036-21105-004 Rev. A (0902)
DESCRIPTION
®
The HDA Series condensing unit is the outdoor part of a ver-
satile system of air conditioning. It is designed to be custom-
matched with one of UPG's complete line of evaporator sec-
tions, each designed to serve a specific function. Matching
Air Handlers are available for upflow, downflow or horizontal
application to provide a complete system. Electric heaters are
available if required.
TECHNICAL GUIDE
STELLAR 2000
FEATURES
• QUALITY CONDENSER COILS - The coil is constructed
of enhanced copper tube and aluminum fins.
• COIL PROTECTION - Coils are protected from damage by
a polymer mesh applied between the coil face, and a PVC
coated steel coil guard.
SPLIT-SYSTEM AIR CONDITIONERS
10 SEER 50 HZ
• PROTECTED COMPRESSOR - The compressor is inter-
nally protected against high pressure and temperature.
This is accomplished by the simultaneous operation of
high pressure relief valve and a temperature sensor which
protect the compressor if undesirable operating conditions
occur.
MODELS: H*DA012 THRU H*DA076
(1 & 3 PHASE)
(1 THRU 7.5 NOMINAL TONS)
• DURABLE FINISH - Cabinet is made of pre-painted steel.
The pre-treated flat galvanized steel provides a better
paint to steel bond, which resists corrosion and rust creep.
Special primer formulas and glossy earth tone finish insure
less fading when exposed to sunlight.
• LOWER INSTALLED COST - Installation time and costs
are reduced by easy power and control wiring connec-
tions. Discharge line heat exchanger knockouts are pro-
vided, if required. Both quick connect and sweat connect
models are available. Both service valves are firmly affixed
to the unit. The sweat unit contains enough refrigerant for
matching indoor coils and 15 feet of interconnecting pip-
ing. The small base dimension means less space is
required on the ground or roof.
• TOP DISCHARGE - The warm air from the top mounted
fan is blown up away from the structure and any landscap-
ing. This allows compact location on multi-unit applica-
tions.
• LOW OPERATING SOUND LEVEL - The upward air flow
carries the normal operating noise up away from the living
area. The rigid top panel effectively isolates any motor
sound. Isolator mounted compressor and the rippled fins
of the condenser coil muffle the normal fan motor and
compressor operating sounds.
• LOW MAINTENANCE - Long life permanently lubricated
motor- bearings need no annual servicing.
• EASY SERVICE ACCESS - Fully exposed refrigerant con-
nections and a single panel covering the electrical controls
make servicing easy.
Due to continuous product improvement, specifica-
tions are subject to change without notice.
up-to-date technical information.
• SECURED SERVICE VALVES - Secured re-usable ser-
vice valves are provided on both the liquid and vapor
sweat connections for ease of evacuating and charging.
• FACTORY TESTED - to verify system operation and con-
trol functioning before shipment.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
036-21105-004 Rev. A (0902)
COOLING PERFORMANCE
AIR TEMP ON CONDENSER
95°F 115°F
MBH
SUCT.T/P @ COMPR.
MODEL
75 °F
125°F
TEMP
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
PSIG
61.5
68.5
76.0
84.0
61.5
68.5
76.0
84.0
61.5
68.5
76.0
84.0
61.5
68.5
76.0
84.0
61.5
68.5
76.0
84.0
61.5
68.5
76.0
84.0
61.5
68.5
76.0
84.0
61.5
68.5
76.0
84.0
MBH
13.0
14.5
16.1
17.7
18.7
20.8
22.9
25.2
21.9
24.3
26.7
29.3
27.6
30.4
33.3
36.3
33.6
37.3
40.9
44.8
46.7
51.7
56.8
62
KW
1.31
1.36
1.41
1.44
1.83
1.90
1.97
2.05
2.34
2.41
2.47
2.53
2.64
2.71
2.78
2.85
3.07
3.09
3.23
3.37
3.87
4.07
4.28
4.49
5.16
5.33
5.51
5.71
5.55
5.69
5.84
5.99
MBH
10.9
12.3
13.7
15.2
15.6
17.6
19.6
21.8
18.7
20.9
23.2
25.6
23.9
26.5
29.2
31.9
28.8
32.1
35.2
39.1
39.1
43.5
48
KW
1.41
1.49
1.54
1.58
1.99
2.07
2.17
2.27
2.54
2.63
2.73
2.82
2.88
2.99
3.08
3.18
3.43
3.48
3.69
3.85
4.82
5.08
5.34
5.6
KW
1.53
1.62
1.69
1.74
2.09
2.20
2.31
2.43
2.71
2.84
2.97
3.10
3.11
3.24
3.37
3.49
3.82
3.88
4.13
4.35
57.8
6.14
6.51
6.89
7.25
7.41
7.58
7.76
7.98
8.14
8.30
8.48
MBH
8.0
9.1
KW
1.59
1.69
1.76
1.82
2.13
2.24
2.37
2.49
2.77
2.91
3.06
3.20
3.20
3.34
3.48
3.62
4.01
4.08
4.36
4.60
6.39
6.83
7.28
7.73
7.92
8.08
8.25
8.43
8.82
8.98
9.15
9.32
9.0
10.2
11.3
12.4
12.5
14.3
16.2
18.3
15.6
17.6
19.7
21.9
20.2
22.5
25.0
27.5
24.0
26.9
30.2
33.3
31.9
35.7
39.6
43.7
43.4
47.5
51.8
56.1
58.3
64.3
70.5
76.9
H3DA012
H3DA018
H3DA024
H3DA030
H3DA036
H3DA048
H3DA060
10.1
11.1
10.9
12.6
14.5
16.5
14.0
15.9
18.0
20.0
18.3
20.5
22.8
25.5
21.6
24.3
27.5
30.4
28.3
31.8
35.4
39.2
40.8
44.7
48.7
52.9
54.4
60.2
66.2
72.4
52.7
48.7
53.1
57.8
62.5
66.2
72.5
79.1
86.1
53.8
58.9
64.1
69.6
73.9
80.7
87.7
95.1
6.09
6.25
6.43
6.61
6.60
6.75
6.91
7.07
H3DA076
NOTES:
1. For condensing unit only. Does not include effect of evaporator motor power or heat.
2. Performance based on 15° superheat and 15° sub-cooling at condensing unit.
a. Increase capacity 1% for each 2° increase in sub-cooling.
b. Decrease capacity 1% for each 2° decrease in sub-cooling.
3. Sub-cooling in excess of 20° may result in excessively high condensing temperature with air on condenser above 115°F.
Maximum recommended condensing temperature is 140°F.
ACCESSORIES
SOUND RATINGS
Refer to Price Manual for specific model numbers.
Off Cycle Timer - Provides a 5 minute off cycle to prevent
rapid recycling of the compressor.
Room Thermostats - A wide selection of matching thermo-
stats is available to provide features required for any installa-
tion.
Start Assist Kit - Provides increased starting torque for
areas with low voltage conditions.
Compressor Blanket - Designed to further reduce the nor-
mal operating sounds of H3DA units.
H*DA
MODEL
SOUND RATING
DECIBELS
H3DA012
H3DA018
H3DA024
H3DA030
H3DA036
H3DA048
H3DA060
H3DA076
7.8
7.8
7.8
7.8
7.8
8.0
8.2
8.2
Unitary Products Group
3
036-21105-004 Rev. A (0902)
COOLING CAPACITY
AIR HANDLER
COOLING
NET MBH
COIL MODEL
RATED
CFM
UNIT MODEL
MODEL
SEER
(EER)
ELECTRIC HEAT KW
W
KW
TOTAL
SENS.
1 & 3 PHASE HDA WITH N1AH AIR HANDLER & G2FD COILS
H3DA018S78
N1AHB12
N1AHB12
N1AHB12
2,5,7.5,10
17
G2FD024S17
G2FD024S17
G2FD030S17
G2FD030S17
G2FD036S17
G2FD036S17
G2FD046S17
G2FD048S21
G2FD048S24
G2FD060S24
G2FD060S24
650
800
20.4
23.5
24.0
30.0
30.2
34.2
-
14.9
17.1
17.5
21.9
22.0
24.9
-
2.23
3.07
2.79
3.32
3.35
4.05
-
9.60
8.90
9.00
9.70
9.70
9.00
-
H3DA024S78
2,5,7.5,10
17
800
5,7.5,10,15,18
-
17
17
17
21
21
24
24
24
1025
1025
1200
1200
1550
1550
1550
1800
H3DA0308S78
H3DA036S50
N1AHB12
N1AHB12
5,7.5,10,15,18
N1AHC16
N1AHD20
N1AHD20
N1AHD20
5,7.5,10,15,20
7.5,10,15,20,25,30
7.5,10,15,20,25,30
7.5,10,15,20,25,30
46.2
46.2
47.8
60.0
34.7
34.7
35.9
43.9
5.06
5.06
5.16
6.45
9.90
9.90
9.90
9.40
H3DA048S50
H3DA060S50
1 & 3 PHASE HDA WITH F2RP SINGLE PIECE AIR HANDLERS
H3DA018S78
H3DA024S78
H3DA030S78
H3DA036S50
H3DA048S50
H3DA060S50
2,5,7.5,10
2,5,7.5,10
18
18
-
-
-
-
-
-
650
850
16.9
21.0
28.0
35.3
42.9
54.1
12.5
15.5
20.8
23.8
31.7
24.5
2.0
2.5
3.2
4.2
5.3
6.4
-
F2RP024
F2RP024
F2RP036
F2RP036
F2RP048
F2RP060
-
5,7.5,10,15,19
5,7.5,10,15,19
10,15,20,25
10,15,20,25
21.5
21.5
24
1090
1090
1490
1735
-
8.5
8.2
8.4
24
3 PHASE HDA WITH COMMERCIAL BELT DRIVE K*EU EVAPORATOR BLOWER UNIT
H3DA060S50
H3DA076S50
K2EU060
K5EU090
10,16,25
36
52
-
-
2000
2550
55.5
74.6
39.5
53.7
6.30
7.61
10.00
9.80
10,16,26,36
MBH based on 80°F entering air temperature, 50% RH, and rated air flow.
KW includes compressor, outdoor fan and indoor blower motor watts. Add-on coils include 365 watts/1000 CFM for blower motor.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTUs during a normal annual usage period for cooling divided
by the total electric power input inwatt-hours during the same period.
(EER) = Energy Efficiency Ratio-steady state total BTUH/electric power input.
4
Unitary Products Group
036-21105-004 Rev. A (0902)
TYPICAL FIELD WIRING
POWER
WIRING
CONTROL
WIRING
GROUND
LUG
LOW VOLTAGE
JUNCTION BOX
ALL OUTDOOR WIRING MUST BE WEATHERPROOF.
USE COPPER CONDUCTORS ONLY.
TYPICAL FIELD WIRING - 1 PHASE
POWER WIRING
CONTROL WIRING
FACTORY WIRING
POWER WIRING
24 VOLT CONTROL WIRING
MINIMUM 18GA. WIRE
(NEC CLASS 2)
230-1-50
FURNACE OR AIR HANDLER TERMINAL BLOCK
Y R G W
C
*
TERMINAL W IS
ONLY REQUIRED
ON SYSTEMS
WITH HEAT.
CONTACTOR
TERMINALS
GND.
LUG
*
COIL
Y
R
G
W
ROOM THERMOSTAT
CONDENSING UNIT
TYPICAL FIELD WIRING - 3 PHASE
POWER WIRING
380/415-3-50
POWER WIRING
CONTROL WIRING
FACTORY WIRING
24 VOLT CONTROL WIRING
MINIMUM 18GA. WIRE
(NEC CLASS 2)
FURNACE OR AIR HANDLER TERMINAL BLOCK
C
Y R G W
TERMINAL W IS
ONLY REQUIRED
ON SYSTEMS
WITH HEAT.
*
CONTACTOR
TERMINALS
GND.
LUG
*
COIL
Y
R
G
W
ROOM THERMOSTAT
CONDENSING UNIT
Unitary Products Group
5
036-21105-004 Rev. A (0902)
TYPICAL INSTALLATION
THERMOSTAT
WEATHERPROOF
DISCONNECT
SWITCH
TO
POWER
SUPPLY
48” OVERHEAD
CLEARANCE
TO
INDOOR
BLOWER
NEC
CLASS 1
WIRING
12” REAR AND
SIDES
NEC
CLASS 2
WIRING
TO COIL
24” SERVICE ACCESS
CLEARANCE
NOTE: All outdoor wiring must be weatherproof
Seal opening(s) with permagum
or equivalent
MATCHING INDOOR COMPONENTS
ADD-ON COILS - FOR FURNACE APPLICATIONS
G2FD*
MULTI-POSITION
(UPFLOW, HORIZONTAL
AND DOWNFLOW)
AIR HANDLERS - FOR NON-FURNACE APPLICATIONS
N1AH
MODULAR BLOWER
(UPFLOW, HORIZONTAL
AND DOWNFLOW)
K*EU060,090
LIGHT COMMERCIAL
APPLICATIONS
F2RP
FAN COIL UNITS
(UPFLOW, HORIZONTAL)
G2FD
COIL
6
Unitary Products Group
036-21105-004 Rev. A (0902)
NOTES
Unitary Products Group
7
Subject to change without notice. Printed in U.S.A.
036-21105-004 Rev. A (0902)
Copyright © by York International Corp. 2002. All rights reserved.
Supersedes: 036-21105-003 Rev. C (0901)
Unitary
Product
Group
5005
York
Drive
Norman
OK