Installation/
Operator
Maintenance
VariTrane™ Single-Duct
and Fan-Powered Units
AllVariTraneVAV Models with pneumatic, electronic, DDC controls and diffusers.
June 2006
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
Service Model Number Description ..................4 – 14
General Information ............................................... 15
Literature Contents
Receiving and Handling
Warnings and Cautions Explanations
Unit Information ............................................. 16 – 17
Single-Duct Units
Dual-Duct Units
Fan-Powered and Low-Height Units
Unit Installation .............................................. 18 – 31
Hanging Bracket Locations
Unit Weights
Water Coil Connections
Unit Accessibility
Clearances
Actuator Mounting
Unit Setup ......................................................32 – 46
Flow Sensor ∆P vs. Airflow Delivery
Maximum Fan Motor Amperage
(SCR) Motor Speed Control Adjustment Procedure
Electrically Commutated Motor (ECM)
ECM CFMTables
Wiring Diagrams ............................................. 47 – 54
Maintenance .......................................................... 55
Motors
FanWheel
Filter
Water Coil
Fan Motor Replacement
Installation of Diffusers .......................................... 56
T-Bar Ceiling
Concealed Spline Ceiling
Drywall/Plaster Ceiling
VAV-SVN01E-EN
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Model
Number Description
Single-Duct Units
Digit 1, 2—UnitType
WARNING
FM00 FM – Customer-supplied
Fiberglass Wool!
actuator & controller
FM01 FM –Trane actuator w/ cusomer-
supplied control
VC
VariTrane single-duct
WARNING: ALL INSULATED UNITS
(except closed-cell foam insulation)
CONTAIN FIBERGLASSWOOL! Read
this literature prior to installation for
proper instruction. Disturbing the
insulation in this product during
installation, maintenance or repair will
expose you to airborne particles of
glass wool fibers and ceramic fibers
known to the state of California to
cause cancer through inhalation. Glass
wool fibers may also cause respiratory,
skin or eye irritation.
Digit 3—Reheat
C
Cooling Only
VMA1 FM – Johnson controlsVMA-1410
VMA2 FM – Johnson controlsVMA-1420
PWR1 FM – Seimens 540-100 w/
GDE131.1P actuator
PWR4 FM – Seimens 540-100 w/Trane
actuator
PWR5 FM – Seimens 540-100 w/
GDE131.1U actuator
AT01 FM – Automated Logic U341V+
AT02 FM – Automated Logic U141V+
EI05 Analog –With optional on/off
reheat
EI28 Analog –With optional on/off
reheat with dual-minimum cfm
EI29 Analog –With optional on/off
reheat with constant-volume cfm
PC00 PN – N.C.Trane pneumatic
actuator
PC04 PN – N.C. with optional on/off HW,
DA Stat
PC05 PN – N.C. with optional on/off
electric, RA Stat
E
Electric Heat
W
HotWater Heat
Digit 4—Development Sequence
Sixth
Digit 5, 6—PrimaryAirValve
F
04
05
06
08
10
12
14
16
24
4" inlet (225 cfm)
5" inlet (350 cfm)
6" inlet (500 cfm)
8" inlet (900 cfm)
10" inlet (1400 cfm)
12" inlet (2000 cfm)
14" inlet (3000 cfm)
16" inlet (4000 cfm)
24" x 16" inlet (8000 cfm)
Digit 7, 8—Not Used
00 N/A
Digit 9—Not Used
N/A
Digit 10, 11—Design Sequence
H0 Fourth (factory assigned)
0
PN00 PN – N.O.Trane pneumatic
actuator, RA Stat
Digit 12, 13, 14, 15—Controls
ENON No controls, field-installed
DDC/electric
PNON No controls, field-installed
pneumatic
DD00 Trane elec actuator only
DD01 DDC – Cooling only
DD02 DDC – N.C. on/off water valve
control
PN04 PN – N.O. PVR, DA Stat
PN05 PN – N.O. PVR, RA Stat
PN11 PN – N.O. dual-minimum cfm,
DA Stat
PN32 PN – WaterValve, N.O. constant
volume, DA Stat
PN34 PN – Electric heat, N.O. constant
volume, DA Stat
DD03 DDC – Prop hot water valve
control
DD04 DDC – On/off electric heat
DD05 DDC – Pulse-width modulation
electric heat
DD07 DDC – N.O. on/off water valve
control
DD11 LonTalk DDC Controller—
Cooling only
DD12 LonTalk DDC Controller w/ N.C.
on/off hot water control
DD13 LonTalk DDC Controller w/
proportional hot water control
DD14 LonTalk DDC Controller–on/off
electric heat control
DD15 LonTalk DDC Controller w/
pulse-width modulation electric
heat control
DD17 LonTalk DDC Controller w/ N.O.
on/off hot water control
Notes:
N.C. =
N.O. =
Normally-closed
Normally-opened
DA Stat = Direct-acting pneumatic t-stat
(by others)
RA Stat = Reverse-acting pneumatic
t-stat (by others)
PN =
FM =
Pneumatic
Factory installation of customer-
supplied controller
PVR =
PneumaticVolume Regulator
Digit 16—Insulation
A
B
C
D
F
1/2" Matte-faced
1" Matte-faced
1/2" Foil-faced
1" Foil-faced
1" Double-wall
3/8" Closed-cell
G
4
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Model
Number Description
Single-Duct Units (con't.)
Digit 17—Not Used
Digit 23—Transformer
Digit 27, 28, 29—Electric Heat kW
0
N/A
Digit 18—Not Used
N/A
0
1
2
3
4
5
6
7
8
None
000
050
010
015
None
120/24 volt (50VA)
208/24 volt (50VA)
240/24 volt (50VA)
277/24 volt (50VA)
480/24 volt (50VA)
347/24Volt (50VA)
575/24Volt (50VA)
380/24Volt (50VA)
0.5 kW
1.0 kW
1.5 kW
0
Digit 19—Outlet Plenum (Connection is
Slip & Drive)
0
A
B
C
D
E
F
None
460
46.0 kW
1 Outlet RH
1 Outlet END
Notes:
1 Outlet LH
0.5 to 8.0 kW – ½ kW increments
8.0 to 18.0 kW – 1 kW increments
18.0 to 46.0 kW – 2 kW increments
Note: ForVCEF units with transformers
theVA depends on the staging, control,
and contactor type (ranges are 40VA
to 75VA)
2 Outlets, 1 RH, 1 END
2 Outlets, 1 LH, 1 END
2 Outlets, 1 RH, 1 LH
3 Outlets, 1 LH, 1 RH, 1 END
4 Outlets, 1 LH, 1 RH, 2 END
H
J
Digit 30—Electric Heat Stages
0
1
2
3
None
1 Stage
2 Stages Equal
3 Stages Equal
Digit 24—Disconnect Switch
0
W
Note: See unit drawings for outlet sizes/
damper information.
None
With
Digit 20—Not Used
Note: VCCF,VCWF –Toggle Disconnect
VCEF – Door Interlocking Power
Disconnect
Digit 31—Contactors
0
N/A
0
1
2
3
4
None
24-volt magnetic
24-volt mercury
PE with magnetic
PE with mercury
Digit 21—Water Coil
0
1
2
None
1-Row
2-Row
Digit 25—Power Fuse
0
W
None
With
Digit 32—Not Used
0 N/A
Digit 22—Electrical Connections (VCCF,
VCWF can be flipped in the field to
achieve opposite-hand connection)
Digit 26—Electric HeatVoltage
0
None
A
B
C
D
E
F
208/60/1
208/60/3
240/60/1
277/60/1
480/60/1
480/60/3
347/60/1
575/60/3
380/50/3
120/60/1
L
R
0
Left (Airflow hitting you in the
face)
Right (Airflow hitting you in the
face)
Opposite side connection – coil
and control
G
H
J
K
VAV-SVN01E-EN
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Model
Number Description
Dual-Duct Units
Digit 1, 2, 3—UnitType
VDD VariTrane dual-duct
Digit 4—Development Sequence
Digit 19—Outlet Plenum (Connection is
slip & drive)
FM00 FM – Customer-supplied
actuator & controller
FM01 FM –Trane actuator w/
customer-supplied controller
PC03 PN – N.C. heating/ N.O. cooling
w/ PVRs, DA stat
PN08 PN – N.O. heating/ N.O. cool
act. only, RA stat
PN09 PN – N.O. htg/clg vlvs w/ PVRs,
DA stat
0
none
A
B
C
D
E
F
1 outlet–RH
F
Sixth
1 outlet–END
1 outlet–LH
Digit 5, 6—PrimaryAirValve
05
06
08
10
12
14
16
5" inlet (350 cfm)
6" inlet (500 cfm)
6" inlet (900 cfm)
10" inlet (1400 cfm)
12" inlet (2000 cfm)
14" inlet (3000 cfm)
16" inlet (4000 cfm)
2 outlets–1 RH, 1 END
2 outlets–1 LH, 1 END
2 outlets–1 RH, 1 LH
2 outlets - END
3 outlets–1 LH, 1 RH, 1 END
4 outlets–1 LH, 1 RH, 2 END
G
H
J
PN10 PN – N.O. htg/clg w/ PVRs (cv
disch), DA stat.
Note: See unit drawings for outlet sizes/
damper information.
Notes:
N.C. =
N.O. =
Digit 7, 8—SecondaryAirValve
Normally-closed
Normally-opened
05
06
08
10
12
14
16
5" inlet (350 cfm)
6" inlet (500 cfm)
8" inlet (900 cfm)
10" inlet (1400 cfm)
12" inlet (2000 cfm)
14" inlet (3000 cfm)
16" inlet (4000 cfm)
DA Stat = Direct-acting pneumatic t-stat
(by others)
RA Stat = Reverse-acting pneumatic t-stat
(by others)
Digit 20—Not Used
0
N/A
Digit 21—Not Used
N/A
Digit 22—Not Used
N/A
Digit 23—Transformer
0
PN =
FM =
Pneumatic
Factory installation of customer-
supplied controller
Digit 9—Not Used
N/A
Digit 10, 11—Design Sequence
C0 Third (factory assigned)
0
PVR =
PneumaticVolume Regulator
0
0
1
2
3
4
5
6
7
None
Digit 16—Insulation
120/24 volt (50VA)
208/24 volt (50VA)
240/24 volt (50VA)
277/24 volt (50VA)
480/24 volt (50VA)
347/24 volt (50VA)
575/24 volt (50VA)
A
B
C
D
F
1/2" Matte-faced
1" Matte-faced
1/2" Foil-faced
1" Foil-faced
1" Double-wall
3/8" Closed-cell
Digit 12, 13, 14, 15—Controls
ENON No Controls, Field-installed
DDC/Electric
PNON No Controls, Field-installed
Pneumatic
DD00 Trane elec actuator only
DD01 DDC – Cooling only
DD08 DDC – Constant-volume
discharge
DD11 LonTalk DDC Controller—
Cooling only
DD18 LonTalk DDC Controller—
ConstantVolume Discharge
G
Digit 17—Not Used
N/A
Digit 18—Not Used
N/A
Digit 24—Disconnect Switch
0
0
W
None
WithToggle
0
Digit 25—Power Fuse
0
W
None
With
6
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Model
Number Description
Fan-Powered Parallel Units
Digit 1, 2—UnitType
Digit 20—Attenuator
DD15 LonTalk DDC Controller w/
pulse-width modulation electric heat
control
DD17 LonTalk DDC Controller w/ N.O.
on/off hot water control
FM00 FM customer actuator & control
FM01 FMTrane actuator w/ customer-
supplied controller
VMA2 FM Johnson Controls
VMA-1420
PWR1 FM Seimens 540-100 w/
GDE131.1P actuator
PWR4 FM Seimens 540-100 w/Trane
actuator
PWR5 FM Seimens 540-100 w/
GDE131.1U actuator
0
W
None
With
VP
VariTrane fan-powered parallel
Digit 3—Reheat
Digit 21—Water Coil
C
Cooling Only
0
1
2
3
4
5
6
None
E
Electric Heat
1-Row–Plenum inlet installed RH
2-Row–Plenum inlet installed RH
1-Row–Discharge installed, LH
1-Row–Discharge installed, RH
2-Row–Discharge installed, LH
2-Row–Discharge installed, RH
W
HotWater Heat
Digit 4—Development Sequence
Sixth
Digit 5, 6—PrimaryAirValve
F
05
06
08
10
12
14
16
5" inlet (350 max cfm)
6" inlet (500 max cfm)
8" inlet (900 max cfm)
10" inlet (1400 max cfm)
12" inlet (2000 max cfm)
14" inlet (3000 max cfm)
16" inlet (4000 max cfm)
Digit 22—Electrical Connections
L
R
Left
Right
Electrical Connections Note:Airflow
hitting you in the face.
AT01 FM Automated Logic U341V+
AT02 FM Automated Logic U141V+
EI05 Analog – fan-powered parallel
with optional on/off reheat
PN00 PN – N.O.Trane pneumatic
actuator, R.A. stat
Digit 7, 8—SecondaryAirValve
00 N/A
Digit 9—Fan
Digit 23—Transformer
0
N/A (provided as standard)
Digit 24—Disconnect Switch
P
02SQ fan (500 nominal cfm)
0
W
None
With
PN05 PN – N.O. PVR, R.A. stat
Q
R
S
T
03SQ fan (1100 nominal cfm)
04SQ fan (1350 nominal cfm)
05SQ fan (1550 nominal cfm)
06SQ fan (1850 nominal cfm)
07SQ fan (2000 nominal cfm)
Notes:
N.C. =
N.O =
Note: VPCF,VPWF –Toggle Disconnect
VPEF – Door Interlocking Power
Disconnect
Normally-closed
Normally-opened
U
DA Stat = Direct-acting pneumatic t-stat
(by others)
RA Stat = Reverse-acting pneumatic
t-stat (by others)
Digit 10, 11—Design Sequence
Digit 25—Power Fuse
J0
Design Sequence (Factory
0
W
None
With
assigned)
PN =
FM =
Pneumatic
Digit 12, 13, 14, 15—Controls
ENON No controls, field-installed DDC
or analog
Digit 26—Electric HeatVoltage
Factory installation of customer-
supplied controller
0
None
A
B
C
D
E
F
208/60/1
208/60/3
240/60/1
277/60/1
480/60/1
480/60/3
347/60/1
575/60/3
380/50/3
120/60/1
PVR =
PneumaticVolume Regulator
ENCL ENON with controls enclosure
PNON No controls, field-installed
pneumatic
DD00 Trane elec actuator only
DD01 DDC – cooling only
DD02 DDC – N.C. on/off water control
DD03 DDC – prop hot water control
DD04 DDC – on/off electric heat
control
Digit 16—Insulation
A
B
C
D
F
1/2" Matte-faced
1" Matte-faced
1/2" Foil-faced
1" Foil-faced
1" Double-wall
3/8" Closed-cell
G
H
J
G
K
DD05 DDC – pulse-width modulation
electric heat control
Digit 17—MotorType
Digit 27, 28, 29—Electric HeatVoltage
D
E
PSC Motor
High-efficiency motor (ECM)
000
050
010
015
None
DD07 DDC – N.O. on/off hot water
control
0.5 kW
1.0 kW
1.5 kW
Digit 18—MotorVoltage
DD11 LonTalk DDC Controller—
1
2
3
4
5
115/60/1
277/60/1
347/60/1
208/60/1
230/50/1
Cooling
only
DD12 LonTalk DDC Controller w/ N.C.
on/off hot water control
260
26.0 kW
DD13 LonTalk DDC Controller w/
proportional hot water control
DD14 LonTalk DDC Control–on/off
electric heat control
Electric HeatVoltage Notes:
Digit 19—Outlet Connection
0.5 to 8.0 kW–½ kW increments
8.0 to 18.0 kW –1 kW increments
18.0 to 46.0 kW–2 kW increments
1
2
Flanged
Slip & Drive
VAV-SVN01E-EN
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Model
Number Description
Fan-Powered Parallel Units (con't)
Digit 30—Electric Heat Stages
0
1
2
3
None
1 Stage
2 Stages Equal
3 Stages Equal
Digit 31—Contactors
0
1
2
3
4
None
24-volt magnetic
24-volt mercury
PE with magnetic
PE with mercury
Digit 32—Airflow Switch
0
W
None
With
8
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Model
Number Description
Fan-Powered Series Units
Digit 1, 2—UnitType
Digit 18—MotorVoltage
DD13 LonTalk DDC Controller w/
proportional hot water control
DD14 LonTalk DDC Controller–on/off
electric heat control
DD15 LonTalk DDC Controller w/
pulse-width modulation electric
heat control
DD17 LonTalk DDC Controller w/ N.O.
on/off hot water control
FM00 FM customer actuator & control
FM01 FMTrane actuator w/ customer-
supplied controller
VMA2 FM Johnson controlsVMA-1420
PWR1 FM Seimens 540-100 w/
GDE131.1P actuator
PWR4 FM Seimens 540-100 w/Trane
actuator
PWR5 FM Seimens 540-100 w/
GDE131.1U actuator
AT01 FM Automated Logic U341V+
AT02 FM Automated Logic U141V+
EI71 Analog fan-powered series
with optional on/off reheat
1
2
3
4
5
115/60/1
277/60/1
347/60/1
208/60/1
230/50/1
VS
VariTrane fan-powered series
Digit 3—Reheat
C
Cooling Only
E
Electric Heat
W
HotWater Heat
Digit 19—Outlet Connection
Digit 4—Development Sequence
Sixth
Digit 5, 6—PrimaryAirValve
1
2
Flanged
Slip & Drive
F
Digit 20—Attenuator
04
05
06
08
10
12
14
16
4" inlet (225 max cfm)
5" inlet (350 max cfm)
6" inlet (500 max cfm)
8" inlet (900 max cfm)
10" inlet (1400 max cfm)
12" inlet (2000 max cfm)
14" inlet (3000 max cfm)
16" inlet (4000 max cfm)
0
W
None
With
Digit 21—Water Coil
0
3
4
5
6
None
1-Row–Discharge installed, LH
1-Row–Discharge installed, RH
2-Row–Discharge installed, LH
2-Row–Discharge installed, RH
Digit 7, 8—SecondaryAirValve
00 N/A
Digit 9—Fan
Digit 22—Electrical Connections
L
R
Left
Right
P
02SQ fan (700 nominal cfm)
PN00 PN – N.O.Trane pneumatic
actuator, R.A. stat
PN51 PN – N.O. PVR, duct pressure
switch, R.A. stat
PN52 PN – N.O. PVR, dual pressure
main, R.A. stat
Q
R
S
T
03SQ fan (1200 nominal cfm)
04SQ fan (1550 nominal cfm)
05SQ fan (1900 nominal cfm)
06SQ fan (2600 nominal cfm)
07SQ fan (3000 nominal cfm)
Water Coil and Electrical Connections
Note:Airflow hitting you in the face.
Digit 23—Transformer
U
0
N/A (provided as standard)
Fan Note: See fan curves for specific
airflows
Digit 24—Disconnect Switch
Notes:
N.C. =
N.O. =
0
W
None
With
Normally-closed
Normally-opened
Digit 10, 11—Design Sequence
Note: VSCF,VSWF –Toggle Disconnect
VSEF – Door Interlocking Power
Disconnect
DA Stat = Direct-acting pneumatic t-stat
(by others)
RA Stat = Reverse-acting pneumatic t-stat
(by others)
J0
Design Sequence
(Factory assigned)
Digit 12, 13, 14, 15—Controls
ENON No controls, field-installed DDC
or analog
Digit 25—Power Fuse
PN =
FM =
Pneumatic
0
W
None
With
Factory installation of customer-
supplied controller
ENCL ENON with control enclosure
PNON No controls, field-installed
pneumatic
DD00 Trane elec actuator only
DD01 DDC – cooling only
DD02 DDC – N.C. on/off water control
DD03 DDC – prop hot water control
DD04 DDC – on/off electric heat
control
DD05 DDC – pulse-width modulation
electric heat control
DD07 DDC N.O. on/off hot water
control
PVR =
PneumaticVolume Regulator
Digit 26—Electric HeatVoltage
0
None
Digit 16—Insulation
A
B
C
D
E
F
208/60/1
208/60/3
240/60/1
277/60/1
480/60/1
480/60/3
347/60/1
575/60/3
380/50/3
120/60/1
A
B
C
D
F
1/2" Matte-faced
1" Matte-faced
1/2" Foil-faced
1" Foil-faced
1" Double-wall
3/8" Closed-cell
G
G
H
J
Digit 17—MotorType
D
E
PSC Motor
High-efficiency motor (ECM)
K
DD11 LonTalk DDC Controller—
Cooling only
DD12 LonTalk DDC Controller w/ N.C.
on/off hot water control
VAV-SVN01E-EN
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Model
Number Description
Fan-Powered Series Units (con't)
Digit 27, 28, 29—Electric Heat Kilowatts
000
050
010
015
None
0.5 kW
1.0 kW
1.5 kW
240
24.0 kW
Digit 30—Electric Heat Stages
0
1
2
3
None
1 Stage
2 Stages Equal
3 Stages Equal
Digit 31—Contactors
0
1
2
3
4
None
24-volt magnetic
24-volt mercury
PE with magnetic
PE with mercury
Digit 32—Airflow Switch
0
W
None
With
10
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Model
Number Description
Fan-Powered Low-Height Parallel Units
Digit 1, 2—UnitType
LP VariTrane fan-powered low-
height parallel
Digit 3—Reheat
Digit 18—MotorVoltage
DD14 LonTalk DDC Controller–on/off
electric heat control
1
2
3
5
115/60/1
277/60/1
347/60/1
230/50/1
DD15 LonTalk DDC Controller w/
pulse-
width modulation
control
electric heat
DD17 LonTalk DDC Controller w/ N.O.
on/off hot water control
FM00 FM customer actuator & control
FM01 FMTrane actuator w/ customer-
supplied controller
VMA2 FM Johnson ControlsVMA-
1420
PWR1 FM Seimens 540-100 w/
GDE131.1P actuator
PWR4 FM Seimens 540-100 w/Trane
actuator
PWR5 FM Seimens 540-100 w/
GDE131.1U actuator
C
Cooling Only
Digit 19—Outlet Connection
E
Electric Heat
W
HotWater Heat
1
2
Flanged
Slip & Drive
Digit 4—Development Sequence
Sixth
Digit 5, 6—PrimaryAirValve
Digit 20—Not Used
N/A
Digit 21—Water Coil
F
0
05
06
08
RT
5" inlet (350 maximum cfm)
6" inlet (500 maximum cfm)
8" inlet (900 maximum cfm)
8" x 14" inlet (1800 maximum cfm)
0
1
2
3
4
5
6
None
1-Row–Plenum inlet installed
2-Row–Plenum inlet installed
1-Row–Discharge installed, LH
1-Row–Discharge installed, RH
2-Row–Discharge installed, LH
2-Row–Discharge installed, RH
Digit 7, 8—Secondary AirValve
00 N/A
Digit 9—Fan
V
W
X
Digit 10, 11—Design Sequence
K0 Sixth (factory assigned)
Digit 12, 13, 14, 15—Controls
AT01 FM Automated Logic U341V+
AT02 FM Automated Logic U141V+
EI05 Analog – fan-powered parallel
with optional on/off reheat
PN00 PN – N.O.Trane pneumatic
actuator, R.A. stat
08SQ 500 nominal cfm
09SQ 900 nominal cfm
10SQ 1800 nominal cfm
Digit 22—Electrical Connections
Left (airflow hitting you in the face)
Digit 23—Transformer
L
0
N/A (provided as standard)
Digit 24—Disconnect Switch
PN05 PN – N.O. PVR, R.A. stat
0
W
None
With
ENON No controls, field-installed DDC/
electric
PNON No controls, field-installed
pneumatic
Notes:
N.C. =
N.O. =
Normally-closed
Normally-opened
Note: LPCF, LPWF –Toggle Disconnect
LPEF – Door Interlocking Power
Disconnect
DA Stat = Direct-acting pneumatic t-stat
(by others)
RA Stat = Reverse-acting pneumatic t-stat
(by others)
PN =
FM =
DD00 Trane elec actuator only
DD01 DDC – cooling only
DD02 DDC – N.C. on/off water valve
control
DD03 DDC – prop hot water valve
control
Digit 25—Power Fuse
0
W
None
With
Pneumatic
Factory installation of customer-
supplied controller
Digit 26—Electric HeatVoltage
DD04 DDC – on/off electric heat control
DD05 DDC – pulse-width modulation
control
DD07 DDC – N.O. on/off water valve
control
DD11 LonTalk DDC Controller—Cooling
only
DD12 LonTalk DDC Controller w/ N.C.
on/off hot water control
DD13 LonTalk DDC Controller w/
proportional hot water control
PVR =
PneumaticVolume Regulator
0
None
A
B
C
D
E
F
208/60/1
208/60/3
240/60/1
277/60/1
480/60/1
480/60/3
347/60/1
575/60/3
380/50/3
Digit 16—Insulation
A
B
C
D
F
1/2" Matte-faced
1" Matte-faced
1/2" Foil-faced
1" Foil-faced
1" Double-wall
3/8" Closed-cell
G
H
J
G
Digit 17—MotorType
D
E
PSC Motor
High-efficiency motor (ECM)
VAV-SVN01E-EN
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Model
Number Description
Fan-Powered Low-Height Parallel Units (con't)
Digit 27, 28, 29—Electric HeatVoltage
Digit 30—Electric Heat Stages
000
005
010
015
020
025
030
035
040
045
050
055
060
065
070
075
080
090
100
110
None
0
1
2
None
0.5 kW
1.0 kW
1.5 kW
2.0 kW
2.5 kW
3.0 kW
3.5 kW
4.0 kW
4.5 kW
5.0 kW
5.5 kW
6.0 kW
6.5 kW
7.0 kW
7.5 kW
8.0 kW
9.0 kW
10.0 kW
11.0 kW
12.0 kW
13.0 kW
14.0 kW
1 Stage
2 Stages Equal
Digit 31—Contactors
0
1
2
3
4
None
24-volt magnetic
24-volt mercury
PE with magnetic
PE with mercury
Digit 32—Airflow Switch
0
W
None
With
120
130
140
12
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Model
Number Description
Fan-Powered Low-Height Series Units
Digit 1, 2—UnitType
Digit 17—MotorType
DD14 LonTalk DDC Controller–on/off
electric heat control
LS
VariTrane low-height series fan-
D
E
PSC Motor
High-efficiency motor (ECM)
powered
DD15 LonTalk DDC Controller w/
pulse-width modulation electric
heat control
DD17 LonTalk DDC Controller w/ N.O.
on/off hot water control
FM00 FM customer actuator & control
FM01 FMTrane actuator w/ customer-
supplied controller
VMA2 FM Johnson controlsVMA-1420
PWR1 FM Seimens 540-100 w/
GDE131.1P actuator
PWR4 FM Seimens 540-100Trane
actuator
PWR5 FM Seimens 540-100 w/
GDE131.1U actuator
AT01 FM Automated Logic U341V+
AT02 FM Automated Logic U141V+
EI71 Analog – Series fan-powered
on/off reheat
PN00 PN – N.O.Trane pneumatic
actuator, R.A. stat
Digit 3—Reheat
Digit 18—MotorVoltage
C
E
W
Cooling Only
1
2
3
5
115/60/1
277/60/1
347/60/1
230/50/1
Electric Heat
HotWater Heat
Digit 4—Development Sequence
Sixth
Digit 5, 6—PrimaryAirValve
Digit 19—Outlet Connection
F
1
2
Flanged
Slip & Drive
05
06
08
RT
5" inlet (350 cfm)
Digit 20—Not Used
N/A
Digit 21—Water Coil
6" inlet (500 cfm)
8" inlet (900 cfm)
0
(8" x 14" inlet (1800 cfm)
Digit 7, 8—SecondaryAirValve
00 N/A
Digit 9—Fan
V
W
X
Digit 10, 11—Design Sequence
K0 Sixth (factory assigned)
Digit 12, 13, 14, 15—Controls
ENON No controls, field-installed DDC/
electric
PNON No controls, field-installed
pneumatic
DD00 Trane elec actuator only
DD01 DDC – cooling only
DD02 DDC – N.C. on/off water valve
control
DD03 DDC – prop hot water valve
control
DD04 DDC – on/off electric heat
control
DD05 DDC – pulse-width modulation
control
0
3
4
5
6
None
1-Row–Discharge installed, LH
1-Row–Discharge installed, RH
2-Row–DIscharge installed, LH
2-Row–Discharge installed, RH
08SQ 500 nominal cfm
09SQ 900 nominal cfm
10SQ 1800 nominal cfm
Digit 22—Electrical Connections
L
R
Left (airflow hitting you in the face)
Right (airflow hitting you in the face)
PN51 PN – N.O. PVR, duct pressure
switch, R.A. stat
PN52 PN – N.O. PVR, dual pressure
main, R.A. stat
Digit 23—Transformer
0
N/A (provided as standard)
Digit 24—Disconnect Switch
Notes:
N.C. =
N.O. =
0
W
None
With
Normally-closed
Normally-opened
Note: LSCF, LSWF –Toggle Disconnect
LSEF – Door Interlocking Power
Disconnect
DA Stat = Direct-acting pneumatic t-stat
(by others)
RA Stat = Reverse-acting pneumatic
t-stat (by others)
PN =
FM =
Digit 25—Power Fuse
Pneumatic
0
W
None
With
Factory installation of customer-
supplied controller
Digit 26—Electric HeatVoltage
PVR =
PneumaticVolume Regulator
0
None
Digit 16—Insulation
A
B
C
D
E
F
208/60/1
208/60/3
240/60/1
277/60/1
480/60/1
480/60/3
347/60/1
575/60/3
380/50/3
DD07 DDC – N.O. on/off water valve
control
A
B
C
D
F
1/2" Matte-faced
1" Matte-faced
1/2" Foil-faced
1" Foil-faced
1" Double-wall
3/8" Closed-cell
DD11 LonTalk DDC Controller—
Cooling only
DD12 LonTalk DDC Controller w/ N.C.
on/off hot water control
DD13 LonTalk DDC Controller w/
proportional hot water control
G
G
H
J
VAV-SVN01E-EN
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Model
Number Description
Fan-Powered Low-Height Series Units (con't)
Digit 27, 28, 29—Electric HeatVoltage
Digit 30—Electric Heat Stages
000
005
010
015
020
025
030
035
040
045
050
055
060
065
070
075
080
090
100
110
None
0
1
2
None
0.5 kW
1.0 kW
1.5 kW
2.0 kW
2.5 kW
3.0 kW
3.5 kW
4.0 kW
4.5 kW
5.0 kW
5.5 kW
6.0 kW
6.5 kW
7.0 kW
1 Stage
2 Stages Equal
Digit 31—Contactors
0
1
2
3
4
None
24-Volt magnetic
24-Volt mercury
PE with magnetic
PE with mercury
Digit 32—Air Flow Switch
0
W
None
With
7.5 kW
8.0 kW
9.0 kW
10.0 kW
11.0 kW
12.0 kW
13.0 kW
14.0 kW
15.0 kW
16.0 kW
17.0 kW
18.0 kW
120
130
140
150
160
170
180
14
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
General
Information
Literature Contents
y Verify that all options have been
included, such as filters, controls,
heating coils, water valves, etc. Also
check that the unit voltages agree with
the building parameters.
y If a discrepancy occurs between what
was ordered and what is received,
contact you localTrane representative
immediately.
This manual describes the installation
ofVariTraneVAV units with recom-
mended wiring, piping, and mounting
of Single-Duct, Dual-Duct, Fan-Pow-
ered, Low-Height terminal units and
diffusers.
y Read the appropriate section in this
manual for installation procedures prior
to actual starting of equipment.
y Manually rotate the fan (if applicable) to
assure that there are no obstructions
within the housing.
Receiving and Handling
Upon receiving the equipment, please
inspect each unit and components for
external or internal damage. Refer to
the bill of lading to insure all equipment
and accessories have been received.
Contact your localTrane sales
representative and notify the trucking
company immediately of any short ship
or damaged equipment.
VariTrane Units are shipped completely
assembled with the exceptions of
optional attenuators for fan-powered
units and accessories.
Upon receiving the equipment,
complete the following:
y Claims for in-transit damage must be
filed immediately with the delivery
carrier.
y For hot water re-heat units, check the
coil fins and make sure that coils are
not damaged.
y Locate the nameplate and refer to the
model and sales order number and
check that the correct units have been
delivered.
y Locate and verify that the correct zone
sensors are with the order.These will be
marked with an orange “Accessories
Enclosed” label. Store in a secure
location until needed. Accessories lost
at the jobsite are NOT covered by
Trane’s warranty.
y Inspect the control enclosures and air
valve casing for dents or punctures.
NOTICE:
Warnings and Cautions appear at appropriate sections throughout this manual.
Read these carefully.
– Indicates a potentially hazardous situation which, if
not avoided, could result in death or serious injury.
WARNING
– Indicates a potentially hazardous situation which, if
not avoided, may result in minor or moderate injury. It may also be used
to alert against unsafe practices.
CAUTION
– Indicates a situation that may result in equipment or
property-damage-only accidents.
CAUTION
VAV-SVN01E-EN
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Information
Single-Duct Units
Figure 1 –Typical Single-Duct Units
Dual-Duct Units
The basic unit consists of a sheet metal
casing with an air valve, which is used
to modulate the air being delivered into
the occupied zone.The unit is designed
to modulate either cooling or heating
air between the temperatures of 40°F
and 140°F. Air enters the air valve
through the round or rectangular inlet
and exits into the sheet metal casing to
be distributed to the zone either
through integral round outlets in the
casing or through rectangular duct
attached to the discharge of the unit.
The basic unit can also be ordered with
factory-mounted electric or hot water
heating coils attached to the discharge.
(See Figure 1.)
Dual-duct units provide two air valves:
one as heating primary air and the
other as cooling primary air. Both
discharge into the common outlet,
which leads to the zone being con-
trolled. (See Figure 2.)
The units are provided with a slip and
drive rectangular duct connection or
can be ordered with integral outlet
plenum.
Sequencing of the hot and cold air
valve is dependent upon job
requirements. One typical control is the
valves working in conjunction with each
other to respond to zone temperature.
VCCF
When the cooling valve becomes fully
closed or reaches a specified minimum,
then the heating valve will begin to
modulate or vice versa.The typical
result is that air flowing to the zone
varies from the maximum down to a
minimum and back up to a maximum
as the load varies and as the controls
would cause one air valve to close and
the other to open.
These re-heat units are used primarily
to reheat air-to-zone temperature when
the load in the occupied space is low.
Primary air is modulated through the
VariTrane air valve by rotating the
damper blade. All air valves have a
round/rectangular inlet for easy fit-up
with incoming ductwork.
Another typical application is when the
unit provides a constant volume to the
zone.When the zone sensor is tied
directly to the heating valve, it will
modulate the heating valve according
to the zone temperature.
VCWF
When the heating valve is fully closed
or there is a call for cooling in the zone,
the cooling valve will be at constant
supply. As the space becomes too cool,
the heating valve will modulate open,
decreasing the cooling valve flow.The
typical result is that the air flowing into
the zone stays at a constant flow
VCEF
whether the unit is heating or cooling.
Figure 2 –Typical Dual-Duct Unit
VDDF
16
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Information
Fan-Powered and Fan-Powered
Low-Height Units
VariTrane fan-powered and low-height
fan-powered units can be either parallel
or series, with or without re-heat. (See
Figure 3.)
VariTrane fan-powered unit fan sizes
02SQ–05SQ and 08SQ–10SQ were
performance tested at .12 in. w.g. and
sizes 06SQ and 07SQ were tested at .15
in. w.g. Units are not designed to
operate unducted and below these
tested static pressures.
The fan on a series unit runs
continuously whenever the main air
handler unit is in operation.There are
various options for starting the fan.The
fan can be started three ways: 1)
remotely, 2) by a duct pressure switch,
or 3) by a combination of both.The
particular fan control method may vary
from unit to unit, depending upon job
needs.
Note: Fan-powered units are available
with rectangular discharge connection
only. The optional heater is mounted on
the discharge of the unit. Hot water coils
are connected to either the plenum inlet
or on the discharge on parallel units, and
to the discharge of series units.
Figure 3 –Typical Fan-Powered Units
Typically, the heater is off while the air
valve modulates primary air and
responds to zone temperature. If zone
temperature decreases to the point
where a decrease in primary air will not
maintain the desired temperature, the
re-heat will be activated to increase the
temperature of the discharge air.
On a parallel unit, theVariTrane air valve
delivers primary cooling air to the unit
outlet.When the space temperature
decreases beyond air valve control, the
fan is turned on as the first stage of
heat.The fan delivers plenum air from
above the occupied space to the unit
outlet, which is mixed with primary air
and delivered to the occupied space.
VSCF
VPCF
Note: Either the fan, the air valve, or both
can deliver airflow into the occupied
space. In order to prevent primary airflow
from exiting through the fan when the
fan is not running on a parallel unit, a
back draft damper is provided. When the
fan is not running, the efficiency of this
system is the same as a standard single-
ductVAV unit.
VSEF
VPEF
Typically, the control systems applied to
parallel units cause the air valve to
close to zero or a minimum flow before
the fan is activated. After the fan is
activated, the optional heat will be
activated upon further reduction in
zone temperature.Therefore, minimal
primary air is mixed with the heated air.
VPWF
VSWF
VAV-SVN01E-EN
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Installation
Dual-Duct
Due to their weight, theVAV terminal
units should be suspended from the
uppermost ceiling, independent of the
false ceiling grid. Suspension devices
are to be supplied by the installer. Units
must be installed level and upright.
Failure to level the unit properly may
prevent proper operation of the
controls and/or terminal unit. Units are
not designed to be installed vertically.
Consequently, this will also void the UL
ratings and any warranty on the unit.
Dual-duct units should be supported by
either hanger straps or by using a
threaded rod in conjunction with the
hanger brackets that are provided on
the unit. See Figure 5.
Figure 5
Dual-Duct Hanger Bracket Locations
Single-Duct
Depending upon the size and weight of
the single-duct unit, it may be capable
of being supported by the ductwork
that is connected to it. No hanger
brackets are provided on these units
since the unit should be supported by
means of a hanger strap.The hanger
strap should be secured directly to the
unit casing as shown in Figure 4.
A
C
AIR
VALVE
COOLING
AIR
VALVE
HEATING
For cooling only single-duct units or
single-duct units with hot water coil, the
unt may be rotated 180° for opposite
side connections.
B
For units with electric heat, the unit
must be ordered from the factory
designating either right- or left-hand
connections.
Figure 4
TOP VIEW
Single-Duct Hanging
Recommendations
A
B
C
Inlet Size
5" thru 10"
1.376" (35 mm)
23.154" (588 mm)
25.154" (639 mm)
25.25" (641 mm)
37.25" (946 mm)
1.376" (35 mm)
12" thru 16"
18
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Installation
Fan-Powered (Standard and Low-
Height)
Figure 6
Fan-powered units should be sup-
ported by either hanger straps or by
using a threaded rod in conjunction
with the hanger brackets that are
provided on the unit. Care should be
exercised to insure that the hanging
straps do not block the side access
panel. See Figures 6–13.
Parallel Hanger Bracket Locations Sizes
C
Water
Coil
Airflow
Plenum Inlet
TOP VIEW
Parallel Cooling & Hot Water
B
Primary
Airflow
Optional Attenuator
Field Installed
Flow Ring
Tubing
F
E
Air
Valve
D
A
Airflow
Discharge Outlet
A
B
C
D
E
F
FAN SIZE
41.154" (1041 mm)
38.95" (989 mm)
26.75" (679 mm) 26.75" (679 mm)
3.25" (83 mm) 20.00" (508 mm)
02SQ
26.75" (679 mm)
3.25" (83 mm)
20.00" (508 mm) 38.95" (989 mm)
03SQ, 04SQ, 05SQ 29.75" (756 mm)
41.154" (1041 mm)
36.75" (933 mm) 26.75" (679 mm) 41.154" (1041 mm) 3.25" (83 mm) 20.00" (508 mm) 38.95" (989 mm)
06SQ, 07SQ
C
Airflow
Plenum Inlet
B
Optional Attenuator
Field Installed
Primary
Airflow
Flow Ring
Tubing
F
E
Air
TOP VIEW
Valve
Parallel Electric Heat
D
A
Heater
Airflow
Discharge Outlet
43.546
(1106 mm)
VAV-SVN01E-EN
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Installation
Figure 7
Series Hanger Bracket Locations
A
B
Flow Ring
Tubing
C
Air
Valve
Optional Attenuator
Field Installed
Airflow
Plenum Inlet
TOP VIEW
Series Cooling & Hot Water
E
D
2.
1.
Fan Inlet w/o
Attenuator
1.
All attenuators are the same length and width.
2.
Sizes 01 and 02 units are smaller than attenuators.
Water
Coil
1.625"
(41 mm)
F
A
B
C
D
41.154" (1041 mm)
E
35.154 (740 mm)
FAN SIZE
02SQ
(Elec. Heat Only)
18.75" (476 mm)
3.25" (83 mm)
20.132" (511 mm)
26.75" (679 mm)
03SQ, 04SQ 20.75" (527 mm)
05SQ 27.25" (692 mm)
26.75" (679 mm) 3.25" (83 mm) 41.154" (1041 mm) 41.154" (1041 mm) 23.875 (606 mm)
41.154" (1041 mm)
26.75" (679 mm) 3.25" (83 mm)
41.154" (1041 mm) 29.875" (759 mm)
06SQ, 07SQ 27.25" (692 mm)
26.75" (679 mm) 3.25" (83 mm) 41.154" (1041 mm) 41.154" (1041 mm) 29.875" (759 mm)
Flow Ring
Tubing
A
B
C
Air
Valve
Optional Attenuator
Field Installed
TOP VIEW
Series Electric Heat
Airflow
Plenum Inlet
D
G
Fan Inlet w/o
Attenuator
Electric
Heater
C
19.00"
B
(483 mm)
F
20
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Installation
Figure 8
Low-Height Parallel 08SQ/09SQ w/ Hot Water or Electric Heat
31.65"
(804 mm)
Airflow
Plenum Inlet
13.00"
(330 mm)
23.90"
(607 mm)
Primary
Airflow
19.86"
(504 mm)
Optional Attenuator
Field Installed
24.30"
(617 mm)
3.35"
(85 mm)
Airflow
Discharge Outlet
TOP VIEW
23.10"
13.80"
4.00"
(587 mm)
(350 mm)
(102 mm)
31.65"
(804 mm)
Airflow
Plenum Inlet
23.90"
(607 mm)
13.00"
(330 mm)
Primary
Airflow
19.86"
(504 mm)
Optional Attenuator
Field Installed
24.30"
(617 mm)
Heater
3.35"
(85 mm)
TOP VIEW
Airflow
Discharge Outlet
23.10"
(587 mm)
3.00"
(76 mm)
13.80"
(350 mm)
4.00"
(102 mm)
VAV-SVN01E-EN
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Installation
Figure 9
Low-Height Parallel10SQ
1.625"
(41 mm)
38.95"
(989 mm)
Primary
Airflow
Flow Ring
Tubing
Plenum
Inlet
Air
Valve
5.625"
(143 mm)
38.75"
(984 mm)
5.625"
(143 mm)
Terminal Box
Optional Heater
Airflow
Discharge Outlet
41.137"
(1045 mm)
TOP VIEW
22
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Installation
Figure 10
Low-Height Series 08SQ/09SQ w/ Hot Water or Electric Heat
31.65"
(804 mm)
Airflow
Plenum Inlet
10.13"
(257 mm)
12.85"
(326 mm)
4.00"
(102 mm)
Primary
Airflow
19.86"
(504 mm)
Optional Attenuator
Field Installed
Air
Valve
3.35"
(85 mm)
34.30"
(871 mm)
31.65"
(804 mm)
3.35"
10.13"
(257 mm)
(85 mm)
Airflow
Plenum Inlet
12.85"
(326 mm)
4.00"
(102 mm)
Water
Coil
Primary
Airflow
TOP VIEW
Optional Attenuator
Field Installed
19.86"
(504 mm)
Air
Valve
Airflow
3.35"
(85 mm)
20.00"
(508 mm)
27.00"
(686 mm)
34.30"
(871 mm)
3.35"
(85 mm)
Optional
Electric Heater
TOP VIEW
Airflow
20.00"
(508 mm)
27.00"
(686 mm)
VAV-SVN01E-EN
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Installation
Figure 11
Low-Height Series 10SQ w/ Hot Water or Electric Heat
19.45"
(494 mm)
19.45"
(494 mm)
10.12"
(257 mm)
31.65"
31.65"
(804 mm)
(804 mm)
Optional Attenuator
Field Installed
Optional Attenuator
Field Installed
Primary
Airflow
19.86"
(504 mm)
19.86"
(504 mm)
Airflow
Plenum Inlet
Airflow
Plenum Inlet
3.35"
(85 mm)
30.30"
(770 mm)
3.35"
(85 mm)
TOP VIEW
Airflow
Discharge Outlet
42.00"
(1067 mm)
3.50"
(89 mm)
3.50"
(89 mm)
19.45"
(494 mm)
19.45"
(494 mm)
10.12"
(257 mm)
31.65"
(804 mm)
31.65"
(804 mm)
Optional Attenuator
Field Installed
Optional Attenuator
Field Installed
Primary
Airflow
19.86"
(504 mm)
19.86"
(504 mm)
Airflow
Plenum Inlet
3.35"
(85 mm)
Airflow
Plenum Inlet
30.30"
(770 mm)
3.35"
(85 mm)
Plenum Area
TOP VIEW
Optional
Heater
1.92"
(49 mm)
Airflow
Discharge Outlet
42.00"
(1067 mm)
3.50"
(89 mm)
3.50"
(89 mm)
24
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Installation
Figure 12
Attenuator Installation—Parallel Units
1. Attach attenuator to unit as shown with provided mounting brackets.
MOUNTING BRACKET
OPTIONAL ATTENUATOR
FIELD INSTALLED
Note: Bottom bracket not shown. Bottom bracket to be installed in same orientation on
bottom of unit.
VAV-SVN01E-EN
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Installation
Figure 13
Attenuator Installation—Series Units
1. Attach attenuator to unit as shown with provided mounting brackets.
MOUNTING BRACKET
OPTIONAL ATTENUATOR
FIELD INSTALLED
Note: Bottom bracket not shown. Bottom bracket to be installed in same
orientation on bottom of unit.
26
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Installation
Figure 14
Attenuator Installation—Low-Height Parallel Units
1. Attach attenuator to unit as shown with provided mounting brackets.
MOUNTING BRACKET
OPTIONAL ATTENUATOR
FIELD INSTALLED
Note: Bottom bracket not shown. Bottom bracket to be installed in
same orientation on bottom of unit.
VAV-SVN01E-EN
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Installation
Figure 15
Attenuator Installation—Low-Height Series Units
1. Attach attenuator to unit as shown with provided mounting brackets.
MOUNTING BRACKET
OPTIONAL ATTENUATOR
FIELD INSTALLED
MOUNTING BRACKET
OPTIONAL ATTENUATOR
FIELD INSTALLED
OPTIONAL ATTENUATOR
FIELD INSTALLED
MOUNTING BRACKET
Note: Bottom bracket not shown. Bottom bracket to be installed in same orientation on bottom of unit.
28
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Installation
Chart 1 – UnitWeights
Single-Duct Units
Unit
Size
VCCF
VCCF w/
DualWall
(lbs/kg)
VCEF
VCEF w/
DualWall
(lbs/kg)
VCWF
1-Row
(lbs/kg)
VCWF
2-Row
(lbs/kg)
VCWF 1-Row
w/ DualWall
(lbs/kg)
VCWF 2-Row
w/ DualWall
(lbs/kg)
(lbs/kg)
(lbs/kg)
4
5
6
8
16/7
16/7
16/7
16/7
19/9
19/9
19/9
20/9
38/17
38/17
38/17
38/17
48/22
48/22
48/22
49/22
21/10
21/10
21/10
21/10
22/10
22/10
22/10
24/11
24/11
24/11
24/11
25/11
25/11
25/11
25/11
28/13
10
12
14
16
24
22/10
27/12
32/15
35/16
52/24
27/12
34/15
41/19
46/21
63/29
46/21
52/24
60/27
69/31
84/38
60/27
68/31
80/36
91/41
106/48
29/13
37/17
44/20
49/22
70/32
32/15
40/18
48/22
54/24
77/35
34/15
43/20
53/24
60/27
81/37
37/17
47/21
57/26
65/29
88/40
Dual-Duct Units
Unit
Size
VDDF
VDDF w/
DualWall
(lbs/kg)
Unit
Size
VDDF
VDDF w/
DualWall
(lbs/kg)
(lbs/kg)
(lbs/kg)
0505
0506
0606
0508
54/24
54/24
54/24
55/25
68/31
68/31
68/31
68/31
1012
1212
0814
1014
59/27
60/27
78/35
79/36
72/33
84/38
102/46
103/47
0608
0510
0808
0610
55/25
56/25
56/25
56/25
69/31
69/31
70/32
70/32
1214
1414
0816
1016
80/36
81/37
79/36
80/36
104/47
105/48
103/47
104/47
0810
1010
0612
0812
57/26
61/28
57/26
58/26
70/32
74/34
70/32
71/32
1216
1416
1616
81/37
82/37
83/38
105/48
105/48
106/48
Parallel Fan-Powered Units
Unit
Size
VPCF VPCF w/
DualWall
VPEF
VPEF w/
DualWall
(lbs/kg)
VPWF
1-Row
(lbs/kg)
VPWF
2-Row
(lbs/kg)
VPWF 1-Row
w/ DualWall
(lbs/kg)
VPWF 2-Row
w/ DualWall
(lbs/kg)
VPxF
Attenuator
(lbs/kg)
(lbs/kg) (lbs/kg)
(lbs/kg)
0502SQ
0602SQ
0603SQ
0802SQ
81/37
80/36
83/38
81/37
115/52
114/52
117/53
115/52
110/550
109/49
112/51
110/50
144/65
143/65
146/66
144/65
92/42
91/41
105/48
92/42
95/43
94/43
108/49
95/43
126/57
125/57
139/63
126/57
129/59
128/58
142/64
129/59
46/21
46/21
48/22
46/21
0803SQ
0804SQ
1002SQ
1003SQ
83/38
84/38
82/37
84/38
117/53
118/54
116/53
118/54
112/51
113/51
111/50
113/51
146/66
147/67
145/66
147/67
105/48
106/48
93/42
108/49
109/49
96/44
139/63
140/64
127/58
140/64
142/64
143/65
130/59
143/65
48/22
48/22
46/21
48/22
106/48
109/49
1004SQ
1005SQ
1006SQ
1007SQ
85/39
98/44
114/52
122/55
119/54
132/60
148/67
156/71
114/52
128/58
144/65
152/69
148/67
162/73
178/81
186/84
107/49
120/54
127/58
135/61
110/50
123/56
130/59
138/63
141/64
154/70
161/73
169/77
144/65
157/71
164/74
172/78
48/22
48/22
54/24
54/24
1203SQ
1204SQ
1205SQ
1206SQ
85/39
86/39
99/45
115/52
119/54
120/54
133/60
149/68
114/52
115/52
129/59
145/66
148/67
149/68
163/74
179/81
107/49
108/49
121/55
128/58
110/50
111/50
124/56
131/59
141/64
142/64
155/70
162/73
144/65
145/66
158/72
165/75
48/22
48/22
48/22
54/24
1207SQ
1404SQ
1405SQ
1406SQ
123/56
87/39
100/45
116/53
157/71
121/55
134/61
150/68
153/69
116/53
130/59
146/66
187/85
150/68
164/74
180/82
136/62
109/49
122/55
129/59
139/63
112/51
125/57
132/60
170/77
143/65
156/71
163/74
173/78
146/66
159/72
166/75
54/24
48/22
48/22
54/24
1407SQ
1606SQ
1607SQ
124/56
117/53
125/57
158/72
151/68
159/72
154/70
147/67
155/70
188/85
181/82
189/86
137/62
130/59
138/63
140/64
133/60
141/64
171/78
164/74
172/78
174/79
167/76
175/79
54/24
54/24
54/24
VAV-SVN01E-EN
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Installation
Chart 1 – UnitWeights (Con't.)
Series Fan-Powered
Unit
VSCF VSCF w/ VSEF VSEF w/ VSWF
VSWF VSWF 1-Row VSWF 2-Row
VSxF
Attenuator
(lbs/kg)
Size
DualWall
(lbs/kg) (lbs/kg)
DualWall
(lbs/kg)
1-Row
2-Row
w/ DualWall
(lbs/kg)
w/ DualWall
(lbs/kg)
(lbs/kg)
(lbs/kg)
(lbs/kg)
0402SQ
0502SQ
0602SQ
0603SQ
0604SQ
78/35
78/35
77/35
76/34
87/39
93/42
93/42
92/42
100/45
111/50
104/47
104/47
103/47
105/48
116/53
119/54
119/54
118/54
129/59
140/64
85/39
85/39
84/38
88/40
99/45
87/39
87/39
86/39
92/42
103/47
100/45
100/45
99/45
112/51
123/56
102/46
102/46
101/46
116/53
127/58
46/21
46/21
46/21
48/22
48/22
0802SQ
0803SQ
0804SQ
1002SQ
1003SQ
79/36
77/35
88/40
81/37
80/36
94/43
101/46
112/51
96/44
105/48
106/48
117/53
107/49
109/49
120/54
130/59
141/64
122/55
133/60
86/39
89/40
100/45
88/40
92/42
88/40
93/42
104/47
90/41
96/44
101/46
113/51
124/56
103/47
116/53
103/47
117/53
128/58
105/48
120/54
46/21
48/22
48/22
46/21
48/22
104/47
1004SQ
1005SQ
1006SQ
1007SQ
1203SQ
91/41
92/42
104/47
117/53
82/37
115/52
116/53
133/60
146/66
106/48
120/54
121/55
135/61
148/67
111/50
144/65
145/66
164/74
177/80
135/61
103/47
104/47
119/54
132/60
94/43
107/49
108/49
124/56
137/62
98/44
127/58
128/58
148/67
161/73
118/54
131/59
132/60
153/69
166/75
122/55
48/22
48/22
54/24
54/24
48/22
1204SQ
1205SQ
1206SQ
1207SQ
1404SQ
92/42
94/43
105/48
118/54
93/42
116/53
118/54
134/61
147/67
117/53
121/55
123/56
136/62
149/68
122/55
145/66
147/67
165/75
178/81
146/66
104/47
106/48
120/54
133/60
105/48
108/49
110/50
125/57
13863
109/49
128/58
130/59
149/68
162/73
129/59
132/60
134/61
154/70
167/76
133/60
48/22
48/22
54/24
54/24
48/22
1405SQ
1406SQ
1407SQ
1606SQ
1607SQ
96/44
106/48
119/54
107/49
120/54
120/54
135/61
148/67
136/62
149/68
125/57
137/62
150/68
138/63
151/68
149/68
166/75
179/81
167/76
180/82
108/49
121/55
134/61
122/55
135/61
112/51
126/57
139/63
127/58
140/64
132/60
150/68
163/74
151/68
164/74
136/62
155/70
168/76
156/71
169/77
48/22
54/24
54/24
54/24
54/24
Low-Height Parallel Units
Unit
LPCF LPCF w/ LPEF LPEF w/
LPWF
1-Row
(lbs/kg)
LPWF
2-Row
(lbs/kg)
LPWF 1-Row LPWF 2-Row
LPxF
Attenuator
(lbs/kg)
Size
DualWall
(lbs/kg) (lbs/kg)
DualWall
(lbs/kg)
w/ DualWall
(lbs/kg)
w/ DualWall
(lbs/kg)
(lbs/kg)
0508SQ
0608SQ
0609SQ
0808SQ
69/31
68/31
73/33
69/31
89/40
88/40
93/42
89/40
84/38
83/38
88/40
84/38
104/47
103/47
108/49
104/47
78/35
77/35
82/37
78/35
81/37
80/36
85/39
81/37
98/44
97/44
102/46
98/44
101/46
100/45
105/48
101/46
10/5
10/5
10/5
10/5
0809SQ
0810SQ
74/34
90/41
14RT09SQ 83/38
94/43
110/50
103/47
117/53
89/40
105/48
98/44
109/49
125/57
118/54
132/60
83/38
99/45
92/42
106/48
86/39
102/46
95/43
103/47
119/54
112/51
126/57
106/48
122/55
115/52
129/59
10/5
10/5
10/5
10/5
14RT10SQ 97/44
112/51
109/49
Low-Height Series Units
Unit
Size
LSCF LSCF w/
DualWall
LSEF
LSEF w/
DualWall
(lbs/kg)
LSWF
1-Row
(lbs/kg)
LSWF
2-Row
(lbs/kg)
LSWF 1-Row
w/ DualWall
(lbs/kg)
LSWF 2-Row
w/ DualWall
(lbs/kg)
LSxF
Attenuator
(lbs/kg)
(lbs/kg) (lbs/kg)
(lbs/kg)
0508SQ
0608SQ
0609SQ
0808SQ
71/32
70/32
80/36
71/32
86/39
85/39
95/43
86/39
86/39
85/39
95/43
86/39
101/45
100/45
110/50
101/46
80/36
79/36
89/40
80/36
82/37
81/37
91/41
82/37
95/43
94/43
104/47
95/43
97/44
96/44
106/48
97/44
10/5
10/5
10/5
10/5
0809SQ
0810SQ
81/37
95/43
14RT09SQ 90/41
96/44
120/54
105/48
130/59
96/44
120/54
105/48
130/59
111/50
145/66
120/54
155/70
90/41
111/50
99/45
92/42
115/52
101/46
125/57
105/48
136/62
114/52
146/66
107/49
140/64
116/53
150/68
10/5
20/9
10/5
20/9
14RT10SQ 105/48
121/55
30
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Installation
Duct Connections
Care should be taken to properly
support the water coil piping
connections while connecting the
adjoining pipe.
Actuator Mounting
AllVariTrane units should be provided
with a minimum of 1.5-duct diameters
of straight duct prior to the inlet of the
unit. It is recommended that at least 48
inches of straight duct be provided
from the discharge of the units prior to
any take-offs or transitions. This is a
requirement for electric heat fan-
powered units used in
Trane offers a factory-mounted actuator
with a 90-second drive time.The
actuator drives 1 degree per second. A
field-installed actuator may be used if
desired.The actuator shaft has a ½-inch
diameter and is designed to travel
clockwise to close the damper and
counter-clockwise to open the damper.
There is an indicator on the end of the
actuator shaft that can be used to
determine the position of the damper.
It is recommended that piping to the
water coil should be done after field-
mounted controls, external insulation,
and ductwork connections have been
completed.
Do not connect water valve or pipe
extensions to the water coil
connections unless supported.
applications with 100%
downward discharge.
Note: In order to maintain the UL rating
forVariTrane electric coils, there must be
four feet of straight unlined ductwork
downstream of the reheat coil prior to
any diffuser takeoffs.
Unit Accessibility
CAUTION
Single-duct and dual-duct units
Equipment Damage
provided with hot water reheat have an
access panel located on the side of the
water coil. All other single-duct and
dual-duct units are provided without
access, as all functioning components
are external to the unit.
Note:When installing or replacing the
actuator tighten the actuator set screw
per the manufacturer’s instructions.
Failure to follow the manufacturer’s
specifications may result in unit
malfunction.
After all connections are made, check
that the entire ductwork system is
airtight. In some high-pressure
Fan-powered terminals are provided
with a sliding side access.
systems, duct sealer may be necessary.
Provide insulation around the entire
inlet collar (all the way to the unit
casing).
Low-height terminal units have a
removable bottom panel.
Clearances
Use caution not to damage the flow
tubes when making ductwork
connections or insulating.
For proper service, it is recommended
that at least 36” of side clearance be
provided to service and access single-
duct and dual-duct terminals units.
Cut “slits” in the insulation for the flow
tubes and secure with duct tape.
Fan-poweredVAV units have a plenum
inlet that must be clear of obstructions.
Allow at least 36” of clearance in front
of the side access and plenum opening.
If the unit is to be installed in a location
with high humidity, external insulation
around the heating coil should be
installed as required.
Low-height fan-powered terminals
require the same plenum clearance
requirement that applies to the
standard fan-powered units. However
the access to the internal components
is located on the bottom of the unit.
Water Coil Connections
Water coil piping connections will be
3/8” or 7/8” OD.
If necessary, you can change the coil
connection from left-handed to right-
handed (and vice-versa) by
disconnecting the coil from the unit
and rotating the coil “like a steering
wheel” 180°.
It is also recommended that 6” of
clearance be provided to the top and
bottom of all the units.
Note:The minimum clearance for
The inlet piping should always be
connected to the bottom connection of
the coil regardless of handedness.
controls and heater controls should be
36” for all models except units with 575-
volt electric heaters, which require 48” of
clearance. NEC and/or local codes
override all clearance requirements.
VAV-SVN01E-EN
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Setup
Chart 2 – Flow Sensor Delta P vs.Airflow Delivery
10
8" x 12"
12" 14" 16"
6
10"
8"
16" x 24"
4
5
1
0.1
0.01
10
100
1,000
10,000
Airflow (CFM)
Chart 3– Fan MotorAmperage
Maximum PSC Fan MotorAmperage (FLA)
Maximum ECM Fan MotorAmperage (FLA)
Fan
HP
VAC
1/8
115
VAC
1.6
277
VAV
0.7
1.6
2.0
2.4
3.8
4.7
2.5
2.5
5.0
3.5
347
VAC
.7
208
Fan
HP
VAC
1/3
1/2
1
115
VAC
4.5
277
VAV
2.4
3.5
5.4
5.1
1.1
Size
Size
Parallel/Series 02SQ
Parallel/Series 03SQ
Parallel/Series 04SQ
Parallel/Series 05SQ
Parallel/Series 06SQ
Parallel/Series 07SQ
Low-height Parallel/Series 08SQ
Low-height Parallel/Series 09SQ
Series Low-height 10SQ
Parallel Low-Height 10SQ
—
—
—
Parallel/Series 03SQ
Parallel/Series 04SQ
Parallel/Series 05SQ
Parallel/Series 06SQ
1/3
1/3
1/2
1/2
1
1/3
1/3
2 x 1/8
2 x 1/8
4.3
5.5
6.7
—
1.4
1.8
2.2
3.3
3.8
1.8
1.8
3.5
3.0
6.5
10.1
9.5
—
1
4.6
6.6
—
—
—
Low-height Parallel/Series 08SQ 1/2
2.0
—
Low-height Parallel/Series 09SQ 1/2
6.7
3.6
4.0
5.5
5.5
11.0
9.4
Low-height Series 10SQ
2 x 1/2
7.5
32
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Setup
(SCR) Motor Speed Control
Adjustment Procedure.
Figure 17 – Internal Potentiometer
Electrically Commutated Motor (ECM)
Trane offers an energy efficient ECM
motor as a motor option. Balancing of
an ECM motor is accomplished
through electronic control adjustments
on the ECM control board (see Figure
15). Potentiometer settings for a
multitude of CFM settings are given in
Charts 4–15. Other potentiometer
settings can be determined either by
interpolating from these tables or by
using the following equation:
In order to make units more convenient
and efficient to balance, an SCR
(silicone control rectifier) is provided as
standard on all fan-powered units.
Max
120 v
The SCR is located on the side of the
fan control box. To adjust the speed of
the motor, the external knob must be
rotated either clockwise or
counterclockwise depending on the
desired speed adjustment.
208 v–
277 v
347 v
CFMsetting = CFMmin +
{(Potentiometer Setting) x [(CFMmax -
CFMmin)/100]}
There is an internal potentiometer
(Figure 14) setting on the SCR controller
that can be accessed by removing the
control box cover. This internal
potentiometer is set at the factory to the
specific motor voltage.
It may be necessary to adjust this in the
field depending on the building’s power
factor.
DO NOT SET THIS
POTENTIOMETER
BELOW THE VOLTAGE
OF THE FAN MOTOR.
There is an LED on the ECM control
board, which will blink one time for
every 100 CFM of motor setting. For
example, the LED on a unit set for 790
CFM will blink 7 times. The LED on a
unit set for 800 CFM will blink 8 times.
NOTE: Do not set this potentiometer
below the voltage of the fan motor.
NOTE:This feature only verifies that the
CFM is set properly. This feature does
not indicate at what speed the motor is
actually running.
WARNING
HazardousVoltage!
Disconnect all electric power, including
remote disconnects before servicing.
Follow proper lockout/tagout proce-
dures to ensure the power cannot be
inadvertently energized. Failure to
disconnect power before servicing
could result in death or serious injury.
The ECM must be “load tested.” In other
words, the fan must be connected to
properly test the ECM.
Figure 18 – ECM Control Board
Figure 16 – SCR
VAV-SVN01E-EN
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Setup
Chart 4 –VPxF 03SQ ECM CFMTable
VPxF 03SQ
Motor Min CFM: 160
Motor Max CFM: 1085
%
Setting
TENS
Switch
UNITS
Switch
%
L/sec
TENS
Setting
UNITS
Switch
CFM
L/sec
CFM
Switch
160
170
179
188
198
76
80
84
89
93
1
2
3
4
5
0
0
0
0
0
1
2
3
4
5
627
637
646
655
665
296
300
305
309
314
51
52
53
54
55
5
5
5
5
5
1
2
3
4
5
207
216
226
235
244
98
102
107
111
6
7
8
9
10
0
0
0
0
1
6
7
8
9
0
674
683
693
702
711
318
323
327
331
336
56
57
58
59
60
5
5
5
5
6
6
7
8
9
0
115
254
263
272
282
291
120
124
129
133
137
11
12
13
14
15
1
1
1
1
1
1
2
3
4
5
721
730
739
749
758
340
345
349
353
358
61
62
63
64
65
6
6
6
6
6
1
2
3
4
5
300
310
319
328
338
142
146
151
155
159
16
17
18
19
20
1
1
1
1
2
6
7
8
9
0
767
777
786
795
805
362
367
371
375
380
66
67
68
69
70
6
6
6
6
7
6
7
8
9
0
347
356
366
375
385
164
168
173
177
181
21
22
23
24
25
2
2
2
2
2
1
2
3
4
5
814
823
833
842
852
384
389
393
397
402
71
72
73
74
75
7
7
7
7
7
1
2
3
4
5
394
403
413
422
431
186
190
195
199
204
26
27
28
29
30
2
2
2
2
3
6
7
8
9
0
861
870
880
889
898
406
411
415
419
424
76
77
78
79
80
7
7
7
7
8
6
7
8
9
0
441
450
459
469
478
208
212
217
221
226
31
32
33
34
35
3
3
3
3
3
1
2
3
4
5
908
917
926
936
945
428
433
437
442
446
81
82
83
84
85
8
8
8
8
8
1
2
3
4
5
487
497
506
515
525
230
234
239
243
248
36
37
38
39
40
3
3
3
3
4
6
7
8
9
0
954
964
973
982
992
450
455
459
464
468
86
87
88
89
90
8
8
8
8
9
6
7
8
9
0
534
543
553
562
571
252
256
261
265
270
41
42
43
44
45
4
4
4
4
4
1
2
3
4
5
1001
1010
1020
1029
1038
472
477
481
486
490
91
92
93
94
95
9
9
9
9
9
1
2
3
4
5
581
590
599
609
618
274
278
283
287
292
46
47
48
49
50
4
4
4
4
5
6
7
8
9
0
1048
1057
1066
1076
1085
494
499
503
508
512
96
97
98
99
100
9
9
9
9
0
6
7
8
9
0
34
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Setup
Chart 5 –VPxF 04SQ ECM CFMTable
VPxF 04SQ
Motor Min CFM: 220
Motor Max CFM: 1510
%
Setting
TENS
Switch
UNITS
Switch
%
Setting
TENS
Switch
UNITS
Switch
CFM
L/sec
CFM
L/sec
220
233
246
259
272
104
110
116
122
128
1
2
3
4
5
0
0
0
0
0
1
2
3
4
5
872
885
898
911
924
411
417
424
430
436
51
52
53
54
55
5
5
5
5
5
1
2
3
4
5
285
298
311
324
337
135
141
147
153
159
6
7
8
9
10
0
0
0
0
1
6
7
8
9
0
937
950
963
976
989
442
448
454
461
467
56
57
58
59
60
5
5
5
5
6
6
7
8
9
0
350
363
376
389
402
165
171
178
184
190
11
12
13
14
15
1
1
1
1
1
1
2
3
4
5
1002
1015
1028
1041
1054
473
479
485
491
497
61
62
63
64
65
6
6
6
6
6
1
2
3
4
5
415
429
442
455
468
196
202
208
215
221
16
17
18
19
20
1
1
1
1
2
6
7
8
9
0
1067
1080
1093
1106
1119
504
510
516
522
528
66
67
68
69
7 0
6
6
6
6
7
6
7
8
9
0
481
494
507
520
533
227
233
239
245
251
21
22
23
24
25
2
2
2
2
2
1
2
3
4
5
1132
1145
1158
1171
1184
534
540
547
553
559
71
72
73
74
75
7
7
7
7
7
1
2
3
4
5
546
559
572
585
598
258
264
270
276
282
26
27
28
29
30
2
2
2
2
3
6
7
8
9
0
1197
1210
1223
1236
1249
565
571
577
584
590
76
77
78
79
80
7
7
7
7
8
6
7
8
9
0
611
624
637
650
663
288
294
301
307
313
31
32
33
34
35
3
3
3
3
3
1
2
3
4
5
1262
1275
1288
1302
1315
596
602
608
614
620
81
82
83
84
85
8
8
8
8
8
1
2
3
4
5
676
689
702
715
728
319
325
331
338
344
36
37
38
39
40
3
3
3
3
4
6
7
8
9
0
1328
1341
1354
1367
1380
627
633
639
645
651
86
87
88
89
90
8
8
8
8
9
6
7
8
9
0
741
754
767
780
793
350
356
362
368
374
41
42
43
44
45
4
4
4
4
4
1
2
3
4
5
1393
1406
1419
1432
1445
657
663
670
676
682
91
92
93
94
95
9
9
9
9
9
1
2
3
4
5
806
819
832
845
859
381
387
393
399
405
46
47
48
49
50
4
4
4
4
5
6
7
8
9
0
1458
1471
1484
1497
1510
688
694
700
706
713
96
97
98
99
100
9
9
9
9
0
6
7
8
9
0
VAV-SVN01E-EN
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Setup
Chart 6 –VPxF 05SQ ECM CFMTable
VPxF 05SQ
Motor Min CFM: 280
Motor Max CFM: 1850
%
L/sec
TENS
Switch
UNITS
Switch
%
Setting
TENS
Switch
UNITS
Switch
CFM
Setting
CFM
L/Sec
280
296
312
327
343
132
140
147
155
162
1
2
3
4
5
0
0
0
0
0
1
2
3
4
5
1073
1089
1105
1120
1136
506
514
521
529
536
51
52
53
54
55
5
5
5
5
5
1
2
3
4
5
359
375
391
407
423
170
177
184
192
199
6
7
8
9
10
0
0
0
0
1
6
7
8
9
0
1152
1168
1184
1200
1216
544
551
559
566
574
56
57
58
59
60
5
5
5
5
6
6
7
8
9
0
438
454
470
486
502
207
214
222
229
237
11
12
13
14
15
1
1
1
1
1
1
2
3
4
5
1231
1247
1263
1279
1295
581
589
596
604
611
61
62
63
64
65
6
6
6
6
6
1
2
3
4
5
518
534
549
565
581
244
252
259
267
274
16
17
18
19
20
1
1
1
1
2
6
7
8
9
0
1311
1327
1342
1358
1374
619
626
634
641
649
66
67
68
69
70
6
6
6
6
7
6
7
8
9
0
597
613
629
645
661
282
289
297
304
312
21
22
23
24
25
2
2
2
2
2
1
2
3
4
5
1390
1406
1422
1438
1454
656
664
671
678
686
71
72
73
74
75
7
7
7
7
7
1
2
3
4
5
676
692
708
724
740
319
327
334
342
349
26
27
28
29
30
2
2
2
2
3
6
7
8
9
0
1469
1485
1501
1517
1533
693
701
708
716
723
76
77
78
79
80
7
7
7
7
8
6
7
8
9
0
756
772
787
803
819
357
364
372
379
387
31
32
33
34
35
3
3
3
3
3
1
2
3
4
5
1549
1565
1580
1596
1612
731
738
746
753
761
81
82
83
84
85
8
8
8
8
8
1
2
3
4
5
835
851
867
883
898
394
402
409
417
424
36
37
38
39
40
3
3
3
3
4
6
7
8
9
0
1628
1644
1660
1676
1691
768
776
783
791
798
86
87
88
89
90
8
8
8
8
9
6
7
8
9
0
914
930
946
962
978
431
439
446
454
461
41
42
43
44
45
4
4
4
4
4
1
2
3
4
5
1707
1723
1739
1755
1771
806
813
821
828
836
91
92
93
94
95
9
9
9
9
9
1
2
3
4
5
994
469
476
484
491
499
46
47
48
49
50
4
4
4
4
5
6
7
8
9
0
1787
1802
1818
1834
1850
843
851
858
866
873
96
97
98
99
100
9
9
9
9
0
6
7
8
9
0
1009
1025
1041
1057
36
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Setup
Chart 7 –VPxF 06SQ ECM CFMTable
VPxF 06SQ
Motor Min CFM: 530
Motor Max CFM: 2100
%
L/sec
TENS
Setting
UNITS
Switch
%
Setting
TENS
Switch
`UNITS
Switch
CFM
Switch
CFM
L/sec
530
546
562
577
593
250
258
265
273
280
1
2
3
4
5
0
0
0
0
0
1
2
3
4
5
1323
1339
1355
1370
1386
624
632
639
647
654
51
52
53
54
55
5
5
5
5
5
1
2
3
4
5
609
625
641
657
673
287
295
302
310
317
6
7
8
9
10
0
0
0
0
1
6
7
8
9
0
1402
1418
1434
1450
1466
662
669
677
684
692
56
57
58
59
60
5
5
5
5
6
6
7
8
9
0
688
704
720
736
752
325
332
340
347
355
11
12
13
14
15
1
1
1
1
1
1
2
3
4
5
1481
1497
1513
1529
1545
699
707
714
722
729
61
62
63
64
65
6
6
6
6
6
1
2
3
4
5
768
784
799
815
831
362
370
377
385
392
16
17
18
19
20
1
1
1
1
2
6
7
8
9
0
1561
1577
1592
1608
1624
737
744
752
759
767
66
67
68
69
70
6
6
6
6
7
6
7
8
9
0
847
863
879
895
911
400
407
415
422
430
21
22
23
24
25
2
2
2
2
2
1
2
3
4
5
1640
1656
1672
1688
1704
774
782
789
796
804
71
72
73
74
75
7
7
7
7
7
1
2
3
4
5
926
942
958
974
990
437
445
452
460
467
26
27
28
29
30
2
2
2
2
3
6
7
8
9
0
1719
1735
1751
1767
1783
811
819
826
834
841
76
77
78
79
80
7
7
7
7
8
6
7
8
9
0
1006
1022
1037
1053
1069
475
482
490
497
505
31
32
33
34
35
3
3
3
3
3
1
2
3
4
5
1799
1815
1830
1846
1862
849
856
864
871
879
81
82
83
84
85
8
8
8
8
8
1
2
3
4
5
1085
1101
1117
1133
1148
512
520
527
535
542
36
37
3 8
39
40
3
3
3
3
4
6
7
8
9
0
1878
1894
1910
1926
1941
886
894
901
909
916
86
87
88
89
90
8
8
8
8
9
6
7
8
9
0
1164
1180
1196
1212
1228
549
557
564
572
579
41
42
43
44
45
4
4
4
4
4
1
2
3
4
5
1957
1973
1989
2005
2021
924
931
939
946
954
91
92
93
94
95
9
9
9
9
9
1
2
3
4
5
1244
1259
1275
1291
1307
587
594
602
609
617
46
47
48
49
50
4
4
4
4
5
6
7
8
9
0
2037
2052
2068
2084
2100
961
969
976
984
991
96
97
98
99
100
9
9
9
9
0
6
7
8
9
0
VAV-SVN01E-EN
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Setup
Chart 8 –VSxF 03SQ ECM CFMTable
VSxF 03SQ
Motor Min CFM: 200
Motor Max CFM: 1100
%
Setting
TENS
Switch
UNITS
Switch
%
L/sec
TENS
Setting
UNITS
Switch
CFM
L/sec
CFN
Switch
200
209
218
227
236
94
99
103
107
112
1
2
3
4
5
0
0
0
0
0
1
2
3
4
5
655
664
673
682
691
309
313
318
322
326
51
52
53
54
55
5
5
5
5
5
1
2
3
4
5
246
255
264
273
282
116
120
124
129
133
6
7
8
9
10
0
0
0
0
1
6
7
8
9
0
700
709
718
727
736
330
335
339
343
348
56
57
58
59
60
5
5
5
5
6
6
7
8
9
0
291
300
309
318
327
137
142
146
150
154
11
12
13
14
15
1
1
1
1
1
1
2
3
4
5
745
755
764
773
782
352
356
360
365
369
61
62
63
64
65
6
6
6
6
6
1
2
3
4
5
336
346
355
364
373
159
163
167
172
176
16
17
18
19
20
1
1
1
1
2
6
7
8
9
0
791
800
809
818
827
373
378
382
386
390
66
67
68
69
70
6
6
6
6
7
6
7
8
9
0
382
391
400
409
418
180
185
189
193
197
21
22
23
24
25
2
2
2
2
2
1
2
3
4
5
836
845
855
864
873
395
399
403
408
412
71
72
73
74
75
7
7
7
7
7
1
2
3
4
5
427
436
446
455
464
202
206
210
215
219
26
27
28
29
30
2
2
2
2
3
6
7
8
9
0
882
891
900
909
918
416
420
425
429
433
76
77
78
79
80
7
7
7
7
8
6
7
8
9
0
473
482
491
500
509
223
227
232
236
240
31
32
33
34
35
3
3
3
3
3
1
2
3
4
5
927
936
945
955
964
438
442
446
451
455
81
82
83
84
85
8
8
8
8
8
1
2
3
4
5
518
527
536
546
555
245
249
253
257
262
36
37
38
39
40
3
3
3
3
4
6
7
8
9
0
973
982
991
1000
1009
459
463
468
472
476
86
87
88
89
90
8
8
8
8
9
6
7
8
9
0
564
573
582
591
600
266
270
275
279
283
41
42
43
44
45
4
4
4
4
4
1
2
3
4
5
1018
1027
1036
1045
1055
481
485
489
493
498
91
92
93
94
95
9
9
9
9
9
1
2
3
4
5
609
618
627
636
646
287
292
296
300
305
46
47
48
49
50
4
4
4
4
5
6
7
8
9
0
1064
1073
1082
1091
110 0
502
506
511
515
519
96
97
98
99
100
9
9
9
9
0
6
7
8
9
0
38
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Setup
Chart 9–VSxF 04SQ ECM CFMTable
VSxF 04SQ
Motor Min CFM: 275
Motor Max CFM: 1500
%
L/sec
TENS
Setting
UNITS
Switch
%
Setting
TENS
Switch
UNITS
Switch
CFM
Switch
CFM
L/sec
275
288
300
312
325
130
136
142
147
153
1
2
3
4
5
0
0
0
0
0
1
2
3
4
5
894
906
919
931
943
422
428
434
439
445
51
52
53
54
55
5
5
5
5
5
1
2
3
4
5
337
350
362
374
387
159
165
171
177
183
6
7
8
9
10
0
0
0
0
1
6
7
8
9
0
956
968
980
993
1005
451
457
463
469
474
56
57
58
59
60
5
5
5
5
6
6
7
8
9
0
399
411
424
436
449
188
194
200
206
212
11
12
13
14
15
1
1
1
1
1
1
2
3
4
5
1018
1030
1042
1055
1067
480
486
492
498
504
61
62
63
64
65
6
6
6
6
6
1
2
3
4
5
461
473
486
498
510
218
223
229
235
241
16
17
18
19
20
1
1
1
1
2
6
7
8
9
0
1079
1092
1104
1117
1129
509
515
521
527
533
66
67
68
69
70
6
6
6
6
7
6
7
8
9
0
523
535
548
560
572
247
253
258
264
270
21
22
23
24
25
2
2
2
2
2
1
2
3
4
5
1141
1154
1166
1178
1191
539
544
550
556
562
71
72
73
74
75
7
7
7
7
7
1
2
3
4
5
585
597
609
622
634
276
282
288
293
299
26
27
28
29
30
2
2
2
2
3
6
7
8
9
0
1203
1215
1228
1240
1253
568
574
579
585
591
76
77
78
79
80
7
7
7
7
8
6
7
8
9
0
646
659
671
684
696
305
311
317
323
328
31
32
33
34
35
3
3
3
3
3
1
2
3
4
5
1265
1277
1290
1302
1314
597
603
609
615
620
81
82
83
84
85
8
8
8
8
8
1
2
3
4
5
708
721
733
745
758
334
340
346
352
358
36
37
38
39
40
3
3
3
3
4
6
7
8
9
0
1327
1339
1352
1364
1376
626
632
638
644
650
86
87
88
89
90
8
8
8
8
9
6
7
8
9
0
770
783
795
807
820
363
369
375
381
387
41
42
43
44
45
4
4
4
4
4
1
2
3
4
5
1389
1401
1413
1426
1438
655
661
667
673
679
91
92
93
94
95
9
9
9
9
9
1
2
3
4
5
832
844
857
869
882
393
399
404
410
416
46
47
48
49
50
4
4
4
4
5
6
7
8
9
0
1451
1463
1475
1488
1500
685
690
696
702
708
96
97
98
99
100
9
9
9
9
0
6
7
8
9
0
VAV-SVN01E-EN
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Setup
Chart 10–VSxF 05SQ ECM CFMTable
VSxF 05SQ
Motor Min CFM: 350
Motor Max CFM: 2050
%
Setting
TENS
Switch
UNITS
Switch
%
Setting
TENS
Switch
UNITS
Switch
CFM
L/sec
CFM
L/sec
350
367
385
402
419
165
173
181
190
198
1
2
3
4
5
0
0
0
0
0
1
2
3
4
5
1209
1226
1243
1260
1277
570
579
587
595
603
51
52
53
54
55
5
5
5
5
5
1
2
3
4
5
436
453
470
488
505
206
214
222
230
238
6
7
8
9
10
0
0
0
0
1
6
7
8
9
0
1295
1312
1329
1346
1363
611
619
627
635
643
56
57
58
59
60
5
5
5
5
6
6
7
8
9
0
522
539
556
573
591
246
254
263
271
279
11
12
13
14
15
1
1
1
1
1
1
2
3
4
5
1380
1398
1415
1432
1449
651
660
668
676
684
61
62
63
64
65
6
6
6
6
6
1
2
3
4
5
608
625
642
659
676
287
295
303
311
319
16
17
18
19
20
1
1
1
1
2
6
7
8
9
0
1466
1483
1501
1518
1535
692
700
708
716
724
66
67
68
69
70
6
6
6
6
7
6
7
8
9
0
694
711
728
745
762
327
335
344
352
360
21
22
23
24
25
2
2
2
2
2
1
2
3
4
5
1552
1569
1586
1604
1621
732
741
749
757
765
71
72
73
74
75
7
7
7
7
7
1
2
3
4
5
779
797
814
831
848
368
376
384
392
400
26
27
28
29
30
2
2
2
2
3
6
7
8
9
0
1638
1655
1672
1689
1707
773
781
789
797
805
76
77
78
79
80
7
7
7
7
8
6
7
8
9
0
865
882
900
917
934
408
416
425
433
441
31
32
33
34
35
3
3
3
3
3
1
2
3
4
5
1724
1741
1758
1775
1792
814
822
830
838
846
81
82
83
84
85
8
8
8
8
8
1
2
3
4
5
951
968
985
1003
1020
449
457
465
473
481
36
37
38
39
40
3
3
3
3
4
6
7
8
9
0
1810
1827
1844
1861
1878
854
862
870
878
886
86
87
88
89
90
8
8
8
8
9
6
7
8
9
0
1037
1054
1071
1088
1106
489
498
506
514
522
41
42
43
44
45
4
4
4
4
4
1
2
3
4
5
1895
1913
1930
1947
1964
895
903
911
919
927
91
92
93
94
95
9
9
9
9
9
1
2
3
4
5
1123
1140
1157
1174
1192
530
538
546
554
562
46
47
48
49
50
4
4
4
4
5
6
7
8
9
0
1981
1998
2016
2033
2050
935
943
951
959
967
96
97
98
99
100
9
9
9
9
0
6
7
8
9
0
40
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Setup
Chart 11–VSxF 06SQ ECM CFMTable
VSxF 06SQ
Motor Min CFM: 700
Motor Max CFM: 2500
%
L/sec
TENS
Setting
UNITS
Switch
%
L/sec
TENS
Setting
UNITS
Switch
CFM
Switch
CFM
Switch
700
718
737
755
773
330
339
348
356
365
1
2
3
4
5
0
0
0
0
0
1
2
3
4
5
1609
1627
1646
1664
1682
759
768
777
785
794
51
52
53
54
55
5
5
5
5
5
1
2
3
4
5
791
809
827
846
864
373
382
391
399
408
6
7
8
9
10
0
0
0
0
1
6
7
8
9
0
1700
1718
1736
1755
1773
802
811
820
828
837
56
57
58
59
60
5
5
5
5
6
6
7
8
9
0
882
900
918
937
955
416
425
433
442
451
11
12
13
14
15
1
1
1
1
1
1
2
3
4
5
1791
1809
1827
1846
1864
845
854
862
871
880
61
62
63
64
65
6
6
6
6
6
1
2
3
4
5
973
991
1009
1027
1046
459
468
476
485
493
16
17
18
19
20
1
1
1
1
2
6
7
8
9
0
1882
1900
1918
1936
1955
888
897
905
914
922
66
67
68
69
70
6
6
6
6
7
6
7
8
9
0
1064
1082
110 0
1118
1137
502
511
519
528
536
21
22
2 3
2 4
25
2
2
2
2
2
1
2
3
4
5
1973
1991
2009
2027
2046
931
940
948
957
965
71
72
73
74
75
7
7
7
7
7
1
2
3
4
5
1155
1173
1191
1209
1227
545
554
562
571
579
26
27
28
29
30
2
2
2
2
3
6
7
8
9
0
2064
2082
2100
2118
2136
974
983
991
1000
1008
76
77
78
79
80
7
7
7
7
8
6
7
8
9
0
1246
1264
1282
1300
1318
588
596
605
614
622
31
32
33
34
35
3
3
3
3
3
1
2
3
4
5
2155
2173
2191
2209
2227
1017
1025
1034
1043
1051
81
82
83
84
85
8
8
8
8
8
1
2
3
4
5
1336
1355
1373
1391
1409
631
639
648
656
665
36
37
38
39
40
3
3
3
3
4
6
7
8
9
0
2245
2264
2282
2300
2318
1060
1068
1077
1085
1094
86
87
88
89
90
8
8
8
8
9
6
7
8
9
0
1427
1446
1464
1482
1500
674
682
691
699
708
41
42
43
44
45
4
4
4
4
4
1
2
3
4
5
2336
2355
2373
2391
2409
1103
1111
1120
1128
1137
91
92
93
94
95
9
9
9
9
9
1
2
3
4
5
1518
1536
1555
1573
1591
717
725
734
742
751
46
47
48
49
50
4
4
4
4
5
6
7
8
9
0
2427
2445
2464
2482
2500
1146
1154
1163
1171
1180
96
97
98
99
100
9
9
9
9
0
6
7
8
9
0
VAV-SVN01E-EN
41
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Setup
Chart 12– LPxF 08SQ ECM CFMTable
LPxF 08SQ
Motor Min CFM: 100
Motor Max CFM: 460
%
TENS
UNITS
Switch
%
Setting
TENS
Switch
UNITS
Switch
CFM
L/sec % Setting Switch
CFM
L/sec
100
103
107
111
47
49
50
52
54
1
2
3
4
5
0
0
0
0
0
1
2
3
4
5
282
285
289
293
296
133
135
136
138
140
51
52
53
54
55
5
5
5
5
5
1
2
3
4
5
114
118
121
125
129
132
56
57
59
61
62
6
7
8
9
10
0
0
0
0
1
6
7
8
9
0
300
303
307
311
314
142
143
145
147
148
56
57
58
59
60
5
5
5
5
6
6
7
8
9
0
136
140
143
147
151
64
66
68
69
71
11
12
13
14
15
1
1
1
1
1
1
2
3
4
5
318
322
325
329
333
150
152
154
155
157
61
62
63
64
65
6
6
6
6
6
1
2
3
4
5
154
158
162
165
169
73
75
76
78
80
16
17
18
19
20
1
1
1
1
2
6
7
8
9
0
336
340
344
347
351
159
160
162
164
166
66
67
68
69
70
6
6
6
6
7
6
7
8
9
0
172
176
180
183
187
81
83
85
87
88
21
22
23
24
25
2
2
2
2
2
1
2
3
4
5
354
358
362
365
369
167
169
171
172
174
71
72
73
74
75
7
7
7
7
7
1
2
3
4
5
191
194
198
202
205
90
92
93
95
97
26
27
28
29
30
2
2
2
2
3
6
7
8
9
0
373
376
380
384
387
176
178
179
181
183
76
77
78
79
80
7
7
7
7
8
6
7
8
9
0
209
212
216
220
223
99
31
32
33
34
35
3
3
3
3
3
1
2
3
4
5
391
394
398
402
405
184
186
188
190
191
81
82
83
84
85
8
8
8
8
8
1
2
3
4
5
100
102
104
105
227
231
234
238
242
107
109
111
112
114
36
37
38
39
40
3
3
3
3
4
6
7
8
9
0
409
413
416
420
424
193
195
196
198
200
86
87
88
89
90
8
8
8
8
9
6
7
8
9
0
245
249
253
256
260
116
117
119
121
123
41
42
43
44
45
4
4
4
4
4
1
2
3
4
5
427
431
435
438
442
202
203
205
207
209
91
92
93
94
95
9
9
9
9
9
1
2
3
4
5
263
267
271
274
278
124
126
128
129
131
46
47
48
49
50
4
4
4
4
5
6
7
8
9
0
445
449
453
456
460
210
212
214
215
217
96
97
98
99
100
9
9
9
9
0
6
7
8
9
0
42
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Setup
Chart 13– LPxF 09SQ ECM CFMTable
LPxF 09SQ
Motor Min CFM: 250
Motor Max CFM: 1025
%
L/sec
TENS
Setting
UNITS
Switch
%
Setting
TENS
Switch
UNITS
Switch
CFM
Switch
CFM
L/sec
250
258
265
273
281
118
122
125
129
133
1
2
3
4
5
0
0
0
0
0
1
2
3
4
5
641
649
657
665
673
303
306
310
314
317
51
52
53
54
55
5
5
5
5
5
1
2
3
4
5
289
297
305
312
320
136
140
144
147
151
6
7
8
9
10
0
0
0
0
1
6
7
8
9
0
680
688
696
704
712
321
325
329
332
336
56
57
58
59
60
5
5
5
5
6
6
7
8
9
0
328
336
344
352
359
155
159
162
166
170
11
12
13
14
15
1
1
1
1
1
1
2
3
4
5
720
727
735
743
751
340
343
347
351
354
61
62
63
64
65
6
6
6
6
6
1
2
3
4
5
367
375
383
391
399
173
177
181
184
188
16
17
18
19
20
1
1
1
1
2
6
7
8
9
0
759
767
774
782
790
358
362
365
369
373
66
67
68
69
70
6
6
6
6
7
6
7
8
9
0
406
414
422
430
438
192
196
199
203
207
21
22
23
24
25
2
2
2
2
2
1
2
3
4
5
798
806
814
821
829
377
380
384
388
391
71
72
73
74
75
7
7
7
7
7
1
2
3
4
5
446
453
461
469
477
210
214
218
221
225
26
27
28
29
30
2
2
2
2
3
6
7
8
9
0
837
845
853
861
868
395
399
402
406
410
76
77
78
79
80
7
7
7
7
8
6
7
8
9
0
485
493
500
508
516
229
232
236
240
244
31
32
33
34
35
3
3
3
3
3
1
2
3
4
5
876
884
892
900
908
414
417
421
425
428
81
82
83
84
85
8
8
8
8
8
1
2
3
4
5
524
532
540
547
555
247
251
255
258
262
36
37
38
39
40
3
3
3
3
4
6
7
8
9
0
915
923
931
939
947
432
436
439
443
447
86
87
88
89
90
8
8
8
8
9
6
7
8
9
0
563
571
579
587
594
266
269
273
277
281
41
42
43
44
45
4
4
4
4
4
1
2
3
4
5
955
962
970
978
986
450
454
458
462
465
91
92
93
94
95
9
9
9
9
9
1
2
3
4
5
602
610
618
626
634
284
288
292
295
299
46
47
48
49
50
4
4
4
4
5
6
7
8
9
0
994
1002
1009
1017
1025
469
473
476
480
484
96
97
98
99
100
9
9
9
9
0
6
7
8
9
0
VAV-SVN01E-EN
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Setup
Chart 14– LSxF 08SQ ECM CFMTable
LSxF 08SQ
Motor Min CFM: 100
Motor Max CFM: 460
%
Setting
TENS
Switch
UNITS
Switch
%
TENS
Switch
UNITS
Switch
CFM
L/sec
CFM
L/sec
Settings
100
103
107
111
47
49
50
52
54
1
2
3
4
5
0
0
0
0
0
1
2
3
4
5
282
285
289
293
296
133
135
136
138
140
51
52
53
54
55
5
5
5
5
5
1
2
3
4
5
114
118
121
125
129
132
56
57
59
61
62
6
7
8
9
10
0
0
0
0
1
6
7
8
9
0
300
303
307
311
314
142
143
145
147
148
56
57
58
59
60
5
5
5
5
6
6
7
8
9
0
136
140
143
147
151
64
66
68
69
71
11
12
13
14
15
1
1
1
1
1
1
2
3
4
5
318
322
325
329
333
150
152
154
155
157
61
62
63
64
65
6
6
6
6
6
1
2
3
4
5
154
158
162
165
169
73
75
76
78
80
16
17
18
19
20
1
1
1
1
2
6
7
8
9
0
336
340
344
347
351
159
160
162
164
166
66
67
68
69
70
6
6
6
6
7
6
7
8
9
0
172
176
180
183
187
81
83
85
87
88
21
22
23
24
25
2
2
2
2
2
1
2
3
4
5
354
358
362
365
369
167
169
171
172
174
71
72
73
74
75
7
7
7
7
7
1
2
3
4
5
191
194
198
202
205
90
92
93
95
97
26
27
28
29
30
2
2
2
2
3
6
7
8
9
0
373
376
380
384
387
176
178
179
181
183
76
77
78
79
80
7
7
7
7
8
6
7
8
9
0
209
212
216
220
223
99
31
32
33
34
35
3
3
3
3
3
1
2
3
4
5
391
394
398
402
405
184
186
188
190
191
81
82
83
84
85
8
8
8
8
8
1
2
3
4
5
100
102
104
105
227
231
234
238
242
107
109
111
112
114
36
37
38
39
40
3
3
3
3
4
6
7
8
9
0
409
413
416
420
424
193
195
196
198
200
86
87
88
89
90
8
8
8
8
9
6
7
8
9
0
245
249
253
256
260
116
117
119
121
123
41
42
43
44
45
4
4
4
4
4
1
2
3
4
5
427
431
435
438
442
202
203
205
207
209
91
92
93
94
95
9
9
9
9
9
1
2
3
4
5
263
267
271
274
278
124
126
128
129
131
46
47
48
49
50
4
4
4
4
5
6
7
8
9
0
445
449
453
456
460
210
212
214
215
217
96
97
98
99
100
9
9
9
9
0
6
7
8
9
0
44
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Setup
Chart 15– LSxF 09SQ ECM CFMTable
LSxF 09SQ
Motor Min CFM: 240
Motor Max CFM: 950
%
L/sec
TENS
Setting
UNITS
Switch
%
Setting
TENS
Switch
UNITS
Switch
CFM
Switch
CFM
L/sec
240
247
255
262
269
113
117
120
123
127
1
2
3
4
5
0
0
0
0
0
1
2
3
4
5
599
606
613
620
627
283
286
289
293
296
51
52
53
54
55
5
5
5
5
5
1
2
3
4
5
276
283
290
298
305
130
134
137
140
144
6
7
8
9
10
0
0
0
0
1
6
7
8
9
0
635
642
649
656
663
299
303
306
310
313
56
57
58
59
60
5
5
5
5
6
6
7
8
9
0
312
319
326
333
341
147
151
154
157
161
11
12
13
14
15
1
1
1
1
1
1
2
3
4
5
670
678
685
692
699
316
320
323
327
330
61
62
63
64
65
6
6
6
6
6
1
2
3
4
5
348
355
362
369
376
164
167
171
174
178
16
17
18
19
20
1
1
1
1
2
6
7
8
9
0
706
713
721
728
735
333
337
340
343
347
66
67
68
69
70
6
6
6
6
7
6
7
8
9
0
384
391
398
405
412
181
184
188
191
195
21
22
23
24
25
2
2
2
2
2
1
2
3
4
5
742
749
756
764
771
350
354
357
360
364
71
72
73
74
75
7
7
7
7
7
1
2
3
4
5
419
427
434
441
448
198
201
205
208
211
26
27
28
29
30
2
2
2
2
3
6
7
8
9
0
778
785
792
799
807
367
371
374
377
381
76
77
78
79
80
7
7
7
7
8
6
7
8
9
0
455
462
470
477
484
215
218
222
225
228
31
32
33
34
35
3
3
3
3
3
1
2
3
4
5
814
821
828
835
842
384
387
391
394
398
81
82
83
84
85
8
8
8
8
8
1
2
3
4
5
491
498
505
513
520
232
235
239
242
245
36
37
38
39
40
3
3
3
3
4
6
7
8
9
0
850
857
864
871
878
401
404
408
411
415
86
87
88
89
90
8
8
8
8
9
6
7
8
9
0
527
534
541
548
556
249
252
255
259
262
41
42
43
44
45
4
4
4
4
4
1
2
3
4
5
885
893
900
907
914
418
421
425
428
431
91
92
93
94
95
9
9
9
9
9
1
2
3
4
5
563
570
577
584
592
266
269
272
276
279
46
47
48
49
50
4
4
4
4
5
6
7
8
9
0
921
928
936
943
950
435
438
442
445
448
96
97
98
99
100
9
9
9
9
0
6
7
8
9
0
VAV-SVN01E-EN
45
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit
Setup
Chart 15– LSxF 10SQ ECM CFMTable
LSxF 10SQ
Motor Min CFM: 400
Motor Max CFM: 1800
%
Setting
TENS
Switch
UNITS
Switch
%
Setting
TENS
Switch
UNITS
Switch
CFM
L/sec
CFM
L/sec
400
414
428
443
457
189
196
202
209
216
1
2
3
4
5
0
0
0
0
0
1
2
3
4
5
1107
1121
1135
1150
1164
523
529
536
543
549
51
52
53
54
55
5
5
5
5
5
1
2
3
4
5
471
485
499
513
527
222
229
236
242
249
6
7
8
9
10
0
0
0
0
1
6
7
8
9
0
1178
1192
1206
1220
1234
556
563
569
576
583
56
57
58
59
60
5
5
5
5
6
6
7
8
9
0
542
556
570
584
598
256
262
269
276
282
11
12
13
14
15
1
1
1
1
1
1
2
3
4
5
1249
1263
1277
1291
1305
589
596
603
609
616
61
62
63
64
65
6
6
6
6
6
1
2
3
4
5
612
626
641
655
669
289
296
302
309
316
16
17
18
19
20
1
1
1
1
2
6
7
8
9
0
1319
1333
1348
1362
1376
623
629
636
643
649
66
67
68
69
70
6
6
6
6
7
6
7
8
9
0
683
697
711
725
740
322
329
336
342
349
21
22
23
24
25
2
2
2
2
2
1
2
3
4
5
1390
1404
1418
1432
1447
656
663
669
676
683
71
72
73
74
75
7
7
7
7
7
1
2
3
4
5
754
768
782
796
810
356
362
369
376
382
26
27
28
29
30
2
2
2
2
3
6
7
8
9
0
1461
1475
1489
1503
1517
689
696
703
709
716
76
77
78
79
80
7
7
7
7
8
6
7
8
9
0
824
838
853
867
881
389
396
402
409
416
31
32
33
34
35
3
3
3
3
3
1
2
3
4
5
1531
1545
1560
1574
1588
723
729
736
743
749
81
82
83
84
85
8
8
8
8
8
1
2
3
4
5
895
909
923
937
952
422
429
436
442
449
36
37
38
39
40
3
3
3
3
4
6
7
8
9
0
1602
1616
1630
1644
1659
756
763
769
776
783
86
87
88
89
90
8
8
8
8
9
6
7
8
9
0
966
980
994
1008
1022
456
462
469
476
482
41
42
43
44
45
4
4
4
4
4
1
2
3
4
5
1673
1687
1701
1715
1729
789
796
803
809
816
91
92
93
94
95
9
9
9
9
9
1
2
3
4
5
1036
1051
1065
1079
1093
489
496
502
509
516
46
47
48
49
50
4
4
4
4
5
6
7
8
9
0
1743
1758
1772
1786
1800
823
829
836
843
850
96
97
98
99
100
9
9
9
9
0
6
7
8
9
0
46
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Wiring
Diagrams
Figure 19 – Single-Duct Units (Electronic or DDC/UCM)
Line Voltage
L1 L2 N - 480
(See Nameplate)
L1 L2 - 208, 240
L1 N - 277, 347
SINGLE DUCT UNITS - ELECTRONIC OR DDC/UCM -
HEATER TERMINALS - TYPICAL OF SINGLE PHASE VOLTAGES
L1
N
TB4
SINGLE
PHASE
G
L1
N
Manual Reset
Cutout
LINE
Optional
Fuse
STAGES
Contactor
1st Stage
VOLTAGES
1
208
240
277
347
480
2
3
Contactor
2nd Stage
Optional
Fuse
(208, 240, and 480)
HEATER
CONTACTORS
Magnetic Contactors (MAGN)
Mercury Contactors (MERC)
Optional
Transformer
Contactor
3rd Stage
Air Flow
Auto Reset
Switch Thermal Cutout
L1
N
G
Optional
Door
Disconnect
Switch
24V Input from
Controller
24V Output to
Controller
SINGLE DUCT UNITS - ELECTRONIC OR DDC/UCM -
HEATER TERMINALS - TYPICAL OF THREE PHASE VOLTAGES
Line Voltage
(See Nameplate)
L1 L2 L3 - 208,480,600
L1 L2 L3
Contactor
1st Stage
G
TB4
L1 L2 L3
THREE
PHASE
STAGES
LINE
1
2
3
VOLTAGES
208
480
575
Contactor
2nd Stage
Manual Reset
Cutout
HEATER
Optional
Fuse
CONTACTORS
Magnetic Contactors (MAGN)
Mercury Contactors (MERC)
Contactor
3rd Stage
Notes:
1.
FACTORY INSTALLED
FIELD INSTALLED
OPTIONAL
Optional
Transformer
Air Flow
Thermal Cutout Switch
Auto Reset
2. Actual heater wiring diagrams are supplied
with each unit (3-stage shown).
L1 L2 L3
G
3. Load carrying P.E. Switches or Contactors
are supplied depending upon amp drawn.
4. Air Flow Switch, Auto Reset Thermal Cutout
and Manual Reset Cutout are provided as standard.
Optional
Door
Disconnect
Switch
5. Heater Line Fuses, Transformers, and Door
Interlocking Disconnect are optional.
6. If transformer is not ordered, a separate 24-volt
power supply is required for operation of unit controls.
24V Input from
Controller
24V Output to
Controller
VAV-SVN01E-EN
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Wiring
Diagrams
Figure 20 – Single-Duct Units (Pneumatic Controls)
SINGLE DUCT UNITS - PNEUMATIC CONTROL -
HEATER TERMINAL - TYPICAL OF SINGLE PHASE VOLTAGES
L1 L2 - 208, 240
L1 L2 N - 480
L1 N - 277, 347
Line Voltage
(See Nameplate)
L1
N
G
SINGLE
PHASE
LINE
TB4
Manual Reset
Cutout
L1
N
Optional
Fuse
VOLTAGES
Contactors
STAGES
208
240
277
347
480
1
2
3
PE Switch
1st Stage
HEATER
CONTACTORS
P.E. with Magnetic Contactors (PEMA)
P.E. with Mercury Contactors (PEME)
Auto Reset
Thermal Cutout
Air Flow
Switch
P.E. Switch
2nd Stage
N
L1
P.E. Switch
3rd Stage
G
Optional
Door
Disconnect
Switch
L1 L2 L3 - 208, 600
L1 L2 L3 N - 480
Line Voltage
(See Nameplate)
SINGLE DUCT UNITS - PNEUMATIC CONTROL -
HEATER TERMINAL - TYPICAL OF THREE PHASE VOLTAGES
L1 L2 L3
G
THREE
Manual Reset
Cutout
Optional
Fuse
PHASE
STAGES
1
Contactors
L1 L2 L3
TB4
LINE
VOLTAGES
208
2
3
480
575
HEATER
CONTACTORS
P.E. with Magnetic Contactors (PEMA)
P.E. with Mercury Contactors (PEME)
PE Switch
1st Stage
Air Flow
Switch
Auto Reset
Thermal Cutout
NOTE:
P.E. Switch
2nd Stage
FACTORY INSTALLED
FIELD INSTALLED
OPTIONAL
L1 L2 L3
N
N
1.
2.
G
Actual heater wiring diagram is supplied
with each unit (3-stage shown).
P.E. Switch
3rd Stage
3.
4.
Load carrying P.E. Switches or Contactors
are supplied depending upon amp drawn.
Optional
Door
Disconnect
Switch
Air Flow Switch, Auto Reset Thermal Cutout
and Manual Reset Cutout provided as standard.
Heater Line Fuses and Door Interlocking
Disconnect are optional.
5.
48
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Wiring
Diagrams
Figure 21 – Fan-Powered Units (Electronic or DDC/UCM)
Line Voltage
(See Nameplate)
L1 L2 N - 208, 240, 480
L1 N - 277, 347
FAN-POWERED UNITS - ELECTRONIC OR DDC/UCM -
HEATER TERMINALS - TYPICAL OF SINGLE PHASE VOLTAGES
L1 L2
N
SINGLE
PHASE
TB4
G
LINE
L1 L2
N
STAGES
1
2
Optional
Fuse
Manual Reset
Cutout
VOLTAGES
Contactor
1st Stage
208
240
277
347
480
HEATER
CONTACTORS
Magnetic Contactors (MAGN)
Mercury Contactors (MERC)
Contactor
2nd Stage
Optional
Air Flow
Switch
Auto Reset
Thermal Cutout
L1 L2
N
G
Optional
Door
Disconnect
Switch
24V Input from
Controller
115 or 277V
Output to Motor
FAN-POWERED UNITS - ELECTRONIC OR DDC/UCM -
HEATER TERMINALS - TYPICAL OF THREE PHASE VOLTAGES
Line Voltage
(See Nameplate)
L1 L2 L3 N - 208,480,600
L1 L2 L3
N
Contactor
1st Stage
G
TB4
THREE
PHASE
L1 L2 L3
N
STAGES
1
2
Optional
Fuse
Manual Reset
Cutout
LINE
VOLTAGES
208
480
575
HEATER
CONTACTORS
Magnetic Contactors (MAGN)
Mercury Contactors (MERC)
Contactor
2nd Stage
Notes:
1.
Optional
Air Flow
FACTORY INSTALLED
FIELD INSTALLED
OPTIONAL
Auto Reset
Thermal Cutout Switch
L1 L2 L3
N
G
2. Actual heater wiring diagrams are supplied
with each unit (2-stage shown).
3. Load carrying P.E. Switches or Contactors
are supplied depending upon amp drawn.
4. Auto Reset Thermal Cutout and Manual Reset
Cutout are provided as standard.
Optional
Door
Disconnect
Switch
5. Heater Line Fuses, Airflow Switch, and Door
Interlocking Disconnect are optional.
24V Input from
Controller
115 or 277V
Output to Motor
VAV-SVN01E-EN
49
Download from Www.Somanuals.com. All Manuals Search And Download.
Wiring
Diagrams
Figure 22 – Fan-Powered Units (Pneumatic Controls)
FAN-POWERED UNITS - PNEUMATIC CONTROL -
HEATER TERMINAL - TYPICAL OF SINGLE PHASE VOLTAGES
L1 L2 N - 208, 240, 480
L1 N - 277, 347
Line Voltage
(See Nameplate)
L1 L2
N
G
SINGLE
PHASE
LINE
TB4
Manual Reset
Cutout
L1 L2
N
Optional
Fuse
Contactors
VOLTAGES
STAGES
PE Switch
1st Stage
208
240
277
347
480
1
2
3
HEATER
CONTACTORS
Auto Reset
Thermal Cutout
Optional
Air Flow
Switch
P.E. with Magnetic Contactors (PEMA)
P.E. with Mercury Contactors (PEME)
L1 L2
N
G
Optional
Door
Disconnect
Switch
115 to 277V
Output to Motor
FAN-POWERED UNITS - PNEUMATIC CONTROL -
HEATER TERMINAL - TYPICAL OF THREE PHASE VOLTAGES
Line Voltage
(See Nameplate)
L1 L2 L3 N - 208, 480, 575
L1 L2 L3
N
G
THREE
Manual Reset
Cutout
Optional
Fuse
PHASE
STAGES
1
Contactors
L1 L2 L3 N
LINE
VOLTAGES
208
TB4
2
3
480
PE Switch
1st Stage
575
HEATER
CONTACTORS
P.E. with Magnetic Contactors (PEMA)
P.E. with Mercury Contactors (PEME)
P.E. Switch
2nd Stage
NOTE:
L1 L2 L3
N
N
FACTORY INSTALLED
G
1.
FIELD INSTALLED
OPTIONAL
Optional
Air Flow
Switch
Auto Reset
Thermal Cutout
2.
Actual heater wiring diagram is supplied
with each unit (1 and 2-stage shown).
Optional
Door
Disconnect
Switch
3.
4.
Load carrying P.E. Switches or Contactors
are supplied depending upon amp drawn.
Auto Reset Thermal Cutout and Manual Reset
Cutout provided as standard.
Heater Line Fuses, Door Interlocking
Disconnect, and Airflow Switch are optional.
5.
115 to 277V
Output to Motor
50
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Wiring
Diagrams
Figure 23 – Fan-Powered Control Boxes
Fan-powered Control Box
with Electronic or DDC Controls
Fan-powered Control Box
with Pneumatic Controls
Duct Pressure Switch Option
LINE VOLTAGE
LINE VOLTAGE
OR FROM HEATER TERMINAL
OR FROM HEATER TERMINAL
GREEN
GROUND
SCREW
GREEN
GROUND
SCREW
N
N
L1
L1
5.
5.
TRANSFORMER
TRANSFORMER
6.
Y
DISCONNECT
SWITCH
DISCONNECT
SWITCH
}
BK
BK
W
W
NO
BL
BR
R
BK
BK
TO VAV
C
CONTROLLER
2.
2.
NC
BK
BK
W
W
BK
BK
DUCT PRESSURE
SWITCH
BK
BK
2
2
4
3
4
3
MOTOR
RELAY
MOTOR
RELAY
BK
BK
BR
BR
FUSE
FUSE
4.
4.
1
1
24V
24V
R
R
W
W
W
W
MOTOR
SPEED
CONTROL
MOTOR
SPEED
CONTROL
TERMINAL
BLOCK
TERMINAL
BLOCK
FAN CONTROL BOX
FAN CONTROL BOX
W
W
BK
BK
BR
BR
BR
BR
MOTOR
FAN
MOTOR
FAN
CAPACITOR
CAPACITOR
3.
3.
Fan-powered Control Box
with Pneumatic Controls
LINE VOLTAGE
WARNING
OR FROM HEATER TERMINAL
HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG
ALL ELECTRIC POWER INCLUDING
REMOTE DISCONNECTS BEFORE
SERVICING.
GREEN
GROUND
SCREW
N
L1
5.
DUCT PRESSURE MAIN CONTROL
6.
DISCHARGE MOTOR START/RUN
CAPACITORS BEFORE SERVICING.
DISCONNECT
SWITCH
BK
FAILURE TO DISCONNECT POWER
BEFORE SERVICING CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
W
NO
NC
NO
BK
2.
C
C
BK
NC
P.E. SWITCH-2
CAUTION
BK
W
USE COPPER CONDUCTORS ONLY!
P.E. SWITCH-1
UNIT TERMINALS ARE NOT DESIGNED
TO ACCEPT OTHER TYPES OF
CONDUCTORS.
BK
BK
BK
NO
6.
FAILURE TO DO SO MAY CAUSE
DAMAGE TO THE EQUIPMENT.
BK
FUSE
C
4.
NC
P.E. SWITCH
W
W
NOTES:
1.
FACTORY INSTALLED
BY OTHERS
MOTOR
SPEED
CONTROL
TERMINAL
BLOCK
OPTIONAL OR ALTERNATE CIRCUITRY
2.
DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED
EXTERNAL TO CONTROL BOX.
3.
4.
5.
CAPACITOR IS INSTALLED ON FAN HOUSING.
FUSE IS OPTIONAL.
FAN CONTROL BOX
W
BK
BR
BR
DETERMINED BY MOTOR VOLTAGE ON ORDER.
VOLTAGE FOUND ON UNIT NAMEPLATE.
MOTOR
FAN
CAPACITOR
3.
6.
FOR SERIES FAN POWERED TERMINAL UNITS ONLY.
VAV-SVN01E-EN
51
Download from Www.Somanuals.com. All Manuals Search And Download.
Wiring
Diagrams
Figure 24 – Fan-Powered Units with ECM
Fan-powered Control Box w/ ECM with Electronic or DDC Controls
(Depending on the size of the unit, the ECM board may or may not be located
in the fan control box.)
Fan-powered Control Box w/ ECM with Pneumatic Controls
Duct Pressure Switch Option
LINE VOLTAGE
OR FROM HEATER TERMINAL
LINE VOLTAGE
FAN
FAN
MOTOR
OR FROM HEATER TERMINAL
MOTOR
4.
4.
L1
N
BK
GR
Y
GR
GREEN
GROUND
SCREW
GREEN
GROUND
SCREW
NEUT.
24V
RED
TERMINAL
BLOCK
RED
TERMINAL
BLOCK
2.
DISCONNECT
SWITCH
2
4
3
DISCONNECT
SWITCH
3.
W
FUSE
2.
BL
BK
ECM
BOARD
3.
W
1
FUSE
24V
Y
MOTOR
RELAY
5.
POWER
FACTOR
CORRECTION
CHOKE
NO
NC
3.
BL
NEUT.
24V
BL
RED
RED
C
Y
TO VAV
CONTROLLER
DUCT
BL
}
PRESSURE
SWITCH
Y
ECM
BOARD
BL
BK
TRANSFORMER
TRANSFORMER
POWER FACTOR
CORRECTION CHOKE
FAN CONTROL BOX
FAN CONTROL BOX
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG
ALL ELECTRIC POWER INCLUDING
REMOTE DISCONNECTS BEFORE
SERVICING.
DISCHARGE MOTOR START/RUN
CAPACITORS BEFORE SERVICING.
Fan-powered Control Box with Pneumatic Controls
FAILURE TO DISCONNECT POWER
BEFORE SERVICING CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
LINE VOLTAGE
FAN
MOTOR
4.
OR FROM HEATER TERMINAL
CAUTION
GR
USE COPPER CONDUCTORS ONLY!
GREEN
GROUND
SCREW
UNIT TERMINALS ARE NOT DESIGNED
TO ACCEPT OTHER TYPES OF
CONDUCTORS.
TERMINAL
BLOCK
FAILURE TO DO SO MAY CAUSE
DAMAGE TO THE EQUIPMENT.
DISCONNECT
SWITCH
2.
BK
3.
W
DUCT PRESSURE MAIN CONTROL
5.
FUSE
BL
POWER FACTOR
NO
NC
NO
BK
CORRECTION CHOKE
C
C
BK
NEUT.
24V
RED
Y
NC
P.E. SWITCH-2
RED
BL
BK
P.E. SWITCH-1
BK
TRANSFORMER
NOTES:
NO
ECM
BOARD
1.
C
FACTORY INSTALLED
BY OTHERS
OPTIONAL OR ALTERNATE CIRCUITRY
NC
P.E. SWITCH
2.
DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED
EXTERNAL TO CONTROL BOX.
FAN CONTROL BOX
3.
4.
FUSE IS OPTIONAL.
DETERMINED BY MOTOR VOLTAGE ON ORDER.
VOLTAGE FOUND ON UNIT NAMEPLATE.
5.
FOR SERIES FAN POWERED TERMINAL UNITS ONLY.
52
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Wiring
Diagrams
Figure 25 – Fan-Powered Low-Height Units
Fan-Powered Low-Height Control Box with Electronic or DDC Controls
CAPACITOR
FAN
3.
MOTOR 2
(SIZE 10 ONLY)
FAN
3.
MOTOR
Fan-Powered Low-Height Control Box with Pneumatic Controls
Duct Pressure Switch Option
5.
BR
CAPACITOR
LINE VOLTAGE
OR FROM HEATER TERMINAL
BR
CAPACITOR
3.
FAN
MOTOR 2
(SIZE 10 ONLY)
BR
FAN
BR
W
L1
N
BK
MOTOR
W
BK
3.
5.
OR FROM HEATER TERMINAL
CAPACITOR
LINE VOLTAGE
GREEN
GROUND
SCREW
BR
BR
W
BR
2.
2.
L1
N
W
BK
BR
MOTOR
SPEED
GREEN
CONTROL
BK
GROUND
SCREW
DISCONNECT
MOTOR
SPEED
BK
W
SWITCH
2.
W
W
BK
BK
W
W
CONTROL
TERMINAL
BLOCK
W
W
2.
DISCONNECT
SWITCH
TERMINAL
BLOCK
W
4.
BK
BK
W
BR
W
FUSE
BR
W
W
4.
FUSE
BK
W or BR
Y
BK
BK
BK
TO VAV
CONTROLLER
BL
BK
6.
2
MOTOR
RELAY
BK
2
4
4
BR
R
}
NO
NC
TRANSFORMER
24V
BR
BL
BL
Y
BL
C
1
24V
3
TRANSFORMER
1
24V
3
R
DUCT
MOTOR
RELAY
PRESSURE
SWITCH
FAN CONTROL BOX
FAN CONTROL BOX
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG
ALL ELECTRIC POWER INCLUDING
REMOTE DISCONNECTS BEFORE
SERVICING.
DISCHARGE MOTOR START/RUN
CAPACITORS BEFORE SERVICING.
Fan-Powered Low-Height Control Box with Pneumatic Controls
FAN
MOTOR 2
(SIZE 10 ONLY)
FAILURE TO DISCONNECT POWER
BEFORE SERVICING CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
FAN
MOTOR
3.
3.
5.
OR FROM HEATER TERMINAL
BR
CAUTION
BR
LINE VOLTAGE
USE COPPER CONDUCTORS ONLY!
BK
UNIT TERMINALS ARE NOT DESIGNED
TO ACCEPT OTHER TYPES OF
CONDUCTORS.
CAPACITOR
W
BR
L1
N
BK
W
CAPACITOR
FAILURE TO DO SO MAY CAUSE
DAMAGE TO THE EQUIPMENT.
GREEN
GROUND
SCREW
MOTOR
SPEED
CONTROL
2.
DUCT PRESSURE MAIN CONTROL
6.
W
W
BK
BK
W
TERMINAL
BLOCK
2.
NO
NC
NO
C
BK
W
DISCONNECT
SWITCH
C
BK
W
BR
W
NC
4.
FUSE
P.E. SWITCH-2
P.E. SWITCH-1
BK
BK
BK
NOTES:
1.
NO
FACTORY INSTALLED
BY OTHERS
OPTIONAL OR ALTERNATE CIRCUITRY
BK
C
NC
2.
3.
DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED
EXTERNAL TO CONTROL BOX.
P.E. SWITCH
CAPACITOR IS INSTALLED ON FAN HOUSING.
FUSE IS OPTIONAL.
FAN CONTROL BOX
4.
5.
DETERMINED BY MOTOR VOLTAGE ON ORDER.
VOLTAGE FOUND ON UNIT NAMEPLATE.
6.
FOR SERIES FAN POWERED TERMINAL UNITS ONLY.
VAV-SVN01E-EN
53
Download from Www.Somanuals.com. All Manuals Search And Download.
Wiring
Diagrams
Figure 26 – Fan-Powered Low-Height Units with ECM
Fan-Powered Low-Height Control Box w/ ECM with Electronic or DDC Controls
(Depending on the size of the unit, the ECM board may or may not be located
in the fan control box.)
Fan-Powered Low-Height Control Box w/ ECM with Pneumatic Controls
Duct Pressure Switch Option
4.
LINE VOLTAGE
LINE VOLTAGE
4.
OR FROM HEATER TERMINAL
FAN
MOTOR
FAN
MOTOR 2
(SIZE 10 ONLY)
OR FROM HEATER TERMINAL
FAN
MOTOR
FAN
MOTOR 2
(SIZE 10 ONLY)
BK
GR
GR
GREEN
GROUND
SCREW
GREEN
GROUND
SCREW
W
Y
W
BK
BK
NEUT.
24V
RED
TERMINAL
BLOCK
TERMINAL
BLOCK
RED
2.
DISCONNECT
DISCONNECT
SWITCH
3.
SWITCH
W
2
2.
4
3
FUSE
BL
BK
3.
W
Y
FUSE
ECM
BOARD
5.
1
24V
NO
BL
NEUT.
24V
MOTOR
RELAY
BL
RED
RED
C
NC
DUCT
PRESSURE
SWITCH
TO VAV
CONTROLLER
Y
Y
ECM
BOARD
BL
BK
}
BL
BK
TRANSFORMER
TRANSFORMER
FAN CONTROL BOX
FAN CONTROL BOX
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG
ALL ELECTRIC POWER INCLUDING
REMOTE DISCONNECTS BEFORE
SERVICING.
DISCHARGE MOTOR START/RUN
CAPACITORS BEFORE SERVICING.
FAILURE TO DISCONNECT POWER
BEFORE SERVICING CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
CAUTION
USE COPPER CONDUCTORS ONLY!
Fan-Powered Low-Height Control Box w/ ECM with Pneumatic Controls
UNIT TERMINALS ARE NOT DESIGNED
TO ACCEPT OTHER TYPES OF
CONDUCTORS.
4.
LINE VOLTAGE
FAILURE TO DO SO MAY CAUSE
DAMAGE TO THE EQUIPMENT.
FAN
FAN
MOTOR 2
OR FROM HEATER TERMINAL
MOTOR
(SIZE 10 ONLY)
GR
GREEN
GROUND
SCREW
W
BK
DUCT PRESSURE MAIN CONTROL
5.
TERMINAL
BLOCK
DISCONNECT
SWITCH
2.
BL
BL
3.
NO
BK
NO
NC
W
Y
FUSE
C
C
BK
NC
NEUT.
RED
24V
RED
Y
P.E. SWITCH-2
P.E. SWITCH-1
BK
BL
BK
TRANSFORMER
NOTES:
1.
FACTORY INSTALLED
BY OTHERS
OPTIONAL OR ALTERNATE CIRCUITRY
ECM
BOARD
NO
NC
C
2.
DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED
EXTERNAL TO CONTROL BOX.
P.E. SWITCH
3.
4.
FUSE IS OPTIONAL.
FAN CONTROL BOX
DETERMINED BY MOTOR VOLTAGE ON ORDER.
VOLTAGE FOUND ON UNIT NAMEPLATE.
5.
FOR SERIES FAN POWERED TERMINAL UNITS ONLY.
54
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
Figure 27 – Standard Motor Removal
Figure 28 – Low-Height Motor Removal
Periodic maintenance of theVariTrane
product is minimal, but necessary for
efficient operation. Routine mainte-
nance consists of inspecting/replacing
the air filters of the fan-powered
terminals.
Motors
Both the PSC (permanent split capaci-
tor) and the ECM (Electrically Commu-
tated Motor) require no lubrication
during its normal life of operation.
FanWheel:
Periodically, the fan wheel should be
inspected for dirt or debris and cleaned
as necessary.
Standard height fan-powered series
and parallel fan motors are replaceable
through the filter opening and the
standard sliding side access panel. To
access the fan motor, the fan housing
must be detached by removing the
mounting bolts that hold the housing to
the fan board. Removing the entire
housing allows the fan motor, fan
housing, and fan wheel to be re-aligned
on a workbench or floor and prevent
any possible fan wheel rubbing that
may occur. Removing the housing will
provide access to the motor shaft set
screw that holds the fan wheel to the
motor shaft.
The low-height fan assembly was
designed with an inlet ring that assists
with removal of the fan motor. To
access the fan motor assembly, the
bottom panel must be removed. The
inlet ring is held in place by six bolts
and three motor mount bolts. Remove
these bolts and the motor and fan
wheel will come out of the fan housing.
Filter
The filter on fan-powered terminals will
need to be inspected/replaced routinely
depending on the environmental
conditions of the plenum.
Water Coil
Water coils should be inspected and the
fins should be cleaned periodically.
Water coils have been provided with an
access panel as standard to assist with
inspection and cleaning.
Fan Motor Replacement
WARNING
HazardousVoltage
w/Capacitors!
Disconnect all electric power, including
remote disconnects and discharge all
motor start/run capacitors before
servicing. Follow proper lockout/tagout
procedures to ensure the power cannot
be inadvertently energized.Verify with
an appropriate voltmeter that all
capacitors have discharged. Failure to
disconnect power and discharge
capacitors before servicing could result
in death or serious injury.
WARNING
Rotating Components!
Disconnect all electric power, including
remote disconnects before servicing.
Follow proper lockout/tagout proce-
dures to ensure the power cannot be
inadvertently energized. Failure to
disconnect power before servicing
could result in death or serious injury.
VAV-SVN01E-EN
55
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
of Diffusers
General
Figure 29 – Diffuser Installation inT-Bar
Ceiling
Drywall/Plaster Ceiling
All units must be installed upright and
level as indicated by the arrow on the
side of the units. Return air slots should
be placed perpendicular and offset to
the slot diffusers to avoid short-
Finish installation of diffusers in plaster
ceiling. Follow these procedures before
completing the ceiling construction
(Figure 31).
1. Suspend the units above the intended
ceiling level and their approximate
horizontal positions and finish running
flexible ductwork.
circuiting of air distribution patterns.
Place the unit in its approximate final
position and check that it is upright and
level. For single- slot units, engage
the back of the diffuser over the t-bar
with an edge and both ends resting on
the t-bar. For double-slot units, slide
the unit over the t-bar. For center-
notch units, place diffuser over the
t-bar, straddling it across a t-bar and
resting on the units ends.
2.After drywall and/or plaster is installed,
cut openings to receive the diffuser air
outlets. Also, allow for access openings
to complete installation and service of
the unit.
3.Slide the trim accessory up and into the
ceiling opening. Using the rim
accessory as a template, drill four guide
holes in the lip of the diffuser slot.
Lower the unit onto the trim frame and
attach with the sheet metal screws.
Concealed Spline Ceiling
Follow these procedures to finish
installation of control and satellite
diffusers and concealed spline for
suspension ceilings before completing
the ceiling construction (Figure 30).
Place the units in their approximate
final positions. If using the trim angle
diffuser, its slots must be even with the
spline level. If applying the trim
If the unit has a fire damper, make sure
that the damper is still fully open.
Diffuser discharge must always be
flush with the ceiling tiles to assure the
proper airflow (Coanda effect).
Note:The bottom of the throat section
must be parallel to the ceilings for proper
air distribution.
Diffusers require specific installation
information when mounting to a
desired ceiling type. Select the ceiling
type that closely matches the job site
application and use the following
procedures.
CAUTION
accessory, the bottom of the diffuser
must be level with the finished ceiling.
Equipment Damage!
Do not install trim frame into ceiling
using screws.When diffuser is placed
on the trim frames, it will pull out.
If installing the trim accessory, insert
the trim into the ceiling opening from
below and engage the diffuser slot to
the trim t-bar structure.With bottom
flange of trim accessory against the
ceiling, and using the pre-drilled holes
in the flange as a guide, drill holes in the
flange of the diffuser. Join the diffuser
and trim accessory with self-taping
sheet metal.
T-Bar Ceiling
Finish installation of the diffuser in t-bar
ceiling. (See Figure 29.) Follow these
procedures before the ceiling construc-
tion is completed.
1.Position the diffuser at each end resting
directly on the structural t-bar for
support and the t-bar fitting into the
channel provided at the unit discharge
air throw.
Figure 31 – Diffuser withTrim
Accessory Installation in Plaster Ceiling
Figure 30 – Diffuser withTrim
Accessory Installation in Concealed
Spline Ceiling
2.A ceiling tile support flange is provided
on each side of the discharge slot of the
unit.Trim ceiling tile approximately 1½
inches each to allow for width of
discharge slot. For revealed edge
ceilings, tile must be cut in a “Z”
pattern.
3.Install ceiling tiles in usual manner with
cut edges resting on the flanges of the
air slot.
Plaster trim frame attaches with 2–4
tension clips on the side of the diffuser.
56
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance/
Service Log
Date
Tag
Serial #
Service Notes
VAV-SVN01E-EN
57
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance/
Service Log
Date
Tag
Serial #
Service Notes
58
VAV-SVN01E-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Notes
VAV-SVN01E-EN
59
Download from Www.Somanuals.com. All Manuals Search And Download.
Literature Order Number
File Number
VAV-SVN01E-EN
SL-TD-000-VAV-SVN01E-EN-0606
SL-TD-000-VAV-SVN01D-EN-0905
Inland
Supersedes
Trane
Stocking Location
An American Standard Company
Trane has a policy of continuous product and product data improvement and reserves the right to change
design and specifications without notice. Only qualified technicians should perform the installation and
servicing of equipment referred to in this publication.
For more information contact
your local district office or
e-mail us at [email protected]
Download from Www.Somanuals.com. All Manuals Search And Download.
|