| 	
		 50A62-820   
					Integrated Furnace Control   
					WHITE-RODGERS   
					INSTALLATION INSTRUCTIONS   
					Operator: Save these instructions for future use!   
					FAILURETOREADANDFOLLOWALLINSTRUCTIONSCAREFULLYBEFORE   
					INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL   
					INJURY AND/OR PROPERTY DAMAGE.   
					DESCRIPTION   
					The 50A62-820 is an automatic gas interrupted ignition   
					control that employs a microprocessor to continually   
					monitor, analyze, and control the proper operation of the   
					gas burner, inducer, and fan.   
					Signals interpreted during continual surveillance of the   
					thermostat and flame sensing element initiate automatic   
					ignition of the burner, sensing of the flame, and system   
					shut-off during normal operation.   
					Thesecontrolsincorporatesystemfaultanalysisforquick   
					gas flow shut-off, coupled with automatic ignition retry   
					upon sensing a fault correction.   
					PRECAUTIONS   
					CAUTION   
					GENERAL PRECAUTION   
					! 
					! 
					To prevent electrical shock and/or equipment   
					damage, disconnect electric power to system at   
					main fuse or circuit breaker box until installation   
					is complete.   
					Application of this type of control may cause   
					flame rollout on initial start-up and could cause   
					personal injury and/or property damage.   
					Replace only with exact model number, includ-   
					ing dash number. Failure to use exact replace-   
					ment control could cause personal injury and/or   
					property damage.   
					Label all wires prior to disconnection when ser-   
					vicing controls. Wiring errors can cause im-   
					proper and dangerous operation.   
					This control is not intended for use in locations   
					where it may come in contact with water. Suit-   
					able protection must be provided to shield the   
					control from exposure to water (dripping, spray-   
					ing, rain, etc.).   
					Ifindoubtaboutwhetheryourwiringismillivolt,line,orlow   
					voltage, have it inspected by a qualified heating and air   
					conditioning contractor, or licensed electrician.   
					Do not exceed the specification ratings.   
					All wiring must conform to local and national electrical   
					codes and ordinances.   
					WARNING   
					Do not use on circuits exceeding specified volt-   
					age. Higher voltage will damage control and   
					could cause shock or fire hazard.   
					! 
					This control is a precision instrument, and should be   
					handled carefully. Rough handling or distorting compo-   
					nents could cause the control to malfunction.   
					Do not short out terminals on gas valve or pri-   
					marycontroltotest. Shortorincorrectwiringwill   
					damage thermostat and could cause personal   
					injury and/or property damage.   
					CONTENTS   
					Description ......................................................... 1   
					Precautions ........................................................ 1   
					Specifications..................................................... 2   
					Installation.......................................................... 3   
					Mounting & Wiring   
					Operation ........................................................... 6   
					WHITE-RODGERS   
					EMERSON ELECTRIC CO.   
					9797 REAVIS ROAD   
					ST. LOUIS, MISSOURI 63123-5398   
					
					PART NO. 37-6266A   
					Printed in U.S.A.   
					0119   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				INSTALLATION   
					MOUNTING AND WIRING   
					WARNING   
					NOTE   
					Replace 50A62 control as a unit - no user serviceable   
					! 
					parts.   
					Do not use on circuits exceeding specified volt-   
					age. Higher voltage will damage control and   
					could cause shock or fire hazard.   
					All wiring should be installed according to local and   
					national electrical codes and ordinances.   
					The 50A62 control may be mounted only in a control box   
					of a Lennox furnace.   
					The control must be secured to an area that will experi-   
					ence a minimum of vibration and remain below the maxi-   
					mum ambient temperature rating of 175°F. The control is   
					approved for minimum ambient temperatures of -40°F.   
					CAUTION   
					! 
					To prevent electrical shock and/or equipment   
					damage, disconnect electric power to system at   
					main fuse or circuit breaker box until installation   
					is complete.   
					Any orientation is acceptable.   
					Refer to the wiring diagram and wiring table when con-   
					necting the 50A62 control to other components of the   
					system.   
					Failure to earth ground the appliance or revers-   
					ingtheneutralandhotwireconnectiontotheline   
					can cause shock hazard.   
					UL approved, 105°C rated 18 gauge, stranded, 2⁄64” thick   
					insulation wire is recommended for all low voltage safety   
					circuit connections. Refer to 50A62 specification sheet   
					for recommended terminals to mate with those on the   
					control.   
					UL approved 105°C rated 16 gauge min., stranded, 4⁄64”   
					thick insulation wire is recommended for all line voltage   
					connections. Refer to 50A62 specification sheet for   
					recommended terminals to mate with those on the   
					control.   
					Shut off main gas to heating system until instal-   
					lation is complete.   
					Route and secure all wiring as far from flame   
					as practical to prevent fire and/or equipment   
					damage.   
					After installation or replacement, follow appliance   
					manufacturer’s recommended installation or service   
					instructions to ensure proper operation.   
					3 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				TYPICAL SYSTEM WIRING DIAGRAM   
					HOT   
					(LINE)   
					NEUTRAL   
					(LINE)   
					120 VAC   
					24 VAC CLASS II   
					TRANSFORMER   
					TH   
					24 VAC   
					50A62   
					TR   
					COOL   
					HEAT   
					FAN   
					M1   
					CIRCULATOR   
					BLOWER   
					M2   
					LINE   
					XFMR   
					EAC   
					HUM   
					INDUCER   
					IND   
					IGN   
					IGNITOR   
					HUMIDIFIER   
					GND   
					GND   
					CIR N   
					LINE N   
					XFMR N   
					HUM N   
					EAC N   
					ELECTRONIC   
					AIR CLEANER   
					Y 
					W 
					G 
					R 
					C 
					Y 
					W 
					G 
					R 
					COMPRESSOR   
					CONTACTOR   
					THERMOSTAT   
					FLAME   
					SENSOR   
					PROBE   
					FP   
					PRESSURE SWITCH   
					(N. O.)   
					PS   
					PS   
					HL   
					HIGH LIMIT   
					(N. C.)   
					RO1   
					GND   
					RO2   
					MV   
					ROLLOUT   
					(N. C.)   
					GAS   
					VALVE   
					MV   
					TR   
					TH   
					LEGEND   
					Low Voltage (24 VAC)   
					Line Voltage (120 VAC)   
					N. C. = Normally closed switch   
					N. O. = Normally open switch   
					4 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				TYPICAL SYSTEM WIRING TABLE   
					50A62   
					TERMINAL   
					TERMINAL   
					SYSTEM COMPONENT   
					CONNECTION   
					TYPE   
					W 
					G 
					R 
					Y 
					captive screw   
					captive screw   
					captive screw   
					low voltage thermostat W terminal (or equivalent)   
					low voltage thermostat G terminal (or equivalent)   
					low voltage thermostat R terminal (or equivalent)   
					low voltage thermostat Y terminal (or equivalent)   
					2nd wire from Y terminal goes to 24 VAC HOT side of   
					compressor contactor coil   
					captive screw   
					captive screw   
					C 
					24 VAC COMMON side of compressor contactor coil   
					gas valve (both gas solenoids are connected in parallel)   
					rollout switch OUTPUT   
					MV (2 terminals)   
					RO1   
					RO2   
					rollout switch INPUT   
					PS   
					pressure switch INPUT   
					9-pin   
					connector   
					& harness   
					PS   
					pressure switch OUTPUT   
					GND   
					MUST BE RELIABLY GROUNDED TO CHASSIS   
					high limit switch input   
					HL   
					(unused terminal)   
					IND   
					inducer HOT side   
					IGN   
					ignitor HOT side   
					6-pin   
					GND   
					connector   
					& harness   
					inducer NEUTRAL side   
					ignitor NEUTRAL side   
					GND   
					(unused 2 terminals)   
					COOL   
					HEAT   
					M1   
					spade terminal circulator blower COOL SPEED terminal   
					spade terminal circulator blower HEAT SPEED terminal   
					spade terminal unused circulator blower terminal   
					spade terminal unused circulator blower terminal   
					spade terminal circulator blower FAN SPEED terminal   
					spade terminal input voltage (120 VAC) HOT side   
					spade terminal 24 VAC transformer line voltage HOT side   
					spade terminal circulator blower NEUTRAL terminal   
					spade terminal input voltage (120 VAC) NEUTRAL side   
					spade terminal 24 VAC transformer line voltage NEUTRAL side   
					spade terminal humidifier HOT side   
					M2   
					FAN   
					LINE   
					XFMR   
					CIR N   
					LINE N   
					XFMR N   
					HUM   
					EAC (optional)   
					HUM N   
					EAC N (optional)   
					TR   
					spade terminal electronic air cleaner HOT side   
					spade terminal humidifier NEUTRAL side   
					spade terminal electronic air cleaner NEUTRAL side   
					spade terminal 24 VAC transformer (low voltage COMMON side)   
					spade terminal 24 VAC transformer (low voltage HIGH side)   
					spade terminal flame sensor port*   
					TH   
					FP   
					* maximum recommended flame probe wire length is 36 inches.   
					5 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				OPERATION   
					OPTION SWITCHES   
					flameloss,theinducerblowerremainsenergizedtopurge   
					the system for 5 seconds. When the purge is complete,   
					Theoptionswitchesonthe50A62-820controlareusedto the inducer blower and humidifier are de-energized and   
					determine the length of the heat delay-to-fan-off period. the delay-to-fan-off period begins. After the delay-to-fan-   
					The following table shows the time periods that will result off period ends, the circulator fan and electronic air   
					from the various switch positions.   
					cleaner are de-energized.   
					If flame is not detected, both valves are de-energized, the   
					ignitor is turned off, and the 50A62 control goes into the   
					“retry” sequence. The “retry” sequence provides a 15-   
					second wait following an unsuccessful ignition attempt   
					(flame not detected). After this wait, the ignition sequence   
					is restarted. If this ignition attempt is unsuccessful, one   
					more retry will be made before the control goes into   
					system lockout.   
					OPTION SWITCH POSITIONS   
					HEAT delay-   
					to-fan-off:   
					Set switch   
					#1   
					#2   
					180 sec.   
					120 sec.   
					90 sec.   
					On   
					On   
					Off   
					Off   
					On   
					Off   
					On   
					Off   
					60 sec.*   
					* Factory setting   
					Ifflameisdetected,thenlost,the50A62controlwillrepeat   
					the initial ignition sequence for a total of three “recycles”.   
					After three unsuccessful “recycle” attempts, the control   
					HEAT MODE   
					In a typical system, a call for heat is initiated by closing the will go into system lockout.   
					thermostat contacts. This starts the 50A62 control’s heat-   
					If flame is established for more than 10 seconds after   
					ing sequence. The inducer blower and humidifier are   
					energized (if there is an optional electronic air cleaner on   
					the system, the humidifier is not energized until the   
					electronic air cleaner is energized). The 768A Silicon   
					Nitride ignitor is powered within one second.   
					ignition, the50A62controllerwillcleartheignitionattempt   
					(or retry) counter. If flame is lost after 10 seconds, it will   
					restart the ignition sequence. This can occur a maximum   
					of five times before system lockout.   
					Duringburneroperation, amomentarylossofpowerof50   
					milliseconds or longer will de-energize the main gas   
					valve. When power is restored, the gas valve will remain   
					de-energized and a restart of the ignition sequence will   
					begin immediately.   
					This controller has an adaptive algorithm that reduces the   
					ignitor temperature to slightly greater than the minimum   
					temperature required to ignite gas in each particular   
					application. The control measures the line voltage and   
					determines an initial ignitor temperature setting based on   
					the measurement. After each successful ignition, the   
					control lowers the ignitor temperature slightly for the next   
					ignition attempt. The control continues to lower the ignitor   
					temperature until ignition does not occur, and the control   
					goes into retry mode. For the second attempt to ignite gas   
					within the same call for heat, the control increases the   
					ignitor temperature to the value it was on the third previ-   
					ous successful ignition. After ignition is successful, the   
					control sets the ignition temperature at this value for the   
					next 255 calls for heat, after which the control repeats the   
					adaptive algorithm. The control is constantly making   
					adjustments to the ignitor temperature to compensate for   
					changes in the line voltage.   
					A momentary loss of gas supply, flame blowout, or a   
					shorted or open condition in the flame probe circuit will be   
					sensed within 2 seconds. The gas valve will de-energize   
					and the control will restart the ignition sequence. Re-   
					cycleswillbeginandtheburnerwilloperatenormallyifthe   
					gas supply returns, or the fault condition is corrected,   
					before the last ignition attempt. Otherwise, the control will   
					go into system lockout.   
					If the control has gone into system lockout, it may be   
					possible to reset the control by a momentary power   
					interruption of one second or longer. Refer to PRECAU-   
					TIONARY, SYSTEM LOCKOUT, AND DIAGNOSTIC   
					FEATURES.   
					The 80 VAC Silicon Nitride ignitor manufactured by   
					White-Rodgers must be used. These ignitors are spe-   
					cially designed to operate with the 50A62’s adaptive   
					ignition routine to ensure the most efficient ignitor tem-   
					perature.   
					COOL MODE   
					In a typical system, a call for cool is initiated by closing the   
					thermostat contacts. This starts the 50A62 control’s cool-   
					ing sequence. The compressor is energized and the cool   
					mode delay-to-fan-on period begins. After the delay-to-   
					fan-on period ends, the circulator fan is energized at cool   
					speed. The electronic air cleaner (optional) is also ener-   
					gized. After the thermostat is satisfied, the compressor is   
					de-energized and the cool mode delay-to-fan-off period   
					begins. After the delay-to-fan-off period ends, the circula-   
					tor fan and electronic air cleaner (optional) are de-ener-   
					gized.   
					At the end of the ignitor warm-up time, both valves in the   
					36E manifold gas valve are opened. Flame must be   
					detected within 4 seconds.   
					If flame is detected, the delay-to-fan-on period begins.   
					After the delay-to-fan-on period ends, the circulator fan is   
					energized at heat speed. If there is an optional electronic   
					air cleaner on the system, the electronic air cleaner and   
					the humidifier are energized. When the thermostat is   
					satisfied, the gas valve is de-energized. After proof of   
					6 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SYSTEM LOCKOUT FEATURES   
					MANUAL FAN ON MODE   
					When system lockout occurs, the gas valve is de-ener-   
					gized, the circulator blower is energized at heat speed,   
					and, ifflameissensed, theinducerblowerisenergizedfor   
					5 seconds. The diagnostic indicator light will flash or glow   
					continuously to indicate system status. (System lockout   
					will never override the precautionary features de-   
					scribed above.)   
					If the thermostat fan switch is moved to the ON position,   
					the circulator fan (fan speed) and optional electronic air   
					cleaner are energized. When the fan switch is returned to   
					the AUTO position, the circulator fan and electronic air   
					cleaner (optional) are de-energized.   
					PRECAUTIONARY, SYSTEM   
					LOCKOUT, AND DIAGNOSTIC   
					FEATURES   
					Toresetthecontrolaftersystemlockout, dooneofthe   
					following:   
					1. Interrupt the call for heat at the thermostat for at least   
					one second (if flame is sensed with the gas valve de-   
					energized, interrupting the call for heat at the thermo-   
					stat will not reset the control).   
					PRECAUTIONARY FEATURES   
					The following precautionary features are built into the   
					50A62 control.   
					2. Interrupt the 24 VAC power at the control for at least   
					one second. You may also need to reset the flame   
					rollout sensor switch.   
					1. If, at any time, the flame rollout sensor opens, the gas   
					valve and ignitor are de-energized.   
					3. Afteronehourinlockout,thecontrolwillautomatically   
					reset itself.   
					2. If, at any time, flame is sensed when the gas valve is   
					de-energized, the heat circulator blower and inducer   
					fan are energized and the ignition sequence will go   
					into system lock out. The heat circulator and inducer   
					will remain on as long as flame is detected. If flame   
					is no longer detected, the inducer will turn off in 5   
					seconds and the circulator will turn off using the   
					maximum heat off delay.   
					DIAGNOSTIC FEATURES   
					The 50A62-820 control continuously monitors its own   
					operation and the operation of the system. If a failure   
					occurs, theDIAG1andDIAG2LEDswillindicateafailure   
					code as shown below.   
					3. If, at any time, the flame rollout switch opens, the heat   
					circulator blower and inducer fan are energized and   
					theignitionsequencewillgointosystemlockout. The   
					inducer will remain energized for 5 seconds. The   
					circulator will remain on as long as the flame rollout   
					switch is detected open, then use the maximum heat   
					off delay.   
					SAFETY CIRCUIT   
					Limit Control   
					DIAG 1   
					Slow Flash   
					Off   
					DIAG 2   
					On   
					Pressure Switch   
					Slow Flash   
					Watch Guard - Burners   
					Failed to Ignite   
					Alternate   
					Slow Flash   
					Alternate   
					Slow Flash   
					4. If at any time the main valve sense input does not   
					correspond to the program’s requested gas valve   
					state, the inducer is de-energized and the ignition   
					sequence will go into system lock out. The heat   
					circulator blower will be energized using the maxi-   
					mum heat off delay, provided a heat off delay is   
					already in progress.   
					Flame Sensed Without   
					Valve Energized   
					Slow Flash   
					Off   
					Roll Out Open or 9-Pin   
					Connector Disconnected   
					On   
					On   
					Slow Flash   
					On   
					Bad Board   
					Power On   
					Simultaneous Simultaneous   
					Slow Flash   
					Slow Flash   
					Fast Flash   
					Slow Flash   
					Slow Flash   
					Slow Flash   
					Low Flame   
					Reverse Polarity   
					Low Voltage or   
					Ignitor Disconnected   
					Alternate   
					Fast Flash   
					Alternate   
					Fast Flash   
					Simultaneous Simultaneous   
					Fast Flash Fast Flash   
					Heat Demand   
					7 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Download from Www.Somanuals.com. All Manuals Search And Download.   
				 |