Mitsubishi Electronics Pac Yg60mca User Manual

Mitsubishi Electric Air Conditioner Network System  
PI controller  
PAC-YG60MCA  
Installation/Instruction Manual  
Contents  
Page  
Safety Precautions.............................................. 1  
Device Capabilities ............................................. 1  
Confirmation of Parts .......................................... 2  
Specifications...................................................... 2  
1.  
2.  
3.  
4.  
4-1.  
4-2.  
Product Specifications ....................... 2  
External View..................................... 2  
5.  
6.  
Example of System Configuration....................... 3  
Installation Method.............................................. 4  
6-1.  
6-2.  
Parts to be Procured Locally.............. 4  
Installation Procedure ........................ 5  
7.  
Wiring Method..................................................... 6  
7-1.  
7-2.  
Names of Parts .................................. 6  
Connecting the Power Line and  
M-NET Transmission Line ................. 7  
Connecting the Signal Lines .............. 8  
(1) Pulse input (non-voltage a contact) ... 8  
7-3.  
8.  
9.  
Initial Setting Procedure...................................... 9  
Switch List......................................................... 10  
10. Display Content................................................. 11  
10-1.  
10-2.  
Display Content List......................... 11  
Communication Error Status  
Display ............................................. 11  
11. Test Run ........................................................... 12  
12. Precautions for Expansion ................................ 12  
Before using the PI controller, please read this installation/instruction manual carefully to ensure proper operation.  
Keep this installation/instruction manual for future reference.  
3 Confirmation of Parts  
• Confirm that the box contains the following parts.  
Number  
Part Name  
Quantity  
1
PI controller  
1
1
2
Installation/instruction manual (this document)  
* In addition to the parts mentioned above, other parts need to be procured locally in order to operate this device. Furthermore, other Mitsubishi optional  
parts may be required depending on how the device is to be used.  
For details, refer to "6 Installation Method".  
4 Specifications  
4-1. Product Specifications  
Item  
Rating and Specification  
17 to 30 VDC (*1)  
Power Supply 24 VDC±10%: 5 W  
M-NET communication  
Screw terminal block (M3)  
Screw terminal block (M3)  
Number of contacts: 4  
Pulse signal: a contact  
Pulse width: 100 ms to 300 ms  
(Idle period until next pulse: 100 ms or more)  
Interface  
100 ms or more  
Non-voltage a contact input  
Screwless terminal block  
100 ms ~ 300 ms  
Rated voltage: 24 VDC  
Rated current: 1 mA or less (*2)  
Operating temperature range  
Storage temperature range  
0 to 40°C [32°F to 104°F]  
-20 to 60°C [-4°F to 140°F]  
Temperature  
Humidity  
Environment  
Conditions  
30 to 90%RH (no condensation)  
7
3
25  
Dimensions  
Weight  
200 (W) × 120 (H) × 45 (D) mm / 7 /8 (W) × 4 /4 (H) × 1 /32 (D) in  
0.6 kg / 1 3/8 lb  
Current Time  
Backup during  
Power Failure  
If the power is cut, the internal capacitor will normally keep counting the current time for approximately one week.  
(The internal capacitor takes approximately a day to charge. Replacement of a battery is not necessary.)  
Installation  
Environment  
Inside a control panel (indoors)  
* Use this product in a hotel, a business office environment or similar environment.  
*1: Supply electric power from a power unit for the transmission line or an outdoor unit. Furthermore, the power consumption factor of the M-NET circuitry  
of this device is "1/4" (equivalent to one ME Remote Controller).  
*2: Supply electric power from the main unit to the contacts of the meters.  
4-2. External View  
7
(
)
200  
7
/
8
25  
/32  
(
)
45  
1
29  
)
/32  
(
150  
5
1
27  
/32  
(
)
(
)
52  
2
/16  
46.5  
1
4.5  
/16  
3
(
)
/8  
9
3
(
)
This device complies with Part15 of the FCC Rules.Operation is  
subject to the following two conditions: (1)this device may not cause  
harmful interference, and (2)this device must accept any interference  
received, including interference that may cause undesired operation.  
[
24 VDC Power Supply]  
5
3
/
(
)
(
1
)
83.5  
3
/16  
27  
32  
1
)
/32  
(
26  
1
Unit: mm (in)  
2
5 Example of System Configuration  
<Restrictions>  
Maximum of 5 units (total of 20 channels) per G(B)-50A  
However, the number of units that can be connected to a  
G(B)-50A is up to 50 including this device, an indoor unit,  
Lossnay unit, etc.  
* For the number of units that can be connected when  
controlling this device with TG-2000A, refer to the  
instruction manual for TG-2000A.  
Centralized control line  
Power supply unit  
PAC-SC50KUA  
Indoor control line  
M-NET  
M-NET  
TB3  
G-50A or GB-50A  
TB7  
LAN  
24 VDC  
PI controller  
power supply  
City Multi  
Uninterruptible  
power supply  
(UPS)  
24 VDC  
power supply  
Watt-hour meter with  
pulse transmitter, etc.  
PI controller  
G(B)-50A Web  
or TG-2000A  
Up to 4 contacts  
Uninterruptible  
power supply  
(UPS)  
Watt-hour meter with  
pulse transmitter, etc.  
Up to 4 contacts  
* This figure omits the power supply line and only shows the transmission line.  
Note:  
• For the shield ground of the M-NET centralized control line for central control, use single-point grounding at the power unit for  
the transmission line.  
However, when supplying electric power to the M-NET centralized control line from the R410A series outdoor unit without using  
a power supply unit for the transmission line, use single-point grounding at the TB7 of that outdoor unit.  
Furthermore, when connecting this device to the M-NET indoor control line, use grounding at the TB3 for each outdoor unit  
system.  
• Connecting an Uninterruptible power supply (UPS) to the 24 VDC power supply is recommended in order to prevent the loss of  
pulse data in the event of a power failure.  
If a UPS cannot be connected, try to make the AC power supply to the 24 VDC power supply as much same as the power supply  
line to the meters.  
• This device does not support level meters. To use a level meter, incorporate a Converter circuit externally and convert to pulse  
input.  
• If this device is connected to an M-NET indoor control line and the outdoor unit is down because, for example, the power supply  
is interrupted for servicing or there is a failure, the PI controller cannot be controlled from the system controller.  
3
6 Installation Method  
6-1. Parts to be Procured Locally  
Prepare the following parts to install this device.  
Required Part  
Specification  
Unit fixing screws  
M4 screw × 4  
Power source: 24 VDC 0.2 A (Minimum loading), SELV circuit, power line with grounding terminal  
Ripple noise: Lower than 200 mVp-p  
Compatible specification  
Power supply for this  
unit  
Authorized or CE marked products  
Subject to regulations: - IEC60950 (or EN60950)  
- CISPR22/24 (or EN55022/24)  
- IEC61000-3-2/3-3 (or EN61000-3-2/3-3)  
Use a sheathed vinyl cord or cable.  
At least 0.75 mm² (AWG18)  
Power line  
Type of the cable: Sheathed vinyl cords or cable which comply with the following specifications or equivalent.  
• CPEV Φ1.2 mm to Φ1.6 mm • CVVS 1.25 mm² to 2 mm² (AWG16 to 14)  
* CPEV: PE insulated PVC jacketed shielded communication cable  
M-NET transmission  
line  
* CVVS: PVC insulated PVC jacketed shielded control cable  
PE: Polyethylene PVC: Polyvinyl choloride  
Power needs to be supplied to the M-NET circuitry of this device. Use an outdoor unit or a separately purchased  
power supply unit for the transmission line.  
Shows the size of the electric wire (copper wire) that is adapted to the terminal block of this device.  
Electric wire size ········· (1) Solid wire: Φ0.65 mm (AWG21) - Φ1.2 mm (AWG16)  
(2) Stranded wire: 0.75 mm² (AWG18) - 1.25 mm² (AWG16)  
Signal lines  
Single strand: At least Φ0.18 mm  
[Parts to be Purchased Separately]  
Name  
Model  
Application  
Remark  
This is not required when power is to be  
supplied from an outdoor unit.  
Power supply unit  
PAC-SC50KUA Power supply to the M-NET transmission line  
[Recommended Pulse Specifications]  
Prepare a measuring instrument that measures the type of pulse signals indicated in table below.  
Type  
Specifications  
Output pulse relay  
method  
Semiconductor relay method  
100 ~ 300 ms (100 ms and above)  
Choose an instrument that outputs non-voltage a-contact  
point pulse per each pulse output.  
ON  
Output pulse width  
100 ~ 300 ms  
Watt-hour meter: 0.1 kWh/pulse, 1 kWh/pulse recommended  
3
Water meter: m /pulse  
3
Pulse unit  
Gas meter: m /pulse  
Calorimeter: MJ/pulse  
* Except for the watt-hour meter, select instruments that take measurements in the appropriate pulse unit.  
4
6-2. Installation Procedure  
The PI controller PAC-YG60MCA does not have a waterproof structure.  
Be sure to install the PI controller inside a control panel that is located indoors.  
Prepare a control panel capable of storing this device such as the one shown in the figure. (Install the device in a control  
3
panel strong enough to withstand a weight of 0.6 kg [1 /8 lb].)  
This device can be installed flat or vertically. Clear the space shown below when installing.  
100  
(315  
/
)
16  
100  
100  
)
16  
(315  
/
(315/  
)
16  
Size of the device: 200 (W) × 120 (H) × 45 (D) mm/  
7
3
25  
7 /8 (W) × 4 /4 (H) × 1 /32 (D) in  
100  
Unit: mm (in)  
(315  
/
)
16  
Note: The space shown above does not include space for peripherals. Additionally, the amount of space necessary varies according to  
the functions that are used and the wiring method. Secure enough space appropriate for the type of installation.  
(1) Fix the top of this unit to the control panel at two points by loosely tightening the screws (M4) that were procured locally.  
Fix the bottom in place with two screws and then tighten all four of the screws.  
Screw pitch  
29  
)
/32  
(
150  
5
11  
)
/32  
(
110  
4
Unit: mm (in)  
(2) To remove the cover, as shown in the figure, remove the two screws for fixing the cover in place and then remove the cover by  
unhooking the upper hook section from the lower case. To attach the cover, hook the upper hook section on the lower case and then  
fix the cover in place with the two screws that were removed.  
Hooks  
Screws for fixing  
the cover  
Note: Two hooks are located on the upper section of the cover.  
5
(3) Refer to "7 Wiring Method" and connect the wires for the power line, M-NET transmission line, and input/output signal lines.  
M-NET  
Pulse Input  
Power line  
Caution: Perform wiring so that the terminal  
block is not strained.  
If strained, use a wire guide or  
junction terminal to alleviate the  
stress on the terminal block.  
PI controller  
Junction  
terminal  
block  
+V  
-V  
FG  
L
N
24 VDC  
Power  
source  
PAC-SC50KUA  
M-NET  
* The wiring in the diagram has been simplified.  
Diagram Image (Installed within a Control Panel)  
7 Wiring Method  
Note: Connecting an Uninterruptible power supply (UPS) to the 24 VDC power supply is recommended in order to prevent the loss of  
pulse data in the event of a power failure.  
7-1. Names of Parts  
LED17  
M-NET  
Power on  
Function Settings  
10s  
1s  
M-NET  
Address  
SW02  
SW01  
SW06 SW07  
SW08  
SW09  
Status LEDs  
SW03  
11/ 12/ 13/ 14/ 15/ 16 (CPU power on)  
LED  
M-NET  
A /  
B
/ S  
Pulse Input  
24 VDC Power Supply  
V+ / V- / FG  
CN17  
CN16  
CN10  
/ 11  
/ 19  
/ 20  
6
7-2. Connecting the Power Line and M-NET Transmission Line  
Tightening torque for terminal screws: 1 N·m  
Connect the device to a power supply unit (PAC-SC50KUA)  
for the transmission line or an outdoor unit (either a centralized  
control line or indoor control line can be connected).  
* Only the M-NET circuitry of this device receives the power from the  
M-NET transmission line. The power consumption factor is "1/4"  
(equivalent to one ME Remote Controller).  
CN17  
A/B/S  
CN16  
V+/V-/FG  
PI controller  
M-NET  
Circuit Onsite  
(example)  
R
Fuse  
Arrester  
Varistor  
24 VDC  
Power  
source  
AC Power Line  
Noise  
Filter  
Varistor  
U
Uninterruptible  
power supply  
(UPS)  
U
S
* Functional  
ground  
FG  
Figure 7-1 Example of Connecting the Power Line and M-NET Transmission Line  
Caution:  
• Use a power line and M-NET transmission line that satisfy the specifications described in "6-1 Parts to Procured Locally".  
• Attach a circuit comprising the following components to the supply primary side of the 24 VDC power supply.  
(1) Varistor, (2) Arrester, (3) Noise filter, (4) Fuse  
• It is important to pay attention to the polarity when connecting to the 24 VDC power supply terminal block.  
Connecting the positive and negative in the reverse order will cause a failure.  
• Fix the power line and M-NET transmission line in place on the outside to ensure that the terminal block is not affected by any  
external force.  
Not securely connecting and fixing the wires in place may cause heat generation and fire.  
• Make sure that the copper wiring is not short-circuiting the plates (cover, lower case) or neighboring wires.  
Cover the shielded line of the M-NET transmission line with materials such as vinyl tape and prevent short-circuiting with the  
plates.  
Note:  
• Connecting an Uninterruptible power supply (UPS) is recommended in order to prevent the loss of pulse data in the event of a  
power failure. If a UPS cannot be connected, try to make the AC power supply to the 24 VDC power supply as much same as  
the power supply line to the meters.  
• If this device is connected to an M-NET indoor control line and the outdoor unit is down because, for example, the power supply  
is interrupted for servicing or there is a failure, the PI controller cannot be set and monitored from the system controller.  
7
7-3. Connecting the Signal Lines  
• Separately procure items such as terminal blocks and cables locally.  
• The maximum wire length is 100 m. However, since the use of long wires makes the device susceptible to  
noise, using wires shorter than 10 m is recommended.  
(1) Pulse input (non-voltage a contact)  
* To use these, various settings need to be configured. Refer to "8 Initial Setting Procedure".  
Note:  
• The pulse weight can be added to each of the inputs of  
channels 1 to 4.  
For details, refer to "9 Switch List".  
• This device does not support level meters.  
24 VDC  
To use a level meter, incorporate a Converter circuit  
externally and convert to pulse input.  
Caution:  
• The polarity of the input terminals is important, so be sure to  
match the polarity when using contacts that have polarity.  
• Select a contact with a minimum applicable load of 1 mA or  
less.  
• Supply 24 VDC 1 mA from the positive terminal to the  
contacts of the meters.  
CN 10  
Ch1  
/
11  
/
19  
/
20  
Ch2  
Ch3  
Ch4  
+
+
+
+
• The pulse unit of the watt-hour meter being used should be  
1 kWh/pulse or less. Note that the apportioning error will  
increase if a watt-hour meter with large pulse unit is used.  
• Strip 12±1 mm (15/32 ±1/32 in) of the wire coating and insert  
firmly into the terminal.  
Line  
Onsite  
Example: Watthour  
meter  
Water  
meter  
Gas  
meter  
Calorimeter  
• Make sure that the copper wiring is not short-circuiting the  
plates (cover, lower case) or neighboring wires.  
• Perform wiring so that the terminal block is not strained.  
If strained, use a wire guide or junction terminal to alleviate  
the stress on the terminal block.  
8
8 Initial Setting Procedure  
After completing the procedures described in "6 Installation Method" and "7 Wiring Method", set the initial settings in  
accordance with the procedure described below.  
(1) M-NET address settings  
Note:  
• An address from 01 to 50 can be set.  
10s  
1s  
• Set an address that is not the same as that of  
another unit.  
The address is set to "01" at factory shipment.  
SW06  
SW07  
In the case of address "41"  
(2) Use the dip switches to select functions.  
Select the function required for each input channel to be used.  
The switch assignment for each channel is shown below. Configure each of the settings while referring to "9 Switch List".  
Operation Switch  
Setting  
Ch1  
Ch2  
Ch3  
Ch4  
Whether to use Input contact  
Pulse weight value  
SW01-1  
SW02-1, 2  
SW01-2  
SW02-3, 4  
SW01-3  
SW02-5, 6  
SW01-4  
SW02-7, 8  
Note: Be sure to configure the pulse weight settings. If these setting are not configured, the charge function and peak cut control will  
not work normally because correct measurement of usage amounts will not be made.  
(3) Turn on the power of this device.  
Verify that the LED16 (CPU power on) and LED17 (M-NET power on) are lit.  
(4) Set the time.  
Set the current time from a system controller (G(B)-50A or TG-2000A) or a Maintenance Tool.  
(5) Set the meter settings so that this device is a target for control from a system controller (G(B)-50A or TG-2000A).  
Configure the settings of the system controller (G(B)-50A or TG-2000A). For details, refer to the instruction manual for the G(B)-50A  
or TG-2000A.  
Setting  
Setting with G(B)-50A  
Setting with TG-2000A  
Set the pulse weight value setting switch (SW02) to the "SC setting", and set the setting with  
G(B)-50A or TG-2000A.  
Pulse weight value  
3
Unit for calculation  
Period of time for calculation  
Time for calculation  
Set the volume unit (kWh, m , MJ) with G(B)-50A or TG-2000A.  
Set the period of time for calculation of the rates.  
Set the time for daily calculation.  
Date for calculation  
Set the date for monthly calculation.  
*1: The pulse unit of the watt-hour meter being used should be 1 kWh/pulse or less. Note that the apportioning error will increase if a watt-hour meter with  
large pulse unit is used.  
*2: Values measured with this device cannot be used for the transaction and certification purposes mentioned in the Measurement Law.  
Note:  
• Configure the settings of the TG-2000A connection system from TG-2000A.  
If these setting are not configured, the charge function and peak cut control will not work normally because correct measurement  
of usage amounts will not be made.  
• Be sure to set the pulse weight settings from this device or a system controller (G(B)-50A or TG-2000A).  
If these setting are not configured, the charge function and peak cut control will not work normally because correct measurement  
of usage amounts will not be made.  
9
9 Switch List  
Supported  
SW  
Function  
OFF  
ON  
Remark  
Channel  
Channel 1  
Channel 2  
Channel 3  
Channel 4  
SW01  
1
2
3
4
5
6
7
8
Use of input contact  
Use of input contact  
Use of input contact  
Use of input contact  
No  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
Set whether to use the Channel 1 input.  
Set whether to use the Channel 2 input.  
Set whether to use the Channel 3 input.  
Set whether to use the Channel 4 input.  
Set to OFF  
Unused  
Unused  
Unused  
Unused  
Set to OFF  
Set to OFF  
Set to OFF  
SW02  
Pulse weight value setting:  
SW02-1,  
OFF  
OFF  
ON  
SW02-2  
OFF  
ON  
OFF  
ON  
1
2
3
4
5
6
7
8
SC setting (*1):  
× 0.1:  
× 1:  
Channel 1  
Set 1 pulse of the meter connected to channel 1.  
Set 1 pulse of the meter connected to channel 2.  
Set 1 pulse of the meter connected to channel 3.  
Set 1 pulse of the meter connected to channel 4.  
× 10:  
ON  
Pulse weight value setting:  
SW02-3,  
OFF  
OFF  
ON  
SW02-4  
OFF  
ON  
OFF  
ON  
SC setting (*1):  
× 0.1:  
× 1:  
Channel 2  
Channel 3  
Channel 4  
× 10:  
ON  
Pulse weight value setting:  
SW02-5,  
OFF  
OFF  
ON  
SW02-6  
OFF  
ON  
OFF  
ON  
SC setting (*1):  
× 0.1:  
× 1:  
× 10:  
ON  
Pulse weight value setting:  
SW02-7,  
OFF  
OFF  
ON  
SW02-8  
OFF  
ON  
OFF  
ON  
SC setting (*1):  
× 0.1:  
× 1:  
× 10:  
ON  
SW03  
1
2
3
4
5
6
7
8
Unused  
Set to OFF  
Set to OFF  
Set to OFF  
Set to OFF  
Set to OFF  
Set to OFF  
Set to OFF  
Set to OFF  
Unused  
Unused  
Unused  
Unused  
Unused  
Unused  
Unused  
An address from 01 to 50 can be set.  
Set an address that is not the same as that of  
another unit.  
SW06  
(Address 10s) 0 to 9 (decimal)  
(Address 1s) 0 to 9 (decimal)  
M-NET address  
SW07  
SW08  
Only enabled during communication error status  
display.  
* The communication error status display is  
masked for 10 seconds and the contact input  
status is displayed.  
Communication error status display (error code  
display)  
Temporary mask setting  
Change the switch to ON once  
and then return it to OFF.  
1
2
3
4
5
6
1
2
Unused  
Unused  
Unused  
Unused  
Unused  
Unused  
Unused  
Set to OFF  
Set to OFF  
Set to OFF  
Set to OFF  
Set to OFF  
Set to OFF  
Set to OFF  
SW09  
Set the dip switches for function selection according to the system to be used.  
At the time of shipment, all dip switches are set to OFF and the M-NET address is set to 01.  
*1: When using a system controller (G(B)-50A or TG-2000A), select the "SC setting" and set the pulse weight value settings from a system controller. If set  
to another setting, this dip switch setting is prioritized even when set from a system controller.  
*2: The pulse unit of the watt-hour meter being used should be 1 kWh/pulse or less. Note that the apportioning error will increase if a watt-hour meter with  
large pulse unit is used.  
10  
10 Display Content  
The LEDs of this device indicate the pulse input status and error status of this device.  
10-1.Display Content List  
Display Item  
Display LED  
Content  
Note  
: On,  
: Off,  
: Flashing  
Power supply status  
(1) Power supply to LED16  
CPU (CPU power on)  
: Lights when the CPU is energized.  
: Flashes during M-NET communication.  
: Lights when the M-NET is energized.  
(2) Power supply to LED17  
M-NET circuit  
(M-NET power on)  
Input status Channels  
1 to 4  
(1) Input status  
LED12/13/14/15  
(Status display LEDs)  
Ch1  
Ch2  
Ch3  
Ch4  
Input  
Method  
LED11  
LED12  
LED13  
LED14  
LED15  
Pulse  
Input  
: Input  
: No Input  
Communication error  
status (*1)  
(1) 4-digit error code LED12/13/14/15  
(Status display LEDs)  
Refer to "Communication Error Status Display".  
*1: If a communication error occurs, switch to "Communication Error Status Display". Changing SW08-1 from ON to OFF masks the "Communication Error  
Status Display" for 10 seconds so that the input status of channels 1 to 4 can be displayed.  
10-2.Communication Error Status Display  
If a communication error occurs, a 4-digit error code will be repeatedly displayed according to the steps shown below.  
Communication error status display consists of the following 10 steps. This operation is performed repeatedly to indicate the  
4-digit error code for the communication error.  
Furthermore, changing SW08-1 from ON to OFF masks the "Communication Error Status Display" for 10 seconds so that  
the input status of channels 1 to 4 can be displayed.  
Note  
:On,  
:Off,  
:Flashing  
LED11  
LED12  
LED13  
LED14  
LED15  
Error cord display (Binary number indication)  
Function  
Remark  
Common  
3
2
1
0
2 =8  
2 =4  
2 =2  
2 =1  
"Error Status Display"  
STEP1  
STEP2  
LEDs 12 to 15 flash 3 times  
Turn Off  
Starting Point Indication  
Blank  
Error code 1000's digit  
indication  
STEP3  
STEP4  
STEP5  
/
/
/
/
/
/
/
/
Error code 1000's digit  
Blank  
In the case of 6,  
Turn Off  
Error code 100's digit  
indication  
In the case of 6,  
Error code 100's digit  
STEP6  
STEP7  
STEP8  
STEP9  
STEP10  
Blank  
Error code 10's digit  
Blank  
Turn Off  
Error code 10's digit indication  
In the case of 0,  
/
/
/
/
/
/
/
/
Turn Off  
Error code 1's digit indication  
In the case of 7,  
Error code 1's digit  
Blank  
Turn Off  
The error codes that are displayed for M-NET communication errors are as shown below.  
Error Code  
6600  
Description of Error  
Multiple address error  
6601  
M-NET polarity unset error  
6602  
Transmission processor hardware error  
Transmission circuit bus-busy error  
Communications with transmission processor error  
No ACK error  
6603  
6606  
6607  
6608  
No return of response frame  
11  
11 Test Run  
Use the following procedure to confirm operation of the system.  
(1) Configure the settings of this device and the system controllers while referring to "8 Initial Setting Procedure".  
(2) Perform an operation from a system controller and confirm whether a connected device can be operated normally.  
(1) Confirm that there is no incorrect wiring of the signal lines from the meters.  
(2) Input a pulse from a connected meter to the PI controller.  
(3) Confirm whether the value increased by the pulse input and the data value on the system controller side match.  
(4) Set the data of the system controller to the current value of the meter and confirm whether the system controller and meter  
values match.  
If there is a problem, check the wiring and settings.  
For details on configuring settings, refer to "8 Initial Setting Procedure" and "9 Switch List".  
Note:  
• Various settings related to the charge operation need to be configured from the TG-2000A prior to starting the charge function  
operation. Furthermore, in such a case, be sure to perform a charge test run according to the instruction manual for TG-2000A.  
• Do not turn the power OFF after starting operation. The power rate will not be counted while the power interruption.  
12 Precautions for Expansion  
Observe the following matters when expanding the watt-hour meter or meters.  
(1) The power must be turned OFF while expanding the units. The power rate will not be counted while the power is OFF.  
(2) After expanding the units in the charge system, change the system settings with TG-2000A, check the settings, and test the operation.  
12  
This product is designed and intended for use in the residential,  
commercial and light-industrial environment.  
This product at hand is  
based on the following  
EU regulations:  
• Low Voltage Directive 73/23/EEC  
• Electromagnetic Compatibility Directive  
2004/108/EC  
NOTE:  
This equipment has been tested and found to comply with the limits for a Class  
B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed  
to provide reasonable protection against harmful interference in a residential  
installation. This equipment generates, uses and can radiate radio frequency  
energy and, if not installed and used in accordance with the instructions, may  
cause harmful interference to radio communications.  
However, there is no guarantee that interference will not occur in a particular  
installation.  
If this equipment does cause harmful interference to radio or television  
reception, which can be determined by turning the equipment off and on, the  
user is encouraged to try to correct the interference by one or more of the  
following measures:  
- Reorient or relocate the receiving antenna.  
- Increase the separation between the equipment and receiver.  
- Connect the equipment into an outlet on a circuit different from that to which  
the receiver is connected.  
- Consult the dealer or an experienced radio/TV technician for help.  
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN  
WT04973X01  

Lexmark Barcode Reader Mx6500e User Manual
Panasonic Cu E24fkr User Manual
Schumacher Inc 800a User Manual
Sharp Ar 287 User Manual
Sharp Mx 312nr User Manual
Sprint Nextel Samsung M320 User Manual
Streamlight Battery Charger 48 59 0192 User Manual
Toshiba 520t User Manual
Toshiba Rav Sm801bt E User Manual
Whirlpool X05002v0 User Manual