MULTISET PRO® - PRE-WIRED  
DIMMING CABINET MDC20  
COMPATIBLE WITH MULTISET PRO® HEATSINK DIMMER MODELS:  
MHP5ES, MHP8ES, MPH5AVES, MHP8AVES, MHP600VA, MHP1000VA, MHP1500VA,  
MHP2000VA, MHP1000ND, MHP2000ND, MHP500QE, MHP600HDF120,  
MHP1500HDF120, MHP600EB, MHP1000EB, MHP1500EB, MHPWHIS  
WARNING: Before installation, disconnect power at circuit breakers or remove fuse to avoid electrical  
shock or damage to the unit. It is recommended that an electrician perform this installation.  
For technical/sales assistance, call: 1-800-526-2731  
Made in U.S.A.  
www.lolcontrols.com P/N 85-1530  
Installation  
and Operation  
®
MULTISET PRO - PRE-WIRED DIMMING CABINET MDC20  
Cabinet Installation  
1. Surface or recess mount on wall using appropriate  
wall anchors. Use wall anchors capable of support-  
ing up to 80-90 pounds.  
BACK  
Figure 1  
Note: All wiring should be in accordance with local  
regulations and the National Electrical Code. All  
wiring shall enter and exit the cabinet via the provided  
knock outs at the top or bottom of the cabinet.  
1
1
2. Terminate 120VAC lines and neutrals to terminal  
blocks. Do not use common neutrals  
3. Connect lighting loads to the load terminal block.  
Be sure to match proper load with the correct  
device (refer to device location sticker on front of  
cabinet).  
4. Connect ground to dimming cabinet.  
5. Connect network "purple" wire to additional cabi-  
nets (when necessary).  
Each Cabinet Cover has a swinging radius of 21"  
1
1
Features  
2
Terminal Blocks  
Figure 2  
Dimmer  
1. Anchor mounts (Figure 1)  
2. Terminal blocks (Figure 2)  
3. Ground terminal strip  
4. Dimmer mounting panel  
5. Cabinet latch  
(see descriptions below)  
Detail C  
Detail C  
3
Enclosure::  
4
- Can be ordered separately for  
rough-in.  
Order part number: MDC20ENC  
6. Door and door frame  
Note: No common neutrals  
Interior:  
- Terminal Blocks  
3
- Mounting Back Plane  
- Dimmer(s) Mounting Panel  
- Door and Door Frame  
- Can be ordered separately and  
6
5
installs into MDC20ENC  
Order part number: MDC20INT*  
*Requires part number MDC20ENC  
2
Terminal Blocks:  
Installed and positioned according to dimmer/master  
configuration for each cabinet.  
FRONT  
- Red Terminal Blocks: Load wire terminations  
- Black Terminal Blocks: Power feed terminations  
- Blue Terminal Block: MultiSet Pro purple wire terminations  
- White Terminal Block: Neutral wire terminations  
- Grey Terminal Block: Lightolier Controls PowerSpec HDF  
dimming ballast TAN wire termination.  
3
Installation  
and Operation  
®
MULTISET PRO - PRE-WIRED DIMMING CABINET MDC20  
Replacing the Keypad Button Labels (Classic Series)  
MultiSet Pro® Classic Series Masters are supplied with over 260  
Figure 3  
labels to personalize the buttons for your own scene names. The  
buttons are labeled at the factory with letters. These button labels  
can easily be changed to customize your system:  
1. Insert a small screwdriver into the outside edge on the side  
of a button and pry off the plastic key cover.  
ON  
CAUTION: Pry from outside edge, do not attempt to insert  
screwdriver between key covers (Figure 3).  
2. Remove the factory label and insert an appropriate label  
from the supplied label sheet into the key cover.  
A
B
3. Snap the cover over the button housing by pressing firmly  
on the plastic key cover.  
4. Repeat for each button you wish to change.  
Replacing the Keypad Membrane (Ellipse Series)  
The overlay on these models is easily replaced, even if the unit is  
currently installed.  
Figure 4  
1. Turn the power off at the circuit breaker.  
2. Remove the faceplate (Figure 4).  
3. Remove the master keypad wall screws (Figure 5).  
3a.On heatsink model, remove heatsink screws and spacers  
(Figure 5).  
4. Remove the retaining plate screws and plate (Figure 6).  
5. Remove the existing keypad membrane.  
6. Install the new keypad membrane, being careful to line it up  
properly with the openings.  
Faceplate  
7. Reinstall the retaining plate and screws (Figure 6).  
7a.On heatsink model, reinstall screws and spacers (Figure 5).  
8. Reinstall the master keypad to wallbox (Figure 5).  
9. Reinstall the faceplate (Figure 4).  
Figure 5  
Figure 6  
10.Turn the power back on at the circuit breaker.  
Note: Spacers on the heatsink model are not attached to the unit.  
Wall  
Screws  
Screws  
Heatsink  
Screws  
4
Installation  
and Operation  
®
MULTISET PRO - PRE-WIRED DIMMING CABINET MDC20  
Dimmer/Switch Operating Instructions  
MULTISET PRO® DIMMER  
To Turn light on to preset level, tap top of rocker, the dimmer fades up at the 1.5 second rate.  
A second tap of the rocker fades the dimmer to full brightness.  
To adjust the light level, press and hold top or bottom of rocker until desired light level is reached, and then release.  
To turn lights off, tap the bottom of the rocker. The dimmer fades at the 3 second fade rate.  
To quickly return to the preset level when light is on, quickly tap OFF and then ON. The lights adjust to the preset level.  
To bypass the fade rate and turn the lights to full ON or OFF, double tap the dimmer for ON or OFF.  
If the Master is in the OFF scene, the Master ON button illuminates when any dimmer is turned on.  
To change the preset level of the current scene:  
Figure 7  
• Press and hold the rocker until lights reach the desired level then release.  
• Press the small set button next to the switch to save the preset in memory.  
LEDs on the MultiSet Pro® Dimmer/Switch indicate status:  
Red LED  
1. Red LED is on when Dimmer/Switch is off to locate Dimmer/Switch when room is dark.  
Green LED  
2. As many as 3 green LEDs may be illuminated at any given time. The bright green LED  
indicates the current level of the dimmer. The medium green LED indicates the preset level  
of the current scene. The dim green LED indicates the preset level of the ON scene.  
Set  
Button  
MULTISET PRO® UNIVERSAL ELECTRONIC SWITCH (NON-DIM)  
The MultiSet Pro® Universal Electronic Switch can be programmed as a four or five-scene non-  
dim switch. When programmed as a five-scene device, it is not suitable for 3-way applications.  
The default mode of the switch is as a normal (4-scene) non-dim device. The AV (5-scene) mode allows the non-dim switch to remain  
off when the master ON button is pressed.  
To change the mode of the switch:  
1. Tap OFF on the Master to place the switch in the OFF scene.  
2. Press and hold the SET button. After 3 Seconds, a green LED illuminates on the bargraph. If the switch is currently in normal  
mode, the bottom green LED illuminates. If it is in AV mode, the top LED illuminates.  
3. Tap the top of the rocker once to toggle the mode.  
4. Release the SET button.  
Note: In normal mode, a “soft start” feature is utilized to extend bulb life. In AV mode, the “soft start” feature is not  
implemented.  
Programming Scenes  
After you have completed installation of all the MultiSet Pro® devices and have  
energized the system, each scene can be programmed.  
Figure 8  
Step 1  
1. Tap the preset button (ON, A - L) on the MultiSet Pro® Master that you wish to  
program (see Step 1, Figure 8).  
Preset  
2. Adjust each MultiSet Pro® Dimmer to the desired intensity and the MultiSet Pro®  
Switches to either ON or OFF (see above).  
Buttons  
(ON, A, B  
C, D)  
3. Press the Set button on each device (see Step 3, pg. 7) after all devices have been  
adjusted.  
Repeat Steps 1-3 until all scenes have been programmed.  
E
G
I
F
H
J
Preset  
Buttons  
(E-L)  
K
L
5
Installation  
and Operation  
®
MULTISET PRO - PRE-WIRED DIMMING CABINET MDC20  
Changing the Fade Rate  
MultiSet Pro® Dimmers can be programmed for 12 different fade rates. Dimmers  
can be programmed to have a different fade rate on each scene.  
Figure 9  
The fade rate choices are:  
2 min  
1.5 seconds  
seconds  
1
2
5
minute  
minutes  
minutes  
60 min  
1 min  
30 sec  
15 sec  
7.5 sec  
4.5 sec  
3 sec  
3
4.5 seconds  
7.5 seconds  
15 seconds  
30 seconds  
30 min  
15 min  
15 minutes  
30 minutes  
60 minutes  
5 min  
1.5 sec  
Global Fade Rate = One fade rate for all scenes.  
Each dimmer’s fade rate affects all scenes. Examples: Dimmer #1 fade rate set 7.5 sec.,  
dimmer #2 set to 15 sec., and dimmer #3 set to 3 sec. When any scene is selected dim-  
mers #1, 2, and 3, will respond with 7.5, 15, and 3 seconds, respectively for ON, OFF,  
A, B, C, D, E, F, G, H, I J, K, and L.  
“Green”  
LED Lights  
To change the Global Fade Rate that affects all scenes:  
Figure 10  
1. Tap the OFF button on the Master.  
2. Press and hold the SET button. After 3 seconds, either a single green LED or a  
pair of green LEDs indicates the current “global” fade rate. The bottom LED indi-  
cates the 1.5 second fade rate, the next LED up is 3 seconds, while the top LED is  
2 minutes. If the bottom two LEDs are on, it indicates the 5 minutes fade rate, if  
the next two LEDs up are lit, it indicates 15 minutes, while the top two LEDs  
indicate the 60 minute fade rate.  
Step 1  
Press and hold Set  
button for 3 seconds.  
Step 2  
Tap top of dimmer paddle  
to increment fade rate.  
Note: When the two LEDs are on, they will not be at the same intensity.  
Step 3  
Release Set button.  
3. While holding the Set button, tap the top of the rocker to sequence the LEDs  
through the various fade rates until the desired fade rate is selected.  
4. Release the SET button.  
5. Repeat steps 2 - 4 for each device.  
To change the fade rate that will affect only an individual scene:  
1. Tap a scene button on the Master to go to a scene.  
2. Press and hold the SET button.  
3. After 3 seconds, either a single green LED or a pair of green LEDs indicates the  
scene’s fade rate.  
4. While holding the SET button, tap the top rocker until the desired fade rate is  
reached.  
5. Release the SET button.  
6. Repeat above for each scene.  
Operating Instructions  
MULTISET PRO® MASTER (CLASSIC SERIES)  
Figure 11  
Tap the ON button to elegantly illuminate the entire area to the ON “preset”.  
Press and hold the ON button to brighten lighting level.  
Tap the OFF button to fade lights to OFF.  
Press and hold OFF button to lower lighting level.  
Tap a scene button to access “preset” light levels.  
All-On  
A
C
B
Classic Series  
D
Off  
Two quick taps of any button (including ON and OFF) will fade lighting quickly.  
MULTISET PRO® MASTER (ELLIPSE SERIES)  
Figure 12  
Press or Tap the ON button to elegantly illuminate the entire area to the ON “preset”.  
Press the RAISE button to brighten lighting level.  
ON  
Raise/Lower  
Tap the OFF button to fade lights to OFF.  
Press LOWER button to lower lighting level.  
Tap a scene button to access one of the “preset” light levels.  
Two quick taps of any button (except RAISE or LOWER) will fade lighting quickly.  
Button  
Ellipse Series  
Built-in IR  
Receiver  
OFF  
6
Installation  
and Operation  
®
MULTISET PRO - PRE-WIRED DIMMING CABINET MDC20  
Setting the Button Brightness (Ellipse Series)  
The brightness level of each Ellipse Master Control Station button can be programmed to 100% (factory default), 75%, 50%, or 25%.  
To change the setting:  
Figure 13  
1. On a 5-Scene Master, press and hold buttons “B” and “D” simultaneously for 3 seconds (on an 8-  
Scene Master, press buttons “H” and “J”). On a 5-Scene Master, buttons “A” thru “D” illuminate  
8-Scene  
LED  
5-Scene  
Master  
(on an 8-Scene Master, buttons “G” thru “J” illuminate). The blinking LED displays the current  
LED brightness setting. The continuously-illuminated LEDs display the available brightness set-  
tings that can be selected.  
Master Brightness  
A
B
C
D
G
H
I
100%  
75%  
50%  
25%  
2. To change the brightness setting, press the button illuminated at the desired brightness. This button  
will begin blinking.  
J
3. To save the selected brightness and exit the mode, press the ON button on a 5-Scene Master (or the  
“E” button on an 8-Scene Master). All buttons on that master will now have the new brightness setting.  
Typical Wiring Diagram  
To Lighting Loads  
(One dimmed 120VAC Line / Neutral per circuit)  
Figure 14  
See Page 3 for Terminal Block  
Up to 20 Circuits...  
Wiring Descriptions.  
120VAC Line / Neutral  
120VAC Line / Neutral  
A
B
C
D
Note: No Common Neutrals  
on Dimmed Circuits.  
120VAC Line / Neutral  
120VAC Line / Neutral  
1
2
3
4
5
120VAC Line / Neutral  
120VAC Line / Neutral  
120VAC Line / Neutral  
Note: Knockouts are provided  
on top and both sides.  
120VAC Line / Neutral  
120VAC Line / Neutral  
120VAC Line / Neutral  
120VAC Line / Neutral  
120VAC Line / Neutral  
120VAC Line / Neutral  
120VAC Line / Neutral  
120VAC Line / Neutral  
120VAC Line / Neutral  
120VAC Line / Neutral  
120VAC Line / Neutral  
120VAC Line / Neutral  
120VAC Line / Neutral  
Circuit Breaker Panel  
MHPWDC20  
Connecting Multiple Cabinets  
Figure 15  
MDC20  
MDC20  
MDC20  
MHPWDC20  
A
B
C
D
A
B
C
D
A
B
C
D
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
Purple Wire  
Purple Wire  
Up to 30 MultiSet Pro® Devices may be controlled as one system.  
7
Installation  
and Operation  
®
MULTISET PRO - PRE-WIRED DIMMING CABINET MDC20  
Cabinet Specifications  
Input Voltage: 108-132VAC, 60Hz, 3Hz  
Operating Temperature: 0°- 40° Celsius  
Weight: 80 lbs empty - 88 lbs with (20) 1000W dimmers  
Dimensions: 45.5"(H) x 20.1"(W) x 5.5"(D)  
Materials: White, 16 Gauge Steel  
Enclosure: Double hinged cover / lockable latching cover  
Dimensions  
20.1"  
18.0"  
4.0"  
1.5"  
45.5"  
45.5"  
Note: Cabinet cover has a swinging radius of 21"  
3 YEAR LIMITED WARRANTY  
Lightolier® Controls warrants that this product will be free from defects in workmanship or materials. This warranty is void  
on any electronic controls which have been overloaded, abused, improperly installed or altered in any manner.  
Lightolier Controls’ sole obligation will be at its option to repair or replace any electronic controls product proven defective  
if it is returned, postage prepaid, to Lightolier Controls, 10911 Petal St. Dallas, Texas 75238. Lightolier Controls will not pay  
for any charge-back or charge for labor or material that does not have its prior written approval.  
This warranty shall be in lieu of any other warranty, express or implied, including but not limited to any implied warranty  
of merchantability or fitness for a particular purpose. Some states do not allow limitations on how long an implied warran-  
ty lasts and do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclu-  
sions may not apply to you. This warranty gives you specific legal rights, and you may also have other rights, which vary  
from state to state.  
This product may be covered by one or more of the following U.S. Patents: #4,413,211; 4,430,576; 4,465,956; 4,733,138; 4,792,731; 4,880,950; 4,988,840; 4,992,709; 5,004,969; 5,004,969;  
5,128,654; 5,153,816; 5,189,259; 5,194,858; 5,239,255; 5,239,255; 5,371,439; 5,371,444; 5,506,480; 5,636,111; 5,642,104; 5,646,490; 5,814,550; 5,821,704; 5,920,156; 5,930,126; Des.  
#307,578; 333,124; 435,203; 440,207; License #4482844; 5,004,969; 5,239,255; and corresponding foreign patents. Other Utility, Design and Foreign Patents Pending. We reserve the right  
to change details of design, materials and finish in any way that will not alter the installed appearance or reduce function performance. Specifications are subject to change without notice.  
Lightolier® Controls  
For technical/sales assistance, call: 1-800-526-2731  
Made in U.S.A. ©Lightolier® Controls 2006  
A Genlyte Company  
www.lolcontrols.com P/N 85-1530  
10911 Petal Street • Dallas, Texas 75238  

Nokia 3720 User Manual
Mr Coffee PRX29 User Manual
Motorola W177 User Manual
Motorola V190 User Manual
Hosa Technology Clock Radio SKJ 600BB User Manual
Dell PowerVault LTO4 EH1 User Manual
Curtis RCD3830 User Manual
Clarion DB356MP User Manual
Clarion DB166 User Manual
Addonics Technologies CF AE6CAHI User Manual