Installation, Operation, &
Maintenance
TM
IntelliPak
Commercial Self-Contained
Modular Series, 20-35 tons
“JO” and later design sequence
Models:
SCWG -020, -025, -030, -032, -035
SIWG -020, -025, -030, -032, -035
SCRG -020, -025, -030, -032
SIRG -020, -025, -030, -032
March 2008
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
Cross reference to related publications/information:
• Product Catalog, PKG-PRC003-EN, Modular Series Commercial Self-Contained
• IntelliPak• Self-Contained Programming Guide, PKG-SVP01B-EN
• Remote Air-Cool-Condenser Installation, Owner, and Diagnostic Manual, CXRC-
SVX01B-EN
Installation …………………………........…....…6
general information …………………………………………6
pre-installation considerations… …………………………11
dimensions & weights ………………………………...…19
mechanical specifications …………………………………30
electrical requirements ……………………………………33
pre-startup requirements …………………………………35
programming ………………………………….……………57
startup …………………………………………………….…67
Operation ………………………………………70
general information ………………………………………70
sequence of operation ………………………………….…84
Maintenance ……………………………………91
maintenance procedures ………………………………92
troubleshooting ………………………………………..…105
diagnostics ………………………………………………..106
SCXG-SVX01B-EN
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Service Equipment and Procedures
To minimize refrigerant emissions while
recovering refrigerant, use the
manufacturer’s recommended recycling
equipment per the MSDS. Use
equipment and methods which will pull
the lowest possible system vacuum while
recovering and condensing refrigerant.
Equipment capable of pulling a vacuum of
less than 1,000 microns of mercury is
recommended.
contain moisture. Reference proper
refrigerant charge requirements in the
maintenance section of this manual to
ensure efficient machine operation.
When charging is complete, purge or
drain charging lines into an approved
refrigerant container. Seal all used
refrigerant containers with approved
closure devices to prevent unused
refrigerant from escaping to the atmo-
sphere.Take extra care to properly
maintain all service equipment directly
supporting refrigerant service work such
as gauges, hoses, vacuum pumps, and
recycling equipment .
Refrigerant Handling
Procedures
Environmental Accountability Policy
Trane urges that all HVAC servicers to
make every effort to eliminate, if possible,
or vigorously reduce the emission of CFC,
HCFC, and HFC refrigerants to the
atmosphere. Always act in a responsible
manner to conserve refrigerants for
continued usage even when acceptable
alternatives are available.
Do not open the unit to the atmosphere
for service work until refrigerant is fully
removed/recovered. When leak-testing
with trace refrigerant and nitrogen, use
HCFC-22 (R-22) rather than CFC-12 (R-
12) or any other fully-halogenated
refrigerant . Be aware of any new leak
test methods which may eliminate
refrigerants as a trace gas. Perform
evacuation prior to charging with a
vacuum pump capable of pulling a
vacuum of 1,000 microns of mercury or
less. Let the unit stand for 12 hours and
with the vacuum not rising above 2,500
microns of mercury.
Recover and Recycle Refrigerants
Never release refrigerant to the
atmosphere! Always recover and/or
recycle refrigerant for reuse,
reprocessing (reclaimed), or properly
dispose if removing from equipment.
Always determine the recycle or reclaim
requirements of the refrigerant before
beginning the recovery procedure.
Obtain a chemical analysis of the
refrigerant if necessary. Questions about
recovered refrigerant and acceptable
refrigerant quality standards are
addressed in ARI Standard 700.
When cleaning system components or
parts, avoid using CFC-11 (R-11) or CFC-
113 (R-113). Use only cleaning-solvents
that do not have ozone depletion factors.
Properly dispose of used materials.
Refrigeration system cleanup methods
using filters and driers are preferred.
Keep abreast of unit enhancements,
conversion refrigerants, compatible
parts, and manufacturer’s recommenda-
tions that will reduce refrigerant emis-
sions and increase equipment operating
efficiencies.
Refrigerant Handling and Safety
Consult the manufacturer’s material
safety data sheet (MSDS) for information
on refrigerant handling to fully
A rise above 2,500 microns of mercury
indicates a leak test is required to locate
and repair any leaks. A leak test is
required on any repaired area.
understand health, safety, storage,
handling, and disposal requirements. Use
the approved containment vessels and
refer to appropriate safety standards.
Comply with all applicable transportation
standards when shipping refrigerant
containers.
Charge refrigerant into the equipment
only after equipment does not leak or
4
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Modular Series Self-Contained
Unit Components
The water-cooled condensers are shell
and tube type with an internal subcooler.
Condensers are available as mechani-
cally or chemically cleanable.The
evaporator fan is double width, double
inlet and forward curved with a fixed
pitch belt drive assembly. Frequency
drives or inlet guide vanes are optional.
Motor options include open drip proof,
high efficiency,TEFC, or mill and chem
spec.
refrigerant connections to the air cooled
condensing unit. Also, air-cooled units
have two refrigerant circuits.Water-
cooled units have four refrigerant circuits;
which include a filter drier, pressure relief
valve, liquid line service valve, sight glass/
moisture indicator, thermal expansion
valve with a sensing bulb and external
equalizing line, discharge line shrader
valve, a suction line shrader valve, and
high and low pressure cutout switches.
Water-cooled units also include a liquid
line service valve for each circuit.
Commercial self contained units are
complete HVAC systems used in floor-by-
floor applications. Units are easy to install
because they feature a single point
power connection, factory installed and
tested controls, single water point
connection, factory installed options, and
an internally trapped drain connection.
Modular self-contained units can ship as
split-apart units for installation ease. Split-
apart units ship with a dry nitrogen
charge and require field refrigerant
charging.
All water-cooled units ship with a full
refrigerant and oil charge. Air-cooled
units ship with oil and a dry nitrogen
holding charge and require field-piping
For more detailed information, see the
Owner’s section of this manual.
Units consist of multiple compressors,
water-cooled condensers (water-cooled
units only), an evaporator coil, dual
forward curved fans, and control panel.
Air-cooled units require a remote air-
cooled condenser, model CXRC.The
hermetically sealed 3-D scroll
compressor motors utilize internal motor
protection and time delays to prevent
excessive cycling. Unit controls are either
an electromechanical thermostat or
microprocessor controls on the IntelliPak
unit. See Figure I-GI-1 for a typical unit.
The hermetically sealed 3-D scroll
compressor motors utilize internal motor
protection and time delays to prevent
excessive cycling.
Figure I-GI-1. IntelliPak® commercial self-contained Modular Series unit.
SCXG-SVX01B-EN
5
Download from Www.Somanuals.com. All Manuals Search And Download.
general
information
Installation
Control Options
system network.
Units may be ordered with either
conventional thermostat interface or
These modules perform specific unit
functions using proportional/integral
control algorithms.They are mounted in
the unit control panel and are factory
wired to their respective internal compo-
nents. Each module receives and
interprets information from other unit
modules, sensors, remote panels, and
customer binary contacts to satisfy the
applicable request; i.e., economizing,
mechanical cooling, heating, ventilation.
See the Operation section of this manual
for a detailed description of each
TM
IntelliPak Direct Digital Control (DDC).
TM
IntelliPak controls include a Human
Interface (HI) panel with two line by forty
(40) character clear English display for
easy operator interface to unit setup and
control parameters. All basic setup
parameters are preset from the factory.
Human Interface Panel
The HI is unit mounted and accessible
without opening the unit’s front panel. It
allows easy setpoint adjustment using
the HI keypad. In addition, the HI displays
all unit operating parameters and
conditions in a clear language display,
which can be configured for either
English, French, or Spanish.
module’s function.
Optional Controls
Optional controls include a disconnect
switch, dirty filter switch, water flow
switch (water-cooled only), supply air
temperature reset, or external setpoint
inputs. Daytime heating is available on
units with electric, steam, or hot water
heat control options. Morning warmup
operation is available on all units.
The optional remote human interface
(RHI) will control up to four self-contained
units, each containing an interprocessor
communications bridge (IPCB). It has all
the same features as the unit-mounted HI
except for the service mode.
The static pressure probe, zone night
heat/morning warmup, supply air
temperature reset sensor options ship
separate inside the unit control panel for
field installation. For more detailed
information on the unit control options,
see the Owner’s section of this manual.
For more information on setpoint defaults
and ranges and unit programming, see
the IntelliPak Self-Contained Program-
ming Guide, PKG-SVP01B-EN. A copy
ships with each unit.
TM
IntelliPak DDC Control
TM
IntelliPak DDC Control provides “smart”
Unit Nameplate
unit control with safety features and
control relays for pumps, dampers, etc.
The Modular Series IntelliPak self-
contained unit is controlled by a
The unit nameplate identifies the unit
model number, appropriate service
literature, and wiring diagram numbers. It
is mounted on the left end of the unit
control panel.
microelectronic control system that
consists of a network of modules.These
modules are referred to as unit control
modules (UCM). In this manual, the
acronym UCM refers to the entire control
6
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Model
Number
Description
SCWG
Model Number Description
Each IntelliPak self-contained unit has a multiple character model number unique to that unit.To determine a unit’s specific options,
reference the model number on the unit nameplate using the model number explanation below.
S C W G N 20 4 2 JO A B 2 10
085
B
A 1 0 1 0 A A C F A 1 1 0 T 2 0
1 2 3 4 5 67 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
Digit 1 - Unit Model
110 = 1100 rpm
115 = 1150 rpm
120 = 1200 rpm
125 = 1250 rpm
130 = 1300 rpm
135 = 1350 rpm
140 = 1400 rpm
145 = 1450 rpm
150 = 1500 rpm
155 = 1550 rpm
160 = 1600 rpm
165 = 1650 rpm
170 = 1700 rpm
175 = 1750 rpm
180 = 1800 rpm
185 = 1850 rpm
E = Vertical Discharge, Ship Separate
F = Vertical Discharge w/ DoubleWall,
Ship Separate
G = Horizontal Discharge, Ship Separate
H = Horizontal Discharge w/ Double
Wall, Ship Separate
S = Self Contained
Digit 2 - UnitType
C = Commercial
I
= Industrial
Digit 3 - Condenser Medium
W = Water-Cooled
R = Remote Air-Cooled
Digit 13 - PlenumType
B = Std Plenum w/ Factory Cut Holes
C = Low Plenum w/ Factory Cut Holes
E = Std Plenum w/ Field Cut Holes
F = Low Plenum w/ Field Cut Holes
H = Std Plenum Double Wall (Perf)
w/ Field Cut Holes
Digit 4 - Development Sequence
G = Modular Series
Digit 5 - Refrigerant Circuit Configuration
N = Independent, R-22 Refrigerant
R = Independent, 407C Refigerant
J = Low Plenum Double Wall (Perf)
w/ Field Cut Holes
L = Std. Plenum w/Factory Cut Holes,
Ship Separate
M = Low Plenum with Factory Cut
Holes, Ship Separate
P = Std Plenum w/ Field Cut Holes, Ship
Separate
R = Low Plenum w/ Field Cut Holes,
Ship Separate
U = Std Plenum Double Wall (Perf) w/
Field Cut Holes, Ship Separate
V = Low Plenum Double Wall (Perf) w/
Field Cut Holes, Ship Separate
0 = Without Plenum
Digit 6, 7 - Unit Nominal Capacity
20 = 20Tons (Water or Air Cooled)
25 = 25Tons (Water or Air Cooled)
30 = 30Tons (Water Cooled Only)
32 = 32Tons (Air Cooled Only)
35 = 35Tons (Water Cooled Only)
Digit 20 - HeatingType
A = Steam Coil, LH
B = Hot Water Coil, LH
C = Electric Heat, 1 Stage
F = Hydronic Heat Ctrl Interface
G = Elec. Heat Ctrl Interface, 1 stage
K = Steam Coil Ship Separate, LH
L = Hot Water Coil Ship Separate, LH
M = Steam Coil, RH
Digit 8 - UnitVoltage
6 = 200Volt/60 Hz/3 ph
4 = 460Volt/60 Hz/3 ph
5 = 575Volt/60 Hz/3 ph
N = Hot Water Coil, RH
Digit 9 -AirVolume/Temp Control
1 = I-Pak & IGV and Supply AirTemp
Ctrl
2 = I-Pak & VFD and Supply Air
Temp Ctrl
3 = I-Pak & VFD w/ Bypass and
Supply AirTemp Ctrl
4 = I-Pak w/oVol. CTRL, w/ ZoneTemp
Cool
5 = I-Pak w/oVol. CTRL, w/ ZoneTemp
Heat/Cool
6 = I-Pak w/oVol. CTRL, w/ Supply Air
Temp Ctrl
8 = Thermostat Interface
P = Steam Coil Ship Separate, RH
R = HotWater Coil Ship Separate, RH
T = Hi-cap. hot water coil, LH
U = Hi-cap, hot water coil LH,
Ship Seperate
Digit 14 - MotorType
1 = Std. Efficiency ODP
2 = Premium Eff. ODP
V = Hi-cap. hot water coil, RH
W = Hi-cap. hot water coil, RH,
Ship Seperate
3 = Std. EfficiencyTotally Enclosed
Digit 15, 16 - Motor HP
05 = 5 HP Motor
07 = 7.5 HP Motor
10 = 10 HP Motor
15 = 15 HP Motor
20 = 20 HP Motor
25 = 25 HP Motor
0 = None
Digit 21 - Unit Isolators
A = Isopads
B = Spring Isolators
0 = None
Digit 10, 11 - Design Sequence
JO= “J” Design
Digit 17, 18, 19 - Fan RPM
085 = 850 rpm
090 = 900 rpm
095 = 950 rpm
100 = 1000 rpm
105 = 1050 rpm
Digit 12 - Unit Construction
A = Vertical Discharge
B = Vertical Discharge with DoubleWall
C = Horizontal Discharge
D = Horizontal Discharge w/ Double
Wall
SCXG-SVX01B-EN
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Model
Number
Description
SCWG
Digit 22 - Unit Finish
Digit 28 -Ventilation Control
B = Airside Econ w/Traq™ Damper
(Top O/A Inlet)
Digit 32 - Miscellaneous System Control
1 = Timeclock
1 = Paint - Executive Beige
2 = Protective Coating
2 = Interface for Remote HI
3 = Dirty Filter Switch
4 = 1 and 2
3 = Protective Coating w/ Finish Coat
C = Airside Econ w/ Standard
Dampers (Top O/A Inlet)
Digit 23
0 = None
E = Airside Econ w/Traq™ Damper and
Comparative Enthalpy
5 = 1 and 3
6 = 2 and 3
Digit 24 - Unit Connection
1 = Disconnect Switch
2 = Terminal Block
(Top O/A Inlet)
7 = 1, 2, and 3
F = Airside Econ w/ Std Dampers and
Comparative Enthalpy (Top O/A
Inlet)
0 = None
Digit 33 - Control Interface Options
A = Generic BAS Module (GBAS)
B = Ventilation Override Module (VOM)
D = Remote Human Interface (RHI)
G = GBAS andVOM
H = GBAS and RHI
J = VOM and RHI
M = GBAS,VOM, and RHI
0 = None
1 = Tracer/LCI-I (COMM5) interface
module
2 = Tracer/LCI-I and GBAS
3 = Tracer/LCI-I andVOM
4 = Tracer/LCI-I and RHI
5 = Tracer/LCI-I, GBAS andVOM
6 = Tracer/LCI-I, GBAS and RHI
7 = Tracer/LCI-I,VOM and RHI
8 = Tracer/LCI-I, GBAS,VOM and RHI
3 = Dual Point Power
G = Traq DamperVentilation Interface
H = Ventilation For 2 Pos. Cntrl Interface
0 = None
Digit 25 - Industrial Options
A = Protective Coated Evaporator Coil
B = Silver Solder
C = Stainless Steel Screws
D = A and B
Digit 29 -Water Piping
A = Right Hand Condenser Connection
B = Left Hand Condenser Connection
C = Right Hand Basic Piping
D = Left Hand Basic Piping
E = Right Hand Intermediate Piping
F = Left Hand Intermediate Piping
J = Right Hand Basic w/ Flow Switch
K = Left Hand Basic w/ Flow Switch
L = Right Hand Intermediate
w/ Flow Switch
E = A and C
F = B and C
G = A, B and C
0 = None
Digit 26 - Drain PanType
A = Galvanized Sloped
B = Stainless Steel Sloped
Digit 27 -Waterside Economizer
A = Mechanical Clean Full Cap. (4-row)
B = Mechanical Clean Low Cap. (2-row)
C = Chemical Clean Full Cap. (4-row)
D = Chemical Clean Low Cap. (2-row)
E = Mechanical Clean Full Capacity
(4-row) Ship Separate
F = Mechanical Clean Low Capacity
(2-row) Ship Separate
G = Chemical Clean Full Capacity
(4-row) Ship Separate
M = Left Hand Intermediate
w/ Flow Switch
0 = None
Digit 34 - Agency
T = UL Agency Listing
0 = None
Digit 30 - CondenserTubeType
A = Standard CondenserTubes
B = 90/10 CuNi CondenserTubes
0 = None
Digit 35 - FilterType
1 = 2-inch ConstructionThrowaway
2 = 2-inch Med Eff. Throwaway
Digit 31 - Compressor ServiceValves
1 = With Service Valves
0 = None
Digit 36 - Miscellaneous Control Option
A = Low Entering AirTemp. Protect
Device (LEATPD)
H = Chemical Clean Low Capacity
(2-row) Ship Separate
0 = None
B = High DuctTempT-Stat
C = Plenum High Static Switch
D = Kit for Heat Mode Output (w/t’stat)
E = A and B
F = A and C
G = B and C
H = A, B, and C
0 = None
8
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Model
Number
Description
PSWG
Self-Contained Ship-WithAccessory Model Number Description
P
1
S
2
W
3
G
4
S
5
A
6
1
7
1
8
0
9
JO
10 11
Digit 1 - Parts/Accessories
P = Parts/Accessories
Digit 7 - Mixed AirTemperature Protec-
tion Kit (field installed)
1 = Mixed AirTemperature Protection Kit
0 = None
Digit 2 - Unit Model
S= Self-Contained
Digit 8 - Carbon Dioxide Sensor (field
installed)
1 = Carbon Dioxide Sensor Kit
0 = None
Digit 3 - Shipment
W = With Unit
Digit 4 - Development Sequence
F = Signature Series
G = Modular Series
Digit 9 - Future Option
0 = None
Digit 5 - Sensors and Other Accessories
S = Sensors
Digit 10, 11 - Design Sequence
J0 = J Design
Digit 6 - Sensors and Thermostats (field
installed)
A = BAYSENS077 - ZoneTemp Only (CV
andVAV)
B = BAYSENS073 - ZoneTemp with
Timed Override Button (CV andVAV)
C = BAYSENS074 - ZoneTemp with
Timed Override Button, Setpoint Dial
(CV andVAV)
D = BAYSENS023 - Remote Min. Position
Potentiometer Control (OA Damper)
E = BAYSENS108 - CV Zone Sensor-dual
setpoint, man/auto changeover
F = BAYSENS110 - CV Zone Sensor-dual
setpoint, man/auto changeover w,
indicator lights
G = BAYSENS019 - CV Programmable
Night Setback Sensor
H = BAYSENS021 -VAV Zone Sensor with
Indicator Lights
J = BAYSENS020 -VAV Programmable
Night Setback Sensor
K = Remote Sensor Kit
L = Outside AirTemperature Sensor Kit
M = Outside Air Humidity Sensor Kit
N = BAYSTAT010 - 2 Heat/2 Cool
Thermostat
P = BAYSTAT037A - 2 Heat/2 Cool
ProgrammableThermostat
0 = None
SCXG-SVX01B-EN
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Model
Number
Description
PSWG
“After-Shipment”Accessory Model Number
P S A G W N 20 4 **
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
0 0 0
1
10
0
0 0 1 0 1 0 1 0 1 0 0 1 1 0 0 0 0
0
L
1
0 0 7 0 0
0
0
41 42 43 44 45
Digit 21 - Sensors andThermostats
A = BAYSENS077 - ZoneTemp Only (CV
andVAV)
B = BAYSENS073 - ZoneTemp with
Timed Override Button (CV andVAV)
C = BAYSENS074 - ZoneTemp with
Timed Override Button, Setpoint Dial
(CV andVAV)
E = BAYSENS108 - CV Zone Sensor-dual
setpoint, man/auto changeover
F = BAYSENS110 - CV Zone Sensor-dual
setpoint, man/auto changeover w,
indicator lights
G = BAYSENS019 - CV Programmable
Night Setback Sensor
H = BAYSENS021 -VAV Zone Sensor
with Indicator Lights
J = BAYSENS020 -VAV Programmable
Night Setback Sensor
K = Remote Sensor Kit
L = Outside AirTemperature Sensor Kit
M = Outside Air Humidity Sensor Kit
0 = None
Digit 1 - Parts/Accessories
Digit 13, 14 - Motor HP
05 = 5 HP Motor
P = Parts/Accessories
07 = 7.5 HP Motor
Digit 2 - Unit Model
S= Self-Contained
10 = 10 HP Motor
15 = 15 HP Motor
Digit 3 - Shipment
A = After Unit
20 = 20 HP Motor
25 = 25 HP Motor
30 = 30 HP Motor
Digit 4 - Development Sequence
F = Signature Series
G = Modular Series
40 = 40 HP Motor
50 = 50 HP Motor (460V & 575V Only)
0 = Not Defined
Digit 5 - Condenser Medium
W = Water Cooled
R = remote Air Cooled
Digit 15 - Exhaust/Comparative Enthalpy
Module (Field Installed)
1 = ECEM Kit
Digit 6 - Refrigerant Circuit Configuration
N = Independent (Water-Cooled)
M = Manifolded (Air-Cooled)
0 = None
Digit 16 - Generic BAS Module
1 = GBAS 0-5 VDC Kit
0 = None
Digits 7, 8 - Unit Nominal Capacity
20 = 20Tons (Water or Air)
22 = 22Tons (Water Only)
25 = 25Tons (Water or Air)
29 = 29Tons (Water or Air)
30 = 30Tons (Air Only)
Digit 17 - Heat Module
1 = Electric Heat Module Kit
2 = Hydronic Heat Module Kit
0 = None
Digit 22 - Low Entering AirTemperature
Protection Device
1 = Low Entering AirTemperature
Protection Device Kit
0 = None
32 = 32Tons (Water Only)
35 = 35Tons (Water or Air)
38 = 38Tons (Water Only)
40 = 40Tons (Air Only)
42 = 42Tons (Water Only)
46 = 46Tons (Water Only)
50 = 50Tons (Air Only)
52 = 52Tons (Water Only)
58 = 58Tons (Water Only)
60 = 60Tons (Air Only)
65 = 65Tons (Water Only)
72 = 72Tons (Water Only)
80 = 80Tons (Water Only)
Digit 18 - Remote Human Interface and
IPCB
1 = Remote Human Interface Panel Kit
(RHI Only)
2 = Interprocessor Communications
Module Kit (IPCB Only)
3 = RHI and IPCB Kit
Digit 23 - High DuctTemperature
Thermostat
1 = High DuctTemp.Thermostat Kit
0 = None
0 = None
Digit 19 - LonTalk Communications
Interface Kit (LCI)
2 =Tracer/LCI-I Comm Interface Kit
0 = None
Digit 24 - Plenum High Static Switch
1 = Plenum High Static Switch Kit
0 = None
Digit 20 -Ventilation Override Module Kit
Digits 25 — 45 - Future Use
0 = None
Digit 9 - UnitVoltage
6 = 200Volt/60 Hz/3 ph
4 = 460Volt/60 Hz/3 ph
5 = 575Volt/60 Hz/3 ph
0 = Not Defined
(VOM)
1 = VOM Kit
0 = None
Digits 10, 11 - Design Sequence
** = Factory Assigned
Digit 12 - Unit Power Connection
1 = Single Point Power
2 = Dual Point Power
0 = Not Defined
10
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-installation
considerations
Installation
Receiving and Handling
Shipping Package
Commercial self-contained units ship
assembled with protective coverings
over the coil and discharge openings.
Figure I-PC-1 illustrates a typical shipping
package.
Ship-Separate Accessories
Field-installed sensors ship separately
inside the unit’s main control panel. Extra
filters, sheaves, and belts ship in the unit’s
fan motor section. Condenser plugs,
spring isolators, and isopads ship in the
unit’s bottom left side.
Receiving Checklist
Complete the following checklist
immediately after receiving unit
shipment to detect possible shipping
damage.
Inspect individual cartons before
accepting. Check for rattles, bent carton
corners, or other visible indications of
shipping damage.
If a unit appears damaged, inspect it
immediately before accepting the
shipment. Make specific notations
concerning the damage on the freight
bill. Do not refuse delivery.
Inspect the unit for concealed damage
before it is stored and as soon as
possible after delivery. Report
concealed damage to the freight line
within the allotted time after delivery.
Check with the carrier for their allotted
time to submit a claim.
Do not move damaged material from
the receiving location. It is the receiver’s
responsibility to provide reasonable
evidence that concealed damage did
not occur after delivery.
Figure I-PC-1. Typical unit mounted on shipping skid.
Do not continue unpacking the
shipment if it appears damaged. Retain
all internal packing, cartons, and crate.
Take photos of damaged material if
possible.
Notify the carrier’s terminal of the
damage immediately by phone and
mail. Request an immediate joint
inspection of the damage by the carrier
and consignee.
Notify yourTrane representative of
the damage and arrange for repair.
Have the carrier inspect the damage
before making any repairs to the unit.
SCXG-SVX01B-EN
11
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-installation
considerations
Installation
Installation Preparation
Before installing the unit, perform
the following procedures to
ensure proper unit operation.
5. Remove the protective shipping covers
from the unit. Refer to the “Unit
Protective Covers” section on page 35.
Note: Unit height and connection locations
will change if external vibration isolators are
used. The unit may be raised an additional
5-7/8 inches with spring-type isolators.
1.Verify the floor or foundation is level.
Shim or repair as necessary.To ensure
proper unit operation, install the unit
level (zero tolerance) in both horizontal
axis. Failure to level the unit properly
can result in condensate management
problems, such as standing water
inside the unit. Standing water and wet
surfaces inside units can result in
microbial growth (mold) in the drain
pan that may cause unpleasant odors
and serious health-related indoor air
quality problem.
Note: Unit height and connection locations
will change if the unit is constructed to be
split-a-part in the field. See unit submittal
drawings for connection locations.
6. Electrical supply power must meet
specific balance and voltage
requirements, as described in the
“Electrical Requirements” section on
page 33.
2. Allow minimum recommended
clearances for maintenance and
routine service. See “Service Access”
section on page 13.
7. Water-cooled units only (model
SCWG): The installer must furnish and
install a condenser main and standby
water pump, cooling tower, pressure
gauges and all components for the
waterside piping. See the “Water
Piping” section on page 30 for general
waterside recommendations.
3. Position the unit and skid assembly in
its final location. If unit shipped split-
apart, follow the procedure in the
“Split-Apart Unit Assembly” section
on page 16 before completing this
step.Test lift the unit to determine exact
unit balance and stability before
hoisting it to the installation location.
See Figure I-PC-7 and I-PC-8 on page 15
for typical rigging procedures,
8. Air-cooled units only (model SCRG):
These units require field-installation of a
remote air-cooled condenser and
refrigerant piping. See the “Refrigerant
Piping” section on page 32 for general
piping recommendations.
including cautions and proper uses of
such equipment as fork lifts, spreader
bars, and hooks.
4. Remove the skids from under the unit.
See the “Rigging and Handling”
section on page 14. Refer to the “Skid
Removal” section on page 18. If you
find internal damage, file a claim
immediately to the delivering carrier.
12
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-installation
considerations
Installation
ServiceAccess
Variable Frequency Drives are shipped
separately and field installed. See page 29
forVFD related dimensions and weights.
ƽWARNING
96” (2132 mm)
HazardousVoltage w/Capacitors!
Disconnect all electric power, including
remote disconnects before servicing.
Follow proper lockout/tagout proce-
dures to ensure the power cannot be
inadvertently energized. For variable
frequency drives or other energy storing
components provided byTrane or others,
refer to the appropriate manufacturer’s
literature for allowable waiting periods
for discharge of capacitors.Verify with an
appropriate voltmeter that all capacitors
have discharged. Failure to disconnect
power and discharge capacitors before
servicing could result in death or serious
injury.
TopView
CCRC/CIRC 20, 29, 32
48” (1066 mm)
48” (1066 mm)
Control
Panel
96” (2132 mm)
Note: For additional information regard-
ing the safe discharge of capacitors, see
PROD-SVB06A-EN or PROD-SVB06A-FR.
Table I-PC-1. Service and code clearance requirements
Side
front
left
Distance
42 in. (20-38 tons)
18 in.
36 in.
77 in.
Purpose
NEC code requirement
air-cooled units only
refrigeration & waterside component service
fan shaft removal
provides uniform airflow
provides uniform airflow
See Figure I-PC-2 andTable I-PC-1 for
recommended service and code
clearances. Access to thermostat unit
controls is through a hinged access panel
door on the front, lower left of the unit’s
compressor section.
right
inlet
36 in.
18 in.
IntelliPak unit controls access is through
a panel on the middle right of the fan
section. The panel is secured with an
automatic latch and quick-acting fasten-
ers, which require a screwdriver to open.
18” minimum
air inlet
Removable front unit panels provide
access to compressors, fan, motor, inlet
guide-vane actuator, and belts.
Removable left side panels give access to
drive side, fan bearing, inlet guide-vanes,
condensers, and waterside economizer
control valve.The compressor, con-
denser and fan motor access panels are
secured with quick-acting fasteners.
Access panels for evaporator coils,
expansion and water valves, and left fan
bearing are sheet metal screws. Access
to other components for service requires
removal of panels secured with sheet
metal screws. During operation, sight
glasses are viewable through portholes
on the upper right side panel of the fan
section.
36”minimum
See table
Control
Panel
42” minimum
Figure I-PC-2.Top view of self-contained unit showing recommended service and code clear-
ances
SCXG-SVX01B-EN
13
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-installation
considerations
Installation
Rigging and Unit Handling
ƽWARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to
verify proper center of gravity lift point.
To avoid dropping of unit, reposition
lifting point if unit is not level. Failure to
properly lift unit could result in death or
serious injury or possible equipment or
property-only damage.
ƽWARNING
Lifting Equipment Capacity!
Ensure lifting equipment capacity
exceeds unit weight by an adequate
safety factor to prevent injury, death, or
unit damage.
Figure I-PC-5.Assembled unit gravity block location.
Table I-PC-2. Gravity Block Dimensions
Before lifting the unit or modular
component, determine the approximate
center of gravity for lifting safety. See
Figure I-PC-5 for assembled modular
units and Figure I -PC-6 for split-apart
units. The center of gravity may vary
slightly within the gravity block
Model
A
B
C
D
SCWG
36
14
38
12
SCRG
36
16
40
12
Fan Section Only
depending on unit options.
Always test-lift the unit to determine the
exact unit balance and stability before
hoisting it to the installation location. See
Figures I-PC-7 and I-PC-8 for typical
rigging procedures and proper rigging
equipment usage.
Compressor Section Only
Figure I-PC-6. Split-apart unit gravity block location.
14
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-installation
considerations
Installation
Unit Handling Procedure
NOTICE
Do not use hooks to lift unit or hook into
open channels to lift unit. This could
cause unit damage.
1. Position rigging sling under wood
shipping skid.
2. Use spreader bars to avoid unit
damage.
3. When using a forklift, exercise caution
to prevent unit damage.
4. Use the standard fork length to lift one
end and drag or pull unit while skidding
the opposite end.
5. The unit center of gravity will fall within
center of gravity block at various
locations depending on unit options.
6. Use hooks to lift fan section only. Do not
hook into open channels to lift unit.
7. See unit nameplate for unit weight.
8. Do not stack units.
Figure I-PC-7.Assembled modular unit proper rigging.
Figure I-PC-8. Split-apart modular unit proper rigging.
SCXG-SVX01B-EN
15
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-installation
considerations
Installation
Split-Apart Unit Assembly
1. Ensure the tagging information on the
fan section nameplate matches that on
the compressor nameplate.
2. Remove the connector brackets
holding the the sheet metal shipping
cover on compressor section. Retain
brackets and screws.
3. Remove shipping cover from the
compressor section and verify the ship-
with packge contains:
12. Insulate discharge and suction lines
with the insulation provided.
13. Remove panel FLR and open the
bottom control panel door, FLL. Pull the
fan motor leads (coiled in the fan
section) through the knockout in the
bottom of the fan section to the control
panel. Ensure that the bushing is
installed in the hole to prevent the
wires from chafing. Refer to the unit
wiring diagrams to connect the fan
motor leads properly and ensure
correct phase sequencing.
• suction and discharge line couplings
• insulation
• sheet metal screws
4. Lift fan section onto the compressor
section using the rigging method in
Figure I-PC-8 on page 13.
5. Remove skid from the fan section,
placing the fan section onto the
compressor section. Reference Figure I-
PC-9.
6. Install the connection brackets with the
sheet metal screws (referenced in step
2) on all sides of the unit. Reference
Detail “A” in Figure I-PC-9.
IntelliPak Units(UCM) Only
14. Remove panels FML, FMM, and FMR.
15. Pull the circular plug connector (CPC)
from the compressor section through
the knockouts into the fan section.
Install the bushings (provided on the
wiring harnesses) in the knockouts.
16. Using the CPC wiring diagram,
connect the male CPC to the female
CPC in the top control panel.
17. If the unit has the mixed air
7. Remove the unit panels labeled RU and
RL in Figure I-PC-10 on page 17. To
remove panels, first remove the four
shipping screws located in the corner of
each panel. Next, turn the remaining 1/4
turn fasteners to the unlatch position.
The panel is supported by a “lip”
channel. So, lift the panel up and off the
unit to remove it. See Detail “A”in
Figure I-PC-9.
8. Connect the drain hose to the drainpan
outlet fitting and secure it with the drain
hose clamp provided.
9. Circulate nitrogen thoughout
refrigerant circuits.
temperature option, route the capillary
tube on back of the filter rack.
Units with Thermostat Only
18. Remove panel FMR. See Note 1 on
Figure I-PC-10.
19. Pull frost protection wires from the
bottom control panel throughknockouts
in bottom of fan section. Route wires to
the appropriate frost protection
switches on the evaporator coil.
Reference the unit wiring diagrams to
connect frost protection wiring
connectors.
10. Unbraze and remove the caps on the
discharge and suction lines in both the
compressor and fan sections.
11. Install and braze discharge and
suction line couplings.
Air-Cooled Units Only:
20. Route the refrigerant circuit wires for
circuits 1 and 2 from the bottom control
panel through the knockouts to the
solenoid valves. The solenoid valves
are located in the liquid refrigerant
lines on the right-hand side of the unit.
Refer to the unit wiring diagrams to
make splice connections.
16
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-installation
considerations
Installation
Figure I-PC-9 How to assemble the split apart modular unit
Figure I-PC-10 Modular unit panel description and internal connections
SCXG-SVX01B-EN
17
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-installation
considerations
Installation
view of Figure I-PC-9, must be 1/4 - 1/
inches.To increase the clearance, li2ft
the unit off the isolator and turn the
leveling bolt counterclockwise. Recheck
the unit level and the housing
clearances. Maximum allowable
difference between isolator heights is 1/4
inch. Shim as required under the
isolators.
Allow three fan diameters above the
unit for the discharge ductwork. Return
air enters the rear of the unit and
conditioned supply air discharges
through the top.
Electrical connection knockouts are on
the top, left side of the unit.
Allow adequate space for piping
access and panel removal. Condenser
water piping, refrigerant piping, and
condensate drain connections are on
the lower left end panel.
Skid Removal
The unit ships on skids to provide forklift
locations from the front or rear.The skid
allows easy maneuverability of the unit
during storage and transportation.
Remove the skids before placing the unit
in its permanent location.
Remove the skids using a forklift or jack.
Lift one end of the unit off of the skids.
See Figure I-PC-5 and I-PC-6 for unit
gravity block location. Slide the skids out
and lower the unit at the installation
location.
Note: The compressors and fan assembly
are internally isolated on most units. Due to
this, the addition of external isolation
devices (spring mounting isolators) is at
the discretion of the building or HVAC
system designer.
Note: Unit height and connection locations
will change if using vibration isolators. The
unit height may increase up to 5 7/8” with
spring type isolators.
Note: External isolation is not necessary
since units are internally isolated. Consult a
vibration specialist before “double-
isolating” the unit.
Electrical supply power must meet
specific balance and voltage
requirements as described in the
Pre-Installation Checklist
Complete the following checklist before
beginning unit installation.
External Unit Isolation
“Electrical Requirements” section.
Water-cooled units only: The installer
is responsible for providing a condenser
main, standby water pump, cooling
tower, pressure gauges, strainers, and
all components for waterside piping.
See the “Water Piping” section for
general waterside recommendations.
Air-cooled units only: The installer is
responsible for providing and installing
the remote air-cooled condenser and
refrigerant piping, including filter driers.
Verify the unit size and tagging with the
unit nameplate.
Make certain the floor or foundation is
level, solid, and sufficient to support the
unit and accessory weights. Level or
repair the floor before positioning the
unit if neccesary.
Allow minimum recommended
clearances for routine maintenance and
service. Refer to unit submittals for
dimensions.
If your job requires external vibration
isolation, two options are available:
isopads or spring-type isolators. Isopads
should be placed under the unit at
locations indicated on the factory-
provided isolator sheet.
Set the spring-type isolators (Figure I-PC-
9) in position after the unit is removed
from skids before making electrical,
piping, or duct connections. All units
require a minimum of four isolators per
unit. But some may require six isolators,
depending upon unit options.
Note: Trane strongly recommends you
consult a vibration specialist before
double-isolating the unit. Double isolation
is not recommended.
If you decide to externally isolate the unit,
use spring-flex, type CP isolators. The
spring number is marked on the outer
housing. See Figure I-PC-9.
To install external isolators, complete the
following procedure.
1. Locate the isolators under unit base at
the locations indicated on the factory-
provided isolator placement sheet. Lift
one end of the unit at a time to position
isolators to the floor, using anchor bolts.
2. Level the unit by adjusting isolator
heights. Unit weight may cause the
upper housing to rest on the lower
housing of the spring isolators. The
isolator clearance shown in the side
Figure I-PC-9. Optional spring isolator dimensional data.
18
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions & SCWG
Weights SIRG
SCWG/SIWG Dimensions, in.
front view
left-side view
factory-piped units
left-side view
direct condenser connections
SCWG/SIWG weight, lbs.
unit tons
20
base weight
2260
25
2730
30
2864
35
3000
Notes:
1. All unit weights include refrigerant, water, inlet guide
vanes and controllers, electric heat and valves.
2. Add 150 lbs. to total weight to obtain approximate
shipping weight.
3. Split-apart unit weights are approximately: 60% total
unit weight = compressor section, 40% total unit weight
= fan section.
top view
back view
right-side view
factory-piped units
right-side view
direct-condenser connections
SCXG-SVX01B-EN
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions & SCRG /
Weights SIRG
SCRG/SIRG Dimensions, in.
front view
left-side view
right-side view
top view
SCRG/SIRGWeight, lbs.
unit tons
20
25
base weight
2344
2479
2614
32
Notes:
1. All unit weights include refrigerant, water, inlet guide
vanes and controllers, electric heat and valves.
2. Add 150 lbs. to total weight to obtain approximate
shipping weight.
3. Split-apart unit weights are approximately: 60% total
unit weight = compressor section, 40% total unit weight
= fan section.
back view
20
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions &
Weights
SCRG/SIRG/SCWG/SIWG Detail “A”
Electrical Connections, in.
Detail “B” Discharge Options , in.
front view
shown with horizontal discharge option
top view
shown with vertical discharge option
Detail Dimensions, in.
model
A
20
B
C
D
E
F
3
1
1
1
1
SCWG/SCRG 20
SCWG/SCRG 25
SCWG 30 - 35/SCRG 32
11 1/2
10 /4 58 /2 5 /8
13 /4 11 /2
13 /4 11 /2
1
1
5
1
1
1
19 /4 12 /4 57 /8 5 /8
5
1
1
18
14
/
56 /2 5 1/8
13 /4
8
SCXG-SVX01B-EN
21
Download from Www.Somanuals.com. All Manuals Search And Download.
CCRC /
CIRC
Dimensions &
Weights
CCRC/CIRC —Air-Cooled Condenser
OPTIONAL LOW
AMBIENT DAMPER
ONE DAMPER PER
RCUIT)
REFRIGERANT
LINE
CONNECTIONS
FRONTAL VIEW
AC
REFRIGERANT CIRCUIT 2
REFRIGERANT CIRCUIT 1
OPTIONAL LOW
AMBIENT DAMPER
24VOLTWIRE ENTRY HOLE SIZED
3
4
FOR / ” CONDUIT
115VOLTWIRE ENTRY HOLE SIZED FOR
3
4
/ ” CONDUIT
SUPPLYVOLTAGEWIRE ENTRY HOLE
SIZED FOR 1” CONDUIT
(LIQUID LINE CONNECTION REFRIG. CIRCUIT 1)
(HOT GAS CONNECTION REFRIG. CIRCUIT 1)
(LIQUID LINE CONNECTION REFRIG. CIRCUIT 2)
(HOT GAS CONNECTION REFRIG. CIRCUIT 2)
B
C
CCRC/CIRC Air-cooled condenser dimensions & weight, in-lbs.
shipping
weight
2030
2084
2138
operating
weight
1906
1960
2014
model
AA
AB
88
88
88
AC
88
88
88
1
CCRC/CIRC Electrical connections, in.
CCRC/CIRC 20
CCRC/CIRC 29
CCRC/CIRC 32
70
/
8
1
1
70
/
8
model
A
B
C
1
CCRC/CIRC 20-32
4 1/2
10 1/2 17 /2
70
/
8
CCRC/CIRC Refrigerant connections, in.
model
CCRC/CIRC 20-32
E
F
G
H
J
K
L
M
N
7
3
1
3
5
5
66 /8 14 /8 18 /2 24 /4 29
/
8
1 1/8
/
8
1 1/8
22
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions &
Weights
HotWater Coil
Hot water coil dimensions & weight, in-lbs.
unit size
20 - 35 tons
A
B
C
D
E
F
G
H
5 /8
J
7 /4
weight
460
1
3
5
1
7
1
1
5
3
37 /4 53 /4 16 /8 73 /2 14 /8 16 /4 43 /4
SCXG-SVX01B-EN
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions &
Weights
Steam Coil
Steam coil dimensions, in-lbs.
unit size
A
B
C
D
E
K
L
M
N
1
P
41
Q
9 3/8
R
4 3/8
weight
460
1
3
5
1
1
7
20 - 35 tons 37 /4 53 /4 16 /8 73 /2 10 7/8 22 /2 3 3/8 15 /8
24
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions &
Weights
Electric Heat Coil
Electric heat coil dimensions & weight, in-lbs.
unit size
20 tons
25 tons
A
B
C
D
weight
460
460
1
7
1
70 /4
4 /8
4 1/8
2 7/8
11 /2
11 1/2
11 1/2
19
19
19
1
70 /4
1
30 - 35 tons
70 /4
460
Note: Coil box height is 8 in.
Flexible Horizontal Discharge
Plenum
Flexible horizontal discharge plenum dimensions & weights, in-lbs.
20-35 tons
low height
standard height
A
35
B
17 /
35
C
weight
262
1
1
4
2
86 /
1
1
4
2
25 /
86 /
352
SCXG-SVX01B-EN
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions &
Weights
Waterside Economizer
Waterside economizer weight, in-lbs.
weight
unit size
20 - 35 tons
2-row 4-row
488 584
26
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions &
Weights
Airside
Economizer
Airside Economizer
Airside economizer dimensions & weight, in-lbs.
unit size
A
36
B
65 /8
C
D
E
F (1) F (2) G (1) G (2) H (1) H (2)
J
K
L
M
weight
5
1
1
1
3
1
1
5
1
1
3
SCWG/SIWG 20, 25
SCRG/SIRG 20
SCWG/SIWG 30, 35
SCRG/SIRG 25, 32
37 74 /4 6 /8 56 /2 49 /4 23 /4 20 /2 5 /8
7
20 /2 17 /8
12 49 /4 273
36
65 /8
37 74 1/4 6 1/8 61 /8 62 /4 28 /8 20 /2 3 1/4
7
20 /2 17 /8
5 1/2 62 /4 273
5
3
3
1
1
1
1
3
Detail “A”
Detail “B”
SCXG-SVX01B-EN
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions &
Weights
VFD
Mounting Requirements
Variable Frequency Drive
Option (VFD)
There must be a minimum eight inch
clearance above and below theVFD. A
minimum two inch clearance is required
on each side.
Proper location of theVFD is important to
achieve proper performance and normal
operating life. Installation must be in an
area where it will be protected from:
• Direct sunlight, rain or moisture.
• Corrosive gases or liquids.
Also, allow enough clearance for opening
theVFD cabinet door.This will ensure
sufficient air space for cooling.
ƽWARNING
Control and LineVoltage!
•Vibration, airborne dust, or metallic
particles.
Control and line voltage wiring from the
VFD to the unit must be in accordance
with all local and National Electric Codes.
Do not touch circuit components until
main power has been turned off and
“charge” lamp is extinguished.The
capacitors are still charged and could
Refer to the “Dimensions andWeights”
section beginning on page 19 forVFD
dimensions and weights.
For effective cooling as well as proper
maintenance, install theVFD vertically to
the ground using four mounting screws.
result in death or serious injury.
ƽWARNING
A
HazardousVoltage w/Capacitors!
Disconnect all electric power, including
remote disconnects before servicing.
Follow proper lockout/tagout proce-
dures to ensure the power cannot be
inadvertently energized. For variable
frequency drives or other energy storing
components provided byTrane or others,
refer to the appropriate manufacturer’s
literature for allowable waiting periods
for discharge of capacitors.Verify with an
appropriate voltmeter that all capacitors
have discharged. Failure to disconnect
power and discharge capacitors before
servicing could result in death or serious
injury.
B
G
F
C
D
E
Note: For additional information regard-
ing the safe discharge of capacitors, see
PROD-SVB06A-EN or PROD-SVB06A-FR.
VFD dimensions, in.
NOTICE
Use Copper Conductors Only!
voltage
460
hp
A
B
C
D
E
F
G
7.5
10
15.55
15.12
7.87
8.66
0.39
0.24 7.87
Unit terminals are not designed to
accept other types of conductors. Failure
to use copper conductors may result in
equipment damage.
208
460
7.5
10
15
20
25
22.05
21.26
7.87
9.53
0.83
0.30 10.24
208
460
15
20
30
40
27.56
26.77
10.63
12.13
0.83
0.30 11.05
0.30 11.65
The variable frequency drive (VFD) option
can only be used with IntelliPak units.The
VFD andVFD w/bypass is available from
5 to 25 hp and is aTraneTR1. AllVFD’s are
pre-configured and run tested at the
factory prior to shipping.TheVFD is wall
mounted.
208
460
30
50
60
31.50
31.49
30.71
30.71
10.63
10.63
12.13
14.57
0.75
1.97
208
40
-
13.19
28
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions &
Weights
VFD
Electrical Installation Procedure
Variable Frequency Drive with Bypass
Refer to the National Electric Code,
section 310-16 for sizing wires 4B - 9B. All
other control wires should be twisted
shielded or twisted pair shielded, 20 - 14
AWG, with lead length not to exceed 164
feet. When using shielded wire, the shield
sheath must be connected at the VFD
only.The connection on units withVFD is
J13-S.The connection on unis withVFD/
bypass is ITBI-10.
C
A
B
F
D
E
G
H
VFD with bypass dimensions, in.
voltage
460
hp
A
B
C
D
E
F
G
H
7.5
10
30.40
28.03
16.14
23.35
24.85
0.75 8.59 10.63
208
7.5
10
15
20
15
20
25
41.28
38.89
16.14
24.00
25.5
0.75 10.95 12.99
460
208
25
50.81
48.35
21.36
31.61
33.41
0.90 12.36 14.41
SCXG-SVX01B-EN
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
Duct Connections
Water Piping
Note:The compressors and fan assembly are
internally isolated.Therefore, external isolation
devices (spring mounting isolators) are at the
discretion of a vibration specialist consulted
by the building or HVAC system designer.
ƽWARNING
ƽWARNING
Hazardous Voltage w/Capaci-
tors!
High PressureWater!
Provide relief valves on system water
piping to prevent instantaneous release
of high pressure water. Failure to provide
relief valves could result in death or
serious injury or water pump damage or
unit failure.
Run the ductwork straight from the
Disconnect all electric power, including
remote disconnects before servicing.
Follow proper lockout/tagout proce-
dures to ensure the power cannot be
inadvertently energized. For variable
frequency drives or other energy storing
components provided byTrane or others,
refer to the appropriate manufacturer’s
literature for allowable waiting periods
for discharge of capacitors.Verify with an
appropriate voltmeter that all capacitors
have discharged. Failure to disconnect
power and discharge capacitors before
servicing could result in death or serious
injury.
opening for a minimum of three fan
diameters. See Figure I-MR-1. Extend
remaining ductwork as far as possible
without changing size or direction. Do not
make abrupt turns or transitions near the
unit due to increased noise and excessive
static losses. Use elbows with splitters or
turning vanes to minimize static losses.
Condenser Connections
Condenser water piping knockouts are in
the lower left end panel. If necessary,
remove insulation to gain access. All field
installed piping must conform to
Poorly constructed turning vanes may
cause airflow generated noise. Align the
fan outlet properly with the ductwork to
decrease noise levels in the duct and to
increase fan performance. To complete
trunk ductwork to theVAV terminal units,
refer to theVAV box manuals for specific
requirements. Check total external static
pressures against fan characteristics to
be sure the required airflow is available
throughout the ductwork.
applicable local, state, and federal codes.
To complete condenser water
connections follow the procedure below.
Note: Four condenser waterline drain plugs
ship in a bag in the unit’s left end. The
installer must field install these four plugs
using pipe thread sealer. An additional plug
is provided for units with a waterside
economizer.
Note: For additional information regard-
ing the safe discharge of capacitors, see
PROD-SVB06A-EN or PROD-SVB06A-FR.
To achieve maximum acoustical perfor-
mance, minimize the duct static pressure
setpoint.
Return air enters the rear of the unit and
conditioned supply air discharges through
the top. Attach supply air ductwork
directly to the unit’s top panel, around the
fan discharge opening. A duct collar is not
provided.
1. Attach the water supply line to the inlet
connection, and the return line to the
outlet connection. Entering and leaving
water connections for all condensers
are factory manifolded and require only
single connections for entering and
leaving water. If the unit has a
waterside economizer and/or control
valves, the factory pipes between these
components.
2. If using a cooling tower, refer to Figure
I-MR-2 for a typical piping circuit from
the unit.
3. Ensure the water pressure to the unit
does not exceed 400 psig.
Note: Units equipped with the flexible
horizontal discharge plenum option may
include a duct collar when holes are factory
cut. If discharge openings are field-cut, refer
to the “Plenum Installation” section.
Discharge
Duct
3 Fan
Diameters
3-inch
Flexible
Duct
Install all air ducts according to the
National Fire Protection Association
standards for the “Installation of Air
Conditioning andVentilation Systems
other than ResidenceType (NFPA 90A)
and ResidenceTypeWarm Air Heating
and Air Conditioning Systems (NFPA
90B).
Return
Air
Note: To prevent water pump damage,
design system piping to provide relief
when using energy saving waterside
economizer valves.
Make duct connections to the unit with a
flexible material such as heavy canvas. If
a fire hazard exists,Trane recommends
using Flexweave 1000, type FW30 or
equivalent canvas. Use three inches for
the return duct and three inches for the
discharge duct. Keep the material loose to
absorb fan vibration.
Figure I-MR-1. Duct connection recommenda-
tions
30
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
Condensate Drain Connections
Waterside PipingArrangements
Install a condenser water pump between
the cooling tower (either open or closed)
and the self-contained unit. Lay out the
remainder of the system’s condenser
piping in reverse returns.This helps
balance the system by equalizing the
length of supply and return pipes.
Multistory buildings may use a direct
return system with balancing valves at
each floor.
Note: Unit does not have floor drains.
The condensate drain is internally
trapped. Condensate drain connections
are on the unit’s left side. Connect
condensate drain piping to the 1 1/4“ NPT
female fitting, using at least 7/8” OD
copper or 3/4“ OD iron pipe. Pitch the
condensate line downward a minimum
WaterTemperature Requirements
Do not allow the entering water
temperature to go below 54°F (12.2°C) on
units with constant water flow (basic
piping). This will cause the compressors
to shut down and the mechanical cooling
function will lockout. However, the
economizer (if enabled) will continue to
function.The compressors will reset
when the entering water temperature
reaches 58°F (15°C).
1
of /2” for each 10' of horizontal run, away
from the unit. Be sure to install the
condensate drain “P” trap drain plug.
Before starting the unit, fill the trap with
water to prevent negative pressure in the
fan section from impeding condensate
flow.To facilitate drain pipe cleaning,
install plugged tees in place of
Install the supply riser and its return in
close proximity. Furnish both with
permanent thermometers to check the
waterside balance during start-up and
routine maintenance checks.
Units with variable water flow
(intremediate piping) have a modulating
condensing pressure control valve that
allows compressor operation down to
entering water temperatures of 35°F
(2°C).
90°elbows.
Also, include strainers at each pump inlet
and unit. Install drain valves at the riser’s
base to allow drainage points for system
flushing during start-up and routine
maintenance. For condenser draining
and header removal, include a shutoff/
balancing valve on the entering and
leaving waterside pipes, drain tees, and
unions of each unit. Also, install a shutoff
valve on the unit entering water pipe for
condenser draining.
General Waterside Recommendations:
Cooling Towers
Cooling tower control affects the unit
cycle rates. Condenser water
temperature swings from 10-15°F may
cause excessive compressor, water
valve, and unit cycling. Be sure to set the
tower controls to minimize compressor/
unit cycling.
For more information on constant and
variable water flow, see the Sequence of
Operation section of this manual.
Note: Units with a waterside economizer
can be set from the human interface panel
for variable or constant water flow.
Table I-MR-1. Water Connection Sizes.
Unit Size
SCWG 20-35
Direct Condenser
1-1/2 NPT
Factory Piped
2-1/2 NPT
Figure I-MR-2. Condenser water piping components for cooling tower system
Figure I-MR-3. Direct condenser connections.
SCXG-SVX01B-EN
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
Refrigerant Piping (Air-Cooled
Units Only)
See the “Startup” section of this manual
for instructions on refrigerant evacuation,
charging, and superheat measurement.
Leak-test the entire refrigeration system
after all piping is complete.
1.When heating copper in the presence
of air, copper oxide forms.To prevent
copper oxide from forming inside the
tubing during brazing, sweep an inert
gas, such as dry nitrogen, through the
tubing. A nitrogen flow of 6 to 10 cubic
feet per hour is sufficient to displace the
air in the tubing and prevent oxidation
of the interior surfaces. Use a pressure
regulating valve or flow meter to
control the flow.
2. Ensure that the tubing surfaces
requiring brazing are clean, and that the
tube ends are carefully reamed to
remove any burrs.
3. Make sure the inner and outer tubes of
the joint are symmetrical and have a
close clearance, providing an easy ‘slip’
fit. If the joint is too loose, the
connection’s tensile strength is
significantly reduced. Ensure the
overlap distance is equal to the inner
tube diameter.
4. Wrap each refrigerant line component
with a wet cloth to keep it cool during
brazing. Excessive heat can damage
the internal components.
5. If using flux, apply it sparingly to the
joint. Excess flux will contaminate the
refrigerant system.
6. Apply heat evenly over the length and
circumference of the joint.
7. Begin brazing when the joint is hot
enough to melt the brazing rod. The hot
copper tubing, not the flame, should
melt the rod.
8. Continue to apply heat evenly around
the joint circumference until the brazing
material is drawn into the joint by
capillary action, making a mechanically
sound and gas-tight connection.
9. Visually inspect the connection after
brazing to locate any pinholes or
crevices in the joint. Use a mirror if joint
locations are difficult to see.
LeakTest (RemoteAir-cooled Units Only)
Units ship with a holding charge of dry
nitrogen. Before installing the unit
refrigerant piping, momentarily depress
either the suction or discharge line access
valve to verify the holding charge has not
been lost. If no nitrogen escapes the
access valve, leak-test the entire
refrigerant system to determine the leak
source. Use a halogen leak detector, a
halide torch, or soap bubbles to leak test.
After finding a leak, remove the test
pressure and repair the leak. Retest the
unit to ensure all leaks are repaired.
Brazing Procedures
Proper brazing techniques are essential
when installing refrigerant piping. The
following factors should be kept in mind
when forming sweat connections:
ƽWARNING
Hazard of Explosion and Deadly
Gases
Never solder, braze or weld on refriger-
ant lines or any unit components that are
above atmospheric pressure or where
refrigerant may be present.Always
remove refrigerant by following the
guidelines established by the EPA Federal
CleanAirAct or other state or local
codes as appropriate.After refrigerant
removal, use dry nitrogen to bring
system back to atmospheric pressure
before opening system for repairs.
Mixtures of refrigerants and air under
pressure may become combustible in
the presence of an ignition source
leading to an explosion. Excessive heat
from soldering, brazing or welding with
refrigerant vapors present can form
highly toxic gases and extremely
10. ReferenceTables M-MP-6 and M-MP-
7 for the correct amount of refrigerant
required for charging the unit.
corrosive acids. Failure to follow all
proper safe refrigerant handling practices
could result in death or serious injury.
32
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Requirements
requirements.
Control Power
UnitWiring Diagrams
Bring supply wiring through the knockout
in the lower left side of the unit control
panel. Connect the three phase wires to
the power terminal block or the non-
fused disconnect switch in the control box
terminals. Refer to specific wiring
diagrams and fuse information in the
unit’s control panel.
NOTICE
Component Failures!
ƽWARNING
Live Electrical Components!
Unit transformers IT1, IT3, 1T4, and IT5
are sized to provide power to the unit
only. Do not use these transformers to
supply power to field equipment. Field
connections to these transformers may
create immediate or premature compo-
nent failures.
During installation, testing, servicing and
troubleshooting of this product, it may be
necessary to work with live electrical
components. Have a qualified licensed
electrician or other individual who has
been properly trained in handling live
electrical components perform these
tasks. Failure to follow all electrical
safety precautions when exposed to live
electrical components could result in
death or serious injury.
NOTICE
Use Copper Conductors Only!
Unit terminals are not designed to
accept other type conductors. Failure to
use copper conductors may result in
equipment damage.
In this example, 2.2% imbalance is not
acceptable.Whenever a voltage
imbalance of more than 2.0% exists,
check the voltage at the unit disconnect
switch. If the imbalance at the unit
disconnect switch does not exceed 2.0%,
faulty unit wiring is causing the
Specific unit wiring diagrams are
provided on the inside of the control
panel door. Use these diagrams for
connections or trouble analysis.
NOTICE
Equipment Damage!
imbalance. Conduct a thorough
inspection of the unit electrical wiring
connections to locate the fault, and make
any repairs necessary.
Correct phase sequence is critical. If
phase sequence of the incoming line
voltage is not correct, it may result in
motor damage.
Supply PowerWiring
Access the connection terminal block
through the control panel on the unit’s
upper left side. All wiring should conform
to NEC and applicable local code require-
ments.
ƽWARNING
Voltage Range
HazardousVoltage w/Capacitors!
Voltages must be within +- 10% the
nameplate voltage. Ensure the unit
voltage is balanced by measuring at the
compressor terminals.Voltage imbalance
on three phase systems can cause motor
overheating and premature failure.
Maximum allowable imbalance is 2.0%.
Disconnect all electric power, including
remote disconnects before servicing.
Follow proper lockout/tagout proce-
dures to ensure the power cannot be
inadvertently energized. For variable
frequency drives or other energy storing
components provided byTrane or others,
refer to the appropriate manufacturer’s
literature for allowable waiting periods
for discharge of capacitors.Verify with an
appropriate voltmeter that all capacitors
have discharged. Failure to disconnect
power and discharge capacitors before
servicing could result in death or serious
injury.
Be sure all wiring connections are secure.
Reference the unit specific diagrams
inside the control panel.
Voltage Imbalance
Read the voltage at the compressor
terminals to determine if it is balanced.
Voltage imbalance on three phase
systems can cause motor overheating
and premature failure.The maximum
allowable imbalance is 2.0%.Voltage
imbalance is defined as 100 times the
sum of the deviation of the three voltages
from the average (without regard to sign)
divided by the average voltage. For
example, if the three measured voltages
are 221, 230, and 227, the average voltage
would be:
Note: For additional information regard-
ing the safe discharge of capacitors, see
PROD-SVB06A-EN or PROD-SVB06A-FR.
(221 + 230 + 227) = 226 volts
It is the installer’s responsibility to
provide power supply wiring to the unit
terminal block or the non-fused
3
The percentage of voltage imbalance is
then:
disconnect switch option.Wiring should
conform to NEC and all applicable code
100 * (226-221) = 2.2%
226
SCXG-SVX01B-EN
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Requirements
Selection Procedures
Table ED-1. Number of Compressors per Unit
RLA = rated load amps
SCWG/SIWG 20
SCRG/SIRG 20
25
30
25
1
35
32
-
Compressor LRA = locked rotor amps
Fan motor LRA = locked rotor amps,
N.E.C. table 430 - 150
10HP
2
-
2
-
15HP
1
2
FLA = full load amps, N.E.C.
Table 430 - 150
Table ED-2. SCWG/SIWG Compressor Motor Data
200V
460V
575V
575V
Voltage utilization range is 10%
HP
10
15
RLA
33.1
46.9
LRA
269
409
RLA
14.4
20.4
LRA
117
178
RLA
11.5
16.4
LRA
94
143
Determination of minimum circuit
ampacity (MCA).
MCA = 1.25 x largest motor amps/VFD
amps (FLA or RLA) + the sum of the
remaining motor amps.
Table ED-3. SCRG/SIRG Compressor Motor Data
200V
460V
Determination of maximum fuse size
(MFS) and maximum circuit breaker size
(MCB).
MFS and MCB = 2.25 x largest motor
amps (FLA or RLA) + the sum of the
remaining motor amps.
HP
10
15
RLA
38.4
55.0
LRA
269
409
RLA
16.7
24.1
LRA
117
178
RLA
13.4
19.1
LRA
94
143
Table ED-4. Fan without VFD
For units with the dual power option,
there are two electrical circuits that need
calculations using the formulas above:
circuit #1 - fans
200V
460V
575V
HP
5
FLA
LRA
FLA
LRA
FLA
5.4
8.2
11.4
16.2
20.0
24.2
LRA
16.1
25.0
32.9
44.8
61.0
74.0
105
152
193
290
373
469
6.7
10.8
14.2
20.3
25.0
31.0
46
37
7.5
10
15
20
25
66
54
84
66
126
162
204
102
132
162
circuit #2 - compressors
If the rating value determined does not
equal a standard current rating of over
current protective device, use the next
lower standard rating for the marked
maximum rating.
Table ED-5. Fan with VFD
200V
460V
HP
7.5
10
15
20
25
FLA
LRA
FLA
10.6
14.2
21.0
27.6
34.0
LRA
66
84
126
162
204
13.8
32.2
48.3
61.9
78.2
152
193
290
373
469
Note:Values are at the maximumVFD input rating and not the reduced motor values.
Table ED-6. Electric Heat - Single Stage
SCWG/SIWG
SCRG/SIRG
Heat
Kw
16
20
24
26
200V
Amps
44.8
55.6
66.8
72.4
78
460V
Amps
19.6
24.2
29.0
31.6
Size
20
25
30
-
Size
20
25
-
32
-
35
28
34.0
Note: Electric heat amperage should not be considered when determining minimum circuit ampacity.The current of the
unit in the heating mode will not exceed the current of the unit in the cooling mode.
Table ED-7. CCRC/CIRC Condenser Electrical Data
Unit Size
Tons
20, 29, 32
Rated
Voltage
200
MFS/
MCB
20
# Fans
FLA (ea.)
4.1
LRA (ea.)
20.7
MCA
17.4
17.4
7.7
4
4
4
4
230
4.1
20.7
20
460
575
1.8
1.4
9.0
7.2
15
15
6.0
Note: All motors for CCRC/CIRC units are rated at 1 hp (.7457 kW).
34
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-startup
requirements
Installation
Pre-Startup Procedures
Supply Fan Isolators
Unit Protective Covers
Remove the shipping channels and
mounting bolts from beneath the fan. See
Figure I-PR-1. Open both fan
Remove the shipping protection
coverings from the human interface
panel (HI) at the control panel, the filter
box (or air inlet opening), the discharge
air opening, and optional variable
frequency drive (VFD).
ƽWARNING
compartment access doors to access the
channels. There are four mounting points
for 20-38 ton units and six mounting
points for 40-80 ton units. See Fig I-PR-2.
HazardousVoltage w/Capacitors!
Disconnect all electric power, including
remote disconnects before servicing.
Follow proper lockout/tagout proce-
dures to ensure the power cannot be
inadvertently energized. For variable
frequency drives or other energy storing
components provided byTrane or others,
refer to the appropriate manufacturer’s
literature for allowable waiting periods
for discharge of capacitors.Verify with an
appropriate voltmeter that all capacitors
have discharged. Failure to disconnect
power and discharge capacitors before
servicing could result in death or serious
injury.
Compressor Isolators
Loosen compressor isolator mounting
bolts and remove shipping bracket from
beneath the compressor feet. Retighten
isolator mounting bolts.Torque to 18 ft.
lbs. (+ 2 ft. Lbs.)
Note: For 20-38 ton units, do not remove the
fan assembly shipping blocks and tie down
bolts if the fan speed is 750 rpm or less.
While keeping the fan mounting frame
level, turn the fan isolator height adjusting
bolts until the fan housing P-gasket
compresses 1/4” against the roof transi-
tion piece. See Figure I-PR-1.
Note: For additional information regard-
ing the safe discharge of capacitors, see
PROD-SVB06A-EN or PROD-SVB06A-FR.
Before starting up units perform the
following procedures to ensure proper
unit operation.
Figure I-PR-1. Supply fan horizontal isolation
shipping bracket.
Figure I-PR-2. Fan isolator locations.
SCXG-SVX01B-EN
35
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-startup
requirements
Installation
Plenum BottomView
Dashed line indicates correct insulation placement.
Figure I-PR-3. Correct plenum insulation placement
Plenum
Before installing the plenum attach the
insulation strip that ships with the plenum.
See Figure I-PR-3 for proper insulation
location. Align the plenum front with the
control panel side of the unit. Using the
strips and screws provided, secure the
plenum to the unit.
Treat field-cut holes to prevent fiberglass
from entering the airstream.
Note: Plenum insulation must be applied
properly to prevent air bypass around the
plenum. See Figure I-PR-3.
36
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-startup
requirements
Installation
Airside Economizer
Installation
Note: Airside economizer option available on
20-80 tons only.
Unit Handling
1. Hoist the damper cabinet to the
installation location with straps
positioned under the skid as shown in
Figure I-PR-4. Use spreader bars to
prevent unit damage during lifting.
2. With the damper cabinet at its final
location (near the unit), remove the
screws securing it to the skid from the
side flanges. Retain these screws for
later use.
Figure I-PR-4. Proper lifting of the airside economizer
Unit Preparation
3. The support legs are secured to the
skid, and the hanging bracket is secured
with wire ties to an inside flange near
the cabinet’s base. Remove the C-
channel collar and install it on the unit, if
not already installed.
o’clock, and secure it with screws
provided. See Figure I-PR-5.
10. Lift the damper cabinet and position it
such that the hanging bracket is
positioned over the unit’s C-channel
collar.
11. Lower the damper cabinet until the
holes in its side flanges are aligned with
the holes in the C-channel collar. Install
screws removed in step 3 through the
damper cabinet’s side flanges and into
the C-channel’s corresponding holes.
12. Attach ductwork to the top and back
dampers according to local codes.
14. Cabinets with TRAQ dampers only:
Unroll the two rolls of pneumatic tubing
located inside the damper cabinet.
Route these tubes through the cabinet’s
front upper panel (0.25 dia. holes
provided). Connect them to the two
pneumatic tubes protruding from the
customer electrical connection panel on
the unit. Be sure to connect like tubes to
each other (black to black, white stripe
to white stripe).
4. Remove the roll of 1/8” thick gasket
from the damper cabinet’sW-supports,
and apply it to the C-channel collar
mounted on the rear of the unit. This
gasket will provide a seal between the
damper cabinet and the unit.
15. Cabinets with TRAQ dampers only:
Locate the “bullet” sensor and rolled up
wiring in the unit’s filter section. Route it
into the damper cabinet and insert the
sensor into the sensor mounting clip
attached to underside of one of theTraq
dampers.
5. Attach the legs (with screws provided)
to the leg brackets located on the
damper’s base.
Field Wiring Connections
6. Attach a field-provided clevis of
suitable strength ( > 1/2” ), to each of the
13. Open the damper cabinet’s door and
connect the factory-provided plug from
the actuator to the factory-provided
plug in the unit’s filter section.
corner lifting brackets through the
7
/8” diameter holes.
7. Attach to the clevises a means of lifting
the damper cabinet from its skid.
Unit Installation
8. Slowly raise the damper cabinet from
its skid.
9. Attach the hanging bracket across the
front of the damper cabinet. Position it
with its short flange pointing to four
Airside
Economizer
Figure I-PR-5. Proper installation of the airside economizer option
SCXG-SVX01B-EN
37
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-startup
requirements
Installation
Static PressureTransducer
Installation (VAV units only)
Installing theTransducer
Complete the following procedure to
properly install the inlet guide vane static
pressure transducer.
Supply air static pressure controls the
inlet guide vane and inverter options. A
static pressure head assembly ships
separate in the control panel for field
installation in the supply air duct work.
The installer is responsible for providing
pneumatic tubing.
1. Mount the pressure sensing head
assembly in the duct so that the sensing
tip is in the middle of the duct so that it
will provide a proper pressure
measurement. See Figure I-PR-6.
2. Connect the pneumatic tubing from the
sensing head to the push-on tubing
connection in the control panel. Use a
plastic static pickup tubing. Do not
exceed 250 feet for 1/4“ OD tubing or
500 feet for 3/8” OD tubing.
Transducer Location
Place the head assembly in an area of the
ductwork that will provide an average
and evenly distributed airflow pattern.
Use the following guidelines to determine
an appropriate installation location.
The transducer inside the control panel
picks up low side or reference pressure.
1. Locate the static head assembly about
2/3 to 3/4 of the way down the longest
duct run, in an area approximately 10
duct diameters downstream and 2 duct
diameters upstream of any major
interferences, turns, or changes in duct
diameter.
Note: If plastic tubing pulls away from a
connection, trim it back before replacing it
on the fitting. Stretched tubing may leak
and cause faulty control.
2. When installing pneumatic tubing
between the head assembly and
transducer in the control panel, do not
exceed 250 feet for 1/4” OD tubing or
500 feet for 3/8” OD tubing.
Figure I-PR-6. Static pressure sensor installation
38
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-startup
requirements
Installation
Waterside Economizer
Installation Procedure
1. Loosen and pull all end devices that go
throught the bushing on the filter rack
(upper right corner of rack).
6. Align economizer holes with the holes
in the unit channel. Install screws in the
top (6x) and bottom (6x) of the
economizer.
7. Remove the unit’s rear middle panel
and unbraze the two copper pipes in
the 2 5/ ” water pipe. Do not remove
the pip8e outlet blockoff panel.
8. Remove the economizer tubing
assemblies from the shipping box.
Check ship-separate parts against
those shown in Figures I-PR-8, I-PR-9, I-
PR-10, and I-PR-11. Face the front of the
unit to see which side the water pipe
exits to determine if the unit has either
right or left-hand piping.
9. Assemble tubing as shown in Figure I-
PR-8 or I-PR-11.Tack all tubes in place
before brazing to ensure proper fit-up.
For right-hand piped units, install the
ball valve actuator assembly and
actuator as shown in Figure I-PR-10.
Refer to the unit wiring diagram for
wiring connection points.
2. Remove the filter rack from the back of
the unit by removing the 1/4” hex head
screws from the top and bottom of the
filter rack assembly.The filter rack
assembly will hang on the unit when
the screws are removed. Remove the
filter rack by lifting it up off the unit.
3. Remove the economizer from the
crate and position it behind the unit with
the headers on the left side, when
facing the back of the unit. Remove the
plastic envelope that is taped to the
economizer box assembly.This
envelope contains the gasket that must
be installed onto the vertical side
flanges of the box.
4. Install the pressure sensitive gasket to
the unit side of the vertical flange on
the economizer box.
5. Hang the economizer on the unit as
shown in Figure I-PR-7. Lift the
economizer by using the holes
10. Install the pipe insulation on all pipe
line to prevent sweating
11. Install the rear panels.
12. Re-install the filter rack on the back of
the economizer coil box and affix with
screws provided.
provided in the top panel of the
economizer.
SCXG-SVX01B-EN
39
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-startup
requirements
Installation
Waterside Economizer with left-hand
factory piping components
Figure
Item Part Description
Waterside Economizer Ship-Separate Parts List
A
B
C
D
E
F
Assembly #1
Assembly #2
Assembly #3
Assembly #4
Tube; 2 5/8” x 16 7/8”
Tube; 2 5/8” x 22 5/8
Factory
Piping
Left-Hand
Item Part #
Qty.
Description
4001
2
5
1
1
1
Tube; 2 5/8” x 9”
X17110026250
4003
4740
Elbow; 2 5/8” x 2 5/8”
Tube; 2 5/8” x 26 1/8”
Tube; 2 5/8” x 33 1/2”
*Tube; 2 5/8” x 14 7/8”
Figure I-PR-8. Detail view of ship-separate
tubing assemblies for waterside econo-
mizer left-hand piping
4009
X21040098390
X21080406110
X16120203570
X17150027060
X17170031210
4738
4007
X45000032020
4006
10 ft. *Gasket
1
1
1
1
1
1
*Insulation; 2 5/8” Rubatex
Plug; 1 1/2” Brass
Bushing; 2 1/2” ftg. x 1 1/2”
Tee; 2 5/8” x 2 1/8” x 2 5/8”
*Tube; 2 5/8” x 19 3/4”
Tube; 2 5/8” x 14 1/2”
1 roll Tape, 1.5’ wide
1
Tube; 2 5/8” x 19 15/16”
40
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-startup
requirements
Installation
Waterside Economizer with right-hand
factory piping components
Waterside Economizer Ship-Separate Parts List
Factory
Piping
Item Part #
Qty.
Description
Right-Hand
4001
4607
X17110026250
4605
X15330177010
4008
X17170031210
X16120203570
X17150027060
4007
4031
4603
1
Tube; 2 5/8” x 9”
Tube; 2 5/8” x 17”
1
5
2
1
1
1
1
1
1
1
1
1
1
Elbow; 2 5/8” x 2 5/8”
Tube; 2 5/8” x 9 1/2”
WaterValve
*Tube; 2 5/8” x 20 1/4”
Tee; 2 5/8” x 2 1/8” x 2 5/8”
Brass Plug, 1 1/2”
Bushing; 2 1/8” ftg. x 1 1/2”
Tube; 2 5/8” x 14 1/2”
Tube; 2 5/8” x 62
*Tube; 2 5/8” x 11 3/ ”
Tube; 2 5/8” x 19 1/44”
*Actuator with wires
*90 Degree Conduit Fitting
*1/2” Conduit
4006
X13610256010
X19110028040
X19110028040
X210804060110
X45000032020
X21040098390
2
3 ft.
14 ft.
1 roll
10 ft.
*Rubatex Insulation, 2 5/8”
Tape, 1.5’ wide
*Gasket
Item Part Description
A
B
C
D
E
Assembly #1
Assembly #2
Assembly #3
Assembly #4
Tube; 2 5/8” x 11 3/4”
Tube; 2 5/8” x 20 1/4”
Actuator Assembly
F
G
Figure I-PR-10.Waterside economizer with right-hand factory piping tubing assembly.
Figure I-PR-11. Detail view of ship-separate tubing assemblies for waterside economizer right-hand factory piping.
SCXG-SVX01B-EN
41
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-startup
requirements
Installation
Hydronic Coil Installation
mounting screws needed to attach the
coil box to the unit and the gasket
required on the vertical side flanges of
the box.
3. Install the pressure sensitive gasket to
the unit side of the vertical flange on the
coil box in two places.
These instructions are for steam and hot
water coil installation. The hydronic coil
assembly has a full coil, piping, a modu-
lating temperature control valve, and a
disc temperature limit device located in
the unit near the fan on the motor frame.
Hydronic coils are available with either
right or left-hand pipe connections. Piping
connections are identical to the unit
piping. For example, if you have right-
hand unit piping, the hydronic coil will
have right-hand connections. The
4. Using 2” x 1/2” standard thread
eyebolts, thread into the coil lift plates
to raise the coil up to the height
necessary to attach it to the unit.The top
panel has a “J” hook on it to allow
hanging, similar to the filter rack. Align
the holes so that the coil hangs on the
unit. If the unit has the dirty filter option,
connect the static pressure tube to the
unit before bolting the coil in place.
Locate the static pressure tubing on the
unit evaporator coil and route through
the knockout in the top corner of the
coil box.
hydronic coil assembly has temperature
controls to keep the unit’s internal cabinet
temperature below 105 F to prevent
motor and bearing damage.
Installation Procedure
5. Align the hydronic coil with the holes in
the unit channel or waterside
economizer option. Move the coil box
up against the unit and install using six
mounting screws in the top and six in
the bottom of the coil box.
6. Remove the valve and pipe cover on
the coil box. Connect the wires that are
coiled in the coil box, referring to the
wiring diagram installed on the unit
control panel door. Route wires into the
unit through knockouts in the top of the
box.
7. Reinstall the filter rack on the back of
the heating coil rack. If the unit has the
waterside economizer option, the filter
rack will require additional support legs.
ƽWARNING
Unit Structural Integrity!
Unit panels provide structural integrity.
Do not remove more than two non-
adjacent panels at one time as this could
cause the plenum frame to collapse.
Failure to follow these recommendations
could result in death, serious injury or
equipment damage.
1. Remove filter rack from the back of the
unit. Remove the 1/4-inch hex head
screws from the top and bottom of the
filter rack assembly.The filter rack
assembly will hang on the unit when
the screws are removed. The filter rack
can now be removed by lifting up on
the filter rack.
2. Remove the hydronic coil from the
crate and position it behind the unit with
the open side facing the unit evaporator
coil inlet. Also, remove the plastic
envelope that is taped to the coil box
assembly.This envelope contains the
42
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-startup
requirements
Installation
Electric Heat Installation
vertical discharge unit, position the
electric heater as shown in Figure I-PR-
12.
4. Use the hole pattern in the electric heat
as a template for marking and drilling
3/16” diameter holes in the unit.
5. Bolt the electric heaters to the unit
using 1/4” sheetmetal screws.
Follow proper lockout/tagout proce-
dures to ensure the power cannot be
inadvertently energized. For variable
frequency drives or other energy storing
components provided byTrane or others,
refer to the appropriate manufacturer’s
literature for allowable waiting periods
for discharge of capacitors.Verify with an
appropriate voltmeter that all capacitors
have discharged. Failure to disconnect
power and discharge capacitors before
servicing could result in death or serious
injury.
The electric heat option consists of a
single stage heater and is used in
IntelliPak units or units with a field-
installed thermostat. The electric heater
ships separate for field installation and
wiring. Available heater kW per unit size
is listed inTable I-PR-2. Electric heat can
be installed on units with a vertical
discharge. However, it cannot be installed
on units with plenums. See Figure I-PR-12
andTable I-PR-3 for electric heat dimen-
sional data.
Note: It is very important that electric heaters
are selected based on unit voltage and
tonnage because discharge opening sizes vary
by unit tonnage.
Electric Heat CoilWiring Procedure
Table I-PR-2.Available Electric Heat kW
Note: For additional information regard-
ing the safe discharge of capacitors, see
PROD-SVB06A-EN or PROD-SVB06A-FR.
Unit Size
20 Tons
25 Tons
30 Tons
32 Tons
35 Tons
Heater kW
16
20
24
26
28
NOTICE
Use Copper Conductors Only!
1. Before wiring the electric heater,
remove the unit wiring diagram from
the unit control panel and refer to the
connection points.
Unit terminals are not designed to
accept other type conductors. Failure to
use copper conductors may result in
equipment damage.
Installation Procedure
1. Remove the fan discharge shipping
covers, if they have not already been
removed.
ƽWARNING
2. Install the open-cell gasket around the
discharge opening on the heater.
3. Position the electric heater so that the
unit fan discharge openings line up with
the electric heater openings. For a
HazardousVoltage w/Capacitors!
Disconnect all electric power, including
remote disconnects before servicing.
Figure I-PR-12. Electric heater dimensions.
Table I-PR-3. Electric Heat Dimensions - English - (inches)
Unit Size
20 Tons
25 Tons
B1
B2
15 /8
15 /8
15 /8
Z
27 /4
26 /4
23 /4
5
3
10 3/4
Figure I-PR-12.Vertical discharge electric heat
installation.
1
5
3
12 /4
14 /4
3
5
3
30, 32, 35Tons
SCXG-SVX01B-EN
43
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-startup
requirements
Installation
Standard with All IntelliPak
Units
Zone Sensor Options for IntelliPak Control Units
Zone sensor options are available and be ordered with the unit or after the unit ships.
Following is a full description of zone sensors and their functions. Installation
instructions are on page 34. Programming instructions for the programmable zone
sensor are on page 36. Refer toTable O-GI-2 on page 61 for the zone sensor
temperature vs. resistance coefficient curve.
BAYSENS077* Description
This zone sensor module ships with all units, and can be used with BAYSENS019,
BAYSENS020, or BAYSENS021 remote sensors.When this sensor is wired to one of
these remote zone sensors, wiring must be 18 AWG shielded twisted pair (Belden 8760
or equivalent). Refer to the specific zone sensor for wiring details. It provides the
following features and system control functions:
• Remote temperature sensing in the zone
• Morning warmup sensor
• Zone sensor for ICS™ systems
• Zone temperature averaging
Figure I-PR-7. BAYSENS077
zone temperature sensor only
When used as a remote sensor for standard zone sensor, the thermistor sensor must
be disabled.
(Possible Schematic Designation(s): 5U23, 5U26, 5U30, and 5RT5.)
CV Unit Zone Sensor Options
BAYSENS108 & BAYSENS110 Description
These zone sensor modules are for use with cooling/heating constant volume units.
They have four system switch settings (heat, cool, auto, and off) and two fan settings
(on and auto).The zone sensor provides either manual or automatic chaneover control
with dual setpoint capability.
BAYSENS108 and BAYSENS110 features and system control functions include:
• System control switch to select heating mode (HEAT), cooling mode (COOL),
automatic selection of heating or cooling as required (AUTO), or to turn the
system off (OFF).
• Fan control switch to select automatic fan operation while actively heating
or cooling (AUTO), or continuous fan operation (ON).
• Dual temperature setpoint levers for setting desired temperature. The blue
lever controls cooling, and the red lever controls heating.
•Thermometer to indicate temperature in the zone.This indicator is factory
calibrated.
Figure I-PR-8. BAYSENS108
Dual setpoint, manual/automatic
changeover sensor, accessory model
number digit 6 = E
(Possible Schematic Designation: 5U29)
BAYSENS110-Specific Feature: Function status indicator lights:
• SYSTEM ON glows continuously during normal operation, or blinks if
system is in test mode.
• COOL glows continuously during cooling cycles, or blinks to indicate a
cooling system failure.
• HEAT glows continuously during heating cycles, or blinks to indicate a
heating system failure.
• SERVICE blinks or glows to indicate a problem. These signals vary
depending on the particular equipment being used.
(Possible Schematic Designation: 5U29)
Figure I-PR-10. BAYSENS110
Dual setpoint, manual/automatic changeover
sensor with system function lights, acces-
sory model number digit 6 = F
44
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-startup
requirements
Installation
CV andVAV Unit Zone Sensor Integrated Comfort™ Systems Sensors for CV andVAV
Options
Applications
These zone sensor options are for use with cooling/heating Integrated Comfort System
(ICS) systems.
BAYSENS074 Description
This electronic analog sensor features single setpoint capability and timed override
with override cancellation.
BAYSENS074 features and system control functions include:
• Remote temperature sensing in the zone
• A timed override button to move an ICS or a building management system from its
“unoccupied” to “occupied” mode.
• Thumbwheel for local setpoint adjustment
• A cancel button to cancel the “unoccupied override” command.
Figure I-PR-11. BAYSENS074
Zone temperature sensor w/timed override
and local setpoint adjustment,
(Possible Schematic Designation: 5U23)
accessory model number digit 6 = C
BAYSENS073 Description
This electronic analog sensor features single setpoint capability and timed override
with override cancellation. It is used with aTrane Integrated Comfort system.
BAYSENS073 features and system control functions include:
• Remote temperature sensing in the zone
• A timed override button to move an ICS or a building management system from its
“unoccupied” to “occupied” mode.
• Cancel button to cancel the “unoccupied override” mode.
(Possible Schematic Designation: 5U23)
Figure I-PR-12. BAYSENS073
Zone temperature sensor w/timed override ,
accessory model number digit 6 = B
VAV Unit Zone Sensor Option
BAYSENS021 Description
This zone sensor module is for use withVAV units without night setback. It allows the
user to control system operation and monitor unit operating status from a remote
location.The sensor has a system switch, a S/A temperature setpoint indicator, a local
sensor, and four LED’s.
BAYSENS021 features and system control functions include:
•Temperature sensing in the zone
• System control switch with mode setting for "AUTO" and "OFF"
• Supply air single temperature setpoint
• Function status indicator lights:
“SYS ON” glows continuously during normal operation, or blinks if system is in
test mode.
“COOL” glows continuously during cooling cycles, or blinks to indicate a
cooling system failure.
“HEAT” glows continuously during heating cycles, or blinks to indicate a
heating system failure.
“SERVICE” blinks or glows to indicate a problem. These signals vary
depending on the particular equipment being used.
Figure I-PR-9. BAYSENS021
Single setpoint sensor with system
function lights, accessory model number
digit 6 = H
(Possible Schematic Designation: 5U25)
SCXG-SVX01B-EN
45
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-startup
requirements
Installation
the unit control panel.
literature for allowable waiting periods
for discharge of capacitors.Verify with an
appropriate voltmeter that all capacitors
have discharged. Failure to disconnect
power and discharge capacitors before
servicing could result in death or serious
injury.
3. Replace the zone sensor cover back on
the subbase and snap securely into
place.
Standard Remote Sensor (BAYSENS077)
When using the remote sensor,
BAYSENS077, mount it in the space that
is to be controlled.Wire according to the
interconnecting wiring diagrams on the
unit.
Note: For additional information regard-
ing the safe discharge of capacitors, see
PROD-SVB06A-EN or PROD-SVB06A-FR.
Standard zone sensors, BAYSENS077,
ships with all units
Table I-PR-1. Zone sensor maximum lengths
and wire size
NOTICE
Use Copper Conductors Only!
Distance from
Unit to Controller
0-150feet
Recommended
Wiring Size
22gauge
Zone Sensor Installation
Unit terminals are not designed to
accept other types of conductors. Failure
to use copper conductors may result in
equipment damage.
All sensor options ship in the main control
panel and are field-installed.
Programmable option installation
procedures.
151--240feet
241-385 feet
386- 610 feet
611-970 feet
20gauge
18gauge
16gauge
14gauge
Mounting Location
Mount the sensor on the wall in an area
with good air circulation at an average
temperature. Avoid mounting space
temperature sensor is areas subject to
the following conditions:
• Drafts or “dead” spots behind doors or
in corners
• Hot or cold air from ducts
• Radiant heat from the sun or appliances
• Concealed pipes and chimneys
• Unheated or non-cooled surfaces
behind the sensor, such as outside walls
• Airflows from adjacent zones or other
units
Remove the zone sensor cover from
subbase, and mount subbase on the wall
or on a 2 x 4 junction box. Route wires
through the wire access hole in the
subbase. See Figure I-PR-14. Seal the hole
in the wall behind the subbase.
Note: Guidelines for wire sizes and lengths
are shown in Table I-PR-1. The total resis-
tance of these low voltage wires must not
exceed 2.5 ohms per conductor. Any resis-
tance greater than 2.5 ohms may cause the
control to malfunction due to excessive
voltage drop.
To mount the sensors, remove the dust
cover and mount the base on a flat
surface or 2" x 4" junction box. Sensors
ship with mounting screws.
Note: Do not run low-voltage control wiring in
same conduit with high-voltage power wiring.
Wiring
Mounting the Subbase
1. Run wires between the unit control
panel and the zone sensor subbase.To
determine the number of wires
required, refer to the unit wiring
diagrams.
2. Connect the wiring to the appropriate
terminals at the unit control panel and
at the zone sensor subbase. In general,
zone sensor connections to the unit use
the convention of connecting zone
sensor terminals to like numbered unit
terminals (1 to 1, 2 to 2, etc.).The
connection detail is shown on the unit
wiring diagrams, which are located in
ƽWARNING
HazardousVoltage w/Capacitors!
Disconnect all electric power, including
remote disconnects before servicing.
Follow proper lockout/tagout proce-
dures to ensure the power cannot be
inadvertently energized. For variable
frequency drives or other energy storing
components provided byTrane or others,
refer to the appropriate manufacturer’s
46
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-startup
requirements
Installation
1-3/32 [27,43 mm]
3/32 [2,00 mm]
1-3/8 [35,00 mm]
19/32 [15,00 mm]
3-5/32 [80,00 mm]
1-1/32 [26,16 mm]
5/32 [3,81 mm] 4X
15/64 [6,00 mm]
RIGHT
BACK
Figure I-PR-22. Zone sensor mounting hole locations for: BAYSENS077, BAYSENS073, BAYSENS074,
BAYSENS108, and BAYSENS110.
Zone sensor mounting hole locations for: BAYSENS021.
SCXG-SVX01B-EN
47
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-startup
requirements
Installation
Mounting Directly to the Wall
Mounting to Junction Box
Junc
Figure I-PR-23. Typical zone sensor installation for vertically-oriented sensors
48
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-startup
requirements
Installation
Programmable Zone Sensors
ConstantVolume Zone Sensor
VariableAirVolume Zone Sensor
Programmable zone sensors provide
programming and zone temperature
sensing for the self-contained unit. It
allows the user to monitor room
temperatures and program settings in
the space, without having to access the
unit control panel.
BAYSENS019 Description
BAYSENS020B Description
This seven day programmable sensor
with night setback has four periods for
occupied\unoccupied programming per
day. If power is interrupted, the program
retains in permanent memory. If power is
off longer than two hours, only the clock
and day may have to be reset.
This seven day programmable sensor
with night setback has four periods for
occupied\unoccupied programming per
day. Either one or all four periods can be
programmed. If power is interrupted, the
program retains in permanent memory. If
power is off longer than twohours, only
the clock and day may have to be reset.
Reference programming instructions for
these zone sensors beginning on page 44.
The six programming keys on the front of
the zone sensor allow selection of system
modes (heat, cool, auto, and off), two fan
modes (on and auto). The zone sensor
has dual temperature selection with
programmable start time capability.
The occupied cooling setpoint range is 40
to 80°F.The warmup setpoint range is 50
to 90°F with a 2° deadband. The
The zone sensor keypad allows you to
select occupied/unoccupied periods with
two temperature inputs (cooling supply
air temperature and heating warmup
temperature) per occupied period. The
occupied cooling setpoint ranges be-
tween 40 and 80°F.The warmup setpoint
ranges between 50 and 90°F with a 2°
deadband. The unoccupied cooling
setpoint ranges between 45 and 98°F.
The heating setpoint ranges between 43
and 96°F.
unoccupied cooling setpoint range is 45 to
98°F.The heating setpoint range is 43 to
96°F.
Two liquid crystal displays (LCD) display
zone temperature, setpoints, week day,
time, and operational mode symbols.
The liquid crystal display (LCD) displays
zone temperature, setpoints, week day,
time, and operational mode symbols.
The DIP switches on the subbase enable
or disable applicable functions; i.e.
morning warmup, economizer minimum
CFM override during unoccupied status,
Fahrenheit or Centigrade, supply air
tempering, remote zone temperature
sensor, 12/24 hour time display, smart
fan, and computed recovery.
The DIP switches on the subbase enable
or disable applicable functions; i.e.
morning warmup, economizer minimum
position override during unoccupied
status, heat installed, remote zone
temperature sensor, 12/24 hour time
display, and daytime warmup. During an
occupied period, an auxiliary relay rated
for 1.25 amps @ 30 volts AC with one set
of single pole double throw contacts
activates.
During an occupied period, an auxiliary
relay rated for 1.25 amps @ 30 volts AC
with one set of single pole double throw
contacts activates.
Figure I-PR-17. BAYSENS020, program-
mable night-setback sensor,
accessory model number digit 6 = J
Figure I-PR-16. BAYSENS019, program-
mable night setback sensor, accessory
model number digit 6 = G
SCXG-SVX01B-EN
49
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-startup
requirements
Installation
Programmable Zone Sensor
Installation
Installation Procedure
a. Hold the subbase in position and mark
the three mounting hole locations on
the wall.
1. Remove the zone sensor module from
the subbase. Carefully hold the zone
sensor module with one hand and
firmly grasp the subbase with the other.
See Figure I-PR-20.To remove the zone
sensor module from the subbase,
gently pull away and upward.
b. Drill three 3/16” (4.8 mm) holes. Gently
tap the plastic wall anchors into the
holes until the anchor tops are flush
with the wall.
Mounting Location
Mount the sensor on the wall in an area
with good air circulation at an average
temperature. Choose a location that is
easily accessible, and on a wall where the
subbase can be mounted about 5 feet
(1.5 meters) above the floor.
6. Pull the zone sensor module wires
through the subbase as shown in Figure
I-PR-21.
7. Loosely secure subbase to the wall
with the mounting screws. Do not
tighten the subbase screws yet.
8. Level the subbase by sight, then firmly
tighten the three subbase mounting
screws.
Note: The zone sensor module is an
electronic sensitive device. Do not touch
printed circuit board, electronic compo-
nents, or connector pins. Handle plastic
housing only to prevent damage to
electronic components.
Avoid mounting space temperature
sensor in areas subject to the following
conditions:
• Drafts or “dead” spots behind doors or
in corners
• Hot or cold air from ducts
• Radiant heat from the sun or appliances
• Concealed pipes and chimneys
• Unheated or non-cooled surfaces
behind the sensor, such as outside walls
• Airflows from adjacent zones or other
units
2. After disassembly, protect the internal
surfaces from contact with objects or
substances that could cause damage.
3. Remove the terminal block from
subbase and set aside for wiring.
Discard the tape.
4. Mount the zone sensor module using
the mounting hardware included in the
shipping package. The mounting
hardware is contained in single plastic
bag and includes:
Note: Do not overtighten the subbase
screws. Overtightening may cause the
screws to crack the subbase.
9. Before wiring the subbase, identify the
wires from the unit’s low voltage
terminal strip. Each screw terminal is
labeled.
10. Remove TB from subbase and
discard the tape.
11. Strip the wires 1/4” and connect the
wires from the unit’s low voltage
terminal strip to the zone sensor
module subbase. Reference connection
details on the unit wiring diagrams,
located on the unit.
12. Firmly tighten each screw terminal.
13. Fit the wires as close to the subbase
as possible.
• Plastic wall anchors (3 x)
• Mounting screws (3 x)
(95 mm)
The zone sensor module can mount
directly to a wall or to a junction box
mounted to a wall.To mount to a
junction box, you must have the
mounting plate and adapter kit,
BAYMTPL003. Installation instructions
are enclosed with the mounting plate.
5.To mount the zone sensor module
directly to a wall:
(140 mm)
Figure I-PR-18. BAYSENS019 dimensions
(95mm)
Figure I-PR-20. Removing the zone sensor
module from the subbase
(140mm)
Figure I-PR-19. BAYSENS020 dimensions
Figure I-PR-21. Securing the subbase
50
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-startup
requirements
Installation
Time Clock Option
The time clock option has a
Time Clock Installation Checklist
1. Ensure operating temperature is 4°F to
131°F.
programmable timer that is factory wired
to the unoccupied input to provide on/off
control. The time clock will not allow the
unit to pass through the night setback/
morning warmup mode, except on units
with optional night heat/morning warm
up, or programmable night setback. See
Figure I-PR-22.
2. Locate the time clock at least 5 feet
away from any large electrical contact
or machinery to avoid possible
electrical interference problems.
3. Provide a separate independent circuit
for the time clock
power supply.
4. Since all electronic instruments are
sensitive to voltage spikes, pay close
attention to the following:
The timeclock, a “Digi 20” by Grasslin, is
inside the control panel, but accessible
with the control panel door closed. This
same type timer is also used for pro-
grammable night setback/morning warm
up. Programming instructions for the
“Digi 20” timer are in the “Program-
ming” section.
Figure I-PR-22. Grasslin time clock option
a. If possible, supply power to the
electronic time clock from a phase
different than the one supplying power
to the load
b. Provide a suitableVaristor or RC
network across the INDUCTIVE LOADS
supply terminals to reduce voltage
spikes.
c. Place a diode across the DC OPERATED
INDUCTOR terminals to eliminate back
EMF.
d. HIGHLY INDUCTIVE LOADS, especially
fluorescent lights, may require a relay
in which case (A) and (C) apply.
Time Clock Installation
1. Ensure operating temperature is
between 4°F and 131°F.
2. Locate the time clock at least 5 feet
away from any large electrical contact
or machinery to avoid possible
electrical interference problems.
3. Provide a separate independent circuit
for the time clock power supply.
4. Since all electronic instruments are
sensitive to voltage spikes, pay close
attention tot he following:
a. If possible, supply power to the
electronic time clock from a phase
different than the one supplying power
to the load.
b. Provide a suitableVaristor or RC
network across the INDUCTIVE
LOADS supply terminals to reduce
voltage spikes.
c. Place a diode across the DC
OPERATED INDUCTOR terminals to
eliminate back EMF.
The Digi 20A timeclock unit can be
surface or flush mounted. Lift off the
front cover and loosen the two screws on
opposite corners. Pull off the base’s plug
with a left to right rolling motion.
Surface Mounting Inside Panel
Place screws through the base’s preset
holes and screw to back of panel or wall.
Wire according to the instructions in the
following section. Depending upon the
specific installation, you may find it more
convenient to complete wiring before
attaching the base.
Place the terminal cover over the
terminal block by aligning the two screws
with the corner holes in the base. Push
the timer firmly onto the plug in the base.
Tighten the two screws. A base for DIN
rail mounting is optional.
d. HIGHLY INDUCTIVE LOADS, especially
fluorescent lights, may require a relay
in which case step a. and c. apply.
The timeclock can be surface or flush
mounted. Lift off the front cover and
loosen the two screws on opposite
corners. Pull off the base’s plug with a left
to right rolling motion.
Wiring theTimeclock
1. Wire 24, 120, or 220VAC to input
terminals. Make sure to apply correct
voltage. Using incorrect voltage will
void the warranty.
2. Connect wire to the screw terminals
according to the unit wiring diagrams.
Use 12 to 22 AWG wire.
SCXG-SVX01B-EN
51
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-startup
requirements
Installation
Remote Human Interface Panel
Installation
Human Interface (HI) Panel
The HI enables the user to communicate
necessary unit operating parameters and
receive operating status information
from within the occupied space.
The HI displays top level information in
the LCD window, unless the operator
initiates other displays, for the various
unit functions. It also displays menu
readouts in a clear language 2 line, 40
character format. The 16-key keypad
allows the operator to scroll through the
various menus to set or modify the
operating parameters. See Figure I-PR-
23 to reference the HI keypad.
Remote Human Interface Panel
The remote human interface (RHI) panel
is identical to the unit mounted HI with the
exception of the “unit select” key.This
key allows the operator to switch from
one unit to the next to program or view
status information regarding a particular
unit.
The RHI functions the same as the unit
mounted HI with two exceptions. The first
is the “test start” function. The operator
can view the service parameters, but can
only initiate the service test function at
the unit. The RHI door has a locking screw
to deter access by unauthorized person-
nel. Additionally, the RHI can control up to
four different units.
Figure I-PR-23. Human interface (HI) panel keypad
Table I-PR-2. Maximum communication link
Location Recommendations
The HI microprocessor module is
mounted inside a molded plastic
enclosure for surface mounting. It is not
weatherproof. Therefore, it is only
applicable for indoor use.
AmbientTemperature and Humidity
Limits
wiring length
Ambient Operating Conditions
•Temperature: 32 to 120°F
• Relative humidity: 10 to 90%, non-
condensing
Ambient Storage Conditions
•Temperatures: -50 to 200°F
• Relative humidity: 5 to 95%, non-
condensing
max. wire
length
1,000 ft
2,000 ft
3,000 ft
4,000 ft
5,000 ft
max. capacitance
between conductors
up to 60 pf/ft
up to 50 pf/ft
up to 40 pf/ft
up to 30 pf/ft
up to 25 pf/ft
Locate the RHI panel in an area that will
ensure the communication link between
the panel and the unit(s) does not exceed
5,000 feet maximum or pass between
buildings. SeeTable I-PR-2.
Note: pf/ft = picofarads/foot
The run length of the low voltage AC
power wiring to the remote HI must not
exceed three (3) ohms/conductor. Refer
toTable I-PR-3.
Table I-PR-3.Wiring recommendations for the
remote HI panel
distance
recommended
wire size
to remote HI
0-460 feet
18 gauge
16 gauge
14 gauge
461-732 feet
733-1000 feet
52
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-startup
requirements
Installation
Mounting the Remote Human
Interface (RHI) Panel
The installer must provide all mounting
hardware such as; hand tools, electrical
boxes, conduit, screws, etc. Refer to
Figure I-PR-24 for the mounting hole and
knockout locations.
a.Verify that the terminal block jumpers
are connected properly.
b. Slide the extruded hinge pin at the top
left of the key pad plate into the hole
located at the top left hand side of the
enclosure.
c. Slide the bottom of the plate into place,
aligning the two (2) clearance holes
with the screw holes on the right. Install
the screws but do not tighten.
Procedure
Refer to Figure I-PR-24 and follow the
procedure below for mounting the
remote HI panel on a 4” by 4” electrical
junction box. Place the microprocessor in
a clean dry location during the enclosure
mounting procedures to prevent
damage.
Note: If the two screws are not installed as
called out in the previous step, hold against
the key pad plate while installing the door
in the next step, to prevent it from falling
out.
1. Mount an electrical junction box in the
wall so that the front edge of the box
will be flush with the finished wall
surface.
2. Prior to mounting the panel, the
microprocessor module must be
carefully removed from the enclosure.
To remove the module:
a. Lay the remote panel face up on a flat
surface and remove the locking screw
from the right hand bottom end of the
panel.
b. Remove the recessed hinge screw
from the left hand bottom end of the
panel.
c. Unlatch the door of the enclosure as if
to open it, and slide the left hand side of
the door upward away from the hinge.
Lay it aside.
d. With the key pad visible, remove the
two (2) screws located on the right hand
side of the key pad.
d. Slide the extruded hinge pin at the top
left of the door into the hole located
under the bottom left side of the display.
e. Install and tighten the hinge screw
located at the bottom left side of the
enclosure.
Wall Mounting the RHI Panel
1. Prior to mounting the panel, the
microprocessor module must be
removed from the enclosure. Complete
step 2 in the previous discussion,
“Mounting on a 4 in. x 4 in. Electrical
Box,” before proceeding.
2. With the microprocessor removed,
refer to Figure I-PR-24 for the location of
the mounting holes to be used for wall
mounting.
3. Place the enclosure against the
mounting surface and mark the
mounting holes.
e. Carefully slide the key pad plate
upward from the bottom, releasing the
extruded hinge pin from its socket at
the top.
f. Set the microprocessor aside until
mounting is complete.
Note: The top of the enclosure is marked
with “TOP.”
4. With the enclosure in the correct
position, remove the enclosure and drill
the necessary holes in the surface for
the appropriate fasteners, (plastic
anchors, molly bolts, screws, etc.)
5. Remove the necessary knockouts for
the wire or conduit entry before
mounting the panel.
3. Remove the junction box knockout in
the back of the enclosure.
Note: The top of the enclosure is marked
“TOP.”
6. Place the enclosure back onto the
surface and secure it with the
appropriate screws.
7. Follow step 5 in the previous section,
“Mounting on a 4” by 4” Electrical
Box,” to replace the microprocessor
within the enclosure.
4. With the enclosure in the correct
position; align the mounting holes
around the knockout in the enclosure
with the screw holes in the electrical
handy box and secure with the
appropriate screws.
5. Replace the microprocessor within the
enclosure as follows:
SCXG-SVX01B-EN
53
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-startup
requirements
Installation
Figure I-PR-24. Remote HI mounting holes and knockout locations
54
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-startup
requirements
Installation
Wiring the Remote Human
Interface
The remote human interface requires 24
VAC + 4 volts power source and a
shielded twisted pair communication link
between the remote panel and the
interprocessor communication bridge
(ICPB) module at the self-contained unit.
LowVoltage (AC) FieldWiring
Note: Although the 24 volt power is not
polarity sensitive, do not connect either the +
(plus) or - (minus) terminals from the remote
panel to ground at the self-contained unit.
Connections
To access the wire entry locations, open
the RHI panel door and remove the two
screws on the right-hand side of the key
pad. Swing the keypad open, exposing
both the wire entries and the back of the
HI module. Refer to Figure I-PR-24 and
connect one end of the three conductor
24 volt wires to the remote panel
terminal strip (+), (-), and (ground).
Connect the wire connected to the
positive (+) terminal at the remote panel.
Connect the wire connected to the
negative (-) terminal at the remote panel.
Connect the ground wire from the remote
panel to the unit control panel casing.
Field wiring for both the low voltage
power and the shielded twisted pair must
meet the following requirements:
Communication Link (ShieldedTwisted
Pair)Wiring
Interprocessor Communication Bridge
ModuleWiring
Trim the outer covering of the shielded
cable back approximately 1 inch. See
Figure I-PR-25. Do not cut the bare shield
wire off. Strip approximately 1/2-inch of
insulation from each insulated wire to
connect them to the terminal strip at the
remote panel.
Refer to Figure I-PR-25 and trim the outer
covering of the shielded cable back
approximately one inch. Cut the bare
shield wire off even with the outer
covering. Strip approximately 1/2-inch of
insulation from each insulated wire in
order to connect them to the terminal
strip at the unit.Wrap tape around any
exposed foil shield and/or base shield
wire.
Note: To prevent control malfunctions, do
not run low voltage wiring (30 volts or less)
in conduit with higher voltage circuits.
ƽWARNING
Connect the white lead to the positive (+)
terminal, the black lead to the negative (-)
terminal, and the bare shield wire to the
terminal at the remote human interface
panel.
HazardousVoltage w/Capacitors!
Disconnect all electric power, including
remote disconnects before servicing.
Follow proper lockout/tagout proce-
dures to ensure the power cannot be
inadvertently energized. For variable
frequency drives or other energy storing
components provided byTrane or others,
refer to the appropriate manufacturer’s
literature for allowable waiting periods
for discharge of capacitors.Verify with an
appropriate voltmeter that all capacitors
have discharged. Failure to disconnect
power and discharge capacitors before
servicing could result in death or serious
injury.
Note:The communication link is polarity
sensitive.
Close the key pad plate. Install and
tighten the two screws removed earlier.
Close the outer door and install the
recessed locking screw at the bottom
right hand side of the enclosure to
prevent accidental starting of the unit by
unauthorized personnel while completing
the wiring at the self-contained unit.
Refer to the unit wiring diagram and
connect the white lead to the positive (+)
terminal and the black lead to the
negative (-) terminal. (These terminals
are numbered. Reference to color is for
clarification to maintain polarity).
Note: To maintain polarity, do not connect
the base shield wire to ground at the self-
contained unit.
At the Self-Contained Unit
Connect the opposite end of the three
conductor 24-volt wire to the appropriate
terminal strip as follows:
Note: For additional information regard-
ing the safe discharge of capacitors, see
PROD-SVB06A-EN or PROD-SVB06A-FR.
1. All wiring must be in accordance with
NEC and local codes.
2. ReferenceTable I-PR-3 for
recommended wiring distance and size.
3. Communication link wiring must be 18
AWG shielded twisted pair (Belden
8760, or equivalent).
4. Communication link must not exceed
5,000 feet maximum for each link. See
Table I-PR-2.
5. Do not run communication link
between buildings.
Figure I-PR-25. Dressing shielded twisted wire
SCXG-SVX01B-EN
55
Download from Www.Somanuals.com. All Manuals Search And Download.
pre-startup
requirements
Installation
Connecting toTracer Summit
establish each communication link
betweenTracer Summit and each unit.
Tighten locking screws, bearing set
screws and sheaves.
Ensure bearing locking collars do not
wobble when rotated.
ƽWARNING
Pre-Startup Checklist
Complete this checklist after installing the
unit to verify all recommended
installation procedures are complete
before unit start-up. This does not replace
the detailed instructions in the
appropriate sections of this manual.
Always read the entire section carefully
to become familiar with the procedures.
Ductwork
Hazardous Voltage w/Capaci-
tors!
If using return ductwork to the unit,
secure it with three inches of flexible
duct connector.
Disconnect all electric power, including
remote disconnects before servicing.
Follow proper lockout/tagout proce-
dures to ensure the power cannot be
inadvertently energized. For variable
frequency drives or other energy storing
components provided byTrane or others,
refer to the appropriate manufacturer’s
literature for allowable waiting periods
for discharge of capacitors.Verify with an
appropriate voltmeter that all capacitors
have discharged. Failure to disconnect
power and discharge capacitors before
servicing could result in death or serious
injury.
Extend discharge duct upward without
change in size or direction for at least
three fan diameters.
Use a 3” flexible duct connection on
discharge ductwork.
Ensure trunk ductwork toVAV boxes is
complete and secure to prevent leaks.
Verify that all ductwork conforms to
NFPA 90A or 90B and all applicable
local codes
Receiving
Inspect unit and components for
shipping damage. File damage claims
immediately with the delivering carrier.
Check unit for missing material. Look
for ship-with drives, isolators, filters,
and sensors that are packaged
separately and placed inside the main
control panel, fan section, or
Water-Cooled Unit Piping
Verify the condensate drain piping is
complete for the unit drain pan. Install
and tighten the condensate “P” trap
drain plug.
Install water piping drain plugs,
economizer header, and condenser
vent plugs.
Make return and supply water
connections to the unit and/or waterside
economizer piping package with
recommended valves and piping
components. Refer to the “Water
Piping” section.
Install unions to allow waterside
maintenance.
Install cooling tower and standby
pumps.
Treat water to prevent algae, slime,
and corrosion.
Prevent refrigerant piping from rubbing
against other objects.
compressor section. See the “Receiving
and Handling” section.
Check nameplate unit data so that it
matches the sales order requirements.
Note: For additional information regard-
ing the safe discharge of capacitors, see
PROD-SVB06A-EN or PROD-SVB06A-FR.
Unit Location
Remove crating from the unit. Do not
remove the shipping skid until the unit is
set in its final position.
IntelliPak commercial self-contained
(CSC) units operate withTrane building
automation software,Tracer Summit
version 10.0.4 or later or any OS2
operating system.
Ensure the unit location is adequate for
unit dimensions, ductwork, piping, and
electrical connections.
Ensure access and maintenance
clearances around the unit are
adequate. Allow space at the end of the
unit for shaft removal and servicing.
See the “Service Access” section.
Note: Tape the non-insulated end of the
shield on shielded wire at the unit. Any
connection between the shield and ground
will cause a malfunction. If daisy-chained in
the unit, splice and tape the shields to
prevent contact with ground.
Unit Mounting
Place unit in its final location.
Remove shipping skid bolts and skid.
If using isolators, properly mount unit
according to the isolator placement
sheet.
Air-Cooled Units Only
Connect refrigerant lines.
Install liquid line filter driers.
CommunicationWiring
Note: Communication link wiring is a
shielded, twisted pair of wire and must
comply with applicable electrical codes.
Units with Hydronic Heat
Verify the entering water temperature
sensor is installed upstream of the
hydronic coil.
Remove shipping brackets on the
compressors and supply fan.
Remove the unit protective shipping
covers.
An optional communication link provides
a serial communication interface (SCI)
betweenTracer Summit and each
commercial self-contained (CSC) unit in
the system. The CSC system can have a
maximum of 12 CSC units per connection
link toTracer Summit. Use a single 18
AWG shielded, twisted pair wire with
stranded, thinned copper conductors to
Units with Electric Heat
Verify the supply air temperature
sensor is downstream of the electric
heat coil.
Component Overview
Verify the fan and motor shafts are
parallel.
Verify the fan and motor sheaves are
aligned.
Check the belt tension for proper
adjustment.
Ensure the fan rotates freely.
56
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
programming
Programmable Zone Sensor
Options
BAYSENS019
Figure I-P-1. BAYSENS019 keypad and display configuration
BAYSENS019 Keypad and Display
Explanation
4. Erase Button
8. Mode Button
• Erases time and temperature settings
throughout each of the programmed
periods.
Toggles the controller through its 4
modes: off, heat, cool, and auto; if HP
version, also emer (emergency).
1. Up and Down Buttons
• Increases or decreased programmed
temperature settings in program menu.
• Shifts to temporary manual override in
normal run mode.
• Exits temporary manual override.
9.
5. Day Button
Toggles through the seven days of the
week.
• Indicates day of the week
• Indicates begin time in program menu
Indicates time setting in temporary
override mode.
•Increases or decreases temperature
while in temporary override menu.
6. HoldTemp Button
2.Time Adjust Button
Shifts controller to temporary manual
override, and begins temperature
override.
Used to set the correct time of day. Used
to set programmed time for temperature
variations.
7. Fan Button
Toggles the fan controller between on
and auto mode.
3. Program Button
Toggles between the display control
screen and the display program screen.
SCXG-SVX01B-EN
57
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
programming
BAYSENS020
Figure I-P-2. BAYSENS020 keypad and display configuration
BAYSENS020 Keypad and Display
Explanation
3. Program Button
Toggles between the display control
screen and the display program screen.
7. Mode Button
•Toggles the controller between the two
modes, off and auto.
• Advances to next setpoint in program
menu.
1. Up and Down Buttons
• Increases or decreased programmed
temperature settings in program menu.
• Shifts to temporary manual override in
normal run mode.
4. Erase Button
• Erases time and temperature settings
throughout each of the programmed
periods.
8. During Programming Indicates:
• Heat supply air
• Cool supply air
• Warmup temperature
•Increases or decreases temperature
while in temporary override menu.
• Pressed together, toggles between
unoccupied/occupied setting.
• Exits temporary manual override.
5. Day Button
Toggles through the seven days of the
week.
2.Time Adjust Button
6. HoldTemp Button
Used to set the correct time of day. Used
to set programmed time for temperature
variations.
Shifts controller to temporary manual
override, and begins temperature
override.
58
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
programming
Initial Power-Up
Program Button
is installed and warmup options are
enabled.
Before applying power to your ZSM, and
before performing setup and operation
procedures, verify that all wiring is
correct. See Figures I-P-9 on page 52 and
I-P-10 on page 53 for a complete zone
sensor icon display description.
Depressing the program button will
toggle the display from normal run mode
to the program menu. See Figure I-P-3.
Before toggling to the program menu,
use the mode button to select the type
setpoints to review or program (heat,
cool or auto). For example, if you select
cool mode before toggling to the program
menu, then only the cool setpoints are
reviewed or programmed. If you select
heat mode, then only the heat setpoints
are reviewed or programmed. In auto
mode, both heat and cool setpoints are
reviewed and programmed.
During unoccupied periods, only the
desired room temperature setpoints are
entered. Each unoccupied period has a
heat and cool setpoint, and both setpoints
are offered during programming.
For BAYSENS020 only: at initial power-
up, the ZSM controls to default tempera-
tures of 68°F (19°C) for warmup, and
55°F (13°C) supply air, until the ZSM is
programmed or the arrow keys are
pressed. If the arrow keys and mode are
moved, the ZSM starts controlling to
these new settings.
Blank temperature settings may also be
entered. When a setpoint is blank, the
program will default to the last setpoint of
its type. If there is no setpoint of its type,
the default setpoint is used. If all setpoints
in the time period are blank, the entire
time period is erased after exiting from
the program menu.
• While in program menu, each time you
press and release the program button,
the ZSM toggles through the four
periods that divide each day.Those four
periods are: Morn(ing), Day, Eve(ning),
and Night.
Time and Day Settings
The ZSM has independent, seven day
programming:
• Each day can be programmed with
different times, temperatures, and
occupied status.
• Each day can be programmed with up
to four periods. Although four periods
are available each day, you can
program just one of the four.
• Each period can be programmed for
occupied or unoccupied.
On power-up your ZSM will be in normal
run mode and will begin operating using
setpoints. The display will show the
wrong day and time and will need to be
set.
•To exit the program menu, depress the
program button for two seconds.
To set the time, there is a single rubber
button on the keypad “minus” and
“plus” mark time.
Depressing the positive side will advance
the time. Depressing the negative side
will decrease the time.
To begin programming, follow these
steps:
Each time you depress the positive or
negative side “minus” and “plus”, the
time will either advance or decrease
respectively by one minute. If you press
and hold either side of the time button,
the time change will accelerate rapidly.
• Determine which periods during the day
will be occupied and unoccupied.
• Write your daily schedule on the sheet
enclosed with the zone sensor.
• Enter your program by following the
steps below.
When you reach the correct time, release
the time button and the time will be set
into permanent memory.
Figure I-P-3. Display program menu screen
To program time periods and setpoints
for a day:
• Press the program button to enter
program mode.
• Press the day button to select first day to
be programmed.
• To set the “begin” time for the first
period of the day, press the minus or
plus keys.
Program Menu
Note: To ensure the time changes are
made, the ZSM will initiate a 30 second
user-stabilization time before making
changes to the ZSM operation mode.
BAYSENS020 Only
Note: After toggling to the program screen,
the week is divided into seven days with
each day divided into four periods.
Keypad Operation
• To set the temperature setpoint for that
period, use ↑ or ↓.
Setpoint programming depends on the
setting status, occupied or unoccupied,
and whether or not heat is installed,
modulated heat, morning warmup, or
daytime warmup options are enabled.
• Press the program button to move to
the next period for that day.
• To program time periods and setpoints
for the next day, press the day button.
• When finished, press and hold the
program button for two seconds to
return to the normal run mode.
Note: After toggling to the program screen,
the week is divided into seven days with
each day divided into four periods.
Therefore, 28 program settings are pos-
sible.
In the occupied period, the cool supply air
temperature is always set. If heat
installed and modulated heat options are
on, the supply air heat is also set during
occupied periods. The warmup tempera-
ture is also set in occupied periods, if heat
SCXG-SVX01B-EN
59
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
programming
Note: Blank temperature settings may be
entered at any of the four daily periods.
When a setpoint is left blank and in an
occupied condition, the ZSM will default to
the last occupied setpoint. When a setpoint
is left blank and in an unoccupied condi-
tion, the ZSM will default to the last
unoccupied setpoint.
• Keypad lockout applies only to normal
run mode and temporary manual
override mode.
a temporary manual override menu. See
Figure I-P-4.
This mode overrides any number of
programmed setpoints through any of
the 28 programmed periods. After
entering setpoints and length of override
time, these settings are now used.
Day Button
• In normal run mode, depressing the day
button will move the current day ahead.
• While in the program menu, depressing
the day button will move you through
the seven days of the week and allow
you to program temperature settings
for each of the four daily periods.
Temporary Manual Override
While in normal run mode, depressing
the hold temp button toggles the ZSM to
the temporary manual override menu.
Erase Button
• Pressing the erase button while in
normal run mode will turn off the check
filter icon.
The mode will override any number of
programmed setpoints through any of
the 28 programmed periods. After
entering setpoints and length of override
time, these new settings are used in place
of the setpoints programmed for normal
run mode.
• Pressing the erase button while in the
program menu, will erase all time and
temperature setpoints of a given
period.
• The erase button will acknowledge the
failure buzzer (option 16) until 12:00 am.
Figure I-P-4.Temporary manual override menu
screen
Time Button
Mode Button
• While in the program menu, each time
you press and release the positive or
negative side of the time button, the
time will advance or decrease by ten
minute increments. If you press and
hold the positive or negative side
(“minus” and “plus” keys), the ZSM
will increment rapidly.
Keypad Operation for Temporary
Manual Override Menu
• BAYSENS019 only: Pressing the mode
button toggles through all modes: off,
heat, cool, auto, and emer (HP unit).
• BAYSENS020 only: Pressing the mode
button while in normal run mode, or
temporary manual override run mode,
will toggle through both modes, off and
auto.
The keypad has the same function in
temporary manual override menu as in
all other menus, with a few exceptions:
• Depressing the day button will toggle
your ZSM between the day and hour
icon. See Figure I-P-4.
• Depressing the mode button will toggle
your ZSM between the heat and cool
icons and setpoints.
• Depressing the erase button will cancel
the override and return the ZSM to
normal run mode.
• Depressing the holdtemp or program
buttons while in the temporary manual
override menu will toggle your ZSM to
the temporary override mode. See
Figure I-P-5.
• When the display is in the normal run
mode, each time you press and release
the positive or negative side of the time
button (“minus” and “plus”keys), the
time will advance or decrease by one
minute. If you press and hold the
positive or negative side (“minus” and
“plus” keys), the ZSM will increment
rapidly.
Fan Button
• The fan button allows you to toggle
between on and auto.
Up and Down Button Arrows
• Depressing ↑ or ↓ arrow while in normal
run mode will cause your ZSM to toggle
to the temporary manual override
menu.
• Depressing either ↑ or ↓ arrow while in
the program menu or temporary
override menu will cause the
temperature setpoint to advance or
decrease in one degree increments.
• Depressing and holding either the ↑ or ↓
arrow will cause the temperature
setting to increment rapidly.
Note: Blank temperature settings may be
entered at any of the four daily periods.
When a setpoint is left blank and in an
occupied condition, the ZSM will default to
the last occupied setpoint.
Keypad Lockout
If you simultaneously depress and hold
both the positive and negative sides of
the “minus” and “plus” keys for four
seconds, the lock icon will appear and all
keypad functions will lock out. If you
repeat this operation, the lock icon will
disappear and all keypad functions will be
available again.
Simultaneously depressing the ↑ or ↓
arrow for two seconds while in the
program menu or temporary override
menu will toggle the ZSM between an
occupied and unoccupied condition.
Holdtemp Button
While in normal run mode, depressing
the hold temp button toggles the ZSM to
Figure I-P-5. Override run mode screen
60
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
programming
Temporary Override Run Mode
• Depressing the day button will toggle
the ZSM between the day and hour
icon.
• Depressing the mode button will toggle
the ZSM between the heat and cool
icons and setpoints.
• Depressing the erase button will cancel
the override and return the ZSM to
normal run mode.
• If no button is pressed for 20 seconds,
the ZSM exits temporary manual
override menu and enters the normal
run mode, ignoring the temporary
manual override menu settings.
The temporary override run mode sends
setpoint data to the unit control module
(UCM) from the setpoint data entered in
the temporary manual override menu.
In temporary override run mode, most of
the keypad functions lock out with these
exceptions:
• The mode button still functions as in
normal run mode.
• The fan button still functions as in
normal run mode.
• Depressing the holdtemp button toggles
the ZSM between the temporary
manual override menu and override
run mode. (if no button is pressed for 20
seconds while in temporary manual
override menu, the ZSM exits to normal
run mode, ignoring the temporary
override settings.)
Temporary Manual Override Run Mode
The temporary manual override run
mode sends setpoint data to the UCM
from the setpoint data entered in the
temporary manual override menu. See
Figure I-P-7.
• Depressing either the ↑ or ↓ arrow while
in the override run mode will cause the
ZSM to toggle to the temporary manual
override menu.
• The erase button will turn off the check
filter icon if displayed.
• Simultaneously depressing and holding
the positive and negative sides of the
“minus” and “plus” for four seconds
will lock out the keypad.
•Time is not adjustable in this mode.
• The program button is disabled.
In temporary manual override run mode,
most of the keypad functions lock out with
these exceptions:
• The mode button still functions as in
normal run mode.
• Depressing the holdtemp button toggles
the ZSM between temporary manual
override menu and temporary manual
override run mode. If no button is
pressed for 20 seconds, while in the
temporary manual override menu, the
ZSM exits to the normal run mode,
ignoring the temporary manual
override settings.
Keypad Operation for Temporary
Manual Override Menu
The keypad has the same function in
temporary manual override menu as in
all other menus, with a few exceptions:
• Depressing the holdtemp or program
buttons while in temporary manual
override menu will enter settings and
begin temporary manual override run
mode. See Figure I-P-6.
• Depressing either the up or down arrow
keys while in temporary manual
override run mode will cause the ZSM
to toggle to temporary manual override
menu.
• The erase button will turn off the check
filter icon if displayed.
• Simultaneously depressing and holding
the positive and negative sides of the
minus/plus key for four seconds will lock
out the keypad.
•Time is not adjustable in this mode.
Figure I-P-6.Temporary manual override menu
screen
SCXG-SVX01B-EN
61
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
programming
Table I-P-1. Zone sensor BAYSENS019 option menu settings
option
1
description
morning warmup
value
factory setting
0
0 = disabled
1 = enabled
2
3
4
5
6
7
8
economizer minimum
position override
0 = disabled
1 = enabled
0 = Fahrenheit
1 = enabled
0 = disabled
1 = enabled
0 = 12 hours
1 = 24 hours
0 = disabled
1 = enabled
0 = disabled
1 = enabled
0 = 7 days (M,T,W,T,F,S,S)
1 = 3 days (M-F, S, S)
2 = 2 days (M-F, S,S)
1
temperature scale
supply air tempering
time clock
0
0
0
1
0
0
smart fan
Figure I-P-7.Temporary manual override run
mode screen
intelligent temperature recovery
programmable days/week
Option Menu and Keypad Operation
The operation menu sets all
programmable options built into your
ZSM. All options are retained in
permanent EEPROM memory.
9
10
programmable periods/day
programmable fan operation
2,3,4
4
0
0 = disallowed
1 = allowed
11
12
remote sensor installed
check filter interval
0 = No
1 =Yes
0
To access the option menu display,
simultaneously depress and hold the
mode button and program button for four
seconds.
0 = disabled
350
3000 to 50 in 50 hour
increments
13
14
15
16
display zone temperature
keypad lockout enabled
0 = no
1
1
3
1
1 = yes
The example in Figure I-P-8 shows option
15 displayed and indicates the initial timer
setting in the temporary override run
mode. The option value shown is in
0 = disabled
1 = enabled
1,2,3,4,5
initial time setting in temporary
override mode (hrs.)
buzzer options
0 = key press only
hours, and value selected is five hours.
1 = key press & check filter
2 = key press, check filter,
and system failures
When the option menu displays, the only
active buttons are the ↑ or ↓ arrow and
the “minus” and “plus” button. The ↑ or
↓ arrow increment through the available
options by number (1-24), and the
“minus” and “plus” button toggles
through the various option values
associated with each option number. See
Table I-P-1.
17
18
zone temperature calibration
baud rate
displays current temp.
with any offsets
0 = 1024 baud
1 = 1200 baud
0 = CV
1 = HP
45 to 98°F
43 to 96°F
45 to 98°F
43 to 96°F
0 offset
1
19
CV or HP operation
0
20
21
22
23
default cooling setpoint
default heating setpoint
minimum cooling setpoint
maximum heating setpoint
74°F
68°F
45°F
96°F
Note: On both programmable zone sensor
options, changing either option 9 or 10 will
erase the current program. To avoid
reprogramming, set options 9 and 10
before programming.
Figure I-P-8.Typical option menu screen
62
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
programming
Note: On both programmable zone sensor
options, changing either option 9 or 10 will
erase the current program. To avoid
reprogramming, set options 9 and 10
before programming.
Table I-P-2. Zone sensor BAYSENS020 option menu settings
option
description
value
factory
setting
0
1
2
3
4
5
6
7
8
morning warmup
0 = disabled
1 = enabled
0 = disabled
1 = enabled
0 = Fahrenheit
1 = enabled
economizer minimum
position override
temperature scale
1
0
0
0
0
0
0
Intelligent Copy
heat installed
0 = no
Note: Once you use Intelligent Copy, you
cannot use it again until you erase all
weekday and weekend time periods by
pressing ERASE for 5 seconds.
1 = yes
time clock
0 = 12 hours
1 = 24 hours
hydronic heat
0 = no
1 = yes
daytime warmup
programmable days/week
0 = disabled
1 = enabled
0 = 7 days (M,T,W,T,F,S,S)
1 = 3 days (M-F, S, S
2 = 2 days (M-F, S,S)
If your heating and cooling requirements
are the same for each day of the week,
and for each day of the weekend, your
ZSM is designed to employ Intelligent
Copy.
9
10
programmable periods/day
remote sensor installed
2,3,4
4
0
0 = no
1 = yes
To program the five weekdays, Monday
through Friday, program only one
weekday. Likewise, to program the
weekend, Saturday and Sunday, pro-
gram only one day. After programming
one weekday and/or one weekend day,
Intelligent Copy automatically copies your
program to the other days.
11
check filter interval
0 = disabled
350
3000 to 50 in 50 hour
increments
12
13
14
15
display zone temperature
keypad lockout rnabled
0 = no
1
1
3
1
1 = yes
0 = disabled
1 = enabled
1,2,3,4,5
initial time setting in temporary
override mode (hrs.)
buzzer options
0 = key press only
1 = key press & check filter
2 = key press, check filter,
and system failures
To use Intelligent Copy:
1) Be sure to select the seven day
programming format in the Options
Menu. SeeTables I-P-1 and I-P-2.
2) Be sure the entire program is blank.
3) Go to Program Menu.
16
zone temperature calibration
displays current temp.
with any offsets
0 offset
17
18
19
20
21
22
23
24
25
26
default cooling setpoint
default heating setpoint
default supply air cool
default supply air heat
default warmup
minimum cooling setpoint
maximum heating setpoint
minimum supply air cool
maximum supply air heat
maximum warmup
45 to 98°F (unoccupied)
43 to 96°F (unoccupied)
40 to 80°F (occupied)
60 to 160°F
50 to 90°F (occupied)
45 to 98°F
43 to 96°F
40 to 80°F (occupied)
60 to 160°F
74°F
68°F
55°F
100°F
68°F
45°F
96°F
40°F
160°F
90°F
4) Enter your setpoint parameters.
Intelligent Copy will automatically copy
these parameters to the other
weekdays.
5) Depress the DAY pushbutton until a
weekend day icon appears.
6) Enter setpoint parameters. Intelligent
Copy will automatically copy these
parameters to the other weekend day.
50 to 90°F
Remote Panel Indicator Signals From
UCM to ZSM
Table I-P-3. UCM signal conditions
The unit control module (UCM) can send
four signals to the ZSM.
signal
on
condition
heat
cool
on
FlashingHEAT is ON and indicated by a solid HEAT icon in the
Display. Failure in the cooling system indicated by a flashing COOL
FAIL icon.
FlashingCOOLING is ON and indicated by a solid COOL icon in the
Display. Failure in the cooling system indicated by a flashing
COOL FAIL icon.
FlashingSystem is OFF and indicated by a solid colon on the time of
day display. System is ON and indicated by a flashing colon on
the time of day display. System is in TEST mode and indicated by a
flashing TEST icon.
• Heat
• Cool
• On
on
off
on
• Service
Each of these four signals have three
different conditions. SeeTable I-P-3.
• Off
• On
• Flashing
service
flashing
ON System requires service and is indicated by a solid SERVICE
icon.There is a FAN failure indicated by a flashing SERVICE icon.
Note: There is no indication for a signal in the OFF condition. If option 16 is set to “2,” any flashing signals will
also give audible buzzer indication
SCXG-SVX01B-EN
63
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
programming
Figure I-P-9. BAYSENS019 complete icon display
Icon Descriptions
9. Displays the desired state of either
OCCUPIED or UNOCCUPIED.
10. The padlock symbol indicates that the
keyboard lockout is in effect.
11. This extends the mode selection box
in order to accommodate the
emergency heat mode on the ZSM heat
pump version.
12. Fan mode selection box.
13. Displayed in normal run mode when
displaying the actual room
temperature.
14. Displayed in option setting mode only.
15. Digits used to display temperature.
16. HEAT and COOL have two functions:
they indicate UCM status in normal run
mode and indicate which type of
setpoint is DESIRED during
programming and override setting.
17. Only used during programming and
override setting to indicate the
DESIRED setpoint temperature.
18. Flashes when check filter timer is
elapsed.
19. Flashing cooling fail status indicator.
20. Only used during UCP self-test mode.
21. Flashing service status indicator and
fan failure.
22. Flashing heating fail status indicator.
23. Operating MODE selection box.
BAYSENS019 Icon Descriptions
Refer to Figure I-P-9 for the written
descriptions below.
1. The four periods of the day used only
during programming mode.
2. The seven days of the week used
during programming and in normal
mode to display the day (not current in
Program Menu).
3. Four digits used to display the time of
day in normal run mode. Also used in
Programming Menu andTemporary
manual Override Menu, and options
menu.
4.Time of day colon used on the time of
day clock. The colon blinks to indicate
the UCM system is functional.
5. AM and PM are used to indicate the
time of day when using a 12 hour clock.
AM and PM are not used when a 24
hour clock is selected.
6. DAYS and HOURS are used to set the
override timer period.
7. Displayed in temporary manual
OVERRIDE mode, and when setting the
override timer.
8. Only used when setting the override
timer.
64
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
programming
Figure I-P-10. BAYSENS020 complete icon display
Programming, Run, and Menu.
10. The padlock symbol indicates that the
keyboard lockout is in effect.
BAYSEN020 Icon Descriptions
Refer to Figure I-P-10 for the written
descriptions below.
1. The four periods of the day used only
during programming mode.
2. The seven days of the week used
during programming and in normal run
mode.
3. Four digits used to display the time of
day in normal run mode. Also used in
Programming Mode, override timer
setting menu, and options menu.
4.Time of day colon used on the time of
day clock. The colon blinks to indicate
the UCM system is functional.
5. AM and PM are used to indicate the
time of day when using a 12 hour clock.
AM and PM are not used when a 24
hour clock is selected.
11. Operating mode selection box.
12. Displayed in normal run mode when
displaying the actual room
temperature.
13. Displayed in option setting mode only.
14. Digits used to display temperature.
15. HEAT and COOL have two functions:
they indicate UCM status in normal run
mode and indicate which type of
setpoint is DESIRED during
programming and override setting.
16. Only used during programming and
override setting to indicate the
DESIRED setpoint temperature.
17. Flashes when check filter timer is
elapsed.
18. Flashing cooling fail status indicator.
19. Only used during UCP self-test mode.
20. Flashing service status indicator and
fan failure.
6. DAYS and HOURS are used to set the
override timer period.
7. Displayed in temporary manual
OVERRIDE mode, and when setting the
override timer.
8. Only used when setting the override
timer.
9. Displays the desired state of either
OCCUPIED or UNOCCUPIED in the
21. Flashing heating fail status indicator.
22. Used in programming mode to set
HEAT SUPPLY AIR, COOL SUPPLY AIR,
and MORNINGWARM-UP
temperatures.
SCXG-SVX01B-EN
65
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
programming
Programming theTime Clock
Option
Programming
Follow the instructions below for
programming the time clock.
To review and change programs:
1.To review a program at any time, press
“Prog.” key. Programs display in the
sequence they were entered with
repeated presses of “Prog.” key.
2.To change a program, select that
program as outlined in step 1. Enter the
time of day and days of week just as in
the programming steps above. The old
program is overwritten with the new
selections. Press “Prog.” to store the
new program.
3.To delete an individual program, select
the program as in step 1 and press “h”
and “m” keys until “—:—” appears in
the display. Press either “Prog.” or “¹”
key until “—:—” flashes. The program
is deleted after a few seconds.
Setting theTime
1. Press “Prog.” key. 1234567 AM—:—
will appear in display. (Pressing “Prog.”
key again, display will show the number
of free programs “Fr 20”). Press again
to RETURN to 1st program.
2. Press “%” key, “~” ON symbol will
appear. Pressing the key again will
toggle to OFF “”. Select ON or OFF
for the program.
3. Press “h+” to select hour for switching
time.
4. Press “m+” to select minute for
switching time.
5. If the program is to occur every day of
the week, (24 hour time control) ignore
“Day” key and press “Prog.” key to
advance to program.
6. For 7 day time control, press “Day”
key. 1 2 3 4 5 6 (Monday through
Saturday) block of days appears in
display. Pressing “Day” key again, 1 2 3
4 5 (Monday through Friday) appears in
display. Repeated presses will cycle
through all days of the week and back
to 1 through 7 (Monday through
Sunday). Select day or block of days
desired.
Important: Depress the reset key before
beginning to set time and program.
1. Select military (24:00 hr.) or AM/PM
(12:00 hr.) time mode by depressing
and holding the “h” key while pressing
“+ 1h” key to toggle between military
and AM/PM. (AM appears in the display
when in AM/PM mode.)
2. Press and hold down “” key.
3. If setting the time when daylight
savings time is in effect, press “+ 1h”
key once (+ 1h will appear in display).
4. Set hour with “h” key. If AM or PM
does not appear in display, the unit is in
military time. See note above to
change display.
Manual Override
While in the “run” mode (“” symbol is
displayed), pressing the “%” key will
reverse the load status (switch load off if
it is on, or switch it on if it is off). A hand
symbol appears in the display to indicate
the override is active. At the next
5. Set minutes with “m” key.
6. Press “Day” key repeatedly to the day
of the week. (1 is Monday, 7 is Sunday)
7. Release “” key, colon will begin
flashing.
scheduled switching time, automatic time
control resumes, eliminating the override.
Note: If keys h + or m + are kept depressed
for longer than 2 seconds, a rapid advance
of figures will result.
Pressing the “%” key a second time
“[~]” appears in the display indicating
the load is permanently on.
7. Press “Prog.” key and repeat steps 2
through 6a to enter additional
programs of ON and OFF times. (Note
that more than one OFF time may be
programmed, enabling automatic
control or manual overrides.)
Pressing the “%” key a third time “[]”
appears in the display indicating the load
is permanently off.
The “Digi 20” electronic time switch is
freely programmable for each day of the
week in one minute increments. For easy
and quick programming, the following 4
block programs are available:
• Monday through Sunday
Pressing the “%” key a fourth time
returns to automatic, “%” appears in the
display.
8. Press “” key to enter run mode.
• Monday through Saturday
All days shown in the respective blocks
will switch on (or off) at the selected hour
and minute.
• Monday through Friday
• Saturday and Sunday
66
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
startup
Unit Startup Procedures
fraying belts in matched sets.
7. Measure amp draw at evaporator fan
motor terminals. FLA data is on the
motor nameplate.
8. After the system has stabilized (15 to 30
minutes), check and record operating
pressures and temperatures for all
circuits.
Startup
ƽWARNING
Hazardous Voltage w/Capaci-
tors!
ƽWARNING
Live Electrical Components!
Using the startup log on the following
pages, establish nominal conditions for
consistent measurements as follows:
Disconnect all electric power, including
remote disconnects before servicing.
Follow proper lockout/tagout proce-
dures to ensure the power cannot be
inadvertently energized. For variable
frequency drives or other energy storing
components provided byTrane or others,
refer to the appropriate manufacturer’s
literature for allowable waiting periods
for discharge of capacitors.Verify with an
appropriate voltmeter that all capacitors
have discharged. Failure to disconnect
power and discharge capacitors before
servicing could result in death or serious
injury.
During installation, testing, servicing and
troubleshooting of this product, it may
be necessary to work with live electrical
components. Have a qualified licensed
electrician or other individual who has
been properly trained in handling live
electrical components perform these
tasks. Failure to follow all electrical safety
precautions when exposed to live
electrical components could result in
death or serious injury.
• Leaving air greater than 60°F
• Entering air temperature = 70 to 90°F
• Entering water temperature > 60°F
• Inlet guide vanes at least halfway open
With all compressors running at full load:
1. Compute superheat from the suction
line pressure and temperature at the
compressor on each circuit. Adjust the
thermal expansion valve settings if
necessary. Superheat should be
between 12 and 17°F.
2. Inspect refrigerant flow in the liquid line
sight glass. Flow should be smooth and
even, with no bubbles once the system
has stabilized.
NOTICE
Compressor Damage!
Note: For additional information regard-
ing the safe discharge of capacitors, see
PROD-SVB06A-EN or PROD-SVB06A-FR.
Never manually or automatically pump
down system below 7 psig.This will
cause the compressor to operate in a
vacuum and result in compressor
damage.
Normal startup will occur provided that
Tracer Summit is not controlling the
module outputs or the generic BAS is not
keeping the unit off.To preventTracer
Summit from affecting unit operation,
removeTracerwiring and make required
changes to setpoint and sensor sources.
Pre-Startup Checklist
1.Verify electrical connections are tight.
2.Water-cooled: Access the liquid line
service valves.Verify the liquid line
service valve is open at startup.
To start the unit, complete the following
steps in order.
1. Apply power to the unit. Close the unit
disconnect switch option.
2. Make sure the liquid line service valves
are open on water cooled units.
3. Adjust setpoints at the HI.
Operating & Programming Instructions
Reference the IntelliPak Self-Contained
Programming Guide, PKG-SVP01B-EN,
for available unit operating setpoints and
instructions. A copy ships with each unit.
For units with the VFD option, reference
the installer guide that ships with each
VFD.
Note: Each compressor suction line
contains a low pressure sensor that will
shut the compressor down in low pressure
situations. See Table O-SO-2.
Note: A sufficient cooling load must be
visible to refrigerant circuit controls for
mechanical refrigeration to operate. If
necessary, temporarily reduce the dis-
charge air setpoint to verify the refrigeration
cycle operation.
3. Ensure system components are
properly set and installed.
4. Inspect all ductwork and connections.
5. Remove compressor and fan
assembly tie down bolts. On 20 - 38 ton
units, do not remove the fan assembly
shipping blocks.Tie down bolts if the fan
speed is 750 rpm or less.
6. Ensure fan rotation is in the direction of
the arrow on the fan housing. If it is
incorrect, verify the incoming power
phasing is correct. Switch wires on the
fan contact to properly phase fan if
necessary.
4. Check voltage at all compressor
terminals to ensure it is within 10% of
nameplate voltage.
5. Check voltage imbalance from these
three voltage readings at each
compressor. Maximum allowable
voltage imbalance, phase to phase is
2%.
6. Check amp draw at compressor
terminals. RLA and LRA is on the unit
nameplate.
7. Check the fan belt condition and tension.
Adjust the tension if belts are floppy or
squeal continually. Replace worn or
SCXG-SVX01B-EN
67
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
startup
Startup Log
Complete this log at unit startup.
Unit: ____________________________
Unit Location: _________________________________________
UnitVoltage: __________ __________ __________
A
B
C
Evaporator:
evaporator fan motor horsepower: __________ evaporator fan motor amps: __________ __________ __________
A
B
C
evaporator fan rpm (actual): ____________________
evaporator system static (from test and balance report or actual readings):
supply duct static: __________
return duct static: __________
evaporator air conditions with both compressors operating:
entering:
dry-bulb °F: __________
leaving:
dry-bulb °F: __________
wet-bulb °F: __________
wet-bulb °F: __________
evaporator system cfm (test and balance sheet or actual tested): __________
________________________________________________________________________________________________________________________
Compressor Amp Draw:
circuit A: __________ __________ __________ circuit B: __________ __________ __________
A
B
C
A
B
C
circuit C: __________ __________ __________ circuit D: __________ __________ __________
A
B
C
A
B
C
circuit E: __________ __________ __________ circuit F: __________ __________ __________
A
B
C
A
B
C
suction pressure, psig:
circuit A: __________
circuit E: __________
circuit B: __________
circuit F: __________
circuit B: __________
circuit F: _________
circuit B: __________
circuit F: _________
circuit B: __________
circuit F: _________
circuit B: __________
circuit F: _________
circuit C: __________
circuit D: __________
circuit D: __________
circuit D: __________
circuit D: __________
circuit D: __________
discharge pressure, psig: circuit A: __________
circuit E: __________
circuit C: __________
circuit C: __________
circuit C: __________
circuit C: __________
super heat °F:
circuit A: __________
circuit E: __________
circuit A: __________
circuit E: __________
circuit A: __________
circuit E: __________
liquid line pressure, psig:
sub cooling °F:
68
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
startup
___________________________________________________________________________________________________________________________
Water Cooled Units:
Circuit A:
entering water temperature °F: __________
leaving water temperature °F: __________
leaving water pressure, psig: __________
entering water pressure, psig: __________
Circuit B:
enter water temperature °F: __________
leaving water temperature °F: __________
leaving water pressure, psig: __________
entering water pressure, psig: __________
Circuit C:
entering water temperature °F: __________
leaving water temperature °F: __________
leaving water pressure, psig: __________
entering water pressure, psig: __________
Circuit D:
enter water temperature °F: __________
leaving water temperature °F: __________
leaving water pressure, psig: __________
entering water pressure - psig: __________
Circuit E:
enter water temperature °F: __________
leaving water temperature °F: __________
leaving water pressure, psig: __________
entering water pressure - psig: __________
Circuit F:
enter water temperature °F: __________
leaving water temperature °F: __________
leaving water pressure, psig: __________
entering water pressure - psig: __________
___________________________________________________________________________________________________________________________
Air Cooled Units:
(data taken from outside condensing unit)
voltage: __________ __________ __________
amp draw: __________ __________ __________
A
B
C
A
B
C
entering air temperature °F: __________
leaving air temperature °F: __________
refrigerant pressures at condenser, psig: __________/ __________ sub cooling at condenser °F: __________
SCXG-SVX01B-EN
69
Download from Www.Somanuals.com. All Manuals Search And Download.
general
information
Operation
Binary outputs
• V.O. relay
Points List - RTM Module
• Supply air temperature
• Supply fan status
• Unit status mode
• Zone CO2
Binary inputs
• Emergency stop
• External auto/stop
• Unoccupied/occupied
• Dirty filter
Points List -TracerTM LCI-I Module
ConstantVolume (CV) Points
Binary inputs
• Zone relative humidity
VariableAirVolume (VAV) Points
•VAV changeover with hydronic heat
• Airside economizer enable/disable
• Condensor type (air or water cooled)
• Condensor water flow status
• Emergency shutdown
• Local fan switch enable/disable
• Mechanical cooling lockout
• Mechanical heating lockout
• Mixed air temperature
Binary inputs
• Airside economizer enable/disable
• Condensor water flow input
• Emergency override
• Local fan switch enable/disable
• Mechanical cooling lockout
• Mechanical heating lockout
• Occupancy
Binary outputs
•VAV box drive max (VAV units only)
• CV unoccupied mode indicator (CV units
only)
• Alarm
• Fan run request
•Water pump request (water-cooled only)
• Occupancy
• Occupancy override
• Occupancy sensor
Binary outputs
• Airside economizer status
• Alarm status
• Compressor on/off status
• Condensor circuit information
• Condensor type (water or air cooled)
• Condensor waterflow status
• Condensor water pump status
Analog input
• Airside economizer damper minimum
position
Binary outputs
• Airside economizer status
• Alarm status
• Compressor on/off status
• Condensor circuit information
• Condensor water pump status
•Waterside economizer status
Analog output
• Outside air damper actuator
Heat Module:
• Analog output
Analog inputs
Points List - GBAS Module
• Airside economizer dry bulb setpoint
• Airside economizer minimum position
• Building static pressure input
• Building static pressure setpoint
• Daytime warm up setpoint
• Daytime warm up terminate setpoint
• Maintenance required time
• Occupancy bypass time
• Outdoor air damp min position setpoint
• Outdoor airflow minimum setpoint
• Outdoor air relative humidity
• Outdoor air temperature
• Supply air cooling setpoint
• Supply air cooling setpoint (default)
Analog inputs
Binary inputs
• Demand limit contacts
• Airside economizer dry bulb setpoint
• Airside economizer minimum setpoint
• Building static pressure input
• Maintenance required time
• Occupancy bypass time
• Outdoor air damper minimum position
setpoint
• Outdoor air relative humidity
• Outdoor air temperature
Binary outputs
• Dirty filter relay
• Refrigeration fail relay
• Heat fail relay
• Supply fan fail relay
• Active diagnostics
Analog inputs
• Unit start delay time setpoint
• Zone temperature
• Occupied zone cooling setpoint
• Occupied zone heating setpoint
• Unoccupied zone cooling setpoint
• Unoccupied zone heating setpoint or
minimum outside air flow setpoint
• Supply air cooling setpoint
• Supply air heating setpoint
• Zone temperature setpoint
• Zone temperature setpoint (default)
• Zone temperature setpoint limits
• Zone temperature setpoint offsets
• Zone temperature setpoint shift
Analog outputs
• Building static pressure status
• Alarm message
• Condensor saturated refrigerant temp.
• Condensor water temperature
• Condensor water temp (local)
• Cooling output status
• Exhaust fan status
• Heating output status
• Heating/cooling mode
• Mixed air temperature
Analog outputs
• Alarm message
• Building static pressure status
•Condensor saturated refrigerant temp
• Condensor water temperature
• Cooling output status
• Effective occupancy
• Exhaust fan status
• Heating output status
• Heating/cooling mode
• Supply air static pressure setpoint
Points List - ECEM Module
Analog inputs
• Return air temperature
• Return air humidity
• Morning warm up sensor temperature
• Outdoor air damper position
• Outdoor air enthalpy
In addition, units with aVOM have:
Binary inputs
•VOM mode A, unit off
• Morning warm up sensor temperature
• Outdoor air damper position
• Outdoor air enthalpy
• Outdoor air relative humidity
• Return air temperature
• Outdoor air flow
•VOM mode B, pressurize
•VOM mode C, exhaust
•VOM mode D, purge
• Outdoor air relative humidity status
• Outdoor air temperature status
• Return air temperature
•VOM mode E, purge w/duct pressure control
70
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
general
information
Operation
Unit Control Components
input of the RTM. The RTM must be
selected as the source for economizer
minimum position. If the RTM is the
selected source for economizer minimum
position, and if a valid resistance per
Table O-GI-1 is provided to the RTM
remote minimum position input, the OA
cfm compensation function will not
operate, even if enabled. “Default” is the
only possible source for economizer
minimum position when using the OA
cfm compensation function.
unoccupied and morning warmup mode.
They will return to the position shown on
the unit wiring diagram when the unit
returns to the occupied mode. This binary
output signals theVAV boxes or other
terminal devices to go full open.
The Modular Series IntelliPakself-
contained unit is controlled by a
microelectronic control system that
consists of a network of modules. These
modules are referred to as unit control
modules (UCM). In this manual, the
acronym UCM refers to the entire control
system network.
RTM Alarm Relay
This is a single pole, double throw relay
rated at a maximum voltage of 24 vac,
two amps max. Relay contacts can be
programmed from the unit human
interface. This relay can be programmed
to pick up on any one or group of
diagnostics from the unit human
interface.
These modules perform specific unit
functions using proportional/integral
control algorithms. They are mounted in
the unit control panel and are factory
wired to their respective internal compo-
nents. Each module receives and
interprets information from other unit
modules, sensors, remote panels, and
customer binary contacts to satisfy the
applicable request; i.e., economizing,
mechanical cooling, heating, ventilation.
Following is a detailed description of each
module’s function.
Table O-GI-1. Economizer remote minimum
position input resistance
input
economizer
Status/Annunciator Output
resistance
min. position
The status annunciator output is an
internal function within the RTM module
on CV andVAV units. It provides:
a. diagnostic and mode status signals to
the remote panel (LEDs) and to the
Human Interface.
0 - 30 ohms
0 %
0-100 % (linear)
100 %
30 - 240 ohms
240 - 350 ohms
> 350 ohms
N/A *
* Note: A resistance greater than 350 ohms is
assumed to be an open circuit. The system will use
the default minimum position value.
RTM Analog Outputs
b. control of the binary alarm output on
the RTM.
c. control of the binary outputs on the
GBAS module to inform the customer
of the operational status and/or
diagnostic conditions.
The RTM has two 0-10 vdc outputs: one
for the inlet guide vane option and one for
the economizer option. These outputs
provide a signal for one or two damper
actuators. There are no terminal strip
locations associated with these wires.
They go directly from pins on the RTM
circuit board to the actuator motor.
RTM Module Board - Standard
on all Units
The RTM responds to cooling, heating,
and ventilation requests by energizing the
proper unit components based on
information received from other unit
modules, sensors, remote panels, and
customer supplied binary inputs. It
initiates supply fan, exhaust fan, exhaust
damper, inlet guide vane positioning or
variable frequency drive output, and
airside economizer operation based on
that information.
Occupied/Unoccupied Inputs
There are four ways to switch to
occupied/unoccupied:
1. Field-supplied contact closure
hardwired binary input to the RTM
2. Programmable night setback zone
sensor
RTM Binary Outputs
The RTM has an output with pressure
switch proving inputs for the supply fan.
There is a 40 second delay from when
the RTM starts the supply fan until the fan
proving input must close. A fan failure
diagnostic will occur after 40 seconds.
This is a manual reset diagnostic, and all
heating, cooling, and economizer
functions will shut down. If this proving
input is jumped, other nuisance
3.Tracer Summit
4. Factory-mounted time clock
Reference the RTM points list.
VAV Changeover Contacts
These contacts are connected to the RTM
when daytime heating onVAV units with
internal or external hydronic heat is
required. Daytime (occupied) heating
switches the system to a CV unit
Note: Emergency stop and external auto/
stop, stop the unit immediately, emergency
stop generates a manual reset diagnostic
that must be reset at the unit human
interface. External auto-stop will return the
unit to the current operating mode when
the input is closed, so this input is auto
reset.
diagnostics will occur. If the proving input
fails to close in 40 seconds, the
economizer cycles to the minimum
position. This is a manual reset
diagnostic. External control of the fan is
not recommended.
operation. Refer to the unit wiring
diagram for the field connection terminals
in the unit control panel. The switch must
be rated at 12 ma @ 24 VDC minimum.
External Auto/Stop Switch
VAV Drive Max Output
RTM Remote Economizer Minimum
Position
The remote minimum position
potentiometer, BAYSTAT023A, provides
a variable resistance (0-270 ohms) to
adjust the economizer minimum position
from 0 to 100% when connected to the
economizer remote minimum position
A field-supplied switch may be used to
shut down unit operation. This switch is a
binary input wired to the RTM. When
opened, the unit shuts down immediately
and can be cancelled by closing the
switch. Refer to the unit wiring diagrams
(attached to the unit control panel) for
proper connection terminals. The switch
This is a single-pole, double-throw relay
rated at a maximum voltage of 24 vac,
two amps. The relay contacts of this relay
switch when theunit goes from the
occupied mode to the unoccupied mode
bymeans of the occupied binary input.
The contacts will stay switched during the
SCXG-SVX01B-EN
71
Download from Www.Somanuals.com. All Manuals Search And Download.
general
information
Operation
must be rated for 12 ma @ 24VDC
Table O-GI-2. RTM sensor resistance vs. temperature
minimum. This input will override all VOM
inputs, if the VOM option is on the unit.
temperature, °F
resistance, Ω ohms
346.1
241.7
temperature, °F
resistance, Ω ohms
11.60
11.31
11.03
10.76
10.50
10.25
10.00
9.76
-40
-30
-20
-10
-5
71
72
73
74
75
76
77
78
79
Occupied/Unoccupied Contacts
170.1
121.4
103.0
87.56
74.65
To provide night setback control if a
remote panel with night setback was not
ordered, install a field-supplied contact.
This binary input provides the building’s
occupied/unoccupied status to the RTM. It
can be initiated by a time clock, or a
building automation system control
output.The relay’s contacts must be rated
for 12 ma @ 24 VDC minimum. Refer to
the appropriate wiring diagrams
0
5
10
15
20
25
30
35
40
45
50
55
60
65
66
67
68
69
70
63.8
54.66
46.94
40.40
34.85
30.18
26.22
22.85
19.96
6.53
9.30
8.25
7.33
5.82
5.21
4.66
3.76
3.05
2.50
2.05
1.69
1.40
1.17
0.985
0.830
80
85
90
100
105
110
120
130
140
150
160
170
180
190
200
(attached to the unit control panel for the
proper connection terminals in the unit
control panel.
17.47
Emergency Stop Input
15.33
13.49
13.15
12.82
12.50
12.19
A binary input is provided on the RTM
board for installation of a field-supplied
normally closed (N.C.) switch to use
during emergency situations to shut
down all unit operations. When open, an
immediate shutdown occurs. An
emergency stop diagnostic enters the
human interface and the unit will require
a manual reset. Refer to the unit wiring
diagrams (attached to the unit control
panel for the proper connection
11.89
Table O-GI-3. RTM setpoint analog inputs
terminals. The switch must be rated for
12 ma @ 24 VDC minimum. This input
will override all VOM inputs, if the VOM
option is on the unit.
cooling or heating setpoint input, °F
(using RTM as zone temp. source)
ohms
cooling setpoint input, °F
(using RTM as supply air temp. source)
resistance, Ω
1084
40
45
50
55
60
65
70
75
80
NA
N A
40
45
50
55
60
65
70
75
80
85
9 0
992
899
796
695
597
500
403
305
208
111
VAV Box Option
To interlockVAV box operation with
evaporator fan and heat/cool modes,
wire theVAV boxes/air valves toVAV box
control connections on the terminal block.
Supply Duct Static Pressure Control
The RTM relies on input from the duct
pressure transducer when a unit is
equipped with IGV or VFD to position the
IGV or set the supply fan speed to
maintain the supply duct static pressure
to within the static pressure setpoint
deadband.
Table O-GI-4. RTM resistance value vs. system operating mode
resistance
applied to RTM mode
input terminals, ohms
CV units
VAV units
system mode
fan mode
auto
auto
auto
on
system mode
off
RTM Sensors
2320
4870
7680
10,770
13,320
16,130
19,480
27,930
off
RTM sensors include: zone sensors with
or without setpoint inputs and modes,
supply air sensor, duct static pressure,
outside air temperature, outside air
humidity, airflow proving, and dirty filter.
cool
auto
off
cool
auto
heat
heat
auto
on
on
auto
on
Note: Mode boundaries are 1000 to 40,000 ohms. Other boundaries are equal to the midpoint between the
nominal mode resistance.
72
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
general
information
Operation
Compressor Module (MCM -
Standard on all Units
Waterside Module - Standard
on all water-cooled units
The waterside module (WSM) controls all
water valves based on unit configuration.
In addition, the WSM monitors waterflow
proving and the following temperatures:
• entering water
• entering air low
• mixed air
• entering condenser water
• refrigerant circuit 3:
activates, the one with the highest priority
(VOM “A”) begins first, with VOM “E”
having lowest priority and beginning last.
The compressor module, (single circuit
and multiple circuit) energizes the
appropriate compressors and condenser
fans upon receiving a request for
mechanical cooling. It monitors the
compressor operation through feedback
information it receives from various
protection devices.
A description of the VOM binary inputs
follows below.
UNIT OFF sequence “A”
When complete system shut down is
required, the following sequence can be
used.
• Supply fan – off
• Supply fan VFD – off (0 Hz)
• Inlet guide vanes – closed
• Outside air dampers – closed
• Heat – all stages – off, modulating heat
output at 0 vdc
• saturated condenser
• evaporator frost
• motor winding
Human Interface Module -
Standard on all Units
• refrigerant circuit 4:
The human interface (HI) module enables
the operator to adjust the operating
parameters for the unit using it's 16-key
keypad on the human interface panel.
The HI panel provides a two line, 40
character, clear language (English,
Spanish, or French) LCD screen with unit
status information and menus to set or
modify operating parameters. It is
mounted in the unit’s main control panel
and accessible through the unit’s control
panel door.
• condenser
• Occupied/Unoccupied output – de-
energized
• VO relay – energized
• Exhaust fan (field-installed) - off
• Exhaust damper (field-installed) - closed
• evaporator
• motor winding
CoolingTower Interlock
To interlock condenser pump/tower with
cooling operation, wire the cooling tower
to an external 115 volt control power
source, to ground, and to control terminal
block. Normally open/closed contacts are
provided.
PRESSURIZE sequence “B”
This override sequence can be used if a
positively pressured space is desired
instead of a negatively pressurized space.
• Supply fan – on
• Supply fan VFD – on (60 Hz)
• Inlet guide vanes/VAV boxes – open
• Outside air dampers – open
• Heat – all stages – off, hydronic heat
output at 0 vdc
• Occupied/ unoccupied output -
energized
• VO relay - energized
• Exhaust fan (field-installed) - off
• Exhaust damper (field-installed) - closed
Heat Module
Remote Human Interface
Module Option
The optional remote-mount human
interface (RHI) panel has all the functions
of the unit-mounted version except for
service mode.To use a RHI, the unit must
be equipped with an optional
interprocessor communications bridge
(IPCB). Model number digit 32 (=2)
indicates if the ICPB was ordered with the
unit. If not, contact your localTrane
representative to order an ICPB kit for
field installation. The RHI can be located
up to 1,000 feet (304.8 m) from the unit. A
single RHI can monitor and control up to
four self-contained units if each one
contains an IPCB. The IPCB switches must
be set as SW1- off, SW2 - off, and SW3 -
on.
The heat module is standard on all units
with factory-installed heat. It controls the
unit heater to stage up and down to bring
the temperature in the controlled space
to within the applicable heating setpoint.
Also, it includes a freezestat, morning
warmup, and heating outputs.
EXHAUST sequence “C”
Ventilation Override Module
(VOM) Option
With the building’s exhaust fans running
and the unit’s supply fan off, the
conditioned space becomes negatively
pressurized. This is desirable for clearing
the area of smoke when necessary; i.e.
from an extinguished fire, to keep smoke
out of areas that were not damaged.
• Supply fan – off
The ventilation override module can be
field-configured with up to five differnent
override sequences for ventilation
override control purpose. When any one
of the module’s five binary inputs are
activated, it will initiate specified functions
such as; space pressurization, exhaust,
purge, purge with duct pressure control,
and unit off.
• Supply fan VFD – off (0 Hz)
• Inlet guide vanes – closed
• Outside air dampers – closed
• Heat – all stages – off, hydronic heat
output at 0 vdc
• Occupied/Unoccupied output – de-
energized
• VO relay – energized
• Exhaust fan (field-installed) - on
• Exhaust damper (field-installed) - open
Interprocessor Communications Board •
Option used with RHI
Once the ventilation sequences are
configured, they can be changed unless
they are locked using the HI. Once locked,
the ventilation sequences cannot be
unlocked.
The interprocessor communication board
expands communications from the unit's
UCM network to a remote human
interface panel. DIP switch settings on the
IPCB module for this application are;
switches 1 and 2 “off,” switch 3 “on.”
The compressors and condenser fans
disable during the ventilation operation. If
more than one ventilation sequence
SCXG-SVX01B-EN
73
Download from Www.Somanuals.com. All Manuals Search And Download.
general
information
Operation
PURGE sequence “D”
This sequence can purge the air out of a
building before coming out of unoccupied
mode of operation in aVAV system. Also,
it can be used to purge smoke or stale air.
• Supply fan – on
• Supply fan VFD – on (60 hz)
• Inlet guide vanes/VAV boxes – open
• Outside air damper – open
• Heat – all stages – off, modulating heat
output at 0 vdc
• Occupied/Unoccupied output –
energized
• VO relay – energized
• Exhaust fan (field-installed) - on
• Exhaust damper (field-installed) - open
Exhaust/Comparative
Ventilation Control Module
(VCM) - Available only with
Traq™ Damper Option
Enthalpy (ECEM ) Module -
Option used on units with
comparative enthalpy option
The ventilation control module (VCM) is
located in the airside economizer section
of the unit and linked to the unit’s UCM
network. Using a velocity pressure
transducer/solenoid (pressure sensing
ring) in the fresh air section allows the
VCM to monitor and control fresh air
entering the unit to a minimum airflow
setpoint. See Figure O-GI-2 for a detail
view of the velocity pressure transducer/
solenoid assembly.
The exhaust/comparative enthalpy
module receives information from the
return air humidity sensor, and the RTM
outside air temperature sensor and
outside air humidity sensor, the outside
air humidity sensor and temperature
sensor to utilize the lowest possible
enthalpy level when considering
economizer operation. In addition, it
receives space pressure information to
maintain the space pressure within the
PURGE with duct pressure control “E”
This sequence can be used when supply
air control is required for smoke control.
• Supply fan – on
• Supply fan VFD – on (if equipped)
• Inlet guide vanes – controlled by supply
air pressure control function with
supply air pressure high limit disabled
• Outside air dampers – open
• Heat – all stages – off, hydronic heat
output at 0 vdc
• Occupied/unoccupied output – energized
• VO relay – energized
An optional temperature sensor can be
connected to the VCM to enable control
of a field installed fresh air preheater.
Also, a field-provided CO2 sensor can be
connected to the VCM to control CO2
reset. The reset function adjusts the
minimum cfm upward as the CO2
concentrations increase. The maximum
effective (reset) setpoint value for fresh
air entering the unit is limited to the
system’s operating cfm.Table O-GI-5 lists
the minimum outside air cfm vs. input
voltage.
• Exhaust fan (field-installed) - on
• Exhaust damper (field-installed) - open
Figure O-GI-1. ECEM relative humidity vs.
voltage
Note: Each system (cooling, exhaust,
supply air, etc.) within the unit can be
redefined in the field for each of the five
sequences, if required. Also the definitions
of any or all of the five sequences may be
locked into the software by simple key
strokes at the human interface panel. Once
locked into the software, the sequences
cannot be changed.
Table O-GI-5. Minimum outside air setpoint
w/VCM module and Traq™ sensing
Unit
InputVolts
0.5 - 4.5 vdc
0.5 - 4.5 vdc
0.5 - 4.5 vdc
0.5 - 4.5 vdc
0.5 - 4.5 vdc
0.5 - 4.5 vdc
0.5 - 4.5 vdc
CFM
SXWG 20
SXWG 25
SXWG 30
SXWG 35
SXRG 20
SXRG 25
SXRG 32
6,350-8,500
7,250-10,625
7,250-12,750
7,250-14,875
7,250-8,500
7,250-10,625
7,250-13,600
Trane IntelliPak Lon-Talk
Communication Module (LCI-I
Option used on units with
Trane ICSTM or 3rd party
Building AutomationSystems)
The LonTalk Communication Interface
module expands communications from
the unit UCM network to aTraneTracer
SummitTM or a 3rd party building
automation system, utilizing LonTalk, and
allows external setpoint and
Figure O-GI-2.Velocity pressure transducer/
solenoid assembly
configuration adjustment and monitoring
of status and diagnostics.
74
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
general
information
Operation
Generic BuildingAutomation
System Module Option
Any of the setpoint or output control
parameters can be assigned to each of
the four analog inputs on the GBAS
module. Also, any combination of the
setpoint and/or output control param-
eters can be assigned to the analog
inputs through the HI.To assign the
setpoints apply an external 0-5 vdc
signal:
inhibit compressor and heater operation.
This can be set at the HI using the setup
menu, under the “demand limit definition
cooling” and “demand limit definition
heating” screens. A toggle switch, time
clock, or building automation system
control output can initiate demand
limiting.
The generic building automation system
module (GBAS) provides broad control
capabilities for building automation
systems other thanTrane’sTracer
system. A field provided potentiometer
or a 0-5 vdc signal can be applied to any
of the inputs of the GBAS to provide the
following points:
If the cooling demand limit is set to 50%,
half of the cooling capacity will disable
when the demand limit binary input
closes. The heating demand limit defini-
tion can only be set at 100%, unless the
unit has field-provided two-stage electric
heat. In that case, if the heating demand
limit is set to 50%, half or one stage of
heating disables when the demand limit
binary input closes. If the demand limit
definition is set to 100%, then all cooling
and/or heating will disable when the
demand limit input closes.
1. directly to the signal input terminals, or
2. to the 5 vdc source at the GBAS
module with a 3-wire potentiometer.
GBAS Analog Inputs
Four analog inputs that can be configured
to be any of the following:
(1) occupied zone cooling
(2) unoccupied zone cooling
(3) occupied zone heating
(4) unoccupied zone heating
(5) SA cooling setpoint
Note: There is a regulated 5 vdc output on
the GBAS module that can be used with a
potentiometer as a voltage divider. The
recommended potentiometer value is 1000-
100,000 ohms.
(6) SA heating setpoint
(7) space static pressure setpoint
(8) SA static pressure setpoint
The setpoints are linear between the
values shown inTable O-GI-6 on page 66.
ReferenceTable O-GI-7 on page 66 for
corresponding input voltage setpoints.
Following are formulas to calculate input
voltage or setpoint. SP = setpoint, IPV =
input voltage.
GBAS Diagnostics (Binary Outputs)
The GBAS can signal up to five alarm
diagnostics, which are fully mappable
through the setup menu on the HI. These
diagnostics, along with the alarm output
on the RTM, allow up to six fully
GBAS Binary Outputs
Five binary outputs to provide
diagnostics, signaling up to five alarms.
Each of the five (5) relay outputs can be
mapped to any/all of the available
diagnostics. Each output contains a dry
N.O. and N.C. contact with aVA rating of 2
amps at 24 VAC.
If the setpoint range is 50-90°F:
IPV = (SP - 50) (0.1) + 0.5
SP = [(IPV - 0.5)/0.1] + 50
mappable alarm outputs.
Each binary output has a NO and NC
contact with a rating of two amps at 24
VAC.The five binary outputs are factory
preset as shown on the unit wiring
diagram (on the unit control panel door).
However, these outputs can be field
defined in a variety of configurations,
assigning single or multiple diagnostics to
any output.
If the setpoint range is 40-90°F:
IPV = (SP - 40)(0.8) + 0.5
SP = [(IPV - 0.5)/0.08] + 40
GBAS Binary Input
One binary input for the self-contained
unit to utilize the demand limit function.
This function is operational on units with a
GBAS and is used to reduce electrical
consumption at peak load times. Demand
limiting can be set at either 50% or
100%. When demand limiting is needed,
mechanical cooling and heating (with
field-provided 2-stage electric heat only)
operation are either partially (50%), or
completely disabled (100%) to save
energy.The demand limit definition is
user definable at the HI panel. Demand
limit binary input accepts a field supplied
switch or contact closure. When the need
for demand limiting has been
If the setpoint range is 40-180°F:
IPV = (SP - 40)(0.029) + 0.5
SP = [(IPV - 0.5)/0.029] + 40
If the static pressure range is 0.03-0.3
iwc:
IPV = (SP - 0.03)(14.8) + 0.5
SP = [(IPV - 0.5)/14.8] + 0.03
For a complete listing of possible diagnos-
tics, see the IntelliPak Self-Contained
Programming Guide, PKG-SVP01B-EN.
For terminal strip locations, refer to the
unit wiring diagram for the GBAS.
If the static pressure range is 0.0-5.0 iwc:
IPV = (SP)(0.8) + 0.5
SP = [IPV/(0.8 + 0.5)]
GBAS Demand Limit Relay (Binary Input)
The GBAS allows the unit to utilize the
demand limit function by using a
discontinued, the unit’s cooling/heating
functions will again become fully enabled.
normally open (N.O.) switch to limit the
electrical power usage during peak
periods. Demand limit can initiate by a
toggle switch closure, a time clock, or an
ICS control output. These contacts must
be rated for 12 ma @ 24 VDC minimum.
GBAS Communication (Analog Inputs)
The GBAS accepts external setpoints in
the form of analog inputs for cooling,
heating, supply air pressure. Refer to the
unit wiring diagram for GBAS input
wiring and the various desired setpoints
with the corresponding DC voltage
inputs.
When the GBAS module receives a
binary input signal indicating demand
limiting is required, a command initiates
to either partially (50%) or fully (100%)
SCXG-SVX01B-EN
75
Download from Www.Somanuals.com. All Manuals Search And Download.
general
information
Operation
Table O-GI-6. GBAS analog input setpoints
control parameter
signal range
setpoint range
50 to 90°F
occupied zone cooling setpoint
(CV units only)
0.5 to 4.5 vdc
unoccupied zone cooling setpoint
(CV and VAV)
0.5 to 4.5 vdc
50 to 90°F
50 to 90°F
50 to 90°F
40 to 90°F
40 to 180 F
occupied zone heating setpoint
(CV units only)
0.5 to 4.5 vdc
0.5 to 4.5 vdc
0.5 to 4.5 vdc
0.5 to 4.5 vdc
unoccupied zone heating setpoint
(CV and VAV)
supply air cooling setpoint
(VAV units only)
supply air hydronic heating setpoint
(VAV units only)
space static pressure setpoint
0.5 to 4.5 vdc
0.5 to 4.5 vdc
0.03 to 0.30 IWC
0.0 to 5.0 IWC
supply air pressure setpoint
(VAV units only)
Notes: 1. Input voltages less than 0.5 vdc are considered as 0.5 vdc input signal is lost, the setpoint will
“clamp” to the low end of the setpoint scale. No diagnostic will result from this condition.
2. Input voltages greater than 4.5 vdc are considered to be 4.5 vdc.
3. The actual measured voltage is displayed at the HI.
Table O-GI-7. GBAS input voltage corresponding setpoints
temp.
°F
temp.
°F
temp
°F
temp
°F
volts
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.5
volts
1.6
1.7
1.8
1.9
2.0
2.1
2.2
2.3
2.4
2.5
volts
2.6
2.7
2.8
2.9
3.0
3.1
3.2
3.3
3.4
3.5
volts
2.7
2.8
2.9
3.0
3.1
3.2
3.3
3.4
3.5
3.6
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
76
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
general
information
Operation
Waterside Components
range of water temperature rise through
the condenser when entering fluid
cooling. If the economizer is unable to
maintain the supply air setpoint, the unit
control module brings on compressors as
required to meet the setpoint.
Waterside components consist of water
piping, water valves, water flow switch
option, water cooled condensers (SXWF
only), and the economizer option.
temperature is less than 58°F (15°C). This
option allows the compressor to operate
with entering fluid temperature down to
35°F (2°C). The minimum valve position
to maintain minimum condenser flow
rates is user-defined at the HI. This valve
drives closed if the unit shuts down or if a
power failure occurs.
The waterside economizer includes a coil,
modulating valves, controls, and piping
with cleanouts. The coil construction is ½-
inch (13 mm) OD seamless copper tubes
expanded into aluminum fins. The
evaporator and economizer coils share a
common sloped (IAQ) drain pan. Drain
pan options are either galvanized or
stainless steel, and are insulated and
internally trapped.
Water Purge
This user-definable feature allows the
user to select a purge schedule to
automatically circulate water through the
economizer and condensers periodically
during non-operational times. This allows
fresh chemicals to circulate in waterside
heat exchangers. This feature is on all
units and is defined at the HI.
Water Flow Switch Option
A water flow switch is factory installed in
the condenser water pipe within the unit.
Whenever the flow switch detects a
water flow loss prior to or during
mechanical cooling, compressor
operation locks out and a diagnostic code
displays. If water flow is restored, the
compressor operation automatically
restores.
The waterside economizer coil is avail-
able with either a two or four row coil,
with no more than 12 fins per inch. The
tubes are arranged in a staggered
pattern to maximize heat transfer.The
coil has round copper supply and return
headers with removable cleanout and
vent plugs. The optional mechanical
cleanable economizer has removable
cast iron headers to allow easy mechani-
cal cleaning of the tubes. The waterside
working pressure is rated for 400 psig
(2758 kPa).
Water Piping Options
Water piping is factory-installed with left-
hand connections on units without a
waterside economizer. Units can be
ordered with either basic piping or
intermediate piping. Also, units with
waterside economizers can be set for
either variable or constant water flow at
the HI. See Figures O-GI-3, O-GI-4, and O-
GI-5 for detailed piping configuration
information.
Water-Cooled Condensers
Units that are set up for variable water
flow will modulate a water valve to
maintain a user-defined condensing
temperature setpoint. Condensing
temperature will be referenced utilizing
factory installed sensors located at each
condenser.
With compatible piping configurations,
the unit can be configured to provide:
1. Constant water flow with basic or
intermediate piping or
2. Variable water flow (head pressure
control) with intermediate piping only.
Waterside Economizer Flow Control
Units equipped with a waterside
economizer can be set from the human
interface panel for variable or constant
water flow.
Table O-GI-8. Condenser water piping
connection sizes
unit size
inlet pipe
2 1/2 NPT
outlet pipe
2 1/2 NPT
Constant water flow is for condenser
pumping systems that are not capable of
unloading the water-pumping system.
Variable water flow maximizes energy
saving by unloading the water pumping
system.
SXWG 20, 25,
Constant Water Flow
30, 32, 35
Two-way modulating control shutoff
valves are wired, controlled, and installed
in the unit. One valve is located in the
economizer’s water inlet, and the other is
in the condenser bypass water inlet.
When the waterside economizer enables,
the two-way valves modulate to maintain
the discharge air temperature setpoint.
As the economizer valve opens, the
condenser bypass valve closes, and vice
versa. Full water flow is always
Waterside Economizer Option
The waterside economizer option takes
advantage of cooling tower water to
either precool the entering air to aid the
mechanical cooling process or, if the
water temperature is low enough,
Basic Water Piping
This option is available on units without a
waterside economizer and with
condenser water applications above 54°F
(12.2°C) that do not require condensing
pressure control. Left hand water
connections and piping are extended to
the unit exterior. Manifold piping is
factory installed.
provide total system cooling. Waterside
economizing enables when the unit’s
entering water temperature is below the
unit’s entering mixed air temperature by
a minimum of 4°F plus the economizer’s
approach temperature. The approach
temperature default is 4°F. Waterside
economizing disables when the unit’s
entering water temperature is not below
the unit’s entering mixed air temperature
by at least the water economizer
maintained through the condensers. Both
valves will close in the event of a power
failure.
Intermediate Water Piping
Variable Water Flow
This option provides condensing
temperature control when the unit is
configured (user defined at the HI) for
variable water flow with or without a
waterside economizer. A two-way
modulating control valve is wired and
installed in the unit to maintains a specific
Two-way modulating control shutoff
valves are wired, controlled, and installed
in the unit. One valve is located in the
economizer’s water inlet, and the other is
in the condenser water inlet. When the
economizer valve is active, the
approach temperature. The approach
temperature defaults to 4°F.The
economizer acts as the first stage of
condenser bypass valve closes. The
SCXG-SVX01B-EN
77
Download from Www.Somanuals.com. All Manuals Search And Download.
general
information
Operation
economizer valve modulates, thus water
flow through the unit modulates. If the
water is cool enough for economizing, but
mechanical cooling is also required, the
economizer valve fully opens to establish
full water flow through the condensers.
Whenever the water is too warm for
economizing and there is a call for
cooling, the economizer valve fully closes
and the bypass valve fully opens,
establishing full water flow through the
condensers. Full water flow is always
maintained through the condensers
when mechanical cooling is required.
Both valves close whenever cooling is
not required, and in the event of a power
failure.
Condenser 1
Condenser 1
Condenser 2
Condenser 2
V2
Figure O-GI-3. Basic water piping, constant
water flow
Figure O-GI-4. Intermediate water piping,
variable water flow
Condenser 1
Condenser 2
Economizer
V1
V2
Figure O-GI-5. Intermediate piping with waterside economizer, variable or
constant water flow
78
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
general
information
Operation
UnitAirside Components
A field installed indicator device may be
wired to relay terminals to indicate when
filter service is required. Contacts are
rated at 115 VAC and are powered by a
field supplied transformer.
modes to prevent supply air duct
overpressurization. However, if for any
reason the supply air pressure exceeds
the user-defined supply air static
The unit’s air delivery system consists of
dampers, enthalpy switch option, airside
economizer option, filters, low ambient
sensors, and factory mounted single or
double wall plenums.
pressure limit set at the HI panel, the
supply fan/VFD shuts down and the IGVs
close. The unit will attempt to restart, up
to three times. If the overpressurization
condition still occurs on the third restart,
the unit shuts down and a manual reset
diagnostic sets and displays at the HI.
Low Ambient Sensor (Air-Cooled Units)
The low ambient sensor is field-installed
on air-cooled units. Position it in a location
subject to ambient temperatures only
and not exposed to direct sunlight or
exhaust fans.
Supply Air Fan
The unit has a single supply fan that runs
at a constant speed. However, the fan
may have the IGV or VFD option that
modulates airflow based on supply air
temperature control. Pressing the stop
key on the HI will turn the supply fan off.
The fan is on continuously when a CV unit
is in occupied mode and except when a
unit is in the night heat/morning warmup
mode. During the night heat and setback
mode the fan cycles on and off in
Variable Frequency Drive Option
The variable frequency drive (VFD) is
driven by a modulating 0-10 vdc signal
from the RTM module. A pressure
transducer measures duct static
pressure, and the VFD adjusts the fan
speed to maintain the supply air static
pressure within an adjustable user-
defined range. The range is determined
by the supply air pressure setpoint and
supply air pressure deadband, which are
set at the HI panel.
The low pressure cutout initiates based
on the ambient temperature. A time
delay on the low pressure cutout initiates
for ambient temperatures between 50
(zero minutes) and 0°F (10 minutes). This
helps to prevent nuisance low pressure
cutout trips.
response to a call for heat. SeeTable O-
GI-9 for available fan horsepower.
Inlet GuideVane Option
Inlet guide vanes (IGV’s) are driven by a
modulating 0-10 vdc signal from the RTM
module. A pressure transducer
Low Entering Air Temperature Sensor
This is standard on all units with a
hydronic coil or waterside economizer. It
can also be ordered as an option.
measures duct static pressure, and the
IGVs modulate to maintain the supply air
static pressure within an adjustable user-
defined range. The range is determined
by the supply air pressure setpoint and
supply air pressure deadband, which are
set through the HI panel.
VFDs provide supply fan motor speed
modulation. The drives will accelerate or
decelerate as required to maintain the
supply air static pressure setpoint.
A thermostat limit switch is factory
mounted on the unit’s entering air side
with a capillary tube serpentine across
the coil face. If the temperature falls
below 35°F (2°C), the fan shuts down and
the waterside economizer and/or
hydronic heat valve options open to allow
full water flow.The heat output also
energizes. A manual reset is required.
The low entering air temperature
setpoint is adjustable at the HI.
VFD with Bypass
Bypass control is an option that provides
full nominal airflow in the event of drive
failure. The user must initiate the bypass
mode at the HI panel. When in bypass
mode,VAV boxes need to be fully open.
The self-contained unit will control
heating and cooling functions to maintain
setpoint from a user-defined zone sensor.
Supply air static pressure limit is active in
this mode.
IGV assemblies installed on the supply
fan inlet regulate fan capacity and limit
horsepower at lower system air require-
ments. When in any position other than
full open, the vanes pre-spin the air in the
same direction as the supply fan rotation.
As the vanes approach the full-closed
position, the amount of “spin” induced by
the vanes increases at the same time
that intake airflow and fan horsepower
diminish. The IGVs will close when the
supply fan is off.
High Duct Temperature Thermostat
A factory-supplied temperature limit
switch with reset element detects the
supply air duct temperature. This sensor
should be field-installed downstream
from the unit’s discharge in the supply air
duct. If the supply air duct temperature
exceeds 240°F (115.6°C), the unit shuts
down and displays a diagnostic. A
manual reset is required at the unit. The
high duct temperature can be adjusted at
the thermostat.
For more detailed information on VFD
operation, reference the VFD technical
manual that ships with the unit.
Supply Air Static Pressure Limit
Airside Economizer Option
The opening of the IGVs andVAV boxes
coordinate during unit startup and
transition to/from occupied/unoccupied
Units with the airside economizer option
are equipped with the necessary control
sequences to use outside air for the first
Dirty Filter Sensor Option
A factory installed pressure switch
senses the pressure differential across
the filters. When the differential pressure
exceeds 0.9-inches (23 mm) WG, contact
closure occurs and the HI will display a
diagnostic. The unit will continue to run
until you replace the air filters.
SCXG-SVX01B-EN
79
Download from Www.Somanuals.com. All Manuals Search And Download.
general
information
Operation
stage of cooling, in occupied or
source has lower enthalpy.This allows
true comparison of outdoor air and return
air enthalpy by measurement of outdoor
air and return air temperatures and
humidities. A factory-installed control
board, with field-installed outside and
return air temperature and relative
humidity sensors, allows monitoring of
outside and return air.
module (VCM) utilizes the velocity
pressure input, the RTM outdoor air
temperature input, and the minimum
outside air cfm setpoint to modify the
volume (cfm) of fresh air entering the unit
as the measured airflow deviates from
setpoint.
unoccupied mode and when ambient
conditions are favorable for economizing.
Inherent in the unit controller is the ability
to suppress the setpoint below the
normal unit setpoint. This allows the
building to improve comfort levels when
possible, and at the same time, optimize
building mechanical cooling operation for
peak operating efficiency. An outside air
temperature and relative humidity
sensor are provided to allow monitoring
of reference enthalpy and are field
installed.
When the optional preheat temperature
sensor is installed at the auxiliary
temperature on the VCM and the preheat
function is enabled, the sensor will
monitor the combined (averaged) fresh
air and return air temperatures. As this
mixed air temperature falls below the
preheat actuate temperature setpoint,
the VCM activates the preheat binary
output to control a field-installed heater.
The output deactivates when the tem-
perature rises 5°F above the preheat
actuate temperature setpoint.
Note: If comparative enthalpy is not
ordered, the standard method is to
compare outdoor air enthalpy with the
fixed reference enthalpy. The reference
enthalpy is set through the human interface
panel.
If the unit has the ECEM board, econo-
mizer operation enables when the
outside air enthalpy is less than 25 BTU’s/
lb. default (adjustable 19-28 BTU’s/lb).
During occupied mode, the outside air
damper opens to 15% (adjustable 0-
100% at the HI) for ventilation purposes.
Also, the ability to alter the outside air
damper position to compensate forVAV
supply air modulation is inherent in the
unit controls, and can be enabled by the
operator.
Units with comparative enthalpy control
are equipped with the necessary control
sequences to allow using outside air for
the first stage of cooling, in occupied or
unoccupied mode and when ambient
conditions are favorable for economizing.
Inherent in the unit controller is the ability
to suppress the setpoint below the
normal unit setpoint. This allows the
building to improve comfort levels when
possible, and at the same time, optimize
building mechanical cooling operation for
peak operating efficiency.
Using a field-installed CO2 sensor with
CO2 reset enabled, as the CO2 concentra-
tion increases above the CO2 reset start
value, the VCM modifies the minimum
outside air cfm setpoint to increase the
amount of fresh air entering the unit. The
setpoint adjusts upward until reaching the
CO2 maximum reset value. The maxi-
mum effective (reset) setpoint value for
fresh air is limited to the system’s
If the unit does not have an ECEM board,
it will economize when the O/A tempera-
ture falls below the O/A economizer
setpoint.
Economizer operation enables when the
outside air enthalpy is 3 BTu/lb less than
the return air enthalpy. During occupied
mode, the outside air damper opens to
15% (adjustable 0-100%) for ventilation
purposes. Also, the ability to alter the
outside air damper position to compen-
sate forVAV supply air modulation is
inherent in the unit controls, and can be
enabled by the operator.
operating cfm. As the CO2 concentration
decreases, the effective (reset) setpoint
value adjusts downward toward the
minimum outside air cfm setpoint. See
Figure O-GI-6 for an airflow cfm vs. CO2
concentration curve.
The mixing box fabrication is galvanized
steel. Opposed low leak damper blades
are fabricated from galvanized steel and
rotate on rustproof nylon bushings. A
factory installed 24V modulating spring
return actuator controls both damper
positions.
Standard Two-Position Damper Interface
Units with the two-position damper
interface are provided with a 0-10 VDC
control output suitable for controlling a
field-provided modulating actuator. In
occupied mode, the output drives to the
maximum position.
When outdoor conditions are not suitable
for economizer cooling, the enthalpy
control disables the economizer function
and permits the outdoor air damper to
open only to the minimum position.
The mixing box fabrication is galvanized
steel. Opposed low leak damper blades
are fabricated from galvanized steel and
rotate on rustproof nylon bushings. A
factory installed 24V modulating spring
return actuator controls both damper
positions.
Airside Economizers withTraqTM Damper
Outside air enters the unit through the
TraqTM damper assembly and is
measured by velocity pressure flow
rings. The velocity pressure flow rings
are connected to a pressure transducer/
solenoid assembly, which compensates
for temperature swings that could affect
the transducer.The ventilation control
On water-cooled units, compressor
operation lockout will not occur at low
ambient air temperatures. However,
lockout will still occur via low condenser
water temperature.
Airside Economizer Interface
Units with airside economizer interface
are equipped with the necessary control
sequences to allow using outside air for
the first stage of cooling, in occupied or
unoccupied mode and when ambient
conditions are favorable for economizing.
Inherent in the unit controller is the ability
to suppress the setpoint below the
The outdoor air dampers drive fully
closed whenever the supply air fan is off,
provided there is power to the unit.
Comparative Enthalpy Control
normal unit setpoint. This allows the
building to improve comfort levels when
possible, and at the same time, optimize
building mechanical cooling operation for
Comparative enthalpy controls the
economizer operation and measures
temperature and humidity of both return
air and outside air to determine which
80
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
general
information
Operation
peak operating efficiency. An outside air
temperature and relative humidity
sensor are provided for field installation
to monitor reference enthalpy.
Economizer operation enables when the
outside air enthalpy is less than 25 BTu/lb
(adjustable 19-28 BTu/lb.). During
occupied mode, the outside air damper
opens to 15% (adjustable 0-100%) for
ventilation purposes. Also, the ability to
alter the outside air damper position to
compensate forVAV supply air
modulation is inherent in the unit controls,
and can be enabled by the operator. An
analog 2-10 VDC output (adjustable (0-10
VDC) is provided to modulate the field-
provided 30 second damper actuators
(adjustable 1-255 seconds).
temperature and relative humidity
sensors, are provided for monitoring
outside and return air.The sensors are
field installed. Economizer operation
enables when the outside air enthalpy is
3 BTU’s/lb. less than the return air
enthalpy. During occupied mode, the
outside air damper opens to 15%
(adjustable 0-100%) for ventilation
purposes. Also, the ability to alter the
outside air damper position to
Air-Cooled Condensers
Model SXRF units are designed for use
with the remote air-cooled condenser,
model CXRC. For more information, see
the air-cooled condenser Installation,
Owner, and Diagnostic Manual, CXRC-
SVX01A-EN.
Condenser fans will stage per a user-
defined setting. If the condenser is
equipped with head pressure control (air
modulation on last stage of condenser
capacity), the condenser airflow will
modulate to maintain condensing
temperature setpoint. Condensing
temperature is determined by sensors
located at each condenser coil.
compensate forVAV supply air
modulation is inherent in the unit
controls, and can be enabled by the
operator. An analog 2-10VDC output
(adjustable (0-10 VDC) is provided to
modulate the field-provided 30-second
damper actuators (adjustable 1-255
seconds).
Airside Economizer Interface with
Comparative Enthalpy
Units with airside economizer interface
and comparative enthalpy are equipped
with the necessary control sequences to
allow using outside air for the first stage
of cooling, in occupied or unoccupied
mode and when ambient conditions are
favorable for economizing. Inherent in the
unit controller is the ability to suppress
the setpoint below the normal unit
setpoint. This allows the building to
improve comfort levels when possible,
and at the same time, optimize building
mechanical cooling operation for peak
operating efficiency. A factory-installed
control board, with outside and return air
Figure O-GI-6. CO2 reset function, outside air vs. CO2
SCXG-SVX01B-EN
81
Download from Www.Somanuals.com. All Manuals Search And Download.
general
information
Operation
Input Devices and System
Functions
Following are basic input device and
system function descriptions used within
the UCM network on IntelliPak self-
contained units. Refer to the unit wiring
diagrams for specific connections.
Compressor MotorWindingThermostats
A thermostat is embedded in the motor
windings of each compressor. Each
thermostat opens if the motor windings
exceed approximately 221°F.The
will restart when the evaporator
temperature rises 10°F above the coil
frost cutout temperature and the
minimum three minute “off” time
elapses.
thermostat resets automatically when the
winding temperature decreases to
approximately 181°F. Rapid cycling, loss
of charge, abnormally high suction
temperatures, or the compressor running
backwards could cause the thermostat to
open. During a request for compressor
operation, if the compressor module
detects a problem outside of it's normal
parameters, it turns any operating
compressor(s) on that circuit off, locks
out all compressor operation for that
circuit, and initiates a manual reset
diagnostic.
Saturated CondenserTemperature
Sensors
The saturated condenser temperature
sensors are analog input devices.They
are mounted inside a temperature well
located on a condenser tube bend on air-
cooled units, and in the condenser shell
on water-cooled units.The sensors
monitor the saturated refrigerant
temperature inside the condenser coil
and are connected to the SCM/MCM for
circuits 1 and 2 (air or water cooled), and
WSM for circuits 3 and 4 (only water-
cooled).
Water Purge
NOTICE
ProperWaterTreatment!
The use of untreated or improperly
treated water in coils may result in
scaling, erosion, corrosion, algae or
slime. It is recommended that the
services of a qualified water treatment
specialist be engaged to determine what
water treatment, if any, is required.Trane
assumes no responsibility for equipment
failures which result from untreated or
improperly treated water or saline or
brackish water.
Low Pressure Control
Low pressure (LP) control is
Head Pressure Control
Head pressure control is accomplished
using two saturated refrigerant
temperature sensors on air-cooled units
and up to four sensors on water-cooled
units.
accomplished using a binary input device.
LP cutouts are mounted on the suction
lines near the compressors.The LP
control contacts close when the suction
pressure exceeds 27 4 psig. If the LP
control is open when a compressor
starts, none of the compressors on that
circuit will operate.They are locked out
and a manual reset diagnostic initiates.
The LP cutouts open if the suction
pressure approaches 7 4 psig. If the LP
cutout opens after a compressor starts,
all compressors operating on that circuit
will turn off immediately and will remain
off for a minimum of three minutes.
During the unoccupied mode, water-
cooled units will periodically circulate
water through the condensers and
waterside economizer if the user has
enabled the purge function at the HI. The
water purge function circulates water to
introduce fresh water-treatment
Air-cooled units: During a request for
compressor operation when the con-
densing temperature rises above the
lower limit of the control band, the
compressor module (SCM/MCM)
sequences condenser fans on. If the
operating fans cannot bring the condens-
ing temperature to within the control
band, more fans turn on. As the satu-
rated condensing temperature ap-
proaches the lower limit of the control
band, fans sequence off. The minimum
on/off time for condenser fan staging is
5.2 seconds. If the system is operating at
a given fan stage below 100% for 30
minutes the saturated condensing
temperature is above the efficiency
check point setting, a fan stage will be
added. If the saturated condensing
temperature falls below the efficiency
check point setting, fan control remains at
the present operating stage. If the fan
stage cycles four times within a 10
minute period, the lower limit tempera-
ture is redefined as being equal to the
lower limit minus the temporary low limit
suppression setting.The unit will utilize
this new low limit temperature for one
hour to reduce condenser fan short
cycling.
chemicals and help prevent water
stagnation.The number of hours between
each periodic purge, or purge duration, is
user-defined at the HI between 1-999
hours. If the periodic purge timer expires
while the unit is in occupied mode, it will
wait for the next available unoccupied
time before initiating water purge.
If the LP cutout trips four consecutive
times during the first three minutes of
operation, the compressors on that circuit
will lock out and a manual reset diagnos-
tic initiates.
Contrary, if a request for cooling occurs
during a purge sequence, purge will
terminate and cooling will commence.
Evaporator Temperature Sensor
Frostat™
The evaporator temperature sensor is an
analog input device used to monitor
refrigerant temperature inside the
evaporator coil to prevent coil freezing. It
is attached to the suction line near the
evaporator coil with circuits 1 and 2
connected to the SCM/MCM and circuits
3 and 4 connected to theWSM.The coil
frost cutout temperature is factory set at
30°F. It is adjustable at the HI from 25-35°F.
The compressors stage off as necessary
to prevent icing. After the last
Compressor Circuit Breakers
The compressors are protected by circuit
breakers that interrupt the compressor
power supply if the current exceeds the
breakers “must trip” value. During a
request for compressor operation, if the
compressor module (MCM or SCM)
detects a problem outside of it’s normal
parameters, it turns any operating
compressor(s) on that circuit off, locks
out all compressor operation for that
circuit, and initiates a manual reset
diagnostic.
compressor stages off, the compressors
82
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
general
information
Operation
Water-cooled: Units withoutWSE, the
condenser valve modulates to maintain
an average saturated condenser tem-
perature. Units withWSE, if economizing
and mechanical cooling is necessary the
economize valve will sacrifice free
cooling and modulate to maintain
condensing saturated temperature. If not
economizing, the condenser valve will
modulate to maintain condensing
saturated temperature.
suited to maintain cooling requirements.
It is mounted in the return air path and
connected to the ECEM.
If the LEATPD is on a unit with factory-
installed heat, it is mounted in the heat
section and connected to the heat
module. If the entering air temperature to
the heating coil falls to 40°F, the normally
open contacts on the LEATPD close and
cause the following events:
a. the hydronic heat actuator fully opens.
b. the supply fan turns off
c. the outside air damper closes
d. the SERVICE light at the remote zone
sensor option turns on.
Supply Fan Circuit Breaker, Fuses, and
Overloads
The supply fan motor is protected by
either circuit breakers fuses or a
combination of fuses and overloads,
dependent upon unit configuration.
Circuit breakers are used on units
without aVFD.They will trip and interrupt
the motor power supply if the current
exceeds the breaker trip value.The RTM
shuts all system functions off when
detecting an open fan proving switch.
Units with a VFD have fuses to protect
theVFD and motor. Units with aVFD w/
bypass have fuses to protect VFD circuit
and overloads to protect the motor when
in bypass.
Water-cooled units without head pres-
sure control will lock out mechanical
cooling at entering condenser water
temperatures below 54°F. Mechanical
cooling will resume when the entering
condenser water temperature exceeds
58°F.
e. a LEATPD diagnostic displays at the
human interface panel.
If the LEATPD is on a water-cooled unit
without factory-installed heat, it is wired
to the WSM. It will trip if the entering
water temperature falls to 34°F, open the
economizer valve, and energize the
pump output.
LowAmbient Control (Air-Cooled Units
Only)
The low ambient modulating output on
the compressor module is functional on
all units with or without the low ambient
option. When the compressor module
stages up to it's highest stage (stage 2 or
3 depending on unit size), the modulating
output is 100% (10 VDC). When the
control is at stage 1, the modulating
output (0-10 VDC) controls the saturated
condensing temperature to within the
programmable condensing temperature
low ambient control point.
Supply Air Temperature Low Limit
The supply air temperature low limit
function uses the supply air temperature
sensor input to modulate the economizer
damper to the minimum position if the
supply air temperature falls below the
occupied heating setpoint temperature.
High DuctTempThermostat Option On
Units with an LCI-I
The high duct temperature thermostats
are binary input devices used on units
with aTrane communication interface
module (Tracer/LCI-I).They provide a high
limit unit shutdown and require a manual
reset.The thermostats are factory set to
open if the supply air temperature
reaches 240°F, or the return air
temperature reaches 135°F. Once tripped,
the thermostat requires a manual reset.
Reset by pressing the sensor’s reset
button when the air temperature
decreases approximately 25°F below the
cutout point.
Supply Air Temperature Sensor
The supply air temperature sensor is an
analog input device. It monitors the
supply air temperature for supply air
temperature control, supply air
temperature reset, supply air
temperature low limiting, and supply air
tempering. It is mounted in the supply air
discharge section of the unit and
connected to the RTM.
Low Ambient Compressor Lockout (Air-
Cooled Units Only)
The low ambient compressor lockout
utilizes an analog input device. When the
system is configured for low ambient
compressor lockout, the compressors will
not operate if the temperature of the
outside air falls below the lockout
setpoint. When the temperature rises 5°F
above the lockout setpoint, the
compressors will operate. The setpoint
for units without the low ambient option is
50°F. For units with the low ambient
option, the setpoint is 0°F.The setpoints
are adjustable at the human interface
panel.
Filter Switch
The filter switch is a binary input device
that measures the pressure differential
across the unit filters. It is mounted in the
filter section and connected to the RTM. A
diagnostic SERVICE signal displays at the
remote panel if the pressure differential
across the filters is at least 0.5” w.c.The
contacts automatically open when the
pressure differential across the filters
decrease to 0.4” w.c.The switch
Supply Airflow Proving Switches
This is binary input device used on units
to signal the RTM when the supply fan is
operating. It is mounted in the supply fan
section and is connected to the RTM.
During a request for fan operation and if
the differential switch opens for 40
consecutive seconds, compressor
operation turns off, heat operation turns
off, the request for supply fan operation is
turns off and locks out, IGV option closes,
economizer damper option closes, and a
manual reset diagnostic initiates.
differential is field adjustable between
0.17” to 5.0” w.c. 0.05 “.
ReturnAirTemperature Sensor
The return air temperature sensor is an
analog input device used with a return
humidity sensor on units with the
High Duct Static Switch Option
The high duct static switch is field-
mounted in the ductwork or plenums
with smoke dampers. It will cause a
manual reset diagnostic if the duct static
exceeds the pre-set static limit.The static
limit is adjustable at the HI.
Low EnteringAir Protection Device
(LEATPD)
The low entering air protection device
(LEATPD) is a binary input on units with
hydronic heat or a waterside economizer.
It is optional on water-cooled units.
comparative enthalpy option.The sensor
monitors the return air temperature and
compares it to the outdoor temperature
to establish which temperature is best
SCXG-SVX01B-EN
83
Download from Www.Somanuals.com. All Manuals Search And Download.
sequence of
operation
Operation
Control Sequences of
Operation
heating setpoint and higher cooling
setpoint). Setpoints can be programmed
at the HI,Tracer Summit, or the night
setback zone sensor.
Occupied/Unoccupied Switching
There are four ways to switch occupied/
unoccupied:
The unit enters the unoccupied mode
when the RTM receives a closed signal
on the unoccupied input for more than
five seconds.
(1) Night setback zone sensor
(2) Field-supplied contact closure
(hardwired binary input to RTM)
(3)Tracer Summit
For units with supply air temperature
control entering unoccupied mode, the
following sequence will occur:
• Heating/cooling functions cease and the
economizer option closes fully.The
supply fan shuts down for proper cool-
down time of the heat exchanger.
However, the supply fan may remain
on for a short period of time.
• After the supply fan shuts down, the
occupied/unoccupied relay energizes
and the IGV option fully opens. Also, the
VAV box stroke time begins.TheVAV
box stroke time is field adjustable to
allow time forVAV boxes to go to the
full open airflow position.
(4) Factory-mounted time clock
Field Supplied Occupied/Unoccupied
Input on the RTM
This input accepts a field supplied switch
or contacts closure, such as a time clock,
with a rating of 12 mA at 24 VDC
minimum.
Tracer Summit System
TheTracer Summit system can control
the occupied/unoccupied status of the
self-contained unit.
Factory MountedTime Clock
A time clock can control the
occupied/unoccupied status of the
self-contained unit.
• After the maxVAV box stroke time
expires and the IGV’s are fully open, the
supply fan, economizer (if enabled),
compressors, and heat are enabled to
satisfy the unoccupied zone
Unoccupied Sequence of
Operation
The unoccupied mode helps conserve
energy during times when a building is
usually unoccupied. When in unoccupied
mode, the unit will control to the
temperature setpoints.
Note: Unoccupied economizer operation
can be enabled or disabled at the HI or
using Tracer Summit.
unoccupied setpoints (usually a lower
Figure O-SO-1.Typical cycling morning warmup cycle
84
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
sequence of
operation
Operation
For units without volume control entering
unoccupied mode, the following se-
quence will occur:
is reached. Next a 60 minute timer
begins. If the building load reaches the
MWU ventilation setpoint, or the 60
minutes expire, whichever is first, the
airside economizer will control to the
minimum position. MWU will end when
the zone temperature rises above the
MWU terminate setpoint.
• The occupied/unoccupied relay ener-
gizes and the economizer option fully
closes.
• The fan mode is set to auto and the unit
will control to the unoccupied zone
temperature setpoints.
Timed Override Activation - ICS™
This function is operational whenever the
unit’s RTM module is used as the zone
temperature sensor source, which can be
set at the HI panel. When this function is
initiated by the push of the override
button on the zone sensor, the unit will
switch to the occupied mode. Unit
operation (occupied mode) during timed
override is terminated by a signal from
Tracer.
With MWU enabled at the HI, if the zone
temperature is below the MWU setpoint,
the unit enters the MWU mode.
Morning Warmup
This feature can be enabled at the HI, and
can be used with factory or field-installed
heat. If MWU is not required disable the
function in the setup menu at the HI.
MWU transitions the zone from
unoccupied to occupied. It will heat until
the MWU setpoint is met. The unit is then
released to occupied mode. Supply duct
static pressure is maintained during this
sequence. MWU can be set (at the HI) to
function as either full or cycling capacity.
Timed OverrideActivation - Non-ICS
This function is active whenever the unit’s
RTM module board is selected as the
zone temperature source, which can be
set at the human interface panel. When
this function is initiated by the push of the
override button on the zone sensor, the
unit will switch to the occupied mode.
Automatic cancellation of the timed
override mode occurs after three hours
of operation.
Full Capacity Morning Warmup (MWU)
Full capacity morning warmup uses full
heating capacity to heat the zone as
quickly as possible. Full heating capacity
is provided until the morning warmup
setpoint is met. At this point, the unit is
released to daytime mode.
VAV Drive Max Output
This is a single-pole, double-throw relay
rated at a maximum voltage of 24 vac,
two amps max. The relay contacts of this
relay switch when the unit goes from the
occupied mode to the unoccupied mode
by means of the unoccupied binary input,
night setback zone sensor, orTracer
Summit. The contacts will stay switched
during the unoccupied and morning
warmup mode. They will return to the
position shown on the unit wiring
diagram when the unit returns to the
occupied mode. The intent of this binary
output is to signal theVAV boxes or other
terminal devices to go to a full open
airflow position.
Cycling Capacity Morning Warmup
(MWU)
Cycling capacity morning warmup
provides a more gradual heating to
overcome “building sink” as the zone is
heated. Normal zone temperature control
with varying capacity is used to raise the
zone temperature to the MWU zone
temperature setpoint. This method of
warmup is used to overcome the
“building sink” effect.
Reference Figure O-SO-1 on page 73 for
a pictorial explanation of the cycling
MWU sequence. Cycling capacity MWU
will heat until MWU temperature setpoint
SCXG-SVX01B-EN
85
Download from Www.Somanuals.com. All Manuals Search And Download.
sequence of
operation
Operation
Occupied Sequence
Cooling
with the highest priority attempts cooling
first. Once it is operating at its maximum,
and if additional cooling is necessary, the
other economizer enables before
Upon entering occupied mode, the RTM
receives an input from either the HI, RHI,
Tracer Summit, or the GBAS to start the
supply fan. The RTM supply fan contacts
close and energize the supply fan
All setpoints can be adjusted using the HI
panel. Also, cooling/heating setpoints can
be adjusted in the zone, if using one of the
zone sensor options (BAYSENS020,
BAYSENS021, BAYSENS108,
mechanical cooling begins.
Cooling/Waterside Economizer
Waterside economizing enables when
the unit’s entering water temperature is
below the unit’s entering mixed air
temperature by 4°F plus the user
adjustable economizer approach
temperature. The approach temperature
default is 4°F.
contactor. OnVAV units with IGV, the fan
delays until the IGV fully close. When the
supply fan starts, the fan proving switch
closes, signaling the RTM that airflow is
established. Depending on unit options,
either the IGV will begin to drive open, the
VFD will ramp the fan, and/or the airside
economizer dampers will open to the
user-defined minimum position.
BAYSENS110, BAYSENS019, or
BAYSENS074). For a complete list of unit
setpoint default values and ranges, see
the IntelliPakSelf-Contained
Programming Guide, PKG-SVP01B-EN.
Occupied ZoneTemperature - Cooling
The unit transitions from unoccupied to
occupied when the occupied/unoccupied
input on the RTM is open for more than
five seconds after having been closed.
This input can be received fromTracer
Summit, the remote NSB zone sensor,
the timed override function, or a field
supplied contact. Dependent on unit
options and the HI programming, the
following sequence will occur:
• The unit will begin MWU and then
switch to the occupied mode after the
MWU setpoint is met.
• Purge will be enabled byTracer Summit.
ThenTracer Summit will enable the
occupied mode.
Waterside economizing disables when
the unit’s entering water temperature is
not below the unit’s entering mixed air
temperature by at least the water
economizer approach temperature
(default value of 4°F). The economizer
acts as the first stage of cooling. If the
economizer is unable to maintain the
zone (CV units) or supply air (VAV units)
temperature setpoint, the compressor
module will bring on compressors as
required to meet the setpoint.
When a cooling request is sent to the
RTM from the zone sensor, the RTM
evaluates the system operating condi-
tions using the supply air and outdoor
temperature input before sending the
request to the MCM for mechanical
cooling. If outdoor conditions (tempera-
ture and humidity) are suitable or the
EWT is within specified setpoints, the
RTM will attempt to use “free cooling”
without using any compressors. The RTM
will use either the airside or waterside
economizer option. When outdoor air
conditions are not suitable, only mechani-
cal cooling will function and outside air
dampers will remain at their minimum
position. If the unit does not have an
economizer, mechanical cooling will
operate to satisfy cooling requirements.
Cooling/Airside Economizer
On units with an airside economizer, a call
for cooling will modulate the fresh air
dampers open. The rate of economizer
modulation is based on deviation of the
zone temperature from setpoint; i.e., the
further away from setpoint, the faster the
fresh air damper will open. The first stage
of cooling will start after the economizer
reaches full open.
• The unit will switch from unoccupied to
occupied control immediately.
Upon entering occupied mode,the IGV
option will close while the supply fan
remains on. The occupied/unoccupied
relay will de-energize.
Units With Economizer
If the entering condenser water
temperature (units with a WSE) or the
outside air enthalpy (units with an ASE) is
appropriate to use “free cooling,” the
economizer will attempt to satisfy the
cooling zone temperature setpoint.
Zone Temperature Control
(Unit Model Number Digit 9 = 4 or 5)
A zone sensor located directly in the
space sends input to the RTM while the
CV unit is in occupied cooling mode.
When the unit is in occupied cooling, the
RTM controls the zone temperature
within the cooling setpoint deadband by
modulating the economizer option and/or
staging mechanical cooling on and off as
required.
Note: The airside economizer will only
function freely if ambient conditions are
below the enthalpy control settings or
below the return air enthalpy if unit has
comparative enthalpy installed. If outside
air is not suitable for “economizing,” the
fresh air dampers drive to the minimum
open position. A field adjustable, factory
default setting at the HI panel or Tracer
Summit can provide the input to establish
the minimum damper position.
Note: When using an ASE with economizer
enabled, O/A temperature enable can be
used instead of comparative enthalpy if the
O/A temperature falls below the economizer
setpoint.
Supply AirTemperature Control
(Unit Model Number Digit 9 = 1, 2, 3, or 6)
When theVAV unit is in occupied cooling,
the RTM controls the supply air
Then compressors will stage on as
necessary to maintain supply air tem-
perature setpoint, which is user-defined
at the HI. Minimum on/off timing of
compressors prevents rapid cycling.
When outdoor air conditions are above
the setpoint or comparative enthalpy
control setting, only mechanical cooling
will function and outside air dampers will
remain at their minimum position.
temperature to the specified supply air
cooling setpoint by modulating the
economizer option and/or staging
mechanical cooling on and off as
required. The changeover relay contacts
(field supplied) must be open on units
with hydronic heat for cooling to operate.
When both airside and waterside
economizers are on a single unit, priority
must be set at the HI. The economizer
86
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
sequence of
operation
Operation
Mechanical Cooling
Hydronic Heat: HotWater or Steam
On units with hot water or steam heating,
the zone temperature can be controlled
to a heating setpoint during the occupied
mode. The zone temperature heating
setpoint and deadband are user defined
at the HI panel or zone sensor.VAV
occupied heating initiates by closing a
field-supplied switch or relay contacts
connected to the changeover input on the
RTM. Supply air static pressure is
maintained.
SupplyAirTempering (HotWater and
SteamVAV Units Only)
When supply air temperature falls below
the supply air temperature deadband low
end, the heating valve modulates open to
maintain the minimum supply air
temperature setpoint.
If the zone temperature cannot be
maintained within the setpoint deadband
using the economizer option or if there is
no economizer, the RTM sends a cooling
request to the MCM. The compressor
module checks the compressor
protection circuit before closing stage
one. After the first functional stage starts,
the compressor module monitors the
saturated refrigerant temperature and
closes the condenser fan output contact
when the saturated refrigerant
Daytime Warmup (Units with Supply Air
Temperature Control Only)
During occupied mode, if the zone
temperature falls to a preset, user-
defined zone low limit temperature
setpoint, the unit is put into daytime
warmup. The system changes over to CV
heating, theVAV boxes drive full open.
However, unit airflow modulation control
operates to maintain duct static setpoint,
and full heating capacity is provided until
the daytime warmup setpoint is reached.
The unit is then returned to normal
occupied mode.
SupplyAir Setpoint Reset (VAV Units
Only)
temperature rises above the lower limit
setpoint.
Supply air reset can be used to adjust the
supply air temperature setpoint on the
basis of a zone temperature or outdoor
air temperature. Supply air reset
adjustment is available at the HI panel for
supply air heating and supply air cooling
control.
Air-Cooled Units Only
The compressor module closes the
condenser fan output contact when the
saturated refrigerant temperature rises
above the lower limit setpoint.
Water-Cooled Units Only
The WSM modulates the condenser coil
water valves to maintain condenser
temperature, if applicable. Otherwise, it
will check the entering condenser water
temperature to ensure it is greater than
54°F or if not, it will lock out cooling.
Reset based on outdoor air temperature
Outdoor air cooling reset is sometimes
used in applications where the outdoor
temperature has a large effect on
building load. When the outside air
temperature is low and the building
cooling load is low, the supply air setpoint
can be raised, thereby preventing
Supply AirTempering
Supply air tempering is available on units
without volume control and with hot
water, steam, or electric heat or units with
supply air temperature control with
steam or electric heat. When the unit is in
heat mode but not actively heating, if the
supply air temperature drops to 10°F
(5.5°C) below the occupied zone heating
temperature setpoint, electric heat will
stage on or the hydronic valve will
modulate to maintain a minimum supply
air temperature. The unit transitions out
of heat mode if the supply air
Auto Changeover (Units with Heat Only)
When the system mode is in auto, the
mode will change to cooling or heating as
necessary to satisfy the zone cooling
andheating setpoints. The zone cooling
and heating setpoints can be as close as
2°F (1.1°C).
subcooling of critical zones. This reset can
lower usage of mechanical cooling, thus
savings in compressor kW, but an
increase in supply fan kW may occur.
Outdoor air heating reset is the inverse of
cooling, with the same principles applied.
Occupied ZoneTemperature - Heating
Relies on input from a sensor directly in
the space, while a system is in occupied
heating mode or an unoccupied period, to
stage electric heat on and off or modulate
the hydronic heating valve as required to
maintain the zone temperature within the
heating setpoint deadband. The supply
fan will operate when there is a request
for heat.
temperature rises to 10°F (5.5°C) above
the occupied zone heating temperature
setpoint.
For both outdoor air cooling reset and
heating reset, there are three user
defined parameters that are adjustable
through the human interface panel.
• Beginning reset temperature
• Ending reset temperature
• Maximum amount of temperature reset
Changeover
This mode only functions on units with
supply air temperature control with
hydronic heat. When the changeover
binary input is closed the unit will control
to a discharge air heating setpoint. This
setpoint is entered from the HI, and can
be a higher temperature than the supply
air cooling setpoint. This function
maintains duct static pressure.
Reset based on zone temperature
Zone reset is applied to the zone(s) in a
building that tends to overcool or
overheat. The supply air temperature
setpoint is adjusted based on the
temperature of the critical zone(s). This
can have the effect of improving comfort
and/or lowering energy usage. The user-
defined parameters are the same as for
outdoor air reset.
Electric Heat
On units with electric heat, the zone
temperature can be controlled to a
heating setpoint during the occupied
mode by cycling a single stage electric
heater. An interface is provided for field
supplied single stage electric heat. The
zone temperature heating setpoint and
deadband are user defined at the HI
panel.
SCXG-SVX01B-EN
87
Download from Www.Somanuals.com. All Manuals Search And Download.
sequence of
operation
Operation
Compressors
compressors are manifolded together. If
there are four compressors, the second
two are manifolded.
turned on as requested by the unit
temperature control algorithm.
Units use two sizes of hermetic scroll
compressors, 10 and 15 hp, and can use
from two to six compressors. When
viewing the front of the unit, compressors
are identified A through B from left to
right. The second compressor from the
left, or B compressor, is always the first to
come on, unless locked out for a
malfunction or shut off on frost protection.
Refer toTable O-SO-1 for compressor
cycling stages andTable O-SO-3 on page
78 for percent cooling capacity by stage.
Compressor Lead/Lag Operation
Compressor lead/lag is a user-selectable
feature at the HI panel and is available on
all units. After each request for
compressor operation, the lead
refrigeration circuit or compressor
switches, thereby causing a more
equitable or balanced run time among
compressors.
Compressor Cycling
Compressors cycle to maintain the
operating state required by the
temperature controls. In the event of a
compressor failure, the next available
compressor turns on. Refer toTable O-
SO-1 for compressor cycling by unit
model and tons.
During normal conditions, compressors
will not shut off until they have been on
for at least three minutes and will not turn
on until they have been off for at least
three minutes. Normal operating condi-
tions are established on an individual
compressor basis. When a compressor
starts, its timer also starts. The compres-
sor evaporator circuit frost protection can
override the “minimum” timer and
reduce the five minute minimum re-
quired time period.
When lead/lag is enabled, each time the
system cycles, it will alternate between
the standard compressor staging and the
lead/lag staging. UsingTable O-SO-1, a
SXWG 30-ton unit will first stage com-
pressor B then A, then AB for first cycle
and A, then AB for the second cycle.
Appropriate condenser valves (water-
cooled and condenser fans (air-cooled)
will stage with appropriate compressors
to maintain saturated condensing
The control system logic permits com-
pressor operation only after the supply
fan is on. If the supply fan shuts down,
compressors will not operate. Units
without head pressure control (units with
intermediate piping packages) will lock
out mechanical cooling when the entering
condenser water temperature falls below
54°F. Mechanical cooling will resume
when the entering condenser water
temperature exceeds 58°F.
temperature. Enabling lead/lag may drop
a cooling stage when compared to
standard staging. SeeTable O-SO-1 for
compressor staging.
When the unit is powered up, or manually
reset there will be a three to eight minute
delay before the first compressor may be
When there are more than two compres-
sors in an air cooled unit, the first two
Table O-SO-1. Compressor Stages.
Unit
Size
Refrigerant
Compressor HP
by Stage
Standard
Lead/Lag
SCM
Circuit Type
Compressor
Compressor or
Model # Digit 5
A
B
Staging
Staging
A/AB
MCM
SXWG 20, 25
SXRG 20
SXWG 30
SXRG 25
SXWG 35
SXRG 32
Independent
Independent
Independent
10
10
B/AB
MCM
MCM
MCM
15
15
10
15
B/A/AB
B/AB
A/AB
A/AB
88
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
sequence of
operation
Operation
Compressor Safety Devices
A minimum time delay of five minutes
follows each change in cooling level. This
time delay promotes stability by allowing
the system to respond to the change
before any further control action occurs.
As the supply air temperature ap-
proaches setpoint, the time duration
between changing levels of cooling
capacity increases.
Low Ambient Compressor Lockout
This function will lock out the compressor
if the outdoor air temperature sensor
reads an outdoor temperature below the
low ambient compressor lockout
temperature setpoint. This setpoint is
adjustable at the human interface panel.
Compressors will lock out when outdoor
air temperature falls below that selected
temperature and will start again when
the temperature rises 5°F above the
setpoint.
The compressors have motor
temperature cutout switches in the motor
windings. These switches are provided
to take the compressors off line during
high motor winding temperature
conditions.
If a compressor low pressure cutout
opens during compressor start-up, the
UCM will not shut the compressor off
during the first two to three minutes after
start-up. This prevents possible nuisance
trips during low ambient start conditions.
SeeTable O-SO-2.
See Figure O-SO-2 for the typical unit
operating curve. Figure O-SO-3 shows
typical unit performance when supply air
temperature swings exceed the control
band limits.
Evaporator Coil Frost Protection
FROSTAT™
Each compressor’s discharge line
Adjust the supply air temperature control
band according to the desired unit
performance. Increasing the control band
reduces the equipment cycle rate and
increases the maximum potential supply
air temperature deviation from setpoint.
Conversely, decreasing the control band
reduces the maximum potential tem-
perature deviation, but increases the
compressor cycle rate.
The FROSTAT™ system eliminates the
need for hot gas bypass. It utilizes an
evaporator temperature sensor mounted
on the suction line near the TXV bulb of
each circuit to protect the evaporator
from freezing.
contains a high pressure cutout. Under
abnormal operating conditions, the cutout
will open to stop compressor operation.
Table O-SO-2. Pressure cutouts
If the evaporator temperature ap-
proaches the specified setpoint (adjust-
able between 25 and 35°F at the HI) the
compressor(s) will cycle off. The supply
fan remains on to help de-ice the coil. The
compressors will restart when the
evaporator temperature has risen 10°F
above the specified cutout temperature
and when the compressor(s) have been
off a minimum of three minutes. This
prevents rapid cycling of the compres-
sors.
Unit
High Pressure
Cutout
Low Pressure
Cutout
Model
SXWF
SXRF
360/270
405/350
20/35
12/27
Follow these recommendations concern-
ing the supply air temperature control
band settings based on expected unit
sizing:
Step Control
Steps of mechanical cooling are control
based on supply air or zone temperature.
SeeTable O-SO-1 for compressor
staging.
2 Cooling stage unit: 9°F
3 Cooling stage unit: 7°F
4 Cooling stage unit: 6°F
Capacity is based on an integrating
control concept. The unit capacity
matches the existing load and maintains
an average supply air temperature within
the supply air setpoint temperature
control band region.
The supply air temperature control band
is centered around supply air tempera-
ture setpoint and is adjustable from 2 to
12°F. In a steady state, the unit will either
maintain a constant level of cooling
capacity with the supply air temperature
within the control band, or the highest
active cooling level will cycle to provide
an average supply air temperature equal
to the setpoint.
If the supply air temperature swings
outside the limits of the control band, the
mechanical cooling capacity will increase
or decrease by one level accordingly.The
change occurs by integrating the tem-
perature offset from the control band
limit.
SCXG-SVX01B-EN
89
Download from Www.Somanuals.com. All Manuals Search And Download.
sequence of
operation
Operation
Service Valve Option
If ordered, service valves are factory
installed on each circuit before and after
the compressor to allow compressor
isolation for servicing.
Figure O-SO-2.Typical pulldown curve for unit operating properly within control band
Figure O-SO-3.Typical pulldown curve for unit operating improperly outside control band
90
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
general
information
Maintenance
Table M-GI-1. SCWG/SIWG/SCRG/SIRG General Maintenance Data
Water-Cooled Units
25
Air-Cooled Units
Unit Size
20
30
35
20
25
32
Compressor Data
Quantity
NominalTon/Comp
Circuits
2
10
2
2
10
2
1/1
10/15
2
2
15
2
2
10
2
1/1
10/15
2
2
15
2
EvaporatorCoilData
Rows
Sq. Ft.
2
22.5
144
4
25.0
144
4
25.0
144
4
25.0
144
3
25.0
144
4
25.0
144
4
25.0
144
FPF
CondenserData
MiniumGPMw/oEcon
MinimumGPMw/Econ
MaximumGPM
EvaporatorFanData
Quantity
36
41
80
36
41
80
46
60
54
65
–
–
–
–
–
–
–
–
–
102
119
2
125/8”x8"
5
2
2
2
125/8 x11"
5
2
125/8”x8"
5
2
125/8”x9"
5
2
125/ ”x11"
85
Size (Dia. x width - inches)
MinimumHP
125/8”x9"
5
125/ ”x11"
85
MaximumHP
MinimumDesignCFM
MaximumDesignCFM
R-22 Refrigerant Data
EER
20
6350
8500
25
7250
10,625
25
7250
12,750
25
7250
14,875
20
7250
8500
25
7250
10,625
25
7250
13600
12.6
13.2
13.9
14.1
13.4
12.9
12.5
12.2
10.3
11.4
10.7
11.4
10.1
10.4
IPLV
Refrigerant Charge - lbs.
Circuit A
Circuit B
25
25
25
25
27
25
27
27
–
–
–
–
–
–
Capacity Steps - %
407C Refrigerant Data
EER
100/53/0
100/53/0
100/65/47/0
100/53/0
100/52/0
100/66/47/0
100/52/0
11.6
12.3
13.2
13.5
12.3
12.2
11.3
11.5
–
–
–
–
–
–
IPLV
Refrigerant Charge - lbs
Circuit A
Circuit B
23.5
23.5
23.5
23.5
26.5
23.5
26.5
26.5
Capacity Steps - %
Filter Data
Quantity
Size (inches)
Quantity
Size (inches)
CCRC/CIRC Condenser Match
100/53/0
100/53/0
100/65/42/6
100/53/0
4
4
4
4
4
16x25x2
4
20x25x2
20
4
16x25x2
4
20x25x2
29
4
16x25x2
4
20x25x2
32
(16x25x2)
(16x25x2)
(16x25x2)
(16x25x2)
4
20x25x2
–
4
20x25x2
–
4
20x25x2
–
4
20x25x2
–
Notes:
1. Compressors areTrane 3D® scroll.
2. EER and IPLV are rated in accordance to theARI Standard 340/360-93 for large unitary equipment. Based on 80/67°F (26.7/19.4°C) to the evaporator coil, nominal airflow and 85-95°F (29.4-
35°C) condenser water.
3. All units operate with R-22. Units ships with full operating charge.
4. Maximum cfm limits are set to prevent moisture carryover on the evaporator coil.
5. Minimum cfm limits are set to ensure stable thermal expansion valve operation at low load conditions.
6. Filter sizes are for units without hot water or steam heating coils
Table M-GI-2. SCWG/SIWG/SCRG/SIRG Self-Contained Heating Coil Maintenance Data
Filter Data for Heating Coil
Quantity
4
Size (inches)
Size (mm)
Quantity
Size (inches)
Size (mm)
20x18x2
(508x457x51)
8
20x20x2
(508x508x51)
Coil Data
Type
Rows
No. - Size (in)
2 - 24 x 58
No. - Size (mm)
2 - 609.6x1473.2
2 - 609.6x1473.2
fpf
42
80
Steam Coil
Hot Water Coil
NS
1
1
WC
2 - 24 x 58
Notes: 1. Hot water and steam heating coils have Prima-Flo® fins and do not have turbulators. 2. For coil capacities, useTOPSS™ (Trane Official
Product Selection Program). 3. Full capacity coils consist of two coils stacked and piped in parallel.
SCXG-SVX01B-EN
91
Download from Www.Somanuals.com. All Manuals Search And Download.
maintenance
procedures
Maintenance
Maintenance Procedures
of the unit.To replace throwaway filters,
remove the dirty elements and install
new filters with the filter’s directional
arrows pointing toward the fan.Verify
that no air bypasses the filters. See
Figures O-M-1 and O-M-2 for proper filter
placement.
Air Filters
Filter access doors are on the unit’s left
side. Filter access for the 2” filter rack on
optional steam and hot water coils and
airside economizers is also on the left side
is this correct?
without steam or hot water coil
with steam or hot water coil
16 x 20
20 x 20
16 x 20
20 x 20
16 x 20
20 x 20
16 x 20
20 x 20
18 x 20
20 x 20
18 x 20
18 x 20
20 x 20
18 x 20
18 x 20
20 x 20
18 x 20
18 x 20
20 x 20
18 x 20
18 x 20
18 x 20
18 x 20
18 x 20
Note: All filters are 2". These views are from the back of the unit (L-R).
Note: All filters are 2". These views are from the back of the unit (L-R).
Figure M-MP-1. Unit Filter Sizes and Placement for SXWG 20-38 tons or SXRG 20-40 tons
ƽWARNING
Hazardous Voltage w/Capaci-
tors!
Disconnect all electric power, including
remote disconnects before servicing.
Follow proper lockout/tagout proce-
dures to ensure the power cannot be
inadvertently energized. For variable
frequency drives or other energy
storing components provided byTrane
or others, refer to the appropriate
manufacturer’s literature for allowable
waiting periods for discharge of capaci-
tors.Verify with an appropriate voltme-
ter that all capacitors have discharged.
Failure to disconnect power and
discharge capacitors before servicing
could result in death or serious injury.
Note: For additional information
regarding the safe discharge of capaci-
tors, see PROD-SVB06A-EN or PROD-
SVB06A-FR.
92
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
maintenance
procedures
Maintenance
Inspecting and Cleaning the
Drain Pan
Check the condensate drain pan and
drain line to ensure that the condensate
drains properly at least every six months
or as dictated by operating experience.
5.Thoroughly clean the contaminated
area(s) with a mild bleach and water
solution or an EPA-approved sanitizer
specifically designed for HVAC use.
Carefully follow the sanitizer
manufacturer’s instructions regarding
product use.
6. Immediately rinse the drain pan
thoroughly with fresh water to prevent
potential corrosion from the cleaning
solution.
7. Allow the unit to dry thoroughly before
putting the system back into service.
8. Properly dispose of all contaminated
materials and cleaning solution.
If evidence of standing water or conden-
sate overflow exists, take steps to identify
and remedy the cause immediately.
Refer to the trouble shooting section of
this manual for possible causes and
solutions.
ƽWARNING
Hazardous Voltage w/Capaci-
tors!
Inspecting and Cleaning the
Fan
Disconnect all electric power, including
remote disconnects before servicing.
Follow proper lockout/tagout proce-
dures to ensure the power cannot be
inadvertently energized. For variable
frequency drives or other energy storing
components provided byTrane or others,
refer to the appropriate manufacturer’s
literature for allowable waiting periods
for discharge of capacitors.Verify with an
appropriate voltmeter that all capacitors
have discharged. Failure to disconnect
power and discharge capacitors before
servicing could result in death or serious
injury.
Inspect the fan section every six months
or more frequently if operating
experience dictates. Clean accumulated
dirt and organic matter on the fan interior
surfaces following the procedure below:
1. Disconnect all electrical power to the
unit.
2. Wear the appropriate personal
protective equipment (PPE).
3. Use a portable vacuum with HEPA
filtration to remove the loose dirt and
organic matter.The filter should be
99.97% efficient at 0.3 micron particle
size.
4. Thoroughly clean the fan and
associated components with an
industrial cleaning solution. Carefully
follow the cleaning solution
manufacturer’s instructions regarding
personal protection and ventilation
when using their product.
5. Rinse the affected surfaces thoroughly
with fresh water and a fresh sponge to
prevent potential corrosion of metal
surfaces.
6. Allow the unit to dry completely before
putting it back into service.
Note: For additional information regard-
ing the safe discharge of capacitors, see
PROD-SVB06A-EN or PROD-SVB06A-FR.
Clean drain pans using the following
procedure:
1. Disconnect all electrical power to the
unit.
2. Don the appropriate personal
protective equipment (PPE).
3. Remove all standing water.
4. Use a scraper or other tools to remove
and solid matter. Remove solid matter
with a vacuum device that utilizes high
efficiency particulate arrestance (HEPA)
filters with a minimum efficiency of
99.97% at 0.3 micron particle size.
7. Properly dispose of all contaminated
materials and cleaning solution.
SCXG-SVX01B-EN
93
Download from Www.Somanuals.com. All Manuals Search And Download.
maintenance
procedures
Maintenance
Variable Frequency Drive (VFD)
The VFD access panel is hinged to allow
service access to the fan motor and belt
drive components that are located behind
it.To swing the panel open:
• Remove the unit center cover panel to
the left of the VFD panel.
• Remove and discard the sheet metal
shipping screws along the top and
bottom edges of the VFD panel.
• Disconnect the communications cable
from the keypad on the VFD door panel.
•Turn the two slotted-head fasteners on
the right edge of the VFD panel fully
counterclockwise.
each sheave and pull it tight for a center
line. See Figure M-MP-6 for
literature for allowable waiting periods
for discharge of capacitors.Verify with an
appropriate voltmeter that all capacitors
have discharged. Failure to disconnect
power and discharge capacitors before
servicing could result in death or serious
injury.
recommended torques.
4. Once the sheaves are properly aligned,
tighten sheave set screws to proper
torque. SeeTables M-MP-1 and M-MP-2
for recommended torques.
5. Check belt tension. Refer to the
“Measuring BeltTension” section.
6. If required, adjust belt to the minimum
recommended tension. Refer to
“Adjusting BeltTension” section.
7. Retighten bearing set screws to the
proper torques after aligning the
sheaves. SeeTables M-MP-1 and M-
MP-2 for proper torques.
8. Check the fan bearing locking collars
for tightness on the shaft.To tighten the
locking collar, loosen the set screw and
slide the collar into its proper position
over the extended end of the inner
case.Tighten the set screw to the
torque value inTables M-MP-1 and M-
MP-2.
Note: For additional information regard-
ing the safe discharge of capacitors, see
PROD-SVB06A-EN or PROD-SVB06A-FR.
1. Rotate the fan wheel to ensure it turns
freely in the proper direction and is not
rubbing on the fan housing, inlet, or inlet
guide vanes. If necessary, center the
fan wheel again.
2. Check the position of both shafts. Fan
and motor shafts should operate
parallel to each other for maximum belt
and bearing life. Shim as necessary
under the motor or fan bearings to
obtain proper alignment.
• Pull on the handle to swing the panel
180°.
To close and reattach the panel, reverse
the procedures listed above.
Note: To secure the panel in the open
position during service procedures, attach
the chain mounted to the cabinet frame
behind the unit center cover panel to the
chain retainer notch on the edge of the VFD
panel.
3. Check the fan motor sheave alignment
with straight edge or a tightly pulled
string. For sheaves of different widths,
place a string in the center groove of
9. During air balancing, verify the sheave
alignment, belt tension, and that the
shaft is parallel.
Note: Verify that all wires are in their proper
position and not rubbing before replacing
the panel.
Note: Panel weight rating = 225 lbs. total,
including factory-installed components.
Supply Fan
Fan Drive
Perform the following procedures
according to the “Periodic Maintenance
Check List”.
ƽWARNING
Hazardous Voltage w/Capaci-
tors!
Disconnect all electric power, including
remote disconnects before servicing.
Follow proper lockout/tagout proce-
dures to ensure the power cannot be
inadvertently energized. For variable
frequency drives or other energy storing
components provided byTrane or others,
refer to the appropriate manufacturer’s
Figure M-MP-4. Fan shaft and motor sheave alignment
94
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
maintenance
procedures
Maintenance
Fan Bearings
Table M-MP-1. Baldor Fan Bearing Lubrication Schedule
The opposite drive end bearing is a
special bearing with close tolerance fit of
balls and races. Replace this bearing with
the same part number as the original
bearing. Follow the fan bearing
lubrication schedules inTables M-MP-1
and M-MP-2. UseTable M-MP-3 to
reference compatible fan bearing grease
for specific bearings.
Baldor
Rated Speed, rpm
Nema/ (IEC) Frame Size
up to 210 incl. (132)
over 210 to 280 incl. (180)
over 360 to 5800 incl. (300)
3600
1800
1200
900
5500 hrs
3600 hrs
2200 hrs
12,000 hrs
9500 hrs
3500 hrs
18,000 hrs
15,000 hrs
7400 hrs
22,000 hrs
18,000 hrs
10,500 hrs
Table M-MP-2.AO Smith Bearing Lubrication Schedule
Speed
Service
Frame
Standard Service
Severe Service
Extreme
Over 1800 rpm
1800 rpm
All
6 mths
3 yrs
3 mths
1 yr
3 mths
6 mths
5 1/2 mths
4 1/2 mths
4 mths
140-180
210-280
320-360
400-440
2 1/2 yrs
2 yrs
1 1/2 yrs
10 1/2 mths
9 mths
8 mths
Note: Service standard - 8 hrs/day, normal to lgith loading, 100°F ambient temp. max.
Severe service - 24 hrs/day, shock loading, vibration, dirt or dust, 100 to 150°F ambient temp.
Extreme service - heavy shock or vibration, dirt or dust, 100 to 150°F ambient temp.
Table M-MP-3. Compatible Fan Bearing Grease
Motor Vendor
Recommended Oil
AOSmith
ExxonPolyrexEM
Chevron SRI 2
Dolium R Grease
Chevron Black Perl EP1
ExxonPolyrexEM
Texaco Polystar
Baldor
RykonPremium#2
PennzoilPen2Lube
ChevronSRI
SCXG-SVX01B-EN
95
Download from Www.Somanuals.com. All Manuals Search And Download.
maintenance
procedures
Maintenance
Fan BeltTension
Table M-MP-4. Fan shaft bearing torques
setscrew
size
1/4"-20
hex-size
recommended torque
Note: Check fan belt tension at least twice
during the first days of new belt operation
since there is a rapid decrease in tension
until belts are run-in.
across flats
In-lb
180
402
ft-lb
15
1/8"
5-32"
5-16"-18
33.5
Table M-MP-5. Fan hub and sheave torques
Proper belt tension is necessary to
endure maximum bearing and drive
component life and is based on fan brake
horsepower requirements. If frayed or
worn, replace belts in matched sets.
unit
size
SCWF 20
SCWF 22
SCWF 25
SCRF 20
SCWF 29
SCWF 32
SCRF 25
SCRF 30
SCWF 35
SCWF 38
SCRF 30
SCRF 35
SCWF 42
SCWF 46
SCWF 52
SCWF 58
SCRF 40
SCRF 50
SCWF 65
SCWF 72
SCWF 80
SCRF 60
SCWF 90
SCWF C0
SCWF C1
fan
setscrew torque
dia.
size
(ft-lbs)
12
5
16.5"
/
/
/
"
"
"
16
16
16
5
5
18"
12
14
24
Measuring BeltTension
Measure fan belt tension with a
Browning, Gates, or equivalent belt
tension gauge. Determine deflection by
dividing the belt span distance (in inches)
by 64. See Figure M-MP-6. Follow the
procedure below to measure belt tension.
20"
25"
3/8"
1. Measure belt span between centers of
sheaves and set the large “O” ring of
the tensioning gauge at 1/64 inch for each
inch of belt span.
27"
3/8"
24
Figure M-MP-5. Belt tension gauge
2. Set the load “O” ring at zero.
3. Place the large end of the gauge at the
center of the belt span. Press down until
the large “O” ring is even with the top
of the belt line or the next belt as in
Figure M-MP-6. Place a straight edge
across the sheaves as a reference
point. See Figure M-MP-4.
deflection = belt span/64
4. Remove the gauge. Note that the load
“O” ring now indicates a number on the
plunger scale. This number represents
pounds of force required to deflect the
belt.
5. Check the reading from step 4 against
the values given inTable M-MP-4. If
necessary, readjust belt tension.
Figure M-MP-6. Fan belt adjustment
96
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
maintenance
procedures
Maintenance
Adjusting BeltTension
NOTICE
Do not over-tension belts. Exces-
sive belt tension will reduce fan
and motor bearing life, accelerate
belt wear, and possibly cause
shaft failure.
To adjust belt tension refer to Figure M-
MP-6 and perform the following
procedure:
1. Loosen bolts A, B, and E on both sides
of the sliding motor base. See Figure M-
MP-7.
2. Loosen nuts C and D (as required for
motor horsepower) to slide the motor
on its mounting plate in the proper
direction to tension or relieve tension on
the belt.
Figure O-M-5. Fan assembly.
3. Adjust nuts A-D and bolt E. Do not
stretch the belts over the sheaves.
4. Retighten all nuts and bolts.
5.Verify tension is adjusted properly.
Recommended belt tension range values
are on the unit fan scroll.To access the
fan scroll, face the right-hand side of the
unit and remove the top left panel. The
belt tension label is on the top right-hand
corner of the fan scroll. See Figures O-M-
8 and O-M-9.
The correct operation tension for aV-belt
drive is the lowest tension at which the
belt will not slip under the peak load
conditions. It may be necessary to
increase the tension of some drives to
reduce flopping or excessive startup
squealing.
Figure M-MP-7. Belt tensioning with fan adjustment points
Figure M-MP-8. Location of fan belt label on
fan scroll
SCXG-SVX01B-EN
97
Download from Www.Somanuals.com. All Manuals Search And Download.
maintenance
procedures
Maintenance
Refrigerant System
•To assist in reducing power generation
emissions, always attempt to improve
equipment performance with improved
maintenance and operations that will
help conserve energy resources.
ƽWARNING
Special Note on Refrigerant Emissions
Follow theTrane recommended
procedures on operation, maintenance,
and service to ensure refrigerant
conservation and emission reduction.
Also, pay specific attention to the
following:
• Whenever removing refrigerant from
air conditioning or refrigerating
equipment, recover for reuse, recycle,
reprocess (reclaim), or properly destroy
it.
• Always determine possible refrigerant
recycling or reclaiming requirements
before beginning recovery. Questions
about recovered refrigerants and
acceptable refrigerant quality
standards are addressed in ARI
Standard 700.
LeakTesting!
Do not exceed 200 psig when leak
testing system. Failure to follow these
instructions could result in an explosion
causing death or serious injury.
ƽWARNING
Confined Space Hazards!
Do not work in confined spaces where
sufficient quantities of refrigerant or
other hazardous, toxic, or flammable gas
may be leaking. Refrigerant or other
gases could displace available oxygen to
breathe, causing possible asphyxiation
or other serious health risks. Some
gases may be flammable and or explo-
sive. Evacuate the area immediately and
contact the proper rescue or response
authority. Failure to take appropriate
precautions or to react properly to a
potential hazard could result in death or
serious injury.
In the event of required system repair,
leak test the liquid line, evaporator coil,
and suction line at pressures dictated by
local codes, and using the following
guidelines.
1. Charge enough dry nitrogen into the
system to raise the pressure to 100
psig.
2. Use a halogen leak detector, halide
torch, or soap bubbles to check for leaks.
Check interconnecting piping joints, the
evaporator coil connections, and all
accessory connections.
3. If a leak is detected, release the test
pressure, break the connections and
reassemble it as a new joint, using
proper brazing techniques.
4. If no leak is detected, use nitrogen to
increase the test pressure to 150 psig
and repeat the leak test. Also, use soap
bubbles to check for leaks when
nitrogen is added.
5. Retest the system to make sure new
connections are solid.
6. If a leak is suspected after the system
has been fully charged with refrigerant,
use a halogen leak detector, halide
torch, or soap bubbles to check for leaks.
• Use approved containment vessels and
safety standards. Comply with all
applicable transportation standards
when shipping refrigerant containers.
•To minimize emissions while recovering
refrigerant, use recycling equipment.
Always attempt to use methods which
will pull the lowest possible system
vacuum while recovering and
condensing refrigerant into
ƽWARNING
Hazard of Explosion!
Use only dry nitrogen with a pressure
regulator for pressurizing unit. Do not
use acetylene, oxygen or compressed air
or mixtures containing them for pressure
testing. Do not use mixtures of a
hydrogen containing refrigerant and air
above atmospheric pressure for pres-
sure testing as they may become
flammable and could result in an explo-
sion. Refrigerant, when used as a trace
gas should only be mixed with dry
nitrogen for pressurizing units. Failure to
follow these recommendations could
result in death or serious injury or
containment.
• Be aware of any new leak test methods
which eliminate refrigerant as a trace
gas.
• When cleaning system components or
parts, do not use CFC11 (R11) or
CFC113 (R113). Refrigeration system
clean up methods using filters and
dryers are recommended. Do not use
solvents which have ozone depletion
factors. Properly dispose of used
materials.
•Take extra care to properly maintain all
service equipment directly supporting
refrigerant service work such as
gauges, hoses, vacuum pumps, and
recycling equipment.
• Stay aware of unit enhancements,
conversion refrigerants, compatible
parts, and vendor components and
manufacturer’s recommendations that
will reduce refrigerant emissions and
increase equipment operating
efficiencies. Follow specific
Refrigerant Evacuation
For field evacuation, use a rotary style
vacuum pump capable of pulling a
vacuum of 400 microns or less.
When connecting the vacuum pump to a
refrigeration system, it is important to
manifold the pump to both the high and
low side of the system. Follow the pump
manufacturer’s directions.
equipment or property-only damage.
manufacturer’s guidelines for
conversion of existing systems.
98
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
maintenance
procedures
Maintenance
refrigerant containers.
NOTICE
Motor Winding Damage!
•To minimize emissions while recovering
refrigerant, use recycling equipment.
Always attempt to use methods that
will pull the lowest possible system
vacuum while recovering and
ƽWARNING
LeakTesting!
Do not use a megohm meter or apply
voltage greater than 50 DVC to a
compressor motor winding while it is
under a deep vacuum.Voltage sparkover
may cause damage to the motor
windings.
Do not exceed 200 psig when leak
testing system. Failure to follow these
instructions could result in an explosion
causing death or serious injury.
condensing refrigerant into
containment.
• Be aware of any new leak test methods
that eliminate refrigerant as a trace gas.
• When cleaning system components or
parts, do not use CFC11 (R11) or CFC
113 (R113). Refrigeration system clean-
up methods using filters and dryers are
recommended. Do not use solvents
which have ozone depletion factors.
Properly dispose of used materials.
•Take extra care to properly maintain all
service equipment directly supporting
refrigerant service work such as
gauges, hoses, vacuum pumps, and
recycling equipment.
• Stay aware of unit enhancements,
conversion refrigerants, compatible
parts, and manufacturer’s
recommendations that will reduce
refrigerant emissions and increase
equipment operating efficiencies.
Follow specific manufacturer’s
In the event of required system repair,
leak test the liquid line, evaporator coil,
and suction line at pressures dictated by
local codes, using the following
guidelines.
1. Charge enough refrigerant and dry
weight. Use an accurate scale or
charging cylinder to determine the
exact weight of the refrigerant entering
the system. Failure to use either a scale
or a charging cylinder can lead to
undercharging or overcharging
resulting in unreliable operation.
Refrigerant Charging
• R22 units
After leak testing and evacuating the
system, charge liquid refrigerant into the
system through the liquid line valve. After
some refrigerant has entered each
circuit, charge gaseous refrigerant into
the suction line shrader valve with the
compressors running.
• R407c
After leak testing and evacuating the
system, charge liquid refrigerant into the
system through the liquid line valve.
NOTICE
Compressor Damage!
ƽWARNING
Hazardous Pressures!
Do not operate the compressors without
some refrigerant in each circuit. Failure
to do so may result in compressor
damage.
If a heat source is required to raise the
tank pressure during removal of refriger-
ant from cylinders, use only warm water
or heat blankets to raise the tank
temperature. Do not exceed a tempera-
ture of 150°F. Do not under any circum-
stances apply direct flame to any portion
of the cylinder. Failure to follow these
safety precautions could result in a
violent explosion, which could result in
death or serious injury.
guidelines for conversion of existing
systems.
•To assist in reducing power generation
emissions, always attempt to improve
equipment performance with improved
maintenance and operations that will
help conserve energy resources.
Special Note on Refrigerant Emissions
Follow theTrane recommended
procedures on operation, maintenance,
and service to endure refrigerant
conservation and emission reduction.
Also, pay specific attention to the
following:
Refrigerant LeakTesting
It is important to follow all warnings and
cautions in this section when leak testing
equipment.
•When removing refrigerant from air
conditioning or refrigerating equipment
recover for reuse, recycling,
reprocessing (reclaim), or properly
destroy it.
• Always determine possible refrigerant
recycling or reclaiming requirements
before beginning recovery. Questions
about recovered refrigerants and
acceptable refrigerant quality
standards are addressed in ARI
Standard 700.
ƽCAUTION
ƽWARNING
Freezing Temperatures!
Use of Pressure Regulator -
Valves - Gauges!
Do not allow liquid refrigerant to contact
skin. If it does, treat the injury similar to
frostbite. Slowly warm the affected area
with lukewarm water and seek immedi-
ate medical attention. Direct contact
with liquid refrigerant may cause minor
or moderate injury.
Always use pressure regulators, valves,
and gauges to control drum and line
pressures when pressure testing
equipment. Failure to follow these
instructions could result in an explosion
causing death, serious injury, or equip-
ment damage.
• Use approved containment vessels and
safety standards when shipping
SCXG-SVX01B-EN
99
Download from Www.Somanuals.com. All Manuals Search And Download.
maintenance
procedures
Maintenance
To charge the system, complete the
following procedure:
1. Charge liquid refrigerant into the liquid
line service valve of each compressor
circuit.The vacuum will draw some of
the required refrigerant into the
system. See Figure O-M-9.
2. Complete the charging process by
charging gaseous refrigerant into the
suction line shrader valve with the unit
running. However, make sure that
some refrigerant is present in each
circuit before starting the compressors.
The refrigerant container should be
upright so that gaseous refrigerant is
drawn off the top.
Note: SeeTables M-MP-6 and M-MP-7 for
refrigerant charge requirements.
NOTICE
Compressor Damage!
Do not allow liquid refrigerant to enter
the suction line. Excessive liquid accumu-
lation in the liquid lines may result in
compressor damage.
Figure M-MP-10.Typical water-cooled (SXWF) compressor section components
100
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
maintenance
procedures
Maintenance
Coil Fin Cleaning
Inlet GuideVanes
Keep coils clean to maintain maximum
performance. For operation at its highest
efficiency, clean the refrigerant coil often
during periods of high cooling demand or
when dirty conditions prevail. Clean the
coil a minimum of once per year to
prevent dirt buildup in the coil fins, where
it may not be visible.
ƽWARNING
Perform the following procedure every
six months for proper inlet guide vane
operation:
1. Spray all parts of guide vane assembly
with WD40.
2. Spray all steel parts of guide vane
assembly with ZRC.
3. Spray hubs and moving parts with dry
silicone lubricant (Mobil Mobilux 2, Shell
alvonia 2, or equivalent).
Hazardous Chemicals!
Coil cleaning agents can be either acidic
or highly alkaline. Handle chemical
carefully. Proper handling should include
goggles or face shield, chemical resistant
gloves, boots, apron or suit as required.
For personal safety refer to the cleaning
agent manufacturer’s Materials Safety
Data Sheet and follow all recommended
safe handling practices. Failure to follow
all safety instructions could result in
death or serious injury.
Remove large debris from the coils and
straighten fins before cleaning. Remove
filters before cleaning.
On occasion, the inlet guide vane actuator
or inlet guide vanes may need to be
removed. For proper adjustment of inlet
guide vanes and/or actuator.
Clean refrigerant coils with cold water
and detergent, or with one of the com-
mercially available chemical coil clean-
ers. Rinse coils thoroughly after cleaning.
Note: Perform this procedure monthly if the
unit is in a coastal area or corrosive
environment.
Economizer and evaporator coils are
installed so the evaporator is directly
behind the economizer.To clean between
the coils, remove the sheet metal block
off. Access the block off by removing the
corner panels on the unit’s left or right
rear side.
If the refrigerant coil is installed back to
back with the waterside economizer coil,
use a cleaner that is acceptable for
cleaning both types of coils.
ƽWARNING
Hazardous Voltage w/Capaci-
tors!
NOTICE
Proper Coil CleaningAgent!
Disconnect all electric power, including
remote disconnects before servicing.
Follow proper lockout/tagout proce-
dures to ensure the power cannot be
inadvertently energized. For variable
frequency drives or other energy storing
components provided byTrane or others,
refer to the appropriate manufacturer’s
literature for allowable waiting periods
for discharge of capacitors.Verify with an
appropriate voltmeter that all capacitors
have discharged. Failure to disconnect
power and discharge capacitors before
servicing could result in death or serious
injury.
Do not clean the refrigerant coil with hot
water or steam.The use of hot water or
steam as a refrigerant coil-cleaner agent
may cause high pressure inside the coil
tubing and subsequent damage to the
coil.
Do not use acidic chemical coil cleaners.
Also, do not use alkaline chemical coil
cleaners with a pH value greater then
8.5 (after mixing) without using an
aluminum corrosion inhibitor in the
cleaning solution. Use of the chemical
may result in equipment damage.
Note: For additional information regard-
ing the safe discharge of capacitors, see
PROD-SVB06A-EN or PROD-SVB06A-FR.
SCXG-SVX01B-EN
101
Download from Www.Somanuals.com. All Manuals Search And Download.
maintenance
procedures
Maintenance
Inspecting and Cleaning Coils
5. Mix a high quality coil cleaning
detergent with water according to the
manufacturer’s instructions. If the
detergent is strongly alkaline after
mixing (pH 8.5 or higher), it must
contain an inhibitor. Carefully follow the
cleaning solution manufacturer’s
instructions regarding product use.
6. Place the mixed solution in a garden
pump-up sprayer or high pressure
sprayer. If using a high pressure
sprayer note the following:
Cleaning the Condenser
Coils become externally fouled as a result
of normal operation. Coil surface dirt
reduces heat transfer ability and can
cause comfort problems, increased
airflow resistance and thus increased
operating energy costs.
NOTICE
ProperWaterTreatment!
The use of untreated or improperly
treated water in a CenTraVac may result
in scaling, erosion, corrosion, algae or
slime. It is recommended that the
services of a qualified water treatment
specialist be engaged to determine what
water treatment, if any, is required.Trane
assumes no responsibility for equipment
failures which result from untreated or
improperly treated water, or saline or
brackish water.
Inspect coils at least every six months or
more frequently as dictated by operating
experience. Cleaning frequently is
dependent upon system operating hours,
filter maintenance, efficiency, and dirt
load. Following is the suggested method
for cleaning steam and hot water coils.
• Maintain a minimum nozzle spray
angle of 15°
• Spray perpendicular to the coil face
• Protect other areas of the equipment
and internal controls from contact with
moisture or the cleaning solution
• Keep the nozzle at least six inches from
the coil
Steam and Hot Water Coils
1. Disconnect all electrical power to the
unit.
2.Wear the appropriate personal
protective equipment (PPE).
Condensing water contains minerals that
collect on the condenser tube walls.
Cooling towers also collect dust and
foreign materials that deposit in the
condenser tube.The formation of scale or
sludge in the condenser is indicated by a
decreased water flow, low temperature
difference between inlet and outlet water,
and abnormally high condensing tem-
peratures.To maintain maximum
condenser efficiency, the condenser must
remain free of built-up scale and sludge.
Clean the condenser either mechanically
or chemically.
3. Access both sides of the coil section.
4. Use a soft brush to remove loose
debris from both sides of the coil.
5. Use a steam cleaning machine, starting
from the top of the coil and working
downward. Clean the leaving air side of
the coil first, then the entering air side.
Use a block-off to prevent steam from
blowing through the coil and into a dry
section of the unit.
6. Repeat step 5 as necessary. Confirm
that the drain line is open following
completion of the cleaning process.
7. Allow the unit to dry thoroughly before
putting the system back into service.
8. Straighten any coil fins that may be
damaged with a fin rake.
9. Replace all panels and parts and
restore electrical power to the unit.
10. Ensure that contaminated material
does not contact other areas of the
equipment or building. Properly dispose
of all contaminated materials and
cleaning solutions.
• Do not exceed 600 psig
Draining theWaterside Economizer Coil
NOTICE
Coil Freezeup!
Properly drain and vent coils when not in
use.Trane recommends glycol protection
in all possible freezing applications. Use a
glycol approved for use with commercial
cooling and heating systems and copper
tube coils. Failure to do so may result in
equipment damage.
Mechanical Cleaning of Condenser and
Economizer Coils
1.Turn off the condenser supply water.
Remove drain plugs discussed in the
“Draining the Coil” section on page 91.
2. Remove the condenser head to expose
the condenser tubes.
3. Rotate a round brush through the tubes
to loosen contaminant.
4. Flush tubes with water to push the
sludge out through the drain opening in
the bottom of the supply header and
the return pipe.
5.To clean the economizer tubes, remove
the cast iron header plates at both sides
of the coil between the inlet and outlet
headers (four-row coils only; two-row
coils do not have cover plates at right
end). Rotate round brush through tubes
from left end to loosen contaminants.
Flush tubes with water.
Drain plugs are in the piping below each
coil’s supply and return header. Use these
plugs to drain the coil and piping.When
draining the coil, open the vents at the top
of the supply and return headers. Also, a
drain plug is at the bottom of the inlet
condenser manifold and in the outlet pipe
near the unit’s left side. Remove these
plugs to drain the condensers. Be sure to
open the vent plugs at the top of the
condenser inlet and outlet manifold. See
Figure O-M-9.
Refrigerant Coils
1. Disconnect all electrical power to the
unit.
2.Wear the appropriate personal
protective equipment (PPE).
3. Access to the coil section of the unit
(both sides).
4. Use a soft brush to remove loose
debris from both sides of the coil.
When refilling the condenser/waterside
economizer coil system with water,
provide adequate water treatment to
prevent the formation of scale or corro-
sion.
102
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
maintenance
procedures
Maintenance
6. Replace condenser end plates and
clamps.The end plates must be
centered when tightening the clamp.
7. Replace coil headers with gaskets and
torque bolts to 50 ft.-lb.
1. Remove actuator motor from support
plate.
2. Remove shaft coupling.
3.Torque the packing nut to 10-ft.-lbs. of
torque.
4. Replace shaft coupling.
5. Replace actuator motor.
direction or the arrow. Push the paddle
assembly in until it hits the barrel cavity
bottom.
7. Place the spring clip into the switch
barrel and push it down with a small,
flat blade screwdriver until the spring
clip engages the groove in the switch
barrel.
8. Replace drain and vent plugs.
Chemical Cleaning of Condenser and
Economizer Coil
Flow Switch Maintenance
8.When replacing the paddle assembly,
check the operation by pushing on the
paddle’s flat side.The paddle should
swing freely in the direction of the
arrow.This action confirms that the
paddle assembly is properly installed.
9. Replace the switch into the unit piping
using a good pipe thread sealer.Tighten
the switch so that its final position has
the arrow parallel to the water pipe and
pointing toward the left end of the unit
(arrow is pointing in the direction of the
water flow).
Chemical cleaning removes scale
deposits built up by minerals in the water.
For a suitable chemical solution, consult a
water treatment specialist. The
condenser water circuit is composed of
copper, steel, and cast iron.
Flow switches have a magnet on the
vane assembly that attracts ferrous
particulate may build up on the magnet to
the point that the vane will wedge and not
operate properly.
When the flow switch does not operate,
remove and replace it or disassemble
and clean it.
The chemical supply house should
approve or provide all materials used in
the external circulating system, along
with the quantity of cleaning material,
duration of cleaning time, and safety
precautions necessary for handling the
cleaning agent.
Cleaning the Flow Switch
If ferrous particulate contaminates tower
water, the ferrous particles may cling to
the magnet on the switch paddle
assembly. Build up of the ferrous particles
may cause the paddle to stick and not
function properly.
Piping Components
To avoid this problem, remove the switch
and clean each time you clean the
condensers, or clean as needed to keep
the switch operational.
WaterValves
Water valves have a stern packing nut. If
there is evidence of water leakage at the
valve stem, proceed as follows:
To clean the paddle assembly, remove it
following the procedure below:
1. Remove the switch from the unit.
2. The paddle assembly and wire retainer
clip holds the paddle assembly in the
switch body.
3. Remove the wire retainer clip by
reaching down past the paddle with a
pair of slim nosed pliers and gripping
the end of the wire. Pull up on the wire,
clip, and remove it.
4. After removing the wire clip, use the
pliers to pull the paddle assembly out of
the switch barrel. Clamp the pliers onto
the end of the paddle and remove the
paddle assembly. It will slide straight
out.
5. Clean the ferrous particulate from the
magnet using a rag or tack cloth.The
particulate is attracted to the magnet,
so it is necessary to pull it off. It will not
easily wipe off.
ƽWARNING
Hazardous Voltage w/Capaci-
tors!
Disconnect all electric power, including
remote disconnects before servicing.
Follow proper lockout/tagout proce-
dures to ensure the power cannot be
inadvertently energized. For variable
frequency drives or other energy storing
components provided byTrane or others,
refer to the appropriate manufacturer’s
literature for allowable waiting periods
for discharge of capacitors.Verify with an
appropriate voltmeter that all capacitors
have discharged. Failure to disconnect
power and discharge capacitors before
servicing could result in death or serious
injury.
6. After cleaning the magnet, replace the
paddle assembly into the switch body’s
barrel. However, it is important to
position the paddle perpendicular to the
arrow on the switch’s side and place the
paddle’s flat side facing the opposite
Note: For additional information regard-
ing the safe discharge of capacitors, see
PROD-SVB06A-EN or PROD-SVB06A-FR.
SCXG-SVX01B-EN
103
Download from Www.Somanuals.com. All Manuals Search And Download.
maintenance
procedures
Maintenance
Maintenance Periodic
Checklists
Remove algae and or any airflow
obstructions.
4. Check the condition and tension of fan
belts. Adjust tension if belts are floppy
or squeal continually. Replace worn or
fraying belts in matched sets.
4. Check the fan assembly sheave
alignment.Tighten set screws to their
proper torques.
5. Check water valves for leakage at
valve stem packing nut.
6. Inspect the inlet vane assembly and
perform maintenance procedures in
the IGV maintenance section.
Monthly Checklist
The following check list provides the
recommended maintenance schedule to
keep the commercial self-contained
equipment running efficiently.
Note: Check belt tension and adjust it at
least twice daily the first days of new belt
operation. Belt tension will rapidly decrease
until the belts are run in.
Note: Perform this procedure monthly if the
unit is in a coastal or corrosive environ-
ment.
ƽWARNING
Hazardous Voltage w/Capaci-
tors!
5. Check the liquid line sight glasses
during operation. Bubbles in the sight
glasses indicate a possible shortage of
refrigerant or an obstruction in the
liquid lines, e.g. dirty liquid line filter
driers.
6. Inspect filter driers for leaks, flow
obstructions, or temperature drop
across the filter drier. A noticeable
temperature differential, e.g. 5°F, in the
liquid line may indicate an obstruction.
Replace the filter drier if it appears
clogged.
Annual Maintenance
Check and tighten all set screws, bolts,
locking collars and sheaves.
1. Inspect, clean, and tighten all electrical
connections.
2. Visually inspect the entire unit casing
for chips or corrosion. Remove rust or
corrosion and repaint surfaces.
3. Visually check for leaks in refrigerant
piping.
4. Inspect fan, motor, and control contacts.
Replace badly worn or eroded contacts.
5. Inspect the thermal expansion valve
sensing bulbs for cleanliness, good
contact with the suction line, and
adequate insulation from ambient air.
6.Verify the superheat setting is 12 -17°F
at the compressor.
Disconnect all electric power, including
remote disconnects before servicing.
Follow proper lockout/tagout proce-
dures to ensure the power cannot be
inadvertently energized. For variable
frequency drives or other energy storing
components provided byTrane or others,
refer to the appropriate manufacturer’s
literature for allowable waiting periods
for discharge of capacitors.Verify with an
appropriate voltmeter that all capacitors
have discharged. Failure to disconnect
power and discharge capacitors before
servicing could result in death or serious
injury.
7. Inspect the optional waterside
economizer coil. Clean the coil to
prevent airflow restrictions through the
fins.
8. Check and record operating pressures.
Semi-Annual Maintenance
1.Verify the fan motor is properly
lubricated. Follow lubrication
Note: For additional information regard-
ing the safe discharge of capacitors, see
PROD-SVB06A-EN or PROD-SVB06A-FR.
When checking operating pressures and
conditions, establish the following
nominal conditions for consistent mea-
surements.
1. Leaving air temperature greater than
60°F
2. Entering air temperature is 80 - 90°F
3. Entering water temperature greater
than 65°F
4. Inlet guide vanes at least halfway open
5. Compressors running at full load
6. Drain the condensing water system
and inspect it thoroughly for fouling,
clean condensers if necessary.
recommendations on the motor tag or
nameplate. Contact the motor
manufacturer for more information.
2. Lubricate fan bearings. For best results,
lubricate bearings during unit operation.
Refer to the “Fan Bearings” section on
page 84.
3.With power disconnected, manually
rotate the fan wheel to check for
obstructions in the housing or
interference with fan blades or inlet
guide vane option. Remove
1. Inspect unit air filters. Clean or replace
if airflow is blocked or if filters are dirty.
2. Inspect coils for excess moisture or
icing. Icing on the coils may indicate low
airflow supply, restricted airflow from
dirty fins, evaporator frost protection
sensor problems, or a shortage of
refrigerant flowing through the coil.
3. Check that condensate from the
evaporator and economizer coils flows
freely through the condensate piping,
traps, drain pan, and drainage holes.
obstructions and debris. Center the fan
wheel if necessary.
104
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
troubleshooting
System Checks
4. Inspect air filters and coils to bel sure
that airflow to the unit is not restricted.
5. Check the zone thermostat settings.
6. Ensure that the fan is rotating in the
proper direction. If phasing is wrong at
the main power terminal block, the fan
and compressors will not run correctly.
7. Inspect ductwork and duct connections
for tightness.
It is important that pressures be mea-
sured under stable and constant condi-
tions in order for the readings to be
useful.
ƽWARNING
Voltage Imbalance
Live Electrical Components!
Voltage imbalance on three-phase
systems can cause motor overheating
and premature failure. Maximum
allowable imbalance is 2.0%, and the
readings used to determine it must be
measured at the compressor terminals.
During installation, testing, servicing and
troubleshooting of this product, it may be
necessary to work with live electrical
components. Have a qualified licensed
electrician or other individual who has
been properly trained in handling live
electrical components perform these
tasks. Failure to follow all electrical
safety precautions when exposed to live
electrical components could result in
death or serious injury.
Operating Procedures
Install pressure gauges on the discharge
and suction line access valves.When the
unit has stabilized (after operating
approximately 15 minutes at full load),
record suction and discharge pressures.
System malfunctions such as low airflow,
line restrictions, incorrect refrigerant
charge, malfunctioning of expansion
valves, damaged compressors, etc. will
result in pressure variations which are
outside the normal range.
Voltage imbalance is defined as 100
times the sum of the division of the three
voltages from the average voltage. If, for
example, the three measured voltages
are 221, 230, 227, the average is:
(221+230+227) = 226 volts
3
Before proceeding with technical trouble
charts or controls checkout, complete the
following system analysis:
1. Measure actual supply voltage at the
compressor and an motor terminals
with the unit running.Voltage must be
within the range listed on the motor
nameplate. Phase imbalance must be
less than 2.0%.
2. Check all wiring and connections to be
sure that they are intact, secure and
properly routed.The as wired system
diagrams are provided in the unit
control panel.
3. Check that all fuses are installed and
properly sized.
Therefore, the percentage of voltage
imbalance is:
100*(226-221) = 2.2%
Note: If phasing at the main incoming
power terminal is incorrect, switch two of
the three incoming power leads. If a
compressor has been replaced and the
phase is changed at the compressor, it will
run backwards and discharge pressure will
be very low. To resolve incorrect compres-
sor wire phasing, change phasing at the
compressor.
226
In this example, 2.2% imbalance of more
than 2.0% exists, be sure to check the
voltage at the unit disconnect and
terminal block switch. If an imbalance at
the unit disconnect switch does not
exceed 2.0%, the imbalance is caused by
faulty wiring within the unit. Be sure to
conduct a thorough inspection of the unit
electrical wiring connections to locate the
fault, and make any repairs necessary.
Common Unit Problems and Solutions
Problem
Possible Cause
Remedy
Drain pan is overflowing
Plugged drain line
Unit not level
Clean drain line
Level unit
Standing water in drain pan
Wet interior insulation
Unit not level
Level Unit
Plugged drain line
Clean drain line
Coil face velocity too high
Improper trap design
Drain pan leaks/overflowing
Condensation on surfaces
Reduce fan speed
Design trap per unit installation instructions
Repair Leaks
Insulate surfaces
Excess dirt in unit
Missing filters
Filter bypass
Replace filters
Reduce filter bypass
Microbial growth (mold)
Standing water in drain pan
Moisture problems
See “Standing water in drain pan” above
See “Wet interior insulation” above
SCXG-SVX01B-EN
105
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
diagnostics
Diagnostics
Reset Required: (PAR) An automatic reset
occurs after the CO2 sensor transducer
input receives a signal that is within range
for ten continuous seconds.
CondenserTemp Sensor Failure - Circuit 1,
2, 3, or 4
Problem: The saturated condenser
temperature input is out of range for circuit
#1, 2, 3, or 4.
Refer to the IntelliPak Self-Contained
Programming Guide, PKG-SVP01B-EN,
for specific unit programming and
troubleshooting information. In particular,
reference the “Service Mode Menu” and
“Diagnostic Menu”sections in the
programming guide. Refer to the
following text for general diagnostic and
troubleshooting procedures. Common
diagnostics and troubleshooting
Compressor Contactor Fail - Circuit 1, 2,
3, or 4
Problem: The compressor contactor for
Ckt. 1, 2, 3, or 4 has malfunctioned.
Check: Sensor resistance should be
between 830 ohms (200°F) and 345.7
ohms (-40°F). If so, check field/unit wiring
between sensor and MCM/SCM.
Reason for Diagnostic: The circuit
compressor proving input is detected
closed continuously for more than three
seconds while neither compressor output
on that circuit closes.
Reason for Diagnostic: The unit is reading a
signal that is out of range for the circuit #1,
2, 3, or 4 saturated condenser temperature
sensor. (temp < -55°F or temp > 209°F).
procedures follow below.
A
Auto Reset S/A Static Pressure Limit
Problem: The supply air static pressure
went too high.
UCM Reaction: A “Lockout Ckt # 1, 2, 3, or
4” request is issued to the compressor
staging control function.
UCM Reaction: A "lockout ckt #1, 2, 3, or 4
request is issued to the compressor
staging control function.
Reason for Diagnostic: The S/A static
pressure exceeded the S/A static
pressure limit setpoint for at least one
second continuously.
Reset Required: (PAR) An automatic reset
occurs after the circuit 1, 2, 3, or 4
condenser temp input returns to its
allowable range within 10 seconds.
Reset Required: (PMR) A manual reset is
required after the disgnostic is set. It can
be reset by the HI orTracer Summit.
UCM Reaction: A "supply air pressure
shutdown" signal is sent to the following
functions:
CompressorTrip - Ckt 1, 2, 3, or 4
Problem: The compressor ckt #1, 2, 3, or 4
has tripped.
D
Dirty Filter
Problem:There is a dirty filter.
a. Compressor staging control,
b. Economizer actuator control,
c. Heat operation,
Reason for Diagnostic: The ckt #1, 2, 3, or
4 compressor proving input is detected
open continuously for more than 3
seconds when either or both compressor
outputs on that circuit energize (as
described in the compressor protection
function).
Reason for Diagnostic: The filter switch
input on the RTM is closed for more than
60 seconds continuously.
d. Supply fan control,
e. IGV/VFD control,
f. Exhaust fan control,
g. Exhaust actuator control
UCM Reaction: An information only
diagnostic is set.
Reset Required: (PAR) An automatic reset
occurs after the IGV close. The supply fan
is not allowed to restart for 15 seconds
after the diagnostic occurs. An auto reset
will also occur if the unit cycles out of
occupied mode and back.
Reset Required: (INFO) An automatic reset
occurs after the dirty filter input reopens
for 60 continuous seconds.
Reason for Diagnostic: The circuit
compressor proving input is detected
open continuously for more than 3
seconds when either or both compressor
outputs on that circuit energize (as
described in the compressor protection
function).
E
C
ECEM Communications Failure
Problem: The RTM has lost communication
with the ECEM.
CO2 Sensor Failure
Problem: The VCM CO2 sensor input
signal is out of range.
UCM’ Reaction: A “lockout ckt #1, 2, 3, or
4” request is issued to the compressor
staging control function.
Check: Field/unit wiring between RTM and
ECEM module.
Check: Check field/unit wiring between
sensor and VCM.
Reset Required: (PMR) A manual reset is
required after this diagnostic occurs. The
diagnostic can be reset by the unit
Reason for Diagnostic: The RTM has lost
communication with the ECEM.
UCM Reaction: If the unit has the
comparative enthalpy option, the
economizer enable r.e. enthalpy function
will revert to level 2 enthalpy comparison.
Reason for Diagnostic: The unit is reading
a signal that is out of range for the CO2
sensor transducer input.
mounted HI module orTracer Summit.
UCM Reaction: The CO2 reset function
disables.
106
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
diagnostics
Reset Required: (PAR) An automatic reset
occurs after communication has been
restored.
configured with water cooled
chilled water cooling function will be
cancelled.
b. If any of the GBAS setpoint control
parameters are the HI-selected setpoint
sources, then those setpoints will revert
to the default HI setpoints.
c. Any active GBAS output control
parameters will be ignored.
d. A failsafe function in the GBAS module
will cause all GBAS outputs to be
zeroed and deenergized.
condenser and/or economizer
c.Time to React: 10 sec <T < 20 sec
d. DiagnosticText (Human Interface
Display) “ENTERINGWATERTEMP
SENSOR FAIL”
e. Actions to be Initiated: A “Disable
Water Side Economizer” request is
issued to “Water Side Economizer
Temperature Enable Function”
f. Reset: An automatic reset occurs after
the EnteringWaterTemp. input returns to
within range continuously for 10 seconds.
Emergency Stop
Problem: The emergency top input is
open.
Reason for Diagnostic: An open circuit
has occurred on the emergency stop
input caused either by a high duct temp t-
stat trip, or the opening of field-provided
contacts, switch, etc.
Reset Required: (PAR) An automatic reset
occurs after communication has been
restored.
UCM Reaction: Off or close requests are
issued as appropriate to the following
functions;
a. Compressor staging/chilled water
cooling control
b. Heat operation
c. Supply fan control and proof of
operation
d. Exhaust fan control and proof of
operation.
e. Exhaust actuator control
f. Outside air damper control
g. OnVAV units, IGV/VFD control
EvapTemp Sensor Failure - Circuit 1, 2, 3,
or 4
Problem: The evaporator temperature
sensor (ckt #1, 2, 3, or 4) is out of range.
H
Heat Failure
Problem: The heat has failed.
(Electric heat unit)Typically, this is
because the electric heat section became
too hot.
Check: Sensor resistance should be
between 830 ohms (200°F) and
345.7Kohms (-40°F). If so, check field/unit
wiring between sensor and MCM/SCM.
Reason for Diagnostic: The heat fail input
on the heat module was closed:
a. for more than 80 seconds,
b. for ten consecutive occurrances (each
lasting five seconds or more) within a
210 second period.
Reason for Diagnostic: The unit is reading
a signal that is out of range for the circuit
#1 evaporator temperature sensor input
(temp < -55°F or temp > 209°F).
Reset Required: (PMR) A manual reset is
required after the emergency stop input
recloses. The diagnostic can be reset by
the HI.
UCM Reaction: The coil frost protection
function for the refrigeration circuit (#1, 2,
3, or 4) only is disabled.
UCM Reaction: An information only
diagnostic is set.
Reset Required: (PAR) An automatic reset
occurs after the #1, 2, 3, or 4 evap temp
input returns to its allowable range for 10
seconds.
Entering Cond WaterTemp Sensor Fail
Problem:
Reset Required: (INFO) An automatic
reset occurs after the heat fail input
remains open for 210 seconds
continuously.
Activation Conditions: temperature < -
50°F or temperature > 209°F, and unit
configured for water cooled
G
condenser
Heat Module Auxilliary Temperature
Sensor Fail
Problem: The heat mod aux temp sensor
input is out of range.
c.Time to React: 10 sec <T < 20 sec
d. DiagnosticText (Human Interface
Display) “ENT CONDWATERTEMP
SENSOR FAIL”
GBAS 0-5 VDC Module Comm Failure
Problem: The RTM has lost
communication with the GBAS module.
e. Actions to be Initiated: A “Lockout All
Ckts ” request is issued to the
“Compressor Staging Function”
f. Reset: An automatic reset occurs after
the entering condenser water
temperature input returns to within range
continuously for 15 seconds.
Check: Field/unit wiring between RTM
and GBAS.
Check: Sensor resistance should be
between 830 ohms (200°F) and 345.7
ohms (-40°F). If so, check field/unit wiring
between sensor and heat module.
Reason for Diagnostic: The RTM has lost
communication with the GBAS module.
Reason for Diagnostic: At least one
enabled unit function has the heat
module auxillary temperature input
designated as its sensor, and the unit is
reading a signal that is out of range for
this input (temp < -55°F or temp > 209°F).
UCM Reaction: The UCM will initiate the
following actions;
a. If the demand limit input was closed
prior to the communications loss, then
the demand limit commands issued to
the heat operation function (if
Entering Water Temp Sensor Fail
a. Data used (module, packet, byte, bit):
WSM, 01,18,05
b. Activation Conditions: temperature < -
50°F or temperature > 209°F, and unit
applicable) and the compressor staging/
UCM Reaction: The functions that
SCXG-SVX01B-EN
107
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
diagnostics
designated the heat module auxillary
temperature input as their input are
disabled.
for > 1 second. On units with both
hydronic heat and chilled water, both low
air temp limit inputs are active, and the
unit will respond in the same manner
regardless of which input is used.
supply air static pressure limit diagnostic
has occurred for the third time while the
unit is operating in occupied mode.
Reset Required: (PAR) An automatic reset
occurs after the heat module auxillary
temperature input returns to its allowable
range for 10 seconds.
UCM Reaction: A "supply air pressure
shutdown" signal is sent to the following
functions;
UCM Reaction: The UCM will initiate the
following actions;
a. Compressor staging control,
b. Economizer actuator control,
c. Heat operation,
a. An “open all water valves”request is
issued to the heat module function,
causing any steam, hot water, or chilled
water valves on the unit to open.
b. An “all heat off” request is issued to
the heat control function.
c. A “fan off” request is sent to the supply
fan control function.
d. A “close damper” request is sent to
the economizer actuator control
function.
Heat Module Comm Failure
Problem: The RTM has lost
communication with the heat module.
d. Supply fan control,
e. IGV/VFD control,
f. Exhaust fan control
g. Exhaust actuator control
Check: Check field/unit wiring between
RTM and heat module.
Reset Required: (PMR) A manual reset is
required and can be accomplished at the
HI,Tracer Summit, or by cycling power to
the RTM.
Reason for Diagnostic: The RTM has lost
communication with the heat module.
UCM Reaction: An “all heat off” request
is sent to the heat operation function.
Reset Required: (PMR) A manual reset is
required after the low air temp limit trip
condition clears. The diagnostic can be
reset at the unit mounted human
interface, byTracer Summit, or by cycling
power to the RTM.
MCM Communications Failure
Problem: The RTM has lost communication
with the MCM.
If the unit has staged gas or electric heat,
all heat module outputs will be zeroed
and deenergized.
Check: Check field/unit wiring between
RTM and MCM.
If the unit has hydronic heat or chilled
water installed, the unit will turn off the
supply fan and close the outside air
damper upon the occurrance of a heat
module comm failure. A failsafe function
in the heat module will cause all water
valves to be set to 100% to provide full
water flow. Unless used for switching
purposes (air handlers with chilled water
and mod gas, or chilled water and
hydronic heat) all binary outputs will be
deenergized.
Low Pressure Control Open - Circuit 1, 2,
3, or 4
Problem: The Low Pressure Control (LPC)
for Ckt #1, 2, 3, or 4 is open.
Reason for Diagnostic: The RTM has lost
communications with the MCM.
UCM Reaction: A “Lockout” request is
sent to the compressor staging control
function. And a failsafe function in the
MCM will cause all MCM outputs to be
zeroed and deenergized.
Check: State of refrigerant charge for ckt
#1, 2, 3, or 4.
Reason for Diagnostic: The Ckt # 1 LPC
input is detected open as described in the
compressor protection function.
Reset Required: (PAR) An automatic reset
occurs after communication has been
restored.
Reset Required: (PAR) An automatic reset
occurs after communication has been
restored.
UCM Reaction: A “Lockout Ckt # 1, 2, 3, or
4” request is issued to the compressor
staging control function.
Mode Input Failure
Problem: The RTM mode input is out of
range.
Reset Required: (PMR) A manual reset is
required anytime after the diagnostic is
set. The diagnostic can be reset by the
human interface,Tracer Summit, or by
cycling power to the RTM.
L
Check: Sensor resistance should be
between 1 ohm and 40 ohms. If so, check
field/unit wiring between sensor and RTM.
Low Air Temp Limit Trip
Problem: The low air temp limit has
tripped. (Units with steam or hot water
heating, or air handlers with chilled water
cooling)
Reason for Diagnostic: The mode input
signal on the RTM is out of range
(resistance < 1 ohm or resistance > 40
ohms).
M
Reason for Diagnostic: A low air temp
limit trip is detected continuously for
more than one second. This can occur if
the hydronic heat low air temp limit input
closes for > 1 second, or if the chilled
water low air temp limit trip input opens
Manual Reset SA Static Press Limit
Problem: The supply air static pressure
went too high for the third consecutive
time.
UCM Reaction: The system mode reverts
to the default (HI set) system mode.
Reason for Diagnostic: The auto reset
Reset Required: (INFO) An automatic reset
108
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
diagnostics
occurs after the mode input returns to its
allowable range for 10 seconds.
temperature changeover (“Level 1”)
control.
range for 10 continuous seconds, or after
a different occupied zone heating setpoint
selection source is user-defined.
Reset Required: (PAR) An automatic reset
occurs after the OA humidity input
returns to its allowable range for 10
seconds.
N
R
NSB Panel ZoneTemperature Sensor
Failure
Problem: The NSB panel's zone temp
sensor input is out of range. (This input is
at the NSB panel, not on the unit itself).
Return Air Humidity Sensor Failure
Problem: On units with both airside
economizer and comparative enthalpy
installed, the return air humidity sensor
input is out of range.
O/ATemp. Sensor Failure
Problem: The outside air temperature
sensor input is out of range.
Check: If have an external sensor
Check: Check field/unit wiring between
the sensor and ECEM.
Check: Sensor resistance should be
between 830 ohms (200°F) and 345.7
ohms (-40°F). If so, check field/unit wiring
between sensor and RTM.
connected to the NSB panel zone sensor
input, then the internal NSB panel zone
sensor should be disabled.Verify sensor
resistance. If in valid range, check wiring
between the sensor and NSB panel.
Reason for Diagnostic: The unit is reading
a signal that is out of range for the return
air humidity sensor (humidity < 5% or
humidity > 100%).
Reason for Diagnostic: The unit is reading
a signal that is out of range for the outside
air temperature input on the RTM (temp.
< -55°F or temp > 209°F).
NSB Panel Comm Failure
Problem: The RTM has lost
communications with the night setback
panel (programmable zone sensor).
UCM Reaction: The economizer enable
r.e. enthalpy function reverts to reference
enthalpy changeover (“Level 2”) control.
UCM Reaction: These unit functions
occur:
• low ambient compressor lockout
disables
• O/A damper drives to minimum position
• onVAV units with S/A temp. reset type
selected as O/A temp. reset, the reset
type reverts to “none” for the duration
of the failure
Check: Field/unit wiring between RTM
and NSB Panel.
Reset Required: (PMR) An automatic
reset occurs after the RA humidity input
returns to its allowable range
Reason for Diagnostic: The RTM has lost
communication with the NSB panel.
continuously for 10 seconds.
UCM Reaction: The unit reverts to the
next lower priority mode switching
source (typically the HI default mode). If
the NSB panel zone sensor is the
designated sensor source for any
functions, those functions are disabled.
Return AirTemp Sensor Failure
Problem: On units with the comparative
enthalpy option, the return air
Reset Required: (PAR) an automatic reset
occurs after the O/A temperature input
returns to its allowable range.To prevent
rapid cycling of the diagnostic, there is a
10 second delay before the automatic
reset.
temperature sensor input is out of range.
Check: Sensor resistance should be
between 830 ohms (200°F) and 345.7
ohms (-40°F). If so, check field/unit wiring
between the sensor and ECEM.
Reset Required: (PAR) An automatic reset
occurs after communication has been
restored.
Occupied Zone Heat Setpoint Failure
Problem: The occupied zone heat setpoint
input is out of range.
Reason for Diagnostic: The unit is reading
a signal that is out of range for the return
air humidity sensor (temp < -55°F or
temp > 209°F).
O
O/A Humidity Sensor Failure
Problem: The outside air humidity sensor
data is out of range.
Reason for Diagnostic: The input
designated as occupied zone heating
setpoint source is out of range for the
outside air temperature input on the RTM
(temp. < 45°F or temp > 94°F).
UCM Reaction: The economizer enable
r.e. enthalpy function reverts to reference
enthalpy changeover (“Level 2”) control.
Check: Check field/unit wiring between
the sensor and RTM.
Reset Required: (PAR) An automatic reset
occurs after the RA temp input returns to
its allowable range continuously for 10
seconds.
UCM Reaction: The active occupied zone
heating setpoint reverts to the default
value.
Reason for Diagnostic: The unit is reading
a signal that is out of range for the outside
air humidity sensor (humidity < 5% or
humidity > 100%).
Reset Required: (PAR) an automatic reset
occurs after the occupied zone heating
setpoint input returns to its allowable
UCM Reaction: The economizer enable
enthalpy function reverts to dry-bulb
SCXG-SVX01B-EN
109
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
diagnostics
RTM Aux.Temp. Sensor Failure
Problem: The RTM auxillary temperature
sensor data is out of range.
ohms (-40°F). If so, check field/unit wiring
between sensor and RTM.
UCM Reaction:The default space
pressure setpoint will become the active
space pressure setpoint.
Reason for Diagnostic: At least one
enabled unit function has the RTM zone
temperature input designated as its
sensor, and the unit is reading a signal
that is out of range for this input (temp. < -
55°F or temp > 150°F).
Check: Sensor resistance should be
between 830 ohms (200°F)and 345.7
ohms (-40°F). If so, check field/unit wiring
between sensor and RTM.
Reset Required: (PAR) An automatic reset
occurs after the designated space
pressure setpoint source sends a signal
within range for 10 continuous seconds,
or after a different space pressure
setpoint source is user-defined.
Reason for Diagnostic: At least one
enabled unit function has the RTM
auxillary temperature input designated
as its sensor, and the unit is reading a
signal that is out of range for this input
(temp. < -55°F or temp > 209°F).
UCM Reaction: The functions with the
RTM zone temperataure input deignated
as their sensor are disabled.
Supply Air Pressure Sensor Failure
Problem: The supply air pressure sensor
voltage input is out of range.
Reset Required: (PAR) an automatic reset
occurs after the designated zone
temperature signal returns to its
allowable range.To prevent rapid cycling
of the diagnostic, there is a 10 second
delay before the automatic reset.
Check: Check field/unit wiring between
the sensor and RTM.
UCM Reaction: The functions with the
RTM auxillliary temperataure input
deignated as their sensor are disabled.
Reason for Diagnostic: The unit is reading
a signal that is out of range for the supply
air pressure sensor voltage input (input <
40mV or input > 4.75V)
Reset Required: (PAR) an automatic reset
occurs after the designated zone
temperature signal returns to its
S
allowable range.To prevent rapid cycling
of the diagnostic, there is a 10 second
delay before the automatic reset.
SCM Communication Failure
Problem: The RTM has lost
communication with the SCM.
UCM Reaction: The IGVs will drive closed,
and the following functions are disabled;
a. SA pressure control
b. SA static pressure limit
Check: Check field/unit wiring between
the RTM and SCM.
RTM Data Storage Error
Problem: There was a data transmission
error.
Reset Required: (PAR) An automatic reset
occurs after the SA temp heating setpoint
input returns to within range for 10
continuous seconds, or after a different
SA temp heating setopint selection
source is user-defined.
Reason for Diagnostic: The RTM has lost
communication with the SCM.
Check: This can be caused by an
intermittant power loss.Turn the unit off
for 1-2 minutes, then back on again. If
diagnostic persists, then the RTM may
need to be replaced.
UCM Reaction: A “lockout” request is
sent to the compressor staging control
function. A failsafe function in the SCM
will cause all SCM outputs to be zeroed
and deenergized.
Supply Air Pressure Setpoint Failure
Problem: The SA pressure input signal is
out of range.
Reason for Diagnostic: An error occurred
while the RTM was writing data to its
internal non-volitile memory (EEPROM).
Reset Required: (PAR) An automatic reset
occurs after communication has been
restored.
Reason for Diagnostic: The SA pressure
setpoint input is sending a signal that is
out of range (Input < 1.0 iwc or input > 4.3
iwc)
UCM Reaction: An information only
diagnostic will be displayed at the human
interface.
Space Static Press Setpt Failure
Problem: The active space static pressure
setpoint is out of range.
UCM Reaction: The default SA pressure
setpoint will become the active SA
pressure setpoint.
Reset Required: (INFO) A manual reset
may be made at the human interface, at
Tracer Summit, or by cycling power to
the RTM.
Check: Check setpoint value. Also, if
space pressure setpoint source is GBAS,
but this setpoint has not been assigned to
any of the four analog inputs on GBAS,
this message will occur.
Reset Required: (PAR) An automatic reset
occurs after the designated SA pressure
setpoint source sends a signal within
range for 10 continuous seconds, or after
a different SA pressure setpoint source is
user-defined.
RTM Zone Sensor Failure
Problem: The RTM zone temperature
sensor input is out of range.
Reason for Diagnostic: The unit is reading
a signal that is out of range for the space
static pressure setpoint (input < 0.03 iwc
or input > 0.20 iwc).
Check: Sensor resistance should be
between 830 ohms (200°F) and 345.7
110
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
diagnostics
SupplyAirTemp Cool Setpoint Fail
Problem: The active supply air
temperature cooling setpoint is out of
range.
UCM Reaction:These unit functions are
disabled:
Supply Fan VFD Bypass Enabled
a. Data used (module,packet,byte,bit): RTM
b. Activation conditions: supply fan VFD
bypass has been activated and supply fan
vfd bypass is installed.
c.Time to React: 10 sec <T < 20 sec
d. Diagnostic text (human interface display)
SUPPLY FAN VFD BYPASS ENABLED”
e. Actions to be Initiated: NONE
• supply air tempering
• economizing
• supply air temperature low limit function
(CV units)
• supply air temperature control heating
and cooling functions (VAV units)
Reason for Diagnostic: The input
designated as the SA temp cooling
setpoint is out is out of range (temp <
35°F or temp > 95°F).
Reset Required: (PAR) an automatic reset
occurs after the designated S/A
temperature input returns to its allowable
range.To prevent rapid cycling of the
diagnostic, there is a 10 second delay
before the automatic reset.
f. Reset: The INFO diagnostic is cleared
when the supply fan VFD bypass is
deactivated.
UCM Reaction: The default HI-set SA
temp cooling setpoint becomes the active
SA temp cooling setpoint.
T
Reset Required: (PAR) An automatic reset
occurs after the SA temp cooling setpoint
input returns to within range for 10
continuous seconds, or after a different
SA temp cooling setopint selection
source is user-defined.
LCI-I Module Comm Failure
Problem: The RTM has lost communication
with the LCI-I.
Supply Fan Failure
Problem: There is no supply airflow
indication after the supply fan is requested
on.
Check: Check field/unit wiring between
RTM and LCI-I module.
Supply AirTemp Heat Setpoint Fail
Problem: The active supply air
temperature cooling setpoint is out of
range.
Check: Check belts, linkages, etc. on the
supply fan assembly. If these are ok, check
field/unit wiring between RTM and supply
fan. If the supply fan runs in service mode,
then verify airflow proving switch and
wiring.
Reason for Diagnostic: The RTM has lost
communication with the LCI-I module.
UCM Reaction: All active commands and
setpoints provided byTracer Summit
through the LCI-I will be cancelled and/or
ignored. And whereTracer Summit has
been designated as setpoint source, local
HI default setpoints will be used.
Reason for Diagnostic: The input
designated as the SA temp heating
setpoint is out is out of range (temp <
35°F or temp > 185°F).
Reason for Diagnostic: The supply airflow
input is detected OPEN for 40 continuous
seconds during any period of time in which
the supply fan binary output is ON.
between 830 ohms (200°F) and 345.7
ohms (-40°F). If so, check field/unit wiring
between the sensor and MCM.
UCM Reaction: The default HI-set SA
temp heating setpoint becomes the
active SA temp heating setpoint.
Reset Required: (PAR) An automatic reset
occurs after communication has been
restored.
Reset Required: (PAR) An automatic reset
occurs after the SA temp heating setpoint
input returns to within range for 10
continuous seconds, or after a different
SA temp heating setopint selection
source is user-defined.
This input is ignored for up to 5 minutes
after the supply fan starts, until airflow is
first detected.
Tracer Communications Failure
Problem:The LCI-I has lost communication
withTracer Summit.
UCM Reaction: “Off” or “Close” requests
are issued as appropriate to the following
functions;
a. Compressor staging/chilled water
control
b. Heat operation
c. Supply fan control & proof of operation
d. Exhaust fan control & proof of operation
e. Exhaust actuator control
f. Economizer actuator control
g. IGV / VFD control
Check:Tracer Summit(building control
panel) is powered up and running properly.
If so, check unit wiring between LCI-I and
Tracer Summit (building control panel).
Supply Air Temperature Failure
Problem: The supply air temperature
sensor input is out of range.
Reason for Diagnostic:The LCI-I has lost
communications withTracer Summit for >
15 minutes.
Check: Sensor resistance should be
between 830 ohms (200°F) and 345.7
ohms (-40°F). If so, check field/unit wiring
between sensor and RTM.
UCM Reaction: All active commands and
setpoints provided byTracer Summit
through the LCI-I will be cancelled and/or
ignored. And whereTracer Summit has
been designated as the setpoint source,
local HI default setpoints are used.
Reason for Diagnostic: The unit is reading
a signal that is out of range for the supply
air temperature input on the RTM (temp.
< -55°F or temp > 209°F).
Reset Required: (PMR) A manual reset is
required anytime after the diagnostic is
set. The diagnostic can be reset at the HI,
Tracer Summit, or by cycling power to the
RTM.
SCXG-SVX01B-EN
111
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
diagnostics
Reset Required: (PAR) An automatic reset
occurs after communication between
Tracer Summit and the LCI-I is restored.
different, valid unoccupied zone cool
setpoint selection source.
Check: Check field/unit wiring between
sensor and VCM.
Reason for Diagnostic: The unit is reading a
signal that is out of range for the velocity
pressure transducer input (during
calibration:V < 40 mV orV > 420 mV,
during operation: V < 40 mV or V > 0.75 V).
Unoccupied Zone Heat Setpoint Failure
Problem: The unoccupied zone heating
setpoint input is out of range.
U
Unit HI Communications Failure
Problem: The RTM has lost
communication with the unit mounted
(local) human interface (HI).
Reason for Diagnostic: The input
designated as unoccupied zone heating
setpoint source is out of range (temp < 45
F or temp > 94 F).
UCM Reaction: The minimum airflow
control function is disabled. The outside air
damper minimum position function reverts
to using the O/A flow compensation
function if O/A flow compensation is
enabled or to the default minimum position
function if O/A flow compensation is
disabled or not available.
Check: Field/unit wiring between RTM
hand local HI.
UCM Reaction: The active unoccupied
zone heating setpoint reverts to the
default value.
Reason for Diagnostic: The RTM has lost
communication with the unit-mounted
human interface.
Reset Required: (PAR) An automatic reset
occurs after the designated unoccupied
zone heat setpoint input returns to its
allowable range for 10 continuous
seconds, or after the user defines a
different, valid unoccupied zone heating
setpoint selection source.
Reset Required: (PAR) An automatic reset
occurs after the designated space pressure
transducer sends a signal within range for
10 continuous seconds.
UCM Reaction: A fail-safe function in the HI
will cause the following sequence:
a. disallow any interaction between the HI
and the RTM (or any other modules),
b. render all HI keystrokes ineffective
c. cause the following message to display
on the unit-mounted HI display: “Local
HI communications loss. Check comm
link wiring between modules.” If the unit
has a remote HI option, then this
VOM Communications Failure
Problem: The RTM has lost communication
with the VCM.
V
VCM Communication Failure
Problem: The RTM has lost
communication with the VCM.
Check: Field/unit wiring between RTM and
VCM.
diagnostic will display as any other
automatic reset diagnostic.
Reason for Diagnostic: The RTM has lost
communications with the VOM.
Verify: Check field/unit wiring between
RTM and VCM.
Reset Required: (INFO) An automatic reset
occurs after communication is restored
between the RTM and the HI. When the
failure screen clears, the general display
restores to allow the HI to interact with the
RTM again.
UCM Reaction:Ventilation override actions
will not be allowed, and the VO Output
relay will be deenergized.
Reason for Diagnostic: The RTM has lost
communication with the VCM.
UCM Reaction: All active commands and
setpoints provided by the VCM are
canceled and/or ignored. A fail-safe
function in the VCM will cause all outputs
to deenergize and/or set to zero. The
outside air damper minimum position
function will revert to using the O/A flow
compensation function if O/A flow
compensation is enabled or set to the
default minimum position function if O/A
flow compensation is disabled or not
available.
Reset Required: (PAR) An automatic reset
occurs after communication has been
restored.
Unoccupied Zone Cool Setpoint Failure
Problem: The unoccupied zone cooling
setpoint input is out of range.
Reason for Diagnostic: The input
designated as the unoccupied zone cooling
setpoint source is out of range (temp <
45°F or temp > 94°F).
W
WSM Communications Fail
Problem: The RTM has lost communication
with the WSM.
Check: Field/unit wiring between RTM and
WSM.
UCM Reaction: The active unoccupied
zone cooling setpoint reverts to the default
value.
Reset Required: (PAR) An automatic reset
occurs after communication is restored.
communications with the VOM.
Reason for Diagnostic: The RTM has lost
communication with the WSM.
UCM Reaction: The UCM will react as if a
freezestat has occurred by issuing:
• An “all heat on” or “mod output full
open” request to “heat control”
Reset Required: (PAR) An automatic reset
occurs after the designated unoccupied
zone cool setpoint input returns to its
allowable range for 10 continuous
seconds, or after the user defines a
Velocity Pressure Sensor Failure
Problem: The velocity pressure input
signal is out of range.
112
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
diagnostics
2. continuously for five minutes while:
·water side economizer is open 100%,
· presetting of a head pressure valve, or
· demand for mechanical cooling.
Unit must be: a. configured with water
cooled condenser and/or water
economizer and b. have water flow
switch installed.
c.Time to React: immediate
• A “fan off” request to “supply fan
control”
• A “close damper” request to
“economizer actuator control”
• The water pump to turn on and position
all water valves to provide maximum
flow through all water source heat
exchangers
• Disables preheat function if WSM mixed
air temp sensor is selected as preheat
sensor
e. Actions to be Initiated: A “lockout all
ckts” request is issued to the
“compressor staging function”
f. Reset: An automatic reset occurs after
the water flow input returns to within
range continuously for 3 seconds, the
water pump is requested OFF, or the
water flow switch becomes not installed.
Reset Required: An automatic reset
occurs after one complete set of IPC
packets is received.
WSM Mixed AirTemp Sensor Fail
b. Activation Conditions: temperature <
-50°F or temperature > 209°F, and sensor
is selected for use by “waterside
economizer temperature enable
Z
Zone Cool Setpoint Failure
Problem: The occupied zone cooling
setpoint is out of range.
function” or “preheat function”
c.Time to React: 10 sec <T < 20 sec
e. Actions to be Initiated: “waterside
economizer temperature enable
Reason for Diagnostic: The input
designated as occupied zone cooling
setpoint source is out of range (temp. <
45°F or temp > 94°F).
function” uses supply air cooling setpoint
instead of mixed air temperature. If xixed
air temperature is used for “preheat
function”, issue a “disable” request to
“preheat function”.
f. Reset: An automatic reset occurs after
the mixed air temp. input returns to
within range continuously for 10 seconds.
UCM Reaction: The active occupied zone
cooling setpoint reverts to the default
occupied zone cooling setpoint.
Reset Required: (PAR) an automatic reset
occurs after the designated occupied
zone CSP input returns to its allowable
range for 10 continuous seconds, or after
a different valid occupied zone CSP
selection source is user-defined.
Water Flow Fail
a. Data used (module,packet,byte,bit):
WSM, 01,19, 05
b. Activation Conditions: The water flow
input is detected open ;
1. at the end of precool water flow
initiation state, or
SCXG-SVX01B-EN
113
Download from Www.Somanuals.com. All Manuals Search And Download.
114
SCXG-SVX01B-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
SCXG-SVX01B-EN
115
Download from Www.Somanuals.com. All Manuals Search And Download.
Literature Order Number
Date
SCXG-SVX01B-EN
March 2008
Supersedes
SCXG-SVX01B-EN July 2000
www.trane.com
For more information, contact your localTrane
office or e-mail us at [email protected]
Trane has a policy of continuous product and product data improvement and reserves the right to change
design and specifications without notice.
Download from Www.Somanuals.com. All Manuals Search And Download.
|