York Air Conditioner 66386 Yum C 1011 User Manual

®
CONTENTS  
USER’S, MAINTENANCE  
and  
SERVICE INFORMATION  
MANUAL  
3 THRU 12.5 TON  
SINGLE PACKAGE  
AIR CONDITIONER  
GAS/ELECTRIC  
& ELECTRIC/ELECTRIC  
The manufacturer recommends that the “User” read all sections of this manual and  
keep the manual for future reference.  
FIRE OR EXPLOSION HAZARD  
Failure to follow safety warnings exactly could  
result in serious injury, death, or property damage.  
- Do not store or use gasoline or other flammable  
vapors and liquids in the vicinity of this or any  
other appliance.  
- WHAT TO DO IF YOU SMELL GAS:  
Do not try to light any appliance.  
Do not touch any electrical switch; do not use  
any phone in your building.  
Leave the building immediately.  
Immediately call your gas supplier from a  
neighbor’s phone. Follow the gas supplier’s  
instructions.  
If you cannot reach your gas supplier, call the  
fire department.  
- Installation and service must be per formed by a  
qualified installer, service agency or the gas  
supplier.  
66386-YUM-C-1011  
66386-YUM-C-1011  
INPUT  
C. Opening and closing the unit's main disconnect switch.  
The correct heat capacity of the furnace is regulated by the  
burner orifices and the gas pressure. The proper orifices are  
furnished but the gas pressure regulator must be adjusted by  
the installer or gas utility service technician.  
M
a
i
o
n
G
a
s
S
h
i
u
t
-
f
f
V
a
l
v
e
F
e
l
d
I
n
s
t
a
l
l
e
d
(
M
o
u
n
t
e
d
E
x
t
e
r
n
a
l
l
y
)
OPERATING INSTRUCTIONS  
TO SHUT DOWN THE FURNACE:  
1. Close the main gas shutoff valve(s).  
2. Turn off the electric power supply.  
TO LIGHT THE FURNACE:  
1. Do not attempt to light manually.  
2. Open the main gas shutoff valve(s).  
3. Adjust the set point of the room thermostat above the  
temperature in the space.  
4. Turn on the electric power supply.  
FIGURE 2- TYPICAL INSTALLATION  
5. The draft fan will operate. After an adequate purge time,  
the electric spark igniter will light the burners.  
If the furnace continues to lock out, a qualified service techni-  
cian should be called to determine the cause of the problem.  
6. The burners will extinguish and relight automatically  
upon the demand of the room thermostat.  
VENT SAFETY SYSTEM:  
This gas furnace is equipped with a manual reset high tem-  
perature sensor or rollout switch which in the unlikely event of  
a sustained main burner flame rollout will shut off the flow of  
gas by closing the main gas valve. The ignition modules will  
also be disabled, preventing the flow of gas to the valve. The  
switch is located inside the gas heat access panel above the  
burner inlet. Flame rollout can be caused by blockage of the  
power vent system, improper gas pressure or adjustment. If  
this event occurs the furnace will not operate properly. The  
gas supply to the furnace should be shut off and no attempt  
should be made to place the furnace in operation. The sys-  
tem should be inspected by a qualified service technician.  
Refer to Figure 2 for a typical installation.  
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD  
Failure to follow safety warnings exactly could result  
in dangerous operation, serious injury, death or prop-  
erty damage.  
Improper servicing could result in dangerous opera-  
tion, serious injury, death or property damage.  
Before servicing, disconnect all electrical power  
to furnace.  
When servicing controls, label all wires prior to  
disconnecting. Reconnect wires correctly.  
Verify proper operation after servicing.  
100% SHUT OFF:  
The ignition modules are designed for 100% shut-off. If the  
furnace fails to ignite after three ignition attempts, the flow of  
gas will be shut off and the ignition module will lock out. The  
module can be reset by:  
Prior to any of the following maintenance procedures,  
shut off all power to the unit to avoid personal injury.  
A. Turning the system switch on the room thermostat to the  
“OFF” position and back to the “HEAT” position.  
B. Decreasing the set point of the room thermostat below  
the temperature in the conditioned space and returning it  
to its original setting.  
Johnson Controls Unitary Products  
3
 
66386-YUM-C-1011  
EXPLAIN UNIT FUNCTION  
When the system is functioning properly, show the owner the  
location of all disconnect switches and the thermostat.  
Explain how to start and stop the unit and how to adjust tem-  
perature settings within the limitations of the system. Advise  
that the flue exhaust hood surface and the immediate area  
will experience high temperatures during the heating cycle,  
and that all unauthorized personnel and debris must be kept  
away from this area.  
H
E
A
T
E
X
C
H
A
N
G
E
R
T
U
B
E
G
S
P
A
S
U
I
P
P
L
Y
B
U
R
N
E
R
F
L
A
M
E
B
U
R
N
E
R
P
E
(
B
L
U
E
O
N
L
Y
)
B
U
R
N
E
R
B
R
A
C
K
E
T
I
G
N
I
T
O
R
GENERAL MAINTENANCE  
FIGURE 3- TYPICAL FLAME  
BURNER CHECK  
In order to insure long and trouble free service from your sys-  
tem, we recommend periodic inspection, cleaning, lubrication  
and adjustment by your installing Dealer/Contractor. Be sure  
to ask about this service. For those who prefer to do-it-your-  
self, please follow the instructions listed below to care for  
your system.  
Periodically (at least annually at the beginning of each heat-  
ing season) make a visual check of the main burner flame to  
determine if the burners need cleaning.  
CLEANING BURNERS  
Snow or debris should not be allowed to accumulate in or  
around the unit. Do not permit overhanging structures or  
shrubs to obstruct outdoor air discharge, combustion air  
inlets or vent outlets on your unit. These provide air for com-  
bustion and ventilation. Adequate air is important to the safe  
and proper operation of the unit.  
Remove them from the furnace as explained the in BURNER/  
ORIFICE INSTRUCTIONS section in the Unit Installation  
Instructions. Clean burners with wire brush and vacuum as  
needed.  
CLEANING FLUE PASSAGES & HEATING ELEMENTS  
With proper combustion adjustment, the heat exchanger  
tubes of a gas-fired furnace will seldom need cleaning. If the  
tubes should become sooted, they can be cleaned as follows:  
HEATING SYSTEM INSPECTION  
It is the owner's responsibility to insure that an annual inspec-  
tion of the entire heating portion of the unit is made by a qual-  
ified service technician. This should include inspection of the  
burner, heating element and flue for any corrosion or soot  
accumulation which may require cleaning and also checking  
of burner and controls for proper operation.  
1. Remove the burner assembly as outlined in “BURNER/  
ORIFICES INSTRUCTIONS” of the unit Installation  
Instructions.  
2. Remove the screws holding the flue collector box. Care-  
fully remove the flue collector box.  
In addition, at least once during the heating season, the  
owner shall make a visual inspection of the flue outlet for evi-  
dence of black soot or blockage of flue outlet by leaves or  
other debris. If any soot is found, it is recommended a quali-  
fied service technician be called immediately. If any blockage  
is found, it must be cleared immediately.  
3. Remove the flue baffles from the tube interiors.  
4. Using a wire brush on a flexible wand, brush out the  
inside of each heat exchanger from the burner inlet and  
flue outlet ends.  
5. Brush out the inside of the flue collector box and the flue  
baffles.  
Check for obvious signs of deterioration of the unit. Check  
that the return and supply ducts attached to the unit are  
sound and air tight. Check that the unit's physical support,  
concrete slab or roof curb, is sound and not in need of repair.  
Make sure there are no gaps between the roof curb and the  
unit where rain could leak into the building.  
6. Run the wire brush into the flue exhaust tube from the  
flue collector end. Do not damage the flue exhaust  
screen, remove if necessary.  
7. If soot build-up is particularly bad, remove the draft motor  
and clean the wheel and housing.  
Start the furnace. The vent motor should start, the igniter will  
start to spark and ignite the burner. If it does not, contact a  
qualified service technician for assistance. Check the appear-  
ance of the main burner flame. The flame should have a blue  
appearance. (See Figure 3.)  
8. After brushing is complete, blow away all brushed areas  
with air or nitrogen. Vacuum as needed.  
9. Replace parts in the reverse order that they were  
removed in Steps 1 through 3.  
10. Assure that all seams on the vent side of the combustion  
system are airtight. Apply a high temperature (500°F+)  
sealing compound where needed.  
4
Johnson Controls Unitary Products  
     
66386-YUM-C-1011  
NOTE: Filters must be installed with “Air Flow” arrows point-  
ing inward -- toward the indoor coil. In the event the  
spacers in the filter section are removed, they must  
be reinstalled in their original position.  
AIR FILTERS  
All units contain four filters. The filter racks on these units will  
receive either 1" or 2" filters. Filters can also be installed in  
the building at a suitable return air location if an economizer  
or outside air accessory is not used. Filters must always be  
used. They should be inspected once a month and thor-  
oughly cleaned or replaced if it appears they are beginning to  
accumulate excessive dirt.  
Slide filters all the way into the filter racks provided. When  
more than one filter in a filter rack is required, they must butt  
each other when sliding into position. Replace the filter  
access panel.  
To install the filters, remove the filter access panel as shown  
in Figure 4.  
F
I
L
T
E
R
S
I
N
D
O
O
R
C
O
I
L
F
I
L
T
E
R
A
L
C
C
E
S
S
P
U
L
S
FIGURE 4- FILTER ACCESS  
BLOWER ASSEMBLY  
Even with good filters properly in place, blower wheels and  
motors will become dust laden after many months of opera-  
tion. The entire blower assembly should be inspected annu-  
ally. If the motor and wheel are heavily coated with dust, they  
can be brushed and cleaned with a vacuum cleaner.  
Perform all maintenance operations on the blower motor  
with electric power disconnected from the unit. Do not  
attempt to lubricate bearings with the unit in operation.  
These units are supplied with blower shaft bearings that do  
not require maintenance but may be lubricated  
MOTORS  
if desired. Every three years, using a low pressure grease  
gun, pump grease into the bearing grease fitting until grease  
just begins to show at the seals. Do not over lubricate. Use  
any lithium base grease recommended for ball bearing ser-  
vice.  
Outdoor fan motors are permanently lubricated and require  
no maintenance.  
Ventor motor is factory lubricated for an estimated 10 year  
life.  
Johnson Controls Unitary Products  
5
     
Indoor Blower Motor and Drive - The indoor blower motor fea-  
tures ball bearings that do not require periodic lubrication.  
However, if the motor has grease  
fittings, periodic lubrication of the motor bearings can extend  
the life of components but is optional.  
Damage can occur if the bearings are overlubricated. Use  
grease sparingly.  
If desired, every three years, using a low pressure grease  
gun, pump grease into the bearing grease fitting until grease  
just begins to show at the seals. Do not over lubricate. Use  
any lithium base grease recommended for ball bearing ser-  
vice.  
REGISTERS  
Supply and return air registers must be open when the unit is  
in operation. Obstructions must not be allowed to block air-  
flow in or out of the registers.  
CONDENSER COIL  
TROUBLESHOOTING  
An annual check and cleaning, if necessary, of the outdoor  
coil should be done. Cleaning should be as often as neces-  
sary to keep the coil clean. Clean any debris and dirt from the  
outside coil face with a brush being careful not to damage the  
fins. If extremely dirty, a hose can be used to wash the coil  
from the inside out while brushing a soapy solution on the  
outside.  
BEFORE CALLING A SERVICE TECHNICIAN:  
A. Check thermostat setting and insure thermostat is calling  
for heat or cooling.  
B. Check thermostat for lint, etc.  
C. Check fuses or circuit breakers.  
D. Check filters for excessive dust accumulation.  
OWNER please have your installer fill in the following information immediately after unit has been installed  
and is properly operating.  
Installed by __________________________________________________________________________________  
Installer’s Address ____________________________________________________________________________  
Installation Date ______________________________________________________________________________  
Owner’s Name _______________________________________________________________________________  
Owner’s Address _____________________________________________________________________________  
Equipment installed at (address) _________________________________________________________________  
Model Number ____________________________________ Serial Number _____________________________  
Distributor from whom the equipment was purchased _________________________________________________  
The owner should keep this information in a place where it can be found if needed for warranty purposes.  
Subject to change without notice. Printed in U.S.A.  
66386-YUM-C-1011  
Supersedes: 366386-YUM-B-0711  
Copyright © 2011 by Johnson Controls, Inc. All rights reserved.  
Johnson Controls Unitary Products  
5005 York Drive  
Norman, OK 73069  
       

Lexmark X864dhe User Manual
Mitsubishi Electronics Msz Fa35va User Manual
Olivetti D Copia 500mf User Manual
Samsung As09a5 A6 Ma User Manual
Schumacher Se 1010 2 Se 1012d Se 1052 Se 1250 User Manual
Toshiba Carrier Rav Sp240ut Ul User Manual
Toshiba Ras 10sa E User Manual
Trane Air Conditioner Gaf2a0a36s31sa User Manual
Whynter Air Conditioner Arc 143mx User Manual
Xerox 470 Dc User Manual