APPLICABILITY & EFFECTIVITY  
Effective for all systems manufactured after May 1, 2001  
FS-8704-07_AB-CSP Manual  
Page 3 of 15  
1.  
Allen Bradley AB_CSP Description  
The AB_CSP driver allows the FieldServer to transfer data to and from devices over AB_CSP  
Ethernet protocol. The FieldServer can emulate either a Server or Client.  
The information that follows describes how to expand upon the factory defaults provided in the  
configuration files included with the FieldServer.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8704-07_AB-CSP Manual  
Page 4 of 15  
2.  
Hardware/Software  
2.1. Supplied by FieldServer Technologies for this Driver  
FieldServer Technologies PART #  
FS-8915-10  
FS-8704-07  
DESCRIPTION  
Ethernet cable (7 foot)  
Driver Manual  
2.2.  
Provided by Supplier of 3rd Party Equipment  
PART # DESCRIPTION  
AB_CSP compatible PLC, e.g. SLC5/05 etc. 1  
AB_CSP Client, e.g. Wonderware, Intellution FIX, GE Cimplicity, etc. 2  
1 If FieldServer used as Allen Bradley AB_CSP Client  
2 If FieldServer used as Allen Bradley AB_CSP Server.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8704-07_AB-CSP Manual  
Page 5 of 15  
3.  
Hardware Connections  
Make sure the device IP_address is configured to be on the same IP network as the  
FieldServer. Use a crossover cable if the FieldServer is connected directly to the PLC device.  
Use a straight cable if the FieldServer is connected to a hub.  
Configure the PLC according to manufacturer’s instructions  
PLC  
Ethernet Interface  
SITE  
FS-8915-10  
ETHERNET  
FS-8915-10  
(408)-262-2299  
FIELDSERVER  
AB-CSP  
CONNECTION DIAGRAM  
BASE NAME:  
FILE NAME:  
DATE: 5/04/04  
BY: MC  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8704-07_AB-CSP Manual  
Page 6 of 15  
4.  
Configuring the FieldServer as a AB-CSP Client  
For a detailed discussion on FieldServer configuration, please refer to the FieldServer  
Configuration Manual. The information that follows describes how to expand upon the factory  
defaults provided in the configuration files included with the FieldServer (See “.csv” sample files  
provided with the FieldServer).  
This section documents and describes the parameters necessary for configuring the FieldServer  
to communicate with an AB-CSP Server.  
4.1.  
Data Arrays/Descriptors  
The configuration file tells the FieldServer about its interfaces, and the routing of data  
required. In order to enable the FieldServer for AB-CSP communications, the driver  
independent FieldServer buffers need to be declared in the “Data Arrays” section, the  
destination device addresses need to be declared in the “Client Side Nodes” section, and  
the data required from the servers needs to be mapped in the “Client Side Map Descriptors”  
section. Details on how to do this can be found below.  
Note that in the tables, * indicates an optional parameter, with the bold legal value being the  
default.  
Section Title  
Data_Arrays  
Column Title  
Function  
Legal Values  
Up to 15 alphanumeric  
characters  
Data_Array_Name  
Provide name for Data Array  
Provide data format. Each Data  
Array can only take on one format.  
Number of Data Objects. Must be  
larger than the data storage area  
required by the Map Descriptors for  
the data being placed in this array.  
INT16, INT32, BIT,  
FLOAT  
Data_Array_Format  
Data_Array_Length  
1-10,000  
Example  
// Data Arrays  
Data_Arrays  
Data_Array_Name,  
DA_AI_01,  
DA_AO_01,  
DA_DI_01,  
Data_Format,  
Float,  
Float,  
Bit,  
Bit,  
Data_Array_Length  
200  
200  
200  
200  
DA_DO_01,  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8704-07_AB-CSP Manual  
Page 7 of 15  
4.2.  
Client Side Connection Descriptors  
Section Title  
Connections  
Column  
Title  
Legal  
Values  
Function  
Specify which port the device is connected to the  
FieldServer  
Specify protocol used  
Adapter  
Protocol  
N1  
AB_CSP  
Example  
// Client Side Connections  
Connections  
Adapter,  
N1,  
Protocol  
AB_CSP  
4.3.  
Client Side Node Descriptors  
Section Title  
Nodes  
Column Title  
Function  
Legal Values  
Up to 32 alphanumeric  
characters  
Node_Name  
Node_ID  
Provide name for node  
Node ID of physical server  
node (PLC)  
1-255  
Must be on the same  
subnet as the server or  
gateway  
IP address of physical server  
node (PLC)  
IP_Address  
Protocol  
Specify protocol used  
AB_CSP  
Specify on which port the  
Adapter  
device is connected to the N1  
FieldServer  
Specify PLC  
Communications type.  
PLC_Type  
PLC3, PLC5, SLC5  
Example  
// Client Side Nodes  
Nodes  
Node_Name, Node_ID,  
Protocol,  
AB_CSP,  
PLC_Type,  
SLC5,  
IP_Address,  
192.168.1.13, N1  
Adapter  
PLC_01,  
1,  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8704-07_AB-CSP Manual  
Page 8 of 15  
4.4.  
4.4.1.  
Client Side Map Descriptors Client Side Map Descriptors  
FieldServer Related Map Descriptor Parameters  
Column Title  
Function  
Name of this Map  
Descriptor  
Name of Data Array  
where data is to be  
stored in the  
Legal Values  
Up to 32 alphanumeric  
characters  
Map_Descriptor_Name  
Data_Array_Name  
One of the Data Array  
names from “Data Array”  
section above  
FieldServer  
Starting location in Data 0 to maximum specified in  
Data_Array_Offset  
Function  
Array  
“Data Array” section above  
Function of Client Map  
Descriptor  
RDBC, WRBC, WRBX  
4.4.2.  
Driver Related Map Descriptor Parameters  
Column Title  
Node_Name  
Function  
Name of Node to fetch  
data from  
Legal Values  
Client Side Nodes  
File_Type  
File type in PLC  
N, B, F, S  
0-255  
File_Number  
File Number in PLC  
Starting address of read  
block  
Address  
0 – 255  
Data_Array_Low_Scale*  
Data_Array_High_Scale*  
Scaling zero in Data Array -32767 to 32767, 0  
Scaling max in Data Array  
-32767 to 32767, 100  
Scaling zero in Connected  
Node  
Scaling max in Connected  
Node  
Override the default  
command  
Node_Low_Scale*  
Node_High_Scale*  
AB_Command  
-32767 to 32767, 0  
-32767 to 32767, 100  
Unprotected Command  
Typed  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8704-07_AB-CSP Manual  
Page 9 of 15  
4.4.3.  
Map Descriptor Example  
// Client Side Map Descriptors  
Map_Descriptors  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, File_Type, File_Number, Address, Length, Scan_Interval  
CMD_AI_01,  
CMD_AO_01,  
DA_AI_01,  
DA_AO_01,  
0,  
0,  
RDBC,  
RDBC,  
PLC_01,  
PLC_01,  
N,  
N,  
10,  
11  
0,  
0,  
16,  
16,  
1.0s  
1.0s  
Map_Descriptors  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, File_Type, File_Number, Address, Length, Scan_Interval  
CMD_DI_01,  
CMD_DO_01,  
DA_DI_01,  
DA_DO_01,  
0,  
0,  
RDBC,  
RDBC,  
PLC_01,  
PLC_01,  
B,  
B
12,  
13,  
0,  
0,  
16,  
16,  
1.0s  
1.0s  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8704-07_AB-CSP Manual  
Page 10 of 15  
5.  
Configuring the FieldServer as an AB_CSP Server  
5.1.  
Server Side Connection Descriptors  
Section Title  
Connections  
Column Title  
Function  
Specify which port the device  
is connected to the  
FieldServer  
Legal Values  
Adapter  
N1  
Protocol  
Specify protocol used  
AB_CSP  
Must be on the same  
subnet as the client or  
gateway  
Virtual IP address of  
FieldServer  
IP_Address optional  
Example  
// Server Side Connections  
Connections  
Adapter,  
N1,  
Protocol,  
AB_CSP,  
IP_address  
192.168.2.1  
5.2.  
Server Side Node Descriptors  
Section Title  
Nodes  
Column Title  
Function  
Legal Values  
Up to 32 alphanumeric  
characters  
Node_Name  
Provide name for node  
Node ID of physical server  
node  
Specify protocol used  
Specify PLC  
Node_ID  
Protocol  
1-255  
AB_CSP  
PLC_Type  
PLC3, PLC5, SLC5  
Communications type.  
Example  
// Server Side Nodes  
Nodes  
Node_Name,  
ABE_Srv_11,  
Node_ID,  
11,  
Protocol,  
AB_CSP,  
PLC_Type  
SLC5  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8704-07_AB-CSP Manual  
Page 11 of 15  
5.3.  
5.3.1.  
Server Side Map Descriptors  
FieldServer Related Map Descriptor Parameters  
Column Title  
Function  
Name of this Map  
Descriptor  
Name of Data Array  
where data is to be  
stored in the  
Legal Values  
Up to 32 alphanumeric  
characters  
Map_Descriptor_Name  
Data_Array_Name  
One of the Data Array  
names from “Data Array”  
section above  
FieldServer  
Starting location in Data 0 to maximum specified in  
Data_Array_Offset  
Function  
Array  
“Data Array” section above  
Function of Client Map  
Descriptor  
Server  
5.3.2.  
Driver Related Map Descriptor Parameters  
Column Title  
Function  
Legal Values  
One of the node names  
specified in “Server Side  
Nodes” above  
Name of Node to fetch  
data from  
Node_Name  
File_Type  
File type in PLC  
File number in PLC  
N, B, F, I, O, S  
0-255  
File_Number  
Starting address of read  
block  
Address  
0 - 255  
Data_Array_Low_Scale*  
Data_Array_High_Scale*  
Scaling zero in Data Array -32767 to 32767, 0  
Scaling max in Data Array  
-32767 to 32767, 100  
Scaling zero in Connected  
Node  
Scaling max in Connected  
Node  
Node_Low_Scale*  
Node_High_Scale*  
-32767 to 32767, 0  
-32767 to 32767, 100  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8704-07_AB-CSP Manual  
Page 12 of 15  
5.3.3.  
Map Descriptor Example  
// Client Side Map descriptors  
Map_Descriptors  
Map_Descriptor_Name,  
SMD_AI_01,  
Data_Array_Name,  
DA_AI_01,  
DA_AO_01,  
Data_Array_Offset,  
0,  
0,  
Function,  
Server,  
Server,  
Node_Name,  
ABE_Srv_11,  
ABE_Srv_11,  
File_Type,  
N,  
N,  
File_Number,  
10,  
11,  
Address,  
0,  
0,  
Length,  
16,  
16,  
Data_Array_Low_Scale,  
0,  
0,  
Data_Array_High_Scale,  
100,  
100,  
Node_Low_Scale,  
0,  
0,  
Node_High_Scale  
100  
100  
SMD_AO_01,  
Map_Descriptors  
Map_Descriptor_Name,  
SMD_DI_01,  
Data_Array_Name,  
DA_DI_01,  
DA_DO_01,  
Data_Array_Offset,  
0,  
0,  
Function,  
Server,  
Server,  
Node_Name,  
ABE_Srv_11,  
ABE_Srv_11,  
File_Type,  
B,  
B,  
File_Number,  
12,  
13,  
Address,  
0,  
0,  
Length  
16  
16  
SMD_DO_01,  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8704-07_AB-CSP Manual  
Page 13 of 15  
Appendix A. Troubleshooting  
Appendix A.1. Continuous Map Descriptors  
RS View has been known to crash if it tries to read a server mapping that is discontinuous.  
e.g.  
Server map 1: N21: 0-31  
Server map 2: N21: 32-100  
This will crash RS view as the AB_CSP will attempt to map N21: 0-100  
If set up as  
Server Map 1: N21: 0-100, no problems are experienced  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8704-07_AB-CSP Manual  
Page 14 of 15  
Appendix B. Command Support  
The following commands are supported by the FieldServer for the various PLC types:  
Typical  
Command  
PLC_Type File_type FNC Read  
FNC Write  
N
F
B
N
F
B
1
1
1
1
1
1
Range Read  
Range Read  
Range Read  
Range Read  
Range Read  
Range Read  
Protected Typed  
Logical Read  
Protected Typed  
Logical Read  
Protected Typed  
Logical Read  
Protected Typed  
Logical Read  
Protected Typed  
Logical Read  
0
0
2
0
67  
26  
Range Write  
Range Write  
Bit Write  
Range Write  
N7: 3, L5  
PLC3  
PLC5  
F12: 3, L5  
B3/4: 5, l5  
N7: 3 , L5  
F12: 3, L5  
B3/4: 5, L5  
Typed Write  
Read Modify Write  
Protected Typed  
Logical Write  
Protected Typed  
Logical Write  
Protected Typed  
Logical Write  
N
F
B
I
A2  
A2  
A2  
A2  
A2  
A2  
AA  
AA  
AB  
-
N7: 3, L5  
B3/4: 5, L7  
B3/4: 5, L8  
I: 13, L5  
SLC5  
-
-
O
S
-
O: 13, L5  
52: 3, L5  
Protected Typed  
Logical Read  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8704-07_AB-CSP Manual  
Page 15 of 15  
Appendix C. Revision History  
Driver Doc.  
Date  
Resp Format  
Comment  
Ver.  
Rev.  
2/3/04  
MF  
MF  
1.00  
1
Formatting updated. Revision table added.  
Added connection diagram. Converted final  
chapters to appendices. Removed nonsense  
text.  
5/6/04  
Meg Meg  
JD  
1.00  
1.00  
2
3
6/14/04  
Releasing  
Changed Appendix numbering to letters and  
added borders and shading. Corrected example  
table formatting. Removed some commas in  
12/27/04 Meg Meg  
1.00  
4
example.  
Created Troubleshooting section.  
DUR0522.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  

MTD 244 640A000 User Manual
Kenwood KDC M9021 User Manual
Huawei Technologies Cell Phone Y 101 User Manual
HTC Dash 3G User Manual
Hitachi CP L540E User Manual
Furuno FS 1503 User Manual
Fujitsu MCM3064SS User Manual
Cecilware Ground Coffee Dispensers User Manual
Carrier WEATHERMASTER 48ZG User Manual
Apple XSERVE RAID User Manual