Sanyo Chdx14053 User Manual

Print Form  
ECO-i Submittal Data  
CHDX14053  
Heat Pump: 12 tons VRF Outdoor Unit  
Job Name:  
Location:  
Approval:  
Date:  
Engineer:  
Construction:  
Unit #:  
Drawing #:  
Submitted to:  
Submitted by:  
Reference:  
Compressor Warranty: 6 Years  
Parts Warranty: 1 Year  
Coil Coated to Protect Against Corrosion  
Salt Protection also avilable  
Capacities  
Fan  
Cooling: Btu/h  
Power Input: KW  
Heating: Btu/h  
Power Input: KW  
153,600  
13.3  
170,600  
13.2  
Quantity/Type:  
Fan Motor Output (KW):  
1 Propeller Fan  
0.7  
Power Supply  
V/PH/Hz.  
208-230 / 3 / 60  
Cooling Mode Nominal Conditions  
Indoor: °F DB/°F WB  
Outdoor: °F DB  
Minimum circuit Amps (MCA): Amps  
Max. Overcurrent Protection (MOCP):  
57  
70  
80/67  
95  
25  
Pipe Length (feet):  
Weight (lbs):  
760  
Level Difference (feet):  
0
Refrigerant:  
410A  
Heating Mode Nominal Conditions  
Indoor: °F DB  
Outdoor: °F DB/ °F WB  
Pipe Length (feet):  
70  
47/43  
25  
Coil  
Coil Face Area (sq. ft.):  
Number of Rows:  
22.5  
4
Level Difference (feet):  
0
Protection Devices  
High Pressure Switch:  
Overcurrent (CT Method):  
Crankcase Heaters (W):  
Operating Range  
Cooling: °F DB:  
Heating: °F DB:  
Yes  
Yes  
25 + 32 x 2  
14 to 109  
-4 to 59  
Compressor  
External Finish:  
Electrostatic Powder Coating  
Quantity/Type:  
1 Inverter driven rotary & 2 fxed speed scroll  
Capacity Control Range:  
10-100%  

Panasonic Cu E28ekr User Manual
Philips Sc479 Dect User Manual
Samsung Avmdh C User Manual
Samsung Multifunction Printer Scx5639fr User Manual 3
Sears 20071224 User Manual
Sharp Af S85px User Manual
Sharp Fo Dc535 User Manual
Sharp Mx B402 User Manual
Turtle Beach Sony V331 User Manual
Vornado Air Cleaner Pco500 User Manual