UPS OPERATING INSTRUCTIONS
PROTECT 1.
PROTECT 1.100
PROTECT 1.150
PROTECT 1.200
Download from Www.Somanuals.com. All Manuals Search And Download.
Thank you for deciding to purchase the PROTECT 1. UPS
from AEG Power Supply Systems.
The following safety instructions are an important part of
the operating instructions are will protect you against
problems from operating errors and possible dangers.
Please read these instructions carefully prior to
commissioning!
3
Download from Www.Somanuals.com. All Manuals Search And Download.
1 Notes on these Operating
Instructions
Duty to provide information
These operating instructions will help you to install and operate
the Uninterruptible Power Supply (UPS), PROTECT 1.100,
PROTECT 1.150 or PROTECT 1.200 as well as the
corresponding external battery units PROTECT 1.100 BP or
PROTECT 1.BP20, all referred to as PROTECT 1 in the
following, safely and correctly. These operating instructions
contain important information for avoiding dangers.
Please read these instructions carefully prior to
commissioning!
These operating instructions are an integral part of
PROTECT 1.
The owner of this unit is obliged to communicate the full content
of these operating instructions to all personnel transporting or
starting the PROTECT 1 or performing maintenance or any
other work on the unit.
Validity
These operating instructions comply with the current technical
specifications of PROTECT 1. at the time of publication. The
contents do not constitute a subject matter of the contract, but
serve for information purposes only.
Warranty and liability
We reserve the right to alter any specifications given in these
operating instructions, especially with regard to technical data
and operation.
Claims in connection with supplied goods must be submitted
within eight days of receiving the goods, along with the packing
slip. Subsequent claims cannot be considered.
The warranty does not apply for damage caused by non-
compliance with these instructions (such damage also includes
damage to the warranty seal). AEG will accept no liability for
4
Download from Www.Somanuals.com. All Manuals Search And Download.
consequential damage. AEG will rescind all obligations such as
warranty agreements, service contracts, etc. entered into by
AEG or its representatives without prior notice in the event of
maintenance and repair work being carried out with anything
other than original AEG parts or spare parts purchased
from AEG.
Handling
PROTECT 1. is designed and constructed so that all necessary
steps for start-up and operation can be performed without any
internal manipulation of the unit. Maintenance and repair work
may only be performed by trained and qualified personnel.
Illustrations are provided to clarify and facilitate certain steps.
If danger to personnel and the unit cannot be ruled out in the
case of certain work, it is highlighted accordingly by pictographs
explained in the safety regulations of chapter 3.
Hotline
If you still have questions after having read these operating
instructions, please contact your dealer or our hotline:
Tel:
+49 (0)180 5 234 787
+49 (0)180 5 234 789
Fax:
Copyright
No part of these operating instructions may be transmitted,
reproduced and/or copied by any electronic or mechanical
means without the express prior written permission of AEG.
© Copyright AEG 2007. All rights reserved.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
1
2
Notes on these Operating Instructions .............................4
General Information ..........................................................8
2.1 Technology................................................................8
2.2 System Description..................................................10
2.3 Technical data .........................................................12
Safety Regulations..........................................................16
3.1 Important Instructions and Explanations .................16
3.2 Accident Prevention Regulations ............................16
3.3 Qualified Personnel .................................................17
3.4 Safety Instructions for PROTECT 1. .......................17
3.5 CE certificate ...........................................................21
Set-up..............................................................................22
3
4
4.1 Unpacking and inspection .......................................22
4.2 Transport to installation site.....................................23
4.3 Set-Up......................................................................23
4.4 Overview: Connections, Operating /
Display Elements.....................................................25
4.4.1 Front view...........................................................25
4.4.2 Display ...............................................................26
4.4.3 Rear view (connections): ...................................27
5
Electrical connection.......................................................29
5.1 Safety of personnel..................................................30
5.2 Mains connection (general) .....................................30
5.2.1 Checklist for cable connections .........................30
5.2.2 Connection Cross-Sections and Fuse
Protection...........................................................31
5.3 Mains connection.....................................................32
5.3.1 Preparation for the three-phase mains
connection
....................................................32
5.3.2 Connection of the three-phase input
mains voltage.....................................................32
5.3.3 Preparation of the output cabling.......................33
5.3.4 Connection of the loads .....................................34
5.4 Connection of external battery modules..................34
5.4.1 Connection of the battery cubicle
PROTECT 1.100 BP..........................................35
6
Download from Www.Somanuals.com. All Manuals Search And Download.
5.4.2 Connection of the battery cubicle PROTECT 1.
BP20 ..................................................................36
5.5 Mechanical blocking of the PROTECT 1.................37
Start-Up...........................................................................38
6.1 Operating modes.....................................................39
6.1.1 Normal operation ...............................................39
6
6.1.2 Battery Operation / Autonomous Operation ......40
6.1.3 Bypass operation ...............................................42
6.1.4 Manual bypass...................................................44
6.1.5 Unit overload......................................................45
7
8
Interfaces and communication........................................46
7.1 Computer interface RS232......................................46
7.2 Communication Slot ................................................46
7.3 Shutdown and UPS Management Software............46
Displays and troubleshooting..........................................48
8.1.1 Signalling ...........................................................48
8.1.2 Overview table of LED displays / acoustic
warning signals ..................................................50
8.2 Faults.......................................................................52
8.2.1 Error Messages..................................................52
9
Parallel Operation ...........................................................54
9.1 Principle of Operation..............................................54
9.2 Set-up / connection of parallel operation board ......55
9.3 Operation of the UPS in a parallel system ..............57
9.3.1 Start-Up..............................................................57
9.3.2 Changes to the parallel system .........................59
10 Maintenance ...................................................................60
10.1 Charging the Battery ...............................................60
10.2 Checks.....................................................................60
10.2.1 Visual check.......................................................60
10.2.2 Checking the battery..........................................61
10.2.3 Fan check ..........................................................61
11 Storage, Dismantling and Disposal.................................62
11.1 Storage....................................................................62
11.2 Dismantling..............................................................62
11.3 Disposal...................................................................62
12 List of terms ....................................................................63
12.1 Technical terminology .............................................63
7
Download from Www.Somanuals.com. All Manuals Search And Download.
2 General Information
2.1
Technology
PROTECT 1. is an Uninterruptible Power
Supply (UPS) for essential loads such as small
data centres, servers, network components,
telecommunications equipment and similar units. It
consists of:
i
♦ Mains filter with overvoltage protection (appliance
protection / class D) and mains energy backfeed
protection
♦ Rectifier section with PFC logic
(power factor correction unit)
♦ Separate battery charger with
switch mode power supply technology
♦ IGBT inverter for continuous supply of connected loads with
sinusoidal AC voltage
♦ Automatic electronic bypass (SBS)
as additional, passive redundancy
SBS = Static Bypass Switch
♦ Manual bypass for maintenance and
service purposes (with automatic
SBS activation upon actuation)
♦ Control unit
on the basis of digital signal processor technology
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Manueller Service - Bypass
Elektron. Verriegelung
EUE
Manual service bypass
Electronic locking
SBS
PFC
PFC
Netzfilter
Mains filter
Last
Load
Netz
Mains
Filter
Filter
Gleichrichter
Rectifier
Wechselrichter
DC/ DC Booster
Ladegleichrichter
DSP Regelungslogik
Komponentendarstellung
Batteriesystem (extern)
RS 232 SNMP
Inverter
DC/DC booster
Battery charger
DSP control logic
Component diagram
Battery system (external)
RS 232 SNMP
9
Download from Www.Somanuals.com. All Manuals Search And Download.
2.2
System Description
The UPS is connected between the public utility mains and the
loads to be protected.
The power section of the rectifier converts the mains voltage to
DC voltage for supplying the inverter. The circuit technology used
(PFC) enables sinusoidal current consumption and therefore
operation with little system disturbance. A separate, second
rectifier (charging REC set up using switch mode power supply
technology) is responsible for charging or trickle-charging the
battery connected in the intermediate circuit. The configuration of
this charging REC means the harmonic content of the charging
current for the battery is almost zero, which increases the service
life of the battery even more. The inverter is responsible for
converting the DC voltage into a sinusoidal output voltage. A
microprocessor-driven control based on a pulse-width modulation
(PWM) guarantees, in conjunction with digital signal processor
technology and extremely fast pulsating IGBT power
semiconductors of the inverter, a voltage system of the highest
quality and availability on the secured busbar.
In the event of mains faults (such as e.g. current failures), the
voltage continues to be supplied from the inverter to the load
without any interruption. From this point onwards, the inverter
draws its power from the battery instead of the rectifier. Since no
switching operations are necessary, there is no interruption in the
supply to the load.
The automatic electronic bypass serves to increase the reliability
of the supply further, especially in the case of individual systems.
It switches the public mains directly through to the load without
any interruption, e.g. when there is an inverter malfunction. As a
result, the automatic bypass represents an extra passive
redundancy for the load.
An integrated, manually operated bypass unit ensures an
uninterrupted supply to the connected loads in the case of
maintenance and/or service work. The internal electronic part
(with the exception of the metal-clad manual bypass) can be
disconnected via the mains input miniature circuit breakers.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
The greatest possible supply reliability of connected loads is
attained by the parallel connection of up to max. three
PROTECT 1. UPS systems. The n+x technology thus
guarantees maximum reliability through up to double active
redundancy on the one hand as well as on the other hand the
possibility of increased power with simple redundancy or even
only higher UPS power without any redundancy. The relationship
between the available output power and the degree of active
redundancy can be seen in the following overview:
Parallel system with PROTECT 1.100
Number of UPS units
Available power
1
10 kVA
---
2
3
0
1
2
20 kVA
10 kVA
---
30 kVA
20 kVA
10 kVA
Active
redundancy
degree
---
Parallel system with PROTECT 1.150
Number of UPS units
2
Available power
1
3
0
15 kVA
---
30 kVA
15 kVA
---
45 kVA
30 kVA
15 kVA
Active
redundancy
degree
1
2
---
Parallel system with PROTECT 1.200
Number of UPS units
2
Available power
1
3
0
20 kVA
---
40 kVA
20 kVA
---
60 kVA
40 kVA
20 kVA
Active
redundancy
degree
1
2
---
11
Download from Www.Somanuals.com. All Manuals Search And Download.
2.3
Technical Data
Type rating
PROTECT 1.100
10000 VA (cos ϕ = 0.7 ind.)
7000 W
PROTECT 1.150
PROTECT 1.200
15000 VA (cos ϕ = 0.7 ind.)
10500 W
20000 VA (cos ϕ = 0.7 ind.)
14000 W
UPS input
3ph~ / N / PE
Rated connection voltage
Voltage range without
battery operation
400 V/ 230 VAC
304 VAC – 478 VAC ± 3 %
(rectifier)
176 VAC – 261 VAC VAC ± 3 %
(bypass)
Frequency
50 Hz / 60 Hz
(autom. detection)
Frequency tolerance range
± 4 Hz
Current consumption at full load (max.)
PROTECT 1.100
13 A (3ph~) / 46 A (bypass)
PROTECT 1.150
19 A (3ph~) / 68 A (bypass)
25 A (3ph~) / 91 A (bypass)
λ ≥ 0.95
PROTECT 1.200
System disturbance factor
UPS output
Nominal voltage output
220 / 230 / 240 VAC ± 1%
(configuration via
“CompuWatch” software )
Nominal frequency
Type of voltage
50 Hz / 60 Hz ± 0.1%
(dependent on mains frequency)
Sine, distortion
≤ 2% THD (linear load)
≤ 6% THD (non-linear load)
Crest factor
3:1
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Overload behaviour
with mains supply
Up to 105% continuous;
> 105% – < 130% for 10 min.
130% for 1s
Following this, automatic,
uninterrupted switchover to
integrated bypass (SBS).
Switch-off after 1 min if overload
continues to be present. (Switch
back if overload decreases = load <
90%)
Overload behaviour with
battery operation
Up to 105% continuous;
> 105% for 10 s
Short-circuit behaviour
2.5 x IN for 100 ms
Battery
Standby times with external standard battery units
Standby times (full load / half load) [min.]
PROTECT
1.200
Coupled
battery cubicles
Recharging time
to 90% capacity
PROTECT
1.100
PROTECT
1.150
1 x PROTECT 1.100 BP
2 x PROTECT 1.100 BP
3 x PROTECT 1.100 BP
16 / 42
42 / 97
60 / 134
---
---
---
---
---
---
5h
7h
10h
1 x PROTECT 1. BP 20
2 x PROTECT 1. BP 20
3 x PROTECT 1. BP 20
4 x PROTECT 1. BP 20
5 x PROTECT 1. BP 20
19 / 47
47 / 103
78 / 77
103 / 243
138 / 312
10 / 29
29 / 68
47 / 103
68 / 153
85 / 202
6 / 19
19 / 47
34 / 62
47 / 103
63 / 138
5h
9h
13h
18h
24h
Nominal DC voltage (intermediate circuit): 240 VDC
Trickle charge voltage: 274 VDC ± 1%
Battery charging current (max.): 4.2 ADC
Type
Sealed, maintenance-free
PROTECT 1.100 BP
2x20 blocks 12V 9Ah,
e.g. CSB HR 1234WF2
PROTECT 1.BP20
1x20 blocks 12V 20Ah,
e.g. Panasonic LC-X1220P
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Communication
Interfaces
RS232
Sub-D (9-pin)
Additionally: Communication slot
for expansions (e.g. AS/400 / USB
/ remote signal indicator /
SNMP, …)
Shutdown software on CD
“CompuWatch” for all common
operating systems, e.g. Windows,
Linux, Mac, Unix, FreeBSD,
Novell, Sun
General data
Classification
VFI SS 111 acc. to IEC 62040–3
Sustained transformer technology
Full load efficiency
(AC-AC / DC-AC)
> 90% / > 88%
Inherent noise (1m distance)
PROTECT 1.100
PROTECT 1.150
PROTECT 1.200
Cooling type
< 55 dB(A)
< 60 dB(A)
< 60 dB(A)
Forced air cooling through
variable-speed fans
Operating temperature range 0°C to +40°C
Recommended: +15°C to +25°C
(due to battery system)
Storage temperature range
Relative humidity
Site altitude
0°C to +40°C
< 95% (without condensation)
Up to 1000 m at nominal output
Use more than 1000 m above sea
level results in the following
reduction in output power:
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Height(m) 1000 1500 2000 2500 3000
Output
100% 95% 90% 85% 80%
power
Housing colour:
Blackline
Weight:
PROTECT 1. 100
PROTECT 1. 150
PROTECT 1. 200
PROTECT 1. 100 BP
PROTECT 1. BP20
Dimensions W x H x D:
39 kg
55 kg
55 kg
135 kg
170 kg
PROTECT 1.100/1.150/1.200 260 mm x 717 mm x 670 mm
PROTECT 1.100 BP
PROTECT 1.BP 20
260 mm x 717 mm x 670 mm
260 mm x 717 mm x 810 mm
Directives
The PROTECT 1. meets the product standard EN 50091.
The CE mark on the unit confirms compliance with the EC
outline directives for 73/23 EEC – Low voltage and for 89/336
EEC – Electromagnetic compatibility if the installation
instructions described in the operating instructions are
observed.
For 73/23 EEC low-voltage
directive reference number
EN 62040-1-1 : 2003
For 89/336 EMC directive
reference number
EN 50091-2 : 1995
EN 61000-3-2 : 1995
EN 61000-3-3 : 1995
Warning:
This is a product for industrial and commercial
use in the second environment – to prevent
malfunctions, restrictions on the installation or
additional measures may be required.
i
15
Download from Www.Somanuals.com. All Manuals Search And Download.
3
Safety Regulations
3.1
Important Instructions and Explanations
The instructions for operation and maintenance, as well as the
following safety regulations must be complied with to ensure
the safety of personnel as well as the continued availability of
the unit. All personnel installing/dismantling, starting up,
operating or servicing the units must be familiar with and
observe these safety regulations. Only trained and qualified
personnel may perform the work described, using tools,
equipment, test equipment and materials intended for the
purpose and in perfect working condition.
Important instructions are emphasized by the words “Caution”,
“Attention”, “Note” and indented text.
Caution
This symbol identifies all working and operational
procedures requiring absolute compliance to
avoid any danger to persons.
Attention
This symbol identifies all working and operational
procedures requiring absolute compliance to
prevent any damage, irreparable or otherwise, to
the unit and its components.
Note
This symbol identifies technical requirements and
additional information requiring the operator's
attention.
i
3.2
Accident Prevention Regulations
Compliance with the accident prevention regulations valid in the
respective country of use and the general safety regulations in
accordance with IEC 364 is mandatory. The following safety
rules must be observed prior to performing any work on the
PROTECT 1.:
♦ Disconnect the unit from the power supply
♦ Secure the unit against being switched back on
16
Download from Www.Somanuals.com. All Manuals Search And Download.
♦ Verify that the unit is disconnected from the power supply
♦ Earth and short-circuit the unit
♦ Provide protection by covers or barriers for any
neighbouring live parts
3.3
Qualified Personnel
The PROTECT 1. may only be transported, installed,
connected and serviced by qualified personnel who are familiar
with the pertinent safety and installation regulations. All work
performed must be inspected by responsible expert personnel.
The qualified personnel must be authorised by the responsible
safety officer of the installation to perform the work required.
Qualified personnel is defined as personnel
♦ having completed training and gained experience in the
respective field,
♦ familiar with the pertinent standards, rules and
regulations and accident prevention regulations,
♦ having received instruction on the mode of operation and
operating conditions of the PROTECT 1.,
♦ capable of recognising and preventing dangers.
Regulations and definitions for qualified personnel can be found
in DIN 57105/VDE 0105 Part 1.
3.4
Safety Instructions for PROTECT 1.
The UPS is live, and the voltage can be
dangerous. The unit may only be installed and
if necessary opened by trained and qualified
personnel. Repairs may only be carried out by
qualified customer service staff!
The output can be live, even when the UPS is not
connected to the mains supply!
For health and safety reasons, the unit must be
earthed correctly!
17
Download from Www.Somanuals.com. All Manuals Search And Download.
The PROTECT 1. may only be operated with or connected to a
three-phase power system with protective grounding using a
mains connection cable with PE conductor that has been tested
according to German standards (VDE).
Risk of burning!
The battery has powerful short-circuit currents.
Incorrect connection or isolation faults can lead to
melting of the plug connections, sparking potential
and severe burns!
The unit has a warning signal that sounds when
the battery voltage of PROTECT 1. is exhausted
or when the UPS is not working in its normal
mode (see also chapter 6.1 "Signalling”, page 47ff
and the following).
Observe the following safety instructions to
ensure permanent operational safety of and safe
work with the UPS and the battery modules
(special accessories):
♦ Do not dismantle the UPS!
(The UPS does not contain any parts that require regular
maintenance. Bear in mind that the warranty will be
invalidated if the unit is opened!)
♦ Do not install the unit in direct sunshine or in close
proximity of heaters!
♦ The unit is designed to be installed inside in heated
rooms. Never install the housing in the vicinity of water or
in an excessively damp environment!
♦ Condensation may occur if the UPS is brought from a
cold environment into the room where it is to be installed.
The UPS must be absolutely dry prior to start-up. As a
result, leave it to acclimate for at least two hours.
♦ Never connect the mains input and the UPS output!
♦ Ensure that no fluids or foreign bodies can penetrate the
housing!
♦ Do not block the air vents of the unit! Make sure, for
example, that children do not insert any objects in the
ventilation openings!
18
Download from Www.Somanuals.com. All Manuals Search And Download.
♦ Do not connect household appliances such as hairdryers
to the UPS! Also take care when working with motor
loads. It is essential to avoid back-feeding the inverter,
e.g. if the load is intermittently operated in regenerative
mode.
Danger! Electric shocks!
Even after the mains voltage has been
disconnected, the components within the UPS
remain connected to the battery and can thus
cause electric shocks. It is therefore imperative
to disconnect the battery circuit before carrying
out any maintenance or repair work!
If it is necessary to replace the battery or carry
out maintenance work, this must be done by or
under the supervision of a specialist familiar
with batteries and the necessary safety
precautions!
Only authorized persons are allowed in the
vicinity of the batteries!
When replacing the batteries, the following must be observed:
Only ever use identical, maintenance-free sealed lead batteries
with the same data as the original batteries.
Danger! Explosive!
Never throw batteries into open fire.
Never open or damage batteries. (Electrolyte
may leak out and damage skin and eyes. It may
be toxic!)
Batteries can cause electric shocks and high
short-circuit currents.
Therefore, take the following safety precautions when working
with batteries:
♦ Take off watches, rings and other metallic objects!
♦ Only use tools with insulated handles!
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Avoid using multiple outlet adapters with a
central on/off switch as protection against
uncontrolled load switch-off as well as for
avoiding peak inrush currents.
i
Switch OFF the UPS using its main switch if you do not intend
to use it for some time. PROTECT 1. must be switched off
every evening if the electricity supply in your company is
switched off every night. Otherwise, the battery will be
discharged. Frequent and exhaustive discharging of the battery
leads to a shorter service life of the battery and should
therefore be avoided!
For personal safety reasons, never switch on
the main switch when the mains connector of
PROTECT 1. is disconnected!
20
Download from Www.Somanuals.com. All Manuals Search And Download.
3.5
CE Certificate
21
Download from Www.Somanuals.com. All Manuals Search And Download.
4 Set-up
4.1
Unpacking and Inspection
The unit has been completely checked and inspected. Although
the unit has been packed and shipped with the usual care,
transport damage cannot be completely excluded.
Any claims due to transport damage must
always be asserted against the transport
company!
i
Check the shipping container for damage on arrival. If
necessary, ask the transport company to check the goods and
make a record of the damage in the presence of the transport
company employee and report the damage to the AEG
representative or dealer within eight days of delivery.
Check that the delivery is complete:
♦ PROTECT 1. with 10000, 15000 or 20000 VA
♦ Cable clamping unit
♦ Special battery connection cable (PROTECT 1.100)
♦ 25-pin parallel operation cable
♦ RS232 communication cable
♦ Management software “CompuWatch” on CD
♦ Operating instructions
Delivery of external battery modules includes:
♦ External battery unit
♦ Battery connection cable
♦ Battery fuses and terminal connectors (PROTECT 1.
BP20)
Please contact our hotline (see page 5) in case of any
discrepancy.
The original packaging provides effective protection against
mechanical shocks and should be retained so the unit can be
transported safely later on.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Please keep plastic packaging bags away from babies and
children in order to safeguard against suffocation accidents.
Handle the components with care. Please take into account the
weight. It may be necessary to engage the help of a second
person.
4.2
Transport to Installation Site
The PROTECT 1. is equipped with transport rolls for easy
transport to the intended installation site. It is recommended to
install the UPS where:
♦ The connection work can be conveniently carried out;
♦ There is enough space for proper operation and, if
necessary, for periodic and extraordinary maintenance
work; in this regard, the connection cables should be
long enough to move the UPS (to open the UPS if
necessary) without having to switch it off.
♦ The use of an external manual bypass is recommended
♦ The UPS is protected against external atmospheric
influences;
♦ The humidity and the ambient temperature are within the
limits;
♦ The fire protection standards are observed.
The battery service life strongly depends on the ambient
temperature. Ambient temperatures between+ 15° and + 25°C
are optimum.
Attention!
Only transport the PROTECT 1. in an upright
position! Never tilt or cant it; avoid displacing
the centre of gravity!
Make sure that no magnetic storage media are stored and/or
operated close to PROTECT 1.
4.3
Set-Up
Note the following points when setting up the UPS system and
its external battery units (special accessories):
23
Download from Www.Somanuals.com. All Manuals Search And Download.
♦ The contact surface must be smooth and level. It must
also be sufficiently strong and sturdy to avoid vibration
and shocks.
♦ Make sure that the mounting is able to support the
weight, especially in conjunction with external battery
units (special accessories).
♦ Set up the units so that adequate air circulation is
assured. There must be at least 200 mm clearance
behind the rear fans for ventilation purposes. Do not
block the intake openings on the front and, if present, on
the side of the unit. There must be a gap of at least
50 mm here.
♦ External battery units must be placed on the side of the
UPS system. To ensure the greatest possible mechanical
stability, do not place the external battery unit(s) above
or below the UPS system.
♦ Avoid extreme temperatures! We recommend an ambient
temperature from 15°C to 25°C in order to maximize the
service life of the batteries. Do not expose the units to
direct sunlight or operate them close to other heat
sources such as radiators.
♦ Protect the units against external effects (in particular
moisture and dust). In this regard, please also refer to the
instructions in chapter 3, page 16 in these operating
instructions.
If you transport the unit from a cold room into a warm one, or if
the room temperature suddenly drops, then condensation may
form inside the unit. To avoid any damage due to condensation,
let the unit acclimate for 2 hours before you switch it on.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
4.4
Overview: Connections, Operating / Display
Elements
4.4.1
Front view
PROTECT 1.100
PROTECT 1.150
PROTECT 1.200
PROTECT 1.100BP
PROTECT 1.BP20
25
Download from Www.Somanuals.com. All Manuals Search And Download.
4.4.2
Display
12
11
10
9
8
7
3
6
4
5
1
2
1.
2.
3.
4.
5.
6.
OFF pushbutton
ON pushbutton / alarm off
Orange-coloured Bypass LED
Green Inverter LED
Orange-coloured Battery LED
Green Line LED
7 – 11. Bar graph LED (7-10 green, 11 orange-coloured) for
UPS capacity utilisation or remaining battery
capacity
7.
8.
LED load (0-35%)
battery capacity (96-100%)
LED load (36-55%) battery capacity (76-95%)
LED load (56-75%) battery capacity (51-75%)
LED load (76-95%) battery capacity (26-50%)
LED load (96-105%) battery capacity (0-25%)
Red Fault LED
9.
10.
11.
12.
A detailed explanation of the displays is found on page 48ff.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
4.4.3
Rear view (connections):
PROTECT 1.100
8
7
13
11
6
5
11
10
9
4
3
2
1
1.1
1.2
1.3
N
L1 L2 L3 JP1 JP2
L
N
PROTECT 1.150 / 1.200
6
6
13
11
12
11
5
3
7
8
10
4
9
1.1
1.3
1.2
2
1
JP1 JP2
N
L1 L2 L3
+
-
L
N
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Explanations:
1.
Connection terminal cover for mains/UPS input (1.1)
and output (1.3), additional pair of terminals for
setting individual or parallel operation (1.2);
Battery connection terminals
(PROTECT 1.150 / 1.200)
2.
3.
4.
Mains input miniature circuit breaker
Manual bypass switch
Socket for external battery module
(PROTECT 1.100) or connection terminals for
external battery (PROTECT 1.150/1.200)
5.
6.
Connectors for parallel operation
Fan (attention: Leave at least 10 cm clearance
behind fan for unobstructed airflow out!)
7.
Communication slot for optional expansion boards:
SNMP, AS/400, USB
8.
9.
Communication interface RS232 (Sub-D9)
Cable clamping unit (is mounted instead of the
cover from no. 1)
10.
11.
12.
Strain relief clamps
PE/earthing terminals
Macrolon plate as additional insulation to prevent
short circuits when using uninsulated cable lugs
(PROTECT 1.150/1.200)
13.
Cover of the cable clamping unit
28
Download from Www.Somanuals.com. All Manuals Search And Download.
5 Electrical Connection
Caution
Prior to commencing work, ensure that the
connection cables are de-energised and that it is
not possible to activate the power supply.
In order to avoid deformation of the supporting rail
and to protect the base of the connection terminal
against torsional forces, it is advisable to hold the
cable in position when tightening the clamping
screw.
i
The protective measure of earth connection serves to prevent
excessive touch voltage on freely accessible metal parts. The
PROTECT 1. is earthed by the provided earthing bolts (
/
PE). Prior to start-up, it must be ensured that the PROTECT 1.
is earthed in accordance with valid regulations, e.g. VDE 0100.
Before the connection work is carried out, check that:
♦ The values of the nominal voltage (input voltage) and
frequency match those on the nameplate of the UPS.
♦ The earth connection matches the prescribed IEC
standards or the local regulations,
♦ The UPS is connected to the electrical mains via a
separate supply line equipped with fuses on the supply-
side MI distribution.
♦ The power fuse in the MI distribution has the same or
higher value as the one indicated on the nameplate of
the UPS system.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
5.1
Safety of Personnel
Note the following points when setting up the UPS system and
its external battery units (special accessories):
♦ Disconnect the unit from the power supply
♦ Secure the unit against being switched back on
♦ Verify that the unit is disconnected from the power supply
♦ Earth and short-circuit the unit
♦ Provide protection by covers or barriers for any
neighbouring live parts
5.2
Mains Connection (General)
In order to ensure the correct functioning of the UPS and its
additional equipment, it is necessary to equip the mains cable
with the corresponding fuses.
5.2.1
Checklist for Cable Connections
The connection and earthing terminals of all PROTECT 1. units
are structured in a similar way. The cables are connected as
follows:
♦ Remove terminal cover (retain the four screws).
♦ Insert the cables to be connected into the terminal space
of the PROTECT 1. from the rear.
♦ Connect the wires of the supply lines to the
corresponding terminal block. Connect the PE to the
terminal block of the PROTECT 1.100 or to the strain
relief unit of the PROTECT 1.150 or 1.200.
♦ Fasten the supplied cable clamping unit (no. 9, p. 27/28)
with the previously removed screws.
In the case of the PROTECT 1.150 and 1.200, also
remove the lateral earthing bolts beforehand and use
them to fasten the cable clamping unit as well.
♦ Check to ensure that the cables are secured correctly
and tighten the fixing bolts if necessary.
♦ Remove any cable debris, tools, bolts, etc. from the
connection panel.
♦ Mechanically secure the cables with the strain relief
clamps of the cable clamping unit.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
♦ Mount the connection cover of the cable clamping unit.
5.2.2
Connection Cross-Sections and Fuse Protection
The required dimensions can be found in the following table:
PROTECT
1.100
PROTECT
1.150*
PROTECT
1.200*
Max.
current
consumption 46A
68A
91A
(bypass)
Incoming mains cable
(UPS input)
min.
max. 16 mm²
min. 10 mm²
10 mm²
16 mm²
35 mm²
25 mm²
35 mm²
Load connection
(UPS output)
16 mm²
35 mm²
25 mm²
35 mm²
max. 16 mm²
Battery connection
Via
Min. 16 mm², Max. 35 mm²
per terminal
enclosed
battery
connection
cable
protected
against
polarity
reversal
Battery connection cable is
included with the battery unit
Observe earth-fault- and
short-circuit-proof routing!
Mains fuse (UPS input)
50A gl
80A gl
100A gl
When using line safety switches, observe
trigger characteristic: “D”
Load fuse
Line safety switch “B” characteristic
(recommended max.)
16A
20A
25A
* To ensure a reliable strain relief, individual wires must be laid
especially for connecting the 15 and 20 kVA UPS systems.
Recommended connection cable acc. to VDE 0298-4:
Specially for 15 and 20 kVA:
Special rubber-insulated wire
NSGAÖU or NSGAFÖU
or NYY or
Radox 4GKW-AX
e.g. Huber & Suhner
Alternatively, the 10 kVA UPS system can also be connected
via a multi-wire rubber-sheathed cable.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
5.3
Mains Connection
5.3.1
Preparation for the three-phase mains connection
Before connection work is performed on the UPS, make sure
that:
♦ The values of the nominal voltage (supply) and frequency
match those on the nameplate of the UPS.
♦ The earth connection matches the prescribed IEC
standards or the local regulations,
♦ The UPS can be connected to the electrical mains via a
separate supply line equipped with fuses in the supply-
side MI distribution.
♦ Back-up fuses or line safety switches are used that
correspond to the values listed in chapter 5.2.2.
♦ The connection cable from the back-up fuse to the UPS
is configured with a minimum cross-section acc. to
chapter 5.2.2 “Connection Cross-Sections and Fuse
Protection”.
The UPS can be live, and the voltage can be
dangerous. The unit may only be installed and
if necessary opened by trained and qualified
personnel. Repairs may only be carried out by
qualified customer service staff!
5.3.2
Connection of the Three-Phase Input Mains Voltage
In order to ensure the safety of personnel during installation
work, make sure that the connections are made under the
following conditions:
♦ No mains voltage present.
♦ The loads are switched off.
♦ The PROTECT 1. is switched off (display completely
blank).
To disconnect the PROTECT 1, carry out the following steps as
well:
♦ Place the “maintenance switch” manual bypass on the back
of the UPS in the “bypass” position. To do this, first remove
the 4 screws of the cover (no.3, p. 27/28).
32
Download from Www.Somanuals.com. All Manuals Search And Download.
♦ Put the mains input miniature circuit breaker (no.2,
p. 27/28) in the “OFF” position.
Connect the UPS terminal “
/ PE “
(earth)
with
the
corresponding earth terminal in the distribution cabinet.
Connect the supply cable from the MI distribution to the
terminals 1.1 of the UPS that are marked with “INPUT”:
/ PE
N
=
=
Ground
Neutral conductor
Phases
L1/L2/L3 =
Check the jumper between “JP1” and “JP2”
(terminal designation “JUMPER”).
Only remove the cable if you want to use the UPS
in parallel operation with further PROTECT 1. units
of the same type (see also chapter 9).
5.3.3
Preparation of the Output Cabling
Before you connect the loads to the UPS, the nominal output
listed on the nameplate must be greater than or equal to the
sum of the load power outputs.
The output of the PROTECT 1. should supply further separate
circuits in a subdistribution. Make sure that the fuse protection is
selectively designed (see also chapter 5.2.2).
For the connection between the PROTECT 1. and the
subdistribution, cable cross-sections acc. to the table
“Connection Cross-Sections and Fuse Protection” on p. 31
must be used. In the subdistribution, note at least the following
information:
♦ Maximum permissible total load
♦ Maximum permissible load of the individual load circuits
In the case of a common distribution cabinet
(circuits with mains as well as UPS voltage), label
each circuit with the respective supply (mains or
UPS).
i
33
Download from Www.Somanuals.com. All Manuals Search And Download.
5.3.4
Connection of the Loads
In order to ensure the safety of personnel during installation work,
make sure that the connections are made under the following
conditions:
♦ No mains voltage present.
♦ The loads are switched off.
♦ UPS is switched off (display completely blank).
To disconnect the PROTECT 1., carry out the following steps:
♦ Place the “maintenance switch” manual bypass on
the back of the UPS in the “bypass” position. For
this purpose, first remove the 4 screws of the cover
(no. 3, p. 27/28).
♦ Put the mains input miniature circuit breaker (no.2, p.
27/28) to the “OFF” position.
Connect the loads as follows (terminals 1.3, p. 27/28):
Connect the UPS terminals
/PE = ground, N = neutral
conductor, L = phase that are marked with “OUTPUT” with the
corresponding terminals of your UPS subdistribution.
5.4
Connection of External Battery Modules
The PROTECT 1. requires the use of at least one external
battery module. Two preconfigured battery cubicle types are
available. Both versions guarantee an increase in the attainable
standby time due to their parallel connection capability (see
also chapter 2.3).
PROTECT 1.100 PROTECT 1.150
PROTECT 1.200
PROTECT
1.100 BP
ꢀ
-
ꢀ
-
ꢀ
No
mix !
PROTECT
1.BP20
ꢀ
The two cubicle types are distinguished in the following. Follow
5.4.1 if you use the PROTECT 1.100 BP or 5.4.2 when using
the PROTECT 1.BP20.
34
Download from Www.Somanuals.com. All Manuals Search And Download.
5.4.1
Connection of the Battery Cubicle PROTECT 1.100 BP
This battery cubicle is completely preconfigured. The
connection to the UPS unit is ready to be plugged in as a result
of the supplied battery connection cable.
PROTECT 1.100 with 1 battery unit PROTECT 1.100 BP
PROTECT 1.100 BP is only intended for connection
to the UPS type PROTECT 1.100.
i
Connect further battery cubicles of identical design (!) to the
second battery connection socket of the neighbouring battery
cubicle. Insert the battery connection plugs quickly and firmly
into the battery connectors.
35
Download from Www.Somanuals.com. All Manuals Search And Download.
5.4.2
Connection of the Battery Cubicle PROTECT 1. BP20
Fig.: Rear view of the PROTECT 1.BP20 with cover removed.
The battery cubicle is supplied with a separate battery string
and separately enclosed battery fuses for safety and transport
protection reasons. Please also note the separate
documentation enclosed with the battery cubicle.
After the battery cubicle has been removed from the pallet, first
remove the rear cover. Now create the electrical connections
with the enclosed connectors (see also circuit diagram
X1/X2/X3) and
The PROTECT 1.100 is connected to the UPS at the socket ꢁ
using the special battery connection cable enclosed with the
UPS, and in the case of the PROTECT 1.150 or
PROTECT 1.200 with the battery connection cables enclosed
with the battery cubicle at the terminals . Make sure to
observe the terminal block assignment concerning the correct
polarity "+" and "-" as well as an earth-fault- and short-circuit-
proof routing, in addition to the proper earthing of the battery
cubicle.
36
Download from Www.Somanuals.com. All Manuals Search And Download.
If the battery cubicle is used in connection with the
PROTECT 1.1.50 or PROTECT 1.200, the strain relief is
implemented with clamps.
The battery system can now be activated. To do this, insert the
two fuses .
As the last step, fasten each cover that was initially removed.
Fig.: PROTECT 1.BP20 in connection with the PROTECT 1.100
PROTECT 1.100 & 1.BP20: When connecting the
battery connection cable, make sure that the plugs
are inserted quickly and firmly in the battery
connectors.
i
Prepare further PROTECT 1.BP20 battery cubicles as
described above and then connect them to the terminals (X2
and X3) of the previously installed battery cubicle with the
enclosed battery connection cables. Observe the correct
polarity "+" and "-" as well as an earth-fault- and short-circuit-
proof routing during connection.
5.5
Mechanical Blocking of PROTECT 1.
After completing the connection work, fasten the connection
terminal cover again. At the final installation site, block the
cubicles against slipping.
37
Download from Www.Somanuals.com. All Manuals Search And Download.
6 Start-Up
Compare the setting of the nominal output voltage of the UPS
with the rated voltage valid in your country. The factory
presetting is 230 V. Changes to 220 VAC or 240 VAC can be
made with the software “CompuWatch”.
Switching on the PROTECT 1. on the mains
14.
Make sure that all connections have been made
according to the installation instructions.
15.
16.
Make sure that all loads are switched off.
Put the “maintenance switch” manual bypass switch
(no. 3, p. 27/28) on the back of the UPS back to the
“USV“ position. Next fasten the cover again with the
4 previously removed screws.
17.
18.
Now insert the back-up fuse in your low-voltage main
distribution (where the UPS system is connected to the
mains on the input side) or switch on the
corresponding line protection switch there.
Next actuate the mains input miniature circuit
breakers on the UPS (no. 2, p. 27/28). Move this to
the "ON" position.
Factory presetting: The loads are supplied via
the integrated bypass, which connects the phase
L1 with the UPS output. Do not switch on your
loads yet, however.
i
19.
20.
Now switch on the inverter of the UPS. To do this,
press the ON pushbutton for approx. 2 seconds.
After switching on, the UPS carries out a self-test,
during which the LED’s for load and battery state
go on and off consecutively in increasing order.
After the successful synchronization of the inverter,
the Inverter LED lights up a few seconds later,
whereby the UPS is now in normal operating mode.
When the mains supply is intact (mains within
tolerance), the "Line" LED also lights up.
38
Download from Www.Somanuals.com. All Manuals Search And Download.
Please shut down the entire system again if you
cannot solve a problem that occurs. To do this,
press the OFF pushbutton for approx. 2 seconds.
Disconnect the UPS from the mains by actuating
the mains input miniature circuit breaker (no. 2,
p. 27/28). Please contact our hotline (see p. 5).
i
21.
When the displays are correctly lit as described,
switch on your loads one after the other. When
doing this, take care not to exceed the maximum
permitted load capacity of the UPS.
6.1
Operating Modes
The following operating modes are distinguished:
Operation with mains supply (6.1.1)
Operation with faulty mains supply (6.1.2)
Operation with faulty inverter (6.1.3)
Manual bypass (6.1.4)
6.1.1
Normal Operation
Energiefluss bei
vorhandenem Netz
Handumgehungspfad
GR
WR
EUE
Netz
Netzeingangs-
sicherungs-
automat
Hand-
umgehung
Gesicherte
Schiene:
Lade GR
Batterie
Schematische
Darstellung
Verbraucher
Energiefluss bei vorhandenem Netz
Power circuit with mains supply
Handumgehungspfad
Manual bypass path
Netz
Mains
GR
REC
EUE
SBS
WR
INV
Netzeingangssicherungsautomat
Schematische Darstellung
Lade GR
Mains input miniature circuit breaker
Schematic diagram
Load REC
Batterie
Battery
Handumgehung
Gesicherte Schiene
Verbraucher
Manual bypass
Secured busbar
Load
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Once you have connected the UPS to a suitable mains
connection, you can start operation using the UPS main switch.
Normally, the UPS operates continuously. The UPS now
supplies the output with voltage, which is signalled by the mains
symbol (Line LED) and the inverter symbol (Inverter LED) being
lit.
This operating mode, generally referred to as “online” mode,
ensures the greatest protection, in particular when there are
mains fluctuations and mains failures, because the loads are
continuously supplied with reliable and “clean” voltage with no
interruptions in this operating mode.
The bar graph LED (LED chain above the pictograph) indicates
the current capacity utilisation of the UPS in this operating
mode (see chapter 8, p. 48 ff).
6.1.2
Battery Operation / Autonomous Operation
Energiefluss bei
gestörtem Netz
Handumgehungspfad
GR
WR
EUE
Netz
Netzeingangs-
sicherungs-
automat
Hand-
umgehung
Gesicherte
Schiene:
Lade GR
Batterie
Schematische
Darstellung
Verbraucher
40
Download from Www.Somanuals.com. All Manuals Search And Download.
Energiefluss bei gestörtem Netz
Power circuit with faulty mains supply
Handumgehungspfad
Manual bypass path
Netz
Mains
GR
REC
EUE
SBS
WR
INV
Netzeingangssicherungsautomat
Lade GR
Mains input miniature circuit breaker
Load REC
Handumgehung
Gesicherte Schiene
Schematische Darstellung
Batterie
Manual bypass
Secured busbar
Schematic diagram
Battery
Verbraucher
Load
The mains is not within the required tolerance range or has
failed. In this case, power is supplied to the inverter from the
charged battery without interruption. The power supply to the
loads is therefore also ensured in the event of a mains failure.
This drains the capacity of the battery and it is discharged. This
status is signalled by the battery symbol lighting up (Battery
LED), as well as an intermittent acoustic signal, at first every 4
seconds and then every second shortly before switching off.
The initial alarm can be suppressed by pressing the “Alarm off”
button. The alarm is automatically reactivated when the battery
capacity decreases. Depending on the expansion level, age
and condition of the battery and in particular on the load to be
supplied, the standby time can vary from a few minutes to
several hours.
The inverter is switched off if the battery voltage drops below a
factory-set minimum voltage value.
Never store the unit in this condition! The discharged battery
system should be recharged within a week at the latest.
When the voltage and frequency are within the tolerance range
again after the mains is restored, the rectifiers switch back on
41
Download from Www.Somanuals.com. All Manuals Search And Download.
automatically. The supply of the inverter through the mains is
resumed and the battery charger charges the battery.
The bar graph LED (LED chain above the pictograph) indicates
the remaining battery capacity during this operating mode (see
chapter 8, p. 48 ff).
6.1.3
Bypass Operation
Energiefluss bei
gestörtem WR
Handumgehungspfad
GR
WR
EUE
Netz
Netzeingangs-
sicherungs-
automat
Hand-
umgehung
Gesicherte
Schiene:
Lade GR
Batterie
Schematische
Darstellung
Verbraucher
Energiefluss bei gestörtem WR
Power circuit with faulty INV
Handumgehungspfad
Manual bypass path
Netz
Mains
GR
REC
EUE
SBS
WR
INV
Netzeingangssicherungsautomat
Lade GR
Mains input miniature circuit breaker
Load REC
Handumgehung
Gesicherte Schiene
Schematische Darstellung
Batterie
Manual bypass
Secured busbar
Schematic diagram
Battery
Verbraucher
Load
If the inverter is overloaded or if overtemperature is detected,
e.g. also if an inverter defect is detected, voltage is supplied to
the load without interruption via the static bypass switch (SBS)
that switches on automatically. This is signalled by the Bypass
LED.
42
Download from Www.Somanuals.com. All Manuals Search And Download.
Bypass
Line
Inverter
Battery
This so-called passive redundancy protects against the total
failure of the voltage supply on the secured busbar; however, in
this operating mode, mains faults would directly affect the load.
As a result, the electronics continuously attempt to switch back
to "online" / normal operating mode (e.g. when the overload or
overtemperature goes away).
The bypass consists of an inverse-parallel thyristor stack and
functions as an extremely rapidly switching link between a load
and the mains. The synchronization unit ensures that the
frequency and phase of the inverter voltage is synchronized
with the mains and can therefore be switched over without
interruption (within the tolerance limits).
The bar graph LED functions as the display of
the UPS capacity utilisation. The acoustic signal
sounds every 2 seconds during this operating
mode.
i
43
Download from Www.Somanuals.com. All Manuals Search And Download.
6.1.4
Manual Bypass
Energiefluss bei aktivierter Handumgehung
Power circuit with activated manual bypass
Handumgehungspfad
Manual bypass path
Netz
Mains
GR
REC
EUE
SBS
WR
INV
Netzeingangssicherungsautomat
Lade GR
Mains input miniature circuit breaker
Load REC
Handumgehung
Gesicherte Schiene
Schematische Darstellung
Batterie
Manual bypass
Secured busbar
Schematic diagram
Battery
Verbraucher
Load
The manual bypass enables maintenance and service
personnel to perform work on the PROTECT 1. without having
to switch off the load circuit.
If the current supply fails while the manual
bypass is active, a total failure of the load supply
results. For this reason, it should be switched
back to normal operating mode as soon as
possible.
44
Download from Www.Somanuals.com. All Manuals Search And Download.
6.1.5
Unit overload
The load on the UPS should never exceed the specified rated load
of the unit. If a unit overload occurs nevertheless (from 105% of
the specified unit rated load) then the Fault LED lights up and an
acoustic signal sounds (twice per second). The connected loads
continue to be supplied for a certain length of time depending on
the level of the overload. However, the connected load must be
reduced without delay.
Non-observance of the "unit overload" condition may cause the
total loss of all UPS functions!
Also avoid short-term unit overloads, which may, for example,
occur when connecting a laser printer or laser fax machine. Do
not connect any household appliances or machine tools to the
UPS.
Never connect or switch on any additional loads
to the UPS if there is a mains failure, i.e. if the
UPS is working in emergency power mode!
As a rule, if there has never been an overload during normal
mode, there will not be one in battery mode either.
When the Fault LED lights up in connection with
a continuous acoustic signal, this is an indication
of a deactivating fault. Follow the instructions in
chapter 0.
45
Download from Www.Somanuals.com. All Manuals Search And Download.
7 Interfaces and Communication
7.1
Computer Interface RS232
For the control of the UPS and convenient reading of status
messages and measured values, various interfaces are
available. The interface protocol is designed for operation with
the "CompuWatch" shutdown and UPS management software
from AEG. Use the supplied RS232 communication cable to
connect your PC. Plug the cable into a corresponding serial port
on your PC.
RS232 interface: The RS232 is connected via the 9-pin Sub-D
socket strip on the back of the unit (no. 8, p. 27/28). Pin
assignment: 2 = TxD; 3 = RxD; 5 = GND.
7.2
Communication Slot
On the back of the UPS, there is a cover (see p. 27/2828, no.
7). When this is removed, additional, optionally available
communication components can be installed there, e.g.:
AS/400 board: Slot board with status messages, realised via
potential-free relay contacts
USB board: Slot board for communication via USB
SNMP board: Slot board for direct connection of the UPS to
the Ethernet network with RJ 45 (TCP/IP)
Details can be found in the description enclosed with the
particular optional component. Other boards in preparation.
Using the communication slot deactivates the
RS232 interface from chapter 7.1.
i
7.3
Shutdown and UPS Management Software
The "CompuWatch" software specially developed for these
purposes by AEG continuously checks the mains supply and
the UPS status.
In conjunction with the “intelligent” UPS, this guarantees the
availability of the EDP components as well as the data security.
46
Download from Www.Somanuals.com. All Manuals Search And Download.
The "CompuWatch" shutdown software supports different
operating systems, e.g. Windows 98SE/ME, Windows
NT/2000/XP, Windows Vista, Linux SUSE, Linux RedHat,
Novell Netware, IBM AIX, HP-UX, SUN Solaris, Mac OS, and
others.
Example of a “CompuWatch” screen
Refer to the manual on the CD for details about installing the
software
on
the
various
operating
systems.
47
Download from Www.Somanuals.com. All Manuals Search And Download.
8 Displays and Troubleshooting
8.1.1
Signalling
22.
23.
OFF pushbutton Press the button for approx.
2 seconds to switch off the UPS.
ON button: Press the button for approx. 2 seconds
to switch the UPS on.
Deactivate acoustic alarm: Press the button during
the alarm for approx. 2 seconds to switch off the
alarm.
UPS test: Press this button during normal mode for
approx. 2 seconds to carry out a UPS self-test.
24.
25.
26.
Bypass LED: The orange-coloured LED lights up
when voltage is supplied via the integrated bypass
of the UPS.
Inverter LED: The green LED lights up when
voltage is supplied via the inverter of the UPS
system.
Battery LED: The orange-coloured LED lights up
when power is supplied from the battery system.
48
Download from Www.Somanuals.com. All Manuals Search And Download.
27.
Line LED (mains status): The green LED lights up
when the mains voltage present is within the
specified tolerance range. If this LED flashes, either
the UPS connection has an incorrect pin assignment
(observe phase sequence / neutral conductor
connection position) or the mains is outside of the
specified tolerance range.
28. to 11. Bar graph LED as the measure of the UPS
capacity utilisation or the remaining battery capacity.
These LED’s show the current UPS capacity
utilisation when mains voltage is present (normal
mode):
11. Orange LED
10. Green LED
9. Green LED
8. Green LED
7. Green LED
96% – 105%
76% – 95%
56% – 75%
36% – 55%
0% – 35%
In battery mode, the LED’s indicate the capacity of
the batteries:
11. Orange LED
10. Green LED
9. Green LED
8. Green LED
7. Green LED
0% – 25%
26% – 50%
51% – 75%
76% – 95%
96% – 100%
12.
Fault LED: The red LED lights up with an acoustic
warning signal when a fault is present in the UPS
system.
49
Download from Www.Somanuals.com. All Manuals Search And Download.
8.1.2
Overview Table of LED Displays / Acoustic Warning Signals
LED display (see chapter 8 on page 47)
Warning
No. Operating mode
signal
0% – 35%
utilisation
1
2
none
none
none
none
none
36% – 55%
utilisation
56% – 75%
utilisation
3
76% – 95%
utilisation
4
96% – 105%
utilisation
5
0% – 20%
capacity
1 acoustic
signal per sec.
6
21% – 40%
capacity
1 acoustic signal
every 4 seconds
7
41% – 60%
capacity
1 acoustic signal
every 4 seconds
8
61% – 80%
capacity
1 acoustic signal
every 4 seconds
9
81% – 100%
capacity
1 acoustic signal
every 4 seconds
10
11
12
13
14
15
16
17
18
Load supply via
bypass of the UPS
1 acoustic signal
every 2 minutes
Unit overload UPS in
INV mode
2 acoustic
signals per sec.
Unit overload UPS
in bypass mode
2 acoustic
signals per sec.
Mains abnormal
Overload in battery
mode, early warning
2 acoustic
signals per sec.
Overload in battery
mode, switch-off
Continuous
warning signal
Overtemperature fault
Inverter fault
Continuous
warning signal
Continuous
warning signal
Note:
= LED lights up
= LED flashes
= Display / acoustic signal state undetermined;
unimportant for displayed operating mode
50
Download from Www.Somanuals.com. All Manuals Search And Download.
Overview table of LED displays / warning signals, cont.
LED display (see chapter 8 on page 47)
Warning
signal
No. Operating mode
Short-circuit output
side
Continuous
warning signal
19
BUS voltage
20
Continuous
warning signal
abnormal
DC circuit faulty;
21
1 acoustic
signal per sec.
poss. battery fault
Battery
faulty
charger
Continuous
warning signal
22
23
24
25
26
1 acoustic
signal per sec.
Fan fault
Fault in inverter
output relay
Continuous
warning signal
Communication
faulty
Continuous
warning signal
Parallel
fault
operation
Continuous
warning signal
Note:
= LED lights up
= LED flashes
= Display / acoustic signal state undetermined;
unimportant for displayed operating mode
51
Download from Www.Somanuals.com. All Manuals Search And Download.
8.2
Faults
PROTECT 1. outputs detailed error messages by means of
which you or the service personnel can quickly and accurately
localise and interpret any malfunctions that occur. You can find
suggestions for action / solutions in the following to correct
problems using error descriptions according to chapter 8.1.2:
8.2.1
Error Messages
Message / display
Cause
Solution
No display, no acoustic
signal although system
is connected to the
Mains and/or
Check mains connection
again. Check the back-
up fuse and the mains
input miniature circuit
breaker as well.
battery voltage not
in tolerance range,
poss. totally
mains current supply.
discharged battery.
Mains OK, but UPS
does not switch to
bypass
PositionMains input Switch mains input
use is in “OFF”
position
miniature circuit breaker
to “ON”
“Line” LED flashes and
“Battery” LED lights up
Mains voltage
and/or mains
Check the mains
(voltage, frequency)
frequency are
outside of tolerance
“Inverter" LED and
"Battery" LED light up.
The acoustic signal
sounds every 4 seconds
(operating states 7-10).
Mains voltage
supply interrupted.
Automatic
switchover to
battery mode.
Try to re-establish the
mains voltage (poss.
fuse triggered in the
subdistribution?).When
the acoustic signal
sounds every second,
the battery is almost
completely discharged.
Carry out a system
shutdown of your IT
equipment at this point
in time at the latest.
“Inverter"
"Battery" LED light up.
The acoustic signal
sounds every second
(operating state no.6).
LED
and
“Fault” LED lights up,
warning signal sounds
twice per second (error
descriptions no. 12/13).
Overload of the
UPS System.
Immediately reduce the
capacity utilisation of the
UPS by disconnecting
part of your loads.
52
Download from Www.Somanuals.com. All Manuals Search And Download.
Message / display
Cause
Solution
Duration of the
emergency power
supply shorter than
setpoint.
Batteries not
completely charged at least the recharging
/ batteries aged or
faulty.
Charge the batteries for
time acc. to chapter 2.3,
and check their capacity.
If the problem remains,
contact your dealer.
“Line” LED and “Fault”
LED light up, continuous
warning signal (error
description no. 17).
Switch-off due to
UPS internal
overtemperature
detection
Make sure that no
overload is present, the
UPS fans are not
blocked and the ambient
temperature is in the
tolerance range. Wait for
10 min. cooling down
phase, then switch on
again.
Error description no. 19
Switch-off due to
short-circuit in UPS
output
Correct short-circuit.
Switch UPS on again,
connect loads one after
the other again.
“Fault” LED lights up,
“Battery” LED flashes,
warning signal sounds
once per second (error
description 21).
Fault in DC circuit
or battery system
faulty.
Notify dealer!
“Fault” LED lights up,
continuous warning
signal.
Fault in the UPS.
Notify dealer!
Further diagnoses can also be found in the table list in
chapter 8.1.2.
If you cannot solve the problem that has occurred, stop the
entire procedure, switch off the UPS and disconnect the UPS
from the mains. Please contact our hotline in this case
(see p. 5).
Please have the serial number of the unit as well as the
purchase date at hand. The hotline will provide you with
technical support and can inform you about further procedures
once you have described the problem.
53
Download from Www.Somanuals.com. All Manuals Search And Download.
9 Parallel Operation
9.1
Principle of Operation
PROTECT 1. has been designed for parallel operation with n+x
technology (“n” here stands for the number of units required for
load supply, “x” for the degree of redundancy). Up to 3 units of
the same type can be connected in parallel here to increase the
output power and/or achieve higher availability.
NS Hauptverteilung
USV Einspeisung
MI main distribution
UPS feed
Parallelfeld
Unterverteilung
/
Handumgehung plus USV
Parallel field / manual bypass plus UPS
subdistribution
54
Download from Www.Somanuals.com. All Manuals Search And Download.
This results in the following constellations with n+x technology:
1 + 0 Use of 1 unit
1 + 1 Use of 2 units
1 + 2 Use of 3 units
2 + 0 Use of 2 units
2 + 1 Use of 3 units
3 + 0 Use of 3 units
max. 10, 15 or
20 kVA
No redundancy
max. 10, 15 or
20 kVA
Single redundancy
max. 10, 15 or
20 kVA
Double redundancy
(max. expansion level)
max. 20, 30 or
40 kVA
No redundancy
max. 20, 30 or
40 kVA
Single redundancy
(max. expansion level)
max. 20, 30 or
40 kVA
No redundancy (max.
expansion level)
The actively redundant parallel operation automatically switches
to power-increasing operation if the output power requirement
exceeds the UPS single block power, i.e. the degree of
redundancy is decreased or is completely eliminated.
Conversely, the active UPS redundancy degree automatically
increases again when the power consumption decreases.
The connection normally takes place in the low-voltage main
distribution, which also contains the external manual bypass
and the following subdistribution of connected load circuits.
Such a parallel board can be purchased in a wall housing incl.
external HU as well as feeder and load distribution board from
AEG Power Supply Systems via your specialist dealer.
9.2
Set-up / Connection of Parallel Operation Board
The mains connection of each individual UPS takes place in the
same way as described in chapter 5.
The three-phase mains connection secured for
each UPS must always have the same phase
sequence, i.e. all UPS units are supplied at the
input terminals L1, L2 and L3 by the same
phase each time (no mix!).
In UPS bypass mode, the phase L1 is used to
connect the single-phase load with the mains.
The central external manual bypass, which must
have an all-pole design, must also be supplied
by this phase L1.
55
Download from Www.Somanuals.com. All Manuals Search And Download.
The UPS outputs are each connected with the parallel
operation busbar via an isolator. The instructions from
chapter 5 apply here too.
The following always holds true for the UPS input and output
conductors: The difference in length in conductors up to 20 m
per UPS can be max. 20% and max. 10% for lengths > 20 m
per UPS.
The jumper installed between “JP1” and “JP2” on the
connection panel of every UPS at the factory must be removed.
The UPS output distribution also has to take place according to
the instructions in chapter 5. In particular, make sure that the
individual switching elements are correctly labelled, in order to
prevent operating errors later as well. The communication of
the units switched in parallel takes place via the 25-pin parallel
operation cable(s) included in the scope of delivery.
For this purpose, first remove the parallel port covers
(no. 5, p. 27/28) and connect the UPS units with each other with
one parallel operation cable each. Use one parallel operation
cable for 2 units and two parallel operation cables for 3 units (do
not create a ring structure!).
(Communicative) parallel operating connection
... for 2 units:
... for 3 units:
After connecting the parallel operation cables, fasten the
previously removed parallel port covers. Turn these by 180° so
that the slot of the cover is facing downwards.
The hardware-related installation is now complete.
56
Download from Www.Somanuals.com. All Manuals Search And Download.
9.3
Operation of the UPS in a parallel system
The start-up process is uncomplicated, does not require any
prior knowledge and is basically oriented to the procedure
described in chapter 6. If you have obtained the parallel
operation board from AEG Power Supply Systems, you can find
further special instructions there. The displays in the parallel
system function the same way as described for the individual
UPS units in chapter 8.
9.3.1
Start-Up
13.
Make sure that all connections have been made
according to the installation instructions.
14.
15.
Make sure that all loads are switched off.
Make sure that all “maintenance switch” manual
bypass switches (no. 3, p. 27/28) on the back of
each UPS are in the “Bypass” position and all mains
input miniature circuit breakers (no. 2, p. 27/28) on
the back of each UPS are in the “OFF” position.
16.
17.
18.
Check the position of the central external manual
bypass. This must be in the “Bypass” position, i.e.
supply of the load busbar by the supplying mains.
Now close all isolators in the output of each UPS,
i.e. connect the output of each UPS with the parallel
operation busbar.
Now insert the back-up fuses in your low-voltage main
distribution (where the central external manual bypass
as well as the individual UPS systems are connected
to the mains on the input side) or switch on the
corresponding line protection switches there.
The load supply now takes place via the central
external manual bypass, and the parallel
operation busbar is supplied with power via the
integrated manual bypasses of each UPS.
However, the parallel operation busbar and load
busbar are not yet connected to each other at
this time!
i
57
Download from Www.Somanuals.com. All Manuals Search And Download.
19.
20.
Now actuate the mains input miniature circuit breakers
(no. 2, p. 27/28) on each UPS one after the other. Move
them to the "ON" position.
Move the “maintenance switch” manual bypass
switches (no. 3, p. 27/28) on the back of each UPS
to the “UPS” position. Finally, fasten the covers on
each UPS again using the 4 respective screws that
were previously removed.
The voltage supply of the parallel operation
busbar now takes place via the integrated
electronic bypass switches of the UPS systems
used. Check this operating state on the display
panel of each UPS = Bypass (chapter 6.1.3).
i
21.
Now actuate your central external manual bypass:
Switch from the “Bypass” position to “UPS operation”,
i.e. connect your load busbar to the UPS parallel
operation busbar.
This is done using a manual bypass switch with
overlapping switching contacts without any
interruption in the load voltage, i.e. completely
interruption-free.
i
22.
Now switch on the inverters of the UPS systems. To
do this, press the ON pushbutton of each UPS for
approx. 2 seconds one after the other.
After switching on, each UPS carries out a self-
test and synchronizes itself with the parallel
operation busbar, while the LED’s for load and
battery state switch on and off consecutively in
i
increasing
order.
After
the
successful
synchronization of all inverters, the Inverter LED
on each UPS lights up a few seconds later,
whereby the UPS systems now work in parallel
normal operating mode and supply the parallel
operation / load busbar with UPS voltage.
The central external manual bypass switch must
be protected against accidental actuation. Never
actuate it when the UPS systems are in inverter
mode.
58
Download from Www.Somanuals.com. All Manuals Search And Download.
23.
When the displays are lit as described, switch on
your loads one after the other. When doing this, take
care not to exceed the maximum permitted load
capacity of the UPS systems. Also take into account
the reserve capacities if active redundancy should
be required.
9.3.2
Changes to the parallel system
If you would like to add a UPS to the parallel system or remove
a UPS from the parallel system, this step is always done by
returning the UPS systems to BYPASS operating mode.
Load supply through mains operation!
(No UPS protection during this measure).
i
First, switch off the inverters of the UPS systems one after the
other (actuate the “OFF” pushbuttons). All UPS systems
function in SBS/bypass operation. Check the operating state on
the operating panels. Next, active the integrated manual
bypasses (no. 3, p. 27/28) on the back of each UPS. To do this,
first remove the 4 screws of the covers on the back.
Put the mains input miniature circuit breakers of each UPS (no. 2,
p. 27/28) to “OFF” position. Use your central external manual
bypass to bypass the loads, i.e. activate the bypass operation and
remove the load supply from the UPS busbar.
The voltage of each UPS is disconnected in its low-voltage
main distribution. You can now expand or reduce your parallel
system. Pay attention to the jumpers “JP1” / “JP2” and the
parallel operation cables. The subsequent start-up is carried out
as described in chapter 9.3.1.
If you only want to switch off a UPS in the
parallel system, press the “OFF” pushbutton
twice in succession to do this. In this way,
individual UPS systems can be disconnected
from the parallel operation busbar.
i
59
Download from Www.Somanuals.com. All Manuals Search And Download.
10 Maintenance
The PROTECT 1. consists of state-of-the-art, non-wearing
components. We do, however, recommend visual checks
(above all battery and fan checks) at regular intervals (at least
every 6 months) to maintain continuous availability and
operational reliability.
CAUTION!
Ensure that the work area is cordoned off and
always observe the safety instructions!
10.1
Charging the Battery
The battery is automatically charged when the mains is
connected, irrespective of the operating mode. This is signalled
by the Load LED’s lighting up (see also chapter 4.4.2).
The complete charging time of the battery after a long
discharge time depends especially on the number of additional
external battery units (see chapter 2.3).
10.2
Checks
The following maintenance work should be performed:
Task
Interval
Described in
Chapter 10.2.1
Chapter 0 / 0
Visual check
Battery/fan check
6 months
6 months
10.2.1 Visual Check
When visually inspecting the unit, check whether …
♦ there is any mechanical damage or foreign bodies can be
found in the system,
♦ any conductive dirt or dust has accumulated in the unit,
♦ accumulation of dust affects heat supply and dissipation.
60
Download from Www.Somanuals.com. All Manuals Search And Download.
CAUTION!
PROTECT 1. must be disconnected from the
power supply prior to carrying out the following
work.
If large quantities of dust have accumulated, the unit should, as
a precaution, be cleaned with dry compressed air, in order to
ensure adequate heat dissipation.
The intervals at which visual checks should be performed are
largely determined by the site conditions.
10.2.2 Checking the Battery
Progressive ageing of the battery system can be detected by
regular capacity checks. Every months, perform
6
measurements to compare the achievable standby times, e.g.
by simulating a mains failure. In this case, the load should
always have approximately the same capacity demand. Please
contact our hotline if the time drops drastically compared to the
previous measurement (see p. 5).
10.2.3 Fan Check
Regularly check the fans for dust build-up and noticeably
untypical noise development. Blocked intake openings must be
cleaned. In the case of unusually loud or uneven running,
please contact our hotline (see p. 5).
61
Download from Www.Somanuals.com. All Manuals Search And Download.
11 Storage, Dismantling and Disposal
11.1
Storage
Long storage times without charging or
discharging the battery at regular intervals may
lead to permanent damage of the battery.
If the battery is stored at room temperature (20 C to 30 C), it will
automatically discharge at a rate of 3-6% per month due to
internal reactions. Storing the battery at temperatures above
room temperature should be avoided.
A
high storage
temperature also means greater battery self-discharge.
Batteries that are stored at room temperature should be
recharged every six months to maintain their full capacity and
service life.
Connect PROTECT 1. to the mains before
putting it into storage, in order to make sure that
the battery is fully charged. The charging time
should at least match the time specified in
chapter 10.1.
i
11.2
11.3
Dismantling
The system is dismantled in reverse order of the installation
instructions.
Disposal
In the interest of environmental protection and recycling, please
dispose of the individual system components in accordance
with the regulations and legal guidelines when permanently
taking the system out of operation. Please consider that
infringements to these regulations may result in prosecution.
62
Download from Www.Somanuals.com. All Manuals Search And Download.
12 List of Terms
12.1
Technical terminology
DC/DC booster
Circuit technology for increasing a DC voltage to a
higher voltage level
SBS
Static Bypass Switch
Appliance protection
Term from overvoltage technology
Classic mains overvoltage protection consists of a
lightning surge arrester (class B), overvoltage protection
(class C) and, finally, the so-called appliance protection
(“TRABTECH” topic)
IGBT
Insulated Gate Bipolar Transistor
The latest design of high-performance transistors with
minimum control power requirement (MOSFET
structure) and minimum losses on the output side
(structure of a bipolar transistor)
Class D
LED
See appliance protection
Light Emitting Diode
Electronic semi-conductor component, commonly
referred to as an LED, used for optic signalling.
PFC
Power Factor Correction
Circuit technology for minimising system disturbances
(particularly important when connecting non-linear
loads)
PWM
Pulse Width Modulation
Here: circuit technology for generating a sinusoidal
voltage of the highest quality from an existing DC
voltage
SNMP
VFD
Simple Network Management Protocol
A protocol encountered frequently in networks for
managing handling components
/
Output Voltage and Frequency Dependent on mains
supply. The UPS output is dependent on mains voltage
and frequency fluctuations. Earlier designation:
OFFLINE
VI
Output Voltage Independent from mains supply
The UPS output is dependent on mains frequency
fluctuations, but the mains voltage is prepared by
electronic / passive voltage control units. Earlier
designation: LINE-INTERACTIVE
VFI
Output Voltage and Frequency Independent from mains
supply. The UPS output is independent of mains voltage
and frequency fluctuations. Earlier designation: ONLINE
63
Download from Www.Somanuals.com. All Manuals Search And Download.
Guarantee Certificate
Type: …….……………….…......................................................
Unit number: ………….…..……………...............................:::::::
Date of purchase: ……………………...........…………………….
Dealer stamp / signature
Errors and changes excepted.
AEG Power Supply Systems GmbH
Emil-Siepmann-Straße 32
D-59581 Warstein-Belecke
Germany
Operating Instructions
BAL 8000019452 EN
AEG0707DE
Download from Www.Somanuals.com. All Manuals Search And Download.
|