FieldServer FS 8700 41 User Manual

-
A Sierra Monitor Company  
Driver Manual  
(Supplement to the FieldServer Instruction Manual)  
FS-8700-41 Simplex Time Recorder  
Company - 4100 Computer Port Protocol  
APPLICABILITY & EFFECTIVITY  
Effective for all systems manufactured after May 1, 2001  
Driver Version:  
1.07  
Document Revision: 8  
FS-8700-41 Simplex Driver Manual  
Table of Contents  
Appendix A.11. Advanced Map Descriptor Example 2. - Read Panel Time.........................33  
Appendix A.12. Advanced Map Descriptor Example 3 - Write Panel Time..........................34  
Appendix A.13. Advanced Map Descriptor Example 4 - Panel Revision Information...........34  
Appendix A.14. Advanced Map Descriptor Example 5 - AckAll ...........................................35  
Appendix A.15. Advanced Map Descriptor Example 6 - Silence / Reset .............................35  
Appendix A.16. Advanced Map Descriptor Example 7 - Acknowledge a specific point........36  
Appendix A.17. Advanced Map Descriptor Example 8 - ClearAll.........................................37  
Appendix A.18. Advanced Map Descriptor Example 9 - Earths...........................................38  
Appendix A.19. Advanced Map Descriptor Example 10 - Show ..........................................39  
Appendix A.20. Using Clist to Write-Through and Store point status from Unsolicited  
Messages41  
Appendix B. Troubleshooting Tips....................................................................................42  
Appendix B.1. Address Errors.............................................................................................42  
Appendix B.2. Driver Limitations .........................................................................................42  
Appendix B.3. Resolving Network Addresses above 255....................................................43  
Appendix C. Error Messages .............................................................................................44  
Appendix D. Pseudo Points ...............................................................................................49  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 4 of 58  
1.  
Simplex Time Recorder Company - 4100 Computer Port Protocol  
The Simplex Time Recorder Company - 4100 Computer Port Protocol driver allows the  
FieldServer to transfer data to and from devices over either RS-232 or RS-485 using Simplex  
Time Recorder Company - 4100 Computer Port Protocol.  
This driver is designed to connect to a Simplex 4100 panel equipped to support the “4100  
Computer Port Protocol” as defined in Simplex’s document 950-004 Revision E dated 28 July  
2000. The implementation provides a selected subset of protocol functions and subset of  
functionality for each of these selected functions. It is important to note the exclusions and  
limitations described in this document.  
The driver is a capable of parsing and storing information sent by a panel in the form of  
unsolicited messages which are typically generated when there is a state change in the panel or  
one of the connected devices. The driver is also capable of polling for point and panel status  
data and some additional data such as the panel’s time and revision information. In addition the  
driver is capable of setting some control points in the panel – acknowledging and resetting  
alarms and writing data (where permitted) to some analog and discrete points.  
This is a client only driver and is not capable of emulating a Simplex Panel. Server emulation is  
provided for test purposes only and is not supported or documented.  
1.1.  
Supported Panel Types  
The driver has been tested against 4020, 4100 and 4100U panels. There is no difference in  
the protocol format between the various panels. What changes is the panel firmware version  
and with the firmware changes the supported function set changes.  
1.2.  
Simplex Panel Firmware Revision vs. Supported Functionality  
This driver was primarily tested against a 4020 panel with firmware revision 9.2. Beta testing  
against a 4100 panel with a firmware revision 10.x was also performed.  
A grid of firmware revision number and supported functions is provided by Simplex. This  
grid is available from Simplex. Request the ‘CPP Revision Compatibility’ Table.  
All the functions described in this manual are supported for firmware revisions 10 or higher.  
For revisions between 9.2 and 10, the ‘Earths’ and ‘Value’ functions described in this driver  
are not supported by the Simplex Panels. For revisions lower than 9.2, then functions  
supported need to be determined by trial and error. We are fairly confident that all the  
functions supported by version 9x are also supported by versions 8x of the panel firmware.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 5 of 58  
2.  
Driver Scope of Supply  
2.1. Supplied by FieldServer Technologies for this driver  
FieldServer Technologies  
PART #  
Description  
FS-8917-16  
Ethernet Cable with pigtail (4020 and 4100 Panels)  
Ethernet cable with 25 pin male connector. (4100u  
Panels)  
FS-8917-07  
SPA59132  
RS-485 connection adapter  
FS-8700-41  
Driver Manual.  
2.2.  
Provided by Supplier of 3rd Party Equipment  
To enable the 4100 Protocol, the 4100 system, supplied by the user, must have a free RS-  
232 port dedicated for use with the computer device. In most cases, this is not included in  
the base configuration of the product provided by The Simplex Time Recorder Company,  
and must be added as a sales option. All 4100 systems limit the number of computer ports  
active at one time in a system. To determine the limit for the specific product configuration,  
refer to the specific product specifications, or contact a Simplex sales representative.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 6 of 58  
3.  
Hardware Connections  
The FieldServer is connected to the Simplex Device’s RS-232 port of device type  
"COMPUTER", the following port attributes may be configured specifically for that particular  
port:  
Ensure that these settings correspond to the settings described in section 4 of this document.  
Sim4100 Panel  
Setting  
Baud Rate 9600  
Parity  
Default Options  
75, 110, 134.5, 300, 600, 1200, 1800, 2000, 2400, 4800, 9600, 19200  
EVEN1 ODD, EVEN, MARK, SPACE, NONE  
Data Bits  
Stop Bits  
8
1
7 or 8  
1 or 2  
Sim4100U Panel  
Setting Default Options  
Baud Rate 9600 75, 110, 134.5, 300, 600, 1200, 1800, 2000, 2400, 4800, 9600, 19200  
NONE1 ODD, EVEN, MARK, SPACE, NONE  
Parity  
Data Bits  
Stop Bits  
8
1
7 or 8  
1 or 2  
The following are the Simplex, recommended connections to be used in cabling between the  
4100 and the FieldServer device. For the computer device, the standard EIA signal description,  
and the 25 pin (DB25) and 9 pin (DB9) connector assignments are shown.  
4100 Host  
4100  
Port  
Computer  
DB25Pin  
Cable  
Signal  
Signal  
DB9Pin  
Port  
ATB1  
DB25 Pin  
BTB2  
8
6
7
5
4
1
3
2
4
5
2
3
4
5
7
TXD  
RXD  
RTS  
CTS  
GND  
RXD  
TXD  
RTS  
CTS  
GND  
2
3
4
5
7
2
3
7
8
5
2
──  
1
Odd or Even parity is recommended (by Simplex) to provide additional error detection at the character  
level.  
2 Note, that if HSHAKE is not used (Simplex Device Setting), the connections between RTS and CTS are  
not required  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 7 of 58  
3.1.  
Connection to a Simplex 4020 Panel  
Communication Board  
Chip 4100 RS2120  
Card 4020/RS-232/2120 modem ready  
assembly.  
Terminal Block Markings  
Port A =1-5, Port B=6-10.  
1=+com(xmt).  
2=+com(rts),  
3=-com(rcv),  
4=-com(cts),  
5=gnd,  
6=xmt,  
7=rts,  
8=rcv,  
9=cts,  
10=gnd,  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Serial Connection  
Page 8 of 58  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 9 of 58  
3.2.  
Connection to a Simplex 4100 Panel  
WIRE LIST  
FROM SIMPLEX 4100  
FS-X40  
FUNCTION  
RX  
TX  
GND  
PANEL  
XMIT  
RCV  
RJ45-01  
RJ45-08  
RJ45-04  
GND  
SIMPLEX 100  
PANEL  
PORT B  
CONNECTION  
GND  
CTS  
RCV  
RTS  
XMIT  
FS-8917-16  
P1-P8  
P1  
P2  
P3  
P4  
P5  
P6  
P7  
P8  
R1  
R2  
N1 N2  
RS485  
10 Base T  
ETHERNET  
RS232  
P1  
P2  
P3  
P4  
P5  
P6  
P7  
P8  
Rx Tx  
R1  
Rx Tx  
R2  
Rx Tx  
Net  
1
Net  
2
Rx Tx Rx Tx Rx Tx Rx Tx Rx Tx Rx Tx Rx Tx  
Tx Rx Con Tx Rx Con  
(408)-262-2299  
SIMPLEX 4100  
CONNECTION DIAGRAM  
BASE NAME:  
FILE NAME: FS-T28700-41 .VSD  
DATE: 09/26/07  
BY: MN  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 10 of 58  
3.3.  
Connection to a Simplex 4100U Panel  
Front of 4100U Panel  
Port A  
Port B  
Pin 3 - Blue  
Pin 7 - Green  
Pin 2 - White  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 11 of 58  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 12 of 58  
4.  
Configuring the FieldServer as a Simplex Time Recorder Company - 4100  
Computer Port Protocol Client  
For a detailed discussion on FieldServer configuration, please refer to the relevant instruction  
manual. The information that follows describes how to expand upon the factory defaults  
provided in the configuration files included with the FieldServer (See “.csv” files provided with  
the FieldServer).  
This section documents and describes the parameters necessary for configuring the FieldServer  
to communicate with a Simplex Time Recorder Company - 4100 Computer Port Protocol  
Server.  
The configuration file tells the FieldServer about its interfaces, and the routing of data required.  
In order to enable the FieldServer for Simplex Time Recorder Company - 4100 Computer Port  
Protocol communications, the driver independent FieldServer buffers need to be declared in the  
“Data Arrays” section, the destination device addresses need to be declared in the “Client Side  
Nodes” section, and the data required from the servers needs to be mapped in the “Client Side  
Map Descriptors” section. Details on how to do this can be found below.  
Note that in the tables, * indicates an optional parameter, with the bold legal value being the  
default.  
4.1.  
Data Arrays  
Section Title  
Data_Arrays  
Column Title  
Data_Array_Name Provide name for Data Array  
Function  
Legal Values  
Up to 15 alphanumeric characters  
Provide data format. Each Data FLOAT, BIT, Uint16, Sint16,  
Data_Format  
Array can only take on one  
format.  
Packed_Bit, Byte, Packed_Byte,  
Swapped_Byte  
Number of Data Objects. Must  
Data_Array_Length be larger than the required data 1-65535  
storage area.  
Example  
// Data Arrays  
Data_Arrays  
Data_Array_Name,  
DA_AI_01,  
DA_AO_01,  
DA_DI_01,  
Data_Format,  
UInt16,  
UInt16,  
Bit,  
Data_Array_Length  
200  
200  
200  
200  
DA_DO_01,  
Bit,  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 13 of 58  
4.2.  
Client Side Connection Descriptions  
Section Title  
Connections  
Column Title  
Function  
Specify which port the device is connected  
to the FieldServer  
Legal Values  
P1-P8, R1-R23  
Port  
110 – 115200, standard baud  
rates only.  
Even, Odd, None, Mark,  
Space  
Baud*  
Parity*  
Specify baud rate  
Specify parity  
Data_Bits*  
Stop_Bits*  
Protocol  
Specify data bits  
Specify stop bits  
7, 8  
1
Specify protocol used  
sim4100  
Handshaking* Specify hardware handshaking  
RTS, RTS/CTS, None  
0-32000 seconds, 1 second  
Poll Delay*  
Time between internal polls  
Example  
//    Client Side Connections  
Connections  
Port,  
P8,  
Protocol,  
Sim4100,  
Baud,  
9600,  
Parity,  
Even,  
Handshaking,  
None,  
Poll_Delay  
0.100s  
4.3.  
Client Side Node Descriptors  
Section Title  
Nodes  
Column Title  
Function  
Legal Values  
Node_Name Provide name for node  
Up to 32 alphanumeric characters  
This parameter is IGNORED. Special  
keywords to define the card-sub-point  
are described in section 4.4  
Sim4100  
Node_ID  
Ad  
Protocol  
Port  
Specify protocol used  
Specify which port the device is  
connected to the FieldServer  
Required for Simplex4100 Panels.  
If not specified then a Simplex  
4100/4020 panel is assumed.  
P1-P8, R1-R23  
PLC_Type* 4020/4100 - panels with firmware  
version 9x or earlier.  
4100, 4020, 4100U  
4100U – panels with firmware  
version 10x or later.  
3 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction  
manual for details of the ports available on specific hardware.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 14 of 58  
Example  
// Client Side Nodes  
Nodes  
Node_Name,  
Device1,  
PLC_Type,  
4100U,  
Protocol,  
Sim4100,  
Connection  
P8  
4.4.  
Client Side Driver Tables  
A driver table is used to extend a table of values/attributes that have been hard coded into  
the driver. It is possible to extend the tables using CSV file parameters.  
Additional information on the use of these tables may be found in Appendix A.8  
4.4.1. SHOW Response Attributes Driver Table  
Column Title  
Function  
Legal Values  
The protocol must be specified on each row  
of a driver table.  
Protocol  
Sim4100  
The exact  
character  
sequence that  
must be  
The SHOW command response consists of  
a number of attributes and their current  
state/ values.  
sim4100_Attr_Name  
sim4100_Attr_Offset  
specified. May  
include an equal  
sign.  
Use this parameter to add a new attribute to  
the table.  
If the response contains the attribute defined  
above, its current state/value must be stored  
at offset x in the associated Data Array.  
Use this parameter to define x. Take care to  
leave enough space for those attributes  
which have multiple values.  
May not be zero.  
This parameter tells the driver how to  
convert the current state/value for storage in  
the Data Array. For example, the driver  
cannot store the state ‘Normal’ . By  
1,2,3  
May not be zero.  
sim4100_Attr_Method specifying method 1, you tell the driver to  
use the state descriptor ‘Normal’ in a lookup  
table of attribute states to find the value  
associated to Normal and to store that  
value.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 15 of 58  
4.4.2. SHOW Response Attribute States Driver Table  
Column Title  
Function  
Legal Values  
The protocol must be  
Protocol  
specified on each row of Sim4100  
a driver table.  
Use this parameter to  
extend this list of  
predefined attribute  
states.  
Define a state word such as  
‘Normal’ and associate a  
value using the ‘value’  
parameter.  
sim4100_Attr_State_Name  
This parameter is the  
sim4100_Attr_State_Value value to be associated  
with the ‘name’  
May not be zero.  
4.5.  
Client Side Map Descriptors  
4.5.1. FieldServer Specific Map Descriptor Parameters  
Column Title  
Function  
Name of this Map  
Descriptor  
Legal Values  
Up to 32 alphanumeric  
characters  
Map_Descriptor_Name  
Name of Data Array where  
data is to be stored in the  
FieldServer  
One of the Data Array  
names from “Data Array”  
section above  
Data_Array_Name  
Starting location in Data  
Array  
Function of Client Map  
Descriptor  
0 to maximum specified in  
“Data Array” section above  
Data_Array_Location  
Function  
RDBC, WRBC, WRBX  
4.5.2. Driver Specific Map Descriptor Parameters  
Column Title Function  
Legal Values  
One of the node  
names specified in  
“Client Node  
Node_Name Name of Node to fetch data from  
Descriptor” above  
Length of Map Descriptor - must always be  
specified.  
If the length of the response (such as errors /  
earths, show, revision) is not known in advance it  
should be set to a value large enough to store to  
allow some contingency. If data cannot be stored  
because an array is too short the driver will  
produce a message in the error log.  
Length  
Not required. The address is specified by using the card-point-sub  
specification described in section 4.4.2  
Address  
4.5.3. Timing Parameters  
Column Title  
Scan_Interval  
Function  
Rate at which data is polled  
Legal Values  
>0.1s  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 16 of 58  
4.5.4. Protocol (Simplex Device) Specific Parameters  
Column Title  
Function  
Legal Values  
Further notes on  
these keywords  
are provided in  
Appendix A  
Ackall, Setd,  
Disable, Restart,  
Clistall, Clist,  
Time, Ctime,  
Ack,  
A keyword which controls the function being  
performed or the type of data being polled /  
written.  
sim4100_func  
Xpoint, Seta,  
Super, Show,  
Earths, Value,  
ClearAll  
The Simplex Time Recorder Company - 4100 Computer Port Protocol only uses the  
standard 4100 address format of <Card>-<Point>-<Sub-point>. Symbolic addressing is  
not supported. The following keywords are used to address devices.  
Further notes  
and examples  
are provided in  
Appendix A  
sim4100_Card  
sim4100_Point  
sim4100_Sub  
Simplex Address <Card>  
Simplex Address <Point>  
Simplex Address <Sub_Type>  
Only appropriate when the  
sim4100_func=clist.  
Controls the write through behavior of the  
clist function. See Appendix A.20 for  
additional information.  
When using the default value then the write  
commands are done using the format SET  
c-p-s ON/OFF. If the parameter is set to  
value then writes are done using the format  
SET c-p-s value.  
sim4100_WriteThru*  
Store_Unsolicited*  
Onoff, value  
Control the ability of ‘CLIST’ map descriptors  
to be used to store data from unsolicited  
messages. Refer also to Appendix A.20  
Yes/No  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 19 of 58  
5.  
Configuring the FieldServer as a Simplex Time Recorder Company - 4100  
Computer Port Protocol Server  
The driver contains some server side functionality which has been developed to meet  
FieldServer’s continuous quality assurance efforts. However, the server side functions are not  
documented or supported for customer use. If you have a strong requirement for this  
functionality then please contact the Sales and Marketing group of FieldServer.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 20 of 58  
Appendix A. Advanced Topics  
Appendix A.1. Hardware Handshaking  
The driver does not support the Simplex RTS/CTS handshaking model. Therefore deselect  
the HSHAKE terminal flag or connect CTS to RTS with a jumper on the 4100 side.  
Appendix A.2. Simplex Address Formatting – Specific Keywords  
The Simplex Time Recorder Company - 4100 Computer Port Protocol only uses the  
standard 4100 address format of <Card>-<Point>-<Sub-point>. Symbolic addressing is not  
supported. The following table lists keywords which control the behavior of the FieldServer  
with respect to connection to a Simplex device and the permissible values determining the  
type of data being read/written.  
Keyword  
Description  
This command acknowledges all card-point-sub states  
based on the values found in the associated arrays.  
The FieldServer watches the Data Array to see if we need  
to send an ack.  
Function  
DA element Accepted  
1st – ack all  
2nd - ack A  
3rd – ack F  
4th – ack P  
5th – ack S  
6th – ack T  
7th – ack C  
primary abnormal state  
Fire alarm  
Priority 2  
Supervisory  
Trouble  
Control  
WRBC  
Do not specify c-p-s in  
the Map Descriptor.  
Ackall  
Set the array element to 1 to initiate the command. The  
FieldServer clears the value on completion.  
This command allows the user to acknowledge a single  
point. The specified Data Array is inspected and the value  
of the single element is used to determine which device  
state's are ack'd. Refer to Appendix A.4  
WRBC  
Specify c-p-s in the  
Map Descriptor.  
Ack  
RDBC  
Specify c-p-s in the  
Map Descriptor.  
This command returns the current point status for one  
point. Refer to Appendix A.4 and Appendix A.20  
Clist  
This function obtains earth/ground status information from  
the panel. Two Data Array elements are used to store the  
normal (=1) or abnormal (=2) for each card. The first  
element is for the positive ground and the second element  
is the negative ground. Where cards do not report both,  
the first element of the pair is used.  
The array position is obtained by multiplying the card  
number by two and adding the offset specified in the Map  
Descriptor. Set the length of this Map Descriptor to twice  
the value of the maximum card number.  
RDBC  
Do not specify c-p-s in  
the Map Descriptor.  
Earths4  
4 This driver function used the Simplex ‘CSHOW c-p-s CVAL’ command. It is only supported by panels  
with firmware revision numbers greater than 10  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 21 of 58  
Function  
Keyword  
Description  
Stores analog value(s) read from a particular devicewithout  
scaling or units. When more than one value is reported the RDBC  
Value  
driver stores the values in consecutive array elements.  
Ensure that the Map Descriptor’s usage of the Data Arrays  
is spaced appropriately.  
Specify c-p-s in the  
Map Descriptor.  
Each type of Simplex device reports a different set of  
attributes and attribute states/values. Refer to Appendix  
A.8 for more information. The driver analyses the response  
from the poll. When an attribute is recognized, the attribute  
state is evaluated. If this is recognized then the driver  
stores a value, corresponding to the attribute state, at an  
array location corresponding to the attribute. 4.4 provides  
additional information. The driver can only recognize  
attributes and attribute states that it is programmed to  
recognize.  
RDBC  
Specify c-p-s in the  
Map Descriptor.  
Show  
Using the information provided in Appendix A.8, set the  
length of the Map Descriptor equal to array position of  
highest attribute.  
Ensure that Map Descriptors using this function do not use  
overlapping areas of the Data Arrays. See example in  
Appendix A.19.  
This command allows the user to manipulate the status  
and/or priority of a control point  
The port access level must be set appropriately in the  
Simplex device otherwise the device returns an error.  
This command allows the user to:  
WRBC  
Specify c-p-s in the  
Map Descriptor.  
Setd  
Seta  
Manipulate the status and/or priority of a control point  
Modify the value of an analog pseudo point.  
Set the sensitivity of a TrueAlarm sensor  
Set the rate-of-rise threshold of a TrueAlarm heat  
sensor  
WRBC  
Specify c-p-s in the  
Map Descriptor.  
Select the audio channel of a speaker circuit  
Point Status Change. This is an unsolicited message sent  
automatically by a Simplex device to report a change in  
point status. The card-point-sub is used to calculate an  
offset into the associated Data Array. Read Appendix A.4 to  
understand this better.  
Passive  
Xpoint  
Specify c-p-s in the  
Map Descriptor.  
The state being reported determines the value being written  
into the Data Array. Read Appendix A.5 to understand this  
better.  
Disable  
Restart  
Not Implemented  
Not Implemented  
This command sets and displays the time and date in  
"user" format.  
As a command it sets the hour minute second of the  
Simplex device by getting the values from the Data Array  
associated with the Map Descriptor. The first element  
contains the hour, the second the minute and the third  
contains the second. A 24 hour clock is assumed.  
As a query, the data is unpacked into the Data Array in the  
same format as described above.  
RDBC (Query) or  
WRBC (Set)  
Do not specify c-p-s in  
the Map Descriptor.  
Time  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 22 of 58  
Function  
Keyword  
Description  
As a command it sets the hour minute second of the  
Simplex device by getting the values from the Data Array  
associated with the Map Descriptor. The first element  
contains the hour, the second the minute, the third element RDBC (Query) or  
contains the second, the 4th contains the day of the week,  
the 5th contains the month, the 6th contains the day of the  
month and the 7th element of the array contains the year  
(value 01 indicates 2001). A 24 hour clock is assumed.  
As a query, the data is unpacked into the Data Array in the  
same format as described above.  
WRBC (Set)  
Do not specify c-p-s in  
the Map Descriptor.  
Ctime  
Used to send a silence signal to the Simplex device. This  
is a triggered command. When the element in the Data  
Array associated with the Map Descriptor is set to 1 then  
the command is sent to the Simplex device. The driver will  
set the value to zero when the command has been  
acknowledged.  
Used to send a reset signal to the Simplex device.  
This is a triggered command. When the element in the  
Data Array associated with the Map Descriptor is set to 1  
then the command is sent to the Simplex device. The  
driver will set the value to zero when the command has  
been acknowledged.  
WRBC  
Do not specify c-p-s in  
the Map Descriptor.  
Silence  
Reset  
WRBC  
Do not specify c-p-s in  
the Map Descriptor.  
Used to request revision information from the Simplex  
panel. Use of this Map Descriptor is recommended as it  
allows the driver to generate a warning if an unknown  
Simplex revision is encountered.  
RDBC  
Do not specify c-p-s in  
Revision  
Make sure that the length of the Map Descriptor is sufficient the Map Descriptor.  
to store all the revision information. A Length of 200 is  
recommended.  
Passive  
Do not specify c-p-s in  
the Map Descriptor.  
If using RUINET to  
monitor the  
FieldServer, display  
Use this keyword to define a Map Descriptor which tells the the Data Array  
driver where to store error messages received from the  
Simplex device. The most recent message is stored in the  
Data Array specified. Make sure that the Data Array length  
is long enough to store enough meaningful information. A  
length of 200 is recommended.  
associated with this  
Map Descriptor in  
‘String’ format so that  
you can read the error  
message easily. The  
driver appends  
Errors  
information about the  
Map Descriptor which  
generated the error to  
make the error more  
easily understandable.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 23 of 58  
Function  
Keyword  
Description  
Map Descriptor’s which use this function do two things;  
Firstly, they register a c-p-s with the driver.  
Secondly they define a Data Array name and element  
range that must be set to zero when the ClearAll function is  
activated.  
Up to 4 c-p-s’s may be registered per FieldServer. These  
registered points are monitored each time a Clist response  
is obtained as well as each time the panel sends an  
unsolicited Xpoint message with a state change. If one of  
these messages reports a ‘U1’ state for a registered point  
then the driver processes all ‘ClearAll’ Map Descriptor’s  
and sets all the associated array values to zero.  
An example of the use of ClearAll is provided in section  
6.12 example 9.  
Passive  
Specify c-p-s in the  
Map Descriptor (but  
read the notes on the  
left)  
ClearAll  
Generates a warm restart message.  
Used to test the driver.  
Used for simulation  
only.  
Used for simulation  
only.  
Warm_Start  
Cold_Start  
Generates a cold restart message. Used to test the driver.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 24 of 58  
Appendix A.2.1.  
Sim4100_Card Keyword  
The FieldServer will accept any positive integer number including zero; however, not all  
values are valid for Simplex devices. Refer to Note (1).  
Many commands and output message contain system point ID fields. These fields  
reflect the way a 4100 point (local, external, real, pseudo), is referred to.  
There are two basic formats allowed, address format <apoint>, and symbolic format  
<spoint>.  
In the Simplex device the terminal ADDRESS flag is set (DEFAULT) so that <apoint> is  
always used in computer messages; otherwise, the symbolic form is used. The  
FieldServer cannot work with symbolic (spoint) addresses.  
Appendix A.2.2.  
<apoint>  
Format <card>-<point>-<sub>  
Legend:  
<card>  
<point>  
<sub>  
Examples:  
0-6-6  
4100 card, pseudos included, See note (1)  
4100 point (sometimes slot), See note (2)  
4100 sub-point (sometime point), See note (2)  
Master trouble point (LCD trouble)  
Typical card status point, card at address 5  
Point 1 for card at address 3  
5-0-1  
3-1-0  
Notes:  
(1)  
The following ranges are valid for Simplex Devices:  
Card address Card type  
0-119  
Physical (Hardware) cards  
Digital Pseudo cards  
Analog Pseudo cards  
List Pseudo cards  
128-143  
144-159  
160-175  
(2)  
The range of point and sub-point fields for point addressing is very sparse and  
depends on the type of card at that location. Contact Simplex Time Company for details  
on point address ranges for specific cards.  
Appendix A.2.3.  
Sim4100_Point Keyword  
The FieldServer will accept any positive integer number including zero; however, not all  
the values are valid for Simplex devices - see Sections 6.3 and 6.4 for further  
information.  
Appendix A.2.4.  
Sim4100_sub Keyword  
The FieldServer will accept any positive integer number including zero; however, not all  
the values are valid for Simplex devices - see Sections 6.3 and 6.4 for further  
information.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 25 of 58  
Appendix A.3. How to use Data Arrays to map to/from Card-Point-Sub  
addresses  
Some commands derive a card-point-sub address by inspecting a FieldServer Data Array.  
Others receive data from a device with a card-point-sub address and modify the data in an  
array based on the card-point-sub address. This section explains how to make the  
connection between an index into a Data Array and a card-point-sub address.  
In a simple world the Data Array index would be  
Index = card * max point per card * max sub point per point + point * max sub point per point  
+ sub  
Where max point per card and max sub point per point could be large numbers.  
As you can imagine this would require huge sparse Data Arrays. To reduce the Data Array  
size the FieldServer uses a mapping algorithm which can be optimized based on the  
addresses of the Simplex devices. The map is manipulated by using the  
sim4100_card/point/sub parameter values.  
Example:  
Consider the following Map Descriptor fragment.  
… ,  
sim4100_func, sim4100_card, sim4100_point, sim4100_sub, data_array_offset  
Xpoint, 5, 10,  
10,  
0
If data is received for point <c>-<p>-<s> = 9-0-0  
This data will NOT be processed because the card number does not match the value of the  
sim4100-card  
If data is received for point <c>-<p>-<s> = 10-20-0, however, the data will be processed.  
The array location is derived using the following formula (sim4100_sub is to be read as the  
“number of sub-points per point”; sim4100_card’s value will be ignored.)  
Location  
= data_array_offset + <p> * sim4100_sub + <s>  
= 0 + 20 * 10 + 0 = 200  
Appendix A.4. Simplex Point Status Data Format  
When a point status is obtained the FieldServer will write one byte of data to a Data Array.  
The byte will contain the following information. Because each point can report a number it  
only makes sense to use Data Arrays that are not bit arrays.  
Bit  
Identifier  
Description  
0 (First Bit)  
F
Fire Alarm  
Priority 2  
Supervisory  
Trouble  
Utility  
Control  
1
2
3
4
5
6
7
P
S
T
U
C
D
A
Disable  
Primary state (based on point type - F if smoke detector, C if signal  
circuit, etc.)  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 26 of 58  
Appendix A.5. Simulation of the Xpoint command  
The following notes apply only to FieldServer Technologies engineers.  
The sim4100_func=xpoint keyword is used to parse unsolicited point status change  
messages sent by Simplex devices. For simulation purposes it a wrbc version of this  
function has been implemented to test the response parsing ability of the slave portion of the  
driver.  
Appendix A.6. Application Supervision Messages  
Section 7.2 of the Simplex 4100 protocol describes unsolicited messages from a Simplex  
device. This sim4100_func=super wrbc command is used to test the driver's ability to parse  
these messages.  
The 4100 protocol supports a periodic application supervision message. This supervision  
poll is performed if the TERMINAL flag POLL is set (COMPUTER DEFAULT). The objective  
of the supervision poll is two-fold:  
It is the only periodic message that can be expected to be sent by the 4100, thus  
establishing the basis for supervising the line.  
To ensure that all layers of the two systems are operating properly and able to respond  
to messages. For example, in a PC implementation that uses a Terminate-and-Stay-  
Resident (TSR) device driver to implement the protocol, the answer to the supervision  
poll should be done in a way such that if the program exits to DOS, the TSR will not  
continue to indicate to the 4100 that everything is OK, when in fact, the PC will not be  
able to annunciate an alarm.  
Appendix A.7. Driver Stats  
Appendix A.7.1.  
How the Driver counts bytes and messages  
received and transmitted.  
"Ack" messages sent/received by the driver in response to read/write messages are  
NOT counted as messages. However, the single byte produced by these messages is  
included in the byte count.  
The driver does not count DLL layer messages as messages.  
The driver counts bytes at the DLL layer. The byte count includes the bytes that wrap  
application layer messages, acks and the port supervision and responses messages.  
The driver counts messages at the application layer.. This means that if you use  
RUINET to monitor the FieldServer and you view the Map Descriptor’s the byte count  
stats will always be zero.  
Some Map Descriptors require data in the Data Arrays to trigger a write command. An  
example is the "Ack" command. The driver does not count one of these messages as  
being sent until the array actually triggers a poll to be sent.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 27 of 58  
Appendix A.7.2.  
Driver Exposed Stats  
The driver is capable of exposing statistics about its behavior in a Data Array. It is  
necessary to create a Data Array with name sim4100-stats as per the example below  
and it will be updated by the driver. Note that the stat number corresponds to the offset.  
Take care not to poke any values into the 1st 10 elements of this Data Array (offsets 0 to  
9). Doing so will trigger internal diagnostics and may interfere with normal operation.  
A different set of stats is maintained for each connection. Each connection uses 100  
elements of the data array. Ensure the array length is large enough if the port number is  
large.  
Data_Arrays  
Data_Array_Name,  
sim4100-stats  
Data_Format,  
UINT16  
Data_Array_Length  
1000  
,
,
At revision 1.07a of the driver and before, no stats had been exposed.  
Stat  
number  
Stats  
Description  
The Card in c-p-s from most  
recent xpoint store  
The Point in c-p-s from most  
recent xpoint store  
The SubPoint in c-p-s from  
most recent xpoint store  
The Qualifier from most recent  
xpoint store  
10  
SIM4100_STAT_XPOINT_CARD  
SIM4100_STAT_XPOINT_POINT  
SIM4100_STAT_XPOINT_SUB  
SIM4100_STAT_XPOINT_QUALIFIER  
11  
12  
13  
The Qualifier from most recent  
xpoint store, stored as an  
enumeration – See Note1 for  
bit states  
The reported state from most  
recent xpoint store. State  
value: 0 FALSE/Normal 1  
TRUE/Abnormal  
The reported ack state from  
most recent xpoint store. Ack  
state: *=needs ack, -=acked  
(always "-" for U or C states)  
The Time from most recent  
xpoint store  
The Time from most recent  
xpoint store  
The Time from most recent  
xpoint store  
The Date from most recent  
xpoint store  
The Date from most recent  
xpoint store  
14  
15  
16  
SIM4100_STAT_XPOINT_QUALIFIER_AS_ENUM  
SIM4100_STAT_XPOINT_STATE  
SIM4100_STAT_XPOINT_ACK_STATE  
17  
18  
19  
20  
21  
22  
SIM4100_STAT_XPOINT_HOUR  
SIM4100_STAT_XPOINT_MIN  
SIM4100_STAT_XPOINT_SEC  
SIM4100_STAT_XPOINT_DOW  
SIM4100_STAT_XPOINT_DAY  
SIM4100_STAT_XPOINT_MONTH  
The Date from most recent  
xpoint store  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 28 of 58  
Stat  
Stats  
number  
Description  
The Date from most recent  
xpoint store  
23  
SIM4100_STAT_XPOINT_YEAR  
A single point could potentially  
be active in more than one  
state simultaneously. The  
driver tracks the combine state  
by building a UINT whose bits  
indicate the state. This is the  
combo state before the update.  
See Note 1 for bit states.  
24  
SIM4100_STAT_XPOINT_COMBO_STATE_OLD  
A single point could potentially  
be active in more than one  
state simultaneously. The  
driver tracks the combine state  
by building a UINT whose bits  
indicate the state. This is the  
combo state after the update.  
See Note 1 for bit states.  
25  
SIM4100_STAT_XPOINT_COMBO_STATE_NEW  
Note 1 – Bit States.  
Qualifier:  
Enum=0 Qual=F Fire alarm state  
Enum=1 Qual=P Priority 2 alarm state  
Enum=2 Qual=T Trouble state  
Enum=3 Qual=S Supervisory state  
Enum=4 Qual=U Utility monitor, digital/analog pseudo state  
Enum=5 Qual=C Control state (non pseudo)  
Enum=6 Qual=D Disable Trouble state  
Appendix A.8. SHOW Function Attributes and Attribute States  
The Show command provides an ASCII response formatted for printing. The driver parses  
these messages and converts the data to numbers which can be sent to upstream devices  
using another protocol.  
The driver performs the following tasks in analyzing the response.  
On a line by line basis from the left, it searches for an attribute against a table of attribute  
strings. If an attribute string is found in the line then processing continues. Otherwise  
the line is discarded.  
The attribute number is recorded. It will be used to determine the array location where  
the attribute state/value will be stored.  
The attribute also determines the state/value extraction method and attempts to  
determine the attribute state/value using the appropriate method.  
o Method 1: The driver uses a table of attribute states, comparing them to the  
remainder of the line. If there is a match the driver stores the value of the  
attribute state in the array location determined by the attribute,  
o Method 2: The driver looks for (up to three) analog values separated by forward  
slashes.  
o Method 3: The driver looks for analog values preceded by an equal sign.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 29 of 58  
The driver stores in the first array location the number of response lines which resulted  
in attribute data being stored. This information can be used for trouble shooting.  
The following table reports the attributes that the driver recognizes. This list may be  
extended by changing the configuration. If, for example, the attribute ‘ENABLED STATE’ is  
recognized then the state of this attribute will be stored at array location 6.  
Attribute  
Array Position  
Method  
Not Defined  
0
1
2
3
4
5
6
7
1
1
1
1
1
1
1
2
1
1
1
2
2
3
3
2
2
2
2
2
2
2
1
1
1
1
2
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
2
PRIMARY STATUS  
PHYSICAL STATE  
RAW STATE  
ACTIVE STATE  
ARMED STATE  
ENABLED STATE  
UNVERIFIED  
CURRENT DEVICE  
DEVICE  
8
9
TEST STATE  
10  
11  
11  
14  
14  
14  
14  
14  
17  
17  
20  
20  
23  
24  
25  
26  
27  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
PRESENT SENSITIVITY SELECTED=  
PRESENT SENSITIVITY SELECTED =  
AVERAGE VALUE =  
AVERAGE VALUE=  
AVERAGE =  
AVERAGE=  
AVERAGE  
VALUE =  
VALUE=  
PEAK=  
PEAK =  
TROUBLE THRESHOLD  
OUTPUT STATE  
OUTPUT STATUS  
DETECTOR SOUNDER  
ALARM TEMPERATURE SELECTED=  
DETECTOR RELAY  
TOTAL NUMBER OF TROUBLES  
NODE MISSING  
VERSION CONTROL  
NODE INITIALIZATION IN PROGRESS  
SIMPLEX SERVICE MODE  
EARTH GROUND  
AC POWER  
BATTERY LOW/DISCHARGED  
BATTERY CHARGE  
SYSTEM PSEUDO STATUS  
NETWORK CARD STATUS  
CARD TROUBLE STATUS  
MISCELLANEOUS STATUS  
RELAY STATUS  
PRIORITY  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 30 of 58  
Attribute  
Array Position  
Method  
CONTROL STATUS  
CURRENT (AMPS)  
46  
47  
48  
49  
40  
41  
42  
43  
1
2
1
1
1
1
1
1
CARD MISSING/FAILED  
CORRECT CARD  
RS-232 Interface PORT A  
RS-232 Interface PORT B  
2120/RS-232 PORT Broadcast Fail  
CARD MISSING/FAILED  
The table below reports the attribute states recognized for attribute method=1.  
Attribute State  
AUTOMATIC CONTROL  
OUTPUT NORMAL  
SELF TEST NORMAL  
CORRECT DEVICE  
PRIORITY 15  
RANGE NORMAL  
ALARM  
SHORT  
Value  
Attribute State  
ARMED  
Value  
10  
11  
12  
13  
14  
15  
16  
17  
0
1
2
3
4
5
6
7
8
9
ENABLED  
ON-LINE  
ENABLED  
NORMAL  
TROUBLE  
OFF  
ON  
SHORT  
Examples:  
PHYSICAL STATE  
SHORT  
Driver recognizes ‘Physical State’ as attribute 2 and uses method 1 to evaluate the rest of  
the line. Driver recognizes ‘Short’ as attribute state with value 8. Therefore, the driver stores  
the number 8 at location 2 in the Data Array.  
VALUE=77 / 0% OF ALARM / 1.0% SMOKE  
Driver recognizes ‘VALUE=’ as attribute 17 and uses method 2 to evaluate the rest of the  
line. Driver stores three values; 77, 0 and 1.0 in three consecutive locations starting at  
location 17. Note that there is a gap between attribute 17 and the next attribute in the table  
sufficient for storing up to 3 values. Note that a slash separates the three values.  
AVERAGE VALUE=75 / ALARM LEVEL=145  
Driver recognizes ‘AVERAGE VALUE’ as attribute 14 and uses method 3 to evaluate the  
rest of the line. Driver stores two values; 75 and 145 in two consecutive locations starting at  
location 14. Note that an equal sign ‘=’ precedes each numeric value.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 31 of 58  
Appendix A.8.1.  
Extending the List of Show Attributes  
You can extend the list of attributes and attribute states that the driver recognizes by  
modifying the configuration CSV file.  
The following example adds three attributes and 4 attribute states. If a device reports an  
attribute of ‘LIGHT STATE’ as ‘BRIGHT’ then the driver will load array element 32 with  
the value 41.  
Use a digit.  
Keyword  
Attribute Definitions.  
The name will be  
stripped of all  
spaces between the  
last character and  
the comma.  
The three  
methods are  
described  
above.  
When allocating  
offsets, be mindful  
of the offsets  
starts a new  
section of the  
CSV file.  
Protocol must  
be defined on  
every line.  
already used.  
Driver_Table  
sim4100_Attr_Name, sim4100_Attr_Offset, sim4100_Attr_Method, protocol  
BROKEN  
FIXED  
LIGHT STATE  
 
,
30  
31  
32  
,
,
,
1
1
1
,
,
,
sim4100  
sim4100  
sim4100  
,
,
Driver_Table  
sim4100_Attr_State_Name,  
sim4100_Attr_State_value,  
protocol  
sim4100  
sim4100  
DIM  
,
40  
41  
,
,
BRIGHT  
,
Use values that are not allocated to the  
pre-defined list of states.  
Attribute States.  
Appendix A.9. Synchronizing the FieldServer with the Panel  
When using the Xpoint function to store point states, each time the panel does a warm-start  
it sets all point states to normal and then starts evaluating every single one. Thus, after a  
warm start, the FieldServer will receive Xpoint messages from the panel for every point not  
in a normal state. This provides one synchronization method. The limitation of this method is  
that the Simplex panels do not report when a point’s state changes back to normal. Thus to  
maintain the synchronization the upstream device must clear the point to zero once it has  
read its abnormal state, i.e. The upstream device should consider the data reported by the  
Xpoint function as latched data.  
A second method is to connect/reset the FieldServer when there are no points in an  
abnormal state.  
A third method is poll point states using the Clist function as described in Appendix A.20.  
This way the FieldServer states will always be updated. Polling is slow and in a system with  
many points it is possible that it may take several minutes to update status information for all  
points. Thus combining this method with the use of Xpoint Map Descriptors gives the best  
of both worlds. When a point changes to ‘not’ normal, then the FieldServer gets the state  
change from the Xpoint function immediately and at the same time synchronization is  
assured by the continuous polling.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 32 of 58  
A fourth method is provided too. This method allows a range of a data array to be set to  
zero when a user specified point reports a normal state. Refer to Appendix A.17 for more  
information.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 40 of 58  
Array Position  
Attribute  
Value  
10  
Filled In5 Note  
0
Not Defined  
1
1
!
1
PRIMARY STATUS  
PHYSICAL STATE  
RAW STATE  
14 (Normal)  
#
~
2
3
4
ACTIVE STATE  
ARMED STATE  
ENABLED STATE  
UNVERIFIED  
5
6
11 (Enabled)  
0
1
1
1
1
1
7
8
CURRENT DEVICE  
DEVICE  
4 (Correct Device)  
12 (On_Line)  
3 (Self test normal)  
9
10  
11  
14  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
30  
TEST STATE  
PRESENT SENSITIVITY SELECTED  
AVERAGE  
VALUE  
0
1
1
-41  
*
*
PEAK  
0
1
1
-41  
TROUBLE THRESHOLD  
OUTPUT STATE  
6 (Range Normal)  
1
OUTPUT STATUS  
DETECTOR SOUNDER  
ALARM TEMPERATURE SELECTED=  
DETECTOR RELAY  
135  
1
Notes:  
! The value 10 represents the count of the number of attributes that were extracted from  
the response. It is not equal to the number of array locations filled in because some  
attributes (e.g. Value) result in more than one array location being updated.  
~ The un-filled-in locations are not updated by the driver when this response is analysed  
because the attributes corresponding to these locations were not reported in the  
response to the query.  
* Room for up two three numbers for attributes like value, peak but in this case only two  
values are relevant for this device.  
5
Locations marked with a 1 are updated when the driver analyses this response  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 41 of 58  
Appendix A.20. Using Clist to Write-Through and Store point status from  
Unsolicited Messages  
From version 1.05 on the functionality of the ‘clist’ Map Descriptor’s has been enhanced.  
The ‘Clist’ Map Descriptors can  
Read a point’s status  
Write to a point when a Write-Through is activated  
Store the point status when an ‘xpoint’ unsolicited message is received from the panel.  
A Write-Through occurs when a Data Array value that is normally updated by a read (rdbc)  
Map Descriptor is updated by some other driver or by using the Ruinet application.  
In this case the updated value is written through the read Map Descriptor and the Simplex  
4100 driver writes the updated value to the panel. The value is written once only each time  
that the Data Array element is updated except when the value is updated by the response to  
the read or if the point status is updated when an unsolicited message is received from the  
panel.  
Ensure that:  
The point is not a read only point  
The Panel’s access level has been set appropriately.  
When an unsolicited message is received from the panel it would normally be stored using a  
Map Descriptor with the ‘xpoint’ function. (See section 4.5.6) However, if you are polling for the  
status of that point using a ‘Clist’ Map Descriptor and if that Map Descriptor has  
‘Store_Unsolicited’ set to yes then you must omit the ‘xpoint’ Map Descriptor as the ‘Clist’ Map  
Descriptor can be used to store the point status when it is updated with an unsolicited message.  
If you have both Map Descriptor’s defined then the result will be unpredictable.  
A write command can be sent to a Simplex panel in one of two formats:  
1) SET c-p-s ON/OFF (default)  
2) SET c-p-s value  
Use the sim4100_WriteThru parameter in the CSV to change to the 2nd format.  
Even if you are writing to an analog pseudo point using format 1 is suitable because by enabling  
the point you force it to take its intrinsic value. By setting the point off you are setting its value to  
zero.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Appendix B. Troubleshooting Tips  
Page 42 of 58  
Appendix B.1. Address Errors  
If the driver produces BAD_ADDRESS stats then do the following  
Read the notes on processing errors. You can see the last error response and a report  
of the MD's which received the error response in the error array.  
Alternatively, take a log, open the ASCII version of the log and look for error messages.  
Error 2 is the response sent by the panel when it is polled for a point that doesn’t exist.  
Find the Error #2's n the log. Now look at the line which precedes the error. It is the poll.  
Look to see which point in being polled. Now you know the c-p-s of the invalid point, edit  
the configuration and remove the MD which polls for data at that point. When you have  
finished editing the configuration, download the modified file and reset the FS for the  
changes to take effect.  
Appendix B.2. Driver Limitations  
Other than being able to write through a Map Descriptor where the sim4100_func=’clist’ ,  
write throughs are not supported by this driver.  
Port expansion is not supported.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 43 of 58  
Appendix B.3. Resolving Network Addresses above 255  
The Standard format for addressing a simplex point is c-p-s (Card-Point-Subpoint). Each of  
these components in the address supports a maximum value of 255. However, when using  
an NDU (Network Display Unit), addresses may be supplied in a Card-Address format  
where the address value could be substantially larger than 255. In these applications it will  
be necessary to convert the Card-Address format into c-p-s format before configuring the  
points in the FieldServer.  
The formula used to convert between the two formats is as follows:  
Card is the same for both formats.  
Network Address = ((Point-1)*256) + Sub-Point + 1  
This conversion procedure is best illustrated by means of an example:  
Example:  
Card–Address point supplied = 5-2936  
From this we deduce the card number to be 5. The next step is to break the address into  
multiples of 256 in order to determine point and sub-point. Since this is also a hex  
denominated calculation, an easy way to do this is to convert the value to Hex:  
2936 = 0xB78  
Now, break out the last two hex numbers for sub-point portion, and use the rest for point  
address. So we get:  
0xB = 11 = (Point-1)  
0x78 = 120 = Sub-Point + 1  
Solving this equation, we get:  
Point = 12  
Sub-Point = 119  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 44 of 58  
Appendix C. Error Messages  
Error Message  
Troubleshooting Tip  
The card-point-sub is being used to derive an array  
offset. The calculation requires division by the point  
& the sub and one or both of these values are zero.  
Sim4100:#1  
invalid for ack. Read manual.  
<card><point><sub>  
Sim4100:#2 RTS has been asserted for If RTS-CTS handshaking has been used then this  
too long. Extend timer, check cable message is produced if the driver finds that the  
uses RTS/CTS or reconfig 4100 device RTS has been asserted by the slave device for too  
to suppress hardware handshaking  
Sim4100:#3 sim4100_chan_init() Init  
with null chan.  
long. The timeout is hard coded at 2.0s.  
Requires support from FieldServer Technologies.  
The driver has found a value for a sim4100_func  
Sim4100:#4 Unknown sim4100_func in keyword that it does not recognize. Check the CSV  
csv <nnn>  
file and read Appendix A.2 of this manual for a list  
of legal keywords.  
The sim4100_func keyword has been assigned the  
value 'ack' but a card-point-sub has not been  
specified. It would be better to use the ackall  
function instead.  
Sim4100:#5 Use Ackall function.  
Sim4100:#6 ack/ackall/seta/setd must You cannot use the rdbc function with these  
be a write.  
keywords. Use a wrbc instead.  
You cannot use these keywords at the present  
time. If you require one of these functions  
implemented call FieldServer Technologies.  
Sim4100:#7  
implemented  
disable/restart/list  
not  
Sim4100:#8 Func=Clistall/Clist, wrbc  
not allowed  
These keywords must be used with a rdbc instead.  
Sim4100:#9 Write ack was not Please  
report  
this  
error  
to  
FieldServer  
expected.  
Technologies.  
Sim4100:#10 Invalid point status  
<s><v><a>=(Hex)<%x><%x><%x>  
<%c><%c><%c>  
Please report his message to FieldServer  
Technologies noting the values in braces.  
Sim4100:#11. Error. Array too short.  
rqd= %d( max= %d) act= %d.  
MapDesc= <%s> Data Abandoned!  
Subsequent msgs suppressed!  
Sim4100:#12 Error.  
Check the CSV file Data Array lengths.  
Incoming data is being abandoned.  
Check the CSV file; there was no matching Map  
Descriptor for a message.  
Subsequent message supressed!  
Sim4100:#13 FYI. Login Function not Please contact FieldServer Technologies if you  
Implemented. would like this feature implemented.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Error Message  
Page 45 of 58  
Troubleshooting Tip  
A write thru is defined as follows. The FieldServer  
reads data from a device and stores it in a Data  
Array. If a remote device changes the value in that  
Data Array, the FieldServer will write the new value  
to the device that is being read. This driver does  
not permit write thru's except when the data is  
being updated using CLIST. Refer also to Sections  
4.5.4, 4.5.6 and Appendix A.20. In versions of the  
driver up to and including 1.07a a panic is produced  
when this message is printed. The message is  
printed to a maximum of 10 times and then  
suppressed.  
Sim4100:#14 MD=%s Addr=%d  
SIM4100:#15  
abandoned. No Map Desc.  
FYI.  
Incoming Check the CSV file; there was no matching Map  
Descriptor for a message.  
If the server can’t find a matching MD (i.e. the point  
being polled for doesn’t exist) then the driver  
responds with Simplex Error #2.  
SIM4100:#16 FYI. No Map Desc.  
Respond with Error.  
Check the driver manual and Simplex User  
Manuals. There is no driver response to the  
message received.  
SIM4100:#17  
Abandoned. No Data.  
FYI.  
Incoming  
SIM4100:#18  
Abandoned. (%d)  
FYI.  
Incoming Please report his message to FieldServer  
Technologies noting the values in braces.  
No corrective action is required on your part. The  
message is printed for your information only.  
Message ‘a’ is printed when version 9 firmware is  
found in the panel.  
Message ‘b’ is printed when version 10 firmware is  
found in the panel.  
Sim4100:#19a FYI. Sim4100 Firmware  
found (%.2f)  
Message ‘b’ is printed when version 11 firmware is  
found in the panel.  
The firmware version found is not one that the  
driver explicitly supports. This does not mean the  
driver will not work but if a feature of the driver isn’t  
working correctly knowing that the firmware version  
is not supported may help diagnose the problem  
Sim4100:#19d FYI. Panel Firmware more easily.  
Rev %.2f may be incompatible.  
No corrective action is required on your part. If  
however, some you suspect that the driver is not  
operating correctly it is important that you mention  
seeing this message in the Error Buffer when  
reporting the problem.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Error Message  
Page 46 of 58  
Troubleshooting Tip  
The format of the firmware version information  
could not be interpreted correctly. This may mean  
that your panel has a firmware version that is not  
one that the driver explicitly supports. This does not  
mean the driver will not work but if a feature of the  
driver isn’t working correctly knowing that the  
Sim4100:#19e FYI. Panel Firmware firmware version is not supported may help  
may be incompatible.  
diagnose the problem more easily.  
No corrective action is required on your part. If  
however, some you suspect that the driver is not  
operating correctly it is important that you mention  
seeing this message in the Error Buffer when  
reporting the problem.  
Sim4100:#20 FYI. Data abandoned!  
Array too short. MapDesc= <%s>  
Sim4100:#21. Error. Data abandoned!  
Array too short c-p-s= %d-%d-%d  
Check the CSV file Data Array lengths.  
Check the CSV file Data Array lengths.  
Polling is disabled until the port supervision  
message has been received. This message can be  
safely ignored. When the panel sends unsolicited  
messages to the FieldServer this message is  
printed. Polling remains inhibited until the  
unsolicited message stream end.  
When a stream of unsolicited messages is received  
from the Simplex panel then polling is inhibited until  
the stream ends. When the stream ends this  
message is printed. It may be safely ignored.  
Sim4100:#22. FYI. Polling Inhibited.  
Sim4100:#23. FYI. Polling Enabled  
Sim4100:#25. Error. Data abandoned!  
Array too short c-p-s= %d-%d-%d  
Sim4100:#26 FYI. Data abandoned!  
Array too short.(%d) MapDesc=<%s>  
Sim4100:#27. FYI. Sequence Number  
reset requested & done.  
Check the CSV file Data Array lengths.  
Check the CSV file Data Array lengths.  
Sim4100:#28.  
Sim4100_Func=%d in MD=<%s>  
Error.  
Bad  
Check the CSV file and driver manual for valid  
Simplex functions.  
Sim4100:#29. FYI. Length changed to 1 Check the CSV file for the correct Map Descriptor  
in MapDesc= <%s> function type.  
Sim4100:#30. FYI. Length changed to 1 Check the CSV file for the correct Map Descriptor  
in MapDesc= <%s> function type.  
Sim4100:#31. FYI. Length changed to 1 Check the CSV file for the correct Map Descriptor  
in MapDesc= <%s>  
function type.  
Sim4100:#32. FYI. Sequence number  
semi-reset.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Error Message  
Page 47 of 58  
Troubleshooting Tip  
Message sequence numbers incorrect. Check  
Sim4100:#33. Error. Invalid Seq Simplex User Manuals, and driver manuals.  
Number.  
Contact FieldServer Technologies for additional  
support.  
Message sequence number incorrect.  
Check  
Sim4100:#34. Bad Seq. Sequence Simplex User Manuals, and driver manuals.  
number reset.  
Sim4100:#36.  
Contact FieldServer Technologies for additional  
support.  
Bad Check the CSV file for the correct Simplex function  
FYI.  
sim4100_func=%d in MapDesc=<%s>  
type.  
Sim4100:#38. FYI. Bad Check the CSV file for the correct Simplex function  
sim4100_func=%d in MapDesc=<%s>  
type.  
Attribute was found, but State not found in driver  
Sim4100:#39 FYI. Data abandoned!  
State not recognized. Mapdesc=<%s>  
table.  
Contact FieldServer Technologies for  
additional support.  
Sim4100:#40 FYI. Data abandoned!  
Array too short.(%d) Mapdesc=<%s>  
Sim4100:#41 FYI. Data abandoned!  
Array too short.(%d) Mapdesc=<%s>  
Check the CSV file Data Array lengths  
Check the CSV file Data Array lengths  
Sim4100:#43. Err. Can only monitor %d Contact FieldServer Technologies for additional  
point(s) for ClearAll support.  
Sim4100:#44 FYI. ClearAll mapDesc's Map Descriptor function has been changed  
must be passive  
automatically  
Sim4100:#45 FYI. User added SHOW  
attribute=<%s> offset=%d method=%d  
Sim4100:#46 Err. No space. Driver No space is available in internal driver table.  
rejects  
offset=%d method=%d  
SHOW  
attribute=<%s> Contact FieldServer Technologies for additional  
support.  
Sim4100:#47 Err. Duplicate. Driver  
Duplicate found in internal driver table. Contact  
FieldServer Technologies for additional support.  
rejects  
SHOW  
attribute=<%s>  
offset=%d method=%d  
Sim4100:#48 FYI. User added SHOW  
attr state=<%s> value=%d  
Sim4100:#49 Err. No space. Driver No space is available in internal driver table.  
rejects  
value=%d  
SHOW  
attr  
state=<%s> Contact FieldServer Technologies for additional  
support.  
Sim4100:#50 Err. Duplicate. Driver  
Duplicate found in internal driver table. Contact  
FieldServer Technologies for additional support.  
rejects  
SHOW  
attr  
state=<%s>  
value=%d  
sim4100:#51 Err. Length must be  
specified and > 0.  
Check the CSV file for the length fields.  
Check the CSV file for node definitions, Simplex  
SIM4100:#52  
Abandoned. Node offline  
FYI.  
Incoming hardware, and connections.  
appears to be offline.  
A device node  
Contact FieldServer  
Technologies for additional support.  
Sim4100:#53. Md=<%s> Abandoned. Obsolete. Contact FieldServer Technologies for  
Polling was inhibited. support.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Error Message  
Page 48 of 58  
Troubleshooting Tip  
Sequence number checking was disabled. Check  
your password. Contact FieldServer Technologies  
for support.  
Sim4100:#54. Err. SeqNumber check  
disabled.  
Sim4100:#55.  
Error.  
Bad Check the CSV file for the correct Simplex function  
Sim4100_Func=%d in MD=<%s>  
type.  
Sim4100:#56  
Not used.  
The driver ignored Login messages. No corrective  
action is required. This message is printed for your  
information only.  
Sim4100:#57* Err. Cant parse Login  
message. Ignored.  
Sim4100:#58 FYI. You could have used This message is printed for your information only. It  
an Array called <%s> to expose can safely be ignored. For additional information  
diagnostic info.  
read section “Appendix A.7.2 Driver Exposed Stats”  
An internal driver diagnostic has been triggered.  
You must report this error to FieldServer’s  
Technical Support.  
Sim4100:#59 Err. Checkpoint. Report  
this to Tech Support.  
Every Sim4100 Map Descriptor must be connected  
to a node. Ensure that the parameter ‘Node_Name’  
has been specified on the Map Descriptor.  
Sim4100:#60 Err. MapDesc=%s. No  
Node.  
To correct this problem, edit the CSV, make the  
correction, download the corrected CSV file and  
reset the FieldServer.  
If you have a Map Descritor which has the  
sim4100_func parameter set to ‘earths’ or to  
‘values’ then you must set the PLC_Type  
parameter on the node to 4100U. (See section 0  
Client Side Node Descriptors ). It is only  
appropriate to do so if the firmware version of your  
Sim4100:#61 Err. PLC_Type=4100u panel is 10.x or later. You can create a map  
rqd for 'values'/'earths'  
descriptor to read the version information if you are  
not sure. You can also use the menu system on the  
Panel to read the version number.  
To correct this problem, edit the CSV, make the  
correction, download the corrected CSV file and  
reset the FieldServer.  
This message is printed when the input buffer  
overflows. This usually occurs when the panel  
sends lots of messages and they are not being  
processed by the driver fast enough. A panic is  
printed immediate after this message.  
Sim4100:#62 Err. Input Buffer Overflow. The driver will clear the buffer and start capturing  
new bytes as they arrive. Messages may have  
been lost. We advise that you re-synch the panel.  
This error has only been seen once. It occurred  
when a panel was connected to the driver with the  
wrong connection settings.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Appendix D. Pseudo Points  
Page 49 of 58  
It is beyond the scope of the driver manual to describe the full functionality of the Simplex  
Panels. However, we have found it useful to provide the following data to customers. The  
following information is not maintained and updated therefore you should use it for reference  
only and should always consult with the vendor of your Simplex system before implementing  
any project decisions or actions based on the information provided in this section.  
Pseudo points are points that report states or attributes based on how the Simplex system has  
been installed, configured and programmed. They are often programmed to groups, devices,  
zones or other logic groupings. For example, a pseudo point may be programmed to report if  
and only if more than one sensor in a particular area is reporting smoke.  
Every Simplex system has a number of default pseudo points programmed into the firmware  
supplied with the panel. These default points depend only on the firmware revision number and  
are generally unaffected by the configuration programmed for a particular site.  
Although the 4100 card number can range from 0-250 in theory, only the following ranges are  
presently used in the system:  
Card address  
0-119  
128-143  
144-159  
160-175  
Card type  
Physical (Hardware) cards  
Digital Pseudo cards  
Analog Pseudo cards  
List Pseudo cards  
Digital Pseudo’s: There are 250 fixed pseudo's in the 4020 panel and 511 in the 4100 and  
4100U. The numbering sequence is simple, 128 starts the first block of 256 (0 to 255), so the  
first point is 128-0-0, the second is 128-1-0, and so on. The next block starts at 129 and follows  
the same sequence, then 130 and so on up to 143. In the 4100 the first user definable pseudo  
is P-256, in the 4100U it's P-512.  
P0 SYSTEM RESET KEY  
P1 ALARM SILENCE KEY  
UTILITY 128-0-0  
UTILITY 128-1-0  
P2 FRONT PANEL LAMPTEST CONTROL (ANNUNC. 0) UTILITY 128-2-0  
P3 FIRE ALARM DETECT  
UTILITY 128-3-0  
UTILITY 128-4-0  
UTILITY 128-5-0  
UTILITY 128-6-0  
TROUBLE128-7-0  
UTILITY 128-8-0  
TROUBLE128-9-0  
UTILITY 128-10-0  
UTILITY 128-11-0  
UTILITY 128-12-0  
UTILITY 128-13-0  
TROUBLE128-14-0  
TROUBLE128-15-0  
UTILITY 128-16-0  
P4 GLOBAL ACKNOWLEDGE ENABLE  
P5 SET SERVICE PSEUDO VALUES  
P6 ALARM SILENCE  
P7 EXTRA CARD IN THE SYSTEM  
P8 KEYPAD ACTIVE  
P9 SYSTEM OUT OF CQB'S  
P10 CODED INPUT ACTIVE  
P11 UNACKNOWLEDGED FIRE ALARM EXISTS  
P12 UNACKNOWLEDGED SUPERVISORY EXISTS  
P13 UNACKNOWLEDGED TROUBLE EXISTS  
P14 SYSTEM DISABLED - PROGRAMMER DOWNLOAD  
P15 CFIG RAM WRITE PROTECT MISSING (SW1-1)  
P16 SMPL PROGRAM 0 - SYSTEM DEFAULT  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 50 of 58  
P17 SMPL PROGRAM 1 - DEFAULT AUDIO  
P18 SMPL PROGRAM 2 - SYSTEM OPTIONS (CODING)  
P19 SMPL PROGRAM 3 - USER CUSTOM CONTROL  
P20 SMPL PROGRAM 4 - USER CUSTOM CONTROL  
P21 SMPL PROGRAM 5 - USER CUSTOM CONTROL  
P22 SMPL PROGRAM 6 - USER CUSTOM CONTROL  
P23 SMPL PROGRAM 7 - USER CUSTOM CONTROL  
P24 CODING GROUP 0 ACTIVE  
P25 CODING GROUP 1 ACTIVE  
P26 CODING GROUP 2 ACTIVE  
P27 CODING GROUP 3 ACTIVE  
P28 CODING GROUP 4 ACTIVE  
P29 CODING GROUP 5 ACTIVE  
P30 CODING GROUP 6 ACTIVE  
P31 CODING GROUP 7 ACTIVE  
P32 COLD START  
P33 WARM START  
P34 CITY DISCONNECT  
P35 MANUAL EVACUATION SWITCH INPUT  
P36 ELEVATOR BYPASS  
P37 DOORHOLDER BYPASS  
UTILITY 128-17-0  
UTILITY 128-18-0  
UTILITY 128-19-0  
UTILITY 128-20-0  
UTILITY 128-21-0  
UTILITY 128-22-0  
UTILITY 128-23-0  
UTILITY 128-24-0  
UTILITY 128-25-0  
UTILITY 128-26-0  
UTILITY 128-27-0  
UTILITY 128-28-0  
UTILITY 128-29-0  
UTILITY 128-30-0  
UTILITY 128-31-0  
TROUBLE128-32-0  
TROUBLE128-33-0  
TROUBLE128-34-0  
UTILITY 128-35-0  
TROUBLE128-36-0  
TROUBLE128-37-0  
TROUBLE128-38-0  
TROUBLE128-39-0  
UTILITY 128-40-0  
UTILITY 128-41-0  
UTILITY 128-42-0  
UTILITY 128-43-0  
UTILITY 128-44-0  
UTILITY 128-45-0  
UTILITY 128-46-0  
UTILITY 128-47-0  
P38 CONTROL POINT BYPASS  
P39 SYSTEM EXECUTING FROM RAM  
P40 AUTOMATIC DETECTOR RESET  
P41 MASTER FIRE ALARM ACK KEY  
P42 MASTER SUPERVISORY ACK KEY  
P43 MASTER TROUBLE ACK KEY  
P44 CODING BUS DISABLE SWITCH  
P45 DRILL SWITCH INPUT  
P46 DOOR HOLDER TRIGGER  
P47 SIGNALS/VISUALS ACTIVE  
P48 MANUAL EVACUATION  
FIRE  
128-48-0  
P49 SYSTEM AT ACCESS LEVEL 1 OR GREATER  
P50 SYSTEM AT ACCESS LEVEL 2 OR GREATER  
P51 SYSTEM AT ACCESS LEVEL 3 OR GREATER  
P52 SYSTEM AT ACCESS LEVEL 4  
UTILITY 128-49-0  
UTILITY 128-50-0  
UTILITY 128-51-0  
UTILITY 128-52-0  
P53 SYSTEM LIST OVERFLOW - WARM START NEEDED TROUBLE128-53-0  
P54 NETWORK MIKE KEYED  
UTILITY 128-54-0  
UTILITY 128-55-0  
UTILITY 128-56-0  
UTILITY 128-57-0  
TROUBLE128-58-0  
TROUBLE128-59-0  
UTILITY 128-60-0  
UTILITY 128-61-0  
UTILITY 128-62-0  
UTILITY 128-63-0  
P55 CRT KEYPAD INACTIVITY TIMER DISABLE  
P56 CITY CIRCUIT STD TROUBLE RELAY OPERATION  
P57 KEYPAD INACTIVITY TIMER DISABLE  
P58 SYSTEM TIME/DATE INVALID OR NOT SET  
P59 ALARM VERIFICATION TALLY LIMIT EXCEEDED  
P60 ALARM VERIFICATION GROUP 0 ACTIVE  
P61 ALARM VERIFICATION GROUP 1 ACTIVE  
P62 ALARM VERIFICATION GROUP 2 ACTIVE  
P63 ALARM VERIFICATION GROUP 3 ACTIVE  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 51 of 58  
P64 ALARM VERIFICATION GROUP 4 ACTIVE  
P65 ALARM VERIFICATION GROUP 5 ACTIVE  
P66 ALARM VERIFICATION GROUP 6 ACTIVE  
P67 ALARM VERIFICATION GROUP 7 ACTIVE  
P68 FIRST STAGE TIMER EXPIRED  
P69 THE EVAC MESSAGE HAS PLAYED  
P70 WALK TEST GROUP 0 ENABLED  
P71 WALK TEST GROUP 1 ENABLED  
P72 WALK TEST GROUP 2 ENABLED  
P73 WALK TEST GROUP 3 ENABLED  
P74 WALK TEST GROUP 4 ENABLED  
P75 WALK TEST GROUP 5 ENABLED  
P76 WALK TEST GROUP 6 ENABLED  
P77 WALK TEST GROUP 7 ENABLED  
P78 ALARM SILENCE/ALARM CUTOUT PSEUDO  
P79 RESET SPKRS WHEN AUDIO CODING COMPLETE  
P80 MASTER MICROPHONE KEYED  
P81 REMOTE MICROPHONE 1 KEYED  
P82 REMOTE MICROPHONE 2 KEYED  
P83 REMOTE MICROPHONE 1 READY TO TALK  
P84 REMOTE MICROPHONE 2 READY TO TALK  
P85 VTG 1 - ACTIVE  
UTILITY 128-64-0  
UTILITY 128-65-0  
UTILITY 128-66-0  
UTILITY 128-67-0  
UTILITY 128-68-0  
UTILITY 128-69-0  
TROUBLE128-70-0  
TROUBLE128-71-0  
TROUBLE128-72-0  
TROUBLE128-73-0  
TROUBLE128-74-0  
TROUBLE128-75-0  
TROUBLE128-76-0  
TROUBLE128-77-0  
UTILITY 128-78-0  
UTILITY 128-79-0  
UTILITY 128-80-0  
UTILITY 128-81-0  
UTILITY 128-82-0  
UTILITY 128-83-0  
UTILITY 128-84-0  
UTILITY 128-85-0  
UTILITY 128-86-0  
UTILITY 128-87-0  
UTILITY 128-88-0  
UTILITY 128-89-0  
UTILITY 128-90-0  
UTILITY 128-91-0  
UTILITY 128-92-0  
UTILITY 128-93-0  
UTILITY 128-94-0  
UTILITY 128-95-0  
UTILITY 128-96-0  
UTILITY 128-97-0  
UTILITY 128-98-0  
UTILITY 128-99-0  
UTILITY 128-100-0  
UTILITY 128-101-0  
UTILITY 128-102-0  
UTILITY 128-103-0  
UTILITY 128-104-0  
UTILITY 128-105-0  
UTILITY 128-106-0  
UTILITY 128-107-0  
UTILITY 128-108-0  
UTILITY 128-109-0  
TROUBLE128-110-0  
P86 VTG 2 - ACTIVE  
P87 EVACUATION MESSAGE ON  
P88 EVACUATION MESSAGE OFF  
P89 EVACUATION MESSAGE LED  
P90 ALERT MESSAGE ON  
P91 ALERT MESSAGE OFF  
P92 ALERT MESSAGE LED  
P93 DRILL MESSAGE ON  
P94 DRILL MESSAGE OFF  
P95 DRILL MESSAGE LED  
P96 ALL CLEAR MESSAGE ON  
P97 ALL CLEAR MESSAGE OFF  
P98 ALL CLEAR MESSAGE LED  
P99 AUX MSG 1 ON  
P100AUX MSG 1 OFF  
P101AUX MSG 1 LED  
P102AUX MSG 2 ON  
P103AUX MSG 2 OFF  
P104AUX MSG 2 LED  
P105PHONE PAGING ON  
P106PHONE PAGING OFF  
P107PHONE PAGING LED  
P108AUDIO OVERRIDE ON  
P109AUDIO OVERRIDE OFF  
P110AUDIO OVERRIDE TROUBLE  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 52 of 58  
P111ALL SPEAKERS MINUS ON  
UTILITY 128-111-0  
P112ALL SPEAKERS MINUS OFF  
P113ALL SPEAKERS MINUS LED  
UTILITY 128-112-0  
UTILITY 128-113-0  
UTILITY 128-114-0  
UTILITY 128-115-0  
UTILITY 128-116-0  
UTILITY 128-117-0  
UTILITY 128-118-0  
UTILITY 128-119-0  
UTILITY 128-120-0  
UTILITY 128-121-0  
UTILITY 128-122-0  
UTILITY 128-123-0  
UTILITY 128-124-0  
UTILITY 128-125-0  
UTILITY 128-126-0  
UTILITY 128-127-0  
UTILITY 128-128-0  
UTILITY 128-129-0  
UTILITY 128-130-0  
UTILITY 128-131-0  
TROUBLE128-132-0  
UTILITY 128-133-0  
TROUBLE128-134-0  
UTILITY 128-135-0  
UTILITY 128-136-0  
UTILITY 128-137-0  
UTILITY 128-138-0  
UTILITY 128-139-0  
UTILITY 128-140-0  
UTILITY 128-141-0  
UTILITY 128-142-0  
UTILITY 128-143-0  
UTILITY 128-144-0  
UTILITY 128-145-0  
UTILITY 128-146-0  
P114ALL SPEAKERS CHANNEL 1 ON  
P115ALL SPEAKERS CHANNEL 1 OFF  
P116ALL SPEAKERS CHANNEL 1 LED  
P117ALL SPEAKERS CHANNEL 2 ON  
P118ALL SPEAKERS CHANNEL 2 OFF  
P119ALL SPEAKERS CHANNEL 2 LED  
P120ALL SPEAKERS CHANNEL 3 ON  
P121ALL SPEAKERS CHANNEL 3 OFF  
P122ALL SPEAKERS CHANNEL 3 LED  
P123LOCAL SPEAKER EVAC ON  
P124LOCAL SPEAKER EVAC OFF  
P125LOCAL SPEAKER EVAC LED  
P126LOCAL SPEAKER ALERT ON  
P127LOCAL SPEAKER ALERT OFF  
P128LOCAL SPEAKER ALERT LED  
P129ALL SPEAKERS TALK ON  
P130ALL SPEAKERS TALK OFF  
P131ALL SPEAKERS TALK LED  
P132ANALOG SENSOR ALMOST DIRTY LOG ENABLE  
P133LOG ANALOG SENSOR PEAK VALUE ENABLE  
P134CLEAR ANALOG SENSOR PEAK VALUE  
P135ALL ALERT  
P136ALL EVAC  
P137ALL ALERT LED  
P138MASTER MIKE PRETONE PLAYING ON VTG2  
P139REMOTE MIKE 1 PRETONE PLAYING ON VTG2  
P140REMOTE MIKE 2 PRETONE PLAYING ON VTG2  
P141MANUAL AUDIO EVAC ON  
P142MANUAL AUDIO EVAC OFF  
P143MANUAL AUDIO EVAC LED  
P144DISABLE SUPERVISION ON VTG 1 (2120 APPL)  
P145DISABLE SUPERVISION ON VTG 2 (2120 APPL)  
P146EMPTY AUDIO SERVICE QUEUE  
P147EVAC MSG PLAYING WHEN MICROPHONE KEYED UTILITY 128-147-0  
P148SYSTEM OUT OF AQB'S  
P149SPEAKER SWITCH OFF AUTO  
TROUBLE128-148-0  
TROUBLE128-149-0  
UTILITY 128-150-0  
UTILITY 128-151-0  
UTILITY 128-152-0  
UTILITY 128-153-0  
UTILITY 128-154-0  
UTILITY 128-155-0  
UTILITY 128-156-0  
UTILITY 128-157-0  
P150AUDIO CODING GROUP 1 ACTIVE  
P151AUDIO CODING GROUP 2 ACTIVE  
P152VTG 1 - AUDIO SUPERVISION ACTIVE  
P153VTG 2 - AUDIO SUPERVISION ACTIVE  
P154PHONE TALK LINE RELAY FEEDBACK  
P155PHONE NETWORK RELAY FEEDBACK  
P156LOCAL MASTER PHONE HANDSET OFF HOOK  
P157PHONE TALK LINE RELAY CONTROL INPUT  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 53 of 58  
P158PHONE NETWORK RELAY CONTROL INPUT  
P159PHONE TALK LINE RELAY CONTROL  
UTILITY 128-158-0  
UTILITY 128-159-0  
UTILITY 128-160-0  
TROUBLE128-161-0  
UTILITY 128-162-0  
UTILITY 128-163-0  
UTILITY 128-164-0  
UTILITY 128-165-0  
P160PHONE NETWORK RELAY CONTROL  
P161MASTER PHONE OFFHOOK SUPERVISION  
P162MASTER MIKE PRETONE PLAYING ON VTG1  
P163REMOTE MIKE 1 PRETONE PLAYING ON VTG1  
P164REMOTE MIKE 2 PRETONE PLAYING ON VTG1  
P165AMPS SWITCHED TO BATTERY  
P166ENABLE RM PHONE TO RM PHONE CONVERSATIONUTILITY 128-166-0  
P167ALERT MSG PLAYING WHEN MICROPHONE KEYED UTILITY 128-167-0  
P168MICROPHONE TO EVAC IN EFFECT  
P169MICROPHONE TO ALERT IN EFFECT  
P170MICROPHONE TO TALK (CHANNEL 3) IN EFFECT  
P171BACKGROUND MUSIC RELAY CHANNEL 1  
P172BACKGROUND MUSIC RELAY CHANNEL 2  
P173BACKGROUND MUSIC RELAY CHANNEL 3  
P174VTG 1 CODE'S PRECODE PLAYING  
P175VTG 1 CODE'S AFTER CODE PLAYING  
P176AFTER CODE START - VTG 1  
P177VTG 1 'QUIET' MESSAGE PLAYING  
P178VTG 2 CODE'S PRECODE PLAYING  
P179VTG 2 CODE'S AFTER CODE PLAYING  
P180AFTER CODE START - VTG 2  
P181VTG 2 'QUIET' MESSAGE PLAYING  
P182(2120 APPL) VTG1 CODE START  
P183(2120 APPL) STOP VTG1 QUEUE  
P184(2120 APPL) VTG2 CODE START  
P185(2120 APPL) STOP VTG2 QUEUE  
P186MIKE DISABLE  
P187VTG & AMPLIFIER TROUBLE DISABLE  
P188VTG SUPERVISION TONE NOT ACTIVE  
P189SATELLITE PHONE TIMEOUT DISABLE  
P190NETWORK MIKE PRETONE PLAYING  
P191MASTER MIKE KEYED  
P192REMOTE MIKE 1 KEYED  
P193REMOTE MIKE 2 KEYED  
P194MIKES ARE READY TO PAGE  
P195S21 SWITCH ACTIVATED  
P196RAM BATTERY MISSING/FAILED  
P1972120 1 COMM LOSS  
UTILITY 128-168-0  
UTILITY 128-169-0  
UTILITY 128-170-0  
UTILITY 128-171-0  
UTILITY 128-172-0  
UTILITY 128-173-0  
UTILITY 128-174-0  
UTILITY 128-175-0  
UTILITY 128-176-0  
UTILITY 128-177-0  
UTILITY 128-178-0  
UTILITY 128-179-0  
UTILITY 128-180-0  
UTILITY 128-181-0  
UTILITY 128-182-0  
UTILITY 128-183-0  
UTILITY 128-184-0  
UTILITY 128-185-0  
UTILITY 128-186-0  
UTILITY 128-187-0  
TROUBLE128-188-0  
UTILITY 128-189-0  
UTILITY 128-190-0  
UTILITY 128-191-0  
UTILITY 128-192-0  
UTILITY 128-193-0  
UTILITY 128-194-0  
UTILITY 128-195-0  
TROUBLE128-196-0  
UTILITY 128-197-0  
UTILITY 128-198-0  
UTILITY 128-199-0  
UTILITY 128-200-0  
UTILITY 128-201-0  
UTILITY 128-202-0  
UTILITY 128-203-0  
UTILITY 128-204-0  
P198INHIBIT SONALERT  
P199INHIBIT ALARM DEFAULT  
P200FORCE COLD START  
P201AC VOLTAGE FAILURE/BROWNOUT  
P202DETECTOR RESET  
P203LCD ANNUNCIATORS OVERRIDE KEYSWITCH  
P204SIGNALS SILENCED  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 54 of 58  
P205TRUEALARM SENSITIVITY MODIFIED  
P206PRINT QUEUE OVERFLOW  
P207NETWORK DIAGNOSTIC MODE  
P208OUT OF NQB'S  
P209COMMUNICATIONS SHORT CIRCUIT TROUBLE  
P210NETWORK DETECTOR RESET  
P211NETWORK SYSTEM RESET  
P212DETECTOR/SYSTEM RESET  
P2134120 NETWORK CARD CONFIGURED  
P214CLEAR VERIFICATION TALLIES  
P215PRIORITY 2 ALARM DETECT  
P216PRIORITY 2 ALARM RESET REQUEST  
P217NETWORK SIGNAL SILENCE  
P218UNACKNOWLEDGED PRIORITY 2 ALARM EXISTS  
P219MASTER PRIORITY 2 ALARM ACK KEY  
P220NETWORK PRIORITY 2 RESET  
P221SIGNALS ACTIVE - OFF ON SILENCE  
P222REMOTE DOWNLOAD ENABLED  
P223MASTER MICROPHONE READY TO TALK  
P224NETWORK INITIALIZATION INCOMPLETE  
P225NETWORK OPERATING IN DEGRADED STYLE-7  
P226NETWORK INITIALIZATION IN PROGRESS  
P227SDACT DATABASE VERSION MISMATCH  
P228PREVENT TIME/DATE LOGGING  
P229TRUEALERT SILENT TEST ACTIVE  
P230TRUEALERT DEVICE TEST MODE ACTIVE  
P231EXTRA NODE ON NETWORK  
TROUBLE128-205-0  
TROUBLE128-206-0  
TROUBLE128-207-0  
TROUBLE128-208-0  
TROUBLE128-209-0  
UTILITY 128-210-0  
UTILITY 128-211-0  
UTILITY 128-212-0  
UTILITY 128-213-0  
TROUBLE128-214-0  
UTILITY 128-215-0  
UTILITY 128-216-0  
UTILITY 128-217-0  
UTILITY 128-218-0  
UTILITY 128-219-0  
UTILITY 128-220-0  
UTILITY 128-221-0  
TROUBLE128-222-0  
UTILITY 128-223-0  
TROUBLE128-224-0  
TROUBLE128-225-0  
TROUBLE128-226-0  
TROUBLE128-227-0  
UTILITY 128-228-0  
TROUBLE128-229-0  
TROUBLE128-230-0  
TROUBLE128-231-0  
TROUBLE128-232-0  
UTILITY 128-250-0  
P232NETWORK POINT LABEL UPDATING INHIBITED  
P250ENABLE END PAIR AND MONITOR LOGGING  
Analog Pseudo's do not have alarm states, they have physical values such as the day, date,  
time, number of fire events, number of troubles and so on.  
A0  
A1  
A2  
A3  
A4  
A5  
A6  
A7  
A8  
A9  
A10  
A11  
A12  
A13  
NUMBER OF SYSTEM FIRE ALARMS  
NUMBER OF SYSTEM SUPERVISORIES  
NUMBER OF SYSTEM TROUBLES  
NUMBER OF OLD (UNCLEARED) FIRE ALARMS  
NUMBER OF OLD (UNCLEARED) SUPERVISORIES  
NUMBER OF OLD (UNCLEARED) TROUBLES  
CURRENT HOUR  
CURRENT MINUTE  
CURRENT SECOND  
CURRENT DAY  
CURRENT MONTH  
ANALOG 144-0-0  
ANALOG 144-1-0  
ANALOG 144-2-0  
ANALOG 144-3-0  
ANALOG 144-4-0  
ANALOG 144-5-0  
ANALOG 144-6-0  
ANALOG 144-7-0  
ANALOG 144-8-0  
ANALOG 144-9-0  
ANALOG 144-10-0  
ANALOG 144-11-0  
ANALOG 144-12-0  
CURRENT YEAR  
CURRENT ACCESS LEVEL  
ACCESS LEVEL TIMEOUT  
TIMER  
144-13-0  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 55 of 58  
A14  
A15  
A16  
A17  
A18  
A19  
A20  
A21  
A22  
A23  
A24  
A25  
A26  
A27  
A28  
A29  
A30  
A31  
A32  
A33  
A34  
A35  
A36  
A37  
A38  
A39  
A40  
A41  
A42  
A43  
A44  
A45  
A46  
A47  
A48  
A49  
A50  
A51  
A52  
A53  
A54  
A55  
A56  
A57  
A58  
A59  
A60  
SYSTEM RESET WINDOW TIMER  
SYSTEM RESET WINDOW TIMER SETPOINT  
DETECTOR RESET PULSE TIMER  
4-WIRE RESET RELAY PULSE TIMER  
FIRE ALARM CLEAR DELAY TIMER  
FIRE ALARM CLEAR DELAY TIMER SETPOINT  
FIRE ALARM CLEAR PULSE TIMER  
SYSTEM RESET PULSE TIMER  
ALARM SILENCE INHIBIT TIMER  
ALARM SILENCE INHIBIT TIMER SETPOINT  
FIRE ALARM CUTOUT TIMER  
FIRE ALARM CUTOUT TIMER SETPOINT  
FIRE ALARM CUTOUT SILENCE PULSE TIMER  
TROUBLE REMINDER CYCLE TIMER  
TROUBLE REMINDER OFF-TIME SETPOINT  
TROUBLE REMINDER ON-TIME SETPOINT  
DOOR HOLDER ALARM DROP TIMER  
DOOR HOLDER ALARM DROP TIMER SETPOINT  
DOOR HOLDER BROWNOUT DROP TIMER  
TIMER  
ANALOG 144-15-0  
TIMER  
TIMER  
TIMER  
144-14-0  
144-16-0  
144-17-0  
144-18-0  
ANALOG 144-19-0  
TIMER  
TIMER  
TIMER  
ANALOG 144-23-0  
TIMER 144-24-0  
ANALOG 144-25-0  
TIMER  
TIMER  
ANALOG 144-28-0  
ANALOG 144-29-0  
144-20-0  
144-21-0  
144-22-0  
144-26-0  
144-27-0  
TIMER  
ANALOG 144-31-0  
TIMER 144-32-0  
144-30-0  
DOOR HOLDER BROWNOUT DROP TIMER SETPOINT ANALOG 144-33-0  
SYSTEM STARTUP PULSE TIMER  
FIRE ALARM AUDIBLE SIGNAL OPERATION  
FIRE ALARM VISUAL SIGNAL OPERATION  
ALARM VERIFICATION - RETARD TIME  
ALARM VERIFICATION - RESET TIME  
ALARM VERIFICATION - CONFIRMATION TIME  
ALARM VERIFICATION - TALLY LIMIT  
WALK TEST ABORT TIMEOUT SETPOINT  
WALK TEST REACTIVATE DELAY SETPOINT  
MONITOR ZONE ENABLE DELAY SETPOINT  
CODED INPUT TIMEOUT SETPOINT  
OFF TIME AFTER PNIS (NON-CONT.) CODES  
CITY CIRCUIT CONFIGURATION  
ALERT TONE/MSG AFTER MICROPHONE UNKEYED  
TOTAL AUDIO CHANNELS  
CHANNEL 1 ROUTING  
CHANNEL 2 ROUTING  
CHANNEL 3 ROUTING  
LOCAL ROUTING  
EVAC TONE/MSG AFTER MICROPHONE UNKEYED  
SUPERVISION MSG#  
EVACUATION MSG#  
ALERT MSG#  
DRILL MSG#  
TIMER  
144-34-0  
ANALOG 144-35-0  
ANALOG 144-36-0  
ANALOG 144-37-0  
ANALOG 144-38-0  
ANALOG 144-39-0  
ANALOG 144-40-0  
ANALOG 144-41-0  
ANALOG 144-42-0  
ANALOG 144-43-0  
ANALOG 144-44-0  
ANALOG 144-45-0  
ANALOG 144-46-0  
ANALOG 144-47-0  
ANALOG 144-48-0  
ANALOG 144-49-0  
ANALOG 144-50-0  
ANALOG 144-51-0  
ANALOG 144-52-0  
ANALOG 144-53-0  
ANALOG 144-54-0  
ANALOG 144-55-0  
ANALOG 144-56-0  
ANALOG 144-57-0  
ANALOG 144-58-0  
ANALOG 144-59-0  
ANALOG 144-60-0  
ALL CLEAR MSG#  
AUX 1 MSG#  
AUX 2 MSG#  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 56 of 58  
A61  
A62  
A63  
A64  
A65  
A66  
A67  
A68  
A69  
A70  
A71  
A72  
A73  
A74  
A75  
A76  
A77  
A78  
A79  
A80  
A81  
A82  
A83  
A84  
A85  
A86  
A87  
A88  
A89  
A90  
A91  
A92  
A93  
A94  
A95  
A96  
A97  
A98  
A99  
A100  
A101  
A102  
A103  
A104  
A105  
A106  
A107  
MICROPHONE PRETONE MSG#  
PHONE OFFHOOK TIMER  
PHONE CALLBACK TIMER  
ANALOG 144-61-0  
TIMER  
TIMER  
TIMER  
TIMER  
144-62-0  
144-63-0  
144-64-0  
144-65-0  
PHONE TIMEOUT TIMER  
REMOTE MASTER PHONE TIMEOUT TIMER  
SPEAKER SWITCH OFF AUTO COUNT  
AUDIO RESET PULSE TIMER  
VTG 1 PRIORITY  
VTG 2 PRIORITY  
ANALOG 144-66-0  
TIMER 144-67-0  
ANALOG 144-68-0  
ANALOG 144-69-0  
ANALOG 144-70-0  
ANALOG 144-71-0  
ANALOG 144-72-0  
ANALOG 144-73-0  
CHANNEL 1 ROUTING PRIORITY  
CHANNEL 2 ROUTING PRIORITY  
CHANNEL 3 ROUTING PRIORITY  
LOCAL SPEAKER ROUTING PRIORITY  
AUDIO SUPERVISION PULSE TIMER VTG1  
AUDIO SUPERVISION PULSE TIMER VTG2  
ENABLE/DISABLE STATISTIC GROUP  
ENABLE/DISABLE STATISTIC OUTPUT PORT  
5 SEC TIMER FOR REMOTE MASTER PHONES  
CLEAR PEAK PULSE  
PRECODE MESSAGE NUMBER - VTG 1  
AFTER CODE MESSAGE NUMBER - VTG 1  
PRECODE MESSAGE NUMBER - VTG 2  
AFTER CODE MESSAGE NUMBER - VTG 2  
' QUIET' MESSAGE NUMBER  
TIMER  
TIMER  
144-74-0  
144-75-0  
ANALOG 144-76-0  
ANALOG 144-77-0  
TIMER  
144-78-0  
ANALOG 144-79-0  
ANALOG 144-80-0  
ANALOG 144-81-0  
ANALOG 144-82-0  
ANALOG 144-83-0  
ANALOG 144-84-0  
2 SECOND TIMER - VTG 1  
2 SECOND TIMER - VTG 2  
MIKE INHIBIT TIMER  
TIMER  
TIMER  
TIMER  
144-85-0  
144-86-0  
144-87-0  
MIKE INHIBIT TIMER SETPOINT  
PHONE CALLBACK TIMER SETPOINT  
PHONE TIMEOUT TIMER SETPOINT  
VTG & AMPLIFIER TROUBLE DISABLE TIMER  
SUPERVISION NOT ACTIVE - TBL DELAY TIMER  
4 WIRE DETECTOR RESET EXTEND TIMER  
ACTIVE MESSAGE NUMBER - VTG 1  
ACTIVE MESSAGE NUMBER - VTG 2  
ACTUAL CHIPSET PLUGGED INTO VTG 1  
ACTUAL CHIPSET PLUGGED INTO VTG 2  
BATTERY TROUBLE COUNTER  
AC POWER FAIL COUNTER  
ANALOG 144-88-0  
ANALOG 144-89-0  
ANALOG 144-90-0  
TIMER  
TIMER  
TIMER  
144-91-0  
144-92-0  
144-93-0  
ANALOG 144-94-0  
ANALOG 144-95-0  
ANALOG 144-96-0  
ANALOG 144-97-0  
COUNTER 144-98-0  
COUNTER 144-99-0  
ANALOG 144-100-0  
ANALOG 144-101-0  
ANALOG 144-102-0  
ANALOG 144-103-0  
ANALOG 144-104-0  
ANALOG 144-105-0  
ANALOG 144-106-0  
ANALOG 144-107-0  
SYSTEM TYPE  
FIRST STAGE TIMER  
FIRST STAGE TIMER SETPOINT  
MASTER MIKE 5 SECOND UNKEY DELAY  
REMOTE MIKE 1 5 SECOND UNKEY DELAY  
REMOTE MIKE 2 5 SECOND UNKEY DELAY  
MASTER MIKE'S PRETONE TIMER  
MASTER MIKE'S PRETONE SETPOINT  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 57 of 58  
A108  
A109  
A110  
A111  
A112  
A113  
A114  
A115  
A116  
A117  
A118  
A119  
A120  
A121  
A122  
A123  
A124  
A125  
A126  
A127  
A128  
A129  
A130  
A131  
A132  
A133  
REMOTE MIKE 1'S PRETONE TIMER  
REMOTE MIKE 1'S PRETONE SETPOINT  
REMOTE MIKE 2'S PRETONE TIMER  
REMOTE MIKE 2'S PRETONE SETPOINT  
GROUND TROUBLE COUNTER  
ANALOG 144-108-0  
ANALOG 144-109-0  
ANALOG 144-110-0  
ANALOG 144-111-0  
COUNTER 144-112-0  
ANALOG 144-113-0  
COUNTER 144-114-0  
ANALOG 144-115-0  
COUNTER 144-116-0  
COUNTER 144-117-0  
PAGING CHANNEL  
TRUEALARM MODIFICATION COUNTER  
EXCESSIVELY DIRTY (OUT OF RANGE)  
DIRTY SENSOR COUNTER  
ALMOST DIRTY COUNTER  
ALARMS SILENCED DELAY TIMER  
NUMBER OF LOCAL SYSTEM POINTS' TROUBLES  
SYSTEM PAGING STATUS  
KEYPAD INACTIVITY TIMEOUT SETPOINT  
NUMBER OF SYSTEM PRIORITY 2 ALARMS  
NUMBER OF OLD (UNCLEARED) PRI2 ALARMS  
PRI2 RESET WINDOW TIMER  
PRI2 RESET WINDOW TIMER SETPOINT  
PRI2 ALARM CLEAR DELAY TIMER  
PRI2 ALARM CLEAR DELAY TIMER SETPOINT  
PRI2 ALARM CLEAR PULSE TIMER  
PRIORITY 2 RESET PULSE TIMER  
PRIORITY 2 RESET START TIMER  
SUPERVISION DELAY SETPOINT CHL1  
SUPERVISION DELAY SETPOINT CHL2  
SUPERVISION NOT ACTIVE DELAY SETPOINT  
TIMER  
144-118-0  
COUNTER 144-119-0  
ANALOG 144-120-0  
ANALOG 144-121-0  
ANALOG 144-122-0  
ANALOG 144-123-0  
TIMER  
ANALOG 144-125-0  
TIMER 144-126-0  
ANALOG 144-127-0  
144-124-0  
TIMER  
TIMER  
TIMER  
144-128-0  
144-129-0  
144-130-0  
ANALOG 144-131-0  
ANALOG 144-132-0  
ANALOG 144-133-0  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-41 Simplex 4100 Driver Manual  
Page 58 of 58  
THIS PAGE INTENTIONALLY LEFT BLANK  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: [email protected]  

Mr Coffee PR14 User Manual
Motorola MOTORIZR Z3 User Manual
Memorex MSP CR1100 User Manual
Maxtor 96147H6 User Manual
LG Electronics Chocolate BL20 User Manual
Kenwood KDC MP5029VG User Manual
COBY electronic CX 90 User Manual
Centon electronic DataStick Bolt 16GBDSB BLUE User Manual
Cambridge Audio AZUR 350C User Manual
Bunn CDBCF TWIN APS User Manual