York Df 072 User Manual

254599-YTG-C-0807  
®
DESCRIPTION  
®
YORK Sunline Plus™ units are convertible single package  
air conditioners. The units were designed for light commercial  
and commercial applications. They can easily be installed on  
a roof curb, slab, roof jack or frame.  
TECHNICAL GUIDE  
SINGLE PACKAGE GAS/ELECTRIC UNITS  
AND SINGLE PACKAGE  
All units include:  
Powder Paint finish that meets ASTM-B-117 1000 hour  
salt spray standards  
AIR CONDITIONERS  
Permanently lubricated motors  
DF 072  
6 NOMINAL TONS  
10.4 EER  
Bottom or side air discharge configuration capability  
(field convertible)  
Manufactured under the quality standards of ISO9001  
®
S implicity Control Board  
Copper tube/aluminum fin coils  
Easy access to all components  
Rigging holes in base rails for lifting  
Fork lift slots on three sides  
Single point power connection  
Complete factory package - tested, charged and wired  
CSA agency listing on all units  
WARRANTY  
Factory Limited Parts Warranty  
One-year parts warranty  
A Five-year parts warranty on the compressor and  
electric heat elements.  
Ten-year parts warranty on the gas-fired heat  
exchangers.  
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE  
 
254599-YTG-C-0807  
PRODUCT NOMENCLATURE  
6 Ton Sunline Model Number Nomenclature  
D F 072 N04 A 2 A AA 1 0 1 2 4 A  
Product Category  
Product Style  
D = A/C, Single Pkg., R-22  
A = Style A  
Product Identifier  
F = 10.4 EER A/C  
Configuration Options (not required for all units)  
These four digits will not be assigned until a quote is requested, or an order placed.  
SS Drain Pan  
CPC Controller, DFS, APS  
Nominal Cooling Capacity  
Johnson Controller, DFS, APS  
Honeywell Controller, DFS, APS  
072 = 6.0 Ton  
Novar Controller, DFS, APS  
Simplicity IntelliComfort Controller  
Heat Type and Nominal Heat Capacity  
Simplicity IntelliComfort Controller w/ModLinc  
2" Pleated filters  
C00 = Cooling Only. Suitable for Field  
Installed Electric Heat  
BAS Ready Economizer (2-10 V. D. C. Actuator without a Controller)  
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned  
Gas Heat Options  
Product Generation  
N08 = 80 MBH Output Aluminized Steel, 1 Stage  
(072)  
1 = First Generation  
2 = Second Generation  
N10 = 100 MBH Output Aluminized Steel, 1 Stage  
(072)  
D06 = 60 MBH Output Aluminized Steel, 2 Stage  
(072)  
Additional Options  
Hinged Filter Door & Toolless Access Cabinet  
D10 = 100 MBH Output Aluminized Steel, 2 Stage  
(072)  
S08 = 80 MBH Output Stainless Steel, 1 Stage  
Standard Cabinet  
(072)  
S10 = 100 MBH Output Stainless Steel, 1 Stage  
AA = None  
BA = Hinged Filter Door & Toolless Access Panels  
BA = Hinged Filter Door & Toolless Access Panels  
BB = Phase Monitor, Hinged Filter Door & Toolless  
Access Panels  
BC = Coil Guard, Hinged Filter Door & Toolless  
Access Panels  
BD = Dirty Filter Switch, Hinged Filter Door &  
Toolless Access Panels  
BE = Phase Monitor & Coil Guard, Hinged Filter  
Door & Toolless Access Panels  
BF = Phase Monitor & Dirty Filter Switch, Hinged  
Filter Door & Toolless Access Panels  
BG = Coil Guard & Dirty Filter Switch, Hinged Filter  
Door & Toolless Access Panels  
(072)  
AB = Phase Monitor  
T06 = 60 MBH Output Stainless Steel, 2 Stage  
AC = Coil Guard  
(072)  
AD = Dirty Filter Switch  
T10 = 100 MBH Output Stainless Steel, 2 Stage  
(072)  
AE = Phase Monitor & Coil Guard  
AF = Phase Monitor & Dirty Filter Switch  
AG = Coil Guard & Dirty Filter Switch  
AH = Phase Monitor, Coil Guard & Dirty Filter Switch  
AS = Bottom Drain Connection  
RC = Coil Guard & American Flag  
TA = Technicoat Condenser Coil  
TJ = Technicoat Evaporator Coil  
TS = Technicoat Evaporator and Condenser Coil  
Electric Heat Options  
E05 = 5 KW  
E07 = 7 KW  
E10 = 10 KW  
E15 = 15 KW  
E20 = 20 KW  
E30 = 30 KW  
BH = Phase Monitor, Coil Guard & Dirty Filter Switch,  
Hinged Filter Door & Toolless Access Panels  
*(D, T) 10 = 92 MBH Output on 036 Models  
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be  
located in digits 15-18.  
Airflow  
A = Direct Drive  
B = Direct Drive/Single Input Economizer  
D = Direct Drive/Motorized Damper  
N = Belt Drive  
P = Belt Drive/Single Input Economizer  
R = Belt Drive/Motorized Damper  
Installation Options  
A = No Options Installed  
B = Option 1  
C = Option 2  
D = Options 1 & 2  
E = Option 3  
Voltage  
F = Option 4  
G = Options 1 & 3  
H = Options 1 & 4  
J = Options 1, 2 & 3  
K = Options 1, 2, & 4  
L = Options 1,3 & 4  
M = Options 1, 2, 3, & 4  
N = Options 2 & 3  
P = Options 2 & 4  
Q = Options 2, 3, & 4  
R = Options 3 & 4  
S = Option 5  
2 = 208/230-3-60  
4 = 460-3-60  
5 = 575-3-60  
T = Options 1 & 5  
U = Options 1, 3, & 5  
V = Options 1, 4, & 5  
W = Options 1, 3, 4, & 5  
X = Options 3 & 5  
Y = Options 4 & 5  
Z = Options 3, 4 & 5  
Options  
1 = Disconnect  
2 = Non-Pwr'd Conv. Outlet  
3 = Smoke Detector S.A.  
4 = Smoke Detector R.A.  
5 = Pwr'd Conv. Outlet  
Unitary Products Group  
3
 
254599-YTG-C-0807  
gas valve, if applicable, and the temperature limit  
switch on gas heat units. The unit control board will  
alarm on ignition failures, compressor lockouts and  
repeated limit switch trips.  
FEATURES  
All models are available with a wide variety of factory-  
mounted options such as stainless steel heat exchangers,  
electric heaters, phase monitor, convenience outlet, dirty filter  
switch, disconnect switch, smoke detectors, and coil guard to  
make them suitable for almost every application.  
Nuisance Trip Protection- To prevent nuisance  
trouble calls, the control board uses a “three strikes,  
you’re out” philosophy. The high and low-pressure  
switches and the freezestats must trip three times  
within two hours before the unit control board will  
lock out the compressor.  
All units are self-contained and assembled on full perimeter  
base rails with forklift holes on three sides and holes for over-  
head rigging. Every unit is completely piped, wired, charged  
and tested at the factory to simplify the field installation and to  
provide years of dependable operation.  
On Board Diagnostics - Each alarm will energize a  
trouble light on the thermostat, if so equipped, and  
flash an alarm code on the control board LED. Each  
high and low-pressure switch alarm as well as each  
freezestat alarm has its own flash code. The control  
board saves the five most recent alarms in memory,  
and these alarms can be reviewed at any time.  
Alarms and programmed values are retained  
through the loss of power.  
All models (including those with an economizer) are suitable  
for either bottom or horizontal duct connections. For bottom  
duct, remove the sheet metal panels from the supply and  
return air openings through the base of the unit. For horizon-  
tal duct, remove the supply and return air panels on the rear  
of the unit.  
All models are available with these “factory mounted” outdoor  
air damper options:  
All units have long lasting powder paint cabinets with 1000  
hour salt spray test approval under ASTM-B117 procedures.  
Single enthalpy economizer  
Motorized outdoor air damper  
All models are CSA listed.  
Warranty - All models include a one-year limited parts  
warranty on the complete unit. Compressors and electric  
heater elements carry a five-year warranty. Gas heat  
exchangers carry a 10-year parts warranty.  
Supply air blowers are equipped with either a direct drive or a  
belt drive that can be adjusted to meet the exact require-  
ments of the job.  
Gas Heat Operation - All single phase models with gas  
heat have minimum annual fuel utilization efficiency  
(AFUE) of 80%. All three phase models with gas heat  
have minimum steady state efficiency of 80%. Each sec-  
tion includes a durable heat exchanger with aluminized  
steel or optional stainless steel tubes, a redundant gas  
valve, spark ignition, power venting, an ignition module for  
100% shut-off and all of the safety controls required to  
meet the latest ANSI standards.  
All compressors are equipped with internal pressure relief.  
Every refrigerant circuit includes a liquid line filter-drier, a high  
pressure switch and a suction line with a freezestat and low  
pressure/loss of charge switch to protect all system compo-  
nents.  
®
®
S implicity Controls - S implicity control boards have  
standardized a number of features previously available  
only as options or by utilizing additional controls.  
The gas supply piping can be routed into the heating  
compartment through a hole in the base pan of the unit  
or through a knockout in the piping panel on the front of  
the unit.  
Low Ambient - An integrated low-ambient control  
allows all units to operate in the cooling mode down  
to 0ºF outdoor ambient without additional assis-  
tance. Optionally, the control board can be pro-  
grammed to lockout the compressors when the  
outdoor air temperature is low or when free cooling  
is available.  
Electric Heat Operation - All electric heat models are  
wired for a single power source and include a bank of  
nickel chromium elements mounted at the discharge of  
the supply air blower to provide a high velocity and uni-  
form distribution of air across the heating elements.  
Every element is fully protected against excessive tem-  
perature by thermal limit switches.  
Anti-Short Cycle Protection - To aid compressor  
life, an anti-short cycle delay is incorporated into the  
standard controls. Compressor reliability is further  
ensured by programmable minimum run times. For  
testing, the anti short cycle delay can be temporarily  
overridden with the push of a button.  
The power supply wiring can be routed into the control  
box through a threaded pipe connection (field supplied)  
in the base pan of the unit or through a knockout in the  
wiring panel on the side of the unit.  
Fan Delays - Fan on and fan off delays are fully pro-  
grammable and are independent of one another. All  
units are programmed with default values based  
upon their configuration of cooling and heat.  
BAS Controls - York’s Sunline™ series units offer factory  
®
mounted BAS controls such as S implicity INTELLI-Com-  
fort™, Novar, Honeywell, Johnson, and CPC.  
Safety Monitoring - The control board monitors the  
high and low-pressure switches, the freezestats, the  
4
Unitary Products Group  
 
254599-YTG-C-0807  
FIGURE 1 - UNIT CUTAWAY  
ELECTRIC HEATERS - Wired for single point power  
supply. These nickel chromium heater elements are pro-  
vided with limit and automatic reset capability to prevent  
operation at excessive temperatures.  
FACTORY-INSTALLED OPTIONS  
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-  
MIZERS - Includes a slide-in / plug-in damper assembly  
with fully modulating spring-return motor actuator capa-  
ble of introducing up to 100% outdoor air with nominal  
1% leakage type dampers.  
FILTER OPTIONS - Standard units are shipped with 1”  
throw-away filters installed. 2” pleated filters are offered  
as a factory installed option.  
The enthalpy system contains one sensor that monitors  
the outdoor air and determines when the air is cool  
enough and dry enough to provide free cooling.  
CONVENIENCE OUTLET - This 110 volt outlet can be  
“powered” by the unit with a stepdown transformer or the  
unit may be ordered with a “non-powered” convenience  
outlet that can be wired in the field.  
The rainhood is painted to match the basic unit and must  
be field-assembled before installing.  
DISCONNECT SWITCH - For gas heat units and cooling  
units with electric heat, a HACR breaker sized to the unit  
is provided. For cooling only units, a switch sized to the  
largest electric heat available for the particular unit is  
provided. Factory installed option only.  
MOTORIZED OUTDOOR AIR INTAKE DAMPER -  
Includes a slide-in / plug-in damper assembly with a 2-  
position, spring return motor actuator which opens to a  
pre-set position whenever the supply air blower is oper-  
ating and will drive fully closed when the blower unit  
shuts down.  
BAS - Building Automation System Controls  
®
S implicity INTELLI-Comfort™ CONTROL - The York®  
®
The rain hood is painted to match the basic unit and  
must be field assembled before installing.  
S implicity INTELLI-Comfort™ control is factory  
installed. It includes a supply air sensor, a return air sen-  
sor, and an outside air sensor. There are provisions for a  
field installed dirty filter indicator switch, an air-proving  
switch, an Outside Air Humidity sensor, a Return Air  
Humidity sensor, an Inside IAQ sensor, and an Outside  
Air IAQ sensor. Construction mode operation, 365-day  
real time clock with 7 day programming plus holiday  
PHENOLIC COATED EVAPORATOR AND CON-  
DENSER COILS - Special coating process that utilizes  
TM  
Technicoat 10-1 processes. Coating is applied by total  
immersion of the complete coil for maximum protection.  
Unitary Products Group  
5
   
254599-YTG-C-0807  
scheduling is built-in. Two different modes of demand  
ventilation are achieved through the INTELLI-Comfort™  
using CO2 sensors. It uses an inside CO2 sensor to per-  
form Demand Ventilation. It can also use an Outside  
CO2 sensor to perform Differential Demand Ventilation.  
It uses a Patented Comfort Ventilation algorithm to pro-  
vide comfortable ventilation air temperature. The pat-  
ented economizer-loading algorithm will protect the  
equipment when harsh operating conditions exist.  
Humidity in the occupied space or return duct can be  
monitored and controlled via humidity sensors and the  
on-board connection for hot gas re-heat system. It uses  
the INTELLI-Start™ algorithm to maximize energy sav-  
ings by recovering the building from the Unoccupied Set-  
points to the Occupied Setpoints just in time for the  
power to the control board if smoke is detected within the  
air compartment.  
Factory installed Smoke Detectors in the return air,  
may be subjected to freezing temperatures during  
“off” times due to outside air infiltration. These  
smoke detectors have an operational limit of 32°F  
to 131°F. Smoke detectors installed in areas that  
could be outside those limitations will have to be  
moved to prevent having false alarms.  
COIL GUARD - Customers can purchase a coil guard kit  
to protect the condenser coil from damage. This is not a  
hail guard kit.  
®
Occupied Time Period to begin. The S implicity  
INTELLI-Comfort™ balances space temperature, venti-  
lation air temperature, CO2 and humidity for ultimate  
comfort.  
STAINLESS STEEL HEAT EXCHANGER - For applica-  
tions in corrosive environments, this option provides a  
full stainless steel heat exchanger assembly.  
®
S implicity INTELLI-Comfort™ with MOD LINK CON-  
®
TROL - The York® S implicity INTELLI-Comfort™ with  
Mod Link control is factory installed. It includes all the  
features of the INTELLI-Comfort™ control with an addi-  
tional control to translate communications from MOD-  
BUS to the BACnet MSTP protocol.  
STAINLESS STEEL DRAIN PAN - An optional rust-  
proof stainless steel drain pan is available to provide  
years of trouble-free operation in corrosive environ-  
ments.  
Novar® BAS CONTROL - The Novar® ETC-3 building  
automation system controller is factory installed.  
Includes supply air sensor, return air sensor, dirty filter  
indicator switch, and air proving switch.  
BOTTOM DRAIN CONNECTION - An optional bottom  
drain connection is available for inside the curb connec-  
tions for applications in cold environments to reduce  
freezing drain lines.  
JOHNSON CONTROLS BAS CONTROL - The Johnson  
Control YK-UNT-1126 building automation system con-  
troller is factory installed. Includes supply air sensor,  
return air sensor, dirty filter indicator switch, and air prov-  
ing switch.  
PHASE MONITORS - Designed to prevent unit damage.  
The phase monitor will shut the unit down in an out-of-  
phase condition.  
DIRTY FILTER SWITCH - This kit includes a differential  
pressure switch that energizes the fault light on the unit  
thermostat, indicating that there is an abnormally high  
pressure drop across the filters. Factory installed option  
or field installed accessory.  
CPC BAS CONTROL - The Computer Process Controls  
Model 810-3060 ARTC Advanced Rooftop building auto-  
mation system controller is factory installed. Includes  
supply air sensor, return air sensor, dirty filter indicator  
switch and air proving switch.  
HINGED FILTER DOOR/“TOOLLESS” BLOWER AND  
ACCESS PANELS (not hinged) - This option allows for  
easy access and maintenance.  
HONEYWELL BAS CONTROL - The Honeywell  
W7750C building automation system controller is factory  
installed. Includes air supply sensor, return air sensor,  
dirty filter indicator switch, and air proving switch.  
NOTE:Knobs are shipped inside the unit to prevent ship-  
ping damage. These must be field installed for  
tool-less operation.  
SMOKE DETECTORS - (supply air & return air) The  
smoke detectors stop operation of the unit by interrupting  
6
Unitary Products Group  
254599-YTG-C-0807  
tudes up to 6,000 feet. This accessory supplements the  
basic propane conversion kit.  
FIELD-INSTALLED ACCESSORIES  
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-  
MIZERS - Includes a slide-in / plug-in damper assembly  
with fully modulating spring-return motor actuator capa-  
ble of introducing up to 100% outdoor air with nominal  
1% leakage type dampers.  
LOW NOX KIT- Required to reduce the emission of  
nitrogen oxides below 40 nanograms per joule.  
POWER EXHAUST - Our single input economizer  
options are available with power exhaust. Whenever the  
outdoor air intake dampers are opened for free cooling,  
the exhaust fan will be energized to prevent the condi-  
tioned space from being over-pressurized during econo-  
mizer operation.  
The enthalpy system contains one sensor that monitors  
the outdoor air and determines when the air is cool  
enough and dry enough to provide free cooling.  
The rainhood is painted to match the basic unit and must  
be field-assembled before installing.  
The power exhaust option can only be used on bot-  
tom duct configurations.  
MOTORIZED OUTDOOR AIR INTAKE DAMPER -  
Includes a slide-in / plug-in damper assembly with a 2-  
position, spring return motor actuator which opens to  
some pre-set position whenever the supply air blower is  
operating and will drive fully closed when the blower unit  
shuts down.  
BAROMETRIC RELIEF DAMPER - This damper acces-  
sory can be used to relieve internal building air pressure  
on units with an economizer without power exhaust. This  
accessory includes a rain hood, a bird screen and a fully  
assembled damper. With bottom duct connections, the  
damper should be mounted over the opening in the  
return air panel. With horizontal ductwork, the accessory  
should be mounted on the return air duct.  
The rain hood is painted to match the basic unit and  
must be field assembled before installing.  
ELECTRIC HEATERS wired for single point power sup-  
ply. These nickel chromium heater elements are pro-  
vided with limit and automatic reset capability to prevent  
operation at excessive temperatures.  
ENTHALPY ACCESSORY CONTROL KIT - This kit  
contains the required components to convert a single  
enthalpy economizer to dual enthalpy.  
BURGLAR BARS - Mount in the supply and return  
openings to prevent entry into the duct work.  
ROOF CURBS - Eight and fourteen-inch high roof curbs  
provide a water-tight seal between the unit and the fin-  
ished roof. These full perimeter curbs meet the require-  
ments of the National Roofing Contractors Association  
(NRCA) and are shipped knocked-down for field assem-  
bly.  
FLUE EXHAUST EXTENSION KIT - In locations with  
wind or weather conditions which may interfere with  
proper exhausting of furnace combustion products, this  
kit can be installed to prevent the flue exhaust from  
entering nearby fresh air intakes.  
Roof curbs are designed to fit inside the base rails of the  
unit and include both a wood nailing strip and duct  
hanger supports.  
CO SENSOR - Senses CO levels and automatically  
2
2
overrides the economizer when levels rise above the  
present limits.  
HIGH ALTITUDE NATURAL GAS - Burner orifices and  
pilot orifices are provided for proper furnace operation at  
altitudes up to 6,000 feet.  
COIL GUARD - Customers can purchase a coil guard kit  
to protect the condenser coil from damage. This is not a  
hail guard kit.  
PROPANE - Burner orifices, pilot orifices and gas valve  
parts are provided to convert a natural gas furnace to  
propane.  
HAIL GUARD - Hail guard kit is available to prevent unit  
from hail damage. This is a sloped hood that fits above  
the coil.  
HIGH ALTITUDE PROPANE - Burner orifices and pilot  
orifices are provided for proper furnace operation at alti-  
GAS PIPING KIT - This kit supplies all necessary fittings  
and shut off valve.  
Unitary Products Group  
7
 
254599-YTG-C-0807  
1
TABLE 1: SOUND POWER RATING  
-12  
SOUND POWER (db 10  
Watts)  
Octave Band Centerline Frequency (Hz)  
ESP  
BLOWER  
UNIT  
SIZE  
dB(A)  
@
10Ft.2  
CFM  
SWL  
dB(A)  
IWG SPEED  
KW  
63  
125  
250  
500  
1,000  
2,000  
4,000  
8,000  
55  
072  
2,200  
0.3  
HIGH  
1.35  
87  
87  
77  
70  
72  
65  
60  
77  
44  
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The  
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan  
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran-  
tee requiring a dBA value or sound data in any other form than sound power level ratings.  
2. At a distance of 10 feet from the blower.  
1
1
TABLE 2: CAPACITY RATINGS - (ARI 210/240)  
TABLE 3: GAS HEAT RATINGS  
EER2  
MBH  
INPUT  
MBH  
OUTPUT  
AFUE  
(%)  
TEMP  
RISE ºF  
MODEL  
DF072  
MBH  
MODEL  
70.5  
10.4  
DF072N08  
DF072N10  
100  
125  
80  
100  
80.5  
80.3  
25 - 55  
35 - 65  
1. 80/67°F Indoor and 95°F outdoor.  
2. EER = Energy Efficiency Ratio at full load - the cooling  
capacity in Btu’s per hour (Btuh) divided by the power  
input in watts, expressed in Btuh per watt (Btuh/watt).  
1. All units are single-stage heating.  
TABLE 4: 2 STAGE GAS HEAT RATINGS  
MBH INPUT  
MBH OUTPUT  
STEADY STATE EFFICIENCY  
RISE  
MINIMUM HEATING  
AIRFLOW (CFM)  
MODEL1  
1
ST STAGE 2ND STAGE 1ST STAGE 2ND STAGE 1ST STAGE  
2ND STAGE  
MIN. MAX.  
45  
75  
75  
35.8  
60.4  
60.8  
79.4  
80.5  
81.1  
35  
45  
70  
75  
1230  
1230  
DF072D06  
DF072D10  
125  
100.6  
80.5  
1. Models are 3Ø only.  
8
Unitary Products Group  
       
254599-YTG-C-0807  
TABLE 5: DF072 COOLING CAPACITIES (6 TON)  
Temperature of Air on Condenser Coil  
2
Return Air  
Gross Sensible Capacity (MBh)  
Return Air Dry Bulb (°F)  
Gross Sensible Capacity (MBh)  
Return Air Dry Bulb (°F)  
Gross  
Capacity  
(MBh)  
Power  
Input  
(kW)  
Gross  
Capacity  
(MBh)  
Power  
Input  
(kW)  
WB  
(°F)  
CFM  
2750  
2475  
2200  
1925  
1650  
1
86  
83  
85°F  
54.6 46.4 38.2 30.0 21.8  
80  
77  
74  
71  
68  
-
90  
85  
95°F  
53.1 44.9 36.7 28.5 20.3  
80  
75  
70  
65  
68  
-
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
83.1  
79.5  
72.7  
66.7  
82.4  
78.8  
72.1  
66.1  
81.7  
78.1  
71.4  
65.5  
79.3  
75.8  
69.4  
63.6  
77  
5.24  
5.15  
5.08  
5.04  
5.25  
5.16  
5.10  
5.05  
5.26  
5.18  
5.11  
5.06  
5.24  
5.15  
5.08  
5.04  
5.21  
5.12  
5.06  
5.01  
-
80.2  
75.3  
68.3  
65.8  
79.9  
75.0  
68.0  
65.5  
79.6  
74.7  
67.7  
65.2  
77.1  
72.3  
65.6  
63.2  
74.5  
69.9  
63.4  
61.1  
5.92  
5.80  
5.74  
5.77  
5.89  
5.78  
5.72  
5.74  
5.87  
5.75  
5.69  
5.72  
5.86  
5.74  
5.68  
5.71  
5.85  
5.73  
5.67  
5.70  
-
67.8 59.6 51.4 43.2 35.0 26.8 18.6  
72.7 72.7 64.8 56.6 48.4 40.2 32.0  
66.7 66.7 64.6 56.4 48.2 40.0 31.8  
66.6 58.4 50.2 42.0 33.8 25.6 17.4  
68.3 68.3 62.5 54.3 46.1 37.9 29.7  
65.8 65.8 64.5 56.3 48.1 39.9 31.7  
52.1 44.8 37.5 30.2 22.9  
-
-
50.5 43.2 35.9 28.6 21.3  
-
-
65.0 57.7 50.4 43.1 35.8 28.5 21.2  
72.1 70.7 63.5 56.2 48.9 41.6 34.3  
66.1 66.1 63.4 56.1 48.8 41.5 34.1  
63.8 56.5 49.1 41.8 34.5 27.2 19.9  
68.0 67.3 61.2 53.9 46.6 39.3 32.0  
65.5 65.5 63.1 55.8 48.5 41.2 33.9  
49.6 43.2 36.8 30.3 23.9  
-
-
48.0 41.6 35.2 28.7 22.3  
-
-
62.3 55.8 49.4 43.0 36.6 30.2 23.8  
71.4 68.7 62.3 55.9 49.5 43.1 36.6  
65.5 65.5 62.1 55.7 49.3 42.9 36.5  
60.9 54.5 48.1 41.7 35.3 28.9 22.4  
67.7 66.3 59.9 53.5 47.1 40.7 34.3  
65.2 65.2 61.8 55.4 49.0 42.6 36.2  
45.6 40.0 34.5 28.9 23.4  
-
-
43.9 38.4 32.8 27.2 21.7  
-
-
57.5 51.9 46.4 40.8 35.3 29.7 24.1  
67.7 64.0 58.5 52.9 47.3 41.8 36.2  
63.6 62.3 58.3 52.7 47.2 41.6 36.1  
56.0 50.4 44.9 39.3 33.8 28.2 22.6  
64.5 61.5 55.9 50.3 44.8 39.2 33.7  
63.2 61.7 57.7 52.1 46.5 41.0 35.4  
41.6 36.9 32.2 27.5 22.8  
-
-
39.8 35.1 30.4 25.7 21.0  
-
-
73.6  
67.3  
61.7  
52.7 48.0 43.3 38.6 33.9 29.2 24.5  
64.0 59.3 54.6 49.9 45.2 40.5 35.8  
61.7 59.2 54.5 49.8 45.0 40.3 35.6  
105°F  
51.0 46.3 41.6 36.9 32.2 27.5 22.8  
61.3 56.6 51.9 47.2 42.5 37.7 33.0  
61.1 58.2 53.5 48.8 44.1 39.4 34.7  
115°F  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
76.3  
70.2  
62.2  
61.2  
76.1  
70.0  
62.0  
61.0  
75.9  
69.8  
61.9  
60.9  
73.1  
67.2  
59.6  
58.6  
70.3  
64.6  
57.3  
56.4  
6.66  
6.55  
6.48  
6.50  
6.63  
6.52  
6.45  
6.47  
6.59  
6.48  
6.41  
6.43  
6.58  
6.47  
6.40  
6.42  
6.57  
6.46  
6.39  
6.41  
51.5 43.3 35.1 26.9 18.7  
-
-
72.4  
65.0  
56.1  
56.7  
72.3  
65.0  
56.1  
56.6  
72.2  
64.9  
56.0  
56.5  
69.1  
62.1  
53.6  
54.1  
66.1  
59.4  
51.2  
51.7  
7.40  
7.31  
7.22  
7.24  
7.36  
7.26  
7.18  
7.19  
7.31  
7.22  
7.13  
7.15  
7.30  
7.20  
7.12  
7.13  
7.28  
7.19  
7.11  
7.12  
50.0 41.8 33.6 25.4 17.2  
-
-
64.2 56.0 47.8 39.6 31.5 23.3 15.1  
62.2 62.2 58.8 50.6 42.4 34.2 26.0  
61.2 61.2 60.1 51.9 43.7 35.5 27.3  
61.9 53.7 45.5 37.3 29.1 20.9 12.7  
56.1 56.1 55.2 47.0 38.8 30.6 22.4  
56.7 56.7 55.7 47.5 39.3 31.1 22.9  
2750  
2475  
2200  
1925  
1650  
49.0 41.7 34.3 27.0 19.7  
-
-
47.4 40.1 32.8 25.5 18.2  
-
-
61.4 54.1 46.8 39.5 32.2 24.9 17.6  
62.0 61.7 57.5 50.2 42.9 35.6 28.3  
61.0 61.0 58.8 51.5 44.2 36.9 29.5  
59.1 51.7 44.4 37.1 29.8 22.5 15.2  
56.1 56.1 53.9 46.6 39.2 31.9 24.6  
56.6 56.6 54.4 47.1 39.8 32.5 25.2  
46.4 40.0 33.6 27.2 20.7  
-
-
44.8 38.4 32.0 25.6 19.2  
-
-
58.6 52.2 45.7 39.3 32.9 26.5 20.1  
61.9 61.2 56.2 49.8 43.4 37.0 30.6  
60.9 60.9 57.5 51.0 44.6 38.2 31.8  
56.2 49.8 43.4 37.0 30.5 24.1 17.7  
56.0 56.0 52.6 46.2 39.7 33.3 26.9  
56.5 56.5 53.1 46.7 40.3 33.9 27.4  
42.3 36.7 31.1 25.6 20.0  
-
-
40.6 35.0 29.5 23.9 18.4  
-
-
53.5 48.0 42.4 36.9 31.3 25.7 20.2  
59.1 57.0 52.2 46.6 41.0 35.5 29.9  
58.6 57.3 53.3 47.7 42.2 36.6 31.0  
51.1 45.5 40.0 34.4 28.8 23.3 17.7  
53.6 52.5 48.4 42.9 37.3 31.7 26.2  
54.1 53.0 48.9 43.3 37.8 32.2 26.7  
38.1 33.4 28.7 24.0 19.3  
-
-
36.4 31.7 26.9 22.2 17.5  
-
-
48.5 43.8 39.1 34.4 29.7 25.0 20.3  
56.3 52.8 48.1 43.4 38.7 34.0 29.2  
56.4 53.8 49.1 44.4 39.7 35.0 30.3  
45.9 41.2 36.5 31.8 27.1 22.4 17.7  
51.2 49.0 44.3 39.6 34.9 30.2 25.5  
51.7 49.4 44.7 40.0 35.3 30.6 25.9  
1. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan  
motor power input is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.  
2. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER  
PERFORMANCE Table, multiply this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity  
of the unit.  
Nominal Rating  
Unitary Products Group  
9
 
254599-YTG-C-0807  
TABLE 6: SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT DRIVE) - SIDE DUCT APPLICATION  
Available External Static Pressure - IWG1  
0.4 0.5 0.6  
RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts  
Unit  
Air Flow  
0.2  
0.3  
0.7  
0.8  
Tonnage (CFM)  
2500  
2400  
2300  
2200  
2100  
2000  
1900  
1800  
1700  
1600  
1500  
1059  
1032  
1005  
980  
930  
877  
-
-
-
-
-
1560  
1405  
1260  
1160  
1060  
950  
-
-
-
-
-
1077  
1054  
1024  
1002  
957  
908  
-
-
-
-
-
1590  
1470  
1275  
1170  
1070  
975  
-
-
-
-
-
1095  
1074  
1049  
1022  
983  
941  
894  
855  
-
1630  
1525  
1370  
1190  
1080  
1000  
885  
815  
-
1114  
1094  
1069  
1044  
1010  
976  
940  
903  
884  
864  
-
1650  
1560  
1440  
1250  
1100  
1020  
940  
860  
815  
770  
-
1134  
1116  
1090  
1066  
1039  
1009  
980  
950  
925  
908  
882  
1660  
1595  
1475  
1350  
1160  
1050  
980  
905  
850  
805  
740  
1158  
1140  
1116  
1090  
1064  
1040  
1014  
988  
1685  
1620  
1505  
1410  
1260  
1100  
1020  
940  
1181  
1167  
1142  
1117  
1092  
1070  
1047  
1022  
1001  
987  
1720  
1640  
1535  
1440  
1340  
1225  
1095  
970  
62,3  
964  
948  
926  
880  
835  
780  
910  
870  
830  
-
-
-
-
965  
Available External Static Pressure - IWG1  
1.1 1.2 1.3  
RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts  
Unit  
Air Flow  
0.9  
1.0  
1.4  
1.5  
Tonnage (CFM)  
2500  
2400  
2300  
2200  
2100  
2000  
1900  
1800  
1700  
1600  
1500  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1193  
1170  
1148  
1121  
1100  
1079  
1058  
1035  
1020  
1004  
1665  
1580  
1480  
1385  
1285  
1180  
1060  
960  
1202  
1180  
1155  
1133  
1110  
1090  
1071  
1056  
1038  
1620  
1530  
1425  
1340  
1240  
1135  
1030  
965  
1190  
1169  
1143  
1122  
1103  
1088  
1070  
1475  
1385  
1280  
1190  
1100  
1035  
925  
-
1205  
1178  
1158  
1134  
1118  
1101  
1445  
1330  
1240  
1140  
1065  
980  
-
-
1222  
1196  
1164  
1145  
1130  
1375  
1295  
1175  
1105  
1045  
1197  
1170  
1158  
1205  
1130  
1075  
-
-
900  
860  
1198  
1184  
1150  
1110  
880  
1. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for resis-  
tance values on applications other than gas / electric units with side duct airflows.  
2. 230/460/575 Volts  
3. For 208 Volts multiply values by 0.95.  
TABLE 7: BELT DRIVE BLOWER MOTOR AND DRIVE DATA  
BELT  
(NOTCHED)  
1
ADJUSTABLE MOTOR PULLEY  
FIXED BLOWER PULLEY  
OUTSIDE PITCH  
MOTOR  
BLOWER  
RANGE  
(RPM)  
MODEL  
SIZE  
OUTSIDE  
DIA.  
PITCH  
DIA.  
PITCH  
LENGTH QTY.  
(IN.)  
DESIG-  
NATION  
BORE DESIG-  
(IN.)  
BORE DESIG-  
HP FRAME  
DIA.  
(IN.)  
DIA.  
(IN.)  
NATION  
(IN.)  
NATION  
(IN.)  
(IN.)  
6 TON  
850/1220 1 1/2  
56  
1VL40  
2.7-3.7  
2.4-3.4  
5/8  
AK56  
5.4  
5.2  
1
A36  
37.3  
1
1. All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located  
in the moving air, upstream of any heating device.  
10  
Unitary Products Group  
         
254599-YTG-C-0807  
TABLE 8: SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT DRIVE) - SIDE DUCT APPLICATION  
Available External Static Pressure - IWG1  
Unit  
Motor  
0.2  
0.3  
0.4  
0.5  
0.6  
Tonnage Speed  
CFM  
2256  
2145  
2020  
-
Watts  
883  
771  
637  
-
CFM  
2258  
2127  
1999  
-
Watts  
931  
784  
656  
-
CFM  
2247  
2119  
1985  
-
Watts  
950  
808  
675  
-
CFM  
2223  
2089  
1947  
-
Watts  
964  
826  
696  
-
CFM  
2182  
2051  
1910  
-
Watts  
979  
844  
715  
-
Hi  
Med/Hi  
62  
Med  
Med/Low  
Low  
-
-
-
-
-
-
-
-
-
-
Available External Static Pressure - IWG1  
0.8 0.9  
Unit  
Motor  
0.7  
1.0  
Tonnage Speed  
CFM  
2125  
2014  
1876  
-
Watts  
971  
859  
730  
-
CFM  
2044  
1965  
1832  
-
Watts  
940  
861  
740  
-
CFM  
1958  
1896  
1793  
-
Watts  
898  
843  
756  
-
CFM  
Watts  
Hi  
1864  
854  
Med/Hi  
1801  
806  
Med  
Med/Low  
Low  
-
-
-
-
-
-
-
-
-
-
-
-
1. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES  
Table for resistance values.  
2. Side Duct application (230 Volts)  
TABLE 9: STATIC RESISTANCES  
RESISTANCE, IWG  
DESCRIPTION  
CFM  
1000  
0.07  
0.04  
0.06  
0.06  
0.08  
1200  
0.08  
0.05  
0.07  
0.07  
0.10  
1400  
0.09  
0.06  
0.08  
0.08  
0.12  
1600  
0.11  
0.07  
0.09  
0.09  
0.14  
1800  
0.13  
0.08  
0.11  
0.10  
0.16  
2000  
0.15  
0.10  
0.13  
0.11  
0.18  
2200  
0.17  
0.12  
0.15  
0.12  
0.20  
2400  
0.20  
0.14  
0.17  
0.14  
0.23  
2600  
0.23  
0.16  
0.20  
0.16  
0.26  
2800  
0.26  
0.19  
0.23  
0.19  
0.29  
3000  
0.30  
0.22  
0.26  
0.22  
0.32  
ECONOMIZER1 3  
ELECTRIC  
7-15KW  
20-30KW  
HEATERS1  
BOTTOM DUCT CONNECTIONS1  
COOLING ONLY2  
1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.  
2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.  
3. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air  
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.  
TABLE 10: ELECTRIC HEATER CFM LIMITATIONS  
MINIMUM SUPPLY AIR CFM  
UNIT MODEL SIZE NOMI-  
VOLTAGE  
HEATER SIZE NOMINAL KW  
NAL TONS  
5
7
10  
15  
20  
30  
208/230-3-60  
460-3-60  
1800  
1800  
1800  
-
1800  
1800  
1800  
1800  
1800  
1800  
1800  
1800  
1800  
1800  
1800  
1800  
6
-
-
575-3-60  
Unitary Products Group  
11  
       
254599-YTG-C-0807  
TABLE 11: ELECTRICAL DATA - DF072 BELT DRIVE W/O POWERED CONV. OUTLET  
COMPRESSORS  
ID  
MIN.  
MAX. FUSE/  
BRKR  
SIZE  
(AMPS)  
45  
OD FAN  
MOTOR  
FLA  
CONV  
OUTLET  
FLA  
1
MODEL  
TONNAGE  
BLOWER  
MOTOR  
FLA  
ELECTRIC HEATER HEATER HEATER CIRCUIT  
VOLTAGE  
RLA  
LRA  
MODEL NO.  
KW  
AMPS  
AMPACITY  
(AMPS)  
33.4  
33.4  
33.4  
34.3  
47.8  
61.7  
83.5  
33.4  
33.4  
33.4  
38.4  
54.3  
70.2  
95.5  
16.4  
16.4  
18.4  
23.7  
32.6  
46.6  
13.3  
15.2  
21.6  
28  
EACH  
EACH  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
None  
-
4
-
2
2
11.1  
15.5  
22.2  
33.0  
44.1  
61.6  
-
12.7  
18.0  
25.5  
38.2  
51.0  
71.2  
-
45  
45  
45  
50  
70  
90  
45  
45  
45  
50  
60  
80  
100  
25  
25  
25  
25  
35  
50  
20  
20  
25  
30  
40  
5.6  
8
11.9  
15.9  
22.2  
-
5.3  
7.5  
10.6  
15.9  
21.2  
29.6  
-
6.8  
10.1  
13.6  
19.5  
28.8  
-
208-3-60  
20.7  
20.7  
156.0  
156.0  
2.3  
2.3  
5.2  
5.2  
0.0  
0.0  
2
2CE04510525  
2CE04510725  
2
230-3-60  
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
None  
2CE04510746  
2CE04511046  
2CE04511546  
2CE04512046  
2CE04513046  
None  
DF072  
(6.0)  
2
8.2  
2
2
2
2
12.1  
16.4  
23.5  
34.6  
-
10.2  
15.3  
20.4  
29.3  
460-3-60  
575-3-60  
10.0  
8.2  
75.0  
54.0  
1.3  
1.3  
2.6  
2.0  
0.0  
0.0  
2CE04511058  
2CE04511558  
2CE04512058  
2CE04513058  
10.6  
15.9  
21.2  
30.4  
39.1  
1. HACR Type per NEC.  
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block  
accessories 2FB04700825 and 2FB04700846 are available for field installation.  
TABLE 12: ELECTRICAL DATA - DF072 DIRECT DRIVE W/O POWERED CONV. OUTLET  
COMPRESSORS  
ID  
MIN.  
MAX. FUSE/  
BRKR  
SIZE  
(AMPS)  
50  
OD FAN  
MOTOR  
FLA  
CONV  
OUTLET  
FLA  
1
MODEL  
TONNAGE  
BLOWER  
MOTOR  
FLA  
ELECTRIC HEATER HEATER HEATER CIRCUIT  
VOLTAGE  
RLA  
LRA  
MODEL NO.  
KW  
AMPS  
AMPACITY  
(AMPS)  
38.8  
EACH  
EACH  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
-
-
2
2
4.0  
5.6  
8.0  
11.9  
15.9  
22.2  
-
5.3  
7.5  
10.6  
15.9  
21.2  
29.6  
11.1  
15.5  
22.2  
33.0  
44.1  
61.6  
-
12.7  
18.0  
25.5  
38.2  
51.0  
71.2  
38.8  
38.8  
41.0  
54.5  
68.4  
90.3  
38.8  
38.8  
38.8  
45.1  
61.1  
77.0  
102.3  
50  
50  
50  
60  
70  
100  
50  
50  
50  
50  
208-3-60  
20.7  
20.7  
156.0  
156.0  
2.3  
2.3  
10.6  
10.6  
0.0  
0.0  
DF072  
(6.0)  
2
2
230-3-60  
70  
80  
110  
1. HACR Type per NEC.  
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block  
accessories 2FB04700825 and 2FB04700846 are available for field installation.  
12  
Unitary Products Group  
   
254599-YTG-C-0807  
TABLE 13: ELECTRICAL DATA - DF072 BELT DRIVE W/POWERED CONV. OUTLET  
COMPRESSORS  
ID  
MIN.  
MAX. FUSE/  
BRKR  
SIZE  
(AMPS)  
60  
OD FAN  
MOTOR  
FLA  
CONV  
OUTLET  
FLA  
1
MODEL  
TONNAGE  
BLOWER  
MOTOR  
FLA  
ELECTRIC HEATER HEATER HEATER CIRCUIT  
VOLTAGE  
RLA  
LRA  
MODEL NO.  
KW  
AMPS  
AMPACITY  
(AMPS)  
43.4  
43.4  
43.4  
46.8  
60.3  
74.2  
96  
EACH  
EACH  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
None  
-
4
-
2
2
11.1  
15.5  
22.2  
33.0  
44.1  
61.6  
-
12.7  
18.0  
25.5  
38.2  
51.0  
71.2  
-
60  
60  
60  
70  
80  
100  
60  
60  
60  
60  
70  
90  
110  
30  
30  
30  
30  
40  
5.6  
8
11.9  
15.9  
22.2  
-
5.3  
7.5  
10.6  
15.9  
21.2  
29.6  
-
6.8  
10.1  
13.6  
19.5  
28.8  
-
208-3-60  
20.7  
20.7  
156.0  
156.0  
2.3  
2.3  
5.2  
5.2  
10.0  
10.0  
43.4  
43.4  
43.4  
50.9  
66.8  
82.7  
108  
21.4  
21.4  
24.7  
29.9  
38.8  
52.8  
17.3  
20.2  
26.6  
33  
2
2CE04510525  
2CE04510725  
2
230-3-60  
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
None  
2CE04510746  
2CE04511046  
2CE04511546  
2CE04512046  
2CE04513046  
None  
DF072  
(6.0)  
2
8.2  
2
2
2
2
12.1  
16.4  
23.5  
34.6  
-
10.2  
15.3  
20.4  
29.3  
460-3-60  
575-3-60  
10.0  
8.2  
75.0  
54.0  
1.3  
1.3  
2.6  
2.0  
5.0  
4.0  
60  
25  
25  
30  
35  
45  
2CE04511058  
2CE04511558  
2CE04512058  
2CE04513058  
10.6  
15.9  
21.2  
30.4  
44.1  
1. HACR Type per NEC.  
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block  
accessories 2FB04700825 and 2FB04700846 are available for field installation.  
TABLE 14: ELECTRICAL DATA - DF072 DIRECT DRIVE W/POWERED CONV. OUTLET  
COMPRESSORS  
ID  
MIN.  
MAX. FUSE/  
BRKR  
SIZE  
(AMPS)  
60  
OD FAN  
MOTOR  
FLA  
CONV  
OUTLET  
FLA  
1
MODEL  
TONNAGE  
BLOWER  
MOTOR  
FLA  
ELECTRIC HEATER HEATER HEATER CIRCUIT  
VOLTAGE  
RLA  
LRA  
MODEL NO.  
KW  
AMPS  
AMPACITY  
(AMPS)  
48.8  
EACH  
EACH  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
None  
2CE04510525  
2CE04510725  
2CE04511025  
2CE04511525  
2CE04512025  
2CE04513025  
-
-
2
2
4.0  
5.6  
8.0  
11.9  
15.9  
22.2  
-
5.3  
7.5  
10.6  
15.9  
21.2  
29.6  
11.1  
15.5  
22.2  
33.0  
44.1  
61.6  
-
12.7  
18.0  
25.5  
38.2  
51.0  
71.2  
48.8  
48.8  
53.5  
67.0  
80.9  
102.8  
48.8  
48.8  
48.8  
57.6  
73.6  
89.5  
114.8  
60  
60  
60  
70  
90  
110  
60  
60  
60  
60  
208-3-60  
20.7  
20.7  
156.0  
156.0  
2.3  
2.3  
10.6  
10.6  
10.0  
10.0  
DF072  
(6.0)  
2
2
230-3-60  
80  
90  
125  
1. HACR Type per NEC.  
2. These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block  
accessories 2FB04700825 and 2FB04700846 are available for field installation.  
Unitary Products Group  
13  
   
254599-YTG-C-0807  
TABLE 15: DF PHYSICAL DATA  
DF  
072  
12 X 10  
1
MODELS  
Centrifugal Blower (Dia. x Wd. in.)  
EVAPORATOR  
BLOWER  
Fan Motor HP (Direct Drive)  
Fan Motor HP (Belt Drive)  
Rows Deep  
1 1/2  
4
EVAPORATOR  
COIL  
Fins Per Inch  
13  
Face Area (Sq. Ft.)  
Propeller Dia. (in.)  
Fan Motor Hp  
5.1  
24  
CONDENSER  
FANS  
1/2  
Nom. CFM  
4200  
2
Rows Deep  
CONDENSER  
COILS  
Fins Per Inch  
18  
Face Area (Sq. Ft.)  
17.1  
COMPRESSOR  
(Qty. Per Unit)  
Recip Type  
1
Quantity Per Unit (15” X 20” X 1” or 2“)  
Quantity Per Unit (14” X 25” X 1” or 2“)  
Total Face Area (sq. ft.)  
2
1
AIR  
FILTERS  
6.3  
Refrigerant 22  
(lbs./oz.)  
CHARGE  
11/10  
1
TABLE 16: ELECTRIC HEAT CORRECTION FACTORS  
TABLE 17: VOLTAGE LIMITATIONS  
NOMINAL VOLTAGE  
VOLTAGE  
kW CAP. MULTIPLIER  
VOLTAGE  
POWER SUPPLY  
MIN.  
187  
432  
540  
MAX.  
252  
208  
230  
460  
575  
0.75  
0.92  
0.92  
0.92  
208  
240  
480  
600  
208/230-3-60  
460-3-60  
504  
575-3-60  
630  
1. Utilization Range “A” in accordance with ARI Standard  
110.  
14  
Unitary Products Group  
     
254599-YTG-C-0807  
TYPICAL POWER WIRING  
REFER TO THE ELECTRICAL DATA  
TABLES TO SIZE THE DISCONNECT  
SWITCH, OVERCURRENT PROTEC-  
TION AND WIRING.  
TYPICAL CONTROL WIRING  
COOLING / HEATING (24 VOLT THERMOSTAT)  
COOLING ONLY (24 VOLT THERMOSTAT)  
THERMOSTAT1  
TERMINALS  
THERMOSTAT1 UNIT TERMINAL  
TERMINALS  
STRIP TB1  
UNIT TERMINAL  
STRIP TB1  
RH  
ADD  
JUMPER  
RV  
R
RC  
Y
R
Y1  
Y2  
W1  
W2  
G
24 VOLT  
TRANSFORMER  
YC  
GF  
Y1  
Y2  
G
24 VOLT  
TRANSFORMER  
W
G
C
C
124 VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZER  
ON SECOND STAGE COOLING, USE THE THERMOSTAT 2TH0401224.  
1
24 VOLT THERMOSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECOND  
STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF  
HEAT, USE THERMOSTAT 2TH0471024.  
COOLING / HEATING (ELECTRONIC THERMOSTAT)  
MULTI STAGE  
1
COOLING / HEATING (ELECTRONIC THERMOSTAT)  
SINGLE STAGE  
THERMOSTAT  
TERMINALS  
UNIT TERMINAL  
STRIP TB1  
RC  
RH  
Y1  
24 VOLT  
TRANSFORMER  
ADD  
JUMPER  
R
Y1  
Y2  
W1  
W2  
G
THERMOSTAT1  
2
3
Y2  
UNIT TERMINAL  
STRIP TB1  
TERMINALS  
W1  
4
W2  
RH  
RC  
Y
G
B
R
Y1  
W1  
G
C
ADD  
JUMPER  
LED 1  
X
NOT  
USED  
LED 2  
COM  
A1  
OCC  
W
4
G
ADD  
JUMPER  
A2  
C
T
TO REMOTE SENSOR  
2TH040702224 IF USED  
T
24 VOLT  
TRANSFORMER  
1 ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 (INCLUDES SUBBASE).  
2 SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.  
1ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET07701024 (INCLUDES SUBBASE).  
TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT  
2TH04700224.  
3 SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE  
ELECTRIC HEATER OR 2 STAGE GAS HEAT.  
4
REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR  
P6 ON UNITS WITH ECONOMIZER. TERMINALS A1 AND A2 PROVIDE A RELAY  
OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE  
THERMOSTAT SWITCHES TO THE SET-BACK POSITION.  
FIGURE 2 - TYPICAL FIELD POWER & CONTROL WIRING  
Unitary Products Group  
15  
 
254599-YTG-C-0807  
FIGURE 3 - UNIT DIMENSIONS (6 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW  
FIGURE 4 - UNIT DIMENSIONS (6 TON COOLING/GAS HEAT) FRONT VIEW  
16  
Unitary Products Group  
   
254599-YTG-C-0807  
DETAIL “A”  
FIGURE 5 - UNIT WITH ECONOMIZER RAINHOOD  
DETAIL “B”  
FIGURE 6 - UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD  
Unitary Products Group  
17  
   
254599-YTG-C-0807  
FIGURE 7 - UNIT DIMENSIONS (REAR VIEW)  
TABLE 18: UTILITIES ENTRY  
FILTER  
ACCESS  
HOLE  
A
OPENING SIZE (DIA.)  
USED FOR  
BLOWER MOTOR  
ACCESS  
Side  
1
2
7/8” KO  
Control Wiring  
Bottom  
Side  
DOT PLUGS  
B
Power Wiring  
2” KO  
FIELD-SUPPLIED  
DISCONNECT SWITCH  
LOCATION  
Bottom  
C
D
1-5/8” KO  
1-1/2” KO  
Gas Piping (Front)  
MOUNTING BRACKET  
FOR DICONNECT SWITCH  
(Shipped attached to the  
blower housing inside  
Gas Piping (Bottom)  
A,B  
the blower compartment)  
1. Opening in the bottom to the unit can be located by the  
side in the insulation.  
2. Do not remove the 2” knockout ring.  
WIRING ENTRY  
(See Detail “B”)  
CONTROL BOX  
ACCESS  
DISCONNECT SWITCH LOCATION  
AND MOTOR ACCESS PANEL FOR  
UNIT WITH “BELT-DRIVE” OPTION  
FIGURE 8 - DISCONNECT/BLOWER ACCESS  
LOCATION  
TABLE 19: MINIMUM CLEARANCES  
CLEARANCE  
LOCATION  
Front  
24” (Cooling/Electric Heat)  
32” (Gas Heat)  
12” (Less Economizer)  
36” (With Economizer or Fixed Air/  
Motorized Damper)  
Rear  
24” (Less Economizer)  
36” (With Economizer)  
Left Side (Filter Access)  
Right Side (Cond. Coil)  
Below Unit1  
24”  
0”  
72” (For  
Condenser Air Discharge)  
Above Unit2  
1. Units may be installed on combustible floors made  
from wood or class A, B, or C roof covering material.  
2. Units must be installed outdoors. Overhanging struc-  
tures or shrubs should not obstruct condenser air dis-  
charge outlet.  
18  
Unitary Products Group  
         
254599-YTG-C-0807  
FIGURE 9 - TYPICAL APPLICATIONS  
Unitary Products Group  
19  
 
254599-YTG-C-0807  
BACK OF UNIT  
BACK OF UNIT  
A
A
7
7
44 /8  
44 /8  
1
1
82 /4  
82 /4  
B
D
F
X
X
B
C
E
APPROXIMATE  
APPROXIMATE  
CENTER OF GRAVITY  
CENTER OF GRAVITY  
CONDENSER COIL  
END OF UNIT  
CONDENSER COIL  
END OF UNIT  
C
D
FRONT OF UNIT  
FRONT OF UNIT  
Y
Y
FIGURE 10 - FOUR AND SIX POINT LOADING  
TABLE 20: DF 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION  
4-Point Loading (lb)  
6-Point Loading (lb)  
UNIT  
TOTAL  
A
B
C
D
A
B
C
D
E
F
147  
158  
160  
162  
144  
155  
157  
159  
183  
197  
200  
202  
186  
201  
203  
206  
98  
97  
96  
122  
131  
133  
135  
123  
132  
134  
136  
125  
134  
136  
138  
DF072 Cooling/ Electric  
DF072D06  
660  
710  
720  
730  
105  
107  
108  
104  
106  
107  
103  
104  
106  
DF072N08  
DF072(D,N)10  
TABLE 21: CENTER OF GRAVITY  
3 - 5 TON  
40-¾”  
6 TON  
44”  
DIMENSION  
X
Y
19-¾”  
22”  
TABLE 22: DF OPERATING WEIGHTS (LBS.)  
MODEL SIZE  
6 TON  
660  
-
DF (Cooling Only)  
N04  
N06  
N08  
N10  
D06  
D10  
-
BASIC  
UNIT  
720  
730  
760  
730  
50  
DF  
(Gas/Electric)  
Economizer  
Motorized Damper  
26  
OPTIONS  
ACCY.  
5 - 7 kW  
10 - 15 kW  
20 - 30 kW  
18  
Electric Heater  
23  
28  
Roof Curb  
92  
Barometric Relief / Fixed Air Damper  
Belt-Drive Blower  
10  
5
20  
Unitary Products Group  
       
254599-YTG-C-0807  
FIGURE 11 - ROOF CURB DIMENSIONS  
with a compressor lockout circuit, a terminal strip for thermo-  
stat wiring, plus an additional set of pin connectors to simplify  
the interface of additional field controls. All units have long  
lasting powder paint cabinets with 1000 hour salt spray test  
approval under ASTMB117 procedures. All models are CSA  
listed. All models include a 1-year limited warranty on the  
complete unit. Compressors and electric heater elements  
carry a 5-year warranty. Aluminized steel and Stainless steel  
tubular heat exchangers carry a 10-year warranty.  
GUIDE SPECIFICATIONS  
GENERAL  
Units shall be manufactured by York International Unitary  
Products Group in an ISO 9001 certified facility.  
TM  
York's Sunline Plus units are convertible single package  
units. Although the units are primarily designed for curb mount-  
ing on a roof, they can also be slab-mounted at ground level or  
set on steel beams above a finished roof. Cooling only, cooling  
with gas heat and cooling with electric heat models are available  
with a wide variety of factory-mounted options and field-installed  
accessories to make them suitable for almost every application.  
All units are self-contained and assembled on full perimeter  
base rails with holes in the four corners for overhead rigging.  
Every unit is completely piped, wired, charged and tested at the  
factory to simplify the field installation and to provide years of  
dependable operation. All models (including those with an econ-  
omizer) are suitable for either bottom or horizontal duct connec-  
tions. Models with power exhaust are suitable for bottom duct  
connections only. For bottom duct, remove the sheet metal pan-  
els from the supply and return air openings through the base of  
the unit. For horizontal duct, remove the supply and return air  
panels on the rear of the unit.  
DESCRIPTION  
Units shall be factory-assembled, single packaged, Electric  
Cooling/Gas Heat, Electric Cooling/Optional Electric Heat  
and designed for outdoor mounted installation.  
The 6 ton unit is rated at 10.4 EER. They shall have built-in  
field convertible duct connections for down discharge supply/  
return or horizontal discharge supply/return, and be available  
with factory installed options or field installed accessories. The  
units shall be factory wired, piped, charged with R-22 refriger-  
ant and factory tested prior to shipment. All unit wiring shall be  
both numbered and color coded. All units the cooling perfor-  
mance shall be rated in accordance with DOE and ARI test  
procedures. Units shall be CSA listed, classified to ANSI  
Z21.47, UL 1995/CSA No. 236 standards.  
All compressors include crankcase heaters and all compres-  
sors have internal pressure relief. Every refrigerant circuit  
includes a liquid line filter-drier, a discharge line high pres-  
sure switch and a suction line with a freezestat and low pres-  
sure/loss of charge switch.The unit control circuit includes a  
75 VA transformer, a 24-volt circuit breaker and a relay board  
UNIT CABINET  
Unit cabinet shall be constructed of G90 galvanized steel,  
with exterior surfaces coated with a non-chalking, powdered  
paint finish, certified at 1000 hours salt spray test per  
ASTMB117 standards. Indoor blower section shall be  
Unitary Products Group  
21  
   
254599-YTG-C-0807  
insulated with a minimum 1/2” thick insulation, coated on the  
airside. Aluminum foil faced insulation shall be used in the  
furnace compartment and be fastened with ridged fasteners  
to prevent insulation from entering the air stream. Cabinet  
panels shall be “large” size, easily removable for servicing  
and maintenance. Full perimeter base rails shall be provided  
to assure reliable transit of equipment, overhead rigging and  
proper sealing on roof curb applications. Disposable 1" filters  
shall be furnished and be accessible through a removable  
access door, sealed airtight. Units filter track shall be  
designed to accommodate either 1” or 2” filters. Fan  
performance measuring ports shall be provided on the  
outside of the cabinet to allow accurate air measurements of  
evaporator fan performance without removing panels or  
creating air by-pass of the coils. Condensate pan shall be  
internally sloped and conform to ASHRAE 62-89 self-draining  
standards. Condensate connection shall be a minimum of 3/  
4” I.D. female and be a ridged mount connection.  
b. Evaporator and Condenser coils shall be of the  
direct expansion, draw-thru, design.  
Refrigerant Circuit and Refrigerant Safety Components shall  
include:  
a. Thermal expansion devices (TXV’s).  
• DF072 uses a fixed orifice distributor.  
b. Filter drier/strainer to eliminate any moisture or for-  
eign matter.  
c. Accessible service gage connections on both suc-  
tion and liquid lines to charge, evacuate, and mea-  
sure refrigerant pressure during any necessary  
servicing or troubleshooting without losing charge.  
d. The refrigeration system shall provide at least 15°F  
of sub-cooling at design conditions.  
UNIT CONTROLS  
a. Unit shall be complete with self-contained low-volt-  
age control circuit protected by a resetable circuit  
breaker on the 24-volt transformer side.  
INDOOR (EVAPORATOR) FAN ASSEMBLY  
The indoor fan shall be direct drive, multi-speed, or a factory  
installed belt drive assembly that includes an adjustable pitch  
motor pulley. Job site selected brake horsepower (B.H.P.)  
shall not exceed the motors nameplate horsepower rating,  
plus the service factor. Units shall be designed not to operate  
above service factor. Fan wheel shall be double-inlet type  
with forward-curved blades, dynamically balanced to operate  
smoothly throughout the entire range of operation. Airflow  
design shall be constant air volume. Bearings shall be sealed  
and permanently lubricated for longer life and no mainte-  
nance.  
b. Unit shall incorporate a lockout circuit which pro-  
vides reset capability at the space thermostat or  
base unit, should any of the following standard  
safety devices trip and shut off compressor.  
c. Loss-of-charge/Low-pressure switch.  
d. High-pressure switch.  
e. Freeze-protection thermostat, evaporator coil.  
f. If any of the above safety devices trip, a LED (light-  
emitting diode) indicator shall flash a diagnostic  
code that indicates which safety switch has tripped.  
OUTDOOR (CONDENSER) FAN ASSEMBLY  
The outdoor fan shall be of the direct-driven propeller type,  
discharge air vertically, have aluminum blades riveted to a  
corrosion resistant steel spider bracket and shall be dynami-  
cally balanced for smooth operation. The outdoor fan motor  
shall be totally enclosed with permanently lubricated bear-  
ings, internally protected against overload conditions and  
staged independently.  
g. Unit shall incorporate “AUTO RESET” compressor  
over temperature, over current protection.  
h. Unit shall operate with conventional thermostat  
designs and have a low voltage terminal strip for  
easy hook-up.  
i.  
Unit control board shall have on-board diagnostics  
and fault code display.  
REFRIGERANT COMPONENTS  
j.  
Standard controls shall include anti-short cycle and  
low voltage protection, and permit cooling operation  
down to 0°F.  
Compressor:  
a. Shall be internally protected with internal high-pres-  
sure relief and over temperature protection.  
k. Control board shall monitor each refrigerant safety  
switch independently.  
b. Shall have internal spring isolation and sound muf-  
fling to minimize vibration and noise, and be exter-  
nally isolated on a dedicated, independent  
mounting.  
l.  
Control board shall retain last 5 fault codes in non  
volatile memory, which will not be lost in the event of  
a power loss.  
Coils:  
GAS HEATING SECTION (SINGLE OR 2 STAGE)  
a. Evaporator and condenser coils shall have alumi-  
num plate fins mechanically bonded to seamless  
internally enhanced copper tubes with all joints  
brazed. Special Phenolic coating shall be available  
as a factory option.  
Shall be designed with induced draft combustion with post  
purge logic, energy saving direct spark ignition, and redun-  
dant main gas valve. Venter wheel shall be constructed of  
stainless steel for corrosion resistance. The heat exchanger  
shall be of the tubular type, constructed of T1-40 aluminized  
22  
Unitary Products Group  
254599-YTG-C-0807  
steel for corrosion resistance and allowing minimum mixed  
air entering temperature of 25°F. Burners shall be of the  
inshot type, constructed of aluminum coated steel and con-  
tain air mixture adjustments. All gas piping shall enter the unit  
cabinet at a single location through either the side or curb,  
without any field modifications. Integrated control boards  
shall provide timed control of evaporator fan functioning and  
burner ignition. Heating section shall be provided with the fol-  
lowing minimum protection:  
ELECTRONIC ENTHALPY AUTOMATIC ECONO-  
MIZER- Outdoor and return air dampers that are inter-  
locked and positioned by a fully-modulating, spring  
return damper actuator. The maximum leakage rate for  
the outdoor air intake dampers shall not exceed 2%  
when dampers are fully closed and operating against a  
pressure differential of 0.5 IWG. A unit-mounted potenti-  
ometer shall be provided to adjust the outdoor and return  
air damper assembly to take in CFM of outdoor air to  
meet the minimum ventilation requirement of the condi-  
tioned space during normal operation. During econo-  
mizer operation, a mixed-air temperature control shall  
modulate the outdoor and return air damper assembly to  
prevent the supply air temperature from dropping below  
55°F. Changeover from compressor to economizer oper-  
ation shall be provided by an integral electronic enthalpy  
control that feeds input into the basic module. The out-  
door intake opening shall be covered with a rain hood  
that matches the exterior of the unit. Water eliminator/fil-  
ters shall be provided. Simultaneous economizer/com-  
pressor operation is also possible. Dampers shall fully  
close on power loss.  
a. Primary and auxiliary high-temperature limit switches.  
b. Induced draft motor speed sensor.  
c. Flame roll out switch.  
d. Flame proving controls.  
e. If any of the above safety devices trip, a LED (light-  
emitting diode) indicator shall flash a diagnostic  
code that indicates which safety switch has tripped.  
ELECTRIC HEATING SECTION  
An electric heating section, with nickel chromium elements,  
shall be provided in a range of 5 thru 30 KW, offering two  
stages of capacity - 16 KW and above on 208/230 volt heaters  
and 20 KW and above on 460 and 575 volt heaters. The heat-  
ing section shall have a primary limit control(s) and automatic  
reset to prevent the heating element system from operating at  
an excessive temperature. The heating section assembly  
shall slide out of the unit for easy maintenance and service.  
Units with Electric Heating shall be wired for a single point  
power supply with branch circuit fusing (where required).  
MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air  
dampers are positioned by a 2-position, spring-return  
damper actuator. The maximum leakage rate for the out-  
door air intake dampers shall not exceed 2% when  
dampers are fully closed and operating against a pres-  
sure differential of 0.5 IWG. A unit-mounted potentiome-  
ter shall be provided to adjust the outdoor damper  
assembly to take in the design CFM of outdoor air to  
meet the ventilation requirements of the conditioned  
space during normal operation. Whenever the indoor fan  
motor is energized, the dampers open up to one of two  
pre-selected positions - regardless of the outdoor air  
enthalpy. Dampers return to the fully closed position  
when the indoor fan motor is de-energized. Dampers  
shall fully close on power loss.  
UNIT OPERATING CHARACTERISTICS  
a. Unit shall be capable of starting and running at 125°F  
outdoor temperature, exceeding maximum load crite-  
ria of ARI Standard 210/240. The compressor, with  
standard controls, shall be capable of operation down  
to 0°F outdoor temperature. Unit shall be provided  
with fan time delay to prevent cold air delivery before  
heat exchanger warms up (Gas heat only).  
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE  
ROOF CURB - 14"and 8” high, full perimeter curb with  
wood nailer (shipped knocked-down).  
ELECTRICAL REQUIREMENTS  
All unit power wiring shall enter unit cabinet at a single factory  
provided location and be capable of side or bottom entry, to  
minimize roof penetrations and avoid unit field modifications.  
Separate side and bottom openings shall be provided for the  
control wiring.  
BAROMETRIC RELIEF DAMPER - Contains a rain  
hood, air inlet screen, exhaust damper and mounting  
hardware. Used to relieve internal air pressure through  
the unit.  
PROPANE CONVERSION KIT - Contains new orifices  
and gas valve parts to convert from natural to L.P. gas.  
One per unit required.  
STANDARD LIMITED WARRANTIES  
Compressor 5 Years  
HIGH ALTITUDE - NATURAL GAS - Contains orifices  
required for applications between 2000 and 6000 feet  
altitude.  
Heat Exchanger 10 Years  
Electric Heat Element 5 Years  
Other Parts 1 Year  
HIGH ALTITUDE - PROPANE GAS - Contains orifices  
required for applications between 2000 and 6000 feet  
altitude. Must be used with propane conversion kit.  
OPTIONAL OUTDOOR AIR (Shall be made available by  
either/or):  
LOW NOX - Required to reduce the emission of nitrogen  
oxides below 40 nanograms per joule.  
Unitary Products Group  
23  
GAS PIPING - Contains 1/2” pipe nipples, fittings and  
gas cock (including panel assess gaskets) required for  
bottom gas supply connection with external shut off.  
TECHNICOAT PHENOLIC COATED CONDENSER  
AND EVAPORATOR COIL  
ELECTRONIC SINGLE ENTHALPY ECONOMIZER  
DIRTY FILTER SWITCH  
POWER EXHAUST OPTION - To work in conjunction  
with economizers.  
PHASE MONITOR  
ELECTRIC HEATERS  
COIL GUARD  
ECONOMIZER/MOTORIZED DAMPER RAIN HOOD -  
Contains all hood panels and the hardware for assem-  
bling.  
POWERED GFI CONVENIENCE OUTLET  
NON-POWERED GFI CONVENIENCE OUTLET  
MANUAL OUTDOOR AIR DAMPER  
COIL GUARD KIT - Guard for cooling coil.  
HAIL GUARD  
®
BAS CONTROLS (S implicity INTELLI- Comfort™,  
CPC, JOHNSON, HONEYWELL, NOVAR)  
BAS READY ECONOMIZER (2 - 10 V. D. C.  
ACTUATOR WITHOUT A CONTROLLER)  
FLUE EXHAUST EXTENSION  
HINGED FILTER DOOR ACCESS AND TOOLESS  
ACCESS PANELS  
OTHER FACTORY INSTALLED OPTIONS  
POWER EXHAUST OPTION - To work in conjunction  
with economizers.  
2" PLEATED FILTERS  
DISCONNECT SWITCH  
STAINLESS STEEL HEAT EXCHANGER  
STAINLESS STEEL DRAIN PAN  
BOTTOM DRAIN CONNECTION  
SUPPLY AIR SMOKE DETECTOR  
RETURN AIR SMOKE DETECTOR  
Subject to change without notice. Printed in U.S.A.  
254599-YTG-C-0807  
Copyright © 2007 by Unitary Products Group. All rights reserved.  
Supersedes: 254599-YTG-B-0507  
Unitary  
Products  
Group  
5005  
York  
Drive  
Norman  
OK  
73069  

Microsoft C4500 User Manual
Ryobi 130503005 User Manual
Saleen Rear Wing Kit S281sc User Manual
Samsung Uq24a1 2 Rc User Manual
Sanyo Ch2432 User Manual
Sanyo Dhx3652 User Manual
Sony Infolithium Np Fp30 User Manual
Xantrex Technology 10 User Manual
Xerox Workcentre Pro 40 Color User Manual
Zebra Technologies Encore User Manual