Traulsen Appliance Trim Kit TE Series User Manual

Traulsen Refrigeration  
SERVICE MANUAL #07  
Instructions For The Troubleshooting  
And Repair Of All Traulsen TE-Series  
Refrigerated Equipment Stand Models  
Traulsen’s equipment stands are solely intended for use with cooking equipment.  
-NOTICE-  
This Manual is prepared for the use of trained Authorized Traulsen Service Agents and should not be used  
by those not properly qualified. This manual is not intended to be all encompassing, but is written to  
supplement the formal training, on-the-job experience and other product knowledge acquired by Autho-  
rized Traulsen Service Agents. Before proceeding with any work, you should read, in its entirety, the repair  
procedure you wish to perform to determine if you have the necessary tools, instruments and skills required  
to perform the procedure. Procedures for which you do not have the necessary tools, instruments and  
skills should be performed only by a trained Authorized Traulsen Service Agent.  
Reproduction or other use of this Manual, without the express written consent of Traulsen, is prohibited.  
FORM NUMBER TR35896 - REVISED. 06/15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
II. GENERAL INFORMATION  
II. a - INTRODUCTION:  
This manual applies to the following Traulsen  
models only:  
II. g - REFN SYSTEM - THEORY OF OPERATION:  
The refrigeration system is the mechanism whereby  
heat is transferred from the cabinet to the outside air.  
It works under the principle that the heat moves from  
hot to cold as it tries to establish equilibrium.  
TE036HT, TE048HT, TE060HT, TE065HT, TE072HT  
TE084HT, TE096HT, TE110HT, TE125HT &  
TE139HT  
The microprocessor control signals a need for heat to  
be removed from the cabinet. The compressor begins  
by compressing the refrigerant gas as it is discharged.  
The high pressure refrigerant now circulates through  
the condenser, removing heat from the refrigerant and  
condensing it into a liquid. From there the refrigerant  
flows to the filter drier which removes all traces of  
moisture and particles from the system.  
II. b - MODEL DESIGNATIONS:  
TE060HT  
Position 1: TE = Traulsen Equipment Stand  
Position 2: 036 = 36” Long Model  
048 = 48” Long Model  
060 = 60” Long Model  
Position 3: HT = Refrigerator  
After the filter drier, the refrigerant passes through a  
“metering device.” Traulsen uses a capillary tube to  
regulate the flow of refrigerant into the evaporator  
coils.  
In the evaporator coil, heat is transferred from the  
cabinet to the refrigerant, which changes from a cold  
liquid to a warm low pressure gas. When the desired  
cabinet air temperature has been reached, the  
microprocessor control shuts off the compressor.  
II. c - WIRING DIAGRAM:  
Refer to the wiring diagram for any service work  
performed on this unit. A copy is located on the unit  
when shipped. Should you require another copy, or a  
wiring diagram for an older production unit, please  
contact Traulsen Service at (800) 825-8220, and  
provide the model and serial number of the unit  
involved (this information is located on the serial  
tag, see page one).  
II. d - INSTALLATION:  
Generally TE-Series refrigeration products are installed  
by the dealer, or others contracted by the dealer or  
owner. Detailed installation instructions are included  
along with each unit when shipped.  
II. e - CLEANING:  
Detailed cleaning instructions are included with each  
unit, however special care MUST be given to the  
condenser coil. The condenser coil must be cleaned  
at a minimum of every six months. This can be done  
with a vacuum cleaner using a brush attachment, or a  
stiff brush or wisk broom. For more information please  
refer to Section V.aof the TE-Series Owners  
Manual.  
Fig. 1 - The Refrigeration System  
II. h - AIR FLOW REQUIREMENTS:  
To assure optimum performance, the condensing unit  
of your Traulsen unit MUST have an adequate supply  
of air for cooling purposes. Therefore, the operating  
location must allow a minimum of 12clearance in  
front of the louvers to allow for unrestricted air flow to  
the condensing unit.  
II. f - TOOL REQUIREMENTS:  
For most jobs a standard set of hand tools, a VOM and  
AC current tester, along with a temperature tester or  
thermometer are adequate. However in some cases  
the following additional tools may be required as well:  
II. i - THE MICROPROCESSOR CONTROL:  
For detailed information on replacement, repair or  
adjustment of the INTELA-TRAUL® microprocessor  
control please refer to it’s service manual (form  
number TR35705).  
Refrigeration Guage Manifold  
Refrigeration Reclaiming Equipment  
Acetylene Torch  
Anti-Static Grounding Kit (TL 84919)  
Nitrogen Bottle With Gauges  
Thin 5/16Open End Wrench  
Refrigerant Reclaim Unit  
-2-  
Download from Www.Somanuals.com. All Manuals Search And Download.  
II. GENERAL INFORMATION (contd)  
II. j - CONTROL LOCATION:  
II. l - SPECIFICATIONS:  
On all TE-Series refrigerator models, the micro-  
processor control is located on the louver assembly.  
The louvers/refrigeration system are mounted standard  
on the left side, but as an option are available mounted  
on the right (see figure 2).  
TE-Series Refrigerated Equipment Stands  
TE036  
1/3 HP  
2440  
4.5  
TE048  
1/3 HP  
2440  
4.5  
TE060  
1/3 HP  
2440  
4.9  
Horsepower  
Condensing Unit - BTU/HR  
Condensing Unit Amp Draw  
Fan, Lights, Etc. Amp Draw  
Refrigerant  
0.6  
0.6  
1.1  
R-404A  
14.0  
R-404A  
14.5  
R-404A  
16.0  
Refrigerant Charge (oz.)  
Fig. 2  
Control Location  
TE-Series Refrigerated Equipment Stands  
TE065  
1/3 HP  
2440  
4.9  
TE072  
1/3 HP  
2440  
4.9  
TE084  
1/3 HP  
2440  
4.9  
Horsepower  
Condensing Unit - BTU/HR  
Condensing Unit Amp Draw  
Fan, Lights, Etc. Amp Draw  
Refrigerant  
II. k - OPERATING DATA CHART:  
Refrigerated Models (cabinet temperature set at 38°F)  
1.1  
1.1  
1.1  
Ambient  
70°F  
35 PSIG  
3°F  
200 PSIG 295 PSIG  
88°F 115°F  
100°F  
50 PSIG  
16°F  
R-404A  
16.5  
R-404A  
16.5  
R-404A  
17.0  
Suction Pressure  
Suction Temperature  
Discharge Pressure  
Discharge Temperature  
Refrigerant Charge (oz.)  
TE-Series Refrigerated Equipment Stands  
TE096  
1/2 HP  
4090  
9.6  
TE110  
1/2 HP  
4090  
9.6  
TE125  
1/2 HP  
4090  
9.6  
Horsepower  
Condensing Unit - BTU/HR  
Condensing Unit Amp Draw  
Fan, Lights, Etc. Amp Draw  
Refrigerant  
1.5  
1.5  
1.5  
R-404A  
20.0  
R-404A  
20.0  
R-404A  
20.0  
Refrigerant Charge (oz.)  
TE-Series Refrigerated Equipment Stands  
TE139  
Horsepower  
1/2 HP  
4090  
9.6  
Condensing Unit - BTU/HR  
Condensing Unit Amp Draw  
Fan, Lights, Etc. Amp Draw  
Refrigerant  
1.9  
R-404A  
21.0  
Refrigerant Charge (oz.)  
-3-  
Download from Www.Somanuals.com. All Manuals Search And Download.  
III. REMOVAL & REPLACEMENT OF BASIC PARTS  
WARNING: DISCONNECT THE ELECTRICAL POWER TO THE MACHINE  
AND FOLLOW LOCKOUT/TAGOUT PROCEDURES.  
III. b - EVAPORATOR HOUSING COVER:  
III. a - LOUVER ASSEMBLY/SYSTEM ACCESS:  
Remove the back cover by removing the four screws  
which secure this to the cabinet (see figure 6).  
To remove the louver assembly first place your hands  
under the louver panel and lift this up off the bracket  
and then away from the cabinet face (see figure 3).  
Fig. 6  
Reverse the procedure when done to reinstall.  
III. c - REMOVING THE DRAWERS:  
Remove the drawer(s) from the drawer frame by lifting  
up on the drawer, and then pulling out.  
Fig. 3  
To gain full access to the refrigeration system from  
the side, remove the cover by removing the bottom  
screws (see figures 4 & 5).  
III. d - REMOVING THE DRAWER FRAME:  
Once the drawer(s) have been removed, the drawer  
frame module can also be removed by loosening the  
front and back clamping knobs (2 of each), located on  
the cross-rail and liner locks (see figures 7 & 8). Slide  
the front cross-rail locks towards the center of the  
drawer frame module and allow the liner locks to drop  
down from the top of the liner.Pull the drawer frame  
module forward, tip forward and pull out. The entire  
frame assembly is now free to slide out of the cabinet.  
Fig. 4  
Screw  
Locations  
Fig. 7  
Fig. 5  
Side System  
Access  
When finished, lower the louver assembly into  
position and replace the side panel. Secure these in  
place using the previously removed screws.  
Fig. 8  
-4-  
Download from Www.Somanuals.com. All Manuals Search And Download.  
III. REMOVAL & REPLACEMENT OF BASIC PARTS (contd)  
WARNING: DISCONNECT THE ELECTRICAL POWER TO THE MACHINE  
AND FOLLOW LOCKOUT/TAGOUT PROCEDURES.  
III. e - DRAWER GASKETS:  
III. h - ACCESSING START COMPONENTS (contd):  
To remove the gasket to be replaced, grasp it firmly by  
one corner and pull it out. Before attempting to install  
a new gasket, both the unit and the gasket itself must  
be at room temperature. Insert the four corners first  
by using a rubber mallet (or hammer with a block of  
wood). After the corners are properly inserted, work  
your way towards the center from both ends by gently  
hitting with a mallet until the gasket is completely  
seated in place (see figure 9 for gasket cross section).  
Fig. 10  
Fig. 9  
NOTE: The gasket may appear too large, but if it is  
installed as indicated above it will slip into place.  
III. f - THE MICROPROCESSOR CONTROL:  
To remove the microprocessor controller from the unit  
in which it was installed, please refer to section Vof  
your INTELA-TRAUL® Master Service Manual.  
III. g - DRAIN PAN:  
To remove the drain pan, begin by removing the  
evaporator housing cover as outlined in section III.  
c.Next, remove the screws and brackets which  
secure the drain pan, and remove the drain tube from  
the drain pan. Finish by sliding the drain pan out from  
under the coil.  
Fig. 11  
Reverse the procedure to install.  
III. h - ACCESSING START COMPONENTS:  
The start components are located behind the front  
louver, inside a metal tray.  
To access the start components, first remove the  
louver assembly as shown in section III. a. Next loosen  
the top set screw (see figure 10). and remove the molex  
connection in the back of the box to gain access to  
the back set screw. Slide the electrical box out the  
font on its tracks.  
See figure 11 for component detail.  
-5-  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IV. a - REPLACING THE CONDENSER FAN MOTOR AND/OR BLADE  
STEP 1:  
STEP 2:  
Remove the louver assembly as outlined in  
section III. ato gain access through left side.  
WARNINGS:  
1) DISCONNECT THE ELECTRICAL POWER TO THE  
MACHINE AND FOLLOW LOCKOUT/TAGOUT  
PROCEDURES.  
Remove the screws holding the fan motor  
bracket to the compressor mounting base (see  
illustration 1).  
STEP 3:  
Remove the blade from the motor shaft by  
removing the nut (see illustration 2).  
NOTE: Install the concave side of the fan blade  
toward the motor.  
NOTE: If the blade is all that is being replaced,  
stop here and reverse procedure to install.  
STEP 4:  
STEP 5:  
Remove the mounting bracket from the motor  
(see illustration 3).  
Illustration 01  
Disconnect the lead wires at the compressor  
junction box.  
STEP 6:  
STEP 7:  
STEP 8:  
Reverse the procedure to install.  
Reconnect power to the unit.  
Reset the microprocessor control defrost time  
settings to the correct time of day.  
\
Illustration 02  
Illustration 03  
-6-  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IV. b - REPLACING THE CONDENSER COIL  
STEP 1:  
STEP 2:  
Remove the louver assembly as outlined in  
section III. a.  
WARNINGS:  
1) DISCONNECT THE ELECTRICAL POWER TO THE  
MACHINE AND FOLLOW LOCKOUT/TAGOUT  
PROCEDURES.  
Recover the refrigerant in the system  
following the current EPA Guidelines for  
refrigerant recovery.  
2) THIS PROCEDURE REQUIRES THE USE OF REFRIG-  
ERANTS. BE CERTAIN THE WORK AREA IS WELL  
VENTILATED. SAFETY GOGGLES AND GLOVES  
SHALL BE WORN SINCE REFRIGERANTS MAY CAUSE  
BURNS TO THE SKIN.  
NOTE: The use of reclaiming equipment is  
required.  
STEP 3:  
STEP 4:  
Disconnect the input and output lines to the  
condenser coil at the soldered joints closest  
to the condenser.  
Remove the four (4) screws which secure the  
condenser coil to the mounting brackets (see  
illustration 1).  
STEP 5:  
STEP 6:  
Remove the condenser coil.  
Reverse the procedure to install the new  
condenser coil.  
STEP 7:  
STEP 8:  
Install a new drier.  
Charge the refrigeration system as outlined  
under CHARGING SYSTEMin SERVICE  
PROCEDUES AND ADJUSTMENTS.”  
Illustration 01  
STEP 9:  
Reconnect power to the unit.  
STEP 10: Reset the microprocessor control defrost time  
settings to the correct time of the day.  
-7-  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IV. c - REPLACING THE EVAPORATOR FAN  
STEP 1:  
Begin by removing the back cover by first  
removing the four screws which secure this to  
the cabinet (see illustration 1).  
WARNINGS:  
1) DISCONNECT THE ELECTRICAL POWER TO THE  
MACHINE AND FOLLOW LOCKOUT/TAGOUT  
PROCEDURES.  
All evaporators and fans are located along the  
back wall of the cabinet and best accessed  
from the rear (see illustration 2).  
STEP 2:  
Remove the holding rod and unhook the rod  
from the other end. This evaporator fan can  
then be lifted away from the assembly (see  
illustration 3).  
STEP 3:  
STEP 4:  
Disconnect the wires from the assembly.  
Reverse the procedure to install the new  
evaporator fan.  
STEP 5:  
STEP 6:  
Reconnect power to the unit.  
Illustration 01  
Reset the microprocessor control defrost time  
settings to the correct time of the day.  
Illustration 02  
Illustration 03  
-8-  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IV. d - REPLACING THE EVAPORATOR COIL  
STEP 1:  
STEP 2:  
Remove evaporator housing cover as outlined  
in section III. b.  
WARNINGS:  
1) DISCONNECT THE ELECTRICAL POWER TO THE  
MACHINE AND FOLLOW LOCKOUT/TAGOUT  
PROCEDURES.  
Recover the refrigerant in the system  
following the current EPA Guidelines for  
refrigerant recovery.  
2) THIS PROCEDURE REQUIRES THE USE OF REFRIG-  
ERANTS. BE CERTAIN THE WORK AREA IS WELL  
VENTILATED. SAFETY GOGGLES AND GLOVES  
SHALL BE WORN SINCE REFRIGERANTS MAY CAUSE  
BURNS TO THE SKIN.  
NOTE: The use of reclaiming equipment is  
required.  
STEP 3:  
Remove the screws which secure the  
evaporator to the mounting brackets.  
STEP 4:  
STEP 5:  
Disconnect the evaporator output line.  
Unsolder the liquid line leading into the  
capillary tube.  
NOTE:  
NOTE:  
When removing the capillary tube care must  
be taken toheat protect. Heat sink or wrap a  
cold, dampcloth over the capillary tube to  
protect it from overheating.  
Inspect the end of the liquid line after  
disassembly, it could become plugged with  
solder.  
STEP 6:  
STEP 7:  
Remove the evaporator coil and capillary tube  
from the unit.  
Reverse the procedure to install the new  
evaporator coil and capillary tube.  
STEP 8:  
STEP 9:  
Install a new drier.  
Charge the refrigeration system as outlined  
under CHARGING SYSTEMin SERVICE  
PROCEDUES AND ADJUSTMENTS.”  
STEP 10: Reconnect power to the unit.  
STEP 11: Reset the microprocessor control defrost time  
settings to the correct time of day.  
-9-  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IV. e - REPLACING THE COMPRESSOR  
NOTE: Compressor models will vary with each cabinet  
model, but the basic removal instructions can be followed.  
WARNINGS:  
1) DISCONNECT THE ELECTRICAL POWER TO THE  
MACHINE AND FOLLOW LOCKOUT/TAGOUT  
PROCEDURES.  
STEP 1:  
Recover the refrigerant in the system  
following the current EPA Guidelines for  
refrigerant recovery.  
2) THIS PROCEDURE REQUIRES THE USE OF REFRIG-  
ERANTS. BE CERTAIN THE WORK AREA IS WELL  
VENTILATED. SAFETY GOGGLES AND GLOVES  
SHALL BE WORN SINCE REFRIGERANTS MAY CAUSE  
BURNS TO THE SKIN.  
NOTE:  
The use of reclaiming equipment is required.  
Remove the compressor junction box cover.  
STEP 2:  
STEP 3:  
Disconnect all wire leads coming into the  
junction box.  
STEP 4:  
STEP 5:  
STEP 6:  
Disconnect the discharge and suction lines to  
the compressor (see illustration 1).  
Remove the compressor which is secured by  
either four (4) nuts or pins.  
Install the new compressor and connect the  
input and output lines.  
STEP 7:  
STEP 8:  
STEP 9:  
Connect the lead wires at the junction box.  
Install a new drier.  
Illustration 01  
Charge the refrigeration system as outlined  
under CHARGING SYSTEMin SERVICE  
PROCEDUES AND ADJUSTMENTS.”  
STEP 10: Reconnect power to the unit.  
STEP 11: Reset the microprocessor control defrost time  
settings to the correct time of day.  
-10-  
Download from Www.Somanuals.com. All Manuals Search And Download.  
V. WIRING DIAGRAM  
-11-  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VI. SERVICE PROCEDURES & ADJUSTMENTS  
WARNING: CERTAIN PROCEDURES IN THIS SECTION REQUIRE ELECTRICAL TEST OR MEASUREMENTS WHILE  
POWER IS APPLIED TO THE MACHINE. EXERCISE EXTREME CAUTION AT ALL TIMES. IF TEST POINTS ARE  
NOT EASILYACCESSIBLE, DISCONNECT POWER, ATTACH TEST EQUIPMENT AND REAPPLY POWER TO TEST.  
VI. a - SYSTEM ACCESS:  
VI. c - REFRIGERANT LEAK CHECK (contd):  
NOTE: The use of a nitrogen requlator is required.  
All external indicators should be checked as part of  
system diagnosis before determining the  
refrigerant pressures. Improper access may expose  
the refrigerant to contaminates and non-condensables  
which will result in system failure.  
7) Set output valve on nitrogen valve to 120 psi.  
8) Open nitrogen bottle valve and low side gauge  
manifold valve. Allow pressure to equalize.  
9) Shut off both valves and disconnect nitrogen bottle.  
VI. b - SWEAT-ON PIERCING VALVES:  
10) Use a leak detector or a thick soapy solution and  
check for leaks at all tubing connections.  
NOTE: Sweat-on piercing valves are used for system  
diagnostics, but may be left on after service is  
complete. They may be installed while the system is  
fully charged.  
A - If leaks are found, repair leaks and repeat process.  
B - If no leaks are found, evacuate system as outlined  
in section V. d - EVACUATING SYSTEM).  
1) Place one piercing valve on the compressor  
process tube and one on the liquid line process tube.  
Follow the installation instructions provided by the  
manufacturer of the piercing valve.  
11) Charge the system by weighing in the exact charge  
and check for proper operation.  
2) When complete, follow the guidelines as outlined  
under LEAK CHECKand EVACUATING SYSTEM.”  
VI. d - EVACUATING SYSTEM:  
Introduction - Refrigeration reclaiming equipment is  
required. Our goal in system evacuation is to remove  
all the non-condensables possible. No evacuation  
method will remove 100% of the moisture and air from  
within the refrigeration circuit. Because of this,  
guidelines and methods must be developed and  
adhered to ensuring only harmless amounts of  
contaminants remain in the system.  
VI. c - REFRIGERANT LEAK CHECK:  
DISCONNECT THE ELECTRICAL POWER TO THE  
MACHINE AT THE MAIN CIRCUIT BOX. PLACE A TAG  
ON THE CIRCUIT BOX INDICATING THE CIRCUIT IS  
BEING SERVICED.  
THIS PROCEDURE REQUIRES THE USE OF  
REFRIGERANTS. BE CERTAIN THE WORK AREA IS  
WELL VENTILATED. SAFETY GOGGLES AND  
GLOVES SHALL BE WORN SINCE REFRIGERANTS  
MAY CAUSE BURNS TO THE SKIN.  
GUIDELINES  
WARNING - DO NOT PRESSURIZE SYSTEM ABOVE  
150 PSIG. PRIOR TO EVACUATION OR DURING LEAK  
TEST PROCEDURES.  
Use only a two stage vacuum pump (2 CFM or  
greater) and electronic micron.  
NOTE: The use of R-22 in small quantities is  
recommended as a trace gas for leak detection.  
Evacuate from high and low sides of the system.  
No chemical additive or alcohols are to be used to  
dry upa system.  
NOTE: This leak check procedure is to be used only  
after the refrigerant has been properly reclaimed.  
Blow down of system with DRY NITROGEN prior to  
evacuation is acceptable and many times desirable.  
See System Clean-Up.”  
1) Access the refrigeration system (note: see section  
V. a - SYSTEM ACCESS).  
2) Attach gauge manifold set to the system, low side  
to process tube on the compressor and the high side  
to the process tube.  
Evacuate to 200 microns.  
PROCEDURE  
3) Connect refrigerant bottle to the center of gauge  
manifold and open the valve on the bottle. Bleed  
charging hose at the manifold gauge to remove air from  
the system.  
WARNING: DISCONNECT THE ELECTRICAL POWER  
TO THE MACHINE AT THE MAIN CIRCUIT BOX. PLACE  
A TAG ON THE CIRCUIT BOX INDICATING THE  
CIRCUIT IS BEING SERVICED.  
4) Open valve on low side of gauge manifold and  
charge system with one ounce of R-22.  
WARNING: THIS PROCEDURE REQUIRES THE USE OF  
REFRIGERANTS. BE CERTAIN THE WORK AREA IS  
WELL VENTILATED. SAFETY GOGGLES AND  
GLOVES SHALL BE WORN SINCE REFRIGERANTS  
MAY CAUSE BURNS TO THE SKIN.  
5) Close low side valve on gauge manifold and the  
valve on the refrigerant bottle.  
6) Disconnect refrigerant bottle and connect nitrogen  
bottle.  
-12-  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VI. SERVICE PROCEDURES & ADJUSTMENTS (contd)  
WARNING: CERTAIN PROCEDURES IN THIS SECTION REQUIRE ELECTRICAL TEST OR MEASUREMENTS WHILE  
POWER IS APPLIED TO THE MACHINE. EXERCISE EXTREME CAUTION AT ALL TIMES. IF TEST POINTS ARE  
NOT EASILYACCESSIBLE, DISCONNECT POWER, ATTACH TEST EQUIPMENT AND REAPPLY POWER TO TEST.  
VI. d - EVACUATING SYSTEM/GUIDELINES (contd):  
1) Access the refrigeration system as outlined under  
SYSTEM ACCESS.”  
VI. e - CHARGING SYSTEM (contd):  
7) Add the remaining amount of refrigeration charge  
through the low side with the compressor running.  
2) Connect low (blue) side of gauge manifold to  
schrader valve on compressor process line and high  
(red) side of gauge manifold to schrader valve on  
filter/drier process line.  
8) Check for proper operation and leaks.  
9) Disconnect power to the unit and replace any  
covers removed.  
3) Connect center line of gauge manifold to vacuum  
pump.  
VI. f - SYSTEM CLEAN UP/INTRODUCTION:  
When a compressor burn-out or moisture infiltration  
is encountered, the service person must make the  
determination as to the degree of system contamina-  
tion. Normally a compressor burn-out will fit into one  
of three catagories:  
4) Turn vacuum pump on and open both sides of gauge  
manifold.  
5) Pull a vacuum to 200 microns.  
6) Break the vacuum with 3 psig of dry nitrogen.  
7) Repeat steps 5 and 6.  
CONTAINED - compressor oil not acidic, no oil dis  
coloration.  
8) Pull vacuum to 200 microns.  
CONTAMINATED COMPRESSOR - oil acidic,  
discoloration of oil, contamination limited to  
compressor.  
MASSIVE CONTAMINATION - contaminated oil  
and/or refrigerant pumped through system.  
9) Charge system and check for proper operation.  
VI. e - CHARGING SYSTEM:  
WARNING: DISCONNECT THE ELECTRICAL POWER  
TO THE MACHINEAT THE MAIN CIRCUIT BOX. PLACE  
A TAG ON THE CIRCUIT BOX INDICATING THE  
CIRCUIT IS BEING SERVICED.  
CONTAINED  
1) Replacement of liquid line drier.  
2) Install suction filter drier for clean up and then  
remove it when service is complete. Usually within  
48-hours.  
WARNING: THIS PROCEDURE REQUIRES THE USE OF  
REFRIGERANTS. BE CERTAIN THE WORK AREA IS  
WELL VENTILATED. SAFETY GOGGLES AND  
GLOVES SHALL BE WORN SINCE REFRIGERANTS  
MAY CAUSE BURNS TO THE SKIN.  
3) Replacement of compressor.  
4) Evacuation (to 200 microns).  
5) Charge by weight.  
1) Access the refrigeration system.  
2) Attach gauge manifold set to system, low side to  
process tube on the compressor and the high side to  
the process tube on the drier.  
CONTAMINATED COMPRESSOR  
The contaminated compressorrequires the same  
procedure as the containedburn-out. Plus, the  
system must be flushed with nitrogen after the  
compressor and drier has been removed.  
NOTE: See SYSTEM ACCESS.”  
3) Be sure the system is properly leak checked and  
evacuated before charging as outlined under LEAK  
CHECKand EVACUATING SYSTEM.”  
4) Make certain both valves are closed on the gauge  
manifold. Open the valve on the bottle. Bleed  
charging hose at the manifold gauge to remove air.  
NOTE: Initially charge system through high side to  
prevent liquid refrigerant from reaching compressor.  
5) Open the high side gauge valve (red). Allow  
refrigerant to flow into the system until the nameplate  
charge is reached or until the high side will not accept  
any more refrigerant. At this point, shut the gauge  
and bottle valves.  
6) Reconnect power to the unit and check for proper  
operation and high pressure leaks.  
-13-  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VI. SERVICE PROCEDURES & ADJUSTMENTS (contd)  
WARNING: CERTAIN PROCEDURES IN THIS SECTION REQUIRE ELECTRICAL TEST OR MEASUREMENTS WHILE  
POWER IS APPLIED TO THE MACHINE. EXERCISE EXTREME CAUTION AT ALL TIMES. IF TEST POINTS ARE  
NOT EASILYACCESSIBLE, DISCONNECT POWER, ATTACH TEST EQUIPMENT AND REAPPLY POWER TO TEST.  
VI. f - SYSTEM CLEAN UP/INTRODUCTION (contd):  
MASSIVE CONTAMINATION (contd):  
10) Return between 24 and 48 hours to recover gas,  
replace liquid line drier with a CW style drier. Remove  
the suction drier, but do not replace.  
MASSIVE CONTAMINATION  
The replacement compressor MUST NOT be installed  
until after system clean-up procedures have been  
completed.  
11) Evacuate and charge system as outlined under  
EVACUATING SYSTEMand CHARGING SYSTEM .  
1) Remove the burned-out compressor as outlined  
under COMPRESSORin Section IV. f.  
VI. g - HEATER TEST - DRAWER PERIMETER HEATER:  
1) Access the heater wire around the drawer frame.  
2) Remove the capillary tube metering device.  
2) Plug the unit in and verify 120 volt supply to the  
heater.  
3) Purge nitrogen through the high and low sides of  
system until moisture and contaminated oil has been  
removed from the remaining components of the  
system.  
3) The reading should be .25 amp.  
4) Reassemble refrigeration system and add a CW style  
liquid drier and a suction line drier.  
5) Purge nitrogen through the high and low sides of  
system for 5 minutes.  
6) Evacuate refrigeration as outlined under  
EVACUATING SYSTEMfor 30 minutes. Repeat  
nitrogen purge and evacuate two more times.  
7) Charge system as outlined under CHARGING  
SYSTEM. Allow for the increased liquid capacity of  
the liquid line drier.  
8) Reconnect power and check for proper operation.  
9) Disconnect power and install any panels removed.  
VII. ELECTRICAL OPERATION  
VII. a - NORMAL OPERATION:  
1. Conditions  
a) Unit connected to correct voltage (check using a  
volt meter).  
VII. b - DEFROST MODE:  
1. Conditions  
a) Unit operating in normal mode.  
b) Microprocessor off cycle defrost settings correct.  
c) Condensing unit controlled by the microprocessor  
control.  
2. Defrost initiated by the microprocessor control (an  
off-cycle defrost should occur every 60-minutes).  
d) Cabinet at desired temperature.  
e) Door perimeter heaters are powered 100% of the  
time as preset by the factory (this can be adjusted  
using the microprocessor control).  
f) Evaporator fan powered.  
3. Defrost terminated by either: 1) Evaporator Coil  
Temperature or 2) Maximum Set Time Interval.  
4. Cabinet returns to normal operation.  
a) Temperature controlled by the microprocessor  
control.  
g) Microprocessor control operating correctly.  
b) Evaporator fan stays ON, evaporator coil will reach  
desired temperature.  
2. Cabinet temperature rises above set temperature.  
a) Microprocessor control initiates compressor  
operation.  
b) Evaporator fan should be ON all the time.  
3. Set temperature is met.  
a) Conditions return to those outlined in step 1.  
-14-  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VII. ELECTRICAL OPERATION  
VII. c - COMPONENT FUNCTION:  
Compressor:  
Pumps refrigerant thru refrigeration system components and  
compresses the low pressure vapor into high pressure vapor.  
Condenser Fan:  
Draws air across condenser coil to aid in removing heat from the  
refrigerant andmoves air across compressor to aid in cooling the  
compressor.  
Evaporator Fan:  
Draws air from the cabinet and pulls the air thru the evaporator coil.  
Stores electrical charge which helps start the compressor motor.  
Helps keep the compressor motor running after starting.  
Start Capacitor:  
Run Capacitor:  
Microprocessor Control:  
Performs the functions of the 1) defrost timer, 2) high limit switch,  
3) thermometer and 4) thermostat.  
Drawer Perimeter Heater:  
Contactor Relay:  
Heats drawer opening to prevent condensation from forming.  
Controls voltage to compressor motors.  
VII. d - INSTALLATION OF THE SENSORS:  
There are two sensors used inside the  
cabinet. The first one is the Cabinet Sensor  
that is used to cycle the compressor on and  
off at the correct temperature. The cabinet  
sensor is mounted between the two coils  
just below the top of the cabinet thru the  
1/2” holes in the back wall and the tip should  
be 1” inside the cabinet. Refer to the  
drawing below. The part number for the  
Cabinet Sensor is 337-60405-03.  
The third sensor used is a Liquid Line  
Sensor. This sensor is to be installed on  
the liquid line as it comes out of the  
condenser coil. The part number for this  
sensor is 337-60407-01.  
Insert sensor inside the cabinet thru  
1/2” holes in back wall  
1” inside cabinet  
Attach sensor to the  
liquid line using the  
wrap  
The Evaporator Coil Sensor is to be mounted  
in the evaporator, in the center of the coil  
and fully inserted into the coil until only the  
wire is visible and then pinch the fins around  
the cable to hold it in place. The part  
number for the Evaporator Coil Sensor is  
When the condensing temperature reaches  
140°F or greater the control will display  
“CLN-FIL.” Should the condensing  
temperature increase to 160°F the  
compressor will automatically shut off.  
When the liquid line temperature drops  
below 140°F the compressor will restart and  
when the line temperature drops to 120°F  
the alarm will reset.  
337-60406-03.  
Fully insert probe  
into coil  
.756 between 1st  
and 2nd hair bend  
Center  
of Coil  
-15-  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VIII. REPLACEMENT PARTS LISTING  
NOTE: Part numbers listed are for standard products as currently manufactured. For products manufactured  
as other than standard, or for older production units, please contact the factory.  
PART NO.  
NAME OF PART  
PART NO.  
NAME OF PART  
CABINET SUPPORTS  
COMPRESSORS  
SER-60536-00  
SER-60536-01  
4” High Caster w/o Lock  
4” High Caster with Lock  
321-60225-00  
321-60226-00  
For Models TE036HT thru TE084HT  
For Models TE096HT thru TE139HT  
DRAWER PARTS  
(models TE036HT & TE065HT)  
MISC. SYSTEM COMPONENTS  
Suction Heat Exchange Evap 9” Coil  
Suction Heat Exchange Evap 18” Coil  
Evaporator Coil 9”  
323-60088-00  
350-10000-00  
322-60048-00  
322-60050-01  
325-60103-00  
325-60144-00  
325-60145-00  
325-60135-00  
338-60050-00  
701-61119-00  
701-61119-01  
337-60360-01  
550-10053-00  
Drawer Assembly  
Drawer Face  
Drawer Frame  
Drawer Frame Insert  
Drawer Gasket  
Drawer Roller  
550-10057-00  
550-10059-00  
SER-60537-00  
341-60176-02  
344-60155-00  
Evaporator Coil 18”  
Liquid Line Drier  
Condenser Fan Motor Assembly  
Evaporator Fan Motor Assembly  
Condenser Fan Blade  
DRAWER PARTS  
(all models except TE036HT, TE060HT, TE065HT, TE125HT &  
Condenser Fan Motor  
Spring Rod 9” Evaporator Coil  
Spring Rod 18” Evaporator Coil  
Compressor Relay  
TE072HT)  
550-10054-00  
550-10058-00  
550-10060-00  
SER-60537-01  
341-60176-03  
344-60155-00  
Drawer Assembly  
Drawer Face  
Drawer Frame  
Drawer Frame Insert  
Drawer Gasket  
Drawer Roller  
MISC. CABINET PARTS  
ON/OFF Power Switch  
Marine Top for TE036HT  
Marine Top for TE048HT  
Marine Top for TE060HT  
Marine Top for TE065HT  
Marine Top for TE072HT  
Marine Top for TE084HT  
Marine Top for TE096HT  
Marine Top for TE110HT  
Marine Top for TE125HT  
Marine Top for TE139HT  
337-60346-00  
509-50118-00  
509-50118-01  
509-50118-02  
509-50118-03  
509-50118-04  
509-50118-05  
509-50118-06  
509-50118-07  
509-50118-08  
509-50118-09  
DRAWER PARTS  
(models TE060HT & TE125HT)  
550-10067-00  
Drawer Assembly  
Drawer Face  
Drawer Frame  
Drawer Frame Insert  
Drawer Gasket  
Drawer Roller  
550-10076-00  
550-10077-00  
SER-60537-03  
341-60176-04  
344-60155-00  
LOUVER PANELS  
For System on Left  
For System on Right  
DRAWER PARTS  
(model TE072HT only)  
500-70075-00  
500-70075-01  
550-10074-00  
550-10069-00  
550-10070-00  
SER-60537-02  
341-60176-01  
344-60155-00  
Drawer Assembly  
Drawer Face  
Drawer Frame  
Drawer Frame Insert  
Drawer Gasket  
Drawer Roller  
CONTROL PARTS  
Control Head  
Cabinet Temp Sensor  
Coil Temp Sensor  
Liquid Line Sensor  
Relay Module  
337-60403-00  
337-60405-03  
337-60406-03  
337-60407-01  
337-60317-00  
-16-  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IX. TROUBLESHOOTING  
WARNING: CERTAIN PROCEDURES IN THIS SECTION REQUIRE ELECTRICAL AND REFRIGERA-  
TION SYSTEM TEST OR MEASUREMENTS WHILE POWER IS APPLIED TO THE MACHINE. EXER-  
CISE EXTREME CAUTION AT ALL TIMES. IF TEST POINTS ARE NOT EASILY ACCESSIBLE, DISCON-  
NECT POWER, ATTACH TEST EQUIPMENT AND REAPPLY POWER TO TEST.  
Compressor will not run, compressor has no current draw.  
1. Main circuit breaker open.  
2. Compressor overload tripped.  
3. Cabinet temperature satisfied.  
4. Wired wrong or faulty connection.  
5. INTELA-TRAUL® control malfunction1.  
6. Start component malfunction.  
7. Compressor motor windings open.  
Compressor will not run, current draw and trips overload.  
Compressor short cycles on overload.  
1. Low voltage.  
2. Start component malfunction.  
3. Compressor windings shorted.  
4. Locked rotor.  
5. Excessive discharge pressure.  
1. Low voltage.  
2. Low refrigerant charge.  
3. Dirty condenser coil and/or filter.  
4. Wired wrong or faulty connection.  
5. Condenser fan inoperative.  
6. Run capacitor malfunction.  
7. Start component malfunction.  
8. INTELA-TRAUL® control malfunction1.  
9. High head pressure.  
Compressor short cycles.  
Continuous unit operation.  
1. Improper air flow over evaporator coil.  
2. Low ambient conditions.  
3. INTELA-TRAUL® control malfunction1.  
4. Bad sensors.  
5. Temp differential set too close.  
1. Loss of refrigerant.  
2. Excessive drawer openings.  
3. INTELA-TRAUL® control malfunction1.  
4. Broken compressor valves.  
5. Very dirty condenser and/or filter.  
6. Check the “DL,” if higher than 160F  
Compressor run time lengthy.  
1. Partial loss of refrigerant.  
2. High ambient conditions.  
3. Dirty condenser coil or improper air flow over  
condenser coil.  
4. Excessive product load.  
5. Excessive drawer openings.  
6. Drawer gasket requires replacement.  
7. INTELA-TRAUL® control malfunction1.  
8. Contaminates in refrigeration system.  
9. Compressor valve leakage.  
10. Inadequate defrost cycle.  
Low suction pressure.  
High head pressure.  
1. Capillary tube restricted.  
2. Drier plugged.  
3. Loss of refrigerant.  
4. Poor air flow.  
5. Iced evaporator coil.  
1. Improper air flow across condenser.  
2. High ambient conditions.  
3. Overcharge of refrigerant.  
4. Air in system.  
5. Dirty condenser coil.  
Will not defrost or inadequate defrost.  
1. Defrost heater malfunction.  
2. Wired wrong or faulty connection.  
3. Cabinet air leak.  
4. Coil sensor failure.  
5. INTELA-TRAUL® control malfunction1.  
Coil icing.  
1. Number of defrost cycles too few.  
2. Defrost duration too short.  
3. Cabinet air leak.  
4. Drain tube plugged.  
5. Defrost heater not working.  
6. Non-frozen product put into cabinet.  
7. Coil sensor failure.  
The cabinet & coil sensors show high temperature.  
1. Sensor needs rreplacing (place sensor tip and  
thermometer in ice water. Change sensor ir readings  
differ, or if sensor displays -40 02 266).  
-17-  
Download from Www.Somanuals.com. All Manuals Search And Download.  
-18-  
Download from Www.Somanuals.com. All Manuals Search And Download.  
For More Information On The Proper Installation, Use and Maintenance Of Traulsen  
Refrigerated Equipment Stand Models, Please Refer To The Following Materials Available From  
Your Local Hobart/Traulsen Sales & Service Location:  
INTELA-TRAUL Master Service Manual - Form Number TR35705  
For Questions Regarding Repair or Warranty Service, Please Contact Traulsen Service At:  
(800) 825-8220, ext. 6509  
HOURS OF OPERATION:  
Monday thru Friday 7:30 am - 4:30 pm CST  
Traulsen  
4401 Blue Mound Road Fort Worth, TX 76106  
Phone: (800) 825-8220 Fax-Svce: (817) 740-6757  
Quality Refrigeration  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Tesla Power Supply TI2000GPU 24 User Manual
Texas Instruments Switch HPL D SLLU064A User Manual
Toastmaster Toaster RH4T9379 User Manual
Toshiba Security Camera IK TU51CU User Manual
Toshiba TV DVD Combo MD24FP1 User Manual
Vector Video Games VEC401 User Manual
Vermont Casting Outdoor Fireplace RAD VTBB User Manual
Vestax Musical Instrument CDX 16 User Manual
Vinotemp Refrigerator VT 34 2Z User Manual
Visonik Carbon Monoxide Alarm MCT 441 User Manual