| 	
		 48ZG,ZN030-105   
					48ZT,ZW,Z6,Z8075-105   
					Gas Heating/Electric Cooling Units   
					with COMFORTLINK™ Controls   
					User’s Information Manual   
					NOTE TO INSTALLER:   
					TO LIGHT UNIT   
					This manual should be left with the equipment owner.   
					1. Do not turn off the electrical power to unit without   
					first turning off the gas supply.   
					2. Before attempting to start the gas heating section,   
					familiarize yourself with all the procedures that must   
					be followed.   
					WARNING: If the information in this   
					manual is not followed exactly, a fire or   
					explosion may result causing property   
					damage, personal injury or loss of life.   
					— Do not store or use gasoline or other   
					flammable vapors and liquids in the   
					vicinity of this or any other appliance.   
					— WHAT TO DO IF YOU SMELL GAS   
					• Do not try to light any appliance.   
					3. Never attempt to manually light the unit with a match,   
					lighter, or any other flame. If the electric sparking de-   
					vice fails to light the burners, refer to the shutdown   
					procedures, then call your dealer as soon as possible.   
					If you do not follow these instructions exactly, a fire or   
					explosion may result, causing property damage, injury, or   
					loss of life.   
					• Do not touch any electrical switch;   
					do not use any phone in your   
					building.   
					• Immediately call your gas supplier   
					from a neighbor’s phone. Follow the   
					gas supplier’s instructions.   
					See Fig. 1 for location of gas valve(s). Refer to Fig. 2 while   
					proceeding with the following steps.   
					1. Turn off the unit demand for cooling or heating by using   
					the scrolling marquee. The scrolling marquee is located in   
					the control box at the compressor end of the unit.   
					• If you cannot reach your gas sup-   
					plier, call the fire department.   
					ESCAPE   
					a. Push the   
					is shown.   
					key unit a blank display screen   
					— Installation and service must be per-   
					formed by a qualified installer, service   
					agency or the gas supplier.   
					b. Push the   
					lit.   
					key until the SERVICE TEST LED is   
					ENTER   
					c. Push the   
					STOP.   
					key. The display will show   
					key again. The NO/YES display   
					key to toggle the display to   
					ENTER   
					d. Push the   
					will flash.   
					Improper installation, adjustment, alteration, service, or   
					maintenance can cause injury or property damage. Refer to   
					this manual. For assistance or additional information, con-   
					sult a qualified installer, service agency, or the gas supplier.   
					e. Push the   
					or   
					ENTER   
					YES and then push   
					. The unit will be   
					locked off from heating, cooling or any operation.   
					The controls will still function and the display will   
					still operate.   
					2. Close the field-installed manual gas shutoff valve.   
					Before performing recommended maintenance, be sure   
					main power switch to unit is turned off. Electrical shock   
					could cause personal injury.   
					3. Turn off the electrical power to the unit using the optional   
					disconnect or the field-installed disconnect and lock off   
					using proper lockout and tag-out procedures.   
					Your combination heating/cooling rooftop unit is equipped   
					with an automatic direct spark ignition system and induced-   
					draft power combustion blower.   
					4. Open the burner section hinged access door.   
					5. Move the switch on the gas valves to the OFF position   
					and wait 5 minutes.   
					NOTE: If this is the first installation of the unit, the gas   
					flue hoods must be installed before operating unit. These   
					must be installed for the unit to run properly.   
					Do not attempt to light by hand; personal injury may result.   
					6. Move the switch on the gas valves to the ON position.   
					7. Close the burner section hinged access door.   
					8. Turn on the electrical supply to the units.   
					9. Open the field-installed manual gas valve.   
					Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.   
					Catalog No. 04-53480045-01 Printed in U.S.A. Form 48Z-5SO Pg 1 7-07 Replaces: 48Z-3SO   
					Book 1   
					Tab 1a   
				MAIN   
					MODE   
					Run Status   
					Service Test   
					Temperature   
					ON   
					Pressures   
					Setpoints   
					Inputs   
					Alarm Status   
					Outputs   
					Configuration   
					Time Clock   
					Operating Modes   
					Alarms   
					ESCAPE ENTER   
					OFF   
					STEP 1   
					STEP 2   
					LOCK-OUT   
					G 
					TA   
					STEP 3   
					a48-8297   
					STEP 5   
					STEP 4   
					a48-8298   
					STEP 6   
					STEP 7   
					MODE   
					Run Status   
					Service Test   
					Temperature   
					Pressures   
					Setpoints   
					Inputs   
					Alarm Status   
					Outputs   
					Configuration   
					Time Clock   
					Operating Modes   
					Alarms   
					ESCAPE ENTER   
					STEP 8   
					STEP 9   
					STEP 10   
					Fig. 2 — To Light Unit   
					3 
				For your safety, keep the gas heating area clear and free of   
					combustible materials, gasoline, and other flammable liquids   
					and vapors.   
					TO SHUT UNIT OFF   
					To ensure proper functioning of the unit, flow of combus-   
					tion and ventilating air must not be obstructed from reaching   
					the gas heating area. Clearance of at least 4 ft on all sides is   
					required.   
					Do not turn off the electrical power to unit without first   
					turning off the gas supply.   
					Never attempt to manually light the main burners on a unit   
					with a match, lighter, or any other flame.   
					ROUTINE MAINTENANCE AND CARE   
					FOR THE EQUIPMENT OWNER   
					If the electric sparking device fails to light the main burn-   
					ers, refer to the following shut off procedure, then call your   
					dealer as soon as possible.   
					Failure to follow these procedures can result in serious fire   
					or personal injury.   
					Before proceeding with those things you might want to   
					maintain yourself, please carefully consider the following:   
					See Fig. 1 for location of gas valve(s). Refer to Fig. 3 while   
					proceeding with the following steps.   
					1. Turn off the unit demand for cooling or heating by using   
					the scrolling marquee. The scrolling marquee is located in   
					the control box at the compressor end of the unit.   
					1. TURN OFF GAS SUPPLY FIRST AND THEN   
					ELECTRICAL POWER TO YOUR UNIT BEFORE   
					SERVICING OR PERFORMING MAINTENANCE.   
					2. Do not turn off electrical power to this unit without   
					first turning off the gas supply.   
					3. When opening access doors or performing mainte-   
					nance functions inside your unit, be aware of sharp   
					sheet metal parts and screws. Although special care   
					has been taken to reduce sharp edges to a minimum,   
					be extremely careful when handling parts or reaching   
					into the unit.   
					ESCAPE   
					a. Push the   
					is shown.   
					key unit a blank display screen   
					b. Push the   
					lit.   
					key until the SERVICE TEST LED is   
					ENTER   
					c. Push the   
					STOP.   
					key. The display will show   
					key again. The NO/YES display   
					key to toggle the display to   
					Failure to follow these procedures can result in serious fire   
					or personal injury.   
					ENTER   
					d. Push the   
					will flash.   
					e. Push the   
					or   
					Air Filters — Air filters should be checked at least every   
					3 or 4 weeks and changed or cleaned whenever they become   
					dirty. Table 1 indicates the correct filter size for your unit. Open   
					the hinged filter access door to replace or inspect the filters. All   
					units have filter tracks into which the filters slide. Remove the   
					filters by pulling outward from the track. See Fig. 4 for filter   
					access door location. Note the direction of flow arrows on the   
					filter frame.   
					ENTER   
					YES and then push   
					. The unit will be   
					locked off from heating, cooling or any operation.   
					The controls will still function and the display will   
					still operate.   
					2. Close the field-installed manual gas shutoff valve.   
					3. Turn off the electrical power to the unit using the optional   
					disconnect or the field-installed disconnect and lock off   
					using proper lockout and tag-out procedures.   
					If you have difficulty in locating your air filter in the return-   
					air duct system, or if you have questions concerning proper   
					filter maintenance, contact your dealer for instructions.   
					4. Open the burner section hinged access door.   
					Table 1 — Indoor-Air Filter Data*   
					5. Move the switch on the gas valves to the OFF position   
					and wait 5 minutes before doing any service in the section   
					or on the piping.   
					6. Close the burner section hinged access door.   
					7. If unit is being shut down because of a malfunction, call   
					your dealer as soon as possible.   
					UNIT SIZE   
					48Z   
					QUANTITY...Size   
					(in.)   
					FILTER TYPE   
					Disposable Fiberglass   
					(Standard) or Medium Effi-   
					ciency 30% Pleated (Optional)   
					8...20 x 25 x 2,   
					8...20 x 20 x 2   
					030-050   
					055-070   
					90% Bag (Optional) with High- 6...20 x 24 x 22,   
					Velocity Pre-Filters   
					6...20 x 20 x 22,   
					12...16 x 20 x 2,   
					3...20 x 24 x 2   
					If unit is being shut down because the heating season has   
					ended, restore electrical power to the unit and reset the   
					scrolling marquee to Run mode to ensure operation of the   
					cooling system during the cooling season.   
					Disposable Fiberglass   
					(Standard) or Medium Effi-   
					ciency 30% Pleated (Optional)   
					12...20 x 25 x 2,   
					12...20 x 25 x 2   
					IMPORTANT: Should overheating occur or the gas supply   
					fail to shut off, shut off the manual gas valve to the unit   
					before shutting off the electrical supply.   
					90% Bag (Optional) with High- 6...24 x 20 x 22,   
					Velocity Pre-Filters   
					6...24 x 24 x 22,   
					6...20 x 24 x 2,   
					6...24 x 24 x 2   
					Do not use this unit if any part has been under water. Imme-   
					diately call a qualified service technician to inspect the unit and   
					to replace any part of the control system and gas control that   
					has been under water.   
					Disposable Fiberglass   
					12...20 x 25 x 2,   
					12...20 x 20 x 2   
					(Standard) or Medium Effi-   
					ciency 30% Pleated (Optional)   
					075   
					High Efficiency 65% Pleated   
					(Optional)   
					12...20 x 25 x 2,   
					12...20 x 20 x 2   
					Disposable Fiberglass   
					MAINTAINING YOUR UNIT   
					12...20 x 25 x 2,   
					12...20 x 20 x 2   
					(Standard) or Medium Effi-   
					ciency 30% Pleated (Optional)   
					090,105   
					All maintenance should be handled by skilled, experienced   
					personnel. Your dealer can help you establish a standard   
					procedure.   
					High Efficiency 65% Pleated   
					(Optional)   
					*See base unit Installation Instructions if field-supplied or optional   
					factory-supplied filters are used. When replacing filters, always use   
					the same type and size originally supplied.   
					12...20 x 25 x 2,   
					12...20 x 20 x 2   
					4 
				When replacing your unit filters, always use the same size   
					and type of filter that was originally supplied by the installer.   
					Units with outdoor air capability have a cleanable filter for   
					the outdoor air. This filter should be checked annually and   
					cleaned as necessary. Remove by removing screws in outdoor-   
					air filter retainer and sliding filters out of the unit.   
					Heat Exchanger — To ensure dependable and efficient   
					heating operation, the heat exchanger should be checked by a   
					qualified maintenance person before each heating season, and   
					cleaned when necessary. This checkout should not be attempt-   
					ed by anyone not having the required expertise and equipment   
					to do the job properly. Checking and/or cleaning the heat   
					exchanger involves removing the gas controls assembly and   
					the flue collector box cover and, when completed, reinstalling   
					the gas controls assembly for proper operation. Also, the flue   
					collector box cover must be replaced correctly so that a proper   
					seal is maintained. Contact your dealer for the required period-   
					ic maintenance.   
					Never operate your unit without filters in place. Failure to   
					heed this warning may result in damage to the blower   
					motor and/or compressor. An accumulation of dust and lint   
					on internal parts of your unit can cause loss of efficiency   
					and, in some cases, fire.   
					MAIN   
					MODE   
					Run Status   
					Service Test   
					Temperature   
					ON   
					Pressures   
					Setpoints   
					Alarm Status   
					Inputs   
					Outputs   
					Configuration   
					Time Clock   
					Operating Modes   
					Alarms   
					ESCAPE ENTER   
					OFF   
					STEP 1   
					STEP 2   
					LOCK-OUT   
					G 
					TA   
					STEP 3   
					STEP 5   
					STEP 4   
					STEP 7   
					STEP 6   
					Fig. 3 — To Shut Unit Off   
					5 
				SIZES 030-050 (040 SHOWN)   
					SIZES 055-070   
					POWER EXHAUST VFD   
					(NEAR SIDE)   
					POWER EXHAUST   
					CONTROL BOX   
					(FAR SIDE)   
					ACCESS DOOR   
					ACCESS DOOR   
					(FAR SIDE ONLY)   
					FLUE OUTLETS   
					(FAR SIDE)   
					(NEAR SIDE ONLY)   
					ACCESS DOOR   
					(BOTH SIDES)   
					ACCESS DOOR   
					(FAR SIDE ONLY)   
					CONTROL BOX   
					GAS SECTION   
					ACCESS DOOR   
					(FAR SIDE)   
					POWER EXHAUST ACCESS DOOR   
					(BOTH SIDES)   
					ACCESS DOOR   
					(BOTH SIDES)   
					FILTER   
					ACCESS   
					SIZES 075-105   
					Fig. 4 — Door Locations (48Z Series Units)   
					6 
				See Fig. 1 and 5 and proceed as follows to inspect the com-   
					bustion area and power-venting system of your unit.   
					1. Turn off gas supply and then electrical power to your unit.   
					2. Open gas section access door.   
					3. Using a flashlight, carefully inspect the burner areas for   
					dirt, soot, rust, or scale.   
					Fan and Belts — Periodically check the condition of fan   
					wheels and housings and belt tension. When service is neces-   
					sary, call your dealer.   
					Evaporator-Fan Motor, Condenser-Fan Motor   
					and Combustion-Fan Motor — Lubrication is not   
					recommended. Bearings will not require lubrication for at least   
					5 years of normal operation. After 5 years, motor life can be   
					extended by having the motors serviced at an authorized motor   
					service shop.   
					If dirt, soot, rust, or scale accumulations are found, call   
					your dealer and do not operate your heating section.   
					Bodily injury or unit damage may result.   
					Fan Shaft Bearings — Charge fittings annually with   
					Shell Alvania No. 2 or equivalent grease.   
					Evaporator and Condenser Coils — Cleaning of the   
					coils should only be done by qualified service personnel.   
					Contact your dealer for the required maintenance as needed.   
					4. When you have completed your inspection, follow the   
					start-up procedures in this manual to restore your unit to   
					operation.   
					5. Observe unit heating operation, and watch the burner   
					flame core to see if it is bright blue. If you observe a sus-   
					pected malfunction, or if the burner flame cores are not   
					bright blue, call your dealer. See Fig. 6.   
					Condensate Drain — The drain pan and condensate   
					drain line should be checked and cleaned at the same time the   
					cooling coils are checked by your dealer.   
					Compressors — All compressors are factory shipped   
					with a normal charge of the correct type refrigeration grade oil   
					in them and should rarely require additional oil. The service   
					technician must be certain the proper oil level is maintained in   
					the compressor when it is installed and running.   
					NOTE: Burner flame cores that have a mixture of orange,   
					yellow, or red flames together with the blue may not be   
					burning gas efficiently. Your dealer may have to adjust   
					the air/gas mixture.   
					6. Replace gas section access panel.   
					Condenser Fan   
					Unit Panels and Doors — After performing any main-   
					tenance or service on the unit, be sure all panels and doors are   
					securely fastened in place to prevent rain from entering   
					unit cabinet and to prevent disruption of the correct unit airflow   
					pattern.   
					Do not poke sticks, screwdrivers, or any other object into   
					revolving fan blades. Severe bodily injury may result.   
					The fan must be kept free of all obstructions to ensure prop-   
					er cooling. Contact your dealer for any required service.   
					Electrical Controls and Wiring — Electrical controls   
					are difficult to check without proper instrumentation; therefore,   
					if there are any discrepancies in the operating cycle, contact   
					your dealer and request service.   
					Refrigerant Circuit — The refrigerant circuit is difficult   
					to check for leaks without the proper equipment; therefore,   
					if inadequate cooling is suspected, contact your dealer for   
					service.   
					Fig. 5 — Typical Location of Access Panel   
					Combustion Area and Vent System — The com-   
					bustion area and vent system should be visually inspected be-   
					fore each heating season. The normal accumulation of dirt,   
					soot, rust, and scale can result in loss of efficiency and improp-   
					er performance if allowed to build up. Accumulation on the   
					burner crossover tube can result in the burners firing out of nor-   
					mal time sequence. This delayed ignition is characterized by an   
					especially loud sound.   
					If your unit makes an unusual or especially loud noise   
					when the main burners are lit, shut down the heating   
					section and call your dealer. Bodily injury or unit damage   
					may result.   
					Fig. 6 — Proper Flame Appearance   
					7 
				REGULAR DEALER MAINTENANCE   
					BEFORE YOU CALL FOR SERVICE, CHECK   
					FOR SEVERAL EASILY SOLVED PROBLEMS   
					In addition to the type of routine maintenance you might be   
					willing to perform, your unit should be inspected regularly by a   
					properly trained service technician. An inspection (preferably   
					each year, but at least every other year) should include the   
					following:   
					1. Inspection of all flue product passages — including the   
					burners, heat exchanger, flue collector box, and vent pipe.   
					If insufficient heat or cooling is suspected:   
					( 
					) Check for sufficient airflow. Check the air filters for dirt.   
					Check for blocked return-air or supply-air grilles. Be sure they   
					are open and unobstructed. Be sure heating and cooling set   
					points are correct. If these checks do not reveal the cause, call   
					your servicing dealer.   
					2. Inspection of all combustion-air and ventilation-air pas-   
					sages and openings.   
					3. Close inspection of all gas pipes leading to and inside   
					your unit.   
					4. Adjustment of the air/gas mixture if the burner flames are   
					not bright blue. (See Fig. 5 and 6 for location of access   
					panel and proper flame appearance.)   
					5. Inspection, and if required, cleaning of the condenser and   
					evaporator coils.   
					If your unit is not operating at all, check the following list for   
					easy solutions:   
					( 
					) Check to be sure that heating temperature set point is set   
					above the indoor temperature during the heating season, or that   
					cooling temperature set point is below the indoor temperature   
					during the cooling season. Be sure the unit on/off switch is in   
					the ON position and not in the OFF position. Be sure unit has   
					been programmed with the appropriate time schedules and   
					desired operating set points.   
					( 
					) Is the electrical supply switch ON? Are any fuses blown,   
					or have any of the circuit breakers tripped?   
					) During the heating season, check the manual shutoff   
					6. Inspection, and if required, cleaning of the evaporator   
					drain pan.   
					7. Inspection, cleaning, and lubrication of blower wheel   
					housing and motor.   
					8. Inspection of all supply-air and return-air ducts for leaks,   
					obstructions, and insulation integrity. Any problems   
					found should be resolved at this time.   
					9. Inspection of the unit base to ensure that no cracks, gaps,   
					etc., exist which may cause a hazardous condition.   
					( 
					valve. Is this lever parallel with the pipe, indicating that the   
					valve is open? Or is the lever at a right angle, indicating that   
					the valve is closed? If closed, has the gas been shut off for   
					safety reasons? Otherwise, you may open the valve and follow   
					the start-up procedures listed in this manual.   
					NOTE: Before proceeding with the next check, turn OFF the   
					electrical power supply to the unit. Open the control access   
					door.   
					10. Inspection of the unit casing for signs of deterioration.   
					11. Inspection of all electrical wiring and components to   
					assure proper connection.   
					12. Inspection for leaks in the refrigerant circuit. Pressure-   
					check to determine appropriate refrigerant charge.   
					( 
					) During the heating season, check the control switch on   
					the gas valve. It is in the ON position? If it is not, be sure it has   
					not been turned off for the purpose of safety. Follow the start-   
					up procedures in this manual.   
					( 
					) If your unit still fails to operate, call your servicing dealer   
					13. Operational check of the unit to determine working con-   
					ditions. Repair or adjustment should be made at this time.   
					14. Your servicing dealer may offer an economical service   
					contract that covers seasonal inspections. Ask for further   
					details.   
					Complete Service Instructions can be found in the base unit   
					Controls, Start-Up, Operation, Service and Troubleshooting   
					literature.   
					for troubleshooting and repairs. Specify the model and serial   
					numbers of your unit. (Record them in this manual in the space   
					provided.) If the dealer knows exactly which unit you have, he   
					may be able to offer suggestions over the phone, or save valu-   
					able time through knowledgeable preparation for the service   
					call.   
					IN CASE OF TROUBLE   
					If, after performing the above, unit performance is unsatis-   
					factory, shut off the unit and call your dealer.   
					Dealer’s Name _____________________________________   
					Telephone No. _____________________________________   
					Unit Model ________________________________________   
					Unit Serial Number _________________________________   
					Unit Address ______________________________________   
					Bus Number _______________________________________   
					Copyright 2007 Carrier Corporation   
					Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.   
					Catalog No. 04-53480045-01 Printed in U.S.A. Form 48Z-5SO Pg 8 7-07 Replaces: 48Z-3SO   
					Book 1   
					Tab 1a   
				 |