VENT-FREE PROPANE/LP GAS
®
MINI-HEARTH HEATER
OWNER’S OPERATION AND INSTALLATION MANUAL
VMH3000TPS
®
15,000 to 30,000 Btu/Hr
Shown With Optional
Mantel Which Features
with Thermostat
a Built-In Base
WARNING: Improper installation,
adjustment, alteration, service, or
maintenance can cause injury or
property damage. Refer to this
WARNING: If the information in this manual is not fol-
lowed exactly, a fire or explosion may result causing
property damage, personal injury, or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
manualforcorrectinstallationand
operational procedures. For as-
sistance or additional information
consult a qualified installer, ser-
vice agency, or the gas supplier.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
WARNING: This is an unvented
gas-fired heater. It uses air (oxy-
gen) from the room in which it is
installed. Provisions for adequate
combustion and ventilation air
must be provided. Refer to Air for
Combustion and Ventilation sec-
tion on page 5 of this manual.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s in-
structions.
• If you cannot reach your gas supplier, call the fire
department.
— Installation and service must be performed by a
qualified installer, service agency, or the gas supplier.
This appliance may be installed in an aftermarket* manufactured (mobile) home, where not prohibited by state
or local codes.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer. (I.E. Installation of this product is permitted after the
manufactured (mobile) home is sited).
Save this manual for future reference.
Download from Www.Somanuals.com. All Manuals Search And Download.
OWNER’S MANUAL
Note: Do not remove
Lighting and Warning
Plates from heater
PRODUCT
UNPACKING
1. Remove heater from carton.
IDENTIFICATION
2. Remove all protective packaging ap-
plied to heater for shipment.
Control Knob
Ignitor Button
3. Make sure your heater includes two
hardware packets.
Lighting and
Warning Plates
4. Check heater for any shipping damage.
If heater is damaged, promptly inform
dealer where you bought heater.
Heater
Cabinet
Screen
Front
Panel
Log
Figure 1 - Vent-Free Gas Log Propane/LP Gas Space Heater
4. Gently slide log between log retaining
brackets on deflector assembly (see
Figure 4, page 4). The log should fit
firmly against bottom of log retaining
brackets.
Installing Log
ASSEMBLY
ASSEMBLING HEATER
Note: For easier installation, lay heater on
its back.
1. Remove log from inside top of heater.
Discard protective packaging.
Tools Required:
• Phillips screwdriver
• 5/16" hex wrench
• slotted screwdriver
5. Reattach screen using four screws re-
moved in step 3.
2. Attach ignitor cable to piezo ignitor
(see Figure 3).
3. With Phillips screwdriver, remove four
screws holding screen in place. Re-
move screen.
Removing Front Panel Of Heater
1. Remove two screws near bottom cor-
ners of front panel with Phillips screw-
driver.
Piezo Ignitor
2. Pull bottom of front panel forward, then
down (see Figure 2) .
Ignitor
Cable
Figure3-AttachingIgnitorCabletoPiezo
Ignitor
Figure2-RemovingFrontPanelofHeater
Continued
106056
3
Download from Www.Somanuals.com. All Manuals Search And Download.
®
GAS RESIDENTIAL HEATERS
5. Slide other end of adjusting plate/shim
in slot on mitered edge of side brass
trim (see Figure 6).
ASSEMBLY
Continued
Log
Heater Cabinet
6. While firmly holding edges of brass
trim together, tighten both set screws
on the adjusting plate with slotted
screwdriver.
Deflector
7. Repeat steps 1 through 6 for other side.
8. Place the assembled trim on front of
heater cabinet. Attach on top and sides
with four brass screws included in hard-
ware package (see Figure 7).
Front Panel
Log
Retaining
Brackets
Screen
9. Reattach front panel to heater if you are
going to mount the heater to the base.
Do not reattach front panel at this time
if you are going to mount heater to wall.
Truss-
Head
Screw
Adjusting
Nut
Top Brass
Plate
Trim
Burner Shield
Side Brass
Trim
Set
Screws
Screw
Brass Front Trim
Screw
Shim
Slot
Figure 4 - Assembling Heater
Front Panel
Brass Front Trim
Mitered Edge
Slot
WARNING: Always have
burnershieldandscreeninplace
beforeoperatingheater.Thispre-
ventsexcessivetemperatureson
heater surfaces.
Figure 6 - Assembling Brass Trim
Screws
Failure to position the parts in
accordance with these diagrams
or failure to use only parts spe-
cificallyapprovedwiththisheater
mayresultinpropertydamageor
personal injury.
Assembled
Brass Trim
Nut
Truss-Head
Screw
Figure 5 - Attaching Brass Front Trim to
Front Panel
Assembling and Attaching
Brass Trim
1. Remove packaging from three remain-
ing pieces of brass trim.
Attaching Brass Front Trim to
Front Panel
1. Locate brass front trim in brass trim
package.
2. Locate four brass screws, two adjust-
ing plates with set screws, and two
shims in the hardware packet.
2. Slide the head of two truss-head screws
from hardware packet into each end of
brass front trim (see Figure 5).
3. Align shim under adjusting plate as
shown in Figure 6.
Figure 7 - Attaching Brass Trim to Heater
3. Line up screws with holes in front panel
(see Figure 4). Insert screws in holes.
Attach nuts from inside of front panel.
Tighten with wrench.
4. Slide one end of adjusting plate/shim
in slot on mitered edge of top brass trim
(see Figure 6).
106056-01
4
Download from Www.Somanuals.com. All Manuals Search And Download.
OWNER’S MANUAL
PROVIDING ADEQUATE
VENTILATION
Confined and Unconfined Space
AIR FOR
The National Fuel Gas Code (ANS Z223.1,
1992 Section 5.3) defines a confined space
as a space whose volume is less than 50
cubic feet per 1,000 Btu per hour (4.8 m3 per
kw) of the aggregate input rating of all
appliances installed in that space and an
unconfined space as a space whose volume
is not less than 50 cubic feet per 1,000 Btu
per hour (4.8 m3 per kw) of the aggregate
inputratingofallappliancesinstalledinthat
space. Rooms communicating directly with
the space in which the appliances are in-
stalled*, through openings not furnished
with doors, are considered a part of the
unconfined space.
COMBUSTION AND
VENTILATION
The following are excerpts from National
Fuel Gas Code. NFPA 54/ANS Z223.1, Sec-
tion5.3, AirforCombustionandVentilation.
WARNING: This heater shall
notbeinstalledinaconfinedspace
or unusually tight construction
unless provisions are provided
foradequatecombustionandven-
tilation air. Read the following in-
structions to insure proper fresh
air for this and other fuel-burning
appliances in your home.
All spaces in homes fall into one of the three
following ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space
The information on pages 5 through 7 will
help you classify your space and provide
adequate ventilation.
Today’s homes are built more energy effi-
cient than ever. New materials, increased
insulation, and new construction methods
helpreduceheatlossinhomes.Homeowners
weather strip and caulk around windows and
doorstokeepthecoldairoutandthewarmair
in. During heating months, home owners
want their homes as airtight as possible.
Unusually Tight Construction
This heater shall not be installed in a con-
fined space or unusually tight construction
unless provisions are provided for adequate
combustion and ventilation air.
The air that leaks around doors and win-
dows may provide enough fresh air for
combustion and ventilation. However, in
buildings of unusually tight construction,
you must provide additional fresh air.
* Adjoining rooms are communicating only
iftherearedoorlesspassagewaysorventila-
tion grills between them.
Unusually tight construction is de-
fined as construction where:
While it is good to make your home energy
efficient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning
appliances need fresh air for proper com-
bustion and ventilation.
a. walls and ceilings exposed to the
outside atmosphere have a con-
tinuous water vapor retarder with
a rating of one perm (6x10-11 kg
per pa-sec-m2) or less with open-
ings gasketed or sealed and
Exhaustfans, fireplaces, clothesdryers, and
fuel burning appliances draw air from the
house to operate. You must provide ad-
equate fresh air for these appliances. This
will insure proper venting of vented fuel-
burning appliances.
b. weather stripping has been
added on openable windows and
doors and
c. caulking or sealants are applied
to areas such as joints around
window and door frames, be-
tween sole plates and floors, be-
tween wall-ceiling joints, be-
tween wall panels, at penetra-
tions for plumbing, electrical, and
gas lines, and at other openings.
If your home meets all of the three criteria
above, you must provide additional fresh
air. See Ventilation Air From Outdoors,
page 7.
If your home does not meet all of the three
criteriaabove,proceedtoDeterminingFresh-
Air Flow For Heater Location, page 6.
Continued
106056
5
Download from Www.Somanuals.com. All Manuals Search And Download.
®
GAS RESIDENTIAL HEATERS
AIR FOR
COMBUSTION AND
VENTILATION
Continued
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Confined or Unconfined Space
Use this worksheet to determine if you have a confined or unconfined space.
Space:Includestheroominwhichyouwillinstallheaterplusanyadjoiningroomswithdoorlesspassagewaysorventilationgrillsbetween
the rooms.
1. Determine the volume of the space (length x width x height).
Length x Width x Height = ____________________ cu. ft. (volume of space)
Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.
2. Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.
_____________________(volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can support)
Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free heater
Gas water heater*
Gas furnace
___________________Btu/Hr
___________________Btu/Hr
___________________Btu/Hr
___________________Btu/Hr
___________________Btu/Hr
Example:
30,000
30,000
60,000
Gas water heater
Vent-free heater +
Btu/Hr
Btu/Hr
Btu/Hr
Vented gas heater
Gas fireplace logs
Total
=
Other gas appliances* + ___________________Btu/Hr
Total = ___________________Btu/Hr
* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
_________________ Btu/Hr (maximum the space can support)
_________________ Btu/Hr (actual amount of Btu/Hr used)
Example: 51,200 Btu/Hr (maximum the space can support)
60,000 Btu/Hr (actual amount of Btu/Hr used)
The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space cansupport.
You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-
ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7.
B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 7.
C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.
WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space
or if building is of unusually tight construction, provide adequate combustion and ventilation air by one of the
methods described in the National Fuel Gas Code, ANS Z223.1, 1992, Section 5.3 or applicable local codes.
106056-01
6
Download from Www.Somanuals.com. All Manuals Search And Download.
OWNER’S MANUAL
AIR FOR
COMBUSTION AND
12"
VENTILATION
Continued
VENTILATION AIR
Ventilation Grills
Into Adjoining Room,
Option 2
Ventilation
Grills
into Adjoining
Room,
Ventilation Air From Inside
Building
Or
Remove
Door into
Adjoining
Room,
Thisfreshairwouldcomefromanadjoining
unconfined space. When ventilating to an
adjoining unconfined space, you must pro-
vide two permanent openings: one within
12" of the ceiling and one within 12" of the
floor on the wall connecting the two spaces
(see options 1 and 2, Figure 8). You can also
remove door into adjoining room (see op-
tion 3, Figure 8). Follow the National Fuel
Gas Code NFPA 54/ANS Z223.1, Section
5.3, Air for Combustion and Ventilation for
required size of ventilation grills or ducts.
Option 1
Option 3
12"
WARNING: Rework work-
sheet, adding the space of the
adjoining unconfined space. The
combined spaces must have
enough fresh air to supply all
appliances in both spaces.
Figure 8 - Ventilation Air from Inside Building
Ventilated
Ventilation Air From Outdoors
Outlet
Attic
Air
Provide extra fresh air by using ventilation
grills or ducts. You must provide two per-
manent openings: one within 12" of the
ceiling and one within 12" of the floor.
Connect these items directly to the outdoors
orspacesopentotheoutdoors.Thesespaces
include attics and crawl spaces. Follow the
National Fuel Gas Code NFPA 54/ANS
Z223.1,Section5.3,AirforCombustionand
Ventilation for required size of ventilation
grills or ducts.
Outlet
Air
To Attic
To
Crawl
Space
Inlet
Air
Ventilated
Crawl Space
IMPORTANT: Do not provide openings for
inlet or outlet air into attic if attic has a
thermostat-controlledpowervent.Heatedair
enteringtheatticwillactivatethepowervent.
Inlet Air
Figure 9 - Ventilation Air from Outdoors
106056
7
Download from Www.Somanuals.com. All Manuals Search And Download.
®
GAS RESIDENTIAL HEATERS
LOCATING HEATER
INSTALLATION
CAUTION:Thisheatercreates
warmaircurrents.Thesecurrents
moveheattowallsurfacesnextto
heater. Installing heater next to
vinyl or cloth wall coverings or
operatingheaterwhereimpurities
(suchastobaccosmoke,aromatic
candles, cleaning fluids, oil or
kerosene lamps, etc.) in the air
exist, may discolor walls.
NOTICE: This heater is intended
foruseassupplementalheat.Use
this heater along with your pri-
mary heating system. Do not in-
stall this heater as your primary
heat source. If you have a central
heating system, you may run
system’scirculatingblowerwhile
using heater. This will help circu-
late the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.
WARNING:Maintainthemini-
mumclearancesshowninFigure
10. If you can, provide greater
clearancesfromfloor,ceiling,and
joining wall.
You can locate heater on floor. The op-
tional hearth base is needed. You can also
install optional decorative mantels on the
heater (some mantels require the hearth
base). IMPORTANT: Only use optional
mantels and hearth base specified in this
manual. Purchase the optional mantel and
hearth base from your dealer. See Accesso-
ries, page 23.
IMPORTANT: Vent-free heaters add mois-
ture to the air. Although this is beneficial,
installing heater in rooms without enough
ventilationairmaycausemildewtoformfrom
too much moisture. See Fresh Air for Com-
bustion and Ventilation, pages 5 through 7.
WARNING: A qualified ser-
vice person must install heater.
Follow all local codes.
The heater may also be mounted on a wall.
Youcannotuseoptionalmantelifmounting
heater on a wall.
CAUTION: If you install the
heater in a home garage
• heaterpilotandburnermustbe
at least 18 inches above floor.
• locateheaterwheremovingve-
hicle will not hit it.
CHECK GAS TYPE
WARNING: Never install the
heater
Useonlypropane/LPgas.Ifyourgassupplyis
not propane/LP, do not install heater. Call
dealer where you bought heater for proper
type heater.
• in a bedroom or a bathroom
• in a recreational vehicle
• where curtains, furniture,
clothing, or other flammable
objectsarelessthan36inches
from the front, top, or sides of
the heater
Forconvenienceandefficiency,installheater
• where there is easy access for operation,
inspection, and service.
INSTALLATION ITEMS
Beforeinstallingheater,makesureyouhave
the items listed below.
• in coldest part of room.
• as a fireplace insert
• in high traffic areas
• in windy or drafty areas
An optional fan kit is available from your
dealer. See Accessories, page 23. If plan-
ning to use fan, locate heater near an electri-
cal outlet.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• manual shutoff valve *
• ground joint union
CEILING
• test gauge connection *
• sediment trap
• tee joint
36"
Minimum
• pipe wrench
6"
Minimum
From
Sides Of
Heater
* AnA.G.A.design-certifiedmanualshutoff
valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Pur-
chase the optional A.G.A. design-certified
manual shutoff valve from your dealer. See
Accessories, page 23.
Left
Side
Right
Side
5"
Minimum To Top Surface
Of Carpeting, Tile Or Other
Combustible Material
FLOOR
Figure 10 - Mounting Clearances As Viewed From Front of Heater
106056-01
8
Download from Www.Somanuals.com. All Manuals Search And Download.
OWNER’S MANUAL
Marking Screw Locations
INSTALLATION OPTIONS
INSTALLATION
1. Tape mounting bracket to wall where
heater will be located. Make sure
mounting bracket is level.
Continued
There are three options for mounting this
heater.
THERMOSTAT SENSING
BULB
A. Mounting heater to wall
B. Mounting heater to optional hearth base
WARNING:Maintainminimum
clearances shown in Figure 13. If
you can, provide greater clear-
ancesfromfloorandjoiningwall.
The thermostat sensing bulb has been placed
insidetheheaterforprotectionduringshipping.
C. Mounting heater to optional mantel
(some mantels require the hearth base)
Locating Thermostat Sensing
Bulb
1. Remove front panel of heater (see Fig-
ure 2, page 3).
A. MOUNTING HEATER TO
WALL
2. Mark screw locations on wall (see Fig-
ure 13).
Mounting Bracket
Note: Only mark last hole on each end
of mounting bracket. Insert mounting
screws through these holes only.
2. Locate thermostat sensing bulb just
under burner assembly.
The mounting bracket is located on back
panel of heater. It has been taped there for
shipping. Remove mounting bracket from
back panel.
IMPORTANT: Attach thermostat sensing
bulb to back of heater for proper operation.
3. Remove tape and mounting bracket
from wall.
11"
Min.
16"
Attaching Thermostat Sensing
Bulb
1. Remove thermostat sensing bulb from
holders inside heater. Route through
slot opening in bottom of heater.
Only Insert Mounting
Screws Through Last
Hole On Each End
20 3/4"
Min.
2. Place clamp on thermostat sensing bulb
as shown in Figure 11. Clamp is pro-
vided in hardware package.
Mounting
Bracket
AjdoingWal
Figure 12 - Mounting Bracket Location
3. Snap clamp into upper mounting hole
as shown in Figure 11. Mounting hole
Floor
Methods For Attaching Mount-
is located on lower left edge on back ing Bracket To Wall
Figure 13 - Mounting Bracket Clearances
of heater. Make sure the thermostat
Only use last hole on each end of mounting
sensing bulb is pointing up.
Attaching Mounting Bracket To
Wall
bracket to attach bracket to wall. These two
holes are 16 inches apart from their centers.
Attach mounting bracket to wall in one of
two ways.
Thermostat
Sensing Bulb
Note: Wall anchors, mounting screws, and
spacers are in hardware package. The hard-
ware package is provided with heater.
1. Attaching to wall stud
2. Attaching to wall anchor
Clamp
Attaching To Wall Stud Method
Attaching To Wall Stud: This method
providesthestrongesthold.Insertmounting
screws through mounting bracket and into
wall studs.
Forattachingmountingbrackettowallstuds
1. Drill holes at marked locations using
9/64" drill bit.
Figure11-AttachingThermostatSensing
Bulb
2. Place mounting bracket onto wall. Line
up last hole on each end of bracket with
holes drilled in wall.
AttachingToWallAnchor: Thismethod
allows you to attach mounting bracket to
hollow walls (wall areas between studs) or
to solid walls (concrete or masonry).
3. Insert mounting screws through bracket
and into wall studs.
Decidewhichmethodbettersuitsyourneeds.
Either method will provide a secure hold for
the mounting bracket.
4. Tighten screws until mounting bracket
is firmly fastened to wall studs.
Continued
106056
9
Download from Www.Somanuals.com. All Manuals Search And Download.
®
GAS RESIDENTIAL HEATERS
Placing Heater On Mounting
Bracket
1. Locate two horizontal slots on back
INSTALLATION
Continued
Attaching To Wall Anchor Method
panel of heater.
For attaching mounting bracket to hollow
walls (wall areas between studs) or solid
walls (concrete or masonry)
2. Place heater onto mounting bracket.
Slide horizontal slots onto stand-out
tabs on mounting bracket.
1. Drill holes at marked locations using
5/16" drill bit. For solid walls (concrete
or masonry), drill at least 1" deep.
Figure 17 - Installing Bottom Mounting
Screws
Horizontal Slots
B. MOUNTING HEATER ON
OPTIONAL HEARTH BASE
2. Fold wall anchor as shown in Figure 14.
Stand-Out
Tab
3. Insert wall anchor (wings first) into
hole. Tap anchor flush to wall.
Tools needed:
4. For thin walls (1/2" or less), insert red
key into wall anchor. Push red key to
“pop” open anchor wings.
• #2 Phillips screwdriver
• slotted screwdriver
Mounting Bracket
(attached to wall)
• electric drill (if securing base to floor)
IMPORTANT: Do not hammer key!
Figure 16 - Mounting Heater Onto Mount-
ing Bracket
The optional hearth base kit includes the
following:
For thick walls (over 1/2" thick) or solid
walls, do not pop open wings.
Installing Bottom Mounting
Screws
1. Locate two bottom mounting holes.
These holes are near bottom on back
panel of heater (see Figure 17).
• Hearth Base
5. Place mounting bracket onto wall. Line
up last hole on each end of bracket with
wall anchors.
• 4 Wood Screws
• 4 Sheet Metal Screws
• Brass Base Trim
• Hearth Insert
6. Insert mounting screws through bracket
and into wall anchors.
2. Mark screw locations on wall.
7. Tighten screws until mounting bracket
is firmly fastened to wall.
• 4 Anchors
3. Remove heater from mounting bracket.
• 2 Brass Screws
4. If installing bottom mounting screws
into hollow or solid wall, install wall
anchors. Follow steps 1 through 4 un-
der Attaching To Wall Anchor Method.
If installing bottom mounting screw
into wall stud, drill holes at marked lo-
cations using 9/64" drill bit.
Note: It is an option to secure “A” model
hearth base to floor. You must secure the
“B” and “C” model hearth base to floor. To
secure hearth base to floor, follow instruc-
tions under Securing Hearth Base to Floor,
page 11. If not securing hearth base to floor,
proceed to Mounting Heater to Optional
Hearth Base, page 11.
Figure 14 - Folding Anchor
5. Replace heater onto mounting bracket.
6. Place spacers between bottom mount-
ing holes and wall anchor or drilled hole.
7. Hold spacer in place with one hand.
With other hand, insert mounting screw
through bottom mounting hole and
spacer. Place tip of screw in opening
of wall anchor or drilled hole.
Figure 15 - Popping Open Anchor Wings
For Thin Walls
8. Tighten both screws until heater is firmly
secured to wall. Do not over tighten.
Note: Do not replace front panel at this
time. Replace front panel after making
gas connections and checking for leaks
(see pages 12 and 13).
106056-01
10
Download from Www.Somanuals.com. All Manuals Search And Download.
OWNER’S MANUAL
Securing Hearth Base to Floor
C. MOUNTING HEATER TO
OPTIONAL MANTEL
INSTALLATION
1. Position hearth base in desired location.
Mark holes for drilling (See Figure 18).
Remove hearth base.
Continued
See Instructions Included
With Mantel Kit.
Mounting Heater to Optional
Hearth Base
1. Lay heater on its back on a table with
the bottom of heater overhanging the
edge of the table.
2. For carpeted floor, make a small cut
with a sharp knife at marked locations
before drilling.
IMPORTANT: Only use the optional man-
tels specified in this manual. See Accesso-
ries, page 23 for proper mantel kits. This
heater is only approved for use with models
GMF800/GMU801 series, GM900F/
GM901Useries,GM902F/GM903Useries,
GM700F/GM701U, and GM702F/
GM703Useriesmantelkits.Usinganyother
mantel will void the A.G.A. approval for
this heater. Only use models GMF800/
GMU801series,GM900F/GM901Useries,
GM902F/GM903U series, GM700F/
GM701U, and GM702F/GM703U series
mantels with this heater. Do not use these
mantels with any other product.
If securing to a wood floor, drill a 3/4"
deep hole using a 1/8" diameter drill bit.
Do not use anchors in wood floors. If
securing to a concrete floor, drill a 1 3/8"
deep hole using a 1/4" diameter concrete
drill bit. Completely insert anchors into
each hole.
2. Remove 2 shipping screws in bottom
of heater. Discard shipping screws.
3. Line up mounting holes on top of hearth
base with holes in bottom of heater (see
Figure 18).
4. Using a Phillips screwdriver, secure
hearth base to heater with four sheet
metal screws (see Figure 18).
3. Mount heater to hearth base following
steps under Mounting Heater to Op-
tional Hearth Base. After mounting
heater, position heater and hearth base
over drilled holes. With slotted screw-
driver, secure hearth base to floor with
four wood screws.
5. Stand heater up on base.
6. Place hearth insert in hearth base as
shown in Figure 19.
7. Assemble brass trim (see steps 1
through 7 under Assembling and At-
taching Brass Trim, page 4).
8. Slide base trim on heater base. Attach
brass trim to base with two brass screws
included as shown in Figure 19.
Hearth
Insert
Shipping Screw
Base
Bottom of Heater
Screw
Brass Base
Trim
Mounting
Holes
Figure19-PlacingHearthInsertonHeater
Base and Attaching Brass Base Trim
Holes for Securing
Heater to Floor
Sheet Metal
Screw
Figure 18 - Attaching Heater to Hearth
Base
Continued
106056
11
Download from Www.Somanuals.com. All Manuals Search And Download.
®
GAS RESIDENTIAL HEATERS
INSTALLATION
CAUTION: Use only new,
CAUTION:Usepipejointseal-
ant that is resistant to liquid pe-
troleum (LP) gas.
Continued
black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
yourlocalcodes. Usepipeof1/2"
or greater diameter to allow
proper gas volume to heater. If
pipe is too small, undue loss of
pressure will occur.
CONNECTING TO GAS
SUPPLY
Apply pipe joint sealant lightly to male
threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe
could result in clogged heater valves.
WARNING: A qualified service
personmustconnectheatertogas
supply. Follow all local codes.
Installsedimenttrapinsupplylineasshown
in Figure 21. Locate sediment trap where it
is within reach for cleaning. Locate sedi-
ment trap where trapped matter is not likely
to freeze. A sediment trap traps moisture
and contaminants. This keeps them from
going into heater controls. If sediment trap
is not installed or is installed wrong, heater
may not run properly.
Installation must include a manual shutoff
valve, union, and plugged 1/8" NPT tap.
Locate NPT tap within reach for test gauge
hook up. NPT tap must be upstream from
heater (see Figure 21). An appliance main
gas valve (manual shutoff valve) must be
located within easy reach for turning the gas
supply on and off.
CAUTION: A qualified service
person must connect heater to
gassupply.Followalllocalcodes.
Never connect heater directly to
the propane/LP supply. This
heater requires an external regu-
lator (not supplied). Install the
external regulator between the
heater and propane/LP supply.
IMPORTANT: Hold pressure regulator
with wrench when connecting it to gas pip-
ing and/or fittings.
The installer must supply an external regu-
lator. The external regulator will reduce
incoming gas pressure. You must reduce
incominggaspressuretobetween11and14
inches of water. If you do not reduce incom-
ing gas pressure, heater regulator damage
could occur. Install external regulator with
the vent pointing down as shown in Figure
20. Pointing the vent down protects it from
freezing rain or sleet.
Note: Burner bracket
not shown for clarity
Pressure
Regulator
3/8" NPT
Pipe Nipple
Propane/LP
Supply Tank
Heater
Cabinet
Ground
Union Joint
Tee Joint
Reducer
Bushing to
1/8" NPT
External
Regulator
Manual Shutoff
Valve *
Test Gauge
Connection *
From External
Regulator (11" W.C.
to 14" W.C. Pressure)
1/8" NPT
Plug Tap
Vent
Pointing
Down
Tee Joint
Sediment Trap
Pipe Nipple
Figure 20 - External Regulator with Vent
Pointing Down
3" Minimum
Cap
Figure 21 - Gas Connection
* An A.G.A. design-certified manual shutoff valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Purchase the optional A.G.A. design-certified manual
shutoff valve from your dealer. See Accessories, page 23.
106056-01
12
Download from Www.Somanuals.com. All Manuals Search And Download.
OWNER’S MANUAL
TestPressuresEqualToorLessThan
1/2 PSIG (3.5 kPa)
Pressure Testing Heater Gas
Connections
1. Open manual shutoff valve (see Fig-
ure 22).
INSTALLATION
Continued
1. Close manual shutoff valve (see Fig-
ure 22).
CHECKING GAS
CONNECTIONS
2. Pressurize supply piping system by ei-
ther using compressed air or opening
propane/LP supply tank valve.
2. Open propane/LP supply tank valve.
3. Make sure control knob of heater is in
the OFF position.
WARNING: Test all gas pip-
ing and connections for leaks
after installing or servicing. Cor-
rect all leaks at once.
3. Check all joints from propane/LP sup-
ply tank to manual shutoff valve (see
Figure 23). Apply mixture of liquid
soap and water to gas joints. Bubbles
forming show a leak.
4. Check all joints from manual shutoff
valve to thermostat gas valve (see Fig-
ure 23). Apply mixture of liquid soap
and water to gas joints. Bubbles form-
ing show a leak.
WARNING:Neveruseanopen
flame to check for a leak. Apply a
mixture of liquid soap and water
toalljoints.Bubblesformingshow
a leak. Correct all leaks at once.
4. Correct all leaks at once.
5. Correct all leaks at once.
Manual
6. Light heater (see Operating Heater,
pages 14 and 15). Check all other in-
ternal joints for leaks.
Shutoff
Valve
Open
7. Turn off heater (see To Turn Off Gas to
CAUTION: Make sure exter-
nal regulator has been installed
between propane/LP supply and
heater.SeeguidelinesunderCon-
necting to Gas Supply, page 12.
Appliance, page 14).
8. Replace front panel.
Closed
Figure 22 - Manual Shutoff Valve
Pressure Testing Gas Supply
Piping System
TestPressuresInExcessOf1/2PSIG
(3.5 kPa)
Thermostat Gas
Valve Location
1. Disconnect heater and its individual
manual shutoff valve from gas supply
piping system. Pressures in excess of
1/2 psig will damage heater regulator.
Propane/LP
Supply Tank
2. Cap off open end of gas pipe where
manual shutoff valve was connected.
3. Pressurize supply piping system by ei-
ther using compressed air or opening
propane/LP supply tank valve.
Manual
Shutoff
Valve
4. Check all joints of gas supply piping
system. Apply mixture of liquid soap
and water to gas joints. Bubbles form-
ing show a leak.
5. Correct all leaks at once.
6. Reconnect fireplace and manual shutoff
valve to gas supply. Check reconnected
fittings for leaks.
Figure 23 - Checking Gas Joints
106056
13
Download from Www.Somanuals.com. All Manuals Search And Download.
®
GAS RESIDENTIAL HEATERS
7. Keep control knob pressed in for 30
seconds after lighting pilot. After 30
seconds, release control knob.
LIGHTING
INSTRUCTIONS
OPERATING
HEATER
• If control knob does not pop up
when released, contact a quali-
fied service person or gas sup-
plier for repairs.
Note: If pilot goes out, repeat steps
3 through 7. This heater has a safety
interlock system. Wait one (1)
minute before lighting pilot again.
1. STOP! Read the safety information,
FOR YOUR SAFETY
column 1.
READ BEFORE
LIGHTING
2. Make sure manual shutoff valve is
fully open.
3. Turn control knob clockwise
to the OFF position.
WARNING: If you do not fol-
low these instructions exactly, a
fireorexplosionmayresultcaus-
ing property damage, personal
injury or loss of life.
4. Wait five (5) minutes to clear out any
gas. Then smell for gas, including
near the floor. If you smell gas,
STOP! Follow “B” in the safety in-
formation. If you don’t smell gas, go
to the next step.
8. Push knob in slightly and turn con-
trol knob counterclockwise
C-clockwise
to desired heating level. The main
burner should light. Set control knob
to any heat level between HI and LO.
A. This appliance has a pilot which must
be lighted by hand. When lighting the
pilot, follow these instructions exactly.
5. Turn control knob counterclockwise
to the PILOT position. Press
in control knob for five (5) seconds
(see Figure 24).
CAUTION:Donottrytoadjust
heating levels by using the
manual shutoff valve.
C-clockwise
B. BEFORE LIGHTING smell all
around the appliance area for gas. Be
sure to smell next to the floor because
some gas is heavier than air and will
settle on the floor.
Note: You may be running this
heater for the first time after hook-
ing up to gas supply. If so, the con-
trol knob may need to be pressed in
for 30 seconds. This will allow air to
bleed from the gas system.
TO TURN OFF GAS
TO APPLIANCE
WHAT TO DO IF YOU SMELL
GAS
Shutting Off Heater
1. Turn control knob clockwise
to the OFF position.
• Do not try to light any appliance.
• Do not touch any electric switch; do
not use any phone in your building.
• Immediately call your gas supplier
from a neighbor’s phone. Follow
the gas supplier’s instructions.
• If you cannot reach your gas sup-
plier, call the fire department.
6. With control knob pressed in, push
down and release ignitor button.
This will light pilot. The pilot is at-
tached to the front of burner. If
needed, keep pressing ignitor but-
ton until pilot lights.
Note:Knob must be depressed slightly
2. Turn off all electric power to the ap-
pliance if service is to be performed.
Shutting Off Burner Only (pilot
stays lit)
Note: If pilot does not stay lit, refer
to Troubleshooting, pages 16 through
18. Also contact a qualified service
person or gas supplier for repairs.
Until repairs are made, light pilot with
match. To light pilot with match, see
Manual Lighting Procedure, page 15.
C. Use only your hand to push in or turn
the gas control knob. Never use tools.
If the knob will not push in or turn
by hand, don’t try to repair it, call a
qualified service technician or gas
supplier. Force or attempted repair
may result in a fire or explosion.
Turn control knob clockwise
the PILOT position.
to
Note: Knob must be depressed slightly.
Ignitor Electrode
Thermocouple
Pilot Burner
D. Do not use this appliance if any part
has been under water. Immediately
call a qualified service technician to
inspect the appliance and to replace
any part of the control system and
any gas control which has been un-
der water.
Ignitor Button
Control Knob
LO
P I L O T
O F F
H I
IGNITOR
Figure 24 - Control Knob In The OFF
Position
Figure 25 - Pilot
106056-01
14
Download from Www.Somanuals.com. All Manuals Search And Download.
OWNER’S MANUAL
BURNER FLAME PATTERN
OPERATING
INSPECTING
BURNER
Figure 28 shows a correct burner flame
pattern.Figure29showsanincorrectburner
flame pattern. The incorrect burner flame
patternshowsyellowtippingoftheflame. It
also shows the flame higher than one inch
above the log.
HEATER
Continued
Check pilot flame pattern and burner flame
pattern often.
THERMOSTAT
CONTROL
OPERATION
PILOT FLAME PATTERN
Figure26showsacorrectpilotflamepattern.
Figure 27 shows an incorrect pilot flame
pattern.Theincorrectpilotflameisnottouch-
ing the thermocouple. This will cause the
thermocouple to cool. When the thermo-
couple cools, the heater will shut down.
Note: When using the heater the first time,
the flame will be yellow for approximately
one hour until the log cures.
The thermostatic control used on this
heater differs from standard thermostats.
Standard thermostats simply turn on and
off the burner. The thermostat used on
this heater senses the room temperature.
The thermostat adjusts the amount of gas
flow to the burner. This increases or de-
creases the burner flame height. At times
the room may exceed the set temperature.
If so, the burner will shut off. The burner
willcyclebackonwhenroomtemperature
drops below the set temperature.
WARNING: If yellow tipping
occurs, your heater could pro-
duce increased levels of carbon
monoxide. If burner flame pat-
tern shows yellow tipping, follow
instructions,bottomofthispage.
If pilot flame pattern is incorrect, as shown
in Figure 27
• turn heater off (see To Turn Off Gas to
Appliance, page 14)
• see Troubleshooting, pages 16 through 18
NOTICE: Do not mistake orange
flames with yellow tipping. Dirt
or other fine particles enter the
heater and burn causing brief
patches of orange flame.
Pilot Burner
The control knob can be set to any heat
level between HI and LO.
Thermocouple
Note: The thermostat sensing bulb mea-
sures the temperature of air near the
heatercabinet.Thismaynotalwaysagree
with room temperature (depending on
housing construction, installation loca-
tion, room size, open air temperatures,
etc.). Frequent use of your heater will let
you determine your own comfort levels.
Ifburnerflamepatternisincorrect,asshown
in Figure 29
• turn heater off (see To Turn Off Gas to
Figure 26 - Correct Pilot Flame Pattern
Appliance, page 14)
• see Troubleshooting, pages 16 through 18
Top of Flame About
One Inch Above Logs
MANUAL LIGHTING
PROCEDURE
Pilot Burner
Thermocouple
1. Remove front panel (see Figure 2,
page 3).
2. Follow steps 1 through 5 under Light-
Figure 27 - Incorrect Pilot Flame Pattern
ing Instructions, page 14.
3. With control knob pressed in, strike
match. Hold match to pilot until pi-
lot lights.
Figure 28 - Correct Burner Flame Pattern
Yellow Tipping
4. Keep control knob pressed in for 30
seconds after lighting pilot. After 30
seconds, release control knob. Now
follow step 8 under Lighting Instruc-
tions, page 14.
5. Replace front panel.
Figure29-IncorrectBurnerFlamePattern
106056
15
Download from Www.Somanuals.com. All Manuals Search And Download.
®
GAS RESIDENTIAL HEATERS
TROUBLESHOOTING
Note: For additional help, visit DESA
International’s Technical Service web
WARNING: Turn off and un-
plug heater and let cool before
servicing. Only a qualified ser-
vice person should service and
CAUTION: Never use a wire,
needle, or similar object to clean
ODS/pilot.ThiscandamageODS/
pilot unit.
repair heater.
Note:Alltroubleshootingitemsarelistedin
order of operation.
OBSERVED PROBLEM
POSSIBLE CAUSE
REMEDY
When ignitor button is pressed, there is no 1. Ignitor electrode positioned wrong
spark at ODS/pilot 2. Ignitor electrode broken
1. Replace ignitor
2. Replace ignitor
3. Ignitor electrode not connected to igni- 3. Reconnect ignitor cable
tor cable
4. Ignitor cable pinched or wet
4. Free ignitor cable if pinched by any
metal or tubing. Keep ignitor cable dry
5. Tighten nut holding piezo ignitor to
heater cabinet. Nut is located inside
heater cabinet at top
5. Piezo ignitor nut is loose
6. Broken ignitor cable
7. Bad piezo ignitor
6. Replace ignitor cable
7. Replace piezo ignitor
When ignitor button is pressed, there is 1. Gas supply turned off or manual shutoff 1. Turn on gas supply or open manual
spark at ODS/pilot but no ignition
valve closed
shutoff valve
2. Control knob not in PILOT position
2. Turn control knob to PILOT position
3. Control knob not pressed in while in 3. Press in control knob while in PILOT
PILOT position
position
4. Air in gas lines when installed
4. Continue holding down control knob. Re-
peat igniting operation until air is removed
5. Contact local propane/LP gas company
6. Clean ODS/pilot (see Cleaning and
Maintenance, page 19) or replace ODS/
pilot assembly
5. Depleted gas supply
6. ODS/pilot is clogged
7. Gas regulator setting is not correct
7. Replace gas regulator
ODS/pilot lights but flame goes out when 1. Control knob not fully pressed in
1. Press in control knob fully
control knob is released
2. Control knob not pressed in long enough 2. After ODS/pilot lights, keep control
knob pressed in 30 seconds
3. Safety interlock system has been trig- 3. Wait one minute for safety interlock sys-
gered
tem to reset. Repeat ignition operation
4. Fully open manual shutoff valve
4. Manual shutoff valve not fully open
5. Thermocouple connection loose at con- 5. Hand tighten until snug, then tighten
trol valve 1/4 turn more
6. Pilot flame not touching thermocouple, 6. A) Contact local propane/LP company
which allows thermocouple to cool,
causing pilot flame to go out. This prob-
lem could be caused by one or both of
the following:
B) Clean ODS/pilot (see Cleaning and
Maintenance, page 19) or replace ODS/
pilot assembly
A) Low gas pressure
B) Dirty or partially clogged ODS/pilot
7. Thermocouple damaged
8. Control valve damaged
7. Replace thermocouple
8. Replace control valve
106056-01
16
Download from Www.Somanuals.com. All Manuals Search And Download.
OWNER’S MANUAL
TROUBLESHOOTING
Continued
OBSERVED PROBLEM
POSSIBLE CAUSE
REMEDY
Burner does not light after ODS/pilot is lit
1. Burner orifice is clogged
1. Clean burner (see Cleaning and Mainte-
nance, page 19) or replace burner orifice
2. Burner orifice diameter is too small
3. Inlet gas pressure is too low
2. Replace burner orifice
3. Contact local propane/LP company
Delayed ignition of burner
1. Manifold pressure is too low
2. Burner orifice is clogged
1. Contact local propane/LP company
2. Clean burner (see Cleaning and Mainte-
nance, page 19) or replace burner orifice
Burner backfiring during combustion
1. Burner orifice is clogged or damaged
1. Clean burner (see Cleaning and Mainte-
nance, page 19) or replace burner orifice
2. Replace burner
2. Burner damaged
3. Gas regulator defective
3. Replace gas regulator
Yellow flame during burner combustion
1. Not enough air
1. Check burner for dirt and debris. If
found, clean burner (see Cleaning and
Maintenance, page 19)
2. Gas regulator defective
2. Replace gas regulator
Slight smoke or odor during initial operation 1. Residues from manufacturing processes 1. Problem will stop after a few hours of
operation
Heater produces a whistling noise when 1. Turning control knob to HI position 1. Turn control knob to LO position and
burner is lit
when burner is cold
2. Air in gas line
let warm up for a minute
2. Operate burner until air is removed from
line. Have gas line checked by local pro-
pane/LP company
3. Air passageways on heater blocked
3. Observe minimum installation clear-
ances (see Figure 10, page 8)
4. Dirty or partially clogged burner orifice 4. Clean burner (see Cleaning and Mainte-
nance, page 19) or replace burner orifice
Whitepowderresidueformingwithinburner 1. When heated, vapors from furniture pol- 1. Turn heater off when using furniture
box or on adjacent walls or furniture
ish, wax, carpet cleaners, etc. turn into
polish, wax, carpet cleaners, or similar
white powder residue
products
Continued
106056
17
Download from Www.Somanuals.com. All Manuals Search And Download.
®
GAS RESIDENTIAL HEATERS
TROUBLESHOOTING
Continued
WARNING: If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your
building.
• Immediatelycallyourgassupplierfromaneighbor’sphone. Followthe
gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
IMPORTANT: Operating heater where impurities in air exist may create odors. Cleaning
supplies, paint, paint remover, cigarette smoke, cements and glues, new carpet or textiles,
etc., create fumes. These fumes may mix with combustion air and create odors.
OBSERVED PROBLEM
POSSIBLE CAUSE
REMEDY
Heater produces a clicking/ticking noise 1. Metal expanding while heating or con-
1. This is common with most heaters. If
noise is excessive, contact qualified ser-
vice person
just after burner is lit or shut off
tracting while cooling
Heater produces unwanted odors
1. Heater burning vapors from paint, hair
spray, glues, etc. (see IMPORTANT
statement above)
1. Ventilate room. Stop using odor caus-
ing products while heater is running
2. Gas leak. SeeWarning statement at
top of page
2. Locate and correct all leaks (see Check-
ing Gas Connections, page 13)
Heater shuts off in use (ODS operates)
1. Not enough fresh air is available
2. Low line pressure
3. ODS/pilot is partially clogged
1. Open window and/or door for ventilation
2. Contact local propane/LP company
3. Clean ODS/pilot (see Cleaning and
Maintenance, page 19)
Gas odor even when control knob is in OFF 1. Gas leak. SeeWarning statement at
1. Locate and correct all leaks (see Check-
ing Gas Connections, page 13)
2. Replace control valve
position
top of page
2. Control valve defective
Gas odor during combustion
1. Foreign matter between control valve
and burner
1. Take apart gas tubing and remove for-
eign matter
2. Gas leak. SeeWarning statement at
top of page
2. Locate and correct all leaks (see Check-
ing Gas Connections, page 13)
106056-01
18
Download from Www.Somanuals.com. All Manuals Search And Download.
OWNER’S MANUAL
4. Check the injector holder located at the
end of the burner tube again. Remove
CLEANING AND
MAINTENANCE
WARNING: Turn off heater
and let cool before cleaning.
REPLACEMENT
any large particles of dust, dirt, lint, or PARTS
pet hairs with a soft cloth or vacuum
Note: Use only original replacement parts.
Thiswillprotectyourwarrantycoveragefor
parts replaced under warranty.
cleaner nozzle.
5. In case any large clumps of dust have
now been pushed into the burner repeat
steps 3 and 4.
PARTS UNDER WARRANTY
CAUTION: You must keep
control areas, burner, and circu-
lating air passageways of heater
clean. Inspect these areas of
heater before each use. Have
heaterinspectedyearlybyaquali-
fied service person. Heater may
needmorefrequentcleaningdue
to excessive lint from carpeting,
pet hair, etc.
Clean the pilot assembly also. A yellow tip
on the pilot flame indicates dust and dirt in
the pilot assembly. There is a small pilot air
inlet hole about two inches from where the
pilot flame comes out of the pilot assembly
(see Figure 30). With the unit off, lightly
blow air through the air inlet hole. You may
blowthroughadrinkingstrawifcompressed
air is not available.
Contact authorized dealers of this product.
If they can’t supply original replacement
part(s), call DESA International’s Techni-
cal Service Department at 1-800-323-5190
for referral information.
When calling DESA International, have
ready
• your name
• your address
Pilot Air Inlet
Hole
CLEANING BURNER
• model and serial numbers of your heater
• how heater was malfunctioning
INJECTOR HOLDER AND
PILOT AIR INLET HOLE
• type of gas used (propane/LP or natural
gas)
The primary air inlet holes allow the proper
amount of air to mix with the gas. This
provides a clean burning flame. Keep these
holesclearofdust, dirt, andlint. Cleanthese
air inlet holes prior to each heating season.
Blocked air holes will create soot. We rec-
ommend that you clean the unit every 2,500
hours of operation or every three months.
• purchase date
Usually, we will ask you to return the defec-
tive part to the factory.
Pilot Assembly
Figure 30 - Pilot Inlet Air Hole
PARTS NOT UNDER
WARRANTY
CABINET
Contact authorized dealers of this product. If
theycan’tsupplyoriginalreplacementpart(s),
call DESA International’s Parts Department
at 1-800-972-7879 for referral information.
Wealsorecommendthatyoukeeptheburner
tube and pilot assembly clean and free of
dustanddirt.Tocleanthesepartswerecom-
mend using compressed air no greater than
30 PSI. Your local computer store, hard-
ware store, or home center may carry com-
pressed air in a can. You can use a vacuum
cleaner in the blow position. If using com-
pressed air in a can, please follow the direc-
tions on the can. If you don't follow direc-
tions on the can, you coulddamage the pilot
assembly.
Air Passageways
• Use a vacuum cleaner or pressurized air
to clean.
When calling DESA International, have
ready
Exterior
• Use a soft cloth dampened with a mild
soap and water mixture. Wipe the cabi-
net to remove dust.
• model number of your heater
• the replacement part number
1. Shut off the unit, including the pilot.
Allow the unit to cool for at least thirty
minutes.
2. Inspect burner, pilot, and primary air
inlet holes on injector holder for dust
and dirt.
3. Blow air through the ports/slots and
holes in the burner.
106056
19
Download from Www.Somanuals.com. All Manuals Search And Download.
®
GAS RESIDENTIAL HEATERS
ILLUSTRATED
PARTS
24
21
BREAKDOWN
25
23
VMH3000TPS
7
8
10
18
20
6
13
16
17
12
5
14
9
6
10
11
22
26
1
15
19
3
4
2
1
1
12-1
12-2
106056-01
20
Download from Www.Somanuals.com. All Manuals Search And Download.
OWNER’S MANUAL
This list contains replaceable parts used in your heater. When ordering parts, follow the
instructions listed under Replacement Parts on page 19 of this manual.
PARTS LIST
VMH3000TPS
KEY
NO.
VMH3000TPS
PART NO.
DESCRIPTION
QTY.
1
2
3
4
5
6
7
8
098304-01
Screw, #10 x 3/8"
Front Panel
6
1
1
1
1
6
1
8
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
2
1
1
1
5
100566-01CK
100573-01BR
100568-02BR
100903-04
098303-02
099066-01
M11084-26
100571-03BR
098271-03
098249-01
099440-06
Screen Assembly
Burner Shield
Log, Service Kit
Screw, #8 x 3/8"
Mounting Bracket
Screw, #10 x 3/8"
Deflector Unit
Ignitor Cable
9
10
11
12
Nut, M5
ODS/Pilot Assembly
Thermocouple
Ignitor Electrode
Burner
3/16" Pilot Tubing
Injector
12-1 098514-01
12-2 098594-01
13
103447-01
099387-03
103845-07
NJF-8C
14
15
16
17
18
19
20
21
22
23
24
25
26
Nut, Hex
099415-06
103408-01
105293-01
105292-01
103837-03
101046-01
105291-02
098529-07
097159-04
098304-03
Pressure Regulator
Burner Bracket
3/8" Outlet (Burner) Tubing
3/8" Inlet Tubing
Bracket Support
Log Strap
Thermostat Gas Valve
Cabinet
Piezo Ignitor
Screw, #8 x 3/8"
PARTS AVAILABLE — NOT SHOWN
100562-01
100563-01
101899-01
100769-02
100642-01
100565-01
101416-30
Lighting Instructions Plate
Warning Plate
1
1
1
1
1
1
1
Brass Trim Assembly
Brass Trim Hardware
Hardware Package
Warning Plate Fastener Kit
Instructional Video
106056
21
Download from Www.Somanuals.com. All Manuals Search And Download.
®
GAS RESIDENTIAL HEATERS
SPECIFICATIONS
TECHNICAL
SERVICE
Btu (Variable)
Type Gas
15,000/30,000
Propane/LP Only
Piezo
You may have further questions about in-
stallation, operation, or troubleshooting. If
so, contact DESA International’s Technical
Service Department at 1-800-323-5190.
Ignition
Pressure Regulator Setting
8" W.C.
Inlet Gas Pressure (in. of water) *
Maximum
14"
11"
You can also visit DESA International’s
Technical Service web site at
Minimum
Dimensions, Inches (H x W x D)
Heater
Carton
23.75 x 25.9 x 8.5
25.8 x 28.7 x 10.1
SERVICE HINTS
Weight (pounds)
Heater
29
35
When Gas Pressure Is Too Low
Shipping
• pilot will not stay lit
* For purposes of input adjustment
• burner(s) will have delayed ignition
• heater will not produce specified heat
• propane/LP gas supply may be low
When Gas Quality Is Bad
• pilot will not stay lit
• burner(s) will produce flames and soot
• heater will backfire when lit
Youmayfeelyourgaspressureistoolowor
gas quality is bad. If so, contact your local
propane/LP supplier.
106056-01
22
Download from Www.Somanuals.com. All Manuals Search And Download.
OWNER’S MANUAL
ACCESSORIES
Purchasetheseheateraccessoriesfromyour
local dealer. If they can not supply these
accessoriescallDESAInternational’sSales
Department at 1-800-458-2472 for infor-
mation. You can also write to the address
listed on the back page of this manual.
PREMIER MANTEL
Unfinished - GM903U Series
Finished - GM902F Series
White Lacquer - GM904W Series
For use with heater. Features a built-in base.
Sturdy hardwood construction with classic
styling and attractive molding. Available in
white lacquer, walnut finish or an unfin-
ished hardwood, ready to stain or paint.
Completeassemblyandinstallationinstruc-
tions included.
Note: White lacquer mantel features differ
slightly from illustration.
MANUAL SHUTOFF VALVE
GA5010
Manual shutoff valve with 1/8" NPT tap.
CORNER MANTEL
Unfinished - GM703U Series
Finished - GM702F Series
For use with heater. Features a built-in base.
Space-savingcornerdesignfeaturingclean,
classic lines. Available in a walnut finish or
an unfinished hardwood, ready to stain or
paint. Complete assembly and installation
instructions included.
FAN KITS
GA3100A - Manually-Controlled
GA3200TA - Thermostatically-
Controlled
Provides better heat distribution. Makes
heater more efficient. Complete installation
and operating instructions included.
HEARTH BASE - GHB802
SERIES
For locating heater on the floor. Includes
brass trim. Complete installation instruc-
tions included.
106056
23
Download from Www.Somanuals.com. All Manuals Search And Download.
WARRANTY INFORMATION
KEEP THIS WARRANTY
Model
Serial No.
Date Purchased
Always specify model and serial numbers when communicating with the factory.
We reserve the right to amend these specifications at any time without notice. The only warranty applicable is our standard written
warranty. We make no other warranty, expressed or implied.
LIMITED WARRANTY
VENT-FREE PROPANE/LP MINI-HEARTH® GAS HEATERS
DESA International warrants this product to be free from defects in materials and components for four (4) years and five (5) years on
stainless steel burners from the date of first purchase, provided that the product has been properly installed, operated and maintained in
accordance with all applicable instructions. To make a claim under this warranty the Bill of Sale or cancelled check must be presented.
Thiswarrantyisextendedonlytotheoriginalretailpurchaser.Thiswarrantycoversthecostofpart(s)requiredtorestorethisheatertoproper
operating condition and an allowance for labor when provided by a DESA Authorized Service Center. Warranty part(s) MUST be obtained
through authorized dealers of this product and/or DESA International who will provide original factory replacement parts. Failure to use
original factory replacement parts voids this warranty. The heater MUST be installed by a qualified installer in accordance with all local
codes and instructions furnished with the unit.
This warranty does not apply to parts that are not in original condition because of normal wear and tear, or parts that fail or become damaged
as a result of misuse, accidents, lack of proper maintenance or defects caused by improper installation. Travel, diagnostic cost, labor,
transportation and any and all such other costs related to repairing a defective heater will be the responsibility of the owner.
TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT;
THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES AND LIMITS THE DURATION
OF ANY AND ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE TO FOUR (4) YEARS ON ALL COMPONENTS AND FIVE (5) YEARS ON STAINLESS STEEL
BURNERS FROM THE DATE OF FIRST PURCHASE; AND DESA INTERNATIONAL’S LIABILITY IS HEREBY LIMITED TO
THE PURCHASE PRICE OF THE PRODUCT AND DESA INTERNATIONAL SHALL NOT BE LIABLE FOR ANY OTHER
DAMAGES WHATSOEVER INCLUDING INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states do not allow a limitation on how long an implied warranty lasts or an exclusion or limitation of incidental or consequential
damages, so the above limitation on implied warranties, or exclusion or limitation on damages may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights that vary from state to state.
For information about this warranty write:
INTERNATIONAL
2701 Industrial Drive
P.O. Box 90004
Bowling Green, KY 42102-9004
106056 01