400034-YTG-B-0708
DESCRIPTION
The 13 SEER Series condensing unit is the outdoor part of a
versatile system of air conditioning. It is designed to be cus-
tom-matched with one of UPG’s complete line of evaporator
sections, with each serving a specific function. Matching Air
Handlers are available for upflow, downflow, or horizontal
applications to provide a complete system. Electric Heaters
are available, if required. Add-On coils are available for use
with upflow, downflow, or horizontal furnaces and air han-
dlers.
WARRANTY
TECHNICAL GUIDE
Single Phase Units:
SPLIT-SYSTEM
AIR CONDITIONERS
5-year limited parts warranty.
5-year limited compressor warranty.
FEATURES
13 SEER – R-22
• QUALITY CONDENSER COILS - The coil is constructed
of aluminum microchannel tubing and enhanced aluminum
fins for increased efficiency and corrosion protection.
MODELS:
TCGD12 THRU 60
(1 THRU 5 NOMINAL TONS, 1 PHASE)
• PROTECTED COMPRESSOR - The compressor is inter-
nally protected against high pressure and temperature.
This is accomplished by the simultaneous operation of
high pressure relief valve and a temperature sensor which
protects the compressor if undesirable operating condi-
tions occur. A liquid line filter-drier further protects the
compressor.
• DURABLE FINISH - The cabinet is made of pre-painted
steel. The pre-treated galvanized steel provides a better
paint to steel bond, which resists corrosion and rust creep.
Special primer formulas and matted-textured finish insure
less fading when exposed to sunlight.
• LOWER INSTALLED COST - Installation time and costs
are reduced by easy power and control wiring connec-
tions. Available in sweat connect models only. The unit
contains enough refrigerant for matching indoor coils and
15 feet of interconnecting piping. The small base dimen-
sion means less space is required on the ground or roof.
• TOP DISCHARGE - The warm air from the top mounted
fan is blown up away from the structure and any landscap-
ing. This allows compact location on multi-unit applica-
tions.
• LOW OPERATING SOUND LEVEL - The upward air flow
carries the normal operating noise away from the living
area. The rigid top panel effectively isolates any motor
sound. Isolator mounted compressor and the rippled fins
of the condenser coil muffle the normal fan motor and
compressor operating sounds.
• LOW MAINTENANCE - Long life permanently lubricated
motor-bearings need no annual servicing.
• EASY SERVICE ACCESS - Fully exposed refrigerant con-
nections, and a single panel covering the electrical con-
trols make for easy servicing of the unit.
ISO 9001
Certified Quality
Management System
• SECURED SERVICE VALVES - Secured re-usable ser-
vice valves are provided on both the liquid and vapor
sweat connections for ease of evacuating and charging.
LISTED
• U.L. and C.U.L. listed - approved for outdoor application.
Due to continuous product improvement, specifications
are subject to change without notice.
Certified in accordance with the Unitary Small Equipment cer-
tification program, which is based on ARI Standard 210/240.
Additional rating information can be found at
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
400034-YTG-B-0708
Additional R-22 Charge / Orifice Size for Various Matched Systems
TCGD12
S21S2(H) S21S2(H)
TCGD18
TCGD24
S21S2(H)
TCGD30
TCGD36
TCGD42
TCGD48
TCGD60
S21S2
Outdoor Unit
S21S2(H) S21S2(H) S21S2(H) S21S2(H)
Required Orifice or TXV 1,2
Factory R-22 Charge, lbs-oz
0.041 / 2A 0.052 / 2A 0.059 / 0.061 / 2A 0.065 / 2A 0.073 / 2A 0.081 / 2C 0.084 / 2C 0.096 / 2C
3 - 2
3 - 0
3 - 13
3 - 7
3 - 15
4 - 2
4 - 5
5 - 4
Indoor Coil3,4
Additional Charge, Oz
FC/MC/PC/UC18A2A
FC/MC/PC/UC18B2A
FC/MC/PC/UC24A2A
FC/MC/PC/UC24B2A
FC/MC/PC32A2A
FC/MC/PC35B2A
FC/MC/PC35C2A
FC/MC/PC/UC36A2A
FC/MC/PC/UC36B2A
FC/MC/PC/UC36C2A
FC/MC/PC37A2A
FC/MC/PC43B2C
FC/MC/PC43C2C
FC/MC/PC/UC48C2C
FC/MC/PC/UC48D2C
FC/MC62D2C
0
0
–
–
–
–
–
–
–
0
0
–
–
–
–
–
–
0
–
–
–
–
–
–
–
0
–
–
–
–
–
–
–
–
+3
+4
–
–
–
–
–
–
+3
+4
–
–
–
–
–
–
+3
+4
–
–
–
–
–
–
0
–
–
–
–
–
–
–
0
–
–
–
–
–
–
–
0
–
–
–
–
–
–
–
+7
+12
+4
–
–
–
–
–
–
–
–
0
–
–
–
–
–
–
–
0
–
–
–
–
–
–
–
+5
+2
–
–
–
–
–
–
+5
+2
–
–
–
–
–
–
–
–
0
HC18A2A
0
0
–
–
–
–
–
–
HC30A2A
–
–
0
–
–
–
–
–
HC36B2A
–
–
+3
+4
–
–
–
–
HC42C2C
–
–
–
+12
+4
0
–
–
AHP18B2A
0
0
–
–
–
–
–
–
AHP24B2A
–
0
–
–
–
–
–
–
AHP30B2A
–
–
+3
+4
–
–
–
–
AHP36C2A
–
–
–
+12
+4
–
–
–
AHP42C2C
–
–
–
–
–
–
0
–
–
AHP/SHP60D2C
AV24B2A
–
–
–
–
–
0
–
–
+2
–
–
–
–
–
–
AV36C2A
–
–
+7
+12
+4
–
–
–
AV/SV48D2C
–
–
–
–
–
–
0
–
FC/MC/PC/UC18A3X
FC/MC/PC/UC18B3X
FC/MC/PC/UC24A3X
FC/MC/PC/UC24B3X
FC/MC/PC32A3X
FC/MC/PC35B3X
FC/MC/PC35C3X
FC/MC/PC/UC36A3X
FC/MC/PC/UC36B3X
FC/MC/PC/UC36C3X
FC/MC/PC37A3X
FC/MC/PC43B3X
FC/MC/PC43C3X
FC/MC/PC/UC48C3X
FC/MC/PC/UC48D3X
FC/MC62D3X
41 + 0
52 + 0
–
–
–
–
–
–
41 + 0
52 + 0
–
–
–
–
–
–
–
52 + 2
–
–
–
–
–
–
–
52 + 2
–
–
–
–
–
–
–
–
61 + 3
61 + 3
61 + 3
59 + 0
59 + 0
59 + 0
61 + 7
61 + 7
61 + 7
–
65 + 4
–
–
–
–
–
–
65 + 4
–
–
–
–
–
–
65 + 4
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
65 + 12
73 + 4
73 + 4
73 + 4
73 + 4
73 + 4
–
–
–
–
–
65 + 12
81 + 0
81 + 0
81 + 5
81 + 5
–
–
–
–
–
65 + 12
–
–
–
–
–
84 + 2
–
–
–
–
–
84 + 2
–
–
–
–
–
–
–
–
–
–
–
96 + 0
–
HC18A3X
41 + 0
52 + 0
–
–
–
HC30A3X
–
–
–
–
–
–
59 + 0
61 + 3
61 + 7
–
–
–
–
HC36B3X
65 + 4
65 + 12
–
–
–
HC42C3X
73 + 4
81 + 0
–
For Notes See Page 4.
Johnson Controls Unitary Products
3
400034-YTG-B-0708
Additional R-22 Charge / Orifice Size for Various Matched Systems (Continued)
TCGD12
S21S2(H) S21S2(H)
TCGD18
TCGD24
S21S2(H)
TCGD30
TCGD36
TCGD42
TCGD48
TCGD60
S21S2
Outdoor Unit
S21S2(H) S21S2(H) S21S2(H) S21S2(H)
Required Orifice or TXV 1,2
Factory R-22 Charge, lbs-oz
0.041 / 2A 0.052 / 2A 0.059 / 0.061 / 2A 0.065 / 2A 0.073 / 2A 0.081 / 2C 0.084 / 2C 0.096 / 2C
3 - 2
3 - 0
3 - 13
3 - 7
3 - 15
4 - 2
4 - 5
5 - 4
Indoor Coil3,4
AHP18B3X
AHP24B3X
AHP30B3X
AHP36C3X
AHP42C3X
AHP/SHP60D3X
AV24B3X
Additional Charge, Oz
41 + 0
52 + 0
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
52 + 0
–
–
–
–
–
–
61 + 3
65 + 4
–
–
–
–
–
–
73 + 4
–
–
–
–
–
73 + 4
81 + 0
–
–
–
–
–
–
84 + 0
52 + 2
–
–
–
–
–
AV36C3X
–
61 + 7
65 + 12
73 + 4
–
–
84 + 0
–
AV/SV48D3X
–
–
–
–
–
52 + 0
–
–
–
–
See Cautionbelow
F4FP024
2A + 0
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
61 + 1
–
–
–
–
See Cautionbelow
F4FP036
2A + 2
–
–
–
–
–
–
–
–
–
–
–
–
65 + 0
–
–
–
See Cautionbelow
F4FP040
2A + 0
–
–
–
–
–
–
–
–
–
73 + 0
81 + 5
84 + 2
2C + 2
84 + 0
2C + 0
84 + 0
2C + 0
See Cautionbelow
F5FP048
2A + 0
2C + 5
–
–
–
–
–
–
–
–
See Cautionbelow
F5FP060
See Cautionbelow
F4FV060
FOOTNOTES:
1. For applications requiring a TXV use 1TVM series kit.
2. Approved orifice shipped with outdoor unit.
3. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit
2FD06700224.
4. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of inter-
connecting line tubing.
2. Verify the TXV or orifice and additional charge required for specific evaporator coil in the system using the above table.
3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical
Data Table.
4. For TXV match charge weight needs to be weighed in for specififc coil match and lineset length.
5. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for
evaporator + adder for line set.
Models 12-48 require start kits for TXV matches. Models with “H” on the end of the model number have factory installed start kits.
For models without an “H” refer to tech guide for kit number reference.
F*FP Air Handlers come with a factory installed R-22 TXV. Please note that some models may take a different TXV then what is factory
installed. The proper TXV must be installed for system reliability and performance. Also note, TXV must be removed for orifice match.
4
Johnson Controls Unitary Products
400034-YTG-B-0708
COOLING CAPACITY - With Air Handler Coils
AIR HANDLER
COOLING
NET MBH
COIL
MODEL1
UNIT
MODEL
RATED
CFM
MODEL
W
SEER
EER
TOTAL
SENS.
13 SEER AC WITH MA
MA08B
MA08B
MA08B
MA08B
MA08B
MA12B
MA12B
MA12B
MA14D
MA16C
MA14D
MA16C
MA16C
MA20D
MA20D
17
17
17
17
17
17
17
17
24
21
24
21
21
24
24
FC/MC18B
FC/MC24B
FC/MC35B
FC/MC36B
FC/MC43B
FC/MC35B
FC/MC43B
FC/MC43B
FC/MC48D
FC/MC43C
FC/MC48D
FC/MC48C
FC/MC48C
FC/MC48D
FC/MC62D
600
18.0
18.0
24.0
24.0
24.0
29.0
29.0
35.0
35.0
42.0
42.0
42.0
46.0
46.0
54.0
12.6
12.6
17.2
17.2
17.2
21.2
21.2
24.4
24.4
29.4
29.4
29.4
32.6
32.6
41.5
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
TCGD18S21S2(H)
TCGD24S21S2(H)
600
800
800
800
1000
1000
1200
1200
1400
1400
1400
1600
1600
1800
TCGD30S21S2(H)
TCGD36S21S2(H)
TCGD42S21S2(H)
TCGD48S21S2(H)
TCGD60S21S2
13 SEER AC WITH MV - VARIABLE SPEED
MV12B
MV12B
MV12B
MV12B
MV12B
MV12B
MV12B
MV16C
MV16C
MV16C
MV16C
MV20D
MV12D
MV16C
MV16C
MV20D
MV16C
MV20D
MV20D
17
17
17
17
17
17
17
21
21
21
21
24
24
21
21
24
21
24
24
FC/MC18B
FC/MC24B
FC/MC36B
FC/MC35B
FC/MC43B
FC/MC35B
FC/MC43B
FC/MC35C
FC/MC43C
FC/MC43C
FC/MC48C
FC/MC48D
FC/MC48D
FC/MC43C
FC/MC48C
FC/MC48D
FC/MC48C
FC/MC48D
FC/MC62D
600
600
18.0
18.0
24.0
24.0
24.0
30.0
30.0
30.0
30.0
36.0
36.0
36.0
35.0
42.0
42.0
42.0
45.0
46.0
55.0
13.0
13.0
17.8
17.8
17.8
21.8
21.8
21.8
21.8
25.0
25.2
25.2
25.2
30.0
30.0
30.0
33.2
33.0
41.5
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
13.50
13.50
13.50
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
11.00
11.00
11.00
TCGD18S21S2(H)
TCGD24S21S2(H)
800
800
800
1000
1000
1000
1000
1200
1200
1200
1135
1400
1400
1400
1600
1600
1800
TCGD30S21S2(H)
TCGD36S21S2(H)
TCGD42S21S2(H)
TCGD48S21S2(H)
TCGD60S21S2
13 SEER AC WITH AV / SV - / F*FV VARIABLE SPEED
TCGD18S21S2(H)
TCGD24S21S2(H)
TCGD30S21S2(H)
TCGD36S21S2(H)
AV24
AV36
17
21
21
21
24
24
–
–
–
–
–
–
565
765
18.0
24.0
30.0
35.0
45.0
45.0
13.1
17.9
22.0
25.0
33.2
33.2
14.00
14.00
14.00
14.00
13.50
13.50
12.00
12.00
12.00
12.00
11.00
11.00
AV36
1015
1270
1610
1600
AV36
AV/SV48
F4FV060
TCGD48S21S2(H)
For Notes See Page 6.
Johnson Controls Unitary Products
5
400034-YTG-B-0708
COOLING CAPACITY - With Air Handler Coils (Continued)
AIR HANDLER
COOLING
NET MBH
COIL
MODEL1
UNIT
MODEL
RATED
CFM
MODEL
W
SEER
EER
TOTAL
SENS.
13 SEER AC WITH AHP / SHP / F*FP
TCGD12S21S2(H)
TCGD18S21S2(H)
AHP18
AHP18
17
17
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
450
650
12.0
18.0
18.0
18.0
24.0
24.0
29.0
29.0
29.0
35.0
35.0
42.0
42.0
46.0
46.0
46.0
8.9
13.00
13.00
13.00
1300
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
12.6
12.6
12.6
17.3
17.3
21.2
21.2
21.2
24.4
24.4
29.4
29.4
33.0
33.0
33.0
AHP24
17
650
F4FP024
AHP30
18
600
17
795
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
TCGD24S21S2(H)
TCGD30S21S2(H)
F4FP036
AHP30
21.5
17
860
1015
1015
1000
1235
1235
1485
1455
1600
1690
1680
AHP36
21
F4FP040
AHP36
21.5
21
TCGD36S21S2(H)
TCGD42S21S2(H)
F5FP048
AHP42
24
21
F5FP048
AHP/SHP60
F5FP048
F5FP060
24
24
TCGD48S21S2(H)
24
24
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210.
Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power
input in watt-hours during the same period.
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
— = Not applicable.
CONDENSER ONLY DATA
Air Temp on Condenser
Suct. T/P @ Compr.
Model
75° F
95° F
115° F
Temp.
40
45
50
40
45
50
40
45
50
40
45
50
40
45
50
40
45
50
40
45
50
40
45
50
PSIG
68.6
76.1
84.1
68.6
76.1
84.1
68.6
76.1
84.1
68.6
76.1
84.1
68.6
76.1
84.1
68.6
76.1
84.1
68.6
76.1
84.1
68.6
76.1
84.1
MBH
11.81
12.65
13.55
17.53
18.63
19.80
22.88
24.93
27.12
28.77
30.28
31.89
31.46
36.54
41.95
40.44
45.28
50.44
42.04
46.86
52.00
52.76
59.98
67.69
KW
0.73
0.73
0.74
1.07
1.07
1.08
1.42
1.44
1.47
1.75
1.80
1.86
2.16
2.20
2.24
2.46
2.52
2.59
2.70
2.77
2.85
3.40
3.41
3.41
MBH
8.15
KW
0.85
0.86
0.87
1.29
1.30
1.31
1.70
1.72
1.75
2.01
2.07
2.13
2.37
2.47
2.58
2.83
2.91
3.00
3.03
3.16
3.30
4.04
4.14
4.25
MBH
5.29
KW
1.01
1.02
1.04
1.57
1.59
1.61
2.02
2.07
2.12
2.21
2.31
2.40
2.78
2.85
2.91
3.21
3.30
3.41
3.49
3.60
3.73
5.08
5.15
5.22
TCGD12S21S2(H)
SH 11 / SC 13 @
95 OD Temp
10.15
12.29
15.03
17.25
19.61
19.07
22.25
25.63
23.85
26.56
29.45
18.41
25.84
33.77
28.86
36.10
43.82
26.14
35.10
44.65
46.38
53.35
60.79
7.21
9.26
11.98
14.07
16.30
13.99
17.25
20.72
17.06
19.76
22.64
13.42
18.88
24.71
21.78
27.55
33.70
21.19
27.59
34.43
36.26
42.46
49.07
TCGD18S21S2(H)
SH 11 / SC 10 @
95 OD Temp
TCGD24S21S2(H)
SH 10 / SC 12 @
95 OD Temp
TCGD30S21S2(H)
SH 12 / SC 10 @
95 OD Temp
TCGD36S21S2(H)
SH 10 / SC 11 @
95 OD Temp
TCGD42S21S2(H)
SH 10 / SC 9 @ 95
OD Temp
TCGD48S21S2(H)
SH 10 / SC 12 @
95 OD Temp
TCGD60S21S2
SH 10 / SC 9 @ 95
OD Temp
6
Johnson Controls Unitary Products
400034-YTG-B-0708
COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils
FURNACE**
COIL
COOLING
NET MBH
UNIT MODEL
CFM RANGE
(Min.-max.)
RATED
CFM
W
SEER1
EER
MODEL
TOTAL
12.0
12.0
12.0
18.0
18.0
18.0
18.0
18.0
24.0
24.0
24.0
24.0
24.0
24.0
24.0
24.0
24.0
29.0
29.0
29.0
29.0
29.0
29.0
35.0
35.0
35.0
35.0
35.0
42.0
42.0
42.0
42.0
46.0
46.0
55.0
SENS.
9.1
450 - 750
450 - 750
14,17
14
FC/MC/PC18
HC18
450
450
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
13.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
TCGD12S21S2(H)
9.1
450 - 750
14,17
14,17
14,17
14
UC18
450
9.1
450 - 750
FC/MC/PC18
FC/MC/PC24
HC18
600
12.6
12.6
12.6
12.6
12.6
17.2
17.2
17.2
17.2
17.2
17.2
17.2
17.2
17.2
21.2
21.2
21.2
21.2
21.2
21.2
24.4
24.4
24.4
24.4
24.4
29.4
29.4
29.4
29.4
32.6
32.6
41.0
450 - 750
600
TCGD18S21S2(H)
450 - 750
600
450 - 750
14,17
14,17
14
UC18
600
450 - 750
UC24
600
600 - 1000
600 - 1000
600 - 1000
600 - 1000
600 - 1000
600 - 1000
600 - 1000
600 - 1000
600 - 1000
800 - 1200
800 - 1200
800 - 1200
800 - 1200
800 - 1200
800 - 1200
1000 - 1400
1000 - 1400
1000 - 1400
1000 - 1400
1000 - 1400
1200 - 1600
1200 - 1600
1200 - 1600
1200 - 1600
1400 - 1800
1400 - 1800
1600 - 2000
FC/MC/PC32
FC/MC/PC35
FC/MC/PC36
FC/MC/PC37
FC/MC/PC43
HC30
800
17,21
14,17,21
14
800
800
800
TCGD24S21S2(H)
17,21
14
800
800
17
HC36
800
21
HC42
800
14,17,21
14
UC36
800
FC/MC/PC32
FC/MC/PC35
FC/MC/PC37
FC/MC/PC43
HC36
1000
1000
1000
1000
1000
1000
1200
1200
1200
1200
1200
1400
1400
1400
1400
1550
1550
2000
17,21
14
TCGD30S21S2(H)
17,21
17
21
HC42
14
FC/MC/PC37
FC/MC/PC43
FC/MC/PC48
HC42
17,21
21,24
21
TCGD36S21S2(H)
TCGD42S21S2(H)
21,24
17,21
21,24
21
UC48
FC/MC/PC43
FC/MC/PC48
HC42
21,24
21,24
21,24
24
UC48
FC/MC/PC48
UC48
TCGD48S21S2(H)
TCGD60S21S2
FC/MC62
1. Requires a 2FD06700224 Blower Time Delay unless a standard furnace is equipped with one.
** Refer to Quick Selection Chart for specific furnace match-up.
Johnson Controls Unitary Products
7
400034-YTG-B-0708
1
COOLING CAPACITY - With Variable Speed Furnaces
COOLING
Net MBH
VARIABLE SPEED
FURNACE MODEL
COIL
UNIT MODEL
W
RATED
CFM
MODEL1
SEER
EER
TOTAL
SENS.
13 SEER AC WITH VARIABLE SPEED FURNACES2
PV8*A12
PV9*A12
FC/MC/PC18A
FC/MC/PC18A
FC/MC/PC18B
FC/MC/PC24A
FC/MC/PC24A
FC/MC/PC24B
HC18
14
14
17
14
14
17
14
14
14
14
17
14
14
17
14
14
17
14
14
17
14
14
17
21
21
17
14
14
17
21
21
17
17
17
21
21
21
600
600
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
24.0
24.0
24.0
24.0
24.0
24.0
24.0
24.0
24.0
24.0
24.0
24.0
30.0
30.0
30.0
30.0
30.0
30.0
30.0
30.0
30.0
30.0
30.0
30.0
30.0
30.0
30.0
30.0
30.0
13.0
12.9
13.0
13.0
12.9
13.0
13.0
12.9
17.7
17.7
17.7
17.7
17.7
17.7
17.7
17.7
17.7
17.7
17.7
17.7
21.8
21.8
21.8
21.8
22.0
21.6
21.8
21.8
21.8
21.8
22.0
21.6
21.8
21.6
22.0
22.0
22.0
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
P(C,V)9*B12
PV8*A12
600
600
TCGD18S21S2(H)
PV9*A12
600
P(C,V)9*B12
PV8*A12
600
600
PV9*A12
HC18
600
PV8*A12
FC/MC/PC32A
FC/MC/PC32A
FC/MC/PC35B
FC/MC/PC36A
FC/MC/PC36A
FC/MC/PC36B
FC/MC/PC37A
FC/MC/PC37A
FC/MC/PC43B
HC30
800
PV9*A12
800
P(C,V)9*B12
PV8*A12
800
800
PV9*A12
800
P(C,V)9*B12
PV8*A12
800
TCGD24S21S2(H)
800
PV9*A12
800
P(C,V)9*B12
PV8*A12
800
800
PV9*A12
HC30
800
P(C,V)9*B12
PV8*A12
HC36
800
FC/MC/PC32A
FC/MC/PC32A
FC/MC/PC35B
FC/MC/PC35C
FC/MC/PC35C
FC/MC/PC35B
FC/MC/PC37A
FC/MC/PC37A
FC/MC/PC43B
FC/MC/PC43C
FC/MC/PC43C
FC/MC/PC43B
HC36
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
PV9*A12
PV8*B16
PV8*C16
PV8*C20
P(C,V)9*B12
PV8*A12
PV9*A12
TCGD30S21S2(H)
PV8*B16
PV8*C16
PV8*C20
P(C,V)9*B12
PV8*B16
P(C,V)9*B12
PV8*C16
HC36
HC42
PV8*C20
HC42
P(C,V)9*C16
HC42
For Notes See Page 8.
8
Johnson Controls Unitary Products
400034-YTG-B-0708
COOLING CAPACITY - With Variable Speed Furnaces (Continued)
COOLING
Net MBH
VARIABLE SPEED
FURNACE MODEL
COIL
UNIT MODEL
W
RATED
CFM
MODEL1
SEER
EER
TOTAL
SENS.
13 SEER AC WITH VARIABLE SPEED FURNACES2
PV8*A12
PV9*A12
FC/MC/PC37A
FC/MC/PC37A
FC/MC/PC43B
FC/MC/PC43C
FC/MC/PC43C
FC/MC/PC43B
FC/MC/PC43C
FC/MC/PC43C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48D
HC42
14
14
17
21
21
17
21
21
21
21
21
21
24
21
21
21
21
21
21
21
21
21
24
21
21
21
21
21
21
21
21
24
21
21
24
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1500
1600
1600
1600
1600
1730
1620
1620
35.2
35.2
35.4
35.4
35.6
35.2
35.4
35.4
35.6
35.6
35.4
35.4
35.4
36.0
36.0
35.0
35.0
41.0
42.0
41.0
42.0
42.0
42.0
42.0
41.0
42.0
41.0
46.0
46.0
46.0
46.0
46.0
54.0
54.0
54.0
25.0
25.0
25.0
25.0
25.0
24.8
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
25.0
29.8
29.8
30.0
29.8
29.8
29.8
29.8
30.0
29.6
29.8
32.8
32.8
32.6
32.8
32.8
41.5
41.5
42.0
14.00
14.00
14.00
14.00
14.00
13.50
13.50
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
14.00
13.50
13.50
13.50
13.50
13.50
13.50
13.50
13.50
13.50
13.50
13.25
13.30
13.10
13.10
13.35
13.15
13.15
13.40
12.00
12.00
12.00
12.00
12.00
11.00
11.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
12.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
PV8*B16
PV8*C16
PV8*C20
P(C,V)9*B12
P(C,V)9*C16
P(C,V)9*C20
PV8*C16
TCGD36S21S2(H)
PV8*C20
P(C,V)9*C16
P(C,V)9*C20
P(C,V)9*D20
PV8*C16
PV8*C20
HC42
P(C,V)9*C16
P(C,V)9*C20
PV8*C20
HC42
HC42
FC/MC/PC43C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48D
HC42
PV8*C16
PV8*C20
P(C,V)9*C16
P(C,V)9*C20
P(C,V)9*D20
PV8*C16
TCGD42S21S2(H)
PV8*C20
HC42
P(C,V)9*C16
P(C,V)9*C20
PV8*C16
HC42
HC42
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48D
FC/MC62D
PV8*C20
TCGD48S21S2(H)
TCGD60S21S2
P(C,V)9*C16
P(C,V)9*C20
P(C,V)9*D20
P V8*C20
P(C,V)9*C20
P(C,V)9*D20
FC/MC62D
FC/MC62D
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2. Variable speed furnaces have B.O.D (Blower on Delay) standard.
Johnson Controls Unitary Products
9
400034-YTG-B-0708
1H/1C, manual changeover electronic non-programmable
thermostat.
ACCESSORIES
Refer to Price Manual for specific model numbers.
1H/1C, auto/manual changeover, electronic programmable,
deluxe 7-day, thermostat.
HARD START KIT - Required when using TXV indoor coil.
Also, provides increased starting torque for areas with low
voltage.
1H/1C, auto/manual changeover, electronic programmable.
* For the most current accessory information, refer to the
price book or consult factory.
Model
12
Source 1 Kit numbers
S1-2SA06708606
S1-2SA06708606
S1-2SA06708706
S1-2SA06705906
S1-2SA06708106
S1-2SA06708106
S1-2SA06708806
SOUND POWER RATINGS*
18
UNIT MODEL
(dBA)
72
24
12
18
24
30
36
42
48
60
30
75
36
76
42
75
48
76
75
OFF CYCLE TIMER DELAY - Provides a 5-minute off cycle
to prevent rapid recycling of the compressor.
76
78
ROOM THERMOSTATS - A wide selection of compatible
thermosets are available to provide optimum performance
and features for any installation.
* Rated in accordance with ARI 270-95 Standards.
TYPICAL INSTALLATION
MINIMUM 18” SERVICE
ACCESS CLEARANCE
ON ONE SIDE
THERMOSTAT
60” OVERHEAD
CLEARANCE
WEATHERPROOF
DISCONNECT
SWITCH
NEC CLASS 1 WIRING
6” CLEARANCE
AROUND PERIMETER
TO FURNACE OR
AIR HANDLER
TERMINAL BLOCK
NEC CLASS 2 WIRING
TO INDOOR COIL
NOTE:
ALL OUTDOOR WIRING
MUST BE WEATHERPROOF.
CONTROL
ACCESS
PANEL
SEAL OPENING(S) WITH
PERMAGUM OR EQUIVALENT
TYPICAL FIELD WIRING
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
POWER WIRING
CONTROL WIRING
FACTORY WIRING
POWER WIRING
208/230-1-60
24 VOLT CONTROL WIRING
MINIMUM 18 GA. WIRE
(NEC CLASS 2)
FURNACE OR AIR HANDLER TERMINAL BLOCK
Y R G W
C
*
TERMINAL W IS ONLY
REQUIRED ON SYSTEMS
WITH HEAT.
CONTACTOR
TERMINALS
GND.
LUG
*
COIL
R
Y
G
W
ROOM THERMOSTAT
CONDENSING UNIT
ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.
10
Johnson Controls Unitary Products
400034-YTG-B-0708
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
TCGD12S21S2(H)
INDOOR COIL MODEL NO.
FC/MC/PC18
IDCFM
ID DB (°F) 80
ID WB (°F) 57
450
75
600
75
750
CONDENSING
ENTERING AIR
TEMPERATURE
80
62
80
67
80
72
80
57
80
62
80
67
80
72
80
57
80
62
75
62
80
67
80
72
62
62
T.C.
S.C.
KW
11.3 11.9 12.1 13.1 14.1 11.7 12.4 12.3 13.2 14.1 12.1 12.9 12.6 13.2 14.1
65
75
11.1 10.2 9.1
0.7 0.7 0.7
9.0
0.7
7.2 11.5 11.0 9.6
0.7 0.7 0.7 0.7
9.2
0.7
7.4 11.9 11.8 10.0 9.5
0.7 0.7 0.7 0.7 0.7
7.5
0.7
T.C.
S.C.
KW
11.1 11.7 11.7 12.9 13.8 11.6 12.2 12.0 13.0 13.8 12.0 12.7 12.3 13.1 13.9
10.9 10.4 9.1
0.7 0.7 0.7
9.0
0.7
7.2 11.4 11.2 9.6
0.7 0.7 0.7 0.7
9.4
0.7
7.4 11.8 11.9 10.1 9.8
0.7 0.7 0.7 0.7 0.7
7.7
0.7
T.C.
S.C.
KW
10.9 11.6 11.4 12.6 13.5 11.4 12.1 11.7 12.8 13.6 11.9 12.6 11.9 13.0 13.7
85
10.7 10.6 9.0
0.8 0.8 0.8
9.0
0.8
7.1 11.2 11.3 9.6
0.8 0.8 0.8 0.8
9.6
0.8
7.5 11.7 12.1 10.3 10.1 7.8
0.8 0.8 0.8 0.8 0.8 0.8
T.C.
S.C.
KW
10.7 11.5 11.1 12.3 13.2 11.2 12.0 11.3 12.6 13.3 11.7 12.4 11.6 12.8 13.4
95
10.5 10.8 9.0
0.9 0.9 0.9
9.0
0.9
7.1 11.0 11.5 9.7
0.9 0.9 0.9 0.9
9.7
0.9
7.5 11.5 12.2 10.4 10.4 7.9
0.9 0.9 0.9 0.9 0.9 0.9
T.C.
S.C.
KW
10.0 10.9 10.2 11.5 12.5 10.6 11.4 10.5 11.8 12.7 11.1 11.9 10.9 12.0 12.9
105
115
125
9.8 10.3 8.6
1.0 1.0 1.0
8.8
1.0
6.9 10.4 10.9 9.2
1.0 1.0 1.0 1.0
9.5
1.0
7.3 11.0 11.5 9.9 10.2 7.8
1.0 1.0 1.0 1.0 1.0 1.0
T.C.
S.C.
KW
9.3 10.3 9.3 10.7 11.9 9.9 10.9 9.7 11.0 12.2 10.5 11.4 10.1 11.3 12.4
9.2
1.1
8.6
8.5
1.1
9.9
1.0
9.7
9.4
1.1
8.2
1.1
8.4
7.8
1.1
8.6
1.1
6.7
1.1
9.8 10.3 8.8
1.1 1.1 1.1
9.3
1.1
7.2 10.4 10.8 9.4 10.0 7.6
1.1 1.1 1.1 1.1 1.1 1.1
T.C.
S.C.
KW
9.9 11.2 9.3 10.3 8.9 10.2 11.6 9.9 10.9 9.4 10.5 11.9
8.4
1.2
6.5
1.2
9.2
1.2
9.8
1.1
8.4
1.1
9.1
1.2
7.0
1.2
9.8 10.1 8.9
1.2 1.2 1.1
9.8
1.2
7.5
1.2
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler
Coil
HC18
UC18
–
T.C.
1.00
1.00
0.98
S.C.
1.00
1.00
0.97
KW
1.00
1.00
0.98
–
–
AHP18
Johnson Controls Unitary Products
11
400034-YTG-B-0708
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
TCGD18S21S2(H)
INDOOR COIL MODEL NO.
FC/MC/PC18
IDCFM
ID DB (°F) 80
ID WB (°F) 57
450
75
600
75
750
75
CONDENSING
ENTERING AIR
TEMPERATURE
80
62
80
67
80
72
80
57
80
62
80
67
80
72
80
57
80
62
80
67
80
72
62
62
62
T.C.
S.C.
KW
15.4 17.1 16.7 18.1 18.0 16.2 17.6 17.2 18.2 18.0 17.0 18.2 17.6 18.3 18.0
15.2 13.4 11.4 11.3 8.6 16.0 14.7 12.6 12.0 9.0 16.8 16.0 13.8 12.7 9.5
65
75
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
T.C.
S.C.
KW
14.9 16.6 16.3 17.7 18.0 15.9 17.3 16.8 17.9 18.1 16.9 18.0 17.3 18.2 18.2
14.7 13.4 11.3 11.1 8.5 15.7 14.9 12.7 12.1 9.2 16.7 16.4 14.1 13.1 9.8
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
T.C.
S.C.
KW
14.4 16.1 15.8 17.3 18.0 15.6 17.0 16.3 17.7 18.2 16.8 17.8 16.9 18.1 18.4
14.3 13.5 11.2 11.0 8.5 15.5 15.2 12.8 12.3 9.3 16.6 16.9 14.4 13.6 10.2
85
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
T.C.
S.C.
KW
13.9 15.7 15.4 16.8 17.9 15.3 16.6 15.9 17.4 18.2 16.7 17.5 16.5 18.0 18.5
13.8 13.5 11.1 10.8 8.5 15.2 15.4 12.9 12.4 9.5 16.5 17.3 14.7 14.0 10.5
95
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
T.C.
S.C.
KW
13.2 14.6 14.2 15.9 17.2 14.6 15.7 14.9 16.5 17.5 16.0 16.8 15.5 17.1 17.8
13.1 13.1 10.6 10.6 8.3 14.4 14.8 12.4 12.3 9.3 15.8 16.4 14.2 13.9 10.4
105
115
125
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
T.C.
S.C.
KW
12.5 13.6 13.1 15.0 16.5 13.9 14.9 13.8 15.6 16.8 15.2 16.2 14.6 16.2 17.2
12.4 12.6 10.1 10.3 8.1 13.7 14.1 11.9 12.1 9.2 15.1 15.7 13.7 13.8 10.2
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
T.C.
S.C.
KW
11.8 12.6 12.0 14.2 15.7 13.2 14.1 12.8 14.8 16.1 14.5 15.5 13.6 15.3 16.5
11.7 12.2 9.6 10.1 7.9 13.0 13.5 11.5 11.9 9.0 14.4 14.9 13.3 13.8 10.1
1.7
1.7
1.7
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler
–
Coil
T.C.
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
S.C.
1.00
1.00
1.00
1.00
1.00
1.03
1.00
1.00
1.00
1.03
1.03
KW
1.00
1.00
1.00
1.00
1.00
0.91
1.00
1.00
1.00
0.91
0.91
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
FC/MC/PC/UC24
PV8*A12
FC/MC/PC18A
FC/MC/PC18A
FC/MC/PC18B
FC/MC/PC24A
FC/MC/PC24A
FC/MC/PC24B
HC18
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.03
1.02
1.03
1.03
1.02
1.03
1.03
1.02
0.91
0.91
0.91
0.91
0.91
0.91
0.91
0.91
–
HC18
PV9*A12
–
UC18
P(C,V)9*B12
PV8*A12
AHP18
AHP24
AV24
–
–
PV9*A12
–
P(C,V)9*B12
PV8*A12
F4FP024
MA08B
MA08B
MV12B
MV12B
–
FC/MC18B
FC/MC24B
FC/MC18B
FC/MC24B
PV9*A12
HC18
12
Johnson Controls Unitary Products
400034-YTG-B-0708
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
TCGD24S21S2(H)
INDOOR COIL MODEL NO.
FC/MC/PC36
IDCFM
ID DB (°F) 80
ID WB (°F) 57
600
75
800
75
1000
CONDENSING
ENTERING AIR
TEMPERATURE
80
62
80
67
80
72
80
57
80
62
80
67
80
72
80
57
80
62
75
62
80
67
80
72
62
62
T.C.
S.C.
KW
21.5 24.0 23.5 25.4 26.2 22.7 24.9 24.2 25.8 26.4 23.9 25.8 24.9 26.2 26.7
21.3 19.0 16.1 15.7 12.2 22.5 21.5 17.8 17.3 12.9 23.7 24.1 19.5 18.9 13.6
75
85
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
T.C.
S.C.
KW
20.6 23.0 22.5 24.7 26.0 22.1 24.1 23.3 25.3 26.3 23.5 25.2 24.1 25.8 26.6
20.4 18.7 15.7 15.5 12.1 21.9 21.4 17.6 17.3 13.0 23.3 24.0 19.5 19.1 13.9
1.4
1.4
1.4
1.4
1.5
1.4
1.4
1.4
1.5
1.5
1.4
1.4
1.4
1.5
1.5
T.C.
S.C.
KW
19.7 22.0 21.4 23.9 25.7 21.4 23.3 22.4 24.7 26.1 23.2 24.7 23.3 25.5 26.5
19.5 18.3 15.3 15.3 12.0 21.2 21.2 17.5 17.3 13.1 22.9 24.0 19.6 19.4 14.2
95
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
T.C.
S.C.
KW
18.8 21.0 20.4 23.2 25.5 20.8 22.5 21.4 24.2 26.0 22.8 24.1 22.5 25.2 26.4
18.6 18.0 14.9 15.1 11.9 20.6 21.0 17.3 17.3 13.2 22.6 24.0 19.7 19.6 14.5
105
115
125
1.7
1.7
1.7
1.7
1.8
1.7
1.7
1.7
1.8
1.8
1.8
1.7
1.7
1.8
1.8
T.C.
S.C.
KW
17.9 19.5 18.8 21.7 24.0 19.8 21.2 19.9 22.6 24.5 21.7 22.9 21.0 23.6 25.0
17.8 17.4 14.2 14.6 11.5 19.7 19.9 16.6 16.9 12.9 21.6 22.5 19.1 19.2 14.4
1.9
1.9
1.9
1.9
2.0
1.9
1.9
1.9
2.0
2.0
2.0
2.0
1.9
2.0
2.0
T.C.
S.C.
KW
17.1 18.2 17.3 20.2 22.5 18.9 20.0 18.4 21.1 23.1 20.8 21.8 19.5 22.0 23.6
16.9 16.7 13.5 14.0 11.1 18.8 18.9 16.0 16.4 12.6 20.6 21.0 18.5 18.8 14.2
2.1
2.1
2.1
2.1
2.2
2.1
2.1
2.1
2.1
2.2
2.2
2.2
2.1
2.2
2.2
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler
Coil
T.C.
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
S.C.
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.04
1.00
1.00
1.00
1.00
1.03
1.03
1.03
KW
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.88
1.00
1.00
1.00
1.00
0.88
0.88
0.88
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
–
FC/MC/PC32
FC/MC/PC35
FC/MC/PC37
FC/MC/PC43
HC30
PV8*A12
FC/MC/PC32A
FC/MC/PC32A
FC/MC/PC35B
FC/MC/PC36A
FC/MC/PC36A
FC/MC/PC36B
FC/MC/PC37A
FC/MC/PC37A
FC/MC/PC43B
HC30
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
0.88
0.88
0.88
0.88
0.88
0.88
0.88
0.88
0.88
0.88
0.88
0.88
–
PV9*A12
–
P(C,V)9*B12
PV8*A12
–
–
PV9*A12
–
HC36
P(C,V)9*B12
PV8*A12
–
HC42
–
UC36
PV9*A12
AHP30
AV36
F4FP036
MA08B
MA08B
MA08B
MV12B
MV12B
MV12B
–
P(C,V)9*B12
PV8*A12
–
–
PV9*A12
HC30
FC/MC35B
FC/MC36B
FC/MC43B
FC/MC36B
FC/MC43B
FC/MC35B
P(C,V)9*B12
HC36
Johnson Controls Unitary Products
13
400034-YTG-B-0708
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
TCGD30S21S2(H)
INDOOR COIL MODEL NO.
FC/MC/PC35
IDCFM
ID DB (°F) 80
ID WB (°F) 57
800
75
1000
75
1200
75
CONDENSING
ENTERING AIR
TEMPERATURE
80
62
80
67
80
72
80
57
80
62
80
67
80
72
80
57
80
62
80
67
80
72
62
62
62
T.C.
S.C.
KW
27.8 29.9 29.6 30.6 31.8 29.2 30.1 29.7 30.8 31.8 30.6 30.4 29.8 31.1 31.8
27.2 24.5 20.5 19.0 14.8 28.2 26.1 21.6 20.0 15.4 29.1 27.7 22.6 21.0 15.9
65
75
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.7
T.C.
S.C.
KW
26.2 28.2 27.9 29.7 31.2 28.0 28.9 28.2 30.0 31.2 29.9 29.5 28.6 30.3 31.2
25.7 23.9 20.0 19.1 14.9 27.0 25.8 21.5 20.5 15.7 28.3 27.6 22.9 21.8 16.5
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
T.C.
S.C.
KW
24.6 26.5 26.1 28.8 30.5 26.9 27.6 26.7 29.2 30.6 29.2 28.6 27.3 29.5 30.6
24.1 23.3 19.4 19.2 14.9 25.8 25.4 21.4 20.9 16.0 27.4 27.5 23.3 22.7 17.1
85
1.9
1.9
1.9
2.0
2.0
1.9
1.9
1.9
2.0
2.0
2.0
2.0
1.9
2.0
2.0
T.C.
S.C.
KW
23.0 24.9 24.4 28.0 29.8 25.7 26.3 25.3 28.4 29.9 28.4 27.7 26.1 28.7 30.0
22.6 22.8 18.9 19.3 15.0 24.6 25.1 21.3 21.4 16.3 26.6 27.5 23.7 23.5 17.7
95
2.1
2.1
2.1
2.1
2.2
2.1
2.1
2.1
2.1
2.2
2.1
2.1
2.1
2.1
2.2
T.C.
S.C.
KW
21.5 23.1 22.1 25.6 27.7 24.1 24.5 23.0 26.0 28.0 26.6 26.0 23.9 26.4 28.3
21.2 21.3 17.9 18.5 14.3 23.0 23.4 20.0 20.6 15.8 24.8 25.5 22.1 22.7 17.2
105
115
125
2.3
2.3
2.2
2.3
2.4
2.3
2.3
2.3
2.3
2.4
2.3
2.3
2.3
2.3
2.4
T.C.
S.C.
KW
20.1 21.4 19.8 23.2 25.5 22.5 22.9 20.8 23.7 26.0 24.9 24.3 21.8 24.1 26.5
19.8 19.9 16.9 17.7 13.7 21.4 21.8 18.7 19.8 15.2 23.1 23.6 20.6 22.0 16.8
2.4
2.4
2.4
2.5
2.5
2.5
2.5
2.4
2.5
2.6
2.5
2.5
2.5
2.5
2.6
T.C.
S.C.
KW
18.7 19.7 17.6 20.9 23.4 20.9 21.2 18.6 21.4 24.1 23.1 22.7 19.7 21.9 24.8
18.4 18.6 15.9 16.8 13.1 19.9 20.1 17.5 19.0 14.7 21.4 21.7 19.1 21.3 16.4
2.6
2.6
2.5
2.6
2.7
2.6
2.6
2.6
2.7
2.7
2.7
2.7
2.6
2.7
2.8
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler
–
Coil
T.C.
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.02
1.00
1.00
1.00
1.02
1.02
1.02
1.02
S.C.
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.03
1.00
1.00
1.00
1.02
1.02
1.02
1.02
KW
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.89
1.00
1.00
1.00
0.89
0.89
0.89
0.89
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
FC/MC/PC32
FC/MC/PC37
FC/MC/PC43
HC36
PV8*A12
FC/MC/PC32A
FC/MC/PC32A
FC/MC/PC35B
FC/MC/PC35C
FC/MC/PC35B
FC/MC/PC35C
FC/MC/PC35A
FC/MC/PC37A
FC/MC/PC37A
FC/MC/PC43B
FC/MC/PC43C
FC/MC/PC43C
FC/MC/PC43B
FC/MC/PC43C
FC/MC/PC43C
HC36
1.00
1.00
1.02
1.02
1.02
1.02
1.00
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.00
1.00
1.02
1.02
1.03
1.01
1.00
1.02
1.02
1.02
1.02
1.03
1.01
1.01
1.01
1.02
1.01
1.03
1.03
1.01
1.01
0.91
0.91
0.89
0.89
0.89
0.89
0.91
0.89
0.89
0.89
0.89
0.89
0.89
0.89
0.89
0.89
0.89
0.89
0.89
0.89
0.89
–
PV9*A12
–
PV8*B16
–
PV8*C16
–
HC42
PV8*C20
AHP30
AHP36
AV36
F4FP040
MA12B
MA12B
MV12B
MV16C
MV12B
MV16C
–
P(C,V)9*B12
PV9*A12
–
–
PV8*A12
–
PV9*A12
FC/MC35B
FC/MC43B
FC/MC43B
FC/MC43C
FC/MC35B
FC/MC35C
PV8*B16
PV8*C16
PV8*C20
P(C,V)9*B12
P(C,V)9*C16
P(C,V)9*C20
PV8*B16
P(C,V)9*B12
PV8*C16
HC36
HC42
PV8*C20
HC42
P(C,V)9*C16
P(C,V)9*C20
HC42
HC42
14
Johnson Controls Unitary Products
400034-YTG-B-0708
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
TCGD36S21S2(H)
INDOOR COIL MODEL NO.
FC/MC/PC43
IDCFM
ID DB (°F) 80
ID WB (°F) 57
1000
75
1200
75
1400
CONDENSING
ENTERING AIR
TEMPERATURE
80
62
80
67
80
72
80
57
80
62
80
67
80
72
80
57
80
62
75
62
80
67
80
72
62
62
T.C.
S.C.
KW
35.6 36.1 34.4 37.6 38.5 37.2 37.4 35.5 38.5 38.9 38.9 38.6 36.7 39.4 39.2
32.9 29.4 24.0 23.3 17.9 34.4 31.7 25.4 24.7 18.3 35.9 34.0 26.7 26.2 18.7
65
75
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
T.C.
S.C.
KW
33.6 34.4 32.7 36.1 37.2 36.0 36.0 34.0 37.1 37.6 38.3 37.6 35.2 38.2 38.0
31.2 29.0 23.6 23.0 17.5 33.1 31.4 25.3 24.8 18.1 35.0 33.9 27.0 26.5 18.7
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.3
T.C.
S.C.
KW
31.6 32.6 31.1 34.6 35.9 34.7 34.6 32.4 35.8 36.3 37.8 36.6 33.7 37.0 36.8
29.6 28.6 23.2 22.8 17.1 31.9 31.2 25.3 24.8 17.9 34.2 33.8 27.3 26.8 18.7
85
2.3
2.3
2.3
2.4
2.5
2.4
2.4
2.4
2.4
2.5
2.4
2.4
2.4
2.4
2.5
T.C.
S.C.
KW
29.7 30.9 29.4 33.1 34.5 33.4 33.2 30.8 34.4 35.1 37.2 35.6 32.3 35.8 35.6
27.9 28.2 22.8 22.5 16.6 30.6 30.9 25.2 24.8 17.7 33.3 33.7 27.6 27.1 18.7
95
2.5
2.5
2.5
2.6
2.7
2.5
2.5
2.5
2.6
2.7
2.6
2.6
2.5
2.6
2.7
T.C.
S.C.
KW
28.0 28.6 26.6 30.1 31.4 30.9 30.7 27.9 31.4 32.0 33.9 32.8 29.2 32.6 32.5
25.9 26.3 21.6 21.5 15.6 28.2 28.6 23.8 23.7 16.7 30.4 30.9 26.0 25.9 17.8
105
115
125
2.7
2.7
2.7
2.8
2.9
2.7
2.7
2.7
2.8
2.9
2.8
2.8
2.7
2.8
2.9
T.C.
S.C.
KW
26.3 26.4 23.9 27.3 28.4 28.6 28.3 25.1 28.5 28.9 30.8 30.1 26.3 29.6 29.5
24.0 24.5 20.4 20.4 14.6 25.8 26.3 22.4 22.5 15.8 27.6 28.2 24.4 24.6 17.0
2.9
2.9
2.9
3.0
3.1
2.9
2.9
2.9
3.0
3.1
3.0
3.0
2.9
3.0
3.1
T.C.
S.C.
KW
24.7 24.2 21.2 24.5 25.3 26.2 25.8 22.3 25.5 25.9 27.6 27.4 23.4 26.6 26.5
22.1 22.7 19.3 19.4 13.5 23.4 24.1 21.1 21.4 14.9 24.8 25.5 22.8 23.4 16.2
3.1
3.1
3.1
3.1
3.2
3.1
3.1
3.1
3.2
3.3
3.2
3.2
3.1
3.2
3.3
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler
–
Coil
T.C.
1.00
1.00
1.00
1.00
1.01
1.00
1.00
1.00
1.01
1.01
1.01
1.01
S.C.
1.00
1.00
1.00
1.00
1.02
1.00
1.00
1.00
1.02
1.03
1.03
1.03
KW
1.00
1.00
1.00
1.00
0.92
1.00
1.00
1.00
0.92
0.92
0.92
0.92
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
FC/MC/PC37A
FC/MC/PC/UC48
HC42
PV8*A12
FC/MC/PC37A
FC/MC/PC37A
FC/MC/PC43B
FC/MC/PC43C
FC/MC/PC43C
FC/MC/PC43B
FC/MC/PC43C
FC/MC/PC43C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48D
HC42
1.01
1.01
1.01
1.01
1.01
1.00
1.01
1.01
1.01
1.01
1.01
1.01
1.01
1.01
1.01
1.01
1.01
1.02
1.02
1.02
1.02
1.02
1.01
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
1.02
0.92
0.92
0.92
0.92
0.92
0.91
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.88
0.92
–
PV9*A12
–
PV8*B16
AHP36
AV36
–
PV8*C16
–
PV8*C20
F5FP048
MA12B
MA14D
MV16C
MV16C
MV20D
MV12D
–
P(C,V)9*B12
P(C,V)9*C16
P(C,V)9*C20
PV8*C16
FC/MC43B
FC/MC48D
FC/MC43C
FC/MC48C
FC/MC48D
FC/MC48D
PV8*C20
P(C,V)9*C16
P(C,V)9*C20
P(C,V)9*D20
PV8*C16
PV8*C20
HC42
P(C,V)9*C16
P(C,V)9*C20
HC42
HC42
Johnson Controls Unitary Products
15
400034-YTG-B-0708
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
TCGD42S21S2(H)
INDOOR COIL MODEL NO.
FC/MC/PC43
IDCFM
ID DB (°F) 80
ID WB (°F) 57
1200
75
1400
75
1600
75
CONDENSING
ENTERING AIR
TEMPERATURE
80
62
80
67
80
72
80
57
80
62
80
67
80
72
80
57
80
62
80
67
80
72
62
62
62
T.C.
S.C.
KW
39.7 42.3 41.6 45.1 46.3 41.4 43.5 42.3 45.7 46.7 43.1 44.7 43.0 46.2 47.0
38.2 34.5 28.8 27.9 21.2 39.3 36.8 30.2 29.0 21.5 40.4 39.0 31.6 30.0 21.9
65
75
2.2
2.3
2.2
2.3
2.3
2.2
2.3
2.3
2.3
2.3
2.2
2.3
2.3
2.3
2.3
T.C.
S.C.
KW
38.1 40.6 39.7 43.7 45.1 40.1 42.0 40.5 44.4 45.5 42.0 43.4 41.3 45.2 45.9
36.8 34.3 28.4 27.9 21.0 38.0 36.5 30.0 29.2 21.6 39.3 38.7 31.7 30.6 22.1
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.6
T.C.
S.C.
KW
36.5 38.9 37.7 42.3 43.9 38.7 40.5 38.6 43.2 44.4 40.9 42.0 39.5 44.1 44.9
35.4 34.1 27.9 27.8 20.8 36.8 36.3 29.8 29.5 21.6 38.2 38.5 31.7 31.2 22.4
85
2.7
2.7
2.7
2.7
2.8
2.7
2.7
2.7
2.8
2.8
2.7
2.7
2.7
2.8
2.8
T.C.
S.C.
KW
35.0 37.2 35.8 40.9 42.7 37.4 39.0 36.8 42.0 43.3 39.8 40.7 37.8 43.1 43.8
33.9 33.8 27.4 27.7 20.7 35.5 36.0 29.6 29.8 21.6 37.1 38.2 31.8 31.8 22.6
95
2.9
2.9
2.9
3.0
3.1
2.9
2.9
2.9
3.0
3.1
3.0
3.0
3.0
3.0
3.1
T.C.
S.C.
KW
33.7 34.8 32.6 38.0 39.5 35.6 36.4 33.7 38.9 40.1 37.5 38.0 34.8 39.8 40.7
31.9 31.9 26.1 26.5 19.4 33.2 33.7 28.2 28.5 20.6 34.6 35.5 30.3 30.6 21.7
105
115
125
3.2
3.2
3.2
3.2
3.3
3.2
3.2
3.2
3.2
3.3
3.2
3.2
3.2
3.3
3.3
T.C.
S.C.
KW
32.4 32.5 29.5 35.1 36.5 33.8 33.9 30.7 35.9 37.1 35.1 35.4 31.8 36.6 37.7
29.9 30.0 24.8 25.3 18.2 31.0 31.5 26.8 27.3 19.5 32.1 33.0 28.8 29.4 20.8
3.4
3.4
3.4
3.5
3.6
3.4
3.4
3.4
3.5
3.6
3.5
3.5
3.4
3.5
3.6
T.C.
S.C.
KW
31.1 30.1 26.4 32.3 33.4 32.0 31.4 27.6 32.8 34.0 32.8 32.8 28.9 33.4 34.7
27.9 28.1 23.5 24.1 17.0 28.8 29.2 25.4 26.1 18.5 29.7 30.4 27.4 28.2 20.0
3.7
3.6
3.6
3.7
3.8
3.7
3.7
3.6
3.7
3.8
3.7
3.7
3.7
3.7
3.9
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler
–
Coil
T.C.
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.01
1.01
1.01
S.C.
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.02
1.02
1.02
KW
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.88
0.88
0.88
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
FC/MC/PC/UC48
HC42
PV8*C20
FC/MC/PC43C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48D
HC42
0.98
1.00
0.98
1.00
1.00
1.00
1.00
0.98
1.00
0.98
1.01
1.01
1.02
1.01
1.01
1.01
1.01
1.02
1.00
1.01
0.89
0.91
0.89
0.91
0.91
0.91
0.91
0.89
0.91
0.89
–
PV8*C16
AHP42
F5FP048
MA16C
MA14D
MA16C
MV16C
MV16C
MV20D
–
PV8*C20
–
P(C,V)9*C16
P(C,V)9*C20
P(C,V)9*D20
PV8*C16
FC/MC43C
FC/MC48D
FC/MC48C
FC/MC43C
FC/MC48C
FC/MC48D
PV8*C20
HC42
P(C,V)9*C16
P(C,V)9*C20
HC42
HC42
16
Johnson Controls Unitary Products
400034-YTG-B-0708
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
TCGD48S21S2(H)
INDOOR COIL MODEL NO.
FC/MC/PC48
IDCFM
ID DB (°F) 80
ID WB (°F) 57
1400
75
1600
75
1800
CONDENSING
ENTERING AIR
TEMPERATURE
80
62
80
67
80
72
80
57
80
62
80
67
80
72
80
57
80
62
75
62
80
67
80
72
62
62
T.C.
S.C.
KW
48.0 48.3 46.7 49.9 49.6 49.2 49.1 47.2 50.1 50.1 50.3 49.9 47.6 50.4 50.6
44.6 41.2 33.8 31.6 23.5 45.9 43.6 35.3 32.6 24.3 47.3 46.0 36.9 33.7 25.1
65
75
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.6
T.C.
S.C.
KW
45.5 45.5 43.7 47.8 48.4 46.8 46.5 44.3 48.4 49.0 48.1 47.6 45.0 49.0 49.5
42.2 40.0 32.7 31.3 23.3 43.7 42.3 34.5 32.8 24.2 45.2 44.7 36.3 34.2 25.1
2.7
2.7
2.7
2.8
2.8
2.7
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.9
T.C.
S.C.
KW
43.0 42.6 40.6 45.6 47.3 44.5 44.0 41.5 46.6 47.8 45.9 45.4 42.4 47.6 48.3
39.9 38.8 31.7 31.0 23.1 41.5 41.1 33.7 32.9 24.1 43.1 43.4 35.6 34.8 25.1
85
3.0
3.0
3.0
3.1
3.1
3.0
3.0
3.0
3.1
3.1
3.0
3.0
3.0
3.1
3.2
T.C.
S.C.
KW
40.5 39.8 37.6 43.5 46.1 42.1 41.5 38.7 44.8 46.7 43.7 43.1 39.7 46.2 47.2
37.5 37.5 30.7 30.7 22.9 39.3 39.8 32.8 33.0 24.0 41.0 42.1 34.9 35.4 25.1
95
3.2
3.2
3.2
3.3
3.4
3.2
3.2
3.2
3.3
3.4
3.3
3.3
3.3
3.4
3.5
T.C.
S.C.
KW
37.7 36.8 34.1 40.1 42.6 39.2 38.3 35.1 41.2 43.1 40.6 39.8 36.2 42.4 43.5
34.8 35.0 29.1 29.4 21.4 36.3 36.9 30.9 31.7 22.7 37.9 38.8 32.7 33.9 23.9
105
115
125
3.5
3.5
3.5
3.6
3.7
3.5
3.5
3.5
3.6
3.7
3.6
3.6
3.5
3.6
3.7
T.C.
S.C.
KW
35.0 33.9 30.7 36.8 39.2 36.3 35.3 31.7 37.8 39.6 37.5 36.6 32.7 38.7 40.0
32.1 32.5 27.4 28.1 20.0 33.5 34.1 29.0 30.3 21.4 34.9 35.6 30.6 32.6 22.7
3.7
3.8
3.7
3.8
4.0
3.8
3.8
3.7
3.8
4.0
3.8
3.8
3.8
3.9
4.0
T.C.
S.C.
KW
32.3 31.0 27.4 33.5 35.8 33.4 32.2 28.3 34.3 36.1 34.5 33.5 29.3 35.0 36.5
29.5 30.0 25.8 26.8 18.6 30.7 31.2 27.1 29.0 20.1 31.9 32.5 28.4 31.2 21.5
4.0
4.0
4.0
4.1
4.2
4.0
4.1
4.0
4.1
4.2
4.1
4.1
4.0
4.1
4.3
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler
–
Coil
T.C.
1.00
1.00
0.98
1.00
1.00
0.98
1.00
1.00
0.98
1.00
S.C.
1.00
1.01
1.01
1.00
1.00
1.01
1.00
1.00
1.01
1.01
KW
1.00
1.00
0.89
1.00
1.00
0.89
1.00
1.00
0.89
0.91
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
UC48
PV8*C16
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48C
FC/MC/PC48D
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.91
0.91
1.00
1.00
0.91
AHP/SHP60
AV/SV48
F5FP048
F5FP060
F4FV060
MA16C
–
PV8*C20
–
P(C,V)9*C16
P(C,V)9*C20
P(C,V)9*D20
–
–
–
FC/MC48C
FC/MC48D
FC/MC48C
FC/MC48D
MA20D
MV16C
MV20D
Johnson Controls Unitary Products
17
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
TCGD60S21S2
INDOOR COIL MODEL NO.
FC/MC62
IDCFM
ID DB (°F) 80
ID WB (°F) 57
1750
75
2000
75
2250
75
CONDENSING
ENTERING AIR
TEMPERATURE
80
62
80
67
80
72
80
57
80
62
80
67
80
72
80
57
80
62
80
67
80
72
62
62
62
T.C.
S.C.
KW
57.5 58.5 57.1 62.2 60.7 59.2 60.1 58.2 63.4 62.8 61.0 61.6 59.3 64.5 64.9
54.4 51.6 42.7 41.3 29.2 55.9 54.9 45.2 43.3 30.4 57.3 58.1 47.6 45.4 31.6
65
75
2.9
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.1
3.0
3.0
3.0
3.0
3.1
T.C.
S.C.
KW
55.4 56.6 54.6 60.1 59.4 57.4 58.3 55.7 61.2 60.1 59.4 60.0 56.8 62.3 60.8
52.4 50.5 41.7 40.7 28.8 53.9 53.4 44.2 43.0 30.0 55.5 56.2 46.7 45.3 31.2
3.3
3.3
3.3
3.4
3.5
3.4
3.4
3.4
3.4
3.5
3.4
3.4
3.4
3.4
3.5
T.C.
S.C.
KW
53.3 54.7 52.1 58.0 58.1 55.5 56.6 53.1 59.0 57.3 57.7 58.4 54.2 60.1 56.6
50.3 49.4 40.6 40.1 28.4 52.0 51.9 43.2 42.6 29.6 53.7 54.4 45.8 45.1 30.8
85
3.7
3.7
3.7
3.8
3.9
3.8
3.8
3.7
3.8
3.9
3.8
3.8
3.8
3.8
3.9
T.C.
S.C.
KW
51.3 52.7 49.6 56.0 56.7 53.7 54.8 50.6 56.9 54.6 56.1 56.9 51.6 57.8 52.5
48.2 48.3 39.5 39.6 28.0 50.0 50.4 42.2 42.3 29.2 51.8 52.6 44.9 45.0 30.4
95
4.1
4.1
4.1
4.2
4.3
4.2
4.1
4.1
4.2
4.3
4.2
4.2
4.2
4.3
4.4
T.C.
S.C.
KW
49.1 49.5 45.8 51.8 52.6 51.3 51.4 46.8 52.7 50.5 53.6 53.2 47.8 53.6 48.4
45.2 45.4 37.8 38.0 26.8 46.9 47.3 40.3 40.6 28.1 48.5 49.2 42.8 43.3 29.4
105
115
125
4.6
4.6
4.6
4.7
4.9
4.7
4.7
4.7
4.7
4.9
4.7
4.7
4.7
4.8
4.9
T.C.
S.C.
KW
47.1 46.4 42.2 47.8 48.5 49.1 48.1 43.2 48.7 46.5 51.1 49.7 44.2 49.5 44.5
42.3 42.6 36.2 36.4 25.8 43.8 44.3 38.5 39.0 27.1 45.3 45.9 40.7 41.6 28.5
5.2
5.2
5.1
5.2
5.4
5.2
5.2
5.2
5.3
5.4
5.2
5.2
5.2
5.3
5.4
T.C.
S.C.
KW
45.0 43.3 38.6 43.8 44.5 46.9 44.8 39.6 44.6 42.5 48.7 46.2 40.5 45.4 40.6
39.4 39.9 34.5 34.9 24.7 40.8 41.2 36.6 37.4 26.1 42.1 42.6 38.7 40.0 27.5
5.7
5.7
5.6
5.7
5.9
5.7
5.7
5.7
5.8
5.9
5.7
5.7
5.7
5.8
5.9
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Air Handler
MA20D
Coil
T.C.
1.00
1.00
S.C.
1.01
1.01
KW
1.00
1.00
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
FC/MC62D
FC/MC62D
PV8*C20
FC/MC62D
FC/MC62D
FC/MC62D
1.00
0.98
1.00
1.01
1.01
1.02
1.00
0.98
1.00
MV20D
P(C,V)9*C20
P(C,V)9*D20