		 A Sierra Monitor Company   
					Driver Manual   
					(Supplement to the FieldServer Instruction Manual)   
					FS-8700-01 Modbus RTU   
					& 
					FS-8700-08 Modbus ASCII   
					There are several similarities between these two drivers and   
					we have incorporated them into the same manual to ensure   
					that our information stays current. Although both drivers   
					are referenced in this manual, they are different drivers and   
					need to be ordered separately."   
					APPLICABILITY & EFFECTIVITY   
					Effective for all systems manufactured after May 1, 2001   
					Instruction Manual Part Number: T28700-01   
					Rev. A.   
					Applicability and Effectivity   
				FS-8700-01_Modbus_RTU_(T28700-01) Driver Manual   
					Page 3 of 21   
					1.   
					Modbus RTU/ Modbus ASCII Description   
					The Modbus RTU and Modbus ASCII drivers allow the FieldServer to transfer data to and from   
					devices over either RS-232 or RS-485 using Modbus RTU or Modbus ASCII protocol   
					respectively. The driver was developed for Modbus Application Protocol Specification V1.1a"   
					
					emulate either a Server or Client.   
					The information that follows describes how to expand upon the factory defaults provided in the   
					configuration files included with the FieldServer.   
					There are various register mapping models being followed by various vendors   
					To cover all these models FieldServer uses the following three Models   
					• 
					Modicon_5digit – Use this format where addresses are defined in 0xxxx, 1xxxx, 3xxxx or   
					4xxxx format. A maximum of 9999 registers can be mapped of each type. This is   
					FieldServer driver’s default format.   
					• 
					• 
					ADU –Application Data Unit address. Use this format where addresses of each type are   
					defined in the range 1-65536   
					PDU –Protocol Data unit address. Use this format where addresses of each type are   
					defined in the range 0-65535.   
					The key difference between ADU and PDU is for example if Address_Type is ADU and address   
					is 1, the driver will poll for register 0. If Address_Type is PDU, the driver will poll for address 1.   
					Note 1: If vendor document shows addresses in extended Modicon (i.e. 6 digit) format like   
					4xxxxx then consider these addresses as xxxxx (omit the first digit) and use either ADU or PDU   
					Note 2: The purpose of providing 3 different ways of addressing the Modbus registers is to allow   
					the user to choose the addressing system most compatible with the address list being used. At   
					the protocol level, the same protocol specification is used for all three with the exception of the   
					limited address range for Modicon_5digit.   
					
					
				FS-8700-01_Modbus_RTU_(T28700-01) Driver Manual   
					Page 4 of 21   
					2.   
					Driver Scope of Supply   
					2.1. Supplied by FieldServer Technologies for this driver   
					FIELDSERVER TECHNOLOGIES PART #   
					FS-8915-10   
					FS-8917-02   
					FS-8917-01   
					FS-8917-21   
					DESCRIPTION   
					UTP cable (7 foot) for RS-232 use   
					RJ45 to DB9F connector adapter   
					RJ45 to DB25M connection adapter   
					RS-485 connection adapter   
					Driver Manual   
					FS-8700-01 (T28700-01)   
					2.2.   
					Provided by Supplier of 3rd Party Equipment   
					PART #   
					DESCRIPTION   
					Modbus RTU or Modbus ASCII device   
					
					
				FS-8700-01_Modbus_RTU_(T28700-01) Driver Manual   
					Page 5 of 21   
					3.   
					Hardware Connections   
					It is possible to connect a Modbus RTU or Modbus ASCII device to any of the existing serial   
					ports on the FieldServer1. These ports simply need to be configured for the appropriate driver in   
					the configuration file.   
					Configure the Modbus RTU or Modbus ASCII device according to manufacturer’s instructions.   
					1 
					Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction   
					manual for details of the ports available on specific hardware.   
					
					
				FS-8700-01_Modbus_RTU_(T28700-01) Driver Manual   
					Page 6 of 21   
					4.   
					Configuring the FieldServer as a Modbus RTU or Modbus ASCII Client.   
					For a detailed discussion on FieldServer configuration, please refer to the FieldServer   
					Configuration Manual. The information that follows describes how to expand upon the factory   
					defaults provided in the configuration files included with the FieldServer (See “.csv” sample files   
					provided with the FieldServer).   
					This section documents and describes the parameters necessary for configuring the FieldServer   
					to communicate with a Modbus RTU or Modbus ASCII Server.   
					4.1.   
					Data Arrays/Descriptors   
					The configuration file tells the FieldServer about its interfaces, and the routing of data   
					required. In order to enable the FieldServer for Modbus RTU or Modbus ASCII   
					communications, the driver independent FieldServer buffers need to be declared in the   
					“Data Arrays” section, the destination device addresses need to be declared in the “Client   
					Side Nodes” section, and the data required from the Servers needs to be mapped in the   
					“Client Side Map Descriptors” section. Details on how to do this can be found below.   
					Note that in the tables, * indicates an optional parameter, with the bold legal value being the   
					default.   
					Section Title   
					Data_Arrays   
					Column Title   
					Function   
					Legal Values   
					Up to 15 alphanumeric   
					characters   
					Data_Array_Name   
					Provide name for Data Array   
					Provide data format. Each FLOAT, BIT, UInt16, SInt16,   
					Data Array can only take on Packed_Bit, Byte,   
					Data_Array_Format   
					Data_Array_Length   
					one format.   
					Packed_Byte, Swapped_Byte   
					Number of Data Objects. Must   
					be larger than the data   
					storage area required by the 1-10,000   
					map descriptors for the data   
					being placed in this array.   
					Example   
					// Data Arrays   
					Data_Arrays   
					Data_Array_Name,   
					DA_AI_01,   
					DA_AO_01,   
					DA_DI_01,   
					Data_Array_Format,   
					Data_Array_Length   
					UInt16,   
					UInt16,   
					Bit,   
					200   
					200   
					200   
					200   
					DA_DO_01,   
					Bit,   
					
					
				FS-8700-01_Modbus_RTU_(T28700-01) Driver Manual   
					Page 7 of 21   
					4.2.   
					Client Side Connection Descriptors   
					Section Title   
					Connections   
					Column Title Function   
					Legal Values   
					Specify which port the device is   
					connected to the FieldServer   
					Port   
					P1-P8, R1-R22   
					110 – 115200, standard baud   
					rates only. 9600   
					Baud*   
					Specify baud rate   
					Parity*   
					Specify parity   
					Even, Odd, None   
					Data_Bits*   
					Specify data bits   
					Specify stop bits   
					7, 8   
					Stop_Bits*   
					1 (Vendor limitation)   
					Modbus RTU   
					Modbus _RTU   
					Modbus ASCII   
					MB_ASCII   
					Protocol   
					Specify protocol used   
					Handshaking* Handshaking is not supported   
					None   
					Poll Delay*   
					Time between internal polls   
					0-32000s, 0.05s   
					Example   
					Change protocol to MB_ASCII to use Modbus ASCII protocol   
					// Client Side Connections   
					Connections   
					Port, Baud, Parity, Data_Bits, Stop_Bits, Protocol,   
					Handshaking, Poll_Delay   
					P8,   
					9600, None, 8,   
					1,   
					Modbus _RTU,   
					None,   
					0.100s   
					2 
					Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction   
					manual for details of the ports available on specific hardware.   
					
					
				FS-8700-01_Modbus_RTU_(T28700-01) Driver Manual   
					Page 8 of 21   
					4.3.   
					Section Title   
					Nodes   
					Client Side Node Descriptors   
					Column Title   
					Function   
					Legal Values   
					Up to 32 alphanumeric   
					characters   
					Node_Name   
					Provide name for Node   
					Modbus station address of physical   
					Server Node   
					Node_ID   
					Protocol   
					Port   
					1-255   
					Modbus RTU   
					Modbus_RTU   
					Modbus ASCII   
					MB_ASCII   
					Specify protocol used   
					Specify which port the device is   
					connected to the FieldServer   
					P1-P8, R1-R22   
					Set to Block_Mode if Remote Server   
					Node (RSN) only supports Write   
					Multiple – FC16 & FC15, and does   
					not support FC05 or FC06   
					Node_Type3   
					Block_Mode   
					Address_Type4 Specify Register Mapping Model   
					ADU,PDU, -, Modicon_5digit   
					Example:   
					Change protocol to MB_ASCII to use Modbus ASCII protocol   
					// Client Side Nodes   
					// For devices where 65536 addresses are available in each memory area.   
					Nodes   
					Node_Name,   
					Modbus device 1,   
					Modbus device 2,   
					Node_ID,   
					1,   
					2,   
					Protocol,   
					Modbus_RTU,   
					Modbus_RTU,   
					Port   
					P8   
					P8   
					Address_Type   
					ADU   
					PDU   
					// For devices where only 9999 registers are available in each memory area.   
					Nodes   
					Node_Name,   
					Modbus device 3,   
					Node_ID,   
					3,   
					Protocol,   
					Modbus_RTU,   
					Port   
					P8   
					3 
					If this parameter is not specified the default function codes will be FC 05 (Single_Coil) and FC 06   
					(Single_Register). Refer to Appendix A.3 for more information.   
					4 Optional for Modicon 5 digit devices   
					
					
				FS-8700-01_Modbus_RTU_(T28700-01) Driver Manual   
					Page 9 of 21   
					4.4.   
					4.4.1.   
					Client Side Map Descriptors   
					FieldServer Related Map Descriptor Parameters   
					Column Title   
					Function   
					Legal Values   
					Up to 32 alphanumeric   
					characters   
					Map_Descriptor_Name Name of this Map Descriptor   
					Name of Data Array where data   
					Data_Array_Name   
					One of the Data Array names   
					from “Data Array” section above   
					0 to maximum specified in “Data   
					Array” section above   
					is to be stored in the FieldServer   
					Data_Array_Offset   
					Function   
					Starting location in Data Array   
					Function of Client Map Descriptor RDBC, WRBC, WRBX   
					4.4.2.   
					Driver Related Map Descriptor Parameters   
					Column Title   
					Function   
					Legal Values   
					Name of Node to One of the Node names specified in “Client   
					Node_Name   
					fetch data from   
					Node Descriptor” above   
					Address_Type = ADU   
					Coil,   
					Holding_Register,   
					Discrete_Input,   
					Input_Register,   
					Single_Coil,   
					Single_Register   
					Specify   
					area   
					memory   
					Data_Type5   
					Address_Type = PDU   
					FC01, FC02, FC03, FC04,   
					FC05, FC06, FC15, FC16   
					Address_Type = Modicon_5digit   
					- (Dash), Single_Register, Single_Coil   
					Address_Type = ADU   
					1-65536   
					Starting address of Address_Type = PDU   
					Address   
					read block   
					0-65535   
					Address_Type = Modicon_5digit   
					40001, 30001, etc   
					Length   
					Descriptor   
					of   
					Map 1-125 (For Analog polls),   
					1-800 (For Binary polls).   
					Length   
					Scaling zero in   
					Data Array   
					Any signed 32 bit integer in the range:   
					-2,147,483,648 to 2,147,483,647. 0   
					Data_Array_Low_Scale*   
					Scaling max in Data   
					Array   
					Any signed 32 bit integer in the range:   
					-2,147,483,648 to 2,147,483,647. 100   
					Data_Array_High_Scale*   
					Scaling zero in   
					Connected Node   
					Scaling max in   
					Connected Node   
					Any signed 32 bit integer in the range:   
					-2,147,483,648 to 2,147,483,647. 0   
					Any signed 32 bit integer in the range:   
					-2,147,483,648 to 2,147,483,647. 100   
					Node_Low_Scale*   
					Node_High_Scale*   
					4.4.3.   
					Timing Parameters   
					Column Title   
					Scan_Interval*   
					Function   
					Rate at which data is polled   
					Legal Values   
					0-32000, 1   
					5 Optional only for Modicon_5digit addressing, and only if Single writes do not need to be forced   
					
					
				FS-8700-01_Modbus_RTU_(T28700-01) Driver Manual   
					Page 11 of 21   
					5.   
					Configuring the FieldServer as a Modbus RTU or Modbus ASCII Server   
					For a detailed discussion on FieldServer configuration, please refer to the FieldServer   
					Configuration Manual. The information that follows describes how to expand upon the factory   
					defaults provided in the configuration files included with the FieldServer (See “.csv” sample files   
					provided with the FieldServer).   
					This section documents and describes the parameters necessary for configuring the FieldServer   
					to communicate with a Modbus RTU or Modbus ASCII Client.   
					The configuration file tells the FieldServer about its interfaces, and the routing of data required.   
					In order to enable the FieldServer for Modbus RTU or Modbus ASCII communications, the   
					driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the   
					FieldServer virtual Node(s) needs to be declared in the “Server Side Nodes” section, and the   
					data to be provided to the clients needs to be mapped in the “Server Side Map Descriptors”   
					section. Details on how to do this can be found below.   
					Note that in the tables, * indicates an optional parameter, with the bold legal value being the   
					default.   
					5.1.   
					Server Side Connection Descriptors   
					Section Title   
					Connections   
					Column Title Function   
					Legal Values   
					Specify which port the device is connected   
					to the FieldServer   
					Port   
					P1-P8, R1-R26   
					110 – 115200, standard baud   
					rates only   
					Baud*   
					Specify baud rate   
					Parity*   
					Specify parity   
					Even, Odd, None   
					Data_Bits*   
					Specify data bits   
					Specify stop bits   
					7, 8   
					Stop_Bits*   
					1 (Vendor limitation)   
					Modbus RTU   
					Modbus_RTU   
					Modbus ASCII   
					MB_ASCII   
					Protocol   
					Specify protocol used   
					Handshaking* Handshaking is not supported.   
					None   
					Example   
					Change protocol to MB_ASCII to use Modbus ASCII protocol   
					// Server Side Connections   
					Connections   
					Port,   
					P1,   
					Baud,   
					9600,   
					Parity, Data_Bits, Stop_Bits, Protocol,   
					None, 8, 1, Modbus_RTU, None   
					Handshaking   
					6 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction   
					manual for details of the ports available on specific hardware.   
					
					
				FS-8700-01_Modbus_RTU_(T28700-01) Driver Manual   
					Page 12 of 21   
					5.2.   
					Server Side Node Descriptors   
					Section Title   
					Nodes   
					Column Title   
					Node_Name   
					Node_ID   
					Function   
					Legal Values   
					Up to 32 alphanumeric characters   
					1 – 255   
					Modbus RTU   
					ADU,PDU, -, Modicon_5digit   
					Provide name for Node   
					Node ID of physical Server Node   
					Specify protocol used   
					Protocol   
					Address_Type7 Specify Register Mapping Model   
					Example   
					Change protocol to MB_ASCII to use Modbus ASCII protocol   
					// Server Side Nodes   
					// For devices where 65536 addresses are available in each memory area.   
					Nodes   
					Node_Name,   
					MB_Srv_11,   
					MB_Srv_12,   
					Node_ID,   
					11,   
					12,   
					Protocol   
					Modbus_RTU   
					Modbus_RTU   
					Address_Type   
					ADU   
					PDU   
					// For devices where only 9999 registers are available in each memory area.   
					Nodes   
					MB_Srv_13,   
					MB_Srv_14,   
					13,   
					14,   
					Modbus_RTU   
					Modbus_RTU   
					Modicon_5digit   
					- 
					7 Optional for Modicon 5 digit devices   
					
					
				FS-8700-01_Modbus_RTU_(T28700-01) Driver Manual   
					Page 13 of 21   
					5.3.   
					5.3.1.   
					Server Side Map Descriptors   
					FieldServer Specific Map Descriptor Parameters   
					Column Title   
					Function   
					Legal Values   
					to 32 alphanumeric   
					Up   
					characters   
					Name of Data Array where data One of the Data Array names   
					Map_Descriptor_Name Name of this Map Descriptor   
					Data_Array_Name   
					Data_Array_Offset   
					Function   
					is to be stored in the FieldServer   
					from “Data Array” section above   
					0 to maximum specified in “Data   
					Array” section above   
					Starting location in Data Array   
					Function   
					Descriptor   
					of   
					Server   
					Map   
					Server   
					5.3.2.   
					Driver Specific Map Descriptor Parameters   
					Column Title   
					Node_Name   
					Function   
					Name of Node to fetch   
					data from   
					Legal Values   
					One of the Node names specified in   
					“Client Node Descriptor” above   
					Address_Type = ADU   
					Coil, Discrete_Input, Input_Register,   
					Holding_Register,   
					Single_Coil,   
					Single_Register   
					Data_Type8   
					Specify memory area   
					Address_Type = PDU   
					FC01, FC02, FC03, FC04,   
					FC05, FC06, FC15, FC16   
					Address_Type = Modicon_5digit   
					- (Dash), Single_Register, Single_Coil   
					Length of Map   
					Descriptor   
					Length   
					1-10000.   
					Address_Type = ADU   
					1-65536   
					Starting address of Address_Type = PDU   
					Address   
					read block   
					0-65535   
					Address_Type = Modicon_5digit   
					40001, 30001, etc   
					Scaling zero in Data   
					Array   
					Scaling max in Data   
					Array   
					Any signed 32 bit integer in the range:   
					-2,147,483,648 to 2,147,483,647. 0   
					Any signed 32 bit integer in the range:   
					-2,147,483,648 to 2,147,483,647. 100   
					Any signed 32 bit integer in the range:   
					-2,147,483,648 to 2,147,483,647. 0   
					Any signed 32 bit integer in the range:   
					-2,147,483,648 to 2,147,483,647. 100   
					No_Response,   
					Old_Data,   
					Zero_Data,   
					FFFF_Data,   
					Refer to Appendix A.6 for further   
					information.   
					Data_Array_Low_Scale*   
					Data_Array_High_Scale*   
					Node_Low_Scale*   
					Scaling zero in   
					Connected Node   
					Scaling max in   
					Connected Node   
					Set the FieldServer   
					response to the   
					Modbus RTU Client   
					when the Server Node   
					supplying the data has   
					gone offline   
					Node_High_Scale*   
					Node_Offline_Response   
					8 Optional only for Modicon_5digit addressing, and only if Single writes do not need to be forced   
					
					
				FS-8700-01_Modbus_RTU_(T28700-01) Driver Manual   
					Page 15 of 21   
					Appendix A. Advanced Topics – Modbus RTU   
					Appendix A.1. Data Types   
					If Node parameter Address_Type is set as ADU or PDU, then Data_Type must be specified   
					as follows   
					For Address_Type ADU :   
					Address range   
					Data_Type   
					Function Code (Write)   
					Function Code (Read)   
					1 - 65536   
					Coil   
					15   
					1 
					2 
					4 
					3 
					1 – 65536   
					1 – 65536   
					1 - 65536   
					Discrete_Input   
					Input_Register   
					Holding_Register   
					n/a.   
					n/a.   
					16   
					For Address_Type PDU :   
					Address range   
					Data_Type   
					Function Code (Write)   
					Function Code (Read)   
					0 - 65535   
					0 – 65535   
					0 – 65535   
					0 – 65535   
					FC01   
					FC02   
					FC04   
					FC03   
					15   
					1 
					2 
					4 
					3 
					n/a.   
					n/a.   
					16   
					For Address_Type Modicon_5digit   
					When a Modbus address range is specified, a particular Data Type is implied. The defaults   
					are as follows:   
					Address range   
					40001 - 49999   
					30001 - 39999   
					10001 - 19999   
					00001 - 09999   
					Data_Type   
					Register   
					Analog _Input   
					Digital_Input   
					Coil   
					Function Code (Write)   
					16   
					n/a.   
					n/a.   
					15   
					Function Code (Read)   
					3 
					4 
					2 
					1 
					
					
				FS-8700-01_Modbus_RTU_(T28700-01) Driver Manual   
					Page 16 of 21   
					Appendix A.2. Single Writes   
					For pure write operations where the function = WRBC or WRBX, the driver defaults to using   
					Function Codes 15 and 16 (Multiple writes). It is possible to force the driver to use Function   
					Codes 5 and 6 (Single Writes) by manipulating the Data_Type parameter as follows:   
					For Address_Type ADU:   
					Address range Data_Type   
					Function Code (Write)   
					1 - 65536   
					1 - 65536   
					Single_Coil   
					Single_Register l   
					5 
					6 
					For Address_Type PDU:   
					Address range Data_Type Function Code (Write)   
					0 - 65535   
					0 - 65535   
					FC05   
					FC06   
					5 
					6 
					For Address_Type Modicon_5digit   
					Address range Data_Type   
					Function Code (Write)   
					40001 - 49999   
					30001 - 39999   
					Single_Register   
					Single_Coil   
					6 
					5.   
					Example: FC 6 = Write Single Register   
					Add a parameter to the Modbus client side Map Descriptor called Data_Type.   
					If you specify the Data_Type as Single_Register and the Function as WRBC or WRBX,   
					then a Modbus poll with FC 6 will be generated.   
					Logically Single Register implies a length of one, and even if you try to set the length longer   
					in the csv file, the length is limited to 1 in the driver.   
					Appendix A.3. Read/write Operation   
					When using the driver as a Modbus master, the function RDBC allows read/write capability   
					with Register and Coil data types. If defaults are used, then Function codes 5 and 6 (Single   
					Writes) are used to write data back to the registers being read, regardless of data length   
					being read. If multiple writes (FC 15 and 16) are needed for Read/write operation, the user   
					needs to specify the Node_Type parameter in the Client Side Nodes Section and set it to   
					Block_Mode.   
					Note that block writes of length 1 are currently all that is supported.   
					
					
				FS-8700-01_Modbus_RTU_(T28700-01) Driver Manual   
					Transferring 32 bit values with two registers   
					Page 18 of 21   
					If a Modbus Server sends two consecutive registers to the FieldServer representing either a   
					floating point value or a 32 bit integer value, the FieldServer can combine and decode these   
					registers back into their original format. To do this, the user must read the registers into an   
					integer data array, and then use the Moves function to move the data to a floating point or   
					32 bit integer data array. The “function” field in the move must be populated with the correct   
					move function required. Details of the available function fields are listed in the FieldServer   
					configuration manual along with a more detailed explanation of moves. Note that functions   
					also exist to split a floating point value into two integers using the reverse operation.   
					A diagrammatic representation of this process is depicted below:   
					Source Data   
					Float Data Array   
					-------------------------   
					Offset 40: Float value   
					-------------------------   
					Modbus   
					Device   
					Two 16 bit   
					integers   
					Special   
					Move   
					Array   
					-------------------------   
					Offset 0: 40001   
					-------------------------   
					Offset 1: 40002   
					-------------------------   
					Modbus   
					polled:   
					e.g:   
					40001,   
					length 2   
					Together, they   
					combine to   
					form a 32 bit   
					IEEE Floating   
					point number.   
					Sensible data   
					Unreadable   
					content   
					The example below shows how a floating point value is retrieved from two Modbus registers   
					that were placed in an integer data array.   
					Example   
					Data_Arrays   
					Data_Array_Name, Data_Format, Data_Array_Length   
					DA1,   
					DA2,   
					int16,   
					float,   
					20   
					10   
					Moves   
					Function,   
					2.i16-1.float-sw, DA1,   
					Source_Data_Array, Source_Offset, Target_Data_Array, Target_Offset   
					0, DA2,   
					6 
					This Move will cause two integers at offsets 0 and 1 in the integer Data Array DA1 to be   
					copied to offset 6 in the float Data Array DA2. In the process of copying the values, the   
					integers will be combined and treated as an IEEE 32 bit floating point number.   
					Appendix A.5. Connection to York Modbus Microgateway   
					If connecting the FieldServer to a York Modbus Microgateway, the Node_ID of the   
					Microgateway is defined by the address DIP switches. If switch 4 is set to ‘On’ and the other   
					switches are set to ‘off’ then Node_ID of the Microgateway is ‘247’, the parity is ‘Even’, and   
					the stop bits are 1. Other Node_ID combinations can be found in the York Modbus   
					Microgateway Installation Manual.   
					
					
				FS-8700-01_Modbus_RTU_(T28700-01) Driver Manual   
					Page 19 of 21   
					Appendix A.6. Node_Offline_Response   
					This function is specific to the Modbus RTU driver.   
					In systems where data is being collected from multiple Server Nodes and made available on   
					a FieldServer configured as a Modbus RTU Server, when a Server Node goes offline the   
					default behavior of the FieldServer would be to stop responding to polls for this data. This   
					might not be what the user wants. Various options exist making it possible to signal that the   
					data quality has gone bad without creating error conditions in systems sensitive to the   
					default option.   
					The following   
					options   
					can   
					be configured   
					under the Node   
					parameter,   
					Node_Offline_Response, to set the response of the FieldServer to the Modbus RTU Client   
					when the Server Node supplying the data is offline:   
					• 
					• 
					No_Response - this is the default option. The FieldServer simply does not respond when   
					the corresponding Server Node is offline.   
					Old_Data - The FieldServer will respond, but with the last known value of the data. This   
					maintains the communication link in an active state, but may hide the fact that the Server   
					Node is offline.   
					• 
					• 
					Zero_Data - The FieldServer will respond, but with the data values set to zero. If the   
					user normally expects non-zero values, this option will signal the offline condition without   
					disrupting communications.   
					FFFF_Data - The FieldServer will respond, but with the data values set to FFFF (hex). If   
					the user normally expects other values, this option will signal the offline condition without   
					disrupting communications.   
					Example:   
					Nodes   
					Node_name,   
					DEV11,   
					DEV12,   
					DEV15,   
					DEV16,   
					Node_ID,   
					11,   
					Protocol,   
					Node_Offline_Response, port   
					Modbus_rtu,   
					Modbus_rtu,   
					Modbus_rtu,   
					Modbus_rtu,   
					No_Response,   
					Old_Data,   
					- 
					- 
					- 
					- 
					12,   
					15,   
					16,   
					Zero_Data,   
					FFFF_Data,   
					
					
				FS-8700-01_Modbus_RTU_(T28700-01) Driver Manual   
					Page 20 of 21   
					Appendix B. Modbus ASCII - Examples of FieldServer setup for typical clients   
					Appendix B.1. FieldServer with GE Cimplicity as client   
					• 
					Run the Cimplicity “Workbench” and create a “New Project” with a unique “Project   
					Name” option of “Basic Control” and protocol “Modbus ASCII”.   
					Check the project properties and continue with the “Project Wizard Setup” that appears.   
					Add Modbus port giving it a description.   
					Create and configure the devices, select “new item”.   
					Name the device, select the port, give it a description (e.g. FieldServer), and choose   
					“SYSTEM” resource.   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					Create and configure the points.   
					Select “new item”, name the point and choose the appropriate device.   
					Under the “General” tab, point properties require a description. Note that the elements   
					must have a value greater than 8.   
					• 
					Under the “Device” tab, properties need the appropriate address (e.g. 40001 and also   
					require the leading 0’s), change the update criteria to “On Scan”.   
					When the project is configured, run by pressing the “play” button.   
					Expect the Cimplicity driver to connect and poll the FieldServer for a range of valid   
					addresses, and then proceed to poll for just the configured Points.   
					From the start menu choose the “Point Control Panel”, select edit and add the project   
					you want to view. Note, to log on the User name “ADMINISTRATOR” must be supplied   
					Use “Modbus ASCII Diagnostics” to connect to host and then read the register.   
					• 
					• 
					• 
					• 
					Appendix B.2. FieldServer with Intellution FIX as a client   
					• 
					• 
					• 
					• 
					• 
					• 
					Install Intellution FIX, choosing the MB1 Modbus ASCII I/O driver   
					Run from Start menu and choose “Intellution Fix”.   
					Choose “System Configuration Utility”.   
					Modify SCADA, add the MB1 Modbus ASCII I/O driver   
					Configure the Modbus ASCII Driver.   
					Device is D11, select 5-digit address, add the FieldServer virtual Node ID to station   
					address   
					• 
					• 
					• 
					• 
					• 
					• 
					• 
					Set up poll record   
					SAVE the configuration.   
					Open “StaRTUp”   
					Open “Mission Control” from the “Apps” menu and confirm Fix is polling.   
					To display the data create a link in Fix draw, add link, data link.   
					Give it a tagname, allow data entry, numeric entry and set enable option.   
					If tag is not in database, select “Add”, choose “AR”. Then set output enable , device   
					MB1, I/O address d11.   
					• 
					• 
					Save the settings   
					Use “Quickview” from the “View” menu to confirm the reading of data without ???   
					appearing   
					• 
					Change the value and wait a few seconds to ensure the change really occurred.   
					
					
				FS-8700-01_Modbus_RTU_(T28700-01) Driver Manual   
					Page 21 of 21   
					THIS PAGE INTENTIONALLY LEFT BLANK   
					
					
				 |