON
È WEEK PROGRAM
•
:
SETTINGS
Confirm with
This means:
1. : Activate the main menu with
2. SETTINGS: Use the and/or buttons to go to
SETTINGSand confirm with
|
LANGUAGE
.
.
EXTRA PERIOD
SETTINGS
.
The main menu comprises:
3. LANGUAGE: Use the and/or buttons to go to
•
OFF
LANGUAGE
Select this option if you wish to turn
4. Confirm with
. After entering
, you
period, but do not wish to drain it. In this mode, the
frost protection is active. This prevents water from
freezing in the appliance.
will have activated the LANGUAGEsubmenu.
11.3 Switching on the "ON mode"
You can switch the appliance to the ONmode from any
operational mode, as follows:
•
•
ON
In this mode, the appliance continually responds to
the hot water demand. (11.3 "Switching on the
1.
:
ON START OPERATION
|
Confirm with
.
WEEK PROGRAM
Select this option to allow the appliance to respond
to demand only during pre-programmed
periods, only frost protection is active.
Note
First consult the chapter about switching
•
•
EXTRA PERIOD
11.4 Setting the water temperature
Select this option to overrule the OFFmode or
PROGmode (i.e. Week program) so that a single
demand will be fulfilled.
11.4.1
Setting the water temperature via
the SET POINT MENU
The water temperature can be set to any value
between 40°C and 80°C.
SETTINGS
language and the time. You can also use this
option to display the regulation interval
(temperature), and the ignition and working
speeds of the fan.
Set the water temperature via:
1.
:
ON
|
CHANGE SETPOINT
Confirm with
.
START OPERATION
^»CHANGE SETPOINT
Note
If you fail to make any selection with the main
È
Tset=65ÉC
menu open, then after 30 seconds, the appliance will
automatically return to the mode it was previously in.
2. Use:
•
•
to increase the value;
to decrease the value.
11.2 Notationalconventionformenu-related
instructions
The MENU
(
) of the electronic controller is divided
into submenus. For example, SETTINGSis one of the
functions reached from the main menu. The
SETTINGSmenu is divided into submenus in turn.
Instruction manual BFC
59
Download from Www.Somanuals.com. All Manuals Search And Download.
11
Main menu
gis
•
Confirm with
.After confirming, the
This following are discussed:
appliance enters "ONmode".
•
•
•
•
SETPOINT
» 65ÉC
11.6 Starting and stopping the week
program
Note
If the preset temperature is higher than the current
The week program can be started up from any other
operating mode, as follows:
water temperature, then the appliance might not
immediately start the heating cycle. To prevent
excessively frequent switching on and off, there is a
heating margin. The standard setting for this margin is
4°C. The appliance starts heating when the water
temperature is 4°C colder than the SETPOINT.
We refer to this margin as the hysteresis. The service
and maintenance engineer can adjust (12.2 "Setting
the hysteresis") this setting.
1.
:
WEEK PROGRAM
|
START OPERATION
Confirm with
.
A week program can be shut down simply by
activating a different operating mode, for example the
"ON mode".
11.7 Changing the appliance's standard
week program
11.4.2
Setting water temperature during
ON mode
Note
First fill-in the desired week program on the
supplied week program card.
The water temperature can also be directly adjusted
when the appliance is in the "ON mode". Simply use:
A week program is made up of a number of
programmable periods in which you can have the
appliance switch on and off. A period consists of:
•
•
•
to increase the value;
to decrease the value.
Confirm with
.
•
switch-on time: day of the week, hours and
minutes:
ON
•
•
•
switch-off time: hours and minutes;
the water temperature setting;
13:45 Thursday 65ÉC
Tset»65ÉC
on/off setting for a program-controlled pump.
11.5 Week program
Note
Using the week program, you can set the water
temperature for the days and times you want.
The switch-off time must always be followed by a
switch-off time on the same day of the week. A
maximum of three periods may be programmed per
day. You can program a maximum of 21 periods.
If the appliance is running under a week program, this
is indicated on the display by the PROGtext on the first
line (see the figure). The second line shows the time
of day, the day of the week and the temperature. The
third line shows the next switching time of the week
program and the programmed temperature. The fourth
line shows the PROGRAM ACTIVATEDtext.
Call up the menu for the week program as follows:
•
:
WEEK PROGRAM PROGRAM OVERVIEW.
|
Confirm with
.
WEEK PROGRAM
PROG
07:55 Monday
MO 08:00 Tset 75ÉC
PROGRAM ACTIVATED
START OPERATION
^»PROGRAM OVERVIEW
È
64ÉC
The appliance's default week program switches the
appliance on every day at 00:00 and off at 23:59. The
default water temperature setting is 65°C.
If you want, you can change every setting in the
appliance's standard week program.
If the water temperature becomes too low while the
week program is running, the appliance will run
through the heating cycle (9.3 "The appliance's
heating cycle") and return to the week program.
60
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
gis
The display shows the menu for the week program,
see the figure below. With the default setting, the
program switches on and off every day at 00:00 and
23:59 hours respectively, the water temperature is
Confirm with
.
The cursor moves to the minute digits, which flash.
ON SU 08»00
OFF SU 08:00
Tset 65ÉC
65°C and the pump is switched on (P).
DAY TIME Tset
ON »SU 00:00 65ÉC P
OFF SU 23:59
PUMP ON
SAVE
Note
ON MO 00:00 65ÉC P
Because the switch-off time can never be earlier
than the switch-on time, the switch-off time setting is
automatically adjusted with the switch-on time.
OFF MO 23:59
ON TU 00:00 65ÉC P
OFF TU 23:59
ON WE 00:00 65ÉC P
OFF WE 23:59
ON TH 00:00 65ÉC P
OFF TH 23:59
4. Use and to set the minutes. In the example,
this is 15
.
Confirm with
.
The cursor moves to the switch-off hour digits,
which flash.
ON FR 00:00 65ÉC P
OFF FR 23:59
ON SA 00:00 65ÉC P
OFF SA 23:59
ON SU 08:15
OFF SU»08:15
Tset 65ÉC
INSERT
DELETE
START OPERATION
PUMP ON
SAVE
11.7.2
Week program: setting the switch-
off time
Example
As an example, we will set the switch-on time for
Sunday to 08:15 hours, and the matching switch-off
time to 12:45 hours. The water temperature will be set
to 75 °C and the pump will run continuously.
The following settings are entered one by one via the
menu: the switch-on time, the switch-off time, the
desired water temperature, and the mode of the
program-controlled pump.
1. Use and to set the hours. In the example, this
is 12
.
Confirm with
.
The cursor moves to the minute digits, which flash.
ON SU 08:15
OFF SU 12»15
Tset 65ÉC
PUMP ON
SAVE
11.7.1
Week program: setting the switch-
on time
2. Use and to set the minutes. In the example,
this is 45
.
1. Bring the cursor to SU
Confirm with
.
Confirm with
.
The cursor moves to the desired water
temperature.
ON »SU 00:00
OFF SU 23:59
Tset 65ÉC
ON SU 08:15
OFF SU 12:45
Tset»65ÉC
PUMP ON
SAVE
flashes.
The day indicated by
»
PUMP ON
SAVE
2. Use and to set the desired day. In the example
this is SU(Sunday).
11.7.3
Week program: setting the water
temperature
Confirm with
.
1. Use and to set the water temperature. In the
example this is 75°C.
ON SU»00:00
OFF SU 00:59
Tset 65ÉC
Confirm with
.
PUMP ON
SAVE
The cursor moves to PUMP ON
The cursor moves to the hour digits, which flash.
ON SU 08:15
OFF SU 12:45
Tset 75ÉC
3. Use and to set the hours. In the example, this
is 08.
PUMP»ON
SAVE
Instruction manual BFC
61
Download from Www.Somanuals.com. All Manuals Search And Download.
11
Main menu
gis
The display shows the menu for the week
program. The cursor points to the active period.
11.7.4
Week program: setting the program-
controlled pump
1. If required, a pump can be controlled during the
period. Use and to set PUMP ON . The pump
ensures a regular circulation of hot water in the hot
water pipes. You can skip this step if you there is
no pump in your hot water circuit.
DAY TIME Tset
ON »SU 08:15 75ÉC P
OFF SU 12:45
ON MO 00:00 65ÉC P
....................
....................
OFF SA 23:59
INSERT
Confirm with
.
The cursor moves to
SAVE.
ON
SU 08:15
OFF SU 12:45
Tset 75ÉC
DELETE
START OPERATION
2. Scroll to INSERT
.
PUMP»ON
SAVE
Confirm with
.
2. Confirm with
.
The sub-menu for adding a period will appear.
The display shown in the figure will appear.
ON »SU 08:15
OFF SU 12:45
Tset 75ÉC
DAY TIME Tset
ON »SU 08:15 75ÉC P
OFF SU 12:45
PUMP ON
SAVE
ON MO 00:00 65ÉC P
OFF MO 23:59
ON TU 00:00 65ÉC P
OFF TU 23:59
Example
As an example, we will program an extra period in
which the switch-on time is set to 18:00 hours, and the
corresponding switch-off time to 22:00 hours. The
water temperature will be set to 75 °C and the pump
will run continuously.
3. If you wish, you can use to scroll to another day,
and change more switch-on times (11.7.1 "Week
program: setting the switch-on time") and switch-
off times (11.7.2 "Week program: setting the
DAY TIME Tset
ON »SU 18:00 75ÉC P
OFF SU 22:00
4. After changing all desired switch-on and switch off
times, you can start running the week program:
ON MO 00:00 65ÉC P
OFF MO 23:59
....................
....................
OFF SA 23:59
INSERT
Scroll with to START OPERATION
Confirm with
.
.
11.8 Adding times to a week program
Call up the menu to INSERTswitch-on and switch-off
times into a week program as follows:
DELETE
START OPERATION
1.
:
WEEK PROGRAM
Confirm with
WEEK PROGRAM
START OPERATION
|
PROGRAM OVERVIEW.
3. Proceed as follows:
.
^»PROGRAM OVERVIEW
È
d. Set the program-controlled
5. To activate the week program with the new period
added, scroll down with to
START OPERATIONand confirm with
.
62
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
gis
11.9 Deleting times from a week program
Confirm with
.
All switch-on/off times are shown sequentially in the
display. Assume that the switch-on/off times for the
appliance are programmed as in the figure.
DAY TIME Tset
ON !SU 18:00 75ÉC P
OFF SU 22:00
ON MO 00:00 65ÉC P
DAY TIME Tset
ON »SU 08:15 75ÉC P
OFF SU 12:45
OFF MO 23:59
....................
....................
OFF SA 23:59
INSERT
ON SU 18:00 75ÉC P
OFF SU 22:00
....................
....................
OFF SA 23:59
INSERT
DELETE
START OPERATION
5. The lines showing switch-on/off times are replaced
DELETE
START OPERATION
by the text DELETE BLOCK?. See the figure.
Confirm with
(or use
.
to cancel)
To delete a period, proceed as follows:
1.
:
WEEK PROGRAM
Confirm with
MENU
OFF
^»ON
È WEEK PROGRAM
|
PROGRAM OVERVIEW.
DAY TIME Tset
ON !
OFF
DELETE
BLOCK?
ON MO 00:00 65ÉC P
.
The switching period has been deleted. You will return
now to the week program menu. The cursor points to
the first programmed period.
2. Scroll with to PROGRAM OVERVIEW
.
DAY TIME Tset
ON »SU 08:15 75ÉC P
OFF SU 12:45
Confirm with
.
WEEK PROGRAM
ON MO 00:00 65ÉC P
START OPERATION
^»PROGRAM OVERVIEW
È
OFF MO 23:59
....................
....................
OFF SA 23:59
INSERT
The display shows the menu for the week
program.
3. Scroll with to DELETE
.
DELETE
START OPERATION
Confirm with
.
To warn you that you are now working in the delete
sub-menu, the cursor is replaced with an
exclamation mark (!) and the period settings flash.
6. Scroll with to START OPERATION
.
Confirm with
.
The week program is active.
DAY TIME Tset
ON !SU 08:15 75ÉC P
OFF SU 12:45
11.10 Extra period
Use an extra period when you either want to have the
appliance switch on and off for a certain period, either
without modifying the active week program, or without
taking the appliance out of the OFF mode (frost
protection active).
ON SU 18:00 75ÉC P
OFF SU 22:00
....................
....................
OFF SA 23:59
INSERT
If the appliance is running under an "extra period",
then this is indicated in the display with the text
DELETE
START OPERATION
EXTRA
.
EXTRA
10:00 Monday
MO 11:15 Tset 75ÉC
PERIOD ACTIVATED
4. Scroll with to the day to be deleted. For
example, SU(Sunday) in the second period. See
the figure.
76ÉC
Instruction manual BFC
63
Download from Www.Somanuals.com. All Manuals Search And Download.
11
Main menu
gis
If the water temperature becomes too low during the
the appliance will run through the heating
back into the extra period.
Setting the switch-off time
1. Use and to set the hours. In the example, this
is 012
Confirm with
The cursor moves to the minute digits, which flash.
.
.
The same settings can be made for an extra period as
for a week program (11.7 "Changing the appliance's
standard week program") period.
ON
SU 08:15
OFF SU 12»15
Tset 65ÉC
11.11 Programming an extra period
PUMP ON
START
1. Call up the menu for entering an extra period via:
2. Use and to set the minutes. In the example,
this is 45
2.
:
EXTRA PERIOD
Confirm with
MENU
ON
.
.
Confirm with
.
The cursor moves to the water temperature. See
the figure
^ WEEK PROGRAM
ȻEXTRA PERIOD
ON
SU 08:15
OFF SU 12:45
Tset»65ÉC
The display show the settings for the extra period.
Setting the switch-on time
PUMP ON
START
1. Use and to set the day. In the example this is
Setting the water temperature
SU
Confirm with
The cursor moves to the hour digits, which flash.
.
1. Use and to set the water temperature. In the
example this is 75°C.
.
Confirm with
.
The cursor moves to PUMP ON
ON
SU»00:00
OFF SU 00:59
Tset 65ÉC
ON
SU 08:15
OFF SU 12:45
Tset 75ÉC
PUMP ON
START
PUMP»ON START
2. Use and to set the switch-on hour to the
desired value. In the example, this is 08.
Setting the program-controlled pump
Confirm with
.
1. If required, a pump can be controlled during the
period. Use and to set PUMP ON. The pump
ensures a regular circulation of hot water in the hot
water pipes. You can skip this step if you there is
no pump in your hot water circuit.
The cursor moves to the minute digits, which flash.
ON
SU 08»00
OFF SU 08:00
Tset 65ÉC
PUMP ON
START
Confirm with
.
The cursor moves to START
.
Note
ON
SU 08:15
OFF SU 12:45
Tset 75ÉC
Because the switch-off time can never be earlier
than the switch-on time, the switch-off time setting is
automatically adjusted with the switch-on time.
PUMP ON »START
3. Use and to set the minutes. In the example,
2. Confirm with
.
this is 15
.
The extra period has been programmed.
Confirm with
.
The cursor moves to the hour digits of the switch-
off period.
Note
Once the extra period has completed running, the
controller returns to the mode ON, OFF or
WEEK PROGRAM. The following week, the extra
period will NOT be automatically switched on.
ON
SU 08:15
OFF SU»08:15
Tset 65ÉC
PUMP ON
START
64
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
gis
11.12 Settings
11.12.2 Setting day and time
Using the SETTINGSoption, you can adjust certain
To enter the time and day:
settings and read certain appliance data:
MENU
•
•
Adjustable settings
WEEK PROGRAM
^ EXTRA PERIOD
ȻSETTINGS
-
-
Language of the menu.
Current day of week and time.
Displayable appliance specifications, this
category is only relevant to the installation
engineer and/or service and maintenance
engineer
1. Call up the menu for entering the day and time as
follows:
2.
:
SETTINGS
Confirm with
The display shows the menu for settings.
3. Scroll with and to DAYTIME
.
.
-
-
-
Control range (water temperature).
Ignition speed of fan.
/
Working speed of fan.
Confirm with
.
11.12.1 Setting menu language
SETTINGS
To set menu language:
LANGUAGE
MENU
^»DAY/TIME
È SPECIFICATIONS
WEEK PROGRAM
^ EXTRA PERIOD
ȻSETTINGS
The display shows the sub-menu for adjusting the
day.
1. Call up the menu for selecting the language as
follows:
DAY
»Sunday
^ Monday
È Tuesday
2.
:
SETTINGS
Confirm with
The display shows the menu for settings.
.
.
Wednesday
Thursday
Friday
SETTINGS
»LANGUAGE
^ DAY/TIME
È SPECIFICATIONS
Saturday
4. The cursor is positioned beside Sunday
.
Scroll with and to the desired day.
3. The cursor is positioned beside LANGUAGE
Confirm with
.
Confirm with
.
The day has been set. The display shows the sub-
menu for adjusting the time.
The display shows the language selection menu.
LANGUAGE
TIME
ENGLISH
»00:00
^ NEDERLANDS
ȻDEUTSCH
FRANCAIS
ITALIANO
CZECH
5. The cursor moves to the hour digits, which flash.
Scroll with and to the current hour, for
example 15.
ESPANOL
4. Scroll with to the desired language.
Confirm with
.
Confirm with
.
TIME
The language is set.
15»00
6. The cursor moves to the minute digits, which flash.
Scroll with and to the next minute, for example
45.
Instruction manual BFC
65
Download from Www.Somanuals.com. All Manuals Search And Download.
11
Main menu
gis
The display shows the sub-menu for displaying
appliance specifications.
Confirm the minute setting with
TIME
15»45
SPECIFICATIONS
»REGULATION INTERVAL
^ IGNITION SPEED
È WORKING SPEED
The time has been set.
3. Scroll with to the section to be displayed, for
example REGULATION INTERVAL
.
Note
The appliance takes no account of daylight saving.
The relevant display appears.
REGULATION INTERVAL
40_80ÉC
11.12.3 Displaying appliance specifications
Note
This category is solely intended for the installation
engineer and/or service and maintenance engineer.
The table shows the correct settings.
BFC 28
BFC 30
Ignition fan speed
(rpm)
4500
4500
Working speed of fan 5000
5400
(rpm)
Regulation interval
( C)
40 - 80
40 - 80
o
BFC 50
BFC 60
Ignition fan speed
(rpm)
4500
4500
Working speed of fan 6000
6660
(rpm)
Regulation interval
( C)
40 - 80
40 - 80
o
Call up the menu to display the appliance
specifications as follows:
1.
:
SETTINGS
Confirm with
MENU
WEEK PROGRAM
.
.
^ EXTRA PERIOD
ȻSETTINGS
2. Scroll with to SPECIFICATIONS
Confirm with
.
SETTINGS
LANGUAGE
^ DAY/TIME
ȻSPECIFICATIONS
66
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
is
12 Service program
hysteresis. The standard setting for this margin is 2°C.
The heating cycle starts if the water temperature drops
to 2°C below the SETPOINT and ends when the water
reaches 2°C above the SETPOINT.
12.1 Introduction
The service program is used by the installation
engineer or service and maintenance engineer for:
•
•
•
•
•
•
•
•
•
HYSTERESE UP »3ÉC
Set the hysteresis via:
•
:
HYSTERESE UP
The figure shows an example
Set the hysteresis via:
HYSTERESE DOWN
•
:
SERVICE MENU
12.3 Displaying the error history
»HYSTERESE
^ HISTORY OF ERRORS
È APPLIANCE HISTORY
Display the error history as follows:
•
:
HISTORY OF ERRORS
The controller will display an overview of "Blocking
errors" and "Lock out errors". In both cases, the
electronic controller reserves 15 lines for the last 15
error messages. If there are fewer than 15 error
messages, an ellipsis (...) is displayed. The display
SELECT APPLIANCE
PUMP RELAY
SERVICE INTERVAL
CONTRAST DISPLAY
TIME BACKLIGHT
SCROLLSPEED
first shows the "Blocking errors". When
is
pressed, the "Lock out errors" are then displayed.
These sub-menus are briefly described in the
following paragraphs. If you are not familiar in general
with how to use the displays and menus, first read the
The figure shows an example of "Blocking errors". In
this case, the text HISTORY OF ERRORSis followed
by (B)
.
HISTORY OF ERRORS(B)
S04 SENSOR ERROR
F06 IONIZATION
Note
The notation convention for the service menu is
identical to that of the main menu (11.2 "Notational
È CO2 50 HZ ERROR
The figure shows an example of "Lock out errors". In
this case, the text HISTORY OF ERRORSis followed
difference is, you use
program, instead of
menu.
to bring up the service
which brings up the main
by (L)
.
HISTORY OF ERRORS(L)
F02 FAN
12.2 Setting the hysteresis
F07 FLAME ERROR
È ...
If the preset temperature (SETPOINT) is higher than
the current water temperature, then the appliance
might not immediately start the heating
excessively frequent switching on and off, there is a
heating margin. We refer to this margin as the
Note
For an overview of all errors and the possible
causes, please refer to the relevant
Instruction manual BFC
67
Download from Www.Somanuals.com. All Manuals Search And Download.
12
Service program
is
12.4 Displaying the appliance history
12.7 Setting the service interval
The appliance history submenu is used to display the
burning hours, the number of ignitions, the number of
flame errors and the number of ignition errors.
To aid servicing, the electronic controller includes a
service interval which is used to set the frequency of
maintenance interval (14.2 "Determining service
interval") by the service and maintenance engineer,
based on the number of burning hours.
Call up the menu for displaying the appliance history
as follows:
The service interval is based on the number of burning
hours. This can be set to 500, 1000 and 1500 hours.
The standard setting for number of hours is 500. Once
the preset number of hours is reached, a
•
:
APPLIANCE HISTORY
The figure shows an example.
appear. Adjust the service interval via:
APPLIANCE HISTORY
BURNINGHOURS 000410
•
:
SERVICE INTERVAL
^IGNITIONS
001000
ÈFLAME ERRORS 000021
SERVICE INTERVAL
» 500
IGNIT ERROR 000013
^ 1000 BURNING HOURS
È 1500
12.5 Display the selected appliance
12.8 Setting the display contrast
Call up the menu for displaying the appliance selection
as follows:
Adjust the display contrast via:
•
:
CONTRAST DISPLAY
•
:
SELECT APPLIANCE
The standard setting is 100%. The range is from 0
through 100%.
The appliance number can be found on the rating
plate.
The figure shows the related display.
The appliance selection has been correctly preset
in the factory.
CONTRAST DISPLAY
SELECT APPLIANCE
»5934
» 95 %
^ 8576
È 3379
12.9 Setting the display backlight time
6527
....
Set the backlight time (the time that the display
backlight remains lit after the last button is pressed) as
follows:
12.6 Switching the pump on or off
•
:
TIME BACKLIGHT
If a program-controlled pump is
installed (3.10.6 "Connecting a program-controlled
pump"), it can be switched ON or OFF as follows:
The standard value is 255 s. The range is 0 to 255
seconds.
The figure shows the related display.
•
:
PUMP RELAY
The standard setting for the pump relay is OFF.
TIME BACKLIGHT
PUMP RELAY
»ON
» 255 sec
OFF
12.10 Setting the display scroll speed
If the mode WEEK PROGRAMor EXTRA PERIODis
active, then the setting for mode WEEK PROGRAMor
EXTRA PERIODhas priority over the ON/OFF
selection for the pump relay in the service menu.
Adjust the control speed via:
•
:
SCROLLSPEED
The default is 10. The range is from 0 through 100.
Setting the value too high or low will make scrolling
difficult.
Example
One of the week program periods is currently active.
During this period, the pump relay setting is OFF. If the
pump relay is set ON in the service menu, the pump
will nonetheless remain OFF. The pump will only
switch ON once the week program period has ended.
SCROLLSPEED
» 10
68
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
gis
13 Troubleshooting
A distinction is made between:
13.1 Introduction
•
General errors
General errors are not reported on the display. General errors are:
-
-
-
-
-
Gas smell
Display does not light up
Insufficient or no hot water.
Water leakage
Explosive ignition.
The manual includes a table with general errors (13.2 "Troubleshooting
•
Displayed errors
Errors are reported on the display, as follows:
-
Line one: an error code and a brief description. The code consists of a
letter and two digits.
-
Lines two, three and four: a long description, alternating with a
recommended action. See the figures. The first shows a possible
error, the second shows the appropriate checking action.
S02: SENSOR ERROR
TOP TANK
SENSOR 1
NOT CONNECTED
S02: SENSOR ERROR
CHECK TOP TANK
SENSOR
There are various types of errors, all falling into one of two groups:
-
LOCK OUT ERRORS
When the cause has been removed, these errors require a reset with
the
button, before the appliance can resume operation.
-
BLOCKING ERRORS
These errors disappear automatically once the cause of the error has
been removed, after which the appliance resumes operation by itself.
The manual includes a table of error messages that can appear on the
Instruction manual BFC
69
Download from Www.Somanuals.com. All Manuals Search And Download.
is
13.2 Troubleshooting table for general errors
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
General errors
Symptom
Gas smell
Cause
Solution
Warning
Remark
Gas leak
Warning
Contact your installation engineer or local gas company
immediately.
Close the main gas valve immediately.
Warning
Do not operate any switches.
Warning
No naked flames.
Warning
Ventilate the boiler room.
Display is off
Appliance is turned off Start the appliance up (9 "Starting and running")
No supply voltage
present
1. Check if the isolator is ON.
See the BFC electrical diagram (17 "Appendices")
If the error persists, consult your installation engineer.
2. Check that there is power to the isolator.
3. Check whether the ON/OFF switch of the electronic controller is
ON (position I).
4. Check whether there is power to the electrical connector block.
5. The measured voltage must be 230 VAC (-15%, +10%).
Replace fuse(s)
Defective fuse(s)
To replace the fuses, you must contact your installation engineer.
Instruction manual BFC
70
Download from Www.Somanuals.com. All Manuals Search And Download.
is
Symptom
Cause
Solution
Remark
Water leakage
Leakage from a water Tighten the threaded connection
connection (threaded)
If the leak persists, consult your installation engineer
Condensate leakage
Check that the condensation water discharge is working properly.
Leakage from another Trace the leak
nearby water appliance
or pipe segment
Leakage from the
appliance's tank
Consult the supplier and/or manufacturer
Set the correct supply pressure and/or burner
Explosive ignition
Incorrect supply
If ignition is not improved, consult your installation engineer.
pressure and/or burner pressure. (3.11 "Checking the supply pressure and burner
pressure
pressure")
Contaminated burner
Contaminated orifice
Clean the burner(s) (15.4.2 "Clean the burner(s)")
Hot water supply
Appliance is turned off Start the appliance up (9 "Starting and running")
insufficient or absent
No supply voltage
present
1. Check if the isolator is ON.
See the BFC electrical diagram (17 "Appendices")
If the error persists, consult your installation engineer.
2. Check that there is power to the isolator.
3. Check whether the ON/OFF switch of the electronic controller is
ON (position I).
4. Check whether there is power to the electrical connector block.
5. The measured voltage must be 230 VAC (-15%, +10%).
Hot water supply is
used up
Reduce hot water consumption and give the appliance time to heat If there continues to be insufficient hot water, or none at all, consult
up. your installation engineer.
The controller is in OFF Switch the controller to the ON mode (11.3 "Switching on the "ON
mode. mode"")
Temperature (T ) is
set too low.
Adjust (11.4 "Setting the water temperature") temperature (T ) to
a higher value.
set
set
Instruction manual BFC
71
Download from Www.Somanuals.com. All Manuals Search And Download.
is
13.3 Troubleshooting table for displayed errors
Displayed errors
Code + Description
S01 (blocking error)
Cause
Solution
Remark
Sensorisnot(correctly) Connect the sensor lead to JP3
connected
See the BFC electrical diagram (17 "Appendices")
Open circuit from
temperature sensor T2
at bottom of the tank
Damaged cable or
defective sensor
Replace the sensor
To replace the necessary parts, you must contact your installation
engineer
S02 (blocking error)
Sensorisnot(correctly) Connect the sensor lead to JP5
connected
See the BFC electrical diagram (17 "Appendices")
Open circuit in sensor 1
of temperature sensor
Damaged cable or
defective sensor
Replace sensor T
To replace the necessary parts, you must contact your installation
engineer
1
T at the top of the
1
(1)
tank
.
S03 (blocking error)
Sensorisnot(correctly) Connect the sensor lead to JP5
connected
See the BFC electrical diagram (17 "Appendices")
Open circuit in sensor 2
of temperature sensor
T1 at the top of the tank
(1).
Damaged cable or
defective sensor
Replace sensor T
To replace the necessary parts, you must contact your installation
engineer
1
S04 (blocking error)
Dummy is not
(correctly) connected
Connect the dummy sensor (dummy sensor 1 and 2) leads to JP4. See the BFC electrical diagram (17 "Appendices")
Open circuit from
dummy 1
Defective dummy
Replace the dummy sensor
To replace the necessary parts, you must contact your installation
engineer
S05 (blocking error)
Dummy is not
(correctly) connected
Connect the dummy sensor (dummy sensor 1 and 2) leads to JP4. See the BFC electrical diagram (17 "Appendices")
Open circuit from
dummy 2
Defective dummy
Replace the dummy sensor
To replace the necessary parts, you must contact your installation
engineer
S11 (blocking error)
Short circuit in sensor Replace sensor T
circuit
To replace the necessary parts, you must contact your installation
engineer
2
Short circuit in the
temp. sensor T2 at the
bottom of the tank
Instruction manual BFC
72
Download from Www.Somanuals.com. All Manuals Search And Download.
is
Code + Description
S12 (blocking error)
Cause
Solution
Remark
Short circuit in sensor Replace sensor T
circuit
To replace the necessary parts, you must contact your installation
engineer
1
1
Short circuit in sensor 1
of temperature sensor
T at the top of the
1
(1)
tank
S13 (blocking error)
Short circuit in sensor Replace sensor T
circuit
To replace the necessary parts, you must contact your installation
engineer
Short circuit in sensor 2
of temperature sensor
T1 at the top of the
(1)
tank
(2)
(2)
S14 (blocking error)
Short circuit in sensor Replace the dummy sensor
circuit
To replace the necessary parts, you must contact your installation
engineer
Short circuit from
dummy 1
S15 (blocking error)
Short circuit in sensor Replace the dummy sensor
circuit
To replace the necessary parts, you must contact your installation
engineer
Short circuit from
dummy 2
F01 (blocking error)
Live and neutral
connected wrong way the appliance is phase-sensitive
round
Connect live and neutral correctly (3.10 "Electrical connection");
See the BFC electrical diagram (17 "Appendices")
If errors persist, contact your installation engineer
Defect in power supply
circuit
Condensation on the
flame probe
1. Disconnect the lead at the flame probe
2. Ignite the appliance three times, with an interrupted ionisation
circuit
3. Reconnect the ionisation lead to the flame probe
4. Ignite the appliance again
5. The repeated ignition attempts will have caused the
condensation to evaporate
Floating neutral
Install an isolating transformer (3.10.4 "Isolating transformer")
Contact your installation engineer to have an isolating transformer
installed
Instruction manual BFC
73
Download from Www.Somanuals.com. All Manuals Search And Download.
is
Code + Description
F02 (lock out error)
Cause
Solution
Remark
Defective motor and/or 1. Check the motor and rotor
rotor.
See the BFC electrical diagram (17 "Appendices")
2. Replace the fan if the motor or rotor is defective.
Fan fails to run at
correct speed.
To have the wiring replaced and a new fan fitted, you must contact
your installation engineer
3. Reset appliance controller
Damaged wiring
1. Check the wiring between the fan and the controller.
2. If any wires are damaged, the wiring harness must be replaced.
3. Reset appliance controller
Dirty or blocked fan
1. Check if the fan is dirty
2. Check that the rotor can rotate freely
3. Reset appliance controller
Because of a drop in
the supply voltage, the
fan is not running at the
correct speed.
1. Check the supply voltage, this must be 230 VAC (-15%, +10%).
2. Reset appliance controller
The F02 entries below are applicable solely to appliances that have a 3-phase fan with frequency controller.
Fun supplying
insufficient pressure
The live (phase) wires, 1. Check the wiring between the fan and the frequency controller See the BFC electrical diagram (17 "Appendices")
betweenfreq. controller
and fan are connected
wrong way around
2. Rectify the assembly if it is incorrect
To replace the necessary parts, you must contact your installation
engineer
3. Reset appliance controller
Fan speed too low
1. Check the fan speed
2. If the fan speed is too low, check the settings
3. If the settings are correct, then replace the fan.
4. Modify the settings if incorrect
5. Reset appliance controller
Instruction manual BFC
74
Download from Www.Somanuals.com. All Manuals Search And Download.
is
Code + Description
Cause
Solution
Remark
Air pressure switch fails Air pressure switch
1. Check the wiring between the air pressure switch and the
controller. Rectify any defect:
to close during pre-
purge.
leads
-
-
if any wires are damaged, replace the wiring harness
properly connect loose or detached hoses
2. Reset appliance controller
Loose air pressure
switch hoses
1. Check hoses between air pressure switch and burner/fan.
Rectify any defect:
-
-
if any wires are damaged, replace the wiring harness
properly connect loose or detached hoses
2. Reset appliance controller
Heat exchanger and/or 3. Measure the pressure differential across the air pressure switch
chimney flue is blocked
4. Check the values (2.4.5 "Pressure switch")
5. Check heat exchanger, condensation drainage and/or chimney
flue for blockages
6. Clear any blockage that may be present.
7. Reset appliance controller
Defective controller
1. Check that the controller is receiving power
2. Check that the controller is correctly connected
3. If there is no electrical power, check the power supply to the
terminal block, or replace the controller.
4. Rectify any incorrect connections.
5. Reset appliance controller
Instruction manual BFC
75
Download from Www.Somanuals.com. All Manuals Search And Download.
is
Code + Description
F03 (lock out error)
Cause
Solution
Remark
Damaged wiring/Open 1. Check the wiring between the pressure switch and the
circuit
If the error cannot be resolved or is persistent, contact your
installation engineer
controller
The pressure switch
fails to work correctly
To replace the necessary parts, you must contact your installation
engineer
2. If necessary, replace the wiring
Pressure switch not
closing
1. Check the running speed of the fan (12.5 "Display the selected
appliance")
hose between fan and burner are correctly fitted. Refit them if
necessary
3. Check for cracks in the hoses on the pressure switch and in the
air supply hose between fan and burner. If necessary, replace
the hoses.
4. Check that the flue gas outlet is compliant (3.9 "Air supply and
flue").
5. Check for blockage in the flue gas discharge. Remove any
blockage that may be present
6. Check for blockage in the condensation water discharge.
Remove any blockage that may be present.
7. Measure the pressure differential across the pressure switch.
See the table in Preparation for
maintenance (15.2 "Preparation for maintenance"). If there is
insufficient pressure differential, clean the heat exchanger. If the
pressure differential is acceptable, check that the pressure
switch is closing, using a multimeter.
Instruction manual BFC
76
Download from Www.Somanuals.com. All Manuals Search And Download.
is
Code + Description
F04 (lock out error)
Cause
Solution
Remark
No gas
1. Open the main gas valve and/or the manual gas valve supplying To repair the gas supply, contact your installation engineer
the water heater
Three unsuccessful
ignition attempts.
2. Check the supply pressure to the gas control
3. If necessary, repair the gas supply
Air in the gas pipes
No burner pressure
Bleed the air out of the gas pipe
See Checking the supply pressure and burner pressure for how to
bleed air from the gas line, and measure the supply pressure and
burner pressure.
To replace the necessary parts, you must contact your installation
engineer
1. Check the burner pressure to the gas control
2. Check that the gas valve(s) open and shut correctly
3. If necessary, replace the gas control.
Defect in the hot
1. Check that the hot surface igniter is correctly connected (JP2). If the error persists, contact your installation engineer.
surface igniter circuit
To replace the necessary parts, you must contact your installation
engineer
2. Check the wiring of the hot surface igniter.
lie between 2 and 5 ohms.
4. Check that the hot surface igniter lights up during ignition.
5. If necessary, replace the hot surface igniter.
Defect in the ionisation 1. Check that the flame probe is correctly connected (JP2)
circuit
2. Check the wiring of the flame probe
3. Measure the ionisation current. This must be at least 1.5
microamps.
4. Replace the wiring if necessary.
Supply voltage too low Check the supply voltage, this must be 230 VAC (-15%, +10%).
F05 (lock out error)
Incorrect roof or wall
conduit.
1. Check that the correct roof or wall flue conduit (3.9 "Air supply If the error cannot be resolved or is persistent, contact your
installation engineer
and flue") has been fitted.
Too many flame errors Recirculating flue
have been signalled. gases.
2. If necessary, install the correct roof or wall conduit.
3. Check that the roof or wall conduit discharges into a permitted
area.
Instruction manual BFC
77
Download from Www.Somanuals.com. All Manuals Search And Download.
is
Code + Description
F06 (lock out error)
Cause
Solution
Remark
Damaged cable in
contact with metal
surface.
Check the wiring of the flame probe. If necessary, replace the
wiring.
If the error persists, contact your installation engineer.
To replace the necessary parts, you must contact your installation
engineer
Short circuit between
flame probe and earth
Ceramic part of the
flame probe is
broken/cracked.
1. Check that the ceramic part of the flame probe is still intact in
the vicinity of the burner's air distribution plate.
2. If not, the flame probe must be replaced.
F07 (lock out error)
Defective gas valves
1. Check whether there is still burner pressure present after the
gas valves have closed.
If the error cannot be resolved or is persistent, contact your
installation engineer
A flame has been
detected after the gas
valve was closed.
To replace the necessary parts, you must contact your installation
engineer
2. Check whether a flame is still present after the gas valves have
closed.
3. If this is the case, the gas control must be replaced.
F08 (lock out error)
Flame detection before 1. Reset the electronic controller.
the gas valve opened.
If the error cannot be resolved or is persistent, contact your
installation engineer
To replace the necessary parts, you must contact your installation
engineer
2. If the error reappears, replace the electronic controller.
Error message from
safety relay
F09 (lock out error)
The temperature at the 1. Check that the circulation pump (if present) is working
top of the tank exceeds
If the error cannot be resolved or is persistent, contact your
installation engineer
2. Check the position of the temperature sensor T .
o
1
93 C.
Water temperature
safety.
3. Reset appliance controller
Instruction manual BFC
78
Download from Www.Somanuals.com. All Manuals Search And Download.
is
Code + Description
F10 (lock out error)
Cause
Solution
Remark
Pressure switch not
closing
1. Check the running speed of the fan (12.5 "Display the selected If the error cannot be resolved or is persistent, contact your
installation engineer
appliance")
Restriction on the
number of ignition
attempts based on
pressure switch state
changes.
To replace the necessary parts, you must contact your installation
engineer
2. Check that the hoses on the pressure switch and the air supply
necessary
3. Check for cracks in the hoses on the pressure switch and in the
air supply hose between fan and burner. If necessary, replace
the hoses.
4. Check that the flue gas outlet is compliant (3.9 "Air supply and
flue").
5. Check for blockage in the flue gas discharge. Remove any
blockage that may be present
6. Check for blockage in the condensation water discharge.
Remove any blockage that may be present.
7. Measure the pressure differential across the pressure switch.
See the table in Preparation for
maintenance (15.2 "Preparation for maintenance"). If there is
insufficient pressure differential, clean the heat exchanger. If the
pressure differential is acceptable, check that the pressure
switch is closing, using a multimeter.
F11 (blocking error)
Defective gas valves
See F07.
Flame detection with
closed gas valve.
Instruction manual BFC
79
Download from Www.Somanuals.com. All Manuals Search And Download.
is
Code + Description
C02 (lock out error)
Cause
Solution
Remark
Incorrect reference
voltage from the AD
converter.
1. Reset electronic controller.
To replace the necessary parts, you must contact your installation
engineer
2. Check that the frequency of the power supply is
compliant (3.4.2 "General and electrical specifications"). If this
is not the case, contact your installation engineer
Error message from the
appliance controller.
3. If the frequency is correct but the error persists, replace the
electronic controller.
from the appliance
controller.
•
EEPROM read
error
•
•
50 Hz error
Internal
communication
error
Internal error message
from the appliance
controller.
•
Gas valve relay
error
•
•
•
•
•
Safety relay error
Ignition relay error
RAM error
EEPROM error
EEPROM contents
do not match the
software version
•
Processor software
error
C03 (blocking error)
Too many resets in too Wait for the error to disappear (maximum 1 hour). If the error does To replace the necessary parts, you must contact your installation
short a period.
not disappear, replace the appliance controller.
engineer
Reset error
C04 (blocking error)
Incorrect appliance
selection / Incorrect
selection resistor
1. Check whether the correct appliance is selected (12.5 "Display If the error cannot be resolved or is persistent, contact your
installation engineer
the selected appliance").
Appliance selection
error
To replace the necessary parts, you must contact your installation
engineer
2. If the correct appliance is selected, fit the correct selection
resistor.
3. If incorrect appliance selected, select the correct one.
Instruction manual BFC
80
Download from Www.Somanuals.com. All Manuals Search And Download.
is
Code + Description
E01 (blocking error)
Cause
Solution
Remark
The temperature of the None. This is a temporary message that may appear from time to
water at the top of the
tank is > 85 C.
time, but will disappear automatically.
o
The temperature
protection at the top of
the tank has been
activated.
E03 (lock-out error)
The two temperature
sensors in the tank
1. Check sensor position and wiring.
To replace the necessary parts, you must contact your installation
engineer
2. If necessary, reset the electronic controller. Replace the sensor
if the error persists.
detect a differential of >
Error in temperature
o
10 C over a period of
sensor T at the top of
1
at least 60 seconds.
the tank.
E04 (lock-out error)
The two dummy
1. Check leads from dummy 1 and dummy 2.
To replace the necessary parts, you must contact your installation
engineer
sensors in the tank
detect a differential of >
2. If necessary, reset the electronic controller. Replace the dummy
sensor if the error persists.
Error in dummy
o
(2)
10 C over a period of
sensor
.
at least 60 seconds.
1) Temperature sensor T is a '2 in 1' sensor, T contains 2 NTCs for the high-limit thermostat and safety thermostat protection.
1
1
(2) The dummy sensor / flue gas sensor comprises dummy sensor / flue gas sensor 1 and dummy sensor / flue gas sensor 2.
Instruction manual BFC
81
Download from Www.Somanuals.com. All Manuals Search And Download.
is
Instruction manual BFC
82
Download from Www.Somanuals.com. All Manuals Search And Download.
is
14 Maintenance
frequency
A service should be carried out at least once a year, both on the water side and
on the gas side. Maintenance frequency depends, among other things, on the
water quality, the average burning time per day and the set water temperature.
14.1 Introduction
Note
Regular maintenance extends the service life of the appliance.
To determine the correct maintenance frequency, it is recommended to arrange
for the service and maintenance engineer to check the appliance on both the
water and gas side, three months after installation. Based on this check, the
best maintenance frequency can be determined.
To aid servicing, the electronic controller has a service interval with which the
service and maintenance engineer can determine the frequency of
maintenance, based on the number of burning hours.
14.2 Determining service
interval
The service interval can be set to: 500, 1000 or 1500 burning hours. The
standard setting is 500 burning hours.
Example
In the first three months, the appliance has burnt 300 hours. During
maintenance, it is evident that one service per year will be sufficient. Therefore,
after one year, some 1200 burning hours will have elapsed. The first value below
1200 hours that can be selected is 1000 burning hours.
In this case, the service and maintenance engineer sets the interval to 1000.
In the first three months, the appliance has burned for 300 hours. During
maintenance, it is evident (perhaps due to the water quality) that service will be
required at least once every 6 months.
Therefore, after six months, some 600 burning hours will have elapsed. The first
value below 600 hours that can be selected is 500 burning hours.
In this case, the service and maintenance engineer sets the interval to 500.
!!! WARNING !!!
MAX. BURNINGHOURS:
SERVICE REQUIRED
Once the set number of burning hours has elapsed, the message
SERVICE REQUIREDwill appear on the display. When this message
appears, the service and maintenance engineer must be contacted.
Instruction manual BFC
83
Download from Www.Somanuals.com. All Manuals Search And Download.
14
Maintenance frequency
is
84
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
s
15 Performing
maintenance
Attention
15.1 Introduction
Maintenance may only be performed by a qualified service and
maintenance engineer.
At each service, the appliance undergoes maintenance on both the water side
and the gas side. The maintenance must be carried out in the following order.
Note
To order spare parts, it is important to write down the appliance type and
model, and the full serial number of the appliance. These details can be found
on the rating plate. Only by ordering with this information can you be sure to
receive the correct spare parts.
To test whether all components are still working properly, complete the following
steps:
15.2 Preparation for
maintenance
1. Activate the MENUwith
.
2. Use: and to place the cursor beside OFF
.
3. Confirm OFFwith
.
MENU
»OFF
^ ON
È WEEK PROGRAM
4. Wait until the fan has stopped. The icon is then dimmed.
Attention
Failure to wait until the fan stops purging can cause damage to the
appliance.
5. Switch the appliance OFF (position 0) using the ON/OFF switch on the
control panel.
Instruction manual BFC
85
Download from Www.Somanuals.com. All Manuals Search And Download.
15
Performing maintenance
s
n
min
0063
IMD-0423 R0
6. Switch the electronic controller ON by setting the ON/OFF switch to
position I.
INTERNAL CHECK
The display will now show INTERNAL CHECKfor about 10 seconds, and
will then go to the main menu.
MENU
»OFF
^ ON
È WEEK PROGRAM
7. Activate "ON mode" by going through the following steps:
-
Press once on the blue arrow ( ) to position the cursor beside ON
then press
Confirm the selection START OPERATIONwith
,
.
-
.
temperature"). Note the original setting. Draw some hot water off to create
heat demand.
set
11. Remove the plastic cover on the top of the appliance.
12. Check the supply and burner pressure (3.11 "Checking the supply pressure
and burner pressure"), and adjust them if necessary.
13. Check that all components of the chimney flue system are properly attached.
14. Check the pressure differential across the orifice plate of the pressure switch
(see the table). If the pressure difference is too low, the heat exchanger must
Pressure switch pressure differential
Appliance Observed pressure differential across the pressure switch
(Pa)
BFC 28
BFC 30
BFC 50
BFC 60
> 635
> 885
> 885
> 1085
86
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
s
15. Test the operation of the overflow valve of the protected cold supply setup.
The water should spurt out.
16. Test the overflow operation of the T&P valve. The water should spurt out.
17. Check the drain pipes from the discharge points of all valves and remove
any lime buildup that may be present.
15.3 Water-side mainte-
nance
15.3.1 Introduction
The following steps must be carried out on the water side:
15.3.2 Checking the anodes
Timely replacement of the anodes extends the service life of the appliance. The
appliance's anodes must be replaced as soon as they are 60% or more
consumed (take this into consideration when determining the maintenance
frequency).
1. Loosen the anodes using suitable tools.
2. Check the anodes, and if necessary, replace them.
15.3.3 Descaling and cleaning the tank
Scale and lime buildup prevent effective conduction of the heat to the water.
Periodic cleaning and descaling prevents buildup of these deposits. This
increases the service life of the appliance, and also improves the heating
process.
Take the rate of scale formation into account when deciding on maintenance
frequency. Scale formation depends on the local water composition, the water
consumption and the water temperature setting. A water temperature setting of
maximum 60°C is recommended for prevention of excessive scale buildup.
To guarantee a good, watertight seal around the cleaning opening, replace the
gasket, washers, bolts and, if necessary, the lid with new parts before
reassembly (see the figure). A special set is obtainable from the
supplier/manufacturer.
To simplify descaling and cleaning of the tank, the appliance is equipped with
two cleaning openings.
1
IMD-0080 R1
1. Remove the cover plate (1) on the outer jacket (see the figure).
2. Undo the bolts.
3. Remove the cover and the gasket.
Instruction manual BFC
87
Download from Www.Somanuals.com. All Manuals Search And Download.
15
Performing maintenance
s
4. Inspect the tank and remove the loose scale deposits and contamination.
5. If the scale cannot be removed by hand, then the appliance will need to be
descaled using a descaling agent. Contact the supplier for advice on the
preferred descaling agent.
6. Close the cleaning opening. To avoid damage to the tank, tighten the bolts
that fasten the lid with a torque no greater than 50 Nm. Use suitable tools for
this.
15.3.4 Cleaning condensation water discharge
Regular cleaning of the condensation drain and siphon is essential for
prevention of blockages.
15.4 Gas-side mainte-
nance
15.4.1 Introduction
The following steps must be carried out on the gas side:
15.4.2 Clean the burner(s)
1. Detach the burner(s)
2. Remove all contamination present on the burner(s).
3. Fit the burner(s)
15.4.3 Clean the orifice(s)
1. Detach the orifice(s)
2. Remove all contamination present in the orifice(s).
3. Fit the orifice(s)
15.4.4 Cleaning the heat exchanger
1. Detach the burner.
2. Clean the combustion chamber of the heat exchanger using a vacuum
cleaner and a soft brush.
3. Detach the flue gas discharge.
4. Clean the end of the heat exchanger using tap water.
5. Fit the burner.
6. Fit the flue gas discharge.
Note
Check the pressure differential again after cleaning. If the pressure
difference is too low following cleaning, please contact the supplier of the
appliance.
To finalize the maintenance carry out the following steps:
15.5 Finalizing mainte-
nance
3. Erase the message SERVICE REQUIRED. Do this by pressing once on
then once on
.
88
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
gis
16 Warranty (certificate)
To register your warranty, you should complete and return the enclosed
warranty card after which a warranty certificate will be sent to you. This
certificate gives the owner of a appliance supplied by A.O. Smith water Products
Company B.V. of Veldhoven, The Netherlands (hereinafter "A.O. Smith") the
right to the warranty set out below, defining the commitments of A.O. Smith to
the owner.
If within one year of the original installation date of a water heater supplied by
A.O. Smith, following verification, and at the sole discretion of A.O. Smith, a
section or part (with exclusion of the tank) proves to be defective or fails to
function correctly due to manufacturing and/or material defects, then A.O. Smith
shall repair or replace this section or part.
16.1 General warranty
16.2 Tank warranty
If within 3 years of the original installation date of a water heater supplied by
A.O. Smith, following inspection, and at the sole discretion of A.O. Smith, the
glass-lined steel tank proves to be leaking due to rust or corrosion occurring on
the water side, then A.O. Smith shall offer to replace the defective water heater
with an entirely new water heater of equivalent size and quality. The warranty
period given on the replacement water heater shall be equal to the remaining
warranty period of the original water heater that was supplied. Notwithstanding
that stated earlier in this article, in the event that unfiltered or softened water is
used, or allowed to stand in the water heater, the warranty shall be reduced to
one year from the original installation date.
The warranty set out in article 1 and 2 will apply solely under the following
conditions:
16.3 Conditions for Instal-
lation and use
a. The water heater is installed under strict adherence to A.O. Smith
installation instructions for the specific model, and the relevant
government and local authority installation and building codes, rules and
regulations in force at the time of installation.
b. The water heater remains installed at the original site of installation.
c. The appliance is exclusively used with drinking water, which at all times
can freely circulate (a separately installed heat exchanger is mandatory
for heating salt water or corrosive water).
d. The tank is safeguarded against harmful scaling and lime buildup by
means of periodic maintenance.
e. The water temperatures in the heater do not exceed the maximum
setting of the thermostats, which form a part of the water heater.
f. The water pressure and/or heat load do not exceed the maximum values
stated on the water heater rating plate.
g. The water heater is installed in a non-corrosive atmosphere or
environment.
h. The water heater is connected to a protected cold supply arrangement,
which is: approved by the relevant authority; with sufficient capacity for
this purpose; supplying a pressure no greater than the working pressure
stated on the water heater; and where applicable by a likewise approved
temperature and pressure relief valve, fitted in accordance with
installation instructions of A.O. Smith applying to the specific model of
water heater, and further in compliance with the government and local
authority installation and building codes, rules and regulations.
Instruction manual BFC
89
Download from Www.Somanuals.com. All Manuals Search And Download.
16
Warranty (certificate)
gis
i. The appliance is at all times fitted with cathodic protection. If sacrificial
anodes are used for this, these must be replaced and renewed when,
and as soon as, they are 60% or more consumed. When electric anodes
are used, it is important to ensure that they continue to work properly.
The warranty set out in articles 1 and 2 will not apply in the event of:
a. damage to the water heater caused by an external factor;
16.4 Exclusions
b. misuse, neglect (including frost damage), modification, incorrect and/or
unauthorised use of the water heater and any attempt to repair leaks;
c. contaminants or other substances having been allowed to enter the tank;
d. the conductivity of the water being less than 125 µS/cm and/or the
hardness (alkaline-earth ions) of the water being less than 1.00
e. unfiltered, recirculated water flowing through or being stored in the water
heater;
f. any attempts at repair to a defective water heater other than by an
approved service engineer.
The obligations of A.O. Smith pursuant to the specified warranty do not extend
beyond free delivery from the Veldhoven warehouse of the replacement
sections, parts or water heater respectively. Shipping, labour, installation and
any other costs associated with the replacement will not be accepted by A.O.
Smith.
16.5 Scope of the
warranty
A claim on grounds of the specified warranty must be submitted to the dealer
from whom the water heater was purchased, or to another authorised dealer for
A.O. Smith water Products Company products. Inspection of the water heater
as referred to in articles 1 and 2 shall take place in one of the laboratories of
A.O. Smith water Products Company.
16.6 Claims
A.O. Smith grants no other warranty or guarantee over its water heaters nor the
(sections or parts of) water heaters supplied for replacement, other than the
warranty expressly set out in this Certificate.
16.7 Obligations of A.O.
Smith
Under the terms of the supplied warranty, A.O. Smith is not liable for damage to
persons or property caused by (sections or parts, or the glass-lined steel tank
of) a (replacement) water heater that it has supplied.
90
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
is
TERMINAL BLOCK CONNECTIONS:
Earth
N
Neutral
1
L
L
L
L
L
Phase input of controller
2
3
4
5
Phase input of isolating transformer (primary side)
Phase output of isolating transformer (secondary side)
Phase input of program-controlled pump
Phase input of continuous pump
COMPONENTS:
A
B
C
D
E
F
Controller
Flame probe
Hot surface igniter
Gas control
Burner earth connection
Extra ON mode switch
Continuous pump
G
H
J
Program-controlled pump
Extra error signal connection
Isolating transformer
Double-pole isolator
Controller 0/I switch
Display
K
L
M
N
O
P
Q
R
S
T
Fan
Temperature sensor (T2 - bottom of tank)
Dummy
Temperature sensor (T1 - top of tank)
Selection resistor
Pressure switch
CONTROLLER CONNECTIONS:
J2
Power connection for controller
J19
J20
J21
J24
J36
JP2
JP3
JP4
JP5
JP6
JP8
Extra error signal connection
Gas control connection
Program-controlled pump connection
Fan connection
Controller display connection
Flame probe and hot surface igniter connection
Temperature sensor T2 connection
Dummy connection
Temperature sensor T1 connection
Selection resistor and pressure switch connection
Extra ON mode switch connection
F1
F3
Fuse
Fuse
Instruction manual BFC
93
Download from Www.Somanuals.com. All Manuals Search And Download.
17
Appendices
is
94
Instruction manual BFC
Download from Www.Somanuals.com. All Manuals Search And Download.
17.3 Week program card
You can cut the week program card out and keep it near the appliance.
Period
DAY
TIME
Tset
Pump
ON OFF
Period
DAY
TIME
Tset
Pump
ON OFF
ON
ON
1.
2.
....°C
/
/
/
/
/
/
/
/
/
/
/
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
....°C
/
/
/
/
/
/
/
/
/
/
OFF
ON
OFF
ON
....°C
....°C
....°C
....°C
....°C
....°C
....°C
....°C
....°C
....°C
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
....°C
....°C
....°C
....°C
....°C
....°C
....°C
....°C
....°C
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
3.
OFF
ON
OFF
ON
4.
OFF
ON
OFF
ON
5.
OFF
ON
OFF
ON
6.
OFF
ON
OFF
ON
7.
OFF
ON
OFF
ON
8.
OFF
ON
OFF
ON
9.
OFF
ON
OFF
ON
10.
OFF
ON
OFF
11.
OFF
Example
Period
DAY
MO
TIME
14:30
16:15
Tset
Pump
ON OFF
ON
1.
70°C
/
OFF
MO
Instruction manual BFC
95
Download from Www.Somanuals.com. All Manuals Search And Download.
Instruction manual BFC
96
Download from Www.Somanuals.com. All Manuals Search And Download.
gis
Index
A
appliance
F
B
G
C
H
I
icons
L
M
maintenance
D
E
Instruction manual BFC
97
Download from Www.Somanuals.com. All Manuals Search And Download.
Index
mode
symbol
N
O
T
temperature sensor
operating modes
to shut down
P
U
W
water
R
S
Instruction manual BFC
0306 059