Power
Generator On
Network
Fault
FGA: 809-0915
Xanbus Automatic Generator Start (AGS)
Owner’s Guide
PN: 809-0915
™
Xanbus Automatic Generator Start (AGS)
Download from Www.Somanuals.com. All Manuals Search And Download.
Trademarks
Product Number
Xantrex, Xanbus, and Smart choice for power are trademarks of Schneider
Electric Services International sprl, registered in the U.S. and other countries. Other
trademarks, registered trademarks, and product names are the property of their
respective owners and are used herein for identification purposes only.
809-0915
Contact Information
Telephone:
1 800 670 0707
Notice of Copyright
Fax:
1 800 994 7828
Xanbus Automatic Generator Start Owner’s Guide © March 2011 Xantrex
Technology USA Inc. All rights reserved. No part of this document may be
reproduced in any form or disclosed to third parties without the express written
consent of: Xantrex Technology USA Inc., 541 Roske Drive, Suite A, Elkhart,
Indiana USA 46516. Xantrex Technology USA Inc. reserves the right to revise this
document and to periodically make changes to the content hereof without obligation
or organization of such revisions or changes unless required to do so by prior
arrangement.
Web:
www.xantrex.com
Exclusion for Documentation
UNLESS SPECIFICALLY AGREED TO IN WRITING, XANTREX TECHNOLOGY USA INC. (“XANTREX”)
(A) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY
TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION;
(B) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR EXPENSES,
WHETHER SPECIAL, DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE
OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY
AT THE USER’S RISK; AND
(C) REMINDS YOU THAT IF THIS MANUAL IS IN ANY LANGUAGE OTHER THAN ENGLISH,
ALTHOUGH STEPS HAVE BEEN TAKEN TO MAINTAIN THE ACCURACY OF THE TRANSLATION, THE
ACCURACY CANNOT BE GUARANTEED. APPROVED XANTREX CONTENT IS CONTAINED WITH THE
ENGLISH LANGUAGE VERSION WHICH IS POSTED AT WWW.XANTREX.COM.
Date and Revision
March 2011 Rev D
Document Part Number
975-0082-01-01
975-0082-01-01
i
Download from Www.Somanuals.com. All Manuals Search And Download.
About This Guide
Purpose
Conventions Used
The following conventions are used in this guide.
The purpose of this Owner’s Guide is to provide explanations and
procedures for installing, troubleshooting, operating and maintaining the
Xanbus Automatic Generator Start (AGS).
Scope
STATEMENT OF HAZARD
The Guide provides safety and operating guidelines, procedures for
installing the AGS, as well as information on configuring the AGS. It also
provides information about troubleshooting the unit. It does not provide
details about configuring every Xanbus-enabled device to which the SCP
connects to within the Xanbus network. You need to consult these other
Xanbus-enabled devices’ owner’s and installation guides.
Contains statements of avoidance or strict compliance.
Failure to follow these instructions will result in death or serious
injury.
Audience
STATEMENT OF HAZARD
The Guide is intended for users and operators of the Xanbus Automatic
Generator Start (AGS). The Installation section is primarily intended for
qualified installers who need to install and configure an AGS. The installer
should have knowledge and experience in installing electrical equipment,
knowledge of the applicable installation codes, and awareness of the
hazards involved in performing electrical work and how to reduce those
hazards. A qualified technician or electrician has this knowledge and
experience.
Contains statements of avoidance or strict compliance.
Failure to follow these instructions can result in death or serious
injury.
STATEMENT OF HAZARD
Contains statements of avoidance or strict compliance.
Failure to follow these instructions can result in minor or moderate
injury.
ii
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
STATEMENT OF HAZARD
Contains statements of avoidance or strict compliance.
Failure to follow these instructions can damage the unit and/or
damage other equipment.
IMPORTANT: These notes describe things which are important for you to
know, however, they are not as serious as a danger, warning, or caution.
Related Information
You can find more information about Xantrex Technology USA Inc. as well
as its products and services at www.xantrex.com.
The product marking on the left when found imprinted on
electrical and electronic units and appliances means that you
are to refer to this guide for cautions and warnings.
975-0082-01-01
iii
Download from Www.Somanuals.com. All Manuals Search And Download.
Important Safety Instructions
IMPORTANT: READ AND SAVE THIS OWNER’S GUIDE FOR FUTURE
REFERENCE.
EXPLOSION HAZARD
This equipment is not ignition protected. To prevent fire or explosion, do
not install the unit in compartments containing flammable materials or in
locations that require ignition-protected equipment. This includes any
space containing gasoline-powered machinery, fuel tanks, as well as
joints, fittings, or other connections between components of the fuel
system.
This chapter contains important safety, operation, and installation
instructions for the Xanbus Automatic Generator Start (AGS). Each time,
before using the AGS, READ ALL instructions and cautionary markings on
or provided with the AGS and all appropriate sections of this guide.
IMPORTANT:
1. If the Xanbus Automatic Generator Start (AGS) is inoperative, see
“Warranty and Return Information” on page 38 for guidance.
Failure to follow these instructions can result in death or serious
injury.
2. The Xanbus Automatic Generator Start (AGS) contains no user-
serviceable parts. For obtaining service, see “Warranty and Return
Information” on page 38 for guidance.
SAFETY HAZARD
3. Protect the Freedom SW Automatic Generator Start from rain, snow,
spray, and water.
Disable the Xanbus Automatic Generator Start (AGS) if the generator or
vehicle equipped with the generator is in an enclosed building or area
where the generator exhaust is not vented to the outside.
4. Disable the generator’s starting circuit by disconnecting the starter
battery, spark plug, et cetera, before wiring this device.
Failure to follow these instructions can result in death or serious
injury.
5. To reduce the risk of electrical shock, put the Xantrex Xanbus system
into Standby before working on any circuits connected to it.
6. Disable the automatic starting circuit and/or disconnect the generator
from its starting battery to prevent accidental starting while
performing maintenance.
iv
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
FCC Information to the User
This equipment has been tested and found to comply with the limits for a
Class B digital device, pursuant to part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference
in a residential installation. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications.
RESTRICTIONS ON USE
The Xanbus Automatic Generator Start (AGS) shall not be used in
connection with life support systems or other medical equipment or
devices.
Failure to follow these instructions can result in death or serious
injury.
However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to
radio or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
•
•
•
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected.
•
Consult the dealer or an experienced radio/TV technician for help.
Unauthorized changes or modifications to the equipment could void the
user’s authority to operate the equipment.
975-0082-01-01
v
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Warranty and Return Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Appendix B: Relay Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction
IMPORTANT: The Xanbus Automatic Generator Start (AGS) is designed
for use in a Xanbus-enabled Freedom SW Power System only.
The Xanbus AGS requires the additional use of a Xanbus System Control
Panel (SCP) for configuration and monitoring. For details see "System
Function The Xanbus AGS continuously monitors battery voltage and
starts, or stops, the generator when battery voltage drops below or exceeds
the preset limits. It also starts the generator to assist the system’s inverter/
charger when output power demands are high.
Start and Stop Triggers The Xanbus AGS requires a source of start and
stop triggers for automatic operation. The Xanbus AGS monitors the
Xanbus network and starts or stops the generator based on the preset limits
programmed into it.
AC Panel
Freedom Sequence
Shore
Power
BATTERY
3012
C/
rge
Cha
F
ault
er
Inv
t
er
A
On
SW
erter
v
3012
In
Enable
R
eset
SW
FREEDOM
FREEDOM
System Control Panel
Automatic Generator Start
Freedom SW Inverter/Charger
Xanbus Automatic Generator Start
Xanbus System Control Panel
Inverter
Load Panel
network terminator
network terminator
Generator
AC Loads
Figure 1 Xanbus Automatic Generator Start (AGS) Basic Function
975-0082-01-01
1
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction
System Requirements
Minimum basic system components include the following:
Generator Compatibility The Xanbus AGS supports most two and
three-wire generator starters. Some manufacturers include, but are not
limited to, Onan (Quiet Diesel, gasoline, and LP), Power Tech, Generac,
Northern Lights, Fisher Panda, Westerbeke, Kohler, Honda, and Yamaha.
Check with the generator manufacturer to ensure the generator in question
includes automatic starting capabilities.
❐
❐
❐
❐
Freedom SW Series Inverter/Charger
AC Generator or DC Generator
Xanbus System Control Panel (SCP)
Xanbus Automatic Generator Start (AGS)
Xanbus System Control Panel (SCP) A Xanbus System Control Panel
(SCP) is required to configure the AGS and monitor generator starting and
stopping activity.
Network Communication Protocol The AGS uses Xanbus, a network
communications protocol developed by Xantrex, to communicate its
settings and activity to other Xanbus-enabled devices. All network
components used in the system must be Xanbus-enabled.
The Xanbus System Control Panel (SCP) also provides real-time clock
information for the AGS Quiet Time and Exercise Time features.
Network Power Supply The Xanbus AGS requires three watts of power
(maximum) to operate. This power supply is provided by the Freedom SW
Series Inverter/Charger through the Xanbus network.
Generator The generator should be a 2-wire or 3-wire generator with
Auto Start capability.
The generator should also supply a Generator Run signal. The Generator
Run signal is connected to the Xanbus AGS and used by the Xanbus AGS
to detect whether the generator is running. Some generator manufacturers
refer to this signal as the Hour Meter Signal or Switched B+.
Connecting the Generator Run signal is optional and only used for
redundancy. The Xanbus AGS requests generator voltage from the Xanbus
in addition to checking the Generator Run signal to detect if the generator is
running.
2
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction
Functions
Generator Starting Triggers
Programmable Features
The AGS can automatically start a generator in response to:
Quiet Time The AGS features a quiet time setting, which prevents the
generator starting at night or during other inconvenient periods.
•
•
•
•
a low battery voltage,
large AC loads when inverter is operating,
a thermostat signal, or
Exercise Period
During times of prolonged generator inactivity, the
AGS can be programmed to run (or “exercise”) the generator for a pre-
defined period. This ensures the generator remains operational and that the
starting battery stays charged.
a pre-programmed exercise period at a specified time of day.
Generator Stopping Triggers
Status Reporting
The AGS can automatically stop a generator in response to:
The AGS reports its operating mode, its settings, generator activity, and the
reason for generator starts to the Xanbus system. This information can be
viewed on the Xanbus System Control Panel (SCP).
•
the introduction of qualified grid power (grid power within acceptable
parameters),
high battery voltage,
battery charge stage (float or absorb stage),
reduction in AC loads when inverter is operating,
a thermostat signal, or
•
•
•
•
•
Installation Options
The AGS can be installed with an external shutdown input, a manual
generator ON/OFF switch, and an external ON/OFF indicator light.
a pre-programmed quiet time period.
The AGS can also be used to manually start and stop the generator at any
time.
975-0082-01-01
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction
Material List
The AGS ships with the following items:
AGS
unit
T
M
•
•
•
•
•
one Xanbus Automatic Generator Start (AGS) unit,
owner’s guide,
wiring harness (20-pin connector),
mounting template, and
Power
Generator On
Network
Fault
mounting screws (4).
NOTE: Keep the carton and packing material in case you need to return
the AGS for servicing.
FGA: 809-0915
Xanbus Automatic Generator Start (AGS)
wiring harness
owner’s guide and
mounting template
mounting screws
4
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction
Xanbus-Enabled Products and Accessories
Freedom SW
Inverter/Charger
Product/Accessory
Product Number
Freedom SW Series Inverter/Charger
815-2012 (2kW power rating),
815-3012 (3kW power rating)
Freedom Sequence Intelligent Power
Manager
809-0913 (four-circuit model),
809-0912 (six-circuit model)
3012
ault
F
C/
A
rge
ha
C
er
t
r
e
v
I
n
On
T
M
er
rt
SW
e
v
n
3012
I
e
s
e
t
E
n
a
b
l
e
R
SW
FREEDOM
Xanbus System Control Panel (SCP)
25-ft network cable for SCP
809-0921
809-0940
809-0942
FREEDOM
75-ft network cable for SCP
SCP
The Freedom SW Inverter/Charger is a true sine wave inverter/charger that
can be used for mobile, marine and commercial applications. The Freedom
SW Inverter/Chargers are designed to operate with a wide variety of
generators and are capable of operating in parallel with a generator for short
durations to assist with starting large loads. The Freedom SW is a
convenient combination of an inverter, multistage battery charger, and
transfer switch in one electronic device.
Freedom Sequence
power manager
25-ft cable
The Xanbus SCP provides configuration and monitoring capability for a
Xanbus system. It monitors activity throughout your power system,
displays the settings and status, as well as, adjusting the settings for each
Xanbus-enabled device.
The Freedom Sequence Intelligent Power Manager is a fully integrated
power management system that provides automatic power and load
management for use in recreational vehicles (RV) while receiving power
from a generator or shore power.
75-ft cable
975-0082-01-01
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Features
The AGS has important features on the front and back of the unit. Features
on the front of the AGS are the indicator lights for reporting statuses on
features the inputs where the AGS connects to the Xanbus system and the
20-contact wiring harness connector port (see Figure 3).
Item
1
Description
Power light (green) indicates that the AGS is receiving power from the
Xanbus network.
2
3
4
Generator On light (green) indicates that the generator is up and
running.
Network light (green) indicates that the Xanbus network is
maintaining a good connection with all Xanbus-enabled components.
Front panel features
Fault light (red) indicates the generator is experiencing a fault and
requires user attention and intervention.
1
Power
2
Generator On
3
Network
4
Fault
FGA: 809-0915
Xanbus Automatic Generator Start (AGS)
Figure 2 AGS Front Panel
6
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Features
Bottom panel features
Gener at or
XANBUS
R
!
!
CAUTION
WARNING
C
CONNECT ONLY TO
CLASS 2 ELV CIRCUITS.
SEE MANUAL.
US
CSA 107.1
Explosion hazar d.
Do n ot ins tall in
loc ation requiring
ignition pr otected
equipmen t. see
man ual .
A
UL 458
LR 86581
MARINE
Two 8-pin RJ-45 Xanbus
network ports
20-contact generator
connector port
Figure 3 AGS Bottom Panel
20-contact wiring harness
connector
EQUIPMENT DAMAGE
Figure 4 Wiring Harness Connector
Only connect the Xanbus Automatic Generator Start (AGS) to other
Xanbus-enabled devices.
Wiring Harness Connector The 20-contact connector supports a wiring
harness (supplied) that connects the AGS to a generator and thermostats.
The wiring harness also provides lines for connecting external generator
shutdown sensors or switches and external generator ON/OFF controls.
Although the cabling and connectors used in this network system are the
same as those used for Ethernet, this network is not an Ethernet system.
Equipment damage may result from attempting to connect these two
different systems.
Failure to follow these instructions can result in minor or moderate
injury.
Network Ports Each network port can accept an eight-pin RJ45 plug
attached to a Category 5 (CAT 5) Xanbus network cable. Depending on the
installation, both ports may be required.
975-0082-01-01
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Before installing the AGS, consider how and where the unit will be mounted.
Pre-plan the connection routes between the AGS, the generator, thermostats,
and the Xanbus System Control Panel (SCP).
Choosing a Location
The AGS should be installed in a location that meets the following
requirements:
Materials and Tools Required
The unit is intended for use in a dry location. The AGS
complies with UL458 Marine Supplement drip-test
requirements, but the location should be as dry as
possible.
Dry
The following materials and tools are required to complete the installation:
❐
❐
Mounting template (supplied)
Wiring harness (manufacturer part number 809-0917, supplied)
❐
❐
Four mounting screws (supplied)
#16 or #18 AWG wire (see “Wire Size and Length” on page 12)
The AGS operation is guaranteed between
-4 and 122 °F (-20 and 50 °C).
Cool
Safe
❐
Xanbus network cables or equivalent (CAT 5 or CAT 5e cable with RJ-
45 connectors wired to T568A standard.
The AGS is not ignition protected. Do not install it in
areas requiring ignition-protected equipment, such as
compartments housing gasoline engines.
❐
Two network terminators
(supplied with the Freedom SW Inverter/Charger)
Avoid excessive wire lengths and use the
recommended wire lengths and sizes (see “Wire Size
and Length” on page 12). It is more important for the
Close to
generator
❐
❐
Phillips head screwdriver
Wire cutters and wire strippers
AGS to be close to the generator than close to the
inverter, although for safety reasons, the AGS should
not be installed in the same compartment as a gasoline-
powered generator.
8
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Routing Connections
EXPLOSION HAZARD
This equipment is not ignition protected. To prevent fire or explosion, do
not install the AGS in locations that require ignition-protected equipment.
This includes any space containing gasoline-powered machinery, fuel
tanks, as well as joints, fittings, or other connections between
components of a fuel system.
20-contact
connector
Network ports
Follow all relevant instructions exactly before installing or using your
AGS.
SHOCK AND ENERGY HAZARDS
Before making any connections to the generator, ensure that the
generator’s starter is disabled and the generator’s start battery is
disconnected.
Network cables
to other Xanbus-
enabled devices
Wiring harness
(connection to
generator,
thermostats, and
external switches)
Failure to follow these instructions will result in death or serious
injury.
Figure 5 AGS External Connections
Connection Types Because the AGS will be part of a Xanbus system, it
is necessary to consider how to route two types of connections:
•
connections to the generator, thermostats, and other external devices
and switches, using the included 20-contact connector and wiring
harness.
•
connections to other Xanbus-enabled devices, using network cables.
975-0082-01-01
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Installation Overview
IMPORTANT: Because each installation varies according to the location,
the type of generator, and the overall complexity of the Xanbus system,
these instructions can offer only general guidelines for the many
installation options available.
Installing the AGS involves the following steps:
1. Mounting the unit.
2. Connecting the wiring harness to:
•
•
•
•
the generator (page 14)
Mounting the Unit
thermostats (optional) (page 29)
external shutdown switch (optional) (page 30)
external ON/OFF switch and LED (optional) (page 30)
The AGS is to be mounted vertically on a wall with the connectors facing
downwards.
To mount the AGS:
1. Hold the unit flush and square against the wall, panel, or horizontal
surface.
ELECTRICAL SHOCK HAZARD
•
If the mounting surface requires pre-drill holes for the screws, use
the supplied mounting template to mark, then drill, four holes.
Before installing the AGS as part of a pre-existing Xanbus system, put
the system in Standby in order to disable the electrical operation of
networked devices. See “Putting the AGS in Standby Mode” on page 67.
2. With a Phillips screwdriver and the supplied mounting screws, secure
each corner of the AGS to the mounting surface.
Failure to follow these instructions can result in death or serious
injury.
3. Connecting the wiring harness to the 20-contact connector on the
AGS.
4. Connecting the AGS to the Xanbus System Control Panel (SCP) and
other network-enabled devices (page 33).
10
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Wiring to the 20-contact Connector
Circuit Limitations The relay contacts in the AGS are rated at 5 A
maximum and all circuits on the 20-contact connector are rated at 30 V
maximum.
ELECTRICAL SHOCK HAZARD
Ensure that all circuits connected to the 20-contact connector comply with
the following limits:
All installation wiring should be performed by a qualified installer or
electrician.
The 20-contact connector is intended for connection to Class 2 ELV
(Extra Low Voltage) circuits only. Do not exceed the circuit limitations
specified in the following section.
Circuit Parameter
Circuit Maximum
30 V maximum
5 A maximum
Open circuit voltage (Voc)
Overcurrent protection
(fuse size for open circuit voltage up to 20 V)
Failure to follow these instructions can result in death or serious
injury.
Overcurrent protection
5 A to 3.33 A
(fuse size for open circuit voltage from 20 V to
30 V)
(100/V amps
oc
ELV Circuits ELV (Extra-Low Voltage) circuits have an open-circuit
maximum)
voltage of not more than 30 V or 42.2 VDC or peak, and are therefore
rms
not a shock hazard.
Wiring Harness Connections to the generator, thermostats, and external
ON/OFF switches are made using a wiring harness that plugs into the 20-
contact connector (see Figure 5).
Class 2 Circuits As per the US National Electrical Code (NEC) and the
Canadian Electrical Code (CEC), available power in Class 2 circuits is
limited to 100 VA, usually by current limiting by means of overcurrent
protection or series resistance. The current is limited to 5 A for circuits with
The wires on the wiring harness can be extended to meet installation
requirements. When extending the wire harness, ensure that the extension
wires are the same color as the wires on the harness.
open-circuit voltage of 20 V, and to I=100/V for circuits with open circuit
oc
voltage between 20 V and 30 V.
975-0082-01-01
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
To install the AGS using the wiring harness:
1. Connect each wire on the harness to its intended wire or contact on the
generator, thermostats, or external switches. Tape, or otherwise secure,
the unused wires to ensure they do not make unintended connections.
To generator,
thermostats, and
external switches
2. Plug the harness into the connector on the bottom panel of the AGS.
Wire Identification Each wire on the harness is identified by a number
and a color. The wire numbers are shown in Figure 6 and their colors and
functions are described in the next table.
To 20-contact
connector on AGS
Wire Size and Length Required wire sizes for the external connections
to the wiring harness are:
Figure 6 AGS Wiring Harness
0–30 ft. (9 m)
Over 30 ft. (9 m)
18 AWG
16 AWG
Wire
Number
Wiring Harness
Wire Color
Function
1
Thermostat 1 input
Thermostat 1 return
Thermostat 2 input
Thermostat 2 return
External shutdown input
External shutdown return
External manual on input
External manual off input
Yellow
When planning the routing for external connections, ensure that wire
lengths are sufficient to plug the wiring harness into the AGS once all the
external connections are complete.
2
Gray
3
Orange
4
Gray
5
White/Black
Gray
6
7
White/Green
White/Red
White/Blue
Red
8
9
External ON/OFF LED Indicator output
10
Constant 12/24 V B+ (battery positive) for External ON/
OFF/LED Indicator
12
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Wire
Number
Wiring Harness
Wire Color
Function
11
External ON/OFF/LED Indicator return (connected
internally to wire number 13)
Black
12
13
14
15
16
17
18
19
20
Generator run signal (switched B+) sense input
Generator run signal (switched B+) sense return
Relay 1 (Generator run/stop) Normally open contact
Relay 1 (Generator run/stop) Normally closed contact
Relay 1 (Generator run/stop) Common contact
Relay 2 (Generator start) Normally open contact
Relay 2 (Generator start) Common contact
Violet
Black
Blue
White/Violet
Gray
White
Gray
Relay 3 (Preheat/cool-down) Normally open contact
Relay 3 (Preheat/cool-down) Common contact
Brown
Gray
975-0082-01-01
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Wiring Requirements Either #16 or #18 AWG wire is required to
connect to the wiring harness. How many of these wires you connect and in
which combination depends on your generator type.
Connecting the Generator
Generator Types The AGS has 14 preset generator configurations, or
“Gen Types” (see “Gen Type” on page 42). After installing the hardware, it
will be necessary to select one of these Gen Types from the AGS
Configuration Menu on the Xanbus System Control Panel (SCP).
EQUIPMENT DAMAGE
Before connecting the AGS to your generator, read the Generator Type
descriptions in this section and consult your generator manufacturer to
ensure that Gen Type settings and connections are compatible with your
generator. Damage to the generator can result from selecting an incorrect
Gen Type and following the connection diagram for an incorrect Gen
Type when connecting the AGS to the generator. Xantrex assumes no
responsibility or liability for loss or damage that might arise out of the use
of this information.
IMPORTANT: Put the system in Standby BEFORE changing the "Gen
Type". See “Putting the AGS in Standby Mode” on page 67.
The following section describes the preset generator configurations and
provides diagrams for connecting the wiring harness to the generator’s start
wiring.
Failure to follow these instructions can damage the unit and/or
damage other equipment.
IMPORTANT: For an explanation of the terminology used in the
following section, refer to Appendix 1, “Appendix A: Generator Auto
Start Requirements and Types”. For more information about AGS
internal relay activity and timing, see Appendix 1, “Appendix B: Relay
To connect the AGS to a generator, identify the start wiring configuration of
the generator to be used. Generators must be auto-start capable, and
generators equipped with remote operation connections are ideal.
IMPORTANT: Connecting the B+ Gen Run signal is optional. It the
B+ Gen Run signal is not connected, it may be necessary to adjust the
Gen Run Signal hold time parameter on the AGS. See “Gen Run Hold
Time” on page 57.
If the generator is equipped for remote operation, examine the wiring of the
remote cable and connector (or read the generator’s documentation, if
available) and identify the following wires:
•
•
•
•
Ground
Start
Stop
Generator run signal, also known as the Hour Meter or Switched B+
(battery positive)
14
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Type 1
Type 1 is a three-wire GlowStop configuration recommended for “three-
wire” generators with glow plugs that need to be operated before a start is
attempted.
Relay Function
Crank retry time
Gen Cool Down
Gen Spin Down
Preset Configuration Setting
30 s
30 s
3 s
AGS Harness W ires
Generator W ires
Shutdown bypass time
Start tries
0 s
3
GENERATOR RUN SIGNAL
12
13
GENERATOR RUN SIGNAL RETURN
5A fuse
5A fuse
14
PREHEAT/STOP
Relay 1
16
17
Relay 2
START
18
For additional information, see “Circuit Limitations” on page 11.
Figure 7 Type 1 Connection Diagram
Relay Function
Relay 1 mode
Preset Configuration Setting
GlowStop
No function
0.5 s
Relay 3 mode
Gen Run signal hold time
Preheat time
20 s
Preheat to crank delay
Crank time
1 s
15 s
975-0082-01-01
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Type 2
Type 2 is a three-wire GlowStop configuration recommended for “three-
wire” generators that don’t require a dedicated preheat signal. In this
configuration, the start signal is applied for longer because the generator
does its own preheat and cranking while the start signal is applied.
Relay Function
Crank time
Preset Configuration Setting
30 s
40 s
30 s
3 s
Crank retry time
Gen Cool Down
Gen Spin Down
Shutdown bypass time
Start tries
AGS Harness W ires
Generator W ires
0 s
12
13
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
3
5A fuse
5A fuse
14
STOP/PREHEAT
START
Relay1
16
17
Relay2
18
For additional information, see “Circuit Limitations” on page 11.
Figure 8 Type 2 Connection Diagram
Relay Function
Relay 1 mode
Preset Configuration Setting
GlowStop
No function
0.5 s
Relay 3 mode
Gen Run signal hold time
Preheat time
0 s
Preheat to crank delay
0 s
16
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Type 3
Type 3 is a three-wire GlowStop with shutdown bypass configuration. The
configuration shown in Figure 9 uses a shutdown bypass output to
temporarily disable the generator’s low oil pressure shutdown functionality
during cranking. Generators with this functionality often have a manual
means of disabling it during cranking.
Relay Function
Preset Configuration Setting
Preheat to crank delay
Crank time
0 s
15 s
30 s
30 s
3 s
Crank retry time
Gen Cool Down
Gen Spin Down
Shutdown bypass time
Start tries
AGS Harness W ires
Generator W ires
10 s
3
12
13
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
PREHEAT
STOP
BYPASS SHUTDOWN
5A fuse
5A fuse
14
Relay 1
16
17
Relay 2
START
18
For additional information, see “Circuit Limitations” on page 11.
Figure 9 Type 3 Connection Diagram
Relay Function
Relay 1 mode
Preset Configuration Setting
GlowStop/Shutdown bypass
Relay 3 mode
Preheat/Shutdown bypass
Gen Run signal hold time
Preheat time
0.5 s
20 s
975-0082-01-01
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Type 4
Type 4 is a three-wire StartStop configuration that uses relay 3 to provide a
60-second preheat signal.
Relay Function
Preheat to crank delay
Crank time
Preset Configuration Setting
5 s
15 s
15 s
30 s
3 s
AGS Harness W ires
Generator W ires
Crank retry time
Gen Cool Down
Gen Spin Down
Shutdown bypass time
Start tries
12
13
14
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
STOP/PREHEAT
5A fuse
5A fuse
Relay 1
16
17
18
19
20
0 s
START
3
Relay 2
Relay 3
5A fuse
FUEL PRIME (PREHEAT)
12V GENERATOR BATTERY+
For additional information, see “Circuit Limitations” on page 11.
Figure 10 Type 4 Connection Diagram
Relay Function
Relay 1 mode
Preset Configuration Setting
StartStop
Preheat
10 s
Relay 3 mode
Gen Run signal hold time
Preheat time
60 s
18
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Type 5
Type 5 is a three-wire StartStop configuration that uses relay 3 to provide a
15-second preheat signal.
Relay Function
Crank time
Preset Configuration Setting
15 s
15 s
30 s
3 s
Crank retry time
Gen Cool Down
Gen Spin Down
AGS Harness W ires
Generator W ires
12
13
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
STOP/PREHEAT
Shutdown bypass time
Start tries
0 s
3
5A fuse
5A fuse
14
Relay 1
16
17
Relay 2
START
18
5A fuse
FUEL PRIME (PREHEAT)
19
Relay 3
12V GENERATOR BATTERY+
20
For additional information, see “Circuit Limitations” on page 11.
Figure 11 Type 5 Connection Diagram
Relay Function
Relay 1 mode
Preset Configuration Setting
StartStop
Preheat
2 s
Relay 3 mode
Gen Run signal hold time
Preheat time
15 s
Preheat to crank delay
2 s
975-0082-01-01
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Type 6
Type 6 is a three-wire GlowStop configuration that has a normally closed
Run/Stop contact.
Relay Function
Crank retry time
Gen Cool Down
Gen Spin Down
Shutdown bypass time
Start tries
Preset Configuration Setting
30 s
30 s
3 s
0 s
3
AGS Harness W ires
Generator W ires
12
13
14
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
PREHEAT
5A fuse
5A fuse
15
STOP
Relay 1
16
5A fuse
START
17
Relay 2
18
For additional information, see “Circuit Limitations” on page 11.
Figure 12 Type 6 Connection Diagram
Relay Function
Relay 1 mode
Preset Configuration Setting
GlowStop
No function
0.5 s
Relay 3 mode
Gen Run signal hold time
Preheat time
10 s
Preheat to crank delay
Crank time
1 s
15 s
20
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Type 7
Type 7 will work with both two-wire and three-wire run mode configurations
that require a preheat signal before cranking. This Gen Type setting is suitable
for generators with an automatic engine cranking control system (two-wire)
and generators that require that the AGS control their starter separately (three-
wire).
Relay Function
Relay 1 mode
Relay 3 mode
Gen Run signal hold time
Preheat time
Preset Configuration Setting
Run
No function
0.5 s
20 s
1 s
AGS Harness W ires
Generator W ires
Preheat to crank delay
Crank time
12
13
14
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
RUN
15 s
30 s
30 s
3 s
Crank retry time
Gen Cool Down
Gen Spin Down
Shutdown bypass time
Start tries
5A fuse
Relay 1
16
For additional information, see “Circuit Limitations” on page 11.
0 s
3
Figure 13 Type 7 Connection Diagram (two-wire)
AGS Harness W ires
Generator W ires
12
13
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
RUN
5A fuse
5A fuse
14
Relay1
16
START
17
Relay2
18
For additional information, see “Circuit Limitations” on page 11.
Figure 14 Type 7 Connection Diagram (three-wire)
975-0082-01-01
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Type 8
Type 8 will work with both two-wire and three-wire run mode
configurations. Type 8 is identical to Type 7 except that it provides no
preheat signal before cranking.
Relay Function
Relay 1 mode
Preset Configuration Setting
Run
No function
0.5 s
0 s
Relay 3 mode
AGS Harness W ires
Generator W ires
Gen Run signal hold time
Preheat time
12
13
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
RUN
5A fuse
14
Preheat to crank delay
Crank time
0 s
Relay 1
16
15 s
30 s
30 s
3 s
For additional information, see “Circuit Limitations” on page 11.
Crank retry time
Gen Cool Down
Gen Spin Down
Shutdown bypass time
Start tries
Figure 15 Type 8 Connection Diagram (two-wire)
0 s
AGS Harness W ires
Generator W ires
3
12
13
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
RUN
5A fuse
5A fuse
14
Relay1
16
START
17
Relay2
18
For additional information, see “Circuit Limitations” on page 11.
Figure 16 Type 8 Connection Diagram (three-wire)
22
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Type 9
Type 9 is a StartStop mode configuration with shutdown bypass
functionality on relay 3.
Relay Function
Crank time
Preset Configuration Setting
15 s
30 s
30 s
3 s
Crank retry time
Gen Cool Down
Gen Spin Down
AGS Harness W ires
Generator W ires
12
13
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
STOP
5A fuse
5A fuse
14
Relay 1
Shutdown bypass time
Start tries
5 s
3
16
17
Relay 2
START
18
5A fuse
FUEL PRIME (PREHEAT)
19
Relay 3
12V GENERATOR BATTERY+
20
For additional information, see “Circuit Limitations” on page 11.
Figure 17 Type 9 Connection Diagram
Relay Function
Preset Configuration Setting
Relay 1 mode
StartStop
Relay 3 mode
Shutdown Bypass
Gen Run signal hold time
Preheat time
0.5 s
0 s
Preheat to crank delay
0 s
975-0082-01-01
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Type 10
Type 10 is a StartStop mode configuration with no preheat signal or
shutdown bypass functionality.
Relay Function
Preset Configuration Setting
Gen Cool Down
Gen Spin Down
Shutdown bypass time
Start tries
30 s
3 s
0 s
3
AGS Harness W ires
Generator W ires
GENERATOR RUN SIGNAL
12
13
GENERATOR RUN SIGNAL RETURN
5A fuse
5A fuse
14
STOP
Relay 1
16
17
Relay 2
START
18
For additional information, see “Circuit Limitations” on page 11.
Figure 18 Type 10 Connection Diagram
Relay Function
Preset Configuration Setting
Relay 1 mode
StartStop
No function
0.5 s
Relay 3 mode
Gen Run signal hold time
Preheat time
0 s
Preheat to crank delay
Crank time
0 s
15 s
Crank retry time
30 s
24
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Type 11
Type 11 is a two-wire run mode configuration. It requires only two wires
and one relay to control the generator. Relay 1 closes momentarily once to
start the generator, and closes momentarily again to stop the generator.
Relay Function
Gen Spin Down
Preset Configuration Setting
3 s
Shutdown bypass time
Start tries
0 s
3
AGS Harness W ires
Generator W ires
12
13
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
RUN
5A fuse
14
Relay 1
16
For additional information, see “Circuit Limitations” on page 11.
Figure 19 Type 11 Connection Diagram
Relay Function
Relay 1 mode
Preset Configuration Setting
MomentaryRun
Relay 3 mode
No function
0.5 s
0 s
Gen Run signal hold time
Preheat time
Preheat to crank delay
Crank time
0 s
10 s
Crank retry time
Gen Cool Down
15 s
30 s
975-0082-01-01
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Type 12
Type 12 is a three-wire GlowStop configuration recommended for “three-
wire” generators that don’t require a dedicated preheat signal. In this
configuration, the start signal is applied for longer because the generator
does its own preheat and cranking while the start signal is applied.
Relay Function
Crank retry time
Gen Cool Down
Gen Spin Down
Shutdown bypass time
Start tries
Preset Configuration Setting
40 s
30 s
3 s
0 s
3
AGS Harness W ires
Generator W ires
GENERATOR RUN SIGNAL
12
13
GENERATOR RUN SIGNAL RETURN
5A fuse
5A fuse
14
STOP
Relay 1
16
17
Relay 2
START
18
For additional information, see “Circuit Limitations” on page 11.
Figure 20 Type 12 Connection Diagram
Relay Function
Relay 1 mode
Preset Configuration Setting
GlowStop
Relay 3 mode
No function
Gen Run signal hold time
Preheat time
4 s
0 s
Preheat to crank delay
Crank time
0 s
30 s
26
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Type 13
Type 13 is a three-wire PulseStop configuration that uses relay 3 to provide
the preheat signal. With this generator type, there will be a delay between
the generator turning off and the AGS recognizing that the generator is off.
Relay Function
Preheat time
Preset Configuration Setting
15 s
Preheat to crank delay
Crank time
2 s
AGS Harness W ires
Generator W ires
15 s
15 s
30 s
3 s
Crank retry time
Gen Cool Down
Gen Spin Down
Shutdown bypass time
Start tries
12
13
GENERATOR RUN SIGNAL
GENERATOR RUN SIGNAL RETURN
STOP/PREHEAT
5A fuse
5A fuse
14
Relay 1
16
0 s
17
Relay 2
START
18
3
5A fuse
FUEL PRIME (PREHEAT)
19
Relay 3
12V GENERATOR BATTERY+
20
For additional information, see “Circuit Limitations” on page 11.
Figure 21 Type 13 Connection Diagram
Relay Function
Relay 1 mode
Preset Configuration Setting
PulseStop
Preheat
5 s
Relay 3 mode
Gen Run signal hold time
975-0082-01-01
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Type 14
Type 14 works with two-wire generators that use an integrated engine
control module to perform the necessary relay cycles to start and stop the
generator. This is similar to Type 8 but without the B+ signal requirement.
The AGS closes relay 1 to start the generator and illuminates the Generator
On light to indicate the relay is closed. To stop the generator, relay 1 is
opened and the Generator On light turned off.
AGS Harness Wires
Generator Wires
5A fuse
14
Relay 1
RUN
16
RELAY 1 RETURN
For additional information, see “Circuit Limitations” on page 11.
IMPORTANT: Since Type 14 does not monitor the generator run status,
illumination of the Generator On light on the AGS does not necessarily
indicate the generator is actually running. If this generator type is used,
ensure the generator’s integrated controller has the ability to monitor,
control and report generator status and faults. With Type 14, no faults are
raised if the generator fails to start or stop or is externally started or
stopped.
Figure 22 Type 14 Connection Diagram (two-wire)
Relay Function
Preset Configuration Setting
Relay 1 mode
RunStop
Not used
0 s
Relay 3 mode
Once the generator is stopped, there is a 10-minute delay before the
generator can be re-started using the AGS. This is to allow the generator’s
integrated engine controller to completely and safely shut down the
generator. This delay can be adjusted by changing the Gen Spin down
setting.
Gen Run signal hold time
Preheat time
0 s
Preheat to crank delay
Crank time
0 s
0 s
Crank retry time
Gen Cool Down
Gen Spin Down
Shutdown bypass time
Start tries
0 s
30 s
600 s
0 s
1
28
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Connecting the Thermostats (optional)
Wires 1, 2, 3, and 4 on the wiring harness can be connected to two
thermostats. Wires 1 (yellow) and 2 (gray) are intended for thermostat 1 and
wires 3 (orange) and 4 (gray) are intended for thermostat 2.
Table 1 Wiring for Connecting Thermostats
Wire
Number
Wiring Harness
Wire Color
Function
1
2
3
4
Thermostat 1 input (12/24 V)
Thermostat 1 return (ground)
Thermostat 2 input (12/24 V)
Thermostat 2 return (ground)
Yellow
Gray
Orange
Gray
These wires connect to 12-volt/24-volt output signals from the thermostats.
The AGS will start the generator in response to these signals. Thermostats
can not be programmed using the AGS.
For specific information about thermostat wiring and where AGS
connections should be made, please consult your thermostat documentation
or contact the thermostat manufacturer.
975-0082-01-01
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
In order for the Xanbus Automatic Generator Start (AGS) to be able to
detect these switches, connect the fused positive of the generator battery to
wire 10 on the harness (the constant 12-volt/24-volt wire). See Figure 23 on
page 32. Ensure all circuits added to the system comply with “Circuit
Limitations” on page 11.
Connecting an External Shutdown (optional)
The external shutdown input is a 12-volt/24-volt input used to assure that
the AGS keeps the generator off under conditions that may be potentially
hazardous. Wire 5 (white/black) and 6 (gray) on the wiring harness are
intended for an external switch or sensor (such as a moisture detector, or
carbon monoxide detector) that produces an active high 12-volt or 24-volt
output.
If the generator battery does not have the required voltage, any 12-volt or
24-volt power source meeting the limits on page 11, will suit this purpose.
If an alternate power source is used, its positive terminal must be connected
to wire 10. Its negative must be connected to wire 11.
Table 2 Wiring for Connecting an External Shutdown
Wire
Number
Wiring Harness
Wire Color
NOTE: Internally, wire 11 is connected to wire 13, so in this
configuration, the alternative power source negative may already be
connected to the negative terminal on the generator battery.
Function
5
6
External shutdown input (12/24 V)
External shutdown return (ground)
White/Black
Gray
Connecting an External Manual ON/OFF
Switch (optional)
FIRE AND ELECTRICAL SHOCK HAZARD
When making connections to a 12-volt or 24-volt power source that
exceeds the class 2 power limitation of 100 VA (e.g., a battery) always
thermostat and external manual ON/OFF connections. Locate the
protection device at the power source in the positive wire.
Do not connect the AGS to a 48-volt battery bank. The AGS is limited to
a 30V open-circuit maximum by its regulatory approval and cannot be
connected to a 48-volt power source.
The external manual ON/OFF inputs (wires 7 and 8 on the wiring harness)
are intended for wiring to one or more remote ON/OFF switches for starting
and stopping the generator manually. Wire 7 (Start) and wire 8 (Stop)
should each run to their own momentary-contact switch or push-button. The
other contact on both switches (common) should be connected to wire 11 on
the harness.
Failure to follow these instructions can result in death or serious
injury.
NOTE: Internally, wire 11 is connected to wire 13 so it may already be
connected to the negative terminal on the generator battery.
30
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
The External Manual On and External Manual Off states are not affected by
maximum generator run time (see “Max Run Time” on page 55).
EQUIPMENT DAMAGE
Connecting an External ON/OFF LED
Tapping 12-volts or 24-volts from a 48-volt battery bank will unevenly
wear out the batteries and shortens the battery bank life.
Failure to follow these instructions can damage the unit and/or
damage other equipment.
Wires 9 (White/Blue) and 11 (Black) on the wiring harness can be
connected to an LED or other light to accompany a remote external ON/
OFF switch. This light turns on when the generator run signal is active to
visually indicate that the generator is running.
Table 3 Wiring for Connecting an External Manual ON/OFF
Switch
IMPORTANT: With some generators, the generator run signal becomes
active during the preheat stage, before the generator is actually running. In
this case, the external ON/OFF LED (and the Generator On light on the
AGS) will turn on during the preheat stage and remain on when the
generator is running.
Wire
Number
Wiring Harness
Wire Color
Function
7
8
9
External manual on input
External manual off input
White/Green
White/Red
White/Blue
For some generators, these lights will also remain on for a period of time
after the generator has stopped.
External On/Off LED Indicator
output
10
11
Constant 12/24 V B+ for External
On/Off/LED Indicator
Red
External On/Off/LED Indicator
return
Black
Multiple generator control panels or simple contact closures can be wired to
the external manual ON/OFF inputs. The AGS detects if any of the contacts
close and will change its operating mode to External Manual On or External
Manual Off (for more information, see “GenMode” on page 60). The AGS
turns the generator on or off according to these inputs and the resulting
operating mode change.
975-0082-01-01
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
2K
H11A817
2K
H11A817
5K11
H11A817
Figure 23 External ON/OFF Switch and LED Wiring Diagram
32
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Connecting the Wiring Harness to the AGS
After all the external connections have been wired to the wiring harness, the
connector on the wiring harness must be plugged into the 20-contact
connector on the AGS.
To connect the wiring harness to the AGS:
◆
With the click-tab on the wiring harness connector on top (away from
the mounting surface), insert the wiring harness connector into the 20-
contact connector on the AGS until the tab clicks into place.
Figure 24 AGS External Connections
975-0082-01-01
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Connecting the AGS to the Xanbus Network
.
AC Panel
EQUIPMENT DAMAGE
Connect only to other Xanbus-enabled devices.
Freedom Sequence
Although the cabling and connectors used in this network system are the
same as those used for Ethernet, this network is not an Ethernet system.
Equipment damage may result from attempting to connect a Xanbus-
enabled device to an Ethernet system.
Shore
Power
BATTERY
3012
lt
C/
rg
Cha
e
F
a
A
er
Inv
t
er
O
n
SW
erter
v
3012
In ble
Ena
set
Re
SW
FREEDOM
FREEDOM
System Control Panel
Automatic Generator Start
Failure to follow these instructions can damage the unit and/or
damage other equipment.
Freedom SW Inverter/Charger
Xanbus Automatic Generator Start
Xanbus System Control Panel
Inverter
Load Panel
network terminator
network terminator
Generator
AC Loads
To connect the AGS to the Xanbus network, plug a Xanbus network cable
(standard straight-through Ethernet cable—CAT 5e) into one of the network
ports on the bottom panel of the AGS. Connect the other end of that same
cable to the next Xanbus-enabled component in the chain. See Figure 25. For
the location of the ports on the AGS, see Figure 5 on page 9
Figure 25 Xanbus Network Example
If the AGS is being installed on an existing Xanbus system, the system must
first be put into Standby. See “Putting the AGS in Standby Mode” on page
67.
Depending on the layout of the Xanbus system, the following options are
available for the other network connector on the AGS:
•
•
A second network cable
A network terminator (when the AGS is the last device at one end of
the network)
34
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Xanbus Automatic Generator Start Installation
Verifying Power Is Available
When the AGS has been installed properly, the Power and Network
indicator lights illuminate.
If one or both lights are out, check the network connections. Check the
Xanbus to ensure it has battery power. Check to make sure the other devices
in the network, such as the Xanbus System Control Panel (SCP), are
responding to confirm the network is still active.
Verify Power and Network
indicator lights are illuminated.
Connect one or two network
cables as required by the
installation configuration.
Figure 26 Connecting the Xanbus System Control Panel (SCP)
Figure 27 Verifying Power is Available
975-0082-01-01
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
Overview
The AGS has a number of settings that must be configured to ensure that
the generator starts and stops under the appropriate conditions and at the
appropriate time. The AGS is configured using the Xanbus System Control
Panel (SCP).
T
M
AC In/Charge
Inverter On
Low Battery
Fault
STBY/ON
Fault Clear
The Freedom SW System Home Screen on the Xanbus System Control
Panel (SCP) displays basic system operational status. On the lower left
corner of the Freedom SW System Home Screen, there is an arrow that
points to the Enter Button below the display. Pressing the Enter Button
when the Freedom SW System Home Screen is displayed will take the
system to the Select Device Menu.
Enter
Func
FGA: 809-0921
Xanbus System Control Panel (SCP)
The AGS Menu is accessed from the Select Device menu screen. All
configurable settings, generator mode, fault clearing, and device
information is provided in the AGS Menu.
Enter Button
Confirms
selection of a
menu item
Moves to the
next screen
Up arrow
Scrolls up
one line of
text
Increases a
selected
value
Down arrow
Scrolls down
one line of text
Decreases a
selected value
Func Button
Cancels
selection of a
menu item
Returns to the
previous screen
Figure 28 Xanbus System Control Panel (SCP) Navigation Buttons and
Freedom SW System Home Screen
36
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
Accessing the AGS Menu
To change operational settings on
the AGS Menu:
T
M
1. Use the arrow buttons to select the
desired operation.
2. Press Enter to highlight the current
value for that setting. Asterisks (*)
indicate the last value set.
3. Use the arrow buttons to change the
value. Holding an arrow button down
without releasing it will scroll through
the values quickly.
4. Press Enter to select the value.
5. Press Func twice to return to the
Freedom SW System Home Screen.
AC In/Charge
Inverter On
Low Battery
Fault
XAGS 00: Setup
STBY/ON
Fault Clear
Use the Xanbus AGS Menu to
change configuration settings, set
operating mode, clear fault
warnings, and view device
information.
T
M
GenMode
Mode
[ManualOff]
[Operating]
Clear Faults Warnings
View Device Info
AC In/Charge
System Status
STBY/ON
Fault Clear
Inverter On
Low Battery
Fault
Battery
BatLev
Load
20.4A
53.9V
E--F
1235W
AC1
Menu
1150W
3202V
Enter
Func
To access the Xanbus AGS Menu,
start from the Xanbus System
Home Screen.
FGA: 809-0921
Xanbus System Control Panel (SCP)
Enter
Func
To view the Select Device Menu,
press Enter.
FGA: 809-0921
Xanbus System Control Panel (SCP)
See Figure 31.
Auto Gen Start Menu
To select the AGS Menu, use the
arrow buttons to highlight AGS
“XAGS”. Press Enter to select the AGS
Menu.
M
To access the advanced settings to
configure specific operational
parameters:
T
M
AC In/Charge
Select Device
STBY/ON
Fault Clear
AC In/Charge
Inverter On
Low Battery
Fault
Inverter On
Low Battery
Fault
AGS 00: Setup
STBY/ON
Fault Clear
System Settings
FSW3012
EMS
Advanced Settings
GenMode
Press the Enter button and the Up and
Down Arrow Buttons at the same time.
[ManualOff]
XAGS
Clear Faults Warnings
View Device Info
Setup
System
See Figure 32.
Enter
Func
Enter
Func
FGA: 809-0921
Xanbus System Control Panel (SCP)
FGA: 809-0921
Xanbus System Control Panel (SCP)
Figure 29 Accessing the AGS Menu
Figure 30 Changing Settings
975-0082-01-01
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
The Xanbus Automatic Generator Start
(AGS) Menu
M
Xanbus AGS Menu
To configure...
AC In/Charge
Inverter On
Low Battery
Fault
XAGS 00: Setup
XAGS 00: Setup
GenMode [ManualOff]
Mode [Operating]
Clear Faults Warnings
View Device Info
XAGS 00: Setup
STBY/ON
Fault Clear
GenMode
Mode
[ManualOff]
[Operating]
Advanced Settings
GenMode
The Xanbus Automatic Generator Start (AGS) menu provides the ability to
configure the changeable parameters, select the generator’s operating mode,
clear fault warnings and view device information.
[ManualOff]
Clear Faults Warnings
View Device Info
Clear Faults Warnings
View Device Info
Enter
Func
Use these buttons to
move UP or DOWN.
Press the ENTER button to
select the menu item.
The Xanbus Automatic Generator Start (AGS) Menu Home Screen is
divided into five sections.
FGA: 809-0921
Xanbus System Control Panel (SCP)
•
•
•
•
•
Advanced Settings (Configuration Settings)
GenMode (Manual on/Manual off/Automatic)
Mode of Operation (Operating/Standby)
Clear Fault Warnings
XAGS 00: Setup
GenMode
Mode
Clear Faults Warnings
View Device Info
XAGS 00: Setup
[ManualOff]
[Operating]
GenMode
Mode
[ManualOff]
[Operating]
To select the Generator
Starting Mode...
Clear Faults Warnings
View Device Info
XAGS 00: Setup
XAGS 00: Setup
View Device Info
GenMode
Mode
[ManualOff]
[Operating]
GenMode
Mode
Clear Faults Warnings
View Device Info
[ManualOff]
To select the Device
Operating Mode...
[Operating]
Clear Faults Warnings
View Device Info
Use these buttons to
change the settings.
Press the ENTER button
accepts the new setting.
XAGS 00: Setup
GenMode
Mode
Clear Faults Warnings
View Device Info
[ManualOff]
[Operating]
To clear faults and
warnings...
Press the Func button to
return to the AGS Home.
XAGS 00: Setup
GenMode
Mode
Clear Faults Warnings
View Device Info
[ManualOff]
[Operating]
To view device
information...
Press the Func button to
return to the FSW System
Home Screen.
Figure 31 AGS Basic Menu Contents
38
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
When the AGS Home Screen is first displayed, the menu defaults to the
GenMode Menu. If configuration changes need to be made, the
Configuration Menu can be accessed by pressing the Enter, Up arrow, and
Down arrow buttons all at same time to access the Advanced Settings.
T
M
AC In/Charge
Inverter On
Low Battery
Fault
XAGS 00: Setup
STBY/ON
Fault Clear
GenMode
Mode
[ManualOff]
[Operating]
Clear Faults Warnings
View Device Info
Xanbus AGS Menu
XAGS 00: Setup
Advanced Settings
GenMode
[ManualOff]
Clear Faults Warnings
View Device Info
Enter
Func
To change configuration parameters...
FGA: 809-0921
Xanbus System Control Panel (SCP)
XAGS 00: Setup
Press Enter to move forward
into the Config menu.
To access the Advanced Settings menu,
Press Enter and Up and Down arrows together
Advanced Settings
GenMode
[ManualOff]
Clear Faults Warnings
View Device Info
XAGS 00: Triggers
Start DCV 30 Sec
[40.0V]
Start DCV 15 Sec [Disabled]
Start DCV hr [Disabled]
Start DCV 24 Hr [Disabled]
2
Stop Float
Stop Absorb
StopV
[Disabled]
[Disabled]
[Disabled]
Temp1
Temp2
Load
Start Load
Stop Load
[Disabled]
[Disabled]
[Disabled]
[15A]
[10A]
Use these buttons to
change the settings.
XAGS 00: Config
QT EN
QT Begin
QT End
Gen Type
[Enabled]
XAGS 00: Gen
[9:00PM]
[8:00AM]
[2]
Starter Cool Down
Gen Cool Down
[60sec]
[30sec]
Press ENTER to accept
the new setting.
Cfg Trigger
Cfg Gen
Multi-Unit Config
Restore Defaults
Gen Spin Down
Max Runtime
Exercise per
Exercise Dur
[3sec]
[4hours]
[21days]
[30min]
Exercise Time
Relay
Gen Run Hold Time
Crank Delay
Crank Time
Crank Retry Time
Preheat Time
Gen Start Tries
[9:00AM]
[Not Used]
[0.5s]
3
[1sec]
[30sec]
[40sec]
[0sec]
[3]
Use these buttons to select
the desired menu.
XAGS 00: Gen
Dev Name
Dev Number
Connections
[AGS]
[00]
Press ENTER to move the cursor
to the changeable settings.
XAGS 00: Conn
DC Conn
AC In
AC Out
[HouseBatt1]
[Grid1]
[ACLoad]
[Gen1]
Generator
To return to the
Press Enter and Up and Down arrows together
B
asic Settings menu,
Press Func to return to the
Xanbus AGS Home screen.
Figure 32 AGS Configuration Menu Contents
975-0082-01-01
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
The Configuration Menu
QT En
The Configuration Menu is where specific start-stop parameters are set.
This menu contains the following settings:
Full name Quiet Time Enable
Purpose "QT En"enables or disables the Quiet Time functionality of the
•
•
•
•
•
•
•
"QT En"
AGS. Quiet time refers to a period of time when the generator should not
run.
"QT Begin"
"QT End"
Dependencies "QT En"requires the AGS to be in Automatic mode.
Setting "QT En"to [Enable] requires that parameters be set for the "QT
Begin"and "QT End".
"Gen Type"
"Cfg Trigger"
"Cfg Gen"
Value
Description
"Restore Defaults"
Enabled/Disabled
Enables or disables the Quiet Time functionality.
When to use Set "QT En"to [Enabled] when there is a period of time
when it is not desired for the generator to run. The AGS will ignore all
automatic start triggers during the time set in "QT Begin"and "QT
Begin".
When there are no preferences or restrictions for when the generator should
run, set "QT En"to [Disabled]. When [Disabled] is selected, the AGS will
ignore the times set for "QT Begin"and "QT End".
Considerations Quiet Time prevents the automatic starting of the
generator regardless of battery condition.
40
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
QT Begin
IMPORTANT: If quiet time is set for overnight, be aware that overnight
battery drain can be significant as it may be necessary to use the inverter
and batteries to supply AC Power without the help of a generator.
Therefore, it is important to conserve battery power during this time.
Minimize the use of interior lights and set thermostat temperature lower to
prevent the furnace from coming on at night during cool weather. Set
thermostats higher to prevent air conditioning coming on at night during
warm weather.
Full name Quiet Time Begin
Purpose "QT Begin"defines the start of quiet time.
Dependencies "QT Begin"functions only if the AGS is in Automatic
mode. This setting requires "QT En"be set to [Enabled].
Ensure the clock on the Xanbus System Control Panel (SCP) is set to the
correct local time.
Sometimes automatic start or automatic stop triggers may overlap with the
beginning and end of quiet time. Three different quiet time scenarios affect
when the generator stops and starts.
Value
Description
12:00AM to
11:59PM (12-hour
clock)
00:00 to 23:59
(24-hour clock)
At the time set for "QT Begin", the generator
will stop (if it is running) and not be able to start
again until the time set for "QT End". It ignores
all automatic start triggers during the time period
between "QT Begin"and "QT End".
1. If quiet time begins after the AGS has started the generator, the
generator will stop. If the condition that started the generator is still
present when quiet time ends, the generator will restart.
2. If a condition that requires starting the generator occurs during quiet
time, the AGS will ignore it until quiet time ends. If the condition still
exists at the end of quiet time, the AGS will start the generator.
3. If the running generator stops when quiet time begins and a condition
that requires stopping the generator occurs during quiet time, the
generator will not restart when quiet time ends.
975-0082-01-01
41
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
QT End
Gen Type
Full name Generator Type
Full name Quiet Time End
Purpose "Gen Type"selects the starting requirements of the generator.
The starting requirements determine how the AGS must be wired to the
generator’s starting system. For more information, see “Connecting the
Generator” on page 14 or Appendix B.
Purpose "QT End"is a changeable setting that defines the end of quiet
time.
This setting also requires a setting for "QT Begin".
Dependencies "QT End"functions only if the AGS is in Automatic
mode. This setting requires "QT En"be set to [Enabled] and also requires a
setting for "QT Begin".
IMPORTANT: "Gen Type"can only be changed after the system is put
into Standby. See “Putting the AGS in Standby Mode” on page 67.
Ensure the clock on the Xanbus System Control Panel (SCP) is set to the
correct local time.
Table 4 Generator Type Descriptions
Description
Value
Description
a
Option
Type 1
Type 2
Type 3
Type 4
Type 5
Type 6
Type 7
Type 8
Type 9
Mode
For Technical Details, see.
page 15
12:00AM to
11:59PM (12-hour
clock)
00:00 to 23:59
(24-hour clock)
At the time set for "QT End"the AGS will be
able to automatically start the generator again. If
a start trigger has occurred during quiet time and
is still active, the generator will start immediately
after quiet time ends.
GlowStop
GlowStop with no preheat
GlowStop with shutdown bypass
StartStop with Relay 3 prime
StartStop with Relay 3 preheat
GlowStop with normally closed RunStop contact
Run with preheat
page 16
page 17
page 18
page 19
page 20
page 21
Run with no preheat
page 22
StartStop with Relay 3 preheat and shutdown
bypass
page 23
Type 10 StartStop
Type 11 MomentaryRun
page 24
page 25
42
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
Table 4 Generator Type Descriptions
Outcomes Selecting a "Gen Type"from the list automatically
configures the following settings:
Description
•
•
•
•
•
•
•
•
•
Preheat time
Preheat end to crank delay time
Crank time
a
Option
Mode
For Technical Details, see.
page 26
Type 12 GlowStop with no preheat
Crank retry time
Type 13 PulseStop with Relay 3 preheat
page 27
Starter cool down time
Generator cool down
Generator spin down time
Generator run signal hold time
Start tries.
Type 14 Run with no preheat and no switched B+
requirement
page 28
When to use Use this setting after installing the AGS hardware. Selecting
a suitable "Gen Type"automatically configures the AGS to work with the
ignition system and starting requirements of the generator. Consult the
generator manual or contact the generator’s manufacturer for specific
generator starting requirements.
If the presets will not work with the desired generator, it may be necessary
to manually configure some of the settings listed above using information
from the generator manufacturer. These settings can be changed in the
CfgGen Menu on page 53.
975-0082-01-01
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
The "Cfg Trigger"menu contains the following items:
Cfg Trigger
Charger Triggers:
•
•
•
•
•
•
•
"Start DCV 30 sec"
"Start DCV 15 min"
"Start DCV 2 hr"
"Start DCV 24 hr"
"Stop Float"
The "Cfg Trigger"menu contains the settings for automatically starting
and stopping the generator. This menu allows the adjustment of the default
settings for battery voltage, thermostat ON/OFF signals, inverter load, and
battery charging stage.
There are three classes of triggers: charger-based, thermostat-based, and
inverter load-based. If the generator is started by a trigger in one class, a
stop condition must also be set in order for the generator to stop. For
example for charger triggers, if the generator is started by the "Start DCV
30 sec"condition, any of the accompanying stop triggers "Stop Float",
"Stop Float"and "Stop V"can be used to stop it.
"Stop Absorb"
"Stop V"
Thermostat Triggers:
•
•
"Temp1"
If at least one start trigger is enabled in two or all three trigger classes, the
first trigger to be true will start the generator. Conversely, the last stop
trigger to be met will stop the generator.
"Temp2"
Inverter Load Triggers:
Changing the default settings is advised for experienced users or users who
have consulted service personnel.
•
•
•
"Load"
"Start Load"
"Stop Load"
IMPORTANT: The Auto Gen Start mode must be set to Manual Off before
any start trigger parameters are set.
44
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
Start DCV 30 sec
Full Name Starting Battery Voltage—30 seconds
If using an automatic generator starting system with the start trigger set to
the same voltage as the LBCO voltage, do not set the LBCO Delay for less
than the amount of time it takes the generator to start and connect.
Otherwise, inverter output turns off and then back on when the generator
auto-starts.
Purpose The "Start DCV 30 sec"trigger enables the AGS to start the
generator whenever the battery voltage reaches or drops below a pre-set
voltage for longer than 30 seconds.
The AGS will stop the generator when the stop trigger is provided
("Stop V", "Stop Absorb", or "Stop Float").
Battery Voltage Information Battery voltage can be monitored from the
System screen or the inverter/charger menu.
Dependencies The "Start DCV 30 sec"trigger requires the AGS to be
in Automatic mode and needs the "Stop Absorb"or "Stop Float"
trigger be enabled or a parameter to be set for the "Stop V"trigger.
If "Stop Float"or "Stop Absorb"has been enabled, the generator will
stop when the Float or Absorption stages of the battery charging have
begun.
If the "Stop V"is used, the generator will stop when the battery voltage
reaches the parameter set in this trigger, regardless of whether the batteries
are charged.
Values
Default
Disabled, 4.0 V to 60.0 V (increments of 0.1 V)
11.3 V
Considerations If the voltage trigger is set too high, the generator will
start more frequently than is convenient.
If the voltage trigger is set too low, the batteries may be damaged by
repeated cycles of excessive discharge. The generator running time
necessary to charge the batteries may exceed "Max Run Time"and use too
much fuel in the process.
If using the Xanbus Low Batt Cut Out voltage setting to trigger a start-on-
voltage setting on the AGS, be sure to set the AGS voltage trigger higher
than the Xanbus Low Batt Cut out voltage. Otherwise the inverter output
turns off and then back on when the generator auto-starts.
975-0082-01-01
45
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
Start DCV 15 min
Full Name Starting Battery Voltage—15 minutes
If the "Stop V"is used, the generator will stop when the battery voltage
reaches the parameter set in this trigger, regardless of whether the batteries
are charged.
Purpose The "Start DCV 15 min"trigger enables the AGS to start the
generator whenever the battery voltage reaches or drops below a pre-set
voltage for longer than 15 minutes.
The AGS will stop the generator when the battery voltage has risen to the
"Stop V", or when the batteries have been recharged to the Absorption or
Float stage.
Dependencies The "Start DCV 15 min"trigger requires the AGS to be
in Automatic mode and needs the "Stop Absorb"or "Stop Float"
trigger be enabled or a parameter to be set for the "Stop V"trigger.
Values
Default
Disabled, 4.0V to 60.0V
Disabled
Considerations If the voltage trigger is set too high, the generator will
start more frequently than is convenient.
If the voltage trigger is set too low, the batteries may be damaged by
repeated cycles of excessive discharge. The generator running time
necessary to charge the batteries may exceed "Max Run Time"and use too
much fuel in the process.
Battery Voltage Information Battery voltage can be monitored from the
System screen or the inverter/charger menu.
If "Stop Float"or "Stop Absorb"has been enabled, the generator will
stop when the Float or Absorption stages of the battery charging have
begun.
46
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
Start DCV 24 hr
Start DCV 2 hr
Full name Starting Battery Voltage—24 hours
Full name Starting Battery Voltage—2 hours
Purpose The "Start DCV 24 hr"trigger enables the AGS to start the
generator whenever the battery voltage reaches or drops below a pre-set
voltage for longer than 24 hours.
Purpose The "Start DCV 2 hr"trigger enables the AGS to start the
generator whenever the battery voltage reaches or drops below a pre-set
voltage for longer than 2 hours.
Dependencies The "Start DCV 24 hr"trigger requires the AGS to be
in Automatic mode and needs the "Stop Absorb"or "Stop Float"
trigger be enabled or a parameter to be set for the "Stop V"trigger.
Dependencies The "Start DCV 2 hr"trigger requires the AGS to be in
Automatic mode and needs the "Stop Float"or "Stop Absorb"trigger
be enabled or a parameter to be set for the "Stop V"trigger.
Values
Default
Values
Default
Disabled, 4.0 V to 60.0 V
Disabled
Disabled, 4.0 V to 60.0 V
Disabled
Considerations If the voltage trigger is set too high, the generator will
start more frequently than is convenient.
Considerations If the voltage trigger is set too high, the generator will
start more frequently than is convenient.
If the voltage trigger is set too low, the batteries may be damaged by
repeated cycles of excessive discharge. The generator running time
necessary to charge the batteries may exceed "Max Run Time"and use too
much fuel in the process.
If the voltage trigger is set too low, the batteries may be damaged by
repeated cycles of excessive discharge. The generator running time
necessary to charge the batteries may exceed "Max Run Time"and use too
much fuel in the process.
Battery Voltage Information Battery voltage can be monitored from the
System screen or the inverter/charger menu.
Battery Voltage Information Battery voltage can be monitored from the
System screen or the inverter/charger menu.
If "Stop Float"or "Stop Absorb"has been enabled, the generator will
stop when the Float or Absorption stages of the battery charging have
begun.
If "Stop Float"or "Stop Absorb"has been enabled, the generator will
stop when the Float or Absorption stages of the battery charging have
begun.
If the "Stop V"is used, the generator will stop when the battery voltage
reaches the parameter set in this trigger, regardless of whether the batteries
are charged.
If the "Stop V"is used, the generator will stop when the battery voltage
reaches the parameter set in this trigger, regardless of whether the batteries
are charged.
975-0082-01-01
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
Stop Absorb
Stop Float
Full name Stop at Absorption Charge Stage
Full name Stop at Float Charge Stage
Purpose The "Stop Absorb"triggers enables the AGS to stop the
generator when the inverter/charger has recharged the batteries to the
Absorption stage.
Purpose The "Stop Float"trigger allows the AGS to stop the
generator when the inverter/charger has recharged the batteries to the Float
stage.
Values
Default
Values
Default
Disabled, Enabled Disabled
Disabled, Enabled Enabled
Considerations Set "Stop Absorb"if it’s desired to only deliver a
partial charge to the batteries. The AGS will start and run the generator until
the inverter/charger charges the batteries through the Bulk charge stage
(restoring the batteries between roughly 75% and 90% of their full charge).
The AGS stops the generator when the inverter/charger determines the
batteries have reached the Absorption charge stage.
Considerations "Stop Float"or "Stop Absorb"would typically be
used if the generator was started due to a low-battery voltage setting.
"Stop Float"is the recommended setting if it is desired that the generator
charge the batteries completely. This will result in somewhat longer run
times. However, if the generator is the primary charging source, charging
them to the Float stage every time will provide longer battery life.
Because Stop Absorption will shut down the generator before the batteries
are fully charged, it is recommended to use it only if there is an alternate
charging source, such as wind or PV, which can complete the charge. If the
generator is the only charging source, Stop Absorption will leave the
batteries consistently undercharged and may shorten the battery life.
Alternately, Stop Absorption can be useful during utility outages, when it is
desired to keep the generator run time to a minimum, but are expecting a
full recharge once the power is restored.
For more information on battery charging, see the Freedom SW Inverter/
Charger Owner’s Guide.
For more information on battery charging, see Freedom SW Inverter/
Charger Owner’s Guide.
48
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
Stop V
Full name Stopping Battery Voltage
Actual battery voltage can be monitored from the Freedom SW System
Home screen on the Xanbus System Control Panel (SCP).
Purpose The "Stop V"trigger enables the AGS to stop the generator
whenever the battery voltage reaches a pre-set DC voltage. Whenever the
generator starts automatically based on the Starting Battery Voltage, it will
shut off once the Stopping Battery Voltage has been reached.
For more information on battery charging, see the Freedom SW Inverter/
Charger Owner’s Guide.
Dependencies The "Stop V"trigger requires the AGS to be in
Automatic mode and needs a parameter to be set for one of the Start DCV
triggers.
Values
Default
Disabled, 14.0 V to 60.0 V Disabled
(increments of 0.1 V)
Considerations The "Stop V"setting is most useful when you want the
inverter/charger to give the batteries a quick, basic charge. If using this
mode, it is recommended to run a complete charge or equalize cycle once in
a while to restore the battery. To give the batteries a more complete,
consistent charge, use the "Stop Float"setting. This will result in longer
generator run times.
If "Stop V"is set too high, the generator may run for too long.
If "Stop V"is set too low, the AGS will stop the generator before the
inverter/charger has charged the batteries.
If "Stop Float"or "Stop Absorb"have been enabled, the AGS will
stop the generator if the Float or Absorption stages of the battery charging
have begun.
975-0082-01-01
49
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
Temp1
Temp2
Full name Thermostat 1
Full name Thermostat 2
Purpose The "Temp1"trigger enables the generator to start in response to Purpose "Temp2"is intended to be used when the AGS is connected to a
a signal from a thermostat. With "Temp1"set to [Enabled], the AGS will
start the generator to help power the item controlled by that thermostat.
second thermostat. All information and procedures for "Temp1"also apply
for "Temp2".
Values
Default
Values
Default
Disabled, Enabled Disabled
Disabled, Enabled
Disabled
When to use Enable "Temp1"if a thermostat is available that controls a
component that has a high-power requirement such as a furnace or an air
conditioning system.
Considerations If "Temp1"is enabled, the generator will start in
response to a signal from the thermostat. Everything related to setting the
thermostat must be done on the thermostat. For example: setting the
temperature at which the furnace or air conditioning system comes on must
be done on the thermostat. There are no thermostat temperature settings on
the AGS or the Xanbus System Control Panel (SCP).
If "Temp1"is disabled, the component connected to that thermostat will
require that the generator be started manually in order for that component to
have power. Otherwise, the component will need to be connected to another
AC input source.
50
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
Load
Start Load
Full name Enable Inverter Load Start and Stop Triggers
Full name Start on Inverter Load Current
Purpose The "Load"trigger enables or disables the Start on Inverter
Load Current and Stop on Inverter Load Current functionality of the AGS.
This function enables the generator to start and stop based on the current
being drawn on the inverter by the loads. See "Start Load"and "Stop
Load".
Purpose The "Start Load"trigger enables the generator to start at a
specified AC load (current draw) on the inverter. This current draw must be
present for 5 minutes before the generator will start. The generator will
assist the inverter with powering the AC load.
Dependencies The "Start Load"trigger requires the AGS to be in
Automatic mode and the "Load"trigger to be set to ON. It also needs to
have a stopping value set in the "Stop Load"trigger.
Dependencies The "Load"trigger requires the AGS to be in Automatic
mode and needs parameters to be set for both the "Start Load"and
"Stop Load"triggers.
Values
Default
Value
Default
10.0 A to 33.0 A (increments of 1A)
10.0 A
Disabled, Enabled
Disabled
Considerations Change this setting if there are certain “peak” times of
power usage or if power demands consistently exceed the output of the
inverter.
IMPORTANT: This function is intended to protect the batteries from rapid
drain. It is not intended to protect the inverter against overload.
If "Load"is set to [Enabled], the generator will start in response to the
"Start Load"setting unless the AGS is in a Quiet Time period.
The inverter load current can be monitored on the System screen.
If "Start Load"is set too high, the AGS may not start the generator in
time to recharge the batteries before the batteries are drained by the AC
load. In addition, if "Start Load"is set too high, the inverter may shut
down due to an overload condition.
If "Start Load"is set too low, the AGS may start the generator too
frequently, wasting fuel in the process.
975-0082-01-01
51
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
Stop Load
Full name Stop on Inverter Load Current
Purpose The "Stop Load"trigger enables the AGS to stop the generator
when the AC load falls below a specific level for 1 minute. The "Stop
Load"setting applies to situations when the AGS has started the generator
to assist the inverter with powering the AC load.
Dependencies The "Stop Load"trigger requires the AGS to be in
Automatic mode and the "Load"trigger to be set to [Enabled]. It also needs
to have a value starting value set in the "Start Load"trigger.
Values
Default
7.0 A to 28.0 A (increments of 1 A) 7.0 A
52
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
Cfg Gen
The "Cfg Gen"menu provides the means to customize the following
settings if the generator being used doesn’t conform to one of the preset
generator types or if an exercise period needs to be scheduled.
Starter Cool Down
Purpose The Starter Cool Down setting allows an interval to be set
between start attempts if the generator fails to start on the first attempt. This
time period allows the start motor to cool sufficiently before the AGS
signals it to begin cranking again.
The Generator Configuration menu contains the following items:
•
•
•
•
•
•
•
•
•
•
•
•
•
•
"Starter Cool Down"
"Gen Cool Down"
"Gen Spin Down"
"Max Run Time"
"Exercise Per"
"Exercise Dur"
"Exercise Time"
"Relay3"
Values
Default
1s to 250s (increments of 1s)
60s
When to use This setting is automatically configured when a "Gen
Type"is selected for the generator. Customize the "Starter Cool Down"
trigger on the advice of the generator manufacturer or authorized service
personnel.
"Gen Run Hold Time"
"Crank Delay"
"Crank Time"
"Crank Retry Time"
"Preheat Time"
"Gen Start Tries"
975-0082-01-01
53
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
Gen Cool Down
Gen Spin Down
Purpose The Gen Cool Down setting allows an interval to be set between Purpose The Gen Spin Down setting allows an interval to be set between
a generator stop trigger occurring and the AGS actually stopping the
generator. This setting is used in Freedom SW system to unload the
generator before the AGS shuts it down. When a stop trigger occurs, the
AGS enters a Generator cool down state where it continues to run the
generator for the specified time period. At the same time the Freedom SW
Series Inverter/Charger will disconnect the generator when it detects the
AGS in Generator Cool Down, allowing the generator operate unloaded and
cool down before it is shut down.
a generator stop signal being sent at the end of a Gen Cool Down cycle and
the AGS changing the Generator State to “stopped.” This setting is used in
the Freedom SW System to allow the generator to completely stop, thereby
reducing its output voltage to zero and pulling the B+ signal low before the
Freedom SW Series Inverter/Charger can qualify and transfer AC power.
This helps the system operate properly in cases where the generator does
not immediately stop when the stop signal is sent to the AGS. Gen Spin
Down applies to all stop triggers—Stop V, Stop Load, Stop Float, Stop
Absorb, Stop Load, and Manual Off.
This helps improves reliability of the generator by reducing temperature
peaking due to abrupt shut down of a loaded generator. It also reduces the
probability of the generator backfiring that typically happens when the
generator is abruptly shutdown while under heavy load. Gen Cool Down
applies to all stop triggers namely Stop V, Stop Load, Stop Float, Stop
Absorb, Stop Load, and Manual Off.
Values
Default
1s to 900s (increments of 1s)
3s
When to use This setting is automatically configured when a “Gen Type”
is selected for the generator. Customize the “Gen Spin Down” trigger on the
advice of the generator manufacturer or authorized service personnel.
Values
Default
1s to 90s (increments of 1s)
30s
When to use This setting is automatically configured when a “Gen Type”
is selected for the generator. Customize the “Gen Cool Down” trigger on
the advice of the generator manufacturer or authorized service personnel.
54
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
Max Run Time
Exercise Per
Full name Maximum Generator Run Time
Full name Set Exercise Period (in days).
Purpose "Max Run Time"allows a limit to be set on how long the
generator will run. This setting overrides any automatic start triggers. For
example, if the generator starts in response to low battery voltage, and the
batteries are not fully charged before "Max Run Time"is reached, the
generator will stop. In addition, when the generator is started manually
from the Xanbus System Control Panel (SCP), the generator will stop when
"Max Run Time"is reached.
Purpose "Exercise Per"sets the minimum time interval between each
running of the generator. If the generator has not been run within this time
frame, the AGS will start the generator to “exercise” it.
The time interval defined by the Exercise Period setting begins with the last
time the generator was run for any reason, not with the last time the AGS
exercised the generator.
For example, setting an exercise period of 30 days would start the generator
if it had not been run at all for 30 days.
When started with an external manual ON/OFF switch, the generator will
not stop when it reaches "Max Run Time". The generator must be stopped
with the external manual ON/OFF switch, or by using the System Control
Panel to change the "GenMode"to ManualOff.
Dependencies The "Exercise Per"trigger requires parameters to be
set in the "Exercise Dur"and "Exercise Time"menu items.
If the AGS reaches "Max Run Time", a warning message will appear on
the Xanbus System Control Panel (SCP). The AGS will stop operating until
the warning is acknowledged by pressing ENTER on the Xanbus System
Control Panel (SCP).
Values
Default
0 (Off), 1day to 250days (increments of 1day)
21days
Considerations Generators need to run regularly in order to maintain
mechanical health and performance. If the generator isn’t needed and
doesn’t run, it is recommended that an Exercise period be set to keep the
generator in good working condition.
Values
Default
0 hours to 24 hours (increments of 1hour)
8 hours
If the generator runs frequently throughout the year, it may not need to be
exercised. In that case, set the "Exercise Per"trigger to 0.
Considerations Adjust the "Max Run Time"if the maximum generator
run time:
•
•
exceeds the fuel capacity of the generator, or
is not long enough to fully recharge the batteries under optimum
conditions.
IMPORTANT: Consult the generator manual or a service representative
from the generator’s manufacturer for the recommended exercise period.
975-0082-01-01
55
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
Exercise Dur
Exercise Time
Full name Exercise Duration (in minutes)
Purpose "Exercise Time"sets the time of day that the AGS exercises
the generator.
Purpose "Exercise Dur"sets how long the generator will run when it
is exercised.
The "Exercise Time"trigger requires that any parameter other than “0”
be set in "Exercise Per"and a value be set in the "Exercise Dur"
trigger.
Dependencies The "Exercise Dur"trigger requires that any parameter
other than “0” be set in "Exercise Per"and a time of day be set in the
"Exercise Time"trigger.
Values
Default
12:00AM to 11:50PM (12-hour clock) 9:00AM
00:00 to 23:50 (24-hour clock)
(increments of 10 minutes)
Values
Default
1min to 250min
30min
Considerations If the Exercise Time is set, the generator will start at that
time after being inactive for the Exercise Period.
IMPORTANT: Ensure that the Exercise Duration is not set for longer than
the "Max Run Time"setting. Attempting to do so will generate a warning
on the System Control Panel.
If the Exercise Time occurs during Quiet Time, the generator will start
when Quiet Time is over and run for the full amount of time set for
"Exercise Dur".
IMPORTANT: Consult the generator manual or a service representative
from the generator’s manufacturer for the recommended exercise duration.
56
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
Gen Run Hold Time
Relay3
Full name Generator Run Signal Hold Time
Purpose "Relay3"sets the function of Relay 3 of the AGS. The function
of Relay 3 affects contacts 19 and 20 of the 20-contact connector and
external wiring harness.
Purpose "Gen Run Hold Time"specifies the length of time the
generator run signal (or B+ or hour meter signal) must be active before the
AGS considers the generator to be running and cranking can be stopped.
Some generators assert their run signal when they are being cranked, but
before they have started. They also have varying delays from when
cranking begins or ends to when the run signal is asserted or unasserted.
The Run Hold Time is designed to accommodate these generators.
Values
Default
NotUsed, Preheat, PreheatSDByp
NotUsed
Considerations Selecting a value for "Gen Type"automatically
configures "Relay3".
Values
Default
It might be necessary to manually set "Relay3"according to the make and
type of generator being used.
0.0s to 20.0s (increments of 0.5s)
0.5s
Some diesel generators require preheating of their glow plugs before start
cranking. Setting "Relay3"to Preheat enables Relay 3 to perform this
function in addition to Relay 1.
Considerations This setting is automatically configured when a "Gen
Type"is selected for the generator. Manually change this setting only on
the advice of the generator manufacturer or authorized service personnel.
Some generators require Relay 3 to switch 12 volts to the glow plugs, while
some generators require ground to be switched to the glow plugs.
If the installation is made without a B+ connection, it might be necessary to
adjust the Gen Run Hold Time for the AGS to successfully start the
generator. When the B+ signal is not connected, the AGS requests generator
status from the Inverter/Charger, which might take longer that if the B+
signal was connected.
“PreheatSDByp” stands for Preheat with Shutdown Bypass. Some
generators require preheat on relay 3 to remain high for crank time and
shutdown bypass period. See “GlowStop Mode” on page 84 for more
details.
975-0082-01-01
57
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
Crank Delay
Crank Retry Time
Purpose "Crank Delay"specifies the delay time from when the preheat Purpose "Crank Retry Time"specifies the length of time the Start
relay is de-energized to when the Start Relay is energized (and cranking the relay is engaged (and cranking the starter motor) for the second and
starter motor). This is also referred to as the preheat-to-crank delay.
subsequent attempts to start the generator, in cases when the generator fails
to start on the first attempt.
Values
Default
Values
Default
0s to 250s
1s
0s to 250s (increments of 1s)
40s
Considerations This setting is automatically configured when a "Gen
Type"is selected for the generator. Manually change this setting only on
the advice of the generator manufacturer or authorized service personnel.
Considerations This setting is automatically configured when a "Gen
Type"is selected for the generator. Manually change this setting only on
the advice of the generator manufacturer or authorized service personnel.
Crank Time
Preheat Time
Purpose "Crank Time"specifies the maximum length of time the Start
relay is engaged (and cranking the starter motor) for the first attempt to start Purpose "Preheat Time"specifies how long the Preheat relay is
the generator.
engaged during the start sequence. The preheat signal may be required for
diesel generators with glow plugs or fuel priming for gas generators.
The Preheat relay may be Relay 1 or Relay 3, depending on the "Relay3"
setting or the Gen Type selected.
Values
Default
0s to 250s (increments of 1s)
30s
Values
Default
Considerations This setting is automatically configured when a "Gen
Type"is selected for the generator. Manually change this setting only on
the advice of the generator manufacturer or authorized service personnel.
0s to 250s (increments of 1s)
0s
Considerations This setting is automatically configured when a "Gen
Type"is selected for the generator. Manually change this setting only on
the advice of the generator manufacturer or authorized service personnel.
58
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
Gen Start Tries
"Gen Start Tries"specifies how many times the AGS will attempt to
start the generator. On the first start try, the AGS cranks the starter motor
for the Crank Time. If the generator does not start, on subsequent start tries,
the AGS cranks the start motor for the Crank Retry Time.
Values
Default
1 to 10
3
Considerations This setting is automatically configured when a "Gen
Type"is selected for the generator. Manually change this setting only on
the advice of the generator manufacturer or authorized service personnel.
975-0082-01-01
59
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
GenMode
Restore Defaults
Purpose The "GenMode"menu item controls the current operating mode
of the AGS.
The "Restore Defaults"returns the AGS to the factory default settings.
Value
Description
Automatic Automatic mode
ManualOn Manual on mode
ManualOff Manual off mode (default mode)
Considerations Use GenMode when it is necessary to switch between
automatic generator control and manual generator control.
When the Xanbus system powers up all network-enabled devices, the AGS
is in ManualOff mode. To enable automatic generator starts, the AGS must
be put in “Automatic” mode.
Automatic Mode
To have the AGS start and stop the generator automatically, select
Automatic. The generator can start and stop automatically in response to
low battery voltage, AC loads on the inverter, thermostat triggers, or
exercise time. Automatic mode also has a Quiet Time feature, which
prevents the generator from starting during evening hours or other
inconvenient times (see “QT Begin” on page 41, “QT End” on page 42, and
“Using Quiet Time” on page 66).
60
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
Automatic Mode Overrides When the AGS is in Automatic mode,
several settings and conditions override automatic start and stop triggers.
These overrides include, in order of priority:
Manual On Mode
Selecting Manual On Mode overrides the automatic start settings and
manually starts the generator. The generator will run until it is manually
stopped or until it reaches its AGS-defined Maximum Run Time (see “Max
Run Time” on page 55).
•
•
Faults—The AGS stops the generator when a fault occurs.
External Shutdown—When the AGS is connected to a sensor or meter
(a moisture detector, for example) wired to contacts 5 and 6 of the 20-
contact connector, it stops the generator when the device is activated.
See “Connecting an External Shutdown (optional)” on page 30.
Manual Off Mode
•
•
External On/Off—The generator is manually started or stopped with a
switch wired to contacts 7 and 8 of the 20-contact connector. See
“Connecting an External Manual ON/OFF Switch (optional)” on page
30. When started with an external manual ON/OFF switch, the
generator will not stop when it reaches Max Run Time. The generator
must be stopped using the external manual ON/OFF switch.
Selecting Manual Off Mode overrides the automatic stop settings and
manually stops the generator. Manual Off must be selected to stop the
generator when the generator has been started manually. The AGS will not
automatically start the generator again until “Automatic” is selected in the
GenMode Menu.
Max Run Time—When the generator has exceeded its maximum run
time, a warning message will appear on the Xanbus System Control
Panel (SCP). The AGS will stop operating until the warning is
acknowledged by pressing Enter on the Xanbus System Control Panel
(SCP). See “Max Run Time” on page 55.
IMPORTANT: The GenMode mode must be set to Manual Off before any
start trigger settings can be changed.
•
•
Manual On—The generator is started by selecting Manual On mode.
Manual Off—The generator is stopped by selecting Manual Off mode.
975-0082-01-01
61
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
View Event Log
Mode
Purpose The Event Log displays the last 20 AGS events for reference.
Events can include:
The "Mode"menu item is a device operating mode and provides the means
to put the AGS in Standby Mode or return it from to Operating Mode.
•
•
•
•
•
Starting and stopping the generator.
Trigger events. See table below for a detailed list of trigger events.
Changing the system mode.
Changing the system clock.
Commands to restore the default settings.
The AGS Mode must be set to [Standby] before selecting a generator type.
Selecting Standby stops the generator (if it is running).
While in Standby, the AGS “listens” to and reports its status to the network.
It will not start the generator manual or automatically while in Standby.
View Device Info
Event
Displayed
Description of Event Trigger
The "View Device Info"menu provides a means to view the Fault,
Warning and Event logs. It is also where the settings can be restored to
factory default settings.
NotOn
Generator is not running
LowBattV
Preset minimum battery voltage with associated time
delay
CntctClosed
ACIHigh
Exercise
Activated thermostat 1 or 2
View Fault Log
Preset maximum inverter load current
Purpose The Fault Log displays the last 20 AGS faults for reference to
assist the user in troubleshooting problems.
Preset exercise period, exercise time, and exercise
duration
When to use Consult the Fault Log when troubleshooting or before
seeking technical assistance.
ManualOn
Started manually using System Control Panel
Started by external switch connected to AGS
Started by switch connected to generator
AGS has lost control of the running generator
ExtOnviaAGS
ExtOnviaGen
UnableToStop
View Warning Log
Purpose The Warning Log displays the last 20 AGS warnings for
reference.
When to use Consult the Warning Log when troubleshooting or before
seeking technical assistance.
62
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration of the Xanbus AGS
Table 5 Generator Configuration Settings, Values, Defaults,
and User Settings
User Settings
Use this table to record any customized AGS settings for future reference.
User
Setting
Setting
Values
Default
Table 5 Generator Configuration Settings, Values, Defaults,
and User Settings
"Temp2"
Enabled, Disabled
Enabled, Disabled
10.0 A–33.0 A
7.0 A–28.0 A
Disabled
Disabled
10.0 A
"Load"
"Start Load"
"Stop Load"
User
Setting
Setting
Values
Default
7.0 A
Generator Menu Items:
Main Menu Items:
GenMode
"Starter Cool
Down"
1s to 250s (increments of 1s)
60s
ManualOn, ManualOff, Automatic ManualOff
Mode
Operating/Standby
Operating
"Gen Cool Down" 0s to 90 s (increments of 1s)
"Gen Spin Down" 0s to 900s (increments of 1s)
30s
Configuration Menu Items:
3s
"QT En"
Enabled, Off
Enabled
"Max Run Time"
"Exercise Per"
"Exercise Dur"
0hours–24 hours
0days (Off)–250days
1min–250min
8hours
21days
30min
"QT Begin"
12:00AM–11:59PM (12-hour
clock)
00:00–23:59 (24-hour clock)
9:00PM (12-hour
clock)
21:00 (24-hour clock)
"QT End"
12:00AM–11:59PM (12-hour
clock)
00:00–23:59 (24-hour clock)
8:00AM (12-hour
clock)
8:00 (24-hour clock)
"Exercise Time" 12:00AM–11:59PM (12-hour
clock)
9:00AM (12-hour
clock)
9:00 (24-hour clock)
00:00–23:59 (24-hour clock)
"Gen Type"
Type 1 to Type 14
Type 2
"Relay3"
Preheat, WrmupCoolDn, Preheat
SDByp, NotUsed
NotUsed
0.5s
Triggers Menu Items:
"Gen Run Hold
Time"
0.5s to 20s (increments of 1s)
"Start DCV 30
sec"
Disabled, 4.0 V–60.0 V
Disabled, 4.0 V–60.0 V
Disabled, 4.0 V–60.0 V
Disabled, 4.0 V–60.0 V
11.3 V
"Crank Delay"
"Crank Time"
0s to 60s (increments of 1s)
0s to 250s (increments of 1s)
0s to 250s (increments of 1s)
0s
"Start DCV 15
min"
Disabled
Disabled
Disabled
30s
40s
"Start DCV 2
hr"
"Crank Retry
Time"
"Start DCV 24
hr"
"Preheat Time"
0s to 250s (increments of 1s)
1 to 10
0s
3
"Gen Start
Tries"
"Stop Float"
"Stop Absorb"
"Stop V"
Enabled, Disabled
Enabled, Disabled
Disabled, 4.0 V–65.0 V
Enabled, Disabled
Disabled
Enabled
Disabled
Disabled
"Temp1"
975-0082-01-01
63
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation of the Xanbus AGS
Accessing the AGS Home Screen
Freedom SW System Home Screen
Use the AGS Home Screen to view basic operational status information for
the generator. The AGS Home Screen displays the generator start settings
(i.e., ManualOff), the generator state (running or stopped), the stop trigger,
and the Generator signal.
AC In/Charge
Inverter On
Low Battery
Fault
XAGS 00: Setup
STBY/ON
Fault Clear
Advanced Settings
GenMode
[ManualOff]
Clear Faults Warnings
View Device Info
Enter
Func
FGA: 809-0921
Xanbus System Control Panel (SCP)
Press the Down Arrow button until the
AGS Home Screen is displayed.
T
M
AC In/Charge
AGS 00: Setup
STBY/ON
Fault Clear
Inverter On
Low Battery
Fault
Advanced Settings
GenMode
[ManualOff]
Clear Faults Warnings
View Device Info
Setup
System
Enter
Func
FGA: 809-0921
Xanbus System Corol Panel (SCP)
When the AGS
Home screen is
displayed,press
the Enter button
to view the AGS
Setup Menu.
Press the Func
button to return
to the Freedom
SW System
Home Screen.
Figure 33 AGS Home Screen
64
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation of the Xanbus AGS
Starting and Stopping the Generator
Use the AGS to start or stop the generator manually using the Xanbus
System Control Panel (SCP) or automatically in response to an electrical
system condition.
FSW System Home Screen
Select Device Menu
AGS Menu
To set the AGS to start and stop the generator automatically:
1. On the AGS menu, highlight GenMode and press Enter.
2. Use the arrow button to select [Automatic].
3. Press Enter.
Select Device
XAGS 00: Setup
System Status
Battery
BatLev
Load
20.4A
53.9V
E--F
1235W
System Settings
FSW3012
EMS
GenMode
Mode
[ManualOff]
[Operating]
Clear Faults Warnings
View Device Info
XAGS
AC1
Menu
1150W
3202V
To start the generator manually:
1. On the AGS menu, highlight GenMode and press Enter.
2. Use the arrow button to select [ManualOn].
3. Press Enter.
Figure 34 Starting and Stopping the Generator
To stop the generator manually:
1. On the AGS menu, highlight GenMode and press Enter.
2. Use the arrow button to select [ManualOff].
3. Press Enter.
IMPORTANT: To avoid AGS faults, try not to combine automatic and
external manual starts and stops.
When the generator has been started automatically, allow it to stop
automatically unless a situation occurs that requires the generator to be
stopped urgently.
Likewise, if the generator has been started manually, ensure that it is
stopped manually. Only the "Max Run Time"setting can automatically
stop the generator after it has been started manually.
975-0082-01-01
65
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation of the Xanbus AGS
To enable Quiet Time:
Using Quiet Time
1. On the Auto Gen Start menu, use the arrow buttons to highlight "QT
En".
Use the Quiet Time feature to ensure that the AGS will not start the
generator during the night or during times that conflict with local noise
restrictions.
2. Press Enter.
3. Use the arrow buttons to select [Enabled].
4. Press Enter.
Using Quiet Time involves three steps.
1. "QT En"must be set to [Enabled]. The default setting is [Enabled].
To set the beginning of Quiet Time:
2. "QT Begin"must have an appropriate time set for Quiet Time to start
on schedule. The default setting for "QT Begin"is [9:00 PM] or 21:00
if using a 24-hour clock.
1. On the Auto Gen Start menu, use the arrow buttons to highlight "QT
Begin", then press Enter.
2. Use the arrow buttons to select the hour, then press Enter.
3. "QT End"must have an appropriate time set for Quiet Time to stop on
schedule. The default setting for "QT End"is [8:00 AM] or 8:00 on
the 24-hour clock.
3. Use the arrow buttons to select the minutes, then press Enter.
If the 24-hour clock is being used, go to step 5.
For more information about Quiet Time settings, see “QT En” on page 40,
“QT Begin” on page 41, and “QT End” on page 42.
4. Use the arrow buttons to select AM or PM, then press Enter.
5. Press Exit twice to return to the System Home screen.
To set the end of Quiet Time:
FSW System Home
Screen
Select Device Menu
AGS Menu
Set Quiet Time settings
1. On the Auto Gen Start menu, use the arrow buttons to highlight "QT
End", then press Enter.
Select Device
System Status
XAGS 00: Setup
XAGS 00: Adv
2. Use the arrow buttons to select the hour, then press Enter.
[Enabled]
[10:00AM]
[7:00AM]
[2]
Battery
BatLev
Load
20.4A
53.9V
E--F
1235W
System Settings
FSW3012
EMS
Advanced Settings
QT En
QT Begin
QT End
Gen Type
GenMode
[ManualOff]
Clear Faults Warnings
View Device Info
3. Use the arrow buttons to select the minute, then press Enter.
XAGS
AC1
Menu
1150W
3202V
If the 24-hour clock is being used, go to step 5.
4. Use the arrow buttons to select AM or PM, then press Enter.
Figure 35 Using the Quiet Time Feature
5. Press Exit twice to return to the System screen.
66
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation of the Xanbus AGS
Putting the AGS in Standby Mode
Modes of Operation
Use the Xanbus System Control Panel (SCP) to put the AGS into Standby
mode.
The AGS, like all other Xanbus-enabled devices, supports two modes,
Operating and Standby. The AGS mode of operation must be set to Standby
before selecting a Generator Type. Selecting Standby stops the generator (if
it is running).
To put the AGS in Standby Mode:
While in Standby, the AGS “listens” to and reports its status to the network.
However, it will not start the generator manually or automatically while in
Standby.
1
2
3
FreedomSWSystem
Home Screen
Select Device Menu
AGS Settings Menus
If the AGS is powered off while in Standby, it will be in Standby when it is
powered on again.
Select Device
System Status
XAGS 00: Setup
[ManualOff]
[Operating]
Clear Faults Warnings
View Device Info
XAGS 00: Setup
[ManualOff]
[Standby]
Clear Faults Warnings
View Device Info
The AGS can also be put in Standby using the system mode option under
system settings. However, note that selecting Standby from system settings
affects the behavior of the entire Freedom SW system. System mode
Standby puts every Xanbus-enabled device in Freedom SW Power System
into Standby.
Battery
BatLev
Load
20.4A
53.9V
E--F
1235W
System Settings
FSW3012
EMS
GenMode
Mode
GenMode
Mode
XAGS
AC1
Menu
1150W
3202V
Use the arrow
buttons to highlight
“XAGS”.
Use the arrow
buttons to highlight
“Mode.”
Use the arrow
buttons to change
the setting from
[Operating] to
[Standby].
From the Freedom
SW System Home
Screen, press
Enter.
Press Enter.
Press Enter.
IMPORTANT: If AGS Fault 201 “Unable to stop gen.” is active, the AGS
cannot be put into Standby. Before Standby can be established, the
generator must be stopped by its external switch and the fault must be
cleared.
Press Enter.
975-0082-01-01
67
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation of the Xanbus AGS
Returning the AGS to Operating Mode
Use the Xanbus System Control Panel (SCP) to return the AGS to
Operating mode.
To return the AGS to Operating Mode:
1
2
3
Freedom SW System
Home Screen
Select Device Menu
AGS Settings Menu
Select Device
System Status
XAGS 00: Setup
[ManualOff]
[Standby]
Clear Faults Warnings
View Device Info
XAGS 00: Setup
[ManualOff]
[Operating]
Clear Faults Warnings
View Device Info
Battery
BatLev
Load
20.4A
53.9V
E--F
1235W
System Settings
FSW3012
EMS
GenMode
Mode
GenMode
Mode
XAGS
AC1
Menu
1150W
3202V
From the Freedom
SW System Home
Screen, press Enter.
Use the arrow
buttons to highlight
“XAGS”.
Use the arrow
buttons to highlight
“Mode”.
Use the arrow
buttons to change
the setting from
[Standby] to
Press Enter.
Press Enter.
[Operating].
Press Enter.
68
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
Under certain conditions, the AGS generates a fault or warning message.
These messages appear on the Xanbus System Control Panel (SCP).
To view a message from a fault list or warning list:
1. On the list, use the arrow buttons to highlight the message to be
viewed.
Acknowledging messages When a fault or warning message appears, it
will remain on the screen until it is acknowledged by pressing Enter on the
Xanbus System Control Panel (SCP). This action removes the message
from the screen, but does not clear the condition that caused the fault or
warning.
2. Press Enter.
The complete message appears.
To return to the fault list or warning list, press Exit.
To continue to the menu for the device that caused the fault or warning
condition by pressing Exit.
Consult Table 6 and Table 7 for recommendations for resolving the fault
after it has been acknowledged.
Each time you return to the list after viewing a complete message, the
viewed message is removed from the list.
Warnings that are in the form of a Yes/No question can be acknowledged by
pressing Enter for Yes and Exit for No.
If you have left the fault list or warning list, you can view them at any time
from the System Settings menu.
Self-clearing warnings If unacknowledged, some warnings may clear
themselves if the condition that generated the message goes away. For
example, if the AGS fails to start the generator, warning message W202
appears. However, if the generator starts on the next start try, the message
goes away.
To view a fault list or warning list:
1. On the Select Device menu, highlight System and press Enter.
2. On the System Settings menu, highlight View Fault List or View
Warning List.
Clearing faults To clear active AGS faults, highlight Clear Faults on the
AGS menu and press Enter.
3. Press Enter.
Multiple faults and warnings If several fault or warning messages occur
before they can be acknowledged or cleared, they are displayed together on
a fault list or a warning list. These lists contain messages from every
Xanbus-enabled device, not just the AGS. Message details can be selected
and viewed from the fault list or warning list.
975-0082-01-01
69
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
Warning Reference Table
Table 6 AGS Warning Messages (Continued)
Warning Message
Number
Self-clearing?
Cause
Action
Table 6 AGS Warning Messages
Warning Message
Number
Self-clearing?
Cause
Action
W205
Generator
started by its
switch. Use
its switch to
stop.
Yes
The generator was
started, but not by the
AGS.
Check your generator.
Stop it using the switch
or control panel on the
generator.
W200
W201
W202
W203
Generator
was stopped
manually.
No
Generator was stopped Acknowledge the
by an external Manual
Off switch.
warning. To resume
automatic starts and
stops, change the AGS
mode to [Automatic].
W206
Mismatched
triggers.
Enable stop
trigger or
disable start
trigger.
No
No
No
You have set a start
trigger, but not a
corresponding stop
trigger.
Acknowledge warning
and set a stop trigger.
Generator
was started
manually.
No
Yes
No
Generator was started
by an external Manual
On switch
Acknowledge the
warning. To resume
automatic starts and
stops, change the AGS
mode to [Automatic].
W207
Mismatched
triggers.
Enable start
trigger or
disable stop
trigger.
You have set a stop
trigger, but not a
corresponding start
trigger.
Acknowledge warning
and set a start trigger.
Unable to
start
generator.
AGS will try
again.
The AGS tried, but
could not start the
generator.
No action required. The
AGS will try to start the
generator again until it
reaches the maximum
number of start tries.
W208
Automatic
start and stop
triggers not
enabled.
Configure
triggers.
You are attempting to
enter Automatic Mode and set start and stop
without setting triggers. triggers.
Acknowledge warning
Manual Off:
Max
The generator has run
for its maximum
allowable time. The
AGS has stopped the
generator and changed or ManualOn]. Ensure
the GenMode to
[ManualOff].
Acknowledge the
warning. Return the
AGS to the desired
GenMode [Automatic
generator run
time reached.
Reset
GenMode.
generator has fuel and
is supplying the
required power for
battery charging and
loads.
70
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
Table 6 AGS Warning Messages (Continued)
Table 6 AGS Warning Messages (Continued)
Warning Message
Number
Self-clearing?
Cause
Action
Warning Message
Number
Self-clearing?
Cause
Action
W209
Gen external Yes
stop. Start
gen via its
control panel.
The generator has
stopped, but not by the fuel level and
AGS. The generator
may have run out of
gas, or may have been
Check the generator’s
W501
AGS has
fixed
memory
problem and
restored
default
No
The AGS encountered
an internal memory
problem upon startup.
To remain operational, necessary.
the AGS restored its
Acknowledge the
warning and reset
configurable settings if
mechanical condition,
then start the generator
manually (using the
shut off by a switch on switch or control panel
default settings.
the generator.
on the generator) to
clear the warning.
settings.
W250
The selected No
value failed
to change.
You have tried to
change the Gen Type
without putting the
system into Standby
first.
Put the system into
Standby, change the
Gen Type, then return
the system to Operating
mode.
Try again.
You have tried to set the Ensure that “Max Run
“Exercise Dur” for
longer than “Max Run
Time,” or “Max Run
Time” for less than
“Exercise Dur.”
Time” is set for longer
than “Exercise Dur.”
W500
Network
Yes
The AGS has lost
Check connection
connection
lost. Check
connections.
communications with
between the AGS and
the network because of the network.
a faulty connection or
electronic signal
disruption.
975-0082-01-01
71
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
Fault Reference Table
When the AGS detects a fault condition, it stops the generator. The red
Fault light also comes on, and the Xanbus System Control Panel (SCP)
displays a fault message.
Table 7 AGS Fault Messages
Fault
Message
Self-clearing?
Cause
Action
Number
The AGS remembers the GenMode that it was in at the time it detected the
fault. After you have cleared the fault, the AGS returns to its last known
GenMode.
F203
Manual Off: No
Gen stopped
by ext
sensor.Reset
GenMode.
An external sensor
connected to the AGS
has stopped the
generator and put the
AGS into Manual Off
mode.
After the sensor
connected to the
external shutdown has
deactivated, clear the
fault and reset the AGS
to the desired mode.
Table 7 AGS Fault Messages
F500
Serial
No
The silicon serial ID
number has failed and
the AGS has gone into USA Inc.
Standby.
Call your dealer or
Xantrex Technology
Fault
Message
Self-clearing?
Cause
Action
Number
Failure,
Service
Required.
Number
F200
Exceeded
No
The AGS has tried and Check the generator’s
max number
of start tries.
Check gen,
clear fault.
failed to start the
generator. To prevent
draining the start
battery, the AGS will
suspend further start
attempts.
fuel level and start
battery condition.
Consult generator
manual.
Clear fault on System
Control Panel screen to
allow retry.
F501
F505
Memory
Failure.
Service
No
No
The AGS has suffered a Call your dealer or
non-volatile memory
failure.
Xantrex Technology
USA Inc.
Required.
Internal
Failure.
Service
Required.
A controller fault has
occurred and the AGS
Clear the fault. If the
fault persists, call your
F201
Unable to
stop gen.
Stop gen via
its control
panel.
No
The AGS has lost
contact with the
generator or the
generator did not stop
after the AGS sent it a
stop signal.
Change the AGS mode
to Manual Off.
If this fails to work,
stop the generator with
the external stop
switch.
has gone into Standby. dealer or Xantrex
Technology USA Inc.
Check generator.
Return AGS to
automatic mode to
resume automatic starts
and stops.
72
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
NOTE: Specifications are subject to change without prior notice.
Electrical Specifications
Electrical Specifications
Communication protocol
Maximum cable length
Xanbus
Nominal input network voltage
Maximum operating current
Relay contact voltage rating
Maximum relay contact current
12 Vdc
130 ft. (40 m)
200 mA @ nominal input network voltage
12 Vdc, 30 Vdc max.*
5 A DC*
Environmental Specifications
Nominal 12/24 V thermostat
input voltage
12 Vdc/24 Vdc* = On
Operating temperature
Storage temperature
Maximum case temperature
Operating humidity
Storage humidity
-4 to 122 °F (-20 to 50 °C)
-40 to 185 °F (-40 to 85 °C)
140 °F (60 °C)
5 to 95%
Minimum 12/24 V thermostat
input voltage
9.5 Vdc*
Maximum 12/24 V thermostat
input voltage
30 Vdc*
5 to 95%
Typical 12/24 V thermostat
input current
14.6 mA @ 12 V
12 Vdc/24 Vdc*= On
9.5 Vdc*
Ignition protection
None
Nominal 12/24 V generator running
B+ voltage
Regulatory Approvals
Minimum 12/24 V generator running
B+ voltage
Safety
CSA certified to CSA 107.1-01 and UL 458 4th
Ed. including the marine supplement
Maximum 12/24 V generator running
B+ voltage
30 Vdc*
EMC
FCC Part 15, Class B
Typical 12/24 V generator running
B+ current
14.6 mA @ 12 V
2, CAN
Industry Canada ICES-0003 Class B
Communication physical layer
975-0082-01-01
73
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
Physical Specifications
Dimensions
3 ¾ × 5 ¾ x 1 ½" (95.5 × 146 × 37 mm)
0.5 lb. (225 g)
Weight
Mounting
Connectors
4 mounting screws
2 × Xanbus: RJ45—8 pins
1 × 20-contact plug-type connector (Tyco Mate’n’
Lok 2 connector)
5.75 in (146 mm)
Power
Generator On
Network
Fault
2.81 in (71 mm)
3.75 in (95 mm)
FGA: 809-0915
Xanbus Automatic Generator Start (AGS)
4.92 in (125 mm)
GENERATOR
XANBUS
R
!
!
CAUTION
WARNING
1.46 in (37 mm)
CONNECT ONLY TO
CLASS ELV CIRCUITS.
SEE MANUAL.
C
US
CSA 107.1
EXPLOSION HAZARD.
DO NOT INSTALL IN A
LOCATION REQUIRING
IGNITION PROTECTED
EQUIPMENT. SEE
2
UL 458
LR 86581
MARINE
MANUAL.
Figure 36 Xanbus AGS Dimensions
74
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Warranty and Return Information
Warranty
Hawaii and outside of the United States and Canada are excluded. Contact
Xantrex Customer Service for details on freight policy for return shipments
from excluded areas.
What does this warranty cover and how long does it last? This
Limited Warranty is provided by Xantrex Technology USA Inc.
(“Xantrex”) and covers defects in workmanship and materials in your
Xanbus Automatic Generator Start (AGS). This warranty period lasts for 24
months from the date of purchase at the point of sale to you, the original end
user customer, unless otherwise agreed in writing (the “Warranty Period”).
You will be required to demonstrate proof of purchase to make warranty
claims.
How do you get service? If your product requires troubleshooting or
warranty service, contact your merchant. If you are unable to contact your
merchant, or the merchant is unable to provide service, contact Xantrex
directly at:
This Limited Warranty is transferable to subsequent owners but only for the
unexpired portion of the Warranty Period. Subsequent owners also require
original proof of purchase as described in “What proof of purchase is
required?”
Telephone: 1 800 670 0707
Fax:
1 800 994 7828
Website:
www.xantrex.com
What will Xantrex do? During the Warranty Period Xantrex will, at
its option, repair the product (if economically feasible) or replace the
defective product free of charge, provided that you notify Xantrex of the
product defect within the Warranty Period, and provided that Xantrex
through inspection establishes the existence of such a defect and that it is
covered by this Limited Warranty.
Direct returns may be performed according to the Xantrex Return Material
Authorization Policy described in your product manual. For some products,
Xantrex maintains a network of regional Authorized Service Centers. Call
Xantrex or check our website to see if your product can be repaired at one
of these facilities.
Xantrex will, at its option, use new and/or reconditioned parts in
performing warranty repair and building replacement products. Xantrex
reserves the right to use parts or products of original or improved design in
the repair or replacement. If Xantrex repairs or replaces a product, its
warranty continues for the remaining portion of the original Warranty
Period or 90 days from the date of the return shipment to the customer,
whichever is greater. All replaced products and all parts removed from
repaired products become the property of Xantrex.
What proof of purchase is required? In any warranty claim, dated
proof of purchase must accompany the product and the product must not
have been disassembled or modified without prior written authorization by
Xantrex.
Xantrex covers both parts and labor necessary to repair the product, and
return shipment to the customer via a Xantrex-selected non-expedited
surface freight within the contiguous United States and Canada. Alaska,
975-0082-01-01
75
Download from Www.Somanuals.com. All Manuals Search And Download.
Warranty and Return Information
Proof of purchase may be in any one of the following forms:
purchased; and
h) any consequential losses that are attributable to the product losing
•
•
•
The dated purchase receipt from the original purchase of the
product at point of sale to the end user; or
power whether by product malfunction, installation error or misuse.
The dated dealer invoice or purchase receipt showing original
equipment manufacturer (OEM) status; or
Disclaimer
The dated invoice or purchase receipt showing the product
exchanged under warranty.
What does this warranty not cover? Claims are limited to repair and
replacement, or if in Xantrex's discretion that is not possible,
Product
reimbursement up to the purchase price paid for the product. Xantrex will
be liable to you only for direct damages suffered by you and only up to a
maximum amount equal to the purchase price of the product.
This Limited Warranty does not warrant uninterrupted or error-free
operation of the product or cover normal wear and tear of the product or
costs related to the removal, installation, or troubleshooting of the
customer's electrical systems. This warranty does not apply to and Xantrex
will not be responsible for any defect in or damage to:
a) the product if it has been misused, neglected, improperly installed,
physically damaged or altered, either internally or externally, or
damaged from improper use or use in an unsuitable environment;
b) the product if it has been subjected to fire, water, generalized
corrosion, biological infestations, or input voltage that creates
operating conditions beyond the maximum or minimum limits listed in
the Xantrex product specifications including but not limited to high
input voltage from generators and lightning strikes;
THIS LIMITED WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY PROVIDED BY
XANTREX IN CONNECTION WITH YOUR XANTREX PRODUCT AND IS, WHERE
PERMITTED BY LAW, IN LIEU OF ALL OTHER WARRANTIES, CONDITIONS, GUARANTEES,
REPRESENTATIONS, OBLIGATIONS AND LIABILITIES, EXPRESS OR IMPLIED, STATUTORY
OR OTHERWISE IN CONNECTION WITH THE PRODUCT, HOWEVER ARISING (WHETHER
BY CONTRACT, TORT, NEGLIGENCE, PRINCIPLES OF MANUFACTURER'S LIABILITY,
OPERATION OF LAW, CONDUCT, STATEMENT OR OTHERWISE), INCLUDING WITHOUT
RESTRICTION ANY IMPLIED WARRANTY OR CONDITION OF QUALITY,
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. ANY IMPLIED
WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE TO THE
EXTENT REQUIRED UNDER APPLICABLE LAW TO APPLY TO THE PRODUCT SHALL BE
LIMITED IN DURATION TO THE PERIOD STIPULATED UNDER THIS LIMITED WARRANTY.
IN NO EVENT WILL XANTREX BE LIABLE FOR: (A) ANY SPECIAL, INDIRECT,
INCIDENTAL OR CONSEQUENTIAL DAMAGES, INCLUDING LOST PROFITS, LOST
REVENUES, FAILURE TO REALIZE EXPECTED SAVINGS, OR OTHER COMMERCIAL OR
ECONOMIC LOSSES OF ANY KIND, EVEN IF XANTREX HAS BEEN ADVISED, OR HAD
REASON TO KNOW, OF THE POSSIBILITY OF SUCH DAMAGE; (B) ANY LIABILITY
ARISING IN TORT, WHETHER OR NOT ARISING OUT OF XANTREX'S NEGLIGENCE, AND
ALL LOSSES OR DAMAGES TO ANY PROPERTY OR FOR ANY PERSONAL INJURY OR
ECONOMIC LOSS OR DAMAGE CAUSED BY THE CONNECTION OF A PRODUCT TO ANY
OTHER DEVICE OR SYSTEM; AND (C) ANY DAMAGE OR INJURY ARISING FROM OR AS A
RESULT OF MISUSE OR ABUSE, OR THE INCORRECT INSTALLATION, INTEGRATION OR
OPERATION OF THE PRODUCT BY PERSONS NOT AUTHORIZED BY XANTREX.
c) the product if repairs have been done to it other than by Xantrex or its
authorized service centers (hereafter “ASCs”);
d) the product if it is used as a component part of a product expressly
warranted by another manufacturer;
e) component parts or monitoring systems supplied by you or purchased
by Xantrex at your direction for incorporation into the product;
f) the product if its original identification (trade-mark, serial number)
markings have been defaced, altered, or removed;
g) the product if it is located outside of the country where it was
76
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Warranty and Return Information
Exclusions
Return Procedure
IF THIS PRODUCT IS A CONSUMER PRODUCT, FEDERAL LAW DOES NOT ALLOW AN
EXCLUSION OF IMPLIED WARRANTIES. TO THE EXTENT YOU ARE ENTITLED TO
IMPLIED WARRANTIES UNDER FEDERAL LAW, TO THE EXTENT PERMITTED BY
APPLICABLE LAW THEY ARE LIMITED TO THE DURATION OF THIS LIMITED
WARRANTY. SOME STATES, PROVINCES AND JURISDICTIONS DO NOT ALLOW
LIMITATIONS OR EXCLUSIONS ON IMPLIED WARRANTIES OR ON THE DURATION OF AN
IMPLIED WARRANTY OR ON THE LIMITATION OR EXCLUSION OF INCIDENTAL OR
CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATION(S) OR EXCLUSION(S) MAY
NOT APPLY TO YOU. THIS LIMITED WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS.
YOU MAY HAVE OTHER RIGHTS WHICH MAY VARY FROM STATE TO STATE, PROVINCE
TO PROVINCE OR JURISDICTION TO JURISDICTION.
Package the unit safely, preferably using the original box and packing
materials. Please ensure that your product is shipped fully insured in the
original packaging or equivalent. This warranty will not apply where the
product is damaged due to improper packaging.
Include the following:
•
•
•
•
The RMA number supplied by Xantrex Technology USA Inc.
clearly marked on the outside of the box.
A return address where the unit can be shipped. Post office boxes
are not acceptable.
A contact telephone number where you can be reached during
work hours.
A brief description of the problem.
Ship the unit prepaid to the address provided by your Xantrex customer
service representative.
Return Material Authorization Policy
If you are returning a product from outside of the USA or
Canada In addition to the above, you MUST include return freight funds
and are fully responsible for all documents, duties, tariffs, and deposits.
For those products that are not being repaired in the field and are being
returned to Xantrex, before returning a product directly to Xantrex you
must obtain a Return Material Authorization (RMA) number and the
correct factory “Ship To” address. Products must also be shipped prepaid.
Product shipments will be refused and returned at your expense if they are
unauthorized, returned without an RMA number clearly marked on the
outside of the shipping box, if they are shipped collect, or if they are
shipped to the wrong location.
If you are returning a product to a Xantrex Authorized Service
Center (ASC) A Xantrex return material authorization (RMA) number is
not required. However, you must contact the ASC prior to returning the
product or presenting the unit to verify any return procedures that may
apply to that particular facility and that the ASC repairs this particular
Xantrex product.
When you contact Xantrex to obtain service, please have your instruction
manual ready for reference and be prepared to supply:
•
•
•
•
The serial number of your product
Information about the installation and use of the unit
Information about the failure and/or reason for the return
A copy of your dated proof of purchase
Record these details on page 78.
975-0082-01-01
77
Download from Www.Somanuals.com. All Manuals Search And Download.
Warranty and Return Information
Information About Your System
As soon as you open your Xanbus Automatic Generator Start (AGS)
package, record the following information and be sure to keep your proof of
purchase.
______________________
809-0915
______________________
______________________
❐
❐
❐
❐
Serial Number
Product Number/s
Purchased From
Purchase Date
If you need to contact Customer Service, please record the following details
before calling. This information will help our representatives give you
better service.
______________________
______________________
❐
❐
Type of installation (e.g.
RV, truck)
Length of time device
has been installed
Battery/battery bank size
Battery type (e.g. flooded,
______________________
______________________
❐
❐
sealed gel cell, AGM)
DC wiring size and length
Alarm sounding?
______________________
______________________
______________________
❐
❐
❐
Description of indicators
on front panel
Appliances operating
______________________
❐
❐
when problem occurred
Description of problem
______________________
________________________________________________
________________________________________________
78
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix A: Generator Auto Start Requirements and Types
Recommended Features
Generator Starting Types
In order for the generator to be automatically started by the AGS, it must
include electric start and an automatic choke. An automatic primer system
may also be required on natural gas and propane powered generators. The
generator should also include remote start ability with accessible remote
start terminals or a connector. Protective systems for low oil pressure, over
temperature, starter lockout and over crank control are valuable features
that will prevent generator damage and increase system reliability. “Two-
wire” start generators are highly recommended because of the greater
simplicity for automatic starting and because they are intended for remote/
automatic/unattended operation.
The AGS supports three major generator starting types:
•
•
•
Two wire
Three-wire “Onan”
Three-wire automotive
NOTE: The terms “two-wire” and “three-wire” refer only to the minimum
number of wires necessary to start the generator. Actual installations will
require additional wires to connect to the generator, including the generator
run signal (switched B+) wiring, and wiring to an optional external ON/OFF
switch. For installation wiring diagrams, see page 15 to page 28.
NOTE: For overcurrent protection guidelines that apply to the wiring types
discussed in this appendix, see page 11.
975-0082-01-01
79
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix A: Generator Auto Start Requirements and Types
Two Wire
Three-Wire Onan
The two-wire type is suitable for generators that are fully automatic. This
merely requires two wires to be connected together for the generator to start
and run. Separating the wires stops the generator.
The three-wire “Onan” starting type is suitable for generators that are not as
automated as the two-wire type. It requires a minimum of three wires: a
common wire, a start wire and a stop wire. You may also need to connect
the glow plug wires to Relay 1 (wire 14) or Relay 3 (wire 19). If the
generator requires independent control of the glow plugs, power may also
need to be run to Relay 3 (wire 20).
Some generators use a momentary two-wire connection for starting and
stopping.
Identification
Identification
Generators of this type are usually operated with a simple toggle switch or
key that turns to on, then off to shut the generator off.
Generators of this type are controlled with a three-position switch that is
normally in a center (or neutral) position. To start the generator, the switch
is pressed and held to the start position until the generator starts. The switch
is then released, and it returns to the center position. To stop the generator,
the switch is pressed and held to the stop position until the generator stops.
Again, releasing the switch returns it to the center position.
Connection
For this type of generator, the two wires are connected to the normally open
and common contacts of Relay 1 (wires 14 and 16). When the AGS receives
a command to start the generator, it closes the contacts inside Relay 1,
allowing the generator to start. The contacts remain closed for the duration
of the generator run and open when the AGS needs the generator to stop.
Connection
The common wire from the generator should connect to the common
connections of both Relay 1 and Relay 2 (wires 16 and 18 respectively).
The start wire from the generator connects to the normally open contact of
Relay 2 and the generator stop wire connects to the normally open contact
of Relay 1.
80
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix A: Generator Auto Start Requirements and Types
Three-Wire Automotive
The third generator starting type that is supported by the AGS is similar to
an automotive-style ignition. In this style, the generator uses a run circuit
that is normally closed, which then receives a momentary start signal. The
run circuit remains active throughout the run and then is opened in order for
the generator to stop.
Identification
Generators of this type are controlled by a key or rotary switch that acts
exactly as an automotive ignition. The switch is first turned to an “on” (or
run) position, then further to a start position. After starting, the switch
returns to the “on” (or run) position. Other variations are a toggle switch
that gets turned on with a separate switch or push button for start. If glow
plugs are used, you would turn the key or rotary switch to the left prior to
starting. A separate momentary switch or button may be used for this
purpose.
Connection
This generator starting type uses the most wires. The common wire from
the generator should connect to the common connections of both Relay 1
and Relay 2 (wires 16 and 18 respectively). You may need an additional two
wires if glow plugs are used. The start wire from the generator connects to
the normally open contact of Relay 2 and the generator stop wire connects
to the normally open contact of Relay 1.
975-0082-01-01
81
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix B: Relay Timing
RunMode
For generators with RunMode starting types (Types 7, 8, and 14):
•
•
•
The Preheat will never overlap the Crank Time.
The “Delay” refers to the “Preheat to Crank Delay” and may be zero.
Cranking will cease when the generator run signal goes high for the
specified hold time or when the crank time has elapsed.
•
•
Relay 1 (RunStop relay) can be used for two-wire configured
generators.
Relay 1 (RunStop) and Relay 2 (Start) can be used with a common
ground for three-wire configured generators.
Start
Run
Stop
Relay 1: Run/Stop
(Ignition)
Shutdown
Bypass
Relay 2: Start
(Cranking)
Crank
Time
Relay 3: Preheat
(Glow)
Preheat
Figure 37 RunMode Timing Diagram
82
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix B: Relay Timing
MomentaryRun Mode
For generators with MomentaryRun mode starting types (Type 11):
•
•
•
•
Preheat will generally not be used in this configuration.
The Preheat will never overlap the Crank Time.
The “Delay” refers to the “Preheat to Crank Delay” and may be zero.
Cranking will cease when the generator run signal goes high for the
specified hold time or when the crank time has elapsed.
•
Relay 1 (Run/Stop relay) can be used for two-wire configured
generators.
•
Relay 2 has no unique function in this configuration, but it is easiest to
leave it doing the cranking so that another configuration is not required
for it.
Run
Stop
Start
Relay 1:
Momentary Run
Crank
Time
Relay 2: Start
(Cranking)
Preheat
Relay 3: Preheat
(Glow)
Figure 38 MomentaryRun Mode Timing Diagram
975-0082-01-01
83
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix B: Relay Timing
GlowStop Mode
For generators with GlowStop mode starting types (Types 1, 2, 3, 6, 12):
•
The Preheat on Relay 3 will only overlap the Crank Time and perform
ShutDown Bypass if Relay 3 is configured for Preheat with ShutDown
Bypass.
The “Delay” refers to the “Preheat to Crank Delay” and may be zero.
Cranking will cease when the generator run signal goes high for the
specified hold time or when the crank time has elapsed.
•
•
•
Relay 1 (Stop) and Relay 2 (Start) can be used with a common ground
for three-wire configured generators.
•
•
The Preheat signal shows up on Relay 1 and also Relay 3 (if enabled)
so that Relay 1 can be used for both Preheat and Stop.
If the ShutDown Bypass is enabled, the Preheat on Relay 1 will remain
high for the Crank Time and for the ShutDown Bypass period after
cranking.
Shutdown
Bypass
Stop
Run
Relay 1: Glow/Stop
Preheat/
Stop
Start
Crank
Time
Relay 2: Start
(Cranking)
Preheat
Relay 3: Preheat
(Glow)
Figure 39 GlowStop Mode Timing Diagram
84
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix B: Relay Timing
StartStop Mode
For generators with StartStop mode starting types (Types 4, 5, 9, 10):
•
•
The “Delay” refers to the “Preheat to Crank Delay” and may be zero.
Cranking will cease when the generator run signal goes high for the
specified hold time or when the crank time has elapsed.
To get the ShutDown Bypass on Relay 3 with no preheat, Relay 3 must
be configured for Preheat with ShutDown Bypass and have the Preheat
time set to zero.
•
•
•
•
Relay 1 (Stop) and Relay 2 (Start) can be used with a common ground
for three-wire configured generators.
If Relay 3 is configured for preheat, the signal only shows up on Relay
3.
The Preheat on Relay 3 will not overlap the Crank Time if ShutDown
Bypass is not enabled.
If the ShutDown Bypass is enabled, the Preheat on Relay 3 will remain
high for the Crank Time and for the ShutDown Bypass period after
cranking.
•
•
StartStop mode is essentially the same as GlowStop mode with no
preheat on Relay 1.
Stop
Relay 1: Stop
Start
Shutdown
Bypass
Crank
Time
Relay 2: Start (Cranking)
Preheat
Relay 3: Preheat (Glow)
& Shutdown Bypass
Figure 40 StartStop Mode Timing Diagram
975-0082-01-01
85
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix B: Relay Timing
PulseStop Mode
For generators with PulseStop mode starting types (Type 13):
•
•
•
To get the ShutDown Bypass on Relay 3 with no preheat, Relay 3 must
be configured for Preheat with ShutDown Bypass and have the Preheat
time set to zero.
The AGS will make three attempts to stop the generator. If the
generator has still not stopped at the end of the third attempt, the
appropriate Fault will be generated.
Each stop attempt will consist of engaging the stop relay for 5 seconds
and then waiting 20 seconds before checking the state of the Gen Run
Signal to see if the stop attempt was successful.
•
Relay 1 (Stop) and Relay 2 (Start) can be used with a common ground
for three-wire configured generators.
•
•
If Relay 3 is configured for Preheat, the signal only shows up on Relay 3.
The Preheat on Relay 3 will not overlap the Crank Time if ShutDown
Bypass is not enabled.
•
If the ShutDown Bypass is enabled, the Preheat on Relay 3 will remain
high for the Crank Time and for the ShutDown Bypass period after
cranking.
•
•
The “Delay” refers to the “Preheat to Crank Delay” and may be zero.
Cranking will cease when the generator run signal goes high for the
specified hold time or when the crank time has elapsed.
Stop
Relay 1: Stop
Start
Shutdown
Bypass
Crank
Time
Relay 2: Start (Cranking)
Preheat
Relay 3: Preheat (Glow)
& Shutdown Bypass
Figure 41 PulseStop Mode Timing Diagram
86
Xanbus Automatic Generator Start (AGS) Owner’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendix B: Relay Timing
Stop
Relay 1: Stop
Wait
Wait
Wait
Stop
Stop
Stop
Pulse
Pulse
Pulse
Figure 42 PulseStop Mode Relay 1 Behavior
975-0082-01-01
87
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.