Raypak 302 902 User Manual

CATALOG NO. 1000.50K  
Effective: 08-01-03  
Replaces: 01-15-03  
INSTALLATION  
AND OPERATING  
INSTRUCTIONS  
Models 302-902  
Type H, WH, & P  
FORYOURSAFETY  
Donotstoreorusegasolineorotherflammablevaporsandliquidsorothercombustiblematerialsinthevicinityof  
this or any other appliance. To do so may result in an explosion or fire.  
WARNING:Improperinstallation, adjustment, alteration, serviceormaintenancecancausepropertydamage,  
personalinjuryorlossoflife. Refertotheuser’sinformationmanualprovidedwiththisboiler. Installationand  
servicemustbeperformedbyaqualifiedinstaller, serviceagencyorthegassupplier.  
FORYOURSAFETY  
WHATTO DO IFYOU SMELLGAS:  
·
·
·
·
Donottrytolightanyappliance.  
Donottouchanyelectricalswitch;donotuseanyphoneinyourbuilding.  
Immediatelycallyourgassupplierfromaneighbor’sphone. Followthegassupplier’sinstructions.  
Ifyoucannotreachyourgassupplier, callthefiredepartment.  
Thismanualshouldbemaintainedinlegiblecondition  
and kept adjacent to the boiler or kept in a safe place  
forfuturereference.  
P/N 240757  
DANGER:  
Make sure the gas on which the boiler will operate is the same type as that specified  
on the boiler model and rating plate.  
WARNING: Should overheating occur or the gas supply valve fail to shut, do not turn off or  
disconnect the electrical supply to the boiler. Instead, shut off the gas supply at a  
location external to the appliance.  
WARNING: Do not use this boiler if any part has been under water. Immediately call a qualified  
service technician to inspect the boiler and to replace any part of the control system  
and any gas control which has been under water.  
WARNING: To minimize the possibility of improper operation, serious personal injury, fire, or  
damage to the boiler, never violate the following safety rules:  
1. Always keep the area around the boiler free of combustible materials,  
gasoline, and other flammable liquids and vapors.  
2. Boiler should never be covered or have any blockage to the flow of fresh air  
to the boiler.  
WARNING: Risk of electrical shock. More than one (1) disconnect switch may be required to de-  
energize the equipment before servicing.  
CAUTION:  
CAUTION:  
Operation of this boiler on low temperature systems requires special piping to insure  
correct operation.  
If this boiler is to be installed above radiation level, it must be provided with a low  
water cutoff device at the time of boiler installation.  
CAUTION:  
This boiler requires forced water circulation when the burner is operating. See  
minimum and maximum flow rates. Severe damage will occur if the boiler is  
operated without proper water flow circulation.  
CALIFORNIAPROPOSITION65WARNING: ThisproductcontainschemicalsknowntotheState  
ofCaliforniatocausecancer,birthdefectsorotherreproductiveharm.  
3
Pay attention to these terms:  
DANGER:  
WARNING:  
CAUTION:  
NOTICE:  
indicates the presence of immediate hazards which will cause severe personal injury, death  
or substantial property damage if ignored.  
indicates the presence of hazards or unsafe practices which could cause severe personal  
injury, death or substantial property damage if ignored.  
indicates the presence of hazards or unsafe practices which could cause minor personal  
injury or product or property damage if ignored.  
indicates special instructions on installation, operation, or maintenance which are important  
but not related to personal injury hazards.  
SECTION A: BEFORE INSTALLING THE BOILER  
Raypak strongly recommends that this manual be reviewed thoroughly before installing your Raypak boiler. Please review  
the General Safety Precautions on Section L before installing the boiler. Factory warranty does not apply to boilers that have  
been improperly installed or operated. Installation and service must be performed by a qualified installer, service agency or  
gas supplier. If, after reviewing this manual, you still have questions which this manual does not answer, please contact the  
factory or your local Raypak representative.  
ThankyouforpurchasingaRaypakproduct. Wehopeyouwillbesatisfiedwiththehighqualityanddurabilityofourequipment.  
PRODUCT RECEIPT  
On receipt of your product it is suggested that you visually check for external damage to the shipping crate. If the crate is  
damaged, make a note to that effect on the Bill of Lading when signing for the shipment. Remove the boiler from the shipping  
packaging. Report any damage to the carrier immediately.  
On occasion, some items will be shipped loose. Be sure that you receive the correct number of packages as indicated on the  
BillofLading.  
Claims for shortages and damages must be filed with the carrier by consignee. Permission to return goods must be received  
from the factory prior to shipping. Goods returned to the factory without an authorized Returned Goods Receipt number will  
not be accepted. All returned goods are subject to a restocking charge.  
Whenorderingparts, youmustspecifytheModelandSerialNumberoftheboiler. Whenorderingunderwarrantyconditions,  
you must also specify the date of installation.  
Purchasedpartsaresubjecttoreplacementonlyunderthemanufacturer'swarranty. Debitsfordefectivereplacementpartwill  
not be accepted and will be replaced in kind only per Raypak's standard warranties.  
4
MODEL IDENTIFICATION  
The model identification number and boiler serial number are found on the boiler data plate located on the left inside jacket  
oftheboiler. ThemodelnumberwillhavetheformH30752orsimilardependingontheboilersizeandconfiguration. Thefirst  
characterofthemodelnumberidentifiesapplication(H=HydronicHeatingSystem, W=HotWaterSupplySystem, P=Pool  
Application). The second character identifies the firing mode (3-two stage firing). The next four places identify the size of  
the boiler.  
RATINGS AND CERTIFICATIONS  
STANDARDS  
ANSIZ21.13b-1994, GasFiredHotWaterBoilers  
CAN3.1M77;IndustrialandCommercialGas-FiredPackageBoilers  
ANSIZ21.56-1998<>CSA4.7-M98Gas-FiredPoolHeaters  
ANSIZ21.10.3-1998<>CSA4.3-M98GasWaterHeaters  
All Raypak boilers are National Board Approved, design certified and tested by the International Approval Services (IAS)  
(a joint venture of American Gas Association Laboratories and the Canadian Gas Association Laboratories) for U.S.A. and  
Canada. EachboilerisconstructedinaccordancewithSectionIVoftheAmericanSocietyofMechanicalEngineers(ASME)  
BoilerPressureVesselCodeandbearstheASMEstamp. ThisboilercomplieswiththelatesteditionofASHRAE90.1Standard.  
Altering any RAYPAK pressure vessel by installing replacement heat-exchangers, tube bundle headers, or any other ASME  
part not manufactured and/or approved by RAYPAK will instantly void the ASME, AGA, and CGA ratings of the vessel and  
any RAYPAK warranty on the vessel. Altering the ASME, AGA and CGA ratings of the vessel also violates national, state,  
and local approval codes.  
Ratedinputsaresuitableforupto4500feetelevationwithoutderate. ConsulttheFactoryforinstallationsataltitudesinexcess  
of4500feet.  
5
HIGH DELTA COMPONENT LOCATION  
Flue Exhaust  
Combustion Air  
Filter (Inlet)  
Optional  
Combustion Air (Inlet)  
Alternate Flue Connection  
BACK  
Electrical Connection  
Gas Supply Connection  
Pressure Relief Connection  
Water Inlet  
View Port  
Water Outlet  
Temperature and Pressure Gauge  
Operational Center Control  
LEFT-SIDE  
Gas Train  
Combustion Air  
Blower  
Pressure Relief Valve  
Igniter  
Heat Exchanger  
Remote Sensor  
Burner Group  
FRONT  
Fig. #9220  
6
General Information  
7
SECTION B: BOILER INSTALLATION  
INSTALLATIONCODES  
Installations must follow these codes:  
· Local, state, provincial, and national codes, laws, regulations and ordinances.  
· National Fuel Gas Code (NFGC),ANSI Z223.1- latest edition.  
· National Electrical Code (NEC),ANSI/NFPA70 - latest edition.  
· Standard for Controls and Safety Devices forAutomatically Fired Boilers, ANSI/ASME CSD-1, when required.  
· For Canada only: CAN/CGA B149.1 and .2 Installation Code and C.S.A. C22. 1 C.E.C. Part 1.  
EQUIPMENT BASE  
The boiler should be mounted on a level, structurally sound surface. The boiler is approved for installation on a combustible  
surface but must NEVER be installed on carpeting. Gas fueled equipment installed in enclosed parking garages must be  
located at least 18 inches above the floor.  
Stacking  
Hi Delta units can be stacked two units high with an optional stacking rack. Astacking kit is available from Raypak for this  
type of installation.  
CAUTION:  
The boiler should be located in an area where water leakage will not result in damage to the  
area adjacent to the appliance or to the structure. When such locations cannot be avoided, it is  
recommended that a suitable catch pan, adequately drained, be installed under the appliance.  
The pan must not restrict air flow.  
In addition, the boiler shall be installed such that the gas ignition system components are protected from water (dripping,  
spraying, rain, etc.) during appliance operation or service (circulator replacement, control replacement, etc.).  
Typical Racked Installation  
36.0  
36.0  
12.0  
12.0  
36.0  
TOP VIEW  
Fig# 9239  
FRONT VIEW  
RIGHT SIDE VIEW  
8
CLEARANCES  
TABLE 1  
INDOOR INSTALLATION  
MINIMUM CLEARANCES FROM COMBUSTIBLE SURFACES  
Boiler Size  
Boiler Side  
Floor  
302-902  
See Note 1  
Rear  
1"  
12”  
1"  
1"  
1"  
2"  
Water Side  
Other Side  
Top  
Front  
Vent  
Note 1. Do not install on carpeting.  
12"  
1"  
1"  
1"  
Fig. #9221.1  
TOP VIEW  
FRONT VIEW  
When installed according to the listed minimum clearances from combustible construction mate-  
rials, the Raypak heaters can still be serviced without removing permanent structural construc-  
tion around the heater.  
However, for ease of servicing, we recommend a clearance of at least 24” in front, and at least  
18” on the water connection side. This will enable the heater to be serviced in its installed  
location, that is, without movement or removal of the heater.  
Clearances less than minimum, may require removal of the heater to service either the heat  
exchanger or the burner tray. In either case, the heater must be installed in a manner that will  
enable the heater to be serviced without removing any structure around the heater.  
9
OUTDOORINSTALLATIONS  
Raypak Hi Delta Boilers are design certified for outdoor installation. Boilers must not be installed under an  
overhang that is less than three (3) feet from the top of the boiler. Three (3) sides must be open in the area  
under the overhang. Roof water drainage must be diverted away from boilers installed under overhangs.  
TABLE 2  
OUTDOOR INSTALLATION MINIMUM CLEARANCES  
Boiler Size  
Boiler Side  
Rear  
302-902  
12"  
Right  
Left  
36”  
36"  
Top  
Vent  
Unobstructed  
N/A  
These clearances required where the outdoor vent cap is used. If installing the boiler outdoors with a vent stack, the  
indoor clearances may be used.  
The air filter box can be installed on top of the boiler or the rear of the boiler.  
For outdoor installations in snow prone areas, it is recommended that the filter kit be installed on to the rear of the boiler,  
to prevent recirculation and blockage.  
Fig # 9297  
SIDEVIEW  
FRONTVIEW  
10  
SECTION C: COMBUSTION AND VENTILATION AIR  
COMBUSTIONAND VENTILATIONAIR (Indoor Units)  
The boiler must be supplied with sufficient quantities of non-contaminated air to support proper combustion and equipment  
ventilation. Combustion air can be supplied via conventional venting, where combustion air is drawn from the area immedi-  
ately surrounding the boiler, or via direct vent, where combustion air is drawn directly from outside. All installations must  
comply with the requirements of NFGC for U.S., CAN/CGA B 149.1 and .2 for Canada, and all local codes.  
CAUTION:  
NOTICE:  
Combustion air must not be contaminated by corrosive chemical fumes which can damage the boiler  
and void the warranty. See appendix A.  
It is recommended that the intake vent be insulated to minimize sweating.  
DIRECT VENT-INSTALLATON  
If outside air is drawn through the intake pipe directly to the unit for combustion:  
1. Install combustion air direct vent in accordance with Section J-3 and Section J-4 of this manual.  
2. Provide adequate ventilation.  
3. In cold climates, and to mitigate potential freeze-up, Raypak highly recommends the installation of a motorized sealed  
damper to prevent the circulation of cold air through the boiler during the non-operating hours.  
CONVENTIONALCOMBUSTIONAIR SUPPLY (FOR U.S. INSTALLATION ONLY)  
(a) All Air from Inside the Building. The confined space shall be provided with two permanent openings communicating  
directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an  
unconfined space. The total input of all gas utilization equipment installed in the combined space shall be considered in  
making this determination. Each opening shall have a minimum free area of 1 square inch per 1,000 Btu per hour (22 cm2 per  
kW) of the total input rating of all gas utilization equipment in the confined space, but not less than 100 square inches  
(645 cm2). One opening shall commence within 12 inches (30 cm) of the top, and one opening shall commence within 12 inches  
(30 cm) of the bottom, of the enclosure. The minimum dimension of air openings shall be not less than 3 inches (8 cm).  
(b)All Air from Outdoors. The confined space shall communicate with the outdoors in accordance with methods 1 or 2. The  
minimum dimension of air openings shall not be less than 3 in. (8cm). Where ducts are used, they shall be of the same cross-  
sectional area as the free area of the openings to which they connect.  
1. Two permanent openings, one commencing within 12in. (30cm) of the top, and one commencing within 12in. (30cm) of  
the bottom, of the enclosure shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or  
spaces (crawl or attic) that freely communicate with the outdoors.  
a. Where directly communicating with the outdoors or where communicating to the outdoors through vertical ducts,  
each opening shall have a minimum free area of 1 sq in. per 4000 Btu per hr (5.5cm2 per kW) of total input rating of all  
equipment in the enclosure.  
b. Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1  
sq in. per 2000 Btu per hr (11 cm2 per kW) of total input rating of all equipment in the enclosure.  
2. One permanent opening, commencing within 12 in. (30cm) of the top of the enclosure, shall be permitted where the  
equipment has clearances of at least 1 in. (2.5 cm) from the sides and back and 6 in. (16cm) from the front of the appliance. The  
opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the  
outdoors or spaces (crawl or attic) that freely communicate with the outdoors, and shall have a minimum free area of:  
a. 1 sq in. per 3000 Btu per hr (7 cm2 per kW) of the total input rating of all equipment located in the enclosure, and  
b. Not less than the sum of the areas of all vent connectors in the confined space.  
WARNING:  
Do not use one permanent opening method if the equipment room is under negative  
pressure condition or the equipment is common vented with other gas-fired appliances.  
11  
COMBUSTIONAND VENTILATIONAIR SUPPLY (FOR CANADA INSTALLATION)  
CAUTION:  
All combustion air has to be drawn from the air outside the building (the mechanical equipment  
room directly communicates with the outdoors).  
1. Ventilation of the space occupied by the boiler shall be provided by an opening(s) for ventilation air at the highest  
practical point communicating with outdoors. The total cross-sectional area of such an opening(s) shall be at  
least 10% of the area required in (2) and (3), but in no case shall the cross-sectional area be less than10 square  
inches (6500 square mm).  
2. For boilers using a barometric damper in the vent system, and when air supply is provided by natural air flow from  
the outdoors for natural draft, partial fan assisted, fan-assisted or power draft-assisted burners, there shall be a  
permanent air supply opening(s) having a cross section area of not less than 1 sq. in. per 7000 BTUH  
(310 sq. mm per kW) up to and including 1 million BTUH, plus 1 sq. in. per 14000 BTUH (155 sq. mm per kW) in  
excess of 1 million BTUH. This opening(s) shall be either located at or ducted to a point neither more than 18  
inches (450 mm) nor less than 6 inches (150 mm) above the floor level. The duct can also "Goose Neck" through  
the roof. The duct is preferred straight down 18" from floor, but do not place near piping. This air supply opening  
requirement shall be in addition to the air opening for ventilation air required in (1).  
3. For boilers not using a barometric damper in the ventsystem, and when air supply is provided by natural air flow  
from outdoors for a power burner and there is no draft regulator, draft hood or similar flue gas dilution device  
installed in the same space, in addition to the opening for ventilation air required in (1), there shall be a permanent  
air supply opening(s) having a total cross-sectional area of not less than 1 sq. in. for each 30,000 BTUH  
(70 sq. mm per kW) of total rated input of the burner(s), and the location of the opening(s) shall not interfere with  
the intended purpose of the opening(s) for ventilation air referred to (1). This opening(s) can be ducted to a point  
neither more than 18 inches (450 mm) nor less than 6 inches (150 mm) above the floor level. The duct can also  
"Goose Neck" through the roof. The duct is preferred to be straight down 18” from floor, but do not place near  
piping.  
4. Refer to the latest version of the CAN/CGA-B149.1 and .2 for additional information.  
12  
SECTION D: WATER PIPING - GENERAL  
The boiler should be located so that any water leaks will not cause damage to the adjacent area or structures.  
CAUTION:  
This boiler requires forced water circulation when the burner is operating. See Table D-1 for  
minimum and maximum flow rates and water pump selection. The pump must be interlocked with the  
boiler toprevent boiler operation without water circulation.  
RELIEFVALVE PIPING  
WARNING: Pressure relief valve discharge piping must be piped near the floor close to a floor drain to eliminate  
the potential of severe burns. Do not pipe to any area where freezing could occur. Refer to local  
codes.  
HYDROSTATIC TEST  
Unlike many other types of boilers, Raypak boilers do not require hydrostatic testing prior to being placed in operation. The  
heat exchanger has already been factory-tested and is rated for 150 PSI operating pressure. However, Raypak does recom-  
mend hydrostatically testing the piping connections to the boiler and the rest of the system prior to operation. This is  
particularly true for hydronic systems using expensive glycol-based antifreeze. Raypak recommends conducting the hydro-  
static test before connecting gas piping or electrical supply.  
Leaks must be repaired at once to prevent damage to the boiler. NEVER use petroleum-based stop-leak compounds.  
1. Connect fill water supply. Fill boiler with water (be sure bleed valve is open). When water flows from bleed  
valve, shut off water. Close bleed valve. Carefully fill the rest of the system, being sure to eliminate any entrapped air  
by using high point vents. Close feed valve. Test at standard operating pressure for at least 24 hours.  
2. Make sure constant gauge pressure has been maintained throughout test.  
3. Check for leaks. Repair if found.  
LOWTEMPERATURE SYSTEM  
Boiler requires minimum inlet temperature of 105°F. Consult sections E, F for piping details.  
TEMPERATURE & PRESSURE GAUGE  
The temperature and pressure gauge is factory-mounted in the inlet/outlet header.  
13  
SECTION E: HYDRONIC HEATING PIPING  
PUMP SELECTION  
In order to insure proper performance of your boiler system, you must install a properly sized pump. Raypak recommends  
using a 20°F Delta T as design Delta T. (Delta T is the temperature difference between the inlet and outlet water when the  
boiler is firing at full rate). If a Delta T larger than 20°F is necessary, see Table D-1 for minimum flow rate requirements.  
PRESSURE DROP IN FEET OF HEAD  
FEEDWATER REGULATOR  
Raypak recommends that a feedwater regulator be installed and set at 12 PSIG minimum pressure at the highest point of  
system. Install a check valve or back flow device upstream of the regulator, with a manual shut off valve as required by local  
codes.  
PIPING - HEATING BOILERS  
All high points should be vented. Purge valves and a bypass valve should be installed. A boiler installed above radiation  
level must be provided with a low water cutoff device. The boiler, when used in connection with a refrigeration system, must  
be installed so the chilled medium is piped in parallel with the boiler with appropriate valves to prevent the chilled medium  
from entering the boiler.  
The boiler piping system of a hot water heating boiler connected to heating coils located in air handling units where they may  
be exposed to circulating refrigerated air, must be equipped with flow control valves or other automatic means to prevent  
gravity circulation of the boiler water during the cooling cycle. It is highly recommended that the piping be insulated.  
AIR-SEPARATION/EXPANSION TANK  
All boilers should be equipped with a properly sized expansion tank and air separator fitting as shown in the following  
diagrams.  
THREE-WAYVALVES  
Valves designed to blend water temperatures or reduce water circulation through the boiler should not be used. Raypak  
heaters are high recovery low mass heaters not subject to thermal shock. Raypak offers a full line of electric sequencers that  
produce direct reset of boiler water temperature. Refer to the Controls Section in our Complete Catalog.  
Table E-1  
NOTE: Basis for Minimum flow -20 gpm or 40° DT  
Maximum flow -90 gpm.  
Flow switch will not operate if flow is less than 20 gpm.  
14  
SINGLEBOILER-LOWTEMPERATUREAPPLICATION(HEATPUMP)PRIMARY/SECONDARYPIPING  
12  
Fig. #9223  
DUALBOILERPRIMARY/SECONDARYPIPING  
Fig. #9232.2  
15  
SECTION F: DOMESTIC HOT WATER PIPING  
When designing the water piping system for domestic water applications, water hardness should be considered. Table F-1  
indicates the suggested flow rates for soft, medium and hard water. Hardness is specified as grains per gallon.  
TABLE F-1  
DOMESTIC WATER HEATER  
FLOWRATE REQUIREMENTS  
DT = Temperature rise, degrees F  
DP = Pressure drop, ft, through heat exchanger  
SHL = System head loss, ft.  
GPM = Gallons/minute, flow rate  
MPS = Minimum pipe size, NPT  
System head loss based on heater and tank placed no more than 5 ft. apart and equivalent length pipe/fittings as follows:  
2” NPT = 75 ft.  
* Must use optional cupronickel tubes.  
POTABLE WATERAND SPACE HEATINGAPPLICATION  
CAUTION:  
When this heater is used for both -potable water and space heating- follow the steps below  
to insure proper operation.  
A. All piping materials and components connected to the water heater for the space heating application  
shall be suitable for use with potable water.  
B. Toxic chemicals, such as used for boiler treatment, shall not be introduced into the potable water used  
for space heating.  
C. If the water heater will be used to supply potable water, it shall not be connected to any heating system  
or components previously used with a nonpotable water heating appliance.  
D. When the system requires water for space heating at temperatures higher than 140°F, a means such as a  
mixing valve shall be installed to temper the water in order to reduce scald hazard potential.  
SINGLE DOMESTIC HOTWATER HEATER WITH ONE STORAGE TANK  
Hot Water Supply  
City Water  
System Return  
Fig. #9224.1  
16  
SECTION G: POOL HEATING  
CAUTIO  
CAUTION:  
Power to the heater should be interlocked with the main system pump to make sure the heater does not fire  
without the main system pump in operation. Improper flow control can damage the heater. Uncontrolled  
flow (too high) or restricted flow (too low) can seriously damage the heater. Follow these instructions to  
make sure your heater is properly installed.  
The Hi-Delta pool heater is equipped with an external pump and bypass arrangement that blends outlet water with the inlet  
to increase the inlet water temperature, thereby reducing the likelihood of condensation forming on the heat exchanger. The  
pump also serves to circulate water through the heater form the main system piping.  
To complete the installation of the pool heater, the pool thermostat needs to be installed in the main return water line. This  
will insure that the heater will be energized at the right time. If the main water line is too far away from the heater and the  
capillary bulb will not reach it, locate the pool thermostat adjacent to the main line and run wires back to the heater. See Figure  
#9225.  
Adjustment of the bypass valve is critical to proper operation of the heater. The bypass valve should be adjusted to achieve  
an inlet water temperature of 100°F and an outlet water temperature between 120°F and 140°F. When starting with a cold pool,  
make initial adjustments. Make final adjustments when pool water approaches desired temperature.  
H BYPASS  
17  
AUTOMATIC CHLORINATORSAND CHEMICALFEEDERS  
All chemicals must be introduced and completely diluted into the pool or spa water before being circulated through the  
heater. Do not place chlorine tablets or bromine sticks in the skimmer. High chemical concentrations will result when the  
pump is not running (i.e. overnight).  
Chlorinators must feed downstream of the heater and have an anti-siphoning device to prevent chemical backup into the  
heater when the pump is shut off.  
NOTE: High chemical concentrates from feeders and chlorinators that are out of adjustment will cause very rapid  
corrosion to the heat exchanger in the heater. Such damage is not covered under the warranty.  
WINTERIZINGYOUR HEATER  
When heaters installed outdoors in freezing climate areas are to be shut down for the winter, please observe the following  
step-by-step procedure:  
1. Turn off manual main gas and main gas shut off. Remove the drain plug or open the drain cock located on the  
bottom header.  
SPAWATER CHEMISTRY  
NOTE: Chemical imbalance can cause severe damage to your heater and associated equipment. Maintain your water  
pH between 7.4 and 7.8 and total alkalinity between 100 and 150 p.p.m. If the mineral content and dissolved solids in the  
water become too high, scale forms inside the heat exchanger tubes, reducing heater efficiency and also damaging the  
heater. If the pH drops below 7.2, the heater will be severely damaged.  
NOTE: Heat exchanger damage resulting from chemical imbalance is not covered under the warranty.  
SINGLEPOOLHEATERAPPLICATION  
Fig. #9225  
18  
SECTION H: GAS SUPPLY CONNECTIONS  
DANGER:  
Make sure the gas on which the boiler will operate is the same type as specified on the boiler  
model and rating plate.  
Gas piping must have a sediment trap ahead of the boiler gas controls, and a manual shut-off valve located outside the heater  
jacket. A pounds to inches regulator must be installed to reduce to gas supply pressure to under 14" W.C. The regulator  
should be placed a minimum distance of 10 times the pipe diameter upstream of the boiler gas controls. All gas piping must  
be tested after installation in accordance with local codes. The boiler and its gas connection must be leak-tested before  
placing it in operation.  
Fig. #9226.1  
GAS SUPPLY CONNECTION  
CAUTION:  
The boiler and its manual shutoff valve must be disconnected from the gas supply during any pressure  
testing of the gas supply system at test pressures in excess of 1/2 PSIG (3.45 KPA). The boiler must be  
isolated from the gas supply piping system by closing the manual shutoff valve during any pressure  
testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG. Relieve test  
pressure in the gas supply line before reconnecting the boiler and its manual shut off valve to the gas  
supply line. FAILURETO FOLLOWTHIS PROCEDURE MAYDAMAGETHE GASVALVES. Over  
pressurized gas valves are not covered by warranty. The boiler and its gas connections shall be leak tested  
before placing the appliance in operation. Use soapy water for leak test: DO NOT use open flame.  
CAUTION:  
CAUTION:  
Do not use Teflon tape on gas line pipe thread. A pipe compound rated for use with gas systems is  
recommended. Apply sparingly only on male pipe ends.  
Support gas supply piping with hangers, not by the boiler or its accessories. Ensure the gas piping is  
protected from physical damage and freezing where required.  
GAS SUPPLY PRESSURE  
Aminimum of 7” W.C. and a maximum of 14” W.C. upstream gas pressure is required under load and no load conditions for  
natural gas. A minimum of 12” W.C. and a maximum of 14” W.C. is required for propane gas. The gas pressure regulator  
supplied on the boiler is for low pressure service. If upstream pressure exceeds 14" W.C, an intermediate gas pressure  
regulator, of the lockup type, must be installed.  
When connecting additional gas utilization equipment to the gas piping system, the existing piping must be checked to  
determine if it has adequate capacity.  
19  
GAS PRESSURE REGULATOR  
The gas valve pressure regulator(s) on the boiler are nominally preset at 3.5" W.C. for Natural gas, and 10.5" W.C. for Propane  
gas manifold pressure. The pressure at the gas valve outlet tap, measured with a manometer,while in operation should be 3.5  
± 0.1" W.C. for Natural gas and 10.5" ± 0.1" W.C. for Propane gas. If an adjustment is needed, turn the adjustment screw  
clockwise to increase pressure or counter-clockwise to lower pressure.  
20  
SECTION I: ELECTRICAL POWER CONNECTIONS  
Installations must follow these codes:  
·
National Electrical Code and any other national, state, provincial or local codes or regulations having  
jurisdiction.  
·
·
·
Safety wiring must be N.E.C. Class 1.  
Boiler must be electrically grounded as required by N.E.C.ANSI/NFPA70-latest edition.  
In Canada, C.S.A. C22. 1 C.E.C. Part 1.  
The boiler is wired for 120 Volts, 12AMPS. The voltage is indicated on the tie-in leads. Consult the wiring diagram shipped  
with the boiler in the instruction packet. The remote tank control stat, thermostat, or electronic boiler control as applicable,  
may be connected to the stage selector terminal (See wiring diagram). 24 Volts are supplied to this connection through the  
boiler transformer. DO NOT attach line voltage to the “TH” leads. Before starting the boiler check to insure proper voltage to  
the boiler and pump.  
ON/OFF  
Stage Selector  
FIELD-CONNECTEDCONTROLLERS  
Facto
Stage 2  
Stage 1  
Jumpe
If unit does not have a factory wired stage  
controller, the unit is factory-wired in On/Off  
configuration with other stage terminals  
jumpered.  
Control  
Control  
Stage 2  
Stage 2  
Stage 1  
To field-connect stage controller, remove fac-  
tory-installed jumper and wire stage control  
as shown.  
Control  
Stage 1  
Install a separate disconnect means for each load. Use appropriate-sized wire as defined by NEC, CSAand/or local code. All  
primary wiring should be 125% of minimum rating.  
It is strongly recommended that all individually-powered control modules and the boiler should be supplied from the same  
power source.  
SURGE PROTECTION  
Microprocessor-based and solid state controls are vulnerable to damage from voltage and amperage fluctuations in the  
power supply.All sensitive control components should be protected by a suitable commercial-grade surge protection device.  
If any of the original wire as supplied with the boiler must be replaced, it must be replaced with 105°C wire or its equivalent.  
CHECK THE POWER SOURCE  
WARNING:  
Using a volt-ohm meter (VOM), check the following voltages at the circuit breaker panel prior to  
connecting any equipment: Make sure proper polarity is followed and house ground is proven.  
FIGURE I-1  
CHECK POWER SOURCE  
BLACK  
CIRCUIT  
BREAKER  
VOLT-OHM  
METER  
WHITE  
GREEN  
GROUND  
A
B
C
Fig. # 9237  
AC = 108 VoltsAC Minimum, 132 VoltsAC MAX  
AB = 108 VoltsAC Minimum, 132 VoltsAC MAX  
21  
MAKING THE ELECTRICAL CONNECTIONS  
Refer to Fig. #9227 Wiring Connection, and Fig. #9233 or Fig. #9234 Wiring Diagram.  
1. Verify circuit breaker is properly sized by referring to boiler rating plate. Adedicated circuit breaker should be  
provided.  
2. Turn off all power to the boiler. Verify that power has been turned off by testing with a volt-ohm meter prior to  
working with any electrical connections or components.  
3. Observe proper wire colors while making electrical connections. Many electronic controls are polarity sensitive.  
Components damaged by improper electrical installation are not covered by warranty.  
4. Provide an external surge suppressor capable of maintaining system integrity.  
5. Provide overload protection and a disconnect means for equipment serviceability as required by local and state code.  
6. Install boiler controls, thermostats, or building management systems in accordance with the applicable manufacturer’s  
instructions.  
7. Conduit should not be used as the ground. There must be a solidly wired ground.  
NOTICE:  
A grounding electrode conductor shall be used to connect the equipment grounding conductors,  
the equipment enclosures, and the grounded service conductor to the grounding electrode.  
FIELD WIRING CONNECTION  
MAIN POWER AND  
PUMP POWER IN  
(ALTERNATE LOCATION  
AT OTHER END)  
ALTERNATE POWER  
IN LOCATIONS  
Fig. #9227  
22  
ELECTRICALCONNECTIONS - DOMESTIC HOTWATER  
CAUTION:  
DANGER  
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and  
dangerous operation. Verify proper operation after servicing.  
-SHOCKHAZARD  
Make sure electrical power to the heater is disconnected to avoid potential serious injury or damage to  
components.  
Installer action is required to electrically enable your Hi-Delta boiler to operate after making the power conections. You must  
make a connection on Terminal Block #3 for temperature control connections. This will be done based on the controller  
option selected with your boiler order.  
1. For Pool and Closed Loop Water Source Heat Pump applications, your boiler should be configured to operate in an ON/  
OFF firing mode. This means that you will connect a single-pole control to stage one of TB-3 (Terminals 1&2). Then jumper  
the remaining firing stages. For example, if your boiler is a 652, you will jumper stage two. Then your boiler will either be on  
at full fire, or it will be off.  
2. For multi-stage controller connections, connect each stage of the control to the corresponding stage of TB-3 in the  
boiler. Stage 1 of the boiler to stage 1 of the control. Stage 2 of the boiler to stage 2 of the control, and so on.  
Set the operating control at the setpoint in which you want the boiler to maintain. Ensure that the sensing bulb of the control  
is at the point in the system that will best maintain the temperature you want. For example, when you are heating a tank of  
water, you want the operating control sensor bulb in the tank.  
Consult the wiring diagram shipped with the boiler in the instruction packet. The "TH" leads are for the remote tank control  
through the boilers 24 volt transformer. DO NOT attach line voltage to the "TH" leads. Before starting boiler check to insure  
proper voltage to boiler and pump.  
SINGLE  
STAGE  
2-STAGE  
TANKSTAT  
TANKSTAT  
ig. #9138.1  
Fig. #9138.2  
BREAKTHE WIRE NUTATTHE  
BOILER "TH" CONNECTIONSAND  
ATTACHTO THE SINGLETANKSTAT  
PER ILLUSTRATION  
BREAKTHE WIRE NUTATTHE  
BOILER "TH" CONNECTIONSAND  
ATTACH TO THE DUALTANKSTAT  
PER ILLUSTRATION  
Boiler must be electrically grounded in accordance with National Electrical CodeANSI/NFPANo. 70, and CSAC22.1  
C.E.C. Part 1 in Canada.  
NOTES:  
1. Field installed ground to inside of junction box.  
2. If any of the original wire as supplied with the boiler must be replaced, it must be replaced with 105°C wire or its  
equivalent.  
3. “TH” leads connect to terminal block 3 (See wiring diagram).  
23  
SECTION J: VENTING CONNECTIONS  
GENERAL  
CAUTION:  
Proper installation of flue exhaust venting is critical for the safe and efficient operation of the boiler.  
Definition ofAppliance Categories  
Boilers are divided into four categories based on the pressure produced in the exhaust and the likelihood of condensate  
production in the vent.  
Category I.  
Category II.  
Category III.  
Category IV.  
A boiler which operates with a non-positive vent static pressure and with a vent gas tempera  
ture that avoids excessive condensate production in the vent.  
A boiler which operates with a non-positive vent static pressure and with a vent gas tempera  
ture that may cause excessive condensate production in the vent.  
A boiler which operates with a positive vent pressure and with a vent gas temperature that  
avoids excessive condensate production in the vent.  
A boiler which operates with a positive vent pressure and with a vent gas temperature that  
may cause excessive condensate production in the vent.  
See Table J-1 for appliance category requirements for the Hi-Delta.  
Note: For additional information on appliance categorization, see appropriate ANSI Z21 Standard and the latest  
edition Standard of National Fuel Gas Code or in Canada, the latest edition of CGA Standard B149 Installation  
Code for Gas Burning Appliances and Equipment, or applicable provisions of local building codes.  
Determination ofAppliance Category forVenting Purposes and VentingArrangements  
WARNING:  
Contact the manufacturer of the vent material if there is any question about the appliance categoriza-  
tion and suitability of a vent material for application on a Category III or IV vent system. Using  
improper venting materials can result in personal injury, death or property damage.  
24  
* As defined in the latest edition of the National Fuel Gas Code, or in Canada, the latest edition of the CAN/CGA  
B149.1 and B149.2.  
TABLEJ-1  
Support of Vent Stack  
The weight of the vent stack or chimney must not rest on the boiler vent connection. Support must be provided in  
compliance with applicable codes. The vent should also be supported to maintain proper clearances from combustible  
materials.  
Use insulated vent pipe spacers where the vent passes through combustible roofs and walls.  
Vent Terminal Location  
NOTICE:  
During winter months check the vent cap and make sure no blockage occurs from build up of snow.  
Condensate can freeze on the vent cap. Frozen condensate on the vent cap can result in a blocked  
flue condition.  
General  
Give special attention to the location of the vent termination to avoid possibility of property damage or personal injury.  
a) Gases may form a white vapor plume in winter. The plume could obstruct a window view if the termination is installed in  
close proximity to windows.  
b) Prevailing winds could cause freezing of condensate and water/ice build-up on building, plants or roof.  
c) The bottom of the vent terminal and the air intake shall be located at least 12 inches above grade.  
d) Un-insulated single-wall metal vent pipe shall not be used outdoors on cold climates for venting gas utilization equip-  
ment.  
e) Through-the-wall vents for Category II and IV appliances and non-categorized condensing appliances shall not termi-  
nate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be  
detrimental to the operation of regulators, relief valves, or other equipment. Where local experience indicates that  
condensate is a problem with Category I and III appliances, this provision shall also apply.  
f) Locate and guard vent termination to prevent accidental contact by people or pets.  
g) DO NOT terminate vent in window well, stairwell, alcove, courtyard or other recessed area, unless previously approved  
by local authority.  
h) DO NOT terminate above any door, window, or gravity air intake. Condensate can freeze, causing ice formations.  
i) Locate or guard vent to prevent condensate from damaging exterior finishes. Use a 2’ x 2’ rust resistant sheet metal  
backing plate against brick or masonry surfaces.  
j) DO NOT extend exposed vent pipe outside of building. Condensate could freeze and block vent pipe.  
US Installations - Refer to latest edition of National Fuel Gas Code  
Vent termination requirements are as follows:  
a) Vent must terminate at least four (4) feet below, four (4) feet horizontally, or one (1) foot above any door, window or  
gravity air inlet to the building.  
b) The vent must not be less than seven (7) feet above grade when located adjacent to public walkways.  
c) Terminate vent at least three (3) feet above any forced air inlet located within ten (10) feet.  
d) Vent must terminate at least four (4) feet horizontally, and in no case above or below unless four (4) feet horizontal  
distance is maintained, from electric meters, gas meters, regulators, and relief equipment.  
e) Terminate vent at least six (6) feet away from adjacent walls.  
f) DO NOT terminate vent closer than five (5) feet below roof overhang.  
g) The vent terminal of a direct vent appliance with an input over 50,000 Btu per hour shall require a 12-inch vent terminal  
clearance.  
h) Terminate vent at least one (1) foot above grade, including normal snow line.  
i) Multiple direct vent installations require a four (4) foot clearance between vent caps.  
26  
Canada Installations - Refer to latest edition of CAN/CGA-B149.1 and .2  
A vent shall not terminate:  
a) Directly above a paved sidewalk or driveway which is located between two single family dwellings and serves both  
dwellings  
b) Less than 7 ft.(2.13m)above a paved sidewalk or paved driveway located on public property  
c) Within 6 ft(1.8m) of a mechanical air supply inlet to any building  
d) Above a meter/regulator assembly within 3 ft(900mm) horizontally of the vertical centre-line of the regulator  
e) Within 6 ft.(1.8m) of any gas service regulator vent outlet  
f) Less than 1 ft.(300mm) above grade level  
g) Within the 3 ft.(1m) of a window or door which can be opened in any building, any non-mechanical air supply inlet to any  
building or the combustion air inlet of any other appliance  
h) Underneath a verandah, porch or deck, unless  
(i) the verandah, porch or deck is fully open on a minimum of two sides beneath the floor, and  
(ii) the distance between the top of the vent termination and the underside of the verandah, porch or deck is greater  
than 1 ft(25cm).  
Venting Installation Tips  
Support piping:  
·
·
·
horizontal runs- at least every five (5) feet.  
vertical runs - use braces:  
under or near elbows  
Follow items listed below to avoid personal injury or property damage.  
·
·
·
·
Cut nonmetallic intake pipe with fine-toothed hacksaw (34 teeth per inch).  
Do not use nonmetallic intake pipe or fittings that are cracked or damaged.  
Do not use nonmetallic intake fittings if they are cut or altered.  
Do not drill holes, or use screws or rivets, in nonmetallic intake pipe or fittings.  
To make metallic vent joints:  
·
·
Do not install seams of vent pipe on bottom of runs.  
100% Seal all joints and seams with silicone sealant.  
WARNING:  
Examine the venting system at least once a year. Check all joints and vent pipe connections for  
tightness, corrosion or deterioration.  
NOTE: The words "Flue Exhaust", "Flue" and "Exhaust Vent" are used interchangeably.  
VENTING CONFIGURATIONS  
For boilers connected to gas vents or chimneys, vent installations shall be in accordance with Part 7, Venting of Equipment,  
of the latest edition of National Fuel Gas Code, or in Canada, the latest edition of CAN/CGA-B149.1 and .2 Installation Code  
for Gas Burning Appliances and Equipment, or applicable provisions of local building codes.  
27  
SECTION J-1  
Natural Draft Vertical Venting (Category I)  
10' OR LESS  
VENT CAP  
2' MIN  
2' MIN  
VENT PIPE  
COMBUSTION  
AIR FILTER  
BOILER UNIT  
Fig. #9228  
NATURALDRAFTVERTICALVENT  
NOTE:  
**Vent lengths are based on a lateral length of 2 feet. Refer to the latest edition of the National Fuel Gas Code for further  
details. (ANSI Z223.1)  
28  
Natural Draft Vertical Venting System Installation  
Natural draft venting uses the natural buoyancy of the heated flue products to create a thermal driving head that expels the  
exhaust gases from the flue. The negative draft must be within the range of -.01” to -.10” negative W.C. as measured 12 inches  
from the appliance flue outlet to insure proper operation. Vent material must be listed by a nationally recognized test agency.  
The maximum and minimum venting length for Category I appliance shall be determined per the latest edition of the National  
Fuel Gas Code (U.S.) or B149.1 and .2 Installation Code (Canada).  
The diameter of vent flue pipe should be sized according to Part 11 of the latest edition of the National Fuel Gas Code (U.S.)  
and part 7 and appendix B of the CAN/CGA-B149.1 and .2 installation code (Canada). The minimum flue pipe diameter for  
conventional negative draft venting using double-wall B type vent is 5” for 302, 6” for 402 & 502 and 8" 652, 752 & 902.  
NOTICE:  
Vent Adapter will have to be used to connect B vent to the unit.  
The connection from the appliance vent to the stack must be as direct as possible and shall be the same diameter as, or larger  
than the vent outlet. The horizontal breaching of a vent must have an upward slope of not less than 1/4 inch per linear foot  
from the boiler to the vent terminal. The horizontal portions of the vent shall also be supported for the design and weight of  
the material employed to maintain clearances and to prevent physical damage or separation of joints.  
Natural Draft Vertical Vent Termination  
The vent terminal should be vertical and should terminate outside the building at least two (2) feet above the highest point  
of the roof that is within 10 feet. The vent cap should have a minimum clearance of four (4) feet horizontally from and in no  
case above or below (unless a four (4) foot horizontal distance is maintained) electric meters, gas meters, regulators and relief  
equipment. The distance of the vent terminal from adjacent public walkways, adjacent buildings, open windows and building  
openings must be consistent with the National Fuel Gas Code, or in Canada, the latest edition of CAN/CGA-B149 Installation  
Code for Gas BurningAppliances and Equipment. Gas vents supported only by flashing and extended above the roof more  
than five feet should be securely guyed or braced to withstand snow and wind loads.  
CAUTION:  
Listed vent cap terminal must be used and sized adequately to evacuate the flue products from the  
boilers.  
Natural Draft Vertical Venting With Common Venting System, Category I Appliance Only  
Manifolds that connect more than one boiler to a common chimney must be sized to handle the combined load. Consult  
available guides for proper sizing of the manifold and the chimney.At no time should the area of the vent be less than the area  
of the largest boiler exhaust outlet.  
WARNING:  
CAUTION:  
Vent connectors serving appliances vented by natural draft shall not be connected into any portion of  
mechanical draft systems operating under a positive pressure.  
Vent connectors for natural draft venting systems must be type “B” vent or better.  
29  
Common venting systems may be too large when an existing unit is removed.At the time of removal of an existing appliance,  
the following steps must be followed with each appliance remaining connected to the common venting system placed in  
operation, while the other appliances remaining connected to the common venting system are not in operation.  
a) Seal any unused opening in the common venting system.  
b) Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or  
restriction, leakage, corrosion or other unsafe condition.  
c) Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances  
remaining connected to the common venting system are located and other spaces of the building. Turn on clothes  
dryers and any appliance not connected to the common vent system. Turn on any exhaust fans, such as range  
hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate summer exhaust fan. Close  
fireplace dampers.  
d) Place in operation the appliances being inspected. Follow the manufacturers instructions for lighting each appli-  
ance. Adjust thermostat so appliance will operate continuously.  
e) Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match  
or candle, or smoke from a cigarette, cigar or pipe, toilet paper trick. For the Hi-Delta, check the pressure at a pressure  
tap located 12 inches above the bottom joint of the first vertical vent pipe. Pressure should be anywhere between  
0 to -.1 inch water column.  
f) After it has been determined that each appliance remaining connected to the common venting system properly  
vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and other gas burning  
appliances to their previous conditions of use.  
g) Any improper operation of the common venting system should be corrected so that the installation conforms with  
the latest edition of the National Fuel Gas Code,ANSI Z223.1, in Canada, the latest edition of CAN/CGA-B 149.1 and  
.2 Installation Code for Gas BurningAppliances and Equipment. When re-sizing any portion of the common venting  
system, the common venting system should be re-sized to approach the minimum size as determined using the  
appropriate tables in Appendix G in the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada,  
Appendix B of the latest edition of the Installation Code for Gas Burning Appliances and Equipment.  
30  
SECTION J-2  
Horizontal Thru-Wall Venting (Category III)  
OPTIONAL FLUE  
EXHAUST VENTING  
COMBUSTION  
AIR FILTER  
9"  
MIN.  
FLUE EXHAUST  
VENT CAP  
BOILER UNIT  
INSULATED  
EXHAUST  
VENTING  
CONDENSATE  
TRAP  
12" MIN.  
Fig. #9229.1  
HORIZONTALTHRU-WALLVENTING(CATEGORY III) TABLE  
HorizontalThru-wall Venting System (Category III) Installation  
These installations utilize the boiler-mounted blower to vent the combustion products to the outdoors. Combustion air is  
taken from inside the room and the vent is installed horizontally through the wall to the outdoors. Adequate combustion and  
ventilation air must be supplied to the boiler room in accordance with the National Fuel Gas Code or, in Canada, the latest  
edition of CAN/CGA-B149.1 and .2 Installation Code for Gas BurningAppliances and Equipment.  
31  
The total length of the horizontal thru-wall exhaust vent system should not exceed seventy (70) feet in length. If horizontal  
run exceeds 70 feet, an appropriately sized extractor must be used. To maintain proper operation pressure reading must be  
between -.01 to -.1 W.C. as measured 12 inches from the appliance flue outlet. Each elbow used is equal to ten (10) feet of  
straight pipe. This will allow installation in one of the four following combinations.  
·
·
·
·
70’ of straight flue pipe.  
60' of straight flue pipe and one elbow.  
50' of straight flue pipe and two elbows.  
40' of straight pipe and three elbows.  
The vent cap is not considered in the overall length of the venting system.  
The vent must be installed to prevent the flue gas leakage. Care must be taken during assembly to insure that all joints are  
sealed properly and are airtight.  
The vent must be installed to prevent the potential accumulation of condensate in the vent pipes. It is recommended that:  
a) The vent be installed with a slight downward slope of not more than 1/4" per foot of horizontal run to the vent terminal.  
b) The vent be insulated through the length of the horizontal run.  
For appliances installed in extreme cold climate, it is recommended that:  
a) The vent be installed with a slight upward slope of not more than 1/4" per foot of horizontal run to the vent terminal. In  
this case, an approved condensate trap must be installed per applicable codes.  
b) The vent be insulated through the length of the horizontal run.  
A sleeve has been added inside the flue box of all Hi Delta heaters, as a redundant heat insulator to eliminate internal  
condensation. It is to be removed only when the application calls for venting through the rear of the unit.  
To remove sleeve, remove the rear exhaust cover panel and lift sleeve upward. Note: The sleeve is not mechanically  
attached, and will lift upward with a rocking motion. Use a knife or razor blade to cut through and loosen the RTV  
sealant.  
HI DELTA SLEEVE FLUE CONVERSION  
Fig. #9436  
32  
Horizontal Thru-wall Direct Vent Termination  
The flue exhaust direct vent cap MUST be mounted on the exterior of the building. The direct vent cap cannot be installed in  
a well or below grade. The direct vent cap must be installed at least one (1) foot above ground level and above normal snow  
levels. The Raypak supplied flue exhaust direct vent cap must be utilized.  
WARNING:  
No substitutions of flue pipe or vent cap material are allowed. Such substitutions would jeopardize the  
safety and health of inhabitants.  
The Stainless Steel direct vent cap must be furnished by the boiler manufacturer in accordance with its  
listing.  
Use only the special gas vent pipes listed for use with category III gas burning heaters, such as the stainless steel Saf-T vent  
by Heat Fab Inc. (413-744-2356). Pipe joints must be positively sealed. Follow carefully the vent manufacturers installation  
instructions.  
33  
DIRECT VENT  
Horizontal Thru-wall Venting  
(Category III)  
SECTION J-3  
9"  
MIN.  
EXHAUST  
VENT  
INTAKE  
VENT  
36"  
MIN.  
CONDENSATE  
TRAP  
BOILER  
UNIT  
AIR  
FILTER  
6"  
MIN.  
12" MIN.  
Fig. #9230.1  
HORIZONTALTHRU-WALLVENTINGTABLE  
34  
Horizontal Thru-wall Direct Vent System (Category III) Installation  
These installations utilize the boiler mounted blower to draw combustion air from outdoors and vent combustion products to  
the outdoors.  
The total length of the thru-wall exhaust vent cannot exceed forty (40) feet in length for the flue outlet. Each elbow used is  
equal to ten (10) feet of straight pipe. This will allow installation in one of the three following combinations.  
·
·
·
40’ of straight combustion air pipe.  
30' of straight combustion air pipe and one elbow.  
20' of straight combustion air pipe and two elbows.  
The total length air supply pipe cannot exceed forty (40) feet in length for the combustion air inlet. Each elbow used is equal  
to ten (10) feet of straight pipe. This will allow installation in one of the three following combinations.  
·
·
·
40’ of straight flue pipe  
30' of straight flue pipe and one elbow.  
20' of straight flue pipe and two elbows.  
The flue exhaust direct vent cap is not considered in the overall length of the venting system.  
Care must be taken during assembly that all joints are sealed properly and are airtight.  
The vent must be installed to prevent the potential accumulation of condensate in the vent pipes. It is recommended that:  
a) The vent be installed with a slight downward slope of not more than 1/4" per foot of horizontal run to the vent terminal.  
b) The vent be insulated through the length of the horizontal run.  
For appliances installed in extreme cold climate, it is recommended that:  
a) The vent be installed with a slight upward slope of not more than 1/4" per foot of horizontal run to the vent terminal. In  
this case, an approved condensate trap must be installed per applicable codes.  
b) The intake vent be insulated through the length of the horizontal run.  
Horizontal Thru-wall Direct Vent Termination  
The flue exhaust direct vent cap MUST be mounted on the exterior of the building. The direct vent cap cannot be installed in  
a well or below grade. The direct vent cap must be installed at least one (1) foot above ground level and above normal snow  
levels.  
Multiple direct vent caps MUST NOT be installed with one combustion air inlet directly above a direct vent cap. This vertical  
spacing would allow the flue products from the direct vent cap to be pulled into the combustion air intake installed above.  
This type of installation can cause non warrantable problems with components and poor operation of the unit due to the  
recirculation of flue products. Multiple direct vent caps should be installed in the same horizontal plane with a three (3) foot  
clearance from the side of one vent cap to the side of the adjacent vent cap(s).  
Combustion air supplied from outdoors must be free of particulate and chemical contaminants. To avoid a blocked flue  
condition, keep the vent cap clear of snow, ice, leaves, debris, etc.  
WARNING:  
No substitutions of flue pipe or vent cap material are allowed. Such substitutions would jeopardize the  
safety and health of inhabitants.  
TheStainlessSteelflueexhaustdirectventcapmustbefurnishedbytheboilermanufacturerinaccordancewithitslisting.  
Use only the special gas vent pipes listed for use with category III gas burning heaters, such as the stainless steel Saf-T vent  
by Heat Fab Inc. (800-772-0739). Pipe joints must be positively sealed. Follow carefully the vent manufacturers installation  
instructions.  
35  
SECTION J-4  
DIRECT VENT  
Vertical Venting (Category I)  
3'  
VENT  
MIN.  
CAP  
3' MIN.  
1' MIN.  
INTAKE VENT  
EXHAUST  
VENT  
BOILER  
UNIT  
AIR FILTER  
Fig. #9231.1  
VERTICALVENTINGTABLE  
36  
Vertical Direct Vent System Installation  
These installations utilize the boiler mounted blower to draw combustion air from outdoors and uses the natural buoyancy  
of the heated flue products to create a thermal driving head that expels the exhaust gases from the flue. The negative draft  
must be within the range of- 0.01 to- 0.10” negative W.C. as measured 12 inches from the appliance outlet to insure proper  
operation. The vent material must be in accordance with the above instructions for vent materials. Vent material must be listed  
by a nationally recognized test agency.  
The maximum and minimum venting length for Category I appliance shall be determined per the latest edition of the National  
Fuel Gas Code (U.S.) and CAN/CGA-B149.1 and .2 Installation Code (Canada).  
The connection from the appliance exhaust vent to the stack must be as direct as possible and should be the same as or larger  
than the vent outlet. The vent must be installed to prevent accumulation of condensate and, where necessary, have means  
provided for drainage of condensate. The horizontal breaching of a vent must have an upward slope of not less than 1/4 inch  
per linear foot from the boiler to the vent terminal. The horizontal portions of the vent shall also be supported for the design  
and weight of the material employed to maintain clearances and to prevent physical damage or separation of joints.  
It is recommended that in colder climates, the intake vent be insulated.  
Vertical Direct Vent Termination  
The exhaust vent terminal should be vertical and should terminate outside the building at least two (2) feet above the highest  
point of the roof within 10 feet. The vent cap should have a minimum clearance of four (4) feet horizontally from and in no case  
above or below (unless a four (4) foot horizontal distance is maintained) electric meters, gas meters, regulators and relief  
equipment. The distance of the vent terminal from adjacent public walkways, adjacent buildings, open windows and building  
openings must be consistent with the National Fuel Gas Code, or in Canada, the latest edition of CAN/CGA-B149.1 and .2.  
Installation Code for Gas BurningAppliances and Equipment. Gas vents supported only by flashing and extended above the  
roof more than five feet should be securely guyed or braced to withstand snow and wind loads.  
The vertical direct vent cap is designed for roof top mounting only. The air inlet opening MUST be installed one (1) foot  
above the roof line or above normal snow levels that might obstruct combustion air flow. This dimension is critical to the  
correct operation of the boiler and venting system and reduces the chance of blockage from snow. The vent cap must have  
a minimum 3 foot clearance from the air inlet opening.  
37  
SECTION J-5  
Outdoor Installation  
Outdoor models are self -venting when installed with the factory-supplied restricted direct vent cap and require no additional  
vent piping. This special vent cap is provided with the boiler in accordance withAGA/CGArequirements. It must be installed  
directly on the boiler. See Section B for correct clearances.  
Care must be taken when locating the outdoor unit because the flue gases discharged from the vent hood can condense as  
they leave the hood. Improper location can result in damage to adjacent structures or building finish. For maximum efficiency  
and safety, the following precautions must be observed:  
a) Outdoor models must be installed outdoors and must use the outdoor vent hood supplied by the manufacturer.  
b) Periodically check venting system. The boiler’s venting areas must never be obstructed in any way and minimum  
clearances must be observed to prevent restriction of combustion and ventilation air. Keep area clear and free of  
combustible and flammable materials.  
c) Do not locate adjacent to any window, door walkway, or gravity air intake. The vent must be located a minimum of  
four (4) feet horizontally, or four (4) feet below, or one (1) foot above such areas.  
d) Install above grade level and above normal snow levels.  
e) Vent terminal must be at least 3 feet above any forced air inlet located within 10 feet.  
f) Adjacent brick or masonry surfaces must be protected with a rust-resistant sheet metal plate.  
g) Multiple Outdoor Vent installations require a four (4) feet clearance between vent caps.  
NOTICE:  
NOTICE:  
Condensate can freeze on the vent cap. Frozen condensate on the vent cap can result in a blocked flue  
condition.  
On snow prone areas it is recommended that the combustion air terminal be located on the rear of  
the appliance to minimize snow blockage.  
The restricted vent cap must be furnished by the boiler manufacturer in accordance with its listing.  
An outdoor air filter, supplied by the manufacturer is mounted on the boiler.  
HIDELTAOUTDOORVENTKITANDINSTRUCTIONS  
NOTICE:  
DANGER:  
These instructions are intended for use by qualified personnel specifically trained and experienced in  
the installation of this type of heating equipment and related system components. Installation and  
service personnel are required to be licensed in some states. Persons not qualified shall not attempt  
repairs according to these instructions.  
-SHOCKHAZARD  
Make sure electrical power to the heater is disconnected to avoid damage to components, potential  
serious personal injury or death. Make sure the gas to the heater has been shut off.  
Vent Cap  
THISKITINCLUDES:  
1- Vent cap  
1- Vent collar  
1- Collector  
8- Self tapping screws  
4- Tinnerman clips  
4- Screws  
Collector  
Cap  
38  
HI DELTA OUTDOOR VENT INSTRUCTIONS  
1. Turn off the power and shut off the gas to heater.  
Heater as shipped  
2. Slide the vent collar from kit over the collar on heater  
as shown in Fig. 1.  
3. Drill a 3/16” pilot hole into the heater collar through  
each of the holes on the lower vent collar. See Fig. 1.  
Fig. 1  
4. Take four of the self-tapping screws from the kit and  
screw into the holes as shown in Fig. 2.  
Fig. 2  
5. Slide tinnerman clips over the small bracket as shown  
in Fig. 3.  
Fig. 3  
39  
HI DELTA OUTDOOR VENT INSTRUCTIONS CONTINUED  
6. Slide the collector over vent collar, aligning the holes  
over the openings in the tinnerman clips as shown  
in Fig. 4.  
Fig. 4  
7. Take four of the screws from the kit and screw into the  
holes as shown in Fig. 4.  
8. Slide the vent cap down into the vent collar as shown  
in Fig. 5.  
Fig. 5  
9. Drill a 3/16” pilot hole into the vent cap through each  
of the upper holes in the vent collar. See Fig. 6. Also  
see finished assembly below.  
Fig. 6  
10. Take four of the self tapping screws from the kit and  
screw into the holes as shown in Fig. 6. Also see  
finished assembly below.  
11. Turn the power on and turn gas on.  
Finished assembly  
40  
HI DELTA FILTER BOX KIT  
NOTICE:  
These instructions are intended for use by qualified personnel specifically trained and experienced  
in the installation of this type of heating equipment and related system components. Installation and  
service personnel are required to be licensed in some states. Persons not qualified shall not attempt  
repairs according to these instructions.  
Vent collar  
Air intake collar  
THISKITINCLUDES:  
1- Filter box  
1- Decal (attached)  
6- Screws  
MODEL  
992-1532  
1802-2342  
PARTNUMBER  
#007101- 8”  
#007102- 10”  
1- Instructions  
Heater as shipped  
HI DELTA FILTER BOX INSTRUCTIONS  
NOTICE:  
These instructions pertain only to units installed outdoors only. All Hi Delta units are shipped with the  
air intake collar mounted temporarily on the top of the heater for shipping purposes. If this is to be  
installed outdoors, the air intake collar and filter box must be relocated to the back of the unit to prevent  
recirculation of flue products.  
1. Turn off the gas and power to the unit.  
Air intake  
collar  
Vent  
collar  
2. Remove the four screws holding the air intake collar on  
the top of the unit.  
3. Remove the four screws holding the cover plate. See Fig. 1.  
Cover  
plate  
4. Remove the white gasket paper off the air intake collar.  
5. Align the four holes of the air intake collar over the four  
holes on the opening on the back of the heater.  
6. Mount air intake collar on back of the heater using four  
screws.  
Fig. 1 Back of heater  
7. Remove the white gasket paper off the cover plate.  
8. Align the four holes of the cover plate over the opening  
on the top of the heater.  
Filter  
9. Mount the cover plate using four screws.  
Align filter  
warning  
box to edges  
10. Hold the box over the air intake filter warning decal  
facing outward and align the top and side edges as  
shown in Fig. 2.  
Fig. 2 Back of heater  
41  
HI DELTA FILTER BOX INSTRUCTIONS CONTINUED  
11. Mark the four holes through filter box for screw locations.  
Air intake  
collar  
12. Using a 1/16 drill bit, drill a pilot hole in each of the holes  
previously marked.  
13. Mount the filter box to the unit using four screws provided  
in the kit.  
14. Install filter under filter box on top of air intake. See Fig. 3.  
NOTE: The filter media fits loosely in the filter box. When  
the fans energize, the filter is drawn onto the top  
of the collar and is held in place by the suction.  
The checked side of filter sits on air intake collar.  
Side view  
15. Install two screws in the holes behind cover plate.  
See Fig. 4.  
Fig. 3  
Filter  
Install screws here  
Fig. 4  
42  
SECTION K: CONTROLS  
WARNING:  
Installation, adjustment and service of boiler controls including timing of various operating  
functions must be performed by a qualified installer, service agency or the gas supplier. Failure to  
do so may result in control damage, boiler malfunction, property damage, personal injury, or death.  
WARNING:  
Turn off the power to the boiler before installation, adjustment or service of the Central Point Wiring  
board or any boiler controls. Failure to do so may result in board damage, boiler malfunction,  
property damage, personal injury, or death.  
CAUTION:  
CAUTION:  
This appliance has provisions to be connected to more than one (1) supply source. To reduce the risk  
of electric shock, disconnect all such connections before servicing.  
Risk of electric shock. More than one (1) disconnect switch may be required to de-energize the  
equipment before servicing.  
VIEWOF EXTERNALLED INDICATOR DECAL  
TABLE L-1 LED INDICATORS  
43  
Boiler Sequence of Operations  
HI-DELTAModel 302-402  
The black (hot) wire leads you directly to the Main Power Switch. This switch is located at the bottom right-front corner of  
the control compartment. When the main power switch is placed in the “ON” position, both the 120 v and 24 v terminal blocks  
on the Main Circuit Board will be powered and the power light will turn on. When theAuto On- Off switch is turned ON, the  
following 24 v safety components are immediately energized: Low Water Cut-off, Blocked Vent Switch, Manual Reset Limit  
Control, Low Gas Pressure Switch (optional) and the High Gas Pressure Switch (optional). At this point if all the preceding  
safety switches are closed, then Relay K. 1 (n.c.) will be energized and the safety light will turn off. The boiler is now ready  
for a call for heat.  
When STAGE 1 calls for heat, the CALLFOR HEAT LIGHT will turn on. The Economaster Board will be energized and the  
pump will turn on. If the pump generates enough flow to activate the flow switch, the flow light would turn on, then power will  
be applied to the thermostat terminal of the Ignition Module and the Blower will activate. TheAir Pressure Switch would then  
close and the pressure switch terminal on the Ignition Module will be energized, the blower light will turn on. The Unit will  
now undergo a 15 second pre-purge. After the pre-purge cycle, Hot Surface Igniter will heat up. The heat-up period takes  
about 30 seconds after which a trial for ignition is initiated. During the trial for ignition, which lasts for four seconds, power  
is applied to Firing Valve No. 1. If within four seconds, the Remote Sensor establishes flame rectification, Firing Valve No. 1  
stays open and the Stage 1 light will turn on. Also, the Valve terminal from the Ignition Module will power Relay K2.  
When Stage 2 calls for heat, power will be applied to Firing Valve No. 2 (Solenoid Gas Valve located on the lower manifold),  
and the Stage 2 light will turn on.  
44  
HI-DELTAModel 502-752  
The black (hot) wire leads you directly to the Main Power Switch. This switch is located at the bottom right-front corner of  
the control compartment. When the main power switch is placed in the “ON” position, both the 120 v and 24 v terminal blocks  
on the Main Circuit Board will be powered and the power light will turn on. When theAuto On- Off switch is turned ON, the  
following 24 v safety components are immediately energized: Low Water Cut-off, Blocked Vent Switch, Manual Reset Limit  
Control, Low Gas Pressure Switch (optional) and the High Gas Pressure Switch (optional). At this point if all the preceding  
safety switches are closed, then Relay K 1 (n.c.) will be energized and the safety light will turn off. The boiler is now ready  
for a call for heat.  
When STAGE 1 calls for heat, the CALLFOR HEAT LIGHT will turn on. The Economaster Board will be energized and the  
pump will turn on. If the pump generates enough flow to activate the flow switch, the flow light will turn on, then power will  
be applied to the thermostat terminal of the Ignition Module and the Blower will activate.TheAir Pressure Switch will close,  
and the pressure switch terminal on the Ignition Module will be energized the blower light will turn on. The Unit will now  
undergo a 15 second pre-purge. After the pre-purge cycle, Hot Surface Igniter will heat up. The heat-up period takes about  
30 seconds after which a trial for ignition is initiated. During the trial for ignition, which lasts for four seconds, power is  
applied to Firing Valve No. 1. If within four seconds, the Remote Sensor establishes flame rectification, the Firing Valve No.  
1 stays open and the Stage 1 light will turn on.Also, the Valve terminal from the ignition Module will power Relays K2, and  
K3.  
When Stage 2 calls for heat, power will pass through the Time Delay Relay, then after 10 seconds through Relay K2, and then  
applied to Firing Valve No. 2, and the Stage 2 light will turn on.  
45  
HI-DELTAModel902  
The black (hot) wire leads you directly to the Main Power Switch. This switch is located at the bottom right-front corner  
of the control compartment. When the main power switch is placed in the “ON” position, both the 120 v and 24 v terminal  
blocks on the Main Circuit Board will be powered and the power light will turn on. When the Auto On- Off switch is  
turned ON, the following 24 v safety components are immediately energized: Low Water Cut-off, Blocked Vent Switch,  
Manual Reset Limit Control, Low Gas Pressure Switch (optional) and the High Gas Pressure Switch (optional).At this  
point if all the preceding safety switches are closed, then Relay No. 1 (n.c.) will be energized and the safety light will turn  
off. The boiler is now ready for a call for heat.  
When STAGE 1 calls for heat, the CALL FOR HEAT LIGHT will turn on. The Economaster Board will be energized and the  
pump will turn on. If the pump generates enough flow to activate the flow switch, the flow light will turn on, power will be  
applied to the thermostat terminal of the Ignition Module and the Blower will activate. The Air Pressure Switch will close,  
and the pressure switch terminal on the Ignition Module will be energized the blower light will turn on. The Unit will now  
undergo a 15 second pre-purge. After the pre-purge cycle, Hot Surface Igniter will heat up. The heat-up period takes  
about 30 seconds after which a trial for ignition is initiated. During the trial for ignition, which lasts for four seconds,  
power is applied to Firing Valve No. 1. If within four seconds, the Remote Sensor establishes flame rectification, then  
Firing Valve No. 1 stays open and the Stage 1 light will turn on. Power from the Valve terminal will power Relay K2 and K3.  
Power will be applied to Time Delay Relay No. 1 and after ten seconds Firing Valve 1Awill turn on.  
When Stage 2 calls for heat, power will pass through Time Delay Relay No. 2, then after 10 seconds through Relay K4,  
and then Firing Valve No. 2. The Stage 2 light will come on also, at this time.  
46  
IGNITION CONTROL MODULE  
The interrupted proved ignition device conserves energy. When additional heat  
is needed, the combustion air blower starts to purge all air from the combustion  
chamber for about 15 seconds. On proof of air flow, the air proving switch closes  
and the igniter is energized, eliminating the fuel costs of maintaining a constant  
pilot. To assure safe operation, the gas valve cannot open until the pilot igniter is  
verified. The 100% igniter safety is an electronic device which closes the main gas  
valve within 8/10 of a second whenever the flame is interrupted. Main burner is  
automatically lit when the device is powered and pre-purged. Unit performs its  
own safety check and opens the main valve only after the igniter is proven to be  
capable of ignition.  
Fig #9322  
IGNITIONMODULE  
HIGH LIMIT (MANUAL RESET)  
The boiler is equipped with a manual reset high limit temperature device. Push the  
reset button and adjust the setting to 30° F or 40° F above desired operating  
temperature.  
Drw. #8644  
Fig. J-3  
MANUALRESETHIGHLIMIT  
FLOW SWITCH  
Dual-purpose control shuts off boiler in case of pump failure or low water flow.  
Mounted and wired in series with the main gas valve. Check with Manufacturer for  
proper paddle size. Utilize correct paddle size for proper operation.  
NOTICE:  
Flow switch will not operate if flow is less than 20 GPM.  
Drw. #8241  
Fig. J-4  
FLOWSWITCH  
OPERATINGCONTROL  
The heater may be equipped with different types of operating controls. Consult  
data sheet supplied with installation instructions. See Section L for adjustment  
safety precautions on domestic hot water applications.  
Drw. #8643  
THERMOSTATCONTROL  
47  
LOW WATER CUT OFF (OPTIONAL)  
The low water cut off automatically shuts down the burner whenever  
water level drops below the level of the sensing probe. A 3 second  
time delay prevents premature lockout due to temporary conditions  
such as power fluctuations or air pockets.  
Drw. #8996  
Fig.# J-5  
LOW WATER CUTOFF  
HIGHAND LOW GAS PRESSURE SWITCHES  
The low gas pressure switch (optional) mounts upstream of the gas valve  
to ensure that sufficient gas pressure is present for proper regulator  
performance. The low gas pressure switch automatically shuts down the  
boiler if gas supply drops below the factory setting of 5" W.C. for Natural  
gas, and 10" W.C. for Propane gas.  
The high gas pressure switch (optional) mounts down-stream of the gas  
valve. If the gas pressure regulator fails, the high gas pressure switch  
automatically shuts down the burner.  
Drw. #8236  
Fig.# J-6  
GAS PRESSURE SWITCH  
48  
WIRE DIAGRAM MODEL 302-402  
Reference Drawing Number M152462-Rev. M  
WIRE DIAGRAM MODEL 302-402  
WIRE DIAGRAM MODEL 502-752  
Reference Drawing Number M152464-Rev R  
SECTION L: GENERAL SAFETY PRECAUTIONS  
To meet commercial water use needs, the temperature Hi-Limt on this hot water boiler is adjustable up to 210°F. However,  
water temperatures over 125°F can cause severe burns instantly or death from scalds. The preferred starting point for setting  
the control for supplying general purpose hot water is 125°F.  
Safety and energy conservation are factors to be considered when setting the water temperature on the thermostat. The  
most energy efficient operation will result when the temperature setting is the lowest that satisfies the needs consistent with  
the application.  
Water temperature over 125°Fcan cause severe burns  
instantly or death from scalds.  
Children, disabled and elderly are at highest risk of  
being scalded.  
See instruction manual before setting temperature at  
waterheater.  
Feel water before bathing or showering.  
Temperature limiting valves are available, see note  
below.  
Maximum water temperatures occur just after the boiler’s burner has shut off. To determine the water temperature being  
delivered, turn on a hot water faucet and place a thermometer in the hot water stream and read the thermometer.  
The following chart details the relationship of water temperature and time with regard to scald injury and may be used as a  
guide in determining the safest water temperature for your applications.  
Temperature  
Time to Produce Serious Burn  
Temperature  
Time to Produce Serious Burn  
120°F. More than 5 minutes  
125°F. 1-1/2 to 2 minutes  
140°F. Less than 5 seconds  
145°F. Less than 3 seconds  
150°F. About 1-1/2 seconds  
155°F. About 1 second  
130°F.  
135°F.  
About 30 seconds  
About 10 seconds  
Table courtesy of The Shriners Burn Institute  
TIME/TEMPERATURE RELATIONSHIPS IN SCALDS  
The temperature of the water in the hot water boiler can be regulated by setting the temperature dial on front of the  
thermostat. To comply with safety regulations the thermostat was set at its lowest setting before the hot water boiler was  
shipped from the factory. The illustration below shows the thermostat and how to adjust the water temperature.  
To adjust the water temperature, insert a small straight  
screwdriver into slotted screw in hole in front of thermostat  
and turn wheel to desired setting.  
Adjustment  
Screw  
CAUTION!!  
- Hotter water Increases the risk of SCALDING!  
There is a Hot Water SCALD Potential if the thermostat is set too high.  
NOTE: When this hot water boiler is supplying general purpose hot water requirements for use by individuals, a thermo-  
statically controlled mixing valve for reducing point of use water temperature is recommended to reduce the risk of scald  
injury. Contact a licensed plumber or the local plumbing authority for further information.  
53  
SECTION M: PRE-START-UP  
FILLINGSYSTEM-HEATINGBOILERS  
Fill system with water. Purge all air from the system using purge valve sequence. After system is purged of air, lower system  
pressure. Open valves for normal system operation, fill system through feed pressure. Manually open air vent on the  
compression tank until water appears, then close vent.  
DOMESTIC HOTWATER BOILERS  
Purge all air from system before lighting boiler. This can be normally be accomplished by opening a downstream valve.  
INSPECT VENTING SYSTEM:  
1. Check all vent pipe connections and flue pipe material.  
2. Ensure vent terminations are installed per code and are clear of all debris or blockage.  
FOR YOUR SAFETY READ BEFORE LIGHTING  
WARNING:  
If you do not follow these instructions exactly, a fire or explosion may result causing property damage,  
personal injury or loss of life.  
1. This appliance does have an intermittant pilot. It is equipped with an ignition device which automatically lights the  
pilot. Do Not try to light the pilot or burner by hand.  
2. BEFORE OPERATING, smell all around the appliance area for gas. Be sure to smell next to the floor because some  
gas is heavier than air and will settle on the floor.  
3. WHATTO DO IFYOU SMELLGAS  
Do not try to light any appliance.  
Do not touch any electrical switch; do not use any telephone in your building.  
Immediately call your gas supplier from a neighbor's telephone. Follow the gas supplier's instructions.  
If you cannot reach your gas supplier, call the fire department.  
4. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not turn by hand, do  
not try to repair it, call a qualified service technician. Forced or attempted repair may result in a fire or explosion.  
5. Do not use this appliance if any part has been under water, immediately call a qualified service technician to inspect  
the appliance and to replace any part of the control system and any gas control which has been under water.  
6. Check around unit for debris and remove combustible products, i.e. gasoline, etc.  
PRE-START-UPCHECK  
1. Verify boiler is filled with water.  
2. Check system piping for leaks. If found, repair immediately.  
3. Vent air from system. Air in system can interfere with water circulation.  
4. Purge air from gas line up to boiler.  
54  
SECTION N: HI-DELTA INITIAL START-UP  
1.0  
TOOLS NEEDED  
One 12-0-12, 24” scale manometer  
6-0-6, 12” scale manometers  
7/16” open end wrench  
1/2” open end wrench  
Screwdriver  
Volt meter  
3/16Allen wrench  
Jumper cable  
2.0  
PREPARATION FOR START-UP  
WARNING:  
2.1 Check Power Supply  
With volt meter at incoming power check voltage between:  
DO NOT TURN ON GAS AT THIS TIME  
Hot - Common  
(~120VAC)  
Hot - Ground  
Common - Ground  
(~120VAC)  
(<1VAC)  
If Common - Ground is > 1 VAC - STOP: Contact electrician to correct ground failure. Warning: Failure to do this may  
burn out 120V-24V transformer, or may cause other safety control damage or failure.  
2.2 Attach Manometers to Measure Pressures  
Attach 24" scale manometer to the first main gas shut-off valve pressure tapping.  
Attach one 12" scale manometer to the outlet side of the second main gas shut-off valve pressure tapping.  
Attach one 12" scale manometer to — Pull rubber tube from air pressure switch off the aluminum tubing and  
connect the manometer using a tee.  
Turn Off Main Gas Valve;  
2.3 Check the Gas Supply Pressure  
1. Slowly turn on main gas shut-off valve;  
2. Read the gas supply pressure from the manometer; minimum supply pressure for natural gas is 5” W.C.,  
recommended supply is 7” W.C., minimum supply pressure for propane is 11” W.C.  
3. If pressure is > 14" W.C.; Turn off the valve;  
4. Check if the service regulator is installed and/or adjust the service regulator;  
55  
3.0 START-UP  
3.1 BlowerAdjustment  
1. Disconnect all fan pressure switch tubings at plenum and connect manometer using a tee.  
2. Close all manual firing valves.  
3. Turn power on;  
4. Check manometers attached to fan pressure switches. The readings should be 1.4 + .2"W.C. for propane and  
natural gas. If not, adjust the air shutter on the blowers to attain the correct value.  
5. Turn power off.  
6. Reconnect all fan pressure switch tubing to original positions.  
3.2 Main BurnerAdjustment  
1. Turn off unit.  
2. Open manual firing valves.  
3. Turn on the unit, wait 15 seconds, and the igniter should glow. Sight glass to check ignitor at both ends of the boiler.  
Gas valves should be open after 45 seconds.  
4. If burner does not light on first trial. It will retry, up to 3 times  
5. Main burner ignition – check manifold gas pressure at gas valve outlet pressure tap. This should read 3.4 + .1"W.C. for  
natural gas and 10.5 + .1” W.C. for propane.  
6. If the pressure reading differs by more than + .1"W.C. Remove screw cover off the gas pressure regulator, adjust  
main burner manifold pressure. Replace the screw cover of the gas regulator. Repeat step 2 – 5 on other valves as  
necessary.  
Your Hi-Delta is tuned in!  
3.4 Safety Inspection  
Replace main gas manifold adjustment cap.  
Check all thermostats and high limit settings.  
During the following safety checks leave manometers hooked up, check and record.  
If other gas fired equipment are in the room and on same gas main check all pressures on the Hi-Delta with all other  
equipment running.  
Remember, incoming gas pressure could be lower than 7.0" W.C. for nat. gas and 11.0” W.C. for pro., provided 3.2.4 is met.  
Check thermostats for ON/OFF operation.  
Check Hi Limits for ON/OFF operation.  
While in operation, check flow switch operation  
Check the low gas pressure switches (For proper adjustment, if available, use the attached manometers to set pressure.  
The scales on the switch are approximately only ); Low gas pressure switch must be set at 5" W.C. for natural gas and  
10.5” W.C. for propane.  
High gas pressure switch (optional) at 1" W.C. above manifold pressure.  
Insert ignition control lockout tests as safety check.  
3.5 Follow-Up  
Safety checks must be recorded as performed.  
Turn unit on.  
After main burner ignition.  
Check Manometer for proper reading.  
Cycle unit several times and recheck readings  
Reanalyze with unit running record or print results.  
Remove all Manometers and replace hose, remove jumper, replace all gas pressure caps.  
Check for gas leaks one more time.  
56  
PILOT TURN DOWN TEST FOR RAYPAK HI DELTA BOILERS  
The Hi Delta boilers, depending on their size, have from two to five burner sections. Each burner section is supplied gas  
by dual gas valves incorporated in single valve body. A maximum of three burner sections may be controlled by a single  
hot surface ignition system. The middle of the three burner sections is lighted directly with a hot surface ignition system.  
The burner section that is ignited directly by the hot surface ignition system serves as a supervised pilot to light the  
burner sections on either side of it. The burner sections on either side of the supervised section (pilot) are electrically  
interlocked with the supervised ignition system so as to not be energized unless flame is proven on the center section  
which is acting as a pilot to light the right and left hand sections.  
The pilot turn down test is conducted as follows:  
1) Turn off manual valves on non-supervised burner sections.  
2)  
Turn on electrical power and adjust thermostat to call for heat.  
3) Wait for completion of ignition sequence to light burner section being utilized as a pilot for those turned off in (1)  
above.  
4) Gradually reduce manifold pressure (flame) on supervised burner section by closing manual gas valve. Watch  
for shut down due to loss of supervised flame signal as pressure is being reduced. Flame signal should be lost  
before manifold pressure goes below 2 inches water column.  
LEAK TEST PROCEDURE: DUAL-SEAT GAS VALVES  
Proper leak testing requires three pressure test points in the gas train.  
Test point A is upstream of the automatic gas valve. On the first automatic valve, this is a bleedle valve. On the  
other valves, this is a plugged port. The bleedle valve on the first valve may be used for all the other valves as  
well.  
Test point B is a bleedle valve located between the two automatic gas valve seats.  
Test point C is located downstream of both automatic gas valve seats and upstream of the manual valve. On the  
manual valve, this is a bleedle valve. Identical readings will be found at the plugged port labeled as Alternate C”.  
Refer to attached diagrams. Numbers on the diagram refer to the steps below:  
These tests are to be conducted with the electrical power to the boiler turned off.  
1) Manually close the downstream leak test valve.  
2) Open test point A and connect a manometer to it. Verify that there is gas pressure and that it is within the proper  
range (note: must not exceed 14 inches water column).  
3) Open test point B and connect a rubber tube to it. Connect the other end of the tube to a manometer and look for a  
build u of pressure. Increasing pressure indicates a leaking gas valve.  
57  
4) Next, close the upstream manual gas valve and remove the manometers from test point A and from test point B.  
Connect a rubber tube from test point A to test point B and open the upstream manual gas valve. Make sure that test  
points A & B have been opened so as to allow gas to flow. This will bring pressure to the second valve seat.  
5) Open test point C and connect a second rubber tube to it. Connect the other end of the tube to a manometer and  
look for a build up of pressure. Increasing pressure indicates a leaking gas valve.  
6) Remove rubber test tube and manometers. Close each test point valve as the tubes are removed.  
7) Connect a manometer to each test point (one at a time) and look for a build up of pressure. If a build up of pressure is  
detected, check each test point valve to see if it is tightly closed. If leak persists, replace test point valve(s).  
8) After no leakage has been verified at all valve seats and test valves, open downstream leak tests valve and restore  
electrical power to boiler.  
This completes leak testing for a single Hi Delta manifold riser. Repeat steps 1-8 for each riser.  
58  
SECTION O: POST START-UP CHECK  
Check off steps as completed:  
1. Boiler and heat distribution units or storage tank filled with water?  
2. Automatic air vent, if used, open two full turns during venting procedure?  
3. Air purged from system?  
4. Air purged from gas piping? Piping checked for leaks?  
5. Followed start-up procedure for proper start-up?  
6. Is burner flame visible?  
7. Test safety controls: If boiler is equipped with a low water cutoff or additional safety controls, test for operation as  
outlined by manufacturer. Burner should be operating and should go off when controls are tested. When safety devices  
are restored, burners should reignite after pre-purge time delay.  
8. Test limit control: While burner is operating, move indicator on high limit control below actual boiler water  
temperature. Burner should go off while blower and circulator continue to operate. Raise setting on limit control above  
boiler water temperature and burner should reignite after pre-purge time delay..  
9. Test ignition system safety device:  
·
·
·
Turn on manual gas valve. Turn power on.  
Set thermostat to call for heat.  
When the unit is in operation. Disconnect combustion air blower pressure switch, burner should go off  
immediately.  
·
·
Wait 5 minutes.  
Reconnect combustion air pressure switch, burner should reignite after pre-purge time delay.  
10. To restart system, follow lighting instructions in Section O.  
11. High limit control set to design temperature requirements of system?  
For multiple zones: flow adjusted as required in each zone?  
12. Boiler cycled with thermostat? Raise to highest setting and verify boiler goes through normal start-up cycle.  
Reduce to lowest setting and verify boiler goes off.  
13. Observed several operating cycles for proper operation?  
14. Set room thermostat or tankstat to desired temperature?  
15. Reviewed all instructions shipped with this boiler with owner or maintenance person, returned to envelope  
and given to owner or placed in pocket inside front panel on boiler?  
59  
SECTION P: OPERATION  
OPERATING INSTRUCTIONS  
Lighting Instructions  
1. STOP! Read the safety information first.  
2. Set the thermostat to the lowest setting.  
3. Turn off all electric power to the appliance.  
4. This appliance is equipped with an ignition device which automatically lights the burner. Do Not try to light the  
burner by hand.  
5. Remove upper front panel.  
6. Turn on main manual gas valve.  
7. Wait five (5) minutes to clear out any gas. Then smell for gas, especially near the floor. If you then smell gas. STOP!  
Follow the steps in the safety information on the front cover.  
If you do not smell gas, go to next step.  
8. Turn on all electric power to the appliance.  
9. Set thermostat to desired setting. The appliance will operate. The igniter will glow after the pre-purge time delay (15  
seconds). After igniter reaches temperature (45 seconds) the main valve will open. System will try for ignition three (3)  
times. If ignition is not sensed, lockout will commence.  
10. If the appliance will not operate, follow the instruction "To Turn Off Gas To Appliance", and call your service  
technician or gas supplier.  
11. Replace access panel.  
TOTURNOFFGASTOAPPLIANCE  
1. Set the thermostat to lowest setting.  
2. Turn off all electric power to the appliance if service is to be performed.  
3. Remove upper front panel.  
4. Turn off main manual gas valve.  
5. Replace access panel.  
If boiler fails to start, check for:  
Loose connections, blown fuse or service switch off?  
High temperature limit switch set below boiler water temperature?  
Thermostat set below room temperature?  
Gas not turned on at meter or boiler/  
Incoming gas pressure less than 6" W.C. for Natural gas, 11" W.C. for Propane.  
60  
SECTION Q: MAINTENANCE  
SUGGESTED MINIMUM MAINTENANCE SCHEDULE:  
Regular service by a qualified service agency and maintenance must be performed to assure maximum boiler operating  
efficiency.  
Maintenance as outlined below may be performed by the owner.  
Yearly (Beginning of each heating season):  
1. Annual service call by qualified service agency.  
2. Visually check top of vent for soot. Call service person to clean. Some sediment at bottom of vent is normal.  
3. Visually inspect venting system for proper function, deterioration or leakage.  
4. Check that boiler area is free from combustible materials, gasoline, and other flammable vapors and liquids.  
5. Check for and remove any obstruction to the flow of combustion or ventilation air to boiler.  
6. Follow pre-start-up check in Section N.  
7. Visually inspect burner flame. Should see light blue flame. Visually inspect hot surface ignitor for damage, cracking  
or debris build-up.  
8. Check operation of safety devices. Refer to manufacturer’s instructions.  
9. Follow oil-lubricating instructions on circulator. Over-oiling will damage circulator. Water-lubricated  
circulators do not need oiling.  
10. To avoid potential of severe burn, DO NOT REST HANDS ON OR GRASP PIPES. Use a light touch - return  
piping will heat up quickly.  
11. Check blower and blower motor. Clean and oil as necessary.  
12. Check for piping leaks around circulators, relief valves and other fittings. Repair, if found. DO NOT use petroleum  
based stop leak.  
Daily:  
1. Check that boiler area is free from combustible materials, gasoline, and other flammable vapors and liquids.  
2. Check for and remove any obstruction to the flow of combustion or ventilation air to boiler.  
Monthly:  
1. Check for piping leaks around circulators, mixing valves, relief valves, and other fittings.  
If found, repair at once. DO NOT use petroleum-based stop leak compounds.  
2. Visually inspect burner flame.  
3. Visually inspect venting system for proper function, deterioration or leakage.  
4. Check air vents for leakage.  
Periodically:  
1. Check relief valve. Refer to manufacturer’s instructions on valve.  
2. Test low water cutoff, if used. Refer to manufacturer’s instructions.  
3. Clean screen and air filter in intake.  
61  
PREVENTIVE MAINTENANCE SCHEDULE  
Required procedure in CSD-1 States and good practice for all Hi-Delta installations.  
Daily  
1.  
2.  
3.  
Check gages, monitors and indicators. (See page 6 of the Operating and Installation Instructions Manual).  
Check instrument and equipment settings. (See page 49-50 of the Operating and Installation Instructions Manual).  
Check burner flame. (Should see light blue flame).  
Weekly  
1.  
For low-pressure boilers, test low-water fuel cutoff device. (With at least one stage of the appliance on, depress the  
low water cut-off test button, appliance should shut-off and ignition fault light should come on. Depress reset  
button to reset).  
2.  
3.  
4.  
5.  
Check igniter. (Resistance reading should be 30- 70 ohms).  
Check flame signal strength. (Flame signal should be greater than 1 microamp).  
Check flame failure detection system. (See attached Turn Down Test Procedure).  
Check firing rate control. (Check manifold pressure, see page 50 of the Operating and Installation Instructions  
Manual).  
6.  
Make aural and visual check of pilot and main fuel valves.  
Monthly  
1.  
2.  
3.  
Check flue, vent, stack, or outlet dampers.  
Test fan air pressure. (See page 50 of the Operating and Installation Instructions Manual).  
Test high and low gas pressure interlocks. (See page 50 of the Operating and Installation Instructions Manual).  
Semi-Annually  
1.  
2.  
3.  
Recalibrate all indicating and recording gages.  
Check flame failure detection system components. (See Turn Down Test Procedure).  
Check firing rate control. (Check manifold pressure, see page 50 of the Operating and Installation Instructions  
Manual).  
4.  
5.  
Check piping and wiring of all interlocks and shutoff valves.  
Inspect burner components.  
Annually  
1.  
2.  
3.  
4.  
5.  
Flame failure detection system, pilot turndown test.  
Test high limit and operating temperature. (See page 48 of the Operating and Installation Instructions Manual).  
Check flame sensors, (Flame signal should be greater than 1 microamp).  
Conduct a combustion test. (Carbon Dioxide 7-9 %; Carbon monoxide < 200 ppm).  
Check all coils and diaphragms; test other operating parts of all safety shutoff and control valves. Coils- check for  
60 cycle hum or buzz; diaphragms- using soapy water solution check for leaks on the vent outlets and all fittings on  
the valves; on other safety devices increase or decrease settings (depending on the type of control) until the safety  
circuit opens. Reset to original setting after each device is tested.  
6.  
7.  
Perform leakage test on pilot and main gas valves. (See Leak Test Procedure).  
Test purge air switch in accordance with manufacturer’s instructions. (Turn panel switch to the on position until  
blower is proven, then turn the switch to off. Blower should stay on for approximately 30 seconds).  
Test burner position interlock in accordance with manufacturer’s instructions. (Remove front panel and visually  
check burner orientation, all three screws holding the burner must be in place and flat portion of the flange must be  
on top in the horizontal position).  
8.  
As Required  
1.  
2.  
3.  
4.  
Recondition or replace low water fuel cutoff device.  
For gas fired burners, check drip leg and gas strainers.  
Flame failure detection system, pilot turndown test.  
Test safety/safety relief valves in accordance with ASME Boiler and Pressure Vessel Code Sections VI and VII.  
62  
APPENDIX A  
INSIDECOMBUSTIONAIRCONTAMINATION:  
All boilers experience some condensation during start-up.  
The condensate from flue gas is slightly acidic. In most cases the pH level is not harmful to vents or drains. When  
combustion air is contaminated by vapors from products in areas listed below, the acidic levels in the condensate increase.  
Higher acidic levels attack many materials, including stainless steel commonly used in high efficiency systems.  
The boiler can use special corrosion-resistant nonmetallic intake vent material. You may, however, choose to use outside  
combustion air for one or more of these reasons:  
installation is in an area containing contaminants listed below which will induce acidic condensation.  
you want to reduce infiltration into your building through openings around windows and doors.  
you are using AL29-4C stainless steel vent pipe, which is more corrosion-resistant than standard metallic vent  
pipe. In extremely contaminated area, this may also experience deterioration.  
Products causing contaminated combustion air:  
spray cans containing chloro/fluorocarbons  
permanent wave solutions  
chlorinated waxes/cleaners  
chlorine-based swimming pool chemicals  
calcium chloride used for thawing  
sodium chloride used for water softening  
refrigerant leaks  
paint or varnish removers  
hydrochloric acid/muriatic acid  
cements and glues  
antistatic fabric softeners used in clothes dryers  
chloride-type bleaches, detergents, and cleaning solvents found in household laundry rooms  
adhesives used to fasten building products  
... and other similar products.  
Areas causing contaminated combustion air:  
dry cleaning/laundry areas and establishments  
metal fabrication plants  
beauty shops  
refrigeration repair shops  
photo processing plants  
auto body shops  
plastic manufacturing plants  
furniture refinishing areas and establishments  
new building construction  
remodeling areas.  
Check for areas and products as listed above before installing boiler. If found:  
remove products permanently, OR  
provide outdoor combustion air.  
63  
LIMITED PARTS WARRANTY COMMERCIAL BOILERS  
TYPE HI-DELTA SIZES 302 TO 902  
MODELS H AND W  
SCOPE:  
Raypak, Inc. ("Raypak") warrants to the original owner that all parts of this boiler which are actually manufactured by Raypak will  
be free from failure under normal use and service for the specified warranty periods and subject to the conditions set forth in this  
Warranty. Labor charges and other costs for parts removal or reinstallation, shipping and transportation are not covered by this  
Warranty but are the owner's responsibility.  
HEATEXCHANGERWARRANTY:  
Domestic Hot Water  
Five (5) years from date of boiler installation. Includes copper heat exchanger with bronze and cast iron waterways.  
Ten (10) years from date of boiler installation. Includes only cupro nickel heat exchanger with bronze or cast iron waterways.  
Space Heating (Closed Loop System)  
Ten (10) years from date of boiler installation. Includes both cupro nickel and copper heat exchanger with bronze or cast iron  
waterways.  
Thermal Shock Warranty  
Twenty (20) years from date of boiler installation against "Thermal Shock" (excluded, however, if caused by boiler operation at large  
changes exceeding 150°F between the water temperature at intake and boiler temperature, or operating at boiler temperatures exceeding  
230°F).  
ANYOTHERPARTMANUFACTUREDBYRAYPAK:  
One (1) Year warranty from date of boiler installation, or eighteen (18) months from date of factory shipment based on Raypak's  
records, whichever comes first.  
SATISFACTORYPROOFOFINSTALLATIONDATE,SUCHASINSTALLERINVOICE,ISREQUIRED. THISWARRANTYWILL  
BEVOIDIFTHEBOILER RATINGPLATEISALTEREDORREMOVED.  
ADDITIONALWARRANTYEXCLUSIONS:  
This warranty does not cover failures or malfunctions resulting from:  
1. Failure to properly install, operate or maintain the boiler in accordance with our printed instructions provided;  
2. Abuse, alteration, accident, fire, flood and the like;  
3. Sediment or lime buildup, freezing, or other conditions causing inadequate water circulation;  
4. High velocity flow exceeding boiler design rates;  
5. Failure of connected systems devices, such as pump or controller;  
6. Use of non-factory authorized accessories or other components in conjunction with the boiler system;  
7. Failing to eliminate air from, or replenish water in, the connected water system;  
8. Chemical contamination of combustion air or use of chemical additives to water.  
PARTSREPLACEMENT:  
Under this Warranty, Raypak will furnish a replacement for any failed part. The failed part must first be returned to Raypak if  
requested, with transportation charges prepaid, and all applicable warranty conditions found satisfied. The replacement part will  
be warranted for only the unexpired portion of the original warranty. Raypak makes no warranty whatsoever on parts not manufactured by  
it, but Raypak will apply any such warranty as may be provided to it by the parts manufacturer.  
TO MAKE WARRANTY CLAIM:  
Promptly notify the original installer, supplying the model and serial numbers of the unit, date of installation and description of the  
problem. The installer must then notify his Raypak distributor for instructions regarding the claim. If either is not available, contact  
Service Manager, Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 or call (805) 278-5300. In all cases proper authorization must first  
be received from Raypak before replacement of any part.  
EXCLUSIVE WARRANTY - LIMITATION OF LIABILITY:  
This is the only warranty given by Raypak. No one is authorized to make any other warranties on Raypak's behalf. THIS  
WARRANTYINLIEUOFALLOTHERWARRANTIES,EXPRESSORIMPLIED,INCLUDINGBUTNOTLIMITEDTOIMPLIEDWARRANTIES OF  
MERCHANTABILITYANDFITNESSFORAPARTICULARPURPOSE. RAYPAK'SSOLELIABILITYANDTHESOLE REMEDYAGAINST  
RAYPAKWITHRESPECtTTODEFECTIVEPARTSSHALLBEASPROVIDEDINTHIS WARRANTY. ITISAGREEDTHATRAYPAKSHALL  
HAVENOLIABILITY,WHETHERUNDERTHISWARRANTY,ORINCONTRACT,TORT,NEGLIGENCEOROTHERWISE,FORANYSPECIAL,  
CONSEQUENTIAL, ORINCIDENTALDAMAGE, INCLUDINGDAMAGEFROMWATERLEAKAGE. Somestatesdonotallowlimitationsonhow  
long an implied warranty lasts, or for the exclusion of incidental or consequential damages. So the above limitation or exclusion may not  
apply to you.  
This Limited Warranty gives you specific legal rights. You may also have other rights which may vary from state to state. We  
suggest that you complete the information below and retain this certificate in the event warranty service is needed. Reasonable proof of  
the effective date of the warranty (date of installation) must be presented, otherwise, the effective date will be based on the rate of  
manufacture plus thirty (30) days.  
_____________________________________________________  
Name of Owner  
______________________________________________  
Name of Dealer  
_____________________________________________________  
Address  
______________________________________________  
Address  
_____________________________________________________  
______________________________________________  
_____________________________________________________  
ModelNo.  
______________________________________________  
Serial No.  
Date of Installation:_____________________________________  
Date of Initial Operation: ___________________________  
CORPORATE HEADQUARTERS:  
64  
Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 FAX: (800) 872-9725  
Raypak Canada LTD, 2805 Slough Street, Mississauga, Ontario, Canada L4T 1G2 (905) 677-7999 FAX: (905) 677-8036  
6-99 Litho in U. S. A.  

Q See Digital Peripheral Solutions Car Video System QR40198 403 User Manual
PYLE Audio View Series PLD179U User Manual
Profile MP6600 User Manual
Pioneer Premier DEH P740MP User Manual
Pentax Camcorder 735 Date User Manual
Panasonic AG HVX200AP User Manual
Nokia HF 200 User Manual
Nikon SB 30 User Manual
Magnadyne M3200CD User Manual
JVC KD G351 User Manual