FILE NO. A05-008
SERVICE MANUAL
SPLIT TYPE
Indoor Unit
Outdoor Unit
<High Wall, Heat Pump Type>
<Heat Pump Type>
RAS-B10GKVP-E RAS-10GAVP-E
RAS-B13GKVP-E RAS-13GAVP-E
RAS-B16GKVP-E RAS-16GAVP-E
R410A
PRINTED IN JAPAN, Nov.,2005 ToMo
1. SAFETY PRECAUTIONS
For general public use
Power supply cord of outdoor unit shall be more than 1.5 mm 2 (H07RN-F or 245IEC66) polychloroprene
sheathed flexible cord.
• Read this “SAFETY PRECAUTIONS” carefully before servicing.
• The precautions described below include the important items regarding safety. Observe them without fail.
• After the servicing work, perform a trial operation to check for any problem.
• Turn off the main power supply switch (or breaker) before the unit maintenance.
CAUTION
New Refrigerant Air Conditioner Installation
• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT
DESTROY OZONE LAYER.
R410A refrigerant is apt to be affected by impurities such as water, oxidizing membrane, and oils because
the working pressure of R410A refrigerant is approx. 1.6 times of refrigerant R22. Accompanied with the
adoption of the new refrigerant, the refrigeration machine oil has also been changed.Therefore, during
installation work, be sure that water, dust, former refrigerant, or refrigeration machine oil does not enter into
the new type refrigerant R410A air conditioner circuit.
To prevent mixing of refrigerant or refrigerating machine oil, the sizes of connecting sections of charging
port on main unit and installation tools are different from those used for the conventional refrigerant units.
Accordingly, special tools are required for the new refrigerant (R410A) units. For connecting pipes, use new
and clean piping materials with high pressure fittings made for R410A only, so that water and/or dust does
not enter. Moreover, do not use the existing piping because there are some problems with pressure fittings
and possible impurities in existing piping.
CAUTION
TO DISCONNECT THE APPLIANCE FROM THE MAIN POWER SUPPLY
This appliance must be connected to the main power supply by a circuit breaker or a switch with a contact
separation of at least 3 mm.
The installation fuse (25A D type
) must be used for the power supply line of this air conditioner.
DANGER
• ASK AN AUTHORIZED DEALER OR QUALIFIED INSTALLATION PROFESSIONAL TO IN-
STALL/MAINTAIN THE AIR CONDITIONER.
INAPPROPRIATE SERVICING MAY RESULT IN WATER LEAKAGE, ELECTRIC SHOCK OR FIRE.
• TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE
ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
DANGER: HIGH VOLTAGE
The high voltage circuit is incorporated.
Be careful to do the check service, as the electric shock may be caused in case of touching parts
on the P.C. board by hand.
• CORRECTLY CONNECT THE CONNECTING CABLE. IF THE CONNECTING CABLE IS INCOR-
RECTLY CONNECTED, ELECTRIC PARTS MAY BE DAMAGED.
• CHECK THAT THE EARTH WIRE IS NOT BROKEN OR DISCONNECTED BEFORE SERVICE AND
INSTALLATION. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
– 3 –
• DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS. FAILURE
TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
• TO PREVENT THE INDOOR UNIT FROM OVERHEATING AND CAUSING A FIRE HAZARD, PLACE
THE UNIT WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEAT
REGISTORS, FURNACE, STOVES, ETC.
• WHEN MOVING THE AIR-CONDITIONER FOR INSTALLATION IN ANOTHER PLACE, BE VERY CARE-
FUL NOT TO ALLOW THE SPECIFIED REFRIGERANT (R410A) TO BECOME MIXED WITH ANY
OTHER GASEOUS BODY INTO THE REFRIGERATION CIRCUIT. IF AIR OR ANY OTHER GAS IS
MIXED IN THE REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CIRCUIT WILL
BECOME ABNORMALLY HIGH AND IT MAY RESULT IN THE PIPE BURSTING AND POSSIBLE PER-
SONNEL INJURIES.
• IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE SERVICE
WORK AND THE INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE
REFRIGERANT GAS IS HEATED, SUCH AS BY FIRE, GENERATION OF POISONOUS GAS MAY
RESULT.
WARNING
• Never modify this unit by removing any of the safety guards or bypass any of the safety interlock
switches.
• Do not install in a place which cannot bear the weight of the unit. Personal injury and property
damage can result if the unit falls.
• After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas
may generate.
• The electrical work must be performed by a qualified electrician in accordance with the Installation
Manual. Make sure the air conditioner uses an exclusive circuit.
An insufficient circuit capacity or inappropriate installation may cause fire.
• When wiring, use the specified cables and connect the terminals securely to prevent external
forces applied to the cable from affecting the terminals.
• Be sure to provide grounding.
Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone cables.
• Conform to the regulations of the local electric company when wiring the power supply.
Inappropriate grounding may cause electric shock.
CAUTION
• Exposure of unit to water or other moisture before installation may result in an electrical short.
Do not store in a wet basement or expose to rain or water.
• Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify
the noise level of the unit or where noise or discharged air might disturb neighbors.
• To avoid personal injury, be careful when handling parts with sharp edges.
• Perform the specified installation work to guard against an earthquake.
If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.
For Reference:
If a heating operation would be continuously performed for a long time under the condition that the outdoor
temperature is 0°C or lower, drainage of defrosted water may be difficult due to freezing of the bottom plate,
resulting in a trouble of the cabinet or fan.
It is recommended to procure an antifreeze heater locally for a safe installation of the air conditioner.
For details, contact the dealer.
– 4 –
2. SPECIFICATIONS
2-1. Specifications
RAS-B10GKVP-E/RAS-B13GKVP-E/RAS-B16GKVP-E, RAS-10GAVP-E/RAS-13GAVP-E/RAS-16GAVP-E
Indoor
Outdoor
RAS-B10GKVP-E
RAS-10GAVP-E
2.5
RAS-B13GKVP-E
RAS-13GAVP-E
3.5
RAS-B16GKVP-E
RAS-16GAVP-E
4.5
Unit model
Cooling capacity
(kW)
(kW)
(kW)
(kW)
Cooling capacity range
Heating capacity
Heating capacity range
Power supply
0.5–3.5
3.2
0.6–5.8
0.6–4.5
4.2
0.6–6.6
0.8–5.0
5.5
0.8–7.8
1 Ph/50Hz/220–240 V, 1 Ph/60Hz/220 V
Operation mode
Running current
Power consumption
Power factor
Operation mode
Running current
Power consumption
Power factor
Cooling
0.15
30
87
Cooling
Heating
0.15
30
87
Heating
Cooling
0.15
30
87
Cooling
Heating
0.15
30
87
Heating
Cooling
0.15
30
87
Cooling
Heating
0.15
30
87
Heating
(A)
(W)
(%)
Indoor
Electric
characteristics
(A) 2.48/2.37/2.26 3.25/3.10/2.96 4.25/4.06/3.89 4.52/4.31/4.13 6.45/6.17/5.90 7.07/6.76/6.47
Outdoor
(W)
(%)
(A)
520
95
3.40/3.25/3.11
680
95
890
95
4.67/4.46/4.28
945
95
1350
95
7.22/6.91/6.62
1480
95
Starting current
COP
(Cooling/Heating)
4.55/4.51
3.80/4.31
3.26/3.64
High
(Cooling/Heating) (dB•A)
42/43
43/44
45/45
Indoor
Medium (Cooling/Heating) (dB•A)
33/34
27/27
34/35
27/27
36/36
29/29
Operating
noise
Low
(Cooling/Heating) (dB•A)
Outdoor
(Cooling/Heating) (dB•A)
46/47
48/50
49/50
Unit model
RAS-B10GKVP-E
RAS-B13GKVP-E
RAS-B16GKVP-E
Height
(mm)
250
250
250
Dimension Width
Depth
(mm)
(mm)
790
215
790
215
790
215
Indoor unit
Net weight
(kg)
(W)
9
30
9
30
9
30
Fan motor output
Air flow rate
Unit model
Height
Dimension Width
Depth
(Cooling/Heating) (m³/h)
550/610
RAS-10GAVP-E
560/640
RAS-13GAVP-E
640/660
RAS-16GAVP-E
(mm)
(mm)
(mm)
(kg)
550
780
290
35
550
780
290
37
550
780
290
37
Net weight
Outdoor unit
Motor output
(W)
750
750
750
Compressor Type
Model
Twin rotary type with DC-inverter variable speed control
DA111A1F-20F1
DA111A1F-20F1
DA111A1F-20F1
Fan motor output
Air flow rate
Type
(W)
43
2150/2150
Flare connection
Ø6.35
Ø9.52
Ø6.35
Ø9.52
25
43
43
2410/2410
Flare connection
Ø6.35
Ø12.7
Ø6.35
Ø12.7
25
(Cooling/Heating) (m³/h)
2410/2410
Flare connection
Liquid side
Gas side
Ø6.35
Ø9.52
Ø6.35
Ø9.52
25
15
10
R410A
Indoor unit
Liquid side
Gas side
Piping
connection
Outdoor unit
Maximum length
Maximum chargeless length
Maximum height difference
Name of refrigerant
Weight
(m)
(m)
(m)
15
10
R410A
0.82
15
10
R410A
0.96
Refrigerant
(kg)
0.96
Power supply
3 Wires : includes earth (Outdoor)
Wiring
connection
Interconnection
4 Wires : includes earth
Indoor (Cooling/Heating) (°C)
Outdoor (Cooling/Heating) (°C)
Installation plate
21–32/0–28
5–43/–15–24
21–32/0–28
5–43/–15–24
21–32/0–28
5–43/–15–24
Usable temperature range
1
1
1
Wireless remote controller
Batteries
1
2
1
2
1
2
Remote controller holder
Zeolite-plus filter
1
1
1
1
1
1
Indoor unit
Accessory
Mounting screw
Remote controller holder
mounting screw
6 (Ø4 × 25L)
6 (Ø4 × 25L)
6 (Ø4 × 25L)
2 (Ø3.1 × 16L)
2 (Ø3.1 × 16L)
2 (Ø3.1 × 16L)
Plasma pure filter
Installation manual
Owner’s manual
Drain nipple
1
1
1
1
2
1
1
1
1
2
1
1
1
1
2
Outdoor unit
Water-proof rubber cap
• The specifications may be subject to change without notice for purpose of improvement.
– 5 –
2-2. Operation Characteristic Curve
<Cooling>
<Heating>
10
10
9
8
9
8
7
6
5
4
3
2
1
0
RAS-B10GKVP-E
RAS-B13GKVP-E
RAS-B16GKVP-E
RAS-B10GKVP-E
7
RAS-B13GKVP-E
RAS-B16GKVP-E
6
5
4
3
• Conditions
• Conditions
Indoor : DB 20˚C
2
1
0
Indoor : DB 27˚C/WB 19˚C
Outdoor : DB 35˚C
Air flow : High
Outdoor : DB 7˚C/WB 6˚C
Air flow : High
Pipe length : 7.5m
Voltage : 230V
Pipe length : 7.5m
Voltage : 230V
0
20
40
60
80
100
120
140
0
20
40
60
80
100
120
140
Compressor speed (rps)
Compressor speed (rps)
2-3. Capacity Variation Ratio According toTemperature
<Cooling>
<Heating>
120
110
100
80
60
40
20
100
90
80
70
60
50
RAS-B10GKVP-E
RAS-B13GKVP-E
RAS-B16GKVP-E
RAS-B10GKVP-E
RAS-B13GKVP-E
RAS-B16GKVP-E
• Conditions
• Conditions
Indoor : DB 20˚C
Indoor air flow : High
Pipe length : 7.5m
Indoor : DB27˚C/WB19˚C
Indoor air flow : High
Pipe length : 7.5m
0
–15
–10
–5
0
5
10
32
33 34 35 36 37 38 39 40 41 42 43 44 45 46
Outdoor temp. (˚C)
Outdoor temp. (˚C)
Capacity ratio :100% = 2.5 kW (RAS-B10GKVP-E)
3.5 kW (RAS-B13GKVP-E)
*
4.5 kW (RAS-B16GKVP-E)
– 6 –
3. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC
(R410A) which does not damage the ozone layer.
6. When an air conditioning system charged with a
large volume of refrigerant is installed in a small
room, it is necessary to exercise care so that,
even when refrigerant leaks, its concentration
does not exceed the marginal level.
The working pressure of the new refrigerant R410A
is 1.6 times higher than conventional refrigerant
(R22). The refrigerating oil is also changed in
accordance with change of refrigerant, so be careful
that water, dust, and existing refrigerant or refrigerat-
ing oil are not entered in the refrigerant cycle of the
air conditioner using the new refrigerant during
installation work or servicing time.
If the refrigerant gas leakage occurs and its
concentration exceeds the marginal level, an
oxygen starvation accident may result.
7. Be sure to carry out installation or removal
according to the installation manual.
The next section describes the precautions for air
conditioner using the new refrigerant. Conforming to
contents of the next section together with the
general cautions included in this manual, perform
the correct and safe work.
Improper installation may cause refrigeration
trouble, water leakage, electric shock, fire, etc.
8. Unauthorized modifications to the air conditioner
may be dangerous. If a breakdown occurs
please call a qualified air conditioner technician
or electrician.
3-1. Safety During Installation/Servicing
Improper repair’s may result in water leakage,
electric shock and fire, etc.
As R410A’s pressure is about 1.6 times higher than
that of R22, improper installation/servicing may
cause a serious trouble. By using tools and materi-
als exclusive for R410A, it is necessary to carry out
installation/servicing safely while taking the following
precautions into consideration.
3-2. Refrigerant Piping Installation
3-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes
and joints are mainly used. Copper pipes and joints
suitable for the refrigerant must be chosen and
installed. Furthermore, it is necessary to use clean
copper pipes and joints whose interior surfaces are
less affected by contaminants.
1. Never use refrigerant other than R410A in an air
conditioner which is designed to operate with
R410A.
If other refrigerant than R410A is mixed, pressure
in the refrigeration cycle becomes abnormally
high, and it may cause personal injury, etc. by a
rupture.
1. Copper Pipes
It is necessary to use seamless copper pipes
which are made of either copper or copper alloy
and it is desirable that the amount of residual oil
is less than 40 mg/10 m. Do not use copper
pipes having a collapsed, deformed or discolored
portion (especially on the interior surface).
2. Confirm the used refrigerant name, and use tools
and materials exclusive for the refrigerant R410A.
The refrigerant name R410A is indicated on the
visible place of the outdoor unit of the air condi-
tioner using R410A as refrigerant. To prevent
mischarging, the diameter of the service port
differs from that of R22.
Otherwise, the expansion valve or capillary tube
may become blocked with contaminants.
3. If a refrigeration gas leakage occurs during
installation/servicing, be sure to ventilate fully.
As an air conditioner using R410A incurs pres-
sure higher than when using R22, it is necessary
to choose adequate materials.
If the refrigerant gas comes into contact with fire,
a poisonous gas may occur.
Thicknesses of copper pipes used with R410A
are as shown in Table 3-2-1. Never use copper
pipes thinner than 0.8 mm even when it is
available on the market.
4. When installing or removing an air conditioner, do
not allow air or moisture to remain in the refrig-
eration cycle. Otherwise, pressure in the refrig-
eration cycle may become abnormally high so
that a rupture or personal injury may be caused.
5. After completion of installation work, check to
make sure that there is no refrigeration gas
leakage.
If the refrigerant gas leaks into the room, coming
into contact with fire in the fan-driven heater,
space heater, etc., a poisonous gas may occur.
– 7 –
Table 3-2-1 Thicknesses of annealed copper pipes
Thickness (mm)
Nominal diameter
Outer diameter (mm)
R410A
0.80
R22
0.80
0.80
0.80
1.00
1/4
3/8
1/2
5/8
6.35
9.52
0.80
12.70
15.88
0.80
1.00
2. Joints
For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants.
a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds
20 mm. In such a case, socket joints can be used.
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 3-2-3 to 3-2-6 below.
b) Socket Joints
Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose
diameter is larger than 20 mm.
Thicknesses of socket joints are as shown in Table 3-2-2.
Table 3-2-2 Minimum thicknesses of socket joints
Reference outer diameter of
copper pipe jointed (mm)
Minimum joint thickness
(mm)
Nominal diameter
1/4
3/8
1/2
5/8
6.35
9.52
0.50
0.60
0.70
0.80
12.70
15.88
3-2-2. Processing of Piping Materials
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not
enter the pipe interior, that no other oil than lubricating oils used in the installed air-water heat pump is used,
and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils
whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any
other cover.
1. Flare processing procedures and precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs, refrigerant leakage may occur.
Carefully remove all burrs and clean the cut surface before installation.
c) Insertion of Flare Nut
– 8 –
d) Flare Processing
Make certain that a clamp bar and copper
pipe have been cleaned.
ØD
By means of the clamp bar, perform the flare
processing correctly.
A
Use either a flare tool for R410A or conven-
tional flare tool.
Flare processing dimensions differ according
to the type of flare tool. When using a con-
ventional flare tool, be sure to secure “dimen-
sion A” by using a gauge for size adjustment.
Fig. 3-2-1 Flare processing dimensions
Table 3-2-3 Dimensions related to flare processing for R410A
A (mm)
Conventional flare tool
Outer
diameter
(mm)
Nominal
diameter
Thickness
(mm)
Flare tool for R410A
clutch type
Clutch type
1.0 to 1.5
1.0 to 1.5
1.0 to 1.5
1.0 to 1.5
Wing nut type
1.5 to 2.0
1/4
3/8
1/2
5/8
6.35
9.52
0.8
0.8
0.8
1.0
0 to 0.5
0 to 0.5
0 to 0.5
0 to 0.5
1.5 to 2.0
12.70
15.88
2.0 to 2.5
2.0 to 2.5
Table 3-2-4 Dimensions related to flare processing for R22
A (mm)
Outer
Nominal
diameter
Thickness
(mm)
diameter
(mm)
Conventional flare tool
Flare tool for R22
clutch type
Clutch type
0.5 to 1.0
0.5 to 1.0
0.5 to 1.0
0.5 to 1.0
Wing nut type
1.0 to 1.5
1/4
3/8
1/2
5/8
6.35
9.52
0.8
0.8
0.8
1.0
0 to 0.5
0 to 0.5
0 to 0.5
0 to 0.5
1.0 to 1.5
12.70
15.88
1.5 to 2.0
1.5 to 2.0
Table 3-2-5 Flare and flare nut dimensions for R410A
Dimension (mm)
Nominal
diameter
Outer diameter
Thickness
(mm)
Flare nut width
(mm)
(mm)
A
B
C
D
1/4
3/8
1/2
5/8
6.35
9.52
0.8
0.8
0.8
1.0
9.1
9.2
6.5
9.7
13
20
23
25
17
22
26
29
13.2 13.5
12.70
15.88
16.6 16.0 12.9
19.7 19.0 16.0
– 9 –
Table 3-2-6 Flare and flare nut dimensions for R22
Dimension (mm)
Nominal
diameter
Outer diameter
Thickness
(mm)
Flare nut width
(mm)
(mm)
A
B
C
D
1/4
3/8
1/2
5/8
3/4
6.35
9.52
0.8
0.8
0.8
1.0
1.0
9.0
9.2
6.5
9.7
13
20
20
23
34
17
22
24
27
36
13.0 13.5
12.70
15.88
19.05
16.2 16.0 12.9
19.7 19.0 16.0
23.3 24.0 19.2
D
B
A
C
Fig. 3-2-2 Relations between flare nut and flare seal surface
2. Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions do not have any scar or dust, etc.
b) Correctly align the processed flare surface with the union axis.
c) Tighten the flare with designated torque by means of a torque wrench. The tightening torque for R410A is
the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur.
When it is strong, the flare nut may crack and may be made non-removable. When choosing the tighten-
ing torque, comply with values designated by manufacturers.Table 3-2-7 shows reference values.
NOTE :
When applying oil to the flare surface, be sure to use oil designated by the manufacturer.
If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
Table 3-2-7 Tightening torque of flare for R410A [Reference values]
Tightening torque of torque
wrenches available on the market
N•m (kgf•cm)
Nominal
diameter
Outer diameter
(mm)
Tightening torque
N•m (kgf•cm)
1/4
3/8
1/2
5/8
6.35
9.52
14 to 18 (140 to 180)
33 to 42 (330 to 420)
50 to 62 (500 to 620)
63 to 77 (630 to 770)
16 (160), 18 (180)
42 (420)
12.70
15.88
55 (550)
65 (650)
– 10 –
3-3. Tools
3-3-1. RequiredTools
The service port diameter of packed valve of the outdoor unit in the air-water heat pump using R410A is
changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing
dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are
lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge,
clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
1. Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2. Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
3. Tools commonly used for R410A and for conventional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
R410A
Conventional air-water
heat pump installation
air-water heat pump installation
No.
Used tool
Usage
Existence of
Whether conven-
Whether new equipment
can be used with
conventional refrigerant
new equipment tional equipment
for R410A
can be used
1
2
Flare tool
Pipe flaring
Ye s
*(Note 1)
¡
Copper pipe gauge for
adjusting projection
margin
Flaring by
conventional flare tool
Ye s
Ye s
Ye s
*(Note 1)
*(Note 1)
Torque wrench
(For Ø12.7)
3
Connection of flare nut
×
×
×
×
4
5
6
Gauge manifold
Charge hose
Evacuating, refrigerant
charge, run check, etc.
Vacuum pump adapter Vacuum evacuating
Ye s
Ye s
×
×
¡
¡
Electronic balance for
Refrigerant charge
refrigerant charging
7
8
9
Refrigerant cylinder
Leakage detector
Refrigerant charge
Gas leakage check
Refrigerant charge
Ye s
Ye s
×
×
×
×
¡
×
10 Charging cylinder
(Note 2)
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary
as the general tools.
1. Vacuum pump
4. Reamer
9. Hole core drill (Ø65)
Use vacuum pump by attaching
vacuum pump adapter.
5. Pipe bender
10. Hexagon wrench
(Opposite side 4mm)
6. Level vial
2. Torque wrench (For Ø6.35, Ø9.52)
11. Tape measure
12. Metal saw
7. Screwdriver (+, –)
8. Spanner or Monkey wrench
3. Pipe cutter
Also prepare the following equipments for other installation method and run check.
1. Clamp meter
2. Thermometer
3. Insulation resistance tester
4. Electroscope
– 11 –
3-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the
following steps.
Recover the refrigerant, and check no refrigerant
remains in the equipment.
When the compound gauge’s pointer has indicated
–0.1 Mpa (–76 cmHg), place the handle Low in the
fully closed position, and turn off the vacuum pump’s
power switch.
Connect the charge hose to packed valve service
port at the outdoor unit’s gas side.
Keep the status as it is for 1 to 2 minutes, and ensure
that the compound gauge’s pointer does not return.
Connect the charge hose to the vacuum pump
adapter.
Set the refrigerant cylinder to the electronic balance,
connect the connecting hose to the cylinder and the
connecting port of the electronic balance, and charge
liquid refrigerant.
Open fully both packed valves at liquid and gas
sides.
(For refrigerant charging, see the figure below.)
Place the handle of the gauge manifold Low in the
fully opened position, and turn on the vacuum pump’s
power switch. Then, evacuating the refrigerant in the
cycle.
1. Never charge refrigerant exceeding the specified amount.
2. If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
3. Do not carry out additional charging.
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the
specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high
pressure, and may cause a rupture or personal injury.
(Water heat
(Outdoor unit)
exchanger unit)
Opened
Refrigerant cylinder
(with siphon)
Check valve
Opened
Opened
Open/close
valve for charging
Closed
Service port
Electronic balance for refrigerant charging
Fig. 3-4-1 Configuration of refrigerant charging
– 12 –
1. Be sure to make setting so that liquid can be charged.
2. When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant.
Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the
cylinder upside down if cylinder is not equipped with siphon.
[ Cylinder with siphon ]
[ Cylinder without siphon ]
Gauge manifold
Gauge manifold
OUTDOOR unit
OUTDOOR unit
c y l i n d e r
a n t i g e r R e f r
Refrigerant
cylinder
Electronic
balance
Electronic
balance
Siphon
R410A refrigerant is HFC mixed refrigerant.
Therefore, if it is charged with gas, the composi-
tion of the charged refrigerant changes and the
characteristics of the equipment varies.
Fig. 3-4-2
3-5. Brazing of Pipes
1. Phosphor bronze brazing filler tends to react
with sulfur and produce a fragile compound
water solution, which may cause a gas
leakage.Therefore, use any other type of
brazing filler at a hot spring resort, etc., and
coat the surface with a paint.
3-5-1. Materials for Brazing
1. Silver brazing filler
Silver brazing filler is an alloy mainly composed
of silver and copper. It is used to join iron, copper
or copper alloy, and is relatively expensive though
it excels in solderability.
2. When performing brazing again at time of
servicing, use the same type of brazing filler.
2. Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used
to join copper or copper alloy.
3-5-2. Flux
1. Reason why flux is necessary
3. Low temperature brazing filler
• By removing the oxide film and any foreign
matter on the metal surface, it assists the flow
of brazing filler.
Low temperature brazing filler is generally called
solder, and is an alloy of tin and lead. Since it is
weak in adhesive strength, do not use it for
refrigerant pipes.
• In the brazing process, it prevents the metal
surface from being oxidized.
• By reducing the brazing filler’s surface tension,
the brazing filler adheres better to the treated
metal.
– 13 –
2. Characteristics required for flux
3-5-3. Brazing
• Activated temperature of flux coincides with the
brazing temperature.
As brazing work requires sophisticated techniques,
experiences based upon a theoretical knowledge, it
must be performed by a person qualified.
• Due to a wide effective temperature range, flux
is hard to carbonize.
In order to prevent the oxide film from occurring in
the pipe interior during brazing, it is effective to
proceed with brazing while letting dry Nitrogen gas
(N2) flow.
• It is easy to remove slag after brazing.
• The corrosive action to the treated metal and
brazing filler is minimum.
• It excels in coating performance and is harm-
less to the human body.
Never use gas other than Nitrogen gas.
1. Brazing method to prevent oxidation
As the flux works in a complicated manner as
described above, it is necessary to select an
adequate type of flux according to the type and
shape of treated metal, type of brazing filler and
brazing method, etc.
1) Attach a reducing valve and a flow-meter to
the Nitrogen gas cylinder.
2) Use a copper pipe to direct the piping mate-
rial, and attach a flow-meter to the cylinder.
3. Types of flux
• Noncorrosive flux
3) Apply a seal onto the clearance between the
piping material and inserted copper pipe for
Nitrogen in order to prevent backflow of the
Nitrogen gas.
Generally, it is a compound of borax and boric
acid.
It is effective in case where the brazing tem-
perature is higher than 800°C.
4) When the Nitrogen gas is flowing, be sure to
keep the piping end open.
• Activated flux
Most of fluxes generally used for silver brazing
are this type.
5) Adjust the flow rate of Nitrogen gas so that it
is lower than 0.05 m3/Hr or 0.02 MPa
(0.2kgf/cm2) by means of the reducing valve.
It features an increased oxide film removing
capability due to the addition of compounds
such as potassium fluoride, potassium chloride
and sodium fluoride to the borax-boric acid
compound.
6) After performing the steps above, keep the
Nitrogen gas flowing until the pipe cools down
to a certain extent (temperature at which
pipes are touchable with hands).
7) Remove the flux completely after brazing.
4. Piping materials for brazing and used
brazing filler/flux
Piping material Used brazing filler
Used flux
Do not use
Paste flux
Vapor flux
Copper - Copper
Copper - Iron
Iron - Iron
Phosphor copper
Silver
M
Flow meter
Silver
Stop valve
Nitrogen gas
cylinder
1. Do not enter flux into the refrigeration cycle.
From Nitrogen cylinder
2. When chlorine contained in the flux remains
within the pipe, the lubricating oil deteriorates.
Therefore, use a flux which does not contain
chlorine.
Pipe
Nitrogen
gas
3. When adding water to the flux, use water
which does not contain chlorine (e.g. distilled
water or ion-exchange water).
Rubber plug
4. Remove the flux after brazing.
Fig. 3-5-1 Prevention of oxidation during brazing
– 14 –
4. CONSTRUCTION VIEWS
4-1. Indoor Unit
RAS-B10GKVP-E
RAS-B13GKVP-E
RAS-B16GKVP-E
790
Plasma pure filter
Indoor heat exchanger
Front panel
Air filter
790
215
53
53
Knockout system
Zeolite-plus filter
Air ionizer
Knockout system
60
54.5
Remote controller holder
64
54.5
60
5
Installation plate hanging section
Wireless remote controller
58
19
Drain hose
(Outside length:0.54m)
290
Installation plate
hanging section
Connecting pipe
(Outside length:0.45m)
Flare Ø6.35
Connecting pipe
(Outside length:0.4m)
Flare Ø9.52
(RAS-B16GKVP-E : Ø12.7)
Parts name of remote controller WH-H03JE
91
674
450
25
Stud bolt hole
for Ø6
10
10
10
10
288
Hanging
section
Minimum
distance
to ceilinfg
Stud bolt hole
for Ø8 to Ø10
Minimum
distance
to wall
Minimum
distance
to wall
74 or more
140 or more
Lower part
hanging section
Outline of
installation plate
Center line
of main unit
Center line of
installation plate
91
304
304
91
790
– 15 –
4-2. Outdoor Unit
RAS-10GAVP-E, RAS-13GAVP-E, RAS-16GAVP-E
Ø25 drain hole
A
leg part
600
108
90
Ø11-14U-shape hole
(for Ø8-Ø10 anchor bolt)
125
54
2-Ø20x88 drain long hole
Connecting pipe port
Pipe dia. Ø9.52:RAS-10GAVP-E, RAS-13GAVP-E
(
)
Ø12.7:RAS-16GAVP-E
Connecting pipe port
(Pipe dia. Ø6.35)
30
8-Ø7 hole
(for fixing outdoor unit)
B
leg part
Ø11x14 long hole
(for Ø8-Ø10 anchor bolt)
483
257
Packed valve cover
108
157
79
69.5
147
145
Z
25
22
31
143
71
342
32
500
780
Charging port
4-Ø4.5 embossment
Fan guard
Fin guard
Detailed
A
leg part
600
54
38
11
When installing the outdoor unit,
leave open in at least two of
directions (A), (B), (C) and (D)
shown in the figure below.
Z
view
Mounting dimensions of anchor bolt
600
Outside line
of product
2-Ø11x14U- Shape hole
(for Ø8-Ø10 anchor bolt)
50 or more
D
Intake
250 or more
A
Intake
11
Outside line
of product
C
100 or more
Outside line
of product
Minimum distance
from wall
200 or more
B
2-Ø11x14 long hole
(for Ø8-Ø10 anchor bolt)
Outlet
38
54
600
Detailed
B
leg part
– 16 –
5. WIRING DIAGRAM
5-1. Outdoor Unit
RAS-10GAVP-E, RAS-13GAVP-E, RAS-16GAVP-E
Color
Identification
RED : RED
WHI : WHITE
BLK : BLACK
BLU : BLUE
BRW : BROWN
ORN : ORANGE
PUR : PURPUL
YEL : YELLOW
GRY : GRAY
PNK : PINK
220-240V ~50Hz
220V ~60Hz
5-2. Indoor Unit
RAS-B10GKVP-E, RAS-B13GKVP-E, RAS-B16GKVP-E
GRN& GREEN&
:
YEL
YELLOW
BLK
BLK
1 1
2 2
3 3
4 4
5 5
6 6
INDOOR
TERMINAL
BLOCK
1 2 3
1 2 3 4
1 2 3 4
Heat
exchanger
Ion electrode
1 2 3 4
GRN & YEL
BLK WHI RED
3
1
1 2 3 4
CN22
CN23
CN21
CN33
CN01
(WHI)
(BLU)
BRW
1 1
BLK
1 1
Micro SW
CN34
FUSE
F01
2 2
(RED)
BLK
BLU
2 2
HEAT EXCHANGER
SENSOR (TC)
AC 250V
T3.15A
CN03
CN10
(WHI)
1 1
FAN MOTOR
(WHI)
RED
BLK
BLK
BLK
1 1
2 2
THERMO SENSOR
(TA)
3 3
4 4
5 5
6 6
WHI DC MOTOR
YEL
BLU
CN100
CN13
(WHI)
(WHI)
BLU
1 1
BLU
2 2
BLU
3 3
BLU
4 4
BLU
5 5
BLU
6 6
BLU
7 7
BLU
8 8
WHI
9 9
9 9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
1 1
DC5V
LINE
FILTER
CN07
(WHI)
DB01
WHI
1 1
YEL
2 2
YEL
3 3
YEL
4 4
YEL
5 5
DC12V
1 1
2 2
3 3
4 4
5 5
TNR
MAIN P.C. BOARD
(MCC-5020)
CN08 (WHI)
1 2 3 4
LOUVER MOTOR
MCC-899
10 10
– 17 –
6. SPECIFICATIONS OF ELECTRICAL PARTS
6-1. Indoor Unit
RAS-B10GKVP-E, RAS-B13GKVP-E, RAS-B16GKVP-E
No.
1
Parts name
Fan motor (for indoor)
Type
MF-280-30-5R
( – )
Specifications
DC280–340V, 30W
2
Room temp. sensor (TA-sensor)
Heat exchanger temp. sensor (TC-sensor)
Louver motor
10kΩ at 25°C
3
( – )
10kΩ at 25°C
4
MP24Z
Output (Rated) 1W, 16 poles, DC12V
6-2. Outdoor Unit
RAS-10GAVP-E, RAS-13GAVP-E, RAS-16GAVP-E
No.
1
Parts name
Model name
CH-57
Rating
L = 10mH, 16A × 2
DC140V, 43W
10kΩ (25°C)
Reactor
2
Outside fan motor
ICF-140-43-4R
(Inverter attached)
(Inverter attached)
(Inverter attached)
(Inverter attached)
——
3
Suction temp. sensor (TS sensor)
Discharge temp. sensor (TD sensor)
Outside air temp. sensor (TO sensor)
Heat exchanger temp. sensor (TE sensor)
Terminal block (6P)
4
62kΩ (20°C)
5
10kΩ (25°C)
6
10kΩ (25°C)
7
20A, AC250V
3-phases 4-poles 750W
DC12V
8
Compressor
DA111A1F-20F1
CAM-MD12TF
VHV
9
Coil for P.M.V.
10
Coil for 4-way valve
AC220–240V
– 18 –
7. REFRIGERANT CYCLE DIAGRAM
7-1. Refrigerant Cycle Diagram
RAS-B10GKVP-E/RAS-10GAVP-E
T1 Temp. measurement
INDOOR UNIT
Indoor heat
exchanger
TC
TA
Cross flow fan
Max. : 25m
Min. : 2m
P
Pressure measurement
Chargeless : 15m
Charge : 20g/m
(16 to 25m)
Deoxidized copper pipe
Outer dia. : 6.35mm
Thickness : 0.8mm
Gauge attaching port
Vacuum pump connecting port
Sectional shape
of heat insulator
Deoxidized copper pipe
Outer dia. : 9.52mm
Thickness : 0.8mm
Strainer
Muffler
4-way valve
(STF-0108Z)
Pulse motor
valve at liquid side
(CAM-B22YGTF-3)
Muffler
TD
Compressor
DA111A1F-20F1
Strainer
TS
TO
Outdoor heat
exchanger
Temp. measurement
T2
TE
Refrigerant amount : 0.82kg
Propeller fan
OUTDOOR UNIT
Gas leak check position
Refrigerant flow (Cooling)
Refrigerant flow (Heating)
NOTE :
NOTE :
• The maximum pipe length of this air conditioner is 25 m. When the pipe length exceeds 15m, the additional
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 200g)
– 19 –
RAS-B13GKVP-E/RAS-13GAVP-E, RAS-B16GKVP-E/RAS-16GAVP-E
T1 Temp. measurement
INDOOR UNIT
Indoor heat
exchanger
TC
TA
Cross flow fan
Max. : 25m
Min. : 2m
P
Pressure measurement
Chargeless : 15m
Charge : 20g/m
(16 to 25m)
Deoxidized copper pipe
Outer dia. : 6.35mm
Thickness : 0.8mm
Gauge attaching port
Vacuum pump connecting port
Sectional shape
of heat insulator
Deoxidized copper pipe
Outer dia. : 9.52mm(13),
12.7mm(16)
Thickness : 0.8mm
Strainer
Muffler
4-way valve
(STF-0108Z)
Pulse motor
valve at liquid side
(CAM-B22YGTF-3)
Muffler
TD
Compressor
DA111A1F-20F1
TS
TO
Outdoor heat
exchanger
Split capillary
Ø1.2 x 80
Ø1.2 x 80
Temp. measurement
T2
TE
Refrigerant amount : 0.96kg
Propeller fan
OUTDOOR UNIT
Gas leak check position
Refrigerant flow (Cooling)
Refrigerant flow (Heating)
NOTE :
NOTE :
• The maximum pipe length of this air conditioner is 25 m. When the pipe length exceeds 15m, the additional
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 200g)
– 20 –
7-2. Operation Data
<Cooling>
Temperature
condition (°C)
Heat exchanger
pipe temp.
Standard
pressure
P (MPa)
Compressor
revolution
(rps)
Model name
RAS-
Indoor
fan mode
Outdoor
fan mode
Indoor Outdoor
T1 (°C)
T2 (°C)
42 to 44
42 to 45
43 to 47
B10GKVP-E
B13GKVP-E
B16GKVP-E
0.9 to 1.1
0.8 to 1.0
0.7 to 0.9
13 to 15
11 to 14
8 to 11
High
High
High
High
High
High
37
59
82
27/19
35/–
<Heating>
Temperature
condition (°C)
Heat exchanger
pipe temp.
Standard
pressure
P (MPa)
Compressor
revolution
(rps)
Model name
RAS-
Indoor
fan mode
Outdoor
fan mode
Indoor Outdoor
T1 (°C)
T2 (°C)
0 to 3
0 to 2
0 to 2
B10GKVP-E
B13GKVP-E
B16GKVP-E
2.2 to 2.4
2.5 to 2.7
2.8 to 3.0
37 to 39
42 to 45
48 to 49
High
High
High
High
High
High
54
65
86
20/–
7/6
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 7.5 m
– 21 –
8. CONTROL BLOCK DIAGRAM
8-1. Indoor Unit
RAS-B10GKVP-E, RAS-B13GKVP-E, RAS-B16GKVP-E
Indoor Unit Control Unit
Louver Motor
M.C.U.
Louver
Motor
Functions
Heat Exchanger Sensor (Tc)
• Cold draft preventing Function
Room Temperature Sensor (Ta)
• 3-minute Delay at Restart for Compressor
Drive Control
Infrared Rays Signal Receiver
• Fan Motor Starting Control
and Indication
Indoor Fan
Motor Control
• Processing
(Temperature Processing)
Initializing Circuit
Indoor
Fan Motor
• Timer
Clock Frequency
Oscillator Circuit
• Serial Signal Communication
• Clean Function
Air purifier
unit
Power Supply
Circuit
Converter
(D.C circuit)
Micro Switch
Noise Filter
Serial Signal Transmitter/Receiver
From Outdoor Unit
220-240V ~50Hz
220V ~60Hz
Serial Signal Communication
(Operation Command and Information)
Infrared Rays, 36.7kHz
Remote Controller
REMOTE CONTROLLER
Operation (START/STOP)
Operation Mode Selection
AUTO, COOL, DRY, HEAT
Thermo. Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver AUTO Swing
Louver Direction Setting
ECO
Hi-POWER
Air Purifier
SLEEP
– 22 –
MICRO-COMPUTER BLOCK DIAGRAM
For INDOOR UNIT
220–240 V ~50Hz
220 V ~60Hz
MCC5009 (P.C.B)
OUTDOOR UNIT
Indoor unit
send/receive
circuit
Current
detect
M.C.U
• PWM synthesis function
• Input current release control
• IGBT over-current detect control
• Outdoor fan control
Gate drive
circuit
Discharge
temp. sensor
• High power factor correction control
• Inverter output frequency control
• A/D converter function
• P.M.V. control
• Discharge temp. control
• 4-way valve control
Outdoor air
temp. sensor
Current
detect
Suction temp.
sensor
Gate drive
circuit
• Signal communication to indoor unit
Heat exchanger
temp.sensor
High Power
factor Correction
circuit
Clock
frequency
4MHz
Noise
Filter
Input current
sensor
Converter
(AC → DC)
Outdoor
Fan motor
Inverter
(DC → AC)
Driver circuit
of P.M.V.
Relay
circuit
Inverter
(DC → AC)
Compressor
P.M.V. : Pulse Motor Valve
M.C.U. : Micro Control Unit
4-way
valve
P.M.V.
9. OPERATION DESCRIPTION
• Detection of inverter input current and current
release operation
• Over-current detection and prevention operation
to IGBT module (Compressor stop function)
• Compressor and outdoor fan stop function when
serial signal is off (when the serial signal does not
reach the board assembly of outdoor control by
trouble of the signal system)
9-1. Outline of Air Conditioner Control
This air conditioner is a capacity-variable type air
conditioner, which uses DC motor for the indoor fan
motor and the outdoor fan motor. And the capacity-
proportional control compressor which can change the
motor speed in the range from 13 to 115 rps is
mounted. The DC motor drive circuit is mounted to the
indoor unit. The compressor and the inverter to control
fan motor are mounted to the outdoor unit.
• Transferring of operation information (Serial
signal) from outdoor unit controller to indoor unit
controller
The entire air conditioner is mainly controlled by the
indoor unit controller.
• Detection of outdoor temperature and operation
revolution control
• Defrost control in heating operation (Temp.
measurement by outdoor heat exchanger and
control for 4-way valve and outdoor fan)
The indoor unit controller drives the indoor fan motor
based upon command sent from the remote controller,
and transfers the operation command to the outdoor
unit controller.
The outdoor unit controller receives operation com-
mand from the indoor unit side, and controls the
outdoor fan and the pulse motor valve. (P.M.V)
Besides, detecting revolution position of the compres-
sor motor, the outdoor unit controller controls speed of
the compressor motor by controlling output voltage of
the inverter and switching timing of the supply power
(current transfer timing) so that motors drive according
to the operation command.
3. Contents of operation command signal
(Serial signal) from indoor unit controller to
outdoor unit controller
The following three types of signals are sent from
the indoor unit controller.
• Operation mode set on the remote controller
• Compressor revolution command signal defined
by indoor temperature and set temperature
(Correction along with variation of room tempera-
ture and correction of indoor heat exchanger
temperature are added.)
And then, the outdoor unit controller transfers reversely
the operating status information of the outdoor unit to
control the indoor unit controller.
As the compressor adopts four-pole brushless
DC motor, the frequency of the supply power
from inverter to compressor is two-times cycles
of the actual number of revolution.
• Temperature of indoor heat exchanger
• For these signals ([Operation mode] and [Com-
pressor revolution] indoor heat exchanger tem-
perature), the outdoor unit controller monitors the
input current to the inverter, and performs the
followed operation within the range that current
does not exceed the allowable value.
1. Role of indoor unit controller
The indoor unit controller judges the operation
commands from the remote controller and assumes
the following functions.
4. Contents of operation command signal
(Serial signal) from outdoor unit controller
to indoor unit controller
• Judgment of suction air temperature of the indoor
heat exchanger by using the indoor temp. sensor.
(TA sensor)
The following signals are sent from the outdoor unit
controller.
• Judgment of the indoor heat exchanger tempera-
ture by using heat exchanger sensor (TC sensor)
(Prevent-freezing control, etc.)
• The current operation mode
• The current compressor revolution
• Outdoor temperature
• Louver motor control
• Indoor fan motor operation control
• LED (Light Emitting Diode) display control
• Existence of protective circuit operation
For transferring of these signals, the indoor unit
controller monitors the contents of signals, and
judges existence of trouble occurrence.
• Transferring of operation command signal (Serial
signal) to the outdoor unit
• Reception of information of operation status
(Serial signal including outside temp. data) to the
outdoor unit and judgment/display of error
Contents of judgment are described below.
• Whether distinction of the current operation
status meets to the operation command signal
• Air purifier operation control
• Whether protective circuit operates
2. Role of outdoor unit controller
When no signal is received from the outdoor
unit controller, it is assumed as a trouble.
Receiving the operation command signal (Serial
signal) from the indoor unit controller, the outdoor
unit performs its role.
• Compressor operation control
• Operation control of outdoor fan motor
• P.M.V. control
Operations followed to judgment
of serial signal from indoor side.
• 4-way valve control
– 24 –
9-2. Operation Description
9-2.
1. Basic operation ........................................................................................................... 26
1. Operation control ................................................................................................... 26
2. Cooling/Heating operation ..................................................................................... 27
3. AUTO operation ..................................................................................................... 27
4. DRY operation........................................................................................................ 27
2. Indoor fan motor control ............................................................................................. 28
3. Outdoor fan motor control........................................................................................... 30
4. Capacity control .......................................................................................................... 31
5. Current release control ............................................................................................... 31
6. Release protective control by temperature of indoor heat exchanger........................ 32
7. Quick heating control .................................................................................................. 33
8. Defrost control (Only in heating operation) ................................................................ 33
9. Louver control ............................................................................................................. 34
1) Louver position....................................................................................................... 34
2) Air direction adjustment ......................................................................................... 34
3) Swing ..................................................................................................................... 34
10. ECO operation ............................................................................................................ 35
11. Temporary operation................................................................................................... 36
12. Air purifying control [Detection of abnormality] .......................................................... 37
13. Discharge temperature control ................................................................................... 37
14. Pulse motor valve (P.M.V.) control .............................................................................. 38
15. Clean operation .......................................................................................................... 39
16. Clean operation release ............................................................................................ 40
17. Select switch on remote controller ............................................................................. 41
9-3. Auto Restart Function.............................................................................................42
9-3-1. How to Set the Auto Restart Function.................................................................... 42
9-3-2. How to Cancel the Auto Restart Function ............................................................. 43
9-3-3. Power Failure During Timer Operation ................................................................... 43
9-4. FILTER Indicator......................................................................................................43
9-4-1. How to Turn Off FILTER Indicator............................................................................ 43
9-5. Remote Controller and Its Fuctions ......................................................................44
9-5-1. Parts Name of Remote Controller ........................................................................... 44
9-5-2. Name and Functions of Indications on Remote Controller ................................. 45
9-6. Hi-POWER Mode
([Hi-POWER] button on the remote controller is pressed) ..................................46
– 25 –
Item
Operation flow and applicable data, etc.
1. Operation control
Description
1. Basic
operation
Receiving the user’s operation condition setup, the operation statuses of indoor/outdoor units are
controlled.
1) The operation conditions are selected by the remote controller as shown in the below.
2) A signal is sent by ON button of the remote controller.
3) The signal is received by a sensor of the indoor unit and processed by the indoor controllers as
shown in the below.
4) The indoor controller controls the indoor fan motor and louver motor.
5) The indoor controller sends the operation command to the outdoor controller, and sends/receives
the control status with a serial signal.
6) The outdoor controller controls the operation as shown in the left, and also controls the compres-
sor, outdoor fan motor, 4-way valve and pulse motor valve.
Remote controller
Selection of
operation conditions
Control contents of remote controller
• ON/OFF (Air conditioner/Air purifier)
• Operation select (COOL/HEAT/AUTO/DRY)
• Temperature setup
• Air direction
ON/OFF
• Swing
• Air volume select (AUTO/LOW/LOW+/MED/MED+/HIGH)
• ECO
• ON timer setup
• OFF timer setup
• High power
Indoor unit
Signal receiving
Indoor unit control
Indoor unit control
• Command signal generating function of
indoor unit operation
• Calculation function (temperature calculation)
• Activation compensation function of indoor fan
• Cold draft preventive function
• Timer function
• Indoor heat exchanger release control
• Indoor fan motor
• Louver motor
Operation command
Serial signal send/receive
~
Outdoor unit
Serial signal send/receive
Outdoor unit control
Outdoor unit control
• Frequency control of inverter output
• Waveform composite function
• Calculation function
(Temperature calculation)
Inverter
• Compressor
• Outdoor fan motor
• 4-way valve
• Pulse motor valve
(P.M.V.)
• AD conversion function
• Quick heating function
• Delay function of compressor reactivation
• Current release function
• GTr over-current preventive function
• Defrost operation function
– 26 –
Item
Operation flow and applicable data, etc.
2. Cooling/Heating operation
Description
1. Basic
operation
The operations are performed in the following parts by controls according to cooling/heating conditions.
1) Receiving the operation ON signal of the remote controller, the cooling or heating operation signal
starts being transferred form the indoor controller to the outdoor unit.
2) At the indoor unit side, the indoor fan is operated according to the contents of “2. Indoor fan
motor control” and the louver according to the contents of “9. Louver control”, respectively.
3) The outdoor unit controls the outdoor fan motor, compressor, pulse motor valve and
4-way valve according to the operation signal sent from the indoor unit.
*1. The power coupler of 4-way valve is usually turned off, and it is turned on during defrost
operation. (Only in heating)
Operation ON
Setup of remote controller
Indoor unit control
Indoor fan motor control / Louver control
Sending of operation command signal
Compressor revolution control / Outdoor fan motor control /
4-way valve control
In cooling operation: ON
Outdoor unit control
[
]
In heating operation: OFF
Pulse motor valve control
3. AUTO operation
Selection of operation mode
1) Detects the room temperature (Ta) when
the operation started.
2) Selects an operation mode from Ta in
the left figure.
As shown in the following figure, the operation starts by
selecting automatically the status of room temperature
(Ta) when starting AUTO operation.
3) Fan operation continues until an
operation mode is selected.
*1. When reselecting the operation mode, the fan
speed is controlled by the previous operation mode.
4) When AUTO operation has started
within 2 hours after heating operation
stopped and if the room temperature is
20°C or more, the fan operation is
performed with ”Super Ultra LOW” mode
for 3 minutes.
Ta
Cooling operation
Ts + 1
Then, select an operation mode.
Monitoring (Fan)
5) If the status of compressor-OFF
continues for 15 minutes the room
temperature after selecting an operation
mode (COOL/HEAT), reselect an
operation mode.
Ts – 1
Heating operation
4. DRY operation
1) Detects the room temperature (Ta) when
the DRY operation started.
DRY operation is performed according to the difference
between room temperature and the setup temperature as 2) Starts operation under conditions in the
shown below.
left figure according to the temperature
difference between the room tempera-
ture and the setup temperature (Tsc).
Setup temperature (Tsc)
= Set temperature on remote controller
(Ts) + (0.0 to 1.0)
In DRY operation, fan speed is controlled in order to
prevent lowering of the room temperature and to avoid air
flow from blowing directly to persons.
[
]
˚C
3) When the room temperature is lower
1°C or less than the setup temperature,
turn off the compressor.
Ta
L– (W5)
(W5+W3) / 2
+
+
1.0
0.5
SL (W3)
Tsc
Fan speed
– 27 –
Item
Operation flow and applicable data, etc.
<In cooling operation>
Description
* Symbols
2. Indoor fan
motor control
(This operation controls the fan speed at indoor unit side.)
The indoor fan (cross flow fan) is operated by the phase-
control induction motor. The fan rotates in 5 stages in
MANUAL mode, and in 5 stages in AUTO mode, respec-
tively. (Table 1)
UH
H
M+
M
L+
L
: Ultra High
: High
: Medium+
: Medium
: Low+
: Low
L-
UL
SUL
: Low–
: Ultra Low
: Super Ultra Low
COOL ON
Fan speed setup
AUTO
MANUAL
* The fan speed broadly varies due
to position of the louver, etc.
The described value indicates one
under condition of inclining
downward blowing.
(Fig. 1)
Indication
Fan speed
W6
L
1) When setting the fan speed to L,
L+, M, M+ or H on the remote
controller, the operation is
performed with the constant
speed shown in Fig. 1.
L+
M
(L + M) / 2
W9
M+
H
(M + H) / 2
WC
2) When setting the fan speed to
AUTO on the remote controller,
revolution of the fan motor is
controlled to the fan speed level
shown in Fig. 2 and Table 1
(Fig. 2)
Air volume AUTO
according to the setup tempera-
ture, room temperature, and heat
exchanger temperature.
Ta
˚C
[
]
M+(WB)
+2.5
+2.0
a
b
c
d
e
*3
*4
*5
*3 :Fan speed = (M + –L) x 3/4 + L
*4 :Fan speed = (M + –L) x 2/4 + L
*5 :Fan speed = (M + –L) x 1/4 + L
+1.5
+1.0
+0.5
Tsc
(Linear approximation
from M+ and L)
L(W6)
(Table 1) Indoor fan air flow rate
RAS-B10GKVP-E
RAS-B13GKVP-E
RAS-B16GKVP-E
Fan speed
level
COOL HEAT DRY
Fan speed Air flow rate Fan speed Air flow rate Fan speed Air flow rate
(rpm)
(m3/h)
(rpm)
(m3/h)
(rpm)
(m3/h)
WF
WE
WD
WC
WB
WA
W9
W8
W7
W6
W5
W4
W3
W2
W1
UH
H
M+
1630
1480
1400
1350
1200
1110
980
910
900
890
880
684
609
569
544
468
423
358
323
318
313
308
232
157
82
1650
1530
1440
1390
1240
1150
1010
910
900
890
880
730
694
634
589
564
488
443
373
323
318
313
308
232
157
82
1650
1580
1550
1530
1380
1230
1080
970
960
950
940
790
694
659
644
634
559
483
408
353
348
343
338
263
187
112
67
UH
H
M+
M
L+
L
M
L+
L
L–
UL
SUL
L–
L+
L
L–
UL
SUL
UL
730
580
430
400
580
430
400
640
490
400
SUL
67
67
– 28 –
Item
Operation flow and applicable data, etc.
Description
2. Indoor fan
motor control
<In heating operation>
1) When setting the fan speed to L,
L+, M, M+ or H on the remote
controller, the operation is per-
formed with the constant speed
shown in Fig. 3 and Table 1.
HEAT ON
2) When setting the fan speed to
AUTO on the remote controller,
revolution of the fan motor is
Fan speed setup
MANUAL
(Fig. 3)
controlled to the fan speed level
shown in Fig. 5 according to the set
temperature and room temperature.
Indication
Fan speed
W8
3) Min air flow rate is controlled by
temperature of the indoor heat
exchanger (Tc) as shown in Fig. 4.
L
L+
M
(L + M) / 2
WA
AUTO
4) Cold draft prevention, the fan
speed is controlled by temperature
of the indoor heat exchanger (Tc)
as shown in Fig. 6.
M+
H
(M + H) / 2
WE
YES
TC ≥ 42˚C
Min air flow rate control
NO
Limited to Min WD tap
Tc
52
51
42
41
No limit
*Fan speed =
(TC
W8) + W8
(Fig. 4)
Cold draft preventive control
Tc
46
45
[
]
C
TA
b
c
d
e
f
46
45
34
TSC
–0.5
–1.0
–1.5
–2.0
–2.5
–5.0
5.5
L (W8)
33
33
32
33
32
21
20
*1
*2
*A+4
*A-4
*A+4
*A-4
*A+4
*A-4
*3
g
Fan speed MANUAL in starting
Fan speed AUTO in stability
Fan speed AUTO in starting
M+ (WD)
H (WE)
*1:
*2:
4 + L
4 + L
(Fig. 5)
[In starting and in stability]
(Fig. 6)
In starting
In stability
• Until 12 minutes passed after operation start
FAN AUTO • When 12 to 25 minutes passed after operation
• When 12 to 25 minutes passed after operation start
and room temp. is higher than (set temp. –3°C)
start and room temp. is 3°C or lower than set temp. • When 25 minutes or more passed after operation start
FAN Manual • Room temp. < Set temp. –4°C • Room temp. ≥ Set temp. –3.5°C
– 29 –
Item
Operation flow and applicable data, etc.
Description
3. Outdoor fan
motor control
The blowing air volume at the outdoor unit side is controlled. 1) The operation command sent
from the remote controller is
Receiving the operation command from the controller of
indoor unit, the controller of outdoor unit controls fan speed.
processed by the indoor unit
controller and transferred to the
controller of the outdoor unit.
* For the fan motor, a DC motor with non-stage variable
speed system is used. However, it is limited to 8 stages for
reasons of controlling.
2) When strong wind blows at
outdoor side, the operation of air
conditioner continues with the
fan motor stopped.
Air conditioner ON
(Remote controller)
3) Whether the fan is locked or not
is detected, and the operation of
air conditioner stops and an
alarm is displayed if the fan is
locked.
Indoor unit controller
4) According to each operation
mode, by the conditions of
outdoor temperature (To) and
compressor revolution, the speed
of the outdoor fan shown in the
table is selected.
1) Outdoor unit
operation command
(Outdoor fan control)
YES
YES
OFF status of
2) Fan speed ≥ 400
fan motor continues.
when the motor stopped.
NO
Fan motor ON
Air conditioner
OFF
Alarm
display
3) Fan lock
NO
4) Motor operates as shown in the table below.
In cooling operation
In Heating operation
~ 13.8
~ 31.7
32.3 ~ MAX
Compressor speed (rps) ~16.8 ~47.9 48.5 ~ MAX
Compressor speed (rps)
>
MIN MAX MIN MAX MIN MAX
To 15°C
f 3
f 3
f 8
f B
f 3
f 3
f 5
f 7
f A
f 8
f 9
f A
f C
f 3
f 3
f 9
f A
f B
f 9
f A
f D
f D
f 6
f 8
f 9
f B
f D
>
To 38°C
f 2
f 2
f 2
f 2
f 1
f 2
f 2
f 3 f C f D f E f F
f 3 f B f C f E f F
To < 15°C
To < 5.5°C
To < –5.0°C
To
>
To 28°C
>
To
To 15°C
f 3
f 3
f 2
f 8
f 6
f 4
f 9 f A f B
>
>
To 5.5°C
f 7
f 5
f 8
f 6
f 9
f 7
To 15°C
>
To 0°C
To < 15°C
To < 5.5°C
To < –5.5°C
During
ECO mode
>
To 38°C
f 3 f B f C f C f D
f 3 f 2 f 3 f B f C
During
ECO mode
To < 38°C
When To is abnormal
f D f F f D f F f D f F
When To is abnormal
Outdoor fan speed (rpm)
Tap
f 1
f 2
f 3
f 4
f 5
f 6
f 7
f 8
10GAVP-E
200
13GAVP-E
200
16GAVP-E
200
Tap
f 9
10GAVP-E
700
13GAVP-E
700
16GAVP-E
700
300
300
300
f A
f B
f C
f D
f E
f F
700
700
700
390
390
390
700
700
700
450
450
450
700
700
700
500
500
500
750
840
920
500
500
500
750
840
920
600
600
600
750
840
920
600
600
600
– 30 –
Item
Operation flow and applicable data, etc.
Description
4. Capacity
control
The cooling or heating capacity depending on the load is
adjusted.
1) The difference between set
temperature on remote controller
(Ts) and room temperature (Ta)
is calculated.
According to difference between the setup value of tempera-
ture and the room temperature, the capacity is adjusted by
the compressor revolution.
2) According to the temperature
difference, the correction value of
Hz signal which determines the
compressor speed is set up.
Remote controller
Set temp. (Ts)
Indoor unit
Room temp. (Ta)
3) The rotating position and speed
of the motor are detected by the
electromotive force occurred on
the motor winding with operation
of the compressor.
Ts –Ta
4) According to the difference
resulted from comparison of the
correction value of Hz signal with
the present operation Hz, the
inverter output and the commuta-
tion timing are varied.
Correction of Hz signal
Detection of electromotive force
of compressor motor winding
5) Change the compressor motor
speed by outputting power to the
compressor.
Detection of motor speed and rotor position
* The contents of control
operation are same in cooling
operation and heating
operation
Correction value of Hz signal ≤ Operating Hz
Inverter output change
Commutation timing change
Change of compressor speed
5. Current release This function prevents troubles on the electronic parts of the 1) The input current of the outdoor
control
compressor driving inverter.
unit is detected in the inverter
section of the outdoor unit.
This function also controls drive circuit of the compressor
speed so that electric power of the compressor drive circuit
does not exceed the specified value.
2) According to the detected
outdoor temperature, the
specified value of the current is
selected.
Outdoor temp. To
Outdoor unit inverter main
3) Whether the current value
exceeds the specified value or
not is judged.
circuit control current
Setup of current release point
4) If the current value exceeds the
specified value, this function
reduces the compressor speed
and controls speed up to the
closest one commanded from the
indoor unit within the range
which does not exceed the
specified value.
High
Operating current ≤
Reduce compressor speed
Current decrease
Setup value
Low
Capacity control continues.
Cooling current
release value
Heating current
release value
Outdoor temp.
6.45A
6.75A
45˚C
40˚C
16˚C
11˚C
44˚C
39˚C
7.72A
15.5˚C
10.5˚C
8.47A
9.22A
10.80A
– 31 –
Item
Operation flow and applicable data, etc.
Description
6. Release protective
control by tempera-
ture of indoor heat
exchanger
<In cooling/dry operation>
1) When temperature of the indoor
heat exchanger drops below 5°C,
the compressor speed is
(Prevent-freezing control for indoor heat exchanger)
In cooling/dry operation, the sensor of indoor heat
exchanger detects evaporation temperature and
controls the compressor speed so that temperature of
the heat exchanger does not exceed the specified
value.
reduced. (P zone)
2) When temperature of the indoor
heat exchanger rises in the
range from 6°C to under 7°C, the
compressor speed is kept.
(Q zone)
Usual cooling capacity control
3) When temperature of the indoor
heat exchanger rises to 7°C or
higher, the capacity control
operation returns to the usual
control in cooling operation.
(R zone)
R
When the value is
7˚C
6˚C
5˚C
in Q zone, the
Q
compressor speed
is kept.
P
Reduction of compressor speed
<In heating operation>
1) When temperature of the indoor
heat exchanger rises in the
range from 50°C to 55°C, the
compressor speed is kept.
(Q zone)
(Prevent-overpressure control for refrigerating cycle)
In heating operation, the sensor of indoor heat ex-
changer detects condensation temperature and controls
the compressor speed so that temperature of the heat
exchanger does not exceed the specified value.
When temperature of the indoor
heat exchanger drops in the
range from 46°C to under 55°C,
the compressor speed is kept.
(Q zone)
Reduction of compressor speed
P
2) When temperature of the indoor
heat exchanger rises to 55°C or
higher, the compressor speed is
reduced. (P zone)
55˚C
When the value is
50˚C
Q
3) When temperature of the indoor
heat exchanger does not rise to
50°C, or when it drops below to
46°C, the capacity control
operation returns to the usual
control in heating operation.
(R zone)
in Q zone, the
compressor speed
is kept.
46˚C
R
Usual heating capacity control
– 32 –
Item
Operation flow and applicable data, etc.
Description
7. Quick heating
control
This function quickens the starting of heating opera-
tion when indoor/outdoor temperature is low.
(Available only in heating operation)
When the following conditions are
satisfied, winding is heated by output
varied by the outdoor heat exchanger
temperature.
When indoor temperature is low, this function stores
the heat by heating winding depended on the outdoor
temperature and then it enables the hot air blowing
out quickly.
Condition 1 :
The previous operation was heating.
Condition 2 :
In case of operation stop
2 hours passed after operation stop.
Condition 3 :
The room temperature is 20°C or lower.
NO
The previous operation was heating and
2 hours passed after the operation had stopped.
The indoor temperature sensor detects
the room temperature.
YES
If the detected room temperature is 20°C
or lower, the outdoor heat exchanger
temperature sensor detects the outdoor
heat exchanger temperature. As shown in
the left figure, winding of the compressor
is heated for each division of the tempera-
ture ( for each outdoor temperature) and
the heat is stored.
Winding is not heated.
20˚C
Heating output for winding
OFF
–1˚C
–3˚C
20W or equivalent
20W or equivalent
–6˚C
–8˚C
8. Defrost control
(This function removes frost adhered to the outdoor
The necessity of defrost operation is
detected by the outdoor heat exchanger
temperature. The conditions to detect the
necessity of defrost operation differ in A,
B, or C zone each. (Table 1)
(Only in heating heat exchanger.)
operation)
The temperature sensor of the outdoor heat ex-
changer (Te sensor) judges the frosting status of the
outdoor heat exchanger and the defrost operation is
performed with 4-way valve reverse defrost system.
<Defrost operation>
• Defrost operation in A to C zones
1) Stop operation of the compressor for
20 seconds.
Start of heating operation
2) Invert (ON) 4-way valve 10 seconds
after stop of the compressor.
Operation time
(Minute)
0’ 10’ 15’
27’40”
34’
3) The outdoor fan stops at the same time
when the compressor stops.
–5˚C
4) When temperature of the indoor heat
exchanger becomes 38°C or lower,
stop the indoor fan.
C zone
–7˚C
<Finish of defrost operation>
A zone
• Returning conditions from defrost
operation to heating operation
–20˚C
B zone
1) Temperature of outdoor heat exchanger
*
rises to +8°C or higher.
2) Temperature of outdoor heat exchanger
* The minimum value of Te sensor 10 to 15 minutes
after start of operation is stored in memory as Te0.
is kept at +5°C or higher for 80 seconds.
3) Defrost operation continues for
15 minutes.
Table 1
<Returning from defrost operation>
1) Stop operation of the compressor for
approx. 50 seconds.
When Te0 - TE ≥ 2.5 continued for 2 minutes in A zone,
A zone
defrost operation starts.
When the operation continued for 2 minutes in B zone,
defrost operation starts.
2) Invert (OFF) 4-way valve approx. 40
seconds after stop of the compressor.
B zone
C zone
When Te0 - TE ≥ 3 continued for 2 minutes in C zone,
defrost operation starts.
3) The outdoor fan starts rotating at the
same time when the compressor starts.
– 33 –
Item
Operation flow and applicable data, etc.
Description
9. Louver control
This function controls the air direction of the indoor unit.
1) Louver
position
• The position is automatically controlled according to the operation mode (COOL/HEAT).
• The set louver position is stored in memory by the microcomputer, and the louver returns to the
stored position when the next operation is performed. (Cooling/heating memory position)
The angle of the louver is indicated as the horizontal angle is 0°.
When the louver closes fully, it directs approx. 49° upward.
Horizontal
(0˚)
Louver angle
1) Louver position in cooling operation
Powerful
Room temp. (Ta) < Set temp. (Tsc) + 3.5 Room temp. (Ta) ≥ Set temp. (Tsc) + 3.5
Initial setting of “Cooling storage position” Initial setting of “Cooling storage position” “Inclined blowing”
Louver : Directs downward (9˚)
Louver : Directs downward (9˚)
Louver : Directs downward (14˚)
YES
NO
Powerful
operation
Cooling memory
Cooling/AUTO
(COOL)/DRY operation
Room temp. ≥
Set temp. +3.5
position
NO
Room temp. ≥ Set temp. +3.5
YES
NO
YES
Cooling memory
position
Inclined
blowing
2) Louver position in heating operation
ECO operation
Heating operation/
AUTO (HEAT)
Room temp. (Ta) < Set temp. (Tsc) – 3
Room temp. (Ta) ≥ Set temp. (Tsc) – 3
or 25 minutes after start of operation
Initial setting of “Heating storage position” “Heating storage position”
“Cooling storage position”
Louver : Directs downward (9˚)
Louver : Directs downward (76˚)
Louver : Directs downward (76˚)
YES
NO
ECO
operation
Room temp. ≥
Set temp. –3.0
Horizontal
position
Heating operation
NO
Room temp. ≥ Set temp. –3.0
YES
NO
YES
Heating memory
position
Heating memory
position
2) Air direction adjustment
• The louver position can
be arbitrarily set up by
pressing [FIX] button.
Air direction
Horizontal
blowing
Inclined
blowing
Blowing
downward
Inclined
blowing
Horizontal
blowing
3) Swing
• Swing operation is performed in width 35° with the stop position as
• Swing
the center.
When pressing
[SWING] button during
operation, the louver
starts swinging.
• If the stop position exceeds either upper or lower limit position,
swing operation is performed in width 35° from the limit which the
stop position exceeded.
– 34 –
Item
Operation flow and applicable data, etc.
Description
10. ECO
When pressing [ECO] button on the remote controller, a quiet
operation and mild operation is performed by reducing the fan speed and
the compressor speed.
<Cooling operation>
<Cooling operation>
This function operates the air conditioner with the difference
between the set and the room temperature as shown in the
following figure.
1) The room temperature (Tao) at
the start time of DRY operation is
detected.
The time correction is performed for 8 minutes each.
(However, the first correction is performed 150 seconds after
start of the operation.)
2) According to difference between
the room temperature and the
set temperature (Tsc), the
operation starts with the condi-
tions shown in the left figure.
Set temp.
Zone
12
11
10
9
Frequency
DRY max
Fan
L+ (W7)
Time correction
TA
[˚C]
(Tsc) = Set temp. on remote
controller (Ts) + (0.0 to 1.0)
*12
*11
*10
+4.0
+3.5
+3.0
+2.5
+2.0
+1.5
+1.0
+0.5
TSC
–0.5
–1.0
3) If the room temperature is down
by 2°C or more, turn off the
compressor.
+ 1
L (W6)
8
*9
7
*8
6
5
4
3
2
1
COOL min
L– (W5)
± 0
UL (W4)
–1 zone: min 1
–2.0
0
OFF
* 12 (DRY max - COOL min) /6 x 5 + COOL min
* 11 (DRY max - COOL min) /6 x 4 + COOL min
* 10 (DRY max - COOL min) /6 x 3 + COOL min
* 9 (DRY max - COOL min) /6 x 2 + COOL min
* 8 (DRY max - COOL min) /6 x 1 + COOL min
<Heating operation>
<Heating operation>
1) The indoor fan speed is con-
trolled within (W7) as maximum
value.
30 minutes
→ Time Compressor
speed
0Hz
2) Setting the compressor speed to
Max. 52Hz, the temperature zone
in which the operation can be
performed with Max. 16Hz is
gradually widened after 30
minutes passed when starting
ECO operation.
0
–0.5
–1.0
–1.5
–2.0
–2.5
–3.0
–4.0
–5.0
–6.0
–7.0
–8.0
–9.0
A
B
A
A zone
16Hz
3) The louver position is set
horizontally (Standard cooling
position) when the room tem-
perature comes close to the set
temperature or when 25 minutes
passed after starting ECO
operation.
B zone
16 to 52Hz
B
C
C
–10.0
–11.0
C zone
52Hz
– 35 –
Item
Operation flow and applicable data, etc.
Description
11. Temporary Pressing [RESET] button starts the temporary opera-
1) When pressing [RESET] button, the
temporary [AUTO] operation starts.
operation
tion of [AUTO] operation. When keeping [RESET]
button pressed for 10 seconds or more, the temporary
[COOL] operation is performed.
2) When keeping [RESET] button pressed
for 3 seconds or more, Pi, Pi, Pi sound is
heard and [AUTO RESTART] control is
changed.
YES
3) When keeping [RESET] button pressed
for 10 seconds or more, “Pi” sound is
heard and the temporary [COOL]
operation starts.
Press RESET button.
Filter lamp ON
NO
NO
Did you press [RESET] button
for 3 seconds or more?
Temporary [AUTO] operation
4) If the filter lamp goes on, press [RESET]
button to go off the filter lamp, and then
press [RESET] button again.
YES
YES
Did you press [RESET] button
for 10 seconds or more?
5) To stop the temporary operation, press
the button again.
NO
Switch to [AUTO RESTART] control.
Temporary [COOL] Operation
12. Air
purifying
This function generates nagative ion while cleaning the air in the room.
If air purifier-ON signal is received while the air conditioner stops, the air purifier starts operation,
and if it is received while the air conditioner operates, the air conditioner and the air purifier start
operation.
control
The air ion generator operates linked with the air purifying operation.
* When the previous operation was the
operation of air conditioner + air purifier,
Operation button
Present status
Stop
PURE button
Air purifier
Air conditioner
AC operation*
AC + Air purifier
All stop
an operation of air conditioner + air purifier
starts by pushing AC button on the remote
controller.
(Operation of air conditioner + air purifier
is stored in memory.)
Air purifier only
Air conditioner
Joint use of AC and air purifier
Stop (All)
AC + Air purifier
AC operation
All stop
*1 Swing is available
Louver*1
Fan speed *2
*2 Fan speed is Fan Auto mode varies in
order, (M + 1) → (L) → (L–) → (SL).
Air purifying operation
Cooling position
AUTO, L, L+, M, M+, H
AC + Air purifying operation Follows to AC operation Follows to AC operation
Sending air purifier-ON
Sending air purifier-OFF
1
2
1
2
3
4
3
4
,
,
Air conditioner stops
Air conditioner operates
Air purifier operates
Air conditioner +
Air purifier operate
Operation lamp ON
Start of air purifier-ON
Operation lamp OFF
Fan stop
Filter-OFF
*1
*2
Memory position
of louver/COOL
Air conditioner +
air purifier operate
Air conditioner operates
Air purifier-OFF
Louver close
All stop
Fan ON
Air purifier ON
Air purifying operation
– 36 –
Item
Operation flow and applicable data, etc.
Description
1. Purpose
12. Air purifying control [Detection of abnormality]
Purifying operation
The air purifying control function is to
alert the user to trouble in the ionizing or
air purifying operation.
2. Description
Trouble is determined to have occurred
(indicated by the FILTER indicator) in the
following four cases.
YES
Total operation
time 1000H
NO
1) When a count of 1000H has been
reached on the timer
Purifier power ON
2) When the panel switch has been set to
OFF by the opening of the air inlet
grile, etc.
NO
Error input
3) When an abnormal discharge caused
by a symptom such as the build-up of
dirt has been detected while the air
purifier is ON
YES
NO
Purifier power ON
1 minute or less
Filter lamp-OFF
continues.
YES
4) When the electric dust collector has
not been installed correctly
Purifier power OFF
Filter lamp ON
* Trouble case (2) or (3) is deemed to
have occurred when the action
concerned continues for more than
one second.
Purifier power ON
after 10 minutes
from the error input.
Purifier power OFF
3. Operation
The sequence that FILTER indicator is
turned on are described in the left
flowchart.
NO
Filter lamp ON
Error input
YES
1) When 1000H timer counts up, the
FILTER indicator keeps lighting even if
the operation is stopped by the remote
controller.
Purifier power OFF
Purifier power OFF
1
The timer is stored in memory of the
microcomputer, and the operation time
is cleared by filter RESET button on
the indoor unit or a power failure.
(FILTER indicator goes off.)
2
3
1) Reset by RESET button.
2) Reset by RESET button or by the stop direction
from the remote controller.
2) A trouble detected within 1 minute
after activation of the air is immedi-
ately judged as an error and the
FILTER indicator goes on.
* When the breaker is turned [ON] (In restart time
after power failure) or RESET button is pressed
while the FILTER indicator is turned on, the air
purifier is not turned on until the integrated
operation time of the indoor fan exceeds 1 hour
after operation start (It is nor the air purifier
operation time).
It is the safety measures considering an incom-
plete drain when electric dust collector has been
cleaned with water.
3) In case that 1 minute passed after
activation of the purifier, the purifier is
turned off while the PURE indicator
keeps ON. After 10 minutes passed,
restart the purifier and an error is
judged again.
13. Discharge temperature control
1. Purpose
This function detects error on the
refrigerating cycle or error on the com-
pressor, and performs protective control.
Td value
Control operation
Judges as an error and stops the compressor.
Reduce the compressor speed.
117°C
112°C
108°C
105°C
2. Operation
Reduce slowly compressor speed.
Keeps the compressor speed.
• Control of the compressor speed
The speed control is performed as
described in the left table based upon
the discharge temperature.
If the operation is performed with lower speed than one
commanded by the serial signal, speed is slowly raised
up to the commanded speed.
98°C
Operates with speed commanded by the serial signal.
– 37 –
Item
Operation flow and applicable data, etc.
Description
14. Pulse motor
valve (P.M.V.)
control
This function controls throttle amount of the
refrigerant in the refrigerating cycle.
1) When starting the operation, move the
valve once until it fits to the stopper.
(Initialize)
According to operating status of the air conditioner,
this function also controls the open degree of valve
with an expansion valve with pulse motor.
* In this time, “Click” sound may be
heard.
2) Adjust the open degree of valve by super
heat amount. (SH control)
3) If the discharge temperature was exces-
sively up, adjust the open degree of valve
so that it is in the range of set tempera-
ture.
Starting up
Initialize
(Discharge temp. control)
4) When defrost operation is performed, the
open degree of valve is adjusted accord-
ing to each setup conditions during
preparation for defrost and during defrost
operation (4-way valve is inversed.).
Move to
initial position
5) To turn off the compressor while the air
conditioner stops by control of the
Compressor ON
thermostat or by remote controller, adjust
the open degree of valve to the setup
value before stop of the compressor.
Td
SH control
release control
PMV open degree control
Stop by
remote controller
Room temp. sensor
(Ta sensor) control
Power OFF
Defrost
* SH (Super Heat amount) =
Ts (Temperature of suction pipe of the compressor) –
Tc or Te (Heat exchanger temperature at evaporation side)
* PMV: Pulse Motor Valve
– 38 –
Item
Operation flow and applicable data, etc.
Description
15. Clean operation
1. Purpose
The clean operation is to minimize the
growth of mold, bacteria etc. by running
the fan and drying so as to keep the
inside of the air conditioner clean.
Unit now performing cooling or dry operation
Clean operation
When the cooling or dry operation shuts
down, the unit automatically starts the
clean operation which is then performed
for the specified period based on duration
of the operation which was performed
prior to the shutdown, after which the
clean operation stops.
Press “STOP” button
Only S.CLEAN indicator lights, and clean operation starts
(The clean operation is not performed
after a heating operation.)
2. Operation
Time set now elapses
Operation stops
1) When the stop signal from the remote
controller is received, the S.CLEAN
indicator (green) on the main body
lights, and the clean operation starts.
(Neither the OPERATION indicator nor
the TIMER indicator light.)
2) The period of the clean operation is
determined by the duration of the
operation performed prior to the
reception of the stop code.
• During clean operations: The louver opens
slightly. The indoor fan operates continuously at
a speed of 260 rpm.
3) After the clean operation has been
performed for the specified period, the
unit stops operating.
Clean operation times
Operation mode
Operation time
Clean operation time
No clean operation
performed (0 minutes)
Up to 10 minutes
Cooling: Auto (cooling) Dry From 10 minutes up
to 1 hour
2 hours
4 hours
1 hour or longer
Heating: Auto (heating)
Auto (fan only)
Shutdown
No clean operation performed
• To stop an ongoing clean operation at any time
Press the start/stop button on the remote controller twice during the clean
operation. (After pressing the button for the first time, press it for the
second time without delay (within 10 minutes).)
– 39 –
Item
Operation flow and applicable data, etc.
Description
16. Clean operation Setting the clean operation release
release
* J04 will be near the MCU so take
steps to ensure that it will not be
exposed to excessive levels of
heat.
Add J04 of the indoor P.C. board assembly.
* This cancels the auto restart function.
Also take care to avoid solder
bridging with the surrounding
components.
Hold down the auto operation switch on the indoor unit
for at least 3 seconds but not more than 10 seconds.
The indoor unit’s buzzer emits three beeps, and
the OPERATION indicator flashes at 5 Hz intervals.
This completes the clean operation release setting.
Setting the clean operation
Cut J04 of the indoor P.C. board
* This step may be skipped if the auto restart function
is not required.
Hold down the auto operation switch on the indoor unit
for at least 3 seconds but not more than 10 seconds.
The indoor unit’s buzzer emits three beeps, and
the OPERATION indicator flashes at 5 Hz intervals.
This completes the clean operation setting.
Indoor P.C. board
J04
– 40 –
Item
Operation flow and applicable data, etc.
Description
17. Select switch on
remote controller
1. Purpose
This operation is to operate only one
indoor unit using one remote controller.
2. Description
Press the operation button
on the remote controller.
When operating one indoor unit in a
situation where two indoor units have
been installed in the same room or
nearby rooms, this operation prevents the
remote controller signal from being
received simultaneously by both units,
thus preventing both units from operating.
Select “B” as the setting for
one of the two indoor units and
for the remote controller.
(See below for details.)
YES
Both indoor units
start operation.
3. Operation
NO
The indoor unit on which the remote
controller selection has been set to B
receives the signal of the remote control-
ler also set to B.
(At the factory the remote controller
selection is set to A on all the indoor
units. There is no A setting display.)
Unnecessary set
[Remote controller select]
Setting the remote controller
Switching between A and B is enabled by cutting the jumper wire
inside the battery box using pliers.
1) Slide open the remote controller cover and remove the
batteries.
HiPOWER
ECO
MEMO
2) Cut the jumper wire inside the battery compartment using
nippers.
.
.
.
1 3 5 9H
SWING
CLR
FIX
FAN
SLEEP
Jumper wire
• The jumper wire should not remain in contact after being cut.
Also, be careful not to let plastic scraps, jumper wire cuttings
or other debris enter the inside of the remote controller.
SET
ON
OFF
CLOCK
RESET
CHECK
3) Insert the batteries. “B” appears in the remote controller
display.
* Even after the jumper wire has been cut, switching between
A and B is still possible by pressing the CHECK button and
FIX button together.
The A or B setting, which was switched by pressing the
CHECK button and FIX button together, is restored to the
setting established prior to the switching when the battery is
replaced or the RESET button is pressed.
Setting the selector switch on the main unit
• Remove the front panel, and then set the selector switch to “B”.
• After making the switch setting, remount the front panel.
Cutting direction
Position of remote controller selector switch
When switching between
settings “A” and “B”, always
switch the indoor unit board and
the remote controller as a pair.
(Otherwise, the indoor unit will
not accept the remote
controller’s signals.)
Selector switch
– 41 –
9-3. Auto Restart Function
This indoor unit is equipped with an automatic restarting function which allows the unit to restart operating with
the set operating conditions in the event of a power supply being accidentally shut down.
The operation will resume without warning three minutes after power is restored.
This function is not set to work when shipped from the factory. Therefore it is necessary to set it to work.
9-3-1. How to Set the Auto Restart Function
To set the auto restart function, proceed as follows:
The power supply to the unit must be on ; the function will not set if the power is off.
Press the [RESET] button located in the center of the front panel continuously for three seconds.
The unit receives the signal and beeps three times.
The unit then restarts operating automatically in the event of power supply being accidentally shut down.
• When the unit is standby (Not operating)
Operation
Motions
Press [RESET] button for more than
three seconds. (Less than 10 seconds)
The unit is on standby.
↓
The unit starts to operate.
The green indicator is on.
↓
After approx. three seconds,
The unit beeps three times
and continues to operate.
The green indicator flashes
for 5 seconds.
If the unit is not required to operate at this time, press [RESET]
button once more or use the remote controller to turn it off.
• When the unit is in operation
Operation
Motions
Press [RESET] button for more than
three seconds. (Less than 10 seconds)
The unit is in operation.
The green indicator is on.
↓
The unit stops operating.
The green indicator is turned off.
↓
After approx. three seconds,
The unit beeps three times.
The green indicator flashes
for 5 seconds.
If the unit is required to operate at this time, press [RESET] button
once more or use the remote controller to turn it on.
• When the unit is turned on by this function, the louver will not swing even though it was swinging automatically
before shutting down.
• While the filter check indicator is on, the RESET button has the function of filter reset button.
– 42 –
9-3-2. How to Cancel the Auto Restart Function
To cancel auto restart function, proceed as follows :
Repeat the setting procedure : the unit receives the signal and beeps three times.
The unit will be required to be turned on with the remote controller after the main power supply is turned off.
• When the system is on stand-by (not operating)
Operation
Motions
Press [RESET] button for more than
three seconds. (Less than 10 seconds)
The unit is on standby.
↓
The unit starts to operate.
The green indicator is on.
↓
After approx. three seconds,
The unit beeps three times and continues to operate.
If the unit is not required to operate at this time, press [RESET]
button once more or use the remote controller to turn it off.
• When the system is operating
Operation
Motions
Press [RESET] button for more than
three seconds. (Less than 10 seconds)
The unit is in operation.
The green indicator is on.
↓
The unit stops operating.
The green indicator is turned off.
↓
After approx. three seconds,
The unit beeps three times.
If the unit is required to operate at this time, press [RESET] button
once more or use the remote controller to turn it on.
9-3-3. Power Failure During Timer Operation
9-4. FILTER Indicator
When the unit is turned off because of power failure
during timer operation, the timer operation is can-
celled. In that case, set the timer operation again.
When the elapsed time reaches 1000 hours after air
purifier operation, the FILTER indicator lights.
After cleaning the filters, turn off the FILTER indicator.
NOTE :
The Everyday Timer is reset while a command signal
can be received from the remote controller even if it
stopped due to a power failure.
9-4-1. How to Turn Off FILTER Indicator
Press [RESET] button on the indoor unit.
NOTE :
If [RESET] button is pushed while the FILTER indica-
tor is not lit, the indoor unit will start the automatic
operation.
When you want a temporary operation while the
FILTER lamp lights, press [RESET] button to turn off
the FILTER lamp. (See page 36)
– 43 –
9-5. Remote Controller and Its Fuctions
9-5-1. Parts Name of Remote Controller
11
Cancel button (CLR)
Press this button to cancel the ON timer and OFF
timer. (A receiving beep is heard.)
1
2
Infrared signal emitter
Transmits signal to the indoor unit.
button
12
13
High power button (Hi POWER)
Press this button to start high power operation.
Press the button to start operation.
(A receiving beep is heard.)
Press the button again to stop operation.
(A receiving beep is heard.)
Memory button (MEMO)
Press this button to ready for storing the settings.
Hold down the button for more than 3 seconds to
store the setting indicated on the remote controller
If no receiving sound is heard from the indoor unit,
press the button twice.
and until the
mark is displayed.
3
Mode select button (MODE)
Press this button to select a mode.
14 Automatic operation button (AUTO)
Each time you press the button, the modes cycle in
order from A : Auto changeover control,
Press this button to operate the air conditioner
automatically. (A receiving beep is heard.)
: Cool,
: Dry,
: Heat and back to A.
15
16
17
Economy button (ECO)
Press this button to operate the air conditioner
economically.
(A receiving beep is heard.)
TEMP
4
5
Temperature button (
)
.. The temperature setting is increased to 30°C.
PRESET button
Press this button to operate the air conditioner to
the settings stored using the MEMO button.
.. The temperature setting is reduced to 17°C.
(A receiving beep is heard.)
Fan speed button (FAN)
Press this button to select the fan speed.
When you select AUTO, the fan speed is automati-
cally adjusted according to the room temperature.
PURE button (PURE)
Press this button to start the electrical air purifying
operation.
Press the button again to stop operation.
You can also manually select the desired fan speed
from five available settings.
18
Sleep time button (SLEEP)
Press this button to start the sleep timer (OFF
timer) operation.
(LOW , LOW+
HIGH
, MED
) (A receiving beep is heard.)
, MED+
,
6
Auto louver button (SWING)
Press this button to swing the louver.
(A receiving beep is heard.)
You can select the OFF timer time from among four
settings (1, 3, 5 or 9 hours).
Press this button again to stop the louver from
swinging. (A receiving beep is heard.)
1
7
8
Set louver button (FIX)
Press this button again to adjust the air flow
direction. (A receiving beep is heard.)
ON timer button (ON)
Use this button to change the clock and ON timer
times.
ON
To move up the time, press of the “ON
”
button.
ON
To move down the time, press of the “ON
button.
”
4
AUTO
PURE
17
14
9
OFF timer button (OFF)
Use this button to change the OFF timer times.
MODE
PRESET
3
16
5
OFF
To move up the time, press of the “OFF
button.
”
2
15
13
7
OFF
To move down the time, press of the “OFF
button.
”
HiPOWER
ECO
MEMO
12
SWING
CLR
FIX
FAN
SLEEP
6
18
10
Reserve button (SET)
Press this button to store the time settings.
(A receiving beep is heard.)
SET
11
10
ON
OFF
CLOCK
RESET
CHECK
9
8
– 44 –
9-5-2. Name and Functions of Indications on Remote Controller
[Display]
All indications, except for the clock time indicator, are displayed by pressing the button.
1
2
Transmission mark
6
TIMER and clock time indicator
The time setting for timer operation or the clock
time is indicated.
This transmission mark indicates when the
remote controller transmits signals to the indoor
unit.
The current time is always indicated except
during TIMER operation.
Mode indicator
Indicates the current operation mode.
(AUTO : Automatic control, A : Auto changeover
7
8
Hi-POWER indicator
Indicates when the Hi-POWER operation starts.
control,
: Cool,
: Dry,
: Heat)
Press the Hi-POWER button to start and press it
again to stop the operation.
3
4
5
Temperature indicator
Indicates the temperature setting.
(17°C to 30°C)
(MEMORY) indicator
Flashes for 3 seconds when the MEMO button is
pressed during operation.
PURE indicator
Shows that the electrical air purifying operation is
in progress.
The
mark is shown when holding down the
button for more than 3 seconds while the mark is
flashing.
FAN speed indicator
Indicates the selected fan speed.
Press another button to turn off the mark.
9
ECO indicator
Indicates when the ECO is in activated.
AUTO or five fan speed levels
(
LOW , LOW+
HIGH
, MED
, MED+
,
Press the ECO button to start and press it again
to stop operation.
) can be shown.
Indicates AUTO when the operating mode is
10
A, B change indicator remote controller
either AUTO or
: Dry.
When the remote controller switching function is
set, “B” appears in the remote controller display.
(When the remote controller setting is “A”, there is
no indication at this position.)
1
10
2
3
8
4
AUTO
• In the illustration, all indications are shown for
9 7
5
6
purposes of explanation.
During operation, only the relevant indicators are
shown on the remote controller.
– 45 –
9-6. Hi-POWER Mode
([Hi-POWER] button on the remote controller is pressed)
When [Hi-POWER] button is pressed while the indoor unit is in Auto, Cooling or Heating operation, Hi-POWER
mark is indicated on the display of the remote controller and the unit operates as follows.
1. Automatic operation
• The indoor unit operates in according to the current operation.
2. Cooling operation
• The preset temperature drops 1°C.
(The value of the preset temperature on the remote controller does not change.)
• If the difference between the preset temperature and the room temperature is big, the horizontal louver
moves to the Hi-POWER position automatically.
Then when the difference between them gets smaller, the horizontal louver returns automatically.
3. Heating operation
• The preset temperature increases 2°C.
(The value of the preset temperature on the remote controller does not change.)
4. The Hi-POWER mode can not be set in Dry operation
– 46 –
10. INSTALLATION PROCEDURE
10-1. Safety Cautions
For the rear left and left piping
Wall
Hook
47 mm or more
1
Installation plate
Hook
140 mm or more
Insert the cushion between
the indoor unit and wall, and
tilt the indoor unit for better
installation work.
74 mm
or more
Hook
7
Mounting screw
Do not allow the drain hose
to become slack.
Cut the piping
hole slightly
sloped
5
Zeolite-plus filter
Z Shield pipe
(for extension
drain hose)
Make sure the drain hose is
sloped downward.
6
Plasma pure filter
The auxiliary piping can be
connected at the left, rear left,
rear right, right, bottom right or
bottom left as shown below.
Air filters
Y
80 mm or more only
when unobstructed to
the front and both sides
2
Wireless
remote controller
Right
100 mm or more
from wall
50 mm or more
from wall
In principle,
leave open
Rear
right
Left
Bottom right Rear left
(C)
Bottom left
(D)
4
Remote controller holder
(Mounting holes on both
left and right sides)
As shown in the figure, position power cord and
connecting cable downward, and lead out along
piping connection port.
200 mm
or more
(B)
(A)
8
Remote controller
holder mounting screw
Insulate the refrigerant pipes
separately, not together.
250 mm or more
from wall
When installing the outdoor unit,
leave open in at least two of
directions (A), (B), (C) and (D)
shown in the right figure.
Power cord
Extension drain hose
(Option: RB-821SW)
Ensure sufficient space
to allow drainage
6 mm thick heat resisting
polyethylene foam
Before installing the wireless remote controller
• With the remote controller cover
Cover
removed, correctly load the
supplied batteries while
observing their polarity.
3
Batteries
2
Wireless remote controller
– 47 –
10-2. Optional Parts, Accessories andTools
10-2-1. Optional Installation Parts
Part Code
Parts name
Q’ty
Refrigerant piping
Liquid side (Outer diameter)
6.35 mm
Indoor unit name
RAS-B10GKVP-E, B13GKVP-E
RAS-B16GKVP-E
Gas side (Outer diameter)
9.52 mm
1 ea.
Y
Z
6.35 mm
12.7 mm
Shield pipe (for extension drain hose) (polyethylene foam, 6 mm thick)
1
Attachment bolt arrangement of outdoor unit
Elongated
drain hole
• Secure the outdoor unit with the attachment bolts and
nuts if the unit is likely to be exposed to a strong wind.
Suction side
( ꢀ )
• Use Ø8 mm or Ø10 mm anchor bolts and nuts.
If it is necessary to drain the defrost water, attach drain
nipple to the base plate of the outdoor unit before
installing it.
Drain hole
( ꢁ )
Diffuser
10-2-2. Accessory and Installation Parts
Part No.
Part name (Q’ty)
Installation plate × 1
Wireless remote control × 1
Battery × 2
Part No.
Part name (Q’ty)
Part No.
Part name (Q’ty)
ꢀ
‰
Š
Drain nipple* × 1
(RAS-10GAVP-E,
13GAVP-E, 16GAVP-E)
Zeolite-plus filter × 1
‚
ƒ
„
†
‡
ˆ
Water-proof rubber cap* × 2
(RAS-10GAVP-E,
13GAVP-E, 16GAVP-E)
Plasma pure filter × 1
Parts marked with asterisk (*) are
packaged with the outdoor unit.
<Others>
Name
Mounting screw Ø4 × 25L × 6
Owner’s manual
Installation manual
Important information and warning*
Remote control
holder mounting screw
Ø3.1 × 16L × 2
Remote control holder × 1
B/W strips*
(Energy efficiency labels)
This model is not equipped with an extension drain hose.
– 48 –
10-2-3. Installation/Servicing Tools
Changes in the product and components
In the case of an air conditioner using R410A, in order to prevent any other refrigerant from being charged
accidentally, the service port diameter of the outdoor unit control valve (3 way valve) has been changed.
(1/2 UNF 20 threads per inch)
• In order to increase the pressure resisting strength of the refrigerant piping flare processing diameter and size
of opposite side of flare nuts has been changed. (for copper pipes with nominal dimensions 1/2 and 5/8)
New tools for R410A
New tools for R410A
Applicable to R22 model
Changes
As pressure is high, it is impossible to measure by means of
conventional gauge. In order to prevent any other refrigerant from
being charged, each port diameter has been changed.
Gauge manifold
×
In order to increase pressure resisting strength, hose materials
and port size have been changed (to 1/2 UNF 20 threads per inch).
When purchasing a charge hose, be sure to confirm the port size.
Charge hose
×
As pressure is high and gasification speed is fast, it is difficult to
read the indicated value by means of charging cylinder, as air
bubbles occur.
Electronic balance
for refrigerant charging
¡
The size of opposite sides of flare nuts have been increased.
Incidentally,
a common wrench is used for nominal diameters 1/4 and 3/8.
Torque wrench
(nominal diam. 1/2, 5/8)
×
By increasing the clamp bar’s receiving hole, strength of spring in
Flare tool (clutch type)
the tool has been improved.
¡
Gauge for projection
adjustment
—
—
Used when flare is made by using conventional flare tool.
Connected to conventional vacuum pump. It is necessary to use
an adapter to prevent vacuum pump oil from flowing back to the
charge hose. The charge hose connecting part has two ports-one
for conventional refrigerant (7/16 UNF 20 threads per inch) and
one for R410A. If the vacuum pump oil (mineral) mixes with R410A
a sludge may occur and damage the equipment.
Vacuum pump adapter
Gas leakage detector
¡
Exclusive for HFC refrigerant.
×
• Incidentally, the “refrigerant cylinder” comes with the refrigerant designation (R410A) and protector coating in the
U. S’s ARI specified rose color (ARI color code: PMS 507).
• Also, the “charge port and packing for refrigerant cylinder” require 1/2 UNF 20 threads per inch corresponding to
the charge hose’s port size.
– 49 –
10-3-2. Drilling a Hole and Mounting Instal-
lation Plate
10-3. Indoor Unit
10-3-1. Installation Place
• A place which provides enough spaces around the
indoor unit as shown in the diagram.
Drilling a hole
When install the refrigerant pipes from the rear.
• A place where there are no obstacle near the air
inlet and outlet.
• A place which allows easy installation of the piping
to the outdoor unit.
The center of the
pipe hole
• A place which allows the front panel to be opened.
• The indoor unit shall be installed so that the top of
the indoor unit is positioned at least 2m in height.
Pipe
hole
• Also, avoid putting anything on the top of the
indoor unit.
CAUTION
• Direct sunlight on the indoor unit wireless
receiver should be avoided.
• The microprocessor in the indoor unit should
not be too close to r-f sources.
Fig. 10-3-2
(For details, see the owner's manual.)
1. After determining the pipe hole position on the
installation plate ( ð ) drill the pipe hole (Ø65
mm) at a slight downward slant to the outdoor
side.
Remote controller
• Should be placed where there are no obstacles,
such as curtains, that may block the signal.
NOTE :
• When drilling into a wall that contains a metal lath,
wire lath or metal plate, be sure to use a pipe hole
brim ring sold separately.
• Do not install the remote controller in a place
exposed to direct sunlight or close to a heating
source, such as a stove.
• Keep the remote controller at least 1 m away from
the nearest TV set or stereo equipment.
(This is necessary to prevent image disturbances or
noise interference.)
Mounting the installation plate
• The location of the remote controller should be
determined as shown below.
Anchor bolt holes
(Side view)
(Top view)
Indoor unit
Pipe hole
Reception
range
Pipe hole
Reception
range
Remote
controller
Indoor unit
Remote controller
1
Installation plate
7
Mounting screw
*: Axial distance
Fig. 10-3-3
Fig. 10-3-1
– 50 –
10-3-3. Electrical Work
When the installation plate is directly
mounted on the wall
1. The supply voltage must be the same as the
rated voltage of the air conditioner.
1. Securely fit the installation plate onto the wall by
screws with the upper and lower catches, that
hold the indoor unit, facing out.
2. Prepare a power source for the exclusive use of
the air conditioner.
2. To mount the installation plate on a concrete wall
use anchor bolts. Drill the anchor bolt holes as
illustrated in the above figure.
NOTE :
• Wire type :
More than H07RN-F or 245IEC66 (1.0mm²)
3. Install the installation plate horizontally and level.
CAUTION
CAUTION
• This appliance can be connected to a main
circuit breaker in either of the following two
ways.
When installing the installation plate with mount-
ing screw, do not use the anchor bolt hole.
Otherwise the unit may fall down and result in
personal injury and property damage.
1. Connection to fixed wiring:
A switch or circuit breaker which discon-
nects all poles and has a contact separa-
tion of at least 3 mm must be incorporated
in the fixed wiring. An approved circuit
breaker or switch must be used.
2. Connection with power supply plug:
Anchor bolt
Attach power supply plug with power cord
and plug it into wall outlet. An approved
power supply cord and plug must be used.
Projection
15mm or less
NOTE :
• Perform wiring work being sure the wire length is
long enough.
Fig. 10-3-4
5 mm dia. hole
10-3-4. Wiring Connection
How to connect the connecting cable
7 Mounting screw
Ø4 × 25L
Wiring the connecting cable can be carried
out without removing the front panel.
Clip anchor
(local parts)
1. Remove the air inlet grille. Open the air inlet grille
upward and pull it toward you.
2. Remove the terminal cover and cord clamp.
Fig. 10-3-5
3. Insert the connecting cable (or as according to
local regulations/codes) into the pipe hole on the
wall.
CAUTION
4. Pull the connecting cable through the cable slot
on the rear panel so that it protrudes about
15 cm out of the front.
Failure to securely install the unit may result in
personal injury and/or property damage if the
unit falls.
5. Insert the connecting cable fully into the terminal
block and secure it tightly with screws.
• In case of block, brick, concrete or similar type
walls, drill 5 mm dia. holes in the wall.
6. Tightening torque: 1.2 N•m (0.12 kgf•m)
7. Secure the connecting cable with the cord clamp.
• Insert clip anchors for the
mounting screws.
‡
8. Attach the terminal cover, rear plate bushing and
air inlet grille on the indoor unit.
NOTE :
• Install the installation plate using mounting screws
between 4 to 6, being sure to secure all four
corners.
– 51 –
10-3-5. Piping and Drain Hose Installation
Piping and drain hose forming
CAUTION
• Be sure to refer to the wiring system diagram
labeled inside the front panel.
• Since condensation results in machine trouble,
make sure to insulate both the connecting pipes
separately.
• Check local electrical regulations for any
specific wiring instructions or limitations.
(Use polyethylene foam as insulating material.)
Terminal cover
Rear right
Rear left
Bottom left
Left
Screw
Screw
Cord clamp
Terminal block
Bottom right
Right
Earth wire
Fig. 10-3-10
Connecting cable
1. Die-cutting front panel slit
Cut out the slit on the left or right side of the front
panel for the left or right connection and the slit
on the bottom left or side of thefront panel for the
bottom left or right connection with a pair of
nippers.
Fig. 10-3-6
Terminal block
2. Changing drain hose
For left connection, left-bottom connection and
rear-left connection’s piping, it is necessary to
relocate the drain hose and drain cap.
Fig. 10-3-7
How to remove the drain cap
Clip drain cap with needle-nose pliers, and pull out.
Connecting cable
About 15 cm
Fig. 10-3-8
Fig. 10-3-11
70 mm
How to remove the drain hose
10 mm
Earth line
The drain hose is secured in place by a screw.
Remove the screw securing the drain hose, then pull
out the drain hose.
10 mm
50 mm
Fig. 10-3-9
NOTE :
Screw
Drain hose
WIRE TYPE : more than H07 RN-F or 245 IEC 66.
(1.0mm²)
Fig. 10-3-12
– 52 –
How to attach the drain cap
In case of bottom right or bottom left piping
1. Insert hexagonal wrench (4 mm).
• After making slits on the front panel with a knife or
similar tool, cut them out with a pair of nippers or
an equivalent tool.
Slit
Fig. 10-3-16
4 mm
Fig. 10-3-13
Left-hand connection with piping
2. Firmly insert drain cap.
Bend the connecting pipes so that they are posi-
tioned within 43 mm above the wall surface.
If the connecting pipes are positioned more than
43 mm above the wall surface, the indoor unit may
be unstable.
No gap
Do not apply lubricating oil
(refrigerant machine oil)
when inserting the drain cap.
If applied, deterioration and
drain leakage of the drain
plug may occur.
When bending the connecting pipe, make sure to
use a spring bender to avoid crushing the pipe.
Insert a hexagon
wrench (Ø4mm)
Refer to the table below for the bending
radius of each connection pipe.
Fig. 10-3-14
Outer diameter
6.35 mm
Bending radius
30 mm
9.52 mm
40 mm
How to attach the drain hose
12.7 mm
50 mm
Always use the original screw that secured the
drain hose to the unit. If using a different screw
may cause water to leak.
To connect the pipe after installation of the
unit (figure)
Insert the drain hose firmly until the connector
contacts with the insulation, then secure it in place
using the original screw.
(To the front flare)
220 mm
Gas side
170 mm
CAUTION
Liquid side
Securely insert the drain hose and drain cap;
otherwise, water may leak.
R30 or less (Ø6.35), R40 or less (Ø9. 52), R50 or less (Ø12. 7)
Use polishing (polyethylene core or the like for bending pipe).
Outward form of indoor unit
In case of right or left piping
• After making slits on the front panel with a knife or
similar tool, cut them out with a pair of nippers or
an equivalent tool.
Use a screwdriver handle, etc.
Fig. 10-3-17
NOTE :
If the pipe is incorrectly bent, the indoor unit may be
unstable on the wall.
Slit
After passing the connecting pipe through the pipe
hole, connect the connecting pipe to the auxiliary
pipes and wrap the facing tape around them.
Fig. 10-3-15
– 53 –
10-3-7. Drainage
CAUTION
1. Run the drain hose at a downward sloped angle.
• Bind the auxiliary pipes (two) and connecting
cable with facing tape tightly.
NOTE :
In case of leftward piping and rear-leftward
piping, bind the auxiliary pipes (two) only with
facing tape.
• Hole should be made at a slight downward slant
on the outdoor side.
Do not rise the drain hose.
Do not form the drain hose
into the waved shape.
Indoor unit
Auxiliary pipes
Connecting
cable
50 mm
or more
Installation
plate
Fig. 10-3-18
Do not put the
Do not put the drain
hose end in the
drainage ditch.
drain hose end
• Carefully arrange the pipes so that none of the
into water.
pipes stick out of the rear plate of the indoor unit.
• Carefully connect the auxiliary pipes and
connecting pipes to each other and cut off the
insulating tape wound on the connecting pipe
to avoid double-taping at the joint, moreover,
seal the joint with the vinyl tape, etc.
Fig. 10-3-21
2. Put water in the drain pan and make sure that the
water is being drained outside.
• Since condensation can result in machine
performance trouble, be sure to insulate both
connecting pipes. (Use polyethylene foam as
insulating material.)
3. When connecting extension drain hose, insulate
the connection part of extension drain hose with
shield pipe.
• When bending a pipe, be careful not to crush it.
Shield pipe
10-3-6. Indoor Unit Installation
Drain hose Inside the room
Extension drain hose
1. Pass the pipe through the hole in the wall, and
hook the indoor unit on the installation plate at
the upper hooks.
Fig. 10-3-22
2. Swing the indoor unit to right and left to confirm
that it is firmly hooked on the installation plate.
3. While pressing the indoor unit onto the wall, hook
it at the lower part on the installation plate.
Pull the indoor unit toward you to confirm that it is
firmly hooked on the installation plate.
CAUTION
Install the drain pipe for proper drainage.
Improper drainage can result in water dripping
inside the room.
Hook here
1
1
Installation
plate
This air conditioner has been designed to drain
water collected from condensation which forms on
the back of the indoor unit, to the drain pan.
2
Push (unhook)
Hook
Therefore, do not locate the power cord and other
parts at a high place than the drain guide.
Fig. 10-3-19
• For detaching the indoor unit from the installation
plate pull the indoor unit toward you while pushing
the bottom up at the specified places.
Wall
Drain
guide
Space for
pipes
Push
Push
Fig. 10-3-23
Fig. 10-3-20
– 54 –
10-4. Outdoor Unit
Precautions for adding refrigerant
10-4-1. Installation Place
• Use a scale having a precision with at least 10 g
per index line when adding the refrigerant.
• A place which provides enough space around the
Do not use a bathroom scale or similar instrument.
outdoor unit as shown in the diagram.
• A place which can bear the weight of the outdoor
unit and does not allow an increase in noise level
and vibration.
• Use liquid refrigerant when refilling the refrigerant.
Since the refrigerant is in liquid form, it can fill
quickly.
Therefore, perform the filling operation carefully
and insert the refrigerant gradually.
• A place where the operation noise and discharged
air do not disturb neighbors.
• A place which is not exposed to a strong wind.
• A place free of combustible gases.
CAUTION
• A place which does not block a passageway.
1. Install the outdoor unit without anything
blocking the discharging air.
• When the outdoor unit is to be installed in an
elevated position, be sure to secure its feet.
2. When the outdoor unit is installed in a place
always exposed to strong winds like on the
coast or on a high story of a building, secure
the normal fan operation using a duct or a
wind shield.
• This air conditioner accepts a connection piping
length of up to 25 m.
• There is no need to add refrigerant as long as
the length of the connection piping is 15 m or
less.
3. Especially in windy areas, install the unit to
prevent the admission of wind.
• You will need to add 20 g of refrigerant per meter
of added connection piping for installations
requiring connection piping to be between 16 m
to 25 m.
4. Installation in the following places may result
in trouble.
Do not install the unit in such places.
• A place full of machine oil.
• An allowable height level is up to 10 m.
• A place where the drain water does not cause any
problems.
• A saline-place such as the coast.
• A place full of sulfide gas.
• A place where high-frequency waves are
likely to be generated, such as from audio
equipment, welders, and medical equip-
ment.
Strong
wind
Fig. 10-4-1
– 55 –
10-4-2. Draining the Water
10-4-3. Refrigerant Piping Connection
• Holes are provided on the base plate of the
outdoor unit to ensure that the defrost water
produced during heating operations is drained off
efficiently.
Flaring
1. Cut the pipe with a pipe cutter.
If a centralized drain is required when installing the
unit on a balcony or wall, follow the steps below to
drain off the water.
90˚
Obliquity Roughness
Warp
1. Proceed with water-proofing by installing the
water-proof rubber caps
in the 2 elongated
Š
holes on the base plate of the outdoor unit. [How
to install the water-proof rubber caps]
Fig. 10-4-4
1) Place four fingers into each cap, and insert
the caps into the water drain holes by pushing
them into place from the underside of the
base plate.
2. Insert a flare nut into the pipe, and flare the pipe.
• Projection margin in flaring : A (Unit : mm)
2) Press down on the outer circumferences of
the caps to ensure that they have been
inserted tightly.
Rigid (Clutch type)
Outer dia. of
copper pipe
R410A
tool used
Conventional
tool used
(Water leaks may result if the caps have not
been inserted properly, if their outer circumfer-
ences lift up or the caps catch on or wedge
against something.)
6.35
9.52
12.7
0 to 0.5
0 to 0.5
0 to 0.5
1.0 to 1.5
1.0 to 1.5
1.0 to 1.5
10 Water-proof rubber caps
(supplied with the outdoor unit)
Imperial (Wing nut type)
A
Outer dia. of
copper pipe
R410A
Base plate
6.35
1.5 to 2.0
1.5 to 2.0
2.0 to 2.5
Die
Pipe
9.52
9
Drain nipple
Fig. 10-4-5
12.7
Fig. 10-4-2
B
• Flaring size : B (Unit : mm)
2. Install the drain nipple
and a commercially
‰
available drain hose (with 16 mm inside diam-
eter), and drain off the water.
Fig. 10-4-6
(For the position where the drain nipple
installed, refer to the installation diagram of the
indoor and outdoor units.)
is
+0
‰
B
–0.4
Outer dia. of copper pipe
R410A
9.1
R22
9.0
• Check that the outdoor unit is horizontal, and
route the drain hose at a downward sloped
angle while ensuring that it is connected tautly.
6.35
9.52
12.7
13.2
16.6
13.0
16.2
Base plate
9
Drain nipple
Commercially available
• In case of flaring for R410A with the conventional
drain hose
flare tool, pull it out approx. 0.5 mm more than that
of R22 to adjust to the specified flare size.
The copper pipe gauge is useful for adjusting
projection margin size.
Do not use ordinary garden hose, but one can
flatten and prevent water from draining.
Fig. 10-4-3
– 56 –
Tightening Connection
Use a vacuum pump
Align the centers of the connecting pipes and tighten
the flare nut as much as possible with your fingers.
Then tighten the nut with a wrench and torque
wrench as shown in the figure.
Be sure to use a vacuum pump with counter-flow
prevention function so that oil inside the pump does
not flow back into the air conditioner pipes when the
pump stops. (If oil inside the vacuum pump enters
into the air conditioner circuit which uses R410A,
trouble with the refrigeration system may develop.)
Half union
Flare nut
1. Connect the charge hose from the manifold valve
to the service port of the gas side packed valve.
Externally
threaded side
Internally
threaded side
2. Connect the charge hose to the port of the
vacuum pump.
Use a wrench
to secure.
Use a torque wrench
to secure.
3. Open fully the low pressure side handle of the
gauge manifold valve.
Fig. 10-4-7
4. Operate the vacuum pump to begin evacuating.
Perform evacuating for about 15 minutes if the
piping length is 20 meters (15 minutes for 20
meters) (assuming a pump capacity of 27 liters
per minute).
CAUTION
• Do not apply excessive force.
Otherwise, the nut may break.
Confirm that the compound pressure gauge
reading is –101 kPa (–76 cmHg).
(Unit : N·m)
5. Close the low pressure valve handle of gauge
manifold.
Outer dia. of copper pipe
Ø6.35 mm
Tightening torque
14 to 18 (1.4 to 1.8 kgf•m)
33 to 42 (3.3 to 4.2 kgf•m)
50 to 62 (5.0 to 6.2 kgf•m)
6. Open fully the valve stem of the packed valves
(both sides of Gas and Liquid).
Ø9.52 mm
7. Remove the charging hose from the service port.
8. Securely tighten the caps on the packed valves.
Ø12.7 mm
• Tightening torque for connection of flare pipe
Compound
Pressure gauge
pressure
The pressure of R410A is higher than R22.
(Approx. 1.6 times.) Therefore securely tighten the
flare pipes which connect the outdoor unit and the
indoor unit with the specified tightening torque
using a torque wrench.
gauge
-101kPa
Manifold valve
(-76cmHg)
Handle Hi
(Keep full closed)
Handle Lo
Charge hose
(For R410A only)
Charge hose
(For R410A only)
If any flare pipe is
Flare at
indoor unit
side
Vacuum pump
adapter for
incorrectly connected,
it may cause not only
a gas leakage but also
trouble in the
counter-flow
prevention
(For R410A only)
Connecting
pipe
refrigeration cycle.
Vacuum
pump
Packed valve at liquid side
Packed valve at gas side
Flare at
outdoor unit
side
Service port
(Valve core (Setting pin))
Fig. 10-4-8
Fig. 10-4-9
CAUTION
10-4-4. Evacuating
After the piping has been connected to the indoor
unit, perform the air purge.
• IMPORTANT POINTS FOR PIPING WORK
1. Keep dust and moisture from entering the
pipes.
2. Tighten connections carefully (between pipes
and unit).
AIR PURGE
Evacuate the air in the connecting pipes and in
the indoor unit using a vacuum pump.
Do not use the refrigerant in the outdoor unit.
3. Evacuate the air in the connecting pipes
using a VACUUM PUMP.
4. Check for gas leaks at all connections.
For details, see the vacuum pump manual.
– 57 –
Packed Valve handling precautions
• Open the valve stem all the way; but do not try to
open it beyond the stopper.
3
1 2
10
N
L
10
• Securely tighten the valve stem cap with torque in
the following table:
10
10
40
40
30
30
Gas side (Ø12.7 mm)
50 to 62 N•m (5.0 to 6.2 kgf•m)
Gas side (Ø9.52 mm)
33 to 42 N•m (3.3 to 4.2 kgf•m)
Connecting
cable
Liquid side (Ø6.35 mm) 14 to 18 N•m (1.4 to 1.8 kgf•m)
Power cord
Earth line
Earth line
Service port
14 to 18 N•m (1.4 to 1.8 kgf•m)
Fig. 10-4-12
Hexagonal wrench is required.
Model RAS-
10GAVP-E 13GAVP-E 16GAVP-E
220 – 240 V ~50 Hz
Power source
220 V ~60 Hz
Maximum running
current
12 A
Fig. 10-4-10
Installation fuse
rating
25A (D type
)
Power cord
H07RN-F or 245IEC66 (1.5 mm²)
H07RN-F or 245IEC66 (1.0 mm²)
10-4-5. Wiring Connection
1. Remove the valve cover, the electric parts cover
and the cord clamp from the outdoor unit.
Connection cable
2. Connect the connecting cable to the terminal as
identified by the matching numbers on the
terminal block of indoor and outdoor unit.
CAUTION
• Incorrect wiring connection may cause electri-
cal parts to burn out.
3. Insert the power cord and the connecting cable
fully into the terminal block and secure it tightly
with screws.
• Be sure to comply with local regulations/codes
when running the wire from outdoor unit to
indoor unit.
4. Insulate the unused cords (conductors) from
water entering in the outdoor unit. Locate them
so that they do not touch any electrical or metal
parts.
(Size of wire and wiring method etc.)
• Every wire must be securely connected.
5. Secure the power cord and the connecting cable
with the cord clamp.
• This installation fuse (25A D type
must be used for the power supply line.
)
6. Attach the electric parts cover and the valve
cover on the outdoor unit.
• If incorrect or incomplete wiring is carried out,
fire or smoke may result.
• Prepare the power supply for the exclusive use
of the air conditioner.
Stripping length of connecting cable
• This product can be connected to the main
breaker.
Terminal block
Connection to fixed wiring:
A switch which disconnects all poles and has a
contact separation of at least 3 mm must be
incorporated in the fixed wiring when connect-
ing to a main breaker circuit.
1
2
3
L
N
Connecting cable
Power cord
Fig. 10-4-11
– 58 –
10-5-4. Remote Controller Selector Switch
Setting
10-5. Test Operation
10-5-1. Gas Leak Test
• Check the flare nut connections for gas leaks with
a gas leak detector and/or soapy water.
Remote controller selector switch
• If two indoor units are installed in the same room
or adjoining rooms, the second unit can inadvert-
ently receive a remote controller signal and start
operation when operating the first unit.This can be
prevented by setting one of the indoor units and
the corresponding remote controller to the B
setting (the A setting is the default setting).
Valve cover
Check places for
flare nut connections
(indoor unit)
1. Setting the selector switch on the main unit
Electric parts
• Remove the front panel, and then set the
selector switch to “B”.
• After making the switch setting, remount the
front panel.
Check places
for outdoor unit
2. Setting the remote controller
Fig. 10-5-1
1) Slide open the remote controller cover and
remove the batteries.
2) Cut the jumper wire inside the battery
compartment using nippers.
10-5-2. Test Operation
To test the system, press and hold RESET button for
10 sec. (There will be one short beep.)
• The jumper wire should not remain in
contact after being cut. Also, be careful
not to let plastic scraps, jumper wire
cuttings or other debris enter the inside of
the remote controller.
3) Insert the batteries. “B” appears in the
remote controller display.
3. Check that the indoor unit can be operated by
the modified remote controller.
Position of remote controller selector switch
Fig. 10-5-2
10-5-3. Auto Restart Setting
This product is designed so that, after a power
failure, it can restart automatically in the same
operating mode as before the power failure.
Selector switch
Fig. 10-5-3
Information
The product was shipped with Auto Restart
function in the OFF position.
Turn it ON as required.
Cutting direction
Jumper wire
HiPOWER
ECO
MEMO
.
.
.
1
3
5 9H
SWING
CLR
FIX
FAN
SLEEP
SET
ON
OFF
CLOCK
RESET
CHECK
When switching between settings “A” and
“B”, always switch the indoor unit board
and the remote controller as a pair.
(Otherwise, the indoor unit will not
How to Set the Auto Restart
• Press and hold the RESET button for about 3
seconds. After 3 seconds, three short electric
beeps will be heard to inform you that the Auto
Restart has been selected.
accept the remote controller’s signals.)
• To cancel the Auto Restart, follow the steps
described in the section Auto Restart Function on
Owner’s Manual.
Fig. 10-5-4
– 59 –
11. HOW TO DIAGNOSE THE TROUBLE
The pulse motor circuits are mounted to both indoor and outdoor units. Therefore, diagnose troubles according
to the trouble diagnosis procedure as described below. (Refer to the check points in servicing written on the
wiring diagrams attached to the indoor/outdoor units.)
Table 11-1
No.
1
Troubleshooting Procedure
First Confirmation
Page
62
No.
6
Troubleshooting Procedure
How to Check Simply the Main Parts
Troubleshooting
Page
72
2
Primary Judgment
63
7
73
3
Judgment by Flashing LED of Indoor Unit
Self-Diagnosis by Remote Controller
Judgment of Trouble by Every Symptom
63
8
How to Diagnose Trouble in Outdoor Unit
How to Check Simply the Main Parts
75
4
64
9
76
5
67
How to Simply Judge Whether Outdoor
Fan Motor is Good or Bad
10
81
u Precautions when handling the new inverter (3DV Inverter)
CAUTION: HIGH VOLTAGEN
The high voltage circuit is incorporated.
Be careful to do the check service, as the electric shock may be caused in case of touching parts on the
P.C. board by hand.
The new inverter (3DV inverter) will be incorporated starting with this unit.
(3DV: 3-shunt Discrete Vector control)
u The control circuitry has an uninsulated construction.
G-Tr
Compressor
Fan motor
FET
(6IN1)
Photocoupler
Shared potential
MCU
Hall device
Photocoupler
JAVP-E series (insulated type)
Compressor
Fan motor
IGBT × 6
Shared potential
Driver
Amplifier
FET × 6
MCU
Driver
Amplifier
GAVP-E, EAVP-E series (uninsulated type)
Fig. 11-1
– 60 –
CAUTION
A high voltage (equivalent to the supply voltage) is also energized to ground through the
sensors, PMV and other low-voltage circuits. The sensor leads and other wires are covered
with insulated tubes for protection. Nevertheless, care must be taken to ensure that these
wires are not pinched.
Take sufficient care to avoid directly touching any of the circuit parts without first turning off
the power.
At times such as when the circuit board is to be replaced, place the circuit board assembly in
a vertical position.
Laying the board flat on an electrically conductive object (such as the top panel of the air conditioner's
outdoor unit) while a charge is still retained by the electrolytic capacitors of the inverter's main circuit may
cause short-circuiting between the electrolytic capacitors and secondary circuit components and result in
damage to the components.
Sensor leads
Fig. 11-2
Do NOT lay the circuit board assembly flat.
u Precautions when inspecting the control section of the outdoor unit
NOTE :
A large-capacity electrolytic capacitor is used in the outdoor unit controller (inverter).Therefore, if the power
supply is turned off, charge (charging voltage DC280 to 380V) remains and discharging takes a lot of time.
After turning off the power source, if touching the charging section before discharging, an electrical shock may
be caused. Discharge the electrolytic capacitor completely by using soldering iron, etc.
< Discharging method >
1. Remove the inverter cover (plating) by opening four mounting claws.
2. As shown below, connect the discharge resistance (approx. 100Ω40W) or plug of the soldering iron to
voltage between + – terminals of the C14 (“CAUTION HIGH VOLTAGE” is indicated.) electrolytic capacitor
(500µF/400V) on P.C. board, and then perform discharging.
Discharging position
(Discharging period
10 seconds or more)
Plug of
soldering iron
Inverter cover
P. C. board
(Soldered surface)
Fig. 11-3
– 61 –
11-1. First Confirmation
11-1-1. Confirmation of Power Supply
Confirm that the power breaker operates (ON) normally.
11-1-2. Confirmation of Power Voltage
Confirm that power voltage is AC 220–230–240 ± 10%.
If power voltage is not in this range, the unit may not operate normally.
11-1-3. Operation Which is not a Trouble (Program Operation)
For controlling the air conditioner, the program operations are built in the microcomputer as described in the
following table.
If a claim is made for running operation, check whether or not it meets to the contents in the following table.
When it does, we inform you that it is not trouble of equipment, but it is indispensable for controlling and main-
taining of air conditioner.
Table 11-1-1
No.
Operation of air conditioner
Description
1
When power breaker is turned “ON”, the
operation indicator (Green) of the indoor
unit flashes.
The OPERATION lamp of the indoor unit flashes when
power source is turned on. If [START/STOP] button is
operated once, flashing stops.
(Flashes also in power failure)
2
Compressor may not operate even if the
room temperature is within range of
compressor-ON.
The compressor does not operate while compressor
restart delay timer (3-minutes timer) operates.
The same phenomenon is found after power source has
been turned on because 3-minutes timer operates.
3
4
In Dry and ECO mode, FAN (air flow)
display does not change even though FAN
(air flow select) button is operated.
The air flow indication is fixed to [AUTO].
Increasing of compressor motor speed
stops approx. 30 seconds after operation
For smooth operation of the compressor, the compres-
sor motor speed is restricted to Max. 41 rps for 2 min-
started, and then compressor motor speed utes, and Max.91 rps for 2 minutes to 3 minutes, respec-
increases again approx. 30 seconds after.
tively after the operation has started.
5
6
In AUTO mode, the operation mode is
changed.
After selecting Cool or Heat mode, select an operation
mode again if the compressor keeps stop status for 15
minutes.
In HEAT mode, the compressor motor
speed does not increase up to the maxi-
mum speed or decreases before the
The compressor motor speed may decrease by high-
temp. release control (Release protective operation by
temp.-up of the indoor heat exchanger) or current
temperature arrives at the set temperature. release control.
– 62 –
11-2. Primary Judgment
To diagnose the troubles, use the following methods.
1) Judgment by flashing LED of indoor unit
2) Self-diagnosis by service check remote controller
3) Judgment of trouble by every symptom
Firstly use the method 1) for diagnosis.Then, use the method 2) or 3) to diagnose the details of troubles.
11-3. Judgment by Flashing LED of Indoor Unit
While the indoor unit monitors the operation status of the air conditioner, if the protective circuit operates, the
contents of self-diagnosis are displayed with block on the indoor unit indication section.
Table 11-3-1
Check
code
Item
A
Block display
Description for self-diagnosis
OPERATION (Green)
Flashing display (1 Hz)
Power failure (when power is ON)
Indoor indication
lamp flashes.
OPERATION (Green)
Flashing display (5 Hz)
B
C
Protective circuit operation for indoor P.C. board
Which lamp
does flash?
OPERATION (Green)
TIMER (Yellow)
Flashing display (5 Hz)
Protective circuit operation for connecting cable
and serial signal system
OPERATION (Green)
FILTER (Orange)
Flashing display (5 Hz)
D
E
Protective circuit operation for outdoor P.C. board
OPERATION (Green)
TIMER (Yellow)
FILTER (Orange)
Protective circuit operation for others
(including compressor)
Flashing display (5 Hz)
NOTES :
1. The contents of items B and C and a part of item E are displayed when air conditioner operates.
2. When item B and C, and item B and a part of item E occur concurrently, priority is given to the block of item B.
3. The check codes can be confirmed on the remote controller for servicing.
– 63 –
11-4. Self-Diagnosis by Remote Controller (Check Code)
1. If the lamps are indicated as shown B to E in Table 11-3-1, execute the self-diagnosis by the remote controller.
2. When the remote controller is set to the service mode, the indoor controller diagnoses the operation condi-
tion and indicates the information of the self-diagnosis on the display of the remote controller with the check
codes. If a fault is detected, all lamps on the indoor unit will flash at 5Hz and it will beep for 10 seconds
(Beep, Beep, Beep ... ). The timer lamp usually flashes (5Hz) during self-diagnosis.
11-4-1. How to Use Remote Controller in Service Mode
1
Press [CHECK] button with a tip of pencil to set the
remote controller to the service mode.
• “
” is indicated on the display of the remote
controller.
2
Press [ON ] or [OFF ] button
If there is no fault with a code, the indoor unit will beep
once (Beep) and the display of the remote controller will
change as follows :
• • •
AUTO
PURE
• The TIMER indicator of the indoor unit flashes continuously.
(5 times per 1 sec.)
MODE
PRESET
• Check the unit with all 52 check codes (
to
)
as shown in Table-11-4-1.
HiPOWER
ECO
MEMO
.
.
.
1 3 5 9H
• Press [ON ] or [OFF ] button to change the check
code backward.
SWING
CLR
FIX
FAN
SLEEP
SET
ON
OFF
CLOCK
RESET
CHECK
If there is a fault, the indoor unit will beep for 10
seconds (Beep, Beep, Beep...).
Note the check code on the display of the remote
controller.
• 2-digits alphanumeric will be indicated on the display.
Alphanumeric characters are
used for the check codes.
• All indicators on the indoor unit will flash.
(5 times per 1 sec.)
is 5.
is A.
is C.
is 6.
is B.
is D.
Press [START/STOP] button to release the service mode.
3
4
• The display of the remote controller returns to as it
was before service mode was engaged.
Time shortening method.
1. Press SET button while pushing CHECK button.
2. Press [START/STOP] button.
Fig. 11-4-1
– 64 –
11-4-2. Caution at Servicing
1. After servicing, press the START/STOP button to return to the normal mode.
2. After servicing by the check code, turn off breaker of the power supply, and turn on breaker of the power
supply again so that memory in the microcomputer returns the initial status.
However, the check codes are not deleted even if the power supply is turned off because they are stored in
the fixed memory.
3. After servicing, press [CLR] button under check mode status and then send the check code “7F” to the
indoor unit. The error code stored in memory is cleared.
Table 11-4-1
Block distinction
Operation of diagnosis function
Air
Judgment and action
Check
code
Check
code
Block
Cause of operation
conditioner
status
Remarks
Indoor P.C.
board etc.
Short-circuit or discon-
nection of the room
temperature sensor
(TA sensor).
Operation Displayed when
continues. error is detected.
1. Check the room temp. sensor.
2. When the room temp. sensor is
normal, check P.C. board.
Being out of place,
disconnection, short-
circuit, or migration of
heat exchanger sensor
(TC sensor)
Operation Displayed when
continues. error is detected.
1. Check heat exchanger sensor.
2. When heat exchanger sensor is
normal, check P.C. board.
Lock of indoor fan or
trouble on the indoor fan
circuit
All off
Displayed when
error is detected.
1. Check the motor.
2. When the motor is normal,
check P.C. board.
Not
displayed
Trouble on other indoor
P.C. boards
Operation Displayed when
continues. error is detected.
Replace P.C. board.
Connecting
cable and
serial signal
Return serial signal is not Operation Flashes when
1. When the outdoor unit never
operate:
sent to indoor side from
operation started.
continues. trouble is detected
on Return serial
1) Check connecting cable, and
correct if defective wiring.
signal, and normal
status when signal
is reset.
1) Defective wiring of
connecting cable
2) Check 25A fuse of inverter
P.C. board.
2) Operation of compres-
sor thermo Gas
3) Check 3.15A of inverter P.C.
board.
shortage Gas leak
2. To display [Other] block during
operation, check compressor
thermo. operation and supply
gas (check gas leak also).
3. Unit operates normally during
check.
If return serial signal does not
stop between indoor terminal
board 2 and 3, replace inverter
P.C. board.
If signal stops between indoor
terminal board 2 and 3, replace
indoor P.C. board.
– 65 –
Block distinction
Operation of diagnosis function
Air
Judgment and action
Check
Block
code
Check
code
Cause of operation
conditioner
status
Remarks
Outdoor P.C.
board
Inverter over-current
protective circuit
operates. (Short time)
All off
All off
Displayed when
error is detected. operations stop immediately. :
Replace P.C. board.
Even if trying operation again, all
Position-detect circuit
error or short-circuit
between windings of
compressor
Displayed when
error is detected.
1. Even if connecting lead wire of
compressor is removed,
position-detect circuit error
occurred. : Replace P.C. board.
2. Measure resistance between
wires of compressor, and
perform short-circuit. : Replace
compressor.
Current-detect circuit
error
All off
All off
Displayed when
error is detected. operations stop immediately. :
Replace P.C. board.
Even if trying operation again, all
Being out of place,
disconnection or short-
circuit of the outdoor
heat exchanger sensor
(TE) or suction temp.
sensor (Ts)
Displayed when
error is detected.
1. Check sensors (TE, TS).
2. Check P.C. board.
Disconnection or short- All off
circuit of discharge
Displayed when
error is detected.
1. Check discharge temp. sensor
(TD).
temp. sensor
2. Check P.C. board
Outdoor fan drive
system error
All off
Displayed when
error is detected. protective operation of outdoor fan
drive system, fan lock, etc. :
Position-detect error, over-current
Replace P.C. board or fan motor.
Not
displayed
Outdoor heat exchanger Operation
temp. sensor error continues
1. Check outdoor temp. sensor
(TO).
——
2. Check P.C. board.
Outdoor P.C.
board
Compressor drive output All off
error, Compressor error
(lock, missing, etc.),
Break down
Displayed when
When 20 seconds passed after
error is detected. start-up, position-detect circuit error
occurred. : Replace compressor.
Trouble on P.M.V.
Others
(including
compressor)
Return serial signal has Operation Flashes when
1. Repeat Start and Stop with
interval of approx. 10 to 40
minutes. (Code is not displayed
during operation.)
Supply gas.
(Check also gas leak).
been sent when
operation started, but it
is not sent from halfway.
continues trouble is detected
on return serial
signal, and normal
status when signal
is reset.
1) Compressor thermo.
operation
Gas shortage
Gas leak
2. Unit operates normally during
check.
If return serial signal does not
stop between indoor terminal
block 2 and 3, replace inverter
P.C. board.
2) Instantaneous power
failure
If signal stops between indoor
terminal block 2 and 3, replace
indoor P.C. board.
Compressor does not
rotate.
(Current protective
circuit does not operate
when a specified time
passed after compressor
had been activated.)
All off
Displayed when
error is detected.
1. Trouble on compressor
2. Trouble on wiring of compressor
(Missed phase)
Discharge temp.
exceeded 117°C
All off
All off
Displayed when
error is detected.
1. Check dischage temp. sensor
(TD).
2. Gas leakage
3. Trouble on P.M.V.
Break down of
compressor
Displayed when
error is detected.
1. Check power voltage.
(220–230–240 V +10%)
2. Overload operation of refrigera-
tion cycle
Check installation condition
(Short-circuit of outdoor diffuser).
4-way valve inverse error Operation
1. Check 4-way valve operation.
(TC sensor value
lowered during heating
operation.)
continues
——
– 66 –
11-5. Judgment ofTrouble by Every Symptom
11-5-1. Indoor Unit (Including Remote Controller)
(1) Power is not turned on (Does not operate entirely)
<Primary check>
1. Is the supply voltage normal?
2. Is the normal voltage provided to the outdoor unit?
3. Is the crossover cable connected properly?
4. Is the fuse (F01) blown?
Operation
Check Item
Considerable principle cause
Turn off power supply once, and
5 second later, turn it on again.
Measures
NO
Item by symptoms
Is OPERATION indicator flashing?
YES
Is it possible to turn on
power supply by pushing
[START/STOP] button
on remote controller?
Does transmission mark
NO
NO
on remote controller flash
normally,and is its signal
transmitted properly?
Remote controller is defective.
YES
YES
Refer to (5) “Troubleshooting
for remote controller”.
Unit operates normally.
Does fan
YES
YES
Is fuse (F01)
of indoor control
board blown?
Parts (R04, R05, DB01, C01,
C03, IC01 and T01) are defective.
motor connector
between CN10 1 –
3 short-circuit?
NO
NO
Is voltage
(DC12V or 5V)
indicated on rear of
indoor control
NO
YES
Microcomputer
is defective.
Replace main
P.C. board
board normal?
Is DC310–340V
supplied between
CN10 1 – 3 ?
NO
Parts of a power supply circuit
defective.
YES
Replace fan
motor.
• Be sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of
damage of the motor.
(2) Power is not turned on though Indoor P.C. board is replaced
<Confirmation procedure>
Turn on power supply.
NO
NO
Is wired correctly to white and
Does OPERATION indicator flash?
YES
Correct wiring.
black lead wires of terminal block?
YES
To item of
“Power supply is not turned on”.
– 67 –
(3) Only the indoor motor fan does not operate
<Primary check>
1. Is it possible to detect the power supply voltage (AC220–240V) between
and
on the terminal block?
‚
2. Does the indoor fan motor operate in cooling operation?
(In heating operation, the indoor fan motor does not operate for approximately 10 minutes after it is turned
on, to prevent a cold air from blowing in.)
Turn off power
supply once, and
turn it on again.
Is it possible to detect
YES
NO
DC 1V or more between
Does fan motor
+
5
and
3
– of
continue to operate?
Peplace indoor
fan motor.
motor connector (CN10).
NO
YES
Start to operate
indoor unit in cooling
operation at airflow
level “LOW”.
Is it possible to detect
NO
NO
DC 310–340V between
Does indoor
fan operate?
+
1
and
3
–
of motor
connector (CN10).
YES
YES
Turn off indoor unit and remove
(Motor connection condition)
Is it possible to detect DC 15V
NO connector from motor.
Then push START/STOP button
on remote controller to stop
flashing lamp on indoor unit.
+
between
4
and
3
– of
motor connector (CN10).
YES
Is it possible to detect
NO
+
DC 15V between
4
Peplace main
P.C. board.
Change airflow level
to “HIGH”.
and
3
– of motor
connector (CN10).
YES
Start to operate the
indoor unit in except
Turn off indoor unit and
heating operation.
NO
remove connector from motor.
Then start to operate indoor
unit with remote controller.
At this time, is it possible to
detect DC 1V or more between
+
5
and
3
– of motor
connector (CN10)?
YES
Start to operate the
indoor unit in except
heating operation.
At this time, is it possible
to detect DC 1V or more
Is it possible to
change airflow level
to “HIGH”?
NO
NO
+
between
5
and
3
–
of motor connector (CN10)?
(Check this condition
within 15 seconds after
starting unit.)
YES
YES
Is it possible to
NO
NO
Peplace
bearing.
rotate cross-flow fan by
hand properly?
YES
Turn off indoor unit
and rotate cross-flow
fan by hand when the
unit is on standby.
At this time, is it possible to
detect DC 1V or more
+
between
5
and
3
–
of motor connector
(CN10).
Fan motor
operates normally.
YES
– 68 –
(4) Indoor fan motor automatically starts to rotate by turning on power supply
<Cause>
The IC is built in the indoor fan motor. Therefore the P.C. board is also mounted to inside of the motor.
If the P.C. board is soldered imperfectly or the IC is defective, the fan motor may automatically rotate by turning
on power supply.
<Inspection procedure>
1. Remove the front panel. (Remove 2 screws.)
2. Remove the cover of the fan motor lead wires.
3. Check DC voltage with CN10 connector while the fan motor is rotating.
NOTE :
• Do not disconnect the connector while the fan motor is rotating.
• Use a thin test rod.
Indoor fan starts rotating when power supply is turned on.
P.C. board
CN10
(Check output DC voltage of fan motor on P.C. board.)
6 (Blue)
5 (Yellow)
4 (White)
3 (Black)
Yellow
Black
Measure voltage between 3 (GND : BLACK)
and 5 (V line : YELLOW) of motor connector (CN10)
while indoor fan motor is rotating.
2
–
1 (Red)
DC 1.0V or more
P.C. board is defective.
Replace P.C. board.
Under DC 1.0V
Motor is defective.
Replace motor.
DC
– 69 –
(5) Troubleshooting for remote controller
<Primary check>
Check that A or B selected on the main unit is matched with A or B selected on the remote controller.
The unit does not beep at all.
Push the START/STOP button. Operation lamp on indoor
unit is not indicated.
NO
Is transmission
mark indicated?
YES
Is receiver
on indoor unit
exposed to
Push RESET button
on remote controller
with tip of pencil.
NO
direct sunlight?
YES
Does indoor unit
operate when moving
remote controller
near receiver or
indoor unit?
Is there any
thyristor
fluorescent light
nearby?
NO
NO
YES
YES
Batteries are
exhausted.
Push the START/
STOP button
Does indoor unit
NO
start to operate by
automatic restart
function?
NO
Is transmission
mark indicated?
YES
YES
NO
Does indoor unit
beep and operate?
YES
Does radio sound
is affected by remote
controller when a signal is
transmitted at distance of
5 cm from radio?
NO
YES
Remote controller
is defective.
P.C. board
is defective.
Keep indoor unit
away from thyristor
fluorescent light.
Avoid direct
sunlight.
Replace
P.C. board.
Replace
batteries.
Replace
remote controller.
Normal
operation
NOTE : After replacing batteries,
push the RESET button
with a tip of a pencil.
– 70 –
11-5-2. Wiring Failure (Interconnecting and Serial Signal Wire)
(1) Outdoor unit does not operate
1) Is the voltage between
and
of the indoor terminal block varied?
‚
ƒ
Confirm that transmission from indoor unit to outdoor unit is correctly performed based upon the follow-
ing diagram.
NOTE:
• Measurement should be performed 2 minutes and 30 seconds after starting of the operation.
• Be sure to prepare a diode for judgment.
Terminal block at indoor side
Red
3
2
1
S5277G or equivalent (G or J type)
(Diode with rated voltage of 400V
or more is acceptable.)
S5277G
White
Tester
Terminal block
Normal time
:Voltage swings between DC15 and 60V. ...................Inverter Assembly check (11-8-1.)
Abnormal time :Voltage does not vary.
(2) Outdoor unit stops in a little while after operation started
<Check procedure> Select phenomena described below.
1) The outdoor unit stops 10 to 20 minutes after operation started, and 10 minutes or more are required to
restart the unit.
Gas circulation amount is down.
Measure gas pressure.
Gas shortage
Gas leak
Pipe clogging
Thermo. operation of compressor
2) If the unit stops once, it does not operate until the power will be turned on again.
To item of Outdoor unit does not operate.
3) The outdoor unit stops 10 minutes to 1 hour after operation started, and an alarm is displayed.
(Discharge temp. error check code 03, 1E Sensor temp. error check code 02, 1C)
Gas leak
P.M.V. is defective.
Refer to the chart in 11-6.
Miswiring of connecting wires of indoor/outdoor units
Clogging of pipe and coming-off of TC sensor
– 71 –
11-6. Check Code 1C (Miswiring in indoor/outdoor units) and 1E
<Check procedure>
1C
1E
Gas leakage,
Discharge temp. error,
gas leakage
(Check code 03, 1E)
disconnection of TS/TC
sensors (Check code 02, 1C)
Valve drive check
NO
NO
Is coil of the pulse motor valve
(P.M.V.) correctly set?
Set it correctly.
Set it correctly.
YES
Is connecter of coil connected to inverter?
YES
Is positioning sound of valve (sound hitting to stopper) heard
from valve when the air conditioner starts the operation after turning off power
of the air conditioner once?
NO
Replace coil valve.
YES
Are temp. sensors of indoor/outdoor units correctly set to the holder?
NOTE :
The temperature sensors which are used to control pulse motor valve
include indoor heat exchanger sensor (TC), outdoor heat exchanger temp.
sensor (TE), outdoor suction temp. sensor (TS) and outdoor sensor (TO).
NO
Set it correctly.
YES
Gas amount check and valve clogging check
Remove TC sensor connector from the P.C. board in indoor unit.
(Remove connector from the P.C. board.)
Operate the air conditioner in COOL mode by TEMP button
(“Beep” sound is heard if keeping pushed for 10 seconds.).
The operation enters temporary operation mode which fixes opening degree of compressor speed.
Check condensation at outlet of PMV, and then check operating pressure from the service port.
Existence of condensation at outlet of P.M.V.
YES
Replace valve.
Add gas.
If there is condensation at outlet (1/4 inch=Ø6.35mm valve side),
the valve is clogged.
Check the operating pressure from service port, and add gas if pressure is low.
– 72 –
11-7. Troubleshooting
11-7-1. How to Check Whether the Air Purifier is Good or Not
Turn off the power breaker once,
and turn on again after 10 seconds.
NO
Does the OPERATION indicator flash?
To item “Power supply is not turned on”
YES
Turn off the power breaker and remove
CN34 (Micro switch connector).
1
2
Short-circuit between
and
pin
of CN34 at PC side, and turn on the
power breaker after 10 seconds.
Is DC12V applied
Is DC12V applied
NO
NO
1
1
2
between
(Red/DC12V) and
between
(+) and
(–)
(Brown/GND) of CN1 of the
high-voltage generator?
of CN33 of the main
P.C. board (MCC5020)?
YES
YES
Replace the main P.C. board (MCC5020)
Is there conduction of
micro-switch connector under
OFF status of the micro-switch
(Front panel opened)?
YES
NO
Micro-switch is stuck
Replace micro-switch.
• Conduction check of micro-switch
Push the switch
NO
Is there conduction of
micro-switch connector under
ON status of the micro-switch
(Front panel closed)?
Micro-switch malfunction
YES
ON
→ ON
1) Check operation while short-circuiting CN34 of the main P.C. board.
2) Perform air purifying operation by the remote controller.
• In this time, check that the remote controller is in status which is shortened by time on
the reactivation preventive timer and all display indicators go on for approx. 3 seconds
when a signal is received.
Release the switch
→ OFF
If time on the reactivation preventive timer is not shortened,
(
)
the high-voltage is not applied to electrode of the air purifier for approx. 1 hour.
• While the air purifier operates, check that the fan speed [AUTO] is not displayed.
(Because the power ON/OFF is controlled on the program)
Tester
3) Be sure not to touch the electric dust collector, ionizer, or ionized wire unit with the human body.
NO
To item “Only indoor fan does not operate”
Does the indoor fan rotate?
YES
NO
NO
Does the PURE indicator (Blue) or
the FILTER indicator (Orange) go on?
Replace the main P.C. board (MCC5020).
YES
Is DC-5V to DC-10V
applied between
• How to check output of the air purifier
<Caution on High Voltage!!>
Does the PURE indicator
go off within 2 seconds after
it was ON, and does the FILTER
indicator (Orange) go on?
NO
(Brown/Negative voltage)
4
2
and
(Brown/GND)
of CN33 of the main
P.C. board?
Collector
output
YES
YES
Dry the electric
dust collector
and ionizer.
Are the electric dust
collector and ionizer dried?
(Electrode check)
NO
YES
GND
Referring to the right figure, check the
Be sure not to come
Ionizer
output
high-output voltage of the air filter unit.
(NOTE)
to contact to the gray
part or not to touch
the ionized cables.
Use an exclusive high voltage tester;
otherwise the tester may be broken.
High-voltage tester
YES
Is output of the ionizer
approx. 4.0 kV to 4.8 kV?
Is output of the collector
approx. 3.0 kV to 3.8 kV?
Refer to items, cleaning and check
for the electric dust collector/ionizer/
ionized wire units.
NO
NO
Replace the high-voltage generator.
When the ionized wire is
disconnected or when dirt is
YES
(
)
not cleaned even cleaned,
replace each unit.
Are the electric dust
collector/ionizer/ionized
wire units dirty?
Is an abnormal sound
(cracking noise) heard
from the electrode?
YES
No trouble
– 73 –
11-7-2. How to Check Whether the Minus Ion Generator is Good or Not
Turn off the power breaker once,
and turn on again after 10 seconds.
NO
Does the OPERATION indicator flash?
YES
To item “Power supply is not turned on”
Turn off the power breaker and remove
CN34 (Micro switch connector).
Short-circuit between
1
and
2
pin
of CN34 at PC side, and turn on the
power breaker after 10 seconds.
Is DC12V applied
between
(Red/DC12V) and
NO
1
Replace the power P.C. board
(MCC5020) or the housing assembly.
(Brown/GND) of CN1 of the
high-voltage generator
in the air purifier?
2
YES
Is there conduction of
YES
NO
micro-switch connector under
OFF status of the micro-switch
(Front panel opened)?
Micro-switch is stuck
Replace micro-switch.
NO
Is there conduction of
micro-switch connector under
ON status of the micro-switch
(Front panel closed)?
Micro-switch malfunction
• Conduction check of micro-switch
YES
Push the switch
→ ON
ON
Release the switch
→ OFF
1) Check operation while short-circuiting CN34 of the main P.C. board.
2) Perform air purifying operation by the remote controller.
• In this time, check that the remote controller is in status which is shortened by time on
the reactivation preventive timer and all display indicators go on for approx. 3 seconds
when a signal is received.
If time on the reactivation preventive timer is not shortened,
(
)
the high-voltage is not applied to electrode of the air purifier for approx. 1 hour.
• While the air purifier operates, check that the fan speed [AUTO] is not displayed.
Tester
(Because the power ON/OFF is controlled on the program)
3) Be sure not to touch the electrode with the human body.
NO
To item “Only indoor fan does not operate”
Does the indoor fan rotate?
YES
NO
Does the PURE indicator (Blue) or
the FILTER indicator (Orange) go on?
Replace the main P.C. board (MCC5020).
YES
Does the PURE indicator
go off within 2 seconds after
it was ON, and does the FILTER
indicator (Orange) go on?
YES
To item “How to check whether
the air purifier is good or not”
NO
• How to check output of minus ion
<Caution on High Voltage!!>
Referring to the right figure, check the
high-voltage output of the air ionizer.
In this time, peel the thermal insulator, and attach
it to the original position after check operation.
high-voltage
unit
NOTE :
Use an exclusive high voltage tester; otherwise
the tester may be broken.
NO
YES
Does the electrode
output approx. –6kV?
No trouble
Electrode
NO
Replace the
high-voltage generator
GND
High-voltage tester
– 74 –
11-8. How to DiagnoseTrouble in Outdoor Unit
11-8-1. Summarized Inner Diagnosis of Inverter Assembly
Table 11-8-1
Diagnosis/Process flowchart
Item
Contents
Summary
Preparation Turn “OFF” the power supply
breaker, and remove 3P
Remove connector
of compressor.
connector which connects
inverter and compressor.
If fuse was blown, be sure to
check the electrolytic
capacitor and diode block.
(DB01)
Check
Check
• Check whether 25A fuse
on the control board
assembly is blown or not.
(F01)
NG
Check 25A fuse
(Part No.F01).
OK
Replace fuse.
• Connect discharge
resistance (approx. 100Ω,
40W) or soldering iron
(plug) between +, –
terminals of the electro-
lytic capacitor (760µF) of
C14 (with printed CAU-
TION HIGH VOLTAGE) on
P.C. board.
Check
electrolytic
capacitor, diode
block (DB01),
etc.
Discharging position
(Discharging period
10 seconds or more)
Check
NG
terminal voltage
of electrolytic
capacitor.
Plug of
soldering
iron
OK
Check
electrolytic
capacitor, diode
(DB01),
etc.
NO
Does outdoor
fan rotate?
Operation
Turn on the power breaker,
and operate the air condi-
tioner in COOL mode by time
shortening.
YES
OK if 760µF →
DC280 to 380V
Measure-
ment
Measure terminal voltage of
the electrolytic capacity.
Remove CN300 while
pushing the part indicated
by an arrow because CN300
is a connector with lock.
760µF:400WV × 3
After operation, turn off the
power breaker after 2
minutes 20 seconds passed,
and discharge the electro-
lytic capacitor by soldering
iron.
Remove connector
Check
Stop
CN300 of outdoor fan
motor, and using a
NG
tester, check resistance
value between every
phases at motor side.
Check voltage between
motor phases.
OK
Check
Measure-
ment
Replace
outdoor
fan motor.
• Is not winding between
-
‚
-
, or
-
opened
→ Resistance between
phases should be
‚ ‚ ƒ ƒ
or short-circuited?
approx. 55 to 77Ω
• Is not frame grounded with
, or
A
B
,
‚
?
ƒ
→ Should be 10MΩ or
more.
– 75 –
Diagnosis/Process flowchart
Item
Contents
Summary
Check
Check winding resistance
between phases of compres-
sor, and resistance between
outdoor frames by using a
tester.
A
B
• Is not grounded.
→ OK if 10MΩ or more
Replace control
board assembly.
• Is not short-circuited
between windings.
→ OK if 0.51Ω → 0.57Ω
(Check by a digital tester.)
Check
compressor
winding
NG
• Winding is not opened.
resistance.
OK
Operation
Remove connector CN300 of
the outdoor fan motor, turn
on the power supply breaker,
and perform the operation.
(Stops though activation is
prompted.)
Replace
control board.
Replace
compressor.
Check operation within 2
minutes 20 seconds after
activation stopped.
11-9. How to Check Simply the Main Parts
11-9-1. How to Check the P.C. Board (Indoor Unit)
(1) Operating precautions
1) When removing the front panel or the P.C. board, be sure to shut off the power supply breaker.
2) When removing the P.C. board, hold the edge of the P.C. board and do not apply force to the parts.
3) When connecting or disconnecting the connectors on the P.C. board, hold the whole housing. Do not pull
at the lead wire.
(2) Inspection procedures
1) When a P.C. board is judged to be defective, check for disconnection, burning, or discoloration of the
copper foil pattern or this P.C. board.
2) The P.C. board consists of the following 2 parts
a. Main P.C. board part :
DC power supply circuit (5V, 12V, 15V), Indoor fan motor control circuit, CPU and peripheral circuits,
buzzer, and Driving circuit of louver.
b. Indication unit of infrared ray receiving infrared ray receiving circuit, LED :
To check defect of the P.C. board, follow the procedure described below.
– 76 –
(3) Check procedures
Table 11-9-1
Check points
No.
Procedure
Causes
1
Turn off the power supply breaker Check whether or not the fuse (F01) Impulse voltage was applied or the
and remove the P.C. board
is blown.
indoor fan motor short-circuited.
assembly from electronic parts
base. Remove the connecting
cables from the terminal block.
2
Remove the connector of the
motor and turn on the power
supply breaker. If OPERATION
indicator flashes (once per
second), it is not necessary to
check steps (1 to 3) in the right
next column.
Check power supply voltage :
1. The terminal block or the crossover
cable is connected wrongly.
1. Between No. 1 and No. 3 of CN23
(AC 220–240V)
2. The capacitor (C01), line filter
(L01), resistor (R05), or the diode
(DB01) is defective.
2. Between
(DC 310–340V)
3. Between of C10 and output
and
of C03
3. IC01, IC08 and T01 are defective.
4. IC01, IC08 and T01 are defective.
side of IC08 (DC 15V)
4. Between 12V and GND
5. Between 5V and GND
5. IC01, IC08, IC07 and T01 are
defective.
3
4
Push [START/STOP] button once Check power supply voltage :
IC03 and IC04 are defective.
to start the unit. (Do not set the
mode to On-Timer operation.)
1. Between CN21 and
No. 1 of CN23 (DC 15–60V)
Shorten the restart delay timer
and start unit.
Check whether or not all indicators
(OPERATION, TIMER, FILTER,
PURE) are lit for 3 seconds and they
return to normal 3 seconds later.
The indicators are defective or the
housing assembly (CN13) is defective.
5
Push [START/STOP] button once 1. Check whether or not the com-
1. The temperature of the indoor heat
exchanger is extremely low.
to start the unit,
pressor operates.
• Shorten the restart delay timer.
2. Check whether or not the OP-
ERATION indicator flashes.
2. The connection of the heat ex-
changer sensor is loose.
(The connector is disconnected.)
(CN01)
• Set the operation mode to
COOL.
• Set the fan speed level to
AUTO.
3. The heat exchanger sensor and the
P.C. board are defective.
• Set the preset temperature
much lower than the room
temperature. (The unit (com-
pressor) operates continuously
in the above condition.)
(Refer to Table 11-4-1.)
4. The main P.C. board is defective.
6
If the above condition (No. 5) still
continues, start the unit in the
following condition.
1. Check whether or not the com-
pressor operates.
1. The temperature of the indoor heat
exchanger is extremely high.
2. Check whether or not the OP-
ERATION indicator flashes.
2. The connection of the heat ex-
changer sensor short-circuited.
(CN01)
• Set the operation mode to
HEAT.
• Set the preset temperature
much higher than room tem-
perature.
3. The heat exchanger sensor and the
P.C. board are defective.
(Refer to Table 11-4-1.)
4. The main P.C. board is defective
7
Connect the motor connector to
the motor and turn on the power
supply.
Start the unit the following
condition.
1. Check it is impossible to detect
the voltage (DC 15V) between 3
and 4 of the motor terminals.
1. The indoor fan motor is defective.
(Protected operation of P.C. board.)
2. The P.C. board is defective.
2. The motor does not operate or
the fan motor does not rotate with
high speed.
3. The connection of the motor
connector is loose.
• Set the fan speed level to HIGH.
(The unit (compressor) operates
continuously in the above
condition in No. 5.)
(But it is possible to receive the
signal from the remote controller.)
3. The motor rotates but vibrates
strongly.
– 77 –
11-9-2. P.C.BoardLayout
GND
+12V
+5V
[1] Sensor characteristic table
100
90
80
70
60
50
40
30
20
TD
TD : Discharge temp. sensor
TA : Room temp. sensor
TC : Heat exchanger temp. sensor
TO : Outdoor temp. sensor
TE : Outdoor heat exchanger temp. sensor
TS : Suction temp. sensor
TA, TC, TO, TE, TS
40 50
10
0
0
10
20
30
Temperature (˚C)
– 78 –
11-9-3. Indoor Unit (Other Parts)
No.
Part name
Checking procedure
1
Room temp. (TA) sensor
Heat exchanger (TC) sensor (Normal temp.)
Disconnect the connector and measure the resistance value with tester.
Temperature
TA, TC (kΩ)
Refer to 11-5-1. (5).
10°C
20°C
25°C
30°C
40°C
Sensor
20.7
12.6
10.0
7.9
4.5
2
3
Remote controller
Louver motor
MP24Z
Measure the resistance value of each winding coil by using the tester.
(Under normal temp. 25°C)
Position
Resistance value
White
Yellow
Yellow
Yellow
Yellow
1
2
3
4
5
1
2
3
4
5
1 to 2
1 to 3
1 to 4
1 to 5
380 ± 40Ω
4
Indoor fan motor
Refer to 11-5-1. (3) and (4).
11-9-4. OutdoorUnit
No.
Part name
Checking procedure
1
Compressor
(Model : DA111A1F-20F1)
Measure the resistance value of each winding by using the tester.
Red
Position
Red - White
White - Black
Black - Red
Resistance value
0.88 to 0.98Ω
Under 20°C
White
Black
2
Outdoor fan motor
(Model : ICF-140-43-4R)
Measure the resistance value of winding by using the tester.
Red
Position
Red - White
White - Black
Black- Red
Resistance value
17 to 25kΩ
17 to 25kΩ
17 to 25kΩ
White
Black
3
4
4-way valve coil
(Model : VHV)
Measure the resistance value of winding by using the tester.
Resistance value
1435 ± 144Ω
Under 20°C
Pulse motor valve coil
(Model : CAM-MD12TF-6)
Measure the resistance value of winding by using the tester.
Position
Red - White
Resistance value
1
6
3
W
R
COM
42 to 50kΩ
42 to 50kΩ
42 to 50kΩ
42 to 50kΩ
O
White - Orange
Brown- Yellow
Brown- Blue
Y BR BL
COM
2
5
4
Under 20°C
5
Outdoor temperature sensor Disconnect the connector, and measure resistance value with the tester.
(TO), discharge temperature (Normal temperature)
sensor (TD), suction
Temperature
10°C 20°C 25°C 30°C 40°C 50°C
temperature sensor (TS),
outdoor heat exchanger
temperature sensor (TE)
Sensor
TD (kW)
100
64
50
41
27
18
TO,TS,TE (kW)
20.7 12.6 10.0
7.9
4.5
—
– 79 –
11-9-5. Checking Method for Each Part
No.
Part name
Checking procedure
1. Turn OFF the power supply breaker.
1
Electrolytic capacitor
(For boost, smoothing)
2. Discharge all three capacitors completely.
3. Check that safety valve at the bottom of capacitor is not broken.
4. Check that vessel is not swollen or exploded.
5. Check that electrolytic liquid does not blow off.
6. Check that the normal charging characteristics are shown in continuity test by
the tester.
C12 C13 C14
Case that product is good
Pointer swings once, and returns
slowly. When performing test
once again under another
MCC-5009
Soldered
surface
polarity, the pointer should return.
C12, C13, C14 → 760µF/400V
2
Diode block
1. Turn OFF the power supply breaker.
2. Completely discharge the four electrolytic capacitors.
3. Remove the diode block from the PCB (which is soldered in place).
4. Use a multimeter with a pointer to test the continuity, and check that the
diode block has the proper rectification characteristics.
Tester rod
+
Resistance value
in good product
1
+
–
~
~
2
3
~
~
+
1
+ ~ ~ –
3
2
∞
~
~
1 2 3 4
(DBO1)
2
3
–
4
–
4
10 to 20 Ω when the multimeter probe
is reversed
– 80 –
11-10. How to Simply Judge Whether Outdoor Fan Motor is Good or Bad
1. Symptom
• Outdoor fan motor does not rotate.
• Outdoor fan motor stops within several tens seconds though it started rotating.
• Outdoor fan motor rotates or does not rotate according to the position where the fan stopped, etc.
Remote controller check code “02 : Outdoor block, 1A : Outdoor fan drive system error”
2. Cause
The following causes are considered when the outdoor fan motor does not normally rotate.
1) Mechanical lock of the outdoor fan motor
2) Winding failure of the outdoor fan motor
3) Position-detect circuit failure inside of the outdoor fan motor
4) Motor drive circuit failure of the outdoor P.C. board
3. How to simply judge whether outdoor fan motor is good or bad
Turn OFF the breaker.
Disconnect two connectors (CN300) of the
outdoor fan motor from the outdoor P.C. board.
NO
Does the fan rotate without trouble
CN300
when rotating it with hands?
YES
If the resistance value between
1 (Red lead)
2 (White lead)
3 (Black lead)
– 2 (White lead)
– 3 (Black lead)
– 1 (Red lead)
NO
of the connector
(CN300 : Motor winding)
is 17 to 25Ω, it is normal.
YES
Fan motor is normal.
Fan motor error
(Outdoor P.C. board error)
NOTE :
However, GND circuit error inside of the motor may be accepted in some cases when the above check is
performed.
When the fan motor does not become normal even if P.C. board is replaced, replace the outdoor fan motor.
– 81 –
12. HOWTO REPLACE THE MAIN PARTS
WARNING
• Since high voltages pass through the electrical parts, turn off the power without fail before proceeding with
the repairs.
Electric shocks may occur if the power plug is not disconnected.
• After the repairs have been completed (after the front panel and cabinet have been installed), perform a
test run, and check for smoking, unusual sounds and other abnormalities.
If this check is omitted, a fire and/or electric shocks may occur.
Before proceeding with the test run, install the front panel and cabinet.
• Ensure that the following steps are taken when doing repairs on the refrigerating cycle.
1. Do not allow any naked flames in the surrounding area.
If a gas stove or other appliance is being used, extinguish the flames before proceeding.
If the flames are not extinguished, they may ignite any oil mixed with the refrigerant gas.
2. Do not use welding equipment in an airtight room.
Carbon monoxide poisoning may result if the room is not properly ventilated.
3. Do not bring welding equipment near flammable objects.
Flames from the equipment may cause the flammable objects to catch fire.
• If keeping the power on is absolutely unavoidable while doing a job such as inspecting the cir-
cuitry, wear rubber gloves to avoid contact with the live parts.
Electric shocks may be received if the live parts are touched.
High-voltage circuits are contained inside this unit.
Proceed very carefully when conducting checks since directly touching the parts on the control circuit
board may result in electric shocks.
12-1. Indoor Unit
No.
Part name
Procedures
Remarks
Front panel
1) Stop operation of the air conditioner and
turn off its main power supply.
2) Open the air inlet grille, push the arm
toward the outside, and remove the grille.
3) Remove the left and right air filters, and
remove the electric dust collector.
– 82 –
No.
Part name
Procedures
Remarks
Front panel
4) Press “
” part under the front panel
and remove hooks of the front panel from
the installation plate.
Pull here
Installation plate
Front panel
Press here
Press here
Press
5) Remove the front panel fixing screws.
(2 pcs.)
6) Press the electric parts box with the right
thumb while pulling the both sides of the
front panel toward you.
<How to assemble the front panel>
Electric dust
collector
Electric dust
collector
Holder
Holder
Protrusion
Protrusion
1) Press three center positions and two lower center positions of the air outlet, and
then hang the hanging hooks (4 pcs.) at the top side of the front panel to the rear
plate.
2) Insert the electric dust collector and left and right air filters.
Press in the electric dust collector until the protrusions on both sides are completely
inserted into the holders.
If installation is incomplete, the FILTER indicator (orange) may light.
3) Tighten two screws.
• Incomplete hanging or incomplete pressing may cause a dewdrops or generation
of a fluttering sound.
– 83 –
No.
Part name
Procedures
Remarks
High voltage 1) Follow to the procedure in the item
.
‚
generator
2) Remove the drain guide.
3) To remove the air ionizer from the back body,
pull it toward you while pressing down on its left
and right claws.
Connector
Disconnect the two leads (black) connected to
the air ionizer from where they are fitted into
the other components.
Drain guide
(Caution: do not remove the Faston.)
4) Disconnect the connectors of the high-voltage
generator, and disconnect the four leads from
where they are fitted into the other compo-
nents.
Air ionizer
5) Remove the fixing screw which secures the
high voltage generator, and remove the high
voltage generator from the evaporator.
Press the
claw here
Screw
Press the
claw here
Pull here
<How to assemble the high voltage generator>
1) Insert the high voltage generator straight into
the evaporator, and secure it using the fixing
screw.
Check whether the
completely inserted.
2) Pass the leads of the high voltage generator
through the area designated and insert them
into its connectors.
Claw
3) Attach the air ionizer to the back body, and
pass the two leads (black) through the area
designated on the electric parts box assembly.
Claw
Claw
4) Attach the drain guide.
– 84 –
No.
Part name
Procedures
Remarks
Electric parts 1) Follow the procedure up to 4) in
box assembly
above.
ƒ
‚
2) Remove screw of earth lead attached to the
end plate of the evaporator.
3) Remove the lead wire cover, and remove
connector (5P) for the fan motor and connec-
tor (5P) for the louver motor from the electric
parts box assembly.
4) Pull out TC sensor from sensor holder of the
evaporator.
TC sensor
Fan motor
connector
Louver moter
connector
Screw
Fixing screw
5) Disengage the two claws at the top of the
display unit.
(They can be easily disengaged by pressing
the drain pan above the claws and at the
same time pulling the display unit toward you.)
Press the
drain pan
6) Remove the fixing screw that secures the
electric parts box assembly, and remove the
assembly.
Pull the display
unit toward you
<How to assemble the electric parts box>
1) Hook the top part of the electric parts box
assembly onto the claws on the back body,
and secure it using the fixing screw.
Now attach the display unit. Connect the
connectors for the fan motor and louver motor.
2) Secure the grounding wire using the fixing
screw. Insert the TC sensor into the sensor
holder.
* Be absolutely sure to loop the grounding
wire and TC sensor leads once at the
bottom.
– 85 –
No.
Part name
Procedures
Remarks
Horizontal louver 1) Remove shaft of the horizontal
louver from the back body.
„
(First remove the left shaft, and
then remove other shafts while
sliding the horizontal louver
leftward.)
Slide the horizontal
louver leftward
Evaporator
1) Follow to the procedure in the item
.
ƒ
ꢀ
(Heat exchanger)
2) Remove the pipe holder from the rear side of the main unit.
3) Remove two fixing screws at the left side of the end plate of the heat exchanger.
Pipe holder
Disengage the claw
4) Remove the heat exchanger fixing holder
Screw
by removing the two fixing screws used to
secure it.
Heat exchanger
fixing holder
Screw
5) Remove right side of the end plate from
two fixing ribs while sliding slightly the
heat exchanger rightward.
– 86 –
No.
Part name
Procedures
Remarks
Bearing
1) Follow to the procedure in the items
.
†
2) Remove the two fixing screws used to secure
the left edge panel of the heat exchanger, and
remove the two screws used to secure the
bearing base.
Screw
Bearing
base
Screw
3) Raise the left side of the heat exchanger
slightly, and remove the bearing base.
Raise the left side
<Caution at assembling>
• If the bearing is out from the housing, push it
into the specified position and then incorporate
it in the main body.
• After assembling the bearing base, check that it
is fitted into the stepped part of the drain pipe.
Remove in this direction
Bearing base
Bearing
Drain pipe
Drain pipe
Bearing base
– 87 –
No.
Part name
Procedures
Remarks
Fan motor
1) Follow to the procedure in the item
.
ƒ
‡
2) Loosen the set screw of the cross flow fan.
3) Remove two fixing screws of the motor band
(Right), and then remove the motor band
(Right).
4) Pull the fan motor outward.
In assembling work, install the fan motor as
follows.
Set screw
• When assembling the fan motor, the fan
motor must be installed in such a way that
the fan motor leads will be taken out is
positioned at the bottom front.
• After assembling the two hooking claws of
the motor band (right) into the main body,
position the fan motor, insert it, and then
secure the motor band (right) using the two
fixing screws.
Secure using
the fixing screw
Screw
Motor band (Right)
Screw
Secure using
the fixing screw
Fan motor leads
Cross flow fan 1) Follow to the procedure in the item
.
†
ˆ
2) Remove the heat exchanger fixing holder by
removing the two fixing screws used to
secure it.
Raise the
left side
3) Loosen the set screw of the cross flow fan.
4) Lift the left side of the heat exchanger, and
pull out the cross flow fan.
Pull out here
– 88 –
No.
Part name
Cross flow fan <Caution at reassembling>
1) At assembling work of the bearing base,
Procedures
Remarks
ˆ
check that the drain pipe is surely incorpo-
rated in the back body.
(Otherwise, water leak is caused.)
2) To incorporate the fan motor, remove the fan
motor rubber (at shaft core side), incorporate
the motor into the position in the following
figure, and then install the fan motor.
Bearing base
Drain pipe
• Install the cross flow fan so that the right
end of the 1st joint from the right of the
cross flow fan is set keeping 70.5 mm from
wall of rear plate of the main unit.
• Holding the set screw, install the cross flow
fan so that U-groove of the fan motor comes
to the mounting hole of the set screw.
Joint
70.5mm
• Perform positioning of the fan motor as
follows:
• When assembling the fan motor, the fan
motor must be installed in such a way that
the fan motor leads will be taken out is
positioned at the bottom front.
• After assembling the two hooking claws of
the motor band (right) into the main body,
position the fan motor, insert it, and then
secure the motor band (right) using the two
fixing screws.
U groove
– 89 –
12-2. Microcomputer
No.
Part name
Procedure
Remarks
Common procedure 1) Turn the power supply off to stop the
operation of air-conditioner.
Replace terminal block,
microcomputer ass’y and the
P.C. board ass’y.
2) Remove the front panel.
• Remove the 2 fixing screws.
3) Remove the electrical part base.
<P.C. board layout>
R05
L01 C01 CN23 FUSE R04 R01
CN10
DB01
C03
T01
IC01
C20 IC03
J04
– 90 –
12-3. Outdoor Unit
No. Part name
Procedure
NOTE
Remarks
Common
1. Detachment
procedure
Upper cabinet
Water
proof
cover
Wear gloves for this job.
Otherwise, you may injure your
hands on the parts, etc.
1) Stop operation of the air conditioner,
and turn off the main switch of the
breaker for air conditioner.
2) Remove the valve cover.
(ST1TØ4 × 8L 1 pc.)
• After removing screw, remove the
valve cover pulling it downward.
3) Remove wiring cover (ST1TØ4 × 8L
2 pcs.), and then remove connecting
cable.
Valve cover
4) Remove the upper cabinet.
(ST1TØ4 × 8L 5 pcs.)
• After removing screws, remove the
upper cabinet pulling it upward.
2. Attachment
1) Attach the water-proof cover.
Insert the bent part
into the rear panel
of the inverter
NOTE
Bring into contact
against these parts
The water-proof cover must be
attached without fail in order to
prevent rain water, etc. from entering
inside the indoor unit.
2) Attach the upper cabinet.
(ST1TØ4 × 8L 5 pcs.)
3) Perform cabling of connecting cable,
and attach the wiring cover.
Align the stitch line
with the top edge
of the front cabinet
Bend downward, and align
with the inside surface
of the front cabinet
• Place the wiring cover over the
opening used to work on the con-
necting wires of the side cabinet,
and secure it using the two fixing
screws (ST1TØ4 × 8L 2 pcs.).
At this point, the top cushion of the
wiring cover must be on the inside of
the opening.
How to mount the water-proof cover
4) Attach the valve cover.
(ST1TØ4 × 8L 1 pc.)
• Insert the upper part into the square
hole of the side cabinet, set hook
claws of the valve cover to square
holes (at three positions) of the main
unit, and attach it pushing upward.
– 91 –
No.
Part name
Procedure
Remarks
Front cabinet 1. Detachment
‚
1) Perform step 1 in
.
2) Remove the fixing screws (ST1TØ4 × 8L
2 pcs.) used to secure the front cabinet
and inverter cover, the screws (ST1TØ4
× 8L 3 pcs.) used to secure the front
cabinet at the bottom, and the fixing
screws (ST1TØ4 × 8L 2 pcs.) used to
secure the motor base.
• The front cabinet is fitted into the side
cabinet (left) at the front left side so
pull up the top of the front cabinet to
remove it.
Front cabinet
2. Attachment
1) Insert the claw on the front left side into
the side cabinet (left).
2) Hook the bottom part of the front right
side onto the concave section of the
bottom plate. Insert the claw of the side
cabinet (right) into the square hole in the
front cabinet.
Claw
3) Return the screws that were removed
above to their original positions, and
attach them.the main unit, and attach it
pushing upward.
Square
hole
Concave section
– 92 –
No.
Part name
Procedure
1) Perform work of item 1 in
Remarks
Inverter
assembly
.
ƒ
Inverter cover
2) Remove screw (ST1TØ4 × 8L 2 pcs.) of the
upper part of the front cabinet.
P. C. board
(Soldered surface)
• If removing the inverter cover in this
condition, P.C. board can be checked.
• If there is no space above the unit, perform
work of 1 in
.
‚
Be careful to check the inverter because
high-voltage circuit is incorporated in it.
Plug of
soldering
iron
Discharging position
(Discharging period
10 seconds or more)
3) Perform discharging by connecting
,
polarity by discharging resistance (approx.
100Ω40W) or plug of soldering iron to
,
terminals a of the C14 (printed “CAUTION
HIGH VOLTAGE” is attached.) electrolytic
capacitor (760µF) on P.C. board.
Be careful to discharge the capacitor
because the electrolytic capacitor
cannot naturally discharge and voltage
remains according to trouble type in
some cases.
A screw
(STIT-4X8MSZN)
Terminal block
NOTE
This capacitor is one with mass capacity.
Therefore, it is dangerous that a large
spark generates if short-circuiting
between
,
polarity with screwdriver,
etc. for discharging.
4) Remove screw (ST1TØ4 × 8L 2 pcs.) fixing
the main body and the inverter box.
Put the compressor Put each leads
leads through
the hole
through the hole
5) Remove the front cabinet by performing step
1 in , and remove the fixing screws
‚
(ST1TØ4 × 8L) for securing the main body
and inverter box.
The connector is one
with lock, so remove
it while pushing the
part indicated by an
arrow.
6) Remove various lead wires from the holder
at upper part of the inverter box.
7) Pull the inverter box upward.
8) Disconnect connectors of various lead wires.
Requirement
As each connector has a lock mecha-
nism, avoid to remove the connector by
holding the lead wire, but by holding the
connector.
Be sure to remove the connector by
holding the connector, not by pulling
the lead wire.
– 93 –
No.
Part name
Procedure
Remarks
Control board 1. Disconnect the leads and connectors connected to
„
assembly
the other parts from the control board assembly.
1) Leads
CN603
CN601 CN600
• 3 leads (black, white, orange) connected to
terminal block.
CN701
CN300
• Lead connected to compressor :
Disconnect the connector (3P).
CN700 CN602
• Lead connected to reactor :
Disconnect the two connectors (2P).
2) Connectors (×8)
CN300 : Outdoor fan motor (3P: white)*
(See NOTE)
CN300, CN701, CN600 and
CN603 are connectors with
locking mechanisms: as such,
to disconnect them, they must
be pressed in the direction of
the arrow while pulling them
out.
CN701 : 4-way valve (2P: yellow)*
CN600 :TE sensor (2P: white)*
CN700 : PMW (6P: white)
CN603 :TS sensor (3P: white)*
CN601 :TD sensor (3P: white)*
CN602 :TO sensor (2P: white)
NOTE
These connectors have a disconnect prevention
mechanism: as such, the lock on their housing
must be released before they are disconnected.
2. Remove the control board assembly from the P.C.
board base. (Remove the heat sink and control
board assembly while keeping them screwed
together.)
NOTE
P.C. board base
P.C. board
Disengage the four claws of the P.C. board base,
hold the heat sink, and lift to remove it.
3. Remove the two fixing screws used to secure the
heat sink and control board assembly.
4. Mount the new control board assembly.
NOTE
When mounting the new control board assembly,
ensure that the P.C. board is inserted properly
into the P.C. board support groove.
– 94 –
No.
Part name
Procedure
1. Side cabinet (right)
1) Perform step 1 in
Remarks
Side cabinet
ꢀ
and all the steps in
‚
.
ƒ
2) Remove the fixing screw (ST1TØ4 × 8L
5 pcs.) used for securing the side
cabinet to the bottom plate and valve
fixing panel.
2. Side cabinet (left)
1) Perform step 1 in
.
‚
Hook the claw onto
the bottom plate here.
2) Remove the fixing screw (ST1TØ4 × 8L
1 pcs.) used to secure the side cabinet
(left) onto the heat exchanger.
A
3) Remove the fixing screw (ST1TØ4 × 8L
2 pc.) used for securing the side cabinet
to the bottom plate and heat exchanger.
B
C
The back body section is hooked
onto the bottom plate here.
Detail A
Detail B
Detail C
Fan motor
1) Perform work of item 1 of
and
.
‚
†
2) Remove the flange nut fixing the fan motor
and the propeller.
• Flange nut is loosened by turning clock-
wise. (To tighten the flange nut, turn
counterclockwise.)
Propeller fan
Fan motor
3) Remove the propeller fan.
4) Disconnect the connector for fan motor
from the inverter.
5) Remove the fixing screws (2 pc.) holding
by hands so that the fan motor does not
fall.
* Precautions when assembling the fan
motor
Flange nut
Tighten the flange nut using a tightening
torque of 4.9 N•m.
– 95 –
No.
Part name
Procedure
Remarks
Compressor 1) Perform work of item 1 of
and
,
‚ ƒ „
,
,
‡
.
ꢀ
2) Extract refrigerant gas.
3) Remove the partition board.
(ST1TØ4 × 8L 3 pcs.)
4) Remove the sound-insulation material.
5) Remove terminal cover of the compressor,
and disconnect lead wire of the compressor
from the terminal.
6) Remove pipe connected to the compressor
with a burner.
Partition
board
Valve
fixing
plate
Compressor
• Take care to keep the 4-way valve away
from naked flames. (Otherwise, it may
malfunction.)
7) Remove the fixing screw of the bottom plate
and heat exchanger. (ST1TØ4 × 8L 1 pc.)
8) Remove the fixing screw of the bottom plate
and valve fixing plate.
(ST1TØ4 × 8L 1 pc.)
9) Pull upward the refrigeration cycle.
10) Remove BOLT (3 pcs.) fixing the compres-
sor to the bottom plate.
* Precautions when assembling the com-
pressor.
Tighten the compressor bolts using a
tightening torque of 4.9 N•m.
Reactor
1) Perform work of item 1 of , and
‚
.
ƒ
ˆ
2) Remove screws fixing the reactor.
(ST1TØ4 × 8L 4 pcs.)
Reactor
– 96 –
No.
Part name
Electronic
expansion valve
coil
Procedure
Remarks
1. Detachment
1) Perform step 1 in , all the steps in
‰
‚
ƒ
and 1 in
.
ꢀ
2) Remove the coil by pulling it up from the
electronic control valve body.
Coil
anti-turn
lock
2. Attachment
1) When assembling the coil into the valve
body, ensure that the coil anti-turn lock is
installed properly in the pipe.
Coil anti-turn
lock position
<Handling precaution>
Coil inserting
position
When handling the parts, do not pull the leads.
When removing the coil from the valve body, use
your hand to secure the body in order to prevent
the pipe from being bent out of shape.
Fan guard
1. Detachment
Š
1) Perform work of item 1 of
.
‚
2) Remove the front cabinet, and put it down
so that fan guard side directs downward.
Minus screwdriver
Hooking claw
Perform work on a corrugated cardboard,
cloth, etc. to prevent flaw to the product.
3) Remove the hooking claws by pushing minus
screwdriver according to the arrow mark in
the right figure, and remove the fan guard.
2. Attachment
1) Insert claws of the fan guard in the holes
of the front cabinet. Push the hooking
claws (9 positions) by hands and fix the
claws.
All the attaching works have completed.
Check that all the hooking claws are fixed
to the specified positions.
– 97 –
No.
Part name
Procedure
Remarks
TE sensor (outdoor heat exchanging temperature sensor)
11
• Attachment
With the leads pointing downward and the sensor leads
pointing in the direction shown in the figure, install the sensor
onto the straight pipe part of the condenser output pipe.
Detail A
Arrow D
Detail B
Detail C for 13, 16GAVP-E
Detail C for 10GAVP-E
Detail C
TS sensor (Suction pipe temperature sensor)
12
• Attachment
• Shown in the above figure is the
model 13GAVP-E.
With its leads pointing downward, point the sensor in the
direction of the packed valve, and install it onto the straight
pipe part of the suction pipe.
• The sensor mounting positions
in the model 10GAVP-E are all
the same with the sole excep-
tion of the TE sensor. Refer to
the figure shown on the left.
TD sensor (Discharge pipe temperature sensor)
13
14
• Attachment
With its leads pointed downward, install the sensor onto the
vertical straight pipe part of the discharge pipe.
TO sensor (Outside air temperature sensor)
• Attachment
Insert the outdoor air temperature sensor into the holder, and
install the holder onto the heat exchanger.
Arrow D
TO sensor
Detail B
TS sensor
Detail A
TD sensor
CAUTION
During the installation work (and on its completion), take care not to damage the coverings of
the sensor leads on the edges of the metal plates or other parts. It is dangerous for these
coverings to be damaged since damage may cause electric shocks and/or a fire.
CAUTION
After replacing the parts, check whether the positions where the sensors were installed are the
proper positions as instructed. The product will not be controlled properly and trouble will result
if the sensors have not been installed in their proper positions.
– 98 –
No.
Part name
Procedure
Remarks
Replacement of
temperature sensor
for servicing only
1) Cut the sensor 100 mm longer than old
one.
15
Cutting here
100
Thermal
sensor part
Connector
2) Cut the protective tube after pulling out
it (200 mm).
Common service
parts of sensor TO,
TS, TE, TD
3) Move the protective tube toward the
thermal sensor side and tear the tip of
lead wire in two then strip the covering
part.
Cutting here
200
4) Pass the stripped part through the
thermal constringent tube.
Thermal
constringent tube
5) Cut the old sensor 100 mm length on
the connector side, and recycle that
connector.
Cutting here
100
6) Tear the lead wire in two on the con-
nector side and strip the covering part.
7) Twist the leads on the connector and
sensor sides, and solder them.
Soldered part
8) Move the thermal constringent tubes
toward the soldered parts and heat
them with the dryer and constring
them.
Dryer
9) Wind the attached color tape round the
both terminals of the protective tube
when colored protective tube is used.
Winding the color tape
10) Fix the sensor again.
NOTE
1) Store the joint part of the sensor and the connector in the electric parts
box.
2) Never joint them near the thermal sensor part. Otherwise it would cause
insulation inferiority because of dew drops.
3) When replacing the sensor using the colored protective tube, wind the
color tape matching the color of that tube.
These are parts for
servicing sensors.
Parts name
Q'ty
1
Remarks
Length : 3m
1
2
3
4
5
6
Sensor
Please check that
the accessories
shown in the right
table are packed.
Sensor Spring (A)
Sensor Spring (B)
Thermal constringent tube
Color tape
1
For spare
1
For spare
3
Including one spare
9 colors
1
Terminal
3
– 99 –
MCC-5009
– 100 –
13. EXPLODED VIEWS AND PARTS LIST
13-1. Indoor Unit (1)
240
238
234
247
217
209
213
214
216
235
225, 226
212
236
230
223
203
201
221, 222, 224
246
215
211
210
218, 219
207
227
206
205
202
228
245
239
229
204
232
233
∗ The parts in the following parts list are conformed to RoHS.
Therefore be sure to use the following parts for repairing and replacing.
Location
No.
Part
No.
Location
No.
Part
No.
Description
Description
201
202
203
204
205
206
207
209
210
211
212
213
214
215
216
217
218
219
43005633 Panel Ass’y, Front
43005610 Grille, Air Inlet
4301V052 Plate, Fix
43080512 Filter, Air, Right
43080521 Filter, Air, Left
43009675 Louver, Horizontal
43009682 Louver, Vertical
4302C067 Motor, Fan
4302C063 Motor, Louver
4306A024 Cord, Motor, Louver
43039363 Band, Motor, Left
43039321 Base, Bearing
43020346 Fan, Cross Flow
43039314 Band, Motor
223
43049674 Spring, Suction
(B16GKVP-E)
43047673 Pipe, Inlet
224
225
43044803 Evaporator
(B10GKVP-E, B13GKVP-E)
43044804 Evaporator (B16GKVP-E)
43039324 Guide, Drain
226
227
228
229
230
232
233
234
235
236
238
239
240
245
246
247
43049728 Guide, Drain, Left
43019904 Holder, Sensor
43049770 Holder, Evaporator, Right
43062256 Cover, Terminal
43062247 Cover, Lead
43082293 Plate, Installation
4306S577 Remote Controller
43083071 Holder, Remote, Comtroller
43003307 Body Ass’y, Back
43070188 Hose, Drain
43020253 Bearing
4301V028 Holder, Pipe
43049701 Pipe, Shield (B16GKVP-E)
43079268 Cap, Drain
43049698 Pipe, Shield
43080516 Electrical Air Purifying Filter
43080527 Generator Ass’y, HV
4308N732 Owner’s Manual
(B10GKVP-E, B13GKVP-E)
221
222
43047671 Pipe, Outlet
(B10GKVP-E, B13GKVP-E)
43047672 Pipe, Outlet (B16GKVP-E)
– 101 –
Indoor Unit (2)
402
407, 408, 409
403
404
406
410
401
405
∗ The parts in the following parts list are conformed to RoHS.
Therefore be sure to use the following parts for repairing and replacing.
Location
No.
Part
No.
Location
No.
Part
No.
Description
Description
401
402
403
404
405
406
4306A123 Terminal Block, 2P
43062263 Cover, E-Parts
43050425 Sensor, TC (F6)
43050426 Sensor, TA
407
408
409
410
4306S709 P.C. Board Ass’y
(B10GKVP-E)
4306S710 P.C. Board Ass’y
(B13GKVP-E)
4306S711 P.C. Board Ass’y
(B16GKVP-E)
4306S728 P.C. Board Ass’y, WRS-LED
43051346 SW-Micro Ass’y
43067115 Clamp, Cord
– 102 –
13-2. Outdoor Unit
4
44
2
28, 29
30, 31
47
6
27
48
14, 15, 17, 18, 20
21, 23, 24, 25, 26
10
11, 12
43
36
38
8
9
33
3
13, 16, 19, 22
34
35
37
2
32
35
3
40
39
7
41
42
34
7
1
5
45
46
10
– 103 –
∗ The parts in the following parts list are conformed to RoHS.
Therefore be sure to use the following parts for repairing and replacing.
Location
No.
Location
No.
Part
Description
Part
Description
1
2
43005657 Cabinet, Front
43005642 Cabinet, Upper
43005658 Cabinet, Side, Right
43005634 Cabinet, Side, Left
4301V035 Guard, Fan
24
25
26
27
28
43047681 Cap, Valve, Packed, 12.7
(16GAVP-E)
43047674 Cap, Charge, Port
(10GAVP-E, 13GAVP-E)
3
4
43047675 Cap, Charge, Port
(16GAVP-E)
5
6
4301V053 Guard, Fin
44246239 Tube, Capillary, I.D 1.2
(13GAVP-E, 16GAVP-E)
7
43042489 Base Ass’y
8
43119471 Cover, Valve, Packed
43062262 Cover, Wiring Ass’y
43046444 Valve, 4-Way,
STF-0108Z, RoHS
9
10
43041634 Compressor,
DA111A1F-20F1, RoHS
29
30
43046443 Coil, 4-Way valve
37546848 Valve, Pulse, Motor,
CAM-B22YGTF-3
11
12
43043749 Condenser Ass’y
(10GAVP-E)
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
37546849 Coil, PMV, CAM-MD12TF-6
43058277 Reactor
43043751 Condenser Ass’y
(13GAVP-E, 16GAVP-E)
4302C068 Motor, Fan, ICF-140-43-4R
43020329 Fan, Propeller, PJ421
43047669 Nut, Flange
13
14
37546845 Valve, Packed, 6.35
43046442 Valve, Packed, 9.52
(10GAVP-E, 13GAVP-E)
43039392 Base, Motor Ass’y
43004233 Plate, Partition
15
37546846 Valve, Packed, 12.7
(16GAVP-E)
4301V064 Plate, Fix, Valve, Packed
43032441 Nipple, Drain
16
17
43147196 Bonnet, 1/4 IN
43047401 Bonnet, 3/8 IN
(10GAVP-E, 13GAVP-E)
43089160 Cap, Waterproof
4301P703 Mark, TOSHIBA
4301P702 Mark, DAISEIKAI
43049749 Rubber, Cushion
43062176 Sleeve, Flag
18
19
20
43147195 Bonnet, 1/2 IN (16GAVP-E)
43047676 Nut, Flare, 6.35
43047677 Nut, Flare, 9.52
(10GAVP-E, 13GAVP-E)
21
22
23
43047678 Nut, Flare, 12.7 (16GAVP-E)
43047679 Cap, Valve, Packed, 6.35
43063321 Holder, Sensor (TD)
43063322 Holder, Sensor (TS)
43063325 Holder, Sensor (TE)
43063339 Holder, Sensor (TO)
43047680 Cap, Valve, Packed, 9.52
(10GAVP-E, 13GAVP-E)
– 104 –
13-3. P.C. Board Layout
704 Base, P.C. Board
706 Sensor, TD (Ø4)
701 Sensor, TE
702 Sensor, TS
703 Sensor, TO
707 P.C. Board Ass’y
705 Terminal (6P)
∗ The parts in the following parts list are conformed to RoHS.
Therefore be sure to use the following parts for repairing and replacing.
Location
No.
Location
No.
Part
Description
Part
Description
701
702
703
704
43050422 Sensor, TE
43050423 Sensor, TS
43050427 Sensor, TO
43062228 Base, P.C. board
705
706
707
43160566 Terminal Block, 6P
43050430 Sensor, TD
4306S737 P.C. board Ass’y, MCC5009
– 105 –
Appendix
Cord Heater Installation Work
Applicable Models: RAS-10GAVP-E, RAS-13GAVP-E, RAS-16GAVP-E
1. Required parts for installation work (Recommendation)
The above products conform to RoHS (2002/95/EC).Therefore when procuring and using the following recom-
mended parts at local site, it is recommended to confirm each part conforms to RoHS before use.
No. Part name Q’ty
Specifications/Vendor
Remarks
1
2
Cord heater
Thermostat
1
1
Drain line heaters CSC2 (1.5m, 40W/m) by Flexelec com.
(Please go to the following URL.)
http://www.flexelec.com
Procured locally
US-622AXRLQE by ASAHI KEIKI
Operating temperature: on 4 ± 4°C, off 15 ± 3°C
Procured locally
A thermostat holder is incorporated with a thermostat in the package.
(Please go to the following URL.)
http://www.asahikeiki.co.jp/product/product.html
On self-responsibility, you can use a product manufactured by other
company (For example, Texas Instruments) if its characteristics are
equivalent to those of ASAHI KEIKI. However, when the shape of the
thermostat holder is different from that of ASAHI KEIKI, apply some
treatment to No.14 thermostat fixing plate and then fix the holder.
3
4
5
Fuse
1
1
ES3-5000, 250V / 5A by NAGASAWA Electric Co.
(Please go to the following URL.)
http://www.nagasawa-el.co.jp/
On self-responsibility, you can use a product manufactured by other
company if its characteristics are equivalent to those of NAGASAWA
Electric Co.
Procured locally
Procured locally
Procured locally
Fuse holder
GM1H-02 by NAGASAWA Electric Co.
(Please go to the following URL.)
http://www.nagasawa-el.co.jp/
On self-responsibility, you can use a product manufactured by other
company if its characteristics are equivalent to those of NAGASAWA
Electric Co.
P-shape
clamp
13 Use heat-resistance, weatherproof and non-hydrolytic type.
Material: 4-fluorinated ethylene copolymer
Harness diameter: Ø5.9
Use equivalence with the above specifications.
11 pieces are used to fix the cord heater to the outdoor unit base plate.
One piece is used to fix the power cord to the thermostat fixing plate .
One piece is used to fix the power cord to the terminal fixing plate.
6
P-shape
clamp
1
Use heat-resistance, weatherproof and non-hydrolytic type.
Material: 4-fluorinated ethylene copolymer
Procured locally
Harness diameter: Ø9.1
Use equivalence with the above specifications.
One piece is used to fix the cord heater to the outdoor unit base plate.
7
8
Screw
Screw
12 Self-tapping screw type-B Ø4 × 6mm, truss head, stainless
These screws are used to fix the cord heater to the outdoor unit base
plate with P-shape clamp.
Procured locally
Procured locally
4
Self-tapping screw type-B Ø4 × 8mm, truss head, stainless
Two screws are used to fix the thermostat fixing plate to the side cabinet (R).
One screw is used to fix the power cord to the thermostat fixing plate.
One screw is used to fix the power cord to the terminal fixing plate.
9
Screw
2
Self-tapping screw type-B Ø3.5 × 6mm, pan head
These screws are used to fix the thermostat to the thermostat fixing
plate with the thermostat holder.
Procured locally
10 Faston
2
2
#250 They are used for the connecting part to the thermostat.
UL sleeve for #250
Procured locally
Procured locally
11 Sleeve for
Faston
12 Close-end
connector
2
Use the most appropriate connector with the power cord diameter.
Procured locally
Appendix-1
Appendix
No. Part name Q’ty
Specifications/Vendor
2-cores x 0.75mm² or more, H05RN-F
Remarks
13 Power cord
1
1
Procured locally
14 Thermostat
fixing plate
Material: SGCC-Z08, Board thickness: 0.8t
Procured locally
(Drawing attached)
15 PVC tube
1
1
Inside diameter Ø8 x outside diameter Ø11 x 70 mm
Procured locally
Procured locally
16 Shield tube
Inside diameter Ø18 x outside diameter Ø26 x 70 mm
Material: Polyethylene foam
17 Bundling tie
1
Bundling tie for securing the wires
Material: 6/6 nylon
Procured locally
NOTE: The parts on the above table are recommended parts.
2. Required tools for installation work
No.
1
Part name
Plus screwdriver
Wrench
Specifications
Usage
It is used for disassembling and assembling of each cabinet.
2
It is used for disassembling and assembling of compressor fixing nuts.
3
Motor drill
Drill diameter:
Ø3.2 and Ø5.0
It is used to make the additional holes on the base or the side cabinet
(R).
4
5
Faston crimping tool Fixing jig for #250
Close-end connec-
tor crimping tool
6
7
8
9
Cutting plier
Stripper
Cutter knife
Insulation tape
10 Metal-cutting shears
It is used to process the side cabinet (L).
Appendix-2
Appendix
3. Cord heater installation wiring diagram
L
N
Fuse
Thermostat
Cord heater
* Be sure to connect the fuse and the thermostat to LIVE side of the cord heater.
Outdoor unit
Earth leakage circuit breaker
Earth leakage circuit breaker
Power supply for air conditioner
Power supply for cord heater
NOTE:
Separate the cord heater power from the air conditioner power, and connect it to its exclusive breaker.
By doing so, the power consumption can be decreased because the breaker can be turned off if there is no
possibility of freezing of the base plate in cooling operation, etc.
When the cord heater power is connected to the inverter P.C. board assembly or others without connected to the
exclusive breaker, the control P.C. board of the inverter assembly may cause a failure.
When the cord heater has been mounted on a base plate, do not mount the water-proof cap and drain nipple which
are provided with the outdoor unit on the base plate.
Appendix-3
Appendix
4. Cord heater installation work procedure
No.
Photo / Explanatory diagram
Procedure
Remove each cabinet, inverter assembly, motor base assembly, and partition board assembly.
* Do not damage the electric parts such as cables, connectors, etc. while this work.
1
Remove the upper cabinet and the valve cover.
Upper cabinet
Related parts / Screws list
Used screw
Part name
Screw type
Quantity
1-1
Upper cabinet
Valve cover
Ø4 × 8
5
1
Ø4 × 1
Valve cover
Remove the front cabinet, the wiring cover and the
water-proof cover.
Water-proof
cover
Related parts / Screws list
Wiring cover
Used screw
Part name
1-2
Screw type
Quantity
Front cabinet
Wiring cover
Ø4 × 8
7
2
Ø4 × 8
Front cabinet
Remove the side cabinet (R/L) and the inverter
assembly.
Side cabinet (L)
Inverter assembly
Side cabinet (R)
Related parts / Screws list
Used screw
Part name
Screw type
Quantity
1-3
Side cabinet (R)
Side cabinet (L)
Inverter assembly
Ø4 × 8
7
3
1
Ø4 × 8
Ø4 × 8
Remove the inverter assembly.
No. Part name Connector No.
Connector color
White
1
2
3
4
TE sensor
TD sensor
TO sensor
TS sensor
CN600
CN601
CN602
CN603
White
White
White
4-way valve
coil
5
CN701
Yellow
1-4
6
7
PMV coil
CN700
CN300
White
White
Fan motor
Compressor
lead
8
9
(Intermediate connector)
(Intermediate connector)
White
White
Reactor
(2 pieces.)
Appendix-4
Appendix
No.
Photo / Explanatory diagram
Procedure
Remove the motor base assembly, partition plate assembly
and the sound insulation board.
Motor base
assembly
Related parts / Screws list
Partition plate
assembly
Used screw
Part name
Screw type
Quantity
1-5
Motor base assembly
Ø4 × 8
2
(Including motor and fan)
Partition plate assembly
(Including reactor)
Ø4 × 8
3
Sound
insulation board
Remove the fixing screws of the heat exchanger and the
valve fixing plate. Remove the compressor fixing bolt.
Valve fixing plate
Heat exchanger
Related parts / Screws list
Used screw
Part name
Screw type
Ø4 × 8
Ø4 × 8
bolt
Quantity
Heat exchanger
Valve fixing plate
Compressor
1
1
3
1-6
Compressor
As shown in the left figure, remove the set of refrigeration cycle
assembly from the outdoor unit base plate.
* In this time, work attentively so that the cycle pipes are not
damaged by dent or deformation. Apply protective
measures to pipes if necessary.
1-7
Appendix-5
Appendix
No.
Photo / Explanatory diagram
Cord heater installation work
Procedure
Drill a hole on the outdoor unit base plate, and fix the cord heater to the outdoor unit base plate using P-shape
clamp.
2
Connect the cord heater cables.
Using a motor drill, etc., drill Ø3.2 holes on the outdoor unit base plate. (12 positions) See Appendix-10 for the
additional hole positions.
2-1
These holes are used to fix the cord heater to the outdoor unit base plate with P-shape clamp.
Insert the PVC tube into the cord heater.
This tube is designed to protect the cord heater from
the fixing screws used to secure the anchoring feet.
As shown in the left figure, install the cord heater
(1.5m) to the outdoor unit base plate by using P-
shape clamp and screws (Self-tapping screw type-B
Ø4 × 6mm, stainless).
Pay attention to the direction of P-shape clamp so
that it is set to the same direction in the left figure.
The PVC tube must be inserted
into the cord heater between
the fixing screws in order to
protect the cord heater from
these screws.
* If the drain port is frozen due to installation
status, etc., draw around the cord heater so that
the end part of the heater is inserted into the
drain port. In this case, add some fixing
positions to fix the cord heater surely.
2-2
Under no circumstances must
the tube be allowed to ride over
the tip of the fixing screws.
PVC tube
Ø9.1 P-shape clamp
* The end part from the marked part of the cord
heater heats up. When there is the heating part
near the electric parts box, a fire may generate.
Be sure to set the heating part on the outdoor
unit base plate at the fan room side or near it.
(within 20cm from the outdoor unit base plate)
* Be careful that the cord heater does not hit the
fan.
Fix the cord heater without any loosening or sag.
Enlarged
marked part
Heating part
Drill a hole on the side cabinet (R) for fixing the
thermostat fixing plate.
Added hole 2-φ5
Ø5 hole at two positions
5
When drilling a hole on the side cabinet (R), be
sure not to damage the cabinet.
46
7
2-3
Side cabinet (R)
Appendix-6
Appendix
No.
Photo / Explanatory diagram
Procedure
Rework the side cabinet (L) to remove part of it.
Side cabinet (L)
The area to be removed is indicated by the shaded
lines in the left figure.
After removing part of the side cabinet (L), deburr the
edges of the side cabinet (L).
2-4
Delete
Perform end process and bundling of each cable.
Using fixing screws (Self-tapping screw type-B Ø3.5
× 6mm), fix the thermostat to the thermostat fixing
plate.
Close-end connector
insulation tape
Thermostat
Power cord
Perform end process for various lead cables and
connect them according to the wiring diagram.
Attach #250 Faston and UL-approved sleeves each
to the end of lead cables which are connected to the
thermostat.
2-5
Cord heater
* Transparent
Using insulation tape, apply protective measures to
the connected parts by the close-end connectors.
Thermostat
fixing plate
L side
Using P-shape clamp and the screws (Self-tapping
screw type-B Ø4 × 8mm), fix the power cord to the
thermostat fixing plate.
P-shape clamp
Fuse
Fuse holder
When the power cord size does not match with P-
shape clamp, procure the most appropriate one at
the local site.
Appendix-7
Appendix
No.
Photo / Explanatory diagram
Procedure
Assembly
Return a set of the refrigeration cycle assembly into the outdoor unit base plate and reassemble sound insulation
board, partition plate assembly, fan motor assembly, and side cabinet (R/L) as original. Fix the thermostat fixing
plate to the side cabinet (R), built in the inverter assembly, and then connect various cables. After then,
incorporate front cabinet, upper cabinet, wiring cover, and valve cover as before.
3
Return a set of the refrigeration cycle assembly into the
outdoor unit base plate, and assemble sound insulation
board, partition plate assembly, fan motor assembly, and
side cabinet (R/L) as original.
3-1
Using screws (Self-tapping screw type-B Ø4 × 8mm,
stainless), fix the thermostat fixing plate to the side
cabinet (R).
Thermostat fixing plate
Side cabinet (R)
3-2
After incorporating the inverter assembly as before,
furthermore perform cable process for cord heater and
power cord.
Do not make cord heater loose.
Do not put the heating part near the electric parts box.
For the cord heater, perform cable process so that there
is no looseness or sag at the fan side.
Perform cable process for collected
cord heater and fan motor lead cables.
Perform cable process for the cord heater together with
the fan motor lead cable, and collect the remained part
of cables at cable process part of the inverter.
Secure the power cord for the cord heater to the
terminal block mounting plate using the P-shape clamp,
and pull it out from the wiring area of the side cabinet
(R).
P-shape
clamp
3-3
* Check that there is the marked part of the cord heater
on the outdoor unit base plate or near it.
When there is the heating part near the electric parts
box, a fire may generate.
Power cord for
cord heater
Since the lead wires connected to the cord heater and
thermostat may come into contact with the edges of the
sheet metal or tips of the screws, wrap the shield tubes
around the leads to protect them and use the bundling
ties to secure them.
To keep the lead wires from coming into contact with the
edges of the sheet metal or tips of the screws, wrap the
shield tubes around the leads to protect them and use
the bundling ties to secure them.
3-4
4
Incorporate front cabinet, upper cabinet, wiring cover, water-proof cover and valve cover as before.
In installation work, connect power cord for the cord heater to another breaker separated from one for power cord
of the air conditioner.
Appendix-8
Appendix
5. Drawing of thermostat fixing plate
37
2-Ø3.4 burring hole
(Upward)
18
11
11
11
18
3-Ø3.4 burring hole
(Downward)
45
Material: SGCC-Z08,Thickness: 0.8t
Appendix-9
Appendix
6. Diagram showing positions φ3.2 mm holes to be additionally drilled in base plate
Appendix-10
This product is compliant with Directive 2002/95/EC, and cannot be disposed as unsorted municipal waste.
TOSHIBA CARRIER CORPORATION
2 CHOME 12-32, KONAN, MINATOKU, TOKYO, 108-0075, JAPAN
Copyright © 1999 to 2005 TOSHIBA CARRIER CORPORATION, ALL Rights Reserved.
|
Metrologic Instruments Focuse Is1650 User Manual
Panasonic Kx Fp121 User Manual
Samsung Avxcs User Manual
Samsung Ch24zax User Manual
Sanyo N 250aaa User Manual
Sanyo Ur 121 User Manual
Schumacher Automatic Ps 1562a User Manual
Trion Air Boss Dc 128 User Manual
Vtech Baby Accessories 91 002537 005 User Manual
Xantrex Technology Dr1512e User Manual