10 INSTALLATION
INSTALLATION
Installation Overview
Please read the following installation instructions first after purchasing this product or transporting it to another
location.
Check and choose the
proper location
Level the dryer
Vent the dryer
Connect the Gas dryer
Connect the Electric dryer
Gas dryer
Electric dryer
Plug in the power cord
Installation test
Test run
Product Specifications
The appearance and specifications listed in this manual may vary due to constant product improvements.
DLE3500*/
DLG3501*
DLEX3700* /
DLGX3701*
DLEX3900* /
DLGX3901*
Dryer Models
Description
Non-steam Dryer
Steam Dryer
Steam Dryer
Electrical requirements
Gas requirements
Please refer to the rating label for detailed information.
NG: 4 - 10.5-inch (10.2 - 26.7 cm) WC
LP: 8 - 13-inch (20.4 - 33.1 cm) WC
27” (W) X 30” (D) X 38.7” (H), 51.4” (D with door open)
68.6 cm (W) X 76.1 cm (D) X 98.3 cm (H), 130.5 cm (D with door
open)
Dimensions
Net weight
Gas : 124.7 lb (56.6 kg) - 137.5 lb (62.4 kg)
Electric : 122.0 lb (55.3 kg) - 134.1 lb (60.8 kg)
Steam Cycle
Normal Cycle
-
IEC 7.4 cu.ft. (8 lb/3.6 kg)
Drying capacity
IEC 7.4 cu.ft. (22.5 lb/10.2 kg)
12 INSTALLATION
Clearances
14" max.*
(356 mm)
14" max.*
(356 mm)
18" min.*
(457 mm)
18" min.*
(457 mm)
1"*
30"
5"**
1"*
30"
5"**
(25 mm)
(761mm) (127 mm)
(25 mm)
(761mm) (127 mm)
3"
*
(76 mm)
48 in.2*
(310 cm2
)
0"
(0 mm)
39"
(991 mm)
24 in.2*
(155 cm 2
)
1"
27"
(686 mm)
1"
3"
*
(25 mm)
(25 mm)
(76 mm)
1"
27"
1"
(25 mm)
(686 mm)
(25 mm)
Closet Door
Vent Requirements
Installation Spacing for Recessed Area or Closet Installation
The following clearances are recommended for this dryer. This dryer has been tested for clearances of 1 inch
(2.5 cm) on the sides and rear. Recommended clearances should be considered for the following reasons:
• Additional clearances should be considered for ease of installation and servicing.
• Additional clearances should be considered on all sides of the dryer to reduce noise transfer. For closet
installation, with a door, minimum ventilation openings in the top and bottom of the door are required. Louvered
doors with equivalent ventilation openings are acceptable.
Closet Ventilation Requirements
Closets with doors must have both an upper and lower vent to prevent heat and moisture buildup in the closet.
One upper vent opening with a minimum opening of 48 sq. in. (310 cm2) must be installed no lower than 6 feet
above the floor. One lower vent opening with a minimum opening of 24 sq. in. (155 cm2) must be installed no
more than one foot above the floor. Install vent grills in the door or cut down the door at the top and bottom to
form openings. Louvered doors with equivalent ventilation openings are also acceptable.
NOTE
• There should be at least a little space around the dryer (or any other appliance) to eliminate the transfer of
vibration from one appliance to another. If there is enough vibration, it could cause appliances to make noise or
come into contact, causing paint damage and further increasing noise.
INSTALLATION 13
Installation Spacing for Recessed Area or Closet, with Stacked Washer and
Dryer
6"
*
3"
*
(152 mm)
(76 mm)
48 in.2*
(310 cm2
)
77 ½"
(1968 mm)
24 in.2*
(155 cm 2
)
3"
*
(76 mm)
1"*
(25 mm)
5 ½" **
1"
27"
1"
(140 mm)
(25 mm)
(686 mm)
(25 mm)
* Required spacing
** For side or bottom venting, 2-inch (5.1 cm) of spacing is allowed.
Installation Spacing for Cabinet
For cabinet installation with a door, minimum ventilation openings in the top of the cabinet are required.
* Required spacing
7" *
7" *
(178 mm)
(178 mm)
9" **
(229 mm)
5"*
30"
1"*
1"
27"
1"
(127 mm) (761 mm) (25 mm)
(25 mm) (686 mm) (25 mm)
14 INSTALLATION
Use an adjustable wrench to turn the leveling
feet. Unscrew the legs to raise the dryer or
screw in the legs to lower it. Raise or lower with
the leveling feet until the dryer is level from side
to side and front to back. Make sure that all four
leveling feet are in firm contact with the floor.
Leveling the Dryer
2
WARNING
To reduce the risk of serious injury or death,
follow basic precautions, including the
following:
• Use long-sleeved gloves and safety glasses.
• The appliance is heavy. Two or more people are
required when installing the dryer.
NOTE
• Adjust the leveling feet only as far as necessary
to level the dryer. Extending the leveling feet more
than necessary may cause the dryer to vibrate.
• To ensure that the dryer provides optimal drying
performance, it must be level. To minimize vibration,
noise, and unwanted movement, the floor must be a
perfectly level, solid surface.
Position the dryer in the final location. Place a
level across the top of the dryer.
1
Level
Leveling Feet
• All four leveling feet must rest solidly on the
floor. Gently push on the top corners of the
dryer to make sure that the dryer does not rock
from corner to corner.
NOTE
• If you are installing the dryer on the optional
pedestal, you must use the leveling feet on the
pedestal to level the dryer. The dryer leveling feet
should be fully retracted.
INSTALLATION 15
While supporting the door, remove the 2 screws
on the door hinge. Remove the door.
Reversing the Door
2
3
Tools Required
• Phillips screwdriver
• Large flat blade screwdriver (recommended for
hinge screws if they are tight or your Phillips
screwdriver is worn)
• Small flat blade screwdriver (for lifting out parts)
WARNING
Turn the door upside down and line up the holes
in the hinge with the holes on the opposite side
of the cabinet. Reinstall the door with the screws
removed in step 2.
To reduce the risk of damage to the dryer,
property damage or personal injury, follow
basic precautions, including the following:
• Support the door with a stool or box that fits
under the door, or have an assistant support the
weight of the door.
• Avoid dropping the door.
• Unplug the dryer or turn off power at the main
circuit breaker before beginning door reversal.
• Always reverse the door BEFORE stacking the
dryer on top of the washer.
Door Reversal Instructions
WARNING
The instructions here are for changing the door swing
from a right to a left side hinge. If the door has been
reversed, and it is necessary to change it back, use
care when following these instructions. Some of
the illustrations and the left/right references will be
reversed, and you will need to read the instructions
carefully.
• Be sure to support the weight of the door before
installing the hinge screws.
Install the two decorative screws, the latch,
4
and two latch screws removed in step 1 on the
opposite side from which they were removed.
WARNING
• Be sure to support the weight of the door before
removing the hinge screws.
Open the door and remove the two decorative
screws, two latch screws, and the latch on the
catch side with a screwdriver. Save these for
step 4.
1
Check that the door closes properly.
5
16 INSTALLATION
Preassemble a 4-inch (10.2 cm) elbow to the
next 4-inch (10.2 cm) duct section, and secure
all joints with duct tape. Be sure that the male
end of the elbow faces AWAY from the dryer.
Insert the elbow/duct assembly through the
side opening and press it onto the adapter duct.
Secure it in place with duct tape. Be sure that
the male end of the duct protrudes 1.5 inches
(3.8 cm) to connect the remaining ductwork.
Attach the cover plate to the back of the dryer
with the included screw.
Installing the Side Vent Kit
3
WARNING
To reduce the risk of serious injury, death or
property damage, follow basic precautions,
including the following:
• Use long-sleeved gloves and safety glasses.
• Use a heavy metal vent.
• Do not use plastic or thin foil ducts.
• Clean old ducts before installing this dryer.
Your new dryer is configured to vent to the rear. It can
also vent to the bottom or side (right-side venting is
not available on gas models).
Cover Plate
An adapter kit, part number 383EEL9001B, may be
purchased from your LG retailer. This kit contains
duct components necessary to change the dryer vent
location.
Elbow
1½" (38 mm)
Remove the rear exhaust duct retaining screw.
Pull out the exhaust duct.
1
Option 2: Bottom Venting
Press the adapter duct onto the blower housing
and secure it to the base of the dryer as shown.
2
Retaining Screw
Adapter Duct
Rear Exhaust Duct
Option 1: Side Venting
Bracket
Press the tabs on the knockout and carefully
remove the knockout for the desired vent
2
Insert the 4-inch (10.2 cm) elbow through the
rear opening and press it onto the adapter duct.
Be sure that the male end of the elbow faces
down through the hole in the bottom of the
dryer. Secure it in place with duct tape. Attach
the cover plate to the back of the dryer with the
included screw.
opening (right-side venting is not available on
gas models). Press the adapter duct onto the
blower housing and secure to the base of the
dryer as shown.
3
Adapter Duct
Bracket
Knockout
Cover Plate
Elbow
INSTALLATION 17
To ensure safe and secure installation, please
observe the following instructions.
Stacking the Dryer
Stacking Kit Installation
Make sure the surface of the washer is clean
and dry. Remove paper backing from the tape
on one of the stacking kit side brackets.
1
This stacking kit includes:
• Two (2) side rails
• One (1) front rail
• Four (4) screws
Fit the side bracket to the side of the washer top
as shown in the below illustration. Firmly press
2
Tools Needed for Installation:
the adhesive area of the bracket to the washer
surface. Secure the side bracket to the washer
with a screw on the back side of the bracket.
Repeat steps 1 and 2 to attach the other side
bracket.
• Phillips screwdriver
WARNING
To reduce the risk of electrical shock, fire,
explosion, property damage, serious injury or
death, follow basic precautions, including the
following:
Place the dryer on top of the washer, fitting the
dryer feet into the side brackets as illustrated.
Avoid finger injuries; do not allow fingers to be
pinched between the washer and dryer.
3
• The weight of the dryer and the height of
installation make this stacking procedure too
risky for one person. Two or more people are
required when installing the stacking kit.
Slowly slide the dryer toward the back of the
washer until the side bracket stoppers catch the
dryer feet.
• Do not use the stacking kit with a gas dryer in
potentially unstable conditions such as a mobile
home.
• Place the washer on a solid, stable, level
floor capable of supporting the weight of both
appliances.
• Do not stack the washer on top of the dryer.
• If appliances are already installed, disconnect
them from all power, water, or gas lines and from
draining or venting connections.
Insert the front rail between the bottom of the
dryer and the top of the washer. Push the front
rail toward the back of the washer until it comes
in contact with the side rail stoppers.
4
Install the two remaining screws to secure the
front rail to the side rails.
18 INSTALLATION
Venting the Dryer
WARNING
• Ductwork is not provided with the dryer. You
should obtain the necessary ductwork locally.
The vent hood should have hinged dampers to
prevent backdraft when the dryer is not in use.
WARNING
To reduce the risk of fire or explosion, electric
shock, property damage, injury to persons or
death when using this appliance, follow basic
safety precautions, including the following:
• The total length of flexible metal duct must not
exceed 8 ft. (2.4 m).
• Do not crush or collapse ductwork.
• Do not allow ductwork to rest on or contact sharp
objects.
Ductwork
Maximum
Number
• If connecting to existing ductwork, make sure it is
length of 4-inch
Wall Cap Type
of 90°
suitable and clean before installing the dryer.
diameter rigid
metal duct
Elbows
• Venting must conform to local building codes.
Recommended
0
1
2
3
65 ft.(19.8 m)
55 ft.(16.8 m)
47 ft.(14.3 m)
36 ft.(11.0 m)
• Gas dryers MUST exhaust to the outdoors.
• Use only 4-inch (10.2 cm) rigid, semi-rigid or
flexible metal ductwork inside the dryer cabinet
and for venting outside.
a
• To reduce the risk of fire, combustion, or
accumulation of combustible gases, DO
NOT exhaust dryer air into an enclosed and
unventilated area, such as an attic, wall, ceiling,
crawl space, chimney, gas vent, or concealed
space of a building.
a
4
28 ft.(8.5 m)
a: 4" (10.2 cm)
Use only for short
run installations
0
1
2
3
55 ft.(16.8 m)
47 ft.(14.3 m)
41 ft.(12.5 m)
30 ft.(9.1 m)
• To reduce the risk of fire, DO NOT exhaust the
dryer with plastic or thin foil ducting.
• The exhaust duct must be 4-inch (10.2 cm) in
diameter with no obstructions. The exhaust duct
should be kept as short as possible. Make sure
to clean any old ducts before installing your new
dryer.
b
4
22 ft.(6.7 m)
b: 2.5" (6.35 cm)
• Rigid, semi-rigid or flexible metal ducting is
recommended for use between the dryer and
the wall. All non-rigid metal transition duct must
be UL-listed. Use of other materials for transition
duct could affect drying time.
NOTE
• Deduct 6 ft. (1.8 m) for each additional elbow. Do
not use more than four 90° elbows.
• In Canada, only those foil-type flexible ducts, if any,
specifically identified for use with the appliance by
the manufacturer should be used. In the United
States, only those foil-type flexible ducts, if any,
specifically identified for use with the appliance by
the manufacturer and that comply with the Outline
for Clothes Dryer Transition Duct, Subject 2158A,
should be used.
• DO NOT use sheet metal screws or other
fasteners which extend into the duct that could
catch lint and reduce the efficiency of the
exhaust system. Secure all joints with duct tape.
• Do not exceed the recommended duct length
limitations noted in the chart. Failure to follow
these instructions may result in extended drying
times, fire or death.
INSTALLATION 19
Routing and Connecting Ductwork
Connecting Gas Dryers
NOTE
Follow the guidelines below to maximize drying
performance and reduce lint buildup and
condensation in the ductwork. Ductwork and
fittings are NOT included and must be purchased
separately.
WARNING
To reduce the risk of fire or explosion, electric
shock, property damage, injury to persons,
or death when using this appliance, follow
requirements including the following:
• Use 4-inch (10.2 cm) diameter rigid, semi-rigid or
flexible metal ductwork.
Electrical Requirements for Gas
Models Only
• The exhaust duct run should be as short as
possible.
• Do not, under any circumstances, cut or remove
• Use as few elbow joints as possible.
the third (ground) prong from the power cord.
• The male end of each section of exhaust duct must
point away from the dryer.
• For personal safety, this dryer must be properly
grounded.
• Use duct tape on all duct joints.
• This dryer must be plugged into a 120-VAC,
60-Hz. grounded outlet protected by a
15-ampere fuse or circuit breaker.
• Insulate ductwork that runs through unheated areas
in order to reduce condensation and lint buildup on
duct surfaces.
• Where a standard 2-prong wall outlet is
encountered, it is your personal responsibility
and obligation to have it replaced with a properly
grounded 3-prong wall outlet.
• Incorrect or inadequate exhaust systems are not
covered by the dryer warranty. Dryer failures or
service required because of such exhaust systems
will not be covered by the dryer warranty.
Correct Venting
ELECTRIC SHOCK HAZARD
Failure to follow safety warnings could result
in serious injury
• This dryer is equipped with a three-prong
grounding plug for protection against shock
hazard and should be plugged directly into a
properly grounded three-prong receptacle. Do
not cut or remove the grounding prong from this
plug.
Gas Supply Requirements
• As shipped from the factory, this dryer is
configured for use with natural gas (NG). It can
be converted for use with propane (LP) gas.
Gas pressure must not exceed 8-inch (20.4 cm)
water column for NG, or 13-inch (33.1 cm) water
column for LP.
Incorrect Venting
• A qualified service or gas company technician
must connect the dryer to the gas service.
• Isolate the dryer from the gas supply system by
closing its individual manual shutoff valve during
any pressure testing of the gas supply.
• DO NOT attempt any disassembly of the dryer;
disassembly requires the attention and tools of
an authorized and qualified service technician or
company.
• Securely tighten all gas connections.
• Connect the dryer to the type of gas shown on
the nameplate.
20 INSTALLATION
NOTE
• In the Commonwealth of Massachusetts: This
product must be installed by a licensed plumber
or gas fitter. When using ball-type gas shut off
valves, they shall be T-handle-type. A flexible gas
connector, when used, must not exceed 3 feet.
WARNING
Gas Supply Requirements (continued)
• Supply line requirements: Your laundry room
must have a rigid gas supply line to your dryer.
In the United States, an individual manual shutoff
valve MUST be installed within at least 6 ft. (1.8
m) of the dryer, in accordance with the National
Fuel Gas Code ANSI Z223.1 or Canadian gas
installation code CSA B149.1. A 1/8-inch NPT
pipe plug must be installed.
This dryer is configured from the factory for natural
gas (NG). If the dryer is to be used with propane
(LP) gas, it must be converted by a qualified service
technician.
Make sure that the gas supply to the laundry
room is turned OFF and the dryer is unplugged.
Confirm that the type of gas available in your
1
• If using a rigid pipe, the rigid pipe should be
0.5-inch IPS. If acceptable under local codes and
ordinances and when acceptable to your gas
supplier, 3/8-inch approved tubing may be used
where lengths are less than 20 ft. (6.1 m). Larger
tubing should be used for lengths in excess of 20
ft. (6.1 m).
laundry room is appropriate for the dryer.
Remove the shipping cap from the gas fitting at
the back of the dryer. Be careful not to damage
the threads of the gas connector when removing
the shipping cap.
2
• To prevent contamination of the gas valve,
purge the gas supply of air and sediment before
connecting the gas supply to the dryer. Before
tightening the connection between the gas
supply and the dryer, purge remaining air until
the odor of gas is detected.
Connect the dryer to your laundry room’s gas
supply using a new flexible stainless steel
connector with a 3/8-inch NPT fitting.
3
• DO NOT use an open flame to inspect for gas
leaks. Use a noncorrosive leak detection fluid.
NOTE
• DO NOT use old connectors.
• Use only a new AGA- or CSA-certified
gas supply line with flexible stainless steel
connectors.
Securely tighten all connections between the
4
dryer and your laundry room’s gas supply.
• Use Teflon tape or a pipe-joint compound that is
Turn on your laundry room’s gas supply.
insoluble in propane (LP) gas on all pipe threads.
5
6
Check all pipe connections (both internal and
external) for gas leaks with a noncorrosive leak-
detection fluid.
Connecting the Gas Supply
• Installation and service must be performed by
a qualified installer, service agency, or the gas
supplier.
Proceed to Venting the Dryer.
7
• Use only a new stainless steel flexible connector
and a new AGA-certified connector.
• A gas shutoff valve must be installed within 6 ft.
(1.8 m) of the dryer.
• The dryer is configured for natural gas when
shipped from the factory. Make sure that the
dryer is equipped with the correct burner nozzle
for the type of gas being used (natural gas or
propane gas).
3/8" NPT gas
Connection
1/8" NPT Pipe Plug
Gas Supply Shutoff
Valve
AGA/CSA-Certified
Stainless Steel Flexible
Connector
• If necessary, the correct nozzle (for the LP
nozzle kit, order part number 383EEL3002D)
should be installed by a qualified technician and
the change should be noted on the dryer.
High-Altitude Installations
The BTU rating of this dryer is AGA-certified for
• All connections must be in accordance with
local codes and regulations. Gas dryers MUST
exhaust to the outdoors.
elevations below 10,000 feet.
If your gas dryer is being installed at an elevation
above 10,000 feet, it must be derated by a qualified
technician or gas supplier.
INSTALLATION 21
Connecting Electric Dryers
WARNING
WARNING
• A 4-wire connection is required for all mobile and
manufactured home installations, as well as all
new construction after January 1, 1996. A 4-wire
connection must be used where local codes do
not permit grounding through the neutral wire.
To reduce the risk of fire or explosion, electric
shock, property damage, injury to persons,
or death when using this appliance, follow
requirements including the following:
• Do not modify the plug and internal wire provided
with the dryer.
Electrical Requirements for
Electric Models Only
• The wiring and grounding must conform to
the latest edition of the National Electrical
Code, ANSI/NFPA 70 and all applicable local
regulations. Please contact a qualified electrician
to check your home’s wiring and fuses to ensure
that your home has adequate electrical power to
operate the dryer.
• The dryer should be connected to a 4-hole outlet.
• If the plug does not fit the outlet, a proper outlet
will need to be installed by a qualified electrician.
• Connect the power cord to the terminal block.
Each colored wire should be connected to
the same color screw. Wire color indicated on
manual is connected to the same color screw in
the block.
• Grounding through the neutral conductor is
prohibited for: (1) new branch-circuit installations,
(2) mobile homes, (3) recreational vehicles, and
(4) areas where local codes prohibit grounding
through the neutral conductor.
• This dryer must be connected to a grounded
metal, permanent wiring system, or an
equipment-grounding conductor must be run
with the circuit conductors and connected to the
equipment-grounding terminal or lead on the
dryer.
• This dryer is supplied with the neutral wire
grounded. This white ground wire MUST BE
MOVED to the neutral terminal when a 4-wire
cord is to be used, or where grounding through
the neutral conductor is prohibited.
• The dryer has its own terminal block that must
be connected to a separate 240 VAC, 60-Hertz,
single-phase circuit, fused at 30 amperes (the
circuit must be fused on both sides of the line).
ELECTRICAL SERVICE FOR THE DRYER
SHOULD BE OF THE MAXIMUM RATE
VOLTAGE LISTED ON THE NAMEPLATE. DO
NOT CONNECT THE DRYER TO 110-, 115-, OR
120-VOLT CIRCUIT.
NOTE
• For electrical requirements for mobile or
manufactured homes, see Special Electrical
Requirements.
• If the branch circuit to dryer is 15 ft. (4.5
m) or less in length, use UL (Underwriters
Laboratories) listed No.-10 AWG wire (copper
wire only), or as required by local codes. If over
15 ft. (4.5 m), use UL-listed No.-8 AWG wire
(copper wire only), or as required by local codes.
Allow sufficient slack in wiring so the dryer
can be moved from its normal location when
necessary.
• The power cord (pigtail) connection between the
wall receptacle and the dryer terminal block IS
NOT supplied with the dryer. Type of pigtail and
gauge of wire must conform to local codes and
with instructions on the following pages.
22 INSTALLATION
Tighten all screws securely.
Four-Wire Power Cord
• A 4-wire connection is required for
all mobile and manufactured home
installations, as well as all new
8
9
Reinstall the terminal block access cover.
construction after January 1, 1996.
Hot (Black)
Neutral (White)
• A UL-listed strain relief is required.
Hot (Red)
Ground Screw
• Use a 30-amp, 240-volt, 4-wire,
UL-listed power cord with #10 AWG-
minimum copper conductor and closed
loop or forked terminals with upturned
ends.
White Wire moved from
Ground Screw
Power Cord Ground
Wire
Remove the terminal block access cover on the
upper back of the dryer.
1
Install a UL-listed strain relief into the power
cord through-hole.
2
Thread a 30-amp, 240-volt, 4-wire, UL-listed
power cord with #10 AWG-minimum copper
conductor through the strain relief.
3
Terminal Block
UL-Listed Strain Relief
UL-Listed 4-Wire Power
Cord
Transfer the dryer’s ground wire from behind the
green ground screw to the center screw of the
terminal block.
4
Attach the two hot leads of the power cord to the
outer terminal block screws.
5
Attach the white neutral wire to the center screw
of the terminal block.
6
Attach the power cord ground wire to the green
ground screw.
7
INSTALLATION 23
Attach the two hot leads of the power cord to the
outer terminal block screws.
Four-Wire Direct Wire
• A 4-wire connection is required for
all mobile and manufactured home
installations, as well as all new
6
7
8
9
Attach the white neutral wire to the center screw
of the terminal block.
construction after January 1, 1996.
• A UL-listed strain relief is required.
• Use UL-listed 4-wire #10 AWG-
minimum copper conductor cable.
Allow at least 5 ft. (1.5 m) of wire to
allow for removal and reinstallation of
the dryer.
m
Attach the power cord ground wire to the green
ground screw.
Tighten all screws securely.
10 Reinstall the terminal block access cover.
Remove 5-inch (12.7 cm) of the outer covering
from the wire. Remove 5-inch of insulation from
1
Hot (Black)
Neutral (White)
the ground wire. Cut off approximately 1.5-inch
(3.8 cm) from the other three wires and strip 1
inch (2.5 cm) insulation from each wire. Bend
the ends of the three shorter wires into a hook
shape.
Hot (Red)
Ground Screw
White Wire moved from
Ground Screw
1" (2.5 cm)
Power Cord Ground
Wire
Ground Wire
5" (12.7 cm)
Remove the terminal block access cover on the
upper back of the dryer.
2
Install a UL-listed strain relief into the power
cord through-hole.
3
Thread the 4-wire #10 AWG-minimum copper
power cable prepared in step 1 through the
strain relief.
4
Terminal Block
UL-Listed Strain Relief
UL-Listed 4-Wire Power
Cord
Transfer the dryer’s ground wire from behind the
green ground screw to the center screw of the
terminal block.
5
24 INSTALLATION
Reinstall the terminal block access cover.
Three-Wire Power Cord
• A 3-wire connection is NOT permitted
on new construction after January 1,
1996.
8
Hot (Black)
Neutral (White)
Hot (Red)
Ground Screw
• A UL-listed strain relief is required.
• Use a 30-amp, 240-volt, 3-wire,
UL-listed power cord with #10 AWG-
minimum copper conductor and closed
loop or forked terminals with upturned
ends.
White Wire from Dryer
harness
External Ground Wire (If
required by local codes)
Remove the terminal block access cover on the
upper back of the dryer.
1
Install a UL-listed strain relief into the power
cord through-hole.
2
Thread a 30-amp, 240-volt, 3-wire, UL-listed
power cord with #10 AWG-minimum copper
conductor through the strain relief.
3
Terminal Block
UL-Listed Strain Relief
UL-Listed 3-Wire Power
Cord
Attach the two hot leads (black and red) of the
power cord to the outer terminal block screws.
4
Attach the neutral (white) wire to the center
terminal block screw.
5
Connect the external ground (if required by local
codes) to the green ground screw.
6
Tighten all screws securely.
7
INSTALLATION 25
Attach the neutral (white) wire to the center
terminal block screw.
Three-Wire Direct Wire
• A 3-wire connection is NOT permitted
on new construction after January 1,
1996.
6
7
Connect the external ground (if required by local
codes) to the green ground screw.
• A UL-listed strain relief is required.
• Use UL-listed 3-wire, #10 AWG-
minimum copper conductor cable.
Allow at least 5 ft. (1.5 m) length to
allow for removal and installation of
dryer.
Tighten all screws securely.
8
9
Reinstall the terminal block access cover.
Hot (Black)
Neutral (White)
Hot (Red)
Remove 3.5-inch (8.9 cm) of the outer covering
from the wire. Strip 1 inch (2.5 cm) insulation
from each wire. Bend the ends of the three wires
into a hook shape.
Ground Screw
1
1" (2.5 cm)
White Wire from Dryer
harness
External Ground Wire (If
required by local codes)
Remove the terminal block access cover on the
upper back of the dryer.
2
Install a UL-listed strain relief into the power
cord through-hole.
3
Thread the 3-wire, #10 AWG-minimum copper
conductor power cable prepared in step 1
through the strain relief.
4
Terminal Block
UL-Listed Strain Relief
UL-Listed 3-Wire Power
Cord
Attach the two hot leads (black and red) of the
power cord to the outer terminal block screws.
5
26 INSTALLATION
Special Electrical
Requirements
Final Installation Check
Once you have completed the installation of the dryer
and it is in its final location, confirm proper operation
with the following tests and Installation Test (Duct
Check).
(For Mobile or Manufactured Homes)
• Any installation in a manufactured or mobile
home must comply with the Manufactured Home
Construction and Safety Standards Title 24 CFR,
Part 3280 or Standard CAN/ CSA Z240 MH and
local codes and ordinances. If you are uncertain
whether your proposed installation will comply with
these standards, please contact a service and
installation professional for assistance.
Testing Dryer Heating
GAS MODELS
Close the dryer door and press the Power button
to turn the dryer on. Press the Time Dry and Start/
Pause buttons to start the test. When the dryer starts,
the igniter should ignite the main burner.
• A 4-wire connection is required for all mobile and
manufactured home installations, as well as all new
construction after January 1, 1996.
NOTE
• A gas dryer must be permanently attached to the
floor.
• If all air is not purged from the gas line, the gas
igniter may turn off before the main burner ignites. If
this happens, the igniter will reattempt gas ignition
after approximately two minutes.
• The electrical connection for an electric dryer must
be a 4-wire connection. More detailed information
concerning the electrical connection is provided in
the section Connecting Electric Dryers.
ELECTRIC MODELS
• To reduce the risk of combustion and fire, the dryer
must be vented to the outside.
Close the dryer door and press the Power button
to turn the dryer on. Press the Time Dry and Start/
Pause buttons to start the test. The exhaust air
should be warm after the dryer has been operating
for 3 minutes.
• DO NOT vent the dryer under a manufactured home
or mobile home.
• Electric dryers may be vented to the outside using
the back, left, right, or bottom panel.
• Gas dryers may be vented to the outside using the
back, left, or bottom panel. Gas dryers may not
be vented to the outside using the right side panel
because of the burner housing.
Checking Airflow
Effective dryer operation requires proper airflow.
The adequacy of the airflow can be measured by
evaluating the static pressure. Static pressure in the
exhaust duct can be measured with a manometer,
placed on the exhaust duct approximately 2 ft.
(60.9 cm) from the dryer. Static pressure in the
exhaust duct should not exceed 0.6 inch (1.5 cm).
The dryer should be checked while the dryer is
running with no load.
• The dryer exhaust duct must be affixed securely to
the manufactured or mobile home structure, and the
exhaust duct must be made of a material that will
resist fire and combustion. It is recommended that
you use a rigid, semi-rigid or flexible metal duct.
• DO NOT connect the dryer exhaust duct to any
other duct, vent, chimney, or other exhaust duct.
• Make sure the dryer has adequate access to
outside fresh air to ensure proper operation. The
opening for outside fresh air must be at least
25 sq. in (163 cm²).
Checking Levelness
Once the dryer is in its final location, recheck the
dryer to be sure it is level. Make sure it is level front
to back and side to side, and that all four leveling feet
are in firm contact with the floor.
• It is important that the clearance of the duct from
any combustible construction be at least 2-inch
(5 cm), and when venting the dryer to the outdoors,
the dryer should be installed with a clearance of at
least 1 inch (2.5 cm) at the sides and back of the
dryer.
• Please be aware that venting materials are not
supplied with the dryer. You must obtain the venting
materials necessary for proper installation.
INSTALLATION 27
Press the START/PAUSE button.
Installation Test (Duct Check)
3
4
The dryer will start the test, which will last a
few minutes. The heat will be turned on and the
temperatures in the drum will be measured.
Once you have completed the installation of the
dryer, use this test to make sure the condition of the
exhaust system is adequate for proper operation of
the dryer. This test should be performed to alert you
to any serious problems in the exhaust system of
your home.
Check the display for results.
During the test cycle, monitor the Flow Sense™
display on the control panel. If the Flow Sense™
LED is not turned on, when the cycle ends,
the exhaust system is adequate. If the exhaust
system is severely restricted, the Flow Sense™
LED will be turned on. Other problems may also
be shown with error codes. See the chart below
for error code details and solutions.
• Your dryer features Flow Sense™, an innovative
sensing system that automatically detects
blockages and restrictions in dryer ductwork.
Keeping ductwork clean of lint buildup and free of
restrictions allows clothes to dry faster and reduces
energy use.
NOTE
• The dryer should be cool before starting this test. If
the dryer was warmed up during installation, run the
Air Dry cycle for a few minutes to reduce the interior
temperature.
LED; turned on :
RESTRICTED
The Flow Sense™ LED indicates that the exhaust
system is severely restricted. Have the system
checked immediately, as performance will be poor.
Activating the Installation Test
Remove the drying rack and literature, and
then close the door.
1
Do not load anything in the drum for this test, as
it may affect the accuracy of the results.
End of cycle.
5
At the end of the test cycle,
will display.
The test cycle will end and the dryer will shut off
automatically after a short delay.
Press and hold the Signal and Temp. buttons
and then press the Power button.
2
(On models with a glass touch control panel,
press the Power button then IMMEDIATELY
press and hold the Temp. and Signal buttons.)
This button sequence activates the installation
test. The code
is successful.
will display if the activation
28 INSTALLATION
Check the Duct Condition
Error Codes
If the Flow Sense™ LED is turned on, check the
exhaust system for restrictions and damage. Repair
or replace the exhaust system as needed.
Check the error code before you call for service.
Error
Code
Possible
Causes
Solutions
NOTE
tE1 or
tE2
Temperature
sensor failure.
Turn off the dryer and call
for service.
• When the dryer is first installed, this test should be
performed to alert you to any existing problems with
the exhaust duct in your home. However, since the
test performed during normal operation provides
more accurate information on the condition of the
exhaust duct than the installation test, the number
of bars displayed during the two tests may not be
the same.
Humidity sensor Turn off the dryer and call
failure.
HS
for service.
Check the power supply
or the connection of
the power cord to the
terminal block. Refer to
the Connecting Electric
Dryers section of this
manual for complete
instructions.
Electric dryer
power cord is
not connected
correctly, or
house power
supply is
• Do not interrupt the test cycle, as this could result in
inaccurate results.
• Even if no bars are displayed during the test cycle,
some restrictions may still be present in the exhaust
system. Refer to the Venting the Dryer section
of this manual for complete exhaust system and
venting requirements.
incorrect.
PS,
PF, or
nP
Reset circuit breaker
or replace fuse. Do
not increase the fuse
capacity.
If the problem is a
circuit overload, have it
corrected by a qualified
electrician.
House fuse is
blown, circuit
breaker has
tripped, or
power outage
has occurred.
• Your dryer features Flow Sense™, an innovative
sensing system that automatically detects
blockages and restrictions in the dryer ductwork.
Keeping ductwork clean of lint buildup and free of
restrictions allows clothes to dry faster and reduces
energy use.
INSTALLATION 29
Restricted or Blocked Airflow
Avoid long runs or runs with multiple elbows or
bends.
Too many elbows or
exhaust too long
Excess or crushed
transition duct
Check for blockages and lint buildup.
Lint buildup or blockage
Make sure the ductwork is not crushed or restricted.
Crushed or damaged
exhaust
|