| 
		 Mitsubishi Electronics Mitsubishi Digital Electronics Air Conditioner Muz D36na User Manual  | 
	
| 	
		 OUTDOOR UNIT   
					No. OBH502   
					HFC   
					utilized   
					SERVICE MANUAL   
					R410A   
					Wireless type   
					Models   
					MUZ-D30NA   
					U1   
					MUZ-D30NA-   
					MUZ-D36NA   
					U1   
					MUZ-D36NA-   
					MUY-D30NA   
					MUY-D36NA   
					Indoor unit service manual   
					MSZ-D•NA Series (OBH501)   
					MSY-D•NA Series (OBH501)   
					CONTENTS   
					1. TECHNICAL CHANGES ··································· 3   
					2. PART NAMES AND FUNCTIONS····················· 3   
					3. SPECIFICATION················································ 4   
					4. OUTLINES AND DIMENSIONS ························ 6   
					5. WIRING DIAGRAM············································ 7   
					6. REFRIGERANT SYSTEM DIAGRAM··············· 9   
					7. DATA·································································11   
					8. ACTUATOR CONTROL··································· 18   
					9. SERVICE FUNCTIONS ··································· 19   
					10. TROUBLESHOOTING····································· 20   
					11. DISASSEMBLY INSTRUCTIONS···················· 39   
					PARTS CATALOG (OBB502)   
					TM   
					NOTE:   
					RoHS compliant products have <G> mark on the spec name plate.   
				1 
					TECHNICAL CHANGES   
					MUZ-D30NA   
					MUZ-D30NA -   
					MUZ-D36NA   
					MUZ-D36NA -   
					MUY-D30NA   
					MUY-D36NA   
					U1   
					U1   
					1. New model   
					2 
					PART NAMES AND FUNCTIONS   
					MUZ-D30NA MUZ-D36NA   
					MUY-D30NA MUY-D36NA   
					Air inlet   
					(back and side)   
					Piping   
					Drain hose   
					Air outlet   
					Drain outlet   
					3 
				3 
					SPECIFICATION   
					Item   
					Model   
					MSZ-D30NA   
					MSY-D30NA   
					MSZ-D36NA   
					MSY-D36NA   
					32,000/33,200   
					33,200/34,600   
					30,700   
					(9,800 ~ 30,700)   
					30,700   
					(9,800 ~ 30,700)   
					Cooling   
					1 
					Btu/h   
					(9,800 ~ 32,000) / (9,800 ~ 33,200) /   
					Capacity   
					(9,800 ~ 33,200)   
					(9,800 ~ 34,600)   
					Rated(Minimum~Maximum)   
					32,600   
					35,200   
					Heating 47 1 Btu/h   
					Heating 17 2 Btu/h   
					— 
					— 
					— 
					— 
					(8,700 ~ 34,000)   
					(8,700 ~ 36,000)   
					Capacity Rated   
					20,800   
					22,800   
					4,140/4,360   
					(620 ~ 4,140) /   
					(620 ~ 4,360)   
					3,840   
					(520 ~ 4,100)   
					4,210/4,240   
					(620 ~ 4,210) /   
					(620 ~ 4,240)   
					3,850   
					3,380   
					Cooling   
					1 
					W 
					Power consumption   
					(620 ~ 3,850)   
					(620 ~ 3,380)   
					Rated(Minimum~Maximum)   
					(TOTAL)   
					3,360   
					(520 ~ 3,600)   
					Heating 47 1 W   
					Heating 17 2 W   
					Cooling   
					— 
					— 
					— 
					— 
					7.9/8.2   
					[15.1]   
					Power consumption Rated   
					2,620   
					3,000   
					7.7/7.6   
					[14.5]   
					1 
					EER   
					[SEER]   
					3 
					8.0 [14.5]   
					9.1 [16.0]   
					HSPF IV(V)   
					COP   
					4 
					Heating   
					Heating   
					(8.2)   
					2.84   
					— 
					— 
					(8.2)   
					2.69   
					— 
					— 
					1 
					Outdoor unit model   
					External finish   
					MUZ-D30NA   
					MUY-D30NA   
					MUZ-D36NA   
					MUY-D36NA   
					Munsell 3Y 7.8/1.1   
					Power supply   
					V , phase , Hz   
					208/230 , 1 , 60   
					Max. fuse size (time delay)   
					Min. circuit ampacity   
					Fan motor   
					A 
					A 
					25   
					21   
					F.L.A   
					Model   
					R.L.A   
					L.R.A   
					0.93   
					TNB220FMCHT   
					Compressor   
					16   
					20   
					Refrigerant control   
					Liner expansion valve   
					Cooling   
					Heating   
					dB(A)   
					dB(A)   
					55   
					57   
					55   
					— 
					— 
					56   
					57   
					56   
					— 
					— 
					Sound level   
					1 
					Defrost method   
					Dimensions   
					Reverse cycle   
					Reverse cycle   
					W 
					D 
					H 
					in.   
					in.   
					in.   
					Ib.   
					33-1/16   
					13   
					33-7/16   
					Weight   
					141   
					126   
					141   
					126   
					Remote controller   
					Control voltage (by built-in transformer)   
					Refrigerant piping   
					Wireless type   
					12 - 24 VDC   
					Not supplied   
					3/8 (0.0315)   
					5/8 (0.0394)   
					Flared   
					Liquid   
					Gas   
					Indoor   
					Outdoor   
					in.   
					in.   
					Refrigerant pipe size   
					(Min. wall thickness)   
					Connection method   
					Flared   
					Height   
					ft.   
					50   
					Between the indoor &   
					outdoor units   
					difference   
					Piping length ft.   
					100   
					Refrigerant charge (R410A)   
					4 lb. 10 oz.   
					4 lb.   
					4 lb. 10 oz.   
					4 lb.   
					Refrigeration oil (Model)   
					NE022   
					NOTE : Test conditions are based on ARI 210/240.   
					1 : Rating conditions(Cooling) — Indoor : 80 ˚FDB, 67 ˚FWB, Outdoor : 95 ˚FDB, (75 ˚FWB)Rated frequency   
					(Heating) — Indoor : 70 ˚FDB, 60 ˚FWB, Outdoor : 47 ˚FDB, 43 ˚FWB Rated frequency   
					(Heating) — Indoor : 70 ˚FDB, 60 ˚FWB, Outdoor : 17 ˚FDB, 15 ˚FWBMaximum frequency   
					2 :   
					4 
				Test condition   
					3, 4   
					Indoor air condition   
					Dry bulb (°F) Wet bulb (°F)   
					Outdoor air condition   
					Dry bulb (°F) Wet bulb (°F)   
					Mode   
					ARI   
					Test   
					"A" Cooling Steady State   
					at rated compressor Speed   
					80   
					67   
					95   
					(75)   
					"B-2" Cooling Steady State   
					at rated compressor Speed   
					80   
					80   
					80   
					80   
					70   
					70   
					70   
					70   
					70   
					70   
					67   
					67   
					67   
					67   
					60   
					60   
					60   
					60   
					60   
					60   
					82   
					82   
					67   
					87   
					47   
					17   
					62   
					47   
					35   
					35   
					(65)   
					(65)   
					(53.5)   
					(69)   
					43   
					SEER "B-1" Cooling Steady State   
					(Cooling) at minimum compressor Speed   
					Low ambient Cooling Steady State   
					at minimum compressor Speed   
					Intermediate Cooling Steady State   
					at Intermediate compressor Speed   
					5 
					Standard Rating-Heating   
					at rated compressor Speed   
					Low temperature Heating   
					at rated compressor Speed   
					15   
					Max temperature Heating   
					at minimum compressor Speed   
					56.5   
					43   
					HSPF   
					(Heating)   
					High temperature Heating   
					at minimum compressor Speed   
					Frost Accumulation   
					at rated compressor Speed   
					33   
					Frost Accumulation   
					at Intermediate compressor Speed   
					33   
					5 
					5 : At Intermediate compressor Speed   
					=("Cooling rated compressor speed" - "minimum compressor speed") / 3 + "minimum compressor speed".   
					OPERATING RANGE   
					(1) POWER SUPPLY   
					Rated voltage   
					Guaranteed Voltage   
					208/230 V   
					1 phase   
					60 Hz   
					Min.187 V 208 V 230 V Max.253 V   
					Outdoor unit   
					(2) OPERATION   
					Intake air temperature (°F)   
					Mode   
					Condition   
					Standard temperature   
					Maximum temperature   
					Minimum temperature   
					Maximum humidity   
					Indoor   
					78 %   
					Outdoor   
					DB   
					80   
					90   
					67   
					WB   
					67   
					73   
					DB   
					95   
					115   
					14   
					WB   
					— 
					— 
					— 
					Cooling   
					57   
					— 
					Standard temperature   
					Heating Maximum temperature   
					Minimum temperature   
					70   
					80   
					70   
					60   
					67   
					60   
					47   
					75   
					14   
					43   
					65   
					13   
					5 
				4 
					OUTLINES AND DIMENSIONS   
					Unit: inch   
					MUZ-D30NA   
					MUZ-D36NA   
					MUY-D30NA   
					MUY-D36NA   
					Open as a rule   
					20 inch or more if   
					the front and both   
					sides are open   
					REQUIRED SPACE   
					4 inch or more /   
					8 inch or more if   
					there are obstacles   
					to both sides   
					Open as a rule   
					20 inch or more if the back,   
					both sides and top are open   
					6 
				5 
					WIRING DIAGRAM   
					MUZ-D30NA MUZ-D36NA   
					7 
				MUY-D30NA MUY-D36NA   
					8 
				6 
					REFRIGERANT SYSTEM DIAGRAM   
					Unit:inch   
					MUZ-D30NA   
					MUZ-D36NA   
					Oil   
					separator   
					Capillary tube   
					Strainer   
					#100   
					O.D. 0.071 x I.D. 0.024   
					x 39-3/8   
					Refrigerant pipe 5/8   
					(with heat insulator)   
					( 1.8 x 0.6 x 1,000)   
					4-way valve   
					Service   
					port   
					Stop valve   
					(with service port)   
					Outdoor   
					heat   
					Defrost   
					High-pressure thermistor   
					RT61   
					Flared connection   
					Ambient   
					temperature   
					thermistor   
					RT65   
					exchanger   
					Switch   
					Discharge   
					temperature   
					thermistor   
					RT62   
					Service   
					port   
					Compressor   
					Outdoor heat   
					exchanger   
					temperature   
					thermistor   
					RT68   
					Flared connection   
					LEV   
					Strainer   
					#100   
					Strainer   
					#100   
					R.V. coil   
					heating ON   
					cooling OFF   
					Receiver   
					Stop valve   
					Capillary tube   
					O.D. 0.142 I.D. 0.094   
					1-31/32   
					Refrigerant pipe 3/8   
					(with heat insulator)   
					Refrigerant flow in cooling   
					Refrigerant flow in heating   
					( 
					3.6   
					2.4 50)   
					Unit:inch   
					MUY-D30NA   
					MUY-D36NA   
					Oil separator   
					Capillary tube   
					Outdoor   
					heat   
					exchanger   
					O.D. 0.071 x I.D. 0.024   
					Ambient   
					x 39-3/8   
					Refrigerant pipe 5/8   
					(with heat insulator)   
					temperature   
					( 1.8 x 0.6 x 1,000)   
					thermistor   
					RT65   
					Strainer   
					#100   
					Service   
					Stop valve   
					(with service port)   
					port   
					High-pressure   
					Switch   
					Flared connection   
					Outdoor heat   
					exchanger   
					temperature   
					thermistor   
					RT68   
					Discharge   
					temperature   
					thermistor   
					RT62   
					Service   
					port   
					Compressor   
					Flared connection   
					LEV   
					Strainer   
					#100   
					Capillary tube   
					Stop valve   
					O.D. 0.142 x I.D. 0.094   
					x 1-31/32   
					( 3.6 x 2.4 x 50)   
					Refrigerant pipe 3/8   
					(with heat insulator)   
					Refrigerant flow in cooling   
					9 
				MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE   
					Refrigerant piping : ft.   
					Piping size O.D : in.   
					Model   
					Max. Length   
					Max. Height difference   
					B 
					Gas   
					5/8   
					Liquid   
					3/8   
					A 
					MUZ-D30NA   
					MUZ-D36NA   
					MUY-D30NA   
					MUY-D36NA   
					100   
					50   
					Indoor   
					unit   
					Max. Height   
					difference   
					B 
					Max. length   
					A 
					Outdoor unit   
					ADDITIONAL REFRIGERANT CHARGE (R410A:oz.)   
					Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.   
					Refrigerant piping length (one way) : ft.   
					Outdoor unit   
					precharged   
					Model   
					25   
					0 
					30   
					40   
					50   
					60   
					70   
					80   
					90   
					100   
					MUZ-D30NA   
					MUZ-D36NA   
					4 lb. 10 oz.   
					2.96   
					8.88   
					14.80   
					20.72   
					26.64   
					32.56   
					38.48   
					44.40   
					Calculation : X oz. = 2.96/5 oz. / ft. x (Refrigerant piping length (ft.) - 25)   
					Refrigerant piping length (one way) : ft.   
					Outdoor unit   
					precharged   
					Model   
					25   
					0 
					30   
					40   
					50   
					60   
					70   
					80   
					90   
					100   
					MUY-D30NA   
					MUY-D36NA   
					4 lb.   
					1.08   
					3.24   
					5.40   
					7.56   
					9.72   
					11.88   
					14.04   
					16.20   
					Calculation : X oz. = 1.08/5 oz. / ft. x (Refrigerant piping length (ft.) - 25)   
					NOTE : Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.   
					10   
				7 DATA   
					MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA   
					7-1. PERFORMANCE DATA   
					1) COOLING CAPACITY   
					Indoor air   
					IWB   
					(˚F)   
					71   
					Outdoor intake air DB temperature (˚F)   
					Model   
					75   
					85   
					95   
					105   
					115   
					TC   
					SHC TPC   
					TC   
					SHC TPC   
					TC   
					SHC TPC   
					TC   
					SHC TPC   
					TC   
					SHC TPC   
					37.6 19.1 3.43 35.2 17.8 3.75 33.0 16.7 4.04 30.7 15.6 4.25 28.2 14.3 4.43   
					35.6 22.8 3.23 33.2 21.2 3.56 30.7 19.6 3.85 28.6 18.3 4.08 26.2 16.8 4.27   
					33.5 25.9 3.08 31.0 24.0 3.41 28.9 22.3 3.68 26.2 20.3 3.93 23.9 18.5 4.08   
					40.7 19.8 3.88 38.0 18.5 4.25 35.7 17.4 4.58 33.2 16.2 4.82 30.5 14.9 5.01   
					38.5 23.9 3.66 35.9 22.2 4.03 33.2 20.6 4.36 30.9 19.1 4.62 28.4 17.6 4.84   
					36.2 27.3 3.49 33.5 25.3 3.86 31.2 23.5 4.16 28.4 21.4 4.45 25.9 19.5 4.62   
					37.6 19.1 3.01 35.2 17.8 3.30 33.0 16.7 3.55 30.7 15.6 3.73 28.2 14.3 3.89   
					35.6 22.8 2.84 33.2 21.2 3.13 30.7 19.6 3.38 28.6 18.3 3.58 26.2 16.8 3.75   
					33.5 25.9 2.70 31.0 24.0 2.99 28.9 22.3 3.23 26.2 20.3 3.45 23.9 18.5 3.58   
					40.7 19.8 3.75 38.0 18.5 4.10 35.7 17.4 4.42 33.2 16.2 4.65 30.5 14.9 4.84   
					38.5 23.9 3.54 35.9 22.2 3.89 33.2 20.6 4.21 30.9 19.1 4.46 28.4 17.6 4.67   
					36.2 27.3 3.37 33.5 25.3 3.73 31.2 23.5 4.02 28.4 21.4 4.29 25.9 19.5 4.46   
					42.4 20.6 3.77 39.6 19.3 4.13 37.2 18.1 4.45 34.6 16.8 4.69 31.8 15.5 4.88   
					40.1 24.9 3.56 37.4 23.2 3.92 34.6 21.5 4.24 32.2 20.0 4.49 29.6 18.3 4.71   
					37.7 28.4 3.39 34.9 26.3 3.75 32.5 24.5 4.05 29.6 22.3 4.32 27.0 20.3 4.49   
					MUZ-D30NA   
					MUZ-D36NA   
					MUY-D30NA   
					67   
					63   
					71   
					67   
					63   
					71   
					67   
					63   
					71   
					MUY-D36NA   
					(208 V)   
					67   
					63   
					71   
					MUY-D36NA   
					(230 V)   
					67   
					63   
					NOTE : 1. IWB : Intake air wet-bulb temperature   
					TC : Total Capacity (x103 Btu/h)   
					SHC: Sensible Heat Capacity (x103 Btu/h)   
					TPC : Total Power Consumption (kW)   
					2. SHC is based on 80 ˚F of indoor Intake air DB temperature.   
					2) COOLING CAPACITY CORRECTIONS   
					Refrigerant piping length (one way : ft.)   
					25 (std.)   
					1.0   
					40   
					65   
					100   
					MUZ-D30NA   
					MUZ-D36NA   
					MUY-D30NA   
					MUY-D36NA   
					0.95   
					0.878   
					0.713   
					3) HEATING CAPACITY   
					Indoor air   
					Outdoor intake air WB temperature (˚F)   
					Model   
					IDB   
					(˚F)   
					75   
					15   
					25   
					35   
					43   
					45   
					55   
					TC   
					TPC   
					TC   
					TPC   
					TC   
					TPC   
					3.28   
					3.19   
					3.11   
					3.74   
					3.65   
					3.55   
					TC   
					TPC   
					3.44   
					3.36   
					3.28   
					3.94   
					3.84   
					3.74   
					TC   
					TPC   
					3.49   
					3.43   
					3.33   
					3.99   
					3.92   
					3.80   
					TC   
					TPC   
					3.63   
					3.56   
					3.49   
					4.15   
					4.07   
					3.99   
					18.9   
					20.0   
					20.5   
					20.4   
					21.6   
					22.2   
					2.50   
					2.42   
					2.32   
					2.86   
					2.76   
					2.65   
					23.6   
					24.5   
					25.6   
					25.5   
					26.4   
					27.6   
					2.94   
					2.87   
					2.77   
					3.36   
					3.28   
					3.17   
					28.2   
					28.9   
					29.8   
					30.4   
					31.2   
					32.2   
					31.8   
					32.6   
					33.6   
					34.3   
					35.2   
					36.3   
					32.8   
					33.6   
					34.6   
					35.4   
					36.3   
					37.3   
					37.2   
					38.0   
					38.8   
					40.1   
					41.0   
					41.9   
					MUZ-D30NA   
					MUZ-D36NA   
					70   
					65   
					75   
					70   
					65   
					NOTE : 1. IDB : Intake air dry-bulb temperature   
					TC : Total Capacity (x103 Btu/h)   
					TPC : Total Power Consumption (kW)   
					2. Above data is for heating operation without any frost.   
					How to operate with fixed operational frequency of the compressor.   
					1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL   
					mode or EMERGENCY HEAT mode before starting to operate the air conditioner.   
					2. The compressor starts with operational frequency.   
					3. The fan speed of the indoor unit is High.   
					4. This operation continues for 30 minutes.   
					5. In order to release this operation, press the EMERGENCY OPERATION switch twice or once, or press any button on   
					the remote controller.   
					11   
				7-2. PERFORMANCE CURVE   
					Cooling   
					MUZ-D36NA   
					MUY-D30NA   
					MUZ-D30NA   
					SHF at rating condition = 0.64   
					SHF at rating condition = 0.62   
					SHF at rating condition = 0.64   
					= 763 CFM   
					= 763 CFM   
					= 763 CFM   
					Airflow   
					Airflow   
					Airflow   
					40   
					38   
					36   
					34   
					32   
					30   
					28   
					26   
					24   
					43   
					41   
					39   
					37   
					35   
					33   
					31   
					29   
					27   
					40   
					38   
					36   
					34   
					32   
					30   
					28   
					26   
					24   
					Indoor intake air   
					Indoor intake air   
					Indoor intake air   
					WB temperature (°F)   
					WB temperature (°F)   
					WB temperature (°F)   
					71   
					67   
					63   
					71   
					67   
					63   
					71   
					67   
					63   
					) 
					) 
					4.5   
					4.3   
					4.1   
					3.9   
					3.7   
					3.5   
					3.3   
					3.1   
					5.2   
					4.8   
					4.4   
					4.0   
					3.6   
					4.0   
					3.8   
					3.6   
					3.4   
					3.2   
					3.0   
					2.8   
					2.6   
					71   
					67   
					63   
					71   
					67   
					63   
					71   
					67   
					63   
					ure (°F   
					ure (°F   
					mperature (°F)   
					Indoor intake air WB temperat   
					Indoor intake air WB temperat   
					Indoor intake air WB te   
					65   
					75   
					85   
					95   
					105   
					115   
					65   
					75   
					85   
					95   
					105   
					115   
					65   
					75   
					85   
					95   
					105   
					115   
					Outdoor intake air DB temperature (°F)   
					Outdoor intake air DB temperature (°F)   
					Outdoor intake air DB temperature (°F)   
					MUY-D36NA   
					SHF at rating condition = 0.62   
					= 763 CFM   
					Airflow   
					46   
					42   
					38   
					34   
					30   
					26   
					Ind   
					oor intak   
					e air WB temperature (°F)   
					71   
					67   
					63   
					5.0   
					4.6   
					4.2   
					3.8   
					3.4   
					71   
					67   
					63   
					rature (°F)   
					mpe   
					oor intake air WB te   
					Ind   
					65   
					75   
					85   
					95   
					105   
					115   
					Outdoor intake air DB temperature (°F)   
					Heating   
					MUZ-D36NA   
					MUZ-D30NA   
					45   
					= 848 CFM   
					Airflow   
					= 848 CFM   
					Airflow   
					48   
					43   
					38   
					33   
					28   
					23   
					18   
					65   
					70   
					75   
					65   
					70   
					75   
					40   
					35   
					30   
					25   
					20   
					15   
					4.0   
					3.6   
					3.2   
					2.8   
					2.4   
					4.5   
					4.1   
					3.7   
					3.3   
					2.9   
					75   
					70   
					65   
					75   
					70   
					65   
					15   
					25   
					35   
					45   
					55   
					15   
					25   
					35   
					45   
					55   
					Outdoor intake air WB temperature (°F)   
					Outdoor intake air WB temperature (°F)   
					This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships   
					between frequency and capacity.   
					12   
				7-3. CONDENSING PRESSURE   
					Cooling   
					Data is based on the condition of indoor humidity 50 %.   
					Air flow should be set to High speed.   
					MUZ-D30NA   
					(PSIG)   
					580   
					86   
					80   
					75   
					70   
					540   
					500   
					460   
					420   
					380   
					340   
					300   
					260   
					(PSIG)   
					150   
					140   
					130   
					120   
					110   
					100   
					90   
					86   
					80   
					75   
					70   
					68 70   
					75   
					80   
					85   
					90   
					95   
					100 105(°F)   
					68 70   
					75   
					80   
					85   
					90   
					95   
					100 105(°F)   
					Outdoor ambient temperature   
					Outdoor ambient temperature   
					MUZ-D36NA   
					(PSIG)   
					580   
					86   
					80   
					75   
					70   
					540   
					500   
					460   
					420   
					380   
					340   
					300   
					260   
					(PSIG)   
					150   
					140   
					130   
					120   
					110   
					100   
					90   
					86   
					80   
					75   
					70   
					68 70   
					75   
					80   
					85   
					90   
					95   
					100 105(°F)   
					68 70   
					75   
					80   
					85   
					90   
					95   
					100 105(°F)   
					Outdoor ambient temperature   
					Outdoor ambient temperature   
					MUY-D30NA   
					(PSIG)   
					580   
					540   
					500   
					460   
					420   
					380   
					340   
					300   
					260   
					86   
					80   
					75   
					70   
					(PSIG)   
					150   
					140   
					130   
					120   
					110   
					100   
					90   
					86   
					80   
					75   
					70   
					68 70   
					75   
					80   
					85   
					90   
					95   
					100 105(°F)   
					68 70   
					75   
					80   
					85   
					90   
					95   
					100 105(°F)   
					Outdoor ambient temperature   
					Outdoor ambient temperature   
					13   
				MUY-D36NA   
					(PSIG)   
					580   
					86   
					80   
					75   
					70   
					540   
					500   
					460   
					420   
					380   
					340   
					300   
					260   
					(PSIG)   
					150   
					140   
					130   
					120   
					110   
					100   
					90   
					86   
					80   
					75   
					70   
					68 70   
					75   
					80   
					85   
					90   
					95   
					100 105(°F)   
					68 70   
					75   
					80   
					85   
					90   
					95   
					100 105(°F)   
					Outdoor ambient temperature   
					Outdoor ambient temperature   
					Heating   
					Data is based on the condition of outdoor humidity 75 %.   
					Air flow should be set to High speed.   
					Data is for heating operation without any frost.   
					MUZ-D30NA   
					(PSIG)   
					(PSIG)   
					500   
					480   
					460   
					440   
					420   
					400   
					380   
					360   
					340   
					320   
					300   
					280   
					260   
					240   
					220   
					200   
					150   
					140   
					130   
					120   
					110   
					100   
					90   
					75   
					70   
					65   
					75   
					70   
					65   
					58Hz   
					80   
					58Hz   
					70   
					60   
					50   
					14   
					20 25 30 35 40 45 50 55 60 65 70(°F)   
					Outdoor ambient temperature   
					14 20 25 30 35 40 45 50 55 60 6570(°F)   
					Outdoor ambient temperature   
					MUZ-D36NA   
					(PSIG)   
					500   
					(PSIG)   
					150   
					75   
					70   
					65   
					480   
					460   
					440   
					420   
					400   
					380   
					360   
					340   
					320   
					300   
					280   
					260   
					240   
					220   
					200   
					140   
					130   
					120   
					110   
					100   
					90   
					75   
					70   
					65   
					58Hz   
					80   
					58Hz   
					70   
					60   
					50   
					14   
					20 25 30 35 40 45 50 55 60 65 70(°F)   
					Outdoor ambient temperature   
					14 20 25 30 35 40 45 50 55 60 6570(°F)   
					Outdoor ambient temperature   
					14   
				7-4. STANDARD OPERATION DATA   
					Model   
					MSZ-D30NA   
					MSZ-D36NA   
					MSY-D30NA MSY-D36NA   
					Item   
					Unit   
					Btu / h   
					— 
					Cooling   
					Heating   
					32,600   
					— 
					Cooling   
					Heating   
					35,200   
					— 
					Cooling   
					30,700   
					0.64   
					Cooling   
					33,200/34,000   
					0.62   
					Capacity   
					SHF   
					30,700   
					0.64   
					3.85   
					84   
					32,000/33,200   
					0.62   
					Input   
					kW   
					3.36   
					84   
					4.14/4.36   
					91   
					3.84   
					91   
					3.38   
					4.21/4.24   
					92   
					Rated frequency   
					Indoor unit   
					Hz   
					79   
					MSZ-D30NA   
					MSZ-D36NA   
					MSY-D30NA MSY-D36NA   
					V,   
					phase,   
					Hz   
					Power supply   
					Input   
					208/230 , 1 , 60   
					0.058   
					kW   
					A 
					Fan motor current   
					Outdoor unit   
					0.45/0.42   
					MUZ-D30NA   
					MUZ-D36NA   
					MUY-D30NA MUY-D36NA   
					V,   
					phase,   
					Hz   
					Power supply   
					208/230 , 1 , 60   
					Input   
					kW   
					A 
					3.792   
					3.302   
					4.082/4.302   
					3.782   
					3.322   
					4.152/4.182   
					18.95/17.26   
					Comp. current   
					17.25/15.56   
					14.95/13.46   
					18.65/17.86   
					17.25/15.56   
					15.05/13.56   
					Fan motor current   
					A 
					0.80/0.72   
					Condensing pressure   
					Suction pressure   
					PSIG   
					PSIG   
					˚F   
					468   
					126   
					404   
					96   
					480   
					122   
					420   
					94   
					453   
					125   
					475   
					119   
					Discharge temperature   
					Condensing temperature   
					Suction temperature   
					Comp. shell bottom temperature   
					Ref. pipe length   
					186.8   
					126.5   
					45.5   
					169.7   
					114.3   
					29.8   
					156.4   
					198.7   
					128.5   
					48.0   
					168.8   
					117.0   
					29.1   
					155.7   
					191.3   
					123.8   
					54.7   
					197.1   
					127.4   
					48.6   
					˚F   
					˚F   
					˚F   
					175.6   
					187.0   
					177.4   
					182.7   
					ft.   
					25   
					Refrigerant charge (R410A)   
					— 
					4 lb. 10 oz.   
					4 lb.   
					DB   
					Intake air temperature   
					WB   
					˚F   
					80   
					67   
					70   
					60   
					80   
					67   
					70   
					60   
					80   
					67   
					80   
					67   
					˚F   
					DB   
					Discharge air temperature   
					WB   
					˚F   
					53.9   
					53   
					112.2   
					73.9   
					53   
					114.9   
					74.6   
					53.7   
					52.8   
					51.7   
					50.8   
					˚F   
					52.1   
					Fan speed (High)   
					rpm   
					CFM   
					˚F   
					1,100   
					Airflow (High)   
					741 (Wet)   
					795   
					47   
					738 (Wet)   
					794   
					47   
					718 (Wet)   
					710 (Wet)   
					DB   
					Intake air temperature   
					WB   
					95   
					— 
					95   
					— 
					95   
					— 
					95   
					— 
					˚F   
					43   
					43   
					Fan speed   
					rpm   
					CFM   
					800   
					Airflow   
					1,941   
					15   
				7-5. CAPACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCY   
					MUZ-D30NA   
					Correction of Cooling capacity   
					Correction of Cooling total input   
					Correction of Heating total input   
					Correction of Heating capacity   
					1.5   
					1.0   
					0.5   
					1.5   
					1.0   
					0.5   
					1.5   
					1.0   
					0.5   
					1.5   
					1.0   
					0.5   
					(Hz)   
					(Hz)   
					150   
					(Hz)   
					(Hz)   
					150   
					0 
					50   
					100   
					150   
					0 
					50   
					100   
					0 
					50   
					100   
					150   
					0 
					50   
					100   
					The operational frequency of compressor   
					The operational frequency of compressor The operational frequency of compressor   
					The operational frequency of compressor   
					MUZ-D36NA   
					Correction of Cooling capacity   
					1.5   
					Correction of Cooling total input   
					Correction of Heating capacity   
					Correction of Heating total input   
					1.5   
					1.0   
					0.5   
					1.5   
					1.5   
					1.0   
					0.5   
					1.0   
					0.5   
					1.0   
					0.5   
					(Hz)   
					(Hz)   
					150   
					(Hz)   
					(Hz)   
					150   
					0 
					50   
					100   
					150   
					0 
					50   
					100   
					0 
					50   
					100   
					150   
					0 
					50   
					100   
					The operational frequency of compressor   
					The operational frequency of compressor The operational frequency of compressor   
					The operational frequency of compressor   
					MUY-D30NA   
					Correction of Cooling capacity   
					Correction of Cooling total input   
					1.5   
					1.5   
					1.0   
					0.5   
					1.0   
					0.5   
					(Hz)   
					0 
					50   
					100   
					150   
					0 
					50   
					100   
					150   
					The operational frequency of compressor   
					The operational frequency of compressor   
					MUY-D36NA   
					Correction of Cooling capacity   
					1.5   
					Correction of Cooling total input   
					1.5   
					1.0   
					0.5   
					1.0   
					0.5   
					(Hz)   
					0 
					50   
					100   
					150   
					0 
					50   
					100   
					150   
					The operational frequency of compressor   
					The operational frequency of compressor   
					16   
				7-6. TEST RUN OPERATION (How to operate fixed-frequency operation)   
					1. Press EMERGENCY OPERATION switch to COOL or HEAT mode (COOL : Press once, HEAT : Press twice).   
					2. Test run operation starts and continues to operate for 30 minutes.   
					3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode.   
					4. Indoor fan operates at High speed.   
					5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (Operation frequency of compressor   
					varies).   
					6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on   
					remote controller.   
					17   
				8 
					ACTUATOR CONTROL   
					MUZ-D30NA   
					MUZ-D36NA   
					MUY-D30NA   
					MUY-D36NA   
					8-1. OUTDOOR FAN MOTOR CONTROL   
					The fan motor turns ON/OFF, interlocking with the compressor.   
					[ON] The fan motor turns ON 5 seconds before the compressor starts up.   
					[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.   
					5 seconds   
					15 seconds   
					ON   
					Compressor   
					OFF   
					ON   
					Outdoor fan   
					motor   
					OFF   
					8-2. R.V. COIL CONTROL   
					<MUZ>   
					. . . . . . . . . . . . . . . . .   
					. . . . . . . . . . . . . . . . .   
					Heating   
					ON   
					OFF   
					OFF   
					Cooling   
					. . . . . . . . . . . . . . . . . . . .   
					Dry   
					NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.   
					<COOL>   
					<HEAT>   
					5 seconds   
					5 seconds   
					ON   
					ON or OFF   
					R.V.coil   
					ON or OFF   
					OFF   
					ON   
					Outdoor fan   
					motor   
					OFF   
					8-3. Relation between main sensor and actuator   
					Actuator   
					Sensor   
					Purpose   
					Outdoor   
					fan motor   
					Indoor   
					fan motor   
					Compressor   
					LEV   
					R.V. coil   
					Discharge temperature thermistor Protection   
					○ ○   
					Cooling : Coil frost prevention   
					Heating : High pressure protection   
					Defrosting   
					○ 
					Indoor coil temperature thermistor   
					○ ○ ○   
					Defrost thermistor   
					○ ○ ○ ○ ○   
					Fin temperature thermistor   
					Protection   
					○ 
					○ 
					Outdoor heat exchanger temperature Protection   
					Ambient temperature thermistor Cooling : Low ambient temperature operation   
					○ ○ ○   
					○ ○ ○   
					18   
				9 
					SERVICE FUNCTIONS   
					MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA   
					9-1. PRE-HEAT CONTROL   
					If moisture gets into the refrigerant cycle, or when refrigerant is liquefied and col-   
					lected in the compressor, it may interfere the start-up of the compressor.   
					To improve start-up condition, the compressor is energized even while it is not   
					operating.   
					ON   
					This is to generate heat at the winding.   
					1 
					2 
					3 
					4 
					The compressor uses about 50 W when pre-heat control is turned ON.   
					Pre-heat control is ON at initial setting.   
					[How to activate pre-heat control]   
					1. Turn OFF the power supply for the air conditioner before making the setting.   
					2. Set the 2nd Dip Switch of SW1 on the outdoor electronic control P.C. board to   
					ON to activate pre-heat control function.   
					The compressor is energized even while it is not operating.   
					This is to generate heat at the winding to improve the compressor's start-up condition.   
					ON   
					Power   
					OFF   
					ON   
					Compressor   
					OFF   
					Outside temperature   
					68 °F (20 °C)   
					30min.   
					30min.   
					30min.   
					30min.   
					30min.   
					30min. 15min. 30min. 15min. 30min.   
					ON   
					Pre-heat   
					OFF   
					Breaker ON   
					Start   
					Stop   
					When outside   
					temperature is   
					above 68 °F   
					(20 °C)   
					operation operation   
					1. Pre-heat control is turned ON for 15 or 30 min. after the breaker is turned ON.   
					2. 30 min. after the unit is stopped, pre-heat control is turned ON for 15 or 30 min. and turned OFF for 30 min.   
					This is repeated as shown in the graph until the breaker is turned OFF.   
					When outside temperature is 68 °F (20 °C) or below , pre-heat control is ON for 30 min.   
					When outside temperature is 70 °F (21 °C) or above, pre-heat control is ON for 15 min.   
					NOTE: When the unit is started with the remote controller, pre-heat control is turned OFF.   
					Compressor uses 50 W when pre-heat control is turned ON.   
					9-2. CHANGE IN DEFROST SETTING   
					Changing defrost finish temperature   
					1. Turn OFF the power supply for the air conditioner before making the setting.   
					2. Set the 4th Dip Switch of SW1 on the outdoor electronic control P.C. board to   
					ON to change the defrost finish temperature. (Refer to 10-6-1.)   
					ON   
					1 
					2 
					3 
					4 
					4th Dip Switch of SW1   
					Defrost finish temperature   
					49.5 °F (9.7 °C)   
					OFF   
					(Initial setting)   
					ON   
					64.9 °F (18.3 °C)   
					19   
				10   
					TROUBLESHOOTING   
					MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA   
					10-1. CAUTIONS ON TROUBLESHOOTING   
					1. Before troubleshooting, check the following   
					1) Check the power supply voltage.   
					2) Check the indoor/outdoor connecting wire for miswiring.   
					2. Take care of the following during servicing   
					1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, then after con-   
					firming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.   
					2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic   
					control P.C. board.   
					3) When removing the electrical parts, be careful to the residual voltage of smoothing capacitor.   
					4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the   
					components.   
					5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.   
					Lead wiring   
					Housing point   
					3. Troubleshooting procedure   
					1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.   
					To make sure, check how many times the abnormality indication is flashing on and off before starting service work.   
					2) Before servicing check that the connector and terminal are connected properly.   
					3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the   
					components for bursting and discoloration.   
					4) Refer to 10-2. and 10-3.   
					20   
				10-2. FAILURE MODE RECALL FUNCTION   
					Outline of the function   
					This air conditioner can memorize the abnormal condition which has occurred once.   
					Even though LED indication listed on the troubleshooting check table (10-3.) disappears, the memorized failure details   
					can be recalled.   
					This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.   
					This figures show about MSZ type.   
					1. Flow chart of failure mode recall function for the indoor/outdoor unit   
					Operational procedure   
					The cause of abnormality cannot be found because the abnormality doesn't recur.   
					Setting up the failure mode recall function   
					Turn ON the power supply.   
					<Preparation of the remote controller>   
					While pressing both OPERATION SELECT button and TOO COOL button on the   
					remote controller at the same time, press RESET button.   
					First, release RESET button.   
					And release the other two buttons after all LCD in operation display section of the   
					remote controller is displayed after 3 seconds.   
					Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature   
					is displayed) with the remote controller headed towards the indoor unit.   
					1 
					1. Regardless of normal or abnormal condition, a short   
					beep is emitted once the signal is received.   
					Does the left lamp of OPERATION INDICATOR lamp on the   
					indoor unit blink at the interval of 0.5 seconds?   
					Blinks: Either indoor or outdoor unit is abnormal. Beep is emit-   
					ted at the same timing as the blinking of the left lamp   
					Indoor unit is normal.   
					But the outdoor unit might be abnormal because there are some abnor-   
					malities that can't be recalled with this way.   
					Confirm if outdoor unit is abnormal according to the detailed outdoor   
					unit failure mode recall function. (Refer to 10-2.2)   
					No   
					(OFF)   
					of OPERATION INDICATOR lamp.   
					2 
					Yes   
					(Blinks)   
					Judgment of indoor/outdoor abnormality   
					Before blinking, does the left lamp of OPERATION INDICA-   
					TOR lamp stay ON for 3 seconds?   
					Yes   
					Stays ON for 3 seconds (without beep):   
					The outdoor unit is abnormal.   
					No   
					The indoor unit is abnormal.   
					The outdoor unit is abnormal.   
					Check the blinking pattern, and confirm the abnormal point with the indoor unit   
					failure mode table. (Refer to indoor unit service manual.)   
					Check the blinking pattern, and confirm the abnormal point with the   
					outdoor unit failure mode table. (Refer to 10-2.3)   
					Make sure to check at least two consecutive blinking cycles.   
					2 
					Make sure to check at least two consecutive blinking cycles.   
					3 
					Releasing the failure mode recall function   
					Release the failure mode recall function by the following procedures.   
					Turn OFF the power supply and turn it ON again.   
					Press RESET button of the remote controller.   
					Repair the defective parts.   
					Deleting the memorized abnormal condition   
					After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall   
					function" mentioned above.   
					Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)   
					with the remote controller headed towards the indoor unit.   
					Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.   
					Release the failure mode recall function according to "Releasing the failure mode recall function"   
					mentioned above.   
					NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.   
					2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.   
					2. Blinking pattern when the indoor unit is abnormal:   
					Blinking at 0.5-   
					second interval   
					Blinking at 0.5-   
					second interval   
					2.5-second OFF   
					2.5-second OFF   
					ON   
					OFF   
					Beeps   
					Beeps   
					Beeps   
					Repeated cycle   
					Repeated cycle   
					Repeated cycle   
					3.Blinking pattern when the outdoor unit is abnormal:   
					Blinking at 0.5-   
					Blinking at 0.5-   
					second interval   
					2.5-second OFF   
					3-second ON   
					second interval   
					2.5-second OFF   
					3-second ON   
					ON   
					OFF   
					No beep   
					Beeps   
					No beep   
					Beeps   
					Repeated cycle   
					Repeated cycle   
					Repeated cycle   
					21   
				2. Flow chart of the detailed outdoor unit failure mode recall function   
					Operational procedure   
					The outdoor unit might be abnormal.   
					Confirm if outdoor unit is abnormal according to the following procedures.   
					Confirm that the remote controller is in the failure mode recall function.   
					With the remote controller headed towards the indoor unit, press TOO   
					COOL or TOO WARM button to adjust the set temperature to 77 ˚F (25 ˚C).   
					1 
					1. Regardless of normal or abnormal condition, 2 short   
					beeps are emitted as the signal is received.   
					Does left lamp of OPERATION INDICATOR lamp on   
					the indoor unit blink at the interval of 0.5 seconds?   
					Blinks: The outdoor unit is abnormal. Beep is emitted   
					No   
					at the same timing as the blinking of the left   
					(OFF)   
					lamp of OPERATION INDICATOR lamp.   
					Yes   
					2 
					) 
					(Blinks   
					The outdoor unit is abnormal.   
					Check the blinking pattern, and confirm the abnormal point with the out-   
					door unit failure mode table. (10-2.3.)   
					The outdoor unit is normal.   
					Make sure to check at least two consecutive blinking cycles.   
					2 
					Releasing the failure mode recall function   
					Release the failure mode recall function by the following procedures.   
					Turn OFF the power supply and turn it ON again.   
					Press RESET button of the remote controller.   
					Release the failure mode recall function accord-   
					ing to the left mentioned procedure.   
					Repair the defective parts.   
					Deleting the memorized abnormal condition   
					After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall   
					function" (10-2.1.).   
					Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)   
					with the remote controller headed towards the indoor unit.   
					Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.   
					Release the failure mode recall function according to "Releasing the failure mode recall function"   
					mentioned above.   
					NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.   
					2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.   
					2.Blinking pattern when outdoor unit is abnormal:   
					Blinking at 0.5-   
					second interval   
					Blinking at 0.5-   
					second interval   
					2.5-second OFF   
					3-second ON   
					2.5-second OFF   
					3-second ON   
					ON   
					OFF   
					No beep   
					Beeps   
					No beep   
					Beeps   
					Repeated cycle   
					Repeated cycle   
					Repeated cycle   
					22   
				3. Outdoor unit failure mode table   
					MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA   
					LED indication   
					(Outdoor P.C.   
					board)   
					The left lamp of OPERA-   
					TION INDICATOR lamp   
					(Indoor unit)   
					Indoor/outdoor   
					unit failure mode   
					recall function   
					Abnormal point   
					Condition   
					Correspondence   
					— 
					(Failure mode / protection)   
					LED 1   
					LED 2   
					OFF   
					Non (Normal)   
					— 
					— 
					— 
					— 
					•Check the connection of the   
					compressor connecting wire.   
					•Refer to 10-5. "How to check   
					inverter / compressor".   
					IPM protection stop or lock protection stop is continuously   
					performed 3 times within 1 minute after the compres-   
					2-time flash   
					Outdoor power system   
					Lighting Lighting sor gets started, or converter protection stop or bus-bar   
					○ 
					voltage protection stop is continuously performed 3 times •Refer to 10-5. "Check of   
					within 3 minutes after start-up.   
					compressor start failure".   
					•Check the stop valve.   
					Discharge temperature thermistor Lighting   
					Once   
					Once   
					Twice   
					Defrost thermistor (MUZ)   
					Lighting   
					Lighting   
					•Refer to 10-5. "Check of   
					outdoor thermistors".   
					Ambient temperature thermistor   
					Fin temperature thermistor   
					3-time flash   
					Thermistor shorts or opens during compressor running.   
					○ 
					Lighting 3 times   
					•Replace the outdoor electronic   
					control P.C. board.   
					P.C. board temperature thermistor Lighting 4 times   
					Outdoor heat exchanger tempera-   
					Lighting 9 times   
					•Refer to 10-5. "Check of   
					outdoor thermistors".   
					ture thermistor   
					•Reconnect compressor con-   
					nector.   
					•Refer to 10-5. "How to check   
					inverter/ compressor."   
					•Refer to 10-5. "Check of   
					compressor start failure".   
					•Check the stop valve.   
					Goes   
					out   
					4-time flash   
					Overcurrent   
					Once   
					28 A current flow into intelligent power module.   
					— 
					Temperature of discharge temperature thermistor exceeds •Check refrigerant circuit and   
					241 °F (116 °C), compressor stops. Compressor can   
					restart if discharge temperature thermistor reads 212 °F   
					(100 °C) or less 3 minutes later.   
					refrigerant amount.   
					•Refer to 10-5. "Check of   
					LEV".   
					5-time flash   
					Discharge temperature   
					High pressure   
					Lighting Lighting   
					— 
					— 
					The outdoor heat exchanger temperature exceeds 158 °F •Check refrigerant circuit and   
					Lighting Lighting (70 °C) during cooling or the indoor gas pipe temperature   
					exceeds 158 °F (70 °C) during heating (MUZ).   
					6-time flash   
					refrigerant amount.   
					•Check the stop valve.   
					Goes   
					out   
					The fin temperature exceeds 189 °F (87 °C) during opera-   
					•Check around outdoor unit.   
					•Check outdoor unit air pas-   
					sage.   
					•Refer to 10-5. "Check of   
					outdoor fan motor".   
					Fin temperature   
					3 times   
					4 times   
					tion.   
					7-time flash   
					— 
					— 
					Goes   
					out   
					The P.C. board temperature exceeds 158 °F (70 °C) during   
					operation.   
					P.C. board temperature   
					Failure occurs continuously 3 times within 30 seconds   
					after the fan gets started.   
					•Refer to 10-5. "Check of   
					outdoor fan motor".   
					8-time flash   
					Outdoor fan motor   
					Lighting Lighting   
					•Replace the outdoor electronic   
					control P.C. board.   
					9-time flash   
					Nonvolatile memory data   
					Lighting 5 times Nonvolatile memory data cannot be read properly.   
					○ 
					•Check refrigerant circuit and   
					refrigerant amount.   
					•Refer to 10-5. "Check of   
					LEV".   
					The frequency of the compressor is kept 80 Hz or more   
					Lighting Lighting and the discharge temperature is kept under 102 °F (39 °C)   
					for more than 20 minutes.   
					10-time flash   
					Discharge temperature   
					— 
					•Check the connecting wire   
					between outdoor electronic   
					control P.C. board and power   
					board.   
					Communication error occurs between the electronic control   
					P.C. board and power board for more than 10 seconds.   
					Lighting 6 times   
					— 
					Communication error between   
					P.C. boards   
					The communication between boards protection stop is   
					continuously performed twice.   
					○ 
					•Replace the power board.   
					A short or open circuit is detected in the current sensor   
					— 
					during compressor operating.   
					Current sensor   
					Lighting 7 times   
					11-time flash   
					Current sensor protection stop is continuously performed   
					twice.   
					○ 
					•Check the connecting wire   
					among electronic control P.C.   
					board, noise filter P.C. board   
					and power board.   
					Zero cross signal cannot be detected while the compres-   
					sor is operating.   
					— 
					Zero cross detecting circuit   
					5 times Goes out   
					The protection stop of the zero cross detecting circuit is   
					continuously performed 10 times.   
					○ 
					NOTE : Blinking patterns of this mode differ from the ones of Troubleshooting check table (10-3.).   
					23   
				LED indication (Out-   
					door P.C. board)   
					The left lamp of OPERA-   
					TION INDICATOR lamp   
					(Indoor unit)   
					Indoor/outdoor   
					unit failure mode   
					recall function   
					Abnormal point   
					(Failure mode / protection)   
					Condition   
					Correspondence   
					LED 1   
					LED 2   
					•Replace the power board.   
					A failure is detected in the operation of the converter dur-   
					ing operation.   
					Converter   
					5 times Goes out   
					5 times Goes out   
					Bus-bar voltage   
					(1)   
					The bus-bar voltage exceeds 400 V or falls to 200 V or   
					below during compressor operating.   
					11-time flash   
					— 
					Bus-bar voltage   
					(2)   
					Even if this protection stop   
					The bus-bar voltage exceeds 400 V or falls to 50 V or   
					below during compressor operating.   
					is performed continuously 3 6 times Goes out   
					times, it does not mean the   
					abnormality in outdoor power   
					system.   
					24   
				10-3. TROUBLESHOOTING CHECK TABLE   
					MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA   
					Indication   
					No. Symptom   
					Abnormal point / Condition   
					Condition   
					Correspondence   
					LED1   
					(Red)   
					LED2   
					(Yellow)   
					•Check the connection of the compressor connect-   
					ing wire.   
					•Refer to 10-5. "How to check inverter/compres-   
					sor".   
					•Refer to 10-5. "Check of compressor start failure".   
					•Check the stop valve.   
					IPM protection stop or lock protection stop is continuously   
					performed three times within 1 minute after the compressor   
					gets started, or converter protection stop or bus-bar voltage   
					protection stop is continuously performed 3 times within 3   
					minutes after start-up.   
					1 
					Lightning Twice   
					Outdoor power system   
					A short circuit is detected in the thermistor during opera-   
					tion, or an open circuit is detected in the thermistor after 10   
					minutes of compressor start-up.   
					Discharge temperature therm-   
					istor   
					2 
					3 
					Lightning 3 times   
					Lightning 4 times   
					•Refer to 10-5. "Check of outdoor thermistor".   
					Fin temperature thermistor   
					•Refer to 10-5. "Check of outdoor thermistor".   
					•Replace the outdoor electronic control P.C. board.   
					A short or open circuit is detected in the thermistor during   
					operation.   
					P.C. board temperature therm-   
					istor   
					Ambient temperature thermis- A short or open circuit is detected in the thermistor during   
					tor   
					operation.   
					Outdoor   
					A short circuit is detected in the thermistor during operation,   
					or an open circuit is detected in the thermistor after 5 minutes   
					(in cooling) and 10 minutes (in heating (MUZ)) of compressor •Refer to 10-5. "Check of outdoor thermistor".   
					start-up.   
					unit does   
					not oper-   
					ate.   
					Outdoor heat exchanger   
					temperature thermistor   
					4 
					Lightning 5 times   
					A short circuit is detected in the thermistor during operation,   
					or an open circuit is detected in the thermistor after 5 minutes   
					of compressor start-up.   
					Defrost thermistor (MUZ)   
					The communication fails between the indoor and outdoor unit •Refer to 10-5. "How to check miswiring and serial   
					5 
					6 
					7 
					Lightning 6 times   
					Lightning 7 times   
					Lightning 8 times   
					Serial signal   
					for 3 minutes.   
					signal error.   
					Nonvolatile memory data   
					Current sensor   
					The nonvolatile memory data cannot be read properly.   
					•Replace the outdoor electronic control P.C. board.   
					Current sensor protection stop is continuously performed   
					twice.   
					•Replace the power board.   
					Communication error between The communication protection stop between boards is con-   
					•Check the connecting wire between outdoor elec-   
					tronic control P.C. board and power board.   
					8 
					9 
					Lightning 11 times   
					P.C. boards   
					tinuously performed twice.   
					•Check the connecting wire among outdoor elec-   
					tronic control P.C. board, noise filter P.C. board and   
					power board.   
					The protection stop of the zero cross detecting circuit is   
					continuously performed 10 times.   
					Lightning 12 times Zero cross detecting circuit   
					IPM protection   
					Overcurrent is detected after 30 minutes of compressor start- •Reconnect compressor connector.   
					up.   
					•Refer to 10-5. "How to check inverter/compres-   
					sor".   
					10   
					11   
					Twice   
					Goes out   
					•Refer to 10-5. "Check of compressor start failure".   
					•Check the stop valve.   
					•Check the power module (PAM module).   
					Overcurrent is detected within 30 minutes of compressor   
					start-up   
					Lock protection   
					Temperature of discharge temperature thermistor exceeds   
					Discharge temperature protec- 241 °F (116 °C), compressor stops. Compressor can restart   
					•Check the amount of gas and refrigerant circuit.   
					if discharge temperature thermistor reads 212 °F (100 °C) or •Refer to 10-5. "Check of LEV".   
					3 times   
					4 times   
					Goes out   
					Goes out   
					tion   
					less 3 minutes later.   
					Fin temperature protection   
					The fin temperature exceeds 189 °F (87 °C) during operation.   
					•Check refrigerant circuit and refrigerant amount.   
					•Refer to 10-5. "Check of LEV".   
					12   
					P.C. board temperature pro-   
					tection   
					The P.C. board temperature exceeds 158 °F (70 °C) during   
					operation.   
					The outdoor heat exchanger temperature exceeds 158 °F (70   
					°C) during cooling or indoor gas pipe temperature exceeds   
					158 °F (70 °C) during heating (MUZ).   
					'Outdoor   
					unit stops   
					and restarts   
					3 minutes   
					later' is   
					repeated.   
					•Check around of gas and the refrigerant circuit.   
					•Check of stop valve.   
					13   
					5 times   
					8 times   
					Goes out High-pressure protection   
					Goes out Converter protection   
					A failure is detected in the operation of the converter during   
					operation.   
					14   
					•Replace the power board.   
					•Replace the power board.   
					The bus-bar voltage exceeds 400 V or falls to 200 V or below   
					during compressor operating.   
					Bus-bar voltage protection (1)   
					Goes out   
					15   
					9 times   
					The bus-bar voltage exceeds 400 V or falls to 50 V or below   
					during compressor operating.   
					Bus-bar voltage protection (2)   
					Failure occurs continuously three times within 30 seconds   
					after the fan gets started.   
					16   
					17   
					13 times Goes out Outdoor fan motor   
					•Refer to 10-5. "Check of outdoor fan motor".   
					•Replace the power board.   
					A short or open circuit is detected in the current sensor during   
					compressor operating.   
					Lighting   
					Lighting   
					8 times   
					Current sensor protection   
					Communication error occurs between the outdoor electronic   
					control P.C. board and power board for more than 10 sec-   
					onds.   
					Communication between P.C.   
					boards protection   
					•Check the connecting wire between outdoor elec-   
					tronic control P.C. board and power board.   
					18   
					19   
					11 times   
					•Check the connecting wire among outdoor elec-   
					tronic control P.C. board, noise filter P.C. board and   
					power board.   
					Zero cross detecting circuit   
					protection   
					Zero cross signal cannot be detected while the compressor is   
					operating.   
					Lighting   
					12 times   
					NOTE 1. The location of LED is illustrated at the right figure. Refer to 10-6.1.   
					Outdoor electronic control P.C. board(Parts side)   
					2. LED is lighted during normal operation.   
					LED2 LED1   
					Lighting   
					0.5-second ON   
					0.5-second ON   
					ON   
					OFF   
					2.5-second OFF   
					2.5-second OFF   
					The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF.   
					(Example) When the flashing frequency is “2”.   
					25   
				Indication   
					No. Symptom   
					20   
					Abnormal point / Condition   
					Primary current protection   
					Condition   
					The input current exceeds 15 A.   
					Correspondence   
					LED1   
					(Red)   
					LED2   
					(Yellow)   
					•These symptoms do not mean any abnormality of   
					the product, but check the following points.   
					•Check if indoor filters are clogged.   
					•Check if refrigerant is short.   
					•Check if indoor/outdoor unit air circulation is short   
					cycled.   
					Once   
					Lighting   
					Lighting   
					Secondary current protection The current of the compressor exceeds 15 A.   
					High-pressure protection   
					(MUZ)   
					The indoor gas pipe temperature exceeds 113 °F (45 °C) dur-   
					ing heating.   
					21   
					Twice   
					The indoor gas pipe temperature falls 37 °F (3 °C) or below   
					during cooling.   
					Defrosting in cooling   
					•Check refrigerant circuit and refrigerant amount.   
					•Refer to 10-5. "Check of LEV".   
					•Refer to 10-5. "Check of outdoor thermistors".   
					Discharge temperature protec- The discharge temperature exceeds 212 °F (100 °C) during   
					22   
					23   
					3 times   
					4 times   
					Lighting   
					Lighting   
					Outdoor   
					unit oper-   
					ates.   
					tion   
					operation.   
					The frequency of the compressor is kept 80 Hz or more and   
					the discharge temperature is kept under 102 °F (39 °C) for   
					more than 20 minutes.   
					Low discharge temperature   
					protection   
					•Refer to 10-5. "Check of LEV".   
					•Check refrigerant circuit and refrigerant amount.   
					•This symptom does not mean any abnormality of   
					the product, but check the following points.   
					Cooling high-pressure protec- The outdoor heat exchanger temperature exceeds 136 °F (58 •Check if indoor filters are clogged.   
					24   
					5 times   
					Lighting   
					tion   
					°C) during operation.   
					•Check if refrigerant is short.   
					•Check if indoor/outdoor unit air circulation is short   
					cycled.   
					25   
					26   
					9 times   
					Lighting   
					Lighting Inverter check mode   
					Lighting Normal   
					The unit is operated with emergency operation switch.   
					– 
					– 
					– 
					Outdoor   
					unit oper-   
					ates   
					26   
				10-4. TROUBLE CRITERION OF MAIN PARTS   
					MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA   
					Part name   
					Check method and criterion   
					Figure   
					Defrost thermistor   
					(RT61) (MUZ)   
					Measure the resistance with a tester.   
					Ambient temperature   
					thermistor (RT65)   
					Refer to 10-6. “Test point diagram and voltage”, 1. “Outdoor electron-   
					ic control P.C. board”, the chart of thermistor.   
					Outdoor heat ex-   
					changer temperature   
					thermistor (RT68)   
					Discharge tem-   
					perature thermistor   
					(RT62)   
					Measure the resistance with a tester. Before measurement, hold the   
					thermistor with your hands to warm it up.   
					Refer to 10-6. “Test point diagram and voltage”, 1. “Outdoor electron-   
					ic control P.C. board”, the chart of thermistor.   
					Fin temperature   
					thermistor (RT64)   
					Measure the resistance between terminals using a tester.   
					(Winding temperature : 14 ~ 104 °F (-10 ~ 40 °C))   
					W 
					RED   
					Compressor   
					Normal   
					V 
					WHT   
					U 
					BLK   
					1.24 ~ 1.53 Ω   
					Measure the resistance between lead wires using a tester.   
					(Part temperature : 14 ~ 104 °F (-10 ~ 40 °C))   
					RED   
					(W)   
					U 
					Color of lead wire   
					RED – BLK   
					BLK – WHT   
					WHT – RED   
					Normal   
					WHT   
					BLK   
					Outdoor fan motor   
					R. V. coil (MUZ)   
					(V)   
					(U)   
					V 
					13 ~ 16 Ω   
					W 
					Measure the resistance using a tester.   
					(Part temperature : 14 ~ 104 °F (-10 ~ 40 °C))   
					Normal   
					1.20 ~ 1.55 kΩ   
					Measure the resistance using a tester.   
					(Part temperature : 14 ~ 104 °F (-10 ~ 40 °C))   
					WHT   
					RED   
					ORN   
					LEV   
					Color of lead wire   
					WHT – RED   
					RED – ORN   
					YLW – BRN   
					BRN – BLU   
					Normal   
					Linear expansion   
					valve   
					38 ~ 50 Ω   
					YLW BRN BLU   
					27   
				10-5. TROUBLESHOOTING FLOW   
					OPERATION / INDICATOR lamp flashes 5-times.   
					Outdoor unit does not operate.   
					A How to check inverter/ compressor   
					Disconnect the terminal of the compressor. 3 minutes after turn-   
					ing on the power supply, start EMERGENCY OPERATION.   
					•After the outdoor fan starts running, wait for 1 minute or more   
					before measuring the voltage.   
					•The output voltage values have the tolerance of ±20 %.   
					Measure the voltage between each lead wire leading   
					to the compressor.   
					U (BLK) - V (WHT)   
					V (WHT) - W (RED)   
					No   
					W (RED) - U (BLK)   
					Is voltage output on right table?   
					Yes   
					Is output balanced?   
					Yes   
					No   
					No   
					Is the input voltage to the outdoor electronic control   
					P.C. board 370 V or more?   
					Replace the power board.   
					Replace the compressor.   
					Yes   
					Turn off power supply of indoor and outdoor unit, and   
					measure the compressor winding resistance between   
					the compressor terminals.   
					No   
					Is the resistance between each terminal normal?   
					Yes   
					Reconnect the lead wire of compressor, and turn on power   
					supply to indoor and outdoor unit.   
					3 minutes later, starts EMERGENCY OPERATION.   
					Clarify the causes by counting time until the inverter stops.   
					0 to 10 seconds: compressor rare short   
					10 to 60 seconds: compressor lock   
					60 seconds to 5 minutes: refrigerant circuit defective   
					5 minutes or more: normal   
					28   
				OPERATION INDICATOR lamp flashes 6-times.   
					Thermistor is abnormal.   
					B Check of outdoor thermistors   
					Disconnect the connector of thermistor in the outdoor P.C. board (see   
					below table), and measure the resistance of thermistor.   
					Replace the thermistor except RT64.   
					When RT64 is abnormal, replace the   
					outdoor power board.   
					Is the thermistor normal? (Refer to 10-6.1.)   
					No   
					Yes   
					Reconnect the connector of thermistor.   
					Turn ON the power supply and press EMERGENCY OPERATION switch.   
					Does the unit operate for 10 minutes or more   
					without showing thermistor abnormality?   
					Replace the outdoor power board.   
					No   
					Yes   
					OK.   
					(Cause is poor contact.)   
					Thermistor   
					Defrost (MUZ)   
					Discharge temperature   
					Outdoor heat exchanger temperature RT68   
					Ambient temperature   
					Fin temperature   
					Symbol   
					RT61   
					RT62   
					Connector, Pin No.   
					Board   
					Between CN661 pin1 and pin2   
					Between CN661 pin3 and pin4   
					Between CN661 pin7 and pin8   
					Between CN663 pin1 and pin2   
					Between CN3 pin1 and pin2   
					Outdoor electronic control P.C. board   
					Outdoor power board   
					RT65   
					RT64   
					29   
				The cooling operation or heating operation does not operate.   
					C Check of R.V. coil   
					MUZ-D30/36   
					• Heating operation does not work.   
					1. Disconnect the lead wire leading to the compressor.   
					2. 3 minutes after turning on the power supply, start EMERGENCY   
					OPERATION in HEAT mode.   
					Is there voltage of 208 / 230 VAC between pin1   
					and pin 2 at connector CN912?   
					1. Turn off power supply of indoor and outdoor unit, and discon-   
					nect the connector CN781 in the outdoor electronic control P.C.   
					board.   
					2. 3 minutes after turning ON the power supply, start EMER-   
					GENCY OPERATION in HEAT mode.   
					No   
					Yes   
					Turn OFF power supply of indoor and outdoor unit.   
					Disconnect the connec-   
					tor CN912 in noise filter   
					P.C. board. Is there normal   
					resistance to R.V. coil?   
					Is there voltage 12 VDC be-   
					Replace the electronic   
					tween the connector CN781   
					Replace the R.V. coil.   
					No   
					control P.C. board.   
					No   
					pin 5 (+) and pin 3 (-)?   
					Yes   
					Yes   
					Replace the noise filter P.C. board.   
					Replace the 4-way valve.   
					• Cooling operation does not work.   
					If the connector CN912 is not   
					1. Disconnect the lead wire leading to the compressor.   
					2. 3 minutes after turning on the power supply, start EMERGENCY   
					OPERATION in COOL mode.   
					connected or R.V. coil is open,   
					voltage occurs between terminals   
					even when the control is OFF.   
					Is there voltage of 208 / 230 VAC between pin1   
					and pin 2 at connector CN912?   
					Replace the 4-way valve.   
					No   
					1. Turn OFF power supply of indoor and outdoor unit, and   
					disconnect the connector CN781 in the outdoor electronic   
					control P.C. board.   
					2. 3 minutes after turning ON the power supply, start EMER-   
					GENCY OPERATION in COOL mode.   
					Is there voltage 12 VDC between the connector   
					CN781 pin 5 (+) and pin 3 (-)?   
					Replace the noise filter P.C. board.   
					No   
					Yes   
					Replace the outdoor electronic control P.C. board.   
					30   
				Fan motor does not operate or stops operating shortly after starting the operation.   
					D Check of outdoor fan motor   
					Check the connection between the   
					connector CN931 and CN932.   
					Is the resistance between each ter-   
					minal of outdoor fan motor normal?   
					(Refer to 10-4.)   
					Yes   
					No   
					Disconnect CN932 from outdoor electronic control P.C. board,   
					and turn on the power supply.   
					Rotate the outdoor fan motor manually and measure the voltage   
					of CN931.   
					Between 1(+) and 5(-)   
					Between 2(+) and 5(-)   
					Between 3(+) and 5(-)   
					(Fixed to either 5 or 0 VDC)   
					No   
					Does the voltage between each terminal become 5 VDC   
					and 0 VDC repeatedly?   
					Yes   
					Does the outdoor fan motor rotate smoothly?   
					Yes   
					No   
					Replace the outdoor DC fan motor.   
					Replace the outdoor electronic control P.C. board.   
					Outdoor unit does not operate.   
					E Check of power supply   
					Check the connecting of parts of main power   
					supply circuit.   
					Turn ON power supply.   
					Is there voltage of 208 / 230 VAC in the   
					power supply terminal block?   
					Check the power supply cable.   
					Replace the noise filter P.C. board.   
					Replace the reactor.   
					No   
					No   
					No   
					No   
					Yes   
					Is the output voltage from the noise filter P.C.   
					board 208 / 230 VAC?   
					Yes   
					Is the input voltage to the power board 208 /   
					230 VAC?   
					Yes   
					Is the input voltage to the outdoor electronic   
					control P.C. board 294 / 325 VDC?   
					Replace the power board.   
					Yes   
					Replace the outdoor electronic control P.C. board.   
					31   
				F Check of compressor start failure   
					Confirm that 1~4 is normal.   
					•Electrical circuit check   
					1.Contact of lead wire leading to compressor   
					2.Output voltage of the outdoor electronic control P.C. board and balance of them   
					(See 10-5. )   
					3.Direct current voltage to the outdoor electronic control P.C. board   
					4.Voltage between outdoor terminal block S1-S2   
					Check the refrigerant circuit.   
					Check the stop valve.   
					Does the compressor run for 10 seconds or   
					more after it starts?   
					Yes   
					No   
					No   
					After the compressor is heated with a drier,   
					Replace the compressor.   
					does the compressor start?   
					1 
					Yes   
					1 
					Compressor start failure. Activate pre-heat control.   
					(Refer to 9-1. "PRE-HEAT CONTROL")   
					Heat the compressor with   
					a drier for about 20 minutes.   
					Do not recover refrigerant   
					gas while heating.   
					Heating part   
					When cooling, heat exchanger of non-operating indoor unit frosts.   
					When heating, non-operating indoor unit gets warm.   
					G Check of LEV   
					Turn ON power supply to the outdoor unit after checking   
					LEV coil is mounted to the LEV body securely.   
					Is "click - click" sound heard?   
					Or, do you feel vibration of the LEV coil with a hand?   
					Normal   
					Yes   
					Yes   
					No   
					Disconnect the connector CN795.   
					Is there normal resistance to LEV coil?   
					Replace the outdoor electronic   
					control P.C. board.   
					No   
					Replace the LEV coil.   
					32   
				• Unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch.   
					Indoor unit does not operate.   
					• OPERATION INDICATOR lamp flashes ON and OFF in every 0.5 seconds.   
					Outdoor unit doesn’t operate.   
					H How to check miswiring and serial signal error   
					Turn OFF the power supply.   
					Is there rated voltage in the   
					Check the power supply.   
					power supply?   
					No   
					Yes   
					Turn ON the power supply.   
					Is there rated voltage between   
					outdoor terminal block S1 and   
					S2?   
					Yes   
					Check the wiring.   
					No   
					Press EMERGENCY OPERATION switch once.   
					Does the left lamp of OPERATION INDICA-   
					TOR lamp light up? <Confirmation of the   
					power to the indoor unit>   
					No   
					No   
					Yes   
					Is there any miswiring, poor   
					contact, or wire disconnec-   
					tion of the indoor/outdoor   
					connecting wire?   
					Is serial signal error indicated 6 minutes later?   
					Yes   
					Correct them.   
					Yes   
					Is fuse (F65) broken?   
					No   
					A 
					Turn OFF the power supply.   
					Check once more if the indoor/outdoor   
					connecting wire is not miswiring.   
					B 
					1. Miswiring may damage indoor electronic control P.C.   
					board during the operation.   
					Be sure to confirm the wiring is correct before the opera-   
					tion starts.   
					Short-circuit outdoor terminal block S2   
					and S3.   
					1 
					3. Be sure to check this within 3 minutes after turning ON.   
					After 3 minutes, LED blinks 6 times. Even when the   
					inverter P.C. board or the outdoor electronic control P.C.   
					board is normal, LED blinks 6 times after 3 minutes.   
					Turn ON the power supply.   
					Outdoor electronic control P.C. board   
					(Parts side)   
					LED2 LED1   
					Does the LED on the inverter P.C. board or   
					the outdoor electronic control P.C. board   
					repeat "3.6-second-OFF and 0.8-second-   
					Replace the inverter P.C. board or   
					the outdoor electronic control P.C. board.   
					2 
					No   
					(Lighted   
					or not   
					ON quick blinking"?   
					3 
					Lighted Blinking   
					2. Be careful to the residual   
					voltage of smoothing capacitor.   
					Yes   
					lighted)   
					Turn OFF the power supply.   
					Remove the short-circuit between   
					outdoor terminal block S2 and S3.   
					Turn ON the power supply.   
					Is there amplitude of 10 to 20 VDC   
					between outdoor terminal block S2 and   
					S3? <Confirmation of serial signal>   
					Yes   
					Is there any error of the in-   
					Replace the indoor/   
					outdoor connecting   
					wire.   
					door/outdoor connecting wire,   
					such as the damage of the wire,   
					intermediate connection, poor   
					contact to the terminal block?   
					No   
					A 
					No   
					Yes   
					• Turn OFF inverter-controlled lighting   
					equipment.   
					• Turn OFF the power supply and then   
					turn ON again.   
					• Press EMERGENCY OPERATION   
					switch.   
					Is there any error of the in-   
					door/outdoor connecting wire,   
					such as the damage of the wire,   
					intermediate connection, poor   
					contact to the terminal block?   
					No   
					Is there rated voltage between   
					indoor terminal block S1 and S2?   
					<Confirmation of power voltage>   
					Replace the indoor/   
					outdoor connecting   
					wire.   
					• Reinstall   
					No   
					Yes   
					either the unit   
					or the light   
					each other   
					Yes   
					away.   
					Is serial signal   
					error indicated 6   
					minutes later?   
					• Attach a filter   
					on remote   
					control   
					No   
					Yes   
					Replace the indoor electronic control P.C. board.   
					receiving   
					Be sure to release the failure-mode recall function   
					after checking.   
					section of the   
					indoor unit.   
					B 
					33   
				The operation frequency does not go up from lowest frequency.   
					I Check of HPS   
					1. Disconnect the connector CN681 in the electronic control P.C. board.   
					2. Check the resistance of HPS 1 minute after the outdoor unit power supply was turned OFF.   
					Check the resistance between each terminal.   
					Replace HPS.   
					Infinity   
					0 Ω   
					Reconnect CN681.   
					Turn ON power supply to the indoor and outdoor unit.   
					3 minutes later, start EMERGENCY OPERATION.   
					Is HPS protection displayed immediately after   
					compressor starts?   
					Replace the outdoor electronic   
					control P.C. board.   
					Yes   
					No   
					Normal   
					34   
				J Electromagnetic noise enters into TV sets or radios   
					Is the unit grounded?   
					Yes   
					Ground the unit.   
					No   
					Is the distance between the antennas   
					and the indoor unit within 9.91 ft., or is   
					the distance between the antennas and   
					the outdoor unit within 9.91 ft.?   
					Extend the distance between the antennas and   
					the indoor unit, and/or the antennas and the   
					outdoor unit.   
					Yes   
					No   
					Is the distance between the TV sets or   
					radios and the indoor unit within 3.28   
					ft., or is the distance between the TV   
					sets or radios and the outdoor unit   
					within 9.91 ft.?   
					Extend the distance between the TV sets and/or   
					radios and the indoor unit, or the TV sets or   
					radios and the outdoor unit.   
					Yes   
					No   
					Are the antennas damaged?   
					Is the coaxial cable damaged?   
					Is there any poor contact in the anten-   
					na wiring?   
					Replace or repair the antenna.   
					Replace or repair the coaxial cable.   
					Yes   
					Yes   
					No   
					Is the indoor/outdoor connecting wire of   
					the air conditioner and the wiring of the   
					antennas close?   
					Extend the distance between the indoor/outdoor   
					connecting wire of the air conditioner and the wir-   
					ing of the antennas.   
					No   
					Even if all of the above conditions are fulfilled, the electromagnetic noise may enter, depending on the electric field strength   
					or the installation condition (combination of specific conditions such as antennas or wiring).   
					Check the followings before asking for service.   
					1. Devices affected by the electromagnetic noise   
					TV sets, radios (FM/AM broadcast, shortwave)   
					2. Channel, frequency, broadcast station affected by the electromagnetic noise   
					3. Channel, frequency, broadcast station unaffected by the electromagnetic noise   
					4. Layout of ;   
					indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring from antennas, receiver   
					5. Electric field intensity of the broadcast station affected by the electromagnetic noise   
					6. Presence or absence of amplifier such as booster   
					7. Operation condition of air conditioner when the electromagnetic noise enters in   
					1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic   
					noise.   
					2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for   
					power ON, and check for the electromagnetic noise.   
					3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the elec-   
					tromagnetic noise.   
					4) Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the   
					indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.   
					35   
				10-6. TEST POINT DIAGRAM AND VOLTAGE   
					1. Outdoor electronic control P.C. board   
					MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA   
					Defrost thermistor (RT61)   
					Ambient temperature thermistor (RT65)   
					Outdoor heat exchanger temperature thermistor (RT68)   
					100   
					Fin temperature thermistor (RT64)   
					Discharge temperature thermistor (RT62)   
					200   
					180   
					160   
					140   
					120   
					100   
					80   
					700   
					600   
					500   
					400   
					300   
					200   
					100   
					0 
					90   
					80   
					70   
					60   
					50   
					40   
					30   
					20   
					10   
					0 
					60   
					40   
					20   
					0 
					32 50 68 86 104 122 140 158 176   
					32   
					50   
					68   
					86 104 122 140 176 194 122 212 230 248   
					Temperature (°F)   
					Temperature (°F)   
					-4   
					14   
					32   
					50   
					68   
					86 104   
					Temperature (°F)   
					LED 1   
					LED 2   
					CN801   
					294 ~ 370   
					VDC   
					Input   
					F801   
					FUSE   
					3.15 A / 250 V   
					CN601   
					( 
					( 
					208/230 VAC   
					60 Hz   
					for indoor   
					5~10 VDC   
					Input   
					( 
					CN681   
					High pressure switch   
					36   
				2. Noise filter P.C. board   
					MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA   
					CN901   
					To electronic   
					control P.C.   
					board   
					CN902   
					To power   
					board   
					CN903   
					To power   
					board   
					208 / 230 VAC   
					60 Hz   
					Input   
					MUZ   
					CN912   
					R.V. coil   
					208 / 230 VAC   
					60 Hz   
					{ 
					Output   
					208 / 230 VAC   
					60 Hz   
					Output   
					{ 
					CN61   
					F64 FUSE   
					2 A / 250 V   
					NR64 VARISTOR   
					37   
				3. Outdoor power board   
					MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA   
					Connect to the compressor   
					Voltage among phases: 180 V   
					Connect to the earth   
					294-370 VDC   
					CN2   
					Output   
					(Red)   
					Connect to the controller board   
					(+)1-5(–): Signal transmission   
					(To electronic control P.C. board)   
					5 VDC pulse wave   
					(+)   
					(–)   
					1 
					3 
					(+)2-5(–): Zero cross signal   
					3-4 : Not used   
					(White)   
					(+)6-5(–): 15 V   
					(+)7-5(–): 15 V   
					CN3   
					Fin temperature thermistor RT64   
					Signal reception (From electronic   
					control P.C. board)   
					) 
					5 VDC pulse wave   
					CN5   
					Primary current detection   
					(Connect to the noise filter)   
					38   
				11   
					DISASSEMBLY INSTRUCTIONS   
					<"Terminal with locking mechanism" Detaching points>   
					The terminal which has the locking mechanism can be detached as shown below.   
					There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism.   
					The terminal without locking mechanism can be detached by pulling it out.   
					Check the shape of the terminal before detaching.   
					(1) Slide the sleeve and check if there is a locking lever or not.   
					(2) The terminal with this connector has the   
					locking mechanism.   
					Sleeve   
					ꢀSlide the sleeve.   
					ꢀHold the sleeve, and   
					ꢁPull the terminal while   
					pushing the locking   
					pull out the terminal   
					slowly.   
					Locking lever   
					lever.   
					Connector   
					MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA   
					OPERATING PROCEDURE   
					PHOTOS   
					1. Removing the cabinet   
					Photo 1   
					(1) Remove the screws of the service panel.   
					(2) Remove the screws of the top panel.   
					(3) Remove the screw of the valve cover.   
					(4) Remove the service panel.   
					Screw of   
					the top   
					panel   
					(5) Remove the top panel.   
					(6) Remove the valve cover.   
					(7) Remove the screws of the cabinet.   
					(8) Remove the cabinet.   
					(9) Remove the screws of the back panel.   
					(10) Remove the back panel.   
					Screws   
					of the   
					cabinet   
					Screws of the cabinet   
					Photo 2   
					Photo 3   
					Screw of the motor support   
					Screw of the service panel   
					Screws of the   
					top panel   
					Conduit plate   
					Set screws of   
					the back panel   
					Screws of   
					the back   
					panel   
					Screws   
					of the   
					cabinet   
					Screw of the   
					valve cover   
					Set screws of the back panel   
					39   
				OPERATING PROCEDURE   
					PHOTOS   
					2. Removing the inverter assembly, P.C. board and   
					power board   
					Photo 4   
					(1) Remove the top panel, cabinet, service panel and the back   
					panel. (Refer to 1.)   
					(2) Disconnect the following connectors;   
					<Electronic control P.C. board>   
					Screws of the reactor   
					CN931 and CN932 (Fan motor)   
					CN795 (LEV)   
					CN661 (Discharge temperature thermistor, defrost   
					thermistor (MUZ) and outdoor heat exchanger   
					temperature thermistor)   
					HPS   
					CN663 (Ambient temperature thermistor)   
					CN681 (High pressure switch) (MUZ)   
					<Noise filter P.C. board>   
					Discharge temperature   
					thermistor   
					CN912 (4-way valve) (MUZ)   
					<Compressor>   
					<Reactor>   
					(4) Remove the screws fixing the relay panel.   
					(5) Remove the inverter assembly.   
					(6) Disconnect all connectors and lead wires on the electronic   
					control P.C. board.   
					(7) Remove the electronic control P.C. board from the inverter   
					assembly.   
					Photo 5 (Inverter assembly)   
					(8) Remove the screws fixing the power board assembly.   
					(9) Disconnect all connectors and lead wires on the power   
					board.   
					Screws of the power board assembly   
					(10) Remove the power board from the inverter assembly.   
					(11) Disconnect all connectors and lead wires on the noise filter   
					P.C. board.   
					(12) Remove the noise filter P.C. board from the inverter   
					assembly.   
					3. Removing R.V. coil (MUZ)   
					(1) Remove the top panel, cabinet, service panel and the back   
					panel. (Refer to 1.)   
					(2) Disconnect the following connectors;   
					<Noise filter P.C. board>   
					Screws of the relay panel   
					CN912 (4-way valve)   
					(3) Remove the R.V. coil. (Photo 9)   
					Photo 6   
					Screws of the   
					relay panel   
					Propeller   
					40   
				OPERATING PROCEDURE   
					PHOTOS   
					4. Removing the defrost thermistor (MUZ), discharge   
					temperature thermistor, outdoor heat exchanger   
					temperature thermistor and ambient temperature   
					thermistor   
					Photo 7   
					Outdoor heat   
					exchanger   
					temperature   
					thermistor   
					(1) Remove the top panel, cabinet, service panel and the back   
					panel. (Refer to 1.)   
					(2) Disconnect the following connectors;   
					<Electronic control P.C. board>   
					CN661 (Discharge temperature thermistor, defrost therm-   
					istor (MUZ) and outdoor heat exchanger tem-   
					perature thermistor)   
					Ambient   
					temperature   
					thermistor   
					CN663 (Ambient temperature thermistor)   
					(3) Pull out the defrost thermistor from its holder. (Photo 7)   
					(MUZ)   
					(4) Pull out the discharge temperature thermistor from its hold-   
					er. (Photo 4)   
					(5) Pull out the outdoor heat exchanger temperature thermistor   
					from its holder. (Photo 7)   
					(6) Pull out the ambient temperature thermistor from its holder.   
					(Photo 7)   
					Defrost   
					thermistor   
					(for MUZ)   
					5. Removing outdoor fan motor   
					(1) Remove the top panel, cabinet, service panel and the back   
					panel. (Refer to 1.)   
					Photo 8   
					Screws of the outdoor fan motor   
					(2) Disconnect the following connectors;   
					<Electronic control P.C. board>   
					Propeller   
					CN931 and CN932 (Fan motor)   
					(3) Remove the propeller.   
					(4) Remove the screws fixing the outdoor fan motor.   
					(5) Remove the outdoor fan motor.   
					41   
				OPERATING PROCEDURE   
					PHOTOS   
					6. Removing the compressor and 4-way valve   
					(1) Remove the top panel, cabinet, service panel and the back   
					panel. (Refer to 1.)   
					Photo 9   
					(2) Remove the inverter assembly. (Refer to 2.)   
					(3) Remove the R.V. coil. (Refer to 3.)   
					(4) Recover gas from the refrigerant circuit.   
					NOTE: Recover gas from the pipes until the pressure   
					gauge shows 0 PSIG.   
					(5) Detach the welded part of the suction and the discharge   
					pipe connected with compressor. (Photo 9)   
					(6) Remove the compressor nuts.   
					(7) Remove the compressor.   
					(8) Detach the welded part of 4-way valve and pipe. (Photo 8)   
					Welded parts of 4-way valve   
					R.V. coil   
					Photo 10   
					Welded part of the   
					discharge pipe   
					Welded part of the   
					suction pipe   
					7. Removing the reactor   
					(1) Remove the top panel, cabinet, service panel and the back   
					panel. (Refer to 1.)   
					(2) Disconnect the reactor lead wire.   
					(3) Remove the screws of the reactor, and remove the reactor.   
					42   
				43   
				TM   
					HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN   
					Copyright 2008 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD   
					Distributed in Feb. 2008. No. OBH502 7   
					Made in Japan   
					New publication, effective Feb. 2008   
					Specifications subject to change without notice.   
				 |