Raypak 751 1501 User Manual

Job:  
ADB™ - Type H  
Hydronic Heating Boilers  
Engineer:  
Contractor:  
Prepared By:  
Model:  
Models 751-1501  
Date:  
Indoor/Outdoor:  
100% Factory Fire Tested  
Efficiency: 84%  
Maximum Outlet Temperature: 230°F  
Minimum Non-Condensing Inlet Temperature: 105°F  
Thermal Shock Proof Heat Exchanger  
Footprint: Less Than 5-1/2 ft2  
Limited Twenty-Year Thermal Shock Warranty  
Limited Ten-Year Heat Exchanger Warranty  
Ten-Year Unconditional Burner Head Warranty  
Operation Status Center and Full Diagnostic Panel  
Heat Exchanger  
ƒ Bronze Headers  
Gas Train  
ƒ Fuel  
Temperature Controls  
B-20 Single-Stage Controller,  
100-200°F  
ƒ ASME Inspected and Stamped  
160 PSIG Working Pressure  
ƒ National Board Approved  
ƒ Copper-finned Tubes  
ƒ ASME Steel Tube Retainer  
ƒ Silicone High Temp O-Rings  
ƒ 60 PSIG ASME Pressure Relief  
Valve  
Natural Gas  
Propane (Models 751 & 1001)  
ƒ Manual Gas Shut-off Valves  
ƒ Gas Pressure Regulator  
ƒ Safety Shut-off Valve  
B-6  
2-Stage Controller, 100-200°F  
B-21 4-Stage TempTracker Digital  
Controller, Loose  
B-23 4-Stage TempTracker Digital  
Controller, Outdoor Reset, Loose  
Y-241 Electronic Sequencer,  
1-4 Stages  
ƒ Firing Control Valve  
ƒ Manual Low Gas Pressure Switch  
ƒ On/Off Firing Mode (H4)  
ƒ Design Certified ANSI Z21.13/  
CSA 4.9  
ƒ Temperature and Pressure Gauge,  
Shipped Loose  
Y-281 Electronic Sequencer,  
5-8 Stages  
Control  
Construction  
Additional Safety Controls (Optional)  
F-10 Low Water Cut-off,  
Remote Probe  
ƒ 120V, 60Hz, Power Supply  
ƒ 120/24V 60Hz Transformer  
ƒ 100% Pilot Shutoff/Lockout  
ƒ Electronic Intermittent Ignition Pilot  
(IID)  
ƒ Indoor/Outdoor Construction  
ƒ Front Controls Enclosed  
ƒ PolyTuf Powder Coat Finish  
ƒ Connections (Water, Electrical,  
Gas)  
S-2  
Manual High Gas Pressure  
Switch  
ƒ High Limit Control, Manual Reset  
ƒ High Limit Control, Auto Reset  
ƒ On/Off Switch  
Rear – Standard  
Right Side – Option A-8  
Regulatory Agency Requirements  
C-5 Ignition Lockout Module  
Venting  
ƒ Vent Location  
ƒ Flow Switch  
ƒ Blocked Vent Pressure Switch  
ƒ Combustion Air Proving Switch  
ƒ Time Delay Pump Off Control  
ƒ Central Point Wiring Diagnostics  
Panel  
Rear – Standard  
Other Equipment  
Condensing Heat Exchanger  
Pump  
Right Side – Option Z-2  
ƒ Vent Termination Cap  
Outdoor - Option D-11  
Indoor, Horizontal – Option D-15  
Indoor, Vertical (by others)  
Burner  
ƒ Aerodynamically Stabilized  
Non-Clog Burner  
ƒ Ultra-Low NOx: Less than 30 PPM  
Catalog No.: 2000.36G  
Effective: 2-1-08  
Replaces: 5-1-05  

Planet Bike 1010 User Manual
Perlick 66134 2 User Manual
Panasonic Camera Accessories AJ0RC10G User Manual
Panasonic Camcorder HDC SD90 User Manual
Mustang Survival Commander Rescue Suit IC9001 U GD User Manual
Metra Electronics 99 8225G User Manual
Lochinvar CREST 3 User Manual
KitchenAid 4KFP720WH1 User Manual
JVC KS T807 User Manual
JVC High Definition Camcorder GZE200RUS User Manual