Western Telematic Network Card NBB 1600 D20, NBB 1600E D20, NBB 1600CE D16 User Manual |
WTI Part No.: 13631
Rev. A
NBB-1600-D20/D16 Series
Network Boot Bars
Models:
NBB-1600-D20
NBB-1600E-D20
NBB-1600CE-D16
User’s Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Warnings and Cautions:
INSTALLATION INSTRUCTIONS
SECURE RACKING
If Secure Racked units are installed in a closed or multi-unit rack assembly, they may require
further evaluation by Certification Agencies. The following items must be considered.
1. The ambient within the rack may be greater than room ambient. Installation should be such
that the amount of air flow required for safe operation is not compromised. The maximum
temperature for the equipment in this environment is 45°C. Consideration should be given to
the maximum rated ambient.
2. Installation should be such that a hazardous stability condition is not achieved due to
uneven loading.
INPUT SUPPLY
Check nameplate ratings to assure there is no overloading of supply circuits that could have an
effect on overcurrent protection and supply wiring.
GROUNDING
Reliable earthing of this equipment must be maintained. Particular attention should be given
to supply connections when connecting to power strips, rather than direct connections to the
branch circuit.
No Serviceable Parts Inside; Authorized Service Personnel Only
Do not attempt to repair or service this device yourself. Internal components must be serviced by
authorized personnel only.
•
Shock Hazard - Do Not Enter
Disconnect Power
If any of the following events are noted, immediately disconnect the unit from the outlet and
contact qualified service personnel:
1. If the power cord becomes frayed or damaged.
2. If liquid has been spilled into the device or if the device has been exposed to rain or water.
Two Power Supply Cables
Note that this unit features two separate power circuits, that require a power supply cable for each
circuit. Before attempting to service or remove this unit, please make certain that both power
cables are disconnected.
i
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
FCC Part 15 Regulation
This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection
against harmful interference in a residential installation. This equipment generates, uses, and can
radiate radio frequency energy, and if not installed and used in accordance with the instructions,
may cause harmful interference to radio communications. However, there is no guarantee that
interference will not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by turning the equipment
off and on, the user is encouraged to try to correct the interference by one or more of the following
measures:
•
•
•
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Plug the equipment into an outlet on a circuit that is different from the one used by the
receiver.
•
Consult the dealer or an experienced radio/TV technician for help.
This device complies with Part 15 of the FCC rules. Operation of this device is subject to the
following conditions: (1) This device may not cause harmful interference, and (2) this device must
accept any interference that may cause undesired operation.
WARNING: Changes or modifications to this unit not expressly approved by the
party responsible for compliance could void the user’s authority to operate the
equipment
EMC, Safety, and R&TTE Directive Compliance
The CE mark is affixed to this product to confirm compliance with the following European
Community Directives:
•
•
Council Directive 89/336/EEC of 3 May 1989 on the approximation of the laws of
Member States relating to electromagnetic compatibility;
and
Council Directive 73/23/EEC of 19 February 1973 on the harmonization of the laws of
Member States relating to electrical equipment designed for use within certain voltage
limits;
and
•
Council Directive 1999/5/EC of 9 March on radio equipment and telecommunications
terminal equipment and the mutual recognition of their conformity.
Industry Canada - EMI Information
This Class A digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.
ii
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
2. Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
3. Quick Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.1. Hardware Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.1.1. Apply Power to the NBB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.1.2. Connect your PC to the NBB. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.2. Communicating with the NBB. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
4. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.1. Power Supply Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.2. Connection to Switched Outlets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
4.3. Console Port Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
4.3.1. Connecting a Local PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
4.3.2. Connecting an External Modem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
4.4. Connecting the Network Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
5. Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.1. System Mode and User Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.2. Communicating with the NBB. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
5.2.1. Accessing the Web Browser Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
5.2.2. Accessing the Text Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
5.3. Configuration Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
5.3.1. The General Parameters Menus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
5.3.2. The Serial Parameters Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10
5.3.3. The Plug Parameters Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
5.3.3.1. Plug Passwords and Co-Location Features . . . . . . . . . . . . . . . 5-14
5.3.3.2. The Boot / Sequence Delay Period.. . . . . . . . . . . . . . . . . . . . . 5-15
5.3.4. Network Parameters Menus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-16
5.3.4.1. IP Security Feature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18
5.3.5. The Telnet Parameters Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-20
5.3.6. Web Server Parameters Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-21
5.4. Save Configuration Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-22
6. Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.1. Operation via the Web Browser Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.1.1. The Plug Status Screen - Web Browser Interface . . . . . . . . . . . . . . . . . . 6-1
6.2. Operation via the Text Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
6.2.1. The Plug Status Screen - Text Interface. . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
6.2.2. Switching and Reboot Commands - Text Interface . . . . . . . . . . . . . . . . . 6-4
6.2.3. Applying Commands to Several Plugs - Text Interface. . . . . . . . . . . . . . 6-6
6.3. Logging Out of Command Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
6.4. The Automated Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
6.5. Manual Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
7. Saving and Restoring Configuration Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.1. Sending Parameters to a File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.2. Restoring Saved Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
8. Upgrading the NBB Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
i
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
Appendices:
A. Interface Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Apx-1
A.1. Console Port Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Apx-1
B. Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Apx-2
C. Customer Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Apx-3
Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Index-1
List of Figures
2.1. NBB-1600 Unit (120 VAC Model Shown). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
3.1. Plug Status Screen - Web Browser Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
3.2. Plug Status Screen - Text Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
5.1. Plug Status Screen - Web Browser Interface (Sample Values Show). . . . . . . . . . . . . . . 5-2
5.2. Plug Status Screen - Text Interface (Sample Values Shown) . . . . . . . . . . . . . . . . . . . . . 5-4
5.3. General Parameters Menu - Web Browser Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
5.4. General Parameters Menu - Text Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
5.5. Serial Parameters Menu - Web Browser Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10
5.6. Serial Parameters Menu - Text Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10
5.7. Plug Parameters Menu - Web Browser Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
5.8. Plug Parameters Menu - Text Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
5.9. Network Parameters - Web Browser Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-17
5.10. Network Parameters Menu - Text Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-17
5.11. IP Security Menu - Text Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18
5.12. Telnet Parameters Menu - Web Browser Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-20
5.13. Telnet Parameters Menu - Text Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-20
5.14. Web Browser Parameters Menu - Web Browser Interface . . . . . . . . . . . . . . . . . . . . . . 5-21
5.15. Web Browser Parameters Menu - Text Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-21
6.1. Plug Status Menu - Web Browser Interface (Sample Values Shown). . . . . . . . . . . . . . . 6-2
6.2. Plug Status Screen - Text Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
6.3. The NBB Help Screen - Text Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
A.1. Console Port Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Apx-1
ii
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Introduction
Electronic equipment sometimes "locks-up," requiring a service call just to flip
the power switch to perform a simple reboot. The NBB-1600-D20,
NBB-1600E-D20 and NBB-1600CE-D16 Network Boot Bars give you the
ability to perform this function from anywhere, just point your browser to the
NBB’s IP address, enter the secure user name and password, and you’re just a
click away from remote power On, Off or Reboot!
20 Amp Power Control
The NBB D20 and D16 series Network Boot Bars provide plenty of power for
rack mount applications; the NBB-1600-D20 and NBB-1600E-D20 feature
two separate 20 Amp power circuits, and provide a total of 40 Amps per unit.
The NBB-1600CE-D16 features two 16 Amp power circuits, for a total of 32
Amps per unit.
Intelligent Power Control
In addition to web browser access, the NBB can also communicate over
any TCP/IP network using standard Telnet, or out-of-band using an external
modem and basic VT100 type terminal emulation.
Security Features and Co-Location Features
To ensure security, web browser access requires the user to enter an assigned
user name and password. The NBB provides two levels of operational
passwords; the System Administrator Level, which allows access to all
configuration and switching functions, and the User Level, which only allows
access to assigned plugs and cannot be used to change unit configuration.
In addition to password security features, the NBB also includes an address
specific IP security mask, which can be employed to prevent unauthorized
network access to the NBB command mode.
Easy to Configure, Easy to Use
The NBB can be configured over the network, via modem, or locally via the
NBB console port. Easy to use commands let you assign a location name, set
system parameters and view plug status. Outlets can be switched On, Off, or
booted using plug numbers or names.
1-1
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
Reliability and Support
The NBB is built in the USA and backed by a two year warranty. NetReach
products are installed in thousands of network sites world wide. Our
customers know they can depend on WTI for superior quality and reliability
for their most mission-critical operations.
NBB-1600-D20, NBB-1600E-D20 and NBB-1600CE-D16 Units
This User’s Guide discusses the NBB-1600-D20, NBB-1600E-D20 and
NBB-1600CE-D16 Network Boot Bars. Throughout this User's Guide, all
three units are referred to as the "NBB." The input voltages and maximum
loads are summarized in the table below. All other features function identically
except where noted.
Total
Input
Max. Load Max. Load Max. Load
Model Number
Outlets
Voltage
per Outlet
per Bus
per Unit
NBB-1600-D20
16
16
16
100 to
120 VAC
15 Amps
20 Amps
40 Amps
NBB-1600E-D20
NBB-1600CE-D16
100 to
240 VAC
15 Amps
10 Amps
20 Amps
16 Amps
40 Amps
32 Amps
100 to
240 VAC
Typographic Conventions
Throughout this manual, typefaces and characters have been used to denote the
following:
COURIER FONT Indicates characters typed on the keyboard.
For example, /ON 3or /OFF 5.
[Bold Font]
Text set in bold face and enclosed in square brackets
indicates a specific key.
For example, [Enter] or [Esc].
1-2
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Unit Description
As shown in Figure 2.1, the NBB unit includes power outlets, LEDs and a
manual control button. The items shown in Figure 2.1 are described on the
following page.
1
PLUGS
2
READY
3
ACTIVITY
10BaseT
4
RS232
CONSOLE
(DTE)
5
Network
Boot Bar
6
PLUG 1
PLUG 2
PLUG 3
7
PLUG 14
PLUG 15
PLUG 16
8
PWR
CKT
A
9
PWR
CKT
B
Figure 2.1: NBB-1600 Unit (120 VAC Model Shown)
2-1
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
Manual Switch Button: A Manual Control Button for the unit’s
switched plugs. To manually switch plugs "On" or "Off", press and
hold the control button for approximately three seconds. If desired, the
Manual Switch Button can also be disabled (Section 5.3.1.)
Note: When the Manual Switch Button is used, Boot / Sequence
Delay Times will be applied as described in Section 5.3.3.2.
Ready Indicator: Flashes when ready to receive commands.
Activity Indicator: Flashes to indicate activity at the Network Port.
10Base-T (Network) Port: An RJ45 Ethernet Port for connection to
your TCP/IP network. The default IP Address is 192.168.168.168, for
more information, please refer to Section 5.3.4.
RS232 Console Port: A DB9, RS232 serial port (DTE), for connection
to a local terminal or external modem, as described in Section 4.3.
Master Power Switch: This switch must be "On" in order for the NBB
to function. Note that this switch is not used to set the On/Off status of
the switched outlets.
Switched Plugs and Plug Indicators: For load ratings, please refer to
the instrument nameplate, and the table in Section 1.
•
•
Model NBB-1600-D20: Sixteen (16) 100 to 120 VAC
NEMA 5-15R outlets, split into two separate power circuits.
Circuit A includes plugs 1 through 8, and Circuit B includes plugs
9 through 16.
Models NBB-1600E-D20 and NBB-1600CE-D16: Sixteen (16)
100 to 240 VAC IEC320-C13 outlets, split into two separate power
circuits. Circuit A includes plugs 1 through 8, and Circuit B
includes plugs 9 through 16.
Power Circuit "A" Input Components: An IEC320-C20 AC inlet
and circuit breaker, which supply power to plugs one through 8. Also
includes two mounting screws for Cable Keeper:
•
•
•
Model NBB-1600-D20: 100 to 120 VAC, 20 Amps.
Model NBB-1600E-D20: 100 to 240 VAC, 20 Amps.
Model NBB-1600CE-D16: 100 to 240 VAC, 16 Amps.
2-2
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit Description
Power Circuit "B" Input Components: An IEC320-C20 AC inlet
and circuit breaker, which supply power to plugs 9 through 16. Also
includes two mounting screws for Cable Keeper. Includes same
components as item 8 above.
Rack Mounting Brackets: (Not Shown.)
2-3
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
2-4
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Quick Start
This Quick Start Guide describes a simplified installation procedure for the
NBB-1600-D20, NBB-1600E-D20 and NBB-1600CE-D16 Network
Boot Bars, which will allow you to communicate with the unit in order to
demonstrate basic features and check for proper operation. In order to take
full advantage of the complete range of features offered by this unit, it is
recommended to complete the remainder of this User's Guide after performing
the Quick Start Procedure.
3.1. Hardware Installation
3.1.1.
Apply Power to the NBB
Refer to power rating nameplate on the NBB, and then connect the unit to an
appropriate power source. Note that the NBB features two separate AC inputs
and two separate power busses; connect power cables to the Circuit "A" and
Circuit "B" Power Inlets, install the cable keepers as described in Section 4.1,
then connect the cables to your power source. Refer to the table below for
information concerning power requirements and maximum loads.
Total
Input
Max. Load Max. Load Max. Load
Model Number
Outlets
Voltage
per Outlet
per Bus
per Unit
NBB-1600-D20
16
16
16
100 to
120 VAC
15 Amps
20 Amps
40 Amps
NBB-1600E-D20
NBB-1600CE-D16
100 to
240 VAC
15 Amps
10 Amps
20 Amps
16 Amps
40 Amps
32 Amps
100 to
240 VAC
Set the Main Power Switch in the ON position; the ON LED should light, and
the RDY LED should begin to flash. This indicates that the NBB is ready to
receive commands.
3-1
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
3.1.2. Connect your PC to the NBB
The NBB can either be controlled by a local PC, that communicates with
the unit via cable, controlled via external modem, or controlled via TCP/IP
network. In order to switch plugs or select parameters, commands are issued
to the NBB via either the Network Port or Console Port. Note that it is not
necessary to connect to both the Network and Console Ports, and that the
Console Port can be connected to either a local PC or External Modem.
•
•
•
Network Port: Connect your 10Base-T or 100Base-T network
interface to the NBB Network (10Base-T) port.
Console Port: Use the supplied null modem cable to connect your PC
COM port to the NBB COM (RS232) Port.
External Modem: Use a standard AT to Modem cable to connect your
external modem to the NBB COM (RS232) Port.
Note that when the NBB is shipped from the factory, RS232 Port Parameters
are set as follows: 9600 bps, 8 Data Bits, One Stop Bit, No Parity. Although
the NBB allows these parameters to be easily redefined, for the purpose of this
Quick Start procedure, it is recommended to configure your communications
program to accept these default parameters.
3.2. Communicating with the NBB
The NBB offers two separate user interfaces: the Web Browser Interface and
the Text Interface. The Web Browser interface allows you to contact the NBB
via TCP/IP network, using a standard, JavaScript enabled web browser (such
as Internet Explorer.) The Text Interface consists of a series of ASCII text
menus, which may be accessed via TCP/IP network, Local PC or modem.
Note: The NBB features a default IP Address (192.168.168.168)
and default Subnet Mask (255.255.255.0). This allows network
access to command mode without first setting up the unit’s network
parameters (providing you are contacting the NBB from a node
on the same subnet.) When attempting to access the NBB from a
node that is not on the same subnet, please refer to Section 5.3.4 for
further configuration instructions.
1. Access the Command Mode: This procedure differs slightly,
depending on whether you’re contacting the NBB via the Web Browser
Interface or Text Interface.
a) Web Browser Interface: Start your Web Browser. Enter the
NBB’s default IP address (192.168.168.168) in your browser address
bar and press [Enter]. A password prompt will be displayed. Since
at this point, the user name and password have not yet been defined,
you can simply click OK in response to the prompt. The Plug Status
Screen will be displayed as shown in Figure 3.1.
3-2
Download from Www.Somanuals.com. All Manuals Search And Download.
Quick Start
Figure 3.1: Plug Status Screen - Web Browser Interface
Network Boot Bar v1.41c
Plug | Name
Site ID: (undefined)
| Password | Status | Boot/Seq. Delay | Default |
-----+------------------+-------------+--------+-----------------+---------+
1
2
3
4
5
6
7
8
9
| (undefined)
| (undefined)
| (undefined)
| (undefined)
| (undefined)
| (undefined)
| (undefined)
| (undefined)
| (undefined)
| (undefined)
| (undefined)
| (undefined)
| (undefined)
| (undefined)
| (undefined)
| (undefined)
| (undefined)
| (undefined)
| (undefined)
| (undefined)
| (undefined)
| (undefined)
| (undefined)
| (undefined)
| (undefined)
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
0.5 Secs
0.5 Secs
0.5 Secs
0.5 Secs
0.5 Secs
0.5 Secs
0.5 Secs
0.5 Secs
0.5 Secs
0.5 Secs
0.5 Secs
0.5 Secs
0.5 Secs
0.5 Secs
0.5 Secs
0.5 Secs
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10 | (undefined)
11 | (undefined)
12 | (undefined)
13 | (undefined)
14 | (undefined)
15 | (undefined)
16 | (undefined)
-----+------------------+-------------+--------+-----------------+---------+
“/H” for help.
NBB>
Figure 3.2: Plug Status Screen - Text Interface
3-3
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
b) Text Interface:
i. Via Telnet: Telnet to the default IP address (192.168.168.168).
The Plug Status Screen (Figure 3.2) should be displayed.
ii. Via Local PC: Start your communications program (e.g.,
Hyperterminal) and press [Enter]. The Plug Status Screen
should be displayed (Figure 3.2.) The default parameters for the
Console Port are 9600 bps, No Parity, 8 data bits, One stop bit.
iii. Via Modem: Use your communications program to dial the
number for the phone line connected to your external modem.
In order to communicate with the unit via modem, you must first
access the command mode via Network or Local PC, and use
the Serial Parameters Menu to set the Port Mode to "Modem."
2. Test Switching Functions: You may wish to perform the following
tests in order to make certain that the NBB is responding to commands.
a) Reboot Outlet: If you are communicating with the unit via the Web
Browser Interface, select the button in the "Boot" column for Plug 1,
and then click on "Apply." If you are operating the unit via the Text
interface, type /BOOT 1and press [Enter]. The status indicator
for Plug 1 should go off, pause for a moment, and then go back on,
indicating that the boot cycle has been successfully completed.
b) Switch Outlet Off: From the Web Browser Interface, select the
button in the "Off" column for Plug 1, and then click "Apply." From
the Text Interface, type /OFF 1and press [Enter]. The status
indicator for Plug 1 should go Off, indicating that the command has
been successfully completed. Leave Plug 1 in the "Off" state, and
then proceed to the next step.
c) Switch Outlet On: From the Web Browser Interface, select the
button in the "On" column for Plug 1, and then click "Apply."
From the Text Interface, type /ON 1and press [Enter]. The status
indicator for Plug 1 should then go back On, indicating that the
command has been successfully completed.
3-4
Download from Www.Somanuals.com. All Manuals Search And Download.
Quick Start
3. Log Out: When you have finished communicating with the unit it is
important to always log off by issuing the appropriate NBB command,
rather than simply closing your Telnet or communications program.
When you log off using the proper NBB command, this ensures that the
unit has completely exited from command mode, and is not waiting for
the inactivity timeout to elapse before allowing additional connections.
a) Web Browser Interface: Click on the "Log Out" button.
b) Text Interface: Type /Xand press [Enter].
This completes the Quick Start Guide for the NBB. Prior to placing the unit
into operation, it is recommended to refer to the remainder of this User’s Guide
for important information regarding advanced configuration capabilities and
more detailed operation instructions. If you have further questions regarding
the NBB unit, please contact WTI Customer Support as described Appendix C.
3-5
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
3-6
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Installation
This section provides further details regarding the connections that are made in
the process of installing the NBB.
4.1. Power Supply Connection
Connect the NBB unit to an appropriate power supply. The NBB’s Master
Power Switch must be "On" in order for the unit to operate.
To install the supplied "Cable Keepers", first, make certain that both power
cables are disconnected from your power supply. Next, loosen (but do not
remove) the two Phillips head screws located directly above each power inlet.
Connect the power supply cables to the NBB’s power inlets, then slip the
Cable Keepers over each supply cable, so the notch on the top of each keeper
secures each cable, and the two slots on the bottom of each keeper slide over
the loosened screws. Tighten the Phillips head screws to secure each cable
keeper to the unit, make certain the cables are secure, and then connect the
cables to your power supply.
CAUTIONS:
•
•
•
This device should only be operated with the type of power
source indicated on the instrument nameplate. If you
are not sure of the type of power service available, please
contact your local power company.
Reliable earthing (grounding) of this unit must be
maintained. Particular attention should be given to supply
connections when connecting to power strips, rather than
directly to the branch circuit.
Check nameplate ratings to ensure that there is no
overloading of supply circuits that could have an effect on
overcurrent protection and supply wiring.
4-1
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
4.2. Connection to Switched Outlets
Connect the power cord from your switched device to one of the AC Outlets on
the IPS unit. Note that when power is applied to the IPS, the AC Outlets will
be switched "ON" by default.
•
•
•
NBB-1600-D20: 100 to 120 VAC. Includes two separate power busses.
Each bus can support a total of 20 Amps. Each AC Outlet can support
up to 15 Amps.
NBB-1600E-D20: 100 to 240 VAC. Includes two separate power
busses. Each bus can support a total of 20 Amps. Each AC Outlet can
support up to 15 Amps.
NBB-1600CE-D16: 100 to 240 VAC. Includes two separate power
busses. Each bus can support a total of 16 Amps. Each AC Outlet can
support up to 10 Amps.
4.3. Console Port Connection
The Console Port is a male, RS232C DB9 connector, wired in a DTE
configuration similar to an AT computer. In the default state, the Console port
is configured for 9600 bps, no parity, 8 data bits, 1 stop bit. The Console Port
can be connected to either an external modem or a local PC, but not both items
at the same time. Appendix A describes the Console Port interface.
4.3.1. Connecting a Local PC
When connecting the Console Port to a Local PC, note that the port uses a
DTE configuration. After the Local PC has been connected, make certain to
set the Serial Port Mode to "Console" as described in Section 5.3.2.
4.3.2. Connecting an External Modem
When connecting directly to an external modem, use a standard AT Style
to Modem cable. Make certain that the modem is initialized to the same
default communications parameters as the NBB Console Port. Next, refer
to Section 5.3.2 and set the Serial Port Mode to "Modem". If necessary, you
may also wish to redefine the Modem initialization command at this point as
described in Section 5.3.2. Please refer to the modem user’s guide for more
information.
4-2
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
4.4. Connecting the Network Cable
The Network Port is an RJ45 Ethernet jack, for connection to a TCP/IP
network. Connect your 10Base-T cable to the Network Port. Note that the
NBB includes a default IP address (192.168.168.168) and a default subnet
mask (255.255.255.0.) When installing the NBB in a working network
environment, it is recommended to define network parameters as described in
Section 5.3.4.
Note: The NBB features a 10Base-T Interface. When connecting
to a 100Base-T interface, most router switches will autosense
to determine if the device is 100Base-T or 10Base-T, and then
configure the network interface accordingly. If your router switch
does not autosense, the network interface port must be manually set
to 10Base-T.
This completes the NBB installation instructions. Please proceed to the next
Section for instructions regarding unit configuration.
4-3
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
4-4
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Configuration
5.1. System Mode and User Mode
In order to restrict access to sensitive command functions, the NBB features
two operating modes; System Mode and User Mode.
•
System Mode: Allows access to all configuration menus, switching
functions and status screens. The System Mode Status Screens show
On/Off conditions for all switched outlets, and list all currently defined
system parameters.
•
User Mode: Allows access to status screens and On/Off/Boot
commands, but does not allow access to configuration functions. Users
may only issue commands to, or view status of the plugs that are
specifically allowed by their password.
The NBB will display a password prompt when the unit is contacted via
the Console Port or Network Port. The password entered at this prompt
determines whether the unit will start-up in System Mode or User Mode. If
the System Password is entered, the System Mode will be active. If a Plug
Password is entered, the User Mode will be active. The System Password
is defined via the General Parameters menu (Section 5.3.1), and the Plug
Passwords are defined via the Plug Parameters Menu (Section 5.3.3.)
Notes:
•
•
•
If you wish to restrict access to configuration menus, you must
define the System Password.
If the System Password is not defined, the NBB will always
start-up in System Mode.
If the System Password is not defined, the Password Prompt
will not be displayed when you access the NBB via the Text
Interface. The prompt will always be displayed when the NBB
is contacted via the Web Browser Interface.
•
When the NBB is contacted via Network, the password prompt
will also include a field for the user name. If you have not
defined a user name, then you may leave this field blank, and
only the password is required to gain access to the unit. The
user name prompt is not displayed when the unit is contacted
via the Text Interface.
5-1
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
Figure 5.1: Plug Status Screen - Web Browser Interface (Sample Values Show)
5.2. Communicating with the NBB
In order to configure the unit or invoke command functions, you must first
connect to the NBB and access the command mode. As discussed in Section 3,
the NBB offers two separate command interfaces: the Web Browser Interface,
and the Text Interface.
The NBB also offers three different methods for accessing command mode;
via network, via external modem, or via local console. The Web Browser
Interface is only available when the NBB is contacted via network, and the
Text Interface is available via network, modem or local PC. The sections that
follow describe the procedure for accessing the Web Browser Interface or the
Text Interface.
Note: Configuration functions are only available when you have
logged into command mode using the System Password.
5-2
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration
5.2.1. Accessing the Web Browser Interface
In order to issue commands via the Web Browser Interface, the NBB must
be connected to a TCP/IP network, and your PC must be equipped with a
JavaScript enabled web browser (such as Internet Explorer or
Netscape Navigator.)
1. Start your JavaScript enabled Web Browser.
web browser’s address bar, and then press [Enter].
3. Password Prompt: The NBB will display a prompt, which asks for
your name and password.
a) User Name: If you have not previously defined a user name, then
this field should be left blank. A user name is only required when
one has been defined via the General Parameters menu.
b) Password: Key in your System Password or Plug Password and
then click "OK" (Note that Plug Passwords do not permit access to
configuration functions.)
c) If the System Password has not been defined, simply click the "OK"
button without keying in a name or password.
If a valid password is entered, the Plug Status Screen (Figure 5.1) will appear.
5-3
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
Network Boot Bar v1.41c
Plug | Name
Site ID: (undefined)
| Password | Status | Boot/Seq. Delay | Default |
-----+------------------+-------------+--------+-----------------+---------+
1
2
3
4
5
6
7
8
9
| Server_1
| Server_2
| Server_3
| Server_4
| Router_1
| Router_2
| Router_3
| DSU-CSU_A
| DSU-CSU-B
| (defined)
| (defined)
| (defined)
| (defined)
| (defined)
| (defined)
| (defined)
| (defined)
| (defined)
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
15 Secs
15 Secs
15 Secs
15 Secs
0.5 Secs
0.5 Secs
0.5 Secs
1 Sec
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ON
ON
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
OFF
ON
OFF
ON
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 Sec
10 | Ethernet_Switch | (defined)
0.5 Secs
2 Secs
2 Secs
2 Secs
5 Secs
5 Secs
30 Secs
11 | atmswitch_1
12 | atmswitch_2
13 | atmswitch_3
14 | LINUX_1
15 | LINUX_2
16 | Modem
| (defined)
| (defined)
| (defined)
| (defined)
| (defined)
| (defined)
-----+------------------+-------------+--------+-----------------+---------+
“/H” for help.
NBB>
Figure 5.2: Plug Status Screen - Text Interface (Sample Values Shown)
5.2.2. Accessing the Text Interface
The Text Interface can be accessed via Network, modem or local PC. In order
to access the Text Interface, your installation must include the following:
•
•
•
Access Via Network: The NBB must be connected to your TCP/IP
Network, and your PC must include a communications program (such as
Hyperterminal™.)
Access Via Modem: An external modem must be connected to the
NBB’s Console Port, and a phone line must be connected to the external
modem. Your PC Must include a communications program.
Access Via Local PC: Your local PC Must be connected to the NBB’s
Console Port. The local PC must include a communications program.
To access command mode via the Text Interface, proceed as follows:
1. The NBB is transparent to parity and will accept 7 or 8 bit characters,
but will always answer back at 8 bits, no parity. Make certain your
communication program is set for the appropriate baud rate, bits, parity
and Comm Port.
a) Via Modem: Start your communications program. Dial the
external modem connected to the NBB. Wait for the Connect
message, then proceed to Step 2.
b) Via Local PC: Start your communications program and press
[Enter]. Wait for the connect message, then proceed to Step 2.
5-4
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration
c) Via Network: The NBB includes a default IP address
(192.168.168.168), which allows you to contact the unit from any
network node on the same subnet. When the NBB is installed in a
working network environment, it is recommended that you redefine
the IP Address, Subnet Mask, and Gateway Address as described in
Section 5.3.4.
i. Telnet to the NBB’s IP address. For example, if the IP address
is "192.168.168.168", then on a UNIX system, the Telnet
command would be:
$ telnet 192.168.168.168 [Enter]
ii. If the Telnet connection is refused, this may mean that
either the IP Security feature has denied the connection (See
Section 5.3.4.1), or that unit is operating on a 100Base-T
network that does not autosense for 10Base-T devices (see
Section 4.4.)
2. Password: If the System Password has been defined, the unit will
display the Password Prompt. Key in either the System Password or
Plug Password, and press [Enter]. If the System Password has not been
defined, the prompt will not be displayed when the unit is accessed via
the Text Interface. Note that the Password feature is case sensitive.
3. If a valid System Password or Plug Password is entered, the NBB will
display the Plug Status Screen shown in Figure 5.2, followed by the
"NBB>" Command Prompt.
Note: The Plug Status Screen will not display actual passwords.
The password column will read either "defined" or "undefined",
depending upon whether or not the System Password or Plug
Passwords have been defined.
5-5
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
5.3. Configuration Menus
As described in the sections that follow, configuration parameters for the NBB
can be selected via the Web Browser Interface or Text Interface. Although
the Web Browser and Text Interface provide two separate means for selecting
parameters, both interfaces allow access to essentially the same set of
parameters, and parameters selected via one interface will also be applied to
the other.
Web Browser Interface: Click the "Setup" button to gain access to the
configuration menus; a row of buttons will be displayed along the left hand
edge of the screen. Click the appropriate button to access the desired menu.
Note the following:
•
•
Newly selected parameters will not be activated until you click the
"Apply" button.
Click "Switch Panel" to return to the main status screen.
Text Interface: Refer to the Help Screen (/H) and then enter the appropriate
command to access the desired menu. When the configuration menu appears,
key in the number or letter for the parameter that you wish to define and follow
the instructions in the resulting submenu. Note the following:
•
To exit from a parameters menu, press the [Esc] key.
The following sections describe the options and parameters that can be
accessed via each of the configuration menus. Please note that essentially
the same selection of parameters and options are available via both the Web
Browser Interface and Text Interface.
Note: Configuration menus are only available when the System
Mode is active. Configuration menus are not available if you have
logged in using a Plug Password.
5.3.1. The General Parameters Menus
The General Parameters Menus allow you to select parameters such as the
System Password, User Name, Site I.D., Modem Commands and other options.
•
•
Web Browser Interface: Click the "Setup" button to access the Setup
Menus, and then click the "General Parameters" button. The General
Parameters Menu will be displayed as shown in Figure 5.3.
Text Interface: Type /Gand press [Enter]. The General Parameters
Menu will be displayed as shown in Figure 5.4.
5-6
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration
Figure 5.3: General Parameters Menu - Web Browser Interface
GENERAL PARAMETERS:
1. System Password:
2. User Name:
3. Site ID:
4. Command Echo:
5. Inactivity Timeout:
(undefined)
(undefined)
(undefined)
On
2 Mins
6. Command Confirmation: On
7. Automated Mode:
Off
8. Manual Switch Button: On
9. Command Prompt:
NBB
A. Default Parameters
Enter Selection,
Press <ESC> to Exit ...
Figure 5.4: General Parameters Menu - Text Interface
5-7
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
The General Parameters Menu allows the following parameters to be defined.
•
System Password: The NBB will display a password prompt when
you attempt to access command mode. When the System Password
is entered at log on, the System Mode will be active, allowing access
to both switching functions and configuration menus. (16 Characters,
Default = undefined.)
Notes:
•
•
If the System Password is not defined, then the NBB will start
up in System Mode, and configuration functions will then be
available to anyone who accesses Command Mode.
Passwords and User Names cannot contain nonprintable
characters, spaces, colons (:), plus signs (+) or
quotation marks.
•
User Name: (Optional) The User Name allows you to set up an
additional layer of security for web access to the command mode by
requiring that users correctly enter a name in addition to a password.
Note that the User Name is only required when the unit is accessed via
the Web Interface. (16 Characters, Default = undefined.)
Notes:
•
If a User Name is defined, then users who log in with a Plug
Password (User Mode) will also need to enter this same User
Name at the login prompt when attempting to access command
mode via the Web Browser Interface.
•
The User Name cannot begin with a forward slash (/) or
backslash (\) character, and cannot include non-printable
characters, space characters, asterisks (*) or quotation marks.
•
•
Site ID: Defines a brief text message, which can be used to describe the
location of the NBB unit. (Up to 32 characters, Default = undefined.)
Note: The Site ID Message cannot begin with a forward slash
(/) or backslash (\)character and cannot include non-printable
characters or quotation marks.
Command Echo: Enables/Disables command echo. When enabled,
ASCII commands sent via the Text Interface to the NBB will be echoed
back, allowing keystrokes to be displayed. Note that this feature applies
primarily to the text interface, and has no visible effect on the Web
Browser Interface. (Default = On.)
5-8
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration
•
•
•
Inactivity Timeout: Determines how long the NBB will wait for
additional commands during periods of inactivity. When the Timeout
Period elapses, the user will be disconnected from the NBB command
mode. (Default = 2 Minutes.)
Command Confirmation: When enabled, the NBB will display
a confirmation prompt before executing certain commands. When
disabled, the prompt will be suppressed and commands will be executed
immediately. (Default = On/Enabled.)
Automated Mode: When enabled, the NBB will execute switching,
reboot and exit commands without displaying a confirmation prompt,
status screen or confirmation messages. This allows the NBB to be
controlled by a device that generates commands to control switching
without human intervention. For more information, please refer to
Section 6.4. (Default = Off.)
Note: When this option is enabled, security functions are
suppressed, and users are able to access System Level menus and
control plugs without entering a password. If security is a concern
and the Automated Mode is required, it is recommended to use the
IP Security feature (Section 5.3.4.1) to restrict access.
•
Manual Switch Button: Enables and configures the manual plug
control button. (Default = "On".)
▪
▪
Off: Disables the manual switch button.
On: Enables the manual switch button. When the manual switch
button is pressed and held for approximately three seconds, all
sixteen outlets will be effected.
•
•
Command Prompt: Allows the Text Interface command prompt to be
set to either "NBB", "IPS", or "NPS." (Default = NBB.)
Default Parameters: Resets the NBB to default parameters. All
menu selected parameters, including port names and passwords, will be
cleared. This option is only available via the Text Interface.
Note: If this function is invoked via the Network Port, the IP
Address will not be reset until you break your connection to the
Network Port. If this function is invoked via the Console Port, the
IP Address will be reset immediately.
5-9
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
Figure 5.5: Serial Parameters Menu - Web Browser Interface
SERIAL PARAMETERS:
1. Baud Rate:
2. Data:
3. Parity:
4. Stop:
9600
8 Bit
None
1 Bit
Console
5. Port Mode:
6. Modem Init. Str: ATE0M0Q1&C1&D2S0=1
Enter selection,
Press <ESC> to return to previous menu ...
Figure 5.6: Serial Parameters Menu - Text Interface
5.3.2. The Serial Parameters Menu
The Serial Parameters Menus are used to configure the NBB's serial console
port, and allow you to select parameters such as the baud rate, parity and
modem initialization string. To access the Serial Parameters Menus, proceed
as follows:
•
Web Browser Interface: Click the "Setup" button to access the Setup
Menus, and then click the "Serial Parameters" button. The Serial
Parameters Menu will be displayed as shown in Figure 5.5.
•
Text Interface: Type /Cand press [Enter]. The Serial Parameters
Menu will be displayed as shown in Figure 5.6.
5-10
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration
As shown in Figure 5.5 and Figure 5.6, the Serial Parameters Menus allow you
to define the following parameters:
Note: When the baud rate, data bits, parity or stop bits settings
are changed via the console port, newly selected parameters will
not be applied until the user exits and then re-enters
command mode.
•
•
Baud Rate: The Baud Rate for the serial Console Port.
(Default = 9600 bps.)
Data: The Data bits setting for the serial Console Port.
(Default = 8 Bits.)
•
•
Parity: The parity setting for the serial Console Port. (Default = None.)
Stop: The stop bits setting for the serial Console Port.
(Default = 1 Bit.)
•
Serial Port Mode: Sets up the NBB Console Port for use with either a
local PC ("Console") or an external modem ("Modem"). Note that when
the Serial Port Mode is set to "Modem" the modem initialization string
will be sent every 15 minutes. (Default = Console.)
•
Modem Initialization String: Defines a command string (up to
32 characters long) which can be sent out the serial Console Port
to initialize an external modem. If the Serial Port Mode is set to
"Console", the modem initialization string will not be sent. For more
information on initialization commands, refer to the user’s guide for
your modem. (Default = ATE0M0Q1&C1&D2S0=1)
Note: The Modem Initialization String cannot begin with a
forward slash (/) or backslash (\) character, and cannot include
non-printable characters or quotation marks.
5-11
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
Figure 5.7: Plug Parameters Menu - Web Browser Interface
PLUG #1 PARAMETERS:
1. Plug Name:
2. Password:
3. Boot/Seq. Delay:
4. Power Up Default:
Server_1
(undefined)
0.5 Secs
On
Enter Selection,
Press <ESC> to Exit ...
Figure 5.8: Plug Parameters Menu - Text Interface
5.3.3. The Plug Parameters Menus
The Plug Parameters Menus are used to define Plug Names, Plug Passwords,
boot/sequence delay times and Power Up Default values for each of the NBB’s
Switched AC Outlets.
•
Web Browser Interface: Click the "Setup" button to access the
configuration menus, then click the "Plug Parameters" button. The Plug
Parameters Menu will be displayed as shown in Figure 5.7.
•
Text Interface: Type /P n and then press [Enter] (Where n is
the number or name of the plug you wish to configure.) The Plug
Parameters Menu will be displayed as shown in Figure 5.8.
5-12
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration
Note that when defining plug parameters via the Web Browser Interface, the
desired plug is selected using the dropdown menu at the top of the page. When
defining plug parameters via the Text Interface, the plug is selected using the
/P n command (where n is the number or name of the desired plug.)
The Plug Parameters Menu allows the following parameters to be defined:
•
Plug Name: Assigns a name to the plug. (Up to 32 Characters,
Default = undefined.)
Note: The Plug name cannot begin with a number, the underscore
character (_), the slash character (/) or an asterisk (*).
•
Plug Password: Assigns a password to the corresponding plug.
When this password is entered at login, the user will be able to issue
commands to this plug, and any other NBB plug that shares the same
password as described in Section 5.3.3.1 below. Note that this password
does not allow access to configuration functions. (16 Characters,
Default = undefined.)
Note: Passwords cannot contain nonprintable characters, spaces,
colons (:), plus signs (+) or quotation marks.
•
•
Boot/Seq. Delay: When more than one plug is switched On/Off or
a reboot cycle is initiated, the Boot/Sequence delay determines how
much time will elapse between switching operations, as described in
Section 5.3.3.2. (Default = 0.5 Seconds.)
Power Up Default: Determines how this plug will react when the
Default command (/D) is invoked, or after power to the unit has been
interrupted and restored. When the Default command is invoked, or
power is restored, the NBB will automatically switch each plug On or
Off as specified by the Power-Up Default. (Default = On.)
Note: If you have accessed command mode using the System
password, the Default command will apply to all sixteen switched
plugs. If you have accessed command mode using a plug
password, then the command will only be applied to plugs that
share the same password entered at login.
5-13
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
5.3.3.1. Plug Passwords and Co-Location Features
The Plug Passwords, which are defined via the Plug Parameters Menu(s) allow
you to determine which plugs an individual user will be permitted to control.
When a plug password is entered while logging into command mode, the user
will be able to issue switching and reboot commands for the corresponding
plug, and every other plug that shares this same password.
For example, if the plug password "switch" is defined for plugs 1, 2, and three,
then if a user logs into command mode using the password "switch", that user
will be allowed to issue switching and reboot commands to plugs 1, 2, and 3,
but not plugs 4 through 16.
Note that the Plug Passwords do not allow access to configuration functions,
and users are only allowed to view the status of the plugs that are permitted by
their password.
5-14
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration
5.3.3.2. The Boot / Sequence Delay Period.
The Boot / Sequence Delay value will be applied differently for Reboot
operations as opposed to simple On/Off operations as described below:
1. Reboot Cycles:
a) Single Plug: The Boot/Seq. Delay determines how long the plug
will remain Off before it is switched back On again.
b) Several Plugs: The Boot/Seq. Delay determines how long the plug
will remain in the "Off" condition, and also how long the NBB will
pause before proceeding to the next plug specified.
2. On/Off Switching: The Boot/Seq. Delay determines how long the NBB
will pause before proceeding to the next plug specified by the
ON command.
Examples: Assume that the Boot / Sequence Delays for each plug have been
set as follows: Plug 1 = 1 Second, Plug 2 = 2 Seconds, Plug 3 = 5 Seconds,
Plug 4 = 1 Minute, Plug 5 = 1 Second
If an "On" command is applied to the first five plugs, the NBB will respond
as follows:
1. Turn On Plug 1, Wait 1 Second.
2. Turn On Plug 2, Wait 2 Seconds
3. Turn On Plug 3, Wait 5 Seconds
4. Turn On Plug 4, Wait 1 Minute
5. Turn On Plug 5
If a "Reboot" Command is applied to Plug 3, the NBB will respond as follows:
1. Turn Off Plug 3, Wait 5 Seconds, Turn On Plug 3.
If a Reboot Command is applied to the first five plugs, the NBB will respond
as follows:
1. Turn Off the first five plugs (short delay between plugs.)
2. Wait 1 Second, Turn On Plug 1, Wait 1 Second.
3. Wait 2 Seconds, Turn On Plug 2, Wait 2 Seconds.
4. Wait 5 Seconds, Turn On Plug 3, Wait 5 Seconds.
5. Wait 1 Minute, Turn on Plug 4, Wait 1 Minute.
6. Wait 1 Second, Turn on Plug 5.
5-15
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
5.3.4. Network Parameters Menus
The Network Parameters Menus are used to select the IP Address and other
network parameters.
•
Web Browser Interface: Click the "Setup" button to access the Setup
Menus, and then click the "Network Parameters" button. The Web
Parameters Menu will be displayed as shown in Figure 5.9.
•
Text Interface: Type /Nand press [Enter]. The Network Parameters
Menu will be displayed as shown in Figure 5.10.
Notes:
•
•
Although the Web Browser Interface and Text Interface both
allow configuration of the same network parameters, note that
for the Text Interface, the IP Security feature is configured via a
separate submenu. For more information on IP Security, please
refer to Section 5.3.4.1.
Settings for network parameters depend on the configuration of
your individual network. Contact your network administrator
for appropriate settings.
The Network Parameters Menu allows the following parameters to be defined.
Except where noted, all parameters listed here are available via both the Web
Browser Interface and the Text Interface.
•
•
•
•
•
•
IPAddress: Defines the IP address for the NBB unit.
(Default = 192.168.168.168.)
Subnet Mask: Defines the Subnet Mask for the NBB unit.
(Default = 255.255.255.0.)
Gateway Address: Defines the Gateway Address for the NBB unit.
(Default = undefined.)
Send MSS: Defines the Maximum Segment Size that will be sent by
the NBB. (Default = 536.)
IP Security: Please refer to Section 5.3.4.1 for a detailed description of
the IP Security feature.
MAC Address: Displays the unit’s MAC Address. Please note that this
item only displays the assigned MAC Address, and cannot be used to
redefine the address.
Notes:
•
•
To display the Network Status Screen, type /SNand press
[Enter].
To reset the Network Port, type /Rand press [Enter].
5-16
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration
Figure 5.9: Network Parameters - Web Browser Interface
NETWORK PARAMETERS:
1. IP Address:
2. Subnet Mask:
3. Gateway Address:
4. Send MSS:
207.212.30.80
255.255.255.0
207.212.30.1
536
5. IP Security
MAC Address:
00-09-9b-00-9b-82
Enter Selection,
Press <ESC> to Exit ...
Figure 5.10: Network Parameters Menu - Text Interface
5-17
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
IP SECURITY:
1. Security Mask #1:
2. Mask #1 Action:
3. Security Mask #2:
4. Mask #2 Action:
5. Security Mask #3:
6. Mask #3 Action:
7. Security Mask #4:
8. Mask #4 Action:
9. Security Mask #5:
10. Mask #5 Action:
(undefined)
Permit
(undefined)
Permit
(undefined)
Permit
(undefined)
Permit
(undefined)
Permit
Enter Selection or <ESC> to Exit ...
Figure 5.11: IP Security Menu - Text Interface
5.3.4.1. IP Security Feature
The IP Security feature can be used to restrict unauthorized IP addresses from
establishing a connection with the NBB. In the default state, the NBB accepts
incoming IP connections from all hosts. To configure the IP Security feature,
proceed as follows:
1. Access the IP Security Menu:
a) Web Browser Interface: The IP Security feature is configured
using the fields at the bottom of the Network Parameters Menu as
shown in Figure 5.9.
b) Text Interface: Go to the Network Parameters menu (/N), type 5
and press [Enter]. The IP Security menu will be displayed as shown
in Figure 5.11.
2. The IP Security menu lists five IP Security "masks" along with the
selected permit/deny action for each mask.
a) Each Security Mask prompt defines a specific IP address or range of
addresses. Each Mask Action prompt defines the permit/deny action
for the corresponding mask.
b) Masks are listed in order of ascending priority; Mask 1 has the
lowest priority, Mask 5 has the highest priority.
c) Masks have a cumulative effect; high priority masks supersede the
effect of lower priority masks.
d) Each IP Address consists of a series of four eight bit numbers. The
number 255 is used as a wild card.
5-18
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration
Example 1: Deny access to all hosts except 192.1.1.5:
Security Mask #1: 255.255.255.255
Security Mask #2: 192.1.1.5
Mask #1 Action: Deny
Mask #2 Action: Permit
Since 255 is a wild card, Mask #1 blocks all IP Addresses. Mask #2 then
specifically grants access to 192.1.1.5 only.
Example 2: Allow access only by addresses that begin with 192.
Security Mask #1: 255.255.255.255
Security Mask #2: 192.255.255.255
Mask #1 Action: Deny
Mask #2 Action: Permit
Since 255 is a wild card, Mask 1 blocks all IP addresses. Mask 2 then grants
access to all addresses that begin with 192.
Example 3: Allow access only by addresses that begin with 192, deny access
to 192.1.1.5.
Security Mask #1: 255.255.255.255
Security Mask #2: 192.255.255.255
Security Mask #3: 192.1.1.5
Mask #1 Action: Deny
Mask #2 Action: Permit
Mask #3 Action: Deny
Since 255 is a wild card, Mask 1 blocks all IP addresses. Mask 2 then grants
access to all addresses that begin with 192. Finally, Mask 3 specifically blocks
access by 192.1.1.5.
Note:
•
Mask #5 has priority over the other four masks. If Mask #5 is
set to deny access by "255.255.255.255" (all wild cards), you
will not be able to access NBB Command Mode via network.
Access will only be allowed via a Local PC or external modem
connected to the NBB Console Port.
•
When using the wild card address "255.255.255.255", make
certain that at least one higher priority mask permits access by
your IP address.
5-19
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
Figure 5.12: Telnet Parameters Menu - Web Browser Interface
TELNET PARAMETERS:
1. Service:
2. Telnet Port #:
On
23
Enter Selection,
Press <ESC> to Exit ...
Figure 5.13: Telnet Parameters Menu - Text Interface
5.3.5. The Telnet Parameters Menus
The Telnet Parameters Menus are used to enable/disable Telnet access to the
NBB command mode and select the TCP port for Telnet connections.
•
Web Browser Interface: Click the "Setup" button to access the
configuration menus, and then click the "Telnet Parameters" button to
display the menu shown in Figure 5.12.
•
Text Interface: Type /Tand press [Enter]. The Telnet Parameters
Menu will be displayed as shown in Figure 5.13.
The Telnet Parameters Menus allow the following parameters to be defined.
Please note that all parameters listed here are available via both the Web
Browser Interface and Text Interface.
•
Service: Enables/Disables Telnet communication with the NBB unit.
When this item is set to the "Off" condition, user’s will not be able to
contact the unit via Telnet. (Default = On.)
•
Port Number: Selects the TCP/IP port number that will be used for
Telnet connections. (Default = 23.)
5-20
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration
Figure 5.14: Web Browser Parameters Menu - Web Browser Interface
WEB SERVER:
1. Service:
2. Server Port #:
On
80
Enter Selection,
Press <ESC> to Exit ...
Figure 5.15: Web Browser Parameters Menu - Text Interface
5.3.6. Web Server Parameters Menus
The Web Server Parameters Menus are used to configure the NBB’s internal
web server, which allows the unit to be operated via the Web Browser
Interface.
•
Web Browser Interface: Click the "Setup" button to access the
configuration menus, and then click the Web Server Parameters button.
The Web Server Parameters Menu will be displayed as shown in
Figure 5.14.
•
Text Interface: Type /Wand press [Enter]. The Web Server
Parameters Menu will be displayed as shown in Figure 5.15.
5-21
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
The Web Server Parameters Menu allows the following parameters to be
defined. Please note that all parameters listed here are available via both the
Web Browser Interface and Text Interface.
•
Service: Enables/Disables the NBB’s Web Server. Note that when the
Web Server is disabled, you will not be able to communicate via the
Web Browser Interface. (Default = On.)
•
Port Number: Sets the TCP/IP Port Number. The Port Number can
be set to any valid number except 23; this is because 23 is the default
port number that is used for communication with the unit via Telnet.
(Default = 80.)
5.4. Save Configuration Parameters
The NBB offers two methods for saving parameters; Saving to Memory, and
Saving to an ASCII File.
Saving parameters to memory ensures that your user-defined configuration
will remain intact if power to the NBB is temporarily interrupted. After the
configuration menus have been used to change parameters, the NBB will
prompt you to save parameters before exiting from Command Mode. At this
point, the NBB offers the options to Save parameters, continue without saving,
or revert to the previously saved parameters.
Saving Parameters to an ASCII file allows you to create a "backup" of your
currently defined configuration. As described in Section 7, this provides quick
recovery in the event that the unit is accidentally reset to default parameters,
and also allows you to copy parameters to other NBB units when several units
need to be configured with the same parameters.
Notes:
•
After new Parameters have been applied, the NBB will display
a "Save" prompt. In the Web Browser Interface, this prompt
appears when you leave the configurations menus. In the Text
Interface, the "Save" prompt appears when you disconnect
from the unit. At this point, you have the option of saving new
parameters to memory, continuing without saving, or reverting
to previously saved parameters.
•
If parameters have not been saved, and if power to the NBB
is interrupted, newly defined parameters will be lost. When
power is restored, the unit will then be configured with the
previously saved parameters.
5-22
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Operation
As discussed in Section 5, "Configuration", the NBB offers two separate
command interfaces; the Web Browser Interface and the Text Interface. Note
that Both interfaces offer essentially the same command options and features,
and that parameters defined via the Web Interface will also apply when
communicating via the Text Interface (and vice versa.)
6.1. Operation via the Web Browser Interface
When using the Web Browser Interface, all switching commands are invoked
via the Plug Status Screen, which also displays the status of the NBB’s
switched AC outlets.
6.1.1. The Plug Status Screen - Web Browser Interface
When you log on to the NBB command mode, using the Web Browser
Interface, the first screen that is displayed after login is the Plug Status Screen
(or "Switch Panel".) The Plug Status Screen (Figure 6.1) lists the current
On/Off status of the NBB’s Switched Outlets and provides a series of "radio
buttons" which are used to control switching and rebooting of the outlets.
To invoke switching and reboot commands or view plug status via the Web
Browser Interface, proceed as follows:
1. Access the NBB Command Mode as described in Section 5.2.1.
2. When the Plug Status Screen (Figure 6.1) appears, note that the screen
includes a status field and switching and reboot controls for each of the
NBB’s Switched AC Outlets.
Notes:
•
•
When switching and reboot operations are initiated, Boot/
Sequence Delay times will be applied as described in
Section 5.3.3.2.
Users who log in to command mode with a Plug password, will
only be allowed to issue commands to the plugs allowed by
that password.
3. Switching Plugs On: Click the "On" button next to the desired plug(s),
and then click "Apply." To switch all plugs On, click the "On" button in
the "All Plugs" row, and then click "Apply."
6-1
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
Figure 6.1: Plug Status Menu - Web Browser Interface (Sample Values Shown)
4. Switching Plugs Off: Click the "Off" button next to the desired plug(s),
and then click "Apply." To switch all plugs Off, click the "Off" button
in the "All Plugs" row, and then click "Apply."
5. Reboot Cycle: Click on the "Boot" button next to the desired plug(s),
and then click "Apply." To reboot all plugs, click the "Boot" button in
the "All Plugs" row and then click "Apply."
6. Set Plugs to Power Up Defaults: To set all plugs to their user-defined
Power Up Default On/Off status, click the "Default" button in the "All
Plugs" row and then click "Apply." Note that in order for this command
to function, Power Up Default values for each plug must first be defined
as described in Section 5.3.3.
When each switching, reboot or default command is invoked, the NBB will
display a screen which indicates that a switching operation is in progress, then
return to the Plug Status Screen when the command is complete. At that time,
the Status Screen will list the updated On/Off status of each plug.
6-2
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Network Boot Bar v1.41c
Plug | Name
Site ID: (undefined)
| Password | Status | Boot/Seq. Delay | Default |
-----+------------------+-------------+--------+-----------------+---------+
1
2
3
4
5
6
7
8
9
| Server_1
| Server_2
| Server_3
| Server_4
| Router_1
| Router_2
| Router_3
| DSU-CSU_A
| DSU-CSU-B
| (defined)
| (defined)
| (defined)
| (defined)
| (defined)
| (defined)
| (defined)
| (defined)
| (defined)
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
15 Secs
15 Secs
15 Secs
15 Secs
0.5 Secs
0.5 Secs
0.5 Secs
1 Sec
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ON
ON
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
OFF
ON
OFF
ON
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 Sec
10 | Ethernet_Switch | (defined)
0.5 Secs
2 Secs
2 Secs
2 Secs
5 Secs
5 Secs
30 Secs
11 | atmswitch_1
12 | atmswitch_2
13 | atmswitch_3
14 | LINUX_1
15 | LINUX_2
16 | Modem
| (defined)
| (defined)
| (defined)
| (defined)
| (defined)
| (defined)
-----+------------------+-------------+--------+-----------------+---------+
“/H” for help.
NBB>
Figure 6.2: Plug Status Screen - Text Interface
6.2. Operation via the Text Interface
When using the Text Interface, all switching functions are performed by
invoking simple, ASCII commands. ASCII commands are also used to display
status screens and to log out of command mode. The Text Interface also
includes a Help Menu, which summarizes all available NBB commands. To
display the Text Interface Help Menu (Figure 6.3), type /Hand press [Enter].
6.2.1. The Plug Status Screen - Text Interface
When you log in to the NBB command mode using the Text Interface, the first
screen displayed after login is the Plug Status Screen. The Plug Status Screen
(Figure 6.2) lists the current status of the NBB’s Switched AC Outlets and
displays the firmware version and currently defined Site I.D. Message.
Normally, the Plug Status Screen will also be redisplayed each time a
command is successfully executed. Note however, that if desired, the
Automated Mode (See Section 6.4) can be enabled to suppress the display of
the Plug Status Screen after each command.
6-3
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
Network Boot Bar v1.41c
Display
Site ID: (undefined)
Configuration
/H
Display Help Screen
/G
View/Set General Parameters
/S
/SN
Display Plug Status
Display Network Status
/P [n]
/C
/N
/T
/W
View/Set Plug Parameters
View/Set Serial Parameters
View/Set Network Parameters
View/set Telnet Parameters
View/Set Web Server
Control
/D
Set Plugs to Default
/Boot <n> Boot Plug n
/E
Save Parameters
/On <n>
/Off <n>
/X
Turn On Plug n
Turn Off Plug n
Exit/Disconnect
/R
/DL
Recall Parameters
Download Parameters to File
Utilities
+------------------------------------+ /I
| [n] = optional plug name or number | /U
| <n> = required plug name or number |
Reset Network Interface
Upgrade Firmware
| n+n or n n = plug n and plug n
| n:n = plug n through plug n
|
|
|
|
| *
= all plugs
| ,y = bypass “Sure? (y/n)”
+------------------------------------+
NBB>
Figure 6.3: The NBB Help Screen - Text Interface
6.2.2. Switching and Reboot Commands - Text Interface
These commands can be used to switch plugs On/Off, reboot plugs or set plugs
to their user-defined Power Up Default values. Plugs may be specified by
name or number.
Notes:
•
Wait for the command prompt to appear before entering
additional commands. The prompt will not reappear until the
previous command is complete.
•
•
Commands are not case sensitive. All commands are invoked
by pressing [Enter].
Users who log into command mode with a Plug password, will
only be allowed to issue commands to the plugs allowed by
that password.
•
•
If command confirmation is enabled, the NBB will display the
Status Screen after commands are successfully completed.
When switching or reboot operations are initiated, Boot/
Sequence Delay times will be applied as described in
Section 5.3.3.2.
6-4
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
To switch plugs On/Off, initiate a reboot cycle, or set plugs to their Power Up
Default values, proceed as follows:
1. Switch Plug(s) On: Type /ON n and press [Enter]. Where "n" is the
number or name of the desired plug. For example:
/ON 1 or /ON ROUTER
2. Switch Plug(s) Off: Type /OFF n and press [Enter]. Where "n" is the
number or name of the desired plug. Note that the "/OFF" command
can also be entered as "/OF". For example:
/OFF 2 or /OF ROUTER
3. Boot Plug(s): To initiate a reboot cycle, type /BOOT n and press
[Enter]. Where "n" is a the number or name of the desired plug. Note
that the "/BOOT" command can also be entered as "/BO". For example:
/BOOT 1 or /BO ATMSWTCH
4. Set Plugs to Power Up Defaults: Type /Dand press [Enter]. Plugs
will be set to their default On/Off status (Power Up Default), which is
defined sing the Plug Parameters Menu as described in Section 5.3.3.
Notes:
•
•
When you have accessed command mode using the System
Password, the Default command will be applied to all plugs.
When you have accessed command mode using a Plug (User)
Password, the Default command will only be applied to the
plugs permitted by the password.
5. Suppress Command Confirmation Prompt: To execute a switching
or reboot command without displaying the "Sure?" prompt, include the
",Y" option at the end of the command line. For example:
/ON ROUTER,Y or /BOOT 2,Y
6-5
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
6.2.3. Applying Commands to Several Plugs - Text Interface
As described below, switching and reboot commands can be applied to only
one Switched AC Outlet, or to an assortment of outlets.
Notes:
•
•
When switching or reboot operations are initiated, Boot/
Sequence Delay times will be applied as described in
Section 5.3.3.2.
Switching and reboot commands will only be applied to the
outlets that are allowed by the password that was used to access
command mode.
1. Several Plugs: To apply a switching or reboot command to several
plugs, enter the numbers or names for the plugs, separated by a "plus
sign" (+). For example to switch plugs 1, 4, and 5 Off, enter the
following:
/OFF 1+4+5 [Enter]
2. Series of Plugs: To apply a command to a series of NBB Plugs, enter
the number for the plugs that mark the beginning and end of the series,
separated by a colon. For example, to switch plugs 1 through 3 On,
enter the following:
/ON 1:3 [Enter]
3. All Plugs: To apply a command to all plugs, enter an asterisk in place
of the name or number. For example, to Boot all plugs, enter the
following:
/BO * [Enter]
6-6
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
6.3. Logging Out of Command Mode
When you have finished communicating with the NBB, it is important to
always disconnect using either the "Log Out" button (Web Browser Interface)
or /X command (Text Interface), rather than simply closing your browser
window or communications program.
When you disconnect using the Log Out button or /X command, this ensures
that the NBB has completely exited from command mode, and is not
waiting for the inactivity timeout period to elapse before allowing additional
connections. This ensures that NBB unit will be available to other users, and
they will not have to wait for the timeout period to elapse before accessing the
NBB Command Mode.
6.4. The Automated Mode
The Automated Mode allows the NBB to execute switching and reboot
commands, without displaying menus or generating response messages.
Automated Mode is designed to allow the NBB to be controlled by a device
which can generate commands to control power switching functions without
human intervention.
When the Automated Mode is enabled, the /ON, /OFF, /BOOT, /D and /X
commands are executed without a "Sure?" confirmation prompt and without
command response messages; the only reply to these commands is the "NBB>"
prompt, which is displayed when the command is complete.
Note that although the Automated Mode can be enabled using either the Web
Browser Interface or Text Interface, Automated Mode is designed primarily
for users who wish to send ASCII commands to the NBB without operator
intervention, and therefore does not specifically apply to a GUI style, Web
Browser Interface. When the Automated Mode is enabled, the Web Browser
Interface can still be used to invoke On / Off / Boot commands.
Notes:
•
•
When Automated Mode is enabled, all NBB password security
functions are disabled, and users are able to access System
Level command functions (including the configuration menus)
and control plugs without entering a password.
If you need to enable the Automated Mode, but want to
restrict network access to NBB configuration menus, it is
recommended to enable and configure the IP Security Function
as described in Section 5.3.4.1.
6-7
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
To enable the Automated Mode, access the General Parameters menu (see
Section 5.3.1) and then set the "Automated Mode" option to the "On" state.
When the Automated Mode is enabled, NBB functions will change
as follows:
1. All Password Security Suppressed: When a user attempts to access
the command mode, the password prompt will not be displayed at either
the Console Port or Network Port. Unless specifically restricted by the
IP Security Function, all users will be allowed to access both switching
and configuration functions, and all commands will be immediately
accepted without the requirement to enter a password.
2. Status Screen Suppressed: The status screens will not be
automatically displayed after commands are successfully executed.
Note however, that the /S command can still be invoked to display the
status screen if needed.
3. "Sure?" Prompt Suppressed: All commands are executed without
prompting for user confirmation.
4. Error Messages Suppressed: If the [Enter] key is pressed without
entering a command, the NBB will not respond with the "Invalid
Command" message. Note however, that an error message will still be
generated if commands are invoked using invalid formats or arguments.
All other status display and configuration commands will still function
as normal.
6.5. Manual Operation
In addition to the command driven functions available via the Web Browser
Interface and Text Interface, the NBB’s switched plugs can also be toggled
On and Off manually. To manually toggle plugs On or Off, press the Manual
Control Button, and hold it down for approximately three seconds.
If desired, the Manual Switch Button Option (accessed via the General
Parameters Menu), can be used to completely disable the manual power button
as described in Section 5.3.1.
For more information on the Manual Switch Button Parameter, please refer to
Section 5.3.1.
Note: When the Manual Switch Button is used, Boot / Sequence
Delay Times will be applied.
6-8
Download from Www.Somanuals.com. All Manuals Search And Download.
7. Saving and Restoring
Configuration Parameters
After the NBB has been properly configured, parameters can be downloaded
and saved as an ASCII text file on your local or remote PC. Later, if the
configuration is accidentally altered, the file with the saved parameters can be
uploaded to automatically reconfigure the unit without the need to manually
assign each parameter.
Saved parameters can also be uploaded to other NBB units. This allows rapid
set-up when several units will be configured with the same parameters.
The "Save Parameters" procedure can be performed from any terminal
emulation program (e.g. ProComm, Crosstalk, Hyperterminal, etc.), which
allows downloading of ASCII files.
Note: Although this function is available only via the Text
Interface, parameters that have been defined via the Web Browser
Interface will also be sent to the ASCII file.
7.1. Sending Parameters to a File
1. Start your communications program and access the NBB command
mode using the System Level Password.
2. When the NBB command prompt appears, type /DLand press [Enter].
The NBB will prompt you to prepare your communications program.
Set up your communications program to receive an ASCII download,
and specify a name for the file that will receive the saved parameters
(e.g., NBB.PAR).
3. When the communications program is ready to receive the file, return to
the NBB command mode, and press [Enter] to proceed.
4. The NBB will send a series of ASCII command lines which specify the
currently selected NBB parameters.
7-1
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
7.2. Restoring Saved Parameters
This section describes the procedure for using ProComm to send saved
parameters to the NBB.
Note: Parameters that have been saved to an ASCII file can
only be restored via the Text Interface. This procedure cannot be
performed via the Web Browser Interface.
1. Start your communications program and access the NBB command
mode via the Text Interface as described in Section 5.2.2.
2. If the Password Prompt is displayed, key in your System Level
Password and press [Enter].
3. Configure your communications program to upload an ASCII text file.
4. Upload the file with the saved parameters. If necessary, key in the file
name and directory path.
5. When the upload is complete, make certain to terminate the
communications program’s upload mode.
Note:
•
•
The current On/Off status of each NBB plug will not be saved
or restored. However, the selected default On/Off setting for
each plug will be saved and restored.
When the configuration file is sent to the NBB via telnet, the
unit’s IP Address, Subnet Mask, and Gateway Address will not
be changed until after you exit from command mode.
At this point, saved parameters should have been restored to the NBB unit.
Check the Plug Status Screen, General Parameters Menu, Plug Parameters
Menu and Network Parameters Menu to make certain that saved parameters
have been accurately restored.
7-2
Download from Www.Somanuals.com. All Manuals Search And Download.
8. Upgrading the NBB Firmware
When new, improved versions of the NBB firmware become available, the
"Upgrade Firmware" function can be used to update the unit. Updates can be
installed via the Console Port or Network Port.
Notes:
•
•
•
The upgrade procedure can only be performed via the Text
Interface.
All other network ports will be disabled during the firmware
upgrade procedure.
When the upgrade procedure is complete, all parameters will be
set to their default states. Therefore, it is recommended to save
NBB configuration parameters to an ASCII file (as described in
Section 7) before beginning this upgrade procedure.
1. Obtain the update file. Firmware modifications can either be mailed to
the customer on a CDR, or downloaded from WTI. Place the upgrade
CDR in your disk drive or copy the file to your hard drive.
2. Access the NBB command mode via the Text Interface. When the
password prompt is displayed, key in the System Level Password.
3. When the command prompt appears, type /U and press [Enter]. The
NBB will display a screen which offers the following options:
•
•
•
•
1. Upgrade Sector 0
2. Upgrade Sectors 1 - 4
3. Upgrade Sectors 5 - 7
4. Abort Upgrade
Note: Instructions regarding the proper Sector option will be
supplied when upgrades become available.
Select the Sector Option indicated for the upgrade and press [Enter], or
type 4[Enter] to abort the upgrade procedure.
8-1
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
4. Set your communication program for ASCII Mode, then use the
program’s "Send File" function to transfer the upgrade file to the NBB.
Select ASCII format, then specify the filename and directory location
where the firmware upgrade file resides.
5. If the upload is successful, the NBB will load the upgrade firmware into
memory, and then reboot itself.
Note: If you are performing the upgrade procedure via the
Network Port, the NBB will break the network connection when
the system is reinitialized. However, the NBB will retain the
current settings for the IP Address, the Telnet Port Number, Web
Server Port Number and Console Port Mode and Baud Rate.
6. Incomplete Upload: If the upload is interrupted, times-out, or if the
update file becomes corrupted during transfer, the NBB will display a
screen which asks for confirmation before proceeding. To proceed, type
1and press [Enter], then return to Step 4 above to retry the upload, or
press [Esc] to reboot the NBB unit.
7. Recovery Mode: In the rare event that the NBB operating system
becomes corrupted during installation, front panel indicators will blink,
and the unit will automatically switch to Recovery Mode. If the unit
switches to Recovery Mode, first access the NBB command mode to
reset the Console Port to 9600 bps, Eight Data Bits, No Parity, One Stop
Bit, and then return to step 3 above and repeat the upload procedure.
When firmware upgrades are available, WTI will provide the necessary files
via download or mailed CDROM. At that time, an updated Users Guide or
addendum will also be available.
8-2
Download from Www.Somanuals.com. All Manuals Search And Download.
A. Interface Descriptions
A.1. Console Port Interface
Figure A.1: Console Port Interface
Apx-1
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
B. Specifications
Power Input / Output ; Model NBB-1600-D20 (120 VAC)
AC Input: Two Separate Circuits; 20 Amps Max. per Circuit (40 Amps Total)
• Voltage: 100 - 120 VAC 60 Hz
• Connectors: Two (2) IEC320-C20 Inlets
AC Outputs: Sixteen (16) Plugs, Split into Two 20 Amp Circuits.
• Connectors: Sixteen (16) NEMA 5-15R Outlets
• Load:
Each Outlet: 15 Amps
Circuit "A" (Plugs 1 to 8): 20 Amps Total
Circuit "B" (Plugs 9 to 16): 20 Amps Total
Power Input / Output ; Model NBB-1600E-D20 (208 VAC)
AC Input: Two Separate Circuits; 20 Amps Max. per Circuit (40 Amps Total)
• Voltage: 100 - 240 VAC 50/60 Hz
• Connectors: Two (2) IEC320-C20 Inlets
AC Outputs: Sixteen (16) Plugs, Split into Two 20 Amp Circuits.
• Connectors: Sixteen (16) IEC320-C13
• Load:
Each Outlet: 15 Amps
Circuit "A" (Plugs 1 to 8): 20 Amps Total
Circuit "B" (Plugs 9 to 16): 20 Amps Total
Power Input / Output ; Model NBB-1600CE-D16 (230 VAC)
AC Input: Two Separate Circuits; 16 Amps Max. per Circuit (32 Amps Total)
• Voltage: 100 - 240 VAC 50/60 Hz
• Connectors: Two (2) IEC320-C20 Inlets
AC Outputs: Sixteen (16) Plugs, Split into Two 16 Amp Circuits.
• Connectors: Sixteen (16) IEC320-C13
• Load:
Each Outlet: 10 Amps
Circuit "A" (Plugs 1 to 8): 16 Amps Total
Circuit "B" (Plugs 9 to 16): 16 Amps Total
Console / Modem Port Interface:
Connector: DB9M, RS232C, DTE
Coding: Serial ASCII, 8 Bits, No Parity
Physical / Environmental:
Size:
• Length: 43.75" (111.1 cm)
• Depth: 3.00" (7.6 cm)
• Width: 1.75" (4.5 cm)
Weight: 12 lbs. Shipping Weight
Temperature: (Operating) 32°F to 122°F (0°C to 50°C)
Humidity: 10 - 90% RH
Apx-2
Download from Www.Somanuals.com. All Manuals Search And Download.
Appendices
C. Customer Service
Customer Service hours are from 8:00 AM to 5:00 PM, PST/PDT, Monday
through Friday. When calling, please be prepared to give the name and model
of the unit, its serial number and a description of its symptoms. If the unit
should need to be returned for factory repair it must be accompanied by a
Return Authorization number from Customer Service.
WTI Customer Service
5 Sterling
Irvine, California 92618
Toll Free Service Line: 1-888-280-7227
Local Phone: (949) 586-9950
Service Fax: (949) 457-8138
Email: [email protected]
Apx-3
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
Trademark and Copyright Information
WTI and Western Telematic are trademarks of Western Telematic Incorporated.
All other product names mentioned in this publication are trademarks of their
respective companies.
Information and descriptions contained herein are the property of Western
Telematic, Inc.. Such information and descriptions may not be copied,
disseminated or distributed without the express written consent of Western
Telematic, Incorporated.
©Copyright Western Telematic, Inc. 2005. All rights reserved. Printed in the
United States of America.
February 2006
WTI Part Number: 13631, Rev. A
Apx-4
Download from Www.Somanuals.com. All Manuals Search And Download.
Index
A
B
F
G
Activity Indicator
Automated Mode
2-2 Firmware Setup
5-9, 6-7 Firmware Upgrade
Front Panel
5-1 to 5-18
8-1 to 8-2
2-1 to 2-2
Baud Rate
Console Port
Boot/Sequence Delay
5-11 Gateway Address
5-16
5-6 to 5-9
i
5-15 General Parameters Menu
6-8 Grounding
Boot/Sequence Delay Time
Booting Plugs
6-5
6-6
H
Boot Command
Button Mode
Hardware Description
5-9
2-1 to 2-2
4-1 to 4-2
6-3
Hardware Installation
C
Cable Keeper
Help Screen
2-2
4-1
I
Cable Keepers
Co-location
Inactivity Timeout
5-14
5-9
2-1 to 2-2
4-1 to 4-2
Apx-1
Indicators
Command Confirmation
Command Echo
Command Mode Access
Local PC
5-9, 6-5, 6-8
Installation
Interface Description
IP Address
Default
IP Security
5-8
5-2 to 5-4
5-4
5-16
4-3, 5-3, 5-16
5-18 to 5-19
Modem
Network
5-4
5-4
J
Text Interface
5-4 to 5-5
5-3 to 5-4
5-9
5-1 to 5-18
5-6 to 5-19
5-9
JavaScript
5-3
Web Browser Interface
Command Prompt
Configuration
Menus
Confirmation Prompt
Console Port
Baud Rate
Data Bits
L
LED Indicators
Local PC
Logging Out
2-1 to 2-2
4-2, 5-4
6-7
2-2, 4-2, 5-11, Apx-1
M
5-11
5-11
5-11
MAC Address
Manual Operation
5-16
6-8
Parity
Manual Switch Button
Master Power Switch
Maximum Segment Size
Modem
Connection
Modem Init String
2-2, 5-9, 6-8
2-2
Stop Bits
Customer Service
5-11
Apx-3
5-16
5-4, 5-11
4-2
D
Data Bits
5-11
5-13
5-9
5-15
5-18
Default On/Off
Default Parameters
Delay Period
Deny Access
Disable Telnet
5-11
N
Network Access
Network Parameters Menus
Network Port
Network Status Screen
5-4, 5-5
5-16 to 5-19
2-2, 4-3, 5-16 to 5-19
5-16
5-20 to 5-21
7-1
Downloading Parameters
Duplex Mode
5-8
O
E
Error Messages
Ethernet Port
Off Command
On Command
Operation
6-5 to 6-6
6-5 to 6-6
6-1 to 6-8
6-8
6-8
2-2, 4-3
4-2, 5-11
External Modem
Manual
Text Interface
Web Browser Interface
6-3 to 6-5
6-1 to 6-3
Index-1
Download from Www.Somanuals.com. All Manuals Search And Download.
NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide
P
S
Parameters
Restoring
Saving
Parity
Password
Plug
System
User
Permit Access
Plugs
Plug Control
Plug Control Button
Plug Name
5-1 to 5-18
7-2
5-22, 7-1
Saving Parameters
Sectors
Security
Segment Size
Send MSS
Sequence Delay
5-22, 7-1
8-1
5-1, 5-18 to 5-19
5-16
5-11
5-1, 5-3, 5-5, 6-8
5-16
5-13
5-8
5-13
5-18
2-2
5-13 to 5-14, 5-15
5-10 to 5-11
2-2, 4-2
5-11
Serial Parameters Menu
Serial Port
Serial Port Mode
Service
Telnet
Web Server
Apx-3
5-20
5-22
5-8
Apx-2
5-11
6-6
5-9
5-13
5-12 to 5-14
5-13
Site I.D. Message
Specifications
Stop Bits
Subnet Mask
Sure Prompt
Switched Outlets
Switched Plugs
Switching Plugs
System Mode
System Password
Plug Parameters Menu
Plug Password
Plug Status Screen
Text Interface
Web Browser Interface
Port Number
Telnet
6-8
6-3
6-1
5-16
5-9, 6-5, 6-8
2-2
4-2
5-20
5-22
6-1 to 6-8, 6-5
5-1, 5-14
5-8
Web Server
Power Control
Manual
6-8
6-3 to 6-5
6-1 to 6-3
2-2
i, 4-1
5-13, 6-2
T
Technical Support
Telnet
Text Interface
Web Browser Interface
Power Inlet
Power Supply
Power Up Default
Apx-3
Disable
Port Number
Service
5-20 to 5-21
5-20
5-20
Q
Telnet Parameters Menu
Text Interface
Timeout
5-20
5-4 to 5-5, 6-3 to 6-5
5-9
Quick Start Procedure
3-1 to 3-4
R
Rack Mounting
i
2-2
6-1 to 6-8
6-2, 6-5
5-9
U
Unit Description
Upgrade Firmware
Uploading Parameters
User Mode
Ready Indicator
Rebooting Plugs
Reboot Cycle
Reset Parameters
Restoring Parameters
2-1 to 2-2
8-1 to 8-2
7-2
5-1, 5-14
5-3, 5-8
5-13
7-2
User Name
User Password
W
Warnings and Cautions
i
Web Browser Interface 5-3 to 5-4, 6-1 to 6-3
Web Server
Port Number
Service
5-22
5-22
Web Server Parameters Menu
Wild Card
5-21 to 5-22
5-18
Index-2