INSTALLATION
MANUAL
MAGNUM
CONTENTS
SINGLE PACKAGE AIR CONDITIONERS AND
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . .4
INSPECTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
REFERENCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
RENEWAL PARTS . . . . . . . . . . . . . . . . . . . . . . . . . .5
APPROVALS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . .6
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
START-UP (COOLING). . . . . . . . . . . . . . . . . . . . . .39
START-UP (GAS HEAT). . . . . . . . . . . . . . . . . . . . .39
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . .43
SINGLE PACKAGE GAS/ELECTRIC UNITS
DJ150
12-1/2 TON
(10.8 EER)
See following pages for a complete Table of Contents.
NOTES, CAUTIONS AND WARNINGS
The installer should pay particular attention to the words:
NOTE, CAUTION, and WARNING. Notes are intended to
clarify or make the installation easier. Cautions are given
to prevent equipment damage. Warnings are given to alert
installer that personal injury and/or equipment damage
may result if installation procedure is not handled properly.
Tested in accordance with:
CAUTION: READ ALL SAFETY GUIDES BEFORE YOU
BEGIN TO INSTALL YOUR UNIT.
SAVE THIS MANUAL
035-19046-002-B-0104
035-19046-002-B-0104
LIST OF FIGURES
Pg. # Fig. #
UNIT SHIPPING BRACKET . . . . . . . . . . . . . . . . . . . . . 8
Fig. #
Pg. #
1
2
3
4
5
6
7
8
9
16 ELECTRONIC THERMOSTAT FIELD WIRING . . . . . 18
17 FIELD WIRING 24 VOLT THERMOSTAT . . . . . . . . . 19
COMPRESSOR SECTION . . . . . . . . . . . . . . . . . . . . . . 9
PREDATOR“ MAGNUM COMPONENT LOCATION . 10
UNIT 4 POINT LOAD . . . . . . . . . . . . . . . . . . . . . . . . . 11
UNIT 6 POINT LOAD . . . . . . . . . . . . . . . . . . . . . . . . . 12
UNIT CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . 12
UNIT DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 13
BOTTOM DUCT OPENINGS (FROM ABOVE). . . . . . 14
REAR DUCT DIMENSIONS . . . . . . . . . . . . . . . . . . . . 15
18 FIELD WIRING DISCONNECT - COOLING UNIT
WITH/WITHOUT ELECTRIC HEAT . . . . . . . . . . . . . . 19
19 FIELD WIRING DISCONNECT - COOLING UNIT
WITH GAS HEAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
20 SIDE ENTRY GAS PIPING. . . . . . . . . . . . . . . . . . . . . 23
21 BOTTOM ENTRY GAS PIPING . . . . . . . . . . . . . . . . . 23
22 ENTHALPY SET POINT CHART . . . . . . . . . . . . . . . . 27
23 HONEYWELL ECONOMIZER CONTROL W7212. . . 27
24 BELT ADJUSTMENT . . . . . . . . . . . . . . . . . . . . . . . . . 28
25 DRY COIL DELTA P. . . . . . . . . . . . . . . . . . . . . . . . . . 32
26 TYPICAL FLAME . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
27 TYPICAL GAS VALVE . . . . . . . . . . . . . . . . . . . . . . . . 42
28 BASIC TROUBLESHOOTING FLOWCHART . . . . . . 44
29 POWER ON FLOW CHART . . . . . . . . . . . . . . . . . . . . 44
30 TRIP FAILURE FLOW CHART. . . . . . . . . . . . . . . . . . 45
10 PREDATOR“ MAGNUM ROOF CURB
DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
11 SUNLINE™ TO PREDATOR“ MAGNUM
TRANSITION ROOF CURBS . . . . . . . . . . . . . . . . . . . 16
12 SIDE PANELS WITH HOLE PLUGS. . . . . . . . . . . . . . 16
13 RETURN DOWNFLOW PLENUM WITH PANEL . . . . 17
14 DISCHARGE PANEL IN PLACE. . . . . . . . . . . . . . . . . 17
15 CONDENSATE DRAIN . . . . . . . . . . . . . . . . . . . . . . . . 17
LIST OF TABLES
Tbl. #
Pg. #
Tbl. #
Pg. #
1
2
3
4
5
6
7
8
UNIT VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . 11
UNIT TEMPERATURE LIMITATIONS 11
16 DJ150, 12-1/2 TON OPTIONAL MOTOR DOWN
SHOT BLOWER PERFORMANCE. . . . . . . . . . . . . . . 29
17 DJ150, 12-1/2 TON STANDARD MOTOR SIDE
SHOT BLOWER PERFORMANCE. . . . . . . . . . . . . . . 30
UNIT WEIGHTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4 POINT LOAD WEIGHT. . . . . . . . . . . . . . . . . . . . . . . 12
6 POINT LOAD WEIGHT. . . . . . . . . . . . . . . . . . . . . . . 12
UNIT CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . . . 13
CONTROL WIRE SIZES . . . . . . . . . . . . . . . . . . . . . . . 17
18 DJ150, 12-1/2 TON OPTIONAL MOTOR SIDE
SHOT BLOWER PERFORMANCE. . . . . . . . . . . . . . . 30
19 INDOOR BLOWER SPECIFICATIONS. . . . . . . . . . . . 31
20 ADDITIONAL STATIC RESISTANCE . . . . . . . . . . . . . 33
21 MOTOR SHEAVE DATUM DIAMETERS . . . . . . . . . . 33
22 ELECTRIC HEAT LIMIT SETTING . . . . . . . . . . . . . . . 36
23 ELECTRIC HEAT ANTICIPATOR SETPOINTS . . . . . 36
24 GAS HEAT LIMIT CONTROL SETTINGS. . . . . . . . . . 38
25 GAS HEAT ANTICIPATOR SETPOINTS . . . . . . . . . . 39
26 GAS HEAT STAGES. . . . . . . . . . . . . . . . . . . . . . . . . . 40
27 GAS RATE CUBIC FEET PER HOUR . . . . . . . . . . . . 41
28 UNIT CONTROL BOARD FLASH CODES . . . . . . . . . 43
29 IGNITION CONTROL FLASH CODES . . . . . . . . . . . . 43
ELECTRICAL DATA DJ150 (12-1/2 TON) WITHOUT
POWERED CONVENIENCE OUTLET . . . . . . . . . . . . 21
9
ELECTRICAL DATA DJ150 (12-1/2 TON) WITH
POWERED CONVENIENCE OUTLET . . . . . . . . . . . . 21
10 PHYSICAL DATA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
11 MINIMUM SUPPLY AIR CFM . . . . . . . . . . . . . . . . . . . 22
12 GAS HEAT APPLICATION DATA . . . . . . . . . . . . . . . . 23
13 GAS PIPE SIZING - CAPACITY OF PIPE. . . . . . . . . . 23
14 SUPPLY AIR LIMITATIONS . . . . . . . . . . . . . . . . . . . . 28
15 DJ150, 12-1/2 TON STANDARD MOTOR DOWN
SHOT BLOWER PERFORMANCE . . . . . . . . . . . . . . . 29
Unitary Products Group
3
035-19046-002-B-0104
GENERAL
YORK Predator Magnum units are single package air con-
ditioners with optional gas heating designed for outdoor
installation on a rooftop or slab and for non-residential use.
These units can be equipped with factory or field installed
electric heaters for heating applications.
If the information in this manual is not followed
exactly, a fire or explosion may result causing prop-
erty damage, personal injury or loss of life.
Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
These units are completely assembled on rigid, permanently
attached base rails. All piping, refrigerant charge, and electri-
cal wiring is factory installed and tested. The units require
electric power, gas supply (where applicable), and duct con-
nections. The electric heaters have nickel-chrome elements
and utilize single-point power connection.
WHAT TO DO IF YOU SMELL GAS:
a. Do not try to light any appliance.
b. Do not touch any electrical switch; do not use
any phone in your building.
SAFETY CONSIDERATIONS
c. Immediately call your gas supplier from a neigh-
bor’s phone. Follow the gas supplier’s instruc-
tions.
d. If you cannot reach your gas supplier, call the fire
department.
Should overheating occur, or the gas supply fail to
shut off, shut off the manual gas valve to the furnace
before shutting off the electrical supply.
Installation and service must be performed by a
qualified installer, service agency or the gas sup-
plier.
Do not use this furnace if any part has been under
water. Immediately call a qualified service technician
to inspect the furnace and to replace any part of the
control system and any gas control which has been
under water.
INSPECTION
As soon as a unit is received, it should be inspected for possi-
ble damage during transit. If damage is evident, the extent of
the damage should be noted on the carrier’s freight bill. A
separate request for inspection by the carrier’s agent should
be made in writing.
Due to system pressure, moving parts, and electrical compo-
nents, installation and servicing of air conditioning equipment
can be hazardous. Only qualified, trained service personnel
should install, repair, or service this equipment. Untrained
personnel can perform basic maintenance functions of clean-
ing coils and filters and replacing filters.
Observe all precautions in the literature, labels, and tags
accompanying the equipment whenever working on air condi-
tioning equipment. Be sure to follow all other applicable
safety precautions and codes including ANSI Z223.1 or CSA-
B149.1- latest edition.
This furnace is not to be used for temporary heating
of buildings or structures under construction.
Before performing service or maintenance opera-
tions on unit, turn off main power switch to unit. Elec-
trical shock could cause personal injury. Improper
installation, adjustment, alteration, service or main-
tenance can cause injury or property damage. Refer
to this manual. For assistance or additional informa-
tion consult a qualified installer, service agency or
the gas supplier.
Wear safety glasses and work gloves. Use quenching cloth
and have a fire extinguisher available during brazing opera-
tions.
4
Unitary Products Group
035-19046-002-B-0104
REFERENCE
APPROVALS
Additional information is available in the following reference
forms:
Design certified by CSA as follows:
1. For use as a cooling only unit, cooling unit with supple-
mental electric heat or a forced air furnace.
•
•
•
•
Technical Guide - DJ150, 036-21484-002
General Installation - DJ150, 035-19046-002
Pre-start & Post-start Check List - 035-18466-000
2. For outdoor installation only.
3. For installation on combustible material and may be
installed directly on combustible flooring or, in the U.S.,
on wood flooring or Class A, Class B or Class C roof cov-
ering materials.
Economizer Accessory -
Downflow Factory Installed, 035-18286-000
Downflow Field Installed, 035-18285-000
Horizontal Field Installed, 035-18287-000
4. For use with natural gas (convertible to LP with kit).
•
•
•
•
•
•
•
•
•
Motorized Outdoor Air Damper 035-18283-000
Manual Outdoor Air Damper (0-100%) 035-18282-000
Manual Outdoor Air Damper (0-35%) 035-18281-000
Gas Heat Propane Conversion Kit 035-17374-000
Gas Heat High Altitude Kit (Natural Gas) 035-17282-000
Gas Heat High Altitude Kit (Propane) 035-17281-000
–60°F Gas Heat Kit 035-18216-000
This product must be installed in strict compliance
with the enclosed installation instructions and any
applicable local, state, and national codes including,
but not limited to, building, electrical, and mechanical
codes.
Electric Heater Accessory 035-17291-001
Unit Renewal Parts List 035-19085-000
All forms referenced in this instruction may be ordered from:
Standard Register
Toll Free Fax: (877) 379-7920
Toll Free Phone: (877) 318-9675
Incorrect installation may create a condition where the
operation of the product could cause personal injury
or property damage.
RENEWAL PARTS
The installer should pay particular attention to the words:
NOTE, CAUTION, and WARNING. NOTES are intended to
clarify or make the installation easier. CAUTIONS are given
to prevent equipment damage. WARNINGS are given to alert
installer that personal injury and/or equipment damage may
result if installation procedure is not handled properly.
Refer to York’s USER’S MAINTENANCE and SERVICE
INFORMATION MANUAL Part Number 035-19047-001.
Unitary Products Group
5
035-19046-002-B-0104
NOMENCLATURE
12½ Ton Predator Model Number Nomenclature
D J 150 N15 A 2 A AA 3
Product Generation
Product Category
3 = Third Generation
D = Air Cond., Single Package
Additional Options
Installation Options
Product Identifier
Voltage
J = R-22 Ultra High Efficiency
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
A = No Options Installed
B = Option 1
C = Option 2
(See Next Page)
D = Options 1 & 2
E = Option 3
F = Option 4
Nominal Cooling Capacity - MBH
150 = 12-½ Ton
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2 & 4
L = Options 1, 3 & 4
M = Options 1, 2, 3 & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3 & 4
R = Options 3 & 4
S = Option 5
Heat Type & Nominal Heat Capacity
C00 = Cooling Only. Suitable for field installed electric heat
Gas Heat Options
N 15 = 150 MBH Output Aluminized Steel
N 20 = 200 MBH Output Aluminized Steel
T = Options 1 & 5
U = Options 1, 3 & 5
V = Options 1, 4 & 5
W = Options 1, 3, 4 & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
S 15 = 150 MBH Output Stainless Steel
S 20 = 200 MBH Output Stainless Steel
Electric Heat Options
Options
E18 = 18 kW Electric Heat
E24 = 24 kW Electric Heat
E36 = 36 kW Electric Heat
E54 = 54 kW Electric Heat
1 = Disconnect
2 = Non-Pwr’d Conv Outlet
3 = Smoke Detector S. A.
4 = Smoke Detector R. A.
5 = Pwr’d Conv Outlet
Airflow
A = Standard Motor
B = Standard Motor/Economizer/Barometric Relief (Downflow only)
C = Standard Motor/Economizer/Power Exhaust (Downflow only)
D = Standard Motor/Motorized Damper (Downflow only)
E = Standard Motor/Horizontal Economizer (No Barometric Relief)
F = Standard Motor/Slab Economizer/Power Exhaust (Downflow only)
G = Standard Motor/Slab Economizer/Barometric Relief (Downflow only)
L = Standard Motor/BAS Ready Econ (NoBASController)/Barometric Relief w/2" Pleated Filters (Downflow only)
M = Standard Motor/BAS Ready Econ (NoBASController)/Power Exhaust w/2" Pleated Filters (Downflow only)
N = High Static Motor
P = High Static Motor/Economizer/Barometric Relief (Downflow only)
Q = High Static Motor/Economizer/Power Exhaust (Downflow only)
R = High Static Motor/Motorized Damper (Downflow only)
S = High Static Motor/Horizontal Economizer (No Barometric Relief)
T = High Static Motor/Slab Economizer/Power Exhaust (Downflow only)
U =High Static Motor/Slab Economizer/Barometric Relief (Downflow only)
Y = High Static Motor/BAS Ready Econ (NoBASController)/Barometric Relief w/2" Pleated Filters (Downflow only)
Z = High Static Motor/BAS Ready Econ (NoBASController)/Power Exhaust w/2" Pleated Filters (Downflow only)
6
Unitary Products Group
035-19046-002-B-0104
NOMENCLATURE, ADDITIONAL OPTIONS:
AA None
AC Coil Guard
AD Dirty Filter Switch
AG Coil Guard & Dirty Filter Switch
CA CPC Controller with Dirty Filter Switch & Air Proving Switch
CC CPC Controller, DFS, APS & Coil Guard
CE CPC Controller, DFS, APS & Technicoat Cond. Coil
CG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
CJ CPC Controller, DFS, APS & Technicoat Evap. Coil
CL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
CN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils
CQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
CV CPC Controller, DFS, APS, & 2” Pleated Filters
HA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch
HC Honeywell Excel 10 Controller, DFS, APS & Coil Guard
HE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil
HG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
HJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil
HL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
HN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils
HQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
JA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch
JC Johnson UNT Controller, DFS, APS & Coil Guard
JE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil
JG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
JJ
JL
Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
JN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils
JQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
NA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch
NC Novar ETC-3 Controller, DFS, APS & Coil Guard
NE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil
NG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
NJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil
NL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
NN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils
NQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
TA Technicoat Condenser Coil
Unitary Products Group
7
035-19046-002-B-0104
TC Technicoat Condenser Coil & Coil Guard
TD Technicoat Condenser Coil & Dirty Filter Switch
TG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch
TJ Technicoat Evaporator Coil
TL Technicoat Evaporator Coil & Coil Guard
TM Technicoat Evaporator Coil & Dirty Filter Switch
TQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch
TS Technicoat Evaporator & Condenser Coils
TU Technicoat Evaporator & Condenser Coils & Coil Guard
TV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch
TY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch
INSTALLATION
INSTALLATION SAFETY INFORMATION
FIRE OR EXPLOSION HAZARD
Read these instructions before continuing this appliance
installation. This is an outdoor combination heating and cool-
ing unit. The installer must assure that these instructions are
made available to the consumer and with instructions to
retain them for future reference.
Failure to follow the safety warning exactly could
result in serious injury, death or property damage.
Never test for gas leaks with an open flame. use a
commercially available soap solution made specifi-
cally for the detection of leaks to check all connec-
tions. A fire or explosion may result causing property
damage, personal injury or loss of life.
1. Refer to the furnace rating plate for the approved type of
gas for this furnace.
2. Install this furnace only in a location and position as
specified on Page 11 of these instructions.
PRECEDING INSTALLATION
1. Remove the two screws holding the brackets in the front,
rear and compressor side fork-lift slots.
3. Never test for gas leaks with an open flame. Use com-
mercially available soap solution made specifically for
the detection of leaks when checking all connections, as
specified on Pages 8, 24, 25 and 40 of these instruc-
tions.
4. Always install furnace to operate within the furnace's
intended temperature-rise range with the duct system
and within the allowable external static pressure range,
as specified on the unit name/rating plate, specified on
Page 42 of these instructions.
Bracket
Turn down
Screws
5. This equipment is not to be used for temporary heating
of buildings or structures under construction.
FIGURE 1 - UNIT SHIPPING BRACKET
8
Unitary Products Group
035-19046-002-B-0104
2. Turn each bracket toward the ground and the protective
plywood covering will drop to the ground.
LIMITATIONS
These units must be installed in accordance with the follow-
ing:
3. Remove the condenser coil external protective covering
prior to operation.
4. Remove the toolless doorknobs and instruction packet
prior to installation.
In U.S.A.:
1. National Electrical Code, ANSI/NFPA No. 70 - Latest
Edition
2. National Fuel Gas Code, ANSI Z223.1 - Latest Edition
3. Gas-Fired Central Furnace Standard, ANSI Z21.47a. -
Latest Edition
4. Local building codes, and
5. Local gas utility requirements
In Canada:
Toolless
Doorknobs
1. Canadian Electrical Code, CSA C22.1
2. Installation Codes, CSA - B149.1.
3. Local plumbing and waste water codes, and
4. Other applicable local codes.
Refer to Tables 1 & 2 for unit application data.
Installation
Instruction
Packet
FIGURE 2 - COMPRESSOR SECTION
After installation, gas fired units must be adjusted to obtain a
temperature rise within the range specified on the unit rating
plate.
If components are to be added to a unit to meet local codes,
they are to be installed at the dealer’s and/or customer’s
expense.
This product must be installed in strict compliance
with the enclosed installation instructions and any
applicable local, state and national codes including,
but not limited to, building, electrical, and mechani-
cal codes.
Size of unit for proposed installation should be based on heat
loss/heat gain calculation made according to the methods of
Air Conditioning Contractors of America (ACCA).
The furnace and its individual shut-off valve must be
disconnected from the gas supply piping system
during any pressure testing at pressures in excess
of 1/2 PSIG.
This furnace is not to be used for temporary heating of build-
ings or structures under construction.
Pressures greater than 1/2 PSIG will cause gas
valve damage resulting in a hazardous condition. If it
is subjected to a pressure greater than 1/2 PSIG, the
gas valve must be replaced.
The furnace must be isolated from the gas supply
piping system by closing its individual manual shut-
off valve during any pressure testing of the gas sup-
ply piping system at test pressures equal to or less
than 1/2 PSIG.
Unitary Products Group
9
035-19046-002-B-0104
"Simplicity™" Control
board w/screw
Disconnect
location
(optional disconnect switch)
Filter access
(2" throw-away)
Filter drier
(solid core)
connectors for T-stat
wiring and Network
connection
Second model
nameplate inside
hinged access panel
Condenser
Section
Belt-drive blower
motor
Dual stage cooling
for maximum comfort
Slide out motor
and blower
assembly for easy
adjustment and
service
Compressor #2
access (high-
efficiency compressor
w/crankcase heater)
Power ventor
motor
20-gauge
aluminized steel tubular
heat exchanger for long
life (stainless steel option)
Base rails w/forklift
slots (three sides)
and lifting holes
Roof curbs in eight and
fourteen-inch heights.
Roof curbs for
Two-stage gas heating to
maintain warm,
comfortable temperature
Slide-out drain pan
with brass 3/4" FPT
connection
transitioning from York
Sunline™ footprint to
the DM/DH/DJ/DR Series
footprint are available
(field-installed accessory)
Compressor #1 access
(high-efficiency
compressor w/
Tool-less door
latch
Intelligent control
board for safe and
efficient operation
Side entry power
and control wiring
knockouts
crankcase heater)
FIGURE 3 - PREDATOR MAGNUM COMPONENT LOCATION
10
Unitary Products Group
035-19046-002-B-0104
RIGGING AND HANDLING
TABLE 1: UNIT VOLTAGE LIMITATIONS
Power Rating*
Exercise care when moving the unit. Do not remove any
packaging until the unit is near the place of installation. Rig
the unit by attaching chain or cable slings to the lifting holes
provided in the base rails. Spreader bars, whose length
exceeds the largest dimension across the unit, MUST be
used across the top of the unit.
Minimum
Maximum
208/230-3-60
460-3-60
187
432
540
252
504
630
575-3-60
*.
Utilization range “A” in accordance with ARI Standard 110.
TABLE 2: UNIT TEMPERATURE LIMITATIONS
Temperature
Min.
Max.
If a unit is to be installed on a roof curb other than a
YORK roof curb, gasketing must be applied to all
surfaces that come in contact with the unit under-
side.
Wet Bulb Temperature (°F) of Air on
57
72
Evaporator Coil
Dry Bulb Temperature (°F) of Air on
0*
125
Condenser Coil
*.
A low ambient accessory is available for operation
down to -20°F.
LOCATION
Before lifting, make sure the unit weight is distrib-
uted equally on the rigging cables so it will lift evenly.
Use the following guidelines to select a suitable location for
these units:
1. Unit is designed for outdoor installation only.
Units may be moved or lifted with a forklift. Slotted openings
in the base rails are provided for this purpose.
2. Condenser coils must have an unlimited supply of air.
Where a choice of location is possible, position the unit
on either north or east side of building.
LENGTH OF FORKS MUST BE A MINIMUM OF 60
INCHES.
3. Suitable for mounting on roof curb.
4. For ground level installation, use a level concrete slab
with a minimum thickness of 4 inches. The length and
width should be at least 6 inches greater than the unit
base rails. Do not tie slab to the building foundation.
All panels must be secured in place when the unit is
lifted.
5. Roof structures must be able to support the weight of the
unit and its options/accessories. Unit must be installed
on a solid, level roof curb or appropriate angle iron
frame.
The condenser coils should be protected from rig-
ging cable damage with plywood or other suitable
material.
6. Maintain level tolerance to 1/2” across the entire width
and length of unit.
Excessive exposure of this furnace to contaminated
combustion air may result in equipment damage or
personal injury. Typical contaminates include: per-
manent wave solution, chlorinated waxes and clean-
ers, chlorine based swimming pool chemicals, water
softening chemicals, carbon tetrachloride, Halogen
type refrigerants, cleaning solvents (e.g. perchloro-
ethylene), printing inks, paint removers, varnishes,
hydrochloric acid, cements and glues, antistatic fab-
ric softeners for clothes dryers, masonry acid wash-
ing materials.
FRONT
LEFT
C
B
A
D
FIGURE 4 - UNIT 4 POINT LOAD
Unitary Products Group
11
035-19046-002-B-0104
CLEARANCES
TABLE 3: UNIT WEIGHTS
Operating
Weight (lb.)
1400
All units require particular clearances for proper operation
and service. Installer must make provisions for adequate
combustion and ventilation air in accordance with section 5.3
of Air for Combustion and Ventilation of the National Fuel Gas
Code, ANSI Z223.1 – Latest Edition (in U.S.A.), or Sections
7.2, 7.3, or 7.4 of Gas Installation Codes, CSA-B149.1 (in
Canada) - Latest Edition, and/or applicable provisions of the
local building codes. Refer to Table 6 for clearances required
for combustible construction, servicing, and proper unit oper-
ation.
Shipping
Weight (lb.)
Model DJ150
Cooling Unit Only
w/Economizer
1415
85
84
150
148
w/Power Exhaust
w/Gas Heat*
110
49
110
49
w/Electric Heat†
*.
†.
8 Tube Heat Exchanger
54 kW heater
TABLE 4: 4 POINT LOAD WEIGHT
Location (lbs.)*
Model
DJ150
A
B
C
D
282
323
424
371
Do not permit overhanging structures or shrubs to
obstruct condenser air discharge outlet, combustion
air inlet or vent outlets.
*.
Weights include largest gas heat option.
TABLE 5: 6 POINT LOAD WEIGHT
Location (lbs.)*
Model
DJ150
A
B
C
D
E
F
184
201
220
289
264
242
*.
Excessive exposure to contaminated combustion air
will result in safety and performance related prob-
lems. To maintain combustion air quality, the recom-
mended source of combustion air is the outdoor air
supply. The outdoor air supplied for combustion
should be free from contaminants due to chemical
exposure that may be present from the following
sources.
Weights include largest gas heat option.
•
•
•
•
•
Commercial buildings
Indoor pools
Laundry rooms
Hobby or craft rooms
Chemical storage areas
FRONT
LEFT
C
D
The following substances should be avoided to
maintain outdoor combustion air quality.
E
B
A
F
•
•
•
•
•
•
•
•
•
•
•
•
•
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine based swimming pool cleaners
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
FIGURE 5 - UNIT 6 POINT LOAD
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Anti-static fabric softeners for clothes dryers
Masonry acid washing materials
25-½"
47-½"
FRONT
LEFT
FIGURE 6 - UNIT CENTER OF GRAVITY
12
Unitary Products Group
035-19046-002-B-0104
119-7/16
30-11/32
See Detail A
Power
Entry
2-1/2
50-3/4
Con-
venience
Outlet
Control
Entry 7/8
4-1/4
11-1/2
Con-
venience
Outlet
Power
Entry
FRONT
7/8
For
Baserail
Dimensions
See
17-3/16
For Drain Dimensions
See Detail C
30-3/16
59
LEFT
24-3/16
6-3/16
Detail B
89
27
FIGURE 7 - UNIT DIMENSIONS
DETAIL A
2
-
3
/
8
DETAIL B
G
a
s
P
i
p
e
I
n
l
e
t
3
-
3
/
4
5
-
1
/
4
B
P
a
a
s
n
e
1
7
-
1
3
/
1
6
3
-
9
/
1
6
V
i
e
w
o
f
W
a
l
l
A
c
r
o
s
s
f
r
o
m
C
o
i
l
DETAIL C
TABLE 6: UNIT CLEARANCES
Top*
Front†
Rear‡
72”
36”
36”
12”
36”
0”
Right
Left
5
-
3
/
8
Bottom**
*.
Units must be installed outdoors. Overhanging struc-
ture or shrubs should not obstruct condenser air dis-
charge outlet.
NOTE: If the unit includes gas heating, locate the unit so
†.
‡.
The products of combustion must not be allowed to
accumulate within a confined space and re-circulate.
the flue exhaust is at least:
To remove the slide-out drain pan, a rear clearance of
sixty inches is required. If space is unavailable, the
drain pan can be removed through the front by separat-
ing the corner wall.
•
•
Three (3) feet above any forced air inlet located within 10
horizontal feet (excluding those integral to the unit).
**.
Four (4) feet below, four (4) horizontal feet from, or one
(1) foot above any door or gravity air inlet into the build-
ing.
Units may be installed on combustible floors made from
wood or class A, B or C roof covering materials.
NOTE: A one-inch clearance must be provided between
any combustible material and the supply ductwork
for a distance of 3 feet from the unit.
•
Four (4) feet from electric meters, gas meters, regula-
tors, and relief equipment.
Unitary Products Group
13
035-19046-002-B-0104
.
32-11/16
6-13/16
6-13/16
Supply
Air
6-13/16
Return
Air
24
27-1/2
LEFT
21
18
21-3/16
19-3/16
17-3/16
12-15/16
7-1/8
FRONT
14-
23/32
Bottom
Bottom Gas
Supply Entry
Bottom
Power, Control
and
Condensate
Entry
16-3/8
18-1/16
19-5/8
Convenience
Outlet Wiring
Entries
63-1/2
FIGURE 8 - BOTTOM DUCT OPENINGS (FROM ABOVE)
14
Unitary Products Group
035-19046-002-B-0104
18-1/4
Dot Plugs
28-1/4
Return
Air
Supply
Air
18-1/4
18-1/16
2-31/32
5-5/32
28-1/4
31-11/16
FIGURE 9 - REAR DUCT DIMENSIONS
DUCTWORK
DUCT COVERS
Units are shipped with the side duct openings covered and a
covering over the bottom of the unit. For bottom duct applica-
tion, no duct cover changes are necessary. For side duct
application, remove the side duct covers and install over the
bottom duct openings. The panels removed from the side
duct connections are designed to be reused by securing each
panel to its respective downflow opening. But keep in mind
that the supply panel is installed with the painted surface UP,
facing the heat exchanger, while the return panel is installed
with the painted surface DOWN, facing the downflow duct
opening. The supply panel is secured with the bracket
(already in place from the factory) and two screws. It’s a snug
fit for the panel when sliding it between the heat exchanger
and unit bottom, but there is room. The return panel is
secured with four screws.
Ductwork should be designed and sized according to the
methods in Manual D of the Air Conditioning Contractors of
America (ACCA) or as recommended by any other recog-
nized authority such as ASHRAE or SMACNA.
A closed return duct system should be used. This will not
preclude use of economizers or outdoor fresh air intake. The
supply and return air duct connections at the unit should be
made with flexible joints to minimize noise.
The supply and return air duct systems should be designed
for the CFM and static pressure requirements of the job. They
should NOT be sized to match the dimensions of the duct
connections on the unit.
Refer to Figure 8 for bottom air duct openings. Refer to Fig-
ure 9 for rear air duct openings.
Unitary Products Group
15
035-19046-002-B-0104
R
I
G
H
T
8
0
-
5
/
8
I
N
S
U
L
A
T
E
D
D
E
C
K
U
N
D
E
R
C
O
N
D
E
N
S
E
R
S
E
C
T
I
O
N
2
0
S
U
P
P
L
Y
2
0
6
R
E
T
U
R
N
2
T
Y
P
.
3
0
I
N
S
O
U
L
A
T
E
D
D
E
C
K
U
N
D
E
R
5
0
-
1
/
2
C
M
P
R
E
S
S
O
R
S
E
C
T
I
O
N
1
R
O
N
T
8
o
r
1
4
FIGURE 10 - PREDATOR MAGNUM ROOF CURB DIMENSIONS
2
T
Y
P
2
3
4
3
0
-
1
/
2
5
0
-
1
/
2
8
0
-
5
/
8
2
6
R
E
T
U
R
N
S
U
P
P
L
Y
1
0
7
6
-
5
/
8
5
9
-
1
/
4
9
4
1
R
O
N
T
R
I
G
H
T
6
4
-
1
/
4
FIGURE 11 - SUNLINE™ TO PREDATOR MAGNUM TRANSITION ROOF CURBS
When fastening ductwork to side duct flanges on
unit, insert screws through duct flanges only. DO
NOT insert screws through casing. Outdoor duct-
work must be insulated and water-proofed.
FIGURE 12 - SIDE PANELS WITH HOLE PLUGS
Note orientation. Panel is “insulation” side up.
16
Unitary Products Group
035-19046-002-B-0104
COMPRESSORS
The compressors are mounted on elastomer insulators. The
mounting bolts have been fully tightened for shipping.
Do not loosen the compressor mounting bolts.
FILTERS
Two-inch filters are supplied with each unit. One-inch filters
may be used with no modification to the filter racks. Filters
must always be installed ahead of evaporator coil and must
be kept clean or replaced with same size and type. Dirty fil-
ters reduce the capacity of the unit and result in frosted coils
or safety shutdown. All units use four (4) 20”x25”x2” filters.
The unit should not be operated without filters properly
installed.
FIGURE 13 - RETURN DOWNFLOW PLENUM WITH
PANEL
Make sure that panel latches are properly positioned
on the unit to maintain an airtight seal.
THERMOSTAT WIRING
FIGURE 14 - DISCHARGE PANEL IN PLACE
CONDENSATE DRAIN
The thermostat should be located on an inside wall approxi-
mately 56 inch above the floor where it will not be subject to
drafts, sun exposure or heat from electrical fixtures or appli-
ances. Follow the manufacturer's instructions enclosed with
thermostat for general installation procedure. Seven (7) color-
coded, insulated wires should be used to connect the thermo-
stat to the unit. Refer to Table 7 for control wire sizing and
maximum length.
The side condensate drain is reversible and maybe re-ori-
ented to the rear of the cabinet to facilitate condensate pip-
ing. A condensate drain connection is available through the
base pan for piping inside the roof curb. Trap the connection
per Figure 15. The trap and drain lines should be protected
from freezing.
TABLE 7: CONTROL WIRE SIZES
Plumbing must conform to local codes. Use a sealing com-
pound on male pipe threads. Install condensate drain line
from the 3/4 inch NPT female connection on the unit to an
open drain.
Maximum Length*
Wire Size
18 AWG
150 Feet
*.
From the unit to the thermostat and back to the unit.
POWER AND CONTROL WIRING
O
P
T
I
O
N
A
L
C
O
I
L
G
U
A
R
D
Field wiring to the unit, fuses, and disconnects must conform
to provisions of National Electrical Code (NEC), ANSI/NFPA
No. 70 – Latest Edition (in U.S.A.), current Canadian Electri-
cal Code C221, and/or local ordinances. The unit must be
electrically grounded in accordance with NEC and CEC as
specified above and/or local codes.
3
"
M
i
n
i
m
u
m
Voltage tolerances which must be maintained at the com-
pressor terminals during starting and running conditions are
indicated on the unit Rating Plate and Table 1.
FIGURE 15 - CONDENSATE DRAIN
Unitary Products Group
17
035-19046-002-B-0104
The internal wiring harnesses furnished with this unit are an
integral part of the design certified unit. Field alteration to
comply with electrical codes should not be required. If any of
the wire supplied with the unit must be replaced, replacement
wire must be of the type shown on the wiring diagram and the
same minimum gauge as the replaced wire.
Refer to Figures 16, 17 and 18 for typical field wiring and to
the appropriate unit wiring diagram mounted inside control
doors for control circuit and power wiring information.
A disconnect must be utilized for these units. Factory
installed disconnects are available. If installing a disconnect
When connecting electrical power and control wiring
to the unit, water-proof connectors must be used so
that water or moisture cannot be drawn into the unit
during normal operation. The above water-proofing
conditions will also apply when installing a field sup-
plied disconnect switch.
(field supplied or York International supplied accessory),
refer to Figure 3 for the recommended mounting location.
Avoid damage to internal components if drilling
holes for disconnect mounting.
POWER WIRING DETAIL
Units are factory wired for the voltage shown on the unit
nameplate. Refer to Electrical Data Tables 8 and 9 to size
power wiring, fuses, and disconnect switch.
NOTE: Since not all local codes allow the mounting of a dis-
connect on the unit, please confirm compliance with
local code before mounting a disconnect on the unit.
Power wiring is brought into the unit through the side of the
unit or the basepan inside the curb.
Electrical line must be sized properly to carry the load. USE
COPPER CONDUCTORS ONLY. Each unit must be wired
with a separate branch circuit fed directly from the meter
panel and properly fused.
1
T
H
E
R
M
O
S
T
A
T
T
E
R
M
I
N
A
L
S
U
N
I
T
T
E
R
M
I
N
A
L
S
S
T
R
I
P
T
B
1
R
C
R
H
R
Y
1
Y
1
Y
2
Y
2
W
1
W
1
W
2
W
2
G
G
C
C
2
T
4
V
o
s
l
t
o
r
a
n
f
r
m
e
r
X
1
X
2
X
3
O
C
C
X
4
A
A
1
2
T
T
T
O
R
E
M
O
T
E
S
E
N
S
O
R
2
E
T
0
4
7
0
1
3
2
4
I
1
U
S
E
D
1
E
l
e
c
t
r
o
n
i
c
p
r
o
g
r
a
m
m
a
b
l
e
T
h
e
r
m
o
s
t
a
t
2
E
T
0
7
7
0
0
1
0
0
2
4
o
(
i
n
c
l
u
d
e
s
s
u
b
b
a
s
e
)
.
T
e
r
m
i
n
a
l
s
A
1
a
n
d
A
2
p
r
o
v
i
d
e
a
r
e
l
a
y
o
u
t
p
u
t
t
o
c
l
o
s
e
t
h
e
o
u
t
d
o
o
r
e
c
o
n
o
m
i
z
e
r
d
a
m
p
e
r
s
w
h
e
n
t
h
e
t
h
e
r
m
o
s
t
a
t
s
w
i
t
c
h
e
s
t
t
h
e
s
e
t
-
b
a
c
k
p
o
s
i
t
i
o
n
.
FIGURE 16 - ELECTRONIC THERMOSTAT FIELD WIRING
18
Unitary Products Group
035-19046-002-B-0104
T
-
S
T
A
T
W
1
W
1
W
2
W
2
Y
Y
1
2
Y
Y
1
2
G
G
O
C
C
U
N
I
T
C
O
N
T
R
O
L
C
B
O
A
R
D
R
H
R
C
X
R
S
D
C
FIGURE 17 - FIELD WIRING 24 VOLT THERMOSTAT
TERMINAL BLOCK TB1
FACTORY OR FIELD
SUPPLIED DISCONNECT
GROUND
LUG
THREE
PHASE
POWER
SUPPLY
FIGURE 18 - FIELD WIRING DISCONNECT - COOLING UNIT WITH/WITHOUT ELECTRIC HEAT
Unitary Products Group
19
035-19046-002-B-0104
CONTACTOR 1M
T1
T2
L2
T3
L3
L1
FACTORY OR FIELD
SUPPLIED DISCONNECT
GROUND
LUG
THREE
PHASE
POWER
SUPPLY
FIGURE 19 - FIELD WIRING DISCONNECT - COOLING UNIT WITH GAS HEAT
20
Unitary Products Group
035-19046-002-B-0104
TABLE 8: ELECTRICAL DATA DJ150 (12-1/2 TON) WITHOUT POWERED CONVENIENCE OUTLET
MCA
Max
Fuse*
Size
Max Fuse* Size
w/Power
Supply
Blower
Pwr
Pwr
Min. Circuit
Ampacity
(Amps)
OD Fan
Motors
w/Power
Exhaust
(Amps)
Compressors
Exh Conv
Electric Heater Actual Heater
Exhaust
Voltage
Motor FLA Motor Outlet
Model No.
KW
Amps
(Amps)
(Amps)
RLA
ea.
LRA
ea.
FLA
ea.
3
5
3
5
3
5
3
5
3
5
FLA
FLA
HP
HP
HP
HP
HP
HP
HP HP
HP
80
HP
90
None
--
13.5
18.0
25.5
40.6
--
--
61.9
61.9
76.1
67.1 67.4 72.6 80 80
67.1 67.4 73.8 80 80
82.6 83.0 89.5 80 90
2TP04521825
2TP04522425
2TP04523625
2TP04525425
None
37.5
50.0
80
90
208
230
460
20.0 146.0
1.5
1.5
0.8
0.6
10.9 16.1
5.5
0.0
90
90
70.8 102.1 108.6 109.0 115.5 110 110
112.7 154.5 161.0 161.4 167.9 175 175
110
175
80
125
175
90
--
61.9
67.8
85.8
67.1 67.4 72.6 80 80
74.3 74.6 81.1 80 80
92.3 92.7 99.2 90 100
2TP04521825
2TP04522425
2TP04523625
2TP04525425
None
18.0
24.0
34.0
54.0
--
43.3
57.7
80
90
20.0 146.0
10.9 16.1
5.5
2.2
1.8
0.0
0.0
0.0
100
125
175
35
100
150
175
40
81.8 115.9 122.4 122.7 129.2 125 125
129.9 143.5 150.0 150.4 156.9 175 175
--
27.4
33.7
42.7
57.7
71.6
21.6
26.8
34
30.2 29.6 32.4 35 35
37.2 36.4 39.9 35 40
2TP04521846
2TP04522446
2TP04523646
2TP04525446
None
18
22.6
30.1
42.7
67.8
--
40
40
8.4
6.7
73.0
60.0
5.3
4.1
8.1
6.0
24
46.2 45.5
61.2 60.5
49
64
45 50
60 70
50
50
34
70
70
54
75.1 74.3 77.8 80 90
23.5 23.4 25.3 25 30
80
90
--
30
30
2TP04521858
2TP04522458
2TP04523658
2TP04525458
18
18.1
24.1
34.1
54.2
29.2
29
31.4 30 30
30
35
575
24
36.4 36.2 38.6 35 40
48.4 48.3 50.6 50 50
59.5 59.3 61.7 70 70
40
40
34
54
46
57.1
50
70
60
70
*
Maximum HACR breaker of the same AMP size is applicable.
TABLE 9: ELECTRICAL DATA DJ150 (12-1/2 TON) WITH POWERED CONVENIENCE OUTLET
MCA
Max
Fuse*
Size
Max Fuse* Size
w/Power
Supply
Blower
Pwr
Pwr
Min. Circuit
Ampacity
(Amps)
OD Fan
Motors
w/Power
Exhaust
(Amps)
Compressors
Exh Conv
Electric Heater Actual Heater
Exhaust
Voltage
Motor FLA Motor Outlet
Model No.
KW
Amps
(Amps)
(Amps)
RLA
ea.
LRA
ea.
FLA
ea.
3
5
3
5
3
5
3
5
3
5
FLA
FLA
HP
HP
HP
HP
HP
HP
HP HP
HP
90
HP
100
100
110
150
200
100
100
125
150
175
45
None
--
13.5
18.0
25.5
40.6
--
--
71.9
73.0
88.6
77.1 77.4 82.6 90 90
79.5 79.8 86.3 90 90
95.1 95.5 102.0 90 100
2TP04521825
2TP04522425
2TP04523625
2TP04525425
None
37.5
50.0
90
208
230
460
20.0 146.0
1.5
1.5
0.8
0.6
10.9 16.1
5.5
10.0
100
125
175
90
70.8 114.6 121.1 121.5 128.0 125 125
112.7 167.0 173.5 173.9 180.4 175 175
--
71.9
80.3
77.1 77.4 82.6 90 90
86.8 87.1 93.6 90 90
2TP04521825
2TP04522425
2TP04523625
2TP04525425
None
18.0
24.0
34.0
54.0
--
43.3
57.7
90
20.0 146.0
10.9 16.1
5.5
2.2
1.8
10.0
5.0
98.3 104.8 105.2 111.7 100 110
110
150
175
40
81.8 128.4 134.9 135.2 141.7 150 150
129.9 156.0 162.5 162.9 169.4 175 175
--
32.4
39.9
49
35.2 34.6 37.4 40 40
43.4 42.7 46.2 40 45
52.5 51.7 55.2 50 60
67.5 66.7 70.2 70 70
81.3 80.6 84.1 90 90
27.5 27.4 29.3 30 30
2TP04521846
2TP04522446
2TP04523646
2TP04525446
None
18
22.6
30.1
42.7
67.8
--
45
50
8.4
6.7
73.0
60.0
5.3
4.1
8.1
6.0
24
60
60
34
64
70
80
54
77.8
25.6
31.8
39
90
90
--
30
35
2TP04521858
2TP04522458
2TP04523658
2TP04525458
18
18.1
24.1
34.1
54.2
34.2
34
36.4 35 35
35
40
575
4.0
24
41.4 41.2 43.6 40 45
53.4 53.3 55.6 60 60
64.5 64.3 66.7 70 70
45
45
34
54
51
62.1
60
70
60
70
*
Maximum HACR breaker of the same AMP size is applicable.
Unitary Products Group
21
035-19046-002-B-0104
TABLE 10: PHYSICAL DATA
Model
DJ150
Component
Blower, Centrifugal (Dia. X Wd. in.)
15 x 15
Evaporator
Blower
Motor, Standard (HP)
Motor, Optional (HP)
Rows
3
5
4
Fins per Inch
Height (in.)
15
40
Evaporator
Coil
2
13.2
Face Area (ft. each)
Propeller Dia. (in., each)
Motor (HP, each)
CFM, Nominal (each)
Rows (each)
24
1/3
3000
2
Condenser
Fan
(4 per Unit)
Condenser
Coil
(2 per unit)
Fins per Inch
20
Height (in. each)
44
2
14.5
Face Area (ft. each)
System 1 (lb./oz.)
System 2 (lb./oz.)
Quantity
11/0
11/8
2
Refrigerant
Charge
Compressors
Air Filters
Type
Scroll
25x20x2
4
Size (Wd. x Ht. x Thickness in.)
Number Per Unit
OPTIONAL ELECTRIC HEAT
TABLE 11: MINIMUM SUPPLY AIR CFM
Heater
kW
Unit Model Size, Nominal Tons
The factory-installed heaters are wired for single point power
supply. Power supply need only be brought into the single
point terminal block.
12.5
Voltage
Minimum Supply Air CFM
18
24
36
54
18
24
36
54
18
24
36
54
These CSA approved heaters are located within the central
compartment of the unit with the heater elements extending
into the supply air chamber.
208/230
3750
3750
3750
Fuses are supplied, where required, by the factory. Some kW
sizes require fuses and other do not. Refer to Table 11 for
minimum CFM limitations and to Tables 8 through 9 for elec-
trical data.
480
600
22
Unitary Products Group
035-19046-002-B-0104
OPTIONAL GAS HEAT
These gas-fired heaters have aluminized-steel or optional
stainless steel, tubular heat exchangers with spark ignition.
OPTIONAL
COIL
GUARD
SHOWN
TABLE 12: GAS HEAT APPLICATION DATA
Unit
Temp Rise
Input (MBH) Output (MBH)
(°F)
Size
150
Opt.
15
180
240
144
192
10-40
20-50
20
GAS PIPING
Proper sizing of gas piping depends on the cubic feet per
hour of gas flow required, specific gravity of the gas and the
length of run. "National Fuel Gas Code" Z223.1 (in U.S.A.) or
the current Gas Installation Codes CSA-B149.1 (in Canada)
should be followed in all cases unless superseded by local
codes or gas utility requirements. Refer to the Pipe Sizing
Table 13. The heating value of the gas may differ with locality.
The value should be checked with the local gas utility.
NOTE: There may be a local gas utility requirement specify-
ing a minimum diameter for gas piping. All units
require a one-inch pipe connection at the entrance
fitting.
FIGURE 21 - BOTTOM ENTRY GAS PIPING
TABLE 13: GAS PIPE SIZING - CAPACITY OF PIPE
Nominal Iron Pipe Size
Length of
Pipe (ft.)
3/4 in.
278
190
152
130
115
105
96
1 in.
520
350
285
245
215
195
180
170
160
150
1-1/4 in.
1050
730
10
20
30
40
50
60
70
80
90
100
590
O
C
G
S
P
T
I
O
N
N
A
L
O
I
A
L
500
U
R
W
D
440
H
O
400
370
90
350
84
320
79
305
NOTE: Maximum capacity of pipe in cubic feet of gas per
hour based upon a pressure drop of 0.3 inch W.C.
and 0.6 specific gravity gas.
FIGURE 20 - SIDE ENTRY GAS PIPING
NOTE: There may be a local gas utility requirement specify-
ing a minimum diameter for gas piping. All units
require a 3/4 inch pipe connection at the entrance
fitting. Line should not be sized smaller than the
entrance fitting size.
Unitary Products Group
23
035-19046-002-B-0104
GAS CONNECTION
The gas supply line can be routed within the space and roof
curb, exiting through the unit’s basepan. Refer to Figure 8 for
the gas piping inlet location. Typical supply piping arrange-
ments are shown in Figures 20 and 21. All pipe nipples, fit-
tings, and the gas cock are field supplied or may be
purchased in UPG accessory kit #1GP0404.
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warning exactly could
result in serious injury, death or property damage.
Never test for gas leaks with an open flame. use a
commercially available soap solution made specifi-
cally for the detection of leaks to check all connec-
tions. A fire or explosion may result causing property
damage, personal injury or loss of life.
Gas piping recommendations:
1. A drip leg and a ground joint union must be installed in
the gas piping.
2. Where required by local codes, a manual shut-off valve
must be installed outside of the unit.
3. Use wrought iron or steel pipe for all gas lines. Pipe dope
should be applied sparingly to male threads only.
The furnace and its individual shut-off valve must be
disconnected from the gas supply piping system
during any pressure testing at pressures in excess
of 1/2 PSIG.
Natural gas may contain some propane. Propane is
an excellent solvent and will quickly dissolve white
lead and most standard commercial compounds. A
special pipe dope must be used when assembling
wrought iron or steel pipe. Shellac based com-
pounds such as Gaskolac or Stalastic, and com-
pounds such as Rectorseal #5, Clydes’s or John
Crane may be used.
Pressures greater than 1/2 PSIG will cause gas
valve damage resulting in a hazardous condition. If it
is subjected to a pressure greater than 1/2 PSIG, the
gas valve must be replaced.
The furnace must be isolated from the gas supply
piping system by closing its individual manual shut-
off valve during any pressure testing of the gas sup-
ply piping system at test pressures equal to or less
than 1/2 PSIG.
4. All piping should be cleaned of dirt and scale by ham-
mering on the outside of the pipe and blowing out loose
particles. Before initial start-up, be sure that all gas lines
external to the unit have been purged of air.
LP UNITS, TANKS AND PIPING
All gas heat units are shipped from the factory equipped for
natural gas use only. The unit may be converted in the field
for use with LP gas with accessory kit model number
1NP0441.
5. The gas supply should be a separate line and installed in
accordance with all safety codes as prescribed under
“Limitations”.
All LP gas equipment must conform to the safety standards of
the National Fire Protection Association.
6. A 1/8-inch NPT plugged tapping, accessible for test gage
connection, must be installed immediately upstream of
the gas supply connection to the unit.
For satisfactory operation, LP gas pressure must be 10.5
inch W.C. at the unit under full load. Maintaining proper gas
pressure depends on three main factors:
7. After the gas connections have been completed, open
the main shut-off valve admitting normal gas pressure to
the mains. Check all joints for leaks with soap solution or
other material suitable for the purpose. NEVER USE A
FLAME.
1. The vaporization rate which depends on the temperature
of the liquid and the “wetted surface” area of the con-
tainer(s).
24
Unitary Products Group
035-19046-002-B-0104
2. The proper pressure regulation. (Two-stage regulation is
recommended).
MOTORIZED OUTDOOR DAMPER
The Motorized Outdoor Damper can be a factory installed
option or a field installed accessory. If factory installed, refer
to the instructions included with the outdoor air hood to com-
plete the assembly. Field installed Motorized Outdoor Damp-
ers accessories include complete instructions for installation.
3. The pressure drop in the lines between regulators and
between the second stage regulator and the appliance.
Pipe size required will depend on the length of the pipe
run and the total load of all appliances.
Complete information regarding tank sizing for vaporization,
recommended regulator settings, and pipe sizing is available
from most regulator manufacturers and LP gas suppliers.
ECONOMIZER
The Economizer can be a factory installed option or a field
installed accessory. If factory installed, refer to the instruc-
tions included with the outdoor air hood to complete the
assembly. Field installed Economizer accessories include
complete instructions for installation.
LP gas is an excellent solvent and will quickly dissolve white
lead and most standard commercial compounds. A special
pipe dope must be used when assembling wrought iron or
steel pipe for LP. Shellac base compounds such as Gaskolac
or Stalastic, and compounds such as Rectorseal #5, Clyde’s,
or John Crane may be used.
There are two Economizer options:
1. Down Flow application with barometric relief hood stan-
dard.
Check all connections for leaks when piping is completed
using a soap solution. NEVER USE A FLAME.
2. Horizontal Flow application that requires the purchase of
a barometric relief hood.
POWER EXHAUST
The Power Exhaust can be a factory installed option or a field
installed accessory. If factory installed, refer to the instruc-
tions included with the outdoor air hood to complete the
assembly. Field installed Power Exhaust accessories include
complete instructions for installation.
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warning exactly could
result in serious injury, death or property damage.
Never test for gas leaks with an open flame. use a
commercially available soap solution made specifi-
cally for the detection of leaks to check all connec-
tions. A fire or explosion may result causing property
damage, personal injury or loss of life.
The Power Exhaust factory installed option is for Down Flow
application only.
There are two field installed Power Exhaust accessories:
1. Down Flow application.
VENT AND COMBUSTION AIR
2. Horizontal Flow application that requires the purchase of
a barometric relief hood.
Venting slots in the heating compartment access panel
remove the need for a combustion air hood. The gas heat
flue exhaust is routed through factory installed exhaust piping
with screen. If necessary, a flue exhaust extension may be
installed at the point of installation.
RAIN HOOD
The following procedure should be used when assembling a
rain hood onto a unit.
FACTORY INSTALLED OPTIONS/
FIELD INSTALLED ACCESSORIES
All of the hood components, including the filters, the gasket-
ing and the hardware for assembling, are packaged and
located between the condenser coil section and the main unit
cabinet, if the unit has factory installed options. If field
installed accessories are being installed all parts necessary
for the installation comes in the accessory.
ELECTRIC HEAT
Electric heaters are available as field installed accessories.
Refer to electric heat instructions for installation. These heat-
ers mount in the heat compartment with the heating elements
extending into the supply air chamber. All electric heaters are
fused and intended for use with single point power supply.
1. Remove the hood components, filters, gasketing and the
hardware from the box.
2. Follow the instructions included with the hood to com-
plete the installation.
Unitary Products Group
25
035-19046-002-B-0104
•
For a dual enthalpy operation, carefully turn the set point
adjusting screw fully clockwise past the "D" setting.
ECONOMIZER AND POWER EXHAUST SET POINT
ADJUSTMENTS AND INFORMATION
POWER EXHAUST DAMPER SET POINT (WITH OR WITH-
OUT POWER EXHAUST)
Remove the top rear access panel from the unit. Locate the
economizer control module, where the following adjustments
will be made.
•
With no power exhaust option, adjust the Exhaust Air
Adjustment Screw fully clockwise. This will allow 2nd
stage cooling to operate.
•
With power exhaust option, each building pressurization
requirement will be different. The point at which the
power exhaust comes on is determined by the econo-
mizer damper position (Percent Open). The Exhaust Air
Adjustment Screw should be set at the Percent Open of
the economizer damper at which the power exhaust is
needed. It can be set from 0 to 100% damper open.
Extreme care must be exercised in turning all set
point, maximum and minimum damper positioning
adjustment screws to prevent twisting them off.
MINIMUM POSITION ADJUSTMENT
•
Check that the damper blades move smoothly with bind-
ing; carefully turn the Minimum Position Adjust screw
(found on the damper control module) fully clockwise
and then set the thermostat indoor fan switch to the ON
position and then OFF or energize and de-energize ter-
minals “R” to “G”.
INDOOR AIR QUALITY AQ
Indoor Air Quality (indoor sensor input): Terminal AQ accepts
a +2 to +10 Vdc signal with respect to the (AQ1) terminal.
When the signal is below it's set point, the actuator is allowed
to modulate normally in accordance with the enthalpy and
mixed air sensor inputs. When the AQ signal exceeds it's set
point setting and there is no call for free cooling, the actuator
is proportionately modulated from the 2 to 10 Vdc signal, with
2 Vdc corresponding to full closed and 10 Vdc corresponding
to full open. When there is no call for free cooling, the damper
position is limited by the IAQ Max damper position setting.
When the signal exceeds it's set point (Demand Control Ven-
tilation Set Point) setting and there is a call for free cooling,
the actuator modulates from the minimum position to the full
open position based on the highest call from either the mixed
air sensor input or the AQ voltage input.
•
With the thermostat set to the indoor fan ON position or
terminals “R” to “G” energized, turn the Minimum Posi-
tion Adjusting screw (located on the damper control
module) counterclockwise until the desired minimum
damper position has been attained.
ENTHALPY SET POINT ADJUSTMENT
The enthalpy set point may now be set by selecting the
desired set point shown in the Enthalpy Set Point Adjustment
Figure 22. Adjust as follows:
•
For a single enthalpy operation carefully turn the set
point adjusting screw (found on the damper control mod-
ule) to the "A", "B", "C" or "D" setting corresponding to
the lettered curve of the Enthalpy Set Point Adjustment
Figure 22.
•
•
Optional CO Space Sensor Kit Part # 2AQ04700324
2
Optional CO Sensor Kit Part # 2AQ04700424
2
Replace the top rear access panel on the unit.
26
Unitary Products Group
035-19046-002-B-0104
CONTROL POINT
APPROX. 0F (0C)
AT 50% RH
CONTROL
CURVE
85 90 95 100 105 110
(29) (32) (35) (38) (41) (43)
A
B
C
D
73 (23)
70 (21)
67 (19)
63 (17)
80
(27)
75
(24)
70
(21)
65
(18)
0
(16)
55
(13)
A
B
50
(10)
C
45
(7)
D
40
(4)
35
(2)
A
B
C
D
40 45
(4) (7)
65 70 75 80
(24) (27)
95
105 110
(41) (43)
35
(2)
50 55 60
(10) (13) (16)
85 90
(29) (32)
100
(38)
(21)
(35)
(18)
APPROXIMATE DRY BULB TEMPERATURE - 0F (0C)
FIGURE 22 - ENTHALPY SET POINT CHART
Exhaust Air
Adjustment
Screw
EXH
Set
N
P
T
N1
TR
TR1
Exhaust Air LED
Damper Min.
Position
Screw
24
Vac
HOT
24
Vac
COM
EXH
P1
T1
Min
Pos
Indoor Air Quality
Max. Adjustment
Screw
+
IAQ
Max
1
2
Indoor Air Quality
LED
IAQ
AQ1
SO+
AQ
SO
5
4
Indoor Air Quality
Min. Adjustment
Screw
IAQ
Min
3
Free
Cool
Free Cooling LED
SR
B
SR+
EF
EF1
C
D
A
Economizer Enthalpy
Set Point Adjustment
Screw
FIGURE 23 - HONEYWELL ECONOMIZER CONTROL W7212
Unitary Products Group
27
035-19046-002-B-0104
PHASING
A
Predator Magnum DJ units are properly phased and pro-
tected by a Phase Monitor from the factory. If the unit does
not start up, the electrical connection to the unit may be mis-
phased. Check the Phase Monitor for a Red LED, indicating a
misphase. Change the phasing of the Field line connection
at the Factory or Field Supplied Disconnect to obtain a
Green LED on the Phase Monitor. (Scroll compressors oper-
ate in only one direction. If the scroll is drawing low amper-
age, has similar suction and discharge pressures, or
producing a high noise level, the scroll is misphased.)
A
C*
* NEVER LOOSEN
A
B
Scroll compressors require proper rotation to oper-
ate correctly. Units are properly phased at the fac-
tory. Do not change the internal wiring to make the
blower condenser fans, or compressor rotate cor-
rectly.
SPAN LENGTH
DEFL. FORCE
BLOWER ROTATION
Check for proper supply air blower rotation. If the blower is
rotating backwards, the line voltage at the unit point of power
connection is misphased (See ‘PHASING’).
TABLE 14: SUPPLY AIR LIMITATIONS
FIGURE 24 - BELT ADJUSTMENT
Unit
Minimum
Maximum
DJ150
3750
6250
BELT TENSION
Procedure for adjusting belt tension:
The tension on the belt should be adjusted as shown in Fig-
ure 24.
1. Loosen six nuts (top and bottom) A.
2. Adjust by turning (B).
3. Never loosen nuts (C).
4. Use belt tension checker to apply a perpendicular
force to one belt at the midpoint of the span as
shown. Deflection distance of 4mm (5/32”) is
obtained.
To determine the deflection distance from normal
position, use a straight edge from sheave to sheave
as reference line. The recommended deflection
force is as follows:
Tension new belts at the max. deflection force rec-
ommended for the belt section. Check the belt ten-
sion at least two times during the first 24 hours of
operation. Any retensioning should fall between the
min. and max. deflection force values.
5. After adjusting retighten nuts (A).
28
Unitary Products Group
035-19046-002-B-0104
* †
TABLE 15: DJ150, 12-1/2 TON STANDARD MOTOR DOWN SHOT BLOWER PERFORMANCE
TURNS OPEN**
ESP‡
0
1
2
3
4
5
W††
W††
W††
W††
W††
W††
CFM
BHP CFM
BHP CFM
BHP CFM
BHP CFM
BHP CFM
BHP
0.4
0.6
0.8
1.0
1.2
1.4
5078 3630 3.89 4809 3103 3.33 4594 3053 3.27 4360 2478 2.66 4090 2093 2.24 3812 1798 1.93
4865 3456 3.71 4584 2961 3.17 4349 2912 3.12 4106 2318 2.49 3814 1964 2.11
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4642 3284 3.52 4356 2828 3.03 4089 2776 2.98 3840 2137 2.29
-
-
-
-
-
-
-
-
-
-
-
-
4408 3114 3.34 4124 2705 2.90 3815 2647 2.84
-
-
-
-
-
-
-
-
-
4164 2947 3.16 3889 2592 2.78
3910 2787 2.99
-
-
-
-
-
-
-
-
-
*.
Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.
Blower performance includes two-inch throwaway filters.
†.
‡.
ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been
deducted from the total static pressure of the blower.
**.
“Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.
W = Watts
††.
* †
TABLE 16: DJ150, 12-1/2 TON OPTIONAL MOTOR DOWN SHOT BLOWER PERFORMANCE
TURNS OPEN**
ESP‡
0
1
2
3
4
5
W††
W††
W††
W††
W††
W††
CFM
BHP CFM
BHP CFM
BHP CFM
BHP CFM
BHP CFM
BHP
5994 5400 5.79 5565 4369 4.69 5488 4169 4.47 5264 3599 3.86 4990 3085 3.31 4738 2812 3.02
5824 5216 5.59 5368 4186 4.49 5289 3991 4.28 5049 3437 3.69 4763 2937 3.15 4491 2655 2.85
5641 5022 5.39 5170 4012 4.30 5076 3807 4.08 4822 3272 3.51 4528 2790 2.99 4235 2497 2.68
5444 4819 5.17 4971 3846 4.12 4847 3618 3.88 4584 3103 3.33 4286 2644 2.83 3969 2340 2.51
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
5233 4609 4.94 4771 3687 3.95 4604 3426 3.67 4335 2933 3.15 4035 2499 2.68
5009 4394 4.71 4571 3537 3.79 4346 3233 3.47 4074 2762 2.96 3777 2356 2.53
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4771 4174 4.48 4370 3395 3.64 4074 3040 3.26 3802 2590 2.78
-
-
-
-
-
-
-
-
-
-
-
-
4520 3951 4.24 4169 3262 3.50 3786 2850 3.06
-
-
-
-
-
-
-
-
-
4255 3728 4.00 3966 3137 3.36
3976 3505 3.76 3763 3020 3.24
-
-
-
-
-
-
*.
Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.
Blower performance includes two-inch throwaway filters.
†.
‡.
ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been
deducted from the total static pressure of the blower.
**.
“Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.
W = Watts
††.
Unitary Products Group
29
035-19046-002-B-0104
* †
TABLE 17: DJ150, 12-1/2 TON STANDARD MOTOR SIDE SHOT BLOWER PERFORMANCE
TURNS OPEN**
ESP‡
0
1
2
3
4
5
W††
W††
W††
W††
W††
W††
CFM
BHP CFM
BHP CFM
BHP CFM
BHP CFM
BHP CFM
BHP
5201 3162 3.39 4966 2796 3.00 4681 2405 2.58 4355 2054 2.20
0.4
0.6
0.8
1.0
1.2
1.4
-
-
-
-
-
-
-
-
-
-
-
-
5220 3395 3.64 4942 2980 3.20 4657 2608 2.80 4358 2230 2.39 4007 1890 2.03
4944 3194 3.43 4661 2806 3.01 4378 2572 2.76 4016 2057 2.21
-
-
-
-
-
-
-
-
-
-
-
-
5003 3490 3.74 4647 2988 3.20 4380 2636 2.83 4030 2257 2.42
-
-
-
-
-
-
-
-
-
4724 3290 3.53 4363 2875 3.08 4012 2505 2.69
4428 3040 3.26
-
-
-
-
-
-
-
-
-
-
-
-
*.
Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.
Blower performance includes two-inch throwaway filters.
†.
‡.
ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been
deducted from the total static pressure of the blower.
**.
“Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.
W = Watts
††.
* †
TABLE 18: DJ150, 12-1/2 TON OPTIONAL MOTOR SIDE SHOT BLOWER PERFORMANCE
TURNS OPEN**
ESP‡
0
1
2
3
4
5
W††
W††
W††
W††
W††
W††
CFM
BHP CFM
BHP CFM
BHP
CFM
BHP CFM
BHP CFM
BHP
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
2.6
-
-
-
-
-
-
-
-
-
6447 5315 5.70 6207 4760 5.1046 5966 4205 4.51 5717 3716 3.98 5470 3307 3.55
6110 4917 5.27 5965 4464
5772 4519 4.85 5741 4274
4.79
4.58
4.34
4.13
3.94
3.71
3.47
3.07
-
5740 4023 4.31 5430 3501 3.75 5126 3054 3.28
5503 3821 4.10 5162 3294 3.53 4849 2870 3.08
5244 3611 3.87 4882 3101 3.33 4530 2667 2.86
4941 3387 3.63 4589 2906 3.12 4225 2502 2.68
4651 3178 3.41 4284 2716 2.91 3858 2280 2.45
4365 2983 3.20 3951 2516 2.70 3491 2058 2.21
6235 5521 5.92 5628 4407 4.73 5474 4048
5881 5137 5.51 5384 4205 4.51 5248 3854
5695 4950 5.31 5123 3996 4.29 5014 3670
5471 4728 5.07 4919 3828 4.11 4732 3460
5242 4514 4.84 4656 3611 3.87 4438 3240
4954 4231 4.54 4339 3380 3.62 3905 2861
3998 2740 2.94 3618 2316 2.48
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3631 2497 2.68
-
-
-
-
-
-
-
-
-
-
-
-
4585 3934 4.22 4022 3149 3.38
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4217 3637 3.90
3848 3340 3.58
-
-
-
-
-
-
-
-
*.
Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.
Blower performance includes two-inch throwaway filters.
†.
‡.
ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been
deducted from the total static pressure of the blower.
**.
“Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.
W = Watts
††.
NOTES FOR TABLE 15 THROUGH TABLE 18:
•
•
Blower performance includes dry coil and two-inch
filters.
Blower performance for gas heat includes the maximum
number of heat tubes available for each tonnage.
•
ESP (External Static Pressure) given is that available for
the supply and return air duct system. All internal resis-
tances have been deducted from the total static pressure
of the blower.
30
Unitary Products Group
035-19046-002-B-0104
TABLE 19: INDOOR BLOWER SPECIFICATIONS
MOTOR
MOTOR SHEAVE
BLOWER SHEAVE
MODEL
BELT
HP
3
RPM Eff.
SF Frame Datum Dia. (in.) Bore (in.) Model Datum Dia. (in.) Bore (in.) Model
1725 80% 1.15
1725 87% 1.15
56
3.4 - 4.4
4.3 - 5.3
7/8
1VM50
1VP56
7.0
6.7
1
1
AK74
BK77
A54
DJ150
5
184T
1 1/8
BX55
AIR BALANCE
Start the supply air blower motor. Adjust the resistances in both the supply and the return air duct systems to balance the air
distribution throughout the conditioned space. The job specifications may require that this balancing be done by someone other
than the equipment installer.
CHECKING AIR QUANTITY
METHOD ONE
METHOD TWO
1. Remove the dot plugs from the duct panel (for location of
the dot plugs see Figure 9).
1. Drill two 5/16 inch holes, one in the return air duct as
close to the inlet of the unit as possible, and another in
the supply air duct as close to the outlet of the unit as
possible.
2. Insert eight-inches of 1/4 inch metal tubing into the air-
flow on both sides of the indoor coil.
2. Insert eight inches of 1/4 inch metal tubing into the air-
flow of both return and supply air ducts of the unit.
NOTE: The tubes must be inserted and held in a position
perpendicular to the air flow so that velocity pres-
sure will not affect the static pressure readings.
NOTE: The tubes must be inserted and held in position per-
pendicular to the airflow so that velocity pressure
will not affect the static pressure readings.
3. Use an Inclined Manometer or Magnehelic to determine
the pressure drop across a dry evaporator coil. Since the
moisture on an evaporator coil can vary greatly, measur-
ing the pressure drop across a wet coil under field condi-
tions could be inaccurate. To assure a dry coil, the
compressors should be de-activated while the test is
being run.
3. Use an Inclined Manometer or Magnehelic to determine
the pressure drop across the unit. This is the External
Static Pressure (ESP).
4. Select the indoor blower specifications for the unit from
Table 19, 3 or 5 H.P. Motor.
5. Determine the number of turns the variable pitch motor
sheave is open.
NOTE: De-energize the compressors before taking any test
measurements to assure a dry evaporator coil.
6. Select the correct blower performance table for the unit
from Tables 15 - 18.
4. The CFM through the unit with clean 2 inch filters can be
determined from the pressure drop indicated by the
manometer by referring to Figure 25.
7. Determine the unit Measured CFM from the Blower Per-
formance Table, External Static Pressure and number of
turns the variable pitch motor sheave is open.
5. To adjust Measured CFM to Required CFM, see ’SUP-
PLY AIR DRIVE ADJUSTMENT’.
8. To adjust Measured CFM to Required CFM, see ’SUP-
PLY AIR DRIVE ADJUSTMENT’.
6. After adjustments have been completed, remove the
tubes and replace the dot plugs.
9. After adjustments have been completed, remove the
tubes and seal holes.
NOTE: With the addition of field installed accessories
repeat this procedure.
Failure to properly adjust the total system air quan-
tity can result in extensive blower damage.
Failure to properly adjust the total system air quan-
tity can result in extensive blower damage.
Unitary Products Group
31
035-19046-002-B-0104
Predator DJ 150 Units
Indoor Coil Pressure Drop vs. Airflow
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
3500
4000
4500
5000
5500
6000
6500
Airflow (CFM)
FIGURE 25 - DRY COIL DELTA P
SUPPLY AIR DRIVE ADJUSTMENT
EXAMPLE
A 12.5 ton unit was selected to deliver 4,000 CFM with a 3
HP motor, but the unit is delivering 3,800 CFM. The variable
pitch motor sheave is set at 2 turns open.
Use the equation to determine the required DD for the new
motor sheave,
Before making any blower speed changes review
the installation for any installation errors, leaks or
undesirable systems effects that can result in loss of
airflow.
4,000 CFM
• 4.0 in. = 4.21 in.
)
(
3,800 CFM
Even small changes in blower speed can result in
substantial changes in static pressure and BHP.
BHP and AMP draw of the blower motor will
increase by the cube of the blower speed. Static
pressure will increase by the square of the blower
speed. Only qualified personnel should make blower
speed changes, strictly adhering to the fan laws.
Use Table 21 to locate the DD nearest to 4.21 in. Close the
sheave to 1 turn open.
New BHP
= (Speed increase)3• BHP at 3,800 CFM
At unit start-up, the measured CFM may be higher or lower
than the required CFM. To achieve the required CFM, the
speed of the drive may have adjusted by changing the datum
diameter (DD) of the variable pitch motor sheave as
described below:
= (Speed increase)3 • Original BHP
= New BHP
Required CFM
Measured CFM
• Existing DD = New DD
)
(
New motor Amps
= (Speed increase)3• Amps at 3,800 CFM
Use the following tables and the DD calculated per the above
equation to adjust the motor variable pitch sheave.
= (Speed increase)3 • Original Amps
= New Amps
32
Unitary Products Group
035-19046-002-B-0104
TABLE 20: ADDITIONAL STATIC RESISTANCE
Electric Heat KW†
*
† ‡
CFM
Cooling Only
Economizer
18
24
36
54
3700
3900
4100
4300
4500
4700
4900
5100
5300
5500
5700
5900
6100
6300
0.20
0.23
0.25
0.28
0.30
0.33
0.36
0.39
0.42
0.45
0.48
0.52
0.56
0.60
0.04
0.04
0.04
0.05
0.05
0.05
0.05
0.06
0.06
0.06
0.06
0.07
0.07
0.07
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.21
0.23
0.25
0.28
0.30
0.33
0.35
0.38
0.41
0.44
0.47
0.50
0.53
0.56
0.22
0.24
0.26
0.29
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.56
0.59
0.26
0.28
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.56
0.59
0.62
0.65
*.
Add these resistance values to the available static resistance in the respective Blower Performance Tables.
†.
‡.
Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
For gas heating, the UCB monitors the "W1" call but does not
TABLE 21: MOTOR SHEAVE DATUM DIAMETERS
handle the operation of the gas furnace. An ignition control
board controls the gas heater operation. For electric heat
units, the UCB passes the call to the electric heater. In both
cases, when the "W1" call is sensed, the indoor air blower is
energized following a specified heating delay.
1VM50x7/8
(3 HP Motor)
1VP56x1-1/8
(5 HP Motor)
Datum
Diameter
Datum
Diameter
Turns Open
Turns Open
0
1/2
1
4.4
1
1-1/2
2
5.3
If at any time a call for both heating and cooling are present,
the heating operation will be performed. If operating, the cool-
ing system is halted as with a completion of a call for cooling.
Heating always takes priority.
4.3
5.2
4.2
5.1
1-1/2
2
4.1
2-1/2
3
5.0
4.0
4.9
COOLING SEQUENCE OF OPERATION
CONTINUOUS BLOWER
2-1/2
3
3.9
3-1/2
4
4.8
3.8
4.7
3-1/2
4
3.7
4-1/2
5
4.6
By setting the room thermostat fan switch to "ON," the supply
air blower will operate continuously.
3.6
4.5
4-1/2
5
3.5
5-1/2
6
4.4
INTERMITTENT BLOWER
3.4
4.3
With the room thermostat fan switch set to "AUTO" and the
system switch set to either the "AUTO" or "HEAT" settings,
the blower is energized whenever a cooling or heating opera-
tion is requested. The blower is energized after any specified
delay associated with the operation.
OPERATION
SEQUENCE OF OPERATIONS OVERVIEW
For the Predator Magnum series of units, the thermostat
makes a circuit between "R" and "Y1" for the first stage of
cooling.
When energized, the indoor blower has a minimum run time
of 30 seconds. Additionally, the indoor blower has a delay of
10 seconds between operations.
The call is passed to the unit control board (UCB), which then
determines whether the requested operation is available and,
if so, which components to energize.
Unitary Products Group
33
035-19046-002-B-0104
NO OUTDOOR AIR OPTIONS
gize compressor #1. If the outdoor air is above the set point,
"Y2" will energize compressor #2.
When the thermostat calls for the first stage of cooling, the
low-voltage control circuit from “R” to “Y1” and “G” is com-
pleted. The UCB energizes the economizer (if installed and
free cooling is available) or the first available compressor*
and the condenser fans. For first stage cooling, compressor
#1 is energized. If compressor #1 is unavailable, compressor
#2 is energized. After completing the specified fan on delay
for cooling, the UCB will energize the blower motor.
Once the thermostat has been satisfied, it will de-energize Y1
and Y2. If the compressors have satisfied their minimum run
times, the compressors and condenser fans are de-ener-
gized. Otherwise, the unit operates each cooling system until
the minimum run times for the compressors have been com-
pleted. Upon the final compressor de-energizing, the blower
is stopped following the elapse of the fan off delay for cooling,
and the economizer damper goes to the closed position. If
the unit is in continues fan operation the economizer damper
goes to the min. position.
When the thermostat calls for the second stage of cooling,
the low-voltage control circuit from “R” to “Y2” is completed.
The control board energizes the first available compressor. If
free cooling is being used for the first stage of cooling, com-
pressor #1 is energized. If compressor #1 is active for first
stage cooling or the first compressor is locked-out, compres-
sor #2 is energized. In free-cooling mode, if the call for the
second stage of cooling continues for 20 minutes, compres-
sor #2 is energized, provided it has not been locked-out.
ECONOMIZER WITH DUAL ENTHALPY SENSORS -
The operation with the dual enthalpy sensors is identical to
the single sensor except that a second enthalpy sensor is
mounted in the return air. This return air sensor allows the
economizer to choose between outdoor air and return air,
whichever has the lowest enthalpy value, to provide maxi-
mum operating efficiency.
If there is an initial call for both stages of cooling, the UCB will
delay energizing compressor #2 by 30 seconds in order to
avoid a power rush.
ECONOMIZER (SINGLE OR DUAL) WITH POWER
EXHAUST -
Once the thermostat has been satisfied, the it will de-ener-
gize Y1 and Y2. If the compressors have satisfied their mini-
mum run times, the compressors and condenser fans are de-
energized. Otherwise, the unit operates each cooling system
until the minimum run times for the compressors have been
completed. Upon the final compressor de-energizing, the
blower is stopped following the elapse of the fan off delay for
cooling.
This system operates as specified above with one addition.
The power exhaust motor is energized 45 seconds after the
actuator position exceeds the exhaust fan set point on the
economizer control. When the power exhaust is operating,
the second stage of mechanical cooling will not operate. As
always, the "R" to "G" connection provides minimum position
but does not provide power exhaust operation.
MOTORIZED OUTDOOR AIR DAMPERS -
* To be available, a compressor must not be locked-out due
to a high or low-pressure switch or freezestat trip and the
anti-short cycle delay (ASCD) must have elapsed.
This system operation is the same as the units with no out-
door air options with one exception. When the "R" to "G" cir-
cuit is complete, the motorized damper drives open to a
position set by the thumbwheel on the damper motor. When
the "R" to "G" circuit is opened, the damper spring returns
fully closed.
ECONOMIZER WITH SINGLE ENTHALPY SENSOR -
When the room thermostat calls for "first-stage" cooling, the
low voltage control circuit from "R" to "G" and "Y1" is com-
pleted. The UCB energizes the blower motor (if the fan switch
on the room thermostat is set in the "AUTO" position) and
drives the economizer dampers from fully closed to their min-
imum position. If the enthalpy of the outdoor air is below the
set point of the enthalpy controller (previously determined),
"Y1" energizes the economizer. The dampers will modulate to
maintain a constant supply air temperature as monitored by
the discharge air sensor. If the outdoor air enthalpy is above
the set point, "Y1" energizes compressor #1, condenser fan
motor #1, and condenser fan motor #2 (if the ambient tem-
perature is above 60°F).
COOLING OPERATION ERRORS
Each cooling system is monitored for operation outside of the
intended parameters. Errors are handled as described below.
All system errors override minimum run times for compres-
sors.
HIGH-PRESSURE LIMIT SWITCH
During cooling operation, if a high-pressure limit switch
opens, the UCB will de-energize the associated compressor,
initiate the ASCD (Anti-short cycle delay), and, if the other
compressor is idle, stop the condenser fans. If the call for
cooling is still present at the conclusion of the ASCD, the
UCB will re-energize the halted compressor.
When the thermostat calls for "second-stage" cooling, the low
voltage control circuit from "R" to "Y2" is completed. The UCB
energizes the first available compressor If the enthalpy of the
outdoor air is below the set point of the enthalpy controller
(i.e. first stage has energized the economizer), "Y2" will ener-
34
Unitary Products Group
035-19046-002-B-0104
Should a high-pressure switch open three times within two
hours of operation, the UCB will lock-out the associated com-
pressor and flash a code (see Table 28). If the other com-
pressor is inactive, the condenser fans will be de-energized.
of compressor operation. The defrost cycle will begin immedi-
ately following the elapse of the minimum run time.
When operating in low ambient mode, the UCB will not lock-
out the compressors due to a freezestat trip. However, a
freezestat trip will de-energize the associated compressor. If
the call for cooling is still present at the end of the ASCD and
the freezestat has closed, the unit will resume operation.
LOW-PRESSURE LIMIT SWITCH
The low-pressure limit switch is not monitored during the ini-
tial 30 seconds of a cooling system's operation. For the fol-
lowing 30 seconds, the UCB will monitor the low-pressure
switch to ensure it closes. If the low-pressure switch fails to
close after the 30-second monitoring phase, the UCB will de-
energize the associated compressor, initiate the ASCD, and,
if the other compressor is idle, stop the condenser fans.
SAFETY CONTROLS
The unit control board monitors the following inputs for each
cooling system:
1. A suction line freezestat to protect against low evapora-
tor temperatures due to a low airflow or a low return air
temperature, (opens at 26 ± 5 °F and resets at 38 ± 5°F).
Once the low-pressure switch has been proven (closed dur-
ing the 30-second monitor period described above), the UCB
will monitor the low-pressure limit switch for any openings. If
the low-pressure switch opens for greater than 5 seconds,
the UCB will de-energize the associated compressor, initiate
the ASCD, and, if the other compressor is idle, stop the con-
denser fans.
2. A high-pressure switch to protect against excessive dis-
charge pressures due to a blocked condenser coil or a
condenser motor failure, (opens at 380 ± 10 psig and
resets at 300 ± 10 psig).
3. A low-pressure switch to protect against loss of refriger-
ant charge, (opens at 7 ± 3 psig and resets at 22 ± 5
psig).
If the call for cooling is still present at the conclusion of the
ASCD, the UCB will re-energize the halted compressor.
Should a low-pressure switch open three times within one
hour of operation, the UCB will lock-out the associated com-
pressor and flash a code (Table 28). If the other compressor
is inactive, the condenser fans will be de-energized.
The above pressure switches are hard-soldered to the unit.
The refrigeration systems are independently monitored and
controlled. On any fault, only the associated system will be
affected by any safety/preventive action. The other refrigerant
system will continue in operation unless it is affected by the
fault as well.
FREEZESTAT
During cooling operation, if a freezestat opens, the UCB will
de-energize the associated compressor, initiate the ASCD,
and, if the other compressor is idle, stop the condenser fans.
If the call for cooling is still present at the conclusion of the
ASCD, the UCB will re-energize the halted compressor.
The unit control board monitors the temperature limit switch
of electric heat units and the temperature limit switch and the
gas valve of gas furnace units.
COMPRESSOR PROTECTION
Should a freezestat open three times within two hours of
operation, the UCB will lock-out the associated compressor
and flash a code (Table 28). If the other compressor is inac-
tive, the condenser fans will be de-energized.
The compressors also have inherent (internal) protection. If
there is an abnormal temperature rise in a compressor, the
protector will open to shut down the compressor. The UCB
incorporates features to minimize compressor wear and dam-
age. An anti-short cycle delay (ASCD) is utilized to prevent
operation of a compressor too soon after its previous run.
Additionally, a minimum run time is imposed any time a com-
pressor is energized.
LOW AMBIENT COOLING
To determine when to operate in low ambient mode, the UCB
has a pair of terminals connected to a temperature-activated
switch set at 45ºF. When the low ambient switch is closed
and the thermostat is calling for cooling, the UCB will operate
in the low ambient mode.
The ASCD is initiated on unit start-up and on any compressor
reset or lock-out.
FLASH CODES
Low ambient mode operates the compressors in this manner:
10 minutes on, 5 minutes off. The indoor blower is operated
throughout the cycle. The 5-minute off period is necessary to
defrost the indoor coil.
The UCB will initiate a flash code associated with errors
within the system. Refer to UNIT CONTROL BOARD FLASH
CODES Table 28.
Low ambient mode always begins with compressor opera-
tion. Compressor minimum run time may extend the minutes
Unitary Products Group
35
035-19046-002-B-0104
RESET
TABLE 22: ELECTRIC HEAT LIMIT SETTING
Remove the call for cooling, by raising thermostat setting
higher than the conditioned space temperature. This resets
any pressure or freezestat flash codes.
LIMIT
SWITCH
OPENS °F
HEATER
kW
UNIT (TONS)
VOLTAGE
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
18
24
34
54
18
24
34
54
18
24
34
54
150
150
150
150
150
150
150
150
150
150
150
150
ELECTRIC HEATING SEQUENCE OF OPERATIONS
208/230
The following sequence describes the operation of the elec-
tric heat section.
Two-stage heating:
480
600
a. Upon a call for first stage heat by the thermostat, the
heater relay (RA) will be energized. After completing
the specified fan on delay for heating, the UCB will
energize the blower motor. If the second stage of
heat is required, heater relay (RB) will be energized.
After completing the specified fan on delay for heat-
ing, the UCB will energize the blower motor.
b. The thermostat will cycle the electric heat to satisfy
the heating requirements of the conditioned space.
FLASH CODES
The UCB will initiate a flash code associated with errors
within the system. Refer to UNIT CONTROL BOARD FLASH
CODES Table 28.
ELECTRIC HEATING OPERATION ERRORS
TEMPERATURE LIMIT
RESET
If the UCB senses zero volts from the high temperature limit,
the indoor blower motor is immediately energized.
Remove the call for heating by lowering the thermostat set-
ting lower than the conditioned space temperature.This
resets any flash codes.
This limit is monitored regardless of unit operation status, i.e.
the limit is monitored at all times.
ELECTRIC HEAT ANTICIPATOR SETPOINTS
If the temperature limit opens three times within one hour, it
will lock-on the indoor blower motor and a flash code is initi-
ated (See Table 28).
It is important that the anticipator setpoint be correct. Too
high of a setting will result in longer heat cycles and a greater
temperature swing in the conditioned space. Reducing the
value below the correct setpoint will give shorter “ON” cycles
and may result in the lowering of the temperature within the
conditioned space. Refer to Table 23 for the required electric
heat anticipator setting.
SAFETY CONTROLS
The UCB monitors the temperature limit switch of electric
heat units.
The control circuit includes the following safety controls:
TABLE 23: ELECTRIC HEAT ANTICIPATOR
SETPOINTS
LIMIT SWITCH (LS)
This control is located inside the heater compartment and is
set to open at the temperature indicated in the Electric Heat
Limit Setting Table 22. It resets automatically. The limit switch
operates when a high temperature condition, caused by inad-
equate supply air flow occurs, thus shutting down the heater
and energizing the blower.
SETTING, AMPS
W1
W2
0.13
0.1
36
Unitary Products Group
035-19046-002-B-0104
If the unit fails after three ignition attempts, the furnace is
locked-out for one hour. The furnace is monitored during this
one-hour period for unsafe conditions.
GAS HEATING SEQUENCE OF OPERATIONS
When the thermostat calls for the first stage of heating, the
low-voltage control circuit from “R” to “W1” is completed. A
call for heat passes through the UCB to the ignition control
board (ICB). The UCB monitors the “W1” call and acts upon
any call for heat by monitoring the gas valve (GV). Once volt-
age has been sensed at the GV, the UCB will initiate the fan
on delay for heating, energizing the indoor blower the speci-
fied delay has elapsed.
RECYCLE OPERATION
When a flame is lost after the flame stabilization period, a
recycle operation occurs. If the unit fails after five recycle
attempts, the furnace is locked-out for one hour.
GAS HEATING OPERATION ERRORS
LOCK-OUT
When the thermostat has been satisfied, heating calls are
ceased. The GV is immediately closed. The blower is de-
energized after the fan off delay for heating has elapsed. The
draft motor performs a 30-second post purge.
A one-hour lockout occurs following three retries or five recy-
cles. During the one-hour lockout, flame detection, limit con-
ditions, and main valves are tested. Any improper results will
cause the appropriate action to occur. Recycling the low volt-
age power cancels the lock-out.
IGNITION CONTROL BOARD
FIRST STAGE OF HEATING
TEMPERATURE LIMIT
When the ICB receives a call for first stage of heating, “W1,”
the draft motor is energized. Once the draft motor has been
proven, a 30-second purge is initiated. At the end of the
purge, both main valves of the GV are opened, and the spark
ignitor is energized for 10 seconds. The ICB then checks for
the presence of flame. If flame is detected, the ICB enters a
flame stabilization period. If flame was not detected, both
main valves close, and a retry operation begins.
If the UCB senses zero volts from the high temperature limit,
the indoor blower motor is immediately energized. When the
UCB again senses 24 volts from the temperature limit, the
draft motor will perform a 15-second post-purge and the
indoor blower will be de-energized following the elapse of the
fan off delay for heating.
This limit is monitored regardless of unit operation status, i.e.
this limit is monitored at all time.
During the flame stabilization period, a loss of the flame for 2
seconds will cause the main valves to close and the retry
operation to begin. After the flame stabilization period, a loss
of flame for 3/4 second will cause the main valves to close
and the retry operation to begin.
If the temperature limit opens three times within one hour, it
will lock-on the indoor blower motor and flash code is initiated
(See Table 28).
FLAME SENSE
At the conclusion of the flame stabilization period, the ICB will
operate the gas heat in high fire (both valves open) for an
additional 100 seconds (for a total for 120 seconds of high fire
operation). After this 100 seconds, the ICB will then use the
call for the second stage of heat to control the second main
valve of the GV.
Flame sensing occurs at all times. If “W1” is not present and
a flame is sensed for 2 seconds, the draft motor is energized
and the main valve is kept off. The ICB halts any operation
until a flame is not detected. Once the flame detection is lost,
the ICB performs a post-purge. Normal operation is allowed
concurrently with the purge (i.e. this purge can be considered
the purge associated with a call for “W1”).
When “W1” is satisfied, both valves are closed.
SECOND STAGE OF HEATING
If “W1” is present, a flame is sensed, but the main valve is not
energized, the draft motor is energized until the flame detec-
tion is lost. Normal operation is now allowed.
When the ICB receives a call for the second stage of heating,
“W2,” the ICB conducts a complete first stage ignition
sequence. If this sequence is satisfied, the second main
valve of the GV is opened.
The flame detection circuitry continually tests itself. If the ICB
finds the flame detection circuitry to be faulty, the ICB will not
permit an ignition sequence. Also, the draft motor is ener-
gized. If this failure should occur during an ignition cycle the
failure is counted as a recycle.
When “W2” is satisfied, the second main valve is closed.
RETRY OPERATION
When a flame is lost or is not detected during an attempt to
achieve ignition, a retry operation occurs. A 30-second purge
is performed between ignition attempts.
GAS VALVE
The UCB and ICB continuously monitor the GV.
Unitary Products Group
37
035-19046-002-B-0104
If the ICB senses voltage at the GV when not requested, the
ICB will energize the draft motor. The ICB will not operate the
furnace until voltage is no longer sensed at the GV. The draft
motor is stopped when voltage is not sensed at the GV.
The auxiliary limit switch is wired in series with the limit
switch. As such, the UCB cannot distinguish the auxiliary limit
and the gas heat limit switch operation except the auxiliary is
manual reset. Consequently, the control will respond in the
same manner as outlined above under “Limit Switch”.
Any time the UCB senses voltage at the GV without a call for
heat for a continuous five-minute period, the UCB will lock-on
the indoor blower and a flash code is initiated (Table 28).
When voltage is no longer sensed at the GV, the UCB will de-
energize the indoor blower following the elapse of the fan off
delay for heating.
*
TABLE 24: GAS HEAT LIMIT CONTROL SETTINGS
# of HX Tubes
Main Limit Setting
195°F
6
8
160°F
If voltage has been sensed at the GV for at least 15 seconds
during the fan on delay for heating and GV voltage or “W1” is
lost, the indoor blower is forced on for the length of the fan off
delay for heating.
*.
Rollout = 300°F, Auxiliary Limit = 200°F
The ICB monitors the Pressure and Rollout switches of gas
heat units.
During a call for heat, if the UCB does not sense voltage at
the GV for a continuous five-minute period the UCB will ini-
tiate a flash code (Table 28). The indoor blower motor will not
be locked-on while there is no GV voltage.
The control circuit includes the following safety controls:
PRESSURE SWITCH (PS)
However, if during a normal ignition sequence, the NPC has
been tested to be open, IDM energized, NPC closes and then
the first stage main valve (MV1) is detected as being on, the
ignition sequence stops and the IDM is de-energized. (Since
the NPC is wired serially with the main valve relays, de-ener-
gizing the IDM will open the NPC). This failure is counted as
a recycle and will result in an eventual recycle lockout. If the
main valve continues to be energized after the IDM is de-
energized the IDM is re-energized. The second stage (MV2)
main valve is not monitored for closure after energization.
Once the draft motor has reached full speed and closes the
pressure switch during a normal ignition sequence, if the
pressure sw opens for 2 seconds, the GV will be de-ener-
gized, the ignition cycle is aborted, and the ICB flashes the
appropriate code. See Table 29 Ignition Control Flash Codes.
The draft motor is energized until the pressure switch closes
or “W1” is lost.
ROLLOUT SWITCH (ROS)
The rollout switch is wired in series with the pressure switch.
As such, the ICB cannot distinguish the rollout switch opera-
tion from that of the pressure switch.
SAFETY CONTROLS
The UCB monitors the temperature limit switch of gas heat
units.
Consequently, the control will only respond in the same man-
ner as outlined above under “Pressure Switch”. An open roll-
out will inhibit the gas valve from actuating.
The control circuit includes the following safety controls:
INTERNAL MICROPROCESSOR FAILURE
LIMIT SWITCH (LS)
If the ICB detects an internal failure, it will turn cease all out-
puts, ignore inputs, and display the proper flash code for con-
trol replacement. The ICB remains in this condition until
replaced.
This control is located inside the gas heat compartment and
is set to open at the temperature indicated in the Gas Heat
Limit Control Settings Table 24. It resets automatically. The
limit switch operates when a high temperature condition,
caused by inadequate supply air flow occurs, thus shutting
down the heater and energizing the blower.
FLASH CODES
The UCB will initiate a flash code associated with errors
within the system. Refer to UNIT CONTROL BOARD FLASH
CODES Table 28.
AUXILIARY LIMIT SWITCH (ALS)
This control is located inside the supply air compartment and
is set to open at the temperature indicated in the Gas Heat
Limit Control Settings Table 24. It resets manually. The limit
switch operates when a high temperature condition, caused
by inadequate supply air flow occurs, thus shutting down the
heater and energizing the blower.
RESETS
Remove the call for heating by lowering the thermostat set-
ting lower than the conditioned space temperature. This
resets any flash codes.
38
Unitary Products Group
035-19046-002-B-0104
GAS HEAT ANTICIPATOR SETPOINTS
OPERATING INSTRUCTIONS
It is important that the anticipator setpoint be correct. Too
high of a setting will result in longer heat cycles and a greater
temperature swing in the conditioned space. Reducing the
value below the correct setpoint will give shorter “ON cycles
and may result in the lowering of the temperature within the
conditioned space. Refer to Table 25 for the required gas
heat anticipator setting.
1. Turn unit electrical power on.
NOTE: Prior to each cooling season, the crankcase heaters
must be energized at least 10 hours before the sys-
tem is put into operation.
2. Set the room thermostat setting to lower than the room
temperature.
3. First stage compressors will energize after the built-in
time delay (five minutes).
TABLE 25: GAS HEAT ANTICIPATOR SETPOINTS
SETTING, AMPS
4. The second stage of the thermostat will energize second
stage compressor if needed.
W1
W2
0.65
0.1
POST START CHECK LIST
1. Verify proper system pressures for both circuits.
2. Measure the temperature drop across the evaporator
coil.
H
E
A
T
E
X
C
H
A
N
G
E
R
T
U
B
E
START-UP (GAS HEAT)
G
S
P
A
S
PRE-START CHECK LIST
U
I
P
P
L
Y
B
U
R
N
E
R
ꢀ
L
A
M
E
B
U
R
N
E
R
P
E
(
B
L
U
E
O
N
L
Y
)
B
U
R
N
E
R
B
R
A
C
K
E
T
Complete the following checks before starting the unit.
I
G
N
I
T
O
R
1. Check the type of gas being supplied. Be sure that it is
the same as listed on the unit nameplate.
FIGURE 26 - TYPICAL FLAME
START-UP (COOLING)
PRESTART CHECK LIST
2. Make sure that the vent outlet and combustion air inlet
are free of any debris or obstruction.
OPERATING INSTRUCTIONS
After installation has been completed:
1. Check the electrical supply voltage being supplied. Be
sure that it is the same as listed on the unit nameplate.
2. Set the room thermostat to the off position.
3. Turn unit electrical power on.
This furnace is equipped with an intermittent pilot and
automatic re-ignition system. DO NOT attempt to
manually light the pilot.
4. Set the room thermostat fan switch to on.
5. Check indoor blower rotation.
LIGHTING THE MAIN BURNERS
1. Turn “OFF” electric power to unit.
2. Turn room thermostat to lowest setting.
•
If blower rotation is in the wrong direction. Refer to
Phasing Section in general information section.
3. Turn gas valve counter-clockwise to “ON” position (see
Figure 27).
•
Check blower drive belt tension.
6. Check the unit supply air (CFM).
4. Turn “ON” electric power to unit.
7. Measure evaporator fan motor's amp draw.
8. Set the room thermostat fan switch to off.
9. Turn unit electrical power off.
5. If thermostat set temperature is above room tempera-
ture, the main burners will ignite. If a second stage of
heat is called for, the main burners for second stage heat
will ignite for the second stage heat.
Unitary Products Group
39
035-19046-002-B-0104
2. Using the outlet pressure port on the gas valve, connect
a manometer to monitor the manifold pressure.
POST START CHECKLIST
After the entire control circuit has been energized and the
heating section is operating, make the following checks:
3. Remove plastic cap covering HI and LO pressure adjust-
ment screws.
1. Check for gas leaks in the unit piping as well as the sup-
ply piping.
4. Turn on power to the unit.
5. Set thermostat to call for second stage heat and start fur-
nace.
6. If necessary, using a screwdriver, turn the second stage
adjustment screw (adjacent to the “HI” marking on the
valve) clockwise to increase manifold pressure or coun-
terclockwise to decrease manifold pressure. Be sure not
to over-fire the unit on second stage.
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warning exactly could
result in serious injury, death or property damage.
7. After the high manifold pressure has been checked,
adjust the thermostat to call for first stage heat.
Never test for gas leaks with an open flame. use a
commercially available soap solution made specifi-
cally for the detection of leaks to check all connec-
tions. A fire or explosion may result causing property
damage, personal injury or loss of life.
8. If necessary, using a screwdriver, turn the first stage
adjustment screw (adjacent to the “LO” marking on the
valve) clockwise to increase manifold pressure or
counterclockwise to decrease manifold pressure. Be
sure not to under-fire the unit on first stage.
2. Check for correct manifold gas pressures. (See ’CHECK-
ING GAS INPUT’.)
9. Once pressure has been checked, replace the plastic
cap covering the HI and LO pressure adjustment screws.
3. Check the supply gas pressure. It must be within the lim-
its shown on the rating nameplate. Supply pressure
should be checked with all gas appliances in the building
at full fire. At no time should the standby gas pressure
exceed 13 in. or the operating pressure drop below 5.0 in
for natural gas units. If gas pressure is outside these
limits, contact the local gas utility or propane supplier for
corrective action.
NOTE: When using natural gas, the manifold pressure for
second stage (100% input) should be 3.5 IWG ±
0.3. The manifold pressure for first stage (60%
input) when using natural gas should be 1.5 IWG ±
0.3.
CHECKING GAS INPUT
NATURAL GAS
SHUT DOWN
1. Set the thermostat to the lowest temperature setting.
2. Turn “OFF” all electric power to unit.
3. Open gas heat access panel.
This unit has two stages of gas heat. The first stage is 60% of
the full fire input and is considered the minimum input for the
furnace. The intended input for each furnace is shown in the
table below. The following Table applies to units operating on
60 Hz power only.
4. Turn gas valve clockwise to “OFF” position (See Figure
27).
TABLE 26: GAS HEAT STAGES
MANIFOLD GAS PRESSURE ADJUSTMENT
2nd Stage
Input (100%
Btuh)
1st Stage
Input (60%
Btuh)
# of Burner Tubes
This gas furnace has two heat stages. Therefore, the gas
valve has two adjustment screws located under a plastic pro-
tective cover. The second stage (100% input) adjustment
screw is adjacent to the “HI” marking on the valve and the
first stage (60% input) adjustment screw is located adjacent
to the “LO” marking on the valve (See Figure 27).
6
8
180,000
240,000
108,000
144,000
To determine the rate of gas flow (second Stage).
1. Turn of all other gas appliances connected to the gas
meter.
Manifold pressure adjustment procedure.
Adjust second stage (100% input) pressure first, then adjust
first stage (60% input) pressure.
2. Turn on the furnace and make sure the thermostat is
calling for Second stage (100% input) heat.
1. Turn off all power to the unit.
40
Unitary Products Group
035-19046-002-B-0104
3. Measure the time needed for one revolution of the hand
on the smallest dial on the meter. A typical gas meter
has a 1/2 or a 1 cubic foot test dial.
TABLE 27: GAS RATE CUBIC FEET PER HOUR
Seconds
for One
Rev.
Size of Test Dial
1/2 cu. ft.
1 cu. ft.
4. Using the number of seconds it takes for one revolution
of the dial, calculate the cubic feet of gas consumed per
hour. (See example below).
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
180
150
129
113
100
90
82
75
69
64
60
56
53
50
47
45
43
41
39
37
36
35
34
32
31
30
360
300
257
225
200
180
164
150
138
129
120
113
106
100
95
5. If necessary, adjust the high pressure regulator as dis-
cussed in the section “Manifold Gas Pressure Adjust-
ment”. Be sure not to over-fire the furnace on Second
stage. If in doubt, it is better to leave the Second stage of
the furnace slightly under-fired. Repeat Steps 1-5.
To determine the rate of gas flow (First Stage)
1. Turn of all other gas appliances connected to the gas
meter.
2. Turn on the furnace and make sure the thermostat is
calling for first stage (60% input) heat.
3. Even when the thermostat is calling for first stage heat,
the unit will light on second stage and will run on Second
stage for 1 minute. Allow this one-minute time period to
expire and be certain the unit is running on first stage.
90
86
4. Measure the time needed for one revolution of the hand
on the smallest dial on the meter. A typical gas meter
has a 1/2 or a 1 cubic foot test dial.
82
78
75
5. Using the number of seconds it takes for one revolution
of the dial, calculate the cubic feet of gas consumed per
hour (See example below).
72
69
67
6. If necessary, adjust the low pressure regulator as dis-
cussed in the section “Manifold Gas Pressure Adjust-
ment”. Be sure not to under-fire the furnace on first
stage. If in doubt, it is better to leave the first stage of the
furnace slightly over-fired (greater than 60% input).
Repeat Steps 1-6.
64
62
60
NOTE: To find the Btu input, multiply the number of cubic
feet of gas consumed per hour by the Btu content of
the gas in your particular locality (contact your gas
company for this information as it varies widely from
area to area).
Unitary Products Group
41
035-19046-002-B-0104
EXAMPLE:
3. Disconnect wiring to the gas valves and spark igniter(s).
Remove the manifold & gas valve assembly. Orifices can
now be inspected and/or replaced.
By actual measurement, it takes 19 seconds for the hand on
a 1 cubic foot dial to make a revolution with a 192,000 Btuh
furnace running. To determine rotations per minute, divide 60
by 19 = 3.16. To calculate rotations per hour, multiply 3.16 •
60 = 189.6. Multiply 189.6 • 1 (0.5 if using a 1/2 cubic foot
dial) = 189.6. Multiply 189.6 • (the Btu rating of the gas). For
this example, assume the gas has a Btu rating of 1050
To service burners, complete step 4.
4. Remove the heat shield on top of the manifold supports.
Burners are now accessible for inspection and/or
replacement.
NOTE: Reverse the above procedure to replace the assem-
Btu/ft.3. The result of 199,000 Btuh is within 5% of the
192,000 Btuh rating of the furnace.
blies.
Make sure that burners are level and seat at the rear of the
gas orifice.
ADJUSTMENT OF TEMPERATURE RISE
The temperature rise (the difference of temperature between
the return air and the heated air from the furnace) must lie
within the range shown on the CSA rating plate and the data
in Table 25.
H
I
G
H
&
L
O
W
G
A
S
A
D
J
U
S
T
M
E
N
T
After the temperature rise has been determined, the CFM can
be calculated as follows:
L
O
H
I
0.8
(1.08 ⋅ ∆°F)
-----------------------------
CFM = Btu Input •
O
N
I
N
L
E
T
O
ꢀ
ꢀ
P
R
E
S
S
U
R
E
After about 20 minutes of operation, determine the furnace
temperature rise. Take readings of both the return air and the
heated air in the ducts (about 6 feet from the furnace) where
they will not be affected by radiant heat. Increase the blower
CFM to decrease the temperature rise; decrease the blower
CFM to increase the rise (See ’SUPPLY AIR DRIVE
ADJUSTMENT’).
T
A
P
O
U
T
L
E
T
R
P
R
E
S
S
U
E
T
A
P
M
A
T
E
N
-
N
-
L
O
C
K
C
O
N
E
C
T
O
R
S
NOTE: Each gas heat exchanger size has a minimum
allowable CFM. Below this CFM, the limit will open
below this rating.
M
V
I
C
H
BURNERS/ORIFICES INSPECTION/SERVICING
Before checking or changing burners, pilot or orifices,
CLOSE MAIN MANUAL SHUT-OFF VALVE AND SHUT OFF
ALL POWER TO THE UNIT.
1. Open the union fitting just upstream of the unit gas valve
and downstream from the main manual shut-off valve in
the gas supply line.
FIGURE 27 - TYPICAL GAS VALVE
2. Remove the screws holding each end of the manifold to
the manifold supports.
42
Unitary Products Group
035-19046-002-B-0104
CHARGING THE UNIT
TABLE 28: UNIT CONTROL BOARD FLASH CODES
Flash Code
On Steady
Heart Beat
1 Flash
Description
Control Failure - Replace Control
Normal Operation
The DJ150 (12-1/2 Ton) High Efficiency Unit, uses a TXV
metering device. Charge unit to 10º sub-cooling at the TXV.
Not Applicable
TROUBLESHOOTING
*
2 Flashes
3 Flashes
4 Flashes
5 Flashes
6 Flashes
7 Flashes
8 Flashes
Control waiting ASCD
HPS1 - Compressor Lock out
HPS2 - Compressor Lock out
LPS1 - Compressor Lock out
LPS2 - Compressor Lock out
FS1 - Compressor Lock out
FS2 - Compressor Lock out
Troubleshooting of components may require open-
ing the electrical control box with the power con-
nected to the unit. Use extreme care when
working with live circuits! Check the unit name-
plate for the correct line voltage and set the voltme-
ter to the correct range before making any
connections with line terminals.
Ignition Control Locked Out/
Ignition Control Failure / Limit Switch Trip / No
Jumper Plug in Heat Section
9 Flashes
Compressors Locked Out On Low
10 Flashes
11 Flashes
12 Flashes
*
Outdoor Air Temperature
When not necessary, shut off all electric power to the
unit prior to any of the following maintenance proce-
dures so as to prevent personal injury.
Compressors Locked Out Because The
*
Economizer Is Using Free Cooling
Fan Overload Switch Trip - Not Applicable On This
Unit
13 Flashes
14 Flashes
OFF
Compressor Held Off Due To Low Voltage*
EEPROM Storage Failure (Control Failure)
No Power or Control Failure
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dan-
gerous operation which could cause injury to person
and/or damage unit components. Verify proper oper-
ation after servicing.
*.
These flash codes do not represent alarms.
TABLE 29: IGNITION CONTROL FLASH CODES
FLASHES
STEADY ON
HEARTBEAT
1
FAULT CONDITIONS
CHECK
PREDATOR MAGNUM FLASH CODES
Control Failure
Control
Normal Operation
Not Applicable
Various flash codes are utilized by the unit control board
(UCB) to aid troubleshooting. Flash codes are distinguished
by the short on and off cycle used (approximately 200ms on
and 200ms off). To show normal operation, the control board
flashes a 1 second on, 1 second off “heartbeat” during normal
operation. This is to verify that the UCB is functioning cor-
rectly. Do not confuse this with an error flash code. To prevent
confusion, a 1-flash, flash code is not used.
Pressure Switch
Stuck Closed
2
3
4
Pressure Switch
Pressure Switch Failed
To Close
Venter Pressure Switch
Vent Blocked
Main Limit
AUX Limit
Limit Switch Open
Current alarms are flashed on the UCB LED. The alarm his-
tory can be checked by pressing and releasing the ALARMS
button on the UCB. The UCB will cycle through the last five
(5) alarms, most recent to oldest, separating each alarm flash
code by approximately 2 seconds.
Flame Present With Gas
Off First Stage Gas Valve
Energized With W1 Off
Second Stage Gas Valve
Energized With First
Stage
5
Gas Valve
Gas Valve Off
In some cases, it may be necessary to “zero” the ASCD for
the compressors in order to perform troubleshooting. To reset
all ASCDs for one cycle, press and release the UCB TEST
button once.
Gas Flow
Gas Pressure
Gas Valve
6
Ignition Lockout
Flame Sensor
No Power Or Control
Failure
24VAC or Control
STEADY OFF
Unitary Products Group
43
035-19046-002-B-0104
Loss of
Call for
Heating?
Monitored
Systems
Problem?
No
Yes
No
No
Call for
Heating?
Programming?
Yes
Heat Off
Yes
Yes
No
Program
Unit
Control
Board
Call for 2nd
Stage
Cooling
Call for
Heat
Trip/Failure
No
Yes
Energize ID
Call for
First
Monitor
Blower Motor
Cooling?
Stage?
Yes
No
Yes
No
Call for 1st
Stage
Cooling
No
Yes
Turn off ID
Blower Motor
Fan on
>30 secs?
Fan off
>10 secs?
Yes
Yes
No
No
No
Yes
Lossof Call
for ID Blower?
Call for
ID Blower?
Loss of Call
for Cooling?
Cool Off
FIGURE 28 - BASIC TROUBLESHOOTING FLOWCHART
Yes
Yes
Voltage @
Gas Valve?
Call for
heat?
Power to
Unit
No
No
Energize ID
Blower
Initialize ASCD
Montior
FIGURE 29 - POWER ON FLOW CHART
44
Unitary Products Group
035-19046-002-B-0104
H
P
L
P
N
o
N
o
N
o
N
o
L
o
s
s
o
f
ꢀ
r
e
e
z
e
s
t
a
t
T
r
i
p
/
ꢀ
a
i
l
u
r
e
S
w
i
t
c
h
S
w
i
t
c
h
O
p
e
n
1
L
S
I
n
p
u
t
O
p
e
n
?
1
2
O
p
e
n
>
5
S
e
c
s
Y
e
s
Y
e
s
Y
e
s
Y
e
s
T
u
r
n
o
f
f
T
u
r
n
o
f
f
T
u
r
n
o
f
f
E
n
e
r
g
i
z
e
b
l
o
w
e
r
:
c
o
m
p
r
e
s
s
o
r
;
C
o
m
p
r
e
s
s
o
r
,
c
o
m
p
r
e
s
s
o
r
,
i
n
c
r
e
a
s
e
i
n
c
i
d
e
n
t
i
n
i
t
i
a
t
e
A
S
C
D
;
i
n
i
t
i
a
t
e
A
S
C
D
;
i
n
i
t
i
a
t
e
A
S
C
D
;
v
a
l
u
e
b
y
1
i
n
c
r
e
a
s
e
i
n
c
i
d
e
n
t
i
n
c
r
e
a
s
e
i
n
c
i
d
e
n
t
i
n
c
r
e
a
s
e
i
n
c
i
d
e
n
t
v
a
l
v
e
b
y
1
v
a
l
u
e
b
y
1
v
a
l
u
e
b
y
1
N
o
N
o
N
o
N
o
I
n
c
i
d
e
n
t
L
S
i
n
p
u
t
I
n
c
i
d
e
n
t
I
n
c
i
d
e
n
t
I
n
c
i
d
e
n
t
v
a
l
u
e
>
=
3
?
r
e
g
a
i
n
e
d
?
v
a
l
u
e
>
=
3
v
a
l
u
e
>
=
3
v
a
l
u
e
>
=
3
N
o
Y
e
s
Y
e
s
Y
e
s
Y
e
s
Y
e
s
L
o
c
k
s
-
s
o
u
t
L
o
c
k
-
o
u
t
L
o
c
k
-
o
u
t
c
o
m
p
r
e
o
r
,
t
u
r
n
L
o
c
k
o
n
b
l
o
w
e
r
;
L
o
a
d
ꢀ
o
f
f
D
c
o
m
p
r
e
s
s
o
r
,
f
l
a
g
c
o
m
p
r
e
s
s
o
r
,
f
l
a
g
o
f
f
I
D
b
l
o
w
e
r
,
t
u
r
n
f
l
a
g
a
l
a
r
m
a
l
a
r
m
a
l
a
r
m
o
f
f
c
o
n
d
e
n
s
e
r
f
a
n
s
,
f
l
a
g
a
l
a
r
m
M
o
n
i
t
o
r
G
V
L
o
s
s
o
f
C
a
l
l
f
o
r
N
o
N
o
N
o
N
o
v
o
l
t
a
g
e
G
V
v
o
l
t
a
g
e
ꢀ
O
S
i
n
p
u
t
H
e
a
t
w
/
o
u
t
G
V
w
/
o
u
t
c
a
l
l
f
o
r
>
5
m
i
n
?
>
5
S
e
c
s
?
v
o
l
t
a
g
e
?
h
e
a
t
?
Y
e
s
Y
e
s
Y
e
s
ꢀ
l
a
g
A
l
a
r
m
T
u
r
n
o
f
f
f
a
n
N
o
Y
e
s
c
o
m
p
r
e
s
s
o
r
&
ꢀ
l
a
g
a
l
a
r
m
,
w
l
o
c
k
v
o
l
t
a
g
e
>
5
c
o
n
d
e
n
s
e
r
f
a
n
s
;
o
n
I
D
b
l
o
e
r
m
i
n
?
i
n
i
t
i
a
t
e
A
S
C
D
N
o
N
o
N
o
I
n
c
i
d
e
n
t
ꢀ
O
S
i
n
p
u
t
L
o
s
s
o
f
G
V
ꢀ
O
S
i
n
p
u
t
>
1
5
v
a
l
u
s
e
>
=
3
r
e
g
a
i
n
e
d
?
V
o
l
t
a
g
e
?
Y
e
s
N
o
m
i
n
u
t
e
s
?
Y
e
Y
e
s
Y
e
s
N
o
L
o
c
k
-
o
u
t
E
n
e
r
g
i
z
e
I
D
c
o
m
p
r
e
s
s
o
r
s
,
t
u
r
n
I
n
c
r
e
a
s
e
i
n
c
i
d
e
n
t
ꢀ
l
a
g
a
l
a
r
m
,
t
u
r
n
o
n
b
l
o
w
e
r
,
l
o
a
d
'
ꢀ
a
n
o
f
f
I
D
b
l
o
w
e
r
,
t
u
r
n
v
a
l
u
e
b
y
1
X
l
i
n
e
O
f
f
D
e
l
a
y
'
f
o
r
o
f
f
c
o
n
d
e
n
s
e
r
h
e
a
t
i
n
g
f
a
n
s
,
f
l
a
g
a
l
a
r
m
M
o
n
i
t
o
r
1
2
T
T
h
h
e
e
c
l
o
n
t
r
o
l
b
s
o
a
r
d
o
n
l
i
y
t
m
o
i
n
i
t
o
r
s
t
h
e
i
n
p
u
t
w
h
e
n
t
h
e
c
o
m
p
r
e
s
s
o
r
r
e
a
l
l
y
i
s
e
n
e
r
g
i
z
e
d
.
o
w
-
p
r
e
s
u
r
e
0
s
s
w
e
c
h
s
n
o
t
m
o
n
i
t
o
o
r
l
e
d
f
o
r
t
h
e
f
i
r
s
t
3
0
s
e
c
o
n
d
s
o
f
c
o
m
p
r
e
s
s
o
r
a
c
t
i
v
i
t
y
.
T
h
e
c
o
n
t
r
o
l
b
o
a
r
d
t
h
e
n
m
o
n
i
t
o
r
s
t
h
e
s
w
i
t
c
h
t
o
e
n
s
u
r
e
i
t
c
l
o
s
e
s
.
I
f
t
h
e
s
w
i
t
c
h
r
e
m
a
i
n
s
o
p
e
n
a
l
n
d
a
d
d
h
i
t
i
o
n
a
l
3
c
o
n
d
s
,
t
h
e
c
o
n
t
r
i
b
o
a
r
d
t
u
r
n
s
o
h
f
a
f
t
h
e
a
s
s
o
c
i
a
t
e
d
c
o
m
p
r
e
s
s
o
r
a
n
d
i
n
i
t
i
a
t
e
s
t
h
e
A
S
C
D
.
O
n
c
e
i
t
h
a
s
c
l
o
s
e
d
d
u
r
i
n
g
t
h
e
s
t
a
r
t
u
p
p
e
r
i
o
d
,
t
h
e
c
o
n
t
r
o
l
b
o
a
r
d
n
o
o
n
g
e
r
a
n
d
l
e
s
t
h
e
l
o
w
-
p
r
e
s
s
u
r
e
s
w
t
c
h
d
i
f
f
e
r
e
n
t
l
y
t
n
o
t
h
e
r
i
n
p
u
t
s
.
FIGURE 30 - TRIP FAILURE FLOW CHART
Unitary Products Group
45
035-19046-002-B-0104
On calls for cooling, the supply air blower motor is operating
but compressor #1 is not (the room thermostat fan switch is in
the “AUTO” position).
COOLING TROUBLESHOOTING GUIDE
On calls for cooling, if the compressors are operating but the
supply air blower motor does not energize after a short delay
(the room thermostat fan switch is in the “AUTO” position).
1. If installed, check the position of the economizer blades.
If the blades are open, the economizer is providing free
cooling and the compressors will not immediately oper-
ate. If both stages of cooling are requested simulta-
neously and the economizer provides free cooling,
following a short delay compressor #1 will be energized
unless it is locked out. If compressor #1 is locked out,
compressor #2 is energized. Compressor #2 is always
energized in place of compressor #1 when compressor
#1 is requested but locked out.
1. Turn the thermostat fan switch to the ON position. If the
supply air blower motor does not energize, go to Step 3.
2. If the blower motor runs with the fan switch in the ON
position but will not run after the first compressor has
energized when the fan switch is in the AUTO position,
check the room thermostat for contact between R and G
in the AUTO position during calls for cooling.
3. If the supply air blower motor does not energize when
the fan switch is set to ON, check that line voltage is
being supplied to the contacts of the M3, contactor, and
that the contactor is pulled in. Check for loose wiring
between the contactor and the supply air blower motor.
2. If no economizer is installed or the economizer is not
opening to provide free cooling and compressor #1 does
not energize on a call for cooling, check for line voltage
at the compressor contactor, M1, and that the contactor
is pulled in. Check for loose wiring between the contac-
tor and the compressor.
4. If M3 is pulled in and voltage is supplied to M3, lightly
touch the supply air blower motor housing. If it is hot, the
motor may be off on internal protection. Cancel any
thermostat calls and set the fan switch to AUTO. Wait for
the internal overload to reset. Test again when cool.
3. If M1 is pulled in and voltage is supplied at M1, lightly
touch the compressor housing. If it is hot, the compres-
sor may be off on inherent protection. Cancel any calls
for cooling and wait for the internal overload to reset.
Test again when cool.
5. If M3 is not pulled in, check for 24 volts at the M3 coil. If
24 volts are present at M3 but M3 is not pulled in,
replace the contactor.
4. If M1 is not pulled in, check for 24 volts at the M1 coil. If
24 volts are present and M1 is not pulled in, replace the
contactor.
6. Failing the above, if there is line voltage supplied at M3,
M3 is pulled in, and the supply air blower motor still does
not operate, replace the motor.
5. Failing the above, if voltage is supplied at M1, M1 is
pulled in, and the compressor still does not operate,
replace the compressor.
7. If 24 volts is not present at M3, check that 24 volts is
present at the UCB supply air blower motor terminal,
“FAN”. If 24 volts is present at the FAN, check for loose
wiring between the UCB and M3.
6. If 24 volts is not present at M1, check for 24 volts at the
UCB terminal, C1. If 24 volts is present, check for loose
wiring between C1 and the compressor contactor.
8. If 24 volts is not present at the “FAN” terminal, check for
24 volts from the room thermostat. If 24 volts are not
present from the room thermostat, check for the follow-
ing:
7. If 24 volts is not present at the C1 terminal, check for 24
volts from the room thermostat at the UCB Y1 terminal.
If 24 volts is not present from the room thermostat, check
for the following:
a. Proper operation of the room thermostat (contact
between R and G with the fan switch in the ON posi-
tion and in the AUTO position during operation
calls).
a. 24 volts at the thermostat Y1 terminal
b. Proper wiring between the room thermostat and the
UCB, i.e. Y1 to Y1, Y2 to Y2
c. Loose wiring from the room thermostat to the UCB.
b. Proper wiring between the room thermostat and the
UCB.
8. If 24 volts is present at the UCB Y1 terminal, the com-
pressor may be out due to an open high-pressure switch,
low-pressure switch, or freezestat. Check for 24 volts at
the HPS1, LPS1, and FS1 terminals of the UCB. If a
switch has opened, there should be a voltage potential
between the UCB terminals, e.g. if LPS1 has opened,
there will be a 24-volt potential between the LPS1 termi-
nals.
c. Loose wiring from the room thermostat to the UCB.
9. If 24 volts is present at the room thermostat but not at the
UCB, check for proper wiring between the thermostat
and the UCB, i.e. that the thermostat G terminal is con-
nected to the G terminal of the UCB, and for loose wir-
ing.
9. If 24 volts is present at the UCB Y1 terminal and none of
the protection switches have opened, the UCB may have
10. If the thermostat and UCB are properly wired, replace
the UCB.
46
Unitary Products Group
035-19046-002-B-0104
locked out the compressor for repeat trips. The UCB
should be flashing an alarm code. If not, press and
release the ALARMS button on the UCB. The UCB will
flash the last five alarms on the LED. If the compressor is
locked out, cancel any call for cooling. This will reset any
compressor lock outs.
On calls for the second stage of cooling, the supply air blower
motor and compressor #1 are operating but compressor #2 is
not (the room thermostat fan switch is in the “AUTO” posi-
tion).
1. If installed, check the position of the economizer blades.
If the blades are open, the economizer is providing free
cooling. If the second stage of cooling is requested, fol-
lowing a short delay, compressor #1 will be energized
unless it is locked out. Typically, compressor #2 is ener-
gized only during free cooling if the call for the second
stage of cooling persists for 20 minutes.
NOTE: While the above step will reset any lockouts, com-
pressor #1 may be held off for the ASCD. See the
next step.
10. If 24 volts is present at the UCB Y1 terminal and none of
the switches are open and the compressor is not locked
out, the UCB may have the compressor in an ASCD.
Check the LED for an indication of an ASCD cycle. The
ASCD should time out within 5 minutes. Press and
release the TEST button to reset all ASCDs.
2. Compressor #2 will not energize simultaneously with
compressor #1 if a call for both stages of cooling is
received. The UCB delays compressor #2 by 30 sec-
onds to prevent a power surge. If after the delay com-
pressor #2 does not energize on a second stage call for
cooling, check for line voltage at the compressor contac-
tor, M2, and that the contactor is pulled in. Check for
loose wiring between the contactor and the compressor.
11. If 24 volts is present at the UCB Y1 terminal and the
compressor is not out due to a protective switch trip,
repeat trip lock out, or ASCD, the economizer terminals
of the UCB may be improperly wired. Check for 24 volts
at the Y1 “OUT” terminal of the UCB. If 24 volts is
present, trace the wiring from Y1 “OUT” for incorrect wir-
ing. If 24 volts is not present at the Y1 “OUT” terminal,
the UCB must be replaced.
3. If M2 is pulled in and voltage is supplied at M2, lightly
touch the compressor housing. If it is hot, the compres-
sor may be off on inherent protection. Cancel any calls
for cooling and wait for the internal overload to reset.
Test again when cool.
12. For units without economizers:If 24 volts is present at the
Y1 OUT terminal, check for 24 volts at the Y1 “ECON”
terminal. If 24 volts is not present, check for loose wiring
from the Y1 “OUT” terminal to the Mate-N-Lock plug, the
jumper in the Mate-N-Lock plug, and in the wiring from
the Mate-N-Lock plug to the Y1 “ECON” terminal.
4. If M2 is not pulled in, check for 24 volts at the M2 coil. If
24 volts is present and M2 is not pulled in, replace the
contactor.
5. Failing the above, if voltage is supplied at M2, M2 is
pulled in, and the compressor still does not operate,
replace the compressor.
13. For units with economizers: If 24 volts is present at the
Y1 “OUT” terminal, check for 24 volts at the Y1 “ECON”
terminal. If 24 volts is not present, check for loose wiring
from the Y1 “OUT” terminal to the Mate-N-Lock plug, a
poor connection between the UCB and economizer
Mate-N-Lock plugs, loose wiring from the Mate-N-Lock
plug to the economizer, back to the Mate-N-Lock plug,
and from the Mate-N-Lock plug to the Y1 “ECON” termi-
nal. If nothing is found, the economizer DME may have
faulted and is failing to return the 24-volt “call” to the Y1
“ECON” terminal even though the economizer is not pro-
viding free cooling. To test, disconnect the Mate-N-Locks
and jumper between the WHITE and YELLOW wires of
the UCB’s Mate-N-Lock plug. If compressor #1 ener-
gizes, there is a fault in the economizer wiring or DME.
6. If 24 volts is not present at M2, check for 24 volts at the
UCB terminal, C2. If 24 volts are present, check for
loose wiring between C2 and the compressor contactor.
7. If 24 volts is not present at the C2 terminal, check for 24
volts from the room thermostat at the UCB Y2 terminal. If
24 volts is not present from the room thermostat, check
for the following:
a. 24 volts at the thermostat Y2 terminal
b. Proper wiring between the room thermostat and the
UCB, i.e. Y1 to Y1, Y2 to Y2
c. Loose wiring from the room thermostat to the UCB.
14. The UCB can be programmed to lock out compressor
operation during free cooling and in low ambient condi-
tions. These options are not enabled by default. Local
York distributors can test the UCB for this programming.
8. If 24 volts is present at the UCB Y2 terminal, the com-
pressor may be out due to an open high-pressure switch,
low-pressure switch, or freezestat. Check for 24 volts at
the HPS2, LPS2, and FS2 terminals of the UCB. If a
switch has opened, there should be a voltage potential
between the UCB terminals, e.g. if LPS2 has opened,
there will be 24 volts of potential between the LPS2 ter-
minals.
15. If none of the above corrected the error, test the integrity
of the UCB. Disconnect the C1 terminal wire and jumper
it to the Y1 terminal. DO NOT jump the Y1 to C1 termi-
nals. If the compressor engages, the UCB has faulted.
16. If none of the above correct the error, replace the UCB.
9. If 24 volts is present at the UCB Y2 terminal and none of
the protection switches have opened, the UCB may have
Unitary Products Group
47
035-19046-002-B-0104
locked out the compressor for repeat trips. The UCB
should be flashing a code. If not, press and release the
ALARMS button on the UCB. The UCB will flash the last
five alarms on the LED. If the compressor is locked out,
6. If 24 volts is not present at M1, check for 24 volts at the
UCB terminal, C1. If 24 volts is present, check for loose
wiring between C1 and the compressor contactor.
7. If 24 volts is not present at the C1 terminal, check for 24
volts from the room thermostat at the UCB Y1 terminal.
If 24 volts are not present at the UCB Y1 terminal, the
UCB may have faulted. Check for 24 volts at the Y1
ECON terminal. If 24 volts is not present at Y1 “ECON”,
the UCB has faulted. The UCB should de-energize all
compressors on a loss of call for the first stage of cool-
ing, i.e. a loss if 24 volts at the Y1 terminal.
remove any call for cooling at the thermostat or by dis-
connecting the thermostat wiring at the Y2 UCB terminal.
This will reset any compressor lock outs.
NOTE: While the above step will reset any lock outs, com-
pressor #1 will be held off for the ASCD, and com-
pressor #2 may be held off for a portion of the
ASCD. See the next step.
8. If 24 volts are present at the UCB Y1 terminal, the com-
pressor may be out due to an open high-pressure switch,
low-pressure switch, or freezestat. Check for 24 volts at
the HPS1, LPS1, and FS1 terminals of the UCB. If a
switch has opened, there should be a voltage potential
between the UCB terminals, e.g. if LPS1 has opened,
there will be a 24-volt potential between the LPS1 termi-
nals.
10. If 24 volts is present at the UCB Y2 terminal and none of
the switches are open and the compressor is not locked
out, the UCB may have the compressor in an ASCD.
Check the LED for an indication of an ASCD cycle. The
ASCD should time out within 5 minutes. Press and
release the TEST button to reset all ASCDs.
11. The UCB can be programmed to lock out compressor
operation during free cooling and in low ambient condi-
tions. These options are not enabled by default. Local
York distributors can test the UCB for this programming.
9. If 24 volts is present at the UCB Y1 terminal and none of
the protection switches have opened, the UCB may have
locked out the compressor for repeat trips. The UCB
should be flashing a code. If not, press and release the
ALARMS button on the UCB. The UCB will flash the last
five alarms on the LED. If the compressor is locked out,
remove any call for cooling. This will reset any compres-
sor lock outs.
12. If none of the above corrected the error, test the integrity
of the UCB. Disconnect the C2 terminal wire and jumper
it to the Y2 terminal. DO NOT jump the Y2 to C2 termi-
nals. If the compressor engages, the UCB has faulted.
13. If none of the above correct the error, replace the UCB.
NOTE: While the above step will reset any lock outs, com-
pressor #2 will be held off for the ASCD, and com-
pressor #1 may be held off for a portion of the
ASCD. See the next step.
On a call for cooling, the supply air blower motor and com-
pressor #2 are operating but compressor #1 is not (the room
thermostat fan switch is in the “AUTO” position).
10. If 24 volts is present at the UCB Y1 terminal and none of
the switches are open and the compressor is not locked
out, the UCB may have the compressor in an ASCD.
Check the LED for an indication of an ASCD cycle. The
ASCD should time out within 5 minutes. Press and
release the TEST button to reset all ASCDs.
1. Compressor #2 is energized in place of compressor #1
when compressor #1 is unavailable for cooling calls.
Check the UCB for alarms indicating that compressor #1
is locked out. Press and release the ALARMS button if
the LED is not flashing an alarm.
2. Check for line voltage at the compressor contactor, M1,
and that the contactor is pulled in. Check for loose wiring
between the contactor and the compressor.
11. If 24 volts is present at the UCB Y1 terminal and the
compressor is not out due to a protective switch trip,
repeat trip lock out, or ASCD, the economizer terminals
of the UCB may be improperly wired. Check for 24 volts
at the Y1 “OUT” terminal of the UCB. If 24 volts is
present, trace the wiring from Y1 “OUT” for incorrect wir-
ing. If 24 volts is not present at the Y1 “OUT” terminal,
the UCB must be replaced.
3. If M1 is pulled in and voltage is supplied at M1, lightly
touch the compressor housing. If it is hot, the compres-
sor may be off on inherent protection. Cancel any calls
for cooling and wait for the internal overload to reset.
Test again when cool.
4. If M1 is not pulled in, check for 24 volts at the M1 coil. If
24 volts is present and M1 is not pulled in, replace the
contactor.
12. For units without economizers: If 24 volts is present at
the Y1 “OUT” terminal, check for 24 volts at the Y1
“ECON” terminal. If 24 volts is not present, check for
loose wiring from the Y1 “OUT” terminal to the Mate-N-
Lock plug, the jumper in the Mate-N-Lock plug, and in
the wiring from the Mate-N-Lock plug to the Y1 “ECON”
terminal.
5. Failing the above, if voltage is supplied at M1, M1 is
pulled in, and the compressor still does not operate,
replace the compressor.
48
Unitary Products Group
035-19046-002-B-0104
For units with economizers:If 24 volts is present at the
Y1 “OUT” terminal, check for 24 volts at the Y1 “ECON”
terminal. If 24 volts is not present, check for loose wiring
from the Y1 “OUT” terminal to the Mate-N-Lock plug, a
poor connection between the UCB and economizer
Mate-N-Lock plugs, loose wiring from the Mate-N-Lock
plug to the economizer, back to the Mate-N-Lock plug,
and from the Mate-N-Lock plug to the Y1 “ECON” termi-
nal. The economizer board may have faulted and is not
returning the 24 volts to the Y1 “ECON” terminal even
though the economizer is not providing free cooling. To
test the economizer board, disconnect the Mate-N-Locks
and jumper between the WHITE and YELLOW wires of
the UCB’s Mate-N-Lock plug.
4. If M3 is not pulled in, check for 24 volts at the M3 coil. If
24 volts is present at M3 but M3 is not pulled in, replace
the contactor.
5. Failing the above, if there is line voltage supplied at M3,
M3 is pulled in, and the supply air blower motor still does
not operate, replace the motor.
6. If 24 volts is not present at M3, check that 24 volts is
present at the supply air blower motor terminal on the
UCB. If 24 volts is present at the UCB terminal, check for
loose wiring between the UCB and M3.
7. If 24 volts is not present at the UCB supply air blower
motor terminal, check for 24 volts from the room thermo-
stat. If 24 volts is not present from the room thermostat,
check for the following:
13. The UCB can be programmed to lock out compressor
operation during free cooling and in low ambient condi-
tions. These options are not enabled by default. They
can be checked by local York distributors.
a. Proper operation of the room thermostat (contact
between R and G with the fan switch in the “ON”
position and in the “AUTO” position during operation
calls).
14. If none of the above corrected the error, test the integrity
of the UCB. Disconnect the C1 terminal wire and jumper
it to the Y1 terminal. DO NOT jump the Y1 to C1 termi-
nals. If the compressor engages, the UCB has faulted.
b. Proper wiring between the room thermostat and the
UCB.
c. Loose wiring from the room thermostat to the UCB.
15. If none of the above correct the error, replace the UCB.
8. If 24 volts is present at the room thermostat but not at the
UCB, check for proper wiring between the thermostat
and the UCB, i.e. that the thermostat G terminal is con-
nected to the G terminal of the UCB, and for loose wir-
ing.
GAS HEAT TROUBLESHOOTING GUIDE
On calls for heating, the draft motor operates and the furnace
lights but the supply air blower motor does not energize after
a short delay (the room thermostat fan switch is in “AUTO”
position).
9. If the thermostat and UCB are properly wired, replace
the UCB.
10. If the blower motor runs with the fan switch in the “ON”
position but does not run shortly after the furnace has
ignited when the fan switch is in the “AUTO” position,
check the room thermostat for contact between R and G
during “W1” calls.
The furnace may shut down on a high temperature
condition during the procedure. If this occurs, the
UCB energize the supply air blower motor until the
high temperature limit has reset. Caution should be
used at all times as the supply air blower may ener-
gize regardless of the room thermostat fan switch
position.
On calls for heating, the supply air blower operates but the
draft motor does not (the room thermostat fan switch is in the
“AUTO” position).
1. The draft motor has inherent protection. If the motor
shell is hot to the touch, wait for the internal overload to
reset.
1. Place the thermostat fan switch in the “ON” position. If
the supply air blower motor energizes, go to Step 10.
2. If the motor shell is cold with the room thermostat calling
for heat, check for line voltage at the motor leads. If line
voltage is present, replace the draft motor.
2. If the supply air blower motor does not energize when
the fan switch is set to “ON,” check that line voltage is
being supplied to the contacts of the M3 contactor, and
that the contactor is pulled in. Check for loose wiring
between the contactor and the supply air blower motor.
3. If line voltage is not present, check for line voltage on the
ignition control at the “inducer” terminal draft motor relay
(DMR or DMC) contacts in the main control box and
check to see if the (DMR or DMC) is pulled in.
3. If M3 is pulled in and voltage is supplied at M3, lightly
touch the supply air blower motor housing. If it is hot, the
motor may be off on inherent protection. Cancel any
thermostat calls and set the fan switch to “AUTO”, wait
for the internal overload to reset. Test again when cool.
The draft motor runs but the furnace does not light and the
spark ignitor does not spark.
Unitary Products Group
49
035-19046-002-B-0104
1. Check for 24 volts at the spark ignitor from the ignition
control board (ICB). Check the 24-volt wiring from the
ICB to the spark ignitor. Check for 24 volts at the ICB
spark ignitor terminal.
The draft motor runs and the spark ignitor sparks at the
burner, but the burner does not ignite and a gas odor is not
detected at the draft motor outlet.
1. Check to ensure gas is being supplied to the unit. Con-
firm that the gas pressure to the unit is within the proper
limits as described in the “POST START CHECKLIST”.
2. Check the ground wiring for the ICB and the gas valve is
intact and making good electrical connection. Check the
ceramic insulator on the spark ignitor for breaks or
cracks. Replace the spark ignitor if damaged.
2. Check the voltage at the gas valve and at the gas valve
terminals on the ICB. Check all wiring between the ICB
and the gas valve. Check to make sure the ground con-
nections are intact.
3. With the draft motor running, check for 24 volts at the
pressure switch terminal on the ICB. If not present,
check for 24 volts on the terminal from the pressure
switch. If present, go to step 4. If 24 volts is not present,
the either pressure or rollout switch is not closed. Or the
draft motor is not sufficiently evacuating the heat
exchanger tubes or the pressure switch has failed.
Check the operation of the pressure switch. Check the
line voltage to the unit; if line voltage is low, call the local
power company. If the problem persists, the draft motor
may need replacement.
3. If 24 volts is present, remove the pilot burner and the ori-
fice. The removal procedure is described in
“BURNER/ORIFICE INSTRUCTIONS.” Inspect the ori-
fice for obstruction. If it is clear, replace the gas valve.
Main burners light but exhibit erratic flame characteristics.
4. Check the main burner orifices for obstruction and align-
ment. The removal procedure is described in
4. If the furnace is hot, it may be out on a high temperature
limit open; wait for limit reset.
“BURNER/ORIFICE INSTRUCTIONS.” Clean or replace
burner orifices and burners as needed.
5. If all are intact replace the ICB.
50
Unitary Products Group
035-19046-002-B-0104
Unitary Products Group
51
Subject to change without notice. Printed in U.S.A.
035-19046-002-B-0104
Copyright © 2004 by Unitary Products Group. All rights reserved.
Supersedes: 035-19046-002-A-0803
Unitary
Products
Group
5005
York
Drive
Norman
OK
73069
|