Lochinvar 5 User Manual

SYNC-I-O Rev N  
Installation & Operation Manual  
Models: 1.0 - 1.3 - 1.5  
This manual must only be used by  
ƽ WARNING  
a qualified heating installer / service  
technician. Read all instructions,  
including this manual and the SYNC  
Service Manual, before installing.  
Perform steps in the order given.  
Failure to comply could result in  
severe personal injury, death, or  
substantial property damage.  
Save this manual for future reference.  
Installation & Operation Manual  
Please read before proceeding  
Installer – Read all instructions, including  
When servicing boiler –  
ƽ WARNING  
this manual and the SYNC Service  
Manual, before installing. Perform steps  
in the order given.  
• To avoid electric shock, disconnect electrical supply  
before performing maintenance.  
User – This manual is for use only  
• To avoid severe burns, allow boiler to cool before  
performing maintenance.  
by  
a
qualified heating installer/  
service technician. Refer to the User’s  
Information Manual for your reference.  
Boiler operation –  
Have this boiler serviced/inspected by  
a qualified service technician, at least  
annually.  
• Do not block flow of combustion or ventilation air to  
the boiler.  
• Should overheating occur or gas supply fail to shut off,  
do not turn off or disconnect electrical supply to  
circulator. Instead, shut off the gas supply at a location  
external to the appliance.  
Failure to comply with the above could  
result in severe personal injury, death or  
substantial property damage.  
When calling or writing about the boiler  
– Please have the boiler model and serial  
number from the boiler rating plate.  
NOTICE  
• Do not use this boiler if any part has been under water.  
The possible damage to a flooded appliance can be  
extensive and present numerous safety hazards. Any  
appliance that has been under water must be replaced.  
Consider piping and installation when  
determining boiler location.  
Any claims for damage or shortage in  
shipment must be filed immediately  
against the transportation company by  
the consignee.  
Boiler water –  
• Thoroughly flush the system (without boiler connected)  
to remove sediment. The high-efficiency heat  
exchanger can be damaged by build-up or corrosion  
due to sediment.  
Factory warranty (shipped with unit) does  
not apply to units improperly installed or  
improperly operated.  
• Do not use petroleum-based cleaning or sealing  
compounds in the boiler system. Gaskets and seals in  
the system may be damaged. This can result in  
substantial property damage.  
Failure to adhere to the guidelines on this  
page can result in severe personal injury,  
death, or substantial property damage.  
ƽ WARNING  
• Do not use “homemade cures” or “boiler patent  
medicines”. Serious damage to the boiler, personnel,  
and/or property may result.  
If the information in this manual is not  
followed exactly, a fire or explosion may  
result causing property damage, personal  
injury or loss of life.  
ƽ WARNING  
• Continual fresh make-up water will reduce boiler life.  
Mineral buildup in the heat exchanger reduces heat  
transfer, overheats the stainless steel heat exchanger,  
and causes failure. Addition of oxygen carried in by  
makeup water can cause internal corrosion in system  
components. Leaks in boiler or piping must be repaired  
at once to prevent the need for makeup water.  
This appliance MUST NOT be installed in  
any location where gasoline or flammable  
vapors are likely to be present.  
WHAT TO DO IF YOU SMELL GAS  
• Do not try to light any appliance.  
• Do not touch any electric switch; do  
not use any phone in your building.  
• Immediately call your gas supplier  
from a near by phone. Follow the  
gas supplier’s instructions.  
• If you cannot reach your gas supplier,  
call the fire department.  
• Installation and service must be  
performed by a qualified installer,  
service agency, or the gas supplier.  
Freeze protection fluids –  
• NEVER use automotive antifreeze. Use only inhibited  
propylene glycol solutions, which are specifically  
formulated for hydronic systems. Ethylene glycol is  
toxic and can attack gaskets and seals used in hydronic  
systems.  
3
Installation & Operation Manual  
The SYNC - How it works...  
1. Access cover - front  
22. Gas valves  
Provides access to the gas train and the heat exchanger.  
2. Air intake adapter  
The gas valves sense the negative pressure created by the  
blowers, allowing gas to flow only if the gas valves are  
powered and combustion air is flowing.  
Allows for the connection of the PVC air intake pipe to the  
23. Heat exchanger access covers  
boiler.  
Allows access to the combustion side of the heat  
exchanger coils.  
24. High gas pressure switches  
Switches provided to detect excessive gas pressure.  
25. High limits  
3. Air pressure switches  
The air pressure switches detect blocked flue/vent conditions.  
4. Air shrouds (1.0 Model only)  
The air shrouds control air and gas flow into the burners.  
5. Automatic air vents  
Designed to remove trapped air from the heat exchanger  
coils.  
6. Blowers  
The blowers pull in air and gas through the venturis (item  
35). Air and gas mix inside the blowers and are pushed into the  
burners, where they burn inside the combustion chamber.  
7. Boiler drain port  
Location from which the heat exchangers can be drained.  
8. Boiler inlet temperature sensors  
These sensors monitor system return water temperature. If  
selected as the controlling sensor, the control  
module adjusts the boiler firing rate so the inlet temperature  
matches the set point.  
9. Boiler outlet temperature sensors  
These sensors monitor boiler outlet water temperature. If  
selected as the controlling sensor, the control  
module adjusts boiler firing rate so the outlet temperature  
matches the set point.  
Devices used to monitor the outlet water temperature. If the  
temperature exceeds its setting, they will break the control  
circuit, shutting the boiler down.  
26. Ignition electrodes  
Provides direct spark for igniting the burners.  
27. Line voltage junction box  
The junction box contains the connection points for the line  
voltage power and all pumps.  
28. Line voltage wiring connections (knockouts)  
Conduit connection points for the high voltage junction box.  
29. Low gas pressure switch  
Switch provided to detect low gas pressure.  
30. Low voltage connection board  
The connection board is used to connect external low voltage  
devices.  
31. Low voltage wiring connections (knockouts)  
Conduit connection points for the low voltage connection board.  
32. Low water cutoff device (LWCO)  
10. Burners (not shown)  
Device used to ensure adequate water is supplied to the boiler  
Made with metal fiber and stainless steel construction,  
the burners use pre-mixed air and gas and provide a  
wide range of firing rates.  
and in the event of inadequate water levels, will ensure the boiler  
will shut down.  
33. Power switch  
Turns 120 VAC ON/OFF to the boiler.  
34. Pump relay boards  
The pump relay boards are used to connect the boiler, system  
and Hot Water Generator (HW) pumps.  
35. Relief valve  
11. Condensate drain connection  
Connects the condensate drain line to a 1/2" PVC union.  
12. Control modules  
The control modules respond to internal and external signals  
and control the blowers, gas valves, and pumps to meet the  
heating demand.  
Protects the heat exchangers from an over pressure condition.  
The relief valve will be set at 50 PSI.  
36. Reset switch  
13. Electronic display  
Digital controls with touch screen technology and full color  
display.  
Reset switch for the low water cutoff. Hold for 10 seconds to  
14. Flame inspection windows  
reset.  
The quartz glass windows provide a view of the burner  
surfaces and flames.  
37. Stainless steel heat exchangers  
Allows system water to flow through specially designed coils for  
maximum heat transfer, while providing protection against flue  
gas corrosion. The coils are encased in a jacket that contains the  
15. Flame sensors  
Used by the control module to detect the presence of burner  
flame.  
combustion process.  
16. Flap valves  
38. Temperature and pressure gauge  
Prevents recirculation of flue products when only one burner is  
running.  
17. Flue gas sensors  
Monitors the outlet temperature of the boiler as well as the  
system water pressure.  
39. Test switch  
These sensors monitor the flue gas exit temperature. The  
control modules will modulate and shut down the boiler if the  
flue gas temperature gets too hot. This protects the flue pipe  
from overheating.  
Test switch for the low water cutoff. Hold for 10 seconds to  
test.  
40. Top panel  
Removable panel to gain access to the internal components.  
41. Venturis  
The venturis control air and gas flow into the burners.  
42. Water inlets  
Two 2" NPT water connections that return water from the  
system to the heat exchangers.  
43. Water outlets  
18. Flue pipe adapter  
Allows for the connection of the PVC vent pipe system to the  
boiler.  
19. Gas connection pipe  
Threaded 1½" pipe connection. This pipe should be  
connected to the incoming gas supply for the purpose of  
delivering gas to the boiler.  
A 3" NPT water connection that supplies hot water to the  
system.  
20. Gas shutoff valves (inside unit)  
Manual valves used to isolate the gas valves from the burners.  
44. O-temp switch (located underneath access cover)  
An electrical switch designed to shut down boiler operation in  
the event the outer back of the heat exchanger, directly above the  
flue connection does not exceed 604°F (318°C). This is a one time  
switch and could warrant a heat exchanger replacement. Check  
the integrity of the rear refractory at the back of the upper coil if  
the switch opens.  
21. Gas shutoff valve (outside unit)  
Manual valve used to isolate the gas valve from the gas supply.  
4
Installation & Operation Manual  
The SYNC - How it works...  
(continued)  
Models 1.0 - 1.3 - 1.5  
12  
34  
3
40  
42  
17  
2
30  
31  
13  
27  
28  
18  
19  
16  
21  
44  
1
38  
35  
11  
Front View  
Rear View  
4
1.0 Model Only  
2
22  
37  
23  
32  
8
9
39  
36  
43  
24  
5
22  
29  
26  
14  
7
41  
33  
25  
15  
6
24  
Left Side (inside unit)  
Right Side (inside unit)  
20  
5
Installation & Operation Manual  
Ratings  
SYNC  
AHRI Rating  
Other Specifications  
Net  
Input  
Vent  
Size  
Appliance  
Water  
Content  
Gallons  
Model Number  
Gross  
Output  
MBH  
Air  
Size  
Outlet  
Inlet  
Gas  
AHRI  
Ratings  
Water,  
MBH  
(Note 2)  
MBH  
Water Water Connections  
Note: Change “N” to  
“L” for L.P. gas models.  
(Note 3)  
(Note 4)  
(Note 1)  
Min  
100  
Max  
8.4  
3"  
3"  
3"  
(2) - 2"  
(2) - 2"  
(2) - 2"  
1½"  
1½"  
1½"  
6"  
6"  
6"  
6"  
6"  
6"  
SBN1000  
SBN1300  
SBN1500  
1000  
941  
1237  
1444  
818  
1076  
1256  
10.0  
11.4  
130  
150  
1300  
1500  
Maximum allowed working pressure is located on the rating plate.  
NOTICE  
Notes:  
1. The ratings are based on standard test procedures  
prescribed by the United States Department of Energy.  
2. Net AHRI ratings are based on net installed radiation of  
sufficient quantity for the requirements of the building  
and nothing need be added for normal piping and pickup.  
Ratings are based on a piping and pickup allowance of  
1.15.  
UNIT EQUIPPED FOR  
HIGH ALTITUDE  
3. SYNC boilers require special gas venting. Use only  
the vent materials and methods specified in the SYNC  
Installation and Operation Manual.  
3,000 FT. TO 12,000 FT.  
4. Standard SYNC boilers are equipped to operate from sea  
level to 4,500 feet only with no adjustments. The boiler  
will de-rate by 4% for each 1,000 feet above sea level up  
to 4,500 feet.  
5. High altitude SYNC boilers are equipped to operate  
from 3,000 to 12,000 feet only with no field adjustments.  
The boiler will de-rate by 2% for each 1,000 feet above  
3,000 feet. High altitude models are manufactured with  
a different control module for altitude operation, but  
the operation given in this manual remains the same as  
the standard boilers. A high altitude label (as shown in  
FIG. A) is also affixed to the unit.  
Figure A High Altitude Label Location  
6. Ratings have been confirmed by the Hydronics Section  
of AHRI.  
6
Installation & Operation Manual  
1 Determine boiler location  
This appliance is certified as an indoor  
appliance. Do not install the appliance  
outdoors or locate where the appliance will  
be exposed to freezing temperatures or to  
temperatures that exceed 100°F.  
Installation must comply with:  
ƽ WARNING  
Local, state, provincial, and national codes, laws,  
regulations, and ordinances.  
National Fuel Gas Code, ANSI Z223.1 – latest edition.  
Standard for Controls and Safety Devices for Automatically  
Fired Boilers, ANSI/ASME CSD-1, when required.  
National Electrical Code.  
For Canada only: B149.1 Installation Code, CSA C22.1  
Canadian Electrical Code Part 1 and any local codes.  
Do not install the appliance where the  
relative humidity may exceed 93%. Do not  
install the appliance where condensation  
may form on the inside or outside of the  
appliance, or where condensation may fall  
onto the appliance.  
Failure to install the appliance indoors  
could result in severe personal injury,  
death, or substantial property damage.  
The SYNC gas manifold and controls  
NOTICE  
met safe lighting and other performance  
criteria when the boiler underwent tests  
specified in ANSI Z21.13 – latest edition.  
This appliance requires a special venting  
system. Use only the vent materials, primer  
and cement specified in this manual to  
make the vent connections. Failure to  
follow this warning could result in fire,  
personal injury, or death.  
ƽ WARNING  
Before locating the boiler, check:  
1. Check for nearby connection to:  
• System water piping  
• Venting connections  
• Gas supply piping  
Closet and alcove installations  
• Electrical power  
A closet is any room the boiler is installed in which is less than  
778 cubic feet for SB1000 models, 847 cubic feet for SB1300  
models, and 914 cubic feet for SB1500 models.  
2. Locate the appliance so that if water connections should  
leak, water damage will not occur. When such locations  
cannot be avoided, it is recommended that a suitable  
drain pan, adequately drained, be installed under the  
appliance. The pan must not restrict combustion air  
flow. Under no circumstances is the manufacturer to be  
held responsible for water damage in connection with  
this appliance, or any of its components.  
An alcove is any room which meets the criteria for a closet  
with the exception that it does not have a door.  
Example: Room dimensions = 9 feet long, 9 feet wide, and  
9 foot ceiling = 9 x 9 x 9 = 729 cubic feet. This would be  
considered a closet for a SYNC Boiler.  
For closet and alcove installations as  
ƽ WARNING  
3. Check area around the boiler. Remove any combustible  
materials, gasoline and other flammable liquids.  
shown in FIG.’s 1-1 and 1-2, CPVC or  
stainless steel vent material must be used  
inside the structure. The ventilating air  
openings shown in FIG.’s 1-1 and 1-2 are  
required for this arrangement. Failure to  
follow this warning could result in fire,  
personal injury, or death.  
Failure to keep boiler area clear and free  
of combustible materials, gasoline, and  
other flammable liquids and vapors can  
result in severe personal injury, death, or  
substantial property damage.  
ƽ WARNING  
Provide clearances:  
4. The SYNC must be installed so that gas control system  
components are protected from dripping or spraying  
water or rain during operation or service.  
Clearances from combustible materials  
1. Hot water pipes – at least 1/4" (6 mm) from combustible  
materials.  
2. Vent pipe – at least 1" (25 mm) from combustible  
materials.  
5. If a new boiler will replace an existing boiler, check for  
and correct system problems, such as:  
• System leaks causing oxygen corrosion or heat exchanger  
cracks from hard water deposits.  
• Incorrectly-sized expansion tank.  
3. See FIG.’s 1-1 and 1-2 on page 8 for other clearance  
minimums.  
• Lack of freeze protection in boiler water causing system  
and boiler to freeze and leak.  
Clearances for service access  
1. See FIG.’s 1-1 and 1-2 on page 8 for recommended  
service clearances. If you do not provide the minimum  
clearances shown, it may not be possible to service the  
boiler without removing it from the space.  
7
Installation & Operation Manual  
1 Determine boiler location  
Figure 1-1 Closet Installation - Minimum Required Clearances  
1/4” (6 MM) MINIMUM CLEARANCE  
AROUND HOT WATER PIPES  
1” (25 MM) MINIMUM CLEARANCE  
AROUND VENT PIPES  
For closet installations, CPVC,  
ƽ WARNING  
polypropylene or stainless steel  
vent material MUST BE used in  
a closet structure due to elevated  
temperatures. Failure to follow  
this warning could result in fire,  
personal injury, or death.  
4" (330 MM)  
TOP  
VENTILATING*  
AIR OPENING  
CLOSED DOOR  
0"  
LEFT  
VENTILATING*  
AIR OPENING  
6" (152 MM)  
24" (610 MM)  
REAR  
0"  
RIGHT  
RECOMMENDED SERVICE  
CLEARANCES:  
6" (152 MM)  
FRONT  
Front  
Top  
-
-
30" (762 mm)  
24" (610 mm)  
*AREA OF EACH OPENING:  
1 SQ. INCH PER 1000 BTU PER HOUR INPUT  
WITH A MINIMUM OF 100 SQ. INCHES  
Left Side - 24" (610 mm)  
Rear - 24" (610 mm)  
Figure 1-2 Alcove Installation - Minimum Required Clearances  
1/4” (6 MM) MINIMUM CLEARANCE  
AROUND HOT WATER PIPES  
1” (25 MM) MINIMUM CLEARANCE  
AROUND VENT PIPES  
For alcove installations, CPVC,  
ƽ WARNING  
polypropylene or stainless steel  
vent material MUST BE used  
in an alcove structure due to  
elevated temperatures. Failure to  
follow this warning could result  
in fire, personal injury, or death.  
13" (330 MM)  
TOP  
OPEN FRONT  
0"  
LEFT  
24" (610 MM)  
REAR  
RECOMMENDED SERVICE  
CLEARANCES:  
0"  
RIGHT  
Front  
Top  
-
-
30" (762 mm)  
24" (610 mm)  
6" (152 40 MM)  
Left Side - 24" (610 mm)  
Rear - 24" (610 mm)  
8
Installation & Operation Manual  
1 Determine boiler location  
Provide air openings to room:  
The SYNC alone in boiler room  
(continued)  
Vent and air piping  
The SYNC requires a special vent system, designed for  
pressurized venting.  
1. No air ventilation openings into the boiler room are  
needed when clearances around the SYNC are at least  
equal to the SERVICE clearances shown in FIG.’s 1-1  
and 1-2. For spaces that do NOT supply this clearance,  
provide two openings as shown in FIG. 1-1. Each  
opening must provide one square inch free area per 1,000  
Btu/hr of boiler input.  
The boiler is to be used for either direct vent installation or  
for installation using indoor combustion air. When room air  
is considered, see Section 4, Vertical Direct Venting. Note  
prevention of combustion air contamination below when  
considering vent/air termination.  
Vent and air must terminate near one another and may be  
vented vertically through the roof or out a side wall, unless  
otherwise specified. You may use any of the vent/air piping  
methods covered in this manual. Do not attempt to install  
2. Combustion air openings are required when using the  
Room Air Option on page 18 of this manual.  
The SYNC in same space with other gas or oil-fired the SYNC using any other means.  
appliances  
Be sure to locate the boiler such that the vent and air piping  
1. Follow the National Fuel Gas Code (U.S.) or CSA B149.1 can be routed through the building and properly terminated.  
(Canada) to size/verify size of the combustion/ventilation The vent/air piping lengths, routing and termination method  
air openings into the space.  
must all comply with the methods and limits given in this  
manual.  
The space must be provided with  
ƽ WARNING  
combustion/ventilation air openings  
correctly sized for all other appliances  
located in the same space as the SYNC.  
Prevent combustion air contamination  
Install air inlet piping for the SYNC as described in this  
manual. Do not terminate vent/air in locations that can allow  
contamination of combustion air. Refer to Table 1A, page  
10 for products and areas which may cause contaminated  
combustion air.  
Do not install the boiler in an attic.  
Failure to comply with the above warnings  
could result in severe personal injury,  
death, or substantial property damage.  
Ensure that the combustion air will not  
ƽ WARNING  
contain any of the contaminants in Table  
2. Size openings only on the basis of the other appliances in  
the space. No additional air opening free area is needed  
for the SYNC because it takes its combustion air from  
outside (direct vent installation).  
1A, page 10. Contaminated combustion  
air will damage the boiler, resulting in  
possible severe personal injury, death  
or substantial property damage. Do not  
pipe combustion air near a swimming  
pool, for example. Also, avoid areas  
subject to exhaust fumes from laundry  
facilities. These areas will always contain  
contaminants.  
Flooring and foundation  
Flooring  
The SYNC is approved for installation on combustible  
flooring, but must never be installed on carpeting.  
Do not install the boiler on carpeting even  
ƽ WARNING  
if foundation is used. Fire can result,  
causing severe personal injury, death, or  
substantial property damage.  
If flooding is possible, elevate the boiler sufficiently to prevent  
water from reaching the boiler.  
9
Installation & Operation Manual  
1 Determine boiler location  
When using an existing vent system to  
install a new boiler:  
Table 1A Corrosive Contaminants and Sources  
Products to avoid:  
Failure to follow all instructions can result  
ƽ WARNING  
in flue gas spillage and carbon monoxide  
Spray cans containing chloro/fluorocarbons  
Permanent wave solutions  
emissions, causing severe personal injury  
or death.  
Chlorinated waxes/cleaners  
Check the following venting components before installing:  
Chlorine-based swimming pool chemicals  
Calcium chloride used for thawing  
Sodium chloride used for water softening  
Refrigerant leaks  
• Material - For materials listed for use with this appliance,  
see Section 2 - General Venting. For polypropylene or  
stainless steel venting, an adapter of the same  
manufacturer must be used at the flue collar connection.  
• Size - To ensure proper pipe size is in place, see Table 2A.  
Check to see that this size is used throughout the vent  
system.  
Paint or varnish removers  
Hydrochloric acid/muriatic acid  
Cements and glues  
• Manufacturer - For a stainless steel or polypropylene  
application, you must use only the listed manufacturers  
and their type product listed in Tables 2D and 2F for CAT  
IV positive pressure venting with flue producing  
condensate.  
Antistatic fabric softeners used in clothes dryers  
Chlorine-type bleaches, detergents, and cleaning solvents  
found in household laundry rooms  
Adhesives used to fasten building products and other similar  
products  
• Supports - Non-combustible supports must be in place  
allowing a minimum 1/4" rise per foot. The supports  
should adequately prevent sagging and vertical slippage,  
by distributing the vent system weight. For additional  
information, consult the vent manufacturer’s  
instructions for installation.  
Areas likely to have contaminants  
Dry cleaning/laundry areas and establishments  
Swimming pools  
• Terminations - Carefully review Sections 2 through 4 to  
ensure requirements for the location of the vent and air  
terminations are met and orientation of these fit the  
appropriate image from the Sidewall or Vertical  
options listed in the General Venting Section. For  
stainless steel vent, only use terminations listed in Table  
2F for the manufacturer of the installed vent.  
Metal fabrication plants  
Beauty shops  
Refrigeration repair shops  
Photo processing plants  
Auto body shops  
• Seal - With prior requirements met, the system should be  
tested to the procedure listed in parts (c) through (f) of  
the Removal of an Existing Boiler Section on page 11.  
Plastic manufacturing plants  
Furniture refinishing areas and establishments  
New building construction  
Remodeling areas  
With polypropylene and stainless steel vent, seal and connect  
all pipe and components as specified by the vent manufacturer  
used; with PVC/CPVC vent, see the Installing Vent or Air  
Piping Section on page 19.  
Garages with workshops  
If any of these conditions are not met,  
the existing system must be updated or  
ƽ WARNING  
replaced for that concern. Failure to  
follow all instructions can result in flue gas  
spillage and carbon monoxide emissions,  
causing severe personal injury or death.  
10  
Installation & Operation Manual  
1 Determine boiler location  
common vent system:  
(continued)  
When removing a boiler from existing Remove boiler from wood pallet  
1. After removing the outer shipping carton from the boiler,  
Do not install the SYNC into a common  
vent with any other appliance. This  
will cause flue gas spillage or appliance  
malfunction, resulting in possible severe  
personal injury, death, or substantial  
property damage.  
remove the parts package (packaged parts inside the jacket  
of the boiler).  
ƽ DANGER  
2. To remove the boiler from the pallet:  
a. Remove the front door of the boiler.  
b. Remove the two lag bolts from the wood pallet  
inside the boiler (FIG. 1-3).  
c. Detach the boiler from the lag bolts in the rear of  
the unit, see FIG. 1-3.  
Failure to follow all instructions can result  
in flue gas spillage and carbon monoxide  
emissions, causing severe personal injury  
or death.  
ƽ WARNING  
Do not drop the boiler or bump the jacket  
NOTICE  
on the floor or pallet. Damage to the boiler  
can result.  
At the time of removal of an existing boiler, the following steps  
shall be followed with each appliance remaining connected  
to the common venting system placed in operation, while  
the other appliances remaining connected to the common  
venting system are not in operation.  
Figure 1-3 Boiler Mounted on Shipping Pallet  
a. Seal any unused openings in the common venting system.  
b. Visually inspect the venting system for proper size and  
horizontal pitch and determine there is no blockage  
or restriction, leakage, corrosion, or other deficiencies,  
which could cause an unsafe condition.  
c. Test vent system – Insofar as is practical, close all building  
doors and windows and all doors between the space  
in which the appliances remaining connected to the  
common venting system are located and other spaces of  
the building. Turn on clothes dryers and any appliance  
not connected to the common venting system. Turn on  
any exhaust fans, such as range hoods and bathroom  
exhausts, so they will operate at maximum speed. Do not  
operate a summer exhaust fan. Close fireplace dampers.  
LAG BOLTS  
(QTY. 3)  
REAR  
FRONT  
LAG BOLTS  
(QTY. 3)  
Maintain minimum specified clearances for adequate operation.  
All installations must allow sufficient space for servicing the  
vent connections, water pipe connections, piping and other  
auxiliary equipment, as well as the appliance. The clearance  
labels on each appliance note the same service and combustible  
clearance requirements as shown in this manual.  
d. Place in operation the appliance being inspected. Follow  
the lighting instructions. Adjust thermostat so appliance  
will operate continuously.  
e. Test for spillage at the draft hood relief opening after 5  
minutes of main burner operation. Use the flame of a  
match or candle, or smoke from a cigarette, cigar, or pipe.  
f. After it has been determined that each appliance  
remaining connected to the common venting system  
properly vents when tested as outlined herein, return  
doors, windows, exhaust fans, fireplace dampers, and any  
other gas-burning appliance to their previous conditions  
of use.  
g. Any improper operation of the common venting system  
should be corrected so the installation conforms with the  
National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or  
CAN/CSA B149.1, Natural Gas and Propane Installation  
Code. When resizing any portion of the common venting  
system, the common venting system should be resized  
to approach the minimum size as determined using the  
appropriate tables in Part 11 of the National Fuel Gas  
Code, ANSI Z223.1/NFPA and/or CAN/CSA B149.1,  
Natural Gas and Propane Installation Code.  
Multiple appliances may be installed in a modular boiler  
installation. Multiple appliances may be installed side by side  
with no clearance between adjacent appliances because this  
appliance is approved for zero clearance from combustible  
surfaces and no service access is required from the sides.  
Consult the Venting section of this manual for specific  
installation instructions for the appropriate type of venting  
system that you will be using.  
11  
Installation & Operation Manual  
1 Determine boiler location  
Combustion  
and  
ventilation  
air  
requirements for appliances drawing air  
from the equipment room  
Provisions for combustion and ventilation air must be in  
accordance with Air for Combustion and Ventilation, of  
the latest edition of the National Fuel Gas Code, ANSI  
Z223.1, in Canada, the latest edition of CGA Standard B149  
Installation Code for Gas Burning Appliances and Equipment,  
or applicable provisions of the local building codes.  
The equipment room MUST be provided with properly sized  
openings to assure adequate combustion air and proper  
ventilation.  
Figure 1-5_Combustion Air Through Ducts  
2. If combustion and ventilation air is taken from the  
outdoors using a duct to deliver the air to the  
equipment room, each of the two openings should be  
sized based on a minimum free area of one square inch  
per 2000 Btu/hr (11 cm2 per kW) of input (see FIG. 1-5).  
IF NECESSARY  
FOR TIGHT  
CONSTRUCTION  
Figure 1-4_Combustion Air Direct from Outside  
1. If air is taken directly from outside the building  
with no duct, provide two permanent openings to  
the equipment room (see FIG. 1-4):  
(a) Combustion air opening, with a minimum free  
area of one square inch per 4000 Btu/hr input  
(5.5 cm2 per kW).  
This opening must be  
Figure 1-6_Combustion Air from Interior Space  
located within 12" (30 cm) of the bottom of the  
enclosure.  
3. If air is taken from another interior space, each of the  
two openings specified above should have a net free  
area of one square inch for each 1000 Btu/hr (22 cm2  
per kW) of input, but not less than 100 square inches  
(645 cm2) (see FIG. 1-6).  
(b) Ventilation air opening, with a minimum free  
area of one square inch per 4000 Btu/hr input  
(5.5 cm2 per kW).  
This opening must be  
located within 12" (30 cm) of the top of the  
enclosure.  
12  
Installation & Operation Manual  
1 Determine boiler location  
(continued)  
Where two openings are provided, one must be within 12"  
(30cm) of the ceiling and one must be within 12" (30cm) of the  
floor of the equipment room. Each opening must have net free  
area as specified in the chart below (Table 1B). Single openings  
shall commence within 12" (30cm) of the ceiling.  
Under no circumstances should the  
ƽ CAUTION  
equipment room ever be under negative  
pressure. Particular care should be taken  
where exhaust fans, attic fans, clothes dryers,  
compressors, air handling units, etc., may  
take away air from the unit.  
The combustion air supply must be completely free of any  
flammable vapors that may ignite or chemical fumes which may  
be corrosive to the appliance. Common corrosive chemical  
fumes which must be avoided are fluorocarbons and other  
halogenated compounds, most commonly present as refrigerants  
or solvents, such as Freon, trichlorethylene, perchlorethylene,  
chlorine, etc. These chemicals, when burned, form acids which  
quickly attack the stainless steel heat exchanger, headers, flue  
collectors, and the vent system.  
Figure 1-7_Combustion Air from Outside - Single  
Opening  
4. If a single combustion air opening is provided to bring  
combustion air in directly from the outdoors, the opening  
must be sized based on a minimum free area of one  
square inch per 3000 Btu/hr (7 cm2 per kW). This  
opening must be located within 12" (30 cm) of the top of  
the enclosure (see FIG. 1-7).  
The result is improper combustion and a non-warrantable,  
premature appliance failure.  
Combustion air requirements are based on the latest edition  
of the National Fuel Gas Code, ANSI Z223.1; in Canada refer  
to the latest edition of CGA Standard CAN B149.1. Check all  
local code requirements for combustion air.  
EXHAUST FANS: Any fan or equipment which exhausts air  
from the equipment room may deplete the combustion air  
supply and/or cause a downdraft in the venting system. Spillage  
of flue products from the venting system into an occupied  
living space can cause a very hazardous condition that must be  
corrected immediately.  
All dimensions based on net free area in square inches. Metal  
louvers or screens reduce the free area of a combustion air  
opening a minimum of approximately 25%. Check with  
louver manufacturers for exact net free area of louvers.  
TABLE - 1B  
MINIMUM RECOMMENDED COMBUSTION  
AIR SUPPLY TO EQUIPMENT ROOM  
FIG. 1-4  
*Outside Air from  
2 Openings Directly from  
Outdoors  
FIG. 1-5  
*Outside Air from  
2 Ducts Delivered from  
Outdoors  
FIG. 1-6  
FIG. 1-7  
**Inside Air from  
2 Ducts Delivered from  
Interior Space  
*Outside Air from  
1 Opening Directly  
from Outdoors, in2  
Model  
Number  
Top  
Bottom  
Top  
Bottom  
Top  
Bottom  
Opening, in2 Opening, in2 Opening, in2 Opening, in2 Opening, in2 Opening, in2  
250  
(1613 cm2) (1613 cm2)  
325 325  
(2097 cm2) (2097 cm2)  
375 375  
(2420 cm2) (2420 cm2)  
250  
500  
500  
1000  
1000  
333  
1.0  
1.3  
1.5  
(3226 cm2)  
650  
(3226 cm2)  
650  
(6452 cm2)  
1300  
(6452 cm2)  
1300  
(2149 cm2)  
433  
(4194 cm2)  
750  
(4839 cm2)  
(4194 cm2)  
750  
(4839 cm2)  
(8388 cm2)  
1500  
(9678 cm2)  
(8388 cm2)  
1500  
(9678 cm2)  
(2794 cm2)  
500  
(3226 cm2)  
*Outside air openings shall directly communicate with the outdoors. When combustion air is drawn from the outside through a  
duct, the net free area of each of the two openings must have twice (2 times) the free area required for Outside Air/2 Openings.  
The above requirements are for the appliance only; additional gas fired appliances in the equipment room will require an increase  
in the net free area to supply adequate combustion air for all appliances.  
**Combined interior space must be 50 cubic feet per 1,000 Btu/hr input. Buildings MUST NOT be of *“Tight Construction”. For  
buildings of *“Tight Construction”, provide air openings into the building from outside.  
*No combustion air openings are needed when the appliance is installed in a space with a volume NO LESS than 50 cubic feet per  
1,000 Btu/hr of all installed gas fired appliances. Buildings MUST NOT be of *“Tight Construction”.  
*”Tight Construction” is defined as a building with less than 0.40 ACH (air changes per hour).  
13  
Installation & Operation Manual  
2 General venting  
Direct venting options - Sidewall Vent  
Figure 2-1 Two Pipe Sidewall Termination -  
See page 22 for more details  
Direct venting options - Vertical Vent  
Figure 2- 2 Two Pipe Vertical Termination -  
Figure 2-3 Vertical Vent, Sidewall Air - See  
See page 26 for more details  
page 18 for more details  
14  
Installation & Operation Manual  
2 General venting  
(continued)  
Install vent and combustion air piping  
The SYNC boiler must be vented and  
supplied with combustion and ventilation  
air as described in this section. Ensure the  
vent and air piping and the combustion  
air supply comply with these instructions  
regarding vent system, air system, and  
combustion air quality. See also Section 1  
of this manual.  
The SYNC boiler vent and air piping can be installed through  
the roof or through a sidewall. Follow the procedures in this  
manual for the method chosen. Refer to the information in  
this manual to determine acceptable vent and air piping length.  
ƽ DANGER  
You may use any of the vent/air piping methods covered in this  
manual. Do not attempt to install the SYNC boiler using any  
other means.  
You must also install air piping from outside to the boiler  
air intake adapter unless following the Optional Room Air  
instructions on page 18 of this manual. The resultant installation  
is direct vent (sealed combustion).  
Inspect finished vent and air piping  
thoroughly to ensure all are airtight and  
comply with the instructions provided and  
with all requirements of applicable codes.  
Failure to provide a properly installed vent  
and air system will cause severe personal  
injury or death.  
Air intake/vent connections  
1. Combustion Air Intake Connector (FIG. 2-4) - Used to  
provide combustion air directly to the unit from outdoors. A  
fitting is provided on the unit for final connection.  
Combustion air piping must be supported per guidelines  
listed in the National Mechanical Code, Section 305, Table  
305.4 or as local codes dictate.  
This appliance requires a special venting  
system. Use only approved stainless steel,  
PVC, CPVC or polypropylene pipe and  
fittings listed in Tables 2C, 2D, and 2F for  
vent pipe, and fittings. Failure to comply  
could result in severe personal injury,  
death, or substantial property damage.  
ƽ WARNING  
2. Vent Connector (FIG.'s 2-5 thru 2-8) - Used to provide a  
passageway for conveying combustion gases to the  
outside. A transition fitting is provided on the unit for  
final connection. Vent piping must be supported per the  
National Building Code, Section 305, Table 305.4 or as  
local codes dictate.  
DO NOT mix components from different  
systems. The vent system could fail,  
causing leakage of flue products into the  
living space. Mixing of venting materials  
will void the warranty and certification of  
the appliance.  
ƽ WARNING  
Figure 2-4 Near Boiler Air Piping  
Installation must comply with local  
requirements and with the National  
Fuel Gas Code, ANSI Z223.1 for U.S.  
installations or CSA B149.1 for Canadian  
installations.  
AIR  
NOTICE  
For closet and alcove installations, CPVC,  
polypropylene or stainless steel material  
MUST BE used in a closet/alcove structure.  
Failure to follow this warning could result  
in fire, personal injury, or death.  
ƽ WARNING  
Improper installation of venting systems  
may result in injury or death.  
ƽ CAUTION  
Follow the instructions in Section 1, page  
11 of this manual when removing a boiler  
from an existing vent system.  
NOTICE  
Do not connect any other appliance to  
the vent pipe or multiple boilers to a  
common vent pipe. Failure to comply  
could result in severe personal injury,  
death, or substantial property damage.  
ƽ WARNING  
15  
Installation & Operation Manual  
2 General venting  
Sizing  
Requirements for installation in  
Canada  
The SYNC boiler uses model specific combustion air  
intake and vent piping sizes as detailed in Table 2A  
below.  
1. Installations must be made with a vent pipe system  
certified to ULC-S636.  
2. The first three (3) feet of plastic vent pipe from the  
applianceflueoutletmustbereadilyaccessibleforvisual  
inspection.  
When determining equivalent combustion air and vent  
length, add 5 feet for each 90° elbow and 3 feet for each  
45° elbow.  
3. Thecomponentsofthecertifiedventsystemmustnotbe  
interchanged with other vent systems or unlisted  
pipe/fittings.  
EXAMPLE: 20 feet of PVC pipe + (4) 90° elbows + (2)  
45° elbows + (1) concentric vent kit (CVK3003) = 49  
equivalent feet of piping.  
Table 2A Air Intake/Vent Piping Sizes  
Input  
De-Rate per  
25 feet of Vent  
Air Intake  
Air Intake  
Air Intake  
Vent  
Vent  
Vent  
Model  
Diameter Min. Length Max. Length Diameter  
Min. Length Max. Length  
SB 1000  
SB 1300  
SB 1300  
SB 1500  
SB 1500  
6"  
6"  
7"  
6"  
7"  
12'  
12'  
12'  
12'  
12'  
100'  
50'  
6"  
6"  
7"  
6"  
7"  
12'  
12'  
12'  
12'  
12'  
100'  
50'  
1.25%  
2.90%  
0.95%  
3.30%  
1.65%  
100'  
50'  
100'  
50'  
100'  
100'  
Note: When using a 7" vent or air pipe, a field supplied increaser is required.  
Increasing or decreasing combustion air or vent piping sizes is not authorized.  
NOTICE  
16  
Installation & Operation Manual  
2 General venting  
(continued)  
Materials  
Air inlet pipe materials:  
The PVC, CPVC, or ABS air inlet pipe should be cleaned and  
sealed with the pipe manufacturer’s recommended solvents  
and standard commercial pipe cement for the material used.  
The PVC, CPVC, ABS, Dryer Vent or Flex Duct air inlet pipe  
should use a silicone sealant to ensure a proper seal at the  
appliance connection and the air inlet cap connection. Dryer  
vent or flex duct should use a screw type clamp to seal the vent  
to the appliance air inlet and the air inlet cap. Proper sealing  
of the air inlet pipe ensures that combustion air will be free of  
contaminants and supplied in proper volume.  
The air inlet pipe(s) must be sealed. Choose acceptable  
combustion air inlet pipe materials from the following list:  
PVC, CPVC, Polypropylene or ABS  
Dryer Vent or Sealed Flexible Duct (not recommended  
for rooftop air inlet)  
Galvanized steel vent pipe with joints and seams sealed as  
specified in this section.  
Type “B” double-wall vent with joints and seams sealed as  
specified in this section.  
AL29-4C, stainless steel material to be sealed to  
specification of its manufacturer.  
When a sidewall or vertical rooftop combustion air supply  
system is disconnected for any reason, the air inlet pipe must  
be resealed to ensure that combustion air will be free of  
contaminants and supplied in proper volume.  
*Plastic pipe may require an adapter (not provided) to  
transition between the air inlet connection on the appliance  
and the plastic air inlet pipe.  
Failure to properly seal all joints and seams  
ƽ DANGER  
as required in the air inlet piping may  
result in flue gas recirculation, spillage  
of flue products and carbon monoxide  
emissions causing severe personal injury  
or death.  
Using air intake materials other than  
those specified can result in personal  
injury, death or property damage.  
ƽ WARNING  
The use of double-wall vent or insulated  
NOTICE  
material for the combustion air inlet pipe is  
recommended in cold climates to prevent  
the condensation of airborne moisture in  
the incoming combustion air.  
Sealing of Type “B” double-wall vent material or galvanized  
vent pipe material used for air inlet piping on a sidewall or  
vertical rooftop Combustion Air Supply System:  
a. Seal all joints and seams of the air inlet pipe using either  
Aluminum Foil Duct Tape meeting UL Standard 723 or  
181A-P or a high quality UL Listed silicone sealant such as  
those manufactured by Dow Corning or General Electric.  
b. Do not install seams of vent pipe on the bottom of  
horizontal runs.  
c. Secure all joints with a minimum of three (3) sheet metal  
screws or pop rivets. Apply Aluminum Foil Duct Tape or  
silicone sealant to all screws or rivets installed in the vent  
pipe.  
d. Ensure that the air inlet pipes are properly supported.  
17  
Installation & Operation Manual  
2 General venting  
Optional room air  
Applications utilizing the SYNC boiler may be installed with  
a single pipe carrying the flue products to the outside while  
using combustion air from the equipment room. In order to  
use the room air venting option the following conditions and  
considerations must be followed.  
Table 2B Room Air Minimum / Maximum Allowable Air /  
Vent Lengths  
Input  
De-Rate per  
25 feet of  
Vent  
Min.  
Length Length  
Vent  
Max.  
Vent  
Diameter  
Model  
The unit MUST be installed with the appropriate  
room air inlet cover (factory installed).  
Vent  
0.63%  
SB 1000  
SB 1300  
SB 1500  
6"  
6"  
6"  
12’  
12’  
12’  
100’  
100’  
100’  
The equipment room MUST be provided with  
properly sized openings to assure adequate  
combustion air. Please refer to instructions provided  
with the room air kit.  
1.45%  
1.65%  
There will be a noticeable increase in the noise level  
during normal operation from the inlet air opening.  
Using the room air configuration makes the unit  
vulnerable to combustion air contamination from  
within the building. Please review Section 1,  
Prevent Combustion Air Contamination, to ensure  
proper installation.  
Vent system and terminations must comply with the  
standard venting instructions set forth in this  
manual.  
Air contamination  
Pool and laundry products and common household and hobby  
products often contain fluorine or chlorine compounds. When  
these chemicals pass through the boiler, they can form strong  
acids. The acid can eat through the boiler wall, causing serious  
damage and presenting a possible threat of flue gas spillage or  
boiler water leakage into the building.  
Please read the information given in Table 1A, page 10,  
listing contaminants and areas likely to contain them. If  
When utilizing the single pipe method, contaminating chemicals will be present near the location of the  
ƽ WARNING  
provisions for combustion and ventilation  
air must be in accordance with Air for  
Combustion and Ventilation, of the latest  
edition of the National Fuel Gas Code,  
ANSI Z223.1, in Canada, the latest edition  
of CGA Standard B149 Installation  
Code for Gas Burning Appliances and  
Equipment, or applicable provisions of  
the local building codes.  
boiler combustion air inlet, have your installer pipe the boiler  
combustion air and vent to another location, per this manual.  
If the boiler combustion air inlet is located in  
ƽ WARNING  
a laundry room or pool facility, for example,  
these areas will always contain hazardous  
contaminants.  
To prevent the potential of severe personal  
ƽ WARNING  
injury or death, check for areas and products  
listed in Table 1A, page 10 before installing  
the boiler or air inlet piping.  
Figure 2-5 Room Air Installation  
FOR DIRECT VENT SYSTEMS  
NOTICE  
REMOVE AIR INLET COVER AND  
INSTALL RUBBER COUPLING FOR  
PVC / CPVC VENT SYSTEMS OR  
STAINLESS STEEL ADAPTER FOR  
STAINLESS STEEL VENT SYSTEMS  
If contaminants are found, you MUST:  
• Remove contaminants permanently.  
—OR—  
• Relocate air inlet and vent terminations  
to other areas.  
18  
Installation & Operation Manual  
2 General venting  
(continued)  
1. Work from the boiler to vent or air termination. Do not  
exceedthelengthsgiveninthismanualfortheairorvent  
piping.  
PVC/CPVC  
This product has been approved for use with the PVC/CPVC  
vent materials listed in Table 2C.  
2. Cut pipe to the required lengths and deburr the inside  
and outside of the pipe ends.  
Installing vent and air piping  
3. Chamfer outside of each pipe end to ensure even  
cement distribution when joining.  
The vent connection to the appliance must  
ƽ WARNING  
be made with the starter CPVC pipe section  
provided with the appliance if PVC/CPVC  
vent is to be used. The field provided  
vent fittings must be cemented to the  
CPVC pipe section using an “All Purpose  
Cement” suitable for PVC and CPVC pipe.  
Use only the vent materials, primer, and  
cement specified in Table 2C to make  
the vent connections. Failure to follow  
this warning could result in fire, personal  
injury, or death.  
4. Clean all pipe ends and fittings using a clean dry rag.  
(Moisture will retard curing and dirt or grease will  
prevent adhesion.)  
5. Dry fit vent or air piping to ensure proper fit up before  
assembling any joint. The pipe should go a third to  
two-thirds into the fitting to ensure proper sealing after  
cement is applied.  
6. Priming and Cementing:  
a. Handle fittings and pipes carefully to prevent  
contamination of surfaces.  
Use only cleaners, primers, and solvents  
NOTICE  
b. Apply a liberal even coat of primer to the fitting  
socket and to the pipe end to approximately 1/2"  
beyond the socket depth.  
that are approved for the materials which  
are joined together.  
All PVC vent pipes must be glued, properly  
NOTICE  
c. Apply a second primer coat to the fitting socket.  
supported, and the exhaust must be  
pitched a minimum of a 1/4 inch per foot  
back to the boiler (to allow drainage of  
condensate).  
d. While primer is still wet, apply an even coat of  
approved cement to the pipe equal to the depth of  
the fitting socket along with an even coat of  
approved cement to the fitting socket.  
Insulation should not be used on PVC  
ƽ WARNING  
or CPVC venting materials. The use of  
e. Apply a second coat of cement to the pipe.  
insulation will cause increased vent wall  
temperatures, which could result in vent  
pipe failure.  
f. While the cement is still wet, insert the pipe into  
the fitting, if possible twist the pipe a 1/4 turn as  
you insert it. NOTE: If voids are present,  
sufficient cement was not applied and joint could  
be defective.  
For all installations, the first ten (10)  
ƽ WARNING  
equivalent feet of vent must be CPVC or  
stainless steel (see FIG. 2-6). Failure to  
follow this warning could result in fire,  
personal inury, or death.  
g. Wipeexcesscementfromthejointremovingringor  
beads as it will needlessly soften the pipe.  
Figure 2-6 Near Boiler PVC/CPVC Venting  
Table 2C PVC/CPVC Vent Pipe, and Fittings  
CPVC ELBOW  
CPVC PIPE  
Approved PVC/CPVC Vent Pipe and Fittings  
Item  
Material  
PVC Schedule 40, 80 ANSI/ASTM D1785  
PVC - DWV ANSI/ASTM D2665  
CPVC Schedule 40, 80 ANSI/ASTM F441  
Standard  
Vent pipe  
5'  
PVC Schedule 40  
ANSI/ASTM D2466  
ANSI/ASTM D2467  
ANSI/ASTM F439  
ANSI/ASTM D2564  
ANSI/ASTM F493  
Vent fittings PVC Schedule 80  
CPVC Schedule 80  
Pipe Cement / PVC  
Primer  
CPVC  
NOTICE: DO NOT USE CELLULAR (FOAM) CORE PIPE  
NOTE: In Canada, CPVC and PVC vent pipe, fittings and cement/  
primer must be ULC-S636 certified.  
19  
Installation & Operation Manual  
2 General venting  
Use only the adapters and vent system listed  
in Tables 2E and 2F. DO NOT mix vent  
systems of different types or manufacturers.  
Failure to comply could result in severe  
personal injury, death, or substantial  
property damage.  
ƽ WARNING  
Polypropylene  
This product has been approved for use with polypropylene  
vent with the manufacturers listed in Table 2D.  
All terminations must comply with listed options in this manual  
and be a single-wall vent offering.  
Installations must comply with applicable  
national, state, and local codes. For  
Canadian installation, polypropylene vent  
must be listed as a ULC-S636 approved  
system.  
For use of flex pipe, it is recommended to have the vent material  
in 32°F or higher ambient space before bending at installation.  
No bends should be made to greater than 45° and ONLY  
installed in vertical or near vertical installations.  
NOTICE  
NOTICE  
For support and special connections required, see the  
manufacturer's instructions. All vent is to conform to standard  
diameter and equivalent length requirements established.  
Installation of a polypropylene vent system  
should adhere to the vent manufacturer’s  
installation instructions supplied with the  
vent system.  
Table 2D Polypropylene Vent Pipe and Fittings  
Approved Polypropylene Vent Manufacturers  
Make  
Model  
Centrotherm Eco Systems  
InnoFlue SW/Flex  
Duravent (M & G Group)  
PolyPro Single-Wall / PolyPro Flex  
The installer must use a specific vent starter  
NOTICE  
adapter at the flue collar connection,  
supplied by the vent manufacturer to  
adapt to its vent system. See Table 2E for  
approved vent adapters. Discard CPVC  
starter piece.  
Figure 2-7 Near Boiler Polypropylene Venting  
Insulation should not be used on  
polypropylene venting materials. The use  
of insulation will cause increased vent wall  
temperatures, which could result in vent  
pipe failure.  
ƽ WARNING  
POLYPROPYLENE  
ADAPTER  
IMG00024  
Table 2E Approved PolypropyleneTerminations  
Duravent Polypro  
Centrotherm InnoFlue SW  
Model  
Polypropylene  
Adapter  
Joint  
Connector  
Sidewall Retaining  
Bracket*  
Sidewall  
Adapter*  
Polypropylene  
Adapter  
Joint  
Connector  
Sidewall  
Kit*  
ISAAL0606 Not Required  
IATP0606  
ISTAGL0606 FSA-6PVCM-6PPS  
N/A  
6PPS-HLK  
1000 -1500  
* These parts are only needed if the sidewall termination assembly is used (see FIG. 3-4B on page 24).  
20  
Installation & Operation Manual  
2 General venting  
(continued)  
Installation of a stainless steel vent system  
should adhere to the stainless steel vent  
manufacturer’s installation instructions  
supplied with the vent system.  
Stainless steel vent  
NOTICE  
This product has been approved for use with stainless steel  
using only FasNSeal vent systems.  
Use only the materials, vent systems, and  
ƽ WARNING  
Figure 2-8 Near Boiler Stainless Steel Venting  
terminations listed in Table 2F. DO NOT  
mix vent systems of different types or  
manufacturers. Failure to comply could  
result in severe personal injury, death, or  
substantial property damage.  
PVC/CPVC or ABS is acceptable air inlet pipe material.  
NOTICE  
REMOVE PVC/CPVC VENT  
CONNECTOR WHEN  
INSTALLING STAINLESS STEEL  
The installer must use a specific vent starter  
NOTICE  
adapter at the flue collar connection,  
supplied by the vent manufacturer to  
adapt to its vent system. See Table 2F for  
approved vent adapters. Discard CPVC  
starter piece.  
Installations must comply with applicable  
NOTICE  
national, state, and local codes. Stainless  
steel vent systems must be listed as a  
UL-1738 approved system for the United  
States and a ULC-S636 approved system  
for Canada.  
The SYNC uses model specific combustion air intake and vent  
piping sizes as detailed in Tables 2A and 2B.  
Increasing or decreasing combustion air  
NOTICE  
or vent piping to sizes not specified in this  
manual is not authorized.  
Table 2F Approved Stainless Steel Terminations and Adapters  
STAINLESS STEEL VENT TERMINATION KITS  
Kit Part Number  
Model  
Component Description  
6" PVC x 6" Stainless Steel Adapter  
KIT30028  
SB 1000 - 1500  
6" Stainless Steel Vent Termination  
6" Stainless Steel Air Inlet  
6" PVC x 6" Stainless Steel Adapter  
6" Stainless Steel x 7" Stainless Steel Adapters (2)  
7" Stainless Steel Vent Termination  
7" Stainless Steel Air Inlet  
KIT30029  
SB 1300 - 1500  
21  
Installation & Operation Manual  
3 Sidewall direct venting  
Figure  
Termination of Air and Vent  
3-1A  
PVC/CPVC/Centrotherm Sidewall  
Vent/air termination – sidewall  
Follow instructions below when  
determining vent location to avoid  
TO BOILER  
INTAKE AIR  
CONNECTION  
ƽ WARNING  
Note: Available in 6"  
diameter only.  
possibility of severe personal injury,  
death, or substantial property damage.  
FROM BOILER  
VENT PIPE  
CONNECTION  
A gas vent extending through an exterior  
ƽ WARNING  
12"  
MIN  
TO  
OVER-  
HANG  
POSSIBLE ORIENTATIONS  
wall shall not terminate adjacent to a wall  
or below building extensions such as eaves,  
parapets, balconies, or decks. Failure to  
comply could result in severe personal  
injury, death, or substantial property  
damage.  
VENT / AIR  
TERMINATION  
12"  
MIN  
Determine location  
GRADE OR  
SNOW LINE  
Locate the vent/air terminations using the following guidelines:  
Table 3A CPVC/PVC Sidewall Vent Kits  
1. The total length of piping for vent or air must not exceed  
the limits given in the General Venting Section on page 16  
of this manual.  
Model Kit Number  
Vent Size  
KIT30047  
6 inch vent  
1.0 - 1.5  
2. You must consider the surroundings when terminating  
the vent and air:  
If using the alternate sidewall termination:  
a. Position the vent termination where vapors will  
not damage nearby shrubs, plants or air  
conditioning equipment or be objectionable.  
b. The flue products will form a noticeable plume as  
they condense in cold air. Avoid areas where the  
plume could obstruct window views.  
c. Prevailing winds could cause freezing of  
condensate and water/ice buildup where flue  
products impinge on building surfaces or plants.  
d. Avoid possibility of accidental contact of flue  
products with people or pets.  
e. Do not locate the terminations where wind eddies  
could affect performance or cause recirculation,  
such as inside building corners, near adjacent  
buildings or surfaces, window wells, stairwells,  
alcoves, courtyards, or other recessed areas.  
3. The air piping must terminate in a down-turned elbow  
as shown in FIG. 3-1B. This arrangement avoids  
recirculation of flue products into the combustion air  
stream.  
4. The vent piping must terminate in an elbow pointed  
outward or away from the air inlet, as shown in FIG. 3-1B.  
Do not exceed the maximum lengths of the  
outside vent piping shown in FIG.’s 3-1B  
ƽ WARNING  
and 3-1C. Excessive length exposed to the  
outside could cause freezing of condensate  
in the vent pipe, resulting in potential boiler  
shutdown.  
Figure 3-1B Alternate Sidewall Termination of Air and  
Vent w/Field Supplied Fittings  
Sidewall vent and air inlet terminations  
must terminate in the same pressure zone.  
ƽ WARNING  
f. Do not terminate above any door or window.  
Condensate can freeze, causing ice formations.  
g. Locate or guard vent to prevent condensate damage  
to exterior finishes.  
22  
Installation & Operation Manual  
3 Sidewall direct venting  
(continued)  
Vent/air termination – sidewall  
Figure 3-2A Clearance to Gravity Air Inlets  
Figure 3-1C Alternate Stainless Steel Sidewall  
Termination w/Field Supplied Fittings  
PVC/CPVC or ABS is acceptable air inlet pipe material.  
NOTICE  
12"  
MIN.  
VENT / AIR  
TERMINATION  
TO BOILER INTAKE  
AIR CONNECTION  
12"  
MIN.  
12" (305 MM) MIN  
15" (381 MM) MAX  
12"  
MIN.  
FROM BOILER VENT  
PIPE CONNECTION  
Figure 3-2B Alternate Clearance to Gravity Air  
Inlets  
w/Field Supplied Fittings  
12" (305 MM) MIN  
Table 3B Stainless Steel Sidewall Vent Kits  
Model Kit Number  
Vent Size  
12” (305 MM)  
MIN  
KIT30028  
6 inch vent  
1.0 - 1.5  
(Stainless Steel)  
KIT30029  
1.3 - 1.5  
7 inch vent  
BIRD  
SCREEN  
(TYPICAL)  
(Stainless Steel)  
5. Maintain clearances as shown in FIG.’s 3-1A thru 3-4B,  
pages 22 and 24. Also maintain the following:  
a. Vent must terminate:  
12” (305 MM)  
MIN  
12” (305 MM)  
MIN  
• At least 6 feet (1.8 m) from adjacent walls.  
• No closer than 12 inches (305 mm) below roof  
overhang.  
• At least 7 feet (2.1 m) above any public walkway.  
• At least 3 feet (.9 m) above any forced air intake  
within 10 feet (3 m).  
Figure 3-3A Clearance to Forced Air Inlets  
IF LESS  
THAN 10’  
• No closer than 12 inches (305 mm) below or  
horizontally from any door or window or any  
other gravity air inlet.  
VENT / AIR  
TERMINATION  
36"  
MIN.  
b. Air inlet must terminate at least 12 inches (305 m)  
above grade or snow line; at least 12 inches  
(305 mm) below the vent termination; and the vent  
pipe must not extend more than 24 inches (610 mm)  
vertically outside the building as shown in FIG.’s  
3-1B and 3-1C.  
FORCED AIR  
INLET  
c. Do not terminate closer than 4 feet (1.2 m)  
horizontally from any electric meter, gas meter,  
regulator, relief valve, or other equipment. Never  
terminate above or below any of these within 4 feet  
(1.2 m) horizontally.  
7' MIN. ABOVE ANY  
PUBLIC WALKWAY  
6. Locate terminations so they are not likely to be damaged  
by foreign objects, such as stones or balls, or subject to  
buildup of leaves or sediment.  
23  
Installation & Operation Manual  
3 Sidewall direct venting  
8. PVC/CPVC terminations are designed to accommodate any  
wall thickness of standard constructions per the directions  
found in this manual.  
Figure 3-3B Alternate Clearance to Forced Air Inlets w/  
Field Supplied Fittings  
IF LESS  
THAN 10’ (3 M)  
9. Stainless steel terminations are designed to penetrate walls  
with a thickness up to 9.25 inches of standard construction.  
36” (914 MM)  
MIN  
Figure 3-4A PVC/CPVC Sidewall Termination Assembly  
FORCED AIR  
INLET  
VENT  
AIR  
BIRD  
SCREEN  
(TYPICAL)  
7’ (2.1 M) MIN ABOVE ANY  
PUBLIC WALKWAY  
CENTERLINE WIDTH  
AIR PIPING  
VENT PIPING  
VENT PLATE  
VENT CAP  
WALL PLATE  
GALVANIZED  
THIMBLE  
Prepare wall penetrations  
1. Use the factory supplied wall plate as a template to locate  
the vent and air intake holes and mounting holes.  
Air pipe penetration:  
a. Cut a hole for the air pipe. Size the air pipe hole as  
close as desired to the air pipe outside  
diameter.  
Table 3C Sidewall Vent Centerline Dimensions  
Model  
Air  
Vent Centerline Width  
Vent pipe penetration:  
All  
6"  
6"  
7 3/4"  
a. Cut a hole for the vent pipe. For either combustible  
or noncombustible construction, size the vent pipe  
hole with at least a 1/2 inch clearance around the  
vent pipe outer diameter:  
• 7½ inch hole for 6 inch vent pipe  
Figure 3-4B Polypropylene Sidewall Termination Assembly  
• 8½ inch hole for 7 inch vent pipe  
SIDEWALL  
ADAPTER  
(AIR)  
Drill 3/16" diameter holes for inserting the plastic anchors  
into the wall.  
WALL  
PLATE  
SIDEWALL  
RETAINING  
PLATE  
2. For Polypropylene Only: Install the vent and air intake  
sidewall adapters from Table 2E on page 20 into the vent  
plate. Slide the sidewall retaining bracket down the  
sidewall adapters flush to the vent plate (FIG. 3-4B).  
3. For PVC/CPVC Only: Install the vent and air intake  
piping through the wall into the vent plate openings.  
Use RTV silicone sealant to seal the air pipe. Use the  
cement/primer listed in Table 2C on page 19 to seal the  
vent pipe.  
VENT  
PLATE  
VENT  
CAP  
SIDEWALL  
ADAPTER  
(VENT)  
4. Mount and secure the vent plate to the wall, using stainless  
steel screws.  
5. Seal all gaps between the pipes and wall. Seal around the  
plate to the wall assuring no air gaps.  
IMG00085  
GALVANIZED  
THIMBLE  
6. Assemble the vent cap to the vent plate (see FIG.’s 3-4A  
and 3-4B). Insert the stainless steel screws into the vent  
cap screw hole openings and securely attach the vent cap  
to the vent plate.  
7. Seal all wall cavities.  
24  
Installation & Operation Manual  
3 Sidewall direct venting  
(continued)  
Multiple vent/air terminations  
Prepare wall penetrations (Alternate  
Field Supplied Options)  
1. When terminating multiple SYNC boilers terminate  
each vent/air connection as described in this manual  
(FIG. 3-5A).  
1. Air pipe penetration (see FIG. 3-4B):  
a. Cut a hole for the air pipe. Size the air pipe hole as  
close as desired to the air pipe outside diameter.  
All vent pipes and air inlets must  
ƽ WARNING  
2. Vent pipe penetration (see FIG. 3-4B):  
a. Cut a hole for the vent pipe. For either combustible  
or noncombustible construction, size the vent pipe  
hole with at least a 1/2 inch clearance around the vent  
pipe outer diameter:  
terminate at the same height to avoid  
possibility of severe personal injury,  
death, or substantial property damage.  
2. Place wall penetrations to obtain minimum clearance of  
12 inches (305 mm) between vent pipe and adjacent air  
inlet elbow, as shown in FIG. 3-5A for U.S. installations.  
For Canadian installations, provide clearances required by  
CSA B149.1 Installation Code.  
• 7½ inch (178 mm) hole for 6 inch (152 mm) vent  
pipe  
• 8½ inch (203 mm) hole for 7 inch (178 mm) vent  
pipe  
3. The air inlet of a SYNC is part of a direct vent connection.  
It is not classified as a forced air intake with regard to  
spacing from adjacent boiler vents.  
b. Insert a galvanized metal thimble in the vent pipe  
hole (when required by local codes).  
3. Use a sidewall termination plate as a template for correct  
location of hole centers.  
Figure 3-5A Multiple Vent Terminations (must also  
comply with Figure 3-1A)  
4. Follow all local codes for isolation of vent pipe when  
passing through floors or walls.  
12" MIN. BETWEEN EDGE OF AIR  
INLET AND ADJACENT VENT OUTLET  
5. Seal exterior openings thoroughly with exterior caulk.  
VENT  
Figure 3-4C Alternate Sidewall Termination Assembly  
AIR  
PVC/CPVC or Stainless Steel  
GALVANIZED  
SIDEWALL  
TERMINATION PLATE  
THIMBLE  
(WHEN REQUIRED BY LOCAL CODES)  
ELBOW  
VENT  
PIPING  
AIR PIPING  
VENT / AIR  
TERMINATION  
Figure 3-5B Alternate Multiple Vent Terminations w/Field  
Supplied Fittings (must also comply with Figure 3-1B)  
BIRD SCREEN  
VENT  
ELBOW  
BIRD SCREEN  
12” (305 MM) MIN  
15” (381 MM) MAX  
12” (305 MM) MIN. BETWEEN EDGE  
OF AIR PIPE AND ADJACENT VENT  
PIPE  
AIR  
25  
Installation & Operation Manual  
4 Vertical direct venting  
Vent/air termination – vertical  
Figure 4-1 PVC/CPVC/Polypropylene Vertical Termination  
of Air and Vent  
Follow instructions below when  
ƽ WARNING  
ALTERNATE INTAKE LOCATIONS:  
INTAKE PIPES MAY BE LOCATED  
ANYWHERE WITHIN 24" (610 MM)  
OF VENT PIPE  
determining vent location to avoid  
possibility of severe personal injury, death  
or substantial property damage.  
BIRD SCREEN  
(TYPICAL)  
Determine location  
VENT  
COUPLING  
(FIELD SUPPLIED)  
6" (152 MM) MINIMUM  
ABOVE ROOF /  
SNOW LINE  
Locate the vent/air terminations using the following  
guidelines:  
VENT OUTLET  
COMBUSTION  
12" MINIMUM  
1. The total length of piping for vent or air must not exceed  
the limits given in the General Venting Section on page  
16 of this manual.  
AIR  
ABOVE AIR INLET  
Figure 4-2 Stainless Steel Vertical Termination of Air  
and Vent  
2. Prepare the vent termination and the air termination  
elbow (FIG. 4-1) by inserting bird screens. Bird screens  
should be obtained locally.  
ALTERNATE INTAKE LOCATIONS:  
INTAKE PIPES MAY BE LOCATED  
ANYWHERE WITHIN 24” (610 MM)  
OF VENT PIPE  
3. The vent must terminate at least 3 feet above the highest  
place in which the vent penetrates the roof and at least  
2 feet above any part of a building within 10 horizontal  
feet.  
BIRD SCREEN  
(TYPICAL)  
VENT  
4. The air piping must terminate in a down-turned 180°  
return pipe no further than 2 feet from the center of the  
vent pipe. This placement avoids recirculation of flue  
products into the combustion air stream.  
6" (152 MM) MINIMUM  
ABOVE ROOF /  
SNOW LINE  
COM,BUSTION  
AIR  
VENT OUTLET  
36” (914 MM) MINIMUM  
ABOVE AIR INLET  
5. The vent piping must terminate in an up-turned coupling  
as shown in FIG. 4-1. The top of the coupling must be  
at least 1 foot above the air intake. When the vent  
termination uses a rain cap as illustrated in FIG. 4-1  
maintain at least 36" (914 mm) above the air inlet. The  
air inlet pipe and vent pipe can be located in any desired  
position on the roof, but must always be no further than  
2 feet (.6 m) apart and with the vent termination at least  
1 foot for PVC and 3 feet for stainless steel, above the air  
intake.  
5. Locate terminations so they are not likely to be damaged  
by foreign objects, such as stones or balls, or subject to  
buildup of leaves or sediment.  
Prepare roof penetrations  
1. Air pipe penetration:  
a. Cut a hole for the air pipe. Size the air pipe hole as  
close as desired to the air pipe outside diameter.  
6. Maintain the required dimensions of the finished  
termination piping as shown in FIG. 4-1.  
2. Vent pipe penetration:  
a. Cut a hole for the vent pipe. For either combustible  
or noncombustible construction, size the vent pipe  
hole with at least a 1/2 inch clearance around the  
vent pipe outer diameter:  
7. Do not extend exposed vent pipe outside of building  
more than shown in this document. Condensate could  
freeze and block vent pipe.  
7½ inch (178 mm) hole for 6 inch (152 mm) vent  
pipe  
Rooftop vent and air inlet terminations  
ƽ WARNING  
8½ inch (203 mm) hole for 7 inch (178 mm) vent  
pipe  
must terminate in the same pressure  
zone, unless vertical vent sidewall air is  
set up as shown in the General Venting -  
Vertical Vent, Sidewall Air Section.  
b. Insert a galvanized metal thimble in the vent pipe  
hole (when required by local codes).  
3. Space the air and vent holes to provide the minimum  
spacing shown in FIG.’s 4-1 and 4-2.  
4. Follow all local codes for isolation of vent pipe when  
passing through floors, ceilings, and roofs.  
5. Provide flashing and sealing boots sized for the vent pipe  
and air pipe.  
26  
Installation & Operation Manual  
4 Vertical direct venting  
(continued)  
Multiple vent/air terminations  
Figure 4-3 Vertical Terminations with Multiple Boilers  
1. When terminating multiple SYNC boilers, terminate  
each vent/air connection as described in this manual  
(FIG. 4-3).  
12" (305 MM) MINIMUM  
VERTICALLY FROM VENT  
OUTLET TO ANY AIR INLET  
VENT  
Terminate all vent pipes at the same height  
ƽ WARNING  
AIR  
12" (305 MM) MINIMUM FROM EDGE  
OF AIR INTAKE PIPE TO ADJACENT  
VENT PIPE FROM ANOTHER BOILER  
and all air pipes at the same height to  
VENT  
avoid recirculation of flue products and  
the possibility of severe personal injury,  
death, or substantial property damage.  
AIR  
2. Place roof penetrations to obtain minimum clearance of  
12 inches (305 mm) between edge of air intake elbow and  
adjacent vent pipe of another boiler for U.S. installations  
(see FIG. 4-3). For Canadian installations, provide  
clearances required by CSA B149.1 Installation Code.  
Figure 4-4 Alternate Vertical Terminations with Multiple  
Boilers  
3. The air inlet of a SYNC boiler is part of a direct vent  
connection. It is not classified as a forced air intake with  
regard to spacing from adjacent boiler vents.  
VENT  
VENT  
12" (305 MM) MINIMUM  
VERTICALLY FROM VENT  
OUTLET TO ANY AIR INLET  
AIR  
AIR  
27  
Installation & Operation Manual  
5 Hydronic piping  
System water piping methods  
General piping information  
The SYNC is designed to function in a closed loop pressurized Basic steps are listed below along with illustrations on the  
system not less than 12 psi (83 kPa). A temperature and following pages (FIG.’s 5-5 and 5-6), which will guide you  
pressure gauge is included to monitor system pressure and through the installation of the SYNC (reference FIG.s 5-1A and  
outlet temperature and should be located on the boiler outlet. 5-1B).  
1. Connect the system returns marked “Inlet”, make sure to  
It is important to note that the boiler has a pressure drop  
install with pipe sealant compound.  
which must be figured in when sizing the circulators. Each  
2. Connect the system supply marked “Outlet”, make sure to  
install with pipe sealant compound.  
boiler installation must have an air elimination device, which  
will remove air from the system. Install the boiler so the  
gas ignition system components are protected from water  
(dripping, spraying, etc.) during appliance operation or basic  
service of circulator replacement, valves, and others.  
3. Install purge and balance valve or shutoff valve and drain  
on system return to purge air out of each zone.  
4. Install a backflow preventer on the cold feed make-up water  
line.  
Observe a minimum of 1/4 inch (6 mm) clearance around  
all un-insulated hot water pipes when openings around the  
pipes are not protected by non-combustible materials.  
5. Install a pressure reducing valve on the cold feed make-up  
water line, (15 psi (103 kPa) nominal). Check temperature  
and pressure gauge (shipped separately), which should read  
a minimum pressure of 12 psi (83 kPa).  
Low water cutoff device  
6. Install the circulators as shown on the piping diagrams in  
this section. Make sure the circulators are properly sized  
for the system and friction loss. Install check valves with  
each boiler circulator.  
An electronic low water cutoff is provided as standard  
equipment on all models. The low water cutoff should be  
inspected every 6 months.  
Chilled water system  
7. Install an expansion tank on the system supply. Consult the  
tank manufacturer’s instruction for specific information  
relating to tank installation. Size the expansion tank for the  
required system volume and capacity.  
If the boiler supplies hot water to heating coils in air handler  
units, flow control valves or other devices must be installed to  
prevent gravity circulation of heater water in the coils during  
the cooling cycle. A chilled water medium must be piped in  
parallel with the heater.  
8. Install an air elimination device on the system supply.  
9. Install a drain valve at the lowest point of the system.  
Note: The boiler cannot be drained completely of water  
without purging the unit with an air pressure of 15 psi  
(103 kPa).  
Freeze protection  
Freeze protection for new or existing systems must use glycol  
that is specially formulated for this purpose. This includes  
inhibitors, which prevent the glycol from attacking the  
metallic system components. Make certain to check that  
the system fluid is correct for the glycol concentration and  
inhibitor level. The system should be tested at least once  
a year and as recommended by the producer of the glycol  
solution. Allowance should be made for the expansion of the  
glycol solution in the system piping.  
10. This appliance is supplied with a relief valve sized in  
accordance with ASME Boiler and Pressure Vessel Code,  
Section IV (“Heating Boilers”). The safety relief valve  
is installed at the factory and is located on the rear of  
the boiler. Pipe the discharge of the safety relief valve to  
prevent injury in the event of pressure relief. Pipe the  
discharge to a drain. Provide piping that is the same size as  
the safety relief valve outlet. Never block the outlet of the  
safety relief valve.  
11. On any pre-existing system, it is good practice to install  
a field supplied strainer to prevent damage to the heat  
exchanger.  
Use only inhibited propylene glycol  
ƽ WARNING  
solutions, which are specifically formulated  
for hydronic systems. Ethylene glycol is  
toxic and can attack gaskets and seals used  
in hydronic systems.  
See the piping illustrations included in this section, FIG.’s 5-5  
and 5-6 for suggested guidelines in piping the SYNC.  
Please note that these illustrations are meant  
NOTICE  
to show system piping concept only, the  
installer is responsible for all equipment and  
detailing required by local codes.  
28  
Installation & Operation Manual  
5 Hydronic piping  
(continued)  
Circulator sizing  
The SYNC heat exchanger does have a pressure drop, which must be considered in your system design. Refer to the graph in  
FIG. 5-4 for pressure drop through the SYNC heat exchanger.  
Near boiler piping connections  
Figure 5-1A Near Boiler Piping w/Y-Strainer  
DRAIN (TYPICAL)  
SYSTEM SUPPLY SENSOR  
(NOTICE: A SYSTEM SUPPLY  
SENSOR MUST BE INSTALLED FOR  
PROPER BOILER OPERATION.)  
SYSTEM PUMP  
ISOLATION VALVE  
(TYPICAL)  
Y-STRAINER  
(RECOMMENDED)  
(TYPICAL)  
TEMPERATURE GAUGE  
HEAT EXCHANGER 1  
BOILER PUMP  
RELIEF VALVE  
HEAT EXCHANGER 2  
BOILER PUMP  
TO FLOOR DRAIN  
CHECK VALVE  
(TYPICAL)  
Figure 5-1B Near Boiler Piping w/Low Loss Header  
AIR VENT VALVE  
LOW LOSS HEADER  
DRAIN VALVE  
DRAIN  
(TYPICAL)  
(TYPICAL)  
AIR SEPARATOR  
SYSTEM SENSOR  
SYSTEM PUMP  
ISOLATION VALVE  
(TYPICAL)  
HEAT EXCHANGER 1  
BOILER PUMP  
EXPANSION TANK  
Y-STRAINER  
(RECOMMENDED)  
TEMPERATURE GAUGE  
RELIEF VALVE  
HEAT EXCHANGER 2  
BOILER PUMP  
TO FLOOR  
DRAIN  
CHECK VALVE  
(TYPICAL)  
29  
Installation & Operation Manual  
5 Hydronic piping  
Hot Water Generator pump sizing  
The SYNC has two (2) heat exchangers that require two (2) individual pumps for proper installation in the boiler loop and an  
additional two (2) pumps for the Hot Water Generator loop.  
Hot Water Pump Head Loss = Ft. of Head for Heat Exchanger 1 (at required flow) + Ft. of Head for the Hot Water Generator  
(at 2 X the flow of Heat Exchanger 1)  
Example:  
Boiler: SB1500  
A T of 30° requires a flow through each heat exchanger of 51 GPM. The heat exchanger head loss is 18 ft. of head (see Table 5A).  
Coupled with a Lochinvar Hot Water Generator with a 8-42 (diameter-length) tube bundle the calculated pressure drop is  
1.2 Ft. of Head at 102 GPM.  
Hot Water Pump Head Loss = 18 Ft/Hd (51 GPM) + 1.2 Ft/Hd (102 GPM) = 19.2 Ft/Hd  
A pump will need to be selected to flow 51 GPM with a head loss of 19.2 Ft/Hd.  
Figure 5-2 Boiler Schematic  
TO SYSTEM  
FROM SYSTEM  
HEAT EXCHANGER 2  
BOILER PUMP  
HEAT EXCHANGER 1  
BOILER PUMP  
AIR COVER  
HOT WATER  
GENERATOR  
HEAT EXCHANGER 1  
HOT WATER PUMP  
51 GPM  
102 GPM  
102 GPM  
51 GPM  
HEAT EXCHANGER 2  
HOT WATER PUMP  
Figure 5-3 Pump Configuration  
FROM SYSTEM  
FROM SYSTEM  
TO BOILER  
INLETS  
TO BOILER  
INLETS  
OK  
NO  
30  
Installation & Operation Manual  
5 Hydronic piping  
(continued)  
Figure 5-4 Pressure Drop vs. Flow  
Pressure Drop vs Flow  
60  
50  
40  
30  
20  
10  
SB1500  
SB1300  
SB1000  
0
0
10  
20  
30  
40  
50  
60  
70  
80  
90  
Flow Rate (GPM) - Single Heat Exchanger Only  
Table 5A Sizing Information for Temperature Rise Applications_20°F, 25°F, 30°F and 35°F  
TEMPERATURE RISE APPLICATIONS  
20°F  
25°F  
30°F  
35°F  
MINIMUM PIPE  
SIZE  
Model  
GPM  
55  
65*  
74*  
FT/HD  
31  
30  
GPM  
40  
52  
FT/HD  
20  
20  
GPM  
38  
45  
FT/HD  
18  
16  
GPM  
32  
37  
FT/HD  
13  
11  
1000  
1300  
1500  
3"  
3"  
3"  
33  
60  
23  
51  
18  
42  
12  
Pump sizing and flow requirements are  
based on 20 feet (6 m) of black iron piping, 4  
- 90° elbows, and 2 - fully ported ball valves.  
5. Check valves:  
NOTICE  
Field supplied.  
Check valves are required for  
installation as shown in FIG.’s 5-5 and 5-6. Failure to  
install check valves could result in a reverse flow condition  
during pump(s) off cycle.  
*When using copper with a 20° temperature  
rise increase piping to 3".  
6. Domestic indirect hot water isolation valves:  
Field supplied.  
required. Failure to use full port ball valves could  
result in a restricted flow rate through the boiler.  
Full port ball valves are  
It is required that near boiler piping systems  
utilize Primary/Secondary configurations as  
shown in FIG.’s 5-5 and 5-6 only. The use of  
other near boiler piping configurations could  
result in improper building and system flow  
rates leading to inadvertent boiler high limit  
shutdowns and poor system performance.  
NOTICE  
7. Anti-scald mixing valve:  
Field supplied.  
recommended when storing domestic hot water above  
115°F (46°C).  
An anti-scald mixing valve is  
8. Unions:  
Near boiler piping components  
1. Boiler piping:  
Field supplied. Recommended for unit serviceability.  
9. Pressure relief valve:  
Factory supplied. The pressure relief valve is sized to  
ASME specifications.  
Boiler system piping MUST be sized per the pipe  
requirements listed in Table 5A. Reducing the pipe size  
can restrict the flow rate through the boiler, causing  
inadvertent high limit shutdowns and poor system  
performance.  
10. System temperature sensor:  
Lochinvar supplies  
a
system temperature sensor.  
The sensor is to be installed in the heating loop  
downstream from the boiler hot water piping and  
2. Boiler circulating pump:  
heating loop junction.  
The sensor should be  
Field supplied. The boiler circulating pump MUST be  
sized to meet the specified minimum flow requirements  
listed in FIG. 5-4.  
located far enough downstream to sense system diluted  
water temperature.  
A system supply sensor (factory supplied)  
MUST BE installed for proper boiler  
operation.  
3. Hot Water Generator circulating pump:  
NOTICE  
Field supplied. The pump MUST be sized to meet  
the specified minimum flow requirements listed in  
FIG. 5-4.  
Consult the indirect boiler operating  
11. Y-Strainer:  
guide to determine flow characteristics for the selected  
product used.  
Field supplied. A Y-strainer or equivalent multipurpose  
strainer is recommended at the inlet of the heat exchanger  
to remove system particles from older hydronic systems and  
protect newer systems.  
4. Boiler isolation valves:  
Field supplied. Full port ball valves are required. Failure  
to use full port ball valves could result in a restricted flow  
rate through the boiler.  
31  
Installation & Operation Manual  
5 Hydronic piping  
Figure 5-5 Single Boiler - Primary/Secondary Piping  
A
system supply sensor (factory  
NOTICE  
supplied) MUST BE installed for proper  
boiler operation.  
BALL VALVE  
(TYPICAL)  
AIR  
MAY SUBSTITUTE LOW LOSS HEADER  
SEPERATOR  
DRAIN POINT  
(TYPICAL)  
SYSTEM SUPPLY  
SENSOR  
SYSTEM  
HOT WATER  
GENERATOR  
CIRCULATOR  
PRESSURE GAUGE  
BACK FLOW  
PREVENTER  
MAKE UP  
WATER  
PRESSURE REDUCING  
(VALVE)  
EXPANSION  
TANK  
WATER GENERATOR  
CIRCULATOR  
(TYPICAL)  
UNION (TYPICAL)  
HEAT EXCHANGER 1  
BOILER PUMP  
TEMPERATURE/  
PRESSURE GAUGE  
PRESSURE RELIEF  
VALVE  
Y-STRAINER  
FLOW CHECK  
(RECOMMEND)  
TO FLOOR  
VALVE (TYPICAL)  
HEAT EXCHANGER 2  
BOILER PUMP  
(TYPICAL)  
DRAIN  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
for all equipment and detailing required by local codes.  
NOTICE  
NOTICE  
32  
System flow should always remain higher than the required flow for the boiler(s) when the boiler(s) is in  
operation to prevent short cycling and high limit issues.  
Installation & Operation Manual  
5 Hydronic piping  
(continued)  
Figure 5-6 Multiple Boilers - Primary/Secondary Piping  
Number of Units  
2
3
4
5
6
7
8
Model  
Manifold Pipe Sizes in Inches (mm)  
1000  
1300  
1500  
4 (102)  
5 (127)  
5 (127)  
5 (127)  
5 (127)  
6 (152)  
6 (152)  
6 (152)  
6 (152)  
6 (152)  
8 (203)  
8 (203)  
8 (203)  
8 (203)  
8 (203)  
8 (203)  
8 (203)  
8 (203)  
8 (203)  
8 (203)  
10 (254)  
A
system supply sensor (factory  
NOTICE  
supplied) MUST BE installed for proper  
boiler operation.  
MAY SUBSTITUTE LOW LOSS HEADER  
BALL VALVE  
(TYPICAL)  
HOT WATER  
GENERATOR  
AIR  
SEPARATOR  
DRAIN POINT  
(TYPICAL)  
SYSTEM SUPPLY  
SENSOR  
SYSTEM  
CIRCULATOR  
BACK FLOW  
PREVENTER  
MAKE UP  
WATER  
WATER GENERATOR  
CIRCULATOR  
(TYPICAL)  
Y-STRAINER  
(RECOMMENDED)  
TYPICAL)  
PRESSURE REDUCING  
(VALVE)  
FLOW CHECK  
VALVE (TYPICAL)  
EXPANSION  
TANK  
PRESSURE GAUGE  
UNION (TYPICAL)  
TEMPERATURE/  
HEAT EXCHANGER 1  
BOILER PUMP  
PRESSURE GAUGE  
PRESSURE RELIEF  
VALVE  
HEAT EXCHANGER 2  
BOILER PUMP  
TO FLOOR  
DRAIN (TYPICAL)  
Please note that these illustrations are meant to show system piping concept only, the installer is responsible  
for all equipment and detailing required by local codes.  
NOTICE  
NOTICE  
System flow should always remain higher than the required flow for the boiler(s) when the boiler(s) is in  
operation to prevent short cycling and high limit issues.  
33  
Installation & Operation Manual  
6 Gas connections  
3. Support piping with hangers, not by the boiler or its  
accessories.  
Connecting gas supply piping  
1. Refer to FIG. 6-1 to pipe gas to the boiler.  
a. Install ground joint union for servicing, when  
required.  
The gas valve and blower will not support  
the weight of the piping. Do not attempt  
ƽ WARNING  
to support the weight of the piping with  
the boiler or its accessories. Failure to  
comply could result in severe personal  
injury, death, or substantial property  
damage.  
b. In Canada – When using manual main shutoff  
valves, it must be identified by the installer.  
2. Install sediment trap / drip leg.  
Figure 6-1 Gas Supply Piping  
4. Purge all air from the gas supply piping.  
Ensure that the high gas pressure regulator  
is at least 10 feet (3 m) upstream of the  
appliance.  
ƽ WARNING  
5. Before placing the boiler in operation, check the boiler  
and its gas connection for leaks.  
a. The appliance must be disconnected from the gas  
supply piping system during any pressure testing of  
that system at a test pressure in excess of 1/2 PSIG  
(3.5 kPa).  
GAS SUPPLY  
b. The appliance must be isolated from the gas supply  
piping system by closing a manual shutoff valve  
during any pressure testing of the gas supply piping  
system at test pressures equal to or less than 1/2 PSIG  
(3.5 kPa).  
10 FT  
c. The appliance and its gas connection must be leak  
tested before placing it in operation.  
(10 LINEAR FEET  
REQUIRED)  
Do not check for gas leaks with an open  
ƽ WARNING  
flame – use the bubble test. Failure to  
use the bubble test or check for gas leaks  
can cause severe personal injury, death, or  
substantial property damage.  
UNION  
DRIP LEG  
MANUAL SHUTOFF  
VALVE  
(FIELD SUPPLIED)  
6. Use pipe sealing compound compatible with propane  
gases. Apply sparingly only to male threads of the pipe  
joints so that pipe dope does not block gas flow.  
Failure to apply pipe sealing compound as  
ƽ WARNING  
detailed in this manual can result in severe  
personal injury, death, or substantial  
property damage.  
34  
Installation & Operation Manual  
6 Gas connections  
(continued)  
Natural gas supply pressure requirements  
Use two wrenches when tightening gas  
piping at boiler (FIG. 6-2), using one  
wrench to prevent the boiler gas line  
connection from turning. Failure to  
support the boiler gas connection pipe  
to prevent it from turning could damage  
gas line components.  
ƽ WARNING  
1. Pressure required at the gas valve inlet pressure port:  
• Maximum 14 inches w.c. (3.5 kPa) with no flow  
(lockup) or with boiler on.  
• Minimum 5 inches w.c. (1.25 kPa) for 1.0 models with gas  
flowing (verify during boiler startup).  
• Minimum 4 inches w.c. (.99 kPa) for 1.3 - 1.5 models with  
gas flowing (verify during boiler startup).  
Figure 6-2 Inlet Pipe with Backup Wrench  
2. Install 100% lockup gas pressure regulator in supply line  
if inlet pressure can exceed 14 inches w.c. (3.5 kPa) at any  
time. Adjust lockup regulator for 14 inches w.c. (3.5 kPa)  
maximum.  
Propane Gas:  
Check boiler rating plate to determine which  
fuel the boiler is set for. SYNC boilers CAN  
ƽ WARNING  
NOT be field converted. Failure to comply  
could result in severe personal injury, death,  
or substantial property damage.  
Pipe sizing for propane gas  
1. Contact gas supplier to size pipes, tanks, and 100% lockup  
gas pressure regulator.  
Propane Supply Pressure Requirements  
1. Adjust propane supply regulator provided by the gas  
supplier for 14 inches w.c. (3.5 kPa) maximum pressure.  
USE BACK UP WRENCH TO  
PREVENT PIPE FROM ROTATING  
2. Pressure required at gas valve inlet pressure port:  
• Maximum 14 inches w.c. (3.5 kPa)with no flow (lockup)  
or with boiler on.  
Maximum inlet gas pressure must not  
NOTICE  
exceed the value specified. Minimum  
value listed is for the purposes of input  
adjustment.  
• Minimum 8 inches w.c. (1.9 kPa) with gas flowing (verify  
during boiler startup).  
Ensure that the high gas pressure regulator  
is at least 10 feet (3 m) upstream of the  
appliance.  
ƽ WARNING  
Natural gas:  
Check boiler rating plate to determine  
ƽ WARNING  
which fuel the boiler is set for. SYNC  
boilers CANNOT be field converted.  
Failure to comply could result in severe  
personal injury, death, or substantial  
property damage.  
Pipe sizing for natural gas  
1. Refer to Table 6A for pipe length and diameter. Based on  
rated boiler input (divide by 1,000 to obtain cubic feet per  
hour).  
a. Table 6A is only for natural gas with specific gravity  
0.60 inches, with a pressure drop through the gas  
piping of 0.5 inches w.c.  
b. For additional gas pipe sizing information, refer to  
ANSI Z223.1 (or B149.1 for Canadian installations).  
35  
Installation & Operation Manual  
6 Gas connections  
Table 6A Natural Gas Pipe Size Chart  
TABLE - 6A  
GAS PIPING SIZE CHART  
Maximum  
Capacity of Pipe  
in Thousands  
of Btu/hr for  
gas pressures of  
14 Inches Water  
Column (0.5  
PSIG) or less and  
a pressure drop  
of 0.5 Inch Water  
Column (Based  
on NAT GAS,  
Nominal  
Iron Pipe  
Size  
Length of Pipe in Straight Feet  
Inches  
10  
20  
30  
40  
50  
60  
70  
80  
90  
100 125 150 175 200  
1½  
2
2,150 1,500 1,210 1,020 923  
830  
769  
707  
666  
636  
564 513  
472  
871  
441  
820  
4,100 2,820 2,260 1,950 1,720 1,560 1,440 1,330 1,250 1,180 1,100 974  
2½  
3
6,460 4,460 3,610 3,100 2,720 2,460 2,310 2,100 2,000 1,900 1,700 1,540 1,400 1,300  
11,200 7,900 6,400 5,400 4,870 4,410 4,000 3,800 3,540 3,300 3,000 2,720 2,500 2,340  
23,500 16,100 13,100 11,100 10,000 9,000 8,300 7,690 7,380 6,870 6,150 5,640 5,130 4,720  
1025 Btu/hr per  
Cubic Foot of  
Gas and 0.60  
Specific Gravity)  
4
4. Slowly turn on the gas supply at the field installed  
manual gas valve.  
Check inlet gas supply  
CSA or UL listed flexible gas connections are  
5. Turn the power switch to the “ON” position.  
NOTICE  
acceptable, but you must exercise caution to  
ensure that the line has adequate capacity to  
allow your boiler to fire at full rate. Consult  
with local codes for proper installation or  
service procedures.  
6. Adjust the temperature set point on the control panel of  
the SMART TOUCH control module to call for heat.  
7. Observe the gas supply pressure as the burner fires at  
100% of rated input. Percent of burner input will be  
displayed on the Burner Screen.  
DO NOT adjust or attempt to measure gas  
valve outlet pressure. Attempting to alter  
or measure the gas valve outlet pressure  
could result in damage to the valve, causing  
potential severe personal injury, death, or  
substantial property damage.  
ƽ WARNING  
8. Ensure inlet pressure is within specified range.  
Minimum and maximum gas supply pressures are  
specified in this section of the manual.  
9. If gas supply pressure is within normal range and no  
adjustments are needed, proceed on to Step 11.  
The gas piping must be sized for the proper flow and length of  
pipe, to avoid excessive pressure drop. Both the gas meter and  
the gas regulator must be properly sized for the total gas load.  
10. If the gas pressure is out of range, contact the gas utility,  
gas supplier, qualified installer or service agency to  
determine the necessary steps to provide proper gas  
pressure to the control.  
If you experience a pressure drop greater than 1 inch w.c.  
(249 Pa), the meter, regulator, or gas line is undersized or in  
need of service. Perform the steps below when checking inlet  
gas supply:  
11. Turn the power switch to the “OFF” position.  
12. Shut off the gas supply at the manual gas valve in the gas  
piping to the appliance.  
1. Turn the main power switch to the “OFF” position.  
13. Remove the manometer from the pressure tap on top of  
the gas valve. Remove the 1/8" (3 mm) field supplied  
fitting and reinstall the pipe plug removed in Step 3.  
2. Shut off gas supply at the manual gas valve in the gas  
piping to the appliance.  
3. Remove the 1/8" pipe plug on the flange to the field  
supplied gas shutoff valve and install a suitable 1/8"  
fitting (field supplied) for the manometer tubing. Place the  
tubing of the manometer over the tap once the 1/8"  
fitting is installed as shown in FIG. 6-3.  
36  
Installation & Operation Manual  
6 Gas connections  
(continued)  
Do not check for gas leaks with an open  
flame -- use the bubble test. Failure to  
use the bubble test or check for gas leaks  
can cause severe personal injury, death, or  
substantial property damage.  
Gas Pressure  
ƽ WARNING  
The gas pressure must remain between 4 inches w.c.  
(.99 kPa) minimum (5 inches w.c. for 1.0 models) and  
14 inches w.c. (3.5 kPa) maximum for Natural gas and  
between 8 inches w.c. (1.9 kPa) minimum and 14 inches  
w.c. (3.5 kPa) maximum for LP gas during standby  
(static) mode and while in operating (dynamic) mode.  
If an in-line regulator is used, it must be a minimum of  
10 feet (3 m) from the SYNC boiler. It is very important  
that the gas line is properly purged by the gas supplier or  
utility company. Failure to properly purge the lines or  
improper line sizing, will result in ignition failure.  
14. Turn on the gas supply at the manual gas valve.  
15. Turn the power switch to the “ON” position.  
16. Adjust the temperature set point on the control panel of  
the SMART TOUCH control module to the desired  
water temperature so the appliance will call for heat.  
17. Check burner performance by cycling the system while  
you observe burner response. The burner should ignite  
promptly. Flame pattern should be stable. Turn system  
off and allow burner to cool, then cycle burner again to  
ensure proper ignition and flame characteristics.  
The problem is especially noticeable in NEW LP  
installations and also in empty tank situations. This can  
also occur when a utility company shuts off service to an  
area to provide maintenance to their lines.  
Figure 6-3 Inlet Gas Supply Check  
Gas valve replacement  
The gas valve MUST NOT be replaced with a  
conventional gas valve under any circumstances. As  
an additional safety feature, this gas valve has a flanged  
connection to the venturi and blower.  
Failure to follow all precautions  
ƽ WARNING  
could result in fire, explosion, or  
death!  
DO NOT adjust or attempt to  
ƽ WARNING  
measure gas valve outlet pressure.  
Attempting to alter or measure the  
gas valve outlet pressure could result  
in damage to the valve, causing  
potential severe personal injury,  
death, or substantial property  
damage.  
37  
Installation & Operation Manual  
7 Field wiring  
ELECTRICAL SHOCK HAZARD – For  
Installation must comply with:  
ƽ WARNING  
your safety, turn off electrical power supply  
before making any electrical connections  
to avoid possible electric shock hazard.  
Failure to do so can cause severe personal  
injury or death.  
1. National Electrical Code and any other national, state,  
provincial, or local codes, or regulations.  
2. In Canada, CSA C22.1 Canadian Electrical Code Part 1, and  
any local codes.  
Wiring must be N.E.C. Class 1.  
NOTICE  
Line voltage connections  
1. Connect 120 VAC power wiring to the line voltage terminal  
strip in the junction box, as shown in FIG. 7-1.  
If original wiring as supplied with boiler  
must be replaced, use only type 105°C  
wire or equivalent.  
2. Provide and install a fused disconnect or service switch  
(15 amp recommended) as required by the code (see  
FIG. 7-1).  
Boiler must be electrically grounded as  
required by National Electrical Code  
ANSI/NFPA 70 – latest edition.  
3. When connecting hot water generator pumps connect  
the wiring to the line voltage terminal strip as shown in  
FIG. 7-1. Maximum current is 1.8 amps, install a field  
supplied contactor.  
Label all wires prior to disconnection when  
servicing controls. Wiring errors can  
cause improper and dangerous operation.  
ƽ CAUTION  
4. To activate a system pump, wire as shown in FIG. 7-1. Dry  
contacts are sized for 1.5 hp/120V, 3 hp/240V or 18 amps.  
5. To activate a louver, connect to the dry contacts provided.  
Contacts are rated for 5 amps, 120V.  
Figure 7-1 Line Voltage Field Wiring Connections  
120V SUPPLY  
NEUTRAL  
GROUND  
W
G
LINE  
BK  
SERVICE SWITCH  
W
G
L
MODULE I  
HOT WATER  
GENERATOR  
MODULE 2  
HOT WATER  
GENERATOR  
W
PUMP CONTROL  
G
L
BK  
G
SYSTEM PUMP  
1.5HP/120V, 3HP/240V  
W
BK  
G
MODULE I  
BOILER PUMP  
W
1.5HP/120V, 3HP/240V  
BK  
G
MODULE 2  
BOILER PUMP  
1.5HP/120V, 3HP/240V  
W
LI  
G
L2/W  
38  
Installation & Operation Manual  
7 Field wiring  
(continued)  
Low voltage connections  
Hot  
Water  
Generator  
(HW)  
thermostat  
1. Route all low voltage wires through the knockouts in the  
rear of the boiler, as shown in FIG. 7-2.  
1. Connect the HW tank thermostat to the Tank Thermostat  
terminals on the connection board (FIG. 7-3).  
2. Connect low voltage wiring to low voltage connection  
board as shown in FIG. 7-3 on page 41 of this manual and  
the boiler wiring diagram.  
Hot Water Generator (HW) tank  
sensor  
1. By installing a HW tank sensor, the SMART TOUCH  
control can perform the tank thermostat function. The  
SMART TOUCH control automatically detects the  
presence of this sensor, and generates a HW call for heat  
when the tank temperature drops 6°F (3°C) below the  
tank set point, and finishes the call for heat when the tank  
temperature reaches the tank set point.  
Figure 7-2 Routing Field Wiring  
LOW VOLTAGE  
CONNECTION BOARD  
LOW VOLTAGE  
WIRING KNOCKOUTS  
2. A TST2032 sensor MUST be used with any indirect tank.  
Failure to use the correct sensor will result in the tank  
temperature being either above or below the set point.  
Connect the correct sensor to the Tank Sensor terminals  
(see FIG. 7-3).  
Louver proving switch  
LINE VOLTAGE  
WIRING KNOCKOUTS  
1. Louvers are used to provide combustion air for the room  
air option. A louver proving switch should be installed on  
the appropriate terminals and verified prior to operation  
(see FIG. 7-3).  
Enable  
1. Connect the room thermostat or boiler enable contacts  
(isolated contact only) to terminals R and W, as shown in  
FIG. 7-3.  
Flow switch (field supplied)  
1. Flow switches are designed to prevent a no flow situation.  
2. If a thermostat is used, install the thermostat on the inside  
wall away from influences of drafts, hot or cold water  
pipes, lighting fixtures, television, sunlight, or fireplaces.  
2. A flow switch may be used to guarantee flow through the  
boiler before allowing it to fire. When used, the SYNC  
boiler requires a flow switch to be installed on each inlet.  
3. Thermostat anticipator (if applicable):  
a. If connected directly to boiler, set for 0.1 amps.  
b. If connected to relays or other devices, set to match  
total electrical power requirements of connected  
devices. See device manufacturers’ specifications  
and thermostat instructions for details.  
3. Remove the jumper wires from the terminals on the  
connection board and connect these terminals to the  
normally open contacts on the flow switches (FIG. 7-3).  
Outdoor temperature sensor  
1. Connect the outdoor temperature sensor (FIG. 7-3) to  
the Outdoor Sensor terminals on the connection board to  
enable outdoor reset operation of the SYNC.  
2. Mount the sensor on an exterior wall, shielded from direct  
sunlight or flow of heat or cooling from other sources.  
3. Route sensor wires through a knockout at the rear of the  
boiler (see FIG. 7-2).  
39  
Installation & Operation Manual  
7 Field wiring  
System supply sensor  
Wiring of the cascade  
1. By installing the system supply sensor into the supply When wiring the boilers for Cascade operation, select one boiler  
of the primary loop, the temperature of the system as the Leader boiler. The remaining boilers will be designated  
supply can be controlled. The SMART TOUCH control as Members. See page 48 “Configuration of the Cascade” for a  
automatically detects the presence of this sensor, and detailed explanation of this procedure.  
controls the boiler firing rate to maintain the system  
supply temperature to the set point.  
Connect the system supply sensor and outdoor air sensor (if  
used) to the Leader boiler. For the Cascade system to work  
properly the system supply sensor must be installed.  
DO NOT INSTALL THE SYSTEM  
SUPPLY SENSOR INTO THE SYSTEM  
RETURN.  
NOTICE  
A system supply sensor (factory supplied)  
MUST BE installed for proper boiler  
operation.  
NOTICE  
2. Connect these terminals to the system supply sensor  
(FIG. 7-3).  
The location of the system supply sensor should be downstream  
of the boiler connections in the main system loop (FIG.’s 5-5  
and 5-6). The system supply sensor should be wired to the Low  
Voltage Connection Board at the terminals marked for the  
system supply sensor (see FIG. 7-3). The Leader control will use  
the water temperature at the system supply sensor to control the  
operation of the Cascade.  
A system supply sensor (factory supplied)  
MUST BE installed for proper boiler  
operation.  
NOTICE  
Boiler management system  
If outdoor air reset is desired, the outdoor air sensor should be  
wired to the Low Voltage Connection Board at the terminals  
marked for the outdoor air sensor on the Leader boiler  
(FIG. 7-3). If the outdoor air sensor is connected, the Leader  
control will calculate the water temperature set point based  
on the programmed reset curve parameters. If the outdoor air  
sensor is not connected, the Leader control will maintain the  
fixed water temperature set point that is programmed into the  
control.  
1. An external control may be connected to control either  
the firing rate or the set point of the boiler. Connect the  
0 - 10 VDC terminals to the 0 - 10 VDC output of the  
external control. The SMART TOUCH control can be  
enabled using the Enable output (see page 39) or using  
the voltage applied to the 0 - 10 VDC input. Reference  
the SYNC Service Manual for more details.  
2. Make sure the ground terminal is connected to the  
ground output terminal of the external control, and the  
0 - 10 VDC terminal is connected to the 0 - 10 VDC  
terminal of the external control.  
If a Thermostat or Zone Control enable output is available, it  
should be wired to the Low Voltage Connection Board on the  
Leader boiler at the terminals marked Enable (FIG. 7-3). If the  
boilers are to run continuously, connect a jumper wire between  
the R and W terminals at the Enable input. This will initiate a  
call for heat on the Cascade. If the SMART TOUCH control  
is being controlled by a Boiler Management System (BMS),  
a call for heat may be initiated by the voltage applied to the  
0 - 10 VDC input.  
Runtime contacts  
The SMART TOUCH control closes a set of dry contacts  
whenever the burner is running. This is typically used by  
Building Management Systems to verify that the boiler is  
responding to a call for heat.  
Communication between the Leader boiler and the Member  
boilers is accomplished by using shielded, 2-wire twisted pair  
communication cable. Connect one of the twisted pair wires  
to terminal A on each of the Low Voltage Connection boards,  
and the other wire of the twisted pair to terminal B on each  
of the Low Voltage Connection Boards. Connect the shield  
wires to one of the shield ground terminals on the Low Voltage  
Connection Boards (FIG. 7-3). If more than two boilers are  
on the Cascade, daisy chain the wiring from the Sequencing  
terminals on the second boiler to the Sequencing terminals on  
the third boiler, then from the third to the forth, and so on.  
The connections between boilers can be made in any order,  
regardless of the addresses of the boilers. Try to keep each cable  
as short as possible.  
Alarm contacts  
The SMART TOUCH control closes another set of contacts  
whenever the boiler is locked out or the power is turned off.  
This can be used to turn on an alarm, or signal a Building  
Management System that the boiler is down. Note that these  
contacts will close momentarily at the end of each call for heat  
or at least every 24 hours.  
40  
Installation & Operation Manual  
7 Field wiring  
(continued)  
Figure 7-3 Low Voltage Field Wiring Connections  
MOD BUS  
CASCADE  
41  
Installation & Operation Manual  
8 Condensate disposal  
Use materials approved by the authority  
having jurisdiction. In the absence of  
other authority, PVC and CPVC pipe  
must comply with ASTM D1785 or D2845.  
Cement and primer must comply with  
ASME D2564 or F493. For Canada use  
CSA or ULC certified PVC or CPVC pipe,  
fittings, and cement.  
Condensate drain  
NOTICE  
1. This boiler is a high efficiency appliance that produces  
condensate.  
2. The rear of the boiler has a 1/2 inch (12.7 mm) PVC  
union for connection of a 1/2 inch (12.7 mm) PVC pipe  
(FIG. 8-1).  
3. Slope condensate tubing down and away from the boiler  
into a drain or condensate neutralizing filter. Condensate  
from the SYNC will be slightly acidic (typically with a pH  
from 3 to 5). Install a neutralizing filter if required by  
local codes.  
To allow for proper drainage on large  
horizontal runs, a second line vent may  
be required and tubing size may need to  
increase to 1 inch (25 mm).  
NOTICE  
The condensate line must remain  
unobstructed, allowing free flow of  
condensate. If condensate is allowed to  
freeze in the line or if the line is obstructed  
in any other manner, condensate can exit  
from the boiler tee, resulting in potential  
water damage to property.  
A Neutralizer Kit (FIG. 8-1) is available from the factory  
(KIT3046).  
4. Install the 1/2 inch (12.7 mm) PVC tee assembly (shipped  
with the unit) as shown in FIG. 8-1.  
5. Leave the top of the 1/2 inch (12.7 mm) tee OPEN. This  
is needed as a vacuum break.  
7. A condensate removal pump is required if boiler is below  
drain. When installing a condensate pump, select one  
approved for use with condensing boilers and furnaces.  
The pump should have an overflow switch to prevent  
property damage from condensate spillage. The switch  
should be wired to the auxiliary device proving switch  
terminals on the low voltage connection board.  
6. Do not expose condensate line to freezing temperatures.  
Figure 8-1 Condensate Disposal  
1/2" (12.7 mm) PVC TEE ASSEMBLY  
(FACTORY SUPPLIED)  
1/2" (12.7 mm) PVC UNION  
(FACTORY SUPPLIED)  
NEUTRALIZER KIT  
FLOOR DRAIN  
OR DRAIN PAN  
42  
Installation & Operation Manual  
9 Start-up  
4. At initial fill and during boiler startup and testing, check  
system thoroughly for any leaks. Repair all leaks before  
proceeding further.  
Check/control water chemistry  
Do not use petroleum-based cleaning or  
ƽ CAUTION  
sealing compounds in the boiler system.  
Damage to elastomer seals and gaskets  
in the system could occur, resulting in  
substantial property damage.  
Eliminate all system leaks. Continual  
ƽ WARNING  
fresh makeup water will reduce boiler  
life. Minerals can build up in the heat  
exchanger, reducing heat transfer,  
overheating the heat exchanger, and  
causing heat exchanger failure.  
Hardness less than 7 grains  
1. Consult local water treatment companies for hard water  
areas (above 7 grains hardness).  
Purge air from water system  
Chlorine concentration less than 200 ppm  
1. Purge air from system:  
1. Do not fill boiler or operate with water containing  
chlorine in excess of 200 ppm.  
2. Open automatic air vent (diaphragm-type or bladder-  
type expansion tank systems only) one turn.  
2. Filling with chlorinated fresh water should be acceptable  
since drinking water chlorine levels are much lower.  
3. Open other vents:  
a. Starting on the lowest floor, open air vents one at a  
time until water squirts out.  
3. Do not use the boiler to directly heat swimming pool or  
spa water.  
b. Repeat with remaining vents.  
Test/replace freeze protection fluid  
4. Refill to correct pressure.  
1. For systems using freeze protection fluids, follow fluid  
manufacturer’s instructions.  
2. Freeze protection fluid must be replaced periodically due  
to degradation of inhibitors over time. Follow all fluid  
manufacturer’s instructions.  
Freeze protection (when used)  
1. Determine freeze protection fluid quantity using  
system water content, following fluid manufacturer’s  
instructions. Boiler water content is listed on page 6.  
Remember to include expansion tank water content.  
2. Local codes may require a backflow preventer or actual  
disconnect from city water supply.  
3. When using freeze protection fluid with automatic fill,  
install a water meter to monitor water makeup. Freeze  
protection fluid may leak before the water begins to  
leak, causing concentration to drop, reducing the freeze  
protection level.  
Fill and test water system  
1. Fill system only after ensuring the water meets the  
requirements of this manual.  
2. Close manual and automatic air vents and boiler drain  
valve.  
3. Fill to correct system pressure. Correct pressure will vary  
with each application.  
a. The minimum cold water fill pressure for a  
commercial system is 12 psi (82.7 kPa).  
b. Pressure will rise when boiler is turned on and  
system water temperature increases.  
43  
Installation & Operation Manual  
9 Start-up  
Check for gas leaks  
Before starting the boiler, and during  
Propane boilers only – Your propane  
suppliermixesanodorantwiththepropane  
to make its presence detectable. In some  
instances, the odorant can fade, and the  
gas may no longer have an odor. Before  
startup (and periodically thereafter), have  
the propane supplier verify the correct  
odorant level in the gas.  
ƽ WARNING  
ƽ WARNING  
initial operation, smell near the floor and  
around the boiler for gas odorant or any  
unusual odor. Remove the top access  
panel and smell the interior of the boiler  
enclosure. Do not proceed with startup  
if there is any indication of a gas leak.  
Use an approved leak detection solution.  
Repair any leaks at once.  
Check thermostat circuit(s)  
DO NOT adjust or attempt to measure  
gas valve outlet pressure. The gas valve is  
factory set for the correct outlet pressure.  
This setting is suitable for natural gas and  
propane, requiring no field adjustment.  
Attempting to alter or measure the gas  
valve outlet pressure could result in  
damage to the valve, causing potential  
severe personal injury, death, or  
substantial property damage.  
ƽ WARNING  
1. Disconnect the two external wires connected to the  
enable terminals on the connection board.  
2. Connect a voltmeter across these two incoming wires.  
Close each thermostat, zone valve, and relay in the  
external circuit one at a time and check the voltmeter  
reading across the incoming wires.  
3. There should NEVER be a voltage reading.  
4. If a voltage does occur under any condition, check and  
correct the external wiring. (This is a common problem  
when using 3-wire zone valves.)  
Figure 9-1 Condensate Trap  
2" PVC CAP WITH  
BLOCKED DRAIN SWITCH  
5. Once the external boiler enable wiring is checked and  
corrected if necessary, reconnect the external thermostat  
circuit wires to the connection board. Allow the boiler to  
cycle.  
RETAINING  
SCREW  
PVC TEE ASSEMBLY  
(FACTORY SUPPLIED)  
CONDENSATE FROM  
HEAT EXCHANGER  
Inspect/fill condensate system  
Inspect/check condensate lines and fittings  
1. Inspect the condensate drain line, condensate PVC  
fittings and condensate trap.  
TO FLOOR  
DRAIN  
Fill condensate trap with water  
1. Remove the PVC cap retaining screw from the PVC cap  
(FIG. 9-1).  
2. Remove the 2 inch PVC cap with the switch located at the  
top of the trap (FIG. 9-1).  
3. Fill with fresh water until the water begins to pour out of  
the drain.  
4. Replace the cap. Press the cap onto the trap until the cap  
makes contact with the drain.  
5. Replace the retaining screw.  
The condensate trap (FIG. 9-1) must be  
filled with water during all times of boiler  
ƽ WARNING  
operation to avoid flue gas emission from  
the condensate drain line. Failure to fill  
the trap could result in severe personal  
injury or death.  
44  
Installation & Operation Manual  
9 Start-up  
(continued)  
Check vent piping and air piping  
Final checks before starting the boiler  
1. Check for gastight seal at every connection, seam of air  
piping, and vent piping.  
Read the SYNC Service Manual to familiarize yourself  
with SMART TOUCH control module operation. Read  
this manual, page 46 for proper steps to start boiler.  
Venting system must be sealed gastight  
ƽ WARNING  
to prevent flue gas spillage and carbon  
Verify the boiler and system are full of water and all  
monoxide emissions, which will result in  
severe personal injury or death.  
system components are correctly set for operation.  
Verify the preparation procedures of Section 9, pages 43  
Check gas piping  
and 44 have been completed.  
1. Check around the boiler for gas odor following the  
procedure on page 34 of this manual (connecting gas  
supply piping).  
Fill the vent condensate trap with water (removing the  
retaining screw in order to remove the 2 inch (50.8 mm)  
PVC cap with the switch located at the top of the trap).  
Replace the cap. Press the cap onto the trap until the  
cap makes contact with the drain. Replace the retaining  
screw.  
If you discover evidence of any gas leak,  
ƽ WARNING  
shut down the boiler at once. Find the  
leak source with a bubble test and repair  
immediately. Do not start the boiler again  
until corrected. Failure to comply could  
result in severe personal injury, death, or  
substantial property damage.  
Verify electrical connections are correct and securely  
attached.  
Inspectventpipingandairpipingforsignsofdeterioration  
from corrosion, physical damage or sagging. Verify air  
piping and vent piping are intact and correctly installed  
per this manual.  
Check flame and combustion  
1. Turn the main power off to the boiler by placing the  
“On/Off” switch in the OFF position.  
Start the boiler  
2. Remove the flue temperature sensors from the flue pipe  
connections. Note: Combustion measurements will be  
made at this point.  
1. Read and follow the Operating instructions in FIG. 9-2,  
page 46.  
If boiler does not start correctly  
3. Turn the main power on to the boiler by placing the  
“On/Off” switch in the ON position.  
1. Check for loose connections, blown fuse or service switch  
off?  
2. Is external limit control (if used) open? Is boiler water  
temperature above 200°F (93°C)?  
3. Is thermostat set below room temperature?  
4. Is gas turned on at meter or boiler?  
5. Is incoming gas pressure less than 4 inches w.c. (.99 kPa)?  
If none of the above corrects the problem, refer to the  
Troubleshooting Section of the SYNC Service Manual.  
Check system and boiler  
Check water piping  
1. Check system piping for leaks. If found, shut down  
the boiler and repair immediately. (See WARNINGS  
on pages 43 and 44 (startup) regarding failure to repair  
leaks.)  
2. Vent any remaining air from the system using manual  
vents. Air in the system will interfere with circulation  
and cause heat distribution problems and noise.  
45  
Installation & Operation Manual  
9 Start-up  
Figure 9-2 Operating Instructions  
FOR YOUR SAFETY READ BEFORE OPERATING  
WARNING: If you do not follow these instructions exactly, a fire or explosion  
may result causing property damage, personal injury, or loss of life.  
A. This appliance does not have a pilot. It is  
equipped with an ignition device which  
automatically lights the burner. Do not try  
to light the burner by hand.  
B. BEFORE OPERATING smell all around  
the appliance area for gas. Be sure to  
smell next to the floor because some gas  
is heavier than air and will settle on the  
floor.  
Immediately call your gas supplier from a  
neighbor’s phone. Follow the gas supplier’s  
instructions.  
If you cannot reach your gas supplier, call  
the fire department.  
C. Use only your hand to turn the gas control knob.  
Never use tools. If the handle will not turn by  
hand, don’t try to repair it, call a qualified service  
technician. Force or attempted repair may result  
in a fire or explosion.  
WHAT TO DO IF YOU SM ELL GAS  
D. Do not use this appliance if any part has been  
under water. Immediately call a qualified  
Do not try to light any appliance.  
Do not touch any electric switch; do  
not use any phone in your building.  
service technician to inspect the appliance and  
to replace any part of the control system and  
any gas control which has been under water.  
OPERATING INSTRUCTIONS  
1. STOP! Read the safety information  
8. Turn gas shutoff valve clockwise to “ON”.  
Handle will be parallel to pipe.  
above on this label.  
2. Set the thermostat to lowest setting.  
9. Install top cover.  
3. Turn off all electric power to the  
10. Turn on all electric power to appliance.  
11. Set thermostat to desired setting.  
appliance.  
4. This appliance is equipped with an  
ignition device which automatically lights  
the burner. Do not try to light the burner  
by hand.  
12. If the appliance will not operate, follow the  
instructions “To Turn Off Gas ToAppliance” and  
call your service technician or gas supplier.  
5. Remove front door.  
6. Turn gas shutoff valves counterclockwise  
to “OFF”. Handle will be perpendicular to  
pipe. Do not force.  
7. Wait five (5) minutes to clear out any gas.  
If you then smell gas, STOP! Follow “B”  
in the safety information above this label.  
If you don’t smell gas, go to next step.  
TO TURN OFF GAS TO APPLIANCE  
1. Set the thermostat to lowest setting.  
2. Turn off all electric power to the appliance  
if service is to be performed.  
4. Turn gas shut off valves counterclockwise to  
“OFF”. Handle will be perpendicular to pipe.  
Do not force.  
5. Install front door.  
3. Remove front door.  
LBL20053 REVA  
46  
Installation & Operation Manual  
9 Start-up  
(continued)  
Check flame and combustion (continued)  
Set space heating operation  
4. Navigate to the Service Mode Screen from the Status  
Screen by pressing the MAIN button and then the  
SERVICE MODE button.  
Verify space heat circulator mode  
The Space Heating Mode controls the system pump (if  
connected), and both boiler pumps. When the SMART  
TOUCH control receives a space heating call for heat, it turns  
on the system pump. If the boiler is not heating an indirect  
HW (Hot Water) tank, it also turns on the boiler pump. After  
the space heating call for heat ends, the system pump continues  
to run for a short period of time. If the boiler pump was  
running, it continues to run for a short period of time as well.  
5. On the Service Screen place Heat Exchanger 1 into  
operation by selecting Heat Exchanger 1 with the SELECT  
button and turning the heat exchanger on by pressing the  
ON/OFF button (OFF indicates that the heat exchanger  
is off and ON indicates that the heat exchanger should be  
firing).  
6. Insert the probe from a combustion analyzer into the hole These pump delays are factory set to 30 seconds. If different  
left by the removal of the flue temperature sensor.  
delays are desired, the appropriate parameters in the control  
must be changed. See the SYNC Service Manual for a detailed  
explanation of this procedure.  
Note: Heat Exchanger 1 is the top heat exchanger; please  
ensure the probe is in the top flue sensor location.  
Set space heating set point temperature  
7. Once the heat exchanger has modulated up to full fire  
measure the combustion. The values should be in  
the range listed in Table 9A below. CO levels should  
be less than 200 ppm for a properly installed unit.  
If the combustion is not within range reference the  
Troubleshooting Section in the SYNC Service Manual for  
possible causes and corrective actions.  
During normal operation, space heating set point temperatures  
can be adjusted from the Set Points Menu. Press the following  
buttons to navigate to the Set Points Menu from the Status  
Screen:  
>>  
>>  
Table 9A Flue Products Chart  
1. To change a set point, press the SELECT button next to the  
user set point parameter.  
Natural Gas  
Propane  
2. The first time the user set point parameter is accessed, you  
will be required to enter the user password. The user  
password is 0704.  
CO2 O2  
CO2  
O2  
8.0% - 10% 3.0% - 6.5% 9.0% - 11% 4.1% - 6.9%  
3. Using the keypad, enter the password and then press the  
OK button. If the password is not entered correctly, the  
screen will revert to the Parameter List Screen and you  
will not be able to adjust the set point. If a digit has been  
entered incorrectly, press the left arrow key on the keypad  
to back the digit up. If the password has been entered  
correctly, the Parameter Change Screen will appear. The  
Parameter Change Screen will display the set point being  
changed, the previous setting of the set point, and  
adjustment buttons.  
8. Once the Heat Exchanger 1 analysis is complete, test the  
safety shutoff device by turning the manual shutoff valve  
to the OFF position and ensuring that Heat Exchanger  
1 shuts down and registers an alarm. Open the manual  
shutoff valve, reset the control, and return to Service  
Mode.  
9. Repeat the same procedure for Heat Exchanger 2  
by selecting Heat Exchanger 2 while on the Service  
Mode Screen. Be certain to insert the probe from the  
combustion analyzer into the Heat Exchanger 2 flue  
temperature sensor location.  
4. To adjust the set point, press the + or - buttons to change  
the value being displayed.  
5. Once the set point has been adjusted to the desired  
setting press the APPLY button to change the set point  
and return to the Parameter List Screen.  
10. Turn the main power off to the boiler and replace the  
flue temperature sensor into the flue pipe connection.  
11. Place the boiler back into normal operation.  
You must replace the flue gas temperature  
ƽ WARNING  
sensor to prevent flue gas spillage into  
the room. Failure to comply could  
result in severe personal injury, death, or  
substantial property damage.  
47  
Installation & Operation Manual  
9 Start-up  
6. If no other changes are necessary, press the BACK button 2. Using the keypad, adjust the date and time by working  
to return to the Parameter List Screen.  
from left to right. If a digit has been entered incorrectly,  
press the left arrow key on the keypad to back the digit  
up. If no change is necessary, press the BACK button to  
return to the Parameter List Screen. Once the correct  
date and time have been entered press the OK button on  
the display to program the date and time into memory  
and return to the Parameter List Screen.  
7. Once all the necessary adjustments have been made,  
press the BACK button to return to the Setup Screen.  
8. Press the SAVE button to program all changes made to  
the set points and return to the Status Screen. Leaving  
the Setup Screen without pressing the SAVE button will  
erase the changes made to the set points and change  
them back to their previous settings.  
The internal clock does not adjust for  
NOTICE  
Daylight Savings Time and therefore, will  
Note: The SAVE button must be pressed to ensure proper  
programming of the controls. Failure to press the SAVE  
button will require all changes to be reprogrammed.  
require a manual adjustment.  
Configuration of the cascade  
Set Hot Water Generator (HW) operation  
Verify HW circulator mode  
When installed in a Cascade system, the individual controls  
must be programmed for cascade operation. To program the  
cascade parameters, access the Cascade Menu found in the  
Setup Menu by pressing the following buttons:  
The HW Mode is programmed to heat an indirect hot water  
tank. When a tank thermostat or a tank sensor initiates a  
call for heat, the SMART TOUCH control will turn on the  
HW pumps and turn off the boiler pumps (if running). If  
the system pump is running, it will remain on. When the  
HW call for heat ends, and there is no space heating call for  
heat, the HW pumps will continue to run for a period of  
time. This pump delay is set at the factory to 30 seconds. If a  
shorter or longer delay is desired, the appropriate parameter  
in the control must be changed. See the SYNC Service  
Manual for a detailed explanation of this procedure. If there  
is an active space heating call for heat, then the boiler pumps  
will be turned on and the HW pumps will be turned off.  
>>  
>>  
Note: The CASCADE button on the Main Menu will only  
display the current status of the cascade.  
1. Once in the Cascade Setup Menu select the appropriate  
parameter by pressing the SELECT button.  
2. The first time the cascade setup parameters are accessed,  
you will be required to enter the service password. Enter the  
service password as described in the SYNC Service Manual.  
Set HW target temperature  
3. Once the password has been entered correctly, the  
Parameter Change Screen will appear. The Parameter  
Change Screen will display the parameter being changed,  
the previous setting of the parameter, and adjustment  
buttons.  
When in the HW Mode, the control will modulate to  
maintain the outlet temperature to a set point. This set point  
is set at the factory to 180°F. If a different set point is desired,  
the appropriate parameter in the control must be changed.  
See the SYNC Service manual for a detailed explanation of  
this procedure.  
4. To adjust the parameter, press the + or - buttons to change  
the value being displayed.  
Set clock  
5. Make the correct adjustments and then press the APPLY  
button.  
To program the clock, access the night setback parameter by  
pressing the following buttons:  
6. Once all the parameters have been adjusted press the BACK  
button. This will return you to the Setup Menu.  
>>  
>>  
7. Press the SAVE button to program all controls.  
The SMART TOUCH control has a built-in clock that it uses  
for its night setback feature and for logging events. This  
clock must be set when the boiler is installed, and anytime the  
boiler has been powered off for more than one month. Use  
the following procedure to set the clock:  
Note: The SAVE button must be pressed to ensure proper  
programming of the controls. Failure to press the SAVE button  
will require all changes to be reprogrammed.  
1. To set the clock, press the SELECT button in the upper  
right-hand corner of the display. The date and time are  
displayed as “Day dd/mm/yy hh:mm”. Day = day of the  
week (1 = Monday, 2 = Tuesday, etc.), dd = date, mm =  
month, yy = year, hh = hour, mm = minutes (24 hour  
time; 2:30PM = 14:30).  
48  
Installation & Operation Manual  
10 Operating information  
General  
HW priority  
The SMART TOUCH control module allows connection of a  
HW thermostat to the low voltage connection board. When the  
HW thermostat calls for heat, the control modules activate the  
HW pumps, shuts down the boiler pumps, and immediately  
sets the target outlet water temperature to 180°F (82.2°C).  
This provides automatic priority heat allocation to the HW  
Generator for maximum response and recovery. The HW  
pumps continue for 30 seconds after the heating cycle to deliver  
the most possible heat.  
How the boiler operates  
The SYNC uses advanced stainless steel heat exchangers  
and electronic control modules that allow fully condensing  
operation. The blowers pull in air and push flue products out  
of the boiler through the heat exchangers and flue piping. The  
control modules regulate blower speed to control the boiler  
firing rate. The gas valve senses the amount of air flowing  
into the boiler and allows only the right amount of gas to flow.  
Controlling sensor  
How the control modules operate  
The control module is programmed to use the outlet sensor  
as the control sensor by default. If a system supply sensor  
is connected, the control automatically uses it as the control  
sensor.  
The SYNC boiler is equipped with two (2) SMART  
TOUCH control modules. The control modules work in  
synchronization to meet the heat demand of the system.  
The SMART TOUCH control modules receive input from  
boiler sensors and external inputs. The control modules  
activate and control the blowers and gas valves to regulate  
heat input and switches the boiler, Hot Water Generator  
(HW), and system pumps on and off as needed. The user  
programs the control modules to meet system needs by  
adjusting control parameters. These parameters set operating  
temperatures and boiler operating modes. Boiler operation is  
based on system temperature.  
Anti-cycling  
After a space heating demand has been satisfied, the control will  
delay the next space heating call for a set time period (time is  
adjustable by the installer). The time delay will be bypassed if  
the inlet water temperature drops too far during the delay.  
Boiler, system, and HW pump control  
When a space heating call for heat starts and no HW call is on,  
the system and boiler pumps are turned on. As long as the space  
heating call for heat is on, the system pump will remain on. If  
a HW call for heat is on, the boiler pumps will wait to turn  
on until just before the HW pumps turn off. After the space  
heating call for heat ends, both pumps will run for an additional  
period of time.  
Control inputs and outputs  
Room thermostat / zone control  
This input tells the boiler to provide water for space heating.  
Hot Water Generator (HW) tank thermostat  
When a HW call for heat starts, the HW pumps are turned on.  
If a space heating call for heat was on, the boiler pumps will turn  
off a few seconds after the HW pumps turn on.  
This input tells the boiler to provide water for heating an  
indirect HW tank.  
Louver  
0 - 10V input (set point or power)  
A dry contact is provided to open and close louvers whenever  
the SYNC boiler requires combustion air from inside the room.  
Connect the Louver End Switch to the Louver Proving Switch  
input on the Low Voltage Connection Board.  
The SYNC can be controlled by a Building Management  
System (BMS) using a 0 - 10 VDC signal. The control can be  
configured by the installer to use this signal to either control  
set point or firing rate.  
Temperature control  
Modulation  
The SYNC is capable of modulating its firing rate from a  
minimum of 10% to a maximum of 100%. The firing rate is  
dictated by the call for heat (i.e., space heating or hot water  
generation), the heating load, and various other temperature  
limitations.  
49  
Installation & Operation Manual  
10 Operating information  
Gradient limiting  
Protection features  
Ifduringoperationoftheboilertheoutletwatertemperature  
is rising too quickly, the control will reduce the firing rate  
to its lowest setting.  
Outlettemperature, fluetemperature, andtemperature  
rise limiting  
The outlet temperature is monitored by the boiler outlet  
temperature sensor. When the outlet temperature exceeds  
185°F (85°C), the unit will reduce the fan speed. If the outlet  
water temperature exceeds 195°F (90°C) the control will shut  
the unit down until it cools off.  
Outdoor air reset  
If an outdoor air sensor is connected, the control module  
will calculate the set point based on the programmed reset  
curve. The installer can change the slope of the reset curve  
by several adjustable parameters. The user can limit the  
maximum set point for the system using the space heating  
set point.  
The control module monitors the flue temperature by a sensor  
located in the flue exhaust. If the flue temperature exceeds  
215°F (102°C) the control will reduce the maximum fan speed.  
If the flue temperature exceeds 240°F (115°C) the control will  
shut the unit down. The unit will restart automatically once  
the flue temperature drops 25°F (14°C) and the minimum off  
time has expired.  
Boost function  
If outdoor air reset is active, and a space heating demand  
has been active continuously for a set period of time  
(time adjustable by installer) and there has been no HW  
demands, the control will increase the set point by a fixed  
number of degrees (adjustable by installer). This process  
will continue until the space heating demand ends, the set  
point reaches the programmed set point or a maximum of  
20 increases has occurred. Once the system heat demand  
is satisfied, the set point will revert to the value determined  
by the reset curve.  
The control monitors the temperature difference between  
the inlet and the outlet sensor. If this difference exceeds  
55°F (31°C) the control will reduce the fan speed. If the  
temperature difference exceeds 60°F (33°C) the control will  
shut the unit down. The unit will restart automatically once  
the temperature difference has dropped below 55°F (31°C) and  
the minimum off time has expired.  
Freeze protection  
Night setback  
DO NOT install the boiler in a room likely to freeze.  
The controller may be programmed to reduce the space  
heating set point during a certain time each day. A start  
and stop time can be programmed for each day of the week.  
The following integral feature of the SMART TOUCH control  
module provides some protection for the boiler only -- not for  
the system.  
Flame current support  
The SMART TOUCH control module provides  
freeze-up protection as follows when the boiler  
water temperature drops below 45°F (7°C):  
Below 45°F (7°C), the boiler and system pumps  
operate constantly.  
To prevent nuisance shutdowns when the boiler is firing  
at minimum rates, the control will increase the firing rate  
when the flame signal drops too low.  
Below 37°F (3°C), the boiler turns on.  
Boiler and pumps turn off if boiler water  
temperature rises above 45°F (7°C).  
This feature of the SMART TOUCH control  
ƽ CAUTION  
module does not eliminate the possibility  
of freezing. The installation must still  
use recognized design, installation and  
maintenance practice to prevent freeze  
potential for the boiler and system.  
50  
Installation & Operation Manual  
10 Operating information  
(continued)  
Monitor external limits  
High limit operations  
Connections are provided on the connection board for  
external limits such as flow switch and a louver proving  
switch. The SMART TOUCH control will shut off the  
burner and inhibit relighting whenever any of these external  
limits open.  
When outlet temperature exceeds 200°F (93.3°C), high limit  
action occurs. The boiler shuts down until the outlet water  
cools down.  
Low water cutoff protection  
1. A low water cutoff device with test and reset functionality is  
provided in the boiler as standard equipment.  
Run-time and alarm outputs  
The boiler provides dry contacts for indicating when the  
boiler is running, and when it is unable to operate.  
Flow sensing device  
1. The SMART TOUCH control module uses temperature  
sensing of both supply and return temperatures of the  
heat exchanger. If the flow rate is too low or the outlet  
temperatures too high, the control module modulates  
down and will shut the boiler off. This ensures boiler  
shutdown in the event of low flow conditions.  
Run-time and cycle counting  
The control uses two timers to monitor the total hours of  
burner operation. One timer monitors the time the boiler  
is firing under 50% of rate. The other timer monitors the  
time the boiler is firing over 50% rate.  
If a mechanical flow switch is required to  
NOTICE  
The control uses four (4) ignition counters to monitor  
the amount of boiler cycles. The first counter counts all  
ignitions of the control. The second counter counts only  
ignition attempts that have failed. The third and fourth  
counters are the same as the first and second respectively,  
but can be reset by the installer.  
meet local code requirements the SYNC  
boiler can be equipped with field supplied  
switches on each inlet. Please reference page  
39 of this manual for more information.  
Outdoor reset operation, if used  
Service reminder  
Target temperature with outdoor reset  
The control can be programmed for service reminder  
notification. This notification will become active when  
either a set time frame has expired, or a set amount of  
running hours or cycles has expired (all adjustable by the  
installer). The display will alternate the standard text on  
the display screen with Service Due every 5 seconds. The  
service reminder notification can be reset by the installer.  
This feature improves the system’s efficiency as the outdoor  
temperature warms up.  
See the SYNC Service Manual to change the settings.  
Reset curve  
The reset curve looks at outdoor air temperature and adjusts  
the set point.  
Error logging  
The control will hold in memory the last 10 error codes as  
well as the last 10 turn-off functions. The date and time of  
the occurrence will be recorded as well. Only the 10 most  
current occurrences will be held in memory.  
Cascade  
When multiple boilers are installed, they can be wired together  
in a cascade sequence. A maximum of eight boilers can be  
controlled from a single control. In this application one boiler  
would be designated as the Leader control and all others would  
be designated as Member controls.  
Boiler temperature regulation  
Operating temperature (target)  
Once the Leader boiler receives a call for heat from the Enable  
input or 0 - 10 VDC input, the control will determine what  
the set point will be. If outdoor air reset is desired, connect  
the outdoor air sensor to the terminals on the Low Voltage  
Connection Board on the Leader boiler. The set point will be  
calculated based on the programmed reset curve parameters.  
See the SYNC Service Manual to program the reset curve. If  
outdoor air reset is not desired, do not connect the outdoor air  
sensor. A fixed temperature set point can be programmed into  
the control.  
The SMART TOUCH control module senses water  
temperature and regulates boiler firing and firing rate to  
achieve a target temperature. The target temperature can  
be set between 70°F (21°C) and 190°F (88°C).  
Target temperature is fixed when the outdoor  
sensor is not installed.  
Target temperature is calculated as described below  
under “Outdoor Reset Operation” and “Target  
Temperature Boost” when the outdoor sensor is  
connected.  
51  
Installation & Operation Manual  
10 Operating information  
If the water temperature at the system supply sensor is less  
than the set point + the turn-off offset - the off-on differential,  
then the control will initiate a call for heat on the Cascade (see  
the SYNC Service Manual for an explanation of the offset and  
differential). The Leader will energize the lead boiler on the  
Cascade. For a new startup this will be the Leader boiler.  
HW operation with cascade  
For HW operation any boiler(s) in the Cascade can be selected  
to provide heat for a HW call. Select a boiler to be designated  
as the HW boiler. Connect the HW thermostat or sensor to  
the terminals on the Low Voltage Connection Board marked  
for the HW Thermostat or sensor. When the boiler receives  
a HW call, the Leader control will take that boiler out of the  
Cascade sequence. If another boiler is available, the Leader  
will start it up to take its place.  
The boiler will fire at its ignition speed and will then modulate  
its firing rate to maintain the set point. If the first boiler  
reaches 100% of its firing rate, the Leader will calculate at  
what point the second boiler could fire at 10% of its firing  
rate. At this point, the Leader will fire the second boiler on the  
Cascade. For a new startup, this would be the first Member  
boiler. The boiler will fire at its ignition speed and will then  
modulate its firing rate to maintain the set point.  
The HW boiler will adjust its set point to the programmed  
HW set point and will adjust its firing rate to maintain this.  
Once the HW call has been satisfied, the Leader control will  
place that boiler back into the Cascade sequence.  
Night Setback operation with cascade  
If the set point still cannot be met, the Leader will continue  
firing more Members until either the heat demand is met  
or all boilers on the Cascade are firing. As the heat demand  
decreases, the last boiler on will modulate down to 10% of its  
firing rate. Once the demand for that boiler is zero, it will shut  
down. As the heat demand decreases further, the second to last  
boiler will modulate down and shut off. This will continue  
until the demand is satisfied and all boilers are shut off.  
Night Setback operation of the boilers within the Cascade is  
available. Programming of the Night Setback will be done  
through the Leader boiler. Refer to the SYNC Service Manual  
for information regarding Night Setback.  
Sequence of the cascade  
To equalize the run time of all boilers on the Cascade, the  
firing sequence will automatically be changed at set intervals.  
For the first 24 hours after initializing the Cascade, the  
sequence will be changed every hour. After that the sequence  
will be changed once every 24 hours. The switching on/off  
sequence will be as follows:  
DAY  
Day 1  
SWITCHING ON SEQUENCE  
L-M1-M2-M3-M4-M5-M6-M7  
M2-M3-M4-M5-M6-M7-L-M1  
Day 1 + 1 hour  
Day 1 + 2 hours  
M4-M5-M6-M7-L-M1-M2-M3  
52  
Installation & Operation Manual  
10 Operating information  
(continued)  
Sequence of operation  
Note: This unit is equipped with two (2) independent, but synchronized combustion systems. The Heat Exchanger 1 combustion  
system will fire first. If the demand cannot be met by one (1) combustion system the same sequence of operation will be followed  
to bring the Heat Exchanger 2 combustion system online.  
Upon a call for heat, the control turns on the appropriate pumps (system and boiler pumps for a space heating call,  
HW pump relay output for a HW call).  
1.  
The control confirms that the low water cutoff and flow switch (optional) contacts are closed.  
2.  
The control starts the blower and closes the louver contacts to begin the Pre-Purge cycle.  
3.  
The control confirms that the blower comes up to the desired speed, the flap valve opens, and the air pressure switch,  
gas pressure switch (optional), louver proving switch (optional), and blocked drain switch contacts close.  
4.  
Once the Pre-Purge cycle is complete, the control lowers the blower speed, initiates sparking of the ignition electrode,  
and opens the gas valve.  
5.  
After a short wait, the control stops sparking and checks for the presence of flame current through the spark and  
flame sense electrodes.  
6.  
If the control does not detect flame current, the control will lockout indefinitely, until the RESET button on the touch  
screen LCD is pressed.  
7.  
If the control detects flame current, the control will hold the blower speed constant for a few seconds to allow the  
flame to stabilize, then begin modulating the firing rate in order to maintain the controlling sensor to the desired set  
point temperature.  
8.  
If the current call for heat is for space heating and a HW call for heat becomes active, the control will turn on the HW  
pump relay output, then turn off the boiler pumps. It will then modulate the blower speed in order to maintain the  
outlet temperature to the desired HW outlet set point temperature.  
9.  
If the first heat exchanger in the boiler is unable to maintain the desired set point temperature, the second heat  
exchanger in the boiler will be started, using much of the same sequences as described above. Once both heat  
exchangers are firing, the controls will work in synchronization to maintain the desired set point temperature. If  
the heat load should decrease sufficiently, the second heat exchanger will be shut down, much like the sequences  
described below.  
10.  
Once both the space heating and HW calls for heat are satisified, the control will turn off the gas valve and begin the  
Post-Purge cycle. Any pumps that are running will begin their respective Pump Delay cycles.  
11.  
At the end of the Post-Purge cycle, the louver contacts will open.  
12.  
The control verifies that the blower stops running and the flap valve closes.  
13.  
At the end of the Pump Delay cycle(s), the pump(s) will be turned off.  
14.  
53  
Installation & Operation Manual  
10 Operating information  
SYNC control module  
The Status Screen displays boiler status, Cascade addresses, outlet water temperature, inlet water temperature, system  
temperature, and tank temperature.  
The boiler can be changed by pressing the ON/OFF button. The Details Screen and Main Menu Screen can be accessed by  
pressing the appropriate button.  
Figure 10-1 Status Screen  
When the ON/OFF switch is turned to the ON position,  
the first screen visible on the LCD display will be the Status  
Screen. This screen displays the current status of the SYNC  
boiler. The following items can be viewed or interacted with  
on the Status Screen:  
• SH BMS - The boiler has received a call for heat from  
a 0-10 VDC BMS control.  
• Service Set Point Met - While in Service Mode, the  
water temperature at either the outlet sensor or the  
system sensor has exceeded 185°F.  
• HW Outlet Set Point Met  
temperature has exceeded the HW Generator Set Point  
parameter.  
-
The outlet water  
On/Off button - Pressing this button allows the boiler to be  
placed in either Manual Shutdown Mode or Standby Mode.  
• OA Shutdown - The outside air temperature has  
exceeded the Outdoor Shutdown Set Point parameter.  
• SH Set Point Met - The water temperature as measured  
by the system supply sensor has exceeded the User Set  
Point parameter or if the optional Outdoor Air Sensor  
was used, the calculated set point based on the  
Outdoor Reset parameters.  
• Anti-Cycle Delay - The boiler has satisfied a system  
heat call, but has received another system heat call  
before the anti-cycling time parameter has elapsed.  
Boiler Status - This line shows the current operating status of  
the SYNC boiler. Displayed items are as follows:  
• Manual Shutdown  
-
The boiler will not  
respond to either a system call or a hot water  
generation call.  
• Standby - The boiler has not received a system call  
or hot water generation call.  
• SH Call for Heat - The boiler has received a system heat  
call.  
• SH Pump Delay - The boiler has satisfied a system heat  
call and the boiler pumps are running for a fixed  
time to remove any residual heat.  
• Cascade ComError  
-
A
communication error has  
occurred between the Control Module 1 and Control  
Module 2 or between the Leader and Member boilers.  
• HW Storage - The boiler has received a hot water  
generation call.  
• HW Pump Delay - The boiler has satisfied a hot water  
generation call and the hot water generator pumps  
are running for a fixed time to remove any residual  
heat.  
54  
Installation & Operation Manual  
10 Operating information  
(continued)  
Hot Water Tank Temperature - This is the temperature as  
Boiler Configuration - This line shows the current  
measured by the tank sensor in the hot water storage tank.  
configuration of the two control modules inside the unit.  
Time - The time is displayed in the upper right-hand corner of  
the display. It is displayed in 24 hour format. Reference the  
SYNC Service Manual for Night Setback parameters and more  
information regarding adjusting the date and time.  
Outlet Water Temperature - This is a calculated temperature  
based on the readings of the outlet temperatures of the two  
(2) heat exchangers.  
System Water Temperature - This is the water temperature  
as measured by the system supply sensor located in the  
downstream piping.  
Details button - Pressing this button brings up the Details  
Screen. This screen shows the status of the various safeties,  
inputs, and outputs to each control module. Reference the  
Details Screen section in the SYNC Service Manual for more  
information regarding this screen.  
Inlet Water Temperature - This is a calculated temperature  
based on the inlet temperature readings from the two (2) heat  
exchangers.  
Main button - Pressing this button brings up the Main Screen.  
From this screen navigation to eight (8) other screens is  
possible. Reference the Main Screen section on page 56 of this  
manual for more information regarding this screen.  
55  
Installation & Operation Manual  
10 Operating information  
Use the Main Menu Screen (FIG. 10-2) to access the screens necessary to set temperatures, operating conditions, and monitor  
boiler operation.  
The SYNC is equipped with a SMART TOUCH control system. All menu options are accessed by touching the screen with  
your finger or a stylus from a PDA.  
Figure 10-2 Main Menu Screen  
The Main Screen allows navigation to eight (8) additional Navigation to the Main Screen can be accomplished by pressing  
screens which are used to set temperatures, operating the MAIN button at the bottom of the page.  
conditions, and monitor boiler operation. These screens are  
Reference the SYNC Service Manual for more information  
as follows:  
regarding the eight (8) accessible screens.  
• Setup - Allows access to seven (7) other screens for the  
adjustment of the control parameters.  
Time - The time is displayed in the upper right-hand corner  
of the display. It is displayed in 24 hour format. Reference  
• Cascade - Shows the status of multiple boilers connected  
the night setback parameters in the SYNC Servie Manual for  
together in a cascade arrangement.  
information regarding adjusting the date and time.  
• Temps - Shows the temperatures measured by the  
individual sensors connected to the boiler.  
• Burners - Shows the status of the two (2) independent  
burner systems used in the boiler.  
• Building - Shows the information from a Building  
Integration System using Modbus Protocols.  
• Graphs - Allows the selection of items to be graphed on a  
chart.  
Status button - Pressing this button displays the Status Screen.  
This screen shows the current status of the SYNC boiler.  
Reference pages 54 - 55 for more information regarding this  
screen.  
• History - Shows the operating and fault history of the  
two (2) control modules.  
• Service Mode - Allows the installer to control the fan  
speed of the individual control modules for the purposes  
of combustion analysis. Service Mode will override all  
other heat demands, however, all safeties will remain  
intact.  
56  
Installation & Operation Manual  
11 Maintenance  
Maintenance and annual startup  
Table 11A Service and Maintenance Schedules  
Owner maintenance  
(see the SYNC User’s Information Manual for  
instructions)  
Service technician  
(see the following pages for instructions)  
General:  
• Address reported problems, if any  
• Check boiler area  
• Inspect interior; clean and vacuum if  
necessary;  
Daily  
• Check pressure/temperature  
gauge  
• Clean condensate trap and fill with fresh  
water  
• Check for leaks (water, gas, flue,  
condensate)  
• Verify flue and air lines in good condition  
and sealed tight  
• Check vent piping  
• Check air piping  
• Check system water pressure/system  
piping/expansion tank  
• Check control settings  
Monthly  
• Check air and vent termination  
screens  
• Check ignition and flame sense  
electrodes (sand off any deposits; clean  
and reposition)  
• Check relief valve  
• Check wiring and connections  
• Check condensate drain system  
• Check automatic air vents  
• Perform start-up checkout and  
performance verification per Section 9.  
• Flame inspection (stable, uniform)  
• Test low water cutoff  
• Flame signal (at least 10 microamps at  
high fire)  
• Reset button (low water cutoff)  
Every  
6 months  
• Clean the heat exchanger if flue  
temperature is more than 54°F (30°C)  
above return water temperature.  
• Check boiler piping (gas and  
water) for leaks  
• Test low water flow conditions  
(reference the SYNC Service Manual).  
• Operate relief valve  
If combustion or performance  
indicate need:  
• Clean heat exchanger  
End  
of season  
months  
Shut boiler down (unless boiler  
used for domestic hot water)  
• Remove and clean burner using  
compressed air only  
• Clean the blower wheel  
57  
Installation & Operation Manual  
11 Maintenance  
Follow the service and maintenance procedures given throughout this manual and in component literature  
shipped with the boiler. Failure to perform the service and maintenance could result in damage to the boiler  
or system. Failure to follow the directions in this manual and component literature could result in severe  
personal injury, death, or substantial property damage.  
ƽ WARNING  
The boiler should be inspected annually only by a qualified service technician. In addition, the maintenance  
and care of the boiler designated in Table 11A and explained on the following pages must be performed to  
assure maximum boiler efficiency and reliability. Failure to service and maintain the boiler and system could  
result in equipment failure.  
ƽ WARNING  
Electrical shock hazard – Turn off power to the boiler before any service operation on the boiler except as  
noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical shock,  
causing severe personal injury or death.  
ƽ WARNING  
Address reported problems  
Figure 11-1 Condensate Trap  
1. Inspect any problems reported by the owner and correct  
before proceeding.  
2” PVC CAP WITH  
BLOCKED DRAIN SWITCH  
Inspect boiler area  
1. Verify that boiler area is free of any combustible materials,  
gasoline and other flammable vapors and liquids.  
RETAINING  
SCREW  
PVC TEE ASSEMBLY  
(FACTORY SUPPLIED)  
CONDENSATE FROM  
HEAT EXCHANGER  
2. Verify that air intake area is free of any of the contaminants  
listed in Section 1 of this manual. If any of these are  
present in the boiler intake air vicinity, they must be  
removed. If they cannot be removed, reinstall the air and  
vent lines per this manual.  
TO FLOOR  
DRAIN  
Inspect boiler interior  
1. Remove the front access cover and inspect the interior of  
the boiler.  
The condensate trap must be filled with  
water during all times of boiler operation  
to avoid flue gas emission from the  
condensate drain line. Failure to fill the  
trap could result in severe personal injury  
or death.  
2. Vacuum any sediment from inside the boiler and  
components. Remove any obstructions.  
ƽ WARNING  
Clean condensate trap  
1. Inspect the condensate drain line, condensate PVC  
fittings, and condensate trap.  
Check all piping for leaks  
2. Remove the PVC cap retaining screw from the PVC cap  
(FIG. 11-1).  
Eliminate all system or boiler leaks.  
ƽ WARNING  
Continual fresh makeup water will  
reduce boiler life. Minerals can build  
up in sections, reducing heat transfer,  
overheating heat exchanger, and causing  
heat exchanger failure. Leaking water may  
also cause severe property damage.  
3. Remove the 2 inch PVC cap with the switch located at the  
top of the trap (FIG. 11-1).  
4. Remove any sediment in the trap.  
5. Fill with fresh water until the water begins to pour out of  
the drain.  
1. Inspect all water and gas piping and verify to be leak free.  
2. Look for signs of leaking lines and correct any problems  
found.  
6. Replace the cap. Press the cap onto the trap until the cap  
makes contact with the drain.  
3. Check gas line using the procedure found in Section 6  
7. Replace the retaining screw.  
- Gas Connections.  
58  
Installation & Operation Manual  
11 Maintenance  
(continued)  
Safety relief valves should be re-inspected  
AT LEAST ONCE EVERY THREE YEARS,  
by a licensed plumbing contractor or  
authorized inspection agency, to ensure  
that the product has not been affected by  
corrosive water conditions and to ensure  
that the valve and discharge line have not  
been altered or tampered with illegally.  
Certain naturally occurring conditions  
may corrode the valve or its components  
over time, rendering the valve inoperative.  
Such conditions are not detectable unless  
the valve and its components are physically  
removed and inspected. This inspection  
must only be conducted by a plumbing  
contractor or authorized inspection  
agency – not by the owner. Failure to  
re-inspect the boiler relief valve as directed  
could result in unsafe pressure buildup,  
which can result in severe personal injury,  
death, or substantial property damage.  
Flue vent system and air piping  
ƽ WARNING  
1. Visually inspect the entire flue gas venting system and air  
piping for blockage, deterioration or leakage. Repair any  
joints that show signs of leakage. Verify that air inlet pipe  
is connected and properly sealed.  
2. Verify that boiler vent discharge and air intake are clean  
and free of obstructions.  
Failure to inspect for the above conditions  
and have them repaired can result in  
severe personal injury or death.  
ƽ WARNING  
Check water system  
1. Verify all system components are correctly installed and  
operational.  
2. Check the cold fill pressure for the system. Verify it is  
correct (must be a minimum of 12 psi (82.7 kPa)).  
3. Watch the system pressure as the boiler heats up (during  
testing) to ensure pressure does not rise too high.  
Excessive pressure rise indicates expansion tank sizing or  
performance problem.  
Following installation, the valve lever  
must be operated AT LEAST ONCE  
A YEAR to ensure that waterways are  
ƽ WARNING  
clear.  
Certain naturally occurring  
4. Inspect automatic air vents and air separators. Remove  
air vent caps and briefly press push valve to flush vent.  
Replace caps. Make sure vents do not leak. Replace any  
leaking vents.  
mineral deposits may adhere to the valve,  
rendering it inoperative. When manually  
operating the lever, water will discharge  
and precautions must be taken to avoid  
contact with hot water and to avoid water  
damage. Before operating lever, check  
to see that a discharge line is connected  
to this valve directing the flow of hot  
water from the valve to a proper place of  
disposal. Otherwise severe personal injury  
may result. If no water flows, valve is  
inoperative. Shut down the boiler until a  
new relief valve has been installed.  
Check expansion tank  
1. Expansion tanks provide space for water to move in  
and out as the heating system water expands due to  
temperature increase or contracts as the water cools.  
Tanks may be open, closed or diaphragm or bladder  
type. See Section 5 - Hydronic Piping for suggested best  
location of expansion tanks and air eliminators.  
2. After following the above warning directions, if the relief  
valve weeps or will not seat properly, replace the relief  
valve. Ensure that the reason for relief valve weeping is  
the valve and not over-pressurization of the system due  
to expansion tank waterlogging or undersizing.  
Check boiler relief valve  
1. Inspect the relief valve and lift the lever to verify flow.  
Before operating any relief valve, ensure that it is piped  
with its discharge in a safe area to avoid severe scald  
potential. Read Section 5 - Hydronic Piping before  
proceeding further.  
59  
Installation & Operation Manual  
11 Maintenance  
Inspect ignition and flame Check burner flame  
sense electrodes  
1. Inspect flame through observation window.  
1. Remove the ignition and flame sense electrodes  
from the boiler heat exchanger access covers.  
2. If the flame is unsatisfactory at either high fire or low fire,  
turn off boiler and allow boiler to cool down. Remove the  
burners and clean them thoroughly using a vacuum cleaner or  
compressed air. Do not use compressed air to clean burners if  
performed inside a building.  
2. Remove any deposits accumulated on the ignition/  
flame sense electrode using sandpaper. If the  
electrodes cannot be cleaned satisfactorily, replace  
with new ones.  
3. Remove the burners, reference FIG. 11-2.  
4. When replacing the burners, ensure gaskets are in good condition  
and positioned correctly (FIG. 11-2).  
3. Replace ignition/flame sense electrodes, making  
sure the gaskets are in good condition and correctly  
positioned.  
Figure 11-2 Burner Assembly  
DOOR FIBER  
Check ignition ground wiring  
BURNER DOOR  
1. Inspect boiler ground wire from the heat exchanger  
access cover to ground terminal strip.  
BURNER DOOR  
HEX NUT (6)  
BURNER  
2. Verify all wiring is in good condition and securely  
attached.  
AIR/GAS GASKET  
IGNITER GASKET  
FLAPPER VALVE  
SCREW (5X)  
3. Check ground continuity of wiring using continuity  
meter.  
IGNITER  
FLAME SENSE  
GASKET  
IGNITER SCREW (2X)  
FLAPPER VALVE  
FLAME SENSE  
FLAME SENSE  
SCREW (2X)  
4. Replace ground wires if ground continuity is not  
satisfactory.  
Check all boiler wiring  
Check flame signal  
1. Inspect all boiler wiring, making sure wires are in  
good condition and securely attached.  
1. At high fire the flame signal shown on the display should be at  
least 10 microamps.  
Check control settings  
2. A lower flame signal may indicate a fouled or damaged flame  
sense electrode. If cleaning the flame sense electrode does not  
improve, ground wiring is in good condition, and ground  
continuity is satisfactory, replace the flame sense electrode.  
1. Set the control module display to Parameter Mode  
and check all settings. See Section 1 of the SYNC  
Service Manual. Adjust settings if necessary.  
See Section 1 of the SYNC Service Manual for  
adjustment procedures.  
3. See Section 3 - Troubleshooting in the SYNC Service Manual for  
other procedures to deal with low flame signal.  
2. Check settings of external limit controls (if any) and  
adjust if necessary.  
Review with owner  
1. Review the SYNC User’s Information Manual with the owner.  
Perform start-up and checks  
2. Emphasize the need to perform the maintenance schedule  
specified in the SYNC User’s Information Manual (and in this  
manual as well).  
1. Start boiler and perform checks and tests specified  
in Section 9 - Start-up.  
2. Verify cold fill pressure is correct and that operating  
pressure does not go too high.  
3. Remind the owner of the need to call a licensed contractor  
should the boiler or system exhibit any unusual behavior.  
4. Remind the owner to follow the proper shutdown procedure  
and to schedule an annual start-up at the beginning of the next  
heating season.  
60  
Installation & Operation Manual  
11 Maintenance  
(continued)  
Cleaning boiler heat exchanger  
Table 11B Heat Exchanger Cleaning Kits  
For recommended materials; including brush, appropriate  
extension(s), refractory cover, and detailed instructions see  
Table 11B - Heat Exchanger Cleaning Kits.  
Model  
Kit  
Part  
Component  
Description  
Number Number Number  
1. Shut down boiler:  
MSC20083* Nylon 4" Wheel Brush*  
SB 1.0 - 1.5 KIT30064 MSC20085 1/4" x 12" Drill Extension  
MSC20086 1/4" x 24" Drill Extension  
• Follow the “To Turn Off Gas to Appliance” instructions  
for the boiler in Section 9 - Startup.  
• Do not drain the boiler unless it will be exposed to  
freezing temperatures. If using freeze prevention fluid  
in system, do not drain.  
* Do NOT use a metal brush. Only use  
the kit provided brush or an equivalent  
replacement nylon brush.  
2. Allow time for the boiler to cool to room temperature if it  
has been firing.  
ƽ CAUTION  
3. Remove the nuts securing the heat exchanger access cover  
to the heat exchanger and set aside.  
Figure 11-3 Rope Gasket - Heat Exchanger Door  
4. Remove the heat exchanger access cover, burner, and  
gas/air arm assembly.  
ROPE GASKET  
The boiler contains ceramic fiber materials.  
ƽ WARNING  
Use care when handling these materials  
per instructions on page 62 of this manual.  
Failure to comply could result in severe  
personal injury.  
5. Remove the condensate hose from the heat exchanger end.  
Connect a field supplied 3/4" diameter hose to a drain pan.  
Using field supplied means, cover the refractory in the back  
of the combustion chamber of the heat exchanger.  
CAUTION: IF GASKET IS DAMAGED  
DO NOT REUSE, THE HEAT EXCHANGER DOOR  
MUST BE REPLACED.  
Rope gasket is intended for sealing combustion  
(FIG. 11-3). If damaged DO NOT reuse, the  
heat exchanger door must be replaced. Consult  
factory for replacement heat exchanger door  
(kit WTR3086).  
NOTICE  
6. Use a vacuum cleaner to remove any accumulation on the  
boiler heating surfaces. Do not use any solvent.  
7. Brush the heat exchanger while dry using a nylon bristle  
brush. Caution: DO NOT use a metal brush. Re-vacuum  
the heat exchanger.  
8. Finish cleaning using a clean cloth dampened with warm  
water. Rinse out debris with a low pressure water supply.  
9. Allow the heat exchanger to thoroughly dry.  
10. Remove the field supplied rear refractory cover from the  
back of the combustion chamber of the heat exchanger and  
reassemble.  
11. Close isolation valves on piping to isolate boiler from  
system. Attach a hose to the boiler drain and flush boiler  
thoroughly with clean water by using purging valves to  
allow water to flow through the water make-up line to the  
boiler.  
12. Perform start-up and check-out procedures in the Check  
Flame and Combustion - Section 9 - Startup on pages 45  
and 47 of this manual.  
13. Replace the access cover and restore boiler to operation.  
61  
Installation & Operation Manual  
11 Maintenance  
Handling ceramic fiber materials  
REMOVAL OF COMBUSTION CHAMBER LINING  
The combustion chamber insulation in this appliance contains ceramic fiber material. Ceramic fibers can  
be converted to cristobalite in very high temperature applications. The International Agency for Research  
on Cancer (IARC) has concluded, “Crystalline silica in the form of quartz or cristobalite from occupational  
sources is carcinogenic to humans (Group 1).” Normal operating temperatures in this appliance are below  
the level to convert ceramic fibers to cristobalite. Abnormal operating conditions would have to be created to  
convert the ceramic fibers in this appliance to cristobalite.  
ƽ WARNING  
The ceramic fiber material used in this appliance is an irritant; when handling or replacing the ceramic  
materials it is advisable that the installer follow these safety guidelines.  
Avoid breathing dust and contact with skin and eyes.  
• Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA  
requirements for cristobalite at the time this document was written. Other types of respirators may  
be needed depending on the job site conditions. Current NIOSH recommendations can be found on  
manufacturers, and phone numbers are also listed on this website.  
• Wear long-sleeved, loose fitting clothing, gloves, and eye protection.  
Apply enough water to the combustion chamber lining to prevent airborne dust.  
Remove the combustion chamber lining from the boiler and place it in a plastic bag for disposal.  
Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer thoroughly.  
NIOSH stated First Aid.  
Eye: Irrigate immediately.  
Breathing: Fresh air.  
62  
Installation & Operation Manual  
12 Diagrams  
Figure 12-1 Ladder Diagram_Part 1  
BOX DEPICTS  
OPTIONAL ITEMS  
LOW VOLTAGE  
120 VAC  
HIGH VOLTAGE  
CONTROL  
MODULE 1  
CONTROL  
MODULE 2  
LOUVER  
RELAY 1  
X8  
X6-8  
X5-7  
X5-4  
X8  
X5-7  
24V  
X5-4  
24V  
LOUVER  
RELAY 2  
FLAP  
VALVE  
AIR PRESSURE  
SWITCH  
FLAP  
VALVE  
AIR PRESSURE  
SWITCH  
X5-14  
X5-14  
HI-LIMIT  
HI-LIMIT  
X6-8  
X5-8  
INLET  
SENSOR  
INLET  
SENSOR  
X5-8  
X5-1  
X5-1  
OUTLET  
SENSOR  
OUTLET  
SENSOR  
X5-9  
X5-2  
X5-9  
X5-2  
FLUE  
SENSOR  
FLUE  
SENSOR  
X5-3  
X5-3  
BLOCKED  
DRAIN  
AUTO RESET  
HIGH LIMIT  
AUTO RESET  
HIGH LIMIT  
X5-10  
X5-10  
GAS VALVE  
BLOWER  
GAS VALVE  
X2-2  
X2-1  
X2-2  
GAS VALVE  
RELAY  
GAS VALVE  
RELAY  
X2-1  
1
2
4
5
X5-5  
BLOWER  
1
X5-5  
X5-13  
X5-6  
2
4
5
X5-13  
X5-6  
X5-12  
X5-12  
TR1  
TR1  
X1-7  
X1-7  
FLAME ROD  
FLAME ROD  
SPARK  
ROD  
SPARK  
ROD  
CAUTION HIGH VOLTAGE SPARK LEAD  
CAUTION HIGH VOLTAGE SPARK LEAD  
4
CONTROL  
MODULE 1  
CONTROL  
MODULE 2  
CONNECTION BOARD  
CN3  
X4-3  
CN4-3  
X4  
X4-3  
X4-1  
X4-2  
X4  
CN3-16  
CN3-15  
CN3-14  
CN3-13  
SHIELD  
CN4-1  
CN4-2  
CN4-4  
CN4-6  
X4-1  
X4-2  
X4-4  
X4-6  
CASCADE  
RS485  
X4-4  
SHIELD  
CN3-12  
CN3-11  
CN3-10  
CN3-9  
TANK  
SENSOR  
CN4-5  
X4-5  
X4-8  
X4-7  
X4-9  
OUTDOOR  
SENSOR  
CN4-8  
CN4-7  
CN4-9  
CN3-8  
SYSTEM  
SENSOR  
CN3-7  
CN3-6  
CN3-5  
CN3-4  
CN3-3  
CN3-2  
CN3-1  
-
EXTERNAL  
CONTROL  
CN4-10  
10VDC  
X4-10  
+
SHIELD  
MOD BUS  
RS485  
SHIELD  
MOD BUS  
KIT  
NOTES:  
1. Where possible, switches are shown without utilities (gas, water or  
LADDER DIAGRAM  
LBL20058 REV E  
electricity) connected to the unit. As such, actual switch states may  
vary from those shown on diagrams depending upon whether utilities  
are connected or a fault condition is present.  
2. See wiring diagram for additional notes.  
63  
Installation & Operation Manual  
12 Diagrams  
Figure 12-2 Ladder Diagram_Part 2  
BOX DEPICTS  
OPTIONAL ITEMS  
LOW VOLTAGE  
120 VAC  
JUNCTION BOX  
120VAC  
NEUTRAL  
GROUND  
HIGH VOLTAGE  
TERMINAL STRIP  
120V SUPPLY "L"  
TERMINAL STRIP  
120V SUPPLY "N"  
L1  
JUNCTION BOX  
N
LOUVER  
MOTOR  
CONTROL MODULE 1  
ON / OFF  
SWITCH  
LOUVER  
CONTACTS  
SYSTEM PUMP  
F5  
5A  
RELAY  
X1-2  
BOILER  
PUMP  
HEX  
1
BOILER PUMP  
CONTACTS  
SYSTEM PUMP  
RELAY  
X1-6  
X1-8  
HEX 1  
BOILER PUMP  
RELAY  
BOILER  
PUMP  
HEX  
2
X1-4  
X1-3  
BOILER PUMP  
CONTACTS  
BOILER PUMP  
RELAY  
DHW PUMP  
JUNCTION BOX  
RELAY  
SYSTEM  
PUMP  
SYSTEM  
PUMP  
CONTACTS  
(FIELD SUPPLIED)  
JUNCTION  
BOX  
DHW PUMP  
RELAY  
BLOWER  
F4  
1
2
X1-1  
3.5A  
DHW  
BLOWER  
RELAY  
PUMP  
3
DHW  
PUMP  
CONTACTS  
F3  
1.25A  
(FIELD SUPPLIED)  
X1-5  
X6-8  
120 VAC  
F2  
X5-7  
DHW  
LWCO  
24 VAC  
X6-7  
X6-2  
3.5A  
PUMP  
J3-2  
X6-3  
CONTROL  
MODULE 1  
X6-5  
LOW GAS  
PRESSURE  
SWITCH  
HIGH GAS  
PRESSURE  
SWITCH 1  
CONTROL MODULE 2  
F5  
ON / OFF  
SWITCH  
CONTROL  
MODULE 2  
X6-5  
X1-2  
HIGH GAS  
PRESSURE  
SWITCH 2  
5A  
SYSTEM PUMP  
RELAY  
X1-6  
X1-8  
HEX 2  
BOILER PUMP  
RELAY  
X1-4  
X1-3  
BOILER PUMP  
RELAY  
JUNCTION  
BOX  
DHW PUMP  
RELAY  
BLOWER  
F4  
1
2
X1-1  
X6-8  
CONTROL  
MODULE 1  
3.5A  
BLOWER  
RELAY  
3
F3  
1.25A  
120 VAC  
F2  
X5-7  
X6-10  
X6-9  
24 VAC  
X6-7  
X6-2  
3.5A  
X6-1  
X6-6  
X3-2  
X3-4  
X3-1  
X3-3  
CONNECTION  
BOARD  
CONNECTION  
BOARD  
6
5
CN1-4  
CONTROL  
MODULE 2  
CN1-6  
LOUVER  
PROVING  
CN1-12  
10  
9
CN1-13  
CN1-5  
HEX 1  
FLOW  
SWITCH  
8
7
CN1-6  
CN1-3  
X6-10  
X6-9  
HEX 2  
FLOW SWITCH  
12  
11  
HW  
THERMOSTAT  
13  
14  
4
X3-2  
X3-4  
CN1-11  
CN1-15  
ENABLE  
X3-1  
X3-3  
RUN TIME  
CONTACTS  
3
1
NOTES:  
CN1-10  
CN1-7  
1. Where possible, switches are shown without utilities (gas, water or  
electricity) connected to the unit. As such, actual switch states may  
vary from those shown on diagrams depending upon whether utilities  
are connected or a fault condition is present.  
LWCO  
J3-4  
J3-5  
J3-6  
2. See wiring diagram for additional notes.  
ALARM  
CONTACTS  
2
CN1-8  
J3-3  
TEST SWITCH  
PROBE  
LADDER DIAGRAM  
LBL20046 REV G  
64  
Installation & Operation Manual  
12 Diagrams  
(continued)  
Figure 12-3 Wiring Diagram  
LOW VOLTAGE  
120 VAC  
HIGH VOLTAGE  
X3  
X5  
BOX DEPICTS  
OPTIONAL ITEMS  
CM 1 PC INTERFACE  
JUNCTION  
BOX  
LOUVER  
CONTACTS  
R2  
CONTROL  
MODULE 1  
R1  
LOUVER  
RELAY  
BOARD  
PC INTERFACE  
X8  
BR  
PR  
OR  
OR  
BR  
BR  
X1-4  
K1  
K2  
K3  
CONNECTION BOARD  
BOILER  
BOILER  
2
1
CM 2 PC  
CN3  
X1-2  
CN3-16  
INTERFACE  
SHIELD  
CN4  
CN3-15  
CASCADE  
RS485  
X4  
CN3-14  
CN3-13  
CN3-12  
CN3-11  
CN3-10  
PR  
PR  
SYSTEM  
PUMP  
SHIELD  
GY  
X1-3  
TANK  
SENSOR  
HW PUMP  
RELAY  
GND  
GND  
ON/OFF SWITCH  
BK  
W
X1-6  
X1-5  
L
OUTDOOR  
SENSOR  
120V SUPPLY  
GND  
CN3-9  
CN3-8  
N
GND  
SYSTEM  
SENSOR  
GR  
X1-8  
X1-1  
CN3-7  
CN3-6  
CN3-5  
-
R
W
G
EXTERNAL  
CONTROL  
4 CONDUCTORS  
10VDC  
1
2
3
+
CN1  
BLOWER  
CN3-4  
SHIELD  
1
2
3
4
5
CN3-3  
CN1-10  
LOUVER  
MOD BUS  
RS485  
RELAY  
1
CN3-2  
CN1-2  
MOD BUS  
KIT  
R
X5-5  
X5-13  
CN3-1  
CN1-9  
SHIELD  
T
FLAP  
VALVE  
W
X5-6  
X5-12  
X5-4  
X5-10  
APS  
BK  
OR  
GY  
PK  
BL  
X6-2  
X6-7  
O-TEMP HEX SW  
GY  
AUTO RESET LIMIT  
BL  
GY  
CN1-11  
X6-6  
CN2-14  
CN2-13  
CN2-12  
CN2-11  
CN2-10  
CN2-9  
ENABLE  
X5-7  
PR  
X5-14  
W
W
CN1-3  
CN1-4  
X6-1  
HI-LIMIT  
TANK  
THERMOSTAT  
X5-3  
X5-8  
PK  
BK  
RD  
INLET  
SENSOR  
T
BR  
HEX  
1
CN1-5  
CN1-6  
T
FLOW  
X5-1  
X5-2  
X6-9  
X6-5  
OUTLET  
SENSOR  
SWITCH  
OR  
CN1-13  
CN1-14  
CN1-12  
CN1-15  
CN1-16  
W
Y
FLUE  
SENSOR  
HEX  
2
OR/BK  
CN2-8  
CN2-7  
CN2-6  
CN2-5  
CN2-4  
CN2-3  
CN2-2  
CN2-1  
X5-9  
X6-8  
FLOW  
X6-10  
SWITCH  
PK  
LOUVER  
PROVING  
RD  
RD  
PR  
RD  
BK  
Y
X3-2  
X3-4  
X2-2  
X2-1  
GAS  
VALVE  
RUNTIME  
CONTACTS  
PR  
PR  
CN1-8  
CN1-7  
G
SPARK  
ROD  
PR  
RD  
X3-1  
X3-3  
ALARM  
CONTACTS  
W/RD  
CN1-1  
X1-7  
FLAME ROD  
CN2  
BLOCKED  
DRAIN  
CAUTION HIGH V  
OLTAGE SPARK LEAD  
CONTROL  
MODULE 2  
X8  
BR/W  
GY  
X1-4  
X1-3  
X4  
W
X1-5  
X1-6  
LOW GAS  
HIGH GAS  
BK  
PRESSURE SWITCH  
PRESSURE  
1
GR  
RD  
X1-8  
X1-1  
R
W
G
1
2
3
HIGH GAS  
PRESSURE  
BLOWER  
2
1
2
3
4
5
X6-5  
LOUVER  
RELAY  
RD  
T/BK  
W
2
X5-5  
X5-13  
BR  
X6-9  
X5-6  
X5-12  
OR/BK  
FLAP VALVE  
APS  
TEST  
SWITCH  
OR/BK  
X6-10  
BK  
LOW  
J3-1  
J3-2  
J3-3  
J3-4  
J3-5  
J3-6  
PROBE  
OR/BK  
GR/BK  
WATER  
CUTOFF  
BOARD  
BK  
X5-4  
X5-10  
O-TEMP HEX SW  
AUTO RESET LIMIT  
BL  
BL/BK  
PR/BK  
X5-7  
RESET  
X5-14  
J2-1  
J2-2  
J2-3  
OR  
HI-LIMIT  
PK  
X5-3  
X5-8  
BK/RD  
INLET  
SENSOR  
RD/BK  
W/BK  
X5-1  
OUTLET  
SENSOR  
X5-2  
X5-9  
FLUE  
SENSOR  
Y/BK  
X6-8  
PR  
BK  
Y
X3-2  
X3-4  
X2-2  
X2-1  
GAS  
VALVE  
RD  
PR  
X3-1  
X3-3  
G
SPARK  
ROD  
RD  
X1-7  
FLAME ROD  
RD/W  
CAUTION HIGH V  
OLTAGE SPARK LEAD  
Notes:  
1. All wiring must be installed  
2. If any original equipment w  
minimum of 105°C. Exception  
in accordance with: local, stat  
e, provincial and national cod  
nce must be replaced, it must  
spark lead and ribbon cables  
e requirements per either N.E.  
C. in USA or C.S.A. in Canad  
same wire gauge (AWG) and  
a.  
ire as supplied with the applia  
s: Replacement high vo ltage  
be replaced with wire having  
rated for a  
must be purchased from the fa  
ctory. Use of a non-approved  
spark lead  
or ribbon cables can lead to ope  
rational problems which could  
result in non-repairable dama  
ge to the integrated controller  
ual components for proper con  
or other components.  
nector block locations when us  
WIRING DIAGRAM  
LBL20045 REV M  
3. Actual connector block locat  
diagrams to troubleshoot unit.  
ions may vary from those sho  
wn on diagrams. Refer to act  
ing  
65  
Notes  
66  
Notes  
67  
Revision Notes: Revision A (ECO #C02428) initial release.  
Revision B (ECO #C03046) reflects the addition of FIG. 5-3 on page 27,  
the addition of a pressure gauge to FIG. 5-6 on page 30, edits made  
to FIG. 7-1 on page 35, edits made to the Low Water Cutoff Protection  
section on page 48 along with the addition of the Flow Sensing Device  
section.  
Revision C (ECO #C03223) reflects edits made to the high altitude  
section on page 6.  
Revision D (ECO #C03735) reflects edits made to the venting section  
removal of B149.2, along with the addition of the hydro and dirt  
separator.  
Revision E (ECO #C04062) reflects changes to the terminology in all  
SYNC manuals and labels from module to heat exchanger (exception:  
control module), along with changing out “dirt separator” for “Y-strainer  
(ECR #R02455), edits made to the ceramic fiber material warning,  
removal of the stabilitor from FIG. 11-2 (C04057), and placing the  
illustrations disclaimer on all the piping drawings (ECR #R02431).  
Revision F (ECO #C04560) reflects the addition of Modbus to the  
manual, new heat exchanger cleaning procedure, schedule 80 as  
acceptable CPVC material (Table 2A) (R02799), and changes made  
to Table 5A.  
Revision G (ECO C07283) reflects the update of FIG. 7-1 on page 38 to  
show current label and wiring connections along with an update to the  
Ladder and Wiring diagrams on pages 64 and 65.  
Revision H (ECO C07679) reflects the update of FIG. 6-1 on page 34 to  
show the gas pressure regulator, ECR 04077 - combustible water pipes  
changed from 1" to a 1/4", addition of the rope gasket notice on page 61  
(R03940) and changes made to Table 2A on page 19.  
Revision I (ECO C07981) reflects the addition of the O-temp switch  
and edits made to LBL20045 (ECR R04243 and C07959 - add O-temp  
switch, changes made to Table 5A on page 31 (ECR R04335) and  
change Module 1 and 2 callouts to HEX 1 and 2 on the label).  
Revision J (ECO C08327) reflects changes made to the temperature  
callouts under Protection Features on page 50 (ECR R04145).  
Revision K (ECO C08407) reflects updates made to LBL20045 (ECR  
R04434) along with changing the water outlet from 2 1/2” NPT to 3”  
NPT (ECR R04003), pages 4, 6, and 31 and updating the O-temp switch  
description on page 4.  
Revision L (ECO #C08689) reflects additional information added to the  
humidity warning on page 7, updates made to LBL20046 Rev F (ECO  
CO8689), the addition of the new Polypropylene Vent material section  
and rearranging the venting section.  
Revision M (ECO C09691) reflects the update of AHRI and ASME logos  
on page 6.  
Revision N (ECO C10594) reflects the update of Wiring and Ladder  
diagrams on pages 64 and 65.  
SYNC-I-O Rev N  
05/12  

PUR Water Purification Products Water Cooler PUR210 User Manual
Plantronics Bluetooth Headset C720 User Manual
Plantronics Bluetooth Headset 925 User Manual
Pioneer TS W1207D2 User Manual
Philips VidQuad Color Video Processors TC8277 User Manual
Orion PARAGON 5360 User Manual
Nikon 1909 User Manual
Lochinvar CREST 15 User Manual
Lanzar Car Audio Car Video System SVHR56 User Manual
Kenwood KDC 4590R User Manual