SUNLINE 2000
®
ELECTRIC / ELECTRIC & GAS / ELECTRIC
SINGLE PACKAGE AIR CONDITIONERS
(Constant Air Volume)
Supersedes: 530.18-N11Y (195)
530.18-N11Y (399)
035-16133
INSTALLATION INSTRUCTION
MODELS D2CE & D2CG300
(8.5 EER)
208/230/575
VOLT ONLY
208/230/460
VOLT ONLY
DCG MODEL
SHOWN
SAFETY CONSIDERATIONS
INSPECTION
Due to system pressure, moving parts and electrical components,
installation and servicing of air conditioning equipment can be
hazardous. Only qualified, trained, service personnel should
install, repair, maintain or service this equipment.
‘YORK Model DCE and DCG units are single package air
conditioners designed for outdoor installation on a rooftop or a
slab and is manufactured under ISO 9002 Quality System
Certification. The DCE models are cooling only and can be
equipped with factory installed electric heaters for cooling /
heating applications. The DCG models are gas-fired central
heating furnaces with cooling.
The units are completely assembled on rigid, permanently attached
baserails.Allpiping, refrigerantcharge, andelectricalwiringisfactory
installed and tested.All units require electric power, duct connections
and fixed outdoor air intake damper (units without economizer or
motorized damper option only) at the point of installation.
As soon as a unit is received, it should be inspected for
possible damage during transit. If damage is evident, the
extent of the damage should be noted on the carrier’s freight
bill. A separate request for inspection by the carrier’s agent
should be made in writing. Refer to Form 50.15-NM for
additional information.
REFERENCE
Additional information on the design, installation, operation and
service of this equipment is available in the following reference forms:
• 44-320-10
- Barometric Relief Damper Accessory
• 530.18-N6.1V - Propane Conversion Accessory
• 530.18-N6.2V - High Altitude Accessory (Nat. Gas)
• 530.18-N6.3V - High Altitude Accessory (Propane)
• 530.18-n13y - Coil Guard Installation
Renewal Parts:
The DCG units additionally require gas connection, installation of the
combustion air inlet hood and the flue gas outlet hoods at the point of
installation.The gas-fired heaters have aluminized-steel tubular heat
exchangers and spark ignition with proven pilot.
Supplemental electric heaters for DCE units have nickel-chrome
elements and utilize single point power connections.
• Refer to the Renewal Parts Manual for complete listing of
replacement parts on this equipment.
All forms referenced in this instruction may be ordered from:
Publications Distribution Center
Unitary Products Group
P.O. Box 1592, York, Pa. 17405
The following safety precautions apply to DCG units:
APPROVALS
Design certified by ETL & CGA as follows:
FOR YOUR SAFETY
1. For use as a central cooling only unit with or without
supplemental electric heat. (DCE models)
If you smell gas:
1. Open windows.
2. For useas aforced air furnacewithcoolingunit.(DCGmodels)
3. For use with natural gas or propane gas. (DCG models)
4. For outdoor installation only.
2. Don’t touch electrical switches; do not use
any phones in the area of the gas leak.
3. Extinguish any open flame.
4. Immediately call your gas supplier from another
location.Follow your gas supplier’s
instructions.
5. For installation on combustible material.
CAUTION
THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH
THE ENCLOSED INSTALLATION INSTRUCTIONS AND ANY
APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUDING, BUT
NOT LIMITEDTO, BUILDING, ELECTRICAL, AND MECHANICALCODES.
5. If you cannot reach your gas supplier, call the
fire department.
WARNING
FOR YOUR SAFETY
INCORRECT INSTALLATION MAY CREATE A CONDITION
WHERE THE OPERATION OF THE PRODUCT COULD CAUSE
PERSONAL INJURY OR PROPERTY DAMAGE
Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
Installer should pay particular attention to the words: NOTE, CAUTION and WARNING. Notes are intended to clarify or make
the installation easier.Cautions are given to prevent equipment damage.Warnings are given to alert installer that personal injury
and/or equipment damage may result if installation procedure is not handled properly.
530.18-N11Y
INSTALLATION
CAUTION: If a unit is to be installed on a roof curb or special
frame, gasketing must be applied to all surfaces
that come in contact with the unit underside.
LIMITATIONS
These units must be installed in accordance with the following
applicable national and local safety codes:
In U.S.A.:
1. National Electrical Code ANSI/NFPA No. 70.
2. National Fuel Gas Code Z223.1.
3. Gas-Fired Central Furnace Standard ANSI Z21.47a.
4. Local gas and electric utility requirements.
In Canada:
5. Maintain level tolerance to 1/2" maximum across the entire
length or width of the unit.
RIGGING AND HANDLING
Exercise care when moving the unit. Do not remove any
packaging until the unit is near the place of installation. Rig the
unit by attaching chain or cable slings to the round lifting holes
provided in the base rails. Spreaders, whose length exceeds
the largest dimension across the unit, MUST be used across
the top of the unit.
Units may also be moved or lifted with a forklift, from the front
or rear only, providing that an accessory skid is used.
LENGTH OF FORKS MUST BE A MINIMUM OF 90".
1. Current Canadian Electrical Code C22.1.
2. Current Gas Installation Codes CAN/CGA-B149.1 and .2
3. Local plumbing and waste water codes.
4. Other applicable local codes.
Refer to the Unit Application Data Table and to the Gas Heat Application
DataTable.
CAUTION: On gas heating units, an adhesive backed label is
provided over the outside of the combustion air inlet
opening to prevent moisture from entering the unit
which could cause damage to electrical
components. Allow this closure label to remain in
place until the combustion air hood is to be
installed.
After installation, units with gas heat must be adjusted to obtain a
temperature rise within the range specified on the unit rating plate.
If components are to be added to a unit to meet local codes, they
are to be installed at the dealer’s and/or the customer’s expense.
Size of unit for proposed installation should be based on heat
loss/heat gain calculation made according to the methods of
the Air Conditioning Contractors of America (ACCA).
This furnace is not to be used for temporary heating of buildings
or structures under construction.
TABLE 1 - UNIT APPLICATION DATA
208/230-3-60
460-3-60
575-3-60
187 / 253
414 / 506
518 / 630
Voltage Variation,
Min. / Max.1
Supply Air CFM, Min. / Max.
8,000 / 12,000
Wet Bulb Temperature (°F) of Air on
57 / 72
Evaporator Coil, Min. / Max.
Dry Bulb Temperature (°F) of Air on
25 / 120
Condenser Coil, Min.2 / Max.
1
2
Utilization range “A” in accordance with ARI Standard 110.
A low ambient accessory is available for applications down to 0°F.
LOCATION
Use the following guidelines to select a suitable location for
these units.
FIG. 1 - TYPICAL RIGGING
1. Unit is designed for outdoor installation only.
2. Condenser coils must have an unlimited supply of air.
Where a choice of location is possible, position the unit on
either north or east side of building.
3. For ground level installation, use a level concrete slab with
a minimum thickness of 4 inches. The length and width
should be at least 6 inches greater than the unit base rails.
Do not tie slab to the building foundation.
5
4
136-1/4"
WARNING:Excessive exposure of this furnace to contami-
nated combustionair may resultinequipmentdam-
age or personal injury. Typical contaminates in-
clude: permanent wave solutions, chlorinated
waxes and cleaners, chlorine based swimming
pool chemicals, water softening chemicals, carbon
tetrachloride, Halogen type refrigerants, cleaning
solvents (e.g. perchloroethylene), printing inks,
paint removers, varnishes, hydrochloric acid, ce-
ments and glues, antistatic fabric softeners for
clothes dryers, masonry acid washing materials.
FIG. 2 - CENTER OF GRAVITY
CLEARANCES
All units require certain clearances for proper operation and
service. Installer must make provisions for adequate combustion
and ventilation air in accordance with Section 5.3, Air for
Combustion and Ventilation of the National Fuel Gas Code, ANSI
Z223.1 (in U.S.A.) or Sections 7.2, 7.3 or 7.4 of Gas Installation
Codes CAN/CGA-B149.1 and .2 (in Canada) and/or applicable
provisions of the local building codes. Refer to Dimensions and
Clearances table for the clearances required for combustible
construction, servicing, and proper unit operation.
4. Roof structures must be able to support the weight of the
unit and its options and/or accessories. Unit must be in-
stalled on a solid level roof curb or appropriate angle iron
frame.
WARNING:Do not permit overhanging structures or shrubs to
obstruct outdoor air discharge outlet, combustion
air inlet or vent outlets.
Unitary Products Group
3
530.18-N11Y
DUCTWORK
Ductwork should be designed and sized according to the
methods in Manual Q of the Air Conditioning Contractors of
America (ACCA).
A closed return duct system shall be used. This shall not
preclude use of economizers or outdoor fresh air intake. The
supply and return air duct connections at the unit should be
made with flexible joints to minimize noise.
The supply and return air duct systems should be designed for
the CFM and static requirements of the job. They should NOT
be sized to match the dimensions of the duct connections on
the unit.
CAUTION: When fastening ductwork to side duct flanges on
unit, insert screws through duct flanges only. DO
NOT insert screws through casing.
Outdoor ductwork must be insulated and
waterproofed.
Refer to the Dimensions and Clearances figure for information
concerning side and bottom supply and return air duct openings.
FIG. 3 - FIXED OUTDOOR AIR DAMPER
CONDENSATE DRAIN
It is recommended that, in Canada, the outlet duct on gas
heating units be provided with a removable access panel. It is
recommended that this opening be accessible when the unit
is installed in service, and of a size such that smoke or
reflected light may be observed inside the casing to indicate
the presence of leaks in the heat exchanger.The cover should
be attached in a manner adequate to prevent leakage.
Plumbing must conform to local codes. Use a sealing
compound on male pipe threads.Install a condensate drain line
from the 1" NPT female connection on the unit to an open drain.
FIXED OUTDOOR AIR INTAKE DAMPER
This damper is shipped inside the return air compartment on units
that are not provided with an economizer or a motorized damper
option. It is completely assembled and ready for installation. A
damper baffle inside of the hood is adjustable to provide variable
amounts of outdoor air intake.
Gasketing and mounting screws are provided in a parts bag
attached to the hood assembly. Apply gasketing to the three
flange surfaces on the hood prior to installing the hood. Extend
gasketing 1/4" beyond the top and bottom of the two side
flanges to insure adequate sealing.
FIG. 4 - RECOMMENDED DRAIN PIPING
NOTE: The condensate drain line MUST be trapped to provide
proper drainage.
Adjusting the damper to the desired air flow may be done before
mounting the hood into position or (after installation) by
removing the front hood panel or the screen on the bottom of
the hood. Damper baffle in position 1 will allow approximately
10% recirculated air flow, position 2 approximately 15% and, to
allow approximately 25%, remove the damper baffle.
COMPRESSORS
Units are shipped with compressor mountings factory-adjusted
and ready for operation.
CAUTION: Do Not loosen compressor mounting bolts.
FILTERS
On units with bottom return air applications, install the damper
assembly over the opening in the side return air access panel.
Remove and discard the opening cover and the covering over
the hood mounting holes (used for shipping) before installing.
Secure with the screws provided.
2"filtersaresuppliedwith each unit.Filtersmust alwaysbeinstalled
ahead of the evaporator coil and must be kept clean or replaced
with same size and type. Dirty filters will reduce the capacity of the
unit and will result in frosted coils or safety shutdown.Minimum filter
area and required sizes are shown in the Physical Data Table.
SERVICE ACCESS
Access to all serviceable components is provided by the
following removable panels:
On units with side return air applications, install the damper
assembly on the return air ductwork as close to the unit as
possible. Cut an opening 16" high by 18" wide in the ductwork
to accommodate the damper. Using the holes in the hood
flanges as a template, drill 9/64" dia. (#26 drill) holes into the
ductwork and secure with the screws provided.
• Compressor compartment
• Electric Heat compartment - DCE models
• Gas Heat compartment (Two panels) - DCG models
• Side Supply & Return Air compartments (Two panels)
• Blower compartment (Three panels)
• Main control box
CAUTION: If outdoor air intake will not be required on units
with bottom return air applications, the damper
assembly should stillbemountedonthesidereturn
air access panel, per the instructions above, to
insure moisture is not drawn into the unit during
operation. The covering over the mounting holes
only need be removed. Do not remove the opening
cover.
• Filter compartment
• Outdoor Air compartment (Two panels)
Refer to the Dimensions and Clearances figure for location of these
access panels.
CAUTION: Make sure that all screws and panel latches are
replaced and properly positioned on the unit to
maintain an air-tight seal.
4
Unitary Products Group
530.18-N11Y
CONTROL WIRE SIZES
Wire Size1 AWG. Gauge
22
25
20
40
19
18
65
16
50
100
Maximum Wire Length2 Feet
Notes:
1. Solid, Class II copper wire
FIG. 5 - TYPICAL FIELD WIRING
Unitary Products Group
5
530.18-N11Y
THERMOSTAT
COMBUSTION DISCHARGE (DCG Models)
The room thermostat should be located on an inside wall
approximately 56" above the floor where it will not be subject
to drafts, sun exposure or heat from electrical fixtures or
appliances. Follow manufacturer’s instructions enclosed with
thermostat for general installation procedure. Seven color
coded insulated wires should be used to connect thermostat to
unit.
The products of combustion are discharged horizontally
through two screened (hooded) openings on the upper gas
heat access panel.
POWER AND CONTROL WIRING
Field wiring to the unit must conform to provisions of the
National Electrical Code, ANSI / NFPA No. 70 (in U.S.A.),
current Canadian Electrical Code C22.1 (in Canada) and/or
local ordinances. The unit must be electrically grounded in
accordance with NEC and CEC (as specified above) and/or
local codes. Voltage tolerances which must be maintained at
the compressor terminals during starting and running
conditions are indicated on the unit Rating Plate.
The internal wiring harness furnished with this unit is an integral
part of a ETL and CGA design certified unit. Field alteration to
comply with electrical codes should not be required.
FIG. 6 - EXTERNAL SUPPLY CONNECTION
EXTERNAL SHUT-OFF
A fused disconnect switch should be field provided for the unit.
The switch must be separate from all other circuits. Wire entry
at knockout openings require conduit fittings to comply with
NEC (in U.S.A.), CEC (in Canada) and/or local codes. If any
ofthe wire supplied withthe unit mustbereplaced, replacement
wire must be of the type shown on the wiring diagram and the
same minimum gauge as the replaced wire.
Electrical line must be sized properly to carry the load. Each
unit must be wired with a separate branch circuit fed directly
from the meter panel and properly fused.
GAS PIPING (DCG Models)
Proper sizing of gas piping depends on the cubic feet per hour
of gas flow required, specific gravity of the gas and the length
of run. “National Fuel Gas Code” Z223.1 (in U.S.A.) or the
current Gas Installation Codes CAN/CGA-B149.1 and .2 (in
Canada) should be followed in all cases unless superseded by
local codes or gas utility requirements. See Pipe Sizing table.
The heating value of the gas may differ with locality. The value
should be checked with the local gas utility.
CAUTION: When connecting electrical power and control
wiring to the unit, waterproof type connectors
MUST BE USED so that water or moisture cannot
be drawn into the unit during normal operation.The
above waterproofing conditions will also apply
when installing a field-supplied disconnect switch.
NOTE: There may be a local gas utility requirement specifying
a minimum diameter for gas piping. All units require a
1 inch pipe connection at the entrance fitting.
TABLE 3 - PIPE SIZING
Nominal Iron Pipe Size
Length in Feet
Refer to Typical Field Wiring Figure for typical field wiring and to
the appropriate unit wiring diagram for control circuit and power
wiring information.
1 in.
1-1/4 in.
10
20
30
40
50
60
70
80
90
100
520
350
285
245
215
195
180
170
160
150
1,050
730
590
500
440
400
370
350
320
305
OPTIONAL ELECTRIC HEATERS (DCE Models)
The factory installed heaters are wired for single point power
supply.Power supply need only be brought into the single point
terminal block and thermostat wiring to the low voltage terminal
block located in the upper portion of the unit control box.
Maximum capacity of pipe in cubic feet of gas per hour. (Based upon a pressure drop of 0.3
inch water column and 0.6 specific gravity gas).
These ETL and CGA approved heaters are located within the
central compartment of the unit with the heater elements
extending into the supply air chamber. Refer to the Dimension
and Clearances figure for access panel location.
GAS CONNECTION (DCG Models)
The gas supply line can be routed through the knockouts
located on the front of the unit or through the opening provided
in the unit’s base. Typical supply piping arrangements are
shown in the Supply Connection figures. All pipe, fittings, etc.
are field-supplied.
Two grommets are shipped in the blower compartment (in parts
bag taped to the blower housing) of every unit with gas heat
and should be used in the knockouts when the gas piping
enters through the front of the unit.
Fuses are supplied, where required, by the factory. Some KW
sizes require fuses and others do not. Refer to the Unit
Application Data Table 1 for minmum CFM limitations and to
Electrical Data Table.
TABLE 2 - GAS HEAT APPLICATION DATA
Input Capacity (Mbh)
Output Capacity (Mbh)
Temp.
Rise °F
At
After the gas supply piping has been installed, the bottom
opening in the unit should be sealed to prevent water from
leaking into the building.
0 To
2,000 To
0 To 2,000 To
Gas
Rate2
2,000 Feet
Above
Sea Level
4,500 Feet 2,000 Feet 4,500 Feet
Above Above Above
Sea Level1 Sea Level Sea Level1
Full Input 3
(Ft.3/Hr.)
Gas piping recommendations:
Max. Min. Max. Min.
Max.
240
Max.
213
Min.
20
Max.
50
1. A drip leg and a ground joint union must be installed in the
gas piping.
2. When required by local codes, a manual shut-off valve may
have to be installed outside of the unit.
3. Use wrought iron or steel pipe for all gas lines. Pipe com-
pound should be applied sparingly to male threads only.
300
400
150 270 135
200 360 180
279
372
320
281
30
60
NOTE: Heaters are shipped available for natural gas, but can be converted to
L.P. / Propane with Kit Model No. 1NP0418.
1
MBH rating should be reduced at the rate of 4 percent for each 1,000 feet above 4,500 feet.
2
3
3
Based on maximum input and 1075 Btu/Ft .
The air flow must be adjusted to obtain a temperature rise within the range shown.
6
Unitary Products Group
530.18-N11Y
L.P. UNITS, TANKS AND PIPING (DCG Models)
All gas heat units are shipped from the factory equipped for
natural gas use only. The unit may be converted in the field for
use with L.P./propane gas with accessory kit model number
1NP0418.
All L.P./propane gas equipment must conform to the safety
standards of the National Fire Protection Association.
For satisfactory operation, L.P./propane gas pressure must be
8.8 inch W.C at the unit under full load. Maintaining proper gas
pressure depends on three main factors:
FIG. 7 - BOTTOM SUPPLY CONNECTION
1. The vaporization rate which depends on (a) the tempera-
ture of the liquid and (b) the “wetted surface” area of the
container or containers.
EXTERNAL SHUT-OFF
WARNING:Natural gas may contain some propane. Propane,
being an excellent solvent, will quickly dissolve
white lead or most standard commercial
compounds. Therefore, a special pipe compound
must be applied when wrought iron or steel pipe is
used. Shellac base compounds such as Gaskolac
or Stalastic, and compounds such as Rectorseal
#5, Cyde’s or John Crane may be used.
2. The proper pressure regulation. (Two-stage regulation is
recommended from the standpoint of both cost and effi-
ciency.)
3. The pressure drop in the lines between regulators and
between the second stage regulator and the appliance.
Pipe size required will depend on the length of the pipe run
and the total load of all appliances.
4. All piping should be cleaned of dirt and scale by hammering
on the outside of the pipe and blowing out the loose dirt and
scale. Before initial start-up, be sure that all of the gas lines
external to the unit have been purged of air.
Complete information regarding tank sizing for vaporization,
recommended regulator settings, and pipe sizing is available
from most regulator manufacturers and L.P./propane gas
suppliers.
5. The gas supply should be a separate line and installed in
accordance with all safety codes as prescribed under
“Limitations”. After the gas connections have been
completed, open the main shut-off valve admitting normal
gas pressure to the mains. Check all joints for leaks with
soap solution or other material suitable for the purpose.
NEVER USE A FLAME.
L.P./propane gas is an excellent solvent and special pipe
compound must be used when assembling piping for this gas
as it will quickly dissolve white lead or most standard
commercial compounds. Shellac base compounds such as
Rectorseal #5 are satisfactory for this type of gas.
6. The furnace and its individual manual shut-off valve must
be disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in
excess of 1/2 psig (3.48kPa).
Check all connections for leaks when piping is completed,
using a soap solution. NEVER USE A FLAME.
The furnace must be isolated from the gas supply piping
system by closing its individual manual shut-off valve during
any pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig (3.48kPa).
7. A 1/8 inch NPT plugged tapping, accessible for test gage
connection, must be installed immediately upstream of the
gas supply connection to the furnace.
Unitary Products Group
7
530.18-N11Y
VENT AND COMBUSTION AIR HOODS
(DCG Models)
OPTIONAL ECONOMIZER/MOTORIZED DAMPER
RAIN HOOD
The instruction for the optional economizer/motorized damper
rain hood can be found in form 44-320-2.Use these instructions
when field assembling an economizer rain hood onto a unit.
The outdoor and return air dampers, the damper actuator, the
damper linkage, the outdoor and return air divider baffles, and
all the control sensors are factory mounted as part of the
"Factory installed" economizer option.
Two vent hoods and a combustion air hood (with screens) are
shipped attached to the blower housing in the blower
compartment. These hoods must be installed to assure proper
unit function. All hoods must be fastened to the outside of the
gas heat access panel with the screws provided in the bag also
attached to the blower housing.
ENTHALPY SET POINT ADJUSTMENT
The screen for the combustion air intake hood is secured to the
inside of the access panel opening with four fasteners and the
screws used for mounting the hood to the panel.The top flange
of this hood slips in under the top of the access panel opening
when installing.Refer to the Vent and Combustion Hood figure.
Remove the economizer access panel from the unit to check
the following adjustments. Loosen but do not remove the two
panel latches.
Each vent hood is installed by inserting the top flange of the
hood into the slotted opening in the access panel and securing
in place.
CAUTION: Extreme care must be exercised in turning both the
setpoint and minimum position adjusting screws to
prevent twisting them off.
1. The enthalpy set point may now be set by selecting the
desired setpoint shown in the Enthalpy figure. Adjust as
follows:
• For a single enthalpy operation, carefully turn the set
point adjusting screw to the “A”, “B”, “C” or “D” setting
corresponding to the lettered curve.
• For a dual enthalpy operation, carefully turn the set point
adjusting screw fully clockwise past the “D” setting.
SLOTTED
OPENINGS IN
ACCESS PANEL
VENT AIR
OUTLET
HOODS
2. To check that the damper blades move smoothly without
binding, carefully turn the minimum position adjusting
screw fully clockwise and then energize and de-energize
terminals “R” to “G”. With terminals “R” to “G” energized,
turn the minimum position screw counterclockwise until the
desired minimum position has been attained.
3. Replace the economizer access panel. Reposition the two
latches horizontally and retighten the screws.
POWER EXHAUST/BAROMETRIC RELIEF DAMPER
AND RAIN HOOD OPTION
COMBUSTION
AIR INTAKE
HOOD
GAS HEAT
ACCESS
PANELS
The instructions for the power exhaust/barometric relief
damper and rain hood can be found in form 44-320-10. The
exhaust fan, all supporting brackets, angles, and the wiring are
factory installed as part of the power exhaust option.
All of the components, including the dampers, hardware, and
mounting instructions are shipped in a single package external
from the unit. The hood must be field assembled and installed.
FIG. 8 - VENT AND COMBUSTION AIR HOODS
Power exhaust is not available as a field installed option.
8
Unitary Products Group
530.18-N11Y
FIG. 9 - ENTHALPY SETPOINT ADJUSTMENT
Unitary Products Group
9
530.18-N11Y
TABLE 4 - PHYSICAL DATA
DCE/DCG
300
18 x 15
15
OPERATING WEIGHTS (LBS.)
DCE (Cooling only)
25 TON
2730
2930
MODELS
CENTRIFUGAL BLOWER (Dia. x Wd. in.)
FAN MOTOR HP
ROWS DEEP
FINS PER INCH
FACE AREA (Sq. Ft.)
PROPELLER DIA. (in.) (Each)
FAN MOTOR HP
NOM. CFM TOTAL
ROWS DEEP
DCG
(Gas /
Electric)
N240
EVAPORATOR
BLOWER
Basic Unit
N320
2970
160
4
EVAPORATOR
COIL
Economizer
Economizer with
Power Exhaust
13.5
25.0
30
1
7200
3
245
CONDENSER
FAN
(Two Per Unit)
Motorized Damper
150
25
30
35
40
(Each)
(Each)
Options
18 KW
36 KW
54 KW
72 KW
Electric
Heater
(DCE only)
CONDENSER
COIL
FINS PER INCH
FACE AREA (Sq. Ft.)
15
43.3
Roof Curb
Barometric Damper
185
45
COMPRESSOR
(Qty. Per Unit)
12.5-TON TANDEM
2
Economizer/Motorized
Accessories Damper Rain Hood
QUANTITY PER UNIT (16" X 20" X 2")
QUANTITY PER UNIT (16" X 25" X 2")
QUANTITY PER UNIT (14" X 20" X 2")
TOTAL FACE AREA (sq. ft.)
2
4
3
21.4
20/8
20/0
55
AIR
FILTERS
Economizer/Power Exhaust
Rain Hood
Wood Skid
90
220
SYSTEM NO. 1
SYSTEM NO. 2
REFRIGERANT
22 (lbs./oz.)
CHARGE
*This compressor will be energized first.
TABLE 5 - ELECTRICAL DATA - BASIC UNITS
COMPRESSORS
COND. FAN
(#1 & #2)
SUPPLY AIR
BLOWER MOTOR
MINIMUM
CIRCUIT
MAXIMUM
POWER
SUPPLY
(QTY. 2)
OVERCURRENT
MODEL NO.
RLA
LRA
(ea.)
HP
(ea.)
FLA
(ea.)
AMPACITY
(AMPS)
DEVICE (1)
(AMPS)
HP
RLA
(ea.)
41.4
20.0
16.4
D2CE300 208/230-3-60
312
140
108
1
1
1
4.2
2.1
2.0
15
15
15
38.6
19.3
15.4
139.5
68.3
56.1
175
80
70
& D2CG300
460-3-60
575-3-60
VOLTAGE
POWER SUPPLY
MIN.
187
414
518
MAX.
253
VOLTAGE
LIMITATIONS**
208/230-3-60
460-3-60
506
575-3-60
630
**Utilization Range “A” in accordance with ARI Standard 110.
TABLE 6 - ELECTRICAL DATA - UNITS w/ELECTRIC HEAT
MINIMUM
CIRCUIT
MAXIMUM
ELECTRIC HEATER OPTION
MODEL
D2CE
POWER
SUPPLY
OVERCURRENT
DEV ICE (1)
A MPA CITY
MODEL
kW(1)
STAGES AMPS
(AMPS)
139.5
142.1
189.0
198.4
139.5
156.5
178.2
221.5
68.3
(AMPS)
175
175
200
225
175
175
200
250
80
300A25
300A25
300A25
300A25
300A25
300A25
300A25
300A25
300A46
300A46
300A46
300A46
300A58
300A58
300A58
300A58
208-3-60
208-3-60
208-3-60
208-3-60
230-3-60
230-3-60
230-3-60
230-3-60
460-3-60
460-3-60
460-3-60
460-3-60
575-3-60
575-3-60
575-3-60
575-3-60
E018
E036
E054
E072
E018
E036
E054
E072
E018
E036
E054
E072
E018
E036
E054
E072
13.5
27.0
40.6
54.1
18.0
36.0
54.0
72.0
18.0
36.0
54.0
72.0
18.0
36.0
54.0
72.0
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
37.5
75.1
112.6
150.1
43.3
86.6
129.9
173.2
21.7
43.3
65.0
86.6
17.3
34.6
52.0
69.3
78.3
80
89.1
100
125
70
110.7
56.1
62.6
71.2
70
80
88.5
100
NOMINAL VOLTAGE
VOLTAGE
208
KW CAP. MULTIPLIER
208
240
480
600
1.00
0.92
0.92
0.92
230
460
575
10
Unitary Products Group
530.18-N11Y
E
F
P
(
C
O
O
N
O
M
I
Z
E
H
R
/
M
O
T
O
R
I
Z
a
E
D
D
A
M
P
E
R
,
I
X
E
e
D
O
U
T
D
O
O
R
I
N
T
A
K
E
A
I
R
A
N
D
F
D
L
I
E
L
D
-
S
U
P
P
L
I
E
D
W
E
R
E
X
A
U
S
T
R
A
I
N
H
O
O
D
S
All dimensions are in inches. They are sub-
ject to change without notice. Certified di-
mensions will be provided upon request.
I
S
C
O
N
N
E
C
T
S
W
I
T
C
H
S
e
d
e
t
a
i
l
"
Y
"
)
B
A
L
C
O
W
E
R
O
C
A
T
I
O
N
C
A
(
O
M
P
R
E
S
G
S
O
R
C
E
S
S
C
C
E
S
S
S
e
e
d
e
t
i
l
"
X
"
)
B
A
L
C
O
W
P
E
R
M
O
T
O
R
C
E
S
S
O
C
P
T
I
O
N
A
L
B
C
A
(
L
C
O
W
E
R
O
I
L
U
A
R
D
O
M
P
A
R
T
M
E
N
T
C
E
S
S
A
u
x
i
l
i
a
r
y
)
5
2
-
5
/
8
"
RETURN AIR
SUPPLY AIR
D
(
D
O
r
T
L
U
G
F
o
r
p
r
e
s
s
u
r
e
o
p
R
e
a
d
i
n
g
)
C
C
O
O
N
I
D
E
N
S
E
R
L
S
2
1
"
5
"
1
3
6
-
1
/
4
"
CONDENSER AIR
F
V
R
O
N
T
9
-
3
/
4
"
E
A
L
C
E
C
T
R
I
C
H
E
A
T
9
2
"
I
E
W
C
E
S
S
(
C
E
A
)
OUTDOOR AIR
(Economizer)
5
-
7
/
8
"
O
N
T
R
O
L
W
I
R
I
N
G
C
A
O
N
T
R
O
L
B
O
X
N
T
R
Y
C
C
E
S
S
1
1
-
1
/
2
"
(
P
E
B
)
3
5
"
B
O
T
T
O
M
S
U
P
P
L
Y
O
N
W
E
R
W
I
R
I
N
G
A
N
D
R
E
T
U
R
N
T
R
S
Y
A
I
R
O
P
E
N
I
N
G
(
S
e
e
N
o
t
e
)
3
5
-
1
/
4
"
R
E
T
U
R
N
3
-
3
/
4
"
A
I
R
3
3
"
S
U
P
P
L
Y
A
I
R
UTILITIES ENTRY DATA
2
-
3
/
2
4
1
"
-
1
/
2
"
OPENING
SIZE
(DIA.)
HOLE
A
USED FOR
U
S
B
C
N
I
T
B
A
S
E
W
I
T
H
R
A
I
L
S
(
P
E
B
A
)
)
h
o
o
t
w
n
s
e
p
a
r
a
t
e
l
y
n
t
n
o
i
l
l
u
s
t
r
a
t
e
O
N
W
E
R
W
I
R
I
N
G
t
o
m
D
u
c
t
o
p
e
i
g
s
a
n
d
P
o
w
e
r
T
T
R
R
Y
Y
1-1/8" KO
3/4" NPS (Fem.)
3-5/8" KO
3" NPS (Fem.)
2-3/8" KO
Front
Bottom
Front
Control
Wiring
o
n
n
e
c
t
i
o
n
l
o
c
a
t
i
o
n
s
(
C
E
O
N
T
R
O
L
W
I
R
I
N
G
8
-
1
/
8
"
N
N
F
d
s
O
T
E
:
Power
Wiring
B
C
o
r
c
u
r
b
m
o
u
n
t
e
d
u
n
i
t
s
,
r
e
f
e
r
t
o
p
t
h
e
c
u
r
b
z
h
a
n
g
e
r
9
-
1
h
/
4
"
Bottom
i
m
e
p
n
s
i
o
n
n
s
o
f
t
h
e
c
u
r
b
f
o
r
t
e
r
o
p
e
r
s
i
e
o
f
t
h
e
1
2
-
1
/
2
"
9
-
3
/
4
"
u
p
l
y
a
d
r
e
t
u
r
n
a
i
r
d
u
c
t
c
o
n
n
e
c
t
i
o
n
s
.
Gas Piping (Front)
D
1-11/16" Hole Gas Piping (Bottom)*
E
F
P
(
C
O
O
N
O
M
I
Z
E
H
R
/
M
O
T
O
R
I
Z
E
D
D
A
M
P
E
R
,
B
A
L
C
O
W
E
R
I
X
E
e
D
O
U
T
D
O
O
R
I
N
T
A
K
E
A
I
R
A
N
D
C
E
S
S
*Opening in the bottom of the unit can be located by the slice
F
D
L
I
E
L
D
-
S
U
P
P
L
I
E
D
W
E
R
E
X
A
U
S
T
R
A
I
N
H
O
O
D
S
I
S
C
O
N
N
E
C
T
S
W
I
T
C
H
B
A
L
C
O
W
E
R
M
O
T
O
R
S
e
d
e
t
a
i
l
"
Y
"
)
in the insulation.
O
C
A
T
I
O
N
C
A
(
O
M
P
R
E
S
S
O
R
C
E
S
S
C
C
E
S
S
B
C
A
(
L
C
O
W
E
R
S
e
e
d
e
t
a
i
l
"
X
"
)
O
M
P
A
R
T
M
E
N
T
C
E
S
S
L CLEARANCES
O
C
P
T
I
O
N
A
A
u
x
i
l
i
a
r
y
)
O
I
L
G
U
A
R
D
Front
36"
D
(
D
O
r
T
P
L
U
G
F
o
r
p
r
e
s
s
u
r
e
5
2
-
5
/
8
24" (Less Economizer)
49" (With Economizer)
o
p
R
e
a
d
i
n
T
g
)
Back
G
A
A
S
H
E
A
24" (Less Economizer)
C
C
E
S
S
Left Side (Filter Access)
36"3(With Economizer)
C
C
O
O
N
I
D
E
N
S
E
R
V
O
H
E
N
T
A
I
R
L
S
U
T
O
L
E
T
Right Side (Cond. Coil)
Below Unit1
36"
20"
O
D
S
2
1
"
5
"
7
-
1
/
8
"
C
A
H
O
O
M
O
B
U
S
T
I
O
N
1
3
6
-
1
/
4
I
R
I
N
L
E
T
72" With 36" Maximum
Horizontal Overhang
(For Condenser Air
Discharge)
D
6
-
3
/
8
"
Above Unit2
9
-
3
/
4
"
9
2
"
(
G
E
C
)
5
-
7
/
8
"
(
C
E
A
)
A
S
S
U
P
P
L
Y
O
N
T
R
O
L
W
I
R
I
N
G
N
T
R
Y
1
N
T
R
Y
4
6
-
5
/
8
"
Units (applicable in U.S.A. only) may be installed on combustible floors
made from wood or class A, B or C roof covering material.
C
A
O
N
T
R
O
L
B
O
X
1
1
-
1
/
2
"
(
P
E
B
)
3
5
"
C
C
E
S
S
2
O
N
W
E
R
W
I
R
N
G
I Units must be installed oudoors. Overhanging structures or shrubs should
B
O
T
T
O
M
S
U
P
P
L
Y
T
R
Y
not obstruct condenser air discharge outlet.
If economizer is factory installed, the assembled hood kit must be removed
prior to final installation. This hood is 54" long.
A
N
D
R
E
T
U
R
N
3
A
I
R
O
P
E
N
I
N
G
S
F
V
R
O
N
T
(
S
e
e
N
o
t
e
)
3
5
-
1
/
4
I
E
W
R
E
T
U
R
N
3
-
3
/
4
"
A
I
R
NOTE:
3
3
"
DCE Models: Units and ductwork are approved for zero clearance to combus-
tible materials when equipped with electric heaters.
S
U
P
P
L
Y
A
I
R
2
-
3
/
2
4
1
"
-
1
/
2
"
DCG Models: A 1" clearance must be provided between any combustible
material and the supply air ductwork for a distance of 3 feet from the unit.
1
1
-
1
/
8
"
The products of combustion must not be allowed to accumulate within a
confined space and recirculate.
G
U
N
I
T
B
A
S
E
W
I
T
H
R
A
I
L
S
(
P
E
B
A
)
)
(
G
E
D
)
S
B
a
l
h
o
o
t
w
n
s
e
p
a
r
a
t
e
l
y
n
t
n
o
i
l
l
u
s
t
r
a
t
e
O
N
W
E
R
W
I
R
I
N
A
S
S
U
P
P
L
Y
t
o
m
D
u
c
t
o
p
e
i
g
s
,
P
o
w
n
e
r
T
T
R
R
Y
Y
N
T
R
Y
Locate unit so that the vent air outlet hood is at least:
n
d
G
a
s
P
i
p
i
n
g
C
o
n
n
e
c
t
i
o
(
C
E
o
c
a
t
i
o
n
s
• Three (3) feet above any forced air inlet located within 10 horizontal feet
O
N
T
R
O
L
W
I
R
I
N
G
8
-
1
/
8
"
N
(excluding those integral to the unit).
N
F
d
s
O
T
E
:
4
6
-
5
/
8
"
o
r
c
u
r
b
m
o
u
n
t
e
d
u
n
i
t
s
,
r
e
f
e
r
t
o
p
t
h
e
c
u
r
b
z
h
a
n
g
e
r
• Four (4) feet below, 4 horizontal feet from, or 1 foot above any door or gravity
9
-
1
h
/
4
"
i
m
e
p
n
s
i
o
n
n
s
o
f
t
h
e
c
u
r
b
f
o
r
t
e
r
o
p
e
r
s
i
e
o
f
t
h
e
air inlet into the building.
1
2
-
1
/
2
"
9
-
3
/
4
"
u
p
l
y
a
d
r
e
t
u
r
n
a
i
r
d
u
c
t
c
o
n
n
e
c
t
i
o
n
s
.
• Four (4) feet from electric meters, gas meters, regulators and relief equip-
ment.
Cont’d.
FIG. 10 - DIMENSIONS & CLEARANCES - DCE & DCG
Unitary Products Group
11
530.18-N11Y
CONDENSER
SECTION
EVAPORATOR
SECTION
GAUGE LINE
ACCESS
DUCT COVERS - Units are shipped with the bottom
duct openings covered. An accessory flange kit is avail-
able for connecting side ducts.
DOT PLUG
(For pressure
drop reading)
For bottom duct applications:
40-3/8"
1. Remove the side panels from the supply and return
air compartments to gain access to the bottom
supply and return air duct covers.
FILTER
ACCESS
2. Remove and discard the bottom duct covers. (Duct
openings are closed with sheet metal covers except
when the unit includes a power exhaust option. The
covering consists of a heavy black paper composition.)
3. Replace the side supply and return air compartment
panels.
SUPPLY
AIR
RETURN
AIR
5-1/2"
COMPRESSOR
ACCESS
OUTDOOR
AIR
For side duct applications;
40-1/2"
SUPPLY AIR
ACCESS
1. Replace the side panels on the supply and return air
compartments with the accessory flange kit panels.
2. Connect ductwork to the duct flanges on the rear of
the unit.
18-5/8"
1" NPT FEMALE
COND. DRAIN
CONNECTION
27-3/4"
5-1/8"
RETURN AIR
ACCESS
OUTDOOR AIR
COMPARTMENT
ACCESS
39-5/8
REAR
VIEW
DETAIL “X”
ACCESSORY SIDE SUPPLY AND RETURN AIR OPENINGS
ECONOMIZER
MOTORIZED
DAMPER
RAIN HOOD
(on Outdoor Air Compartment)
POWER EXHAUST
RAIN HOOD
(on Return Air Compartment)
SUPPLY AIR
COMPARTMENT
ECONOMIZER MOTORIZED DAMPER
/
AND POWER EXHAUST RAIN HOODS
FIXED
OUTDOOR AIR
INTAKE HOOD
(located on
Return Air
34-1/4"
Compartment)
1" CONDENSTATE
DRAIN
16-1/8"
(Must be trapped)
5"
36"
92"
36-1/4"
2"
66-1/2"
LH VIEW
REAR VIEW
DETAIL "Y"
UNIT WITH RAIN HOODS
DETAIL “Y”
UNIT WITH RAIN HOODS
FIG. 10 - DIMENSIONS & CLEARANCES (Cont’d.)- DCE & DCG
12
Unitary Products Group
530.18-N11Y
B
E
F
C
D
A
A
C
FRONT
FRONT
4 POINT LOADS
6 POINT LOADS
D
B
FIG. 11- FOUR AND SIX POINT LOADS
TABLE 7 - FOUR AND SIX POINT LOADS
4 - POINT LOADS (LBS)
UNIT
TOTAL
3,130
A
615
B
671
C
D
300
962
882
NOTE: These weights are with economizer, high heat, and the largest blower motor available.
6 - POINT LOADS (LBS)
UNIT
TOTAL
3,130
A
B
C
D
628
E
603
F
510
300
418
438
533
NOTE: These weights are with economizer, high heat, and the largest blower motor available.
DCE300 - BOTTOMDUCTCONNECTIONS(COOLING APPLICATIONS)
TABLE 8 - SUPPLY AIR BLOWER PERFORMANCE
7500 CFM
OUTPUT
(bhp)
8750 CFM
OUTPUT
(bhp)
10000 CFM
OUTPUT
(bhp)
11250 CFM
OUTPUT
(bhp)
12500 CFM
OUTPUT
(bhp)
BLOWER PULLEY
SPEED
(rpm)
TURNS
OPEN:
ESP
(iwg)
INPUT
(kW)
ESP
(iwg)
INPUT
(kW)
ESP
(iwg)
INPUT
(kW)
ESP
(iwg)
INPUT
(kW)
ESP
(iwg)
INPUT
(kW)
STANDARD DRIVE:
975
6.0*
5.0
4.0
3.0
2.0
1.0
0.0
1.4
1.6
1.8
2.0
2.1
2.4
2.6
5.9
6.2
6.6
6.9
7.3
7.7
8.0
4.9
5.1
5.4
5.7
6.0
6.3
6.6
1.0
1.2
1.4
1.6
1.8
2.0
2.2
7.3
7.7
8.1
8.5
8.9
9.3
9.7
6.0
0.5
0.7
0.9
1.1
1.3
1.6
1.8
8.8
9.2
9.7
10.2
10.6
11.1
11.6
7.2
7.6
8.0
8.3
8.7
9.1
9.5
-
-
-
-
-
-
-
-
-
-
-
-
1005
1040
1070
1100
1135
1165
6.3
6.7
7.0
7.3
7.6
8.0
0.1
0.3
0.6
0.8
1.0
1.3
10.9
11.4
11.9
12.4
13.0
13.5
8.9
9.4
9.8
10.2
10.6
11.0
-
-
-
0.2
0.4
0.7
14.3
14.9
15.5
11.7
12.2
12.7
ACCESSORY DRIVE:
1140
1180
1215
1255
1290
1330
1365
NOTES:
6.0
5.0
4.0
3.0
2.0
1.0
0.0
2.4
2.7
2.9
3.2
3.4
3.7
3.9
7.7
8.2
8.6
9.1
9.5
10.0
10.5
6.3
6.7
7.0
7.4
7.8
8.2
8.6
2.1
2.3
2.6
2.9
3.1
3.4
3.7
9.4
9.9
7.7
8.1
8.5
9.0
9.4
9.9
10.3
1.6
1.9
2.2
2.5
2.7
3.0
3.3
11.2
11.8
12.3
12.9
13.5
14.1
14.7
9.2
9.7
1.1
1.4
1.7
2.0
2.2
2.6
2.9
13.1
13.7
14.3
15.0
15.6
16.4
17.0
10.7
11.2
11.7
12.3
12.8
13.4
13.9
0.5
0.8
1.1
1.4
-
-
-
15.0
15.8
16.4
17.2
-
-
-
12.3
12.9
13.5
14.1
-
-
-
10.4
11.0
11.5
12.0
12.6
10.1
10.6
11.1
11.6
12.1
Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry evaporator coil.
Refer to page 14 for additional static resistances.
ESP - External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the
blower.
* FACTORY SETTING
Unitary Products Group
13
530.18-N11Y
TABLE 9 - SUPPLY AIR BLOWER PERFORMANCE DCG300-BOTTOM DUCT CONNECTIONS(COOLING APPLICATIONS)
7500 CFM
OUTPUT
(bhp)
8750 CFM
OUTPUT
(bhp)
10000 CFM
OUTPUT
(bhp)
11250 CFM
OUTPUT
(bhp)
12500 CFM
OUTPUT
(bhp)
BLOWER PULLEY
SPEED
(rpm)
TURNS
OPEN:
ESP
(iwg)
INPUT
(kW)
ESP
(iwg)
INPUT
(kW)
ESP
(iwg)
INPUT
(kW)
ESP
(iwg)
INPUT
(kW)
ESP
(iwg)
INPUT
(kW)
STANDARD DRIVE:
975
6.0
5.0
4.0
3.0
2.0
1.0
0.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
5.9
6.2
6.6
6.9
7.3
7.7
8.0
4.9
5.1
5.4
5.7
6.0
6.3
6.6
0.5
0.7
0.9
1.1
1.3
1.6
1.8
7.3
7.7
8.1
8.5
8.9
9.3
9.7
6.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1005
1040
1070
1100
1135
1165
6.3
6.7
7.0
7.3
7.6
8.0
0.2
0.4
0.6
0.8
1.0
9.7
8.0
8.3
8.7
9.1
9.5
10.2
10.6
11.1
11.6
-
0.2
13.5
11.0
ACCESSORY DRIVE:
1140
1180
1215
1255
1290
1330
1365
NOTES:
6.0
5.0
4.0
3.0
2.0
1.0
0.0
2.2
2.5
2.7
3.0
3.2
3.5
3.7
7.7
8.2
8.6
9.1
9.5
10.0
10.5
6.3
6.7
7.0
7.4
7.8
8.2
8.6
1.6
1.9
2.1
2.4
2.7
3.0
3.2
9.4
9.9
7.7
8.1
8.5
9.0
9.4
9.9
10.3
0.9
1.2
1.4
1.7
2.0
2.3
2.6
11.2
11.8
12.3
12.9
13.5
14.1
14.7
9.2
9.7
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.3
0.6
0.9
1.2
1.5
1.8
13.7
14.3
15.0
15.6
16.4
17.0
11.2
11.7
12.3
12.8
13.4
13.9
10.4
11.0
11.5
12.0
12.6
10.1
10.6
11.1
11.6
12.1
Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry evaporator coil.
Refer to page 14 for additional static resistances.
ESP - External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the
blower.
* FACTORY SETTING
TABLE 10 - STATIC RESISTANCES*
AIRFLOW (CFM)
7500
ESP
8750
ESP
10000
ESP
11250
ESP
12500
ESP
DESCRIPTION
(IWG)
(IWG)
(IWG)
(IWG)
(IWG)
DEDUCTIONS: (SUBTRACT VALUES BELOW FROM UNIT'S AVAILABLE ESP)
ALLOWANCE FOR WET COIL:
ECONOMIZER (RETURN DUCT):
18kW ELECTRIC HEAT:
0.10
0.06
0.31
0.38
0.62
0.68
0.10
0.09
0.43
0.52
0.84
0.93
0.10
0.11
0.56
0.68
1.10
1.21
0.10
0.14
0.71
0.87
1.39
1.54
0.10
0.18
0.87
1.07
1.72
1.90
36kW ELECTRIC HEAT:
54kW ELECTRIC HEAT:
72kW ELECTRIC HEAT:
ADDITIONS: (ADD VALUES BELOW TO UNIT'S AVAILABLE ESP)
HORIZONTAL (SIDE) SUPPLY DUCT:
HORIZONTAL (SIDE) RETURN DUCT:
0.31
0.05
0.26
0.05
0.27
0.05
0.31
0.05
0.41
0.05
TABLE 11 - POWER EXHAUST PERFORMANCE
STATIC RESISTANCE OF RETURN DUCTWORK, IWG
0.3 0.4 0.5
MOTOR
SPEED
0.2
0.6
CFM
5250
KW
CFM
KW
CFM
KW
CFM
KW
CFM
3000
KW
HIGH*
0.83
4500
0.85
4200
0.88
3750
0.93
0.99
MEDIUM
4900
4400
0.77
0.72
3900
3700
0.79
0.74
3500
3000
0.82
0.78
2900
-
0.85
-
-
-
-
-
LOW
*Factory Setting
Power Exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection.
TABLE 12 - BLOWER MOTOR AND DRIVE DATA
BELT
(NOTCHED)
MOTOR1
ADJUSTABLE MOTOR PULLEY
FIXED BLOWER PULLEY
OUTSIDE PITCH
BLOWER
DRIVE RANGE
(RPM)
MODEL
SIZE
OUT-
PITCH
PITCH
LENGTH
(IN.)
EFF.
(%)
DESIG-
NATION
SIDE
DIA.
(IN.)
BORE DESIG-
(IN.) NATION
BORE DESIG-
QTY.
HP FRAME
DIA.
(IN.)
DIA.
(IN.)
DIA.
(IN.)
(IN.) NATION
Stan-
975/1165
dard
1B5V110 11.3
11.1 1-7/16 5VX860 86.0
9.5 1-7/16 5VX840 84.0
1
1
6.2-
7.4
25 TON
15 254T
91 1LVP58B70A 7.5
1-5/8
High
Speed 1140/1365
Access
1B5V94
9.7
1
All motors have a nominal speed of 1800 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because they are located in the moving air, upstream
of any heating device.
14
Unitary Products Group
530.18-N11Y
OPERATION
addition. The power exhaust motor is energized whenever the
economizer is chosen by the enthalpy sensor for first stage
cooling, “Y1". As always, the ”R" to “G” connection provides
minimum position but does not provide power exhaust
operation.
MOTORIZED OUTDOOR AIR DAMPERS - This system
operation is the same as the units with no outdoor air options
with one exception. When the “R” to “G” circuit is complete, the
motorized damper drives open to a position set by the damper
motor adjustment. When the “R” to “G” circuit is opened, the
damper spring returns fully closed.
COOLING SYSTEM
The cooling section is a complete factory package utilizing an
air-cooled condenser. The system is factory-charged with
Refrigerant-22.
The compressors are hermetically sealed, internally sprung
and base-mounted with rubber-insulated hold-down bolts.
Compressors have inherent (internal) protection. If there is an
abnormal temperature rise in a compressor, the protector will
open to shut down the compressor.
PRELIMINARY OPERATION COOLING
CONTINUOUS BLOWER - Continuous blower operation is
possible by closing the R to G circuit on the thermostat.
After the initial installation, the compressors should be given
three false starts (energized just long enough to make a few
revolutions) with 5-7 minutes delay between each start, before
being put into full time service.
SAFETY CONTROLS
Each refrigerant system is equipped with the following safety
controls:
COOLING SEQUENCE OF OPERATION
NO OUTDOOR AIR OPTIONS - When the room thermostat
calls for “first-stage”cooling, the low voltage control circuit from
“R” to “G” and “Y1" is completed to energize compressors #1/2
(50% capacity), condenser fan motor #1, and the supply air
blower motor (if the fan switch on the room thermostat is set in
the ”AUTO" position).
When the thermostat calls for “second-stage” cooling, the low
voltage control circuit from “R” to “Y2" is completed to energize
compressor #3/4.
After the thermostat is satisfied and opens, all components will
stop simultaneously. The blower motor will continue to operate
if the fan switch on the room thermostat is set in the “ON”
position.
1. A Suction Line Freezestat to protect against low evaporator
temperatures due to a low air flow or a low return air
temperature. (Opens at 26°F + 5°F and resets at 38°F +
5°F)
2. A High Pressure Cutout Switch to protect against excessive
discharge pressures due to a blocked condenser coil or a
condenser motor failure.(Opens at380 psig +10and resets
at 300 psig +10)
3. A Low Pressure Switch/Loss Of Charge to protect against
loss of refrigerant charge. (Opens at 7 psig + 3 and resets
at 22 psig + 5)
ECONOMIZER WITH SINGLE ENTHALPY SENSOR - When
the room thermostat calls for “first-stage” cooling, the low
voltage control circuit from “R” to “G” and “Y1" is completed.
The ”R" to “G” circuit energizes the blower motor (if the fan
switch on the room thermostat is set in the “AUTO” position)
and drives the economizer dampers from fully closed to their
minimum position.If the enthalpy of the outdoor air is below the
setpoint of the enthalpy controller (previously determined), “Y1"
energizes the economizer. The dampers will modulate to
maintain a constant supply air temperature as monitored by the
discharge air sensor. If the outdoor air enthalpy is above the
setpoint, ”Y1" energizes compressors #1/2, and condenser fan
motor #1.
When the thermostat calls for “second-stage” cooling, the low
voltage control circuit from “R” to “Y2" is completed. If the
enthalpy of the outdoor air is below the setpoint of the enthalpy
controller (i.e. first stage has energized the economizer), ”Y2"
will energize compressors #1/2. If the outdoor air is above the
setpoint, “Y2" will energize compressor #3/4.
If either one of the above safety controls opens, that individual
refrigerant system will be locked out. The other refrigerant
system will continue in operation unless it too is effected by the
same fault. The lock out of either system can be reset by
opening the 24V circuit either at the room thermostat or at the
unit disconnect.
ELECTRIC HEATING - SEQUENCE OF OPERATION
WITH POWER TO UNIT AND THERMOSTAT IN THE
HEATING MODE
Single-stage heating: (applies only to 18 KW heater, all other
heaters MUST use a two-stage thermostat:)
a) If the fan switch is in the “ON” position, the evaporator
blower motor contactor (3M) will be energized through
terminal G to provide continuous blower operation.If the fan
switch is in the “AUTO”position, the blower will operate only
when there is a call for heating by the thermostat.
NOTE: All 240 & 480V heaters are provided with manual
reset backup protection limits. These will de-ener-
gize the heaters should the primary limit fail to open
or the contactors fail to open in a failure mode.
After the thermostat is satisfied and opens, all components will
stop simultaneously. The blower motor will continue to operate
if the fan switch on the room thermostat is set in the “ON”
position.
b) Upon a call for heat by the thermostat, the heater contactor
(6M) will be energized.
c) The thermostat will cycle the electric heat to satisfy the
heating requirements of the conditioned space.
ECONOMIZER WITH DUAL ENTHALPY SENSORS - The
operation with the dual enthalpy sensors is identical to the
single sensor except that a second enthalpy sensor is mounted
in the return air. This return air sensor allows the economizer
to choose between outdoor air and return air, whichever has
the lowest enthalpy value, to provide maximum operating
efficiency.
Two-stage heating: (applies to all heaters except 18 KW):
a) If the fan switch is in the “ON” position, the evaporator
blower motor contactor (3M) will be energized through
terminal G to provide continuous blower operation.If the fan
ECONOMIZER (SINGLE OR DUAL) WITH POWER
EXHAUST - This system operates as specified above with one
Unitary Products Group
15
530.18-N11Y
switch is in the “AUTO”position, the blower will operate only
At the same time power was supplied to the “RW1”, a parallel
circuit activates “ETD” which closes the “ETD” contact after
approximately 35 seconds and energizes “K5" which closes
”K5-2" and starts the blower by energizing “3M”.
When “TH2" closes, heat relay ”RW2" is energized. The
“RW2-1" contact is closed energizing the second stage ignition
module ”IC2". “IC2" will immediately start the second stage
ignitor sparking and will open the redundant valve located
inside the second stage main gas valve ”GV2" to allow a flow
of gas to the second stage carryover tube. Only after the pilot
flame has been ignited and the presence of pilot flame detected
at “IC2" by a signal sent back through the flame sensor is
sparking terminated and the main gas valve opened.
Gas flows into each of the second stage main burners and is
ignited from the carryover tube flame.
If “IC2" fails to detect a pilot flame, it will continue to try for a
maximum of 85 seconds to ignite the pilot tube.If the pilot flame
is not detected, then ”IC2" will lock out furnace operation for 5
minutes, then retry ignition sequence. Note that the second
stage furnace can operate even if first stage has locked out.
when there is a call for heating by the thermostat.
b) Upon a call for first-stage heat by the thermostat, the heater
contactor (6M) (6M & 7M on 72 KW, 240V) will be
energized.
If the second stage of heat is required, heater contactor
(7M) will be energized. Note that on the 54 KW, 240V
heater, heater contactors (7M & 8M) will be energized and
on the 72 KW, 240V heater, heater contactors (8M & 9M)
TABLE 9 - HEAT ANTICIPATOR SETTING
SETTING, AMPS
HEATER
KW
VOLTAGE
TH1
TH2
-
18
36
54
72
18
36
54
72
18
36
54
72
0.29
0.29
0.29
0.58
0.29
0.29
0.29
0.29
0.29
0.29
0.29
0.29
0.29
0.58
0.58
-
208/230-3-60
0.29
0.29
0.29
-
460-3-60
575-3-60
When the heating cycle is complete, “TH2" opens de-energizing
the ”RW2" then “TH1" opens de-energizing ”RW1" and “ETD”,
REDUNDANT
VALVE
MAIN VALVE
0.29
0.29
0.29
GAS MAIN
will be energized.
c) The thermostat will cycle the electric heat to satisfy the
heating requirements of the conditioned space.
GAS
VALVE
TO MAIN
BURNER
TO PILOT BURNER
FIG. 12 - GAS VALVE PIPING
HEAT ANTICIPATOR SETPOINTS
It is important that the anticipator setpoint be correct. Too high of
a setting will result in longer heat cycles and a greater temperature
swing in the conditioned space. Reducing the value below the
correct setpoint will give shorter “ON” cycles and may result in the
lowering of the temperture within the conditioned space. Refer to
the Heat Anticipator Setpoints table for the required .
thus closing all gas valves. The blower motor will continue to
run (approximately 45 seconds after the furnace is shut down)
until “ETD” opens, de-energizing the “K5" relay and ”3M"
contactor. The draft motor will continue to run for a brief
post-purge cycle.
SAFETY CONTROLS
The control circuit includes the following safety controls:
GAS HEATING SEQUENCE OF OPERATION
The following sequence describes the operation of the gas heat
section.
1. LimitControl(LS).Thiscontrolislocatedinsidetheheatexchanger
compartment and is set to open at the temperature indicated in
the Limit Control Setting Table. It resets automatically. The limit
switch operates when a high temperature condition, caused by
inadequate supply air flow occurs, thus shutting down the ignition
controland closingthe maingas valvesandenergizingtheblower.
2. Centrifugal Switch (CS). If the draft motor should fail, the
centrifugal switch attached to the shaft of the motor prevents
the ignition controls and gas valves from being energized.
3. Redundant Gas Valve. There are two separate gas valves
in the furnace.Each valve contains a main and a redundant
valve. The redundant valves are located upstream of the
main gas valves. Should either or both of the main gas
valves fail in the open position the redundant valves serve
as back-ups and shuts off the flow of gas.
4. Flame Sensor Rod / 100% Ignition Control Lock-Out. If an
ignition control fails to detect a signal from the flame sensor
indicating the pilot flame is properly ignited, then the main
gas valve will not open. It will continue to try and ignite the
pilot for a maximum of 85 seconds, then if the pilot flame is
not detected, the ignition control will lock out furnace
operation until 24V power is removed from the module
either at the unit or by resetting the room thermostat.
CONTINUOUS BLOWER
With the room thermostat switch set to “ON”, the supply air
blower will operate continuously. The normally closed contact
“K5-1" provides 24 volt power to the “3M”contactor.The “3M-1,
2 & 3" power contacts close and the blower motor operates.
INTERMITTENT BLOWER
With the room thermostat system switch set to the “AUTO”or “HEAT”
position and the fan switch set to “AUTO”, the supply air blower will
operate after the room thermostat calls for heat and the time delay
relay closes.
The “TH1" closes, the heat relay ”RW1" is energized. The “RW1-1”
power contact closes energizing the line voltage draft motor. The
“RW1-2" contact is also closed. As the speed of the draft motor
reaches approximately 2500 RPM, the centrifugal switch contact
located on the end of the draft motor shaft closes to power the first
stage ignition module “IC1”.
After a brief pre-purge time, ignition module “IC1" will start the first
stage ignitor sparking and will open the redundant valve located
inside the first stage main gas valve “GV1”to allow a flow of gas to
only the first stage carryover tube. Only after the pilot flame has
been ignited and the presence of pilot flame detected at the “IC1”
by a signal sent back through the flame sensor is sparking
terminated and the first stage main gas valve opened.
5. Rollout Switch. This switch is located above the main burn-
ers in the control compartment which in the event of a
sustained main burner rollout shuts off and locks out both
ignition controls closing both gas valves. The ignition con-
trols lock out furnace operation until 24V power is removed
from the controls either at the unit or by resetting the room
thermostat. Note the auto reset rollout switch must reset
before allowing furnace operation.
Gas flows into each of the main burners and is ignited from
the carryover tube flame.
If “IC1”fails to detect a pilot flame, it will continue to try for a maximum
of 85 seconds to ignite the pilot tube. If the pilot flame is not detected,
then “IC1" will lock out furnace operation for 5 minutes, then retry
ignition sequence.
16
Unitary Products Group
530.18-N11Y
TABLE 10 - LIMIT CONTROL SETTING
Capacity, MBH
Limit Control
Opens, °F
195
I
G
N
.
C
O
N
T
R
O
L
#
2
Input
300
Output
240
400
320
195
I
G
N
.
C
O
N
T
R
O
L
#
1
HEAT ANTICIPATOR SETPOINTS
It is important that the anticipator setpoint be correct. Too high of
a setting will result in longer heat cycles and a greater
temperature swing in the conditioned space. Reducing the value
below the correct setpoint will give shorter “ON” cycles and may
result in the lowering of the temperture within the conditioned
space.
R
O
L
L
O
U
T
S
W
.
G
V
1
S
E
N
S
O
R
#
1
G
A
S
V
A
L
V
E
G
V
2
I
G
N
I
T
O
R
#
1
Anticipator Setpoint
Gas Valve
G
A
S
V
A
L
V
E
1st Stage
0.30 amp
2nd Stage
0.11 amp
Honeywell VR8440
White-Rodgers 36C68
S
E
N
S
O
R
#
2
I
G
N
I
T
O
R
#
2
PRE-START CHECK LIST
Complete the following checks before starting the unit.
1. Check the type of gas being supplied. Be sure that it is the
same as listed on the unit nameplate.
2. Make sure that the vent and combustion air hoods have been
properly installed.
B
U
R
N
E
R
C
O
M
P
A
R
T
M
E
N
T
FIG 13-GAS VALVE AND CONTROLS
START-UP
6. Auxiliary Limit Switch (AUX) This control is located inside
the heat exchanger compartment and is set to open at
190°F. It is a manual reset switch. If AUX limit trips, then the
primary limit has not functioned correctly., Replace the
primary limit
2. Check for correct manifold gas pressures. See “Checking
Gas Input”.
3. Check the supply gas pressure. It must be within the limits
shown on rating nameplate. Supply pressure should be
checked with all gas appliances in the building at full fire.At
no time should the standby gas line pressure exceed 13",
nor the operating pressure drop below 5.0" for natural gas
units. If gas pressure is outside these limits, contact the
OPERATING INSTRUCTIONS
CAUTION: This furnace is equipped with an intermittent pilot
and automatic re-ignition system.DO NOT attempt
to manually light the pilot.
ON-OFF CONTROL
TO LIGHT PILOT AND MAIN BURNERS:
HIGH FIRE ADJ.
(UNDER SCREW)
1. Turn “off” electric power to unit.
2. Turn room thermostat to lowest setting.
3. Turn gas valve knob to “on” position.
4. Turn “on” electric power to unit.
PILOT ADJ.
(UNDER SCREW)
5. Set room thermostat to desired temperature.
(If thermostat “set”temperature is above room temperature,
pilot burner ignition will occur and, after an interval to prove
pilot flame, main burners will ignite).
FIG. 14 - TYPICAL GAS VALVE
TO SHUT DOWN:
local gas utility for corrective action.
1. Turn “off” electric power to unit.
MANIFOLD GAS PRESSURE ADJUSTMENT
Small adjustments to the high-fire gas flow may be made by
turning the pressure regulator adjusting screw onthe automatic
gas valve. Refer to figure below.
2. Depress knob of gas valve while turning to “off” position.
POST-START CHECK LIST (GAS)
After the entire control circuit has been energized and the
heating section is operating, make the following checks:
Adjust as follows:
1. Remove the cap on the regulator. It’s located next to the
1. Check for gas leaks in the unit piping as well as the supply
piping.
push-on electrical terminals.
2. To decrease the gas pressure, turn the adjusting screw
counterclockwise.
Unitary Products Group
17
530.18-N11Y
Reverse the above procedure to replace the assemblies.Make
sure that burners are level and seat at the rear of the heat
exchanger.
BURNER ASSEMBLY BRACKET
FLAME SENSOR BULB
BURNER AIR SHUTTER ADJUSTMENT
Adjust burner shutters so no yellow flame is observed in the
heat exchanger tubes.
CHECKING SUPPLY AIR CFM
TheRPMofthesupplyairblowerwilldependontherequiredCFM,
the unit accessories or options and the static resistances of both
the supply and the return air duct systems. With this information,
the RPM for the supply air blower and the motor pulley adjustment
(turns open) can be determined from the Blower Performance
Data Table.
1/8" GAP BETWEEN CARRY-OVER
TUBE AND FLAME SENSOR BULB
CARRY-OVER TUBE
FIG. 15 - PROPER FLAME ADJUSTMENT
A high speed drive accessory 1LD0435 (containing a smaller
blower pulley and shorter belts) is available for applications
requiring the supply air blower to produce higher CFM’s and/or
higher static pressures. Refer to the Blower Motor and Drive
Data Table.
3. To increase the gas pressure, turn the adjusting screw
clockwise.
NOTE: The correct manifold pressure for these furnaces is
3.65 IWG ±0.3.
PILOT CHECKOUT
Note the following:
The pilot flame should envelope the end of the flame sensor.Refer
to Proper Flame Adjustment figure. To adjust pilot flame, (1)
remove pilot adjustment cover screw, (2) increase or decrease the
clearance for air to the desired level, (3) be sure to replace cover
screw after adjustment to prevent possible gas leakage.
Put the system into operation and observe through complete
cycle to be sure all controls function properly.
BURNER INSTRUCTIONS
To check or change burners, pilot or orifices, CLOSE MAIN
MANUAL SHUT-OFF VALVE AND SHUT OFF ALL ELECTRIC
POWER TO THE UNIT.
1. Remove the screws holding either end of the manifold to
the burner supports.
2. Open the union fitting in the gas supply line just upstream
of the unit gas valve and downstream from the main manual
shut-off valve.
3. Remove the gas piping closure panel.
4. Disconnect wiring to the gas valves and spark ignitors.
Remove the manifold-burner gas valve assembly by lifting
up and pulling back.
FIG.17 - BELT ADJUSTMENT
Burners are now accessible for service.
1. The supply air CFM must be within the limitations shown in
Unit Application DataTable.
2. Pulleys can be adjusted in half turn increments.
3. The tension on the belts should be adjusted as shown in
the belt adjustment figure below.
Start the supply air blower motor.Adjust the resistances in both
the supply and the return air duct systems to balance the air
distribution throughout the conditioned space. The job
specifications may require that this balancing be done by
someone other than the equipment installer.
To check the supply air CFM after the initial balancing has been
completed:
1. Remove the two 5/16" dot plugs from the blower motor and
the filter access panels.
FIG. 16 - TYPICAL FLAME APPEARANCE
18
Unitary Products Group
530.18-N11Y
2. Insert at least 8" of 1/4 inch tubing into each of these holes
for sufficient penetration into the air flow on both sides of
the indoor coil.
NOTE:
DE-ENERGIZE THE COMPRESSORS BEFORE TAKING ANY TEST
MEASUREMENTS TO ASSURE A DRY INDOOR COIL.
ADJUSTMENT OF TEMPERATURE RISE
NOTE: The tubes must be inserted and held in a position
perpendicular to the air flow so that velocity pres-
sure will not affect the static pressure readings.
The temperature rise (or temperature difference between the
return air and the heated air from the furnace) must lie within the
range shown on the ETL rating plate.
After the temperature rise has been determined, the cfm can
be calculated as follows:
3. Using an inclined manometer, determine the pressure drop
across a dry evaporator coil. Since the moisture on an
evaporator coil may vary greatly, measuring the pressure
drop across a wet coil under field conditions would be
inaccurate. To assure a dry coil, the compressors should
be deactivated while the test is being run.
After about 20 minutes of operation, determine the furnace
temperature rise. Take readings of both the return air and the
heated air in the ducts (about six feet from the furnace) where they
will not be affected by radiant heat. Increase the blower cfm to
decrease the temperature rise; decrease the blower cfm to
increase the rise. Refer to the Blower Motor And Drive Data table.
4K.nowingthepressuredropacrossadrycoil,theactualCFM
through the unit and clean 2" filters, can be determined from
the curve in the Pressure Drop Verses Supply Air CFM
figure.
BELT DRIVE BLOWER
WARNING:Failure to properly adjust the total system air quan-
All units have belt drive single-speed blower motors. The
variable pitch pulley on the blower motor can be adjusted to
obtain the desired supply air CFM. Tighten belts enough to
prevent slipping. but do not over tighten. Belt deflection should
be between 1/4" and 1/2" per foot.Refer to the table for Blower
Motor And Drive Data.
CHECKING GAS INPUT
NATURAL GAS
1. Turn off all other gas appliances connected to the gas meter.
2. With the furnace turned on, measure the time needed for
one revolution of the hand on the smallest dial on the meter.
A typical gas meter usually has a 1/2 or a 1 cubic foot test
dial.
3. Using the number of seconds for each revolution and the
size of the test dial increment, find the cubic feet of gas
consumed per hour from the Gas RateTable.
TABLE 11 - GAS RATE - CUBIC FEET PER HOUR
Seconds
for One
Rev.
Size of Test Dial
1/2 cu. ft.
1 cu. ft.
4
6
8
450
300
228
180
900
600
450
360
10
12
14
16
18
20
150
129
113
100
90
300
257
225
200
180
FIG. 18 - PRESSURE DROP ACROSS A DRY INDOOR
COIL VS SUPPLY AIR CFM
tity can result in extensive blower damage.
22
24
26
28
82
75
69
64
164
150
138
129
After readings have been obtained, remove the tubes and
reinstall the two 5/16" dot plugs that were removed in Step 1.
Example: By actual measurement, it takes 13 seconds for the hand on the 1-cubic
foot dial to make a revolution with just a 300,000 Btuh furnace running. Read
across to the column in the table above, headed “1 Cubic Foot”, where you will see
that 278 cubic feet of gas per hour are consumed by the furnace at that rate.
Multiply 278 x 1050 (the Btu rating of the gas obtained from the local gas company).
The result is 292,425 Btuh, which is close to the 300,000 Btuh rating of the furnace.
Btuh Input x 0.8
1.08 x oF Temp. Rise
CFM =
SECURE OWNER’S APPROVAL: When the system is functioning properly, secure the owner’s approval. Show him the
location of all disconnect switches and the thermostat. Teach him how to start and stop the unit and how to adjust temperature
settings within the limitations of the system.
Unitary Products Group
19
530.18-N11Y
MAINTENANCE
If the actual input is not within 5% of the furnace rating (with
allowance being made for the permissible range of the regulator
setting), replace the orifice spuds with spuds of the proper size.
GAS HEATING UNITS
BURNER & PILOT - Periodically (at least annually at the
beginning of each heating season) make a visual check of the
pilot and main burner flame. If necessary, adjust main burner
primary air shutters to give a distinct, sharp blue flame as
explained under “BURNER AIR SHUTTER ADJUSTMENT”. If
it is not possible to adjust for the proper flame, the burners may
need cleaning.
NOTE To find the Btu input, multiply the number of cubic feet of
gas consumed per hour by the Btu content of the gas in
your particular locality (contact your gas company for this
information - it varies widely from city to city.)
NORMAL MAINTENANCE
TO CLEAN BURNERS - Remove them from the furnace as
explained in “Burner Instructions”.Clean burners with hot water
applied along top of the burner.
COMBUSTION AIR DISCHARGE - Visually inspect discharge
outlet periodically to make sure that the buildup of soot and dirt
is not excessive. If necessary, clean to maintain adequate
combustion air discharge.
CAUTION: Prior to any of the following maintenance proce-
dures, shut off all electric power to the unit to
prevent personal injury.
Periodic maintenance normally consists of changing or
cleaning filters and (under some conditions) cleaning the main
burners.
FILTERS - Inspect once a month. Replace disposable or clean
permanent type as necessary. DO NOT replace permanent
type with disposable. The dimensional size of the replacement
filter must be the same as the replaced filter.
CLEANING FLUE PASSAGES AND HEATING ELEMENTS
With proper combustion adjustment the heating element of a
gas fired furnace will seldom need cleaning. If the element
should become sooted, it can be cleaned as follows:
MOTORS
1. Remove the burner assembly as outlined in “BURNER
Outdoor fan motors are permanently lubricated and require no
maintenance.
INSTRUCTIONS”.
2. Remove the roof over the gas heat section.
3. At the top plate from the top draft blower housing and the
top draft blower wheel.
4. Remove the screws holding the top of the flue collector box.
Carefully remove the top of the flue collector box without
ripping the adjacent insulation. Then remove the center
divider plate separating the upper and lower flue boxes.
Ventor motor is factory lubricated for an estimated 10 year
life.
Indoor Blower Motor and Drive - The indoor blower motor
features ball bearings that do not require periodic lubrication.
Periodic lubrication of the motor and bearings can extend the
life of components but is optional.
CAUTION: Damage can occur if the bearings are overlubri-
cated. Use grease sparingly.
5. On the inside of the flue collector box, remove the flue
baffles from the tube interiors. Note the last bend of the
baffle fits tightly against the tube forcing the end of the baffle
to lock into the tube collar. This collar is formed when the
tube is expanded into the end sheet. To remove, move the
end of the baffle toward the center of the tube releasing the
end of the baffle from the tube collar, then pull straight out
of the tube.
6. Using a wire brush on a flexible wand, brush out the inside
of each heat exchanger from the burner inlet and flue outlet
ends.
7. Brush out the inside of the flue collector box and the flue
baffles.
WARNING:Perform all maintenance operations on the blower
motor with electric power disconnected from the
unit. Do not attempt to lubricate bearings with the
unit in operation.
On an annual basis, check the motor for accumulations of dust,
etc. that may block the cooling slots in the motor shell. Check for
loose, damaged or misaligned drive components. Check that all
mounting bolts are tight. Replace defective parts as required.
If desired, every three years remove both pipe plugs at each end
shell and clean out any hardened grease or foreign matter.
Replace one plug on each end with a clean grease fitting. Using
a low pressure grease gun, pump grease (Chevron SRI-2 or
equivalent) into the bearing cavity until new grease shows at the
open port. Do not over lubricate. Run the motor for ten minutes
until excess grease is purged from the cavity. Replace the plugs.
8. Run the wire brush down the vent hoods from the flue
collector end.
9. If soot build-up is particularly bad, remove the vent motor
and cleanthewheelandhousings.Runthewirebrushdown
the flue extentions at the outlet of the vent housings.
Units are supplied withblower shaft bearingsthatdonot require
maintenance but may be relubricated if desired. Every three
years, using a low pressure grease gun, pump grease into the
bearing grease fitting until grease just begins to show at the
seals. Do not over lubricate. Use any lithium base grease
recommended for ball bearing service.
OUTDOOR COIL - Dirt should not be allowed to accumulate
on the outdoor coil surface or other parts in the air circuit.
Cleaning should be as often as necessary to keep coil clean.
Use a brush, vacuum cleaner attachment, or other suitable
means. If water is used to clean coil, be sure electric power to
the unit is shut off prior to cleaning.
NOTE: Exercise care when cleaning the coil so that the coil
fins are not damaged.
Do not permit the hot condenser air discharge to be
obstructed by overhanging structures of shrubs.
FIG. 19 - TYPICAL FLUE BAFFLE INSTALLATION
20
Unitary Products Group
530.18-N11Y
TROUBLESHOOTING
10. After brushing is complete, blow all brushed areas with air
or nitrogen. Vacuum as needed.
11. Replace parts in the order they were removed in Steps
1 thru 4.
12. When replacing the center and top of the flue collector box,
be careful not to tear the adjoining insulation.
13. Ensure that all seams on the vent side of the combustion
system are air tight. Apply a high temperature (+500°F)
sealing compound where needed.
2. Draft motor operates and furnace lights but supply air
blower does not start after a short time delay with room
thermostat fan switch set to “AUTO”.
a. Set fan switch to “ON”. If blower motor runs, go to Step f.
If it does not, check to see if line voltage is being
supplied to the contacts of the contactor (M3), and if the
contactor is pulled in. Check for loose wiring.
b. If contactor (M3) is pulled in, proceed with the trou-
bleshooting steps indicated in Step 1 above.
WARNING:Troubleshooting of components necessarily re-
quires opening the electrical control box with the
power connected to the unit. Use extreme care
when working with live circuits! Check the unit
nameplate for the correct line voltage and set the
volt meter to the correct range before making any
connections with line terminals.
c. If (M3) is pulled in and the blower motor still does not
run, replace the blower motor.
d. If (M3) is not pulled in, check for 24 volts at the (M3) coil.
If 24 volts is present, replace the (M3) contactor.
WARNING: Prior to any of the following maintenance proce-
dures, shut off all electric power to the unit to
prevent personal injury.
e. If 24 volts is not present at the (M3) coil, check for loose
24 volt wiring back to the relay board. Check control
wiring to the room thermostat. If all is fine, replace the
relay board.
CAUTION: Label all wires prior to disconnection when servic-
ing controls. Wiring errors can cause improper and
dangerous operation. Verify proper operation after
servicing.
f. If the blower motor runs with the fan switch in the “ON”
position but does not run soon after the furnace has
ignited with the fan switch in the “AUTO” position, check
for loose 24 volt wiring between the relay board in the
main control box, the Mate-N-Lok connector in the
partition between the evaporator and gas heat sections
and the time delay relay (ETD).
NOTE: To find the Btu input, multiply the number of cubic feet of
gas consumed per hour by the Btu content of the gas in
your particular locality (contact your gas company for this
information - it varies widely from city to city.)
g. If all control wiring is fine, check for 24 volts at the relay
board. If 24 volts is present, replace the relay board. If
24 volts is not present, replace the (ETD) relay.
1. The indoor blower motor is a non-inherently protected
three-phase motor. Protection is provided by an overload
relay for overcurrent and fuses for short circuit. If the motor
fails to run, check the line voltage circuit and control voltage
circuit per the following procedure:
NOTE: The furnace may shut itself down on a high tempera-
ture condition during the procedure, but this will not
effect the test if it is done within 5 minutes of furnace
shut-down.
a. If the Indoor Blower Motor does not operate, check
visually that contactor M3 is pulled in. If so, check for
line voltage between all three phases at the line termi-
nals of the Blower Overload Relay (BOR). If line voltage
is found, check the leads to the blower motor for open
circuit. If line voltage is found at the motor leads (inside
the conduit box on the motor shell), disconnect the
motor and check for open windings per the motor wiring
diagram. If open windings are found, replace the motor.
If line voltage is not found at the BOR, trace the leads
back to the field supply terminal block, checking for an
open circuit or blown fuses.
3. The supply air blower operates but the draft motor does not
when the room thermostat is set to call for heat and the fan
switch in the “ON” position.
a. The draft motor has inherent protection. If the motor shell
is hot to the touch, wait for the internal overload to reset.
b. If the motor shell is cold with the room thermostat calling
for heat, check for line voltage at the motor’s Mate-N-
Lok connector attached to the evaporator partition. If
line voltage is present, replace the draft motor.
b. If the contactor M3 is not pulled in, check for control
voltage (24V) at the M3 coil. If voltage is found, replace
the contactor.If control voltage is not found at M3, check
for voltage across terminals 95 & 96 of the BOR. If
voltage exists, the BOR is open on overload. The BOR
should be set to the auto reset position. The BOR must
cool down in order to reset. If the BOR will not reset,
replace the BOR. If the BOR resets and M3 pulls in, but
the indoor blower motor will still not run, refer to para.
(a) for troubleshooting the line voltage supply circuit. If
control voltage is not found at the BOR, trace the circuit
back to the relay board and thermostat per the unit
wiring diagram. Replace any defective components.
c. If line voltage is not present, check for line voltage at the
heat relay (RW1) contacts in the main control box and
check to see if the (RW1) is pulled in.
d. If the (RW1) relay is pulled in, check for a loose line
voltage connection.
e. If the (RW1) relay is not pulled in, check for 24 volts at
the (RW1) coil. If 24 volts is present, replace the (RW1)
relay. If 24 volts is not present, check for a loose 24 volt
connection back to the relay board and check the con-
nections from the room thermostat to the relay board. If
all connections are correct, replace the relay board.
Cont’d.
Unitary Products Group
21
530.18-N11Y
TROUBLESHOOTING - Cont’d.
4. The draft motor runs but the furnace does not light and the
sparker does not spark.
d. If 24 volts is present, remove the pilot burner and
remove the pilot orifice from the pilot burner. The orifice
is removed in the direction opposite the flow of gas.
Inspect the orifice for obstruction. If it is clear, replace
the main gas valve.
a. The ignition control (IC1, IC2) may be locked out due to
either a flame roll out or 100% shut off. These safety
features are described above. If lock-out has occurred,
24V must be removed from the ignition controls. This is
done at the unit or by resetting the room thermostat.
After resetting 24V, check for proper furnace operation.
If lock-out continues to occur, locate the source of the
problem and correct.
6. The sparker sparks at the pilot burner but the pilot does not
ignite and a gas odor is detected at the draft motor outlet.
a. Adjust the pilot adjust screw on the gas valve as de-
scribed in “PILOT CHECKOUT”.
b. Check the supply pressure as described in “POST
b. Check all 24 volt connections from the relay board to
and in the gas heat section. Check low voltage connec-
tions to the (ETD) located in the control box.
START CHECK LIST”.Makeadjustmentsasnecessary.
c. Check the pilot orifice for obstruction as described in
para. 5d. Clean as needed but the problem should not
be the gas valve.
c. If the furnace is hot, it may be out on an over-tempera-
ture condition, wait for limit reset.
7. The pilot burner ignites but the sparker continues to spark
and the main burners do not ignite.
d. If the furnace is cold, check for 24 volts at wire 241
attached to the electronic time delay (ETD) located in
the main control box. If 24 volts is not found, replace the
ETD.
a. Make the same checks and adjustment as described in
para. 6.
e. With the draft motor running, check for 24 volts at
terminal 4 of (RW1-2) and (RW2-1). If 24 volts is not
present, the centrifugal switch (CS) has not closed or
has gone bad. Check the line voltage to the unit - if it is
correct, replace the draft motor.If line voltage is low, call
the power company.
b. Make sure that the pilot burner is not bent or damaged.
c. Make sure that the ground connections at the pilot
burner, gas valve and ignitor control are intact. Check
the high tension wire for good electrical connection. If
all are intact, replace the ignitor module.
8. The pilot burner lights and the spark stops but the main
burners do not light.
f. Check for 24V at terminal 2 of (RW1-2 and RW2-1). If
24V is not present, check for 24V at (RW1 and RW2)
relay coils. If these relays are pulled in, then check for
a loose connection at terminal 2 and terminal 4 of each
relay. If no problem is found, then replace (RW1 and/or
RW2) as required.
a. Check electrical connections between the ignitor con-
trol and the gas valve.If intact, check for 24 volts across
terminals “MV” and “COMMON” terminals. If no voltage
detected, replace ignitor control. If voltage is present,
replace gas valve.
g. If 24 volts is present at the ignitor controls, check all
control wiring at the ignitor controls and the high tension
wire to the ignitors. Check that the ground wires from
the ignitor controls, the gas valves and pilot burners are
all intact and making good electrical connection.Check
to make sure that the ceramic insulator on the pilot
ignitors or sensors is not broken or cracked, if all are
intact, replace the ignition control IC1 or IC2.
9. Furnace lights with roll-out or one burner has delayed
ignition.
a. Make sure that the pilot burner is aligned properly with
the carryover as described in “PILOT CHECKOUT”.
b. Make sure that the carryovers on adjoining burners are
screwed fast and are level with respect to one another.
5. The draft motor runs and the sparker sparks at the pilot
burner but the pilot does not ignite and a gas odor is not
detected at the draft motor outlet.
10. Main burners light but exhibit erratic flame characteristics.
a. Adjust air shutters as described in “BURNER AIR
a. Check to make sure gas is being supplied to the unit.
Make sure that the gas pressure to the unit is within the
proper limits as described in the “POST START CHECK
LIST” and that the pilot adjust screw is allowing some
flow of gas as described in “PILOT CHECKOUT”.
SHUTTER ADJUSTMENT”.
b. Check the main burner orifices for obstruction and
alignment. Removal procedure is described in
“BURNER INSTRUCTIONS”. Clean or replace burner
orifices and burners as needed.
b. Check all wiring between the ignitor control and the gas
valve. Check to make sure the ground connections are
intact.
c. If the wiring is intact, check for 24 volts across terminals
“PV” and “COMMON” on the ignitor control. If 24 volts
is not present, replace the ignitor control.
22
Unitary Products Group
530.18-N11Y
REPLACEMENT PARTS
GAS HEAT SECTION
COMPRESSOR SECTION
FABRICATED PARTS SECTION
• Hermetic compressor
• Compressor mounting
MOTOR SECTION
• Heat exchanger
• Panels
• Gas valve
• Posts
• Pilot
• Covers Drain pans
• Base rails
• Air hoods
• Flame sensor
• Spark ignitor
• Gas manifold
• Gas burner
• Blower motor
• Fan motor
MISCELLANEOUS SECTION
• Ventor motor
AIR MOVING SECTION
• Air inlet hood screen
ELECTRICAL SECTION
• Fan guard
• Blower wheel
• Air filters
• Ignition control
• Relay board
• Contactor
• Blower wheel housing
REFRIGERANT SECTION
• Circuit breaker
• Temperature controls
• Capacitors
• Evaporator coil
• Evaporator coil header
• Expansion valve assembly
• Condenser coil
• Relays
• Transformers
• Connectors
• Condenser coil header
TO OBTAIN PARTS INFORMATION: Replacement parts and information from OUR current parts list for this unit are available to
your servicing contractor through our local distributor. The name and address of our nearest distributor may be obtained by
consulting the Yellow Pages of a local telephone directory.
IMPORTANT: In order to supply the correct part or information from the parts list, our distributor will need to be provided with the
complete model number listed on the rating plate located on your unit. See page 2 for Product Nomenclature.
WARNING:IMPROPER INSTALLATION,ADJUSTMENT,SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY
DAMAGE. CONSULT A QUALIFIED INSTALLER, SERVICE AGENCY OR YOUR LOCAL GAS SUPPLIER FOR INFORMATION
OR ASSISTANCE.
Unitary Products Group
23
Unitary Products Group
5005 York Drive, Norman, Oklahoma 73069
Subject to change without notice. Printed in U.S.A.
Copyright by York International Corporation 1999. All Rights Reserved.
530.18-N11Y
Code: SBY
|