Smith Cast Iron Boilers GT Series User Manual

GTIOM-3  
MODEL GT SERIES  
INSTALLATION, OPERATING  
AND MAINTENANCE MANUAL  
Modulating, Direct Vent, Gas-Fired Condensing Boilers  
Natural Or Propane  
150,000 to 399,000 Btuh Input  
ENERGGY STAR  
gama  
see note  
WARNING: If the information in this manual is not followed exactly, a fire or explosion  
may result causing property damage, personal injury or loss of life.  
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of  
this or any other appliance.  
WHAT TO DO IFYOU SMELL GAS:  
• Do not try to light any appliance.  
• Do not touch any electrical switch. Do not use any phone in your building.  
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s  
instructions.  
• If you cannot reach your gas supplier, call the fire department.  
Installation and service must be performed by a qualified installer, service agency or  
the gas supplier.  
WARNING: Installation and service must be performed by a qualified installer, service  
agency or the gas supplier in accordance with all local and national codes. Failure to  
comply with this warning can result in a fire or explosion causing property damage,  
personal injury or loss of life!  
WARNING: It is the responsibility of the homeowner to keep the vent terminal clear  
of snow and ice. Failure to comply with this warning can result in excessive levels of  
carbon monoxide causing severe personal injury or death!  
INSTALLER: THESE INSTRUCTIONS MUST BE AFFIXED ADJACENT TO THE BOILER.  
CONSUMER: RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE PURPOSES.  
Note: For LP gas use conversion kit: GT82650-1 on GT-150 & 200, GT83017-1 on GT-400  
WESTCAST, INC.  
260 NORTH ELM STREET WESTFIELD, MA 01085  
TEL. (413) 562-9631 FAX (413) 562-3799  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Page 3  
Figure 1- Input vs Elevation Graph  
400  
300  
200  
100  
0
0-2000  
3000  
4000  
5000  
6000  
7000  
8000  
9000  
10000  
Elevation (ft)  
GT-150  
GT-200  
GT-400  
WARNING: At elevations greater than 2000 ft,  
660 m, the combustion of the GT must be checked  
with a calibrated combustion analyzer to ensure  
safe and reliable operation. Consult the Operating  
Instructions Section for instructions on adjusting  
the input to provide proper operation. Failure to  
comply with this warning can result in excessive  
levels of carbon monoxide causing severe  
personal injury or death!  
2. An optimum site will be level, central to the hot water  
piping system and close to an outside wall.  
NOTE:This boiler is designed for direct placement  
on a combustible floor. Never install this boiler on  
carpeting!  
3. DO NOT install this boiler in a location that would  
subject any of the gas ignition components to direct  
contact with water or excessive moisture during  
operation or servicing.The boiler location ambient  
temperature must be no less than 50°F, 10°C  
including the condensate line.  
BOILER LOCATION  
WARNING: The clearances to combustible  
construction listed inTable 1 must be maintained.  
Failure to comply with this warning can result in  
a extensive property damage, severe personal  
injury or death!  
4. NEVER store objects on or around the boiler.  
5. This boiler may be wall mounted. See the Wall Hung  
Conversion section listed in the table of contents.  
CAUTION: This boiler is designed to operate only  
in residential and commercial heating systems. It is  
not intended for:  
1. Outdoor installations, or unheated spaces, which  
can cause freezing.  
WARNING: Never store combustible materials,  
gasoline or any product containing flammable  
vapors or liquids in the vicinity of the boiler.  
Failure to comply with this warning can result  
in extensive property damage, severe personal  
injury or death!  
2. Process heating of potable water, or any other  
fluids.  
3. Un-pressurized, and gravity feed heating  
systems.  
4. Heating systems with very low pressures or  
flow.  
WARNING: Liquefied Petroleum, LP, gas is  
heavier than air; it is imperative that your boiler  
is not installed in a pit or similar location that  
will permit heavier than air gas to collect. Local  
Codes may require appliances fueled with LP  
gas be provided with an approved means, of  
removing unburned gases from the room. Check  
your local codes for this requirement. Failure to  
comply with this warning can result in extensive  
property damage, severe personal injury or  
death!  
Improper use or installation will seriously damage  
the boiler, voiding warranty!  
1. Locate the boiler in an area that provides good  
access to the unit. Keep in mind that servicing may  
require the removal of jacket panels. Accessibility  
clearances should take precedence over fire  
protection clearances. Table 1 lists the minimum  
clearances for servicing, however 24 in, 610 mm is  
recommended.  
Page 4  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Table 1 - Clearances  
One of the following materials is to be used for the air  
intake pipe:  
Combustible  
Clearance  
Service  
Clearance  
GT-150 & 200: 3 in, 76 mm, PVC Sch.40 pipe or  
Galvanized Steel pipe.  
GT-400: 4 in, 102 mm or 6 in 152 mm, PVC Sch.40  
pipe or Galvanized Steel pipe.  
Surface  
Front  
Back  
Sides  
in  
0
0
0
0
0
0
2
0
mm  
0
0
0
0
0
0
51  
0
in  
24  
0
12  
12  
12  
0
mm  
610  
0
305  
305  
305  
0
See Table 2 for the maximum equivalent air intake  
system length.  
Top  
Bottom - 150 & 200  
Bottom - 400  
Flue Pipe - enclosed  
Flue Pipe - in free air  
CAUTION:Combustion air contaminated with fluoro-  
carbons or other halogenated compounds such as  
cleaning solvents, refrigerants, chloride, flouride,  
bromine or iodine will result in the formation of  
acids in the combustion chamber. These acids will  
cause premature failure of the boiler voiding the  
warranty!  
n/a  
n/a  
n/a  
n/a  
COMBUSTION AIR  
WARNING: This boiler must be supplied with  
combustion air in accordance with Section 5.3,  
Air for Combustion & Ventilation, of the latest  
revision of the National Fuel Gas Code, ANSI  
Z223.1/NFPA 54 and all applicable local building  
codes. Failure to provide adequate combustion  
air for this boiler can result in excessive levels  
of carbon monoxide which can result in severe  
personal injury or death!  
GENERAL VENTING GUIDELINES  
WARNING: The vent installation must be in  
accordance with Part 7,Venting of Equipment, of  
the latest revision of the National Fuel Gas Code,  
ANSI Z223.1/NFPA 54 applicable provisions of  
the local building codes. Improper venting can  
result in excessive levels of carbon monoxide  
which can result in severe personal injury or  
death!  
WARNING: Never operate this boiler unless the  
air intake is connected to the outdoors. Failure to  
comply with this warning can result in excessive  
levels of carbon monoxide causing severe  
personal injury or death!  
NOTE: Compliance with code requirements doesn’t  
insure a satisfactory installation; good common  
sense must also be applied.  
WARNING: Each boiler must have it’s own intake  
air system. Common intake air systems are not  
to be used! Improper installation can result in  
excessive levels of carbon monoxide which can  
cause severe personal injury or death!  
WARNING: Each boiler must have it’s own vent  
system. Common positive pressure vent systems  
are not to be used! Improper installation can  
result in excessive levels of carbon monoxide  
which can cause severe personal injury or  
death!  
To operate properly and safely this boiler requires a  
continuous supply of air for combustion. NEVER store  
objects around the air inlet!  
1
WARNING: Field supplied piping and fittings  
are required to complete installation. The  
combustion air and vent pipe and fittings must  
conform to ANSI and ASTM standard D1785  
for schedule 40 PVC, D2665 for PVC-DWV, and  
D2661 for ABS-DWV. Pipe cement and primer  
must conform to ASTM standard D2564 for PVC  
or D2235 for ABS. Improper venting can result in  
excessive levels of carbon monoxide which can  
result in severe personal injury or death!  
2
Use appropriate adapters to increase the 1 ⁄ in,  
38 mm air inlet collar to 3 in, 76 mm at the boiler,  
GT-150 & 200, Figure 2. Use a 2 in, 51 mm to 4 in,  
102 mm adapter on the GT-400. Terminate the air inlet  
system per the instructions found in the venting sections  
that follow.  
Figure 2 - Air Inlet System Attachment  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Page 5  
The GT condensing gas boiler is a high efficiency  
Table 2 - Vent & Air Intake System Sizing  
boiler utilizing induced power venting. It is designed  
to be vented directly to the outdoors using the venting  
methods and materials detailed in this section. The  
vent system must be both gas tight and watertight. All  
horizontal vent piping must be sloped back to the boiler  
a minimum of 1/4 in/ft, 21mm/m of vent.  
Model  
Number  
GT-150  
GT-200  
GT-400  
PGT-150  
PGT-200  
PGT-400  
Equivalent Combined Vent & Air Intake  
System Length (see note)  
105 ft, 32 m  
105 ft, 32 m  
4" - 30 ft, 9 m 6" - 65 ft, 20 m  
50 ft, 15 m  
50 ft, 15 m  
4" - 30 ft, 9 m 6" - 65 ft, 20 m  
NOTE:Steps must be taken to ensure that condensate  
does not collect in the venting system or the boiler  
will not operate properly.  
Note: Subtract 5 ft, 1.5 m, for each 90° elbow except for the vent and  
air intake elbows. These don’t need to be considered. The length of  
the air inlet system must never exceed the length of the vent system.  
The vent system length may exceed the air inlet system length by no  
more than 20 equivalent ft, 6.1 equivalent m.  
This boiler may be vented using the following materials,  
but local codes must be followed:  
GT150 & 200: 3 in, 76 mm, PVC Sch.40 solid core  
pipe, CPVC Sch.40 pipe, AL29-4C Flex StainlessVent  
or AL29-4C Rigid Stainless Vent.  
GT-400: 4 in, 102 mm or 6 in, 152 mm, PVC Sch.40  
solid core pipe, CPVC Sch.40 pipe, AL29-4C Flex  
Stainless Vent or AL29-4C Rigid Stainless Vent.  
HORIZONTAL  
DIRECT VENT SYSTEMS  
Read the information in the GENERAL VENTING  
GUIDELINES section. It is recommended that two  
elbows be used, so that the 1/4 in/ft, 21mm/m slope of  
the horizontal vent system does not affect the vertical  
plumb of the pipe connected to the boiler, Figure 4.  
CAUTION: All vent systems must be fully supported  
by the building structure. The vent connection and  
vent piping MUST be perfectly aligned to the boiler  
connection, Figure 3. It MUST NOT APPLY ANY  
WEIGHT OR LATERAL FORCETOTHE FLUE BOX or  
the flue box will be damaged voiding the warranty!  
Figure 4 - Vent System Attachment  
Appropriate adapters must be used to increase the  
2 in, 51 mm vent collar to 3 in, 76 mm at the boiler,  
GT-150 & 200, Figure 3. On the GT-400 the 4 in,  
102 mm long 4 inch diameter ABS pipe provided with  
the boiler must be inserted into the exhaust connection  
on the top of the boiler and tightened in place with the  
supplied clamp.  
Figure 3- Vent Pipe To Boiler Attachment  
When horizontal vent runs exceed 5 ft, 1.5m, they must  
be supported at 3 ft, 0.9 m, intervals with overhead  
hangers, 4 ft, 1.2 m for 6" pipe. The vent system must  
be pitched down, toward the boiler, 1/4 in/ft, 21mm/m.  
of vent. Structural penetrations must be made using  
approved thimbles.  
The maximum combined equivalent vent and intake  
pipe lengths are listed in Table 2. The length specified  
is the equivalent vent length added to the equivalent  
intake length.  
Page 6  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
The vent terminal shall not terminate:  
Consult your weather office for the maximum typical  
snowfall for your region. For example, in Boston MA the  
maximum typical snowfall is 12 in, 305 mm. Therefore  
the inlet must be 24 in, 610 mm, above any surface  
that will support snow and the exhaust must be 42 in,  
1067 mm, above this surface.  
• Directly above a paved sidewalk or a paved drive-way  
that is located between two buildings, and that serves  
both buildings;  
• Less than 7 ft, 2.1 m above grade where located  
adjacent to a paved driveway or public walkway.  
• Within 3 ft, 0.9 m, horizontally of a window or door that  
can be opened, or non-mechanical air supply inlet to  
any building.  
• Within 6 ft, 1.8 m, of a mechanical air supply inlet to  
any building or roof eve containing soffit openings.  
• Above a meter/regulator assembly within 3 ft, 0.9 m,  
horizontally of the vertical centerline of the regulator.  
• Within 6 ft, 1.8 m, of any gas service regulator vent  
outlet.  
• Less than 30 in, 762 mm, plus snow allowance above  
grade, or any surface that will support snow, ice, or  
debris. The exhaust must be a minimum of 18 in,  
457 mm, above the air inlet, and the air inlet must  
always be a minimum of 12 in, 305 mm. plus snow  
allowance above any surface that will support  
snow. A 24 in, 610 mm, plus snow allowance is  
highly recommended. Consult your weather office,  
for the maximum typical snowfall for your region.  
• Underneath a verandah, porch, or deck.  
The horizontal centerline distance between the inlet  
and exhaust terminals must be a minimum of 4 in,  
102 mm. If the horizontal distance between the inlet  
and exhaust is more than 12 in, 305 mm, increase the  
vertical separation by the same amount to prevent flue  
gas recirculation.  
For example, if the horizontal separation is 24 in,  
610 mm, a minimum vertical separation of 18 in,  
457mm, + 12 in, 305mm, = 30 in, 762 mm is required,.  
If the horizontal distance is greater than 6 ft, 1.8 m,  
no additional vertical spacing is required. The vertical  
separ-ation is never required to be greater then 36 in,  
914 mm.  
Figure 5 - Horizontal Terminal Locations  
• So situated that the flue gases are directed towards  
brickwork, siding, or other construction, in such  
a manner that may cause damage from heat or  
condensate from the flue gases.  
• Less than 3 ft, 0.9 m, from an inside corner of an  
L-shaped structure including walls and fences.  
Under normal operating conditions this appliance will  
produce a plume of water vapor, and should be taken  
into consideration when selecting an adequate vent  
terminal location. A 3 ft, 0.9 m, diameter stainless,  
plastic, or vinyl shield can be used to flash the exterior  
of the residence to protect is from damage.  
Separate Air Intake and Vent Terminals  
It is highly recommended that the air intake and vent  
terminals not be located where they will be exposed to  
normal prevailing winds. Both terminals must be on the  
same wall.  
The vent terminal must be a minimum of 18 in,  
457 mm above the air inlet terminal. The air inlet terminal  
must always be a minimum of 12 in, 305 mm, plus the  
snow allowance above any surface that will support  
snow, however a snow allowance of two feet is highly  
recommended Figure 5, 6, 7 & 8.  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Page 7  
When penetrating an outside wall the air intake and vent  
pipes must be constrained as shown in Figure 6. The  
openings through which the air intake and vent pipes  
pass must be properly sealed to prevent products of  
combustion from entering the building.  
For installations that have to exit the foundation below  
grade excavate the site as shown in Figure 8 to a point  
below where the pipes exit the building. Maintain the  
proper vent clearances as outlined above.Attach the vent  
and air intake pipes to the outside of the building using  
special bracket 82075. Ensure that the wall penetrations  
are properly sealed before backfilling the site.  
WARNING: Failure to properly install and seal  
the air intake and vent system can result in  
excessive levels of carbon monoxide which can  
cause severe personal injury or death!  
Figure 8 - Below Grade Installation  
Figure 6 - Wall Penetration Detail  
If required, the air intake and vent systems may be run  
along an outside wall, Figure 9, providing the following  
conditions are met:  
1. The maximum length on the outside of the building  
In some cases it may be necessary to attach the air  
intake and vent pipes to the outside wall for added rigidity,  
Figure 7. If this is the case, special bracket GT-82075  
must be ordered for each pipe. Proper clearances must  
be maintained.  
is not more than 20 ft, 6.1 m.  
2. All normal termination clearances are maintained.  
3. The entire vent system external to the building is  
insulated using closed cell foamed polyolefin tubing  
having a minimum wall thickness of 1/2 in, 13 mm.  
4. The air intake and vent systems are supported  
every 24 in, 610 mm.  
Figure 7 - Air Intake & Vent Pipe Attachment  
5. The air intake and vent systems are sloped 1/4 in/ft,  
21mm/m back toward the boiler.  
Page 8  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 9 - External Air Intake and Vent Systems  
Figure 11- Horizontal Concentric Terminal Location  
SUPPORTS EVERY 24 IN  
EXHAUST  
20 FOOT MAX OUTSIDE  
USING ONLY 3" PIPE ON  
THE 150 & 200 AND 4"  
PIPE ON THE 400  
INLET  
12 IN ABOVE MAXIMUM  
SNOW LINE  
The debris screens provided with the boiler must be  
installed in both the air intake and vent terminals. Install  
the screens in the outer most opening then glue a 1 in,  
25 mm length of pipe into the opening to retain them,  
Figure 10.  
Figure 10 - Debris Screen Installation  
Figure 12 - Vertical Concentric Terminal Location  
Concentric Air Intake and Vent Terminal  
GT-150 & 200 Only  
If a concentric terminal is used it must be Smith part  
number GT-82666 or York part number 1CT0303. The  
concentric terminal must be located at least 12 in, 305  
mm, above the normal snow line, Figure 11. Position the  
air intake pipe on the top or to the side to prevent rain  
from entering the boiler, Figure 13.  
When penetrating an outside wall the concentric terminal  
must be constrained as shown in Figure 13.The opening  
through which the concentric terminal passes must be  
properly sealed to prevent products of combustion from  
entering the building. The air intake of the boiler must  
be connected to the terminal!  
When terminals from multiple boiler installations exit a  
common wall the following conditions must apply:  
1. If limited to two terminals the horizontal centerline  
distance must be 4 in, 102 mm, or greater than  
24 in, 610 mm, to prevent flue gas recirculation.  
For more than two terminals located along a  
horizontal plane, the centerline distance between  
them must be 24 in, 610 mm, Figure 11.  
WARNING:Failure to properly install and seal the  
concentric terminal can result in excessive levels  
of carbon monoxide which can cause severe  
personal injury or death!  
2. If the terminals are located in a vertical plane the  
centerline distance between them must be at least  
48 in, 1220 mm, Figure 12.  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Page 9  
Figure 13 - Wall Penetration Detail  
Consult your weather office for the maximum typical  
snowfall for your region. For example, in Boston MA the  
maximum typical snowfall is 12 in, 305 mm. Therefore  
the inlet must be 24 in, 610 mm, above any surface that  
will support snow.The exhaust must be 42 in, 1067 mm,  
above this surface.  
Figure 15 - Two Pipe Through the Roof  
The debris screen provided with the boiler must be  
installed in the concentric terminal as shown in Figure  
14.  
Figure 14 - Debris Screen Installation  
The horizontal centerline distance between the inlet  
and exhaust terminals must be a minimum of 4 in,  
102 mm. If the horizontal distance between the inlet  
and exhaust is more than 12 in, 305 mm, increase  
the vertical separation by the same amount. For  
example, if the horizontal separation is 24 in, 610 mm,  
a minimum vertical separationof 30 in, 762 mm,  
is required, 18 in, 457 mm, + 12 in, 305 mm, = 30 in,  
762 mm. If the horizontal distance is greater then  
6 ft, 1.8 m no additional vertical spacing is required.  
The vertical separation is never required to be greater  
then 36 in, 914 mm.  
VERTICAL DIRECT VENT SYSTEMS  
Read the information in the GENERAL VENTING  
GUIDELINES section before proceeding.  
The GT can be vented vertically directly through the  
building’s roof or through a dormant chimney used as  
a chase, Figures 15 & 16. All roof penetrations must be  
properly flashed and sealed.  
A dormant chimney can be used as a chase through  
which the air intake and vent pipes can be run, Figure  
16. The chimney must not be connected to a fireplace,  
water heater or any other heating appliance.  
WARNING: Under no conditions, shall this boiler  
vent gases directly into a masonry chimney  
nor can an active chimney be used as a chase.  
Failure to comply with this warning can result in  
excessive levels of carbon monoxide which can  
cause severe personal injury or death!  
Figure 16 - Two Pipe Using Dormant Chimney  
Separate Air Intake and Vent Terminals  
The discharge of the vent terminal must point away  
from the pitch of the roof. The vent terminal must be a  
minimum of 18 in, 457 mm, above the air inlet terminal.  
The vent terminal must also be 24 in, 610 mm, above  
any roof surface within a horizontal distance of 10 ft,  
3 m. The air inlet terminal must always be a minimum  
of 12 in, 305 mm, plus the snow allowance above  
any surface that will support snow, however a snow  
allowance of 24 in, 610 mm, is highly recommended  
Figures 15 & 16.  
Page 10  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Install and seal a rain cap over the dormant chimney  
opening to prevent water from entering the building.  
Use only ABS, PVCsch.40, CPVC, or AL294C pipe for the  
air inlet and vent systems as stated previously. Ensure  
that the air inlet and vent system lengths are within the  
maximums specified in Table 2.  
Figure 18 - Multiple Concentric Through the Roof  
The debris screens provided with the boiler must be  
installed in both the air intake and vent terminals. Install  
the screens in the outer most opening then glue a 1 in,  
25 mm, length of pipe into the opening to retain them,  
Figure 9.  
Concentric Air Intake and Vent Terminal  
GT-150 & 200 Only  
If a concentric terminal is used it must be Smith part  
number GT-82666 or York part number 1CT0303. The  
concentric terminal must be located at least 24 in, 610  
mm, above the normal snow line, Figure 17.The building  
structure must support the air inlet and vent systems. All  
roof penetrations must be properly flashed and sealed.A  
dormant chimney can be used as a chase through which  
the air intake and vent pipes can be run. All previous  
instructions and warnings apply.  
CONDENSATE DRAIN  
WARNING: The condensate siphon must be  
connected to the boiler per the following  
instructions or combustion gases will enter  
the room. This can result in excessive levels  
of carbon monoxide which can cause severe  
personal injury or death!  
When terminals from multiple boiler installations exit a  
roof the following conditions must apply:  
This unit produces water as a byproduct of combustion.  
Much of this water condenses on the heat exchanger  
and in the venting system. Condensate must be drained  
from the boiler into a household drain as shown in  
Figure 19.  
If limited to two terminals the horizontal centerline  
distance must be 4 in, 102 mm or greater than 24 in,  
610 mm, to prevent flue gas recirculation. For more  
than two terminals located along a given plane, the  
centerline distance between them must be 24 in,  
610 mm, Figure 18.  
Figure 19 - Condensate Piping  
Figure 17 - Concentric Through the Roof  
NOTE: Check with your municipality, or local gas  
company to determine if disposal of untreated  
combustion condensate is permitted. If not, the  
condensate will have to be neutralized with lime  
crystals, marble chips or phosphate chips.  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Page 11  
The following are important rules that must be followed  
when constructing the condensate system:  
1. Connect the condensate trap to the drain using  
1/2 in, 13 mm, silicone, rubber, reinforced nylon, or  
PEX tubing. Long runs must be properly pitched  
and supported to prevent blockage.  
CAUTION: All systems must be flushed to remove  
sediment, flux, filings and other foreign matter.  
Use products such as Fernox “Superfloc” for new  
installations and CHR “Central Heating Restorer”  
for retrofits. Also add an inhibitor to the system  
water to prevent limestone and magnetite deposits  
from forming and to protect the boiler from galvanic  
corrosion. An inhibitor such as CHP, Central  
Heating Protector” from Fernox is recomended.  
2. Do not use nylon tubing, as it will collapse, blocking  
drainage. This could damage the boiler.  
3. Do not seal the opening between the condensate pipe  
and the condensate drain pipe, Figure 19. In the event  
of a blocked drain the opening will allow the condensate  
to overflow and prevent the boiler from flooding.  
4. Never have the drain pipe higher than the hole in the  
back cabinet, this will flood the boiler.  
5. Never allow the drain to freeze or become blocked.  
This will cause condensate to fill the combustion  
chamber resulting in a no heat condition and damage  
to the boiler.  
If connecting this boiler to a system containing  
cast iron radiation, be sure to add a strainer to the  
system to trap any sediment that may dislodge.  
Failure to do this could harm the heat exchanger  
and void the warranty!  
The use of non-oxygen barrier radiant tubing is  
acceptable, provided that non-ferrous pipe, valves,  
and fittings are used throughout the entire hydronic  
system. Failure to comply with these instructions  
will seriously damage the boiler, voiding warranty!  
6. NEVER use copper, steel, or galvanized piping in  
the construction of the condensate system.  
7. When a condensate pump is used or required, select  
a pump that is designed for residential furnaces.  
CAUTION: The boiler fittings cannot support any  
weight.The plumbing system must be supported by  
the building structure. A wrench must be used to  
hold the boiler fittings when installing the heating  
system piping. Failure to do so can seriously  
damage the boiler, voiding warranty!  
GENERAL PLUMBING GUIDELINES  
If connecting this boiler to a system containing cast iron  
radiation, be sure to add a strainer to the system to trap  
any sediment that may dislodge. Failure to do this could  
harm the heat exchanger and void the warranty! The  
use of non-oxygen barrier radiant tubing is acceptable,  
provided that non-ferrous pipe, valves, and fittings are  
used throughout the entire hydronic system.  
The GT hot water boiler comes from the factory ready  
to be piped to the heating system. The boiler must be  
used only in a Primary/Secondary pumping system to  
avoid cycling problems in systems that have poor flow  
or heating zones with very small capacities.  
CAUTION: All heating system piping must be  
installed in accordance with the ANSI/ASME Boiler  
and Pressure Vessel Code, Section IV. All applicable  
local codes and ordinances must also be followed. If  
the boiler is installed above any radiation elements  
it must be fitted with a low water cutoff device  
installed above the normal boiler water level!  
1
4
CAUTION: A 1 ⁄ in, 32 mm, primary loop system  
must be used for GT-150 & 200 models regardless of  
the configuration of the secondary system design.  
1
2
A 1 ⁄ in, 38 mm, primary loop system must be used  
for the GT-400. Failure to properly plumb the boiler  
may void the warranty!  
CAUTION: This boiler must have adequate water  
flowing through it whenever the burner is on.  
Failure to do this will damage the unit and void the  
warranty!  
Page 12  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Understand and follow the plumbing requirements  
provided in this section. Keep serviceability in mind  
when installing plumbing around the boiler cabinetry.  
Install fittings that will allow the system to be flushed if  
needed during annual check-ups. Add an inhibitor to the  
system water to prevent lime and magnetite deposits  
from forming, and to protect the boiler from galvanic  
corrosion. A minimum clearance of 1 in, 25 mm must  
be maintained between heating system pipes and all  
combustible construction.All heating system piping must  
be supported by suitable hangers not the boiler. The  
thermal expansion of the system must be considered  
when supporting the system. A minimum system  
pressure of 12 psig, 84 kPa must be maintained.  
Pressure Relief Valve  
Each boiler is equipped with a 30 psi pressure relief  
valve that must be piped in accordance with the ANSI/  
ASME Boiler and Pressure Vessel Code, Section IV to  
prevent scalding of persons with hot liquid or vapor in  
the event of a discharge, see Figure 20.  
Support the relief valve discharge piping to prevent  
strain on the valve body. Leave the open end of the relief  
valve discharge pipe visible for periodic inspection.  
NOTE: The discharge pipe diameter must be the  
same at the relief valve output diameter. Never  
restrict the outlet relief valve.  
Hot water boilers are designed to operate with airless  
water in the system. The GT boiler is provided with  
a 1/8 in, 3 mm, air vent located on the top of the unit.  
This air vent is intended to vent the boiler on initial  
startup. This device will NOT continuously vent air  
collecting in the primary loop and is not intended  
to be the primary venting device. The air scoop as  
shown in Figure 21 is the primary venting location. It is  
recommended that an additional air scoop be used in  
the secondary plumbing. If air continues to be a problem  
an air scrubber must be used.  
WARNING: Never install any type of valve  
between the boiler and the relief valve or an  
explosion causing extensive property damage,  
severe personal injury or death may occur!  
Figure 20 - Relief Valve Piping  
NOTE: Only inhibited propylene glycol solutions  
should be used if freeze protection is required.  
Avoid using mixtures greater than 30%, unless  
the size of the boilers’ circulator(s) is increased  
accordingly. Under no circumstances should a 50%  
mixture be exceeded.  
Non ASME GT-150  
All ASME Models  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Page 13  
Low Water Cut Off, LWCO  
Figure 22 - Boiler Head Loss  
If a LWCO is used ensure that the water line of the “Low  
Water Cutoffis at least 6 in, 152 mm, above the top of the  
boiler, Figure 21. It is recommended that the LWCO be  
situated so that it can be tested without removing water  
from the boiler. Tri-cocks and a gauge glass are highly  
recommended. Valves shall not be installed between  
the LWCO and the boiler. Use an air vent if installed as  
per our diagram to be used as a vacuum breaker and to  
eliminate air upon filling.  
GT-150  
GT-200  
GT-400  
60  
40  
20  
0
2
4
6
8
10 12 14 16 18 20 22 24 26 27  
Figure 21 - LWCO & Air Vent Piping  
GPM us  
Table 3 lists the recommended circulators for use as the  
primary and indirect loop pumps.  
Figure 23 shows the proper way to plumb a primary loop  
for single boiler installations.  
MULTIPLE BOILER PRIMARY LOOP  
Figure 24 shows the proper way to plumb a primary loop  
for multiple boiler installations.  
SECONDARY LOOP PLUMBING  
Figures 25 and 26 show some typical primary/ secondary  
piping systems. It is the responsibility of the installing  
contractor to determine which system best meets the  
need of the installation.Contractor modifications to these  
instructions may be required, based upon the existing  
piping and system design.  
PRIMARY LOOP PLUMBING  
This low mass boiler requires a continuous minimum  
water flow for proper operation. The heat exchanger in  
this boiler is more restrictive than a conventional boiler.  
The system pump must be sized to overcome the head  
loss of the boiler, Figure 22. Greater consideration must  
be given to the capabilities of the circulating pump(s) in  
the primary-loop. This includes the pump used for an  
indirect tank.  
Table 3 - Recommended Primary and Indirect Loop Circulators  
Minimum  
Flow  
GPM, L/s  
Max. Temp.  
Rise  
°F, °C  
Minimum Primary &  
Indirect Pump Size  
Grundfos  
Restriction  
Head Loss  
Model  
GT-150  
GT-200  
GT-400  
B&G  
NRF-33  
PL-36  
PL-36  
Taco  
0010  
0011  
0011  
7 ft at 6 GPM, 2.1 m at 0.4 L/s  
10 ft at 8 GPM, 3 m at 0.5 L/s  
10 ft at 20 GPM, 3 m at 1.25 L/s  
6, 0.4  
8, 0.5  
45, 25  
45, 25  
57, 45  
UP 26-64  
UP 26-99  
UP 26-99  
13, 0.8  
Page 14  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 23 - Single Boiler with Indirect Hot Water Heater  
NOTES:  
1. All piping and pumps must be supported so that no loads or stresses are applied to boiler heat exchanger. To make boiler service easy  
use Unions or flexible Vibration Isolation Kit.  
2. This boiler is provided with a 1/8" vent that is not intended for continuous system venting.  
3. For continuous system venting use a cast iron air scoop, for excessive air conditions use a Spirovent. Do not fire boiler until all air is  
purged from the system piping. Heat exchanger damage caused by air is not covered by warranty.  
4. See Table 3 for boiler pump flow requirements. This pump is wired to terminals C1-L2.  
5. See Table 3 for Indirect Water Heater pump flow requirements. This pump is wired to terminals AP-L2.  
6. Set pressure reducing valve to 12 PSI.  
7. Use 30 psi relief valve max. Locate where discharge will not cause injury or damage. Follow local codes.  
8. Add an inhibitor to protect system. (CHP from Fernox)  
9. Boiler circuit piping must be sized large enough to handle maximum flow through unit.  
10. Suggested piping. When installing an indirect water heater consult manufacturer’s manual for full details.  
11. Do not install any valves between the Vacuum Relief valve and the tank.  
12. Do not operate boiler with service valves closed isolating the boiler from the expansion tank.  
13. Failure to follow these instructions will result in heat exchanger damage: All flux and contaminants must be flushed from piping before  
connecting boiler. Do not connect this boiler to older systems with cast iron radiation without installing a fine particulate separator. TYP:  
Spirotrap Junior Model TDN 125 FT. Do Not use non-oxygen barrier radiant tubing.  
Notice: This drawings show suggested piping configuration and valving. Check with local codes and ordinances for specific requirements.  
Spirotrap  
Fine Particulate  
Separator  
Pump  
Gate Valve  
Ball Valve  
Backflow-Prevention Differential Pressure  
Pressure  
Reducing  
Valve  
Pressure  
Relief Valve  
Heating  
Load  
Drain Valve  
(Typ.)  
Check Valve  
Thermometer Union Automatic  
Air Vent  
Device  
Bypass Valve  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Page 15  
Figure 24 - Multiple Boiler Installation  
NOTES:  
1. All piping and pumps must be supported so that no loads or stresses are applied to boiler heat exchanger. To make boiler service easy  
use Unions or flexible Vibration Isolation Kit.  
2. This boiler is provided with a 1/8" vent that is not intended for continuous system venting.  
3. For continuous system venting use a cast iron air scoop, for excessive air conditions use a Spirovent. Do not fire boiler until all air is  
purged from system piping. Heat exchanger damage caused by air is not covered by warranty.  
4. See Table 3 for boiler pump flow requirements. This pump is wired to terminals C1-L2.  
5. Indirect Water Heater pump is wired to terminals AP-L2.  
6. Set pressure reducing valve to 12 PSI.  
7. Use 30 psi relief valve max. Locate where discharge will not cause injury or damage. Follow local codes.  
8. Add an inhibitor to protect system. (CHP from Fernox)  
9. Boiler circuit piping must be sized large enough to handle maximum flow through unit.  
10. Do not operate boiler with service valves closed isolating the boiler from the expansion tank.  
11. Failure to follow these instructions will result in heat exchanger damage. All flux and contaminants must be flushed from piping before  
connecting boiler. Do not connect this boiler to older systems with cast iron radiation without installing a fine particulate separator. TYP:  
Spirotrap Junior Model TDN 125 FT. Do not use non-oxygen barrier radiant tubing.  
Notice: This drawings show suggested piping configuration and valving. Check with local codes and ordinances for specific requirements.  
Spirotrap  
Fine Particulate  
Separator  
Pump  
Gate Valve  
Ball Valve  
Backflow-Prevention Differential Pressure  
Pressure  
Reducing  
Valve  
Pressure  
Relief Valve  
Heating  
Load  
Drain Valve  
(Typ.)  
Check Valve  
Thermometer Union Automatic  
Air Vent  
Device  
Bypass Valve  
Page 16  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 25 - Multiple Zones Using Circulators  
NOTES:  
1. All piping and pumps must be supported so that no loads or stresses are applied to boiler heat exchanger. To make boiler service easy  
use Unions or flexible Vibration Isolation Kit.  
2. This boiler is provided with a 1/8" vent that is not intended for continuous system venting.  
3. For continuous system venting use a cast iron air scoop, for excessive air conditions use a Spirovent. Do not fire boiler until all air is  
purged from the system piping. Heat exchanger damage caused by air is not covered by warranty.  
4. See Table 3 for boiler pump flow requirements. This pump is wired to terminals C1-L2.  
5. Indirect Water Heater pump is wired to terminals AP-L2.  
6. Set pressure reducing valve to 12 PSI.  
7. Use 30 psi relief valve max. Locate where discharge will not cause injury or damage. Follow local codes.  
8. Add an inhibitor to protect system. (CHP from Fernox)  
9. Boiler circuit piping must be sized large enough to handle maximum flow through unit.  
10. Do not operate boiler with service valves closed isolating the boiler from the expansion tank.  
11. Failure to follow these instructions will result in heat exchanger damage: All flux and contaminants must be flushed from piping before  
connecting boiler. Do not connect this boiler to older systems with cast iron radiation without installing a fine particulate separator. TYP:  
Spirotrap Junior Model TDN 125 FT. Do Not use non-oxygen barrier radiant tubing.  
Notice: This drawings show suggested piping configuration and valving. Check with local codes and ordinances for specific requirements.  
Spirotrap  
Fine Particulate  
Separator  
Pump  
Ball Valve  
Differential Pressure  
Bypass Valve  
Zone  
Valve  
Check Valve  
Automatic  
Air Vent  
Heating  
Load  
Drain Valve  
(Typ.)  
Expansion  
Tank  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Page 17  
Figure 26 - Multiple Zones Valves with Bypass Valve  
Note: Velocity noise may be  
a problem when the entire  
output of the system pump is  
flowing through the zone with  
the highest pressure drop.  
Adjust the differential bypass  
valve to eliminate noise.  
NOTES:  
1. All piping and pumps must be supported so that no loads or stresses are applied to boiler heat exchanger. To make boiler service easy  
use Unions or flexible Vibration Isolation Kit.  
2. This boiler is provided with a 1/8" vent that is not intended for continuous system venting.  
3. For continuous system venting use a cast iron air scoop, for excessive air conditions use a Spirovent. Do not fire boiler until all air is  
purged from system piping. Heat exchanger damage caused by air is not covered by warranty.  
4. See Table 3 for boiler pump flow requirements. This pump is wired to terminals C1-L2.  
5. Indirect Water Heater pump is wired to terminals AP-L2.  
6. Set pressure reducing valve to 12 PSI.  
7. Use 30 psi relief valve max. Locate where discharge will not cause injury or damage. Follow local codes.  
8. Add an inhibitor to protect system. (CHP from Fernox)  
9. Boiler circuit piping must be sized large enough to handle maximum flow through unit.  
10. Do not operate boiler with service valves closed isolating the boiler from the expansion tank.  
11. Failure to follow these instructions will result in heat exchanger damage. All flux and contaminants must be flushed from piping before  
connecting boiler. Do not connect this boiler to older systems with cast iron radiation without installing a fine particulate separator. TYP:  
Spirotrap Junior Model TDN 125 FT. Do not use non-oxygen barrier radiant tubing.  
Notice: This drawings show suggested piping configuration and valving. Check with local codes and ordinances for specific requirements.  
Spirotrap  
Fine Particulate  
Separator  
Pump  
Ball Valve  
Differential Pressure  
Bypass Valve  
Zone  
Valve  
Check Valve  
Automatic  
Air Vent  
Heating  
Load  
Drain Valve  
(Typ.)  
Expansion  
Tank  
Page 18  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Safe lighting and other performance criteria were met  
with the gas manifold and control assembly provided on  
the boiler when the boiler underwent tests specified in  
ANSI Z21.13/CSA 4.9.All gas connections MUST be leak  
tested before putting the boiler into operation.  
GAS SUPPLY PIPING  
The GT hot water boiler comes from the factory ready  
to be piped to the gas supply. The National Fuel Gas  
Code, ANSI Z223.1/NFPA 54 and local codes for gas  
piping requirements and sizing must be followed. If for  
any reason the boiler is not for the type of gas available  
at the installation site, call the nearest Smith distributor  
to resolve the problem.  
WARNING: Never use an open flame to test for  
gas leaks. Always use an approved leak detection  
method. Failure to comply with this WARNING  
could result in an explosion!  
Figure 27 depicts the proper way to connect the boiler to  
the gas supply piping.The manual shut-off valve MUST be  
installed in the supply piping. It should be approximately  
5 ft, 1.5 m, above the floor. Provide a sediment trap/drip  
leg at the bottom of the vertical section of the gas supply  
pipe. A ground joint union should be installed between  
the boiler gas controls and the supply piping. Each of  
these items is needed to ensure long life and ease of  
servicing. Always use a pipe sealant that is suitable for  
use with LP gas. Flexible gas piping is recommended if  
accepted by the local codes. Make sure the gas piping  
doesn’t hinder boiler access.  
Table 4 - Gas Pipe Capacity  
Pipe Length  
30' 40' 50' 60'  
Gas Pipe Capacity (ft3/hr)  
Nominal  
Iron Pipe 10'  
Size  
20'  
80' 100' 150'  
3/4"  
1"  
278 190 152 130 115 105 90 79 64  
520 350 285 245 215 195 170 150 120  
1050 730 590 500 440 400 350 305 250  
1600 1100 890 760 670 610 530 460 380  
1 1/4"  
1 1/2”  
Note:Maximum pipe capacity in ft3/hr is based on a 0.60 specific gravity  
gas at a pressure of 0.5 psig and a 0.3" WC pressure drop.  
CAUTION: Always use a wrench on the gas valve  
body when making gas connections to it. Never over-  
tighten the piping entering the gas valve body or the  
gas valve will be damaged voiding the warranty!  
Table 5 - Equivalent Pipe Length Chart  
Type of Pipe Fitting  
Tee Gate Valve  
(branch flow) (full port)  
Equivalent length of pipe fittings in feet  
Nominal  
Iron  
Pipe  
90°  
Gas Cocks  
Size  
CAUTION: The gas piping must be properly supported  
by the building structure and not by the boiler or the  
gas valve will be damaged voiding the warranty!  
3/4"  
1"  
2.06  
2.62  
3.45  
4.02  
4.12  
5.24  
6.90  
8.04  
0.48  
0.61  
0.81  
0.94  
1.25  
1.60  
2.15  
2.50  
1 1/4"  
1 1/2"  
Figure 27 - Gas Supply Piping  
Whenever the gas supply piping is pressure tested the  
boiler gas controls must be protected.If the test pressure  
is equal to, or less than 1/2 psi, 3.5 kPa, isolate the boiler  
by closing it’s manual shut off valve, see Figure 27. If the  
test pressure is greater than 1/2 psi, 3.5 kPa, disconnect  
the boiler and it’s individual shut-off valve from the gas  
supply piping.  
WARNING: Failure to protect the gas valve from  
excessive pressure can damage the gas valve  
which can cause a fire or explosion!  
Table 4 should be used to ensure that the gas supply  
piping is sized properly. If more than one appliance is  
supplied by the same supply pipe, the piping must be  
sized based on the maximum possible demand. Do not  
neglect the pressure drop due to pipe fittings. Table 5  
should be used in conjunction withTable 4 to ensure that  
the gas supply piping is sized properly.  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Page 19  
Before supplying 120 volts to the boiler, do a continuity  
check between all the wires and the ground to make sure  
that there are no electrical shorts that could damage the  
Sentry 2100 board.  
ELECTRICAL WIRING  
CAUTION: Label all wires prior to disconnection  
when servicing controls. Wiring errors can cause  
improper and dangerous operation!  
Never use magnetic tip screwdriver near the Sentry  
2100.  
The electrical connections to this boiler must be made  
in accordance with all applicable local codes and the  
latest revision of the National Electrical Code, ANSI/  
NFPA-70. Install a separate 120 volt 15 amp circuit  
for the boiler, Figures 28 and 29. A properly rated shut-  
off switch should be located at the boiler. The boiler  
must be grounded in accordance with the authority  
having jurisdiction, or if none, the latest revision of  
the National Electrical Code, ANSI/NFPA-70. Line  
voltage field wiring of any controls or other devices must  
conform to the temperature limitation of type T wire  
at 95°F, 35°C, above room temperature.Use copper  
conductors with a minimum size of #14 awg. Low voltage  
wiring must not be less than #18 awg with a neoprene,  
thermoplastic or other equivalent insulation having a  
minimum insulation thickness of 0.012 in, 3 mm.  
Verify that the wires connected to the Sentry TC and  
AC terminals are not grounded, or have any voltage  
applied to them, or voltage to ground - dry contact  
closure only.  
Ensure that the probe wire is not damaged.  
CAUTION: Damage to the electrical system  
components caused by improper wiring will void  
the warranty!  
Thermostat Installation  
ALWAYS follow the instructions included with the  
thermostat to be used to control the boiler. Proper  
location of the thermostat will ensure efficient trouble-free  
operation of the boiler.Mount the thermostat to an inside  
wall at a height approximately five feet above the floor.  
Schematic and ladder diagrams of the boilers wiring are  
shown in Figures 33 & 34.  
Avoid placing the thermostat in areas that will not provide  
an accurate measurement of the room temperature.  
Locating the thermostat behind a door, in an alcove,  
close to a source of thermal radiation or in a drafty area  
will cause poor or sporadic heating.  
CAUTION:The contact capacity of outputs C1 or Ap  
is 3 amps with a maximum inrush of 6 amps. If the  
amp draw of the pumps exceeds these maximums,  
a pump controller, or isolation relay must be used  
to prevent damage to the boiler. Damage caused by  
improper wiring will void the warranty!  
Figure 28 - Basic Heating System Wiring  
Page 20  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 29 - Basic Heating System and Indirect Tank Wiring  
Multiple 4 Wire Zone Valves  
Multiple Zones w/ Taco Valve Controller  
Figure 30 shows the basic multiple zoned system uses  
normally closed four (4) wire zone valves. This wiring  
system is used with the piping shown in Figure 26.  
Models ZVC403 to ZVC 406  
Figure 31 shows the basic multiple zoned system using  
normally closed 2, 3 or 4 wire Taco zone valves. This  
wiring system is used with the piping as shown in Figure  
26.  
When there is a call for heat the room thermostat closes  
the circuit to the zone valve motor, thus opening the zone  
valve. When the zone valve is opened, the end switch  
closes the circuit between terminals T and C on the  
Sentry 2100 control.The Sentry 2100 provides power to  
the primary and secondary pumps via terminal C1. Once  
these pumps are on, the burner fires.  
When there is a call for heat the room thermostat closes  
the circuit between the TT terminals on the Taco zone  
controller. The controller energizes the appropriate zone  
valve and closes the circuit between terminalsT and C on  
the Sentry 2100 control.The Sentry 2100 provides power  
to the primary and secondary pumps via terminal C1.  
Once the room thermostat is satisfied, it breaks power  
to the zone valve motor.The end switch opens the circuit  
between terminals T and C shutting down the pumps  
and the burner.  
Once these pumps are on, the burner fires.  
Once the room thermostat is satisfied, it breaks power  
to the zone valve motor.The end switch opens the circuit  
between terminals T and C shutting down the pumps  
and the burner.  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Page 21  
Figure 30 - Multiple 4 Wire Zone Valves  
Page 22  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 31 - Multiple Zones w/ Taco Valve Controller, Models ZVC403 to ZVC 406  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Page 23  
Multiple Zone Pump Controller  
Once the room thermostat is satisfied, it breaks power  
to the TT terminal of the pump controller de-energizing  
the XX contacts. The circuit between terminals T and C  
opens shutting down the pumps and the burner.  
Models Taco SR504, Argo ARM 861 Series  
Figure 32 shows the basic multiple zoned system using  
circulating pumps. This wiring system is used with the  
piping as shown in Figures 25.  
When there is a call for heat the room thermostat  
closes the circuit between the TT terminals on the pump  
controller. The controller energizes the appropriate  
circulating pump and closes the circuit between terminals  
T and C on the Sentry 2100 control. The Sentry 2100,  
provides power to the primary pump via terminal C1.  
Once these pumps are on, the burner fires.  
Figure 32 - Multiple Zone Pump Controller, Models Taco SR504, Argo ARM 861 Series  
Page 24  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 33 - Boiler Ladder Diagram  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Page 25  
Figure 34 - Boiler Connection Diagram  
Page 26  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 37 - 2100T Display Screen  
SENTRY 2100T CONTROLLER  
CAUTION: The T4.0 controller can only be used  
on the GT-400 and the T2.0 on the GT-150 & 200.  
Misapplication of the controller will result in  
improper boiler operation.  
The Sentry 2100T controller is the central controller for  
the GT boiler. The Sentry handles all of the combustion  
logic, along with the energy management functions.  
The Sentry 2100T operates in two different modes,  
Conventional or Reset, see Figures 35 & 36.The mode is  
automatically determined by the presence of the outdoor  
sensor. When the Sentry 2100T detects the presence of  
the outdoor sensor the controller will operate in the Reset  
Mode.If the outdoor sensor is not installed, the controller  
will operate in the Conventional Mode.  
Burner/Bruleur - Indicates that the ignition system is  
activated.  
Circ. - Indicates that the heating pump is energized.  
NOTE: If the outdoor sensor is connected after the  
boiler has been started power to the boiler must be  
shut off and then turned back on.  
Circ. Aux.- Indicates a call for DHW, and Indirect pump  
or 3-way valve is activated.  
Boiler Modulation  
Thermostat Demand - Indicates that terminals T-C are  
The GT boiler employs a pneumatic modulation system.  
This modulation system increases or decreases the  
speed of the blower to meet the heating demand. The  
gas valve pressure regulator senses the air pressure  
and adjusts the gas flow to ensure correct combustion.  
The term “Set Point” is used to indicate the desired  
temperature that the GT will maintain by increasing or  
decreasing the input.  
closed, iniating a call for heat.  
The LED screen will display one of four values.A light will  
illuminate above the function to indicate what information  
is being displayed.  
Water Temp - Indicates that the display is showing the  
boiler water temperature.  
Indirect Water Heaters  
Air - if the air sensor is used.When illuminated, indicates  
that the display is showing outdoor air temperature.  
The Sentry 2100 comes with an input and output for  
a 120-volt indirect pump. When the A and C terminals  
are closed, dry contact, the boiler will go immediately  
to indirect domestic mode, whereby the indirect pump  
is activated, and the boiler will modulate to the LO  
setpoint.  
Gas InputValue - Indicates the current input level.Figure  
38 must be used to determine the actual input. GT-150  
use 46 to 240, GT-200 use 40 to 240 and GT-400 use  
35 to 195.  
Sentry Display  
The Sentry 2100T contains four green lights that illuminate  
to indicate the boilers state of operation, Figure 37.  
DHW Temp. - indicates that there is a call for domestic  
hot water.  
Figure 35 - Conventional Mode Operation Chart  
T-C & A-C Open  
T-C Closed & A-C open  
T-C Closed & A-C Closed  
T-C Open & A-C Closed  
Condition  
Set Point  
Burner On  
Burner Off  
Heat Circ.  
Aux. Circ.  
Standby  
Off  
Off  
Heating Only  
HI  
HI - DIF  
HI + 10  
On  
Domestic Only  
Domestic Only  
L0  
LO-10  
200°F  
Off  
L0  
LO-10  
200°F  
Off  
Off  
On  
On  
Figure 36 - Reset Mode Operation Chart  
T-C & A-C Open  
T-C Closed & A-C open  
T-C Closed & A-C Closed  
T-C Open & A-C Closed  
Condition  
Set Point  
Burner On  
Burner Off  
Heat Circ. (C1)  
Aux. Circ. (Ap)  
Standby  
Off  
Off  
Heating Only  
Domestic Only  
Domestic Only  
Calc.  
HI  
L0  
LO-10  
200°F  
Off  
L0  
LO-10  
200°F  
Off  
Calc  
HI  
HI  
- DIF  
+ 10  
Calc  
On  
Off  
On  
On  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Page 27  
Figure 38 - Input Conversion Chart  
Display Data - Input conversion chart  
400  
350  
300  
250  
200  
150  
100  
50  
GT-150  
GT-400  
GT-200  
0
240  
215  
190  
165  
140  
115  
90  
65  
48  
40  
LED Display  
Setting Sentry 2100T control  
Recommended Settings  
Programming is accomplished by a series of three push  
buttons located on the bottom side of the control. To  
enter the programming mode, press the function key  
once, “RUN” should be displayed on the screen.To scroll  
through the various menu options depress .To alter the  
value of a menu option press “Function” once while the  
menu option is displayed, and the current value will be  
displayed, then use for up, and for down, until the  
desired value is obtained. To enter the selected value  
press “Function”, which will return to the menu and store  
the new setting.When all desired values are set, scroll to  
the “RUN” menu option, and press Function, which exits  
the Programming Mode and initiates normal operation.  
If the control is left in the Program Mode longer than 30  
seconds without receiving any input the unit will turn off.  
Press “Function” once to continue programming or to  
restart boiler operation.  
When programming the Sentry 2100T determine  
what the hottest boiler temperature required for the  
coldest day will be. This will be the HI SETTING. If  
an indirect tank is used for domestic hot water, DHW,  
determine the minimum boiler temperature required  
to ensure an adequate supply of hot water. This is the  
LO SETTING. The LO SETTING is only used during  
a call for DHW, when A and C terminals are closed.  
Set the LO to the temperature required for the Indirect  
Water Heater. 140 °F, 60°C or at least 30°F, -1°C higher  
than the indirect Aquastat is recommend.  
WARNING:Proper control settings must be used  
to prevent water supplied for domestic use from  
exceeding 130°F, 54°C or a scald injury will occur!  
When higher water temperatures are required  
for appliances such as a dishwasher, a mixing  
valve or some other tempering means must be  
installed. Households with small children may  
require water temperatures less than 120°F, 49°C.  
Local codes must be complied with!  
Below is a list of functions and a description of what  
they control:  
RUN - Stores Values & initiates  
LO - Boiler Setpoint for DHW, 80 - 200°F, 27 - 93°C  
HI - Boiler Setpoint for Heating, 80 - 200°F, 27 - 93°C  
DIF - Differential, 1 - 40°F, -17°C - 4°C  
RES - Sets Outdoor Reset Curve Slope,  
70°F, 21°C to HI  
Table 6 - Recommend System Temperatures  
Hi  
Dif  
RES  
System  
°F, °C  
°F, °C  
°F, °C  
85, 29  
85, 29  
85, 29  
Finned Tube Baseboard  
Cast Iron Radiators  
Radiant  
190, 88  
150, 66  
130, 54  
20, 11.7  
20, 11.7  
20, 11.7  
SFS - Sets Starting Gas Input Value, 60 to 100  
GT150 & 200 is 60 to 100  
GT-400 is 45 to 90  
HFS - Sets Highest Gas Input Value, 100 to 240  
GT-150 & 200 is 100 to 240  
Outdoor Sensor (10K)  
The outdoor sensor should be installed to take advantage  
of the energy saving features of the Sentry Controller.  
Install the sensor on the north, or coldest side of the  
building out of direct sun. It must be at least 10 ft, 3 m  
from the vent terminal or other source of heat.  
GT-400 is 90 to 195  
LFS - Sets Lowest Gas Input Value, 40 to 100  
GT-150 & 200 is 40 to 100 (see note)  
GT-400 is 35 to 90  
NOTE: LFS must not be set below 48 on the GT150  
model. To start the control operation return to  
“RUN” on the menu and press “Function”. Normal  
operation will begin.  
Page 28  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Determining Reset Temperature HICalc  
NOTE:The design temperature is 0°F, -18°C outside  
air, so at 0°F, -18°C or less, the hi setting is used,  
and not surpassed.  
Once the Sentry 2100T control identifies the presence  
of a good outdoor sensor, the control will automatically  
reduce the HI setting based upon the outdoor  
temperature. For example, if Hi = 200°F, 93°C, RES =  
70°F, 21°C and the Air Temperature = 32°F, 0°C, the HI  
setpoint, HICalc, would be calculated as follows:  
Figures 39 & 40 are examples of reset temperatures  
based upon different set points and outdoor air temper-  
atures. The vertical axis is the water temperature that  
the boiler will maintain and is also the Hi setting of the  
Sentry 2100T control.The Horizontal axis is the outdoor  
air temperature.  
RESET RATIO  
= (High Setting - RES)/RES  
= (200°F, 93°C - 70°F, 21°C) /70°F, 21°C  
= 1.85  
RESET TEMPERATURE HICalc  
=[(RES-Outdoor Air) x Reset Ratio] + RES  
=[(70°F, 21°C - 32°F, 0°C) x 1.85] + 70°F, 21°C  
=[70.6°F, 21°C] + 70°F, 21°C  
=140.6 F, 42°C  
Figures 39 - Reset Curve For Res = 85 °F, 29°C  
Figures 40 - Reset Curve For Res = 70 °F, 21°C  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Page 29  
Do not use this appliance if any part has been under  
water. Immediately call a qualified service technician  
to inspect the appliance and to replace any part of the  
control system and any gas control that has been under  
water.  
BOILER SET UP  
NOTE: Before starting the boiler, turn off the  
electrical supply going to it. Make sure that gas is  
available at the gas valve inlet. Open the valves in  
the hot water return and supply piping. Failure to  
take these precautions will prevent the boiler from  
operation properly.  
NOTE:The GT was tested with Natural Gas having a  
heating value of 1020 BTU per cubic foot. For areas  
with lower heating values, a combustion test is  
required to obtain optimum operation.  
Fill the boiler and all of the radiation with water. Make  
sure that the system is completely purged of air, see  
GENERAL PLUMBING GUIDELINES.  
WARNING: The input Screw MUST NEVER BE  
ADJUSTED without verifying proper combustion  
with a calibrated combustion analyzer. Failure to  
comply with this warning can result in excessive  
levels of carbon monoxide which can cause  
severe personal injury or death!  
Review these instructions and make sure that the boiler  
installation complies with ALL of the instructions up to  
this point.  
OPERATING INSTRUCTIONS  
Table 7 contains the range for the CO, CO2 and NOx that  
should be in a flue gas sample of a properly operating  
boiler at maximum input.  
The GT boiler employs a pneumatic modulation system.  
This modulation system increases or decreases the  
speed of the blower to meet the heating demand. The  
gas valve pressure regulator senses the air pressure and  
adjusts the gas flow to ensure correct combustion.  
Table 7 - Normal Flue Gas Composition  
Natural Gas Propane  
WARNING: Before operating read and under-  
stand the instructions contained in this manual.  
Do not attempt to operate this boiler if it has  
not been installed in accordance with the  
guidelines set forth in this manual. Read and  
fully understand the operating instructions in  
the “For Your Safety Read Before Operating”  
section of this manual. Failure to comply with  
this WARNING could result in a fire or explosion  
causing severe personal injury or death!  
Carbon Dioxide CO2 %  
Carbon Monoxide CO ppm  
NOX ppm  
Note: At maximum fan speed of 240 on the Sentry  
display  
8-9.5  
25-175  
10-50  
9-10.5  
25-175  
10-50  
Should overheating occur or the gas supply fail to shut  
off, do not turn off or disconnect the electrical supply to  
the pump. Instead, shut off the gas supply at a location  
external to the appliance.  
Page 30  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
The gas supply pressure to the boiler while running  
at maximum rate must be between 4 to 9 in, 102 to  
229 mm, W.C.for natural gas installations;9 to 12 in, 229  
to 305 mm, W.C. for propane installations.This pressure  
can be measured on the gas valve using a manometer,  
Figure 41 or 42. Ensure that the regulator is capable of  
maintaining this pressure under all operating conditions.  
The gas valve is also equipped with a manifold pressure  
port, Figure 41 or 42.  
Ignition System  
A. Connect a manometer to the line pressure port  
shown in Figure 41 or 42. Make sure that the gas  
supply piping has been purged of air and that all  
gas joints up to the gas valve have been thoroughly  
checked for leaks. Wait at least five minutes for any  
gas to dissipate before turning on the electrical  
power.  
Figure 41 - Gas Valve Layout, GT-150 & 200  
B. Read, understand and follow the operating  
instructions below.  
C. Raise the thermostat at least 5 degrees above the  
room temperature. The boiler should enter the pre-  
purge mode before energizing the silicon carbide  
igniter. Once the igniter is hot, the main gas valve  
will open and the burner should light. If the burner  
fails to light the system will make three more ignition  
attempts. If the burner has not lit after the last  
ignition try, the gas valve will close and the system  
will go into lock out. DO NOT attempt to reset the  
system until the ignition system has been inspected  
and the problem resolved. Once the problem has  
been resolved and 5 minutes have passed since  
the last ignition attempt, reset the system by turning  
the thermostat to it’s lowest setting and then back  
to where it was or by momentarily interrupting the  
electrical power to the boiler.  
Figure 42 - Gas Valve Layout, GT-400  
D. With the burner in operation close the manual shutoff  
valve in the gas supply line. As soon as the burner  
flame goes out, open the manual shutoff valve. A  
normal ignition sequence should take place.  
Manifold Pressure  
Line Pressure  
E. With the burner in operation, interrupt the power to the  
control circuit by lowering and raising the thermostat.  
A normal ignition sequence should follow.  
Input Screw  
F. To test the ignition safety shutoff device, close the  
manual shutoff valve in the gas supply line.Within 6  
seconds of main burner flame extinction, the main  
gas valve solenoid should close with an audible noise.  
The igniter should glow and make three attempts at  
ignition. After unsuccessfully attempting to light the  
burner the ignition module should lock out.  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Page 31  
Figure 43 - Operational Flow Chart  
120v Power  
Applied  
Displays version  
t2.0 or t4.0  
Boiler in  
standby Mode  
Indirect thermostat or flow  
Thermostat End switch  
or relay closes T-C  
(Call for Heat)  
switch closes A-C  
(Call for Domestic)  
Combi model  
Combi or  
indirect  
Awaiting  
Input  
Energizes 3 way  
diverter valve  
Indirect  
Water  
Heater  
Energizes Primary  
Pump (C1)  
Energizes Indirect Pump  
(Ap) turns off C1  
Energizes Primary  
Pump (C1)  
Air  
Switches  
Closed  
Error  
ASC  
Sentry 2100  
(Call for Ignition)  
Sentry 2100  
24 V  
Open  
Sentry 2100  
24 Volt signal  
to blower  
Sentry 2100  
Fan to SFS (75)  
Manifold & Stack Limit  
(GT 150 & GT 200)  
Open  
Closed  
Open  
Hi pressure  
N. C. switch on  
GT 400 only  
Manifold Limit & Flow  
Switch  
NC  
NO  
Closed  
(GT 400)  
Error  
ASO  
24 V  
Prepurge  
IGNITION MODULE  
Power to ignitor  
120v from S1  
S1 L1 L2 S2  
W
MV GND  
Igniter warm-up  
5 seconds  
Three retries  
for flame  
Flame Probe  
Signal <1 microA  
Power to Gas valve  
Less than  
1.0 microA  
Sentry 2100  
Modulates fan based  
upon setpoint and  
programming  
Greater than 1.0 microA  
Call for flame ends  
Page 32  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
FORYOUR SAFETY READ BEFORE OPERATING  
WARNING: If you do not follow these instructions exactly, a fire or explosion may result  
causing property damage, personal injury or loss of life.  
A. This appliance does not have a pilot.It is equipped  
with an ignition device which automatically lights  
the burner. Do not try to light the burner by hand.  
• If you cannot reach your gas supplier, call the fire  
department.  
C. Use only your hand to push in or turn the gas  
control knob. Never use tools. If the knob will not  
push in or turn by hand, don’t try to repair it, call  
a qualified service technician. Force or attempted  
repair may result in a fire or explosion.  
B. BEFORE OPERATING smell all around the  
appliance area for gas. Be sure to smell next to  
the floor because some gas is heavier than air  
and will settle on the floor.  
WHAT TO DO IF YOU SMELL GAS  
• Do not try to light any appliance.  
• Do not tough any electric switch; do not use any  
phone in your building.  
• Immediately call your gas supplier from a neighbor’s  
phone. Follow the gas suppliers instructions.  
D. Do not use this appliance if any part has been  
under water. Immediately call a qualified service  
technician to inspect the appliance and to replace  
any part of the control system and any gas control  
that has been under water.  
OPERATING INSTRUCTIONS  
1. STOP! Read the safety information above.  
2. Turn off all electric power to the appliance.  
3. Set the thermostat to lowest setting.  
5. Remove control access panel.  
6. Turn the manual gas supply shut off valve clock-  
wise  
to the full “OFF” position.  
7. Wait five (5) minutes to clear out any gas. Then  
smell for gas, including near the floor. If you  
then smell gas STOP! Follow “B” in the safety  
information above. If you don’t smell gas, go to  
the next step.  
4. This appliance is equipped with an ignition device,  
which automatically lights the burner. Do not try  
to light the burner by hand!  
GAS IN  
8. Turn the manual gas supply shut off valve  
LINE  
PRESSURE  
counter-clockwise  
to “ON”.  
9. Replace control access panel.  
10. Turn on all electric power to the appliance.  
11. Set thermostat to desired setting.  
MANIFOLD  
PRESSURE  
12. If the appliance will not operate, follow the instruct-  
tions “TO TURN OFF GAS TO APPLIANCE” and  
call your service technician or gas supplier.  
INPUT  
SCREW  
TO TURN OFF GAS TO APPLIANCE  
1. Turn off all electric power to the appliance.  
2. Set the thermostat to lowest setting.  
3. Remove control access panel.  
4. Turn the manual gas supply shut off valve clock-  
wise  
to the full “OFF” position.  
5. Replace control access panel.  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Page 33  
Gas Pressure Adjustment  
BOILER CHECKING  
Optimum results are obtained when the boiler is operated  
at its full input rating. If adjustment is necessary the  
following steps must be followed:  
& ADJUSTMENT  
Input Rate  
Gas appliances are rated based on sea level operation  
with no adjustment required at elevations up to 2000 ft,  
610 m. At elevations above 2000 ft, 610 m, input ratings  
should be reduced by 4% for each 1000 ft, 305 m, above  
sea level. Check the input rate as follows:  
1. Connect a flue gas analyzer to the vent pipe.  
2. Rotate the input adjustment screw clockwise to  
decrease the manifold pressure, counterclockwise  
to increase it, Figure 41 or 42. The input screw on  
the GT-150 & 200 is a multi turn needle valve. From  
fully open to fully closed is approximately 17 turns.  
A typical adjustment is 0 to 1 turn for natural gas,  
0 to 3 turns for LP. The input screw on the GT-400  
turns a geared ball valve with a 4 to 1 ratio.Two turns  
will take the valve from fully open to fully closed.  
0 to 1/4 turn is a typical adjustment. Never force  
the input adjustment screw or the gas valve will be  
damaged!  
NATURAL GAS:  
1. Turn off all other gas appliances that use the same  
gas meter as the boiler.  
2. Call the gas company for the gas heating value.  
3. Start the boiler and let it run for 15 minutes.  
4. Using the gas meter and a stopwatch, clock the time  
that it takes to burn 10 cubic feet of gas and divide  
the time by 10.  
3. For natural gas the CO2 reading should fall between  
8% and 9.5% with a CO reading of less than 175  
ppm air free. For LP gas the CO2 reading should fall  
between 9% and 10.5% with a CO reading of less  
than 175 ppm air free.  
5. Insert the heating value and the time, in seconds,  
into the formula below.  
Input Rate = Heating Value(Btu/ft3)(3600 s/hr)  
Flow Rate(s/ft3)  
Main Burner Flame  
EXAMPLE: If the heating value = 1000 Btu/ft3  
and the flow rate = 18 s/ft3  
A properly adjusted main burner flame will produce a  
tight blue flame pattern about 1/2 in, 13 mm, tall from  
the burner’s surface, Figure 44. A yellow floating or tall  
stringy flame is not normal and must be corrected.  
Input Rate = (1000 Btu/ft3)(3600 s/hr)  
18 s/ft3  
WARNING:Yellow, floating flames indicate a lack  
of combustion air. DO NOT operate the boiler until  
the problem is solved or severe personal injury  
or death may occur!  
Input Rate = 200,000 Btu/hr  
If the computed rate deviates by more than 5% from the  
rated input value of the unit adjust the gas valve pressure  
according to the GAS PRESSURE ADJUSTMENT  
instructions that follow.  
Figure 44 - Burner Flame  
PROPANE GAS:  
The input rate for LP units is factory set based on the  
orifice size. Use the factory supplied kit to convert the  
boiler to LP. A combusiton analyzer must be used to  
ensure that the CO2 reading falls between 9% and 10.5%  
with a CO reading of less than 175 ppm air free.  
CAUTION: Never increase the input to the boiler  
above that for which it is rated. Doing so can cause  
premature failure of the boiler!  
Thermostat Adjustment  
Set the heat anticipator to 1.1 amps when controlling  
the boiler directly. For zoned systems set the heat  
anticipator to match the amp draw of the zone valves or  
pump relays.  
Page 34  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
1. Close the manual shutoff valve in the gas supply line  
and turn off electrical power to the boiler.  
2. Remove the front and left jacket panels.  
3. Disconnect the wires going to the igniter, flame rod,  
ground rod, blower and gas valve.  
4. Carefully disconnect the gas piping at the union,  
Figure 27.  
5. Carefully disconnect the air inlet piping at the valve,  
Figure 2.  
BOILER MAINTENANCE  
The boiler should be cleaned and inspected once a year,  
before each heating season.  
CAUTION: Servicing, inspection and adjustment  
must be done by a trained technician in accordance  
with all applicable local and national codes. Improper  
servicing or adjustment could damage the boiler!  
6. Remove the nuts used to attach the burner to the  
heat exchanger.  
Controls  
Use a soft brush and/or a vacuum cleaner to ensure that  
the electrical components are free from dust or deposits  
that would impair the boiler’s performance.  
7. Carefully slide the burner out of the unit.  
8. Inspect the burner for damage or signs of  
deterioration. Use a brush or vacuum cleaner  
to remove any debris from the burner ports.  
9. DO NOT install a damaged or badly corroded burner,  
replace it.  
Heat Exchanger Cleaning  
Natural Gas - once every two years.  
Propane - once per year.  
10. Inspect the ceramic burner disc for signs of damage  
or deterioration and replace it if necessary.  
11. Inspect the burner door gasket for signs of damage  
or deterioration and replace it if necessary.  
12. Inspect the ignition components for signs of damage  
or deterioration and replace them if necessary.  
13. Reassemble the unit following the removal steps in  
reverse order.  
The burner door should be removed so the combustion  
chamber can be inspected for flue gas blockage,  
see BURNER REMOVAL & REPLACEMENT below.  
Once the burner has been removed remove the heat  
exchanger baffle. Blockage of the heat exchanger  
will reduce the boiler’s capacity/firing rate and can  
negatively impact on how smooth and efficiently the  
burner lights. Vacuum out any loose build-up and clean  
the heat exchanger surface with an appropriate cleaner  
for combustion chambers such as Sotin 300. Use a  
nylon or other non-metallic brush to loosen the sulfate  
incrustations and any other contaminates. Rinse with  
water allowing the solution to exit via the condensate  
drain. This process may warrant removing the insulation  
disc from the back of the heat exchanger.  
14. All gas connections MUST be leak tested before  
putting the boiler into operation.  
WARNING: Never use an open flame to test for  
gas leaks. Always use an approved leak detection  
method. Failure to comply with this WARNING  
could result in an explosion!  
15. Confirm proper operation of the boiler and replace  
the jacket panels.  
Heat Exchanger Flushing  
Listen for water flow noises that indicate a drop in the  
boiler water flow rate. The boiler and hydronic system  
may need to be flushed to eliminate hard water scale. A  
de-scalar such as Fernox DS-40 is recommend.  
Condensate System  
Ensure that the condensate removal system is clean,  
sound and working properly.  
Vent System  
Burner Removal & Replacement  
The entire vent system must be thoroughly inspected  
for any signs of blockage, damage or leaks. Immediately  
replace any unsound vent system piping. Remove any  
foreign matter in or near the vent and air inlet terminals  
that might obstruct them.  
WARNING: The ceramic door disc on the rear  
of the burner contains crystalline silica. Wear  
proper respiration protection when servicing  
the burner and gently handle the burner and  
its disc to prevent inhalation of airborne fibers.  
Crystalline silica fibers have been identified as  
carcinogenic, or possibly carcinogenic when  
inhaled.  
Low Water Cutoff  
If the system has been equipped with a low water cut-off  
device, follow the manufacturer’s instructions for cleaning  
and to confirm proper operation  
CAUTION:The burner should not be removed unless  
there is a problem with it. Careless handling can  
damage the burner!  
Relief Valve  
The relief valve should vent water when the test lever is  
lifted. It should not weep or discharge water at normal  
system pressure. NEVER try to clean or repair the relief  
valve! If the valve fails replace it!  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Page 35  
Aquastat High Limit  
Figure 46 - Gas Valve Rotation  
The aquastat high limit controls the maximum water  
temperature in the boiler. If the water temperature  
reaches the set temperature before the demand for heat  
has been met, the aquastat high limit should shut the  
burners off. The outlet water temperature should never  
exceed 220°F, 104°C. If the aquastat high limit fails to  
function properly replace it.  
NEW LOCATIONS  
FOR SCREWS  
t u o u t  
WALL HUNG CONVERSION  
This boiler is certified to be either mounted on the floor  
as supplied, or mounted on a wall.  
REMOVE SCREWS  
1/2 IN THREADED  
CONNECTION  
AND ROTATE 90°  
RE-INSTALL SCREWS  
IN NEW LOCATIONS  
For wall mounting, perform the following steps.  
1. Ensure that the desired location provides adequate  
room for the clearance, see Table 1, venting, and  
servicing.  
2. Remove the right stainless steel panel, and  
discard.  
3. Youwillseethatunderneaththepanel, theboilerframe  
has mounting holes, designed for wall attachment.  
4. The boiler must be mounted so the lag bolts enter  
the studs of the wall. If this is not possible use a 3/4"  
thick of plywood approximately 24 in, 610 mm, wide  
by 36 in, 914 mm, high.  
10. Reattach the gas valve-venturi assembly to the side  
of the blower making sure the gasket is correctly  
orientated.  
11. Re-install the Air Inlet Pipe assembly and Metering  
elbow from the gas valve-venturi assembly, in the  
vertical position, Figure 47.  
Figure 47 - Air Inlet Pipe Installation  
5. Install two #14-3" lag bolts three quarters of the  
way into the surface, to the height you desire for  
mounting.  
6. Lift the boiler onto the wall, and tighten the top lag  
bolts.  
7. Once the unit is level, install the bottom two #14-3"  
lag bolts.  
8. Remove the Air Inlet Pipe assembly and Metering  
elbow from the gas valve-venturi assembly, Figure  
45.  
12. Install the gas line as per Figure 48 and follow  
the instructions in the GAS PIPING section of this  
manual.  
Figure 45 - Air Inlet Pipe Removal  
Figure 48 - Gas Supply Piping  
9. Remove the two screws attaching the gas valve-  
venturi assembly to the side of the blower and rotate  
the valve 90° so the 1/2" threaded connection is  
pointing down, Figure 46. Pay close attention to how  
the cork gasket is aligned.  
Page 36  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
TROUBLE SHOOTING  
This section is intended to assist the service technician in detecting and correcting common errors.The Sentry 2100  
is equipped with an internal diagnostic system that verifies control operation.The following series of error codes has  
been developed to aid in diagnosing control problems:  
Problem  
Detected Problem  
Solution  
ER1 On Display  
The Safety High Limit of 215°F, 102°C,  
has been reached.  
1. Check to see if water is dripping on the  
sensor.  
2. Reduce the Hi setting (and/or) ensure  
that there is proper water circulation in  
the system.  
ER2 On Display  
Water Probe... The water probe is  
transmitting an invalid signal - closed  
circuit.  
Check wiring  
ER3 On Display  
Water probe...Sentry is sensing an open  
Check wiring. (Note: ER3 will be  
circuit at water probe. Or, the wiring to the displayed if temperature sensed is  
outdoor probe is grounded.  
less then 32°F, 0°C.)  
Note: If problem is corrected by resetting  
power, Sentry control had locked-up;  
contact Smith.  
ER5 On Display  
DHW Problem  
The control has determined an Indirect  
water heater problem; the boiler has  
cycled off 10 times during a single call  
for domestic. The Indirect call will now be  
ignored until power is reset or the indirect  
call is interrupted.  
1. Not enough flow to keep boiler from  
tripping on limit. Verify that a min. of  
6 GPM, 0.4 L/s, flow is going through  
boiler & indirect circuit.  
2. Reduce indirect Aquastat setting,  
or Increase difference between (Lo  
Setting) and (indirect Aquastat setting).  
3. Indirect limit or wiring failure.  
ER6  
“Flame Lock Out”  
1. There is a problem in the ignition  
sequence; it could be caused by a  
faulty igniter, flame sensor, gas valve or  
improper line pressure or combustion.  
Check ignition sequence to determine  
which component is not functioning.  
(Sentry will retry ignition sequence  
1 hour after ER6 code originally  
occurs or if control is reset)  
Sentry has sensed a lack of 24V to the  
gas valve during operation or a Fenwal  
ignition lockout.  
2. Check for 24V between B on terminal  
block and F1 on Sentry plug, if not  
present a limit has tripped (see wiring  
diagram).  
3. the Flow Switch on the GT-400 is also  
in the 24V circuit. Check for proper  
water flow and flow switch operation.  
Burner shuts off  
before set-point  
temperature is  
reached (and burner  
light goes out)  
Reset calculation being used to  
lower HI setting.  
If OD probe is being used, the HI setting will  
be calculated using formula in Section 8.  
Thermostat is satisfied  
1. If the thermostat demand light is  
turning off, the thermostat has satisfied.  
2. If DHW temp light is turning off; the  
aquastat or call for domestic has been  
satisfied.  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Page 37  
Problem  
Detected Problem  
Solution  
ASO  
This is displayed when the boiler is  
expecting the air switch to be closed by a  
differential pressure generated when the  
combustion blower turns on. It can occur  
momentarily during normal operation.  
A problem is indicated when ASO is  
displayed continuously.  
1. Are the vinyl tubes connected between  
the air switch and the ports on the inlet  
pipe. Negative side of switch connects  
to the port on the 1 1/2 in, 38 mm,  
ABS elbow.  
Indicates that the  
Air Switch is Open  
2. Check for blockage on the intake and  
exhaust vents.  
3. If fan is running, air switch may be faulty,  
ensure that it’s set for 0.2 in, 5.1 mm WC.  
The GT-400 condensate drain switch  
must be set at 3 in, 76 mm WC.  
4. If fan is not running, check 120V wiring  
to blower, if ok remove low voltage  
harness from blower, if blower fails to  
start, replace blower, if blower does  
start problem may be with blower or  
Sentry control.  
ASC  
Indicates that the  
Air Switch is Closed the air switch to be open. It can occur  
momentarily during normal operation.  
A problem is indicated when ASC is  
This is displayed when the boiler has  
turned the blower off and is expecting  
1. Is the fan running. If so check for 24V  
between C and D terminals, see wiring  
diagrams. If 24V is not present replace  
transformer.  
2. Check venting termination with  
required venting described in manual.  
displayed continuously.  
Ignition Sequence  
not activated when  
burner light is on  
(Fan is on and  
Check for 24 Volts between terminal B1  
on Sentry & Ground.  
1. If there is 24V, indicates faulty wiring  
between BI and W1 on Fenwal, or  
faulty Fenwal.  
2. If 24V is not present proceed to next  
step.  
Fenwal not flashing)  
Check for 24 Volts between terminal F1  
on Sentry & Ground.  
1. If 24V exists here but not at B1,  
indicates faulty relay inside Sentry,  
contact NTI, replace control.  
2. If 24V is not present check for 24V  
at transformer.  
3. If 24V exists at transformer, check  
wiring and safety limits. If 24V not  
present at transformer, check wiring  
and replace transformer if necessary.  
Water Safety Limit trips (Automatic reset)  
Located in the supply manifold inside the  
boiler cabinet.  
May be caused by an error in the reading  
of the water temperature by the Sentry  
control. Watch cycle, and ensure the  
Sentry is displaying the correct water  
temperature and is modulating.  
This device protects the boiler from  
overheating due to a lack of flow passing  
through the unit when the burner is on.  
FLOW MUST NEVER BE BLOCKED BY  
ANY VALVES INCLUDING MIXING OR  
ZONE VALVES.  
Install unit as described in this manual.  
Page 38  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Problem  
Detected Problem  
Solution  
Ignition Sequence  
not activated when  
burner light is on  
(Fan is on and  
Fenwal not flashing)  
continued  
Stack Safety Limit Trips (Automatic Reset) This device protects the integrity of the  
Located on the front of the flue box.  
plastic venting material.  
If the temperature of the flue gases  
exceeds 225°F, 107°C, the limit will cut  
power to the control. Blocked internal  
tubes can increase the stack temperature  
to an unacceptable level. Flush out the  
boiler.  
Two Flashes on  
Fenwal  
The Fenwal controller thinks that there is a If the combustion sequence is normal,  
flame prior to ignition.  
and there is no flame prior to ignition, the  
Fenwal control is defective, and must be  
replaced.  
Three Flashes on  
Fenwal  
Indicates Ignition Lockout.  
If the condensate drain gets blocked,  
the boiler will become flooded, and  
terminate operation, as the flame rod  
becomes immersed. This will damage  
the flame probe. To correct, free the drain  
blockage, and permanently prevent it from  
reoccurring. Remove and dry off the probe.  
Reinstall the probe and try for ignition, if  
it fails to ignite, leave the fan run for up to  
three hours to dry out the insulation and  
probe.  
Reset Boiler so it will attempt to ignite.  
Check for proper operation of ignition  
components. Make sure igniter glows and  
gas valve opens.  
Check for proper line pressure at gas  
valve when it opens.  
If boiler lights check for flame signal  
between FC1 And FC2 on Fenwal control.  
If lower then 1.2 micro amps see Boiler  
will not stay lit below.  
Check combustion properties.  
Boiler will not stay  
lit.  
Indicates lack of a good flame signal. In  
order to stay running the flame signal must out, go to “Burner shutting off”.  
be at least 0.7 micro Amps. Check condensate drain for blockage and  
If the Burner light on the Sentry is going  
check the inlet piping for ingested snow  
or water (if the flame rod gets wet, it may  
need to be replaced). Check for resistance  
from flame rod to ground, must be an  
open circuit (O.L).  
Check for proper polarity of line and  
neutral wiring to the boiler.  
Boiler bangs or  
hisses  
Bangs or sounds like a kettle while burner Ensure the plumbing is as shown in  
is running indicating insufficient flow.  
manual. Check to see if pumps are faulty  
or end switches are stuck. This problem  
can lead to boiler overheating!  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Page 39  
Problem  
Detected Problem  
Solution  
Excessive noise, current, or voltage spikes Check for voltage at the wires going to the  
Sentry Controller  
Locks-up  
in the 120V power supply.  
A-C-T terminals of the Boiler.  
Check the magnitude of the line voltage  
power supply.  
Check the Amp draw of output C1 and Ap  
(max 3 Amp).  
Check the Amp draw of control on start-up  
(max 6 Amps)  
Contact Smith.  
No power to control or control failure.  
Check for 120V between terminals L1 and  
L2 at Sentry.  
Display Goes Blank  
If 120V exists turn power off and remove  
line voltage harness from Sentry. Then  
check for resistance between L1 and L2  
of control, if the circuit is open (O.L) the  
internal fuse has blown. Check for shorts  
in wires leading to circulators prior to  
replacing controller.  
If 120V not present, check wiring and for  
120V at source.  
Typically an imbalance in the air to gas  
ratio.  
Ensure that the venting lengths are in  
compliance with the venting sections  
above.  
Boiler Lights rough  
or pulsates  
Ensure that the line pressure during  
operation does not drop more than 20%  
from the static line pressure.  
Momentarily remove the intake vent from  
the boiler during ignition, if unit lights  
smoothly with intake vent disconnected  
reconnect and check for proper  
combustion if unit maintains smooth  
operation after ignition. Calibrate for  
proper combustion. If problem persists  
contact Smith.  
Slight vibration can cause noise in the  
residence. This is not a warranty issue.  
Use flexible gas line to insolate the  
vibration noises between the gas valve  
and the line.  
Fan appears to be  
creating a noise in  
the housing  
Don’t hang gas lines from floor joists.  
Use rubber insulators with gas line  
supports.  
Making a rubbing noise. This is not a  
warranty issue.  
If gas valve is not held when the gas  
nipple is connected, the force of tightening  
the fitting can damage the valve, and warp  
the fan housing.  
If pipe is used, the gas line must not  
create any forces to the valve, either  
vertically (weight of line), or horizontally  
(misaligned connection)  
Page 40  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
The following are the thermister curves for diagnosing  
the water and outdoor air sensors.  
1. Measure the resistance of the thermister when  
disconnected.  
2. Using the appropriate chart, find the resistance and  
move vertically for the water probe or horizontally for  
the air probe until the line is intersected.  
3. Move 90 degrees to the corresponding temperature.  
4. If the temperature is plus or minus 10°F, - 12 °C,  
then the probe is operating correctly.  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Page 41  
REPLACEMENT PARTS LIST  
Replacement parts are available from your stocking wholesaler. Homeowners must contact their  
local installer or wholesaler.  
Figure 48 - Replacement Parts Exploded View - Models GT150 and GT200  
30  
27A  
27  
2
8
3
6B  
6
11C  
11B  
12  
7
11  
15  
13  
26  
19A  
19B  
11A  
18  
19  
20  
9
32  
5A  
18A  
1
1A  
10  
4
22  
5
14  
28  
SIOM-151  
5B  
16  
28A  
17  
29  
Item Part Number Description  
Item Part Number Description  
1
1
1A  
2
3
4
4
5
5A  
5B  
6
GT-82657  
GT-82658  
GT-82761  
GT-82457  
GT-82013  
GT-82052  
GT-82661  
GT-82054  
GT-82065  
GT-82600  
GT-82662  
GT-82671  
GT-83035  
GT-82058  
GT-82708  
GT-82762  
GT-82763  
GT-82764  
GT-82765  
GT-83291-1  
GT-82659  
GT-82992  
GT-82596  
GT-83012  
GT-82647  
GT-82650  
GT-82660  
GT-82766  
Premix burner, 135.8 – 150 Only  
Premix burner, 200.6 – 200 Only  
Premix Burner Gasket  
Transformer, 24V  
Sentry 2100  
Blower #RG130 – 150 Only  
Blower #RG148/1200 – 200 Only  
Gas Valve (CVI) VK8115F1134B  
Gas Valve 1/2" npt elbow  
Gas Valve Vent connection  
Air switch Huba @ .15"wc.  
16  
17  
18  
18A  
19  
19A  
19B  
20  
22  
27  
27A  
28  
28A  
29  
30  
31  
31  
32  
A
B
C
D
E
F
G
H
I
GT-82719  
GT-82622-1  
GT-82127  
GT-82913  
GT-82767  
GT-82769  
GT-82770  
GT-82768  
GT-82771  
Blower gasket 200 Only  
Inlet Pipe assembly  
Condensate nylon Y  
Siphon Condensate Trap  
Cast aluminum Burner door  
Ceramic burner door disc  
Burner door gasket  
Igniter gasket  
Extended air tube  
Complete Control panel & Harness  
PCB Optocoupler  
CVI Venturi 01 – 150-200 Only  
CVI Venturi Gasket  
GT-82754  
GT-82754-1  
GT-82054-1  
GT-82054-2  
GT-82104-1  
GT-81027-1  
GT-83223  
7
7
8
9
Thermister #T7335C2016 1 Mohm (150-200)  
Thermister NTC 1/4" NPT, 1 Mohm (150ASME)  
Ignition Moduel Fenwal #2465H  
IGNITER, #601, c/w SS Heat shield  
Rauscchert Flame Rod  
Composit Flue Box  
Composit Flue Box Gasket  
Composit Flue Outlet Gasket  
Flue Adapter Assembly  
Manifold Limit, 1/8BSP, Brass (150-200)  
Manifold Limit, 1/4NPT, Brass (150 ASME)  
150 non-ASME Heat Exchanger  
150 ASME Heat Exchanger  
Air metering Elbow  
Sentry 2100 (10k) Outdoor Air Sensor  
1/8NPT Water Pressure Switch (after 5-1-06)  
1/4NPT Water Pressure Switch (150 ASME)  
Divider Plate Insulation c/w washer and screw  
Stainless steel Top  
10  
11  
11A  
11B  
11C  
12  
12  
13  
13  
13  
14  
15  
16  
GT-83223-1  
GT-83112  
GT-82976-A  
GT-82976-B  
GT-82976-C  
GT-82976-D  
GT-82976-E  
GT-82976-F  
GT-82976-G Galvanized Bottom base  
GT-82976-H  
GT-82976-I  
Electrical box cover  
Stainless steel Left side  
Stainless steel Right side  
Stainless steel Front Door  
Galvanized Right Side  
200 Heat Exchanger  
LP orifice 5.20mm – 150-200 Only  
Stack Limit, 1/4BSP, SS, 190F, Dif=30  
Blower gasket 150 Only  
Bottom Base support  
Galvanized Back  
Page 42  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
REPLACEMENT PARTS LIST  
Replacement parts are available from your stocking wholesaler. Homeowners must contact their  
local installer or wholesaler.  
Figure 49 - Replacement Parts Exploded View - Model GT400  
31  
32  
33  
30  
34  
36  
30  
14A  
Reverse  
Angle  
6C  
15  
7
12  
11  
21  
26  
8
6
3
2
23  
13  
19A  
19B  
19  
20  
37  
9
17A  
17  
18  
1
10  
5
1A  
14  
5B  
22  
5A  
16  
25  
4
24  
28  
29  
SIOM-152  
Item Part Number Description  
Item Part Number Description  
1
1A  
2
3
4
5
5A  
5B  
GT-83173  
GT-82761  
GT-82457  
GT-83171  
GT-82994  
GT-82989  
GT-82991  
GT-83194  
GT-83016  
GT-82662  
GT-82539  
GT-83035  
GT-82058  
GT-82708  
GT-82762  
GT-82906  
GT-82992  
GT-82926  
GT-82993  
GT-83017  
GT-81887  
GT-82766  
Premix Burner (For 400)  
Premix Burner Gasket  
Transformer, 24V  
17  
17A  
18  
19A  
19B  
20  
21  
22  
23  
24  
GT-83037  
GT-83038  
GT-82913  
GT-82769  
GT-82770  
GT-82768  
GT-83034  
GT-83195  
GT-83141  
GT-82990  
GT-83106  
GT-83001  
GT-82754-1  
TEE NYLON 3/4"HB to 3/4"  
ADAPTER NYLON, 3/4" x 1/4"  
SIPHON CONDENSATE TRAP  
Burner Door Ceramic Disc  
Burner Door Viton Gasket  
Igniter Gasket  
Sentry 2100 Assembly  
EBM BLOWER #RG148/E  
Gas Valve VR8615VB 1044B  
Gas Valve Adapter, 3/4" NPT  
Gas Valve Connector O-ring  
Gas Valve Harness  
Air switch Huba @ 0.2"wc.  
Air Vent  
Thermister NTC 1/4" NPT, 1Mohm  
Ignition Module (Fenwal)  
Exhaust Test Plug  
Extended Air Tube  
Control Panel, Complete  
CVI Venturi  
O-ring, Venturi to Blower  
Test Port Retaining Clamp  
PCB Optocoupler  
Air Metering Assembly  
Sentry 2100 (10K) Outdoor Probe  
Vent Screen, 4"  
6
6C  
7
8
9
10  
11  
12  
13  
14  
14A  
15  
16  
25  
26  
27  
IGNITER, #601, c/w SS Heat shield  
Flame Rod Rauschert  
28 29 GT-83170-1  
30  
31  
32  
33  
34  
35  
36  
37  
GT-81027-1  
GT-83018  
GT-83019  
GT-83013  
GT-83005  
GT-13701  
GT-82148  
GT-83112  
Air Switch 604.E421180 set @ 3" wc  
Limit Switch, 1/4"NPT, (Manifold)  
400 Heat Exchanger, ASME  
Gas Valve Orifice, 8.0mm, NG  
Gas Valve Orifice, 6.2mm, LP  
Flow Switch, FS-10C  
Vent Screen, 6"  
Nipple, 1-1/4" x 8", Brass  
1-1/4"x 1-1/4"x 3/4" Tee Brass  
RELIEF VALVE 3/4" #335 30 PSI  
PRESSURE GAUGE 0-30 PSI  
Divider Insul. (c/w washer & screw)  
Blower Gasket  
GT INSTALLATION AND OPERATION INSTRUCTIONS  
Page 43  
WESTCAST, INC.  
260 NORTH ELM STREET WESTFIELD, MA 01085  
TEL. (413) 562-9631 FAX (413) 562-3799  

Westcott 2348 User Manual
Toshiba Blu ray Player BDX5300KU User Manual
Tektronix Car Amplifier 7A18A User Manual
Sony XS F6920SL User Manual
Sony Handycam DCR SX65E User Manual
Sony Cyber shot DSCW180B User Manual
Sennheiser MZQ 30 User Manual
Schwinn FITNESS 223 User Manual
Samsung VP D361W(i) User Manual
Samsung BD C7500 User Manual