Contents
■
■
■
■
■
■
Terminal Number Plan
3-4
■
Y-Cable to the SID
4-8
■
5
Installing SID Software on the
iv Issue 2 December 1995
Contents
6-1
■
■
■
Interface Link
7-13
■
■
■
■
■
Issue 2 December 1995
v
Contents
■
■
■
vi Issue 2 December 1995
Contents
Message Retrieval in Lodging Systems
without AUDIX
C-2
C-2
AUDIX
■
■
Issue 2 December 1995 vii
Contents
viii Issue 2 December 1995
About This Document
INTUITY™ Integration with NEC® NEAX™ 2400 Switch contains installation and
administration instructions for integrating a NEAX 2400 MCI switch with an
INTUITY system. The document contains instructions or information on the
following topics.
■
■
■
■
■
■
■
Switch integration planning strategies
Switch Integration Device (SID) hardware installation instructions
Software installation instructions
NEAX 2400 administration instructions
Acceptance test procedures
Cut-to-Service procedures
SID troubleshooting guide
The document contains information only for the NEAX switch integration with the
INTUITY system. If you have another type of switch, refer to the switch integration
document for that switch.
Issue 2 December 1995 xi
About This Document
Intended Audiences
This document is designed primarily for the on-site AT&T-certified services
technician, the customer’s technical personnel, and the customer’s NEAX
services technician. Use the document to install INTUITY system
integration-required hardware and software, perform acceptance tests, and
perform cut-to-service. The customer or the customers’ switch vendor should use
the document when performing switch administration tasks and other customer
required tasks.
Secondary audiences include the AT&T personnel shown in the following list.
■
■
■
■
■
■
Field support
The Technical Service Center (TSC)
Provisioning project managers
The Sales and Technical Resource Center (STRC)
Helpline personnel
Factory assemble, load, and test (ALT) personnel
Prerequisite Skills or Knowledge
Typical readers should understand AT&T computer systems, switches, and
hardware and software installation procedures. AT&T provides and recommends
INTUITY system training for customers. Customers should be familiar with the
NEAX switch or contact their switch vendor.
Document Organization
■
■
INTUITY configuration and includes a component connectivity diagram
that shows you each component in the configuration. The chapter also
contains a hardware and software component checklist.
components of the SID and how to use the system forms or screens. The
chapter contains SID hardware component descriptions and illustrations,
menu, edit, and action form explanations, and provides basic help
functions.
■
the switch integration. The chapter includes instructions for completing
SID and switch integration worksheets that you use throughout the
document as you complete the integration.
xii Issue 2 December 1995
About This Document
■
cables to the switch, and cables to the INTUITY system. This chapter only
contains information for installing the hardware components required for
the integration.
■
■
instructions for installing the INTUITY system software required to
integrate with the NEAX 2400 switch.
contains instructions for administering an INTUITY system to integrate with
the switch. The chapter includes instructions for setting the message
waiting lamp parameters, setting the switch interface parameters, and
associating the application and the switch interface.
■
■
■
■
Chapter 7, "NEAX 2400 Switch Administration", contains information and
instructions for administering a NEAX 2400 MCI switch to work with an
INTUITY system.
Chapter 8, "Switch Integration Device Administration", contains information
and instructions for administering the SID to work with the INTUITY
system.
administration you must perform before you can continue with the
acceptance tests.
administration you must perform before you can continue with
cut-to-service.
■
■
■
information to help you isolate and correct integration problems.
the SID real-time views of the integration process.
Appendix C, "Switch Administration for INTUITY Lodging", provides switch
administration procedures if you have INTUITY Lodging.
The document also includes a list of common abbreviations, a glossary, and an
index.
Issue 2 December 1995 xiii
About This Document
How to Use this Document
This document provides additional information you need to know when
integrating a NEAX switch with an INTUITY system. Use this document as
additional information with the following documents:
■
■
■
■
INTUITY MAP/5 Hardware Installation, 585-310-146
INTUITY MAP/40 Hardware Installation, 585-310-138
INTUITY MAP/100 Hardware Installation, 585-310-139
INTUITY Software Installation, 585-310-140
Do not perform any tasks in this document until you complete the required tasks
in the installation documents.
Conventions Used
The following conventions were used in this book:
■
Rounded boxes represent keyboard keys that you press.
For example, an instruction to press the enter key is shown as follows:
ENTER
Press
.
■
Square boxes represent phone pad keys that you press.
For example, an instruction to press zero on the phone pad is shown as
follows:
0
Press
.
ENTER
■
The word “enter” means to type a value and press
.
ENTER
For example, an instruction to type y and press
Enter y to continue.
is shown as follows:
■
■
Commands and text you type or enter appear in bold.
Values, instructions, and prompts that you see on the screen are shown as
follows:
Press any key to continue.
■
■
Variables that the system supplies or that you must supply are shown in
italics. For example, an error message including one of your filenames is
shown as follows:
The filefilename is formatted incorrectly
The sequence of menu options that you must select to display a specific
screen is shown as follows:
xiv Issue 2 December 1995
About This Document
Begin at the Administration menu, and select the following sequence:
> Voice System Administration
> Voice Equipment
In this example, you would first access the Administration menu. Then you
would select the Voice System Administration option to display the Voice
System Administration menu. From that menu, you would select the Voice
Equipment option to display the Voice Equipment screen. For information
about how to select a menu option, see
Issue 2 December 1995 xv
About This Document
Trademarks and Service Marks
The following trademarked products may be mentioned in this book:
Product Name
Company
5ESS™
AT™
Registered trademark of AT&T
Trademark of Hayes Microcomputer Products, Inc.
Registered trademark of AT&T
AUDIX®
BT-542B™
Trademark of BusLogic Inc.
COMSPHERE®
Registered trademark of AT&T Paradyne Corp.
Registered trademark of AT&T
CONVERSANT® Voice Information System
DEFINITY®
Dterm™
Registered trademark of AT&T
Trademark of NEC Telephones, Inc.
Trademark of Equinox Systems, Inc.
Trademark of AT&T
Equinox™
INTUITY™
MD110®
Registered trademark of Ericsson, Inc.
Trademark of Equinox Systems, Inc.
Trademark of Equinox Systems, Inc.
Trademark of Northern Telecom Limited
Registered trademark of Microcom, Inc.
Trademark of NEC Telephone, Inc.
MEGAPLEX™
MEGAPORT™
Meridian™
Microcom Networking Protocol®
NEAX™
NEC®
Registered trademark of NEC
Inc.
Telephones,
Northern Telecom®
ORACLE™
Paradyne®
Phillips®
Registered trademark of Northern Telecom Limited
Trademark of Oracle Corporation
Registered trademark of AT&T
Registered trademark of Phillips Screw Company
Trademark of Northern Telecom Limited
Trademark of Texas Micro Systems, Inc.
SL-1™
TMI™
UNIX®
Registered trademark of UNIX Systems Laborato-
ries, Inc.
VT100™
Trademark of Digital Equipment Corporation
xvi Issue 2 December 1995
About This Document
Related Resources
In addition to this book, you may need to reference the following books:
Title
Order Number
585-310-211
585-310-212
585-310-540
585-310-602
585-310-603
585-310-146
585-310-147
585-310-138
585-310-141
585-310-139
585-310-137
585-310-140
585-310-214
INTUITY System Description
INTUITY AUDIX Feature Descriptions
INTUITY Documentation Guide
Migration to the INTUITY System
INTUITY New System Planning
INTUITY MAP/5 Hardware Installation
INTUITY MAP/5 Installation Checklist
INTUITY MAP/40 Hardware Installation
INTUITY MAP/40 Installation Checklist
INTUITY MAP/100 Hardware Installation
INTUITY MAP/100 Installation Checklist
INTUITY Software Installation
INTUITY Integration with System 75 and DEFINITY Communications
System G1and G3
INTUITY Integration with System 85 and DEFINITY Communications
System G2
585-310-215
INTUITY Integration with 5ESS
585-310-219
585-310-220
585-310-216
585-310-533
585-300-512
585-310-716
585-310-534
585-310-535
585-310-536
INTUITY Integration with DMS-100
Integration with NEAX
INTUITY AUDIX Digital Networking Administration
AMIS Analog Networking
INTUITY Intro Voice Response
INTUITY Platform Administration and Maintenance
INTUITY AUDIX Announcement Customization- American English
INTUITY AUDIX Announcement Customization-
British English
INTUITY AUDIX Announcement Customization- Latin Spanish
585-310-537
Issue 2 December 1995 xvii
About This Document
Title
Order Number
585-310-538
585-302-502
585-300-701
585-300-702
585-300-705
585-300-704
585-310-721
585-304-705
585-310-724
INTUITY AUDIX Announcement Customization- French Canadian
AUDIX Administration and Data Acquisition Package
A Portable Guide to Voice Messaging
Voice Messaging Quick Reference
Multiple Personal Greetings Quick Reference
Voice Messaging Wallet Card
Outcalling Quick Reference
Voice Messaging Business Card Stickers
Voice Messaging Subscriber Artwork Package
How to Make Comments About This
Book
A reader comment card is behind the title page of this book. While we have tried
to make this book fit your needs, we are interested in your suggestions for
improving it and urge you to complete and return a reader comment card.
If the reader comment card has been removed, send your comments to:
AT&T
Product Documentation Development Department
Room 22-2C11
11900 North Pecos Street
Denver CO 80234-2703
Please include the title and order number of this book.
xviii Issue 2 December 1995
Introduction and Requirements for
Integration
1
This chapter describes and defines requirements for the NEC NEAX 2400 MCI
switch integration with an INTUITY Messaging System. The chapter includes
diagrams and checklists that show the configuration for INTUITY Messaging
System.
To create an integrated environment between INTUITY Messaging System and
an NEC NEAX 2400 MCI switch, AT&T uses an electronic box called a Switch
Integration Device (SID). The SID operates as a protocol converter between the
switch and the INTUITY Messaging System, converting NEAX 2400 call
information into Simplified Message Desk Interface (SMDI) format and sending
the information to the application. The SID does not restrict any switch features.
For the SID to perform integrated call transactions, the switch must contain a
Message Center Interface (MCI) link. The MCI link provides an RS-232
connection between the NEAX 2400 and the SID. The NEAX 2400 sends call
information to the SID through the MCI link.
All channels reserved for the INTUITY Messaging System must be administered
in a Uniform Call Distribution (UCD) group. The first channel in the UCD serves
as the forwarding or central number for INTUITY Messaging System subscribers.
After administering the switch, all covered and forwarded calls transfer to the first
channel or central number of the UCD group. If the first channel is busy, the
system searches through the other members of the UCD group until the system
the hunting process.
Issue 2 December 1995 1-1
Introduction and Requirements for Integration
1. Incoming call sent
to the 1st extension
of the UCD Group.
The extension is busy.
BUSY
5001
2. The call Hunts
BUSY
to the next
5002
extension which
is also busy.
OPEN
Completed Call
5003
3. The call finds an
open extension.
The call is completed
using the open extension.
5004
Figure 1-1 UCD Group Hunting Process
By administering the UCD group, you enable the switch to support the following
features.
■
■
■
Calling party information for incoming calls
Call forward to a personal extension
Set and cancel message waiting indications
Subscribers also use the UCD central number to access the INTUITY Messaging
System.
Before you connect the NEAX 2400 MCI to the SID and the INTUITY System,
confirm that you have all required hardware and software integration
components. This chapter provides you with hardware and software diagrams,
checklists, and explanations. Use the information to confirm that you have all
required integration components.
1-2 Issue 2 December 1995
Safety Considerations
Safety Considerations
!
CAUTION:
Electrostatic discharge damages electronic equipment. Do not touch any
electronic component until you properly ground yourself.
To prevent damage to the equipment and yourself, follow these precautions:
■
Familiarize yourself with the procedures necessary to prevent electrostatic
damage to equipment.
■
■
■
■
Shut off all power and remove all cables from equipment.
Properly ground a work mat and wrist strap.
Place the equipment on the work mat.
Place the grounded wrist strap on your bare wrist. The wrist strap must
contact your bare skin directly. Do not wear the wrist strap over your
clothes.
Factory Assembled Systems
The factory performs assembly, load, and test (ALT) processes for most of the
INTUITY hardware and software before shipping the system to the site. Use the
information in this chapter to confirm that the system contains the hardware and
software for your configuration.
After checking the installed hardware and software, perform all tasks not
completed during ALT, such as connecting the voice and data lines, setting up
and cabling the peripherals, and installing the switch communications software.
Use one of the following checklists to make sure you complete all necessary
tasks:
■
■
■
INTUITY MAP/5 Installation Checklist, 585-310-147
INTUITY MAP/40 Installation Checklist, 585-310-137
INTUITY MAP/100 Installation Checklist, 585-310-141
Issue 2 December 1995 1-3
Introduction and Requirements for Integration
Determining the Placement of the SID
The Switch Integration Device (SID) and the MAP/5, MAP/40, or MAP/100
represent local devices. Place the SID and the MAP in the same area and close
enough together so the RS-232 cable supplied with the SID can connect to the
computer. During installation, the AT&T technician will place the SID and the
MAP in the location specified by the customer.
For the link between the MCI port and the INTUITY System, AT&T uses an
Electronic Industries Association (EIA) RS-232-C serial data electrical interface.
AT&T supplies an EIA standard RS-232 cable with a 25-pin connector. You
cannot directly connect the cable to the switch. The MCI port on the backplane of
the switch has a 25-pair connector. AT&T supplies the 25-pair to 25-pin adaptor
required to connect the RS-232 cable to the backplane of the switch. The
customer or the switch vendor representative must connect the adaptor to the
switch. AT&T assumes responsibility only for the RS-232 cable that connects to
the SID.
If the distance from the switch to the SID is longer than the RS-232 cable
reaches, you, the customer, must supply a cable that attaches between the AT&T
supplied cable and the NEAX 2400 MCI port adaptor. Use a cable that meets the
EIA RS-232 standards, including the 50 feet maximum cable length. Failure to
meet EIA communication standards may cause data transmission errors. If you
cannot reach the switch with the 50 feet maximum cable length, you, the
customer, must determine and engineer a method of connecting the SID and the
switch, such as using a limited-distance modem. AT&T does not recommend any
particular methods.
1-4 Issue 2 December 1995
System Configuration
System Configuration
The Intuity system connects to the NEAX switch through a Switch Integration
connections between an Intuity system on a MAP/5 platform and a NEAX switch
through COM1.
Digital
information
link
Demarcation
point
(MCI link)
Multi-port
serial card
Customer-
provided
connection
to NEAX
NEAX 2400
switch
Null cable
(shipped
with SID)
SID
Modular
cable
RS-232
6-25 pin
adapter
RS-232
cable
Analog
(voice) link
PA-16LCQ
analog port
IVC6
Modular
cable
Figure 1-2 Connections through the Multiport Serial Card for an Intuity Integration with
a NEAX Switch
Issue 2 December 1995 1-5
System Configuration
Intuity System Required Hardware
Table 1-1 lists the hardware components required on the Intuity system for the
NEAX integration.
Table 1-1. Intuity System Hardware Components Required for the Integration
AT&T
Supplied
Customer
Supplied
Component
Description
MAP/5, MAP/40, or Hardware platform that operates the
X
X
MAP/100
Intuity system software
IVC6 cards
Integrated Voice Processing (IVC6)
cards used for voice port connections.
May have a maximum of 11 cards.
Includes any of the following hardware:
885A adaptors and cables
X
X
25-ft. modular cords with 6-pin to 25-pin
adapters
Two high density cables, RJ21X, with a
356B adapter for T/R distribution
X
X
Multiport serial
port card
Equinox multiport card provides multiple
serial ports for adjunct component
connections. On the MAP/40 and MAP/
100, the COM ports are occupied by
other components and the Equinox card
must be used for the SID connection. On
the MAP/5, the COM1 port can be used
for the SID connection.
MAP5 only:
RS-232 cable
(DB-25)
For a COM1 connection on the MAP/5, an
RS-232 cable, DB-25, is required to
connect the SID to the Intuity system.
The cable includes a 25-pin to 9-pin
adapter (DB-9).
X
X
Equinox
For a connection to the Equinox multiport
serial card, an RS-232 cable with a 6-pin
to 25-pin adapter is required.
connection only:
RS-232 cable with
6-pin to 25-pin
adapter
Issue 2 December 1995 1-7
Introduction and Requirements for Integration
Switch Integration D evice Required Hardware
Table 1-1 lists the required SID components for the integration.
Table 1-2. Switch Integration Device Hardware Components Required for the
Integration
AT&T
Supplied
Customer
Supplied
Component
SID
Description
AT&T Switch Integration Device,
Release 2
X
Null Cable
Y-Cable
Used for connection to SID
X
X
Used for connection from Null cable to
customer A25B Cable
A25B Cable
MCI Cable
25-pair Amphenol female-to-female cable
used to connect Y-Cable and NEAX port
cable or MCI cable
X
X
Cable that connects from the NEAX MCI
digital port to the A25B cable
NOTE:
AT&T only assumes responsibility for connecting the Null cable and the
Y-cable to the SID. All remaining connections must be performed by the
customer or the customer’s switch technician.
1-8 Issue 2 December 1995
System Configuration
NEC NEAX 2400 MCI Hardware
The customer must provide the correct switch and related components as
before an AT&T technician arrives to install the INTUITY system. The INTUITY
system integrates only with the NEC NEAX 2400 switch and related components
Table 1-3. NEAX Switch Required Components
AT&T
Supplied
Customer
Supplied
Component
Description
NEAX 2400 MCI
Switch
■ Models UMG and MMG with software
level 4000 or greater with support for
the MCI link
X
■ Models SIM and IMG with software
level 5200 or greater with support for
the MCI link
■ The switch must have the 5200
Feature Application Floppy Disk
software installed. After installing the
software, reboot the switch.
MCI Digital Port
Configure an I/O port, for example
PA-IO02, as the MCI link
X
X
PA-16LCQ analog
ports
PA-16LCQ recommended because it can
be programmed to provide loop current
disconnect. An analog port is required
for each voice port. An analog port is
also needed for the internal modem on
the SID.
Issue 2 December 1995 1-9
Introduction and Requirements for Integration
following administration on the NEAX 2400.
■
Program the PA-16LCQ analog ports to provide an adequate loop current
disconnect, or wink. The PA-16LCQ card provides a default value of
approximately 128ms wink. The wink can be increased to approximately
448ms with a firmware upgrade from NEC. Without the upgrade and the
increase, two items occur:
— Call holding times increase substantially because the default
disconnect time is lower than the minimum time required by the
INTUITY System.
— Call answer messages end with a reorder tone of approximately
one second.
■
■
Set the recall timer on the NEAX switch to an amount of time longer than
the ring-no-answer time. If you do not, calls blind transferred to
subscribers administered for forward on ring-no-answer recall back to the
INTUITY System channel.
Administer the INTUITY System to transfer calls to a station other than an
actual attendant console, for example a digital telephone capable of
displaying calling party information. The NEAX 2400 switch does not allow
stations to transfer calls to an attendant console.
1-10 Issue 2 December 1995
Switch Integration Device Basics
2
Before you attempt to operate and administer the Switch Integration Device (SID)
and integrate an NEC NEAX 2400 MCI switch with an INTUITY System, you need
to understand the hardware components of the SID and how to use the device.
The information in this chapter explains the basic components of the SID and
how to use the system forms or screens.
The chapter covers the following topics.
■
■
■
■
■
■
SID hardware component descriptions
SID hardware component illustrations
Menu forms
Edit forms
Actions forms
Help functions
Read the information in this chapter to understand the SID hardware and
software.
Issue 2 December 1995 2-1
Switch Integration Device Basics
The Switch Integration Device
Hardware
Before you use the SID, you need to understand each hardware component.
locate the component.
Front Panel
LCD display
A two-line, 40-character, backlighted LCD display
screen used to show all menus and information on the
SID.
Diagnostic lights
LED lights used to indicate and trace possible
problems in the SID. The LEDs help to determine if
problems exist in the SID, the link to the PBX, the link to
the INTUITY System, or any combination of the
different links or systems. The Status LED lights when
you power on the SID.
Keypad
A 19-key, membrane-style keypad used to select
menu items, enter information, and perform all
administration on the SID. The keys include ten
numbered keys (0-9), four directional arrow keys, a
#
pound sign (
)key, a star key (
), a Function key,
*
Integration Device Administration", of this document
contains tables that show the function of each key, if
different than marked.
Rear Panel
Power switch
The toggle switch used to turn the SID on and off.
Power cord outlet
The male outlet where you plug in the power cord
shipped with the SID.
Link A and Link B
Modem port
Two RS-232 ports used to connect the SID to the PBX
connections for the two ports. (Detail 25 pin)
The SID contains an internal modem used for
diagnostic and software upgrade purposes. Use the
modem port to connect the SID’s modem to an
analog line.
Continue to the next section, “Using the SID Software,” for an explanation of how
to use the SID displays and menus.
2-2 Issue 2 December 1995
The Switch Integration Device Hardware
ABC
2
DEF
3
Func Mode
1
JKL
5
G4HI
M6NO
LCD
DISPLAY
PRS
7
TUV WXY
8
9
VM
PBX
COM
APP
0
#
Enter
Status
*
KEYPAD
DIAGNOSTIC
LIGHTS
25 Pin
25 Pin
Power
Switch
Link B
Link A
Line B
Power
Cord
Outlet
(Male)
Diag
Net B
Net A
Modem
Line A
115-230V AC
50/60 Hz
(Fan Outlet)
Figure 2-1. Top: SID Front Panel
Bottom: SID Back Panel
Issue 2 December 1995 2-3
Switch Integration Device Basics
The Switch Integration Device
Software
The SID contains software that allows you to perform installation, configuration,
and diagnostic tasks by using the keypad and the LCD screen. As you
administer the SID, you use three types of forms or screen displays. Each type of
form has a specific task.
■
■
■
Menu Forms — used to select one of several options.
Edit Forms — used to enter information into the SID’s configuration.
Action Forms — used to perform an action, view event logs, or monitor the
system.
This section contains descriptions and examples of each form and provides you
with instructions for using the forms. You also can find tables that show you valid
key actions for each form.
Menu Forms
Menu forms allow you to select options by pressing a key. You can select another
menu, an edit form, or an action form. The menu forms allow you to move
MCI User Interface Main Menu.
NEC
1-View
2-Utils
5-Logs
3-System
4-Setup
Figure 2-2. The MCI User Interface Main Menu
A menu form contains two items:
Name
You can find the menu name in the upper left hand corner
of the LCD display. Use the name as a reference item.
List of options
Menus show you different options. Each option has a
number and a label. Not all menus contain the same
number of options. To select an option from a menu, press
the option number on the keypad. The SID clears the
current form from the LCD display and places the form you
selected on the display. The label you selected appears
as the name of the form.
2-4 Issue 2 December 1995
The Switch Integration Device Software
Example: If you wanted option 4, SETUP, from the MCI User Interface Main Menu
SETUP
1-Params
2-Ports
3-Clear
4-Advanced
Figure 2-3. The Setup Form
The SID uses menus to organize all options and functions into categories. Menus
also permit the user to navigate easily through the forms by pressing one or more
keys.
Each type of form requires you to use different keys on the keypad to make
selections and enter information. The table below shows you what keys to use
with the menu forms.
Key
Action
1,2,3,4,5,6,7,8,9,0 Select menu option
*,#
No action
Func
Mode
Arrows
Enter
Return to main menu
No action
No action
No action
Edit Forms
Edit forms allow you to use the keypad to enter information into the SID’s
configuration. There are three types of edit forms:
■
■
■
Single Item
Two Item
Scroll Item
This section contains descriptions and examples of each type of edit form and
provides you with instructions for using the forms.
Issue 2 December 1995 2-5
Switch Integration Device Basics
Single Item Edit Forms
On a Single Item Edit form, you must enter one piece of information or answer
SETUP form. On the form, you need to enter the number of ports assigned to the
INTUITY System. In this example, you enter the appropriate value using the digits
ENTER
on the keypad and press
.
SETUP
Number of Ports
------
Figure 2-4. The Setup Form
Two Item Edit Forms
Two Item Edit forms ask two related questions. After you answer the first question
ENTER
and press
, the cursor moves to the second line. You must now enter
ENTER
information for the second question. When you press
the second time, the
cursor wraps or moves back to the first line. If you have entered all information
FUNC
press
correctly, press
or
to move to the next edit form. You can
to
return to Main Menu. If you did not enter the information correctly, you can
the VM Port form, an example of a two item edit form.
VM Port
LTN:
------
------
Extension:
Figure 2-5. The VM Port Form
Scroll Item Edit Forms
Scroll Item Edit forms ask questions that have a limited number of answers. The
SID places a default value in the field, but allows you to scroll or search through
the options. You use the left and right arrow keys on the keypad to scroll through
MCI
Baud Rate:
1200
<- ->1
Figure 2-6. The MCI Form
2-6 Issue 2 December 1995
The Switch Integration Device Software
In the example, you use the MCI form to set the baud rate for the MCI link. You
can set the baud rate to specific values between 300 and 9600 baud. On the
form you see a default value of 1200. To see the other options, you press the left
arrow key to decrease the baud rate or press the right arrow key to increase the
ENTER
rate. When you find the rate you want, press
to confirm your choice. You
can recognize scroll item edit forms by the small arrow symbols (<- ->) shown
below the form name.
Edit Form Keys
Edit forms require you to enter data for SID setup and configuration. Most edit
forms have default values already entered on them. If you choose to use the
FUNC
default value, press
to exit the form. As you edit forms, you can move to
the next or previous edit form, return to the main menu, or access a help screen.
Refer to the table below for a list of keys and the action each key performs.
Key
Action
1,2,3,4,5,6,7,8,9,0
*,#
Data entry keys
Data entry keys
Return to main menu
Help
Func
Mode
Up Arrow
Down Arrow
Right Arrow
Left Arrow
Enter
Go to previous edit form
Go to next edit form
Get higher value
Get lower value
Confirm entry
With some menu selections, you can access multiple edit forms that link together.
When you access multiple edit forms, press
to move to the previous form.
to move to the next form or press
Issue 2 December 1995 2-7
Switch Integration Device Basics
Edit Form H elp Functions
Edit forms allow you to actively access help screens. To access the help screen,
MODE
press
at any edit form. The SID places the help screen on the LCD
display. The SID retains any information you may have entered on the edit form
and places the edit form with your information back on the display when you exit
the help screen. You do not lose any information. Most help screens appear as
EDIT
1-Overtype
4-Undo
2-Insert 3-Clear
Figure 2-7. Help Screen Options Accessed From an Edit Form
The following list shows you each available option and explains the action of
each option shown on the help screen.
Overtype
The option places the editor into a mode that allows you to
enter new characters over existing characters.
Insert
The option changes the editor into a mode that allows you to
insert new characters between existing characters.
Clear
Undo
The option erases all characters in the field.
The option replaces any new information typed in the field with
information from the stored configuration.
Action Forms
Action Forms provide you with a window or a view into the integration application.
With action forms, you can monitor the application activity, review event logs, or
Statistics View form.
STATISTICS VIEW
Calls:
12481
MWIs:
10412
Figure 2-8. The Statistic View Action Form
Action forms operate in a dynamic or real-time mode. The screen changes with
each transaction processed by the SID. When you finish observing an action
FUNC
MODE
press
form, you can press
to return to the main menu. You also can
to access any available help options for the action form. Although not all action
MODE
forms have help options, by pressing
you usually can find optional ways
to look at the information presented on the action form.
2-8 Issue 2 December 1995
The Switch Integration Device Software
All action forms use the same keys on the keypad to perform functions and make
selections. The table below shows you what keys to use with the action forms.
Key
Action
1,2,3,4,5,6,7,8,9,0
No action
*,#
No action
Func
Mode
Arrows
Enter
Return to main menu
Help for Action Form
No action
No action
You have read the basic information necessary to integrate and INTUITY System
administration procedures.
Issue 2 December 1995 2-9
Switch Integration Device Basics
2-10 Issue 2 December 1995
Switch Integration Planning
3
Before you implement the NEC NEAX 2400 Message Center Interface (MCI)
integration with an INTUITY System, you must plan the process. This chapter
provides worksheets and information to help you plan and record the integration.
You use the worksheets later to complete the switch integration process.
By completing the worksheets you collect the following information:
■
■
■
■
■
■
■
■
Number of voice mail ports
Message desk number
Calling party identification pad string
Message waiting indicator pad string
Message waiting indicator features
Extensions/Logical terminal number plan
Message center interface baud rate
Simplified message desk interface baud rate
Continue with the instructions on the next page to plan the switch integration.
Issue 2 December 1995 3-1
Switch Integration Planning
Determining the Number of Voice
Mail Ports
You must specify the number of voice mail ports for the Switch Integration Device
(SID) to support and monitor.
The number of ports for the SID is the same as the number of ports assigned to
the INTUITY System. The maximum number of supported lines depends on the
switch software level. Your switch software must support the UCD overflow
feature. The SID assigns a default value of 140 to this field. To find the number of
voice ports assigned on the INTUITY System, refer to INTUITY New System
Planning, 585-310-603. After you determine the number of voice mail ports you
need to assign on the SID, write the number on line 1 of Worksheet A.
Worksheet A: Switch Integration Information
Line
Field or Feature Name
Number of voice mail ports:
Value
1
2
3
4
5
Message Desk Number:
CPID Pad String Number:
MWI Pad String Number:
001
0000000
0000000
MWI Feature:
(ENABLE = on, DISABLE = off)
6
7
MCI Baud Rate:
SMDI Baud Rate:
Setting the Message Desk Number
The Simplified Message Desk Interface (SMDI) message desk number must
match the number assigned on the voice mail system. For an INTUITY System,
use the default value assigned to the SID. The default value is 001. Line 2 of
Worksheet A already contains the value 001 as the message desk number.
3-2 Issue 2 December 1995
Setting the Calling Party Identification Pad String
Setting the Calling Party Identification
Pad String
The Message Center Interface (MCI) protocol, used by the NEAX 2400 switch to
communicate with the SID, provides calling and called party information
consistent with the dial plan administered on the switch. The SID operates on
Simplified Message Desk Interface (SMDI) protocol which uses a seven-digit
field. To compensate for the difference between the MCI and SMDI protocols, the
SID uses a seven-digit string, called the Calling Party Identification Pad (CPID)
string, that the SID overwrites with caller identification information. The SID
assigns the field a default value of 0000000. For an INTUITY System, use the
0000000 as the CPID pad string.
Example: If you set the CPID pad string to 0000000 and the SID receives a caller
ID of 245, the SMDI caller ID information becomes 0000245.
Setting the Message Waiting Indicator
Pad String
The Message Waiting Indicator (MWI) Pad String operates on the same basis as
the CPID Pad String. As with the CPID Pad String, the SID uses a seven-digit
string, called the Message Waiting Indicator (MWI) pad string, that informs the
SID about the format of MWI information generated by an INTUITY System. The
SID uses the MWI pad string to strip off digits not required by MCI. The SID
assigns a default MWI pad string of 0000000. For an INTUITY System, use the
value 0000000 as the MWI pad string.
Setting the Message Waiting Indicator
Feature
The MWI feature enables the INTUITY System to activate message waiting
lamps. The SID sets the default value for this field to ENABLE, which activates the
MWI feature. If you do not want the INTUITY System to activate the MWIs, change
the field to DISABLE. Write the value on line 5 of Worksheet A.
Determining the Message Center
Interface Baud Rate
You must set the baud rate for the MCI link. The SID provides baud rate
selections of 300, 1200, 2400, and 9600 baud and sets a default of 1200 baud.
Make sure that the baud rate equals the dip switch settings on the MCI link
to use the default setting, write 1200 on the worksheet.
Issue 2 December 1995 3-3
Switch Integration Planning
Determining the SMDI Baud Rate
You must set the baud rate for the Simplified Message Desk Interface (SMDI)
link. The SID provides baud rate selections of 300, 1200, 2400, and 9600 baud
and sets a default of 1200 baud. AT&T recommends that you use a baud rate of
2400. Write the SMDI link baud rate on line 7 of Worksheet A.
Determining the Extension/Logical
Terminal Number Plan
On the INTUITY System, you assign a channel to each extension to allow for
switch communications. For the SID application, you associate a Logical
Terminal Number (LTN) with each analog extension number used by the INTUITY
System.
For example, if you assign channel 0 to extension 2222 on the INTUITY System,
you assign LTN 1 (0001) to the extension on the SID. Assigning the LTN to an
extension tells the SID where to send information for the extension. If you do not
assign the LTNs, the SID does not integrate calls properly.
NOTE:
The INTUITY System uses 0 as the first channel number assigned to an
extension. The SID assigns 1 as the first LTN assigned to an extension. As
you assign channels and LTNs, the number is always one greater than the
number assigned on the INTUITY System.
To assign LTNs and extensions on the SID, refer to the planning document or
have your switch administrator list the extensions of all the analog ports assigned
channels, and extensions. After you complete all of the worksheets, proceed to
1
3-4 Issue 2 December 1995
Determining the Extension/Logical Terminal Number Plan
Worksheet B: Extension/LTN Plan
Extension LTN
Extension
LTN
1
2
3
4
5
6
7
8
9
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
43
45
47
49
51
53
55
57
59
61
63
Issue 2 December 1995 3-5
Switch Integration Planning
3-6 Issue 2 December 1995
Hardware Installation
4
This chapter describes the hardware and cable installation tasks required to
integrate the NEAX 2400 MCI switch with an INTUITY System through a switch
integration device (SID). Before you proceed with the instructions in this chapter,
verify that the hardware has been installed and that all required steps have been
completed on one of the following checklists:
■
■
■
INTUITY MAP/5 Installation Checklist, 585-310-147
INTUITY MAP/40 Installation Checklist, 585-310-141
INTUITY MAP/100 Installation Checklist, 585-310-137
This chapter covers the installation of all integration-related hardware
components. The tasks must be performed by the AT&T installation technician,
the customer, or the customer’s switch technician. Each task provides an
explanation of who should perform the task.
The hardware installation tasks covered in this chapter include:
■
■
■
■
■
■
Connect an analog line to the modem
Connect the MCI line to the switch
Connect the MCI cable to the A25B cable
Connect the Null cable and the Y-cable to the SID
Connect the SID to the INTUITY system
Connect the SID power cord
Continue with the instructions on the next page to install the hardware.
Issue 2 December 1995 4-1
Hardware Installation
Connect an Analog Line to the Modem
This task should be performed by the AT&T installation technician and the
customer or the customer’s switch technician.
The SID contains an internal modem that allows for remote site access and
maintenance. You must connect an analog line from the switch to the remote
modem to allow for maintenance. Connect the analog line to the switch before
the AT&T installation technician arrives.
Use the following procedure to connect the analog line to the modem.
1. Connect the analog line to the MODEM port on the SID, as shown in Figure
Proceed to the next task.
25 Pin
25 Pin
Power
Switch
Link B
Net B
Link A
Line B
Power
Cord
Outlet
(Male)
Diag
Net A
Modem
Line A
115-230V AC
50/60 Hz
(Fan Outlet)
Figure 4-1. Back View of the SID
4-2 Issue 2 December 1995
Connect the MCI Line to the Switch
Connect the MCI Line to the Switch
The customer or the customer’s switch technician must complete this task. AT&T
does not assume responsibility for any cable connections to the NEAX 2400
switch.
The NEAX 2400 switch communicates with the SID through a Message Center
Interface (MCI) link. To connect the link, the customer must provide a cable to
connect to the MCI digital port and also provide an A25B cable to connect to the
integration.
Digital
information
link
Demarcation
point
(MCI link)
Multi-port
serial card
Customer-
provided
connection
to NEAX
NEAX 2400
switch
Null cable
(shipped
with SID)
SID
Modular
cable
RS-232
6-25 pin
adapter
RS-232
cable
Analog
(voice) link
PA-16LCQ
analog port
IVC6
Modular
cable
Figure 4-2. NEAX Connections to the INTUITY System
NOTE:
To reduce the chance for data communication errors, do not exceed the
Electronics Industry of America (EIA) RS-232 standard cable length of 50
feet.
Issue 2 December 1995 4-3
Hardware Installation
Use the following instructions to connect the MCI line to the NEAX 2400 switch.
1. Set the MCI I/O port (PN PAIO02) at the same baud rate as the SID, 2400
NOTE:
To set the baud rate for the MCI Link, you must set switches 1, 2,
and 3 in a specific combination. For example, to set the baud rate
at 2400BPS, set switch 1 to ON, switch 2 to OFF, and switch 3 to
OFF.
Table 4-1. MCI I/O Port DIP-Switch SW01 or SW11 Settings for Switches 1
through 3
Switch Number
1
2
3
Function
ON
ON
ON
ON
ON
300BPS
OFF
ON
600BPS
ON
OFF
OFF
ON
1200BPS
2400BPS
4800BPS
9600BPS
Settings
ON
OFF
ON
OFF
OFF
ON
OFF
4-4 Issue 2 December 1995
Connect the MCI Line to the Switch
2. Set the parity of the MCI link to even and the word length to 7 bits.
in the switch.
NOTE:
If you need more information for setting the baud rate, parity, and
DIP-switches on the NEAX 2400 MCI port, refer to the
documentation supplied with your switch or contact your switch
service representative.
Table 4-2. MCI I/O Port DIP-Switch SW01 or SW11 Settings for Switches 4
through 8
Switch
Number
Setting
Function
ON
Parity bit valid
Parity bit invalid
Odd parity
4
OFF
ON
5
6
7
8
OFF
ON
Even parity
7 bits
OFF
ON
8 bits
1 stop bit
OFF
ON
2 stop bits
Send side FIFO is 1 byte
Send side FIFO is 64 bytes
OFF
Issue 2 December 1995 4-5
Hardware Installation
Table 4-3. MCI I/O Port DIP-Switch SW02 or SW12 Settings for Switches 1
through 8
Switch
Number
Setting
Function
ON
When PB lead is - terminal is busy
When PB lead is + terminal is busy
DTR signal is always ON
DTR signal is controlled by the CPU
DSR signal is not provided
DSR signal is provided
CD is not provided
1
2
3
4
5
6
OFF
ON
OFF
ON
OFF
ON
OFF
ON
CD is provided
CS is not provided
OFF
ON
CS is provided
CI is not provided
OFF
ON
CI is provided
PB signal is not provided
PB signal is provided
Not used
7
8
OFF
OFF
NOTE:
Recommended Default Settings:
■
■
■
If you use port 0, configure switches 01 and 02. If you use
port 1, configure switches 11 and 12.
Standard switch settings for SW01 or SW11 are 1 ON, 2 OFF,
3 ON, 4 OFF, 5 OFF, 6 OFF, 7 ON, and 8 ON.
Standard switch settings for SW02 or SW12 are 1 ON, 2 ON,
3 ON, 4 ON, 5 ON, 6 ON, 7 ON, and 8 OFF.
3. Connect one end of a 25-pair cable to the MCI I/O port on the switch.
4-6 Issue 2 December 1995
Connect the MCI Cable to the A25B Cable
Table 4-4. Cable Pinouts
RS-232
Pin
Number
NEAX 2400
25 Pair
RS-232
Function
Port 0
Violet/Slate
Blue/White
Orange/White
Blue/Red
Frame Ground
Transmit Data
Receive Data
Signal Ground
1
3
2
7
Port 1
Violet/Slate
Frame Ground
Transmit Data
Receive Data
Signal Ground
1
3
2
7
Green/Black
Brown/Black
Green/Yellow
Proceed to the next section.
Connect the MCI Cable to the A25B
Cable
The customer or the customer’s switch technician must connect the cable. AT&T
does not assume responsibility for connecting the MCI cable and the A25B
cable.
After connecting the MCI cable to the switch, you must connect the MCI cable to
the A25B 25-pair Amphenol cable. Use the following instructions to complete the
connection.
1. Connect the free end of the MCI cable to one end of the A25B cable.
2. Connect the free end of the A25B cable to the Amphenol connector on the
Y-cable shipped with the SID.
Proceed to the next section.
Issue 2 December 1995 4-7
Hardware Installation
Connect the Null Cable and the
Y-Cable to the SID
The AT&T installation technician, the customer, or the customer’s switch
technician must complete this task.
The NEAX 2400 switch communicates with the SID through a Message Center
Interface (MCI) link. To connect the SID to the MCI digital port, you must connect
a Null cable and a Y-cable to the SID. Use the following instructions to connect
the cables to the SID.
1. Connect one end of the Null cable to the 25-pin Link B on the SID, shown
2. Connect Port 0 of the Y-cable to the free end of the Null cable.
NOTE:
Port 1 on the Y-cable is not used for any connections with this
integration.
Proceed to the next section.
25 Pin
25 Pin
Power
Switch
Link B
Net B
Link A
Line B
Power
Cord
Outlet
(Male)
Diag
Net A
Modem
Line A
115-230V AC
50/60 Hz
(Fan Outlet)
Figure 4-3. Back View of the SID
4-8 Issue 2 December 1995
Connect the SID to the INTUITY System
Connect the SID to the INTUITY
System
This task requires you to connect the 6’ RS-232 cable to the SID and to the
INTUITY System and should be completed by the AT&T installation technician.
The cable connects directly to the SID and connects to the INTUITY system
through a 6-to-25-pin adaptor and a modular cable. Use the following
instructions to connect the SID to the INTUITY System.
1. Connect the 25-pin RS-232 connector to Link A on the back of the SID.
Figure 4-3 shows you the location of Link A.
2. Connect the 25-pin end of the 6-to-25-pin adaptor to the free end of the
RS-232 cable.
NOTE:
If you are connecting the SID to a MAP/5 through the COM1 port,
you do not need the adaptor. Connect the free end of the RS-232
cable to the COM1 port.
3. Plug the modular cable into the 6-to-25-pin adaptor.
4. Plug the free end of the modular cable into the multiport serial card in the
MAP/5, MAP/40, or MAP/100 platform.
Proceed to the next section.
Connect the SID Power Cord
The AT&T installation technician or the customer must complete this task.
1. Plug the female end of the power cord into the AC power-in socket on the
SID, shown in Figure 4-3.
2. Plug the male end of the power cord into the AC outlet provided by the
customer.
3. Locate the power switch on the back of the SID, shown in Figure 4-3.
4. Toggle the power switch to the ON position.
When you turn on the power switch, the Status LED on the front of the SID
illuminates.
You have completed the hardware installation steps required for the NEAX 2400
System", in this document.
Issue 2 December 1995 4-9
Hardware Installation
4-10 Issue 2 December 1995
Installing SID Software on the
INTUITY System
5
This chapter provides procedures for installing the SID software on the INTUITY
system.
NOTE:
Before you install the SID software, make sure that the voice system and
maintenance software are installed. Also, ensure that no other switch
software is already installed.
To install the SID software, perform the following 4 procedures:
1. Stop the voice system.
2. Load the SID software.
3. Start the voice system.
4. Turn on INTUITY AUDIX transfer feature.
Each of these procedures is described in the following sections.
Requirements
Before you install the SID software, note the following requirements:
Login: craft
Materials: SID Switch Integration
Software (2 floppy disks)
Issue 2 December 1995 5-1
Installing SID Software on the INTUITY System
Stop the Voice System
Before you can load the SID software, you must stop the voice system.
!
CAUTION:
All calls in progress will be disconnected.
Use the following procedure to stop the voice system.
1. Login as craft.
ENTER
2. Press
to accept the AT386 default.
You see the INTUITY Administration menu.
3. Select the following series of menu options:
> Customer/Services Administration
> System Management
> System Control
>Stop Voice System
After you select the last option, Stop Voice System, you receive the
following message:
Enter y to continue, n to quit.
4. Enter y to begin the process.
Before stopping the voice system, the system pauses until all calls in
progress disconnect. During the pause, you see a series of messages.
When all calls have disconnected, you receive the following message:
The Voice System has stopped
Press ENTER to continue...
ENTER
5. Press
.
The system returns you to the System Control menu.
CANCEL
6. Press
until you see the INTUITY Administration menu.
You are now ready to load the SID software, as described in the next
section.
5-2 Issue 2 December 1995
Load the SID Software
Load the SID Software
1. Starting at the INTUITY Administration menu, select the following series of
menu options:
> Customer/Services Administration
>System Management
>UNIX Management
>Software Install
After you select the last option, you see the Software Install menu, as shown in
Figure 5-1. Software Install Menu
Issue 2 December 1995 5-3
Installing SID Software on the INTUITY System
2. Select Floppy drive from the Software Install menu.
The system responds:
Insert diskette into Floppy Drive 1.
Type [go] when ready
or [q] to quit: (default: go)
3. Insert SID Switch Integration Package Disk 1 of 2 into the 3.5” floppy drive.
ENTER
4. Press
to install the software.
The system responds:
Installation in progress. Do not remove the diskette.
The following packages are available:
1
sid INTUITY SID Switch Integration Package
(486) 1.0-16
Select package(s) you wish to process (or ‘all’ to
process all packages). (default: all) [?, ??, q]
ENTER
5. Press
to accept the default of all.
You will see a series of messages indicating that the software is being
installed including a copyright statement. The system pauses at the
following prompt:
Select type of switch:
1) NEAX
2) ROLM
3) MITEL
4) NORTHERN
5) QUIT
Enter Selection:
6. Enter 1 to select NEAX. You receive the following confirmation message:
Confirm: You selected option 1. (y/n)
7. Enter y to select yes. The installation continues. The system pauses when
you see the following prompt:
Insert diskette 2 of 2 into Floppy Drive 1.
Type [go] when ready
or [q] to quit: (default: go)
8. Remove Disk 1 of 2 from the floppy drive.
9. Insert Disk 2 of 2 into the floppy drive.
ENTER
10. Press
to continue the installation.
Following several screen messages, you see the Switch Link
system defaults that are automatically set when you load the software.
5-4 Issue 2 December 1995
Installing SID Software on the INTUITY System
Table 5-1. Switch Link Administration Screen Entries
Field
Description
Data link test number Indicates the test number sent to the switch to verify
whether the switch is active.
Setting: A 7- or 10-digit number that is not an in-
service extension number. The number of digits must
agree with the setting for the dialstring size set on the
to find the dialstring size.
Serial port
Indicates which port on the multi-port circuit card in
the INTUITY system is connected to the integration
device.
Setting: Press
(F2) to choose from a menu of
CHOICES
available ports. Settings are in the format /dev/ttysax,
where x is a letter a - h representing a port on the
circuit card (from right to left). AT&T recommends
that you use /dev/ttysaa as the serial port.
Baud rate
Indicates the rate at which the SID and the INTUITY
system communicate.
Setting: A baud rate of 1200, 2400, 4800, or 9600.
Press
(F2) to choose from a menu of
CHOICES
possible settings. This setting must agree the BAUD
setting on the SID. AT&T recommends that you use a
baud rate of 2400.
Comment
Use the field to enter a comment. Enter a maximum of
30 characters. In your comment, do not use double
SHIFT
quotation marks (“)
or
+ baaschksl
(\).
5-6 Issue 2 December 1995
Load the SID Software
SAVE
12. Press
(F3).
After you press the key, you receive a confirmation message as shown in
successfully and that you need to start the voice system
Figure 5-3 Switch Link Administration Confirmation Message
CANCEL
13. Press
(F6).
You see the Switch Link Administration screen.
CANCEL
14. Press
(F6) again.
You see
smeevsesralges indicating that the installation is still running.
When the installation process finishes, you see the following messages:
Installation of INTUITY SID Integration Package (sid)
was successful.
Insert a diskette into Floppy Drive 1.
Type [go] when ready
or [q] to quit: (default: go)
15. Remove Disk 2 of 2 from the floppy drive.
16. Enter q to quit.
The Software Install screen is redisplayed.
CANCEL
17. Press
until you see the INTUITY Administration menu.
Restart the voice system as described in the next section.
Issue 2 December 1995 5-7
Installing SID Software on the INTUITY System
Start the Voice System
Restart the voice system for the INTUITY system to accept and process calls.
Use the following procedure to start the voice system.
1. Starting at the INTUITY Administration menu, select the following series of
menu options:
> Customer/Services Administration
> System Management
> System Control
>Start Voice System
You see messages indicating that the voice system is being restarted.
When the process finishes, you see the following message:
Startup of the Voice System is complete
Press ENTER to continue...
ENTER
2. Press
.
You see the System Control menu.
CANCEL
3. Press
until you see the INTUITY Administration menu.
Turn on Transfer Feature
After you install the NEAX software and restart the voice system, you need to turn
on the transfer feature in INTUITY AUDIX. For this procedure, see INTUITY
AUDIX Administration, 585-310-539, and set the transfer type field to basic.
5-8 Issue 2 December 1995
Administering the INTUITY System
for the NEAX Integration
6
This chapter describes how to administer the INTUITY system for integration with
the NEAX switch. To integrate with the NEAX switch, the INTUITY system needs
to know specific information about how the integration is set up, such as the
serial port and baud rate being used. To administer the INTUITY system, you
must complete the following screens:
■
■
Switch Link Administration screen
System Translation screen
Issue 2 December 1995 6-1
Administering the INTUITY System for the NEAX Integration
Administering the Switch Link
Administration Screen
During the NEAX software installation process, the values for the Switch Link
Administration screen were administered. You need to change the default
settings on this screen. Use the following procedure to change the settings.
1. Login as craft.
ENTER
2. Press
to accept the AT386 default.
You see the INTUITY Administration menu as shown in Figure 6-1.
Figure 6-1. INTUITY Main Menu
3. Select Switch Interface Administration from the INTUITY Main Menu.
After you select the option, you see the Switch Interface Administration
menu as shown in Figure 6-2.
6-2 Issue 2 December 1995
Administering the Switch Link Administration Screen
Figure 6-2
Switch Interface Administration Menu
4. Select Switch Link Administration from the menu. After you select the
option, you see the Switch Link Administration screen as shown in Figure
Figure 6-3 Switch Link Administration Screen
Administration screen.
Issue 2 December 1995 6-3
Administering the INTUITY System for the NEAX Integration
Table 6-1. Switch Link Administration Screen Entries
Field
Description
Data link test
number
Indicates the test number sent to the switch to verify
whether the switch is active.
Setting: A 7- or 10-digit number that is not an in-
service extension number. The number of digits must
agree with the setting for the dialstring size set on the
to find the dialstring size.
Serial port
Baud rate
Comment
Indicates which port on the multi-port circuit card in the
INTUITY system is connected to the integration device.
Setting: Press
(F2) to choose from a menu of
CHOICES
available ports. Settings are in the format /dev/ttysax,
where x is a letter a - h representing a port on the
circuit card (from right to left). AT&T recommends that
you use /dev/ttysaa as the serial port.
Indicates the rate at which the SID and the INTUITY
system communicate.
Setting: A baud rate of 1200, 2400, 4800, or 9600.
Press
(F2) to choose from a menu of possible
CHOICES
settings. This setting must agree the BAUD setting on
the SID. AT&T recommends that you use a baud rate
of 2400.
Use the field to enter a comment. Enter a maximum of
30 characters. In your comment, do not use double
SHIFT
quotation marks (“) or
+ backslash (\).
6-4 Issue 2 December 1995
Administering the Switch Link Administration Screen
SAVE
6. Press
(F3).
After you press the key, you receive a confirmation message as shown in
successfully and that you need to stop and restart the voice system
Figure 6-4 Switch Link Administration Confirmation Message
CANCEL
7. Press
(F6) until you see the INTUITY Administration menu as
shown in the Figure 6-1.
Issue 2 December 1995 6-5
Administering the INTUITY System for the NEAX Integration
Stopping and Restarting the Voice
System
To execute the changes you made on the Switch Link Administration screen, use
the following procedure to stop and restart the voice system.
the following series of menu options:
> Customer/Services Administration
> System Management
> System Control
>Stop Voice System
After you select the last option, Stop Voice System, you receive the
following message:
Enter y to continue, n to quit.
2. Enter y to begin the process.
Before stopping the voice system, the system pauses until all calls in
progress disconnect. During the pause, you see a series of messages.
When all calls have disconnected, you receive the following message:
The Voice System has stopped
Press ENTER to continue...
ENTER
3. Press
.
The system returns you to the System Control menu.
4. Select Start Voice System from the System Control menu.
After you select the option, you receive a message indicating that the
voice system is restarting. When the process finishes, you receive the
following messages:
Startup of the Voice System is complete
Press ENTER to continue...
ENTER
5. Press
.
The system returns you to the System Control menu.
CANCEL
6. Press
until you see the INTUITY Administration menu.
6-6 Issue 2 December 1995
Administering the System Translation Screen
Administering the System Translation
Screen
Use the following procedure to administer the System Translation screen.
the following series of menu options:
> Switch Interface Administration
> System Translation
After you select the System Translation option, you see the System
Translation screen as shown in Figure 6-5.
Figure 6-5. System Translation Screen
Administration screen.
Issue 2 December 1995 6-7
Administering the INTUITY System for the NEAX Integration
Table 6-2. System Translation Screen Entries
Field
Description
Switch link type
The field contains the current switch link type. You
cannot change this setting.
Host type
The field contains the current host switch type. You
cannot change this setting.
Host link ID
Extension length
The field contains the current host link ID. You
cannot change this setting.
The field indicates the number of digits allowed for
each extension in the address range.
Setting: Enter a number from 3 to 10.
Address Ranges: first
Address Ranges: last
Address Ranges:
The fields indicate the first and last extension
number in the address range and the public network
number.
public network number
Setting: Address ranges are obtained from the
switch. You can have up to 8 address ranges, one
for each public network number. These ranges
cannot overlap.
The number of digits for the first and last extensions
corresponds to the setting in the Extension length
field. The number of digits for the public network
number must match the dial string on the SID. The
public network number must end with the digits of
the first extension number. For an example, see
6-8 Issue 2 December 1995
Administering the System Translation Screen
SAVE
3. Press
(F3) to save you entries on the screen.
After you press the key, you see the Command Output screen as shown in
successfully.
Figure 6-6 Command Output Screen
CANCEL
4. Press
(F6) until you return to the INTUITY Administration menu.
You have completed the procedure required on the INTUITY System.
Issue 2 December 1995 6-9
Administering the INTUITY System for the NEAX Integration
6-10 Issue 2 December 1995
NEAX 2400 Switch Administration
7
This chapter contains instructions for administering an NEC NEAX 2400 MCI
switch to work with an INTUITY System. If you have another type of switch, refer
to the documentation provided with that switch or the switch integration package
for more information.
The instructions in this chapter only explain the screen fields and information
necessary to integrate the NEAX 2400 switch with an INTUITY System. If you
require more information for any screens or processes not explained in this
chapter, refer to the documentation supplied with your switch for more
information.
As you administer the switch, you must perform the following processes:
■
■
■
Administer analog voice mail ports
Assign voice mail ports to a UCD group (switch group)
Configure the Message Center Interface link
NOTE:
This chapter contains administration guidelines for the NEAX 2400 switch
with the INTUITY System. The switch administration process should be
performed by a trained NEC switch technician.
Issue 2 December 1995 7-1
NEAX 2400 Switch Administration
Administer Analog Voice Mail Ports
Each voice mail port connects to the switch through an analog line. For the
integration process to function, you must configure the voice mail port analog
lines in the same manner as you configure analog lines for a 2500 telephone set.
After configuring the ports on the switch, you must assign the analog port
extension numbers on the SID configuration. You perform the SID processes in
NOTE:
Automated Attendant may not work properly on the NEAX 2400 with
software version 4200 due to limitations in the NEAX 2400 switch.
Use the following instructions to administer the analog lines for the voice mail
ports.
1. Log on to the NEAX 2400 Maintenance and Administration Terminal
(MAT). For NEAX 2400 MAT logon instructions, contact your system
administrator.
2. After you log on to the MAT, you see the 2400 Maintenance Command
MENU as shown in Figure 7-1.
***
SYSTEM CONTROL
SYSTEM BACKUP
MAKE BUSY CONTROL
TRAFFIC DATA
TEST
2400 MAINTENANCE COMMAND MENU
***
1
2
3
4
5
6
7
STATION DATA
TRUNK DATA
8
NUMBERING PLAN
9
SERVICE FEATURE DATA (1)
SERVICE FEATURE DATA (2)
SIGNAL TRANSLATION DATA
RESTRICTION DATA
INSTALLATION
LIST UP
10
11
12
13
14
ENTER MENU ITEM NO [ 6 ]
Figure 7-1. 2400 Maintenance Command Menu
7-2 Issue 2 December 1995
Administer Analog Voice Mail Ports
3. Enter 6 to select the Station Data option. After you select the option, you
see the Station Data Commands screen as shown in Figure 7-2.
*** STATION DATA COMMANDS ***
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
ASDT: Assignment of Station Data
ASCL: Assignment of Station Class Data
ASTN: Assignment of Station Number
[CM01]
[CM01]
[CM01]
[CM01]
[CM01]
[CM01]
[CM01]
[CM01]
[CM01]
[CM01]
[CM02]
[CM02]
[CM01]
[CM01]
[CM01]
DSTN: Display of Station Data
AKYD: Assignment of Key Data for Dterm
ASHP: Assignment of Station Hunting-Pilot
RSHP: Remove Station Hunting-Pilot
ASHC: Assignment of Station Hunting-Circularn
RSHC: Remove Station Hunting-Circular
ACPG: Assignment of Call Pickup Group
AISA: Assignment of Individual Speed Calling Entry Area
APHN: Assignment of Phantom Station Number
ASHU: Assignment of Station Hunting-UCD
RSHU: Remove Station Hunting-UCD
AUOG: Assignment of UCD Overflow Group
ENTER MENU ITEM NO [ 1 ]
Figure 7-2. Station Data Commands Menu
Issue 2 December 1995 7-3
NEAX 2400 Switch Administration
4. Enter 1 to select the Assignment of Station Data option and enter station
administration information for each voice mail port. After you select the
option, you see the screen as shown in Figure 7-3.
Assignment of Station Data
TN: 1 STN:
LENS: 000000
TEC: 1 RSC: 0 SFC: 0
TN : Tenant Number
STN : Station Number
LENS: Line Equipment Number (6 Digits)
TEC : Telephone Class (1-31)
1-DP (10PPS) 22-EMM
2-PB
3-DP/PB
11-VMM/VMZ
12-Dterm V
13-Data Terminal via Dterm V
14-Hot Line
15-Cas Line
RSC: Route Restriction Class (0-15)
for assignment of RSC,ARSC cmnd
SFC: Service Feature Class (0-15)
for assignment of SFC,ASFC cmnd
16-Data Terminal via Data Module
18-Virtual Line Appearance
19-TMM
20-PSM
Figure 7-3. Assignment of Station Data Screen
5. In the TN (Tenant Number) field, you see a default value of 1. To select the
ENTER
default value, press
. The cursor moves to the STN field.
Contact your switch system administrator to determine if this value must
be modified.
6. At the STN (station) field, enter the number you plan to use as an analog
ENTER
voice mail port extension. After you press
LENS field.
the cursor moves to the
For example, if you want to assign extensions 500, 501, 502, and 503 to a
four port system, enter 500 as the first extension.
7. In the LENS (Line Equipment Number) field, you see a default value of
ENTER
00000. Enter the correct LENS. After you press
the TEC field.
the cursor moves to
Contact your switch system administrator for the correct line equipment
assignment.
8. In the TEC (Telephone Class) field, you see a default value of 1. Enter 3 in
the field to permit dial pulse and push button functionality. After you press
ENTER
the cursor moves to RSC field.
7-4 Issue 2 December 1995
Administer Analog Voice Mail Ports
9. In the RSC (Route Restriction Class) field, you see a default value of 0.
ENTER
Enter the correct RSC. After you press
field.
the cursor moves to the SFC
Contact your switch system administrator to determine if the default value
is correct.
10. In the SFC (Service Feature Class) field, you see a default value of 0. Enter
the correct SFC.
Contact your switch system administrator for the correct SFC value.
ENTER
11. When you finish editing the final field, press
administration.
to confirm the station
12. When you assign the first station data command for a Line Package, the
message PKG CHECKappears on the screen.
ENTER
Check that the correct circuit card is in the correct slot and press
.
ENTER
After you press
the cursor returns to the first field.
If you continue to assign station data commands to the same Line
Package, you receive a WRT? message after entering the station
information.
ENTER
press the cursor
Enter Y to confirm the information. After you
returns to the first field.
13. Repeat steps 5 through 12 for each analog voice mail port you need to
assign. For example, if you have already assigned extension 500 but you
still need to assign extensions 501, 502, and 503, return to Step 5 and
enter 501 as the second extension. Repeat the process until 502 and 503
have been assigned. When you finish entering the analog voice mail port
/
numbers, press
to return to the Station Data Commands menu.
Proceed to the next section, “Assign Voice Mail Extensions to a UCD
Group.”
Issue 2 December 1995 7-5
NEAX 2400 Switch Administration
Assign Voice Mail Extensions to a
UCD Group
After administering the analog voice mail ports, you must assign the ports to a
Uniformed Call Distribution (UCD) group or switch group. The first extension of a
UCD group becomes the forwarding target number for the group. When a
subscriber calls INTUITY System, they dial the target number of the UCD group.
If the target number is busy, the system hunts or moves through the other
members of the UCD group until the system finds an open channel and
completes the call.
The examples in the previous section assigned extensions 500, 501, 502, and
503 to the analog voice mail ports. 500 was assigned as the first port extension
and is the target number.
The NEAX 2400 supports up to seven UCD groups with twenty members in each
group. The UCD groups do not automatically transfer calls to each other. To
connect the groups, you must use the UCD Overflow feature. Using UCD
Overflow, calls flow to the next UCD group if all members of the first UCD group
are busy. To support more than 24 ports on the INTUITY System, use UCD
for UCD Overflow groups setup instructions.
Use the following instructions to assign voice mail port extensions to a UCD
group.
7-6 Issue 2 December 1995
Assign Voice Mail Extensions to a UCD Group
select the Assignment of Station Hunting-UCD option. After you enter the
selection, you see the Assignment Of Station Hunting - UCD screen as
shown in Figure 7-4.
Assignment of Station Hunting - UCD
TN: 1
TN : Tenant Number
STN: 500
CNT: 4
STN: Station Number
2
STN: 501
CNT: Number of Stations to entered
(Recommend Max of 20 stations)
ADD: Number of Stations to be added
(Recommend Max of 20 stations)
*STN: Station Numbers of the Stations
included in the UCD group
(* indicates the order of
a station in the group)
Figure 7-4. Assignment of Station Hunting -UCD Screen
2. In the TN field, enter the Tenant Number you assigned to the analog voice
mail ports. The system shows a default value of 1 in the field.
ENTER
After you press
, the cursor moves to the STN field.
3. In the STN field, enter the number you assigned as the first voice mail port
extension. After you enter the station number, the cursor moves to the
CNT field.
For example, in the previous section a group of analog voice mail ports
was assigned extensions 500, 501, 502, and 503. 500 was the first
extension assigned.
4. In the CNT (count) field, enter the number of extensions you need to
include in the UCD group. After you enter the count, the cursor moves to
the second STN field.
For example, to set up a UCD group using extensions 500, 501, 502, and
503, enter 4.
Issue 2 December 1995 7-7
NEAX 2400 Switch Administration
5. In the second STN field, enter the second voice mail port station you need
to assign to the UCD group.
Using the 500, 501, 502, and 503 example, enter 501 as the second voice
mail port station.
6. Repeat Step 5 until you enter all voice mail port extensions in the UCD
group. The system continues to ask for voice mail port extensions until you
enter the enough stations to match the CNT field.
In the examples above, CNT was set to 4. Extensions 500, 501, 502, and
503 were assigned to the UCD group. 503 is the fourth and last extension.
7. After you enter the last extension for the UCD group, you see the message
WRT?on the screen. Enter Y to confirm and save the information you
entered.
/
8. Press
menu.
to exit the screen and return to the Station Data Commands
Setting Up a UCD Overflow Group
On the NEAX 2400 switch, you can create a maximum of 7 UCD groups with 20
station extensions in each UCD group. If all the extensions in a UCD group are
busy, calls do not automatically transfer to the next group. You must use the
UCD Overflow feature to link the groups together. By using the UCD Overflow
feature, an incoming call transfers from a busy UCD group to another UCD
group. If you plan to use an INTUITY System with more than 24 ports, you must
use the UCD overflow feature.
NOTE:
The NEAX 2400 switch must have software version 4200 or greater to
support UCD overflow. If the switch does not contain software version
4200 or greater, the SID only supports 20 voice mail extensions, the
maximum allowed in one UCD group.
Use the following instructions to administer UCD Overflow.
Extensions to a UCD Group"” to assign all voice mail ports to UCD groups.
For example, if you are setting up an INTUITY System with 24 ports, you
could set up 4 UCD groups with 6 ports in each group. Determine the
best method for your application.
2. After you create all necessary UCD groups and return to the Station Data
Command menu, enter 15 to select the Assignment of UCD Overflow
option.
7-8 Issue 2 December 1995
Assign Voice Mail Extensions to a UCD Group
After you select the option, you see the Assignment of Ucd Overflow
Group screen as shown in Figure 7-5.
Assignment of UCD Overflow Group
TN-A:
TN-B:
1 STN-A:
1 STN-B:
500
502
TN-A, STN-A: Tenant Number and Station
which belongs to a UCD group
TN-B, STN-B: Tenant Number and Station
Number of member station
in a UCD group to be hunted
in the case where the UCD
designated by TN-A and STN-A
happens to be busy.
Figure 7-5. Assignment of UCD Overflow Group Screen
3. In the TN-A field, enter the Tenant Number you assigned to the first UCD
ENTER
group you created. After you press
field.
, the cursor moves to the STN-A
4. In the STN-A field, enter the target number of the first UCD group you
ENTER
created. After you press
, the cursor moves to the TN-B field.
For example, if you create two UCD groups with extensions 500 and 501
in the first group and extensions 502 and 503 in the second group, the
target number for the first UCD group is 500.
5. In the TN-B field, enter the Tenant Number you assigned to the UCD
group you want the system to transfer to when the first UCD group is busy.
Figure 7-5. use 1.
6. In the STN-B field, enter the target number of the UCD group you want the
system to transfer to when the first UCD group is busy.
Figure 7-5. uses 502 as the target number of the second group.
In the example, when all stations in UCD group 500 are busy, voice messaging
traffic automatically overflows or transfers to the target number of the second
UCD group, 502. You can link more than two UCD groups. If you do need to link
more than two UCD group, assign overflow for the target number of the second
UCD group to the target number of the third UCD group. You may assign
overflow to as many as 7 groups of 20 stations each.
Issue 2 December 1995 7-9
NEAX 2400 Switch Administration
Configuring the Message Center
Interface Link
Voice messaging information travels from the switch to the SID through the
Message Center Interface (MCI) link. For the MCI link to function properly, you
must configure the MCI data link. During the process you perform the following
actions:
■
■
■
Administer the Message Waiting Lamp
Assign a port for the MCI link
Define the MCI port as a terminal
Administer the Message Waiting Lamp
You must administer the switch to assign Message Waiting Lamp (MWL) control
to the MCI link. Use the following instructions to administer the MCI link MWL
parameters.
NOTE:
Do not change any information on any screen until you contact your NEAX
2400 switch administrator. Few switches are identically configured. The
instructions in this section provide the minimum requirements for the MCI
integration to function with the SID. If you need more information on
configuring the switch, contact your switch administrator or consult the
documentation supplied with the switch.
7-10 Issue 2 December 1995
Configuring the Message Center Interface Link
to select the Installation option. After you select the option, you see the
Installation Commands menu as shown in Figure 7-6.
***
INSTALLATION COMMANDS
***
1
2
3
4
5
6
ASYD: Assignment of System Data
AUNT: Assignment of Unit Data
ASTD: Assignment of State Translation Data
ATCC: Assignment Terminal Configuration Command
ASMD: Assignment Service Module Data
MMNF: Make Menu File
[CM03]
[CM03]
[CM03]
[CM03]
[CM03]
[CM02]
ENTER MENU ITEM NO [ 1 ]
Figure 7-6. Installation Commands Menu
Issue 2 December 1995 7-11
NEAX 2400 Switch Administration
ENTER
press
2. Enter 1 to select the System Data option. After you
seyeou
the Assignment Of Station Data screen as shown in Figure 7-7.
Assignment of System Data
SYS: 1
INDEX:
SYS : System Data Items
1-System Data 1
28
DATA:
20
2-System Data 2
3-System Data 3
TN
: Tenant Number
INDEX: System Data Index
System
Index
0-255
0-15
1
2
3
0-31
DATA : System Data (Hexa-decimal)
Figure 7-7. Assignment of System Data Screen
3. Enter 1 in the SYS field.
You can select three types of switch system parameters. Each type has a
different effect on the switch, as shown in the following list.
■
■
■
Type 1 — parameters that effect the entire system
Type 2 — parameters that effect specific system tenants
Type 3 — parameters that effect the system timing
MWL control effects the entire system.
4. Enter 28 in the INDEX field.
System data (SYS) 1, which you specified in Step 3, uses 255 indexes to
control a variety of system parameters. Index 28 controls MWLs.
5. Enter 20 in the DATA field.
The value of 20 works with the information you entered in SYS and INDEX
to set MWL control to the MCI link.
/
6. After entering the information, press
to exit the screen and return to the
Installation Commands menu as shown in Figure 7-6.
7-12 Issue 2 December 1995
Configuring the Message Center Interface Link
If you need more information for any of the screen fields or processes described
in this section, contact your switch administrator or consult the documentation
supplied with your switch.
Assign a Port for the Message Center
Interface Link
Use the instructions in this section to assign a port for the MCI link. Assigning a
port tells the switch the proper port to send information to the SID through the
MCI link.
ENTER
the System Data option. After you press
you see the ASsignment
Of Station Data screen as shown in Figure 7-8.
Assignment of System Data
SYS: 1
INDEX:
SYS : System Data Items
29
DATA:
02
1-System Data 1
2-System Data 2
3-System Data 3
TN
: Tenant Number
INDEX: System Data Index
System
Index
0-255
0-15
1
2
3
0-31
DATA : System Data (Hexa-decimal)
Figure 7-8. Assignment of System Data Screen
2. Enter 1 in the SYS field to tell the switch that the parameter changes effect
the entire system.
3. Enter 29 in the INDEX field.
System data (SYS) 1 uses 255 indexes to control a variety of system
parameters. Index 29 controls the port assignment for the MCI link.
Issue 2 December 1995 7-13
NEAX 2400 Switch Administration
determine the port assignment for the MCI link.
To use the chart, find the port number you want to use under the Port
heading. When you find the port number, find the Data value in the Data
column across from the port number. One port is reserved for the MAT.
Table 7-1. Port Assignment Data Field Values
Port
Data
Bit
MAT Terminal
1
2
3
4
5
02
04
08
20
40
1
2
3
4
5
/
5. After entering the information, press
to exit the screen and return to the
Installation Commands menu as shown in Figure 7-6.
If you need more information for any of the screen fields or processes used in this
section, contact your switch administrator or consult the documentation supplied
with your switch.
7-14 Issue 2 December 1995
Configuring the Message Center Interface Link
Define the Port as a Terminal
You must now designate that the port assigned to the MCI link is a terminal or
two-way communication port. If you do not perform this step, the switch uses the
port as a printer or one-way communication port.
Use the following instructions to define the MCI port type.
ENTER
the System Data option. After you press
, you see the Assignment of
Assignment of System Data
SYS: 1
INDEX:
SYS : System Data Items
117
DATA:
01
1-System Data 1
2-System Data 2
3-System Data 3
TN
: Tenant Number
INDEX: System Data Index
System
Index
0-255
0-15
1
2
3
0-31
DATA : System Data (Hexa-decimal)
Figure 7-9. Assignment of System Data
2. Enter 1 in the SYS field to tell the switch that the parameter changes effect
the entire system.
3. Enter the index number in the INDEX field that corresponds to the port
number for the port.
Issue 2 December 1995 7-15
NEAX 2400 Switch Administration
Under the Port heading, find the port number you assigned to the MCI link
you find the port number, locate the index value in the Index column
showing that the MCI link was assigned port number 1.
Table 7-2. Index Assignment Values
Port
Index
Data
MAT Terminal
1
2
3
4
5
117
118
119
120
121
01
01
01
01
01
4. Enter 1 in the DATA field. The number tells the switch that the port is a
terminal and allows two-way communication.
Assign the MCI Link to a UCD Group
You must instruct the switch that the MCI link is associated with the UCD group
you created in the previous section. If you do not perform this step, the switch
does not communicate through the MCI link.
7-16 Issue 2 December 1995
Configuring the Message Center Interface Link
Use the following instructions to configure the UCD group with the MCI link.
ENTER
select the System Data option. After you press
, you see the
ASSIGNMENT OF STATION DATA screen as shown in Figure 7-10.
Assignment of System Data
SYS: 2
INDEX:
TN:
DATA:
1
SYS : System Data Items
1-System Data 1
6
01
2-System Data 2
3-System Data 3
TN
: Tenant Number
INDEX: System Data Index
System
Index
0-255
0-15
1
2
3
0-31
DATA : System Data (Hexa-decimal)
Figure 7-10. Assignment of System Data
2. Enter 2 in the SYS field to tell the switch to associate the MCI link with a
UCD group on a tenant by tenant basis.
3. Enter 1 in the TN field. You must use the same tenant value that you used
to create the analog stations and UCD groups.
4. Enter 6 in the INDEX field. The value contains fields that allow the system
to associate the MCI link with the UCD group or groups.
Issue 2 December 1995 7-17
NEAX 2400 Switch Administration
5. Look at the value in the DATA field and write the value on the following line
Current DATA value: _________
NOTE:
Do not change the value in the DATA field until you consult with
your switch administrator. This index contains other fields that
control features not related to MCI.
6. Enter 01 in the DATA field.
You have completed the NEAX 2400 MCI switch administration. Proceed to
integration device.
7-18 Issue 2 December 1995
Switch Integration Device
Administration
8
The instructions in this chapter explain how to configure the SID to integrate with
an NEAX 2400 MCI switch and an INTUITY System. The installation technician
administers the SID based on NEAX switch administration information provided
by the customer. As you administer the SID configuration, you must perform the
following tasks:
■
Administer the basic parameters
— Number of voice mail ports
— Message desk number
— CPID pad string
— MWI pad string
— MWI feature
■
■
■
■
■
Administer the extensions and logical terminal numbers
Save and start the configuration
Administer the serial data links
Set the security level
Change the system parameters
— Set the date and time
— Adjust the LCD contrast
Issue 2 December 1995 8-1
Switch Integration Device Administration
Administer the Basic Parameters
planning worksheets and determined the values for each of the basic
parameters. If you did not complete the worksheets, turn to Chapter 3 and
complete them now before you proceed with the instructions in this chapter.
After you complete the worksheets in Chapter 3, continue with the instructions on
the next page to configure the basic parameters.
FUNC
1. To access the basic parameters edit forms, press
keypad.
on the SID
After you press the key, you see the MCI MAIN MENU as shown in the
following example:
NEC
1-View
2-Utils
5-Logs
3-System
4-Setup
4
2. To set up the basic parameters for the MCI data link, press
keypad to select the SETUP option.
on the SID
After you press the key, you see the SETUP menu as shown in the
following example:
SETUP
1-Params
2-Ports
3-Clear
4-Advanced
1
3. Press
on the SID keypad to access the first in a series of eight
PARAMS edit forms as shown in the following example:
SETUP
Number of Ports
140
0
4. Enter the number of analog voice mail ports from worksheet A that the SID
must support for the INTUITY System.
5. Press
to confirm the number and move to the next basic parameter edit
form, the MSG DESK NUMBER form, as shown in the following example:
SETUP
Msg Desk Number:
001
8-2 Issue 2 December 1995
Administer the Basic Parameters
6. Enter the three-digit message desk number from worksheet A in Chapter
3.
7. Press
to confirm the number and move to the next basic parameter edit
form, the CPID PAD STRING form, as shown in the following example:
SETUP
CPID Pad String:
0000000
8. Press
to accept the default CPID Pad String number of 0000000 and
move to the next basic parameter edit form, the MWI PAD STRING form,
as shown in the following example:
SETUP
MWI Pad String:
0000000
9. Press
to accept the default MWI pad string number of 0000000 and
move to the next basic parameter edit form, the MWI FEATURE form, as
shown in the following example:
SETUP
MWI Feature:
ENABLE
<- ->1
10. Set the value for the message waiting feature as listed on worksheet A in
The SID defaults to Enable. If you want to turn off the feature, press the left
or right arrow key to change the value to Disable.
ENTER
11. Press
to confirm the information.
You have finished entering the MCI basic parameter information. To return to the
FUNC
MCI MAIN MENU, press
.
Proceed to the “Assign Extensions and LTNs” section on the next page to
continue the SID configuration.
Issue 2 December 1995 8-3
Switch Integration Device Administration
Assign Extensions and LTNs
As you assign extensions and LTNs, you associate an LTN (Centrex LTN) with
each analog extension number used by an INTUITY System. For each extension,
you must assign the same LTN to the extension as the INTUITY System assigns
to the extension. If you do not assign the same LTN, the SID does not integrate
calls properly. Read the section on the AutoFill feature before you assign
extensions and LTNs.
Use the following instructions to assign extensions and LTNs.
FUNC
1. To access the extension and LTN edit forms, press
keypad.
on the SID
After you press the key, you see the SETUP menu as shown in the
following example:
SETUP
1-Params
2-Ports
3-Clear
4-Advanced
2
2. Press
to select Ports and access the chain of forms used to enter and
edit extension and LTN information.
After you press the key, you see the VM PORT form as shown in the
following example:
VM Port 1
LTN:
0001
Extension:
------
The VM PORT0 form and the next series of forms link together. The
number of VM PORT0 forms linked together depends on the number you
entered on the NUMBER OF VOICE MAIL PORTS form in the “Basic
Parameters” section. If you entered 4, for example, the SID would link 4
VM PORT forms together.
3. If you do not want to use the default LTN, use the keypad to type an LTN
over the default. The sample screen uses an LTN of 0001.
In Chapter 3, you completed worksheet B, “Extension/LTN Plan.” Use
worksheet B as you enter LTNs and extensions.
ENTER
4. Press
to confirm the LTN. The cursor moves to the Extension field.
8-4 Issue 2 December 1995
Assign Extensions and LTNs
5. Use the keypad to type an extension for the LTN.
Use worksheet B as you enter LTNs and extensions.
NOTE:
Each VM PORT0 form contains a default LTN, starting with 0001. If
ENTER
you want to use the default, press
to select the default and
move the cursor to the Extension field. Enter the extension number
ENTER
for the LTN. Press
to confirm the number then press
to
move to the next form.
6. After you enter the extension, press
as shown in the following example:
to move to the next VM PORT form
VM Port 2
LTN:
0002
Extension:
211__
In the example, notice that the LTN default automatically increased by one
to 0002. You also can set the extension field to automatically increase by
using the Autofill feature. For more information on the Autofill feature, refer
to the section titled “Using AutoFill.”
7. Repeat steps 4 through 6 until you have entered an LTN and an extension
for each analog voice mail port.
8. After you have entered valid LTNs and extensions for all forms, press
FUNC
to return to the MCI MAIN MENU.
Using AutoFill
If you use consecutive extension numbers, numbers that increase by one, the
SID provides an AutoFill feature that automates the entry process. Using AutoFill,
you enter the first extension number on the first VM PORT form. As you move to
the next VM PORT form, AutoFill adds one to the extension you entered and
places the number in the Extension field.
Example: At the first VM PORT form for a four port configuration, you enter 210 in
the Extension field. After selecting AutoFill, you move to the next VM PORT form.
The SID adds one to the extension and places 211 in the Extension field. On the
next form, the SID places 212 in the field and 213 in the extension number field
on the fourth (last) form.
Issue 2 December 1995 8-5
Switch Integration Device Administration
Follow the instructions on the next page to use the AutoFill feature.
1. After accessing the first VM PORT form as instructed in the previous
section of this document, enter an extension number in the Extension field.
The following example uses 210 as the first extension number:
VM Port 1
LTN:
0001
Extension:
210__
2. Position the cursor on the extension number you entered.
3. Press the MODE key for editor help.
After you press the key, you see an editor help screen as shown in the
following example:
EDIT
1-Overtype
4-Undo
2-Insert
3-Clear
5-AutoFill
5
4. Press
to activate the AutoFill option. The SID now uses the number you
entered in the first extension field as the base number, adds one to the
number for each form, and places the new number in the extension fields
of the remaining forms. In the example, 210 was used as the first
extension number. AutoFill automatically places the extension numbers
211, 212, and 213 into the second, third and fourth forms and returns you
to the VM PORT form.
If only part of your extensions are numbered consecutively, you can still use the
AutoFill feature.
Example: You have a 12 port system. The five extension numbers from 100 to
104 are consecutive. After extension 104, your extensions skip to 200 and
continue consecutively to 206. To use the AutoFill feature, follow the regular
Autofill instructions for numbers 100 to 104. When you reach the form that
contains extension 105, move the cursor to the Extension field. Enter 200 in the
field and turn on AutoFill again. The SID places extensions 201 to 206 in the
remaining 6 edit forms.
You also can use AutoFill for LTN data. If you need to start your LTNs at 0010, for
example, enter 0010 into the first form. Turn on AutoFill. AutoFill enters 0011 and
up in the LTN fields of the remaining forms.
Continue to the procedure in the next section, “Saving and Starting the
Configuration.”
8-6 Issue 2 December 1995
Saving and Starting the Configuration
Saving and Starting the Configuration
After you administer the basic parameters and assign extensions and LTNs, you
must save the configuration. You also can start the integration at this point,
although you should perform the tasks in the “Administer Serial Data Links”
section to check the default settings for the MCI and SMDI communication links.
Use the following instructions to save the configuration and start the system.
FUNC
1. Press
on the SID keypad.
After you press the key, you see the SETUP menu.
FUNC
2. Press
again to return to the MAIN MENU.
After you press the key and return to the MAIN MENU, the SID checks the
current configuration against the information you entered. Because you
made changes to the configuration, the SID places the following prompt
on the screen:
SAVE EDITS?
1-Yes
2-No
1
3. Press
to select Yes and save your configuration changes.
After you press the key, the SID saves the information you entered and
shows the following message on the screen:
Setup Saved...
4. After a short pause, the SID places another prompt on the screen as
shown below:
START SYSTEM?
1-Yes
2-No
1
5. If you want to start the integration, press
to select Yes.
2
If you are not ready to start the integration, press
to select NO.
1
After you press
you see the Restarting System... message on the screen. The
SID pauses for a few seconds then starts the integration. When the integration
Issue 2 December 1995 8-7
Switch Integration Device Administration
starts, you see the SMDI VIEW MODE screen as shown in the following diagram.
below:
SMDI Idle
When the SID receives calls, the screen changes to show the SMDI packet being
sent to the INTUITY System.
The screen appears similar to the following example:
SMDI MWI:
CPID:
0OP:MWI 0000202!.
..MD0010001D 0000201 ...
“Administer Serial Data Links.”
Administer Serial Data Links
The SID assigns default configurations to both the MCI and SMDI communication
ports. You need to check the SID to make sure the defaults are set correctly and
match the requirements of your integration. The SID sets the defaults shown in
Table 8-1 for the serial data links.
Table 8-1. Serial Data Link Default Values
Link Type
Settings
SMDI:
1200 baud
7 data bits
1 stop bit
EVEN parity
1200 baud
7 data bits
1 stop bit
MCI:
EVEN parity
8-8 Issue 2 December 1995
Administer Serial Data Links
Use the following instructions to check or correct the default settings.
1. To access the edit forms used to change the serial data links, press
FUNC
to access the MCI MAIN MENU.
After you press the key, you see the MCI MAIN MENU as shown in the
following example:
NEC
1-View
2-Utils
5-Logs
3-System
4-Setup
2
2. Select Utils from the menu by pressing
on the SID keypad.
After you press the key, you see the UTILS menu as shown in the following
example:
UTILS
1-Login
2-Date/Time
3-Serial
3
3. Press
on the SID keypad to access the SERIAL menu.
After you press the key you see the SERIAL menu as shown in the
following example:
SERIAL
1-Centrex
2-MCI
4. Enter the menu item number of the serial data link you need to edit.
When you select MCI or Centrex (SMDI) from the menu, you access four
edit forms. Use the forms to set the serial data to the values your
2
application requires. For example, press
on the keypad.
NOTE:
Both the MCI and Centrex edit forms appear the same, except for
the edit form name. The MCI forms were chosen only as an
example in this document. You can select either serial data link or
both. You also can use the default values, as described earlier in
this section.
5. After you press the key, you see the BAUD RATE edit form as shown in the
following example:
MCI
Baud Rate:
1200
<- ->1
Issue 2 December 1995 8-9
Switch Integration Device Administration
6. To change the default value shown, press the left or right arrow key to
toggle through the optional values. The value you set for the baud rate
must equal the value set for the SID to the INTUITY System communication
link baud rate. Do not set two different values for these links. Stop
pressing the arrow keys when you find the value you want to use.
NOTE:
In Chapter 3 you completed worksheet A which contained lines for
the MCI baud rate and the SMDI baud rate. Refer to the worksheet
to review the baud rates you selected. For the INTUITY system, the
baud must be set to 2400.
7. After you select a baud rate, press
the next form.
to confirm your choice and move to
After you press enter, you see the PARITY form as shown in the following
example:
MCI
Parity:
EVEN
<- ->1
8. To change the default parity value shown in the field, press the left or right
arrow key to toggle through the optional values. Stop pressing the arrow
keys when you find the parity value you want to use.
9. After you select a parity, press
next form.
to confirm your choice and move to the
After you press enter, you see the BYTE LENGTH form as shown in the
following example:
MCI
Byte Length:
7 Bits
<- ->1
10. To change the default byte length shown in the field, press the left or right
arrow key to toggle through the optional values. Stop pressing the arrow
keys when you find the byte length you want to use.
11. After you select a byte length, press
to the last form.
to confirm your choice and move
After you press the key, you see the STOP BITS form as shown in the
following example:
MCI
Stop Bits:
1
<- ->1
8-10 Issue 2 December 1995
Changing System Parameters
12. To change the default stop bit value shown in the field, press the left or
right arrow key to toggle through the optional values. Stop pressing the
arrow keys when you find the stop bit value you want to use.
ENTER
13. After you select a stop bit value, press
to confirm your choice.
FUNC
14. Press
to return to the MCI MAIN MENU. If you need to reconfigure
the SMDI data link, return to step 2.
You have completed the MCI or SMDI configuration setup. The SID automatically
accepts and saves any information you change. Continue to the procedure in the
next section, “Changing System Parameters.”
Changing System Parameters
The SID provides access to some adjustable global system parameters. You can
change the following two parameters:
■
■
Time and date
LCD contrast setting
Use the instructions in this section to change the two system parameters.
Setting the Date and Time
Set the date and time when you install your SID system so error log messages
are properly timestamped. Although the date and time are set at the factory, you
may need to change the time to correct differences in time zones. Follow the
instructions below to set the date and time.
FUNC
1. Press
2. Press
3. Press
to access the MCI MAIN MENU.
to access the UTILITIES menu.
2
2
to access the DATE AND TIME form.
After you press the key, you see the DT/TM form as shown in the following
example. The cursor appears in the month field.
DT/TM
Date:
Time
11/18/91
15:35:00
4. Place the cursor on the Date field.
5. Enter the correct date in the format MM/DD/YY (month/day/year) by
ENTER
pressing
and typing the month, day, and year in each part of the
date field. If the date is correct, do not change the information and
proceed to the next step.
Issue 2 December 1995 8-11
Switch Integration Device Administration
ENTER
6. After you enter the year in the last date field, press
date and move the cursor to the Time field.
to confirm the
7. Enter the correct time in the format HH:MM:SS (hour:minute:second) by
ENTER
pressing
and typing the hour, minutes, and seconds in each part of
the time field. If the time shown is correct, proceed to the next step.
FUNC
8. Press
to return to the MCI MAIN MENU.
The SID accepts and uses the information. You do not have to save the
information or restart the integration. Continue to the next section, “Adjusting the
LCD Contrast.”
Adjusting the LCD Contrast
The LCD has a contrast adjustment edit form that you use to adjust the screen.
Follow the instructions below to adjust the LCD contrast.
FUNC
1. Press
2. Press
to access the MCI MAIN MENU.
3
to access the SYSTEM TOOLS menu.
After you press the key, you see the SYSTEM TOOLS menu as shown in
the following example:
SYSTEM
1-Info
4-Stop
2-Contrast
5-Reboot
3-Start
2
3. Press
to access the CONTRAST form.
After you press the key, you see the CONTRAST form as shown in the
following example:
CONTRAST 50%
<- ->
4. Change the setting by pressing the right and left arrow keys. As you press
the arrow keys, the display changes.
5. Stop pressing the arrow keys when you adjust the LCD to a comfortable
level.
FUNC
6. Press
to return to the MCI MAIN MENU.
Continue to the procedure in the next section, “Special Processing for Message
Waiting Lamps.”
8-12 Issue 2 December 1995
Special Processing for Message Waiting Lamps
Special Processing for Message
Waiting Lamps
NOTE:
The instructions in this section only can be performed by trained AT&T
software specialists.
The SID can buffer up to 4000 individual message waiting transactions and wait
for small intervals of time to perform the transactions. Incoming calls receive a
higher priority. If you use the Metrics View and discover that the SID is holding
large numbers of MWL transactions you can perform one of the following actions.
■
You can alter the MWL Interleave Factor. By decreasing the MWL
Interleave Factor, the speed of transactions out of the queue increases,
but call processing speed decreases. See the documentation supplied
with your switch for more information.
■
You can use the SID’s enhanced MWL processing. Continue with the
instructions in this section to use the enhanced MWL processing.
On a very active voice mail system, a subscriber can receive multiple messages
in a very short period of time. Each message turns on the MWL which quickly
increases the size of the buffer. Enhanced MWL handling insures that only a
single entry in the MWL queue is used for a specific subscriber, which reduces
the queue loading.
For example, an INTUITY System receives three MWL requests in rapid
succession. The first turns on John Smith’s lamp, the second turns off J. Doe’s
lamp, and the third turns on John Smith’s lamp. Each is a valid request and each
is queued for processing. John Smith’s lamp does not need to be lit twice,
however.
Enhanced MWL processing defaults to disabled and the SID queues and
processes all MWL requests in sequence. In the example above, all three
requests would be processed and John Smith’s lamp would be lit twice in quick
succession.
If you enable enhanced MWL processing, the MWL command for John Smith is
sent to the queue as a normal request. Any future requests for John Smith
overwrite the first, insuring that John’s lamp is only turned on once and set to the
state that the voice messaging system expects at the time of the operation. When
enhanced MWL processing is activated, the number of requests made by the
INTUITY System can be considerably larger than the actual number of
transactions undertaken by the SID.
Use the instructions on the next page to enable the enhanced MWL processing
feature.
Issue 2 December 1995 8-13
Switch Integration Device Administration
FUNC
1. Press
to access the SETUP menu as shown in the following
example:
SETUP
1-Params
2-Ports
3-Clear
4-Advanced
4
2. Press
to select the Advanced option. After you press the key, you see
the ADVNC screen as shown in the following example:
ADVNC
MWI Compress:
OFF
<- ->1
3. Use the left and right arrow keys to turn MWL Enhanced processing to
ON.
After you set enable MWL Enhanced processing, the SID automatically begins to
use the feature.
You do not have to save or restart the configuration. Continue to the procedure in
the next section, “Setting a Security Level.”
Setting a Security Level
The various features and functions of the SID are available only at specific
security levels. The list below shows each security level and the options available
to that level.
■
Access Level 0 — The lowest security level. The only options available to
level 0 are the ability to view integration activities, change the contrast on
the LCD display, see the software version level, and log in to other access
levels. The SID normally operates at level 0 and you do not need a
password to access level 0.
■
■
Access Level 1 — The second security level. Level 1 allows you to access
all level 0 features and all of the tools needed to administer the system.
The password for this level is the last five digits of your serial number.
Access Level 2 — The highest level of security. Level 2 allows you to
access all level 0 and level 1 features and several special diagnostic tools
available only to trained personnel. Only AT&T authorized personnel can
access this level, either on-site or remotely, to perform testing and
diagnostics on the SID. The password for this level is only given to
authorized personnel.
8-14 Issue 2 December 1995
Setting a Security Level
The factory sets the SID to access level 1. When you first power on the SID, the
unit accesses the SETUP menu and allows you to access all tools required to
perform the administration tasks. You can select a security level for the SID and
make the security level part of the configuration. AT&T recommends that you
select security level 0 as the normal operating mode for the SID. Users only can
access level 0 features, which reduces the risk of tampering by unauthorized
users.
Use the following instructions to set the security level on the SID.
FUNC
1. Press
to access the MAIN menu as shown in the following
example:
NEC
1-View
2-Utils
5-Logs
3-System
4-Setup
2
2. Press
to select the UTILS menu as shown in the following example:
UTILS
1-Login
2-Date/Time
3-Serial
1
3. Press
to select the LOGIN form as shown in the following example:
LOGIN
Access Level:
Password
1
<- ->0
4. Press the arrow (<- ->) keys to change the access level to 0.
ENTER
5. Press
to save the change. The SID immediately updates your
security level.
To log in to level 1, use the instructions above to access the LOGIN form. Use the
arrow keys to set Access Level to 1. The SID now asks you for a password. Type
ENTER
in the level 1 password and press
.
NOTE:
As you type the password, you do not see the letters on the screen.
Issue 2 December 1995 8-15
Switch Integration Device Administration
8-16 Issue 2 December 1995
Acceptance Tests
9
Do not perform any tasks in this chapter until you complete the required tasks in
the following appropriate documents:
■
■
■
■
Intuity MAP/5 Hardware Installation, 585-310-137
Intuity MAP/40 Hardware Installation, 585-310-138
Intuity MAP/100 Hardware Installation, 585-310-139
Intuity Software Installation, 585-310-140
The installation documents explain when you must use the instructions in this
chapter. If you have not performed the tasks in the installation documents,
complete the tasks now. This chapter explains how to administer the switch to
perform acceptance tests for the Intuity system.
Issue 2 December 1995 9-1
Acceptance Tests
As explained in INTUITY New System Planning, 585-310-603, two test
subscribers should have been administered on the switch for acceptance tests.
Acceptance tests begin after you complete initial administration and administer
two test subscribers on the INTUITY System. This chapter explains how to
administer two test subscribers on the NEAX 2400 MCI switch for performing
acceptance tests. If you have another type of switch, refer to the documentation
provided with that switch or the switch integration package for more information.
NOTE:
The MCI link controls the message waiting indication. Four- and
eight-button Dterm telephones have a message waiting lamp. On a
16-button Dterm telephone, you see VMMon the display to tell you that you
have voice mail. Analog (2500) sets require neon lamps and the switch
must have an auxiliary 90V power supply to operate the lamps.
Continue with the procedures in this chapter to administer the switch for
acceptance tests. Before you proceed, though, select two test extensions to use
for acceptance tests. Use the test subscribers listed in Intuiy New System
Planning, 585-310-603.
Administer the Test Subscribers
By forwarding a subscriber extension to the main extension of the Uniformed
Caller Distribution (UCD) group, the switch sends call information over the MCI
link to the SID. The SID converts and sends the information to the INTUITY
System. A call forwarded from the switch to the application is called an
integrated call. You can set the following call forwarding conditions:
■
■
■
Forward subscribers for ring-no-answer
Forward subscribers for busy conditions
Forward subscribers for all calls
For acceptance tests, activate all three conditions.
Task 1: Forward Calls for Ring-No-Answ er
Ring-No-Answer (RNA) refers to an unanswered call. After a specific length of
time, set on the switch, without the call being answered, the call transfers to the
UCD group assigned to the INTUITY System.
NOTE:
The test subscriber’s service feature class must contain call forward RNA
SFI=8. Dterm sets may have a function key for forward on busy (FKY=22).
For a station transferred blindly to a ring-no-answer station, the recall timer
takes priority over forward RNA. A call transferred to a busy extension
transfers back to the station that initiated the transfer.
9-2 Issue 2 December 1995
Administer the Test Subscribers
Use the following instructions to forward an RNA call for the test subscribers.
1. Using the phone of the first test subscriber, lift the handset and listen for
the dial tone.
2. Dial the access code or press the function key for forward RNA.
After you perform the action, you hear a second dial tone.
NOTE:
If you do not know the access code or the function key for forward
RNA, contact your switch administrator. The switch administrator
sets the codes and function keys during the initial setup of the
switch.
3. Dial the main extension of the UCD group to forward RNA calls to
integrated voice mail. You created the UCD main extension during the
After you complete the process, process to the next task, “Forward Calls for Busy
Conditions.”
Task 2: Forward Calls for Busy Conditions
Use this feature to forward a call when the extension is busy. When the switch
attempts to send a call and finds a busy extension, the switch transfers the call to
the INTUITY System.
NOTE:
The subscriber’s service feature class must contain call forward busy
SFI=9. Dterm sets may have a function key for forward on busy (FKY=1).
Use the following instructions to forward a busy call for acceptance tests.
1. Using the phone of the first test subscriber, lift the handset and listen for
the dial tone.
2. Dial the access code or press the function key for forward on busy.
After you perform the action you hear a second dial tone.
NOTE:
If you do not know the access code or the function key for forward
on busy, contact your switch administrator. The switch
administrator sets the codes and function keys during the initial
setup of the switch.
3. Dial the main extension of the UCD group to forward busy calls to
integrated voice mail. You created the UCD main extension during the
switch administration process in Chapter 7 of this document.
Issue 2 December 1995 9-3
Acceptance Tests
Task 3: Forward Subscribers for All Calls
Use this feature to forward all calls to the INTUITY System. The switch
automatically transfers the call to the UCD group administered for the INTUITY
System.
NOTE:
The subscriber’s service feature class must contain call forward RNA
SFI=7. Dterm sets may have a function key for forward on busy (FKY=2).
Use the following instructions to forward all calls for acceptance tests.
1. Using the phone of the first test subscriber, lift the handset and listen for
the dial tone.
2. Dial the access code or press the function key for forward all calls.
After you perform the action you hear a second dial tone.
NOTE:
If you do not know the access code or the function key for forward
all calls, contact your switch administrator. The switch administrator
sets the codes and function keys during the initial setup of the
switch.
3. Dial the main extension of the UCD group to forward all calls to integrated
voice mail. You created the UCD main extension during the switch
administration process in Chapter 7 of this document.
Repeat Task 1, 2, and 3 for the second test subscriber. After you administer all
features for both test subscribers, return to the “Acceptance Test” chapter in
INTUITY Software Installation, 585-310-140, and complete the acceptance test
procedures.
9-4 Issue 2 December 1995
Cut-to-Service
10
Do not perform any tasks in this chapter until you complete the necessary cut-to-
service tasks in the Cut-to-Service chapter of INTUITY System Software
Installation, 585-310-140. The installation document explains when you must use
the instructions in this chapter. If you have not performed the tasks in the
installation document, complete the tasks now.
This chapter explains how to administer the switch for the INTUITY system cut-to-
service process. Cutting over an INTUITY system requires you to change the
coverage path used by all subscribers. All INTUITY system initial administration,
switch administration, and acceptance tests must be completed before you cut
the system into service. To perform the cut-to-service process, you must perform
the following
Cutting to service on the NEAX 2400 MCI switch is a phone-based task. A
procedure must be performed at each subscriber telephone to administer the
extension on the switch. Although each telephone only requires administration
once, the process may require a large amount of time if you have a large
subscriber base.
Instead of having the system administrator perform the subscriber telephone
tasks, have each subscriber perform the task. Use an In-service letter to provide
instructions to the user for performing the tasks. Use the instructions in this
chapter to write the user instructions. Determine the best cut-to-service strategy
in advance and plan a time to administer the subscriber extensions.
NOTE:
When you cut the subscribers into service, all subscribers receive
INTUITY System service. You need to prepare the subscribers and train
the system attendants before you cut to service.
Issue 2 December 1995 10-1
Cut-to-Service
Administer the Subscriber Telephones
By forwarding a subscriber extension to the main extension of the UCD group,
the switch sends call information over the MCI link to the SID. The SID converts
the information to SMDI protocol and sends the information to the INTUITY
System. A call forwarded from the switch to an INTUITY System is called an
integrated call.
You can set three different call forwarding conditions, listed below, depending on
your needs or the needs of the individual subscribers.
■
■
■
Forward subscribers for ring-no-answer
Forward subscribers for busy conditions
Forward subscribers for all calls
Task 1: Forward Subscribers for Ring-No-Answer
Ring-No-Answer (RNA) refers to an unanswered call. After a specific number of
rings without the call being answered, the call transfers to the UCD group
assigned to the INTUITY System.
NOTE:
The subscriber’s service feature class must contain call forward RNA
SFI=8. Dterm sets may have a function key for forward RNA (FKY=22).
For a station transferred blindly to a ring-no-answer station, the recall timer
takes priority over forward RNA. A call transferred to a busy extension
transfers back to the station that initiated the transfer.
Use the following instructions to forward an RNA call for cut-to-service.
1. Using the subscriber telephone, lift the handset and listen for the dial tone.
2. Dial the access code or press the function key for forward RNA.
After you perform the action, you hear a second dial tone.
NOTE:
If you do not know the access code or the function key for forward
RNA, contact your switch administrator. The switch administrator
sets the codes and function keys during the initial setup of the
switch.
3. Dial the main extension of the UCD group administered for INTUITY
System service.
10-2 Issue 2 December 1995
Administer the Subscriber Telephones
You created the UCD main extension during the switch administration
calls to the INTUITY UCD group, creating an integrated voice mail system.
Proceed to the next task.
Task 2: Forward Calls for Busy Conditions
Use this feature to forward calls that reach busy extensions. When the switch
attempts to send a call and finds a busy extension, the switch transfers the call to
the UCD group assigned to the INTUITY System.
NOTE:
The subscriber’s service feature class must contain call forward busy
SFI=9. Dterm sets may have a function key for forward on busy (FKY=1).
Use the following instructions to forward a busy call.
1. Using the subscriber telephone, lift the handset and listen for the dial tone.
2. Dial the access code or press the function key for forward on busy.
After you perform the action you hear a second dial tone.
NOTE:
If you do not know the access code or the function key for forward
on busy, contact your switch administrator. The switch
administrator sets the codes and function keys during the initial
setup of the switch.
3. Dial the main extension of the UCD group administered for INTUITY
System service.
You created the UCD main extension during the switch administration
calls to the INTUITY UCD group, creating an integrated voice mail system.
Issue 2 December 1995 10-3
Cut-to-Service
Task 3: Forward Subscribers for All Calls
Use this feature to forward subscribers for all calls to the INTUITY System. The
switch automatically transfers the call to the UCD group administered for
INTUITY service.
NOTE:
The subscriber’s service feature class must contain call forward RNA
SFI=7. Dterm sets may have a function key for forward all calls (FKY=2).
Use the following instructions to forward all calls.
1. Using the subscriber telephone, lift the handset and listen for the dial tone.
2. Dial the access code or press the function key for forward all calls.
After you perform the action you hear a second dial tone.
NOTE:
If you do not know the access code or the function key for forward
all calls, contact your switch administrator. The switch administrator
sets the codes and function keys during the initial setup of the
switch.
3. Dial the main extension of the UCD group administered for INTUITY
System service.
You created the UCD main extension during the switch administration
to the application UCD group, creating an integrated voice mail system.
4. Repeat steps 1 through 3 for each subscriber extension that uses the
INTUITY System.
When you complete the station administration for all subscribers, return to the
“Cut-to-Service” chapter in INTUITY System Software Installation, 585-310-140,
and complete the cut-to-service procedure.
10-4 Issue 2 December 1995
Troubleshooting and Error Logs
A
Appendix A provides troubleshooting information to help you isolate and correct
problems that may occur with an INTUITY System integrated with the NEAX 2400
MCI switch. The problems outlined in this appendix only refer to problems related
to the integration device and processes. If you do not find your problem in this
appendix, refer to INTUITY Platform Administration and Maintenance, 585-310-
534, for more information.
Issue 2 December 1995 A-1
Switch Integration Device Problems
The SID does not power on.
Possible Reason:
The power cord connection may be loose or not
completed.
Remedy:
Make sure the power cord is firmly plugged into the
wall outlet and the SID.
Possible Reason:
Remedy:
The wall outlet may not have power.
Make sure the circuit breaker for the wall outlet is on.
The SID power switch may be set to the OFF position.
Turn the SID power switch to the ON position.
The SID may have a bad fuse.
Possible Reason:
Remedy:
Possible Reason:
Remedy:
Check the fuse on the SID.
Nothing appears on the LCD display.
Possible Reason:
Remedy:
You may need to adjust the LCD contrast.
Administration" for instructions on adjusting the LCD
contrast.
Calls are not integrated.
Possible Reason:
The cables between the SID and the INTUITY System
may not be connected correctly.
Remedy:
the cable connections.
Possible Reason:
Remedy:
The INTUITY System may not be administered
correctly.
Check the administration of the system using Chapter 6
of this document.
Possible Reason:
Remedy:
The SID may be administered incorrectly.
Administration", and check the administration of the
system. Make sure the channels and extensions are
configured correctly.
Possible Reason:
The baud rate for the SID-to-INTUITY System
connection may not be set correctly.
A-2 Issue 2 December 1995
Switch Integration Device Problems
Remedy:
Administration", and set the baud rate correctly.
Possible Reason:
Remedy:
The baud rate for the SID-to-PBX MCI connection may
not be set correctly.
Administration" and set the baud rate correctly.
Calls are integrated but the message waiting lamp (MWL) does not work.
Possible Reason:
The MWL may not be administered correctly on the
INTUITY System.
Remedy:
Check the administration of the system using Chapter
6 of this document
Possible Reason:
Remedy:
The packet format and MWL codes are set incorrectly
on the switch.
and set the information correctly.
Possible Reason:
Remedy:
The SMDI cable between the INTUITY System and the
SID may be defective.
Replace the cable.
You receive constant MWI Packet error messages.
Possible Reason:
Remedy:
The RS-232 MCI cable may be defective.
Replace the cable.
Possible Reason:
The baud rate and parity are not configured correctly
on the SID.
Remedy:
Administration" for instructions on configuring the baud
rate and parity for the MCI link and the SMDI link.
The LCD display contains the message Waiting for Remote Access.
Possible Reason:
You did not connect an analog phone line to the
modem port.
Remedy:
instructions on connecting an analog phone line to the
modem port.
Issue 2 December 1995 A-3
The VM LED is yellow constantly (more than 5% packet transmission error).
Possible Reason:
Remedy:
The SMDI cable is loose.
Tighten the SMDI cable connections.
Possible Reason:
The SMDI communications port baud rate, parity, and
other settings are not correct.
Remedy:
SMDI link.
Possible Reason:
Remedy:
The SMDI cable may be defective.
cable.
VM LED is red constantly (more than 50% packet transmission error).
Possible Reason:
Remedy:
The SMDI cable is loose.
Tighten the SMDI cable connections.
Possible Reason:
The SMDI communications port baud rate, parity, and
other settings are not correct.
Remedy:
Administration", for instructions on configuring the
SMDI link.
Possible Reason:
Remedy:
The SMDI cable may be defective.
Installation", for instructions on connecting the SMDI
cable.
A-4 Issue 2 December 1995
Error Logs
Error Logs
The SID accumulates and records or logs error messages. The error messages
can help solve problems and trace errors. You can access the error logs on the
SID if you are authorized to use security level 1 features.
The error logs also are available to trained support personnel to assist with
troubleshooting. Use the instructions in this section to log on to the SID and view
the error logs.
FUNC
1. Press
to access the MAIN MENU as shown in the following
example:
NEC
1-View
2-Utils
5-Logs
3-System
4-Setup
5
2. Press
to select Logs. After you press the key, you see the LOGS menu
as shown in the following example:
LOGS
1-View
2-Purge
0
1
3. Press
to view the error logs. After you press the key, you see the an
error log screen similar to the following example:
ER_LOG
16-Bad PBX Pkts > 5%000000000000000I
01/12 12:34 01/16 23:14000000000056
0
NOTE:
Your error log screens may appear different than the screen shown in the
example.
Issue 2 December 1995 A-5
Read the following explanation of the error log to understand the information.
16
The error code number used by AT&T support personnel
when they access the SID through the remote maintenance
modem.
No PBXPkts in
60 Secs
Informational text that provides a brief description of the
error. In the example, the SID wrote an informational
message indicating that no packets had been received
from the switch in the previous 60 seconds.
I
A letter that indicates the error type and severity. The error
messages can be informational (I), warning (W), or error (E)
types.
01/12_12:34
The date and time, rounded to the nearest minute, that the
error or warning first occurred.
01/16_23:14
56
The date and time the error or warning last occurred.
The number of times the SID produced the error or warning
between the first and last occurrence. The number tells you
the how frequently the errors occur. If you see a severe
error occurring frequently, contact your support
representative.
The SID can record many different errors. All errors are displayed in the same
format, explained in the above example. You may use the up arrow and down
and contains a description and action for each error code.
A-6 Issue 2 December 1995
Error Logs
Table A-1. SID Error Codes and Descriptions
Code
Description
Type
Action
1
VM Comm Error
W
W
W
W
W
W
E
W
W
I
Check SMDI connection and parameters
Check SMDI connection and parameters
Check SMDI connection and parameters
Check SMDI connection and parameters
Check SMDI connection and parameters
Check MCI connection and parameters
2
No Free VM_IN Packets
Excess Data -- VM_IN Pkts
Bad MWI Pkt
3
5
6
No Free Centrex Pkts
Excess Data - PBX_IN pkt
Kernel Error
10
11
12
13
15
16
17
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
No Free PBX_OUT Packets
Idle Task Not Enough Time
Bad PBX Pkts > 50%
Bad PBX Pkts > 5%
System Startup
Check MCI connection and parameters
Check MCI connection and parameters
Check MCI connection and parameters
No action required
I
I
System Powerdown
VM Comm Error > 5%
VM Comm Error > 50%
Boot Error: RTC
I
No action required
E
E
E
E
E
E
E
I
Check SMDI connection and parameters
Check SMDI connection and parameters
Set time and date
Boot Error: SCC
Boot Error: LED
Boot Error: Modem
Boot Error: DPRAM
Bad MWI Pkts > 50%
Bad MWI Pkts > 5%
PBX Comm Error > 5%
PBX Comm Error > 50%
Bad PBX Packet
Check SMDI connection and parameters
Check SMDI connection and parameters
Check MCI connection and parameters
Check MCI connection and parameters
Check MCI connection and parameters
I
E
E
W
E
I
Hardware Watchdog Reboot
Integration Stop
No action required
Integration Start
I
No action required
No Free PBX_IN Packets
Hardware Reset
W
I
Check MCI connection and parameters
No action required
VM Remote Reset
I
No action required
Software Reset
I
No action required
Issue 2 December 1995 A-7
From time to time, you may need to purge your error logs. You can purge error
logs on the SID if you have authorization to access security level 1 features. Use
the following instructions to purge error logs.
FUNC
1. Press
2. Press
to access the Main Menu.
5
to select Logs. After you press the key, you see the Logs menu
as shown in the following example:
LOGS
1-View
2-Purge
0
2
3. Press
to select Purge. After you press the key, you see the screen
shown in the following example:
PURGE LOGS?
1-Yes
2-No
0
2
4. Press
Press
to cancel the purge. The SID save the error logs.
to erase the error logs.
1
The SID starts to record new error messages after you purge the old logs.
After the SID completes the purge, you see the following message on the
screen:
Purging Logs...
0
A-8 Issue 2 December 1995
Clearing Your Configuration
Clearing Your Configuration
When you add voice mail ports or change the switch dial plan, you may need to
reconfigure the SID. In most cases, you can accomplish the task by editing the
existing setup and restarting the system. If required, the SID provides the
capability to restore the factory default settings.
To clear your configuration and restore the factory setting, use the following
instructions.
FUNC
1. Press
2. Press
to access the Main Menu.
4
to select the Setup option. After you press the key, you see the
SETUP menu as shown in the following example:
SETUP
1-Params
2-Ports
3-Clear
4-Advanced
0
3
3. Press
to select Clear. After you press the key, you see the Clear Setup
screen as shown in the following example:
CLEAR SETUP?
1-Yes
2-No
0
2
4. Press
Press
to cancel the clear and return to the SETUP menu.
1
to restore the factory default settings. When you clear your
configuration, you remove all global parameter information, dial plan,
logical terminal number information, and SMDI and MCI serial port
information. The contrast and Enhanced MWI handling settings are
restored to the factory defaults. The only information preserved are your
error logs and statistical tables. Using the clear command stops the
integration. You must configure and start the system to integrate calls.
Issue 2 December 1995 A-9
A-10 Issue 2 December 1995
Using Views During Integration
B
The SID provides you with four real-time views of the integration process:
■
■
■
■
SMDI monitor mode
MCI monitor mode
Statistics mode
Metrics mode
Each mode shows you different information in a common screen layout. A typical
view mode appears as shown in the following example:
SMDI MWI:
CPID:
0OP:MWI 0000202
..MD0010001D 0000201...
View modes remain on the screen, constantly changing as calls and message
waiting transactions are processed. Use the information in this appendix to
access and use the view modes.
Issue 2 December 1995 B-1
SMDI Monitor Mode
The first option on the View menu is the SMDI monitor mode. The mode permits
you to observe transactions as they occur on the SMDI data link that connects
the SID to the INTUITY System. The SMDI monitor is a useful tool that provides
condensed, real-time reporting of all transactions on the SMDI data link. The
SMDI link connects the SID to the INTUITY System. The view is set as the default
display mode for a configured SID. When the system first boots up and is idle,
the display appears as shown in the following example:
SMDI Idle
Use the following instructions to access the SMDI monitor mode.
1
1. At the NEC Main Menu, press
following screen:
to select the View option. You see the
VIEW
1-SMDI
2-MCI
3-Stats
4-Metrics
1
2. Press
to select the SMDI option and access the SMDI0 view screen as
shown in the following example:
SMDI MWI
CPID
..MD0010002B0000201 0000202...
MODE
3. To exit the SMDI view screen, press
Menu.
to return to the NEC Main
B-2 Issue 2 December 1995
SMDI Monitor Mode
When transactions are being processed, the screen updates continuously. The
example SMDI view screen above shows a call covered to the pilot number of the
UCD group. The following descriptions explain the content of each field. Each
type of view screen contains similar fields.
CPID
The bottom line of the display is reserved for calling
party ID packets, or information about the call that the
INTUITY System is about to answer.
MD0010002
The number notifies the INTUITY System that the
calling party information is specific to message desk 1
and logical terminal number (LTN) 2. This permits the
appropriate mail box to be opened on the correct
analog voice mail port.
B0000201 0000202
The information represents calling and called party
information. In this case, extension 201 called a busy
extension 202. The call covered to the UCD group
pilot number. The caller at extension 201 listens to the
personal greeting for mailbox 202.
When the SID processes a message waiting command, the screen appears as
shown in the following example:
SMDI MWI:
RMV:MWI 0000201!.
The example indicates that the message waiting lamp at extension 201 has been
turned on. Since the SID preserves the most recent CPID or MWI transaction on
the screen, you can see a mix of information on the screen, as shown in the
following example:
SMDI MWI:
CPID:
0OP:MWI 0000202!.
..MD0010001D 0000201 ...
If you attempt to use the view monitor before configuring the SID, the warning
shown below appears on your screen. You must first configure your system
before you use the view modes.
SMDI Integration Stopped
Issue 2 December 1995 B-3
Using MCI Monitor Mode
The SID provides an MCI data link monitor that allows you to view transactions
sent between the switch and the SID. This view is similar in format to the SMDI
Monitor. The top line on the display shows message waiting commands and the
bottom line shows calling party data. Use the following instructions to use the
MCI monitor view:
1. Access the View menu as described in the previous section.
MODE
2. Press
3. Press
.
2
to select the MCI option. You see the following screen.
MCI .0!B230100000001.
The display updates as packets are transmitted and received on the MCI data
link. You see the Idle message and the Integration Stopped message under the
same circumstances as in the SMDI monitor mode.
Using Statistics Mode
Use the following instructions to use the Statistics monitor mode.
1. Access the View menu as described in the previous section.
MODE
2. Press
3. Press
.
3
to select the Statistics oiopnt . You see the following screen.
STATS
Calls:
MWIs:
978 BdPkts:
4
456 BdMWIs: 3 Q: 120-03%
The screen updates continuously, showing the total number of calls processed
and the number of bad packets received from the switch. The screen also shows
the total number of message waiting commands processed, the number of bad
MWI packets received from the INTUITY System, and the total number of MWI
commands residing in the SID’s queue. Use the Statistics mode to monitor
activity on your integrated system.
B-4 Issue 2 December 1995
Using Metrics Mode
Using Metrics Mode
Use the following instructions to use the Metrics monitor mode.
1. Access the View menu as described in the previous section.
MODE
2. Press
3. Press
.
4
to select the Statistics oiopnt . You see the following screen:
METRICS
Calls/Hr:
MWIs/Hr:
12001
9071
This display updates occasionally, showing performance measurements for both
the SID’s call processing and message waiting activities. The top line shows a
running average for the number of calls serviced by the INTUITY System per
hour. The bottom line shows a similar statistic for the number of message waiting
commands serviced by the SID per hour. Use the Metric mode to monitor the
performance characteristics of your integrated system.
Clearing Statistical Information
The SID accumulates data that supports the Statistics and Metrics views. You
may wish to purge the data to begin taking new measurements, especially when
you add subscribers to the system, analog voice mail ports, or change your
usage habits. To clear the data, use the following instructions.
1. Log into security level 1. For instructions on logging in to the security level,
MODE
2. Press
at the VIEW action form.
5
3. Press
to select Clear and remove the old statistics. After you press the
key, you see the following message on the screen:
Clearing Statistics...
The SID clears all statistical information. After a few seconds, the display clears
and the SID returns to the View menu.
Issue 2 December 1995 B-5
B-6 Issue 2 December 1995
Switch Administration for INTUITY
Lodging
C
Introduction
Appendix C describes the switch administration you need to complete if you
have INTUITY Lodging. Read the information and configure your switch as
required.
Hunt Group Administration
A hunt group is a set of extension numbers assigned to another phone number.
When a call is received by this number, a programmed search of the hunt group
is made and the call is forwarded to a member of the hunt group that is not busy.
For example, when two calls are made to the designated phone number, both
are forwarded to two free extensions in the hunt group. Hunt groups are a
commonly-used switch feature. Your switch probably has some hunt groups
already assigned.
In order to configure a hunt group for calls being received by the INTUITY system
you must:
1. Administer your switch to create a hunt group for your INTUITY system.
2. Have the switch ports that terminate the hunt group extensions wired to
the voice ports on the INTUITY platform. Wire them as described in one of
the following documents, depending on your system:
■
■
■
INTUITY™ MAP/5 Hardware Installation, 585-310-146
INTUITY™ MAP/40 Hardware Installation, 585-310-138
INTUITY™ MAP/100 Hardware Installation, 585-310-139
Issue 2 December 1995 C-1
Message Retrieval Administration
The message retrieval number is the telephone number that subscribers call to
retrieve voice mail messages. Like other calls to the INTUITY system, message
retrieval calls are ultimately forwarded to the INTUITY hunt group.
Message Retrieval in Lodging Systems
without AUDIX
Provide the INTUITY system’s message retrieval number to your subscribers.
Message Retrieval in Systems Shared with
AUDIX
There must be two message retrieval numbers in a shared system, one to
retrieve from the AUDIX application, and one to retrieve from the Lodging
application.
Retrieval from the AUDIX Application
Provide the INTUITY system message retrieval number to your subscribers for
the AUDIX application.
Retrieval from the Lodging Application
1. Administer on your switch an extension number not associated with a
switch port. (These are often called phantom or dummy numbers.) This
number becomes the Lodging message-retrieval number for your system.
2. Configure the Lodging message retrieval number so that the INTUITY hunt
group covers all calls.
3. Provide the Lodging message retrieval number to your subscribers for the
Lodging application.
Alternate Message Retrieval Method
Guests can also be allowed to log on from a remote phone to any mailbox for
which they have a password. A guest will call a number to access this service
then enter an extension number and a password to retrieve messages in the
mailbox.
To provide this service:
1. Administer on your switch a phantom number. This is the message
retrieval number used from a remote phone.
2. Configure the phantom number so the INTUITY system hunt group covers
all calls.
C-2 Issue 2 December 1995
Voice Mail Administration
3. If your switch has password capability, assign a password to the new
extension.
4. Assign to the new extension, the service: ldg_ni_vm
a. Log on to the INTUITY system as sa or craft.
b. From the INTUITY Administration menu select the following
sequence:
>Voice System Administration
Voice Equipment
CHG-KEYS
c. From the Voice Equipment screen, press
(F8) then
ASSIGN
(F3).
d. Select Services to Called Numbers from the Assign menu.
e. Press (F2) and select ldg_ni_vm.
CHOICES
f. Enter the called number that was administered on the switch for this
purpose.
SAVE
g. Press
(F3). A command-output screen appears confirming
your choice.
CANCEL
h. Press
screen.
(F6) three times to exit to the Voice Equipment
5. If the phantom extension is to be accessed from outside your system,
assign the extension to a Direct-Inward-Dialing number.
6. Provide the Lodging message retrieval number to your subscribers for the
Lodging application.
Voice Mail Administration
Voice mail is enabled when the switch sends a guest’s call to a coverage path.
The following procedure, however, provides a separate number that can be used
at any time to send voice mail to a guest.
To provide this service:
1. Administer on your switch a phantom number. This number is used to
send voice messages to your subscribers.
2. Configure the phantom number so that the INTUITY system hunt group
covers all calls.
Issue 2 December 1995 C-3
3. Assign to the new extension, the service: ldg_ni_ca as follows:
a. Log on to the INTUITY system as sa or craft.
b. From the INTUITY Administration menu select the following
sequence:.
>Voice System Administration
Voice Equipment
CHG-KEYS
c. From the Voice Equipment screen, press
(F8) then
ASSIGN
(F3).
d. Select Services to Called Numbers from the Assign menu.
e. Press (F2) and select ldg_ni_ca
CHOICES
f. Enter the called number of your choice.
SAVE
g. Press
(F3). A command-output screen appears confirming
your choice.
CANCEL
h. Press
screen.
(F6) three times to exit to the Voice Equipment
4. If the phantom extension will be accessed from outside your system,
assign the extension to a Direct-Inward-Dialing number.
5. Provide the Lodging voice mail number to subscribers for the Lodging
application.
Call Coverage Path
A coverage path directs the switch to transfer unanswered calls to a hunt group,
to a service, or to another extension.
When a call goes to coverage, the switch forwards the called number to the
INTUITY system. The INTUITY system detects that the called number is
administered as a specific subscriber’s extension and treats the call as one to be
answered and recorded. Depending on how the extension is configured, the call
may be answered by either the AUDIX or the Lodging application.
1. Administer your switch to assign call coverage for each guest’s extension
to the associated INTUITY system hunt group number.
C-4 Issue 2 December 1995
Do-Not-Disturb
Do-Not-Disturb
Look for features on your switch that adapt themselves especially well to lodging
situations. One example is the Do-not-Disturb feature on some switches. This
feature makes it possible to request that a particular extension not receive calls
until a specified time. At the specified time, the switch automatically deactivates
the feature and allows calls to terminate normally at the extension.
If this extension is covered by the INTUITY system hunt group, then calls
received while Do-Not-Disturb is active will be recorded for later retrieval.
Cut-to-Service
A cut-to-service of the INTUITY Lodging application amounts to changing the
coverage path for each guest extension to the INTUITY system hunt group. The
associated system must be completely installed before you cut the INTUITY
Lodging application into service. Furthermore, all INTUITY system initial
administration, associated switch administration, and acceptance tests must be
completed.
Some switching systems make it possible to group these extensions as a set
allowing the coverage path to be changed simultaneously. Most switching
systems permit changing the coverage path for guest extensions one extension
at a time. You may use either method.
Gradual Cut-to-Service
Using this cut-to-service strategy, enter guests into the INTUITY Lodging system
as they check in. Only new guests, not current guests, receive INTUITY Lodging
services.
The advantages of this method include:
■
Attendants can learn the new system while only a portion of guests are
also learning to use it.
■
Guests do not have to learn both the previous and the new systems.
Current guests use the previous system; new guests use the INTUITY
Lodging system.
■
Custom passwords and language options can be assigned to each guest
as the guest is checked in.
Gradually cut-to-service as follows:
1. Administer your switch to send the guests’ telephone call coverage to the
INTUITY system hunt group.
2. Check in each new guest as described in INTUITY Lodging Administration
and Feature Operations, 585-310-559.
Issue 2 December 1995 C-5
One-Step Cut-to-Service
On switches where a coverage path is separately defined and then applied to a
class of stations, assign all guest stations to INTUITY Lodging at once.
Using this cut-to-service strategy, all guest stations are changed to INTUITY
Lodging at the same time.
The advantages of this method include:
■
■
■
Since INTUITY Lodging is brought up in one step, attendants must cope
with only one call-answering system at a time.
Cut-to-service is over at once. Multiple messaging systems can confuse
the guests.
Reasonable coverage options can be assigned to all guests at once;
administration can be modified for the few that have unusual
requirements.
Cut-to-service as follows:
1. Use INTUITY Lodging to administer the options that guests require.
2. Make sure guests and attendants know when the change will take place
and have some idea of how the new service operates.
3. On your switch, determine the coverage path that applies to your guests’
stations.
4. On your switch, set the new coverage path for your guests’ stations to the
INTUITY system hunt group.
Summary
You have completed the switch integration tasks necessary to configure your
INTUITY system for the Lodging application.
C-6 Issue 2 December 1995
Abbreviations
C
CCA
call classification analysis
A
CDH
call data handler process
CELP
AC
alternating current
code excited linear prediction
ACD
automatic call distribution
CIC
customer information center
CICS
ADAP
administration and data acquisition package
ADU
customer information control system
asynchronous data unit
CNT
count
ALT
assemble load and test
AMIS
CO
central office
Audio Messaging Interchange Specification
COIN
central office implemented network
COM1
AT&T
American Telegraph and Telephone
AUDIX
serial communications port 1
Audio Information Exchange
COM2
serial communications port 2
COR
AWG
American wire gauge
class of restriction
COS
class of service
CPID
B
BIOS
basic input/output system
calling party identification pad
CPU
bps
central processing unit
CTS
bits per second
BRI
clear to send
basic rate interface
BSC
binary synchronous communications
BTU
British thermal unit
Issue 2 December 1995 ABB-1
Abbreviations
D
E
DAC
EIA
dial access code
Electronic Industries Association
DC
ESD
direct current
electrostatic discharge
ESS
DCE
data communications equipment
electronic switching system
DCIU
EXT
data communications interface unit
Extension
DCP
digital communications protocol
DCS
F
distributed communications system
FACE
DID
framed access command environment
direct inward dialing
FIFO
DIP
first-in first-out
FOOS
data interface process
DMA
facility out of service
direct memory access
FMLI
DN
form and menu language interpreter
FKY
directory number
DNIS
function key
dialed number identification service
DSP
digital signal processor
G
DSU
data service unit
GBCS
DTE
Global Business Communications Systems
data terminal equipment
DTMF
dual tone multifrequency
H
DTR
data terminal ready
Hz
hertz
ABB-2 Issue 2 December 1995
Abbreviations
I
M
IDI
MANOOS
isolating data interface
manually out of service
IMG
Mbyte
Interface Module Group
megabyte (one million bytes)
MCI
INADS
initialization and administration system
Message Center Interface
I/O
MD
input/output
Message Desk
MHz
IRQ
interrupt request
megahertz
ISDN
MMG
integrated services digital network
multi-module group
modem
IVC6
integrated voice CELP card (6 channels)
modulator/demodulator
MPDM
modular processor data module
ms
K
millisecond
Kbps
MT
kilobits per second
maintenance (INTUITY™ software component)
Kbyte
MTBF
mean time between failures
kilobyte (1024 bytes)
kHz
MWI
message-waiting indicator
kilohertz
L
N
LCD
NW
liquid crystal display
INTUITY AUDIX Digital Networking
LED
light-emitting diode
LENS
logical equipment number
LTN
logical terminal number
LWC
leave word calling
Issue 2 December 1995 ABB-3
Abbreviations
RSC
route restriction class
O
RTS
request to send
OA&M
operations, administration, and maintenance
RTU
right to use
OP
operate
OS
operating system
S
SCSI
small computer systems interface
P
SID
switch integration device
SFC
PBX
private branch exchange
service feature class
PC
power converter or personal computer
SFI
service feature index
PDM
processor data module
SIMM
single in-line memory module
SMDI
PEC
price element code
simplified message desk interface
POST
power-on self test
SMSI
simplified message service interface
STN
station
R
STRC
RAM
Sales and Technical Resource Center
random-access memory
SW
REN
switch integration (INTUITY software component)
ringer equivalence number
SYS
RMV
system
remove
RNA
ring-no-answer
ROM
read-only memory
ABB-4 Issue 2 December 1995
Abbreviations
T
TDD
telecommunications device for the deaf
TDM
time division multiplex
TEC
telephone class
TN
tenant number
T/R
tip/ring
TRIP
tip/ring input process
TSC
AT&T's Technical Services Center
U
UCD
uniform call distribution
UMG
ultra-module group
UPS
uninterruptible power supply
V
VM
INTUITY AUDIX Voice Messaging
VP
voice platform (INTUITY software component)
VR
INTUITY Intro Voice Response
VROP
voice response output process
Issue 2 December 1995 ABB-5
Abbreviations
ABB-6 Issue 2 December 1995
Glossary
1A ESS Switch
An AT&T central office switch that can be integrated with the INTUITY system.
5ESS Switch
An AT&T central office switch that can be integrated with the INTUITY system.
A
accessed message
A voice mail message that was received and scanned (either the entire message or just the
header).
ACD
See automatic call distribution.
activity menu
The list of options voiced to INTUITY AUDIX subscribers when they first access the system.
Selecting an activity is the starting point for all user operations.
ADAP
See administration and data acquisition package.
address
INTUITY AUDIX subscriber identification, containing the subscriber’s extension and machine, that
indicates where the system needs to deliver a voice mail message. An address may include sev-
eral subscribers or mailing lists. Name or number addressing can be selected with the *A com-
mand.
adjunct
A separate system closely integrated with a switch, such as an INTUITY system or a call manage-
ment system (CMS).
administration
The process of setting up a system (such as a switch or a voice messaging system) to function as
desired. Options and defaults are normally set up (translated) by the system administrator or ser-
vice personnel.
administration and data acquisition package (ADAP)
A software package that allows the system administrator to transfer system subscriber, mainte-
nance, or traffic data from an INTUITY AUDIX system to a personal computer (PC).
ADU
See asynchronous data unit.
alarm log
A list of alarms that represent all of the active or resolved problems on an INTUITY system. The
alarm log is stored in a software file on disk and can be accessed either locally or remotely on a
terminal connected to the system.
alarms
Hardware, software, or environmental problems that may affect system operation. Alarms are
classified as major, minor, or warning.
Issue 2 December 1995 GL-1
Glossary
alphanumeric
Alphabetic, numeric, or punctuation symbols.
AMIS
See Audio Messaging Interchange Specification.
AMIS Prefix
A number added to the destination number to indicate that the destination number is an AMIS
analog networking number.
ampere (amp)
The unit of measurement of electric current. One volt of potential across one ohm causes a cur-
rent flow of one amp.
analog networking
A method of transferring a voice mail message from one voice messaging system to another
whereby the message is played back (voiced) during the transmission from one system to
another.
analog signal
A communications path that, in teleprocessing usage, usually refers to a voice-grade telephone
line.
announcement fragment
A numbered piece of spoken information that makes up a system message or prompt.
antistatic
A material that is treated to prevent the build-up of static electricity.
asynchronous communication
A method of data transmission in which bits or characters are sent at irregular intervals and bits or
characters are spaced by start and stop bits and not by time. See also synchronous communica-
tion.
asynchronous data unit (ADU)
An electronic communications device that can extend data transmission over asynchronous lines
more than 50 feet in length. Recommended ADUs include Z3A1 or Z3A4.
asynchronous transmission
A form of serial communications where each transmitted character is bracketed with a start bit
and one or two stop bits. The INTUITY system provides asynchronous RS-232 capabilities for
INTUITY AUDIX Digital Networking, if required.
Audio Messaging Interchange Specification (AMIS)
An analog networking feature that allows subscribers to exchange voice mail messages with any
voice messaging system that also has AMIS Analog Networking capabilities. Messages can be
exchanged with subscribers on INTUITY systems as well as with users on remote voice messag-
ing systems made by vendors other than AT&T.
Audio Information Exchange (AUDIX)
A complete voice messaging system accessed and operated by touch-tone telephones and inte-
grated with a switch.
audit
A software program that resolves filesystem incompatibilities and updates restored filesystems to
a workable level of service. Audits are done automatically on a periodic basis, or can be per-
formed on demand.
GL-2 Issue 2 December 1995
Glossary
AUDIX
See Audio Information Exchange.
automated attendant
A feature that allows a user of an INTUITY system to set up a main extension number with a menu
of options that routes callers to an appropriate department at the touch of a button.
automatic call distribution (ACD)
The System 85, Generic 2, or Generic 3 call-distribution group of analog ports that connects
INTUITY subscribers and users to the system. See also call-distribution group.
automatic message scan
An INTUITY AUDIX feature that allows subscribers to scan all message headers and messages at
the touch of two buttons.
B
background testing
Testing that runs continuously when the system is not busy doing other tasks.
backup
A duplicate copy of files and directories saved on a removable media such as floppy diskette or
tape. The backup filesystem may be copied back (restored) if the active version is damaged
(corrupted) or lost.
basic input/output system (BIOS)
A system that contains the buffers for sending information from a program to the actual hardware
device the information should go to.
baud
A unit of measurement that describes the speed of transferred information.
baud rate
Transmission signaling speed.
basic call transfer
A switchhook-flash method used to send the INTUITY AUDIX transfer command over analog
voice ports.
basic rate access
See basic rate interface.
basic rate interface (BRI)
International standard protocol for connecting a station terminal to an integrated systems digital
network (ISDN) switch. ISDN BRI supports two 64 Kbps information bearer channels (B1 and B2),
and one 16 Kbps call status and control (D) channel (a 2B + D format). Also called basic rate
access.
binary digit (bit)
Two-number notation that uses the digits 0 and 1. Low-order bits are on the right (for example,
0001=1, 0010=2, and so forth). Four bits make a nybble; eight bits make a byte.
binary synchronous communications (BSC)
A character-oriented synchronous link protocol.
Issue 2 December 1995 GL-3
Glossary
BIOS
See basic input/output system.
bit
See binary digit.
body
The part of subscriber voice mail that contains the actual spoken message. For a leave word call-
ing (LWC) message, it is a standard system announcement.
boot
The operation to start a computer system by loading programs from disk to main memory (part of
system initialization). Booting is typically accomplished by physically turning on or restarting the
system. Also called reboot.
boot filesystem
The filesystem from which the system loads its initial programs.
bps (bits per second)
The number of binary units of information (1s or 0s) that can be transmitted per second. Mbps
refers to a million bits per second; Kbps refers to a thousand bits per second.
BRI
See basic rate interface.
broadcast messaging
An INTUITY AUDIX feature that enables the system administrator and other designated users to
send a voice mail message to all subscribers automatically.
BSC
See binary synchronous communications.
buffer
Memory used to compensate for time differences in transmission by temporarily storing data.
bulletin board
An INTUITY AUDIX feature that allows a message to be played to callers who dial the extension.
Callers cannot leave a message since it is a listen-only service. Also called information service.
bus
An electrical connection/cable allowing two or more wires, lines, or peripherals to be connected
together.
busy-out/release
To remove an INTUITY device from service (make it appear busy or in use), and later restore it to
service (release it). The INTUITY switch data link, voice ports, or networking ports may be busied
out if they appear faulty or if maintenance tests are run.
byte
A unit of storage in the computer. On many systems, a byte is eight bits (binary digits), the equiv-
alent of one character of text.
GL-4 Issue 2 December 1995
Glossary
C
call-answer
An INTUITY AUDIX feature that allows the system to answer a call and record a message when
the subscriber is unavailable. Callers may be redirected to the system through the call coverage
or call forwarding switch features. Subscribers may record a personal greeting for these callers.
callback number
In AMIS analog networking, the telephone number transmitted to the recipient machine to be
used in returning voice mail messages that cannot be delivered.
call coverage
A switch feature that defines a preselected path for calls to follow if the first (or second) coverage
points are not answered. The INTUITY system may be placed at the end of a coverage path to
handle redirected calls through call coverage, send all calls, go to cover, etc.
call-distribution group
The set of analog port cards on the switch that connects subscribers and users to the INTUITY
system by distributing new calls to idle ports. This group (or split) is called automatic call distribu-
tion (ACD) on System 85, Generic 2, and Generic 3 and uniform call distribution (UCD) on System
75, Generic 1, and Generic 3. See also automatic call distribution and uniform call distribution.
call vectoring
A System 85 R2V4, Generic 2, and Generic 3 feature that uses a vector (switch program), allow-
ing a switch administrator to customize the behavior of calls sent to an automatic call distribution
(ACD) group.
card cage
An area within the INTUITY hardware platform that contains and secures all of the standard and
optional circuit cards used in the system.
cartridge tape drive
A high-capacity data storage/retrieval device that can be used to transfer large amounts of infor-
mation onto high-density magnetic cartridge tape based on a predetermined format. This tape is
to be removed from the system and stored as a backup.
central office (CO)
An office or location in which large telecommunication machines such as telephone switches and
network access facilities are maintained. In a CO, private customer lines are terminated and con-
nected to the public network through common carriers.
central processing unit (CPU)
The component of the computer that manipulates data and processes instructions coming from
software.
channel capacity
A measure of the maximum bit rate through a channel.
class of service (COS)
The standard set of INTUITY AUDIX features given to subscribers when they are first adminis-
tered (set up with a voice mailbox).
clear to send (CTS)
Located on Pin 5 of the 25-conductor RS-232 interface, CTS is used in the transfer of data
between the computer and a serial device.
Issue 2 December 1995 GL-5
Glossary
CO
See central office.
collocated
An INTUITY system installed in the same physical location as the host switch. See also local
installation.
collocated adjunct
Two or more adjuncts that are serving the same switch (i.e., each has voice port connections to
the switch) or that are serving different switches but can be networked through a direct RS-232
connection due to their proximity.
comcode
AT&T’s numbering system for telecommunications equipment. Each comcode is a nine digit
number that represents a specific piece of hardware, software, or documentation.
command
An instruction or request given by the user to the software to perform a particular function. An
entire command consists of the command name and options. Also, one- or two-key touch tones
that control a voice mailbox activity or function.
configuration
The particular combination of hardware and software components selected for a system, includ-
ing external connections, internal options, and peripheral equipment.
controller circuit card
A circuit card used on a computer system that controls its basic functionality and makes the sys-
tem operational. These cards are used to control magnetic peripherals, video monitors, and
basic system communications.
COS
See class of service.
CPU
See central processing unit.
cross connect
Distribution system equipment used to terminate and administer communication circuits.
cross connection
The connection of one wire to another, usually by anchoring each wire to a connecting block and
then placing a third wire between them so that an electrical connection is made.
CTS
See clear to send.
GL-6 Issue 2 December 1995
Glossary
D
database
A structured set of files, records, or tables. Also, a collection of filesystems and files in disk mem-
ory that store the voice and nonvoice (program data) necessary for INTUITY system operation.
data communications equipment (DCE)
Standard type of data interface normally used to connect to data terminal equipment (DTE)
devices. DCE devices include the data service unit (DSU), the isolating data interface (IDI), and
the modular processor data module (MPDM).
data communications interface unit (DCIU)
A switch device that allows nonvoice (data) communication between an INTUITY system and an
AT&T switch. The DCIU is a high-speed synchronous data link that communicates with the com-
mon control switch processor over a direct memory access (DMA) channel that reads data
directly from FP memory.
data link
A term used to describe the communications link used for data transmission from a source to a
destination. For example, a phone line for data transmission.
data service unit (DSU)
A device used to access digital data channels. DATAPHONE II 2500 DSUs are synchronous data
communications equipment (DCE) devices used forextended-local INTUITY system connections.
The 2600 or 2700 series may also be used; these are more expensive DSU options and support
diagnostic testing and the DATAPHONE II Service network system.
data set
AT&T term for a modem. A data set usually includes the telephone. See also modem.
data terminal equipment (DTE)
Standard type of data interface normally used for the endpoints in a connection. Normally the
INTUITY system, most terminals, and the switch data link are DTE devices.
data terminal ready (DTR)
A control signal sent from the data terminal equipment (DTE) to the data communications equip-
ment (DCE) that indicates the DTE is on and ready to communicate.
DBP
See data base processor.
DCE
See data communications equipment.
DCIU
See data communications interface unit.
DCP
See digital communications protocol.
DCS
See distributed communications system.
debug
See troubleshoot.
Issue 2 December 1995 GL-7
Glossary
dedicated line
A communications path that does not go through a switch. A dedicated (hard-wired) path may be
formed with directly connected cables. MPDMs, DSUs, or other devices may also be used to
extend the distance that signals can travel directly through the building wiring.
default
A value that is automatically supplied by the system if no other value is specified.
delivered message
A voice mail message that has been successfully transmitted to a recipient's incoming mailbox.
demand testing
Testing performed on request (usually by service personnel).
diagnostic testing
A program run for testing and determining faults in the system.
dial-ahead/dial-through
The act of interrupting or preceding INTUITY AUDIX system announcements by typing (buffering)
touch-tone commands in the order the system would normally prompt for them.
digital
Discrete data or signals such as 0 and 1.
digital communications protocol (DCP)
A 64 Kbps digital data transmission code with a 160 Kbps bipolar bit stream divided into two
information (I) channels and one signaling (S) channel.
digital networking
A method of transferring voice mail messages between voice messaging systems in a digital for-
mat. See also INTUITY AUDIX Digital Networking.
DIP switch
See dual in-line package switch.
direct memory access (DMA)
A quick method of moving data from a storage device directly to RAM, which speeds processing.
directory
An INTUITY AUDIX feature allowing you to hear a subscriber's name and extension after typing
**N at the activity menu. Also, a group of related files accessed by a common name in software.
display terminal
A data terminal with a screen and keyboard used for displaying INTUITY screens and performing
maintenance or administration activities.
distributed communications system (DCS)
A network of two or more switches that uses logical and physical data links to provide full or par-
tial feature transparency. Voice links are made using tie trunks.
distribution list
See mailing list.
DMA
See direct memory access.
DSR
See data set ready.
GL-8 Issue 2 December 1995
Glossary
DSU
See data service unit.
DTE
See data terminal equipment.
DTR
See data terminal ready.
dual in-line package (DIP) switch
A very small switch, usually attached to a printed circuit card, in which there are only two settings:
on or off (or 0 or 1). DIP switches are used to configure the card in a semipermanent way.
E
electrostatic discharge (ESD)
Discharge of a static charge on a surface or body through a conductive path to ground. An ESD
can be damaging to integrated circuits.
enabled/disabled
The state of a hardware device that indicates whether the INTUITY system can use it. Devices
must be equipped before they can be enabled (made active). See also equipped/unequipped.
enhanced call transfer
An INTUITY AUDIX feature that allows compatible switches to transmit messages digitally over
the BX.25 (data) link. This feature is used for quick call transfers and requires a fully integrated
digital switch. Callers can only transfer to other extensions in the switch dial plan.
enhanced serial data interface
A software- and hardware-controlled method used to store data on magnetic peripherals.
equipped/unequipped
The state of a networking channel that indicates whether INTUITY software has recognized it.
Devices must be equipped before they can be enabled (made active). See also enabled/dis-
abled.
error message
A message on the screen indicating that something is wrong and possibly suggesting how to cor-
rect it.
errors
Problems detected by the system during operation and recorded in the maintenance log. Errors
can produce an alarm if they exceed a threshold.
escape to attendant
An INTUITY AUDIX feature that allows a subscriber with the call answer feature to have a personal
attendant or operator administered to potentially pick up an unanswered call. A system-wide
extension could also be used to send callers to a live agent.
ESD
See electrostatic discharge.
events
Informational messages about the system’s activities. For example, an event is logged when the
system is rebooted. Events may or may not be related to errors and alarms.
Issue 2 December 1995 GL-9
Glossary
F
field
An area on a screen, menu, or report where information can be typed or displayed.
file
A collection of data treated as a basic unit of storage.
filename
Alphanumeric characters used to identify a particular file.
file redundancy
See mirroring.
filesystem
A collection of related files (programs or data) stored on disk that are required to initialize a INTU-
ITY system and provide full service.
F key
See function key.
format
To set up a disk, floppy diskette, or tape with a predetermined arrangement of characters so that
the system can interpret meaningful information.
function
Individual steps or procedures within a voice mailbox activity.
function key (F key)
A key on a computer keyboard that performs a defined function when pressed. The user inter-
face for the INTUITY system defines keys F1 through F8.
G
Generic 1, 2, or 3
AT&T switch system software releases. Generic 1, Generic 3i, and Generic 3s correspond to the
new generation of System 75-based software. Generic 2 and Generic 3r correspond to the new
release of System 85-based software.
generic tape
A copy of the standard software and standalone tape utilities that is shipped with a new INTUITY
system.
guest password
A feature that allows users who are not INTUITY AUDIX subscribers to leave messages on the
system by dialing a subscriber’s extension and entering a system-wide guest password.
GL-10 Issue 2 December 1995
Glossary
H
hard disk drive
A high-capacity data storage/retrieval device that is located inside a computer platform. A hard
disk drive stores data on non-removable high-density magnetic media based on a predetermined
format for retrieval by the system at a later date.
hardware
The physical components of a computer system. The central processing unit, disks, tape and
floppy drives are all hardware.
header
Information that the system creates to identify a message. A message header includes the origi-
nator or recipient, type of message, creation time, and delivery time.
help
HELP
CTRL
?
A command run by pressing
or
on an INTUITY display terminal to show the
H
options available at your current screen position. In the INTUITY AUDIX system, press
the telephone keypad to get a list of options. See also on-line help.
on
*
hertz (Hz)
A measurement of frequency in cycles per second. A hertz is one cycle per second.
host switch
The switch directly connected to the INTUITY system over the data link. Also, the physical link
connecting an INTUITY system to a distributed communications system (DCS) network.
hunt group
A group of analog ports on a switch usually administered to search for available ports in a circular
pattern.
Hz
See hertz.
I
IDI
See isolating data interface.
INADS
See initialization and administration system.
information service
See bulletin board.
initialization
The process of bringing a system to a predetermined operational state. The start-up procedure
tests hardware; loads the boot filesystem programs; locates, mounts, and opens other required
filesystems; and starts normal service.
initialization and administration system (INADS)
A computer-aided maintenance system used by remote technicians to track alarms.
Issue 2 December 1995 GL-11
Glossary
initialize
To start up the system for the first time.
input
A signal fed into a circuit or channel.
integrated services digital network (ISDN)
A network that provides end-to-end digital connectivity to support a wide range of voice and data
services.
integrated voice processing CELP card
The IVC6 card.
interface
The device or software that forms the boundary between two devices or parts of a system, allow-
ing them to work together.
interrupt request (IRQ)
A device that signals the data bus and the CPU that it needs attention.
INTUITY AUDIX Digital Networking
An INTUITY feature that allows customers to link together up to 500 remote INTUITY machines for
a total of up to 500,000 remote subscribers. See also digital networking.
I/O address
input/output address.
IRQ
See interrupt request.
ISDN
See integrated services digital network.
isolating data interface (IDI)
A synchronous, full duplex data device used for cable connections between an INTUITY
GPSC-AT/E card and the switch data communications interface unit (DCIU).
J
jumper
Pairs or sets of small prongs on circuit cards and mother boards that allow the user to instruct the
computer to select one of its available operation options. When two pins are covered, an electri-
cal circuit is completed.
K
Kbps
kilobits per second. One thousand bits per second.
GL-12 Issue 2 December 1995
Glossary
L
label
The name assigned to a disk device (either a removable tape cartridge or permanent drive)
through software. Cartridge labels may have a generic name (such as 3:3) to show the software
release or a descriptive name if for backup copies (such as back01). Disk drive labels usually
indicate the disk position (such as disk00 or disk02).
LCD
See liquid crystal display.
leave word calling (LWC)
A switch feature that allows the calling party to leave a standard (nonvoice) message for the
called party using a feature button or dial access code.
LED
See light emitting diode.
light emitting diode (LED)
A light indicator on the hardware platform that shows the status of operations.
liquid crystal display (LCD)
The 10-character alphanumeric display that shows status of the system, including alarms.
load
To read software from external storage (such as disk) and place a copy in system memory.
local AUDIX machine
The AUDIX system where a subscriber's voice mailbox is located. All subscribers on this home
machine are called local subscribers.
local installation
A switch, adjunct, or peripheral equipment installed physically near the host switch or system.
See also collocated.
local network
An INTUITY AUDIX Digital Network in which all INTUITY systems are connected to the same
switch.
login
A unique code used to gain approved access to the INTUITY system. See also password.
login announcement
A feature enabling the system administrator and other designated users to create a voice mail
message that is automatically played to all INTUITY AUDIX subscribers every time they login to
the system.
Issue 2 December 1995 GL-13
Glossary
M
magnetic peripherals
Data storage devices that use magnetic media to store information. Such devices include hard
disk drives, floppy disk drives, and cartridge tape drives.
mailbox
A portion of disk memory given to each INTUITY AUDIX subscriber for creating and storing outgo-
ing and incoming voice mail messages.
mailing list
A group of INTUITY AUDIX subscriber addresses assigned a list ID# and public or private status.
A mailing list may be used to simplify sending messages to several subscribers.
maintenance
The process of identifying system errors and correcting them, or taking steps to prevent problems
from occurring.
major alarm
An alarm detected by INTUITY software that affects at least one fourth of the INTUITY ports in ser-
vice. Often a major alarm indicates that no service is available.
megabyte
A unit of memory equal to 1,048,576 bytes (1024 x 1024). It is often rounded to one million.
memory
A device which can store logic states such that data can be accessed and retrieved. Memory
may be temporary (such as system RAM) or permanent (such as disk).
message categories
Groups of messages in INTUITY AUDIX subscribers' mailboxes. Categories include new,
unopened, and old for the incoming mailbox and delivered, accessed, undelivered, undeliverable
(not deliverable), and file cabinet for the outgoing mailbox.
message delivery
An optional INTUITY feature that permits subscribers to send recorded messages to any
touch-tone telephone, as long as the telephone number is in the range of allowable numbers.
This feature is an extension of the AMIS analog networking feature and is automatically available
when the AMIS feature is activated.
message-waiting indicator (MWI)
An indicator that alerts subscribers that they have received new voice mail messages. An MWI
can be LED, neon, or audio (stutter dial tone).
minor alarm
An alarm detected by maintenance software that affects less than one fourth of the INTUITY ports
in service, but has exceeded error thresholds or may impact service.
mirroring
An INTUITY system feature that allows data from crucial filesystems to be continuously copied to
backup (mirror) filesystems while the system is running. If the system has some problem where
an original filesystem cannot be used, the backup filesystem is placed in service automatically.
modem
A device that converts data from a form that is compatible with data processing equipment (digi-
tal) to a form compatible with transmission facilities (analog), and vice-vera.
GL-14 Issue 2 December 1995
Glossary
modular
A term that describes equipment made of plug-in units that can be added together to make the
system larger, improve its capabilities, or expand its size.
modular processor data module (MPDM).
A data device that converts RS-232C or RS-449 protocol signals to digital communications proto-
col (DCP) used by System 75/85, Generic1, and Generic 3 switches. MPDMs may connect INTU-
ITY to a switch DCIU or SCI link or connect terminals to a switch port card.
MPDM
See modular processor data module.
MWI
See message-waiting indicator.
N
networking
See INTUITY AUDIX Digital Networking.
networking prefix
A set of digits that identifies an INTUITY machine.
not deliverable message
A voice mail message that could not be delivered after a specified number of attempts. This usu-
ally means that the subscriber’s mailbox is full.
O
on-line help
An INTUITY feature that provides information about INTUITY user interface screens by pressing a
predetermined key. See also help.
operating system (OS)
The set of programs that runs the hardware and interprets software commands.
option
A choice selected from a menu, or an argument used in a command line to modify program out-
put by modifying the execution of a command. When you do not specify any options, the com-
mand will execute according to its default options.
OS
See operating system.
outcalling
An INTUITY feature that allows the system to dial subscribers’ numbers to inform them they have
new messages.
outgoing mailbox
A storage area for subscribers to keep copies of messages for future reference or action.
Issue 2 December 1995 GL-15
Glossary
P
parallel transmission
The transmission of several bits of data at the same time over different wires. Parallel transmis-
sion of data is usually faster than serial transmission.
password
A code assigned to every INTUITY terminal user and INTUITY AUDIX subscriber for security rea-
sons. After dialing the system, subscribers must dial their personal password correctly to log on.
Passwords are also assigned to local and remote networked machines to identify the machines or
the network. See also login.
PBX
See private branch exchange.
PDM (processor data module)
See modular processor data module (MPDM).
peripheral device
Equipment external to the INTUITY cabinet, such as printers or terminals, necessary for full oper-
ation and maintenance of the INTUITY system. Also called peripherals.
personal directory
An INTUITY AUDIX feature allowing each subscriber to create a private list of customized names.
pinouts
The signal description per pin number for a particular connector.
port
A connection or link between two devices, allowing information to travel to a desired location. For
example, a switch port connects to an INTUITY voice port to allow a subscriber to leave a mes-
sage.
priority messaging
An INTUITY AUDIX feature that allows some subscribers to send messages that are specially
marked and preferentially presented to recipients. See also priority outcalling.
priority outcalling
Works with the priority messaging feature by allowing the message recipient to elect to be notified
by outcalling only when a priority message has been received. See also priority messaging.
private branch exchange (PBX)
A private switching system. See also switch.
private mailing list
A list of voice mail addresses that only the owning subscriber can access.
private messaging
A feature of INTUITY AUDIX that allows a subscriber to send a voice mail message that cannot be
forwarded by the recipient.
processor data module (PDM)
See modular processor data module (MPDM).
processor interface (PI)
A System 75, Generic 1, Generic 3i, Generic 3s, and Generic 3vs switch data link. Also called
processor interface board (PIB).
GL-16 Issue 2 December 1995
Glossary
programmed function key
See function key.
protocol
A set of conventions or rules governing the format and timing of message exchanges (signals) to
control data movement and the detection and possible correction of errors.
public mailing list
A list of voice mail addresses that any INTUITY AUDIX subscriber can use if that subscriber
knows the owner's list ID# and extension number. Only the owner can modify a public mailing list.
R
RAM
See random access memory.
random access memory (RAM)
The primary memory in a computer that can be overwritten with new information.
reboot
See boot.
remote access
Sending and receiving data to and from a computer or controlling a computer with terminals or
PCs connected through communications links.
remote installation
A system, site, or piece of peripheral equipment that is installed in a different location from the
host switch or system.
remote network
A network in which the systems are integrated with more than one switch.
remote service center
An AT&T or AT&T-certified organization that provides remote support to INTUITY customers.
Depending upon the terms of the maintenance contract, your remote service center may be noti-
fied of all major and minor alarms and have the ability to remotely log into your system and rem-
edy problems.
remote subscribers
INTUITY AUDIX voice mail subscribers whose mailboxes reside on a remote INTUITY AUDIX Dig-
ital Networking machine.
remote terminal
A terminal connected to a computer over a phone line.
REN
See ringer equivalence number.
reply loop escape
An INTUITY AUDIX feature that allows a subscriber the option of continuing to respond to a mes-
sage after trying to reply to a nonsubscriber message.
reply to sender
An INTUITY AUDIX feature that allows subscribers to immediately place a call to the originator of
an incoming message if that person is in the switch's dial plan.
Issue 2 December 1995 GL-17
Glossary
request to send (RTS)
One of the control signals on a RS-232 connector that places the modem in the originate mode so
that it can begin to send.
restart
An INTUITY feature that allows INTUITY AUDIX subscribers who have reached the system
through the call answer feature to access their own mailboxes by typing the *R (Restart) com-
mand. This feature is especially useful for long-distance calls or for users who wish to access the
INTUITY system when all the voice mail ports are busy. Also, the reinitialization of certain soft-
ware. For example, restarting the voice system.
restore
The process of recovering lost or damaged files by retrieving them from available backup tapes,
floppy diskette, or another disk device.
retention time
The amount of time voice mail messages are saved on disk before being automatically deleted
from a subscriber's mailbox.
ringer equivalence number (REN)
A number required in the United States for registering your telephone equipment with the phone
company.
RTS
See request to send.
S
sales representative
An AT&T or AT&T-certified person who assists you in the purchasing, planning, and implementa-
tion of AT&T equipment and solutions.
SCA
See switch communications adapter.
scan
To automatically play voice mail messages, headers, or both.
scheduled delivery time
A time and/or date that an INTUITY AUDIX subscriber optionally assigns to a message that tells
the system when to deliver it. If a delivery time is omitted, the system sends the message immedi-
ately.
SCSI
See small computer system interface.
serial transmission
The transmission of one bit at a time over a single wire.
shielded cables
Cables that are protected from interference with metallic braid or foil.
SIMMs
See single in-line memory modules.
GL-18 Issue 2 December 1995
Glossary
simplified message service interface (SMSI)
Type of data link connection to an integrated 1A ESS switch or 5ESS switch in the INTUITY sys-
tem.
single in-line memory modules (SIMMs)
A method of containing random access memory (RAM) chips on narrow circuit card strips that
attach directly to sockets on the CPU circuit card. Multiple SIMMs are sometimes installed on a
single CPU circuit card.
small computer systems interface (SCSI)
An interface standard defining the physical, logical, and electrical connections to computer sys-
tem peripherals such as tape and disk drives.
SMSI
See simplified message service interface.
split
Group (or queue) of analog ports on the switch. See also call-distribution group.
subscriber
An INTUITY user who has been assigned the ability to access the INTUITY AUDIX Voice Messag-
ing system.
surge
A sudden voltage rise and fall in an electrical circuit.
surge protector
A device that plugs into the phone system and the commercial AC power outlet. It is designed to
protect the phone system from high voltage surges that could be damaging to the phone system.
switch
An automatic telephone exchange that allows the transmission of calls to and from the public tele-
phone network. See also private branch exchange (PBX).
switched access
A connection made from one endpoint to another through switch port cards. This allows the end-
point (such as a terminal) to be used for several applications.
switch hook
The device at the top of most telephones which is depressed when the handset is resting in the
cradle (on hook). This device is raised when the handset is picked up (the phone is off hook).
switch hook flash
A signaling technique in which the signal is originated by momentarily depressing the switch
hook.
switch network
Two or more interconnected switching systems.
synchronous communication
A method of data transmission in which bits or characters are sent at regular time intervals, rather
than being spaced by start and stop bits. See also asynchronous communication.
synchronous transmission
A type of data transmission where the data characters and bits are exchanged at a fixed rate with
the transmitter and receiver synchronized. This allows greater efficiency and supports more pow-
erful protocols.
system configuration
See configuration.
Issue 2 December 1995 GL-19
Glossary
T
tape cartridge
One or more spare removable cartridges required to back up system information.
tape drive
The physical unit that holds, reads, and writes magnetic tape.
terminal
See display terminal.
terminal type
A number indicating the type of terminal being used to log on to the INTUITY system. Terminal
type is the last required entry before gaining access to the INTUITY display screens.
terminating resistor
A grounding resistor placed at the end of bus, line, or cable to prevent signals from being
reflected or echoed.
tip/ring
A term used to denote the analog telecommunications interface.
tone generator
A device acoustically coupled to a rotary phone, used to produce touch-tone sounds when voice
mail subscribers cannot use a regular touch-tone generating voice terminal.
traffic
The flow of attempts, calls, and messages across a telecommunications network.
translations
Software assignments that tell a system what to expect on a certain voice port or the data link, or
how to handle incoming data. They customize the INTUITY system and switch features for users.
troubleshoot
The process of locating and correcting errors in computer programs. Also called debug.
U
UCD
See uniform call distribution.
undelivered message
A message that has not yet been sent to an INTUITY AUDIX subscriber's incoming mailbox. The
message resides in the sender's outgoing message and may be modified or redirected by the
sender.
Unequipped
See equipped/unequipped.
unfinished message
A message that was recorded but not approved or addressed, usually the result of an interrupted
INTUITY AUDIX session. Also called working message.
GL-20 Issue 2 December 1995
Glossary
uniform call distribution (UCD)
The type of call-distribution group (or hunt group) of analog port cards on some switches that
connects subscribers and users to the INTUITY AUDIX system. System 75, Generic 1, Generic 3,
and some central office switches use UCD groups. See also call-distribution group.
UNIX operating system
A multi-user, multitasking computer operating system.
untouched message
An INTUITY AUDIX feature that allows a subscriber to keep a message in its current category by
using the **H (Hold) command. If the message is in the new category, message-waiting indica-
tion remains active (for example, the message-waiting lamp will remain lit).
user population
A combination of light, medium, and heavy users on which INTUITY configuration guidelines are
based.
V
vector
A customized program in the switch for processing incoming calls.
voice link
The INTUITY analog connection(s) to a call-distribution group (or hunt group) of analog ports on
the switch.
voice mail
See voice message.
voice mailbox
See mailbox.
voice message
Digitized voice information stored by the INTUITY system on disk memory. Also called voice mail.
voice port
The IVC6 port that provides the voice interface between the INTUITY system and the analog ports
on the switch.
voice terminal
A telephone used for spoken communications with the INTUITY system. A touch-tone telephone
with a message-waiting indicator is recommended for all INTUITY AUDIX subscribers.
voicing
Either speaking a message into the INTUITY system during recording, or having the system play-
back a message or prompt to a subscriber.
volt
The unit of measurement of electromotive force. One volt is the force required to product a cur-
rent of one ampere through a resistance of one ohm.
Issue 2 December 1995 GL-21
Glossary
W
watt
A unit of electrical power that is required to maintain a current of one amp under the pressure of
one volt.
GL-22 Issue 2 December 1995
Ind e x
E
Forms
EIA
ENTER key
Erase
Forward
Forwarding
Front panel
FUNC key
F
Fields
G
H
Hardware
SID
IN-2 Issue 2 December 1995
Ind e x
Link A
Link B
lodging
Logical terminal number
hunt group
I
M
Installation
administration
baud rate
K
dip switches
table, 4-4
Keypad
Keys
connection
L
LCD
LED
menu
Intuity system
Issue 2 December 1995 IN-3
Ind e x
P
Parity
Messages
Planning
baud rate
MODE key
Modem
Modem port
Port
administration
pad string
MWI feature
MWL
administration
Power cord outlet
Power switch
N
Purge
R
Rear panel
Requirements
IN-4 Issue 2 December 1995
Ind e x
S
Safety
screen
Intuity system
screens
NEAX
NEAX2400
SID
LCD
baud rate
Software
Issue 2 December 1995 IN-5
Ind e x
Subscribers
Word length
System parameters
Worksheets
Y
T
U
assignments
UCD overflow
V
W
IN-6 Issue 2 December 1995
|