Tyco Network Card KT MOD OUT16 User Manual

KT-MOD-OUT16  
KT-400 Expansion Module 16-Output with SPI Cable Install Sheet  
3.2. Mounting  
1. Introduction  
The KT-MOD-OUT16 is a 16 zones output module. It can be  
used for elevator access control (may require additional  
hardware).  
The KT-MOD-OUT16 can be installed inside a compatible cabinet  
(KT-MOD-CAB or KT-400) or mounted in a dry and secure  
location at less than 1 m (3 ft) from the KT-400.  
The module supports daisy chaining; you can interconnect up to  
16 KT-MOD-OUT16 modules for a total of 256 external outputs  
per KT-400. You can mix relays and outputs in the same SPI  
group, up to 256 outputs.  
Perform the following steps to mount the unit:  
1. Press the four (4) plastic standoffs through the mounting  
holes of the cabinet,  
Note 1: The KT-400 SPI port maximum current draw, when the  
12V AUX terminals are not used, is 500 mA.  
2. Secure the cabinet to the wall in the desired location. Use  
appropriate wall anchors when securing the cabinet to  
drywall, plaster, concrete, brick or other surfaces,  
Note 2: External power supply (12 VDC, 2 Amps) is required  
when the total current draw exceeds 500mA on the SPI Port.  
3. Press the module into the plastic standoffs to secure the  
Note 3: There are already 4 relays available on the KT-400.  
Make sure to check the relays number assignments to prevent  
redundancy unless it has been planned on purpose.  
module to the cabinet.  
Once the unit is mounted, wiring may be started.  
3.3. Installation and Wiring  
2. Specifications  
Before beginning to wire the unit, ensure that all power (AC  
transformer and battery) is disconnected from the KT-400.  
Maximum Current draw: up to 750 mA per module  
Connects to the KT-400 via the 6-pin SPI connector  
16 outputs low current module, 5 to 24 VDC, 4 to 750 mA  
Can be used for elevator access control or general output  
Perform the following steps to complete wiring:  
1. Connect the 6-pin SPI connector to:  
the KT-400 SPI port, or  
the SPI OUT of the previous output module (KT-MOD-  
REL8 and KT-MOD-OUT16 only), or  
Can be mixed with output module KT-MOD-REL8 in the  
same SPI group  
the SPI EXP of the 1st input module KT-MOD-INP16  
connected to the KT-400 SPI port.  
2. Connect the six SPI wires (blue (BLU), white (WHT), green  
(GRN), yellow (YEL), black (BLK) and red (RED)) to the SPI  
IN (TB1) terminals.  
3. Installing the KT-MOD-OUT16  
3.1. Unpacking  
3. Connect the 6-pin SPI connector from the SPI OUT to the  
next output module (KT-MOD-REL8 and KT-MOD-OUT16  
only).  
The KT-MOD-OUT16 package includes the following parts:  
4. Complete all output wiring.  
One (1) KT-MOD-OUT16 module, 14 cm x 8 cm (5.7 in x  
3.25 in)  
One (1) SPI cable with 1 SPI connector, 41 cm (16 in)  
Four (4) plastic standoffs  
Two (2) installation sheets, English and French  
Tel.: 1 (450) 444 2030 Toll Free: 1-888-222-1560 Fax: 1 (450) 444 2029 Internet: www.kantech.com  
Copyright © 2008 Tyco International Ltd. and its Respective Companies. All Rights Reserved. Specifications may change without notice.  
Kantech and the Kantech logo are trademarks of Tyco International Ltd. and its Respective Companies.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DN1781-0809  

Teac Stereo Receiver PD H600 User Manual
Toshiba IP Phone IP Communications System User Manual
Trane Air Conditioner SS PRC003 EN User Manual
TRENDnet Webcam TV IP100 User Manual
Tripp Lite Switch B034 102 R User Manual
Troy Bilt Air Conditioner MXZ 3A30NA User Manual
Turbo Air Refrigerator TUR 28SD User Manual
United States Stove Electric Heater 3000 L User Manual
ViewSonic Computer Monitor G70m G70mb User Manual
Viking Range F1605G User Manual