Weil McLain PFG 7 User Manual

Gas-fired  
water boiler  
Series 7  
PFG  
• Installation • Operation  
• Service  
• Parts  
For additional information,  
refer to . . .  
Control Supplement  
Read all instructions before installing  
This manual must only be used by a qualified heating installer/service technician.  
Read all instructions before installing. Perform steps in the order given. Failure  
to comply could result in severe personal injury, death or substantial property  
damage.  
Installer Leave all instructions with boiler for future reference.  
Any claims for damage or shortage in shipment must be filed immediately against  
the transportation company by the consignee.  
Owner  
Installation and service must be performed by qualified contractor.  
Part No. 550-110-641/0605  
PFG SerieS 7 GaS-Fired Water Boiler — Boiler Manual  
Section I: Installation  
Combustion air and ventilation openings  
Select the boiler location  
Combustion air and ventilation openings must comply with Sec-  
tion 5.3, Air for Combustion and Ventilation, of National Fuel  
Gas Code ANSI Zꢀꢀ3.1-latest edition, or applicable local build-  
ing codes. Canadian installations must comply with CAN/CSA  
B149.1 or .ꢀ Installation Codes.  
Consider all connections to boiler before selecting a location.  
Boiler must be installed so gas control system components are pro-  
tected from dripping or spraying water or rain during operation or  
service.  
Non-combustible floor ONLY. See “Boiler foundation, Page 5.  
Provide adequate combustion and ventilation air to:  
To avoid personal injury,death or property damage,  
keep boiler area clear and free from combustible  
materials, gasoline and other flammable vapors  
and liquids.  
Ensure proper combustion  
Reduce risk or severe personal injury or  
death from flue gas spillage and carbon  
monoxide emissions.  
Do not install an exhaust fan in the boiler room.  
Installation clearances  
Boiler installation must ensure sufficient openings in building  
and boiler room to provide adequate combustion air and ventila-  
tion. Consider construction tightness of building when deciding  
whether additional outside openings may be needed.  
Older buildings with single-pane windows, minimal weather-  
stripping and no vapor barrier often provide enough natural  
infiltration and ventilation without dedicated openings.  
Suggested minimum clearances for servicing  
ꢀ4 inches for cleaning and servicing, left side.  
18 inches for access to controls and components, front.  
48 inches from top for cleaning flueways.  
6 inches on remaining sides.  
New construction or remodeled buildings are most often built  
tighter. Windows and doors are weather stripped, vapor barriers  
are used and openings in walls are caulked. As a result, such tight  
construction is unlikely to allow proper natural air infiltration  
and ventilation.  
PFG-5 through PFG-7: Required minimum clearances  
to combustible surface in alcove installations (see  
below)  
PFG 5 thru 7: Top 4ꢀ”  
Rear 5”  
R. Side 5”  
L. Side 5”  
Front: Alcove 18”  
Air from inside building (boiler in interior room):  
PFG-8: Required minimum clearances to combustible  
surfacel in alcove installations  
Tightly constructed buildings must be provided with openings to  
outside for combustion and ventilation air. These openings must be  
sized to handle all fuel burning appliances, exhaust and ventilation  
fans and fireplaces.  
PFG 8: Provide minimum ꢀ4” between jacket and any com-  
bustible wall(s). Provide minimum 48” between jacket top and  
combustible ceiling or surface above the boiler.  
When openings to boiler room are taken to interior spaces, provide  
two permanent openings: a combustion air opening within 1ꢀ inches  
of floor and a ventilation opening within 1ꢀ inches of ceiling. Each  
opening must provide a minimum free area of one square inch per  
1,000 Btuh input of all appliances in room plus requirements for  
any exhaust fans in room. The interior space supplying combustion  
and ventilation air must have adequate infiltration from outside.  
Install in a space large in comparison to size of boiler.  
Clearances from piping materials to combustible sur-  
faces  
Single wall vent pipe must be at least 6 inches from combustible  
surface.  
Type “B” double wall metal vent pipe - refer to vent manufacturer’s  
recommendation for clearances to combustible surface.  
Air directly from outside to boiler room:  
Tightly constructed buildings must be provided with combustion  
air and ventilation openings to boiler room which are adequate to  
handle the boiler needs plus the needs of all other fuel-burning ap-  
pliances, fireplaces and exhaust or ventilation fans.  
Hot water pipes must be at least ½” from combustible surface.  
Note  
Minimum clearances from combustible  
surfaces for models PFG-5 through PFG-7  
Combustion and ventilation openings connecting directly or by  
ducting to outside, or to attic or crawl spaces that freely connect  
with outside, must be sized as follows:  
1. Outside wall or vertical ducting - one square inch per 4,000  
Btuh input of all appliances in room plus requirements for any  
exhaust fans or other appliances in room.  
ꢀ. Horizontal ducting - one square inch per ꢀ,000 Btuh of all appli-  
ances in room plus requirements for any exhaust fans or other  
appliances in room.  
3. All ducting must be same size as permanent openings.Minimum  
size of ducting must be no less than 9 square inches.  
4. Other size ducting must comply with local codes.  
Part Number 550-110-641/0605  
3
PFG SerieS 7 GaS-Fired Water Boiler — Boiler Manual  
Chimney or vent requirements  
(also refer to Breaching erection, Page 12)  
When removing boiler from  
common venting system  
Venting must be installed according to Part 7,Venting of  
Equipment, of National Fuel Gas Code, ANSI Zꢀꢀ3.1-  
latest edition and applicable building codes. Canadian  
installations must comply with CAN/CSA B149.1 or .ꢀ  
Installation Codes.  
Failure to follow all instructions listed  
below can cause flue gas spillage and  
carbon monoxide emissions, resulting in  
severe personal injury,death or substantial  
property damage.  
Minimum chimney or vent sizes are on page ꢀꢀ.A chim-  
ney or vent without a listed cap should extend at least  
3 feet above the highest point where it passes through  
a roof of a building and at least ꢀ feet higher than any  
portion of a building within a horizontal distance of 10  
feet. A chimney or vent must not extend less than those  
distances stated above.  
At the time of removal of an existing boiler,the following  
steps shall be followed with each appliance remaining  
connected to the common venting system placed in op-  
eration,while the other appliances remaining connected  
to the common venting system are not in operation.  
a. Seal any unused openings in the common venting sys-  
tem.  
A lined chimney is preferred and must be used when  
required by federal, provincial, territorial, state or local  
building codes. Vitreous tile linings with joints which  
prevent the retention of moisture and linings made  
of corrosion-resistant materials are best. Advice for  
flue connections and chimney linings can usually be  
obtained from the local gas utility. Type “B” double  
wall metal vent pipe or single wall vent pipe may be  
used as a liner.  
Cold masonry chimneys, also known as outside chim-  
neys, typically have one or more walls exposed to  
outside air.  
When any atmospheric gas-fired boiler with automatic  
vent damper is vented through this type of chimney, the  
potential exists for condensation to occur.Condensation  
can damage a masonry chimney.  
b. Visually inspect the venting system for proper size and  
horizontal pitch and determine there is no blockage or  
restriction,leakage,corrosion and other deficiencies which  
could cause an unsafe condition.  
c. Insofar as is practical,close all building doors and windows  
and all doors between the space in which the appliances  
remaining connected to the common venting system are  
located and other spaces of the building. Turn on clothes  
dryers and any appliance not connected to the common  
venting system. Turn on any exhaust fans, such as range  
hoods and bathroom exhausts, so they will operate at  
maximum speed. Do not operate a summer exhaust fan.  
Close fireplace dampers.  
d. Place in operation the appliance being inspected. Follow  
the lighting instructions. Adjust thermostat so appliance  
will operate continuously.  
Weil-McLain recommends the following to prevent  
possible damage:  
1. Line chimney with corrosion-resistant metal liner such as  
ALꢀ9-4C® single wall stainless steel or B-vent. Size liner  
per National Fuel Code ANSI Zꢀꢀ3.1-latest edition.  
e. Test for spillage at the draft hood relief opening after  
5 minutes of main burner operation. Use the flame of  
a match or candle, or smoke from a cigarette, cigar or  
pipe.  
f. After it has been determined that each appliance remain-  
ing connected to the common venting system properly  
vents when tested as outlined above, return doors, win-  
dows, exhaust fans, fireplace dampers, and any other gas-  
burning appliance to their previous conditions of use.  
ꢀ. Provide drain trap to remove any condensate.  
Inspect existing chimney or vent before  
installing boiler.Failure to clean or replace  
perforated pipe or tile lining will cause  
severe injury or death.  
g. Any improper operation of the common venting system  
should be corrected so the installation conforms with the  
National Fuel Gas Code,ANSI Zꢀꢀ3.1-latest edition.When  
resizing any portion of the common venting system, the  
common venting system should be resized to approach  
the minimum size as determined using the appropriate  
tables in Part 11 in the National Fuel Gas Code, ANSI  
Zꢀꢀ3.1-latest edition.  
Do not alter boiler draft hood or place  
any obstruction or non-approved damper  
in the breeching of vent system. CSA  
certification becomes void. Flue gas  
spillage and carbon monoxide emissions  
will occur causing severe personal injury  
or death.  
Canadian installations must comply with CAN/CSA  
B149.1 or B149.ꢀ Installation Code.  
Where two or more gas appliances vent into a common  
chimney or vent, equivalent area should be at least equal  
to the area of the vent outlet on the largest appliance  
plus 50 percent of the area of the vent outlet on the ad-  
ditional appliance(s).  
Part Number 550-110-641/0605  
4
PFG SerieS 7 GaS-Fired Water Boiler — Boiler Manual  
Boiler foundation  
Placing the boiler  
1. Remove boiler from shipping pallet. Do not drop boiler or bump  
jacket on floor or pallet.  
Never install boiler on combustible flooring or  
carpeting, even if a concrete or aerated foundation  
is used. Severe personal injury, death or substantial  
property damage can result.  
ꢀ. Level boiler so that the built-in air separation will work correctly.  
Shim legs if necessary. Do not alter legs.  
1. See Figure 1. A level concrete or solid brick pad is required if:  
a) There is a possibility of the floor becoming flooded.  
b) Non-level conditions exist.  
3. Remove front jacket door and burner access panel. Unscrew access  
panel screws, remove and discard shipping washers, and reinstall  
screws.  
4. Check for proper orifice sizing from charts below.  
Proper orifices must be used. Failure to do so will  
cause severe personal injury, death or substantial  
property damage.  
ꢀ. An aerated boiler foundation is recommended if any of the following  
conditions exist:  
a) Electrical wiring or telephone cables buried in the concrete floor  
of the boiler room.  
b) Concrete floor is “green.”  
c) There is a history of the floor becoming flooded.  
d) Water is channeled under the concrete.  
5. Level and straighten the burners.  
Burners must be seated properly in locating slots  
with their openings facing up. Gas orifices must  
inject down the center of the burner. Failure to  
properly seat burners will result in severe personal  
injury, death or substantial property damage.  
Figure 1  
Boiler foundation  
6. Reinstall access panel.  
Residential garage installation  
Install boiler so burners are at least 18 inches above the floor.  
Hydrostatic pressure test  
Pressure test before attaching gas piping or electrical supply.  
1. Plug any necessary boiler tappings or openings.  
ꢀ. Connect water supply. Fill boiler and purge all air. Test at 45 psi for  
more than 10 minutes.  
Do not leave boiler unattended. A cold water  
fill could expand and cause excessive pressure,  
resulting in severe personal injury, death or  
substantial property damage.  
3. Check for maintained gauge pressure and leaks. Repair if found.  
Leaks must be repaired at once. Failure to do so  
can cause boiler damage, resulting in substantial  
property damage.  
Do not use petroleum-based sealing compounds in  
boiler system. Severe damage to boiler will result,  
causing substantial property damage.  
4. Drain boiler and remove testing plugs.  
Part Number 550-110-641/0605  
5
PFG SerieS 7 GaS-Fired Water Boiler — Boiler Manual  
4. Expansion tank installations.  
Boiler piping connections to the heating  
a) Closed type expansion tanks - connect from the ¾” N.P.T.  
system (refer to piping diagrams, Page 7)  
expansion tank tapping on the left end section (located just  
behind the supply outlet tapping) to the expansion tank using  
¾” N.P.T. piping. Any horizontal expansion tank piping must  
pitch upward toward the tank at least 1 inch for each 5 feet of  
piping.  
Failure to properly pipe the boiler may result in  
improper operation and damage to the boiler or  
building.  
These boilers are provided with built-in air elimination sys-  
tems.  
b) Diaphragm type expansion tank - may be located anywhere in  
the system, preferably near the boiler.  
1. Install relief valve vertically in top ¾” tapping in right end section.  
See WARNING following.  
A manual or automatic type air vent must be  
installed in the ¾N.P.T.tapping when a diaphragm  
type tank is used.  
To avoid water damage or scalding due to relief  
valve operation:  
The most common cause of lime deposits in boilers is inadequate  
expansion tank volume. If the expansion tank is too small, system  
water is lost from the relief valve and make-up water is added  
through the fill valve. Eventual section failure will result.  
5. Connect the system supply piping to the supply outlet tapping on  
the left end of the boiler. See Figure ꢀa for minimum pipe size.  
Discharge line must be connected to relief valve  
outlet and run to a safe place of disposal. Terminate  
the discharge line to eliminate possibility of severe  
burns should the valve discharge.  
Discharge line must be as short as possible and be  
the same size as the valve discharge connection  
throughout its entire length.  
6. Connect the system return piping to the return tapping on the right  
end of the boiler. See Figure ꢀa for minimum pipe size.  
Discharge line must pitch downward from the valve  
and terminate at least 6above the floor drain where  
any discharge will be clearly visible.  
7. Install drain valve provided with boiler on left side. The installer  
must provide a drain cock to drain the right (return) side of the  
boiler and its connecting piping. The drain cock on the left side of  
the boiler will not fully drain the right side.  
The discharge line shall terminate plain,not thread-  
ed, with a material serviceable for temperatures of  
375 °F or greater.  
8. Low water cut off:  
a) Must be installed on any PFG boiler if the boiler is located above  
radiation level.  
Do not pipe the discharge to any place where freez-  
ing could occur.  
b) Must be installed on all PFG-8 boilers to meet ASME specifica-  
tions (low water cut-off not supplied by Weil-McLain).  
No shutoff valve shall be installed between the  
relief valve and boiler, or in the discharge line. Do  
not plug or place any obstruction in the discharge  
line.  
c) May be required by certain state, local or territorial codes or  
insurance companies.  
If a low water cut-off is required, use a control designed especially  
for water installations. An electrode probe type low water cut-off  
may be located in a tee in the supply line above the boiler.  
Failure to comply with the above guidelines could  
result in failure of the relief valve to operate, result-  
ing in possibility of severe personal injury, death or  
substantial property damage.  
9. If the system is to be ASME inspected and approved, an additional  
high temperature limit is needed. Purchase and install the control  
in the supply outlet piping to the boiler.  
Test the operation of the valve after filling and pres-  
surizing system by lifting the lever. Make sure the  
valve discharges freely. If the valve fails to operate  
correctly, replace it with a new relief valve.  
Figure 2a Minimum recommended pipe sizes  
(Supply and return sizes refer to minimum size of  
pipe connected to the boiler for 20°F temperature  
drop between supply and return.)  
ꢀ. Install pressure-temperature gauge in tapping provided in left end  
section.  
3. This boiler is for forced hot water circulation only.The circulator and  
expansion tank must be selected and sized according to the design  
requirements of the system.  
a) Size and install circulator. Can be installed on supply or return  
piping  
b) Size expansion tank to handle the volume of water in the sys-  
tem.  
Part Number 550-110-641/0605  
6
PFG SerieS 7 GaS-Fired Water Boiler — Boiler Manual  
Multiple zoning  
Figure 2b Piping – Closed type expansion tank  
1. Zone valves:  
a) Refer to zone valve manufacturer’s literature for wiring  
and application.A separate transformer is required to  
power zone valves.  
b) Provide balancing valves to adjust the flow so it is  
about the same in each zone.  
ꢀ. Circulators:  
a) Zoning with circulators requires a relay for each cir-  
cuit.  
b) Install flow control valves to prevent gravity circula-  
tion.  
c) Provide balancing valves to adjust the flow so it is  
about the same in each zone.  
d) Size common return and supply piping for total flow  
of all circulators.  
Filling the system  
1. Close manual air vents, drain cock, and automatic air vent,  
if used.  
Use circulators or zone valves in each circuit for multiple  
circuit applications.  
ꢀ. Fill to correct system pressure. Correct pressure will vary  
with each application. Residential systems are often de-  
signed for 1ꢀ pounds cold fill pressure.  
3. Open automatic air vent one turn, if used.  
Figure 2c Piping – Closed diaphragm type expansion tank  
4. Air must be vented for the system. Air in the system can  
interfere with water circulation and cause improper heat  
distribution.  
a) Open manual water feed valve.  
b) Starting on the lowest floor, open the air vents one at  
a time until water squirts out. Close vent.  
c) Repeat with remaining vents.  
d) Close manual water feed valve when correct boiler  
pressure is reached.  
5. To purge air from system, install isolation valve in return  
piping.  
a) Connect a garden hose to the purge valve located  
above the isolation valve.  
b) Close isolation valve. Open purge valve.  
c) Open hand water feed valve and allow system to purge  
all air. If system has more than one circuit, purge each  
circuit separately by opening each balancing valve one  
at a time.  
Use circulators or zone valves in each circuit for multiple  
circuit applications.  
d) Close purge valve.  
e) Open isolation valve.  
f) Fill the system to the correct pressure.  
6. Keep the system filled by occasionally opening the air  
vents as in Step 4 above. Add water to make up system  
pressure.  
Part Number 550-110-641/0605  
7
PFG SerieS 7 GaS-Fired Water Boiler — Boiler Manual  
Bypass piping  
Figure 3  
Bypass piping is not normally required on  
any baseboard system.  
Bypass piping should be used for the following instal-  
lations. (Bypass, supply, and return piping should be  
same size.)  
1. Use the piping shown in Figure 3 to protect:  
radiant panels, plaster, etc. from high temperature  
water supplied from boiler, or  
boiler from condensation caused by low temperature  
water returned from system.  
ꢀ. Use the piping shown in Figure 4 to protect boiler from  
condensation formed by low water temperature returned  
from large water content converted gravity systems, etc.  
Figure 4  
Part Number 550-110-641/0605  
8
PFG SerieS 7 GaS-Fired Water Boiler — Boiler Manual  
External heat exchangers  
The PFG boiler can be used with a storage tank/heat exchanger unit for  
domestic hot water. The boiler/tank combination should be installed and  
wired in accordance with the tank manufacturer’s instructions, which will  
also show any additional components required. A zone valve or separate  
circulator must be installed to regulate the production of hot water.  
Freeze protection  
Use antifreeze especially made for hydronic systems. Inhibited propylene  
glycol is recommended.  
Do not use automotive,ethylene glycol or undiluted antifreeze.  
Severe personal injury, death or substantial property damage  
can result.  
50% solution provides protection to about -30°F  
Local codes may require a back-flow preventer or actual disconnect from  
city water supply.  
Determine quantity according to system water content. Boiler water content  
is listed on page ꢀ3.  
Follow antifreeze manufacturer’s instructions.  
Using with refrigeration system  
The boiler must be installed so that chilled medium is piped in parallel with  
the heating boiler with appropriate valves to prevent the chilled medium  
from entering the boiler. Consult I=B=R Installation and Piping Guides.  
If boiler is connected to heating coils located in air handling units where they  
can be exposed to refrigerated air,gravity circulation during the cooling cycle  
must be prevented with flow control valves or other automatic means.  
Part Number 550-110-641/0605  
9
PFG SerieS 7 GaS-Fired Water Boiler — Boiler Manual  
If boileristobepropanered,aconversion  
Size and install gas piping  
In sizing the gas piping, the following factors should  
be considered.  
kit must be used. Failure to use kit or to  
properly install kit will result in severe  
personal injury, death or substantial  
property damage.  
a) Diameter and length of the gas supply piping.  
b) Number of fittings.  
3. Remove jacket door and connect from gas valve to  
gas meter. Use a street elbow or an elbow and close  
nipple at the inlet connection of the gas valve to run  
gas piping through opening in jacket side panel.  
c) Maximum gas consumption (including any pos-  
sible future expansion).  
d) Allowable loss in gas pressure from gas meter out-  
let to boiler. For pressure drops, see ANSI Zꢀꢀ3-1  
latest edition.Canadian installations must comply  
with CAN/CSA B149.1 or .ꢀ Installation Codes.  
4. Follow good piping practices.  
5. Pipe joint compound (pipe dope) must be resistant  
to corrosive action of liquefied petroleum gases and  
applied sparingly only to male threads of pipe joints.  
1. Size natural gas piping from the following table. Piping  
must be sized to provide proper inlet gas pressure to the  
gas valve when boiler is operating at rated input. For  
natural gas, inlet gas pressure to gas valve should be a  
minimum of 5 inches water column and a maximum of 13  
inches water column. If inlet natural gas pressure exceeds  
13 inches water column, a 100 percent lock-up type gas  
pressure regulator of adequate size must be installed in gas  
supply piping and adjusted to prevent pressure in excess  
of 13 inches water column.  
6. A drip leg must be installed at inlet of gas connection to  
boiler.Where local utility requires drip leg be extended  
to the floor, use an appropriate length of pipe between  
the cap and tee.  
7. A ground joint union must be installed in the piping  
to provide for servicing (see Figure 5).  
8. Install manual shut-off valve outside boiler jacket as  
shown in Figure 5 when required by local codes.  
9. Piping must be supported by hangers, not by the boiler  
or its accessories.  
To obtain cubic feet per hour, divide the input (Btu per  
hour) by the heating value (Btu per cubic foot).  
10. In Canada only - when manual main shut off valve is  
used, it must be identified by installer.  
11. Purge all air from the supply piping.  
Pipe delivery schedule  
Before starting the boiler, and during  
initial operation, smell near the floor and  
around the boiler for gas odorant or any  
unusual odor. Remove boiler front door  
and smell interior of boiler enclosure. Do  
not proceed with startup if there is any  
indication of a gas leak. Repair any leak  
at once.  
1ꢀ. Before placing boiler in operation, check boiler and its  
gas connection for leaks.  
a) If test pressure is less than 13.0 inches water column  
then close manual main shut-off valve.  
b) If test pressure is greaterthan 13.0 inches water column  
then boiler and gas valve must be disconnected from  
gas supply piping.  
Do not check for gas leaks with an open  
flame - use bubble test. Failure to do so  
can cause severe personal injury, death or  
substantial property damage.  
ꢀ. PFG 6 thru 8 only (and no damper on PI boilers) - for  
propane gas, inlet gas pressure to gas valve should be  
11 to 13 inches water column. The gas pressure regula-  
tor (furnished by the gas supplier) must be adjusted  
to provide lock-up pressures not exceeding 13 inches  
water column. Select the pipe size, tanks and regulators  
as required.  
PFG-8,as required byANSI Zꢀ1.13/CSA 4.9,is equipped  
with a manual test valve as shown in Figure 5a. Close  
this valve to test boiler gas valve without supplying gas  
to the manifold.  
Part Number 550-110-641/0605  
10  
PFG SerieS 7 GaS-Fired Water Boiler — Boiler Manual  
Figure 5  
Gas supply piping  
Figure 5a Leak test valve (model PFG-8 ONLY)  
Part Number 550-110-641/0605  
11  
PFG SerieS 7 GaS-Fired Water Boiler — Boiler Manual  
Draft hood installation  
Wiring  
Secure the draft hood to the outlet at the top of the boiler  
with sheet metal screws. The bottom of the draft hood  
orskirtmust have the clearance dimension above the  
jacket top panel as indicated on the draft hood.  
For your safety, turn off the electrical  
power supply at the service entrance panel  
before making any electrical connections  
to avoid possible electrical shock hazard.  
Do not alter draft hood. CSA design  
certification becomes void. If draft hood  
is altered, severe personal injury or death  
will occur, resulting from flue gas spillage  
or carbon monoxide emissions.  
All wiring must be installed in accordance with re-  
quirements of the National Electrical Code and any  
additional national, state or local code requirements  
having jurisdiction. All wiring must be N.E.C. Class 1.  
The boiler must be electrically grounded in accordance  
with the National Electrical Code, ANSI/NFPA No. 70-  
latest edition.  
In Canada, all wiring must be done in accordance with  
the CSA Cꢀꢀ.1 Canadian Electrical Code Part 1.  
Iforiginalrolloutthermalfuseelementwireassuppliedwith  
PFG-5 boiler must be replaced, type ꢀ00°C wire or  
equivalent must be used. If other original wire as sup-  
plied with any PFG boiler must be replaced, type 105°C  
wire or equivalent must be used.  
The boiler is shipped with control components com-  
pletely wired except for spill switch and damper (if  
provided).  
A separate electrical circuit should be used for the  
boiler with a fused disconnect switch (15 amp. recom-  
mended).  
Refer to wiring diagram label affixed to the inside of  
the jacket door. Bring electrical supply through proper  
opening in the jacket left end panel and into the electri-  
cal junction box. Wire electrical supply, circulator and  
thermostat as shown on the wiring diagram.  
For boilers equipped with control systems other than  
constant burner pilot, refer to separate instructions for  
application data.  
Spill switch installation (PFG-5 ONLY)  
Fasten spill switch to draft hood as shown on page ꢀ1.  
Connect wires as shown on wiring diagram label located  
inside boiler door.  
Damper installation  
If damper will be installed, see Control Supplement for  
information.  
Breeching erection  
(Also refer to chimney or vent requirements, Page 4)  
Connect from draft hood or damper outlet to chimney  
or vent with same size as breeching. Where possible,  
vertical venting to the outside from the draft hood or  
damper outlet will offer best performance.Where hori-  
zontal breeching is used, slope upward at least ¼ inch  
per lineal foot toward the chimney or vent and support  
with hangers to prevent sagging.  
A minimum vertical height of 3 feet of  
breeching before any elbow or horizontal  
breeching is recommended to reduce  
chances of flue gas spillage at the draft  
hood. Long horizontal breechings,  
excessive numbers of elbows or tees, or  
other obstructions that restrict the flow  
of combustion gas should be avoided.  
Install room thermostat  
Install room thermostat on an inside wall. Never install  
where it will be influenced by drafts, hot or cold water  
pipes, lighting fixtures, television, rays of the sun or  
near a fireplace.  
Breeching must not be connected to any portion of a  
mechanical draft system that can operate under posi-  
tive pressure.  
Heat anticipator in thermostat must be set to match the  
power requirements of the primary control to which it  
is connected. Refer to wiring diagram on jacket door for  
recommended heat anticipator setting with standard  
equipment. Wire the thermostat as shown.  
Part Number 550-110-641/0605  
1ꢀ  
PFG SerieS 7 GaS-Fired Water Boiler — Boiler Manual  
Wiring multiple zones  
Figure 6  
Typical wiring – zoning with zone valves  
Refer to zone valve manufacturer’s literature for wiring  
and application. A separate transformer is required to  
power zone valves. Zoning with circulators requires a  
relay for each zone circulator.  
Canadian installations – Chain &  
s-hook  
See illustration below.  
The chain and s-hook should be installed  
according to this instruction by a qualified  
installer/service technician prior to boiler  
installation. Please follow steps outlined  
below for the installation of the chain and  
s-hook.  
1. Crimp one side of each s-hook to each end of the chain.  
ꢀ. Remove the two screws that attach the transformer plate  
to the junction box.  
3. Remove the transformer relay assembly and drill a 1/8”  
hole through the plate as shown below. Do not allow  
drill shavings to fall into the boiler jacket or onto any  
control.  
4. Crimp the s-hook to the 1/8” hole in the transformer  
plate. Crimp the other side of the chain to the junction  
box lower flange as shown below.  
5. Replace the transformer relay assembly on the junction  
box and secure with the two screws removed in step ꢀ.  
Figure 6  
Chain and s-hook installation – Canadian installations only  
Part Number 550-110-641/0605  
13  
PFG SerieS 7 GaS-Fired Water Boiler — Boiler Manual  
b. For standing pilot systems: Turn gas knob to PILOT position  
Check-out procedure  
and extinguish pilot flame - Pilot gas flow should stop in less  
than 3 minutes. Put system back into operation. See page 17.  
Check off steps as completed.  
High limit control set to design temperature requirements of the  
system? Maximum high limit setting - ꢀ40 °F.  
Check to make sure base insulation is secure. See "To inspect base  
insulation," page 17.  
For multiple zones, flow adjusted so it is about the same in each  
zone?  
Boiler and heat distribution units filled with water?  
Automatic air vent, if used, open one turn?  
Thermostat heat anticipator is set properly? Refer to "Install room  
thermostat," page 1ꢀ, and wiring diagram on jacket door.  
Air purged from system?  
Air purged from gas piping? Piping checked for leaks per page 10?  
Boiler cycled with the thermostat? Raise to highest setting. Boiler  
should go through normal start-up cycle. Lower to lowest setting.  
Boiler should go off.  
Follow operating/lighting instruction label on boiler for proper  
start-up. Also refer to “To place in operation,page 17.  
Measure gas input (natural gas only):  
a. Operate boiler 10 minutes.  
Are proper orifices installed? See page 5 for proper orifice size.  
Proper orifices must be used.Failure to do so will cause  
severe personal injury, death or substantial property  
damage.  
b. Turn off all other appliances served by the gas meter, including  
gas stove, pilot lights and gas yard lights.  
c. At natural gas meter measure time (in seconds) required to use  
on cubic foot of gas.  
Proper burner flame? Refer to "Check main burner  
flames" and "Check pilot burner flame," page 17.  
d. Calculate gas input:  
Test limit control: While burners are operating, move the indicator  
of the high limit control below actual boiler water temperature.  
The burners should go off while the circulator continues to operate.  
Raise the limit control above the boiler water temperature and the  
burners should reignite.  
e. Btuh calculated should approximate input rating on rating  
label.  
Check manifold gas pressure by connecting manometer to down-  
stream test tapping on main gas valve. Manifold gas pressure for  
natural gas should be 3 1/ꢀ inches water column and for propane  
gas should be 10 inches water column.  
Test any additional field-installed controls: If boiler has low water  
cut-off, additional high limit or other controls, test for operation as  
outlined by manufacturer. Burners should be operating and should  
go off when controls are tested.When controls are restored, burners  
should reignite.  
Several operating cycles observed for proper operation? If damper  
is provided, see Control Supplement for check-out procedure.  
To test ignition system shut-off device:  
a. For PI systems: Connect a manometer to outlet side of gas  
valve. Start boiler, allowing for normal start-up cycle to occur  
and main burners to ignite. With main burners on, manually  
shut off gas supply at manual main shut-off gas valve. Burners  
should go off. Open manual main shut-off gas valve. The ma-  
nometer should confirm there is no gas flow. Pilot will relight,  
flame sensing element will sense pilot flame and the main burn-  
ers reignite.  
Room thermostat set to desired temperature?  
Installation and Service Certificate on this page completed?  
All instructions shipped with this boiler reviewed with owner or  
maintenance person, returned to envelope and given to owner or  
displayed near boiler?  
Installation and Service Certificate  
Boiler model __________________  
Series __________  
CP number ___________  
Date installed _______________  
o Installation instructions have been followed.  
o Check-out sequence has been performed.  
Measured Btuh input ____________  
o Above information is certified to be correct.  
o Information received and left with owner/maintenance person.  
Installer ________________________  
(company)  
________________________________  
(address)  
______________________________  
(phone)  
_____________________________________  
(installer’s signature)  
Part Number 550-110-641/0605  
14  
PFG SerieS 7 GaS-Fired Water Boiler — Boiler Manual  
Section II: Service  
Also Refer to Additional Instructions Shipped With The Boiler For  
Specific Control Operation and Troubleshooting.  
Verify Proper Operation After Servicing.  
Your boiler should be inspected, cleaned  
and, if necessary, adjusted once a year.  
A qualified service agency should be  
called.  
Toavoidpersonalinjury,deathorproperty  
damage, keep the boiler area clear and free  
from combustible materials, gasoline and  
other flammable vapors and liquids.  
Do not block flow of air to boiler.  
Incomplete combustion and carbon  
monoxide emissions can cause severe  
personal injury, death or substantial  
property damage.  
To avoid personal injury, before  
servicing:  
1. Disconnect electrical supply.  
ꢀ. Shut-off gas supply.  
Do not store sources of hydrocarbons (i.e.,  
bleaches,cleaners,chemicals,sprays,paint  
removers, fabric softeners, etc.) in boiler  
area. This can contribute to shortened  
boiler/vent system life.  
3. Allow boiler to cool.  
Labelallwirespriortodisconnectionwhen  
servicing controls.Wiring errors can cause  
improper and dangerous operation.  
Handling ceramic fiber and fiberglass materials  
respirators may be needed depending on the job site condi-  
tions. Current NIOSH recommendations can be found on  
html.NIOSH approved respirators,manufacturers,and phone  
numbers are also listed on this web site.  
This product contains fiberglass jacket insulation and  
ceramic fiber materials in combustion chamber lining  
or base panels in gas fired products. Airborne fibers  
from these materials have been listed by the State  
of California as a possible cause of cancer through  
inhalation. The combustion chamber lining or base  
insulation panels in this product contain ceramic  
fiber materials. Ceramic fibers can be converted to  
cristobalite in very high temperature applications. The  
International Agency for Research on Cancer (IARC)  
has concluded, “Crystalline silica inhaled in the form  
of quartz or cristobalite from occupational sources is  
carcinogenic to humans (Group 1).:  
Wear long-sleeved, loose fitting clothing, gloves, and eye  
protection.  
Apply enough water to the combustion chamber lining or base  
insulation to prevent airborne dust.  
Remove combustion chamber lining or base insulation from  
the boiler and place it in a plastic bag for disposal.  
Operations such as sawing, blowing, tear out and spraying  
may generate airborne fiber  
ditional protection. Bag for disposal.  
concentration requiring ad-  
Suppliers of fiberglass wool products recommend the  
following precautions be taken when handling these  
materials:  
Wash potentially contaminated clothes separately from other  
clothing. Rinse clothes washer thoroughly.  
Precautionary measures  
Avoid breathing fiberglass dust and contact with skin or  
eyes.  
NIOSH stated First Aid.  
Eye: Irrigate immediately  
Breathing: Fresh air.  
Use NIOSH certified dust respirator (N95). This type of  
respirator is based on the OSHA requirements for fiberglass  
wool at the time this document was written. Other types of  
Part Number 550-110-641/0605  
15  
PFG SerieS 7 GaS-Fired Water Boiler — Boiler Manual  
Suggested Minimum Service Schedule  
for Qualified Service Technician Only  
Beginning of each heating season:  
1. Annual service call by a qualified service agency.  
ꢀ. Check burners and flueways and clean if necessary. ReferenceTo clean boiler heating surfacesandTo clean main  
burners,page 18.  
3. Visually inspect base insulation. Reference “To inspect base insulation,page 17.  
4. Follow procedure “To place in operation,page 17.  
5. Visually inspect main burner flames. Refer to “Check main burner flames,page 17.  
6. Check pilot burner flame. Refer to page 17.  
7. Visually inspect venting system for blockage, deterioration or leakage. Reference “Inspect venting system,”  
page 18.  
8. Check operation of low water cut-off, if used, and additional safety devices. Refer to manufacturer’s instruc-  
tions.  
9. Check that boiler area is free from combustible materials, gasoline and other flammable vapors and liquids.  
10. Check for and remove any obstruction to the flow of combustion or ventilation air to the boiler.  
11. Follow instructions on circulator to oil, if oil lubricated. Over oiling will damage the circulator. Water lubricated  
circulators do not need oiling.  
Daily during heating season:  
1. Check that boiler area is free from combustible materials, gasoline and other flammable vapors and liquids.  
ꢀ. Check for and remove any obstruction to the flow of combustion or ventilation air to the boiler.  
Periodically during heating season:  
1. Check relief valve. Reference manufacturer’s instructions on relief valve tag.  
ꢀ. Test low water cut-off, if used. Blowdown if low water cut-off is float type. Reference manufacturer’s instruc-  
tions.  
Monthly during heating season:  
1. Check for leaks in the boiler and piping. If found, repair at once.  
Leaks must be repaired at once. Failure to do so can cause boiler damage, resulting in substantial  
property damage.  
Do not use petroleum-based sealing compounds in boiler system. Severe damage to boiler will result,  
causing substantial property damage.  
ꢀ. Visually inspect main burner flames. Reference “Check Main Burner Flames.”  
3. Check pilot burner flame. Refer to page 17.  
4. Visually inspect venting system for blockage, deterioration or leakage. Reference “Inspect venting system,”  
page 18.  
5. Check automatic air vent for leakage. If leaking, remove vent cap and push valve core in to wash off sediment that  
may have accumulated on the valve seat. Release valve, replace cap, and open one turn.  
End of each heating season:  
1. Follow Annual shut-down procedure,page 18.  
Part Number 550-110-641/0605  
16  
PFG SerieS 7 GaS-Fired Water Boiler — Boiler Manual  
To inspect base insulation:  
Check pilot burner flame:  
1. Proper pilot flame  
The boiler contains ceramic fiber and fiberglass materials.  
Use care when handling these materials. See WARNING  
above. Failure to comply could result in severe personal  
injury.  
a) Blue flame.  
b) Inner cone engulfing pilot flame sensor.  
c) Pilot flame sensor glows cherry red.  
ꢀ. Improper pilot flame  
Make sure base insulation is secure against base front and back panels. If  
base insulation is damaged or displaced, do not operate boiler. Replace  
or reposition insulation.  
a) Overfired - flames large and lifting or blowing past pilot flame  
sensor.  
Failure to replace damaged insulation or reposition  
insulation can result in a fire hazard, causing severe  
personal injury, death or substantial property damage.  
b) Underfired - flame small; pilot flame sensor not engulfed by  
inner cone.  
c) Lack of primary air - flame tip yellow.  
d) Pilot flame sensor not heated properly.  
To place in operation:  
Figure 7  
Typical pilot burner flame  
1. Make sure boiler is filled with water.  
ꢀ. Follow lighting/operating instructions on boiler.  
PROPANE BOILERS ONLY Your propane  
supplier mixes an odorant with the propane to  
make its presence detectable. In some instances, the  
odorant can fade, and the gas may no longer have  
an odor.  
Propane gas can accumulate at floor level. Smell  
near the floor for the gas odorant or any unusual  
odor. If you suspect a leak, do not attempt to light  
the pilot.  
Use caution when attempting to light a propane  
pilot. This should be done by a qualified service  
technician, particularly if pilot outages are  
common.  
Periodically check the odorant level of your gas.  
Inspect boiler and system at least yearly to make  
sure all gas piping is leak-tight.  
Check main burner flames:  
1. Proper burner flame - Yellow-orange streaks may appear - caused  
by dust.  
Consultyourpropanesupplierregardinginstallation  
of a gas leak detector. There are some products on  
the market intended for this purpose. Your supplier  
may be able to suggest an appropriate device.  
ꢀ. Improper flame  
a) Overfired - Flames large.  
3. If boiler starts, go to Step 5. If boiler fails to start, go to Step 4.  
4. If boiler fails to start, check for following conditions:  
a) Loose connection or blown fuse?  
b) Underfired - Flames small.  
c) Lack of primary air - Yellow tipping on flames; sooting will oc-  
cur.  
b) High limit setting below boiler water temperature?  
c) Thermostat setting below room temperature?  
d) Gas not turned on at meter?  
Figure 8  
Typical main burner flame  
e) Gas not turned on at boiler?  
f) If above fails to eliminate the trouble, refer to Control Supple-  
ment.  
5. Make sure boiler goes through several normal operating cycles.  
6. Turn thermostat or operating control to desired setting.  
Part Number 550-110-641/0605  
17  
PFG SerieS 7 GaS-Fired Water Boiler — Boiler Manual  
Inspect venting system:  
Annual shut-down procedure:  
1. Check venting system at least once a month during heating season.  
With boiler in operation (at least 5 minutes), hold a candle or match  
below lower edge of draft hood “skirt.If flame is undisturbed or  
leans under skirt, vent system is functioning properly. If flame is  
extinguished, flickers, or reduced while flame is pushed out side  
skirt, the vent system must be checked for obstructions or other  
causes of improper venting.  
1. Follow lighting/operating instructions label on boiler.  
ꢀ. DO NOT drain the system unless exposure to freezing  
temperatures will occur. If antifreeze is used with system,  
do not drain.  
3. If the complete boiler and piping system must be drained  
to avoid freezing, then a means must be provided for  
draining water from BOTH ends of the boiler at or below  
the level of the return tapping. A boiler drain cock is pro-  
vided by Weil-McLain on the left side of the boiler only.  
ꢀ. Inspect all parts of venting systems for deterioration from corrosion,  
physical damage, sagging, etc. Correct all conditions found.  
3. Verify damper, if used, is open when burner ignites. For additional  
information, see Control Supplement.  
To replace a boiler section  
If replacing any section (see Figure 9):  
To clean boiler heating surfaces  
Approved RTV silicone sealant (Dow Corning 700 or  
73ꢀ or G.E. 808 or 108) must be used to seal between  
sections.  
The boiler contains ceramic fiber and fiberglass materials.  
Use care when handling these materials per instructions  
on page 15 of this manual. Failure to comply could result  
in severe personal injury.  
Place ball bearings in the holes in the locator holes on  
the sides of the sections to ensure section alignment and  
reliable placement.  
1. Follow shut-down procedure.  
ꢀ. Remove breeching, draft hood and damper (when used).  
Failure to use PFG Series 7 intermediates  
or to properly seal sections per Figure  
9 can cause flue gas spillage or carbon  
monoxide emissions, resulting in severe  
personal injury, death or substantial  
property damage.  
Remove jacket top panel. Turn back jacket insulation to expose col-  
lector hood.  
3. Remove collector hood. Clean excess boiler cement from collector  
hood and cast iron sections.  
4. Remove radiation plates.  
5. Remove burners from base of boiler.FollowTo clean main burners,”  
page 18, to thoroughly clean burners.  
Figure 9  
Section assembly  
6. Place newspaper in base of the boiler to collect soot that will fall.  
7. With a wire flue brush, clean between the sections.  
8. Remove newspaper and soot.Vacuum or brush base and surrounding  
area to remove soot.  
9. Reinstall radiation plates.  
10. Reinstall collector hood. Seal with boiler cement.  
11. Reinstall insulation and jacket panel.  
1ꢀ. Reinstall burners.  
When reinstalling, burner tubes must be seated in their  
locating slots with the openings facing up. Gas orifices  
must inject down center of burner. Failure to properly  
seat burner will result in severe personal injury, death or  
substantial property damage.  
13. Reinstall draft hood, damper (when used), and breeching.  
14. Follow To Place in Operation” procedure.  
Excessive sooting indicates improper combustion of the  
gas. Call a qualified service agency or your local gas utility  
to check for proper combustion and make any necessary  
adjustments.  
To clean main burners:  
1. Vacuum or brush burners to remove dust and lint.  
When reinstalling, burner tubes must be seated in their  
locating slots with the openings facing up. Gas orifices  
must inject down center of burner. Failure to properly  
seat burner will result in severe personal injury, death or  
substantial property damage.  
Part Number 550-110-641/0605  
18  
PFG SerieS 7 GaS-Fired Water Boiler — Boiler Manual  
Common problems and possible solutions  
Part Number 550-110-641/0605  
19  
PFG SerieS 7 GaS-Fired Water Boiler — Boiler Manual  
Section III: Replacement Parts  
The boiler contains ceramic fiber and fiberglass materials. Use care when handling these materials, per  
instructions on page 15 of this manual. Failure to comply could result in severe personal injury.  
To avoid personal injury, before replacing any parts on the boiler:  
1. Turn off power.  
ꢀ. Shut off gas supply.  
3. Allow boiler to cool.  
Item  
1
Description  
Part Number  
Draft hood:  
PFG-5 (7” x 7” dia x 24.45”)  
PFG-6 (8” x 8” dia x 27.80”)  
PFG-7 (9” x 9” dia x 31.05”)  
PFG-8 (9” x 9” dia x 36.55”)  
PFG-5  
PFG-6  
PFG-7  
PFG-8  
450-021-200  
450-021-201  
450-021-202  
450-021-205  
450-014-819  
450-014-820  
450-014-821  
450-014-822  
312-804-405  
312-804-416  
312-804-405  
386-700-856  
512-200-022  
512-200-023  
452-800-655  
452-800-500  
452-800-501  
452-800-502  
452-800-503  
591-222-020  
591-222-021  
591-222-022  
591-222-025  
452-800-540  
452-800-541  
452-800-542  
452-800-543  
591-125-820  
591-125-821  
591-125-822  
591-125-823  
452-800-580  
452-800-581  
452-800-582  
452-800-583  
591-222-030  
591-222-031  
591-222-032  
591-222-033  
560-134-506  
560-134-507  
560-134-508  
560-134-509  
452-800-449  
452-800-450  
452-800-451  
452-800-452  
591-222-095  
591-222-096  
591-222-097  
591-222-098  
510-300-014  
512-050-230  
460-003-700  
562-930-250  
386-700-856  
560-529-055  
560-529-056  
2
Collector hood:  
3
4
5
NS  
6
NS  
7
Right hand end section, 51113  
Intermediate section, 51125  
Left hand end section, 51113  
Section replacement kit (one per joint; 4 seals, 4 ball bearings, and sealant)  
Burner, main  
Burner, main with pilot bracket  
Right hand/left hand base rail  
Base front panel:  
8
PFG-5  
PFG-6  
PFG-7  
PFG-8  
PFG-5  
PFG-6  
PFG-7  
PFG-8  
PFG-5  
PFG-6  
PFG-7  
PFG-8  
PFG-5  
PFG-6  
PFG-7  
PFG-8  
PFG-5  
PFG-6  
PFG-7  
PFG-8  
PFG-5  
PFG-6  
PFG-7  
PFG-8  
PFG-5 ⁵⁄₈”-11 UNC x 15”  
PFG-6 ⁵⁄₈”-11 UNC x 18”  
PFG-7 ⁵⁄₈”-11 UNC x 21”  
PFG-8 ⁵⁄₈”-11 UNC x 24”  
PFG-5  
PFG-6  
PFG-7  
PFG-8  
PFG-5  
PFG-6  
PFG-7  
PFG-8  
9
Front base insulation:  
Base access panel:  
Manifold:  
10  
11  
12  
13  
14  
15  
16  
Base back panel:  
Back base insulation:  
Tie rod without nut (2 per boiler):  
Flue baffle:  
Flue baffle insulation:  
17  
18  
19  
20  
Spill switch, PFG-5 only  
Rollout thermal fuse element, PFG-5 only  
Radiation shield (2 per joint)  
Section alignment ball bearings, 1/4” diameter (4 per joint)  
Ball bearing kit (4 bearings)  
Main burner orifice (natural gas) #37 drill  
Main burner orifice (propane gas) 1.65 mm  
NS  
NS  
Part Number 550-110-641/0605  
ꢀ0  
PFG SerieS 7 GaS-Fired Water Boiler — Boiler Manual  
Part Number 550-110-641/0605  
ꢀ1  
PFG SerieS 7 GaS-Fired Water Boiler — Boiler Manual  
Section IV: Ratings and dimensions  
DOE  
Standard equipment  
Factory Fire Tested  
Combination Pressure-Temperature Gauge  
(shipped in separate carton)  
Insulated Extended Jacket  
Built-In Air Separator  
Drain Valve (shipped in separate carton)  
Draft Hood (Shipped in separate carton)  
Combination Gas Valve  
PIDN  
Non-Linting Pilot Burner  
Aluminized Steel Burners  
Intermittent Electronic Ignition System  
Automatic Vent Damper  
Combination Relay Receptacle and 40 VA Trans-  
former  
PIN  
Relay  
Intermittent Electronic Ignition System  
High Limit Control  
SPN  
Spill Switch (PFG-5 only)  
Rollout Thermal Fuse Element (PFG-5 only)  
Constant Burning Thermally Supervised Pilot System  
Thermocouple  
30 P.S.I. Relief Valve (shipped in separate carton)  
(boiler sections tested for 50 P.S.I. water working  
pressure)  
Part Number 550-110-641/0605  
ꢀꢀ  
PFG SerieS 7 GaS-Fired Water Boiler — Boiler Manual  
* Locate manual main Shut-Off Gas Valve (where required) according to local utility requirements.  
Part Number 550-110-641/0605  
ꢀ3  
PFG SerieS 7 GaS-Fired Water Boiler — Boiler Manual  
Part Number 550-110-641/0605  
ꢀ4  

VocoPro Car Amplifier VP 600X User Manual
Vizio Blu Ray Player With Wireless Internet Application VBR140 User Manual
TP Link Car Stereo System TL ANT2409A User Manual
Tiffen 37DIGEFK User Manual
Sony XR CA370X User Manual
Sony VCT R100 User Manual
Sony HDR CX6EK User Manual
Sony Handycam HDR XR500V User Manual
Sony DCR TRV118E User Manual
Sony CCD TRV69E User Manual