Trion Air Cleaner 600m User Manual

Air Boss MP 600M  
Vertical Air Flow Mist Precipitator  
Installation  
Operation  
Service  
Please read these instructions carefully for  
trouble free operation and to get the most out of  
your purchase.  
For further information  
concerning this project, contact your local Trion  
representative.  
101 McNeill Road Sanford, NC 27330  
Phone: 800-884-0002 Fax: 800-458-2379 Email: [email protected]  
Manual Part No. 153632-001 June 2002  
Figure 1 - MP 600M High Static  
SPECIFICATIONS  
STANDARD  
OPTIONAL MP600M and High Static  
MP 600M  
Voltage  
Phase  
115  
1
208-230  
1
208-230/460 575  
115/230  
1
3
3
HZ  
60  
60  
60  
60  
1.9  
60  
AMPS  
17  
9.4-8.5  
1 ½ hp  
600  
4.9-4.6/2.3  
1 ½ hp  
600  
8.0-4.0  
Motor  
½ hp  
600  
175 lbs  
1 ½ hp ½ hp  
600 600  
225 lbs. 225 lbs.  
CFM  
Shipping Weight  
225 lbs.  
225 lbs.  
3
Figure 2 – Dimension and Access Data  
GENERAL SAFETY INFORMATION  
INSTALLATION  
Prior to beginning installation, select the location for the  
air cleaner. The air cleaner should be located as close to  
the contaminant source as possible. The air enters the  
air cleaner from the bottom (or specified side with inlet  
plenum as viewed from the access door side) and  
discharges vertically through the grille in the cabinet top  
panel. Do not obstruct the air flow from the unit. Maintain  
at least 18 inches (45 cm) clearance above the unit.  
WARNING: RISK OF ELECTRIC SHOCK  
These serving instructions are for use by qualified  
personnel only, To reduce the risk of electric shock, do  
not perform any servicing other than that contained in  
the operating instructions unless you are qualified to do  
so.  
1. Read this manual thoroughly before beginning  
the installation of this unit.  
MOUNTING  
2. Conference to all local ordinances associated  
with building codes and electrical codes is  
required prior to beginning installation of this  
unit. Authorities having jurisdiction should be  
consulted before installation is made. If there are  
no local codes, the installation should conform to  
the National Electrical Code.  
WALL OR VERTICAL SUPPORT MOUNTED  
1. Four (4) tapped holes are provided in the  
cabinet back. Bars may be mounted to the  
cabinet with existing hard ware. The MP600M  
can then be mounted to the wall or vertical  
support stand (not provided) with 3/8” hardware  
(not provided).  
2. The inlet plenum is equipped with a ½” half  
coupling to connect drain piping. Plumbing  
should be routed to the collection point to  
facilitate drainage.  
CAUTION:  
The weight of the air cleaner is 150 lbs. Any mounting  
arrangement must be able to support this weight. Failure  
to determine if mounting is sufficient may result in  
damage or injury within the area.  
3. Affix duct(s) or elbow fitting(s) or flex hose(s) to  
the inlet plenum flange collar using hose clamps  
or other similar connection method. (Clamps,  
elbows and/or duct are not provided).  
4
CAUTION:  
TRAPEZE MOUNT  
When using flex duct connections with other than  
straight runs of duct, 45 degree elbows should be used  
to connect ducting to flanged collars to maximize air  
flow.  
1. Four (4) through holes are provided in the inlet  
plenum bottom flange to which two (2) mounting  
channels are affixed with 3/8” hardware (not  
provided).  
2. The MP600M can be suspended from overhead  
with chains or 3/8” diameter (minimum) rods (not  
provided).  
3. The inlet plenum is equipped with a ½” half  
coupler to connect drain piping. Plumbing should  
be routed to the collection point to facilitate  
drainage (P – trap not Required).  
4. Affix duct(s) or elbow fitting(s) or flex hose(s) to  
the inlet plenum flange collar using hose clamps  
or other similar connection method (not  
provided).  
ENCLOSED MACHINING CENTER DIRECT MOUNT  
1. When mounting directly to an enclosed  
machining center ensure there is 53” (135 cm)  
clearance above the enclosure and structure  
integrity is sufficient to support the MP 600M.  
2. Open the filter access door and remove all the  
filtering elements. Set these components aside  
until the installation is complete.  
3. Prepare an outlet opening on the top of he  
enclosed machining center (8” minimum to 20”  
maximum diameter opening).  
4. Center the MP600M over opening and secure to  
the enclosure with self-drilling/self-tapping  
screws or other similar method in accordance  
with local codes. No additional duct connections  
or drain plumbing is required on this type of  
installation.  
MINI-HELIC GAUGE (Optional Mounting)  
1. Gauge may be mounted directly on MP600M  
unit or may be remotely mounted for improved  
visibility.  
2. Gauge may be connected to measure entire  
system static pressure or only pressure drop  
across filter section.  
ARM ASSEMBLY (OPTIONAL) MOUNTING  
3. All hardware, components and detailed  
installation instructions are included in gauge kit  
option.  
Mount the arm assembly(s) to the arm connection collar  
on the inlet plenum in accordance with the mounting  
instructions provided in the arm assembly kit.  
Figure 3 - MP 600M Wall Mounted with 8” Arm Assembly and Drain Pipe  
5
Figure 4 - MP 600M Inlet Plenum and Stand Options  
6
Figure 5 – Wiring Diagrams for Model MP 600M  
7
Figure 6 – Wiring Diagram  
8
Figure 6A – Motor Wiring Diagram  
9
The MP600M is wired directly from the power source  
with 20 amps minimum, service utilizing 3 wire grounded  
cable, (115-208-230-460-575/60/3) for single 208-  
230/60/1, phase service and 4 wire grounded cable for 3  
phase service, routed through appropriate conduit (See  
figure 5 wiring diagram). All wiring must be connected in  
accordance with local electrical codes.  
the pressure reading when the pre-filter is replaced. At  
that point, the unit would be allowed to run until 3.1” w.c.  
and both filters replaced.  
NOTE:  
The unit can continue to run beyond the 3.1” w.c.  
pressure reading; however, airflow will be reduced  
further.  
The conduit is connected to the cabinet junction box, or  
motor starter enclosure on the top-right front corner of  
unit.  
CAUTION:  
To check internal components, disconnect power source  
to unit to prevent accidental shock.  
OPERATION  
To start the air cleaner, close the access door and  
activate the ON-OFF control switch to ON. The blower  
motor should start.  
MAINTENANCE  
Precision equipment will require a minimum amount of  
maintenance to keep it in operating condition. You can  
perform all normal preventative maintenance. If you are  
unfamiliar with the terminology used in the in the  
following sections, refer to the Parts List (Figure 7-A).  
Blower Rotation (3 phase power only)  
By looking down through the MP600M discharge grille  
confirm blower rotation agrees with rotation label on  
motor mount. If rotation is incorrect reverse two (2) input  
power leads connections in the junction box, switch box  
or motor starter enclosure. Again verify correct blower  
rotation.  
CLEANING AND INSPECTION  
FILTER CHANGE (MINI-HELIC GAUGE)  
INDICATOR (OPTIONAL) OPERATION  
Cleaning of Impinger, and inspection and replacement of  
pre-filter and main filter.  
Change filter according to the pressure drop across the  
filter. A minihelic gauge with a range from 0-5” water  
column is optional for reading filter pressure.  
CAUTION:  
Always disconnect the power source before working on  
or near any electrical component. If the disconnect point  
is out of sight, lock it in the proper position and tag to  
prevent unexpected application of power.  
Estimated Filter Change Pressure  
Main Filter Both Filters  
Change Pre-filter  
Estimated  
Recommended Final  
Estimated  
1. Turn unit off.  
2. Open access door by turning door latches  
counter clockwise.  
95%  
1.8”w.c.  
1.8”w.c.  
3.1”w.c.  
3.1”w.c.  
HEPA  
3. Remove filter element, pre-filter and impinger  
assembly or pre-filter support.  
NOTE:  
4. Clean impinger by first rinsing with warm to hot  
water, then immerse in a commercial grade  
detergent. Trion recommends our specially  
formulated Tridex detergent to provide maximum  
cleaning efficiency on air cleaning equipment.  
For best results, the cleaning solution should be  
140ºF to 160ºF. The impinger should be soaked  
in the solution for 1½ to 2 hours (longer if  
extremely dirty).  
These readings will vary slightly due to altitude and  
temperature.  
Upon installation of the unit, note the initial pressure  
reading and record in the table above. Check daily and  
replace pre-filter at the reading shown in the table.  
Pressure should return to near the initial pressure  
reading. When the pressure reading, with new pre-filter,  
shows little improvement (less than 0.1”) allow unit to run  
until recommended final pressure is reached. At that  
point, both pre-filter and main filter should be replaced.  
Impinger models will have greater pressure initially than  
standard models.  
NOTE:  
Using non-factory approved detergents can cause  
damage to the metal surface.  
Once a pattern is established, the pre-filters can be  
replaced on a calendar basis with the main filter being  
replaced when the gauge reads “Recommended Final”  
in the Table. For example, if the unit takes 6 weeks to go  
from initial reading to 1.8” w.c., the pre-filter would then  
be replaced every 6 weeks until no change occurred in  
5. While impinger is soaking, make the following  
inspections:  
10  
A. Thoroughly inspect the main and pre-  
filter for holes, tears or any other  
condition that might allow air to leak  
through or around the filter. Replace the  
filters if any damage is found.  
F. Check rubber gasketing and adhesion of  
gasketing to cabinet surfaces.  
6. When soaking of impinger is complete, rinse  
with clean water and allow to dry.  
B. Inspect the cabinet. Remove all foreign  
debris and dirt accumulation inside the  
cabinet.  
7. Reinstall impinger and filters into the unit.  
8. Switch unit on at the control switch. The blower  
should start.  
C. Check for dirt accumulation on the  
blower wheel blades and clean if there  
is a buildup.  
D. Bearings of blower motor should be  
checked for signs of unusual wear.  
E. If liquids are being collected, check the  
drain fittings for proper drainage.  
9. If the air flow is now adequate to draw the  
contaminant being collected off the process, it  
will not be necessary to replace the main filter.  
If, however, the air flow remains unsatisfactory,  
replace the main and pre-filter.  
TROUBLESHOOTING CHART  
POSSIBLE CAUSES  
SYMPTOM  
CORRECTIVE ACTION  
1. Proper power not reaching unit  
2. Loose electrical connections  
3. Defective control switch  
4. Defective Motor  
1. Check that unit is connected to live  
power line with good fuses, and  
that the voltage at the unit is  
correct  
2. Check; tighten if necessary  
3. Replace control switch  
Failure to start  
(motor does not start when unit is  
turned on  
4. Replace motor/ blower assembly  
1. Dirty or dogged filters  
2. Discharge grille obstructed  
3. Blower wheel blades loaded with  
dirt  
4. Blower wheel loose on motor shaft  
5. Incorrect voltage  
1. Replace filters  
2. Clean or remove obstruction  
3. Clean blower wheel blades  
4. Tighten blower wheel on shaft  
5. Supply correct line voltage  
6. Clean impinger  
Motor / Blower operates with little or  
no air volume  
6. Dirty or dogged impinger  
7. Motor rotation incorrect  
7. Reverse 2 of the 3 input power  
leads (3 Phase only)  
1. Filter ruptured or torn  
2. Gasket missing or damaged  
3. Filter saturated or damaged  
1. Replace filter  
2. Install or repair  
3. Replace filter  
Blow Through / Bypass  
11  
Figure 7 – MP 600M Unit Assembly  
12  
Figure 7A – Unit Assembly Parts List  
MP 600M  
MP 600M HS  
Qty  
Qty  
1
1
1
2
2
2
6’  
-
-
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Item Part No.  
Description  
Remarks  
1
1
1
2
2
2
6’  
1
1
-
-
-
-
-
-
-
-
-
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
-
1
353613-001  
354477-001  
253619-001  
248956-002  
321449-002  
146442-002  
224779-015  
247350-101  
253631-001  
150825-001  
150825-003  
150825-004  
150825-005  
150825-006  
250819-007  
250837-102  
253617-001  
253621-001  
353622-001  
353622-002  
353622-003  
353622-004  
353622-005  
353622-006  
354988-001  
246901-011  
248533-001  
148534-001  
224451-022  
248535-008  
248535-007  
248535-006  
248535-005  
248535-004  
248535-003  
248535-002  
248535-001  
248535-009  
253625-002  
253625-003  
253625-004  
355032-006  
355032-007  
355032-008  
355032-009  
355032-010  
355032-011  
355032-012  
355032-013  
253625-002  
253625-003  
253625-001  
253763-001  
253763-002  
253763-003  
253763-004  
354970-001  
253761-001  
60000-0003-01-00  
238001-002  
238001-003  
254643-001  
145541-003  
Cabinet Assembly  
2
3
5
6
7
8
9
10  
11A  
11B  
11C  
11D  
11E  
12  
13  
14  
15  
16A  
16B  
16C  
16D  
16E  
16F  
16G  
17A  
17B  
18A  
18B  
19A  
19B  
19C  
19D  
19E  
19F  
19G  
19H  
19J  
20A  
20B  
20C  
20D  
20E  
20F  
20G  
20H  
20I  
Access Door  
Blower Housing Cover  
Clamping Knob  
Nut Retainer  
Hinge  
Gasket ¼” x 1”  
Blower Motor Assembly 120/240/50-60/1  
Adapter Plate  
Motor 115/208/-230/60/1  
Motor 208-230/460/60/3  
Motor 575/60/3  
Motor 110/220/50/1  
Motor 220/380-440/50/3  
Inlet Cone  
Blower Wheel  
Motor Mount  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Feature & Option  
Not Shown  
Motor Adjusting Angle  
Plenum 1 – 8” Hose  
Plenum 2 – 6” Hose @ 90º  
Plenum 2 – 6” Hose @ 180º  
Plenum 2 – 6” Hose @ 0º  
Plenum 1 – 8” Arm @ Bottom  
Plenum 1 – 8” Hose @ Bottom  
Plenum 1 – 8” Arm @ Side  
Impinger  
Pre-Filter Support  
Synthetic Filter - 22¼ x 22¼ x 2  
Aluminum Mesh  
Filter 55%, 30 SF – Special Order  
Filter 65%, 30 SF – Special Order  
Filter 85%, 30 SF – Special Order  
Filter 95%, 30 SF – Special Order  
Filter 65%, 54 SF – Special Order  
Filter 85%, 54 SF – Special Order  
Filter 95%, 70 SF – Stock  
Filter 99.97% DOP, 90 SF – Stock  
Filter 95% DOP – Stock  
Switch Box Assembly 1Ø  
Switch Box Assembly 1Ø w/ Cord  
Switch Box Assembly 3Ø  
Compact Starter 110-120/50-60/1  
Compact Starter 220-240/50-60/1  
Compact Starter 208/60/1  
Compact Starter 208/60/3  
Compact Starter 220-230/50-60/3  
Compact Starter 380/50/3  
Compact Starter 440-460/50-60/3  
Compact Starter 575/60/3  
Switch Box Assembly 1Ø  
Switch Box Assembly 1Ø w/ Cord  
Junction Box Assembly  
Gauge Kit System  
-
-
-
-
-
-
-
-
-
-
20J  
20K  
21A  
21B  
22  
23A  
23B  
23C  
23D  
24A  
25  
1
1
REF  
1
1
1
1
1
1
1
REF  
REF  
1
-
-
-
REF  
1
1
1
1
1
1
1
Gauge Kit Filter  
Gauge Kit System – Remote  
Gauge Kit Filter – Remote  
Arm Assembly 8” x 10”  
Mounting Bar  
Swivel Caster  
Toggle Switch 1Ø  
Toggle Switch 3Ø  
Stand  
Vibration Isolator  
26  
REF  
REF  
1
27A  
27B  
28  
4
29  
13  
Figure 8 – Filter Locking Mechanism  
-
-
-
Access opening increased 3.5” height  
16 GA tapered filter retainer welded in door and cabinet rear  
As door closes, filter gasket is compressed and seal is made  
14  
Figure 9 – System Performance Curves (without Filters)  
Flow – CFM @ 60 Hz  
Added Static @ Filter  
600 CFM  
Inches W.C.  
1.00  
1000 m3/hr  
Pascals  
250  
87  
Filter  
99.97% DOP HEPA  
95% DOP  
0.35  
90-95% ASHRAE  
80-85% ASHRAE  
60-65% ASHRAE  
45-55% ASHRAE  
Impinger  
0.20  
0.15  
0.10  
0.05  
50  
37  
25  
13  
0.15  
37  
Aluminum Mesh Pre-Filter  
Glass Pre-Filter  
0.05  
0.00  
13  
1
** To determine performance with various filter combinations, add total static of filters (from table)  
15  
WARRANTY  
All Trion air cleaners are warranted for component failure and workmanship for a  
period of three years after purchase. Do not return defective parts without prior  
permission from the factory. Contact your local Trion Distributor or Trion Customer  
Service Department at 1-800-884-002 of Fax 1-800-458-2379 to obtain  
material return authorizations and service information.  
Corporate Office: 101 McNeill Road Sanford, NC 27330  
Form No. 153632-001  
June 2002  
Phone: 800-884-0002 Fax: 800-458-2379 Email: [email protected]  

Murphy Voltmeter Vm 24 User Manual
Oricom Secure 50 User Manual
Panasonic Cu E21jkr User Manual
Samsung Avmkh020ca0 User Manual
Sanyo C2432 User Manual
Savin 9027l User Manual
Sharp Al 1456 User Manual
Sterling Power Products 1230ced User Manual
Sterling Power Products Ab24100 User Manual
Studer Innotec Xpc 2200 48 User Manual