TOSHIBA 4200FA UPS
Installation Planning Guide for 15-80kVA UPS
Standard System: 208/120V Input, 208/120V Output
General Mechanical Information
Dimensions
(W x D x H)
Weight
Approximate Full-Load Heat Loss
UPS kVA/ kW Rating
Inches
Lbs.
kBtu/Hr
15 kVA/12 kW
25 kVA/ 20 kW
30 kVA/ 24 kW
50 kVA/ 40 kW
80 kVA/ 64 kW
20 x 36.25 x 59.85
20 x 36.25 x 59.85
20 x 36.25 x 59.85
35.59 x 38.19 x 59.39
44 x 31 x 74
900
910
915
2,548
1,560
5.7
7.6
9.1
17.7
40.0
Primary AC Input (208/120V 3-Phase / 4-Wire)
Maximum Input Power
Demand
Suggested External
Overcurrent Protection
Suggested Minimum Feeder
Wire Size Per Phase / Neutral For Min. Wire Size in Steel Conduit
Suggested Maximum Feeder Length
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
(1) x 8 / (1) x 6
(1) x 4 / (1) x 2
(1) x 3 / (1) x 1
(1) x 1/0 / (1) 4/0
(1) x 300 / (1) x 500
Feet
15
25
30
50
80
>0.97
>0.97
>0.97
>0.97 152.6
>0.97 244.3
45.7
76.3
92.4
60 AT
90 AT
125 AT
200 AT
300 AT
380
380
380
380
380
Optional Alternate AC Input (208/120V 3-Phase / 4-Wire)
Maximum Input Power
Suggested External
Suggested Minimum Feeder
Suggested Maximum Feeder Length
Demand
Overcurrent Protection
Wire Size Per Phase / Neutral For Min. Wire Size in Steel Conduit
kVA
15
25
30
50
80
PF
Amps
41.6
69.4
83.3
Amps
AWG at 75º C Temp. Rating
(1) x 8 / (1) x 6
(1) x 4 / (1) x 2
(1) x 3 / (1) x 1
(1) x 1/0 / (1) 4/0
(1) x 4/0 / (1) x 400
Feet
>0.97
>0.97
>0.97
>0.97 138.8
>0.97 222.1
60 AT
90 AT
110 AT
175 AT
300 AT
380
380
380
380
380
Battery Input (288VDC Nominal)
Battery Capacity Required Maximum Discharge
Suggested External
Overcurrent Protection
Suggested Minimum Feeder
Wire Size Per Phase
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
for Full Load Output
at Full Load Output
kWB
Amps DC
Amps
AWG or kcmil at 75º C Temp. Rating
Feet
70
70
70
70
70
15
25
30
50
80
13.33
22.22
26.67
44.44
71.11
61.7
102.8
123.0
205.7
90 AT
(1) x 6
(1) x 2
(1) x 1
(1) x 4/0
125 AT
175 AT
225 AT
400 AT
329.2
(2) x 3/0
AC Output (208/120V 3-Phase / 4-Wire)
Suggested External
Overcurrent Protection
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
Rated Output Power
kVA
PF
Amps
Amps
AWG or kcmil at 75º C Temp. Rating
Feet
15
25
30
50
80
0.8
0.8
0.8
0.8
0.8
41.6
69.4
83.3
138.8
222.1
60 AT
90 AT
110 AT
175 AT
300 AT
(1) x 8 / (1) x 6
(1) x 4 / (1) x 2
(1) x 3 / (1) x 1
(1) x 1/0 / (1) 4/0
(1) x 4/0 / (1) x 400
380
380
380
380
380
Rev. 1.03
Page 1 of 2
4200FA-IPG-208v
Download from Www.Somanuals.com. All Manuals Search And Download.
|