| SUNLINE 2000   ® ELECTRIC / ELECTRIC & GAS / ELECTRIC   SINGLE PACKAGE AIR CONDITIONERS   (Constant Air Volume)   Supersedes: 530.18-N11Y (195)   530.18-N11Y (399)   035-16133   INSTALLATION INSTRUCTION   MODELS D2CE & D2CG300   (8.5 EER)   208/230/575   VOLT ONLY   208/230/460   VOLT ONLY   DCG MODEL   SHOWN   SAFETY CONSIDERATIONS   INSPECTION   Due to system pressure, moving parts and electrical components,   installation and servicing of air conditioning equipment can be   hazardous. Only qualified, trained, service personnel should   install, repair, maintain or service this equipment.   ‘YORK Model DCE and DCG units are single package air   conditioners designed for outdoor installation on a rooftop or a   slab and is manufactured under ISO 9002 Quality System   Certification. The DCE models are cooling only and can be   equipped with factory installed electric heaters for cooling /   heating applications. The DCG models are gas-fired central   heating furnaces with cooling.   The units are completely assembled on rigid, permanently attached   baserails.Allpiping, refrigerantcharge, andelectricalwiringisfactory   installed and tested.All units require electric power, duct connections   and fixed outdoor air intake damper (units without economizer or   motorized damper option only) at the point of installation.   As soon as a unit is received, it should be inspected for   possible damage during transit. If damage is evident, the   extent of the damage should be noted on the carrier’s freight   bill. A separate request for inspection by the carrier’s agent   should be made in writing. Refer to Form 50.15-NM for   additional information.   REFERENCE   Additional information on the design, installation, operation and   service of this equipment is available in the following reference forms:   • 44-320-10   - Barometric Relief Damper Accessory   • 530.18-N6.1V - Propane Conversion Accessory   • 530.18-N6.2V - High Altitude Accessory (Nat. Gas)   • 530.18-N6.3V - High Altitude Accessory (Propane)   • 530.18-n13y - Coil Guard Installation   Renewal Parts:   The DCG units additionally require gas connection, installation of the   combustion air inlet hood and the flue gas outlet hoods at the point of   installation.The gas-fired heaters have aluminized-steel tubular heat   exchangers and spark ignition with proven pilot.   Supplemental electric heaters for DCE units have nickel-chrome   elements and utilize single point power connections.   • Refer to the Renewal Parts Manual for complete listing of   replacement parts on this equipment.   All forms referenced in this instruction may be ordered from:   Publications Distribution Center   Unitary Products Group   P.O. Box 1592, York, Pa. 17405   The following safety precautions apply to DCG units:   APPROVALS   Design certified by ETL & CGA as follows:   FOR YOUR SAFETY   1. For use as a central cooling only unit with or without   supplemental electric heat. (DCE models)   If you smell gas:   1. Open windows.   2. For useas aforced air furnacewithcoolingunit.(DCGmodels)   3. For use with natural gas or propane gas. (DCG models)   4. For outdoor installation only.   2. Don’t touch electrical switches; do not use   any phones in the area of the gas leak.   3. Extinguish any open flame.   4. Immediately call your gas supplier from another   location.Follow your gas supplier’s   instructions.   5. For installation on combustible material.   CAUTION   THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH   THE ENCLOSED INSTALLATION INSTRUCTIONS AND ANY   APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUDING, BUT   NOT LIMITEDTO, BUILDING, ELECTRICAL, AND MECHANICALCODES.   5. If you cannot reach your gas supplier, call the   fire department.   WARNING   FOR YOUR SAFETY   INCORRECT INSTALLATION MAY CREATE A CONDITION   WHERE THE OPERATION OF THE PRODUCT COULD CAUSE   PERSONAL INJURY OR PROPERTY DAMAGE   Do not store or use gasoline or other flammable   vapors and liquids in the vicinity of this or any   other appliance.   Installer should pay particular attention to the words: NOTE, CAUTION and WARNING. Notes are intended to clarify or make   the installation easier.Cautions are given to prevent equipment damage.Warnings are given to alert installer that personal injury   and/or equipment damage may result if installation procedure is not handled properly.   530.18-N11Y   INSTALLATION   CAUTION: If a unit is to be installed on a roof curb or special   frame, gasketing must be applied to all surfaces   that come in contact with the unit underside.   LIMITATIONS   These units must be installed in accordance with the following   applicable national and local safety codes:   In U.S.A.:   1. National Electrical Code ANSI/NFPA No. 70.   2. National Fuel Gas Code Z223.1.   3. Gas-Fired Central Furnace Standard ANSI Z21.47a.   4. Local gas and electric utility requirements.   In Canada:   5. Maintain level tolerance to 1/2" maximum across the entire   length or width of the unit.   RIGGING AND HANDLING   Exercise care when moving the unit. Do not remove any   packaging until the unit is near the place of installation. Rig the   unit by attaching chain or cable slings to the round lifting holes   provided in the base rails. Spreaders, whose length exceeds   the largest dimension across the unit, MUST be used across   the top of the unit.   Units may also be moved or lifted with a forklift, from the front   or rear only, providing that an accessory skid is used.   LENGTH OF FORKS MUST BE A MINIMUM OF 90".   1. Current Canadian Electrical Code C22.1.   2. Current Gas Installation Codes CAN/CGA-B149.1 and .2   3. Local plumbing and waste water codes.   4. Other applicable local codes.   Refer to the Unit Application Data Table and to the Gas Heat Application   DataTable.   CAUTION: On gas heating units, an adhesive backed label is   provided over the outside of the combustion air inlet   opening to prevent moisture from entering the unit   which could cause damage to electrical   components. Allow this closure label to remain in   place until the combustion air hood is to be   installed.   After installation, units with gas heat must be adjusted to obtain a   temperature rise within the range specified on the unit rating plate.   If components are to be added to a unit to meet local codes, they   are to be installed at the dealer’s and/or the customer’s expense.   Size of unit for proposed installation should be based on heat   loss/heat gain calculation made according to the methods of   the Air Conditioning Contractors of America (ACCA).   This furnace is not to be used for temporary heating of buildings   or structures under construction.   TABLE 1 - UNIT APPLICATION DATA   208/230-3-60   460-3-60   575-3-60   187 / 253   414 / 506   518 / 630   Voltage Variation,   Min. / Max.1   Supply Air CFM, Min. / Max.   8,000 / 12,000   Wet Bulb Temperature (°F) of Air on   57 / 72   Evaporator Coil, Min. / Max.   Dry Bulb Temperature (°F) of Air on   25 / 120   Condenser Coil, Min.2 / Max.   1 2 Utilization range “A” in accordance with ARI Standard 110.   A low ambient accessory is available for applications down to 0°F.   LOCATION   Use the following guidelines to select a suitable location for   these units.   FIG. 1 - TYPICAL RIGGING   1. Unit is designed for outdoor installation only.   2. Condenser coils must have an unlimited supply of air.   Where a choice of location is possible, position the unit on   either north or east side of building.   3. For ground level installation, use a level concrete slab with   a minimum thickness of 4 inches. The length and width   should be at least 6 inches greater than the unit base rails.   Do not tie slab to the building foundation.   5 4 136-1/4"   WARNING:Excessive exposure of this furnace to contami-   nated combustionair may resultinequipmentdam-   age or personal injury. Typical contaminates in-   clude: permanent wave solutions, chlorinated   waxes and cleaners, chlorine based swimming   pool chemicals, water softening chemicals, carbon   tetrachloride, Halogen type refrigerants, cleaning   solvents (e.g. perchloroethylene), printing inks,   paint removers, varnishes, hydrochloric acid, ce-   ments and glues, antistatic fabric softeners for   clothes dryers, masonry acid washing materials.   FIG. 2 - CENTER OF GRAVITY   CLEARANCES   All units require certain clearances for proper operation and   service. Installer must make provisions for adequate combustion   and ventilation air in accordance with Section 5.3, Air for   Combustion and Ventilation of the National Fuel Gas Code, ANSI   Z223.1 (in U.S.A.) or Sections 7.2, 7.3 or 7.4 of Gas Installation   Codes CAN/CGA-B149.1 and .2 (in Canada) and/or applicable   provisions of the local building codes. Refer to Dimensions and   Clearances table for the clearances required for combustible   construction, servicing, and proper unit operation.   4. Roof structures must be able to support the weight of the   unit and its options and/or accessories. Unit must be in-   stalled on a solid level roof curb or appropriate angle iron   frame.   WARNING:Do not permit overhanging structures or shrubs to   obstruct outdoor air discharge outlet, combustion   air inlet or vent outlets.   Unitary Products Group   3 530.18-N11Y   DUCTWORK   Ductwork should be designed and sized according to the   methods in Manual Q of the Air Conditioning Contractors of   America (ACCA).   A closed return duct system shall be used. This shall not   preclude use of economizers or outdoor fresh air intake. The   supply and return air duct connections at the unit should be   made with flexible joints to minimize noise.   The supply and return air duct systems should be designed for   the CFM and static requirements of the job. They should NOT   be sized to match the dimensions of the duct connections on   the unit.   CAUTION: When fastening ductwork to side duct flanges on   unit, insert screws through duct flanges only. DO   NOT insert screws through casing.   Outdoor ductwork must be insulated and   waterproofed.   Refer to the Dimensions and Clearances figure for information   concerning side and bottom supply and return air duct openings.   FIG. 3 - FIXED OUTDOOR AIR DAMPER   CONDENSATE DRAIN   It is recommended that, in Canada, the outlet duct on gas   heating units be provided with a removable access panel. It is   recommended that this opening be accessible when the unit   is installed in service, and of a size such that smoke or   reflected light may be observed inside the casing to indicate   the presence of leaks in the heat exchanger.The cover should   be attached in a manner adequate to prevent leakage.   Plumbing must conform to local codes. Use a sealing   compound on male pipe threads.Install a condensate drain line   from the 1" NPT female connection on the unit to an open drain.   FIXED OUTDOOR AIR INTAKE DAMPER   This damper is shipped inside the return air compartment on units   that are not provided with an economizer or a motorized damper   option. It is completely assembled and ready for installation. A   damper baffle inside of the hood is adjustable to provide variable   amounts of outdoor air intake.   Gasketing and mounting screws are provided in a parts bag   attached to the hood assembly. Apply gasketing to the three   flange surfaces on the hood prior to installing the hood. Extend   gasketing 1/4" beyond the top and bottom of the two side   flanges to insure adequate sealing.   FIG. 4 - RECOMMENDED DRAIN PIPING   NOTE: The condensate drain line MUST be trapped to provide   proper drainage.   Adjusting the damper to the desired air flow may be done before   mounting the hood into position or (after installation) by   removing the front hood panel or the screen on the bottom of   the hood. Damper baffle in position 1 will allow approximately   10% recirculated air flow, position 2 approximately 15% and, to   allow approximately 25%, remove the damper baffle.   COMPRESSORS   Units are shipped with compressor mountings factory-adjusted   and ready for operation.   CAUTION: Do Not loosen compressor mounting bolts.   FILTERS   On units with bottom return air applications, install the damper   assembly over the opening in the side return air access panel.   Remove and discard the opening cover and the covering over   the hood mounting holes (used for shipping) before installing.   Secure with the screws provided.   2"filtersaresuppliedwith each unit.Filtersmust alwaysbeinstalled   ahead of the evaporator coil and must be kept clean or replaced   with same size and type. Dirty filters will reduce the capacity of the   unit and will result in frosted coils or safety shutdown.Minimum filter   area and required sizes are shown in the Physical Data Table.   SERVICE ACCESS   Access to all serviceable components is provided by the   following removable panels:   On units with side return air applications, install the damper   assembly on the return air ductwork as close to the unit as   possible. Cut an opening 16" high by 18" wide in the ductwork   to accommodate the damper. Using the holes in the hood   flanges as a template, drill 9/64" dia. (#26 drill) holes into the   ductwork and secure with the screws provided.   • Compressor compartment   • Electric Heat compartment - DCE models   • Gas Heat compartment (Two panels) - DCG models   • Side Supply & Return Air compartments (Two panels)   • Blower compartment (Three panels)   • Main control box   CAUTION: If outdoor air intake will not be required on units   with bottom return air applications, the damper   assembly should stillbemountedonthesidereturn   air access panel, per the instructions above, to   insure moisture is not drawn into the unit during   operation. The covering over the mounting holes   only need be removed. Do not remove the opening   cover.   • Filter compartment   • Outdoor Air compartment (Two panels)   Refer to the Dimensions and Clearances figure for location of these   access panels.   CAUTION: Make sure that all screws and panel latches are   replaced and properly positioned on the unit to   maintain an air-tight seal.   4 Unitary Products Group   530.18-N11Y   CONTROL WIRE SIZES   Wire Size1 AWG. Gauge   22   25   20   40   19   18   65   16   50   100   Maximum Wire Length2 Feet   Notes:   1. Solid, Class II copper wire   FIG. 5 - TYPICAL FIELD WIRING   Unitary Products Group   5 530.18-N11Y   THERMOSTAT   COMBUSTION DISCHARGE (DCG Models)   The room thermostat should be located on an inside wall   approximately 56" above the floor where it will not be subject   to drafts, sun exposure or heat from electrical fixtures or   appliances. Follow manufacturer’s instructions enclosed with   thermostat for general installation procedure. Seven color   coded insulated wires should be used to connect thermostat to   unit.   The products of combustion are discharged horizontally   through two screened (hooded) openings on the upper gas   heat access panel.   POWER AND CONTROL WIRING   Field wiring to the unit must conform to provisions of the   National Electrical Code, ANSI / NFPA No. 70 (in U.S.A.),   current Canadian Electrical Code C22.1 (in Canada) and/or   local ordinances. The unit must be electrically grounded in   accordance with NEC and CEC (as specified above) and/or   local codes. Voltage tolerances which must be maintained at   the compressor terminals during starting and running   conditions are indicated on the unit Rating Plate.   The internal wiring harness furnished with this unit is an integral   part of a ETL and CGA design certified unit. Field alteration to   comply with electrical codes should not be required.   FIG. 6 - EXTERNAL SUPPLY CONNECTION   EXTERNAL SHUT-OFF   A fused disconnect switch should be field provided for the unit.   The switch must be separate from all other circuits. Wire entry   at knockout openings require conduit fittings to comply with   NEC (in U.S.A.), CEC (in Canada) and/or local codes. If any   ofthe wire supplied withthe unit mustbereplaced, replacement   wire must be of the type shown on the wiring diagram and the   same minimum gauge as the replaced wire.   Electrical line must be sized properly to carry the load. Each   unit must be wired with a separate branch circuit fed directly   from the meter panel and properly fused.   GAS PIPING (DCG Models)   Proper sizing of gas piping depends on the cubic feet per hour   of gas flow required, specific gravity of the gas and the length   of run. “National Fuel Gas Code” Z223.1 (in U.S.A.) or the   current Gas Installation Codes CAN/CGA-B149.1 and .2 (in   Canada) should be followed in all cases unless superseded by   local codes or gas utility requirements. See Pipe Sizing table.   The heating value of the gas may differ with locality. The value   should be checked with the local gas utility.   CAUTION: When connecting electrical power and control   wiring to the unit, waterproof type connectors   MUST BE USED so that water or moisture cannot   be drawn into the unit during normal operation.The   above waterproofing conditions will also apply   when installing a field-supplied disconnect switch.   NOTE: There may be a local gas utility requirement specifying   a minimum diameter for gas piping. All units require a   1 inch pipe connection at the entrance fitting.   TABLE 3 - PIPE SIZING   Nominal Iron Pipe Size   Length in Feet   Refer to Typical Field Wiring Figure for typical field wiring and to   the appropriate unit wiring diagram for control circuit and power   wiring information.   1 in.   1-1/4 in.   10   20   30   40   50   60   70   80   90   100   520   350   285   245   215   195   180   170   160   150   1,050   730   590   500   440   400   370   350   320   305   OPTIONAL ELECTRIC HEATERS (DCE Models)   The factory installed heaters are wired for single point power   supply.Power supply need only be brought into the single point   terminal block and thermostat wiring to the low voltage terminal   block located in the upper portion of the unit control box.   Maximum capacity of pipe in cubic feet of gas per hour. (Based upon a pressure drop of 0.3   inch water column and 0.6 specific gravity gas).   These ETL and CGA approved heaters are located within the   central compartment of the unit with the heater elements   extending into the supply air chamber. Refer to the Dimension   and Clearances figure for access panel location.   GAS CONNECTION (DCG Models)   The gas supply line can be routed through the knockouts   located on the front of the unit or through the opening provided   in the unit’s base. Typical supply piping arrangements are   shown in the Supply Connection figures. All pipe, fittings, etc.   are field-supplied.   Two grommets are shipped in the blower compartment (in parts   bag taped to the blower housing) of every unit with gas heat   and should be used in the knockouts when the gas piping   enters through the front of the unit.   Fuses are supplied, where required, by the factory. Some KW   sizes require fuses and others do not. Refer to the Unit   Application Data Table 1 for minmum CFM limitations and to   Electrical Data Table.   TABLE 2 - GAS HEAT APPLICATION DATA   Input Capacity (Mbh)   Output Capacity (Mbh)   Temp.   Rise °F   At   After the gas supply piping has been installed, the bottom   opening in the unit should be sealed to prevent water from   leaking into the building.   0 To   2,000 To   0 To 2,000 To   Gas   Rate2   2,000 Feet   Above   Sea Level   4,500 Feet 2,000 Feet 4,500 Feet   Above Above Above   Sea Level1 Sea Level Sea Level1   Full Input 3   (Ft.3/Hr.)   Gas piping recommendations:   Max. Min. Max. Min.   Max.   240   Max.   213   Min.   20   Max.   50   1. A drip leg and a ground joint union must be installed in the   gas piping.   2. When required by local codes, a manual shut-off valve may   have to be installed outside of the unit.   3. Use wrought iron or steel pipe for all gas lines. Pipe com-   pound should be applied sparingly to male threads only.   300   400   150 270 135   200 360 180   279   372   320   281   30   60   NOTE: Heaters are shipped available for natural gas, but can be converted to   L.P. / Propane with Kit Model No. 1NP0418.   1 MBH rating should be reduced at the rate of 4 percent for each 1,000 feet above 4,500 feet.   2 3 3 Based on maximum input and 1075 Btu/Ft .   The air flow must be adjusted to obtain a temperature rise within the range shown.   6 Unitary Products Group   530.18-N11Y   L.P. UNITS, TANKS AND PIPING (DCG Models)   All gas heat units are shipped from the factory equipped for   natural gas use only. The unit may be converted in the field for   use with L.P./propane gas with accessory kit model number   1NP0418.   All L.P./propane gas equipment must conform to the safety   standards of the National Fire Protection Association.   For satisfactory operation, L.P./propane gas pressure must be   8.8 inch W.C at the unit under full load. Maintaining proper gas   pressure depends on three main factors:   FIG. 7 - BOTTOM SUPPLY CONNECTION   1. The vaporization rate which depends on (a) the tempera-   ture of the liquid and (b) the “wetted surface” area of the   container or containers.   EXTERNAL SHUT-OFF   WARNING:Natural gas may contain some propane. Propane,   being an excellent solvent, will quickly dissolve   white lead or most standard commercial   compounds. Therefore, a special pipe compound   must be applied when wrought iron or steel pipe is   used. Shellac base compounds such as Gaskolac   or Stalastic, and compounds such as Rectorseal   #5, Cyde’s or John Crane may be used.   2. The proper pressure regulation. (Two-stage regulation is   recommended from the standpoint of both cost and effi-   ciency.)   3. The pressure drop in the lines between regulators and   between the second stage regulator and the appliance.   Pipe size required will depend on the length of the pipe run   and the total load of all appliances.   4. All piping should be cleaned of dirt and scale by hammering   on the outside of the pipe and blowing out the loose dirt and   scale. Before initial start-up, be sure that all of the gas lines   external to the unit have been purged of air.   Complete information regarding tank sizing for vaporization,   recommended regulator settings, and pipe sizing is available   from most regulator manufacturers and L.P./propane gas   suppliers.   5. The gas supply should be a separate line and installed in   accordance with all safety codes as prescribed under   “Limitations”. After the gas connections have been   completed, open the main shut-off valve admitting normal   gas pressure to the mains. Check all joints for leaks with   soap solution or other material suitable for the purpose.   NEVER USE A FLAME.   L.P./propane gas is an excellent solvent and special pipe   compound must be used when assembling piping for this gas   as it will quickly dissolve white lead or most standard   commercial compounds. Shellac base compounds such as   Rectorseal #5 are satisfactory for this type of gas.   6. The furnace and its individual manual shut-off valve must   be disconnected from the gas supply piping system during   any pressure testing of that system at test pressures in   excess of 1/2 psig (3.48kPa).   Check all connections for leaks when piping is completed,   using a soap solution. NEVER USE A FLAME.   The furnace must be isolated from the gas supply piping   system by closing its individual manual shut-off valve during   any pressure testing of the gas supply piping system at test   pressures equal to or less than 1/2 psig (3.48kPa).   7. A 1/8 inch NPT plugged tapping, accessible for test gage   connection, must be installed immediately upstream of the   gas supply connection to the furnace.   Unitary Products Group   7 530.18-N11Y   VENT AND COMBUSTION AIR HOODS   (DCG Models)   OPTIONAL ECONOMIZER/MOTORIZED DAMPER   RAIN HOOD   The instruction for the optional economizer/motorized damper   rain hood can be found in form 44-320-2.Use these instructions   when field assembling an economizer rain hood onto a unit.   The outdoor and return air dampers, the damper actuator, the   damper linkage, the outdoor and return air divider baffles, and   all the control sensors are factory mounted as part of the   "Factory installed" economizer option.   Two vent hoods and a combustion air hood (with screens) are   shipped attached to the blower housing in the blower   compartment. These hoods must be installed to assure proper   unit function. All hoods must be fastened to the outside of the   gas heat access panel with the screws provided in the bag also   attached to the blower housing.   ENTHALPY SET POINT ADJUSTMENT   The screen for the combustion air intake hood is secured to the   inside of the access panel opening with four fasteners and the   screws used for mounting the hood to the panel.The top flange   of this hood slips in under the top of the access panel opening   when installing.Refer to the Vent and Combustion Hood figure.   Remove the economizer access panel from the unit to check   the following adjustments. Loosen but do not remove the two   panel latches.   Each vent hood is installed by inserting the top flange of the   hood into the slotted opening in the access panel and securing   in place.   CAUTION: Extreme care must be exercised in turning both the   setpoint and minimum position adjusting screws to   prevent twisting them off.   1. The enthalpy set point may now be set by selecting the   desired setpoint shown in the Enthalpy figure. Adjust as   follows:   • For a single enthalpy operation, carefully turn the set   point adjusting screw to the “A”, “B”, “C” or “D” setting   corresponding to the lettered curve.   • For a dual enthalpy operation, carefully turn the set point   adjusting screw fully clockwise past the “D” setting.   SLOTTED   OPENINGS IN   ACCESS PANEL   VENT AIR   OUTLET   HOODS   2. To check that the damper blades move smoothly without   binding, carefully turn the minimum position adjusting   screw fully clockwise and then energize and de-energize   terminals “R” to “G”. With terminals “R” to “G” energized,   turn the minimum position screw counterclockwise until the   desired minimum position has been attained.   3. Replace the economizer access panel. Reposition the two   latches horizontally and retighten the screws.   POWER EXHAUST/BAROMETRIC RELIEF DAMPER   AND RAIN HOOD OPTION   COMBUSTION   AIR INTAKE   HOOD   GAS HEAT   ACCESS   PANELS   The instructions for the power exhaust/barometric relief   damper and rain hood can be found in form 44-320-10. The   exhaust fan, all supporting brackets, angles, and the wiring are   factory installed as part of the power exhaust option.   All of the components, including the dampers, hardware, and   mounting instructions are shipped in a single package external   from the unit. The hood must be field assembled and installed.   FIG. 8 - VENT AND COMBUSTION AIR HOODS   Power exhaust is not available as a field installed option.   8 Unitary Products Group   530.18-N11Y   FIG. 9 - ENTHALPY SETPOINT ADJUSTMENT   Unitary Products Group   9 530.18-N11Y   TABLE 4 - PHYSICAL DATA   DCE/DCG   300   18 x 15   15   OPERATING WEIGHTS (LBS.)   DCE (Cooling only)   25 TON   2730   2930   MODELS   CENTRIFUGAL BLOWER (Dia. x Wd. in.)   FAN MOTOR HP   ROWS DEEP   FINS PER INCH   FACE AREA (Sq. Ft.)   PROPELLER DIA. (in.) (Each)   FAN MOTOR HP   NOM. CFM TOTAL   ROWS DEEP   DCG   (Gas /   Electric)   N240   EVAPORATOR   BLOWER   Basic Unit   N320   2970   160   4 EVAPORATOR   COIL   Economizer   Economizer with   Power Exhaust   13.5   25.0   30   1 7200   3 245   CONDENSER   FAN   (Two Per Unit)   Motorized Damper   150   25   30   35   40   (Each)   (Each)   Options   18 KW   36 KW   54 KW   72 KW   Electric   Heater   (DCE only)   CONDENSER   COIL   FINS PER INCH   FACE AREA (Sq. Ft.)   15   43.3   Roof Curb   Barometric Damper   185   45   COMPRESSOR   (Qty. Per Unit)   12.5-TON TANDEM   2 Economizer/Motorized   Accessories Damper Rain Hood   QUANTITY PER UNIT (16" X 20" X 2")   QUANTITY PER UNIT (16" X 25" X 2")   QUANTITY PER UNIT (14" X 20" X 2")   TOTAL FACE AREA (sq. ft.)   2 4 3 21.4   20/8   20/0   55   AIR   FILTERS   Economizer/Power Exhaust   Rain Hood   Wood Skid   90   220   SYSTEM NO. 1   SYSTEM NO. 2   REFRIGERANT   22 (lbs./oz.)   CHARGE   *This compressor will be energized first.   TABLE 5 - ELECTRICAL DATA - BASIC UNITS   COMPRESSORS   COND. FAN   (#1 & #2)   SUPPLY AIR   BLOWER MOTOR   MINIMUM   CIRCUIT   MAXIMUM   POWER   SUPPLY   (QTY. 2)   OVERCURRENT   MODEL NO.   RLA   LRA   (ea.)   HP   (ea.)   FLA   (ea.)   AMPACITY   (AMPS)   DEVICE (1)   (AMPS)   HP   RLA   (ea.)   41.4   20.0   16.4   D2CE300 208/230-3-60   312   140   108   1 1 1 4.2   2.1   2.0   15   15   15   38.6   19.3   15.4   139.5   68.3   56.1   175   80   70   & D2CG300   460-3-60   575-3-60   VOLTAGE   POWER SUPPLY   MIN.   187   414   518   MAX.   253   VOLTAGE   LIMITATIONS**   208/230-3-60   460-3-60   506   575-3-60   630   **Utilization Range “A” in accordance with ARI Standard 110.   TABLE 6 - ELECTRICAL DATA - UNITS w/ELECTRIC HEAT   MINIMUM   CIRCUIT   MAXIMUM   ELECTRIC HEATER OPTION   MODEL   D2CE   POWER   SUPPLY   OVERCURRENT   DEV ICE (1)   A MPA CITY   MODEL   kW(1)   STAGES AMPS   (AMPS)   139.5   142.1   189.0   198.4   139.5   156.5   178.2   221.5   68.3   (AMPS)   175   175   200   225   175   175   200   250   80   300A25   300A25   300A25   300A25   300A25   300A25   300A25   300A25   300A46   300A46   300A46   300A46   300A58   300A58   300A58   300A58   208-3-60   208-3-60   208-3-60   208-3-60   230-3-60   230-3-60   230-3-60   230-3-60   460-3-60   460-3-60   460-3-60   460-3-60   575-3-60   575-3-60   575-3-60   575-3-60   E018   E036   E054   E072   E018   E036   E054   E072   E018   E036   E054   E072   E018   E036   E054   E072   13.5   27.0   40.6   54.1   18.0   36.0   54.0   72.0   18.0   36.0   54.0   72.0   18.0   36.0   54.0   72.0   1 2 2 2 1 2 2 2 1 2 2 2 1 2 2 2 37.5   75.1   112.6   150.1   43.3   86.6   129.9   173.2   21.7   43.3   65.0   86.6   17.3   34.6   52.0   69.3   78.3   80   89.1   100   125   70   110.7   56.1   62.6   71.2   70   80   88.5   100   NOMINAL VOLTAGE   VOLTAGE   208   KW CAP. MULTIPLIER   208   240   480   600   1.00   0.92   0.92   0.92   230   460   575   10   Unitary Products Group   530.18-N11Y   E F P ( C O O N O M I Z E H R / M O T O R I Z a E D D A M P E R , I X E e D O U T D O O R I N T A K E A I R A N D F D L I E L D - S U P P L I E D W E R E X A U S T R A I N H O O D S All dimensions are in inches. They are sub-   ject to change without notice. Certified di-   mensions will be provided upon request.   I S C O N N E C T S W I T C H S e d e t a i l " Y " ) B A L C O W E R O C A T I O N C A ( O M P R E S G S O R C E S S C C E S S S e e d e t i l " X " ) B A L C O W P E R M O T O R C E S S O C P T I O N A L B C A ( L C O W E R O I L U A R D O M P A R T M E N T C E S S A u x i l i a r y ) 5 2 - 5 / 8 " RETURN AIR   SUPPLY AIR   D ( D O r T L U G F o r p r e s s u r e o p R e a d i n g ) C C O O N I D E N S E R L S 2 1 " 5 " 1 3 6 - 1 / 4 " CONDENSER AIR   F V R O N T 9 - 3 / 4 " E A L C E C T R I C H E A T 9 2 " I E W C E S S ( C E A ) OUTDOOR AIR   (Economizer)   5 - 7 / 8 " O N T R O L W I R I N G C A O N T R O L B O X N T R Y C C E S S 1 1 - 1 / 2 " ( P E B ) 3 5 " B O T T O M S U P P L Y O N W E R W I R I N G A N D R E T U R N T R S Y A I R O P E N I N G ( S e e N o t e ) 3 5 - 1 / 4 " R E T U R N 3 - 3 / 4 " A I R 3 3 " S U P P L Y A I R UTILITIES ENTRY DATA   2 - 3 / 2 4 1 " - 1 / 2 " OPENING   SIZE   (DIA.)   HOLE   A USED FOR   U S B C N I T B A S E W I T H R A I L S ( P E B A ) ) h o o t w n s e p a r a t e l y n t n o i l l u s t r a t e O N W E R W I R I N G t o m D u c t o p e i g s a n d P o w e r T T R R Y Y 1-1/8" KO   3/4" NPS (Fem.)   3-5/8" KO   3" NPS (Fem.)   2-3/8" KO   Front   Bottom   Front   Control   Wiring   o n n e c t i o n l o c a t i o n s ( C E O N T R O L W I R I N G 8 - 1 / 8 " N N F d s O T E : Power   Wiring   B C o r c u r b m o u n t e d u n i t s , r e f e r t o p t h e c u r b z h a n g e r 9 - 1 h / 4 " Bottom   i m e p n s i o n n s o f t h e c u r b f o r t e r o p e r s i e o f t h e 1 2 - 1 / 2 " 9 - 3 / 4 " u p l y a d r e t u r n a i r d u c t c o n n e c t i o n s . Gas Piping (Front)   D 1-11/16" Hole Gas Piping (Bottom)*   E F P ( C O O N O M I Z E H R / M O T O R I Z E D D A M P E R , B A L C O W E R I X E e D O U T D O O R I N T A K E A I R A N D C E S S *Opening in the bottom of the unit can be located by the slice   F D L I E L D - S U P P L I E D W E R E X A U S T R A I N H O O D S I S C O N N E C T S W I T C H B A L C O W E R M O T O R S e d e t a i l " Y " ) in the insulation.   O C A T I O N C A ( O M P R E S S O R C E S S C C E S S B C A ( L C O W E R S e e d e t a i l " X " ) O M P A R T M E N T C E S S L CLEARANCES   O C P T I O N A A u x i l i a r y ) O I L G U A R D Front   36"   D ( D O r T P L U G F o r p r e s s u r e 5 2 - 5 / 8 24" (Less Economizer)   49" (With Economizer)   o p R e a d i n T g ) Back   G A A S H E A 24" (Less Economizer)   C C E S S Left Side (Filter Access)   36"3(With Economizer)   C C O O N I D E N S E R V O H E N T A I R L S U T O L E T Right Side (Cond. Coil)   Below Unit1   36"   20"   O D S 2 1 " 5 " 7 - 1 / 8 " C A H O O M O B U S T I O N 1 3 6 - 1 / 4 I R I N L E T 72" With 36" Maximum   Horizontal Overhang   (For Condenser Air   Discharge)   D 6 - 3 / 8 " Above Unit2   9 - 3 / 4 " 9 2 " ( G E C ) 5 - 7 / 8 " ( C E A ) A S S U P P L Y O N T R O L W I R I N G N T R Y 1 N T R Y 4 6 - 5 / 8 " Units (applicable in U.S.A. only) may be installed on combustible floors   made from wood or class A, B or C roof covering material.   C A O N T R O L B O X 1 1 - 1 / 2 " ( P E B ) 3 5 " C C E S S 2 O N W E R W I R N G I Units must be installed oudoors. Overhanging structures or shrubs should   B O T T O M S U P P L Y T R Y not obstruct condenser air discharge outlet.   If economizer is factory installed, the assembled hood kit must be removed   prior to final installation. This hood is 54" long.   A N D R E T U R N 3 A I R O P E N I N G S F V R O N T ( S e e N o t e ) 3 5 - 1 / 4 I E W R E T U R N 3 - 3 / 4 " A I R NOTE:   3 3 " DCE Models: Units and ductwork are approved for zero clearance to combus-   tible materials when equipped with electric heaters.   S U P P L Y A I R 2 - 3 / 2 4 1 " - 1 / 2 " DCG Models: A 1" clearance must be provided between any combustible   material and the supply air ductwork for a distance of 3 feet from the unit.   1 1 - 1 / 8 " The products of combustion must not be allowed to accumulate within a   confined space and recirculate.   G U N I T B A S E W I T H R A I L S ( P E B A ) ) ( G E D ) S B a l h o o t w n s e p a r a t e l y n t n o i l l u s t r a t e O N W E R W I R I N A S S U P P L Y t o m D u c t o p e i g s , P o w n e r T T R R Y Y N T R Y Locate unit so that the vent air outlet hood is at least:   n d G a s P i p i n g C o n n e c t i o ( C E o c a t i o n s • Three (3) feet above any forced air inlet located within 10 horizontal feet   O N T R O L W I R I N G 8 - 1 / 8 " N (excluding those integral to the unit).   N F d s O T E : 4 6 - 5 / 8 " o r c u r b m o u n t e d u n i t s , r e f e r t o p t h e c u r b z h a n g e r • Four (4) feet below, 4 horizontal feet from, or 1 foot above any door or gravity   9 - 1 h / 4 " i m e p n s i o n n s o f t h e c u r b f o r t e r o p e r s i e o f t h e air inlet into the building.   1 2 - 1 / 2 " 9 - 3 / 4 " u p l y a d r e t u r n a i r d u c t c o n n e c t i o n s . • Four (4) feet from electric meters, gas meters, regulators and relief equip-   ment.   Cont’d.   FIG. 10 - DIMENSIONS & CLEARANCES - DCE & DCG   Unitary Products Group   11   530.18-N11Y   CONDENSER   SECTION   EVAPORATOR   SECTION   GAUGE LINE   ACCESS   DUCT COVERS - Units are shipped with the bottom   duct openings covered. An accessory flange kit is avail-   able for connecting side ducts.   DOT PLUG   (For pressure   drop reading)   For bottom duct applications:   40-3/8"   1. Remove the side panels from the supply and return   air compartments to gain access to the bottom   supply and return air duct covers.   FILTER   ACCESS   2. Remove and discard the bottom duct covers. (Duct   openings are closed with sheet metal covers except   when the unit includes a power exhaust option. The   covering consists of a heavy black paper composition.)   3. Replace the side supply and return air compartment   panels.   SUPPLY   AIR   RETURN   AIR   5-1/2"   COMPRESSOR   ACCESS   OUTDOOR   AIR   For side duct applications;   40-1/2"   SUPPLY AIR   ACCESS   1. Replace the side panels on the supply and return air   compartments with the accessory flange kit panels.   2. Connect ductwork to the duct flanges on the rear of   the unit.   18-5/8"   1" NPT FEMALE   COND. DRAIN   CONNECTION   27-3/4"   5-1/8"   RETURN AIR   ACCESS   OUTDOOR AIR   COMPARTMENT   ACCESS   39-5/8   REAR   VIEW   DETAIL “X”   ACCESSORY SIDE SUPPLY AND RETURN AIR OPENINGS   ECONOMIZER   MOTORIZED   DAMPER   RAIN HOOD   (on Outdoor Air Compartment)   POWER EXHAUST   RAIN HOOD   (on Return Air Compartment)   SUPPLY AIR   COMPARTMENT   ECONOMIZER MOTORIZED DAMPER   / AND POWER EXHAUST RAIN HOODS   FIXED   OUTDOOR AIR   INTAKE HOOD   (located on   Return Air   34-1/4"   Compartment)   1" CONDENSTATE   DRAIN   16-1/8"   (Must be trapped)   5"   36"   92"   36-1/4"   2"   66-1/2"   LH VIEW   REAR VIEW   DETAIL "Y"   UNIT WITH RAIN HOODS   DETAIL “Y”   UNIT WITH RAIN HOODS   FIG. 10 - DIMENSIONS & CLEARANCES (Cont’d.)- DCE & DCG   12   Unitary Products Group   530.18-N11Y   B E F C D A A C FRONT   FRONT   4 POINT LOADS   6 POINT LOADS   D B FIG. 11- FOUR AND SIX POINT LOADS   TABLE 7 - FOUR AND SIX POINT LOADS   4 - POINT LOADS (LBS)   UNIT   TOTAL   3,130   A 615   B 671   C D 300   962   882   NOTE: These weights are with economizer, high heat, and the largest blower motor available.   6 - POINT LOADS (LBS)   UNIT   TOTAL   3,130   A B C D 628   E 603   F 510   300   418   438   533   NOTE: These weights are with economizer, high heat, and the largest blower motor available.   DCE300 - BOTTOMDUCTCONNECTIONS(COOLING APPLICATIONS)   TABLE 8 - SUPPLY AIR BLOWER PERFORMANCE   7500 CFM   OUTPUT   (bhp)   8750 CFM   OUTPUT   (bhp)   10000 CFM   OUTPUT   (bhp)   11250 CFM   OUTPUT   (bhp)   12500 CFM   OUTPUT   (bhp)   BLOWER PULLEY   SPEED   (rpm)   TURNS   OPEN:   ESP   (iwg)   INPUT   (kW)   ESP   (iwg)   INPUT   (kW)   ESP   (iwg)   INPUT   (kW)   ESP   (iwg)   INPUT   (kW)   ESP   (iwg)   INPUT   (kW)   STANDARD DRIVE:   975   6.0*   5.0   4.0   3.0   2.0   1.0   0.0   1.4   1.6   1.8   2.0   2.1   2.4   2.6   5.9   6.2   6.6   6.9   7.3   7.7   8.0   4.9   5.1   5.4   5.7   6.0   6.3   6.6   1.0   1.2   1.4   1.6   1.8   2.0   2.2   7.3   7.7   8.1   8.5   8.9   9.3   9.7   6.0   0.5   0.7   0.9   1.1   1.3   1.6   1.8   8.8   9.2   9.7   10.2   10.6   11.1   11.6   7.2   7.6   8.0   8.3   8.7   9.1   9.5   - - - - - - - - - - - - 1005   1040   1070   1100   1135   1165   6.3   6.7   7.0   7.3   7.6   8.0   0.1   0.3   0.6   0.8   1.0   1.3   10.9   11.4   11.9   12.4   13.0   13.5   8.9   9.4   9.8   10.2   10.6   11.0   - - - 0.2   0.4   0.7   14.3   14.9   15.5   11.7   12.2   12.7   ACCESSORY DRIVE:   1140   1180   1215   1255   1290   1330   1365   NOTES:   6.0   5.0   4.0   3.0   2.0   1.0   0.0   2.4   2.7   2.9   3.2   3.4   3.7   3.9   7.7   8.2   8.6   9.1   9.5   10.0   10.5   6.3   6.7   7.0   7.4   7.8   8.2   8.6   2.1   2.3   2.6   2.9   3.1   3.4   3.7   9.4   9.9   7.7   8.1   8.5   9.0   9.4   9.9   10.3   1.6   1.9   2.2   2.5   2.7   3.0   3.3   11.2   11.8   12.3   12.9   13.5   14.1   14.7   9.2   9.7   1.1   1.4   1.7   2.0   2.2   2.6   2.9   13.1   13.7   14.3   15.0   15.6   16.4   17.0   10.7   11.2   11.7   12.3   12.8   13.4   13.9   0.5   0.8   1.1   1.4   - - - 15.0   15.8   16.4   17.2   - - - 12.3   12.9   13.5   14.1   - - - 10.4   11.0   11.5   12.0   12.6   10.1   10.6   11.1   11.6   12.1   Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry evaporator coil.   Refer to page 14 for additional static resistances.   ESP - External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the   blower.   * FACTORY SETTING   Unitary Products Group   13   530.18-N11Y   TABLE 9 - SUPPLY AIR BLOWER PERFORMANCE DCG300-BOTTOM DUCT CONNECTIONS(COOLING APPLICATIONS)   7500 CFM   OUTPUT   (bhp)   8750 CFM   OUTPUT   (bhp)   10000 CFM   OUTPUT   (bhp)   11250 CFM   OUTPUT   (bhp)   12500 CFM   OUTPUT   (bhp)   BLOWER PULLEY   SPEED   (rpm)   TURNS   OPEN:   ESP   (iwg)   INPUT   (kW)   ESP   (iwg)   INPUT   (kW)   ESP   (iwg)   INPUT   (kW)   ESP   (iwg)   INPUT   (kW)   ESP   (iwg)   INPUT   (kW)   STANDARD DRIVE:   975   6.0   5.0   4.0   3.0   2.0   1.0   0.0   1.2   1.4   1.6   1.8   2.0   2.2   2.4   5.9   6.2   6.6   6.9   7.3   7.7   8.0   4.9   5.1   5.4   5.7   6.0   6.3   6.6   0.5   0.7   0.9   1.1   1.3   1.6   1.8   7.3   7.7   8.1   8.5   8.9   9.3   9.7   6.0   - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1005   1040   1070   1100   1135   1165   6.3   6.7   7.0   7.3   7.6   8.0   0.2   0.4   0.6   0.8   1.0   9.7   8.0   8.3   8.7   9.1   9.5   10.2   10.6   11.1   11.6   - 0.2   13.5   11.0   ACCESSORY DRIVE:   1140   1180   1215   1255   1290   1330   1365   NOTES:   6.0   5.0   4.0   3.0   2.0   1.0   0.0   2.2   2.5   2.7   3.0   3.2   3.5   3.7   7.7   8.2   8.6   9.1   9.5   10.0   10.5   6.3   6.7   7.0   7.4   7.8   8.2   8.6   1.6   1.9   2.1   2.4   2.7   3.0   3.2   9.4   9.9   7.7   8.1   8.5   9.0   9.4   9.9   10.3   0.9   1.2   1.4   1.7   2.0   2.3   2.6   11.2   11.8   12.3   12.9   13.5   14.1   14.7   9.2   9.7   - - - - - - - - - - - - - - - - - - - - - - - - 0.3   0.6   0.9   1.2   1.5   1.8   13.7   14.3   15.0   15.6   16.4   17.0   11.2   11.7   12.3   12.8   13.4   13.9   10.4   11.0   11.5   12.0   12.6   10.1   10.6   11.1   11.6   12.1   Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry evaporator coil.   Refer to page 14 for additional static resistances.   ESP - External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the   blower.   * FACTORY SETTING   TABLE 10 - STATIC RESISTANCES*   AIRFLOW (CFM)   7500   ESP   8750   ESP   10000   ESP   11250   ESP   12500   ESP   DESCRIPTION   (IWG)   (IWG)   (IWG)   (IWG)   (IWG)   DEDUCTIONS: (SUBTRACT VALUES BELOW FROM UNIT'S AVAILABLE ESP)   ALLOWANCE FOR WET COIL:   ECONOMIZER (RETURN DUCT):   18kW ELECTRIC HEAT:   0.10   0.06   0.31   0.38   0.62   0.68   0.10   0.09   0.43   0.52   0.84   0.93   0.10   0.11   0.56   0.68   1.10   1.21   0.10   0.14   0.71   0.87   1.39   1.54   0.10   0.18   0.87   1.07   1.72   1.90   36kW ELECTRIC HEAT:   54kW ELECTRIC HEAT:   72kW ELECTRIC HEAT:   ADDITIONS: (ADD VALUES BELOW TO UNIT'S AVAILABLE ESP)   HORIZONTAL (SIDE) SUPPLY DUCT:   HORIZONTAL (SIDE) RETURN DUCT:   0.31   0.05   0.26   0.05   0.27   0.05   0.31   0.05   0.41   0.05   TABLE 11 - POWER EXHAUST PERFORMANCE   STATIC RESISTANCE OF RETURN DUCTWORK, IWG   0.3 0.4 0.5   MOTOR   SPEED   0.2   0.6   CFM   5250   KW   CFM   KW   CFM   KW   CFM   KW   CFM   3000   KW   HIGH*   0.83   4500   0.85   4200   0.88   3750   0.93   0.99   MEDIUM   4900   4400   0.77   0.72   3900   3700   0.79   0.74   3500   3000   0.82   0.78   2900   - 0.85   - - - - - LOW   *Factory Setting   Power Exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection.   TABLE 12 - BLOWER MOTOR AND DRIVE DATA   BELT   (NOTCHED)   MOTOR1   ADJUSTABLE MOTOR PULLEY   FIXED BLOWER PULLEY   OUTSIDE PITCH   BLOWER   DRIVE RANGE   (RPM)   MODEL   SIZE   OUT-   PITCH   PITCH   LENGTH   (IN.)   EFF.   (%)   DESIG-   NATION   SIDE   DIA.   (IN.)   BORE DESIG-   (IN.) NATION   BORE DESIG-   QTY.   HP FRAME   DIA.   (IN.)   DIA.   (IN.)   DIA.   (IN.)   (IN.) NATION   Stan-   975/1165   dard   1B5V110 11.3   11.1 1-7/16 5VX860 86.0   9.5 1-7/16 5VX840 84.0   1 1 6.2-   7.4   25 TON   15 254T   91 1LVP58B70A 7.5   1-5/8   High   Speed 1140/1365   Access   1B5V94   9.7   1 All motors have a nominal speed of 1800 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because they are located in the moving air, upstream   of any heating device.   14   Unitary Products Group   530.18-N11Y   OPERATION   addition. The power exhaust motor is energized whenever the   economizer is chosen by the enthalpy sensor for first stage   cooling, “Y1". As always, the ”R" to “G” connection provides   minimum position but does not provide power exhaust   operation.   MOTORIZED OUTDOOR AIR DAMPERS - This system   operation is the same as the units with no outdoor air options   with one exception. When the “R” to “G” circuit is complete, the   motorized damper drives open to a position set by the damper   motor adjustment. When the “R” to “G” circuit is opened, the   damper spring returns fully closed.   COOLING SYSTEM   The cooling section is a complete factory package utilizing an   air-cooled condenser. The system is factory-charged with   Refrigerant-22.   The compressors are hermetically sealed, internally sprung   and base-mounted with rubber-insulated hold-down bolts.   Compressors have inherent (internal) protection. If there is an   abnormal temperature rise in a compressor, the protector will   open to shut down the compressor.   PRELIMINARY OPERATION COOLING   CONTINUOUS BLOWER - Continuous blower operation is   possible by closing the R to G circuit on the thermostat.   After the initial installation, the compressors should be given   three false starts (energized just long enough to make a few   revolutions) with 5-7 minutes delay between each start, before   being put into full time service.   SAFETY CONTROLS   Each refrigerant system is equipped with the following safety   controls:   COOLING SEQUENCE OF OPERATION   NO OUTDOOR AIR OPTIONS - When the room thermostat   calls for “first-stage”cooling, the low voltage control circuit from   “R” to “G” and “Y1" is completed to energize compressors #1/2   (50% capacity), condenser fan motor #1, and the supply air   blower motor (if the fan switch on the room thermostat is set in   the ”AUTO" position).   When the thermostat calls for “second-stage” cooling, the low   voltage control circuit from “R” to “Y2" is completed to energize   compressor #3/4.   After the thermostat is satisfied and opens, all components will   stop simultaneously. The blower motor will continue to operate   if the fan switch on the room thermostat is set in the “ON”   position.   1. A Suction Line Freezestat to protect against low evaporator   temperatures due to a low air flow or a low return air   temperature. (Opens at 26°F + 5°F and resets at 38°F +   5°F)   2. A High Pressure Cutout Switch to protect against excessive   discharge pressures due to a blocked condenser coil or a   condenser motor failure.(Opens at380 psig +10and resets   at 300 psig +10)   3. A Low Pressure Switch/Loss Of Charge to protect against   loss of refrigerant charge. (Opens at 7 psig + 3 and resets   at 22 psig + 5)   ECONOMIZER WITH SINGLE ENTHALPY SENSOR - When   the room thermostat calls for “first-stage” cooling, the low   voltage control circuit from “R” to “G” and “Y1" is completed.   The ”R" to “G” circuit energizes the blower motor (if the fan   switch on the room thermostat is set in the “AUTO” position)   and drives the economizer dampers from fully closed to their   minimum position.If the enthalpy of the outdoor air is below the   setpoint of the enthalpy controller (previously determined), “Y1"   energizes the economizer. The dampers will modulate to   maintain a constant supply air temperature as monitored by the   discharge air sensor. If the outdoor air enthalpy is above the   setpoint, ”Y1" energizes compressors #1/2, and condenser fan   motor #1.   When the thermostat calls for “second-stage” cooling, the low   voltage control circuit from “R” to “Y2" is completed. If the   enthalpy of the outdoor air is below the setpoint of the enthalpy   controller (i.e. first stage has energized the economizer), ”Y2"   will energize compressors #1/2. If the outdoor air is above the   setpoint, “Y2" will energize compressor #3/4.   If either one of the above safety controls opens, that individual   refrigerant system will be locked out. The other refrigerant   system will continue in operation unless it too is effected by the   same fault. The lock out of either system can be reset by   opening the 24V circuit either at the room thermostat or at the   unit disconnect.   ELECTRIC HEATING - SEQUENCE OF OPERATION   WITH POWER TO UNIT AND THERMOSTAT IN THE   HEATING MODE   Single-stage heating: (applies only to 18 KW heater, all other   heaters MUST use a two-stage thermostat:)   a) If the fan switch is in the “ON” position, the evaporator   blower motor contactor (3M) will be energized through   terminal G to provide continuous blower operation.If the fan   switch is in the “AUTO”position, the blower will operate only   when there is a call for heating by the thermostat.   NOTE: All 240 & 480V heaters are provided with manual   reset backup protection limits. These will de-ener-   gize the heaters should the primary limit fail to open   or the contactors fail to open in a failure mode.   After the thermostat is satisfied and opens, all components will   stop simultaneously. The blower motor will continue to operate   if the fan switch on the room thermostat is set in the “ON”   position.   b) Upon a call for heat by the thermostat, the heater contactor   (6M) will be energized.   c) The thermostat will cycle the electric heat to satisfy the   heating requirements of the conditioned space.   ECONOMIZER WITH DUAL ENTHALPY SENSORS - The   operation with the dual enthalpy sensors is identical to the   single sensor except that a second enthalpy sensor is mounted   in the return air. This return air sensor allows the economizer   to choose between outdoor air and return air, whichever has   the lowest enthalpy value, to provide maximum operating   efficiency.   Two-stage heating: (applies to all heaters except 18 KW):   a) If the fan switch is in the “ON” position, the evaporator   blower motor contactor (3M) will be energized through   terminal G to provide continuous blower operation.If the fan   ECONOMIZER (SINGLE OR DUAL) WITH POWER   EXHAUST - This system operates as specified above with one   Unitary Products Group   15   530.18-N11Y   switch is in the “AUTO”position, the blower will operate only   At the same time power was supplied to the “RW1”, a parallel   circuit activates “ETD” which closes the “ETD” contact after   approximately 35 seconds and energizes “K5" which closes   ”K5-2" and starts the blower by energizing “3M”.   When “TH2" closes, heat relay ”RW2" is energized. The   “RW2-1" contact is closed energizing the second stage ignition   module ”IC2". “IC2" will immediately start the second stage   ignitor sparking and will open the redundant valve located   inside the second stage main gas valve ”GV2" to allow a flow   of gas to the second stage carryover tube. Only after the pilot   flame has been ignited and the presence of pilot flame detected   at “IC2" by a signal sent back through the flame sensor is   sparking terminated and the main gas valve opened.   Gas flows into each of the second stage main burners and is   ignited from the carryover tube flame.   If “IC2" fails to detect a pilot flame, it will continue to try for a   maximum of 85 seconds to ignite the pilot tube.If the pilot flame   is not detected, then ”IC2" will lock out furnace operation for 5   minutes, then retry ignition sequence. Note that the second   stage furnace can operate even if first stage has locked out.   when there is a call for heating by the thermostat.   b) Upon a call for first-stage heat by the thermostat, the heater   contactor (6M) (6M & 7M on 72 KW, 240V) will be   energized.   If the second stage of heat is required, heater contactor   (7M) will be energized. Note that on the 54 KW, 240V   heater, heater contactors (7M & 8M) will be energized and   on the 72 KW, 240V heater, heater contactors (8M & 9M)   TABLE 9 - HEAT ANTICIPATOR SETTING   SETTING, AMPS   HEATER   KW   VOLTAGE   TH1   TH2   - 18   36   54   72   18   36   54   72   18   36   54   72   0.29   0.29   0.29   0.58   0.29   0.29   0.29   0.29   0.29   0.29   0.29   0.29   0.29   0.58   0.58   - 208/230-3-60   0.29   0.29   0.29   - 460-3-60   575-3-60   When the heating cycle is complete, “TH2" opens de-energizing   the ”RW2" then “TH1" opens de-energizing ”RW1" and “ETD”,   REDUNDANT   VALVE   MAIN VALVE   0.29   0.29   0.29   GAS MAIN   will be energized.   c) The thermostat will cycle the electric heat to satisfy the   heating requirements of the conditioned space.   GAS   VALVE   TO MAIN   BURNER   TO PILOT BURNER   FIG. 12 - GAS VALVE PIPING   HEAT ANTICIPATOR SETPOINTS   It is important that the anticipator setpoint be correct. Too high of   a setting will result in longer heat cycles and a greater temperature   swing in the conditioned space. Reducing the value below the   correct setpoint will give shorter “ON” cycles and may result in the   lowering of the temperture within the conditioned space. Refer to   the Heat Anticipator Setpoints table for the required .   thus closing all gas valves. The blower motor will continue to   run (approximately 45 seconds after the furnace is shut down)   until “ETD” opens, de-energizing the “K5" relay and ”3M"   contactor. The draft motor will continue to run for a brief   post-purge cycle.   SAFETY CONTROLS   The control circuit includes the following safety controls:   GAS HEATING SEQUENCE OF OPERATION   The following sequence describes the operation of the gas heat   section.   1. LimitControl(LS).Thiscontrolislocatedinsidetheheatexchanger   compartment and is set to open at the temperature indicated in   the Limit Control Setting Table. It resets automatically. The limit   switch operates when a high temperature condition, caused by   inadequate supply air flow occurs, thus shutting down the ignition   controland closingthe maingas valvesandenergizingtheblower.   2. Centrifugal Switch (CS). If the draft motor should fail, the   centrifugal switch attached to the shaft of the motor prevents   the ignition controls and gas valves from being energized.   3. Redundant Gas Valve. There are two separate gas valves   in the furnace.Each valve contains a main and a redundant   valve. The redundant valves are located upstream of the   main gas valves. Should either or both of the main gas   valves fail in the open position the redundant valves serve   as back-ups and shuts off the flow of gas.   4. Flame Sensor Rod / 100% Ignition Control Lock-Out. If an   ignition control fails to detect a signal from the flame sensor   indicating the pilot flame is properly ignited, then the main   gas valve will not open. It will continue to try and ignite the   pilot for a maximum of 85 seconds, then if the pilot flame is   not detected, the ignition control will lock out furnace   operation until 24V power is removed from the module   either at the unit or by resetting the room thermostat.   CONTINUOUS BLOWER   With the room thermostat switch set to “ON”, the supply air   blower will operate continuously. The normally closed contact   “K5-1" provides 24 volt power to the “3M”contactor.The “3M-1,   2 & 3" power contacts close and the blower motor operates.   INTERMITTENT BLOWER   With the room thermostat system switch set to the “AUTO”or “HEAT”   position and the fan switch set to “AUTO”, the supply air blower will   operate after the room thermostat calls for heat and the time delay   relay closes.   The “TH1" closes, the heat relay ”RW1" is energized. The “RW1-1”   power contact closes energizing the line voltage draft motor. The   “RW1-2" contact is also closed. As the speed of the draft motor   reaches approximately 2500 RPM, the centrifugal switch contact   located on the end of the draft motor shaft closes to power the first   stage ignition module “IC1”.   After a brief pre-purge time, ignition module “IC1" will start the first   stage ignitor sparking and will open the redundant valve located   inside the first stage main gas valve “GV1”to allow a flow of gas to   only the first stage carryover tube. Only after the pilot flame has   been ignited and the presence of pilot flame detected at the “IC1”   by a signal sent back through the flame sensor is sparking   terminated and the first stage main gas valve opened.   5. Rollout Switch. This switch is located above the main burn-   ers in the control compartment which in the event of a   sustained main burner rollout shuts off and locks out both   ignition controls closing both gas valves. The ignition con-   trols lock out furnace operation until 24V power is removed   from the controls either at the unit or by resetting the room   thermostat. Note the auto reset rollout switch must reset   before allowing furnace operation.   Gas flows into each of the main burners and is ignited from   the carryover tube flame.   If “IC1”fails to detect a pilot flame, it will continue to try for a maximum   of 85 seconds to ignite the pilot tube. If the pilot flame is not detected,   then “IC1" will lock out furnace operation for 5 minutes, then retry   ignition sequence.   16   Unitary Products Group   530.18-N11Y   TABLE 10 - LIMIT CONTROL SETTING   Capacity, MBH   Limit Control   Opens, °F   195   I G N . C O N T R O L # 2 Input   300   Output   240   400   320   195   I G N . C O N T R O L # 1 HEAT ANTICIPATOR SETPOINTS   It is important that the anticipator setpoint be correct. Too high of   a setting will result in longer heat cycles and a greater   temperature swing in the conditioned space. Reducing the value   below the correct setpoint will give shorter “ON” cycles and may   result in the lowering of the temperture within the conditioned   space.   R O L L O U T S W . G V 1 S E N S O R # 1 G A S V A L V E G V 2 I G N I T O R # 1 Anticipator Setpoint   Gas Valve   G A S V A L V E 1st Stage   0.30 amp   2nd Stage   0.11 amp   Honeywell VR8440   White-Rodgers 36C68   S E N S O R # 2 I G N I T O R # 2 PRE-START CHECK LIST   Complete the following checks before starting the unit.   1. Check the type of gas being supplied. Be sure that it is the   same as listed on the unit nameplate.   2. Make sure that the vent and combustion air hoods have been   properly installed.   B U R N E R C O M P A R T M E N T FIG 13-GAS VALVE AND CONTROLS   START-UP   6. Auxiliary Limit Switch (AUX) This control is located inside   the heat exchanger compartment and is set to open at   190°F. It is a manual reset switch. If AUX limit trips, then the   primary limit has not functioned correctly., Replace the   primary limit   2. Check for correct manifold gas pressures. See “Checking   Gas Input”.   3. Check the supply gas pressure. It must be within the limits   shown on rating nameplate. Supply pressure should be   checked with all gas appliances in the building at full fire.At   no time should the standby gas line pressure exceed 13",   nor the operating pressure drop below 5.0" for natural gas   units. If gas pressure is outside these limits, contact the   OPERATING INSTRUCTIONS   CAUTION: This furnace is equipped with an intermittent pilot   and automatic re-ignition system.DO NOT attempt   to manually light the pilot.   ON-OFF CONTROL   TO LIGHT PILOT AND MAIN BURNERS:   HIGH FIRE ADJ.   (UNDER SCREW)   1. Turn “off” electric power to unit.   2. Turn room thermostat to lowest setting.   3. Turn gas valve knob to “on” position.   4. Turn “on” electric power to unit.   PILOT ADJ.   (UNDER SCREW)   5. Set room thermostat to desired temperature.   (If thermostat “set”temperature is above room temperature,   pilot burner ignition will occur and, after an interval to prove   pilot flame, main burners will ignite).   FIG. 14 - TYPICAL GAS VALVE   TO SHUT DOWN:   local gas utility for corrective action.   1. Turn “off” electric power to unit.   MANIFOLD GAS PRESSURE ADJUSTMENT   Small adjustments to the high-fire gas flow may be made by   turning the pressure regulator adjusting screw onthe automatic   gas valve. Refer to figure below.   2. Depress knob of gas valve while turning to “off” position.   POST-START CHECK LIST (GAS)   After the entire control circuit has been energized and the   heating section is operating, make the following checks:   Adjust as follows:   1. Remove the cap on the regulator. It’s located next to the   1. Check for gas leaks in the unit piping as well as the supply   piping.   push-on electrical terminals.   2. To decrease the gas pressure, turn the adjusting screw   counterclockwise.   Unitary Products Group   17   530.18-N11Y   Reverse the above procedure to replace the assemblies.Make   sure that burners are level and seat at the rear of the heat   exchanger.   BURNER ASSEMBLY BRACKET   FLAME SENSOR BULB   BURNER AIR SHUTTER ADJUSTMENT   Adjust burner shutters so no yellow flame is observed in the   heat exchanger tubes.   CHECKING SUPPLY AIR CFM   TheRPMofthesupplyairblowerwilldependontherequiredCFM,   the unit accessories or options and the static resistances of both   the supply and the return air duct systems. With this information,   the RPM for the supply air blower and the motor pulley adjustment   (turns open) can be determined from the Blower Performance   Data Table.   1/8" GAP BETWEEN CARRY-OVER   TUBE AND FLAME SENSOR BULB   CARRY-OVER TUBE   FIG. 15 - PROPER FLAME ADJUSTMENT   A high speed drive accessory 1LD0435 (containing a smaller   blower pulley and shorter belts) is available for applications   requiring the supply air blower to produce higher CFM’s and/or   higher static pressures. Refer to the Blower Motor and Drive   Data Table.   3. To increase the gas pressure, turn the adjusting screw   clockwise.   NOTE: The correct manifold pressure for these furnaces is   3.65 IWG ±0.3.   PILOT CHECKOUT   Note the following:   The pilot flame should envelope the end of the flame sensor.Refer   to Proper Flame Adjustment figure. To adjust pilot flame, (1)   remove pilot adjustment cover screw, (2) increase or decrease the   clearance for air to the desired level, (3) be sure to replace cover   screw after adjustment to prevent possible gas leakage.   Put the system into operation and observe through complete   cycle to be sure all controls function properly.   BURNER INSTRUCTIONS   To check or change burners, pilot or orifices, CLOSE MAIN   MANUAL SHUT-OFF VALVE AND SHUT OFF ALL ELECTRIC   POWER TO THE UNIT.   1. Remove the screws holding either end of the manifold to   the burner supports.   2. Open the union fitting in the gas supply line just upstream   of the unit gas valve and downstream from the main manual   shut-off valve.   3. Remove the gas piping closure panel.   4. Disconnect wiring to the gas valves and spark ignitors.   Remove the manifold-burner gas valve assembly by lifting   up and pulling back.   FIG.17 - BELT ADJUSTMENT   Burners are now accessible for service.   1. The supply air CFM must be within the limitations shown in   Unit Application DataTable.   2. Pulleys can be adjusted in half turn increments.   3. The tension on the belts should be adjusted as shown in   the belt adjustment figure below.   Start the supply air blower motor.Adjust the resistances in both   the supply and the return air duct systems to balance the air   distribution throughout the conditioned space. The job   specifications may require that this balancing be done by   someone other than the equipment installer.   To check the supply air CFM after the initial balancing has been   completed:   1. Remove the two 5/16" dot plugs from the blower motor and   the filter access panels.   FIG. 16 - TYPICAL FLAME APPEARANCE   18   Unitary Products Group   530.18-N11Y   2. Insert at least 8" of 1/4 inch tubing into each of these holes   for sufficient penetration into the air flow on both sides of   the indoor coil.   NOTE:   DE-ENERGIZE THE COMPRESSORS BEFORE TAKING ANY TEST   MEASUREMENTS TO ASSURE A DRY INDOOR COIL.   ADJUSTMENT OF TEMPERATURE RISE   NOTE: The tubes must be inserted and held in a position   perpendicular to the air flow so that velocity pres-   sure will not affect the static pressure readings.   The temperature rise (or temperature difference between the   return air and the heated air from the furnace) must lie within the   range shown on the ETL rating plate.   After the temperature rise has been determined, the cfm can   be calculated as follows:   3. Using an inclined manometer, determine the pressure drop   across a dry evaporator coil. Since the moisture on an   evaporator coil may vary greatly, measuring the pressure   drop across a wet coil under field conditions would be   inaccurate. To assure a dry coil, the compressors should   be deactivated while the test is being run.   After about 20 minutes of operation, determine the furnace   temperature rise. Take readings of both the return air and the   heated air in the ducts (about six feet from the furnace) where they   will not be affected by radiant heat. Increase the blower cfm to   decrease the temperature rise; decrease the blower cfm to   increase the rise. Refer to the Blower Motor And Drive Data table.   4K.nowingthepressuredropacrossadrycoil,theactualCFM   through the unit and clean 2" filters, can be determined from   the curve in the Pressure Drop Verses Supply Air CFM   figure.   BELT DRIVE BLOWER   WARNING:Failure to properly adjust the total system air quan-   All units have belt drive single-speed blower motors. The   variable pitch pulley on the blower motor can be adjusted to   obtain the desired supply air CFM. Tighten belts enough to   prevent slipping. but do not over tighten. Belt deflection should   be between 1/4" and 1/2" per foot.Refer to the table for Blower   Motor And Drive Data.   CHECKING GAS INPUT   NATURAL GAS   1. Turn off all other gas appliances connected to the gas meter.   2. With the furnace turned on, measure the time needed for   one revolution of the hand on the smallest dial on the meter.   A typical gas meter usually has a 1/2 or a 1 cubic foot test   dial.   3. Using the number of seconds for each revolution and the   size of the test dial increment, find the cubic feet of gas   consumed per hour from the Gas RateTable.   TABLE 11 - GAS RATE - CUBIC FEET PER HOUR   Seconds   for One   Rev.   Size of Test Dial   1/2 cu. ft.   1 cu. ft.   4 6 8 450   300   228   180   900   600   450   360   10   12   14   16   18   20   150   129   113   100   90   300   257   225   200   180   FIG. 18 - PRESSURE DROP ACROSS A DRY INDOOR   COIL VS SUPPLY AIR CFM   tity can result in extensive blower damage.   22   24   26   28   82   75   69   64   164   150   138   129   After readings have been obtained, remove the tubes and   reinstall the two 5/16" dot plugs that were removed in Step 1.   Example: By actual measurement, it takes 13 seconds for the hand on the 1-cubic   foot dial to make a revolution with just a 300,000 Btuh furnace running. Read   across to the column in the table above, headed “1 Cubic Foot”, where you will see   that 278 cubic feet of gas per hour are consumed by the furnace at that rate.   Multiply 278 x 1050 (the Btu rating of the gas obtained from the local gas company).   The result is 292,425 Btuh, which is close to the 300,000 Btuh rating of the furnace.   Btuh Input x 0.8   1.08 x oF Temp. Rise   CFM =   SECURE OWNER’S APPROVAL: When the system is functioning properly, secure the owner’s approval. Show him the   location of all disconnect switches and the thermostat. Teach him how to start and stop the unit and how to adjust temperature   settings within the limitations of the system.   Unitary Products Group   19   530.18-N11Y   MAINTENANCE   If the actual input is not within 5% of the furnace rating (with   allowance being made for the permissible range of the regulator   setting), replace the orifice spuds with spuds of the proper size.   GAS HEATING UNITS   BURNER & PILOT - Periodically (at least annually at the   beginning of each heating season) make a visual check of the   pilot and main burner flame. If necessary, adjust main burner   primary air shutters to give a distinct, sharp blue flame as   explained under “BURNER AIR SHUTTER ADJUSTMENT”. If   it is not possible to adjust for the proper flame, the burners may   need cleaning.   NOTE To find the Btu input, multiply the number of cubic feet of   gas consumed per hour by the Btu content of the gas in   your particular locality (contact your gas company for this   information - it varies widely from city to city.)   NORMAL MAINTENANCE   TO CLEAN BURNERS - Remove them from the furnace as   explained in “Burner Instructions”.Clean burners with hot water   applied along top of the burner.   COMBUSTION AIR DISCHARGE - Visually inspect discharge   outlet periodically to make sure that the buildup of soot and dirt   is not excessive. If necessary, clean to maintain adequate   combustion air discharge.   CAUTION: Prior to any of the following maintenance proce-   dures, shut off all electric power to the unit to   prevent personal injury.   Periodic maintenance normally consists of changing or   cleaning filters and (under some conditions) cleaning the main   burners.   FILTERS - Inspect once a month. Replace disposable or clean   permanent type as necessary. DO NOT replace permanent   type with disposable. The dimensional size of the replacement   filter must be the same as the replaced filter.   CLEANING FLUE PASSAGES AND HEATING ELEMENTS   With proper combustion adjustment the heating element of a   gas fired furnace will seldom need cleaning. If the element   should become sooted, it can be cleaned as follows:   MOTORS   1. Remove the burner assembly as outlined in “BURNER   Outdoor fan motors are permanently lubricated and require no   maintenance.   INSTRUCTIONS”.   2. Remove the roof over the gas heat section.   3. At the top plate from the top draft blower housing and the   top draft blower wheel.   4. Remove the screws holding the top of the flue collector box.   Carefully remove the top of the flue collector box without   ripping the adjacent insulation. Then remove the center   divider plate separating the upper and lower flue boxes.   Ventor motor is factory lubricated for an estimated 10 year   life.   Indoor Blower Motor and Drive - The indoor blower motor   features ball bearings that do not require periodic lubrication.   Periodic lubrication of the motor and bearings can extend the   life of components but is optional.   CAUTION: Damage can occur if the bearings are overlubri-   cated. Use grease sparingly.   5. On the inside of the flue collector box, remove the flue   baffles from the tube interiors. Note the last bend of the   baffle fits tightly against the tube forcing the end of the baffle   to lock into the tube collar. This collar is formed when the   tube is expanded into the end sheet. To remove, move the   end of the baffle toward the center of the tube releasing the   end of the baffle from the tube collar, then pull straight out   of the tube.   6. Using a wire brush on a flexible wand, brush out the inside   of each heat exchanger from the burner inlet and flue outlet   ends.   7. Brush out the inside of the flue collector box and the flue   baffles.   WARNING:Perform all maintenance operations on the blower   motor with electric power disconnected from the   unit. Do not attempt to lubricate bearings with the   unit in operation.   On an annual basis, check the motor for accumulations of dust,   etc. that may block the cooling slots in the motor shell. Check for   loose, damaged or misaligned drive components. Check that all   mounting bolts are tight. Replace defective parts as required.   If desired, every three years remove both pipe plugs at each end   shell and clean out any hardened grease or foreign matter.   Replace one plug on each end with a clean grease fitting. Using   a low pressure grease gun, pump grease (Chevron SRI-2 or   equivalent) into the bearing cavity until new grease shows at the   open port. Do not over lubricate. Run the motor for ten minutes   until excess grease is purged from the cavity. Replace the plugs.   8. Run the wire brush down the vent hoods from the flue   collector end.   9. If soot build-up is particularly bad, remove the vent motor   and cleanthewheelandhousings.Runthewirebrushdown   the flue extentions at the outlet of the vent housings.   Units are supplied withblower shaft bearingsthatdonot require   maintenance but may be relubricated if desired. Every three   years, using a low pressure grease gun, pump grease into the   bearing grease fitting until grease just begins to show at the   seals. Do not over lubricate. Use any lithium base grease   recommended for ball bearing service.   OUTDOOR COIL - Dirt should not be allowed to accumulate   on the outdoor coil surface or other parts in the air circuit.   Cleaning should be as often as necessary to keep coil clean.   Use a brush, vacuum cleaner attachment, or other suitable   means. If water is used to clean coil, be sure electric power to   the unit is shut off prior to cleaning.   NOTE: Exercise care when cleaning the coil so that the coil   fins are not damaged.   Do not permit the hot condenser air discharge to be   obstructed by overhanging structures of shrubs.   FIG. 19 - TYPICAL FLUE BAFFLE INSTALLATION   20   Unitary Products Group   530.18-N11Y   TROUBLESHOOTING   10. After brushing is complete, blow all brushed areas with air   or nitrogen. Vacuum as needed.   11. Replace parts in the order they were removed in Steps   1 thru 4.   12. When replacing the center and top of the flue collector box,   be careful not to tear the adjoining insulation.   13. Ensure that all seams on the vent side of the combustion   system are air tight. Apply a high temperature (+500°F)   sealing compound where needed.   2. Draft motor operates and furnace lights but supply air   blower does not start after a short time delay with room   thermostat fan switch set to “AUTO”.   a. Set fan switch to “ON”. If blower motor runs, go to Step f.   If it does not, check to see if line voltage is being   supplied to the contacts of the contactor (M3), and if the   contactor is pulled in. Check for loose wiring.   b. If contactor (M3) is pulled in, proceed with the trou-   bleshooting steps indicated in Step 1 above.   WARNING:Troubleshooting of components necessarily re-   quires opening the electrical control box with the   power connected to the unit. Use extreme care   when working with live circuits! Check the unit   nameplate for the correct line voltage and set the   volt meter to the correct range before making any   connections with line terminals.   c. If (M3) is pulled in and the blower motor still does not   run, replace the blower motor.   d. If (M3) is not pulled in, check for 24 volts at the (M3) coil.   If 24 volts is present, replace the (M3) contactor.   WARNING: Prior to any of the following maintenance proce-   dures, shut off all electric power to the unit to   prevent personal injury.   e. If 24 volts is not present at the (M3) coil, check for loose   24 volt wiring back to the relay board. Check control   wiring to the room thermostat. If all is fine, replace the   relay board.   CAUTION: Label all wires prior to disconnection when servic-   ing controls. Wiring errors can cause improper and   dangerous operation. Verify proper operation after   servicing.   f. If the blower motor runs with the fan switch in the “ON”   position but does not run soon after the furnace has   ignited with the fan switch in the “AUTO” position, check   for loose 24 volt wiring between the relay board in the   main control box, the Mate-N-Lok connector in the   partition between the evaporator and gas heat sections   and the time delay relay (ETD).   NOTE: To find the Btu input, multiply the number of cubic feet of   gas consumed per hour by the Btu content of the gas in   your particular locality (contact your gas company for this   information - it varies widely from city to city.)   g. If all control wiring is fine, check for 24 volts at the relay   board. If 24 volts is present, replace the relay board. If   24 volts is not present, replace the (ETD) relay.   1. The indoor blower motor is a non-inherently protected   three-phase motor. Protection is provided by an overload   relay for overcurrent and fuses for short circuit. If the motor   fails to run, check the line voltage circuit and control voltage   circuit per the following procedure:   NOTE: The furnace may shut itself down on a high tempera-   ture condition during the procedure, but this will not   effect the test if it is done within 5 minutes of furnace   shut-down.   a. If the Indoor Blower Motor does not operate, check   visually that contactor M3 is pulled in. If so, check for   line voltage between all three phases at the line termi-   nals of the Blower Overload Relay (BOR). If line voltage   is found, check the leads to the blower motor for open   circuit. If line voltage is found at the motor leads (inside   the conduit box on the motor shell), disconnect the   motor and check for open windings per the motor wiring   diagram. If open windings are found, replace the motor.   If line voltage is not found at the BOR, trace the leads   back to the field supply terminal block, checking for an   open circuit or blown fuses.   3. The supply air blower operates but the draft motor does not   when the room thermostat is set to call for heat and the fan   switch in the “ON” position.   a. The draft motor has inherent protection. If the motor shell   is hot to the touch, wait for the internal overload to reset.   b. If the motor shell is cold with the room thermostat calling   for heat, check for line voltage at the motor’s Mate-N-   Lok connector attached to the evaporator partition. If   line voltage is present, replace the draft motor.   b. If the contactor M3 is not pulled in, check for control   voltage (24V) at the M3 coil. If voltage is found, replace   the contactor.If control voltage is not found at M3, check   for voltage across terminals 95 & 96 of the BOR. If   voltage exists, the BOR is open on overload. The BOR   should be set to the auto reset position. The BOR must   cool down in order to reset. If the BOR will not reset,   replace the BOR. If the BOR resets and M3 pulls in, but   the indoor blower motor will still not run, refer to para.   (a) for troubleshooting the line voltage supply circuit. If   control voltage is not found at the BOR, trace the circuit   back to the relay board and thermostat per the unit   wiring diagram. Replace any defective components.   c. If line voltage is not present, check for line voltage at the   heat relay (RW1) contacts in the main control box and   check to see if the (RW1) is pulled in.   d. If the (RW1) relay is pulled in, check for a loose line   voltage connection.   e. If the (RW1) relay is not pulled in, check for 24 volts at   the (RW1) coil. If 24 volts is present, replace the (RW1)   relay. If 24 volts is not present, check for a loose 24 volt   connection back to the relay board and check the con-   nections from the room thermostat to the relay board. If   all connections are correct, replace the relay board.   Cont’d.   Unitary Products Group   21   530.18-N11Y   TROUBLESHOOTING - Cont’d.   4. The draft motor runs but the furnace does not light and the   sparker does not spark.   d. If 24 volts is present, remove the pilot burner and   remove the pilot orifice from the pilot burner. The orifice   is removed in the direction opposite the flow of gas.   Inspect the orifice for obstruction. If it is clear, replace   the main gas valve.   a. The ignition control (IC1, IC2) may be locked out due to   either a flame roll out or 100% shut off. These safety   features are described above. If lock-out has occurred,   24V must be removed from the ignition controls. This is   done at the unit or by resetting the room thermostat.   After resetting 24V, check for proper furnace operation.   If lock-out continues to occur, locate the source of the   problem and correct.   6. The sparker sparks at the pilot burner but the pilot does not   ignite and a gas odor is detected at the draft motor outlet.   a. Adjust the pilot adjust screw on the gas valve as de-   scribed in “PILOT CHECKOUT”.   b. Check the supply pressure as described in “POST   b. Check all 24 volt connections from the relay board to   and in the gas heat section. Check low voltage connec-   tions to the (ETD) located in the control box.   START CHECK LIST”.Makeadjustmentsasnecessary.   c. Check the pilot orifice for obstruction as described in   para. 5d. Clean as needed but the problem should not   be the gas valve.   c. If the furnace is hot, it may be out on an over-tempera-   ture condition, wait for limit reset.   7. The pilot burner ignites but the sparker continues to spark   and the main burners do not ignite.   d. If the furnace is cold, check for 24 volts at wire 241   attached to the electronic time delay (ETD) located in   the main control box. If 24 volts is not found, replace the   ETD.   a. Make the same checks and adjustment as described in   para. 6.   e. With the draft motor running, check for 24 volts at   terminal 4 of (RW1-2) and (RW2-1). If 24 volts is not   present, the centrifugal switch (CS) has not closed or   has gone bad. Check the line voltage to the unit - if it is   correct, replace the draft motor.If line voltage is low, call   the power company.   b. Make sure that the pilot burner is not bent or damaged.   c. Make sure that the ground connections at the pilot   burner, gas valve and ignitor control are intact. Check   the high tension wire for good electrical connection. If   all are intact, replace the ignitor module.   8. The pilot burner lights and the spark stops but the main   burners do not light.   f. Check for 24V at terminal 2 of (RW1-2 and RW2-1). If   24V is not present, check for 24V at (RW1 and RW2)   relay coils. If these relays are pulled in, then check for   a loose connection at terminal 2 and terminal 4 of each   relay. If no problem is found, then replace (RW1 and/or   RW2) as required.   a. Check electrical connections between the ignitor con-   trol and the gas valve.If intact, check for 24 volts across   terminals “MV” and “COMMON” terminals. If no voltage   detected, replace ignitor control. If voltage is present,   replace gas valve.   g. If 24 volts is present at the ignitor controls, check all   control wiring at the ignitor controls and the high tension   wire to the ignitors. Check that the ground wires from   the ignitor controls, the gas valves and pilot burners are   all intact and making good electrical connection.Check   to make sure that the ceramic insulator on the pilot   ignitors or sensors is not broken or cracked, if all are   intact, replace the ignition control IC1 or IC2.   9. Furnace lights with roll-out or one burner has delayed   ignition.   a. Make sure that the pilot burner is aligned properly with   the carryover as described in “PILOT CHECKOUT”.   b. Make sure that the carryovers on adjoining burners are   screwed fast and are level with respect to one another.   5. The draft motor runs and the sparker sparks at the pilot   burner but the pilot does not ignite and a gas odor is not   detected at the draft motor outlet.   10. Main burners light but exhibit erratic flame characteristics.   a. Adjust air shutters as described in “BURNER AIR   a. Check to make sure gas is being supplied to the unit.   Make sure that the gas pressure to the unit is within the   proper limits as described in the “POST START CHECK   LIST” and that the pilot adjust screw is allowing some   flow of gas as described in “PILOT CHECKOUT”.   SHUTTER ADJUSTMENT”.   b. Check the main burner orifices for obstruction and   alignment. Removal procedure is described in   “BURNER INSTRUCTIONS”. Clean or replace burner   orifices and burners as needed.   b. Check all wiring between the ignitor control and the gas   valve. Check to make sure the ground connections are   intact.   c. If the wiring is intact, check for 24 volts across terminals   “PV” and “COMMON” on the ignitor control. If 24 volts   is not present, replace the ignitor control.   22   Unitary Products Group   530.18-N11Y   REPLACEMENT PARTS   GAS HEAT SECTION   COMPRESSOR SECTION   FABRICATED PARTS SECTION   • Hermetic compressor   • Compressor mounting   MOTOR SECTION   • Heat exchanger   • Panels   • Gas valve   • Posts   • Pilot   • Covers Drain pans   • Base rails   • Air hoods   • Flame sensor   • Spark ignitor   • Gas manifold   • Gas burner   • Blower motor   • Fan motor   MISCELLANEOUS SECTION   • Ventor motor   AIR MOVING SECTION   • Air inlet hood screen   ELECTRICAL SECTION   • Fan guard   • Blower wheel   • Air filters   • Ignition control   • Relay board   • Contactor   • Blower wheel housing   REFRIGERANT SECTION   • Circuit breaker   • Temperature controls   • Capacitors   • Evaporator coil   • Evaporator coil header   • Expansion valve assembly   • Condenser coil   • Relays   • Transformers   • Connectors   • Condenser coil header   TO OBTAIN PARTS INFORMATION: Replacement parts and information from OUR current parts list for this unit are available to   your servicing contractor through our local distributor. The name and address of our nearest distributor may be obtained by   consulting the Yellow Pages of a local telephone directory.   IMPORTANT: In order to supply the correct part or information from the parts list, our distributor will need to be provided with the   complete model number listed on the rating plate located on your unit. See page 2 for Product Nomenclature.   WARNING:IMPROPER INSTALLATION,ADJUSTMENT,SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY   DAMAGE. CONSULT A QUALIFIED INSTALLER, SERVICE AGENCY OR YOUR LOCAL GAS SUPPLIER FOR INFORMATION   OR ASSISTANCE.   Unitary Products Group   23   Unitary Products Group   5005 York Drive, Norman, Oklahoma 73069   Subject to change without notice. Printed in U.S.A.   Copyright by York International Corporation 1999. All Rights Reserved.   530.18-N11Y   Code: SBY   |