CUSTOM PACKAGED
ELECTRONIC
AIR CLEANER
Air Boss
T-Series
Model T5200
• INSTALLATION
• OPERATION
• SERVICE
Electrostatic Precipitators for
Commercial & Industrial
Applications
101 McNeill Road • Sanford, NC 27330
(919) 775-2201 • Fax: (919) 774-8771 • (800) 884-0002
MANUAL PART NO. 150391-001 • January 2002
OPERATION
I. SPECIFICATIONS
What is your Electronic Air Cleaner?
POWER REQUIREMENTS
Model
Voltage
HP
2
AMPS (Max)
Your air cleaner is a high efficiency contaminant
collector designed to remove up to 95% of the dust,
smoke, liquid aerosol and other pollutants from the air
passing through it.
T5200B
T5200B
T5200C
T5200C
T5200D
230V, 60 HZ, 3 PH.
230V, 60 HZ, 3 PH.
460V, 60 HZ, 3 PH.
460V, 60 HZ, 3 PH.
575V, 60 HZ, 3 PH.
208V, 60 HZ, 3 PH.
6.8
9.7
3.4
4.9
3.2
6.8
3
2
3
2
HOW IT OPERATES
T5200N
2
Note:
Ionizer Voltage:
Collector Voltage: 12 KVDC
Motor: (where applicable) Ball bearing, Totally enclosed, Fan Cooled.
Polluted air is drawn into the unit by the belt driven
blower on the T5200 unit. The T1001 and T2002 units
require an external air handler to move the air.
6 KVDC
After passing through a pre-filter, the particles in the air
are given an electrical charge supplied by the power
supply. As the particles enter the collector cells, these
charged particles are attracted to and collected on
grounded collecting plates.
II. PREPARATION FOR INSTALLATION
This manual should be carefully read before starting the
preparation and installation of the air cleaner.
The installation should conform to all local ordinances
associated with building codes and electrical codes
required for the unit. Authorities having jurisdiction
should be consulted before installation is made. If there
are no local codes, the installation should conform to
the National Electrical Code.
SAFETY NOTE:
Typical Electronic Cell Operation
UNIT OPERATION
Factory designed access to all electrically charged
high voltage components contain electrical
interlocks for the safety of operating personnel. Any
additional access that may be provided in the
system, where there is access to high voltage, must
be equipped with such interlocks. Interlocks are
readily available from the factory.
The 575V, 3 Phase unit does not have internal motor
overload protection. The installer must provide overload
protection in accordance with National Electrical Code,
Canadian Electrical Code, Part 1 or other applicable
electrical codes.
For maximum air cleaning efficiency, your air cleaner
should be located as specified by your Trion
representative.
The unit can be either wall-mounted or chain-hung.
Eyebolts can be supplied by Trion.
NEW UNIT INSPECTION
Control Switch (A): The control switch is located on
the cell access door. It controls the operation of the
power pack and the belt driven blower. The control
switch should be in the “OFF” position when the cell
access door is open for maintenance of the unit.
Immediately, upon receiving the unit, carefully examine
the package for damage during transit. If the unit is
damaged, contact the last carrier for claim filing and
contact your Trion representative.
While unpacking the unit, look for concealed shipping
damage. If there is damage, it should be reported to the
last carrier for claim filing.
Indicating Light (B): The light located adjacent to the
control switch is an indicator of the performance of your
electronic air cleaner. When the control switch is “ON”,
the blower should operate and the indicator light should
glow. If the light does not glow or if it continually flickers
3
and is accompanied with a continual snapping or arcing
noise, the air cleaner requires attention and may need
to be cleaned.
2. Remove ionizer/collector cell(s), pre-filters and
after-filters.
Cell Access Door Knobs (C): The cell access
doorknobs are located on the door near the intake end
of the unit. To open the cell access door, turn the knobs
counter clockwise until it releases from the cabinet.
3. Attach 600 pound test chain to the ceiling joist
using:
a. Wood joist – 1/2” –13 eye bolts
b. Metal joist – wrap chain around joist at least
twice and secure with 600 pound test
connecting link
Arcing (snapping or cracking noise): An occasional
arcing noise may be emitted from the air cleaner. This is
a normal occurrence caused by exceptionally large
pieces of dirt, etc., entering the collecting elements. In
addition, an arcing noise accompanied by a flickering of
the indicating light may be noticed after washing the
cells. Should this occur, allow more drying time. Also,
see “Troubleshooting Chart”, for additional causes of
arcing.
4. Chain should be cut to allow the unit to hang from a
predetermined height from the floor. (Usually 10-12
feet).
5. The unit is equipped with a locator dimple in each
corner on the top and bottom and (1) each on the
approximate mid point edge of the top and bottom..
Using the dimples as a guide, drill (6) 19/32” dia.
Holes that will be required for mounting the eye
bolts, which are attached to the suspension chain.
The louvers on the grill are adjustable so the direction of
airflow can be controlled as desired.
NOTE: The unit is equipped with an interlock switch for
your safety. The unit will not operate if the cell access
door is not closed securely.
6. Screw a ½”-13 x 1-1/4” long eye bolt (or larger) in
each hole. The T5200 unit is supplied with weld
nuts at each dimple location.
NOTE: The blower access door is not protected by an
interlock switch. Do not attempt to operate the unit
unless the door is fastened securely.
7. Using 1/2” connecting links, attach unit to chain.
Use turnbuckles on diagonally opposite chains.
NOTE: Foul threads on turnbuckles after leveling
unit to ensure that the turnbuckle will not "“back off"
or loosen and cause the unit to fall.
DUCTING APPLICATION
The T5200 air cleaner is designed for free hanging
applications or for limited duct system applications. The
duct systems must be carefully designed to keep the
external static pressure to a minimum while still moving
the required amount of air. Some added static pressure
can be overcome by adjusting the blower drive pulleys
or using a more powerful motor. Capture hoods and
duct design information may be obtained from the
Industrial Ventilation Handbook or from your local Trion
representative.
8. The units can be suspended with the direction of
airflow from the right to left. If a left to right airflow is
desired, the unit may be flipped over and the
eyehooks installed in what was originally the
bottom.
To maintain the selected cleaning efficiency, it is
important to assure that the total air volume (capacity in
CFM) is uniformly distributed across the entire face area
of the unit. The metal mesh filters, perforated plate or
mist suppressors; provide some resistance to effect
even air distribution. However, since most air ducts are
designed to handle air velocities greater than the rated
velocity of the air cleaner, it is necessary to properly
transition any attached ducting. If possible, a contraction
ratio of 1 in 3 (approximately 20°) should be maintained.
If space prohibits, turning vanes, air baffles or other
means may be utilized. Ducting – where attached to the
cabinet collars – should be gasketed, caulked or
otherwise made watertight.
III. INSTALLATION – READ THOROUGHLY
1. Carefully unpack unit from shipping crate or carton
and examine for damage in shipment.
4
IV. MAINTENANCE
LIQUID AEROSOL APPLICATION
INSTALLATIONS
The following instructions are for use by qualified
personnel.
The unit is equipped with a sump, drain hole sized to
accept a ½” NPT fitting.
For the collection of liquid contaminant:
WARNING
RISK OF ELECTRIC SHOCK
These serving instructions are for use by qualified
personnel only. To reduce the risk of electric shock,
do not perform any servicing other than that
contained in the operating instructions unless you
are qualified to do so.
1. Install drain fitting to allow for the attachment of a
liquid collection cup or drain hose. A drain fitting is
available from your representative. An “S” trap is
required in the drain hose to ensure proper drainage
of the collected liquid.
2. Raise the front corner of the unit, opposite of the
drain corner, ½” to enable the collected liquid to flow
to the drain sump.
SAFETY NOTE:
Factory designed access to all electrically charged
high voltage components contain electrical
interlocks for the safety of operating personnel. Any
additional access that may be provided in the
system, where there is access to high voltage, must
be equipped with such interlocks. Interlocks are
readily available from the factory.
Contaminants to be collected – such as oils in vaporous
state – must be condensed into particulate form prior to
entering the ionizing-collecting cells in order to maintain
the anticipated efficiency. Gases, vapors or any non-
particulate cannot be precipitated and will therefore
pass through the air cleaner. Any condensing that takes
place downstream from the air cleaner defeats the
purpose. Similarly, heavy concentrations of water vapor,
or other matter that becomes highly conductive when
condensed, must be prevented from entering and/or
condensing in the collecting elements to prevent
electrical arc over and shorting.
Cleaning
The pre-filters, ionizer/collector cells should be removed
periodically and soaked in a solution of hot water and
Trion Tridex detergent for 2 to 4 hours, rinsed
thoroughly and then air dried completely before
reinstalling in the unit.
The frequency of cleaning is dependent on the type of
contaminant being collected. Liquid aerosol requires
less cleaning while welding smoke may require more
frequent cleaning.
The unit should be kept clean to maintain the maximum
collection efficiency.
ELECTRICAL INSTALLATION
All units must be wired directly in the junction box on the
access door side of the unit. Use NEC Class I wiring
methods. Size branch circuit protection in accordance
with the NEC. Refer to the appropriate enclosed wiring
diagram in the attached figures.
Note: Trion Tridex Detergent is specially formulated
for use with Trion electronic air cleaners. Use of
other cleaners and detergents, not specifically
approved by Trion, can cause possible failures in
the unit and will void any and all warranties on our
equipment.
WARNING:
EXERCISE ALL THE NORMAL PRECAUTIONS
WHEN WORKING WITH HIGH VOLTAGE AND
COMPLY WITH NEC AND ALL APPROPRIATE
LOCAL CODES.
Check Out for System Start-up
When the installation has been completed, assure that
the equipment is ready for start-up by checking the
following:
A. All construction debris is removed from the ionizing-
collecting cells, drain connections and ductwork.
B. The drain line from the Trion drain basin is clear and
completely connected to its point of termination.
C. Supply line power is available and electrical wiring
is completed to the junction box.
5
Belt tension should be checked periodically. When a
moderate force is applied to the belt midway between
the pulleys, the belt should deflect approximately ½ “.
CAUTION
Having too much tension on the belts will shorten
the belt life and place undue stress on the motor
and blower bearings.
V. REPLACEMENT PARTS ORDERING
INFORMATION
The following pages contain exploded views and Bills of
Material for the Trion T Series Air Cleaners. Use these
pages to determine the part numbers of the items
needed. To order parts contact your local Trion
representative and provide the following information:
Wash Ionizing/ Collecting Cells
a. Unit Model number – located on the data label near
WARNING:
the junction box.
DO NOT USE HIGH PRESSURE STEAM CLEANING
EQUIPMENT TO CLEAN CELLS. THE EXCESSIVE
HEAT AND PRESSURE WILL CAUSE THE PLATES
TO WARP AND IN TURN POSSIBLY CAUSE
EXCESSIVE ARCING.
b. Part Number and description – from exploded
views.
VI. WARRANTY
All Trion Electronic Air Cleaners are warranted for 3
Year Limited Warranty on units and 1 Year Limited
Warranty on replacement parts. Labor is NOT included.
Do not return defective parts without permission from
the factory and receiving a material return acceptance
number.
1. Turn the control switch “OFF” and disconnect power
to the unit.
2. Open the cell access door.
3. Remove ionizer/collector cells and wash in HOT
detergent water. If the collected contaminant is of
extremely dry nature, it can be blown off the cells
with a pressure hose or gently tapping the end plate
of the cell.
VII. TROUBLESHOOTING GUIDE
T5200 Problems and Possible Causes:
4. Remove the mechanical pre-filter. Remove
collected dust or lint by vacuuming or brushing.
Wash with warm, soapy water.
1. Indicating Light Out
a. Unit not plugged in
b. Control switch “Off”
c. Cell access panel not fully closed
d. Broken cell insulator
e. Extremely dirty cells
5. Rinse all components thoroughly in warm, clear
water and allow to drip dry completely.
f. Service panel not secured in place
6. Replace pre-filter and ionizer/collector cells.
ENSURE the airflow arrows point in the direction of
airflow (towards the blower).
2. Excessive arcing noise after washing
a. Collector elements still wet – Allow more drying
time
7. Close the access door; reconnect power to the unit.
b. See “Continuous arcing noise” below
8. Turn control switch to “ON”. If arcing occurs or the
indicating light flickers, the components may still be
damp. Turn the unit OFF and allow the cells to dry
completely.
3. Continuous arcing noise and flickering indicating
light
a. Extremely dirty collector plates
b. Bent collector plates
c. Large piece of material lodged between cell
plates
Inspections
4. Contaminant Bypass
The motor and blower on Trion T5200 air cleaners have
sealed ball bearings and never need lubricating.
a. Velocity of airflow is too high through unit
b. Collector plates not grounded
6
c. Collector cell not making solid connection to
access door and high voltage contact.
WARNING
T5200 Troubleshooting Guide
Factory designed access to all electrically charged
high voltage components contain electrical
interlocks for the safety of operating personnel.
Always unplug the unit while performing service
within the cabinet.
The troubleshooting chart, shown on the next page, will
enable the user to pinpoint the cause of most problems.
Refer to the Ordering Information for replacement parts.
Before performing any troubleshooting, ensure the
correct input line voltage is present.
IF PROBLEM CANNOT BE DETERMINED OR
CORRECTED - CONTACT YOUR LOCAL TRION
REPRESENTATIVE OR CALL TRION CUSTOMER
SERVICE AT 1-800-884-0002 FOR ASSISTANCE.
7
|