York Dj150 User Manual

INSTALLATION  
MANUAL  
MAGNUM  
CONTENTS  
SINGLE PACKAGE AIR CONDITIONERS AND  
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . .4  
INSPECTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4  
REFERENCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
RENEWAL PARTS . . . . . . . . . . . . . . . . . . . . . . . . . .5  
APPROVALS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . .6  
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . .8  
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33  
START-UP (COOLING). . . . . . . . . . . . . . . . . . . . . .39  
START-UP (GAS HEAT). . . . . . . . . . . . . . . . . . . . .39  
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . .43  
SINGLE PACKAGE GAS/ELECTRIC UNITS  
DJ150  
12-1/2 TON  
(10.8 EER)  
See following pages for a complete Table of Contents.  
NOTES, CAUTIONS AND WARNINGS  
The installer should pay particular attention to the words:  
NOTE, CAUTION, and WARNING. Notes are intended to  
clarify or make the installation easier. Cautions are given  
to prevent equipment damage. Warnings are given to alert  
installer that personal injury and/or equipment damage  
may result if installation procedure is not handled properly.  
Tested in accordance with:  
CAUTION: READ ALL SAFETY GUIDES BEFORE YOU  
BEGIN TO INSTALL YOUR UNIT.  
SAVE THIS MANUAL  
035-19046-002-B-0104  
035-19046-002-B-0104  
LIST OF FIGURES  
Pg. # Fig. #  
UNIT SHIPPING BRACKET . . . . . . . . . . . . . . . . . . . . . 8  
Fig. #  
Pg. #  
1
2
3
4
5
6
7
8
9
16 ELECTRONIC THERMOSTAT FIELD WIRING . . . . . 18  
17 FIELD WIRING 24 VOLT THERMOSTAT . . . . . . . . . 19  
COMPRESSOR SECTION . . . . . . . . . . . . . . . . . . . . . . 9  
PREDATOR“ MAGNUM COMPONENT LOCATION . 10  
UNIT 4 POINT LOAD . . . . . . . . . . . . . . . . . . . . . . . . . 11  
UNIT 6 POINT LOAD . . . . . . . . . . . . . . . . . . . . . . . . . 12  
UNIT CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . 12  
UNIT DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
BOTTOM DUCT OPENINGS (FROM ABOVE). . . . . . 14  
REAR DUCT DIMENSIONS . . . . . . . . . . . . . . . . . . . . 15  
18 FIELD WIRING DISCONNECT - COOLING UNIT  
WITH/WITHOUT ELECTRIC HEAT . . . . . . . . . . . . . . 19  
19 FIELD WIRING DISCONNECT - COOLING UNIT  
WITH GAS HEAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20  
20 SIDE ENTRY GAS PIPING. . . . . . . . . . . . . . . . . . . . . 23  
21 BOTTOM ENTRY GAS PIPING . . . . . . . . . . . . . . . . . 23  
22 ENTHALPY SET POINT CHART . . . . . . . . . . . . . . . . 27  
23 HONEYWELL ECONOMIZER CONTROL W7212. . . 27  
24 BELT ADJUSTMENT . . . . . . . . . . . . . . . . . . . . . . . . . 28  
25 DRY COIL DELTA P. . . . . . . . . . . . . . . . . . . . . . . . . . 32  
26 TYPICAL FLAME . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39  
27 TYPICAL GAS VALVE . . . . . . . . . . . . . . . . . . . . . . . . 42  
28 BASIC TROUBLESHOOTING FLOWCHART . . . . . . 44  
29 POWER ON FLOW CHART . . . . . . . . . . . . . . . . . . . . 44  
30 TRIP FAILURE FLOW CHART. . . . . . . . . . . . . . . . . . 45  
10 PREDATOR“ MAGNUM ROOF CURB  
DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16  
11 SUNLINE™ TO PREDATOR“ MAGNUM  
TRANSITION ROOF CURBS . . . . . . . . . . . . . . . . . . . 16  
12 SIDE PANELS WITH HOLE PLUGS. . . . . . . . . . . . . . 16  
13 RETURN DOWNFLOW PLENUM WITH PANEL . . . . 17  
14 DISCHARGE PANEL IN PLACE. . . . . . . . . . . . . . . . . 17  
15 CONDENSATE DRAIN . . . . . . . . . . . . . . . . . . . . . . . . 17  
LIST OF TABLES  
Tbl. #  
Pg. #  
Tbl. #  
Pg. #  
1
2
3
4
5
6
7
8
UNIT VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . 11  
UNIT TEMPERATURE LIMITATIONS 11  
16 DJ150, 12-1/2 TON OPTIONAL MOTOR DOWN  
SHOT BLOWER PERFORMANCE. . . . . . . . . . . . . . . 29  
17 DJ150, 12-1/2 TON STANDARD MOTOR SIDE  
SHOT BLOWER PERFORMANCE. . . . . . . . . . . . . . . 30  
UNIT WEIGHTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12  
4 POINT LOAD WEIGHT. . . . . . . . . . . . . . . . . . . . . . . 12  
6 POINT LOAD WEIGHT. . . . . . . . . . . . . . . . . . . . . . . 12  
UNIT CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
CONTROL WIRE SIZES . . . . . . . . . . . . . . . . . . . . . . . 17  
18 DJ150, 12-1/2 TON OPTIONAL MOTOR SIDE  
SHOT BLOWER PERFORMANCE. . . . . . . . . . . . . . . 30  
19 INDOOR BLOWER SPECIFICATIONS. . . . . . . . . . . . 31  
20 ADDITIONAL STATIC RESISTANCE . . . . . . . . . . . . . 33  
21 MOTOR SHEAVE DATUM DIAMETERS . . . . . . . . . . 33  
22 ELECTRIC HEAT LIMIT SETTING . . . . . . . . . . . . . . . 36  
23 ELECTRIC HEAT ANTICIPATOR SETPOINTS . . . . . 36  
24 GAS HEAT LIMIT CONTROL SETTINGS. . . . . . . . . . 38  
25 GAS HEAT ANTICIPATOR SETPOINTS . . . . . . . . . . 39  
26 GAS HEAT STAGES. . . . . . . . . . . . . . . . . . . . . . . . . . 40  
27 GAS RATE CUBIC FEET PER HOUR . . . . . . . . . . . . 41  
28 UNIT CONTROL BOARD FLASH CODES . . . . . . . . . 43  
29 IGNITION CONTROL FLASH CODES . . . . . . . . . . . . 43  
ELECTRICAL DATA DJ150 (12-1/2 TON) WITHOUT  
POWERED CONVENIENCE OUTLET . . . . . . . . . . . . 21  
9
ELECTRICAL DATA DJ150 (12-1/2 TON) WITH  
POWERED CONVENIENCE OUTLET . . . . . . . . . . . . 21  
10 PHYSICAL DATA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22  
11 MINIMUM SUPPLY AIR CFM . . . . . . . . . . . . . . . . . . . 22  
12 GAS HEAT APPLICATION DATA . . . . . . . . . . . . . . . . 23  
13 GAS PIPE SIZING - CAPACITY OF PIPE. . . . . . . . . . 23  
14 SUPPLY AIR LIMITATIONS . . . . . . . . . . . . . . . . . . . . 28  
15 DJ150, 12-1/2 TON STANDARD MOTOR DOWN  
SHOT BLOWER PERFORMANCE . . . . . . . . . . . . . . . 29  
Unitary Products Group  
3
035-19046-002-B-0104  
GENERAL  
YORK Predator Magnum units are single package air con-  
ditioners with optional gas heating designed for outdoor  
installation on a rooftop or slab and for non-residential use.  
These units can be equipped with factory or field installed  
electric heaters for heating applications.  
If the information in this manual is not followed  
exactly, a fire or explosion may result causing prop-  
erty damage, personal injury or loss of life.  
Do not store or use gasoline or other flammable  
vapors and liquids in the vicinity of this or any other  
appliance.  
These units are completely assembled on rigid, permanently  
attached base rails. All piping, refrigerant charge, and electri-  
cal wiring is factory installed and tested. The units require  
electric power, gas supply (where applicable), and duct con-  
nections. The electric heaters have nickel-chrome elements  
and utilize single-point power connection.  
WHAT TO DO IF YOU SMELL GAS:  
a. Do not try to light any appliance.  
b. Do not touch any electrical switch; do not use  
any phone in your building.  
SAFETY CONSIDERATIONS  
c. Immediately call your gas supplier from a neigh-  
bor’s phone. Follow the gas supplier’s instruc-  
tions.  
d. If you cannot reach your gas supplier, call the fire  
department.  
Should overheating occur, or the gas supply fail to  
shut off, shut off the manual gas valve to the furnace  
before shutting off the electrical supply.  
Installation and service must be performed by a  
qualified installer, service agency or the gas sup-  
plier.  
Do not use this furnace if any part has been under  
water. Immediately call a qualified service technician  
to inspect the furnace and to replace any part of the  
control system and any gas control which has been  
under water.  
INSPECTION  
As soon as a unit is received, it should be inspected for possi-  
ble damage during transit. If damage is evident, the extent of  
the damage should be noted on the carrier’s freight bill. A  
separate request for inspection by the carrier’s agent should  
be made in writing.  
Due to system pressure, moving parts, and electrical compo-  
nents, installation and servicing of air conditioning equipment  
can be hazardous. Only qualified, trained service personnel  
should install, repair, or service this equipment. Untrained  
personnel can perform basic maintenance functions of clean-  
ing coils and filters and replacing filters.  
Observe all precautions in the literature, labels, and tags  
accompanying the equipment whenever working on air condi-  
tioning equipment. Be sure to follow all other applicable  
safety precautions and codes including ANSI Z223.1 or CSA-  
B149.1- latest edition.  
This furnace is not to be used for temporary heating  
of buildings or structures under construction.  
Before performing service or maintenance opera-  
tions on unit, turn off main power switch to unit. Elec-  
trical shock could cause personal injury. Improper  
installation, adjustment, alteration, service or main-  
tenance can cause injury or property damage. Refer  
to this manual. For assistance or additional informa-  
tion consult a qualified installer, service agency or  
the gas supplier.  
Wear safety glasses and work gloves. Use quenching cloth  
and have a fire extinguisher available during brazing opera-  
tions.  
4
Unitary Products Group  
035-19046-002-B-0104  
REFERENCE  
APPROVALS  
Additional information is available in the following reference  
forms:  
Design certified by CSA as follows:  
1. For use as a cooling only unit, cooling unit with supple-  
mental electric heat or a forced air furnace.  
Technical Guide - DJ150, 036-21484-002  
General Installation - DJ150, 035-19046-002  
Pre-start & Post-start Check List - 035-18466-000  
2. For outdoor installation only.  
3. For installation on combustible material and may be  
installed directly on combustible flooring or, in the U.S.,  
on wood flooring or Class A, Class B or Class C roof cov-  
ering materials.  
Economizer Accessory -  
Downflow Factory Installed, 035-18286-000  
Downflow Field Installed, 035-18285-000  
Horizontal Field Installed, 035-18287-000  
4. For use with natural gas (convertible to LP with kit).  
Motorized Outdoor Air Damper 035-18283-000  
Manual Outdoor Air Damper (0-100%) 035-18282-000  
Manual Outdoor Air Damper (0-35%) 035-18281-000  
Gas Heat Propane Conversion Kit 035-17374-000  
Gas Heat High Altitude Kit (Natural Gas) 035-17282-000  
Gas Heat High Altitude Kit (Propane) 035-17281-000  
–60°F Gas Heat Kit 035-18216-000  
This product must be installed in strict compliance  
with the enclosed installation instructions and any  
applicable local, state, and national codes including,  
but not limited to, building, electrical, and mechanical  
codes.  
Electric Heater Accessory 035-17291-001  
Unit Renewal Parts List 035-19085-000  
All forms referenced in this instruction may be ordered from:  
Standard Register  
Toll Free Fax: (877) 379-7920  
Toll Free Phone: (877) 318-9675  
Incorrect installation may create a condition where the  
operation of the product could cause personal injury  
or property damage.  
RENEWAL PARTS  
The installer should pay particular attention to the words:  
NOTE, CAUTION, and WARNING. NOTES are intended to  
clarify or make the installation easier. CAUTIONS are given  
to prevent equipment damage. WARNINGS are given to alert  
installer that personal injury and/or equipment damage may  
result if installation procedure is not handled properly.  
Refer to York’s USER’S MAINTENANCE and SERVICE  
INFORMATION MANUAL Part Number 035-19047-001.  
Unitary Products Group  
5
035-19046-002-B-0104  
NOMENCLATURE  
12½ Ton Predator Model Number Nomenclature  
D J 150 N15 A 2 A AA 3  
Product Generation  
Product Category  
3 = Third Generation  
D = Air Cond., Single Package  
Additional Options  
Installation Options  
Product Identifier  
Voltage  
J = R-22 Ultra High Efficiency  
2 = 208/230-3-60  
4 = 460-3-60  
5 = 575-3-60  
A = No Options Installed  
B = Option 1  
C = Option 2  
(See Next Page)  
D = Options 1 & 2  
E = Option 3  
F = Option 4  
Nominal Cooling Capacity - MBH  
150 = 12-½ Ton  
G = Options 1 & 3  
H = Options 1 & 4  
J = Options 1, 2 & 3  
K = Options 1, 2 & 4  
L = Options 1, 3 & 4  
M = Options 1, 2, 3 & 4  
N = Options 2 & 3  
P = Options 2 & 4  
Q = Options 2, 3 & 4  
R = Options 3 & 4  
S = Option 5  
Heat Type & Nominal Heat Capacity  
C00 = Cooling Only. Suitable for field installed electric heat  
Gas Heat Options  
N 15 = 150 MBH Output Aluminized Steel  
N 20 = 200 MBH Output Aluminized Steel  
T = Options 1 & 5  
U = Options 1, 3 & 5  
V = Options 1, 4 & 5  
W = Options 1, 3, 4 & 5  
X = Options 3 & 5  
Y = Options 4 & 5  
Z = Options 3, 4 & 5  
S 15 = 150 MBH Output Stainless Steel  
S 20 = 200 MBH Output Stainless Steel  
Electric Heat Options  
Options  
E18 = 18 kW Electric Heat  
E24 = 24 kW Electric Heat  
E36 = 36 kW Electric Heat  
E54 = 54 kW Electric Heat  
1 = Disconnect  
2 = Non-Pwr’d Conv Outlet  
3 = Smoke Detector S. A.  
4 = Smoke Detector R. A.  
5 = Pwr’d Conv Outlet  
Airflow  
A = Standard Motor  
B = Standard Motor/Economizer/Barometric Relief (Downflow only)  
C = Standard Motor/Economizer/Power Exhaust (Downflow only)  
D = Standard Motor/Motorized Damper (Downflow only)  
E = Standard Motor/Horizontal Economizer (No Barometric Relief)  
F = Standard Motor/Slab Economizer/Power Exhaust (Downflow only)  
G = Standard Motor/Slab Economizer/Barometric Relief (Downflow only)  
L = Standard Motor/BAS Ready Econ (NoBASController)/Barometric Relief w/2" Pleated Filters (Downflow only)  
M = Standard Motor/BAS Ready Econ (NoBASController)/Power Exhaust w/2" Pleated Filters (Downflow only)  
N = High Static Motor  
P = High Static Motor/Economizer/Barometric Relief (Downflow only)  
Q = High Static Motor/Economizer/Power Exhaust (Downflow only)  
R = High Static Motor/Motorized Damper (Downflow only)  
S = High Static Motor/Horizontal Economizer (No Barometric Relief)  
T = High Static Motor/Slab Economizer/Power Exhaust (Downflow only)  
U =High Static Motor/Slab Economizer/Barometric Relief (Downflow only)  
Y = High Static Motor/BAS Ready Econ (NoBASController)/Barometric Relief w/2" Pleated Filters (Downflow only)  
Z = High Static Motor/BAS Ready Econ (NoBASController)/Power Exhaust w/2" Pleated Filters (Downflow only)  
6
Unitary Products Group  
035-19046-002-B-0104  
NOMENCLATURE, ADDITIONAL OPTIONS:  
AA None  
AC Coil Guard  
AD Dirty Filter Switch  
AG Coil Guard & Dirty Filter Switch  
CA CPC Controller with Dirty Filter Switch & Air Proving Switch  
CC CPC Controller, DFS, APS & Coil Guard  
CE CPC Controller, DFS, APS & Technicoat Cond. Coil  
CG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard  
CJ CPC Controller, DFS, APS & Technicoat Evap. Coil  
CL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard  
CN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils  
CQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard  
CV CPC Controller, DFS, APS, & 2” Pleated Filters  
HA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch  
HC Honeywell Excel 10 Controller, DFS, APS & Coil Guard  
HE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil  
HG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard  
HJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil  
HL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard  
HN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils  
HQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard  
JA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch  
JC Johnson UNT Controller, DFS, APS & Coil Guard  
JE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil  
JG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard  
JJ  
JL  
Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil  
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard  
JN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils  
JQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard  
NA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch  
NC Novar ETC-3 Controller, DFS, APS & Coil Guard  
NE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil  
NG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard  
NJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil  
NL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard  
NN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils  
NQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard  
TA Technicoat Condenser Coil  
Unitary Products Group  
7
035-19046-002-B-0104  
TC Technicoat Condenser Coil & Coil Guard  
TD Technicoat Condenser Coil & Dirty Filter Switch  
TG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch  
TJ Technicoat Evaporator Coil  
TL Technicoat Evaporator Coil & Coil Guard  
TM Technicoat Evaporator Coil & Dirty Filter Switch  
TQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch  
TS Technicoat Evaporator & Condenser Coils  
TU Technicoat Evaporator & Condenser Coils & Coil Guard  
TV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch  
TY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch  
INSTALLATION  
INSTALLATION SAFETY INFORMATION  
FIRE OR EXPLOSION HAZARD  
Read these instructions before continuing this appliance  
installation. This is an outdoor combination heating and cool-  
ing unit. The installer must assure that these instructions are  
made available to the consumer and with instructions to  
retain them for future reference.  
Failure to follow the safety warning exactly could  
result in serious injury, death or property damage.  
Never test for gas leaks with an open flame. use a  
commercially available soap solution made specifi-  
cally for the detection of leaks to check all connec-  
tions. A fire or explosion may result causing property  
damage, personal injury or loss of life.  
1. Refer to the furnace rating plate for the approved type of  
gas for this furnace.  
2. Install this furnace only in a location and position as  
specified on Page 11 of these instructions.  
PRECEDING INSTALLATION  
1. Remove the two screws holding the brackets in the front,  
rear and compressor side fork-lift slots.  
3. Never test for gas leaks with an open flame. Use com-  
mercially available soap solution made specifically for  
the detection of leaks when checking all connections, as  
specified on Pages 8, 24, 25 and 40 of these instruc-  
tions.  
4. Always install furnace to operate within the furnace's  
intended temperature-rise range with the duct system  
and within the allowable external static pressure range,  
as specified on the unit name/rating plate, specified on  
Page 42 of these instructions.  
Bracket  
Turn down  
Screws  
5. This equipment is not to be used for temporary heating  
of buildings or structures under construction.  
FIGURE 1 - UNIT SHIPPING BRACKET  
8
Unitary Products Group  
035-19046-002-B-0104  
2. Turn each bracket toward the ground and the protective  
plywood covering will drop to the ground.  
LIMITATIONS  
These units must be installed in accordance with the follow-  
ing:  
3. Remove the condenser coil external protective covering  
prior to operation.  
4. Remove the toolless doorknobs and instruction packet  
prior to installation.  
In U.S.A.:  
1. National Electrical Code, ANSI/NFPA No. 70 - Latest  
Edition  
2. National Fuel Gas Code, ANSI Z223.1 - Latest Edition  
3. Gas-Fired Central Furnace Standard, ANSI Z21.47a. -  
Latest Edition  
4. Local building codes, and  
5. Local gas utility requirements  
In Canada:  
Toolless  
Doorknobs  
1. Canadian Electrical Code, CSA C22.1  
2. Installation Codes, CSA - B149.1.  
3. Local plumbing and waste water codes, and  
4. Other applicable local codes.  
Refer to Tables 1 & 2 for unit application data.  
Installation  
Instruction  
Packet  
FIGURE 2 - COMPRESSOR SECTION  
After installation, gas fired units must be adjusted to obtain a  
temperature rise within the range specified on the unit rating  
plate.  
If components are to be added to a unit to meet local codes,  
they are to be installed at the dealer’s and/or customer’s  
expense.  
This product must be installed in strict compliance  
with the enclosed installation instructions and any  
applicable local, state and national codes including,  
but not limited to, building, electrical, and mechani-  
cal codes.  
Size of unit for proposed installation should be based on heat  
loss/heat gain calculation made according to the methods of  
Air Conditioning Contractors of America (ACCA).  
The furnace and its individual shut-off valve must be  
disconnected from the gas supply piping system  
during any pressure testing at pressures in excess  
of 1/2 PSIG.  
This furnace is not to be used for temporary heating of build-  
ings or structures under construction.  
Pressures greater than 1/2 PSIG will cause gas  
valve damage resulting in a hazardous condition. If it  
is subjected to a pressure greater than 1/2 PSIG, the  
gas valve must be replaced.  
The furnace must be isolated from the gas supply  
piping system by closing its individual manual shut-  
off valve during any pressure testing of the gas sup-  
ply piping system at test pressures equal to or less  
than 1/2 PSIG.  
Unitary Products Group  
9
035-19046-002-B-0104  
"Simplicity™" Control  
board w/screw  
Disconnect  
location  
(optional disconnect switch)  
Filter access  
(2" throw-away)  
Filter drier  
(solid core)  
connectors for T-stat  
wiring and Network  
connection  
Second model  
nameplate inside  
hinged access panel  
Condenser  
Section  
Belt-drive blower  
motor  
Dual stage cooling  
for maximum comfort  
Slide out motor  
and blower  
assembly for easy  
adjustment and  
service  
Compressor #2  
access (high-  
efficiency compressor  
w/crankcase heater)  
Power ventor  
motor  
20-gauge  
aluminized steel tubular  
heat exchanger for long  
life (stainless steel option)  
Base rails w/forklift  
slots (three sides)  
and lifting holes  
Roof curbs in eight and  
fourteen-inch heights.  
Roof curbs for  
Two-stage gas heating to  
maintain warm,  
comfortable temperature  
Slide-out drain pan  
with brass 3/4" FPT  
connection  
transitioning from York  
Sunline™ footprint to  
the DM/DH/DJ/DR Series  
footprint are available  
(field-installed accessory)  
Compressor #1 access  
(high-efficiency  
compressor w/  
Tool-less door  
latch  
Intelligent control  
board for safe and  
efficient operation  
Side entry power  
and control wiring  
knockouts  
crankcase heater)  
FIGURE 3 - PREDATORMAGNUM COMPONENT LOCATION  
10  
Unitary Products Group  
035-19046-002-B-0104  
RIGGING AND HANDLING  
TABLE 1: UNIT VOLTAGE LIMITATIONS  
Power Rating*  
Exercise care when moving the unit. Do not remove any  
packaging until the unit is near the place of installation. Rig  
the unit by attaching chain or cable slings to the lifting holes  
provided in the base rails. Spreader bars, whose length  
exceeds the largest dimension across the unit, MUST be  
used across the top of the unit.  
Minimum  
Maximum  
208/230-3-60  
460-3-60  
187  
432  
540  
252  
504  
630  
575-3-60  
*.  
Utilization range “A” in accordance with ARI Standard 110.  
TABLE 2: UNIT TEMPERATURE LIMITATIONS  
Temperature  
Min.  
Max.  
If a unit is to be installed on a roof curb other than a  
YORK roof curb, gasketing must be applied to all  
surfaces that come in contact with the unit under-  
side.  
Wet Bulb Temperature (°F) of Air on  
57  
72  
Evaporator Coil  
Dry Bulb Temperature (°F) of Air on  
0*  
125  
Condenser Coil  
*.  
A low ambient accessory is available for operation  
down to -20°F.  
LOCATION  
Before lifting, make sure the unit weight is distrib-  
uted equally on the rigging cables so it will lift evenly.  
Use the following guidelines to select a suitable location for  
these units:  
1. Unit is designed for outdoor installation only.  
Units may be moved or lifted with a forklift. Slotted openings  
in the base rails are provided for this purpose.  
2. Condenser coils must have an unlimited supply of air.  
Where a choice of location is possible, position the unit  
on either north or east side of building.  
LENGTH OF FORKS MUST BE A MINIMUM OF 60  
INCHES.  
3. Suitable for mounting on roof curb.  
4. For ground level installation, use a level concrete slab  
with a minimum thickness of 4 inches. The length and  
width should be at least 6 inches greater than the unit  
base rails. Do not tie slab to the building foundation.  
All panels must be secured in place when the unit is  
lifted.  
5. Roof structures must be able to support the weight of the  
unit and its options/accessories. Unit must be installed  
on a solid, level roof curb or appropriate angle iron  
frame.  
The condenser coils should be protected from rig-  
ging cable damage with plywood or other suitable  
material.  
6. Maintain level tolerance to 1/2” across the entire width  
and length of unit.  
Excessive exposure of this furnace to contaminated  
combustion air may result in equipment damage or  
personal injury. Typical contaminates include: per-  
manent wave solution, chlorinated waxes and clean-  
ers, chlorine based swimming pool chemicals, water  
softening chemicals, carbon tetrachloride, Halogen  
type refrigerants, cleaning solvents (e.g. perchloro-  
ethylene), printing inks, paint removers, varnishes,  
hydrochloric acid, cements and glues, antistatic fab-  
ric softeners for clothes dryers, masonry acid wash-  
ing materials.  
FRONT  
LEFT  
C
B
A
D
FIGURE 4 - UNIT 4 POINT LOAD  
Unitary Products Group  
11  
035-19046-002-B-0104  
CLEARANCES  
TABLE 3: UNIT WEIGHTS  
Operating  
Weight (lb.)  
1400  
All units require particular clearances for proper operation  
and service. Installer must make provisions for adequate  
combustion and ventilation air in accordance with section 5.3  
of Air for Combustion and Ventilation of the National Fuel Gas  
Code, ANSI Z223.1 – Latest Edition (in U.S.A.), or Sections  
7.2, 7.3, or 7.4 of Gas Installation Codes, CSA-B149.1 (in  
Canada) - Latest Edition, and/or applicable provisions of the  
local building codes. Refer to Table 6 for clearances required  
for combustible construction, servicing, and proper unit oper-  
ation.  
Shipping  
Weight (lb.)  
Model DJ150  
Cooling Unit Only  
w/Economizer  
1415  
85  
84  
150  
148  
w/Power Exhaust  
w/Gas Heat*  
110  
49  
110  
49  
w/Electric Heat†  
*.  
†.  
8 Tube Heat Exchanger  
54 kW heater  
TABLE 4: 4 POINT LOAD WEIGHT  
Location (lbs.)*  
Model  
DJ150  
A
B
C
D
282  
323  
424  
371  
Do not permit overhanging structures or shrubs to  
obstruct condenser air discharge outlet, combustion  
air inlet or vent outlets.  
*.  
Weights include largest gas heat option.  
TABLE 5: 6 POINT LOAD WEIGHT  
Location (lbs.)*  
Model  
DJ150  
A
B
C
D
E
F
184  
201  
220  
289  
264  
242  
*.  
Excessive exposure to contaminated combustion air  
will result in safety and performance related prob-  
lems. To maintain combustion air quality, the recom-  
mended source of combustion air is the outdoor air  
supply. The outdoor air supplied for combustion  
should be free from contaminants due to chemical  
exposure that may be present from the following  
sources.  
Weights include largest gas heat option.  
Commercial buildings  
Indoor pools  
Laundry rooms  
Hobby or craft rooms  
Chemical storage areas  
FRONT  
LEFT  
C
D
The following substances should be avoided to  
maintain outdoor combustion air quality.  
E
B
A
F
Permanent wave solutions  
Chlorinated waxes and cleaners  
Chlorine based swimming pool cleaners  
Water softening chemicals  
De-icing salts or chemicals  
Carbon tetrachloride  
FIGURE 5 - UNIT 6 POINT LOAD  
Halogen type refrigerants  
Cleaning solvents (such as perchloroethylene)  
Printing inks, paint removers, varnishes, etc.  
Hydrochloric acid  
Cements and glues  
Anti-static fabric softeners for clothes dryers  
Masonry acid washing materials  
25-½"  
47-½"  
FRONT  
LEFT  
FIGURE 6 - UNIT CENTER OF GRAVITY  
12  
Unitary Products Group  
035-19046-002-B-0104  
119-7/16  
30-11/32  
See Detail A  
Power  
Entry  
2-1/2  
50-3/4  
Con-  
venience  
Outlet  
Control  
Entry 7/8  
4-1/4  
11-1/2  
Con-  
venience  
Outlet  
Power  
Entry  
FRONT  
7/8  
For  
Baserail  
Dimensions  
See  
17-3/16  
For Drain Dimensions  
See Detail C  
30-3/16  
59  
LEFT  
24-3/16  
6-3/16  
Detail B  
89  
27  
FIGURE 7 - UNIT DIMENSIONS  
DETAIL A  
2
-
3
/
8
DETAIL B  
G
a
s
P
i
p
e
I
n
l
e
t
3
-
3
/
4
5
-
1
/
4
B
P
a
a
s
n
e
1
7
-
1
3
/
1
6
3
-
9
/
1
6
V
i
e
w
o
f
W
a
l
l
A
c
r
o
s
s
f
r
o
m
C
o
i
l
DETAIL C  
TABLE 6: UNIT CLEARANCES  
Top*  
Front†  
Rear‡  
72”  
36”  
36”  
12”  
36”  
0”  
Right  
Left  
5
-
3
/
8
Bottom**  
*.  
Units must be installed outdoors. Overhanging struc-  
ture or shrubs should not obstruct condenser air dis-  
charge outlet.  
NOTE: If the unit includes gas heating, locate the unit so  
†.  
‡.  
The products of combustion must not be allowed to  
accumulate within a confined space and re-circulate.  
the flue exhaust is at least:  
To remove the slide-out drain pan, a rear clearance of  
sixty inches is required. If space is unavailable, the  
drain pan can be removed through the front by separat-  
ing the corner wall.  
Three (3) feet above any forced air inlet located within 10  
horizontal feet (excluding those integral to the unit).  
**.  
Four (4) feet below, four (4) horizontal feet from, or one  
(1) foot above any door or gravity air inlet into the build-  
ing.  
Units may be installed on combustible floors made from  
wood or class A, B or C roof covering materials.  
NOTE: A one-inch clearance must be provided between  
any combustible material and the supply ductwork  
for a distance of 3 feet from the unit.  
Four (4) feet from electric meters, gas meters, regula-  
tors, and relief equipment.  
Unitary Products Group  
13  
035-19046-002-B-0104  
.
32-11/16  
6-13/16  
6-13/16  
Supply  
Air  
6-13/16  
Return  
Air  
24  
27-1/2  
LEFT  
21  
18  
21-3/16  
19-3/16  
17-3/16  
12-15/16  
7-1/8  
FRONT  
14-  
23/32  
Bottom  
Bottom Gas  
Supply Entry  
Bottom  
Power, Control  
and  
Condensate  
Entry  
16-3/8  
18-1/16  
19-5/8  
Convenience  
Outlet Wiring  
Entries  
63-1/2  
FIGURE 8 - BOTTOM DUCT OPENINGS (FROM ABOVE)  
14  
Unitary Products Group  
035-19046-002-B-0104  
18-1/4  
Dot Plugs  
28-1/4  
Return  
Air  
Supply  
Air  
18-1/4  
18-1/16  
2-31/32  
5-5/32  
28-1/4  
31-11/16  
FIGURE 9 - REAR DUCT DIMENSIONS  
DUCTWORK  
DUCT COVERS  
Units are shipped with the side duct openings covered and a  
covering over the bottom of the unit. For bottom duct applica-  
tion, no duct cover changes are necessary. For side duct  
application, remove the side duct covers and install over the  
bottom duct openings. The panels removed from the side  
duct connections are designed to be reused by securing each  
panel to its respective downflow opening. But keep in mind  
that the supply panel is installed with the painted surface UP,  
facing the heat exchanger, while the return panel is installed  
with the painted surface DOWN, facing the downflow duct  
opening. The supply panel is secured with the bracket  
(already in place from the factory) and two screws. It’s a snug  
fit for the panel when sliding it between the heat exchanger  
and unit bottom, but there is room. The return panel is  
secured with four screws.  
Ductwork should be designed and sized according to the  
methods in Manual D of the Air Conditioning Contractors of  
America (ACCA) or as recommended by any other recog-  
nized authority such as ASHRAE or SMACNA.  
A closed return duct system should be used. This will not  
preclude use of economizers or outdoor fresh air intake. The  
supply and return air duct connections at the unit should be  
made with flexible joints to minimize noise.  
The supply and return air duct systems should be designed  
for the CFM and static pressure requirements of the job. They  
should NOT be sized to match the dimensions of the duct  
connections on the unit.  
Refer to Figure 8 for bottom air duct openings. Refer to Fig-  
ure 9 for rear air duct openings.  
Unitary Products Group  
15  
035-19046-002-B-0104  
R
I
G
H
T
8
0
-
5
/
8
I
N
S
U
L
A
T
E
D
D
E
C
K
U
N
D
E
R
C
O
N
D
E
N
S
E
R
S
E
C
T
I
O
N
2
0
S
U
P
P
L
Y
2
0
6
R
E
T
U
R
N
2
T
Y
P
.
3
0
I
N
S
O
U
L
A
T
E
D
D
E
C
K
U
N
D
E
R
5
0
-
1
/
2
C
M
P
R
E
S
S
O
R
S
E
C
T
I
O
N
1
R
O
N
T
8
o
r
1
4
FIGURE 10 - PREDATORMAGNUM ROOF CURB DIMENSIONS  
2
T
Y
P
2
3
4
3
0
-
1
/
2
5
0
-
1
/
2
8
0
-
5
/
8
2
6
R
E
T
U
R
N
S
U
P
P
L
Y
1
0
7
6
-
5
/
8
5
9
-
1
/
4
9
4
1
R
O
N
T
R
I
G
H
T
6
4
-
1
/
4
FIGURE 11 - SUNLINE™ TO PREDATORMAGNUM TRANSITION ROOF CURBS  
When fastening ductwork to side duct flanges on  
unit, insert screws through duct flanges only. DO  
NOT insert screws through casing. Outdoor duct-  
work must be insulated and water-proofed.  
FIGURE 12 - SIDE PANELS WITH HOLE PLUGS  
Note orientation. Panel is “insulation” side up.  
16  
Unitary Products Group  
035-19046-002-B-0104  
COMPRESSORS  
The compressors are mounted on elastomer insulators. The  
mounting bolts have been fully tightened for shipping.  
Do not loosen the compressor mounting bolts.  
FILTERS  
Two-inch filters are supplied with each unit. One-inch filters  
may be used with no modification to the filter racks. Filters  
must always be installed ahead of evaporator coil and must  
be kept clean or replaced with same size and type. Dirty fil-  
ters reduce the capacity of the unit and result in frosted coils  
or safety shutdown. All units use four (4) 20”x25”x2” filters.  
The unit should not be operated without filters properly  
installed.  
FIGURE 13 - RETURN DOWNFLOW PLENUM WITH  
PANEL  
Make sure that panel latches are properly positioned  
on the unit to maintain an airtight seal.  
THERMOSTAT WIRING  
FIGURE 14 - DISCHARGE PANEL IN PLACE  
CONDENSATE DRAIN  
The thermostat should be located on an inside wall approxi-  
mately 56 inch above the floor where it will not be subject to  
drafts, sun exposure or heat from electrical fixtures or appli-  
ances. Follow the manufacturer's instructions enclosed with  
thermostat for general installation procedure. Seven (7) color-  
coded, insulated wires should be used to connect the thermo-  
stat to the unit. Refer to Table 7 for control wire sizing and  
maximum length.  
The side condensate drain is reversible and maybe re-ori-  
ented to the rear of the cabinet to facilitate condensate pip-  
ing. A condensate drain connection is available through the  
base pan for piping inside the roof curb. Trap the connection  
per Figure 15. The trap and drain lines should be protected  
from freezing.  
TABLE 7: CONTROL WIRE SIZES  
Plumbing must conform to local codes. Use a sealing com-  
pound on male pipe threads. Install condensate drain line  
from the 3/4 inch NPT female connection on the unit to an  
open drain.  
Maximum Length*  
Wire Size  
18 AWG  
150 Feet  
*.  
From the unit to the thermostat and back to the unit.  
POWER AND CONTROL WIRING  
O
P
T
I
O
N
A
L
C
O
I
L
G
U
A
R
D
Field wiring to the unit, fuses, and disconnects must conform  
to provisions of National Electrical Code (NEC), ANSI/NFPA  
No. 70 – Latest Edition (in U.S.A.), current Canadian Electri-  
cal Code C221, and/or local ordinances. The unit must be  
electrically grounded in accordance with NEC and CEC as  
specified above and/or local codes.  
3
"
M
i
n
i
m
u
m
Voltage tolerances which must be maintained at the com-  
pressor terminals during starting and running conditions are  
indicated on the unit Rating Plate and Table 1.  
FIGURE 15 - CONDENSATE DRAIN  
Unitary Products Group  
17  
035-19046-002-B-0104  
The internal wiring harnesses furnished with this unit are an  
integral part of the design certified unit. Field alteration to  
comply with electrical codes should not be required. If any of  
the wire supplied with the unit must be replaced, replacement  
wire must be of the type shown on the wiring diagram and the  
same minimum gauge as the replaced wire.  
Refer to Figures 16, 17 and 18 for typical field wiring and to  
the appropriate unit wiring diagram mounted inside control  
doors for control circuit and power wiring information.  
A disconnect must be utilized for these units. Factory  
installed disconnects are available. If installing a disconnect  
When connecting electrical power and control wiring  
to the unit, water-proof connectors must be used so  
that water or moisture cannot be drawn into the unit  
during normal operation. The above water-proofing  
conditions will also apply when installing a field sup-  
plied disconnect switch.  
(field supplied or York International supplied accessory),  
refer to Figure 3 for the recommended mounting location.  
Avoid damage to internal components if drilling  
holes for disconnect mounting.  
POWER WIRING DETAIL  
Units are factory wired for the voltage shown on the unit  
nameplate. Refer to Electrical Data Tables 8 and 9 to size  
power wiring, fuses, and disconnect switch.  
NOTE: Since not all local codes allow the mounting of a dis-  
connect on the unit, please confirm compliance with  
local code before mounting a disconnect on the unit.  
Power wiring is brought into the unit through the side of the  
unit or the basepan inside the curb.  
Electrical line must be sized properly to carry the load. USE  
COPPER CONDUCTORS ONLY. Each unit must be wired  
with a separate branch circuit fed directly from the meter  
panel and properly fused.  
1
T
H
E
R
M
O
S
T
A
T
T
E
R
M
I
N
A
L
S
U
N
I
T
T
E
R
M
I
N
A
L
S
S
T
R
I
P
T
B
1
R
C
R
H
R
Y
1
Y
1
Y
2
Y
2
W
1
W
1
W
2
W
2
G
G
C
C
2
T
4
V
o
s
l
t
o
r
a
n
f
r
m
e
r
X
1
X
2
X
3
O
C
C
X
4
A
A
1
2
T
T
T
O
R
E
M
O
T
E
S
E
N
S
O
R
2
E
T
0
4
7
0
1
3
2
4
I
1
U
S
E
D
1
E
l
e
c
t
r
o
n
i
c
p
r
o
g
r
a
m
m
a
b
l
e
T
h
e
r
m
o
s
t
a
t
2
E
T
0
7
7
0
0
1
0
0
2
4
o
(
i
n
c
l
u
d
e
s
s
u
b
b
a
s
e
)
.
T
e
r
m
i
n
a
l
s
A
1
a
n
d
A
2
p
r
o
v
i
d
e
a
r
e
l
a
y
o
u
t
p
u
t
t
o
c
l
o
s
e
t
h
e
o
u
t
d
o
o
r
e
c
o
n
o
m
i
z
e
r
d
a
m
p
e
r
s
w
h
e
n
t
h
e
t
h
e
r
m
o
s
t
a
t
s
w
i
t
c
h
e
s
t
t
h
e
s
e
t
-
b
a
c
k
p
o
s
i
t
i
o
n
.
FIGURE 16 - ELECTRONIC THERMOSTAT FIELD WIRING  
18  
Unitary Products Group  
035-19046-002-B-0104  
T
-
S
T
A
T
W
1
W
1
W
2
W
2
Y
Y
1
2
Y
Y
1
2
G
G
O
C
C
U
N
I
T
C
O
N
T
R
O
L
C
B
O
A
R
D
R
H
R
C
X
R
S
D
C
FIGURE 17 - FIELD WIRING 24 VOLT THERMOSTAT  
TERMINAL BLOCK TB1  
FACTORY OR FIELD  
SUPPLIED DISCONNECT  
GROUND  
LUG  
THREE  
PHASE  
POWER  
SUPPLY  
FIGURE 18 - FIELD WIRING DISCONNECT - COOLING UNIT WITH/WITHOUT ELECTRIC HEAT  
Unitary Products Group  
19  
035-19046-002-B-0104  
CONTACTOR 1M  
T1  
T2  
L2  
T3  
L3  
L1  
FACTORY OR FIELD  
SUPPLIED DISCONNECT  
GROUND  
LUG  
THREE  
PHASE  
POWER  
SUPPLY  
FIGURE 19 - FIELD WIRING DISCONNECT - COOLING UNIT WITH GAS HEAT  
20  
Unitary Products Group  
035-19046-002-B-0104  
TABLE 8: ELECTRICAL DATA DJ150 (12-1/2 TON) WITHOUT POWERED CONVENIENCE OUTLET  
MCA  
Max  
Fuse*  
Size  
Max Fuse* Size  
w/Power  
Supply  
Blower  
Pwr  
Pwr  
Min. Circuit  
Ampacity  
(Amps)  
OD Fan  
Motors  
w/Power  
Exhaust  
(Amps)  
Compressors  
Exh Conv  
Electric Heater Actual Heater  
Exhaust  
Voltage  
Motor FLA Motor Outlet  
Model No.  
KW  
Amps  
(Amps)  
(Amps)  
RLA  
ea.  
LRA  
ea.  
FLA  
ea.  
3
5
3
5
3
5
3
5
3
5
FLA  
FLA  
HP  
HP  
HP  
HP  
HP  
HP  
HP HP  
HP  
80  
HP  
90  
None  
--  
13.5  
18.0  
25.5  
40.6  
--  
--  
61.9  
61.9  
76.1  
67.1 67.4 72.6 80 80  
67.1 67.4 73.8 80 80  
82.6 83.0 89.5 80 90  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
37.5  
50.0  
80  
90  
208  
230  
460  
20.0 146.0  
1.5  
1.5  
0.8  
0.6  
10.9 16.1  
5.5  
0.0  
90  
90  
70.8 102.1 108.6 109.0 115.5 110 110  
112.7 154.5 161.0 161.4 167.9 175 175  
110  
175  
80  
125  
175  
90  
--  
61.9  
67.8  
85.8  
67.1 67.4 72.6 80 80  
74.3 74.6 81.1 80 80  
92.3 92.7 99.2 90 100  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
18.0  
24.0  
34.0  
54.0  
--  
43.3  
57.7  
80  
90  
20.0 146.0  
10.9 16.1  
5.5  
2.2  
1.8  
0.0  
0.0  
0.0  
100  
125  
175  
35  
100  
150  
175  
40  
81.8 115.9 122.4 122.7 129.2 125 125  
129.9 143.5 150.0 150.4 156.9 175 175  
--  
27.4  
33.7  
42.7  
57.7  
71.6  
21.6  
26.8  
34  
30.2 29.6 32.4 35 35  
37.2 36.4 39.9 35 40  
2TP04521846  
2TP04522446  
2TP04523646  
2TP04525446  
None  
18  
22.6  
30.1  
42.7  
67.8  
--  
40  
40  
8.4  
6.7  
73.0  
60.0  
5.3  
4.1  
8.1  
6.0  
24  
46.2 45.5  
61.2 60.5  
49  
64  
45 50  
60 70  
50  
50  
34  
70  
70  
54  
75.1 74.3 77.8 80 90  
23.5 23.4 25.3 25 30  
80  
90  
--  
30  
30  
2TP04521858  
2TP04522458  
2TP04523658  
2TP04525458  
18  
18.1  
24.1  
34.1  
54.2  
29.2  
29  
31.4 30 30  
30  
35  
575  
24  
36.4 36.2 38.6 35 40  
48.4 48.3 50.6 50 50  
59.5 59.3 61.7 70 70  
40  
40  
34  
54  
46  
57.1  
50  
70  
60  
70  
*
Maximum HACR breaker of the same AMP size is applicable.  
TABLE 9: ELECTRICAL DATA DJ150 (12-1/2 TON) WITH POWERED CONVENIENCE OUTLET  
MCA  
Max  
Fuse*  
Size  
Max Fuse* Size  
w/Power  
Supply  
Blower  
Pwr  
Pwr  
Min. Circuit  
Ampacity  
(Amps)  
OD Fan  
Motors  
w/Power  
Exhaust  
(Amps)  
Compressors  
Exh Conv  
Electric Heater Actual Heater  
Exhaust  
Voltage  
Motor FLA Motor Outlet  
Model No.  
KW  
Amps  
(Amps)  
(Amps)  
RLA  
ea.  
LRA  
ea.  
FLA  
ea.  
3
5
3
5
3
5
3
5
3
5
FLA  
FLA  
HP  
HP  
HP  
HP  
HP  
HP  
HP HP  
HP  
90  
HP  
100  
100  
110  
150  
200  
100  
100  
125  
150  
175  
45  
None  
--  
13.5  
18.0  
25.5  
40.6  
--  
--  
71.9  
73.0  
88.6  
77.1 77.4 82.6 90 90  
79.5 79.8 86.3 90 90  
95.1 95.5 102.0 90 100  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
37.5  
50.0  
90  
208  
230  
460  
20.0 146.0  
1.5  
1.5  
0.8  
0.6  
10.9 16.1  
5.5  
10.0  
100  
125  
175  
90  
70.8 114.6 121.1 121.5 128.0 125 125  
112.7 167.0 173.5 173.9 180.4 175 175  
--  
71.9  
80.3  
77.1 77.4 82.6 90 90  
86.8 87.1 93.6 90 90  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
18.0  
24.0  
34.0  
54.0  
--  
43.3  
57.7  
90  
20.0 146.0  
10.9 16.1  
5.5  
2.2  
1.8  
10.0  
5.0  
98.3 104.8 105.2 111.7 100 110  
110  
150  
175  
40  
81.8 128.4 134.9 135.2 141.7 150 150  
129.9 156.0 162.5 162.9 169.4 175 175  
--  
32.4  
39.9  
49  
35.2 34.6 37.4 40 40  
43.4 42.7 46.2 40 45  
52.5 51.7 55.2 50 60  
67.5 66.7 70.2 70 70  
81.3 80.6 84.1 90 90  
27.5 27.4 29.3 30 30  
2TP04521846  
2TP04522446  
2TP04523646  
2TP04525446  
None  
18  
22.6  
30.1  
42.7  
67.8  
--  
45  
50  
8.4  
6.7  
73.0  
60.0  
5.3  
4.1  
8.1  
6.0  
24  
60  
60  
34  
64  
70  
80  
54  
77.8  
25.6  
31.8  
39  
90  
90  
--  
30  
35  
2TP04521858  
2TP04522458  
2TP04523658  
2TP04525458  
18  
18.1  
24.1  
34.1  
54.2  
34.2  
34  
36.4 35 35  
35  
40  
575  
4.0  
24  
41.4 41.2 43.6 40 45  
53.4 53.3 55.6 60 60  
64.5 64.3 66.7 70 70  
45  
45  
34  
54  
51  
62.1  
60  
70  
60  
70  
*
Maximum HACR breaker of the same AMP size is applicable.  
Unitary Products Group  
21  
035-19046-002-B-0104  
TABLE 10: PHYSICAL DATA  
Model  
DJ150  
Component  
Blower, Centrifugal (Dia. X Wd. in.)  
15 x 15  
Evaporator  
Blower  
Motor, Standard (HP)  
Motor, Optional (HP)  
Rows  
3
5
4
Fins per Inch  
Height (in.)  
15  
40  
Evaporator  
Coil  
2
13.2  
Face Area (ft. each)  
Propeller Dia. (in., each)  
Motor (HP, each)  
CFM, Nominal (each)  
Rows (each)  
24  
1/3  
3000  
2
Condenser  
Fan  
(4 per Unit)  
Condenser  
Coil  
(2 per unit)  
Fins per Inch  
20  
Height (in. each)  
44  
2
14.5  
Face Area (ft. each)  
System 1 (lb./oz.)  
System 2 (lb./oz.)  
Quantity  
11/0  
11/8  
2
Refrigerant  
Charge  
Compressors  
Air Filters  
Type  
Scroll  
25x20x2  
4
Size (Wd. x Ht. x Thickness in.)  
Number Per Unit  
OPTIONAL ELECTRIC HEAT  
TABLE 11: MINIMUM SUPPLY AIR CFM  
Heater  
kW  
Unit Model Size, Nominal Tons  
The factory-installed heaters are wired for single point power  
supply. Power supply need only be brought into the single  
point terminal block.  
12.5  
Voltage  
Minimum Supply Air CFM  
18  
24  
36  
54  
18  
24  
36  
54  
18  
24  
36  
54  
These CSA approved heaters are located within the central  
compartment of the unit with the heater elements extending  
into the supply air chamber.  
208/230  
3750  
3750  
3750  
Fuses are supplied, where required, by the factory. Some kW  
sizes require fuses and other do not. Refer to Table 11 for  
minimum CFM limitations and to Tables 8 through 9 for elec-  
trical data.  
480  
600  
22  
Unitary Products Group  
035-19046-002-B-0104  
OPTIONAL GAS HEAT  
These gas-fired heaters have aluminized-steel or optional  
stainless steel, tubular heat exchangers with spark ignition.  
OPTIONAL  
COIL  
GUARD  
SHOWN  
TABLE 12: GAS HEAT APPLICATION DATA  
Unit  
Temp Rise  
Input (MBH) Output (MBH)  
(°F)  
Size  
150  
Opt.  
15  
180  
240  
144  
192  
10-40  
20-50  
20  
GAS PIPING  
Proper sizing of gas piping depends on the cubic feet per  
hour of gas flow required, specific gravity of the gas and the  
length of run. "National Fuel Gas Code" Z223.1 (in U.S.A.) or  
the current Gas Installation Codes CSA-B149.1 (in Canada)  
should be followed in all cases unless superseded by local  
codes or gas utility requirements. Refer to the Pipe Sizing  
Table 13. The heating value of the gas may differ with locality.  
The value should be checked with the local gas utility.  
NOTE: There may be a local gas utility requirement specify-  
ing a minimum diameter for gas piping. All units  
require a one-inch pipe connection at the entrance  
fitting.  
FIGURE 21 - BOTTOM ENTRY GAS PIPING  
TABLE 13: GAS PIPE SIZING - CAPACITY OF PIPE  
Nominal Iron Pipe Size  
Length of  
Pipe (ft.)  
3/4 in.  
278  
190  
152  
130  
115  
105  
96  
1 in.  
520  
350  
285  
245  
215  
195  
180  
170  
160  
150  
1-1/4 in.  
1050  
730  
10  
20  
30  
40  
50  
60  
70  
80  
90  
100  
590  
O
C
G
S
P
T
I
O
N
N
A
L
O
I
A
L
500  
U
R
W
D
440  
H
O
400  
370  
90  
350  
84  
320  
79  
305  
NOTE: Maximum capacity of pipe in cubic feet of gas per  
hour based upon a pressure drop of 0.3 inch W.C.  
and 0.6 specific gravity gas.  
FIGURE 20 - SIDE ENTRY GAS PIPING  
NOTE: There may be a local gas utility requirement specify-  
ing a minimum diameter for gas piping. All units  
require a 3/4 inch pipe connection at the entrance  
fitting. Line should not be sized smaller than the  
entrance fitting size.  
Unitary Products Group  
23  
035-19046-002-B-0104  
GAS CONNECTION  
The gas supply line can be routed within the space and roof  
curb, exiting through the unit’s basepan. Refer to Figure 8 for  
the gas piping inlet location. Typical supply piping arrange-  
ments are shown in Figures 20 and 21. All pipe nipples, fit-  
tings, and the gas cock are field supplied or may be  
purchased in UPG accessory kit #1GP0404.  
FIRE OR EXPLOSION HAZARD  
Failure to follow the safety warning exactly could  
result in serious injury, death or property damage.  
Never test for gas leaks with an open flame. use a  
commercially available soap solution made specifi-  
cally for the detection of leaks to check all connec-  
tions. A fire or explosion may result causing property  
damage, personal injury or loss of life.  
Gas piping recommendations:  
1. A drip leg and a ground joint union must be installed in  
the gas piping.  
2. Where required by local codes, a manual shut-off valve  
must be installed outside of the unit.  
3. Use wrought iron or steel pipe for all gas lines. Pipe dope  
should be applied sparingly to male threads only.  
The furnace and its individual shut-off valve must be  
disconnected from the gas supply piping system  
during any pressure testing at pressures in excess  
of 1/2 PSIG.  
Natural gas may contain some propane. Propane is  
an excellent solvent and will quickly dissolve white  
lead and most standard commercial compounds. A  
special pipe dope must be used when assembling  
wrought iron or steel pipe. Shellac based com-  
pounds such as Gaskolac or Stalastic, and com-  
pounds such as Rectorseal #5, Clydes’s or John  
Crane may be used.  
Pressures greater than 1/2 PSIG will cause gas  
valve damage resulting in a hazardous condition. If it  
is subjected to a pressure greater than 1/2 PSIG, the  
gas valve must be replaced.  
The furnace must be isolated from the gas supply  
piping system by closing its individual manual shut-  
off valve during any pressure testing of the gas sup-  
ply piping system at test pressures equal to or less  
than 1/2 PSIG.  
4. All piping should be cleaned of dirt and scale by ham-  
mering on the outside of the pipe and blowing out loose  
particles. Before initial start-up, be sure that all gas lines  
external to the unit have been purged of air.  
LP UNITS, TANKS AND PIPING  
All gas heat units are shipped from the factory equipped for  
natural gas use only. The unit may be converted in the field  
for use with LP gas with accessory kit model number  
1NP0441.  
5. The gas supply should be a separate line and installed in  
accordance with all safety codes as prescribed under  
“Limitations”.  
All LP gas equipment must conform to the safety standards of  
the National Fire Protection Association.  
6. A 1/8-inch NPT plugged tapping, accessible for test gage  
connection, must be installed immediately upstream of  
the gas supply connection to the unit.  
For satisfactory operation, LP gas pressure must be 10.5  
inch W.C. at the unit under full load. Maintaining proper gas  
pressure depends on three main factors:  
7. After the gas connections have been completed, open  
the main shut-off valve admitting normal gas pressure to  
the mains. Check all joints for leaks with soap solution or  
other material suitable for the purpose. NEVER USE A  
FLAME.  
1. The vaporization rate which depends on the temperature  
of the liquid and the “wetted surface” area of the con-  
tainer(s).  
24  
Unitary Products Group  
035-19046-002-B-0104  
2. The proper pressure regulation. (Two-stage regulation is  
recommended).  
MOTORIZED OUTDOOR DAMPER  
The Motorized Outdoor Damper can be a factory installed  
option or a field installed accessory. If factory installed, refer  
to the instructions included with the outdoor air hood to com-  
plete the assembly. Field installed Motorized Outdoor Damp-  
ers accessories include complete instructions for installation.  
3. The pressure drop in the lines between regulators and  
between the second stage regulator and the appliance.  
Pipe size required will depend on the length of the pipe  
run and the total load of all appliances.  
Complete information regarding tank sizing for vaporization,  
recommended regulator settings, and pipe sizing is available  
from most regulator manufacturers and LP gas suppliers.  
ECONOMIZER  
The Economizer can be a factory installed option or a field  
installed accessory. If factory installed, refer to the instruc-  
tions included with the outdoor air hood to complete the  
assembly. Field installed Economizer accessories include  
complete instructions for installation.  
LP gas is an excellent solvent and will quickly dissolve white  
lead and most standard commercial compounds. A special  
pipe dope must be used when assembling wrought iron or  
steel pipe for LP. Shellac base compounds such as Gaskolac  
or Stalastic, and compounds such as Rectorseal #5, Clyde’s,  
or John Crane may be used.  
There are two Economizer options:  
1. Down Flow application with barometric relief hood stan-  
dard.  
Check all connections for leaks when piping is completed  
using a soap solution. NEVER USE A FLAME.  
2. Horizontal Flow application that requires the purchase of  
a barometric relief hood.  
POWER EXHAUST  
The Power Exhaust can be a factory installed option or a field  
installed accessory. If factory installed, refer to the instruc-  
tions included with the outdoor air hood to complete the  
assembly. Field installed Power Exhaust accessories include  
complete instructions for installation.  
FIRE OR EXPLOSION HAZARD  
Failure to follow the safety warning exactly could  
result in serious injury, death or property damage.  
Never test for gas leaks with an open flame. use a  
commercially available soap solution made specifi-  
cally for the detection of leaks to check all connec-  
tions. A fire or explosion may result causing property  
damage, personal injury or loss of life.  
The Power Exhaust factory installed option is for Down Flow  
application only.  
There are two field installed Power Exhaust accessories:  
1. Down Flow application.  
VENT AND COMBUSTION AIR  
2. Horizontal Flow application that requires the purchase of  
a barometric relief hood.  
Venting slots in the heating compartment access panel  
remove the need for a combustion air hood. The gas heat  
flue exhaust is routed through factory installed exhaust piping  
with screen. If necessary, a flue exhaust extension may be  
installed at the point of installation.  
RAIN HOOD  
The following procedure should be used when assembling a  
rain hood onto a unit.  
FACTORY INSTALLED OPTIONS/  
FIELD INSTALLED ACCESSORIES  
All of the hood components, including the filters, the gasket-  
ing and the hardware for assembling, are packaged and  
located between the condenser coil section and the main unit  
cabinet, if the unit has factory installed options. If field  
installed accessories are being installed all parts necessary  
for the installation comes in the accessory.  
ELECTRIC HEAT  
Electric heaters are available as field installed accessories.  
Refer to electric heat instructions for installation. These heat-  
ers mount in the heat compartment with the heating elements  
extending into the supply air chamber. All electric heaters are  
fused and intended for use with single point power supply.  
1. Remove the hood components, filters, gasketing and the  
hardware from the box.  
2. Follow the instructions included with the hood to com-  
plete the installation.  
Unitary Products Group  
25  
035-19046-002-B-0104  
For a dual enthalpy operation, carefully turn the set point  
adjusting screw fully clockwise past the "D" setting.  
ECONOMIZER AND POWER EXHAUST SET POINT  
ADJUSTMENTS AND INFORMATION  
POWER EXHAUST DAMPER SET POINT (WITH OR WITH-  
OUT POWER EXHAUST)  
Remove the top rear access panel from the unit. Locate the  
economizer control module, where the following adjustments  
will be made.  
With no power exhaust option, adjust the Exhaust Air  
Adjustment Screw fully clockwise. This will allow 2nd  
stage cooling to operate.  
With power exhaust option, each building pressurization  
requirement will be different. The point at which the  
power exhaust comes on is determined by the econo-  
mizer damper position (Percent Open). The Exhaust Air  
Adjustment Screw should be set at the Percent Open of  
the economizer damper at which the power exhaust is  
needed. It can be set from 0 to 100% damper open.  
Extreme care must be exercised in turning all set  
point, maximum and minimum damper positioning  
adjustment screws to prevent twisting them off.  
MINIMUM POSITION ADJUSTMENT  
Check that the damper blades move smoothly with bind-  
ing; carefully turn the Minimum Position Adjust screw  
(found on the damper control module) fully clockwise  
and then set the thermostat indoor fan switch to the ON  
position and then OFF or energize and de-energize ter-  
minals “R” to “G”.  
INDOOR AIR QUALITY AQ  
Indoor Air Quality (indoor sensor input): Terminal AQ accepts  
a +2 to +10 Vdc signal with respect to the (AQ1) terminal.  
When the signal is below it's set point, the actuator is allowed  
to modulate normally in accordance with the enthalpy and  
mixed air sensor inputs. When the AQ signal exceeds it's set  
point setting and there is no call for free cooling, the actuator  
is proportionately modulated from the 2 to 10 Vdc signal, with  
2 Vdc corresponding to full closed and 10 Vdc corresponding  
to full open. When there is no call for free cooling, the damper  
position is limited by the IAQ Max damper position setting.  
When the signal exceeds it's set point (Demand Control Ven-  
tilation Set Point) setting and there is a call for free cooling,  
the actuator modulates from the minimum position to the full  
open position based on the highest call from either the mixed  
air sensor input or the AQ voltage input.  
With the thermostat set to the indoor fan ON position or  
terminals “R” to “G” energized, turn the Minimum Posi-  
tion Adjusting screw (located on the damper control  
module) counterclockwise until the desired minimum  
damper position has been attained.  
ENTHALPY SET POINT ADJUSTMENT  
The enthalpy set point may now be set by selecting the  
desired set point shown in the Enthalpy Set Point Adjustment  
Figure 22. Adjust as follows:  
For a single enthalpy operation carefully turn the set  
point adjusting screw (found on the damper control mod-  
ule) to the "A", "B", "C" or "D" setting corresponding to  
the lettered curve of the Enthalpy Set Point Adjustment  
Figure 22.  
Optional CO Space Sensor Kit Part # 2AQ04700324  
2
Optional CO Sensor Kit Part # 2AQ04700424  
2
Replace the top rear access panel on the unit.  
26  
Unitary Products Group  
035-19046-002-B-0104  
CONTROL POINT  
APPROX. 0F (0C)  
AT 50% RH  
CONTROL  
CURVE  
85 90 95 100 105 110  
(29) (32) (35) (38) (41) (43)  
A
B
C
D
73 (23)  
70 (21)  
67 (19)  
63 (17)  
80  
(27)  
75  
(24)  
70  
(21)  
65  
(18)  
0  
(16)  
55  
(13)  
A
B
50  
(10)  
C
45  
(7)  
D
40  
(4)  
35  
(2)  
A
B
C
D
40 45  
(4) (7)  
65 70 75 80  
(24) (27)  
95  
105 110  
(41) (43)  
35  
(2)  
50 55 60  
(10) (13) (16)  
85 90  
(29) (32)  
100  
(38)  
(21)  
(35)  
(18)  
APPROXIMATE DRY BULB TEMPERATURE - 0F (0C)  
FIGURE 22 - ENTHALPY SET POINT CHART  
Exhaust Air  
Adjustment  
Screw  
EXH  
Set  
N
P
T
N1  
TR  
TR1  
Exhaust Air LED  
Damper Min.  
Position  
Screw  
24  
Vac  
HOT  
24  
Vac  
COM  
EXH  
P1  
T1  
Min  
Pos  
Indoor Air Quality  
Max. Adjustment  
Screw  
+
IAQ  
Max  
1
2
Indoor Air Quality  
LED  
IAQ  
AQ1  
SO+  
AQ  
SO  
5
4
Indoor Air Quality  
Min. Adjustment  
Screw  
IAQ  
Min  
3
Free  
Cool  
Free Cooling LED  
SR  
B
SR+  
EF  
EF1  
C
D
A
Economizer Enthalpy  
Set Point Adjustment  
Screw  
FIGURE 23 - HONEYWELL ECONOMIZER CONTROL W7212  
Unitary Products Group  
27  
035-19046-002-B-0104  
PHASING  
A
Predator Magnum DJ units are properly phased and pro-  
tected by a Phase Monitor from the factory. If the unit does  
not start up, the electrical connection to the unit may be mis-  
phased. Check the Phase Monitor for a Red LED, indicating a  
misphase. Change the phasing of the Field line connection  
at the Factory or Field Supplied Disconnect to obtain a  
Green LED on the Phase Monitor. (Scroll compressors oper-  
ate in only one direction. If the scroll is drawing low amper-  
age, has similar suction and discharge pressures, or  
producing a high noise level, the scroll is misphased.)  
A
C*  
* NEVER LOOSEN  
A
B
Scroll compressors require proper rotation to oper-  
ate correctly. Units are properly phased at the fac-  
tory. Do not change the internal wiring to make the  
blower condenser fans, or compressor rotate cor-  
rectly.  
SPAN LENGTH  
DEFL. FORCE  
BLOWER ROTATION  
Check for proper supply air blower rotation. If the blower is  
rotating backwards, the line voltage at the unit point of power  
connection is misphased (See ‘PHASING’).  
TABLE 14: SUPPLY AIR LIMITATIONS  
FIGURE 24 - BELT ADJUSTMENT  
Unit  
Minimum  
Maximum  
DJ150  
3750  
6250  
BELT TENSION  
Procedure for adjusting belt tension:  
The tension on the belt should be adjusted as shown in Fig-  
ure 24.  
1. Loosen six nuts (top and bottom) A.  
2. Adjust by turning (B).  
3. Never loosen nuts (C).  
4. Use belt tension checker to apply a perpendicular  
force to one belt at the midpoint of the span as  
shown. Deflection distance of 4mm (5/32”) is  
obtained.  
To determine the deflection distance from normal  
position, use a straight edge from sheave to sheave  
as reference line. The recommended deflection  
force is as follows:  
Tension new belts at the max. deflection force rec-  
ommended for the belt section. Check the belt ten-  
sion at least two times during the first 24 hours of  
operation. Any retensioning should fall between the  
min. and max. deflection force values.  
5. After adjusting retighten nuts (A).  
28  
Unitary Products Group  
035-19046-002-B-0104  
* †  
TABLE 15: DJ150, 12-1/2 TON STANDARD MOTOR DOWN SHOT BLOWER PERFORMANCE  
TURNS OPEN**  
ESP‡  
0
1
2
3
4
5
W††  
W††  
W††  
W††  
W††  
W††  
CFM  
BHP CFM  
BHP CFM  
BHP CFM  
BHP CFM  
BHP CFM  
BHP  
0.4  
0.6  
0.8  
1.0  
1.2  
1.4  
5078 3630 3.89 4809 3103 3.33 4594 3053 3.27 4360 2478 2.66 4090 2093 2.24 3812 1798 1.93  
4865 3456 3.71 4584 2961 3.17 4349 2912 3.12 4106 2318 2.49 3814 1964 2.11  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4642 3284 3.52 4356 2828 3.03 4089 2776 2.98 3840 2137 2.29  
-
-
-
-
-
-
-
-
-
-
-
-
4408 3114 3.34 4124 2705 2.90 3815 2647 2.84  
-
-
-
-
-
-
-
-
-
4164 2947 3.16 3889 2592 2.78  
3910 2787 2.99  
-
-
-
-
-
-
-
-
-
*.  
Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.  
Blower performance includes two-inch throwaway filters.  
†.  
‡.  
ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been  
deducted from the total static pressure of the blower.  
**.  
“Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.  
W = Watts  
††.  
* †  
TABLE 16: DJ150, 12-1/2 TON OPTIONAL MOTOR DOWN SHOT BLOWER PERFORMANCE  
TURNS OPEN**  
ESP‡  
0
1
2
3
4
5
W††  
W††  
W††  
W††  
W††  
W††  
CFM  
BHP CFM  
BHP CFM  
BHP CFM  
BHP CFM  
BHP CFM  
BHP  
5994 5400 5.79 5565 4369 4.69 5488 4169 4.47 5264 3599 3.86 4990 3085 3.31 4738 2812 3.02  
5824 5216 5.59 5368 4186 4.49 5289 3991 4.28 5049 3437 3.69 4763 2937 3.15 4491 2655 2.85  
5641 5022 5.39 5170 4012 4.30 5076 3807 4.08 4822 3272 3.51 4528 2790 2.99 4235 2497 2.68  
5444 4819 5.17 4971 3846 4.12 4847 3618 3.88 4584 3103 3.33 4286 2644 2.83 3969 2340 2.51  
0.4  
0.6  
0.8  
1.0  
1.2  
1.4  
1.6  
1.8  
2.0  
2.2  
5233 4609 4.94 4771 3687 3.95 4604 3426 3.67 4335 2933 3.15 4035 2499 2.68  
5009 4394 4.71 4571 3537 3.79 4346 3233 3.47 4074 2762 2.96 3777 2356 2.53  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4771 4174 4.48 4370 3395 3.64 4074 3040 3.26 3802 2590 2.78  
-
-
-
-
-
-
-
-
-
-
-
-
4520 3951 4.24 4169 3262 3.50 3786 2850 3.06  
-
-
-
-
-
-
-
-
-
4255 3728 4.00 3966 3137 3.36  
3976 3505 3.76 3763 3020 3.24  
-
-
-
-
-
-
*.  
Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.  
Blower performance includes two-inch throwaway filters.  
†.  
‡.  
ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been  
deducted from the total static pressure of the blower.  
**.  
“Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.  
W = Watts  
††.  
Unitary Products Group  
29  
035-19046-002-B-0104  
* †  
TABLE 17: DJ150, 12-1/2 TON STANDARD MOTOR SIDE SHOT BLOWER PERFORMANCE  
TURNS OPEN**  
ESP‡  
0
1
2
3
4
5
W††  
W††  
W††  
W††  
W††  
W††  
CFM  
BHP CFM  
BHP CFM  
BHP CFM  
BHP CFM  
BHP CFM  
BHP  
5201 3162 3.39 4966 2796 3.00 4681 2405 2.58 4355 2054 2.20  
0.4  
0.6  
0.8  
1.0  
1.2  
1.4  
-
-
-
-
-
-
-
-
-
-
-
-
5220 3395 3.64 4942 2980 3.20 4657 2608 2.80 4358 2230 2.39 4007 1890 2.03  
4944 3194 3.43 4661 2806 3.01 4378 2572 2.76 4016 2057 2.21  
-
-
-
-
-
-
-
-
-
-
-
-
5003 3490 3.74 4647 2988 3.20 4380 2636 2.83 4030 2257 2.42  
-
-
-
-
-
-
-
-
-
4724 3290 3.53 4363 2875 3.08 4012 2505 2.69  
4428 3040 3.26  
-
-
-
-
-
-
-
-
-
-
-
-
*.  
Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.  
Blower performance includes two-inch throwaway filters.  
†.  
‡.  
ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been  
deducted from the total static pressure of the blower.  
**.  
“Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.  
W = Watts  
††.  
* †  
TABLE 18: DJ150, 12-1/2 TON OPTIONAL MOTOR SIDE SHOT BLOWER PERFORMANCE  
TURNS OPEN**  
ESP‡  
0
1
2
3
4
5
W††  
W††  
W††  
W††  
W††  
W††  
CFM  
BHP CFM  
BHP CFM  
BHP  
CFM  
BHP CFM  
BHP CFM  
BHP  
0.4  
0.6  
0.8  
1.0  
1.2  
1.4  
1.6  
1.8  
2.0  
2.2  
2.4  
2.6  
-
-
-
-
-
-
-
-
-
6447 5315 5.70 6207 4760 5.1046 5966 4205 4.51 5717 3716 3.98 5470 3307 3.55  
6110 4917 5.27 5965 4464  
5772 4519 4.85 5741 4274  
4.79  
4.58  
4.34  
4.13  
3.94  
3.71  
3.47  
3.07  
-
5740 4023 4.31 5430 3501 3.75 5126 3054 3.28  
5503 3821 4.10 5162 3294 3.53 4849 2870 3.08  
5244 3611 3.87 4882 3101 3.33 4530 2667 2.86  
4941 3387 3.63 4589 2906 3.12 4225 2502 2.68  
4651 3178 3.41 4284 2716 2.91 3858 2280 2.45  
4365 2983 3.20 3951 2516 2.70 3491 2058 2.21  
6235 5521 5.92 5628 4407 4.73 5474 4048  
5881 5137 5.51 5384 4205 4.51 5248 3854  
5695 4950 5.31 5123 3996 4.29 5014 3670  
5471 4728 5.07 4919 3828 4.11 4732 3460  
5242 4514 4.84 4656 3611 3.87 4438 3240  
4954 4231 4.54 4339 3380 3.62 3905 2861  
3998 2740 2.94 3618 2316 2.48  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3631 2497 2.68  
-
-
-
-
-
-
-
-
-
-
-
-
4585 3934 4.22 4022 3149 3.38  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4217 3637 3.90  
3848 3340 3.58  
-
-
-
-
-
-
-
-
*.  
Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.  
Blower performance includes two-inch throwaway filters.  
†.  
‡.  
ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been  
deducted from the total static pressure of the blower.  
**.  
“Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.  
W = Watts  
††.  
NOTES FOR TABLE 15 THROUGH TABLE 18:  
Blower performance includes dry coil and two-inch  
filters.  
Blower performance for gas heat includes the maximum  
number of heat tubes available for each tonnage.  
ESP (External Static Pressure) given is that available for  
the supply and return air duct system. All internal resis-  
tances have been deducted from the total static pressure  
of the blower.  
30  
Unitary Products Group  
035-19046-002-B-0104  
TABLE 19: INDOOR BLOWER SPECIFICATIONS  
MOTOR  
MOTOR SHEAVE  
BLOWER SHEAVE  
MODEL  
BELT  
HP  
3
RPM Eff.  
SF Frame Datum Dia. (in.) Bore (in.) Model Datum Dia. (in.) Bore (in.) Model  
1725 80% 1.15  
1725 87% 1.15  
56  
3.4 - 4.4  
4.3 - 5.3  
7/8  
1VM50  
1VP56  
7.0  
6.7  
1
1
AK74  
BK77  
A54  
DJ150  
5
184T  
1 1/8  
BX55  
AIR BALANCE  
Start the supply air blower motor. Adjust the resistances in both the supply and the return air duct systems to balance the air  
distribution throughout the conditioned space. The job specifications may require that this balancing be done by someone other  
than the equipment installer.  
CHECKING AIR QUANTITY  
METHOD ONE  
METHOD TWO  
1. Remove the dot plugs from the duct panel (for location of  
the dot plugs see Figure 9).  
1. Drill two 5/16 inch holes, one in the return air duct as  
close to the inlet of the unit as possible, and another in  
the supply air duct as close to the outlet of the unit as  
possible.  
2. Insert eight-inches of 1/4 inch metal tubing into the air-  
flow on both sides of the indoor coil.  
2. Insert eight inches of 1/4 inch metal tubing into the air-  
flow of both return and supply air ducts of the unit.  
NOTE: The tubes must be inserted and held in a position  
perpendicular to the air flow so that velocity pres-  
sure will not affect the static pressure readings.  
NOTE: The tubes must be inserted and held in position per-  
pendicular to the airflow so that velocity pressure  
will not affect the static pressure readings.  
3. Use an Inclined Manometer or Magnehelic to determine  
the pressure drop across a dry evaporator coil. Since the  
moisture on an evaporator coil can vary greatly, measur-  
ing the pressure drop across a wet coil under field condi-  
tions could be inaccurate. To assure a dry coil, the  
compressors should be de-activated while the test is  
being run.  
3. Use an Inclined Manometer or Magnehelic to determine  
the pressure drop across the unit. This is the External  
Static Pressure (ESP).  
4. Select the indoor blower specifications for the unit from  
Table 19, 3 or 5 H.P. Motor.  
5. Determine the number of turns the variable pitch motor  
sheave is open.  
NOTE: De-energize the compressors before taking any test  
measurements to assure a dry evaporator coil.  
6. Select the correct blower performance table for the unit  
from Tables 15 - 18.  
4. The CFM through the unit with clean 2 inch filters can be  
determined from the pressure drop indicated by the  
manometer by referring to Figure 25.  
7. Determine the unit Measured CFM from the Blower Per-  
formance Table, External Static Pressure and number of  
turns the variable pitch motor sheave is open.  
5. To adjust Measured CFM to Required CFM, see ’SUP-  
PLY AIR DRIVE ADJUSTMENT’.  
8. To adjust Measured CFM to Required CFM, see ’SUP-  
PLY AIR DRIVE ADJUSTMENT’.  
6. After adjustments have been completed, remove the  
tubes and replace the dot plugs.  
9. After adjustments have been completed, remove the  
tubes and seal holes.  
NOTE: With the addition of field installed accessories  
repeat this procedure.  
Failure to properly adjust the total system air quan-  
tity can result in extensive blower damage.  
Failure to properly adjust the total system air quan-  
tity can result in extensive blower damage.  
Unitary Products Group  
31  
035-19046-002-B-0104  
Predator DJ 150 Units  
Indoor Coil Pressure Drop vs. Airflow  
1
0.9  
0.8  
0.7  
0.6  
0.5  
0.4  
0.3  
0.2  
0.1  
0
3500  
4000  
4500  
5000  
5500  
6000  
6500  
Airflow (CFM)  
FIGURE 25 - DRY COIL DELTA P  
SUPPLY AIR DRIVE ADJUSTMENT  
EXAMPLE  
A 12.5 ton unit was selected to deliver 4,000 CFM with a 3  
HP motor, but the unit is delivering 3,800 CFM. The variable  
pitch motor sheave is set at 2 turns open.  
Use the equation to determine the required DD for the new  
motor sheave,  
Before making any blower speed changes review  
the installation for any installation errors, leaks or  
undesirable systems effects that can result in loss of  
airflow.  
4,000 CFM  
• 4.0 in. = 4.21 in.  
)
(
3,800 CFM  
Even small changes in blower speed can result in  
substantial changes in static pressure and BHP.  
BHP and AMP draw of the blower motor will  
increase by the cube of the blower speed. Static  
pressure will increase by the square of the blower  
speed. Only qualified personnel should make blower  
speed changes, strictly adhering to the fan laws.  
Use Table 21 to locate the DD nearest to 4.21 in. Close the  
sheave to 1 turn open.  
New BHP  
= (Speed increase)3• BHP at 3,800 CFM  
At unit start-up, the measured CFM may be higher or lower  
than the required CFM. To achieve the required CFM, the  
speed of the drive may have adjusted by changing the datum  
diameter (DD) of the variable pitch motor sheave as  
described below:  
= (Speed increase)3 • Original BHP  
= New BHP  
Required CFM  
Measured CFM  
• Existing DD = New DD  
)
(
New motor Amps  
= (Speed increase)3• Amps at 3,800 CFM  
Use the following tables and the DD calculated per the above  
equation to adjust the motor variable pitch sheave.  
= (Speed increase)3 • Original Amps  
= New Amps  
32  
Unitary Products Group  
035-19046-002-B-0104  
TABLE 20: ADDITIONAL STATIC RESISTANCE  
Electric Heat KW†  
*
† ‡  
CFM  
Cooling Only  
Economizer  
18  
24  
36  
54  
3700  
3900  
4100  
4300  
4500  
4700  
4900  
5100  
5300  
5500  
5700  
5900  
6100  
6300  
0.20  
0.23  
0.25  
0.28  
0.30  
0.33  
0.36  
0.39  
0.42  
0.45  
0.48  
0.52  
0.56  
0.60  
0.04  
0.04  
0.04  
0.05  
0.05  
0.05  
0.05  
0.06  
0.06  
0.06  
0.06  
0.07  
0.07  
0.07  
0.18  
0.20  
0.22  
0.24  
0.26  
0.29  
0.31  
0.34  
0.37  
0.40  
0.43  
0.46  
0.49  
0.53  
0.21  
0.23  
0.25  
0.28  
0.30  
0.33  
0.35  
0.38  
0.41  
0.44  
0.47  
0.50  
0.53  
0.56  
0.22  
0.24  
0.26  
0.29  
0.31  
0.34  
0.37  
0.40  
0.43  
0.46  
0.49  
0.53  
0.56  
0.59  
0.26  
0.28  
0.31  
0.34  
0.37  
0.40  
0.43  
0.46  
0.49  
0.53  
0.56  
0.59  
0.62  
0.65  
*.  
Add these resistance values to the available static resistance in the respective Blower Performance Tables.  
†.  
‡.  
Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.  
The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return  
air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.  
For gas heating, the UCB monitors the "W1" call but does not  
TABLE 21: MOTOR SHEAVE DATUM DIAMETERS  
handle the operation of the gas furnace. An ignition control  
board controls the gas heater operation. For electric heat  
units, the UCB passes the call to the electric heater. In both  
cases, when the "W1" call is sensed, the indoor air blower is  
energized following a specified heating delay.  
1VM50x7/8  
(3 HP Motor)  
1VP56x1-1/8  
(5 HP Motor)  
Datum  
Diameter  
Datum  
Diameter  
Turns Open  
Turns Open  
0
1/2  
1
4.4  
1
1-1/2  
2
5.3  
If at any time a call for both heating and cooling are present,  
the heating operation will be performed. If operating, the cool-  
ing system is halted as with a completion of a call for cooling.  
Heating always takes priority.  
4.3  
5.2  
4.2  
5.1  
1-1/2  
2
4.1  
2-1/2  
3
5.0  
4.0  
4.9  
COOLING SEQUENCE OF OPERATION  
CONTINUOUS BLOWER  
2-1/2  
3
3.9  
3-1/2  
4
4.8  
3.8  
4.7  
3-1/2  
4
3.7  
4-1/2  
5
4.6  
By setting the room thermostat fan switch to "ON," the supply  
air blower will operate continuously.  
3.6  
4.5  
4-1/2  
5
3.5  
5-1/2  
6
4.4  
INTERMITTENT BLOWER  
3.4  
4.3  
With the room thermostat fan switch set to "AUTO" and the  
system switch set to either the "AUTO" or "HEAT" settings,  
the blower is energized whenever a cooling or heating opera-  
tion is requested. The blower is energized after any specified  
delay associated with the operation.  
OPERATION  
SEQUENCE OF OPERATIONS OVERVIEW  
For the Predator Magnum series of units, the thermostat  
makes a circuit between "R" and "Y1" for the first stage of  
cooling.  
When energized, the indoor blower has a minimum run time  
of 30 seconds. Additionally, the indoor blower has a delay of  
10 seconds between operations.  
The call is passed to the unit control board (UCB), which then  
determines whether the requested operation is available and,  
if so, which components to energize.  
Unitary Products Group  
33  
035-19046-002-B-0104  
NO OUTDOOR AIR OPTIONS  
gize compressor #1. If the outdoor air is above the set point,  
"Y2" will energize compressor #2.  
When the thermostat calls for the first stage of cooling, the  
low-voltage control circuit from “R” to “Y1” and “G” is com-  
pleted. The UCB energizes the economizer (if installed and  
free cooling is available) or the first available compressor*  
and the condenser fans. For first stage cooling, compressor  
#1 is energized. If compressor #1 is unavailable, compressor  
#2 is energized. After completing the specified fan on delay  
for cooling, the UCB will energize the blower motor.  
Once the thermostat has been satisfied, it will de-energize Y1  
and Y2. If the compressors have satisfied their minimum run  
times, the compressors and condenser fans are de-ener-  
gized. Otherwise, the unit operates each cooling system until  
the minimum run times for the compressors have been com-  
pleted. Upon the final compressor de-energizing, the blower  
is stopped following the elapse of the fan off delay for cooling,  
and the economizer damper goes to the closed position. If  
the unit is in continues fan operation the economizer damper  
goes to the min. position.  
When the thermostat calls for the second stage of cooling,  
the low-voltage control circuit from “R” to “Y2” is completed.  
The control board energizes the first available compressor. If  
free cooling is being used for the first stage of cooling, com-  
pressor #1 is energized. If compressor #1 is active for first  
stage cooling or the first compressor is locked-out, compres-  
sor #2 is energized. In free-cooling mode, if the call for the  
second stage of cooling continues for 20 minutes, compres-  
sor #2 is energized, provided it has not been locked-out.  
ECONOMIZER WITH DUAL ENTHALPY SENSORS -  
The operation with the dual enthalpy sensors is identical to  
the single sensor except that a second enthalpy sensor is  
mounted in the return air. This return air sensor allows the  
economizer to choose between outdoor air and return air,  
whichever has the lowest enthalpy value, to provide maxi-  
mum operating efficiency.  
If there is an initial call for both stages of cooling, the UCB will  
delay energizing compressor #2 by 30 seconds in order to  
avoid a power rush.  
ECONOMIZER (SINGLE OR DUAL) WITH POWER  
EXHAUST -  
Once the thermostat has been satisfied, the it will de-ener-  
gize Y1 and Y2. If the compressors have satisfied their mini-  
mum run times, the compressors and condenser fans are de-  
energized. Otherwise, the unit operates each cooling system  
until the minimum run times for the compressors have been  
completed. Upon the final compressor de-energizing, the  
blower is stopped following the elapse of the fan off delay for  
cooling.  
This system operates as specified above with one addition.  
The power exhaust motor is energized 45 seconds after the  
actuator position exceeds the exhaust fan set point on the  
economizer control. When the power exhaust is operating,  
the second stage of mechanical cooling will not operate. As  
always, the "R" to "G" connection provides minimum position  
but does not provide power exhaust operation.  
MOTORIZED OUTDOOR AIR DAMPERS -  
* To be available, a compressor must not be locked-out due  
to a high or low-pressure switch or freezestat trip and the  
anti-short cycle delay (ASCD) must have elapsed.  
This system operation is the same as the units with no out-  
door air options with one exception. When the "R" to "G" cir-  
cuit is complete, the motorized damper drives open to a  
position set by the thumbwheel on the damper motor. When  
the "R" to "G" circuit is opened, the damper spring returns  
fully closed.  
ECONOMIZER WITH SINGLE ENTHALPY SENSOR -  
When the room thermostat calls for "first-stage" cooling, the  
low voltage control circuit from "R" to "G" and "Y1" is com-  
pleted. The UCB energizes the blower motor (if the fan switch  
on the room thermostat is set in the "AUTO" position) and  
drives the economizer dampers from fully closed to their min-  
imum position. If the enthalpy of the outdoor air is below the  
set point of the enthalpy controller (previously determined),  
"Y1" energizes the economizer. The dampers will modulate to  
maintain a constant supply air temperature as monitored by  
the discharge air sensor. If the outdoor air enthalpy is above  
the set point, "Y1" energizes compressor #1, condenser fan  
motor #1, and condenser fan motor #2 (if the ambient tem-  
perature is above 60°F).  
COOLING OPERATION ERRORS  
Each cooling system is monitored for operation outside of the  
intended parameters. Errors are handled as described below.  
All system errors override minimum run times for compres-  
sors.  
HIGH-PRESSURE LIMIT SWITCH  
During cooling operation, if a high-pressure limit switch  
opens, the UCB will de-energize the associated compressor,  
initiate the ASCD (Anti-short cycle delay), and, if the other  
compressor is idle, stop the condenser fans. If the call for  
cooling is still present at the conclusion of the ASCD, the  
UCB will re-energize the halted compressor.  
When the thermostat calls for "second-stage" cooling, the low  
voltage control circuit from "R" to "Y2" is completed. The UCB  
energizes the first available compressor If the enthalpy of the  
outdoor air is below the set point of the enthalpy controller  
(i.e. first stage has energized the economizer), "Y2" will ener-  
34  
Unitary Products Group  
035-19046-002-B-0104  
Should a high-pressure switch open three times within two  
hours of operation, the UCB will lock-out the associated com-  
pressor and flash a code (see Table 28). If the other com-  
pressor is inactive, the condenser fans will be de-energized.  
of compressor operation. The defrost cycle will begin immedi-  
ately following the elapse of the minimum run time.  
When operating in low ambient mode, the UCB will not lock-  
out the compressors due to a freezestat trip. However, a  
freezestat trip will de-energize the associated compressor. If  
the call for cooling is still present at the end of the ASCD and  
the freezestat has closed, the unit will resume operation.  
LOW-PRESSURE LIMIT SWITCH  
The low-pressure limit switch is not monitored during the ini-  
tial 30 seconds of a cooling system's operation. For the fol-  
lowing 30 seconds, the UCB will monitor the low-pressure  
switch to ensure it closes. If the low-pressure switch fails to  
close after the 30-second monitoring phase, the UCB will de-  
energize the associated compressor, initiate the ASCD, and,  
if the other compressor is idle, stop the condenser fans.  
SAFETY CONTROLS  
The unit control board monitors the following inputs for each  
cooling system:  
1. A suction line freezestat to protect against low evapora-  
tor temperatures due to a low airflow or a low return air  
temperature, (opens at 26 ± 5 °F and resets at 38 ± 5°F).  
Once the low-pressure switch has been proven (closed dur-  
ing the 30-second monitor period described above), the UCB  
will monitor the low-pressure limit switch for any openings. If  
the low-pressure switch opens for greater than 5 seconds,  
the UCB will de-energize the associated compressor, initiate  
the ASCD, and, if the other compressor is idle, stop the con-  
denser fans.  
2. A high-pressure switch to protect against excessive dis-  
charge pressures due to a blocked condenser coil or a  
condenser motor failure, (opens at 380 ± 10 psig and  
resets at 300 ± 10 psig).  
3. A low-pressure switch to protect against loss of refriger-  
ant charge, (opens at 7 ± 3 psig and resets at 22 ± 5  
psig).  
If the call for cooling is still present at the conclusion of the  
ASCD, the UCB will re-energize the halted compressor.  
Should a low-pressure switch open three times within one  
hour of operation, the UCB will lock-out the associated com-  
pressor and flash a code (Table 28). If the other compressor  
is inactive, the condenser fans will be de-energized.  
The above pressure switches are hard-soldered to the unit.  
The refrigeration systems are independently monitored and  
controlled. On any fault, only the associated system will be  
affected by any safety/preventive action. The other refrigerant  
system will continue in operation unless it is affected by the  
fault as well.  
FREEZESTAT  
During cooling operation, if a freezestat opens, the UCB will  
de-energize the associated compressor, initiate the ASCD,  
and, if the other compressor is idle, stop the condenser fans.  
If the call for cooling is still present at the conclusion of the  
ASCD, the UCB will re-energize the halted compressor.  
The unit control board monitors the temperature limit switch  
of electric heat units and the temperature limit switch and the  
gas valve of gas furnace units.  
COMPRESSOR PROTECTION  
Should a freezestat open three times within two hours of  
operation, the UCB will lock-out the associated compressor  
and flash a code (Table 28). If the other compressor is inac-  
tive, the condenser fans will be de-energized.  
The compressors also have inherent (internal) protection. If  
there is an abnormal temperature rise in a compressor, the  
protector will open to shut down the compressor. The UCB  
incorporates features to minimize compressor wear and dam-  
age. An anti-short cycle delay (ASCD) is utilized to prevent  
operation of a compressor too soon after its previous run.  
Additionally, a minimum run time is imposed any time a com-  
pressor is energized.  
LOW AMBIENT COOLING  
To determine when to operate in low ambient mode, the UCB  
has a pair of terminals connected to a temperature-activated  
switch set at 45ºF. When the low ambient switch is closed  
and the thermostat is calling for cooling, the UCB will operate  
in the low ambient mode.  
The ASCD is initiated on unit start-up and on any compressor  
reset or lock-out.  
FLASH CODES  
Low ambient mode operates the compressors in this manner:  
10 minutes on, 5 minutes off. The indoor blower is operated  
throughout the cycle. The 5-minute off period is necessary to  
defrost the indoor coil.  
The UCB will initiate a flash code associated with errors  
within the system. Refer to UNIT CONTROL BOARD FLASH  
CODES Table 28.  
Low ambient mode always begins with compressor opera-  
tion. Compressor minimum run time may extend the minutes  
Unitary Products Group  
35  
035-19046-002-B-0104  
RESET  
TABLE 22: ELECTRIC HEAT LIMIT SETTING  
Remove the call for cooling, by raising thermostat setting  
higher than the conditioned space temperature. This resets  
any pressure or freezestat flash codes.  
LIMIT  
SWITCH  
OPENS °F  
HEATER  
kW  
UNIT (TONS)  
VOLTAGE  
12.5  
12.5  
12.5  
12.5  
12.5  
12.5  
12.5  
12.5  
12.5  
12.5  
12.5  
12.5  
18  
24  
34  
54  
18  
24  
34  
54  
18  
24  
34  
54  
150  
150  
150  
150  
150  
150  
150  
150  
150  
150  
150  
150  
ELECTRIC HEATING SEQUENCE OF OPERATIONS  
208/230  
The following sequence describes the operation of the elec-  
tric heat section.  
Two-stage heating:  
480  
600  
a. Upon a call for first stage heat by the thermostat, the  
heater relay (RA) will be energized. After completing  
the specified fan on delay for heating, the UCB will  
energize the blower motor. If the second stage of  
heat is required, heater relay (RB) will be energized.  
After completing the specified fan on delay for heat-  
ing, the UCB will energize the blower motor.  
b. The thermostat will cycle the electric heat to satisfy  
the heating requirements of the conditioned space.  
FLASH CODES  
The UCB will initiate a flash code associated with errors  
within the system. Refer to UNIT CONTROL BOARD FLASH  
CODES Table 28.  
ELECTRIC HEATING OPERATION ERRORS  
TEMPERATURE LIMIT  
RESET  
If the UCB senses zero volts from the high temperature limit,  
the indoor blower motor is immediately energized.  
Remove the call for heating by lowering the thermostat set-  
ting lower than the conditioned space temperature.This  
resets any flash codes.  
This limit is monitored regardless of unit operation status, i.e.  
the limit is monitored at all times.  
ELECTRIC HEAT ANTICIPATOR SETPOINTS  
If the temperature limit opens three times within one hour, it  
will lock-on the indoor blower motor and a flash code is initi-  
ated (See Table 28).  
It is important that the anticipator setpoint be correct. Too  
high of a setting will result in longer heat cycles and a greater  
temperature swing in the conditioned space. Reducing the  
value below the correct setpoint will give shorter “ON” cycles  
and may result in the lowering of the temperature within the  
conditioned space. Refer to Table 23 for the required electric  
heat anticipator setting.  
SAFETY CONTROLS  
The UCB monitors the temperature limit switch of electric  
heat units.  
The control circuit includes the following safety controls:  
TABLE 23: ELECTRIC HEAT ANTICIPATOR  
SETPOINTS  
LIMIT SWITCH (LS)  
This control is located inside the heater compartment and is  
set to open at the temperature indicated in the Electric Heat  
Limit Setting Table 22. It resets automatically. The limit switch  
operates when a high temperature condition, caused by inad-  
equate supply air flow occurs, thus shutting down the heater  
and energizing the blower.  
SETTING, AMPS  
W1  
W2  
0.13  
0.1  
36  
Unitary Products Group  
035-19046-002-B-0104  
If the unit fails after three ignition attempts, the furnace is  
locked-out for one hour. The furnace is monitored during this  
one-hour period for unsafe conditions.  
GAS HEATING SEQUENCE OF OPERATIONS  
When the thermostat calls for the first stage of heating, the  
low-voltage control circuit from “R” to “W1” is completed. A  
call for heat passes through the UCB to the ignition control  
board (ICB). The UCB monitors the “W1” call and acts upon  
any call for heat by monitoring the gas valve (GV). Once volt-  
age has been sensed at the GV, the UCB will initiate the fan  
on delay for heating, energizing the indoor blower the speci-  
fied delay has elapsed.  
RECYCLE OPERATION  
When a flame is lost after the flame stabilization period, a  
recycle operation occurs. If the unit fails after five recycle  
attempts, the furnace is locked-out for one hour.  
GAS HEATING OPERATION ERRORS  
LOCK-OUT  
When the thermostat has been satisfied, heating calls are  
ceased. The GV is immediately closed. The blower is de-  
energized after the fan off delay for heating has elapsed. The  
draft motor performs a 30-second post purge.  
A one-hour lockout occurs following three retries or five recy-  
cles. During the one-hour lockout, flame detection, limit con-  
ditions, and main valves are tested. Any improper results will  
cause the appropriate action to occur. Recycling the low volt-  
age power cancels the lock-out.  
IGNITION CONTROL BOARD  
FIRST STAGE OF HEATING  
TEMPERATURE LIMIT  
When the ICB receives a call for first stage of heating, “W1,”  
the draft motor is energized. Once the draft motor has been  
proven, a 30-second purge is initiated. At the end of the  
purge, both main valves of the GV are opened, and the spark  
ignitor is energized for 10 seconds. The ICB then checks for  
the presence of flame. If flame is detected, the ICB enters a  
flame stabilization period. If flame was not detected, both  
main valves close, and a retry operation begins.  
If the UCB senses zero volts from the high temperature limit,  
the indoor blower motor is immediately energized. When the  
UCB again senses 24 volts from the temperature limit, the  
draft motor will perform a 15-second post-purge and the  
indoor blower will be de-energized following the elapse of the  
fan off delay for heating.  
This limit is monitored regardless of unit operation status, i.e.  
this limit is monitored at all time.  
During the flame stabilization period, a loss of the flame for 2  
seconds will cause the main valves to close and the retry  
operation to begin. After the flame stabilization period, a loss  
of flame for 3/4 second will cause the main valves to close  
and the retry operation to begin.  
If the temperature limit opens three times within one hour, it  
will lock-on the indoor blower motor and flash code is initiated  
(See Table 28).  
FLAME SENSE  
At the conclusion of the flame stabilization period, the ICB will  
operate the gas heat in high fire (both valves open) for an  
additional 100 seconds (for a total for 120 seconds of high fire  
operation). After this 100 seconds, the ICB will then use the  
call for the second stage of heat to control the second main  
valve of the GV.  
Flame sensing occurs at all times. If “W1” is not present and  
a flame is sensed for 2 seconds, the draft motor is energized  
and the main valve is kept off. The ICB halts any operation  
until a flame is not detected. Once the flame detection is lost,  
the ICB performs a post-purge. Normal operation is allowed  
concurrently with the purge (i.e. this purge can be considered  
the purge associated with a call for “W1”).  
When “W1” is satisfied, both valves are closed.  
SECOND STAGE OF HEATING  
If “W1” is present, a flame is sensed, but the main valve is not  
energized, the draft motor is energized until the flame detec-  
tion is lost. Normal operation is now allowed.  
When the ICB receives a call for the second stage of heating,  
“W2,” the ICB conducts a complete first stage ignition  
sequence. If this sequence is satisfied, the second main  
valve of the GV is opened.  
The flame detection circuitry continually tests itself. If the ICB  
finds the flame detection circuitry to be faulty, the ICB will not  
permit an ignition sequence. Also, the draft motor is ener-  
gized. If this failure should occur during an ignition cycle the  
failure is counted as a recycle.  
When “W2” is satisfied, the second main valve is closed.  
RETRY OPERATION  
When a flame is lost or is not detected during an attempt to  
achieve ignition, a retry operation occurs. A 30-second purge  
is performed between ignition attempts.  
GAS VALVE  
The UCB and ICB continuously monitor the GV.  
Unitary Products Group  
37  
035-19046-002-B-0104  
If the ICB senses voltage at the GV when not requested, the  
ICB will energize the draft motor. The ICB will not operate the  
furnace until voltage is no longer sensed at the GV. The draft  
motor is stopped when voltage is not sensed at the GV.  
The auxiliary limit switch is wired in series with the limit  
switch. As such, the UCB cannot distinguish the auxiliary limit  
and the gas heat limit switch operation except the auxiliary is  
manual reset. Consequently, the control will respond in the  
same manner as outlined above under “Limit Switch”.  
Any time the UCB senses voltage at the GV without a call for  
heat for a continuous five-minute period, the UCB will lock-on  
the indoor blower and a flash code is initiated (Table 28).  
When voltage is no longer sensed at the GV, the UCB will de-  
energize the indoor blower following the elapse of the fan off  
delay for heating.  
*
TABLE 24: GAS HEAT LIMIT CONTROL SETTINGS  
# of HX Tubes  
Main Limit Setting  
195°F  
6
8
160°F  
If voltage has been sensed at the GV for at least 15 seconds  
during the fan on delay for heating and GV voltage or “W1” is  
lost, the indoor blower is forced on for the length of the fan off  
delay for heating.  
*.  
Rollout = 300°F, Auxiliary Limit = 200°F  
The ICB monitors the Pressure and Rollout switches of gas  
heat units.  
During a call for heat, if the UCB does not sense voltage at  
the GV for a continuous five-minute period the UCB will ini-  
tiate a flash code (Table 28). The indoor blower motor will not  
be locked-on while there is no GV voltage.  
The control circuit includes the following safety controls:  
PRESSURE SWITCH (PS)  
However, if during a normal ignition sequence, the NPC has  
been tested to be open, IDM energized, NPC closes and then  
the first stage main valve (MV1) is detected as being on, the  
ignition sequence stops and the IDM is de-energized. (Since  
the NPC is wired serially with the main valve relays, de-ener-  
gizing the IDM will open the NPC). This failure is counted as  
a recycle and will result in an eventual recycle lockout. If the  
main valve continues to be energized after the IDM is de-  
energized the IDM is re-energized. The second stage (MV2)  
main valve is not monitored for closure after energization.  
Once the draft motor has reached full speed and closes the  
pressure switch during a normal ignition sequence, if the  
pressure sw opens for 2 seconds, the GV will be de-ener-  
gized, the ignition cycle is aborted, and the ICB flashes the  
appropriate code. See Table 29 Ignition Control Flash Codes.  
The draft motor is energized until the pressure switch closes  
or “W1” is lost.  
ROLLOUT SWITCH (ROS)  
The rollout switch is wired in series with the pressure switch.  
As such, the ICB cannot distinguish the rollout switch opera-  
tion from that of the pressure switch.  
SAFETY CONTROLS  
The UCB monitors the temperature limit switch of gas heat  
units.  
Consequently, the control will only respond in the same man-  
ner as outlined above under “Pressure Switch”. An open roll-  
out will inhibit the gas valve from actuating.  
The control circuit includes the following safety controls:  
INTERNAL MICROPROCESSOR FAILURE  
LIMIT SWITCH (LS)  
If the ICB detects an internal failure, it will turn cease all out-  
puts, ignore inputs, and display the proper flash code for con-  
trol replacement. The ICB remains in this condition until  
replaced.  
This control is located inside the gas heat compartment and  
is set to open at the temperature indicated in the Gas Heat  
Limit Control Settings Table 24. It resets automatically. The  
limit switch operates when a high temperature condition,  
caused by inadequate supply air flow occurs, thus shutting  
down the heater and energizing the blower.  
FLASH CODES  
The UCB will initiate a flash code associated with errors  
within the system. Refer to UNIT CONTROL BOARD FLASH  
CODES Table 28.  
AUXILIARY LIMIT SWITCH (ALS)  
This control is located inside the supply air compartment and  
is set to open at the temperature indicated in the Gas Heat  
Limit Control Settings Table 24. It resets manually. The limit  
switch operates when a high temperature condition, caused  
by inadequate supply air flow occurs, thus shutting down the  
heater and energizing the blower.  
RESETS  
Remove the call for heating by lowering the thermostat set-  
ting lower than the conditioned space temperature. This  
resets any flash codes.  
38  
Unitary Products Group  
035-19046-002-B-0104  
GAS HEAT ANTICIPATOR SETPOINTS  
OPERATING INSTRUCTIONS  
It is important that the anticipator setpoint be correct. Too  
high of a setting will result in longer heat cycles and a greater  
temperature swing in the conditioned space. Reducing the  
value below the correct setpoint will give shorter “ON cycles  
and may result in the lowering of the temperature within the  
conditioned space. Refer to Table 25 for the required gas  
heat anticipator setting.  
1. Turn unit electrical power on.  
NOTE: Prior to each cooling season, the crankcase heaters  
must be energized at least 10 hours before the sys-  
tem is put into operation.  
2. Set the room thermostat setting to lower than the room  
temperature.  
3. First stage compressors will energize after the built-in  
time delay (five minutes).  
TABLE 25: GAS HEAT ANTICIPATOR SETPOINTS  
SETTING, AMPS  
4. The second stage of the thermostat will energize second  
stage compressor if needed.  
W1  
W2  
0.65  
0.1  
POST START CHECK LIST  
1. Verify proper system pressures for both circuits.  
2. Measure the temperature drop across the evaporator  
coil.  
H
E
A
T
E
X
C
H
A
N
G
E
R
T
U
B
E
START-UP (GAS HEAT)  
G
S
P
A
S
PRE-START CHECK LIST  
U
I
P
P
L
Y
B
U
R
N
E
R
L
A
M
E
B
U
R
N
E
R
P
E
(
B
L
U
E
O
N
L
Y
)
B
U
R
N
E
R
B
R
A
C
K
E
T
Complete the following checks before starting the unit.  
I
G
N
I
T
O
R
1. Check the type of gas being supplied. Be sure that it is  
the same as listed on the unit nameplate.  
FIGURE 26 - TYPICAL FLAME  
START-UP (COOLING)  
PRESTART CHECK LIST  
2. Make sure that the vent outlet and combustion air inlet  
are free of any debris or obstruction.  
OPERATING INSTRUCTIONS  
After installation has been completed:  
1. Check the electrical supply voltage being supplied. Be  
sure that it is the same as listed on the unit nameplate.  
2. Set the room thermostat to the off position.  
3. Turn unit electrical power on.  
This furnace is equipped with an intermittent pilot and  
automatic re-ignition system. DO NOT attempt to  
manually light the pilot.  
4. Set the room thermostat fan switch to on.  
5. Check indoor blower rotation.  
LIGHTING THE MAIN BURNERS  
1. Turn “OFF” electric power to unit.  
2. Turn room thermostat to lowest setting.  
If blower rotation is in the wrong direction. Refer to  
Phasing Section in general information section.  
3. Turn gas valve counter-clockwise to “ON” position (see  
Figure 27).  
Check blower drive belt tension.  
6. Check the unit supply air (CFM).  
4. Turn “ON” electric power to unit.  
7. Measure evaporator fan motor's amp draw.  
8. Set the room thermostat fan switch to off.  
9. Turn unit electrical power off.  
5. If thermostat set temperature is above room tempera-  
ture, the main burners will ignite. If a second stage of  
heat is called for, the main burners for second stage heat  
will ignite for the second stage heat.  
Unitary Products Group  
39  
035-19046-002-B-0104  
2. Using the outlet pressure port on the gas valve, connect  
a manometer to monitor the manifold pressure.  
POST START CHECKLIST  
After the entire control circuit has been energized and the  
heating section is operating, make the following checks:  
3. Remove plastic cap covering HI and LO pressure adjust-  
ment screws.  
1. Check for gas leaks in the unit piping as well as the sup-  
ply piping.  
4. Turn on power to the unit.  
5. Set thermostat to call for second stage heat and start fur-  
nace.  
6. If necessary, using a screwdriver, turn the second stage  
adjustment screw (adjacent to the “HI” marking on the  
valve) clockwise to increase manifold pressure or coun-  
terclockwise to decrease manifold pressure. Be sure not  
to over-fire the unit on second stage.  
FIRE OR EXPLOSION HAZARD  
Failure to follow the safety warning exactly could  
result in serious injury, death or property damage.  
7. After the high manifold pressure has been checked,  
adjust the thermostat to call for first stage heat.  
Never test for gas leaks with an open flame. use a  
commercially available soap solution made specifi-  
cally for the detection of leaks to check all connec-  
tions. A fire or explosion may result causing property  
damage, personal injury or loss of life.  
8. If necessary, using a screwdriver, turn the first stage  
adjustment screw (adjacent to the “LO” marking on the  
valve) clockwise to increase manifold pressure or  
counterclockwise to decrease manifold pressure. Be  
sure not to under-fire the unit on first stage.  
2. Check for correct manifold gas pressures. (See ’CHECK-  
ING GAS INPUT’.)  
9. Once pressure has been checked, replace the plastic  
cap covering the HI and LO pressure adjustment screws.  
3. Check the supply gas pressure. It must be within the lim-  
its shown on the rating nameplate. Supply pressure  
should be checked with all gas appliances in the building  
at full fire. At no time should the standby gas pressure  
exceed 13 in. or the operating pressure drop below 5.0 in  
for natural gas units. If gas pressure is outside these  
limits, contact the local gas utility or propane supplier for  
corrective action.  
NOTE: When using natural gas, the manifold pressure for  
second stage (100% input) should be 3.5 IWG ±  
0.3. The manifold pressure for first stage (60%  
input) when using natural gas should be 1.5 IWG ±  
0.3.  
CHECKING GAS INPUT  
NATURAL GAS  
SHUT DOWN  
1. Set the thermostat to the lowest temperature setting.  
2. Turn “OFF” all electric power to unit.  
3. Open gas heat access panel.  
This unit has two stages of gas heat. The first stage is 60% of  
the full fire input and is considered the minimum input for the  
furnace. The intended input for each furnace is shown in the  
table below. The following Table applies to units operating on  
60 Hz power only.  
4. Turn gas valve clockwise to “OFF” position (See Figure  
27).  
TABLE 26: GAS HEAT STAGES  
MANIFOLD GAS PRESSURE ADJUSTMENT  
2nd Stage  
Input (100%  
Btuh)  
1st Stage  
Input (60%  
Btuh)  
# of Burner Tubes  
This gas furnace has two heat stages. Therefore, the gas  
valve has two adjustment screws located under a plastic pro-  
tective cover. The second stage (100% input) adjustment  
screw is adjacent to the “HI” marking on the valve and the  
first stage (60% input) adjustment screw is located adjacent  
to the “LO” marking on the valve (See Figure 27).  
6
8
180,000  
240,000  
108,000  
144,000  
To determine the rate of gas flow (second Stage).  
1. Turn of all other gas appliances connected to the gas  
meter.  
Manifold pressure adjustment procedure.  
Adjust second stage (100% input) pressure first, then adjust  
first stage (60% input) pressure.  
2. Turn on the furnace and make sure the thermostat is  
calling for Second stage (100% input) heat.  
1. Turn off all power to the unit.  
40  
Unitary Products Group  
035-19046-002-B-0104  
3. Measure the time needed for one revolution of the hand  
on the smallest dial on the meter. A typical gas meter  
has a 1/2 or a 1 cubic foot test dial.  
TABLE 27: GAS RATE CUBIC FEET PER HOUR  
Seconds  
for One  
Rev.  
Size of Test Dial  
1/2 cu. ft.  
1 cu. ft.  
4. Using the number of seconds it takes for one revolution  
of the dial, calculate the cubic feet of gas consumed per  
hour. (See example below).  
10  
12  
14  
16  
18  
20  
22  
24  
26  
28  
30  
32  
34  
36  
38  
40  
42  
44  
46  
48  
50  
52  
54  
56  
58  
60  
180  
150  
129  
113  
100  
90  
82  
75  
69  
64  
60  
56  
53  
50  
47  
45  
43  
41  
39  
37  
36  
35  
34  
32  
31  
30  
360  
300  
257  
225  
200  
180  
164  
150  
138  
129  
120  
113  
106  
100  
95  
5. If necessary, adjust the high pressure regulator as dis-  
cussed in the section “Manifold Gas Pressure Adjust-  
ment”. Be sure not to over-fire the furnace on Second  
stage. If in doubt, it is better to leave the Second stage of  
the furnace slightly under-fired. Repeat Steps 1-5.  
To determine the rate of gas flow (First Stage)  
1. Turn of all other gas appliances connected to the gas  
meter.  
2. Turn on the furnace and make sure the thermostat is  
calling for first stage (60% input) heat.  
3. Even when the thermostat is calling for first stage heat,  
the unit will light on second stage and will run on Second  
stage for 1 minute. Allow this one-minute time period to  
expire and be certain the unit is running on first stage.  
90  
86  
4. Measure the time needed for one revolution of the hand  
on the smallest dial on the meter. A typical gas meter  
has a 1/2 or a 1 cubic foot test dial.  
82  
78  
75  
5. Using the number of seconds it takes for one revolution  
of the dial, calculate the cubic feet of gas consumed per  
hour (See example below).  
72  
69  
67  
6. If necessary, adjust the low pressure regulator as dis-  
cussed in the section “Manifold Gas Pressure Adjust-  
ment”. Be sure not to under-fire the furnace on first  
stage. If in doubt, it is better to leave the first stage of the  
furnace slightly over-fired (greater than 60% input).  
Repeat Steps 1-6.  
64  
62  
60  
NOTE: To find the Btu input, multiply the number of cubic  
feet of gas consumed per hour by the Btu content of  
the gas in your particular locality (contact your gas  
company for this information as it varies widely from  
area to area).  
Unitary Products Group  
41  
035-19046-002-B-0104  
EXAMPLE:  
3. Disconnect wiring to the gas valves and spark igniter(s).  
Remove the manifold & gas valve assembly. Orifices can  
now be inspected and/or replaced.  
By actual measurement, it takes 19 seconds for the hand on  
a 1 cubic foot dial to make a revolution with a 192,000 Btuh  
furnace running. To determine rotations per minute, divide 60  
by 19 = 3.16. To calculate rotations per hour, multiply 3.16 •  
60 = 189.6. Multiply 189.6 1 (0.5 if using a 1/2 cubic foot  
dial) = 189.6. Multiply 189.6 (the Btu rating of the gas). For  
this example, assume the gas has a Btu rating of 1050  
To service burners, complete step 4.  
4. Remove the heat shield on top of the manifold supports.  
Burners are now accessible for inspection and/or  
replacement.  
NOTE: Reverse the above procedure to replace the assem-  
Btu/ft.3. The result of 199,000 Btuh is within 5% of the  
192,000 Btuh rating of the furnace.  
blies.  
Make sure that burners are level and seat at the rear of the  
gas orifice.  
ADJUSTMENT OF TEMPERATURE RISE  
The temperature rise (the difference of temperature between  
the return air and the heated air from the furnace) must lie  
within the range shown on the CSA rating plate and the data  
in Table 25.  
H
I
G
H
&
L
O
W
G
A
S
A
D
J
U
S
T
M
E
N
T
After the temperature rise has been determined, the CFM can  
be calculated as follows:  
L
O
H
I
0.8  
(1.08 ⋅ ∆°F)  
-----------------------------  
CFM = Btu Input •  
O
N
I
N
L
E
T
O
P
R
E
S
S
U
R
E
After about 20 minutes of operation, determine the furnace  
temperature rise. Take readings of both the return air and the  
heated air in the ducts (about 6 feet from the furnace) where  
they will not be affected by radiant heat. Increase the blower  
CFM to decrease the temperature rise; decrease the blower  
CFM to increase the rise (See ’SUPPLY AIR DRIVE  
ADJUSTMENT’).  
T
A
P
O
U
T
L
E
T
R
P
R
E
S
S
U
E
T
A
P
M
A
T
E
N
-
N
-
L
O
C
K
C
O
N
E
C
T
O
R
S
NOTE: Each gas heat exchanger size has a minimum  
allowable CFM. Below this CFM, the limit will open  
below this rating.  
M
V
I
C
H
BURNERS/ORIFICES INSPECTION/SERVICING  
Before checking or changing burners, pilot or orifices,  
CLOSE MAIN MANUAL SHUT-OFF VALVE AND SHUT OFF  
ALL POWER TO THE UNIT.  
1. Open the union fitting just upstream of the unit gas valve  
and downstream from the main manual shut-off valve in  
the gas supply line.  
FIGURE 27 - TYPICAL GAS VALVE  
2. Remove the screws holding each end of the manifold to  
the manifold supports.  
42  
Unitary Products Group  
035-19046-002-B-0104  
CHARGING THE UNIT  
TABLE 28: UNIT CONTROL BOARD FLASH CODES  
Flash Code  
On Steady  
Heart Beat  
1 Flash  
Description  
Control Failure - Replace Control  
Normal Operation  
The DJ150 (12-1/2 Ton) High Efficiency Unit, uses a TXV  
metering device. Charge unit to 10º sub-cooling at the TXV.  
Not Applicable  
TROUBLESHOOTING  
*
2 Flashes  
3 Flashes  
4 Flashes  
5 Flashes  
6 Flashes  
7 Flashes  
8 Flashes  
Control waiting ASCD  
HPS1 - Compressor Lock out  
HPS2 - Compressor Lock out  
LPS1 - Compressor Lock out  
LPS2 - Compressor Lock out  
FS1 - Compressor Lock out  
FS2 - Compressor Lock out  
Troubleshooting of components may require open-  
ing the electrical control box with the power con-  
nected to the unit. Use extreme care when  
working with live circuits! Check the unit name-  
plate for the correct line voltage and set the voltme-  
ter to the correct range before making any  
connections with line terminals.  
Ignition Control Locked Out/  
Ignition Control Failure / Limit Switch Trip / No  
Jumper Plug in Heat Section  
9 Flashes  
Compressors Locked Out On Low  
10 Flashes  
11 Flashes  
12 Flashes  
*
Outdoor Air Temperature  
When not necessary, shut off all electric power to the  
unit prior to any of the following maintenance proce-  
dures so as to prevent personal injury.  
Compressors Locked Out Because The  
*
Economizer Is Using Free Cooling  
Fan Overload Switch Trip - Not Applicable On This  
Unit  
13 Flashes  
14 Flashes  
OFF  
Compressor Held Off Due To Low Voltage*  
EEPROM Storage Failure (Control Failure)  
No Power or Control Failure  
Label all wires prior to disconnection when servicing  
controls. Wiring errors can cause improper and dan-  
gerous operation which could cause injury to person  
and/or damage unit components. Verify proper oper-  
ation after servicing.  
*.  
These flash codes do not represent alarms.  
TABLE 29: IGNITION CONTROL FLASH CODES  
FLASHES  
STEADY ON  
HEARTBEAT  
1
FAULT CONDITIONS  
CHECK  
PREDATORMAGNUM FLASH CODES  
Control Failure  
Control  
Normal Operation  
Not Applicable  
Various flash codes are utilized by the unit control board  
(UCB) to aid troubleshooting. Flash codes are distinguished  
by the short on and off cycle used (approximately 200ms on  
and 200ms off). To show normal operation, the control board  
flashes a 1 second on, 1 second off “heartbeat” during normal  
operation. This is to verify that the UCB is functioning cor-  
rectly. Do not confuse this with an error flash code. To prevent  
confusion, a 1-flash, flash code is not used.  
Pressure Switch  
Stuck Closed  
2
3
4
Pressure Switch  
Pressure Switch Failed  
To Close  
Venter Pressure Switch  
Vent Blocked  
Main Limit  
AUX Limit  
Limit Switch Open  
Current alarms are flashed on the UCB LED. The alarm his-  
tory can be checked by pressing and releasing the ALARMS  
button on the UCB. The UCB will cycle through the last five  
(5) alarms, most recent to oldest, separating each alarm flash  
code by approximately 2 seconds.  
Flame Present With Gas  
Off First Stage Gas Valve  
Energized With W1 Off  
Second Stage Gas Valve  
Energized With First  
Stage  
5
Gas Valve  
Gas Valve Off  
In some cases, it may be necessary to “zero” the ASCD for  
the compressors in order to perform troubleshooting. To reset  
all ASCDs for one cycle, press and release the UCB TEST  
button once.  
Gas Flow  
Gas Pressure  
Gas Valve  
6
Ignition Lockout  
Flame Sensor  
No Power Or Control  
Failure  
24VAC or Control  
STEADY OFF  
Unitary Products Group  
43  
035-19046-002-B-0104  
Loss of  
Call for  
Heating?  
Monitored  
Systems  
Problem?  
No  
Yes  
No  
No  
Call for  
Heating?  
Programming?  
Yes  
Heat Off  
Yes  
Yes  
No  
Program  
Unit  
Control  
Board  
Call for 2nd  
Stage  
Cooling  
Call for  
Heat  
Trip/Failure  
No  
Yes  
Energize ID  
Call for  
First  
Monitor  
Blower Motor  
Cooling?  
Stage?  
Yes  
No  
Yes  
No  
Call for 1st  
Stage  
Cooling  
No  
Yes  
Turn off ID  
Blower Motor  
Fan on  
>30 secs?  
Fan off  
>10 secs?  
Yes  
Yes  
No  
No  
No  
Yes  
Lossof Call  
for ID Blower?  
Call for  
ID Blower?  
Loss of Call  
for Cooling?  
Cool Off  
FIGURE 28 - BASIC TROUBLESHOOTING FLOWCHART  
Yes  
Yes  
Voltage @  
Gas Valve?  
Call for  
heat?  
Power to  
Unit  
No  
No  
Energize ID  
Blower  
Initialize ASCD  
Montior  
FIGURE 29 - POWER ON FLOW CHART  
44  
Unitary Products Group  
035-19046-002-B-0104  
H
P
L
P
N
o
N
o
N
o
N
o
L
o
s
s
o
f
r
e
e
z
e
s
t
a
t
T
r
i
p
/
a
i
l
u
r
e
S
w
i
t
c
h
S
w
i
t
c
h
O
p
e
n
1
L
S
I
n
p
u
t
O
p
e
n
?
1
2
O
p
e
n
>
5
S
e
c
s
Y
e
s
Y
e
s
Y
e
s
Y
e
s
T
u
r
n
o
f
f
T
u
r
n
o
f
f
T
u
r
n
o
f
f
E
n
e
r
g
i
z
e
b
l
o
w
e
r
:
c
o
m
p
r
e
s
s
o
r
;
C
o
m
p
r
e
s
s
o
r
,
c
o
m
p
r
e
s
s
o
r
,
i
n
c
r
e
a
s
e
i
n
c
i
d
e
n
t
i
n
i
t
i
a
t
e
A
S
C
D
;
i
n
i
t
i
a
t
e
A
S
C
D
;
i
n
i
t
i
a
t
e
A
S
C
D
;
v
a
l
u
e
b
y
1
i
n
c
r
e
a
s
e
i
n
c
i
d
e
n
t
i
n
c
r
e
a
s
e
i
n
c
i
d
e
n
t
i
n
c
r
e
a
s
e
i
n
c
i
d
e
n
t
v
a
l
v
e
b
y
1
v
a
l
u
e
b
y
1
v
a
l
u
e
b
y
1
N
o
N
o
N
o
N
o
I
n
c
i
d
e
n
t
L
S
i
n
p
u
t
I
n
c
i
d
e
n
t
I
n
c
i
d
e
n
t
I
n
c
i
d
e
n
t
v
a
l
u
e
>
=
3
?
r
e
g
a
i
n
e
d
?
v
a
l
u
e
>
=
3
v
a
l
u
e
>
=
3
v
a
l
u
e
>
=
3
N
o
Y
e
s
Y
e
s
Y
e
s
Y
e
s
Y
e
s
L
o
c
k
s
-
s
o
u
t
L
o
c
k
-
o
u
t
L
o
c
k
-
o
u
t
c
o
m
p
r
e
o
r
,
t
u
r
n
L
o
c
k
o
n
b
l
o
w
e
r
;
L
o
a
d
o
f
f
D
c
o
m
p
r
e
s
s
o
r
,
f
l
a
g
c
o
m
p
r
e
s
s
o
r
,
f
l
a
g
o
f
f
I
D
b
l
o
w
e
r
,
t
u
r
n
f
l
a
g
a
l
a
r
m
a
l
a
r
m
a
l
a
r
m
o
f
f
c
o
n
d
e
n
s
e
r
f
a
n
s
,
f
l
a
g
a
l
a
r
m
M
o
n
i
t
o
r
G
V
L
o
s
s
o
f
C
a
l
l
f
o
r
N
o
N
o
N
o
N
o
v
o
l
t
a
g
e
G
V
v
o
l
t
a
g
e
O
S
i
n
p
u
t
H
e
a
t
w
/
o
u
t
G
V
w
/
o
u
t
c
a
l
l
f
o
r
>
5
m
i
n
?
>
5
S
e
c
s
?
v
o
l
t
a
g
e
?
h
e
a
t
?
Y
e
s
Y
e
s
Y
e
s
l
a
g
A
l
a
r
m
T
u
r
n
o
f
f
f
a
n
N
o
Y
e
s
c
o
m
p
r
e
s
s
o
r
&
l
a
g
a
l
a
r
m
,
w
l
o
c
k
v
o
l
t
a
g
e
>
5
c
o
n
d
e
n
s
e
r
f
a
n
s
;
o
n
I
D
b
l
o
e
r
m
i
n
?
i
n
i
t
i
a
t
e
A
S
C
D
N
o
N
o
N
o
I
n
c
i
d
e
n
t
O
S
i
n
p
u
t
L
o
s
s
o
f
G
V
O
S
i
n
p
u
t
>
1
5
v
a
l
u
s
e
>
=
3
r
e
g
a
i
n
e
d
?
V
o
l
t
a
g
e
?
Y
e
s
N
o
m
i
n
u
t
e
s
?
Y
e
Y
e
s
Y
e
s
N
o
L
o
c
k
-
o
u
t
E
n
e
r
g
i
z
e
I
D
c
o
m
p
r
e
s
s
o
r
s
,
t
u
r
n
I
n
c
r
e
a
s
e
i
n
c
i
d
e
n
t
l
a
g
a
l
a
r
m
,
t
u
r
n
o
n
b
l
o
w
e
r
,
l
o
a
d
'
a
n
o
f
f
I
D
b
l
o
w
e
r
,
t
u
r
n
v
a
l
u
e
b
y
1
X
l
i
n
e
O
f
f
D
e
l
a
y
'
f
o
r
o
f
f
c
o
n
d
e
n
s
e
r
h
e
a
t
i
n
g
f
a
n
s
,
f
l
a
g
a
l
a
r
m
M
o
n
i
t
o
r
1
2
T
T
h
h
e
e
c
l
o
n
t
r
o
l
b
s
o
a
r
d
o
n
l
i
y
t
m
o
i
n
i
t
o
r
s
t
h
e
i
n
p
u
t
w
h
e
n
t
h
e
c
o
m
p
r
e
s
s
o
r
r
e
a
l
l
y
i
s
e
n
e
r
g
i
z
e
d
.
o
w
-
p
r
e
s
u
r
e
0
s
s
w
e
c
h
s
n
o
t
m
o
n
i
t
o
o
r
l
e
d
f
o
r
t
h
e
f
i
r
s
t
3
0
s
e
c
o
n
d
s
o
f
c
o
m
p
r
e
s
s
o
r
a
c
t
i
v
i
t
y
.
T
h
e
c
o
n
t
r
o
l
b
o
a
r
d
t
h
e
n
m
o
n
i
t
o
r
s
t
h
e
s
w
i
t
c
h
t
o
e
n
s
u
r
e
i
t
c
l
o
s
e
s
.
I
f
t
h
e
s
w
i
t
c
h
r
e
m
a
i
n
s
o
p
e
n
a
l
n
d
a
d
d
h
i
t
i
o
n
a
l
3
c
o
n
d
s
,
t
h
e
c
o
n
t
r
i
b
o
a
r
d
t
u
r
n
s
o
h
f
a
f
t
h
e
a
s
s
o
c
i
a
t
e
d
c
o
m
p
r
e
s
s
o
r
a
n
d
i
n
i
t
i
a
t
e
s
t
h
e
A
S
C
D
.
O
n
c
e
i
t
h
a
s
c
l
o
s
e
d
d
u
r
i
n
g
t
h
e
s
t
a
r
t
u
p
p
e
r
i
o
d
,
t
h
e
c
o
n
t
r
o
l
b
o
a
r
d
n
o
o
n
g
e
r
a
n
d
l
e
s
t
h
e
l
o
w
-
p
r
e
s
s
u
r
e
s
w
t
c
h
d
i
f
f
e
r
e
n
t
l
y
t
n
o
t
h
e
r
i
n
p
u
t
s
.
FIGURE 30 - TRIP FAILURE FLOW CHART  
Unitary Products Group  
45  
035-19046-002-B-0104  
On calls for cooling, the supply air blower motor is operating  
but compressor #1 is not (the room thermostat fan switch is in  
the “AUTO” position).  
COOLING TROUBLESHOOTING GUIDE  
On calls for cooling, if the compressors are operating but the  
supply air blower motor does not energize after a short delay  
(the room thermostat fan switch is in the “AUTO” position).  
1. If installed, check the position of the economizer blades.  
If the blades are open, the economizer is providing free  
cooling and the compressors will not immediately oper-  
ate. If both stages of cooling are requested simulta-  
neously and the economizer provides free cooling,  
following a short delay compressor #1 will be energized  
unless it is locked out. If compressor #1 is locked out,  
compressor #2 is energized. Compressor #2 is always  
energized in place of compressor #1 when compressor  
#1 is requested but locked out.  
1. Turn the thermostat fan switch to the ON position. If the  
supply air blower motor does not energize, go to Step 3.  
2. If the blower motor runs with the fan switch in the ON  
position but will not run after the first compressor has  
energized when the fan switch is in the AUTO position,  
check the room thermostat for contact between R and G  
in the AUTO position during calls for cooling.  
3. If the supply air blower motor does not energize when  
the fan switch is set to ON, check that line voltage is  
being supplied to the contacts of the M3, contactor, and  
that the contactor is pulled in. Check for loose wiring  
between the contactor and the supply air blower motor.  
2. If no economizer is installed or the economizer is not  
opening to provide free cooling and compressor #1 does  
not energize on a call for cooling, check for line voltage  
at the compressor contactor, M1, and that the contactor  
is pulled in. Check for loose wiring between the contac-  
tor and the compressor.  
4. If M3 is pulled in and voltage is supplied to M3, lightly  
touch the supply air blower motor housing. If it is hot, the  
motor may be off on internal protection. Cancel any  
thermostat calls and set the fan switch to AUTO. Wait for  
the internal overload to reset. Test again when cool.  
3. If M1 is pulled in and voltage is supplied at M1, lightly  
touch the compressor housing. If it is hot, the compres-  
sor may be off on inherent protection. Cancel any calls  
for cooling and wait for the internal overload to reset.  
Test again when cool.  
5. If M3 is not pulled in, check for 24 volts at the M3 coil. If  
24 volts are present at M3 but M3 is not pulled in,  
replace the contactor.  
4. If M1 is not pulled in, check for 24 volts at the M1 coil. If  
24 volts are present and M1 is not pulled in, replace the  
contactor.  
6. Failing the above, if there is line voltage supplied at M3,  
M3 is pulled in, and the supply air blower motor still does  
not operate, replace the motor.  
5. Failing the above, if voltage is supplied at M1, M1 is  
pulled in, and the compressor still does not operate,  
replace the compressor.  
7. If 24 volts is not present at M3, check that 24 volts is  
present at the UCB supply air blower motor terminal,  
“FAN”. If 24 volts is present at the FAN, check for loose  
wiring between the UCB and M3.  
6. If 24 volts is not present at M1, check for 24 volts at the  
UCB terminal, C1. If 24 volts is present, check for loose  
wiring between C1 and the compressor contactor.  
8. If 24 volts is not present at the “FAN” terminal, check for  
24 volts from the room thermostat. If 24 volts are not  
present from the room thermostat, check for the follow-  
ing:  
7. If 24 volts is not present at the C1 terminal, check for 24  
volts from the room thermostat at the UCB Y1 terminal.  
If 24 volts is not present from the room thermostat, check  
for the following:  
a. Proper operation of the room thermostat (contact  
between R and G with the fan switch in the ON posi-  
tion and in the AUTO position during operation  
calls).  
a. 24 volts at the thermostat Y1 terminal  
b. Proper wiring between the room thermostat and the  
UCB, i.e. Y1 to Y1, Y2 to Y2  
c. Loose wiring from the room thermostat to the UCB.  
b. Proper wiring between the room thermostat and the  
UCB.  
8. If 24 volts is present at the UCB Y1 terminal, the com-  
pressor may be out due to an open high-pressure switch,  
low-pressure switch, or freezestat. Check for 24 volts at  
the HPS1, LPS1, and FS1 terminals of the UCB. If a  
switch has opened, there should be a voltage potential  
between the UCB terminals, e.g. if LPS1 has opened,  
there will be a 24-volt potential between the LPS1 termi-  
nals.  
c. Loose wiring from the room thermostat to the UCB.  
9. If 24 volts is present at the room thermostat but not at the  
UCB, check for proper wiring between the thermostat  
and the UCB, i.e. that the thermostat G terminal is con-  
nected to the G terminal of the UCB, and for loose wir-  
ing.  
9. If 24 volts is present at the UCB Y1 terminal and none of  
the protection switches have opened, the UCB may have  
10. If the thermostat and UCB are properly wired, replace  
the UCB.  
46  
Unitary Products Group  
035-19046-002-B-0104  
locked out the compressor for repeat trips. The UCB  
should be flashing an alarm code. If not, press and  
release the ALARMS button on the UCB. The UCB will  
flash the last five alarms on the LED. If the compressor is  
locked out, cancel any call for cooling. This will reset any  
compressor lock outs.  
On calls for the second stage of cooling, the supply air blower  
motor and compressor #1 are operating but compressor #2 is  
not (the room thermostat fan switch is in the “AUTO” posi-  
tion).  
1. If installed, check the position of the economizer blades.  
If the blades are open, the economizer is providing free  
cooling. If the second stage of cooling is requested, fol-  
lowing a short delay, compressor #1 will be energized  
unless it is locked out. Typically, compressor #2 is ener-  
gized only during free cooling if the call for the second  
stage of cooling persists for 20 minutes.  
NOTE: While the above step will reset any lockouts, com-  
pressor #1 may be held off for the ASCD. See the  
next step.  
10. If 24 volts is present at the UCB Y1 terminal and none of  
the switches are open and the compressor is not locked  
out, the UCB may have the compressor in an ASCD.  
Check the LED for an indication of an ASCD cycle. The  
ASCD should time out within 5 minutes. Press and  
release the TEST button to reset all ASCDs.  
2. Compressor #2 will not energize simultaneously with  
compressor #1 if a call for both stages of cooling is  
received. The UCB delays compressor #2 by 30 sec-  
onds to prevent a power surge. If after the delay com-  
pressor #2 does not energize on a second stage call for  
cooling, check for line voltage at the compressor contac-  
tor, M2, and that the contactor is pulled in. Check for  
loose wiring between the contactor and the compressor.  
11. If 24 volts is present at the UCB Y1 terminal and the  
compressor is not out due to a protective switch trip,  
repeat trip lock out, or ASCD, the economizer terminals  
of the UCB may be improperly wired. Check for 24 volts  
at the Y1 “OUT” terminal of the UCB. If 24 volts is  
present, trace the wiring from Y1 “OUT” for incorrect wir-  
ing. If 24 volts is not present at the Y1 “OUT” terminal,  
the UCB must be replaced.  
3. If M2 is pulled in and voltage is supplied at M2, lightly  
touch the compressor housing. If it is hot, the compres-  
sor may be off on inherent protection. Cancel any calls  
for cooling and wait for the internal overload to reset.  
Test again when cool.  
12. For units without economizers:If 24 volts is present at the  
Y1 OUT terminal, check for 24 volts at the Y1 “ECON”  
terminal. If 24 volts is not present, check for loose wiring  
from the Y1 “OUT” terminal to the Mate-N-Lock plug, the  
jumper in the Mate-N-Lock plug, and in the wiring from  
the Mate-N-Lock plug to the Y1 “ECON” terminal.  
4. If M2 is not pulled in, check for 24 volts at the M2 coil. If  
24 volts is present and M2 is not pulled in, replace the  
contactor.  
5. Failing the above, if voltage is supplied at M2, M2 is  
pulled in, and the compressor still does not operate,  
replace the compressor.  
13. For units with economizers: If 24 volts is present at the  
Y1 “OUT” terminal, check for 24 volts at the Y1 “ECON”  
terminal. If 24 volts is not present, check for loose wiring  
from the Y1 “OUT” terminal to the Mate-N-Lock plug, a  
poor connection between the UCB and economizer  
Mate-N-Lock plugs, loose wiring from the Mate-N-Lock  
plug to the economizer, back to the Mate-N-Lock plug,  
and from the Mate-N-Lock plug to the Y1 “ECON” termi-  
nal. If nothing is found, the economizer DME may have  
faulted and is failing to return the 24-volt “call” to the Y1  
“ECON” terminal even though the economizer is not pro-  
viding free cooling. To test, disconnect the Mate-N-Locks  
and jumper between the WHITE and YELLOW wires of  
the UCB’s Mate-N-Lock plug. If compressor #1 ener-  
gizes, there is a fault in the economizer wiring or DME.  
6. If 24 volts is not present at M2, check for 24 volts at the  
UCB terminal, C2. If 24 volts are present, check for  
loose wiring between C2 and the compressor contactor.  
7. If 24 volts is not present at the C2 terminal, check for 24  
volts from the room thermostat at the UCB Y2 terminal. If  
24 volts is not present from the room thermostat, check  
for the following:  
a. 24 volts at the thermostat Y2 terminal  
b. Proper wiring between the room thermostat and the  
UCB, i.e. Y1 to Y1, Y2 to Y2  
c. Loose wiring from the room thermostat to the UCB.  
14. The UCB can be programmed to lock out compressor  
operation during free cooling and in low ambient condi-  
tions. These options are not enabled by default. Local  
York distributors can test the UCB for this programming.  
8. If 24 volts is present at the UCB Y2 terminal, the com-  
pressor may be out due to an open high-pressure switch,  
low-pressure switch, or freezestat. Check for 24 volts at  
the HPS2, LPS2, and FS2 terminals of the UCB. If a  
switch has opened, there should be a voltage potential  
between the UCB terminals, e.g. if LPS2 has opened,  
there will be 24 volts of potential between the LPS2 ter-  
minals.  
15. If none of the above corrected the error, test the integrity  
of the UCB. Disconnect the C1 terminal wire and jumper  
it to the Y1 terminal. DO NOT jump the Y1 to C1 termi-  
nals. If the compressor engages, the UCB has faulted.  
16. If none of the above correct the error, replace the UCB.  
9. If 24 volts is present at the UCB Y2 terminal and none of  
the protection switches have opened, the UCB may have  
Unitary Products Group  
47  
035-19046-002-B-0104  
locked out the compressor for repeat trips. The UCB  
should be flashing a code. If not, press and release the  
ALARMS button on the UCB. The UCB will flash the last  
five alarms on the LED. If the compressor is locked out,  
6. If 24 volts is not present at M1, check for 24 volts at the  
UCB terminal, C1. If 24 volts is present, check for loose  
wiring between C1 and the compressor contactor.  
7. If 24 volts is not present at the C1 terminal, check for 24  
volts from the room thermostat at the UCB Y1 terminal.  
If 24 volts are not present at the UCB Y1 terminal, the  
UCB may have faulted. Check for 24 volts at the Y1  
ECON terminal. If 24 volts is not present at Y1 “ECON”,  
the UCB has faulted. The UCB should de-energize all  
compressors on a loss of call for the first stage of cool-  
ing, i.e. a loss if 24 volts at the Y1 terminal.  
remove any call for cooling at the thermostat or by dis-  
connecting the thermostat wiring at the Y2 UCB terminal.  
This will reset any compressor lock outs.  
NOTE: While the above step will reset any lock outs, com-  
pressor #1 will be held off for the ASCD, and com-  
pressor #2 may be held off for a portion of the  
ASCD. See the next step.  
8. If 24 volts are present at the UCB Y1 terminal, the com-  
pressor may be out due to an open high-pressure switch,  
low-pressure switch, or freezestat. Check for 24 volts at  
the HPS1, LPS1, and FS1 terminals of the UCB. If a  
switch has opened, there should be a voltage potential  
between the UCB terminals, e.g. if LPS1 has opened,  
there will be a 24-volt potential between the LPS1 termi-  
nals.  
10. If 24 volts is present at the UCB Y2 terminal and none of  
the switches are open and the compressor is not locked  
out, the UCB may have the compressor in an ASCD.  
Check the LED for an indication of an ASCD cycle. The  
ASCD should time out within 5 minutes. Press and  
release the TEST button to reset all ASCDs.  
11. The UCB can be programmed to lock out compressor  
operation during free cooling and in low ambient condi-  
tions. These options are not enabled by default. Local  
York distributors can test the UCB for this programming.  
9. If 24 volts is present at the UCB Y1 terminal and none of  
the protection switches have opened, the UCB may have  
locked out the compressor for repeat trips. The UCB  
should be flashing a code. If not, press and release the  
ALARMS button on the UCB. The UCB will flash the last  
five alarms on the LED. If the compressor is locked out,  
remove any call for cooling. This will reset any compres-  
sor lock outs.  
12. If none of the above corrected the error, test the integrity  
of the UCB. Disconnect the C2 terminal wire and jumper  
it to the Y2 terminal. DO NOT jump the Y2 to C2 termi-  
nals. If the compressor engages, the UCB has faulted.  
13. If none of the above correct the error, replace the UCB.  
NOTE: While the above step will reset any lock outs, com-  
pressor #2 will be held off for the ASCD, and com-  
pressor #1 may be held off for a portion of the  
ASCD. See the next step.  
On a call for cooling, the supply air blower motor and com-  
pressor #2 are operating but compressor #1 is not (the room  
thermostat fan switch is in the “AUTO” position).  
10. If 24 volts is present at the UCB Y1 terminal and none of  
the switches are open and the compressor is not locked  
out, the UCB may have the compressor in an ASCD.  
Check the LED for an indication of an ASCD cycle. The  
ASCD should time out within 5 minutes. Press and  
release the TEST button to reset all ASCDs.  
1. Compressor #2 is energized in place of compressor #1  
when compressor #1 is unavailable for cooling calls.  
Check the UCB for alarms indicating that compressor #1  
is locked out. Press and release the ALARMS button if  
the LED is not flashing an alarm.  
2. Check for line voltage at the compressor contactor, M1,  
and that the contactor is pulled in. Check for loose wiring  
between the contactor and the compressor.  
11. If 24 volts is present at the UCB Y1 terminal and the  
compressor is not out due to a protective switch trip,  
repeat trip lock out, or ASCD, the economizer terminals  
of the UCB may be improperly wired. Check for 24 volts  
at the Y1 “OUT” terminal of the UCB. If 24 volts is  
present, trace the wiring from Y1 “OUT” for incorrect wir-  
ing. If 24 volts is not present at the Y1 “OUT” terminal,  
the UCB must be replaced.  
3. If M1 is pulled in and voltage is supplied at M1, lightly  
touch the compressor housing. If it is hot, the compres-  
sor may be off on inherent protection. Cancel any calls  
for cooling and wait for the internal overload to reset.  
Test again when cool.  
4. If M1 is not pulled in, check for 24 volts at the M1 coil. If  
24 volts is present and M1 is not pulled in, replace the  
contactor.  
12. For units without economizers: If 24 volts is present at  
the Y1 “OUT” terminal, check for 24 volts at the Y1  
“ECON” terminal. If 24 volts is not present, check for  
loose wiring from the Y1 “OUT” terminal to the Mate-N-  
Lock plug, the jumper in the Mate-N-Lock plug, and in  
the wiring from the Mate-N-Lock plug to the Y1 “ECON”  
terminal.  
5. Failing the above, if voltage is supplied at M1, M1 is  
pulled in, and the compressor still does not operate,  
replace the compressor.  
48  
Unitary Products Group  
035-19046-002-B-0104  
For units with economizers:If 24 volts is present at the  
Y1 “OUT” terminal, check for 24 volts at the Y1 “ECON”  
terminal. If 24 volts is not present, check for loose wiring  
from the Y1 “OUT” terminal to the Mate-N-Lock plug, a  
poor connection between the UCB and economizer  
Mate-N-Lock plugs, loose wiring from the Mate-N-Lock  
plug to the economizer, back to the Mate-N-Lock plug,  
and from the Mate-N-Lock plug to the Y1 “ECON” termi-  
nal. The economizer board may have faulted and is not  
returning the 24 volts to the Y1 “ECON” terminal even  
though the economizer is not providing free cooling. To  
test the economizer board, disconnect the Mate-N-Locks  
and jumper between the WHITE and YELLOW wires of  
the UCB’s Mate-N-Lock plug.  
4. If M3 is not pulled in, check for 24 volts at the M3 coil. If  
24 volts is present at M3 but M3 is not pulled in, replace  
the contactor.  
5. Failing the above, if there is line voltage supplied at M3,  
M3 is pulled in, and the supply air blower motor still does  
not operate, replace the motor.  
6. If 24 volts is not present at M3, check that 24 volts is  
present at the supply air blower motor terminal on the  
UCB. If 24 volts is present at the UCB terminal, check for  
loose wiring between the UCB and M3.  
7. If 24 volts is not present at the UCB supply air blower  
motor terminal, check for 24 volts from the room thermo-  
stat. If 24 volts is not present from the room thermostat,  
check for the following:  
13. The UCB can be programmed to lock out compressor  
operation during free cooling and in low ambient condi-  
tions. These options are not enabled by default. They  
can be checked by local York distributors.  
a. Proper operation of the room thermostat (contact  
between R and G with the fan switch in the “ON”  
position and in the “AUTO” position during operation  
calls).  
14. If none of the above corrected the error, test the integrity  
of the UCB. Disconnect the C1 terminal wire and jumper  
it to the Y1 terminal. DO NOT jump the Y1 to C1 termi-  
nals. If the compressor engages, the UCB has faulted.  
b. Proper wiring between the room thermostat and the  
UCB.  
c. Loose wiring from the room thermostat to the UCB.  
15. If none of the above correct the error, replace the UCB.  
8. If 24 volts is present at the room thermostat but not at the  
UCB, check for proper wiring between the thermostat  
and the UCB, i.e. that the thermostat G terminal is con-  
nected to the G terminal of the UCB, and for loose wir-  
ing.  
GAS HEAT TROUBLESHOOTING GUIDE  
On calls for heating, the draft motor operates and the furnace  
lights but the supply air blower motor does not energize after  
a short delay (the room thermostat fan switch is in “AUTO”  
position).  
9. If the thermostat and UCB are properly wired, replace  
the UCB.  
10. If the blower motor runs with the fan switch in the “ON”  
position but does not run shortly after the furnace has  
ignited when the fan switch is in the “AUTO” position,  
check the room thermostat for contact between R and G  
during “W1” calls.  
The furnace may shut down on a high temperature  
condition during the procedure. If this occurs, the  
UCB energize the supply air blower motor until the  
high temperature limit has reset. Caution should be  
used at all times as the supply air blower may ener-  
gize regardless of the room thermostat fan switch  
position.  
On calls for heating, the supply air blower operates but the  
draft motor does not (the room thermostat fan switch is in the  
“AUTO” position).  
1. The draft motor has inherent protection. If the motor  
shell is hot to the touch, wait for the internal overload to  
reset.  
1. Place the thermostat fan switch in the “ON” position. If  
the supply air blower motor energizes, go to Step 10.  
2. If the motor shell is cold with the room thermostat calling  
for heat, check for line voltage at the motor leads. If line  
voltage is present, replace the draft motor.  
2. If the supply air blower motor does not energize when  
the fan switch is set to “ON,” check that line voltage is  
being supplied to the contacts of the M3 contactor, and  
that the contactor is pulled in. Check for loose wiring  
between the contactor and the supply air blower motor.  
3. If line voltage is not present, check for line voltage on the  
ignition control at the “inducer” terminal draft motor relay  
(DMR or DMC) contacts in the main control box and  
check to see if the (DMR or DMC) is pulled in.  
3. If M3 is pulled in and voltage is supplied at M3, lightly  
touch the supply air blower motor housing. If it is hot, the  
motor may be off on inherent protection. Cancel any  
thermostat calls and set the fan switch to “AUTO”, wait  
for the internal overload to reset. Test again when cool.  
The draft motor runs but the furnace does not light and the  
spark ignitor does not spark.  
Unitary Products Group  
49  
035-19046-002-B-0104  
1. Check for 24 volts at the spark ignitor from the ignition  
control board (ICB). Check the 24-volt wiring from the  
ICB to the spark ignitor. Check for 24 volts at the ICB  
spark ignitor terminal.  
The draft motor runs and the spark ignitor sparks at the  
burner, but the burner does not ignite and a gas odor is not  
detected at the draft motor outlet.  
1. Check to ensure gas is being supplied to the unit. Con-  
firm that the gas pressure to the unit is within the proper  
limits as described in the “POST START CHECKLIST”.  
2. Check the ground wiring for the ICB and the gas valve is  
intact and making good electrical connection. Check the  
ceramic insulator on the spark ignitor for breaks or  
cracks. Replace the spark ignitor if damaged.  
2. Check the voltage at the gas valve and at the gas valve  
terminals on the ICB. Check all wiring between the ICB  
and the gas valve. Check to make sure the ground con-  
nections are intact.  
3. With the draft motor running, check for 24 volts at the  
pressure switch terminal on the ICB. If not present,  
check for 24 volts on the terminal from the pressure  
switch. If present, go to step 4. If 24 volts is not present,  
the either pressure or rollout switch is not closed. Or the  
draft motor is not sufficiently evacuating the heat  
exchanger tubes or the pressure switch has failed.  
Check the operation of the pressure switch. Check the  
line voltage to the unit; if line voltage is low, call the local  
power company. If the problem persists, the draft motor  
may need replacement.  
3. If 24 volts is present, remove the pilot burner and the ori-  
fice. The removal procedure is described in  
“BURNER/ORIFICE INSTRUCTIONS.” Inspect the ori-  
fice for obstruction. If it is clear, replace the gas valve.  
Main burners light but exhibit erratic flame characteristics.  
4. Check the main burner orifices for obstruction and align-  
ment. The removal procedure is described in  
4. If the furnace is hot, it may be out on a high temperature  
limit open; wait for limit reset.  
“BURNER/ORIFICE INSTRUCTIONS.” Clean or replace  
burner orifices and burners as needed.  
5. If all are intact replace the ICB.  
50  
Unitary Products Group  
035-19046-002-B-0104  
Unitary Products Group  
51  
Subject to change without notice. Printed in U.S.A.  
035-19046-002-B-0104  
Copyright © 2004 by Unitary Products Group. All rights reserved.  
Supersedes: 035-19046-002-A-0803  
Unitary  
Products  
Group  
5005  
York  
Drive  
Norman  
OK  
73069  

Oki Es 1624n Mfp User Manual
Pac Swi Ps User Manual
Panasonic Cs Mc12dku User Manual
Panasonic Cw Xc145hu User Manual
Philips Sbcsc486 User Manual
Philips Workio Dp C262 User Manual
Samsung As18a9 A0 Rcd User Manual
Samsung Aw1293l User Manual
Samsung Um 19a1 B1 E2 User Manual
York Ycjd18 Thru 60 User Manual