Bunn H5E H5X User Manual

®
BUNN  
W
H5E  
H5X  
R E P L A C E M E N T O F A N Y C O M P O N E N T !  
B E F O R E R E M O V A L O F A N Y P A N E L O R  
D I S C O N N E C T F R O M P O W E R S O U R C E  
!
A R N  
I N G  
WARNING  
!
Very Hot Water  
Use With Care!  
OPERATING & SERVICE MANUAL  
BUNN-O-MATIC CORPORATION  
POST OFFICE BOX 3227  
SPRINGFIELD, ILLINOIS 62708-3227  
PHONE: (217) 529-6601 FAX: (217) 529-6644  
10420.0000G 7/00 © 1989 BUNN-O-MATIC CORPORATION  
USER NOTICES  
The notices on this dispenser should be kept in good condition. Replace unreadable or damaged labels.  
12593.0000  
00831.0000  
00656.0000  
10044.0000  
10420 072500  
3
ELECTRICAL REQUIREMENTS  
CAUTION - The dispenser must be disconnected from the power source until specified in Initial Set-Up.  
This dispenser requires 2-wire, grounded service rated 120, 208, or 240 volts ac, 20 amp, single phase.  
(Refer to the dispensers dataplate for exact voltage requirement.)  
Electrical Hook-Up  
CAUTION – Improper electrical installation will damage electronic components.  
WHITE  
1. An electrician must provide electrical service as specified.  
NEUTRAL  
120V.A.C.  
L1 BLACK  
2. Using a voltmeter, check the voltage and color coding of each conductor at  
the electrical source.  
3. Remove the upper and lower rear panels. Place the tank heater switch on the  
electronic control assembly in the OFFposition.  
4. Install a strain relief and the proper electrical wiring to the terminal block.  
L2 RED  
5. Connect the dispenser to the power source and verify the voltage at the termi-  
208 or 240V.A.C.  
nal block before proceeding. Reinstall both rear panels.  
L1 BLACK  
6. Ifplumbingistobehooked-uplaterbesurethedispenserisdisconnectedfrom  
the power source. If Plumbing has been hooked-up, the dispenser is ready for  
Initial Set-Up.  
PLUMBING REQUIREMENTS  
This dispenser must be connected to a COLD WATER system with operating pressure between 20 and 90 psi (138  
1
and 620 kPa) from a 2" or larger supply line. A shut-off valve should be installed in the line before the dispenser.  
Install a regulator in the line when pressure is greater than 90 psi (620 kPa) to reduce it to 50 psi (345 kPa). The  
1
water inlet fitting is 4" flare.  
1
3
NOTE - Bunn-O-Matic recommends 4" copper tubing for installations of less than 25 feet and 8" for more than  
1
25 feet from the 2" water supply line. At least 18 inches of an FDA approved flexible beverage tubing, such as  
reinforced braided polyethylene or silicone, before the dispenser will facilitate movement to clean the countertop.  
It can be purchased direct from Bunn-O-Matic (part number 00326-0000). Bunn-O-Matic does not recommend  
the use of a saddle valve to install the dispenser. The size and shape of the hole made in the supply line by this type  
of device may restrict water flow.  
This equipment must be installed to comply with the Basic Plumbing Code of the Building Officials  
and Code Administrators International, Inc. (BOCA) and the Food Service Sanitation Manual of the  
Food and Drug Administration (FDA).  
A
b
C
F
IRUYIN  
G
ustibles.  
al co  
O
B
E
READ THE ENT  
M
IRE OPERATING MANUAL  
,
P
LIABILITY BEFORE  
INCLUDING THE LIMIT OF WARRANTY AND  
LY  
O
R
G
OR USING THIS PRODUCT  
des  
E
R
S
,
.
IS  
H
K
S
C
E
O
Q
U
A
K
IP  
ENEVER  
THIS APPLIANCE IS HEATED WH  
H
M
E
R
POWER SOURCE  
D
Z
N
A
T
CONNECTED TO  
A
00831.0000A 5/88 1988 BUNN-O-MATIC CORPORATION  
©
Plumbing Hook-Up  
1. Flush the water line and securely attach it to the flare fitting on the  
rear of the dispenser.  
2. Turn-on the water supply.  
This equipmen
comply with the Ba
Administrators International,
the Building Officials an
and the Food Service Sanitation M  
of the Food and Drug Administration (
anual  
P1770  
10420 072500  
4
INITIAL SET-UP  
CAUTION - The dispenser must be disconnected from the power source throughout the initial set-up, except  
when specified in the instructions.  
1. Remove the upper rear panel and place the tank heater switch in  
the OFFposition and replace the panel.  
Connect the dispenser to the power source and turn-on the water  
supply.  
Water will automatically flow into the tank to the proper level and  
shut-off. This will take approximately 10 minutes.  
Disconnect the dispenser from the power source, remove the up-  
per rear panel and place the tank heater switch in the ONposi-  
tion, and replace the panel.  
2.  
3.  
4.  
DO NOT  
!
O
ON  
O
CAUTIO
Until Water Comes From Ope
Turn On The Tank He
STOP  
H
ot  
W
READ NOT
Automatically When Unit Is  
C
ater Systems  
Coffee Brew  
Accordance  
W
W
ers  
ater Tank  
W
Failure To Comply Voids Warranty!  
ith The Installation Instructions!  
Fill The  
W
onnected To Power!  
ill Fill  
ater Tank In  
WARNING  
HAZARDO
VOLTAGE  
DISCONNECT FROM  
POWER SOURCE  
BEFORE REMOVING!  
5. Connect the dispenser to the power source and wait approximately  
twenty minutes for the water in the tank to heat.  
P1771  
6.  
On models with ready indicator, the indicator will glow when the  
proper water temperature for use is achieved.  
NOTE - Discontinue dispensing if the indicator LED turns off. Dispense only when the indicator LED glows.  
DRAINING THE DISPENSER  
CAUTION - The dispenser must be disconnected from the power source throughout these steps.  
1. Disconnect the dispenser from the power source.  
2. Shut-off and disconnect the incoming water supply  
3. Remove the 4-40 screws at the sides of the top panel.  
4. Gently remove one of the grommets from the tank lid.  
5. Insert a tube to the bottom of the tank and syphon ALL of the water out. Bunn-O-Matic has a syphon assem-  
bly available (#12440.0000) for this purpose.  
NOTE - The dispenser must be full using the INITIAL SET-UP steps before reconnecting to the power source.  
CLEANING  
The use of a damp cloth rinsed in any mild, non-abrasive, liquid detergent is recommended for cleaning all  
surfaces on Bunn-O-Matic equipment.  
WALL MOUNTED INSTALLATION  
If the dispenser is wall mounted, the bottom of the dispenser should be at the same height as a counter or  
table top. Use B.O.M. part #12542.0000 for side mounted Wall Bracket Kit or # 13125.0001 for front mounted  
Wall Bracket Kit .  
SUPPORT FOR LARGE RECEPTACLES  
CAUTION: If the dispenser is to be used with larger receptacles such as pitchers or pots, those receptacles must  
be adequately supported during dispensing of hot water to avoid spillage of very hot water. This support may be  
provided by a table or counter top, or use B.O.M. part #12599.0000 Shelf Kit  
10420 072500  
5
TROUBLESHOOTING  
A troubleshooting guide is provided to suggest probable causes and remedies for the most likely problems  
encountered. If the problem remains after exhausting the troubleshooting steps, contact the Bunn-O-Matic Tech-  
nical Service Department.  
Inspection, testing, and repair of electrical equipment should be performed only by qualified service person-  
nel.  
All electronic components have 120 240 volt ac and low voltage dc potential on their terminals. Shorting of  
terminals or the application of external voltages may result in board failure.  
Intermittent operation of electronic circuit boards is unlikely. Board failure will normally be permanent. If an  
intermittent condition is encountered, the cause will likely be a switch contact or a loose connection at a  
terminal or crimp.  
Solenoid removal requires interrupting the water supply to the valve. Damage may result if solenoids are  
energized for more than ten minutes without a supply of water.  
The use of two wrenches is recommended whenever plumbing fittings are tightened or loosened. This will  
help to avoid twists and kinks in the tubing.  
Make certain that all plumbing connections are sealed and electrical connections tight and isolated.  
This dispenser is heated at all times. Keep away from combustibles.  
WARNING  
Exercise extreme caution when servicing electrical equipment.  
Disconnect the dispenser from the power source when servicing, except when electrical tests are speci-  
fied.  
Follow recommended service procedures  
Replace all protective shields or safety notices  
Problem  
Probable Cause  
Remedy  
Equipment will not operate.  
1. No power or incorrect voltage (A) Check the terminal block for the cor-  
rect voltage. It should be:  
a.) 100 to 120 volts ac across the black and  
white terminals for 100 to 120 volt models  
or,  
b.) 200 to 240 volts ac across the red and  
black terminals for 200 to 240 volt models.  
(B) Check circuit breakers or fuses.  
2. Safety overflow switch  
Refer to Service safety overflow switch  
for testing procedures. See page 17.  
10420 011599  
6
TROUBLESHOOTING (cont.)  
Problem  
Probable Cause  
Remedy  
Automatic refill will not operate 1. No water  
after drawing hot water.  
Check plumbing and shut-off valves.  
2. Water strainer/flow control  
(A) Direction of flow arrow must be point-  
ing towards dispenser.  
(B) Remove the strainer/flow control and  
check for obstructions. Clear or replace.  
3. Safety overflow switch  
4. Liquid level system  
5. Solenoid valve  
Refer to Service safety overflow switch  
for testing procedures. See page 17.  
Refer to Service electronic controls for  
testing procedures. See page 10.  
Refer to Service solenoid valve for test-  
ing procedures. See page 18.  
Water flows into the tank con- 1. Solenoid valve  
tinuously (Dispenser discon-  
nected from power source).  
Refer to Service solenoid valve for test-  
ing procedures. See page 18.  
Water flows into the tank con- 1. Liquid level system  
tinuously (Dispenser connected  
Refer to Service electronic controls for  
testing procedures. See page 10.  
to power source).  
Water is cold.  
1. Tank heater switch  
2. Safety overflow switch  
3. Limit thermostat  
Tank heater switch must be in the ON”  
position.  
Refer to Service safety overflow switch  
for testing procedures. See page 17.  
Refer to Service limit thermostat for test-  
ing procedures. See page 16.  
CAUTION Do not eliminate or bypass limit thermostat. Use only B.O.M. replacement part #23717.0001.  
4. Tank heater  
Refer to Service tank heater for testing  
procedures. See page 19.  
5. Temperature control  
Refer to Service electronic controls for  
testing procedures. See page 10.  
10420 011599  
7
TROUBLESHOOTING (cont.)  
Problem  
Probable Cause  
Remedy  
Water boils continuously.  
1. Temperature control  
Refer to Service electronic controls for  
testing procedures. See page 10.  
2. Lime build-up  
Inspect the tank assembliy for excess lime  
deposits. Delime as required.  
CAUTION – Tanks and tank components should be delimed reglarly depending on local water conditions. Exces-  
sive mineral build-up on stainless steel surfaces can initiate corrosive reactions resulting in serious leaks.  
Dispenser is making unusual  
noises.  
1. Solenoid valve  
2. Plumbing lines  
3. Water supply  
The nut on top of the solenoid valve must  
be tight or it will vibrate during operation.  
Plumbing lines should not be resting on the  
counter top.  
(A) The dispenser must be connected to a  
cold water line.  
(B) Water pressure to the dispenser must  
not be higher than 90 psi (620 kPa). Install  
a regulator if necessary to lower the work-  
ing pressure to approximately 50 psi (345  
kPa).  
Ready indicator will not light.  
(when temperature is within 4°  
of its selected setting.)  
1. Temperature control  
2. Ready Indicator LED  
Refer to Service electronic controls for  
testing procedures. See page 10.  
Replace the indicator LED.  
10420 072500  
8
SERVICE  
This section provides procedures for testing and  
r
i  
l
l  
i
i
I
i
l
il  
ll  
T
t
l
l
i
V
I
i  
t
r
replacing various major components used in this dis-  
penser should service become necessary. Refer to  
Troubleshooting for assistance in determining the cause  
of any problem.  
F
! W  
ill  
e
w
rm  
th  
to  
U
a
A
te  
s
r
t
RNING  
o
a
n
k
p
ta  
o
b
c
w
t
o
e
s
e
r
fo  
e
r
re  
o
s
o
p
lly  
o
n
a
o
c
n
nn  
t
i
rc  
le  
l
u
u
y
rc  
e
rn  
g
u
e
c
in  
a
it  
.
tin  
E
g
ca  
a
a
b
-
lia  
o
c
p
n
tr  
ro  
p
F
ic  
l
p
p
o
e
er  
e
th  
l
l
o
l
n
o
f
y
c
e
w
g
t
p
r
D
r
h
o
n
o
o
te  
a
u
r
n
tio  
n
a
o
d
t
c
te  
t
n
e
u
a
d
d
F
s
l
e
l
s
A
e
/l  
r
o
a
IL  
n
o
c
c
h
U
A
e
a
a
d
.
R
M
a
l
E
A
e
s
is  
D
c
le  
T
G
o
c
.
O
m
t
C
F
b
ri  
ca  
O
IR  
u
s
R
IN  
E
M
E
ti  
l
E
C
,
P
b
c
o
A
L
le  
d
e
D
Y
R
s
L
T
R
S
.
s
.
IA  
H
,
B
L
E
O
IS  
H
IL  
U
B
K
O
IT  
D
E
T
N
S
C
Y
IN  
T
E
E
Q
G
IR  
E
E
IM  
IN  
U
A
F
H
O
O
K
IP  
M
T
R
L
P
E
R
O
H
E
H
IS  
E
N
R
B
IT  
G
A
Z
A
U
T
A
T
P
Y
IN  
C
P
F
G
D
O
00  
L
IA  
W
N
83  
1.  
00  
O
A
M
A
N
N
N
E
R
IN  
E
00A  
C
R
R
G
C
E
U
A
U
A
T
IS  
S
N
L
D
H
T
Y
T
E
P
A
A
P
5/  
O
T
88  
T
H
N
©
A
E
IS  
D
O
19  
D
88  
O
W
H
BU  
W
R
NN  
-O  
E
E
D
U
R
N
-M  
S
E
C
AT  
IC  
O
V
E
R
T
CO  
RP  
OR  
AT  
IO  
U
R
C
N
E
T
m
c
h
is  
p
o
e
q
w
ly  
u
ip  
A
a
f
th  
ith  
m
e
d
m
d
e
e
th  
ild  
n
t
B
is  
to  
ic  
in  
n
is  
u
e
B
O
te  
o
th th tra  
e
in  
a
b
to  
g
s
e
m
a
F
d
r
P
i
s
In  
n
b
Fo  
o
f
f
i
c
l
u
s
t
a
o
o
d
ia  
ll  
S
D
r
n
a
l
s
e
d
e
at  
in  
n
r
g
to  
d
v
i
i
o
n
d
C
ce  
n
r
S
d
a
C
o
e
d
u
l
g
a
m
,
I
n
o
e
A
n
in  
d
o
f
i
t
a
c
.
ti (B  
O
CA  
o
is  
n
tio  
M
tra  
an  
)
l
u
D
n
a
(F  
A
)
.
Component Access  
WARNING – Disconnect the dispenser from the power  
source before the removal of any panel or the replace-  
ment of any component.  
P1770  
The limit thermostat, liquid level probe, tank heater,  
and temperature sensor are located at the top of the  
dispenser. Access is gained by removing the top lid,  
attached with three 4-40 slotted-head screws.  
!
T
R
N
E
N
O
E
C
L
E
O
R
N
P
U
A
M
O
P
O
S
C
Y
R
N
Y
N
F
E
A
O
W
A
O
F
A
P
L
O
O
C
M
T
V
N
O
E
R
R
M
M
F
E
E
T
C
A
E
E
L
P
W A R N I N  
N
N G R  
O
E
R
O
F
E
B
!
C
S
I
D
i
N  
r
r  
t
l
i
The triac assembly is located beneath the tank. Access  
is gained by removing four feet and the bottom panel  
attached with seven 8-32 slotted-head screws.  
il il
i
rs  
T
i
i
t
il  
I
l
i
i
t
F
il  
e
l
! W  
w
rm  
th  
to  
U
a
A
te  
s
r
R
N
ta  
o
n
p
e
c
ta  
k
ING  
o
b
c
w
t
e
s
e
o
r
fo  
r
re  
o
s
o
p
lly  
o
n
a
o
c
n
n
tu  
n
ir  
ly  
u
n
rc  
e
rn  
g
u
e
p
c
in  
g
it  
.
ti  
E
le  
c
a
a
-o  
li  
c
a
p
p
n
a
n
tr  
ro  
F
ic  
b
l
p
o
a
e
er  
e
l
l
o
l
o
f
y
r
a
e
c
e
w
g
t
p
D
r
h
r
e
o
n
ou  
o
a
te  
n
t
n
o
io  
d
t
c
c
t
n
t
te  
a
u
a
h
d
d
d
.
F
s
l
l
A
e
/l  
r
o
IL  
D
n
o
c
c
h
U
e
a
a
R
a
l
s
E
A
e
s
is  
.
le  
u
A
T
G
o
c
M
O
m
t
b
ri  
C
ca  
O
s
R
IN  
E
M
E
ti  
l
E
C
,
P
b
c
o
A
F
L
le  
d
e
D
IR  
Y
R
s
L
T
.
s
.
IA  
H
,
R
S
B
L
E
O
IS  
H
IL  
U
B
K
O
IT  
D
E
N
S
C
Y
IN  
T
E
E
Q
H
G
IR  
L
E
T
E
E
IM  
IN  
U
A
F
H
O
IP  
M
O
K
T
R
P
E
H
IS  
R
F
E
N
R
B
IT  
G
A
Z
A
U
T
A
T
P
Y
O
IN  
C
P
G
D
O
L
IA  
W
N
O
A
M
A
N
N
00  
N
R
IN  
00  
E
00  
C
D
R
R
G
83  
C
A
E
U
A
U
A
1.  
T
IS  
S
N
T
Y
E
L
H
T
1
E
P
A
A
P
5
/8  
O
T
H
8
T
O
N
©
A
E
D
IS  
D
O
98  
8
W
R
B
UN  
W
H
N-  
E
R
E
N
D
U
O-  
M
S
E
C
T
AT  
O
V
E
R
IC  
U
C
OR  
R
PO  
C
E
RA  
TI  
ON  
NOTE - Completely drain the tank before tipping the  
dispenser.  
T
c
h
is  
p
o
m
e
w
q
u
ly  
ip  
m
e
A
a
f
th  
it  
th  
e
il  
d
d
n
h
u
m
e
n
in  
th  
B
t
a
is  
is  
o
d
tr  
B
to  
P
a
o
in  
th  
to  
g
s
b
e
ic  
ic  
e
e
r
O
F
s
in  
b
F
o
o
In ff  
e
lu  
s
o
d
te  
m
a
ta  
ll  
e
in  
d
ia  
o
S
d
S
r
ls  
a
n
d
n
r
u
a
g
d
v
ti  
n
to  
ic  
d
In  
C
o
D
n
e
a
r
C
d
e
l,  
o
d
e
g
a
A
n
it  
in  
o
f
c
a
is  
.
m
(
ti  
B
o
n
O
a
(
M
o
C
A
tr  
a
ti  
n
F
)
l
A
u
a
n
D
)
.
WARNING – Inspection, testing, and repair of electrical  
equipment should be performed only by qualified ser-  
vice personnel. Disconnect the dispenser from the  
P1770  
The check valve, electronic control assembly, safety power source when servicing, except when electrical  
overflow switch, solenoid valve, overflow tube tem- tests are required and the test procedure specifically  
perature sensor and terminal block are located at the states to connect the dispenser to the power source.  
rear of the dispenser. Access is gained by removing  
the upper and lower rear panels. The upper is attached Electronic Controls ............................................. 10  
with six 8-32 slotted-head screws. The lower is attached Limit Thermostat ................................................ 16  
with four 8-32 slotted-head screws. The middle panel Safety Overflow Switch....................................... 17  
must not be removed from the dispenser.  
Solenoid Valve .................................................... 18  
Tank Heater ........................................................ 19  
Electronic Control Assembly Troubleshooting:  
Check these items first  
Is circuit board popped-out of bracket?  
Is circuit board wet due to misaligned overflow  
tube?  
!
R
T
N
E
N
E
O
C
L
E
O
R
N
P
U
A
M
O
P
O
S
C
Y
R
N
Y
N
E
A
W
F
A
O
O
F
P
L
O
M
A
T
V
T
N
O
E
R
R
O
C
F
M
M
E
E
C
A
E
E
L
P
W A R N I N  
N
N G R  
O
E
R
O
F
E
B
!
C
S
I
D
Is water in overflow cup activating float switch?  
Isoverflowcupnotmakinggoodcontactwithtank?  
Is dispenser being operated with panels removed?  
r
il
y
e
i
I
iil
illl  
ll
i
V
t
i
r
P1770  
10420 011599  
9
SERVICE (cont.)  
Electronic Controls  
D
Un  
!
O
O
NO  
ON  
O
CAUTIO
IC  
P
O
T
T
T
til  
W
Tu  
O
N
S  
a
rn  
D
ter  
O
nem  
mes Fhero  
A
Hot Water  
C
S
o
yst  
Ts  
E
R
Automatically When Unit Is Connected To P
m
Tank  
Coffee Brewers  
Accordance With The Installation Instructions!  
H
Openeater  
S
Water Tank Will Fill  
ed Fa  
F
w
itch  
a
il  
Fill The Water Tank  
I
u
uce  
t!  
r
e
T
o
C
o
m
p
ly  
V
o
n
id  
s
W
ar  
r
a
n
t
y
!
W
A
R
N
I
N
G
H
A
Z
A
L
V
R
D
T
O
O
G
U
A
S
D
E
IS  
C
O
P
N
N
O
B
W
E
E
C
R
R
F
E
O
T
U
O
R
S
O
F
E
R
O
R
M
E
M
C
E
V
IN  
G
!
12561.0000  
M2522.1000  
12565.0002  
01520.0000  
P1772  
00971.0000  
FIG. 1 ELECTRONIC CONTROL  
02328.0003  
P1773  
FIG. 2 TRIAC  
Location:  
The electronic control assembly is located inside the rear of the dispenser. Access will also be needed to the  
temperature sensor, overflow tube temperature sensor, and liquid level probe located on the tank lid and to the  
triac assembly located beneath the tank.  
General:  
H5E, H5X LIQUID LEVEL CONTROL  
This system controls the liquid level and water tem-  
perature of the dispenser. These two functions act in-  
PROBLEM: Overflows  
dependently of each other and should be tested sepa-  
Drain cup  
rately.  
Unplug Ready Lamp  
Retry  
Liquid Level Control Flow Charts  
No  
Overflow  
Replace Ready Lamp  
?
Yes  
H5E, H5X LIQUID LEVEL CONTROL  
Drain cup  
PROBLEM: Does Not Refill  
Disconnect Probe  
Wire From Probe  
Short Probe Wire  
To Chassis  
Yes  
Overflow Cup Full  
?
Remove Power  
Retry  
Drain cup  
Retry  
No  
Disconnect Level Probe  
No  
Overflow  
?
Replace Probe  
Yes  
Yes  
Yes  
Voltage present at  
Solenoid Valve  
?
Does Water Flow  
?
Replace Probe  
Drain cup  
Disconnect Wire From  
Solenoid Valve  
No  
No  
Retry  
Unplug Ready Lamp  
Replace Solenoid Valve  
Yes  
Overflow  
?
Replace Solenoid Valve  
Yes  
Voltage present at  
Solenoid Valve  
?
Replace Ready Lamp  
No  
No  
Replace Control Assembly  
Replace Control Assembly  
10420 011599  
10  
SERVICE (cont.)  
tronic control assembly.  
5. Check the voltage across terminals 1 & 4 of the  
electronic control assembly with a voltmeter. Con-  
nect the dispenser to the power source. The indi-  
cation must be:  
a.) 100 to 120 volts ac for 100 to 120 voltmodels  
or  
b.) 200 to 240 volts ac for 200 to 240 volt models  
after a delay of approximately 5 seconds.  
6. Disconnect the dispenser from the power source.  
Electronic Controls (cont.)  
Liquid Level Control Test Procedure  
1. Disconnect the dispenser from the power source.  
2. Check the voltage across terminals 3 & 4 of the  
electronic control assembly with a voltmeter. Con-  
nect the dispenser to the power source. The indi-  
cation must be:  
a.) 100 to 120 volts ac for 100 to 120 volt models  
or  
If voltage was present as described, the liquid level  
control of the system is operating properly, proceed to  
#7.  
If voltage was not present as described, replace the  
electronic control assembly and the temperature sen-  
sor in the tank lid.  
b.) 200 to 240 volts ac for 200 to 240 volt models.  
3. Disconnect the dispenser from the power source.  
If voltage was present as described, proceed to #4.  
If voltage was not present as described, refer to  
the Wiring Diagrams and check the dispenser wir-  
ing harness.  
4. Remove the pink wire from terminal 5 of the elec-  
NOTE - Each electronic control assembly is calibrated  
to a temperature sensor. Both components MUST be  
replaced as a set.  
Temperature Control Flow Charts  
H5X THERMOSTAT  
H5E THERMOSTAT  
PROBLEM:Water Not Hot Enough  
PROBLEM:Water Not Hot Enough  
Jumper JP1  
No  
Reposition Jumper  
In Boil Position  
?
Turn Temperature  
Adjustment Screw  
Clockwise Contiuously  
No  
Red Light On  
Constantly  
?
Yes  
Yes  
Red Light On  
?
Yes  
Measure Voltage  
At Tank Heater  
No  
Adjust For Correct  
Water Temperature  
Red Light On  
Constantly  
?
Replace Steam Sensor  
No  
Yes  
Replace Control Assembly  
Replace Tank Heater  
Red Light On  
Constantly  
?
Yes  
Yes  
Voltage Present  
?
Measure Voltage  
At Tank Heater  
Recheck Water Temperature  
No  
No  
Replace Control Assembly  
Replace Tank Heater  
Yes  
Voltage Present  
?
No  
Replace Limit Thermostat  
Limit Thermostat OK  
?
No  
Yes  
No  
Replace Control Assembly  
Replace Limit Thermostat  
Limit Thermostat OK  
?
Measure Voltage  
At Tank Heater  
Yes  
Replace Triac  
Replace Control Assembly  
No  
Measure Voltage  
At Tank Heater  
Voltage Present  
?
Check For Split Tank Heater  
Reinstall Original  
Control Assembly  
Yes  
Replace Triac  
No  
Recheck Water Temperature  
Voltage Present  
?
Check For Split Tank Heater  
Reinstall Original  
Control Assembly  
Yes  
Recheck Water Temperature  
10420 011599  
11  
SERVICE (cont.)  
If voltage was present as described, reinstall the probe,  
the sensing function of the system is operating prop-  
erly.  
If voltage was not present as described, check the pink  
probe wire and the green ground wire for continuity  
and/or replace the probe.  
Electronic Controls (cont.)  
7. Reconnect the pink wire to terminal 5 of the elec-  
tronic control assembly.  
8. Loosen the compression fitting, remove the probe  
from the tank lid, and inspect it for mineral depos-  
its. Replace it if necessary. Keep the exposed ends  
of the probe away from any metal surface of the  
dispenser.  
9. Check the voltage across terminals 1 & 4 of the  
electronic control assembly with a voltmeter. Con-  
nect the dispenser to the power source. The indi-  
cation must be:  
Temperature Control Test Procedure  
1. Disconnect the dispenser from the power source.  
2. Check the voltage across terminals 3 & 4 of the  
electronic control circuit board with a voltmeter.  
Connect the dispenser to the power source.The in-  
dication must be:  
a.) 100 to 120 volts ac for 100 to 120 volt models  
or  
b.) 200 to 240 volts ac for 200 to 240 volt models.  
3. Disconnect the dispenser from the power source.  
a.) 100 to 120 volts ac for 100 to 120 volt models  
or  
b.) 200 to 240 volts ac for 200 to 240 volt models  
after a delay of approximately 5 seconds.  
10. Touch the screw head end of the probe to the dis-  
penser housing. The indication must be 0.  
11. Move the probe away from the dispenser housing.  
The indication must again be:  
a.) 100 to 120 volts ac for 100 to 120 volt models  
or  
b.) 200 to 240 volts ac for 200 to 240 volt models  
after a delay of approximately 5 seconds.  
12. Disconnect the dispenser from the power source.  
If voltage was present as described, proceed to #4.  
If voltage was not present as described, refer to the  
Wiring Diagram and check the dispenser wiring har-  
ness.  
4. Connect the dispenser to the power source and  
place the tank heater switch in the ONposition.  
5. Observe the red indicator on the electronic control  
circuit board.  
6. Disconnect the dispenser from the power source.  
Temperature Control Flow Charts (cont.)  
H5X THERMOSTAT  
H5E THERMOSTAT  
PROBLEM: Boils  
PROBLEM: Boils Excessively - Fills Cup  
Drain cup  
Retry  
Drain cup  
Retry  
Yes  
Red Light On While  
Replace Steam Sensor  
Boiling  
?
Yes  
Red Light On While  
Replace Control Assembly  
Boiling  
?
No  
No  
Yes  
Disconnect Blue Wire From  
Control Board Pin 7  
Still Boiling  
?
Replace Control Assembly  
Disconnect Blue Wire From  
Control Board Pin 7  
Retry  
Retry  
No  
Finished  
Yes  
Still Boiling  
?
Replace Triac Assembly  
Yes  
Still Boiling  
?
Replace Triac Assembly  
Check For Split  
Tank Heater  
No  
Check For Split  
Tank Heater  
No  
Replace Control Assembly  
Replace Control Assembly  
10420 011599  
12  
SERVICE (cont.)  
Electronic Controls (cont.)  
to a temperature sensor. Both components MUST be  
replaced as a set.  
If the indicator was on or blinking, the temperature sen-  
sor is operating properly, proceed to #7.  
If the indicator was off, check the sensor connection  
on the electronic control circuit board and/or replace  
the temperature sensor and the electronic control as-  
sembly.  
10. Check the voltage across the tank heater terminals  
with a voltmeter. Connect the dispenser to the  
power source. The indication must be:  
a.) 100 to 120 volts ac for 100 to 120 volt models  
or  
b.) 200 to 240 volts ac for 200 to 240 volt models  
while the red indicator on the circuit board is on or  
blinking.  
NOTE - Each temperature sensor is calibrated to an  
electronic control assembly. Both components MUST  
be replaced as a set.  
11. Disconnect the dispenser from the power source.  
If voltage was present as described, return the new  
triac assembly to Bunn-O-Matic for credit. The tem-  
perature control of the system is operating properly.  
If voltage was not present as described, reinstall your  
existing electronic control assembly and temperature  
sensor, and proceed to #12.  
7. Check the voltage across the tank heater terminals  
with a voltmeter. Connect the dispenser to the  
power source. The indication must be:  
a.) 100 to 120 volts ac for 100 to 120 volt models  
or  
b.) 200 to 240 volts ac for 200 to 240 volt models  
while the red indicator on the circuit board is on or  
blinking.  
12. Replace the triac assembly.  
13. Check the voltage across the tank heater terminals  
with a voltmeter. Connect the dispenser to the  
power source. The indication must be:  
a.) 100 to 120 volts ac for 100 to 120 volt models  
or  
8. Disconnect the dispenser from the power source.  
If voltage was present as described, the temperature  
control of the system is operating properly.  
If voltage was not present as described, contact Bunn-  
O-Matic to order an electronic control assembly, tem-  
perature sensor, and triac assembly for evaluation and  
proceed to #9.  
b.) 200 to 240 volts ac for 200 to 240 volt models  
while the red indicator on the circuit board is on or  
blinking.  
14. Disconnect the dispenser from the power source.  
9. Replace the electronic control assembly and tem-  
perature sensor.  
If voltage was present as described, the temperature  
control of the system is operating properly. Return the  
new electronic control assembly and temperature sen-  
sor to Bunn-O-Matic for credit.  
NOTE - Each electronic control assembly is calibrated  
10420 011599  
13  
SERVICE (cont.)  
8. Reconnect the wires.  
Electronic Controls (cont.)  
9. Review the initial set-up procedures.  
Electronic Controls Removal and Replacement  
Triac Assembly Removal and Replacement  
NOTE - Each electronic control assembly is calibrated  
toatemperaturesensorprobe.BothcomponentsMUST  
be replaced as a set.  
NOTE - Each triac installation requires the use of an  
approved silicone heat sink compound. Bunn-O-Matic  
recommendstheuseofDowCorning340compoundor  
equivalent. It can be purchased direct from Bunn-O-  
Matic (part # 12572.0002).  
1. Remove all wires from the electronic control as-  
sembly terminals.  
2. Remove the two 8-32 screws holding the electronic  
control assembly to the component bracket.  
3. Disconnect the temperature sensor, overflow tube  
temperature sensor, and indicator wires from the  
left side of the electronic control assembly board.  
4. Remove the temperature sensor from the grom-  
met in the tank lid.  
5. Install the new temperature sensor into the grom-  
met on the tank lid. Route the wires to the location  
of the new electronic control assembly.  
6. Attach the temperature sensor, overflow tube tem-  
perature sensor, and indicator wires to the elec-  
tronic control assembly.  
1. Place the tank heater switch on the electronic con-  
trol assembly in the OFFposition.  
2. Completely drain the tank.  
3. Carefully set the dispenser on its face (faucet side).  
4. Remove the four feet attached with four 8-32  
phillips-head screws.  
5. Remove the bottom panel and four feet attached  
with seven 8-32 slotted-head screws.  
6. Remove the existing triac assembly held in place  
with a 10-32 hex keps nut.  
7. Apply a small amount of the silicone heat sink com-  
pound to the copper heat sink.  
8. Securely fasten the new triac assembly to the bot-  
tom of the tank in the same relative position as the  
one removed. Bunn-O-Matic recommends tighten-  
ing the nut to a torque setting of approximately 18  
inch-pounds.  
7. Fasten the new electronic control assembly to its  
bracket.  
BLU to Triac Assy  
WHI/BRN to Tank Heater Switch  
9. Route the wires up around the rear of the dispenser.  
10. Reinstall the bottom panel and four feet.  
11. Stand the dispenser upright.  
12. Disconnect the other ends of the old triac assem-  
bly wires.  
13. Connect the TAN and BLU wires with spade termi-  
nals of the new assembly to the electronic control  
assembly, FIG. 3.  
14. Connect the BLU wire with the ring terminal to the  
tank heater, FIG. 13.  
TAN to Triac Assy  
PNK to Liquid Level Probe  
WHI or RED to Terminal Block  
BLK to Overflow Safety Switch  
GRN to Chassis Ground  
WHI/BLU to Solenoid  
P1774  
FIG. 3 WIRING CONNECTIONS  
WHI & WHI to  
Temperature Sensor  
15. Connect the WHI/VIO wire of the new assembly to  
the WHI or RED terminal at the terminal block.  
PNK & GRY to  
Heater Indicator  
Refill Indicator  
Power Indicator  
Ready Indicator  
GRY & GRY  
toThermistor  
P1774  
FIG. 4 WIRING CONNECTIONS  
10420 011599  
14  
SERVICE (cont.)  
4. Take the temperature of the stream of water imme-  
diately below the faucet as it flows from the dis-  
penser with an accurate thermometer. Do not take  
the temperature of water collected in a container.  
Electronic Controls (cont.)  
Adjustments  
5A. TO INCREASE THE TEMPERATURE  
This dispenser can maintain any temperature between  
85 and 208°F by selecting and setting one of five vari-  
able range control potentiometers.  
Turn the potentiometer screw of the temperature  
range selected in step 2 in a clockwise direction  
with a small screwdriver. One full turn of the screw  
will result in an approximate 1°F change. Allow  
the temperature to stabilize as described in step 3  
and repeat step 4. Continue until the desired water  
temperature is achieved.  
1. Fill the dispenser according to the steps in the Ini-  
tial Set-up.  
2. Select the range containing the desired tempera-  
ture by plugging the two-pin socket onto the mat- 5B. TO DECREASE THE TEMPERATURE  
ing connector of one of the range control boards.  
Both pins must be connected to the socket.  
Turn the potentiometer screw of the temperature  
range selected in step 2 in a counterclockwise di-  
rection with a small screwdriver. One full turn of  
the screw will result in an approximate 1°F change.  
Draw a large quantity of water at the faucet, allow  
the temperature to stabilize as described in step 3  
and repeat step 4. Continue until the desired water  
temperature is achieved.  
3. Place the tank heater switch in the ONposition  
and observe the glowing red indicator near the right  
edge of the control board. The controller is apply-  
ing full power to the heater when the indicator is  
on all the time. The indicator will begin to flash as  
the temperature nears the set point. The set tem-  
perature is reached when the indicator flashes only NOTE - The entire adjustment span is approximately  
very briefly. The water is hotter than the set tem- 25 complete revolutions. The potentiometer will cease  
perature when the indicator remains off. This ini- to adjust when turned too far in either direction. It is  
tial setting will only be an approximation.  
not damaged, simply turn it back a few turns and try  
again.  
85-115°  
110-140° 135-165° 160-190° 185-208°  
P1775  
FIG. 5 TEMPERATURE RANGE SELECTION  
10420 011599  
15  
SERVICE (cont.)  
Limit Thermostat  
Location:  
If voltage was present as described, reconnect the black  
wire and proceed to #5.  
The limit thermostat is located on the tank lid.  
To test the limit thermostat, access will also be needed  
to the terminal block located at the rear of the dispenser.  
If voltage was not present as described, refer to the  
Wiring Diagrams and check the dispenser wiring har-  
ness.  
5. Check for continuity across the terminals of the  
limit thermostat.  
If continuity is not present as described, the circuit is  
broken. Press the reset button of the limit thermostat  
and recheck for continuity.  
If continuity is not present as described, replace the  
limit thermostat.  
P1772  
FIG. 6 LIMIT THERMOSTAT  
Removal and Replacement:  
1. Remove both wires from the limit thermostat ter-  
minals.  
2. Remove the two #10-32 nuts attaching the limit  
thermostat to the top of the tank.  
3. Install the new limit thermostat and secure into  
place with two #10-32 nuts.  
Test Procedure:  
1. Disconnect the dispenser from the power source.  
2. There are two black wires on the limit thermostat  
terminals. One comes from the terminal block. The  
other goes directly to the tank heater terminal.  
Remove the black wire at the limit thermostat com-  
ing from the terminal block.  
3. Check the voltage across the black wire removed  
from the limit thermostat and the white wire or red  
wire of the terminal block with a voltmeter. Con-  
nect the dispenser to the power source. The indi-  
cation must be:  
4. Refer to FIG. 7 when reconnecting the wires.  
Reset  
BLK to Terminal Block  
a.) 100 to 120 volts ac for 100 to 120 volt models  
or  
BLK to Tank Heater  
b.) 200 to 240 volts ac for 200 to 240 volt models.  
4. Disconnect the dispenser from the power source.  
P1776  
FIG. 7 LIMIT THERMOSTAT WIRING  
10420 011599  
16  
SERVICE (cont.)  
Removal and Replacement:  
1. Disconnect the black wires from the safety over-  
flow switch.  
Safety Overflow Switch  
2. Remove the nut beneath the copper overflow cup.  
3. Remove the entire switch assembly from the cup.  
4. Place the new switch assembly into the cup, wires  
first. Make sure that a gasket is in place around the  
threaded switch stem.  
NOTE - The magnets must be at the top of the float and  
there must be NO stainless steel washers installed for  
the safety overflow switch to operate properly.  
DO NOT  
!
O
ON  
O
CA  
I
Until Water Comes From Ope
Turn On The Tank Hei
UTION  
T
O
STOP  
N
D
A
H
E
ot  
W
R
A
uto  
ate  
m
C
a
r
S
ys  
tic  
a
e
lly  
B
o
te  
m
ffe  
W
A
c
h
s
co  
e
n
U
W
rd  
r
ew  
W
an  
nit  
e
rs  
ith  
I
ater  
T
Failure To Comply Voids Warranty!  
ce  
s
ill  
C
h
ank  
F
onn  
T
W
T
e
he  
c
t
e
d
i
l
l
F
e
Ins  
W
a
ill  
Po  
To  
an  
ta  
ter  
llation  
T
w
er!  
In  
k
In  
struct  
io  
ns  
!
P1772  
5. Install the nut beneath the copper overflow cup.  
Be sure not to overtighten.  
6. Reconnect the wires, FIG. 9.  
FIG. 8 SAFETY OVERFLOW SWITCH  
Location:  
The safety overflow switch is located inside the rear of  
the dispenser inside the copper overflow cup.  
For testing or removal of the safety overflow switch,  
access may also be needed by removing the two screws  
attaching the electronic control assembly to its mount-  
ing bracket.  
RED to BLK Wire from  
Terminal Block  
Test Procedure:  
1. Once voltage is verified at the power source, check  
for continuity across the safety overflow switch  
red wires only until the plastic float is raised and  
check that continuity returns when the plastic float  
is again lowered.  
RED to BLK Wire from  
Electronic Control #3  
P1777  
FIG. 9 SAFETY OVERFLOW WIRING  
If continuity is present as described, reconnect each  
of the red wires to the black wires, the safety overflow  
switch is operating properly.  
If continuity is not present as described, replace the  
safety overflow switch.  
10420 011599  
17  
SERVICE (cont.)  
7. Check the solenoid valve for coil action. Connect  
the dispenser to the power source. Listen carefully  
in the vicinity of the solenoid valve for a clicking”  
sound after approximately 5 seconds, as the coil  
magnet attracts the plunger.  
Solenoid Valve  
Location:  
The solenoid valve is located inside the rear of the dis-  
penser on the right side near the bottom.  
To test the solenoid valve, access will also be needed 9. Reconnect the pink wire to terminal 5 of the elec-  
to the electronic control assembly.  
8. Disconnect the dispenser from the power source.  
tronic control assembly.  
If the sound was heard as described and water will not  
pass through the solenoid valve, there may be a block-  
age in the water line before or after the solenoid valve  
or the solenoid valve may require inspection for wear  
and removal of waterborne particles.  
F
il  
e
l
! W  
w
rm  
th  
to  
U
a
A
te  
s
r
RNING  
ta  
ta  
t
o
n
p
e
c
k
o
b
c
w
e
s
ir  
le  
e
o
r
fo  
r
re  
o
s
o
p
lly  
o
n
a
o
c
n
n
tu  
ti  
ly  
u
rc  
n
rn  
g
e
u
e
p
c
in  
g
-o  
it  
.
E
n
c
a
a
c
a
p
p
n
tr  
ro  
F
ic  
b
l
p
l
o
a
e
er  
e
i
a
l
l
o
l
n
c
o
f
y
r
a
e
w
g
t
p
e
D
r
h
r
e
o
n
ou  
o
a
te  
n
t
n
o
io  
d
t
c
c
t
n
t
te  
d
d
u
a
h
d
F
s
l
l
A
e
/l  
r
o
IL  
D
n
o
c
c
h
a
U
e
a
a
.
R
a
l
s
E
A
e
s
is  
le  
A
T
G
o
c
.
M
O
m
t
b
ri  
C
ca  
le  
O
u
s
R
E
M
E
ti  
l
E
,
P
b
c
o
A
F
L
d
e
IN  
D
T
IR  
Y
R
s
L
.
s
.
IA  
C
H
R
S
,
IS  
H
B
L
E
O
IL  
U
B
K
IT  
D
E
N
S
C
Y
IN  
T
E
E
Q
H
G
IR  
L
E
T
E
IM  
IN  
O
A
U
A
F
H
O
IP  
M
O
K
T
R
P
E
O
H
E
IS  
R
E
N
R
B
IT  
G
Z
A
U
T
A
T
P
Y
IN  
C
P
F
R
G
D
O
L
IA  
W
M
N
O
A
N
N
R
A
00  
E
C
D
R
G
N
U
83  
C
E
U
A
1.0  
T
IS  
S
N
T
Y
A
L
00  
E
IN  
0A  
H
5
T
1
E
P
A
T
A
P
/8  
O
N
8
A
T
H
©
E
D
IS  
D
O
98  
8
O
W
H
R
B
UN  
W
N-  
E
R
C
E
N
D
U
O-  
M
S
OR  
E
C
T
ATI  
O
PO  
V
E
R
C
U
R
TI  
C
RA  
E
ON  
If the sound was not heard as described, replace the  
solenoid valve.  
Removal and Replacement:  
P1778  
1. Remove all wires from the solenoid valve coil.  
2. Turn-off the water supply to the dispenser.  
3. Disconnect the water lines to and from the sole-  
noid valve.  
FIG. 10 SOLENOID VALVE  
Test Procedure:  
1. Disconnect the dispenser from the power source  
and turn-off the water supply to the dispenser.  
2. Remove the pink wire from terminal 5 of the elec-  
tronic control assembly.  
4. Remove the two 8-32 slotted-head screws holding  
the solenoid valve and mounting bracket to the  
component bracket.  
5. Lift-out the solenoid valve.  
3. Check the voltage across the solenoid valve coil  
terminals with a voltmeter. Connect the dispenser  
to the power source. The indication must be:  
a.) 100 to 120 volts ac for 100 to 120 volt models  
or  
6. Remove the two 10-32 slotted-head screws hold-  
ing the solenoid valve to its mounting bracket.  
7. Securely install the new solenoid valve to its mount-  
ing bracket. The direction of flow arrow must be  
pointing towards the tank lid.  
b.) 200 to 240 volts ac for 200 to 240 volt models  
after a delay of approximately 5 seconds.  
4. Disconnect the dispenser from the power source.  
8. Attach the solenoid valve and mounting bracket to  
the component bracket.  
9. Securely fasten the water lines to and from the so-  
lenoid valve.  
If voltage was present as described, proceed to #5.  
If voltage was not present as described, refer to the  
Wiring Diagrams and check the dispenser wiring har-  
ness.  
10. Reconnect the wires, FIG. 11.  
WHI/BLU to Electronic Control #1  
WHI or RED to Terminal Block  
5. Remove both wires from the solenoid valve coil  
terminals.  
6. Check for continuity across the solenoid valve coil  
terminals.  
If continuity is present as described, reconnect the  
wires and proceed to #7.  
If continuity is not present as described, replace the  
solenoid valve coil.  
P1779  
FIG. 11 SOLENOID VALVE WIRING  
10420 011599  
18  
SERVICE (cont.)  
Tank Heater  
Location:  
Removal and Replacement:  
The tank heater is located in the tank lid.  
1. Remove the wires to the tank heater.  
2. Remove the 8-32 nuts from the tank heater flange.  
3. Remove the tank heater.  
4. Inspect the tank heater gasket and replace if nec-  
essary.  
5. Securely install the new tank heater. Be certain of a  
watertight seal.  
6. Reconnect the wires, FIG. 13.  
BLU to Triac Assy  
BLK to Limit  
Thermostat  
P1772  
D
!
O
O
ON  
N
til  
H
CAUTIO  
O
O
P
U
T
O
T
T
n
W
T
u
S  
READ  
rn  
NO  
a
O
om  
te  
n
r
e
C
o
T
h
A
t
W
uto  
N
e
a
m
t
e
T
an  
a
r
s
FIG. 12 TANK HEATER  
Test Procedure:  
1. Disconnect the dispenser from the power source.  
2. Check the voltage across the terminals of the tank  
heater with a voltmeter. Connect the dispenser to  
the power source. The indication must be:  
a.) 100 to 120 volts ac for 100 to 120 volt models  
or  
P1780  
FIG. 13 TANK HEATER WIRING  
b.) 200 to 240 volts ac for 200 to 240 volt models.  
3. Disconnect the dispenser from the power source.  
If voltage is present as described, proceed to #4.  
If voltage is not present as described, replace the tank  
heater.  
4. Remove the tank heater from the tank lid and in-  
spect it for cracks in the sheath.  
If the sheath shows no sign of damage, proceed to #5.  
If the sheath is damaged, replace the tank heater.  
5. Check for continuity across the tank heater termi-  
nals.  
If continuity is present as described, reinstall the tank  
heater. The tank heater is operating properly.  
If continuity is not present as described, replace the  
tank heater.  
10420 011599  
19  
WIRING DIAGRAMS  
SCHEMATIC WIRING DIAGRAM H5X  
L1  
N
GRN  
LIMIT  
THERMOSTAT  
TRIAC  
BLK  
BLK  
BLU  
WHI/VIO  
W
H
I
TANK HEATER  
TAN  
W
H
I
t°  
HEATER  
REFILL  
BLU  
7
PNK  
WHI/BRN  
6
G
R
Y
TANK  
HEATER  
SW  
GRY  
PNK  
PNK  
PNK 20  
(PROBE)  
5
ELECTRONIC  
CONTROL  
ASSY  
WHI  
4
PNK  
3
2
1
GRY  
GRY  
WHI/BLU  
GRN  
WHI  
SOL  
POWER  
BLK  
READY  
G
R
Y
G
R
Y
t°  
SAFETY  
SW  
RED  
RED  
BLK  
100-120 VOLTS A C  
2 WIRE  
SINGLE PHASE  
L1  
L2  
GRN/YEL  
LIMIT  
THERMOSTAT  
TRIAC  
WHI/VIO  
BLK  
BLK  
BLU  
TANK HEATER  
TAN  
W
H
I
W
H
I
t°  
REFILL  
HEATER  
BLU  
WHI/BRN  
7
6
PNK  
G
R
Y
TANK  
HEATER  
SW  
GRY  
PNK  
PNK  
PNK 20  
(PROBE)  
5
RED  
RED  
ELECTRONIC  
CONTROL  
ASSY  
4
PNK  
3
2
1
GRY  
GRY  
WHI/BLU  
GRN/YEL  
SOL  
POWER  
READY  
G
R
Y
G
R
Y
t°  
SAFETY  
SW  
BLK  
RED  
RED  
BLK  
200-240 VOLTS A C  
2 WIRE  
SINGLE PHASE  
10420 121598  
20  
WIRING DIAGRAMS  
SCHEMATIC WIRING DIAGRAM H5E  
L1  
N
GRN  
LIMIT  
THERMOSTAT  
TRIAC  
WHI/VIO  
BLK  
BLK  
BLU  
TANK HEATER  
TAN  
W
H
I
W
H
I
t°  
REFILL  
HEATER  
BLU  
WHI/BRN  
7
6
PNK  
G
R
Y
TANK  
HEATER  
SW  
GRY  
PNK  
PNK  
PNK 20  
(PROBE)  
5
4
3
2
1
WHI  
WHI  
PNK  
ELECTRONIC  
CONTROL  
ASSY  
GRY  
GRY  
WHI/BLU  
GRN  
SOL  
POWER  
READY  
SAFETY  
SW  
BLK  
RED  
RED  
BLK  
100-120 VOLTS A C  
2 WIRE  
SINGLE PHASE  
L1  
L2  
GRN/YEL  
LIMIT  
THERMOSTAT  
TRIAC  
WHI/VIO  
BLK  
BLK  
BLU  
TANK HEATER  
TAN  
W
H
I
W
H
t°  
HEATER  
REFILL  
BLU  
WHI/BRN  
7
6
I
PNK  
G
R
Y
TANK  
GRY  
HEATER  
SW  
PNK  
PNK  
PNK 20  
(PROBE)  
5
4
3
2
1
RED  
RED  
PNK  
GRY  
ELECTRONIC  
CONTROL  
ASSY  
GRY  
WHI/BLU  
GRN/YEL  
SOL  
POWER  
BLK  
READY  
SAFETY  
SW  
RED  
BLK  
RED  
200-240 VOLTS A C  
2 WIRE  
1
SINGLE PHASE  
10420 121598  
21  

Nokia 3100 User Manual
Maxtor RPM 4200 User Manual
Kenwood KDC 37MR User Manual
Helio Ocean User Manual
Hamilton Beach CJ 100 User Manual
Fujitsu MAP3147 User Manual
Bunn Coffeemaker CEZF User Manual
Bloomfield 2212 User Manual
Addonics Technologies JUPITER CIPHER EXDRIVE JCEDIS64 User Manual
Addonics Technologies Computer Drive RTM25N335H User Manual