INFRARED VENT-FREE PROPANE/LP GAS HEATER
This appliance may be installed in an aftermarket* manufactured (mobile) home,
where not prohibited by state or local codes.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
OWNER’S OPERATION AND INSTALLATION MANUAL
Models: VP1600D, VP1600ITA, VP2600D, and VP2200ITA
WARNING: If the information in this manual is not followed exactly, a fire or
explosion may result causing property damage, personal injury, or loss of life.
— Do not store or use gasoline or other flammable vapors and liquids in the
vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the
gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a qualified installer, service
agency, or the gas supplier.
®
Save this manual for future reference.
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY
WARNINGS Continued
WARNING ICON
G
001
INFORMATION
WARNING: Any change to this heater or its controls can be dangerous.
1. This appliance is only for use with the type of gas indicated on the rating plate.
This appliance is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) inside any structure. Locate propane/
LP supply tank(s) outdoors.
Continued
3. This heater shall not be installed in a bedroom or bathroom.
4. If you smell gas
• Shut off gas supply
• Do not try to light any appliance
• Do not touch any electrical switch; do not use any phone in your building
• Immediately call your gas supplier from a neighbor’s phone. Follow the
gas supplier’s instructions
• If you cannot reach your gas supplier, call the fire department
5. Never install the heater
• in a recreational vehicle
• where curtains, furniture, clothing, or other flammable objects are less than
36 inches from the front, top, or sides of the heater
• as a fireplace insert
• in high traffic areas
• in windy or drafty areas
6. Always run heater with plaque control knob at the 1, 2, 3, or 4 locked posi-
tions. Never set control knob between locked positions. Poor combustion and
higher levels of carbon monoxide may result.
7. This heater needs fresh, outside air ventilation to run properly. This heater has
an oxygen depletion sensor (ODS) pilot light safety system. The ODS shuts
down the heater if not enough fresh air is available. See Fresh Air for Combus-
tion and Ventilation, pages 5 through 8.
8. If heater shuts off, do not relight until you provide fresh, outside air. If heater
keeps shutting off, have it serviced.
9. Do not run heater
• where flammable liquids or vapors are used or stored
• under dusty conditions
10. Never place any objects on the heater.
11. Surface of heater becomes very hot when running heater. Keep children and
adults away from hot surface to avoid burns or clothing ignition. Heater will
remain hot for a time after shut-down. Allow surface to cool before touching.
12. Carefully supervise young children when they are in same room with heater.
13. Make sure grill guard is in place before running heater.
14. Do not use heater if any part has been under water. Immediately call a quali-
fied service technician to inspect the room heater and to replace any part of the
control system and any gas control which has been under water.
15. Turn off and unplug heater and let cool before servicing. Only a qualified
service person should service and repair heater.
16. Operating heater above elevations of 4,500 feet could cause pilot outage.
3
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
Thermostat Control Knob (Models VP1600ITA and VP2200ITA Only)
Piezo Ignitor (Models VP1600ITA and VP2200ITA Only)
Control Knob
PRODUCT
IDENTIFICATION
Grill
Guard
Burners
Front
Panel
Heater
Cabinet
Figure 1 - Vent-Free Propane/LP Gas Heater (Model VP2200ITA Shown)
Install and use heater with care. Follow all local codes. In the absence of local
codes, use the latest edition of National Fuel Gas Code ANSI Z223.1, also known
as NFPA 54*.
LOCAL CODES
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
1. Remove heater from carton.
UNPACKING
PRODUCT
2. Remove all protective packaging applied to heater for shipment.
3. Check heater for any shipping damage. If heater is damaged, promptly inform
dealer where you bought heater.
Safety Device
This heater has a pilot with an Oxygen Depletion Sensor Shutoff System (ODS).
FEATURES The ODS/pilot is a required feature for vent-free room heaters. The ODS/pilot shuts
off the heater if there is not enough fresh air.
Piezo Ignition System
This heater has a piezo ignitor. This system requires no matches, batteries, or other
sources to light heater.
Thermostatic Heat Control
(Models VP1600ITA and VP2200ITA Only)
This heater has a thermostat sensing bulb and thermostat control. This results in the
greatest heater comfort. This can also result in lower gas bills.
4
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING
WARNING ICON
G
001
FRESH AIR
FOR
COMBUSTION
AND
This heater shall not be installed in a confined space unless
provisions are provided for adequate combustion and ventilation
air. Read the following instructions to insure proper fresh air for
this and other fuel-burning appliances in your home.
Today’s homes are built more energy efficient than ever. New materials, increased
insulation, and new construction methods help reduce heat loss in homes. Home
owners weather strip and caulk around windows and doors to keep the cold air out
and the warm air in. During heating months, home owners want their homes as
airtight as possible.
VENTILATION
While it is good to make your home energy efficient, your home needs to breathe.
Fresh air must enter your home. All fuel-burning appliances need fresh air for
proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from
the house to operate. You must provide adequate fresh air for these appliances.
This will insure proper venting of vented fuel-burning appliances.
PROVIDING ADEQUATE VENTILATION
The following is exerpts from National Fuel Gas Code. NFPA 54/ANSI Z223.1,
Section 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation classifications:
1. Unusually Tight Contruction; 2. Unconfined Space; 3. Confined Space.
The information on pages 5 through 8 will help you classify your space and provide
adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for
combustion and ventilation. However, in buildings of unusually tight construction,
you must provide additional fresh air.
Unusually tight construction is defined as construction where:
a. walls and ceilings exposed to the outside atmosphere have a continu-
ous water vapor retarder with a rating of one perm or less with open-
ings gasketed or sealed and
b. weather stripping has been added on openable windows and doors and
c. caulking or sealants are applied to areas such as joints around window
and door frames, between sole plates and floors, between wall-ceiling
joints, between wall panels, at penetrations for plumbing, electrical, and
gas lines, and at other openings.
If your home meets all of the three criteria above, you must provide addi-
tional fresh air. See Ventilation Air From Outdoors, page 8.
If your home does not meet all of the three criteria above, proceed to page 6.
Unconfined Space
The National Fuel Gas Code, ANSIZ223.1, 1992, Section 5.3 defines uncon-
fined space as having a minimum air volume of 50 cubic feet (127 cubic cm) for
each 1000 Btu/Hr input rating of all appliances in the space (cubic feet equals
length x width x height of space). Include adjoining rooms only if there are
doorless passageways or ventilation grills between the rooms.
Confined Space
The National Fuel Gas Code, ANSIZ223.1, 1992, Section 5.3 defines confined
space as having an air volume of less than 50 cubic feet (127 cubic cm) for each
1000 Btu/Hr input rating of all appliances in the space (cubic feet equals length
x width x height of space). Include adjoining rooms only if there are doorless
passageways or ventilation grills between the rooms.
Continued
5
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
FRESH AIR
FOR
Determining if You Have a Confined or Unconfined Space
Use this worksheet to determine if you have a confined or unconfined space.
COMBUSTION
AND
Space: Includes the room in which you will install heater plus any adjoining rooms with
doorless passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x width x height).
VENTILATION
Length x Width x Height =
___________________
cu. ft. (volume of space)
Continued
Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) =
2560 cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with grills or openings, add the
volume of these rooms to the total volume of the space.
2. Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space
can support.
____________ (volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr
the space can support)
Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. =
Btu/Hr the space can support)
51.2 or 51,200 (maximum
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free heater
Gas water heater*
Gas furnace
Vented gas heater
Gas fireplace logs
Other gas appliances*
Total
___________________ Btu/Hr
___________________ Btu/Hr
___________________ Btu/Hr
___________________ Btu/Hr
___________________ Btu/Hr
+ ___________________ Btu/Hr
= ___________________ Btu/Hr
Example: Gas water heater
Vent-free heater
Total
40,000
18,000
58,000
Btu/Hr
Btu/Hr
Btu/Hr
+
=
* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the
outdoors and vents to the outdoors.
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr
used.
_________________ Btu/Hr (maximum the space can support)
_________________ Btu/Hr (actual amount of Btu/Hr used)
Example: 51,200 Btu/Hr (maximum the space can support)
58,000 Btu/Hr (actual amount of Btu/Hr used)
The space in the above example is a confined space because the actual Btu/Hr used is more
than the maximum Btu/Hr the space can support. You must provide additional fresh air.
Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the extra space provides
an unconfined space, remove door to adjoining room or add ventilation grills between
rooms. See Ventilation Air From Inside Building, page 7.
B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 8.
C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space
is an unconfined space. You will need no additional fresh air ventilation.
6
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
FRESH AIR
FOR
COMBUSTION
AND
WARNING
If the area in which the heater may be operated is smaller than
that defined as an unconfined space, provide adequate combus-
tion and ventilation air by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3.
VENTILATION
VENTILATION AIR
Ventilation Air From Inside Building
Continued
This fresh air would come from an adjoining unconfined space. When ventilating to an
adjoining unconfined space, you must provide two permanent openings: one within 12" of the
ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and
2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow
the National Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and
Ventilation for required size of ventilation grills or ducts.
WARNING
Rework worksheet, adding the space of the adjoining unconfined
space. The combined spaces must have enough fresh air to supply all
appliances in both spaces.
12"
Ventilation Grills
Into Adjoining Room,
Ventilation
Grills
Option 2
Or
into Adjoining
Room,
Option 1
Remove
Door into
Adjoining
Room,
Option 3
12"
Figure 2 - Ventilation Air from Inside Building
Continued
7
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
Ventilation Air From Outdoors
FRESH AIR
FOR
COMBUSTION
AND
Provide extra fresh air by using ventilation grills or ducts. You must provide two perma-
nent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these
items directly to the outdoors or spaces open to the outdoors. These spaces include attics
and crawl spaces.
IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermo-
stat-controlled power vent. Heated air entering the attic will activate the power vent.
VENTILATION
Continued
Ventilated
Outlet
Attic
Air
Outlet
Air
To Attic
To
Crawl
Space
Inlet
Air
Ventilated
Inlet Air
Crawl Space
Figure 3 - Ventilation Air from Outdoors
8
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLING
TO WALL
NOTICE
A qualified service person must install heater. Follow all local codes.
CHECK GAS TYPE
Use only propane/LP gas. If your gas supply is not propane/LP, do not install
heater. Call dealer where you bought heater for proper type heater.
INSTALLATION ITEMS
Before installing heater, make sure you have the items listed below.
• external regulator (supplied by
installer, see page 14)
• sediment trap
• tee joint
• manual shutoff valve *
• ground joint union
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• pipe wrench
• test gauge connection *
(see Figure 14, page 15)
* An AGA design certified manual shutoff valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Purchase the optional AGA design certified
manual shutoff valve from your dealer. See Accessories, page 31.
LOCATING HEATER
This heater is designed to be mounted on a wall.
WARNING
WARNING ICON
G
001
Maintain the minimum clearances shown in Figure 4 (page 10). If you
can, provide greater clearances from floor, ceiling, and joining wall.
You can locate heater on floor, away from a wall. An optional floor mounting stand is
needed. Purchasethefloormountingstandfromyourdealer. SeeAccessories, page31.
WARNING
WARNING ICON
G
001
Never install the heater
• in a bedroom or bathroom
• in a recreational vehicle
• wherecurtains,furniture,clothing,orotherflammableobjectsare
less than 36 inches from the front, top, or sides of the heater
• as a fireplace insert
• in high traffic areas
• in windy or drafty areas
CAUTION
WARNING ICON
G
001
If you install the heater in a home garage
• heater pilot and burner must be at least 18 inches above floor
• locate heater where moving vehicle will not hit it
CAUTION
This heater creates warm air currents. These currents move heat
to wall surfaces next to heater. Installing heater next to vinyl or
cloth wall coverings or operating heater where impurities in the air
(such as tobacco smoke) exist, may discolor walls.
IMPORTANT: Vent-free heaters add moisture to the air. Although this is beneficial, in-
stalling heater in rooms without enough ventilation air may cause mildew to form from
too much moisture. See Fresh Air for Combustion and Ventilation, pages 5 through 8.
Continued
9
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
For convenience and efficiency, install heater
• where there is easy access for operation, inspection, and service
• in coldest part of room
INSTALLING
TO WALL
Continued
An optional fan kit is available from your dealer. See Accessories, page 31 If
planning to use fan, locate heater near an electrical outlet.
CEILING
36"
Minimum
8"
Minimum
From
Sides Of
Heater
Left
Side
Right
Side
3"
Minimum To Top Surface
Of Carpeting, Tile Or Other
Combustible Material
FLOOR
Figure 4 - Mounting Clearances As Viewed From Front of Heater
THERMOSTAT SENSING BULB
(Models VP1600ITA and VP2200ITA Only)
The thermostat sensing bulb has been placed inside the heater for protection during
shipping.
Locating Thermostat Sensing Bulb
1. Remove front panel of heater (see Figure 7, page 11).
2. Locate thermostat sensing bulb just under burner assembly.
IMPORTANT: Attach thermostat sensing bulb to back of heater for proper operation.
Attaching Thermostat Sensing Bulb
1. Remove thermostat sensing bulb from holders inside heater. Route through slot
opening in bottom of heater.
2. Place clamp on thermostat sensing bulb as shown in Figure 5. Clamp is provided
in hardware package.
3. Snap clamp into upper mounting hole as shown in Figure 5. Mounting hole is
located on lower left edge on back of heater. Make sure the thermostat sensing
bulb is pointing up.
Thermostat
Sensing Bulb
Clamp
Figure 5 - Attaching Thermostat Sensing Bulb
10
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLING HEATER TO WALL
Mounting Bracket
The mounting bracket is located on back panel of heater. It has been taped there for
shipping. Remove mounting bracket from back panel.
INSTALLING
TO WALL
Continued
Mounting
Bracket
Figure 6 - Mounting Bracket Location
Removing Front Panel Of Heater
1. Remove two screws near bottom corners of front panel.
2. Lift straight up on grill guard until it stops. Grill guard will slide up about 1/4".
3. Pull bottom of front panel forward, then down.
Figure 7 - Removing Front Panel Of Heater
Methods For Attaching Mounting Bracket To Wall
Only use last hole on each end of mounting bracket to attach bracket to wall. These
two holes are 16 inches apart from their centers. Attach mounting bracket to wall in
one of two ways.
1. Attaching to wall stud
2. Attaching to wall anchor
Attaching to wall stud This method provides the strongest hold. Insert mounting
screws through mounting bracket and into wall studs.
Attaching to wall anchor This method allows you to attach mounting bracket to
hollow walls (wall areas between studs) or to solid walls (concrete or masonry).
Decide which method better suits your needs. Either method will provide a secure
hold for the mounting bracket.
Continued
11
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
Marking Screw Locations
1. Tape mounting bracket to wall where heater will be located. Make sure mount-
ing bracket is level.
INSTALLING
TO WALL
Continued
WARNING
WARNING ICON
G
001
Maintain minimum clearances shown in Figure 8. If you can,
provide greater clearances from floor and joining wall.
2. Mark screw locations on wall (see Figure 8).
Note: Only mark last hole on each end of mounting bracket. Insert mounting
screws through these holes only.
3. Remove tape and mounting bracket from wall.
13"
Min.
9 1/4"
Min.
16"
16"
Only Insert Mounting
Screws Through Last
Hole On Each End
Only Insert Mounting
Screws Through Last
Hole On Each End
18 3/4"
Min.
18 3/4"
Min.
AjdoingWal
AjdoingWal
Floor
Floor
Models VP2600D and VP2200ITA
Models VP1600D and VP1600ITA
Figure 8 - Mounting Bracket Clearances
Attaching Mounting Bracket To Wall
Note: Wall anchors, mounting screws, and spacers are in hardware package. The
hardware package is provided with heater.
Attaching to wall stud method
For attaching mounting bracket to wall studs
1. Drill holes at marked locations using 9/64" drill bit.
2. Place mounting bracket onto wall. Line up last hole on each end of bracket with
holes drilled in wall.
3. Insert mounting screws through bracket and into wall studs.
4. Tighten screws until mounting bracket is firmly fastened to wall studs.
Attaching to wall anchor method
For attaching mounting bracket to hollow walls (wall areas between studs) or solid
walls (concrete or masonry)
1. Drill holes at marked locations using 5/16" drill bit. For solid walls (concrete or
masonry), drill at least 1" deep.
2. Fold wall anchor as shown in Figure 9.
Figure 9 - Folding Anchor
3. Insert wall anchor (wings first) into hole. Tap anchor flush to wall.
12
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
4. For thin walls (1/2" or less), insert red key into wall anchor. Push red key to
“pop” open anchor wings. IMPORTANT: Do not hammer key!
INSTALLING
TO WALL
Continued
For thick walls (over 1/2" thick) or solid walls, do not pop open wings.
Figure 10 - Popping Open Anchor Wings For Thin Walls
5. Place mounting bracket onto wall. Line up last hole on each end of bracket with
wall anchors.
6. Insert mounting screws through bracket and into wall anchors.
7. Tighten screws until mounting bracket is firmly fastened to wall.
Placing Heater On Mounting Bracket
1. Locate two horizontal slots on back panel of heater.
2. Place heater onto mounting bracket. Slide horizontal slots onto stand-out tabs on
mounting bracket.
Horizontal Slots
Stand-Out Tab
Mounting Bracket
(attached to wall)
Figure 11 - Mounting Heater Onto Mounting Bracket
Installing Bottom Mounting Screws
1. Locate two bottom mounting holes. These holes are near bottom on back panel
of heater (see Figure 12).
2. Mark screw locations on wall.
3. Remove heater from mounting bracket.
4. If installing bottom mounting screws into hollow or solid wall, install wall
anchors. Follow steps 1 through 4 under Attaching To Wall Anchor Method,
page 12.
If installing bottom mounting screw into wall stud, drill holes at marked loca-
tions using 9/64" drill bit.
5. Replace heater onto mounting bracket.
6. Place spacers between bottom mounting holes and wall anchor or drilled hole.
7. Hold spacer in place with one hand. With other hand, insert mounting screw
through bottom mounting hole and spacer. Place tip of screw in opening of wall
anchor or drilled hole.
8. Tighten both screws until heater is firmly secured to wall. Do not over tighten.
Note: Do not replace front panel at this time. Replace front panel after making
gas connections and checking for leaks (see pages 14-16).
Figure 12 - Installing Bottom Mounting Screws
13
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
CONNECTING
TO GAS
NOTICE
A qualified service person must connect heater to gas supply.
Follow all local codes.
SUPPLY
CAUTION
WARNING ICON
G
001
Never connect heater directly to the propane/LP supply. This heater
requires an external regulator (not supplied). Install the external
regulator between the heater and propane/LP supply.
The installer must supply an external regulator. The external regulator will reduce
incoming gas pressure. You must reduce incoming gas pressure to between 11 and
14 inches of water. If you do not reduce incoming gas pressure, heater regulator
damage could occur. Install external regulator with the vent pointing down as
shown in Figure 13. Pointing the vent down protects it from freezing rain or sleet.
Propane/LP
Supply Tank
External
Regulator
Vent Pointing
Down
Figure 13 - External Regulator With Vent Pointing Down
CAUTION
WARNING ICON
G
001
Use only new, black iron or steel pipe. Internally-tinned copper
tubing may be used in certain areas. Check your local codes. Use
pipe of large enough diameter to allow proper gas volume to heater.
If pipe is too small, undue loss of pressure will occur.
Typical Pipe Diameters
VP1600D or VP1600ITA 3/8" or greater
VP2600D or VP2200ITA 1/2" or greater
Installation must include a manual shutoff valve, union, and plugged 1/8" NPT tap.
Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream
from heater (see Figure 14, page 15).
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe could result in clogged heater valves.
CAUTION
WARNING ICON
G
001
Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
Install sediment trap in supply line as shown in Figure 14. Locate sediment trap
where it is within reach for cleaning. Locate sediment trap where trapped matter is
not likely to freeze. A sediment trap traps moisture and contaminants. This keeps
them from going into heater controls. If sediment trap is not installed or is installed
wrong, heater may not run properly.
14
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
IMPORTANT: Hold pressure regulator with wrench when connecting it to gas piping
and/or fittings.
CONNECTING
TO GAS
SUPPLY
Continued
Pressure Regulator
Regulator Bracket
1/2" NPT
Heater
Pipe Nipple
Cabinet
Ground Joint
Union
Tee Joint
Manual Shutoff Valve *
Test
Gauge
Connection *
Reducer
Bushing to
1/8" NPT
From
External Regulator
(11" W.C. to 14" W.C. Pressure)
1/8" NPT
Plug Tap
Tee Joint
Sediment
Trap
3" Minimum
Pipe
Nipple
Cap
Figure 14 - Gas Connection
* An AGA design certified manual shutoff valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Purchase the optional AGA design certified
manual shutoff valve from your dealer. See Accessories, page 31.
CHECKING
GAS
CONNECTIONS
WARNING ICON
G
001
WARNING
Test all gas piping and connections for leaks after installing or
servicing. Correct all leaks at once.
WARNING ICON
G
001
WARNING
Never use an open flame to check for a leak. Apply a mixture of
liquid soap and water to all joints. Bubbles forming show a leak.
Correct all leaks at once.
WARNING ICON
G
001
CAUTION
Make sure external regulator has been installed between propane/
LP supply and heater. See guidelines under Connecting to Gas
Supply, page 14.
PRESSURE TESTING GAS SUPPLY PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
1. Disconnect heater and its individual manual shutoff valve from gas supply
piping system. Pressures in excess of 1/2 PSIG will damage heater regulator.
2. Cap off open end of gas pipe where manual shutoff valve was connected.
Continued
15
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Pressurize supply piping system by either using compressed air or
opening propane/LP supply tank valve.
CONNECTING
TO GAS 4. Check all joints of gas supply piping system. Apply mixture of liquid soap and
water to gas joints. Bubbles forming show a leak.
5. Correct all leaks at once.
SUPPLY
Continued
Test Pressures Equal To or Less Than 1/2 PSIG
1. Close manual shutoff valve (see Figure 15).
2. Pressurize supply piping system by either using compressed air or opening
propane/LP supply tank valve.
3. Check all joints from propane/LP supply tank to manual shutoff valve (see
Figure 16). Apply mixture of liquid soap and water to gas joints. Bubbles
forming show a leak.
4. Correct all leaks at once.
PRESSURE TESTING HEATER GAS CONNECTIONS
1. Open manual shutoff valve (see Figure 15).
2. Open propane/LP supply tank valve.
3. Make sure control knob of heater is in the OFF position.
4. Check all joints from manual shutoff valve to control valve (see Figure 16). Apply
mixture of liquid soap and water to gas joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Light heater (see Operating Heater, pages 17 through 24). Check the rest of the
internal joints for leaks.
7. Turn off heater (see To Turn Off Gas to Appliance, page 20 [models
VP1600ITA and VP2200ITA] or page 24 [models VP1600D and VP2600D]).
8. Replace front panel.
Open
Manual
Shutoff
Valve
Closed
Figure 15 - Manual Shutoff Valve
Control Valve Location
Propane/LP
Supply Tank
Manual
Shutoff
Valve
Figure 16 - Checking Gas Joints
16
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATING
FOR YOUR SAFETY READ BEFORE LIGHTING
HEATER
Models VP1600ITA
and VP2200ITA
WARNING
If you do not follow these instructions exactly, a fire or
explosion may result causing property damage, personal
injury or loss of life.
WARNING ICON
G
001
A. This appliance has a pilot which must be lighted by hand. When lighting
the pilot, follow these instructions exactly.
B. BEFORE LIGHTING smell all around the appliance area for gas. Be sure
to smell next to the floor because some gas is heavier than air and will
settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow
the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob. Never use
tools. If the knob will not push in or turn by hand, don’t try to repair it,
call a qualified service technician or gas supplier. Force or attempted
repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Immediately
call a qualified service technician to inspect the appliance and to replace
any part of the control system and any gas control which has been under
water.
Continued
17
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
LIGHTING INSTRUCTIONS
OPERATING
HEATER
Models VP1600ITA
1. STOP! Read the safety information at the top of page 17.
2. Make sure manual shutoff valve is fully open.
and VP2200ITA
3. Turn thermostat control knob on left side of heater clockwise
OFF position.
to the
Clockwise
Continued
Plaque
Control Knob
Thermostat
Ignitor Button
Control Knob
1
2
LO
P I L O T
O F F
H I
3
IGNITOR
4
Figure 17 - Thermostat Control Knob In The OFF Position
4. Wait five minutes to clear out any gas. Then smell for gas, including near
the floor. If you smell gas, STOP! Follow “B” in the safety information at
the top of page 17. If you don’t smell gas, go to the next step.
5. Turn thermostat control knob on left side of heater counterclockwise
to the PILOT position. Press in thermostat control knob for 5
C-clockwise
seconds.
Note: You may be running this heater for the first time after hooking up
to gas supply. If so, you may need to press in thermostat control knob for
30 seconds. This will allow air to bleed from the gas system.
• If thermostat control knob does not pop up when released, contact a
qualified service person or gas supplier for repairs.
6. Keep thermostat control knob pressed in while pushing down and releasing
the ignitor button. This will light pilot. If necessary, continue to press
ignitor button until pilot lights.
If pilot does not light
• turn thermostat control knob clockwise
• repeat steps 5 and 6
to the OFF position
Clockwise
If pilot does not stay lit after several tries
• refer to Troubleshooting, pages 26 through 29
• contact a qualified service person or gas supplier
Until repairs are made, light pilot with match. To light pilot with match, see
Manual Lighting Procedure, page 20.
7. Keep thermostat control knob pressed in for 30 seconds after lighting pilot.
After 30 seconds, release control knob.
Note: If pilot goes out, repeat steps 3 through 7. This heater has a safety
interlock system. Wait one minute before lighting pilot again.
8. Turn thermostat control knob counterclockwise
to the desired
C-clockwise
heating level. The plaque directly above the pilot should light.
18
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
Ignitor Electrode
Pilot Burner
Thermocouple
OPERATING
HEATER
Models VP1600ITA
and VP2200ITA
Continued
Figure 18 - Pilot
TO SELECT HEATING LEVEL
WARNING
WARNING ICON
G
001
When running heater, set control knob at the 1, 2, 3, or 4
locked positions. Never set control knob between locked
positions. Poor combustion and higher levels of carbon
monoxide may result.
CAUTION
WARNING ICON
G
001
Do not try to adjust heating levels by using the manual shut-
off valve.
1. Slightly press in plaque control knob on right side of heater and turn
counterclockwise
to the desired position.
C-clockwise
IMPORTANT: Release downward pressure while turning control knob.
Control knob will lock at the desired position.
2. Turn thermostat control knob on left side of heater to any setting between
LO and HI. Note: When burners cycle on, or from LO to HI, a “click” will
be heard. When the burners light, a “whoosh” noise will be heard.
Plaque
Control Knob VP1600ITA
VP2200ITA
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
Figure 19 - Burner Patterns
Continued
19
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATING
TO TURN OFF GAS TO APPLIANCE
HEATER
Models VP1600ITA
Shutting Off Heater
1. Turn thermostat control knob clockwise
to the OFF position.
Clockwise
and VP2200ITA
2. Turn off all electric power to the appliance if service is to be performed.
Continued
Shutting Off Burner Only (pilot stays lit)
1. Turn thermostat control knob clockwise
to the PILOT position.
Clockwise
THERMOSTAT OPERATION
(Models VP1600ITA and VP2200ITA Only)
The thermostat measures the temperature of air near the heater cabinet. This
may not always agree with room temperature (depending on housing con-
struction, installation location, room size, open air temperatures, etc.). Fre-
quent use of your heater will let you determine your own comfort levels.
MANUAL LIGHTING PROCEDURE
1. Follow steps 1 through 5 under Lighting Instructions, page 18.
2. With thermostat control knob pressed in, strike match. Hold match to pilot
until pilot lights.
3. Keep thermostat control knob pressed in for 30 seconds after lighting pilot.
After 30 seconds, release control knob.
20
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATING
FOR YOUR SAFETY READ BEFORE LIGHTING
HEATER
Models VP1600D
and VP2600D
WARNING
If you do not follow these instructions exactly, a fire or
explosion may result causing property damage, personal
injury or loss of life.
WARNING ICON
G
001
A. This appliance has a pilot which must be lighted by hand. When lighting
the pilot, follow these instructions exactly.
B. BEFORE LIGHTING smell all around the appliance area for gas. Be sure
to smell next to the floor because some gas is heavier than air and will
settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your build-
ing.
• Immediately call your gas supplier from a neighbor’s phone. Follow
the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob. Never use
tools. If the knob will not push in or turn by hand, don’t try to repair it,
call a qualified service technician or gas supplier. Force or attempted
repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Immediately
call a qualified service technician to inspect the appliance and to replace
any part of the control system and any gas control which has been under
water.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Make sure manual shutoff valve is fully open.
3. Turn control knob clockwise
to the OFF position.
Clockwise
Control Knob
OFF
PILOT
IGN
LOW
IGNITOR
HIGH
MED
Figure 20 - Control Knob In The OFF Position
Continued
21
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Wait five minutes to clear out any gas. Then smell for gas, including near
the floor. If you smell gas, STOP! Follow “B” in the safety information at
the top of page 21. If you don’t smell gas, go to the next step.
OPERATING
HEATER
Models VP1600D
and VP2600D
Continued
5. Press in control knob.
Note: You may be running this heater for the first time after hooking up
to gas supply. If so, you may need to press in control knob for 30 seconds.
This will allow air to bleed from the gas system.
• If control knob does not pop up when released, contact a qualified
service person or gas supplier for repairs.
6. With control knob pressed in, push down and release ignitor button. This
will light pilot. The pilot is attached to the front of burner. If needed, keep
pressing ignitor button until pilot lights.
If pilot does not light
• turn control knob clockwise
• repeat steps 5 and 6
to the OFF position
Clockwise
If pilot does not stay lit after several tries
• refer to Troubleshooting, pages 26 through 29
• contact a qualified service person or gas supplier for repairs
Until repairs are made, light pilot with match. To light pilot with match, see
Manual Lighting Procedure, page 24 .
Ignitor Electrode
Pilot Burner
Thermocouple
Figure 21 - Pilot
7. Keep control knob pressed in for 30 seconds after lighting pilot. After 30
seconds, release control knob.
Note: If pilot goes out, repeat steps 3 through 7.
22
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
TO SELECT HEATING LEVEL
OPERATING
HEATER
Models VP1600D
and VP2600D
Continued
WARNING ICON
G
001
WARNING
When running heater, set control knob at LOW, MEDIUM, or
HIGH locked positions. Never set control knob between
locked positions. Poor combustion and higher levels of
carbon monoxide may result.
WARNING ICON
G
001
CAUTION
Do not try to adjust heating levels by using the manual shut-
off valve.
1. Slightly press in control knob and turn counterclockwise
LOW, MEDIUM, or HIGH positions.
to the
C-clockwise
IMPORTANT: Release downward pressure while turning control knob.
Control knob will lock at the desired position.
Control
Knob
VP1600D
VP2600D
OFF
PILOT
IGN
LOW
MED
LOW
OFF
PILOT
IGN
MED
OFF
PILOT
IGN
HIGH
OFF
HIGH
OFF
Figure 22 - Burner Patterns
23
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATING
HEATER
TO TURN OFF GAS TO APPLIANCE
Shutting Off Heater
Models VP1600D 1. Turn control knob clockwise
to the OFF position.
Clockwise
and VP2600D
2. Turn off all electric power to the appliance if service is to be performed.
Continued
Shutting Off Burner Only (pilot stays lit)
1. Turn control knob clockwise
to the PILOT position.
Clockwise
MANUAL LIGHTING PROCEDURE
1. Follow steps 1 through 5 under Lighting Instructions, pages 21 and 22.
2. With control knob pressed in, strike match. Hold match to pilot until pilot
lights.
3. Keep control knob pressed in for 30 seconds after lighting pilot. After 30
seconds, release control knob.
Check pilot flame pattern and burner flame pattern often.
INSPECTING
BURNER
PILOT FLAME PATTERN
Figure 23 shows a correct pilot flame pattern. Figure 24 shows an incorrect pilot
flame pattern. The incorrect pilot flame is not touching the thermocouple. This will
cause the thermocouple to cool. When the thermocouple cools, the heater will shut
down.
Pilot Burner
Thermocouple
GOOD PILOT/LP
GRH/OV 007
Figure 23 - Correct Pilot Flame Pattern
Pilot Burner
Thermocouple
BAD PILOT/LP
GRH/OV 008
Figure 24 - Incorrect Pilot Flame Pattern
If pilot flame pattern is incorrect, as shown in Figure 24
• turn heater off (see To TurnOff Gas to Appliance, page 20 [models
VP1600ITA and VP2200ITA] or page 24 [models VP1600D and VP2600D])
• see Troubleshooting, pages 26 through 29
24
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
BURNER FLAME PATTERN
Figure 25 shows a correct burner flame pattern. Figure 26 shows an incorrect
INSPECTING
BURNER
burner flame pattern.
Continued
Figure 25 - Correct Burner Flame Pattern
Figure 26 - Incorrect Burner Flame Pattern
If burner flame pattern is incorrect, as shown in Figure 26
• turn heater off (see To Turn Off Gas to Appliance, page 20 [models
VP1600ITA and VP2200ITA] or page 24 [models VP1600D and VP2600D])
• see Troubleshooting, pages 26 through 29
25
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
CLEANING
AND
WARNING
WARNING ICON
G
001
Turn off heater and let cool before cleaning.
MAINTENANCE
CAUTION
WARNING ICON
G
001
You must keep control areas, burner, and circulating air
passageways of heater clean. Inspect these areas of heater before
each use. Have heater inspected yearly by a qualified service
person. Heater may need more frequent cleaning due to excessive
lint from carpeting, bedding material, etc.
ODS/PILOT AND BURNER ORIFICE
• Use a vacuum cleaner, pressurized air, or small, soft bristled brush to clean.
CABINET
Air Passageways
• Use a vacuum cleaner or pressurized air to clean.
Exterior
• Use a soft cloth dampened with a mild soap and water mixture. Wipe the
cabinet to remove dust.
TROUBLE-
SHOOTING
Note: All troubleshooting
items are listed in order of
operation.
WARNING
WARNING ICON
G
001
Turn off and unplug heater and let cool before servicing. Only a
qualified service person should service and repair heater.
CAUTION
WARNING ICON
G
001
Never use a wire, needle, or similar object to clean ODS/pilot. This
can damage ODS/pilot unit.
OBSERVED
PROBLEM
POSSIBLE
CAUSE
REMEDY
When ignitor button is
pressed in, there is no
spark at ODS/pilot.
1. Ignitor electrode posi-
tioned wrong.
1. Replace ignitor.
2. Ignitor electrode broken.
3. Ignitor electrode not
connected to ignitor cable.
4. Ignitor cable pinched or
wet.
2. Replace ignitor.
3. Reconnect ignitor cable.
4. Free ignitor cable if pinched
by any metal or tubing.
Keep ignitor cable dry.
5. Broken ignitor cable.
6. Bad piezo ignitor.
5. Replace ignitor cable.
6. Replace control valve
(piezo is part of control
valve).
7. Piezo ignitor nut is loose.
7. Tighten nut holding piezo
ignitor. Nut is located in-
side heater cabinet at top.
26
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
OBSERVED
PROBLEM
POSSIBLE
CAUSE
TROUBLE-
REMEDY
SHOOTING
When ignitor button is 1. Gas supply turned off or
1. Turn on gas supply or
open manual shutoff
valve.
2. Press in control knob
while pressing ignitor
button (non-thermostat
models only).
pressed in, there is a
spark at ODS/Pilot but
no ignition.
manual shutoff valve
closed.
Continued
2. Control knob not pressed
in while pressing ignitor
button (non-thermostat
models only).
Thermostat control knob
not pressed in (thermostat
models only).
Press in thermostat
control knob while
turning to PILOT/IGN
position (thermostat
models only)
3. Air in gas lines when
installed.
3. Continue holding down
control knob. Repeat
igniting operation until
air is removed.
4. Depleted gas supply
5. ODS/pilot is clogged.
4. Contact local propane/LP
gas company.
5. Clean ODS/pilot (see
Cleaning and Mainte-
nance, page 26) or
replace ODS/pilot
assembly.
6. Gas regulator setting is
not correct.
6. Replace gas regulator.
7. Thermostat control knob
is not in pilot position
(thermostat models only).
7. Turn thermostat control
knob to pilot position.
ODS/pilot lights but
flame goes out when
control knob is
released.
1. Control knob not fully
pressed in.
2. Control knob not pressed
in long enough.
1. Press in control knob
fully.
2. After ODS/pilot lights,
keep control knob pressed
in 30 seconds.
3. Manual shutoff valve not
fully open.
3. Fully open manual shut-
off valve.
4. Thermocouple connection
loose at control valve.
5. Pilot flame not touching
thermocouple, which
4. Hand tighten until snug,
then tighten 1/4 turn more.
5. A) Contact local pro-
pane/LP gas company.
allows thermocouple to
cool, causing pilot flame
to go out. This problem
could be caused by one or
both of the following:
A) Low gas pressure
B) Clean ODS/pilot (see
Cleaning and Mainte-
nance, page 26) or
replace ODS/pilot
assembly.
B) Dirty or partially
clogged ODS/pilot
6. Thermocouple damaged.
7. Control valve damaged.
8. Safety interlock system
has been triggered (ther-
mostat models only).
6. Replace thermocouple.
7. Replace control valve.
8. Wait one minute for safety
interlock system to reset.
Repeat ignition operation.
Continued
27
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
OBSERVED
PROBLEM
POSSIBLE
CAUSE
TROUBLE-
REMEDY
SHOOTING
Burner(s) does not
light after ODS/pilot is
lit.
1. Burner orifice(s) is
clogged.
1. Clean burner orifice(s)
(see Cleaning and
Maintenance, page 26) or
replace burner orifice(s).
2. Replace burner orifice(s).
Continued
2. Burner orifice(s)
diameter is too small.
3. Inlet gas pressure is too
low.
3. Contact local propane/LP
gas company.
Delayed ignition of
burner(s)
1. Manifold pressure is too
low.
1. Contact local propane/LP
gas company.
2. Burner orifice(s) is
clogged.
2. Clean burner orifice(s)
(see Cleaning and
Maintenance, page 26 or
replace burner orifice(s).
Burner backfiring
during combustion.
1. Burner orifice(s) is
clogged or damaged.
1. Clean burner orifice(s)
(see Cleaning and
Maintenance, page 26) or
replace burner orifice(s).
2. Replace burner.
2. Burner damaged.
3. Gas regulator defective.
3. Replace gas regulator.
Burner plaque(s) does
not glow.
1. Plaque damaged.
2. Inlet gas pressure is too
low.
1. Replace burner.
2. Contact local propane/LP
gas company.
3. Control knob set be-
tween locked positions.
3. Turn control knob until it
locks at desired setting.
Slight smoke or odor
during initial opera-
tion
1. Residues from manu-
facturing processes
1. Problem will stop after a
few hours of operation.
Heater produces a
clicking/ticking noise
just after burner is lit
or shut off.
1. Metal expanding while
heating or contracting
while cooling.
1. This is common with
most heaters. If noise is
excessive, contact
qualified service person.
28
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLE-
WARNING
WARNING ICON
G
001
SHOOTING
If you smell gas
• Shut off gas supply.
Continued
• Do not try to light any appliance.
• Donottouchanyelectricalswitch;donotuse
any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• Ifyoucannotreachyourgassupplier,callthe
fire department.
IMPORTANT: Operating heater where impurities in air exist may create odors.
Cleaning supplies, paint, paint remover, cigarette smoke, cements and glues, new
carpet or textiles, etc., create fumes. These fumes may mix with combustion air and
create odors.
OBSERVED
PROBLEM
POSSIBLE
CAUSE
REMEDY
Heater produces
unwanted odors.
1. Heater burning vapors
from paint, hair spray,
glues, etc. See IMPOR-
TANT statement above
2. Low fuel supply
3. Gas leak. See Warn-
ing statement at top
of page.
1. Ventilate room. Stop
using odor causing
products while heater is
running.
2. Refill supply tank.
3. Locate and correct all
leaks (see Checking Gas
Connections, page 15).
Heater shuts off in use
(ODS operates).
1. Not enough fresh air is
available.
2. Low line pressure
1. Open window and/or
door for ventilation.
2. Contact local propane/
LP gas company.
3. ODS/pilot is partially
clogged.
3. Clean ODS/pilot (see
Cleaning and Mainte-
nance, page 26).
Gas odor even when
control knob is in OFF
position
1. Gas leak. See Warn-
ing statement at top
of page.
1. Locate and correct all
leaks (see Checking Gas
Connections, page 15).
2. Replace control valve.
2. Control valve defective.
Gas odor during
combustion
1. Foreign matter between
control valve and
burner.
1. Take apart gas tubing
and remove foreign
matter.
2. Gas leak. See Warn-
ing statement at top
of page.
2. Locate and correct all
leaks (see Checking Gas
Connections, page 15).
Moisture/condensation
noticed on windows
1. Not enough combus-
tion/ventilation air.
1. Refer to Fresh Air for
Combustion and Venti-
lation requirements
(page 5)
You may have further questions about installation, operation, or troubleshooting.
If so, contact DESA International’s Technical Service Department at 1-800-323-
5190.
TECHNICAL
SERVICE
29
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
VP1600ITA
6,000-16,000
Propane/LP Only
Piezo
VP2200ITA
6,500-22,000
Propane/LP Only
Piezo
SPECIFICATIONS
Btu (Variable)
Type Gas
Ignition
Pressure Regulator Setting
Inlet Gas Pressure (in. of water)
Maximum
8" W.C.
8" W.C.
14"
11"
14"
11"
Minimum
Dimensions, Inches (H x W x D)
Heater
Carton
23.5 x 18.5 x 8
25.8 x 21.3 x 10.1
23.5 x 25.9 x 8
25.8 x 28.7 x 10.1
Weight (pounds)
Heater
24
29
32
38
Shipping
VP1600D
VP2600D
Btu (Variable)
Type Gas
Ignition
6,000/11,000/16,000
Propane/LP Only
Piezo
6,000/16,000/26,000
Propane/LP Only
Piezo
Pressure Regulator Setting
Inlet Gas Pressure (in. of water)
Maximum
8" W.C.
8" W.C.
14"
11"
14"
11"
Minimum
Dimensions, Inches (H x W x D)
Heater
Carton
23.5 x 18.5 x 8
25.8 x 21.3 x 10.1
23.5 x 25.9 x 8
25.8 x 28.7 x 10.1
Weight (pounds)
Heater
22
27
30
36
Shipping
Note: Dimensions listed are outer most points on the heater (includes control
knobs and grill).
You can purchase a service manual from the address listed on the back page of this
manual. Send a check for $5.00 payable to DESA International.
SERVICE
PUBLICATIONS
When gas pressure is too low
SERVICE
HINTS
• pilot will not stay lit
• burner(s) will have delayed ignition
• heater will not produce specified heat
• propane/LP gas supply may be low
When gas quality is bad
• pilot will not stay lit
• burner(s) will produce flames and soot
• heater will backfire when lit
You may feel your gas pressure is too low or gas quality is bad. If so, contact your
local propane/LP gas supplier.
30
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
Note: Use only original replacement parts. This will protect your warranty coverage
for parts replaced under warranty.
REPLACEMENT
PARTS
Parts Under Warranty
Contact authorized dealer from whom you purchased this product. If they are
unable to supply original replacement part(s), call DESA International’s Technical
Service Department at 1-800-323-5190 for information.
When contacting your dealer or DESA International, have ready:
• your name
• your address
• model number of your heater
• how heater was malfunctioning
• type of gas used (propane/LP or natural gas)
• purchase date
Usually, we will ask you to return the defective part to the factory.
Parts Not Under Warranty
Contact authorized dealers of this product. If they can’t supply original replacement
part(s), call DESA International’s Parts Department at 1-800-972-7879 for referral
information. When calling DESA International, have ready:
• model number of your heater
• the replacement part number
Purchase these heater accessories from your local dealer. If they can not supply
these accessories, call DESA International’s Parts Department at 1-800-972-7879
or write to the address listed on the back page of this manual for referral information.
ACCESSORIES
FAN KITS - GA3100A and GA3200TA
For all models. Provides better heat distribution.
Makes heater more efficient. Complete installation
and operating instructions included.
Manually controlled - GA3100A. Includes ON/OFF
switch.
Thermostatically controlled - GA3200TA. Includes
three settings: ON/OFF/AUTO.
FLOOR MOUNTING STAND
Models VP1600D & VP1600ITA - GA4000B
Models VP2600D & VP2200ITA - GA4010B
For locating heater on the floor, away from a
wall. Complete installation instructions provided
with floor mounting stand.
MANUAL SHUTOFF
VALVE - GA5010
For all models. Manual
shutoff valve with 1/8"
NPT tap.
31
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
14
ILLUSTRATED
PARTS
BREAKDOWN
Model VP1600ITA
12
11
16
20
22
19
10
17
15
9
24
4
18
21
8
6
HEATER EXPLODED VIEW
23
7
5
13
3
6
2
23-1
A
1
B
C
23-12
23-10
23-2
23-11
23-16
23-17
23-4
23-3
23-13
23-15
23-7
23-6
23-5
23-9
23-14
BURNER ASSEMBLY
23-8
ODS/PILOT
32
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
This list contains replaceable parts used in your heater. When ordering parts, follow
the instructions listed under Replacement Parts on page 31 of this manual.
PARTS LIST
Model VP1600ITA
KEY
PART
NO.
NUMBER
DESCRIPTION
QTY.
1
2
3
4
5
6
7
8
098304-01
098742-13
098238-06
101108-01
098198-03
M11084-26
098462-01
098457-01
098867-06
M11084-38
098455-06
098324-01
098325-01
102445-01
100537-01
098522-05
098265-02
098264-02
098271-03
100614-01
100610-01
099211-01
See Detail
099218-01
098508-01
099056-01
099048-01
099049-01
099057-01
099050-01
100605-01
099387-06
Screw, #10 x 3/8"
Front Panel
Grill Guard
Clip-Grill Guard
Apron
Screw, #10 x 3/8"
Control Rod Assembly
Reflector Assembly
Regulator
Screw, #8 x 3/8"
Cabinet Assembly
Control Knob
Roll Pin
Piezo Ignitor
2
1
1
2
1
9
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
3
1
1
1
1
1
1
1
1
2
3
1
2
1
1
1
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
Regulator Bracket
Thermostat Gas Valve
Male Elbow
Male Connector
Ignitor Cable
SIT Tube
Inlet Tube
Hex-Head Screw
Burner Assembly
Burner
Valve Retainer Nut
Injector
Tubing-Valve to Plaque A
Tubing-Valve to Plaque B
Pressure Tap Fitting
Tubing-Valve to Plaque C
Control Valve
Pilot Tubing-Thermostat Control Valve to Pilot
Control Valve Tube
ODS/Pilot
23-1
23-2
23-3
23-4
23-5
23-6
23-7
23-8
23-9
23-10 100616-01
23-11 099440-06
23-12 100615-01
23-13 M11084-37
23-14 098276-01
23-15 M11084-26
23-16 098514-01
23-17 098594-01
Male Connector
Screw, #8 x 1/4"
Plug, 1/8
Screw, #10 x 3/8"
Thermocouple
Ignitor Electrode
Mounting Bracket
24
099066-01
PARTS AVAILABLE - NOT SHOWN
100619-01
100619-02
100642-01
Thermostat Control Position Label
Control Position Label
Hardware Assembly
1
1
1
33
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
14
ILLUSTRATED
PARTS
BREAKDOWN
Model VP2200ITA
12
11
16
20
22
19
10
17
15
9
24
4
18
21
8
6
HEATER EXPLODED VIEW
23
7
5
13
3
6
2
23-1
1
A
B
C
23-17
23-18
D
23-15
23-11
23-9
23-2
23-4
23-3
23-13
23-14
23-5
23-12
23-6
23-10
ODS/PILOT
23-16
23-8
BURNER ASSEMBLY
23-7
34
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
This list contains replaceable parts used in your heater. When ordering parts, follow
the instructions listed under Replacement Parts on page 31 of this manual.
PARTS LIST
Model VP2200ITA
KEY
NO.
PART
NUMBER
DESCRIPTION
QTY.
1
2
3
4
5
6
7
8
098304-01
098742-14
098238-07
101108-01
098198-04
Screw, #10 x 3/8"
Front Panel
Grill Guard
Clip-Grill Guard
Apron
2
1
1
2
1
9
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
5
1
1
1
1
1
1
1
1
2
4
1
2
1
1
1
1
M11084-26 Screw, #10 x 3/8"
098462-01
098457-05
098867-06
Control Rod Assembly
Reflector Assembly
Regulator
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
23-1
23-2
23-3
23-4
23-5
23-6
23-7
23-8
23-9
M11084-38 Screw, #8 x 3/8"
098698-04
098324-01
098325-01
102445-01
100537-01
098522-05
098265-02
098264-02
098271-03
100614-01
100610-01
099211-01
See Detail
099218-03
098508-01
099056-01
100620-01
100607-01
099057-01
100608-01
100605-02
100616-02
Cabinet Assembly
Control Knob
Roll Pin
Piezo Ignitor
Regulator Bracket
Thermostat Gas Valve
Male Elbow
Male Connector
Ignitor Cable
SIT Tubing
Inlet Tubing
Hex-Head Screw
Burner Assembly
Burner
Valve Retainer Nut
Injector
Tubing-Valve to Plaque A
Tubing-Valve to Plaque B
Pressure Tap Fitting
Tubing-Valve to Plaque C
Control Valve
Control Valve Tube
Pilot Tubing-Thermostat Control Valve to Pilot
ODS/Pilot
23-10 099387-06
23-11 099440-06
23-12 M11084-26 Screw, #10 x 3/8"
23-13 M11084-37 Screw, #8 x 1/4"
23-14 100606-01
23-15 100615-01
23-16 098276-01
23-17 098514-01
23-18 098594-01
Tubing - Valve to Plaque D
Male Connector
Plug, 1/8
Thermocouple
Ignitor Electrode
Mounting Bracket
24
099066-01
PARTS AVAILABLE - NOT SHOWN
100619-01
100619-03
100642-01
Thermostat Control Position Label
Control Position Label
Hardware Assembly
1
1
1
35
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
11
ILLUSTRATED
PARTS
17
12
BREAKDOWN
10
14
15
9
Model VP1600D
4
6
18
13
8
HEATER EXPLODED VIEW
7
5
16
3
6
2
13-1
1
A
B
13-14
13-15
C
13-2
13-10
13-11
13-13
13-4
13-3
13-12
13-6
13-7
13-5
13-16
ODS/PILOT
13-8
13-9
BURNER ASSEMBLY
36
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
This list contains replaceable parts used in your heater. When ordering parts, follow
the instructions listed under Replacement Parts on page 31 of this manual.
PARTS LIST
Model VP1600D
KEY
PART
NO.
1
2
3
4
5
6
7
8
NUMBER
098304-01 Screw, #10 x 3/8"
098742-13 Front Panel
098238-06 Grill Guard
101108-01 Clip-Grill Guard
098198-03 Apron
M11084-26 Screw, #10 x 3/8"
098462-01 Control Rod Assembly
098457-01 Reflector Assembly
098867-06 Regulator
M11084-38 Screw, #8 x 3/8"
098455-09 Cabinet Assembly
098324-01 Control Knob
See Detail
099218-01 Burner
098508-01 Valve Retainer Nut
099056-01 Injector
099048-01 Tubing-Valve to Plaque A
099049-01 Tubing-Valve to Plaque B
099050-01 Tubing-Valve to Plaque C
099057-01 Pressure Tap Fitting
100747-01 Control Valve
099043-01 Pilot Tubing-Valve to Pilot
099051-01 Inlet Tubing
DESCRIPTION
QTY.
2
1
1
2
1
9
1
1
1
2
1
1
1
1
1
3
1
1
1
1
1
1
1
1
3
2
1
1
1
1
1
1
1
1
9
10
11
12
13
13-1
13-2
13-3
13-4
13-5
13-6
13-7
13-8
13-9
13-10
13-11
13-12
13-13
13-14
13-15
13-16
Burner Assembly
099059-02 ODS/Pilot
M11084-37 Screw, #8 x 1/4"
M11084-26 Screw, #10 x 3/8"
098593-01 Thermocouple
098594-01 Ignitor Electrode
098276-01 Plug, 1/8"
099066-01 Mounting Bracket
100537-01 Regulator Bracket
098325-01 Roll Pin
14
15
16
17
18
102445-01 Piezo Ignitor
098271-03 Ignitor Cable
PARTS AVAILABLE - NOT SHOWN
100822-01 Control Position Label
100642-01 Hardware Assembly
1
1
37
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
11
ILLUSTRATED
PARTS
17
12
BREAKDOWN
10
15
14
Model VP2600D
4
9
6
8
18
13
HEATER EXPLODED VIEW
7
5
16
3
6
2
1
A
B
13-1
13-14
13-15
C
D
13-9
E
13-11
13-2
13-4
13-5
13-3
13-12
13-13
13-7
13-6
13-16
ODS/PILOT
13-8
13-10
BURNER ASSEMBLY
38
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
This list contains replaceable parts used in your heater. When ordering parts, follow
the instructions listed under Replacement Parts on page 31 of this manual.
PARTS LIST
Model VP2600D
KEY
PART
NO.
NUMBER
DESCRIPTION
QTY.
1
2
3
4
5
6
7
8
098304-01
098742-14
098238-07
101108-01
098198-04
Screw, #10 x 3/8"
Front Panel
Grill Guard
Clip-Grill Guard
Apron
2
1
1
2
1
9
1
1
1
2
1
1
1
1
1
5
1
1
1
1
1
1
1
1
5
2
1
1
1
1
1
1
1
1
M11084-26 Screw, #10 x 3/8"
098462-01
098457-02
098867-06
Control Rod Assembly
Reflector Assembly
Regulator
9
10
11
12
13
13-1
13-2
13-3
13-4
13-5
13-6
13-7
13-8
13-9
13-10
13-11
13-12
13-13
13-14
13-15
13-16
M11084-38 Screw, #8 x 3/8"
098456-03
098324-01
See Detail
099218-02
098508-01
099056-01
099052-01
099053-01
099057-01
099054-01
100747-01
099051-02
099044-01
099059-02
M11084-37 Screw, #8 x 1/4"
M11084-26 Screw, #10 x 3/8"
098593-01 Thermocouple
098594-01 Ignitor Electrode
098276-01 Plug, 1/8"
099066-01 Mounting Bracket
100537-01 Regulator Bracket
098325-01 Roll Pin
Cabinet Assembly
Control Knob
Burner Assembly
Burner
Valve Retainer Nut
Injector
Tubing-Valve to Plaque B & D
Tubing-Valve to Plaque C
Pressure Tap Fitting
Tubing-Valve to Plaque A & E
Control Valve
Inlet Tubing
Pilot Tubing-Valve to Pilot
ODS/Pilot
14
15
16
17
18
102445-01 Piezo Ignitor
098271-03 Ignitor Cable
PARTS AVAILABLE - NOT SHOWN
100822-01 Control Position Label
100642-01 Hardware Assembly
1
1
39
101823
Download from Www.Somanuals.com. All Manuals Search And Download.
WARRANTY INFORMATION
KEEP THIS WARRANTY
Model
Serial No.
Date Purchased
Always specify model and serial numbers when communicating with the factory.
We reserve the right to amend these specifications at any time without notice. The only warranty applicable is our standard
written warranty. We make no other warranty, expressed or implied.
LIMITED WARRANTY
VANGUARD VENT-FREE PROPANE/LP GAS HEATERS
DESA International warrants this product to be free from defects in materials and components for three (3) years from the
date of first purchase, provided that the product has been properly installed, operated and maintained in accordance with all
applicable instructions. To make a claim under this warranty the Bill of Sale or cancelled check must be presented.
This warranty is extended only to the original retail purchaser. This warranty covers the cost of part(s) required to restore this
heater to proper operating condition and an allowance for labor when provided by a DESA Authorized Service Center.
Warranty part(s) MUST be obtained through authorized dealers of this product and/or DESA International who will provide
original factory replacement parts. Failure to use original factory replacement parts voids this warranty. The heater MUST
be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit.
This warranty does not apply to parts that are not in original condition because of normal wear and tear, or parts that fail or
become damaged as a result of misuse, accidents, lack of proper maintenance or defects caused by improper installation.
Travel, diagnostic cost, labor, transportation and any and all such other costs related to repairing a defective heater will be
the responsibility of the owner.
TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE
PRODUCT; THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES AND
LIMITS THE DURATION OF ANY AND ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MER-
CHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO THREE (3) YEARS ON ALL COMPONENTS
FROM THE DATE OF FIRST PURCHASE; AND DESA INTERNATIONAL’S LIABILITY IS HEREBY LIMITED TO
THE PURCHASE PRICE OF THE PRODUCT AND DESA INTERNATIONAL SHALL NOT BE LIABLE FOR ANY
OTHER DAMAGES WHATSOEVER INCLUDING INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states do not allow a limitation on how long an implied warranty lasts or an exclusion or limitation of incidental or
consequential damages, so the above limitation on implied warranties, or exclusion or limitation on damages may not apply
to you.
This warranty gives you specific legal rights, and you may also have other rights that vary from state to state.
For information about this warranty write:
2701 Industrial Drive
P.O. Box 90004
Bowling Green, KY 42102-9004
101823-01
REV. D
3/96