Model No. CZ-RWSU2U
INSTALLATION INSTRUCTIONS
If a group of units are to be controlled by 2 remote controllers;
Warnings about Installation of Receivers
※ Main/sub remote controllers will work regardless of which indoor unit they are installed to.
ꢀThe wireless remote uses a very weak infrared light for its signal, which can result in the signal not
being received because of the following influences, so take care in where the unit is installed.
• Inverter or rapid-start type fluorescent lights. (Models without glow lamps)
• Plasma display or LCD televisions.
Cross-wiring Remotes for Group
Control (Field Supply)
CZ-RWSU2U
Wireless Remote
Controller
ꢀUse wiring of AWG#20 –
AWG#14 for field supply.
ꢀMake the total wire length
when cross-wiring a group
no more than 650 ft.
Wired Remote
Controller
DIP Switch 3
• Direct sunlight or other sources of bright light.
(Main)
㧯㧺㧝
※
※ (Sub)
㧝
㧞
㧝
㧞
Warnings about Installing Remote Controllers
ꢀIf a remote controller is to be operated from a remote control holder that is hung on a wall, turn
on the lights in the room as well as any electrical appliances and then check to make sure the air
conditioner works with the remote controller in the location where it will be installed. If it works,
continue with installation.
ꢀIf the air conditioner is to be switched from the main sensor to a remote control sensor, pay attention
to the following when installing.
1st Indoor
Unit
2nd Indoor
Unit
3rd Indoor
Unit
4th Indoor
Unit
• Locate where no warm or cold drafts will affect it.
• Locate in a place free from direct sunlight.
• Locate where it will not be affected by any other heat/cold source.
Accessories
No.
1
Accessories
Quantity
No.
Accessories
Quantity
Operation Panel
1
7
Dry-cell Batteries
2
Customer Explanation
8
Operating Instructions
Truss Self-Tapping Screws
Pan Head Self-Tapping Screws
Plastic Clamp
1
2
4
3
2
ꢀGive the Operating Instructions and this manual to the customer after finishing the installation.
Display
2
1
ꢀUse the Operating Instructions to explain to the customer how to use and care for the unit.
9
3
4
Remote Controller
1
1
Things to remember when wired and wireless remotes are
installed at the same time
10
11
12
Remote Control Holder
5
6
Badge
Label
1
1
Two remote controllers can be used to control the unit if the wireless remote controller is installed at the
same time as the wired remote controller.
Spacer
(Up to 2 remotes [a wireless remote controller and the wired remote controller] can be installed.)
When using 2 remotes, one or more units can be operated by the remotes.
<Note> When wiring remote controllers, be sure to double-check the terminal numbers of the indoor unit before
connecting them so there are no mistakes in the wiring. (Damage will occur if high voltage [e.g. supply
voltage] is applied.)
<Note> It is not possible to use more than one wireless remote controller with one indoor unit. (A receiver located
separately can be used at the same time.)
<Note> If both a wireless and a wired remote controller are to be installed and used at the same time, one of
them must be set up as the sub remote controller.
ꢀIf the wired remote controller is to be the sub remote, change the wired remote controller to the sub remote.
ꢀIf the wireless remote controller is to be the secondary, turn the #3 switch on the wireless receiver (operation
panel) from OFF to ON.
Wiring
Wiring Diagram
Indoor Unit
Display
Operation Panel
㹕㸰
㹕㸱
Connections
Blue
Blue
㹕㸯
Yellow
Pink
Yellow
Pink
RC
When 1 indoor unit is operated by 2 remote controllers:
※ Either of the remotes can be set to main/sub.
White
Black
Red
Red
Gray
Black
Gray
Black
Wired Remote Controller
(Sold Separately)
Wireless Remote Controller
※ (Main)
Relay connector
※ (Sub)
㧯㧺㧝
㧝
Receiver
Connections
㧞
㧝
㧞
1 Connect W3 from the display with W2 from the operation panel using the relay connector.
ꢀUse wiring of AWG#20 – AWG#14 for
field supply.
ꢀUse a total wire length of no more than
1300 ft.
Enclosed wire joints
1. Strip the wire to be connected of its sheathing for 35/64 in.
2. Twist the two wires together and crimp the enclosed wire joint.
3. If a special crimping tool is not used, or if the connection is made using solder,
wrap the joint with insulating tape.
W1
Remote Control Wiring
(Field Supply)
Indoor Unit
1
2
ꢁ
Ceiling Type
Installing the Display/Operation Panel
Installing the Display
1 Remove the side panel.
ꢁ
4-Way Casette Type
Open the air intake grille, remove the screw at one place and then remove the side panel by sliding it toward the
front (arrow direction).
Installing the Display
1 Remove the ceiling panel.
2 Remove cover A and cover B.
Insert a standard screwdriver into the recess of cover A to remove cover A and cover B. (When removing the cover,
take care not to scratch the panel.)
3 Remove cover B from cover A.
4 Install the display at cover A.
5 After passing through the lead wires, install cover A and the display at the panel hole. (The protrusion part of cover
A is fixed with the panel hole.)
6 Bundle the lead wires along with the wiring of the louver motor.
7 Install the side panel.
Remove the air-intake grille and air filter, disconnect the wiring connector
inside the electrical component box, and then remove the 4 mounting screws.
2 Remove the corner cover behind the mark section. (3 screws)
3 Remove the mark section inside the ceiling panel. (2 screws)
4 Install the display in the location where the mark section was attached. (2 screws)
5 Form the wire to match the panel ribs as shown in FIg. 1.
6 Install the corner cover. (Restrain the wire with the corner cover.)
Panel catch
Clamp
Wiring connector
Panel
Electrical
component box
Display
Ceiling panel
Ceiling panel
Corner cover
2 screws
Display
Cover B
Screws with washer
Side Panel
Air filter
Wiring
3 screws
Pass the wiring through
under the shaft.
Air-intake grille
Cover A
Air intake grille
Fig. 1
Installing the Operation Panel
Fig.3
1 Fasten the operation panel to the indoor unit intake port section (electrical component box opposite side) with
the 2 accessory screws.
Installing the Operation Panel
1 Fasten the operating controller to the ceiling panel of the air intake section with the 2 supplied screws.
2 Connect the operation panel 2 wires (WHT, BLK) to the remote control wire (WHT) in the electrical component
box. (For details on wiring, see “Wiring”)
3 Install the ceiling panel.
2 Draw the lead wires into the electrical component box and connect the operating controller 2 wires (WHT, BLK) to
the remote control wires in the electrical component box.
4 Connect the display and the operation panel with 6P connector (white).
5 Form the wires with vinyl clamps and fasten.
6 Install the wiring connector from the ceiling panel to the connector in the electrical component box of the indoor
unit. After installing the connector, use the clamp on the body of the indoor unit to secure the wiring.
7 Install the air filter and air-intake grille.
3 Connect the indicator section and the operating controller using the 6P connector in the electrical component box.
Operation Panel
Electrical
component box
Electrical
component box
Electrical component box
Fig.4
Operation Panel
Fig. 2
Operation Panel
<Note 1> If the wiring to the operation panel is bundled together with other wiring, such as the incoming line from
the power source, it can cause a malfunction, so avoid doing so.
<Note 2> If something causes the unit’s power source to make noise, it will be necessary to resolve the problem,
such as by installing a noise filter.
<Note 1> If the wiring to the operation panel is bundled together with other wiring, such as the incoming line from
the power source, it can cause a malfunction, so avoid doing so.
<Note 2> If something causes the unit’s power source to make noise, it will be necessary to resolve the problem,
such as by installing a noise filter.
ꢀFor more information about wiring or test runs, refer to Wiring the Receiver and Test Run.
ꢀFor more information about wiring or test runs, refer to Wiring the Receiver and Test Run.
3
4
Panasonic_CZ-RWSU2U.indd
1
2012/01/23 9:43:42
|