White Rodgers Thermostat 150 User Manual

1G66 and 150  
ELECTRIC-HEAT THERMOSTAT  
(Double Line Disconnect)  
INSTALLATION INSTRUCTIONS  
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE  
INSTALLINGOROPERATINGTHISCONTROLCOULDCAUSEPERSONALINJURY  
AND/OR PROPERTY DAMAGE.  
DESCRIPTION  
The Type 1G66 Electric Heat Thermostat is designed for use on  
all types of electrical heating installations such as cable heat,  
baseboards, wall insert heaters, etc.  
50  
60  
40  
70  
The Type 1G66 thermostat is intended for use on 240 or 277  
VAC where local codes require that a double line disconnect  
thermostat be used. This thermostat can also be used on 120  
VAC. (See specific wiring information for 120 VAC.)  
OFF  
80  
Dial Setting: This thermostat may be set anywhere between  
40° and 80°F by simply turning the knob so the indicator on  
knob points to the desired setting.  
The knob may be turned past 40° to the “OFF” position to  
obtain temporary shutdown of the heating equipment for short  
periods of time such as on weekends, vacation, etc. Turning  
knob to “OFF” position will break both sides of line.  
This Thermostat includes:  
NOTE: Only one side of line is broken during normal cycling of  
this thermostat.  
Wall cover plate (required when thermostat will not hide  
wall imperfections behind old thermostat)  
Two cover mounting screws  
Three Temperature Limiting Pins  
PRECAUTIONS  
This control is a precision instrument, and should be handled  
carefully. Rough handling or distorting components could cause  
the control to malfunction. Take care not to push or damage  
the internal bimetal sensing element during installation.  
WARNING  
!
Do not use on circuits exceeding specified voltages.  
Higher voltages will damage control and could cause  
shock or fire hazard.  
CAUTION  
To prevent electrical shock and/or equipment damage,  
disconnect electric power to system, at main fuse or  
circuit breaker box, until installation is complete.  
!
Do not use on inductive loads. Inductive (motor) loads  
will damage control and could cause shock, fire hazard  
or failure of thermostat.  
All wiring must conform to local and national electrical codes  
and ordinances.  
SPECIFICATIONS  
Switch Rating: Non-Inductive  
22A (5000W) 240VAC  
19A (5000W) 277VAC  
22A (2500W) 120VAC  
Temperature Range: 40° to 80°F  
Differential: 3.0°F  
Switch Action: Open on rise  
Contact Structure: Double Line Disconnect - DPST  
PART NO. 37-6756A  
White-Rodgers is a division  
of Emerson Electric Co.  
0610  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Western Digital Network Card Network hard drive User Manual
Whirlpool Washer 8182674 User Manual
Woodstock Router D3080 User Manual
Wyse Technology Webcam wyse usb firmware tool User Manual
Yamaha CD Player CRW8824E User Manual
Yamaha Electronic Keyboard B900 User Manual
Zanussi Freezer 728304 User Manual
Zanussi Washer Z468TX User Manual
Zebra Technologies Printer P1048352 001 User Manual
Zhone Technologies Network Router 6218 13 User Manual