246695-YTG-C-0708  
TECHNICAL  
GUIDE  
®
DESCRIPTION  
®
®
YORK Predator Magnum is a convertible single package unit  
with a common footprint cabinet and common roof curb for 12-  
1/2 ton models. All units have two compressors with indepen-  
dent refrigeration circuits to provide 2 stages of cooling. The  
units were designed for light commercial applications and can  
be easily installed on a roof curb, slab, or frame.  
MAGNUM  
ULTRA HIGH EFFICIENCY  
®
SINGLE PACKAGE AIR CONDITIONERS AND  
SINGLE PACKAGE GAS/ELECTRIC UNITS  
All Predator Magnum units are self-contained and assembled  
on rigid full perimeter base rails allowing for 3-way forklift  
access and overhead rigging. Every unit is completely charged,  
wired, piped, and tested at the factory to provide a quick and  
easy field installation.  
DJ 150  
12-1/2 NOMINAL TONS  
11.35 EER  
All units are convertible between side and down airflow. Inde-  
pendent economizer designs are used on side and down dis-  
charge applications, as well as all tonnage sizes.  
®
Predator Magnum units are available in the following configu-  
rations: cooling only, cooling with electric heat, and cooling with  
gas heat. Electric heaters are available as factory-installed  
options or field-installed accessories.  
Tested in accordance with:  
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE  
 
246695-YTG-C-0708  
Second model  
nameplate inside  
hinged access panel  
Filter access  
(2" throw-away)  
Disconnect location  
(optional disconnect switch)  
Filter drier  
(solid core)  
Simplicity™ Control board  
w/screw connectors for T-stat  
wiring and Network Connection  
Condenser  
Section  
Dual stage cooling  
for maximum comfort  
Belt-drive  
blower motor  
Compressor #2 access  
(high-efficiency compressor  
w/crankcase heater)  
Slide out motor and  
blower assembly  
for easy adjustment  
and service  
Power ventor motor  
20-gauge aluminized steel  
tubular heat exchanger for  
long life (stainless steel option)  
Base rails  
w/forklift slots  
(three sides)  
and lifting holes  
Roof curbs in eight-and  
fourteen-inch heights.  
Two-stage gas heating  
to maintain warm,  
Slide-out drain pan  
with steel ¾" NPT,  
female connection  
Roof curbs for transitioning  
comfortable temperature  
Toolless  
doorlatch  
from York Sunline™ footprint to  
the DM/DH/DJ Series footprint  
are available  
Compressor #1 access  
(high-efficiency compressor  
w/crankcase heater)  
Side entry power  
and control wiring  
knockouts  
(field-installed accessory)  
Intelligent control board  
for safe and efficient operation  
FIGURE 1 - PREDATOR® MAGNUM COMPONENT LOCATION  
FEATURES  
High Efficiency – High efficiency units are rated at 11.35  
EER. Gas/electric units have electronic spark ignition and  
power vented combustion with steady state efficiencies of  
80%. These efficiencies meet or exceed all legislated min-  
imum levels and provide low operating costs.  
Service windows have been placed in both condenser  
section walls. Rotation of the cover allows easy access  
to the condenser coils for cleaning or inspection.  
Both the unit control board and ignition control board uti-  
lize flash codes to aid in diagnosis of unit malfunctions.  
Unique alarm codes quickly identify the source of the  
unit alarm.  
®
Service Friendly – The Predator Magnum incorpo-  
rates a number of enhancements which improve service-  
ability.  
All units use the same standard filter size. This standard-  
ization removes any confusion on which filter sizes are  
needed for replacement.  
The motor and blower slide out of the unit as a common  
assembly. This facilitates greater access to all the indoor  
airflow components, thus simplifying maintenance and  
adjustment.  
The non-corrosive drain pan slides out of the unit to per-  
mit easy cleaning. The drain pan is accessed by remov-  
ing the drain pan cover plate on the rear of the unit. Once  
the plate is removed, the drain pan slides out through the  
rear of the unit.  
Service time is reduced through the use of hinged, toolless  
panels. Such panels provide access to frequently  
inspected components and areas, including the control  
box, compressors, filters, indoor motor & blower, and the  
heating section. The panels are screwed in place at the  
factory to prevent access by children or other unauthorized  
persons. It is recommended that the panels be secured  
with screws once service is complete.  
®
All Predator Magnum units have a second model name-  
plate located inside the control access door. This is to pre-  
vent deterioration of the nameplate through weathering.  
Johnson Controls Unitary Products  
3
   
246695-YTG-C-0708  
Environmentally Aware – For improved Indoor Air  
Quality, foil faced insulation is used exclusively through-  
out the units.  
three times within two hours before the unit control  
board will lock out the associated compressor.  
On Board Diagnostics - Each alarm will energize a  
trouble light on the thermostat, if so equipped, and  
flash an alarm code on the control board LED. Each  
high and low-pressure switch alarm as well as each  
freezestat alarm has its own flash code. The control  
board saves the five most recent alarms in memory,  
and these alarms can be reviewed at any time.  
Alarms and programmed values are retained  
through the loss of power.  
®
Balanced Heating – The Predator Magnum offers  
st  
“Ultimate Heating Comfort” with a balance between 1  
nd  
and 2 stage gas heating. The first stage of a gas heat  
Predator Magnum unit provides 60% of the heating  
®
capacity. Balanced heating allows the unit to better main-  
tain desired temperatures.  
Convertible Airflow Design – The side duct openings  
are covered when they leave the factory. If a side supply/  
return is desired, the installer simply removes the two  
side duct covers from the outside of the unit and installs  
them over the down shot openings. No panel cutting is  
required. Convertible airflow design allows maximum  
field flexibility and minimum inventory.  
Reliable – From the beginning – All units undergo com-  
puter automated testing before they leave the factory.  
Units are tested for refrigerant charge and pressure, unit  
amperage, and 100% functionality. For the long term –  
®
All Predator units are painted with a long lasting, pow-  
der paint that stands up over the life of the unit. The paint  
used has been proven by a 1000 hour salt spray test.  
System Protection – Suction line freezestats are sup-  
plied on all units to protect against loss of charge and coil  
frosting when the economizer operates at low outdoor air  
temperatures while the compressors are running. Every  
unit has solid-core liquid line filter-driers and high and  
low-pressure switches. Internal compressor protection is  
standard on all compressors. Crankcase heaters are  
standard on reciprocating compressors. Scroll compres-  
sors do not require crankcase heaters. Phase monitors  
are standard on all units.  
Flexible Placement – All models and configurations  
share the same cabinet/footprint and thus the same roof  
curb. You have the flexibility to set one curb and choose  
the correct tonnage size and heating option after the  
internal loads have been determined.  
®
To further simplify planning and installation, Predator  
Magnum cabinets are designed to fit your roof. With the  
optional roof curb, the unit ductwork is designed to fit  
around 24” on-center joists or between 48” on-center joists.  
Advanced Controls - S implicitycontrol boards have  
standardized a number of features previously available  
only as options or by utilizing additional controls.  
The drain pan can be rotated to drain to either the front  
or the rear of the unit. Additionally, the drain pan can be  
fitted to drain through the roof curb. As it is sometimes  
difficult to have a level installation, the drain pan features  
a generous slope to ensure proper drainage.  
Low Ambient - An integrated low-ambient control  
allows all units to operate in the cooling mode down  
to 0°F outdoor ambient without additional assistance.  
Optionally, the control board can be programmed to  
lockout the compressors when the outdoor air tem-  
perature is low or when free cooling is available.  
Full Perimeter Base Rails – The permanently attached  
base rails provide a solid foundation for the entire unit  
and protect the unit during shipment. The rails offer  
forklift access from 3 sides, and rigging holes are  
available so that an overhead crane can be used to  
place the units on a roof.  
Anti-Short Cycle Protection - To aid compressor  
life, an anti-short cycle delay is incorporated into the  
standard controls. Compressor reliability is further  
ensured by programmable minimum run times. For  
testing, the anti-short cycle delay can be temporarily  
overridden with the push of a button.  
Easy Installation – Gas and electric utility knockouts are  
supplied in the unit underside as well as the side of the  
unit. A clearly identified location is provided to mount a  
field supplied electrical disconnect switch. Utility connec-  
tions can be made quickly and with a minimum amount  
of field labor.  
Fan Delays - Fan on and fan off delays are fully pro-  
grammable. Furthermore, the heating and cooling  
fan delay times are independent of one another. All  
units are programmed with default values based  
upon their configuration of cooling and heat.  
All units are shipped with 2” throw-away filters installed.  
Wide Range of Indoor Airflows – All indoor fan motors  
are belt-drive type providing maximum flexibility to han-  
dle most airflow requirements. For high static applica-  
tions, factory installed alternate indoor fan motors are  
available. With the optional indoor fan motor, all units can  
supply nominal airflow at a minimum of 1.5” ESP.  
Safety Monitoring - The control board monitors the  
high and low-pressure switches, the freezestats, the  
gas valve, if applicable, and the temperature limit  
switch on gas and electric heat units. The unit con-  
trol board will alarm on ignition failures, compressor  
lockouts and repeated limit switch trips.  
Warranty - All models include a 1-year limited warranty  
on the complete unit. Compressors and electric heater  
elements each carry a 5-year warranty. Aluminized steel  
and stainless steel tubular heat exchangers carry a 10-  
year warranty.  
Nuisance Trip Protection and Strikes - To prevent  
nuisance trouble calls, the control board uses a  
“three times, you’re out” philosophy. The high and  
low-pressure switches and the freezestats must trip  
4
Johnson Controls Unitary Products  
246695-YTG-C-0708  
CO input for demand ventilation. With single enthalpy  
FACTORY INSTALLED OPTIONS  
2
input, the economizer control monitors outdoor air. The  
dual enthalpy kit provides a second input used to mon-  
itor the return air. With a dual input kit installed, the  
economizer control compares the values of the two  
enthalpy or temperature inputs and positions the  
dampers to provide the maximum efficiency possible.  
®
YORK offers several equipment options factory installed, for  
®
the Predator Magnum line.  
Optional Factory Installed Economizers - Predator  
units offer a variety of optional factory installed econo-  
mizers with low leak dampers. The outdoor air enthalpy  
sensor enables economizer operation if the outdoor  
enthalpy is less than the setpoint of the economizer logic  
module. See Table 19 to determine the correct econo-  
mizer for your application.  
Power Exhaust (Downflow only) - This accessory  
installs in the unit with a down flow economizer.  
Motorized Outdoor Air Damper - The motorized out-  
door air damper includes a slide-in/plug-in damper  
assembly with an outdoor air hood and filters. The out-  
door air dampers open to the preset position when the  
indoor fan motor is energized. The damper has a range  
of 0% to 100% outdoor air entry. Factory installed option  
or field installed accessory.  
Downflow Economizer - (With barometric relief) -  
The economizer is provided with a single enthalpy  
input. The economizer is 2% low leakage type, and is  
shipped installed and wired. The installer needs only  
to assemble and mount the outdoor air hood (Pro-  
vided). The economizer has spring return, fully modu-  
lating damper actuators and is capable of introducing  
up to 100% outdoor air. As the outdoor air intake  
dampers open, the return air dampers close. The  
changeover from mechanical refrigeration to econo-  
mizer operation is regulated by the standard single  
enthalpy input. There is an optional input dual dry  
bulb available. To meet regulated air standards, the  
Alternate Indoor Blower Motor - For applications with  
high static restrictions, units are offered with optional  
indoor motors that provide higher static output and/or  
higher airflow, depending upon the installer’s needs.  
Aluminized Steel Gas Heat Exchanger - For applica-  
tions in non-corrosive environments.  
Stainless Steel Gas Heat Exchanger - For applications  
in corrosive environments, this option provides a full  
stainless steel heat exchanger assembly.  
economizer control accepts an optional CO input for  
2
demand ventilation. With single enthalpy input, the  
economizer control monitors outdoor air. The dual  
enthalpy kit provides a second input used to monitor  
the return air. With a dual input kit installed, the econ-  
omizer control compares the values of the two  
enthalpy or temperature inputs and positions the  
dampers to provide the maximum efficiency possible.  
Stainless Steel Drain Pan - An optional rust-proof stain-  
less steel drain pan is available to provide years of trou-  
ble-free operation in corrosive environments.  
Electric Heaters - The electric heaters range from 18kW  
to 54kW and are available in all the voltage options of the  
base units. All heaters are dual staged. All heaters are  
intended for single point power supply.  
Horizontal Economizer - (Without barometric  
relief) - All features of the downflow economizer  
exist except you must order the duct mount baro-  
metric relief separately. You must order a 1EH0408  
if you are installing a power exhaust. You can  
order a 1RD0411 Barometric Relief for horizontal  
flow economizers only.  
Disconnect Switch - For gas heat units and cooling  
units with electric heat, an HACR breaker sized to the  
unit is provided. For cooling only units, a switch sized to  
the largest electric heat available for the particular unit is  
provided. Factory installed option only.  
Convenience Outlet - (Non-Powered/Powered) - This  
option locates a 120V single-phase GFCI outlet with  
cover, on the corner of the unit housing adjacent to the  
compressors. The “Non-powered” option requires the  
installer to provide the 120V single-phase power source  
and wiring. The “Powered” option is powered by a step-  
down transformer in the unit. Factory installed option only.  
BAS Ready Economizer -(With barometric relief)  
- The economizer is provided with a Belimo actuator  
that requires a 0-10V DC input from an external  
source (i.e., field installed building automation sys-  
tem controller). Power exhaust options are avail-  
able. The economizer is 2% low leakage type with  
spring return and fully modulating dampers capable  
of introducing up to 100% outside air. Also include 2”  
pleated filters.  
Smoke Detectors - The smoke detectors stop operation  
of the unit by interrupting power to the control board if  
smoke is detected within the air compartment. Available  
for both the supply and/or return air.  
Slab Economizer for Energy Recovery Ventilators-  
(With barometric relief and Fresh Air Hood) - The  
economizer is provided with a single enthalpy input.  
The economizer is 2% low leakage type, and is  
shipped installed and wired. The economizer has  
spring return, fully modulating damper actuators and is  
capable of introducing up to 100% outdoor air. As the  
outdoor air intake dampers open, the return air damp-  
ers close. The changeover from mechanical refrigera-  
tion to economizer operation is regulated by the  
standard single enthalpy input. There is an optional  
input dual dry bulb available. To meet regulated air  
standards, the economizer control accepts an optional  
Factory installed smoke detectors in the return air,  
may be subjected to freezing temperatures during  
"off" times due to out side air infiltration. These  
smoke detectors have an operational limit of 32 °F  
to 131°F. Smoke detectors installed in areas that  
could be out side those limitations will have to be  
moved to prevent having false alarms.  
Johnson Controls Unitary Products  
5
 
246695-YTG-C-0708  
Phase Monitors - Designed to prevent unit damage.  
The phase monitor will shut the unit down in an out-of  
phase condition. (Standard on units with Scroll Com-  
pressors.)  
Johnson Controls BAS Control - The Johnson Control  
YK-UNT-1126 building automation system controller is  
factory installed. Includes supply air sensor, return air  
sensor, dirty filter indicator switch, and air proving switch.  
Coil Guard - Customers can purchase a coil guard kit to  
protect the condenser coil from damage. Additionally,  
this kit stops animals and foreign objects from entering  
the space between the inner condenser coil and the  
main cabinet. This is not a hail guard kit.  
CPC BAS Control - The Computer Process Controls  
Model 810-3060 ARTC Advanced Rooftop building auto-  
mation system controller is factory installed. Includes  
supply air sensor, return air sensor, dirty filter indicator  
switch and air proving switch.  
Dirty Filter Switch - This kit includes a differential pres-  
sure switch that energizes the fault light on the unit ther-  
mostat, indicating that there is an abnormally high  
pressure drop across the filters. Factory installed option  
or field installed accessory.  
Honeywell BAS Control - The Honeywell W7750C  
building automation system controller is factory installed.  
Includes air supply sensor, return air sensor, dirty filter  
indicator switch, and air proving switch.  
York Commercial Comfort System (YCCS) - Provides  
rooftop system integration for YCCS single zone and  
change-over bypass systems.  
Technicoat Condenser Coils - The condenser coils are  
coated with a phenolic coating for protection against cor-  
rosion due to harsh environments.  
FIELD INSTALLED ACCESSORIES  
Technicoat Evaporator Coil - The evaporator coils are  
coated with a phenolic coating for protection against cor-  
rosion due to harsh environments.  
®
YORK offers several equipment accessories for field instal-  
®
lation, for the Predator Magnum line.  
BAS - Building Automation System Controls S implic-  
ity™ Intelli-Comfort™ Control - The York® S implicity™  
Intelli-Comfort™ control is factory installed. It includes a  
supply air sensor, a return air sensor, and an outside air  
sensor. There are provisions for a field installed dirty filter  
indicator switch, an air-proving switch, an Outside Air  
Humidity sensor, a Return Air Humidity sensor, an Inside  
IAQ sensor, and an Outside Air IAQ sensor. Construction  
mode operation, 365-day real time clock with 7 day pro-  
gramming plus holiday scheduling is built-in. Two differ-  
ent modes of demand ventilation are achieved through  
Downflow Economizer - (With barometric relief) - The  
economizer is provided with a single enthalpy input. The  
economizer is 2% low leakage type. The economizer has  
spring return, fully modulating damper actuators and is  
capable of introducing up to 100% outdoor air. As the  
outdoor air intake dampers open, the return air dampers  
close. The changeover from mechanical refrigeration to  
economizer operation is regulated by the standard single  
enthalpy input. There is an optional input dual dry bulb  
available. To meet regulated air standards, the econo-  
mizer control accepts an optional CO input for demand  
2
the Intelli-Comfort™ using CO sensors. It uses an  
2
ventilation. With single enthalpy input, the economizer  
control monitors outdoor air. The dual enthalpy kit pro-  
vides a second input used to monitor the return air. With  
a dual input kit installed, the economizer control com-  
pares the values of the two enthalpy or temperature  
inputs and positions the dampers to provide the maxi-  
mum efficiency possible  
inside CO sensor to perform Demand Ventilation. It can  
2
also use an Outside CO sensor to perform Differential  
2
Demand Ventilation. It uses a Patented Comfort Ventila-  
tion algorithm to provide comfortable ventilation air tem-  
perature. The patented economizer-loading algorithm  
will protect the equipment when harsh operating condi-  
tions exist. Humidity in the occupied space or return duct  
can be monitored and controlled via humidity sensors  
and the on-board connection for hot gas re-heat system.  
It uses the Intelli-Start™ algorithm to maximize energy  
savings by recovering the building from the Unoccupied  
Setpoints to the Occupied Setpoints just in time for the  
Occupied Time Period to begin. The S implicity™ Intelli-  
Comfort™ balances space temperature, ventilation air  
Horizontal Economizer - (Without barometric relief) -  
All features of the downflow economizer exist except you  
must order the duct mount barometric relief separately.  
You must order a 1EH0408 if you are installing a  
power exhaust. You can order a 1RD0411 Barometric  
Relief for horizontal flow economizer.  
Slab Economizer for Energy Recovery Ventilator-  
(Without barometric relief or Fresh Air Hood) - The  
economizer is provided with a single enthalpy input. The  
economizer is 2% low leakage type. The economizer has  
spring return, fully modulating damper actuators and is  
capable of introducing up to 100% outdoor air. As the  
outdoor air intake dampers open, the return air dampers  
close. The changeover from mechanical refrigeration to  
economizer operation is regulated by the standard single  
enthalpy input. There is an optional input dual dry bulb  
available. To meet regulated air standards, the econo-  
temperature, CO and humidity for ultimate comfort.  
2
S implicity™ Intelli-Comfort™ with ModLINC  
Control - The York® S implicity™ Intelli-Comfort™ with  
ModLINC control is factory installed. It includes all the  
features of the Intelli-Comfort™ control with an additional  
control to translate communications from MODBUS to  
the BACnet MSTP protocol.  
Novar® BAS Control - The Novar® ETC-3 building  
automation system controller is factory installed. Incudes  
supply air sensor, return air sensor, dirty filter indicator  
switch, and air proving switch.  
mizer control accepts an optional CO input for demand  
2
6
Johnson Controls Unitary Products  
 
246695-YTG-C-0708  
ventilation. With single enthalpy input, the economizer  
control monitors outdoor air. The dual enthalpy kit pro-  
vides a second input used to monitor the return air. With  
a dual input kit installed, the economizer control com-  
pares the values of the two enthalpy or temperature  
inputs and positions the dampers to provide the maxi-  
mum efficiency possible.  
-60°F Gas Heat Kit - For installations which require gas  
heat units to perform in low ambient temperatures, a gas  
section heating kit is available. This kit provides electric  
heat in the gas heat controls section to ensure the gas  
valve and controls will continue to function properly at  
extremely low temperatures.  
Gas Heat High Altitude Kit - This kit converts a gas  
heat unit to operate at high altitudes, 2,000 to 6,000 feet.  
Conversion kits are available for natural gas and pro-  
pane.  
You can order 1EH0409 Barometric Relief/FA Hood  
for field installations without an ERV.  
Dual Enthalpy Control, Accessory - This kit contains  
the required components to convert a single enthalpy  
economizer to dual enthalpy.  
Gas Heat Propane Conversion Kit - This kit converts a  
gas-fired heater from natural gas to propane. It contains  
the main burner orifices and gas valve replacement  
springs.  
Barometric Relief Damper - Zero to 100% capacity  
barometric relief dampers for use with horizontal flow, or  
field installed slab economizers.  
Gas Piping Kit - Contains pipe nipples, fittings and gas  
cock required for gas supply connection with external  
shut off.  
Power Exhaust - This accessory installs in the unit with  
a down flow economizer. Power exhaust plugs into the  
connector in the unit bulkhead. You must purchase  
1EH0408 barometric relief when applying to a hori-  
zontal flow application.  
Electric Heaters - The electric heaters range from 18  
kW to 54kW and are available in all the voltage options  
of the base units. All heaters are dual staged. Cooling  
units include an adapter panel for easy installation of the  
electric heaters. Necessary hardware and connectors  
are included with the heaters. All heaters are intended  
for single point power supply.  
Manual Outdoor Air Damper - Like the motorized out-  
door air damper, each manual outdoor air damper  
includes a slide-in damper assembly with an outdoor air  
hood and filters. Customers have a choice of dampers  
with ranges of 0% to 100% or 0% to 35% outdoor air entry.  
Low Limit / Compressor Lockout Kit  
1. Compressor Lockout (CLO): To prevent mechani-  
cal (compressorized) operation of the unit during  
cold outdoor conditions where there is a risk of  
returning liquid refrigerant back to the compressors.  
Motorized Outdoor Air Damper - The motorized out-  
door air damper includes a slide-in/plug-in damper  
assembly with an outdoor air hood and filters. The out-  
door air dampers open to the preset position when the  
indoor fan motor is energized. The damper has a range  
of 0% to 100% outdoor air entry. Factory installed option  
or field installed accessory.  
2. Low Limit Control (LLC): To prevent the supply air  
from dropping below a specified setpoint by utilizing  
the units first stage heating means when there is a  
demand for cooling during cold outside conditions.  
Smoke Detectors - The smoke detectors stop operation  
of the unit by interrupting power to the control board if  
smoke is detected within the air compartment.  
Metal Frame Filter Kit - Metal frame with polyester filter  
medium.  
CO Sensor - Senses CO levels and automatically  
2
2
Permanent Filters - Permanent filters are available.  
overrides the economizer when levels rise above the  
preset limits.  
Roof Curbs - The roof curbs have insulated decks and  
are shipped disassembled The roof curbs are available  
in 8” and 14” heights. For applications with security con-  
cerns, burglar bars are available for the duct openings of  
the roof curbs.  
Dirty Filter Switch - This kit includes a differential pres-  
sure switch that energizes the fault light on the unit ther-  
mostat, indicating that there is an abnormally high  
pressure drop across the filters.  
Roof Curb Transition - Single Piece Adapter (10” High) -  
Coil Guard - Field installed decorative wire coil guard.  
Roof curbs for transitioning from Sunline™ units to Pred-  
®
ator Magnum. Fits 7.5 to 12.5 Sunline™ roof curbs only.  
Hail Guard - This kit includes a sloped hood which  
installs over the outside condenser coil and prevents  
damage to the coil fins from hail strikes. Field installed  
accessory only.  
Burglar Bars - Mount in the supply and return openings  
to prevent entry into the duct work.  
Thermostat - The units are designed to operate with 24-  
volt electronic and electro-mechanical thermostats. All  
units (with or without an economizer) operate with two-  
stage heat/two-stage cool or two-stage cooling only ther-  
mostats, depending upon unit configuration.  
Flue Exhaust Extension Kit - In locations with wind or  
weather conditions which may interfere with proper  
exhausting of furnace combustion products, this kit can  
be installed to prevent the flue exhaust from entering  
nearby fresh air intakes.  
Johnson Controls Unitary Products  
7
246695-YTG-C-0708  
TABLE 1: ACCESSORIES  
Part Number  
Description  
Weight  
1RC0470  
Roof Curb, 8" Height  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1RC0471  
Roof Curb, 14" Height  
1RC0472  
Roof Curb, Transition (7.5 T through 12.5 T)  
Burglar Bars, Downflow  
1BD0408  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
2TP04521846  
2TP04522446  
2TP04523646  
2TP04525446  
2TP04521858  
2TP04522458  
2TP04523658  
2TP04525458  
1FA0411  
Electric Heat 18kW 230V  
Electric Heat 24kW 230V  
Electric Heat 36kW 230V  
Electric Heat 54kW 230V  
Electric Heat 18kW 460V  
Electric Heat 24kW 460V  
Electric Heat 36kW 460V  
Electric Heat 54kW 460V  
Electric Heat 18kW 575V  
Electric Heat 24kW 575V  
Electric Heat 36kW 575V  
Electric Heat 54kW 575V  
Manual Outside Air Damper 0-35%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief)  
Manual Outside Air Damper 0-100%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief)  
Motorized Damper, Downflow (Incl. Hood, Damper & Filter, no Barometric Relief)  
Motorized Damper, Horizontal (Incl. Hood, Damper & Filter, no Barometric Relief)  
Economizer, Downflow (Incl. Barometric Relief & All Hoods)  
Economizer, Horizontal (Incl. Dampers & Hoods, no Barometric Relief)  
Economizer, Slab, Downflow (Incl. Dampers only no Hoods or Barometric Relief)  
Power Exhaust, Downflow, 230V (For Units with Economizer only)  
Power Exhaust, Downflow, 460V (For Units with Economizer only)  
Power Exhaust, Downflow, 580V (For Units with Economizer only)  
Dual Enthalpy Control (Use with Single Enthalpy Economizer)  
Hood Kit, Downflow Economizer (Included with all Downflow Economizers)  
Barometric Relief Kit, Ductmount for Horizontal Application (Incl. Damper & Hood)  
Barometric Relief Kit, Ductmount for Horizontal Application w/Power Exhaust (Incl. Damper & Hood)  
Barometric Relief / Hood Kit, for Field Installed Slab Econ. w/o ERV (Incl. Barometric Relief & FA Hood)  
CO2 Detector Unit Mount  
1FA0412  
2MD04702724  
2MD04703324  
2EE04705024  
2EE04705124  
2EE04705224  
2PE04703225  
2PE04703246  
2PE04703258  
2EC04700924  
1EH0407  
124 lbs.  
97 lbs.  
-
-
-
-
1RD0411  
1EH0408  
25 lbs.  
1EH0409  
-
-
-
-
2AQ04700424  
2AQ04700324  
2SD04700424  
2MK04700624  
1CG0424  
CO2 Detector Space Mount  
Smoke Detector, Supply or Return (Return Not Available with Horizontal Economizer)  
Low Limit / Compressor Lockout Kit  
Coil Guard (Electric / Electric & HP models)  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1CG0425  
Coil Guard (Gas / Electric models)  
1HG0411  
Hail Guard Kit  
1GP0404  
Gas Piping Kit  
1NP0441  
Propane Conversion Kit  
1HA0442  
High Altitude Kit for Natural Gas  
1HA0443  
High Altitude Kit for Propane  
1FE0411  
Flue Exhaust Extension Kit  
2BC04700106  
2BC04700151  
2BC04700154  
1FL0402  
Gas Heat Kit, -60 deg F, 230V  
Gas Heat Kit, -60 deg F, 460V  
Gas Heat Kit, -60 deg F, 575V  
Permanent Filter Kit  
2DF0401  
Dirty Filter Switch  
1FF0410  
Filter Frame Kit, Metal  
8
Johnson Controls Unitary Products  
 
246695-YTG-C-0708  
NOMENCLATURE  
12.5 Ton Model Number Nomenclature  
D J 150 N15 A 2 A AA 4 0 1 2 4 A  
Product Category  
Product Style  
D = A/C, Single Pkg., R-22  
A = Style A  
B = Style B  
C = Style C  
Product Identifier  
Configuration Options (not required for all units)  
These four digits will not be assigned until a quote is requested, or an order placed.  
J = 12.5 Ton 11.3 EER A/C  
SS Drain Pan  
CPC Controller, DFS, APS  
Nominal Cooling Capacity  
Johnson Controller UNT 1126 (N2 protocol), DFS, APS  
Honeywell Controller, DFS, APS  
150 = 12.5 Ton  
Novar Controller, DFS, APS  
Simplicity IntelliComfort Controller  
Heat Type and Nominal Heat Capacity  
C00 = Cooling Only. No heat installed  
Simplicity IntelliComfort Controller w/ModLinc  
York Commercial Comfort System (YCCS) Rtu Controller  
2" Pleated filters  
BAS Ready Unit with Belimo Economizer  
Shipping Bag  
Gas Heat Options  
N15 = 150 MBH Output Aluminized Steel  
N20 = 200 MBH Output Aluminized Steel  
S15 = 150 MBH Output Stainless Steel  
S20 = 200 MBH Output Stainless Steel  
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned  
Product Generation  
4 = Fourth Generation  
Electric Heat Options  
E18 = 18 KW  
E24 = 24 KW  
E36 = 36 KW  
E54 = 54 KW  
Additional Options  
AA = None  
RC = Coil Guard, Shipping Bag & American Flag  
AB = Phase Monitor  
TA = Technicoat Condenser Coil  
AC = Coil Guard  
AD = Dirty Filter Switch  
TJ = Technicoat Evaporator Coil  
TS = Technicoat Evaporator & Condenser Coils  
Airflow  
AE = Phase Monitor & Coil Guard  
AF = Phase Monitor & Dirty Filter Switch  
AG = Coil Guard & Dirty Filter Switch  
AH = Phase Monitor, Coil Guard & Dirty Filter Switch  
A = Std. Motor  
B = Std. Motor/Econo./Barometric Relief (Downflow  
Only)  
C = Std. Motor/Econo./Power Exhaust (Downflow Only)  
D = Std. Motor/Motorized Damper (Downflow Only)  
E = Std. Motor/Horizontal Economizer (No Baro.)  
F = Std. Motor/Slab Econo./Power Exhaust  
(Downflow Only)  
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be  
located in digits 15-18.  
G = Std. Motor/Slab Econo./Barometric Relief  
(Downflow Only)  
Installation Options  
N = Hi Static Mtr.  
P = Hi Static Mtr./Econo./Barometric Relief  
(Downflow Only)  
A = No Options Installed  
B = Option 1  
Q = Hi Static Mtr./Econo./Power Exhaust  
(Downflow Only)  
C = Option 2  
R = Hi Static Mtr./Motorized Damper (Downflow Only)  
S = Hi Static Mtr./Horizontal Economizer (No Baro.)  
T = Hi Static Mtr./Slab Econo./Power Exhaust  
(Downflow Only)  
D = Options 1 & 2  
E = Option 3  
F = Option 4  
G = Options 1 & 3  
H = Options 1 & 4  
J = Options 1, 2 & 3  
K = Options 1, 2, & 4  
L = Options 1,3 & 4  
M = Options 1, 2, 3, & 4  
N = Options 2 & 3  
P = Options 2 & 4  
Q = Options 2, 3, & 4  
R = Options 3 & 4  
S = Option 5  
U = Hi Static Mtr./Slab Econo./Barometric Relief  
(Downflow only)  
Voltage  
2 = 208/230-3-60  
4 = 460-3-60  
5 = 575-3-60  
T = Options 1 & 5  
U = Options 1, 3, & 5  
V = Options 1, 4, & 5  
W = Options 1, 3, 4, & 5  
X = Options 3 & 5  
Y = Options 4 & 5  
Z = Options 3, 4 & 5  
Options  
1 = Disconnect  
2 = Non-Pwr'd Conv. Outlet  
3 = Smoke Detector S.A.  
4 = Smoke Detector R.A.  
5 = Pwr'd Conv. Outlet  
Johnson Controls Unitary Products  
9
 
246695-YTG-C-0708  
TABLE 2: PHYSICAL DATA  
Model  
DJ 150 (12-1/2)  
Component  
Blower, Centrifugal (Dia. X Wd. in.)  
15 x 15  
3
Evaporator  
Blower  
Motor, Standard (HP)  
Motor, Optional (HP)  
Rows  
5
4
Fins per Inch  
Height (in.)  
15  
Evaporator  
Coil  
40  
Face Area (ft.2 each)  
Propeller Dia. (in., each)  
Motor (HP, each)  
CFM, Nominal (each)  
Rows (each)  
13.2  
24  
Condenser  
Fan  
(4 per Unit)  
1/3  
3500  
2
Condenser  
Coil  
(2 per unit)  
Fins per Inch  
15  
Height (in., each)  
36  
Face Area (ft.2 each)  
System 1 (lb./oz.)  
System 2 (lb./oz.)  
Quantity  
11.88  
2/0  
20/8  
2
Refrigerant  
Charge  
Compressors  
Air Filters  
Type  
Scroll  
25x20x2  
4
Size (Wd. x Ht. x Thickness in.)  
Number Per Unit  
TABLE 3: DJ 150 (12-1/2 TON) CAPACITY RATINGS  
Cooling Capacity  
Nominal  
Gas  
Line  
Size  
Gas Heat Capacity  
Input Output Seasonal  
1
Sound  
Rating  
Electric  
Heat  
ARI Ratings  
Size  
(Tons)  
Model  
CFM  
3
2
Temp.  
Capacity  
(kW)  
(dB)  
MBH EER IPLV  
(in. OD)  
(MBH) (MBH) Efficiency (%) Rise (°F)  
Cooling  
Only  
-
-
-
-
-
-
-
-
-
-
-
Electric  
Heat  
18, 24, 36  
54  
150  
(12-1/2)  
150  
11.35 12.3  
3750  
86  
Gas Heat  
Gas Heat  
-
-
180  
240  
144  
192  
80  
80  
10-40  
25-55  
3/4  
3/4  
1
2
3
Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb.  
Rated in accordance with ARI 270 standard.  
See Table 8.  
TABLE 4: UNIT VOLTAGE LIMITATIONS  
POWER RATING  
208/230-3-60  
460-3-60  
MIN.  
187  
432  
540  
MAX.  
252  
504  
575-3-60  
630  
10  
Johnson Controls Unitary Products  
     
246695-YTG-C-0708  
TABLE 5: DJ 150 (12 1/2 TON) COOLING CAPACITY  
Air On  
Temperature of Air on Condenser Coil 85°F  
Evap. Coil  
Temperature of Air on Condenser Coil 95°F  
Sensible Capacity (MBH)1  
Return Dry Bulb (°F)  
Sensible Capacity (MBH)1  
Return Dry Bulb (°F)  
Tot.  
Cap.1 Input2  
(MBH)  
Tot.  
Tot.  
Cap.1 Input2  
(MBH)  
Tot.  
WB  
(°F)  
CFM  
3750  
4375  
5000  
5625  
6250  
(kW)  
(kW)  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
173  
160  
148  
147  
177  
163  
151  
150  
180  
167  
154  
154  
184  
170  
157  
157  
188  
173  
161  
160  
10.9  
10.6  
10.5  
10.5  
10.9  
10.7  
10.6  
10.5  
11.0  
10.7  
10.6  
10.6  
11.0  
10.8  
10.7  
10.6  
11.1  
10.8  
10.7  
10.6  
102  
92  
81  
70  
95  
60  
84  
49  
73  
99  
38  
63  
88  
91  
37  
63  
90  
93  
35  
63  
92  
95  
33  
63  
89  
90  
32  
63  
86  
85  
168  
154  
143  
141  
170  
156  
145  
143  
173  
158  
147  
145  
176  
161  
150  
147  
179  
164  
152  
150  
11.8  
11.6  
11.4  
11.5  
11.8  
11.7  
11.5  
11.5  
11.9  
11.8  
11.6  
11.6  
12.0  
11.8  
11.7  
11.7  
12.1  
11.9  
11.7  
11.8  
101  
90  
79  
69  
92  
58  
81  
47  
71  
95  
94  
47  
72  
98  
98  
47  
74  
37  
60  
84  
84  
35  
60  
86  
85  
33  
60  
87  
87  
31  
60  
83  
81  
30  
61  
78  
75  
127 116 105  
148 141 131 120 109  
147 144 133 123 112 101  
112 100  
138 126 113 101  
151 148 141 128 115 103  
150 149 143 131 118 106  
122 108  
150 136 121 107  
154 154 150 136 121 107  
154 154 154 139 124 110  
133 116 100  
162 146 129 113  
157 157 155 139 122 106  
157 157 157 140 123 107  
143 125 106  
173 156 138 119 101  
161 161 161 142 123 105  
160 160 160 141 122 104  
124 114 103  
143 138 127 116 106  
141 137 126 116 105  
87  
74  
62  
88  
49  
75  
111  
98  
85  
73  
98  
60  
85  
136 123 110  
145 142 136 124 111  
143 141 136 123 110  
120 106  
147 132 118 103  
147 147 146 131 116 102  
145 145 145 130 116 101  
131 114  
155 143 127 110  
150 150 149 132 116  
147 147 147 131 114  
93  
79  
64  
92  
49  
77  
91  
76  
62  
89  
83  
66  
96  
50  
80  
98  
81  
65  
93  
48  
77  
99  
98  
49  
79  
96  
94  
87  
69  
50  
82  
142 123 105  
164 154 135 117  
152 152 152 134 115  
150 150 150 131 113  
86  
67  
98  
Temperature of Air on Condenser Coil 105°F  
Temperature of Air on Condenser Coil 115°F  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
158  
145  
134  
134  
160  
147  
136  
136  
162  
149  
138  
138  
165  
152  
140  
141  
168  
154  
143  
143  
13.0  
12.9  
12.7  
12.8  
13.1  
13.0  
12.8  
12.9  
13.2  
13.0  
12.8  
12.9  
13.2  
13.1  
12.9  
13.0  
13.3  
13.1  
12.9  
13.0  
99  
88  
77  
99  
67  
88  
56  
78  
97  
98  
58  
81  
45  
67  
87  
87  
45  
69  
90  
91  
46  
71  
93  
94  
46  
73  
90  
91  
47  
75  
87  
87  
34  
56  
76  
77  
33  
56  
77  
78  
31  
56  
79  
80  
29  
56  
74  
74  
28  
57  
68  
68  
148  
136  
125  
128  
150  
138  
127  
130  
152  
140  
129  
131  
155  
143  
131  
134  
157  
145  
133  
136  
14.3  
14.2  
14.0  
14.2  
14.4  
14.2  
14.1  
14.2  
14.4  
14.3  
14.1  
14.3  
14.5  
14.3  
14.1  
14.3  
14.5  
14.3  
14.2  
14.3  
96  
86  
75  
95  
64  
84  
54  
74  
89  
91  
56  
78  
94  
97  
58  
82  
43  
63  
78  
80  
43  
65  
82  
84  
44  
67  
85  
88  
44  
69  
81  
84  
44  
71  
77  
80  
32  
52  
67  
70  
31  
52  
69  
71  
29  
53  
70  
73  
28  
53  
65  
67  
26  
53  
59  
61  
120 110  
134 129 119 108  
134 130 119 109  
116 106  
125 121 110 100  
128 123 112 102  
3750  
4375  
5000  
5625  
6250  
109  
96  
83  
71  
94  
107  
94  
81  
69  
90  
132 119 107  
136 134 128 115 103  
136 134 129 116 103  
119 104  
144 129 114 100  
138 138 137 123 108  
138 138 138 124 109  
129 112  
149 139 123 106  
140 140 140 123 107  
141 141 141 124 107  
128 116 103  
127 125 120 107  
130 127 122 109  
117 102  
140 126 111  
129 129 129 114 100  
131 131 131 117 102  
127 111  
143 135 119 102  
131 131 131 114  
134 134 134 117 100  
89  
75  
60  
85  
88  
73  
96  
96  
79  
63  
90  
94  
77  
61  
86  
98  
140 121 102  
154 150 131 113  
143 143 143 124 106  
143 143 143 124 106  
84  
65  
94  
138 119 100  
82  
63  
90  
96  
99  
145 145 127 108  
133 133 133 115  
136 136 136 117  
Temperature of Air on Condenser Coil 125°F  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
137  
127  
116  
121  
139  
129  
118  
123  
141  
131  
120  
125  
144  
133  
122  
127  
146  
136  
124  
129  
15.6  
15.5  
15.3  
15.5  
15.7  
15.5  
15.3  
15.5  
15.7  
15.5  
15.3  
15.6  
15.7  
15.5  
15.4  
15.6  
15.7  
15.6  
15.4  
15.6  
94  
83  
73  
91  
62  
80  
91  
95  
67  
87  
99  
51  
70  
81  
84  
54  
74  
86  
90  
57  
78  
91  
95  
59  
82  
89  
94  
61  
86  
87  
92  
41  
59  
70  
73  
41  
61  
73  
77  
42  
64  
77  
81  
42  
65  
72  
77  
42  
67  
68  
73  
30  
48  
59  
63  
29  
49  
61  
64  
28  
49  
62  
66  
26  
49  
56  
60  
24  
48  
49  
54  
1
These capacities are gross ratings. For net  
capacity, deduct air blower motor, MBh = 3.415  
x kW. Refer to the appropriate Blower Perfor-  
mance Table for the kW of the supply air  
blower motor.  
These ratings include condenser fan motors  
(total 1 kW) and the compressor motors but  
not the supply air blower motor.  
112 102  
116 113 102  
121 116 105  
105  
125 112  
118 116 111  
123 120 115 102  
115 100  
131 122 108  
120 120 120 106  
125 125 125 110  
125 109  
133 131 115  
122 122 122 106  
127 127 127 110  
3750  
4375  
5000  
5625  
6250  
92  
79  
99  
2
86  
71  
93  
92  
75  
99  
135 117  
98  
80  
136 136 123 104  
124 124 124 105  
129 129 129 110  
Johnson Controls Unitary Products  
11  
 
246695-YTG-C-0708  
TABLE 6: ELECTRICAL DATA DJ150 (12-1/2 TON) W/O PWRD CONVENIENCE OUTLET  
MCA  
Max  
Fuse1  
Size  
Max Fuse1 Size  
w/Power  
Supply  
Blower  
Pwr  
Pwr  
Min. Circuit  
Ampacity  
(Amps)  
OD Fan  
Motors  
w/Power  
Exhaust  
(Amps)  
Compressors  
Exh Conv  
Electric Heater Actual Heater  
Exhaust  
Voltage  
Motor FLA Motor Outlet  
Model No.  
KW  
Amps  
(Amps)  
(Amps)  
RLA  
ea.  
LRA  
ea.  
FLA  
ea.  
3
HP  
5
HP  
3
HP  
5
HP  
3
5
3
5
3
HP  
80  
80  
90  
5
HP  
90  
90  
90  
FLA  
FLA  
HP  
HP  
HP HP  
None  
--  
13.5  
18.0  
25.5  
40.6  
--  
--  
37.5  
50.0  
61.9  
61.9  
76.1  
67.1 67.4 72.6 80 80  
67.1 67.4 73.8 80 80  
82.6 83.0 89.5 80 90  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
208  
230  
460  
20.0 146.0  
1.5  
1.5  
0.8  
0.6  
10.9 16.1  
10.9 16.1  
5.5  
0.0  
70.8 102.1 108.6 109.0 115.5 110 110  
112.7 154.5 161.0 161.4 167.9 175 175  
110  
175  
80  
125  
175  
90  
--  
61.9  
67.8  
85.8  
67.1 67.4 72.6 80 80  
74.3 74.6 81.1 80 80  
92.3 92.7 99.2 90 100  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
2TP04521846  
2TP04522446  
2TP04523646  
2TP04525446  
None  
2TP04521858  
2TP04522458  
2TP04523658  
2TP04525458  
18.0  
24.0  
34.0  
54.0  
--  
43.3  
57.7  
80  
90  
20.0 146.0  
5.5  
2.2  
1.8  
0.0  
0.0  
0.0  
100  
125  
175  
35  
100  
150  
175  
40  
81.8 115.9 122.4 122.7 129.2 125 125  
129.9 143.5 150.0 150.4 156.9 175 175  
--  
27.4  
33.7  
42.7  
57.7  
71.6  
21.6  
26.8  
34  
30.2 29.6 32.4 35 35  
37.2 36.4 39.9 35 40  
46.2 45.5  
61.2 60.5  
18  
22.6  
30.1  
42.7  
67.8  
--  
40  
40  
8.4  
6.7  
73.0  
60.0  
5.3  
4.1  
8.1  
6.0  
24  
49  
64  
45 50  
60 70  
50  
50  
34  
70  
70  
54  
75.1 74.3 77.8 80 90  
23.5 23.4 25.3 25 30  
80  
90  
--  
30  
30  
18  
18.1  
24.1  
34.1  
54.2  
29.2  
29  
31.4 30 30  
30  
35  
575  
24  
36.4 36.2 38.6 35 40  
48.4 48.3 50.6 50 50  
59.5 59.3 61.7 70 70  
40  
40  
34  
46  
50  
60  
54  
57.1  
70  
70  
1
Maximum HACR breaker of the same AMP size is applicable.  
TABLE 7: ELECTRICAL DATA DJ150 (12-1/2 TON) WITH PWRD CONVENIENCE OUTLET  
MCA  
Max  
Fuse1  
Size  
Max Fuse1 Size  
w/Power  
Supply  
Blower  
Pwr  
Pwr  
Min. Circuit  
Ampacity  
(Amps)  
OD Fan  
Motors  
w/Power  
Exhaust  
(Amps)  
Compressors  
Exh Conv  
Electric Heater Actual Heater  
Exhaust  
Voltage  
Motor FLA Motor Outlet  
Model No.  
KW  
Amps  
(Amps)  
(Amps)  
RLA  
ea.  
LRA  
ea.  
FLA  
ea.  
3
HP  
5
HP  
3
HP  
5
HP  
3
5
3
5
3
5
FLA  
FLA  
HP  
HP  
HP HP  
HP  
90  
HP  
100  
100  
110  
150  
200  
100  
100  
125  
150  
175  
45  
None  
--  
13.5  
18.0  
25.5  
40.6  
--  
--  
37.5  
50.0  
71.9  
73.0  
88.6  
77.1 77.4 82.6 90 90  
79.5 79.8 86.3 90 90  
95.1 95.5 102.0 90 100  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
90  
208  
230  
460  
20.0 146.0  
1.5  
1.5  
0.8  
0.6  
10.9 16.1  
10.9 16.1  
5.5  
10.0  
100  
125  
175  
90  
70.8 114.6 121.1 121.5 128.0 125 125  
112.7 167.0 173.5 173.9 180.4 175 175  
--  
71.9  
80.3  
77.1 77.4 82.6 90 90  
86.8 87.1 93.6 90 90  
98.3 104.8 105.2 111.7 100 110  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
2TP04521846  
2TP04522446  
2TP04523646  
2TP04525446  
None  
2TP04521858  
2TP04522458  
2TP04523658  
2TP04525458  
18.0  
24.0  
34.0  
54.0  
--  
43.3  
57.7  
90  
20.0 146.0  
5.5  
2.2  
1.8  
10.0  
5.0  
110  
150  
175  
40  
81.8 128.4 134.9 135.2 141.7 150 150  
129.9 156.0 162.5 162.9 169.4 175 175  
--  
32.4  
39.9  
49  
35.2 34.6 37.4 40 40  
43.4 42.7 46.2 40 45  
52.5 51.7 55.2 50 60  
67.5 66.7 70.2 70 70  
81.3 80.6 84.1 90 90  
27.5 27.4 29.3 30 30  
18  
22.6  
30.1  
42.7  
67.8  
--  
45  
50  
8.4  
6.7  
73.0  
60.0  
5.3  
4.1  
8.1  
6.0  
24  
60  
60  
34  
64  
70  
80  
54  
77.8  
25.6  
31.8  
39  
90  
90  
--  
30  
35  
18  
18.1  
24.1  
34.1  
54.2  
34.2  
34  
36.4 35 35  
35  
40  
575  
4.0  
24  
41.4 41.2 43.6 40 45  
53.4 53.3 55.6 60 60  
64.5 64.3 66.7 70 70  
45  
45  
34  
51  
60  
60  
54  
62.1  
70  
70  
1
Maximum HACR breaker of the same AMP size is applicable.  
TABLE 8: ELECTRIC HEAT MULTIPLIERS  
NOTES FOR TABLES 9 AND TABLE 10:  
VOLTAGE  
kW Cap. Multiplier  
Blower performance includes dry coil and 2” throwaway  
filters.  
NOMINAL  
RATING  
208  
0.75  
0.92  
0.92  
0.92  
240  
230  
Blower performance for gas heat includes the maximum  
number of heat tubes available for each tonnage.  
480  
600  
460  
575  
ESP (External Static Pressure) given is that available for the  
supply and return air duct system. All internal resistances  
have been deducted from the total static pressure of the  
blower.  
NOTE: Electric heaters are rated at nominal voltage. Use  
this table to determine the electric heat capacity for  
heaters supplied at lower voltages.  
12  
Johnson Controls Unitary Products  
     
246695-YTG-C-0708  
Johnson Controls Unitary Products  
13  
 
246695-YTG-C-0708  
14  
Johnson Controls Unitary Products  
 
246695-YTG-C-0708  
TABLE 11: ADDITIONAL STATIC RESISTANCE  
Electric Heat KW2  
1
2 3  
CFM  
Cooling Only  
Economizer  
18  
24  
36  
54  
3700  
3900  
4100  
4300  
4500  
4700  
4900  
5100  
5300  
5500  
5700  
5900  
6100  
6300  
0.20  
0.23  
0.25  
0.28  
0.30  
0.33  
0.36  
0.39  
0.42  
0.45  
0.48  
0.52  
0.56  
0.60  
0.04  
0.04  
0.04  
0.05  
0.05  
0.05  
0.05  
0.06  
0.06  
0.06  
0.06  
0.07  
0.07  
0.07  
0.18  
0.20  
0.22  
0.24  
0.26  
0.29  
0.31  
0.34  
0.37  
0.40  
0.43  
0.46  
0.49  
0.53  
0.21  
0.23  
0.25  
0.28  
0.30  
0.33  
0.35  
0.38  
0.41  
0.44  
0.47  
0.50  
0.53  
0.56  
0.22  
0.24  
0.26  
0.29  
0.31  
0.34  
0.37  
0.40  
0.43  
0.46  
0.49  
0.53  
0.56  
0.59  
0.26  
0.28  
0.31  
0.34  
0.37  
0.40  
0.43  
0.46  
0.49  
0.53  
0.56  
0.59  
0.62  
0.65  
1
2
3
Add these resistance values to the available static resistance in the respective Blower Performance Tables.  
Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.  
The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return  
air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.  
TABLE 12: ELECTRIC HEAT MINIMUM SUPPLY AIR CFM  
UNIT NOMINAL TONS  
12.5  
HEATER  
VOLTAGE  
kW  
MINIMUM SUPPLY AIR CFM  
18  
24  
36  
54  
18  
24  
36  
54  
18  
24  
36  
54  
208/230  
3750  
3750  
3750  
480  
600  
TABLE 13: INDOOR BLOWER SPECIFICATIONS  
MOTOR  
RPM Eff.  
MOTOR SHEAVE  
BLOWER SHEAVE  
MODEL  
DJ150  
BELT  
HP  
3
SF Frame Datum Dia. (in.) Bore (in.) Model Datum Dia. (in.) Bore (in.) Model  
1725 80% 1.15  
1725 87% 1.15  
56  
3.4 - 4.4  
4.3 - 5.3  
7/8  
1VM50  
1VP56  
7.0  
6.7  
1
1
AK74  
BK77  
A54  
5
184T  
1 1/8  
BX55  
TABLE 14: POWER EXHAUST SPECIFICATIONS  
MOTOR  
RPM1  
ELECTRICAL  
POWER EXHAUST  
FUSE  
SIZE  
CFM@  
0.1 ESP  
VOLT  
PHASE  
MODEL  
HP  
QTY  
LRA  
24.9  
FLA  
5.0  
MCA  
2PE0473125  
2PE0473146  
2PE0473158  
208/230  
460  
1
1
1
6.3  
2.8  
1.9  
10  
5
1075  
1050  
0.75  
1
2.2  
3,800  
N/A  
575  
1.5  
4
1
Motors are multi-tapped and factory wired for high speed.  
Johnson Controls Unitary Products  
15  
         
246695-YTG-C-0708  
FRONT  
FRONT  
C
D
LEFT  
B
LEFT  
A
C
E
A
B
D
F
FIGURE 2 - UNIT 4 POINT LOAD  
TABLE 15: 4 POINT LOAD WEIGHT  
FIGURE 4 - UNIT WITH 6 POINT LOAD  
TABLE 16: 6 POINT LOAD WEIGHT  
Locations (lbs.)  
Model  
Location (lbs.)  
Model  
DJ150  
A
B
C
D
E
F
A
B
C
D
DJ150  
184  
210  
246  
323  
275  
242  
282  
359  
468  
371  
TABLE 17: UNIT WEIGHTS  
Operating  
Weight (lb.)  
1480  
Shipping  
Weight (lb.)  
Model DJ150  
25-½"  
60"  
Cooling Unit Only  
w/Economizer  
1495  
85  
FRONT  
84  
LEFT  
w/Power Exhaust  
150  
110  
148  
w/Gas Heat1  
FIGURE 3 - UNIT CENTER OF GRAVITY  
110  
49  
w/Electric Heat2  
49  
1
2
8 Tube Heat Exchanger  
54 kW heater  
16  
Johnson Controls Unitary Products  
           
246695-YTG-C-0708  
119-7/16  
For Gas Pipe Entry  
see DETAIL A  
Convenience  
Outlet  
Power  
Entry  
2-1/2  
30-11/32  
Convenience  
Outlet Power  
Entry 7/8  
4-1/4  
Control  
Entry  
7/8  
11-1/2  
50-3/4  
FRONT  
For Baserail  
Dimensions  
see  
30-3/16  
17-3/16  
24-3/16  
DETAIL B  
59  
6-3/16  
89  
27  
LEFT  
For Drain Dimensions  
see DETAIL C  
FIGURE 5 - UNIT DIMENSIONS  
G
a
s
P
i
p
e
I
n
l
e
t
DETAIL A  
DETAIL B  
2
-
3
/
8
5
-
1
/
4
B
P
a
a
s
n
e
1
7
-
1
3
/
1
6
3
-
3
/
4
V
i
e
w
o
f
W
a
l
l
A
c
r
o
s
s
f
r
o
m
C
o
i
l
3
-
9
/
1
6
TABLE 18: UNIT CLEARANCES  
DETAIL C  
Top1  
72”  
36”  
36”  
Right  
12”  
36”  
0”  
Front  
Left  
Rear2  
Bottom3  
5
-
3
/
8
1
2
Units must be installed outdoors. Overhanging structure or  
shrubs should not obstruct condenser air discharge outlet.  
To remove the slide-out drain pan, a rear clearance of 60” is  
required. If space is unavailable, the drain pan can be  
removed through the front by separating the corner wall.  
Units may be installed on combustible floors made from  
wood or class A, B or C roof covering materials.  
3
Johnson Controls Unitary Products  
17  
   
246695-YTG-C-0708  
R
I
G
H
T
8
0
-
5
/
8
I
N
S
U
L
A
T
E
D
D
E
C
K
U
N
D
E
R
C
O
N
D
E
N
S
E
R
S
E
C
T
I
O
N
2
0
S
U
P
P
L
Y
2
0
6
R
E
T
U
R
N
2
T
Y
P
.
3
0
I
N
S
O
U
L
A
T
E
D
D
E
C
K
U
N
D
E
R
5
0
-
1
/
2
C
M
P
R
E
S
S
O
R
S
E
C
T
I
O
N
F
R
O
N
T
8
o
r
1
4
FIGURE 6 - PREDATOR® MAGNUM ROOF CURB DIMENSIONS  
2
T
Y
P
2
3
4
3
0
-
1
/
2
5
0
-
1
/
2
8
0
-
5
/
8
2
6
R
E
T
U
R
N
S
U
P
P
L
Y
1
0
7
6
-
5
/
8
5
9
-
1
/
4
9
4
F
R
O
N
T
R
I
G
H
T
6
4
-
1
/
4
FIGURE 7 - SUNLINE™ TO PREDATOR® MAGNUM TRANSITION ROOF CURBS  
18  
Johnson Controls Unitary Products  
   
246695-YTG-C-0708  
32-11/16  
6-13/16  
Supply  
Air  
6-13/16  
6-13/16  
Return  
Air  
24  
LEFT  
27-1/2  
21  
18  
21-3/16  
19-3/16  
17-3/16  
12-5/16  
7-1/8  
FRONT  
14-23/32  
16-3/8  
Bottom  
Bottom  
Bottom  
Gas Supply Entry  
18-1/16  
19-5/8  
Condensate  
Drain  
Power, Control and  
Convenience Outlet  
Wiring Entries  
63-1/2  
FIGURE 8 - BOTTOM DUCT OPENINGS (FROM ABOVE)  
Dot  
Plugs  
18-1/4  
Return  
Air  
28-1/4  
Supply  
Air  
18-1/4  
18-1/16  
2-31/32  
31-11/16  
28-1/4  
5-5/32  
FIGURE 9 - SIDEFLOW DUCT DIMENSIONS  
Johnson Controls Unitary Products  
19  
   
246695-YTG-C-0708  
FIGURE 10 - DOWNFLOW ECONOMIZER HOOD DETAIL  
TABLE 19: ECONOMIZER USAGE  
Application  
Description  
Model  
Bottom Return  
Side Return  
Downflow economizer with barometric relief  
Horizontal economizer without barometric relief  
Slab Economizer, 50” tall cabinet  
2EE04705424  
2EE047055241  
2EE047052242  
ERV or End Return  
1
2
Barometric relief must be ordered separately and installed in duct work.  
Barometric relief or fresh air hood not included. Must be ordered separately.  
2EE04705424  
Fresh Air Hood Fresh Air Damper Return Air Damper  
Barometric Relief Damper  
2EE04705424  
2EE04705424  
2EE04705424  
2EE04705424  
Barometric Relief Hood  
FIGURE 11 - FACTORY INSTALLED DOWNFLOW ECONOMIZER  
20  
Johnson Controls Unitary Products  
     
246695-YTG-C-0708  
2EE04705424  
Fresh Air Hood  
2EE04705424  
2EE04705424  
2PE047032XX  
Power Exhaust  
Fresh Air Damper Return Air Damper  
2EE04705424  
Barometric Relief Damper  
2EE04705424  
Barometric Relief Hood  
FIGURE 12 - FIELD INSTALLED DOWNFLOW ECONOMIZER W/POWER EXHAUST  
2EE04705524  
Return Air Damper  
Field Installed  
Duct Work  
2EE04705524  
Fresh Air Damper  
2PE047032XX  
Power Exhaust  
1EH0408  
Barometric  
Relief Damper  
1EH0408  
Barometric  
Relief Hood  
2EE04705524  
Fresh Air Hood  
FIGURE 13 - FIELD INSTALLED HORIZONTAL ECONOMIZER W/POWER EXHAUST  
Johnson Controls Unitary Products  
21  
   
246695-YTG-C-0708  
1EH0409  
Fresh Air Hood  
2EE04705X24  
Slab Economizer  
2PE047032XX  
Power Exhaust  
1EH0409 Barometric  
Relief Damper  
1EH0409 Barometric  
Relief Hood  
FIGURE 14 - SLAB ECONOMIZER DOWNFLOW W/POWER EXHAUST  
1EH0409  
Fresh Air Hood  
Field Installed  
Duct Work  
2EE04705X24  
Slab Economizer  
1EH0409  
Barometric Relief Hood  
2PE047032XX  
Power Exhaust  
1EH0409  
Barometric Relief Damper  
FIGURE 15 - SLAB ECONOMIZER END RETURN W/POWER EXHAUST  
22  
Johnson Controls Unitary Products  
   
246695-YTG-C-0708  
FIGURE 16 - COOLING UNIT WITH GAS HEAT WIRING 230 V. DIAGRAM  
Johnson Controls Unitary Products  
23  
 
246695-YTG-C-0708  
FIGURE 17 - COOLING UNIT W/WO ELECTRIC HEAT WIRING DIAGRAM  
24  
Johnson Controls Unitary Products  
 
246695-YTG-C-0708  
FIGURE 18 - COOLING UNIT WITH GAS HEAT WIRING 460, 575 & 50 HZ DIAGRAM  
Johnson Controls Unitary Products  
25  
 
246695-YTG-C-0708  
MECHANICAL SPECIFICATIONS  
SINGLE PACKAGE AIR COOLED GAS/ELECTRIC UNITS FOR 12.5 NOMINAL TONS  
PREDATOR® MAGNUM - DJ 150  
11.35 EER  
evaporator fan performance without removing panels or cre-  
ating bypass of the coils. Condensate pan shall be slide out  
design, constructed of a non corrosive material, internally  
sloped and conforming to ASHRAE 62-B9 standards. Con-  
densate connection shall be a minimum of ¾” I.D. female and  
be rigid mount connection.  
GENERAL  
Units shall be manufactured by York International Unitary  
Products Group in an ISO 9001 certified facility. YORK®  
®
Predator Magnum units are convertible single packages  
with a common footprint cabinet and common roof curb for all  
12-1/2 ton models. All units have two compressors  
with independent refrigeration circuits to provide 2 stages of  
cooling. The units were designed for light commercial appli-  
cations and can be easily installed on a roof curb, slab, or  
INDOOR (EVAPORATOR) FAN ASSEMBLY  
Fan shall be a belt drive assembly and include an adjustable  
pitch motor pulley. Job site selected brake horsepower shall  
not exceed the motors nameplate horsepower rating plus the  
service factor. Units shall be designed to operate within the  
service factor. Fan wheel shall be double inlet type with for-  
ward curve blades, dynamically balanced to operate  
smoothly throughout the entire range of operation. Airflow  
design shall be constant volume. Bearings shall be sealed  
and permanently lubricated for longer life and no  
®
frame. All Predator units are self-contained and assembled  
on rigid full perimeter base rails allowing for 3-way forklift  
access and overhead rigging. Every unit is completely  
charged, wired, piped, and tested at the factory to provide a  
quick and easy field installation. All units are convertible  
®
between side and down airflow. Independent Predator Mag-  
num Economizer designs are used on side and down  
discharge applications, as well as all tonnage sizes. Preda-  
®
tor Magnum units are available in the following  
maintenance. Entire blower assembly and motor shall be  
slide out design.  
configurations: cooling only, cooling with electric heat, and  
cooling with gas heat. Electric heaters are available as fac-  
tory-installed options or field-installed accessories.  
OUTDOOR (CONDENSER) FAN ASSEMBLY  
The outdoor fans shall be of the direct drive type, discharge  
air vertically, have aluminum blades riveted to corrosion  
resistant steel spider brackets and shall be dynamically bal-  
anced for smooth operation. The outdoor fan motors shall  
have permanently lubricated bearings internally protected  
against overload conditions and staged independently. A  
cleaning window shall be provided on two sides of the units  
for coil cleaning.  
DESCRIPTION  
Units shall be factory assembled, single package, (Elec/Elec,  
Gas/Elec), designed for outdoor installation. Units shall have  
a minimum EER of 11.35. They shall have built in field con-  
vertible duct connections for down discharge supply/return or  
horizontal discharge supply/return and be available with fac-  
tory installed options or field installed accessories. The units  
shall be factory wired, piped and charged with R-22 refriger-  
ant and factory tested prior to shipment. All unit wiring shall  
be both numbered and color coded. The cooling performance  
shall be rated in accordance with DOE and ARI test proce-  
dures. Units shall be CSA certified to ANSI Z21.47 and UL  
1995/CAN/CSA No. 236-M90 standards.  
REFRIGERANT COMPONENTS  
Compressors:  
a. Shall be scroll type, direct drive, internally protected with  
internal high-pressure relief and over temperature pro-  
tection. The hermetic motor shall be suction gas cooled  
and have a voltage range of + or – 10% of the unit name-  
plate voltage.  
UNIT CABINET  
Unit cabinet shall be constructed of G90 galvanized steel with  
exterior surfaces coated with a non-chalking, powder paint  
finish, certified at 1000 hours salt spray test per ASTM-B117  
standards. Indoor blower sections shall be insulated with  
1/2” thick insulation coated on the airside. Aluminum foil  
faced insulation shall be used in the unit’s compartments and  
be fastened to prevent insulation from entering the air  
stream. Cabinet doors shall be hinged with toolless access  
for easy servicing and maintenance. Full perimeter base rails  
shall be provided to assure reliable transit of equipment,  
overhead rigging, fork truck access and proper sealing on  
roof curb applications. Disposable 2” filters shall be fur-  
nished and be accessible through hinged access door. Fan  
performance measuring ports shall be provided on the out-  
side of the cabinet to allow accurate air measurements of  
b. Shall have internal spring isolation and sound muffling to  
minimize vibration and noise, and be externally isolated  
on a dedicated, independent mounting.  
Coils:  
a. Evaporator and condenser coils shall have aluminum  
plate fins mechanically bonded to seamless internally  
enhanced copper tubes with all joints brazed. Special  
Phenolic coating shall be available as a factory option.  
b. Evaporator and condenser coils shall be of the direct  
expansion, draw-thru design.  
26  
Johnson Controls Unitary Products  
 
246695-YTG-C-0708  
Refrigerant Circuit and Refrigerant Safety Components shall  
include:  
ing temperature of 40 °F. Burners shall be of the in-shot type,  
constructed of aluminum-coated steel. All gas piping shall  
enter the unit cabinet at a single location, through either the  
side or bottom, without any field modifications. An integrated  
control board shall provide timed control of evaporator fan  
functioning and burner ignition. Heating section shall be pro-  
vided with the following minimum protection:  
a. Independent fixed-orifice or thermally operated expan-  
sion devices.  
b. Solid core filter drier/strainer to eliminate any moisture or  
foreign matter.  
a. Primary and auxiliary high-temperature limit switches.  
b. Induced draft pressure sensor.  
c. Accessible service gage connections on both suction  
and discharge lines to charge, evacuate, and measure  
refrigerant pressure during any necessary servicing or  
troubleshooting, without losing charge.  
c. Flame roll out switch (manual reset).  
d. The unit shall have two independent refrigerant circuits,  
equally split in 50% capacity increments.  
d. Flame proving controls. Unit shall have two independent  
st  
nd  
stages of capacity (60% 1 stage, 100% 2 stage).  
Unit Controls:  
ELECTRIC HEATING SECTION (IF EQUIPPED)  
a. Unit shall be complete with self-contained low-voltage  
control circuit protected by a resetable circuit breaker on  
the 24-volt transformer side.  
An electric heating section, with nickel chromium elements,  
shall be provided in a range of 9 thru 54 KW, offering two  
stages of capacity all sizes. The heating section shall have a  
primary limit control(s) (automatic reset) to prevent the heat-  
ing element system from operating at an excessive tempera-  
ture. The Heating Section assembly shall slide out of the unit  
for easy maintenance and service. Units with Electric Heating  
Sections shall be wired for a single point power supply with  
branch circuit fusing (where required).  
b. Unit shall incorporate a lockout circuit which provides  
reset capability at the space thermostat or base unit,  
should any of the following standard safety devices trip  
and shut off compressor:  
(1) loss-of-charge/Low-pressure switch,  
(2) high-pressure switch,  
UNIT OPERATING CHARACTERISTICS  
Unit shall be capable of starting and running at 125 °F out-  
door temperature, exceeding maximum load criteria of ARI  
Standard 340/360. The compressor, with standard controls,  
shall be capable of operation down to 0 °F outdoor tempera-  
ture. Unit shall be provided with fan time delay to prevent cold  
air delivery before heat exchanger warms up. (Gas heat  
only).  
(3) freeze-protection thermostat, evaporator coil.  
c. If any of the above safety devices trip, a LED (light-emit-  
ting diode) indicator shall flash a diagnostic code that  
indicates which safety switch has tripped.  
d. Unit shall incorporate “AUTO RESET” compressor over  
temperature, over current protection.  
ELECTRICAL REQUIREMENTS  
e. Unit shall operate with conventional thermostat designs  
and have a low voltage terminal strip for easy hook-up.  
All unit power wiring shall enter unit cabinet at a single factory  
provided location and be capable of side or bottom entry to  
minimize roof penetrations and avoid unit field modifications.  
Separate side and bottom openings shall be provided for the  
control wiring.  
f. Unit control board shall have on-board diagnostics and  
fault code display.  
g. Standard controls shall include anti-short cycle and low  
voltage protection, and permit cooling operation down to  
0 °F.  
STANDARD LIMITED WARRANTIES  
Compressor – 5 Years, Heat Exchanger – 10 Years, Elect.  
Heat Elem. – 5 Years, Parts – 1 Year  
h. Control board shall monitor each refrigerant safety  
switch independently.  
FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall  
be made available by either/or):  
i.  
Control board shall retain last 5 fault codes in non vola-  
tile memory, which will not be lost in the event of a power  
loss.  
1. ELECTRONIC ENTHALPY AUTOMATIC ECONO-  
MIZER – Outdoor and return air dampers that are inter-  
locked and positioned by a fully-modulating, spring-  
return damper actuator. The maximum leakage rate for  
the outdoor air intake dampers shall not exceed 2%  
when dampers are fully closed and operating against a  
pressure differential of 0.5 IWG. A unit-mounted potenti-  
ometer shall be provided to adjust the outdoor and return  
air damper assembly to take in outdoor air to meet the  
minimum ventilation requirement of the conditioned  
GAS HEATING SECTION (IF EQUIPPED)  
Heat exchanger and exhaust system shall be constructed of  
aluminized steel or optional stainless steel. Shall be designed  
with induced draft combustion with post purge logic, energy  
saving direct spark ignition, and redundant main gas valve.  
The heat exchanger shall be of the tubular type, constructed  
of T1-40 aluminized steel (or optional 304 stainless steel) for  
corrosion resistance and allowing minimum mixed air enter-  
Johnson Controls Unitary Products  
27  
space during normal operation. During economizer oper-  
ation, a mixed-air temperature control shall modulate the  
outdoor and return air damper assembly to prevent the  
supply air temperature from dropping below 55 °F.  
Changeover from compressor to economizer operation  
shall be provided by an integral electronic enthalpy con-  
trol that feeds input into the basic module. The outdoor  
intake opening shall be covered with a rain hood that  
matches the exterior of the unit. Water eliminator/filters  
shall be provided. Simultaneous economizer/compressor  
operation is also possible. Dampers shall fully close on  
power loss. Available with barometric relief or power  
exhaust.  
DIRTY FILTER SWITCH – This kit includes a differential  
pressure switch that energizes the fault light on the unit  
thermostat, indicating that there is an abnormally high-  
pressure drop across the filters.  
BREAKER – An HACR breaker can be factory installed  
on the gas heat units or cooling units with electric heater.  
DISCONNECT SWITCH - A disconnect can be factory  
installed on cooling only units, sized for the largest elec-  
tric heat available.  
ELECTRIC HEAT - The electric heaters range from 18  
kW to 54 kW and are available in all the voltage options  
of the base units.  
2. MOTORIZED OUTDOOR AIR DAMPERS – Outdoor  
and return air dampers that are interlocked and posi-  
tioned by a 2-position, spring-return damper actuator.  
The maximum leakage rate for the outdoor air intake  
dampers shall not exceed 2% when dampers are fully  
closed and operating against a pressure differential of  
0.5 IWG. A unit-mounted potentiometer shall be provided  
to adjust the outdoor and return air damper assembly to  
take in the design CFM of outdoor air to meet the ventila-  
tion requirements of the conditioned space during normal  
operation. Whenever the indoor fan motor is energized,  
the dampers open up to one of two pre-selected posi-  
tions – regardless of the outdoor air enthalpy. Dampers  
return to the fully closed position when the indoor fan  
motor is de-energized. Dampers shall fully close on  
power loss.  
STAINLESS STEEL HEAT EXCHANGER – For applica-  
tions in a corrosive environment, this option provides a  
full stainless steel heat exchanger assembly.  
STAINLESS STEEL DRAIN PAN - Provides years of  
trouble free operation in corrosive environments.  
SMOKE DETECTOR – A smoke detector can be factory  
mounted and wired in the supply and/or return air com-  
partments.  
OTHER PRE-ENGINEERED ACCESSORIES AVAIL-  
ABLE  
ROOF CURB - 14” and 8” high, full perimeter knockdown  
curb, with hinged design for quick assembly.  
BAROMETRIC RELIEF DAMPER – (Unit mounted –  
Downflow, Duct Mounted – Sideflow) – Contains a rain  
hood, air inlet screen, exhaust damper and mounting  
hardware. Used to relieve internal air pressure through  
the unit during economizer operation.  
ADDITIONAL FACTORY INSTALLED OPTIONS  
ALTERNATE INDOOR BLOWER MOTOR – For appli-  
cations with high restrictions, units are available with  
optional indoor blower motors that provide higher static  
output and/or higher airflow.  
PROPANE CONVERSION KIT – Contains new orifices  
and gas valve springs to convert from natural to L.P. gas.  
CONVENIENCE OUTLET (POWERED/NON-POW-  
ERED) – Unit can be provided with an optional 120VAC  
GFCI outlet with cover on the corner of the unit housing  
the compressors.  
–60 °F GAS HEAT KIT – Provides an electric heat kit for  
the gas compartment for use in extreme low ambient  
conditions.  
PHASE MONITOR - Designed to prevent damage in out-  
of-phase condition.  
ECONOMIZER (Downflow and Sideflow)  
POWER EXHAUST – (Unit mount – Downflow, Duct  
mount – Sideflow)  
COIL GUARD - Designed to prevent condenser coil  
damage.  
DUAL ENTHALPY KIT - Provides a second input to  
economizer to monitor return air.  
BAS CONTROLS - Include supply air sensor, return air  
sensor, dirty filter indicator and air proving switch.  
Subject to change without notice. Printed in U.S.A.  
246695-YTG-C-0708  
Copyright © 2008 by Johnson Controls, Inc. All rights reserved.  
Supersedes: 246695-YTG-B-0606  
Johnson Controls Unitary Products  
5005 York Drive  
Norman, OK 73069  

Master Lock B70cea User Manual
Minolta W121ca Tsc2 User Manual
Mitsubishi Motors Automobile Parts F5mr2 User Manual
Murphy Cng 92200h User Manual
Panasonic Cu A7ckp5 User Manual
Philips Scd499 User Manual
Sanyo Kr 1700au User Manual
Sears 2871234 User Manual
Sterling Sterlcool Cfp25 A User Manual
T Tech 1002 User Manual