Trane Video Game Controller Tracer User Manual

WSHP-IOP-2  
May 1998  
Installation, Operation,  
and Programming  
Tracer™ ZN510 Controller  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Start-up Procedure  
Power-up Sequence  
Unit Identification Tag  
4
5
6
Unit Operation  
General Information  
Communication  
Power  
7
7
7
8
Binary Outputs  
Analog Outputs  
Binary Inputs  
8
9
9
Analog Inputs  
12  
Zone Sensors  
15  
Heating or Cooling Control  
Mode Operation  
Single or Dual Compressor  
Operation  
18  
19  
Data Sharing  
Configuration  
20  
21  
22  
27  
28  
29  
31  
33  
Troubleshooting  
Diagnostics  
ZN510 Controller Replacement  
Wiring Diagram  
Hardware Specifications  
Appendix  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start-up  
Procedure  
Installation of New Units  
1. Follow all instruction for  
installation of water source  
heat pumps as detailed in the  
IOM (Installation Operation  
Maintenance manual).  
5. Verify that water connections  
have been made to unit, then  
ensure that water is circulating  
through the unit.  
6. Reapply power.  
2. Disconnect power or disable  
7. Check for STATUS GREEN LED  
operation to ensure power and  
communication has been made  
the circuit breaker to unit.  
3. Run communication link wire to  
field terminal strips 14 and 16.  
(See wiring diagram in the  
unit).  
to the ZN510 .  
Peel IDENTIFICATION TAG from unit  
and place in the ZN510 IOP, on a  
copy of Sheet 6 of this document, or  
on building plans for future location  
use. The actual room location on the  
tag may be hand written.  
4. Install zone sensor to low  
voltage control terminals 1  
through 6. (See wiring diagram  
in the unit and zone sensor  
submittals).  
Zone Sensor Placement  
Zone sensor location is an important  
element of effective room control  
and comfort.  
The following are typical areas  
where the zone sensor should not  
be mounted:  
z Near drafts or “dead spots”  
The best sensor location is typically  
on a wall, remote from the HVAC unit.  
Readings at this location assure that  
the desired setpoint is achieved  
across the space, not just near the  
unit itself. It may be necessary to  
subdivide the zone with multiple  
units to ensure adequate control  
and comfort.  
(e.g., behind doors or corners)  
z Near hot or cold air ducts  
z Near radiant heat (e.g., heat  
emitted from appliances or the  
sun)  
z Near concealed pipes or  
chimneys  
z On outside walls or other non-  
conditioned surfaces  
z In air flows from adjacent zones  
or other units  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Power Up  
Sequence  
Power Up Sequence  
3. A random start time is hard  
coded on every board and  
cannot be disabled. The board  
generates a random time delay  
between 0 and 25 seconds.  
Once this time expires, the  
power up control wait time (if  
configured) will wait for 120  
seconds. The power up control  
wait allows ample time for a  
communicated request to  
arrive. If the power up control  
wait time expires, and the  
controller does not receive a  
communicated occupancy  
command, the unit assumes  
stand alone operation.  
When 24 VAC power initially is  
applied to the ZN510 controller, the  
following sequence occurs:  
1. All outputs are controlled off.  
2. The controller reads all inputs  
to determine their initial values.  
Note: Because the space tempera-  
ture can be hardwired to the con-  
troller or communicated, the  
controller waits for several minutes  
to check for the presence of a com-  
municated value.  
4. Normal operation begins.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unit  
Identification  
Tag  
Unit Identification Tag  
The unit identification tag is factory  
mounted and provided for easy  
identification of an installed unit. It  
contains model number, tagging,  
and location information. See  
Figure 1.  
The top portion of the unit  
identification tag remains  
permanently affixed to the unit for  
identity purposes. The bottom  
portion of the tag provides pertinent  
information that is removable to be  
placed on building plans or in the  
ZN510 IOP on page 33. This provides  
identification history about the unit’s  
location for quick reference.  
These tags provide information  
about unit location, unit serial  
number, and NID (neuron  
identification number). The NID is  
similar to the serial number of the  
unit but is specific to the  
identification of the ZN510 Board.  
The location identification is a  
customer defined, clear English  
description, of the unit’s physical  
location. This is a 27 character  
description of the location. For  
example, if the location identification  
for a unit is “Conference Room 101”,  
the ZN510 and Rover (the Trane  
Comm 5 service tool) will recognize  
this clear English description so  
maintenance can be performed on  
the appropriate unit. If location  
identification is not defined, it will  
default to the unit serial number. This  
provides some information so the  
user has multiple references to the  
unit. The blank location is provided  
for field modification in case the unit  
is moved from the initial location.  
Figure 1: Unit Identification Tag  
Note: Fold and tear carefully along dashed  
removable line.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unit Operation  
General Information  
The ZN510 controller is a  
z Console water source heat  
z Up to two compressors.  
pumps.  
z Reversing valve.  
microprocessor-based direct digital  
controller that controls a variety of  
water source heat pump equipment  
including:  
z Standard efficiency horizontal  
and vertical units up to 10 tons.  
ZN510 is designed to provide  
accurate and reliable zone  
temperature control by using  
custom proportional integral (PI)  
algorithms. The controller is factory  
installed and configured to support:  
z 2-position outdoor air damper  
or generic binary output.  
Peer-to-peer communication across  
controllers is possible even when a  
building automation system is not  
present. ZN510 is also adaptable as  
a standalone system.  
z High efficiency horizontal and  
z Single fan speed.  
vertical units.  
Figure 2: Communication connections  
Communication  
are provided for direct con-  
nection of Rover to the ZN510  
Board or provided as spare ter-  
minals.  
z Two terminals (TB2-5, TB2-6)  
are connected to the field  
terminal strip (1TB1-5, 1TB1-6)  
which should be connected to  
the zone sensor communication  
jack. This provides direct  
The ZN510 controller communicates  
via Trane’s Comm5 protocol.  
Typically, a communication link is  
applied between unit controllers and  
a building automation system.  
Communication is also possible  
z Two terminals (TB2-3, TB2-4)  
are connected to the field  
terminal strip (1TB1-14,  
1TB1-16) for connection to the  
communication link (daisy  
chain).  
connect of Rover to the commu-  
nication link without having to  
connect directly to the ZN510  
board or provided as spare ter-  
minals.  
with Trane’s service tool Rover .  
ZN510 provides a total of six 1/4-inch  
quick-connect terminals for  
connection to the Comm5  
communication link. These  
connections include:  
z The field terminal strip 1TB1  
provides screw terminations for  
all field connections.  
z Two terminals (TB2-1, TB2-2)  
COMM  
COMM  
COMM  
Space  
Communication  
Connection  
20 pole low voltage  
terminal strip screw  
connections for  
field hook-up  
Zone  
Sensor  
Communication  
Link  
Figure 3: Communication Wiring  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unit Operation  
Power  
Factory Supplied Transformer  
The ZN510 controller is powered by 24  
VAC. A total of two 1/4-inch quick-  
connect terminals are provided for 24  
VAC connection to the board. See  
Figure 4 for ZN510 power requirement.  
Line  
Voltage  
24VAC  
Note: Power for field installed ancil-  
lary devices is not available from the  
board. It must be tapped at trans-  
former. See Table 21 for excess power  
available.  
Figure 4: Power Connections  
Binary Outputs  
The ZN510 uses five of its binary  
outputs to control heat pump units.  
Outputs are load side switching triacs.  
The triac acts as a switch by either  
making or breaking the circuit  
between the load (reversing valve,  
damper, contactor, relay) and ground.  
Field installed  
2 position  
damper actuator  
24VAC  
1TB1-17  
See Figure 5 for the configuration of  
the five binary outputs.  
1TB1-18  
2-Position Damper Actuator or  
Generic Binary Output  
Binary output 6 (BOP 6) is factory  
configured to control a normally  
closed 2-position outdoor air damper.  
It may be field modified to control a  
generic output for control by a  
building automation system. If set up  
as a generic output, the controller  
does not use BOP 6 as part of the  
normal control. A building automation  
system must issue commands to  
control the generic binary output.  
Binary Outputs  
Figure 5: Binary outputs  
.
Note:  
Table 1: BOP 6 control of a 2-position outdoor air damper  
z During occupied mode, the  
outdoor air damper is closed  
when the fan is controlled off.  
Model  
Occupied  
Fan Operation  
Outdoor Air Damper  
On or cycling  
Open  
Off  
Closed  
Closed  
z During unoccupied mode, the  
outdoor air damper normally  
remains closed.  
Occupied warm up or  
cool down  
On or cycling  
Occupied standby  
Unoccupied  
On or cycling  
Cycling  
Closed  
Closed  
Closed  
z 2-position damper must not  
exceed 10 VA power output from  
board.  
Diagnostic present  
Diagnostic dependent  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unit Operation  
Output Overrides  
z Force compressor operation,  
allowing the technician to use  
refrigerant gauges or other test  
equipment to verify unit  
operation.  
manual output test. See  
The ZN510 controller includes a  
manual output test function. Use this  
feature to manually exercise the  
outputs in a defined sequence. The  
purpose of the test sequence, is to  
verify output and end device  
operation. Use the manual output  
test to:  
Troubleshooting section for Green  
LED and Testing Heat Pump  
Configurations on page 21 & 22.  
The test sequence resets unit  
diagnostics and attempts to restore  
normal unit operation prior to  
testing the outputs. If the diagnostics  
remains after a reset, the status LED  
indicates the diagnostic condition is  
still present and has affected the  
z Verify output wiring and  
operation without using Trane’s  
service tool, Rover.  
Analog Outputs  
ZN510 does not use analog outputs.  
Binary Inputs  
The ZN510 controller has three  
available binary inputs (BI). These  
inputs are factory-configured for  
the following functions:  
J2-1  
Low Temperature  
Detection (Circuit 2)  
J2-2  
z BI 1= Low temperature  
detection (freezestat) (Circuit 2).  
z BI 2 = Condensate overflow.  
J2-3  
Condensate Overflow  
J2-4  
z BI 3 = Occupancy or generic  
binary input.  
Each binary input may be  
configured as not used depending  
on options selected. BI 3 is  
J2-5  
configured as a normally open  
occupancy input, but may be field  
modified for generic binary input  
which is only supported by a build-  
ing automation system.  
Field Wired  
Occupancy Input  
J2-6  
Figure 6: Binary inputs.  
Note:  
The diagnostic functions related to  
binary inputs such as low tempera-  
ture detection and condensate  
overflow are fixed sequences.  
Table 2: Binary input configurations  
Configuratio  
n
Contact  
Closure  
Contact  
Open  
Binary Input  
Description  
Each binary input associates an  
input signal of 0 VAC with open  
contacts and 24 VAC with closed  
contacts. See Figure 6 for typical  
binary input configurations for the  
heat pump.  
Low Temperature  
Detection (Cir 2)  
Normally  
closed  
BI 1  
Normal  
Normal  
Diagnostic  
Diagnostic  
Normally  
closed  
BI 2  
Condensate Overflow  
Occupancy  
Generic  
Normally open Unoccupied  
Normally open Normal  
Occupied  
Normal  
BI 3  
Note:  
See Page 10 for specific information concerning BI 1, BI 2 and BI 3.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unit Operation  
Low Temperature Detection  
The low temperature detection  
diagnostic protects the heat  
temperature condition exists for that  
circuit.  
outdoor air damper also operates  
normally.  
exchanger by using an analog  
leaving water temperature sensor to  
protect refrigerant circuit 1 and a  
binary low temperature detection  
device to protect refrigerant circuit  
2. Each individual refrigerant circuit  
is disabled when the low  
For two compressor units, the  
controller responds to low  
All unit operation is disabled when  
the heat pump shuts down both  
circuits, due to low temperature  
conditions. See Table 3 for more  
information.  
temperature detection by allowing  
the fan to operate, while disabling  
the compressor for the faulty circuit.  
The compressor for the normal  
circuit continues to operate. The  
Table 3: ZN510 response to low temperature detection diagnostic  
Fan  
Operation  
Damper  
Operation  
Description  
Compressor Operation  
Low Temperature Detection  
(Circuit 1)  
Circuit 1-Disabled  
Circuit 2-Normal Operation operation  
Normal  
Enabled  
Low Temperature Detection  
(Circuit 2)  
Circuit 1-Normal Operation Normal  
Enabled  
Disabled  
Circuit 2-Disabled  
operation  
Closed  
Low Temperature Detection  
(Circuits 1 and 2)  
Circuit 1-Disabled  
Circuit 2-Disabled  
Note:  
z The low temperature detection device automatically resets when the heat exchanger temperature returns to  
normal. However, you must manually reset the low temperature detection diagnostic to clear the diagnostic and  
restart the unit. Refer to page 28 on how to reset a unit.  
z If BOP 6 is configured as a generic binary output, the state of the output is not affected by the low temperature  
detection diagnostic or by other diagnostics.  
Condensate Overflow  
Note:  
system), the occupancy binary input  
determines the unit’s occupancy  
based on the hardwired signal.  
Typically, the signal is a dry set of  
binary contacts which is either  
connected to a switch or timeclock  
contacts.  
A condensate overflow switch  
detects the condensate condition.  
The condensate overflow switch is a  
normally closed device. This switch  
is physically connected to the binary  
input 2 (BI 2). When the  
condensation reaches the trip point,  
the binary input detects the  
diagnostic condition. A condensate  
overflow signal generates a  
diagnostic which disables the fan,  
disables all compressors, and closes  
the 2-position outdoor air damper  
(when present). The condensate  
overflow diagnostic does not affect  
the generic binary output (when  
present).  
The condensate overflow switch,  
located in the condensate pan, auto-  
matically resets when the conden-  
sation returns to normal levels.  
However, you must manually reset  
the controllers condensate over-  
flow diagnostic to clear the diagnos-  
tic and restart the unit. Refer to page  
28 on how to reset a unit.  
When a hardwired occupancy signal  
is open, the unit switches to  
occupied mode (if the occupancy  
input is configured as normally  
open). When a hardwired  
occupancy signal is closed, the  
controller switches to Unoccupied  
mode.  
Occupancy  
ZN510 uses the occupancy binary  
input for two occupancy-related  
functions. For standalone  
controllers (any unit not receiving a  
communicated occupancy request,  
typically from a building automation  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unit Operation  
In Occupied mode, the controller  
operates according to the occupied  
setpoints. In Occupied Standby  
Mode, the unit controller operates  
according to the Occupied Standby  
setpoints. When the controller  
receives a communicated  
operates according to the  
unoccupied setpoints regardless of  
the state of the hardwired  
occupancy input.  
controller defaults to occupied  
mode because the occupancy binary  
input (if present) typically is  
configured as normally open  
without an occupancy device  
connected.  
If neither the binary input nor the  
communicated input is used to  
select the occupancy mode, the  
unoccupied request, the controller  
Table 4: Normally open hardwired input configuration (BI 3)  
Description  
Communicated Request  
NA  
Hardwired State  
Result  
Occupied  
Standalone  
Standalone  
Open = Occupied  
NA  
Closed = Unoccupied  
Open = Occupied  
Unoccupied  
Communicating  
Communicating  
Communicating  
Communicating  
Communicating  
Communicating  
Occupied  
Occupied  
Unoccupied  
Occupied Standby  
Occupied  
Open = Occupied  
Unoccupied  
Open = Occupied  
Occupied Standby  
Occupied Standby  
Unoccupied  
Closed = Occupied Standby  
Closed = Occupied Standby  
Closed = Occupied Standby  
Unoccupied  
Occupied Standby  
Occupied Standby  
Note:  
If configured for normally closed, all states are opposite of Table 4.  
Generic Binary Input  
compressor contactor from  
energizing keeping the compressor  
from running. The controller  
automatically detects the fault  
condition by measuring the  
compressor triac output signal.  
unit operation. See Figure 7 for high  
and low pressure switch.  
Building automation systems can  
monitor the status of the generic  
binary input. This input does not  
affect controller operation.  
When the refrigerant circuit returns  
to normal, the HPC and the LPC  
switches automatically reset. The  
high or low pressure cutout  
diagnostic may need to be manually  
reset to clear the diagnostic and  
enable compressor operation for the  
fault circuit.  
High and Low Pressure  
Switches  
By default, when the HPC or LPC  
switches detect a high or low  
pressure condition in the refrigerant  
circuit, the special input detects the  
diagnostic and disables all  
compressor operation for that  
circuit. The unit fan continues to  
operate, if only one circuit is  
disabled in a two compressor unit.  
When the HPC/LPC diagnostic is  
present on both circuits, the ZN510  
shuts off the unit fan and disables  
The high and low pressure cutout  
switches are wired in series with the  
compressor contactor in the unit.  
The ZN510 controller detects the  
state of each switch circuit by  
monitoring the controller’s  
compressor triac outputs. If either  
the high pressure switch (HPC) or  
the low pressure switch (LPC) switch  
opens, a fault condition occurs. This  
open circuit prevents the  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unit Operation  
24 VAC  
Compr 2  
Compr 1  
LPC  
HPC  
Binary Outputs  
Figure 7: High and low pressure switch  
Note:  
The ZN510 controller includes an automatic diag-  
nostic reset function that allows the controller to  
automatically recover after a high or low pres-  
sure cutout diagnostic. After 30 minutes the con-  
troller will reset the diagnostics. Most  
diagnostics occur due to intermittent water tem-  
perature or flow problem. The “smart reset” may  
eliminate many service calls.  
1
2
3
4
5
6
7
Analog Inputs  
The ZN510 controller has five  
available analog inputs (AI). These  
inputs are factory-configured for the  
following functions:  
z Zone = Space temperature.  
z Set = Local setpoint.  
J3-4  
J3-3  
Discharge Air  
Sensor  
z Fan = Fan mode input.  
z AI 1 = Leaving water tem-  
perature (Circuit 1).  
z AI 2 = Discharge air tem-  
J3-2  
J3-1  
perature.  
Leaving Water  
Sensor (Circuit)  
Zone Sensor  
See Figure 8 for analog inputs.  
Figure 8: Analog inputs.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unit Operation  
Space Temperature  
ZN510 controls the space  
temperature according to the active  
space temperature, the active  
heating/cooling setpoint, and the  
space temperature control  
pressed, the zone sensor sends a  
signal to the controller. This signal is  
then interpreted as a timed override  
cancel which places the unit into  
unoccupied.  
space temperature, the active  
setpoint, and the proportional/  
integral control algorithm,  
regardless of the presence of a  
hardwired or communicated  
setpoint.  
algorithm. The ZN510 controller  
receives the space temperature  
from either a wired zone sensor or  
as a communicated value. When  
neither a zone sensor nor  
communicatedspacetemperatureis  
present, the ZN510 controller  
generates a space temperature  
failure diagnostic.  
Local Setpoint  
Once a valid setpoint is established  
(through the hardwired input or  
through communication) and when  
neither a local setpoint or  
communicated setpoint is present,  
the controller generates a setpoint  
failure diagnostic.  
The local setpoint analog input is  
designed as the local (hardwired)  
setpoint input. This input cannot be  
used for any other function. The  
local input is a resistance input  
intended for use with Trane zone  
sensors.  
When a setpoint failure diagnostic  
occurs, the controller operates using  
the default heating and cooling  
setpoints. These setpoints are  
factory-configured, but may be  
changed using the Trane service  
tool, Rover.  
If neither a hardwired nor  
communicated setpoint is present,  
the controller uses the stored default  
setpoints:  
Note:  
The ZN510 controller cannot oper-  
ate without a valid space tempera-  
ture value (either hardwired or  
communicated).  
z Occupied setpoints:  
In the occupied mode, the unit  
attempts to maintain the space  
temperature at the active  
occupied heating or cooling  
setpoint based on the measured  
space temperature, the active  
setpoint, and the proportional/  
integral control algorithm.  
The space temperature input can  
communicate timed override ON or  
CANCEL requests to the ZN510  
controller. If the ON button is  
temporarily pressed, the zone  
sensor sends a signal to the  
controller. This signal is then  
interpreted as a timer override  
request which places the unit into  
occupied.  
The ZN510 controller uses the  
following validation sequence for  
the setpoints:  
1. Check for a communicated  
setpoint. If present, validate this  
setpoint.  
z Occupied standby setpoints:  
In occupied standby mode, the  
controller uses the occupied  
standby cooling and heating  
setpoints. Because the occupied  
standby setpoints typically  
cover a wider range than the  
occupied setpoints, the ZN510  
controller reduces the demand  
for heating and cooling the  
space. Also, the outdoor air  
damper is normally closed  
during occupied standby mode  
to further reduce the heating  
and cooling demands.  
2. Check for a hardwired setpoint  
and validate the setpoint.  
3. Use the default setpoint and  
The controller uses the timed  
override request (while the zone is  
unoccupied) as a request to switch  
to the Occupied Bypass mode  
(occupied bypass). This Occupied  
Bypass mode lasts for the duration  
of the occupied bypass time,  
typically 120 minutes.  
validate this setpoint.  
Fan Mode Input  
The fan mode analog input (Fan) is  
designed to operate as the fan mode  
switch input. This input cannot be  
used for any other function. The fan  
switch on a Trane zone sensor  
generates the fan mode signal.  
or  
The controller’s Occupancy mode is  
determined from either a system  
level controller or another peer  
controller.  
The ZN510 controller detects the  
unique resistance corresponding to  
each position of the fan switch. By  
measuring the resistance, the  
controller determines the requested  
fan mode.  
z Unoccupied setpoints:  
In unoccupied mode, the unit  
attempts to maintain the space  
temperature at the stored unoc-  
cupied heating or cooling  
The CANCEL button cancels the timed  
override request and returned the  
unit to unoccupied mode. If the  
CANCEL button is temporarily  
setpoint based on the measured  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unit Operation  
Leaving Water Temperature  
ZN510 uses analog input 1 (AI 1) as  
the leaving water temperature input  
for use with a thermistor. This input  
(AI 1) is automatically assigned as a  
leaving water temperature input. As  
explained in the binary input  
section, the leaving water  
temperature input protects the heat  
exchanger (circuit 1) from low  
temperatures. The second heat  
exchanger, present in units with two  
compressors is protected with a  
binary low temperature detection  
device. Based on the application of  
the unit, circuit operation is  
See the Diagnostics section on page  
28 for information about the  
automatic diagnostic reset function.  
Possible  
Fan Modes  
Heat Pump  
(1-speed)  
Filter Maintenance Timer  
The controller’s filter maintenance  
timer is based on the unit fan’s  
cumulative run hours. The controller  
compares the fan run time against  
an adjustable fan run hours limit  
(maintenance required setpoint  
time, stored in the controller) and  
recommends unit maintenance (i.e.  
changing the filter).  
OFF  
Fan Off  
Continuous: (Field  
Modified)  
z In occupied mode, the  
fan runs continuously.  
In unoccupied mode,  
the fan cycles OFF  
AUTO  
when no heating or  
cooling is required.  
Cycling: (Factory Default)  
Use Rover or BAS system to edit the  
maintenance required setpoint time.  
Once the setpoint limit is exceeded  
the controller generates a filter  
maintenance timer diagnostic.  
When the maintenance required  
setpoint time is zero, the controller  
disables the diagnostic feature.  
z The fan cycles ON and  
OFF with compressor  
operation.  
AUTO  
terminated when the leaving water  
temperature falls below 35 F or  
20 F. This is set when the unit is  
ordered.  
The ZN510 controller receives the  
fan mode from either a wired zone  
sensor or as a communicated valve.  
When neither a zone sensor nor  
communicated fan mode are  
The ZN510 controller compares the  
measured leaving water  
temperature to the leaving water  
temperature low limit value to  
determine a fault condition. When  
the measured leaving water  
temperature is less than the leaving  
water temperature low limit, the  
controller generates a Low Temp  
Detect diagnostic. If the Leaving  
Water Temp Sensor fails to open or  
close the controller generates a  
Leaving Water Temp Failure  
diagnostic. This disables unit  
operation.  
Discharge Air Temperature  
Analog input 2 (AI 2) is used as the  
discharge air temperature input for  
use with a 10,000 ohm thermistor.  
Typical factory placement of the  
thermistor is at the discharge area of  
the unit. The discharge air  
temperature sensor does not affect  
unit operation. The measured  
temperature is for information only  
to be read by the building  
present, the ZN510 controller will  
default unit operation to AUTO.  
Note:  
z A building automation system  
can also generate a fan mode  
request and communicate this  
request to the controller.  
z If the ZN510 controller does not  
receive a hardwired or commu-  
nicated request for the fan  
mode, the unit recognizes the  
fan input as AUTO and the fan  
operates according to the  
automation system or for  
troubleshooting unit operation with  
Rover.  
Note:  
A low temperature detection failure  
diagnostic for compressor 1 may  
require you to manually reset the  
unit to restore compressor opera-  
tion.  
Once a valid discharge air  
default configuration.  
temperature signal has been  
established by the thermistor or  
communicated and the value is no  
longer present, the controller  
generates a discharge air  
temperature failure diagnostic. This  
will not disable unit operation. If the  
sensor returns with a valid  
temperature, the diagnostic  
automatically clears  
Fan Off Delay  
When the heating output is  
controlled off, the ZN510  
automatically runs the fan ON for an  
additional 30 seconds to give the fan  
time to blow off any residual heat.  
Similarly, the ZN510 controller uses  
a binary low temperature detection  
device (fixed low limit trip point) to  
lock-out circuit 2 when a fault condi-  
tion is detected.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Zone Sensor  
Zone Sensor  
The ZN510 controller accepts the  
following zone sensor inputs:  
values exist, the controller ignores  
the hardwired space temperature  
input and uses the communicated  
value.  
(when present) is exposed on the  
zone sensor’s front cover.  
When the hardwired setpoint  
adjustment is used to determine the  
setpoints, all unit setpoints are  
calculated based on the hardwired  
setpoint values, the configured  
setpoints, and the active mode of  
the controller.  
z Space temperature mea-  
surement.  
Internal and External Setpoint  
Adjustment  
Zone sensors with an internal or  
z Local setpoint (internal or  
external on the zone sensor).  
external setpoint adjustment  
provide the ZN510 controller with a  
local setpoint (50 to 85 F or 10 to 29.4  
C). The internal setpoint adjustment  
is concealed under the zone sensor’s  
cover. To reveal the adjustable  
setpoint wheel, remove the zone  
sensor cover. The external setpoint  
z Fan switch. (Optional)  
z Timed override (ON and CANCEL).  
z Communication Jack.  
Setpoint Operation  
The controller has three methods of  
heating and cooling setpoints  
operation. See Table 5 for the  
methods of setpoint operation.  
If both hardwired and  
communicated space temperature  
Table 5: Methods of setpoint operation.  
Method  
Situation used  
Zone Sensor  
(with an adjustable hardwired  
setpoint)  
A hardwired, adjustable setpoint is connected to the controller. Local setpoints are  
enabled in the unit configuration. No communicated setpoint is present.  
A setpoint is communicated to the unit controller (typically from a building automation  
system or a peer controller). If both a hardwired setpoint and a communicated setpoint  
exist, the controller uses the communicated value. The configuration feature for enabling  
or disabling the local setpoint does not affect the setpoint handling when communicated  
setpoints are used. The communicated setpoint always takes priority over the hardwired  
setpoint, even when the local setpoint is enabled.  
Communicated source  
Stored default setpoints  
The controller uses the locally stored default heating and cooling setpoints when neither  
a local hardwired setpoint or communicated setpoint is present. When a building  
automation system is present, the controller uses the default setpoints when no setpoint  
is communicated to the controller and no hardwired setpoint exists. The controller uses  
stored default setpoints when only a local setpoint exists, but the local setpoint is  
disabled in the configuration of the controller. The controller always uses the stored  
default (unoccupied) setpoints in unoccupied mode.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Zone Sensor  
Zone Sensor Features  
Fan Switch (Optional)  
during unoccupied mode places the  
controller in occupied bypass mode  
for 120 minutes. You can adjust the  
number of minutes in the unit  
controller configuration using  
Trane’s service tool, Rover. The  
controller remains in occupied  
standby mode until the override  
timer expires or until the CANCEL  
button is pressed.  
controller). By accessing the  
communication jack via Rover,  
entrance to all controllers on the link  
may be gained.  
The zone sensor fan switch provides  
the controller with an occupied (and  
occupied standby) fan request signal  
of OFF or AUTO. If the fan control  
request is communicated to the  
controller, the controller ignores the  
hardwired fan switch input and uses  
the communicated value. The zone  
sensor fan switch signal can be  
enabled or disabled through  
configuration in the ZN510  
Communication Jack  
Use the RJ-11 communication jack  
as the connection point from Rover  
to the communication link (when the  
communication jack is wired to the  
communication link at the  
controller.  
ON or CANCEL Buttons  
Momentarily pressing the ON button  
Table 6: Zone Sensor Options  
Part Number:  
X13510628010  
Description:  
ZONE  
RT1  
10K OHM @  
25 °C ± 2°C  
1
SIGNAL (COMMON)  
2
3
4
5
VR1  
R7 1K  
200  
CSP  
z Space temperature (0.2 C  
ADJUSTABLE  
SETPOINT  
resolution).  
COMM HIGH (+ )  
z Internal setpoint.  
z Communication jack.  
z Vertical case with Trane logo  
COMM LOW (-)  
COMMUNICATIONS  
JACK  
MJ1  
ZONE  
RT1  
10K OHM @  
25 °C ± 2°C  
1
2
3
4
Part Number:  
X13510606010  
Description:  
SIGNAL (COMMON)  
VR1  
R7 1K  
200  
CSP  
ADJUSTABLE  
SETPOINT  
z Space temperature (0.2 C  
COMM HIGH (+ )  
resolution).  
z External setpoint.  
z Communication jack.  
z Vertical case with Trane logo  
COMM LOW (-)  
5
COMMUNICATIONS  
JACK  
MJ1  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Zone Sensor Specifications  
Part Number:  
X13510606020  
Description:  
z Space temperature (0.2 C  
resolution).  
z External setpoint.  
z ON and CANCEL buttons.  
z Communication jack.  
z Vertical case with Trane  
logo.  
Part Number:  
X13510635010  
Description:  
z Space temperature (0.2 C  
resolution).  
z External setpoint.  
ON  
z Fan Switch (OFF and  
AUTO).  
z ON and CANCEL buttons.  
z Communication jack.  
z Vertical case with Trane  
logo.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Heating or  
Cooling Control  
Mode Operation  
Heating or Cooling  
Operation  
For both single and dual compressor  
operation, the ZN510 controller  
cycles the compressor(s) on and off  
to meet heating or cooling zone  
demands. The controller uses the  
unit capacity and pulse width  
controlling only the first  
modulation (PWM) logic along with  
minimum on/off timers to determine  
the operation for compressor 1.  
compressor, the controller runs  
compressor 1 continuously and  
controls compressor 2 according to  
PWM logic along with the minimum  
on/off timers. See Table 6 for heat  
pump heating or cooling operation.  
With a dual compressor unit, if the  
desired conditions are not met by  
Table 7: Heat pump heating or cooling operation*  
Capacity  
Unit  
Between  
0 and 50%  
Between  
100%  
0%  
50 and 100%  
Compressor output is controlled according to pulse width  
modulation (PWM) logic between 0 and 100%. The  
controller calculates the compressor on/off times based  
on PWM logic and heating/cooling capacities. The  
compressor is controlled on for longer periods as the  
capacity increases and shorter periods as the capacity  
decreases.  
Compressor OFF  
continuously.  
Compressor ON  
continuously.  
Single compressor  
Both compressors  
OFF continuously.  
#1: ON PWM.  
#2: OFF continuously.  
#1: ON continuously.  
#2: ON PWM.  
Both compressors ON  
continuously.  
Dual (Two) compressors  
*Note: No diagnostics present.  
Certain heat pump configurations  
may use one or two compressors for  
cooling control. Heat pumps use  
reversing valve control to switch  
between heating and cooling. The  
controller supports cooling only  
configurations and heat pump  
configurations.  
simultaneously de-energizing the  
reversing valve. The reversing valve  
only changes state when the  
controller uses the compressor  
stages for cooling.  
controller turns on compressor 1.  
Compressor Minimum  
ON/OFF Timers  
When a power failure occurs, the  
reversing valve output defaults to  
the heating (de-energized) state. To  
reduce noise due to refrigeration  
migration after compressor  
shutdown, the controller does not  
immediately operate the reversing  
valve. The reversing valve changes  
state only when the compressor  
controls on, except when the  
z When fan mode = OFF, Com-  
pressor minimum ON timers are  
ignored.  
For heat pump configurations, the  
unit’s reversing valve is energized in  
cooling and de-energized in heating.  
For cooling, the reversing valve  
output is energized simultaneously  
with the compressor (compressor 1  
in two compressor applications).  
The reversing valve remains  
z When fan mode = AUTO, Com-  
pressor minimum OFF timers are  
observed.  
z The diagnostic reset ignores the  
compressor timers ON and OFF.  
controller is in off mode.  
z A communicated compressor  
disabled or unoccupied signal  
ignores minimum ON times.  
energized until the controller turns  
on the compressor for heating,  
For cooling only configurations, no  
reversing valve is present and the  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Single and Dual  
Compressor  
Operation  
Other Modes  
Occupancy Operation  
controller interprets the request and  
initiates the occupied setpoint  
operation. During a timed override,  
the controller applies the occupied  
heating and cooling setpoint, but  
reports the effective occupancy  
mode as occupied bypass mode. In  
the occupied bypass mode, a  
building automation system can  
detect whether the occupancy mode  
was overrode.  
damper normally is open during the  
occupied mode when the controller  
turns on the unit fan. The damper is  
normally closed during:  
Unoccupied operation normally is  
associated with evening hours when  
the space is vacant. In unoccupied  
mode, the controller always uses the  
default unoccupied heating and  
cooling setpoints stored in the  
controller. As the unit goes  
unoccupied, the compressors ON  
timers are ignored and the  
z occupied mode when the fan is  
OFF.  
z warm up/cool down mode.  
z occupied standby mode.  
z unoccupied mode.  
compressors are disabled.  
Morning Warm Up  
z certain diagnostic conditions.  
When ZN510 controls the space to  
unoccupied mode, the occupant  
may have the ability to request  
timed override through the Trane  
zone sensor’s ON button. Based on  
the controller or system setup, the  
The damper (field installed or for the  
console product) remains closed  
during morning warm up until the  
space temperature is within two  
degrees of the effective heating  
setpoint. The 2-position outdoor air  
ZN510 keeps the 2-position outside  
air damper closed on a transition  
from unoccupied mode to occupied  
mode as part of the morning warm  
up sequence.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Data Sharing  
Master Controller  
ZN510 can send or receive data  
(such as setpoint, heat/cool mode,  
fan request and space temperature)  
to and from other controllers on the  
communication link, with or without  
a building automation system. This  
includes applications where  
Master Controller  
ON  
CANCEL  
multiple unit controllers share a  
common space temperature sensor,  
both for standalone and building  
automation applications.  
Zone Sensor  
Communication Link  
The master controller (the unit  
controller with the hardwired zone  
sensor) in peer-to-peer  
communication can send its zone  
temperature to one or more slave  
controllers which allows the slave  
controllers to track each other’s  
zone temperature. For these  
applications, Rover is used in set up  
of the controller.  
Slave Controller  
Slave Controller  
Figure 9: Master/slave setpoint operation for peer-to-peer setup  
See Figure 9 for Master/Slave  
setpoint operation for peer-to-peer  
set up.  
Setpoint Operation  
Controllers sharing information  
peer-to-peer can share a variety of  
data, including the heating/cooling  
setpoint (communicated from a  
master to a slave).  
Note:  
z Heating/cooling mode.  
z Occupancy.  
Each controller derives its effective  
setpoint and default setpoints  
(including deadbands between set-  
points) from the setpoint input  
(hardwired or communicated). To  
make sure the peer-to-peer setpoint  
application results in identical set-  
points for each communicating con-  
troller, each controller must have  
exactly the same default setpoints.  
z Fan status.  
The standalone master controller  
derives its setpoint from either the  
local hardwired setpoint input or  
from its default setpoints. Peer-to-  
peer applications often require the  
use of one hardwired setpoint to be  
shared across two or more  
controllers. This can be achieved by  
wiring the adjustable setpoint  
(typically included as a part of the  
Trane zone sensor module) to the  
controller defined as the master.  
Trane’s service tool, Rover may be  
used to set up the master and one or  
more slaves to share that setpoint.  
For this application, each  
z Unit control algorithm capacity.  
This information is communicated  
from the master to the slave to  
ensure similar unit operation.  
Use Rover, Trane’s service tool, to  
set up peer-to-peer applications.  
Simplified Peer-to-Peer (Master/  
Slave) Setup  
Refer to the Rover product literature  
for more information on setting up  
applications.  
To simplify setting up master/slave  
applications, the controller provides  
information that groups all  
necessary shared data into one  
communication variable. This  
master/slave variable includes the  
following information:  
communicating controller uses the  
same setpoint.  
z Space temperature.  
z Setpoint.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configuration  
Configurable Parameters  
information, such as the default  
analog inputs, the default binary  
inputs, and the default binary output  
configurations. See Table 7 for  
default configurations for heat  
pumps.  
Rover, Trane’s service tool, uses the  
unit type “heat pump” to determine  
and download unit configuration  
Table 8: Heat pump heating or cooling operation.  
Unit Type  
Heat pump  
Cooling Source  
Heating Source  
Compressors  
Compressor  
Compressor (none for cooling only units)  
1 (2 for 2-compressor units)  
BOP 1: Fan on (normally open)  
BOP 2: Reversing valve (normally open)*  
BOP 3: Not used  
BOP 4: Compressor 1 (normally open)  
BOP 5: Compressor 2 (normally open)**  
BOP 6: Outdoor Air Damper (normally open)***  
Binary Outputs  
BI 1: Low temperature detection, circuit 2 (normally closed)*  
**  
BI 2: Condensate overflow (normally closed)†  
BI 3: Occupancy (normally open)  
Binary Inputs  
Analog Inputs  
Zone: Space temperature (0.0 F calibration)  
Set: Setpoint (0.0 F calibration)  
Fan: Fan mode  
AI 1: Leaving water temperature  
AI 2: Discharge air temperature  
Fan operation (heating): Cycling  
Fan operation (cooling): Cycling  
Fan speed default (heating): On/high  
Fan speed default (cooling): On/high  
Fan switch (hardwired): Enabled  
Fan  
Unoccupied cooling setpoint: 85 F  
Occupied standby cooling: 78 F  
Occupied cooling setpoint: 74 F  
Occupied heating setpoint: 71 F  
Occupied standby heating: 67 F  
Unoccupied heating setpoint: 60 F  
Cooling setpoint high limit: 115 F  
Cooling setpoint low limit: 40 F  
Heating setpoint high limit: 115 F  
Heating setpoint low limit: 40 F  
Thumbwheel set point: Enabled  
The heating and cooling setpoint  
high and low limits only apply to the  
occupied and occupied standby  
setpoints. These limits never apply  
to the unoccupied setpoints.  
Setpoints  
The occupied bypass time is used for timed  
override applications. The timed override  
timer is maintained in the unit controller.  
When the timed override is applicable, the  
controller reports “Occupied Bypass” as its  
effective occupancy mode.  
Occupied Bypass  
Timer  
120 minutes  
Leaving Water  
Temperature  
Low Limit  
Unit specific (20 F ground source or 35 F standard)  
Unit specific (maximum of 30 characters)  
Location Identifier  
The leaving water temperature low  
limit is used for freeze protection of  
circuit 1 on heat pumps. Circuit 2 is  
protected by a binary low  
temperature detection device  
(freezestat) with a fixed trip point.  
* BOP 2, BI1: Not used on cooling only units.  
** BOP 5: Not used on signal compressor unit.  
*** Configured but not required.  
† Optional model number dependent  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Red Service LED  
Table 9: Red LED activity  
Red LED Activity  
Description  
LED off continuously when power is applied to the  
controller.  
Normal operation.  
LED on continuously, even when power is applied to Someone is pressing the service button or the controller has  
the controller.  
failed.  
Use Rover, Trane’s service tool, to restore the unit to normal  
operation or unconfigured.  
LED flashes once every second.  
!Warning! Service Button  
The black Service button on the ZN510 board allows the user to send a service pin message, which allows  
efficient identification of the unit's location. However, if the Service button is held for more than 10  
seconds, the ZN510 will shut down the software application and disable the unit's operation. The only  
method to restore the unit is through the use of Rover service tool. We strongly suggest that this function  
only be exercised under the strict direction of factory service personnel.  
Green Status LED  
The green LED normally indicates  
Table 10: Green LED activity  
whether the controller is powered  
on (24 VAC).  
Green LED Activity  
Description  
LED on continuously.  
Power on (normal operation).  
Manual output test mode (2-second hold), No  
diagnostics present.  
LED blinks (one blink).  
LED blinks (two blinks).  
Manual output test mode (2-second hold),  
One or more diagnostics are present.  
“Wink” mode.  
This feature allows the identification of a  
controller. By sending a request from a device,  
such as Rover, Trane’s service tool or ZN510  
Loop Controller, a request to the controller  
can be made to “wink” a notification that the  
controller received the signal. When the zone  
sensor ON button is held for 10 seconds  
“Wink” mode is sent from Comfort Link  
Controller.  
LED blinks (1/4 second on,  
1/4 second off for 10 seconds.  
z Power off.  
z Abnormal condition.  
z Test button is pressed.  
LED off.  
Yellow Service LED  
Table 11: Yellow LED activity  
Yellow LED Activity  
Description  
The controller is not detecting any communication.  
(Normal for standalone applications).  
LED off continuously.  
The controller detects communication. (normal for  
communicating applications, including data sharing).  
LED blinks.  
LED on continuously.  
Abnormal condition.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Manual Output Testing the Heat  
Pump Configurations  
The procedure for testing heat pump  
for at least three seconds to  
start the test mode.  
3. Press the Test button several  
more times (no more than once  
per second) to advance through  
the test sequence.  
2. The test sequence resets  
diagnostics and turns off all  
outputs.  
configurations is:  
1. Press and hold the Test button  
Table 12: Test sequence  
Fan  
BOP 1  
Reversing Valve  
BOP 2  
Compr 1 Compr 2  
BOP 4 BOP 5  
Damper  
BOP 6  
Step  
1. Off  
Off  
Off  
Off  
Off Off  
Closed  
2. Fan on (At the beginning of step 2, the  
controller attempts to clear all diagnostics).  
On  
Off  
Off  
Closed  
3. Reversing Valve  
4. Cool 1  
On  
On  
On  
On  
On  
On  
Off  
On  
On  
Off  
Off  
On  
Closed  
Closed  
Closed  
5. Cool 2  
6. Compressor(s) off  
This stage helps avoid compressor cooling  
and heating in sequential steps by turning the On  
compressors off prior to changing the  
reversing valve state.  
Off  
Off  
Off  
Closed  
7. Heat 1  
On  
On  
On  
Off  
Off  
Off  
On  
On  
Off  
Off  
On  
Off  
Closed  
Closed  
Open  
8. Heat 2  
9. Outdoor air damper  
10. Exit  
After the outdoor air damper step, the test  
sequence performs the exit step. This  
initiates a reset and attempts to return the  
controller to normal operation.  
Testing the Heat Pump  
Configurations  
The outputs are not subject to  
minimum times during the test  
sequence. However, the test  
sequence only permits one step per  
second which limits output time.  
the same as two compressor units.  
For single compressor units, the  
cool 2 and heat 2 steps control the  
appropriate binary outputs, but do  
not affect unit operation.  
Pump Operation for  
Systems with ZN510  
Loop Controller  
During Unoccupied, the pumps will  
be OFF but should be energized to  
test compressor operation. The user  
must override the pumps either at  
the ZN510 Loop Controller or by  
pushing the ON button of the zone  
sensor. This will send the units to an  
occupied bypass, which will turn the  
pumps on prior to operating  
manual output test.  
Reversing valve and damper  
outputs cycle independent of  
configuration.  
All outputs are exercised regardless  
what timer they are or are not  
configured for. For example, single  
compressor heat pumps function  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Questionable Unit  
Operation  
Table 13: Fan output does not energize  
Probable Cause  
Explanation  
After power up, the controller always observes a random start from 0 to 25  
seconds. The controller remains off until the random start time expires.  
Random start observed.  
Power up control wait.  
When power up control wait is enabled (non-zero time), the controller remains  
off until one of two conditions occurs:  
z The controller exits power up control wait once it receives commu-  
nicated information.  
z The controller exits power up control wait once the power up control  
wait time expires.  
When configured to cycle with capacity, normally the unit fan cycles off with  
heating or cooling. The heating/cooling sources cycle on or off periodically with  
the unit fan to provide varying amounts of capacity to the space.  
Cycling fan operation.  
Unoccupied operation.  
Even when the controller is configured for continuous fan operation, the fan  
normally cycles with capacity during unoccupied mode. While unoccupied, the  
fan cycles on or off with heating/cooling to provide varying amounts of heating  
or cooling to the space.  
When a local fan mode switch determines the fan operation, the off position  
controls the unit fan off.  
Fan mode off.  
The desired operating mode (such as off, heat and cool) can be communicated to  
the controller. When off is communicated to the controller, the unit controls the  
fan off. There is no heating or cooling.  
Requested mode off.  
Diagnostic present.  
A specific list of diagnostics affects fan operation. See Diagnostics section on  
page 27.  
If the controller does not have power, the unit fan does not operate. For the  
ZN510 controller to operate normally, it must have an input voltage of 24 VAC.  
When the green LED is off continuously, the controller does not have sufficient  
power or has failed.  
No power to the controller.  
Unit configuration.  
Manual output test.  
Unit wiring.  
The controller must be properly configured based on the actual installed end  
devices and application.  
The controller includes a manual output test sequence that may be used to verify  
output operation and associated output wiring. However, based on the current  
step in the test sequence, the unit fan may not be on. Refer to the manual output  
overrides on page 9.  
The wiring between the controller outputs and the fan relays and contacts must  
be present and correct for normal fan operation.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Questionable Unit  
Operation  
Table 14: Compressor(s) not running  
Probable Cause  
Explanation  
The controller compressor(s) turn on and off to meet the unit capacity  
requirements.  
Normal operation.  
The desired operating mode (such as off, heat and cool) can be communicated to  
the controller. When off is communicated to the controller, the unit shuts off all  
unit compressor(s).  
Requested mode off.  
Numerous communicated requests may disable the compressor, including a  
compressor enable input. Depending on the state of the communicated request,  
the unit may disable the compressor.  
Communicated disable.  
Manual output test.  
The controller includes a manual output test sequence that may be used to verify  
output operation and associated output wiring. However, based on the current  
step in the test sequence, the compressor(s) may not be on. Refer to the manual  
output overrides on page 9.  
A specific list o f diagnostics affects compressor operation, depending whether  
the unit is configured as heat pump. For more information, see the Diagnostics  
section on page 27.  
Diagnostic present.  
Unit configuration.  
The controller must be properly configured based on the actual installed end  
devices and application. When the unit configuration does not match the actual  
end device, the compressor may not work correctly.  
If the controller does not have power, the compressor does not operate. For the  
ZN510 controller to operate normally, a voltage input of 24 VAC must be applied.  
When the green LED is off continuously, the controller does not have sufficient  
power or has failed.  
No power to the controller.  
Unit wiring.  
The wiring between the controller outputs and the compressor contacts must be  
present and correct for normal compressor operation.  
Table 15: Outdoor air damper stays open  
Probable Cause  
Explanation  
The controller opens and closes the outdoor air damper based on the controllers  
occupancy mode and fan status. Normally, the outdoor air damper is open  
during occupied mode when the fan is running and closed during unoccupied  
mode. Refer to the outdoor air damper section on page 8.  
Normal operation.  
Manual output test.  
The controller includes a manual output test sequence that may be used to verify  
output operation and associated output wiring. However, based on the current  
step in the test sequence, the outdoor air damper may not open. Refer to the  
manual output overrides on page 9.  
The controller must be properly configured based on the actual installed end  
devices and application. When the unit configuration does not match the actual  
end device, the outdoor air damper may not work correctly.  
Unit configuration.  
Unit wiring.  
The wiring between the controller outputs and the compressor contacts must be  
present and correct for normal damper operation.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Questionable Unit  
Operation  
Table 16: Outdoor air damper stays closed  
Probable Cause  
Explanation  
The controller opens and closes the outdoor air damper based on the controllers  
occupancy mode and fan status. Normally, the outdoor air damper is open  
during occupied mode when the fan is running and closed during unoccupied  
mode. Refer to the outdoor air damper section on page 8.  
Normal operation.  
The controller includes both a morning warm-up and cool down sequence to  
keep the outdoor air damper closed during the transition from unoccupied to  
occupied. This is an attempt to bring the space under control as quickly as  
possible.  
Warm up and cool down.  
Requested mode off.  
Manual output test.  
The desired operating mode (such as off, heat and cool) can be communicated to  
the controller. When off is communicated to the controller, the unit closes the  
outside air damper.  
The controller includes a manual output test sequence that may be used to verify  
output operation and associated output wiring. However, based on the current  
step in the test sequence, the outdoor air damper may not be open. Refer to the  
manual output overrides on page 9.  
A specific list o f diagnostics affects outdoor air damper operation, depending  
whether the unit is configured as heat pump. For more information, see the  
Diagnostics section on page 27.  
Diagnostic present.  
Unit configuration.  
The controller must be properly configured based on the actual installed end  
devices and application. When the unit configuration does not match the actual  
end device, the outdoor air damper may not work correctly.  
If the controller does not have power, the compressor does not operate. For the  
ZN510 controller to operate normally, a voltage input of 24 VAC must be applied.  
When the green LED is off continuously, the controller does not have sufficient  
power or has failed.  
No power to the controller.  
Unit wiring.  
The wiring between the controller outputs and the outdoor air damper must be  
present and correct for normal outdoor air damper operation.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Diagnostics  
Table 17: ZN510 controller diagnostics  
Diagnostic  
Condensate overflow  
Fan  
Other Outputs  
Compressors: Off  
Off  
Damper: Closed  
Compressor 1: Off  
Low temp detect - Crt 1  
Enabled  
Enabled  
Off  
Compressor 2: See note below.  
Damper: See note below.  
Compressor 1: See note below.  
Compressor 2: Off  
Damper: See note below.  
Low temp detect - Crt 1  
Compressor 1: Off  
Compressor 2: Off  
Damper: Closed  
Low temp detect - Crt 1 and 2  
High/low press cutout - Crt 1  
High/low press cutout - Crt 2  
Compressor 1: Off  
Compressor 2: See note below.  
Damper: See note below.  
Enabled  
Enabled  
Compressor 1: See note below.  
Compressor 2: Off  
Damper: See note below.  
Compressor 1: Off  
Compressor 2: Off  
Damper: Closed  
High/low press cutout - Crt 1 and 2  
Space temperature failure*  
Off  
Off  
Compressor(s): Off  
Damper: Closed  
Compressor 1: Off  
Compressor 2: See note below.  
Damper: See note below.  
Leaving water temp failure  
Enabled  
Compressor(s): No action  
Damper: No Action  
Discharge air temp failure*  
Enabled  
Enabled  
Enabled  
Enabled  
Disabled  
Maintenance required  
(example: Filter Status)  
Compressor(s): No action  
Damper: No Action  
Compressor(s): Enabled  
Damper: Enabled  
Local setpoint failure*  
Local fan mode failure*  
Invalid unit configuration  
Compressor(s): Enabled  
Damper: Enabled  
Compressor(s): Disabled  
Damper: Disabled  
High/low pressure cutout and low temperature detection diagnostics for heat pump configurations isolate  
each circuit and independently disable compressor operation. For single compressor units, these diagnostics cause  
the compressor to shut down, the unit fan to be controlled off, and the outdoor air damper to be closed (when  
present).  
When BOP 6 is configured as a generic binary output, BOP 6’s state is unaffected by all unit diagnostics.  
* Note: Non-latching diagnostics automatically reset when the input is present and valid.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Diagnostics  
Translating Multiple  
Diagnostics  
z High/low pressure cutout,  
Rover Service Tool  
Circuit 1 and 2  
Trane’s service tool, Rover, can reset  
diagnostics in the ZN510 controller.  
For complete information about  
Rover, refer to the Rover product  
literature.  
The controller senses and records  
each diagnostic independently of  
the diagnostics. It is possible to have  
multiple diagnostics present  
simultaneously. The diagnostics are  
reported in the order they occur.  
When one or more of these special  
diagnostics occurs, the controller  
responds to the diagnostic as  
defined in the table 17 on page 27.  
After the controller detects the first  
special diagnostic (listed on page  
27), the unit waits 30 minutes before  
invoking the automatic diagnostic  
reset function. The automatic  
diagnostic reset function clears all  
special diagnostics and attempts to  
restore the controller to normal  
operation. The controller resumes  
normal operation until another  
diagnostic occurs.  
Alarm Reset  
Any device that can communicate  
alarm reset information can reset  
diagnostics in the ZN510 controller.  
Resetting Diagnostics  
1. Automatically by the controller.  
2. By initiating a manual output  
ZN510 Controller Replacement  
1. Disconnect power or disable  
the circuit breaker to unit.  
test at the controller.  
3. By cycling power to the  
controller.  
2. Remove bad or questionable  
ZN510 Controller.  
4. Through a building automation  
system such as ZN510 Loop  
Controller.  
3. Install controller in the unit with  
the heatsink placement at the  
top of the control box. (See  
page 32).  
If a special diagnostic occurs within  
24 hours after an automatic  
diagnostic reset, the diagnostic  
must be manually reset.  
5. Through Rover, Trane’s service  
tool.  
4. Connect the power to the ZN510  
6. Through any communicating  
device with the ability to access  
the controllers alarm reset  
input.  
Cycling Power  
ONLY. (TB1-1 & TB1-2 on ZN510)  
When the 24 VAC power to the  
controller has been turned off, the  
unit cycles through a power up  
sequence. By default, the controller  
attempts to reset all diagnostics at  
power up. Diagnostics present at  
power up and those that occur after  
power up are handled according to  
the table on page 27.  
5. Connect Rover and properly  
configure the controller, unless  
a previously configured board  
is purchased.  
Automatic Diagnostic Reset  
The ZN510 controller includes an  
automatic diagnostic reset function.  
This function attempts to  
automatically recover a unit when  
the following diagnostics occur:  
z Low temperature detection,  
Circuit 1  
6. Power down.  
7. Connect the remaining input  
and output wiring to the  
controller.  
Building Automation System  
(CLC)  
8. Reapply power.  
z Low temperature detection,  
Some building automation systems  
can reset diagnostics in the ZN510  
controller. The ZN510 Loop  
Controller can reset diagnostics in  
the ZN510 Controller. For complete  
information, refer to the building  
automation system product  
literature.  
9. Complete sequence 7 and 8  
above in the installation section  
of this manual.  
Circuit 2  
z Low temperature detection,  
Circuit 1 and 2  
10. Refer to BAS manual for  
instructions on how to install  
the new ZN510 into BAS  
system.  
z High/low pressure cutout,  
Circuit 1  
z High/low pressure cutout,  
Circuit 2  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagram  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Diagram  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hardware  
Specifications  
Specifications  
Storage Environment  
-40 to 185 F (-40 to 85 C)  
5 to 95% non-condensing  
Power Requirements  
18 to 32 VAC (24 VAC nominal)  
50 or 60 Hz  
(EFT), IEC 1000-4-5 (Surge), FCC Part  
15, Class A.  
Board Dimensions  
Input/Output Summary  
z Three binary inputs.  
Height:  
Width:  
Depth:  
4” (102 mm)  
z Six binary outputs only five are  
5-1/2” (140 mm)  
2-1/4” (57mm)  
300 mA  
used.  
z Five analog inputs.  
Agency Listings  
z Timed override ON and CANCEL.  
z Comm5 communication.  
UL and CUL 916 Energy  
Management System  
Agency Compliance  
Operating Environment  
32 to 140 F (0 to 60 C)  
5 to 95% non-condensing  
IEC 1000-4-2 (ESD), IEC 1000-4-4  
Heat sink is mounted to the top  
of the control box  
4”  
5 1/2”  
Figure 10: ZN510 Circuit Board  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hardware  
Specifications  
Table 18: Binary Inputs  
Description  
Terminals  
Function  
Binary Input 1  
J2-1  
J2-2  
J2-3  
J2-4  
J2-5  
J2-6  
24 VAC  
Input  
Binary Input 2  
Binary Input 3  
24 VAC  
Input  
24 VAC  
Input  
Table 19: Binary Outputs  
Output  
Description  
Terminals  
Load Energized  
Rating  
Load De-energized  
Binary Output 1  
Binary Output 2  
Binary Output 3  
Binary Output 4  
Binary Output 5  
Binary Output 6  
J1-1  
J1-2  
J1-4  
J1-5  
J1-6  
J1-7  
12 VA  
1 VAC RMS (typical)  
1 VAC RMS (typical)  
24 VAC RMS (typical)  
24 VAC RMS (typical)  
12 VA  
NOT USED  
12 VA  
1 VAC RMS (typical)  
1 VAC RMS (typical)  
1 VAC RMS (typical)  
24 VAC RMS (typical)  
24 VAC RMS (typical)  
24 VAC RMS (typical)  
12 VA  
12 VA  
Table 20: Analog Inputs  
Description Terminals  
Zone  
Function  
Range  
TB3-1  
TB3-2  
TB3-3  
TB3-4  
Zone temperature input  
Analog ground  
5 to 122 F (-15 to 50 C)  
Ground  
Set  
NA  
Setpoint input  
40 to 115 F (4.4 to 46.1 C)  
Fan  
Fan switch input  
OFF = 4821 to 4919 Ohms  
AUTO = 2297 to 2342 Ohms  
Ground  
TB3-6  
J3-1  
Analog ground  
NA  
Analog Input 1  
Leaving water  
temperature  
-40 to 212 F (-40 to 100 C)  
J3-2  
J3-3  
J3-4  
Analog ground  
NA  
Analog Input 2  
Discharge air temperature -40 to 212 F (-40 to 100 C)  
Analog ground NA  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Technicolor Thomson CRT Television ETC210 User Manual
Texas Instruments Musical Instrument Amplifier TMS320C645X User Manual
Toshiba Cell Phone TG01 User Manual
Toshiba Security Camera IK WB81A User Manual
Transcend Information Camera Accessories CF 266X User Manual
TRENDnet Router N300 Wireless PoE Access Point User Manual
Tripp Lite Surge Protector SS7619 15 User Manual
Uniden Cordless Telephone DCX520 User Manual
Universal Laser Systems Printer CLP 100NI NPRT User Manual
ViewSonic Computer Monitor VS13818 User Manual