Installation/
Operation
Maintenance
VariTrane™
Pneumatic Controls
March 2002
VAV-SVX02B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Thermostat
Specifications
Operation
Figure 4 illustrates the pressure/
temperature characteristics for a
reverse-acting thermostat. As room
temperature increases, the thermostat
output pressure decreases.
TP970 Series PneumaticT-stats
Maximum Safe Air Pressure:
25psi (172 kPa)
Maximum Safe AirTemperature:
150°F (66°C)
Pneumatic thermostats modulate
output air pressure in response to room
air temperature. Pneumatic thermo-
stats fall into two categories: direct-
acting or reverse-acting.This section
describes how thermostat output
pressure responds to changes in room
temperature.
Figure 4–Reverse-Acting
Thermostat Response
Throttling Range:
2–10°F (1–5°C)
Figure 3 graphically illustrates the
relationship between room
Gain:
2.5 psi/°F Adjustable
temperature and output pressure of a
direct-acting thermostat.The graph in
Figure 3 shows that as the room
temperature increases, so does the
output pressure of the thermostat.
Figure 3–Direct-Acting
Thermostat Response
InputTemperature
A thermostat in proper working order
will be able to output a pressure
ranging from approximately .5 psi to
supply air pressure depending on
distance from indicated setpoint.
InputTemperature
VAV-SVX02B-EN
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Reversing Relay
Figure 6–Reversing Relay Connections
Installation and Operation
The reversing relay is a proportional,
non-bleeding device for use in pneu-
matic control systems where a propor-
tional signal from a controlling device
must be reversed (see Figure 5).The
most common use of the reversing
relay is to change the action of a
pneumatic thermostat.
Output
Branch
S
20
(137.9)
Figure 5–Pneumatic Reversing Relay
Trane Part No. RLY-755
9 PSI In
(62.06 kPa)
B
M
S
Reversing
Relay
9 PSI Out
(62.06 kPa)
Input
Branch
The reversing relay requires three
piping connections: main/supply air,
input signal air, and output branch air
(see Figure 6).The branch line pressure
decreases in direct proportion to an
increase in the input signal pressure
and vice-versa.The input signal is also
amplified, thereby minimizing any
pneumatic line transmission lag
(see Figure 7).
Input pressure to the relay and output
pressure to the PR should always add
up to a constant, which is usually set
between 16 and 25 psi. For example,
with a constant of 18, six-pound input
signal will result in a 12 pound branch
signal. A bias adjustment screw is
provided to retard or advance the out
signal.
Figure 7–Reversing Relay Characteristics
15
12
3
15
3
6
Inc.
Input Pressure Signal
VAV-SVX02B-EN
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Reversing Relay
Calibration
Figure 8–Recalibrating Reversing Relay
By using the “bias” adjustment on the
relay, the factory-set 8.0–9.0 “cross-
over” can be changed.To recalibrate,
the relay should be connected as
illustrated in Figure 8.
Gage
1
C
3
Pressure
Regulator
Bias
Adjustment
Screw
M
M
If the new desired “cross-over”
pressure is 11.0 psi, this must be applied
to port #3 by adjusting the pressure
regulator.The “bias” adjustment is then
turned until 11.0 psi is obtained on the
output gage.Turning the “bias” adjust-
ment “CW” increases the output;
“CCW” decreases it.
This 11.0 psi “cross-over” would yield
the following operational chart:
New Cross-over pressure
Chart
Input:
Output:
1
20
2
19
3
18
4
17
5
16
6
15
7
14
8
13
9
12
10
11
11
10
12
9
13
8
14
7
15
6
16
5
17
4
18
3
19
2
20
1
Specifications
Ambient Limits:
+40°F/+120°F operating (+4°C/+49°C)
Maximum Pressure:
30 psig
Connections:
3/16" (4.& mm) nipples for ¼" (6.4 mm) OD
polyethylene tubing
Mounting:
In-line via air connections
Factory Settings:
9 psig in./9 psig out and 8 psig in./8 psig
out
Air Consumption:
0.5 SCFH (.236 L/M) @ 20 psig
Material:
ABS
Bias Adjustment:
+/-15 psi
Weight:
3 ½ oz
VAV-SVX02B-EN
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Model 3011—Pneumatic
Volume Regulator
Installation
Model 3011
1. Attach bracket either vertically or horizontally to the illustration surface. Horizontal
is preferred, vertical is acceptable, any other position is not acceptable (see Figure 9).
The model 3011 PneumaticVolume
Regulator (PVR) is capable of operating
with normally-open or normally-closed
air valves and can operate with either
direct-acting (DA) or reverse-acting
(RA) thermostats.
2. Insert controller into its bracket. Controller may be face up, face down, face left, or
face right.The controller LO and HI stat delta P must be calibrated in the same
position that it is mounted.
Figure 9–Acceptable Installation Positions
Connections
Figure 10 illustrates a typical piping diagram of a normally-open or normally-
closed unit.
Figure 10–Typical Piping Diagram of Normally-Open or Normally-Closed Unit
Normally-Open Unit or
Normally-Closed Unit
One-Pipe
Remote-Installed
Volume
Regulator
LO
T-Stat
Restrictor
Tee
HI
T
H
LO STAT ∆P
B
Actuator
HI STAT∆P
R
N
N
Restricted Leg
M
RESET SPAN
DAMPER
G
Airflow Sensor
S
S
20
20
Selecting Direct- or Reverse-Acting Thermostat (3011)
The model 3011 PVR must be calibrated to operate with either a direct-acting or
reverse-acting thermostat.The control must also be changed when used with a
normally-open or normally-closed air valve.
VAV-SVX02B-EN
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Model 3011—Pneumatic
Volume Regulator
Use the following procedure to set-up the PVR:
1. Select damper action (NO or NC). Loosen damper selection switch screw and align to either the NO or NC pointer with damper
pointer and tighten screw.
2. Now determine the type of thermostat that will be used. If a direct-acting thermostat is used, the reset start pressure is typically
8 psi. If a reverse-acting thermostat is used, the reset start pressure is typically 3 psi (see Figure 11).
3. With an accurate gage (0-10 psi) connected to port “G”, regulate the thermostat pressure to port “T” to desired start point pressure.
4. Adjust reset start to indicate 0 psi on port “G” and continuing adjusting to indicate a pressure slightly higher than 0 psi, (i.e., 0.1 psi).
Figure 11–Adjusting Reset Start
Adjust to obtain 0–0.1 psi at port G
Connect Hand Pump
Input desired LO stat
pressure at t-stat port
0–20 psi
Handpump
RESET START
B
LO STAT ∆P
HI STAT ∆P
NO
M
DAMPER
psi
RESET SPAN
10
Connect 0–10 psi Gage
0
G
Factory-set at 5 psi
Adjustable (0–10 psi)
NOTE: The arrows on the damper selector must be aligned
exactly or the range of the controller will be limited .0 psi
Adjusting the Reset Span (3011)
The reset span is factory-set at 5 psi.This is the thermostat pressure difference from which the PVR delivers flow from minimum
to maximum setpoints.This range is not normally changed unless a special control scheme is used where control operation
must be changed.
To field adjust a different reset span, follow these steps:
1. Connect an accurate gage to port “G”.
2. Apply 20 psi to port “T”.
3. Adjust reset span to indicate the desired span on port “G” (see Figure 12).
4. LO-stat and HI-stat delta P must now be readjusted (see following calibration procedure)
Figure 12–Adjusting Reset Span
Apply 20 psi
T
H
RESET START
LO STAT
P
B
HI STAT
P
NO
R
M
RESET SPAN
DAMPER
G
PSI
Adjust to obtain desired reset span
0
VAV-SVX02B-EN
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Calibration
Procedures
Calibration Procedure (Steps 1–4 apply to all thermostat models)
1. Be sure the PVR is installed correctly and that all connections are hooked up to the proper ports. See Figure 9 for unit application.
2. Remove the caps on the tees which are connected to the lines to the flow sensor. Connect a 0–2" magnehelic gage to monitor
flow sensor delta P. The higher-pressure port is further upstream on the air valve inlet.
3. Remove the thermostat line and connect a hand pump with a 0–20 psi gage to port “T”.
4. Tee a 0–20 psi gage in the line from port “B” on the volume regulator to the air valve actuator.
Normally-OpenValve
Normally-OpenValve
Reverse-Acting Thermostat
(See Figure 13 for proper
connections):
Reverse-Acting Thermostat
(See Figure 14 for proper
connections):
Direct-Acting Thermostat
(See Figure 13 for proper
connections)
Direct-Acting Thermostat
(See Figure 14 for proper
connections):
5. Set port “T” at 0 psi.
5. Set port “T” at 0 psi.
5. Set port “T” at 0 psi.
5. Set port “T” at 0 psi.
6. Monitor the delta P and
adjust the LO-stat delta P
(maximum) adjustment to
desired maximum. If the
actuator pressure is less
than 3 psi, the air valve is
wide open and duct
6. Monitor the delta P and
adjust the LO-stat delta P
(maximum) adjustment to
desired maximum flow. If
the actuator pressure is
greater than 13 psi, the air
valve is wide open and
duct pressure must
6. Monitor the delta P and
adjust the LO-stat mini-
mum) adjustment to
desired minimum.
6. Monitor the delta P and
adjust the LO-stat (mini-
mum) adjustment to
desired minimum.
7. Set port “T” input at 16
psi or greater with the
hand pump.
7. Set port “T” input at
16 psi or greater with the
hand pump.
pressure must increase to
increase flow.
8. Monitor the delta P and
adjust the HI-stat (maxi-
mum) adjustment to
8. Monitor the delta P and
adjust the HI-stat
increase to increase flow.
7. Set prot “T” to 16 psi
7. Set prot “T” to 16 psi
or greater with the
hand pump.
(maximum) adjustment
to desired maximum flow.
If the actuator pressure is
greater than 13 psi, the air
valve is wide open and duct
pressure must increase to
increase flow.
or greater with the
hand pump.
desired maximum flow. If
the actuator pressure is
less than 3 psi, the air
valve is wide open and
duct pressure must
8. Monitor the delta P and
adjust the HI-stat (mini-
mum) adjustment to
8. Monitor the delta P and
adjust the HI-stat (mini-
mum) adjustment to
desired minimum flow.
increase to increase flow.
desired minimum flow.
9. Set port “T” at 0 psi.
9. Set port “T” at 0 psi.
9. Set port “T” at 0 psi.
9. Set port “T” at 0 psi.
10.Monitor the maximum
flow delta P. If it is not
correct, adjust the LO-stat
adjustment knob.
10. Monitor the minimum
flow delta P. If it is not
correct, adjust the LO-stat
adjustment knob.
10.Monitor the minimum
flow delta P. If it is not
correct, adjust the LO-stat
adjustment knob.
10.Monitor the maximum
flow delta P. If it is not
correct, adjust the LO-stat
adjustment knob.
Figure 13–Connections of Direct/Reverse-Acting
Thermostat with Normally-Open Valve
Figure 14–Connections of Direct/Reverse-Acting
Thermostat with Normally-Closed Valve
0–2' Magnahelic Gage
0–2' Magnahelic Gage
HI LO
HI LO
Normally-Closed Unit
Normally-Open Unit
Apply 20 psi
Apply 20 psi
Volume
Regulator
Volume
Regulator
LO
LO
HI
HI
T
T
H
H
RESET START
LO STAT
RESET START
LO STAT
P
P
B
B
Actuator
Actuator
HI STAT
P
HI STAT
P
PSI
R
R
N
NO
NC
M
M
DAMPER
DAMPER
0
10
0
10
Connect 0–20 psi Gage
Connect 0–20 psi Gage
G
G
Airflow Sensor
Airflow Sensor
Connect Hand Pump
0–2 psi
Handpump
Connect Hand Pump
0–2 psi
Handpump
S
20
S
20
8
VAV-SVX02B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications (3011)
Specifications (3011)
Differential Pressure Range:
0 to 1.0 in. wg
Minimum Setpoint Range:
0 to 1.0" H2O
Normal Supply Air Pressure:
20.0 psi
Reset Span Range:
0–10 psi
Minimum Supply air Pressure:
15.0 psi
Maximum SafeThermostat Input:
30 psi (closed chamber)
Maximum Supply Air Pressure:
30.0 psi
OperatingTemperature:
+40/+120°F
Maximum Setpoint Range:
minimum to 1.0 in. wg
Average Supply Air Consumption:
28.8 scim at 20 psi
StorageTemperature:
-40/+140°F
Operating Static Range:
0.25–6.0 in. wg
Thermostat Pressure Input Range:
Adjustable 0–10 psi band from 0–20 psi
Main,Thermostat, Actuator and Static
Pick-up Connections:
.250 O.D.
Reset Start Point Range:
0–10 psi
VAV-SVX02B-EN
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Model 3501—Pneumatic
Volume Regulator
Installation
Adjusting the Reset Span (3501)
Model 3501
1. Attach bracket either vertically or
horizontally to the installation surface.
Horizontal is preferred, vertical is
acceptable, any other position is
not acceptable.
The reset span is factory-set at 5 psi.
This is the thermostat pressure differ-
ence from which the PVR delivers
flow from minimum to maximum
setpoints.This range is not normally
changed unless a special control
scheme is used where control
The model 3501 PneumaticVolume
Regulator (PVR) is capable of operating
with normally-open or normally-closed
air valves and can operate with either
direct-acting (DA) or reverse-acting
(RA) thermostats.
2. Insert controller into its bracket.
Controller may be face up, face down,
face left, or face right.The controller
LO and HI stat delta P must be
calibrated in the same position that it
is installed.
operation must be changed.
To field adjust a different reset span,
follow these steps:
1. Connect an accurate gage to port “G”.
Selecting Direct- or Reverse-Acting
Thermostat (3501)
2. Apply 20 psi to port “T”.
3. Adjust reset span to indicate the
desired span on port “G”.
The model 3501 PVR must be calibrated
to operate with either a direct-acting or
reverse-acting thermostat.The control
must also be changed when used with
a normally-open or normally-closed
air valve.
4. LO-stat and HI-stat delta P must now
be readjusted (see following
calibration procedure).
Use the following procedure to set-up
the PVR:
1. Select damper action (NO or NC).
Loosen damper selection switch
screw and align to either the NO or
NC pointer with damper pointer and
tighten screw.
2. Now determine the type of thermostat
that will be used. If a direct-acting
thermostat is used, the reset start
pressure is typically 8 psi. If a reverse-
acting thermostat is used, the reset
start pressure is typically 3 psi.
3. With an accurate gage (0–30 psi)
connected to port “G”, regulate the
thermostat pressure to port “T” to
10.5 psi.
4. Adjust reset start to indicate 2.5 psi on
port “G”
10
VAV-SVX02B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Calibration
Procedures
Calibration Procedure (Steps 1–4 apply to all thermostat models)
1. Be sure the PVR is installed correctly and that all connections are hooked up to the proper ports.
2. Remove the caps on the tees, which are connected to the lines to the flow sensor. Connect a 0–2" magnehelic gage to monitor
flow sensor delta P.The higher-pressure port is further upstream on the air valve inlet.
3. Remove the thermostat line and connect a hand pump with a 0–20 psi gage to port “T“.
4. Tee a 0–20 psi gage in the line from port “B” on the volume regulator to the air valve actuator.
Normally-Open Valve
Normally-Closed
Direct-Acting Thermostat
5. Set port “T” at 0 psi.
Reverse-Acting Thermostat
5. Set port “T” at 0 psi.
Direct-Acting Thermostat
5. Set port “T” at 0 psi.
Reverse-Acting Thermostat
5. Set port “T” at 0 psi.
6. Monitor the delta P and
adjust the LO-stat delta P
(maximum) adjustment to
desired maximum. If the
actuator pressure is less
than 3 psi, the air valve is
wide open and duct
6. Monitor the delta P and
adjust the LO-stat
6. Monitor the delta P and
adjust the LO-stat delta P
(maximum) adjustment to
desired maximum. If the
actuator pressure is
6. Monitor the delta P and
adjust the LO-stat
(minimum) adjustment to
desired minimum.
(minimum) adjustment
to desired minimum.
7. Set port “T” input at
16 psi or greater with
the hand pump.
7. Set port “T” input at
16 psi or greater with
the hand pump.
greater than 13 psi, the air
valve is wide open and
duct pressure must
pressure must increase
to increase flow.
8. Monitor the delta P and
adjust the HI-stat
8. Monitor the delta P and
adjust the HI-stat
increase to increase flow.
7. Set prot “T” to 16 psi
or greater with the
hand pump.
7. Set prot “T” to 16 psi
or greater with the
hand pump.
(maximum) adjustment to
desired maximum flow. If
the actuator pressure is
greater than 13 psi, the air
valve is wide open and duct
pressure must increase to
increase flow.
(maximum) adjustment to
desired maximum flow. If
the actuator pressure is
less than 3 psi, the air
valve is wide open and
duct pressure must
8. Monitor the delta P and
adjust the HI-stat
8. Monitor the delta P and
adjust the HI-stat
(minimum) adjustment
to desired minimum flow.
(minimum) adjustment to
desired minimum flow.
increase to increase flow.
9. Set port “T” at 0 psi.
9. Set port “T” at 0 psi.
9. Set port “T” at 0 psi.
9. Set port “T” at 0 psi.
10. Monitor the minimum
flow delta P. If it is not
correct, adjust the LO-stat
adjustment knob.
10. Monitor the maximum
flow delta P. If it is not
correct, adjust the LO-stat
adjustment knob.
10. Monitor the minimum
flow delta P. If it is not
correct, adjust the LO-stat
adjustment knob.
10.Monitor the maximum
flow delta P. If it is not
correct, adjust the LO-stat
adjustment knob.
VAV-SVX02B-EN
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications (3501)
Specifications (3501)
Differential Pressure Range:
0 to 1.0 in. wg
Minimum Setpoint Range:
0 to 1.0" H2O
Output Sensitivity:
5 psi/.02
Average Supply Air Consumption:
43.2 scim at 20 psi
Reset Start Point Range:
0–10 psi
Maximum Setpoint Range:
minimum to 1.0 in. wg
Reset Span Range:
0–7 psi
Maximum Setpoint Range:
6.0 in. wg
OperatingTemperature:
+40/+120°F
Normal Supply Air Pressure:
20.0 psi
StorageTemperature:
-40/+140°F
Minimum Supply air Pressure:
15.0 psi
Maximum Supply Air Pressure:
30.0 psi
12
VAV-SVX02B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
MCP-3631—Rotary
Pneumatic Damper Actuator
Installation Method:
Specifications:
Effective Area:
8 sq in. (52 sq cm)
Normal Rotation:
100 deg
MCP-3631—Rotary
Pneumatic Damper Actuator
Description:
Rotary actuators mounts to a standard
½" diameter shaft by a locking collar
and bushing.
Slide collar onto shaft. Slide actuator
onto shaft noting directional rotation.
Slide bushing onto shaft into actuator,
aligns actuator with damper, lock
collar and bushing set screws, and
install bracket.
Supply Pressure:
0 to 20 psig (138 kPa) operating
30 psig (207 kPa) max
Spring Ranges:
Retracted/extendedTorque
(Based on 0 & 20 psi applied)
Models:
Maintenance:
No routine maintenance is required.
MCP-3631-5000 8–13 psi range
(55–90 kPa) Normally-Closed operation
MCP-3631-8000 3–8 psi range
(21–55 kPa) Normally-Open operation
8–13 psi (55–90 kPa);
68/59 in. lbs (8/7 Nm) @ 90 deg
3–8 psi (21–55 kPa);
25/102 in. lbs (3/12 Nm) @ 90 deg
Supply Connection:
3/16" (5 mm) nipple for ¼" (6 mm)
OD polyethylene tubing
Material:
Body
Glass-filled nylon
Diaphragm Neoprene
Weight:
1.5 lbs (0.68 kg)
Ambient Limits:
Operating -20°F–120°F (-29°C–49°C)
Shipping
-40°F–140°F (-40°C–60°C)
VAV-SVX02B-EN
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Constant-Volume Dual-Duct
Calibration (3011)
This PVR does not require a thermostat
connected to the PVR.
3. Set t-stat to full cool.
ConstantVolume Dual-Duct
Calibration (3011)
4. Set HI thermostat (minimum) to
the desired minimum flow on the
heating deck.
The following procedure must be used
when calibrating a constant-volume
dual-duct unit. See Figure 15 for a
typical piping diagram.
This calibration procedure is used when
a constant volume of air must be
maintained through a unit. On a dual-
duct unit, a constant-volume discharge
sensor is used to measure the air
leaving the unit.The PVR controlling to a
constant-volume of air leaving the unit
uses the discharge sensor to maintain
the specified cfm.
5. Set LO thermostat adjustment knob
on cooling deck (CV deck) to desired
constant-volume.
6. Exercise the system to check flows
for proper operation.
1. Set t-stat to full heat.
2. Set LO thermostat (maximum) to the
desired maximum flow on the
heating deck.
Figure 15–Typical Constant-Volume
Dual-Duct Piping Diagram
Constant-Volume
Flow Ring
LO
HI
Outlet
T
H
L
Cooling
Valve
Heating
Valve
B
Actuator
Volume
Regulator
Normally-
Open
Normally-
Open
M
LO
HI
S
G
20
(137.9)
Two-Pipe
Remote-Mounted
T-Stat
(Direct-Acting)
T
H
L
Restrictor
Tee
B
Actuator
Volume
Regulator
S
M
20
(137.9)
G
S
20
(137.9)
14
VAV-SVX02B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Variable Air Volume Dual-Duct
Calibration (3011)
Figure 16–Typical VAV Dual-Duct Piping Diagram
Variable-Air-Volume Dual-
Duct Calibration (3011)
Figure 16 is a typical piping diagram of
aVAV dual-duct unit.The unit has a
thermostat piped to both pneumatic
volume regulators (PVR) which will
operate the heating deck from a
thermostat signal of 3–8 psi.The cooling
deck will operate from a thermostat
signal of 8–13 psi.With normal
calibration of the PVR, the unit will have
both the heating and cooling deck at
minimum with a thermostat signal of
8 psi.
Outlet
T
H
L
Heating
Cooling
B
Valve
Valve
Actuator
Volume
Regulator
Normally-
Open
Normally-
Open
LO
HI
LO
HI
S
20
(137.9)
G
Two-Pipe
Remote-Mounted
T-Stat
(Direct-Acting)
T
H
L
Restrictor
Tee
In order to have a unit minimum cfm
and still have 0 cfm minimums on both
the heating and cooling deck, special
calibration is required.The PVR has a
“reset start” adjustment knob, which
allows the unit to be calibrated to a
minimum cfm.This is achieved by
crossing over the thermostat ranges.
Figure 17 illustrates this concept.
B
Actuator
Volume
Regulator
S
20
(137.9)
G
20
(137.9)
Figure 17–Example
Thermostat Range: 3–8 psi
HeatingValve = 5 psi range
Thermostat Range: 8–13 psi
CoolingValve = 5 psi range
Unit Minimum 400 cfm
Approximately 1000 cfm divided by 5 psi =
200 cfm/1b*
N.O. HeatingValve
Min 0 cfm
Max 1000 cfm
N.O. CoolingValve
Min 0 cfm
Max 1000 cfm
*Due to the relationship between velocity
pressure and cfm; for both the cooling and
heating PVR, a linear relationship between
cfm and psi does not exist.
To obtain a unit minimum cfm of 400 cfm, the
heating deck volume regulator must have its
thermostat range changed from 3–8 psi to
4–9 psi.This is adjusted by changing the “reset
start” point from 3 psi to approximately 4 psi.
Max
Unit Min
Valve Min
4
The cooling deck volume regulator must have its
thermostat range changed from 8–13 psi to
7–12 psi. This is adjusted by changing the “reset
start” point from 8 psi to approximately 7 psi.
7
8
9
12
By overlapping the thermostat spring ranges, we
were able to have 0 cfm minimum settings on
both the heat and cool deck and still maintain the
required unit minimum cfm of 400 cfm.
The calibration of the PVR is the same as the
normal calibration procedures previously
described in this manual.
VAV-SVX02B-EN
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Constant-Volume
Single-Duct VAV (VCV 3011)
1. Be sure there is 0 psi at the “T” port.
2. Set LO thermostat adjustment knob to
desired unit cfm.
Constant-Volume Single-
Duct VAV (VCV 3011)
This is used when a constant volume of
air is required to supply a zone. A
thermostat is still often required to
modulate a reheat coil to maintain
temperature control.The thermostat is
never connected to the “T” port on the
volume regulator.The following
procedure is used to calibrate this type
of unit with a PVR.
The unit will now modulate to the
calibrated cfm setting. See Figure 18 for
typical constant volume single-duct
piping diagram.
Figure 18–Typical Constant-Volume Single-Duct Piping Diagram
HI
H
L
LO
T
Flow Ring
B
Volume
Regulator
M
S
Actuator
S
20
(137.9)
20
(137.9)
Tee
Two-Pipe
Remote-Mounted
T-Stat
11
(75.8)
(Reverse-Acting)
Airflow
Safety Switch
Stage 1
12.5
(86.2)
Stage 2
14
(96.5)
Stage 3
P.E. Stage Switch(es)
(Normally-Open)
Electric Heater Terminal Box
Literature Order Number
File Number
VAV-SVX02B-EN
SV-TD-VAV000-SVX02B-EN-0302
VAV-SVX02A-EN &VAV-IOM-6
La Crosse
Supersedes
Trane
Stocking Location
An American Standard Company
Trane has a policy of continuous product and product data improvement and reserves the right to change design
and specifications without notice. Only qualified technicians should perform installation and servicing of
equipment referred to in this publication.
For more information contact
your local district office or
e-mail us at [email protected]
Download from Www.Somanuals.com. All Manuals Search And Download.
|