Packaged Cooling with
Electric Heat Rooftop Units
Precedent™
3 - 10Tons — 60 Hz
RT-PRC005-EN
February 2004
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
Introduction
2
4
Features and Benefits
Application Considerations
10
Selection Procedure
Model Number Description
General Data
11
13
14
Performance Data
18
Cooling Performance
Fan Performance
Heat Performance
18
31
56
Controls
59
61
76
85
Electric Power
Dimension andWeights
Mechanical Specifications
RT-PRC005-EN
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Easy Access Panels
Remove two screws for access to the
standardized internal components and
wiring.
Easy-Adjust Idler Arm
With the Easy-Adjust Idler Arm, the belt
and sheaves on belt drive units can be
quickly adjusted without moving the
mounted fan motor.The result is a major
savings in time and money.
Patented Condenser Coil
Precedent boasts a patented 1+1+1
Hybrid coil, permanently gapped for easy
of cleaning.
Unit Cabinet
The compact cabinet with rounded
corners takes up less room and is less
costly to ship. The beveled and ribbed top
is not only aesthetically pleasing, it is
designed to prevent water from pooling.
Single Point Power
ColoredAnd NumberedWiring
A single electrical connection powers the
unit.
You save time and money tracing wires
and diagnosing the unit.
Convertible Units
Sloped Drain Pans
• The units ship in a downflow
configuration.They can be easily
converted to horizontal by simply
moving two panels.
Every Precedent unit has a non-
corrosive, removable, double-sloped
drain pan that’s easy to clean and
reversible to allow installation of drain
trap on either side of the unit.
• Units come complete with horizontal
duct flanges so the contractor doesn’t
have to field fabricate them.These duct
flanges are a time and cost saver.
Compressors
Through the Base Condensate
Precedent™ contains the best
compressor technology available to
achieve the highest possible
performance. Our compressor line
includesTrane built reciprocating and
scrolls.
Every unit includes provisions for through
the base condensate drain connections.
This allows the drain to be connected
through the roof curb instead of a roof
penetration.
Foil-Faced Insulation
Easy Access Panels
All panels in the Evaporator section of the
unit have cleanable foil-faced insulation.
All edges are either captured or sealed to
ensure no fibers get into the airstream.
Easy access panels reduce the number of
possible water entry points.
LowAmbient Cooling
All Precedent microprocessor units have
cooling capabilities down to 0°F as
standard. Electromechanical models
have cooling capabilities to 40°F as built,
or to 0°F by adding the optional low
ambient control (frostat).
Unit Base
For added water integrity, Precedent has
a raised 11/8" lip around the unit’s
downflow supply and return to prevent
water from blowing into the ductwork.
4
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Standardized Components
FlexibleApplications
• Only two roof curbs for the 3-10 ton
Precedent line simplifies curb selection.
• Standard or High Efficiency Cooling
• Electromechanical or ReliaTel
microprocessor controls to meet either
the simple or the more complex
application.
• Components are placed in the same
location on all Precedent™ units.
Familiarize yourself with one Precedent
and you are familiar with every
Precedent.
• Airflow is outstanding.The Precedent
can replace an older machine with old
ductwork and, in many cases, improve
comfort through better air distribution.
• Belt or direct drive — standard or
oversized supply fan motors meet a
wide airflow range.
• Precedent offers ultimate flexibility.
Options and components are not pre-
packaged at the factory. Units are built
to order in our standard “shortest in the
industry” ship cycle time.
Easy Access LowVoltageTerminal Board
Precedent’s LowVoltageTerminal Board
is external to the electrical control cabinet.
It is extremely easy to locate and attach
the thermostat wire.This is another cost
and time saving installation feature.
LowVoltage Connections
The wiring of the low voltage connections
to the unit and the zone sensors is as
simple as 1-1, 2-2, and 3-3.This simplified
system makes it easy for the installer to
wire
Single-Side Service
Single-side service is standard on all
Precedent units.
RT-PRC005-EN
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
• Requires no special tools to run the
Precedent unit through its paces during
testing. Simply place a jumper between
Test 1 andTest 2 terminals on the Low
VoltageTerminal Board and the unit will
walk through its operational steps.The
unit automatically returns control to the
zone sensor after stepping through the
test mode a single time, even if the
jumper is left on the unit.
• As long as the unit has power and the
LED is lit, the Micro is operational.The
light indicates that the Micro is
functioning properly.
Micro Controls
Several years ago,Trane was the first to
introduce microprocessor controls into
the Light Commercial Market.That
design, along with immeasurable
experience, has provided the technology
forTrane’s second-generation ReliaTel™
microprocessor controls.
• Features expanded diagnostic
capabilities when used withTrane’s
Integrated ComfortTM Systems.
• As an energy benefit, softens electrical
‘’spikes’’ by staging on fans,
compressors and heaters.
ReliaTel™ Micro:
• The Intelligent Fallback or Adaptive
Control is a benefit to the building
occupant. If a component goes astray,
the unit will continue to operate at
predetermined temperature set points.
• Provides unit control for heating,
cooling, and ventilating by utilizing input
from sensors that measure outdoor
and indoor temperature.
• Intelligent Anticipation is a standard
feature of the Micro. Functioning
constantly, the Micro and zone sensors
work together in harmony, to provide
tight comfort control.
• Improves quality and reliability through
the use of time-tested microprocessor
controls and logic.
• Prevents the unit from short cycling,
considerably improving compressor
life.
Electromechanical Controls
• For the simpler job that does not
require a building automation system,
or expanded diagnostics capabilities,
Precedent offers electromechnical
controls. This 24-volt control includes
the control transformer, contactor
pressure lugs for power wiring.
• Ensures that the compressor will run for
a specific amount of time, which allows
oil to return for better lubrication,
enhancing the reliability of the
compressor.
• Reduces the number of components
required to operate the unit, thereby
reducing possibilities for component
failure.
• Eliminates the need for field-installed
components with its built-in anti-short-
cycle timer, time delay relay and
minimum ‘’on’’ time controls.These
controls are factory tested to assure
proper operation.
6
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Economizer
Factory-installed Options
Equipped with either dry bulb, reference
or comparative enthalpy sensing, this
feature provides free cooling as the
outdoor temperature and/or humidity
decreases. Economizers, correctly
installed, offer a valuable energy savings.
Factory-installed economizers save time
and ensure proper installation.
Dehumidification (Hot Gas Reheat)
Option
This option allows for increased outdoor
air ventilation. It reduces humidity levels
while increasing comfort level in the air
space. Cooling can operate without a
demand for dehumidification.The hot gas
reheat coil is designed to deliver
Through the Base Electrical Utility
Access
maximum reheat temperatures and
pivot to allow for easy access cleaning.
Factory provided through the base
openings simplify wiring and piping.
Because these utility openings frequently
minimize the number of roof
penetrations, the integrity of roofing
materials is enhanced.
Phase Monitor
Phase monitor shall provide 100%
protection for motors and compressors
against problems caused by phase loss,
phase imbalance, and phase reversal.
Phase monitor is equipped with an LED
that provides an ON or FAULT indicator.
Hinged Access Doors
Clogged Filter/Fan Fail Switches
These doors permit easy access to the
filter, fan/heat, and compressor/control
sections. They reduce the potential roof
damage from screws or sharp access
door corners.
These sensors allow a zone sensor
service light or Integrated Comfort
System to indicate a dirty filter or a fan
that’s not working.The field installation
charges for these valuable feedback
devices often eliminate them from
consideration. Factory installation can
make such features a good investment.
Unit Mounted Disconnect or Circuit
Breaker
Codes require a method of assured unit
shutdown for servicing. Field-installed
disconnects sometimes interfere with
service access. Factory installation of unit
disconnects reduces costs, assures
proper mounting and provides the
opportunity to upgrade to unit circuit
breaker protection.
Trane Communication Interface
Available factory or field-installed.This
module when applied with ReliaTel™
easily interfaces withTrane’s Integrated
ComfortTM System.
Unit Disconnect
Convenience Outlet
RT-PRC005-EN
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Quality and ReliabilityTesting
• We perform a 100% coil leak test at the
factory.The evaporator and condenser
coils are leak tested at 200 psig and
pressure tested to 450 psig.
• All Precedent™ designs were
rigorously rain tested at the factory to
ensure water integrity.
• All parts are inspected at the point of
final assembly. Sub-standard parts are
identified and rejected immediately.
• Actual shipping tests were performed
to determine packaging requirements.
Units were test shipped around the
country to determine the best
packaging.
• Every unit receives a 100% unit run test
before leaving the production line to
make sure it lives up to rigorous Trane
requirements.
• Factory shake and drop tests were
used as part of the package design
process to help assure that the unit
arrives at the job site in top condition.
We test designs at our factory not on our
customers!
• Rigging tests include lifting a unit into
the air and letting it drop one foot,
assuring that the lifting lugs and rails
hold up under stress.
VariTrac™
VariTrac
WhenTrane’s changeover VAV System
for light commercial applications is
coupled with Precedent, it provides the
latest in technological advances for
comfort management systems and can
allow thermostat control in every zone
served by VariTrac.
8
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
The following options round-out the
complete line of Precedent™ options:
— 0 - 50% Manual or Motorized
Outside Air
— Hail Protection Quality Coil Guards
— Electric Heaters
— Supply and/or Return Smoke
Detectors
— High Pressure Cutout
(standard on 3-phase models with
scroll compressors and all standard
efficiency 3-ton models)
— Thermal ExpansionValve for a wider
range of applications
— Discharge Air Sensor
— Wide array of Zone Sensors and
Thermostats
— Factory built Roof Curb
— Power Exhaust
— LonTalk Communications Interface
One of Our FinestAssets:
Trane Sales Representatives are a
Support group that can assist you with:
— Product
— Application
— Service
— Training
— Special Applications
— Specifications
— Computer Programs and much more
Precedent has the features and benefits
that make it first class in the light
commercial rooftop market. Designed
with input from field contractors and
engineers, its airflow performance is
outstanding.
Precedent…The same Trane
quality…with added flexibility.
RT-PRC005-EN
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Application
Considerations
Application of this product should be
within the cataloged airflow and cooling
considerations.
Condensate Trap
The evaporator is a draw-thru
configuration. A trap must be field
provided prior to start-up on the cooling
cycle.
LowAmbient Cooling
The Precedent™ line features, with
ReliaTel™ microprocessor controls, low
ambient cooling down to 0F. With
electromechanical controls, Precedent
features low ambient cooling to 40F.
Contact your localTrane Representative
for more assistance with low ambient
cooling applications.
Clearance Requirements
The recommended clearances identified
with unit dimensions should be
maintained to assure adequate service
maximum capacity and peak operating
efficiency. Actual clearances which
appear inadequate should be reviewed
with the localTrane sales personnel.
Barometric Relief
Unit Pitch
This product line offers an optional
barometric relief damper. for use in
conjunction with economizer option. This
accessory consists of gravity dampers
which open with increased pressure. As
the building air pressure increases, the
pressure in the unit return air section
also increases, opening the dampers and
relieving the conditioned space.
These units have reversible sloped
condensate drain pans. Units must be
installed level, any unit slope must be
toward the side of unit where condensate
drain is connected.
NOTE:THE EFFECTIVENESS OF
BAROMETRIC RELIEF DAMPER DURING
ECONOMIZING OPERATION IS SYSTEM
RELATED.
PRESSURE DROP OFTHE RETURN AIR
SYSTEM SHOULD BE CONSIDEREDTO
CONTROL BUILDING PRESSURIZATION.
10
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Selection
Procedures
Cooling Capacity
Step 4
Heating Capacity
In order to select the correct unit which
meets the building’s requirements, the
fan motor heat must be deducted from
the gross cooling capacity.The amount of
heat that the fan motor generates is
dependent on the effort by the motor -
cfm and static pressure.To determine the
total unit static pressure:
Step 1
Step 1
Calculate the building’s total and sensible
cooling loads at design conditions. Use
theTrane calculation methods or any
other standard accepted method.
Calculate the building heating load using
theTrane calculation form or other
standard accepted method.
Step 2
Size the system heating capacity to
Factors used in unit selection:
match the calculated building heating
A
load.The following are building heating
Total Cooling Load: 59 MBh
External Static (duct system)
0.36 wg
requirements:
B
A
Sensible Cooling Load: 40 MBh
Standard Filter 1 in.
fromTable PD-73
0.15 wg
Total heating load of 15 MBH
C
B
Airflow: 2000 cfm
2000 cfm
D
Economizer
0.18 wg
C
Electrical Characteristics: 460/60/3
(100% Outside Air)
fromTable
PD-73
460 volt/3 phase Power Supply
E
Summer Design Conditions: Entering
Evaporator Coil: 80 DB, 67WB Outdoor
Ambient: 95
The electric heat accessory capacities
are listed inTable PD-74 From the table,
a 6 kW heater will deliver 20.48 MBH at
480 volts. In order to determine capacity
at 460 volts, the heater voltage
correction factor fromTable PD-75 must
be used.Therefore, 20.48 MBH x .9118
(voltage correction factor) = 18.80 MBH.
Electric Heater Size 6 kW 0.056 wg
fromTable PD-73
F
External Static Pressure: 0.36 in. wg
(reference “Heating Capacity” section on
this page for determination of heater
size)
G
Downflow Configuration
H
High Efficiency
Total Static Pressure
0.75 wg
I
Economizer
Note:The Evaporator Fan Performance
Table PD-50 has deducted the pressure
drop for a 1 in. filter already in the unit
(see note belowTable PD-24).Therefore,
the actual total static pressure is 0.75 -
0.15 (fromTable PD - 73) = 0.60 wg.
Air Delivery Selection
External static pressure drop through
the air distribution system has been
calculated to be 0.60 inches of water.
EnterTable PD-50 for aTHC060A4 at
2000 cfm and 0.60 static pressure.The
standard direct drive motor will give the
desired airflow at a rated bhp of 0.90
and 998 rpm.
Step 2
As a starting point, a rough determination
must be made of the size of the unit.The
final selection will be made after
examining the performance at the given
conditions. Divide the total cooling load by
nominal BTUH per ton (12 MBh per ton);
then round up to the nearest unit size.
With 2000 cfm and 0.60 wg.
Table PD-50 shows .90 bhp for this unit.
Note below the table gives a formula to
calculate Fan Motor Heat,
59 MBh / 12 MBh = approx. 5 tons
2.829 x bhp + .4024 = MBH.
2.829 x .83 + .4024 = 2.75 MBH.
Step 3
Table PD-15 shows that aTHC060A4 has
a gross cooling capacity of 62.4 MBh and
48.4 MBh sensible capacity at 2000 cfm
and 95 DB outdoor ambient with 80 DB,
67 WB air entering the evaporator.
Now subtract the fan motor heat from
the gross cooling capacity of the unit:
NetTotal Cooling Capacity
= 62.4 MBH - 2.95 = 59.45 MBH.
Net Sensible Cooling Capacity
= 48.4 MBH - 2.95 = 45.45 MBH.
To Find Capacity at Intermediate
Conditions Not in theTable
Step 5
When the design conditions are between
two numbers that are in the capacity
table, interpolation is required to
approximate the capacity. Note:
Extrapolation outside of the table
conditions is not recommended.
If the performance will not meet the
required load of the building’s total or
sensible cooling load, try a selection at
the next higher size unit.
RT-PRC005-EN
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Selection
Procedure
Dehumidification Selection
Step 3: Determine reheat
temperature rise
Go to PD-78 for reheat temperature rise:
26.7°F db
Typical 10 tonTHC120A
2000 cfmTotal Supply airflow
800 cfm Outside Air (40%)
1200 cfm Return Air
0.41” External Static Pressure
68°F DB,
67°F WB
OA Conditions
Part load day and raining
68°F db
OA
75°F DB,
RA'
52% RH
67°F wb
MA' 72.2°F DB
65°F WB
RA’ conditions
75°F db
63°F wb
OA
47°F DB
SA'
MA'
RA'
73°F DB
SA
Step 1: Determine the mixed/
entering air condition (MA’)
MA’ = (% outside air*outside air dry-bulb
temperature) + (% return air*return air
dry-bulb temperature)
SA
REHEAT
SA'
MA’ = (0.40*68°F) + (0.60*75°F)
MA’ = 72.20°F db
Chart C-1
Note: Repeat for wet-bulb
temperature (wb).
Plot on psychrometric chart.
Note: Reheat temperature rise is based
on supply airflow and leaving evaporator
coil temperature.
Step 5: Determine static pressure
drop add for reheat
MA’
72.2°F db
65°F wb
Table PD-73 shows a static pressure drop
of 0.09” wc 0.41”+ 0.09” = 0.5” wc
Step 4: Determine leaving unit
temperature
Reheat temperature (obtained in step 3)
+ SA’
26.7°F db + 47°F = 73.7°F db
SA=73.7°F
Table PD-65 indicates that a standard
motor and field installed low static drive
kit is needed for this airflow and static
pressure range.
Step 2: Determine leaving unit
temperature
Leaving UnitTemperature = SA’
Utilize theTOPSS™ program to
determine the leaving unit temperature.
Consider Chart C-1. If the space relative
humidity is equal to or above the space
relative humidity setpoint, the
45°F db
44°F wb
43°F dp
Dehumidification Option will:
• Energize compressor or both
compressors (2 stage compressor units).
• Hot gas reheat valve is energized and
hot gas is diverted to the reheat coil.
• Dehumidification/reheat is terminated
when space humidity is reduced to 5%
below relative humidity setpoint.
At MA’, air enters the RTU.The RTU filters,
cools, and dehumidifies the air as it
moves through the evaporator coil. Air
leaves the evaporator coil saturated at
the preset dew point condition (SA’) and
is reheated by the hot gas reheat coil to
deliver 73.7°F (SA) supply air to the
space.
12
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Model
Number
Description
T
1
S
2
C 036 A
3 4,5,6 7
3
8
R
9
B
A
**
C
0
0
0
A
1
0
0
0
1
A
1
10 11 12,13 14 15 16 17 18 19 20 21 22 23 24 25
DIGIT 1 - Unit Function
DIGITS 12, 13 - Service Sequence
** Factory Assigned
DIGIT 20 - Convenience Outlet
T = DX Cooling
=
0 = No Convenience Outlet
A = Unpowered Convenience Outlet
B = Powered Convenience Outlet
(3 phase only)
DIGIT 2 - Efficiency
DIGIT 14 - Fresh Air Selection
S = Standard Efficiency
H = High Efficiency
0 = No Fresh Air
A = Manual Outside Air Damper 0-50%
B = Motorized Outside Air Damper 0-50%
C = Economizer, Dry Bulb 0-100%
without Barometric Relief
DIGIT 21 - Communications Options
0 = No Communications Interface
1 = Trane Communications Interface
2 = LonTalk® Communications Interface
3 = Novar 2024 Controls
DIGIT 3 - Airflow
C = Convertible
D = Economizer, Dry Bulb 0-100%
with Barometric Relief
E = Economizer, Reference Enthalpy
0-100% without Barometric Relief
F = Economizer, Reference Enthalpy
0-100% with Barometric Relief
G = Economizer, Comparative Enthalpy
0-100% without Barometric Relief
H = Economizer, Comparative Enthalpy
0-100% with Barometric Relief
DIGITS 4,5,6 - Nominal Gross Cooling
Capacity (MBh)
4 = Novar 3051 Controls
DIGIT 22 - Refrigeration System Option
036 =
048 =
060 =
072 =
090 =
092 =
102 =
120 =
3 Ton
4 Ton
0 = Standard Refrigeration System
A = Thermal Expansion Valve (TXV)
B = Dehumidification (Hot Gas Reheat
Coil)
5 Ton
6 Ton
7½ Ton, Single Compressor
7½ Ton, Dual Compressor
8½ Ton
DIGIT 23 - Refrigeration Controls
DIGIT 15 - Supply Fan/Drive Type/Motor
10 Ton
0 = No Refrigeration Control
1 = High Pressure Control
2 = Frostat
0 = Standard Drive
1 = Oversized Motor
2 = Optional Belt Drive Motor
DIGIT 7 - Major Design Sequence
A = First
3 = Crankcase Heater
4 = High Pressure Control and Frostat
5 = High Pressure Control and Crankcase
Heater
6 = Frostat and Crankcase Heater
7 = High Pressure Control, Frostat and
Crankcase Heater
DIGIT 16 - Hinged Service Access/Filters
DIGIT 8 - Unit Voltage
0 = Standard Panels/Standard Filters
A = Hinged Access Panels/Standard Filters
B = Standard Panels/2” Pleated Filters
C = Hinged Access Panels/2” Pleated
Filters
1 = 208-230/60/1
3 = 208-230/60/3
4 = 460/60/3
W= 575/60/3
K = 380/60/3
DIGIT 24 - Smoke Detector
DIGIT 17 - Condenser Coil Protection
DIGIT 9 - Unit Controls
0 = No Smoke Detector
A = Return Air Smoke Detector
B = Supply Air Smoke Detector
C = Supply and Return Air Smoke
Detectors
0 = Standard Coil
E = Electromechanical
R = ReliaTel™Microprocessor
1 = Standard Coil with Hail Guard
2 = Epoxy Coated Condenser Coil
3 = Epoxy Coated Condenser Coil with
Hail Guard
DIGIT 10 - Heating Capacity
0 = No Electric Heat
A = 5 kW (1 phase)
B = 6 kW (3 phase)
C = 9 kW (3 phase)
D = 10 kW (1 phase)
E = 12 kW (3 phase)
F = 14 kW (1 phase)
G = 18 kW (1 and 3 phase)
J = 23 kW (3 phase)
K = 27 kW (3 phase)
N = 36 kW (3 phase)
P = 54 kW (3 phase)
DIGIT 25 - Monitoring Controls
DIGIT 18 - Through the Base Provisions
0 = No Monitoring Control
1 = Clogged Filter Switch
2 = Fan Failure Switch
3 = Discharge Air Sensing Tube
4 = Clogged Filter Switch and Fan Fail
Switch
5 = Clogged Filter Switch and Discharge
Air Sensing Tube
6 = Fan Fail Switch and Discharge Air
Sensing Tube
0 = No Through the Base Provisions
A = Through the Base Electric
DIGIT 19 - Disconnect/Circuit Breaker/
Phase Monitor (3 phase only)
0 = No Disconnect/NoCircuit Breaker/No
Phase Monitor
1 = Unit Mounted Non-Fused Disconnect
2 = Unit Mounted Circuit Breaker
3 = Phase Monitor
4 = Phase Monitor & Non-Fused
Disconnect Switch
5 = Phase Monitor & Circuit Breaker
7 = Clogged Filter and Fan Fail Switches
and Discharge Air Sensing Tube
8 = Novar Return Air Sensor
DIGIT 11 - Minor Design Sequence
A = First Sequence
Example:
ModelnumberTSC036A3RBA**C000A10001A1describesaunitwiththefollowingcharacteristics:DXCooling,3tonnominalcoolingcapacity,208-230/60/3powersupply,ReliaTel™ controls,6kW
electric heater model. 0-100% dry bulb economizer without barometric relief, standard direct drive motor, standard access panels/filters, standard condenser coil with no coil protection, through the
base electric, non-fused disconnect, no convenience outlet or communications interface, standard refrigeration coil, high pressure control, return air smoke detector, and clogged filter switch.
RT-PRC005-EN
13
Download from Www.Somanuals.com. All Manuals Search And Download.
General
Data
(3 - 5Ton)
Standard Efficiency
Table GD - 1 — General Data
3Ton Convertible Units
TSC036A1, A3, A4, AW
4Ton Convertible Units
TSC048A1 TSC048A3, A4, AW
5Ton Convertible Units
TSC060A1 TSC060A3, A4, AW TSC060AK
Cooling Performance1
Gross Cooling Capacity
SEER2
37,400
10.75
50,300
10.1
49,200
10.0
63,100
9.9
63,100
10.2
63,100
10.2
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
System Power (kW)
1,200/1,200
36,000
1,600/1,600
48,000
5.28
1,600/1,600
47,000
2,000/2,000
60,000
6.86
2,000/2,000
60,000
6.78
2,000/2,000
60,000
6.78
3.798
5.40
Compressor
No./Type
Outdoor Sound Rating (dB)3
1/Recip.
83
1/Scroll
86
1/Scroll
82
1/Scroll
84
1/Scroll
84
1/Scroll
84
Outdoor Coil —Type
Tube Size (in.) O.D.
Face Area (sq ft)
Rows/FPI
Lanced
0.3125
7.19
Lanced
0.3125
6.17
Lanced
0.3125
9.59
Lanced
0.3125
8.81
Lanced
0.3125
8.81
Lanced
0.3125
8.81
2/17
2/17
1/17
2/17
2/17
2/17
Indoor Coil —Type
Tube Size (in.)
Lanced
0.3125
Lanced
0.3125
Lanced
0.3125
Lanced
0.3125
Lanced
0.3125
Lanced
0.3125
Face Area (sq ft)
5.67
6.68
6.17
5.00
5.00
5.00
Rows/FPI
2/16
3/16
3/16
3/16
3/16
3/16
Refrigerant Control
Drain Connection No./Size (in.)
Short Orifice
1/¾ NPT
Short Orifice
1/¾ NPT
Short Orifice
1/¾ NPT
Short Orifice
1/¾ NPT
Short Orifice
1/¾ NPT
Short Orifice
1/¾ NPT
Outdoor Fan —Type
No. Used/Diameter (in.)
DriveType/No. Speeds
CFM
Propeller
1/22
Direct/1
2550
Propeller
1/22
Direct/1
2850
Propeller
1/22
Direct/1
3610
Propeller
1/22
Direct/1
3470
Propeller
1/22
Direct/1
3470
Propeller
1/22
Direct/1
3470
No. Motors/HP
1/.20
1/.33
1/.33
1/.33
1/.33
1/.40
Motor RPM
1115
1115
1115
1115
1115
1115
Direct Drive Indoor Fan —Type
No. Used
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
Diameter xWidth (in.)
DriveType/No. Speeds
No. Motors
10 x 10
Direct/2
1
11 x 11
Direct/2
1
11 x 11
Direct/2
1
11 x 11
Direct/2
1
11 x 11
Direct/2
1
12x11/–
Direct/2
1
Motor HP (Standard/Oversized)
Motor RPM (Low/High Speed)
Oversized Motor RPM
(Low/High Speed)
Motor Frame Size
(Standard/Oversized)
.33/.50
950/1060
.60/.80
930/1000
.60/.80
930/1000
.90/1.00
985/1100
.90/1.00
985/1100
1.0/–
935/1100
1100/1145
48/48
1000/1100
48/48
1000/1100
48/48
1080/1135
48/48
1080/1135
48/48
—
48/—
Belt Drive Indoor Fan —Type
No. Used
FC Centrifugal
—
—
—
—
—
—
—
—
FC Centrifugal
—
—
—
—
—
—
—
—
FC Centrifugal
—
—
—
—
—
—
—
—
1
1
1
Diameter xWidth (in.)
DriveType/No. Speeds
No. Motors
Motor HP
Motor RPM
11 x 11
11 x 11
Belt/Variable Speed
11 x 11
Belt/Variable Speed
Belt/Variable Speed6
1
1
1
1.00
1750
56
1.00
1750
56
1.00
1750
56
Motor Frame Size
Filters —Type Furnished 7
Throwaway
(2) 20 x 25 x 1
Throwaway
(2) 20 x 25 x 1
Throwaway
(2) 20 x 25 x 1
Throwaway
(2) 20 x 25 x 1
Throwaway
(2) 20 x 25 x 1
Throwaway
(2) 20 x 25 x 1
(No.) Size Recommended (in.)
Refrigerant Charge (Lbs of R-22)4
3.8
4.4
3.8
4.7
4.9
4.9
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is
basedonARIStandard210/240exceptAK(380V/60Hz).
2. SEER is rated at ARI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-72.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5. TSC036A1SEERis10.5.
6. Belt Drive Motor is not available for TSC036A1.
7. Optional 2” Pleated Filters also available.
8. TSC036A1SystemPower(kW)is3.91.
14
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
General
Data
(6 - 10Ton)
Standard Efficiency
Table GD - 2— General Data
6Ton
Convertible Units
7½Ton
Convertible Units
8½Ton
Convertible Units
10Ton
Convertible Units
TSC072A3, A4, AW, AK TSC090A3,A4,AW, AK TSC092A3, A4, AW
TSC102A3, A4, AW, AK TSC120A3, A4, AW, AK
Cooling Performance1
Gross Cooling Capacity
EER2
72,000
10.3
95,000
10.3
92,000
10.3
105,000
10.3
118,000
10.46
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Part LoadValue (IPLV)3
System Power (kW)
Compressor
2,400/2,100
3,000/2,625
3,000/2,625
87,000
11.18
3,400/3,000
100,0007
11.98
4,000/3,200
114,0007
11.58
69,000
90,000
—
—
6.7
8.74
8.45
9.719
10.969
No./Type
1/Scroll
88
Lanced
0.3125
13.88
1/Scroll
90
Lanced
0.3125
17.00
2/Scrolls
87
Lanced
0.3125
2/Scrolls
86
Lanced
0.3125
2/Scrolls
86
Lanced
0.3125
Outdoor Sound Rating (dB)4
Outdoor Coil —Type
Tube Size (in.) O.D.
Face Area (sq ft)
17.00
19.83
19.83
Rows/FPI
2/17
3/17
2/17
2/17
2/17
Indoor Coil —Type
Tube Size (in.)
Lanced
0.3125
9.89
Lanced
0.3125
9.89
Lanced
0.3125
9.89
Lanced
0.3125
12.36
Lanced
0.3125
12.36
Face Area (sq ft)
Rows/FPI
2/16
3/16
3/16
3/16
4/16
Refrigerant Control
Drain Connection No./Size (in.)
Outdoor Fan —Type
No. Used/Diameter (in.)
DriveType/No. Speeds
CFM
Short Orifice
1/¾ NPT
Propeller
1/26
Short Orifice
1/¾ NPT
Propeller
1/26
Short Orifice
1/¾ NPT
Propeller
1/26
Direct/1
6500
Short Orifice
1/¾ NPT
Propeller
1/26
Direct/1
7100
Short Orifice
1/¾ NPT
Propeller
1/26
Direct/1
7000
Direct/1
6100
Direct/1
6200
No. Motors/HP
Motor RPM
1/0.7011
1115
1/0.7011
1115
1/0.70
1115
1/0.75
1115
1/0.75
1115
Belt Drive Indoor Fan —Type
No. Used
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
Diameter xWidth (in.)
DriveType/No. Speeds
No. Motors
Motor HP (Standard/Oversized)
Motor RPM (Standard/Oversized)
Motor Frame Size
12 x 12
Belt/Variable Speed
1
12 x 12
Belt/Variable Speed
1
12 x 12
Belt/Variable Speed
1
15 x 15
Belt/Variable Speed
1
15 x 15
Belt/Variable Speed
1
1.00/2.0012
1750
2.00/3.00
1750
2.00/3.00
1750
2.00/3.00
1750
3.00/5.00
1750/3450
56
56
56
56
56
Filters —Type Furnished 10
(No.) Size Recommended (in.)
Refrigerant Charge (Lbs of R-22)5
Throwaway
(4) 16 x 25 x 2
7.1
Throwaway
(4) 16 x 25 x 2
11.5
Throwaway
(4) 16 x 25 x 2
6.2 Circuit 1
3.4 Circuit 2
Throwaway
(4) 20 x 25 x 2
7.9 Circuit 1
4.0 Circuit 2
Throwaway
(4) 20 x 25 x 2
7.2 Circuit 1
5.3 Circuit 2
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is
basedonARIStandard210/240exceptAK(380V/60Hz).
2. SEER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb ar ARI rated cfm.
4. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-72.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. EER shown is for downflow airflow. EER for horizontal airflow is 10.3.
7. ARI Net Cooling Capacity shown is for downflow airflow. Cooling Capacity for Horizontal airflow TSC102A is 99,000; TSC120A is 112,000.
8. Integrated Part Load Value (IPLV) shown is for downflow airflow. IPLV for Horizontal airflow TSC092A is 10.8, TSC102A is 11.5; TSC120A is 11.0.
9. System Power (kW) shown is for downflow airflow. System Power (kW) forHorizontal airflow TSC102A is 9.61; for TSC120A is 10.87.
10. Optional 2” Pleated Filters also available.
11. Outdoor motor is 0.75 hp for AK (380V/60 Hz units).
12. Standard indoor motor is 2.00 hp for AK (380V/60 Hz) units.
RT-PRC005-EN
15
Download from Www.Somanuals.com. All Manuals Search And Download.
General
Data
(3 - 5Ton)
High Efficiency
Table GD - 3 — General Data
3Ton
4Ton
5 Ton
Convertible Units
THC036A1,A3,A4,AW
Convertible Units
THC048A1,A3,A4,AW
Convertible Units
THC060A1
THC060A3,A4,AW
Cooling Performance1
Gross Cooling Capacity
38,000
49,800
62,100
62,400
SEER / EER2
12.5/—
12.0/—
11.8/—
12.0/ —
Nominal CFM / ARI Rated CFM
1,200/1,200
1,600/1,600
2,000/2,000
2,000/2,000
ARI Net Cooling Capacity
System Power (kW)
Compressor
36,600
3.33
47,500
4.48
59,000
5.73
59,500
5.56
No./Type
1/Climatuff Scroll
83
1/Climatuff Scroll
85
1/Climatuff Scroll
84
1/Climatuff Scroll
84
Outdoor Sound Rating (dB)3
Outdoor Coil —Type
Tube Size (in.) O.D.
Face Area (sq ft)
Lanced
0.3125
7.19
Lanced
0.3125
9.59
Lanced
0.3125
10.96
Lanced
0.3125
10.96
Rows/FPI
2/17
3/17
3/17
3/17
Indoor Coil —Type
Tube Size (in.)
Lanced
0.3125
6.68
Lanced
0.3125
6.68
Lanced
0.3125
7.71
Lanced
0.3125
7.71
Face Area (sq ft)
Rows/FPI
3/16
4/16
4/16
4/16
Refrigerant Control
Drain Connection No./Size (in.)
Outdoor Fan —Type
No. Used/Diameter (in.)
DriveType/No. Speeds
CFM
Short Orifice
1/¾ NPT
Propeller
1/22
Short Orifice
1/¾ NPT
Propeller
1/22
Short Orifice
1/¾ NPT
Propeller
1/22
Direct/1
3170
Short Orifice9
1/¾ NPT
Propeller
1/22
Direct/110
2550
Direct/110
3050
Direct/110
3370
No. Motors/HP
1/.20
1/.33
1/.33
1/.33
Motor RPM
1115
1115
1115
1115
Direct Drive Indoor Fan —Type
No. Used
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
Diameter xWidth (in.)
DriveType/No. Speeds
No. Motors
10 x 10
Direct/2
1
11 x 11
Direct/2
1
11 x 11
Direct/2
1
11 x 11
Direct/2
1
Motor HP (Standard/Oversized)
Standard Motor RPM (Low/High Speed)
Oversized Motor RPM (Low/High Speed)
Motor Frame Size (Standard/Oversized)
Belt Drive Indoor Fan —Type
No. Used
.33/.50
950/1060
1100/1145
48/48
FC Centrifugal
1
.60/.80
930/1000
1000/1100
48/48
FC Centrifugal
1
.90/1.00
985/1100
1080/1135
48/48
.90/1.00
985/1100
1080/1135
48/48
FC Centrifugal
1
—
—
Diameter xWidth (in.)
11 x 11
11 x 11
—
11 x 11
DriveType/No. Speeds
Belt/Variable Speed 6
1
Belt/Variable Speed 6
1
—
Belt/Variable Speed
No. Motors
—
1
Motor HP
Standard Motor RPM
Motor Frame Size
1.00
1750
56
1.00
1750
56
—
—
—
1.00
1750
56
Filters —Type Furnished 7
(No.) Size Recommended (in.)
Optional Hot Gas Reheat Coil -Type
Tube Size (in.) OD
Face Area (sq. ft)
Rows/FPI
Refrigerant Charge (Lbs of R-22)4
Standard
Throwaway
(2) 20 x 25 x 1
Lanced
0.375
Throwaway
(2) 20 x 25 x 1
Lanced
0.375
Throwaway
(2) 20 x 30 x 1
Throwaway
(2) 20 x 30 x 111
Lanced
0.375
—
—
—
—
2.22
1/16
2.22
1/16
2.22
2/16
5.38
5.3
7. 7 5
8.5
7.9
—
8.4
10.7
Optional Hot Gas Reheat Coil
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program,
whichisbasedonARIStandard210/240.
2. EER and SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-72.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5. Refrigerant Charge shown is for 3 phase. 1 phase Refrigerant Charge is 8.1.
6. Belt Drive Motor is not available for THC036A1, THC048A1.
7. Optional 2” Pleated Filters also available.
8. Refrigerant Charge shown is for 3 phase. 1 phase Refrigerant Charge is 4.5.
9. TXV is supplied from the factory as standard with the Dehumidification (Hot Gas Reheat) option.
10. With Dehumidification (Hot Gas Reheat) option: Direct/2.
11. 2" pleated filters is a factory installed option. 2" pleated filters is standard with the Dehumidification (Hot Gas Reheat) option.
16
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
General
Data
(6 - 10Ton)
High Efficiency
Table GD - 4— General Data
6Ton
7½Ton
8½Ton
10Ton
Convertible Units
THC072A3, A4, AW
Convertible Units
THC092A3, A4, AW
Convertible Units
THC102A3, A4. AW
Convertible Units
THC120A3, A4, AW
Cooling Performance1
Gross Cooling Capacity
EER2
73,000
11.56
94,000
11.56
103,000
11.56
117,000
11.26
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Part LoadValue (IPLV)3
System Power (kW)
Compressor
2,400/2,100
3,000/2,625
90,00010
11.98
3,400/3,000
98,00010
12.18
4,000/3,200
109,00010
12.08
70,000
—
6.097
7.837
8.527
9.737
No./Type
1/Climatuff Scroll
2/Climatuff Scrolls
91
2/Climatuff Scrolls
89
2/Climatuff Scrolls
88
Outdoor Sound Rating (dB)4
Outdoor Coil —Type
Tube Size (in.) O.D.
Face Area (sq ft)
89
Lanced
0.3125
17.00
Lanced
0.3125
17.50
Lanced
0.3125
19.83
Lanced
0.3125
27.21
Rows/FPI
3/17
3/17
3/17
3/17
Indoor Coil —Type
Tube Size (in.)
Lanced
0.3125
9.89
Lanced
0.3125
12.36
Lanced
0.3125
12.36
Lanced
0.3125
12.36
Face Area (sq ft)
Rows/FPI
3/16
3/16
4/16
5/16
Refrigerant Control
Drain Connection No./Size (in.)
Outdoor Fan —Type
No. Used/Diameter (in.)
DriveType/No. Speeds
CFM
Short Orifice
1/¾ NPT
Propeller
1/26
Direct/1
6100
Short Orifice
1/¾ NPT
Propeller
1/26
Direct/1
6200
Short Orifice
1/¾ NPT
Propeller
1/26
Direct/1
6600
Short Orifice
1/¾ NPT
Propeller
1/26
Direct/1
7000
No. Motors/HP
Motor RPM
1/0.70
1075
1/0.70
1075
1/0.75
1075
1/0.75
1075
Belt Drive Indoor Fan —Type
No. Used
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
FC Centrifugal
1
Diameter xWidth (in.)
DriveType/No. Speeds
No. Motors
12 x 12
Belt/Variable Speed
1
15 x 15
Belt/Variable Speed
1
15 x 15
Belt/Variable Speed
1
15 x 15
Belt/Variable Speed
1
Motor HP (Standard/Oversized)
Motor RPM (Standard/Oversized)
Motor Frame Size
1.00/2.00
1750
56
2.00/3.00
1750
2.00/3.00
1750
3.00/5.00
1750/3450
56
56
56
Filters —Type Furnished 9
(No.) Size Recommended (in.)
Optional Hot Gas Reheat Coil —Type
Tube Size (in.) OD
Throwaway
(4) 16 x 25 x 2
—
Throwaway
(4) 20 x 25 x 2
Lanced
0.375
Throwaway
(4) 20 x 25 x 2
Lanced
0.375
Throwaway
(4) 20 x 25 x 2
Lanced
0.375
—
Face Area (sq. ft.)
—
5.19
5.19
5.19
Rows/FPI
Refrigerant Charge (Lbs of R-22)5
—
10.7
2/16
6.4 Circuit 1
6.2 Circuit 2
2/16
7.4 Circuit 1
7.1 Circuit 2
2/16
11.0 Circuit 1
7.3 Circuit 2
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes
the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is
basedonARIStandard210/240.
2. SEER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb ar ARI rated cfm.
4. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-72.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. EER shown is for downflow airflow. EER for horizontal airflow: THC072A - 11.3, THC092A and THC102A - 11.3, THC120A - 10.7.
7. System Power (kW) shown is for downflow airflow. System Power (kW) for horizontal airflow: THC072A - 6.2, THC092A - 7.88, THC102A - 8.58, THC120A - 10.09.
8. Integrated Part Load Value (IPLV) shown is for downflow airflow. IPLV for horizontal airflow: THC092A - 11.5, THC102A - 11.6, THC120A - 11.5.
9. Optional 2” Pleated Filters also available.
10. Net Cooling Capacity shown is for downflow airflow. Net Cooling for horizontal airflow: THC092A - 89,000, THC102A - 97,000, THC120A - 108,000.
RT-PRC005-EN
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance (3, 4Ton)
Data
Standard Efficiency
Table PD-1 — Gross Cooling Capacities (MBH) 3 Ton Single/Three Phase TSC036A1, A3, A4, AW
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 34.6 29.0 38.6 22.3 40.6 14.7 31.2 27.3 36.6 21.1 39.5 13.8 28.2 25.6 33.4 19.6 37.8 12.9 25.1 24.1 29.6 18.2 35.5 11.9
80 35.6 35.0 38.8 27.3 41.0 20.2 32.6 32.6 36.8 26.6 39.8 19.5 30.0 30.0 33.5 25.2 38.0 18.5 27.3 27.3 29.9 23.5 35.6 17.5
1080
1200
1320
85
37.6 37.6 39.2 32.5 41.5 24.7 35.6 35.6 37.2 32.2 40.1 24.2 32.8 32.8 34.2 31.0 38.2 23.8 30.1 30.1 30.7 29.3 35.8 23.0
90 39.3 39.3 39.7 37.6 42.0 29.2 37.8 37.8 37.9 37.6 40.4 29.1 35.7 35.7 35.7 35.7 38.5 28.9 33.0 33.0 32.9 32.9 36.0 28.4
75 35.6 30.9 39.0 22.8 40.9 14.9 32.2 29.2 37.3 22.1 39.8 14.1 29.0 27.5 34.3 20.7 38.2 13.1 25.9 25.9 30.4 19.0 36.0 12.1
80 36.7 36.7 39.3 28.4 41.4 20.6 34.3 34.3 37.4 28.1 40.2 20.3 31.4 31.4 34.5 26.9 38.4 19.3 28.6 28.6 30.7 25.2 36.1 18.3
85 38.7 38.7 39.7 33.9 41.9 25.3 37.0 37.0 37.9 34.0 40.5 25.0 34.5 34.5 35.3 33.2 38.7 24.8 31.5 31.5 31.7 31.6 36.3 24.2
90 40.2 40.2 40.4 39.2 42.3 30.1 38.8 38.8 38.8 38.8 40.9 30.2 37.1 37.1 37.0 37.0 39.1 30.3 34.6 34.6 34.6 34.6 36.6 30.0
75 36.4 32.6 39.4 23.5 41.1 15.1 33.2 31.0 37.7 23.0 40.1 14.3 29.8 29.3 34.9 21.8 38.5 13.4 26.8 26.8 30.9 20.0 36.3 12.4
80
37.7 37.7 39.7 29.4 41.6 20.9 35.7 35.7 37.9 29.3 40.4 21.2 32.7 32.7 35.2 28.5 38.7 19.9 29.8 29.8 31.4 26.8 36.5 19.0
85 39.4 39.4 40.2 35.2 42.1 25.9 37.9 37.9 38.5 35.6 40.8 25.7 35.9 35.9 36.2 35.3 39.1 25.7 32.9 32.9 32.9 32.9 36.7 25.3
90 40.8 40.8 40.9 40.5 42.6 30.8 39.7 39.7 39.6 39.6 41.2 31.2 38.0 38.0 38.0 38.0 39.5 31.6 35.9 35.9 35.9 35.9 37.1 31.5
75
37.0 34.1 39.7 24.0 41.3 15.3 34.1 32.8 38.0 23.7 40.3 14.5 30.6 30.6 35.5 22.7 38.7 13.6 27.7 27.7 31.4 21.0 36.6 12.6
80 38.4 38.4 40.0 30.3 41.8 21.2 36.7 36.7 38.3 30.5 40.8 21.0 33.9 33.9 35.8 30.0 39.0 20.4 30.8 30.8 32.0 28.4 36.8 19.7
85 40.0 40.0 40.6 36.3 42.4 26.4 38.7 38.7 39.0 37.0 41.2 26.7 36.8 36.8 36.8 36.8 39.4 26.6 34.2 34.2 34.2 34.2 37.0 26.4
90 41.4 41.4 41.4 41.4 42.9 31.6 40.3 40.3 40.3 40.3 41.5 32.1 38.7 38.7 38.7 38.7 39.9 32.7 36.7 36.7 36.7 36.7 37.6 33.0
1440
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-2 — Gross Cooling Capacities (MBH) 4 Ton Single Phase TSC048A1
AmbientTemperature (F)
85
95
105
67
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 45.5 38.7 52.4 30.0 56.4 20.1 41.6 36.6 49.0 28.3 54.4 18.9 37.6 34.5 44.4 26.7 51.8 17.5 33.5 32.3 39.8 24.5 48.0 15.8
80 46.5 46.5 52.5 37.6 56.8 28.1 43.2 43.2 49.1 35.9 54.8 26.7 39.9 39.9 44.6 33.8 52.0 25.2 36.5 36.5 40.1 31.6 48.2 23.4
85 50.3 50.3 53.0 45.1 57.4 34.9 47.0 47.0 49.7 43.7 55.0 33.9 43.6 43.6 45.3 41.6 52.2 32.8 40.2 40.2 41.0 39.5 48.3 31.0
90 53.3 53.3 53.8 52.5 57.7 41.1 50.8 50.8 50.8 50.8 55.5 41.0 47.5 47.5 47.5 47.5 52.5 40.1 44.0 44.0 44.0 44.0 48.6 38.6
75 46.8 41.3 53.1 31.3 56.9 20.5 42.7 39.1 50.1 29.7 55.0 19.2 38.7 37.0 45.4 27.5 52.4 17.9 34.4 34.4 40.8 25.4 48.9 16.3
80 48.7 48.7 53.4 39.5 57.5 28.9 45.2 45.2 50.3 38.2 55.4 27.8 41.8 41.8 45.7 36.0 52.7 26.3 38.2 38.2 41.1 33.9 49.1 24.7
85 52.2 52.2 53.9 47.5 58.1 36.1 49.3 49.3 51.0 46.7 55.7 35.3 45.7 45.7 46.7 44.7 52.9 34.5 42.1 42.1 42.1 42.1 49.2 33.0
90 54.9 54.9 54.9 54.9 58.4 42.8 52.7 52.7 52.7 52.7 56.2 42.9 49.8 49.8 49.8 49.8 53.3 42.5 46.2 46.2 46.2 46.2 49.7 41.3
75 48.1 43.8 53.6 32.5 57.3 20.8 43.8 41.6 50.8 31.1 55.5 19.6 39.8 39.5 46.3 29.0 52.9 18.2 35.8 35.8 41.5 26.7 49.6 16.7
80 50.5 50.5 54.0 41.2 58.0 29.6 47.1 47.1 51.1 40.3 55.9 29.0 43.4 43.4 46.7 38.2 53.2 27.4 39.8 39.8 42.0 36.0 49.7 25.8
85 53.6 53.6 54.8 49.8 58.6 37.1 51.1 51.1 52.0 49.4 56.3 36.6 47.7 47.7 48.1 47.9 53.5 36.1 43.9 43.9 43.9 43.9 49.9 34.9
90 56.1 56.1 56.1 56.1 59.0 44.2 54.2 54.2 54.1 54.1 56.9 44.8 51.5 51.5 51.5 51.5 54.1 44.7 48.2 48.2 48.2 48.2 50.5 43.9
75 49.1 46.3 54.2 33.5 57.7 21.2 44.9 44.0 51.5 32.4 55.9 20.0 40.7 40.7 47.1 30.4 53.3 18.6 37.0 37.0 42.2 28.1 50.1 17.0
80 51.9 51.9 54.6 42.7 58.4 30.1 48.8 48.8 51.8 42.2 56.3 30.2 45.0 45.0 47.7 40.4 53.7 28.5 41.2 41.2 42.9 38.2 50.3 26.9
85 54.7 54.7 55.5 51.8 59.1 38.1 52.5 52.5 52.9 51.8 56.8 37.8 49.4 49.4 49.4 49.4 54.1 37.6 45.5 45.5 45.5 45.5 50.5 36.6
1440
1600
1760
1920
90
57.1 57.1 57.1 57.1 59.4 45.6 55.3 55.3 55.3 55.3 57.4 46.4 52.8 52.8 52.8 52.8 54.7 46.7 49.8 49.8 49.8 49.8 51.3 46.2
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
18
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance (4, 5Ton)
Data
Standard Efficiency
Table PD-3 — Gross Cooling Capacities (MBH) 4 Ton Three Phase TSC048A3, A4, AW
AmbientTemperature (F)
85
95
105
67
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 44.8 38.6 51.4 29.8 56.1 20.1 41.0 36.6 48.2 28.2 53.7 18.9 37.3 34.7 44.2 26.4 50.8 17.6 33.4 32.7 39.6 25.2 47.1 16.0
80 46.0 46.0 51.6 37.4 56.5 27.9 42.9 42.9 48.3 35.8 54.0 26.6 39.7 39.7 44.4 34.0 51.0 25.2 36.4 36.4 40.0 32.0 47.2 23.6
85 49.6 49.6 52.0 44.8 56.7 34.8 46.8 46.8 48.9 43.6 54.2 34.0 43.6 43.6 45.1 41.8 51.2 32.7 40.3 40.3 41.0 39.8 47.4 31.1
90 52.5 52.5 52.9 52.2 57.2 41.6 50.2 50.2 50.1 50.1 54.6 41.1 47.2 47.2 47.2 47.2 51.5 40.1 43.9 43.9 43.9 43.9 47.7 38.6
75 46.1 41.1 52.1 31.1 56.7 20.5 42.1 39.0 49.1 29.6 54.4 19.3 38.3 37.1 45.1 27.8 51.5 18.0 34.3 34.3 40.6 25.7 47.9 16.5
80 48.1 48.1 52.4 39.3 57.2 29.0 44.9 44.9 49.2 37.9 54.7 27.7 41.5 41.5 45.4 36.2 51.7 26.3 38.1 38.1 41.0 34.2 48.0 24.8
1440
1600
1760
85
90 54.2 54.2 54.2 54.2 58.0 43.5 51.9 51.9 51.9 51.9 55.4 43.2 49.1 49.1 49.1 49.1 52.3 42.5 45.9 45.9 45.9 45.9 48.7 41.3
75 47.2 43.5 52.8 32.3 57.3 20.9 43.3 41.5 49.8 30.9 54.9 19.7 39.1 39.1 45.8 29.1 52.0 18.3 35.6 35.6 41.3 27.1 48.5 16.8
51.4 51.4 53.0 47.3 57.7 36.7 48.7 48.7 50.0 46.4 55.0 35.5 45.6 45.6 46.3 44.8 51.9 34.6 42.1 42.1 42.1 42.1 48.2 33.0
80 49.7 49.7 53.1 41.0 57.8 30.1 46.7 46.7 50.1 40.0 55.3 28.8 43.3 43.3 46.2 38.3 52.3 27.4 39.7 39.7 41.8 36.3 48.7 25.9
85 52.8 52.8 53.8 49.7 58.1 37.7 50.3 50.3 51.0 49.1 55.6 37.0 47.2 47.2 47.2 47.2 52.5 36.1 43.7 43.7 43.7 43.7 48.9 34.9
90 55.5 55.5 55.5 55.5 58.7 45.3 53.4 53.4 53.4 53.4 56.1 45.2 50.7 50.7 50.7 50.7 53.1 44.7 47.6 47.6 47.6 47.6 49.5 43.8
75 48.2 45.8 53.3 33.4 57.8 21.3 44.4 43.8 50.4 32.1 55.4 20.0 40.3 40.3 46.5 30.4 52.5 18.6 36.6 36.6 41.9 28.3 49.0 17.2
80 51.0 51.0 53.7 42.7 58.3 31.1 48.1 48.1 50.7 41.9 55.7 29.6 44.7 44.7 47.0 40.3 52.8 28.4 41.1 41.1 42.6 38.3 49.2 26.9
85 53.9 53.9 54.6 51.8 58.6 38.7 51.6 51.6 51.9 51.5 56.2 38.4 48.6 48.6 48.6 48.6 53.1 37.7 45.2 45.2 45.2 45.2 49.4 36.6
90 56.6 56.6 56.6 56.6 59.3 47.0 54.6 54.6 54.5 54.5 56.8 47.1 52.0 52.0 52.0 52.0 53.8 46.9 49.0 49.0 49.0 49.0 50.3 46.1
1920
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-4 — Gross Cooling Capacities (MBH) 5 Ton Single/Three Phase TSC060A1, A3, A4, AW, AK
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 57.4 49.1 64.8 37.9 69.2 25.3 53.3 47.0 61.8 36.3 67.2 24.1 49.4 45.0 57.6 34.3 64.3 22.8 45.2 42.9 52.4 32.7 60.6 21.2
80 59.0 59.0 65.1 47.1 69.8 35.0 55.6 55.6 62.0 45.7 67.6 33.8 52.2 52.2 57.8 43.9 64.6 32.3 48.6 48.6 52.8 41.6 60.8 30.6
85 63.1 63.1 65.7 56.2 70.2 42.9 60.3 60.3 62.7 55.3 68.0 42.3 56.8 56.8 58.9 53.6 64.9 41.3 52.9 52.9 54.0 51.4 61.0 39.9
90 66.4 66.4 66.9 65.2 70.8 51.0 64.1 64.1 64.1 64.1 68.5 50.8 61.1 61.1 61.1 61.1 65.4 50.1 57.5 57.5 57.5 57.5 61.5 49.0
75 59.0 52.2 65.7 39.4 69.8 25.7 54.9 50.1 62.8 37.9 67.8 24.6 50.7 48.0 58.9 36.1 64.9 23.2 46.5 45.9 53.5 33.8 61.3 21.6
80 61.3 61.3 66.0 49.2 70.2 35.6 58.1 58.1 63.1 48.2 68.1 34.8 54.4 54.4 59.2 46.6 65.3 33.7 50.6 50.6 54.0 44.3 61.5 32.0
85 65.1 65.1 66.8 59.1 70.9 44.2 62.5 62.5 64.0 58.5 68.7 43.8 59.3 59.3 60.4 57.3 65.7 43.1 55.2 55.2 55.8 55.2 61.8 41.9
90 68.1 68.1 68.0 68.0 71.6 52.9 65.9 65.9 65.9 65.9 69.4 52.9 63.1 63.1 63.1 63.1 66.3 52.5 59.7 59.7 59.7 59.7 62.4 51.7
75 60.3 55.2 66.3 40.6 70.2 26.1 56.3 53.1 63.6 39.5 68.2 25.0 52.0 51.0 59.9 37.8 65.4 23.6 47.7 47.7 54.5 35.4 61.8 22.0
80 63.1 63.1 66.8 51.2 70.8 37.9 60.2 60.2 64.0 50.5 68.7 35.6 56.5 56.5 60.3 49.1 65.8 34.6 52.4 52.4 55.2 46.9 62.1 33.3
85 66.5 66.5 67.7 61.6 71.5 45.4 64.2 64.2 65.0 61.3 69.4 45.2 61.2 61.2 61.7 60.5 66.4 44.7 57.3 57.3 57.3 57.3 62.5 43.8
90 69.4 69.4 69.3 69.3 72.2 54.6 67.3 67.3 67.3 67.3 70.1 54.9 64.6 64.6 64.6 64.6 67.1 54.8 61.2 61.2 61.2 61.2 63.2 54.2
75 61.5 58.0 66.9 41.8 70.6 26.5 57.6 56.0 64.2 40.8 68.6 25.4 53.0 53.0 60.6 39.3 65.9 24.0 49.1 49.1 55.4 37.1 62.2 22.4
80 64.5 64.5 67.5 53.0 71.2 38.8 61.8 61.8 64.7 52.5 69.1 36.4 58.3 58.3 61.1 51.4 66.3 35.5 53.9 53.9 56.3 49.5 62.5 34.3
1800
2000
2200
2400
85
67.7 67.7 68.5 63.9 72.0 46.5 65.4 65.4 65.9 63.9 69.9 46.5 62.5 62.5 62.5 62.5 66.9 46.2 58.9 58.9 58.9 58.9 63.0 45.5
90 70.4 70.4 70.4 70.4 72.8 56.1 68.4 68.4 68.4 68.4 70.6 56.6 65.8 65.8 65.8 65.8 67.7 56.8 62.4 62.4 62.4 62.4 63.9 56.5
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC005-EN
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(6, 7½Ton)
Standard Efficiency
Table PD-5 — Gross Cooling Capacities (MBH) 6 Ton Three Phase
TSC072A3, A4, AW, AK
AmbientTemperature (F)
95
85
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 65.9 55.0 73.4 43.5 76.7 28.3 61.0 52.5 70.7 40.9 75.4 27.3 56.3 50.1 66.3 38.8 73.2 26.0 51.7 47.7 60.9 36.4 70.3 24.6
80
67.6 66.2 73.7 52.2 77.5 38.9 63.2 63.2 70.9 51.1 76.0 37.8 59.2 59.2 66.4 49.1 73.7 36.4 55.3 55.3 61.0 46.6 70.6 34.9
2160
2400
2640
85 71.4 71.4 74.2 61.9 78.6 47.4 68.5 68.5 71.4 61.3 76.5 46.6 64.4 64.4 67.3 59.7 74.0 46.0 60.4 60.4 62.2 57.3 70.8 45.0
90 74.6 74.6 75.3 71.3 79.3 55.7 72.4 72.4 72.8 71.3 77.2 55.5 69.5 69.5 69.5 69.5 74.6 55.4 65.7 65.7 65.6 65.6 71.2 54.8
75
80 69.7 69.7 74.6 54.1 78.0 39.5 66.2 66.2 72.0 53.6 76.6 39.2 61.8 61.8 68.0 52.0 74.3 37.9 57.8 57.8 62.6 49.6 71.3 36.3
85 73.4 73.4 75.3 64.5 79.0 48.2 70.9 70.9 72.7 64.5 77.2 47.9 67.4 67.4 69.1 63.6 74.8 47.6 63.2 63.2 64.2 61.4 71.7 47.0
90 76.2 76.2 76.5 74.3 79.9 57.1 74.3 74.3 74.3 74.3 77.9 57.4 71.7 71.7 71.7 71.7 75.5 57.7 68.5 68.5 68.4 68.4 72.2 57.5
75 69.1 61.4 74.7 44.9 77.4 29.0 64.5 59.1 72.5 44.3 76.2 28.1 59.4 56.6 69.0 42.5 74.2 26.9 54.7 54.2 63.6 40.1 71.3 25.4
80 71.6 71.6 75.3 55.8 78.4 40.0 68.6 68.6 72.8 55.8 77.0 41.1 64.2 64.2 69.1 54.7 74.6 38.6 60.0 60.0 63.9 52.4 71.9 37.7
85 74.8 74.8 76.1 66.8 79.4 49.1 72.7 72.7 73.8 67.3 77.8 49.3 69.7 69.7 70.5 66.9 75.4 49.1 65.7 65.7 66.1 65.4 72.3 48.7
67.7 58.3 74.0 43.8 77.1 28.7 62.9 55.9 71.7 42.6 75.9 27.7 57.9 53.4 67.9 40.8 73.7 26.4 53.2 51.0 62.4 38.3 70.9 25.0
90
77.4 77.4 77.5 76.8 80.3 58.4 75.8 75.8 75.8 75.8 78.5 59.0 73.4 73.4 73.3 73.3 76.2 59.7 70.5 70.5 70.5 70.5 73.0 59.8
75 70.2 64.1 75.2 45.8 77.6 29.4 66.1 62.3 73.1 45.4 76.5 28.5 60.9 59.7 69.8 44.2 74.5 27.3 56.2 56.2 64.7 41.9 71.7 25.8
80 72.9 72.9 75.9 57.4 78.7 40.4 70.3 70.3 73.6 57.8 77.3 41.8 66.5 66.5 70.1 57.1 75.2 41.1 62.0 62.0 65.2 55.2 72.1 38.5
85 75.9 75.9 76.8 68.8 79.7 49.9 74.0 74.0 74.7 69.8 78.5 50.6 71.3 71.3 71.6 69.8 75.9 50.4 67.8 67.8 67.7 67.7 72.9 50.1
90 78.3 78.3 78.3 78.3 80.7 59.6 76.8 76.8 76.8 76.8 79.0 60.5 74.6 74.6 74.6 74.6 76.7 61.6 71.9 71.9 71.9 71.9 73.7 61.9
2880
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-6 — Gross Cooling Capacities (MBH) 7½ Ton Three Phase Single Compressor
TSC090A3, A4, AW, AK
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 87.4 73.8 96.2 56.7 98.8 36.7 80.6 70.3 93.3 54.3 98.8 35.6 73.5 66.6 86.9 51.2 96.8 33.9 66.6 63.1 78.4 48.2 92.8 31.8
80 89.6 88.9 96.6 68.7 100.0 49.9 83.4 83.4 93.5 68.3 99.9 50.2 77.6 77.6 87.2 65.3 97.4 48.2 71.6 71.6 78.9 61.5 92.9 46.0
85 94.2 94.2 97.5 81.6 101.2 60.4 90.4 90.4 94.4 82.2 100.9 61.9 84.8 84.8 88.5 79.8 97.8 61.4 78.5 78.5 80.7 76.2 93.2 59.9
90 98.0 98.0 98.7 93.9 102.3 71.0 95.8 95.8 96.2 95.8 101.2 72.9 91.6 91.6 91.6 91.6 98.5 74.3 86.0 86.0 86.0 86.0 93.7 73.5
75 89.7 78.4 96.7 57.3 99.1 37.2 83.0 75.0 94.6 56.7 99.2 36.1 75.8 71.3 88.9 53.9 97.5 34.5 68.7 67.7 80.3 50.1 93.8 32.5
80 92.2 92.2 97.5 70.9 100.3 50.4 87.4 87.4 95.0 71.8 100.4 50.9 81.4 81.4 89.3 69.5 98.3 50.3 75.0 75.0 81.1 65.8 94.1 48.1
85 96.5 96.5 98.5 84.4 101.5 61.2 93.8 93.8 96.1 86.6 101.6 63.4 88.9 88.9 91.0 85.5 98.8 63.7 82.5 82.5 83.7 82.1 94.4 63.1
90 99.5 99.5 99.9 97.0 102.6 72.3 98.2 98.2 98.2 98.2 101.9 75.0 94.9 94.9 94.9 94.9 99.7 77.4 90.1 90.1 90.0 90.0 95.3 77.7
75 91.5 82.5 97.7 59.0 99.3 37.7 85.2 79.6 95.5 58.8 99.5 36.6 78.0 76.0 90.5 56.5 98.0 35.1 70.5 70.5 82.1 52.8 94.5 33.2
80 94.4 94.4 98.1 72.8 100.5 55.0 90.7 90.7 96.2 74.8 100.8 51.6 84.7 84.7 91.1 73.5 98.9 51.5 78.0 78.0 83.2 70.0 95.0 50.1
85 98.0 98.0 99.2 86.8 101.7 62.0 96.1 96.1 97.5 90.5 102.0 64.7 92.0 92.0 93.1 90.6 99.5 65.6 86.2 86.2 86.2 86.2 95.4 65.8
90 100.5 100.5 100.7 99.4 102.8 73.4 99.9 99.9 99.9 99.9 102.4 76.8 97.2 97.2 97.2 97.2 100.5 80.1 93.0 93.0 93.0 93.0 96.5 81.4
75 92.9 86.2 98.1 59.9 99.4 38.2 87.3 84.1 96.3 60.6 99.8 37.2 79.6 79.6 91.7 58.9 98.3 35.7 72.9 72.9 83.7 55.4 95.1 33.8
80 96.0 96.0 98.6 74.3 100.7 56.8 93.1 93.1 97.1 77.5 101.0 55.7 87.6 87.6 92.5 77.2 99.5 52.7 80.7 80.7 85.1 74.1 95.5 51.6
85 99.0 99.0 99.7 88.7 101.8 62.7 97.8 97.8 98.6 93.7 102.3 65.8 94.4 94.4 94.4 94.4 100.0 67.3 89.1 89.1 89.1 89.1 96.3 68.3
90 101.1 101.1 101.1 101.1 103.0 74.4 101.0 101.0 101.0 101.0 102.8 78.4 98.9 98.9 98.9 98.9 101.2 82.4 95.1 95.1 95.1 95.1 97.5 84.6
2700
3000
3300
3600
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
20
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(7½, 8½Ton)
Standard Efficiency
Table PD-7 — Gross Cooling Capacities (MBH) 7½ Ton Three Phase Dual Compressors TSC092A3, A4, AW
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 84.6 72.9 93.9 55.3 98.4 36.4 78.2 69.6 90.1 53.3 96.9 35.1 71.8 66.3 83.9 50.4 94.0 33.3 65.3 63.1 76.5 47.1 89.4 31.2
80 86.8 86.8 94.4 68.5 99.6 50.0 81.8 81.8 90.5 67.5 98.0 49.7 76.4 76.4 84.3 64.7 94.5 47.5 70.9 70.9 77.1 61.4 89.6 45.3
85 92.2 92.2 95.4 81.7 100.8 61.3 88.4 88.4 91.5 81.5 99.0 62.4 83.2 83.2 85.8 79.3 94.9 60.9 77.6 77.6 79.0 76.1 89.9 59.3
90 96.3 96.3 96.9 94.4 102.0 72.8 93.6 93.6 93.6 93.6 99.3 73.4 89.6 89.6 89.6 89.6 95.8 74.0 84.5 84.5 84.5 84.5 90.6 73.0
75 86.8 77.5 94.7 57.0 98.9 37.1 80.5 74.4 91.5 55.8 97.6 35.7 74.0 71.1 85.6 53.1 94.8 34.0 67.1 67.1 78.2 49.8 90.5 31.9
80 90.1 90.1 95.6 71.2 100.2 50.8 85.4 85.4 92.0 71.1 98.7 50.7 79.9 79.9 86.3 68.9 95.5 49.6 74.1 74.1 79.1 65.7 90.8 47.4
85 94.7 94.7 96.8 85.3 101.4 62.7 91.5 91.5 93.3 86.2 99.7 63.7 86.9 86.9 88.2 84.9 96.1 63.5 81.3 81.3 81.2 81.2 91.2 62.6
90 98.3 98.3 98.3 98.3 102.7 74.8 96.2 96.2 96.1 96.1 100.3 76.2 92.7 92.7 92.7 92.7 97.1 77.5 88.0 88.0 88.0 88.0 92.2 77.4
75 88.7 81.9 95.7 58.9 99.3 37.6 82.6 79.0 92.5 58.2 98.1 36.2 75.5 75.5 87.1 55.7 95.4 34.6 69.6 69.6 79.6 52.4 91.3 32.5
80 92.3 92.3 96.5 73.7 100.7 51.5 88.4 88.4 93.2 74.4 99.3 51.7 82.9 82.9 87.9 72.8 96.1 51.0 76.9 76.9 80.8 69.8 91.7 49.5
85 96.5 96.5 97.8 88.4 102.0 63.9 93.8 93.8 94.8 90.3 100.0 65.0 89.8 89.8 89.8 89.8 96.9 65.8 84.4 84.4 84.4 84.4 92.3 65.5
90 99.7 99.7 99.7 99.7 103.3 76.5 98.0 98.0 98.0 98.0 101.1 78.5 94.9 94.9 94.9 94.9 98.1 80.6 90.7 90.7 90.7 90.7 93.5 81.3
75 90.2 85.7 96.4 60.6 99.7 38.1 84.6 83.6 93.3 60.0 98.5 36.8 77.9 77.9 88.2 58.1 96.0 35.2 71.8 71.8 80.9 55.0 92.0 33.2
80 94.0 94.0 97.2 75.8 101.0 52.1 90.7 90.7 94.3 77.4 99.7 52.6 85.6 85.6 89.2 76.6 96.6 52.0 79.5 79.5 82.3 73.8 92.5 51.5
2700
3000
3300
3600
85
97.8 97.8 98.7 91.1 102.4 65.0 95.6 95.6 96.1 93.9 100.5 66.3 91.9 91.9 91.9 91.9 97.6 67.9 86.9 86.9 86.9 86.9 93.1 68.2
90 100.8 100.8 100.8 100.8 103.7 78.1 99.3 99.3 99.3 99.3 101.7 80.7 96.6 96.6 96.6 96.6 98.9 83.4 92.7 92.7 92.7 92.7 94.6 84.9
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-8 — Gross Cooling Capacities (MBH) 8½ Ton Three Phase TSC102A3, A4, AW, AK
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 96.3 82.3 106.6 62.7 112.5 41.5 89.0 78.5 103.2 60.6 110.9 40.0 81.8 74.9 96.6 57.5 107.6 38.1 74.9 71.3 87.6 55.2 102.5 35.8
80 98.0 98.0 107.2 77.1 113.7 57.0 92.9 91.4 103.4 76.3 111.5 57.1 86.3 86.2 96.9 73.3 108.2 54.0 80.2 80.2 88.1 69.4 102.8 51.5
85 103.9 103.9 108.1 91.7 114.8 69.6 100.1 100.1 104.3 91.7 112.4 70.0 94.3 94.3 98.3 89.5 108.6 68.9 87.6 87.6 89.9 85.7 103.1 67.1
90 108.6 108.6 109.6 105.7 116.0 82.4 105.9 105.9 105.9 105.9 113.2 83.0 101.6 101.6 101.9 100.2 109.3 83.4 95.6 95.6 95.6 95.5 103.6 82.3
75 98.7 87.2 107.8 65.9 113.0 42.0 91.8 83.8 104.7 63.7 111.8 40.7 84.2 80.0 98.7 60.5 108.6 38.9 76.3 76.3 89.6 58.6 103.7 36.5
80 101.6 100.0 108.5 80.1 114.6 58.1 96.9 96.5 105.0 80.1 112.8 57.8 90.3 90.3 99.1 77.9 109.3 56.3 83.8 83.8 90.3 74.0 104.0 53.8
85 106.8 106.8 109.6 95.7 115.8 71.4 103.6 103.6 106.2 96.7 114.0 70.7 98.7 98.7 100.9 95.5 109.8 71.7 91.7 91.7 91.7 91.7 104.3 70.7
90 111.0 111.0 111.0 111.0 117.0 84.9 108.8 108.8 108.9 107.2 114.4 86.1 105.1 105.1 105.0 104.8 110.7 87.4 99.8 99.8 99.7 99.7 105.2 87.1
75 100.7 91.7 109.2 64.5 114.0 42.8 93.8 88.7 106.1 66.5 113.5 41.7 85.4 85.4 100.4 63.3 109.4 39.6 79.4 77.5 91.3 59.4 104.6 37.2
80 104.1 103.6 109.6 82.9 115.3 59.0 100.0 100.0 106.6 84.3 113.7 59.0 94.0 94.0 100.9 82.2 109.6 60.2 87.0 87.0 92.2 78.5 105.1 56.0
85 108.9 108.9 110.9 99.2 116.6 73.0 106.7 106.7 108.3 102.4 114.8 74.4 102.0 102.0 102.0 102.0 110.8 74.3 95.6 95.6 96.4 93.7 105.5 73.9
90 112.8 112.8 112.8 112.8 117.8 87.2 111.8 111.8 111.8 111.2 116.0 90.0 107.7 107.7 107.7 107.7 111.9 90.9 102.9 102.9 102.9 102.9 106.6 91.4
75 102.3 95.8 110.2 66.1 114.6 43.5 95.2 95.2 106.7 68.3 113.1 42.2 88.2 88.2 101.6 65.9 110.1 40.3 81.6 80.6 92.7 62.1 105.3 38.1
80 106.2 106.2 110.5 85.3 115.9 59.8 102.8 102.8 107.4 86.8 114.3 60.0 97.4 97.4 102.4 86.2 111.0 58.6 89.9 89.9 94.1 82.9 105.9 58.2
85 110.5 110.5 111.9 102.3 117.2 74.4 108.3 108.3 109.2 105.1 115.5 76.3 104.5 104.5 104.4 104.4 111.5 77.2 98.7 98.7 99.0 97.4 106.4 76.8
90 114.2 114.2 114.2 114.2 118.5 89.3 112.7 112.7 112.7 112.7 116.8 92.7 109.7 109.7 109.7 109.7 112.9 94.2 105.2 105.2 105.2 105.2 107.8 95.4
3060
3400
3740
4080
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC005-EN
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(10 Ton)
Standard Efficiency
Table PD-9 — Gross Cooling Capacities (MBH) 10 Ton Three Phase TSC120A3, A4, AW, AK
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 108.6 95.7 120.5 71.5 126.0 46.0 100.1 91.3 115.5 68.8 123.6 43.3 91.0 86.5 107.2 64.9 119.3 41.0 82.2 82.0 96.5 60.1 113.1 37.9
80 112.8 112.8 121.2 89.2 127.5 65.7 106.3 106.3 116.1 88.1 124.8 62.8 98.5 98.5 108.2 84.5 120.1 60.5 90.5 90.5 97.8 79.7 113.6 57.4
85 119.5 119.5 122.6 106.9 129.0 78.5 114.8 114.8 117.7 107.0 126.2 79.2 108.2 108.2 110.5 104.5 121.8 76.8 100.1 100.1 100.1 100.1 114.2 76.6
90 124.3 124.3 124.6 123.6 130.4 93.6 121.0 121.0 121.0 121.0 127.6 95.7 116.0 116.0 116.0 116.0 122.0 95.1 109.4 109.4 109.4 109.4 115.3 94.5
3600
4000
4400
75 111.6 102.3 121.7 73.9 126.7 46.9 103.4 98.1 117.1 72.3 124.5 42.7 94.2 93.4 109.5 68.7 120.2 41.9 85.3 85.3 98.8 64.0 114.3 38.8
80 116.7 116.7 122.6 92.7 128.2 64.5 111.1 111.1 118.0 93.0 125.7 64.2 103.4 103.4 110.8 90.4 121.4 63.2 95.0 95.0 100.6 85.8 114.9 60.3
85 122.3 122.3 124.2 111.4 129.7 80.2 118.5 118.5 120.0 113.1 127.1 81.6 112.8 112.8 113.6 112.1 122.6 82.1 105.1 105.1 105.1 105.1 115.6 80.4
90 126.9 126.9 126.4 126.4 131.3 96.0 123.7 123.7 123.7 123.7 128.7 99.0 119.3 119.3 119.3 119.3 124.1 100.7 113.4 113.4 113.4 113.4 117.1 100.0
75 114.1 108.4 122.5 75.8 127.3 47.7 106.5 104.9 118.4 75.8 124.9 45.4 97.1 97.1 111.3 72.3 121.3 40.2 88.6 88.6 100.9 67.7 115.1 39.7
80 119.5 119.5 123.8 96.1 128.9 65.5 114.7 114.7 119.5 97.3 126.3 69.2 107.7 107.7 112.9 95.9 122.2 64.9 99.0 99.0 103.1 91.7 115.8 63.2
85 124.9 124.9 125.5 115.5 130.4 81.9 121.1 121.1 121.8 118.3 127.9 83.7 116.0 116.0 116.0 116.0 123.6 85.0 109.2 109.2 109.2 109.2 116.8 84.0
90 127.9 127.9 128.0 128.0 132.0 98.3 126.1 126.1 125.6 125.6 129.5 101.8 121.7 121.7 121.7 121.7 125.3 104.7 116.2 116.2 116.2 116.2 118.5 104.7
75 116.1 113.8 123.1 77.6 127.8 48.5 108.9 108.9 119.2 78.1 125.4 46.2 100.5 100.5 112.8 76.1 121.4 43.6 91.6 91.6 102.6 71.3 115.8 40.6
80 121.4 121.4 124.5 98.6 129.4 66.4 117.3 117.3 120.8 101.1 126.9 66.5 111.1 111.1 114.6 100.9 122.9 66.4 102.5 102.5 105.4 97.5 116.5 65.7
85 126.0 126.0 126.4 118.6 130.9 83.4 122.9 122.9 123.2 122.6 128.5 85.6 118.4 118.4 118.4 118.4 124.3 87.5 112.1 112.1 112.1 112.1 117.8 87.3
90 129.1 129.1 129.1 129.1 132.5 100.4 127.2 127.2 126.9 126.9 130.2 104.4 124.0 124.0 123.7 123.7 126.2 108.0 118.2 118.2 118.2 118.2 119.7 108.9
4800
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
22
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(3Ton)
High Efficiency
Table PD-10 — Gross Cooling Capacities (MBH) 3 Ton THC036A1, A3, A4, AW
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
CFM
Bulb
61
67
73
61
67
73
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 34.2 29.2 39.8 22.7 43.1 15.2 31.1 27.4 37.0 21.2 41.3 14.1 28.0 25.7 33.3 19.8 39.0 12.9 24.8 24.0 29.8 18.1 36.1 11.6
80 34.9 34.9 40.0 28.5 43.5 21.3 32.3 32.3 37.1 27.1 41.6 20.1 29.7 29.7 33.5 25.3 39.2 18.8 27.1 27.1 30.0 23.6 36.2 17.5
1080
1200
1320
85
37.9 37.9 40.3 34.3 44.0 26.5 35.3 35.3 37.5 33.0 41.9 25.6 32.6 32.6 34.0 31.3 39.5 24.6 30.0 30.0 30.6 29.6 36.4 23.2
90 40.5 40.5 40.9 40.0 44.5 31.7 38.4 38.4 38.4 38.4 42.3 31.0 35.7 35.7 35.7 35.7 39.7 30.3 32.9 32.9 32.9 32.9 36.7 29.0
75 35.3 31.2 40.4 23.7 43.5 15.5 32.0 29.4 37.8 22.4 41.8 14.4 28.8 27.7 34.1 20.6 39.5 13.2 25.5 25.5 30.5 18.8 36.7 11.9
80 36.7 36.7 40.7 30.0 44.0 21.9 33.9 33.9 38.0 28.9 42.1 20.9 31.2 31.2 34.4 27.1 39.8 19.7 28.5 28.5 30.8 25.3 36.9 18.4
85 39.6 39.6 41.1 36.3 44.6 27.4 37.1 37.1 38.5 35.4 42.5 26.8 34.3 34.3 35.1 33.8 40.0 26.0 31.5 31.5 31.5 31.5 37.1 24.8
90 41.9 41.9 41.9 41.9 45.1 33.0 39.9 39.9 39.9 39.9 42.9 32.6 37.6 37.6 37.6 37.6 40.4 32.1 34.7 34.7 34.7 34.7 37.4 31.1
75 36.2 33.2 40.9 24.7 43.8 15.8 32.8 31.4 38.4 23.4 42.1 14.7 29.4 29.4 34.8 21.7 39.9 13.5 26.5 26.5 31.0 19.9 37.2 12.2
80 38.2 38.2 41.2 31.4 44.4 22.4 35.4 35.4 38.7 30.5 42.6 21.7 32.5 32.5 35.2 28.9 40.2 20.5 29.7 29.7 31.5 27.1 37.4 19.2
85 40.8 40.8 41.8 38.1 45.0 28.3 38.7 38.7 39.4 37.6 43.1 28.0 35.9 35.9 36.2 36.2 40.5 27.2 32.9 32.9 32.9 32.9 37.6 26.2
90 42.9 42.9 42.9 42.9 45.6 34.2 41.1 41.1 41.1 41.1 43.4 34.0 38.9 38.9 38.9 38.9 41.0 33.8 36.3 36.3 36.3 36.3 38.1 33.1
75
37.1 35.1 41.3 25.5 44.1 16.1 33.6 33.3 38.9 24.4 42.4 15.0 30.4 30.4 35.5 22.8 40.2 13.8 27.5 27.5 31.5 21.0 37.5 12.5
80 39.4 39.4 41.7 32.6 44.7 22.9 36.8 36.8 39.3 32.1 42.9 22.3 33.8 33.8 35.9 30.6 40.6 21.4 30.8 30.8 32.1 28.8 37.8 20.1
85 41.7 41.7 42.4 39.7 45.3 29.0 39.8 39.8 40.1 39.5 43.5 29.0 37.3 37.3 37.3 37.3 40.9 28.3 34.2 34.2 34.2 34.2 38.0 27.6
90 43.7 43.7 43.7 43.7 45.9 35.3 42.1 42.1 42.1 42.1 43.9 35.3 40.0 40.0 40.0 40.0 41.5 35.4 37.5 37.5 37.5 37.5 38.6 34.9
1440
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-11 — Gross Cooling Capacities (MBH) 3 Ton THC036A1, A3, A4, AW – Dehumidification (Hot Gas Reheat) Option
AmbientTemperature (F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 30.8 21.6 34.9 17.8 39.2 13.7 28.9 20.4 32.8 16.6 37.0 12.5 26.9 19.1 30.6 15.3 34.7 11.3 24.8 17.8 28.4 14.1 32.3 10.0
80 30.9 25.0 35.0 21.2 39.3 17.2 29.0 23.8 32.9 19.9 37.1 16.0 26.9 22.5 30.8 18.7 34.8 14.8 24.9 21.1 28.6 17.4 32.4 13.5
85 31.0 28.4 35.1 24.6 39.5 20.6 29.0 27.1 33.1 23.3 37.3 19.3 27.0 25.8 30.9 22.0 35.0 18.1 25.0 24.5 28.7 20.7 32.6 16.8
90 31.2 31.2 35.2 27.9 39.6 23.9 29.6 29.6 33.1 26.6 37.4 22.7 28.0 28.0 31.0 25.4 35.1 21.4 26.3 26.3 28.8 24.0 32.7 20.1
600
780
960
75 33.1 24.8 37.3 19.7 41.8 14.5 30.9 23.5 35.0 18.5 39.3 13.2 28.8 22.2 32.6 17.1 36.7 12.0 26.5 20.8 30.2 15.8 34.1 10.7
80 33.2 29.2 37.4 24.1 41.9 18.9 31.1 27.9 35.1 22.8 39.5 17.6 29.0 26.6 32.8 21.5 36.9 16.3 26.7 25.2 30.4 20.1 34.3 15.0
85 33.4 33.4 37.5 28.4 42.1 23.2 31.6 31.6 35.3 27.1 39.6 21.9 29.8 29.8 32.9 25.8 37.0 20.6 27.9 27.9 30.5 24.4 34.4 19.3
90 35.4 35.4 37.7 32.7 42.2 27.5 33.6 33.6 35.5 31.4 39.8 26.2 31.8 31.8 33.1 30.1 37.2 24.9 29.8 29.8 30.8 28.7 34.6 23.6
75 34.6 27.8 38.9 21.5 43.4 15.1 32.4 26.5 36.5 20.2 40.9 13.8 30.1 25.1 34.0 18.9 38.1 12.6 27.7 23.7 31.4 17.5 35.3 11.2
80 35.0 33.2 39.0 26.8 43.5 20.4 32.8 31.9 36.6 25.5 41.0 19.2 30.6 30.5 34.1 24.1 38.3 17.8 28.3 28.3 31.6 22.7 35.5 16.5
85 36.4 36.4 39.2 32.0 43.7 25.6 34.5 34.5 36.8 30.7 41.2 24.4 32.5 32.5 34.4 29.4 38.5 23.0 30.4 30.4 31.9 28.0 35.7 21.7
90 38.6 38.6 39.6 37.3 43.9 30.8 36.7 36.7 37.3 36.0 41.4 29.5 34.6 34.6 34.9 34.7 38.6 28.2 32.5 32.5 32.5 32.5 35.9 26.8
75 35.5 29.7 39.7 22.9 44.1 15.4 33.2 28.4 37.2 21.6 41.6 14.2 30.8 27.0 34.6 20.3 38.8 12.9 28.4 25.6 32.0 18.9 35.9 11.6
80 36.0 35.8 39.9 28.5 44.3 21.3 33.8 33.8 37.4 27.2 41.7 20.1 31.7 31.7 34.8 25.8 39.0 18.8 29.6 29.6 32.2 24.4 36.1 17.4
85 38.1 38.1 40.1 34.4 44.5 27.2 36.0 36.0 37.7 33.1 41.9 25.9 33.9 33.9 35.2 31.7 39.2 24.6 31.8 31.8 32.6 30.3 36.3 23.2
90 40.4 40.4 40.8 40.4 44.7 33.0 38.3 38.3 38.3 38.3 42.1 31.7 36.2 36.2 36.2 36.2 39.4 30.4 34.0 34.0 33.9 33.9 36.5 29.0
1080
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC005-EN
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(4Ton)
High Efficiency
Table PD-12 — Gross Cooling Capacities (MBH) 4 Ton THC048A1, A3, A4, AW
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
CFM
Bulb
61
67
73
61
67
73
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 45.3 39.9 51.4 30.3 54.9 19.9 41.1 37.7 48.4 28.8 53.1 18.7 37.1 35.6 43.9 26.7 51.0 17.4 33.2 33.2 39.3 24.6 47.8 16.0
80
47.1 47.1 52.0 38.4 55.5 28.1 43.8 43.8 48.7 36.9 54.6 27.2 40.3 40.3 44.3 34.9 51.3 25.6 36.9 36.9 39.8 32.8 47.9 24.1
1440
1600
1760
85 50.5 50.5 52.5 46.3 56.2 34.5 47.8 47.8 49.4 45.2 54.9 34.9 44.3 44.3 45.3 43.3 51.6 33.6 40.9 40.9 40.9 40.9 48.1 32.2
90 53.1 53.1 53.5 53.5 56.9 41.4 51.2 51.2 51.2 51.2 54.6 41.4 48.4 48.4 48.4 48.4 52.0 41.2 45.0 45.0 45.0 45.0 48.6 40.2
75 46.7 42.7 52.7 31.9 55.2 20.2 42.4 40.5 49.4 30.3 54.4 19.3 38.2 38.2 45.0 28.4 51.6 17.8 34.7 34.7 40.2 26.2 48.6 16.4
80 49.2 49.2 52.8 40.4 55.9 28.2 46.0 46.0 49.8 39.4 55.2 28.4 42.3 42.3 45.6 37.5 51.9 26.9 38.7 38.7 40.9 35.3 48.7 25.4
85 52.1 52.1 53.5 48.8 56.6 35.4 49.9 49.9 50.6 48.3 55.7 36.8 46.7 46.7 47.0 46.8 52.2 35.2 43.0 43.0 42.9 42.9 49.0 34.3
90 54.5 54.5 54.8 54.8 57.4 42.7 52.8 52.8 52.8 52.8 55.2 42.9 50.5 50.5 50.5 50.5 52.9 43.5 47.4 47.4 47.4 47.4 49.6 43.0
75
47.8 45.4 53.2 33.4 55.5 20.6 43.7 43.3 50.1 31.8 54.7 19.6 39.7 39.7 46.0 30.0 51.9 18.2 36.1 36.1 41.0 27.7 49.1 16.8
80 50.6 50.6 53.4 42.1 56.2 28.7 47.8 47.8 50.5 41.5 55.7 29.4 44.1 44.1 46.7 39.9 52.4 28.1 40.4 40.4 41.9 37.8 49.3 26.7
85 53.1 53.1 54.2 50.9 57.0 36.2 51.4 51.4 51.6 51.0 56.2 38.0 48.6 48.6 48.6 48.6 52.8 36.7 44.9 44.9 44.9 44.9 49.7 36.3
90 55.1 55.1 55.7 55.7 57.7 43.8 53.9 53.9 53.9 53.9 55.6 44.3 51.9 51.9 51.9 51.9 53.5 45.6 49.2 49.2 49.2 49.2 50.5 45.7
75 48.8 48.1 53.6 34.4 55.7 20.9 45.0 45.0 50.6 33.2 55.0 20.0 41.0 41.0 46.8 31.5 52.3 18.5 37.3 37.3 41.7 29.3 49.6 17.2
80 51.7 51.7 53.9 43.5 56.4 31.7 49.3 49.3 51.2 43.5 56.0 30.1 45.8 45.8 47.6 42.3 52.8 28.9 41.8 41.8 42.8 40.2 49.8 27.9
85 53.9 53.9 54.8 52.7 57.2 36.9 52.4 52.4 52.4 52.4 56.5 39.1 50.0 50.0 50.0 50.0 53.2 38.1 46.6 46.6 46.6 46.6 50.3 38.1
90 55.7 55.7 56.3 56.3 58.0 44.8 54.7 54.7 54.7 54.7 56.0 45.6 53.0 53.0 53.0 53.0 54.0 47.4 50.5 50.5 50.5 50.5 51.2 48.1
1920
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-13 — Gross Cooling Capacities (MBH) 4 Ton THC048A1, A3, A4, AW – Dehumidification (Hot Gas Reheat) Option
AmbientTemperature (F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 40.4 29.1 45.7 23.7 51.3 18.2 38.2 27.7 43.3 22.4 48.8 16.9 35.8 26.3 40.6 20.9 45.9 15.4 33.3 24.8 38.0 19.5 43.1 14.0
80 40.5 33.8 45.8 28.4 51.5 22.8 38.3 32.4 43.4 27.0 48.9 21.5 35.9 31.0 40.8 25.5 46.0 20.0 33.4 29.5 38.1 24.1 43.2 18.6
85 40.8 38.5 45.9 33.1 51.6 27.5 38.5 37.1 43.5 31.7 49.0 26.1 36.2 35.7 40.8 30.2 46.1 24.6 33.9 33.9 38.2 28.7 43.3 23.2
90 42.0 42.0 46.1 37.7 51.7 32.1 40.1 40.1 43.7 36.3 49.1 30.7 38.1 38.1 41.0 34.8 46.2 29.2 36.1 36.1 38.4 33.3 43.4 27.8
800
75 43.3 33.5 48.8 26.4 54.6 19.2 40.8 32.1 46.2 25.0 51.8 17.8 38.2 30.6 43.2 23.5 48.6 16.3 35.5 29.1 40.4 22.0 45.5 14.9
80 43.6 39.6 48.9 32.4 54.7 25.1 41.1 38.2 46.3 31.0 51.9 23.8 38.6 36.7 43.3 29.5 48.7 22.3 36.0 35.2 40.5 28.0 45.7 20.8
85 44.7 44.7 49.1 38.4 54.9 31.1 42.6 42.6 46.5 37.0 52.1 29.7 40.4 40.4 43.6 35.4 48.8 28.2 38.2 38.2 40.7 33.9 45.8 26.7
1040
1280
90
47.3 47.3 49.4 44.4 55.0 37.0 45.2 45.2 46.8 42.9 52.2 35.6 43.0 43.0 44.0 41.4 49.0 34.0 40.7 40.7 41.2 39.9 46.0 32.6
75 45.3 37.7 50.8 28.9 56.7 20.0 42.7 36.2 48.0 27.5 53.8 18.6 40.0 34.7 44.9 25.9 50.3 17.0 37.2 33.1 41.9 24.4 47.1 15.6
80 46.0 45.1 51.0 36.2 56.9 27.3 43.4 43.4 48.2 34.7 53.9 25.9 41.1 41.1 45.1 33.1 50.5 24.3 38.7 38.7 42.1 31.6 47.3 22.9
85 48.5 48.5 51.3 43.5 57.0 34.5 46.2 46.2 48.6 42.0 54.1 33.1 43.9 43.9 45.5 40.4 50.6 31.5 41.4 41.4 42.6 38.9 47.5 30.0
90 51.4 51.4 52.1 50.8 57.3 41.7 49.1 49.1 49.5 49.4 54.3 40.3 46.7 46.7 46.7 46.7 50.9 38.7 44.2 44.2 44.2 44.2 47.7 37.2
75 46.3 40.3 51.5 30.3 57.4 20.3 43.7 38.8 48.7 28.9 54.3 18.9 41.0 37.3 45.7 27.4 51.2 17.5 38.1 35.8 42.7 25.9 47.9 16.0
80
47.6 47.6 51.8 38.5 57.6 28.5 45.2 45.2 49.0 37.0 54.5 27.1 42.8 42.8 46.0 35.5 51.3 25.6 40.3 40.3 43.0 34.0 48.1 24.2
1440
85 50.6 50.6 52.3 46.6 57.7 36.5 48.2 48.2 49.5 45.2 54.7 35.1 45.7 45.7 46.6 43.7 51.5 33.7 43.2 43.2 43.7 42.2 48.3 32.2
90 53.6 53.6 53.6 53.6 58.1 44.6 51.2 51.2 51.2 51.2 55.0 43.2 48.7 48.7 48.7 48.7 51.9 41.7 46.1 46.1 46.1 46.1 48.7 40.2
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
24
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(5Ton)
High Efficiency
Table PD-14 — Gross Cooling Capacities (MBH) 5 Ton Single Phase THC060A1
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
CFM
Bulb
61
67
73
61
67
73
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 56.2 48.2 64.3 37.8 68.4 24.8 51.4 45.6 60.5 35.2 66.7 23.5 46.8 43.2 55.3 32.8 63.9 21.9 42.2 40.8 50.0 31.0 59.9 20.1
80
57.6 57.6 64.6 46.6 69.3 34.7 53.7 53.7 60.7 44.8 67.3 33.1 49.8 49.8 55.5 42.3 64.2 31.5 45.9 45.9 50.5 39.9 60.1 29.6
1800
2000
2200
85 62.2 62.2 65.2 55.8 70.1 42.6 58.4 58.4 61.4 54.5 68.0 42.2 54.5 54.5 56.5 52.0 64.6 40.9 50.6 50.6 51.6 49.7 60.3 39.0
90 65.8 65.8 66.3 64.9 70.9 50.8 63.0 63.0 63.0 63.0 68.2 52.0 59.3 59.3 59.2 59.2 65.0 49.9 55.3 55.3 55.3 55.3 60.7 48.5
75
80 60.3 60.3 65.6 48.8 69.8 35.2 56.2 56.2 62.1 47.6 68.0 34.6 52.1 52.1 56.9 45.1 65.0 32.9 48.1 48.1 51.7 42.7 61.2 31.1
85 64.4 64.4 66.3 58.7 70.7 43.8 61.2 61.2 63.0 58.1 68.7 43.9 57.1 57.1 58.2 56.0 65.4 42.8 53.0 53.0 53.0 53.0 61.4 41.5
90
75 59.4 54.5 65.7 40.1 69.3 25.6 54.3 51.9 62.7 38.7 67.7 24.3 49.6 49.4 57.6 36.3 65.1 22.8 45.0 45.0 52.2 33.8 61.6 21.1
80 62.4 62.4 66.3 50.7 70.3 35.8 58.4 58.4 63.1 50.1 68.5 35.4 54.2 54.2 58.2 47.9 65.7 34.2 50.0 50.0 52.9 45.4 61.9 32.5
85 66.0 66.0 67.3 61.2 71.2 44.8 63.3 63.3 64.2 61.3 69.4 45.3 59.4 59.4 59.9 59.8 66.1 44.6 55.2 55.2 55.2 55.2 62.2 43.7
90 68.9 68.9 68.9 68.9 72.2 54.0 66.9 66.9 66.9 66.9 70.2 55.4 64.0 64.0 64.0 64.0 66.8 55.1 60.4 60.4 60.4 60.4 63.0 54.6
75 60.6 57.4 66.1 41.5 69.7 26.0 55.6 54.9 63.4 40.3 68.1 24.7 50.8 50.8 58.5 38.0 65.5 23.2 46.5 46.5 53.0 35.5 62.1 21.5
80 64.0 64.0 67.0 52.5 70.6 38.5 60.4 60.4 63.9 52.4 69.0 36.1 56.1 56.1 59.2 50.5 66.1 35.8 51.8 51.8 54.0 48.1 62.5 33.8
57.8 51.4 65.2 38.8 69.6 25.4 52.9 48.8 61.8 37.0 67.3 23.9 48.2 46.3 56.5 34.6 64.6 22.4 43.3 43.3 51.2 32.1 60.9 20.7
67.6 67.6 67.6 67.6 71.6 52.5 65.2 65.2 65.2 65.2 69.5 53.3 62.0 62.0 62.0 62.0 66.0 52.6 58.0 58.0 58.0 58.0 62.0 51.8
2400
85
67.2 67.2 68.0 63.5 71.5 50.9 64.9 64.9 65.3 64.2 69.9 46.6 61.4 61.4 61.4 61.4 67.0 46.8 57.2 57.2 57.2 57.2 62.9 45.6
90 69.8 69.8 69.8 69.8 72.6 55.3 68.1 68.1 68.1 68.1 70.8 57.1 65.5 65.5 65.5 65.5 67.5 57.3 62.2 62.2 62.2 62.2 63.9 57.2
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-15 — Gross Cooling Capacities (MBH) 5Ton Three Phase THC060A3, A4, AW
AmbientTemperature (F)
85
95
105
67
115
67
Enter.
Dry
EnteringWet Bulb (F)
73 61
CFM
Bulb
61
67
73
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 56.6 49.0 64.4 37.5 67.7 24.7 52.0 46.8 60.9 35.7 66.2 23.3 47.0 44.2 55.9 33.3 63.6 21.8 42.3 41.7 50.0 30.7 59.8 20.0
80 58.5 58.5 64.6 47.0 68.6 34.7 54.7 54.7 61.2 45.5 66.8 33.3 50.6 50.6 56.3 43.2 64.1 31.7 46.4 46.4 50.5 40.5 60.0 29.8
85 62.9 62.9 65.3 56.4 69.4 42.2 59.6 59.6 61.9 55.5 67.7 42.3 55.6 55.6 57.3 53.2 64.3 41.1 51.2 51.2 51.9 50.7 60.3 39.5
90 66.2 66.2 66.4 65.6 70.3 50.3 63.7 63.7 63.7 63.7 68.4 51.2 60.3 60.3 60.3 60.3 64.9 50.3 56.4 56.4 56.3 56.3 60.8 49.1
1800
2000
2200
75 58.3 52.5 65.0 39.1 68.1 25.1 53.6 50.0 62.0 37.6 66.6 23.8 48.6 47.7 57.2 35.4 64.2 22.3 43.8 43.8 51.2 32.7 60.6 20.5
80 61.1 61.1 65.6 49.2 69.0 34.6 57.3 57.3 62.4 48.4 67.5 34.8 53.2 53.2 57.8 46.2 64.7 33.2 48.7 48.7 52.0 43.6 60.9 31.4
85 64.9 64.9 66.4 59.2 69.9 43.1 62.1 62.1 63.4 59.1 67.8 43.0 58.4 58.4 59.2 57.5 64.9 43.9 54.0 54.0 54.0 54.0 61.2 42.0
90
67.7 67.7 67.7 67.7 70.8 51.7 65.7 65.7 65.7 65.7 68.6 52.2 62.8 62.8 62.8 62.8 65.9 52.9 59.0 59.0 59.0 59.0 61.9 52.3
75 59.9 55.8 65.8 40.7 68.4 25.5 55.2 53.4 62.9 39.5 67.0 24.2 50.0 50.0 58.3 37.3 64.6 22.7 45.6 45.6 52.4 34.7 61.2 21.0
80 63.1 63.1 66.3 51.0 69.3 35.2 59.7 59.7 63.5 51.0 67.9 35.1 55.5 55.5 59.0 49.2 65.4 34.5 50.8 50.8 53.4 46.6 61.6 32.9
85 66.4 66.4 67.2 61.6 70.2 43.9 64.0 64.0 64.6 62.4 68.8 44.9 60.6 60.6 60.6 60.6 66.0 45.1 56.4 56.4 56.4 56.4 62.0 44.2
90 68.7 68.7 68.7 68.7 71.2 52.8 67.1 67.1 67.1 67.1 69.7 54.9 64.5 64.5 64.5 64.5 66.9 55.8 61.0 61.0 61.0 61.0 62.9 55.3
75 61.2 59.0 66.2 41.7 68.6 25.9 56.3 56.3 63.6 41.3 67.3 24.6 51.9 51.9 59.2 39.0 65.0 23.1 47.2 47.2 53.4 36.6 61.7 21.4
80 64.5 64.5 67.0 53.1 69.6 35.6 61.6 61.6 64.2 53.3 68.2 35.7 57.5 57.5 60.1 52.1 65.8 35.5 52.8 52.8 54.7 49.6 62.1 34.3
2400
85
67.3 67.3 68.1 64.0 70.5 44.7 65.4 65.4 65.6 65.2 69.1 46.0 62.4 62.4 62.3 62.3 66.6 46.8 58.4 58.4 58.4 58.4 62.6 46.2
90 69.4 69.4 69.5 69.5 71.5 53.9 68.1 68.1 68.1 68.1 70.1 56.3 65.7 65.7 65.7 65.7 67.6 58.0 62.5 62.5 62.5 62.5 63.7 57.9
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC005-EN
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(5Ton)
High Efficiency
Table PD-16 — Gross Cooling Capacities (MBH) 5Ton THC060A3, A4, AW – Dehumidification (Hot Gas Reheat) Option
AmbientTemperature (F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 50.7 36.2 57.0 29.4 63.7 22.6 48.1 34.6 54.2 27.9 60.7 21.0 45.5 32.9 51.3 26.2 57.5 19.4 42.7 31.2 48.2 24.5 54.1 17.7
80 50.8 41.8 57.1 35.1 63.8 28.2 48.3 40.2 54.4 33.5 60.8 26.6 45.6 38.6 51.5 31.9 57.6 25.0 42.9 36.8 48.4 30.1 54.2 23.3
85 51.0 47.5 57.2 40.7 64.0 33.8 48.6 45.9 54.5 39.1 61.0 32.2 46.0 44.2 51.6 37.4 57.8 30.6 43.3 42.5 48.5 35.7 54.4 28.8
90 52.2 52.2 57.4 46.3 64.1 39.4 50.1 50.1 54.6 44.7 61.1 37.8 47.8 47.8 51.7 43.0 57.9 36.1 45.5 45.5 48.7 41.3 54.5 34.4
1000
1300
1600
75 54.3 41.5 60.7 32.7 67.6 23.8 51.5 39.9 57.7 31.0 64.3 22.1 48.6 38.1 54.5 29.3 60.8 20.4 45.5 36.4 51.1 27.5 57.0 18.7
80 54.6 48.8 60.9 40.0 67.8 31.0 51.9 47.1 57.9 38.3 64.5 29.3 49.0 45.4 54.7 36.6 60.9 27.6 46.0 43.6 51.3 34.8 57.2 25.9
85 55.6 55.6 61.1 47.2 67.9 38.2 53.2 53.2 58.1 45.5 64.6 36.5 50.7 50.7 54.9 43.7 61.1 34.8 48.1 48.1 51.5 41.9 57.4 33.0
90 58.8 58.8 61.5 54.4 68.1 45.3 56.3 56.3 58.5 52.7 64.8 43.6 53.7 53.7 55.3 50.9 61.3 41.9 51.0 51.0 52.0 49.1 57.5 40.1
75 56.8 46.5 63.2 35.6 70.2 24.7 53.9 44.9 60.0 33.9 66.6 23.0 50.8 43.1 56.6 32.2 62.9 21.3 47.5 41.3 53.0 30.4 58.9 19.5
80
57.6 55.5 63.4 44.5 70.3 33.5 54.7 53.8 60.2 42.7 66.8 31.8 51.6 51.6 56.8 41.0 63.0 30.1 48.8 48.8 53.2 39.1 59.1 28.3
85 60.3 60.3 63.8 53.2 70.5 42.2 57.7 57.7 60.6 51.5 67.0 40.5 54.9 54.9 57.3 49.7 63.2 38.8 52.0 52.0 53.7 47.9 59.3 36.9
90 63.8 63.8 64.7 62.1 70.8 50.9 61.1 61.1 61.6 60.4 67.3 49.2 58.2 58.2 58.2 58.2 63.5 47.4 55.1 55.1 55.1 55.1 59.6 45.6
75 58.1 49.6 64.5 37.5 71.4 25.2 55.1 48.2 61.1 35.8 67.8 23.5 51.9 46.3 57.6 34.0 63.9 21.8 48.6 44.5 53.9 32.2 59.8 20.0
80 59.3 59.3 64.7 47.4 71.6 35.1 56.6 56.6 61.4 45.6 67.9 33.4 53.8 53.8 57.9 43.8 64.1 31.6 50.8 50.8 54.2 42.0 60.0 29.8
85 62.9 62.9 65.3 57.2 71.8 44.9 60.1 60.1 62.0 55.4 68.2 43.1 57.2 57.2 58.6 53.6 64.3 41.3 54.1 54.1 55.0 51.8 60.2 39.5
90 66.5 66.5 66.5 66.5 72.2 54.6 63.7 63.7 63.7 63.7 68.5 52.9 60.6 60.6 60.6 60.6 64.7 51.0 57.4 57.4 57.4 57.4 60.7 49.1
1800
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
26
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(6Ton)
High Efficiency
Table PD-17 — Gross Cooling Capacities (MBH) 6Ton Three Phase THC072A3, A4, AW
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 67.3 56.6 73.6 42.5 74.5 27.6 61.6 53.5 71.8 41.9 75.1 26.6 55.8 50.4 66.8 38.7 74.1 25.3 49.8 47.2 59.9 36.3 71.3 23.5
80 68.7 68.2 73.8 51.7 75.4 37.0 63.6 63.6 72.0 52.1 76.0 38.1 58.9 58.9 66.9 49.7 74.7 36.4 54.1 54.1 60.2 46.5 71.5 34.5
85 72.2 72.2 74.5 61.4 76.2 44.5 69.2 69.2 72.5 62.8 76.8 46.1 64.6 64.6 67.8 60.9 75.0 46.2 59.5 59.5 61.3 57.7 71.7 45.4
90 74.7 74.7 75.3 70.6 77.0 51.9 73.4 73.4 73.7 73.2 77.7 55.1 70.1 70.1 70.1 70.1 75.6 56.1 65.4 65.4 65.4 65.4 72.1 55.8
75 69.0 60.1 74.0 43.3 74.5 27.9 63.5 57.2 72.7 43.1 75.2 27.0 57.5 54.0 68.4 40.9 74.5 25.7 51.8 51.0 61.5 37.6 72.0 24.0
80 70.7 70.7 74.3 52.9 75.4 37.2 66.8 66.8 73.0 54.6 76.2 37.8 61.9 61.9 68.7 53.0 75.1 37.4 56.7 56.7 61.9 49.8 72.4 36.1
85 73.8 73.8 75.0 63.0 76.2 44.9 71.9 71.9 73.8 66.0 77.1 47.0 67.9 67.9 69.7 65.4 75.5 47.5 62.7 62.7 63.6 62.4 72.6 47.7
90 75.6 75.6 75.9 72.4 77.0 52.5 75.2 75.2 75.1 75.1 78.0 56.3 72.8 72.8 72.7 72.7 76.4 58.2 68.8 68.8 68.8 68.8 73.2 59.0
75 70.3 63.2 74.2 43.9 74.6 28.3 65.2 60.8 73.2 44.5 75.4 27.4 59.2 57.7 69.6 42.9 74.7 26.2 53.2 53.2 62.9 39.8 72.5 24.6
80 72.3 72.3 74.5 53.9 75.4 37.4 69.5 69.5 73.8 56.7 76.3 38.2 64.6 64.6 70.0 56.1 75.6 38.5 59.2 59.2 63.5 53.0 73.0 37.7
85 74.7 74.7 75.3 64.3 76.2 45.2 73.7 73.7 74.7 68.7 77.3 47.6 70.5 70.5 71.3 69.3 76.1 48.9 65.6 65.6 65.6 65.6 73.4 49.7
90 76.1 76.1 76.2 73.6 76.9 53.0 76.2 76.2 76.2 76.2 78.1 57.2 74.5 74.5 74.5 74.5 76.9 59.9 71.2 71.2 71.2 71.2 74.1 61.7
75 71.3 65.8 74.3 44.4 74.6 28.7 66.8 64.4 73.7 45.6 75.5 27.8 60.5 60.5 70.6 44.8 74.9 26.6 55.1 55.1 64.1 41.8 72.9 25.0
80 73.3 73.3 74.7 54.8 75.4 37.6 71.4 71.4 74.4 58.5 76.4 38.5 67.0 67.0 71.0 58.9 75.9 39.1 61.4 61.4 64.9 56.2 73.3 38.6
85 75.1 75.1 75.5 65.3 76.2 45.6 74.8 74.8 75.4 70.8 77.4 48.2 72.4 72.4 72.4 72.4 76.4 49.9 68.2 68.2 68.1 68.1 74.0 51.5
90 76.3 76.3 76.3 74.5 76.9 53.5 76.9 76.9 76.9 76.9 78.2 58.0 75.7 75.7 75.7 75.7 77.2 61.3 72.9 72.9 72.9 72.9 74.8 64.1
2160
2400
2640
2880
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC005-EN
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(7½Ton)
High Efficiency
Table PD-18 — Gross Cooling Capacities (MBH) 7½ Ton Three Phase THC092A3, A4, AW
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 85.7 72.4 95.8 56.8 99.9 37.1 79.3 69.3 92.0 53.7 98.8 35.8 72.8 66.0 85.9 50.8 96.1 34.2 66.1 62.6 78.5 49.1 91.8 32.2
80
87.5 87.0 96.2 68.5 101.1 50.4 81.8 81.8 92.4 67.4 99.6 50.2 76.6 76.6 86.2 64.6 96.7 48.0 71.1 71.1 79.0 61.4 92.0 45.8
2700
3000
3300
85 92.8 92.8 97.0 81.6 102.3 61.3 88.5 88.5 93.1 81.1 100.3 61.3 83.4 83.4 87.1 78.6 97.0 60.9 77.9 77.9 80.3 75.4 92.3 59.4
90
75
80 90.5 90.5 97.4 71.2 101.6 51.1 85.6 85.6 94.0 71.0 100.4 50.9 80.2 80.2 88.2 68.7 97.3 49.8 74.5 74.5 81.0 65.5 93.2 47.9
85 95.6 95.6 98.4 85.1 102.9 62.5 92.2 92.2 95.0 85.8 101.3 63.3 87.3 87.3 89.5 84.1 98.1 63.3 81.8 81.8 82.9 81.2 93.6 62.5
90 99.4 99.4 99.9 98.1 104.1 74.1 97.2 97.2 97.2 97.2 102.1 75.5 93.6 93.6 93.5 93.5 99.1 77.0 88.8 88.8 88.7 88.7 94.4 76.9
75 89.8 81.3 97.5 59.0 100.7 38.1 83.6 78.2 94.6 58.3 99.8 37.1 77.0 75.0 89.2 55.9 97.5 35.4 70.0 70.0 82.1 52.8 93.6 33.4
80 93.2 93.2 98.3 73.5 102.0 51.7 88.9 88.9 95.2 74.2 101.0 52.0 83.4 83.4 89.8 72.6 97.9 50.6 77.6 77.6 82.8 69.5 94.1 49.9
97.2 97.2 98.3 94.2 103.5 72.4 94.3 94.3 94.3 94.3 101.1 73.1 90.0 90.0 90.0 90.0 97.8 73.7 84.9 84.9 84.9 84.9 92.9 72.7
87.9 77.0 96.6 57.3 100.4 37.6 81.5 73.7 93.5 56.1 99.4 36.4 74.9 70.5 87.8 53.4 96.9 34.8 67.4 67.4 80.5 50.2 92.8 32.8
85
97.6 97.6 99.4 88.0 103.3 67.9 94.9 94.9 96.5 90.0 101.9 64.8 90.5 90.5 91.7 89.4 99.0 67.3 85.2 85.2 85.1 85.1 94.7 65.2
90 100.9 100.9 100.9 100.9 104.6 75.6 99.2 99.2 99.2 99.2 102.8 77.7 96.1 96.1 96.1 96.1 100.1 80.0 91.8 91.8 91.8 91.8 95.7 80.7
75 91.5 85.3 98.2 60.6 101.0 38.6 85.5 82.6 95.4 60.2 100.2 37.5 78.5 78.5 90.5 58.3 98.0 35.9 72.4 72.4 83.4 55.2 94.3 34.0
80 95.2 95.2 99.0 75.4 102.3 56.8 91.5 91.5 96.3 77.2 101.5 52.7 86.3 86.3 91.3 76.3 98.4 51.4 80.4 80.4 84.4 73.4 94.7 51.4
85 99.1 99.1 100.2 90.6 103.6 69.8 96.9 96.9 97.8 93.6 102.4 66.1 93.1 93.1 93.1 93.1 99.7 69.8 88.0 88.0 87.9 87.9 95.6 67.8
90 101.9 101.9 101.9 101.9 105.0 76.9 100.7 100.7 100.7 100.7 103.4 79.6 98.0 98.0 97.9 97.9 100.8 82.5 94.0 94.0 94.0 94.0 96.7 84.1
3600
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-19 — Gross Cooling Capacities (MBH) 7½ Ton Three Phase THC092A3, A4, AW – Dehumidification (Hot Gas Reheat) Option
AmbientTemperature (F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (F)
73
CFM
61
67
73
61
67
61
67
73
61
67
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 76.3 54.5 85.6 45.2 95.8 34.8 72.9 52.4 81.9 43.2 91.7 32.8 69.2 50.2 77.9 41.1 87.3 30.8 65.3 48.0 73.7 38.9 82.8 28.6
80 76.5 62.6 85.8 53.0 95.9 43.1 73.0 60.5 82.0 50.9 91.8 41.1 69.3 58.3 78.0 48.7 87.4 39.0 65.4 56.0 73.8 46.5 82.9 36.8
85 76.6 70.6 85.9 61.0 96.0 51.1 73.1 68.4 82.1 58.9 91.9 49.0 69.4 66.2 78.1 56.7 87.5 46.9 65.6 63.8 73.9 54.4 83.0 44.7
1500
1950
2400
90
77.3 77.3 86.1 69.0 96.1 59.0 74.5 74.5 82.3 66.9 92.0 57.0 71.5 71.5 78.3 64.6 87.7 54.8 68.3 68.3 74.0 62.3 83.1 52.6
75 81.6 61.9 91.2 49.4 101.6 36.5 77.7 59.7 87.0 47.2 97.1 34.5 73.7 57.5 82.6 45.0 92.3 32.3 69.4 55.1 78.0 42.7 87.3 30.1
80 81.9 72.2 91.3 59.6 101.7 47.0 78.1 70.0 87.2 57.5 97.2 44.8 74.0 67.7 82.8 55.2 92.4 42.6 69.8 65.4 78.2 52.9 87.4 40.4
85 82.3 82.3 91.6 69.9 101.9 57.1 79.2 79.2 87.4 67.7 97.3 55.0 75.8 75.8 83.0 65.4 92.6 52.8 72.3 72.3 78.4 63.1 87.6 50.5
90 86.9 86.9 91.9 80.0 102.0 67.2 83.6 83.6 87.8 77.8 97.5 65.1 80.2 80.2 83.4 75.5 92.7 62.8 76.5 76.5 78.9 73.2 87.8 60.6
75 85.2 68.7 94.9 53.4 105.5 37.9 81.1 66.5 90.5 51.2 100.7 35.8 76.8 64.2 85.8 48.9 95.6 33.6 72.3 61.8 80.9 46.6 90.3 31.4
80 86.0 81.3 95.1 65.8 105.6 50.4 82.0 79.1 90.7 63.6 100.8 48.2 77.9 76.9 86.0 61.4 95.7 46.0 73.4 73.4 81.2 59.0 90.4 43.7
85 89.2 89.2 95.5 78.2 105.8 62.7 85.7 85.7 91.1 76.0 101.0 60.5 82.0 82.0 86.5 73.7 95.9 58.2 78.1 78.1 81.6 71.3 90.6 55.9
90 94.2 94.2 96.4 90.6 106.1 74.9 90.6 90.6 92.1 88.4 101.3 72.8 86.8 86.8 87.6 86.2 96.2 70.4 82.8 82.8 82.8 82.8 90.9 68.1
75
87.1 73.0 96.8 57.3 107.4 38.7 82.9 70.9 92.2 55.1 102.5 36.6 78.5 68.6 87.4 52.9 97.2 34.4 73.9 66.2 82.3 50.6 91.8 32.2
80 88.4 87.3 97.0 69.7 107.6 52.5 84.2 84.2 92.5 67.5 102.6 50.4 80.4 80.4 87.7 65.2 97.4 48.1 76.4 76.4 82.7 62.8 91.9 45.8
85 92.9 92.9 97.6 83.5 107.8 66.2 89.3 89.3 93.1 81.3 102.8 64.0 85.4 85.4 88.4 79.0 97.6 61.8 81.3 81.3 83.4 76.7 92.1 59.4
90 98.2 98.2 99.1 97.6 108.1 79.8 94.4 94.4 94.4 94.4 103.2 77.6 90.4 90.4 90.4 90.4 98.0 75.3 86.2 86.2 86.2 86.2 92.5 73.0
2700
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
28
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(8½Ton)
High Efficiency
Table PD-20— Gross Cooling Capacities (MBH) 8½ Ton Three Phase THC102A3, A4, AW
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 94.0 81.8 105.7 62.8 110.8 40.9 86.3 77.8 100.7 59.7 109.7 39.3 79.0 74.2 92.4 56.0 105.5 37.1 71.8 70.5 84.0 53.1 99.6 34.6
80 96.9 96.9 106.2 77.6 112.0 56.0 90.6 90.6 101.1 75.9 110.1 55.4 84.5 84.5 92.9 72.2 106.1 53.2 78.3 78.3 84.7 68.5 99.8 50.6
85 103.5 103.5 107.2 92.9 113.2 68.7 98.6 98.6 102.2 92.1 111.6 70.3 92.1 92.1 94.5 88.8 106.4 68.8 85.8 85.8 86.7 85.2 100.0 66.5
90 108.4 108.4 109.0 107.7 114.4 81.6 105.0 105.0 105.0 105.0 112.6 84.9 99.9 99.9 99.9 99.9 107.3 83.9 93.5 93.5 93.5 93.5 100.8 82.6
75 96.6 87.2 107.1 64.7 111.4 41.5 88.7 83.3 102.4 62.6 110.7 40.1 81.4 79.6 94.4 59.1 106.6 37.9 74.2 74.2 85.9 55.4 101.1 35.5
80 100.9 100.9 107.7 81.0 112.7 56.9 94.9 94.9 103.0 80.4 111.7 57.5 88.3 88.3 95.2 77.1 107.3 55.7 81.8 81.8 86.8 73.4 101.4 53.1
85 106.6 106.6 108.9 97.4 114.0 70.2 102.6 102.6 104.4 97.8 112.8 72.9 96.5 96.5 97.6 95.6 108.0 72.4 89.9 89.9 89.8 89.8 101.8 70.8
90 110.8 110.8 110.8 110.8 115.3 83.8 108.1 108.1 108.1 108.1 114.0 88.5 103.8 103.8 103.8 103.8 108.9 88.3 97.8 97.8 97.8 97.8 102.8 87.9
75 98.9 92.5 107.4 65.9 112.0 42.2 91.2 88.7 103.7 65.4 111.1 40.7 83.5 83.5 96.3 62.2 107.5 38.7 76.9 76.9 87.5 58.4 102.2 36.2
80 103.7 103.7 108.8 84.0 113.3 57.7 98.7 98.7 104.5 84.5 112.4 58.7 91.7 91.7 97.3 81.9 108.3 57.6 85.0 85.0 88.8 78.2 102.6 55.5
85 108.8 108.8 110.1 100.9 114.6 76.9 105.4 105.4 106.4 103.0 113.7 75.1 100.2 100.2 100.2 100.2 109.3 75.7 93.4 93.4 93.4 93.4 103.1 74.4
90 112.3 112.3 112.1 112.1 115.9 85.7 110.4 110.4 110.4 110.4 114.9 91.4 106.5 106.5 106.5 106.5 110.2 92.3 101.3 101.3 101.3 101.3 104.4 92.7
75 100.9 97.3 108.1 67.4 112.5 42.9 93.1 93.1 104.7 67.9 111.5 41.4 86.2 86.2 97.8 65.2 108.2 39.4 79.4 79.4 88.8 61.3 103.0 36.9
80 105.9 105.9 109.5 86.2 113.8 58.4 101.6 101.6 105.8 88.2 112.8 59.6 94.9 94.9 99.1 86.5 109.2 59.6 87.9 87.9 90.6 82.8 103.5 57.8
85 110.2 110.2 110.9 103.4 115.1 79.5 107.6 107.6 107.6 107.6 114.1 76.6 103.0 103.0 103.0 103.0 109.9 77.6 96.6 96.6 96.6 96.6 104.2 77.7
90 112.9 112.9 112.9 112.9 116.5 87.5 112.2 112.2 112.2 112.2 115.4 93.4 108.6 108.6 108.6 108.6 111.3 95.9 103.9 103.9 103.9 103.9 105.8 97.0
3060
3400
3740
4080
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-21— Gross Cooling Capacities (MBH) 8½ Ton Three Phase THC102A3, A4, AW – Dehumidification (Hot Gas Reheat) Option
AmbientTemperature (F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (F)
73
CFM
61
67
73
61
67
61
67
73
61
67
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 84.4 60.9 94.7 49.8 105.6 38.0 80.3 58.5 90.3 47.5 100.8 35.7 75.9 56.0 85.6 45.0 95.7 33.3 71.3 53.3 80.6 42.4 90.3 30.8
80 84.5 70.3 94.8 59.1 105.8 47.6 80.4 67.9 90.4 56.7 100.9 45.2 76.1 65.3 85.7 54.1 95.9 42.7 71.5 62.6 80.7 51.5 90.5 40.2
85 84.8 79.7 94.9 68.4 105.9 56.8 80.8 77.3 90.6 66.0 101.1 54.4 76.5 74.7 85.9 63.4 96.0 51.9 72.2 71.0 80.9 60.8 90.6 49.3
1700
2210
2720
90
87.0 87.0 95.1 77.7 106.0 66.0 83.6 83.6 90.7 75.2 101.2 63.6 80.0 80.0 86.0 72.6 96.1 61.1 76.2 76.2 81.0 70.0 90.8 58.5
75 90.0 69.6 100.5 54.9 111.8 39.9 85.6 67.0 95.7 52.4 106.5 37.5 80.8 64.4 90.6 49.8 100.9 35.0 75.8 61.6 85.1 47.1 95.1 32.4
80 90.5 81.7 100.7 66.8 111.9 51.9 86.1 79.2 95.9 64.3 106.7 49.5 81.5 76.6 90.8 61.7 101.1 47.0 76.6 73.8 85.3 59.0 95.3 44.3
85 92.3 92.3 101.0 78.8 112.1 63.8 88.6 88.6 96.1 76.3 106.8 61.3 84.6 84.6 91.0 73.6 101.3 58.7 80.3 80.3 85.6 70.9 95.4 56.1
90
97.5 97.5 101.5 90.7 112.3 75.6 93.6 93.6 96.7 88.2 107.0 73.1 89.5 89.5 91.7 87.1 101.5 70.5 85.1 85.1 86.4 82.9 95.6 67.9
75 94.0 77.6 104.4 59.5 115.8 41.4 89.3 75.1 99.3 57.0 110.2 38.9 84.3 72.4 93.8 54.4 104.3 36.4 79.0 69.6 88.1 51.7 98.2 33.8
80 95.2 92.6 104.7 74.1 116.0 55.9 90.7 90.1 99.5 71.5 110.4 53.4 86.0 86.0 94.1 68.9 104.5 50.9 81.4 81.4 88.4 66.2 98.4 48.2
85 99.8 99.8 105.2 88.7 116.2 70.3 95.7 95.7 100.1 86.1 110.6 67.8 91.3 91.3 94.7 83.5 104.7 65.2 86.6 86.6 89.1 80.7 98.6 62.5
90 105.4 105.4 106.5 103.4 116.5 84.7 101.1 101.1 101.6 100.9 110.9 82.1 96.6 96.6 96.6 96.6 105.1 79.5 91.8 91.8 91.8 91.8 98.9 76.9
75 96.1 82.8 106.4 63.2 117.8 42.2 91.3 80.2 101.0 60.7 112.1 39.8 86.2 77.5 95.4 58.1 106.0 37.2 80.8 74.7 89.6 55.4 99.7 34.6
80 98.1 98.1 106.7 78.8 118.1 58.5 93.8 93.8 101.4 76.2 112.2 55.9 89.3 89.3 95.8 73.5 106.2 53.3 84.6 84.6 90.0 70.8 99.9 50.7
85 103.8 103.8 107.5 95.1 118.3 74.5 99.5 99.5 102.3 92.5 112.5 72.0 94.8 94.8 96.9 89.9 106.4 69.4 89.9 89.9 91.2 87.2 100.1 66.7
90 109.7 109.7 109.7 109.7 118.7 90.6 105.2 105.2 105.2 105.2 112.9 88.1 100.4 100.4 100.4 100.4 106.9 85.4 95.4 95.4 95.4 95.4 100.7 82.7
3060
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
RT-PRC005-EN
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(10 Ton)
High Efficiency
Table PD-22 — Gross Cooling Capacities (MBH) 10 Ton Three Phase THC120A3, A4, AW
AmbientTemperature (F)
85
95
105
115
67
Enter.
Dry
EnteringWet Bulb (F)
73
CFM
Bulb
61
67
73
61
67
61
67
73
61
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 107.0 94.4 117.4 75.0 123.4 46.0 98.7 90.1 114.7 68.8 121.9 44.4 88.5 88.5 107.2 65.3 118.6 42.2 82.3 78.8 97.8 61.1 113.6 39.6
80 110.9 108.6 119.9 88.2 125.0 62.5 104.5 104.1 115.2 87.5 123.4 62.3 97.7 97.7 107.8 84.3 119.4 60.8 90.6 90.6 98.5 80.1 114.3 58.3
85 117.6 117.6 120.9 105.0 126.6 76.7 113.1 113.1 116.5 105.8 124.9 78.1 106.9 106.9 107.0 107.0 120.9 78.1 99.9 99.9 100.0 100.0 114.8 76.5
90 122.5 122.5 122.4 122.4 128.2 91.1 119.6 119.6 119.6 117.1 126.4 94.1 115.0 115.0 114.7 114.6 121.6 94.3 109.0 109.0 109.0 109.0 115.8 94.3
3600
4000
4400
75 109.8 100.5 119.4 71.9 122.5 46.5 99.7 99.7 116.1 71.5 121.7 45.0 92.5 92.5 110.1 69.1 119.4 43.0 85.6 83.4 100.9 65.0 114.6 40.5
80 114.6 114.1 120.8 90.1 124.1 68.3 109.3 109.3 117.0 91.2 123.4 62.7 102.3 102.3 110.8 89.9 120.6 62.5 94.8 94.8 101.9 86.0 115.5 61.1
85 120.5 120.5 122.3 107.9 125.9 76.4 117.0 117.0 118.6 110.2 125.0 78.8 111.6 111.6 111.8 111.8 122.1 80.4 104.7 104.7 105.8 102.6 116.3 79.7
90 125.2 125.2 124.2 124.2 127.6 90.9 122.4 122.4 121.7 120.9 126.6 95.1 118.5 118.5 118.3 118.3 123.6 98.4 113.1 113.1 113.3 113.3 117.7 98.6
75 112.3 106.1 121.2 74.8 124.6 47.6 103.6 103.6 117.1 75.5 123.0 46.0 96.7 93.9 111.2 72.2 120.0 43.7 88.6 88.0 102.0 68.2 115.3 41.2
80 117.6 117.6 122.5 94.7 126.3 64.2 113.0 113.0 118.4 95.8 124.7 64.4 106.3 106.3 112.2 94.9 121.5 64.3 98.8 98.8 103.5 91.1 116.1 62.8
85 122.4 122.4 124.3 113.8 128.0 79.6 119.6 119.6 119.6 119.6 126.4 81.8 115.1 115.1 115.5 111.7 122.7 83.0 109.1 109.1 108.8 107.4 117.2 83.2
90 126.0 126.0 127.1 125.0 129.6 95.2 124.3 124.3 124.2 124.2 128.0 99.4 120.9 120.9 120.9 120.9 123.9 101.2 116.1 116.1 116.1 116.1 118.8 103.3
75 113.4 113.4 121.8 76.2 125.0 48.4 107.6 104.0 118.5 77.0 123.5 46.9 99.6 98.2 112.7 75.4 120.5 44.8 91.6 91.6 103.7 71.6 115.9 41.9
80 119.5 119.5 123.2 97.0 126.7 64.8 115.8 115.8 119.8 99.6 125.2 65.3 109.8 109.8 113.9 99.4 122.1 65.5 102.3 102.3 105.5 96.3 117.2 66.8
85 124.3 124.3 125.2 116.6 128.4 80.7 121.5 121.5 121.5 121.5 126.9 83.3 117.5 117.5 117.6 115.4 123.7 85.6 111.8 111.8 111.8 111.8 118.5 86.4
90 127.5 127.5 128.0 126.7 130.1 96.9 126.0 126.0 125.5 125.5 128.6 101.5 122.6 122.6 123.0 123.0 125.5 105.5 118.2 118.2 118.2 118.2 120.3 107.5
4800
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
Table PD-23— Gross Cooling Capacities (MBH) 10Ton THC120A3, A4, AW – Dehumidification (Hot Gas Reheat) Option
AmbientTemperature (F)
85
95
105
115
Enter.
Dry
Bulb
EnteringWet Bulb (F)
73 61
CFM
61
67
73
61
67
67
73
61
67
73
Airflow
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 94.2 68.9 105.8 56.2 118.4 42.6 89.7 66.2 101.0 53.6 113.2 40.0 84.8 63.4 95.8 50.9 107.6 37.3 79.7 60.4 90.2 48.1 101.5 34.6
80 94.4 79.8 106.0 66.8 118.6 53.6 89.9 77.1 101.2 64.1 113.4 51.0 85.0 74.2 96.0 61.4 107.8 48.3 79.9 71.2 90.4 58.4 101.7 45.4
85 93.0 93.0 106.3 77.6 118.8 64.3 90.4 86.3 101.4 74.9 113.6 61.7 86.1 82.8 96.2 72.1 108.0 59.0 81.6 79.1 90.7 69.2 101.9 56.1
90 98.0 97.2 106.4 88.3 119.0 75.0 94.4 94.4 101.6 85.6 113.8 72.4 90.4 90.4 96.4 82.8 108.2 69.6 86.1 86.1 90.9 79.8 102.1 66.7
2000
2600
3200
75 100.5 78.8 112.6 62.6 125.6 44.8 95.6 76.0 107.3 59.9 119.9 42.2 90.4 73.0 101.6 57.1 113.8 39.5 84.8 70.0 95.6 54.1 107.2 36.6
80 101.1 92.6 112.9 75.8 125.8 58.8 96.4 89.9 107.6 73.1 120.1 56.1 89.7 89.7 101.9 70.2 114.0 53.3 86.0 81.9 95.8 67.1 107.4 50.4
85 104.0 102.0 113.2 89.6 126.1 72.5 99.7 98.7 107.9 86.8 120.4 69.8 95.4 95.4 102.3 83.9 114.2 67.0 90.6 90.6 96.2 80.9 107.6 64.0
90 109.9 109.9 113.9 103.3 126.4 86.1 105.6 105.6 108.7 100.5 120.7 83.4 101.1 101.1 101.1 101.1 114.5 80.6 96.2 96.2 97.5 92.3 107.9 77.6
75 104.9 87.8 117.1 67.4 130.2 46.6 99.8 85.0 111.5 65.7 124.2 44.0 94.3 82.0 110.8 64.8 117.7 41.2 88.4 78.9 99.0 59.8 110.7 38.2
80 106.6 102.0 117.4 84.1 130.5 63.4 102.0 98.4 111.8 81.3 124.5 60.6 97.0 94.6 105.8 78.4 118.0 57.8 91.6 90.5 99.4 75.3 111.0 54.8
85 112.2 112.2 118.1 100.7 130.8 79.9 107.8 107.8 112.6 98.0 124.7 77.2 103.0 103.0 106.7 95.0 118.2 74.3 97.7 97.7 100.4 91.9 111.2 71.3
90 118.6 118.6 118.8 118.8 131.1 96.5 114.2 114.2 115.0 110.5 125.1 93.7 109.2 109.2 109.6 106.5 118.7 90.8 103.8 103.8 103.9 102.2 111.7 87.8
75 107.3 93.6 119.4 70.7 132.5 47.7 102.1 90.8 113.6 67.9 126.3 45.0 96.5 87.8 107.2 64.9 119.4 42.1 90.4 84.7 100.6 61.8 112.1 39.1
80 110.3 107.5 119.7 89.4 132.8 66.3 105.6 104.0 114.0 86.6 126.6 63.5 100.4 100.3 107.6 83.5 119.6 60.5 95.1 95.1 101.1 80.4 112.4 57.5
85 116.7 116.7 120.8 107.9 133.2 84.7 112.2 112.2 115.2 105.1 126.9 82.0 107.1 107.1 108.9 102.1 119.9 79.0 101.4 101.4 101.4 101.4 112.7 75.9
90 123.5 123.5 124.2 120.7 133.7 103.1 118.8 118.8 119.0 116.9 127.5 100.3 113.6 113.6 113.2 112.8 120.6 97.3 107.7 107.7 107.7 107.7 113.4 94.2
3600
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
30
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(3, 4, 5Ton)
Standard Efficiency
Table PD-24— Direct Drive Evaporator Fan Performance 3, 4 and 5 Ton TSC036A, TSC048A, TSC060A
External Static Pressure (Inches ofWater) & Motor Power (Bhp)1
Standard Motor
High Speed Low Speed
ESP ESP
Oversized Motor
High Speed Low Speed
ESP ESP
Unit
Model No. CFM
Tons
3
BHP
0.36
0.37
0.38
0.39
0.40
0.41
0.42
0.42
0.43
0.53
0.54
0.54
0.55
0.55
0.56
0.56
0.57
0.57
0.78
0.82
0.85
0.88
0.90
0.93
0.95
0.97
1.00
0.36
0.37
0.38
0.39
0.40
0.41
0.42
0.42
0.43
0.53
0.54
0.54
0.55
0.55
0.56
0.56
0.57
0.57
0.78
0.82
0.85
0.88
0.90
0.93
0.95
0.97
1.00
BHP
0.28
0.28
0.29
0.29
0.30
0.30
0.31
0.31
—
BHP
0.39
0.41
0.43
0.44
0.45
0.46
0.48
0.49
0.52
0.67
0.68
0.70
0.73
0.75
0.78
0.82
0.83
0.85
0.90
0.94
0.98
1.02
1.05
1.10
1.12
1.17
1.20
0.39
0.41
0.43
0.44
0.45
0.46
0.48
0.49
0.52
0.67
0.68
0.70
0.73
0.75
0.78
0.82
0.83
0.85
0.90
0.94
0.98
1.02
1.05
1.10
1.12
1.17
1.20
BHP
0.35
0.47
0.39
0.40
0.41
0.42
0.44
0.45
0.48
0.56
0.58
0.60
0.63
0.64
0.66
0.68
0.70
0.73
0.85
0.89
0.91
0.94
0.95
0.96
0.96
0.97
—
0.35
0.47
0.39
0.40
0.41
0.42
0.44
0.45
0.48
0.56
0.58
0.60
0.63
0.64
0.66
0.68
0.70
—
960
1020
1080
1140
0.81
0.77
0.73
0.69
0.66
0.60
0.55
0.49
0.44
0.93
0.87
0.80
0.73
0.66
0.57
0.47
0.37
0.27
0.90
0.85
0.80
0.70
0.60
0.50
0.40
0.30
0.20
0.86
0.82
0.78
0.74
0.71
0.65
0.60
0.54
0.49
0.98
0.92
0.85
0.78
0.71
0.62
0.52
0.42
0.32
0.95
0.90
0.85
0.75
0.65
0.55
0.45
0.35
0.25
0.61
0.57
0.50
0.42
0.34
0.26
0.14
0.05
—
0.81
0.75
0.68
0.60
0.51
0.38
0.23
0.13
—
0.82
0.68
0.56
0.46
0.30
0.14
0.05
—
0.96
0.94
0.91
0.88
0.84
0.80
0.75
0.70
0.64
1.20
1.15
1.10
1.05
1.00
0.95
0.90
0.83
0.75
1.20
1.15
1.05
0.98
0.90
0.80
0.70
0.60
0.48
1.01
0.99
0.96
0.93
0.89
0.85
0.80
0.75
0.69
1.25
1.20
1.15
1.10
1.05
1.00
0.95
0.88
0.80
1.25
1.20
1.10
1.03
0.95
0.85
0.75
0.65
0.53
0.89
0.86
0.82
0.77
0.74
0.70
0.65
0.59
0.54
0.99
0.94
0.88
0.81
0.74
0.65
0.50
0.35
0.25
1.05
0.95
0.85
0.75
0.65
0.50
0.35
0.15
—
0.89
0.91
0.87
0.82
0.79
0.75
0.70
0.64
0.59
1.04
0.99
0.93
0.86
0.79
0.70
0.55
0.40
—
TSC036A 1200
Horizontal 1260
1320
1380
1440
1280
1360
1440
1520
0.47
0.47
0.48
0.48
0.49
0.49
0.50
0.50
—
0.64
0.65
0.65
0.65
0.66
0.66
0.67
—
4
5
3
4
5
TSC048A 1600
Horizontal 1680
1760
1840
1920
1600
1700
1800
1900
TSC060A3 2000
Horizontal 2100
2200
2300
2400
960
1020
1080
1140
—
—
0.61
0.62
0.55
0.47
0.39
0.31
0.19
0.10
—
0.86
0.80
0.73
0.65
0.56
0.43
0.28
0.18
—
0.87
0.73
0.61
0.51
0.35
0.19
0.10
—
0.28
0.28
0.29
0.29
0.30
0.30
0.31
0.31
—
0.47
0.47
0.48
0.48
0.49
0.49
0.50
0.50
—
0.64
0.65
0.65
0.65
0.66
0.66
0.67
—
TSC036A 1200
Downflow 1260
1320
1380
1440
1280
1360
1440
1520
TSC048A 1600
Downflow 1680
1760
1840
1920
1600
1700
1800
1900
1.10
1.00
0.90
0.80
0.70
0.55
0.40
0.20
—
0.85
0.89
0.91
0.94
0.95
0.96
0.96
0.97
—
TSC060A3 2000
Downflow 2100
2200
2300
2400
—
—
Fan motor heat (MBH) = 3.72 x Fan Bhp + .24.
Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product’s warranty will not be affected.
NOTES:
1. Data includes pressure drop due to wet coil and filters.
2. 5 ton oversized motor performance is with 12 x 11 FC blower wheel.
3. YSC060AK uses a 1.0 hp direct drive motor and 12x11 FC centrifugal blower wheel. Refer to oversized motor column for the standard motor
performancedata.
RT-PRC005-EN
31
Download from Www.Somanuals.com. All Manuals Search And Download.
(3Ton)
Standard Efficiency
Performance
Data
Table PD-25 — Belt Drive Evaporator Fan Performance — 3 Ton — TSC036A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HPStandardMotor
&FieldSupplied
LowStaticDrive(1)
1-HPStandardMotor&Drive
960
—
—
—
552
588
—
—
—
0.18
0.23
528
557
588
622
657
0.12
0.15
0.19
0.23
0.28
599
625
652
681
713
0.16
0.19
0.23
0.27
0.33
658
685
712
738
765
0.20
0.24
0.28
0.32
0.37
713
738
764
790
817
0.24
0.28
0.33
0.38
0.43
763
786
811
838
865
0.29
0.33
0.38
0.44
0.50
810
832
856
882
909
0.33
0.38
0.43
0.49
0.56
855
876
898
923
949
0.38
0.43
0.48
0.55
0.62
898 0.43
917 0.48
939 0.54
962 0.60
987 0.68
939 0.49
957 0.54
978 0.59
1000 0.66
1024 0.74
1080
1200
1320
1440
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. FieldSuppliedFanSheaveAK69required. FieldSuppliedBeltmaybenecessary.
2. FieldSuppliedFanSheaveAK41required.FieldSuppliedBeltmaybenecessary.
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedto
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in
our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
Table PD-25 — Continued
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
1-HPStandardMotor&Drive
960
978
995
1015
1036
1060
0.54
0.59
0.65
0.72
0.80
1016
1033
1051
1072
1094
0.60
0.65
0.71
0.78
0.86
1052
0.66
0.71
0.77
0.85
0.93
1086
1103
1120
1138
1160
0.72
0.78
0.84
0.91
1.00
1120
1136
1154
1171
1192
0.78
0.84
0.91
0.98
1.07
1080
1200
1320
1440
1069
1086
1106
1128
1-HPStandardMotor&
FieldSuppliedHighStaticDrive(2)
Table PD-26 — Belt Drive Evaporator Fan Performance — 3 Ton — TSC036A3,A4,AW — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard Motor & Field Supplied
1-HPStandardMotor&Drive
Low Static Drive (1)
960
—
—
588
622
654
687
723
0.15
0.18
0.23
0.28
0.33
661
694
727
760
793
0.19
0.24
0.28
0.34
0.40
725
756
787
821
855
0.24
0.29
0.34
0.40
0.47
782
813
843
875
908
0.29
0.34
0.40
0.46
0.53
832
864
895
925
956
0.35
0.40
0.46
0.53
0.60
878
910
942
0.40
0.46
0.52
0.59
919
954
986
0.46
0.52
0.59
958 0.51
993 0.59
1026 0.66 1064 0.73
996 0.56
1031 0.65
1080
1200
1320
1440
531
570
610
651
0.13
0.17
0.22
0.27
973
1017
0.66 1058 0.73 1095 0.81
0.75 1088 0.82 1127 0.89
1003
0.67 1047
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils
1-HPStandardMotor&
Field Supplied High Static Drive (2)
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. FieldSuppliedFanSheaveAK69required. FieldSuppliedBeltmaybenecessary.
2. FieldSuppliedFanSheaveAK41required.FieldSuppliedBeltmaybenecessary.
Table PD-26 — Continued
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
1-HPStandardMotor&Drive
960
1032 0.62
1066
1099
1133
1167
1199
0.67
0.76
0.86
0.96
1.05
1101
0.73
0.82
0.93
1.04
1.14
1133
1164
1197
1230
1263
0.79
0.89
0.99
1.11
1.22
1166
1194
1227
1261
1294
0.86
0.95
1.06
1.19
1.30
1080
1200
1320
1440
1065
1099
1132
1164
0.70
0.80
0.88
0.97
1132
1166
1200
1232
1-HPStandardMotor&
FieldSuppliedHighStaticDrive(2)
32
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
(4Ton)
Standard Efficiency
Performance
Data
Table PD-27 — Belt Drive Evaporator Fan Performance — 4 Ton — TSC048A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard Motor & Field Supplied
1-HP Standard Motor & Drive
Low Static Drive (1)
1280
1440
1600
1760
1920
—
—
616
663
711
758
807
0.22
0.29
0.37
0.46
0.57
677
719
764
811
859
0.26
0.33
0.42
0.52
0.64
734
772
813
856
903
0.31
0.38
0.47
0.58
0.71
787
823
860
901
945
0.37
0.44
0.53
0.64
0.77
834
871
906
944
985
0.42
0.51
0.59
0.70
0.83
878
914
951
986
1024
0.48
0.57
0.66
0.77
919
954
992
0.53
0.63
0.74
959 0.59
993 0.69
1029 0.80 1065 0.87
997 0.64
1029 0.75
596
647
701
755
0.23
0.31
0.41
0.52
1027
0.85 1066 0.93
0.97 1101 1.05
1102 1.00
1137 1.14
0.89 1063
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. FieldSuppliedFanSheaveAK61required. FieldSuppliedBeltmaybenecessary.
Table PD-27 — Continued
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
1-HPStandardMotor&Drive
1280
1440
1600
1760
1920
1033
1066
1099
1136
1172
0.70
0.81
0.93
1.08
1.23
1069
1099
1132
1168
1205
0.77
0.87
1.00
1.15
1.31
1103
0.83
0.94
1.07
1.22
1.39
1136
1165
1196
1229
—
0.89
1.01
1.14
1.29
—
1170
1196
1228
—
0.96
1.08
1.21
—
1133
1166
1200
1236
—
—
Table PD-28 — Belt Drive Evaporator Fan Performance — 4 Ton — TSC048A3,A4,AW — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
RPM BHP
1.00
RPM BHP
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HP Standard Motor & Field Supplied
1-HPStandardMotor&Drive
Low Static Drive (1)
1280
1440
1600
1760
1920
604
660
717
774
833
0.20
0.28
0.36
0.47
0.59
683
731
783
837
892
0.26
0.34
0.43
0.54
0.67
756
800
846
894
946
0.32
0.41
0.51
0.62
0.76
816
862
907
952
998
0.39
0.48
0.58
0.70
0.85
869
914
961
1006
1050
0.45
0.54
0.66
0.79
0.94
920
963
1008
1054
1100
0.51
0.61
0.73
0.87
1.03
967
0.57
0.68 1053
0.81 1095
1011
0.64
1052 0.71 1090 0.79
1009
1053
1098
1144
0.76 1094 0.83
1133 0.91
1174 1.05
1216 1.21
1259 1.39
0.89
1.04
1.21
1135 0.97
1178 1.12
1224 1.30
0.95
1.12
1139
1185
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1-HPStandardMotor&
FieldSuppliedHighStaticDrive
1. FieldSuppliedFanSheaveAK61required. FieldSuppliedBeltmaybenecessary.
2. FieldSuppliedFanSheaveAK41required.FieldSuppliedBeltmaybenecessary.
Table PD-28 — Continued
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
1-HPStandardMotor&Drive
1280
1440
1600
1760
1920
1125
1169
1211
1253
1295
0.86
0.98
1.13
1.30
1.48
1160
1204
1247
1289
—
0.94
1.07
1.21
1.39
—
1192
1.01
1.15
1.30
1.47
—
1223
1269
1312
—
1.08
1.23
1.39
—
1254
1300
1343
—
1.15
1.32
1.48
—
1237
1280
1322
—
—
—
—
—
1-HPStandardMotor&
FieldSuppliedHighStaticDrive
RT-PRC005-EN
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(5Ton)
Standard Efficiency
Table PD-29— Belt Drive Evaporator Fan Performance — 5 Ton — TSC060A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard Motor & Field Supplied
1-HP Standard Motor & Drive
Low Static Drive (1)
1600
1800
2000
2200
2400
674
743
813
886
959
0.33
0.46
0.61
0.80
1.03
735
801
0.39
0.52
0.68
0.87
1.10
786
849
914
0.45
0.59
0.76
0.96
1.19
835
894
956
0.50
0.65
0.83
1.03
1.28
883
937
995
1057
1121
0.56
0.70
0.89
1.11
1.36
928
979
1035
1093
1154
0.63
0.77
0.96
1.18
1.45
972
1021
1073
1129
1188
0.70
0.85 1060
1011
0.77
1048 0.84 1084 0.90
0.93 1098 1.01
1134 1.09
1183 1.28
1233 1.50
866
933
1000
1.02
1.25
1.53
1111
1164
1221
1.10
1.33
1.60
1147 1.19
1198 1.40
—
980
1045
1019
1085
—
—
—
Trane’s factory supplied motors, in commercial equipment, are
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
1. FieldSuppliedFanSheaveAK56required. FieldSuppliedBeltmaybenecessary.
Table PD-29 — Continued
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
1-HPStandardMotor&Drive
1600
1800
2000
2200
2400
1117
1167
1216
—
0.97
1.16
1.37
—
1150
1199
1249
—
1.04
1.24
1.47
—
1183
1.11
1.31
—
—
—
1215
1259
—
—
—
1.18
1.39
—
—
—
1244
1289
—
—
—
1.25
1.47
—
—
—
1230
—
—
—
—
—
—
—
Table PD-30 — Belt Drive Evaporator Fan Performance — 5 Ton — TSC060A3,A4,AW — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard Motor & Field Supplied
Low Static Drive (1)
1-HPStandardMotor&Drive
1600
1800
2000
2200
2400
746
824
902
981
1061
0.39
0.54
0.72
0.93
1.19
812
883
957
1032
1109
0.47
0.62
0.80
1.03
1.29
876
940
1008
1080
1153
0.54
0.70
0.90
1.13
1.40
934
996
1059
1126
1196
0.62
0.79
0.99
1.23
1.50
985
1048
1110
1173
—
0.70
0.88
1.09
1.34
—
1032
1094
1157
1219
—
0.77
0.96
1.19
1.44
—
1074
1137
1200
—
0.85
1.05
1.28
—
1117
1176
1239
—
0.93
1.14
1.38
—
1157 1.01
1214 1.22
1276 1.47
1196 1.09
1252 1.31
1311 1.50
—
—
—
—
—
—
—
—
—
—
—
—
Trane’s factory supplied motors, in commercial equipment, are
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories.
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
1. FieldSuppliedFanSheaveAK56required. FieldSuppliedBeltmaybenecessary.
Table PD-30 — Continued
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
1-HPStandardMotor&Drive
1600
1800
2000
2200
2400
1232
1289
—
—
—
1.18
1.41
—
1267
1323
—
1.26
1.50
—
1299
1.35
—
—
—
—
1332
—
—
—
—
1.45
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
34
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(6 Ton)
Standard Efficiency
Table PD-31 — Belt Drive Evaporator Fan Performance — 6-Ton — TSC072A3,A4,AW — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard Motor & Field Supplied
1-HPStandardMotor&Drive
Low Static Drive (1)
1920
2160
2400
2640
2880
—
—
—
—
—
—
—
573
602
635
670
706
0.34
0.42
0.52
0.64
0.78
630
656
682
715
749
0.41
0.50
0.60
0.72
0.86
680
706
732
758
789
0.48
0.58
0.69
0.81
0.96
726
751
777
802
830
0.55
0.65
0.77
0.91
1.06
769
792
818
845
870
0.62
0.73
0.86
1.01
1.16
811
832
856
883
909
0.70
0.81
0.95
1.10
1.27
851 0.78
871 0.90
893 1.04
919 1.20
945 1.37
889 0.87
908 0.99
930 1.13
953 1.29
979 1.48
548
584
621
660
0.35
0.45
0.56
0.69
—
569
612
0.47
0.60
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories.
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. FieldSuppliedFanSheaveAK84andBeltAX34required.
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
Table PD-31 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
BHP
1 HP Standard Motor & Drive
1.20
1.30
BHP
1.70
BHP
1.80
RPM
1.90
2.00
CFM
RPM
RPM
BHP
RPM
RPM
BHP RPM RPM BHP
BHP
RPM
BHP
RPM BHP
RPM BHP
1HP Standard Motor & High Static Drive Kit
(or2HPOversizedMotor&Drive)
1920
2160
2400
2640
2880
925
944
964
986
1011
0.95
1.08
1.22
1.39
1.58
960
978
998
1019
1043
1.03
1.17
1.32
1.49
1.69
994
1.11
1.26
1.42
1.60
1.79
1026
1043
1063
1082
1103
1.19
1.36
1.53
1.71
1.90
1057
1073
1092
1112
1133
1.27
1.44
1.63
1.81
2.02
1087
1104
1123
1141
1161
1.36
1.54
1.73
1.92
2.13
1116
1133
1151
1169
1190
1.44
1.63
1.83
2.03
2.26
1144
1162
1179
1198
—
1.52
1.72
1.93
1173 1.61
1189 1.81
1206 2.03 1233 2.13
1200 1.70
1216 1.91
1010
1030
1051
1073
2.15 1225 2.26
—
—
—
—
—
—
—
2HPOversizedMotor&Drive
Table PD-32 — Belt Drive Evaporator Fan Performance — 6-Ton — TSC072A3,A4,AW — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HPStandardMotor
&FieldSupplied
LowStaticDrive(1)
1-HPStandardMotor&Drive
1920
2160
2400
2640
2880
—
—
565
609
660
710
762
0.31
0.41
0.54
0.68
0.86
627
663
701
745
795
0.39
0.48
0.60
0.76
0.94
679
716
751
788
828
0.45
0.57
0.69
0.83
1.02
726
762
798
833
869
0.52
0.64
0.78
0.93
1.11
771
804
839
875
911
0.60
0.72
0.87
1.04
1.21
814
843
877
914
950
0.69
0.80
0.95
1.13
1.33
857
883
914
949
986
0.77
0.90
1.04
1.22
1.44
899 0.85
922 0.99
950 1.14
984 1.31
1019 1.53
2-HPOversized
Motor&Drive
939 0.93
960 1.08
984 1.24
1016 1.42
1051 1.63
566
619
672
726
0.35
0.47
0.61
0.77
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop
duetootheroptionsaccessories.
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. FieldSuppliedFanSheaveAK84andBeltAX34required.
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
1HP Standard Motor & High Static Drive
Kit (or 2 HP Oversized Motor & Drive)
Table PD-32 — Continued
External Static Pressure (Inches of Water)
1.10
RPM
1.20
RPM
1.30
RPM
1.40
RPM
1.50
RPM
1.60
RPM
1.70
RPM
1.80
1.90
RPM BHP
2.00
RPM BHP
CFM
BHP
BHP
BHP
BHP
BHP
BHP
BHP
RPM
BHP
1-HP Standard
Motor& Drive
1-HP Standard Motor & High Static Drive Kit
(or 2 HP oversized Motor& Drive)
1920
2160
2400
2640
2880
978
996
1020
1049
1081
1.02
1015
1034
1055
1081
1112
1.11
1.27
1.45
1.65
1.86
1051
1069
1089
1113
1141
1.20
1.36
1.55
1.76
1.97
1086
1103
1122
1144
1170
1.30
1.46
1.66
1.87
2.10
1118
1136
1154
1176
1199
1.39
1.56
1.76
1.98
2.22
1150
1169
1186
1207
—
1.49
1.67
1.86
2.10
—
1180
1199
1216
1237
—
1.58
1.77
1.97
2.21
—
1209
1229
1246
—
1.68
1.88
1236 1.77
1258 1.98
1263 1.86
1.17
1.35
1.53
1.74
—
—
—
—
—
—
—
—
2.08 1276 2.20
—
—
—
—
—
—
—
2-HPOversizedMotor&Drive
RT-PRC005-EN
35
Download from Www.Somanuals.com. All Manuals Search And Download.
(6 Ton)
Standard Efficiency
Performance
Data
Table PD-33 — Belt Drive Evaporator Fan Performance — 6-Ton — TSC072,AK — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&FieldSuppliedLowStaticDrive(1)
2-HPStandardMotor&Drive
1920
2160
2400
2640
2880
-
-
-
-
-
-
-
573
602
635
670
706
0.34
0.42
0.52
0.64
0.78
630
656
682
715
749
0.41
0.50
0.60
0.72
0.86
680
706
732
758
789
0.48
0.58
0.69
0.81
0.96
726
751
777
802
830
0.55
0.65
0.77
0.91
1.06
769
792
818
845
870
0.62
0.73
0.86
1.01
1.16
811
832
856
883
909
0.70
0.81
0.95
1.10
1.27
851 0.78
871 0.90
893 1.04
919 1.20
945 1.37
889 0.87
908 0.99
930 1.13
953 1.29
979 1.48
548
584
621
660
0.35
0.45
0.56
0.69
-
569
612
0.47
0.60
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
Table PD-33 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
BHP
2-HPStandardMotor&Drive
1.20
1.30
BHP
1.70
BHP
1.80
RPM BHP
1.90
2.00
CFM
RPM
RPM
BHP
RPM
RPM
BHP RPM RPM BHP
BHP
RPM
RPM BHP
RPM BHP
2-HPStandard Motor&HighStaticDrive
1920
2160
2400
2640
2880
925
944
964
986
1011
0.95
1.08
1.22
1.39
1.58
960
978
998
1019
1043
1.03
1.17
1.32
1.49
1.69
994
1.11
1.26
1.42
1.60
1.79
1026
1043
1063
1082
1103
1.19
1.36
1.53
1.71
1.90
1057
1073
1092
1112
1133
1.27
1.44
1.63
1.81
2.02
1087
1104
1123
1141
1161
1.36
1.54
1.73
1.92
2.13
1116
1133
1151
1169
1190
1.44
1.63
1.83
2.03
2.26
1144
1162
1179
1198
-
1.52
1.72
1.93
1173 1.61
1189 1.81
1206 2.03 1233 2.13
1200 1.70
1216 1.91
1010
1030
1051
1073
2.15 1225 2.26
-
-
-
-
-
-
-
2-HPStandardMotor&HighStaticDrive
Table PD-34 — Belt Drive Evaporator Fan Performance — 6-Ton — TSC072,AK — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
RPM BHP
1.00
RPM BHP
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2-HPStandardMotor&FieldSuppliedLowStaticDrive(1)
2-HPStandardMotor&Drive
1920
2160
2400
2640
2880
-
-
565
609
660
710
762
0.31
0.41
0.54
0.68
0.86
627
663
701
745
795
0.39
0.48
0.60
0.76
0.94
679
716
751
788
828
0.45
0.57
0.69
0.83
1.02
726
762
798
833
869
0.52
0.64
0.78
0.93
1.11
771
804
839
875
911
0.60
0.72
0.87
1.04
1.21
814
843
877
914
950
0.69
0.80
0.95
1.13
1.33
857
883
914
949
986
0.77
0.90
1.04
1.22
1.44
899 0.85
922 0.99
950 1.14
984 1.31
1019 1.53
939 0.93
960 1.08
984 1.24
1016 1.42
1051 1.63
566
619
672
726
0.35
0.47
0.61
0.77
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
Trane’sfactorysuppliedmotors, incommercialequipment, aredefinitepurpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range
of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product’s warranty will not be
affected.
Table PD-34 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
BHP
1.20
BHP
1.30
BHP
1.70
BHP
1.80
RPM
1.90
2.00
CFM
RPM
RPM
RPM
RPM
BHP RPM RPM BHP
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandard Motor&HighStaticDrive
2-HPStandard
Motor&Drive
1920
2160
2400
2640
2880
978
996
1.02
1.17
1.35
1.53
1.74
1015
1034
1055
1081
1112
1.11
1.27
1.45
1.65
1.86
1051
1069
1089
1113
1141
1.20
1.36
1.55
1.76
1.97
1086
1103
1122
1144
1170
1.30
1.46
1.66
1.87
2.10
1118
1136
1154
1176
1199
1.39
1.56
1.76
1.98
2.22
1150
1169
1186
1207
-
1.49
1.67
1.86
2.10
-
1180
1199
1216
1237
-
1.58
1.77
1.97
2.21
-
1209
1229
1246
-
1.68
1.88
1236 1.77
1258 1.98
1263 1.86
-
-
-
-
-
-
-
-
1020
1049
1081
2.08 1276 2.20
-
-
-
-
-
-
-
2-HPStandardMotor&HighStaticDrive
36
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
(7½ Ton)
Standard Efficiency
Performance
Data
Table PD-35 — Belt Drive Evaporator Fan Performance — 7½-Ton — TSC090,092A3,A4,AW,AK — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&FieldSuppliedLowStaticDrive(1)
2-HP Standard Motor & Drive
2400
2700
3000
3300
3600
—
—
656
713
771
—
—
0.71
0.93
1.19
—
—
652
699
747
797
848
0.54
0.70
0.91
1.15
1.42
701
743
789
836
885
0.63
0.79
0.99
1.24
1.53
750
787
827
873
921
0.72
0.89
1.10
1.34
1.63
794
830
867
908
954
0.81
0.99
1.20
1.45
1.74
834
871
906
944
986
0.90
1.09
1.31
1.57
1.87
873
908
944
980
1019
0.98
1.19
1.43
1.69
1.99
909 1.08
943 1.29
980 1.54
1016 1.82
945 1.17
977 1.39
1013 1.65
1050 1.94
652
703
755
809
0.63
0.81
1.03
1.29
1052 2.13 1085 2.26
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. FieldSuppliedMotorSheave1VL40Lx7/8andFanSheaveAK71required.
Table PD-35 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
BHP
2-HPStandardMotor&Drive
1.20
1.30
BHP
1.70
BHP
1.80
RPM BHP
1.90
2.00
CFM
RPM
RPM
BHP
RPM
RPM
BHP RPM RPM BHP
BHP
RPM
RPM BHP
RPM BHP
2-HPStandard Motor&HighStaticDrive
Kit (or 3-HP Oversized Motor & Drive)
2400
2700
3000
3300
3600
980
1010
1045
1081
1116
1.27
1.49
1.76
2.06
2.39
1013
1043
1076
1111
1.37
1.60
1.87
2.18
2.53
1046
1074
1105
1141
1177
1.47
1.71
1.98
2.30
2.66
1076
1105
1134
1168
1204
1.57
1.82
2.09
2.42
2.79
1106
1134
1163
1197
1232
1.68
1.93
2.21
2.55
2.93
1137
1163
1192
1222
1257
1.78
2.04
2.34
2.66
3.05
1166
1192
1219
1249
1283
1.89
2.16
2.45
2.79 1276
3.19
1194
1219
1247
1.99
2.27
1220 2.08 1248 2.19
1246 2.39 1273 2.51
2.58 1272 2.71 1299 2.84
2.92 1301 3.06 1326 3.19
1148
1309 3.32
—
—
—
—
3-HPOversizedMotor&Drive
Table PD-36 — Belt Drive Evaporator Fan Performance — 7½-Ton — TSC090,092A3,A4,AW,AK — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
RPM BHP
1.00
RPM BHP
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2-HPStandardMotor&Drive
2-HPStandardMotor&Field
SuppliedLowStaticDrive(1)
2400
2700
3000
3300
3600
—
—
673
738
805
873
942
0.56
0.76
1.00
1.29
1.63
718
773
837
903
970
0.63
0.83
1.08
1.38
1.74
769
817
870
930
996
0.72
0.92
1.17
1.47
1.84
814
862
912
963
1021
0.82
1.02
1.26
1.57
1.94
855
904
951
1000
1052
0.90
1.13
1.38
1.68
2.04
893
941
989
0.98
1.23
1.51
1.80
2.16
929
975
1025
1073
1121
1.08
1.32
1.62
1.94
2.29
965 1.18
1009 1.42
1056 1.72
1106 2.08
1153 2.44
999 1.29
1041 1.52
1088 1.82
1136 2.19
1184 2.59
702
771
842
913
0.68
0.91
1.19
1.53
1037
1086
3-HPOversizedMotor
&Drive
2-HPStandardMotor&HighStatic
Drive Kit (or 3-HP Oversized Motor)
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories.
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
1. FieldSuppliedMotorSheave1VL40Lx7/8andFanSheaveAK71required.
Table PD-36 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
BHP
1.20
BHP
1.30
BHP
1.70
BHP
1.80
RPM BHP
1.90
2.00
CFM
RPM
RPM
RPM
RPM
BHP RPM RPM BHP
2-HP Standard Motor & High Static Drive Kit
(or3-HPOversizedMotor&Drive)
BHP
RPM
RPM BHP
RPM BHP
2-HPStandardMotor&Drive
2400
2700
3000
3300
3600
1035
1073
1117
1165
1215
1.39
1.64
1.93
2.30
2.73
1070
1104
1146
1194
1242
1.50
1.76
2.05
2.41
2.86
1104
1136
1176
1220
1269
1.60
1.87
2.17
2.52
2.98
1137
1167
1205
1248
1295
1.70
1168
1198
1233
1275
1319
1.81
2.11
2.44
2.79
3.22
1201
1228
1261
1301
1345
1.92
2.22
2.56
2.93
3.35
1232
1258
1289
1326
—
2.03 1261
2.14 1291 2.26
2.46 1315 2.58 1343 2.69
2.82 1344 2.95 1372 3.08
1319 2.38
1.99
2.31
2.66
3.10
2.34 1287
2.69 1317
3.07 1352
3.22 1378 3.36
—
—
—
—
—
—
—
—
—
3-HPOversizedMotor&Drive
RT-PRC005-EN
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(8½ Ton)
Standard Efficiency
Table PD-37— Belt Drive Evaporator Fan Performance — 8½-Ton — TSC102A3,A4,AW, AK —DownflowAirflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&FieldSupplied
2-HP Standard Motor
& Drive
LowStaticDrive(1)
2720
3060
3400
3740
4080
—
—
—
622
671
—
—
—
0.76
0.96
—
—
612
659
706
—
—
0.68
0.86
1.08
—
—
613
650
689
729
770
0.60
0.74
0.91
1.10
1.32
655
688
724
764
804
0.72
0.85
1.02
1.23
1.46
695
725
759
795
834
0.84
0.98
1.15
1.35
1.60
733
761
792
826
864
0.95
1.11
1.29
1.49
1.74
769
796
825
857
892
1.08
1.25
1.43
1.64
1.88
802 1.21
828 1.38
856 1.58
887 1.79
920 2.04
833 1.34
861 1.52
887 1.72
916 1.96
948 2.20
611
651
693
738
0.64
0.79
0.97
1.19
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to stnadard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. FieldSuppliedFanSheaveAK79andBeltAX38required.
Table PD-37 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
BHP
2-HPStandardMotor&Drive
1.20
1.30
BHP
1.70
BHP
1.80
RPM BHP
1.90
2.00
CFM
RPM
RPM
BHP
RPM
RPM
BHP RPM RPM
BHP
BHP
RPM
RPM BHP
RPM BHP
3-HPOversizedMotor&Drive
2720
3060
3400
3740
4080
863
891
917
945
976
1.48
1.66
1.87
2.11
2.38
892
919
946
974
1002
1.63
1.81
2.03
2.28
2.56
920
946
974
1001
1029
1.78
1.96
2.18
2.44
2.73
946
973
1001
1028
1055
1.93
2.12
2.34
2.61
2.91
973
999
1026
1054
1081
2.08
2.29
2.52
2.78
3.09
999
2.24
2.46
2.69
2.96
3.26
1025
1048
1074
1103
1130
2.39 1050
2.63 1072
2.86 1099
3.14
3.45
2.55 1073 2.71 1098 2.88
2.80 1096 2.98
1024
1051
1079
1105
1119 3.14
1143 3.41
3.05
3.32
—
1121 3.23
—
—
1126
—
—
—
—
—
—
—
Table PD-38 — Belt Drive Evaporator Fan Performance — 8½-Ton — TSC102A3,A4,AW, AK —Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
RPM BHP
1.00
RPM BHP
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2-HPStandardMotor&FieldSupplied
2-HPStandardMotor&Drive
LowStaticDrive(1)
2720
3060
3400
3740
4080
—
—
598
654
711
770
828
0.57
0.77
1.01
1.30
1.65
646
693
743
799
857
0.67
0.86
1.10
1.40
1.76
689
735
781
830
883
0.78
0.98
1.22
1.51
1.86
734
773
819
865
913
0.90
1.10
1.36
1.65
1.99
781
812
853
899
945
1.04
1.23
1.49
1.79
2.15
826
855
886
930
977
1.18
1.39
1.62
1.94
2.30
865
897
925
960
1006
1.31
1.55
1.79
2.09
898 1.44
934 1.70
964 1.97
994 2.26
928 1.56
969 1.85
1000 2.14
1028 2.44
616
675
735
796
0.69
0.92
1.20
1.53
2.47 1034 2.63 1061 2.79
3-HPOversizedMotor&Drive
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750.
1. FieldSuppliedFanSheaveAK79andBeltAX38required.
Table PD-38 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
BHP
1.20
BHP
1.30
BHP
1.70
BHP
1.80
RPM BHP
1.90
2.00
CFM
RPM
RPM
RPM
RPM
BHP RPM RPM
BHP
BHP
RPM
RPM BHP
RPM BHP
2-HPStandardMotor&Drive
3-HPOversizedMotor&Drive
2720
3060
3400
3740
4080
956
999
1.67
1.99
2.32
2.63
2.99
982
1.79
2.12
2.49
2.84
3.19
1008
1052
1094
1129
1157
1.91
2.26
2.64
3.03
3.40
1033
1078
1120
1158
—
2.03
2.39
2.79
3.21
—
1056
1101
1145
1185
—
2.14
2.52
2.94
3.39
—
1079
1124
1168
—
2.26
2.66
3.09
—
1102
1146
1191
—
2.38
2.79
3.24 1213
—
—
1125
1168
2.50
2.92
3.39
—
1146 2.62
1168 2.74
1026
1067
1098
1125
1188 3.05 1209 3.18
1034
1063
1093
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
38
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(10 Ton)
Standard Efficiency
Table PD-39 — Belt Drive Evaporator Fan Performance — 10-Ton — TSC120A3,A4,AW,AK — Downflow Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
3-HPStandardMotor&FieldSupplied
LowStaticDrive(1)
3200
3600
4000
4400
4800
—
—
—
741
803
—
—
—
1.27
1.62
—
—
715
773
833
—
—
1.09
1.40
1.76
—
—
747
803
861
—
—
1.21
1.53
1.90
—
—
718
764
814
864
916
0.97
1.20
1.49
1.82
2.20
754
797
844
894
945
1.10
1.33
1.63
1.98
2.38
789
829
874
922
972
1.25
1.48
1.77
2.13
2.55
822
860
903
948
997
1.38
1.63
1.93
2.28
2.71
856 1.53
892 1.79
932 2.09
975 2.44
887 1.67
922 1.95
960 2.27
1001 2.62
731
782
834
887
1.08
1.35
1.67
2.04
1022 2.87 1046 3.04
3-HPStandardMotor&Drive
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475. 5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. FieldSuppliedMotorSheave1VM50x7/8”,FanSheaveAK89 andBeltAX40required.
Table PD-39 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
BHP
1.20
BHP
1.30
BHP
1.70
BHP
1.80
RPM
1.90
2.00
CFM
RPM
RPM
RPM
RPM
BHP RPM RPM
BHP
BHP
RPM
BHP
RPM BHP
RPM BHP
3-HPStandardMotor&Drive
3200
3600
4000
4400
4800
917
951
988
1028
1071
1.82
2.11
2.44
2.81
3.23
945
979
1015
1053
1095
1.97
2.27
2.62
3.00
3.42
973
1007
1042
1078
1119
2.14
2.43
2.79
3.19
3.62
999
1033
1068
1103
1142
2.30
2.60
2.97
3.38
3.83
1024
2.47
2.78
3.15
3.57
4.04
1048
1082
1117
1152
1189
2.65
2.95
3.33
3.77
4.25
1072
1107
1142
1176
1212
2.82 1095
3.00
3.33
3.70
1117 3.17
1152 3.52
1187 3.91
1140 3.36
1173 3.71
1209 4.11
1059
1093
1128
1166
3.14
3.52
3.96
1130
1164
1198
4.15 1221 4.36 1243 4.56
4.66 1256 4.88 1277 5.09
4.46 1233
5-HPOversizedMotor&Drive
Table PD-40— Belt Drive Evaporator Fan Performance — 10-Ton — TSC120A3,A4,AW,AK — Horizontal Airflow
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1.72
RPM BHP
RPM BHP
3-HPStandardMotor&FieldSupplied
LowStaticDrive(1)
771
829
890
955
3200
3600
4000
4400
4800
—
—
—
—
730
792
860
931
1002
1.00
1.32
1.73
2.24
2.84
1.13
1.45
1.86
2.35
2.96
807
865
923
983
1048
1.26
1.60
2.01
2.49
3.08
844
898
956
1014
1074
1.39
1.74
2.17
2.66
3.24
886
930
986
1045
1102
1.55
1.89
2.32
2.84 1072
3.43 1131
926
965
1015
965 1.89
1000 2.06
729
802
876
950
1.13
1.52
1.99
2.56
761
833
905
977
1.22
1.63
2.12
2.70
2.06 1002 2.24 1038 2.43
2.48 1044 2.65 1077 2.85
3.01 1098 3.18
3.63 1156 3.81
1125 3.36
1181 4.00
1025
3-HPStandardMotor&Drive
5-HPOversizedMotor&Drive
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475. 5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. FieldSuppliedMotorSheave1VM50x7/8”,FanSheaveAK89 andBeltAX40required.
Table PD-40 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
BHP
3-HPStandardMotor&Drive
1.20
1.30
1.70
BHP
1.80
RPM
1.90
2.00
CFM
RPM
RPM
BHP
RPM
BHP
RPM
BHP RPM RPM
BHP
BHP
RPM
BHP
RPM BHP
RPM BHP
3200
3600
4000
4400
4800
1029
1072
1111
1152
1205
2.20
1057
1106
1143
1182
2.35
2.81
3.26
3.76
1084
1134
1174
1211
1253
2.49
2.98
3.47
3.99
4.58
1108
1160
1204
1241
1280
2.63
3.15
3.68
4.21
4.81
1132
1185
1232
1270
1309
2.77
3.31
3.88
4.44
5.06
1155
1209
1260
1299
1336
2.91
3.47
4.09
4.68
5.31
1177
1231
1283
1327
1363
3.05
1198
3.18
1219 3.32 1239 3.46
2.62
3.05
3.55
4.19
3.63 1252
4.27 1306
4.91 1352
3.78 1274 3.94 1295 4.10
4.46 1327 4.63 1349 4.81
5.14 1377 5.37 1400 5.57
1229 4.39
5.56
—
—
—
—
—
—
5-HPOversizedMotor&Drive
RT-PRC005-EN
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(3, 4, 5Ton)
High Efficiency
Table PD-41— Direct Drive Evaporator Fan Performance — 3, 4, and 5 Ton — THC036A, THC048A, THC060A
External Static Pressure (Inches ofWater) & Motor Power (Bhp)1
Standard Motor
Low Speed
Oversized Motor
Low Speed
Unit
High Speed
ESP
High Speed
ESP
Tons Model No.
CFM
960
BHP
0.36
0.37
0.38
0.39
0.40
0.41
0.42
0.43
0.44
0.53
0.54
0.54
0.55
0.55
0.56
0.56
0.57
0.57
0.78
0.80
0.85
0.88
0.90
0.93
0.94
0.95
0.97
0.36
0.37
0.38
0.39
0.40
0.41
0.42
0.43
0.44
0.53
0.54
0.54
0.55
0.55
0.56
0.56
0.57
0.57
0.78
0.80
0.85
0.88
0.90
0.93
0.94
0.95
0.97
ESP
0.56
0.49
0.44
0.37
0.29
0.19
0.10
0.00
—
0.79
0.71
0.65
0.56
0.44
0.32
0.17
0.05
—
0.94
0.81
0.70
0.61
0.45
0.30
0.15
—
BHP
0.28
0.28
0.29
0.29
0.30
0.30
0.31
0.31
—
0.47
0.47
0.48
0.48
0.49
0.49
0.50
0.50
—
0.64
0.65
0.65
0.65
0.66
0.66
0.67
—
BHP
0.38
0.39
0.41
0.43
0.44
0.45
0.47
0.48
0.51
0.67
0.68
0.70
0.73
0.75
0.78
0.82
0.83
0.85
0.90
0.94
0.98
1.02
1.05
1.10
1.12
1.17
1.20
0.38
0.39
0.41
0.43
0.44
0.45
0.47
0.48
0.51
0.67
0.68
0.70
0.73
0.75
0.78
0.82
0.83
0.85
0.90
0.94
0.98
1.02
1.05
1.10
1.12
1.17
1.20
ESP
0.82
0.77
0.74
0.69
0.65
0.61
0.57
0.52
0.45
0.95
0.90
0.85
0.77
0.68
0.59
0.42
0.29
0.18
1.23
1.13
1.02
0.92
0.81
0.68
0.47
0.23
—
0.82
0.82
0.79
0.74
0.70
0.66
0.62
0.57
0.50
1.00
0.95
0.90
0.82
0.73
0.64
0.47
0.34
—
BHP
0.35
0.36
0.38
0.40
0.41
0.42
0.44
0.45
0.48
0.56
0.58
0.60
0.63
0.64
0.66
0.68
0.70
0.73
0.85
0.89
0.91
0.94
0.95
0.96
0.96
0.97
—
0.35
0.36
0.38
0.40
0.41
0.42
0.44
0.45
0.48
0.56
0.58
0.60
0.63
0.64
0.66
0.68
0.70
—
0.74
0.69
0.65
0.61
0.55
0.51
0.46
0.41
0.34
0.90
0.83
0.76
0.69
0.60
0.51
0.42
0.31
0.21
1.04
0.97
0.92
0.82
0.74
0.64
0.51
0.42
0.31
0.79
0.74
0.70
0.66
0.60
0.56
0.51
0.46
0.39
0.95
0.88
0.81
0.74
0.65
0.56
0.47
0.36
0.26
1.09
1.02
0.97
0.87
0.79
0.69
0.56
0.47
0.36
0.89
0.85
0.82
0.77
0.74
0.70
0.67
0.64
0.57
1.16
1.11
1020
1080
1140
1200
1260
1320
1380
1440
1280
1360
1440
1520
1600
1680
1760
1840
1920
1600
1700
1800
1900
2000
2100
2200
2300
2400
960
1020
1080
1140
1200
1260
1320
1380
1440
1280
1360
1440
1520
1600
1680
1760
1840
1920
1600
1700
1800
1900
2000
2100
2200
2300
2400
3
4
5
3
4
5
THC036A
Horizontal
1.06
1.01
0.94
0.89
0.84
0.75
0.67
1.37
1.29
1.21
1.20
1.03
0.94
0.83
0.73
0.60
0.94
0.90
0.87
0.82
0.79
0.75
0.72
0.69
0.62
1.21
1.16
1.11
1.06
0.99
0.94
0.89
0.80
0.72
1.42
1.34
1.26
1.25
1.08
0.99
0.88
0.78
0.65
THC048A
Horizontal
THC060A
Horizontal
—
—
0.56
0.54
0.49
0.42
0.34
0.24
0.15
0.05
—
0.84
0.76
0.70
0.61
0.49
0.37
0.22
0.10
—
0.99
0.86
0.75
0.66
0.50
0.35
0.20
—
0.28
0.28
0.29
0.29
0.30
0.30
0.31
0.31
—
0.47
0.47
0.48
0.48
0.49
0.49
0.50
0.50
—
0.64
0.65
0.65
0.65
0.66
0.66
0.67
—
THC036A
Downflow
THC048A
Downflow
1.28
1.18
1.07
0.97
0.86
0.73
0.52
0.28
—
0.85
0.89
0.91
0.94
0.95
0.96
0.96
0.97
—
THC060A
Downflow
—
—
Fan motor heat (MBH) = 3.72 x Fan Bhp + .24.
Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will
not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
NOTE:
1. Data includes pressure drop due to wet coil and filters.
2. 5 ton oversized motor performance is with 12 x 11 FC blower wheel.
40
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(3 Ton)
High Efficiency
Table PD-42 — Belt Drive Evaporator Fan Performance — 3 Ton — THC036A3,A4,AW — Downflow Airflow— Standard Refrigeration System
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HPStandardMotor
&FieldSupplied
LowStaticDrive(1)
1-HPStandardMotor&Drive
960
—
—
—
552
588
—
—
—
0.18
0.23
528
557
588
622
657
0.12
0.15
0.19
0.23
0.28
599
625
652
681
713
0.16
0.19
0.23
0.27
0.33
658
685
712
738
765
0.20
0.24
0.28
0.32
0.37
713
738
764
790
817
0.24
0.28
0.33
0.38
0.43
763
786
811
838
865
0.29
0.33
0.38
0.44
0.50
810
832
856
882
909
0.33
0.38
0.43
0.49
0.56
855
876
898
923
949
0.38
0.43
0.48
0.55
0.62
898 0.43
917 0.48
939 0.54
962 0.60
987 0.68
939 0.49
957 0.54
978 0.59
1000 0.66
1024 0.74
1080
1200
1320
1440
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedto
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in
our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. FieldSuppliedFanSheaveAK69required. FieldSuppliedBeltmaybenecessary.
2. FieldSuppliedFanSheaveAK41required.FieldSuppliedBeltmaybenecessary.
Table PD-42 — Continued
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
1-HPStandardMotor&Drive
960
978
995
1015
1036
1060
0.54
0.59
0.65
0.72
0.80
1016
1033
1051
1072
1094
0.60
0.65
0.71
0.78
0.86
1052
0.66
0.71
0.77
0.85
0.93
1086
1103
1120
1138
1160
0.72
0.78
0.84
0.91
1.00
1120
1136
1154
1171
1192
0.78
0.84
0.91
0.98
1.07
1080
1200
1320
1440
1069
1086
1106
1128
1-HPStandardMotor&
FieldSuppliedHighStaticDrive(2)
Table PD-43— Belt Drive Evaporator Fan Performance — 3Ton —THC036A3,A4,AW — DownflowAirflow — Dehumidification (Hot Gas Reheat) Option
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard Motor
&LowStaticDrive
AccessoryKit(1)
1-HP Standard Motor & Low Static
1-HP Standard Motor & Drive
DriveAccessoryKit(2)
600
720
840
960
—
—
—
—
—
—
449
475
501
528
0.06
0.08
0.10
0.12
525
547
572
599
0.09
0.11
0.13
0.16
593
612
634
658
0.12
0.14
0.17
0.20
653
669
690
713
0.16
0.18
0.21
0.24
707
724
742
763
0.20
0.22
0.25
0.29
757
774
791
810
0.23
0.26
0.29
0.33
802
821
837
855
0.27
0.31
0.34
0.38
845 0.31
864 0.35
881 0.39
898 0.43
885 0.36
905 0.40
922 0.44
939 0.49
447
0.09
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 960 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR006ARequired.
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
2. BAYLSDR006ARequired.
Table PD-43— Continued
External Static Pressure (Inches of Water)
1.10
RPM
1.20
RPM
1.30
RPM
1.40
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
1-HPStandardMotor&Drive
600
720
840
960
924
943
962
978
0.40
0.45
0.50
0.54
962
980
999
0.45
0.50
0.55
0.60
997
0.49
0.55
0.60
0.66
1031
1050
1068
1086
0.54
0.60
0.66
0.72
1065
1082
1103
—
0.59
0.65
0.71
—
1016
1034
1052
1016
RT-PRC005-EN
41
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(3 Ton)
High Efficiency
Table PD-44— Belt Drive Evaporator Fan Performance — 3 Ton — THC036A3,A4,AW — Horizontal Airflow— Standard Refrigeration System
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard Motor & Field Supplied
1-HPStandardMotor&Drive
Low Static Drive (1)
960
—
—
588
622
654
687
723
0.15
0.18
0.23
0.28
0.33
661
694
727
760
793
0.19
0.24
0.28
0.34
0.40
725
756
787
821
855
0.24
0.29
0.34
0.40
0.47
782
813
843
875
908
0.29
0.34
0.40
0.46
0.53
832
864
895
925
956
0.35
0.40
0.46
0.53
0.60
878
910
942
0.40
0.46
0.52
0.59
919
954
986
0.46
0.52
0.59
958 0.51
993 0.59
1026 0.66 1064 0.73
996 0.56
1031 0.65
1080
1200
1320
1440
531
570
610
651
0.13
0.17
0.22
0.27
973
1017
0.66 1058 0.73 1095 0.81
0.75 1088 0.82 1127 0.89
1003
0.67 1047
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1-HPStandardMotor&
Field Supplied High Static Drive (2)
1. FieldSuppliedFanSheaveAK69required. FieldSuppliedBeltmaybenecessary.
2. FieldSuppliedFanSheaveAK41required.FieldSuppliedBeltmaybenecessary.
Table PD-44— Continued
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedto
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in
our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
CFM
BHP
BHP
BHP
BHP
BHP
1-HPStandardMotor&Drive
960
1032 0.62
1066
1099
1133
1167
1199
0.67
0.76
0.86
0.96
1.05
1101
0.73
0.82
0.93
1.04
1.14
1133
1164
1197
1230
1263
0.79
0.89
0.99
1.11
1.22
1166
1194
1227
1261
1294
0.86
0.95
1.06
1.19
1.30
1080
1200
1320
1440
1065
1099
1132
1164
0.70
0.80
0.88
0.97
1132
1166
1200
1232
1-HPStandardMotor&
FieldSuppliedHighStaticDrive(2)
Table PD-45— Belt Drive Evaporator Fan Performance — 3Ton —THC036A3,A4,AW — Horizontal Airflow— Dehumidification (Hot Gas Reheat) Option
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard Motor & Low
StaticDriveAccessoryKit(2)
1-HP Standard Motor & Low
StaticDriveAccessoryKit(1)
1-HPStandardMotor&Drive
600
720
840
960
—
—
493
523
555
588
0.07
0.09
0.12
0.15
567
599
631
661
0.11
0.13
0.16
0.19
628
662
694
725
0.14
0.17
0.21
0.24
683
716
750
782
0.18
0.21
0.25
0.29
737
766
799
832
0.22
0.25
0.30
0.35
786
811
844
878
0.26
0.29
0.35
0.40
832
856
886
919
0.30
0.34
0.39
0.46
876 0.35
899 0.39
925 0.44
958 0.51
918 0.40
940 0.44
965 0.49
996 0.56
427
460
493
0.06
0.08
0.10
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 960 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR006ARequired.
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedto
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in
our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
2. BAYLSDR006ARequired.
Table PD-45— Continued
External Static Pressure (Inches of Water)
1.10
RPM
1.20
RPM
1.30
RPM
1.40
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
1-HPStandardMotor&Drive
600
720
840
960
958
978
0.45
0.49
996
0.50
0.55
0.60
0.67
1032
0.55
0.61
0.67
0.73
1068
1087
1109
—
0.60
0.66
0.72
—
1102
—
—
0.66
—
—
1016
1039
1066
1053
1076
1101
1002 0.55
1032 0.62
—
—
42
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(4 Ton)
High Efficiency
Table PD-46 — Belt Drive Evaporator Fan Performance — 4 Ton — THC048A3,A4,AW — Downflow Airflow— Standard Refrigeration System
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard Motor & Field Supplied
1-HP Standard Motor & Drive
Low Static Drive (1)
1280
1440
1600
1760
1920
—
—
626
674
724
775
825
0.23
0.30
0.38
0.48
0.59
686
730
776
825
875
0.27
0.34
0.44
0.54
0.66
744
783
825
870
918
0.32
0.39
0.49
0.60
0.73
796
834
872
915
959
0.38
0.45
0.54
0.66
0.79
843
882
919
958
1000
0.43
0.52
0.61
0.72
0.86
885
924
962
999
1039
0.49
0.58
0.68
0.79
927
964
1002
1040
0.54
0.64
967 0.60
1002 0.70 1038 0.76
1005 0.66
609
661
716
771
0.24
0.32
0.42
0.53
0.75 1039 0.82 1076 0.89
0.87 1078 0.95
1.00 1116 1.09
1113 1.03
1151 1.17
0.92 1078
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. FieldSuppliedFanSheaveAK61required. FieldSuppliedBeltmaybenecessary.
Table PD-46 — Continued
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
1-HPStandardMotor&Drive
1280
1440
1600
1760
1920
1041
1074
1109
1147
1186
0.72
0.83
0.95
1.10
1.26
1076
1108
1142
1179
1218
0.78
0.89
1.02
1.17
1.34
1110
0.84
0.96
1.09
1.25
1.42
1143
1174
1207
1241
—
0.91
1.03
1.17
1.32
—
1176
1205
1236
—
0.98
1.10
1.24
—
1141
1175
1211
1249
—
—
Table PD-47 — Belt Drive Evaporator Fan Performance — 4Ton —THC048A3,A4,AW — DownflowAirflow— Dehumidification (Hot Gas Reheat) Option
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HPStandardMotor&
LowStaticDrive
1-HPStandardMotor&LowStaticDriveAccessoryKit(2)
1-HPStandardMotor&Drive
AccessoryKit(1)
800
960
1120
1280
—
—
501
539
580
626
0.09
0.13
0.17
0.23
571
609
646
686
0.13
0.17
0.21
0.27
633
668
706
744
0.16
0.21
0.26
0.32
690
721
758
796
0.20
0.25
0.31
0.38
742
771
805
843
0.25
0.29
0.36
0.43
792
819
850
885
0.29
0.34
0.41
0.49
838
864
893
927
0.34
0.39
0.46
0.54
882 0.39
906 0.44
934 0.51
967 0.60
923 0.44
947 0.50
973 0.57
1005 0.66
459
509
559
0.09
0.13
0.18
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1280 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR007ARequired.
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
2. BAYLSDR007ARequired.
Table PD-47 — Continued
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
1-HPStandardMotor&Drive
800
960
1120
1280
963
986
1012
1041
0.49
0.55
0.63
0.72
999
0.54
0.61
0.69
0.78
1034
0.59
0.67
0.75
0.84
1068
1095
1118
1143
0.65
0.73
0.81
0.91
1101
1127
1151
1176
0.70
0.79
0.88
0.98
1023
1048
1076
1060
1084
1110
RT-PRC005-EN
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(4 Ton)
High Efficiency
Table PD-48 — Belt Drive Evaporator Fan Performance — 4 Ton — THC048A3,A4,AW — Horizontal Airflow— Standard Refrigeration System
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard Motor & Field Supplied
1-HPStandardMotor&Drive
Low Static Drive (1)
1280
1440
1600
1760
1920
617
674
733
793
853
0.21
0.29
0.38
0.49
0.62
696
745
799
854
911
0.27
0.35
0.45
0.56
0.70
767
815
862
911
964
0.34
0.42
0.53
0.65
0.79
826
874
922
969
1018
0.40
0.49
0.60
0.73
0.88
879
925
975
1023
1069
0.46
0.56
0.68
0.82
0.97
930
974
1020
1069
1118
0.52
0.63
0.75
0.90
1.06
976
1020
1065
1112
1161
0.59
0.70 1064
0.83
0.98
1.15
1020
0.66 1060 0.73 1098 0.80
0.77
0.91
1.07
1.25
1104 0.85
1147 0.99
1191 1.15
1239 1.34
1142 0.92
1186 1.07
1230 1.24
1275 1.43
1107
1152
1201
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1-HPStandardMotor&Field
SuppliedHighStaticDrive(2)
1. FieldSuppliedFanSheaveAK61required. FieldSuppliedBeltmaybenecessary.
2. FieldSuppliedFanSheaveAK41required. FieldSuppliedBeltmaybenecessary.
Trane’s factory supplied motors, in commercial equipment, are
Table PD-48 — Continued
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
CFM
BHP
BHP
1-HPStandardMotor
BHP
BHP
BHP
1280
1440
1600
1760
1920
1132
1179
1223
1267
—
0.88
1.01
1.15
1.33
—
1167
1213
1258
1301
—
0.95
1.09
1.24
1.42
—
1199
1.03
1.17
1.33
—
1231
1277
1322
—
1.10
1.26
1.42
—
1260
1307
—
1.17
1.34
—
1245
1291
—
—
—
—
—
—
—
—
—
1-HP Standard Motor &
FieldSuppliedHighStaticDrive(2)
Table PD-49 — Belt Drive Evaporator Fan Performance — 4Ton —THC048A3,A4,AW — Horizontal Airflow— Dehumidification (Hot Gas Reheat) Option
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HPStandardMotor&Low
StaticDriveAccessoryKit(1)
1-HPStandardMotor&LowStaticDriveAccessoryKit(2)
1-HPStandardMotor&Drive
800
960
1120
1280
461
509
561
617
0.08
0.11
0.16
0.21
553
600
649
696
0.11
0.16
0.21
0.27
629
672
719
767
0.16
0.20
0.26
0.34
692
736
779
826
0.20
0.25
0.32
0.40
745
791
836
879
0.25
0.30
0.37
0.46
794
841
886
930
0.29
0.36
0.43
0.52
838
887
932
976
0.34
0.42
0.50
0.59
881
927
975
0.38
0.47
0.56
922 0.43
966 0.52
1014 0.63 1052 0.69
962 0.48
1004 0.58
1020
0.66 1060 0.73 1098 0.80
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1280 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR007ARequired.
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
2. BAYLSDR007ARequired.
Table PD-49 — Continued
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
1-HPStandardMotor&Drive
800
960
1120
1280
1001 0.54
1040 0.63
1038
1073
1119
0.60
0.68
0.81
0.95
1072
1108
1152
1199
0.65
0.75
0.88
1.03
1108
1141
1183
1231
0.71
0.81
0.94
1.10
1142
1175
1213
—
0.78
0.88
1.00
—
1087
1132
0.75
0.88
1167
44
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(5 Ton)
High Efficiency
Table PD-50— Belt Drive Evaporator Fan Performance — 5 Ton — THC060A3,A4,AW — Downflow Airflow— Standard Refrigeration System
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard Motor & Field Supplied
1-HP Standard Motor & Drive
Low Static Drive (1)
1600
1800
2000
2200
2400
—
—
703
760
821
885
950
0.36
0.47
0.62
0.80
1.02
757
815
873
930
990
0.41
0.54
0.69
0.87
1.08
806
861
918
977
1034
0.47
0.60
0.76
0.95
1.16
854
904
958
1016
1074
0.52
0.66
0.83
1.03
1.25
899
947
998
1053
1110
0.58
0.72
0.90
1.10
1.00
944
988
1036
1089
1143
0.65
0.78
985
1028
0.73
1023 0.79 1060 0.86
706
773
840
909
0.42
0.57
0.75
0.96
0.86 1067 0.94
1104 1.02
1147 1.19
1191 1.39
0.96 1073
1.02
1.24
1.50
1111 1.10
1158 1.31
1.17
1.42
1124
1177
—
—
—
—
Trane’s factory supplied motors, in commercial equipment, are
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
1. FieldSuppliedFanSheaveAK56required. FieldSuppliedBeltmaybenecessary.
Table PD-50 — Continued
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
1-HPStandardMotor&Drive
1600
1800
2000
2200
2400
1093
1138
1182
1226
—
0.92
1.10
1.28
1.48
—
1126
1171
1215
—
0.99
1.17
1.37
—
1160
1.06
1.25
1.46
—
1190
1232
—
—
—
1.13
1.32
—
—
—
1222
1262
—
—
—
1.20
1.39
—
—
—
1203
1246
—
—
—
—
—
Table PD-51 — Belt Drive Evaporator Fan Performance — 5Ton —THC060A3,A4,AW — DownflowAirflow — Dehumidification (Hot Gas Reheat) Option
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard Motor & Low
1-HPStandardMotor&Low
StaticDriveAccessoryKit(2)
1-HPStandard
Motor&Drive
Static Drive Accessory Kit (1)
1000
1200
1400
1600
—
—
537
588
645
703
0.13
0.19
0.26
0.36
608
652
702
757
0.17
0.23
0.31
0.41
667
712
756
806
0.21
0.28
0.36
0.47
721
764
808
854
0.25
0.33
0.41
0.52
770
811
856
899
0.30
0.38
0.48
0.58
817
856
900
944
0.35
0.43
0.54
0.65
861
898
941
985
0.39
0.48
0.59
0.73
905 0.45
939 0.54
979 0.65
944 0.50
978 0.59
1017 0.71
517
576
640
0.15
0.21
0.31
1023 0.79 1060 0.86
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1600 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR008ARequired.
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will
not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
2. BAYLSDR008ARequired.
PD-51 — Continued
External Static Pressure (Inches of Water)
1.10
RPM
1.20
RPM
1.30
RPM
1.40
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
1-HPStandardMotor&Drive
1000
1200
1400
1600
985
0.56
0.65
0.77
0.92
1021
1051
1088
1126
0.62
0.71
0.84
0.99
1058
0.68
0.77
0.90
1.06
1093
1120
1153
1190
0.74
0.84
0.97
1.13
1126
1154
1185
1222
0.80
0.91
1.04
1.20
1015
1052
1093
1086
1121
1160
RT-PRC005-EN
45
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(5 Ton)
High Efficiency
Table PD-52 — Belt Drive Evaporator Fan Performance — 5 Ton — THC060A3,A4,AW — Horizontal Airflow— Standard Refrigeration System
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard Motor & Field Supplied
1-HPStandardMotor&Drive
Low Static Drive (1)
1600
1800
2000
2200
2400
707
778
850
923
997
0.35
0.48
0.65
0.84
1.07
774
840
908
978
1049
0.42
0.56
0.73
0.93
1.17
837
897
961
1028
1096
0.50
0.64
0.81
1.02
1.27
898
953
1012
1075
1140
0.57
0.72
0.90
1.12
1.37
953
1008
1062
1120
1183
0.65
0.81
1.00
1.22
1.48
1001
1058
1111
1166
—
0.72
0.89
1.09
1.32
—
1045
1102
1157
1211
—
0.80 1087
0.87
1.06
1.28
—
1129 0.95
1181 1.15
1237 1.37
1168 1.03
1219 1.23
1274 1.47
0.98
1.19
1.43
—
1143
1198
—
—
—
—
—
—
—
—
—
—
—
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedto
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in
our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. FieldSuppliedFanSheaveAK56required. FieldSuppliedBeltmaybenecessary.
Table PD-52 — Continued
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
CFM
BHP
BHP
1-HPStandardMotor
BHP
BHP
BHP
1600
1800
2000
2200
2400
1206
1256
—
—
—
1.12
1.32
—
—
—
1241
1291
—
1.20
1.41
—
1275
1326
—
1.28
1.50
—
1306
—
—
1.37
—
—
1338
—
1.46
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Table PD-53— Belt Drive Evaporator Fan Performance — 5Ton —THC060A3,A4,AW — Horizontal Airflow — Dehumidification (Hot Gas Reheat) Option
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-HPStandardMotor&Low
StaticDriveAccessoryKit(2)
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard Motor & Low
Static Drive Accessory Kit (1)
1-HP Standard Motor & Drive
1000
1200
1400
1600
507
570
638
707
0.11
0.17
0.25
0.35
599
654
711
774
0.16
0.23
0.31
0.42
671
727
782
837
0.21
0.28
0.38
0.50
735
787
844
898
0.26
0.34
0.44
0.57
792
843
896
953
0.31
0.40
0.51
0.65
843
895
946
0.37
0.46
0.58
0.72
889
942
993
0.42
0.52
0.65
931
986
1037
0.48
0.59
971 0.54
1026 0.66 1064 0.73
1007 0.59
0.72 1078 0.79
0.87 1129 0.95
1117 0.86
1168 1.03
1001
1045
0.80 1087
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1600 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR008ARequired.
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedto
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in
our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
2. BAYLSDR008ARequired.
Table PD-53 — Continued
External Static Pressure (Inches of Water)
1.20 1.30 1.40
RPM RPM RPM
1.10
RPM
1.50
RPM
CFM
BHP
BHP
BHP
BHP
BHP
1-HPStandardMotor&Drive
1000
1200
1400
1600
1042
1099
1153
1206
0.65
0.80
0.94
1.12
1078
1133
1188
1241
0.70
0.86
1.02
1.20
1110
1166
1221
1275
0.76
0.93
1.10
1.28
1142
1197
1253
1306
0.82
0.99
1.18
1.37
1175
1227
1284
1338
0.89
1.06
1.27
1.46
46
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(6 Ton)
High Efficiency
Table PD-54— Belt Drive Evaporator Fan Performance — 6 Ton — THC072A3,A4,AW* — Downflow Airflow— Standard Refrigeration System
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard Motor & Field Supplied
1-HPStandardMotor&Drive
LowStaticDrive(1)
1920
2160
2400
2640
2880
—
—
—
589
634
—
—
—
0.50
0.63
—
—
588
618
652
690
728
0.35
0.44
0.54
0.67
0.82
643
672
701
734
770
0.43
0.52
0.63
0.76
0.91
693
721
750
779
810
0.50
0.60
0.72
0.85
1.01
738
765
794
822
851
0.57
0.68
0.81
0.95
1.11
782
806
834
864
892
0.65
0.76
0.90
1.05
1.22
823
847
873
901
930
0.73
0.85
0.98
1.15
1.33
862 0.81
885 0.93
909 1.08
936 1.24
965 1.44
900 0.89
922 1.02
945 1.17
971 1.34
999 1.54
564
602
642
682
0.37
0.47
0.59
0.74
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024. 2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. FieldSuppliedFanSheaveAK84andBeltAX34required.
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
Table PD-54 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
BHP
1.20
BHP
1.30
BHP
1.70
BHP
1.80
RPM
1.90
2.00
CFM
RPM
RPM
RPM
RPM
BHP RPM RPM
BHP
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HPStandard
Motor & Drive
1-HP Standard Motor & High Static Drive Kit
(or 2 HP Oversized Motor & Drive)
1920
2160
2400
2640
2880
937
0.98
1.12
1.27
1.44
1.64
971
1.06
1.21
1.37
1.55
1.75
1004
1024
1046
1067
1092
1.14
1.30
1.47
1.65
1.86
1037
1057
1076
1098
1123
1.22
1.40
1.57
1.77
1.98
1068
1087
1106
1129
1151
1.30
1.49
1.68
1.88
2.09
1097
1.38
1.58
1.78
1.99
2.22
1127
1146
1166
1185
—
1.47
1.67
1.89
2.10 1214
—
1154
1174
1194
1.55
1.76
1.99
2.22
—
1182 1.64
1201 1.85
1220 2.08 1248 2.19
1210 1.74
1227 1.95
957
980
1004
1030
991
1117
1137
1158
1181
1013
1036
1061
—
—
—
—
—
—
—
—
—
2-HPOversizedMotor&Drive
Table PD-55 — Belt Drive Evaporator Fan Performance — 6 Ton — THC072A3,A4,AW — Horizontal Airflow— Standard Refrigeration System
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard Motor & Field Supplied
1-HPStandardMotor&Drive
LowStaticDrive(1)
1920
2160
2400
2640
2880
—
—
580
623
673
725
778
0.33
0.43
0.56
0.71
0.90
641
679
718
762
811
0.41
0.51
0.63
0.79
0.98
692
731
769
808
848
0.47
0.59
0.72
0.87
1.06
738
775
814
853
891
0.54
0.67
0.82
0.98
1.16
783
817
855
894
932
0.63
0.74
0.90
1.09
1.28
827
857
893
931
970
0.71
0.83
0.98
1.17
1.40
870
896
929
966
1004
0.79
0.93
1.08
1.26
1.49
912 0.88
935 1.02
965 1.18
1000 1.36
1037 1.59
2-HPOversized
Motor &Drive
951 0.96
974 1.12
999 1.29
1032 1.47
1068 1.69
578
633
688
743
0.37
0.49
0.64
0.81
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due
tootheroptions/accessories.
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. FieldSuppliedFanSheaveAK84andBeltAX34required.
2. FieldSuppliedFanSheaveAK54andBeltAX30.
Trane’sfactorysuppliedmotors, incommercialequipment,
aredefinitepurposemotors, specificallydesignedandtested
to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan
motors as shown in our tabular data will not result in
nuisance tripping or premature motor failure. Our product’s
warranty will not be affected.
1-HPStandardMotor&HighStatic
Drive Kit (or 2-HP Oversized Motor)
Table PD-55 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
BHP
1.20
BHP
1.30
BHP
1.70
BHP
1.80
RPM
1.90
2.00
CFM
RPM
RPM
RPM
RPM
BHP RPM RPM
BHP
BHP
RPM
BHP
RPM BHP
RPM BHP
1-HP Standard
Motor & Drive
1-HP Standard Motor & High Static Drive Kit
(or2HPOversizedMotor&Drive)
1920
990
1.05
1026
1047
1070
1097
1130
1.14
1.31
1.50
1.71
1.93
1062
1082
1104
1129
1159
1.24
1.40
1.60
1.82
2.05
1096
1116
1137
1161
1188
1.33
1.50
1.70
1.93
2.18
1130
1.43
1.61
1.81
2.05
2.30
1160
1182
1201
1223
—
1.52
1.71
1.92
2.16
—
1190
1211
1232
1252
—
1.61
1.81
2.03 1261
2.27
—
1218
1242
1.71
1.92
1247 1.80
1271 2.03 1298 2.14
1273 1.90
2160
2400
2640
2880
1010
1035
1065
1099
1.21
1.39
1.59
1.80
1150
1168
1192
1217
2.14 1291 2.26
—
—
—
—
—
—
2-HPOversizedMotor&
FieldSuppliedDrive(2)
2-HPOversizedMotor&Drive
RT-PRC005-EN
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(7½Ton)
High Efficiency
Table PD-56 — Belt Drive Evaporator Fan Performance — 7½-Ton — THC092A3,A4,AW — Downflow Airflow— Standard Refrigeration System
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HP Standard Motor & Field Supplied
Low Static Drive (1)
2400
2700
3000
3300
3600
—
—
—
—
601
—
—
—
—
—
—
—
—
—
—
—
604
639
675
—
—
0.61
0.74
0.89
583
611
643
678
713
0.50
0.60
0.71
0.86
1.02
627
653
682
713
748
0.61
0.71
0.83
0.97
1.14
669
693
719
748
780
0.72
0.83
0.95
1.09
1.26
708
731
755
783
811
0.83
0.95
1.08
1.23
1.40
743
768
791
815
844
0.95
1.07
1.21
1.37
1.55
776 1.08
801 1.20
824 1.35
848 1.52
874 1.70
808 1.21
832 1.33
856 1.48
880 1.66
904 1.86
—
0.68
599
640
0.63
0.79
2-HPStandardMotor&Drive
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors,specificallydesignedandtestedtooperate
reliablyandcontinuouslyatallcatalogedconditions.Usingthefull
horsepower range of our fan motors as shown in our tabular data will
not result in nuisance tripping or premature motor failure. Our
product’swarrantywillnotbeaffected.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
RefertoTablePD-73todetermineadditionalstaticpressuredropduetootheroptions/accessories
2-HPFanMotorHeat(MBH)=2.000xFanBHP+.5000.
3-HPFanMotorHeat(MBH)=2.900xFanBHP+.4750
1. FieldSuppliedFanSheaveAK79andBeltAX38required.
Table PD-56— Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
BHP
2-HP Standard Motor & Drive
1.20
1.30
BHP
1.70
BHP
1.80
RPM BHP
1.90
2.00
CFM
RPM
RPM
BHP
RPM
RPM
BHP RPM RPM
BHP
BHP
RPM
RPM BHP
RPM BHP
2400
2700
3000
3300
3600
839
862
886
910
933
1.34
1.48
1.63
1.81
2.01
868
891
915
939
962
1.48
1.62
1.78
1.96
2.17
898
918
942
967
990
1.61
1.77
1.93
2.12
2.33
926
946
968
993
1016
1.75
1.92
2.09
2.28
2.49
953
971
994
1019
1042
1.89
2.07
2.25
2.45
2.66
980
998
1019
1043
1067
2.04
2.23
2.42
2.62
2.84
1006
1023
1044
1066
1091
2.18 1032
2.38 1049
2.59 1067
2.79 1091
2.34 1056 2.49 1080 2.64
2.54 1074 2.70 1097 2.86
2.75 1092 2.93
1115 3.09
1136 3.34
1158 3.58
2.98
3.21
1113 3.15
1137 3.39
3.02
1114
3-HPOversizedMotor&Drive
Table PD-57 — Belt Drive Evaporator Fan Performance — 7½-Ton —THC092A3,A4,AW — DownflowAirflow — Dehumidification (Hot Gas Reheat) Option
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&LowStaticDrive
AccessoryKit(1)
1500
1800
2100
2400
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
510
534
557
583
0.30
0.36
0.42
0.50
557
579
604
627
0.39
0.45
0.52
0.61
602
621
645
669
0.48
0.55
0.62
0.72
643
661
683
708
0.57
0.65
0.73
0.83
682
699
719
743
0.66
0.75
0.85
0.95
718 0.76
735 0.86
754 0.97
776 1.08
753 0.87
770 0.97
787 1.08
808 1.21
481
506
536
0.27
0.33
0.40
487
0.32
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 2400 CFM.
NOTES:
Trane’s factory supplied motors, in commercial equipment, are
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR009ARequired.
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
2-HPStandardMotor&Drive
2. BAYLSDR009ARequired.
Table PD-57— Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
BHP
1.20
BHP
1.30
BHP
1.70
BHP
1.80
RPM
1.90
2.00
CFM
RPM
RPM
RPM
RPM
BHP RPM RPM
BHP
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HP Standard Motor & Drive
1500
1800
2100
2400
785
802
819
839
0.99
1.09
1.21
1.34
818
833
850
868
1.11
1.20
1.33
1.48
847
863
880
898
1.23
1.32
1.46
1.61
875
892
909
926
1.35
1.46
1.59
1.75
903
920
936
953
1.48
1.59
1.72
1.89
930
947
963
980
1.62
1.73
1.86
2.04
954
973
989
1.74
1.87
2.00 1014
2.18 1032
977
998
1.88
1001 2.01 1023 2.15
2.02 1023 2.17
2.15 1039 2.30
2.34
—
—
—
—
—
—
1006
—
—
2-HPStandardMotor&Low
StaticDriveAccessoryKit(2)
48
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(7½Ton)
High Efficiency
Table PD-58 — Belt Drive Evaporator Fan Performance — 7½-Ton — THC092A3,A4,AW—Horizontal Airflow— Standard Refrigeration System
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&FieldSupplied
LowStaticDrive(1)
2400
2700
3000
3300
3600
—
—
605
658
711
—
—
0.65
0.84
1.07
—
—
603
644
684
728
776
0.52
0.66
0.82
1.02
1.27
653
686
726
767
809
0.63
0.77
0.94
1.15
1.38
707
732
765
805
846
0.75
0.89
1.06
1.28
1.52
754
780
806
840
880
0.88
1.03
1.20
1.40
1.66
792
824
849
876
912
0.99
1.17
1.35
1.55
1.80
825
863
891
916
943
1.09
1.30
1.51
1.71
1.95
857 1.19
895 1.42
929 1.66
955 1.89
886 1.30
925 1.54
962 1.80
991 2.06
595
644
694
746
0.56
0.73
0.93
1.18
980 2.13 1016 2.30
2-HPStandardMotor&Drive
Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors,specificallydesignedandtestedtooperatereliablyandcontinuouslyat
allcatalogedconditions. Usingthefullhorsepowerrangeofourfanmotorsas
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
RefertoTablePD-73todetermineadditionalstaticpressuredropduetootheroptions/accessories
2-HPFanMotorHeat(MBH)=2.000xFanBHP+.5000.
3-HPFanMotorHeat(MBH)=2.900xFanBHP+.4750
1. FieldSuppliedFanSheaveAK79andBeltAX38required..
Table PD-58 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
BHP
1.20
BHP
2-HPStandardMotor&Drive
1.30
1.70
BHP
1.80
RPM
1.90
2.00
CFM
RPM
RPM
RPM
BHP
RPM
BHP RPM RPM
BHP
BHP
RPM
BHP
RPM BHP
RPM BHP
2400
2700
3000
3300
3600
913
954
992
1025
1052
1.40
1.66
1.94
2.22
2.50
941
981
1.51
1.77
2.07
2.38
2.69
966
1006
1045
1082
1117
1.61
1.89
2.20
2.53
2.88
991
1030
1069
1108
1144
1.71
2.00
2.32
2.67
3.05
1017
1054
1094
1132
1170
1.82
2.12
2.46
2.82
3.21
1040
1077
1116
1156
1193
1.92
2.24
2.58
2.96
3.37
1064
1100
1138
1178
—
2.04 1087
2.14
2.47
2.84
1110 2.26
1144 2.60
1181 2.97
1132 2.37
1164 2.71
1202 3.10
2.36
2.71
3.11
—
1121
1160
1200
—
1019
1055
1085
3.25 1221 3.39
—
—
—
—
—
—
—
3-HPOversizedMotor&Drive
Table PD-59— Belt Drive Evaporator Fan Performance — 7½-Ton —THC092A3,A4,AW—Horizontal Airflow — Dehumidification (Hot Gas Reheat) Option
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&Low
StaticDriveAccessoryKit(1)
2-HPStandardMotor&LowStaticDriveAccessoryKit(2)
1500
1800
2100
2400
—
—
—
—
—
—
—
—
509
542
568
603
0.26
0.34
0.42
0.52
558
597
628
653
0.32
0.42
0.52
0.63
601
640
678
707
0.39
0.50
0.63
0.75
640
678
718
754
0.45
0.58
0.72
0.88
678
714
754
792
0.52
0.65
0.81
0.99
715
748
787
825
0.59
0.73
0.90
1.09
750 0.67
780 0.81
817 0.99
857 1.19
783 0.75
811 0.89
846 1.08
886 1.30
472
511
552
0.24
0.33
0.43
502
0.36
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 2400 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils. Trane’s factory supplied motors, in commercial equipment, are
2-HPStandardMotor&Drive
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR009ARequired.
2. BAYLSDR009ARequired.
Table PD-59— Continued
External Static Pressure (Inches of Water)
1.10
BHP
1.20
BHP
1.30
BHP
1.40
BHP
2-HPStandardMotor&Drive
1.50
1.60
1.70
1.80
1.90
2.00
CFM
RPM
RPM
RPM
RPM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
1500
1800
2100
2400
815
842
876
913
0.83
0.98
1.18
1.40
847
872
904
941
0.91
1.07
1.27
1.51
876
901
931
966
0.99
1.16
1.36
1.61
904
929
956
991
1.07
932
957
982
1.16
1.35
1.55
1.82
958
983
1008
1040
1.25
1.44
1.66
1.92
985
1.34
1.54
1.77
1009
1034
1059
1.43
1.64
1.87
2.14
1033 1.51
1058 1.74
1083 1.99
1057 1.61
1081 1.84
1.25
1.46
1.71
1008
1034
1064
—
—
—
—
1017
2.04 1087
—
—
RT-PRC005-EN
49
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(8½ Ton)
High Efficiency
Table PD-60— Belt Drive Evaporator Fan Performance — 8½-Ton — THC102A3,A4,AW — Downflow Airflow— Standard Refrigeration System
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&FieldSupplied
LowStaticDrive(1)
2720
3060
3400
3400
4080
--
--
--
641
693
--
--
--
0.81
1.03
--
--
628
677
726
--
--
0.72
0.92
1.15
584
626
669
713
758
0.53
0.68
0.84
1.04
1.27
626
665
706
749
792
0.64
0.78
0.96
1.17
1.41
668
703
741
781
824
0.76
0.90
1.08
1.30
1.56
708
740
775
813
854
0.88
1.04
1.21
1.43
1.69
746
775
809
845
883
1.00
1.17
1.36
1.58
1.83
781
810
841
875
912
1.12
1.30
1.51
1.73
1.99
814 1.26
843 1.44
873 1.65
905 1.89
940 2.16
845 1.40
875 1.58
904 1.81
935 2.06
968 2.33
2-HPStandardMotor&Drive
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
Trane’sfactorysuppliedmotors, incommercialequipment, aredefinitepurpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. FieldSuppliedFanSheaveAK79andBeltAX38required.
Table PD-60 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
BHP
1.20
BHP
2-HPStandardMotor&Drive
1.30
1.70
BHP
1.80
RPM BHP
1.90
2.00
CFM
RPM
RPM
RPM
BHP
RPM
BHP RPM RPM
BHP
BHP
RPM
RPM BHP
RPM BHP
2720
3060
3400
3400
4080
874
905
933
964
995
1.54
1.73
1.96
2.22
2.51
904
933
1.69
1.89
2.11
2.39
2.69
930
960
990
1.84
2.05
2.27
2.55
2.86
958
986
1016
1045
1075
2.00
2.20
2.44
2.72
3.05
983
2.14
2.37
2.62
2.90
3.23
1010
1035
1065
1095
1124
2.30
2.54
2.79
3.08
3.41
1035
1059
1089
1118
--
2.46 1060
2.71 1083
2.97
3.26
--
2.62 1084 2.78
1109 2.95
1131 3.24
1010
1041
1071
1100
2.89
3.15
3.45
--
1107 3.06
1134 3.34
962
992
1023
1112
1141
--
--
--
--
--
--
--
1018
1048
--
--
--
--
3-HPOversizedMotor&Drive
Table PD-61— Belt Drive Evaporator Fan Performance — 8½-Ton —THC102A3,A4,AW — DownflowAirflow — Dehumidification (Hot Gas Reheat) Option
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&LowStatic
DriveAccessoryKit(2)
2-HPStandardMotor&LowStaticDrive
AccessoryKit(1)
1700
2040
2380
2720
—
—
—
—
—
—
—
—
496
539
—
—
0.33
0.44
481
511
545
584
0.26
0.34
0.42
0.53
533
562
592
626
0.35
0.43
0.52
0.64
578
608
637
668
0.44
0.52
0.63
0.76
621
649
678
708
0.54
0.63
0.74
0.88
661
686
716
746
0.64
0.74
0.86
1.00
700
722
751
781
0.74
0.85
0.98
1.12
736 0.85
757 0.97
784 1.11
814 1.26
770 0.96
791 1.09
815 1.24
845 1.40
490
0.35
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 2720 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR009ARequired.
Trane’s factory supplied motors, in commercial
equipment,aredefinitepurposemotors,
specifically designed and tested to operate reliably
and continuously at all cataloged conditions. Using
the full horsepower range of our fan motors as
2-HPStandardMotor&Drive
shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product’s
warranty will not be affected.
2. BAYLSDR009ARequired.
Table PD-61 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
BHP
1.20
BHP
2-HPStandardMotor&Drive
1.30
1.70
BHP
1.80
RPM BHP
1.90
2.00
CFM
RPM
RPM
RPM
BHP
RPM
BHP RPM RPM
BHP
BHP
RPM
RPM BHP
RPM BHP
1700
2040
2380
2720
802
823
846
874
1.07
1.21
1.37
1.54
833
854
876
904
1.19
1.34
1.51
1.69
864
884
906
930
1.32
1.47
1.65
1.84
893
913
934
958
1.45
1.60
1.79
2.00
921
940
962
983
1.59
1.73
1.93
2.14
948
967
988
1.72
1.87
2.08
2.30
972
993
1014
1035
1.86
998
2.01 1022 2.15 1045 2.30
2.16 1043 2.32 1068 2.48
2.37 1064 2.53 1087 2.69
2.01 1018
2.22 1038
2.46 1060
1010
2.62 1084 2.78
1109 2.95
3-HPOversizeMotor&Drive
Download from Www.Somanuals.com. All Manuals Search And Download.
50
RT-PRC005-EN
Performance
Data
(8½ Ton)
High Efficiency
Table PD-62 — Belt Drive Evaporator Fan Performance — 8½-Ton — THC102A3,A4,AW —Horizontal Airflow— Standard Refrigeration System
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&FieldSupplied
LowStaticDrive(1)
2720
3060
3400
3740
4080
—
—
612
667
726
786
848
0.60
0.80
1.05
1.36
1.72
660
709
760
815
874
0.71
0.91
1.15
1.46
1.83
703
750
800
850
903
0.81
1.03
1.29
1.59
1.95
751
788
836
886
935
0.95
1.15
1.42
1.74
2.10
798
830
870
918
968
1.09
1.29
1.56
1.88
2.26
841
873
907
949
998
1.23
1.45
1.71
2.03
2.42
877
914
945
980
1026
1.36
1.62
1.88
2.19
909 1.48
951 1.77
984 2.06
939 1.60
983 1.92
1020 2.24
631
692
754
817
0.72
0.96
1.26
1.61
1015 2.37 1052 2.57
2.58 1054 2.75 1085 2.94
2-HPStandardMotor&Drive
3-HPOversizedMotor&Drive
Trane’sfactorysuppliedmotors, incommercialequipment, aredefinitepurpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
2-HP Fan Motor Heat (MBH) = 2.000 x Fan BHP+.5000.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.4750
1. FieldSuppliedFanSheaveAK79andBeltAX38required.
Table PD-62 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
BHP
2-HPStandardMotor&Drive
1.20
1.30
BHP
1.70
BHP
1.80
RPM
1.90
2.00
CFM
RPM
RPM
BHP
RPM
RPM
BHP RPM RPM
BHP
BHP
RPM
BHP
RPM BHP
RPM BHP
2720
3080
3400
3740
4080
967
1012
1052
1086
1117
1.72
2.06
2.41
2.77
3.14
994
1039
1083
1119
1.84
2.19
2.58
2.96
3.36
1018
1065
1109
1149
—
1.96
2.32
2.73
3.15
—
1042
1090
1135
1178
—
2.07
2.46
2.88
3.34
—
1066
1113
1159
—
2.19
2.59
3.04
—
1089
1136
1183
—
2.31
2.73
3.19
—
1112
1158
1204
—
2.43
2.86
3.33
—
1134
1179
—
2.55
2.99
—
1155 2.67
1199 3.12 1220 3.26
—
—
—
1176 2.79
—
—
—
—
—
—
—
—
—
—
—
—
—
1151
—
—
—
—
—
—
3-HPOversizedMotor&Drive
Table PD-63 — Belt Drive Evaporator Fan Performance — 8½-Ton —THC102A3,A4,AW —HorizontalAirflow — Dehumidification (Hot Gas Reheat) Option
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
2-HPStandardMotor&FieldSupplied
2-HPStandardMotor&FieldSupplied
LowStaticDriveAccessoryKit(1)
LowStaticDriveAccessoryKit(1)
1700
2040
2380
2720
—
—
—
—
0.36
0.52
473
513
562
612
0.24
0.32
0.45
0.60
542
575
612
660
0.32
0.42
0.54
0.71
591
634
666
703
0.40
0.53
0.66
0.81
633
679
719
751
0.47
0.62
0.78
0.95
672
719
763
798
0.55
0.71
0.90
1.09
707
754
800
841
0.62
0.80
1.01
1.23
742
787
832
877
0.70
0.89
1.11
1.36
774 0.77
817 0.97
863 1.21
909 1.48
807 0.86
846 1.06
893 1.32
939 1.60
509
570
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 2720 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
1. BAYLSDR009ARequired.
2-HPOversizeMotor&Drive
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
2. BAYLSDR009ARequired.
Table PD-63 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
BHP
2-HPStandardMotor&Drive
1.20
1.30
BHP
1.70
BHP
1.80
RPM
1.90
2.00
CFM
RPM
RPM
BHP
RPM
RPM
BHP RPM RPM
BHP
BHP
RPM
BHP
RPM BHP
RPM BHP
1700
2040
2380
2720
839
876
920
967
0.94
1.16
1.42
1.72
869
903
946
994
1.03
1.25
1.52
1.84
898
930
973
1.12
1.34
1.63
1.96
926
957
998
1.21
1.44
1.73
2.07
953
984
1021
1066
1.30
1.54
1.83
2.19
980
1.40
1.64
1.95
2.31
1005
1036
1069
1112
1.49
1.75
2.05 1093
2.43 1134
1031
1061
1.59
1.86
2.16
2.55
1054 1.68
1084 1.96
1115 2.27
1155 2.67
1078 1.78
1108 2.07
1138 2.39
1176 2.79
1010
1047
1089
1018
1042
3-HPOversizedMotor&Drive
RT-PRC005-EN
51
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(10 Ton)
High Efficiency
Table PD-64— Belt Drive Evaporator Fan Performance — 10-Ton — THC120A3,A4,AW — Downflow Airflow— Standard Refrigeration System
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
3-HP Standard Motor & Field Supplied Low Static Drive (1)
3200
3600
4000
4400
4800
—
—
—
764
828
—
—
—
1.36
1.74
—
—
734
795
857
—
—
1.16
1.49
1.88
—
—
—
—
734
782
834
888
942
1.03
1.27
1.58
1.95
2.36
770
815
863
916
970
1.17
1.41
1.72
2.10
2.53
804
847
894
943
996
1.31
1.57
1.87
2.25
2.70
839
879
923
970
1021
1.45
1.73
2.04
2.41
871 1.60
909 1.89
952 2.21
997 2.59
901 1.74
939 2.04
979 2.39
1024 2.78
714
768
825
884
1.02
1.30
1.63
2.02
749
803
857
913
1.14
1.44
1.79
2.18
2.86 1045 3.03 1070 3.22
3-HPStandardMotor&Drive
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. FieldSuppliedMotorSheave1VM50x7/8inch, FanSheaveAK89, andBeltAX40required.
Table PD-64 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
BHP
1.20
BHP
1.30
BHP
1.70
BHP
1.80
RPM
1.90
2.00
CFM
RPM
RPM
RPM
RPM
BHP RPM RPM
BHP
BHP
RPM
BHP
RPM BHP
RPM BHP
3200
3600
4000
4400
4800
931
969
1007
1050
1095
1.89
2.21
2.57
2.97
3.42
959
997
1034
1075
1119
2.06
2.37
2.74
3.17
3.62
986
1024
1062
1101
1143
2.22
2.54
2.93
3.36
3.83
1012
1050
1087
1126
1166
2.39
2.72
3.11
3.55
4.05
1037
1074
1112
1150
1189
2.56
2.89
3.29
3.75
4.26
1061
1098
1136
1173
1212
2.74
3.08
3.47
3.94
4.47
1084
1122
1159
1198
1235
2.91
3.27
3.66
4.15
1108
1145
1182
1219
3.09
3.46
1131 3.28
1166 3.65
1153 3.46
1188 3.85
3.86 1204 4.07 1226 4.28
4.34 1241 4.54 1264 4.77
4.90 1280 5.12 1300 5.32
4.68 1258
5-HPOversizedMotor&Drive
Table PD-65— Belt Drive Evaporator Fan Performance—10-Ton—THC120A3,A4,AW— DownflowAirflow— Dehumidification (Hot Gas Reheat) Option
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
3-HPStandardMotor&Low
StaticDriveAccessoryKit(1)
3-HPStandardMotor&Low
StaticDriveAccessoryKit(2)
2000
2400
2800
3200
—
—
—
—
—
—
—
—
564
618
—
—
0.50
0.67
—
—
607
659
—
—
0.60
0.79
568
606
649
697
0.43
0.56
0.71
0.90
613
650
689
734
0.53
0.67
0.83
1.03
653
691
728
770
0.64
0.78
0.95
1.17
691
728
766
804
0.75
0.90
1.08
1.31
727
763
801
839
0.86
1.02
1.21
1.45
763 0.98
796 1.16
833 1.35
871 1.60
797 1.10
826 1.29
864 1.50
901 1.74
576
0.57
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 3200 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
1. BAYLSDR010ARequired.
Trane’sfactorysuppliedmotors, incommercialequipment,
aredefinitepurposemotors, specificallydesignedandtested
to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan motors
as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product’s warranty
will not be affected.
2. BAYLSDR010ARequired.
Table PD-65 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
BHP
1.20
BHP
1.30
BHP
1.70
BHP
1.80
RPM
1.90
2.00
CFM
RPM
RPM
RPM
RPM
BHP RPM RPM BHP
BHP
RPM
BHP
RPM BHP
RPM BHP
3 HP Standard Motor & Drive
2000
2400
2800
3200
828
858
894
931
1.22
1.43
1.65
1.89
859
888
921
959
1.35
1.56
1.79
2.06
888
916
949
986
1.48
1.70
1.95
2.22
917
945
975
1.61
1.85
2.11
2.39
945
972
1001
1037
1.75
1.99
2.27
2.56
971
998
1027
1061
1.88
2.14
2.43
2.74
998
2.03 1023
2.29 1050
2.59 1076
2.19
1048 2.35 1072 2.50
1023
1051
1084
2.45 1073 2.60 1097 2.76
2.75
3.09
1100 2.92
1131 3.28
1123 3.09
1012
2.91
1108
—
—
52
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
(10 Ton)
High Efficiency
Table PD-66— Belt Drive Evaporator Fan Performance — 10-Ton — THC120A3,A4,AW —Horizontal Airflow— Standard Refrigeration System
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
3-HP Standard Motor & Field Supplied
3-HPStandardMotor&Drive
1.81 983 1.97 1015 2.13
Low Static Drive (1)
3200
3600
4000
4400
4800
—
—
—
777
850
925
1000
—
748
811
1.06
1.39
1.81
2.32
2.95
787
849
1.19
1.54
1.95
2.46
3.07
824
883
1.32
1.68
2.12
2.63
3.23
864
916
977
1039
1101
1.47
1.82
2.28
2.81
3.42
906
950
1006
1067
1130
1.64
1.98
2.43 1035
2.98 1094
946
987
746
822
898
974
1.18
1.59
2.09
2.69
1.27
1.70
2.21
2.83
2.16 1024 2.35 1060 2.55
879
950
1023
912
977
1046
946
1008
1072
2.60 1067 2.79
1101 2.99
1147 3.52
1206 4.19
3.16
3.81
1121 3.33
1181 4.00
3.62
1156
5-HPOversizedMotor&Drive
Trane’s factory supplied motors, in commercial equipment, are
definitepurposemotors, specificallydesignedandtestedtooperate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
product’s warranty will not be affected.
ForStandardEvaporatorFanSpeed(RPM), referenceTablePD-68.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-73 to determine additional static pressure drop due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. FieldSuppliedMotorSheave1VM50x7/8inch,FanSheaveAK89,andBeltAX40required
Table PD-66 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
BHP
1.20
BHP
3-HPStandardMotor&Drive
1.30
1.70
BHP
1.80
RPM
1.90
2.00
CFM
RPM
RPM
RPM
BHP
RPM
BHP RPM RPM
BHP
BHP
RPM
BHP
RPM BHP
RPM BHP
3200
3600
4000
4400
4800
1044
1093
1135
1177
1229
2.28
2.74
3.21
3.73
4.39
1072
1124
1167
1207
1254
2.42
2.92
3.42
3.96
4.59
1097
1151
1198
1239
1282
2.57
3.09
3.63
4.19
4.83
1122
1176
1227
1268
1310
2.71
3.25
3.84
4.42
5.07
1145
1201
1254
1297
1338
2.84
3.42
4.05
4.67
5.32
1168
1224
1278
1324
1365
2.99
3.58
4.23
4.90
5.58
1189
1246
1301
1351
—
3.12 1210
3.74 1268
4.41 1323
5.12 1376
3.27 1231 3.41 1250 3.54
3.90 1289 4.06 1308 4.20
4.60 1344 4.77 1365 4.95
5.35 1398 5.56 1420 5.75
—
—
—
—
—
—
—
5-HPOversizedMotor&Drive
Table PD-67— Belt Drive Evaporator Fan Performance — 10-Ton —THC120A3,A4,AW —Horizontal Airflow — Dehumidification (Hot Gas Reheat) Option
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM BHP
RPM BHP
3-HPStandardMotor&Low
StaticDriveAccessoryKit(1)
3-HPStandardMotor&Low
StaticDriveAccessoryKit(2)
2000
2400
2800
3200
—
—
596
671
—
—
0.58
0.85
—
—
584
627
686
748
0.43
0.57
0.79
1.06
639
683
728
787
0.53
0.70
0.90
1.19
682
734
776
824
0.62
0.83
1.04
1.32
721
776
822
864
0.71
0.94
1.19
1.47
755
812
865
906
0.79
1.05
1.34
1.64
787
845
900
946
0.88
1.15
1.47
1.81
818 0.97
876 1.26
932 1.60
983 1.97
849 1.06
904 1.36
962 1.73
1015 2.13
578
640
706
0.48
0.67
0.93
3-HPOversizedMotor&Drive
***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 3200 CFM.
NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
1. BAYLSDR010ARequired.
Trane’s factory supplied motors, in commercial equipment, are definite
purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower
range of our fan motors as shown in our tabular data will not result in
nuisance tripping or premature motor failure. Our product’s warranty
will not be affected.
2. BAYLSDR010ARequired.
Table PD-67 — Continued
External Static Pressure (Inches of Water)
1.40 1.50 1.60
1.10
BHP
1.20
BHP
1.30
BHP
1.70
BHP
1.80
RPM
1.90
2.00
CFM
RPM
RPM
RPM
RPM
BHP RPM RPM
BHP
BHP
RPM
BHP
RPM BHP
RPM BHP
3-HPStandardMotor&Low
StaticDriveAccessoryKit(2)
3-HPStandardMotor&Drive
2000
2400
2800
3200
877
931
1.15
1.47
1.84
2.28
906
958
1015
1072
1.24
1.58
1.97
2.42
933
983
1040
1097
1.33
1.68
2.09
2.57
961
1008
1064
1122
1.43
1.78
2.21
2.71
988
1032
1087
1145
1.54
1.89
2.34
2.84
1014
1056
1110
1168
1.64
2.00
2.46
2.99
1038
1080
1132
1189
1.74
2.11
2.58
1063
1103
1154
1.85
2.22
2.71
3.27
1087 1.96
1126 2.34
1176 2.83
1111 2.07
1149 2.46
1196 2.95
989
1044
3.12 1210
—
—
—
—
RT-PRC005-EN
53
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Table PD-68— Standard Motor & Sheave/Fan Speed (Rpm)
Unit
6Turns
Open
NA
NA
NA
N/A
N/A
N/A
N/A
5Turns
Open
745
833
897
723
835
787
908
4Turns
Open
819
916
987
779
891
847
969
3Turns
Open
894
1000
1077
835
946
908
1029
2Turns
Open
968
1083
1166
890
1002
968
1090
1Turn
Open
1043
1167
1256
946
1057
1029
1150
Tons
3
Model No.
T#C036A
T#C048A
T#C060A
T#C072A
TSC090,092A
T#C102A
T#C120A
Closed
1117
4
5
6
7½
8½
10
1250
1346
1002
1113
1089
1211
Factory set at 3 turns open.
Table PD-69— Standard Motor & Low Static Drive Accessory Sheave/Fan Speed (Rpm)
Tons
Unit Model
Number
THC036A
Drive Accessory Fan
5Turns
4Turns
Open
470
574
500
652
558
675
498
627
3Turns 2Turns
1Turn
Open
597
732
637
831
710
860
604
761
Kit Sheave Open
BAYLSDR006A AK84x3/4" 427
AK69x3/4" 522
BAYLSDR007A AK79x3/4" 455
AK61x3/4" 593
BAYLSDR008A AK71x3/4" 507
AK59x3/4" 614
BAYLSDR009A AK99x1" 462
AK79x1" 582
BAYLSDR009A AK99x1" 462
AK79x1" 582
BAYLSDR010A AK94x1" 563
AK74x1" 719
Open
512
627
546
712
609
737
533
672
533
672
638
815
Open
555
679
591
771
659
798
569
716
569
716
675
862
Closed
3
640
784
682
890
761
921
640
806
640
806
750
958
4
THC048A
THC060A
THC092A
THC102A
THC120A
5
7.5
8.5
10
498
627
600
767
604
761
713
910
Factory set at 3 turns open.
Table PD-70— Standard Motor & High Static Drive Accessory Sheave/Fan Speed (Rpm)
Unit
6Turns
Open
N/A
N/A
N/A
5Turns
Open
831
958
958
4Turns
Open
895
1022
1022
3Turns
Open
959
1086
1086
2Turns
Open
1022
1150
1150
1Turn
Open
1086
1214
1214
Tons
6
6
Model No.
T#C072A3,A4,AW
TSC072AK
TSC090,092A
Closed
1150
1278
1278
7½
Factory set at 3 turns open.
Table PD-71— Oversized Motor & Drive Sheave/Fan Speed (Rpm)
Unit
6Turns
Open
N/A
N/A
N/A
5Turns
Open
958
1068
958
4Turns
Open
1022
1150
1022
1200
3Turns
Open
1086
1232
1086
1275
2Turns
Open
1150
1315
1150
1Turn
Open
1214
1397
1214
1425
Tons
6
7½
8½
10
Model No.
T#C072A3,A4,AW
TSC090,T#C092A
T#C102A
Closed
1278
1479
1278
N/A
T#C120A
1050
1135
1350
Factory set at 3 turns open.
Table PD-72— Outdoor Sound Power Level - dB (ref. 10 -12 Watts)
Unit
Octave Center Frequency
Overall
Tons
3
Model No.
T*C036A
63.
86
92
90
92
94
94
90
91
92
89
92
88
91
91
94
125
83
87
84
86
87
87
94
95
95
93
96
92
95
88
89
250
81
84
78
83
83
82
90
90
91
88
92
87
90
84
87
500
80
83
77
82
82
81
87
87
88
85
89
84
87
82
85
1000
78
81
76
81
79
78
83
84
84
81
85
80
84
81
84
2000
74
76
72
75
75
74
78
79
80
76
80
75
79
76
78
4000
69
72
70
72
73
72
74
75
75
72
76
72
75
73
75
8000
dBA
83
86
82
85
84
84
88
89
90
87
91
86
89
86
88
68
69
68
69
69
69
67
68
68
66
69
65
68
67
69
TSC048A1
TSC048A3,A4,AW
THC048A
TSC060A
THC060A
TSC072A
THC072A
TSC090A
TSC092A
THC092A
TSC102A
THC102A
TSC120A
THC120A
4
5
6
7½
8½
# Indicates both Standard
and High Efficiency.
10
Note:
Tests follow ARI270-95.
54
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Table PD-73— Static Pressure DropsThrough Accessories (InchesWater Column) — 3 - 10 Tons
Economizer with
Electric Heater
Unit
Model No.
Standard Through
2 Inch
Pleated Filters 100% OA 100% RA 100%OA 100%RA
Downflow Horizontal
0.05 0.05
OA/RA Dampers2
Accessory (kW)3
Tons
CFM
Filters1
Reheat
5-6
9-15
17-36
54
Coil (WC)
960
1200
1440
600
0.03
0.04
0.06
0.01
0.02
0.03
0.04
0.04
0.05
0.08
0.02
0.04
0.05
0.08
0.10
0.15
0.22
0.02
0.04
0.06
0.09
0.04
0.06
0.09
0.06
0.10
0.14
0.02
0.04
0.06
0.09
0.05
0.08
0.12
0.02
0.05
0.08
0.12
0.07
0.11
0.16
0.03
0.07
0.11
0.16
—
—
—
.01
.03
.04
.06
—
0.05
0.07
0.10
0.03
0.04
0.05
0.07
0.06
0.09
0.12
0.03
0.06
0.09
0.12
0.15
0.22
0.29
0.04
0.07
0.10
0.14
0.07
0.09
0.12
0.09
0.13
0.18
0.03
0.06
0.09
0.13
0.08
0.11
0.16
0.05
0.08
0.11
0.16
0.10
0.15
0.20
0.06
0.10
0.15
0.20
0.01
0.02
0.03
0.01
0.01
0.02
0.03
0.03
0.04
0.06
0.01
0.03
0.04
0.06
0.04
0.07
0.10
0.01
0.04
0.07
0.10
0.01
0.02
0.04
0.02
0.05
0.07
0.01
0.02
0.05
0.07
0.03
0.06
0.07
0.01
0.03
0.06
0.07
0.05
0.07
0.09
0.03
0.05
0.07
0.09
0.00
0.01
0.01
0.00
0.00
0.01
0.01
0.01
0.01
0.02
0.00
0.01
0.01
0.02
0.01
0.02
0.04
0.01
0.01
0.02
0.04
0.02
0.02
0.04
0.02
0.05
0.08
0.01
0.02
0.05
0.08
0.04
0.06
0.09
0.02
0.04
0.06
0.09
0.05
0.08
0.10
0.02
0.05
0.08
0.10
.013
.020
.029
—
.013
.020
.029
.023
.036
.052
—
.023
.036
.052
.036
.056
.081
—
.036
.056
.081
0.02
0.02
0.04
0.02
0.05
0.08
—
0.02
0.05
0.08
0.04
0.06
0.09
—
0.04
0.06
0.09
0.05
0.08
0.10
—
.016
.025
.036
—
.019
.030
.043
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
TSC036A
0.07
0.10
0.03
0.05
0.07
0.10
0.08
0.12
0.17
0.04
0.08
0.12
0.17
0.12
0.18
0.26
0.06
0.12
0.18
0.26
0.10
0.11
0.13
0.11
0.14
0.21
0.07
0.11
0.14
0.21
0.12
0.19
0.30
0.07
0.12
0.19
0.30
0.17
0.26
0.34
0.08
0.17
0.26
0.34
0.07
0.10
0.03
0.05
0.07
0.10
0.08
0.12
0.17
0.04
0.08
0.12
0.17
0.12
0.18
0.26
0.06
0.12
0.18
0.26
0.06
0.08
0.10
0.08
0.12
0.25
0.04
0.08
0.12
0.25
0.09
0.18
0.31
0.05
0.09
0.18
0.31
0.14
0.30
0.35
0.07
0.14
0.30
0.35
3
960
.016
.025
.036
.029
.045
.064
—
.019
THC036A
TSC048A
1200
1440
1280
1600
1920
800
.030
.043
.034
.053
.077
—
—
—
4
.02
.05
.07
.09
—
1280
1600
1920
1600
2000
2400
1000
1600
2000
2400
1920
2400
2880
2400
3000
3600
1500
2400
3000
3600
2720
3400
4080
1700
2720
3400
4080
3200
4000
4800
2000
3200
4000
4800
.029
.045
.064
.045
.070
.100
—
.034
.053
.077
.053
.083
.120
—
THC048A
TSC060A
THC060A
—
—
5
.03
.07
.10
.14
—
—
—
—
—
.045
.070
.100
0.011
0.020
0.033
0.020
0.042
0.077
—
.053
.083
.120
0.021
0.034
0.052
0.034
0.063
0.102
—
6
T#C072A
TSC090, 092A
—
7½
.07
.10
.14
.19
—
0.016
0.025
0.036
0.020
0.032
0.047
—
0.021
0.032
0.046
0.026
0.041
0.059
—
THC092A
TSC102A
—
—
—
—
—
—
8½
.08
.12
.17
.23
—
—
—
0.09
0.15
0.22
0.31
0.020
0.032
0.047
0.028
0.045
0.065
—
0.026
0.041
0.059
0.036
0.056
0.081
—
THC102A
TSC120A
THC120A
—
0.042
0.070
0.106
—
0.042
0.070
0.106
10
0.05
0.08
0.10
0.028
0.045
0.065
0.036
0.056
0.081
NOTES:
1. Tested with standard filters (3-5 tons 1" filters, 6-10 tons 2” filters). Difference in
pressure drop should be considered when utilizing optional 2”pleated filters.
2. OA = Outside Air and RA = Return Air.
3. Nominal kW ratings at 240, 480, 600 volts.
RT-PRC005-EN
55
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Table PD-74— Auxiliary Electric Heat Capacity
Total2
Stage1
Stage 2
Unit
Model No.
kW
Input1
MBH
Output1
No. of
Stages
kW
Input1
MBH
Output1
kW
Input1
MBH
Output1
Tons
3
5.00
10.00
13.80
17.07
34.14
47.11
1
2
2
5.00
5.00
8.80
17.07
17.07
30.04
—
5.00
5.00
—
17.07
17.07
T#C036A1
6.00
12.00
17.40
5.00
20.48
40.97
59.40
17.07
1
2
2
1
6.00
6.00
8.70
5.00
20.48
20.48
29.70
17.07
—
6.00
8.70
—
—
T#C036A3, A4, AW
20.48
29.69
—
10.00
13.80
17.60
34.14
47.11
60.09
2
2
2
5.00
8.80
8.80
17.07
30.04
30.04
5.00
5.00
8.80
17.07
17.07
30.04
T#C048A1
4
5
6.00
12.00
17.40
20.48
40.97
59.40
1
2
2
6.00
6.00
8.70
20.48
20.48
29.70
—
6.00
8.70
—
20.48
29.70
T#C048A3, A4, AW
5.00
10.00
13.80
17.60
17.07
34.14
47.11
60.09
1
2
2
2
5.00
5.00
8.80
8.80
17.07
17.07
30.04
30.04
—
—
5.00
5.00
8.80
17.07
17.07
30.04
T#C060A1
6.00
12.00
17.40
23.00
20.48
40.97
59.40
78.52
1
2
2
2
6.00
6.00
8.70
20.48
20.48
29.70
48.82
—
—
T#C060A3, A4, AW
6.00
8.70
8.70
20.48
29.70
29.70
14.30
7.50
10.90
14.4
25.61
37.23
49.18
2
2
2
3.25
5.45
7.20
11.10
18.61
24.59
3.25
5.45
7.20
11.10
18.61
24.59
TSC060AK
9.00
18.00
27.00
36.00
30.73
61.45
92.18
1
1
2
2
9.00
18.00
18.00
18.00
30.73
61.45
61.45
61.45
—
—
9.00
18.00
—
—
30.73
61.45
T#C072A3, A4, AW
6
122.90
11.30
16.90
22.60
38.60
57.72
77.18
1
2
2
11.30
11.30
11.30
38.60
38.60
38.60
—
5.60
11.30
—
19.13
38.60
TSC072AK
9.00
18.00
27.00
36.00
30.73
61.45
92.18
1
1
2
2
9.00
18.00
18.00
18.00
30.73
61.45
61.45
61.45
—
—
9.00
18.00
—
—
30.73
61.45
T#SC090A3, A4, AW
122.90
11.30
16.90
22.60
38.60
57.72
77.18
1
2
2
11.30
11.30
11.30
38.60
38.60
38.60
—
5.60
11.30
—
19.13
38.60
7½
TSC090AK
9.00
18.00
27.00
36.00
30.73
61.45
92.18
1
1
2
2
9.00
18.00
18.00
18.00
30.73
61.45
61.45
61.45
—
—
9.00
18.00
—
—
30.73
61.45
T#C092A3, A4, AW
122.90
9.00
18.00
27.00
36.00
30.73
61.45
92.18
1
1
2
2
9.00
18.00
18.00
18.00
30.73
61.45
61.45
61.45
—
—
9.00
18.00
—
—
30.73
61.45
T#C102A3, A4, AW
TSC102AK
8 ½
122.90
16.90
22.60
18.00
57.72
77.18
61.45
2
2
1
11.30
11.30
18.00
38.60
38.60
61.45
5.60
11.30
—
19.13
38.60
—
T#C120A3, A4, AW
27.00
36.00
54.00
92.18
122.90
184.36
2
2
2
18.00
18.00
36.00
61.45
61.45
122.90
9.00
18.00
18.00
30.73
61.45
61.45
10
16.90
22.60
33.80
57.72
77.18
115.43
2
2
2
11.30
11.30
22.50
38.60
38.60
76.84
11.30
11.30
11.30
38.60
38.60
38.60
TSC120AK
NOTES:
1. Does not include indoor fan power or heat.
2. Heaters are rated at 240v, 380v, 480v. and 600v. For other than rated voltage, CAP =
2
Voltage
Rated Voltage
x rated cap.
(
)
56
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Table PD-75— Electric HeaterVoltage
Correction Factors (Applicable to Auxiliary
Heat Capacity)
Nominal
Voltage
Distribution
Voltage
Capacity
Multiplier
208
230
240
380
440
460
480
540
575
600
0.751
0.918
1.000
1.000
0.840
0.918
1.000
0.810
0.918
1.000
240
380
480
600
Table PD-76 — 3-5Tons AirTemperature Rise Across Electric Heaters (Degrees F)
3Ton
4Ton
5Ton
1
1200 CFM
1600CFM
2000CFM
SinglePhase
Stages T#C036A1
ThreePhase
T#C036A3,A4,AW
SinglePhase
T#C048A1
ThreePhase
T#C048A3,A4,AW
SinglePhase
T#C060A1
ThreePhase
kW
5.00
6.00
7.50
10.00
10.90
12.00
13.80
14.40
17.40
17.60
23.00
T#C060A3,A4,AW
TSC060AK
1
1
2
2
2
2
2
2
2
2
2
13.2
—
—
26.3
—
—
36.4
—
—
—
—
—
15.8
—
—
—
31.6
—
—
45.8
—
—
9.9
—
—
19.8
—
—
27.3
—
—
34.8
—
—
11.9
—
—
—
23.7
—
—
34.4
—
—
7.9
—
—
15.8
—
—
21.8
—
—
27.8
—
—
9.5
—
—
—
19.0
—
—
27.5
—
36.4
—
—
11.9
—
17.2
—
—
22.8
—
—
—
For minimum design airflow, see airflow performance table for each unit.
To calculate temp rise at different air flow, use the following formula: Temp. rise across Electric Heater =
NOTE:
kW x 3414
1.08 x CFM
1. Minimum allowable aiflow with a 17.4 or 17.6 KW heater is 1440 cfm.
Table PD-77 — 6-10Tons AirTemperature Rise Across Electric Heaters (Degrees F)
6Ton
2000CFM
7½Ton
3000CFM
8½Ton
3400CFM
10 Ton
4000CFM
1
T#C090A3, A4, AW
kW
9.00
Stages T#C072A3, A4, AW TSC072AK T#C092A3, A4, AW
TSC090AK
T#C102A3, A4, AW TSC102AK T#C120A3,A4,AW
TSC120AK
1
1
2
1
2
2
2
2
2
14.2
—
—
28.5
—
42.7
—
—
14.9
22.3
—
29.8
—
—
—
—
9.5
—
—
19.0
—
28.5
—
—
11.9
17.8
—
23.8
—
—
—
—
8.4
—
—
—
—
—
—
—
13.4
—
17.9
—
26.7
—
11.30
16.90
18.00
22.60
27.00
33.80
36.00
54.00
—
16.7
—
25.1
—
15.7
—
21.0
—
—
14.2
—
21.3
—
—
56.9
—
37.9
—
33.5
—
—
—
28.5
42.7
—
For minimum design airflow, see airflow performance table for each unit.
To calculate temp rise at different air flow, use the following formula: Temp. rise across Electric Heater =
NOTE:
kW x 3414
1.08 x CFM
1. Minimum allowable aiflow with a 17.4 or 17.6 KW heater is 1440 cfm.
RT-PRC005-EN
57
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Table PD-78— Hot Gas ReheatTemperature Rise3
Leaving Evaporator Dry Bulb [F]
Tons
SCFM
600
720
840
960
1080
1200
1320
1440
35
40
45
50
55
60
65
20.3
19.4
18.5
17.6
16.7
15.8
14.9
14.0
20.0
19.1
18.2
17.3
16.4
15.5
14.6
13.8
19.6
18.7
17.9
17.0
16.1
15.2
14.3
13.5
19.2
18.3
17.5
16.6
15.7
14.9
14.0
13.1
18.8
17.9
17.1
16.2
15.4
14.5
13.6
12.8
18.4
17.6
16.7
15.8
15.0
14.1
13.3
12.4
18.0
17.2
16.3
15.5
14.6
13.8
12.9
12.0
3
Tons
4
SCFM
800
960
1120
1280
1440
1600
1760
1920
35
40
45
50
55
60
65
22.0
21.0
20.0
19.0
17.9
16.9
15.9
14.8
21.8
20.7
19.7
18.7
17.7
16.6
15.6
14.6
21.5
20.5
19.5
18.4
17.4
16.4
15.4
14.4
21.2
20.2
19.2
18.1
17.1
16.1
15.1
14.1
20.9
19.9
18.9
17.9
16.9
15.8
14.8
13.8
20.6
19.6
18.6
17.5
16.5
15.5
14.5
13.5
20.3
19.3
18.2
17.2
16.2
15.2
14.2
13.2
Tons
5
SCFM
1000
1200
1400
1600
1800
2000
2200
2400
35
40
45
50
55
60
65
23.7
22.6
21.4
20.3
19.1
17.9
16.8
15.6
23.6
22.4
21.2
20.1
18.9
17.8
16.6
15.4
23.4
22.2
21.0
19.9
18.7
17.6
16.4
15.2
23.2
22.0
20.9
19.7
18.5
17.4
16.2
15.1
23.0
21.8
20.7
19.5
18.4
17.2
16.0
14.9
22.8
21.6
20.4
19.3
18.1
16.9
15.7
14.6
22.5
21.3
20.2
19.0
17.8
16.6
15.4
14.3
Tons
7½
SCFM
1500
1800
2100
2400
2700
3000
3300
3600
35
40
45
50
55
60
65
22.0
20.2
18.5
16.7
14.9
13.1
11.4
9.6
22.9
21.0
19.2
17.3
15.5
13.7
11.8
10.0
23.8
21.9
19.9
18.0
16.1
14.2
12.3
10.3
24.7
22.7
20.7
18.7
16.7
14.7
12.7
10.7
25.6
23.5
21.4
19.3
17.3
15.2
13.1
11.1
26.5
24.4
22.3
20.1
18.0
15.9
13.7
11.6
27.5
25.3
23.1
20.9
18.7
16.5
14.3
12.2
Tons
8½
SCFM
1700
2040
2380
2720
3060
3400
3740
4080
35
40
45
50
55
60
65
22.6
20.6
18.6
16.6
14.7
12.7
10.7
8.7
23.7
21.6
19.5
17.4
15.3
13.2
11.1
9.0
24.9
22.7
20.4
18.2
15.9
13.7
11.4
9.2
26.1
23.7
21.3
18.9
16.6
14.2
11.8
9.4
27.2
24.7
22.2
19.7
17.2
14.7
12.2
9.6
28.3
25.7
23.0
20.3
17.7
15.0
12.3
9.7
29.4
26.6
23.8
21.0
18.1
15.3
12.5
9.7
Tons
10
SCFM
2000
2400
2800
3200
3600
4000
4400
4800
35
40
45
50
55
60
65
26.0
23.5
21.1
18.7
16.2
13.8
11.3
8.9
26.5
24.1
21.8
19.5
17.2
14.9
12.5
10.2
26.9
24.7
22.5
20.3
18.1
15.9
13.7
11.5
27.4
25.3
23.3
21.2
19.1
17.0
14.9
12.9
27.9
25.9
24.0
22.0
20.1
18.1
16.1
14.2
28.3
26.4
24.6
22.7
20.8
19.0
17.1
15.3
28.6
26.9
25.1
23.4
21.6
19.8
18.1
16.3
NOTES:
1. Temperature rise does not account for indoor fan heat.
2. 70 deg OD Ambient Temperature.
3. For units with the Dehumidification (Hot Gas Reheat) option.
58
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Zone
Controls
Integrated ComfortTM System —
Sensor(s) available with optional
temperature adjustment and override
buttons to provide
Programmable Night Setback — Auto
or manual changeover with seven-day
programming. Keyboard selection of
ReliaTel™ Controlled Units
Zone Sensors are the building
occupant’s comfort control devices for
Precedent™ units with the Micro control:
central control
through aTrane
Integrated
Manual Changeover — Heat, Cool or Off
System Switch. Fan Auto or Off Switch.
One temperature
ComfortTM system.
setpoint lever.
Heat, Cool, Fan, Auto, or On. All
programmable sensors have System On,
Heat, Cool, Service LED/indicators as
standard. Night Setback Sensors have
one (1) Occupied, one (1) Un-occupied,
and two (2) Override programs per day.
DualThermistor Remote Zone Sensor
This sensor will allow the customer to
reduce the total number of remote
sensors to obtain space temperature
averaging. This sensor should be utilized
with ReliaTel controls.
Humidity Sensor — Field installed,
wall-mounted or duct-mounted humidity
sensor is used to control activation of the
hot gas reheat
Manual/Automatic Changeover —
Auto, Heat, Cool or Off System Switch.
Fan Auto or Off Switch.Two temperature
setpoint levers.
Digital Display Zone Sensor
The Digital LCD (Liquid Crystal Display)
zone sensor has the look and functionality
of standard zone
dehumidification
option.The
Optional Status
humidity sensor
sensors.This sensor
Indication LED
can be set for
includes a digital
lights, System On,
humidity levels
display of set point
Heat, Cool, or
between 40% and
60% relative
adjustment and
Service.
space temperature
humidity by
in F (Fahrenheit) or C
adjusting the
(Celsius). Includes
ReliaTel Options
FAN and SYSTEM
Module.
buttons (supports
the service functions
of the standard
CO2 Sensing —The CO2 sensor shall
have the ability to to monitor space
occupancy levels within the building by
measuring the parts per million of CO
(Carbon Dioxide) in the air. As the CO22
levels increase,
sensor). E-squared
memory stores last
programmed set points. Requires 24VAC
(Volts AC).This sensor should be utilized
with ReliaTel™ controls.
Remote Sensor — Sensor(s) available
for all zone sensors to provide remote
sensing capabilities.
the outside air
damper
modulates to
meet the CO2
space ventilation
requirements.
The CO2
accessory shall
be available as
field installed.
RT-PRC005-EN
59
Download from Www.Somanuals.com. All Manuals Search And Download.
Zone
Controls
Electromechanically Controlled
Units
ConventionalThermostats are the
building occupant’s comfort control
devices for electromechanically
controlled units.
Manual Changeover — One Heat, One
CoolThermostat.
Heat, Cool or Off
System Switch.
Fan Auto or On
Switch. Set Point
TM
Dial. Adjustable
90
Heat Anticipator.
70
80
Automatic
Changeover — One Heat,Two Cool
Thermostat. Off, Auto System Switch.
Auto/On Fan Switch.
HEAT
COOL
50 60 70 80
50 60 70 80
50 60 70 80
TM
FAN
AUTO
ON
OFF
AUTO
Programmable Electronic Night Setback
Thermostat — Heating setback and
cooling setup with 7-day, 5-1-1
programming
capability.
Available in two
heating/cooling or
one heating/
cooling versions
with automatic
changeover.
60
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(Standard
Efficiency)
Table ED-1 — Unit Wiring — Standard Efficiency
Optional
Belt Drive Indoor Fan Motor2
Standard Indoor Fan Motor
Minimum Maximum Fuse
Oversize Indoor Fan Motor
Unit
Operating
Voltage Range
187-253
187-253
414-506
Minimum
Circuit
Maximum Fuse
Size or Maximum
Minimum
Circuit
Maximum Fuse
Size or Maximum
Unit
Circuit
Size or Maximum
Tons
3
Model No.
TSC036A1
TSC036A3
TSC036A4
TSC036AW
Ampacity Circuit Breaker1
Ampacity Circuit Breaker1
Ampacity Circuit Breaker1
25.3
17.9
9.2
40
25
15
15
27.7
20.3
10.4
8.3
40
30
15
15
N/A
20.6
10.6
8.3
N/A
30
15
517-633
7.7
15
TSC048A1
TSC048A3
TSC048A4
TSC048AW
TSC060A1
TSC060A3
TSC060A4
TSC060AW
TSC060AK
TSC072A3
TSC072A4
TSC072AW
TSC072AK
TSC090A3
TSC090A4
TSC090AW
TSC090AK
TSC092A3
TSC092A4
TSC092AW
TSC102A3
TSC102A4
TSC102AW
TSC102AK
TSC120A3
TSC120A4
187-253
187-253
414-506
517-633
187-253
187-253
414-506
517-633
342-418
187-253
414-506
517-633
342-418
187-253
414-506
517-633
342-418
187-253
414-506
517-633
187-253
414-506
517-633
342-418
187-253
414-506
34.0
23.9
12.8
9.8
50
35
20
15
60
50
25
15
30
50
25
20
35
60
35
25
40
50
25
20
60
30
25
40
60
35
36.1
26.0
14.4
10.6
49.0
33.2
16.3
12.8
—
34.0
18.2
13.6
—
45.8
24.1
18.8
29.9
42.0
22.0
16.7
48.2
25.5
20.7
35.6
56.6
28.9
50
40
20
15
60
50
25
20
—
50
25
20
—
60
35
25
45
50
25
20
60
35
25
45
60
35
N/A
25.3
13.6
10.0
N/A
30.3
15.6
11.8
—
—
—
—
—
—
—
—
—
—
—
—
—
N/A
35
20
15
N/A
45
25
15
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
4
5
6
47.3
31.5
16.0
12.2
19.6
32.7
17.6
12.8
23.2
42.7
22.6
17.6
28.4
38.9
20.5
15.5
45.1
24.0
19.5
32.6
52.6
26.9
7½
8½
—
—
—
—
10
—
TSC120AW
517-633
21.8
25
23.5
30
—
—
TSC120AK
342-418
32.6
40
35.6
45
—
—
NOTES:
1. HACR breaker per NEC.
2. Optional Belt Drive motor applies to 3-5 ton models only.
The standard motor for 6-10 ton models is belt drive.
RT-PRC005-EN
61
Download from Www.Somanuals.com. All Manuals Search And Download.
(High
Efficiency)
Electrical
Data
Table ED-2 — Unit Wiring — High Efficiency
Optional
Standard Indoor Fan Motor
Minimum Maximum Fuse
Oversize Indoor Fan Motor
Minimum Maximum Fuse
Circuit Size or Maximum
Ampacity Circuit Breaker1
Belt Drive Indoor Fan Motor2
Minimum Maximum Fuse
Unit
Operating
Voltage Range
187-253
187-253
414-506
517-633
187-253
187-253
414-506
517-633
187-253
187-253
414-506
517-633
187-253
414-506
517-633
187-253
414-506
517-633
187-253
414-506
517-633
187-253
414-506
517-633
Unit
Circuit
Size or Maximum
Circuit
Size or Maximum
Tons
3
Model No.
THC036A1
THC036A3
THC036A4
THC036AW
THC048A1
THC048A3
THC048A4
THC048AW
THC060A1
THC060A3
THC060A4
THC060AW
THC072A3
THC072A4
THC072AW
THC092A3
THC092A4
THC092AW
THC102A3
THC102A4
THC102AW
THC120A3
THC120A4
THC120AW
Ampacity Circuit Breaker1
Ampacity Circuit Breaker1
23.9
17.2
9.0
40
25
15
15
45
30
15
15
60
45
20
15
50
25
20
50
25
15
50
25
20
60
30
25
26.3
19.6
10.2
7.7
40
30
15
15
50
35
15
15
60
45
20
15
50
25
20
50
25
20
60
30
20
60
35
25
N/A
19.9
10.4
7.7
N/A
22.6
11.8
8.5
N/A
28.8
14.3
11.4
—
N/A
30
15
15
N/A
35
15
15
N/A
45
20
15
—
7.1
29.4
21.2
11.0
8.3
31.5
23.3
12.6
9.1
4
39.5
30.0
14.7
11.8
34.8
17.5
13.5
38.1
19.4
14.8
42.3
21.4
16.6
48.6
25.3
19.9
41.2
31.7
15.0
12.4
36.1
18.1
14.3
41.2
20.9
16.0
45.4
22.9
17.8
52.6
27.3
21.6
5
6
—
—
—
—
—
—
7½
8½
—
—
—
—
—
—
—
—
—
—
—
—
10
—
—
—
—
NOTES:
1. HACR breaker per NEC.
62
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(Standard
Efficiency)
Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection) —208/230 Volts — Standard Efficiency
Standard Indoor Motor
Oversize Indoor Motor
Max Fuse Size or
To Use
With
Heater
ModelNo.
Heater
kW Rating1
Control
Stages
Max Fuse Size or
Tons
MCA
Max Circuit Breaker2
MCA
Max Circuit Breaker2
208/230 Volts Single Phase
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
3.8/5.0
7.5/10.0
10.4/13.8
1
2
2
25.5/28.9
48.0/55.0
65.1/74.8
40/40
50/60
70/80
28.5/31.9
51.0/58.0
68.1/77.8
40/40
60/60
70/80
3
4
TSC036A1
TSC048A1
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
BAYHTRR118A
3.8/5.0
7.5/10.0
10.4/13.8
13.2/17.6
1
2
2
2
34.0/34.0
49.6/56.6
66.8/76.4
84.0/96.1
50/50
50/60
70/80
90/100
36.1/36.1
52.3/59.3
69.4/79.0
86.6/98.8
50/50
60/60
70/80
90/100
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
BAYHTRR118A
3.8/5.0
7.5/10.0
10.4/13.8
13.2/17.6
1
2
2
2
47.3/47.3
52.9/59.9
70.0/79.6
87.3/99.4
60/60
60/60
80/80
90/100
49.0/49.0
55.0/62.0
72.1/81.8
60/60
60/70
80/90
90/110
5
TSC060A1
89.4/101.54
208/230 Volts Three Phase
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
4.5/6.0
9.0/12.0
13.1/17.4
1
2
2
18.5/20.9
34.1/39.0
48.3/55.3
25/25
35/40
50/60
21.5/23.9
37.1/42.0
51.3/58.3
30/30
40/45
60/60
3
4
TSC036A3
TSC048A3
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
4.5/6.0
9.0/12.0
13.1/17.4
1
2
2
23.9/23.9
35.8/40.6
49.9/56.9
35/35
40/45
50/60
26.0/26.0
38.4/43.3
52.5/59.5
40/40
40/45
60/60
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
BAYHTRR323A
4.5/6.0
9.0/12.0
13.1/17.4
17.3/23.0
1
2
2
2
31.5/31.5
39.0/43.9
53.1/60.1
67.8/76.9
50/50
50/50
60/70
70/80
33.2/33.2
41.1/46.0
55.3/62.3
69.9/79.0
50/50
50/50
60/70
70/80
5
6
TSC060A3
TSC072A3
TSC090A3
TSC092A3
TSC102A3
TSC120A3
BAYHTRS309A
6.8/9.0
1
32.7/33.4
50/50
34.0/35.0
50/50
BAYHTRS318A
BAYHTRS327A
BAYHTRS336A
13.5/18.0
20.3/27.0
27.0/36.0
1
2
2
53.1/60.4
76.6/87.5
100.1/114.5
60/70
80/90
110/125
54.8/62.0
78.3/89.1
101.8/116.1
60/70
80/90
110/125
BAYHTRS309A
BAYHTRS318A
BAYHTRS327A
BAYHTRS336A
6.8/9.0
1
1
2
2
42.7/42.7
54.8/62.0
78.3/89.1
60/60
60/70
80/90
45.8/45.8
58.6/65.9
82.1/93.0
60/60
60/70
90/100
110/125
13.5/18.0
20.3/27.0
27.0/36.0
101.8/116.1
110/125
105.6/120.0
7½
8½
BAYHTRS309A
BAYHTRS318A
BAYHTRS327A
BAYHTRS336A
6.8/9.0
1
1
2
2
38.9/38.9
54.8/62.0
78.3/89.1
50/50
60/70
80/90
42.0/42.0
58.6/65.9
82.1/93.0
50/50
60/70
90/100
110/125
13.5/18.0
20.3/27.0
27.0/36.0
101.8/116.1
110/125
105.6/120.0
BAYHTRT309A
BAYHTRT318A
BAYHTRT327A
BAYHTRT336A
6.8/9.0
1
1
2
2
45.1/45.1
54.8/62.0
78.3/89.1
60/60
60/70
80/90
48.2/48.2
58.6/65.9
82.193.0
60/60
60/70
90/100
110/125
13.5/18.0
20.3/27.0
27.0/36.0
101.8/116.1
110/125
105.6/120.0
BAYHTRT318A
BAYHTRT327A
BAYHTRT336A
BAYHTRT354A
13.5/18.0
20.3/27.0
27.0/36.0
40.6/54.0
1
2
2
2
58.6/65.9
82.1/93.0
105.8/120.0
152.5/141.7
60/70
90/100
110/125
175/150
63.6/70.9
87.1/98.0
110.6/125.0
157.5/146.7
70/80
90/100
125/125
175/150
10
NOTES:
1. Heater kW ratings are at 208/240 for 208/230V unit.
2. HACR type circuit breaker per NEC.
RT-PRC005-EN
63
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(Standard
Efficiency)
Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection)—380, 460 Volts — Standard Efficiency, continued
Standard Indoor Motor
Oversize Indoor Motor
To Use
With
Heater
ModelNo.
Heater
kW Rating1
Control
Stages
Max Fuse Size or
Max Circuit Breaker2
Max Fuse Size or
Max Circuit Breaker2
Tons
MCA
MCA
380 Volts Three Phase
BAYHTRR412A
BAYHTRR418A
BAYHTRR423A
7.5
10.9
14.4
2
2
2
19.6
26.1
32.8
30
30
35
—
—
—
—
—
—
5
6
TSC060AK
TSC072AK
BAYHTRS418A
BAYHTRS427A
BAYHTRS436A
11.3
16.9
22.6
1
2
2
27.6
38.3
49.0
35
40
50
—
—
—
—
—
—
BAYHTRS418A
BAYHTRS427A
BAYHTRS436A
11.3
16.9
22.6
1
2
2
28.4
38.3
49.0
40
40
50
29.9
40.1
50.9
45
45
60
7½
8½
TSC090AK
TSC102AK
BAYHTRT427A
BAYHTRT436A
16.9
22.6
2
2
38.8
49.0
40
50
40.1
50.9
45
60
BAYHTRT427A
BAYHTRT436A
BAYHTRT454A
16.9
22.6
33.8
2
2
2
40.1
50.9
72.3
45
60
80
43.6
54.4
75.8
45
60
80
10
TSC120AK
460 Volts Three Phase
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
6.0
12.0
17.4
1
2
2
10.4
19.4
27.5
15
20
30
11.9
20.9
29.0
15
25
30
3
4
TSC036A4
TSC048A4
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
6.0
12.0
17.4
1
2
2
12.8
20.1
28.3
20
25
30
14.4
22.1
30.3
20
25
35
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
BAYHTRR423A
6.0
1
2
2
2
16.0
21.6
29.8
38.3
25
25
30
40
16.3
22.0
30.1
38.6
25
25
35
40
12.0
17.4
23.0
5
6
TSC060A4
TSC072A4
BAYHTRS409A
BAYHTRS418A
BAYHTRS427A
BAYHTRS436A
9.0
1
1
2
2
17.6
30.3
43.8
57.3
25
35
45
60
18.2
31.0
44.5
58.0
25
35
45
60
18.0
27.0
36.0
BAYHTRS409A
BAYHTRS418A
BAYHTRS427A
BAYHTRS436A
9.0
1
1
2
2
22.6
31.0
44.5
58.0
35
35
45
60
24.1
32.9
46.4
59.9
35
35
50
60
TSC090A4
18.0
27.0
36.0
7½
8½
BAYHTRS409A
BAYHTRS418A
BAYHTRS427A
BAYHTRS436A
9.0
1
1
2
2
20.5
31.0
44.5
58.0
25
35
45
60
22.0
32.9
46.4
59.9
25
35
50
60
TSC092A4
TSC102A4
TSC120A4
18.0
27.0
36.0
BAYHTRT409A
BAYHTRT418A
BAYHTRT427A
BAYHTRT436A
9.0
1
1
2
2
24.0
31.0
44.5
58.0
30
35
45
60
25.5
32.9
46.4
59.9
35
35
50
60
18.0
27.0
36.0
BAYHTRT418A
BAYHTRT427A
BAYHTRT436A
BAYHTRT454A
18.0
27.0
36.0
54.0
1
2
2
2
32.9
46.4
59.9
70.8
35
50
60
80
35.4
48.9
62.4
73.3
40
50
70
80
10
NOTES:
1. Heater kW ratings are at 208/240 for 208/230V, unit.
2. HACR type circuit breaker per NEC.
64
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(Standard
Efficiency)
Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection) — 575 Volts — Standard Efficiency, continued
Standard Indoor Motor
Oversize Indoor Motor
To Use
With
Heater
ModelNo.
Heater
Control
Stages
Max Fuse Size or
Max Fuse Size or
Tons
kW Rating1
MCA
Max Circuit Breaker2
MCA
Max Circuit Breaker2
575 Volts Three Phase
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
6.0
12.0
17.4
1
2
2
8.6
15.8
22.3
15
20
25
9.3
16.6
23.1
15
20
25
3
4
TSC036AW
TSC048AW
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
6.0
12.0
17.4
1
2
2
9.8
16.3
22.8
15
20
25
10.6
17.3
23.8
15
20
25
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
BAYHTRRW23A
6.0
1
2
2
2
12.2
17.1
23.6
30.3
15
20
25
35
12.8
17.8
24.3
31.0
20
20
25
35
12.0
17.4
23.0
5
6
TSC060AW
TSC072AW
BAYHTRSW09A
BAYHTRSW18A
BAYHTRSW27A
BAYHTRSW36A
9.0
1
1
2
2
13.0
23.8
34.6
45.4
20
25
35
50
14.0
24.8
35.6
46.4
20
25
40
50
18.0
27.0
36.0
BAYHTRSW09A
BAYHTRSW18A
BAYHTRSW27A
BAYHTRSW36A
9.0
1
1
2
2
17.6
24.8
35.6
46.4
25
25
40
50
18.8
26.3
37.1
47.9
25
30
40
50
TSC090AW
TSC092AW
18.0
27.0
36.0
7½
8½
BAYHTRSW09A
BAYHTRSW18A
BAYHTRSW27A
BAYHTRSW36A
9.0
1
1
2
2
15.5
24.8
35.6
46.4
20
25
40
50
16.7
26.3
37.1
47.9
20
30
40
50
18.0
27.0
36.0
BAYHTRTW18A
BAYHTRTW27A
BAYHTRTW36A
18.0
27.0
36.0
1
2
2
24.8
35.6
46.4
25
40
50
26.3
37.1
47.9
30
40
50
TSC102AW
TSC120AW
BAYHTRTW18A
BAYHTRTW27A
BAYHTRTW36A
BAYHTRTW54A
18.0
27.0
36.0
54.0
1
2
2
2
26.3
37.1
47.9
56.6
30
40
50
60
28.4
39.3
50.0
58.8
30
40
50
60
10
NOTES:
1. Heater kW ratings are at 208/240 for 208/230V unit.
2. HACR type circuit breaker per NEC.
RT-PRC005-EN
65
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(Standard
Efficiency)
Table ED-4 — Unit Wiring With Electric Heat (Single Point Connection) — Optional Belt Drive — Standard Efficiency
Optional Belt Drive Indoor Motor
To Use
With
Heater
ModelNo.
Heater
Control
Stages
Max Fuse Size or
Tons
kW Rating1
MCA
Max Circuit Breaker2
208/230 Volts Single Phase
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
3
4
TSC036A1
TSC048A1
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
BAYHTRR118A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
BAYHTRR118A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
5
TSC060A1
208/230 Volts Three Phase
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
4.5/6.0
9.0/12.0
13.1/17.4
1
2
2
21.9/24.3
37.5/42.4
51.6/58.6
30/30
40/45
60/60
3
4
TSC036A3
TSC048A3
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
4.5/6.0
9.0/12.0
13.1/17.4
1
2
2
25.3/25.3
37.5/42.4
51.6/58.6
35/35
40/45
60/60
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
BAYHTRR323A
4.5/6.0
9.0/12.0
13.1/17.4
17.3/23.0
1
2
2
2
30.3/30.3
37.5/42.4
51.6/58.6
66.3/75.4
45/45
45/45
60/60
70/80
5
TSC060A3
460 Volts Three Phase
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
6.0
12.0
17.4
1
2
2
12.1
21.1
29.3
15
25
30
3
TSC036A4
TSC048A4
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
6.0
12.0
17.4
1
2
2
13.6
21.1
29.3
20
25
30
4
5
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
BAYHTRR423A
6.0
1
2
2
2
15.6
21.1
29.3
37.8
25
25
30
40
12.0
17.4
23.0
TSC060A4
575 Volts Three Phase
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
6.0
12.0
17.4
1
2
2
9.3
16.6
23.1
15
20
25
3
4
TSC036AW
TSC048AW
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
6.0
12.0
17.4
1
2
2
10.0
16.6
23.1
15
20
25
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
BAYHTRRW23A
6.0
1
2
2
2
11.8
16.6
23.1
29.8
15
20
25
30
12.0
17.4
23.0
5
TSC060AW
NOTES:
1. Heater kW ratings are at 208/240 for 208/230V unit.
2. HACR type circuit breaker per NEC.
66
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(High Efficiency)
Table ED-5 — Unit Wiring With Electric Heat (Single Point Connection) — 208/230 Volts — High Efficiency
Standard Indoor Motor
Oversize Indoor Motor
To Use
With
Heater
ModelNo.
Heater
Control
Stages
Max Fuse Size or
Max Fuse Size or
Tons
kW Rating1
MCA
Max Circuit Breaker2
MCA
Max Circuit Breaker2
208/230 Volts Single Phase
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
3.8/5.0
7.5/10.0
10.4/13.8
1
2
2
25.5/28.9
48.0/55.0
65.1/74.8
40/40
50/60
70/80
28.5/31.9
51.0/58.0
68.1/77.8
40/40
60/60
70/80
3
4
THC036A1
THC048A1
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
BAYHTRR118A
3.8/5.0
7.5/10.0
10.4/13.8
13.2/17.6
1
2
2
2
29.4/30.5
49.6/56.6
66.8/76.4
84.0/96.1
45/45
50/60
70/80
90/100
31.5/33.1
52.3/59.3
69.4/79.0
86.6/98.8
50/50
60/60
70/80
90/100
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
BAYHTRR118A
3.8/5.0
7.5/10.0
10.4/13.8
13.2/17.6
1
2
2
2
39.5/39.5
52.9/59.9
70.0/79.6
87.3/99.4
60/60
60/60
80/80
90/100
41.2/41.2
55.0/62.0
72.1/81.8
89.4/101.5
60/60
60/70
80/90
90/100
5
THC060A1
208/230 Volts Three Phase
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
4.5/6.0
9.0/12.0
13.1/17.4
1
2
2
18.5/20.9
34.1/39.0
48.3/55.3
30/30
35/40
50/60
21.5/23.9
37.1/42.0
51.3/58.3
30/30
40/45
60/60
3
4
THC036A3
THC048A3
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
4.5/6.0
9.0/12.0
13.1/17.4
1
2
2
21.2/22.5
35.8/40.6
49.9/56.9
30/30
40/45
50/60
23.3/25.1
38.4/43.3
52.5/59.5
35/35
40/45
60/60
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
BAYHTRR323A
4.5/6.0
9.0/12.0
13.1/17.4
17.3/23.0
1
2
2
2
30.0/30.0
39.0/43.9
53.1/60.1
67.8/76.9
45/45
45/45
60/70
70/80
31.7/31.7
41.1/46.0
55.3/62.3
69.9/79.0
45/45
45/50
60/70
70/80
5
6
THC060A3
THC072A3
BAYHTRS309A
BAYHTRS318A
BAYHTRS327A
BAYHTRS336A
6.8/9.0
1
1
2
2
34.8/34.8
53.1/60.4
76.6/87.5
50/50
60/70
80/90
35.7/35.7
54.8/62.0
78.3/89.1
101.8/116.1
50/50
60/70
80/90
13.5/18.0
20.3/27.0
27.0/36.0
100.1/114.5
110/125
110/125
BAYHTRT309A
BAYHTRT318A
BAYHTRT327A
BAYHTRT336A
6.8/9.0
1
1
2
2
38.1/38.1
54.8/62.0
78.3/89.1
50/50
60/70
80/90
44.2/44.2
58.6/65.9
82.1/93.0
50/50
60/70
90/100
110/125
7½
8½
THC092A3
THC102A3
THC120A3
13.5/18.0
20.3/27.0
27.0/36.0
101.8/116.1
110/125
105.6/120.0
BAYHTRT309A
BAYHTRT318A
BAYHTRT327A
BAYHTRT336A
6.8/9.0
1
1
2
2
42.3/42.3
54.8/62.0
78.3/89.1
50/50
60/70
80/90
44.2/44.2
58.6/65.9
82.1/93.0
50/50
60/70
90/100
110/125
13.5/18.0
20.3/27.0
27.0/36.0
101.8/116.1
110/125
105.6/120.0
BAYHTRT318A
BAYHTRT327A
BAYHTRT336A
BAYHTRT354A
13.5/18.0
20.3/27.0
27.0/36.0
40.6/54.0
1
2
2
2
58.6/65.9
82.1/93.0
105.6/120.0
152.5/141.7
60/70
90/100
110/125
175/150
63.6/70.9
87.1/98.0
110.6/125.0
157.5/146.7
70/80
90/100
125/125
175/150
10
NOTES:
1. Heater kW ratings are at 208/240 for 208/230V unit.
2. HACR type circuit breaker per NEC.
RT-PRC005-EN
67
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(High Efficiency)
Table ED-5 — Unit Wiring With Electric Heat (Single Point Connection) — 460 Volts — High Efficiency, continued
Standard Indoor Motor
Oversize Indoor Motor
To Use
With
Heater
ModelNo.
Heater
kW Rating1
Control
Stages
Max Fuse Size or
Max Circuit Breaker2
Max Fuse Size or
Max Circuit Breaker2
Tons
MCA
MCA
460 Volts Three Phase
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
6.0
12.0
17.4
1
2
2
10.4
19.4
27.5
15
20
30
11.9
20.9
29.9
15
25
30
3
4
5
THC036A4
THC048A4
THC060A4
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
6.0
12.0
17.4
1
2
2
11.1
20.1
28.3
15
25
30
13.1
22.1
30.3
15
25
35
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
BAYHTRR423A
6.0
1
2
2
2
14.7
21.6
29.8
38.3
20
25
30
40
15.0
22.0
30.1
38.6
20
25
35
40
12.0
17.4
23.0
BAYHTRS409A
BAYHTRS418A
BAYHTRS427A
BAYHTRS436A
9.0
1
1
2
2
17.5
30.3
43.8
57.3
25
35
45
60
18.1
31.0
44.5
58.0
25
35
45
60
6
THC072A4
THC092A4
THC102A4
THC120A4
18.0
27.0
36.0
BAYHTRT409A
BAYHTRT418A
BAYHTRT427A
BAYHTRT436A
9.0
1
1
2
2
19.4
31.0
44.5
58.0
25
35
45
60
20.9
32.9
46.4
59.9
25
35
50
60
7½
8½
18.0
27.0
36.0
BAYHTRT409A
BAYHTRT418A
BAYHTRT427A
BAYHTRT436A
9.0
1
1
2
2
21.4
31.0
44.5
58.0
25
35
45
60
22.9
32.9
46.4
59.9
30
35
50
60
18.0
27.0
36.0
BAYHTRT418A
BAYHTRT427A
BAYHTRT436A
BAYHTRT454A
18.0
27.0
36.0
54.0
1
2
2
2
32.9
46.4
59.9
70.8
35
50
60
80
35.4
48.9
62.4
73.3
40
50
70
80
10
NOTES:
1. Heater kW ratings are at 208/240 for 208/230V unit.
2. HACR type circuit breaker per NEC.
68
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(High Efficiency)
Table ED-5 — Unit Wiring With Electric Heat (Single Point Connection) — 575 Volts — High Efficiency, continued
Standard Indoor Motor
Oversize Indoor Motor
To Use
With
Heater
ModelNo.
Heater
Control
Stages
Max Fuse Size or
Max Fuse Size or
Tons
kW Rating1
MCA
Max Circuit Breaker2
MCA
Max Circuit Breaker2
575 Volts Three Phase
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
6.0
12.0
17.4
1
2
2
8.6
15.8
22.3
15
20
25
9.3
16.6
23.1
15
20
25
3
4
THC036AW
THC048AW
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
6.0
12.0
17.4
1
2
2
9.1
16.3
22.8
15
20
25
10.1
17.3
23.8
15
20
25
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
BAYHTRRW23A
6.0
1
2
2
2
11.8
17.1
23.6
30.3
15
20
25
35
12.4
17.8
24.3
31.0
15
20
25
35
12.0
17.4
23.0
5
6
THC060AW
THC072AW
BAYHTRSW09A
9.0
1
13.5
20
14.3
20
BAYHTRSW18A
BAYHTRSW27A
BAYHTRSW36A
18.0
27.0
36.0
1
2
2
23.8
34.6
45.4
25
35
50
24.8
35.6
46.4
25
40
50
BAYHTRTW18A
BAYHTRTW27A
BAYHTRTW36A
18.0
27.0
36.0
1
2
2
24.8
35.6
46.4
25
40
50
26.3
37.1
47.9
30
40
50
7½
8½
THC092AW
THC102AW
THC120AW
BAYHTRTW18A
BAYHTRTW27A
BAYHTRTW36A
18.0
27.0
36.0
1
2
2
24.8
35.6
46.4
25
40
50
26.3
37.1
47.9
30
40
50
BAYHTRTW18A
BAYHTRTW27A
BAYHTRTW36A
BAYHTRTW54A
18.0
27.0
36.0
54.0
1
2
2
2
26.3
37.1
47.9
56.6
30
40
50
60
28.4
39.3
50.0
58.8
30
40
50
60
10
NOTES:
1. Heater kW ratings are at 208/240 for 208/230V unit.
2. HACR type circuit breaker per NEC.
RT-PRC005-EN
69
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
(High Efficiency)
Table ED-6 — Unit Wiring With Electric Heat (Single Point Connection) — Optional Belt Drive — High Efficiency
Belt Drive Indoor Motor
To Use
With
Heater
ModelNo.
Heater
kW Rating1
Control
Stages
Max Fuse Size Or
Max Circuit Breaker2
Tons
MCA
208/230 Volts Single Phase
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
3
4
THC036A1
THC048A1
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
BAYHTRR118A
N/A
N/A
1N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
BAYHTRR105A
BAYHTRR110A
BAYHTRR114A
BAYHTRR118A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
5
THC060A1
208/230 Volts Three Phase
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
4.5/6.0
9.0/12.0
13.1/17.4
1
2
2
21.9/24.3
37.5/42.4
51.6/58.6
25/25
40/45
60/60
3
4
THC036A3
THC048A3
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
4.5/6.0
9.0/12.0
13.1/17.4
1
2
2
22.6/24.3
37.5/42.4
51.6/58.6
35/35
40/45
60/60
BAYHTRR306A
BAYHTRR312A
BAYHTRR318A
BAYHTRR323A
4.5/6.0
9.0/12.0
13.1/17.4
17.3/23.0
1
2
2
2
28.8/28.8
37.5/42.4
51.6/58.6
66.3/75.4
45/45
45/45
60/60
70/80
5
THC060A3
460 Volts Three Phase
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
6.0
12.0
17.4
1
2
2
12.1
21.1
29.3
15
25
30
3
4
5
THC036A4
THC048A4
THC060A4
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
6.0
12.0
17.4
1
2
2
12.1
21.1
29.3
15
25
30
BAYHTRR406A
BAYHTRR412A
BAYHTRR418A
BAYHTRR423A
6.0
1
2
2
2
14.3
21.1
29.3
37.8
20
25
30
40
12.0
17.4
23.0
575 Volts Three Phase
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
6.0
12.0
17.4
1
2
2
9.3
16,6
23.1
15
20
25
3
4
THC036AW
THC048AW
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
6.0
12.0
17.4
1
2
2
9.3
16.6
23.1
15
20
25
BAYHTRRW06A
BAYHTRRW12A
BAYHTRRW18A
BAYHTRRW23A
6.0
1
2
2
2
11.4
16.6
23.1
29.8
15
20
25
30
12.0
17.4
23.0
5
THC060AW
NOTES:
1. HeaterkWratingsareat208/240for208/230Vunit.
2. HACR type circuit breaker per NEC.
70
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
Table ED-7 — Electrical Characteristics — Evaporator Fan Motor — 60 Cycle — Standard and Oversized
Standard Evaporator Fan Motor
Oversized Evaporator Fan Motor
Amps
FLA
Amps
Unit
Tons Model No.
No.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Volts
208-230
208-230
460
Phase
1
1
1
1
1
1
1
1
1
1
1
1
HP
.33
.33
.33
.33
.60
.60
.60
.60
.90
.90
.90
.90
1.00
1.00
1.00
1.00
2.0
FLA
2.30
2.30
1.10
1.10
3.60
3.60
1.70
1.50
6.20
6.20
2.90
2.10
4.3
LRA
3.90
3.90
2.00
1.80
6.60
6.60
2.80
2.40
14.0
14.0
6.60
4.90
8.3
32.20
16.10
13.20
35.0
No.
1
1
1
1
1
1
1
1
1
1
1
1
—
1
1
1
Volts
208-230
208-230
460
Phase
1
HP
.50
LRA
9.80
9.80
5.20
3.60
T#C036A1
4.70
4.70
2.30
1.70
5.70
5.70
3.30
2.30
7.90
7.90
3.2
3
T#C036A3
T#C036A4
T#C036AW
T#C048A1
T#C048A3
T#C048A4
T#C048AW
T#C060A1
T#C060A3
T#C060A4
T#C060AW
TSC060AK
T#C072A3
T#C072A4
T#C072AW
TSC072AK
T#C090A3
T#C090A4
T#C090AW
TSC090AK
T#C092A3
T#C092A4
T#C092AW
T#C102A3
T#C102A4
T#C102AW
TSC102AK
T#C120A3
T#C120A4
T#C120AW
TSC120AK
1
1
1
1
1
1
1
1
1
1
1
—
.50
.50
.50
.80
..80
.80
.80
1.00
1.00
1.00
1.00
—
575
460
208-230
208-230
460
208-230
208-230
460
13.60
13.60
7.20
4
5
6
575
575
5.80
208-230
208-230
460
575
380
208-230
208-230
460
575
—
16.40
16.40
8.20
2.4
—
5.00
—
1
208-230
460
575
3
3
3
3
5.00
2.50
1.70
4.9
208-230
460
575
3
3
3
—
2.00
2.00
2.00
—
6.30
3.10
2.50
—
48.00
24.00
18.20
—
380
—
—
208-230
460
575
3
3
3
3
2.00
2.00
2.00
2.0
6.30
3.10
2.50
4.9
48.00
24.00
18.20
35.0
1
1
1
1
208-230
460
575
3
3
3
3
3.00
3.00
3.00
3.0
9.40
4.60
3.70
6.4
83.00
42.00
31.00
51.1
380
380
7½
8½
10
208-230
460
575
208-230
460
575
3
3
3
3
3
3
3
2.00
2.00
2.00
2.00
2.00
2.00
2.0
6.30
3.10
2.50
6.30
3.10
2.50
4.9
48.00
24.00
18.20
48.00
24.00
18.20
35.0
1
1
1
1
1
1
1
208-230
460
575
208-230
460
575
3
3
3
3
3
3
3
3.00
3.00
3.00
3.00
3.00
3.00
3.0
9.40
4.60
3.70
9.40
4.60
3.70
6.4
83.00
42.00
31.00
83.00
42.00
31.00
51.1
380
380
208-230
460
575
3
3
3
3
3.00
3.00
3.00
3.0
9.40
4.60
3.70
6.4
83.00
42.00
31.00
51.1
1
1
1
1
208-230
460
575
3
3
3
3
5.00
5.00
5.00
5.0
13.40
6.60
5.40
10.8
112.00
56.00
44.0
380
380
66.5
Table ED-8 — Electrical Characteristics — Evaporator Fan Motor — 60 Cycle — Optional Belt Drive
Amps
Unit
Tons
3
Model No.
No.
Volts
Phase
HP
FLA
LRA
T#C036A3
T#C036A4
T#C036AW
1
1
1
208-230
460
575
3
3
3
1.00
1.00
1.00
5.00
2.50
1.70
32.20
16.10
13.20
T#C048A3
T#C048A4
T#C048AW
1
1
1
208-230
460
575
3
3
3
1.00
1.00
1.00
5.00
2.50
1.70
32.20
16.10
13.20
4
5
T#C060A3
T#C060A4
T#C060AW
1
1
1
208-230
460
575
3
3
3
1.00
1.00
1.00
5.00
2.50
1.70
32.20
16.10
13.20
RT-PRC005-EN
71
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
Table ED-9— Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — Standard Efficiency
Compressor Motors
Condenser Fan Motors
Amps
FLA
1
Amps
Unit
Tons
Model No.
No.
Volts
Phase
HP2
RPM
RLA
LRA
No.
Phase
HP
LRA
TSC036A1
TSC036A3
TSC036A4
TSC036AW
TSC048A1
TSC048A3
TSC048A4
TSC048AW
TSC060A1
TSC060A3
TSC060A4
TSC060AW
TSC060AK
TSC072A3
TSC072A4
TSC072AW
TSC072AK
TSC090A3
TSC090A4
TSC090AW
TSC090AK
TSC092A3
TSC092A4
TSC092AW
TSC102A3
TSC102A4
TSC102AW
TSC102AK
TSC120A3
TSC120A4
TSC120AW
TSC120AK
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
1
2
2
2
1
208-230
208-230
460
1
3
3
3
1
3
3
3
1
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3.1
3.1
3.1
3.1
3.9
3.9
3.9
3.9
5.1
5.1
5.1
5.1
5.1
6
6
6
6
7.5
7.5
7.5
7.5
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
17.2
11.3
6.0
104.0
74.0
37.6
30.4
131.0
91.0
46.0
37.0
144.0
128.0
63.0
49.0
64
156
75
54
70
181.5
95.0
69.0
106.3
91/77
50/39
37/31
128/77
63/39
49/31
64/39
128/91
63/46
49/37
64/54
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
.20
.20
.20
.20
.33
.33
..33
.33
.33
.33
.33
.33
.40
.70
.70
.70
.75
.70
.70
.70
.75
.70
.70
.70
.75
.75
.75
.75
.75
.75
.75
.75
1.5
1.5
.6
2.5
2.5
1.3
3
575
4.9
.5
1.2
208-230
208-230
460
22.7
14.6
7.9
2.0
2.0
1.2
6.6
6.6
2.5
1.5
6.6
6.6
2.5
1.5
4.3
9.30
5.80
3.60
7.7
9.30
5.80
3.60
7.7
9.30
5.80
3.60
9.4
6.8
6.2
7.7
9.4
6.8
6.2
7.7
4
5
575
6.1
.7
208-230
208-230
460
575
380
208-230
460
575
380
208-230
460
575
380
208-230
460
575
208-230
460
575
380
208-230
460
31.3
18.6
9.5
2.0
2.0
1.2
.7
1.1
7.5
11.4
19.0
10.1
7.7
12.2
26.0
13.6
10.9
16.4
3.85
2.50
1.54
2.5
3.85
2.50
1.54
2.5
3.85
2.50
1.54
4.0
2.8
2.4
2.5
4.0
2.8
2.4
2.5
6
7½
8½
4/2.8
4/2.8
4/2.8
3450 14.7/10.3
3450
3450
7.6/5.4
5.8/4.2
5.1/2.8 3450 18.6/10.3
5.1/2.8 3450 10.0/5.4
5.1/2.8 3450
5.1/2.8 3450 12.1/6.6
5.1/3.9 3450 18.6/14.7
5.1/3.9 3450
5.1/3.9 3450
5.1/3.9 3450
8.2/4.2
10
9.5/7.4
7.8/5.8
11.5/9.0
575
380
NOTES:
1. Amp draw for each motor; multiply value by number of motors to determine total amps.
2. HP for each compressor.
72
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
Table ED-10 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — High Efficiency
Compressor Motors
Condenser Fan Motors
Amps1
Unit
Amps1
RLA LRA
88.0
Tons
Model No.
No.
Volts
Phase
HP2
RPM
No.
Phase
HP
FLA
LRA
THC036A1
THC036A3
THC036A4
THC036AW
THC048A1
THC048A3
THC048A4
THC048AW
THC060A1
THC060A3
THC060A4
THC060AW
THC072A3
THC072A4
THC072AW
THC092A3
THC092A4
THC092AW
THC102A3
THC102A4
THC102AW
THC120A3
THC120A4
THC120AW
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
208-230
208-230
460
1
3
3
3
1
3
3
3
1
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
2.8
2.8
2.8
2.8
3.5
3.5
3.5
3.5
4.5
4.5
4.5
4.5
5.7
5.7
5.7
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
16.1
10.7
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
.20
.20
.20
.20
.33
.33
.33
.33
.33
.33
.33
.33
.70
.70
.70
.70
.70
.70
.75
.75
.75
.75
.75
.75
1.5
1.5
2.5
2.5
1.3
1.2
6.6
6.6
2.5
1.5
6.6
77.0
39.0
31.0
3
5.8
4.4
0.6
0.5
2.0
2.0
1.2
0.7
2.0
2.0
1.2
0.9
3.85
2.50
1.54
3.85
2.50
1.54
4.0
2.8
2.4
4.0
2.8
2.4
575
208-230
208-230
460
19.0
12.5
6.5
4.9
25.0
17.4
7.8
6.2
109.0
88.0
44.0
34.0
169.0
124.0
59.6
49.4
156
4
575
208-230
208-230
460
575
208-230
460
575
208-230
460
575
208-230
460
6.6
2.5
1.5
5
20.7
9.30
5.80
3.60
9.30
5.80
3.60
9.4
6.8
6.2
9.4
6
10
75
8.2
54
3.5/3.3 3450
3.5/3.3 3450
3.5/3.3 3450
3.9/3.5 3450
3.9/3.5 3450
3.9/3.5 3450
4.8/3.5 3450
4.8/3.5 3450
4.8/3.5 3450
12.4/12.4
6.4/5.8
4.8/4.8
14.7/12.4
7.1/6.4
5.4/4.8
88/88
44/44
34/34
91/88
50/44
37/34
7½
8½
575
208-230
460
17.3/12.4 124/88
10
9.0/6.4
7.1/4.8
59.6/44
49.4/34
6.8
6.2
575
NOTES:
1. Amp draw for each motor; multiply value by number of motors to determine total amps.
2. HP for each compressor.
RT-PRC005-EN
73
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
Table ED-11— Electrical Characteristics — Power Exhaust
Accessory
Tons
6-10
6-10
6-10
Note:
Model No.
Volts
208-230
460
Phase
HP
RPM1
1075
1075
1075
FLA
5.7
3.3
2.3
LRA
16.3
6.8
BAYPWRX026
BAYPWRX027
BAYPWRX028
1
1
1
0.87
0.87
0.87
575
5.4
1. Two speed.
74
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Jobsite
Connections
Zone Sensors —Typical Number OfWires
DISCONNECT
SWITCH
(BYOTHERS)
A— Manual Changeover...................................... 4
Manual/Auto Changeover ............................. 5
Manual/Auto Changeover with
Status Indication LED’s .......................... 10
Programmable Night Setback with
ZONESENSOR
OR THERMOSTAT
Status Indication LED’s ............................ 7
ROOFTOP
UNIT
Thermostats — Typical Number of Wires
A — 3 wires, 24-volts, Cooling Only
4 wires, 24-volts, with Electric Heat
B— 3 Power Wires + 1 Ground Wire (three phase)
2 Power Wires + 1 Ground Wire (single phase)
For specific wiring information, see the installation instructions.
All wiring except power wires is low voltage.
All customer supplied wiring to be copper and must conform to applicable electrical codes (such as NEC or CEC) and local electrical codes. Wiring shown dotted is to be
furnished and installed by the customer.
RT-PRC005-EN
75
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(3-5Tons)
All dimensions are in inches/millimeters.
3 - 5 Tons Standard Efficiency
3 and 4Tons High Efficiency
32 1/4"
819 MM
4 1/4"
108 MM
23 9/16"
598 MM
42 1/4"
69 7/8"
1073 MM
1775 MM
5 9/16"
141 MM
5 5/8"
143 MM
7 5/8"
194 MM
9 5/8"
244 MM
44 1/4"
1124 MM
36 1/4"
921 MM
5 Tons High Efficiency
4 1/4"
108 MM
23 9/16"
598 MM
42 1/4"
69 7/8"
1073 MM
1775 MM
5 9/16"
141 MM
5 5/8"
143 MM
7 5/8"
194 MM
9 5/8"
244 MM
44 1/4"
1124 MM
76
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(3-5Tons)
All dimensions are in inches/millimeters.
Downflow Airflow Supply/Return
Through the Base Utilities
Horizontal Airflow Supply/Return
Unit Clearance and Roof Opening
RT-PRC005-EN
77
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(3-5Tons)
All dimensions are in inches.
37 1/8”
928 MM
Downflow Duct Connections — Field Fabricated
78
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(6-10Tons)
All dimensions are in inches.
6 Tons Standard and High
Efficiency 7½ Tons Standard
Efficiency
7½ Tons High Efficiency
8½ and 10Tons Standard and High Efficiency
RT-PRC005-EN
79
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(6-10Tons)
All dimensions are in inches.
6-10 Tons — Downflow Airflow Supply and Return;
Through the Base Utilities
Return
6-10 Tons — Horizontal Airflow Supply and Return
Supply
6-10 Tons — Unit Clearance and Roof
Opening
80
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(6-10Tons)
All dimensions are in inches.
6-10 Tons — Roof Curb
857
857
ALL FLANGES 1 1/4” (31 MM)
6-10 Tons — Downflow Duct
Connections — Field Fabricated
RT-PRC005-EN
81
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(3-5Tons Options/
Accessories)
All dimensions are in inches.
Barometric Relief Damper Hood
Economizer , Manual or Motorized Fresh Air Damper
Swing Diameter for Hinged Doors Option
See Page 75 for Through the Base Utilities Information
82
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
(6-10 Tons Options/
Accessories)
All dimensions are in inches.
6-10 Tons — Power Exhaust
6-10 Tons — Economizer and Barometric
Relief Damper Hoods
6-10 Tons — Swing Diameter for Hinged
Door(s) Option
See Page 78 for Through the Base Utilities Information
RT-PRC005-EN
83
Download from Www.Somanuals.com. All Manuals Search And Download.
Weights
Table W-1— Maximum Unit and Corner Weights (Lbs) And Center of Gravity Dimensions (In.)
Maximum Weights (Lbs)
Corner Weights (Lbs)1
Center of Gravity (In.)
Unit
Model No.
Tons
Shipping2
501
Net
409
A
B
C
D
Length
31
Width
19
TSC036A
132
104
79
94
3
4
5
6
THC036A
TSC048A
THC048A
TSC060A
THC060A
518
526
560
543
610
426
434
468
451
518
139
140
146
149
165
108
110
113
114
124
84
91
95
94
32
33
31
31
31
19
19
20
18
19
97
88
111
99
105
124
TSC072A
THC072A
824
861
681
718
236
235
177
182
119
128
150
173
38
38
21
22
TSC090A
TSC092A
THC092A
897
899
1000
754
756
857
257
261
289
188
202
222
129
131
148
180
162
197
37
39
38
22
21
21
7½
8½
TSC102A
THC102A
978
1036
835
893
281
294
223
233
149
159
181
207
40
39
21
22
TSC120A
THC120A
1023
1125
880
982
298
323
238
253
158
178
187
229
40
39
21
22
10
NOTES:
1. Corner weights are given for information only.
2. Weights are approximate.
Table W-2 — Factory-installed Options Net Weights (Lbs)1,2
NetWeight
Accessory
Economizer
Barometric Relief
Powered Exhaust
Motorized Outside Air Damper
Manual Outside Air Damper
Roof Curb
3-5Tons
26
7
—
20
16
70
5
6-10Tons
36
10
80
30
26
115
8
Oversized Motor
Belt Drive Motor
31
7
5
12
10
38
8
15
5
—
7
5
20
12
38
13
30
5
Smoke Detector, Return
Smoke Detector, Supply
Coil Guards
Hinged Doors
Powered Convenience Outlet
Through the Base Electrical
Electric Heaters
Unit Mounted Circuit Breaker
Unit Mounted Disconnect
Novar Control
5
8
5
8
Dehumidification (Hot Gas Reheat) Coil
15
25
NOTES:
1.Weights for options not listed are < 5 lbs.
2.Net weight should be added to unit weight when ordering factory-installed
accessories.
84
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
General
UnitTop
Evaporator and Condenser Coils
The units shall be convertible airflow.
The operating range shall be between
115°F and 0°F in cooling as standard
from the factory for units with
The top cover shall be one piece
construction or where seams exist, it
shall be double-hemmed and gasket-
sealed. The ribbed top adds extra
strength and prevents water from
pooling on unit top.
Internally finned, 5/16” copper tubes
mechanically bonded to a configured
aluminum plate fin shall be standard.
Coils shall be leak tested at the factory to
ensure the pressure integrity.The
microprocessor controls. Operating
range for units with electromechanical
controls shall be between 115°F and
40°F. Cooling performance shall be
rated in accordance with ARI testing
procedures. All units shall be factory
assembled, internally wired, fully
charged with R-22, and 100 percent run
tested to check cooling operation, fan
and blower rotation, and control
sequence before leaving the factory.
Wiring internal to the unit shall be
colored and numbered for simplified
identification. Units shall be UL listed
and labeled, classified in accordance to
UL 1995/CAN/CSA No. 236-M90 for
Central Cooling Air Conditioners.
Canadian units shall be CSA Certified.
evaporator coil and condenser coil shall
be leak tested to 200 psig and pressure
tested to 450 psig.The condenser coil
shall have a patent pending 1 + 1 + 1
hybrid coil designed with slight gaps for
ease of cleaning. A removeable,
reversible, double-sloped condensate
drain pan with provision for through the
base condensate drain is standard.
Filters
One inch, throwaway filters shall be
standard on all 3-5 ton units.The filter
rack can be converted to two inch
capability.Two inch filters shall be factory
supplied on all 6-10 ton units. Optional 2-
inch pleated filters shall be available.
Compressors
Outdoor Fans
All 3 ton standard units shall have direct-
drive, hermetic, reciprocating type
compressors.The reciprocating type
compressors have a centrifugal oil pump
providing positive lubrication to moving
parts. Motor shall be suction gas-cooled
and shall have a voltage utilization range
of plus or minus 10 percent of unit
nameplate voltage. Crankcase heater,
internal temperature, and current-
sensitive motor overloads shall be
included for maximum protection.
Compressors shall have internal spring
isolation and sound muffling to minimize
vibration transmission and noise. Low
pressure switches shall be standard.
The outdoor fan shall be direct-drive,
statically and dynamically balanced,
draw-through in the vertical discharge
position.The fan motor shall be
permanently lubricated and shall have
built-in thermal overload protection.
Indoor Fan
Casing
All 3-5 ton 3-phase units offer a choice of
direct-drive, FC, centrifugal fans or belt
driven, FC centrifugal fans with
Unit casing shall be constructed of zinc
coated, heavy gauge, galvanized steel.
Exterior surfaces shall be cleaned,
phosphatized, and finished with a
weather-resistant baked enamel finish.
Unit’s surface shall be tested 1000
hours in a salt spray test in compliance
with ASTM B117. Cabinet construction
shall allow for all maintenance on one
side of the unit. Service panels shall
have lifting handles and be removed
and reinstalled by removing only a
single fastener while providing a water
and air tight seal. All exposed vertical
panels and top covers in the indoor air
section shall be insulated with a
adjustable motor sheaves. 3-5 ton direct
drive oversized motors shall be available
for high static operations. All 6-10 ton
units shall have belt drive motors with
an adjustable idler-arm assembly for
quick-adjustment to fan belts and motor
sheaves. All motors shall be thermally
protected. All indoor fan motors meet
the U.S. Energy Policy Act of 1992
(EPACT).
3 ton high efficiency and 4-10 ton
standard and high efficiency units shall
have direct-drive, hermetic, scroll type
compressors with centrifugal type oil
pumps. Motor shall be suction gas-
cooled and shall have a voltage
utilization range of plus or minus 10
percent of unit nameplate voltage.
Internal overloads shall be provided with
the scroll compressors. Crankcase
heaters shall be included on 7½ ton
standard efficiency units.
cleanable foil-faced, fire-retardent
permanent, odorless glass fiber
material. The base of the unit shall be
insulated with 1/2 inch, 1 pound density
foil-faced, closed-cell material. All
insulation edges shall be either
captured or sealed.The unit’s base pan
shall have no penetrations within the
perimeter of the curb other than the
raised 11/8 inch high downflow supply/
return openings to provide an added
water integrity precaution, if the
Refrigerant Circuits
Each refrigerant circuit offers a choice of
independent fixed orifice expansion
devices or thermal expansion valve.
Service pressure ports, and refrigerant
line filter driers are factory-installed as
standard. An area shall be provided for
replacement suction line driers.
condensate drain backs up.The base of
the unit shall have provisions for forklift
and crane lifting, with forklift
capabilities on three sides of the unit.
RT-PRC005-EN
85
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
Controls
Roof Curb
Unit shall be completely factory-wired
with necessary controls and contactor
pressure lugs or terminal block for power
wiring. Unit shall provide an external
location for mounting a fused disconnect
device.
The roof curb shall be designed to mate
with the unit’s downflow supply and
return and provide support and a water
tight installation when installed properly.
The roof curb design shall allow field-
fabricated rectangular supply/return
ductwork to be connected directly to the
curb. Curb design shall comply with
NRCA requirements. Curb shall be
shipped knocked down for field assembly
and shall include wood nailer strips.
A choice of microprocessor or
electromechanical controls shall be
available.
Microprocessor controls provide for all 24
volt control functions.The resident control
algorithms shall make all heating, cooling,
and/or ventilating decisions in response
to electronic signals from sensors
Economizer
This accessory shall be either field or
factory-installed and shall be available
with or without barometric relief.The
assembly includes fully modulating 0-100
percent motor and dampers, minimum
position setting, preset linkage, wiring
harness with plug, spring return actuator
and fixed dry bulb control.The barometric
relief shall provide a pressure operated
damper that shall be gravity closing and
shall prohibit entrance of outside air
during the equipment “off” cycle.
Optional solid state or differential
enthalpy control shall be available for
either factory or field installation.The
factory-installed economizer arrives in
the shipping position and shall be moved
to the operating position by the installing
contractor.
measuring indoor and outdoor
temperatures.The control algorithm
maintains accurate temperature control,
minimizes drift from set point, and
provides better building comfort. A
centralized Microprocessor shall provide
anti-short cycle timing and time delay
between compressors to provide a
higher level of machine protection.
24-volt electromechanical control circuit
shall include control transformer and
contactor pressure lugs for power wiring.
Units shall have single point power entry
as standard.
Accessories/Options
Powered Exhaust
Electric Heaters
The field installed powered exhaust,
available for 6-10 ton units, shall provide
exhaust of return air, when using an
economizer, to maintain better bulding
pressurization.
Factory or field-installed electric heat
modules shall be available for installation
within basic unit. Electric heater elements
shall be constructed of heavy-duty nickel
chromium elements internally delta
connected for 240 volt, wye connected
for 480 and 600 volt. Staging shall be
achieved through the unitary control
processor (UCP). Each heater package
shall have automatically reset high limit
control operating through heating
Remote Potentiometer
The minimum position setting of the
economizer shall be adjusted with this
accessory.
Manual Outside Air Damper
Factory or field-installed rain hood and
screen shall provide up to 50 percent
outside air.
element contactors. All heaters shall be
individually fused from the factory, where
required, and shall meet all NEC and CEC
requirements when properly installed.
Power assemblies shall provide single-
point connection. Electric heat modules
shall be UL listed or CSA certified.
Motorized Outside Air Dampers
Factory or field-installed manually set
outdoor air dampers shall provide up to
50 percent outside air. Once set, outdoor
air dampers shall open to set position
when indoor fan starts.The damper shall
close to the full closed position when
indoor fan shuts down.
86
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
Discharge Air Sensing
Powered or Unpowered Convenience
Outlet
This factory or field-installed option
provides true discharge air sensing in
heating models.This sensor is a status
indicator readable throughTracer™ or
Tracker™. This option is available for
microprocessor controlled units.
This factory-installed option is a GFCI,
120v/15amp, 2 plug, convenience outlet,
either powered or unpowered.When the
convenience outlet is powered, a service
receptacle disconnect will be available.
The convenience outlet is powered from
the line side of the disconnect or circuit
breaker, and therefore will not be affected
by the position of the disconnect or circuit
breaker.This option can only be ordered
when theThrough the Base Electrical with
either the Disconnect Switch or Circuit
Breaker option is ordered.
Oversized Motors
Factory or field-installed direct drive
oversized motors shall be available for
high static applications.
Through the Base Electrical Access
An electrical service entrance shall be
factory provided allowing electrical
access for both control and main power
connections inside the curb and through
the base of the unit. Option will allow for
field installation of liquid-tight conduit and
an external field-installed disconnect
switch.
Phase Monitor
Phase monitor shall provide 100%
protection for motors and compressors
against problems caused by phase loss,
phase imbalance, and phase reversal.
Phase monitor is equipped with an LED
that provides an ON or FAULT indicator.
Through the Base Electrical with
Disconnect Switch
Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch is
available, factory-installed, to achieve
active fan failure indication and/or
clogged filter indication.These indications
will be registered with either a zone
sensor with status indication lights or an
Integrated Comfort™ System.This option
is available for microprocessor controlled
units.
Factory-installed 3-pole, molded case,
disconnect switch with provisions for
through the base electrical connections
are available.The disconnect switch will
be installed in the unit in a water tight
enclosure with access through a swinging
door. Factory wiring will be provided from
the switch to the unit high voltage
terminal block.The switch will be UL/CSA
agency recognized. Note:The disconnect
switch will be sized per NEC and UL
guidelines but will not be used in place of
unit overcurrent protection.
Reference or Comparative Enthalpy
Factory-installed Reference or
Comparative Enthalpy option shall be
available when a factory-installed
Economizer is ordered.This option is
available for microprocessor controlled
units.
Through the Base Electrical with Circuit
Breaker
This option is a factory-installed, thermal
magnetic, molded case, HACR Circuit
Breaker with provisions for through the
base electrical connections.The circuit
breaker will be installed in a water tight
enclosure in the unit with access through
a swinging door. Factory wiring will be
provided from the switch to the unit high
voltage terminal block.The circuit breaker
will provide overcurrent protection, be
sized per NEC and UL guidelines, and be
agency recognized by UL/CSA.
High Pressure Cutout
This factory-installed option is offered for
units that do not have High Pressure
cutout as standard. All 3-phase units with
scroll compressors include High Pressure
Cutout as standard.
Hinged Access Doors
Sheet metal hinges are available factory-
installed on the Filter/Evaporator, Supply
Fan/Heat, and the Compressor/Control
Access Doors.
RT-PRC005-EN
87
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
Supply and/or Return Air Smoke
Detector
Zone Sensor
This field-installed control shall be
provided to interface with the Micro
equipped units and shall be available in
either manual, automatic programmable
with night setback, with system
malfunction lights, or remote sensor
options.
With this option factory-installed, if smoke
is detected, all unit operation will be shut
down. Reset will be manual at the unit.
Return Air Smoke Detectors require
minimum allowable airflow when used
with certain models. See the Installation,
Operation, and Maintenance (IOM)
manual for the models affected and the
minimum allowable airflow required.This
option is available for microprocessor
controlled units.
Thermostat
Two stage heating and cooling operation
or one stage heating and cooling shall be
available, for field installation, in either
manual or automatic changeover.
Automatic programmable electronic with
night set back shall also be available.
Black Epoxy Coated Condenser Coil
The coil provides corrosion protection to
condenser coils for seacoast application.
The protection is a factory-applied
thermoset vinyl coating, bonded to
normal aluminum fin stock.The uniform
thickness of the bonded vinyl layer
exhibits excellent corrosion protection in
salt spray tests performed in accordance
with ASTM B117.
Differential Pressure Switches
These factory or field-installed sensors
allow individual fan failure and dirty filter
indication for microprocessor controlled
units.The fan failure switch will disable all
unit functions and “flash” the Service
LED on the zone sensor.The dirty filter
switch will light the Service LED on the
zone sensor and will allow continued unit
operation.
Dehumidification Option
The dehumidification (hot gas reheat)
option shall be a factory-installed option
that provides increased dehumidification.
The option shall consist of a hot-gas
reheat coil located on the leaving air side
of the evaporator coil prepiped and
circuited.
Enthalpy Control
Replaces the dry bulb control with a wet
bulb changeover controller which has a
fully adjustable set point. Enthalpy control
offers a higher level of comfort control,
along with energy savings potential, than
the standard dry bulb control. This is due
to the additional wet bulb sensing
The option shall be equipped with
crankcase heater(s), low pressure
switch(es), Frostat™, and a thermostatic
expansion valve(s) (TXV) as standard.
capability.This option shall be available
for microprocessor controlled units. It can
be field-installed, or factory-installed with
the factory-installed economizer.
Control Options
Trane Communication Interface
This factory or field-installed option shall
be provided to interface microprocessor
controlled units with theTrane Integrated
ComfortTM systems.
Differential Enthalpy
Replaces the standard dry bulb control
with two enthalpy sensors that compare
total heat content of the indoor air and
outdoor air to determine the most
efficient air source.This control option
offers the highest level of comfort control,
plus energy efficiency, available.This
option shall be available for
LonTalk® Communication Interface
This factory or field-installed option shall
be provided to allow the unit to
communicate as aTracer™LCI-R device
or directly with generic LonTalk Network
Building Automation System Controls.
microprocessor controlled units. It can be
field-installed, or factory-installed with the
factory-installed economizer.
88
RT-PRC005-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
LowAmbient Cooling
Digital Display Zone Sensor
All microprocessor units shall have
cooling capabilities down to 0°F as
standard. Electromechanical models
have cooling capabilites to 40°F as built,
or to 0°F by adding the optional low
ambient (frostat) control.
The Digital LCD (Liquid Crystal Display)
zone sensor has the look and functionality
of standard zone sensors.This sensor
includes a digital display of set point
adjustment and space temperature in F
(Fahrenheit) or C (Celsius). Includes FAN
and SYSTEM buttons (supports the
service functions of the standard sensor).
E-squared memory stores last
Thermal ExpansionValve
All units shall have a short orifice
refrigerate control metering device. For
more exact refrigerant flow, when using
unit in low airflow applications, aThermal
ExpansionValve option shall be available.
programmed set points. Requires 24VAC
(Volts AC).This sensor should be utilized
with ReliaTel™ controls.
DualThermistor Remote Zone Sensor
This sensor will allow the customer to
reduce the total number of remote
sensors to obtain space temperature
averaging. This sensor should be utilized
with ReliaTel controls.
Novar Unit Controls
Optional Novar rooftop unit controls shall
be factory installed and tested. The
Novar electronic thermostat module will
interface to the unit microprocesser and
will control the unit to the desired stage of
cooling or heating.
Humidity Sensor
Field installed, wall-mounted humidity
sensor is used to control activation of the
hot gas reheat dehumidification option.
The humidity sensor can be set for
humidity levels between 40% and 60%
relative humidity by adjusting the ReliaTel
Options Module.
Novar Return Air Sensor
This option, when used in conjunction
with Novar Controls, will contain a factory
provided and wired zone temperature
sensor located in the return air stream.
CO2 Sensing
The CO2 sensor shall have the ability to
monitor space occupancy levels within
the building by measuring the parts per
million of CO2 (Carbon Dioxide) in the air.
As the CO2 levels increase, the outside air
damper modulates to meet the CO2
space ventilation requirements.The CO2
accessory shall be available as field
installed.
Humidity Sensor
Field installed, duct-mounted humidity
sensor is used to control activation of the
hot gas reheat dehumidification option.
The humidity sensor can be set for
humidity levels between 40% and 60%
relative humidity by adjusting the ReliaTel
Options Module.
Ventilation Override Accessory
With theVentilation Override Accessory
installed, the unit can be set to transition
up to 3 different pre-programmed
sequences for Smoke Purge,
Pressurization, and Exhaust.The
transition occurs when a binary input on
the RTOM is closed (shorted).This would
typically be a hard wired relay output
from a smoke detector or fire control
panel.The ventilation override accessory
shall be available as field installed.
RT-PRC005-EN
89
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
*High Efficiency Units only
Literature Order Number
File Number
RT-PRC005-EN
PL-UN-RT-TSC/THC 3-10TONS-PRC005-EN-2-04
PL-UN-RT-TSC/THC 3-10TONS-PRC005-EN-12-03
06-03 Webb/Mason 2-04 Electronic Only
Supersedes
Trane
Stocking Location
A business of American Standard Companies
For more information contact your local dealer
(distributor), local district office, or e-mail us at
Trane has a policy of continuous product and product data improvement and reserves the right to change design
and specifications without notice.
Download from Www.Somanuals.com. All Manuals Search And Download.
|