York Sunline 2000 D3ce User Manual

530.26-TG3YI (1294)  
®
SINGLE PACKAGE  
GAS / ELECTRIC UNITS AND  
SINGLE PACKAGE AIR CONDITIONERS  
D3CE / D3CG 180 & 240  
(WORLD 50 HZ)  
SUNLINE 2000  
DCG  
Shown  
DESCRIPTION  
Sunline 2000 units are highly efficient, convertible rooftops. All  
models have dual refrigerant circuits for efficient part load  
operation. Although the units are primarily designed for curb  
mounting on a roof, they can also be slab-mounted at ground  
level or set on steel beams above a finished roof.  
With horizontal ductwork, it should be mounted on the return  
air duct.  
All supply air blowers are equipped with a belt drive that can  
be adjusted to meet the exact requirements of the job.  
These units are designed and manufactured under ISO 9002  
Quality System Certification.  
All compressors include crankcase heat and internal pressure  
relief. Every refrigerant circuit includes an expansion valve, a  
liquid line filter-drier, a discharge line high pressure switch and  
a suction line with a freezestat and low pressure switch. The  
unit control circuit includes a 75 VAtransformer, a 24-volt circuit  
breaker and a relay board with two compressor lockout circuits,  
a terminal strip for thermostat wiring, plus an additional set of  
pin connectors to simplify the interface of additional field  
controls.  
Cooling only, cooling with gas heat and cooling with  
supplemental electric heat units are available with a wide  
variety of field-installed accessories to make them suitable for  
almost every application.  
All units are self-contained and assembled on full perimeter  
base rails. The base rails have holes in the four corners for  
overhead rigging.  
Every unit is completely piped, wired, charged and tested at  
the factory to simplify the field installation and to provide years  
of dependable operation. Powder paint cabinets provide an  
exceptionally durable finish with the 750 hour salt spray  
process per ASTM-B117 test standard.  
All gas heat models are built with two heating sections for two  
equal stages of capacity control. Each section includes a  
durable heat exchanger with aluminized steel tubes, a  
redundant gas valve, spark ignition, power venting, an ignition  
module for 100% shut-off and all of the safety controls required  
to meet the latest ANSI standards.  
All models are available with three different outdoor air damper  
accessosries:  
Single enthalpy economizer  
Differential enthalpy economizer  
Motorized outdoor air intake damper  
The gas supply piping can be routed into the heating  
compartment through a hole in the base pan of the unit or  
through a knockout in the piping panel on the front of the unit.  
All models (including those with an economizer ) are suitable  
for either downflow or sideflow duct connections. For downflow  
duct, remove the sheet metal panels from the supply and return  
air openings through the base of the unit. For sideflow duct,  
replace the supply and return air panels on the rear of the unit  
with a side duct flange accessory.  
All electric heat models are wired for a single power source and  
include a bank of nickel chromium elements mounted at the  
discharge of the supply air blower to provide a high velocity and  
uniform distribution of air across the heating elements. Every  
element is fully protected against excessive current and  
temperature by fuses and two thermal limit switches.  
A fixed outdoor air intake assembly is shipped in the return air  
compartment of all units. The assembly includes a rain hood  
with a damper that can be set for 10, 15 or 25% outdoor air.  
With bottom duct connections, the intake damper assembly  
should be mounted over the opening in the return air panel.  
The power supply wiring can be routed into the control box  
through a threaded pipe connection in the base pan of the unit  
or through a knockout in the wiring panel on the front of the unit.  
530.26-TG3YI  
® SUNLINE 2000  
(OPTION / ACCESS.) DCE UNITS  
ALUMINIZED STEEL  
THROWAWAY  
D*CG UNITS  
(OPTION / ACCESSORY)  
FEMALE  
MODEL DCG  
(Gas Heating)  
RATINGS  
CAPACITY RATINGS - Cooling / Electric Heating  
Electric Heat4  
Nominal Capacity,  
kW  
Rating1  
Point  
Total Output,  
Mbh / kW  
Total Input,  
kW  
Sensible Output,  
Mbh / kW  
Latent Output,  
Mbh / kW  
Model  
COP2  
EER3  
T1  
T2  
T3  
T1  
T2  
T3  
159 / 46.6  
142 / 41.7  
152 / 44.6  
210 / 61.5  
182 / 53.3  
196 / 57.5  
18.2  
20.0  
16.4  
24.8  
27.1  
22.2  
2.60  
2.10  
2.75  
2.50  
2.00  
2.60  
8.80  
7.15  
9.40  
8.50  
6.75  
8.80  
132 / 38.7  
141 / 41.2  
119 / 34.9  
176 / 51.5  
182 / 53.3  
152 / 44.6  
26.9 / 7.9  
1.6 / 0.5  
33.2 / 9.7  
34.0 / 10.0  
0.0 / 0.0  
D3CE180  
18, 36, 54, 72  
18, 36, 54, 72  
D3CE240  
42.6 / 12.5  
1
2
3
4
T1 = Moderate Climates, T2 = Hot Climates, T3 = Cool Climates.  
COP = Coefficient of Performance - total output kW divided by the total input kW.  
EER = Energy Efficiency Ratio - total output Mbh divided by the total input kW.  
Heaters available as factory-installed options or field-installed accessories - all with single point power supply.  
CAPACITY RATINGS - Gas Heating  
Gas Heat Capacity  
Cooling Capacity,  
Temp. Rise (°F / °C)  
At Full Input  
Model  
Input (Net)  
Mbh / kW  
Output  
Mbh / kW  
Gas Rate*  
cfh / m3/h  
Mbh / kW  
Min.  
Max.  
D3CG180N320  
D3CG240N320  
180 / 52.7  
240 / 70.3  
291 / 85.2  
258 / 75.6  
302 / 8.5  
30 / 17  
60 / 33  
NOTE: Gas Heaters are shipped available for natural gas, but can be converted to L.P. / propane gas with a field-installed conversion accessory. All gas units are two-stage heating.  
First stage is 50% of total.  
3
*Based on net input and 2nd. -H family, G20 (methane) net fuel value (9.97 kWh/m ).  
Unitary Products Group  
3
530.26-TG3YI  
3
COOLING CAPACITIES (m /s Air Flow) - 180 UNITS  
Sensible Capacity1, kW  
Entering Dry Bulb Temp., °C  
Air On  
Evaporator Coil  
Total  
Cap.1  
kW  
Power  
Input2  
kW  
m3/s  
32  
30  
28  
26  
24  
22  
WB °C  
@27°C Air Temperature on Condenser Coil  
23  
21  
19  
17  
15  
23  
21  
19  
17  
15  
23  
21  
19  
17  
15  
66.4  
62.3  
58.2  
56.7  
55.2  
61.5  
57.7  
53.9  
52.5  
51.1  
57.1  
53.6  
50.1  
48.7  
47.4  
14.7  
14.4  
14.0  
14.0  
13.9  
14.5  
14.2  
13.9  
13.8  
13.7  
14.3  
14.0  
13.6  
13.6  
13.5  
51  
59  
58  
57  
55  
46  
53  
54  
52  
51  
37  
43  
48  
49  
47  
44  
52  
58  
57  
55  
40  
46  
53  
52  
51  
32  
38  
44  
47  
47  
37  
44  
52  
56  
55  
34  
40  
47  
51  
51  
28  
33  
39  
42  
45  
30  
37  
45  
49  
52  
27  
34  
41  
44  
48  
23  
29  
34  
37  
40  
23  
30  
38  
41  
45  
21  
28  
35  
38  
42  
19  
24  
30  
33  
36  
-
23  
31  
34  
37  
-
22  
28  
32  
35  
-
3.40  
2.80  
2.10  
19  
25  
28  
31  
@35°C Air Temperature on Condenser Coil  
23  
21  
19  
17  
15  
23  
21  
19  
17  
15  
23  
21  
19  
17  
15  
60.7  
57.2  
53.7  
52.3  
51.0  
56.3  
53.1  
49.8  
48.6  
47.3  
51.9  
48.9  
45.9  
44.7  
43.6  
15.9  
15.5  
15.2  
15.1  
15.0  
15.9  
15.6  
15.2  
15.1  
15.0  
15.6  
15.3  
14.9  
14.8  
14.7  
50  
57  
54  
52  
51  
44  
51  
50  
49  
47  
36  
41  
46  
45  
44  
43  
50  
54  
52  
51  
38  
44  
50  
49  
47  
31  
37  
42  
45  
44  
36  
43  
51  
52  
51  
32  
38  
45  
48  
47  
27  
32  
38  
40  
43  
29  
36  
43  
47  
47  
25  
32  
39  
41  
44  
22  
27  
33  
35  
38  
22  
29  
36  
40  
40  
19  
26  
32  
35  
38  
17  
23  
28  
31  
33  
-
22  
29  
32  
33  
-
20  
26  
29  
32  
-
3.40  
2.80  
2.10  
18  
24  
26  
29  
@46°C Air Temperature on Condenser Coil  
23  
21  
19  
17  
15  
23  
21  
19  
17  
15  
23  
21  
19  
17  
15  
49.6  
47.3  
45.0  
43.6  
42.1  
49.4  
47.2  
44.9  
43.4  
42.0  
46.5  
44.4  
42.3  
40.9  
39.5  
18.2  
17.6  
17.1  
17.1  
17.1  
17.8  
17.2  
16.6  
16.6  
16.6  
17.5  
17.0  
16.4  
16.4  
16.4  
46  
47  
45  
44  
42  
41  
47  
45  
43  
42  
33  
39  
42  
41  
40  
39  
46  
45  
44  
42  
35  
42  
45  
43  
42  
29  
34  
40  
41  
40  
32  
39  
45  
44  
42  
29  
36  
42  
43  
42  
24  
30  
35  
36  
38  
25  
32  
39  
40  
39  
23  
29  
36  
37  
39  
19  
25  
31  
32  
33  
18  
25  
32  
33  
31  
17  
23  
30  
31  
33  
15  
20  
26  
27  
28  
-
18  
25  
26  
24  
-
17  
24  
25  
27  
-
3.40  
2.80  
2.10  
16  
21  
22  
24  
1
2
These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance Table for the kW of the  
supply air blower motor.  
These ratings include the condenser fan motors (Total 2.3 kW) and the compressor motors but not the supply air blower motor.  
4
Unitary Products Group  
530.26-TG3YI  
COOLING CAPACITIES (CFM Air Flow) - 180 UNITS  
Sensible Capacity1, MBH  
Entering Dry Bulb Temp., °F  
Air On  
Evaporator Coil  
Total  
Cap.1  
MBH  
Power  
Input2  
kW  
CFM  
90  
86  
82  
79  
75  
72  
WB °F  
@80°F Air Temperature on Condenser Coil1  
73  
70  
66  
63  
59  
73  
70  
66  
63  
59  
73  
70  
66  
63  
59  
227  
213  
199  
193  
188  
210  
197  
184  
179  
174  
195  
183  
171  
166  
162  
14.7  
14.4  
14.0  
14.0  
13.9  
14.5  
14.2  
13.9  
13.8  
13.7  
14.3  
14.0  
13.6  
13.6  
13.5  
175  
200  
199  
193  
188  
157  
180  
184  
179  
174  
127  
146  
165  
166  
162  
151  
176  
199  
193  
188  
136  
159  
182  
179  
174  
111  
130  
149  
159  
162  
126  
152  
177  
190  
188  
115  
138  
160  
172  
174  
95  
102  
127  
153  
166  
176  
93  
116  
139  
151  
163  
79  
78  
103  
128  
142  
152  
72  
-
79  
104  
117  
128  
-
74  
97  
109  
121  
-
7200  
95  
5930  
4450  
118  
130  
142  
63  
114  
133  
143  
153  
98  
82  
66  
86  
96  
105  
117  
127  
137  
101  
111  
121  
@95°F Air Temperature on Condenser Coil  
73  
70  
66  
63  
59  
73  
70  
66  
63  
59  
73  
70  
66  
63  
59  
207  
195  
183  
179  
174  
192  
181  
170  
166  
161  
177  
167  
157  
153  
149  
15.9  
15.5  
15.2  
15.1  
15.0  
15.9  
15.6  
15.2  
15.1  
15.0  
15.6  
15.3  
14.9  
14.8  
14.7  
170  
195  
183  
179  
174  
150  
172  
170  
166  
161  
123  
142  
157  
153  
149  
146  
171  
183  
179  
174  
129  
151  
170  
166  
161  
107  
126  
145  
153  
149  
122  
147  
172  
179  
174  
108  
130  
153  
162  
161  
91  
98  
74  
99  
124  
135  
138  
66  
-
123  
148  
159  
162  
87  
109  
132  
141  
151  
75  
75  
100  
111  
113  
-
67  
89  
99  
109  
-
7200  
5930  
4450  
88  
110  
120  
130  
59  
78  
97  
110  
129  
137  
145  
94  
62  
81  
89  
97  
113  
121  
129  
105  
113  
@115°F Air Temperature on Condenser Coil  
73  
70  
66  
63  
59  
73  
70  
66  
63  
59  
73  
70  
66  
63  
59  
169  
161  
154  
149  
144  
169  
161  
153  
148  
143  
159  
151  
144  
139  
135  
18.2  
17.6  
17.1  
17.1  
17.1  
17.8  
17.2  
16.6  
16.6  
16.6  
17.5  
17.0  
16.4  
16.4  
16.4  
157  
161  
154  
149  
144  
141  
161  
153  
148  
143  
114  
133  
144  
139  
135  
133  
158  
154  
149  
144  
120  
142  
153  
148  
143  
98  
109  
134  
154  
149  
144  
99  
121  
144  
148  
143  
82  
85  
61  
85  
110  
112  
107  
57  
-
110  
135  
137  
132  
78  
100  
123  
128  
133  
66  
61  
86  
88  
83  
-
58  
81  
86  
90  
-
7200  
5930  
4450  
79  
102  
107  
112  
50  
69  
88  
117  
136  
139  
135  
101  
120  
124  
128  
85  
53  
72  
76  
80  
104  
108  
112  
92  
96  
1
2
These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance Table for the kW of the  
supply air blower motor.  
These ratings include the condenser fan motors (Total 2.3 kW) and the compressor motors but not the supply air blower motor.  
Unitary Products Group  
5
530.26-TG3YI  
3
COOLING CAPACITIES (m /s Air Flow) - 240 UNITS  
Sensible Capacity1, kW  
Entering Dry Bulb Temp., °C  
Air On  
Evaporator Coil  
Total  
Cap.1  
kW  
Power  
Input2  
kW  
m3/s  
32  
30  
28  
26  
24  
22  
WB °C  
@27°C Air Temperature on Condenser Coil  
23  
21  
19  
17  
15  
23  
21  
19  
17  
15  
23  
21  
19  
17  
15  
80.4  
77.6  
74.8  
72.4  
70.0  
76.9  
74.3  
71.6  
69.3  
67.0  
71.2  
68.7  
66.3  
64.1  
62.0  
19.0  
18.8  
18.6  
18.4  
18.1  
18.8  
18.6  
18.4  
18.2  
17.9  
18.5  
18.3  
18.1  
17.9  
17.6  
74  
78  
75  
72  
70  
68  
73  
72  
69  
67  
56  
60  
65  
64  
62  
65  
70  
75  
72  
70  
60  
65  
70  
69  
67  
50  
54  
59  
62  
62  
55  
61  
67  
71  
70  
52  
57  
62  
67  
67  
44  
48  
52  
56  
60  
46  
52  
57  
62  
65  
44  
49  
54  
59  
63  
37  
42  
46  
50  
54  
37  
43  
48  
53  
56  
36  
41  
46  
51  
55  
31  
36  
40  
44  
47  
-
33  
39  
44  
47  
-
33  
38  
43  
47  
-
4.40  
3.80  
2.80  
30  
34  
38  
41  
@35°C Air Temperature on Condenser Coil  
23  
21  
19  
17  
15  
23  
21  
19  
17  
15  
23  
21  
19  
17  
15  
74.9  
72.3  
69.8  
67.4  
65.0  
71.3  
68.9  
66.4  
64.2  
61.9  
65.4  
63.1  
60.9  
58.8  
56.7  
21.0  
20.7  
20.4  
20.1  
19.9  
20.7  
20.5  
20.2  
19.9  
19.7  
20.4  
20.1  
19.8  
19.6  
19.3  
71  
72  
70  
67  
65  
65  
69  
66  
64  
62  
52  
57  
61  
59  
57  
61  
68  
70  
67  
65  
57  
62  
66  
64  
62  
46  
51  
56  
58  
57  
52  
58  
65  
67  
65  
49  
54  
60  
63  
62  
40  
45  
50  
52  
54  
43  
49  
55  
58  
60  
41  
46  
52  
55  
58  
34  
39  
44  
46  
48  
34  
40  
46  
49  
51  
33  
38  
44  
47  
50  
28  
33  
38  
40  
42  
-
31  
37  
40  
42  
-
30  
36  
39  
42  
-
4.40  
3.80  
2.80  
27  
31  
34  
36  
@46°C Air Temperature on Condenser Coil  
23  
21  
19  
17  
15  
23  
21  
19  
17  
15  
23  
21  
19  
17  
15  
66.4  
63.3  
60.2  
59.0  
57.8  
63.8  
60.8  
57.8  
56.7  
55.5  
59.4  
56.6  
53.8  
52.8  
51.7  
23.4  
22.9  
22.3  
22.3  
22.2  
23.3  
22.7  
22.2  
22.1  
22.1  
23.1  
22.5  
22.0  
21.9  
21.9  
65  
63  
60  
59  
58  
60  
61  
58  
57  
56  
49  
54  
54  
53  
52  
56  
62  
60  
59  
58  
52  
58  
58  
57  
56  
42  
47  
53  
53  
52  
47  
53  
60  
59  
58  
44  
50  
56  
57  
56  
36  
41  
46  
48  
49  
38  
44  
51  
53  
53  
36  
42  
48  
50  
52  
30  
35  
40  
42  
43  
29  
35  
41  
43  
44  
28  
34  
40  
42  
44  
24  
29  
34  
36  
37  
-
26  
32  
34  
35  
-
26  
32  
34  
35  
-
4.40  
3.80  
2.80  
23  
28  
30  
31  
1
2
These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance Table for the kW of the  
supply air blower motor.  
These ratings include the condenser fan motors (Total 2.3 kW) and the compressor motors but not the supply air blower motor.  
6
Unitary Products Group  
530.26-TG3YI  
COOLING CAPACITIES (CFM Air Flow) - 240 UNITS  
Sensible Capacity1, MBH  
Entering Dry Bulb Temp., °F  
Air On  
Evaporator Coil  
Total  
Cap.1  
MBH  
Power  
Input2  
kW  
CFM  
90  
86  
82  
79  
75  
72  
WB °F  
@80°F Air Temperature on Condenser Coil  
73  
70  
66  
63  
59  
73  
70  
66  
63  
59  
73  
70  
66  
63  
59  
274  
265  
255  
247  
239  
263  
253  
244  
236  
229  
243  
234  
226  
219  
212  
19.0  
18.8  
18.6  
18.4  
18.1  
18.8  
18.6  
18.4  
18.2  
17.9  
18.5  
18.3  
18.1  
17.9  
17.6  
252  
265  
255  
247  
239  
232  
250  
244  
236  
229  
191  
206  
221  
219  
212  
221  
240  
255  
247  
239  
205  
222  
240  
236  
229  
170  
185  
200  
212  
212  
189  
208  
227  
243  
239  
177  
195  
213  
228  
229  
149  
164  
179  
191  
204  
158  
177  
196  
211  
223  
150  
168  
186  
200  
215  
128  
143  
158  
170  
183  
127  
146  
164  
180  
192  
123  
141  
158  
173  
188  
107  
122  
137  
149  
162  
-
114  
133  
149  
161  
-
113  
131  
146  
160  
-
9320  
8050  
5930  
101  
116  
128  
141  
@95°F Air Temperature on Condenser Coil  
73  
70  
66  
63  
59  
73  
70  
66  
63  
59  
73  
70  
66  
63  
59  
256  
247  
238  
230  
222  
243  
235  
227  
219  
211  
223  
215  
208  
201  
193  
21.0  
20.7  
20.4  
20.1  
19.9  
20.7  
20.5  
20.2  
19.9  
19.7  
20.4  
20.1  
19.8  
19.6  
19.3  
241  
247  
238  
230  
222  
221  
235  
227  
219  
211  
179  
195  
208  
201  
193  
209  
230  
238  
230  
222  
193  
213  
227  
219  
211  
158  
174  
191  
199  
193  
178  
199  
220  
230  
222  
166  
186  
206  
215  
211  
137  
153  
170  
178  
186  
147  
168  
189  
199  
206  
139  
158  
178  
188  
197  
116  
133  
149  
157  
165  
115  
136  
157  
168  
175  
111  
131  
151  
161  
170  
95  
-
105  
126  
136  
143  
-
104  
124  
133  
143  
-
9320  
8050  
5930  
112  
128  
136  
144  
91  
107  
115  
123  
@115°F Air Temperature on Condenser Coil  
73  
70  
66  
63  
59  
73  
70  
66  
63  
59  
73  
70  
66  
63  
59  
226  
216  
205  
201  
197  
218  
207  
197  
193  
189  
203  
193  
184  
180  
176  
23.4  
22.9  
22.3  
22.3  
22.2  
23.3  
22.7  
22.2  
22.1  
22.1  
23.1  
22.5  
22.0  
21.9  
21.9  
223  
216  
205  
201  
197  
204  
207  
197  
193  
189  
166  
183  
184  
180  
176  
191  
213  
205  
201  
197  
177  
197  
197  
193  
189  
145  
162  
179  
180  
176  
160  
182  
204  
201  
197  
149  
170  
190  
193  
189  
124  
141  
158  
164  
169  
129  
151  
172  
179  
182  
122  
142  
163  
169  
176  
103  
120  
137  
143  
148  
97  
119  
141  
148  
150  
95  
115  
136  
142  
148  
82  
-
88  
110  
117  
119  
-
9320  
8050  
5930  
88  
108  
115  
121  
-
78  
95  
99  
116  
122  
127  
101  
106  
1
2
These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance Table for the kW of the  
supply air blower motor.  
These ratings include the condenser fan motors (Total 2.3 kW) and the compressor motors but not the supply air blower motor.  
Unitary Products Group  
7
530.26-TG3YI  
BLOWER PERFORMANCE (D*CE180 UNIT SUPPLY AIR) -  
w/DOWNFLOW DUCT APPLICATIONS  
3
STANDARD DRIVE (m /s)  
AIRFLOW  
2.80 m3/s  
MOTOR  
PULLEY  
(TURNS  
OPEN)*  
BLOWER  
SPEED,  
RPM  
2.10 m3/s  
2.45 m3/s  
3.10 m3/s  
3.40 m3/s  
ESP Output Input ESP Output Input ESP Output Input ESP Output Input ESP Output Input  
(Pa)  
173  
208  
245  
281  
323  
369  
(kW)  
1.8  
1.9  
2.0  
2.1  
2.3  
2.4  
(kW)  
2.2  
2.3  
2.4  
2.6  
2.7  
2.9  
(Pa)  
138  
172  
208  
242  
283  
327  
(kW) (kW)  
(Pa)  
83  
(kW) (kW)  
(Pa)  
18  
49  
82  
114  
152  
193  
(kW) (kW)  
(Pa)  
-
-
-
30  
67  
107  
(kW) (kW)  
-
-
845  
885  
925  
960  
1000  
1040  
6.0  
5.0  
4.0  
3.0  
2.0  
1.0  
2.2  
2.3  
2.4  
2.6  
2.7  
2.9  
2.6  
2.8  
2.9  
3.1  
3.2  
3.4  
2.6  
2.7  
2.9  
3.0  
3.2  
3.3  
3.1  
3.3  
3.4  
3.6  
3.8  
4.0  
3.0  
3.1  
3.3  
3.4  
3.6  
3.8  
3.5  
3.7  
3.9  
4.1  
4.3  
4.5  
-
-
-
115  
149  
182  
222  
264  
-
3.8  
4.0  
4.2  
4.6  
4.8  
5.1  
3
HIGH SPEED DRIVE (m /s)  
AIRFLOW  
2.80 m3/s  
MOTOR  
PULLEY  
(TURNS  
OPEN)*  
BLOWER  
SPEED,  
RPM  
2.10 m3/s  
2.45 m3/s  
3.10 m3/s  
3.40 m3/s  
ESP Output Input ESP Output Input ESP Output Input ESP Output Input ESP Output Input  
(Pa)  
357  
405  
461  
514  
577  
636  
(kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW)  
1030  
1070  
1115  
1155  
1200  
1240  
6.0  
5.0  
4.0  
3.0  
2.0  
1.0  
2.4  
2.5  
2.7  
2.9  
3.1  
3.3  
2.8  
3.0  
3.2  
3.4  
3.7  
3.9  
316  
362  
416  
468  
529  
587  
2.8  
3.0  
3.2  
3.4  
3.6  
3.8  
3.4  
3.6  
3.8  
4.0  
4.3  
4.5  
253  
298  
351  
401  
461  
-
3.3  
3.5  
3.7  
3.9  
4.1  
-
3.9  
4.2  
4.4  
4.7  
5.0  
-
183  
226  
278  
-
-
-
3.7  
3.9  
4.2  
-
-
-
4.5  
4.7  
5.0  
-
-
-
97  
-
-
-
-
4.2  
5.0  
-
-
-
-
-
-
-
-
-
-
-
STANDARD DRIVE (CFM)  
AIRFLOW  
5930 CFM  
MOTOR  
BLOWER  
SPEED,  
RPM  
PULLEY  
(TURNS  
OPEN)*  
4450 CFM  
5190 CFM  
6565 CFM  
7200 CFM  
ESP Output Input ESP Output Input ESP Output Input ESP Output Input ESP Output Input  
(iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW)  
845  
885  
925  
960  
1000  
1040  
6.0  
5.0  
4.0  
3.0  
2.0  
1.0  
0.7  
0.8  
1.0  
1.1  
1.3  
1.5  
2.4  
2.6  
2.7  
2.9  
3.0  
3.2  
2.2  
2.3  
2.4  
2.6  
2.7  
2.9  
0.6  
0.7  
0.8  
1.0  
1.1  
1.3  
2.9  
3.1  
3.3  
3.4  
3.6  
3.8  
2.6  
2.8  
2.9  
3.1  
3.2  
3.4  
0.3  
0.5  
0.6  
0.7  
0.9  
1.1  
3.5  
3.7  
3.8  
4.0  
4.2  
4.5  
3.1  
3.3  
3.4  
3.6  
3.8  
4.0  
0.1  
0.2  
0.3  
0.5  
0.6  
0.8  
4.0  
4.2  
4.4  
4.6  
4.8  
5.1  
3.5  
3.7  
3.9  
4.1  
4.3  
4.5  
-
-
-
-
-
-
-
-
-
0.1  
0.3  
0.4  
5.2  
5.4  
5.7  
4.6  
4.8  
5.1  
HIGH SPEED DRIVE (CFM)  
AIRFLOW  
5930 CFM  
MOTOR  
BLOWER  
SPEED,  
RPM  
PULLEY  
(TURNS  
OPEN)*  
4450 CFM  
5190 CFM  
6565 CFM  
7200 CFM  
ESP Output Input ESP Output Input ESP Output Input ESP Output Input ESP Output Input  
(iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW)  
1030  
1070  
1115  
1155  
1200  
1240  
6.0  
5.0  
4.0  
3.0  
2.0  
1.0  
1.4  
1.6  
1.9  
2.1  
2.3  
2.6  
3.2  
3.4  
3.6  
3.9  
4.1  
4.4  
2.8  
3.0  
3.2  
3.4  
3.7  
3.9  
1.3  
1.5  
1.7  
1.9  
2.1  
2.4  
3.8  
4..0  
4.3  
4.5  
4.8  
5.1  
3.4  
3.6  
3.8  
4.0  
4.3  
4.5  
1.0  
1.2  
1.4  
1.6  
1.8  
-
4.4  
4.7  
5.0  
5.2  
5.5  
-
3.9  
4.2  
4.4  
4.7  
5.0  
-
0.7  
0.9  
1.1  
-
-
-
5.0  
5.3  
5.6  
-
-
-
4.5  
4.7  
5.0  
-
-
-
0.4  
5.6  
5.0  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
NOTES:  
1. Blower performance values include fixed outdoor air, a dry indoor coil, the standard unit filters and no electric heat.  
2. Refer to Page 12 for the resistance values for all other unit options or applications.  
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower.  
*Do NOT close pulley below minimum turns open.  
8
Unitary Products Group  
530.26-TG3YI  
BLOWER PERFORMANCE (D*CE240 UNIT SUPPLY AIR) -  
w/DOWNFLOW DUCT APPLICATIONS  
3
STANDARD DRIVE (m /s)  
AIRFLOW  
3.80 m3/s  
MOTOR  
PULLEY  
(TURNS  
OPEN)*  
BLOWER  
SPEED,  
RPM  
2.80 m3/s  
3.30 m3/s  
4.10 m3/s  
4.40 m3/s  
ESP Output Input ESP Output Input ESP Output Input ESP Output Input ESP Output Input  
(Pa)  
137  
176  
209  
250  
284  
327  
(kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW)  
765  
795  
820  
850  
875  
905  
6.0  
5.0  
4.0  
3.0  
2.0  
1.0  
2.9  
3.0  
3.1  
3.3  
3.4  
3.6  
3.3  
3.4  
3.6  
3.8  
3.9  
4.1  
93  
2.9  
3.1  
3.2  
3.4  
3.6  
3.8  
3.3  
3.5  
3.7  
3.9  
4.1  
4.3  
23  
62  
95  
136  
170  
212  
3.2  
3.4  
3.6  
3.8  
4.0  
4.3  
3.7  
3.9  
4.1  
4.4  
4.6  
4.9  
-
-
-
-
-
-
-
-
-
16  
51  
93  
-
-
-
4.7  
4.9  
5.2  
-
-
-
5.3  
5.6  
5.9  
132  
165  
206  
240  
283  
40  
81  
115  
157  
4.0  
4.2  
4.4  
4.7  
4.5  
4.8  
5.0  
5.3  
3
HIGH SPEED DRIVE (m /s)  
AIRFLOW  
3.80 m3/s  
MOTOR  
PULLEY  
(TURNS  
OPEN)*  
BLOWER  
SPEED,  
RPM  
2.80 m3/s  
3.30 m3/s  
4.10 m3/s  
4.40 m3/s  
ESP Output Input ESP Output Input ESP Output Input ESP Output Input ESP Output Input  
(Pa)  
312  
362  
421  
473  
535  
590  
(kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW)  
895  
930  
970  
1005  
1045  
1080  
6.0  
5.0  
4.0  
3.0  
2.0  
1.0  
3.5  
3.7  
4.0  
4.2  
4.4  
4.6  
4.0  
4.3  
4.5  
4.8  
5.0  
5.3  
268  
318  
377  
429  
491  
546  
3.7  
4.0  
4.2  
4.5  
4.8  
5.0  
4.3  
4.5  
4.9  
5.1  
5.5  
5.8  
198  
248  
306  
359  
420  
475  
4.2  
4.5  
4.8  
5.1  
5.4  
5.7  
4.8  
5.1  
5.5  
5.8  
6.2  
6.5  
143  
193  
252  
304  
365  
420  
4.6  
4.9  
5.2  
5.6  
5.9  
6.2  
5.2  
5.6  
6.0  
6.4  
6.8  
7.1  
79  
129  
187  
240  
-
5.1  
5.4  
5.8  
6.1  
-
5.8  
6.2  
6.6  
7.0  
-
-
-
-
STANDARD DRIVE (CFM)  
AIRFLOW  
8050 CFM  
MOTOR  
BLOWER  
PULLEY  
5930 CFM  
6990 CFM  
8685 CFM  
9320 CFM  
SPEED,  
(TURNS  
OPEN)*  
ESP Output Input ESP Output Input ESP Output Input ESP Output Input ESP Output Input  
(iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW)  
RPM  
765  
795  
820  
850  
875  
905  
6.0  
5.0  
4.0  
3.0  
2.0  
1.0  
0.6  
0.7  
0.8  
1.0  
1.1  
1.3  
3.8  
4.0  
4.2  
4.4  
4.6  
4.8  
3.3  
3.4  
3.6  
3.8  
3.9  
4.1  
0.4  
0.5  
0.7  
0.8  
1.0  
1.1  
3.9  
4.1  
4.4  
4.6  
4.8  
5.1  
3.3  
3.5  
3.7  
3.9  
4.1  
4.3  
0.1  
0.2  
0.4  
0.5  
0.7  
0.9  
4.3  
4.6  
4.8  
5.1  
5.4  
5.7  
3.7  
3.9  
4.1  
4.4  
4.6  
4.9  
-
-
-
-
-
-
-
-
-
0.1  
0.2  
0.4  
-
-
-
6.2  
6.6  
6.9  
-
-
-
5.3  
5.6  
5.9  
0.2  
0.3  
0.5  
0.6  
5.3  
5.6  
5.9  
6.3  
4.5  
4.8  
5.0  
5.3  
HIGH SPEED DRIVE (CFM)  
AIRFLOW  
8050 CFM  
MOTOR  
BLOWER  
SPEED,  
RPM  
PULLEY  
(TURNS  
OPEN)*  
5930 CFM  
6990 CFM  
8685 CFM  
9320 CFM  
ESP Output Input ESP Output Input ESP Output Input ESP Output Input ESP Output Input  
(iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW)  
895  
930  
970  
1005  
1045  
1080  
6.0  
5.0  
4.0  
3.0  
2.0  
1.0  
1.3  
1.5  
1.7  
1.9  
2.1  
2.4  
4.7  
5.0  
5.3  
5.6  
5.9  
6.2  
4.0  
4.3  
4.5  
4.8  
5.0  
5.3  
1.1  
1.3  
1.5  
1.7  
2.0  
2.2  
5.0  
5.3  
5.7  
6.0  
6.4  
6.8  
4.3  
4.5  
4.9  
5.1  
5.5  
5.8  
0.8  
1.0  
1.2  
1.4  
1.7  
1.9  
5.6  
6.0  
6.4  
6.8  
7.3  
7.7  
4.8  
5.1  
5.5  
5.8  
6.2  
6.5  
0.6  
0.8  
1.0  
1.2  
1.5  
1.7  
6.1  
6.6  
7.0  
7.4  
7.9  
8.4  
5.2  
5.6  
6.0  
6.4  
6.8  
7.1  
0.3  
0.5  
0.8  
1.0  
-
6.8  
7.2  
7.8  
8.2  
-
5.8  
6.2  
6.6  
7.0  
-
-
-
-
NOTES:  
1. Blower performance values include fixed outdoor air, a dry indoor coil, the standard unit filters and no electric heat.  
2. Refer to Page 12 for the resistance values for all other unit options or applications.  
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower.  
*Do NOT close pulley below minimum turns open.  
Unitary Products Group  
9
530.26-TG3YI  
BLOWER PERFORMANCE (D*CG180 UNIT SUPPLY AIR) -  
w/DOWNFLOW DUCT APPLICATIONS  
3
STANDARD DRIVE (m /s)  
AIRFLOW  
2.80 m3/s  
MOTOR  
PULLEY  
(TURNS  
OPEN)*  
BLOWER  
SPEED,  
RPM  
2.10 m3/s  
2.45 m3/s  
3.10 m3/s  
3.40 m3/s  
ESP Output Input ESP Output Input ESP Output Input ESP Output Input ESP Output Input  
(Pa)  
206  
242  
278  
311  
349  
387  
(kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW)  
845  
885  
925  
960  
1000  
1040  
6.0  
5.0  
4.0  
3.0  
2.0  
1.0  
1.8  
1.9  
2.0  
2.1  
2.2  
2.3  
2.2  
2.3  
2.4  
2.5  
2.6  
2.8  
146  
183  
220  
253  
292  
331  
2.0  
2.2  
2.3  
2.4  
2.6  
2.7  
2.5  
2.6  
2.7  
2.9  
3.1  
3.3  
80  
2.4  
2.5  
2.7  
2.8  
3.0  
3.2  
2.8  
3.0  
3.2  
3.4  
3.6  
3.9  
18  
56  
94  
128  
168  
209  
2.7  
2.9  
3.1  
3.2  
3.5  
3.7  
3.2  
3.4  
3.7  
3.9  
4.2  
4.4  
-
-
-
-
3.5  
3.7  
4.0  
4.3  
-
-
4.2  
4.5  
4.8  
5.1  
117  
155  
189  
228  
268  
28  
63  
103  
144  
3
HIGH SPEED DRIVE (m /s)  
AIRFLOW  
2.80 m3/s  
MOTOR  
PULLEY  
(TURNS  
OPEN)*  
BLOWER  
SPEED,  
RPM  
2.10 m3/s  
2.45 m3/s  
3.10 m3/s  
3.40 m3/s  
ESP Output Input ESP Output Input ESP Output Input ESP Output Input ESP Output Input  
(Pa)  
378  
417  
461  
502  
548  
590  
(kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW)  
1030  
1070  
1115  
1155  
1200  
1240  
6.0  
5.0  
4.0  
3.0  
2.0  
1.0  
2.3  
2.4  
2.6  
2.8  
3.0  
3.2  
2.7  
2.9  
3.1  
3.3  
3.6  
3.8  
321  
361  
407  
448  
495  
538  
2.7  
2.9  
3.1  
3.3  
3.6  
3.8  
3.2  
3.4  
3.7  
4.0  
4.3  
4.6  
258  
299  
345  
387  
435  
-
3.2  
3.4  
3.7  
3.9  
4.2  
-
3.8  
4.1  
4.4  
4.7  
5.0  
-
199  
240  
286  
-
-
-
3.6  
3.9  
4.2  
-
-
-
4.4  
4.7  
5.0  
-
-
-
134  
4.2  
5.0  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
STANDARD DRIVE (CFM)  
AIRFLOW  
5930 CFM  
MOTOR  
BLOWER  
SPEED,  
RPM  
PULLEY  
(TURNS  
OPEN)*  
4450 CFM  
5190 CFM  
6565 CFM  
7200 CFM  
ESP Output Input ESP Output Input ESP Output Input ESP Output Input ESP Output Input  
(iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW)  
845  
885  
925  
960  
1000  
1040  
6.0  
5.0  
4.0  
3.0  
2.0  
1.0  
0.8  
1.0  
1.1  
1.2  
1.4  
1.6  
2.5  
2.6  
2.7  
2.8  
2.9  
3.1  
2.2  
2.3  
2.4  
2.5  
2.6  
2.8  
0.6  
0.7  
0.9  
1.0  
1.2  
1.3  
2.7  
2.9  
3.1  
3.2  
3.4  
3.7  
2.5  
2.6  
2.7  
2.9  
3.1  
3.3  
0.3  
0.5  
0.6  
0.8  
0.9  
1.1  
3.2  
3.4  
3.6  
3.8  
4.0  
4.3  
2.8  
3.0  
3.2  
3.4  
3.6  
3.9  
0.1  
0.2  
0.4  
0.5  
0.7  
0.8  
3.6  
3.8  
4.1  
4.3  
4.7  
5.0  
3.2  
3.4  
3.7  
3.9  
4.2  
4.4  
-
-
-
-
-
-
0.1  
0.3  
0.4  
0.6  
4.7  
5.0  
5.3  
5.7  
4.2  
4.5  
4.8  
5.1  
HIGH SPEED DRIVE (CFM)  
AIRFLOW  
5930 CFM  
MOTOR  
BLOWER  
SPEED,  
RPM  
PULLEY  
(TURNS  
OPEN)*  
4450 CFM  
5190 CFM  
6565 CFM  
7200 CFM  
ESP Output Input ESP Output Input ESP Output Input ESP Output Input ESP Output Input  
(iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW)  
1030  
1070  
1115  
1155  
1200  
1240  
6.0  
5.0  
4.0  
3.0  
2.0  
1.0  
1.5  
1.7  
1.9  
2.0  
2.2  
2.4  
3.1  
3.3  
3.5  
3.7  
4.0  
4.3  
2.7  
2.9  
3.1  
3.3  
3.6  
3.8  
1.3  
1.4  
1.6  
1.8  
2.0  
2.2  
3.6  
3.8  
4.1  
4.4  
4.8  
5.1  
3.2  
3.4  
3.7  
4.0  
4.3  
4.6  
1.0  
1.2  
1.4  
1.6  
1.7  
-
4.3  
4.5  
4.9  
5.2  
5.6  
-
3.8  
4.1  
4.4  
4.7  
5.0  
-
0.8  
1.0  
1.2  
-
-
-
4.9  
5.2  
5.6  
-
-
-
4.4  
4.7  
5.0  
-
-
-
0.5  
5.6  
5.0  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
NOTES:  
1. Blower performance values include fixed outdoor air, a dry indoor coil, the standard unit filters and no electric heat.  
2. Refer to Page 12 for the resistance values for all other unit options or applications.  
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower.  
*Do NOT close pulley below minimum turns open.  
10  
Unitary Products Group  
530.26-TG3YI  
BLOWER PERFORMANCE (D*CG240 UNIT SUPPLY AIR) -  
w/DOWNFLOW DUCT APPLICATIONS  
3
STANDARD DRIVE (m /s)  
AIRFLOW  
3.80 m3/s  
MOTOR  
PULLEY  
(TURNS  
OPEN)*  
BLOWER  
SPEED,  
RPM  
2.80 m3/s  
3.30 m3/s  
4.10 m3/s  
4.40 m3/s  
ESP Output Input ESP Output Input ESP Output Input ESP Output Input ESP Output Input  
(Pa)  
202  
238  
268  
305  
336  
347  
(kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW)  
765  
795  
820  
850  
875  
905  
6.0  
5.0  
4.0  
3.0  
2.0  
1.0  
2.1  
2.3  
2.4  
2.5  
2.7  
2.8  
2.4  
2.6  
2.7  
2.9  
3.0  
3.2  
80  
2.7  
2.9  
3.0  
3.2  
3.4  
3.6  
3.1  
3.3  
3.4  
3.7  
3.8  
4.1  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
117  
150  
189  
222  
262  
-
-
50  
85  
128  
3.9  
4.1  
4.3  
4.5  
4.7  
5.0  
37  
4.8  
5.5  
3
HIGH SPEED DRIVE (m /s)  
AIRFLOW  
3.80 m3/s  
MOTOR  
BLOWER  
PULLEY  
2.80 m3/s  
3.30 m3/s  
4.10 m3/s  
4.40 m3/s  
SPEED,  
RPM  
(TURNS  
OPEN)*  
ESP Output Input ESP Output Input ESP Output Input ESP Output Input ESP Output Input  
(Pa)  
361  
400  
439  
486  
527  
569  
612  
(kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW) (Pa) (kW) (kW)  
895  
925  
955  
6.0  
5.0  
4.0  
3.0  
2.0  
1.0  
0.0  
2.8  
2.9  
3.1  
3.3  
3.5  
3.7  
3.9  
3.2  
3.4  
3.6  
3.8  
4.0  
4.2  
4.4  
249  
290  
332  
381  
425  
469  
514  
3.5  
3.7  
3.9  
4.1  
4.3  
4.6  
4.8  
4.0  
4.2  
4.4  
4.7  
5.0  
5.2  
5.5  
114  
157  
201  
254  
299  
346  
393  
4.3  
4.5  
4.7  
5.0  
5.2  
5.5  
5.8  
4.9  
5.1  
5.4  
5.7  
6.0  
6.3  
6.6  
22  
66  
4.7  
5.0  
5.2  
5.5  
5.8  
6.1  
6.4  
5.4  
5.7  
6.0  
6.3  
6.7  
7.0  
7.3  
-
-
-
-
-
-
112  
166  
213  
261  
310  
15  
70  
119  
-
5.8  
6.1  
6.4  
-
6.6  
7.0  
7.3  
-
990  
1020  
1050  
1080  
-
-
-
STANDARD DRIVE (CFM)  
AIRFLOW  
8050 CFM  
MOTOR  
BLOWER  
PULLEY  
5930 CFM  
6990 CFM  
8685 CFM  
9320 CFM  
SPEED,  
(TURNS  
OPEN)*  
ESP Output Input ESP Output Input ESP Output Input ESP Output Input ESP Output Input  
(iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW)  
RPM  
765  
795  
820  
850  
875  
905  
6.0  
5.0  
4.0  
3.0  
2.0  
1.0  
0.8  
1.0  
1.1  
1.2  
1.3  
1.5  
2.8  
3.0  
3.2  
3.4  
3.6  
3.8  
2.4  
2.6  
2.7  
2.9  
3.0  
3.2  
0.3  
0.5  
0.6  
0.8  
0.9  
1.1  
3.6  
3.8  
4.0  
4.3  
4.5  
4.8  
3.1  
3.3  
3.4  
3.7  
3.8  
4.1  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.2  
0.3  
0.5  
5.3  
5.5  
5.8  
4.5  
4.7  
5.0  
0.1  
6.5  
5.5  
HIGH SPEED DRIVE (CFM)  
AIRFLOW  
8050 CFM  
MOTOR  
BLOWER  
SPEED,  
RPM  
PULLEY  
(TURNS  
OPEN)*  
5930 CFM  
6990 CFM  
8685 CFM  
9320 CFM  
ESP Output Input ESP Output Input ESP Output Input ESP Output Input ESP Output Input  
(iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW) (iwg) (bhp) (kW)  
895  
925  
955  
6.0  
5.0  
4.0  
3.0  
2.0  
1.0  
0.0  
1.5  
1.6  
1.8  
2.0  
2.1  
2.3  
2.5  
3.7  
3.9  
4.2  
4.4  
4.7  
4.9  
5.2  
3.2  
3.4  
3.6  
3.8  
4.0  
4.2  
4.4  
1.0  
1.2  
1.3  
1.5  
1.7  
1.9  
2.1  
4.7  
4.9  
5.2  
5.5  
5.8  
6.1  
6.4  
4.0  
4.2  
4.4  
4.7  
5.0  
5.2  
5.5  
0.5  
0.6  
0.8  
1.0  
1.2  
1.4  
1.6  
5.7  
6.0  
6.3  
6.7  
7.0  
7.4  
7.7  
4.9  
5.1  
5.4  
5.7  
6.0  
6.3  
6.6  
0.1  
0.3  
0.4  
0.7  
0.9  
1.0  
1.2  
6.3  
6.7  
7.0  
7.4  
7.8  
8.2  
8.5  
5.4  
5.7  
6.0  
6.3  
6.7  
7.0  
7.3  
-
-
-
-
-
-
0.1  
0.3  
0.5  
-
7.8  
8.2  
8.6  
-
6.6  
7.0  
7.3  
-
990  
1020  
1050  
1080  
NOTES:  
1. Blower performance values include fixed outdoor air, a dry indoor coil, the standard unit filters and no electric heat.  
2. Refer to Page 12 for the resistance values for all other unit options or applications.  
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower.  
*Do NOT close pulley below minimum turns open.  
Unitary Products Group  
11  
530.26-TG3YI  
BLOWER MOTOR AND DRIVE DATA  
ADJUSTABLE  
MOTOR PULLEY2  
PITCH  
FIXED  
BLOWER PULLEY  
MOTOR1  
BELT (NOTCHED)  
BLOWER  
RANGE  
(RPM)  
UNIT  
SIZE  
PITCH  
DIA.  
(mm / in.)  
PITCH  
LENGTH  
(mm/in.)  
FRAME EFF.  
SIZE  
BORE  
DESIG-  
BORE  
(mm/in.) NATION  
DESIG-  
DESIG-  
NATION  
kW/HP  
DIA.  
(mm/in.)  
QTY  
(%)  
84  
87  
84  
87  
(mm/in.) NATION  
109-135  
4.3-5.3  
140-165  
5.5-6.5  
124-150  
4.9-5.9  
147-178  
5.8-7.0  
180 845-1040 3.0 / 4.0 184T  
240 765-905 5.6 / 7.5 213T  
180 1030-1240 3.0 / 4.0 184T  
240 895-1080 5.6 / 7.5 213T  
29 / 118 1VP56 188 / 7.4  
35 / 138 1VP68 264 / 10.4 30 / 1316 BK110 2103 / 82.8 BX81  
29 / 118 1VP62 175 / 6.9  
25 / 1 BK75 1773 / 69.8 BX68  
35 / 138 1VP75 239 / 9.4 30 / 1316 BK100 2103 / 82.8 BX81  
25 / 1  
BK80 1773 / 69.8 BX68  
1
1
1
1
STD.  
DRIVE  
HIGH  
SPEED  
DRIVE  
1
2
All motors are totally enclosed, fan cooled (TEFC), 1450 RPM with solid bases and a 1.15 service factor.  
Do NOT close this pulley below the minimum number of turns open.  
STATIC RESISTANCES*  
EXTERNAL STATIC [RESSURE DRP RESISTANCE, Pa/IWG  
M3/S / CFM  
DESCRIPTION  
MODEL 180  
2.8 / 6000  
24.8 / 0.1  
24.8 / 0.1  
50.0 / 0.2  
74.4 / 0.3  
99.2 / 0.4  
24.8 / 0.1  
MODEL 240  
3.8 / 8000  
24.8 / 0.1  
24.8 / 0.1  
50.0 / 0.2  
74.4 / 0.3  
99.2 / 0.4  
24.8 / 0.1  
2.1 / 4500  
3.4 / 7200  
24.8 / 0.1  
24.8 / 0.1  
74.4 / 0.3  
99.2 / 0.4  
149.0 / 0.6  
24.8 / 0.1  
2.8 / 6000  
24.8 / 0.1  
24.8 / 0.1  
24.8 / 0.1  
50.0 / 0.2  
50.0 / 0.2  
24.8 / 0.1  
4.4 / 9400  
24.8 / 0.1  
24.8 / 0.1  
74.4 / 0.3  
99.2 / 0.4  
149.0 / 0.6  
24.8 / 0.1  
WET COIL  
24.8 / 0.1  
24.8 / 0.1  
24.8 / 0.1  
50.0 / 0.2  
50.0 / 0.2  
24.8 / 0.1  
18 kW  
36 kW  
54 kW  
72 kW  
ELECTRIC HEAT  
OPTIONS  
ECONOMIZER OPTION  
HORIZONTAL DUCT  
CONNECTIONS  
50.0 / 0.2  
74.4 / 0.3  
124.0 / 0.5  
50.0 / 0.2  
74.4 / 0.3  
124.0 / 0.5  
* Deduct these resistance values from the available unit ESP values listed in the respective blower performance table except for Horizontal Duct Connections. Add the Horizontal Duct  
Connection values due to less airflow resistance.  
12  
Unitary Products Group  
530.26-TG3YI  
FIELD WIRING - Electric/Electric and Gas/Electric Units  
L1  
L2  
L3  
LINE VOLTAGE  
TERMINAL  
BLOCK 2TB  
IN UNIT  
CONTROL BOX  
Refer to the  
ELECTRICAL DATA  
tables to size the  
power wiring, the fuses and  
the disconnect switch.  
NEUTRAL  
TERMINAL  
N
GRD. LUG  
24 VOLT  
TRANSFORMER  
ELECTRICAL DATA - Cooling Only Units and Units With Gas Heat  
SUPPLY AIR  
BLOWER  
MOTOR, (FLA)  
TOTAL UNIT  
AMPACITY,  
(AMPS)  
OUTDOOR  
FAN  
MOTOR,  
(#1 & #2)  
FLA, EACH  
COMPRESSOR  
MAX.  
FUSE  
SIZE1  
MIN.  
UNIT  
SIZE  
POWER  
SUPPLY  
WIRE SIZE2,  
(mm2/AWG)  
RLA LRA  
3 kW  
5.6 kW  
3 kW  
4 HP  
5.6 kW  
7.5 HP  
4 HP 7.5 HP  
#1  
380/400/415-3+N-50 19.2  
#2  
#1  
#2  
73  
146  
180  
240  
9.6  
146  
146  
2.4  
2.4  
8.6  
-
-
47.0  
-
-
60  
70  
10 / 8  
16 / 6  
380/400/415-3+N-50 19.2 19.2  
11.7  
59.7  
NOTES:  
1. Slow blow type fuse.  
2. Based on 105°C insulated copper conductors in conduit.  
Unitary Products Group  
13  
530.26-TG3YI  
ELECTRICAL DATA - Units With Supplemental Electric Heating  
HEATER OPTION  
OUTPUT  
MINIMUM  
POWER  
SUPPLY  
(VOLTS)  
MINIMUM  
WIRE SIZE2  
(mm2/AWG)  
UNIT  
SIZE  
CIRCUIT  
AMPACITY  
(AMPS)  
MAXIMUM  
FUSE SIZE1  
MODEL  
STAGES  
AMPS  
kW  
E018  
E036  
E054  
E072  
E018  
E036  
E054  
E072  
E018  
E036  
E054  
E072  
E018  
E036  
E054  
E072  
11.3  
22.6  
33.8  
45.1  
13.5  
26.9  
40.4  
53.8  
11.3  
22.6  
33.8  
45.1  
13.5  
26.9  
40.4  
53.8  
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
17.1  
34.3  
51.4  
68.6  
18.7  
37.4  
56.2  
74.9  
17.1  
34.3  
51.4  
68.6  
18.7  
37.4  
56.2  
74.9  
47.0  
53.6  
75.0  
96.5  
47.0  
57.5  
80.9  
104.0  
59.7  
59.7  
78.9  
100.0  
59.7  
61.4  
84.8  
108.0  
60  
60  
80  
100  
60  
60  
90  
110  
70  
70  
80  
110  
70  
70  
90  
110  
10 / 8  
16 / 6  
25 / 4  
35 / 2  
10 / 8  
16 / 6  
25 / 4  
35 / 2  
16 / 6  
16 / 6  
25 / 4  
35 / 2  
16 / 6  
16 / 6  
25 / 4  
50 / 2  
380-3+N-50  
415-3+N-50  
380-3+N-50  
415-3+N-50  
180  
240  
NOTES:  
1. Slow blow type fuse.  
2. Based on 105°C copper conductors.  
PHYSICAL DATA  
UNIT SIZE (MBH)  
WEIGHTS (kg. / lbs.)  
D*CE UNITS  
COMPONENT DESCRIPTION  
180  
381 x 381  
15 x 15  
3.7 / 5  
3
240  
457 x 381  
18 x 15  
5.6 / 7.5  
3
DIA. x WD. (mm)  
DIA. x WD. (in.)  
kW / HP  
180  
240  
D*CG UNITS  
866 / 1910  
957 / 2110  
CENTRIFUGAL BLOWER  
SUPPLY AIR  
BLOWER  
BASIC  
UNIT  
FAN MOTOR  
ROWS DEEP  
FINS PER 25mm (1 in.)  
FACE AREA  
PROPELLER DIA.  
FAN MOTOR  
180  
240  
975 / 2150  
1066 / 2350  
INDOOR  
COIL  
13.5  
13.5  
m2 / Ft.2  
mm / in.  
kW / HP  
m3 / s  
1.45 / 15.5 1.92 / 20.5  
762 / 30 (ea.)762 / 30 (ea.)  
0.7 / 1 (ea.) 0.7 / 1 (ea.)  
OPTIONS / ACCESSORIES  
Economizer 73 / 160  
Motorized Damper  
18 kW  
OUTDOOR  
FANS  
68 / 150  
11 / 25  
2.83 (ea.)  
3.78 (ea.)  
(Two Per Unit)  
NOMINAL AIRFLOW  
CFM  
6000 (ea.)  
8000 (ea.)  
36 kW  
54 kW  
72 kW  
180  
14 / 30  
16 / 35  
18 / 40  
79 / 175  
84 / 185  
20 / 45  
Electric  
Heaters  
ROWS DEEP  
FINS PER 25mm (1 in.)  
FACE AREA  
TANDEM (10 TON NOMINAL CAPACITY)  
HERMETIC (5 TON NOMINAL CAPACITY)  
2
2
OUTDOOR  
COIL  
13  
20  
m2 / Ft.2  
3.35 / 36.0 4.02 / 43.3  
Roof Curb  
1*  
1
2
-
COMPRESSOR  
(Qty. Per Unit)  
240  
Barometric Damper  
406 x 508 x 51 (mm)  
180  
240  
91 / 200  
100 / 220  
Wood  
Skid*  
QUANTITY PER UNIT  
QUANTITY PER UNIT  
-
-
4
4
-
16 x 20 x 2 (in.)  
406 x 635 x 51 (mm)  
16 x 25 x 2 (in.)  
*Allows handling of unit using 2300mm (90")  
long forks.  
AIR  
FILTERS  
457 x 610 x 51 (mm)  
18 x 24 x 2 (in.)  
QUANTITY PER UNIT  
TOTAL FACE AREA  
REFRIGERANT 22  
5
m2 / Ft.2  
1.40 / 15.0 1.87 / 20.0  
7.94 / 17.5 8.16 / 18.0  
3.86 / 8.5  
SYS. #1 ( kg. / lbs.)  
SYS. #2 (kg. / lbs.)  
CHARGE  
8.16 / 18.0  
*This compressor will be energized first.  
14  
Unitary Products Group  
530.26-TG3YI  
UNIT DIMENSIONS - D*CE180 & 240 UNITS  
1235 (48-5/8") (180)  
1337 (52-5/8") (240)  
3181 (125-1/4") (180)  
3461 (136-1/4") (240)  
616 (24-1/4") (180)  
895 (35-1/4") (240)  
RETURN AIR  
All dimensions are in millimeters and inches,  
unless otherwise specified. They are subject  
to change without notice. Certified  
dimensions will be provided upon request.  
SUPPLY AIR  
OUTDOOR AIR  
(Discharge)  
CLEARANCES (mm / in.)  
OUTDOOR AIR  
(Economizer)  
Front  
Back  
914 / 36  
610 / 24 (Less Economizer)  
1245 / 49 (With Economizer)  
610 / 24 (Less Economizer)  
1372 / 54 (With Economizer)  
Left Side (Filter Access)  
UTILITIES ENTRY DATA  
Right Side (Outdoor Coil)  
Below Unit  
914 / 36  
20 / 0  
1829 / 72 With 914 / 36  
Maximum Horizontal Overhang  
(For Outdoor Air Discharge)  
OPENING  
DIAMETER*  
(mm / in.)  
HOLE  
USED FOR  
28.6 / 118 KO  
Front  
Above Unit*  
Control  
Wiring  
A
B
19.1 / 34 NPS (Fem.)  
92.1 / 358 KO  
Bottom  
Front  
NOTE: Unit and ductwork are approved for zero clearance to combustible  
materials when equipped with electric heat.  
Power  
Wiring  
76.2 / 3 NPS (Fem.)  
Bottom  
*Units must be installed oudoors. Overhanging structures or shrubs should not  
obstruct outdoor air discharge outlet.  
*KO denotes Knockout facility.  
Unitary Products Group  
15  
530.26-TG3YI  
UNIT DIMENSIONS - D*CG180 & 240 UNITS  
1235 (48-5/8") (180)  
1337 (52-5/8") (240)  
3181 (125-1/4") (180)  
3561 (136-1/4") (240)  
616 (24-1/4") (180)  
895 (35-1/4") (240)  
RETURN AIR  
SUPPLY AIR  
OUTDOOR AIR  
(Discharge)  
OUTDOOR AIR  
(Economizer)  
CLEARANCES (mm / in. )  
Front1  
Back  
914 / 36  
610 / 24 (Less Economizer)  
1245 / 49 (With Economizer)  
610 / 24 (Less Economizer)  
1372 / 54 (With Economizer)  
All dimensions are in millimeters and inches,  
unless otherwise specified. They are subject to  
change without notice. Certified dimensions  
will be provided upon request.  
Left Side (Filter Access)  
Right Side (Outdoor Coil) 914 / 36  
Below Unit2  
0 / 0  
UTILITIES ENTRY DATA  
1829 / 72 with 914 / 36 maximum  
Horizontal Overhang  
Above Unit3  
OPENING  
(For Outdoor Air Discharge)  
Locate unit so that the vent air outlet hoods are at least:  
HOLE  
DIAMETER*  
(in. / mm)  
USED FOR  
1
0.9 meter (3 ft) above any forced air inlet located within 3.0m (10 ft) horizontal  
(excluding those integral to the unit).  
1.2 meters (4 ft) below, 1.2m (4 ft.) horizontal from, or 0.31m(1 ft) above any door  
or gravity air inlet into the building.  
1-1/8 / 29 KO  
3/4 NPS / 19 (Fem.)  
3-5/8 / 92 KO  
3 NPS / 76 (Fem.)  
2-3/8 / 60 KO  
Front  
Bottom  
Front  
A
B
Control Wiring  
Power Wiring  
1.2 meters (4 ft) from electric meters, gas meters, regulators and relief equipment.  
Bottom  
2
Units may be installed on combustible surfaces capable of continuous exposure to  
C
D
Gas Piping (Front)  
temperatures of 92°C (197°F), and intermittent exposure to temperatures of 124°C (255°F).  
Units must be installed outdoors. Overhanging structures or shrubs should not  
3
1-11/16 / 43 Hole  
Gas Piping (Bottom)**  
obstruct the outdoor air discharge outlet.  
*KO denotes Knockout facility.  
**Opening in the bottom of the unit can be located by the slice in the insulation.  
NOTE: A 25mm (1 in.) clearance must be provided between any combustible material and the  
supply air ductwork for a distance of 0.9m (3 ft) from the unit.  
The products of combustion must not be allowed to accumulate within a confined space  
and recirculate.  
16  
Unitary Products Group  
530.26-TG3YI  
UNIT DIMENSIONS - D*CE / D*CG180 & 240 UNITS (Cont’d.)  
DUCT COVERS - Units are shipped with the bottom  
duct openings covered. An accessory flange kit is  
available for connecting side ducts.  
For downflow duct applications:  
1. Remove the side panels from the supply and return  
air compartments to gain access to the bottom  
supply and return air duct covers.  
2. Remove and discard the bottom duct covers.  
3. Replace the side supply and return air compartment  
panels.  
For sideflow duct applications;  
1. Replace the side panels on the supply and return air  
compartments with the accessory flange kit panels.  
2. Connect ductwork to the duct flanges on the rear of  
the unit.  
727 (28-5/8") (180)  
1006 (39-5/8") (240)  
DETAIL “X”  
ACCESSORY SIDE SUPPLY AND RETURN AIR DUCT OPENINGS  
397  
5
15 “  
8
610 (24") (180)  
889 (35") (240)  
DETAILY”  
UNIT WITH ECONOMIZER AND FIXED OUTDOOR AIR HOODS  
OUTDOOR COIL  
END OF UNIT  
2337  
(92")  
1524  
(60")  
3181 (125-1/4") (180)  
3461 (136-1/4") (240)  
1143  
(45")  
CENTER OF GRAVITY  
Unitary Products Group  
17  
530.26-TG3YI  
ROOF CURB DIMENSIONS - D*CE / D*CG180 & 240 UNITS  
362 (14-1/4") (180)  
641 (25-1/4") (240)  
2927 (115-1/4") (180)  
3207 (126-1/4") (240)  
* Supply and Return Air (including duct suppport rails)  
as shown, are typical for downflow duct applications.  
For location of sideflow duct applications  
(on back of unit), refer to Unit Dimension details.  
ROOF CURB BENEFITS  
UNIT AND CURB APPLICATION  
2927 (115-1/4") (180)  
3207 (126-1/4") (240)  
TYPICAL APPLICATIONS  
18  
Unitary Products Group  
530.26-TG3YI  
TYPICAL APPLICATIONS - Cont’d.  
ROOF-TOP INSTALLATION  
(GAS/ELECTRIC UNIT SHOWN)  
Unitary Products Group  
19  
P.O. Box 1592, York, Pennsylvania USA 17405-1592  
Subject to change without notice. Printed in U.S.A  
530.26TG3YI  
Supersedes: Nothing  
Copyright by York International Corporation 1994. All Rights Reserved.  

Toshiba All In One Printer 355 User Manual
Samsung Aw088aa User Manual
Lexmark X 2650 User Manual
Lanier 5613 User Manual
EPSON EB 97H User Manual
DELL D1000 User Manual
CRAFTSMAN 315.220100 User Manual
ASUS VG246H User Manual
ACER AW329 User Manual
ACER ASPIRE E1 E1 472PG User Manual