Toshiba Ras 16gavp E User Manual

FILE NO. A05-008  
SERVICE MANUAL  
SPLIT TYPE  
Indoor Unit  
Outdoor Unit  
<High Wall, Heat Pump Type>  
<Heat Pump Type>  
RAS-B10GKVP-E RAS-10GAVP-E  
RAS-B13GKVP-E RAS-13GAVP-E  
RAS-B16GKVP-E RAS-16GAVP-E  
R410A  
PRINTED IN JAPAN, Nov.,2005 ToMo  
1. SAFETY PRECAUTIONS  
For general public use  
Power supply cord of outdoor unit shall be more than 1.5 mm 2 (H07RN-F or 245IEC66) polychloroprene  
sheathed flexible cord.  
Read this SAFETY PRECAUTIONScarefully before servicing.  
The precautions described below include the important items regarding safety. Observe them without fail.  
After the servicing work, perform a trial operation to check for any problem.  
Turn off the main power supply switch (or breaker) before the unit maintenance.  
CAUTION  
New Refrigerant Air Conditioner Installation  
• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT  
DESTROY OZONE LAYER.  
R410A refrigerant is apt to be affected by impurities such as water, oxidizing membrane, and oils because  
the working pressure of R410A refrigerant is approx. 1.6 times of refrigerant R22. Accompanied with the  
adoption of the new refrigerant, the refrigeration machine oil has also been changed.Therefore, during  
installation work, be sure that water, dust, former refrigerant, or refrigeration machine oil does not enter into  
the new type refrigerant R410A air conditioner circuit.  
To prevent mixing of refrigerant or refrigerating machine oil, the sizes of connecting sections of charging  
port on main unit and installation tools are different from those used for the conventional refrigerant units.  
Accordingly, special tools are required for the new refrigerant (R410A) units. For connecting pipes, use new  
and clean piping materials with high pressure fittings made for R410A only, so that water and/or dust does  
not enter. Moreover, do not use the existing piping because there are some problems with pressure fittings  
and possible impurities in existing piping.  
CAUTION  
TO DISCONNECT THE APPLIANCE FROM THE MAIN POWER SUPPLY  
This appliance must be connected to the main power supply by a circuit breaker or a switch with a contact  
separation of at least 3 mm.  
The installation fuse (25A D type  
) must be used for the power supply line of this air conditioner.  
DANGER  
• ASK AN AUTHORIZED DEALER OR QUALIFIED INSTALLATION PROFESSIONAL TO IN-  
STALL/MAINTAIN THE AIR CONDITIONER.  
INAPPROPRIATE SERVICING MAY RESULT IN WATER LEAKAGE, ELECTRIC SHOCK OR FIRE.  
TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE  
ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.  
DANGER: HIGH VOLTAGE  
The high voltage circuit is incorporated.  
Be careful to do the check service, as the electric shock may be caused in case of touching parts  
on the P.C. board by hand.  
CORRECTLY CONNECT THE CONNECTING CABLE. IF THE CONNECTING CABLE IS INCOR-  
RECTLY CONNECTED, ELECTRIC PARTS MAY BE DAMAGED.  
CHECK THAT THE EARTH WIRE IS NOT BROKEN OR DISCONNECTED BEFORE SERVICE AND  
INSTALLATION. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.  
3 –  
DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS. FAILURE  
TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.  
TO PREVENT THE INDOOR UNIT FROM OVERHEATING AND CAUSING A FIRE HAZARD, PLACE  
THE UNIT WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEAT  
REGISTORS, FURNACE, STOVES, ETC.  
WHEN MOVING THE AIR-CONDITIONER FOR INSTALLATION IN ANOTHER PLACE, BE VERY CARE-  
FUL NOT TO ALLOW THE SPECIFIED REFRIGERANT (R410A) TO BECOME MIXED WITH ANY  
OTHER GASEOUS BODY INTO THE REFRIGERATION CIRCUIT. IF AIR OR ANY OTHER GAS IS  
MIXED IN THE REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CIRCUIT WILL  
BECOME ABNORMALLY HIGH AND IT MAY RESULT IN THE PIPE BURSTING AND POSSIBLE PER-  
SONNEL INJURIES.  
IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE SERVICE  
WORK AND THE INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE  
REFRIGERANT GAS IS HEATED, SUCH AS BY FIRE, GENERATION OF POISONOUS GAS MAY  
RESULT.  
WARNING  
• Never modify this unit by removing any of the safety guards or bypass any of the safety interlock  
switches.  
• Do not install in a place which cannot bear the weight of the unit. Personal injury and property  
damage can result if the unit falls.  
• After the installation work, confirm that refrigerant gas does not leak.  
If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas  
may generate.  
• The electrical work must be performed by a qualified electrician in accordance with the Installation  
Manual. Make sure the air conditioner uses an exclusive circuit.  
An insufficient circuit capacity or inappropriate installation may cause fire.  
• When wiring, use the specified cables and connect the terminals securely to prevent external  
forces applied to the cable from affecting the terminals.  
• Be sure to provide grounding.  
Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone cables.  
• Conform to the regulations of the local electric company when wiring the power supply.  
Inappropriate grounding may cause electric shock.  
CAUTION  
Exposure of unit to water or other moisture before installation may result in an electrical short.  
Do not store in a wet basement or expose to rain or water.  
Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify  
the noise level of the unit or where noise or discharged air might disturb neighbors.  
To avoid personal injury, be careful when handling parts with sharp edges.  
• Perform the specified installation work to guard against an earthquake.  
If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.  
For Reference:  
If a heating operation would be continuously performed for a long time under the condition that the outdoor  
temperature is 0°C or lower, drainage of defrosted water may be difficult due to freezing of the bottom plate,  
resulting in a trouble of the cabinet or fan.  
It is recommended to procure an antifreeze heater locally for a safe installation of the air conditioner.  
For details, contact the dealer.  
4 –  
2. SPECIFICATIONS  
2-1. Specifications  
RAS-B10GKVP-E/RAS-B13GKVP-E/RAS-B16GKVP-E, RAS-10GAVP-E/RAS-13GAVP-E/RAS-16GAVP-E  
Indoor  
Outdoor  
RAS-B10GKVP-E  
RAS-10GAVP-E  
2.5  
RAS-B13GKVP-E  
RAS-13GAVP-E  
3.5  
RAS-B16GKVP-E  
RAS-16GAVP-E  
4.5  
Unit model  
Cooling capacity  
(kW)  
(kW)  
(kW)  
(kW)  
Cooling capacity range  
Heating capacity  
Heating capacity range  
Power supply  
0.53.5  
3.2  
0.65.8  
0.64.5  
4.2  
0.66.6  
0.85.0  
5.5  
0.87.8  
1 Ph/50Hz/220240 V, 1 Ph/60Hz/220 V  
Operation mode  
Running current  
Power consumption  
Power factor  
Operation mode  
Running current  
Power consumption  
Power factor  
Cooling  
0.15  
30  
87  
Cooling  
Heating  
0.15  
30  
87  
Heating  
Cooling  
0.15  
30  
87  
Cooling  
Heating  
0.15  
30  
87  
Heating  
Cooling  
0.15  
30  
87  
Cooling  
Heating  
0.15  
30  
87  
Heating  
(A)  
(W)  
(%)  
Indoor  
Electric  
characteristics  
(A) 2.48/2.37/2.26 3.25/3.10/2.96 4.25/4.06/3.89 4.52/4.31/4.13 6.45/6.17/5.90 7.07/6.76/6.47  
Outdoor  
(W)  
(%)  
(A)  
520  
95  
3.40/3.25/3.11  
680  
95  
890  
95  
4.67/4.46/4.28  
945  
95  
1350  
95  
7.22/6.91/6.62  
1480  
95  
Starting current  
COP  
(Cooling/Heating)  
4.55/4.51  
3.80/4.31  
3.26/3.64  
High  
(Cooling/Heating) (dBA)  
42/43  
43/44  
45/45  
Indoor  
Medium (Cooling/Heating) (dBA)  
33/34  
27/27  
34/35  
27/27  
36/36  
29/29  
Operating  
noise  
Low  
(Cooling/Heating) (dBA)  
Outdoor  
(Cooling/Heating) (dBA)  
46/47  
48/50  
49/50  
Unit model  
RAS-B10GKVP-E  
RAS-B13GKVP-E  
RAS-B16GKVP-E  
Height  
(mm)  
250  
250  
250  
Dimension Width  
Depth  
(mm)  
(mm)  
790  
215  
790  
215  
790  
215  
Indoor unit  
Net weight  
(kg)  
(W)  
9
30  
9
30  
9
30  
Fan motor output  
Air flow rate  
Unit model  
Height  
Dimension Width  
Depth  
(Cooling/Heating) (m³/h)  
550/610  
RAS-10GAVP-E  
560/640  
RAS-13GAVP-E  
640/660  
RAS-16GAVP-E  
(mm)  
(mm)  
(mm)  
(kg)  
550  
780  
290  
35  
550  
780  
290  
37  
550  
780  
290  
37  
Net weight  
Outdoor unit  
Motor output  
(W)  
750  
750  
750  
Compressor Type  
Model  
Twin rotary type with DC-inverter variable speed control  
DA111A1F-20F1  
DA111A1F-20F1  
DA111A1F-20F1  
Fan motor output  
Air flow rate  
Type  
(W)  
43  
2150/2150  
Flare connection  
Ø6.35  
Ø9.52  
Ø6.35  
Ø9.52  
25  
43  
43  
2410/2410  
Flare connection  
Ø6.35  
Ø12.7  
Ø6.35  
Ø12.7  
25  
(Cooling/Heating) (m³/h)  
2410/2410  
Flare connection  
Liquid side  
Gas side  
Ø6.35  
Ø9.52  
Ø6.35  
Ø9.52  
25  
15  
10  
R410A  
Indoor unit  
Liquid side  
Gas side  
Piping  
connection  
Outdoor unit  
Maximum length  
Maximum chargeless length  
Maximum height difference  
Name of refrigerant  
Weight  
(m)  
(m)  
(m)  
15  
10  
R410A  
0.82  
15  
10  
R410A  
0.96  
Refrigerant  
(kg)  
0.96  
Power supply  
3 Wires : includes earth (Outdoor)  
Wiring  
connection  
Interconnection  
4 Wires : includes earth  
Indoor (Cooling/Heating) (°C)  
Outdoor (Cooling/Heating) (°C)  
Installation plate  
2132/028  
543/1524  
2132/028  
543/1524  
2132/028  
543/1524  
Usable temperature range  
1
1
1
Wireless remote controller  
Batteries  
1
2
1
2
1
2
Remote controller holder  
Zeolite-plus filter  
1
1
1
1
1
1
Indoor unit  
Accessory  
Mounting screw  
Remote controller holder  
mounting screw  
6 (Ø4 × 25L)  
6 (Ø4 × 25L)  
6 (Ø4 × 25L)  
2 (Ø3.1 × 16L)  
2 (Ø3.1 × 16L)  
2 (Ø3.1 × 16L)  
Plasma pure filter  
Installation manual  
Owners manual  
Drain nipple  
1
1
1
1
2
1
1
1
1
2
1
1
1
1
2
Outdoor unit  
Water-proof rubber cap  
The specifications may be subject to change without notice for purpose of improvement.  
5 –  
2-2. Operation Characteristic Curve  
<Cooling>  
<Heating>  
10  
10  
9
8
9
8
7
6
5
4
3
2
1
0
RAS-B10GKVP-E  
RAS-B13GKVP-E  
RAS-B16GKVP-E  
RAS-B10GKVP-E  
7
RAS-B13GKVP-E  
RAS-B16GKVP-E  
6
5
4
3
Conditions  
Conditions  
Indoor : DB 20˚C  
2
1
0
Indoor : DB 27˚C/WB 19˚C  
Outdoor : DB 35˚C  
Air flow : High  
Outdoor : DB 7˚C/WB 6˚C  
Air flow : High  
Pipe length : 7.5m  
Voltage : 230V  
Pipe length : 7.5m  
Voltage : 230V  
0
20  
40  
60  
80  
100  
120  
140  
0
20  
40  
60  
80  
100  
120  
140  
Compressor speed (rps)  
Compressor speed (rps)  
2-3. Capacity Variation Ratio According toTemperature  
<Cooling>  
<Heating>  
120  
110  
100  
80  
60  
40  
20  
100  
90  
80  
70  
60  
50  
RAS-B10GKVP-E  
RAS-B13GKVP-E  
RAS-B16GKVP-E  
RAS-B10GKVP-E  
RAS-B13GKVP-E  
RAS-B16GKVP-E  
Conditions  
Conditions  
Indoor : DB 20˚C  
Indoor air flow : High  
Pipe length : 7.5m  
Indoor : DB27˚C/WB19˚C  
Indoor air flow : High  
Pipe length : 7.5m  
0
15  
10  
5  
0
5
10  
32  
33 34 35 36 37 38 39 40 41 42 43 44 45 46  
Outdoor temp. (˚C)  
Outdoor temp. (˚C)  
Capacity ratio :100% = 2.5 kW (RAS-B10GKVP-E)  
3.5 kW (RAS-B13GKVP-E)  
*
4.5 kW (RAS-B16GKVP-E)  
6 –  
3. REFRIGERANT R410A  
This air conditioner adopts the new refrigerant HFC  
(R410A) which does not damage the ozone layer.  
6. When an air conditioning system charged with a  
large volume of refrigerant is installed in a small  
room, it is necessary to exercise care so that,  
even when refrigerant leaks, its concentration  
does not exceed the marginal level.  
The working pressure of the new refrigerant R410A  
is 1.6 times higher than conventional refrigerant  
(R22). The refrigerating oil is also changed in  
accordance with change of refrigerant, so be careful  
that water, dust, and existing refrigerant or refrigerat-  
ing oil are not entered in the refrigerant cycle of the  
air conditioner using the new refrigerant during  
installation work or servicing time.  
If the refrigerant gas leakage occurs and its  
concentration exceeds the marginal level, an  
oxygen starvation accident may result.  
7. Be sure to carry out installation or removal  
according to the installation manual.  
The next section describes the precautions for air  
conditioner using the new refrigerant. Conforming to  
contents of the next section together with the  
general cautions included in this manual, perform  
the correct and safe work.  
Improper installation may cause refrigeration  
trouble, water leakage, electric shock, fire, etc.  
8. Unauthorized modifications to the air conditioner  
may be dangerous. If a breakdown occurs  
please call a qualified air conditioner technician  
or electrician.  
3-1. Safety During Installation/Servicing  
Improper repairs may result in water leakage,  
electric shock and fire, etc.  
As R410As pressure is about 1.6 times higher than  
that of R22, improper installation/servicing may  
cause a serious trouble. By using tools and materi-  
als exclusive for R410A, it is necessary to carry out  
installation/servicing safely while taking the following  
precautions into consideration.  
3-2. Refrigerant Piping Installation  
3-2-1. Piping Materials and Joints Used  
For the refrigerant piping installation, copper pipes  
and joints are mainly used. Copper pipes and joints  
suitable for the refrigerant must be chosen and  
installed. Furthermore, it is necessary to use clean  
copper pipes and joints whose interior surfaces are  
less affected by contaminants.  
1. Never use refrigerant other than R410A in an air  
conditioner which is designed to operate with  
R410A.  
If other refrigerant than R410A is mixed, pressure  
in the refrigeration cycle becomes abnormally  
high, and it may cause personal injury, etc. by a  
rupture.  
1. Copper Pipes  
It is necessary to use seamless copper pipes  
which are made of either copper or copper alloy  
and it is desirable that the amount of residual oil  
is less than 40 mg/10 m. Do not use copper  
pipes having a collapsed, deformed or discolored  
portion (especially on the interior surface).  
2. Confirm the used refrigerant name, and use tools  
and materials exclusive for the refrigerant R410A.  
The refrigerant name R410A is indicated on the  
visible place of the outdoor unit of the air condi-  
tioner using R410A as refrigerant. To prevent  
mischarging, the diameter of the service port  
differs from that of R22.  
Otherwise, the expansion valve or capillary tube  
may become blocked with contaminants.  
3. If a refrigeration gas leakage occurs during  
installation/servicing, be sure to ventilate fully.  
As an air conditioner using R410A incurs pres-  
sure higher than when using R22, it is necessary  
to choose adequate materials.  
If the refrigerant gas comes into contact with fire,  
a poisonous gas may occur.  
Thicknesses of copper pipes used with R410A  
are as shown in Table 3-2-1. Never use copper  
pipes thinner than 0.8 mm even when it is  
available on the market.  
4. When installing or removing an air conditioner, do  
not allow air or moisture to remain in the refrig-  
eration cycle. Otherwise, pressure in the refrig-  
eration cycle may become abnormally high so  
that a rupture or personal injury may be caused.  
5. After completion of installation work, check to  
make sure that there is no refrigeration gas  
leakage.  
If the refrigerant gas leaks into the room, coming  
into contact with fire in the fan-driven heater,  
space heater, etc., a poisonous gas may occur.  
7 –  
Table 3-2-1 Thicknesses of annealed copper pipes  
Thickness (mm)  
Nominal diameter  
Outer diameter (mm)  
R410A  
0.80  
R22  
0.80  
0.80  
0.80  
1.00  
1/4  
3/8  
1/2  
5/8  
6.35  
9.52  
0.80  
12.70  
15.88  
0.80  
1.00  
2. Joints  
For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants.  
a) Flare Joints  
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds  
20 mm. In such a case, socket joints can be used.  
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 3-2-3 to 3-2-6 below.  
b) Socket Joints  
Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose  
diameter is larger than 20 mm.  
Thicknesses of socket joints are as shown in Table 3-2-2.  
Table 3-2-2 Minimum thicknesses of socket joints  
Reference outer diameter of  
copper pipe jointed (mm)  
Minimum joint thickness  
(mm)  
Nominal diameter  
1/4  
3/8  
1/2  
5/8  
6.35  
9.52  
0.50  
0.60  
0.70  
0.80  
12.70  
15.88  
3-2-2. Processing of Piping Materials  
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not  
enter the pipe interior, that no other oil than lubricating oils used in the installed air-water heat pump is used,  
and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils  
whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any  
other cover.  
1. Flare processing procedures and precautions  
a) Cutting the Pipe  
By means of a pipe cutter, slowly cut the pipe so that it is not deformed.  
b) Removing Burrs and Chips  
If the flared section has chips or burrs, refrigerant leakage may occur.  
Carefully remove all burrs and clean the cut surface before installation.  
c) Insertion of Flare Nut  
8 –  
d) Flare Processing  
Make certain that a clamp bar and copper  
pipe have been cleaned.  
ØD  
By means of the clamp bar, perform the flare  
processing correctly.  
A
Use either a flare tool for R410A or conven-  
tional flare tool.  
Flare processing dimensions differ according  
to the type of flare tool. When using a con-  
ventional flare tool, be sure to secure dimen-  
sion Aby using a gauge for size adjustment.  
Fig. 3-2-1 Flare processing dimensions  
Table 3-2-3 Dimensions related to flare processing for R410A  
A (mm)  
Conventional flare tool  
Outer  
diameter  
(mm)  
Nominal  
diameter  
Thickness  
(mm)  
Flare tool for R410A  
clutch type  
Clutch type  
1.0 to 1.5  
1.0 to 1.5  
1.0 to 1.5  
1.0 to 1.5  
Wing nut type  
1.5 to 2.0  
1/4  
3/8  
1/2  
5/8  
6.35  
9.52  
0.8  
0.8  
0.8  
1.0  
0 to 0.5  
0 to 0.5  
0 to 0.5  
0 to 0.5  
1.5 to 2.0  
12.70  
15.88  
2.0 to 2.5  
2.0 to 2.5  
Table 3-2-4 Dimensions related to flare processing for R22  
A (mm)  
Outer  
Nominal  
diameter  
Thickness  
(mm)  
diameter  
(mm)  
Conventional flare tool  
Flare tool for R22  
clutch type  
Clutch type  
0.5 to 1.0  
0.5 to 1.0  
0.5 to 1.0  
0.5 to 1.0  
Wing nut type  
1.0 to 1.5  
1/4  
3/8  
1/2  
5/8  
6.35  
9.52  
0.8  
0.8  
0.8  
1.0  
0 to 0.5  
0 to 0.5  
0 to 0.5  
0 to 0.5  
1.0 to 1.5  
12.70  
15.88  
1.5 to 2.0  
1.5 to 2.0  
Table 3-2-5 Flare and flare nut dimensions for R410A  
Dimension (mm)  
Nominal  
diameter  
Outer diameter  
Thickness  
(mm)  
Flare nut width  
(mm)  
(mm)  
A
B
C
D
1/4  
3/8  
1/2  
5/8  
6.35  
9.52  
0.8  
0.8  
0.8  
1.0  
9.1  
9.2  
6.5  
9.7  
13  
20  
23  
25  
17  
22  
26  
29  
13.2 13.5  
12.70  
15.88  
16.6 16.0 12.9  
19.7 19.0 16.0  
9 –  
Table 3-2-6 Flare and flare nut dimensions for R22  
Dimension (mm)  
Nominal  
diameter  
Outer diameter  
Thickness  
(mm)  
Flare nut width  
(mm)  
(mm)  
A
B
C
D
1/4  
3/8  
1/2  
5/8  
3/4  
6.35  
9.52  
0.8  
0.8  
0.8  
1.0  
1.0  
9.0  
9.2  
6.5  
9.7  
13  
20  
20  
23  
34  
17  
22  
24  
27  
36  
13.0 13.5  
12.70  
15.88  
19.05  
16.2 16.0 12.9  
19.7 19.0 16.0  
23.3 24.0 19.2  
D
B
A
C
Fig. 3-2-2 Relations between flare nut and flare seal surface  
2. Flare Connecting Procedures and Precautions  
a) Make sure that the flare and union portions do not have any scar or dust, etc.  
b) Correctly align the processed flare surface with the union axis.  
c) Tighten the flare with designated torque by means of a torque wrench. The tightening torque for R410A is  
the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur.  
When it is strong, the flare nut may crack and may be made non-removable. When choosing the tighten-  
ing torque, comply with values designated by manufacturers.Table 3-2-7 shows reference values.  
NOTE :  
When applying oil to the flare surface, be sure to use oil designated by the manufacturer.  
If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.  
Table 3-2-7 Tightening torque of flare for R410A [Reference values]  
Tightening torque of torque  
wrenches available on the market  
N•m (kgf•cm)  
Nominal  
diameter  
Outer diameter  
(mm)  
Tightening torque  
N•m (kgf•cm)  
1/4  
3/8  
1/2  
5/8  
6.35  
9.52  
14 to 18 (140 to 180)  
33 to 42 (330 to 420)  
50 to 62 (500 to 620)  
63 to 77 (630 to 770)  
16 (160), 18 (180)  
42 (420)  
12.70  
15.88  
55 (550)  
65 (650)  
10 –  
3-3. Tools  
3-3-1. RequiredTools  
The service port diameter of packed valve of the outdoor unit in the air-water heat pump using R410A is  
changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing  
dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are  
lengthened.  
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge,  
clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.  
1. Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))  
2. Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)  
3. Tools commonly used for R410A and for conventional refrigerant (R22)  
The table below shows the tools exclusive for R410A and their interchangeability.  
Tools exclusive for R410A (The following tools for R410A are required.)  
Tools whose specifications are changed for R410A and their interchangeability  
R410A  
Conventional air-water  
heat pump installation  
air-water heat pump installation  
No.  
Used tool  
Usage  
Existence of  
Whether conven-  
Whether new equipment  
can be used with  
conventional refrigerant  
new equipment tional equipment  
for R410A  
can be used  
1
2
Flare tool  
Pipe flaring  
Ye s  
*(Note 1)  
¡
Copper pipe gauge for  
adjusting projection  
margin  
Flaring by  
conventional flare tool  
Ye s  
Ye s  
Ye s  
*(Note 1)  
*(Note 1)  
Torque wrench  
(For Ø12.7)  
3
Connection of flare nut  
×
×
×
×
4
5
6
Gauge manifold  
Charge hose  
Evacuating, refrigerant  
charge, run check, etc.  
Vacuum pump adapter Vacuum evacuating  
Ye s  
Ye s  
×
×
¡
¡
Electronic balance for  
Refrigerant charge  
refrigerant charging  
7
8
9
Refrigerant cylinder  
Leakage detector  
Refrigerant charge  
Gas leakage check  
Refrigerant charge  
Ye s  
Ye s  
×
×
×
×
¡
×
10 Charging cylinder  
(Note 2)  
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection  
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.  
(Note 2) Charging cylinder for R410A is being currently developed.  
General tools (Conventional tools can be used.)  
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary  
as the general tools.  
1. Vacuum pump  
4. Reamer  
9. Hole core drill (Ø65)  
Use vacuum pump by attaching  
vacuum pump adapter.  
5. Pipe bender  
10. Hexagon wrench  
(Opposite side 4mm)  
6. Level vial  
2. Torque wrench (For Ø6.35, Ø9.52)  
11. Tape measure  
12. Metal saw  
7. Screwdriver (+, )  
8. Spanner or Monkey wrench  
3. Pipe cutter  
Also prepare the following equipments for other installation method and run check.  
1. Clamp meter  
2. Thermometer  
3. Insulation resistance tester  
4. Electroscope  
11 –  
3-4. Recharging of Refrigerant  
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the  
following steps.  
Recover the refrigerant, and check no refrigerant  
remains in the equipment.  
When the compound gauges pointer has indicated  
0.1 Mpa (76 cmHg), place the handle Low in the  
fully closed position, and turn off the vacuum pumps  
power switch.  
Connect the charge hose to packed valve service  
port at the outdoor units gas side.  
Keep the status as it is for 1 to 2 minutes, and ensure  
that the compound gauges pointer does not return.  
Connect the charge hose to the vacuum pump  
adapter.  
Set the refrigerant cylinder to the electronic balance,  
connect the connecting hose to the cylinder and the  
connecting port of the electronic balance, and charge  
liquid refrigerant.  
Open fully both packed valves at liquid and gas  
sides.  
(For refrigerant charging, see the figure below.)  
Place the handle of the gauge manifold Low in the  
fully opened position, and turn on the vacuum pumps  
power switch. Then, evacuating the refrigerant in the  
cycle.  
1. Never charge refrigerant exceeding the specified amount.  
2. If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.  
3. Do not carry out additional charging.  
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the  
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the  
specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high  
pressure, and may cause a rupture or personal injury.  
(Water heat  
(Outdoor unit)  
exchanger unit)  
Opened  
Refrigerant cylinder  
(with siphon)  
Check valve  
Opened  
Opened  
Open/close  
valve for charging  
Closed  
Service port  
Electronic balance for refrigerant charging  
Fig. 3-4-1 Configuration of refrigerant charging  
12 –  
1. Be sure to make setting so that liquid can be charged.  
2. When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.  
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant.  
Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the  
cylinder upside down if cylinder is not equipped with siphon.  
[ Cylinder with siphon ]  
[ Cylinder without siphon ]  
Gauge manifold  
Gauge manifold  
OUTDOOR unit  
OUTDOOR unit  
c y l i n d e r  
a n t i g e r R e f r  
Refrigerant  
cylinder  
Electronic  
balance  
Electronic  
balance  
Siphon  
R410A refrigerant is HFC mixed refrigerant.  
Therefore, if it is charged with gas, the composi-  
tion of the charged refrigerant changes and the  
characteristics of the equipment varies.  
Fig. 3-4-2  
3-5. Brazing of Pipes  
1. Phosphor bronze brazing filler tends to react  
with sulfur and produce a fragile compound  
water solution, which may cause a gas  
leakage.Therefore, use any other type of  
brazing filler at a hot spring resort, etc., and  
coat the surface with a paint.  
3-5-1. Materials for Brazing  
1. Silver brazing filler  
Silver brazing filler is an alloy mainly composed  
of silver and copper. It is used to join iron, copper  
or copper alloy, and is relatively expensive though  
it excels in solderability.  
2. When performing brazing again at time of  
servicing, use the same type of brazing filler.  
2. Phosphor bronze brazing filler  
Phosphor bronze brazing filler is generally used  
to join copper or copper alloy.  
3-5-2. Flux  
1. Reason why flux is necessary  
3. Low temperature brazing filler  
By removing the oxide film and any foreign  
matter on the metal surface, it assists the flow  
of brazing filler.  
Low temperature brazing filler is generally called  
solder, and is an alloy of tin and lead. Since it is  
weak in adhesive strength, do not use it for  
refrigerant pipes.  
In the brazing process, it prevents the metal  
surface from being oxidized.  
By reducing the brazing fillers surface tension,  
the brazing filler adheres better to the treated  
metal.  
13 –  
2. Characteristics required for flux  
3-5-3. Brazing  
Activated temperature of flux coincides with the  
brazing temperature.  
As brazing work requires sophisticated techniques,  
experiences based upon a theoretical knowledge, it  
must be performed by a person qualified.  
Due to a wide effective temperature range, flux  
is hard to carbonize.  
In order to prevent the oxide film from occurring in  
the pipe interior during brazing, it is effective to  
proceed with brazing while letting dry Nitrogen gas  
(N2) flow.  
It is easy to remove slag after brazing.  
The corrosive action to the treated metal and  
brazing filler is minimum.  
It excels in coating performance and is harm-  
less to the human body.  
Never use gas other than Nitrogen gas.  
1. Brazing method to prevent oxidation  
As the flux works in a complicated manner as  
described above, it is necessary to select an  
adequate type of flux according to the type and  
shape of treated metal, type of brazing filler and  
brazing method, etc.  
1) Attach a reducing valve and a flow-meter to  
the Nitrogen gas cylinder.  
2) Use a copper pipe to direct the piping mate-  
rial, and attach a flow-meter to the cylinder.  
3. Types of flux  
• Noncorrosive flux  
3) Apply a seal onto the clearance between the  
piping material and inserted copper pipe for  
Nitrogen in order to prevent backflow of the  
Nitrogen gas.  
Generally, it is a compound of borax and boric  
acid.  
It is effective in case where the brazing tem-  
perature is higher than 800°C.  
4) When the Nitrogen gas is flowing, be sure to  
keep the piping end open.  
• Activated flux  
Most of fluxes generally used for silver brazing  
are this type.  
5) Adjust the flow rate of Nitrogen gas so that it  
is lower than 0.05 m3/Hr or 0.02 MPa  
(0.2kgf/cm2) by means of the reducing valve.  
It features an increased oxide film removing  
capability due to the addition of compounds  
such as potassium fluoride, potassium chloride  
and sodium fluoride to the borax-boric acid  
compound.  
6) After performing the steps above, keep the  
Nitrogen gas flowing until the pipe cools down  
to a certain extent (temperature at which  
pipes are touchable with hands).  
7) Remove the flux completely after brazing.  
4. Piping materials for brazing and used  
brazing filler/flux  
Piping material Used brazing filler  
Used flux  
Do not use  
Paste flux  
Vapor flux  
Copper - Copper  
Copper - Iron  
Iron - Iron  
Phosphor copper  
Silver  
M
Flow meter  
Silver  
Stop valve  
Nitrogen gas  
cylinder  
1. Do not enter flux into the refrigeration cycle.  
From Nitrogen cylinder  
2. When chlorine contained in the flux remains  
within the pipe, the lubricating oil deteriorates.  
Therefore, use a flux which does not contain  
chlorine.  
Pipe  
Nitrogen  
gas  
3. When adding water to the flux, use water  
which does not contain chlorine (e.g. distilled  
water or ion-exchange water).  
Rubber plug  
4. Remove the flux after brazing.  
Fig. 3-5-1 Prevention of oxidation during brazing  
14 –  
4. CONSTRUCTION VIEWS  
4-1. Indoor Unit  
RAS-B10GKVP-E  
RAS-B13GKVP-E  
RAS-B16GKVP-E  
790  
Plasma pure filter  
Indoor heat exchanger  
Front panel  
Air filter  
790  
215  
53  
53  
Knockout system  
Zeolite-plus filter  
Air ionizer  
Knockout system  
60  
54.5  
Remote controller holder  
64  
54.5  
60  
5
Installation plate hanging section  
Wireless remote controller  
58  
19  
Drain hose  
(Outside length:0.54m)  
290  
Installation plate  
hanging section  
Connecting pipe  
(Outside length:0.45m)  
Flare Ø6.35  
Connecting pipe  
(Outside length:0.4m)  
Flare Ø9.52  
(RAS-B16GKVP-E : Ø12.7)  
Parts name of remote controller WH-H03JE  
91  
674  
450  
25  
Stud bolt hole  
for Ø6  
10  
10  
10  
10  
288  
Hanging  
section  
Minimum  
distance  
to ceilinfg  
Stud bolt hole  
for Ø8 to Ø10  
Minimum  
distance  
to wall  
Minimum  
distance  
to wall  
74 or more  
140 or more  
Lower part  
hanging section  
Outline of  
installation plate  
Center line  
of main unit  
Center line of  
installation plate  
91  
304  
304  
91  
790  
15 –  
4-2. Outdoor Unit  
RAS-10GAVP-E, RAS-13GAVP-E, RAS-16GAVP-E  
Ø25 drain hole  
A
leg part  
600  
108  
90  
Ø11-14U-shape hole  
(for Ø8-Ø10 anchor bolt)  
125  
54  
2-Ø20x88 drain long hole  
Connecting pipe port  
Pipe dia. Ø9.52:RAS-10GAVP-E, RAS-13GAVP-E  
(
)
Ø12.7:RAS-16GAVP-E  
Connecting pipe port  
(Pipe dia. Ø6.35)  
30  
8-Ø7 hole  
(for fixing outdoor unit)  
B
leg part  
Ø11x14 long hole  
(for Ø8-Ø10 anchor bolt)  
483  
257  
Packed valve cover  
108  
157  
79  
69.5  
147  
145  
Z
25  
22  
31  
143  
71  
342  
32  
500  
780  
Charging port  
4-Ø4.5 embossment  
Fan guard  
Fin guard  
Detailed  
A
leg part  
600  
54  
38  
11  
When installing the outdoor unit,  
leave open in at least two of  
directions (A), (B), (C) and (D)  
shown in the figure below.  
Z
view  
Mounting dimensions of anchor bolt  
600  
Outside line  
of product  
2-Ø11x14U- Shape hole  
(for Ø8-Ø10 anchor bolt)  
50 or more  
D
Intake  
250 or more  
A
Intake  
11  
Outside line  
of product  
C
100 or more  
Outside line  
of product  
Minimum distance  
from wall  
200 or more  
B
2-Ø11x14 long hole  
(for Ø8-Ø10 anchor bolt)  
Outlet  
38  
54  
600  
Detailed  
B
leg part  
16 –  
5. WIRING DIAGRAM  
5-1. Outdoor Unit  
RAS-10GAVP-E, RAS-13GAVP-E, RAS-16GAVP-E  
Color  
Identification  
RED : RED  
WHI : WHITE  
BLK : BLACK  
BLU : BLUE  
BRW : BROWN  
ORN : ORANGE  
PUR : PURPUL  
YEL : YELLOW  
GRY : GRAY  
PNK : PINK  
220-240V ~50Hz  
220V ~60Hz  
5-2. Indoor Unit  
RAS-B10GKVP-E, RAS-B13GKVP-E, RAS-B16GKVP-E  
GRN& GREEN&  
:
YEL  
YELLOW  
BLK  
BLK  
1 1  
2 2  
3 3  
4 4  
5 5  
6 6  
INDOOR  
TERMINAL  
BLOCK  
1 2 3  
1 2 3 4  
1 2 3 4  
Heat  
exchanger  
Ion electrode  
1 2 3 4  
GRN & YEL  
BLK WHI RED  
3
1
1 2 3 4  
CN22  
CN23  
CN21  
CN33  
CN01  
(WHI)  
(BLU)  
BRW  
1 1  
BLK  
1 1  
Micro SW  
CN34  
FUSE  
F01  
2 2  
(RED)  
BLK  
BLU  
2 2  
HEAT EXCHANGER  
SENSOR (TC)  
AC 250V  
T3.15A  
CN03  
CN10  
(WHI)  
1 1  
FAN MOTOR  
(WHI)  
RED  
BLK  
BLK  
BLK  
1 1  
2 2  
THERMO SENSOR  
(TA)  
3 3  
4 4  
5 5  
6 6  
WHI DC MOTOR  
YEL  
BLU  
CN100  
CN13  
(WHI)  
(WHI)  
BLU  
1 1  
BLU  
2 2  
BLU  
3 3  
BLU  
4 4  
BLU  
5 5  
BLU  
6 6  
BLU  
7 7  
BLU  
8 8  
WHI  
9 9  
9 9  
8 8  
7 7  
6 6  
5 5  
4 4  
3 3  
2 2  
1 1  
DC5V  
LINE  
FILTER  
CN07  
(WHI)  
DB01  
WHI  
1 1  
YEL  
2 2  
YEL  
3 3  
YEL  
4 4  
YEL  
5 5  
DC12V  
1 1  
2 2  
3 3  
4 4  
5 5  
TNR  
MAIN P.C. BOARD  
(MCC-5020)  
CN08 (WHI)  
1 2 3 4  
LOUVER MOTOR  
MCC-899  
10 10  
17 –  
6. SPECIFICATIONS OF ELECTRICAL PARTS  
6-1. Indoor Unit  
RAS-B10GKVP-E, RAS-B13GKVP-E, RAS-B16GKVP-E  
No.  
1
Parts name  
Fan motor (for indoor)  
Type  
MF-280-30-5R  
( )  
Specifications  
DC280340V, 30W  
2
Room temp. sensor (TA-sensor)  
Heat exchanger temp. sensor (TC-sensor)  
Louver motor  
10kat 25°C  
3
( )  
10kat 25°C  
4
MP24Z  
Output (Rated) 1W, 16 poles, DC12V  
6-2. Outdoor Unit  
RAS-10GAVP-E, RAS-13GAVP-E, RAS-16GAVP-E  
No.  
1
Parts name  
Model name  
CH-57  
Rating  
L = 10mH, 16A × 2  
DC140V, 43W  
10k(25°C)  
Reactor  
2
Outside fan motor  
ICF-140-43-4R  
(Inverter attached)  
(Inverter attached)  
(Inverter attached)  
(Inverter attached)  
——  
3
Suction temp. sensor (TS sensor)  
Discharge temp. sensor (TD sensor)  
Outside air temp. sensor (TO sensor)  
Heat exchanger temp. sensor (TE sensor)  
Terminal block (6P)  
4
62k(20°C)  
5
10k(25°C)  
6
10k(25°C)  
7
20A, AC250V  
3-phases 4-poles 750W  
DC12V  
8
Compressor  
DA111A1F-20F1  
CAM-MD12TF  
VHV  
9
Coil for P.M.V.  
10  
Coil for 4-way valve  
AC220240V  
18 –  
7. REFRIGERANT CYCLE DIAGRAM  
7-1. Refrigerant Cycle Diagram  
RAS-B10GKVP-E/RAS-10GAVP-E  
T1 Temp. measurement  
INDOOR UNIT  
Indoor heat  
exchanger  
TC  
TA  
Cross flow fan  
Max. : 25m  
Min. : 2m  
P
Pressure measurement  
Chargeless : 15m  
Charge : 20g/m  
(16 to 25m)  
Deoxidized copper pipe  
Outer dia. : 6.35mm  
Thickness : 0.8mm  
Gauge attaching port  
Vacuum pump connecting port  
Sectional shape  
of heat insulator  
Deoxidized copper pipe  
Outer dia. : 9.52mm  
Thickness : 0.8mm  
Strainer  
Muffler  
4-way valve  
(STF-0108Z)  
Pulse motor  
valve at liquid side  
(CAM-B22YGTF-3)  
Muffler  
TD  
Compressor  
DA111A1F-20F1  
Strainer  
TS  
TO  
Outdoor heat  
exchanger  
Temp. measurement  
T2  
TE  
Refrigerant amount : 0.82kg  
Propeller fan  
OUTDOOR UNIT  
Gas leak check position  
Refrigerant flow (Cooling)  
Refrigerant flow (Heating)  
NOTE :  
NOTE :  
The maximum pipe length of this air conditioner is 25 m. When the pipe length exceeds 15m, the additional  
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 200g)  
19 –  
RAS-B13GKVP-E/RAS-13GAVP-E, RAS-B16GKVP-E/RAS-16GAVP-E  
T1 Temp. measurement  
INDOOR UNIT  
Indoor heat  
exchanger  
TC  
TA  
Cross flow fan  
Max. : 25m  
Min. : 2m  
P
Pressure measurement  
Chargeless : 15m  
Charge : 20g/m  
(16 to 25m)  
Deoxidized copper pipe  
Outer dia. : 6.35mm  
Thickness : 0.8mm  
Gauge attaching port  
Vacuum pump connecting port  
Sectional shape  
of heat insulator  
Deoxidized copper pipe  
Outer dia. : 9.52mm(13),  
12.7mm(16)  
Thickness : 0.8mm  
Strainer  
Muffler  
4-way valve  
(STF-0108Z)  
Pulse motor  
valve at liquid side  
(CAM-B22YGTF-3)  
Muffler  
TD  
Compressor  
DA111A1F-20F1  
TS  
TO  
Outdoor heat  
exchanger  
Split capillary  
Ø1.2 x 80  
Ø1.2 x 80  
Temp. measurement  
T2  
TE  
Refrigerant amount : 0.96kg  
Propeller fan  
OUTDOOR UNIT  
Gas leak check position  
Refrigerant flow (Cooling)  
Refrigerant flow (Heating)  
NOTE :  
NOTE :  
The maximum pipe length of this air conditioner is 25 m. When the pipe length exceeds 15m, the additional  
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 200g)  
20 –  
7-2. Operation Data  
<Cooling>  
Temperature  
condition (°C)  
Heat exchanger  
pipe temp.  
Standard  
pressure  
P (MPa)  
Compressor  
revolution  
(rps)  
Model name  
RAS-  
Indoor  
fan mode  
Outdoor  
fan mode  
Indoor Outdoor  
T1 (°C)  
T2 (°C)  
42 to 44  
42 to 45  
43 to 47  
B10GKVP-E  
B13GKVP-E  
B16GKVP-E  
0.9 to 1.1  
0.8 to 1.0  
0.7 to 0.9  
13 to 15  
11 to 14  
8 to 11  
High  
High  
High  
High  
High  
High  
37  
59  
82  
27/19  
35/–  
<Heating>  
Temperature  
condition (°C)  
Heat exchanger  
pipe temp.  
Standard  
pressure  
P (MPa)  
Compressor  
revolution  
(rps)  
Model name  
RAS-  
Indoor  
fan mode  
Outdoor  
fan mode  
Indoor Outdoor  
T1 (°C)  
T2 (°C)  
0 to 3  
0 to 2  
0 to 2  
B10GKVP-E  
B13GKVP-E  
B16GKVP-E  
2.2 to 2.4  
2.5 to 2.7  
2.8 to 3.0  
37 to 39  
42 to 45  
48 to 49  
High  
High  
High  
High  
High  
High  
54  
65  
86  
20/–  
7/6  
NOTES :  
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.  
(Thermistor themometer)  
2. Connecting piping condition : 7.5 m  
21 –  
8. CONTROL BLOCK DIAGRAM  
8-1. Indoor Unit  
RAS-B10GKVP-E, RAS-B13GKVP-E, RAS-B16GKVP-E  
Indoor Unit Control Unit  
Louver Motor  
M.C.U.  
Louver  
Motor  
Functions  
Heat Exchanger Sensor (Tc)  
Cold draft preventing Function  
Room Temperature Sensor (Ta)  
3-minute Delay at Restart for Compressor  
Drive Control  
Infrared Rays Signal Receiver  
Fan Motor Starting Control  
and Indication  
Indoor Fan  
Motor Control  
Processing  
(Temperature Processing)  
Initializing Circuit  
Indoor  
Fan Motor  
Timer  
Clock Frequency  
Oscillator Circuit  
Serial Signal Communication  
Clean Function  
Air purifier  
unit  
Power Supply  
Circuit  
Converter  
(D.C circuit)  
Micro Switch  
Noise Filter  
Serial Signal Transmitter/Receiver  
From Outdoor Unit  
220-240V ~50Hz  
220V ~60Hz  
Serial Signal Communication  
(Operation Command and Information)  
Infrared Rays, 36.7kHz  
Remote Controller  
REMOTE CONTROLLER  
Operation (START/STOP)  
Operation Mode Selection  
AUTO, COOL, DRY, HEAT  
Thermo. Setting  
Fan Speed Selection  
ON TIMER Setting  
OFF TIMER Setting  
Louver AUTO Swing  
Louver Direction Setting  
ECO  
Hi-POWER  
Air Purifier  
SLEEP  
22 –  
MICRO-COMPUTER BLOCK DIAGRAM  
For INDOOR UNIT  
220240 V ~50Hz  
220 V ~60Hz  
MCC5009 (P.C.B)  
OUTDOOR UNIT  
Indoor unit  
send/receive  
circuit  
Current  
detect  
M.C.U  
PWM synthesis function  
Input current release control  
IGBT over-current detect control  
Outdoor fan control  
Gate drive  
circuit  
Discharge  
temp. sensor  
High power factor correction control  
Inverter output frequency control  
A/D converter function  
P.M.V. control  
Discharge temp. control  
4-way valve control  
Outdoor air  
temp. sensor  
Current  
detect  
Suction temp.  
sensor  
Gate drive  
circuit  
Signal communication to indoor unit  
Heat exchanger  
temp.sensor  
High Power  
factor Correction  
circuit  
Clock  
frequency  
4MHz  
Noise  
Filter  
Input current  
sensor  
Converter  
(AC DC)  
Outdoor  
Fan motor  
Inverter  
(DC AC)  
Driver circuit  
of P.M.V.  
Relay  
circuit  
Inverter  
(DC AC)  
Compressor  
P.M.V. : Pulse Motor Valve  
M.C.U. : Micro Control Unit  
4-way  
valve  
P.M.V.  
9. OPERATION DESCRIPTION  
Detection of inverter input current and current  
release operation  
Over-current detection and prevention operation  
to IGBT module (Compressor stop function)  
Compressor and outdoor fan stop function when  
serial signal is off (when the serial signal does not  
reach the board assembly of outdoor control by  
trouble of the signal system)  
9-1. Outline of Air Conditioner Control  
This air conditioner is a capacity-variable type air  
conditioner, which uses DC motor for the indoor fan  
motor and the outdoor fan motor. And the capacity-  
proportional control compressor which can change the  
motor speed in the range from 13 to 115 rps is  
mounted. The DC motor drive circuit is mounted to the  
indoor unit. The compressor and the inverter to control  
fan motor are mounted to the outdoor unit.  
Transferring of operation information (Serial  
signal) from outdoor unit controller to indoor unit  
controller  
The entire air conditioner is mainly controlled by the  
indoor unit controller.  
Detection of outdoor temperature and operation  
revolution control  
Defrost control in heating operation (Temp.  
measurement by outdoor heat exchanger and  
control for 4-way valve and outdoor fan)  
The indoor unit controller drives the indoor fan motor  
based upon command sent from the remote controller,  
and transfers the operation command to the outdoor  
unit controller.  
The outdoor unit controller receives operation com-  
mand from the indoor unit side, and controls the  
outdoor fan and the pulse motor valve. (P.M.V)  
Besides, detecting revolution position of the compres-  
sor motor, the outdoor unit controller controls speed of  
the compressor motor by controlling output voltage of  
the inverter and switching timing of the supply power  
(current transfer timing) so that motors drive according  
to the operation command.  
3. Contents of operation command signal  
(Serial signal) from indoor unit controller to  
outdoor unit controller  
The following three types of signals are sent from  
the indoor unit controller.  
Operation mode set on the remote controller  
Compressor revolution command signal defined  
by indoor temperature and set temperature  
(Correction along with variation of room tempera-  
ture and correction of indoor heat exchanger  
temperature are added.)  
And then, the outdoor unit controller transfers reversely  
the operating status information of the outdoor unit to  
control the indoor unit controller.  
As the compressor adopts four-pole brushless  
DC motor, the frequency of the supply power  
from inverter to compressor is two-times cycles  
of the actual number of revolution.  
Temperature of indoor heat exchanger  
For these signals ([Operation mode] and [Com-  
pressor revolution] indoor heat exchanger tem-  
perature), the outdoor unit controller monitors the  
input current to the inverter, and performs the  
followed operation within the range that current  
does not exceed the allowable value.  
1. Role of indoor unit controller  
The indoor unit controller judges the operation  
commands from the remote controller and assumes  
the following functions.  
4. Contents of operation command signal  
(Serial signal) from outdoor unit controller  
to indoor unit controller  
Judgment of suction air temperature of the indoor  
heat exchanger by using the indoor temp. sensor.  
(TA sensor)  
The following signals are sent from the outdoor unit  
controller.  
Judgment of the indoor heat exchanger tempera-  
ture by using heat exchanger sensor (TC sensor)  
(Prevent-freezing control, etc.)  
The current operation mode  
The current compressor revolution  
Outdoor temperature  
Louver motor control  
Indoor fan motor operation control  
LED (Light Emitting Diode) display control  
Existence of protective circuit operation  
For transferring of these signals, the indoor unit  
controller monitors the contents of signals, and  
judges existence of trouble occurrence.  
Transferring of operation command signal (Serial  
signal) to the outdoor unit  
Reception of information of operation status  
(Serial signal including outside temp. data) to the  
outdoor unit and judgment/display of error  
Contents of judgment are described below.  
Whether distinction of the current operation  
status meets to the operation command signal  
Air purifier operation control  
Whether protective circuit operates  
2. Role of outdoor unit controller  
When no signal is received from the outdoor  
unit controller, it is assumed as a trouble.  
Receiving the operation command signal (Serial  
signal) from the indoor unit controller, the outdoor  
unit performs its role.  
Compressor operation control  
Operation control of outdoor fan motor  
P.M.V. control  
Operations followed to judgment  
of serial signal from indoor side.  
4-way valve control  
24 –  
9-2. Operation Description  
9-2.  
1. Basic operation ........................................................................................................... 26  
1. Operation control ................................................................................................... 26  
2. Cooling/Heating operation ..................................................................................... 27  
3. AUTO operation ..................................................................................................... 27  
4. DRY operation........................................................................................................ 27  
2. Indoor fan motor control ............................................................................................. 28  
3. Outdoor fan motor control........................................................................................... 30  
4. Capacity control .......................................................................................................... 31  
5. Current release control ............................................................................................... 31  
6. Release protective control by temperature of indoor heat exchanger........................ 32  
7. Quick heating control .................................................................................................. 33  
8. Defrost control (Only in heating operation) ................................................................ 33  
9. Louver control ............................................................................................................. 34  
1) Louver position....................................................................................................... 34  
2) Air direction adjustment ......................................................................................... 34  
3) Swing ..................................................................................................................... 34  
10. ECO operation ............................................................................................................ 35  
11. Temporary operation................................................................................................... 36  
12. Air purifying control [Detection of abnormality] .......................................................... 37  
13. Discharge temperature control ................................................................................... 37  
14. Pulse motor valve (P.M.V.) control .............................................................................. 38  
15. Clean operation .......................................................................................................... 39  
16. Clean operation release ............................................................................................ 40  
17. Select switch on remote controller ............................................................................. 41  
9-3. Auto Restart Function.............................................................................................42  
9-3-1. How to Set the Auto Restart Function.................................................................... 42  
9-3-2. How to Cancel the Auto Restart Function ............................................................. 43  
9-3-3. Power Failure During Timer Operation ................................................................... 43  
9-4. FILTER Indicator......................................................................................................43  
9-4-1. How to Turn Off FILTER Indicator............................................................................ 43  
9-5. Remote Controller and Its Fuctions ......................................................................44  
9-5-1. Parts Name of Remote Controller ........................................................................... 44  
9-5-2. Name and Functions of Indications on Remote Controller ................................. 45  
9-6. Hi-POWER Mode  
([Hi-POWER] button on the remote controller is pressed) ..................................46  
25 –  
Item  
Operation flow and applicable data, etc.  
1. Operation control  
Description  
1. Basic  
operation  
Receiving the users operation condition setup, the operation statuses of indoor/outdoor units are  
controlled.  
1) The operation conditions are selected by the remote controller as shown in the below.  
2) A signal is sent by ON button of the remote controller.  
3) The signal is received by a sensor of the indoor unit and processed by the indoor controllers as  
shown in the below.  
4) The indoor controller controls the indoor fan motor and louver motor.  
5) The indoor controller sends the operation command to the outdoor controller, and sends/receives  
the control status with a serial signal.  
6) The outdoor controller controls the operation as shown in the left, and also controls the compres-  
sor, outdoor fan motor, 4-way valve and pulse motor valve.  
Remote controller  
Selection of  
operation conditions  
Control contents of remote controller  
ON/OFF (Air conditioner/Air purifier)  
Operation select (COOL/HEAT/AUTO/DRY)  
Temperature setup  
Air direction  
ON/OFF  
Swing  
Air volume select (AUTO/LOW/LOW+/MED/MED+/HIGH)  
ECO  
ON timer setup  
OFF timer setup  
High power  
Indoor unit  
Signal receiving  
Indoor unit control  
Indoor unit control  
Command signal generating function of  
indoor unit operation  
Calculation function (temperature calculation)  
Activation compensation function of indoor fan  
Cold draft preventive function  
Timer function  
Indoor heat exchanger release control  
Indoor fan motor  
Louver motor  
Operation command  
Serial signal send/receive  
~
Outdoor unit  
Serial signal send/receive  
Outdoor unit control  
Outdoor unit control  
Frequency control of inverter output  
Waveform composite function  
Calculation function  
(Temperature calculation)  
Inverter  
Compressor  
Outdoor fan motor  
4-way valve  
Pulse motor valve  
(P.M.V.)  
AD conversion function  
Quick heating function  
Delay function of compressor reactivation  
Current release function  
GTr over-current preventive function  
Defrost operation function  
26 –  
Item  
Operation flow and applicable data, etc.  
2. Cooling/Heating operation  
Description  
1. Basic  
operation  
The operations are performed in the following parts by controls according to cooling/heating conditions.  
1) Receiving the operation ON signal of the remote controller, the cooling or heating operation signal  
starts being transferred form the indoor controller to the outdoor unit.  
2) At the indoor unit side, the indoor fan is operated according to the contents of 2. Indoor fan  
motor controland the louver according to the contents of 9. Louver control, respectively.  
3) The outdoor unit controls the outdoor fan motor, compressor, pulse motor valve and  
4-way valve according to the operation signal sent from the indoor unit.  
*1. The power coupler of 4-way valve is usually turned off, and it is turned on during defrost  
operation. (Only in heating)  
Operation ON  
Setup of remote controller  
Indoor unit control  
Indoor fan motor control / Louver control  
Sending of operation command signal  
Compressor revolution control / Outdoor fan motor control /  
4-way valve control  
In cooling operation: ON  
Outdoor unit control  
[
]
In heating operation: OFF  
Pulse motor valve control  
3. AUTO operation  
Selection of operation mode  
1) Detects the room temperature (Ta) when  
the operation started.  
2) Selects an operation mode from Ta in  
the left figure.  
As shown in the following figure, the operation starts by  
selecting automatically the status of room temperature  
(Ta) when starting AUTO operation.  
3) Fan operation continues until an  
operation mode is selected.  
*1. When reselecting the operation mode, the fan  
speed is controlled by the previous operation mode.  
4) When AUTO operation has started  
within 2 hours after heating operation  
stopped and if the room temperature is  
20°C or more, the fan operation is  
performed with Super Ultra LOWmode  
for 3 minutes.  
Ta  
Cooling operation  
Ts + 1  
Then, select an operation mode.  
Monitoring (Fan)  
5) If the status of compressor-OFF  
continues for 15 minutes the room  
temperature after selecting an operation  
mode (COOL/HEAT), reselect an  
operation mode.  
Ts 1  
Heating operation  
4. DRY operation  
1) Detects the room temperature (Ta) when  
the DRY operation started.  
DRY operation is performed according to the difference  
between room temperature and the setup temperature as 2) Starts operation under conditions in the  
shown below.  
left figure according to the temperature  
difference between the room tempera-  
ture and the setup temperature (Tsc).  
Setup temperature (Tsc)  
= Set temperature on remote controller  
(Ts) + (0.0 to 1.0)  
In DRY operation, fan speed is controlled in order to  
prevent lowering of the room temperature and to avoid air  
flow from blowing directly to persons.  
[
]
˚C  
3) When the room temperature is lower  
1°C or less than the setup temperature,  
turn off the compressor.  
Ta  
L(W5)  
(W5+W3) / 2  
+
+
1.0  
0.5  
SL (W3)  
Tsc  
Fan speed  
27 –  
Item  
Operation flow and applicable data, etc.  
<In cooling operation>  
Description  
* Symbols  
2. Indoor fan  
motor control  
(This operation controls the fan speed at indoor unit side.)  
The indoor fan (cross flow fan) is operated by the phase-  
control induction motor. The fan rotates in 5 stages in  
MANUAL mode, and in 5 stages in AUTO mode, respec-  
tively. (Table 1)  
UH  
H
M+  
M
L+  
L
: Ultra High  
: High  
: Medium+  
: Medium  
: Low+  
: Low  
L-  
UL  
SUL  
: Low–  
: Ultra Low  
: Super Ultra Low  
COOL ON  
Fan speed setup  
AUTO  
MANUAL  
* The fan speed broadly varies due  
to position of the louver, etc.  
The described value indicates one  
under condition of inclining  
downward blowing.  
(Fig. 1)  
Indication  
Fan speed  
W6  
L
1) When setting the fan speed to L,  
L+, M, M+ or H on the remote  
controller, the operation is  
performed with the constant  
speed shown in Fig. 1.  
L+  
M
(L + M) / 2  
W9  
M+  
H
(M + H) / 2  
WC  
2) When setting the fan speed to  
AUTO on the remote controller,  
revolution of the fan motor is  
controlled to the fan speed level  
shown in Fig. 2 and Table 1  
(Fig. 2)  
Air volume AUTO  
according to the setup tempera-  
ture, room temperature, and heat  
exchanger temperature.  
Ta  
˚C  
[
]
M+(WB)  
+2.5  
+2.0  
a
b
c
d
e
*3  
*4  
*5  
*3 :Fan speed = (M + L) x 3/4 + L  
*4 :Fan speed = (M + L) x 2/4 + L  
*5 :Fan speed = (M + L) x 1/4 + L  
+1.5  
+1.0  
+0.5  
Tsc  
(Linear approximation  
from M+ and L)  
L(W6)  
(Table 1) Indoor fan air flow rate  
RAS-B10GKVP-E  
RAS-B13GKVP-E  
RAS-B16GKVP-E  
Fan speed  
level  
COOL HEAT DRY  
Fan speed Air flow rate Fan speed Air flow rate Fan speed Air flow rate  
(rpm)  
(m3/h)  
(rpm)  
(m3/h)  
(rpm)  
(m3/h)  
WF  
WE  
WD  
WC  
WB  
WA  
W9  
W8  
W7  
W6  
W5  
W4  
W3  
W2  
W1  
UH  
H
M+  
1630  
1480  
1400  
1350  
1200  
1110  
980  
910  
900  
890  
880  
684  
609  
569  
544  
468  
423  
358  
323  
318  
313  
308  
232  
157  
82  
1650  
1530  
1440  
1390  
1240  
1150  
1010  
910  
900  
890  
880  
730  
694  
634  
589  
564  
488  
443  
373  
323  
318  
313  
308  
232  
157  
82  
1650  
1580  
1550  
1530  
1380  
1230  
1080  
970  
960  
950  
940  
790  
694  
659  
644  
634  
559  
483  
408  
353  
348  
343  
338  
263  
187  
112  
67  
UH  
H
M+  
M
L+  
L
M
L+  
L
L–  
UL  
SUL  
L–  
L+  
L
L–  
UL  
SUL  
UL  
730  
580  
430  
400  
580  
430  
400  
640  
490  
400  
SUL  
67  
67  
28 –  
Item  
Operation flow and applicable data, etc.  
Description  
2. Indoor fan  
motor control  
<In heating operation>  
1) When setting the fan speed to L,  
L+, M, M+ or H on the remote  
controller, the operation is per-  
formed with the constant speed  
shown in Fig. 3 and Table 1.  
HEAT ON  
2) When setting the fan speed to  
AUTO on the remote controller,  
revolution of the fan motor is  
Fan speed setup  
MANUAL  
(Fig. 3)  
controlled to the fan speed level  
shown in Fig. 5 according to the set  
temperature and room temperature.  
Indication  
Fan speed  
W8  
3) Min air flow rate is controlled by  
temperature of the indoor heat  
exchanger (Tc) as shown in Fig. 4.  
L
L+  
M
(L + M) / 2  
WA  
AUTO  
4) Cold draft prevention, the fan  
speed is controlled by temperature  
of the indoor heat exchanger (Tc)  
as shown in Fig. 6.  
M+  
H
(M + H) / 2  
WE  
YES  
TC 42˚C  
Min air flow rate control  
NO  
Limited to Min WD tap  
Tc  
52  
51  
42  
41  
*
No limit  
*Fan speed =  
(TC
–  
W8) + W8  
(Fig. 4)  
Cold draft preventive control  
Tc  
46  
45  
[
]
C
TA  
b
c
d
e
f
46  
45  
34  
TSC  
0.5  
1.0  
1.5  
2.0  
2.5  
5.0  
5.5  
L (W8)  
33  
33  
32  
33  
32  
21  
20  
*1  
*2  
*A+4  
*A-4  
*A+4  
*A-4  
*A+4  
*A-4  
*3  
g
Fan speed MANUAL in starting  
Fan speed AUTO in stability  
Fan speed AUTO in starting  
M+ (WD)  
H (WE)  
*1:  
*2:  
4 + L  
4 + L  
(Fig. 5)  
[In starting and in stability]  
(Fig. 6)  
In starting  
In stability  
Until 12 minutes passed after operation start  
FAN AUTO When 12 to 25 minutes passed after operation  
When 12 to 25 minutes passed after operation start  
and room temp. is higher than (set temp. 3°C)  
start and room temp. is 3°C or lower than set temp. When 25 minutes or more passed after operation start  
FAN Manual Room temp. < Set temp. 4°C Room temp. Set temp. 3.5°C  
29 –  
Item  
Operation flow and applicable data, etc.  
Description  
3. Outdoor fan  
motor control  
The blowing air volume at the outdoor unit side is controlled. 1) The operation command sent  
from the remote controller is  
Receiving the operation command from the controller of  
indoor unit, the controller of outdoor unit controls fan speed.  
processed by the indoor unit  
controller and transferred to the  
controller of the outdoor unit.  
* For the fan motor, a DC motor with non-stage variable  
speed system is used. However, it is limited to 8 stages for  
reasons of controlling.  
2) When strong wind blows at  
outdoor side, the operation of air  
conditioner continues with the  
fan motor stopped.  
Air conditioner ON  
(Remote controller)  
3) Whether the fan is locked or not  
is detected, and the operation of  
air conditioner stops and an  
alarm is displayed if the fan is  
locked.  
Indoor unit controller  
4) According to each operation  
mode, by the conditions of  
outdoor temperature (To) and  
compressor revolution, the speed  
of the outdoor fan shown in the  
table is selected.  
1) Outdoor unit  
operation command  
(Outdoor fan control)  
YES  
YES  
OFF status of  
2) Fan speed 400  
fan motor continues.  
when the motor stopped.  
NO  
Fan motor ON  
Air conditioner  
OFF  
Alarm  
display  
3) Fan lock  
NO  
4) Motor operates as shown in the table below.  
In cooling operation  
In Heating operation  
~ 13.8  
~ 31.7  
32.3 ~ MAX  
Compressor speed (rps) ~16.8 ~47.9 48.5 ~ MAX  
Compressor speed (rps)  
>
MIN MAX MIN MAX MIN MAX  
To 15°C  
f 3  
f 3  
f 8  
f B  
f 3  
f 3  
f 5  
f 7  
f A  
f 8  
f 9  
f A  
f C  
f 3  
f 3  
f 9  
f A  
f B  
f 9  
f A  
f D  
f D  
f 6  
f 8  
f 9  
f B  
f D  
>
To 38°C  
f 2  
f 2  
f 2  
f 2  
f 1  
f 2  
f 2  
f 3 f C f D f E f F  
f 3 f B f C f E f F  
To < 15°C  
To < 5.5°C  
To < 5.0°C  
To  
>
To 28°C  
>
To  
To 15°C  
f 3  
f 3  
f 2  
f 8  
f 6  
f 4  
f 9 f A f B  
>
>
To 5.5°C  
f 7  
f 5  
f 8  
f 6  
f 9  
f 7  
To 15°C  
>
To 0°C  
To < 15°C  
To < 5.5°C  
To < 5.5°C  
During  
ECO mode  
>
To 38°C  
f 3 f B f C f C f D  
f 3 f 2 f 3 f B f C  
During  
ECO mode  
To < 38°C  
When To is abnormal  
f D f F f D f F f D f F  
When To is abnormal  
Outdoor fan speed (rpm)  
Tap  
f 1  
f 2  
f 3  
f 4  
f 5  
f 6  
f 7  
f 8  
10GAVP-E  
200  
13GAVP-E  
200  
16GAVP-E  
200  
Tap  
f 9  
10GAVP-E  
700  
13GAVP-E  
700  
16GAVP-E  
700  
300  
300  
300  
f A  
f B  
f C  
f D  
f E  
f F  
700  
700  
700  
390  
390  
390  
700  
700  
700  
450  
450  
450  
700  
700  
700  
500  
500  
500  
750  
840  
920  
500  
500  
500  
750  
840  
920  
600  
600  
600  
750  
840  
920  
600  
600  
600  
30 –  
Item  
Operation flow and applicable data, etc.  
Description  
4. Capacity  
control  
The cooling or heating capacity depending on the load is  
adjusted.  
1) The difference between set  
temperature on remote controller  
(Ts) and room temperature (Ta)  
is calculated.  
According to difference between the setup value of tempera-  
ture and the room temperature, the capacity is adjusted by  
the compressor revolution.  
2) According to the temperature  
difference, the correction value of  
Hz signal which determines the  
compressor speed is set up.  
Remote controller  
Set temp. (Ts)  
Indoor unit  
Room temp. (Ta)  
3) The rotating position and speed  
of the motor are detected by the  
electromotive force occurred on  
the motor winding with operation  
of the compressor.  
Ts Ta  
4) According to the difference  
resulted from comparison of the  
correction value of Hz signal with  
the present operation Hz, the  
inverter output and the commuta-  
tion timing are varied.  
Correction of Hz signal  
Detection of electromotive force  
of compressor motor winding  
5) Change the compressor motor  
speed by outputting power to the  
compressor.  
Detection of motor speed and rotor position  
* The contents of control  
operation are same in cooling  
operation and heating  
operation  
Correction value of Hz signal Operating Hz  
Inverter output change  
Commutation timing change  
Change of compressor speed  
5. Current release This function prevents troubles on the electronic parts of the 1) The input current of the outdoor  
control  
compressor driving inverter.  
unit is detected in the inverter  
section of the outdoor unit.  
This function also controls drive circuit of the compressor  
speed so that electric power of the compressor drive circuit  
does not exceed the specified value.  
2) According to the detected  
outdoor temperature, the  
specified value of the current is  
selected.  
Outdoor temp. To  
Outdoor unit inverter main  
3) Whether the current value  
exceeds the specified value or  
not is judged.  
circuit control current  
Setup of current release point  
4) If the current value exceeds the  
specified value, this function  
reduces the compressor speed  
and controls speed up to the  
closest one commanded from the  
indoor unit within the range  
which does not exceed the  
specified value.  
High  
Operating current ≤  
Reduce compressor speed  
Current decrease  
Setup value  
Low  
Capacity control continues.  
Cooling current  
release value  
Heating current  
release value  
Outdoor temp.  
6.45A  
6.75A  
45˚C  
40˚C  
16˚C  
11˚C  
44˚C  
39˚C  
7.72A  
15.5˚C  
10.5˚C  
8.47A  
9.22A  
10.80A  
31 –  
Item  
Operation flow and applicable data, etc.  
Description  
6. Release protective  
control by tempera-  
ture of indoor heat  
exchanger  
<In cooling/dry operation>  
1) When temperature of the indoor  
heat exchanger drops below 5°C,  
the compressor speed is  
(Prevent-freezing control for indoor heat exchanger)  
In cooling/dry operation, the sensor of indoor heat  
exchanger detects evaporation temperature and  
controls the compressor speed so that temperature of  
the heat exchanger does not exceed the specified  
value.  
reduced. (P zone)  
2) When temperature of the indoor  
heat exchanger rises in the  
range from 6°C to under 7°C, the  
compressor speed is kept.  
(Q zone)  
Usual cooling capacity control  
3) When temperature of the indoor  
heat exchanger rises to 7°C or  
higher, the capacity control  
operation returns to the usual  
control in cooling operation.  
(R zone)  
R
When the value is  
7˚C  
6˚C  
5˚C  
in Q zone, the  
Q
compressor speed  
is kept.  
P
Reduction of compressor speed  
<In heating operation>  
1) When temperature of the indoor  
heat exchanger rises in the  
range from 50°C to 55°C, the  
compressor speed is kept.  
(Q zone)  
(Prevent-overpressure control for refrigerating cycle)  
In heating operation, the sensor of indoor heat ex-  
changer detects condensation temperature and controls  
the compressor speed so that temperature of the heat  
exchanger does not exceed the specified value.  
When temperature of the indoor  
heat exchanger drops in the  
range from 46°C to under 55°C,  
the compressor speed is kept.  
(Q zone)  
Reduction of compressor speed  
P
2) When temperature of the indoor  
heat exchanger rises to 55°C or  
higher, the compressor speed is  
reduced. (P zone)  
55˚C  
When the value is  
50˚C  
Q
3) When temperature of the indoor  
heat exchanger does not rise to  
50°C, or when it drops below to  
46°C, the capacity control  
operation returns to the usual  
control in heating operation.  
(R zone)  
in Q zone, the  
compressor speed  
is kept.  
46˚C  
R
Usual heating capacity control  
32 –  
Item  
Operation flow and applicable data, etc.  
Description  
7. Quick heating  
control  
This function quickens the starting of heating opera-  
tion when indoor/outdoor temperature is low.  
(Available only in heating operation)  
When the following conditions are  
satisfied, winding is heated by output  
varied by the outdoor heat exchanger  
temperature.  
When indoor temperature is low, this function stores  
the heat by heating winding depended on the outdoor  
temperature and then it enables the hot air blowing  
out quickly.  
Condition 1 :  
The previous operation was heating.  
Condition 2 :  
In case of operation stop  
2 hours passed after operation stop.  
Condition 3 :  
The room temperature is 20°C or lower.  
NO  
The previous operation was heating and  
2 hours passed after the operation had stopped.  
The indoor temperature sensor detects  
the room temperature.  
YES  
If the detected room temperature is 20°C  
or lower, the outdoor heat exchanger  
temperature sensor detects the outdoor  
heat exchanger temperature. As shown in  
the left figure, winding of the compressor  
is heated for each division of the tempera-  
ture ( for each outdoor temperature) and  
the heat is stored.  
Winding is not heated.  
20˚C  
Heating output for winding  
OFF  
1˚C  
3˚C  
20W or equivalent  
20W or equivalent  
6˚C  
8˚C  
8. Defrost control  
(This function removes frost adhered to the outdoor  
The necessity of defrost operation is  
detected by the outdoor heat exchanger  
temperature. The conditions to detect the  
necessity of defrost operation differ in A,  
B, or C zone each. (Table 1)  
(Only in heating heat exchanger.)  
operation)  
The temperature sensor of the outdoor heat ex-  
changer (Te sensor) judges the frosting status of the  
outdoor heat exchanger and the defrost operation is  
performed with 4-way valve reverse defrost system.  
<Defrost operation>  
Defrost operation in A to C zones  
1) Stop operation of the compressor for  
20 seconds.  
Start of heating operation  
2) Invert (ON) 4-way valve 10 seconds  
after stop of the compressor.  
Operation time  
(Minute)  
01015’  
2740”  
34’  
3) The outdoor fan stops at the same time  
when the compressor stops.  
5˚C  
4) When temperature of the indoor heat  
exchanger becomes 38°C or lower,  
stop the indoor fan.  
C zone  
7˚C  
<Finish of defrost operation>  
A zone  
Returning conditions from defrost  
operation to heating operation  
20˚C  
B zone  
1) Temperature of outdoor heat exchanger  
*
rises to +8°C or higher.  
2) Temperature of outdoor heat exchanger  
* The minimum value of Te sensor 10 to 15 minutes  
after start of operation is stored in memory as Te0.  
is kept at +5°C or higher for 80 seconds.  
3) Defrost operation continues for  
15 minutes.  
Table 1  
<Returning from defrost operation>  
1) Stop operation of the compressor for  
approx. 50 seconds.  
When Te0 - TE 2.5 continued for 2 minutes in A zone,  
A zone  
defrost operation starts.  
When the operation continued for 2 minutes in B zone,  
defrost operation starts.  
2) Invert (OFF) 4-way valve approx. 40  
seconds after stop of the compressor.  
B zone  
C zone  
When Te0 - TE 3 continued for 2 minutes in C zone,  
defrost operation starts.  
3) The outdoor fan starts rotating at the  
same time when the compressor starts.  
33 –  
Item  
Operation flow and applicable data, etc.  
Description  
9. Louver control  
This function controls the air direction of the indoor unit.  
1) Louver  
position  
The position is automatically controlled according to the operation mode (COOL/HEAT).  
The set louver position is stored in memory by the microcomputer, and the louver returns to the  
stored position when the next operation is performed. (Cooling/heating memory position)  
The angle of the louver is indicated as the horizontal angle is 0°.  
When the louver closes fully, it directs approx. 49° upward.  
Horizontal  
(0˚)  
Louver angle  
1) Louver position in cooling operation  
Powerful  
Room temp. (Ta) < Set temp. (Tsc) + 3.5 Room temp. (Ta) Set temp. (Tsc) + 3.5  
Initial setting of Cooling storage positionInitial setting of Cooling storage position” “Inclined blowing”  
Louver : Directs downward (9˚)  
Louver : Directs downward (9˚)  
Louver : Directs downward (14˚)  
YES  
NO  
Powerful  
operation  
Cooling memory  
Cooling/AUTO  
(COOL)/DRY operation  
Room temp. ≥  
Set temp. +3.5  
position  
NO  
Room temp. Set temp. +3.5  
YES  
NO  
YES  
Cooling memory  
position  
Inclined  
blowing  
2) Louver position in heating operation  
ECO operation  
Heating operation/  
AUTO (HEAT)  
Room temp. (Ta) < Set temp. (Tsc) 3  
Room temp. (Ta) Set temp. (Tsc) 3  
or 25 minutes after start of operation  
Initial setting of Heating storage position” “Heating storage position”  
Cooling storage position”  
Louver : Directs downward (9˚)  
Louver : Directs downward (76˚)  
Louver : Directs downward (76˚)  
YES  
NO  
ECO  
operation  
Room temp. ≥  
Set temp. 3.0  
Horizontal  
position  
Heating operation  
NO  
Room temp. Set temp. 3.0  
YES  
NO  
YES  
Heating memory  
position  
Heating memory  
position  
2) Air direction adjustment  
The louver position can  
be arbitrarily set up by  
pressing [FIX] button.  
Air direction  
Horizontal  
blowing  
Inclined  
blowing  
Blowing  
downward  
Inclined  
blowing  
Horizontal  
blowing  
3) Swing  
Swing operation is performed in width 35° with the stop position as  
Swing  
the center.  
When pressing  
[SWING] button during  
operation, the louver  
starts swinging.  
If the stop position exceeds either upper or lower limit position,  
swing operation is performed in width 35° from the limit which the  
stop position exceeded.  
34 –  
Item  
Operation flow and applicable data, etc.  
Description  
10. ECO  
When pressing [ECO] button on the remote controller, a quiet  
operation and mild operation is performed by reducing the fan speed and  
the compressor speed.  
<Cooling operation>  
<Cooling operation>  
This function operates the air conditioner with the difference  
between the set and the room temperature as shown in the  
following figure.  
1) The room temperature (Tao) at  
the start time of DRY operation is  
detected.  
The time correction is performed for 8 minutes each.  
(However, the first correction is performed 150 seconds after  
start of the operation.)  
2) According to difference between  
the room temperature and the  
set temperature (Tsc), the  
operation starts with the condi-  
tions shown in the left figure.  
Set temp.  
Zone  
12  
11  
10  
9
Frequency  
DRY max  
Fan  
L+ (W7)  
Time correction  
TA  
[˚C]  
(Tsc) = Set temp. on remote  
controller (Ts) + (0.0 to 1.0)  
*12  
*11  
*10  
+4.0  
+3.5  
+3.0  
+2.5  
+2.0  
+1.5  
+1.0  
+0.5  
TSC  
0.5  
1.0  
3) If the room temperature is down  
by 2°C or more, turn off the  
compressor.  
+ 1  
L (W6)  
8
*9  
7
*8  
6
5
4
3
2
1
COOL min  
L(W5)  
± 0  
UL (W4)  
1 zone: min 1  
2.0  
0
OFF  
* 12 (DRY max - COOL min) /6 x 5 + COOL min  
* 11 (DRY max - COOL min) /6 x 4 + COOL min  
* 10 (DRY max - COOL min) /6 x 3 + COOL min  
* 9 (DRY max - COOL min) /6 x 2 + COOL min  
* 8 (DRY max - COOL min) /6 x 1 + COOL min  
<Heating operation>  
<Heating operation>  
1) The indoor fan speed is con-  
trolled within (W7) as maximum  
value.  
30 minutes  
Time Compressor  
speed  
0Hz  
2) Setting the compressor speed to  
Max. 52Hz, the temperature zone  
in which the operation can be  
performed with Max. 16Hz is  
gradually widened after 30  
minutes passed when starting  
ECO operation.  
0
0.5  
1.0  
1.5  
2.0  
2.5  
3.0  
4.0  
5.0  
6.0  
7.0  
8.0  
9.0  
A
B
A
A zone  
16Hz  
3) The louver position is set  
horizontally (Standard cooling  
position) when the room tem-  
perature comes close to the set  
temperature or when 25 minutes  
passed after starting ECO  
operation.  
B zone  
16 to 52Hz  
B
C
C
10.0  
11.0  
C zone  
52Hz  
35 –  
Item  
Operation flow and applicable data, etc.  
Description  
11. Temporary Pressing [RESET] button starts the temporary opera-  
1) When pressing [RESET] button, the  
temporary [AUTO] operation starts.  
operation  
tion of [AUTO] operation. When keeping [RESET]  
button pressed for 10 seconds or more, the temporary  
[COOL] operation is performed.  
2) When keeping [RESET] button pressed  
for 3 seconds or more, Pi, Pi, Pi sound is  
heard and [AUTO RESTART] control is  
changed.  
YES  
3) When keeping [RESET] button pressed  
for 10 seconds or more, Pisound is  
heard and the temporary [COOL]  
operation starts.  
Press RESET button.  
Filter lamp ON  
NO  
NO  
Did you press [RESET] button  
for 3 seconds or more?  
Temporary [AUTO] operation  
4) If the filter lamp goes on, press [RESET]  
button to go off the filter lamp, and then  
press [RESET] button again.  
YES  
YES  
Did you press [RESET] button  
for 10 seconds or more?  
5) To stop the temporary operation, press  
the button again.  
NO  
Switch to [AUTO RESTART] control.  
Temporary [COOL] Operation  
12. Air  
purifying  
This function generates nagative ion while cleaning the air in the room.  
If air purifier-ON signal is received while the air conditioner stops, the air purifier starts operation,  
and if it is received while the air conditioner operates, the air conditioner and the air purifier start  
operation.  
control  
The air ion generator operates linked with the air purifying operation.  
* When the previous operation was the  
operation of air conditioner + air purifier,  
Operation button  
Present status  
Stop  
PURE button  
Air purifier  
Air conditioner  
AC operation*  
AC + Air purifier  
All stop  
an operation of air conditioner + air purifier  
starts by pushing AC button on the remote  
controller.  
(Operation of air conditioner + air purifier  
is stored in memory.)  
Air purifier only  
Air conditioner  
Joint use of AC and air purifier  
Stop (All)  
AC + Air purifier  
AC operation  
All stop  
*1 Swing is available  
Louver*1  
Fan speed *2  
*2 Fan speed is Fan Auto mode varies in  
order, (M + 1) (L) (L) (SL).  
Air purifying operation  
Cooling position  
AUTO, L, L+, M, M+, H  
AC + Air purifying operation Follows to AC operation Follows to AC operation  
Sending air purifier-ON  
Sending air purifier-OFF  
1
2
1
2
3
4
3
4
,
,
Air conditioner stops  
Air conditioner operates  
Air purifier operates  
Air conditioner +  
Air purifier operate  
Operation lamp ON  
Start of air purifier-ON  
Operation lamp OFF  
Fan stop  
Filter-OFF  
*1  
*2  
Memory position  
of louver/COOL  
Air conditioner +  
air purifier operate  
Air conditioner operates  
Air purifier-OFF  
Louver close  
All stop  
Fan ON  
Air purifier ON  
Air purifying operation  
36 –  
Item  
Operation flow and applicable data, etc.  
Description  
1. Purpose  
12. Air purifying control [Detection of abnormality]  
Purifying operation  
The air purifying control function is to  
alert the user to trouble in the ionizing or  
air purifying operation.  
2. Description  
Trouble is determined to have occurred  
(indicated by the FILTER indicator) in the  
following four cases.  
YES  
Total operation  
time 1000H  
NO  
1) When a count of 1000H has been  
reached on the timer  
Purifier power ON  
2) When the panel switch has been set to  
OFF by the opening of the air inlet  
grile, etc.  
NO  
Error input  
3) When an abnormal discharge caused  
by a symptom such as the build-up of  
dirt has been detected while the air  
purifier is ON  
YES  
NO  
Purifier power ON  
1 minute or less  
Filter lamp-OFF  
continues.  
YES  
4) When the electric dust collector has  
not been installed correctly  
Purifier power OFF  
Filter lamp ON  
* Trouble case (2) or (3) is deemed to  
have occurred when the action  
concerned continues for more than  
one second.  
Purifier power ON  
after 10 minutes  
from the error input.  
Purifier power OFF  
3. Operation  
The sequence that FILTER indicator is  
turned on are described in the left  
flowchart.  
NO  
Filter lamp ON  
Error input  
YES  
1) When 1000H timer counts up, the  
FILTER indicator keeps lighting even if  
the operation is stopped by the remote  
controller.  
Purifier power OFF  
Purifier power OFF  
1
The timer is stored in memory of the  
microcomputer, and the operation time  
is cleared by filter RESET button on  
the indoor unit or a power failure.  
(FILTER indicator goes off.)  
2
3
1) Reset by RESET button.  
2) Reset by RESET button or by the stop direction  
from the remote controller.  
2) A trouble detected within 1 minute  
after activation of the air is immedi-  
ately judged as an error and the  
FILTER indicator goes on.  
* When the breaker is turned [ON] (In restart time  
after power failure) or RESET button is pressed  
while the FILTER indicator is turned on, the air  
purifier is not turned on until the integrated  
operation time of the indoor fan exceeds 1 hour  
after operation start (It is nor the air purifier  
operation time).  
It is the safety measures considering an incom-  
plete drain when electric dust collector has been  
cleaned with water.  
3) In case that 1 minute passed after  
activation of the purifier, the purifier is  
turned off while the PURE indicator  
keeps ON. After 10 minutes passed,  
restart the purifier and an error is  
judged again.  
13. Discharge temperature control  
1. Purpose  
This function detects error on the  
refrigerating cycle or error on the com-  
pressor, and performs protective control.  
Td value  
Control operation  
Judges as an error and stops the compressor.  
Reduce the compressor speed.  
117°C  
112°C  
108°C  
105°C  
2. Operation  
Reduce slowly compressor speed.  
Keeps the compressor speed.  
Control of the compressor speed  
The speed control is performed as  
described in the left table based upon  
the discharge temperature.  
If the operation is performed with lower speed than one  
commanded by the serial signal, speed is slowly raised  
up to the commanded speed.  
98°C  
Operates with speed commanded by the serial signal.  
37 –  
Item  
Operation flow and applicable data, etc.  
Description  
14. Pulse motor  
valve (P.M.V.)  
control  
This function controls throttle amount of the  
refrigerant in the refrigerating cycle.  
1) When starting the operation, move the  
valve once until it fits to the stopper.  
(Initialize)  
According to operating status of the air conditioner,  
this function also controls the open degree of valve  
with an expansion valve with pulse motor.  
* In this time, Clicksound may be  
heard.  
2) Adjust the open degree of valve by super  
heat amount. (SH control)  
3) If the discharge temperature was exces-  
sively up, adjust the open degree of valve  
so that it is in the range of set tempera-  
ture.  
Starting up  
Initialize  
(Discharge temp. control)  
4) When defrost operation is performed, the  
open degree of valve is adjusted accord-  
ing to each setup conditions during  
preparation for defrost and during defrost  
operation (4-way valve is inversed.).  
Move to  
initial position  
5) To turn off the compressor while the air  
conditioner stops by control of the  
Compressor ON  
thermostat or by remote controller, adjust  
the open degree of valve to the setup  
value before stop of the compressor.  
Td  
SH control  
release control  
PMV open degree control  
Stop by  
remote controller  
Room temp. sensor  
(Ta sensor) control  
Power OFF  
Defrost  
* SH (Super Heat amount) =  
Ts (Temperature of suction pipe of the compressor) –  
Tc or Te (Heat exchanger temperature at evaporation side)  
* PMV: Pulse Motor Valve  
38 –  
Item  
Operation flow and applicable data, etc.  
Description  
15. Clean operation  
1. Purpose  
The clean operation is to minimize the  
growth of mold, bacteria etc. by running  
the fan and drying so as to keep the  
inside of the air conditioner clean.  
Unit now performing cooling or dry operation  
Clean operation  
When the cooling or dry operation shuts  
down, the unit automatically starts the  
clean operation which is then performed  
for the specified period based on duration  
of the operation which was performed  
prior to the shutdown, after which the  
clean operation stops.  
Press STOPbutton  
Only S.CLEAN indicator lights, and clean operation starts  
(The clean operation is not performed  
after a heating operation.)  
2. Operation  
Time set now elapses  
Operation stops  
1) When the stop signal from the remote  
controller is received, the S.CLEAN  
indicator (green) on the main body  
lights, and the clean operation starts.  
(Neither the OPERATION indicator nor  
the TIMER indicator light.)  
2) The period of the clean operation is  
determined by the duration of the  
operation performed prior to the  
reception of the stop code.  
During clean operations: The louver opens  
slightly. The indoor fan operates continuously at  
a speed of 260 rpm.  
3) After the clean operation has been  
performed for the specified period, the  
unit stops operating.  
Clean operation times  
Operation mode  
Operation time  
Clean operation time  
No clean operation  
performed (0 minutes)  
Up to 10 minutes  
Cooling: Auto (cooling) Dry From 10 minutes up  
to 1 hour  
2 hours  
4 hours  
1 hour or longer  
Heating: Auto (heating)  
Auto (fan only)  
Shutdown  
No clean operation performed  
To stop an ongoing clean operation at any time  
Press the start/stop button on the remote controller twice during the clean  
operation. (After pressing the button for the first time, press it for the  
second time without delay (within 10 minutes).)  
39 –  
Item  
Operation flow and applicable data, etc.  
Description  
16. Clean operation Setting the clean operation release  
release  
* J04 will be near the MCU so take  
steps to ensure that it will not be  
exposed to excessive levels of  
heat.  
Add J04 of the indoor P.C. board assembly.  
* This cancels the auto restart function.  
Also take care to avoid solder  
bridging with the surrounding  
components.  
Hold down the auto operation switch on the indoor unit  
for at least 3 seconds but not more than 10 seconds.  
The indoor units buzzer emits three beeps, and  
the OPERATION indicator flashes at 5 Hz intervals.  
This completes the clean operation release setting.  
Setting the clean operation  
Cut J04 of the indoor P.C. board  
* This step may be skipped if the auto restart function  
is not required.  
Hold down the auto operation switch on the indoor unit  
for at least 3 seconds but not more than 10 seconds.  
The indoor units buzzer emits three beeps, and  
the OPERATION indicator flashes at 5 Hz intervals.  
This completes the clean operation setting.  
Indoor P.C. board  
J04  
40 –  
Item  
Operation flow and applicable data, etc.  
Description  
17. Select switch on  
remote controller  
1. Purpose  
This operation is to operate only one  
indoor unit using one remote controller.  
2. Description  
Press the operation button  
on the remote controller.  
When operating one indoor unit in a  
situation where two indoor units have  
been installed in the same room or  
nearby rooms, this operation prevents the  
remote controller signal from being  
received simultaneously by both units,  
thus preventing both units from operating.  
Select Bas the setting for  
one of the two indoor units and  
for the remote controller.  
(See below for details.)  
YES  
Both indoor units  
start operation.  
3. Operation  
NO  
The indoor unit on which the remote  
controller selection has been set to B  
receives the signal of the remote control-  
ler also set to B.  
(At the factory the remote controller  
selection is set to A on all the indoor  
units. There is no A setting display.)  
Unnecessary set  
[Remote controller select]  
Setting the remote controller  
Switching between A and B is enabled by cutting the jumper wire  
inside the battery box using pliers.  
1) Slide open the remote controller cover and remove the  
batteries.  
HiPOWER  
ECO  
MEMO  
2) Cut the jumper wire inside the battery compartment using  
nippers.  
.
.
.
1 3 5 9H  
SWING  
CLR  
FIX  
FAN  
SLEEP  
Jumper wire  
The jumper wire should not remain in contact after being cut.  
Also, be careful not to let plastic scraps, jumper wire cuttings  
or other debris enter the inside of the remote controller.  
SET  
ON  
OFF  
CLOCK  
RESET  
CHECK  
3) Insert the batteries. Bappears in the remote controller  
display.  
* Even after the jumper wire has been cut, switching between  
A and B is still possible by pressing the CHECK button and  
FIX button together.  
The A or B setting, which was switched by pressing the  
CHECK button and FIX button together, is restored to the  
setting established prior to the switching when the battery is  
replaced or the RESET button is pressed.  
Setting the selector switch on the main unit  
Remove the front panel, and then set the selector switch to B.  
After making the switch setting, remount the front panel.  
Cutting direction  
Position of remote controller selector switch  
When switching between  
settings Aand B, always  
switch the indoor unit board and  
the remote controller as a pair.  
(Otherwise, the indoor unit will  
not accept the remote  
controllers signals.)  
Selector switch  
41 –  
9-3. Auto Restart Function  
This indoor unit is equipped with an automatic restarting function which allows the unit to restart operating with  
the set operating conditions in the event of a power supply being accidentally shut down.  
The operation will resume without warning three minutes after power is restored.  
This function is not set to work when shipped from the factory. Therefore it is necessary to set it to work.  
9-3-1. How to Set the Auto Restart Function  
To set the auto restart function, proceed as follows:  
The power supply to the unit must be on ; the function will not set if the power is off.  
Press the [RESET] button located in the center of the front panel continuously for three seconds.  
The unit receives the signal and beeps three times.  
The unit then restarts operating automatically in the event of power supply being accidentally shut down.  
• When the unit is standby (Not operating)  
Operation  
Motions  
Press [RESET] button for more than  
three seconds. (Less than 10 seconds)  
The unit is on standby.  
The unit starts to operate.  
The green indicator is on.  
After approx. three seconds,  
The unit beeps three times  
and continues to operate.  
The green indicator flashes  
for 5 seconds.  
If the unit is not required to operate at this time, press [RESET]  
button once more or use the remote controller to turn it off.  
• When the unit is in operation  
Operation  
Motions  
Press [RESET] button for more than  
three seconds. (Less than 10 seconds)  
The unit is in operation.  
The green indicator is on.  
The unit stops operating.  
The green indicator is turned off.  
After approx. three seconds,  
The unit beeps three times.  
The green indicator flashes  
for 5 seconds.  
If the unit is required to operate at this time, press [RESET] button  
once more or use the remote controller to turn it on.  
When the unit is turned on by this function, the louver will not swing even though it was swinging automatically  
before shutting down.  
While the filter check indicator is on, the RESET button has the function of filter reset button.  
42 –  
9-3-2. How to Cancel the Auto Restart Function  
To cancel auto restart function, proceed as follows :  
Repeat the setting procedure : the unit receives the signal and beeps three times.  
The unit will be required to be turned on with the remote controller after the main power supply is turned off.  
• When the system is on stand-by (not operating)  
Operation  
Motions  
Press [RESET] button for more than  
three seconds. (Less than 10 seconds)  
The unit is on standby.  
The unit starts to operate.  
The green indicator is on.  
After approx. three seconds,  
The unit beeps three times and continues to operate.  
If the unit is not required to operate at this time, press [RESET]  
button once more or use the remote controller to turn it off.  
• When the system is operating  
Operation  
Motions  
Press [RESET] button for more than  
three seconds. (Less than 10 seconds)  
The unit is in operation.  
The green indicator is on.  
The unit stops operating.  
The green indicator is turned off.  
After approx. three seconds,  
The unit beeps three times.  
If the unit is required to operate at this time, press [RESET] button  
once more or use the remote controller to turn it on.  
9-3-3. Power Failure During Timer Operation  
9-4. FILTER Indicator  
When the unit is turned off because of power failure  
during timer operation, the timer operation is can-  
celled. In that case, set the timer operation again.  
When the elapsed time reaches 1000 hours after air  
purifier operation, the FILTER indicator lights.  
After cleaning the filters, turn off the FILTER indicator.  
NOTE :  
The Everyday Timer is reset while a command signal  
can be received from the remote controller even if it  
stopped due to a power failure.  
9-4-1. How to Turn Off FILTER Indicator  
Press [RESET] button on the indoor unit.  
NOTE :  
If [RESET] button is pushed while the FILTER indica-  
tor is not lit, the indoor unit will start the automatic  
operation.  
When you want a temporary operation while the  
FILTER lamp lights, press [RESET] button to turn off  
the FILTER lamp. (See page 36)  
43 –  
9-5. Remote Controller and Its Fuctions  
9-5-1. Parts Name of Remote Controller  
11  
Cancel button (CLR)  
Press this button to cancel the ON timer and OFF  
timer. (A receiving beep is heard.)  
1
2
Infrared signal emitter  
Transmits signal to the indoor unit.  
button  
12  
13  
High power button (Hi POWER)  
Press this button to start high power operation.  
Press the button to start operation.  
(A receiving beep is heard.)  
Press the button again to stop operation.  
(A receiving beep is heard.)  
Memory button (MEMO)  
Press this button to ready for storing the settings.  
Hold down the button for more than 3 seconds to  
store the setting indicated on the remote controller  
If no receiving sound is heard from the indoor unit,  
press the button twice.  
and until the  
mark is displayed.  
3
Mode select button (MODE)  
Press this button to select a mode.  
14 Automatic operation button (AUTO)  
Each time you press the button, the modes cycle in  
order from A : Auto changeover control,  
Press this button to operate the air conditioner  
automatically. (A receiving beep is heard.)  
: Cool,  
: Dry,  
: Heat and back to A.  
15  
16  
17  
Economy button (ECO)  
Press this button to operate the air conditioner  
economically.  
(A receiving beep is heard.)  
TEMP  
4
5
Temperature button (  
)
.. The temperature setting is increased to 30°C.  
PRESET button  
Press this button to operate the air conditioner to  
the settings stored using the MEMO button.  
.. The temperature setting is reduced to 17°C.  
(A receiving beep is heard.)  
Fan speed button (FAN)  
Press this button to select the fan speed.  
When you select AUTO, the fan speed is automati-  
cally adjusted according to the room temperature.  
PURE button (PURE)  
Press this button to start the electrical air purifying  
operation.  
Press the button again to stop operation.  
You can also manually select the desired fan speed  
from five available settings.  
18  
Sleep time button (SLEEP)  
Press this button to start the sleep timer (OFF  
timer) operation.  
(LOW , LOW+  
HIGH  
, MED  
) (A receiving beep is heard.)  
, MED+  
,
6
Auto louver button (SWING)  
Press this button to swing the louver.  
(A receiving beep is heard.)  
You can select the OFF timer time from among four  
settings (1, 3, 5 or 9 hours).  
Press this button again to stop the louver from  
swinging. (A receiving beep is heard.)  
1
7
8
Set louver button (FIX)  
Press this button again to adjust the air flow  
direction. (A receiving beep is heard.)  
ON timer button (ON)  
Use this button to change the clock and ON timer  
times.  
ON  
To move up the time, press of the ON  
button.  
ON  
To move down the time, press of the ON  
button.  
4
AUTO  
PURE  
17  
14  
9
OFF timer button (OFF)  
Use this button to change the OFF timer times.  
MODE  
PRESET  
3
16  
5
OFF  
To move up the time, press of the OFF  
button.  
2
15  
13  
7
OFF  
To move down the time, press of the OFF  
button.  
HiPOWER  
ECO  
MEMO  
12  
SWING  
CLR  
FIX  
FAN  
SLEEP  
6
18  
10  
Reserve button (SET)  
Press this button to store the time settings.  
(A receiving beep is heard.)  
SET  
11  
10  
ON  
OFF  
CLOCK  
RESET  
CHECK  
9
8
44 –  
9-5-2. Name and Functions of Indications on Remote Controller  
[Display]  
All indications, except for the clock time indicator, are displayed by pressing the button.  
1
2
Transmission mark  
6
TIMER and clock time indicator  
The time setting for timer operation or the clock  
time is indicated.  
This transmission mark indicates when the  
remote controller transmits signals to the indoor  
unit.  
The current time is always indicated except  
during TIMER operation.  
Mode indicator  
Indicates the current operation mode.  
(AUTO : Automatic control, A : Auto changeover  
7
8
Hi-POWER indicator  
Indicates when the Hi-POWER operation starts.  
control,  
: Cool,  
: Dry,  
: Heat)  
Press the Hi-POWER button to start and press it  
again to stop the operation.  
3
4
5
Temperature indicator  
Indicates the temperature setting.  
(17°C to 30°C)  
(MEMORY) indicator  
Flashes for 3 seconds when the MEMO button is  
pressed during operation.  
PURE indicator  
Shows that the electrical air purifying operation is  
in progress.  
The  
mark is shown when holding down the  
button for more than 3 seconds while the mark is  
flashing.  
FAN speed indicator  
Indicates the selected fan speed.  
Press another button to turn off the mark.  
9
ECO indicator  
Indicates when the ECO is in activated.  
AUTO or five fan speed levels  
(
LOW , LOW+  
HIGH  
, MED  
, MED+  
,
Press the ECO button to start and press it again  
to stop operation.  
) can be shown.  
Indicates AUTO when the operating mode is  
10  
A, B change indicator remote controller  
either AUTO or  
: Dry.  
When the remote controller switching function is  
set, Bappears in the remote controller display.  
(When the remote controller setting is A, there is  
no indication at this position.)  
1
10  
2
3
8
4
AUTO  
In the illustration, all indications are shown for  
9 7  
5
6
purposes of explanation.  
During operation, only the relevant indicators are  
shown on the remote controller.  
45 –  
9-6. Hi-POWER Mode  
([Hi-POWER] button on the remote controller is pressed)  
When [Hi-POWER] button is pressed while the indoor unit is in Auto, Cooling or Heating operation, Hi-POWER  
mark is indicated on the display of the remote controller and the unit operates as follows.  
1. Automatic operation  
The indoor unit operates in according to the current operation.  
2. Cooling operation  
The preset temperature drops 1°C.  
(The value of the preset temperature on the remote controller does not change.)  
If the difference between the preset temperature and the room temperature is big, the horizontal louver  
moves to the Hi-POWER position automatically.  
Then when the difference between them gets smaller, the horizontal louver returns automatically.  
3. Heating operation  
The preset temperature increases 2°C.  
(The value of the preset temperature on the remote controller does not change.)  
4. The Hi-POWER mode can not be set in Dry operation  
46 –  
10. INSTALLATION PROCEDURE  
10-1. Safety Cautions  
For the rear left and left piping  
Wall  
Hook  
47 mm or more  
1
Installation plate  
Hook  
140 mm or more  
Insert the cushion between  
the indoor unit and wall, and  
tilt the indoor unit for better  
installation work.  
74 mm  
or more  
Hook  
7
Mounting screw  
Do not allow the drain hose  
to become slack.  
Cut the piping  
hole slightly  
sloped  
5
Zeolite-plus filter  
Z Shield pipe  
(for extension  
drain hose)  
Make sure the drain hose is  
sloped downward.  
6
Plasma pure filter  
The auxiliary piping can be  
connected at the left, rear left,  
rear right, right, bottom right or  
bottom left as shown below.  
Air filters  
Y
80 mm or more only  
when unobstructed to  
the front and both sides  
2
Wireless  
remote controller  
Right  
100 mm or more  
from wall  
50 mm or more  
from wall  
In principle,  
leave open  
Rear  
right  
Left  
Bottom right Rear left  
(C)  
Bottom left  
(D)  
4
Remote controller holder  
(Mounting holes on both  
left and right sides)  
As shown in the figure, position power cord and  
connecting cable downward, and lead out along  
piping connection port.  
200 mm  
or more  
(B)  
(A)  
8
Remote controller  
holder mounting screw  
Insulate the refrigerant pipes  
separately, not together.  
250 mm or more  
from wall  
When installing the outdoor unit,  
leave open in at least two of  
directions (A), (B), (C) and (D)  
shown in the right figure.  
Power cord  
Extension drain hose  
(Option: RB-821SW)  
Ensure sufficient space  
to allow drainage  
6 mm thick heat resisting  
polyethylene foam  
Before installing the wireless remote controller  
With the remote controller cover  
Cover  
removed, correctly load the  
supplied batteries while  
observing their polarity.  
3
Batteries  
2
Wireless remote controller  
47 –  
10-2. Optional Parts, Accessories andTools  
10-2-1. Optional Installation Parts  
Part Code  
Parts name  
Q’ty  
Refrigerant piping  
Liquid side (Outer diameter)  
6.35 mm  
Indoor unit name  
RAS-B10GKVP-E, B13GKVP-E  
RAS-B16GKVP-E  
Gas side (Outer diameter)  
9.52 mm  
1 ea.  
Y
Z
6.35 mm  
12.7 mm  
Shield pipe (for extension drain hose) (polyethylene foam, 6 mm thick)  
1
Attachment bolt arrangement of outdoor unit  
Elongated  
drain hole  
Secure the outdoor unit with the attachment bolts and  
nuts if the unit is likely to be exposed to a strong wind.  
Suction side  
( )  
Use Ø8 mm or Ø10 mm anchor bolts and nuts.  
If it is necessary to drain the defrost water, attach drain  
nipple to the base plate of the outdoor unit before  
installing it.  
Drain hole  
( )  
Diffuser  
10-2-2. Accessory and Installation Parts  
Part No.  
Part name (Q’ty)  
Installation plate × 1  
Wireless remote control × 1  
Battery × 2  
Part No.  
Part name (Q’ty)  
Part No.  
Part name (Q’ty)  

Š
Drain nipple* × 1  
(RAS-10GAVP-E,  
13GAVP-E, 16GAVP-E)  
Zeolite-plus filter × 1  
ƒ
ˆ
Water-proof rubber cap* × 2  
(RAS-10GAVP-E,  
13GAVP-E, 16GAVP-E)  
Plasma pure filter × 1  
Parts marked with asterisk (*) are  
packaged with the outdoor unit.  
<Others>  
Name  
Mounting screw Ø4 × 25L × 6  
Owners manual  
Installation manual  
Important information and warning*  
Remote control  
holder mounting screw  
Ø3.1 × 16L × 2  
Remote control holder × 1  
B/W strips*  
(Energy efficiency labels)  
This model is not equipped with an extension drain hose.  
48 –  
10-2-3. Installation/Servicing Tools  
Changes in the product and components  
In the case of an air conditioner using R410A, in order to prevent any other refrigerant from being charged  
accidentally, the service port diameter of the outdoor unit control valve (3 way valve) has been changed.  
(1/2 UNF 20 threads per inch)  
In order to increase the pressure resisting strength of the refrigerant piping flare processing diameter and size  
of opposite side of flare nuts has been changed. (for copper pipes with nominal dimensions 1/2 and 5/8)  
New tools for R410A  
New tools for R410A  
Applicable to R22 model  
Changes  
As pressure is high, it is impossible to measure by means of  
conventional gauge. In order to prevent any other refrigerant from  
being charged, each port diameter has been changed.  
Gauge manifold  
×
In order to increase pressure resisting strength, hose materials  
and port size have been changed (to 1/2 UNF 20 threads per inch).  
When purchasing a charge hose, be sure to confirm the port size.  
Charge hose  
×
As pressure is high and gasification speed is fast, it is difficult to  
read the indicated value by means of charging cylinder, as air  
bubbles occur.  
Electronic balance  
for refrigerant charging  
¡
The size of opposite sides of flare nuts have been increased.  
Incidentally,  
a common wrench is used for nominal diameters 1/4 and 3/8.  
Torque wrench  
(nominal diam. 1/2, 5/8)  
×
By increasing the clamp bars receiving hole, strength of spring in  
Flare tool (clutch type)  
the tool has been improved.  
¡
Gauge for projection  
adjustment  
Used when flare is made by using conventional flare tool.  
Connected to conventional vacuum pump. It is necessary to use  
an adapter to prevent vacuum pump oil from flowing back to the  
charge hose. The charge hose connecting part has two ports-one  
for conventional refrigerant (7/16 UNF 20 threads per inch) and  
one for R410A. If the vacuum pump oil (mineral) mixes with R410A  
a sludge may occur and damage the equipment.  
Vacuum pump adapter  
Gas leakage detector  
¡
Exclusive for HFC refrigerant.  
×
Incidentally, the refrigerant cylindercomes with the refrigerant designation (R410A) and protector coating in the  
U. Ss ARI specified rose color (ARI color code: PMS 507).  
Also, the charge port and packing for refrigerant cylinderrequire 1/2 UNF 20 threads per inch corresponding to  
the charge hoses port size.  
49 –  
10-3-2. Drilling a Hole and Mounting Instal-  
lation Plate  
10-3. Indoor Unit  
10-3-1. Installation Place  
A place which provides enough spaces around the  
indoor unit as shown in the diagram.  
Drilling a hole  
When install the refrigerant pipes from the rear.  
A place where there are no obstacle near the air  
inlet and outlet.  
A place which allows easy installation of the piping  
to the outdoor unit.  
The center of the  
pipe hole  
A place which allows the front panel to be opened.  
The indoor unit shall be installed so that the top of  
the indoor unit is positioned at least 2m in height.  
Pipe  
hole  
Also, avoid putting anything on the top of the  
indoor unit.  
CAUTION  
Direct sunlight on the indoor unit wireless  
receiver should be avoided.  
The microprocessor in the indoor unit should  
not be too close to r-f sources.  
Fig. 10-3-2  
(For details, see the owner's manual.)  
1. After determining the pipe hole position on the  
installation plate ( ð ) drill the pipe hole (Ø65  
mm) at a slight downward slant to the outdoor  
side.  
Remote controller  
Should be placed where there are no obstacles,  
such as curtains, that may block the signal.  
NOTE :  
When drilling into a wall that contains a metal lath,  
wire lath or metal plate, be sure to use a pipe hole  
brim ring sold separately.  
Do not install the remote controller in a place  
exposed to direct sunlight or close to a heating  
source, such as a stove.  
Keep the remote controller at least 1 m away from  
the nearest TV set or stereo equipment.  
(This is necessary to prevent image disturbances or  
noise interference.)  
Mounting the installation plate  
The location of the remote controller should be  
determined as shown below.  
Anchor bolt holes  
(Side view)  
(Top view)  
Indoor unit  
Pipe hole  
Reception  
range  
Pipe hole  
Reception  
range  
Remote  
controller  
Indoor unit  
Remote controller  
1
Installation plate  
7
Mounting screw  
*: Axial distance  
Fig. 10-3-3  
Fig. 10-3-1  
50 –  
10-3-3. Electrical Work  
When the installation plate is directly  
mounted on the wall  
1. The supply voltage must be the same as the  
rated voltage of the air conditioner.  
1. Securely fit the installation plate onto the wall by  
screws with the upper and lower catches, that  
hold the indoor unit, facing out.  
2. Prepare a power source for the exclusive use of  
the air conditioner.  
2. To mount the installation plate on a concrete wall  
use anchor bolts. Drill the anchor bolt holes as  
illustrated in the above figure.  
NOTE :  
Wire type :  
More than H07RN-F or 245IEC66 (1.0mm²)  
3. Install the installation plate horizontally and level.  
CAUTION  
CAUTION  
This appliance can be connected to a main  
circuit breaker in either of the following two  
ways.  
When installing the installation plate with mount-  
ing screw, do not use the anchor bolt hole.  
Otherwise the unit may fall down and result in  
personal injury and property damage.  
1. Connection to fixed wiring:  
A switch or circuit breaker which discon-  
nects all poles and has a contact separa-  
tion of at least 3 mm must be incorporated  
in the fixed wiring. An approved circuit  
breaker or switch must be used.  
2. Connection with power supply plug:  
Anchor bolt  
Attach power supply plug with power cord  
and plug it into wall outlet. An approved  
power supply cord and plug must be used.  
Projection  
15mm or less  
NOTE :  
Perform wiring work being sure the wire length is  
long enough.  
Fig. 10-3-4  
5 mm dia. hole  
10-3-4. Wiring Connection  
How to connect the connecting cable  
7 Mounting screw  
Ø4 × 25L  
Wiring the connecting cable can be carried  
out without removing the front panel.  
Clip anchor  
(local parts)  
1. Remove the air inlet grille. Open the air inlet grille  
upward and pull it toward you.  
2. Remove the terminal cover and cord clamp.  
Fig. 10-3-5  
3. Insert the connecting cable (or as according to  
local regulations/codes) into the pipe hole on the  
wall.  
CAUTION  
4. Pull the connecting cable through the cable slot  
on the rear panel so that it protrudes about  
15 cm out of the front.  
Failure to securely install the unit may result in  
personal injury and/or property damage if the  
unit falls.  
5. Insert the connecting cable fully into the terminal  
block and secure it tightly with screws.  
In case of block, brick, concrete or similar type  
walls, drill 5 mm dia. holes in the wall.  
6. Tightening torque: 1.2 Nm (0.12 kgfm)  
7. Secure the connecting cable with the cord clamp.  
Insert clip anchors for the  
mounting screws.  
8. Attach the terminal cover, rear plate bushing and  
air inlet grille on the indoor unit.  
NOTE :  
Install the installation plate using mounting screws  
between 4 to 6, being sure to secure all four  
corners.  
51 –  
10-3-5. Piping and Drain Hose Installation  
Piping and drain hose forming  
CAUTION  
Be sure to refer to the wiring system diagram  
labeled inside the front panel.  
Since condensation results in machine trouble,  
make sure to insulate both the connecting pipes  
separately.  
Check local electrical regulations for any  
specific wiring instructions or limitations.  
(Use polyethylene foam as insulating material.)  
Terminal cover  
Rear right  
Rear left  
Bottom left  
Left  
Screw  
Screw  
Cord clamp  
Terminal block  
Bottom right  
Right  
Earth wire  
Fig. 10-3-10  
Connecting cable  
1. Die-cutting front panel slit  
Cut out the slit on the left or right side of the front  
panel for the left or right connection and the slit  
on the bottom left or side of thefront panel for the  
bottom left or right connection with a pair of  
nippers.  
Fig. 10-3-6  
Terminal block  
2. Changing drain hose  
For left connection, left-bottom connection and  
rear-left connections piping, it is necessary to  
relocate the drain hose and drain cap.  
Fig. 10-3-7  
How to remove the drain cap  
Clip drain cap with needle-nose pliers, and pull out.  
Connecting cable  
About 15 cm  
Fig. 10-3-8  
Fig. 10-3-11  
70 mm  
How to remove the drain hose  
10 mm  
Earth line  
The drain hose is secured in place by a screw.  
Remove the screw securing the drain hose, then pull  
out the drain hose.  
10 mm  
50 mm  
Fig. 10-3-9  
NOTE :  
Screw  
Drain hose  
WIRE TYPE : more than H07 RN-F or 245 IEC 66.  
(1.0mm²)  
Fig. 10-3-12  
52 –  
How to attach the drain cap  
In case of bottom right or bottom left piping  
1. Insert hexagonal wrench (4 mm).  
After making slits on the front panel with a knife or  
similar tool, cut them out with a pair of nippers or  
an equivalent tool.  
Slit  
Fig. 10-3-16  
4 mm  
Fig. 10-3-13  
Left-hand connection with piping  
2. Firmly insert drain cap.  
Bend the connecting pipes so that they are posi-  
tioned within 43 mm above the wall surface.  
If the connecting pipes are positioned more than  
43 mm above the wall surface, the indoor unit may  
be unstable.  
No gap  
Do not apply lubricating oil  
(refrigerant machine oil)  
when inserting the drain cap.  
If applied, deterioration and  
drain leakage of the drain  
plug may occur.  
When bending the connecting pipe, make sure to  
use a spring bender to avoid crushing the pipe.  
Insert a hexagon  
wrench (Ø4mm)  
Refer to the table below for the bending  
radius of each connection pipe.  
Fig. 10-3-14  
Outer diameter  
6.35 mm  
Bending radius  
30 mm  
9.52 mm  
40 mm  
How to attach the drain hose  
12.7 mm  
50 mm  
Always use the original screw that secured the  
drain hose to the unit. If using a different screw  
may cause water to leak.  
To connect the pipe after installation of the  
unit (figure)  
Insert the drain hose firmly until the connector  
contacts with the insulation, then secure it in place  
using the original screw.  
(To the front flare)  
220 mm  
Gas side  
170 mm  
CAUTION  
Liquid side  
Securely insert the drain hose and drain cap;  
otherwise, water may leak.  
R30 or less (Ø6.35), R40 or less (Ø9. 52), R50 or less (Ø12. 7)  
Use polishing (polyethylene core or the like for bending pipe).  
Outward form of indoor unit  
In case of right or left piping  
After making slits on the front panel with a knife or  
similar tool, cut them out with a pair of nippers or  
an equivalent tool.  
Use a screwdriver handle, etc.  
Fig. 10-3-17  
NOTE :  
If the pipe is incorrectly bent, the indoor unit may be  
unstable on the wall.  
Slit  
After passing the connecting pipe through the pipe  
hole, connect the connecting pipe to the auxiliary  
pipes and wrap the facing tape around them.  
Fig. 10-3-15  
53 –  
10-3-7. Drainage  
CAUTION  
1. Run the drain hose at a downward sloped angle.  
Bind the auxiliary pipes (two) and connecting  
cable with facing tape tightly.  
NOTE :  
In case of leftward piping and rear-leftward  
piping, bind the auxiliary pipes (two) only with  
facing tape.  
Hole should be made at a slight downward slant  
on the outdoor side.  
Do not rise the drain hose.  
Do not form the drain hose  
into the waved shape.  
Indoor unit  
Auxiliary pipes  
Connecting  
cable  
50 mm  
or more  
Installation  
plate  
Fig. 10-3-18  
Do not put the  
Do not put the drain  
hose end in the  
drainage ditch.  
drain hose end  
Carefully arrange the pipes so that none of the  
into water.  
pipes stick out of the rear plate of the indoor unit.  
Carefully connect the auxiliary pipes and  
connecting pipes to each other and cut off the  
insulating tape wound on the connecting pipe  
to avoid double-taping at the joint, moreover,  
seal the joint with the vinyl tape, etc.  
Fig. 10-3-21  
2. Put water in the drain pan and make sure that the  
water is being drained outside.  
Since condensation can result in machine  
performance trouble, be sure to insulate both  
connecting pipes. (Use polyethylene foam as  
insulating material.)  
3. When connecting extension drain hose, insulate  
the connection part of extension drain hose with  
shield pipe.  
When bending a pipe, be careful not to crush it.  
Shield pipe  
10-3-6. Indoor Unit Installation  
Drain hose Inside the room  
Extension drain hose  
1. Pass the pipe through the hole in the wall, and  
hook the indoor unit on the installation plate at  
the upper hooks.  
Fig. 10-3-22  
2. Swing the indoor unit to right and left to confirm  
that it is firmly hooked on the installation plate.  
3. While pressing the indoor unit onto the wall, hook  
it at the lower part on the installation plate.  
Pull the indoor unit toward you to confirm that it is  
firmly hooked on the installation plate.  
CAUTION  
Install the drain pipe for proper drainage.  
Improper drainage can result in water dripping  
inside the room.  
Hook here  
1
1
Installation  
plate  
This air conditioner has been designed to drain  
water collected from condensation which forms on  
the back of the indoor unit, to the drain pan.  
2
Push (unhook)  
Hook  
Therefore, do not locate the power cord and other  
parts at a high place than the drain guide.  
Fig. 10-3-19  
For detaching the indoor unit from the installation  
plate pull the indoor unit toward you while pushing  
the bottom up at the specified places.  
Wall  
Drain  
guide  
Space for  
pipes  
Push  
Push  
Fig. 10-3-23  
Fig. 10-3-20  
54 –  
10-4. Outdoor Unit  
Precautions for adding refrigerant  
10-4-1. Installation Place  
Use a scale having a precision with at least 10 g  
per index line when adding the refrigerant.  
A place which provides enough space around the  
Do not use a bathroom scale or similar instrument.  
outdoor unit as shown in the diagram.  
A place which can bear the weight of the outdoor  
unit and does not allow an increase in noise level  
and vibration.  
Use liquid refrigerant when refilling the refrigerant.  
Since the refrigerant is in liquid form, it can fill  
quickly.  
Therefore, perform the filling operation carefully  
and insert the refrigerant gradually.  
A place where the operation noise and discharged  
air do not disturb neighbors.  
A place which is not exposed to a strong wind.  
A place free of combustible gases.  
CAUTION  
A place which does not block a passageway.  
1. Install the outdoor unit without anything  
blocking the discharging air.  
When the outdoor unit is to be installed in an  
elevated position, be sure to secure its feet.  
2. When the outdoor unit is installed in a place  
always exposed to strong winds like on the  
coast or on a high story of a building, secure  
the normal fan operation using a duct or a  
wind shield.  
This air conditioner accepts a connection piping  
length of up to 25 m.  
There is no need to add refrigerant as long as  
the length of the connection piping is 15 m or  
less.  
3. Especially in windy areas, install the unit to  
prevent the admission of wind.  
You will need to add 20 g of refrigerant per meter  
of added connection piping for installations  
requiring connection piping to be between 16 m  
to 25 m.  
4. Installation in the following places may result  
in trouble.  
Do not install the unit in such places.  
A place full of machine oil.  
An allowable height level is up to 10 m.  
A place where the drain water does not cause any  
problems.  
A saline-place such as the coast.  
A place full of sulfide gas.  
A place where high-frequency waves are  
likely to be generated, such as from audio  
equipment, welders, and medical equip-  
ment.  
Strong  
wind  
Fig. 10-4-1  
55 –  
10-4-2. Draining the Water  
10-4-3. Refrigerant Piping Connection  
Holes are provided on the base plate of the  
outdoor unit to ensure that the defrost water  
produced during heating operations is drained off  
efficiently.  
Flaring  
1. Cut the pipe with a pipe cutter.  
If a centralized drain is required when installing the  
unit on a balcony or wall, follow the steps below to  
drain off the water.  
90˚  
Obliquity Roughness  
Warp  
1. Proceed with water-proofing by installing the  
water-proof rubber caps  
in the 2 elongated  
Š
holes on the base plate of the outdoor unit. [How  
to install the water-proof rubber caps]  
Fig. 10-4-4  
1) Place four fingers into each cap, and insert  
the caps into the water drain holes by pushing  
them into place from the underside of the  
base plate.  
2. Insert a flare nut into the pipe, and flare the pipe.  
• Projection margin in flaring : A (Unit : mm)  
2) Press down on the outer circumferences of  
the caps to ensure that they have been  
inserted tightly.  
Rigid (Clutch type)  
Outer dia. of  
copper pipe  
R410A  
tool used  
Conventional  
tool used  
(Water leaks may result if the caps have not  
been inserted properly, if their outer circumfer-  
ences lift up or the caps catch on or wedge  
against something.)  
6.35  
9.52  
12.7  
0 to 0.5  
0 to 0.5  
0 to 0.5  
1.0 to 1.5  
1.0 to 1.5  
1.0 to 1.5  
10 Water-proof rubber caps  
(supplied with the outdoor unit)  
Imperial (Wing nut type)  
A
Outer dia. of  
copper pipe  
R410A  
Base plate  
6.35  
1.5 to 2.0  
1.5 to 2.0  
2.0 to 2.5  
Die  
Pipe  
9.52  
9
Drain nipple  
Fig. 10-4-5  
12.7  
Fig. 10-4-2  
B
• Flaring size : B (Unit : mm)  
2. Install the drain nipple  
and a commercially  
available drain hose (with 16 mm inside diam-  
eter), and drain off the water.  
Fig. 10-4-6  
(For the position where the drain nipple  
installed, refer to the installation diagram of the  
indoor and outdoor units.)  
is  
+0  
B
0.4  
Outer dia. of copper pipe  
R410A  
9.1  
R22  
9.0  
Check that the outdoor unit is horizontal, and  
route the drain hose at a downward sloped  
angle while ensuring that it is connected tautly.  
6.35  
9.52  
12.7  
13.2  
16.6  
13.0  
16.2  
Base plate  
9
Drain nipple  
Commercially available  
In case of flaring for R410A with the conventional  
drain hose  
flare tool, pull it out approx. 0.5 mm more than that  
of R22 to adjust to the specified flare size.  
The copper pipe gauge is useful for adjusting  
projection margin size.  
Do not use ordinary garden hose, but one can  
flatten and prevent water from draining.  
Fig. 10-4-3  
56 –  
Tightening Connection  
Use a vacuum pump  
Align the centers of the connecting pipes and tighten  
the flare nut as much as possible with your fingers.  
Then tighten the nut with a wrench and torque  
wrench as shown in the figure.  
Be sure to use a vacuum pump with counter-flow  
prevention function so that oil inside the pump does  
not flow back into the air conditioner pipes when the  
pump stops. (If oil inside the vacuum pump enters  
into the air conditioner circuit which uses R410A,  
trouble with the refrigeration system may develop.)  
Half union  
Flare nut  
1. Connect the charge hose from the manifold valve  
to the service port of the gas side packed valve.  
Externally  
threaded side  
Internally  
threaded side  
2. Connect the charge hose to the port of the  
vacuum pump.  
Use a wrench  
to secure.  
Use a torque wrench  
to secure.  
3. Open fully the low pressure side handle of the  
gauge manifold valve.  
Fig. 10-4-7  
4. Operate the vacuum pump to begin evacuating.  
Perform evacuating for about 15 minutes if the  
piping length is 20 meters (15 minutes for 20  
meters) (assuming a pump capacity of 27 liters  
per minute).  
CAUTION  
Do not apply excessive force.  
Otherwise, the nut may break.  
Confirm that the compound pressure gauge  
reading is 101 kPa (76 cmHg).  
(Unit : N·m)  
5. Close the low pressure valve handle of gauge  
manifold.  
Outer dia. of copper pipe  
Ø6.35 mm  
Tightening torque  
14 to 18 (1.4 to 1.8 kgfm)  
33 to 42 (3.3 to 4.2 kgfm)  
50 to 62 (5.0 to 6.2 kgfm)  
6. Open fully the valve stem of the packed valves  
(both sides of Gas and Liquid).  
Ø9.52 mm  
7. Remove the charging hose from the service port.  
8. Securely tighten the caps on the packed valves.  
Ø12.7 mm  
Tightening torque for connection of flare pipe  
Compound  
Pressure gauge  
pressure  
The pressure of R410A is higher than R22.  
(Approx. 1.6 times.) Therefore securely tighten the  
flare pipes which connect the outdoor unit and the  
indoor unit with the specified tightening torque  
using a torque wrench.  
gauge  
-101kPa  
Manifold valve  
(-76cmHg)  
Handle Hi  
(Keep full closed)  
Handle Lo  
Charge hose  
(For R410A only)  
Charge hose  
(For R410A only)  
If any flare pipe is  
Flare at  
indoor unit  
side  
Vacuum pump  
adapter for  
incorrectly connected,  
it may cause not only  
a gas leakage but also  
trouble in the  
counter-flow  
prevention  
(For R410A only)  
Connecting  
pipe  
refrigeration cycle.  
Vacuum  
pump  
Packed valve at liquid side  
Packed valve at gas side  
Flare at  
outdoor unit  
side  
Service port  
(Valve core (Setting pin))  
Fig. 10-4-8  
Fig. 10-4-9  
CAUTION  
10-4-4. Evacuating  
After the piping has been connected to the indoor  
unit, perform the air purge.  
• IMPORTANT POINTS FOR PIPING WORK  
1. Keep dust and moisture from entering the  
pipes.  
2. Tighten connections carefully (between pipes  
and unit).  
AIR PURGE  
Evacuate the air in the connecting pipes and in  
the indoor unit using a vacuum pump.  
Do not use the refrigerant in the outdoor unit.  
3. Evacuate the air in the connecting pipes  
using a VACUUM PUMP.  
4. Check for gas leaks at all connections.  
For details, see the vacuum pump manual.  
57 –  
Packed Valve handling precautions  
Open the valve stem all the way; but do not try to  
open it beyond the stopper.  
3
1 2  
10  
N
L
10  
Securely tighten the valve stem cap with torque in  
the following table:  
10  
10  
40  
40  
30  
30  
Gas side (Ø12.7 mm)  
50 to 62 Nm (5.0 to 6.2 kgfm)  
Gas side (Ø9.52 mm)  
33 to 42 Nm (3.3 to 4.2 kgfm)  
Connecting  
cable  
Liquid side (Ø6.35 mm) 14 to 18 Nm (1.4 to 1.8 kgfm)  
Power cord  
Earth line  
Earth line  
Service port  
14 to 18 Nm (1.4 to 1.8 kgfm)  
Fig. 10-4-12  
Hexagonal wrench is required.  
Model RAS-  
10GAVP-E 13GAVP-E 16GAVP-E  
220 240 V ~50 Hz  
Power source  
220 V ~60 Hz  
Maximum running  
current  
12 A  
Fig. 10-4-10  
Installation fuse  
rating  
25A (D type  
)
Power cord  
H07RN-F or 245IEC66 (1.5 mm²)  
H07RN-F or 245IEC66 (1.0 mm²)  
10-4-5. Wiring Connection  
1. Remove the valve cover, the electric parts cover  
and the cord clamp from the outdoor unit.  
Connection cable  
2. Connect the connecting cable to the terminal as  
identified by the matching numbers on the  
terminal block of indoor and outdoor unit.  
CAUTION  
Incorrect wiring connection may cause electri-  
cal parts to burn out.  
3. Insert the power cord and the connecting cable  
fully into the terminal block and secure it tightly  
with screws.  
Be sure to comply with local regulations/codes  
when running the wire from outdoor unit to  
indoor unit.  
4. Insulate the unused cords (conductors) from  
water entering in the outdoor unit. Locate them  
so that they do not touch any electrical or metal  
parts.  
(Size of wire and wiring method etc.)  
Every wire must be securely connected.  
5. Secure the power cord and the connecting cable  
with the cord clamp.  
This installation fuse (25A D type  
must be used for the power supply line.  
)
6. Attach the electric parts cover and the valve  
cover on the outdoor unit.  
If incorrect or incomplete wiring is carried out,  
fire or smoke may result.  
Prepare the power supply for the exclusive use  
of the air conditioner.  
Stripping length of connecting cable  
This product can be connected to the main  
breaker.  
Terminal block  
Connection to fixed wiring:  
A switch which disconnects all poles and has a  
contact separation of at least 3 mm must be  
incorporated in the fixed wiring when connect-  
ing to a main breaker circuit.  
1
2
3
L
N
Connecting cable  
Power cord  
Fig. 10-4-11  
58 –  
10-5-4. Remote Controller Selector Switch  
Setting  
10-5. Test Operation  
10-5-1. Gas Leak Test  
Check the flare nut connections for gas leaks with  
a gas leak detector and/or soapy water.  
Remote controller selector switch  
If two indoor units are installed in the same room  
or adjoining rooms, the second unit can inadvert-  
ently receive a remote controller signal and start  
operation when operating the first unit.This can be  
prevented by setting one of the indoor units and  
the corresponding remote controller to the B  
setting (the A setting is the default setting).  
Valve cover  
Check places for  
flare nut connections  
(indoor unit)  
1. Setting the selector switch on the main unit  
Electric parts  
Remove the front panel, and then set the  
selector switch to B.  
After making the switch setting, remount the  
front panel.  
Check places  
for outdoor unit  
2. Setting the remote controller  
Fig. 10-5-1  
1) Slide open the remote controller cover and  
remove the batteries.  
2) Cut the jumper wire inside the battery  
compartment using nippers.  
10-5-2. Test Operation  
To test the system, press and hold RESET button for  
10 sec. (There will be one short beep.)  
The jumper wire should not remain in  
contact after being cut. Also, be careful  
not to let plastic scraps, jumper wire  
cuttings or other debris enter the inside of  
the remote controller.  
3) Insert the batteries. Bappears in the  
remote controller display.  
3. Check that the indoor unit can be operated by  
the modified remote controller.  
Position of remote controller selector switch  
Fig. 10-5-2  
10-5-3. Auto Restart Setting  
This product is designed so that, after a power  
failure, it can restart automatically in the same  
operating mode as before the power failure.  
Selector switch  
Fig. 10-5-3  
Information  
The product was shipped with Auto Restart  
function in the OFF position.  
Turn it ON as required.  
Cutting direction  
Jumper wire  
HiPOWER  
ECO  
MEMO  
.
.
.
1
3
5 9H  
SWING  
CLR  
FIX  
FAN  
SLEEP  
SET  
ON  
OFF  
CLOCK  
RESET  
CHECK  
When switching between settings Aand  
B, always switch the indoor unit board  
and the remote controller as a pair.  
(Otherwise, the indoor unit will not  
How to Set the Auto Restart  
Press and hold the RESET button for about 3  
seconds. After 3 seconds, three short electric  
beeps will be heard to inform you that the Auto  
Restart has been selected.  
accept the remote controllers signals.)  
To cancel the Auto Restart, follow the steps  
described in the section Auto Restart Function on  
Owners Manual.  
Fig. 10-5-4  
59 –  
11. HOW TO DIAGNOSE THE TROUBLE  
The pulse motor circuits are mounted to both indoor and outdoor units. Therefore, diagnose troubles according  
to the trouble diagnosis procedure as described below. (Refer to the check points in servicing written on the  
wiring diagrams attached to the indoor/outdoor units.)  
Table 11-1  
No.  
1
Troubleshooting Procedure  
First Confirmation  
Page  
62  
No.  
6
Troubleshooting Procedure  
How to Check Simply the Main Parts  
Troubleshooting  
Page  
72  
2
Primary Judgment  
63  
7
73  
3
Judgment by Flashing LED of Indoor Unit  
Self-Diagnosis by Remote Controller  
Judgment of Trouble by Every Symptom  
63  
8
How to Diagnose Trouble in Outdoor Unit  
How to Check Simply the Main Parts  
75  
4
64  
9
76  
5
67  
How to Simply Judge Whether Outdoor  
Fan Motor is Good or Bad  
10  
81  
u Precautions when handling the new inverter (3DV Inverter)  
CAUTION: HIGH VOLTAGEN  
The high voltage circuit is incorporated.  
Be careful to do the check service, as the electric shock may be caused in case of touching parts on the  
P.C. board by hand.  
The new inverter (3DV inverter) will be incorporated starting with this unit.  
(3DV: 3-shunt Discrete Vector control)  
u The control circuitry has an uninsulated construction.  
G-Tr  
Compressor  
Fan motor  
FET  
(6IN1)  
Photocoupler  
Shared potential  
MCU  
Hall device  
Photocoupler  
JAVP-E series (insulated type)  
Compressor  
Fan motor  
IGBT × 6  
Shared potential  
Driver  
Amplifier  
FET × 6  
MCU  
Driver  
Amplifier  
GAVP-E, EAVP-E series (uninsulated type)  
Fig. 11-1  
– 60 –  
CAUTION  
A high voltage (equivalent to the supply voltage) is also energized to ground through the  
sensors, PMV and other low-voltage circuits. The sensor leads and other wires are covered  
with insulated tubes for protection. Nevertheless, care must be taken to ensure that these  
wires are not pinched.  
Take sufficient care to avoid directly touching any of the circuit parts without first turning off  
the power.  
At times such as when the circuit board is to be replaced, place the circuit board assembly in  
a vertical position.  
Laying the board flat on an electrically conductive object (such as the top panel of the air conditioner's  
outdoor unit) while a charge is still retained by the electrolytic capacitors of the inverter's main circuit may  
cause short-circuiting between the electrolytic capacitors and secondary circuit components and result in  
damage to the components.  
Sensor leads  
Fig. 11-2  
Do NOT lay the circuit board assembly flat.  
u Precautions when inspecting the control section of the outdoor unit  
NOTE :  
A large-capacity electrolytic capacitor is used in the outdoor unit controller (inverter).Therefore, if the power  
supply is turned off, charge (charging voltage DC280 to 380V) remains and discharging takes a lot of time.  
After turning off the power source, if touching the charging section before discharging, an electrical shock may  
be caused. Discharge the electrolytic capacitor completely by using soldering iron, etc.  
< Discharging method >  
1. Remove the inverter cover (plating) by opening four mounting claws.  
2. As shown below, connect the discharge resistance (approx. 10040W) or plug of the soldering iron to  
voltage between + terminals of the C14 (CAUTION HIGH VOLTAGEis indicated.) electrolytic capacitor  
(500µF/400V) on P.C. board, and then perform discharging.  
Discharging position  
(Discharging period  
10 seconds or more)  
Plug of  
soldering iron  
Inverter cover  
P. C. board  
(Soldered surface)  
Fig. 11-3  
61 –  
11-1. First Confirmation  
11-1-1. Confirmation of Power Supply  
Confirm that the power breaker operates (ON) normally.  
11-1-2. Confirmation of Power Voltage  
Confirm that power voltage is AC 220230240 ± 10%.  
If power voltage is not in this range, the unit may not operate normally.  
11-1-3. Operation Which is not a Trouble (Program Operation)  
For controlling the air conditioner, the program operations are built in the microcomputer as described in the  
following table.  
If a claim is made for running operation, check whether or not it meets to the contents in the following table.  
When it does, we inform you that it is not trouble of equipment, but it is indispensable for controlling and main-  
taining of air conditioner.  
Table 11-1-1  
No.  
Operation of air conditioner  
Description  
1
When power breaker is turned ON, the  
operation indicator (Green) of the indoor  
unit flashes.  
The OPERATION lamp of the indoor unit flashes when  
power source is turned on. If [START/STOP] button is  
operated once, flashing stops.  
(Flashes also in power failure)  
2
Compressor may not operate even if the  
room temperature is within range of  
compressor-ON.  
The compressor does not operate while compressor  
restart delay timer (3-minutes timer) operates.  
The same phenomenon is found after power source has  
been turned on because 3-minutes timer operates.  
3
4
In Dry and ECO mode, FAN (air flow)  
display does not change even though FAN  
(air flow select) button is operated.  
The air flow indication is fixed to [AUTO].  
Increasing of compressor motor speed  
stops approx. 30 seconds after operation  
For smooth operation of the compressor, the compres-  
sor motor speed is restricted to Max. 41 rps for 2 min-  
started, and then compressor motor speed utes, and Max.91 rps for 2 minutes to 3 minutes, respec-  
increases again approx. 30 seconds after.  
tively after the operation has started.  
5
6
In AUTO mode, the operation mode is  
changed.  
After selecting Cool or Heat mode, select an operation  
mode again if the compressor keeps stop status for 15  
minutes.  
In HEAT mode, the compressor motor  
speed does not increase up to the maxi-  
mum speed or decreases before the  
The compressor motor speed may decrease by high-  
temp. release control (Release protective operation by  
temp.-up of the indoor heat exchanger) or current  
temperature arrives at the set temperature. release control.  
62 –  
11-2. Primary Judgment  
To diagnose the troubles, use the following methods.  
1) Judgment by flashing LED of indoor unit  
2) Self-diagnosis by service check remote controller  
3) Judgment of trouble by every symptom  
Firstly use the method 1) for diagnosis.Then, use the method 2) or 3) to diagnose the details of troubles.  
11-3. Judgment by Flashing LED of Indoor Unit  
While the indoor unit monitors the operation status of the air conditioner, if the protective circuit operates, the  
contents of self-diagnosis are displayed with block on the indoor unit indication section.  
Table 11-3-1  
Check  
code  
Item  
A
Block display  
Description for self-diagnosis  
OPERATION (Green)  
Flashing display (1 Hz)  
Power failure (when power is ON)  
Indoor indication  
lamp flashes.  
OPERATION (Green)  
Flashing display (5 Hz)  
B
C
Protective circuit operation for indoor P.C. board  
Which lamp  
does flash?  
OPERATION (Green)  
TIMER (Yellow)  
Flashing display (5 Hz)  
Protective circuit operation for connecting cable  
and serial signal system  
OPERATION (Green)  
FILTER (Orange)  
Flashing display (5 Hz)  
D
E
Protective circuit operation for outdoor P.C. board  
OPERATION (Green)  
TIMER (Yellow)  
FILTER (Orange)  
Protective circuit operation for others  
(including compressor)  
Flashing display (5 Hz)  
NOTES :  
1. The contents of items B and C and a part of item E are displayed when air conditioner operates.  
2. When item B and C, and item B and a part of item E occur concurrently, priority is given to the block of item B.  
3. The check codes can be confirmed on the remote controller for servicing.  
63 –  
11-4. Self-Diagnosis by Remote Controller (Check Code)  
1. If the lamps are indicated as shown B to E in Table 11-3-1, execute the self-diagnosis by the remote controller.  
2. When the remote controller is set to the service mode, the indoor controller diagnoses the operation condi-  
tion and indicates the information of the self-diagnosis on the display of the remote controller with the check  
codes. If a fault is detected, all lamps on the indoor unit will flash at 5Hz and it will beep for 10 seconds  
(Beep, Beep, Beep ... ). The timer lamp usually flashes (5Hz) during self-diagnosis.  
11-4-1. How to Use Remote Controller in Service Mode  
1
Press [CHECK] button with a tip of pencil to set the  
remote controller to the service mode.  
• “  
is indicated on the display of the remote  
controller.  
2
Press [ON ] or [OFF ] button  
If there is no fault with a code, the indoor unit will beep  
once (Beep) and the display of the remote controller will  
change as follows :  
• • •  
AUTO  
PURE  
The TIMER indicator of the indoor unit flashes continuously.  
(5 times per 1 sec.)  
MODE  
PRESET  
Check the unit with all 52 check codes (  
to  
)
as shown in Table-11-4-1.  
HiPOWER  
ECO  
MEMO  
.
.
.
1 3 5 9H  
Press [ON ] or [OFF ] button to change the check  
code backward.  
SWING  
CLR  
FIX  
FAN  
SLEEP  
SET  
ON  
OFF  
CLOCK  
RESET  
CHECK  
If there is a fault, the indoor unit will beep for 10  
seconds (Beep, Beep, Beep...).  
Note the check code on the display of the remote  
controller.  
2-digits alphanumeric will be indicated on the display.  
Alphanumeric characters are  
used for the check codes.  
All indicators on the indoor unit will flash.  
(5 times per 1 sec.)  
is 5.  
is A.  
is C.  
is 6.  
is B.  
is D.  
Press [START/STOP] button to release the service mode.  
3
4
The display of the remote controller returns to as it  
was before service mode was engaged.  
Time shortening method.  
1. Press SET button while pushing CHECK button.  
2. Press [START/STOP] button.  
Fig. 11-4-1  
64 –  
11-4-2. Caution at Servicing  
1. After servicing, press the START/STOP button to return to the normal mode.  
2. After servicing by the check code, turn off breaker of the power supply, and turn on breaker of the power  
supply again so that memory in the microcomputer returns the initial status.  
However, the check codes are not deleted even if the power supply is turned off because they are stored in  
the fixed memory.  
3. After servicing, press [CLR] button under check mode status and then send the check code 7Fto the  
indoor unit. The error code stored in memory is cleared.  
Table 11-4-1  
Block distinction  
Operation of diagnosis function  
Air  
Judgment and action  
Check  
code  
Check  
code  
Block  
Cause of operation  
conditioner  
status  
Remarks  
Indoor P.C.  
board etc.  
Short-circuit or discon-  
nection of the room  
temperature sensor  
(TA sensor).  
Operation Displayed when  
continues. error is detected.  
1. Check the room temp. sensor.  
2. When the room temp. sensor is  
normal, check P.C. board.  
Being out of place,  
disconnection, short-  
circuit, or migration of  
heat exchanger sensor  
(TC sensor)  
Operation Displayed when  
continues. error is detected.  
1. Check heat exchanger sensor.  
2. When heat exchanger sensor is  
normal, check P.C. board.  
Lock of indoor fan or  
trouble on the indoor fan  
circuit  
All off  
Displayed when  
error is detected.  
1. Check the motor.  
2. When the motor is normal,  
check P.C. board.  
Not  
displayed  
Trouble on other indoor  
P.C. boards  
Operation Displayed when  
continues. error is detected.  
Replace P.C. board.  
Connecting  
cable and  
serial signal  
Return serial signal is not Operation Flashes when  
1. When the outdoor unit never  
operate:  
sent to indoor side from  
operation started.  
continues. trouble is detected  
on Return serial  
1) Check connecting cable, and  
correct if defective wiring.  
signal, and normal  
status when signal  
is reset.  
1) Defective wiring of  
connecting cable  
2) Check 25A fuse of inverter  
P.C. board.  
2) Operation of compres-  
sor thermo Gas  
3) Check 3.15A of inverter P.C.  
board.  
shortage Gas leak  
2. To display [Other] block during  
operation, check compressor  
thermo. operation and supply  
gas (check gas leak also).  
3. Unit operates normally during  
check.  
If return serial signal does not  
stop between indoor terminal  
board 2 and 3, replace inverter  
P.C. board.  
If signal stops between indoor  
terminal board 2 and 3, replace  
indoor P.C. board.  
65 –  
Block distinction  
Operation of diagnosis function  
Air  
Judgment and action  
Check  
Block  
code  
Check  
code  
Cause of operation  
conditioner  
status  
Remarks  
Outdoor P.C.  
board  
Inverter over-current  
protective circuit  
operates. (Short time)  
All off  
All off  
Displayed when  
error is detected. operations stop immediately. :  
Replace P.C. board.  
Even if trying operation again, all  
Position-detect circuit  
error or short-circuit  
between windings of  
compressor  
Displayed when  
error is detected.  
1. Even if connecting lead wire of  
compressor is removed,  
position-detect circuit error  
occurred. : Replace P.C. board.  
2. Measure resistance between  
wires of compressor, and  
perform short-circuit. : Replace  
compressor.  
Current-detect circuit  
error  
All off  
All off  
Displayed when  
error is detected. operations stop immediately. :  
Replace P.C. board.  
Even if trying operation again, all  
Being out of place,  
disconnection or short-  
circuit of the outdoor  
heat exchanger sensor  
(TE) or suction temp.  
sensor (Ts)  
Displayed when  
error is detected.  
1. Check sensors (TE, TS).  
2. Check P.C. board.  
Disconnection or short- All off  
circuit of discharge  
Displayed when  
error is detected.  
1. Check discharge temp. sensor  
(TD).  
temp. sensor  
2. Check P.C. board  
Outdoor fan drive  
system error  
All off  
Displayed when  
error is detected. protective operation of outdoor fan  
drive system, fan lock, etc. :  
Position-detect error, over-current  
Replace P.C. board or fan motor.  
Not  
displayed  
Outdoor heat exchanger Operation  
temp. sensor error continues  
1. Check outdoor temp. sensor  
(TO).  
——  
2. Check P.C. board.  
Outdoor P.C.  
board  
Compressor drive output All off  
error, Compressor error  
(lock, missing, etc.),  
Break down  
Displayed when  
When 20 seconds passed after  
error is detected. start-up, position-detect circuit error  
occurred. : Replace compressor.  
Trouble on P.M.V.  
Others  
(including  
compressor)  
Return serial signal has Operation Flashes when  
1. Repeat Start and Stop with  
interval of approx. 10 to 40  
minutes. (Code is not displayed  
during operation.)  
Supply gas.  
(Check also gas leak).  
been sent when  
operation started, but it  
is not sent from halfway.  
continues trouble is detected  
on return serial  
signal, and normal  
status when signal  
is reset.  
1) Compressor thermo.  
operation  
Gas shortage  
Gas leak  
2. Unit operates normally during  
check.  
If return serial signal does not  
stop between indoor terminal  
block 2 and 3, replace inverter  
P.C. board.  
2) Instantaneous power  
failure  
If signal stops between indoor  
terminal block 2 and 3, replace  
indoor P.C. board.  
Compressor does not  
rotate.  
(Current protective  
circuit does not operate  
when a specified time  
passed after compressor  
had been activated.)  
All off  
Displayed when  
error is detected.  
1. Trouble on compressor  
2. Trouble on wiring of compressor  
(Missed phase)  
Discharge temp.  
exceeded 117°C  
All off  
All off  
Displayed when  
error is detected.  
1. Check dischage temp. sensor  
(TD).  
2. Gas leakage  
3. Trouble on P.M.V.  
Break down of  
compressor  
Displayed when  
error is detected.  
1. Check power voltage.  
(220230240 V +10%)  
2. Overload operation of refrigera-  
tion cycle  
Check installation condition  
(Short-circuit of outdoor diffuser).  
4-way valve inverse error Operation  
1. Check 4-way valve operation.  
(TC sensor value  
lowered during heating  
operation.)  
continues  
——  
66 –  
11-5. Judgment ofTrouble by Every Symptom  
11-5-1. Indoor Unit (Including Remote Controller)  
(1) Power is not turned on (Does not operate entirely)  
<Primary check>  
1. Is the supply voltage normal?  
2. Is the normal voltage provided to the outdoor unit?  
3. Is the crossover cable connected properly?  
4. Is the fuse (F01) blown?  
Operation  
Check Item  
Considerable principle cause  
Turn off power supply once, and  
5 second later, turn it on again.  
Measures  
NO  
Item by symptoms  
Is OPERATION indicator flashing?  
YES  
Is it possible to turn on  
power supply by pushing  
[START/STOP] button  
on remote controller?  
Does transmission mark  
NO  
NO  
on remote controller flash  
normally,and is its signal  
transmitted properly?  
Remote controller is defective.  
YES  
YES  
Refer to (5) Troubleshooting  
for remote controller.  
Unit operates normally.  
Does fan  
YES  
YES  
Is fuse (F01)  
of indoor control  
board blown?  
Parts (R04, R05, DB01, C01,  
C03, IC01 and T01) are defective.  
motor connector  
between CN10 1 –  
3 short-circuit?  
NO  
NO  
Is voltage  
(DC12V or 5V)  
indicated on rear of  
indoor control  
NO  
YES  
Microcomputer  
is defective.  
Replace main  
P.C. board  
board normal?  
Is DC310340V  
supplied between  
CN10 1 3 ?  
NO  
Parts of a power supply circuit  
defective.  
YES  
Replace fan  
motor.  
Be sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of  
damage of the motor.  
(2) Power is not turned on though Indoor P.C. board is replaced  
<Confirmation procedure>  
Turn on power supply.  
NO  
NO  
Is wired correctly to white and  
Does OPERATION indicator flash?  
YES  
Correct wiring.  
black lead wires of terminal block?  
YES  
To item of  
Power supply is not turned on.  
67 –  
(3) Only the indoor motor fan does not operate  
<Primary check>  
1. Is it possible to detect the power supply voltage (AC220240V) between  
and  
on the terminal block?  

2. Does the indoor fan motor operate in cooling operation?  
(In heating operation, the indoor fan motor does not operate for approximately 10 minutes after it is turned  
on, to prevent a cold air from blowing in.)  
Turn off power  
supply once, and  
turn it on again.  
Is it possible to detect  
YES  
NO  
DC 1V or more between  
Does fan motor  
+
5
and  
3
of  
continue to operate?  
Peplace indoor  
fan motor.  
motor connector (CN10).  
NO  
YES  
Start to operate  
indoor unit in cooling  
operation at airflow  
level LOW.  
Is it possible to detect  
NO  
NO  
DC 310340V between  
Does indoor  
fan operate?  
+
1
and  
3
of motor  
connector (CN10).  
YES  
YES  
Turn off indoor unit and remove  
(Motor connection condition)  
Is it possible to detect DC 15V  
NO connector from motor.  
Then push START/STOP button  
on remote controller to stop  
flashing lamp on indoor unit.  
+
between  
4
and  
3
of  
motor connector (CN10).  
YES  
Is it possible to detect  
NO  
+
DC 15V between  
4
Peplace main  
P.C. board.  
Change airflow level  
to HIGH.  
and  
3
of motor  
connector (CN10).  
YES  
Start to operate the  
indoor unit in except  
Turn off indoor unit and  
heating operation.  
NO  
remove connector from motor.  
Then start to operate indoor  
unit with remote controller.  
At this time, is it possible to  
detect DC 1V or more between  
+
5
and  
3
of motor  
connector (CN10)?  
YES  
Start to operate the  
indoor unit in except  
heating operation.  
At this time, is it possible  
to detect DC 1V or more  
Is it possible to  
change airflow level  
to HIGH?  
NO  
NO  
+
between  
5
and  
3
of motor connector (CN10)?  
(Check this condition  
within 15 seconds after  
starting unit.)  
YES  
YES  
Is it possible to  
NO  
NO  
Peplace  
bearing.  
rotate cross-flow fan by  
hand properly?  
YES  
Turn off indoor unit  
and rotate cross-flow  
fan by hand when the  
unit is on standby.  
At this time, is it possible to  
detect DC 1V or more  
+
between  
5
and  
3
of motor connector  
(CN10).  
Fan motor  
operates normally.  
YES  
68 –  
(4) Indoor fan motor automatically starts to rotate by turning on power supply  
<Cause>  
The IC is built in the indoor fan motor. Therefore the P.C. board is also mounted to inside of the motor.  
If the P.C. board is soldered imperfectly or the IC is defective, the fan motor may automatically rotate by turning  
on power supply.  
<Inspection procedure>  
1. Remove the front panel. (Remove 2 screws.)  
2. Remove the cover of the fan motor lead wires.  
3. Check DC voltage with CN10 connector while the fan motor is rotating.  
NOTE :  
Do not disconnect the connector while the fan motor is rotating.  
Use a thin test rod.  
Indoor fan starts rotating when power supply is turned on.  
P.C. board  
CN10  
(Check output DC voltage of fan motor on P.C. board.)  
6 (Blue)  
5 (Yellow)  
4 (White)  
3 (Black)  
Yellow  
Black  
Measure voltage between 3 (GND : BLACK)  
and 5 (V line : YELLOW) of motor connector (CN10)  
while indoor fan motor is rotating.  
2
1 (Red)  
DC 1.0V or more  
P.C. board is defective.  
Replace P.C. board.  
Under DC 1.0V  
Motor is defective.  
Replace motor.  
DC  
69 –  
(5) Troubleshooting for remote controller  
<Primary check>  
Check that A or B selected on the main unit is matched with A or B selected on the remote controller.  
The unit does not beep at all.  
Push the START/STOP button. Operation lamp on indoor  
unit is not indicated.  
NO  
Is transmission  
mark indicated?  
YES  
Is receiver  
on indoor unit  
exposed to  
Push RESET button  
on remote controller  
with tip of pencil.  
NO  
direct sunlight?  
YES  
Does indoor unit  
operate when moving  
remote controller  
near receiver or  
indoor unit?  
Is there any  
thyristor  
fluorescent light  
nearby?  
NO  
NO  
YES  
YES  
Batteries are  
exhausted.  
Push the START/  
STOP button  
Does indoor unit  
NO  
start to operate by  
automatic restart  
function?  
NO  
Is transmission  
mark indicated?  
YES  
YES  
NO  
Does indoor unit  
beep and operate?  
YES  
Does radio sound  
is affected by remote  
controller when a signal is  
transmitted at distance of  
5 cm from radio?  
NO  
YES  
Remote controller  
is defective.  
P.C. board  
is defective.  
Keep indoor unit  
away from thyristor  
fluorescent light.  
Avoid direct  
sunlight.  
Replace  
P.C. board.  
Replace  
batteries.  
Replace  
remote controller.  
Normal  
operation  
NOTE : After replacing batteries,  
push the RESET button  
with a tip of a pencil.  
70 –  
11-5-2. Wiring Failure (Interconnecting and Serial Signal Wire)  
(1) Outdoor unit does not operate  
1) Is the voltage between  
and  
of the indoor terminal block varied?  
ƒ
Confirm that transmission from indoor unit to outdoor unit is correctly performed based upon the follow-  
ing diagram.  
NOTE:  
Measurement should be performed 2 minutes and 30 seconds after starting of the operation.  
Be sure to prepare a diode for judgment.  
Terminal block at indoor side  
Red  
3
2
1
S5277G or equivalent (G or J type)  
(Diode with rated voltage of 400V  
or more is acceptable.)  
S5277G  
White  
Tester  
Terminal block  
Normal time  
:Voltage swings between DC15 and 60V. ...................Inverter Assembly check (11-8-1.)  
Abnormal time :Voltage does not vary.  
(2) Outdoor unit stops in a little while after operation started  
<Check procedure> Select phenomena described below.  
1) The outdoor unit stops 10 to 20 minutes after operation started, and 10 minutes or more are required to  
restart the unit.  
Gas circulation amount is down.  
Measure gas pressure.  
Gas shortage  
Gas leak  
Pipe clogging  
Thermo. operation of compressor  
2) If the unit stops once, it does not operate until the power will be turned on again.  
To item of Outdoor unit does not operate.  
3) The outdoor unit stops 10 minutes to 1 hour after operation started, and an alarm is displayed.  
(Discharge temp. error check code 03, 1E Sensor temp. error check code 02, 1C)  
Gas leak  
P.M.V. is defective.  
Refer to the chart in 11-6.  
Miswiring of connecting wires of indoor/outdoor units  
Clogging of pipe and coming-off of TC sensor  
71 –  
11-6. Check Code 1C (Miswiring in indoor/outdoor units) and 1E  
<Check procedure>  
1C  
1E  
Gas leakage,  
Discharge temp. error,  
gas leakage  
(Check code 03, 1E)  
disconnection of TS/TC  
sensors (Check code 02, 1C)  
Valve drive check  
NO  
NO  
Is coil of the pulse motor valve  
(P.M.V.) correctly set?  
Set it correctly.  
Set it correctly.  
YES  
Is connecter of coil connected to inverter?  
YES  
Is positioning sound of valve (sound hitting to stopper) heard  
from valve when the air conditioner starts the operation after turning off power  
of the air conditioner once?  
NO  
Replace coil valve.  
YES  
Are temp. sensors of indoor/outdoor units correctly set to the holder?  
NOTE :  
The temperature sensors which are used to control pulse motor valve  
include indoor heat exchanger sensor (TC), outdoor heat exchanger temp.  
sensor (TE), outdoor suction temp. sensor (TS) and outdoor sensor (TO).  
NO  
Set it correctly.  
YES  
Gas amount check and valve clogging check  
Remove TC sensor connector from the P.C. board in indoor unit.  
(Remove connector from the P.C. board.)  
Operate the air conditioner in COOL mode by TEMP button  
(Beepsound is heard if keeping pushed for 10 seconds.).  
The operation enters temporary operation mode which fixes opening degree of compressor speed.  
Check condensation at outlet of PMV, and then check operating pressure from the service port.  
Existence of condensation at outlet of P.M.V.  
YES  
Replace valve.  
Add gas.  
If there is condensation at outlet (1/4 inch=Ø6.35mm valve side),  
the valve is clogged.  
Check the operating pressure from service port, and add gas if pressure is low.  
72 –  
11-7. Troubleshooting  
11-7-1. How to Check Whether the Air Purifier is Good or Not  
Turn off the power breaker once,  
and turn on again after 10 seconds.  
NO  
Does the OPERATION indicator flash?  
To item Power supply is not turned on”  
YES  
Turn off the power breaker and remove  
CN34 (Micro switch connector).  
1
2
Short-circuit between  
and  
pin  
of CN34 at PC side, and turn on the  
power breaker after 10 seconds.  
Is DC12V applied  
Is DC12V applied  
NO  
NO  
1
1
2
between  
(Red/DC12V) and  
between  
(+) and  
()  
(Brown/GND) of CN1 of the  
high-voltage generator?  
of CN33 of the main  
P.C. board (MCC5020)?  
YES  
YES  
Replace the main P.C. board (MCC5020)  
Is there conduction of  
micro-switch connector under  
OFF status of the micro-switch  
(Front panel opened)?  
YES  
NO  
Micro-switch is stuck  
Replace micro-switch.  
• Conduction check of micro-switch  
Push the switch  
NO  
Is there conduction of  
micro-switch connector under  
ON status of the micro-switch  
(Front panel closed)?  
Micro-switch malfunction  
YES  
ON  
ON  
1) Check operation while short-circuiting CN34 of the main P.C. board.  
2) Perform air purifying operation by the remote controller.  
In this time, check that the remote controller is in status which is shortened by time on  
the reactivation preventive timer and all display indicators go on for approx. 3 seconds  
when a signal is received.  
Release the switch  
OFF  
If time on the reactivation preventive timer is not shortened,  
(
)
the high-voltage is not applied to electrode of the air purifier for approx. 1 hour.  
While the air purifier operates, check that the fan speed [AUTO] is not displayed.  
(Because the power ON/OFF is controlled on the program)  
Tester  
3) Be sure not to touch the electric dust collector, ionizer, or ionized wire unit with the human body.  
NO  
To item Only indoor fan does not operate”  
Does the indoor fan rotate?  
YES  
NO  
NO  
Does the PURE indicator (Blue) or  
the FILTER indicator (Orange) go on?  
Replace the main P.C. board (MCC5020).  
YES  
Is DC-5V to DC-10V  
applied between  
• How to check output of the air purifier  
<Caution on High Voltage!!>  
Does the PURE indicator  
go off within 2 seconds after  
it was ON, and does the FILTER  
indicator (Orange) go on?  
NO  
(Brown/Negative voltage)  
4
2
and  
(Brown/GND)  
of CN33 of the main  
P.C. board?  
Collector  
output  
YES  
YES  
Dry the electric  
dust collector  
and ionizer.  
Are the electric dust  
collector and ionizer dried?  
(Electrode check)  
NO  
YES  
GND  
Referring to the right figure, check the  
Be sure not to come  
Ionizer  
output  
high-output voltage of the air filter unit.  
(NOTE)  
to contact to the gray  
part or not to touch  
the ionized cables.  
Use an exclusive high voltage tester;  
otherwise the tester may be broken.  
High-voltage tester  
YES  
Is output of the ionizer  
approx. 4.0 kV to 4.8 kV?  
Is output of the collector  
approx. 3.0 kV to 3.8 kV?  
Refer to items, cleaning and check  
for the electric dust collector/ionizer/  
ionized wire units.  
NO  
NO  
Replace the high-voltage generator.  
When the ionized wire is  
disconnected or when dirt is  
YES  
(
)
not cleaned even cleaned,  
replace each unit.  
Are the electric dust  
collector/ionizer/ionized  
wire units dirty?  
Is an abnormal sound  
(cracking noise) heard  
from the electrode?  
YES  
No trouble  
73 –  
11-7-2. How to Check Whether the Minus Ion Generator is Good or Not  
Turn off the power breaker once,  
and turn on again after 10 seconds.  
NO  
Does the OPERATION indicator flash?  
YES  
To item Power supply is not turned on”  
Turn off the power breaker and remove  
CN34 (Micro switch connector).  
Short-circuit between  
1
and  
2
pin  
of CN34 at PC side, and turn on the  
power breaker after 10 seconds.  
Is DC12V applied  
between  
(Red/DC12V) and  
NO  
1
Replace the power P.C. board  
(MCC5020) or the housing assembly.  
(Brown/GND) of CN1 of the  
high-voltage generator  
in the air purifier?  
2
YES  
Is there conduction of  
YES  
NO  
micro-switch connector under  
OFF status of the micro-switch  
(Front panel opened)?  
Micro-switch is stuck  
Replace micro-switch.  
NO  
Is there conduction of  
micro-switch connector under  
ON status of the micro-switch  
(Front panel closed)?  
Micro-switch malfunction  
• Conduction check of micro-switch  
YES  
Push the switch  
ON  
ON  
Release the switch  
OFF  
1) Check operation while short-circuiting CN34 of the main P.C. board.  
2) Perform air purifying operation by the remote controller.  
In this time, check that the remote controller is in status which is shortened by time on  
the reactivation preventive timer and all display indicators go on for approx. 3 seconds  
when a signal is received.  
If time on the reactivation preventive timer is not shortened,  
(
)
the high-voltage is not applied to electrode of the air purifier for approx. 1 hour.  
While the air purifier operates, check that the fan speed [AUTO] is not displayed.  
Tester  
(Because the power ON/OFF is controlled on the program)  
3) Be sure not to touch the electrode with the human body.  
NO  
To item Only indoor fan does not operate”  
Does the indoor fan rotate?  
YES  
NO  
Does the PURE indicator (Blue) or  
the FILTER indicator (Orange) go on?  
Replace the main P.C. board (MCC5020).  
YES  
Does the PURE indicator  
go off within 2 seconds after  
it was ON, and does the FILTER  
indicator (Orange) go on?  
YES  
To item How to check whether  
the air purifier is good or not”  
NO  
• How to check output of minus ion  
<Caution on High Voltage!!>  
Referring to the right figure, check the  
high-voltage output of the air ionizer.  
In this time, peel the thermal insulator, and attach  
it to the original position after check operation.  
high-voltage  
unit  
NOTE :  
Use an exclusive high voltage tester; otherwise  
the tester may be broken.  
NO  
YES  
Does the electrode  
output approx. 6kV?  
No trouble  
Electrode  
NO  
Replace the  
high-voltage generator  
GND  
High-voltage tester  
74 –  
11-8. How to DiagnoseTrouble in Outdoor Unit  
11-8-1. Summarized Inner Diagnosis of Inverter Assembly  
Table 11-8-1  
Diagnosis/Process flowchart  
Item  
Contents  
Summary  
Preparation Turn OFFthe power supply  
breaker, and remove 3P  
Remove connector  
of compressor.  
connector which connects  
inverter and compressor.  
If fuse was blown, be sure to  
check the electrolytic  
capacitor and diode block.  
(DB01)  
Check  
Check  
Check whether 25A fuse  
on the control board  
assembly is blown or not.  
(F01)  
NG  
Check 25A fuse  
(Part No.F01).  
OK  
Replace fuse.  
Connect discharge  
resistance (approx. 100,  
40W) or soldering iron  
(plug) between +, –  
terminals of the electro-  
lytic capacitor (760µF) of  
C14 (with printed CAU-  
TION HIGH VOLTAGE) on  
P.C. board.  
Check  
electrolytic  
capacitor, diode  
block (DB01),  
etc.  
Discharging position  
(Discharging period  
10 seconds or more)  
Check  
NG  
terminal voltage  
of electrolytic  
capacitor.  
Plug of  
soldering  
iron  
OK  
Check  
electrolytic  
capacitor, diode  
(DB01),  
etc.  
NO  
Does outdoor  
fan rotate?  
Operation  
Turn on the power breaker,  
and operate the air condi-  
tioner in COOL mode by time  
shortening.  
YES  
OK if 760µF →  
DC280 to 380V  
Measure-  
ment  
Measure terminal voltage of  
the electrolytic capacity.  
Remove CN300 while  
pushing the part indicated  
by an arrow because CN300  
is a connector with lock.  
760µF:400WV × 3  
After operation, turn off the  
power breaker after 2  
minutes 20 seconds passed,  
and discharge the electro-  
lytic capacitor by soldering  
iron.  
Remove connector  
Check  
Stop  
CN300 of outdoor fan  
motor, and using a  
NG  
tester, check resistance  
value between every  
phases at motor side.  
Check voltage between  
motor phases.  
OK  
Check  
Measure-  
ment  
Replace  
outdoor  
fan motor.  
Is not winding between  
-

-
, or  
-
opened  
Resistance between  
phases should be  
‚ ‚ ƒ  ƒ  
or short-circuited?  
approx. 55 to 77Ω  
Is not frame grounded with  
, or  
A
B
,
 ‚  
?
ƒ
Should be 10Mor  
more.  
75 –  
Diagnosis/Process flowchart  
Item  
Contents  
Summary  
Check  
Check winding resistance  
between phases of compres-  
sor, and resistance between  
outdoor frames by using a  
tester.  
A
B
Is not grounded.  
OK if 10Mor more  
Replace control  
board assembly.  
Is not short-circuited  
between windings.  
OK if 0.51Ω → 0.57Ω  
(Check by a digital tester.)  
Check  
compressor  
winding  
NG  
Winding is not opened.  
resistance.  
OK  
Operation  
Remove connector CN300 of  
the outdoor fan motor, turn  
on the power supply breaker,  
and perform the operation.  
(Stops though activation is  
prompted.)  
Replace  
control board.  
Replace  
compressor.  
Check operation within 2  
minutes 20 seconds after  
activation stopped.  
11-9. How to Check Simply the Main Parts  
11-9-1. How to Check the P.C. Board (Indoor Unit)  
(1) Operating precautions  
1) When removing the front panel or the P.C. board, be sure to shut off the power supply breaker.  
2) When removing the P.C. board, hold the edge of the P.C. board and do not apply force to the parts.  
3) When connecting or disconnecting the connectors on the P.C. board, hold the whole housing. Do not pull  
at the lead wire.  
(2) Inspection procedures  
1) When a P.C. board is judged to be defective, check for disconnection, burning, or discoloration of the  
copper foil pattern or this P.C. board.  
2) The P.C. board consists of the following 2 parts  
a. Main P.C. board part :  
DC power supply circuit (5V, 12V, 15V), Indoor fan motor control circuit, CPU and peripheral circuits,  
buzzer, and Driving circuit of louver.  
b. Indication unit of infrared ray receiving infrared ray receiving circuit, LED :  
To check defect of the P.C. board, follow the procedure described below.  
76 –  
(3) Check procedures  
Table 11-9-1  
Check points  
No.  
Procedure  
Causes  
1
Turn off the power supply breaker Check whether or not the fuse (F01) Impulse voltage was applied or the  
and remove the P.C. board  
is blown.  
indoor fan motor short-circuited.  
assembly from electronic parts  
base. Remove the connecting  
cables from the terminal block.  
2
Remove the connector of the  
motor and turn on the power  
supply breaker. If OPERATION  
indicator flashes (once per  
second), it is not necessary to  
check steps (1 to 3) in the right  
next column.  
Check power supply voltage :  
1. The terminal block or the crossover  
cable is connected wrongly.  
1. Between No. 1 and No. 3 of CN23  
(AC 220240V)  
2. The capacitor (C01), line filter  
(L01), resistor (R05), or the diode  
(DB01) is defective.  
2. Between  
(DC 310340V)  
3. Between of C10 and output  
and  
of C03  
3. IC01, IC08 and T01 are defective.  
4. IC01, IC08 and T01 are defective.  
side of IC08 (DC 15V)  
4. Between 12V and GND  
5. Between 5V and GND  
5. IC01, IC08, IC07 and T01 are  
defective.  
3
4
Push [START/STOP] button once Check power supply voltage :  
IC03 and IC04 are defective.  
to start the unit. (Do not set the  
mode to On-Timer operation.)  
1. Between CN21 and  
No. 1 of CN23 (DC 1560V)  
Shorten the restart delay timer  
and start unit.  
Check whether or not all indicators  
(OPERATION, TIMER, FILTER,  
PURE) are lit for 3 seconds and they  
return to normal 3 seconds later.  
The indicators are defective or the  
housing assembly (CN13) is defective.  
5
Push [START/STOP] button once 1. Check whether or not the com-  
1. The temperature of the indoor heat  
exchanger is extremely low.  
to start the unit,  
pressor operates.  
Shorten the restart delay timer.  
2. Check whether or not the OP-  
ERATION indicator flashes.  
2. The connection of the heat ex-  
changer sensor is loose.  
(The connector is disconnected.)  
(CN01)  
Set the operation mode to  
COOL.  
Set the fan speed level to  
AUTO.  
3. The heat exchanger sensor and the  
P.C. board are defective.  
Set the preset temperature  
much lower than the room  
temperature. (The unit (com-  
pressor) operates continuously  
in the above condition.)  
(Refer to Table 11-4-1.)  
4. The main P.C. board is defective.  
6
If the above condition (No. 5) still  
continues, start the unit in the  
following condition.  
1. Check whether or not the com-  
pressor operates.  
1. The temperature of the indoor heat  
exchanger is extremely high.  
2. Check whether or not the OP-  
ERATION indicator flashes.  
2. The connection of the heat ex-  
changer sensor short-circuited.  
(CN01)  
Set the operation mode to  
HEAT.  
Set the preset temperature  
much higher than room tem-  
perature.  
3. The heat exchanger sensor and the  
P.C. board are defective.  
(Refer to Table 11-4-1.)  
4. The main P.C. board is defective  
7
Connect the motor connector to  
the motor and turn on the power  
supply.  
Start the unit the following  
condition.  
1. Check it is impossible to detect  
the voltage (DC 15V) between 3  
and 4 of the motor terminals.  
1. The indoor fan motor is defective.  
(Protected operation of P.C. board.)  
2. The P.C. board is defective.  
2. The motor does not operate or  
the fan motor does not rotate with  
high speed.  
3. The connection of the motor  
connector is loose.  
Set the fan speed level to HIGH.  
(The unit (compressor) operates  
continuously in the above  
condition in No. 5.)  
(But it is possible to receive the  
signal from the remote controller.)  
3. The motor rotates but vibrates  
strongly.  
77 –  
11-9-2. P.C.BoardLayout  
GND  
+12V  
+5V  
[1] Sensor characteristic table  
100  
90  
80  
70  
60  
50  
40  
30  
20  
TD  
TD : Discharge temp. sensor  
TA : Room temp. sensor  
TC : Heat exchanger temp. sensor  
TO : Outdoor temp. sensor  
TE : Outdoor heat exchanger temp. sensor  
TS : Suction temp. sensor  
TA, TC, TO, TE, TS  
40 50  
10  
0
0
10  
20  
30  
Temperature (˚C)  
78 –  
11-9-3. Indoor Unit (Other Parts)  
No.  
Part name  
Checking procedure  
1
Room temp. (TA) sensor  
Heat exchanger (TC) sensor (Normal temp.)  
Disconnect the connector and measure the resistance value with tester.  
Temperature  
TA, TC (k)  
Refer to 11-5-1. (5).  
10°C  
20°C  
25°C  
30°C  
40°C  
Sensor  
20.7  
12.6  
10.0  
7.9  
4.5  
2
3
Remote controller  
Louver motor  
MP24Z  
Measure the resistance value of each winding coil by using the tester.  
(Under normal temp. 25°C)  
Position  
Resistance value  
White  
Yellow  
Yellow  
Yellow  
Yellow  
1
2
3
4
5
1
2
3
4
5
1 to 2  
1 to 3  
1 to 4  
1 to 5  
380 ± 40Ω  
4
Indoor fan motor  
Refer to 11-5-1. (3) and (4).  
11-9-4. OutdoorUnit  
No.  
Part name  
Checking procedure  
1
Compressor  
(Model : DA111A1F-20F1)  
Measure the resistance value of each winding by using the tester.  
Red  
Position  
Red - White  
White - Black  
Black - Red  
Resistance value  
0.88 to 0.98Ω  
Under 20°C  
White  
Black  
2
Outdoor fan motor  
(Model : ICF-140-43-4R)  
Measure the resistance value of winding by using the tester.  
Red  
Position  
Red - White  
White - Black  
Black- Red  
Resistance value  
17 to 25kΩ  
17 to 25kΩ  
17 to 25kΩ  
White  
Black  
3
4
4-way valve coil  
(Model : VHV)  
Measure the resistance value of winding by using the tester.  
Resistance value  
1435 ± 144Ω  
Under 20°C  
Pulse motor valve coil  
(Model : CAM-MD12TF-6)  
Measure the resistance value of winding by using the tester.  
Position  
Red - White  
Resistance value  
1
6
3
W
R
COM  
42 to 50kΩ  
42 to 50kΩ  
42 to 50kΩ  
42 to 50kΩ  
O
White - Orange  
Brown- Yellow  
Brown- Blue  
Y BR BL  
COM  
2
5
4
Under 20°C  
5
Outdoor temperature sensor Disconnect the connector, and measure resistance value with the tester.  
(TO), discharge temperature (Normal temperature)  
sensor (TD), suction  
Temperature  
10°C 20°C 25°C 30°C 40°C 50°C  
temperature sensor (TS),  
outdoor heat exchanger  
temperature sensor (TE)  
Sensor  
TD (kW)  
100  
64  
50  
41  
27  
18  
TO,TS,TE (kW)  
20.7 12.6 10.0  
7.9  
4.5  
79 –  
11-9-5. Checking Method for Each Part  
No.  
Part name  
Checking procedure  
1. Turn OFF the power supply breaker.  
1
Electrolytic capacitor  
(For boost, smoothing)  
2. Discharge all three capacitors completely.  
3. Check that safety valve at the bottom of capacitor is not broken.  
4. Check that vessel is not swollen or exploded.  
5. Check that electrolytic liquid does not blow off.  
6. Check that the normal charging characteristics are shown in continuity test by  
the tester.  
C12 C13 C14  
Case that product is good  
Pointer swings once, and returns  
slowly. When performing test  
once again under another  
MCC-5009  
Soldered  
surface  
polarity, the pointer should return.  
C12, C13, C14 760µF/400V  
2
Diode block  
1. Turn OFF the power supply breaker.  
2. Completely discharge the four electrolytic capacitors.  
3. Remove the diode block from the PCB (which is soldered in place).  
4. Use a multimeter with a pointer to test the continuity, and check that the  
diode block has the proper rectification characteristics.  
Tester rod  
+
Resistance value  
in good product  
1
+
~
~
2
3
~
~
+
1
+ ~ ~ –  
3
2
~
~
1 2 3 4  
(DBO1)  
2
3
4
4
10 to 20 when the multimeter probe  
is reversed  
80 –  
11-10. How to Simply Judge Whether Outdoor Fan Motor is Good or Bad  
1. Symptom  
Outdoor fan motor does not rotate.  
Outdoor fan motor stops within several tens seconds though it started rotating.  
Outdoor fan motor rotates or does not rotate according to the position where the fan stopped, etc.  
Remote controller check code 02 : Outdoor block, 1A : Outdoor fan drive system error”  
2. Cause  
The following causes are considered when the outdoor fan motor does not normally rotate.  
1) Mechanical lock of the outdoor fan motor  
2) Winding failure of the outdoor fan motor  
3) Position-detect circuit failure inside of the outdoor fan motor  
4) Motor drive circuit failure of the outdoor P.C. board  
3. How to simply judge whether outdoor fan motor is good or bad  
Turn OFF the breaker.  
Disconnect two connectors (CN300) of the  
outdoor fan motor from the outdoor P.C. board.  
NO  
Does the fan rotate without trouble  
CN300  
when rotating it with hands?  
YES  
If the resistance value between  
1 (Red lead)  
2 (White lead)  
3 (Black lead)  
2 (White lead)  
3 (Black lead)  
1 (Red lead)  
NO  
of the connector  
(CN300 : Motor winding)  
is 17 to 25, it is normal.  
YES  
Fan motor is normal.  
Fan motor error  
(Outdoor P.C. board error)  
NOTE :  
However, GND circuit error inside of the motor may be accepted in some cases when the above check is  
performed.  
When the fan motor does not become normal even if P.C. board is replaced, replace the outdoor fan motor.  
81 –  
12. HOWTO REPLACE THE MAIN PARTS  
WARNING  
• Since high voltages pass through the electrical parts, turn off the power without fail before proceeding with  
the repairs.  
Electric shocks may occur if the power plug is not disconnected.  
• After the repairs have been completed (after the front panel and cabinet have been installed), perform a  
test run, and check for smoking, unusual sounds and other abnormalities.  
If this check is omitted, a fire and/or electric shocks may occur.  
Before proceeding with the test run, install the front panel and cabinet.  
• Ensure that the following steps are taken when doing repairs on the refrigerating cycle.  
1. Do not allow any naked flames in the surrounding area.  
If a gas stove or other appliance is being used, extinguish the flames before proceeding.  
If the flames are not extinguished, they may ignite any oil mixed with the refrigerant gas.  
2. Do not use welding equipment in an airtight room.  
Carbon monoxide poisoning may result if the room is not properly ventilated.  
3. Do not bring welding equipment near flammable objects.  
Flames from the equipment may cause the flammable objects to catch fire.  
If keeping the power on is absolutely unavoidable while doing a job such as inspecting the cir-  
cuitry, wear rubber gloves to avoid contact with the live parts.  
Electric shocks may be received if the live parts are touched.  
High-voltage circuits are contained inside this unit.  
Proceed very carefully when conducting checks since directly touching the parts on the control circuit  
board may result in electric shocks.  
12-1. Indoor Unit  
No.  
Part name  
Procedures  
Remarks  
Front panel  
1) Stop operation of the air conditioner and  
turn off its main power supply.  

2) Open the air inlet grille, push the arm  
toward the outside, and remove the grille.  
3) Remove the left and right air filters, and  
remove the electric dust collector.  
– 82 –  
No.  
Part name  
Procedures  
Remarks  
Front panel  
4) Press “  
” part under the front panel  

and remove hooks of the front panel from  
the installation plate.  
Pull here  
Installation plate  
Front panel  
Press here  
Press here  
Press  
5) Remove the front panel fixing screws.  
(2 pcs.)  
6) Press the electric parts box with the right  
thumb while pulling the both sides of the  
front panel toward you.  
<How to assemble the front panel>  
Electric dust  
collector  
Electric dust  
collector  
Holder  
Holder  
Protrusion  
Protrusion  
1) Press three center positions and two lower center positions of the air outlet, and  
then hang the hanging hooks (4 pcs.) at the top side of the front panel to the rear  
plate.  
2) Insert the electric dust collector and left and right air filters.  
Press in the electric dust collector until the protrusions on both sides are completely  
inserted into the holders.  
If installation is incomplete, the FILTER indicator (orange) may light.  
3) Tighten two screws.  
• Incomplete hanging or incomplete pressing may cause a dewdrops or generation  
of a fluttering sound.  
– 83 –  
No.  
Part name  
Procedures  
Remarks  
High voltage 1) Follow to the procedure in the item  
.

generator  
2) Remove the drain guide.  
3) To remove the air ionizer from the back body,  
pull it toward you while pressing down on its left  
and right claws.  
Connector  
Disconnect the two leads (black) connected to  
the air ionizer from where they are fitted into  
the other components.  
Drain guide  
(Caution: do not remove the Faston.)  
4) Disconnect the connectors of the high-voltage  
generator, and disconnect the four leads from  
where they are fitted into the other compo-  
nents.  
Air ionizer  
5) Remove the fixing screw which secures the  
high voltage generator, and remove the high  
voltage generator from the evaporator.  
Press the  
claw here  
Screw  
Press the  
claw here  
Pull here  
<How to assemble the high voltage generator>  
1) Insert the high voltage generator straight into  
the evaporator, and secure it using the fixing  
screw.  
Check whether the  
completely inserted.  
2) Pass the leads of the high voltage generator  
through the area designated and insert them  
into its connectors.  
Claw  
3) Attach the air ionizer to the back body, and  
pass the two leads (black) through the area  
designated on the electric parts box assembly.  
Claw  
Claw  
4) Attach the drain guide.  
– 84 –  
No.  
Part name  
Procedures  
Remarks  
Electric parts 1) Follow the procedure up to 4) in  
box assembly  
above.  
ƒ
2) Remove screw of earth lead attached to the  
end plate of the evaporator.  
3) Remove the lead wire cover, and remove  
connector (5P) for the fan motor and connec-  
tor (5P) for the louver motor from the electric  
parts box assembly.  
4) Pull out TC sensor from sensor holder of the  
evaporator.  
TC sensor  
Fan motor  
connector  
Louver moter  
connector  
Screw  
Fixing screw  
5) Disengage the two claws at the top of the  
display unit.  
(They can be easily disengaged by pressing  
the drain pan above the claws and at the  
same time pulling the display unit toward you.)  
Press the  
drain pan  
6) Remove the fixing screw that secures the  
electric parts box assembly, and remove the  
assembly.  
Pull the display  
unit toward you  
<How to assemble the electric parts box>  
1) Hook the top part of the electric parts box  
assembly onto the claws on the back body,  
and secure it using the fixing screw.  
Now attach the display unit. Connect the  
connectors for the fan motor and louver motor.  
2) Secure the grounding wire using the fixing  
screw. Insert the TC sensor into the sensor  
holder.  
* Be absolutely sure to loop the grounding  
wire and TC sensor leads once at the  
bottom.  
– 85 –  
No.  
Part name  
Procedures  
Remarks  
Horizontal louver 1) Remove shaft of the horizontal  
louver from the back body.  
(First remove the left shaft, and  
then remove other shafts while  
sliding the horizontal louver  
leftward.)  
Slide the horizontal  
louver leftward  
Evaporator  
1) Follow to the procedure in the item  
.
ƒ
(Heat exchanger)  
2) Remove the pipe holder from the rear side of the main unit.  
3) Remove two fixing screws at the left side of the end plate of the heat exchanger.  
Pipe holder  
Disengage the claw  
4) Remove the heat exchanger fixing holder  
Screw  
by removing the two fixing screws used to  
secure it.  
Heat exchanger  
fixing holder  
Screw  
5) Remove right side of the end plate from  
two fixing ribs while sliding slightly the  
heat exchanger rightward.  
– 86 –  
No.  
Part name  
Procedures  
Remarks  
Bearing  
1) Follow to the procedure in the items  
.

2) Remove the two fixing screws used to secure  
the left edge panel of the heat exchanger, and  
remove the two screws used to secure the  
bearing base.  
Screw  
Bearing  
base  
Screw  
3) Raise the left side of the heat exchanger  
slightly, and remove the bearing base.  
Raise the left side  
<Caution at assembling>  
• If the bearing is out from the housing, push it  
into the specified position and then incorporate  
it in the main body.  
• After assembling the bearing base, check that it  
is fitted into the stepped part of the drain pipe.  
Remove in this direction  
Bearing base  
Bearing  
Drain pipe  
Drain pipe  
Bearing base  
– 87 –  
No.  
Part name  
Procedures  
Remarks  
Fan motor  
1) Follow to the procedure in the item  
.
ƒ
2) Loosen the set screw of the cross flow fan.  
3) Remove two fixing screws of the motor band  
(Right), and then remove the motor band  
(Right).  
4) Pull the fan motor outward.  
In assembling work, install the fan motor as  
follows.  
Set screw  
• When assembling the fan motor, the fan  
motor must be installed in such a way that  
the fan motor leads will be taken out is  
positioned at the bottom front.  
• After assembling the two hooking claws of  
the motor band (right) into the main body,  
position the fan motor, insert it, and then  
secure the motor band (right) using the two  
fixing screws.  
Secure using  
the fixing screw  
Screw  
Motor band (Right)  
Screw  
Secure using  
the fixing screw  
Fan motor leads  
Cross flow fan 1) Follow to the procedure in the item  
.
ˆ
2) Remove the heat exchanger fixing holder by  
removing the two fixing screws used to  
secure it.  
Raise the  
left side  
3) Loosen the set screw of the cross flow fan.  
4) Lift the left side of the heat exchanger, and  
pull out the cross flow fan.  
Pull out here  
– 88 –  
No.  
Part name  
Cross flow fan <Caution at reassembling>  
1) At assembling work of the bearing base,  
Procedures  
Remarks  
ˆ
check that the drain pipe is surely incorpo-  
rated in the back body.  
(Otherwise, water leak is caused.)  
2) To incorporate the fan motor, remove the fan  
motor rubber (at shaft core side), incorporate  
the motor into the position in the following  
figure, and then install the fan motor.  
Bearing base  
Drain pipe  
• Install the cross flow fan so that the right  
end of the 1st joint from the right of the  
cross flow fan is set keeping 70.5 mm from  
wall of rear plate of the main unit.  
• Holding the set screw, install the cross flow  
fan so that U-groove of the fan motor comes  
to the mounting hole of the set screw.  
Joint  
70.5mm  
• Perform positioning of the fan motor as  
follows:  
• When assembling the fan motor, the fan  
motor must be installed in such a way that  
the fan motor leads will be taken out is  
positioned at the bottom front.  
• After assembling the two hooking claws of  
the motor band (right) into the main body,  
position the fan motor, insert it, and then  
secure the motor band (right) using the two  
fixing screws.  
U groove  
– 89 –  
12-2. Microcomputer  
No.  
Part name  
Procedure  
Remarks  
Common procedure 1) Turn the power supply off to stop the  
operation of air-conditioner.  
Replace terminal block,  
microcomputer ass’y and the  
P.C. board ass’y.  

2) Remove the front panel.  
• Remove the 2 fixing screws.  
3) Remove the electrical part base.  
<P.C. board layout>  
R05  
L01 C01 CN23 FUSE R04 R01  
CN10  
DB01  
C03  
T01  
IC01  
C20 IC03  
J04  
– 90 –  
12-3. Outdoor Unit  
No. Part name  
Procedure  
NOTE  
Remarks  
Common  
1. Detachment  

procedure  
Upper cabinet  
Water  
proof  
cover  
Wear gloves for this job.  
Otherwise, you may injure your  
hands on the parts, etc.  
1) Stop operation of the air conditioner,  
and turn off the main switch of the  
breaker for air conditioner.  
2) Remove the valve cover.  
(ST1TØ4 × 8L 1 pc.)  
• After removing screw, remove the  
valve cover pulling it downward.  
3) Remove wiring cover (ST1TØ4 × 8L  
2 pcs.), and then remove connecting  
cable.  
Valve cover  
4) Remove the upper cabinet.  
(ST1TØ4 × 8L 5 pcs.)  
• After removing screws, remove the  
upper cabinet pulling it upward.  
2. Attachment  
1) Attach the water-proof cover.  
Insert the bent part  
into the rear panel  
of the inverter  
NOTE  
Bring into contact  
against these parts  
The water-proof cover must be  
attached without fail in order to  
prevent rain water, etc. from entering  
inside the indoor unit.  
2) Attach the upper cabinet.  
(ST1TØ4 × 8L 5 pcs.)  
3) Perform cabling of connecting cable,  
and attach the wiring cover.  
Align the stitch line  
with the top edge  
of the front cabinet  
Bend downward, and align  
with the inside surface  
of the front cabinet  
• Place the wiring cover over the  
opening used to work on the con-  
necting wires of the side cabinet,  
and secure it using the two fixing  
screws (ST1TØ4 × 8L 2 pcs.).  
At this point, the top cushion of the  
wiring cover must be on the inside of  
the opening.  
How to mount the water-proof cover  
4) Attach the valve cover.  
(ST1TØ4 × 8L 1 pc.)  
• Insert the upper part into the square  
hole of the side cabinet, set hook  
claws of the valve cover to square  
holes (at three positions) of the main  
unit, and attach it pushing upward.  
– 91 –  
No.  
Part name  
Procedure  
Remarks  
Front cabinet 1. Detachment  
1) Perform step 1 in  
.

2) Remove the fixing screws (ST1TØ4 × 8L  
2 pcs.) used to secure the front cabinet  
and inverter cover, the screws (ST1TØ4  
× 8L 3 pcs.) used to secure the front  
cabinet at the bottom, and the fixing  
screws (ST1TØ4 × 8L 2 pcs.) used to  
secure the motor base.  
• The front cabinet is fitted into the side  
cabinet (left) at the front left side so  
pull up the top of the front cabinet to  
remove it.  
Front cabinet  
2. Attachment  
1) Insert the claw on the front left side into  
the side cabinet (left).  
2) Hook the bottom part of the front right  
side onto the concave section of the  
bottom plate. Insert the claw of the side  
cabinet (right) into the square hole in the  
front cabinet.  
Claw  
3) Return the screws that were removed  
above to their original positions, and  
attach them.the main unit, and attach it  
pushing upward.  
Square  
hole  
Concave section  
– 92 –  
No.  
Part name  
Procedure  
1) Perform work of item 1 in  
Remarks  
Inverter  
assembly  
.

ƒ
Inverter cover  
2) Remove screw (ST1TØ4 × 8L 2 pcs.) of the  
upper part of the front cabinet.  
P. C. board  
(Soldered surface)  
• If removing the inverter cover in this  
condition, P.C. board can be checked.  
• If there is no space above the unit, perform  
work of 1 in  
.
Be careful to check the inverter because  
high-voltage circuit is incorporated in it.  
Plug of  
soldering  
iron  
Discharging position  
(Discharging period  
10 seconds or more)  
3) Perform discharging by connecting  
,
polarity by discharging resistance (approx.  
10040W) or plug of soldering iron to  
,
terminals a of the C14 (printed “CAUTION  
HIGH VOLTAGE” is attached.) electrolytic  
capacitor (760µF) on P.C. board.  
Be careful to discharge the capacitor  
because the electrolytic capacitor  
cannot naturally discharge and voltage  
remains according to trouble type in  
some cases.  
A screw  
(STIT-4X8MSZN)  
Terminal block  
NOTE  
This capacitor is one with mass capacity.  
Therefore, it is dangerous that a large  
spark generates if short-circuiting  
between  
,
polarity with screwdriver,  
etc. for discharging.  
4) Remove screw (ST1TØ4 × 8L 2 pcs.) fixing  
the main body and the inverter box.  
Put the compressor Put each leads  
leads through  
the hole  
through the hole  
5) Remove the front cabinet by performing step  
1 in , and remove the fixing screws  
(ST1TØ4 × 8L) for securing the main body  
and inverter box.  
The connector is one  
with lock, so remove  
it while pushing the  
part indicated by an  
arrow.  
6) Remove various lead wires from the holder  
at upper part of the inverter box.  
7) Pull the inverter box upward.  
8) Disconnect connectors of various lead wires.  
Requirement  
As each connector has a lock mecha-  
nism, avoid to remove the connector by  
holding the lead wire, but by holding the  
connector.  
Be sure to remove the connector by  
holding the connector, not by pulling  
the lead wire.  
– 93 –  
No.  
Part name  
Procedure  
Remarks  
Control board 1. Disconnect the leads and connectors connected to  
assembly  
the other parts from the control board assembly.  
1) Leads  
CN603  
CN601 CN600  
• 3 leads (black, white, orange) connected to  
terminal block.  
CN701  
CN300  
• Lead connected to compressor :  
Disconnect the connector (3P).  
CN700 CN602  
• Lead connected to reactor :  
Disconnect the two connectors (2P).  
2) Connectors (×8)  
CN300 : Outdoor fan motor (3P: white)*  
(See NOTE)  
CN300, CN701, CN600 and  
CN603 are connectors with  
locking mechanisms: as such,  
to disconnect them, they must  
be pressed in the direction of  
the arrow while pulling them  
out.  
CN701 : 4-way valve (2P: yellow)*  
CN600 :TE sensor (2P: white)*  
CN700 : PMW (6P: white)  
CN603 :TS sensor (3P: white)*  
CN601 :TD sensor (3P: white)*  
CN602 :TO sensor (2P: white)  
NOTE  
These connectors have a disconnect prevention  
mechanism: as such, the lock on their housing  
must be released before they are disconnected.  
2. Remove the control board assembly from the P.C.  
board base. (Remove the heat sink and control  
board assembly while keeping them screwed  
together.)  
NOTE  
P.C. board base  
P.C. board  
Disengage the four claws of the P.C. board base,  
hold the heat sink, and lift to remove it.  
3. Remove the two fixing screws used to secure the  
heat sink and control board assembly.  
4. Mount the new control board assembly.  
NOTE  
When mounting the new control board assembly,  
ensure that the P.C. board is inserted properly  
into the P.C. board support groove.  
– 94 –  
No.  
Part name  
Procedure  
1. Side cabinet (right)  
1) Perform step 1 in  
Remarks  
Side cabinet  
and all the steps in  
.
ƒ
2) Remove the fixing screw (ST1TØ4 × 8L  
5 pcs.) used for securing the side  
cabinet to the bottom plate and valve  
fixing panel.  
2. Side cabinet (left)  
1) Perform step 1 in  
.
Hook the claw onto  
the bottom plate here.  
2) Remove the fixing screw (ST1TØ4 × 8L  
1 pcs.) used to secure the side cabinet  
(left) onto the heat exchanger.  
A
3) Remove the fixing screw (ST1TØ4 × 8L  
2 pc.) used for securing the side cabinet  
to the bottom plate and heat exchanger.  
B
C
The back body section is hooked  
onto the bottom plate here.  
Detail A  
Detail B  
Detail C  
Fan motor  
1) Perform work of item 1 of  
and  
.

2) Remove the flange nut fixing the fan motor  
and the propeller.  
• Flange nut is loosened by turning clock-  
wise. (To tighten the flange nut, turn  
counterclockwise.)  
Propeller fan  
Fan motor  
3) Remove the propeller fan.  
4) Disconnect the connector for fan motor  
from the inverter.  
5) Remove the fixing screws (2 pc.) holding  
by hands so that the fan motor does not  
fall.  
* Precautions when assembling the fan  
motor  
Flange nut  
Tighten the flange nut using a tightening  
torque of 4.9 N•m.  
– 95 –  
No.  
Part name  
Procedure  
Remarks  
Compressor 1) Perform work of item 1 of  
and  
,
‚ ƒ „  
,
,

.
2) Extract refrigerant gas.  
3) Remove the partition board.  
(ST1TØ4 × 8L 3 pcs.)  
4) Remove the sound-insulation material.  
5) Remove terminal cover of the compressor,  
and disconnect lead wire of the compressor  
from the terminal.  
6) Remove pipe connected to the compressor  
with a burner.  
Partition  
board  
Valve  
fixing  
plate  
Compressor  
Take care to keep the 4-way valve away  
from naked flames. (Otherwise, it may  
malfunction.)  
7) Remove the fixing screw of the bottom plate  
and heat exchanger. (ST1TØ4 × 8L 1 pc.)  
8) Remove the fixing screw of the bottom plate  
and valve fixing plate.  
(ST1TØ4 × 8L 1 pc.)  
9) Pull upward the refrigeration cycle.  
10) Remove BOLT (3 pcs.) fixing the compres-  
sor to the bottom plate.  
* Precautions when assembling the com-  
pressor.  
Tighten the compressor bolts using a  
tightening torque of 4.9 N•m.  
Reactor  
1) Perform work of item 1 of , and  
.
ƒ
ˆ
2) Remove screws fixing the reactor.  
(ST1TØ4 × 8L 4 pcs.)  
Reactor  
– 96 –  
No.  
Part name  
Electronic  
expansion valve  
coil  
Procedure  
Remarks  
1. Detachment  
1) Perform step 1 in , all the steps in  
ƒ
and 1 in  
.
2) Remove the coil by pulling it up from the  
electronic control valve body.  
Coil  
anti-turn  
lock  
2. Attachment  
1) When assembling the coil into the valve  
body, ensure that the coil anti-turn lock is  
installed properly in the pipe.  
Coil anti-turn  
lock position  
<Handling precaution>  
Coil inserting  
position  
When handling the parts, do not pull the leads.  
When removing the coil from the valve body, use  
your hand to secure the body in order to prevent  
the pipe from being bent out of shape.  
Fan guard  
1. Detachment  
Š
1) Perform work of item 1 of  
.
2) Remove the front cabinet, and put it down  
so that fan guard side directs downward.  
Minus screwdriver  
Hooking claw  
Perform work on a corrugated cardboard,  
cloth, etc. to prevent flaw to the product.  
3) Remove the hooking claws by pushing minus  
screwdriver according to the arrow mark in  
the right figure, and remove the fan guard.  
2. Attachment  
1) Insert claws of the fan guard in the holes  
of the front cabinet. Push the hooking  
claws (9 positions) by hands and fix the  
claws.  
All the attaching works have completed.  
Check that all the hooking claws are fixed  
to the specified positions.  
– 97 –  
No.  
Part name  
Procedure  
Remarks  
TE sensor (outdoor heat exchanging temperature sensor)  
11  
• Attachment  
With the leads pointing downward and the sensor leads  
pointing in the direction shown in the figure, install the sensor  
onto the straight pipe part of the condenser output pipe.  
Detail A  
Arrow D  
Detail B  
Detail C for 13, 16GAVP-E  
Detail C for 10GAVP-E  
Detail C  
TS sensor (Suction pipe temperature sensor)  
12  
• Attachment  
• Shown in the above figure is the  
model 13GAVP-E.  
With its leads pointing downward, point the sensor in the  
direction of the packed valve, and install it onto the straight  
pipe part of the suction pipe.  
• The sensor mounting positions  
in the model 10GAVP-E are all  
the same with the sole excep-  
tion of the TE sensor. Refer to  
the figure shown on the left.  
TD sensor (Discharge pipe temperature sensor)  
13  
14  
• Attachment  
With its leads pointed downward, install the sensor onto the  
vertical straight pipe part of the discharge pipe.  
TO sensor (Outside air temperature sensor)  
• Attachment  
Insert the outdoor air temperature sensor into the holder, and  
install the holder onto the heat exchanger.  
Arrow D  
TO sensor  
Detail B  
TS sensor  
Detail A  
TD sensor  
CAUTION  
During the installation work (and on its completion), take care not to damage the coverings of  
the sensor leads on the edges of the metal plates or other parts. It is dangerous for these  
coverings to be damaged since damage may cause electric shocks and/or a fire.  
CAUTION  
After replacing the parts, check whether the positions where the sensors were installed are the  
proper positions as instructed. The product will not be controlled properly and trouble will result  
if the sensors have not been installed in their proper positions.  
– 98 –  
No.  
Part name  
Procedure  
Remarks  
Replacement of  
temperature sensor  
for servicing only  
1) Cut the sensor 100 mm longer than old  
one.  
15  
Cutting here  
100  
Thermal  
sensor part  
Connector  
2) Cut the protective tube after pulling out  
it (200 mm).  
Common service  
parts of sensor TO,  
TS, TE, TD  
3) Move the protective tube toward the  
thermal sensor side and tear the tip of  
lead wire in two then strip the covering  
part.  
Cutting here  
200  
4) Pass the stripped part through the  
thermal constringent tube.  
Thermal  
constringent tube  
5) Cut the old sensor 100 mm length on  
the connector side, and recycle that  
connector.  
Cutting here  
100  
6) Tear the lead wire in two on the con-  
nector side and strip the covering part.  
7) Twist the leads on the connector and  
sensor sides, and solder them.  
Soldered part  
8) Move the thermal constringent tubes  
toward the soldered parts and heat  
them with the dryer and constring  
them.  
Dryer  
9) Wind the attached color tape round the  
both terminals of the protective tube  
when colored protective tube is used.  
Winding the color tape  
10) Fix the sensor again.  
NOTE  
1) Store the joint part of the sensor and the connector in the electric parts  
box.  
2) Never joint them near the thermal sensor part. Otherwise it would cause  
insulation inferiority because of dew drops.  
3) When replacing the sensor using the colored protective tube, wind the  
color tape matching the color of that tube.  
These are parts for  
servicing sensors.  
Parts name  
Q'ty  
1
Remarks  
Length : 3m  
1
2
3
4
5
6
Sensor  
Please check that  
the accessories  
shown in the right  
table are packed.  
Sensor Spring (A)  
Sensor Spring (B)  
Thermal constringent tube  
Color tape  
1
For spare  
1
For spare  
3
Including one spare  
9 colors  
1
Terminal  
3
– 99 –  
MCC-5009  
– 100 –  
13. EXPLODED VIEWS AND PARTS LIST  
13-1. Indoor Unit (1)  
240  
238  
234  
247  
217  
209  
213  
214  
216  
235  
225, 226  
212  
236  
230  
223  
203  
201  
221, 222, 224  
246  
215  
211  
210  
218, 219  
207  
227  
206  
205  
202  
228  
245  
239  
229  
204  
232  
233  
The parts in the following parts list are conformed to RoHS.  
Therefore be sure to use the following parts for repairing and replacing.  
Location  
No.  
Part  
No.  
Location  
No.  
Part  
No.  
Description  
Description  
201  
202  
203  
204  
205  
206  
207  
209  
210  
211  
212  
213  
214  
215  
216  
217  
218  
219  
43005633 Panel Ass’y, Front  
43005610 Grille, Air Inlet  
4301V052 Plate, Fix  
43080512 Filter, Air, Right  
43080521 Filter, Air, Left  
43009675 Louver, Horizontal  
43009682 Louver, Vertical  
4302C067 Motor, Fan  
4302C063 Motor, Louver  
4306A024 Cord, Motor, Louver  
43039363 Band, Motor, Left  
43039321 Base, Bearing  
43020346 Fan, Cross Flow  
43039314 Band, Motor  
223  
43049674 Spring, Suction  
(B16GKVP-E)  
43047673 Pipe, Inlet  
224  
225  
43044803 Evaporator  
(B10GKVP-E, B13GKVP-E)  
43044804 Evaporator (B16GKVP-E)  
43039324 Guide, Drain  
226  
227  
228  
229  
230  
232  
233  
234  
235  
236  
238  
239  
240  
245  
246  
247  
43049728 Guide, Drain, Left  
43019904 Holder, Sensor  
43049770 Holder, Evaporator, Right  
43062256 Cover, Terminal  
43062247 Cover, Lead  
43082293 Plate, Installation  
4306S577 Remote Controller  
43083071 Holder, Remote, Comtroller  
43003307 Body Ass’y, Back  
43070188 Hose, Drain  
43020253 Bearing  
4301V028 Holder, Pipe  
43049701 Pipe, Shield (B16GKVP-E)  
43079268 Cap, Drain  
43049698 Pipe, Shield  
43080516 Electrical Air Purifying Filter  
43080527 Generator Ass’y, HV  
4308N732 Owner’s Manual  
(B10GKVP-E, B13GKVP-E)  
221  
222  
43047671 Pipe, Outlet  
(B10GKVP-E, B13GKVP-E)  
43047672 Pipe, Outlet (B16GKVP-E)  
– 101 –  
Indoor Unit (2)  
402  
407, 408, 409  
403  
404  
406  
410  
401  
405  
The parts in the following parts list are conformed to RoHS.  
Therefore be sure to use the following parts for repairing and replacing.  
Location  
No.  
Part  
No.  
Location  
No.  
Part  
No.  
Description  
Description  
401  
402  
403  
404  
405  
406  
4306A123 Terminal Block, 2P  
43062263 Cover, E-Parts  
43050425 Sensor, TC (F6)  
43050426 Sensor, TA  
407  
408  
409  
410  
4306S709 P.C. Board Ass’y  
(B10GKVP-E)  
4306S710 P.C. Board Ass’y  
(B13GKVP-E)  
4306S711 P.C. Board Ass’y  
(B16GKVP-E)  
4306S728 P.C. Board Ass’y, WRS-LED  
43051346 SW-Micro Ass’y  
43067115 Clamp, Cord  
– 102 –  
13-2. Outdoor Unit  
4
44  
2
28, 29  
30, 31  
47  
6
27  
48  
14, 15, 17, 18, 20  
21, 23, 24, 25, 26  
10  
11, 12  
43  
36  
38  
8
9
33  
3
13, 16, 19, 22  
34  
35  
37  
2
32  
35  
3
40  
39  
7
41  
42  
34  
7
1
5
45  
46  
10  
– 103 –  
The parts in the following parts list are conformed to RoHS.  
Therefore be sure to use the following parts for repairing and replacing.  
Location  
No.  
Location  
No.  
Part  
Description  
Part  
Description  
1
2
43005657 Cabinet, Front  
43005642 Cabinet, Upper  
43005658 Cabinet, Side, Right  
43005634 Cabinet, Side, Left  
4301V035 Guard, Fan  
24  
25  
26  
27  
28  
43047681 Cap, Valve, Packed, 12.7  
(16GAVP-E)  
43047674 Cap, Charge, Port  
(10GAVP-E, 13GAVP-E)  
3
4
43047675 Cap, Charge, Port  
(16GAVP-E)  
5
6
4301V053 Guard, Fin  
44246239 Tube, Capillary, I.D 1.2  
(13GAVP-E, 16GAVP-E)  
7
43042489 Base Ass’y  
8
43119471 Cover, Valve, Packed  
43062262 Cover, Wiring Ass’y  
43046444 Valve, 4-Way,  
STF-0108Z, RoHS  
9
10  
43041634 Compressor,  
DA111A1F-20F1, RoHS  
29  
30  
43046443 Coil, 4-Way valve  
37546848 Valve, Pulse, Motor,  
CAM-B22YGTF-3  
11  
12  
43043749 Condenser Ass’y  
(10GAVP-E)  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
37546849 Coil, PMV, CAM-MD12TF-6  
43058277 Reactor  
43043751 Condenser Ass’y  
(13GAVP-E, 16GAVP-E)  
4302C068 Motor, Fan, ICF-140-43-4R  
43020329 Fan, Propeller, PJ421  
43047669 Nut, Flange  
13  
14  
37546845 Valve, Packed, 6.35  
43046442 Valve, Packed, 9.52  
(10GAVP-E, 13GAVP-E)  
43039392 Base, Motor Ass’y  
43004233 Plate, Partition  
15  
37546846 Valve, Packed, 12.7  
(16GAVP-E)  
4301V064 Plate, Fix, Valve, Packed  
43032441 Nipple, Drain  
16  
17  
43147196 Bonnet, 1/4 IN  
43047401 Bonnet, 3/8 IN  
(10GAVP-E, 13GAVP-E)  
43089160 Cap, Waterproof  
4301P703 Mark, TOSHIBA  
4301P702 Mark, DAISEIKAI  
43049749 Rubber, Cushion  
43062176 Sleeve, Flag  
18  
19  
20  
43147195 Bonnet, 1/2 IN (16GAVP-E)  
43047676 Nut, Flare, 6.35  
43047677 Nut, Flare, 9.52  
(10GAVP-E, 13GAVP-E)  
21  
22  
23  
43047678 Nut, Flare, 12.7 (16GAVP-E)  
43047679 Cap, Valve, Packed, 6.35  
43063321 Holder, Sensor (TD)  
43063322 Holder, Sensor (TS)  
43063325 Holder, Sensor (TE)  
43063339 Holder, Sensor (TO)  
43047680 Cap, Valve, Packed, 9.52  
(10GAVP-E, 13GAVP-E)  
– 104 –  
13-3. P.C. Board Layout  
704 Base, P.C. Board  
706 Sensor, TD (Ø4)  
701 Sensor, TE  
702 Sensor, TS  
703 Sensor, TO  
707 P.C. Board Ass’y  
705 Terminal (6P)  
The parts in the following parts list are conformed to RoHS.  
Therefore be sure to use the following parts for repairing and replacing.  
Location  
No.  
Location  
No.  
Part  
Description  
Part  
Description  
701  
702  
703  
704  
43050422 Sensor, TE  
43050423 Sensor, TS  
43050427 Sensor, TO  
43062228 Base, P.C. board  
705  
706  
707  
43160566 Terminal Block, 6P  
43050430 Sensor, TD  
4306S737 P.C. board Ass’y, MCC5009  
– 105 –  
Appendix  
Cord Heater Installation Work  
Applicable Models: RAS-10GAVP-E, RAS-13GAVP-E, RAS-16GAVP-E  
1. Required parts for installation work (Recommendation)  
The above products conform to RoHS (2002/95/EC).Therefore when procuring and using the following recom-  
mended parts at local site, it is recommended to confirm each part conforms to RoHS before use.  
No. Part name Q’ty  
Specifications/Vendor  
Remarks  
1
2
Cord heater  
Thermostat  
1
1
Drain line heaters CSC2 (1.5m, 40W/m) by Flexelec com.  
(Please go to the following URL.)  
http://www.flexelec.com  
Procured locally  
US-622AXRLQE by ASAHI KEIKI  
Operating temperature: on 4 ± 4°C, off 15 ± 3°C  
Procured locally  
A thermostat holder is incorporated with a thermostat in the package.  
(Please go to the following URL.)  
http://www.asahikeiki.co.jp/product/product.html  
On self-responsibility, you can use a product manufactured by other  
company (For example, Texas Instruments) if its characteristics are  
equivalent to those of ASAHI KEIKI. However, when the shape of the  
thermostat holder is different from that of ASAHI KEIKI, apply some  
treatment to No.14 thermostat fixing plate and then fix the holder.  
3
4
5
Fuse  
1
1
ES3-5000, 250V / 5A by NAGASAWA Electric Co.  
(Please go to the following URL.)  
http://www.nagasawa-el.co.jp/  
On self-responsibility, you can use a product manufactured by other  
company if its characteristics are equivalent to those of NAGASAWA  
Electric Co.  
Procured locally  
Procured locally  
Procured locally  
Fuse holder  
GM1H-02 by NAGASAWA Electric Co.  
(Please go to the following URL.)  
http://www.nagasawa-el.co.jp/  
On self-responsibility, you can use a product manufactured by other  
company if its characteristics are equivalent to those of NAGASAWA  
Electric Co.  
P-shape  
clamp  
13 Use heat-resistance, weatherproof and non-hydrolytic type.  
Material: 4-fluorinated ethylene copolymer  
Harness diameter: Ø5.9  
Use equivalence with the above specifications.  
11 pieces are used to fix the cord heater to the outdoor unit base plate.  
One piece is used to fix the power cord to the thermostat fixing plate .  
One piece is used to fix the power cord to the terminal fixing plate.  
6
P-shape  
clamp  
1
Use heat-resistance, weatherproof and non-hydrolytic type.  
Material: 4-fluorinated ethylene copolymer  
Procured locally  
Harness diameter: Ø9.1  
Use equivalence with the above specifications.  
One piece is used to fix the cord heater to the outdoor unit base plate.  
7
8
Screw  
Screw  
12 Self-tapping screw type-B Ø4 × 6mm, truss head, stainless  
These screws are used to fix the cord heater to the outdoor unit base  
plate with P-shape clamp.  
Procured locally  
Procured locally  
4
Self-tapping screw type-B Ø4 × 8mm, truss head, stainless  
Two screws are used to fix the thermostat fixing plate to the side cabinet (R).  
One screw is used to fix the power cord to the thermostat fixing plate.  
One screw is used to fix the power cord to the terminal fixing plate.  
9
Screw  
2
Self-tapping screw type-B Ø3.5 × 6mm, pan head  
These screws are used to fix the thermostat to the thermostat fixing  
plate with the thermostat holder.  
Procured locally  
10 Faston  
2
2
#250 They are used for the connecting part to the thermostat.  
UL sleeve for #250  
Procured locally  
Procured locally  
11 Sleeve for  
Faston  
12 Close-end  
connector  
2
Use the most appropriate connector with the power cord diameter.  
Procured locally  
Appendix-1  
Appendix  
No. Part name Q’ty  
Specifications/Vendor  
2-cores x 0.75mm² or more, H05RN-F  
Remarks  
13 Power cord  
1
1
Procured locally  
14 Thermostat  
fixing plate  
Material: SGCC-Z08, Board thickness: 0.8t  
Procured locally  
(Drawing attached)  
15 PVC tube  
1
1
Inside diameter Ø8 x outside diameter Ø11 x 70 mm  
Procured locally  
Procured locally  
16 Shield tube  
Inside diameter Ø18 x outside diameter Ø26 x 70 mm  
Material: Polyethylene foam  
17 Bundling tie  
1
Bundling tie for securing the wires  
Material: 6/6 nylon  
Procured locally  
NOTE: The parts on the above table are recommended parts.  
2. Required tools for installation work  
No.  
1
Part name  
Plus screwdriver  
Wrench  
Specifications  
Usage  
It is used for disassembling and assembling of each cabinet.  
2
It is used for disassembling and assembling of compressor fixing nuts.  
3
Motor drill  
Drill diameter:  
Ø3.2 and Ø5.0  
It is used to make the additional holes on the base or the side cabinet  
(R).  
4
5
Faston crimping tool Fixing jig for #250  
Close-end connec-  
tor crimping tool  
6
7
8
9
Cutting plier  
Stripper  
Cutter knife  
Insulation tape  
10 Metal-cutting shears  
It is used to process the side cabinet (L).  
Appendix-2  
Appendix  
3. Cord heater installation wiring diagram  
L
N
Fuse  
Thermostat  
Cord heater  
* Be sure to connect the fuse and the thermostat to LIVE side of the cord heater.  
Outdoor unit  
Earth leakage circuit breaker  
Earth leakage circuit breaker  
Power supply for air conditioner  
Power supply for cord heater  
NOTE:  
Separate the cord heater power from the air conditioner power, and connect it to its exclusive breaker.  
By doing so, the power consumption can be decreased because the breaker can be turned off if there is no  
possibility of freezing of the base plate in cooling operation, etc.  
When the cord heater power is connected to the inverter P.C. board assembly or others without connected to the  
exclusive breaker, the control P.C. board of the inverter assembly may cause a failure.  
When the cord heater has been mounted on a base plate, do not mount the water-proof cap and drain nipple which  
are provided with the outdoor unit on the base plate.  
Appendix-3  
Appendix  
4. Cord heater installation work procedure  
No.  
Photo / Explanatory diagram  
Procedure  
Remove each cabinet, inverter assembly, motor base assembly, and partition board assembly.  
* Do not damage the electric parts such as cables, connectors, etc. while this work.  
1
Remove the upper cabinet and the valve cover.  
Upper cabinet  
Related parts / Screws list  
Used screw  
Part name  
Screw type  
Quantity  
1-1  
Upper cabinet  
Valve cover  
Ø4 × 8  
5
1
Ø4 × 1  
Valve cover  
Remove the front cabinet, the wiring cover and the  
water-proof cover.  
Water-proof  
cover  
Related parts / Screws list  
Wiring cover  
Used screw  
Part name  
1-2  
Screw type  
Quantity  
Front cabinet  
Wiring cover  
Ø4 × 8  
7
2
Ø4 × 8  
Front cabinet  
Remove the side cabinet (R/L) and the inverter  
assembly.  
Side cabinet (L)  
Inverter assembly  
Side cabinet (R)  
Related parts / Screws list  
Used screw  
Part name  
Screw type  
Quantity  
1-3  
Side cabinet (R)  
Side cabinet (L)  
Inverter assembly  
Ø4 × 8  
7
3
1
Ø4 × 8  
Ø4 × 8  
Remove the inverter assembly.  
No. Part name Connector No.  
Connector color  
White  
1
2
3
4
TE sensor  
TD sensor  
TO sensor  
TS sensor  
CN600  
CN601  
CN602  
CN603  
White  
White  
White  
4-way valve  
coil  
5
CN701  
Yellow  
1-4  
6
7
PMV coil  
CN700  
CN300  
White  
White  
Fan motor  
Compressor  
lead  
8
9
(Intermediate connector)  
(Intermediate connector)  
White  
White  
Reactor  
(2 pieces.)  
Appendix-4  
Appendix  
No.  
Photo / Explanatory diagram  
Procedure  
Remove the motor base assembly, partition plate assembly  
and the sound insulation board.  
Motor base  
assembly  
Related parts / Screws list  
Partition plate  
assembly  
Used screw  
Part name  
Screw type  
Quantity  
1-5  
Motor base assembly  
Ø4 × 8  
2
(Including motor and fan)  
Partition plate assembly  
(Including reactor)  
Ø4 × 8  
3
Sound  
insulation board  
Remove the fixing screws of the heat exchanger and the  
valve fixing plate. Remove the compressor fixing bolt.  
Valve fixing plate  
Heat exchanger  
Related parts / Screws list  
Used screw  
Part name  
Screw type  
Ø4 × 8  
Ø4 × 8  
bolt  
Quantity  
Heat exchanger  
Valve fixing plate  
Compressor  
1
1
3
1-6  
Compressor  
As shown in the left figure, remove the set of refrigeration cycle  
assembly from the outdoor unit base plate.  
* In this time, work attentively so that the cycle pipes are not  
damaged by dent or deformation. Apply protective  
measures to pipes if necessary.  
1-7  
Appendix-5  
Appendix  
No.  
Photo / Explanatory diagram  
Cord heater installation work  
Procedure  
Drill a hole on the outdoor unit base plate, and fix the cord heater to the outdoor unit base plate using P-shape  
clamp.  
2
Connect the cord heater cables.  
Using a motor drill, etc., drill Ø3.2 holes on the outdoor unit base plate. (12 positions) See Appendix-10 for the  
additional hole positions.  
2-1  
These holes are used to fix the cord heater to the outdoor unit base plate with P-shape clamp.  
Insert the PVC tube into the cord heater.  
This tube is designed to protect the cord heater from  
the fixing screws used to secure the anchoring feet.  
As shown in the left figure, install the cord heater  
(1.5m) to the outdoor unit base plate by using P-  
shape clamp and screws (Self-tapping screw type-B  
Ø4 × 6mm, stainless).  
Pay attention to the direction of P-shape clamp so  
that it is set to the same direction in the left figure.  
The PVC tube must be inserted  
into the cord heater between  
the fixing screws in order to  
protect the cord heater from  
these screws.  
* If the drain port is frozen due to installation  
status, etc., draw around the cord heater so that  
the end part of the heater is inserted into the  
drain port. In this case, add some fixing  
positions to fix the cord heater surely.  
2-2  
Under no circumstances must  
the tube be allowed to ride over  
the tip of the fixing screws.  
PVC tube  
Ø9.1 P-shape clamp  
* The end part from the marked part of the cord  
heater heats up. When there is the heating part  
near the electric parts box, a fire may generate.  
Be sure to set the heating part on the outdoor  
unit base plate at the fan room side or near it.  
(within 20cm from the outdoor unit base plate)  
* Be careful that the cord heater does not hit the  
fan.  
Fix the cord heater without any loosening or sag.  
Enlarged  
marked part  
Heating part  
Drill a hole on the side cabinet (R) for fixing the  
thermostat fixing plate.  
Added hole 2-φ5  
Ø5 hole at two positions  
5
When drilling a hole on the side cabinet (R), be  
sure not to damage the cabinet.  
46  
7
2-3  
Side cabinet (R)  
Appendix-6  
Appendix  
No.  
Photo / Explanatory diagram  
Procedure  
Rework the side cabinet (L) to remove part of it.  
Side cabinet (L)  
The area to be removed is indicated by the shaded  
lines in the left figure.  
After removing part of the side cabinet (L), deburr the  
edges of the side cabinet (L).  
2-4  
Delete  
Perform end process and bundling of each cable.  
Using fixing screws (Self-tapping screw type-B Ø3.5  
× 6mm), fix the thermostat to the thermostat fixing  
plate.  
Close-end connector  
insulation tape  
Thermostat  
Power cord  
Perform end process for various lead cables and  
connect them according to the wiring diagram.  
Attach #250 Faston and UL-approved sleeves each  
to the end of lead cables which are connected to the  
thermostat.  
2-5  
Cord heater  
* Transparent  
Using insulation tape, apply protective measures to  
the connected parts by the close-end connectors.  
Thermostat  
fixing plate  
L side  
Using P-shape clamp and the screws (Self-tapping  
screw type-B Ø4 × 8mm), fix the power cord to the  
thermostat fixing plate.  
P-shape clamp  
Fuse  
Fuse holder  
When the power cord size does not match with P-  
shape clamp, procure the most appropriate one at  
the local site.  
Appendix-7  
Appendix  
No.  
Photo / Explanatory diagram  
Procedure  
Assembly  
Return a set of the refrigeration cycle assembly into the outdoor unit base plate and reassemble sound insulation  
board, partition plate assembly, fan motor assembly, and side cabinet (R/L) as original. Fix the thermostat fixing  
plate to the side cabinet (R), built in the inverter assembly, and then connect various cables. After then,  
incorporate front cabinet, upper cabinet, wiring cover, and valve cover as before.  
3
Return a set of the refrigeration cycle assembly into the  
outdoor unit base plate, and assemble sound insulation  
board, partition plate assembly, fan motor assembly, and  
side cabinet (R/L) as original.  
3-1  
Using screws (Self-tapping screw type-B Ø4 × 8mm,  
stainless), fix the thermostat fixing plate to the side  
cabinet (R).  
Thermostat fixing plate  
Side cabinet (R)  
3-2  
After incorporating the inverter assembly as before,  
furthermore perform cable process for cord heater and  
power cord.  
Do not make cord heater loose.  
Do not put the heating part near the electric parts box.  
For the cord heater, perform cable process so that there  
is no looseness or sag at the fan side.  
Perform cable process for collected  
cord heater and fan motor lead cables.  
Perform cable process for the cord heater together with  
the fan motor lead cable, and collect the remained part  
of cables at cable process part of the inverter.  
Secure the power cord for the cord heater to the  
terminal block mounting plate using the P-shape clamp,  
and pull it out from the wiring area of the side cabinet  
(R).  
P-shape  
clamp  
3-3  
* Check that there is the marked part of the cord heater  
on the outdoor unit base plate or near it.  
When there is the heating part near the electric parts  
box, a fire may generate.  
Power cord for  
cord heater  
Since the lead wires connected to the cord heater and  
thermostat may come into contact with the edges of the  
sheet metal or tips of the screws, wrap the shield tubes  
around the leads to protect them and use the bundling  
ties to secure them.  
To keep the lead wires from coming into contact with the  
edges of the sheet metal or tips of the screws, wrap the  
shield tubes around the leads to protect them and use  
the bundling ties to secure them.  
3-4  
4
Incorporate front cabinet, upper cabinet, wiring cover, water-proof cover and valve cover as before.  
In installation work, connect power cord for the cord heater to another breaker separated from one for power cord  
of the air conditioner.  
Appendix-8  
Appendix  
5. Drawing of thermostat fixing plate  
37  
2-Ø3.4 burring hole  
(Upward)  
18  
11  
11  
11  
18  
3-Ø3.4 burring hole  
(Downward)  
45  
Material: SGCC-Z08,Thickness: 0.8t  
Appendix-9  
Appendix  
6. Diagram showing positions φ3.2 mm holes to be additionally drilled in base plate  
Appendix-10  
This product is compliant with Directive 2002/95/EC, and cannot be disposed as unsorted municipal waste.  
TOSHIBA CARRIER CORPORATION  
2 CHOME 12-32, KONAN, MINATOKU, TOKYO, 108-0075, JAPAN  
Copyright © 1999 to 2005 TOSHIBA CARRIER CORPORATION, ALL Rights Reserved.  

Metrologic Instruments Focuse Is1650 User Manual
Panasonic Kx Fp121 User Manual
Samsung Avxcs User Manual
Samsung Ch24zax User Manual
Sanyo N 250aaa User Manual
Sanyo Ur 121 User Manual
Schumacher Automatic Ps 1562a User Manual
Trion Air Boss Dc 128 User Manual
Vtech Baby Accessories 91 002537 005 User Manual
Xantrex Technology Dr1512e User Manual