254599-YTG-C-0807
®
DESCRIPTION
®
YORK Sunline Plus™ units are convertible single package
air conditioners. The units were designed for light commercial
and commercial applications. They can easily be installed on
a roof curb, slab, roof jack or frame.
TECHNICAL GUIDE
SINGLE PACKAGE GAS/ELECTRIC UNITS
AND SINGLE PACKAGE
All units include:
•
Powder Paint finish that meets ASTM-B-117 1000 hour
salt spray standards
AIR CONDITIONERS
•
•
Permanently lubricated motors
DF 072
6 NOMINAL TONS
10.4 EER
Bottom or side air discharge configuration capability
(field convertible)
•
•
•
•
•
•
•
•
•
Manufactured under the quality standards of ISO9001
®
S implicity Control Board
Copper tube/aluminum fin coils
Easy access to all components
Rigging holes in base rails for lifting
Fork lift slots on three sides
Single point power connection
Complete factory package - tested, charged and wired
CSA agency listing on all units
WARRANTY
•
•
•
Factory Limited Parts Warranty
One-year parts warranty
A Five-year parts warranty on the compressor and
electric heat elements.
•
Ten-year parts warranty on the gas-fired heat
exchangers.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
254599-YTG-C-0807
PRODUCT NOMENCLATURE
6 Ton Sunline Model Number Nomenclature
D F 072 N04 A 2 A AA 1 0 1 2 4 A
Product Category
Product Style
D = A/C, Single Pkg., R-22
A = Style A
Product Identifier
F = 10.4 EER A/C
Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.
SS Drain Pan
CPC Controller, DFS, APS
Nominal Cooling Capacity
Johnson Controller, DFS, APS
Honeywell Controller, DFS, APS
072 = 6.0 Ton
Novar Controller, DFS, APS
Simplicity IntelliComfort Controller
Heat Type and Nominal Heat Capacity
Simplicity IntelliComfort Controller w/ModLinc
2" Pleated filters
C00 = Cooling Only. Suitable for Field
Installed Electric Heat
BAS Ready Economizer (2-10 V. D. C. Actuator without a Controller)
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
Gas Heat Options
Product Generation
N08 = 80 MBH Output Aluminized Steel, 1 Stage
(072)
1 = First Generation
2 = Second Generation
N10 = 100 MBH Output Aluminized Steel, 1 Stage
(072)
D06 = 60 MBH Output Aluminized Steel, 2 Stage
(072)
Additional Options
Hinged Filter Door & Toolless Access Cabinet
D10 = 100 MBH Output Aluminized Steel, 2 Stage
(072)
S08 = 80 MBH Output Stainless Steel, 1 Stage
Standard Cabinet
(072)
S10 = 100 MBH Output Stainless Steel, 1 Stage
AA = None
BA = Hinged Filter Door & Toolless Access Panels
BA = Hinged Filter Door & Toolless Access Panels
BB = Phase Monitor, Hinged Filter Door & Toolless
Access Panels
BC = Coil Guard, Hinged Filter Door & Toolless
Access Panels
BD = Dirty Filter Switch, Hinged Filter Door &
Toolless Access Panels
BE = Phase Monitor & Coil Guard, Hinged Filter
Door & Toolless Access Panels
BF = Phase Monitor & Dirty Filter Switch, Hinged
Filter Door & Toolless Access Panels
BG = Coil Guard & Dirty Filter Switch, Hinged Filter
Door & Toolless Access Panels
(072)
AB = Phase Monitor
T06 = 60 MBH Output Stainless Steel, 2 Stage
AC = Coil Guard
(072)
AD = Dirty Filter Switch
T10 = 100 MBH Output Stainless Steel, 2 Stage
(072)
AE = Phase Monitor & Coil Guard
AF = Phase Monitor & Dirty Filter Switch
AG = Coil Guard & Dirty Filter Switch
AH = Phase Monitor, Coil Guard & Dirty Filter Switch
AS = Bottom Drain Connection
RC = Coil Guard & American Flag
TA = Technicoat Condenser Coil
TJ = Technicoat Evaporator Coil
TS = Technicoat Evaporator and Condenser Coil
Electric Heat Options
E05 = 5 KW
E07 = 7 KW
E10 = 10 KW
E15 = 15 KW
E20 = 20 KW
E30 = 30 KW
BH = Phase Monitor, Coil Guard & Dirty Filter Switch,
Hinged Filter Door & Toolless Access Panels
*(D, T) 10 = 92 MBH Output on 036 Models
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
Airflow
A = Direct Drive
B = Direct Drive/Single Input Economizer
D = Direct Drive/Motorized Damper
N = Belt Drive
P = Belt Drive/Single Input Economizer
R = Belt Drive/Motorized Damper
Installation Options
A = No Options Installed
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
Voltage
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
Options
1 = Disconnect
2 = Non-Pwr'd Conv. Outlet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
Unitary Products Group
3
254599-YTG-C-0807
gas valve, if applicable, and the temperature limit
switch on gas heat units. The unit control board will
alarm on ignition failures, compressor lockouts and
repeated limit switch trips.
FEATURES
All models are available with a wide variety of factory-
mounted options such as stainless steel heat exchangers,
electric heaters, phase monitor, convenience outlet, dirty filter
switch, disconnect switch, smoke detectors, and coil guard to
make them suitable for almost every application.
•
•
Nuisance Trip Protection- To prevent nuisance
trouble calls, the control board uses a “three strikes,
you’re out” philosophy. The high and low-pressure
switches and the freezestats must trip three times
within two hours before the unit control board will
lock out the compressor.
All units are self-contained and assembled on full perimeter
base rails with forklift holes on three sides and holes for over-
head rigging. Every unit is completely piped, wired, charged
and tested at the factory to simplify the field installation and to
provide years of dependable operation.
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
All models (including those with an economizer) are suitable
for either bottom or horizontal duct connections. For bottom
duct, remove the sheet metal panels from the supply and
return air openings through the base of the unit. For horizon-
tal duct, remove the supply and return air panels on the rear
of the unit.
All models are available with these “factory mounted” outdoor
air damper options:
All units have long lasting powder paint cabinets with 1000
hour salt spray test approval under ASTM-B117 procedures.
•
•
Single enthalpy economizer
Motorized outdoor air damper
All models are CSA listed.
•
Warranty - All models include a one-year limited parts
warranty on the complete unit. Compressors and electric
heater elements carry a five-year warranty. Gas heat
exchangers carry a 10-year parts warranty.
Supply air blowers are equipped with either a direct drive or a
belt drive that can be adjusted to meet the exact require-
ments of the job.
•
Gas Heat Operation - All single phase models with gas
heat have minimum annual fuel utilization efficiency
(AFUE) of 80%. All three phase models with gas heat
have minimum steady state efficiency of 80%. Each sec-
tion includes a durable heat exchanger with aluminized
steel or optional stainless steel tubes, a redundant gas
valve, spark ignition, power venting, an ignition module for
100% shut-off and all of the safety controls required to
meet the latest ANSI standards.
All compressors are equipped with internal pressure relief.
Every refrigerant circuit includes a liquid line filter-drier, a high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch to protect all system compo-
nents.
®
®
•
S implicity Controls - S implicity control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
The gas supply piping can be routed into the heating
compartment through a hole in the base pan of the unit
or through a knockout in the piping panel on the front of
the unit.
•
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0ºF outdoor ambient without additional assis-
tance. Optionally, the control board can be pro-
grammed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
•
Electric Heat Operation - All electric heat models are
wired for a single power source and include a bank of
nickel chromium elements mounted at the discharge of
the supply air blower to provide a high velocity and uni-
form distribution of air across the heating elements.
Every element is fully protected against excessive tem-
perature by thermal limit switches.
•
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti short cycle delay can be temporarily
overridden with the push of a button.
The power supply wiring can be routed into the control
box through a threaded pipe connection (field supplied)
in the base pan of the unit or through a knockout in the
wiring panel on the side of the unit.
•
•
Fan Delays - Fan on and fan off delays are fully pro-
grammable and are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
•
BAS Controls - York’s Sunline™ series units offer factory
®
mounted BAS controls such as S implicity INTELLI-Com-
fort™, Novar, Honeywell, Johnson, and CPC.
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
4
Unitary Products Group
254599-YTG-C-0807
FIGURE 1 - UNIT CUTAWAY
•
ELECTRIC HEATERS - Wired for single point power
supply. These nickel chromium heater elements are pro-
vided with limit and automatic reset capability to prevent
operation at excessive temperatures.
FACTORY-INSTALLED OPTIONS
•
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa-
ble of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
•
•
FILTER OPTIONS - Standard units are shipped with 1”
throw-away filters installed. 2” pleated filters are offered
as a factory installed option.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
CONVENIENCE OUTLET - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or the
unit may be ordered with a “non-powered” convenience
outlet that can be wired in the field.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•
•
DISCONNECT SWITCH - For gas heat units and cooling
units with electric heat, a HACR breaker sized to the unit
is provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is oper-
ating and will drive fully closed when the blower unit
shuts down.
BAS - Building Automation System Controls
®
S implicity INTELLI-Comfort™ CONTROL - The York®
®
The rain hood is painted to match the basic unit and
must be field assembled before installing.
S implicity INTELLI-Comfort™ control is factory
installed. It includes a supply air sensor, a return air sen-
sor, and an outside air sensor. There are provisions for a
field installed dirty filter indicator switch, an air-proving
switch, an Outside Air Humidity sensor, a Return Air
Humidity sensor, an Inside IAQ sensor, and an Outside
Air IAQ sensor. Construction mode operation, 365-day
real time clock with 7 day programming plus holiday
•
PHENOLIC COATED EVAPORATOR AND CON-
DENSER COILS - Special coating process that utilizes
TM
Technicoat 10-1 processes. Coating is applied by total
immersion of the complete coil for maximum protection.
Unitary Products Group
5
254599-YTG-C-0807
scheduling is built-in. Two different modes of demand
ventilation are achieved through the INTELLI-Comfort™
using CO2 sensors. It uses an inside CO2 sensor to per-
form Demand Ventilation. It can also use an Outside
CO2 sensor to perform Differential Demand Ventilation.
It uses a Patented Comfort Ventilation algorithm to pro-
vide comfortable ventilation air temperature. The pat-
ented economizer-loading algorithm will protect the
equipment when harsh operating conditions exist.
Humidity in the occupied space or return duct can be
monitored and controlled via humidity sensors and the
on-board connection for hot gas re-heat system. It uses
the INTELLI-Start™ algorithm to maximize energy sav-
ings by recovering the building from the Unoccupied Set-
points to the Occupied Setpoints just in time for the
power to the control board if smoke is detected within the
air compartment.
Factory installed Smoke Detectors in the return air,
may be subjected to freezing temperatures during
“off” times due to outside air infiltration. These
smoke detectors have an operational limit of 32°F
to 131°F. Smoke detectors installed in areas that
could be outside those limitations will have to be
moved to prevent having false alarms.
•
•
•
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
®
Occupied Time Period to begin. The S implicity
INTELLI-Comfort™ balances space temperature, venti-
lation air temperature, CO2 and humidity for ultimate
comfort.
STAINLESS STEEL HEAT EXCHANGER - For applica-
tions in corrosive environments, this option provides a
full stainless steel heat exchanger assembly.
®
•
S implicity INTELLI-Comfort™ with MOD LINK CON-
®
TROL - The York® S implicity INTELLI-Comfort™ with
Mod Link control is factory installed. It includes all the
features of the INTELLI-Comfort™ control with an addi-
tional control to translate communications from MOD-
BUS to the BACnet MSTP protocol.
STAINLESS STEEL DRAIN PAN - An optional rust-
proof stainless steel drain pan is available to provide
years of trouble-free operation in corrosive environ-
ments.
•
•
Novar® BAS CONTROL - The Novar® ETC-3 building
automation system controller is factory installed.
Includes supply air sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
•
BOTTOM DRAIN CONNECTION - An optional bottom
drain connection is available for inside the curb connec-
tions for applications in cold environments to reduce
freezing drain lines.
JOHNSON CONTROLS BAS CONTROL - The Johnson
Control YK-UNT-1126 building automation system con-
troller is factory installed. Includes supply air sensor,
return air sensor, dirty filter indicator switch, and air prov-
ing switch.
•
•
PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-of-
phase condition.
DIRTY FILTER SWITCH - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
•
CPC BAS CONTROL - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building auto-
mation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
•
HINGED FILTER DOOR/“TOOLLESS” BLOWER AND
ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance.
•
•
HONEYWELL BAS CONTROL - The Honeywell
W7750C building automation system controller is factory
installed. Includes air supply sensor, return air sensor,
dirty filter indicator switch, and air proving switch.
NOTE:Knobs are shipped inside the unit to prevent ship-
ping damage. These must be field installed for
tool-less operation.
SMOKE DETECTORS - (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
6
Unitary Products Group
254599-YTG-C-0807
tudes up to 6,000 feet. This accessory supplements the
basic propane conversion kit.
FIELD-INSTALLED ACCESSORIES
•
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa-
ble of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
•
•
LOW NOX KIT- Required to reduce the emission of
nitrogen oxides below 40 nanograms per joule.
POWER EXHAUST - Our single input economizer
options are available with power exhaust. Whenever the
outdoor air intake dampers are opened for free cooling,
the exhaust fan will be energized to prevent the condi-
tioned space from being over-pressurized during econo-
mizer operation.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
The power exhaust option can only be used on bot-
tom duct configurations.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
•
BAROMETRIC RELIEF DAMPER - This damper acces-
sory can be used to relieve internal building air pressure
on units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•
•
ELECTRIC HEATERS wired for single point power sup-
ply. These nickel chromium heater elements are pro-
vided with limit and automatic reset capability to prevent
operation at excessive temperatures.
•
ENTHALPY ACCESSORY CONTROL KIT - This kit
contains the required components to convert a single
enthalpy economizer to dual enthalpy.
•
•
BURGLAR BARS - Mount in the supply and return
openings to prevent entry into the duct work.
ROOF CURBS - Eight and fourteen-inch high roof curbs
provide a water-tight seal between the unit and the fin-
ished roof. These full perimeter curbs meet the require-
ments of the National Roofing Contractors Association
(NRCA) and are shipped knocked-down for field assem-
bly.
FLUE EXHAUST EXTENSION KIT - In locations with
wind or weather conditions which may interfere with
proper exhausting of furnace combustion products, this
kit can be installed to prevent the flue exhaust from
entering nearby fresh air intakes.
Roof curbs are designed to fit inside the base rails of the
unit and include both a wood nailing strip and duct
hanger supports.
•
CO SENSOR - Senses CO levels and automatically
2
2
overrides the economizer when levels rise above the
present limits.
•
•
•
HIGH ALTITUDE NATURAL GAS - Burner orifices and
pilot orifices are provided for proper furnace operation at
altitudes up to 6,000 feet.
•
•
•
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
PROPANE - Burner orifices, pilot orifices and gas valve
parts are provided to convert a natural gas furnace to
propane.
HAIL GUARD - Hail guard kit is available to prevent unit
from hail damage. This is a sloped hood that fits above
the coil.
HIGH ALTITUDE PROPANE - Burner orifices and pilot
orifices are provided for proper furnace operation at alti-
GAS PIPING KIT - This kit supplies all necessary fittings
and shut off valve.
Unitary Products Group
7
254599-YTG-C-0807
1
TABLE 1: SOUND POWER RATING
-12
SOUND POWER (db 10
Watts)
Octave Band Centerline Frequency (Hz)
ESP
BLOWER
UNIT
SIZE
dB(A)
@
10Ft.2
CFM
SWL
dB(A)
IWG SPEED
KW
63
125
250
500
1,000
2,000
4,000
8,000
55
072
2,200
0.3
HIGH
1.35
87
87
77
70
72
65
60
77
44
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran-
tee requiring a dBA value or sound data in any other form than sound power level ratings.
2. At a distance of 10 feet from the blower.
1
1
TABLE 2: CAPACITY RATINGS - (ARI 210/240)
TABLE 3: GAS HEAT RATINGS
EER2
MBH
INPUT
MBH
OUTPUT
AFUE
(%)
TEMP
RISE ºF
MODEL
DF072
MBH
MODEL
70.5
10.4
DF072N08
DF072N10
100
125
80
100
80.5
80.3
25 - 55
35 - 65
1. 80/67°F Indoor and 95°F outdoor.
2. EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).
1. All units are single-stage heating.
TABLE 4: 2 STAGE GAS HEAT RATINGS
MBH INPUT
MBH OUTPUT
STEADY STATE EFFICIENCY
RISE
MINIMUM HEATING
AIRFLOW (CFM)
MODEL1
1
ST STAGE 2ND STAGE 1ST STAGE 2ND STAGE 1ST STAGE
2ND STAGE
MIN. MAX.
45
75
75
35.8
60.4
60.8
79.4
80.5
81.1
35
45
70
75
1230
1230
DF072D06
DF072D10
125
100.6
80.5
1. Models are 3Ø only.
8
Unitary Products Group
254599-YTG-C-0807
TABLE 5: DF072 COOLING CAPACITIES (6 TON)
Temperature of Air on Condenser Coil
2
Return Air
Gross Sensible Capacity (MBh)
Return Air Dry Bulb (°F)
Gross Sensible Capacity (MBh)
Return Air Dry Bulb (°F)
Gross
Capacity
(MBh)
Power
Input
(kW)
Gross
Capacity
(MBh)
Power
Input
(kW)
WB
(°F)
CFM
2750
2475
2200
1925
1650
1
86
83
85°F
54.6 46.4 38.2 30.0 21.8
80
77
74
71
68
-
90
85
95°F
53.1 44.9 36.7 28.5 20.3
80
75
70
65
68
-
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
83.1
79.5
72.7
66.7
82.4
78.8
72.1
66.1
81.7
78.1
71.4
65.5
79.3
75.8
69.4
63.6
77
5.24
5.15
5.08
5.04
5.25
5.16
5.10
5.05
5.26
5.18
5.11
5.06
5.24
5.15
5.08
5.04
5.21
5.12
5.06
5.01
-
80.2
75.3
68.3
65.8
79.9
75.0
68.0
65.5
79.6
74.7
67.7
65.2
77.1
72.3
65.6
63.2
74.5
69.9
63.4
61.1
5.92
5.80
5.74
5.77
5.89
5.78
5.72
5.74
5.87
5.75
5.69
5.72
5.86
5.74
5.68
5.71
5.85
5.73
5.67
5.70
-
67.8 59.6 51.4 43.2 35.0 26.8 18.6
72.7 72.7 64.8 56.6 48.4 40.2 32.0
66.7 66.7 64.6 56.4 48.2 40.0 31.8
66.6 58.4 50.2 42.0 33.8 25.6 17.4
68.3 68.3 62.5 54.3 46.1 37.9 29.7
65.8 65.8 64.5 56.3 48.1 39.9 31.7
52.1 44.8 37.5 30.2 22.9
-
-
50.5 43.2 35.9 28.6 21.3
-
-
65.0 57.7 50.4 43.1 35.8 28.5 21.2
72.1 70.7 63.5 56.2 48.9 41.6 34.3
66.1 66.1 63.4 56.1 48.8 41.5 34.1
63.8 56.5 49.1 41.8 34.5 27.2 19.9
68.0 67.3 61.2 53.9 46.6 39.3 32.0
65.5 65.5 63.1 55.8 48.5 41.2 33.9
49.6 43.2 36.8 30.3 23.9
-
-
48.0 41.6 35.2 28.7 22.3
-
-
62.3 55.8 49.4 43.0 36.6 30.2 23.8
71.4 68.7 62.3 55.9 49.5 43.1 36.6
65.5 65.5 62.1 55.7 49.3 42.9 36.5
60.9 54.5 48.1 41.7 35.3 28.9 22.4
67.7 66.3 59.9 53.5 47.1 40.7 34.3
65.2 65.2 61.8 55.4 49.0 42.6 36.2
45.6 40.0 34.5 28.9 23.4
-
-
43.9 38.4 32.8 27.2 21.7
-
-
57.5 51.9 46.4 40.8 35.3 29.7 24.1
67.7 64.0 58.5 52.9 47.3 41.8 36.2
63.6 62.3 58.3 52.7 47.2 41.6 36.1
56.0 50.4 44.9 39.3 33.8 28.2 22.6
64.5 61.5 55.9 50.3 44.8 39.2 33.7
63.2 61.7 57.7 52.1 46.5 41.0 35.4
41.6 36.9 32.2 27.5 22.8
-
-
39.8 35.1 30.4 25.7 21.0
-
-
73.6
67.3
61.7
52.7 48.0 43.3 38.6 33.9 29.2 24.5
64.0 59.3 54.6 49.9 45.2 40.5 35.8
61.7 59.2 54.5 49.8 45.0 40.3 35.6
105°F
51.0 46.3 41.6 36.9 32.2 27.5 22.8
61.3 56.6 51.9 47.2 42.5 37.7 33.0
61.1 58.2 53.5 48.8 44.1 39.4 34.7
115°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
76.3
70.2
62.2
61.2
76.1
70.0
62.0
61.0
75.9
69.8
61.9
60.9
73.1
67.2
59.6
58.6
70.3
64.6
57.3
56.4
6.66
6.55
6.48
6.50
6.63
6.52
6.45
6.47
6.59
6.48
6.41
6.43
6.58
6.47
6.40
6.42
6.57
6.46
6.39
6.41
51.5 43.3 35.1 26.9 18.7
-
-
72.4
65.0
56.1
56.7
72.3
65.0
56.1
56.6
72.2
64.9
56.0
56.5
69.1
62.1
53.6
54.1
66.1
59.4
51.2
51.7
7.40
7.31
7.22
7.24
7.36
7.26
7.18
7.19
7.31
7.22
7.13
7.15
7.30
7.20
7.12
7.13
7.28
7.19
7.11
7.12
50.0 41.8 33.6 25.4 17.2
-
-
64.2 56.0 47.8 39.6 31.5 23.3 15.1
62.2 62.2 58.8 50.6 42.4 34.2 26.0
61.2 61.2 60.1 51.9 43.7 35.5 27.3
61.9 53.7 45.5 37.3 29.1 20.9 12.7
56.1 56.1 55.2 47.0 38.8 30.6 22.4
56.7 56.7 55.7 47.5 39.3 31.1 22.9
2750
2475
2200
1925
1650
49.0 41.7 34.3 27.0 19.7
-
-
47.4 40.1 32.8 25.5 18.2
-
-
61.4 54.1 46.8 39.5 32.2 24.9 17.6
62.0 61.7 57.5 50.2 42.9 35.6 28.3
61.0 61.0 58.8 51.5 44.2 36.9 29.5
59.1 51.7 44.4 37.1 29.8 22.5 15.2
56.1 56.1 53.9 46.6 39.2 31.9 24.6
56.6 56.6 54.4 47.1 39.8 32.5 25.2
46.4 40.0 33.6 27.2 20.7
-
-
44.8 38.4 32.0 25.6 19.2
-
-
58.6 52.2 45.7 39.3 32.9 26.5 20.1
61.9 61.2 56.2 49.8 43.4 37.0 30.6
60.9 60.9 57.5 51.0 44.6 38.2 31.8
56.2 49.8 43.4 37.0 30.5 24.1 17.7
56.0 56.0 52.6 46.2 39.7 33.3 26.9
56.5 56.5 53.1 46.7 40.3 33.9 27.4
42.3 36.7 31.1 25.6 20.0
-
-
40.6 35.0 29.5 23.9 18.4
-
-
53.5 48.0 42.4 36.9 31.3 25.7 20.2
59.1 57.0 52.2 46.6 41.0 35.5 29.9
58.6 57.3 53.3 47.7 42.2 36.6 31.0
51.1 45.5 40.0 34.4 28.8 23.3 17.7
53.6 52.5 48.4 42.9 37.3 31.7 26.2
54.1 53.0 48.9 43.3 37.8 32.2 26.7
38.1 33.4 28.7 24.0 19.3
-
-
36.4 31.7 26.9 22.2 17.5
-
-
48.5 43.8 39.1 34.4 29.7 25.0 20.3
56.3 52.8 48.1 43.4 38.7 34.0 29.2
56.4 53.8 49.1 44.4 39.7 35.0 30.3
45.9 41.2 36.5 31.8 27.1 22.4 17.7
51.2 49.0 44.3 39.6 34.9 30.2 25.5
51.7 49.4 44.7 40.0 35.3 30.6 25.9
1. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan
motor power input is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
2. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER
PERFORMANCE Table, multiply this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity
of the unit.
Nominal Rating
Unitary Products Group
9
254599-YTG-C-0807
TABLE 6: SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT DRIVE) - SIDE DUCT APPLICATION
Available External Static Pressure - IWG1
0.4 0.5 0.6
RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts
Unit
Air Flow
0.2
0.3
0.7
0.8
Tonnage (CFM)
2500
2400
2300
2200
2100
2000
1900
1800
1700
1600
1500
1059
1032
1005
980
930
877
-
-
-
-
-
1560
1405
1260
1160
1060
950
-
-
-
-
-
1077
1054
1024
1002
957
908
-
-
-
-
-
1590
1470
1275
1170
1070
975
-
-
-
-
-
1095
1074
1049
1022
983
941
894
855
-
1630
1525
1370
1190
1080
1000
885
815
-
1114
1094
1069
1044
1010
976
940
903
884
864
-
1650
1560
1440
1250
1100
1020
940
860
815
770
-
1134
1116
1090
1066
1039
1009
980
950
925
908
882
1660
1595
1475
1350
1160
1050
980
905
850
805
740
1158
1140
1116
1090
1064
1040
1014
988
1685
1620
1505
1410
1260
1100
1020
940
1181
1167
1142
1117
1092
1070
1047
1022
1001
987
1720
1640
1535
1440
1340
1225
1095
970
62,3
964
948
926
880
835
780
910
870
830
-
-
-
-
965
Available External Static Pressure - IWG1
1.1 1.2 1.3
RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts
Unit
Air Flow
0.9
1.0
1.4
1.5
Tonnage (CFM)
2500
2400
2300
2200
2100
2000
1900
1800
1700
1600
1500
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1193
1170
1148
1121
1100
1079
1058
1035
1020
1004
1665
1580
1480
1385
1285
1180
1060
960
1202
1180
1155
1133
1110
1090
1071
1056
1038
1620
1530
1425
1340
1240
1135
1030
965
1190
1169
1143
1122
1103
1088
1070
1475
1385
1280
1190
1100
1035
925
-
1205
1178
1158
1134
1118
1101
1445
1330
1240
1140
1065
980
-
-
1222
1196
1164
1145
1130
1375
1295
1175
1105
1045
1197
1170
1158
1205
1130
1075
-
-
900
860
1198
1184
1150
1110
880
1. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for resis-
tance values on applications other than gas / electric units with side duct airflows.
2. 230/460/575 Volts
3. For 208 Volts multiply values by 0.95.
TABLE 7: BELT DRIVE BLOWER MOTOR AND DRIVE DATA
BELT
(NOTCHED)
1
ADJUSTABLE MOTOR PULLEY
FIXED BLOWER PULLEY
OUTSIDE PITCH
MOTOR
BLOWER
RANGE
(RPM)
MODEL
SIZE
OUTSIDE
DIA.
PITCH
DIA.
PITCH
LENGTH QTY.
(IN.)
DESIG-
NATION
BORE DESIG-
(IN.)
BORE DESIG-
HP FRAME
DIA.
(IN.)
DIA.
(IN.)
NATION
(IN.)
NATION
(IN.)
(IN.)
6 TON
850/1220 1 1/2
56
1VL40
2.7-3.7
2.4-3.4
5/8
AK56
5.4
5.2
1
A36
37.3
1
1. All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located
in the moving air, upstream of any heating device.
10
Unitary Products Group
254599-YTG-C-0807
TABLE 8: SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT DRIVE) - SIDE DUCT APPLICATION
Available External Static Pressure - IWG1
Unit
Motor
0.2
0.3
0.4
0.5
0.6
Tonnage Speed
CFM
2256
2145
2020
-
Watts
883
771
637
-
CFM
2258
2127
1999
-
Watts
931
784
656
-
CFM
2247
2119
1985
-
Watts
950
808
675
-
CFM
2223
2089
1947
-
Watts
964
826
696
-
CFM
2182
2051
1910
-
Watts
979
844
715
-
Hi
Med/Hi
62
Med
Med/Low
Low
-
-
-
-
-
-
-
-
-
-
Available External Static Pressure - IWG1
0.8 0.9
Unit
Motor
0.7
1.0
Tonnage Speed
CFM
2125
2014
1876
-
Watts
971
859
730
-
CFM
2044
1965
1832
-
Watts
940
861
740
-
CFM
1958
1896
1793
-
Watts
898
843
756
-
CFM
Watts
Hi
1864
854
Med/Hi
1801
806
62
Med
Med/Low
Low
-
-
-
-
-
-
-
-
-
-
-
-
1. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES
Table for resistance values.
2. Side Duct application (230 Volts)
TABLE 9: STATIC RESISTANCES
RESISTANCE, IWG
DESCRIPTION
CFM
1000
0.07
0.04
0.06
0.06
0.08
1200
0.08
0.05
0.07
0.07
0.10
1400
0.09
0.06
0.08
0.08
0.12
1600
0.11
0.07
0.09
0.09
0.14
1800
0.13
0.08
0.11
0.10
0.16
2000
0.15
0.10
0.13
0.11
0.18
2200
0.17
0.12
0.15
0.12
0.20
2400
0.20
0.14
0.17
0.14
0.23
2600
0.23
0.16
0.20
0.16
0.26
2800
0.26
0.19
0.23
0.19
0.29
3000
0.30
0.22
0.26
0.22
0.32
ECONOMIZER1 3
ELECTRIC
7-15KW
20-30KW
HEATERS1
BOTTOM DUCT CONNECTIONS1
COOLING ONLY2
1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.
2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.
3. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
TABLE 10: ELECTRIC HEATER CFM LIMITATIONS
MINIMUM SUPPLY AIR CFM
UNIT MODEL SIZE NOMI-
VOLTAGE
HEATER SIZE NOMINAL KW
NAL TONS
5
7
10
15
20
30
208/230-3-60
460-3-60
1800
1800
1800
-
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
6
-
-
575-3-60
Unitary Products Group
11
254599-YTG-C-0807
TABLE 11: ELECTRICAL DATA - DF072 BELT DRIVE W/O POWERED CONV. OUTLET
COMPRESSORS
ID
MIN.
MAX. FUSE/
BRKR
SIZE
(AMPS)
45
OD FAN
MOTOR
FLA
CONV
OUTLET
FLA
1
MODEL
TONNAGE
BLOWER
MOTOR
FLA
ELECTRIC HEATER HEATER HEATER CIRCUIT
VOLTAGE
RLA
LRA
MODEL NO.
KW
AMPS
AMPACITY
(AMPS)
33.4
33.4
33.4
34.3
47.8
61.7
83.5
33.4
33.4
33.4
38.4
54.3
70.2
95.5
16.4
16.4
18.4
23.7
32.6
46.6
13.3
15.2
21.6
28
EACH
EACH
None
2CE04510525
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
None
-
4
-
2
2
11.1
15.5
22.2
33.0
44.1
61.6
-
12.7
18.0
25.5
38.2
51.0
71.2
-
45
45
45
50
70
90
45
45
45
50
60
80
100
25
25
25
25
35
50
20
20
25
30
40
5.6
8
11.9
15.9
22.2
-
5.3
7.5
10.6
15.9
21.2
29.6
-
6.8
10.1
13.6
19.5
28.8
-
208-3-60
20.7
20.7
156.0
156.0
2.3
2.3
5.2
5.2
0.0
0.0
2
2CE04510525
2CE04510725
2
230-3-60
2CE04511025
2CE04511525
2CE04512025
2CE04513025
None
2CE04510746
2CE04511046
2CE04511546
2CE04512046
2CE04513046
None
DF072
(6.0)
2
8.2
2
2
2
2
12.1
16.4
23.5
34.6
-
10.2
15.3
20.4
29.3
460-3-60
575-3-60
10.0
8.2
75.0
54.0
1.3
1.3
2.6
2.0
0.0
0.0
2CE04511058
2CE04511558
2CE04512058
2CE04513058
10.6
15.9
21.2
30.4
39.1
1. HACR Type per NEC.
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block
accessories 2FB04700825 and 2FB04700846 are available for field installation.
TABLE 12: ELECTRICAL DATA - DF072 DIRECT DRIVE W/O POWERED CONV. OUTLET
COMPRESSORS
ID
MIN.
MAX. FUSE/
BRKR
SIZE
(AMPS)
50
OD FAN
MOTOR
FLA
CONV
OUTLET
FLA
1
MODEL
TONNAGE
BLOWER
MOTOR
FLA
ELECTRIC HEATER HEATER HEATER CIRCUIT
VOLTAGE
RLA
LRA
MODEL NO.
KW
AMPS
AMPACITY
(AMPS)
38.8
EACH
EACH
None
2CE04510525
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
None
2CE04510525
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
-
-
2
2
4.0
5.6
8.0
11.9
15.9
22.2
-
5.3
7.5
10.6
15.9
21.2
29.6
11.1
15.5
22.2
33.0
44.1
61.6
-
12.7
18.0
25.5
38.2
51.0
71.2
38.8
38.8
41.0
54.5
68.4
90.3
38.8
38.8
38.8
45.1
61.1
77.0
102.3
50
50
50
60
70
100
50
50
50
50
208-3-60
20.7
20.7
156.0
156.0
2.3
2.3
10.6
10.6
0.0
0.0
DF072
(6.0)
2
2
230-3-60
70
80
110
1. HACR Type per NEC.
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block
accessories 2FB04700825 and 2FB04700846 are available for field installation.
12
Unitary Products Group
254599-YTG-C-0807
TABLE 13: ELECTRICAL DATA - DF072 BELT DRIVE W/POWERED CONV. OUTLET
COMPRESSORS
ID
MIN.
MAX. FUSE/
BRKR
SIZE
(AMPS)
60
OD FAN
MOTOR
FLA
CONV
OUTLET
FLA
1
MODEL
TONNAGE
BLOWER
MOTOR
FLA
ELECTRIC HEATER HEATER HEATER CIRCUIT
VOLTAGE
RLA
LRA
MODEL NO.
KW
AMPS
AMPACITY
(AMPS)
43.4
43.4
43.4
46.8
60.3
74.2
96
EACH
EACH
None
2CE04510525
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
None
-
4
-
2
2
11.1
15.5
22.2
33.0
44.1
61.6
-
12.7
18.0
25.5
38.2
51.0
71.2
-
60
60
60
70
80
100
60
60
60
60
70
90
110
30
30
30
30
40
5.6
8
11.9
15.9
22.2
-
5.3
7.5
10.6
15.9
21.2
29.6
-
6.8
10.1
13.6
19.5
28.8
-
208-3-60
20.7
20.7
156.0
156.0
2.3
2.3
5.2
5.2
10.0
10.0
43.4
43.4
43.4
50.9
66.8
82.7
108
21.4
21.4
24.7
29.9
38.8
52.8
17.3
20.2
26.6
33
2
2CE04510525
2CE04510725
2
230-3-60
2CE04511025
2CE04511525
2CE04512025
2CE04513025
None
2CE04510746
2CE04511046
2CE04511546
2CE04512046
2CE04513046
None
DF072
(6.0)
2
8.2
2
2
2
2
12.1
16.4
23.5
34.6
-
10.2
15.3
20.4
29.3
460-3-60
575-3-60
10.0
8.2
75.0
54.0
1.3
1.3
2.6
2.0
5.0
4.0
60
25
25
30
35
45
2CE04511058
2CE04511558
2CE04512058
2CE04513058
10.6
15.9
21.2
30.4
44.1
1. HACR Type per NEC.
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block
accessories 2FB04700825 and 2FB04700846 are available for field installation.
TABLE 14: ELECTRICAL DATA - DF072 DIRECT DRIVE W/POWERED CONV. OUTLET
COMPRESSORS
ID
MIN.
MAX. FUSE/
BRKR
SIZE
(AMPS)
60
OD FAN
MOTOR
FLA
CONV
OUTLET
FLA
1
MODEL
TONNAGE
BLOWER
MOTOR
FLA
ELECTRIC HEATER HEATER HEATER CIRCUIT
VOLTAGE
RLA
LRA
MODEL NO.
KW
AMPS
AMPACITY
(AMPS)
48.8
EACH
EACH
None
2CE04510525
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
None
2CE04510525
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
-
-
2
2
4.0
5.6
8.0
11.9
15.9
22.2
-
5.3
7.5
10.6
15.9
21.2
29.6
11.1
15.5
22.2
33.0
44.1
61.6
-
12.7
18.0
25.5
38.2
51.0
71.2
48.8
48.8
53.5
67.0
80.9
102.8
48.8
48.8
48.8
57.6
73.6
89.5
114.8
60
60
60
70
90
110
60
60
60
60
208-3-60
20.7
20.7
156.0
156.0
2.3
2.3
10.6
10.6
10.0
10.0
DF072
(6.0)
2
2
230-3-60
80
90
125
1. HACR Type per NEC.
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block
accessories 2FB04700825 and 2FB04700846 are available for field installation.
Unitary Products Group
13
254599-YTG-C-0807
TABLE 15: DF PHYSICAL DATA
DF
072
12 X 10
1
MODELS
Centrifugal Blower (Dia. x Wd. in.)
EVAPORATOR
BLOWER
Fan Motor HP (Direct Drive)
Fan Motor HP (Belt Drive)
Rows Deep
1 1/2
4
EVAPORATOR
COIL
Fins Per Inch
13
Face Area (Sq. Ft.)
Propeller Dia. (in.)
Fan Motor Hp
5.1
24
CONDENSER
FANS
1/2
Nom. CFM
4200
2
Rows Deep
CONDENSER
COILS
Fins Per Inch
18
Face Area (Sq. Ft.)
17.1
COMPRESSOR
(Qty. Per Unit)
Recip Type
1
Quantity Per Unit (15” X 20” X 1” or 2“)
Quantity Per Unit (14” X 25” X 1” or 2“)
Total Face Area (sq. ft.)
2
1
AIR
FILTERS
6.3
Refrigerant 22
(lbs./oz.)
CHARGE
11/10
1
TABLE 16: ELECTRIC HEAT CORRECTION FACTORS
TABLE 17: VOLTAGE LIMITATIONS
NOMINAL VOLTAGE
VOLTAGE
kW CAP. MULTIPLIER
VOLTAGE
POWER SUPPLY
MIN.
187
432
540
MAX.
252
208
230
460
575
0.75
0.92
0.92
0.92
208
240
480
600
208/230-3-60
460-3-60
504
575-3-60
630
1. Utilization Range “A” in accordance with ARI Standard
110.
14
Unitary Products Group
254599-YTG-C-0807
TYPICAL POWER WIRING
REFER TO THE ELECTRICAL DATA
TABLES TO SIZE THE DISCONNECT
SWITCH, OVERCURRENT PROTEC-
TION AND WIRING.
TYPICAL CONTROL WIRING
COOLING / HEATING (24 VOLT THERMOSTAT)
COOLING ONLY (24 VOLT THERMOSTAT)
THERMOSTAT1
TERMINALS
THERMOSTAT1 UNIT TERMINAL
TERMINALS
STRIP TB1
UNIT TERMINAL
STRIP TB1
RH
ADD
JUMPER
RV
R
RC
Y
R
Y1
Y2
W1
W2
G
24 VOLT
TRANSFORMER
YC
GF
Y1
Y2
G
24 VOLT
TRANSFORMER
W
G
C
C
124 VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZER
ON SECOND STAGE COOLING, USE THE THERMOSTAT 2TH0401224.
1
24 VOLT THERMOSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECOND
STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF
HEAT, USE THERMOSTAT 2TH0471024.
COOLING / HEATING (ELECTRONIC THERMOSTAT)
MULTI STAGE
1
COOLING / HEATING (ELECTRONIC THERMOSTAT)
SINGLE STAGE
THERMOSTAT
TERMINALS
UNIT TERMINAL
STRIP TB1
RC
RH
Y1
24 VOLT
TRANSFORMER
ADD
JUMPER
R
Y1
Y2
W1
W2
G
THERMOSTAT1
2
3
Y2
UNIT TERMINAL
STRIP TB1
TERMINALS
W1
4
W2
RH
RC
Y
G
B
R
Y1
W1
G
C
ADD
JUMPER
LED 1
X
NOT
USED
LED 2
COM
A1
OCC
W
4
G
ADD
JUMPER
A2
C
T
TO REMOTE SENSOR
2TH040702224 IF USED
T
24 VOLT
TRANSFORMER
1 ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 (INCLUDES SUBBASE).
2 SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.
1ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET07701024 (INCLUDES SUBBASE).
TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT
2TH04700224.
3 SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE
ELECTRIC HEATER OR 2 STAGE GAS HEAT.
4
REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR
P6 ON UNITS WITH ECONOMIZER. TERMINALS A1 AND A2 PROVIDE A RELAY
OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE
THERMOSTAT SWITCHES TO THE SET-BACK POSITION.
FIGURE 2 - TYPICAL FIELD POWER & CONTROL WIRING
Unitary Products Group
15
254599-YTG-C-0807
FIGURE 7 - UNIT DIMENSIONS (REAR VIEW)
TABLE 18: UTILITIES ENTRY
FILTER
ACCESS
HOLE
A
OPENING SIZE (DIA.)
USED FOR
BLOWER MOTOR
ACCESS
Side
1
2
7/8” KO
Control Wiring
Bottom
Side
DOT PLUGS
B
Power Wiring
2” KO
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
Bottom
C
D
1-5/8” KO
1-1/2” KO
Gas Piping (Front)
MOUNTING BRACKET
FOR DICONNECT SWITCH
(Shipped attached to the
blower housing inside
Gas Piping (Bottom)
A,B
the blower compartment)
1. Opening in the bottom to the unit can be located by the
side in the insulation.
2. Do not remove the 2” knockout ring.
WIRING ENTRY
(See Detail “B”)
CONTROL BOX
ACCESS
DISCONNECT SWITCH LOCATION
AND MOTOR ACCESS PANEL FOR
UNIT WITH “BELT-DRIVE” OPTION
FIGURE 8 - DISCONNECT/BLOWER ACCESS
LOCATION
TABLE 19: MINIMUM CLEARANCES
CLEARANCE
LOCATION
Front
24” (Cooling/Electric Heat)
32” (Gas Heat)
12” (Less Economizer)
36” (With Economizer or Fixed Air/
Motorized Damper)
Rear
24” (Less Economizer)
36” (With Economizer)
Left Side (Filter Access)
Right Side (Cond. Coil)
Below Unit1
24”
0”
72” (For
Condenser Air Discharge)
Above Unit2
1. Units may be installed on combustible floors made
from wood or class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging struc-
tures or shrubs should not obstruct condenser air dis-
charge outlet.
18
Unitary Products Group
254599-YTG-C-0807
BACK OF UNIT
BACK OF UNIT
A
A
7
7
44 /8
44 /8
1
1
82 /4
82 /4
B
D
F
X
X
B
C
E
APPROXIMATE
APPROXIMATE
CENTER OF GRAVITY
CENTER OF GRAVITY
CONDENSER COIL
END OF UNIT
CONDENSER COIL
END OF UNIT
C
D
FRONT OF UNIT
FRONT OF UNIT
Y
Y
FIGURE 10 - FOUR AND SIX POINT LOADING
TABLE 20: DF 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION
4-Point Loading (lb)
6-Point Loading (lb)
UNIT
TOTAL
A
B
C
D
A
B
C
D
E
F
147
158
160
162
144
155
157
159
183
197
200
202
186
201
203
206
98
97
96
122
131
133
135
123
132
134
136
125
134
136
138
DF072 Cooling/ Electric
DF072D06
660
710
720
730
105
107
108
104
106
107
103
104
106
DF072N08
DF072(D,N)10
TABLE 21: CENTER OF GRAVITY
3 - 5 TON
40-¾”
6 TON
44”
DIMENSION
X
Y
19-¾”
22”
TABLE 22: DF OPERATING WEIGHTS (LBS.)
MODEL SIZE
6 TON
660
-
DF (Cooling Only)
N04
N06
N08
N10
D06
D10
-
BASIC
UNIT
720
730
760
730
50
DF
(Gas/Electric)
Economizer
Motorized Damper
26
OPTIONS
ACCY.
5 - 7 kW
10 - 15 kW
20 - 30 kW
18
Electric Heater
23
28
Roof Curb
92
Barometric Relief / Fixed Air Damper
Belt-Drive Blower
10
5
20
Unitary Products Group
254599-YTG-C-0807
FIGURE 11 - ROOF CURB DIMENSIONS
with a compressor lockout circuit, a terminal strip for thermo-
stat wiring, plus an additional set of pin connectors to simplify
the interface of additional field controls. All units have long
lasting powder paint cabinets with 1000 hour salt spray test
approval under ASTMB117 procedures. All models are CSA
listed. All models include a 1-year limited warranty on the
complete unit. Compressors and electric heater elements
carry a 5-year warranty. Aluminized steel and Stainless steel
tubular heat exchangers carry a 10-year warranty.
GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility.
TM
York's Sunline Plus units are convertible single package
units. Although the units are primarily designed for curb mount-
ing on a roof, they can also be slab-mounted at ground level or
set on steel beams above a finished roof. Cooling only, cooling
with gas heat and cooling with electric heat models are available
with a wide variety of factory-mounted options and field-installed
accessories to make them suitable for almost every application.
All units are self-contained and assembled on full perimeter
base rails with holes in the four corners for overhead rigging.
Every unit is completely piped, wired, charged and tested at the
factory to simplify the field installation and to provide years of
dependable operation. All models (including those with an econ-
omizer) are suitable for either bottom or horizontal duct connec-
tions. Models with power exhaust are suitable for bottom duct
connections only. For bottom duct, remove the sheet metal pan-
els from the supply and return air openings through the base of
the unit. For horizontal duct, remove the supply and return air
panels on the rear of the unit.
DESCRIPTION
Units shall be factory-assembled, single packaged, Electric
Cooling/Gas Heat, Electric Cooling/Optional Electric Heat
and designed for outdoor mounted installation.
The 6 ton unit is rated at 10.4 EER. They shall have built-in
field convertible duct connections for down discharge supply/
return or horizontal discharge supply/return, and be available
with factory installed options or field installed accessories. The
units shall be factory wired, piped, charged with R-22 refriger-
ant and factory tested prior to shipment. All unit wiring shall be
both numbered and color coded. All units the cooling perfor-
mance shall be rated in accordance with DOE and ARI test
procedures. Units shall be CSA listed, classified to ANSI
Z21.47, UL 1995/CSA No. 236 standards.
All compressors include crankcase heaters and all compres-
sors have internal pressure relief. Every refrigerant circuit
includes a liquid line filter-drier, a discharge line high pres-
sure switch and a suction line with a freezestat and low pres-
sure/loss of charge switch.The unit control circuit includes a
75 VA transformer, a 24-volt circuit breaker and a relay board
UNIT CABINET
Unit cabinet shall be constructed of G90 galvanized steel,
with exterior surfaces coated with a non-chalking, powdered
paint finish, certified at 1000 hours salt spray test per
ASTMB117 standards. Indoor blower section shall be
Unitary Products Group
21
254599-YTG-C-0807
insulated with a minimum 1/2” thick insulation, coated on the
airside. Aluminum foil faced insulation shall be used in the
furnace compartment and be fastened with ridged fasteners
to prevent insulation from entering the air stream. Cabinet
panels shall be “large” size, easily removable for servicing
and maintenance. Full perimeter base rails shall be provided
to assure reliable transit of equipment, overhead rigging and
proper sealing on roof curb applications. Disposable 1" filters
shall be furnished and be accessible through a removable
access door, sealed airtight. Units filter track shall be
designed to accommodate either 1” or 2” filters. Fan
performance measuring ports shall be provided on the
outside of the cabinet to allow accurate air measurements of
evaporator fan performance without removing panels or
creating air by-pass of the coils. Condensate pan shall be
internally sloped and conform to ASHRAE 62-89 self-draining
standards. Condensate connection shall be a minimum of 3/
4” I.D. female and be a ridged mount connection.
b. Evaporator and Condenser coils shall be of the
direct expansion, draw-thru, design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Thermal expansion devices (TXV’s).
• DF072 uses a fixed orifice distributor.
b. Filter drier/strainer to eliminate any moisture or for-
eign matter.
c. Accessible service gage connections on both suc-
tion and liquid lines to charge, evacuate, and mea-
sure refrigerant pressure during any necessary
servicing or troubleshooting without losing charge.
d. The refrigeration system shall provide at least 15°F
of sub-cooling at design conditions.
UNIT CONTROLS
a. Unit shall be complete with self-contained low-volt-
age control circuit protected by a resetable circuit
breaker on the 24-volt transformer side.
INDOOR (EVAPORATOR) FAN ASSEMBLY
The indoor fan shall be direct drive, multi-speed, or a factory
installed belt drive assembly that includes an adjustable pitch
motor pulley. Job site selected brake horsepower (B.H.P.)
shall not exceed the motors nameplate horsepower rating,
plus the service factor. Units shall be designed not to operate
above service factor. Fan wheel shall be double-inlet type
with forward-curved blades, dynamically balanced to operate
smoothly throughout the entire range of operation. Airflow
design shall be constant air volume. Bearings shall be sealed
and permanently lubricated for longer life and no mainte-
nance.
b. Unit shall incorporate a lockout circuit which pro-
vides reset capability at the space thermostat or
base unit, should any of the following standard
safety devices trip and shut off compressor.
c. Loss-of-charge/Low-pressure switch.
d. High-pressure switch.
e. Freeze-protection thermostat, evaporator coil.
f. If any of the above safety devices trip, a LED (light-
emitting diode) indicator shall flash a diagnostic
code that indicates which safety switch has tripped.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fan shall be of the direct-driven propeller type,
discharge air vertically, have aluminum blades riveted to a
corrosion resistant steel spider bracket and shall be dynami-
cally balanced for smooth operation. The outdoor fan motor
shall be totally enclosed with permanently lubricated bear-
ings, internally protected against overload conditions and
staged independently.
g. Unit shall incorporate “AUTO RESET” compressor
over temperature, over current protection.
h. Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for
easy hook-up.
i.
Unit control board shall have on-board diagnostics
and fault code display.
REFRIGERANT COMPONENTS
j.
Standard controls shall include anti-short cycle and
low voltage protection, and permit cooling operation
down to 0°F.
Compressor:
a. Shall be internally protected with internal high-pres-
sure relief and over temperature protection.
k. Control board shall monitor each refrigerant safety
switch independently.
b. Shall have internal spring isolation and sound muf-
fling to minimize vibration and noise, and be exter-
nally isolated on a dedicated, independent
mounting.
l.
Control board shall retain last 5 fault codes in non
volatile memory, which will not be lost in the event of
a power loss.
Coils:
GAS HEATING SECTION (SINGLE OR 2 STAGE)
a. Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless
internally enhanced copper tubes with all joints
brazed. Special Phenolic coating shall be available
as a factory option.
Shall be designed with induced draft combustion with post
purge logic, energy saving direct spark ignition, and redun-
dant main gas valve. Venter wheel shall be constructed of
stainless steel for corrosion resistance. The heat exchanger
shall be of the tubular type, constructed of T1-40 aluminized
22
Unitary Products Group
254599-YTG-C-0807
steel for corrosion resistance and allowing minimum mixed
air entering temperature of 25°F. Burners shall be of the
inshot type, constructed of aluminum coated steel and con-
tain air mixture adjustments. All gas piping shall enter the unit
cabinet at a single location through either the side or curb,
without any field modifications. Integrated control boards
shall provide timed control of evaporator fan functioning and
burner ignition. Heating section shall be provided with the fol-
lowing minimum protection:
•
ELECTRONIC ENTHALPY AUTOMATIC ECONO-
MIZER- Outdoor and return air dampers that are inter-
locked and positioned by a fully-modulating, spring
return damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit-mounted potenti-
ometer shall be provided to adjust the outdoor and return
air damper assembly to take in CFM of outdoor air to
meet the minimum ventilation requirement of the condi-
tioned space during normal operation. During econo-
mizer operation, a mixed-air temperature control shall
modulate the outdoor and return air damper assembly to
prevent the supply air temperature from dropping below
55°F. Changeover from compressor to economizer oper-
ation shall be provided by an integral electronic enthalpy
control that feeds input into the basic module. The out-
door intake opening shall be covered with a rain hood
that matches the exterior of the unit. Water eliminator/fil-
ters shall be provided. Simultaneous economizer/com-
pressor operation is also possible. Dampers shall fully
close on power loss.
a. Primary and auxiliary high-temperature limit switches.
b. Induced draft motor speed sensor.
c. Flame roll out switch.
d. Flame proving controls.
e. If any of the above safety devices trip, a LED (light-
emitting diode) indicator shall flash a diagnostic
code that indicates which safety switch has tripped.
ELECTRIC HEATING SECTION
An electric heating section, with nickel chromium elements,
shall be provided in a range of 5 thru 30 KW, offering two
stages of capacity - 16 KW and above on 208/230 volt heaters
and 20 KW and above on 460 and 575 volt heaters. The heat-
ing section shall have a primary limit control(s) and automatic
reset to prevent the heating element system from operating at
an excessive temperature. The heating section assembly
shall slide out of the unit for easy maintenance and service.
Units with Electric Heating shall be wired for a single point
power supply with branch circuit fusing (where required).
•
MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air
dampers are positioned by a 2-position, spring-return
damper actuator. The maximum leakage rate for the out-
door air intake dampers shall not exceed 2% when
dampers are fully closed and operating against a pres-
sure differential of 0.5 IWG. A unit-mounted potentiome-
ter shall be provided to adjust the outdoor damper
assembly to take in the design CFM of outdoor air to
meet the ventilation requirements of the conditioned
space during normal operation. Whenever the indoor fan
motor is energized, the dampers open up to one of two
pre-selected positions - regardless of the outdoor air
enthalpy. Dampers return to the fully closed position
when the indoor fan motor is de-energized. Dampers
shall fully close on power loss.
UNIT OPERATING CHARACTERISTICS
a. Unit shall be capable of starting and running at 125°F
outdoor temperature, exceeding maximum load crite-
ria of ARI Standard 210/240. The compressor, with
standard controls, shall be capable of operation down
to 0°F outdoor temperature. Unit shall be provided
with fan time delay to prevent cold air delivery before
heat exchanger warms up (Gas heat only).
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
•
ROOF CURB - 14"and 8” high, full perimeter curb with
wood nailer (shipped knocked-down).
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory
provided location and be capable of side or bottom entry, to
minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the
control wiring.
•
BAROMETRIC RELIEF DAMPER - Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit.
•
•
•
•
PROPANE CONVERSION KIT - Contains new orifices
and gas valve parts to convert from natural to L.P. gas.
One per unit required.
STANDARD LIMITED WARRANTIES
•
•
•
•
Compressor 5 Years
HIGH ALTITUDE - NATURAL GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude.
Heat Exchanger 10 Years
Electric Heat Element 5 Years
Other Parts 1 Year
HIGH ALTITUDE - PROPANE GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude. Must be used with propane conversion kit.
OPTIONAL OUTDOOR AIR (Shall be made available by
either/or):
LOW NOX - Required to reduce the emission of nitrogen
oxides below 40 nanograms per joule.
Unitary Products Group
23
•
•
GAS PIPING - Contains 1/2” pipe nipples, fittings and
gas cock (including panel assess gaskets) required for
bottom gas supply connection with external shut off.
•
TECHNICOAT PHENOLIC COATED CONDENSER
AND EVAPORATOR COIL
•
•
•
•
•
•
•
ELECTRONIC SINGLE ENTHALPY ECONOMIZER
DIRTY FILTER SWITCH
POWER EXHAUST OPTION - To work in conjunction
with economizers.
PHASE MONITOR
•
ELECTRIC HEATERS
COIL GUARD
•
ECONOMIZER/MOTORIZED DAMPER RAIN HOOD -
Contains all hood panels and the hardware for assem-
bling.
POWERED GFI CONVENIENCE OUTLET
NON-POWERED GFI CONVENIENCE OUTLET
•
•
•
•
MANUAL OUTDOOR AIR DAMPER
COIL GUARD KIT - Guard for cooling coil.
HAIL GUARD
®
BAS CONTROLS (S implicity INTELLI- Comfort™,
CPC, JOHNSON, HONEYWELL, NOVAR)
•
•
BAS READY ECONOMIZER (2 - 10 V. D. C.
ACTUATOR WITHOUT A CONTROLLER)
FLUE EXHAUST EXTENSION
HINGED FILTER DOOR ACCESS AND TOOLESS
ACCESS PANELS
OTHER FACTORY INSTALLED OPTIONS
•
POWER EXHAUST OPTION - To work in conjunction
with economizers.
•
•
•
•
2" PLEATED FILTERS
DISCONNECT SWITCH
•
•
•
STAINLESS STEEL HEAT EXCHANGER
STAINLESS STEEL DRAIN PAN
BOTTOM DRAIN CONNECTION
SUPPLY AIR SMOKE DETECTOR
RETURN AIR SMOKE DETECTOR
Subject to change without notice. Printed in U.S.A.
254599-YTG-C-0807
Copyright © 2007 by Unitary Products Group. All rights reserved.
Supersedes: 254599-YTG-B-0507
Unitary
Products
Group
5005
York
Drive
Norman
OK
73069
|