INSTALLATION INSTRUCTIONS
Ventilating Fan
Model No.
FV-05-11VKSL1
FV-05-11VKL1
FV-11-15VKL1
Contents
Representative models:
2-3
GENERAL SAFETY INFORMATION
PLEASE READ PRIOR TO INSTALLING THIS FAN
DESCRIPTION
3-4
4
4
UNPACKING
5
SUPPLIED ACCESSORIES
5
DIMENSIONS
5
WIRING DIAGRAM
5-6
FEATURE
6-7
INDICATION (PLUG ‘N PLAY FUNCTION DEVICES)
DESCRIPTION FOR NIGHT LIGHT MODULE
MOTION (PLUG ‘N PLAY FUNCTION DEVICES)
INSTALLATION (PLUG ‘N PLAY FUNCTION DEVICES)
INSTALLATION (NEW CONSTRUCTION)
INSTALLATION (RETROFIT)
FV-05-11VKSL1 FV-05-11VKL1
7
7
8
8-10
10
MAINTENANCE
MAINTENANCE
(CLEANING)
11
(REPLACEMENT OF LAMP)
11
BACK COVER
BACK COVER
BACK COVER
PRACTICAL GUIDE TO INSTALLATION
SPECIFICATIONS
FV-11-15VKL1
PRODUCT SERVICE
READ AND SAVE THESE INSTRUCTIONS
Thank you for purchasing this Panasonic product.
Please read these instructions carefully before attempting to install, operate or service
the Panasonic product. Failure to comply with instructions could result in personal injury
or property damage. Please explain to users how to operate and maintain the product
after installation, and this booklet should be presented to users.
Please retain this booklet for future reference.
GENERAL SAFETY INFORMATION CONTINUED
WARNING
When this product is no longer being operated, please remove the product to prevent the
possibility of falling.
Ceiling joist must be subjected to static load more than five times the weight of the product.
Do not install with a method which is not approved in the instructions.
Do not use this fan with any solid-state speed control device. Solid state controls may cause
harmonic distortion which can cause motor humming noise.
This product must be properly grounded.
CAUTION
Do not install this ventilating fan where interior room temperature may
exceed 104°F(40°C).
Prohibited
Make sure that the electric service supply voltage is AC 120V, 60Hz.
Follow all local electrical and safety codes, as well as the National
Electrical Code (NEC) and the Occupation Safety and Health Act (OSHA).
Prohibited
Always disconnect the power source before working on or near the fan,
motor, light fixture or junction box.
Protect the supply wiring from sharp edges, oil, grease, hot surfaces,
Prohibited
chemicals or other objects.
Adaptor
Do not kink the supply wiring.
Prohibited
Provide make up air for proper ventilation.
For general ventilating use only. Do not use to exhaust hazardous or
explosive materials and vapors.
(Cooking area)
Do not install above or
inside this area
Do not install the unit where ducts are configured as shown
in Fig.A.
Not for use in cooking area. (Fig.B)
Floor
Cooking
equipment
The special-purpose or dedicated parts, such as mounting
fixtures, must be used if such parts are provided.
Fig. B
PLEASE READ PRIOR TO INSTALLING THIS FAN
Spot and Continuous Ventilation: These fans are designed to run continuously ensuring a healthy
environment at low CFM levels 24 hours a day. By utilizing the optional CustomVent Multi-Speed module
the fans are built to run continuously at a pre-set lower level (FV-05-11VKSL1 and FV-05-11VKL1: 0, 30,
40, 50, 60, 70, 80, 90, 100 CFM; FV-11-15VKL1: 0, 50, 60, 70, 80, 90, 100, 110, 120 CFM). The setting is
dependent on the size of the house and the individual wishes of the homeowner. It is crucial that the
installer pre-set the lower setting during the installation. Please refer to the chart below and the
switch indication on page 6.
3
PLEASE READ PRIOR TO INSTALLING THIS FAN CONTINUED
CustomVent Multi-Speed module (Lower Setting). ASHRAE 62.2-2010
(sq.feet)
Two Bedrooms Three Bedrooms Four Bedrooms Five Bedrooms
33
38
43
48
53
58
63
68
73
78
83
88
93
40
45
50
55
60
65
70
75
80
85
90
95
100
<1,000
1,500
2,000
2,500
3,000
3,500
4,000
4,500
5,000
5,500
6,000
6,500
7,000
48
53
58
63
68
73
78
83
88
93
98
103
108
55
60
65
70
75
80
85
90
95
100
105
110
These fans are also built to take care of the homeowner’s spot ventilation needs when the room is
occupied. The basic fan models allow a choice of three speeds. When fans are equipped with the optional
Multi-Speed module, these models kick up to a maximum level of 150 CFM for the FV-11-15VKL1 and 110
CFM for the FV-05-11VKSL1 and FV-05-11VKL1 either when the switch is turned on or activated by the
optional Condensation Sensor module or the optional Motion Sensor module.
A High/Low Delay Timer, located inside the fan unit, is utilized to return the fan back to the pre-set
Continuous ventilation mode. The installer needs to consult with the homeowner for the desired
setting on the timer (0 - 60 minutes) and make the adjustments during the installation.
DESCRIPTION
These products are listed by UL under UL file No. E78414.
These products use a sirocco fan driven by a DC motor powered by an integral transformer. The motor is
designed to have long operating life, high dynamic response, higher speed ranges with saving energy.
The grille covering the fan body is a spring-loaded, quick remove type. A damper for preventing air counter
flow is provided. The blower uses a high-capacity sirocco fan developed to reduce the noise level.
The lighting unit is an energy-saving LED lighting device that uses two 7W LED lamps and produces almost
the same illumination as a standard 60W incandescent lamp.
FCC Note: This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interference will not occur in
a particular installation. If this equipment does cause harmful interference to radio or television reception,
which can be determined by turning this product on and off, the user is encouraged to try to correct the
interference by one of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect equipment into outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
Warning: This equipment must be installed by qualified person in accordance with the provided installation
instructions; and all applicable codes and standards. Also, any changes or modifications not expressly
approved by the party responsible for compliance could void the user’s authority to operate this equipment.
DoC Responsible Party:
Panasonic Corporation of North America
Two Riverfront Plaza, Newark, NJ 07102
1-866-292-7299
Customer Call Support:
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
Risk of Fire: Type IC-Inherently Protected, Only Use LED Lamp, Max 7W, Type GU24.
UNPACKING
Unpack and carefully remove the unit from carton.
Refer to the Supplied Accessories list to verify that all parts are present.
4
SUPPLIED ACCESSORIES
Part name
Part name
Appearance
Quantity
1
Appearance
Quantity
2
Installation
instructions
Grille
Flex-Z FastTM bracket(with
4 tapping screws-ST4.2X20)
Warranty
sheet
1
2
1
4
Self-drilling
screw
7W LED lamp
DIMENSIONS
1 1/2 (38)
1 (26)
4
5/8 (116)
Unit: inches (mm)
FV-11-15VKL1
13
FV-11-15VKL1
6
3/8 (163)
7
3/8 (190)
15
14
14
FV-05-11VKSL1
No.
1
No.
8
Part name
Part name
Connector cover
Base PCB box
Pick-A-Flow switch
Lighting unit
LED lamp
Blade
Grille
Lens
FV-05-11VKL1
FV-11-15VKL1
13 (330)
2
3
9
10
11
12
13
14
Motion sensor location
(FV-MSVK1 not included)
4
5
6
Junction box
Adaptor
Fan body
Damper
Multi-Speed module
15 Flex-Z FastTM bracket
3 7/8 (100)
10 1/4 (260)
7
(FV-05-11VKSL1 only,
3 7/8 (100)
other models not included)
WIRING DIAGRAM
Junction box
Fan body
Power switch
Live (Fan)
(114°C Fuse)
Black
DC-Motor
(Power supply)
AC120V 60Hz
Thermally
protected
Neutral
Control switch
White
Red
Multi-Speed module (FV-05-11VKSL1
only, other models not included)
Hi/Low switch: When plug in Multi-Speed module;
On/Off switch: When plug in other Plug ‘N Play modules.
Red wires are non-powered control wires.
Plug ‘N Play module slot
Red
(Red wires are not low voltage (i.e.: 24VAC))
Plug ‘N Play module slot
Green
Earth ground
Green
Power switch
LED
lamp
Live (Light)
Black
(Power supply)
AC120V 60Hz
White
Neutral
FEATURE
[For models of: FV-05-11VKSL1, FV-05-11VKL1, FV-11-15VKL1.]
The WhisperGreen Select Line of ventilation fans employs innovative, state-of-the-art technologies that
provide a number of customizable unique features that lead to improved indoor air quality. Please
read the installation manual first in order to realize the benefits of this customizable, modular fan.
5
FEATURE
CONTINUED
Optimum Ventilation Performance:
Duct length, elbows and other factors increase static pressure which can hinder the performance of most
ventilation fans. This fan utilizes SmartFlow microchip technology that monitors the static pressure in the
system and speeds up or slows down the rpm of the fan depending upon the amount of resistance within
the ducts. This feature allows the fan to perform as rated and avoid potential installation issues.
Outstanding Energy Savings:
The WhisperGreen Select Line of fans are built using DC motor technology. The DC motor is 30% - 70%
more energy efficient than the minimum ENERGY STAR requirements.
Pick-A-Flow Feature
All the WhisperGreen Select base models of fans come with Pick-A-Flow
speed options. The Pick-A-Flow switch on the face of all WhisperGreen
Select fans allows the option to choose 50 – 80 – 110 CFM for the
FV-05-11VKL1, FV-05-11VKSL1 or 110 – 130 – 150 CFM for the
FV-11-15VKL1. These fans can run continuously or intermittently,
depending upon the needs of the owner.
Air volume type (CFM)
Factory setting
(
)
AIR VOLUME CFM
05-11 50
Pick-A-Flow
switch
80 110
FV-05-11VKSL1
FV-05-11VKL1
MODEL
50
80
110
80 CFM
11-15
MODEL110130150
FV-11-15VKL1 110 130 150
130 CFM
INDICATION (PLUG ‘N PLAY FUNCTION DEVICES)
PLUG ‘N PLAY Modular Component Accessories
Sold Separately, Not Included With Base Model Fan
FV-VS15VK1 Multi-Speed module allows the fan to run continuously at lower
speeds to maintain ventilation standards to meet Indoor Air Quality and then
boost up to high speed to meet intermittent needs for ‘Spot’ or ‘Point Source’
exhaust needs. The FV-VS15VK1 Modular Component will operate for both the
Note that there is ONLY
ONE Plug ‘N Play slot to
insert the Multi-Speed
module within the base
model fan. There are
TWO interchangeable
Plug ‘N Play slots to
insert the Condensation
Sensor module, Motion
Sensor module or
FV-05-11VKL1 and the FV-11-15VKL1 matching the appropriate Multi-Speed
setting shown below. The FV-05-11VKSL1 comes with the FV-VS15VK1
Multi-Speed module. It is not necessary to purchase this component.
Note the options on the face of the FV-VS15VK1 Multi-Speed module to
choose appropriate levels of airflow (CFM) and time delay before returning
back to low speed (TIME). Choosing the Pick-A-Flow setting automatically
adjusts the Multi-Speed setting accordingly. As an example,if the Pick-A-Flow
Multi-speed setting is 80 CFM, the Multi-Speed settings adjust automatically
to be 0, 30, 40, 50, 60 or 70CFM at the lower speeds. The fan will ‘boost’
to the 80 CFM speed as the high speed setting. Selecting a particular TIME
option will cause the fan to run for the selected amount of time before
returning to the lower speed setting chosen on the CFM dial.
Nite-GloTM LED Night
Light module within the
base model fan.
Multi-Speed Air volume (CFM)
Pick-A-Flow (CFM)
50
80
110
110
130
150
0
0
0
0
0
0
30
30
30
50
50
50
40
40
40
60
60
60
40
50
50
70
70
70
40
60
60
80
80
80
40
70
70
40
70
80
40
70
90 100
40
70
FV-05-11VKSL1,
FV-05-11VKL1
(plug-in FV-VS15VK1)
90 100 100 100
90 100 110 110
90 100 110 120
FV-11-15VKL1
(plug-in FV-VS15VK1)
Delay Time (min)
45
Factory setting: 20 minutes.
Delay Time position “0“ : Manual wall switch control is 0 minute;
without manual wall switch control is 0.5 minute.
FV-CSVK1 Condensation Sensor module turns the base fan on or boosts
to higher speed when humidity is detected when used in combination
with the FV-VS15VK1. The Condensation Sensor works based on
calculations from the Psychrometric Chart, or combination of Relative
Humidity (RH) and Temperature. This allows the fan to anticipate the
formation of condensation and automatically turn on when needed to
expel humid air. The Condensation Sensor is pre-set to run for 20 minutes;
it will then check the RH and Temperature to detect if the fan needs to
run for another 20 minutes cycle.
6
INDICATION (PLUG ‘N PLAY FUNCTION DEVICES) CONTINUED
PLUG ‘N PLAY Modular Component Accessories
Sold Separately, Not Included With Base Model Fan
FV-MSVK1 Motion Sensor module turns the base fan on or boosts
to higher speed when motion is detected when using in combination
with the FV-VS15VK1. The Motion Sensor is pre-set to run for 20
minutes; it will then re-check for movement; if detected the fan will
run for another 20 minutes cycle. The Motion Sensor detects within
the range shown below.
The distance that motion
can be detected is limited
to 10 feet (3m). The field
of view of the sensor is 90°.
(Room temperature is 25 C).
FV-NLVK1 Nite-GloTM LED Night Light module automatically turns
on when ambient light setting is met. Turn the dial on the
Night Light module to 'DARK' if the fan is in an isolated room
with little ambient light. Turn the dial to 'BRIGHT' if ambient
light is present.
DESCRIPTION FOR NIGHT LIGHT MODULE
Please note that if plan to use the FV-NLVK1 Nite-Glo™ LED Night Light
module, it is recommended to control the fan by the control switch
(see wiring diagram in page 5) with power switch ON, otherwise below
Junction box
Red
Wire
nuts
Red
Fig.a
cases may happen:
1.No power to Night Light module when user turns the fan off using the power switch.
2.The fan may not run if the two red wires are open. (Fig. a)
The fan will turn on with control switch, and turn off 20 minutes (integrated delay function) after
control switch is off.
MOTION (PLUG ‘N PLAY FUNCTION DEVICES)
PLUG ‘N PLAY Modular
Components used in
Combinations
PLUG ‘N PLAY Modular Component Accessories
Sold Separately, Not Included With Base Model Fan
FV-CSVK1 + FV-MSVK1
Turns the fan on for 20 minutes when either
motion or excess humidity is detected.
FV-CSVK1 + FV-VS15VK1
Cycles the fan to high speed from low speed
for the amount of time selected on the Control
Dial based upon detection of excess humidity.
FV-MSVK1 + FV-VS15VK1
Cycles the fan to high speed from low speed
for the amount of time selected on the Control
Dial based upon motion within the room.
Fan
Time delay
operation
Motion
Human
active
operation
FV-CSVK1 only
Fan
ON/OFF
20 minutes
time delay
When motion or
excess humidity is
detected, fan runs the delay time has
at high speed. passed.
Remains running
at high speed until
FV-MSVK1 only
Fan
active
At low
speed
Depend on
FV-VS15VK1 Time
delay setting
FV-CSVK1 + FV-VS15VK1
FV-MSVK1 + FV-VS15VK1
Fan
Hi/Low speed
7
INSTALLATION (PLUG ‘N PLAY FUNCTION DEVICES)
You can purchase the specified Plug ‘N Play devices that are explained on page 6-7 and install them in positions
2
3
,
and
. Position
can only be used with Multi-Speed module (model FV-05-11VKSL1 already have
and can be used for any of the other optional control modules.
this control installed), position
2
3
1. Remove the connector cover from position
, 2 or 3 .
2. Plug in the specified devices to Base PCB box and fix to the slot, till hear the sound installed in place.
Connector
cover
Base PCB box
Slot
2
2
3
3
Clasp
Squeeze tabs on the Clasp to
remove. Squeeze, insert and
release the tabs on Clasp to replace.
INSTALLATION (NEW CONSTRUCTION)
The fan position between joists from 16" to 24"
on center can be adjusted flexibly.
Adaptor
Machine screw
(M4X6)
CAUTION
Please wear gloves during the installation
work as follow.
Fig.1
Fan body
1. Disconnet plug connector from receptacle and
remove adaptor from fan body by removing the
machine screw (M4X6) before installation. (Fig.1)
Joist
IMPORTANT:
Remove the tape from damper and adaptor
before installation. As shown below:
Bend down
4 tabs
Adaptor
Damper
2 Tapping screws
(ST4.2X20)
Fig.2
Tape
Joist
2. Bend down 4 tabs for positioning, install the
Flex-Z FastTM bracket to joists by drilling 2 tapping
screws which have been fixed on it. (Fig.2)
3. Adjust the length of Flex-Z FastTM bracket as the
spacing between joists, and install to joists by
drilling the other 2 tapping screws which have
been fixed on it. (Fig.3)
2 Tapping screws
(ST4.2X20)
Fig.3
Circular duct
Mastic or
approved
foil tape
Conduit
4. Remove junction box cover and secure conduit
or stress relief to junction box knock-out hole.
(Fig.4)
5. Install a circular duct and secure it with clamps,
or ties and seal it with mastic or approved foil tape.
A 4 or 6 inch circular duct is needed to connect to
the relevant part of adaptor. (Fig.4)
6. Install the adaptor to Flex-Z FastTM bracket by
using 2 self-drilling screws. (Fig.4)
Knock-out
hole
Junction box
cover
2 Self-drilling screws
Fig.4
8
INSTALLATION (NEW CONSTRUCTION) CONTINUED
7. Refer to wiring diagram on page 5.
Follow all the local electrical safety
codes as well as the National Electrical
Code (NEC). Using UL approved wire
nuts, connect house power wires to
ventilating fan wires. (Fig.5)
WHITE
BLACK
RED
Conduit
GREEN
Wire nuts
Earth ground
Junction
box
Switch box
L
N
Live (Fan)
Netural
120 VAC
LINE IN
CAUTION
Netural
Earth ground
Two red wires (Connect to a
general manual wall switch)
Mount junction box cover carefully
so that lead wires are not pinched.
Live
(Light)
Fig.5
8. Insert fan body and slide into adaptor assy with some
strength, untill the flange overlaps the Flex-Z FastTM
bracket. Secure the fan body to Flex-Z FastTM bracket
by using 2 self-drilling screws, plug connector to
receptacle and secure the fan body to adaptor by
using machine screw (M4X6). (Fig.6)
Joist
CAUTION
Plug connector
Receptacle
Secure machine screw (M4X6) to the suitable
hole and not touch the Flex-Z FastTM bracket.
Please fix the screw carefully to avoid screw
slip teeth.
Machine
screw
(M4X6)
2 Self-drilling
screws
Fig.6
9. Finish ceiling work. Ceiling hole should be aligned
with the inside edge of the flange. (Fig.7)
10. Remove the tapes from louver and springs before
installation. Remove screw (M4X8) and light cover.
(Fig.8)
Ceiling
Unit: inches (mm)
IMPORTANT:
Replace the sensor cover before the installation
(only for plug-in Motion sensor module FV-MSVK1).
As shown below:
After finishing the ceiling job, fill gap between flange
and ceillng with caulk or other sealant to prevent air
leakage
Keep on pressing the clasps when removing the ornamental cover.
Gloves
Fig.7
Remove screw
(M4X8)
Tapes
Ornamental
cover
Fig.8
Fig.9
Light cover
Insert the sensor cover (attachment for FV-MSVK1) into slot.
Sensor
cover
LED lamp
Secure
screw
(M4X8)
11. Install the LED lamps. (Fig.9)
12. Install light cover. (Fig.10)
13. Insert the grille mounting spring on the wiring side
into the slot and insert the plug connector into the
housing of the lighting unit. (Fig.11 of page 10)
Fig.10
Light cover
9
INSTALLATION (NEW CONSTRUCTION) CONTINUED
Ceiling
Mounting spring
Plug
CAUTION
Motion sensor
connector
(FV-MSVK1 only)
Before turn on the light, make sure the
connector at the correct position. If not,
Clasp
Gloves
Lighting
unit
the lighting can’t work.
The claw of connector must latch the rib
completely.
LED night light
(FV-NLVK1 only)
Rib
Inser plug
connector
14. Plug in the specified devices as your choice
(refer to installation on page 8). Insert the
motion sensor (FV-MSVK1 only) or LED night
light (FV-NLVK1 only) into slot of the grille.
Fix the lead wire into the clasp (Fig.11).
Fig.11
Claw
Ceiling
Grille
15. Adjust Pick-A-Flow switch; if used, adjust the
FV-VS15VK1 Multi-Speed module. (Fig.12)
Refer to indication on page 6.
16. Insert the other mounting spring into the slot
as shown and mount grille to fan body. (Fig.13)
Fig.12
Ceiling
Mounting spring
CAUTION
Gloves
Mount grille carefully so that lead wire of
lighting unit is not pinched.
Grille
Fig.13
INSTALLATION (RETROFIT)
Unit: inches (mm)
Joist
Conduit
Circular duct
WARNING
Disconnect power source before working
on unit.
4 Tapping
screws (ST4.2x20)
1. Remove the existing fan and cut ceiling openning.
Secure the Flex-Z FastTM bracket to joists by drilling
4 tapping screws (ST4.2x20) which have been fixed
on it. Existing ductwork and wiring left in place.
(Fig.14)
(275)
10 7/8
Fig.14
Ceiling (already existed)
Conduit
Circular duct
Mastic or
approved
foil tape
2. Follow the step 1, 4, 5 on page 8 and step 7 on
page 9. (Before connect the circular duct to the
adaptor, should pull down the circular duct from
the ceiling)
Joist
Knock-out
hole
3. Install the adaptor to Flex-Z FastTM bracket by using
2 self-drilling screws. (Fig.15)
Junction box
cover
2 Self-drilling screws
4. Secure the fan body to Flex-Z FastTM bracket by
using 2 self-drilling screws, plug connector to
receptacle and secure the fan body to adaptor
by using machine screw (M4X6). (Fig.16)
Ceiling
Joist
Fig.15
CAUTION
Secure machine screw (M4X6) to the suitable
hole and not touch the Flex-Z FastTM bracket.
Please fix the screw carefully to avoid screw
slip teeth.
Ceiling
Flange
Machine screw (M4X6)
2 Self-drilling screws (Fix the
5. Follow the step 10 to 16 on page 9 to 10.
Fig.16
TM
flange and Flex-Z Fast bracket through the ceiling)
10
MAINTENANCE (CLEANING)
WARNING
Gloves
Disconnect power source before working on unit.
Fig.17
CAUTION
Ceiling
Routine maintenance must be done every year.
Please wear gloves during the cleaning work.
Never use gasoline, benzene, thinner or any other
such chemicals for cleaning the ventilating fan.
Vacuum
cleaner
Do not immerse motor in water when cleaning.
Do not soak resin parts in water over 140 F (60 C).
Fig.18
1. Clean grille. (Don’t put into hot water. Use non-abrasive
kitchen detergent, wipe dry with clean cloth) (Fig.17)
2. The grille should be dry after cleaning.
3. Remove dust and dirt from fan body using a vacuum
cleaner. (Fig.18)
Ceiling
4. Using a cloth dampened with kitchen detergent, remove
any dirt from fan body. Wipe dry with clean cloth. (Fig.19)
5. Reinstall grille.
Gloves
Fig.19
MAINTENANCE
(REPLACEMENT OF LAMP)
Mounting spring
Ceiling
WARNING
Motion sensor
Plug
(FV-MSVK1 only)
connector
Disconnect power source before working on unit.
Clasp
The lamp’s glass is fragile, be careful when the lamp
Gloves
is replaced.
Make sure the temperature of lens and lighting
unit has cooled down before maintenance
(cleaning) or replacement of lamp.
LED night light
(FV-NLVK1 only)
Remove
Grille
CAUTION
Rib
Claw
Lighting
unit
plug
connector
Fig.20
Remove dust and dirt from light cover and lens,
before replace the lamps.
The LED lamps should be replaced as the specified
type. The supplied LED lamps are not intended for
other use.
Remove screw
(M4X8)
1. Remove grille by pulling down one mounting spring
(Fig.20). Remove plug connector then pull down the other.
(For models plug-in FV-MSVK1 or FV-NLVK1: Pull down the
mounting spring that without lead wire passed side, and
remove motion sensor or LED night light as shown in Fig.20)
(Squeeze mounting spring and pull down carefully)
Light cover
Fig.21
Fig.22
2. Remove the screw as shown in step
Remove the light cover as shown in step
of Fig.21.
of Fig.21.
Lens
3. Replace the LED lamps (CX-GU24-H-B, 7W) as shown in
step 1 and step 2 of Fig.22.
4. Install the LED lamps (CX-GU24-H-B, 7W) as shown in
step 1 and step 2 of Fig.9 (Page 9).
LED lamp
5. Install light cover. (Fig.10 of page 9)
11
PRACTICAL GUIDE TO INSTALLATION
Properly insulate the area around the fan to
4 inches or 6 inches roof jack, wall cap,
minimize building heat loss and gain. (Fig.23) or soffit vent with backdraft damper
Loose fill or batt insulation can be placed
directly over the fan housing in the attic.
Mechanically connect duct to termination
and seal with mastic or approved foil
faced tape
Our fans and fan/light combination units do
2-3 ft straight run before elbow
not create excessive heat that is a common
In attic installation,
problem with recessed light fixtures or some
caulk box to drywall
competitor’s fan/light combination. Our
efficient, cool-running motors and our LED
lighting unit do not create enough ambient
heat to be subjected to these limitations.
The ducting from this fan to the outside of
Short piece of flexible duct helps
alignment and absorbs sound.
Clamps plus mastic or approved
foil faced tape at all flex joints
Insulation
Foil tape tightly covers all metal
duct joints (glue PVC joints)
3
the building has a strong effect on the air flow, noise and energy use of the fan. Use the shortest,
straightest duct routing possible for best performance, and avoid installing the fan with smaller
ducts than recommended. Insulation around the ducts can reduce energy loss and inhibit mold
growth. Fans installed with existing ducts may not achieve their rated air flow.
SPECIFICATIONS
Specifications for Base Model fans
Duct
Air volume
Power (W)
Air
direction
Voltage Frequency
(V) (Hz)
Noise
(sones)
Speed
(rpm)
Weight
lb.
diameter at 0.1"WG
Lighting
Model No.
Fan
(inches)
4 or 6
(CFM)
unit
14
<0.3
<0.3
0.4
<0.3
<0.3
0.6
50
80
110
110
130
150
750
825
965
650
680
730
3.6
6.0
FV-05-11VKSL1
FV-05-11VKL1
Exhaust
Exhaust
11.5(5.2)
11.7(5.3)
11.0
8.5
12.0
16.5
14
FV-11-15VKL1
HVI Certified performance based on HVI Procedures 915, 916, and 920.
Specifications for Multi Speed fans
Duct
Air volume
Power (W)
Air
direction
Voltage Frequency
(V) (Hz)
Noise
(sones)
Speed
(rpm)
Weight
lb.
diameter at 0.1"WG
(inches)
Model No.
Lighting
unit
Fan
(CFM)
100
90
80
70
60
50
40
30
0
120
110
100
90
80
70
<0.3
<0.3
<0.3
<0.3
<0.3
<0.3
<0.3
<0.3
8.7
7.0
6.0
4.7
3.9
3.6
2.8
2.5
915
865
825
795
770
750
FV-05-11VKSL1,
FV-05-11VKL1
(Plug-in
FV-VS15VK1)
11.5(5.2)
11.7(5.3)
Exhaust
Exhaust
14
14
730
725
<0.3
<0.3
<0.3
<0.3
<0.3
<0.3
<0.3
<0.3
9.5
8.5
6.9
5.7
5.0
4.3
4.0
3.2
665
650
645
640
635
630
FV-11-15VKL1
(Plug-in
FV-VS15VK1)
60
50
625
620
0
Reference performance based on HVI Procedures 915, 916, and 920. [( ) Standby wattage.]
*
PRODUCT SERVICE
Warning Concerning Removal of Covers. The unit should be serviced by qualified technicians only.
Your product is designed and manufactured to ensure a minimum of maintenance. Should your unit
require service or parts, call Panasonic Call Center at 1-866-292-7299 (USA) or 1-800-669-5165 (Canada).
Panasonic Corporation of North America
Two Riverfront Plaza, Newark, NJ 07102
Panasonic Canada lnc.
5770 Ambler Drive, Mississauga, Ontario L4W 2T3
Panasonic Corporation 2014-2015
Printed in China