Raypak TYPE H HD101 User Manual

USER’S INFORMATION MANUAL  
®
Models HD101–HD401  
Type H  
WARNING: If the information in this manual is  
not followed exactly, a fire or explosion may  
result causing property damage, personal  
injury or loss of life.  
AVERTISSEMENT: Assurez-vous de bien  
suivres les instructions données dans cette  
notice pour réduire au minimum le risque  
d’incendie ou d’explosion ou pour éviter tout  
dommage matériel, toute blessure ou la mort.  
Do not store or use gasoline or other flammable  
vapors and liquids or other combustable  
materials in the vicinity of this or any other  
appliance. To do so may result in an explosion  
or fire.  
Ne pas entreposer ni utiliser d’essence ni  
d’autres vapeurs ou liquides inflammables dans  
le voisinage de cet appareil ou de tout autre  
appareil.  
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE  
WHAT TO DO IF YOU SMELL GAS:  
GAZ:  
Do not try to light any appliance.  
Do not touch any electrical switch; do  
not use any phone in your building.  
Immediately call your gas supplier  
from a neighbor's phone. Follow the  
gas supplier's instructions.  
Ne pas tenter d’allumer d’appareils.  
Ne touchez à aucun interrupteur. Ne pas  
vous servir des téléphones dansle bâtiment  
où vous vous trouvez.  
Appelez immédiatement votre fournisseur  
de gaz depuis un voisin. Suivez les  
instructions du fournisseur.  
Si vous ne pouvez rejoindre le fournisseur  
de gaz, appelez le sservice des incendies.  
If you cannot reach your gas supplier,  
call the fire department.  
Installation and service must be performed by a  
qualified installer, service agency or the gas  
supplier.  
L’installation et l’entretien doivent être assurés  
par un installateur ou un service d’entretien  
qualifié ou par le fournisseur de gaz.  
CATALOG NO. 1000.521  
Effective: 05-05-09  
Replaces: NEW  
P/N 241368 Rev. 1  
3
Component Locations  
Fig. 2: Component Locations – Left Side  
Fig. 1: Component Locations – Angle  
Fig. 3: Component Locations – Front  
4
13. Check air filter and replace if necessary.  
MAINTENANCE  
Daily:  
Suggested Minimum  
1. Check that heater area is free from combustible  
materials, gasoline, and other flammable vapors  
and liquids.  
Maintenance Schedule:  
Regular service by a qualified service agency and  
maintenance must be performed to ensure maximum  
heater operating efficiency. Maintenance as outlined  
below may be performed by the owner.  
2. Check for and remove any obstruction to the flow  
of combustion or ventilation air to heater.  
Monthly:  
Yearly (Beginning of each heating  
season):  
1. Check for piping leaks around circulators, mixing  
valves, relief valves, and other fittings. If found,  
repair at once. DO NOT use petroleum-based stop  
leak compounds.  
1. Annual service call by qualified service agency.  
2. Visually check top of vent for soot. Call service  
person to clean. Some sediment at bottom of vent  
is normal.  
2. Visually inspect burner flame.  
3. Visually inspect venting system for proper func-  
tion, deterioration or leakage.  
3. Visually inspect venting system for proper func-  
tion, deterioration or leakage.  
4. Check air vents for leakage.  
4. Check that heater area is free from combustible  
materials, gasoline, and other flammable vapors  
and liquids.  
Quarterly:  
1. Check relief valve. Refer to manufacturer’s  
instructions on valve.  
5. Check for and remove any obstruction to the flow  
of combustion or ventilation air to heater.  
2. Test low water cut-off, if used. Refer to manufac-  
turer’s instructions.  
6. Follow pre-start-up check in the Initial Start-up  
section.  
3. Check the air filter; replace if necessary.  
7. Visually inspect burner flame. Should see light  
blue flame. Visually inspect hot surface igniter for  
damage, cracking or debris build-up.  
8. Check operation of safety devices. Refer to manu-  
facturer’s instructions.  
9. Follow oil-lubricating instructions on circulator (if  
required). Over-oiling will damage circulator.  
Water-lubricated circulators do not need oiling.  
10. To avoid potential of severe burn, DO NOT REST  
HANDS ON OR GRASP PIPES. Use a light touch  
- return piping will heat up quickly.  
11. Check blower and blower motor. Clean and oil as  
necessary.  
12. Check for piping leaks around circulators, relief  
valves and other fittings. Repair, if found. DO NOT  
use petroleum based stop leak.  
5
6
7
Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (805) 278-5468  
Litho in U.S.A.  

Rockford Fosgate ND8 XFM User Manual
Raypak XTHERM 1005 2005 User Manual
Philips AUDIOSPELER SA4146 User Manual
Panasonic DVD ecam VDR VDR D210 User Manual
Panasonic CQ VX2200W User Manual
Panasonic AJ P2C004HG User Manual
Panasonic AJ HDC20A P User Manual
Kenwood KDC W4537UA User Manual
Kalorik USK BL 7 User Manual
JVC TK WD310U User Manual